Rectificadores Controlados
Rectificadores Controlados
Rectificadores Controlados
N T S R G1 K1 G2 K2 G3 K3 G4 K4 G5 K5 G6 K6
SEMICODE
ELECTRONICA
®
PWR
SC6006
LCD CONTRAST
FIRING
FAULT
OV CURR
EXT BLK
MENU OK
RESET
COARSE FINE
SC6006
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
130320 Rev.:2.4
Index of contents
1 GENERAL.................................................................................................................................................... 4
1.1 Special Features................................................................................................................................... 4
1.2 Warranty............................................................................................................................................... 4
2 SAFETY INSTRUCTIONS............................................................................................................................ 5
2.1 Operator and personnel requirements.................................................................................................. 5
2.2 Proper and intended use...................................................................................................................... 5
2.3 Use and operation of the device........................................................................................................... 5
3 FUNCTIONS................................................................................................................................................. 6
3.1 Topology configuration.......................................................................................................................... 6
3.2 Operating modes.................................................................................................................................. 6
3.3 Setpoint signals processing.................................................................................................................. 9
3.3.1 Analog or digital references / setpoints.........................................................................................9
3.3.2 Setpoints signal processing diagrams.......................................................................................... 9
3.4 Feedback signals processing.............................................................................................................. 11
3.5 Setpoints and feedback live input signals configuration.....................................................................12
3.6 Control Modes.................................................................................................................................... 12
3.7 Soft power ON and soft power OFF................................................................................................... 13
3.8 Fault sources and pulse inhibition...................................................................................................... 14
3.9 Start up mode..................................................................................................................................... 15
3.10 Autoset function................................................................................................................................ 15
3.11 Output assignation option................................................................................................................. 16
3.12 Saving all the changes and configurations.......................................................................................16
3.13 Restore default configurations.......................................................................................................... 16
4 SETTINGS AND OPERATION................................................................................................................... 17
4.1 PCB connectors overview................................................................................................................... 17
4.2 Connectors......................................................................................................................................... 18
4.2.1 Power supply connector (J1)...................................................................................................... 18
4.2.2 Synchronism connector (J11)..................................................................................................... 18
4.2.3 Feedback voltage signal connector (J12)...................................................................................19
4.2.4 External block and dry output fault connector (J13)....................................................................19
4.2.5 Current input feedback connector (J14).....................................................................................20
4.2.6 Setpoints and inhibit connector (J15)......................................................................................... 21
4.2.7 Feedback and alpha setpoint input connector (J16)...................................................................22
4.2.8 Output SCR firing connectors (SCR1-SCR6).............................................................................23
4.2.9 Serial communications DB-9 connector (J32).............................................................................23
4.3 LCD menu settings and navigation..................................................................................................... 24
4.3.1 Main Menu:................................................................................................................................. 24
4.3.1.1 LCD contrast adjusting potentiometer................................................................................25
4.3.1.2 LCD backlight..................................................................................................................... 25
4.3.2 Settings menu............................................................................................................................. 25
4.3.2.1 Topology option.................................................................................................................. 25
4.3.2.2 Mode option........................................................................................................................ 26
4.3.2.3 Reference submenu........................................................................................................... 26
4.3.2.4 Live-zero input submenu.................................................................................................... 26
4.3.2.5 Control option..................................................................................................................... 26
4.3.2.6 Soft ON/OFF ramps submenu............................................................................................ 26
4.3.2.7 Faults submenu.................................................................................................................. 27
4.3.2.8 Start up option.................................................................................................................... 27
4.3.2.9 Autoset options submenu................................................................................................... 28
4.3.2.10 Outputs assignation submenu.......................................................................................... 28
4.3.2.11 Communications submenu............................................................................................... 28
4.3.2.12 Save changes option........................................................................................................ 28
4.3.2.13 Restore option.................................................................................................................. 29
4.3.3 Registers menu.......................................................................................................................... 29
4.3.4 Debug menu............................................................................................................................... 30
4.4 Jumpers and DIP Switches configurations......................................................................................... 30
2
4.4.1 Jumpers J7 and J20 to J24........................................................................................................ 30
4.4.2 DIP Switches.............................................................................................................................. 31
4.4.3 Setting the gain for direct voltage feedback input.......................................................................32
4.5 LED Indications.................................................................................................................................. 32
5 SERIAL COMMUNICATION....................................................................................................................... 33
5.1 Overview available command set....................................................................................................... 34
5.2 Query instruction set........................................................................................................................... 34
5.2.1 “?ver” query version command................................................................................................... 34
5.2.2 “?S” query status register........................................................................................................... 34
5.2.3 “?A” query alpha register............................................................................................................ 34
5.2.4 “?U” query voltage register......................................................................................................... 34
5.2.5 “?I” query current register........................................................................................................... 34
5.3 Signal instruction set.......................................................................................................................... 34
5.3.1 “*OK” signal command............................................................................................................... 35
5.3.2 “*MENU” signal command.......................................................................................................... 35
5.3.3 “*UP” signal command................................................................................................................ 35
5.3.4 “*DW” signal command............................................................................................................... 35
5.3.5 “*RMT” signal command............................................................................................................. 35
5.3.6 “*ECHO” signal command.......................................................................................................... 35
5.3.7 “*HOME” signal command.......................................................................................................... 35
5.3.8 “*RST” signal command............................................................................................................. 35
5.3.9 “*SV” signal command................................................................................................................ 35
5.4 Memory read instruction..................................................................................................................... 36
5.5 Memory write instruction..................................................................................................................... 36
6 INTERNAL MEMORY AND REGISTERS................................................................................................... 37
6.1 Readable registers............................................................................................................................. 37
6.1.1 status registers........................................................................................................................... 37
6.1.2 p_status registers....................................................................................................................... 38
6.2 Writable registers................................................................................................................................ 40
7 INSTALLATION........................................................................................................................................... 41
7.1 Typical application circuits.................................................................................................................. 41
7.2 Control AC/AC applications................................................................................................................ 41
7.2.1 W3C topology connection example............................................................................................ 41
7.2.2 W3C current and voltage feedback scheme...............................................................................42
7.2.3 Load connection types for W3C scheme....................................................................................42
7.2.4 M6CK and M3.2CK schemes of connection...............................................................................43
7.3 Control AC/DC applications. B6C scheme.......................................................................................... 44
7.3.1 B6C topology connection example............................................................................................. 44
7.3.2 DC current sense feedback using a shunt..................................................................................44
7.3.3 Feedback using a current and voltage isolated sensors.............................................................45
7.4 Direct drive mode with block signal.................................................................................................... 46
7.5 Mounting recommendations............................................................................................................... 48
7.5.1 General mounting recommendations.......................................................................................... 48
7.5.2 Recommended start up procedure............................................................................................. 48
7.5.3 Notes about the control card in systems controlled by microcontrollers or PLC.........................49
8 AVAILABLE ACCESSORIES...................................................................................................................... 50
8.1 SCRP6006.......................................................................................................................................... 50
8.1.1 Interfacing SC6006 with remote panel SCRP6006.....................................................................50
8.2 SCGI24............................................................................................................................................... 51
8.2.1 Galvanically isolated current loop with shunt using SCGI24.......................................................51
8.3 SCST700............................................................................................................................................ 52
8.3.1 Obtaining a neutral reference using SCST700 for improved synchronism aquisition.................52
9 FIRMWARE REVISIONS............................................................................................................................ 53
10 TECHNICAL SPECIFICATIONS............................................................................................................... 54
10.1 Mechanical dimensions.................................................................................................................... 58
10.2 Connectors overview........................................................................................................................ 58
3
1 GENERAL
These operation instructions describe the configuration and functions of the SC6006 and are designed to
enable qualified personnel to perform the planning, commissioning and maintenance of this equipment.
