HANDBOOK OF
ELECTRICAL INSTALLATION
PRACTICE
HANDBOOK OF
ELECTRICAL
INSTALLATION
PRACTICE
FOURTH EDITION
Edited by
Eur Ing GEOFFREY STOKES
BSc(Hons), CEng, FIEE, FCIBSE
Blackwell
Science
© 2003 by Blackwell Science Ltd,
a Blackwell Publishing Company
Editorial Offices:
9600 Garsington Road, Oxford OX4 2DQ
Tel: 01865 776868
Blackwell Publishing, Inc., 350 Main Street,
Malden, MA 02148-5018, USA
Tel: +1 781 388 8250
Iowa State Press, a Blackwell Publishing
Company, 2121 State Avenue, Ames, Iowa
50014-8300, USA
Tel: +1 515 292 0140
Blackwell Publishing Asia Pty Ltd,
550 Swanston Street, Carlton South,
Victoria 3053, Australia
Tel: +61 (0)3 9347 0300
Blackwell Wissenschafts Verlag,
Kurfürstendamm 57, 10707 Berlin, Germany
Tel: +49 (0)30 32 79 060
The right of the Author to be identified as the
Author of this Work has been asserted in
accordance with the Copyright, Designs and
Patents Act 1988.
All rights reserved. No part of this publication
may be reproduced, stored in a retrieval system,
or transmitted, in any form or by any means,
electronic, mechanical, photocopying, recording
or otherwise, except as permitted by the UK
Copyright, Designs and Patents Act 1988,
without the prior permission of the publisher.
First published 2003 by Blackwell Science Ltd
Library of Congress
Cataloging-in-Publication Data
is available
ISBN 0-632-06002-6
A catalogue record for this title is available
from the British Library
Set in 10 on 12 pt Times
by SNP Best-set Typesetter Ltd., Hong Kong
Printed and bound in Great Britain by
MPG Books Ltd, Bodmin, Cornwall
For further information on
Blackwell Science, visit our website:
www.blackwell-science.com
Contents
xiii
Preface
1
2
3
1
Power Supplies in the UK
g.s. finlay
NETA
Voltage and frequency
System impedance and short-circuit levels
Loading effects on the system
Superimposed signals
Radio teleswitching
System and installation earthing
Protection
Reliability
Embedded generation
Supply arrangements
Intake arrangements
Consumers’ substations
h.v. or l.v. supply
Metering
6
6
8
9
11
12
14
16
17
19
21
24
28
28
28
Substations and Control Rooms
d.m . ba r r
33
Introduction
Substations
Enclosures
Substation cabling
Installation
Erection procedures
33
37
42
45
55
58
Site Distribution Systems
m.g. twitchett
67
Intake arrangements
Site distribution networks
On-site generation
Switchgear
Cables
Cables installation
Provision for maintenance
68
70
72
74
76
77
77
v
vi
4
5
6
7
Contents
System operation
Identification of substations and switchgear
Faults level
Testing and commissioning
79
79
81
83
Cable Management Systems
m. j. dy e r
84
Introduction
Decision making
Definitions
Types of system
Underfloor systems
Cable tray and cable basket
Hybrid systems
Conduit and trunking
Overall considerations
Particular considerations
Segregation
84
86
86
87
88
90
91
92
94
95
96
Electricity on Construction Sites
g. stokes
98
Equipment design and manufacture
Range of equipment
Design of system
Supply systems
Selection of equipment
Cable routing
Construction site lighting
Testing and inspection
Installation maintenance
99
99
107
110
112
117
119
120
121
Standby Power Supplies
g.m. mcdowell
122
Standby diesel generating sets
Batteries for static systems
d.c. standby systems
Alternating current systems
Composite standby systems
122
138
140
146
159
Ground Earthing
t.e. charlton and j.r. wales
162
Introduction
Soil resistivity
Resistivity surveying
Interpreting measurements
162
163
164
167
Contents
8
9
vii
Resistance measurement of electrode systems
Types of earth electrodes
Installation
Standards applicable to earthing practice
174
175
177
179
Cathodic Protection
j.d. thirkettle
180
Introduction
Principles of cathodic protection
Cathodic protection systems
Installation practice
Equipment
Monitoring, inspection and maintenance
Interaction
Protection of steel in concrete
Recent developments
Conclusions
Further information
180
183
186
188
191
193
194
194
195
195
195
Lightning Protection
j. sherlock and p. woods
197
Introduction
Part 1. Protection of structures
Strike probability
Installation of lightning protection
Inspection and testing of a system
Part 2. Protecting electronic systems from lightning
197
197
199
218
219
219
10 Special Installations or Locations
l. d. markwell
Locations containing a bath tub or a shower basin
Swimming pools
Hot air saunas
Construction site installations
Agricultural and horticultural premises
Equipment having high protective conductor currents
Caravans and motor caravans
Caravan site supply arrangements
Highway power supplies and street furniture
11 Electrical Safety
r.t.r. pilling
Legislation
Safe design and installation
Maintenance
248
249
252
255
256
258
261
261
263
264
267
267
273
274
viii
Contents
Training and systems of work
Tools
Buried cables
Overhead lines
Electric shock
Protection from electric shock
Burns
Fires
Explosions
Flammable atmospheres
Conclusion
12 Standards, Specifications and Codes of Practice
m. h. graham
British Electrotechnical Committee (BEC)
British Standards Institution (BSI)
The International Electrotechnical Commission (IEC)
European Committee for Electrotechnical Standardisation
(CENELEC)
The Institution of Electrical Engineers (IEE)
Standards and the law
European Union (EU)
Conclusion
13 Distribution Transformers
k. frewin
275
278
279
280
281
283
293
295
296
298
303
304
305
305
308
310
312
313
315
316
318
Types of transformer
Performance
Tappings and connections
Cooling
Impulse withstand
Operation in tropical climates
Parallel operation
Packaged substations
Protection
Shipment of transformers
Installation
Cabling
Commissioning
Maintenance
318
329
339
343
345
346
347
347
348
350
352
353
354
354
14 Switchgear
a. headley and r.w. b l ow e r
358
Definitions
Circuit-breaking
Medium voltage switchgear
358
360
360
Contents
Types of switching device
Comparison of circuit-breaker types
Specification and testing
High-voltage circuit-breaker switchboards
Erection of switchgear
Electrical testing and commissioning
15 Rotating Machines
g. walton
Motor types
Variable-speed drives
Motor application
Efficiency
Storage
Installation
Commissioning
Maintenance
16 HBC Fuses and Fusegear in Low Voltage Systems
p.g. newbery
HBC fuselinks design and performance
Design of cartridge fuse-links
Overload characteristics
Fuse-holder
Application of HBC fuses
Discrimination and co-ordination
Fuses in high ambient temperatures
Protection against electric shock
Domestic fuse applications
Semiconductor fuse-links
Fuse-links for electricity authority networks
Compact fuses to BS 88: Part 6
Fuse switchgear
Thermal ratings
17 Motor Control Gear
t. fairhall
Contactor
Contactor selection
Product standards for contactors
Overload protection
Starter types
Isolation
Enclosures
ix
364
372
372
380
386
390
394
394
407
413
417
418
418
422
423
427
428
431
436
437
437
440
443
443
446
447
447
448
448
451
453
454
456
460
463
466
471
473
x
Contents
18 Lighting
h.r. king
The nature of light
Units of light measurement
Electric lamps
Control gear and starting
Luminaires (lighting fittings)
Outdoor lighting equipment
Floodlighting calculations
Lighting design for interiors
Emergency lighting
19 Mains Cables
t. l. journeaux
475
475
477
477
484
485
489
490
491
499
502
Cable specifications
Cable conductors
Insulation
Cable construction
Installation
Jointing and terminating
Cable ratings
Testing and fault finding
502
504
506
509
518
521
525
527
20 Selection of Wiring Systems
m. coates
529
Introduction
Wiring systems
Construction of wiring cables and flexibles
Cable enclosure and support systems
Temperature limits
Cable ratings
Factors affecting the selection of types of cable
Installation methods
529
531
536
538
540
541
564
578
21 Control and Protection of Low Voltage Installations
h.r. l ov e g rov e
585
Isolation and switching
Protection
22 Protective Systems
p. r. rosen
Protective system requirements
Unit and non-unit protection
Graded protection
585
590
597
597
599
603
Contents
Unit protection
Transformer protection
Rotating plant
Relay accommodation
Commissioning tests
xi
608
617
623
628
631
23 Power Factor Correction and Tariffs
t. longland
635
Importance of power factor
Theory of power factor correction
Power factor improvement
Economic considerations
Calculation of capacitor size
Practical power factor improvement
Capacitor size related to tariff
Determination of load conditions
Reduced CO2 emissions
Methods of correction
Location of capacitors
Capacitors and harmonics
Installation of capacitors
Capacitor maintenance
635
636
636
637
638
639
644
647
648
648
652
653
654
657
Appendices
I
Main Authoritative Documents
II IP Codes of Ingress Protection (BS EN 60947–1: 1998)
III British Standards
660
661
665
Index
669
Preface
My first task as editor is to acknowledge and thank my predecessors Alan Smith
and Eric Reeves for their work in editing the three previous editions. It is to be
hoped that they will not disapprove of this latest fourth edition.
Since the third edition was published in 1996, developments in many aspects of
the electrical installation industry have continued apace, both on the technological
and Standards fronts. The revolution in electronic microtechnology has made it possible to introduce more complex technologies in protective equipment and control
systems. This, together with the rationalisation of national, European and international harmonised Standards, has led to the need to provide new guidance in some
areas. So, after seven years, the time is ripe for an update to take account of such
developments.
Additionally, since the third edition was published, the political and financial
aspects of the supply industry have further escalated, with further fragmentation.
Chapter 1 therefore was particularly difficult, trying to take account of the continuous change in practice. At the time of writing this book, the replacement of the
Electricity Supply Regulations 1988 (as amended) was anticipated. The Electricity
Safety, Quality, and Continuity Regulations came into force on 31 January 2003, but
for the purposes of this book reference is made to the earlier Statutory Regulations.
The effect of changes in the industry over the last few years has meant the update
of nearly all the 23 chapters. It is not possible to highlight here particular alterations
for they are too numerous. Sections dealing with the safety aspects of electrical
installations, most particularly Chapter 11, naturally take into account Electricity at
Work Regulations. To a great extent these statutory requirements complement BS
7671: Requirements for Electrical Installations, known as the IEE Wiring Regulations. All chapters required some revision to take account of revisions and amendments to British and other Standards. It has to be recognised that, both on Standards
and technology evolution, the target is continually moving. However, every effort
has been made to bring the text as up-to-date as possible.
Over recent years lighting design development has continued. Extra-low voltage
luminaires continue to be used extensively for display and feature illumination.
Security lighting has now become an industry in its own right, and Chapter 18 takes
all these factors into account.
The declared low voltage supply has for a number of years been harmonised
across Europe to 400/230 V with tolerances of +10% and -6%. Further consideration of these tolerances is expected in 2008.
Geoffrey Stokes
xiii
CHAPTER 1
Power Supplies in the UK
D.C. Murch, CEng, FIEE
Revised by G.S. Finlay, BSc, CEng, MIEE
(Private Consultant)
In Great Britain the electricity supply industry was fully nationalised on 1 April
1948. Changes were made in 1957 which created a UK structure consisting of the
Central Electricity Generating Board (CEGB) responsible for major generation
and transmission throughout England and Wales, twelve Area Boards responsible
for distribution within their areas in England and Wales, two Scottish Boards and
a Northern Ireland board responsible for both generation and distribution within
their areas, and the Electricity Council which had a co-ordinating role and performed special functions in relation to research, industrial relations and finance.
Privatisation of the supply industry was implemented in England, Wales and
Scotland under the 1989 Electricity Act and in Northern Ireland by the Electricity
(Northern Ireland) Orders 1992. The Area Boards were replaced by twelve
Regional Electricity Companies (RECs) operating distribution networks under
franchises. Two companies in Scotland and one in Ireland, having transmission and
distribution networks, received franchises (see Fig. 1.2). A company which holds
licences under the Act and Orders is designated a public electricity supplier (PES).
Most of the industry is now owned by private investors following flotation on the
stock market, and returns on capital investment are now made to shareholders
instead of the Government. The Electricity Council was abolished by the Act but
some of its engineering functions are now carried out by two new companies. EA
Technology Ltd now offers a research and development service to the electricity
industry (EI), while the Electricity Association (EA) operates as a trade association on behalf of all its member companies, most of whom are mentioned in the
following text.
The structure of the UK electricity industry is shown in Fig. 1.1. In England
and Wales approximately 33% of the system peak demand of 58 GW is met from
thermal power stations, 41% from combined cycle gas turbine (CCGT) power stations and 20% from nuclear power stations. Powergen UK and Innogy, known in
the UK as npower, own most of the thermal and CCGT power stations while British
Energy plc and BNFL Magnox Generation, which is state owned, control all the
nuclear power stations in the UK. The pumped-storage facilities at Dinorwig and
Festiniog are owned by Edison Mission Energy, which is a subsidiary of Edison
International.
1
2
Handbook of Electrical Installation Practice
Generation
Distribution
Transmission
npower
Many Electricity
England and
Wales
Suppliers and 11
PowerGen
Distribution Network
Operating
National Grid
British Energy
Companies
BNFL Magnox
Scottish Power
Scottish Southern
Scotland
British Energy
Northern Ireland
4 Generators
Viridian
Fig. 1.1 Structure of the UK electricity industry.
