WEG Contatores
WEG Contatores
WEG Contatores
Panorama Geral
Contatores
RW17-1D RW17-2D
0,28...0,4 2,8...4 7...10
0,4...0,63 4...6,3 8...12,5
0,56...0,8 5,6...8 10...15
Relés de Sobrecarga (A) 0,8...1,2 7...10 11...17
1,2...1,8 8...12,5 15...23
1,8...2,8 10...15 22...32
11...17
BFC0-20 (2NA)
BFC0-22 (2NA + 2NF)
BFC0-11 (1NA + 1NF) BFC025-11 (1NA + 1NF)
BFC0-04 (4NF) BFC025-20 (2NA)
Bloco de contatos auxiliares - BFC025-02 (2NF)
BFC0-02 (2NF)
BFC0-31 (2NA + 1NF)
Frontal BFC0-40 (4NA)
BFC0-13 (1NA + 3NF) Frontal
_
Intertravamento mecânico
CWI07 BICO
Bloco Varistor:
VRC0-1 E01 12-48V 50/60Hz / 12-60VCC
Bloco RC:
VRC0-2 E34 50-127V 50/60Hz / 60-180VCC
RCC0-1 D59 12-24V 50/60Hz
VRC0-3 E38 130-275V 50/60Hz / 180-300VCC
Bloco RC: RCC0-2 D53 24-48V 50/60Hz
VRC0-4 E41 277-380V 50/60Hz / 300-510VCC
RC01 D53 24-48V 50/60Hz RCC0-3 D55 50-127V 50/60Hz
Protetores de Surto VRC0-5 D73 400-510V 50/60Hz
RC06 D62 110-220V 50/60Hz RCC0-4 D63 130-250V 50/60Hz
RC10 D33 380-400V 50/60Hz RCC0-5 D84 275-380V 50/60Hz
Bloco Diodo(CWC07...16):
RCC0-6 D73 400-510V 50/60Hz
DIC0-1 C33 12-600VCC
RCAC0 D87 180-230V 50/60Hz
Bloco Diodo zener(CWC07...16):
DIZC0 C26 12-250VCC
Notas: 1) Valores orientativos para motores trifásicos IP55, 4 pólos (1800rpm), regime de serviço contínuo S1, fator de serviço igual a 1.
2) Ue ≤ 415V
3) Para combinações de mais de dois blocos de contatos auxiliares laterais.
4) Permite intertravamento mecânico e elétrico
CWM9 CWM12 CWM18 CWM25 CWM32 CWM40 CWM50 CWM65 CWM80 CWM95 CWM105
9 12 18 25 32 40 50 65 80 95 105
25 25 32 45 60 60 90 110 110 140 140
5 7 8 12 16 18.5 23 30 37 44 50
0,28...0,4
RW27-1D 0,4...0,63
5,6...8 RW67-1D RW67-2D RW117-1D
7...10
0,56...0,8
8...12,5 25...40 40...57 63...80
0,8...1,2
10...15 32...50 50...63 75...97
1,2...1,8
11...17 57...70 90...112
1,8...2,8
15…23 63...80
2,8...4
22…32
4...6,3
Frontal Lateral
BLIM9-105
BLIM.02 4)
Bloco RC (CWM32...40):
Bloco RC: BAMRC4 D53 24-48 V 50/60Hz
BAMRC4 D53 24-48 V 50/60Hz BAMRC5 D55 50-127 V 50/60Hz
BAMRC5 D55 50-127 V 50/60Hz BAMRC6 D63 130-250 V 50/60Hz
BAMRC6 D63 130-250 V 50/60Hz Bloco RC(CWM50...105):
Bloco Diodo: BAMRC7 D53 24-48 V 50/60Hz
BAMDI10 C33 12-600 VDC BAMRC8 D55 50-127 V 50/60Hz
Bloco Varistor: BAMRC9 D63 130-250 V 50/60Hz
BAMV1 D68 270-380 V 50/60Hz Bloco Varistor:
BAMV2 D73 400-510 V 50/60Hz BAMV1 D68 270-380 V 50/60Hz
BAMV2 D73 400-510 V 50/60Hz
Panorama Geral
Contatores
RW117-2D RW317-1D
100...150
75...97 140...215
Relés de Sobrecarga (A) 90...112 200...310
275...420
RW407-1D
400…600
560…840
BLIM CWME800
BLIM CWME400
Pesquisa e Desenvolvimento
Produtos Certificados
Minicontatores
www.weg.net
g Minicontatores CWC0 com bobinas em corrente contínua de baixo consumo permitindo a conexão direta a CLP´s;
Ie = Ith
Ie Potência nominal de emprego em AC-3 1) Contatos auxiliares
(Ue ≤ 690V)
(Ue ≤ 440V) Motor trifásico - IV pólos - 60Hz - 1800rpm por minicontator
θ ≤ 55ºC Referência para completar Peso 5)
220V 400V 660V 3 1 com a tensão de comando kg
AC-3 AC-1
230V 380V 415V 440V 500V 690V
4 2
A A kW / cv kW / cv kW / cv kW / cv kW / cv kW / cv NA NF
1 0 CW07-10-30♦
7 2) 16 2) 1,5 / 2 3/4 3/4 - - - 0,130
0 1 CW07-01-30♦
1 0 CWC07-10-30♦
7 18 1,5 / 2 3/4 3/4 3,7 / 5 3,7 / 5 3/4
0 1 CWC07-01-30♦
1 0 CWC09-10-30♦
9 20 2,2 / 3 3,7 / 5 3,7 / 5 4,5 / 6 4,5 / 6 3,7 / 5
0 1 CWC09-01-30♦
0,188
1 0 CWC012-10-30♦
12 22 3/4 5,5 / 7,5 5,5 / 7,5 5,5 / 7,5 5,5 / 7,5 5,5 / 7,5
0 1 CWC012-01-30♦
1 0 CWC016-10-30♦
16 22 3,7 / 5 7,5 / 10 7,5 / 10 7,5 / 10 7,5 / 10 7,5 / 10
0 1 CWC016-01-30♦
22 35 5,5 / 7,5 11 / 15 11 / 15 11 / 15 11 / 15 11 / 15 0 0 CWC025-00-30♦ 0,203
Corrente alternada:
Aplicável ao modelo CW07 Aplicável aos modelos CWC07...25
Código: V05 V73 V16 V25 V40 Código: V04 V10 V15 V26 V41 V42 V47
V(50Hz) 20 42 95 190 325 380 415
V(60Hz) 24 48 110 220 380
V(60Hz) 24 48 110 220 380 440 480
Código: D02 D13 D23 D33 D34 Código: D02 D13 D23 D33 D34 D35 D36
V(50/60Hz) 24 110 220 380 400 V(50/60Hz) 24 110 220 380 400 415 440
Corrente contínua:
Aplicável aos modelos CWC07...16 Aplicável aos modelos CWC07...16
Código: C03 C06 C07 C12 C15 Código: L03 L06 L07 L12 L15
Minicontatores auxiliares
g Fixação por parafusos ou diretamente em trilho DIN 35mm;
g Protegido contra corpos estranhos e toques;
g Alta confiabilidade dos contatos (17V - 5mA);
g Minicontator CWCA0 com bobinas em corrente contínua de baixo consumo permitindo a conexão direta a CLP´s;
Ie máxima
AC-14 / AC-15 DC-13 Nº de contatos auxiliares por contator
(Ue ≤ 230V) (Ue ≤ 24V)
Referência para completar Peso 4)
3 1
com a tensão de comando kg
A A
4 2
NA NF
6 2,5 CAW04-22-00♦ 0,130
2 2
10 6 CWCA0-22-00♦ 0,188
6 2,5 CAW04-31-00♦ 0,130
3 1
10 6 CWCA0-31-00♦ 0,188
6 2,5 CAW04-40-00♦ 0,130
4 -
10 6 CWCA0-40-00♦ 0,188
6 2,5 CAW04-13-00♦ 0,130
1 3
10 6 CWCA0-13-00♦ 0,188
10 6 - 4 CWCA0-04-00♦ 0,188
Corrente alternada:
Aplicável ao modelo CAW04 Aplicável ao modelo CWCA0
Código: V05 V73 V16 V25 V40 Código: V04 V10 V15 V26 V41 V42 V47
V(50Hz) 20 42 95 190 325 380 415
V(60Hz) 24 48 110 220 380
V(60Hz) 24 48 110 220 380 440 480
Código: D02 D13 D23 D33 D34 Código: D02 D13 D23 D33 D34 D35 D36
V(50/60Hz) 24 110 220 380 400 V(50/60Hz) 24 110 220 380 400 415 440
Corrente contínua:
Aplicável ao modelo CWCA0 Aplicável ao modelo CWCA0
Código: C03 C06 C07 C12 C15 Código: L03 L06 L07 L12 L15
g Minicontatores CWC07...16 com bobinas em corrente contínua de baixo consumo permitindo a conexão direta a CLP´s;
Ie = Ith Nº de pólos
(Ue ≤ 690V) 3 1 Referência para Peso 4)
θ ≤ 55°C completar com a
AC-1 tensão de comando kg
4 2
A NA NF
16 1) CW07-00-40♦ 0,130
18 CWC07-00-40♦
20 4 0 CWC09-00-40♦
0,188
22 CWC012-00-40♦
22 CWC016-00-40♦
16 1) CW07-00-22♦ 0,130
18 CWC07-00-22♦
20 2 2 CWC09-00-22♦
0,188
22 CWC012-00-22♦
22 CWC016-00-22♦
Corrente alternada :
Aplicável ao modelo CW07 Aplicável ao modelo CWC07...16
Código: V05 V73 V16 V25 V40 Código: V04 V10 V15 V26 V41 V42 V47
V(50Hz) 20 42 95 190 325 380 415
V(60Hz) 24 48 110 220 380
V(60Hz) 24 48 110 220 380 440 480
Código: D02 D13 D23 D33 D34 Código: D02 D13 D23 D33 D34 D35 D36
V(50/60Hz) 24 110 220 380 400 V(50/60Hz) 24 110 220 380 400 415 440
Corrente contínua:
Aplicável ao modelo CWC0 tetrapolares 4P(4NA) Aplicável ao modelo CWC0 tetrapolares 4P(4NA)
Código: C03 C06 C07 C12 C15 Código: L03 L06 L07 L12 L15
Notas: 1) Ue ≤ 415V
2) Outras tensões disponíveis sob consulta.