These operation instructions comply with the current technical specifications of the device at the time of
publication. The contents do not constitute a subject matter of the contract, but serve for information
purposes only.
We reserve the right to alter any specification given in these operating instructions, especially with regard to
technical data and operation. SEMICODE reserves the right to make modifications with regard to the content
and technical data in these operation instructions.
Versatility and ruggedness are the main features of SC6006 providing a lot of regulation options and a great
performance in many different applications and environments.
SC6006 is designed to adapt to most common rectification and control schemes, like W3C, B6C, M6C and
M3.2C. Optionally can also be applied to W3H, B6H and M3C. The power adjustment can be made by
current or voltage through potentiometers or by external analog signals. SC6006 also has protection against
current peaks, soft start up ramp, inhibit input by external relay, possibility of a shunt terminal + or -, current
transformer direct input, etc.
The SC6006 is also a communication-capable thyristor power controller. It can be used wherever alternating
voltages, alternating currents or outputs in thermal process technology e.g. need to be controlled. Main
applications for this circuit are those where is needed a safe control for large currents through thyristors, for
example thermal process, surfaced treatments, electrolytic process, ovens, lightning, etc.
1.2 Warranty
In the event of any claims in connection with the SC6006, please contact us quoting:
• Fabrication number / serial number.
• Reason for the complaint.
• Environmental conditions of the device.
• Operating mode.
• Period of use.
Goods and services are subject to the general conditions of supply for products of the electrical industry, and our general sales
conditions.
Claims in connection with supplied goods must be submitted within one week of receip, along with the delivery note. SEMICODE Will
rescind all obligations such as warranty agreements, service contacts, etc. entered into by SEMICODE Or its representatives without
prior notice if maintenance and repair work is carried out using anything other than original SEMICODE spare parts or spare parts
purchased from SEMICODE
4
2 SAFETY INSTRUCTIONS
The safety instructions and operating manual are to be carefully read prior to installation and
commissioning
5
3 FUNCTIONS
In order to adapt as best as possible to a wide range of applications SC6006 has numerous functions which
had to be properly configured before its use along with a SCR power stack. All the functions available and its
proper configuration are described in the following chapter.
0%
time
PSA
waveform
time
6
- Full wave switch mode (FWS)
In FWS operating mode, the mains voltage is switched periodically firing in burst packets of AC waves,
relative to the defined setpoint. Integer multiples of the mains periods are switched to avoid D.C.
components. The operating mode full wave switch principle FWS is particularly suited for loads with a high
thermal inertia.
This mode only works along with alpha set input J15[p12]-ALPHA_INP or D_ALPHA_REG[M011] software
register in open loop and switches packets of 100 semi periods in the zero-cross of the mains, proportionally
to the value of alpha set.
In figure 2 is shown a FWS waveform example according the alpha setpoint. In this image and for sake of
simplicity the wave packets are of 5 periods.
alpha
setpoint
100%
0%
time
FWS
waveform
time
When using this mode it is also possible to define a number of periods in which PSA will be applied as an
initializing slope on each packet. Please read a more detailed description of this option on chapter 3.7 -Soft
power ON and soft power OFF.
Using all 6 firing outputs it is possible to implement up to 3 static relays driving an antiparallel SCR power
scheme each. There are available 3 different static relays (one for each phase.) You can configure which
outputs will fire. This mode works as a switch controller for 3 static relays with a W3C topology or as 3
independent static relay firing W1C.
7
Working as a relay mode the inputs voltage setpoint (J15[p15]-U_SETPOINT), current setpoint (J15[p14]-
I_SETPOINT) and alpha setpoint (J16[p21]-ALPHA_INP) works as digital triggering inputs (according to its
configuration: TTL, 0-10 V, 0-20 mA or 4-20mA) and firing the outputs SCR1 & SCR2, SCR3 & SCR4, SCR5
& SCR6 respectively.
System mode of operation can be configured by software, please refer to chapter 4.3.2.2 on page 26 for a
more detailed explanation.
8
3.3 Setpoint signals processing
There are 3 different analog input setpoints available: voltage setpoint (J15[p15]-U_SETPOINT), current
setpoint (J15[p14]-I_SETPOINT) and alpha setpoint (J16[p21]-ALPHA_INP ), this signals works as external
references which should be provided by the operator or PLC to the controller (SC6006) giving the
corresponding setpoint when regulating the ouptut voltage of the converter, the output current of the
converter or the firing phase angle of the converter respectively.
As mentioned before all these input setpoint signals can be configured to work as 0-5 V or 0-10 V and also
0-20 mA and live input 4-20 mA. This configurations are made using the PCB DIP switches and LCD screen.
Furthermore all this inputs can be digitally overrode. There are 3 software setpoint registers which can be set
by the operator through LCD and push-buttons on board or by using the serial communication port.
Please refer to chapter 5-SERIAL COMMUNICATION for further explanation regarding the communications
interface and communications protocol of the system if it is needed to change this registers remotely.
If an input reference is set as analog the corresponding value is obtained by his assigned PCB input:
alpha_setpoint: J16[p21]-ALPHA_INP
u_setpoint: J15[p15]-U_SETPOINT
i_setpoint: J15[p14]-I_SETPOINT
Note:
All analog setpoint input signals can be configured to work as 0-5 V or 0-10 V and also 0-20 mA. Additionally they can be
interfaced connecting a potentiometer (2 included). The recommended value of this potentiometers is 4.7 kΩ.
Configuration are made using the PCB DIP switches. Please refer to chapter 4.4.2 on page 31 for the DIP-switches
configurations.
Also all inputs can be configured as 4-20 mA (Live Input). The Live Input is enabled through software. Please refer to
chapter 4.3.2.4 on page 26.
9
Alpha setpoint signal processing.
In figure 4 is shown the diagram for acquisition and setting of alpha setpoint.
ALPHA_INP
0
J16 21 ADC
0-5V / 0-20mA ALPHA_REG[M005]
U13-A 0-5V / 0-10V : U13-B
J16 18 0-20/4-20mA : Live inp. D_ALPHA_REG[M011] 1
By default SC6006 takes the alpha setpoint from the analog ALPHA_INP input configured as 0-5 V DC.
U_SETPOINT
0
J15 15 ADC
0-5V / 0-20mA U_REF_REG[M008]
U11-C 0-5V / 0-10V : U11-D
0-20/4-20mA : Live inp. D_UREF_REG[M012] 1
J15 13
By default SC6006 takes the voltage setpoint from the analog U_SETPOINT input configured as 0-5 V DC.
I_SETPOINT
0
J15 14 ADC
0-5V / 0-20mA I_REF_REG[M009]
U11-A 0-5V / 0-10V : U11-B
0-20/4-20mA : Live inp. D_IREF_REG[M013] 1
J15 13
By default SC6006 takes the current setpoint from the analog I_SETPOINT input configured as 0-5 V DC.
10
3.4 Feedback signals processing
SC6006 have 2 independent feedback signals: current feedback signal and voltage feedback signal. This
signals are used when a closed loop control is needed.
As on the previous chapter, following, simplified diagrams are provided regarding the different sources of
feedback signals available with the aim of clarify the way this feedback signals are processed and routed or
selected by SC6006.
I_SHUNT
J15 14
0-60 mV
J15 13 J21
J22
I_AUX
J14 09 ADC IMEAS_REG[M007]
J14 10
J14 11
I_SENS
J16 19
0-5V / 0-20mA
U11-A 0-5V / 0-10V : U11-B
0-20/4-20mA : Live inp.
J16 18
The operator must choose and configure which source for current and voltage feedback signal wants to work
with according the application, the configuration of current feedback signal processing, filters and selection
or routing is as shown in figure 7.