When the National Grid Company (NGC) was sold by the twelve RECs to private
investors in 1995, it retained its statutory duties to facilitate competition in the
supply and generation of electricity and to develop and maintain an efficient, coordinated and economic transmission system. National Grid, as it is now named, is
the only company holding a Transmission Licence for England and Wales. The 7000
route kilometres of circuits and approximately 300 substations which comprise the
Grid are operated at 400 kV and 275 kV.
In Northern Ireland there are four major power stations with an aggregate
capacity of 2300 MW and supplying a national peak demand of 1550 MW but also
exporting to the Republic of Ireland. These power stations were sold to private
investors in 1992, and Premier Power, a subsidiary of British Gas, now operates
the largest at Ballylumford. NIGEN, a subsidiary of Tractebel and AES, operates
two power stations and the fourth one at Coolkeeragh is operated privately by a
management buy-out team. Northern Ireland Electricity (NIE) acts as the Independent System Operator with responsibility for both transmission and distribution
systems, and responsibility for the purchase of electricity from Generators. A separate supply business has been established within the company, which facilitates competition and the unbundling of the core business. NIE became part of the Viridian
Group in 1998.
In Scotland, the peak demand of approximately 4500 MW is met from 10 400 MW
of generating plant owned and operated by British Energy, Scottish Power and
Scottish and Southern Energy. The two latter companies operate as vertically
Power Supplies in the UK
3
integrated electricity companies and under their regulatory regime their generation,
transmission, distribution and supply activities are treated as separate businesses
and each is subject to separate regulation, which prevents cross-subsidy and excessive profit from manipulation of use-of-system charges.
There are two double-circuit connections, between the Scottish transmission
network and that of National Grid, which are used to export power to England and
Wales.
The original electricity supply franchise areas for distribution companies are
shown in Fig. 1.2 and they now represent the areas under the control of Distribution Network Operating Companies (DNOs) which no longer have a monopoly to
supply consumers connected to their networks. Some of the company names have
changed since privatisation as a result of acquisitions and mergers.
Fig. 1.2 The original franchised supply areas.
4
Handbook of Electrical Installation Practice
In 1999 the electricity supply and gas markets were liberalised so that now all
customers in the UK are able to choose the company or companies from which
to buy their supplies of gas and electricity, regardless of the company to whose
network they are physically connected. These competitive markets have resulted in
considerable savings to users. In the first year more than three million electricity
users of the 22 million in England and Wales had switched supplier. Most of the
original RECs still supply electricity to consumers and operate distribution networks but since liberalisation of the electricity market some RECs have either
sold their supply businesses and only operate distribution networks, or have separated their supply and distribution businesses. There is an increasing tendancy for
electricity supply to be integrated with generation.
The Office of the Gas and Electricity Markets (Ofgem) regulates the gas and electricity industries in Great Britain. Ofgem aims to bring choice and value to customers by promoting competition and regulating monopolies. Ofgem itself is
governed by the Gas and Electricity Markets Authority (GEMA) and is organised
into Directorates which have to report GEMA. The role of Ofgem’s Director of
Distribution and Financial Affairs is to oversee implementation of the Utilities Act
2000 and the Electricity Act 1989, particularly with regard to price regulation,
protection of interests of customers by setting standards of service and promoting
competition in electricity generation and supply, and gas markets.
The price of electricity is policed by Ofgem, which requires that the average use
of system charge per unit distributed should not increase year on year by more than
RPI - x, per cent after adjusting for an incentive to reduce electrical losses. The
initial values for x were agreed between Government and individual supply companies, and range from 0 to -2.5%. In fact, increases in use of system charges have
generally been kept well below the permitted limits.
The 1988 Electricity Supply Regulations and amendments, which were replaced
by the Electricity, Safety, Quality and Continuity Regulations in late 2002, contain
the statutory technical requirements for supplies to consumers in the UK. There are
other technical requirements of a statutory nature in the Health and Safety at Work
etc. Act 1989.
NGC was obliged to produce a Grid Code approved by the then Director-General
of Electricity Supply, which defines the technical aspects of the working relationship between NGC and all those connected to its transmission system. Some generation embedded in distribution networks is subject to the provisions of the Grid
Code. National Grid provides open access to the grid under terms which are nondiscriminatory. However, all Generators and Distributors seeking connection must
meet the appropriate standards to ensure that technical difficulties are not caused
for others connected to the system.
The Grid Code covers items such as planning requirements, connection conditions, demand forecasting, coordination and testing requirements, together with the
registration of appropriate data.
Each company operating an electrical distribution network is required to produce
a Distribution Code, which establishes the basic terms of connection for users. In
England and Wales the DNOs have a common Distribution Code as they all use
the same preprivatisation Engineering Recommendations of the Electricity Council
as technical references and the technical basis for managing their networks.
Power Supplies in the UK
5
The Engineering Recommendations referred to in the Distribution Code are now
published by the Electricity Association and are as follows:
(1) G5/4 Planning Levels for Harmonic Voltage Distortion and the Connection of
Non-Linear Equipment to Transmission Systems and Distribution Networks in
the UK.
(2) G12/3 Requirements for the Application of Protective Multiple Earthing to Low
Voltage Networks.
(3) G59/1 Recommendation for the Connection of Embedded Generating Plant to
PES’ Distribution Systems.
(4) P2/5 Security of Supply.
(5) P25/1 The Short Circuit Characteristics of PES’ Low Voltage Distribution
Networks and the Coordination of Overcurrent Protective Devices on 230 V
Single Phase Supplies up to 100 A.
(6) P26 The Estimation of the Maximum Prospective Short Circuit Current for
Three Phase 415 V Supplies.
(7) P28 Planning Limits for Voltage Fluctuations Caused by Industrial, Commercial and Domestic Equipment in the United Kingdom.
(8) G75 Recommendations for the Connection of Embedded Generating Plant
to Public Electricity Suppliers’ Distribution Systems Above 20 kV and with
Outputs Over 5 MW.
(9) S34 A Guide for Assessing the Rise of Earth Potential at Substation Sites.
(10) P29 Planning Limits for Voltage Unbalance in the United Kingdom.
(11) ER41–24 Guidelines for the Design, Testing and Maintenance of Main Earthing Systems in Substations.
Other recommendations referred to in this chapter are:
(12) G22/2 Superimposed Signals on PES Networks.
(13) G19/1 Model Guidelines for Operations or Work on the Premises of Consumers
Receiving H.V. Supply.
All the documents listed above have been exempted from the requirements of the
Restrictive Trade Practices Act 1976.
Distribution Code Review Panels comprised of representatives of Suppliers, Distributors, Generators and Users, as well as Ofgem, meet regularly to agree amendments to the Distribution Codes and their reference documents.
The Scottish companies operate under common transmission codes and separate
distribution codes.
The biggest change in the electricity industry (EI), resulting from privatisation
and Government incentives, has been the reduction of coal fired generation, the
increase in gas fired generation, particularly combined cycle gas turbines (CCGTs),
and the increase of generation embedded in DNO networks.
CCGTs are particularly attractive as they offer major environmental advantages
over coal fired plant; they consume 27% less fuel, and emit 58% less CO2 and 80%
less NOx for each kWh of electricity generated. Moreover they emit no SO2 and so
they do not contribute towards acid rain and global warming.
Also increasing are the numbers and size of wind farms connected to DNO networks. Schemes of 10 MW asynchronous generation are becoming common and
6
Handbook of Electrical Installation Practice
development of photo-voltaic generation systems has just commenced. These nonfossil fuel systems are encouraged by Government financial incentives as they are
environment friendly. In 1995 the completion of Sizewell B station added another
1250 MW of ‘green’ energy to the system and a similar station is proposed by British
Energy for the same site.
NETA
Until 2001, trading of bulk generation and supply of electricity was carried out
through the Electricity Pool of England and Wales (the Pool). This did not require
bilateral contracts directly relating to supply between a Supplier or his customer
and a Generator as the vast majority of all trading was carried out through the Pool.
The Grid Operator was responsible for matching supply and demand by estimating
the latter and dispatching generation to provide the former.
The New Electricity Trading Arrangements (NETA), which started in mid-2001,
mean that Suppliers now contract directly with Generators for supplies; excesses
or shortfalls are covered by a Balancing Market. This change has not affected the
metering arrangements, which were previously in place for the Pooling arrangements (see Fig. 1.3 and the section on metering later in this chapter).
The Grid Operator continues to balance generation and demand in real time but
now electricity is traded competitively between companies in ‘forward’ and ‘futures’
markets like any other commodity. In the first few months of operation, wholesale
electricity prices fell by 20 to 25 per cent.
VOLTAGE AND FREQUENCY
The supply system in the UK was standardised at 240 V single-phase and 415 V
three-phase with a frequency of 50 Hz following nationalisation in 1947 but was
recently redeclared. The supply voltage for low voltage (l.v.) consumers is now
400 V + 10%, -6%, for three-phase supplies, and 230 V + 10%, -6%, for single-phase
supplies at a frequency of 50 Hz ± 1%. In the year 2008 it is expected that all voltages in Europe will be redeclared within the range 400/230 V ± 10% in line with
the Cenelec Harmonised Document, HD472, S. Distribution network design and
voltage control will ensure that existing consumers’ supplies will be unaffected by
the new declaration and that their apparatus will continue to function satisfactorily.
The greater part of electrical energy is sold at 230 V and used directly by most apparatus. Major generation is connected to the supergrid system which operates at
400 kV although some sections are at 275 kV. In England and Wales this network is
owned and operated by NGC. The original 132 kV grid system which was started
in 1926 was transferred from the CEGB to the area boards in the 1970s and is now
the highest strata of distribution systems.
The major primary distribution voltage is 11 kV although a small proportion
still operates at 6.6 kV. For most of the system there is an intermediate stage
of 33 kV, but direct transformation between 132 kV and 11 kV is becoming common
policy in city areas, where over 150 MW can be economically distributed
Power Supplies in the UK
7
Fig. 1.3 Pool metering arrangements.
at 11 kV from one site. The frequency is maintained by NGC which regulates the
input power to the generators to match the instantaneous load on the system and
thus maintain their speed and thereby the frequency. This is manually controlled to
very close limits, thus enabling synchronous clocks, time-switches and other motors
to be used.
The voltage supplied to the consumers is mainly regulated by on-load tap-change
gear on the transformers which supply the 11 kV system. Fixed tappings are used
on the 11 kV to 433/250 V transformers as it would not be economic to put on-load
tap-changing on these. For large machines or equipment, supply is at a higher
voltage, usually 11 kV or transformed to 3.3 kV.
Apart from the size of the largest item, the need to bring a high voltage (h.v.)
supply on to a consumer’s premises is determined by the relative strength of the
local network in relation to the total load. In order to determine what supply can
be made available at any particular location, the local office of the appropriate DNO
should be consulted at an early stage.While generators produce a near perfect waveform and the on-load tap-change gear maintains voltage at the 11 kV source within
fine limits, all load on the system creates some distortion. The extent to which
8
Handbook of Electrical Installation Practice
the various types of consumer load can be connected to the system depends on the
distortion they are likely to create and the nuisance this disturbance causes to other
consumers. This subject is dealt with more fully in a later section.
SYSTEM IMPEDANCE AND SHORT-CIRCUIT LEVELS
From the consumer’s point of view another important parameter of the supply
system is its impedance as viewed from his terminals. On the one hand, the lower
the impedance the greater will be the stress on his switchgear and protective devices,
but on the other hand, the higher the impedance the greater will be the risk of
annoyance due to distortion caused by either the consumer’s own load or by that
of a nearby consumer. High network impedances are troublesome to installation
designers because they result in low values of fault current, which severely limit the
number of series graded protection devices and cause an increase in the I2t energy
let through of inverse characteristic devices such as fuses. The 16th edition of the
IEE Wiring Regulations, BS 7671, requires installation designers to have a knowledge of the limits of system impedance to which the supply will be kept in order
that they may install the necessary protective devices to an appropriate rating and
to operate within the required time. All supply systems are dynamic and many DNO
staff are continually employed laying cables and moving and installing plant in order
to ensure that the system configuration meets the demands of the customers. For
this reason it is not possible to give an exact impedance figure for any one location,
but the appropriate local area office should be able to give installation designers
the maximum and minimum likely to be encountered for a particular location. A
maximum earth loop impedance figure of 0.35 W is quoted nationally for l.v., singlephase, PME system supplies of 100 A or less. An appropriate maximum prospective
short-circuit current of 16 kA is quoted for many urban supplies; further information may be gained from Engineering Recommendation P25/1.
For many years it has been common practice to express the energy available on
short-circuit in terms of ‘short-circuit MVA’. This is simply 3 VA ¥ 10 -6 where V is
the normal system voltage between phases and A the symmetrical component of
the short-circuit current.
In 1971 the International Electrical Commission (IEC) introduced a standard for
switchgear ratings (IEC 56) which specified that the working voltage rating should
be expressed in terms of the system maximum, for example 12 kV for an 11 kV
system, and that short-circuit ratings should be expressed in terms of the maximum
symmetrical fault current. A range of ratings was specified, for example 12.5, 16, and
25 kA for 12 kV gear.
For any three-phase system voltage the short-circuit level and the system impedance are inverse functions of each other, kA = kV 3 Z.
On l.v. systems the cables will generally be the major contributors to the system
impedance as the h.v./l.v. transformers are of low impedance. The governing factor
is thus the distance of the consumer from the nearest substation.
On DNO h.v. systems the short-circuit ratings of the switchgear have a considerable economic significance and, therefore, system designers aim at keeping these to
as low a figure as practicable. A common method of achieving this is to employ high
Power Supplies in the UK
9
impedance 33/11 kV or 132/11 kV transformers. The high impedance is achieved by
judicious spacing of the windings and does not increase the transformer losses or
costs to any appreciable extent. The high impedance does not affect the voltage
output as the tap-changer regulates accordingly. At 11 kV the impedance of the
cables is generally much less significant.