3) Os minicontatores CWC0 com bobinas CC de Baixo Consumo somente permitem montagem de 2 contatos auxiliares.
4) Pesos para minicontatores com circuito de comando em corrente alternada. Para minicontatores CWC07...16 em corrente contínua acrescentar 0,030kg
ao peso.
Ie = Ith
Ie Potência nominal de emprego em AC-3 1) Contatos auxiliares
(Ue ≤ 690V)
(Ue ≤ 440V) Motor trifásico - IV pólos - 60Hz - 1800rpm por minicontator
θ ≤ 55ºC Referência para completar Peso 5)
220V 400V 660V 3 1 com a tensão de comando kg
AC-3 AC-1
230V 380V 415V 440V 500V 690V
4 2
A A kW / cv kW / cv kW / cv kW / cv kW / cv kW / cv NA NF
1 0 CWI07-10-30♦
7 2) 16 2) 1,5 / 2 3/4 3/4 - - - 0,275
0 1 CWI07-01-30♦
1 0 CWCI07-10-30♦
7 18 1,5 / 2 3/4 3/4 3,7 / 5 3,7 / 5 3/4
0 1 CWCI07-01-30♦
1 0 CWCI09-10-30♦
9 20 2,2 / 3 3,7 / 5 3,7 / 5 4,5 / 6 4,5 / 6 3,7 / 5
0 1 CWCI09-01-30♦
0,395
1 0 CWCI012-10-30♦
12 22 3/4 5,5 / 7,5 5,5 / 7,5 5,5 / 7,5 5,5 / 7,5 5,5 / 7,5
0 1 CWCI012-01-30♦
1 0 CWCI016-10-30♦
16 22 3,7 / 5 7,5 / 10 7,5 / 10 7,5 / 10 7,5 / 10 7,5 / 10
0 1 CWCI016-01-30♦
Corrente alternada:
Aplicável ao modelo CWI07 Aplicável ao modelo CWCI07...16
Códigos de tensões Y05 Y73 Y16 Y25 Y40 Código: V04 V10 V15 V26 V41 V42 V47
V(50Hz) 20 42 95 190 325 380 415
V(60Hz) 24 48 110 220 380
V(60Hz) 24 48 110 220 380 440 480
Corrente contínua:
Aplicável ao modelo CWCI07...16 Aplicável ao modelo CWCI07...16
Código: C03 C06 C07 C12 C15 Código: L03 L06 L07 L12 L15
Minicontatores auxiliares
Ie máxima
AC-14 / AC-15 DC-13 Nº de contatos auxiliares por contator
(Ue ≤ 230V) (Ue ≤ 24V) Peso
Referência para completar
3 4)
1
com a tensão de comando
A A kg
4 2
NA NF
10 6 2 2 CWCHA0-22-00♦
10 6 3 1 CWCHA0-31-00♦
10 6 4 - CWCHA0-40-00♦ 0,377
10 6 1 3 CWCHA0-13-00♦
10 6 - 4 CWCHA0-04-00♦
Ie = Ith
Ie Potência nominal de emprego em AC-3 1) Contatos auxiliares
(Ue ≤ 690V)
(Ue ≤ 440V) Motor trifásico - IV pólos - 60Hz - 1800rpm por minicontator
θ ≤ 55ºC Referência para completar Peso 5)
220V 400V 660V 3 1 com a tensão de comando kg
AC-3 AC-1
230V 380V 415V 440V 500V 690V
4 2
A A kW / cv kW / cv kW / cv kW / cv kW / cv kW / cv NA NF
1 0 CW07-10-30♦I
7 2) 16 2) 1,5 / 2 3/4 3/4 - - - 0,150
0 1 CW07-01-30♦I
1 0 CWC07-10-30♦I
7 18 1,5 / 2 3/4 3/4 3,7 / 5 3,7 / 5 3/4
0 1 CWC07-01-30♦I
1 0 CWC09-10-30♦I
9 20 2,2 / 3 3,7 / 5 3,7 / 5 4,5 / 6 4,5 / 6 3,7 / 5
0 1 CWC09-01-30♦I
0,215
1 0 CWC012-10-30♦I
12 22 3/4 5,5 / 7,5 5,5 / 7,5 5,5 / 7,5 5,5 / 7,5 5,5 / 7,5
0 1 CWC012-01-30♦I
1 0 CWC016-10-30♦I
16 22 3,7 / 5 7,5 / 10 7,5 / 10 7,5 / 10 7,5 / 10 7,5 / 10
0 1 CWC016-01-30♦I
Corrente alternada:
Aplicável ao modelo CW07 Aplicável aos modelos CWC07...16
Código: V05 V73 V16 V25 V40 Código: V04 V10 V15 V26 V41 V42 V47
V(50Hz) 20 42 95 190 325 380 415
V(60Hz) 24 48 110 220 380
V(60Hz) 24 48 110 220 380 440 480
Código: D02 D13 D23 D33 D34 Código: D02 D13 D23 D33 D34 D35 D36
V(50/60Hz) 24 110 220 380 400 V(50/60Hz) 24 110 220 380 400 415 440
Corrente contínua:
Aplicável aos modelos CWC07...16 Aplicável aos modelos CWC07...16
Código: C03 C06 C07 C12 C15 Código: L03 L06 L07 L12 L15
Acessórios
Bloco de contatos auxiliares frontais 1)
Contatos Para uso com CWC0 Para uso com CWC0 Peso
Modelo Número de Para uso com CWCA0
Foto Ilustrativa Auxiliares (3 pólos) (4 pólos)
aplicável pólos kg
NO NC Referência Referência Referência
2 0 BFC025-20 - -
CWC025 2 1 1 BFC025-11 - -
0 2 BFC025-02 - -
Intertravamento mecânico
Peso
Foto Ilustrativa Modelo aplicável Descrição Referência
kg
Montagem frontal;
Permite a função de intertravamento entre 2 minicontatores sem o aumento de
CWC07...16 dimensões (laterais) ao conjunto;
BIC0 0,014
CWCA0 Possibilita a utilização de blocos de contatos auxiliares frontais, blocos
supressores de surto e temporizadores;
Utilizar com intertravamento elétrico.
Nota: 1) Os minicontatores CWC07...16 e CWCA0 com bobinas CC de Baixo Consumo não permitem montagem de 4 contatos auxiliares. Para aplicações que
necessitem de 4 contatos auxiliares utilizar minicontatores com bobina CC de Consumo Normal.
Acessórios
Retenção mecânica
Peso
Foto Ilustrativa Modelo aplicável Descrição Referência
kg
Montagem frontal;
Para o funcionamento deste acessório é necessário a utilização de
2 minicontatores;
Realiza somente a retenção mecânica do minicontator que é
CWC07...16 montado a direita deste acessório;
RMC0 0,014
CWCA0 Possibilita a utilização de blocos de contatos auxiliares frontais,
supressores de surto e temporizadores;
Peso
Foto Ilustrativa Modelo aplicável Diagrama Tensão Referência
kg
CW07
110-220V 50/60Hz RC06 D62 0,014
CAW04
CWC07...16
CWCA0
Peso
Foto Ilustrativa Modelo aplicável Descrição Referência
Kg
Nota: 1) Garante o desligamento seguro de minicontatores com bobina CA, no caso de comando direto através de saídas de equipamentos a semicondutores ou a
relés, protegidos por capacitores em paralelo as chaves(Snubbers). Também realiza a função de supressor de surtos de tensão. Utilizado em circuitos que
possuam correntes residuais maiores que 1,4mA × Us . (Us = tensão nominal) .