By default SC6006 takes the current feedback signal from the analog I_SENS input configured as 0-5 V
signal.
11
Voltage feedback signal processing.
The voltage feedback signal can be obtained with direct output voltage connection (J12[p1]-V_REAL) or with
an analog (0-5 V or 0-10 V and also 0-20 mA or 4-20 mA) voltage signal ( J16[p20]-U_SENS). The operator
must ensure and configure which source for voltage feedback signal wants to be used in his application as
shown in figure 8.
R01
U_REAL
J12 01
0-700 VDC
J12 02 J20
ADC UMEAS_REG[M006]
U_SENS
J16 20
0-5V / 0-20mA
U11-C 0-5V / 0-10V : U11-D
J16 18 0-20/4-20mA : Live inp.
By default SC6006 takes the voltage feedback signal from the analog U_SENS input configured as 0-5 V.
12
3.7 Soft power ON and soft power OFF
• Soft init slope and soft turn off slope for phase-shift mode (PSA)
When working in PSA mode SC6006 can operate making a soft power ON and soft power OFF. When soft
power ON is set and the unit is started, the phase delay will be gradually decreased until it reaches the
setpoint. The soft power ON time can also be set by software.
Same way, when soft power off is set and the unit is being stop, the phase delay will be gradually increased
from the actual setpoint until it reaches the off state.
In the image is shown a soft power on from 0 to 100%.
alpha
setpoint
100%
0%
time
PSA
waveform
time
The power on and the power off times can be set by software varying from 1 to 30 seconds, how to set the
soft power on and off and the timings is further explained in chapter 4.3.2.6 on page 26.
• Soft init slope and soft turn off slope for proportional mode (FWS). Avoiding transformer
inrush current.
It is recommended to use this configuration in order to reduce the inrush current when controlling a
transformer primary driving resistive loads on its secondary on proportional mode. When a transformer is
first energized a high transient current can flow for several cycles due core saturation. Usually the worst
case inrush happens when the primary winding is connected at an instant around the zero-crossing of the
primary voltage as it occurs every starting period on each mains wave packet when operating in FWS mode.
The inrush current is greater than the nominal operating current of transformer and the ratio can vary from a
few percent up to many times the operating current, this can blow up fuses and trip circuit breaker it also
causes causes harmonics which can excite system resonances and cause dynamic overvoltage, all this
effects may lead to the breakdown of the power equipment.
figure 10: Pulse train example with a soft init on FWS mode.
In many cases a single period (1 st period of the pulse train) fired at 90º will suffice to reduce to its minimum
the inrush peak. In other cases a specific number periods of soft on would reduce at its maximum the initial
inrush current. A recommendation would be to initially set a single cycle of soft turn on, monitorize the initial
peak current and compare it with different number of cycles and select the most suitable for the application.
On figure 10 is depicted as example the initial transient on each packet working with FWS with 5 cycles of
PSA soft init. In this image and for sake of simplicity the wave packets are of 7 periods.
You can find more information regarding the procedure to configure SC6006 to operate with this firing mode
in chapter 4.3.2.6 Soft ON/OFF ramps submenu on page 26 of this manual.
13
3.8 Fault sources and pulse inhibition
When the system is in ON state, the output pulse inhibition it is produced when an enabled fault source in
working condition occurs.
There are 3 different sources that triggers a fault: incorrect mains sync or rotation, external blocking signal
through an external logic inhibit signal or contact block signal and overcurrrent condition.
All this fault conditions can be masked through software or some of them modified. The triggering of fault
signal is made as it is shown in diagram on figure 11.
Sync signal: When unmasked, it is triggered when the phase rotation of mains is reversed than the
configured one or triggered when mains is out of sync, for example by its disconnection or by the
disconnection or out of phasing of one of its phases.
Halt signal: When unmasked, it is triggered when inhibition input (J15[p16]-INHIBIT) or block input (J13[p6]-
BLK) switches on activation state given by signals en_inh and en_ext_blq set by software (chapter 4.3.2.7
on page 27).
OvCurr signal: When unmasked, it is triggered when the measured feedback current exceeds the maximum
set by OV_CURRENT_REG[M036].
EN_SYNC sync_bit
SYNC
EN_INH EN_FAULT
EN_HALT
INH
halt_bit FAULT
EN_EXT_BLQ
BLQ
When any of this 3 fault signals is triggered and fault generation is enabled, a fault condition will occur and
will stop (if it is in working state) the system and set the fault fault flags, those are visible in main menu of on-
board display and with signaling LEDs.
The fault condition will be reset when all fault signals returns to OFF state. Then the system can be triggered
ON again or, if it is set this way, it will resume its previous operation mode.
Fault interlock
SC6006 can interlock a fault condition by using its interlock function. When fault interlock mode is enabled
(see chapter 4.3.2.7 in page 27.) any fault signal will stop the firing mode, and the system will not resume its
previous working and release the fault state mode until all the fault sources are deactivated again and the
system put on OFF state by pressing [OK] push-button on the main menu.
14
3.9 Start up mode
Using the start up setting SC6006 can be configured to, when powered on, start in ON mode, OFF mode or
remembering the last state before it was powered down. By default the unit is configured to start up with the
last system state. This option is software set (chapter 4.3.2.8 on page 27).
Autoset function SC6006 automatically checks the mains frequency mode, the SCR output assignation and
the phase rotation. By default Autoset function is executed automatically every SC6006 startup, but user can
mask or unmask which properties will set up this function. All its options can be software configured. Also,
Autoset function can be triggered by software in any moment with no need to turn on and off the system. See
chapter 4.3.2.9 on page 28.
Note:
When powered on, SC6006 automatically starts the autoset function before initialize all the system. So, in order to work
properly all the power system must be connected and powered on at the same time or before power on the SC6006.
Otherwise the Autoset function would be unable to determine the frequency of mains or rotation or output assignation
and will be configured in a default mode or with the previous detected configuration.
15
If the operator wants to use this option SC6006 must be connected to a resistive load in B6C scheme, and in
a delta or wye resistive load in W3C. It is also recommended to connect the neutral.
In some cases outputs autoset may be unable to find the correct outputs assignation and, by default will
disable all the outputs (0). The user can override the automatic configuration by manually setting up the
output assignation.
SCRs output assignation option can be disabled and configured by software:
SUBMENU 1.8: AUTOSET > Outputs > [No/Auto]
By default outputs autoset is disabled. Can be useful to use this function when installing the power stack the
first time to get a quick and easy configuration and, then, save the configuration and disabling the outputs
autoset mode.
If the automatic outputs detection in autoset is enabled but during the autoset process the system cannot
determine it, the outputs assignation will be the same as the last time was saved in EEPROM.
Note:
The SCRs automatic assignation option works only for W3C and B6C schemes with resistive loads. For other topologies
the user must leave disabled the outputs autoset option and configure the system according the SCRs connection
scheme through SUBMENU 1.9: OUTPUTS.
Note:
Remember to save the configurations to the internal EEPROM every time a change is made or all the changes will be
lost when system is powered off.
16
4 SETTINGS AND OPERATION
In this chapter is given a complete device overview, with a description of all available input/output signals
and connections available and a brief description of all software options and on-board hardware
configurations made by jumpers and DIP-switches.
N T S R G1 K1 G2 K2 G3 K3 G4 K4 G5 K5 G6 K6
SEMICODE
ELECTRONICA
®
PWR
SC6006
LCD CONTRAST
FIRING
SIGNALING LEDS
FAULT
OV CURR
EXT BLK
MENU OK
RESET
COARSE FINE
SC6006
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
J1 - POWER J12 - FEEDBACK J13 - EXTERNAL BLOCK J14 - CURRENT J15 - SETPOINTS J16 - FEEDBACK AND
SUPPLY VOLTAGE AND DRY OUTPUT FAULT INPUT FEEDBACK AND INHIBIT ALPHA SETPOINT
17
4.2 Connectors
Following is listed and described every connector and every output/input signal available of the SC6006.