Until the publication of IEC 56 many 11 kV systems were designed for a
maximum level of 250 MVA which is equal to 13.1 kA. The new rating method
therefore poses a problem where new or additional switchgear is required on an
existing system, since the 16 kA switchgear is more expensive. In general, however,
UK manufacturers can supply switchgear tested to 13.1 kA at similar to 12.5 kA
prices. With the low growth of demand, these 250 mVA systems will remain for many
years.
LOADING EFFECTS ON THE SYSTEM
Any normal load causes a voltage drop throughout the system. This is allowed for
in the design, and the cost associated with the losses incurred is recovered in the
related unit sales.
Unbalanced loads
Unequal loading between the phases of the network causes an unequal displacement of the voltages. Extreme inequality causes motors and other polyphase equipment to take unequal current and perhaps become overloaded on one phase. For
this reason DNOs impose limits on the extent to which they accept unbalanced loads
at any particular location in order to ensure that other consumers are not adversely
affected. Installation designers need to ensure that the same problem does not arise
due to an unbalanced voltage drop within the consumer’s installation itself.
While most voltage unbalance is caused by single-phase loading, the effect on a
three-phase motor can best be assessed in terms of the negative phase sequence
component of the voltage thereby created. Providing that this is less than 2% the
inequality of current between phases should not be more than the motor has been
designed to withstand. Engineering Recommendation P29 aims to limit continuous
levels of voltage unbalance to 1%.
Power factor
Many types of apparatus such as motors and fluorescent lighting also require reactive power and thereby take a higher current than is necessary to supply the true
power alone. This extra current is not recorded by the kWh meter but nevertheless
has to be carried by the distribution system and uses up its capacity thereby. It also
increases the losses on the system. A power factor of 0.7 means that the current
is 1/0.7 = 1.43 times as great as absolutely necessary and thus doubles the losses
(I2 R). If all the loads in the UK were permitted to have as low a power factor as
this, the additional cost of the losses (if the system could stand the burden) would
be in the order of £200 million per annum.
10
Handbook of Electrical Installation Practice
It will readily be seen, therefore, why DNOs are keen to ensure that their consumer’s power factors are near to unity. Where practical, some penalty for poor
power factor is built into the tariff or supply agreement.
Power factor correction is therefore an important aspect in the design of installations, although too often forgotten at the outset (see Chapter 23). The most simple
and satisfactory method is to have each equipment individually corrected as this
saves special switching and reduces the loading on such circuits. Bulk correction of
an installation is, however, quite commonly used, particularly where it is installed
as an afterthought. There are then problems of switching appropriate blocks of
capacitance to match the load, as overcorrection again increases losses and, in addition, creates voltage control problems at light load.
Switching transients
One of the primary uses of electricity is for general lighting and the local DNO must
ensure that its supply is suitable for this purpose. Repeated sudden changes in
voltage of a few per cent are noticeable and are likely to cause annoyance. The local
DNO must ensure that these sudden variations are kept within acceptable levels
and this means placing limits on consumers’ apparatus which demands surges of
current large enough to cause lighting to flicker.
In order to evaluate flicker in measurable terms, two levels have been selected:
the threshold of visibility and the threshold of annoyance. Both are functions of frequency of occurrence as well as voltage change. Since both these thresholds are subjective it has been necessary to carry out experiments with various forms of lighting
and panels of observers to ascertain consensus relationships between frequency
of occurrence and percentage voltage change for the two thresholds. The DNOs
have used this information in setting the planning levels for flicker contained in
Engineering Recommendation P28, which govern motor starting currents, etc.
The network impedance from the source to the point of common coupling
between the lighting and the offending load is of paramount importance and thus
the local office of the DNO should be consulted in cases where the possibility of
creating an annoyance arises.
Intermittently loaded or frequently started motors, such as those on lifts, car
crushers, etc., together with instantaneous waterheaters, arc welders and furnaces,
are all potential sources of disturbance. Large electric furnaces present a particular
problem and it is frequently necessary to connect them to a higher voltage system
than is necessary to meet their load in order to achieve a lower source impedance.
Fluctuations occurring about ten times a second exhibit the maximum annoyance
to most people, but even those as intermittent as one or two an hour will annoy if
the step change is of sufficient magnitude.
CENELEC Standard EN61000-3-3, limits voltage fluctuation emissions from
equipment rated less than or equal to 16 A and EN61000-3-11 limits emissions from
equipment rated from 16 A to 75 A.
Harmonics
Harmonics on the supply system are becoming a greater problem due to the increasing use of fluorescent lighting and semiconductor equipment. Cases have been
Power Supplies in the UK
11
known where large balanced loads of fluorescent lighting have resulted in almost
as much current in the neutral as in the phases. This current is almost entirely third
harmonic. The use of controlled rectifiers and inverters for variable speed drives, as
used on many continuous process lines, can also be a problem and DNOs have frequently to insist that 6- or 12-phase rectification be used. It is another case for local
consultation to determine what the system will stand. Even a multiplicity of small
equipment can summate to create a big problem, for example television set rectification, and for this reason international standards have been agreed. Engineering
Recommendation G5/4 sets out the limits of harmonic voltage distortion which are
acceptable to the supply industry for the connection of load at various voltage levels.
CENELEC Standard EN61000-3-2 limits harmonic emissions from equipment rated
less than or equal to 16 A and IEC TR61000-3-4 is applicable to equipment rated
at more than 16 A.
SUPERIMPOSED SIGNALS
For many years load control systems which superimposed signals on the normal
supply system have been in use. The earlier ones were usually at a higher frequency
and were referred to as ripple control, though one system used a d.c. bias. Tuned
relays respond to the appropriate signal and switch public lighting, change various
tariffs according to time of day or system load, switch water or space heating according to tariff availability or weather conditions, and perform various other functions,
even to calling emergency staff.
Although these did and still do perform satisfactorily, they did not come into universal use, probably because the full expenditure on signal generators was necessary to cover the system even though initially there were only a few receivers, and
this caused cash flow problems.
Equipment came on the market which could communicate from one premises to
another over the supply system. The EI predicted severe interference problems if
bandwidths were not allocated for specific types of usage. Self regulation has
evolved under the guidance of TACMA and the EI has produced its own working
document Engineering Recommendation G22/2. The British Standards Institution
has published BS 6839 on the subject.
With the advent of the thyristor and the transistor, supply companies started
experimenting with them on their network as a communication media, using pulse
techniques both for one-way and two-way communication. Practical installations
have been developed and a number of one-way systems installed to perform similar
functions to those carried out by the earlier ripple control method.
One such system developed by London Electricity was a range of codes transmitted by short pulses injected at the zero point of the 50 Hz wave (Fig. 1.4). Injection at this point requires less power and thus enables smaller transmitters to be
used. This method has been taken up by a major UK manufacturer and several oneway systems called Cyclocontrol are now controlling over 150 MW of off-peak load
in London. The two-way communication objective is to read meters remotely and
a workable system has been in use for several years, but only as a pilot scheme
because it was not economically viable using discrete components.
12
Handbook of Electrical Installation Practice
Fig. 1.4 Cyclocontrol signals.
The advent of the microprocessor and its relatively low cost in quantity production has widened the development field and made many schemes attractive. Solid
state metering with sophisticated control and tariff regulating functions will definitely be in use in the near future. Deciding what these ‘black boxes’ should be
made to do is the big problem facing the EI, remembering that there are some
20 million energy meters in the UK alone and the task of changing these is a
mammoth one. If the changes were carried out as part of the normal recertification
programme it would take 15–20 years to complete. Consumers who had to wait this
long for an attractive tariff or control function to be available to them would be far
from happy.
There is another side to the picture. Sophisticated control systems which are
already available for use within a consumer’s premises enable a master programme
controller to send signals over the main conductors to slave controllers on appropriate apparatus. The master controller being flexibly programmed via a keyboard
and display is even capable of responding to signals sent via the telephone.
Interference, both accidental and wilful, is a problem which needs careful consideration and rejection circuits may be needed where such systems are in use on
both sides of the supply terminals.
While the use of the network itself, as a control medium, is attractive to a DNO,
it has its drawbacks and other methods using superimposed signals over the radio
or telephone are being used. The radio is attractive for one-way communication as
the transmitter cost is minimal and full coverage is available.The telephone is attractive for two-way communication as the addressability exists within the telephone
system.
From the electrical contractor’s point of view this expanding field of superimposed control is likely to extend the range of his work and so add to the complexity of some installations.
RADIO TELESWITCHING
The EI in collaboration with the BBC investigated the possibility of superimposing
digital data on BBC long-wave transmissions for the purposes of sending information and control signals from its offices to its customers’ premises. Suitable
Power Supplies in the UK
13
technology to enable this was developed and the radio teleswitching (RT) system
was approved by the relevant authorities. An important requirement was that the
superimposed signals should not impair the reception of normal audio (Radio 4)
programmes transmitted on long-wave band. Fully operational facilities became
available in 1984.
The EI holds a patent on the development and issues licences to approved manufacturers of RT devices. The RT device consists of three essential components –
a radio receiver capable of satisfactory performance under low signal strength and
high noise level areas, a microprocessor which decodes the received signals and
includes a time clock and memory, and a set of contacts or switches which are controlled by the microprocessor.
Companies supporting the RT system use it for one-way communication with load
and metering apparatus in their customers’ premises. The system does not need
routing or rerouting of signal paths. Nationwide broadcast coverage and the use
of unique codes enables a user company to send signals to its customers no matter where they are located in the UK and prevents one company’s data affecting
customers of another company. A company can store an entire week’s programme
for all its groups of RT devices in the central computer of the RT system or,
through the same computer system, it can send immediate command control signals
addressed to any of its groups. This central teleswitch control unit (CTCU) is
managed by the Electricity Association which also manages the development and
operational arrangements of the whole RT system. The CTCU converts the programme information into the required codes, minimises the signals required and
schedules and despatches them for transmission at the appropriate times. Off-air
monitors are installed for each transmitter area, and the signals from these are fed
back to the CTCU as a check that all despatched messages have been broadcast
and therefore should have been received by all RT devices.
The most common type of RT device used by companies has a 24-hour clock
and a memory which stores programme messages for a day. The RT device then
controls customer load and tariff according to the received and stored 24-hour
programme. The problem of inaccuracy and drifting of load and tariff switching
times is eliminated by the broadcasting of time signals every minute. A stored programme can be removed and replaced by an entirely different 24-hour programme
at any time, or it can be gradually changed to the following day’s programme on a
rolling basis. A programme may also be suspended and replaced by an immediate
command broadcast at any time. The devices have a standard fallback programme
which they follow under certain conditions. To keep new devices updated and help
ensure reception, broadcast messages are repeated as a routine. If a device misses
a programmed broadcast and its repeats it will follow the last programme it
received.
By being first in establishing radio teleswitching as a fully operational cost effective option for use in energy management on a national scale the EI has given the
UK a world lead in this field. Further developments of the RT system are intended
to increase its data carrying capability, enable weather and cost related information
to be broadcast as energy management parameters and allow the system to be integrated with other developing technologies, such as smart cards, so that the full potential of the system can be realised.
14
Handbook of Electrical Installation Practice
SYSTEM AND INSTALLATION EARTHING
In the UK the Electricity Supply Regulations have governed the way systems are
connected to earth. The successor Regulations, The Electricity Safety, Quality and
Continuity Regulations 2002, came into force on 31 January 2003. For the purposes
of this book reference will be made to the earlier Statutory Regulations.
Low voltage systems
For many years the Regulations required that each l.v. system should be solidly connected to earth at only one point, that being the neutral of the source transformer.
Special permission was necessary to earth at more than one point. The Regulations
also required that cables buried in the highway must have a metallic sheath. Systems
earthed at only one point require the neutral conductor to be electrically separate
and are now known as SNE (separate neutral and earth).
It was, and still is, the responsibility of each consumer to provide the earth connection for his own installation. This was commonly achieved by connection to a
metallic pipe water main. The growing use of PVC water mains makes this impossible for new installations and causes problems with existing ones when water mains
are replaced. Gradually, supply companies developed a practice of providing consumers with an earth terminal connected to the sheath of their service cable. This
is, of course, a very satisfactory arrangement but it is not universally practical as
many cables laid in the 1920s or earlier are still in use and many of these are not
bonded across at joints. The arrangement is not practical on most overhead systems.
In Germany and elsewhere in Europe an earthing system known as ‘nulling’ grew
up. This employed the principle of earthing the neutral at as many points as possible.
It simplified the problem of earthing in high resistance areas and by combining the
sheath with the neutral conductor permitted a cheaper cable construction. These
benefits were attractive and during the 1960s the official attitude in the UK gradually changed to permit and then encourage a similar system known as PME (protective multiple earthing). Blanket approvals for the use of this system, and the required
conditions to be met, were finally given to all area boards in 1974. In BS 7671 – the
16th edition of the IEE Wiring Regulations this system is classified as TN-C-S.
Providing the consumer with an earth terminal which is connected to the neutral
conductor ensures that there is a low impedance path for the return of fault currents, but without additional safeguards there are possibilities of dangerous situations arising under certain circumstances.
If the neutral conductor becomes disconnected from the source of supply then
the earthed metalwork in the consumer’s premises would be connected via any load
to the live conductor and thus present an electric shock hazard from any metalwork
not bonded to it, but which has some connection with earth. In order to eliminate
this rare potential hazard the Secretary of State, in his official Regulations, requires
that all accessible metalwork should be bonded together as specified in the IEE
Wiring Regulations and so render the consumer’s premises a ‘Faraday cage’. This is
the reason for the more stringent bonding regulations associated with PME.
