Caida de Tension RP
Caida de Tension RP
Caida de Tension RP
Datos de la tabla de especificaciones tecnicas Datos de la tabla de especificaciones tecnicas de conductores de AAAC
P
U SECCION POTENCIA SUMA I L K ∆V ∑∆V %∑∆V Pp
N CONDUCTOR DE POTENCIA INTENSIDAD LONGITUD FACTOR CAIDA CAIDA DE CAIDA DE TENSION CAIDA DE TENSION PERDIDA DE
T AAAC TRANSF. TRANSF. DE CORRIENTE DE TENSION TENSION ACUMULADA ACUMULADA % POTENCIA
O (mm²) (KVA) (KVA) (AMP.) (m) (ohm/Km) (V) (V) (%) (W)
PA 25 0.0 150.0 6.56 0.0 2.6163 396.00 396.000 3.000 0.00
1 25 0.0 150.0 6.56 62.5 2.6163 1.073 397.073 3.008 11.69
2 25 0.0 150.0 6.56 37.0 2.6163 0.635 397.708 3.013 6.92
3 25 0.0 75.0 3.28 61.0 2.6163 0.523 398.231 3.017 2.85
4 25 0.0 75.0 3.28 60.0 2.6163 0.515 398.746 3.021 2.80
5 25 0.0 75.0 3.28 20.0 2.6163 0.172 398.918 3.022 0.93
6 25 0.0 75.0 3.28 65.0 2.6163 0.558 399.475 3.026 3.04
SAM N° 01 7 25 75.0 75.0 3.28 70.0 2.6163 0.601 400.076 3.031 3.27
2.1 25 0.0 75.0 3.28 23.0 2.6163 0.197 397.905 3.014 1.08
2.2 25 0.0 75.0 3.28 65.0 2.6163 0.558 398.463 3.019 3.04
SAM N° 02 2.3 25 75.0 75.0 3.28 72.0 2.6163 0.618 399.081 3.023 3.37
TOTAL PERDIDAS 38.99
Se considera una Caida de tension en el punto de alimentacion = 3%