Hoja de Calculo Tierra Armada

Descargar como xls, pdf o txt
Descargar como xls, pdf o txt
Está en la página 1de 10

DISEÑO DE MURO DE CONTENCION DE CONCRETO ARMADO

DATOS
Angulo de fricción interna (relleno) = 33 °
Peso especifico del terreno (relleno) = 1.80 ton/m3
Angulo de fricción interna (suelo) = 33 ° 0.84
Angulo de inclinacion (suelo) = 0 ° 1.00
Peso especifico del terreno (suelo) = 1.60 ton/m3
Coeficiente de fricción = 0.50
Resistencia del terreno = 1.00 kg/cm2
Resistencia del concreto (f´c) = 210 kg/cm2
Resistencia del acero (fy) = 4,200 kg/cm2
Sobrecarga = 2196 kg/m2

Fuerzas verticales actuantes


Fv (ton) Xcg (m) M (ton-m)
W1 0.82 1.20 0.98
W2 1.15 0.80 0.92
W3 0.00 0.55 0.00
W4 0.82 1.45 1.18
S/C 1.10 1.35 1.48
TOTAL 3.88 Mv = 4.57

Fuerzas horizontales actuantes


Fh (ton) Ycg (m) M (ton-m)
EA = KAgh(h/2) = 1.06 0.67 0.71
ES/C= KA(s/c) h = 0.97 1.00 0.97
EP = KPgh(h/2) = 1.15 0.10 0.11 0.65

VERIFICACIONES

1.- Estabilidad al volteo

F.S.V = M resistente = 2.79 > 2 CUMPLE


M actuante

2.- Estabilidad al deslizamiento

E P+ E f 1.52 > 1.5 CUMPLE


F . S . D .= =
E A + E S /C

3.- Verificación de compresiones y tracciones

S Fw = 3.88 Ton
S Mo = 3.00 Ton-m M 0.027 m
e= =
M cg = 0.773 Ton-m F

σ máx=
∑ Fv ( 1+ 6 e )= 0.27 kg/cm2 < 1.00 CUMPLE
B B

σ min=
∑ Fv ( 1− 6 e )=
B B
σ min=
∑ Fv ( 1− 6 e )= 0.22 kg/cm2 > 0.00 NO HAY TRACCION
B B

Cargas distribuidas
w (s/c) = 2.20 ton/m
w (s) = 3.06 ton/m
w (pp) = 0.72 ton/m

Cargas últimas
q (ton/m) q'b (ton/m) qb (ton/m) q'd (ton/m) Wu (ton-m)
s máx 2.67 0.33 3.89
s mín 2.18 0.09 2.28 2.07 9.03

Esfuerzos (ton/m2)
NFZ NSZ a "d" zapata
sEA = KAghx1.7 = 1.80 1.53 1.39
sES/C= KA.s/cx1.7= 1.10 1.10 1.10
sEP = KPghx1.7= 2.77 0.00 0.00

DISEÑO DEL MURO

PANTALLA TALON PUNTA


Dimensiones
b (m) = 0.20 0.30 0.30
d (m) = 0.16 0.23 0.23
Verificación por corte
Vu (ton) = 2.76 1.59 4.28
f Vc (ton) = 10.45 14.69 14.69
Condición > Vu CUMPLE CUMPLE CUMPLE
Verificación por flexión
Mu (ton-m) = 2.33 0.22 1.97
As requerido = 4.96 0.35 3.12

* En todos los casos el área de acero requerida es menor al mínimo. Entonces consideramos:

En la pantalla:
Vertical
As mín = 0.0015*b*d = 2.40 cm2
As = 4.96 cm2
doble malla
VARILLA No 4 Ø = 1/2'' @ 25.5 cm

Horizontal:
As mín = 0.0020*b*d = 3.20 cm2
As = 1.60 cm2
doble malla
VARILLA No 3 Ø = 3/8'' @ 45 cm