Under the extremely rare circumstances of a broken service neutral and intact
phase conductor, there may be a danger of electric shock on the perimeter of the
Power Supplies in the UK
15
‘cage’ to someone using an earthed metal appliance in a garden, even though the
appliance may be protected by an RCD (residual current device) in accordance with
the IEE Wiring Regulations. For the same reason metal external meter cabinets are
undesirable.
In order to eliminate as far as possible the chance of a completely separated
neutral, a number of precautions are taken. First, all cables must be of an approved
type with a concentric neutral, either solid or stranded, of sufficient current carrying capacity. Secondly the neutral conductor of a spur end on the system is
connected to an earth electrode if more than four consumers’ installations are
connected to the spur, or if the length of the spur connection from the furthest connected consumer to the distributing main exceeds 40 metres. Where reasonably
practicable, cable neutrals are joined together to form duplicate earth connections.
A faulty or broken neutral will give an indication of its presence by causing supply
voltages to fluctuate, which, of course, should be reported to the local DNO as soon
as possible. All these measures contribute to a system which is as safe as practicable and self monitoring.
It is the declared intention of the EI in the UK to provide earth terminals wherever required and practicable within the foreseeable future. The local DNO should
be contacted regarding their requirements for the use of PME earth terminals for
TN-C-S systems.
High voltage system earthing
The Electricity Supply Regulations specified that every h.v. system shall be connected
with earth at or as near as reasonably practicable to a source of voltage in the system.
They also specified that conductors, which respectively connect a supply neutral conductor with earth and any apparatus used in an h.v. system with earth, shall not be
interconnected unless the combined resistance to earth is 1 W or less; the conductors
shall not be connected to separate earth electrodes unless any overlap between the
resistance areas of those electrodes is sufficiently small as not to cause danger.
There are various methods used to earth an h.v. system and practices between
DNOs in the UK vary considerably. Most of the 11 kV systems are derived from
33/11 kV delta star transformers and thus there is a neutral point available. In quite
a number of cases these are solidly earthed and the resultant potential earth fault
current can be slightly higher than on a phase-to-phase fault. It is also quite common
to restrict the current by the insertion of a resistance or reactance in the neutral
to earth connection to limit the fault current to about the full load of the supply
transformer.
Where the h.v. supply is designed directly for 132 or 66 kV, it is usual to have a
star wound primary to minimise the transformer cost. In order to get the correct
phase relationship, it is necessary to use a delta secondary winding in some cases
and a star winding in others. When delta secondaries are used it is necessary to
employ a separate earthing transformer to create a star point and this transformer
limits the earth fault current, though frequently a resistor is also used. Where the
secondary winding is star connected, this is either directly connected to earth or
through a resistor. Usually the resistors for this purpose are water-filled but in some
cases a reactor is employed.
16
Handbook of Electrical Installation Practice
Where an h.v. supply is afforded, the installation designer needs to know the range
of the protective earth fault current in order to provide the correct protection.
Where a consumer transforms an h.v. supply it is necessary to earth the secondary system. Some DNOs allow the use of a common earthing system, which means
that the sheaths of their cables are probably providing the major return path for
any earth fault current. Where there is a requirement for the segregation of earthing systems for technical or security reasons, such as the provision of ‘clean’ earths
to computer systems, special care must be taken with the earthing system design.
All electrical and other metal installations within an associated structure must be
considered when assessing the overall design to ensure that earthing systems extended by equipotential bonding are not close enough to cause safety problems
related to indirect contact. The earthing problem takes on an extra dimension where
generating plant is embedded in DNO distribution networks. Engineering Recommendation G59/1 and Engineering Technical Report ETR113 (1994) give the
requirements and guidance, respectively, for the connection of embedded generating plant up 5 MW to DNO distribution systems less than 20 kV.
PROTECTION
The design of the protective arrangements on a supply authority’s system is influenced by the need to provide as economic a supply as possible commensurable with
a reasonable degree of reliability. Because of the high cost of circuit-breakers this
means using as few as possible. Experience also indicates that the simplest system
is often the most reliable as it is less prone to human error.
Most DNO systems employ the simple principle of time and current grading up
to the 33 kV level. Besides the benefits of simplicity and economy it can cater for
the ever-changing topography of the network to meet the changing load pattern,
and each protective stage also provides back-up to the one nearer the load if that
fails to operate.
On rural overhead systems a fairly high proportion of faults are transient and
immediately clear as soon as the supply is disconnected and it is therefore common
practice to install automatically reclosing circuit-breakers on the h.v. system. These
eventually lock out if the fault persists.
Throughout the life of the industry there has been a continuous evolution of
electromagnetic relays for protection and control purposes and these now perform
satisfactorily for the majority of applications. The development of modern semiconductors makes the use of analogue circuits a practical alternative with the benefit
of no moving parts. Their adoption, apart from one or two specialised roles, has been
slow, probably because there were a number of early failures and their benefits in
terms of increased reliability or cost reduction were insufficiently attractive.
With the advent of microprocessors entirely new concepts of protection are offered. Their speed, flexibility and memory capacity, coupled with their low power
requirement, have put the design of the power system back in the melting pot. It is
generally appreciated that a lot of trial and error experience will need to be undertaken before they come into general use on old or new systems, but their ultimate
take-over seems to be inevitable.
Power Supplies in the UK
17
The Electricity Supply Regulations require that each consumer is fed through a
suitable fusible cut-out or automatic switching device, the purpose of which is to
protect the supplier’s works on the consumer’s premises which are not under the
control of the consumer. It is the general practice to install the maximum size of
cut-out fuse which matches the incoming service capacity, in order to give the widest
discrimination with the consumer’s first protective device.
A typical urban system
Urban l.v. cables are typically protected at the h.v./l.v. substation by 400–600 A fuses
(Fig. 1.5). Using the simple proven ratio of 2 to 1 for correct discrimination of series
connected fuses, means that 200–300 A fuses may be installed for individual supplies to offices, factories, shops, flats, etc. Larger loads frequently need to be fed
directly from an h.v/l.v. substation. The transformers in these substations are protected by h.v. fuses as these are less expensive than a circuit-breaker and operate
faster under short-circuit conditions.
The next stage of protection is at the h.v. substation where each outgoing h.v.
circuit is protected by inverse definite minimum time lag (idmtl) relays, two elements connected to detect and operate on overcurrents and the third detecting and
operating on earth faults.
RELIABILITY
Electricity plays a vital part in modern society and loss of supply causes much
consternation, inconvenience, financial loss and some danger to life. By putting in
surplus generation, alternative circuits and high standards of construction it is possible to achieve a very high standard of supply. It is not possible to achieve absolute
security and the question of how much money should be spent on security to obtain
a reasonable level of reliability is one which is under continuous review and sophisticated techniques have been developed by the industry in order to obtain the most
cost effective arrangements.
The Electricity Association operates a comprehensive computer-based system,
the National Fault and Interruption Reporting Scheme (NAFIRS), on behalf of its
member companies, which builds up statistics to highlight weaknesses, etc., and
assists in improving techniques. The average UK consumer loses supply about once
every two years for about three hours. Rural supplies, by virtue of their sparseness,
are less reliable than those in urban areas.
Having developed systems and equipment which can provide a high degree of
reliability, the supply industry finds that third-party damage is a major hazard
and in conjunction with the Health and Safety Executive it is trying to instil
into those who work in the public highway the need to know the location of supply
mains in the vicinity of the work. New sites are particularly vulnerable in this
respect.
Where a consumer requires a more reliable supply than normally afforded by the
system to which he is or will be connected, then it may be possible to provide him
with an alternative source from another substation, the cost being chargeable. It
18
Handbook of Electrical Installation Practice
Fig. 1.5 Typical urban system protection.
Power Supplies in the UK
19
would, of course, be vulnerable to a mutual failure including industrial action, but
might, nevertheless, be worthwhile as the alternative of standby generators is not
100% reliable.
EMBEDDED GENERATION
The Energy Act 1983 was the statutory instrument which placed an obligation on
the EI to publish tariffs for the purchase of energy from companies operating generating plant and to support and adopt combined heat and power (CHP) schemes.
These tariffs also include the charges appropriate to the provision of standby capacity to a supplier and the charges associated with using the EI power systems between
a generator or supplier and their dedicated customers. On occasions DNOs have
been unable to permit the connection of embedded generating plant because either
the resulting fault levels would have been in excess of plant ratings or the devices
used to limit fault current have not been approved by the EI approvals panel as
being safe.
Engineering Recommendation G59/1 sets out the EI’s basic requirements with
regard to the connection of generating plant installations up to 5 MW to systems up
to 20 kV. Engineering Technical Report ETR113 (1994) gives guidance on the connection of embedded generating plant to DNO networks.
A consumer may install his own generators because he feels he may be able to
generate more cheaply or because he hopes it will give him a more reliable supply.
There are many possible modes of operation:
(1) Full generation of electricity only, without any incoming public supply. This is
unlikely to be profitable, particularly if hidden costs are evaluated.
(2) Full generation in association with process steam:
(a) With public supply as standby. Providing the steam and electricity demands
are well matched throughout the working period this can be a viable
arrangement.
(b) With public supply meeting some of the load which is switched to suit the
generation capability at the time.This could be a viable arrangement subject
to a satisfactory supply agreement. It has the advantage of avoiding parallel operation, which imposes technical problems.
(c) Generating in parallel with the public supply system. This can permit any
surplus or deficiency of generation to be exported or imported within
agreed levels and controlled by the metering and protection. Separate
metering is used for import and export as the price paid for the excess units
will be less than for those from the public supply. Because excess units are
not of prime value at times of light load, the price offered often appears
mean to those who are not aware of the wide range of incremental value
with time and committed availability. DNOs are generally keen to make
this arrangement work as it can be financially attractive to both sides, as
well as giving a high degree of reliability.
One major problem is the increase in short-circuit level created by the
generators, as each power system is likely to have a source short-circuit level
20
Handbook of Electrical Installation Practice
Fig. 1.6 High voltage consumer with switchable reactors.
near that of the switchgear rating. Switchable reactors may be required to
overcome this problem; one such arrangement is shown in Fig. 1.6. There is
also a problem of earthing the generators should they become separated
from the power system and its source earth point.
This method of supply seems a good one for the application of microprocessors. On the metering side they could calculate the value of the
units on an incremental worth basis to suit a time/load/power factor agreement. On the control side they could monitor the number of generators
and reactors to contain the short-circuit level within limits. They could
be used to control voltage and reactive power generated, and also for
protection.
(3) Standby generation. Load shedding due to shortage of fuel or other industrial
action caused an upsurge in the installation of small generators by those consumers whose business could not stand the risk of loss of supply, ranging from
just a few kilowatts at low voltage to several thousand kilowatts switched at
high voltage.These cause some anxiety on safety grounds as cases have occurred
where the generator has been started up and connected to the installation
without the latter being disconnected from the incoming supply.
It is easy to imagine a small l.v. generator being plugged in to supply a milking
machine on a farm at the end of a line and a linesman repairing the fault receiving a shock and being thrown to the ground. Problems have also occurred on
large sets due to incorrect changeover arrangements, for example, in one case
a loss of supply on one phase only brought in the standby set without the normal
feed being disconnected.
The local DNO is generally pleased to give advice on appropriate changeover
arrangements.
Power Supplies in the UK
21
SUPPLY ARRANGEMENTS
Electricity supply tariffs are normally specified according to the type of consumer,
i.e. domestic, commercial or industrial, and it is convenient to use the same categories to discuss the supply arrangements.
Domestic supplies
Houses are now provided with a 100 A single-phase supply. Flats without off-peak
heating are provided with a 60 A supply. Service installation is an expensive labourintensive activity and it is therefore important that the capacity and location are
such as to ensure that very few installations need early alteration. On the other
hand, the number that need installing every year means that even the most modest
economy is worthwhile.
Domestic meter reading is a heavy recurring expense and ease of access is therefore an important factor in the siting of the meter. External meter cabinets are thus
preferred wherever practical but their use is not without problems. It has taken quite
a long time to get their general acceptance architecturally as they do little to enhance the appearance of premises.
From the structural point of view there have also been problems, because the hole
they occupy in the wall causes a reduction in its fire resistance.The entry of the supply
cable also presents problems. It is important to arrange for the builder to install a
pipe which has a suitable diameter and radius, and if any cavity insulation is to be
used it should be omitted adjacent to the pipe as otherwise it will derate the cable.
The pipe has to be sealed at the bottom end in order to prevent the possible entry
of gas into the premises should a leakage occur outside the house (Fig. 1.7).
An external meter cabinet is outside the Faraday cage and therefore it is preferable to use one of insulated construction.
The gas companies are also keen on external meter reading and there are pressures for a common cabinet to be used, although clearly there are problems of
bonding and ensuring that there is no danger of ignition if a gas leak occurs.
Not all domestic development is in the form of individual housing; quite a large
proportion is made up of maisonettes and flats, either low- or high-rise, although
the latter have declined considerably in popularity. Where more than one dwelling
is to be fed from one service it is necessary to extend the mains from the termination of the incoming cable to the remote dwelling units. For this purpose individual
rising or lateral connections will need to be installed. High-rise buildings may also
require a common main (Fig. 1.8).
The ownership and installation of these mains are dependent on agreement
between the developer and the local DNO. In many cases the DNO will pull their
cables into pipes, ducts or chases provided by the developer. Such installations must
resist interference and the spread of fire. Early agreement and architectural provision is essential as some modern methods of construction can present acute problems of routeing. If the local DNO is to be the owner then a PME system may be
employed using CNE cables.