230V
Acessórios
Bloco temporizador para minicontatores CWC07...25 e CWCA0
Peso
Foto Ilustrativa Funções Temporizações Tensões (V) Referência
kg
3 0,3 até 3 s TEC0-U003S-E05
10 - 1 até 10 s TEC0-U010S-E05
30 - 3 até 30 s TEC0-U030S-E05
Retardo na Energização
60 - 6 até 60 s 24...240 CA/CC TEC0-U060S-E05
(TECO)
100 - 10 até 100 s TEC0-U100S-E05
300 - 30 até 300 s TEC0-U300S-E05
1800 - 180 até 1800 s TEC0-U030M-E05
- 24...60 V CA/CC 100...240 V CA/CC
3 - 0,3 até 3 s TDC0-U010S-E04 TDC0-U003S-E09
0,02
10 - 1 até 10 s TDC0-U003S-E04 TDC0-U010S-E09
Retardo na 30 - 3 até 30 s 24...60 CA/CC TDC0-U030S-E04 TDC0-U030S-E09
Desenergização (TDCO) 60 - 6 até 60 s 100...240 CA/CC TDC0-U060S-E04 TDC0-U060S-E09
100 - 10 até 100 s TDC0-U100S-E04 TDC0-U100S-E09
300 - 30 até 300 s TDC0-U300S-E04 TDC0-U300S-E09
1800 - 180 até 1800 s TDC0-U030M-E04 TDC0-U030M-E09
24...28 CA TETC0-U030S-D52
Partida Estrela-Triângulo
30 - 3 até 30 s 110...130 CA TETC0-U030S-D61
(TETCO)
220...240 CA TETC0-U030S-D66
Funções Retardo na energização TEC0 Retardo na desenergização TDC0 Partida Estrela-Triângulo TETC0
Diagrama
Funcional
Led Ligado
Led Desligado
B2 Y
Peso
Foto Ilustrativa Modelo aplicável Descrição Referência
kg
Acessórios
Barramentos easy-connection
Chave estrela-triângulo
Potência do motor trifásico (cv) - Regime AC-3 Modelo
4 pólos - 60Hz aplicável Peso
Referência
kg
220V 380V 440V K1 = K2 K3
5 5 5
- 6 6 CWC07
- 7,5 7,5 CWC07
- - 10 CWC09 ECC0-SD 0,130
6 10 12,5
CWC012
7,5 12,5 15
CWC09
10 15 20 CWC016
Chave reversora
Potência do motor trifásico (cv) - Regime AC-3 Modelo
4 pólos - 60Hz aplicável Bloco de Peso
Referência
Intertravamento kg
220V 380V 440V K1 = K2
1 1 1
1,5 1,5 1,5
2 2 2 CWC07
3 3 3
- 4 4 BIC0 ECC0-R 0,130
- 5 5 CWC09
4 6 6
CWC012
- 7,5 7,5
5 10 10 CWC016
Bobina de reposição para os minicontatores CWC0 Jogo de contatos dos minicontatores CWC0
Tensões de bobina CC
Aplicável ao modelo: CWC0 tetrapolar 2P/2R(2NA+2NF)
Códigos de tensões R03 R06 R07 R12 R15
Vcc 24 42 48 110 220
Dados Técnicos
Numeração dos contatos
- - - CWC025-00-30♦
Minicontatores auxiliares
13 23 33 43
CAW04-40-00♦
40 1 0
CWCA0-40-00♦
14 24 34 44
CAW04-31-00♦
31 0 1
CWCA0-31-00♦
CAW04-22-00♦
22 1 0
CWCA0-40-00♦
CAW04-13-00♦
13 0 1
CWCA0-13-00♦
CAW04-04-00♦
04 0 1
CWCA0-04-00♦
22 2 2 CW07-00-22♦
2 R2 R4 4
1 3 R1 R3 CWC07-00-22♦
CWC09-00-22♦
22 2 2
CWC012-00-22♦
2 4 R2 R4
CWC016-00-22♦
Dados Técnicos
Numeração dos contatos
BFC0-20
2 0 BFC4-20 BFCA-20
BFC025-20
BFC0-11
2 1 1 BFC4-11 BFCA-11
BFC025-11
BFC0-02
0 2 BFC4-02 BFCA-02
BFC025-02
Dados Técnicos
Dados básicos
Modelos CAW04 CW07 CWCA0 CWC07 CWC09 CWC012 CWC016 CWC025
Conformidade às normas IEC/EN 60947-1, IEC/EN 60947-4, DIN VDE 0660(102), UL508
Tensão nominal de isolação Ui IEC/EN 60947-4-1, VDE 0660 (V) 415 690
(Grau de poluição 3) UL, CSA (V) 600
Tensão nominal de impulso Uimp (IEC/EN 60947-1) (kV) 4
Limites de frequência (Hz) 25...400
Vida mecânica Bobina CA (milhões de manobras) 4 10 3
Bobina CC (milhões de manobras) - 12 -
Vida elétrica Ie AC-3 (milhões de manobras) - 0,7 - 1,4 1,3 1,2 1,1 0,6
Grau de proteção (VDE 0160) Terminais principais IP20
Bobina e contatos auxiliares IP20
Montagem Parafusos ou trilho DIN 35 mm (EN 50022)
Pontos de conexão a bobina 2
Resistência a vibrações Contator aberto (g) 2 2
Contator fechado (g) 3 4
Resistência a choques mecânicos Contator aberto (g) 4 6
(½ senóide = 11ms) Contator fechado (g) 6 10
Temperatura ambiente Operação -25ºC ...+55ºC
Armazenagem -55ºC ... +80ºC
Altitude máxima de utilização sem alteração dos valores nominais 3000 m
Dados Técnicos
Contatos principais
Modelos CW07 CWC07 CWC09 CWC012 CWC016 CWC025
Corrente nominal de emprego Ie AC-3 (Ue ≤ 440V) (A) 7(415V) 7 9 12 16 22
AC-4 (Ue ≤ 440V) (A) - 2,8 3,5 4,5 5 9
AC-1 (θ ≤ 55 ºC, Ue ≤ 690V) (A) 16 (415V) 18 20 22 22 32
Tensão nominal de emprego Ue IEC/EN 60947-4-1, VDE 0660 (V) 415 690
UL, CSA (V) 600 600
Corrente térmica convencional Ith (θ ≤ 55ºC) (A) 16 18 20 22 22 32
Capacidade de estabelecimento (Making capacity) - IEC/EN 60947 (A) - 70 90 120 160 250
Capacidade de interrupção (Ue≤400V) (A) - 50 72 96 128 200
(Breaking capacity) (Ue=500V) (A) - 50 72 96 128 200
IEC/EN 60947
(Ue=690V) (A) - 35 54 72 96 150
Corrente temporária admissível 1 seg (A) - 250 250 250 250 -
(Sem condução de corrente 5 seg (A) - 125 125 125 125 -
anteriormente durante 10 min 10 seg (A) - 95 95 95 95 -
com θ ≤ 40 ºC) 30 seg (A) - 70 70 70 70 -
1 min (A) - 50 50 50 50 -
3 min (A) - 40 40 40 40 -
Proteção contra curto-circuito @600V - UL/CSA (kA) 5
dos contatos principais Coordenação Tipo 1 (A) 20 35 35 35 35 50
Fusível(gL/gG) Coordenação Tipo 2 (A) 16 20 20 25 25 35
Impedância média por pólo (mΩ) - 6 6 5 5 6
Potência média dissipada por pólo AC-1 (W) - 1,9 2,4 2,4 2,4 6,1
AC-3 (W) - 0,3 0,5 0,7 1,3 3,8
Categoria de utilização AC-3
Corrente nominal de emprego Ie Ue ≤ 440 V (A) 7(415V) 7 9 12 16 22
(θ ≤ 55ºC) Ue ≤ 500 V (A) - 6,2 7,5 8,8 13 16
Ue ≤ 690 V (A) - 4,5 5,5 6,6 10 13
Ue ≤ 1000 V (A) Não disponível
Valores orientativos de potência 220 / 230 V (kW) 1,5 1,5 2,2 3 3,7 5,5
(cv) 2 2 3 4 5 7,5
Motores de indução trifásico (50/60Hz) 380 / V (kW) 3 3 3,7 5,5 7,5 11
IV pólos - 1800rpm (cv) 4 4 5 7,5 10 15
400 / 415 V (kW) 3 3 3,7 5,5 7,5 11
(cv) 4 4 5 7,5 10 15
440 V (kW) - 3,7 4,5 5,5 7,5 11
(cv) - 5 6 7,5 10 15
500 V (kW) - 3,7 4,5 5,5 7,5 11
(cv) - 5 6 7,5 10 15
660 / 690 V (kW) - 3 3,7 5,5 7,5 11
(cv) - 4 5 7,5 10 15
Frequência máxima 600 ops./h (%) - 100 100 100 100 100
de ciclos de manobras 1200 ops./h (%) - 75 75 75 75 75
3000 ops./h (%) - 50 50 50 50 50
Categoria de utilização AC-4
Corrente nominal de emprego Ie AC-4 (Ue ≤ 440V) (A) - 2,8 3,5 4,5 5 9
Valores orientativos de potência 220 / 230 V (kW) - 0,55 0,75 0,75 1,1 2,2
(cv) - 0,7 1 1 1,5 2,9
Motores de indução trifásico (50/60Hz) 380 / 400 V (kW) - 1,1 1,1 1,8 2,2 4
IV pólos - 1800rpm (cv) - 1,5 1,5 2,4 2,9 5,4
(200.000 operações) 415 V (kW) - 1,1 1,5 2,2 2,2 4,5
(cv) - 1,5 2 2,9 2,9 6
440 V (kW) - 1,1 1,5 2,2 2,2 4,5
(cv) - 1,5 2 2,9 2,9 6
500 V (kW) - 1,1 1,5 2,2 2,2 4,5
(cv) - 1,5 2 2,9 2,9 6
660 / 690 V (kW) - 1,1 1,5 2,2 2,2 4,5
(cv) - 1,5 2 2,9 2,9 6
Dados Técnicos
Contatos principais
CW07 CWC07 CWC09 CWC012 CWC016 CWC025
Modelos Categoria de utilização AC-1
3P(NA) ou 4P(4NA) 3P(NA)
Corrente térmica convencional Ith (θ ≤ 55ºC) (A) 16 18 20 22 22 32
Máxima corrente de emprego segundo a θ ≤ 40ºC (A) 16 18 20 22 22 32
temperatura ambiente (até 690V) θ ≤ 55ºC (A) 16 18 20 22 22 32
θ ≤ 70ºC (A) - 14,4 16 17,6 17,6 25,6
Potência máxima de emprego 220 / 230 V (kW) 6 6,8 7,5 8,3 8,3 12
θ ≤ 55ºC 380 / 400 V (kW) 10 11,5 13 14,5 14,5 21
(Resistores trifásicos)
415 / 440 V (kW) - 13 14,5 16 16 23
500 V (kW) - 14,8 16.5 18 18 26
660 / 690 V (kW) - 20 22 25 25 36
Valores atuais para conexão 2 pólos em paralelo Ie x 1,7
3 pólos em paralelo Ie x 2,4
4 pólos em paralelo Ie x 3,2
Frequência máxima de ciclos de manobras 600 ops./h (%) 100
1200 ops./h (%) 60 100
3000 ops./h (%) -
2P(NA/NF) ou 4P(2NA + 2NF) 2P(NA/NF)
Potência máxima de emprego 220 / 230 V (kW) 6 3,9 4,4 4,8 4,8 6,6
θ ≤ 55ºC 380 / 400 V (kW) 10 6,8 7,6 8,4 8,4 11,4
(Carga resistiva)
415 / 440 V (kW) - 7,5 8,4 9,2 9,2 12,5
500 V (kW) - 8,6 9,5 10,5 10,5 14,5
660 / 690 V (kW) - 11,8 13,1 14,4 14,4 19,5
Dados Técnicos
Contatos auxiliares
Modelo BFC0 / BFC025
Conformidade às normas IEC 60947-5-1, IEC 60947-4-1
Tensão nominal de isolação Ui IEC, VDE 0660 (V) 1000
(Grau de poluição 3) UL, CSA (V) 600
Tensão nominal de emprego Ue IEC, VDE 0660 (V) 690
UL, CSA (V) 600
Corrente térmica convencional Ith (θ ≤ 55ºC) (A) 10
Corrente nominal de emprego Ie
AC-15(IEC 60947-5-1) Ue ≤ 240V (A) 10
380-400V (A) 6
415-440V (A) 6
500V (A) 4
660-690V (A) -
UL, CSA A600
DC-13(IEC 60947-5-1) 24V (A) 1,5
60V (A) 0,5
110V (A) 0,4
220-240V (A) 0,4
UL, CSA Q600
Capacidade de estabelecimento Ue ≤ 400V 50/60Hz - AC-15 (A) 30
Capacidade de Interrupção Ue ≤ 400V 50/60Hz - AC-15 (A) 3
Proteção contra curto-circuito com fusível (gL/gG) (A) 10
Mínima capacidade de manobra (V / mA) 17 / 5
Vida elétrica (milhões de manobras) 1
Vida mecânica (milhões de manobras) 10
Tempo de não sobreposição entre contatos NA e NF (ms) -
Impedância dos contatos (mΩ) 4,7
Dados Técnicos
Categorias de emprego DC-1, DC-3 e DC-5
DC-5(L/R ≤ 15 ms)
1 pólo em série
Modelos CW07 CWC07 CWC09 CWC012 CWC016 CWC025
Pólos em
Ue Corrente nominal de emprego Ie (A)
série
1 1,5 8 8 8 8 10
2 2,5 12 12 12 12 14
≤ 24 V carga
3 3 15 15 15 15 18
4 3 15 15 15 15 -
1 1,5 8 8 8 8 9 2 pólos em série
2 2,5 12 12 12 12 14
≤ 48 V
3 3 15 15 15 15 18
4 3 15 15 15 15 -
1 1,2 5 5 5 5 7
2 2,5 10 10 10 10 12
≤ 60 V
3 3 14 14 14 14 18 carga carga
4 3 15 15 15 15 -
1 0,7 1,5 1,5 1,5 1,5 0,8 3 pólos em série
2 1,5 5,5 5,5 5,5 5,5 5
≤ 125 V
3 2,5 9 9 9 9 12
4 3 14 14 14 14 -
1 0,1 0,4 0,4 0,4 0,4 -
2 0,5 0,7 0,7 0,7 0,7 0,8
≤ 220 V
3 1,5 2,5 2,5 3 3 3
carga carga
4 2,2 9 9 9 9 -
1 - - - - - -
4 pólos em série
2 - - - - - -
≤ 440 V
3 0,1 0,3 0,3 0,3 0,3 0,5
4 0,3 0,7 0,7 0,7 0,7 -
1 - - - - - -
2 - - - - - -
≤ 600 V
3 - - - - - -
carga carga
4 - 0,2 0,2 0,2 0,2 -
Dados Técnicos
Descrição de funcionamento dos minicontatores com retenção mecânica
ou
Diagrama funcional
A1
K1
Tempo
A2 Tempo mínimo do pulso de ligamento para garantir a
retenção mecânica > 100 ms
E1/A1
K2 Tempo
Tempo mínimo do pulso de desligamento
E2/A2
para garantir o destravamento > 100 ms
g Depois de um pulso na bobina do minicontator K1 pelo tempo mínimo de 100ms o acessório RMC0 mantém retidos os
Observação: Se o minicontator “RESET” K2 se mantiver energizado o sistema de retenção mecânica não fará a retenção mecânica do minicontator K1.
