AMERICAN Ductile Iron Pipe

ANSI/AWWA C150/A21.50
and
ANSI/AWWA C151/A21.51
Standard Pressure Classes Wall Thickness and Nominal Wall Thickness

Table No. 3-8


Pressure Class
Outside
Size Diameter 150 200 250 300 350
in. in.
Nominal Thickness in Inches
4 4.80 - - - - 0.25
6 6.90 - - - - 0.25
8 9.05 - - - - 0.25
10 11.10 - - - - 0.26
12 13.20 - - - - 0.28
14 15.30 - - 0.28 0.30 0.31
16 17.40 - - 0.30 0.32 0.34
18 19.50 - - 0.31 0.34 0.36
20 21.60 - - 0.33 0.36 0.38
24 25.80 - 0.33 0.37 0.40 0.43
30 32.00 0.34 0.38 0.42 0.45 0.49
36 38.30 0.38 0.42 0.47 0.51 0.56
42 44.50 0.41 0.47 0.52 0.57 0.63
48 50.80 0.46 0.52 0.58 0.64 0.70
54 57.56 0.51 0.58 0.65 0.72 0.79
60 61.61 0.54 0.61 0.68 0.76 0.83
64 65.67 0.56 0.64 0.72 0.80 0.87
Pressure classes are defined as the rated water working pressure of the pipe in psi. The thicknesses shown are ade-
quate for the rated water working pressure plus a surge allowance of 100 psi. Calculations result in net thicknesses and
are based on a minimum yield strength in tension of 42,000 psi and 2.0 safety factor times the sum of working pressure
and 100 psi surge allowance.
Thickness can be calculated for rated water working pressure and surges other than the above by use of equation 1 in
ANSI/AWWA C150/A21.50.
AMERICAN Ductile Iron pipe is available for water working pressures greater than 350 psi. Check AMERICAN for details.
These are standard pressure classes as given in AWWA C150 and C151. AMERICAN can furnish any thickness in
between these standard thicknesses if deemed economical for major projects.
AMERICAN Ductile Iron pipe is also available with thicknesses greater than Pressure Class 350. For special applica-
tions, contact AMERICAN.