The question which arises is the siting of the meters; the possibilities are for them
to be in a common intake room, in meter cabinets outside each flat or inside each
22
Handbook of Electrical Installation Practice
Fig. 1.7 Typical service entry into a house.
flat itself. None of these is ideal as each fails to meet one of the following requirements: capable of being read by the consumer, capable of being read by a meter
reader without entry to premises, not observable by persons with malicious intent
(no movement of the meter might give an ‘all clear’ to a break-in), allow a prepayment meter to be used. This latter possibility was not an attractive one from the
local DNO point of view as the collection of the money was a big problem. Fortunately, the development of token meters has solved the problem of theft. Trial
schemes have been so successful that existing money prepayment meters are rapidly
being replaced by token meters; 25 000 were installed in London alone in 1988. Each
token meter has a unique key identified with a consumer, which is recharged at
streetside vending machines; hence the keys have no intrinsic value. Load and
address data stored in a key’s memory chip can be recovered by a vending machine
and used for load analysis purposes.
In each case the meter position is decided on which factors are important and
which disadvantages can be overcome.
In high-rise buildings electric heating can simplify the construction and be an
economic solution but the interdependence of the heating gives problems of
Power Supplies in the UK
23
Fig. 1.8 Rising and lateral mains.
individual control and payment. In many cases it has been necessary for the landlords
to be responsible and make an appropriate charge with the rent. If designed for at
the outset this may be done by a completely separate installation. Where the heating
is taken over at a later stage, control can be by the use of superimposed signals.
Commercial supplies
Commercial development can be either purpose or speculatively built. If the occupier and the intended use of the building are known before it is built the electrical
installation is designed to meet the consumer’s requirements. If it is to be a branch
of a departmental chainstore or something similar then the consumer may well have
his own electrical engineer who is able to give an accurate estimate of the loading
requirement based on the experience of other branches.
In other cases it may be that consultants are used and the supply engineer needs
to be on guard against being led to install capacity which will not be fully utilised
due to a liberal load estimate. Providing that space is earmarked for the contingency
24
Handbook of Electrical Installation Practice
of putting in extra or larger plant, the local DNO may on its own experience discount the estimate and put in smaller plant, being prepared to be wrong on the odd
occasion.
Despite the fact that many new office developments remain empty for long periods,
speculation goes on. The design of the electrical installation poses many problems,
some of which also concern the local DNO. Is there a possibility of multiple occupancy and, if so, can the installation be split up to permit individual metering?
In a tower block this can sometimes be achieved by using a number of cable rising
mains each feeding, say, three or five floors with facilities to swing the intermediate
floors either way. Cases have been known where a developer has had to change his
intention of letting to a single tenant. With a single heavy busbar riser this means
that sub-metering had to be used which is not a very satisfactory arrangement, particularly with regard to maximum demand. In other cases this has not been acceptable and the rising main system has to be replaced.
The increasing use of office automation and air conditioning makes the problem
of estimating the loading more difficult and thereby the designing of the integral
substation. No local DNO is happy about installing plant which may not be used
for several years but which, nevertheless, has to be kept live and maintained. It may
therefore not only want a full contribution to cover the initial cost but also some
provision for the maintenance.
Industrial supplies
While most large companies have their factories purpose built, light industry frequently rents its premises which may well be part of a factory estate. It is now quite
common for small factory estates to be set up speculatively with the purpose of
encouraging local industry. Because in most cases the use of these buildings is not
known, the problem of providing suitable services is a difficult one. The developers
want to be able to offer adequate availability of electricity but the local DNO does
not want to put in plant to meet any eventuality with little chance that the full capacity will be used.
The range of consumption and demand per square metre for industrial use is very
wide – it can range from a storage warehouse to a heavy power consuming process.
Some quite small units may requite an h.v. supply in order to withstand load variations without undue voltage fluctuations. Even a continuously running motor can
cause problems if it is driving a cutting or stamping machine or a similar machine
which makes sudden demands on power and draws heavy currents.
The local DNO may well compromise by putting down a skeleton network, earmarking possible substation sites and laying down spare ducts to cater for the possible future h.v. cables to feed them. Without any guaranteed load or customers the
local DNO almost certainly requires a full expenditure contribution.
INTAKE ARRANGEMENTS
Installation designers and contractors may find it helpful to understand some of the
factors which influence local DNO supply arrangements. Prior consultation and cooperation is necessary to ensure a neat and efficient combined arrangement.
Power Supplies in the UK
25
Low voltage
Except for supplies to street lighting and furniture, the smallest service size normally used is 60 A single-phase. In most locations now, 100 A single-phase services
are provided. Above this size the load must be spread over three phases and the
typical range of sizes is 60, 100, 200, 300, 400, 600, 800 and 1000 A. Those up to 200
A may come from the network if there is sufficient capacity. The larger sizes normally come from an adjacent substation. Those below 600 A are generally provided
by multicore cables. The larger sizes need single-core cables to provide the necessary capacity. Where the service is fed from a normal distributor it is terminated in
a sealed chamber containing the appropriate fuse. Where the service is fed direct
from a substation in the consumer’s premises the fuses may be in the l.v. board in
the substation.
As there is a need to insert and withdraw main fuses with one side live they are
arranged in carriers. Round tagless fuses are used for the 60 and 100 A sizes where
the fuse-carriers rely on spring contacts. For all sizes above these the contacts are
tightened by screwed wedges which compress the double tags on the fuses on to the
contact fingers. It is preferable to terminate the service as soon as possible on the
consumer’s premises as the small section service cables are not fully protected by
the large fuses which protect the distributors.
The common practice of using metal-clad enclosures for the fuses on three-phase
services is no longer favoured by DNOs as some flashovers have occurred when the
DNO staff have been inserting or withdrawing fuses. Those installed need to remain
for many years and safe working practices have been developed. New designs are
of all-insulated construction with separate covers on each phase so that only one
needs to be exposed at any one time. These cut-outs are sealed to prevent access by
other than the local DNO authorised staff and should not be tampered with even
by highly skilled contracting staff; besides being illegal there have been some very
serious accidents.
Where a PME terminal is provided this is sealed to prevent its use until compliance with the appropriate regulations has been checked by the local DNO.
High voltage
Every h.v. supply has to be tailored to suit the needs of the consumer and the capability of the local DNO network.
The Electricity Supply Regulations require provision to be made to guard against
excess energy. The most simple arrangement is an h.v. switch-fuse and this is a
satisfactory arrangement for a single transformer.
The most common arrangement for the provision of an h.v. supply is to loop in
an h.v. circuit from a ring main network. These circuits are usually operated with a
switch open at the mid-point, to provide a radial system. The open point can be
altered by switching to permit any part of the ring to be maintained or altered (Fig.
1.9). By looping in an h.v. consumer the supply is maintained while such work is
carried out. With this simple arrangement supply is lost if the circuit develops a fault
but can be restored in an hour or so by simple switching operations. In some cases
it is possible to arrange for the open point to be at the consumer’s premises and this
26
Handbook of Electrical Installation Practice
Fig. 1.9 High-voltage ring main.
Fig. 1.10 High-voltage supply to a consumer using directional protection.
enables the supply to be restored by automatic changeover equipment or by the
consumer carrying out the switching. A system of interlocks is used to prevent the
circuits being paralleled.
In densely loaded areas it is often possible to tee on to two circuits to provide a
normally available alternative. In London a variation of this has been developed and
there are now a considerable number of installations which have proved successful
in maintaining supply (Fig. 1.10). There are two incoming circuit-breakers and both
are normally closed. One set of relays provides overcurrent and earth leakage protection, having a definite minimum time multiplier setting of 0.15 which operates in
about half a second, and another faster operating directional relay. The operation
of the overcurrent or earth fault relays opens one of the two circuit-breakers. The
Power Supplies in the UK
27
directional relay, by operating faster, decides which is the faulty feeder and switches
the tripping circuit to the appropriate circuit-breaker. The protection on the outgoing circuit-breakers at the source substation has a longer time setting and thus
the feeders are separated and only the faulty feeder loses its supply. This simple
arrangement can only be used n - 1 times between n feeders forming a group,
otherwise parallel paths are formed for the flow of fault current and discrimination
between DOC circuit-breakers and source substation circuit-breakers is jeopardised.
In areas where there is likely to be a considerable number of h.v. consumers in
close proximity it becomes a practical proposition to employ a unit protected closed
ring main (Fig. 1.11). Here each cable section is fitted at both ends with similar
current transformers, summators and relays which compare outputs via a pilot cable
and the circuit-breakers at both ends are tripped if there is a certain level and proportion of difference.
Two typical systems in use are Solkor (see Chapter 22) and Translay. Both names
have existed for many years and each have passed through a number of revisions
to increase speed, improve stability, and reduce size and manufacturing costs. These
systems by their nature do not provide back-up for each other and it is thus prudent
for a few strategically placed slower operating overcurrent relays to be installed to
provide back-up protection.
This back-up protection also operates on a busbar fault in one of the substations.
Such faults are, however, very rare with modern equipment and the risk is acceptable. There are several ways that have been used to protect the busbars – for
example, overlapping the unit protection schemes – but such arrangements complicate the issue and increase the risk of human error and cost and thus the more
simple arrangement is now preferred.
A hybrid DOC/unit protection ring system has been developed in London in
order to afford firm supplies to a group of h.v. consumers without having to install
pilot cables some distance back to a source substation. The busbars of two DOCprotected consumers have been coupled together by unit protected cable links
which contain several h.v. supplies. Overcurrent protection is fitted at one end of
Fig. 1.11 Unit protected ring.
28
Handbook of Electrical Installation Practice
the unit protected circuits to act as a ring-buster and limit supply failure in the event
of a busbar fault.
CONSUMERS’ SUBSTATIONS
In order to control and transform an h.v. supply, the consumer needs one or more
substations. They have to be designed to meet the regulations which apply for the
particular location. Regulations cover such matters as fire protection, safety, means
of escape, etc. To ensure that these are complied with it is advisable to employ an
experienced consultant. The work of installing and maintaining h.v. equipment is a
specialist activity and DNOs are generally prepared to quote for such work.
The main consumer switchboard is fed by the local DNO through its service
circuit-breaker with associated metering. At first sight it sounds attractive to use a
composite DNO/consumers’ switchboard, but taking all things into consideration it
is probably better to have the local DNO’s switchgear in a separate switchroom.
The single switchboard poses problems of meeting both specifications and of agreeing the supplier. There are problems of authorisation of entry and of keys and security locking. By providing an intervening brick wall and a short through-connection
the problem of co-ordination is much reduced and the cost is recovered in terms of
reduced overheads and a faster completion.
The consumer needs to have some of his staff authorised to operate the h.v. gear
and for this they require training. Depending on the equipment and layout it may
be appropriate for this to be done by the plant manufacturers but it may also be
appropriate for some training in safety procedures to be given by the local DNO.
Many have training establishments for their own staff and they may be prepared to
give the required training for an appropriate fee.
H.V. OR L.V. SUPPLY?
The local DNO generally charges slightly less for supplies at h.v. than at l.v., the difference being determined by what it estimates to be the extra cost of transforming
and distributing the l.v. Providing all the supply is to be transformed to l.v. at a point
where the local DNO could equally well do it with its standard range of equipment,
then it probably pays to take a supply at l.v., since the local DNO has the advantage of economy of scale in its activities and can exchange plant to match the load
most economically. Where economies can be made by deploying transformers
around the site or by using equipment at a higher voltage, this will tip the balance
in favour of the use of h.v.
METERING
Metering of bulk supplies
Metered values of supplies generated (by generating set) are summated and aggregated as to each generating company. Supplies taken by suppliers are likewise
Power Supplies in the UK
29
summated and referenced to Grid Supply Point (GSP) groups from which bulk supplies are taken. Within NETA there is then reconciliation, known as Settlement,
between Generators and Suppliers, on a half hour by half hour basis for every day.
Figure 1.3 illustrates the concept of metering at commercial boundaries but the Area
Data Collection A and B boxes are not relevant to bulk supplies.
Codes of Practice set out the requirements for bulk supply metering and data collection. These specify static meters of Class 0.2S, impulsing into a data collection
unit from which half-hourly energy values are extracted by telephone dial-up each
day. At this level both main and check meters are installed.
Metering of end-customer supplies
Since 1998, customers of any size have been able to choose their supplier. Competitive supply is underpinned by contracts struck between the various parties involved.
A customer will have a contract with his supplier and a Connection Agreement with
the distributor in whose area he is. There is no contract regarding supply between
a supplier and a distributor, other than that both abide by market rules, as set out
in the Balancing and Settlement Code, which includes agreement to payment of useof-system charges.
Larger customers and ‘metering by differences’
The current end-customer metering arrangements are a complex mix within which
not all customers are metered to the same criteria. The basic difference is whether
a meter recording half-hourly energy values is fitted which can provide data to the
same requirements as Settlement; i.e. 48 half-hourly values every day by remote
dial-up. As this type of metering equipment is expensive it is uneconomic below a
certain level of customer demand, which reflects the value of the supply.
The market rules require that all customers with a demand of 100 kW and above
involved in competitive supply must have these ‘Settlement timescales’ metering
systems. All customers of >100 kW have these metering systems irrespective of
whether they elected to change supplier as a result of a deliberate decision taken
in 1998 to fit such meters. The class of meter and the need, or not, for check-meters
varies according to the demand.