J1
figure 13: Detail of mains supply input connector.
The connector type is a MSTBVA series (or equivalent) from Phoenix Contact (ref. MSTBVA2,5/3-G-5,08).
The board is also provided with the matching plug connector (ref. MSTB2,5/3-ST-5,08).
J11
figure 14: Detail of sync input connector.
The connector type is an MSTBA series (or equivalent) from Phoenix Contact (ref. MSTBA 2,5/7-G-5,08).
The board is also provided with the matching plug connector (ref. MSTB 2,5/7-ST-5,08).
18
4.2.3 Feedback voltage signal connector (J12)
Direct voltage feedback input is made on J12 connector. Please note that in those cases where control
board is controlled by external equipments, like PLC, microcontrollers, etc, without isolated outputs, it must
be considered to have all the feedback elements isolated. Using elements like shunts to close the current
loop, and voltage feedback could not be done directly if galvanic isolation is required.
There are available isolated feedback modules designed to work with this control board. Please see chapter
8 -AVAILABLE ACCESSORIES on page 50 for a list and explanation of suitable accessories for SC6006.
- J12 PINOUT:
• Terminal 1 (V_REAL): Direct voltage input feedback signal.
• Terminal 2 (GND): PCB signal ground.
J12
The connector type is an MSTBVA series (or equivalent) from Phoenix Contact (ref. MSTBVA2,5/3-G-5,08).
The board is also provided with the matching plug connector (ref. MSTB2,5/3-ST-5,08).
- J13 PINOUT:
• Terminal 3 (K_NC): Output dry relay N/C contact.
• Terminal 4 (K_COM): Output dry relay COM contact.
• Terminal 5 (K_NO): Output dry relay N/O contact.
• Terminal 6 (BLQ): Input terminal of the blocking signal.
• Terminal 7 (VDD): Positive terminal blocking signal (15 VDC).(*) J13
(*) please do not use this terminal to power other external devices. Refer to ELECTRICAL CHARACTERISTICS TABLE for further
information.
Terminal 6 (BLQ) must be shortcircuited with Terminal 7 (VDD) for trigger ON the input blocking signal.
Terminals 3-5 are those corresponding to the dry output fault relay. Relay switches ON (Terminal 4
connected with Terminal 5) when fault occurs. Otherwise, if there is no fault, relay switchs OFF (Terminal 4
connected with Terminal 3). Please see the connection diagram for J13 in figure 15.
output fault
signaling relay
K1
2 3 4 5 6 7 8 9
external block
switch
19
The J13 connector type is an MCV series (or equivalent) from Phoenix Contact (ref. 1803442). SC6006 is
also provided with the matching plug connector (ref. 1803604).
Note:
By default SC6006 is configured to operate with a normally-off blocking contactor. To work without the blocking mode or
with a normally-on contact you must set this option through software. Please see chapter 4.3.2.7 in page 27.
- J14 PINOUT:
• Terminal 8 (GND): Ground connection
• Terminal 9 (AUX_I_R): R phase input for auxiliary CT feedback.
• Terminal 10 (AUX_I_S): S phase input for auxiliary CT feedback.
• Terminal 11 (AUX_I_T): T phase input for auxiliary CT feedback.
• Terminal 12 (I_SHUNT): Shunt input terminal.
J14
U_SENS
6 7 8 9 10 11 12
I_R
I_S
I_T
current
sensors
figure 16: Connection diagram example for J14.
The J14 connector type is an MCV series (or equivalent) from Phoenix Contact (ref. 1803442). The board is
also provided with the matching plug connector (ref. 1803604).
Note:
Auxiliary feedback uses the signal from a current transformer (200 mA output), in order to be able to regulate AC
currents. Below are indicated our recommended current transformers:
Current Transformers
TTS017 25-50-100A/0.2A Input current: 25, 50 or 100 A
TTS040 200-300-400/0.2A Input current: 200, 300 or 400 A
TTS040 600/0.2A Input current: 600 A
20
4.2.6 Setpoints and inhibit connector (J15)
Voltage and current setpoints and inhibit signal are interfaced with this connector. It also provides a 5 V
reference in case setpoint potentiometers are used.
- J15 PINOUT:
• Terminal 13 (GND): Negative terminal from the regulator
potentiometers or GND reference.
• Terminal 14 (I_SETPOINT): Adjustment terminal from the current
regulator potentiometer or current setpoint input.
• Terminal 15 (U_SETPOINT): Adjustment terminal from the voltage
regulator potentiometer or voltage setpoint input. J15
(*) please do not use this terminal to power other external devices. Refer to ELECTRICAL CHARACTERISTICS TABLE for further
information.
The J15 connector type is an MCV series (or equivalent) from Phoenix Contact (ref. 1803442). The board is
also provided with the matching plug connector (ref. 1803604).
11 12 13 14 15 16 17
Notes:
- Inputs can be driven by potentiometers. This potentiometers can be any type, but with a recommended value of 4.7 kΩ.
- When the adjustment cursor of the potentiometer is situated to the positive side, the supplying voltage is at the
maximum level.
- It is also possible to control the inputs with 0-5 V, 0-10 V, 0-20 mA or 4-20 mA signals applied to the adjustment
terminals (referred to ground).
21
4.2.7 Feedback and alpha setpoint input connector (J16)
Voltage and current feedback signals and alpha setpoint signal are interfaced with this connector.
- J16 PINOUT:
• Terminal 18 (GND): Negative terminal from the regulator
potentiometers or GND reference.
• Terminal 19 (I_SENS): Current feedback signal input.
• Terminal 20 (U_SENS): Voltage feedback signal input.
• Terminal 21 (ALPHA_INP): Alpha reference input.
• Terminal 22 (VDD): Positive terminal from 15 V reference(*). J16
(*) please do not use this terminal to power other external devices. Refer to ELECTRICAL CHARACTERISTICS TABLE for further
information.
The J16 connector type is an MCV series (or equivalent) from Phoenix Contact (ref. 1803442). The board is
also provided with the matching plug connector (ref. 1803604).
Current
18 19 20 21 22
sensor
+5 VDC
Alpha reg.
Potentiometer
COM GND
Voltage
sensor
figure 18: Connection diagram example for J16.
Notes:
- ALPHA_INP setpoint can be driven by a potentiometer. This potentiometer can be any type, but with a recommended
value of 4.7 kΩ. If a potentiometer is used its positive +5 V DC reference can be wired to J15:17 (VCC) and GND
reference to J16:18 (GND).
I_SENS, U_SENS and ALPHA_INP can work with 0-5 V, 0-10 V, 0-20 mA or 4-20 mA signals level.
22
4.2.8 Output SCR firing connectors (SCR1-SCR6)
The output SCR firing connectors are labelled (PCB silkscreen) indicating the six outputs SCR1 to SCR6
and its correspondent G and K connections, please see figure 19. Mains connection must guarantee
concordance with the SCRs to get sure that the synchronism and phase rotation is correct.
If the concordance is wrong this can be fixed without reconnecting the SCRs by means Autoset function or
manually assigning the correct outputs by software.
In case the phase rotation is wrong the PCB can autodetect and solve it using the Autoset function or, if it is
enabled phase rotation autoset during the power on, just by reset the system.
TO SCRs (SCR1-SCR6)
N T S R G1 K1 G2 K2 G3 K3 G4 K4 G5 K5 G6 K6
SCR6 G6 K6
The connectors type is an MSTBVA series (or equivalent) from Phoenix Contact (ref. 1755736). The board is
also provided with the matching plug connectors (ref. 1757019).