Dados Técnicos
Vida Elétrica
10
CW07 e CAW04
de manobras
de manobras
CWC07
1
Milhões
Milhões
CWC025
CWC016
CWC012
CWC09
CW07
0,1
10
1 7 9 12 16 22
Corrente
Corrente de de desligamento
desligamento Ie (A) Ie (A)
0,1
CWC012
CWC016
CWC025
CWC07
CWC09
0,01
100
10 32 41 54 72 112 200
Dimensões (mm)
CWI07
CW07 ♦ I
Dimensões (mm)
CWCI07...16 1) e CWCH07...16/CWCHA0 2)
CWC07...16♦I 3)
Dimensões (mm)
CWC025
Posição de montagem de
todos minicontatores
30° 30°
360°
Contatores
www.weg.net
Ie = Ith
Ie máx. Potência nominal de emprego em AC-3 1) Contatos auxiliares Bloco de contato auxiliar
(Ue ≤ 690V)
(Ue ≤ 440V) Motor trifásico - IV pólos - 60Hz - 1800rpm por contator fornecido separadamente
θ ≤ 55°C
Referência para
Peso 5)
220V 400V 660V 3 1 completar com a
AC-3 AC-1 kg
230V 380V 415V 440V 500V 690V tensão de comando
BCXMF10 BCXMF01
4 2
A A kW / cv kW / cv kW / cv kW / cv kW / cv kW / cv NA NF
1 - integrado - CWM9-10-30♦
- 1 - integrado CWM9-01-30♦
9 25 2,2 / 3 3,7 / 5 3,7 / 5 4,5 / 6 4,5 / 6 5,5 / 7,5 0,360
1 1 integrado 1 CWM9-11-30♦
2 2 1 2 CWM9-22-30♦
1 - integrado - CWM12-10-30♦
- 1 - integrado CWM12-01-30♦
12 25 3/4 5,5 / 7,5 5,5 / 7,5 5,5 / 7,5 5,5 / 7,5 7,5 / 10 0,360
1 1 integrado 1 CWM12-11-30♦
2 2 1 2 CWM12-22-30♦
1 - integrado - CWM18-10-30♦
- 1 - integrado CWM18-01-30♦
18 32 4,5 / 6 7,5 / 10 7,5 / 10 9,2 / 12,5 9,2 / 12,5 11 / 15 0,360
1 1 integrado 1 CWM18-11-30♦
2 2 1 2 CWM18-22-30♦
- - - - CWM25-00-30♦
1 - 1 - CWM25-10-30♦
25 45 5,5 / 7,5 11 / 15 11 / 15 11 / 15 11 / 15 11 / 15 - 1 - 1 CWM25-01-30♦ 0,330
1 1 1 1 CWM25-11-30♦
2 2 2 2 CWM25-22-30♦
- - - - CWM32-00-30♦
1 - 1 - CWM32-10-30♦
32 60 9,2 / 12,5 15 / 20 15 / 20 15 / 20 15 / 20 18,5 / 25 - 1 - 1 CWM32-01-30♦ 0,620
1 1 1 1 CWM32-11-30♦
2 2 2 2 CWM32-22-30♦
- - - - CWM40-00-30♦
40 60 11 / 15 18,5 / 25 18,5 / 25 22 / 30 22 / 30 22 / 30 1 1 1 1 CWM40-11-30♦ 0,650
2 2 2 2 CWM40-22-30♦
Código: D02 D07 D13 D23 D25 D33 D34 D35 D36
V(50/60Hz) 24 28 110 220 240 380 400 415 440
Corrente Contínua:
Código(CWM9...25): C02 C03 C07 C12 C13 C15 Código(CWM32/40): C34 C37 C40 C44
Vcc 12 24 48 110 125 220 Vcc 24-28 42-50 110-130 208-240
Notas: 1) Valores orientativos
2) Outras tensões sob consulta
3) Blocos de contatos auxiliares e demais acessórios ver página 35.
4) Para maiores informações consulte a seção Dados Técnicos na página 42.
5) Pesos para contatores com circuito de comando em corrente alternada. Para circuito de comando em corrente contínua acrescentar 0,200 kg aos
modelos CWM9...25 e 0,020kg aos modelos CWM32/40 em corrente alternada.
g Sistema “Box” (grampo de conexão duplo) nos contatos principais, para conexão perfeita de condutores com seções
diferentes;
g Possibilidade de acrescentar até 8 contatos auxiliares.
Ie = Ith
Ie máx. Potência nominal de emprego em AC-3 1) Contatos auxiliares Bloco de contato auxiliar
(Ue ≤ 690V)
(Ue ≤ 440V) Motor trifásico - IV pólos - 60Hz - 1800rpm por contator fornecido separadamente
θ ≤ 55°C
Referência para
Peso 5)
220V 400V 660V 3 1 completar com a
AC-3 AC-1 kg
230V 380V 415V 440V 500V 690V tensão de comando
BCXMF10 BCXMF01
4 2
A A kW / cv kW / cv kW / cv kW / cv kW / cv kW / cv NA NF
- - - - CWM50-00-30♦
50 90 15 / 20 22 / 30 22 / 30 22 / 30 30 / 40 30 / 40 1 1 1 1 CWM50-11-30♦ 1,205
2 2 2 2 CWM50-22-30♦
- - - - CWM65-00-30♦
65 110 18,5 / 25 30 / 40 30 / 40 37 / 50 37 / 50 40 / 50 1 1 1 1 CWM65-11-30♦ 1,215
2 2 2 2 CWM65-22-30♦
- - - - CWM80-00-30♦
80 110 22 / 30 37 / 50 37 / 50 45 / 60 45 / 60 45 / 60 1 1 1 1 CWM80-11-30♦ 1,220
2 2 2 2 CWM80-22-30♦
- - - - CWM95-00-30♦
95 140 22 / 30 45 / 60 55 / 75 55 / 75 55 / 75 55 / 75 1 1 1 1 CWM95-11-30♦ 1,500
2 2 2 2 CWM95-22-30♦
- - - - CWM105-00-30♦
105 140 30 / 40 55 / 75 55 / 75 55 / 75 55 / 75 65 / 90 1 1 1 1 CWM105-11-30♦ 1,525
2 2 2 2 CWM105-22-30♦
Código: D02 D07 D13 D23 D25 D33 D34 D35 D36
V(50/60Hz) 24 28 110 220 240 380 400 415 440
Corrente Contínua:
Código: C34 C37 C40 C44
Vcc 24-28 42-50 110-130 208-240
g Permite a troca dos contatos principais sem necessitar retirar cabos de ligação;
g Contatores CWM112, CWM180 e CWM250 com possibilidade de bobinas convencionais CA ou com módulo eletrônico CA/CC.