En la zapata continua:
Longitudinal
As mín = 0.0018*b*d = 4.05 cm2
As = 4.05 cm2

As inf = 0.0012*b*d = 2.70 cm2 26

As sup = 0.0009*b*d = 2.03 cm2 35

As = 2.70 cm2 doble malla

VARILLA No 3 Ø = 3/8'' @ 26 cm

Transversal
As mín = 0.0018*b*d = 4.05 cm2

As inf = 0.0012*b*d = 2.70 cm2 26

As sup = 0.0009*b*d = 2.03 cm2 35

As = 2.70 cm2

VARILLA No 3 Ø = 3/8'' @ 26 cm

* Por montaje se colocará más acero del requerido, según los planos.
Dimensionh1 = 1.70 m
h2 = 0.00 m
t = 0.30 m
D = 1.10 m
2D = 0.30 m 0.82 m3
b = 0.20 m 0.12
B = 1.60 m 0.9
H = 2.00 m
m (0.5-0.7) = 0.50
KP = 3.39
Ka = 0.29
Hpedestal = 0.65 m
Altura libre = 0 m

0.773
0.027
HAY TRACCION

ϒconcreto = 2.40 tn/m3 f = 0.9


bw = 1.00 m f´c = 210
h = 0.20 m fy = 4200
d =
Mu 0.16 m β1 = 0.85
(ton.m w ρ As (cm2) ρb
EJE B )
2.33 0.050 0.25% 4.96 2.13%

ϒconcreto = 2.40 tn/m3 f = 0.9


bw = 1.00 m f´c = 210
h = 0.30 m fy = 4200
d = 0.23 m β1 = 0.85

ϒconcreto = 2.40 tn/m3 f = 0.9


bw = 1.00 m f´c = 210
h = 0.30 m fy = 4200
d =
Mu 0.23 m β1 = 0.85
(ton.m w ρ As (cm2) ρb
una malla PUNTA )
1.97 0.021 0.10% 3.12 2.13%
doble malla 2/3 EN LADO MAS DESFAVORABLE
Kg/cm2
Kg/cm2

ρmax
1.06%

Kg/cm2
Kg/cm2

Kg/cm2
Kg/cm2

ρmax
1.06%
MURO DE TIERRA ARMADA
Propiedades del muro
Altura de Muro H 8.00 m
Propiedades del Relleno
Peso especifico del relleno γ1 18.0 kN/m²
angulo de rozamiento/friccion del relleno ∅1 30 º
Coeficiente de activo Ka 0.333
Sobrecarga s/c 5.00 kN/m²
Propiedades de los tirantes
angulo de rozamiento/friccion entre el suelo y el tirante ∅μ 20 º
Espaciamiento horizontal de los tirantes 1.00 m
espaciamiento vertical de los tirantes 0.50 m
longitud del tirante 12.00 m
Ancho del tirante 80.00 mm
espesor nominal del tirante 6.00 mm
tasa de corrosion 0.03 mm/años
vida util 50 años
espesor del tirante 4.75 mm
resistencia a fluencia de acero del tirante 240.00 N/mm²
resistencia del tirante 91.00 kN
Comprobaciones
Posicion
Profundidad analizada 6.00 m
Rotura del tirante
Empuje debido al terrenoa cota z 36.00 kN/m²
empuje debido a la sobrecarga a cota z 0.00 kN/m²
empuje a cota z 36.00 kN/m²
fuerza en el tirante 18.00 kN/m²
Factor de seguridad contra la rotura del tirante 3.00 kN/m²
Arrancamiento del tirante
Longitud dentro de la zona de falla de 0.00 m
longitud efectiva 12.00 m
Presion Vertical debida al terreno a cota 108.00 kN/m²
Presion Vertical debida a la sobrecarga a cota z 0.00 kN/m²
empuje a cota z 108.00 kN/m²
Resistencia al arrancamiento del tirante 75.00 kN
Factor de seguridad contra la rotura del tirante 3.00 kN/m²