Notes:
- For thyristor connection, see chapter 7 where there are the most typical circuits. And please read the mounting
recommendations on page 48,
- Avoid long cables in the firing system, and always use twisted or shielded cables (preferred).
J32
23
4.3 LCD menu settings and navigation
SC6006 has an on-board integrated alphanumeric LCD that provides an user interface to easy set up and
monitor every configuration or setting of the system.
When initializes SC6006 starts on main menu as is shown in figure 20 and there are a total of 3 menus. The
main menu (on top of the figure), settings menu, and registers menu. User can go cyclically through this
menus clicking the [MENU] push-button.
[MENU]
[MENU]
[MENU]
The [OK] push button triggers ON the SCR controller when its pushed at main menu and accepts the
introduced changes or access to the submenus when it's pressed in the other menus.
The [UP] an [DOWN] push buttons move up and down in the menus and, when selected, increases or
decreases the settings variables.
PWR
FIRING
FAULT
OV CURR
EXT BLK
MENU OK
RESET
By default SC6006 will show in the first line of main menu its version and if there is any fault. In the second
line the values (in %) of the reference inputs (current and voltage).
By pressing the push-button [UP] the first line of main menu will switch to the default information to show the
24
actual values (in %) of the sensed current and voltage. If the SC6006 is in fault mode then the first line
always will show the default information.
By pressing the push-button [DOWN] the second line of the main menu will switch to the default information
to show the actual value (in %) of the alpha reference.
When during the initialization SC6006 could not determine the phase-rotation, frequency or output
assignation and its default configuration it is ben made a “!” character will be shown on the fist position of the
second line.
N T S R G1 K1 G2 K2 G3 K3 G4 K4 G5 K5 G6 K6
PWR
SC6006
LCD CONTRAST
FIRING
FAULT
OV CURR
EXT BLK
MENU OK
RESET
COARSE FINE
SC6006
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
Note:
All the changes of visualization, information and backlight state introduced in the main menu can be saved in EEPROM
by submenu 1.11 (submenu save).
TOPOLOGY OPTION
By pressing [OK] button we can change between B6C topology and W3C topology operation.
25
4.3.2.2 Mode option
MENU 1: SETTINGS > Mode > [PSA / FWS / RLY / DRV]
MODE OPTION
By pressing [OK] button we can change between PSA, FWS, RLY and DRV modes of operation.
By pressing [OK] button we access to the Reference submenu. In this submenu we can change the
references which SC6006 uses to calculate the setpoint. It is possible to choose between analog references
for alpha, voltage and current or use the digital registers for this setpoints .
By default all inputs in SC6006 are configured in zero mode (no live-input).
CONTROL OPTION
By pressing [OK] button system changes between “OL” (open loop), “I” (current regulation), “V” (voltage
regulation) or “IV” (both current and voltage regulation).
26
• When SC6006 is operating on PSA Mode:
By pressing [OK] button it access to the Soft ON/OFF ramps submenu. In this submenu you can activate or
deactivate the soft turn on and soft turn off and set up the both times.
By default SC6006 is configured with 10 seconds (both UP and DOWN) ramps but with soft on and off
options disabled.
By pressing [OK] button it access to the Soft ON/OFF ramps submenu. In this submenu you can activate or
deactivate the soft turn on and soft turn off on FWS mode and set up the both number of cycles in which
PSA will be used.
By default SC6006 is configured with 10 cycles (both UP and DOWN) ramps but with soft on and off options
disabled.
Note:
On cases where a determinated number of cycles of turn on is set, the minimum firing packet will be this number of
cycles A. On those cases where a determinated number of cycles B of turn off where set the minimum firing packet will
be B. On those cases where turn on and turn off is set with A and B cycles respectively the minimum firing packet will be
A+B cycles. Additionally, if alpha setpoint is set to 0% SC6006 will not fire, alternatively if alpha setpoint is set to 100%
the board will be permanently activated ignoring turn on and turn off clycles.
In this submenu we can enable or disable each one of the sources of fault (Halt, Sync and OvCurr) and even
the fault signal itself (Fault). We also can set if the signals block and inhibit works as a normally-on or
normally-off signals. Besides, the last option in submenu (Lock fault) interlocks the fault signal in case of fault
event and stops the system and blocks it until all faults are gone and the SC6006 is in OFF mode by
pressing [OK] push button in main menu.
By default SC6006 is configured with all the faults enabled and block and inhibit signals normally off.
Interlock fault disabled.
START UP OPTION
By pressing [OK] button we can change between ON, OFF or Last state.
Mode “ON” enables the firing every time the system is powered up. Mode “OFF” starts always SC6006
stopped. In “Last state” mode starts the system maintaining the last state when it was powered down.
27
By default SC6006 is configured with LAST state when start up the system.
> Autoset?
By pressing [OK] button we access to the Autoset submenu. In this submenu we can configure the mains
frequency (50 or 60 Hz) or leave the SC6006 finds by itself the working frequency. Also SC6006 can set up
by itself the outputs configuration and the phase rotation.
With the last option the SC6006 will start the autoset procedure.
The autoset is launched every time the system is powered on autosetting the enabled configurations.
By default SC6006 is configured as 50 Hz mains frequency with the outputs detect disabled and automatic
rotation enabled.
By pressing [OK] in “RS232” option we can activate or deactivate the serial communication of the unit.
By pressing [OK] in “Remote” option we can activate or deactivate the serial communication of the unit when
operating with a SCRP6006 remote panel please read on chapter 8.1 - SCRP6006 for further information.
By default SC6006 is configured with its serial port activated and the communication with a SCRP6006
deactivated.
By pressing [OK] in “Save all?” a warning message will be displayed and then, if we push another time [OK]
28
all changes introduced will be saved in the internal EEPROM. By pressing [MENU] we will return to previous
menu.
By pressing [OK] in “Restore?” a warning message will be displayed and then, if we push another time [OK]
all configurations will be restored to the factory settings and then the controller rebooted.
values.
Next will be briefly explained each of this set registers.
> uref_d: This is the corresponding digital register to adjust the voltage setpoint when the unit is
configurated to operate with the digital voltage setpoint register.
This is a 10 bit register and can be set from 0 (0%) to 1023 (100%).
> iref_d: This is the corresponding digital register to adjust the current setpoint when the unit is
configurated to operate with the digital current setpoint register.
This is a 10 bit register and can be set from 0 (0%) to 1023 (100%).
> duty: This register adjust the duty cycle for the output pulse gate train. Can be set from 5% to
30% and by default it is set for a duty of 25%.
> dly2: This register adjust the firing delay when B6C topology is used. It is, by default, configured
to adjust the firing signal to the mains signal and normally there is no need to change its value.
29
4.3.4 Debug menu
If, when power on the SC6006, we maintain pressed the [UP] push-button we will enter in debug mode. In
this mode we can access to another menu called debug menu. In this menu we can see with the on board
LCD the values of many internal registers of the system. This mode is intended only for debug purposes.
Note: All configuration changes introduced by user must be saved before power down or resetting the equipment or all
changes will be lost.
Jumper Description
J7 Used to control the gain of the direct voltage feedback input. Further description in 4.4.3.
Used to change the source of voltage feedback signal between direct voltage feedback input
JP20
and analog input voltage signal input.
JP21 Used to select between auxiliary current transformers or shunt.
Used to change the source of current feedback signal between auxiliary current transformers or
JP22
shunt and analog input current signal input.
It will be used for feedback with shunt in positive terminal and inverted voltage feedback. See
JP23
chapter 7.3.2 on page 44.
JP24 Do not use this jumper, leave all its pins unconnected.