Data collection systems for large customers overlay the bulk arrangements shown
in Fig. 1.3. Metered half-hourly consumption values are recorded and ‘tagged’ to the
GSP group and supplier, and the consumption at each meter point is allocated to
the respective supplier under Settlement reconciliation. Figure 1.12 shows that at
each GSP group the total metered quantities of all half-hourly metered supplies are
deducted from its overall input to provide the value of other supplies at that GSP
group. This is a principle known as ‘metering by differences’ and means that not all
25 million customers in the UK need have expensive half-hourly meters.
Small customers without half-hourly meters
Metering equipment as used above was not seen as economic for smaller customers
when the third phase opened up competition to all customers in the UK. It was
30
Handbook of Electrical Installation Practice
GSP TOTAL
‘MIST’
1
2
‘MOST’
hourly meters
Aggregates of
each customer’s
S1
profile for each
supplier (estimates)
Source of
back-up for each
supplier’s estimates
‘Residue’
S2
S3
S4
Code 6 HHM
(no comms)
..etc..
Spes
Existing meter
(quarterly, monthly)
Fig. 1.12 Trading arrangements post 1998.
finally agreed to allow the use of estimates, rather than metered values, based on
standard ‘load profiles’ and to place the onus on the supplier to choose by which
route he would bring customer data to Settlement. There are some supplies (say
above 70 kW) where a supplier may choose to install a half-hourly metering system,
which he is entitled to do because it is his commercial decision.
Figure 1.12 illustrates the concepts whereby daily Settlement (now termed
Primary Settlement) uses two distinct sources of data:
(1) MIST (Metering Inside Settlement Timescales) – half-hourly metering and
data collection, which provides remotely collected metered values to Pool
Timescales.
(2) MOST (Metering Outside Settlement Timescales) – profiling. Each supplier
with customers at a GSP group provides estimates of the 48 half-hourly values
of energy it expects to take at that GSP group by summating expected demands
of each individual customer calculated from standard profiles. All Suppliers’
submissions are then aggregated and an element of manipulation takes place
subsequently to ‘fit’ the submissions to the actual recorded value of that day,
as identified by the ‘metering by differences’. This enables clearance of transactions relating to that day’s trading.
At a later stage a secondary reconciliation takes place in some six ‘runs’ over the
subsequent 14 months. As meter readings come in various forms to various
timescales, the supplier can verify his estimated profiles, either fully, if meters record
half-hourly values, or partly, the volumetric element, if meters are read monthly and
quarterly.
It has been stressed that there is no requirement to provide a half-hourly
meter, which effectively means that the existing meter can be left in place and
31
Power Supplies in the UK
arrangements made by the supplier to read it. However, there is an inherent though
weak incentive to move away from profiling towards metering solutions since these
reduce the trading risk. There is a Code of Practice 6, which is relevant to a ‘low
cost’ meter with optional communications facilities and a capability for recording
and retaining half-hourly values to ‘MOST’ criteria for 3 to 12 months.
Agents and the development of metering services
It is the supplier who is seen as the ‘hub’ of the current arrangements and who, as
previously indicated, is responsible for deciding on the metering arrangements of
his customer and for providing meter data to Settlement. To do this he must appoint
three agents – a meter operator, a data collector and a data aggregator. Each agent
must go through an accreditation process to ensure that its systems are compatible
with the Settlement process.
With the ending of the PES non-half-hourly franchise and with the splitting of
the PESs into the separate business functions of supply and distribution, Ofgem is
involved in consultation with companies about exactly what this will mean to the
future of metering. A consultation paper foresaw emergence of independent meter
services providers (MSPs) to offer:
•
•
•
•
•
Meter provision
Meter maintenance
Meter reading
Data processing
Data aggregation
The situation is now in a state of flux. Meter provision and maintenance are currently carried out in the half-hourly market by the meter operator; in the non-half-
Distributor
Supplier
Billing
Default meter reading/data retrieval
Registration (MPAS)
Data transfer services
Data Aggregator
Default meter provision/installation
Data aggregation
Meter Operator
Meter provision
Meter maintenance
Meter supply
Certified repaired meters
Meter supply
Certified new meters
New COP meters
Data Collector
Meter reading
Data processing
Customers
Fig. 1.13 Model following separation of businesses.
32
Handbook of Electrical Installation Practice
hourly market meter provision is seen as a default function of the distributor, which
is to be responsible for supplying meters as at present unless the supplier advises
that he would take this on via his own meter operator. Meter reading and data processing are currently carried out by the data collector; default meter reading is seen
as the responsibility of the supplier. Ex-PES MSPs exist which can cover the whole
range of services, but there are also some companies which operate in one or two
areas only; for example, meter reading companies. Figure 1.13 illustrates this new
structure. Some PESs sold their MSP businesses and there is likely to be future rationalisation and consolidation.
Requirements for accuracy of metering
In UK legal metrology, product standards published by BSI are used as the basis
for approval by the Electricity Metering Examining Service and for accuracy levels
for certification testing. Meter standards relate to class, e.g. a Class 2 meter has a
reference accuracy of ±2%. Standards exist for Classes 0.2, 0.5, 1 and 2 meters, both
electromechanical and electronic.
So-called ‘whole current meters’ are suitable only for voltages at 400/230 V and
currents of up to 100 A. Instrument transformers are necessary to match base meters
to higher voltage and/or higher current supplies. Standards exist for various classes
of voltage and current transformers, which typically operate on secondary values of
110 V and 5 A respectively.
The metering equipment at customers’ premises was specified in national Codes
of Practice at privatisation. That for supplies of 1 MW and above required fourquadrant metering to Class 0.5 accuracy (Class 0.2 above 10 MW). The Code for
100 kW metering equipment reduced the requirements to Class 2 accuracy, measuring only import active and lagging reactive energy. The code and the agreed procedures are still relevant and now form part of the NETA Balancing and Settlement
Code.
CHAPTER 2
Substations and Control Rooms
D.M. Barr, BSc, CEng, FIEE
(Consultant, Balfour Beatty Engineering Ltd)
INTRODUCTION
Health and safety
In recent years there have been a number of developments in the industry, particularly in relation to health and safety issues. Dangerous practices must be avoided
and equipment must be suitable for its purpose.
Substations are potentially lethal. During their training, virtually all electrical
engineers have witnessed the enormous power available in even a low voltage
system. Careless mistakes made with a test set or battery illustrate the potential consequences of a high voltage accident.
Privatisation
Privatisation has drawn attention to the fact that electricity is a commodity to be
sold to the consumer at a profit which depends on the time of day or season when
it is produced. Tariffs are constructed by calculating the cost of energy production
at the time that it is required.
Costs are made up of :
(1) Capital invested This was probably borrowed at a commercial rate of interest.
(2) Cost of upkeep A combination of labour and material costs.
(3) Cost of fuel In the UK this is a mixture of nuclear, coal, oil and gas with a contribution from other forms such as hydro, waste disposal and wind power.
The fuel cost is the main basis for the variable kWh element in a tariff. Transmission and distribution costs are virtually all for capital and maintenance but do
include an element to cover energy losses. This provides an incentive to make the
network as efficient as possible.
The tariff has to take into account the huge cost of maintaining standby capacity
to cater for outages of a large generator or generating station or of an interconnecting line. Pumped storage stations will assist, if they are pumped up, but their
overall efficiency is about 70%. This is the first additional cost that must be recovered for power at peak load times. Others include the additional capital, maintenance and fuel costs involved in providing spare capacity plant on standby.
33
34
Handbook of Electrical Installation Practice
Reactive power component
Expenditure is incurred for the provision of reactive power. Alternating current
systems have to receive excitation current continuously. The effect is that there are
large reactive currents being transmitted across the network causing real energy
losses and voltage drop (regulation). The result produces additional capital and
running costs. These costs are reflected in tariffs by use of appropriate metering
which records the various quantities and time of day and date.
At peak load times, efforts are made to reduce the kW and kVAr maximum
demand. This maximum demand charge can be onerous and difficult to reduce.
For many years there have been recommendations to install equipment to
improve the power factor and to manage the energy demand. The long term financial recovery from such outlay has not often been sufficiently attractive to those
managements who are anxious to reduce forced outages.
New technology
The introduction of digital, data handling systems with programmable devices and
transmission capability has provided a powerful new tool for control and monitoring of the supply. Protection and interlocking have been improved with the introduction of information technology equipment in substations.
A typical, classical substation secondary system would perhaps have 40 cores per
unit marshalled at the switchgear for transmission, via the alarm and station control
cubicle, to the network control centre.
The equivalent digital control system has single parallel connections between
each of the switchgear units and their protection panels. There is a single serial connection from each unit to the local control panel, plus a further serial connection
to each of the computer input/output modules and the network control centre.
Procedural planning and design
Remote monitoring and control, together with a degree of automation, can be introduced into existing substations at a reasonable cost and with suitable checking facilities. This ensures that wrong procedures leading to unsafe conditions are not
possible. Illustrations of modern equipment are shown in Figs 2.1 and 2.2.
The downside is that operational sequences based on logic diagrams must be produced with the co-operation and approval of the client’s engineer. Comprehensive
checks are needed, preferably physically on a mock-up on the supplier’s premises,
to ensure that the procedures are safe. It should not be possible to defeat interlocks
either deliberately or accidentally.
It is important that the installation contractor understands the purpose of
sequences and is able to test the installed hardware connected to the various items
of plant. A thorough knowledge of the software and the required settings is essential. The designer must be able to supply this information well in advance of the
final commissioning procedures.
Electricity distributors provide a single point of supply to a site which can be at
different levels of security depending on the importance of the electrical loads
Substations and Control Rooms
Fig. 2.1 11 kV switchboard, Jersey (Siemens plc).
Fig. 2.2 Digital control panel, Jersey (Siemens plc).
35
36
Handbook of Electrical Installation Practice
served. If the load demand is of sufficient magnitude, the consumer will find it practical and economic to take the supply at high voltage (h.v.). For the purpose of this
handbook the upper limit is 11 kV, although for very large complexes the intake
might be at 33 kV or even higher. It is the consumer’s responsibility to control and
distribute the electricity around his site or premises to suit his own requirements.
The main substation serving a network incorporates the supply intake point,
but there may be other substations located at strategic areas in a large complex
and connected to the main substation by a cable network. The manner in which
this interlinking occurs depends on a number of factors and is fully discussed in
Chapter 3.
If the supply is taken at 11 kV the main substation will include 11 kV switchgear
which may serve other substations at 11 kV throughout the site. Stepdown transformers at the site substations provide power at the consumer voltage. For very
small installations the intake may be a single cable providing a three-phase 400/
230 V supply to a switch and fuse board. In between are a variety of arrangements.
Depending on the importance of the load served, there may be a standby generator(s) linked to the system and arranged to supply essential loads. Some
manufacturing complexes may generate their own power, particularly where the
generation of process steam is related to the electrical requirements. Generally
speaking it is uneconomic to rely on self-generation totally because of the cost of
standby generators. Such sites would normally have a standby supply from the mains
network. In that case synchronising is required in the main substation to allow
paralleling of the two systems. Alternatively, the two systems are interlocked to
prevent accidental paralleling. Particular attention would be required to limit the
fault power, the effects of reverse power and for discrimination under fault conditions. There would also be a problem in sharing responsibility. The magnitude and
the importance of the load dictate the nature of the supply and distribution network
and hence the design of the substations and control facilities.
Two points should be noted in respect of the demarcation between the supply
authority and the consumer’s equipment. The first is that there may be annual rates
levied on any transformer between the supply point and the consumer’s distribution system. Secondly, while the supply authority may provide, install, operate and
own all of the equipment up to the point of supply, it may require the consumer to
make a contribution to the capital cost of making this supply available and will in
many cases ask for a site on the consumer’s premises to house it. It is common but
not invariable for the supply authority to insist on a separate room or locked-off
area for its apparatus.
There is therefore a wide variety of possible arrangements. The client’s contractor is normally responsible for ensuring that the whole scheme is installed in a safe
and secure manner with due regard to all health and safety regulations in accordance with the Health and Safety at Work etc. Act and in compliance with the
client’s specifications. The site engineer therefore has a heavy responsibility. If a
design drawing shows an unsafe arrangement or one which conflicts with good practice, he must draw this to the attention of his employer so that it may be remedied.
Electrical power systems can cause death and injury if not properly installed. The
local authority and the fire authority inspect any new properties to check that they
are safe. If they are not, the remedial work could be expensive, especially if it
Substations and Control Rooms
37
involves civil works. The supply authority will normally require information about
any new installation but apart from checking the busbars immediately after their
own protection the supply authority does not have a responsibility for the client’s
installation.
As stated, the arrangement of supply to consumers’ premises depends primarily
on the nature of the load. For loads from say 100 to 300 kVA, a 400/230 V threephase supply from an Electricity Distributor’s substation is normally satisfactory. A
load of between, say, 200 and 500 kVA may have its own Electricity Distributor’s
transformer. Above 500 kVA one might expect an 11 kV supply and above 1000 kVA
it would normally be split into two or more 11 kV circuits. Where a duplicate supply
is provided the incomers are generally arranged to have manual changeover facilities or to be fully automatic with feeder protection depending on whether or not a
firm supply is required. Firm supplies are normally provided for all loads above
5 MVA.
Internal to the factory or other industrial complexes single radial feeders are generally acceptable provided that there is no safety hazard or process which is unduly
sensitive to the loss of supply. A smelter or furnace could be badly damaged by the
solidification of molten metal caused by a supply failure. In such circumstances a
ring main may be installed or duplication of connections to the sensitive load. It is
also important to remember that electrical equipment including busbars, transformers and circuit-breakers needs maintenance, and therefore bus-section
switches, duplicate transformers and interconnecting cabling may be inescapable for
a continuous process.