Código: D02 D07 D13 D23 D25 D33 D34 D35 D36
V(50/60Hz) 24 28 110 220 240 380 400 415 440
Ie = Ith Nº de pólos
(Ue ≤ 690V) 3 1 Referência para
Peso 4)
θ ≤ 55°C completar com a
kg
AC-1 4 2
tensão de comando
A NA NF
2 2 CWM9-00-22♦
25 0,360
4 - CWM9-00-40♦
2 2 CWM12-00-22♦
25 0,360
4 - CWM12-00-40♦
2 2 CWM18-00-22♦
32 0,360
4 - CWM18-00-40♦
Corrente Alternada:
Código: V04 V06 V10 V11 V15 V18 V26 V30 V32 V37 V41 V42 V45 V46 V47 V50
V(50Hz) 20 24 42 48 95 110 190 208 220 240 325 380 - 400 415 440
V(60Hz) 24 28 48 56 110 120 220 240 255 277 380 440 400 460 480 510
Código: D02 D07 D13 D23 D25 D33 D34 D35 D36
V(50/60Hz) 24 28 110 220 240 380 400 415 440
Corrente Contínua:
Código: C02 C03 C07 C12 C13 C15
Vcc 12 24 48 110 125 220
Notas: 1) Outras tensões sob consulta
2) Blocos de contatos auxiliares e demais acessórios, ver página 35.
3) Para maiores informações consulte a seção Dados Técnicos na página 42.
4) Pesos para contatores com circuito de comando em corrente alternada. Para circuito de comando em corrente contínua acrescentar 0,210kg ao peso.
Acessórios
Bloco de contatos auxiliares frontais
1 0 BCXMF10
4 / CWM9...25
0 1 BCXMF01
4 / CAWM4
CWM9...105,
0,016
CAWM4
6 / CWM32/40
1# 0 BCXMFA10
8 / CWM50...105
0 1† BCXMFR01
2 0 BCXML20
4 / CWM9...25
4 / CAWM4
1 1 BCXML11
CWM9...300
6 / CWM32/40 0,055
CAWM4
2 0 BCXMRL20 *
8 / CWM50...105
8 / CWM112...300
1 1 BCXMRL11 *
BCXML11 CWME800
BCXMRL11 CWME800 *
Acessórios
Supressores de surto - Conexão direta aos terminais A1-A2 1)
Peso
Foto ilustrativa Uso com Tensões Diagrama Referência
kg
24 - 48 Vca 50/60Hz BAMRC4 D53
CWM9...40,
50 - 127 Vca 50/60Hz BAMRC5 D55
CAWM4
130 - 250 Vca 50/60Hz BAMRC6 D63
24 - 48 Vca 50/60Hz BAMRC7 D53
CWM50...105 50 - 127 Vca 50/60Hz BAMRC8 D55
130 - 250 Vca 50/60Hz BAMRC9 D63
24 - 48 Vca 50/60Hz BAMRC13 D53
CWM112...250
50 - 250 Vca 50/60Hz BAMRC14 D56
A1 0,015
CWM9...25,
12 - 600 Vcc BAMDI10 C33
CAWM4
A2
CWM9...105, 270 - 380 Vca 50/60Hz BAMV1 D68
CAWM4 400 - 510 Vca 50/60Hz BAMV2 D73
270 - 380 Vca 50/60Hz BAMV3 D68
CWM112...250
400 - 510 Vca 50/60Hz BAMV4 D73
Intertravamento mecânico
Peso
Foto ilustrativa Uso com Referência
kg
BLIM9-105
CWM9...105, CAWM4 0.050
BLIM.02 2)
Notas: 1) Contatores com módulo eletrônico não necessitam de blocos supressores de surto, pois possuem supressor já integrado ao módulo eletrônico.
2) Permite intertravamento mecânico e elétrico.
Acessórios
Kit de conexão para Partidas Reversoras - “Easy connection”
Acessórios
Protetor dos terminais
Peso
Foto ilustrativa Uso com Descrição Referência
kg
Prensa cabos
Peso
Foto ilustrativa Uso com Descrição Referência
kg
Peso
Foto ilustrativa Uso com Descrição Referência
kg
CWM32 JC CWM32-3P 0,030
CWM40 JC CWM40-3P 0,030
CWM50 JC CWM50-3P 0,080
CWM65 JC CWM65-3P 0,085
CWM80 JC CWM80-3P 0,085
CWM95 JC CWM95-3P 0,130
CWM105 1 jogo = 3 contatos móveis JC CWM105-3P 0,130
CWM112 e 6 contatos fixos JC CWM112-3P 0,165
CWM150 JC CWM150-3P 0,178
CWM180 JC CWM180-3P 0,295
CWM250 JC CWM250-3P 0,465
CWM300 JC CWM300-3P 0,465
CWME400 JC CWME400-3P 1,520
CWME630 JC CWME630-3P 2,270
CWME800 JC CWME800-3P 2,300
Peso
Foto ilustrativa Uso com Descrição Referência
kg
CWM112 CE112 0,510
CWM150 CE150 0,510
1 câmara de extinção tripolar
CWM180 CE180 0,780
CWM250 CE250 1,050
CWM300 CE300 1,050
Acessórios
Bobinas de reposição para contatores tripolares, tetrapolares e auxiliares
Módulo eletrônico
Código: D02 D07 D13 D23 D25 D33 D34 D35 D36
V(50/60Hz) 24 28 110 220 240 380 400 415 440
Dados Técnicos
Numeração dos contatos
CWM9-10
10 1 0 CWM12-10 -
CWM18-10
CWM9-01
01 0 1 CWM12-01 -
CWM18-01
Contatores com contato auxiliar integrado + bloco auxiliar frontal BCXMF10 ou BCXMF01
CWM9-10
11 1 1 CWM12-10 + BCXMF01
CWM18-10
CWM9-10
+ BCXMF10
21 2 1 CWM12-10
+ BCXMF01
CWM18-10
CWM9-10
12 1 2 CWM12-10 + 2 BCXMF01
CWM18-10
CWM9-10
+ 2 BCXMF10
31 3 1 CWM12-10
+ BCXMF01
CWM18-10
CWM9-10
+ 3 BCXMF10
41 4 1 CWM12-10
+ BCXMF01
CWM18-10
CWM9-10
+ BCXMF10
22 2 2 CWM12-10
+ 2 BCXMF01
CWM18-10
CWM9-10
+ 2 BCXMF10
32 3 2 CWM12-10
+ 2 BCXMF01
CWM18-10
CWM9-10
13 1 3 CWM12-10 + 3 BCXMF01
CWM18-10
CWM9-10
+ BCXMF10
23 2 3 CWM12-10
+ 3 BCXMF01
CWM18-10
CWM25-00
11 1 1 a + BCXML11
CWM105-00
CWM25-00
+ BCXML11
31 3 1 a
+ BCXML20
CWM105-00
CWM25-00
+ BCXML11
22 2 2 a
+ BCXML11
CWM105-00
Dados Técnicos
Numeração dos contatos
CWM25-00
- - - a -
CWM105-00
Contatores sem contatos auxiliares integrados + bloco auxiliar frontal BCXMF10 ou BCXMF01
CWM25-00
10 1 0 a + BCXMF10
CWM105-00
CWM25-00
01 0 1 a + BCXMF01
CWM105-00
CWM25-00
+ BCXMF10
11 1 1 a
+ BCXMF01
CWM105-00
CWM25-00
+ 2 BCXMF10
21 2 1 a
+BCXMF01
CWM105-00
CWM25-00
+ BCXMF10
12 1 2 a
+ 2 BCXMF01
CWM105-00
CWM25-00
+ 3 BCXMF10
31 3 1 a
+ BCXMF01
CWM105-00
CWM50-00
+ 4 BCXMF10
41 4 1 a
+ BCXMF01
CWM105-00
CWM25-00
+ 2 BCXMF10
22 2 2 a
+ 2 BCXMF01
CWM105-00
CWM50-00
+ 3 BCXMF10
32 3 2 a
+ 2 BCXMF01
CWM105-00
CWM25-00
+ BCXMF10
13 1 3 a
+ 3 BCXMF10
CWM105-00
CWM50-00
+ 2 BCXMF10
23 2 3 a
+ 3 BCXMF01
CWM105-00
Contatores sem contatos auxiliares integrados + bloco auxiliar lateral BCXML e BCXMRL
CWM112
22 2 2 a + 2 BCXML11
CWM800
53 61 71 83
CWM112
+ 2 BCXML11
44 4 4 a
+ 2 BCXMRL11
54 62 72 84 CWM800
Dados Técnicos
Numeração dos contatos
40 1 0 CAWM4-40-00♦
14 24 34 44
31 0 1 CAWM4-31-00♦
22 1 0 CAWM4-40-00♦
13 0 1 CAWM4-13-00♦
04 0 1 CAWM4-04-00♦
Contatores tetrapolares
1 3 5 7
CWM9-00-40♦
- 4 0 CWM12-00-40♦
CWM18-00-40♦
2 4 6 8
1 R1 R3 3
CWM9-00-22♦
- 2 2 CWM12-00-22♦
CWM18-00-22♦
2 R2 R4 4
Contatos auxiliares
Diagrama Configuração Referência
NA NF
Blocos de contatos frontais
10 1 0 BCXMF10
01 0 1 BCXMF01
10 1 0 BCXMFA10
01 0 1 BCXMFR01
Dados Técnicos
Numeração dos contatos
Contatos auxiliares
Diagrama Configuração Referência
NA NF
Blocos de contatos auxiliares laterais
20 2 0 BCXML20
11 1 1 BCXML11
20 2 0 BCXMRL20
11 1 1 BCXMRL11
11 BCXML11 CWME800
1
1
11 BCXMRL11 CWME800
02 0 2 BLIM.02
Dados Técnicos
Dados básicos
Modelos CAWM4 CWM9 CWM12 CWM18 CWM25 CWM32 CWM40 CWM50 CWM65 CWM80 CWM95 CWM105
Conformidade às normas IEC/EN 60947-1, IEC/EN 60947-4, DIN VDE 0660(102), UL508, CSA C.22.2/14
Tensão nominal de isolação Ui IEC/EN 60947-4-1, VDE 0660 (V) 1000
(Grau de poluição 3) UL, CSA (V) 600
Tensão nominal de impulso Uimp (IEC/EN 60947-1) (kV) 6 8
Limites de frequência (Hz) 25...400
Vida mecânica Bobina CA (milhões de manobras) 10
Bobina CC (milhões de manobras) 12 10
Vida elétrica Ie AC-3 (milhões de manobras) - 1,6 1,8 1,2 1,3 1,2 1,2 1,1 1,3 1,1 1,1 1,0
Grau de proteção (VDE 0160) Terminais principais IP20 IP10
Bobina e contatos auxiliares IP20
Montagem Parafusos ou trilho DIN 35 mm (EN 50022)
Pontos de conexão a bobina Contatores com bobina em CA 4 4 4 3
Contatores com bobina em CC 3 3 4 3