Notes:
In case of using an isolated sensor for the DC current feedback with J16[p19]-I_SENS, please double check
the measuring direction of the sensor. Current feedback signal must be always positive.
In the following table can find the correct jumper configuration for common application schemes.
Warning notes:
- Make sure and double check the position of the plugging connectors (jumpers), following previous indications.
- JP70 and JP71 are reserved, do not use them, they always must be connected.
- Do not let any jumper unconnected except for the J24 jumper.
30
4.4.2 DIP Switches
DIP switches sets the type of signal input for current and voltage references (I_SET, U_SET, voltage and
current references (I_SENS, U_SENS) and alpha reference (ALPHA).
All this signals can be configured with DIP switches to work as 0-5 V, 0-10 V and 0-20 mA. For live input (4-
20 mA) the configuration is made through software.
1 2 3 4 1 2 3 4 1 2 3 4
I_SET U_SET I_SENS U_SENS ALPHA
There are 2 switches assigned to each input as we can see in figure 23. In this figure is shown the default
configuration of the switches. With this configuration all inputs are set to work as 0-5 V signals.
0-5 V mode (ON-OFF):
ON If we want to adjust I_SET (e.g.) input for 0-5 V mode the 2 correspondig switches must be set as
follows: first switch ON (up position) and second switch OFF (down position). Same way for the
1 2 other input signals.
Warning note:
Please double check if the configuration set by the DIP switches corresponds to the input signals you use. And avoid by
all means the OFF-ON configuration.
31
4.4.3 Setting the gain for direct voltage feedback input
Voltage input feedback gain for J12[p1]-V_REAL input can be precisely adjusted for work correctly sensing a
wide range of load voltages (see technical specification and maximum rated values). The gain of direct
voltage feedback is adjusted by regulating R01 resistance using a pair of potentiometers (R01C and R01F)
and a jumper on board (J7).
MENU
A
COARSE FINE
R01
PWR
B
SC6006
LCD CONTR AST
MENU
COARSE FINE
SC6006
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
R01 resistance for the maximum voltage regulation, it must be calculated and regulated with R01C
and R01F potentiometers following the indications below:
Note: When gain is properly regulated according the input voltage, the signal present in the upper pin of J20 must go
from 0 to 5 V when input voltage go from 0 to 100%.
In case R01 has been set but the output regulation do not reach the 100% try to decrease gradually the gain voltage
feedback to the point where the unit regulation go from 0 to 100%.
By default SC6006 is factory calibrated for measurement of 400 VAC through bridge rectifier input (565 VDC
input).
32
5 SERIAL COMMUNICATION
SC6006 has a serial communication port (J32) to make basic operations of control and configuration of the
system through a RS232 interface with, for example, a remote PC or a PLC.
The default configuration of the serial link is as follows:
Baud rate: 9600bps
Parity bit: none
Stop: 1 bit
Flow control: none
To interface it with a standard RS-232 serial communication port, you will need a specific DB-9 null modem
cable. You can, additionally, order the cable with the SC6006 board.
PIN #1 PIN #5
PIN #6 PIN #9
figure 25: J32 Connector (male D-SUB9) pinning detail. SC6006 lateral view.
When powered on SC6006 sends a welcome message and awaits for the user instructions. If we interface
SC6006 with a PC with HyperTerminal (e.g.) when system is power up we will see the following:
>
33
5.1 Overview available command set
SC6006 has 4 different types of instructions:
– Query instructions (?).
– Signal instructions (*).
– Memory read instructions (R).
– Memory write instructions (S).
To send any instruction to SC6006 and for being processed this instruction must end with a 0x10[“NL”]
character (or an enter pulsation if HyperTerminal is used).
All the sent instructions will return back to the user (at least) the 0x10[“NL”] character plus the character of
waiting for a new instruction: 0x3E[“>”]. This 2 characters will always be sent back even when the echo
mode is deactivated.
>?ver
PCB:v1.0 firmware:v1.28
34
5.3.1 “*OK” signal command
Sends a remote pulsation of the [OK] push-button.
35
5.4 Memory read instruction
The memory read instructions starts with 0x4D[“M”] character followed by 3 numeric characters which
specifies the memory address to read through communications port.
This instruction returns the decimal value of the specified register.
>M001
SC6006: 65460d
Note:
The table 2 in page 37 shows the a list of available registers to read with its corresponding brief description.
>M011
SC6006: 00000d
>S00128
SC6006: 00128d
>S00000
SC6006: 00000d
Note:
The table 8 in page 40 shows a list of available registers to write with its corresponding brief description.
36
6 INTERNAL MEMORY AND REGISTERS
Following you will find a list of some important internal software registers of SC6006 and its description. Most
of the features of SC6006 can be set using the on-board LCD menu but the operator/installer can also
access or set a great deal of internal configurations making use of RS-232 communications port described in
last chapter.
37
M000: STATUS0 register
bit Name Description
0 on system status. ON(1)/OFF(0)
1 fault system status. Fault bit signal
2 halt halt bit signal
3 inh inhibit bit signal
4 ext_blq external block bit signal
5 sync system status. Sync bit signal
6 ov_curr system status. Overcurrent bit signal
7 N/A
8 N/A
9 N/A
10 N/A
11 N/A
12 N/A
13 N/A
14 N/A
15 N/A
table 3: bit list for status0 register.
38
M002: P_STATUS0 register
bit Name Description
0 en_on enable ON (firing) mode
1 en_fault enable fault signal
2 en_halt enable halt signal
3 en_inh enable inhibit signal
4 en_ext_blq enable external block signal
5 en_sync enable sync fault signal
6 en_ovcurr enable overcurrent fault signal
7 sw_fault enable interlock fault
8 N/A
9 N/A
10 topo0 topology bit. B6C=0, W3C=1
11 N/A
12 N/A
13 backlight enable LCD backlight
14 N/A
15 N/A
table 5: bit list for p_status0 register.
39
M004: P_STATUS2 register
bit Name Description
0 u_ref_src voltage setpoint reference bit
1 i_ref _src current setpoint reference bit
2 N/A
3 N/A
4 alpha_ref_src alpha setpoint reference bit
5 N/A
6 N/A
7 echo comm. echo mode
8 mode0 mode0 bit. PSA=0 FWS=1
9 mode1 mode1 bit. RLY=1
10 N/A
11 N/A
12 fb0 feedback mode bits:
13 fb1 00:I, 01:V, 10:IV, 11:OL
14 N/A
15 N/A
table 7: bit list for p_status2 register.
Warning note:
Take special care when attempting to change any of the configuration bits of p_status registers, if accidentally a wrong
value is written the system can stop working or malfunction.
Warning note:
Please do not attempt to make a writing in a register not appearing in table 8.And do not write to a register a value out of
the defined range.
40
7 INSTALLATION
In the following chapter it is given a walk-through for the most common configurations and topologies where
a SC6006 can be used, and examples on how to properly connect the SCR scheme or how the feedback
loop (V/I) can be set. Also is given some mounting recommendations.
Below there are some schematics of the most common applications (different combinations of rectifiers and
antiparallel thyristors), as well as feedback connections by shunt, transformer, etc.
The following descriptions are made separately for what concerns the firing and feedback, because they can
combine in different ways (for example, it can be done an antiparallel control (AC) taking the feedback from a
rectifier (DC), a typical application of this example would be the primary control of a transformer of a surface
treatment).
In the application examples SCR are labeled with concordance with standard output software configuration
(r-r'-s-s'-t-t').
At the end of this descriptions some advice as mounting recommendations are given, with the aim to
improve the working security and prevent possible external problems along the installation process.