An alternative supply may be better obtained from an in-house standby generator than a duplicate feed. This is particularly so in remote areas where it is recognised that there is only a single overhead line, or in overseas territories with
unreliable power supply systems.
It is simpler and there is less risk of damage to equipment if the standby supply
is not synchronised with the public supply. This is generally satisfactory since a small
diesel generator can pick up full load in about a minute. Where there are installations such as computers for which a continuous supply is essential, a batteryoperated inverter may be used. Emergency lighting is traditionally energised by
direct current (d.c.) and it is wise to consider whether circuit-breaker closing and
tripping supplies should be d.c. together with supplies to contactors and electrically
operated valves.
SUBSTATIONS
Early consultation with the local Electricity Distributor is essential for agreement
on a mutually approved substation to act as the intake point for a particular site.
This consultation is usually before detailed knowledge of the plant or project is
known but it is essential that a fairly accurate load requirement be determined. Plant
manufacturers must be approached to provide information relative to the equipment they are supplying and this, together with experience, enables a reasonably
reliable load demand to be ascertained. Having this knowledge enables the rating
of the power transformers and of associated switchgear to be decided.
38
Handbook of Electrical Installation Practice
All substations ought to be designed to be capable of extension unless it is obvious
that such a facility will not be needed.The extent of such provisions must be weighed
against the monetary outlay and be agreed as a viable proposition. Depending on
the nature of the system the substations may be required to accommodate h.v.
and/or l.v. switchgear, transformer(s) and protective and control facilities. They can
be wholly or partially outdoor or indoor and can take many forms.
Standard equipment should be selected as far as possible to keep cost and delivery to reasonable levels. This equipment should comply with an appropriate standard; in the UK this would be a British standard.
One can conveniently divide the subject into two sections: the various network
supply arrangements possible which determine the nature of the equipment utilised,
and how this equipment is laid out and protected, i.e. the type of enclosure
provided.
High voltage substations
There are three common ways that an 11 kV supply may be provided to a site: by
a ring main, by duplicate feeders, or by a radial feeder or a single spur from a radial
feeder.
The duplicate supply may be provided with either automatic or manual changeover facilities.
Ring-main unit
A ring-main unit consists of two manually operated incoming isolators and a teeoff circuit to an 11 kV/400 V/230 V transformer. The tee-off may be controlled by a
circuit-breaker or a fuse-switch, both providing a measure of protection to the transformer and acting as a back-up to the l.v. consumer’s network. This is a very common
arrangement.
If the site contains three-phase motors at various points remote from the substation, the designer may provide a motor control centre at the substation either integral with the main distribution board or adjacent to it. Alternatively, a number of
circuits may be established to supply motor starters at sites closer to the motors.
The main distribution board may also supply local general services such as lighting
and small power directly in addition to circuits for more remote sub-distribution
boards.
It is preferable to use motor control centres for process plant such as food or
chemical manufacture where the production is automatically controlled. The cross
connections between the monitoring equipment and the drive controller may be
more readily effected. Duplicate supplies may also be provided economically to the
motor control panel.
Where the supplies are only for small power and lighting the main l.v. switchboard may be less elaborate with fuse-switches, mccbs and fuse boards. Where splitter boards are used a 400 V isolating switch is needed to enable fuses to be changed
in safety. This should be so interlocked that access to the fuses is not possible until
the switch is open. A typical ring-main unit is shown in Fig. 2.3 where the tee-off is
controlled by a circuit-breaker and Fig. 2.4 where a fuse-switch is employed for this
purpose.
Substations and Control Rooms
39
Fig. 2.3 A typical ring-main unit incorporating a circuit-breaker in the tee-off circuit.
Fig. 2.4 A typical ring-main unit incorporating a fuse-switch in the tee-off circuit.
Duplicate supply substation
A more elaborate and expensive design of substation is shown in Fig. 2.5. This would
provide firm power to a site where security of supply is important. Generally the
bus-section switch is kept open and the two halves of the board are supplied by
their respective cable feeds. If there is a failure of one of the incoming cables the
bus-section switch is closed and the faulty cable is isolated by its circuit-breaker.
Interlocking ensures that only two out of the three circuit-breakers (i.e. controlling
the supply cables and the bus-section switch) are closed at any one time. With this
system each intake must be capable of providing the full load of the network.
Single-supply substation
Where a consumer is able to accept an interruption in supply there is no necessity
to go to the expense of a duplicate feed, either from a ring-main unit or two
40
Handbook of Electrical Installation Practice
Fig. 2.5 Duplicate 11 kV supply substation.
Fig. 2.6 Single-cable supply to an 11 kV substation.
separate cables. A single cable supplying an 11 kV switchboard can be used as shown
in Fig. 2.6, and this could well be the responsibility of the Electricity Distributor.
Low voltage substations
For loads up to about 300 kVA the power is usually provided from the local supply
authority’s network at 400 V. As for h.v. substations, either single or duplicate feeds
may be provided to the consumer’s main switchboard. Quite often these boards are
divided into sections, one supplying non-essential plant and the other essential
equipment. In the event of a mains failure, the essential supplies can either be provided by a duplicate mains cable or more likely from a standby generator set.
Substations and Control Rooms
41
Generally, the main switchboard is a factory-built assembly often of composite
design, incorporating circuit-breakers, fuse-switches and circuit-breaker panels.
Motor starters may also be included or may form a separate mcc board.
The rating of circuits is discussed in detail elsewhere, in Chapter 3, Site distribution systems, but there are a number of general points which are often overlooked
in respect of substation design, which make it easier to understand the ratings commonly utilised.
A widespread site such as a dockyard or a large petrochemical plant may have
a total load measured in megawatts. It is necessary therefore to have a number of
substations.
Circuits supplying current-using equipment should not have a voltage drop
exceeding 4.0% of the nominal voltage at the design current. However, it may be
necessary to use a conductor larger than that required for the voltage drop to satisfy
the motor starting conditions. In addition the cables and protective gear must be
designed to match the prospective fault current.
To size a cable therefore requires consideration of:
(1)
(2)
(3)
(4)
Full load continuous rating
Voltage drop under full load conditions
Motor starting voltage drop
Prospective fault current short time rating.
Each of these conditions is subject to additional constraints. For example, the full
load rating must take into account the effect of a low voltage and a low power factor.
These conditions will also apply to the voltage drop. In addition, continuous full
load rating must be available despite proximity to other cables and high ambient
temperature. The motor starting situation will also be made more difficult by low
mains voltage and power factor. The fault current is obviously a function of the
supply characteristics. It is wise to allow for some strengthening of the supply system
as time passes.
Fault clearance
The circuit-breakers and fusegear must be able to clear faults before cables are overheated. They must also themselves be capable of accepting the mechanical, thermal
and electrical stresses imposed by faults. Transformers, busbars, cable boxes and
insulators must also be suitable for the fault level.
To assist in the correct selection of fuses, manufacturers offer a variety of fuse
characteristics. These cover variations in current, voltage, time/current, Joule integral, cut-offs, power dissipation and frequency including direct current.
The contractor must ensure that he is installing fuses which are appropriate to
the duty. A fuse failure may result in an explosion or the emission of flame. Comprehensive guides are available from such organisations as ERA (Report No.
87–0186R) and the manufacturers on the selection of fuses. It is particularly important to ensure that fuses in substations (which are subject to the highest fault levels
on the system) have adequate short-circuit capacity and are fitted with the correct
fuse link to protect the outgoing cables.
42
Handbook of Electrical Installation Practice
ENCLOSURES
Substations may be either outdoor or indoor types or a combination of both. Site
substations generally are no different from main substations, having the same equipment and layout but usually on a smaller scale. All the same precautions have to be
taken with respect to safety, access arrangements, protection, etc., as with main
substations.
Outdoor substations
Where all the equipment is mounted in the open the enclosures must be of weatherproof design (i.e. suitable for all the relevant external influences); this generally
relates to h.v. substations. Transformers are automatically suitable for outdoor
mounting but if liquid-filled designs are employed they need to be provided with
drainage facilities, as discussed later.
Ring-main units are often used outdoors and designs are available that are suitable for this. Distribution cabinets are needed for the l.v. distribution feeder cables.
Railings or anti-vandal fencing are provided to enclose the equipment to form the
substation (Fig. 2.7).
There are also packaged h.v./l.v. substations that utilise standard indoor equipment mounted inside a weatherproof enclosure. The transformer may be outside
the housing which contains the h.v. and l.v. switchboards, separated by a corridor.
Room for rear access to the switchboards may have to be provided. A claimed
advantage for this type of substation is that it allows the foundation to be prepared well in advance and is ready to accept the assembled equipment direct
from the manufacturer. It is not so popular today because of economic considerations but has the advantage that maintenance on the switchgear is possible in all
weathers.
An economic arrangement of outdoor substations is the so-called integrated
design which has switchgear mounted on the transformer cable boxes, permitting a
naturally cooled transformer to be employed (Fig. 2.8).
Fig. 2.7 Typical outdoor substation layout.
Substations and Control Rooms
43
Fig. 2.8 Typical multi-transformer substation.
Outdoor/indoor substations
The more conventional arrangement of h.v. substations is to have outdoor transformers with indoor 11 kV and 400 V switchboards. Transformers are housed in an
annexe to the switchroom and there may be separate chambers for 11 kV and
400 V switchboards, battery and charger and controls. It is often convenient to have
a separate control room for installations which include more than one substation,
standby generation, combined heat and power systems and process plant requiring
sequencing and interlocks.
This arrangement is preferable for town or urban substations because of the convenience of using standard indoor switchgear rather than the more expensive
weatherproof designs. The difference in cost between indoor and outdoor transformers is not great, and because of the need to provide adequate ventilation the
trend is to install them outside with protection against vandalism.
A common practice for multi-transformer substations is to have weatherproof
chambers for the h.v. and l.v. switchgear and metering and to mount the transformers in open pens as shown in Fig. 2.9.
Where the h.v. switchgear is under different operational management from the
l.v. side, the more conventional design of substation is probably the best. It is also
much more flexible to cater for special protection, extensions, non-standard
ratings or bulk-buying of components. However, these advantages must be weighed
44
Handbook of Electrical Installation Practice
Fig. 2.9 Cabling of substation.
against the undoubted counter-advantages of packaged designs requiring less liaison
at site between civil and electrical engineering, protection of sensitive equipment
from weather and theft during transport and at site, lower design and installation
costs, short completion times, and previous testing as a unit in the factory.The chance
of a mistake in connecting up is also reduced.
It ought to be noted that a number of materials such as steel, glass fibre and concrete are available to house the switchgear, metering and distribution equipment.
Extensions are also available from some manufacturers.
Indoor substations
Indoor substations require non-flammable equipment to make them safe or precautions to limit the fire risk. Basically there are two types of indoor substation. The
Substations and Control Rooms
45
first comprises separate components such as switchgear, control and metering panels
installed in a room(s); the disposition depends on the space available, size of equipment and importance of segregation. The second, and becoming increasingly
popular, is the packaged substation. This should not be confused with the outdoor
package design which is quite different.
The indoor packaged substation is a single transformer assembly with integral l.v.
switchgear housed in a suitably designed indoor enclosure which can be shipped as
a complete unit or split up into sections for transport. The h.v. switchgear may be
integral with the unit but it is more likely that an 11 kV cable will be brought from
a nearby substation into the packaged substation.
A particular advantage of this form of h.v./l.v. substation is that it can be
located at the load centre of the area it is serving, even on the factory floor. It is
extremely compact and, like the outdoor equivalent, requires the minimum of site
work.
SUBSTATION CABLING
Substation cabling may be run in trenches or ducts for outdoor substations or
from overhead trays and cleats indoors. An attractive alternative for the large
indoor installation is a cable basement with trays supporting cables running directly
below the equipment. Such an arrangement facilitates changes and additions at a
later date if it is known that the factory or process may be subject to alteration. It
is also convenient if there is a separate control room because the control cabling
then becomes significant so that it may be marshalled into reasonably large
multicores for distribution to the associated controls, relays, interlocks and process
plant.
For modest sized plants a cable trench is satisfactory. It is always true that where
cables enter a building there are problems of preventing access of water and vermin.
The best arrangement is to have the cable trench in the building at a higher level
than outside. This is illustrated in Fig. 2.9. However there are many buildings where
the cables are taken from a below-ground-level trench outside to a below-groundlevel trench inside the building without letting water into the building. A set of salt
glazed ducts installed at a level of say 200 mm above the floor of the trench prevents normal rain-water entering the building, particularly if they are sealed with a
weak concrete mix of waterproof cement or some proprietary sealant such as
Densoplast which is elastic enough to accommodate a modest relative movement
of the cables.
In general, the more extensive substations, such as those illustrated in Figs 2.5
and 2.6, are made up as special combinations of standard parts. The choice of
equipment is described below in general terms and in more detail in the chapters
on each type of equipment. It is not proposed to describe all the combinations of
circuit-breaker, isolator, fuse-switch, contactor, fusegear, transformer and control
gear which are possible. One important feature which both designer and installer
should strive for is standardisation. The installer should be able to instigate site procedures which ensure that all the systems when completed are in accordance with
good practice.
46
Handbook of Electrical Installation Practice
Transformers
In general 11 kV transformers are rated between 300 kVA and 2 MVA. If they are
installed outdoors they are usually mineral oil filled, naturally cooled units. These
transformers can be used indoors where the fire risk is not high but they must be
provided with a bund and oil drainage facilities.