Resistência a vibrações Contator aberto (g) 3 4,5 7 4,5 5
Contator fechado (g) 6 5 9 7
Resistência a choques mecânicos Contator aberto (g) 8 7 6
(½ senóide = 11ms) Contator fechado (g) 12 10
Temperatura ambiente Operação -25ºC ...+55ºC
Armazenagem -55ºC ... +80ºC
Altitude máxima de utilização sem alteração dos valores nominais 3000 m
Dados Técnicos
Contatos principais
Modelos CWM9 CWM12 CWM18 CWM25 CWM32 CWM40 CWM50 CWM65 CWM80 CWM95 CWM105
Corrente nominal de emprego Ie AC-3 (Ue ≤ 440V) (A) 9 12 18 25 32 40 50 65 80 95 105
AC-4 (Ue ≤ 440V) (A) 5 7 8 12 16 18,5 23 30 37 44 50
AC-1 (θ ≤ 55 ºC, Ue ≤ 690V) (A) 25 25 32 45 60 60 90 110 110 140 140
Tensão nominal de emprego Ue IEC/EN 60947-4-1, VDE 0660 (V) 690 1000
UL, CSA (V) 600
Corrente térmica convencional Ith (θ ≤ 55ºC) (A) 25 25 32 45 60 60 90 110 110 140 140
Capacidade de estabelecimento (Making capacity) - IEC/EN 60947 (A) 300 300 300 450 550 550 1000 1000 1000 1280 1280
Capacidade de interrupção (Ue≤400V) (A) 250 250 250 350 450 450 920 920 920 1050 1050
(Breaking capacity) (Ue=500V) (A) 250 250 250 320 450 450 920 920 920 1050 1050
IEC/EN 60947
(Ue=690V) (A) 130 130 130 170 205 205 780 780 780 950 950
Corrente temporária admissível 1 seg (A) 455 455 570 630 1010 1265 1580 2530 2530 3300 3300
(Sem condução de corrente 5 seg (A) 205 205 254 280 450 450 710 1130 1130 1485 1485
anteriormente durante 10 min 10 seg (A) 144 144 180 200 320 400 500 800 800 1050 1050
com θ ≤ 40 ºC) 30 seg (A) 85 85 104 115 185 230 290 460 460 600 600
1 min (A) 60 60 74 80 130 165 205 325 325 430 430
3 min (A) 35 35 46 50 90 100 120 185 185 250 250
Proteção contra curto-circuito @600V - UL/CSA (kA) 5 10
dos contatos principais Coordenação Tipo 1 (A) 50 50 63 63 100 125 200 200 200 250 250
Fusível(gL/gG) Coordenação Tipo 2 (A) 25 35 35 50 63 80 100 125 125 160 200
Impedância média por pólo (mΩ) 2,4 2,4 2,4 1,7 1,3 1,0 0,9 0,9 0,9 0,8 0,8
Potência média dissipada por pólo AC-1 (W) 1,5 1,5 2,5 3,3 4,6 3,4 6,7 10,4 10,4 14,9 14,9
AC-3 (W) 0,2 0,3 0,8 1,0 1,3 1,5 2,1 3,6 5.5 6,9 8,4
Categoria de utilização AC-3
Corrente nominal de emprego Ie Ue ≤ 440 V (A) 9 12 18 25 32 40 50 65 80 95 105
(θ ≤ 55ºC) Ue ≤ 500 V (A) 7,5 10,5 14 19 24 32 38 55 63 79 85
Ue ≤ 690 V (A) 7 9 13 15 22 25 34 44 48 60 80
Ue ≤ 1000 V (A) Não disponível 19 25 30 37 42
Valores orientativos de potência 220 / 230 V (kW) 2,2 3 4,5 5,5 9,2 11 15 18,5 22 22 30
(cv) 3 4 6 7,5 12,5 15 20 25 30 30 40
Motores de indução trifásico (50/60Hz) 380 / V (kW) 3,7 5,5 7,5 11 15 18,5 22 30 37 45 55
IV pólos - 1800rpm (cv) 5 7,5 10 15 20 25 30 40 50 60 75
400 / 415 V (kW) 3,7 5,5 7,5 11 15 18,5 22 30 37 45 55
(cv) 5 7,5 10 15 20 25 30 40 50 60 75
440 V (kW) 4,5 5,5 9,2 11 15 22 30 37 45 55 55
(cv) 6 7,5 12,5 15 20 30 40 50 60 75 75
500 V (kW) 4,5 5,5 9,2 11 15 22 30 37 45 55 55
(cv) 6 7,5 12,5 15 20 30 40 50 60 75 75
660 / 690 V (kW) 5,5 7,5 11 11 18,5 22 30 37 45 55 55
(cv) 7,5 10 15 15 25 30 40 50 60 75 75
Frequência máxima 600 ops./h (%) 100 100 100 100 100 100 100 100 100 100 100
de ciclos de manobras 1200 ops./h (%) 100 100 100 100 100 100 100 100 100 75 75
3000 ops./h (%) 35 35 35 35 35 35 35 35 35 25 25
Categoria de utilização AC-4
Corrente nominal de emprego Ie AC-4 (Ue ≤ 690V) (A) 5 7 8 12 16 18,5 23 30 37 44 50
Valores orientativos de potência 220 / 230 V (kW) 1,1 1,5 1,5 3 3,7 4,5 5,5 7,5 9,2 11 11
(cv) 1,5 2 2 4 5 6 7,5 10 12,5 15 15
Motores de indução trifásico (50/60Hz) 380 / 400 V (kW) 2,2 3 3,7 5,5 7,5 9,2 11 15 18,5 22 22
IV pólos - 1800rpm (cv) 3 4 5 7,5 10 12,5 15 20 25 30 30
(200.000 operações) 415 V (kW) 2,2 3,7 4,5 5,5 9,2 11 11 15 22 22 30
(cv) 3 5 6 7,5 12,5 15 15 20 30 30 40
440 V (kW) 2,2 3,7 4,5 5,5 9,2 11 11 15 22 22 30
(cv) 3 5 6 7,5 12,5 15 15 20 30 30 40
500 V (kW) 3 3,7 5,5 7,5 9,2 11 15 18,5 22 22 30
(cv) 4 5 7,5 10 12,5 15 20 25 30 30 40
660 / 690 V (kW) 3 4,5 5,5 7,5 11 11 15 18,5 22 30 30
(cv) 4 6 7,5 10 15 15 20 25 30 40 40
Dados Técnicos
Contatos principais
CWM9 CWM12 CWM18 CWM25 CWM32 CWM40 CWM50 CWM65 CWM80 CWM95 CWM105
Modelos Categoria de utilização AC-1
3P(NA) ou 4P(4NA) 3P(NA)
Corrente térmica convencional Ith (θ ≤ 55ºC) (A) 25 25 32 45 60 60 90 110 110 140 140
Máxima corrente de emprego segundo a θ ≤ 55ºC (A) 25 25 32 45 60 60 90 110 110 140 140
temperatura ambiente (até 690V) θ ≤ 70ºC (A) 20 20 25 32 48 48 72 88 88 110 110
θ ≤ 75ºC (A) 17 17 22 26 42 42 63 77 77 95 95
Potência máxima de emprego 220 / 230 V (kW) 9,5 9,5 12 17 22,5 22,5 34 42 42 53 53
θ ≤ 55ºC 380 / 400 V (kW) 16,5 16,5 21 29,5 39,5 39,5 59 72,5 72,5 92 92
(Resistores trifásicos)
415 / 440 V (kW) 19 19 24 34 45,5 45,5 68,5 84 84 106,5 106,5
500 V (kW) 21,5 21,5 27,5 39 52 52 77 95 95 121 121
575 / 600 V (kW) 24,1 24,1 30,9 43,4 57,9 57,9 86,8 106,1 106,1 135,1 135,1
660 / 690 V (kW) 28,5 28,5 38 51 68,5 68,5 100 125 125 160 160
Seção do cabo (mm²) 4 4 6 10 16 16 35 35 35 50 50
Valores atuais para conexão 2 pólos em paralelo I e x 1,7
3 pólos em paralelo Ie x 2,4
4 pólos em paralelo Ie x 3,2
Frequência máxima de ciclos de manobras 600 ops./h (%) 100 100 100 100 100 100 100 100 100 100 100
1200 ops./h (%) 100 100 100 100 100 100 100 100 100 80 80
3000 ops./h (%) 50 50 50 50 50 50 50 50 50 40 40
2P(NA/NF) ou 4P(2NA + 2NF) 2P(NA/NF)
Potência máxima de emprego 220 / 230 V (kW) 5,5 5,5 7,04 9,9 13,2 14,9 22,2 27,5 27,5 34,1 34,1
θ ≤ 55ºC 380 / 400 V (kW) 9,5 9,5 12,1 17,1 22,8 25,8 38,6 47,5 47,5 58,9 58,9
(Carga resistiva)
415 / 440 V (kW) 10,3 10,3 13,2 18,6 24,9 28,2 42,3 51,8 51,8 64,3 64,3
500 V (kW) 12,5 12,5 16 22,5 30 34 50,6 62,5 62,5 77,5 77,5
660 / 690 V (kW) 16,5 16,5 21,1 29,7 39,6 44,8 66 82,5 82,5 102,3 102,3
Dados básicos
Dados Técnicos
Circuito de Comando - Corrente Alternada (CA)
Dados Técnicos
Contatos principais
Dados Técnicos
Contatos principais
Dados Técnicos
Contatos auxiliares
Dados Técnicos
Capacidade dos terminais e torques de aperto - Circuito de potência
Dados Técnicos
Capacidade dos terminais e torques de aperto - Circuito de comando
Dados básicos
Dados Técnicos
Contatos principais
Dados Técnicos
Bloco de Contatos Auxiliares
Modelos CWME400...800
Tipo do parafuso do sistema de fixação M4
Fenda / Philips
Seção dos Condutores
Fio / Cabo com ou sem terminal (mm²) 2 x 1...2,5
AWG 17...13
Torque (Nm) 2,3
Dados Técnicos
Aplicação de contatores em circuitos de iluminação
Notas: 1) Valores orientativos. É extremamente recomendado levar em consideração os valores de capacidade de estabelecimento e os valores da corrente nominal
AC-1 quando dimensionar o contator pela categoria de emprego AC-5b(Manobra de lâmpadas incandescentes)
2) Corrente nominal absorvida de cada lâmpada em sua tensão nominal.