SCR2
SCR3
LOAD
S V
SCR4
SCR5
T W
SCR6
41
7.2.2 W3C current and voltage feedback scheme
In figure 27 is shown a typical feedback connection for a W3C scheme. Current feedback made with current
transformers and voltage feedback using an auxiliar rectifier. Please note that if we use this configuration
with an auxiliary bridge connected to J12[p1]-V_REAL it not provides a galvanic isolation.
SCR1 CURRENT
TRANSF.
R U
SCR2
SCR3 CURRENT
TRANSF.
S V
SCR4
SCR5 CURRENT
T TRANSF. W
SCR6
AUX_I_T J14 11 U_REAL
J12 01
AUX_I_S J14 10
J12 02 GND
AUX_I_R J14 09 AUXILIAR
RECTIFIER
SCR1
R
SCR2
SCR3
S
SCR4
SCR5
T
SCR6
42
SCR1
R
SCR2
SCR3
S
SCR4
SCR5
T
SCR6
SCR1
R
SCR2
SCR3
S
SCR4
SCR5
T
SCR6
43
R R
T S T S
Note:
Autoset function will not be capable to determine the output connection for this topologies due its common cathode
connection. The user must check the concordance between the software output phase assignation and the wiring to the
SCRs.
R
S
T
-
figure 32: B6C topology connection example.
44
N T S R G1 K1 G2 K2 G3 K3 G4 K4 G5 K5 G6 K6
I_SHUNT SHUNT
MENU
J14 12
COARSE FINE
GND JP23
LOAD
J14 08 PWR
SC6006
U_REAL
L CD CONTRAST
J12 01 MENU
UP
C OARSE F INE
0-700 VDC
U_SENS I_SENS I_SET U_SET I _SENS U_SE NS ALPHA
SC60 06 2 3
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
MENU
U_REAL
J12 01
COARSE FINE
JP23
I_SHUNT
LOAD
PWR
J14 12
SC6006
LCD CONTRAST
GND MENU
DOWN
J14 08 COARSE FINE
2 3
SHUNT SC60 06
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
Warning note:
By default jumper JP23 is in DW configuration. Only change it to UP position when using a shunt in positive terminal and
direct voltage input feedback.
SCR1
U
R
SCR2
S SCR3
V
SCR4
T SCR5
W
SCR6
figure 35: AC/DC converter example with current and voltage feedback from transformer in primary side.
For this example circuit U_SENS and I_SENS inputs must be set through DIP-switches as 0-10 V inputs.
45
7.4 Direct drive mode with block signal
When SC6006 is operated in 'DRV' mode please note overcurrent fault and synchronism fault are
automatically disabled, and also the inhibition signal is no longer a source for halt fault.
SCR1
SCR2
SCR3
SCR5
SCR6
SCR4
N T S R G1 K1 G2 K2 G3 K3 G4 K4 G5 K5 G6 K6
PWR
SC6006
LCD CONTRAST
FIRING
FAULT
OV CURR
EXT BLK
MENU OK
RESET
COARSE FINE
SC6006
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
SCR3_CTL
R S
J15 16
MAINS POWER SUPPLY
SCR's control SCR4_CTL
signals
J16 19
SCR5_CTL
J16 20
SCR6_CTL
J16 21
46
Following you will find a walkthrough to set up this operation mode according the circuit example given at
figure 36.
47
7.5 Mounting recommendations
1- Avoid long cables in the firing system, or use twisted or shielded cables. Apply it also for the
potentiometer cables.
2- Ground the device in accordance with local regulations.
3- Make sure that the board is not in environments of strong magnetic fields, for example, high power
transformers, or apply it a conductive envelop connected to ground.
3- For use it in inductive or capacitive loads, with regular connection cycles, it’s recommended to use a
fixed resistive load (with low value), in order to avoid any kind of error during the start up process
(this is valid for all assemblies).
4- Is convenient to realize working tests with small loads (for example, bulbs or resistors), in this way if
there is any connection error will be detected without further consequences. It’s important to know
that the feedback susceptibility couldn’t be enough with loads which consumes very low current,
thus, the control operation can be wrong.
5- In AC current control applications with voltage regulation, it must be added the auxiliary rectifier
module SCCAV02, knowing that the galvanic isolation disappears with the net, otherwise use the
isolated version SCCAV02 OA.
6- Shunt elements doesn’t provide galvanic isolation in current feedback power stage. If galvanic
isolation is a requirement, it must be used isolated current sensors (Hall sensors).
7- In applications with presence of variable loads, parasitic in the net, regulations with minimums voltage
and currents, can cause non desired oscillation regulations. For this cases, please contact to our
technical department.
8- Install the device in a upright or flat position and ensure a minimum ventilation distance between
surroundings. If mounted in a cabinet ensure sufficient ventilation and always observe minimum
spacing (clearance: 150 mm above and below).
8- For specific applications, there is the possibility to realize customized software and hardware
adaptations and include auxiliary control modules, so please, don’t hesitate to ask about your
application.
CAUTION:
Before plugging the supply voltage for the control unit, be sure that the card is locked or will be start up in OFF mode
and set the regulation potentiometers to the minimum level.
2- Regulate to the minimum level all the voltage and current or alpha potentiometers or setpoints.
3- If Autoset mode is configured for check and set the mains frequency operation, the phase rotation or
outputs assignation, it will be done when the control board is powered up. Then SC6006 must be
powered after or at the same time as the power stack.
48
4- Check operation and configuration settings are correct for your application.
49
8 AVAILABLE ACCESSORIES
There are available several accessories to work with the SC6006 which will be briefly described in this
section, those accessories are normally used in applications with the firing board to enhance or complete its
integration in a power converter.
8.1 SCRP6006
SCRP6006 (datasheet) is specially designed to interface our SC6006 SCR digital firing board. It provides a
neat and easy way to remotely monitor and set up SC6006 SCR controller board using its serial interface.
This panel expands the on-board LCD screen, buttons and status LEDs for mounting in a cabinet door.
Additionally provides an extension to SC6006 serial link communication port.
Typical application
PWR
FIRING
FAULT
OV CURR
EXT BLK
MENU OK
RESET
COARSE FINE
SC6006
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
50
8.2 SCGI24
SCGI24 (datasheet) is a single-channel universal galvanical isolator well suited to interface standard 60 mV
shunt current loops and direct voltage feedback signaling with a great input range (up to 700 V).
Typical applications
SHUNT
POS. TERM.
POS. TERM. SCGI24 02
SCGI24 02
LOAD
LOAD
NEG. TERM.
NEG. TERM. SCGI24 03
SCGI24 03
SHUNT
TO POS. TERM.
TO NEG. TERM.
N T S R G1 K1 G2 K2 G3 K3 G4 K4 G5 K5 G6 K6
6 5 4
3 2 1
SEMICODE
ELECTRONICA
GRUESO FINO
SCGI24
CERO
®
PWR
Input : 0-60 mV
Output: 4-20 mA
SPAN
SC6006
GRUESO FINO
LCD CONTRAST
FIRING
FAULT
OV CURR
EXT BLK
MENU OK
RESET
COARSE FINE
9 8 7
12 11 10
SCGI24:9
SCGI24:8
SC6006
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 0V +24V
J16:19
J16:18
figure 38: Interfacing 60 mV shunt application with SCGI24 and 4-20 mA current loop signal.
51
8.3 SCST700
SCST700 (datasheet) is a 3-phase signal transformer for synchronism signaling which also provides a
neutral signal to the controller card in installations without neutral take which is necessary to acquire a good
synchronizing signal for SC6006. It is recommended to use it in those cases neutral connection is not
available on the installation.
Typical applications
R
MAINS
S J11 - SC6006
SYNCHRONISM
T CONNECTOR
SCST700 J2 CONNECTOR
N T S R N T S R G1 K1 G2 K2
T S R
SEMICODE
ELECTRONICA
RG140902
N T S R
®
SCST700 J1 CONNECTOR
figure 39: Interfacing SC6006 with mains voltage from 200 to 700 VAC.
SCST700 J2 CONNECTOR
N T S R N T S R G1 K1 G2 K2
T S R
SEMICODE
ELECTRONICA
RG140902
N T S R
®
SCST700 J1 CONNECTOR
R
MAINS
S
T
figure 40: Interfacing SC6006 with mains voltage from 65 to 200 VAC.
52
9 FIRMWARE REVISIONS
Changes introduced on each firmware version of SC6006 along the initial serial number from each firmware
revision has been released are listed in the following table and described in detail below.
Please note that is possible to upgrade an old control card with the newest revision available on request.
● Added a new mode of operation called "DRV" giving the option of fire
v1.05 2013-06-25 126553 each of the 6 channels independently from the rest and from
synchronism.
v1.20 2014-01-13 129519 ● Block and inhibit ON/OFF signal mode. Block and inhibit can work as
board's ON/OFF signals.
● Saving last correct outputs assignation for use when the board is
unable to autoset outputs.
v1.25 2015-04-10 138426
● Improved given on-screen information for autoset and autoconf.
v1.28 2016-02-11 138440 ● Rugged behaviour on FWS with slope in for temperature treatments
with resistors controlled on primary.
53
10 TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS
Description Symbol Notes / Test Conditions Min Typ Max Units
Input supply voltage VIN RMS 50Hz - 60Hz 195 230 480 VRMS
Input AC voltage (sync) Vsync 10 700 VRMS
Direct input voltage sense VREAL 10 700 VDC
Thyristor triggering current IOUT Vout = 5V 600 mA
Working frequency fw 50 / 60 Hz
Load Delta / wye
Topologies W3C, B6C, M6C, M3.2C, W3H, B6H, M3C…
Working modes Phase angle modulation, Full wave switch and relay mode
Protection degree IP-00
Pollution degree III
Humidity 50% Rh @ 35ºC / 70% Rh @ 20ºC
Power-to-control isolation voltage VISOp-c 50 Hz @1min 5300 VAC
SUPPLY SPECIFICATIONS
Description Symbol Notes / Test Conditions Min Typ Max Units
Line voltage VIN RMS ±10% 195 230 480 VRMS
Frequency range fw 47 63 Hz
Power output Pout 25 W
Typical input current Full load @ 230VAC IN 180 mA
Full load @ 400 VAC IN 130 mA
Inrush current limiting @ 230VAC IN 11,5 A
@ 400 VAC IN 20 A
Isolation between mains and output @ 1min 4000 VRMS
Isolation between secondaries @ 1min 4000 VRMS
Power supply starting time 1.5 s
System start up time without sync signals 5 s
Data at Ta = 25 °C, VIN = 230 VAC and rated v alues, unless otherwise indicated
54
BLOCK DIAGRAM
4
Line IN EMI RECTIFIERS POWER RECTIFIERS
FILTER & SWITCHING &
FILTER FILTERS
Vdd
Cathode synch. detector
R, S, T IN
3
Synch C.T. feedback input
Neutral
3
Digital I/O
From mains
current
Block DSPa transformers
2 Shunt feedback input
Ext. Block
Fault
DSPb
Direct voltage feedback input
2
To
COM
SCR FIRING BOARD
Device
55
PROTECTIONS AND TIMMINGS
Description Symbol Notes / Test Conditions Min Typ Max Units
Phase los s, sync or rotation fault
External block signal Disables thyristor f iring
Overcurrent fault Fault auto-reset sof tw are conf igurable
Max. time detect and stop phase loss tph_dly 50 60 ms
Maximum time ext. Block to stop tblk_dly 0.25 ms
Maximum time to response RS232 op. tRS232_dly 0.2 ms
Tim e to get mains sync tsync 50 cycles
SOFTWARE ADJUSTMENTS
Description Notes / Test Conditions
Maximum/minimum voltage limit 0 – 100%
Maximum/minimum current limit 0 – 100%
Soft start and stop time 1 – 30 s (independently adjustable)
Overcurrent 0 – 300%
56
OUTPUT FIRING PULSE TRAIN
Description Symbol Notes/Test conditions Min Typ Max Units
Thyristor triggering current IOUT Vout = 5V 600 mA
Maximum output voltage VOUT max 7.5 V
Max transferred power to load POUT max 3 W
Output firing train frequency f OUT 1 12 25 kHz
Output firing train duty cycle Dc OUT 5 25 30 %
3,50
3,00
2,50
2,00
Power [W]
1,50
1,00
0,50
0,00
0 2,5 5 7,5 10 12,5 15 17,5 20 22,5 25
Load [Ω]
CONFORMALS
Conformal coating MIL-1-46058, Type UR
Security EN60950-1, UL60950-1
EMC DIRECTIVE
This Thyristor power controller is intended to work as part of an industrial fixed installation and is not for itself a functional
unit destined to an end user. According 2004/108/CE directive, CE marking for this device not apply.
57
10.1 Mechanical dimensions
Description Notes/Test conditions Units
Board 225 x 170 x 45 mm
Fixations fixation holes diameter 4.5 mm
Weight (aprox) 700 gr
N T S R G1 K1 G2 K2 G3 K3 G4 K4 G5 K5 G6 K6
SEMICODE
ELECTRONICA
®
PWR
SC6006
LCD CONTRAST
FIRING
FAULT
OV CURR
EXT BLK
MENU OK
RESET
COARSE FINE
SC6006
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
N T S R G1 K1 G2 K2 G3 K3 G4 K4 G5 K5 G6 K6
SEMICODE
ELECTRONICA
®
PWR
SC6006
LCD CONTRAST
FIRING
SIGNALING LEDS
FAULT
OV CURR
EXT BLK
MENU OK
RESET
COARSE FINE
SC6006
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
J1 - POWER J12 - FEEDBACK J13 - EXTERNAL BLOCK J14 - CURRENT J15 - SETPOINTS J16 - FEEDBACK AND
SUPPLY VOLTAGE AND DRY OUTPUT FAULT INPUT FEEDBACK AND INHIBIT ALPHA SETPOINT
58
Cost Effective Products
SEMICODE ELECTRONICA
Offers to the market a comprehensive range of products from recognized manufacturers at the best
price/quality relationship, this products are provided with a basic reference code that allows maintaining the
same product reference even if the original device manufacturer is replaced. SEMICODE product reference
has to be considered as a generic brand.
Seeking the market needs and trends, we are constantly increasing the product portfolio with new products
and suppliers, please ask for the updated information available to our local contacts.
SEMICODE products include semiconductors, passive components and accessories focused in power
electronics market.
Datasheet Annotations:
SEMICODE ELECTRONICA annotate datasheets in the top left hard corner of the front page, to indicate
product status. The annotations are as follows:
Tentative information: This is the most tentative form of information and represents a very preliminary
specification. No actual design work on the product has been started.
Preliminary Information: The product is in design and development. The datasheet represents the product
as it is understood but details may change.
Advance Information: The product design is complete and final characterisation for volume production is
well in hand.
No Annotation: The product parameters are fixed and the product is available to datasheet specification.
NOTICE: The technical data are to specify components, not to guarantee their properties.No warranty or guarantee expressed or
implied is made regarding delivery or performance. The Company reserves the right to alter without prior notice the specification of any
product. Information concerning possible methods of use is provided as a guide only and does not constitute any guarantee that such
methods of use will be satisfactory in a specific piece of equipment. It is the user’s responsibility to fully determine the performance and
suitability of any equipment using such information and to ensure that any publication or data used is up to date.
All brand names and product names used in this publication are trademarks, registered trademarks or trade names of their respective
owners.
59