Dados Técnicos
Aplicação de contatores em circuitos de iluminação
Notas: 1) Valores orientativos. É extremamente recomendado levar em consideração os valores de capacidade de estabelecimento e os valores da corrente nominal
AC-1 quando dimensionar o contator pela categoria de emprego AC-5b(Manobra de lâmpadas incandescentes)
2) Corrente nominal absorvida de cada lâmpada em sua tensão nominal.
Dados Técnicos
Aplicação de contatores em circuitos de corrente contínua
Modelos CWM9 CWM12 CWM18 CWM25 CWM32 CWM40 CWM50 CWM65 CWM80 CWM95 CWM105
Ue Pólos em série Corrente nominal de emprego Ie (A)
1 18 18 18 25 32 40 50 65 65 80 80
2 25 25 32 45 60 60 90 110 110 140 140
≤ 24V
3 25 25 32 45 60 60 90 110 110 140 140
4 25 25 32 -
1 15 15 15 20 25 35 45 55 55 70 70
2 25 25 32 45 60 60 90 110 110 140 140
≤ 48V
3 25 25 32 45 60 60 90 110 110 140 140
4 25 25 32 -
1 12 12 12 18 18 32 40 50 50 65 65
2 25 25 32 45 60 60 90 110 110 140 140
≤ 60V
3 25 25 32 45 60 60 90 110 110 140 140
4 25 25 32 -
1 6 6 6 8 8 8 16 16 16 16 16
2 18 18 18 25 45 45 80 90 90 110 110
≤ 125V
3 25 25 25 32 60 60 90 110 110 140 140
4 25 25 32 -
1 0,8 0,8 0,8 0,8 1 1 2 2 2 2 2
2 7,5 7,5 7,5 8 8 8 20 20 20 20 20
≤ 220V
3 25 25 25 32 50 50 90 110 110 140 140
4 25 25 32 -
1 0,4 0,4 0,4 0,4 0,5 0,5 0,8 0,8 0,8 0,8 0,8
2 0,8 0,8 0,8 0,8 1 1 2 2 2 2 2
≤ 440V
3 8 8 8 10 10 10 15 15 15 15 15
4 15 15 15 -
1 - - - - - - - - - - -
2 0,4 0,4 0,4 0,4 0,5 0,5 1 1 1 1 1
≤ 600V
3 4 4 4 5 5 5 7,5 7,5 7,5 7,5 7,5
4 8 8 10 -
Dados Técnicos
Aplicação de contatores em circuitos de corrente contínua
Modelos CWM9 CWM12 CWM18 CWM25 CWM32 CWM40 CWM50 CWM65 CWM80 CWM95 CWM105
Ue Pólos em série Corrente nominal de emprego Ie (A)
1 12 12 12 18 25 32 40 50 50 65 65
2 18 18 18 25 40 40 65 80 80 105 105
≤ 24V
3 18 18 18 25 40 40 65 80 80 105 105
4 18 18 18 -
1 9 9 9 12 18 20 30 35 35 45 45
2 18 18 18 25 40 40 65 80 80 105 105
≤ 48V
3 18 18 18 25 40 40 65 80 80 105 105
4 18 18 18 -
1 7,5 7,5 7,5 10 15 15 25 30 30 35 35
2 18 18 18 25 40 40 65 80 80 105 105
≤ 60V
3 18 18 18 25 40 40 65 80 80 105 105
4 18 18 18 -
1 0,8 0,8 0,8 0,8 1,2 1,2 1,2 1,2 1,2 1,2 1,2
2 5 5 5 5 5 5 50 60 60 80 80
≤ 125V
3 15 15 15 20 25 32 60 70 70 95 95
4 15 15 18 -
1 - - - - - - 0,5 0,5 0,5 0,5 0,5
2 0,8 0,8 0,8 0,8 0,8 0,8 3 3 3 4 4
≤ 220V
3 3 3 3 3 3 3 7 7 7 7 7
4 10 10 10 -
1 - - - - - - - - - - -
2 - - - - - - - - - - -
≤ 440V
3 0,4 0,5 0,5 0,5 0,7 0,7 1 1 1 1 1
4 1,5 2 2 -
1 - - - - - - - - - - -
2 - - - - - - - - - - -
≤ 600V
3 - - - - - - - - - - -
4 0,5 0,75 0,75 -
Dados Técnicos
Categoria de emprego DC-3 / DC-5 ( L/R ≤ 15 ms )
2 pólos em série
4 pólos em série
Dados Técnicos
Curvas de vida elétrica
CWME400
CWME630
CWME800
CWME400
CWME630
CWME800
Dados Técnicos
Curvas de vida elétrica
Dados Técnicos
Curvas de vida elétrica
CWME400
CWME630
CWME800
400 630 800
CWME400
CWME630
CWME800
Dados Técnicos
Curvas de vida elétrica
CWM105
CWM12
CWM18
CWM25
CWM32
CWM40
CWM50
CWM65
CWM80
CWM95
CWM9
Números de operações (x106)
25 32 45 60 90 110 140
Corrente de desligamento Ie (A)
CWM112
CWM150
CWM180
CWM250
CWM300
Números de operações (x106)
Dimensões (mm)
Bobina CWM9, CWM12, CWM18
CA CC
A = 87 A = 115
DIN 35mm
Bobina CWM25
CA CC
A = 87 A = 117
DIN 35mm
DIN 35mm
DIN 35mm
Dimensões (mm)
Bobina CWM95 e CWM105
CA CC
A = 126 A = 126
DIN 35mm
CWM112 e CWM150
162,5
CWM180
Dimensões (mm)
CWM250 e CWM300
BLIM9-105
Modelos A B C D
CWM9...25 35 72,5 22 102
CWM32/40 45 79 22 122
CWM50...80 57 90 21 144
CWM95/105 57 90 29,8 153
BLIM112-300
Modelos A B C D
CWM112/150 100 130 51 272,5
CWM180 110 160 58,5 303,5
CWM250/300 120 180 57 325,4
Posição de montagem
CWM9...105 CWM112...300
°
30
30°
30
° 30°
Dimensões (mm)
CWME400
225
CWME630 e CWME800
Dimensões (mm)
BLIM CWME400
225
BLIM CWME800
Dimensões (mm)
CWME400 + BMJ
Posição de montagem
CWME 400...800
Relés de Sobrecarga
www.weg.net
Montagem em separado
Faixas de corrente Fusível máximo para Peso
ou através de garras aos Diagrama Referência
(A) coordenação Tipo 2 (gL/gG) kg
contatores
63...80 200 RW117-2D3-U080
CWM112 75...97 225 RW117-2D3-U097 0,750
90...112 250 RW117-2D3-U112
100...150 315 RW317-1D3-U150
CWM112...300, 140...215 355 RW317-1D3-U215
1,985
CWME400 200...310 500 RW317-1D3-U310
275...420 710 RW317-1D3-U420
CWME630 400...600 1000 RW407-1D3-U600 1)
3,435
CWME630 e CWME800 560...840 1250 RW407-1D3-U840 1)
Acessórios
Base de montagem individual
Peso
Foto ilustrativa Descrição Uso com os relés Referência
kg
RW27-1D BF27D 0,050
RW67-1D BF67-1D
Permite ao relés de sobrecarga serem montados diretamente através de 0,095
parafusos ou por trilho de montagem DIN 35mm RW67-2D BF67-2D
Peso
Foto ilustrativa Uso com os relés Uso com os contatores Referência
kg
RW117-2D CWM112 GA117D 0,135
CWM150 GA317-1D 0,250
CWM180 GA317-2D 0,270
RW317
CWM250...300 GA317-3D 0,630
CWME400 GA317-10D 0,500
Nota: 1) Modelo RW407 permite conexão através dos terminais de potência ou a utilização da janela de passagem de Ø 32mm do relé, conectando assim os cabos
diretamente ao contator.
Dados Técnicos
Observações Gerais:
Descrição:
Os relés de sobrecarga bimetálicos protegem cargas contra o aquecimento indevido causado por sobrecarga ou falta de fase.
Quando temos uma sobrecarga ou uma falta de fase no circuito ocorre um aumento na corrente do motor. Esta elevação de
corrente causa o acionamento do mecanismo de disparo que atuará sobre os contatos auxiliares 95-96(NF) e 97-98(NA).
Os contatos auxiliares desligam a carga por meio de um contator. O tempo para o desligamento é uma função da corrente de
disparo em relação à corrente ajustada, que se encontra devidamente representada na curva de disparo do relé.
Após o desarme, deve-se aguardar o restabelecimento do sistema para que se faça o rearme, que pode ser feito de forma
manual ou automática.
Aplicações:
Os relés de sobrecarga bimetálicos RW foram projetados para a proteção de motores trifásicos e monofásicos em CA, e para
motores em CC. Se os relés de sobrecarga RW forem utilizados na proteção de cargas monofásicas em CA ou cargas em
CC, os esquemas de ligação apresentados neste catálogo deverão ser respeitados.
Nas aplicações de relés de sobrecarga em partida estrela-triângulo deve-se observar que pelo contator passará uma corrente
correspondente a um fator de 0,577(√3 / 3) x Inmotor. O relé de sobrecarga acoplado ao contator de rede deverá ser ajustado
então a um fator de 0,577(√3 / 3) x Inmotor.
Condições climáticas:
Os relés de sobrecarga bimetálicos RW têm compensação de temperatura atuando conforme as normas IEC60947-4-1 e DIN
VDE0660 Parte 102, na faixa de temperatura entre –20°C e +60°C. Para temperaturas acima de +60°C até +80°C, deverá ser
utilizado um fator de correção, de acordo com a tabela abaixo.
Dados Técnicos
Sensibilidade contra falta de fase:
De acordo com a norma IEC 60947-4-1, quando dois pólos do relé possuirem sobrecargas de 15% e um dos pólos zero de
corrente, o relé de sobrecarga deverá desarmar/disparar em menos de 2 horas.
Para proteção efetiva contra falta de fase deverão ser avaliados produtos específicos para esta função o qual permitem a
detecção em poucos segundos a partir de uma falta de fase.
Curva característica de disparo é a relação entre tempo e corrente de desarme, na forma de múltiplos da corrente de ajuste
para cargas trifásicas simétricas funcionando a partir do estado a frio.
Os limites da corrente de disparo, nos relés de sobrecarga bimetálicos RW para cargas trifásicas simétricas se situam entre
105% e 120% da corrente de ajuste.
A curva característica de disparo de um relé de sobrecarga RW é válida quando as três fases estiverem sob a mesma
intensidade de corrente. Se ocorrer uma falta de fase, o tempo de desarme será mais longo ou um valor maior de corrente
será necessário para que o mecanismo dispare. Este valor maior de corrente necessário pode resultar em um dano à carga
se prevalecer durante muito tempo. Para evitar isso, os relés de sobrecarga bimetálicos RW são equipados com um sensor
de falta de fase, que acelera a atuação das duas fases ativas sobre o mecanismo de disparo, mantendo as características da
curva de disparo adequada.
A curva a seguir mostra valores médios da faixa de tolerância, com temperatura ambiente de 20ºC partindo do estado frio. Ela
mostra o tempo de disparo em relação à corrente nominal. Para uma temperatura de operação diferente, o tempo de disparo
do relé térmico reduz-se para aproximadamente 25% do apresentado.
Bipolar Tripolar
seg
(A)
Ajuste de corrente
Dados Técnicos
Tecla Reset + Multifunção
Tempo de rearme:
Os relés de sobrecarga bimetálicos RW necessitam de um determinado tempo para o resfriamento dos bimetálicos após o
disparo. Somente após este tempo o relé poderá ser rearmado.
Este intervalo de tempo é uma função da curva de disparo e da intensidade da corrente de disparo. Após a atuação do relé
por sobrecarga a carga se resfria durante o intervalo de tempo de rearme do relé.
Os relés de sobrecarga bimetálicos RW17, RW27, RW67 e RW117 podem operar com inversores de freqüência.
Dependendo da freqüência de operação do inversor, deverá ser feito um ajuste de corrente maior do que a corrente nominal
do motor, em função de correntes parasitas e de efeitos peliculares de corrente.
Dados Técnicos
Dados básicos
Contatos principais
Dados Técnicos
Circuito Auxiliar
Modelos RW17 RW27 RW67 RW117 RW317 RW407
Conformidade às normas IEC 60 947-4-1, VDE 0660, CSA C.22.2/14 e UL508
Tensão nominal de isolação Ui IEC, VDE 0660 (V) 690
(Grau de poluição 3) UL, CSA (V) 600
IEC, VDE 0660 (V) 690
Tensão nominal de emprego Ue
UL, CSA (V) 600
Corrente térmica convencional Ith (θ ≤ 55ºC) (A) 6
Corrente nominal de emprego Ie
AC-14/AC-15(IEC 60947-5-1) 24V (A) 4
60V (A) 3,5
125V (A) 3
230V (A) 2
400V (A) 1,5
500V (A) 0,5
690V (A) 0,3
UL, CSA C600
DC-13/DC-14(IEC 60947-5-1) 24V (A) 1
60V (A) 0,5
110V (A) 0,25
220V (A) 0,1
UL, CSA R300
Proteção contra curto-circuito com fusível (gL/gG) (A) 6
C
Sextavado Sextavado Sextavado
Cabo com terminal (mm²) 2 x (20x4) 2 x (25x5) 2x(60x10)
Barramentos(AxBxC) (mm) B
20x18,5x12,5 25x18,5x12,5 31,7x28,3x15
Torque (Nm) 14...26 23...26 23...26
Dados Técnicos
Esquemas de ligação
Unipolar Bipolar
+ -
1 3 5
K1
1 3 5 2 4 6
K1
2 4 6
_M
1 3 5
_M
1 3 5 FT1
FT1 2 4 6
2 4 6
Tripolar Bipolar
L1 L2 L3 L1 L2
1 3 5 1 3 5
K1 K1
2 4 6 2 4 6
1 3 5
1 3 5
FT1
FT1
2 4 6
2 4 6
U1 V1 W1 U1/T1 U2/T3
M M
3~ 1~
L1 L1
1
0
2
3 13
I K1 1 1
F R
4 14 2 2
3 13 3 13
R K1 F K2
4 14 4 14
95
FT1
96
21 21
K2 K1
A2 22 22
K1 A2 A2
A1 K1 K2
A1 A1
1
0
95
2
FT1
96
N N
Dimensões (mm)
RW17-1D RW17-2D
2A
DIN
RW27D 35mm
2A
RW67-1D RW67-2D
81
50,4
50,4
Dimensões (mm)
RW67 + BF67
DIN
35mm
RW67D
125A
RW67
RW117-1D RW117-2D
DIN
35mm
200A
200A
Dimensões (mm)
RW317
Ranges de correntes A B
100...150A
39 20
140...215A
200...310A
45 25
275...420A
RW407
Dimensões (mm)
CW07 + RW17-1D
4545 45 45
82,9 85,2
82,9
22,6 82,9 22,6 22,6
22,6
32,4
32,4
32,4
32,4
108,4
108,4
108,4
108,4
22
2
CWC07...16 + RW17-1D
CWC025 + RW17-2D
Dimensões (mm)
CWM9...25 + RW27
CWM9...25 A
Bobina CA 94
A Bobina CC 124
CWM32 + RW27
CWM32 A
Bobina CA 98
Bobina CC 118
Dimensões (mm)
CWM32/40 + RW67-1D
CWM32/40 A
Bobina CA 106,5
Bobina CC 126,5
CWM50...80 + RW67-2D
CWM50...80 A
Bobina CA 116
Bobina CC 116
Dimensões (mm)
CWM95/105 + RW117-1D
CWM95/105 A
Bobina CA 127,5
Bobina CC 127,5
CWM112 + RW117-2D
CWM112 A B
Bobina convencional - 317,7
Módulo eletrônico 325 317,7
Dimensões (mm)
CWM112/150 + RW317
121,5 166
9,5
100
130
125
2T1 4T2 6T3
GA317-1D
A
B
60,5
40
110
A B
CWM112(Bobina convencional) - 335,5
CWM112/150(Módulo eletrônico) 343 335,5
CWM180 + RW317
Dimensões (mm)
CWM250/300 + RW317
CWME400 + RW317
225
Posição de montagem
GA317-10D
RW17...407
360° 360°
Corrente Continua:
Código(CWMC25): C02 C03 C07 C12 C13 C15 Código(CWMC32...65): C34 C37 C40 C44
Vcc 12 24 48 110 125 220 Vcc 24-28 42-50 110-130 208-240
Acessórios
Bloco de contatos auxiliares frontais *
1 0 BCXMF10
0 1 BCXMF01
Peso
Foto ilustrativa Uso com Tensões Circuito diagrama Referência
kg
24-48 Vca 50/60Hz BAMRC4 D53
CWMC25
50-127 Vca 50/60Hz BAMRC5 D55
CWMC32
130-250 Vca 50/60Hz BAMRC6 D63
24-48 Vca 50/60Hz BAMRC7 D53
CWMC50
50-127 Vca 50/60Hz BAMRC8 D55
CWMC65
130-250 Vca 50/60Hz BAMRC9 D63
A1
A2
Bobinas de reposição
Corrente Contínua:
Código (CWMC25): C02 C03 C07 C12 C13 C15 Código (CWMC32...65): C34 C37 C40 C44
Vcc 12 24 48 110 125 220 Vcc 24-28 42-50 110-130 208-240
Dados Técnicos
Dados básicos
Dados Técnicos
Circuito de Comando - Corrente Contínua (CC)
Modelo BCXMF
Conformidade às normas IEC 60947-5-1, IEC 60947-4-1
Tensão nominal de isolação Ui IEC, VDE 0660 (V) 1000
(Grau de poluição 3) UL, CSA (V) 600
Tensão nominal de emprego Ue IEC, VDE 0660 (V) 690
UL, CSA (V) 600
Corrente térmica convencional Ith (θ ≤ 55ºC) (A) 10
Corrente nominal de emprego Ie
AC-15(IEC 60947-5-1) 110-120V (A) 10
220-230V (A) 10
380-400V (A) 6
415-440V (A) 5
500V (A) 4
660-690V (A) 2
UL, CSA A600
DC-13(IEC 60947-5-1) 24V (A) 4
48V (A) 2
110V (A) 0,7
220V (A) 0,3
440V (A) 0,15
UL, CSA Q600
Capacidade de estabelecimento Ue ≤ 400V 50/60Hz - AC-15 (A) 90
Capacidade de Interrupção Ue ≤ 400V 50/60Hz - AC-15 (A) 60
Proteção contra curto-circuito com fusível (gL / gG) (A) 10
Mínima capacidade de manobra (V / mA) 17 / 5
Vida elétrica (milhões de manobras) 1
Vida mecânica (milhões de manobras) 10
Tempo de não sobreposição entre contatos NA e NF (ms) >1,5
Impedância dos contatos (mΩ) 1,28
Dados Técnicos
Capacidade dos terminais e torques de aperto - Circuito de potência
Modelos CWMC25...65
Tipo do parafuso do sistema de fixação M3,5
Fenda / Philips
Seção dos Condutores
Fio / Cabo com ou sem terminal mm²
2 x 0,5...2,5 ou 1 x 4
Torque Nm 0,8...1,5
Modelos BCXMF
Tipo do parafuso do sistema de fixação M3,5
Fenda / Philips
Seção dos Condutores
Fio / Cabo com ou sem terminal mm² 2 x 0,5...2,5 ou 1 x 4
AWG 12...22 AWG
Torque Nm 0,8 ... 1,5
Dimensões (mm)
CWMC25
A
45
35
Bobina
4,6 CA CC
A=129 A=159
113
58,
81
DIN
35mm
10
CWMC32
A
55
45
Bobina
CA CC
4,5 A=140 A=160
125
79
DIN
59
35mm
8,5
CWMC50 e CWMC65
66 A
58 Bobina
7,5
CA CC
A=158 A=158
56
6
185
90
DIN
35mm
4,5
7,5