Where it is important to minimise the fire risk, i.e. for office blocks or commercial premises, one can use a transformer filled with a fire resistant liquid or a dry
type Class C design. Until quite recently askarel liquids (composed of polychlorinated biphenyls, or pcbs) were used to replace mineral oil to provide a good cooling
and insulating medium with fire resistant characteristics. Following accidents where
pcbs have been spilled and have come in contact with human beings, it has been
realised that the liquid is toxic and is to be avoided.
Where transformers presently installed are filled with an askarel, care should be
exercised and steps taken if necessary to retrofill them with a safer fire resistant
liquid like silicone fluid. Askarels are marketed under a number of trade names such
as Pyroclor, Aroclor, Pyranol, Phenocolor, Clophen and Fenchlor.
Silicone liquid is a satisfactory product to replace mineral oil as a cooling and
insulating medium where this is desirable. It is much more economic than changing
the transformer.
Dry type Class C transformers are an alternative fire resistant design but are not
normally economic above 50 kVA, although where the situation demands it or the
user prefers it, designs are available up to about 5 MVA. Not only is the cost much
higher than liquid-filled designs but dimensions and weight may also be significantly
increased. This may be critical if substation space is restricted or the foundations
are not able to support the increased weight.
High voltage switchgear
There is a wide choice of 11 kV switchgear to choose from including oil break, air
break, vacuum or sulphur hexafluoride (SF6). The switchboards are either metalclad or metal-enclosed designs with withdrawable circuit-breakers.
The bulk oil breaker board is probably cheapest but suffers from the risk of fire,
high maintenance costs and a limited number of operations between overhaul.
Vacuum gear is attractive where a large number of operations is envisaged but it
has a relatively low fault breaking capacity and may impose a switching overvoltage on connected equipment. Air-break gear has a good fault rating, has low
maintenance costs and has no fire risk but is very bulky and is expensive. Sulphur
hexafluoride gear is relatively untried but promises to be attractive from the point
of view of space, maintenance and safety.
The form of enclosure varies from company to company, some favoring metalclad designs with segregated busbars and separate current transformer (CT) chambers, cable entry chambers, voltage transformer (VT) chamber or tank, control and
instrumentation and protective relay panels. Other companies provide a cheaper
but less secure system without the earthed metal barriers between circuit chamber
and busbars. There is a risk with such an arrangement that circuit faults will develop
into busbar faults thus shutting down a whole network.
Substations and Control Rooms
47
There are a number of variations to the main types of supply switchboard to suit
particular circumstances; for example, double-bus switchboards where the circuitbreakers may be connected to one of two busbars; vertical or horizontal isolation;
full interlocking to prevent operation of the circuit-breaker in the wrong position
or withdrawal when closed; integral earthing where the circuit-breaker can earth
either the circuit or the busbars when selected to do so; secondary isolating contacts
which can be arranged to allow testing without danger to the commissioning
staff; bus-section circuit-breakers; extensibility on either side of the switchboard; h.v.
cable test facilities; and current injection test facilities.
There are also a wide variety of operating mechanisms to suit site conditions such
as: independent manual closing; hand-charged spring-operated power closing mechanism with or without an electrical release; motor-charged spring-operated power
closing mechanism; and solenoid closing mechanism.
There are also a number of 11 kV units which have been specially designed for
ring-main supplies as discussed earlier. These usually consist of oil switches on the
two connections to the ring and either an oil fuse-switch or exceptionally a circuitbreaker on the transformer tee connection. The oil switches are normally able to
close on to a fault and to open full load current safely. This is an economic way of
providing a secure supply and is widely used in the UK.
The ring-main unit can conveniently be provided as part of a package substation
(discussed later) including the transformer and 400 V distribution fused pillar. Such
a unit can be completely enclosed in a weatherproof cubicle and transported to site
in one piece. The cubicle also serves to keep out of danger members of the public
or staff who are not concerned with its operation or maintenance. Figure 2.10 shows
a typical 12 kV switchboard.
Fig. 2.10 Typical 12 kV metal-clad switchboard using SF6 circuit-breakers (Yorkshire
Switchgear and Engineering Co. Ltd).
48
Handbook of Electrical Installation Practice
Control panels
In respect of control there may be separate panels or control may be entirely from
the switchboard. This is often most satisfactory as a permanent 11 kV supply need
only be switched off in an emergency. Such an occasion may never occur and the
extra expense of separate controls is not worthwhile. However, where two or more
sources of supply are involved, or if synchronising of a private generator is necessary, or if there is a great deal of switching owing to load management or fluctuations of loads or supply systems, then a separate control panel is best. This is
equipped with instruments indicating the normal electrical parameters such as
voltage and current with perhaps, where necessary, power, vars, power factor and
frequency; it could also have switchgear position indicator lamps together with a
remote control switch for each circuit-breaker. The normally accepted colour code
for indicator lamps is given in BS EN 60073. There may be a requirement for additional facilities such as auto-trip alarm, overload alarm, earth-leakage alarms, trip
circuit supervision and remote/local changeover switches.
Protective relays, alarm facias, mimic diagrams, secondary circuit fusegear and
test blocks may all be mounted on the control panels which must therefore be of
substantial construction and vermin proof with adequate space to mount the
equipment, run the wiring and terminate the incoming cables. Control equipment
may be on the front panel of a vertical cubicle or on the horizontal or sloping face
of a desk-cubicle. The cubicles may have bottom cable entry with gland plates near
the floor to leave room for making off; alternatively, they can be terminated in marshalling boxes below the floor with wiring run into the cubicle in conduits. Another
design allows for the termination of the cables in terminal boxes mounted on the
wall behind the cubicles with wiring running overhead in ducts or trunking to enter
the cubicle from above.
Since a control board or desk is a man–machine interface its design and features
are to some extent subjective. However, the indications and controls which are
extended from the primary equipment to the control room need careful selection
to ensure that the operator has sufficient information and control facilities without
cluttering the panel with irrelevant signals or unnecessary switches. Data which are
only required for post-fault analysis or long term records should not appear on the
operator’s panel.
There is also the possibility of bringing together individual alarms where a
detailed knowledge of each item of plant which has failed will not assist in deciding the immediate course of action. In this case the cause of the alarm must be ascertained by going to the initiating device.
In the larger installations there may be scope for visual display units using small
computers to receive, process, store and have available for display by instruction
from the operator, the data needed to decide on the correct sequence of operations.
Such systems are very powerful tools which can also provide facilities such as data
recording and analysis, alarm limit setting and display, high-speed pre- and postfault recording, sequencing control and monitoring, equipment status as well as
loading information and the selection of sections of the network to be illustrated
on the screen while the status is being changed.
Substations and Control Rooms
49
On the more conventional installations, however, it is common to rely on a
mimic diagram, possibly using a mosaic-type or similar construction for ease of alteration, and including either indicating lamps for important features such as circuitbreakers and isolating switches or discrepancy-type semaphores. The semaphore
may also include the operating switch with a system of illumination to show whether
the primary plant has altered position in accordance with that taken up by the
control switch. Miniature ammeters, voltmeters, etc. may also be incorporated but
as these become illegible on the larger panels unless the operators approach them
closely, it may be preferable to mount them separately from the mimic panel on a
desk immediately in front of a seated operator.
On the smaller installations a combined mimic and operator’s panel is of course
quite satisfactory and this would be the case in the majority of industrial premises.
Such a panel is commonly placed in the same room as panels controlling factory
boilers, compressed air systems, and processes of various kinds. Associated with
them are energy management systems which are becoming more and more an economic necessity. It is important to have a reliable internal communication system
associated with the control room both for the normal and emergency operation.
Such a system enables the control room to be kept informed when switching
operations are required or when emergencies arise.
The arrangement of lighting and of the panels themselves is an aesthetic question as well as one of ergonomics. The site supervision engineer will be wise to
ensure that the designers have taken care to ensure that there is adequate access
for the sections of panels being shipped and that there are clear working areas
behind the panels for connection, maintenance and testing. He should also check
that the lighting provides adequate illumination for operation and maintenance
without glare or reflections. The equipment should also be handled carefully as it
can be badly scratched and chipped by carelessness during installation. Instruments
and relays must be checked on arrival to ensure that they have not suffered damage
during transit.
The layout of the equipment on the desks and panels should be such that the
more important switches are nearest to hand and they are accompanied by the corresponding indications. Instruments should therefore be at eye level and switches
at hand level. Switches should not be placed in such a position that they can be inadvertently operated by passing personnel or by carelessly pressing on them with
books or with the hands when leaning. Instruments should not be in a position to
be broken by vacuum cleaners or washing down mops and brushes. Fuses and links
should also be out of harm’s way and should not be so mounted that they can work
loose by vibration.
All control panels and desks must be properly labelled so that there can be no
ambiguity about the purpose of the indication or switch or the circuit being controlled. Many serious accidents have resulted from mistaken panel identities.
The mimic, which is a simplified circuit diagram, permanently secured to the
panel, may itself be illuminated to indicate the status of the various sections of the
distribution network, but it is more usually painted in bright colours using a
different colour for each voltage. It often illustrates only the busbars of the main
switchboards, with the minimum of instrumentation. Designers should ensure that
the order of the circuits from left to right on the control panel corresponds with
50
Handbook of Electrical Installation Practice
Fig. 2.11 Final adjustments being made on a control and instrumentation panel for
Equador. Note the semaphores on the panel front (Arcontrol Ltd).
that on the switchboard. Synchronising equipment must be visible to operators
along the whole length of the control panel.
One of the important aspects from the site engineer’s point of view is the illumination of the cubicles and the method of switching the lighting supply on. Accidents
have occurred from inadvertent contact by electricians with the lighting supplies
and it is essential to ensure that all live wiring is properly shrouded. A control board
is shown in Fig. 2.11.
Low voltage switchgear
The variety of l.v. switchgear is also very wide. Typically a switchboard includes
circuit-breakers for incoming supplies, a bus-section(s), important feeders and
interconnectors, some or all of which may require interlocks. The individual supplies
to equipment such as local lighting and small power, battery chargers, trace
heaters and domestic supplies in general tend to be controlled by switch-fuse units
Substations and Control Rooms
51
or fuse-switches. The difference between a switch-fuse and fuse-switch is defined in
Chapter 16.
Where there is a substantial incoming power supply to an industrial complex, an
air-break circuit-breaker is often utilised.This can be a single cubicle unit with cables
both in and out or it can be the incoming unit on a main switchboard or it can be
connected direct to the switchboard busbar system. Such a unit may be fitted
with CT-operated overcurrent trips with inverse time characteristics, an automatic
operating mechanism and other features such as on/off indication, fuses for
metering supplies, direct acting earth faults trip, auxiliary switches, shunt trip
release and undervoltage release.
Typically these circuit-breakers have thermal ratings up to 4000 A, a short time
rating of 40–50 kA for one second and a short-circuit breaking capacity of a similar
level. One point which is worth noting is that the rated insulation voltage should be
about 660 V. As the normal insulation level of l.v. cable is 1000 V it is possible to
consider the use of 600 V motors and control gear as a means of reducing costs.
Increasingly popular as alternatives to fuses for fault protection are moulded case
circuit-breakers. These are now offered in a wide variety with ratings in excess of
2500 A and breaking capacities up to 150 kA at 380/415 V. They are offered with
either thermal/magnetic or electronic protection. Ratings up to 3000 A and 660 V
a.c. are also available. However, the fault breaking capacity of these may be limited
to 60 or 65 kA.
Open-type power circuit-breakers in compact ranges are available up to 8000 A.
These compact breakers are available in modular form with a wide range of accessories. They can be plugged in with terminal shields. They can be locally or remotely
controlled and they have arrangements for earth leakage, shunt trip or undervoltage release. Auxiliary and alarm switches are fitted and a visible indication is available confirming that in the ‘off’ position all contacts are separated by the required
distance.
The main outgoing cables can therefore be selected taking into account the most
onerous of the circuit duties.
Mechanical strength and protection is also important. For example, vibration may
be significant if the substation is adjacent to a road or heavy machinery. Fire precautions are also necessary if the cables are being run in a confined space where
personnel may be in danger from heat or smoke. Corrosion may also be a hazard.
Single-core cables may cause overheating of adjacent metalwork and can also
produce high induced voltages under fault conditions. They are also a source of
interference unless suitable precautions are taken to segregate them from sensitive
equipment.
The alternative to a circuit-breaker is an isolating switch with or without backup fuses. The isolating switch should preferably have a making capacity of about ten
times and a breaking capacity of about eight times normal full load current at say
0.3 p.f. This is to deal with the stalled rotor current or starting current of any motor
connected to the board. Alternatively on-load switches can be obtained which
provide a capability of making onto a fault and breaking a current of about three
times normal rating.
On the incomer an alternative may be to use a fuse-switch. It is important in this
case that the moving parts are connected to the busbars and not to the incoming
52
Handbook of Electrical Installation Practice
cable, otherwise the fuses are still alive when the switch is open. On those boards
which are protected by a circuit-breaker or fuse at the sending end of the incoming
cable no fusegear is required on the incomer itself. This can then be an isolating
switch using perhaps a fuse-switch with fuses replaced by links of adequate throughfault rating.
For outgoing units the same range of equipment is available, such as air circuitbreakers, mccbs, fuse-switches and isolators, but with the addition of switch-fuses,
i.e. an isolator associated with separate fuses, distribution fuseboards and motor
starters for the control of rotating equipment. All such gear is connected through
busbars of appropriate rating to the incoming supply. It is imperative that the busbars
are adequately insulated and protected from vermin, insects, dust and damp but most
important that they should not be adversely affected by a fault on an outgoing circuit.
There are many ways of cabling a switchboard but the majority have rear access
from the bottom. However, a modern trend is to have front access to the cable
compartments allowing the board to be set against the rear wall. Additional space
is required for aluminium cables, and shrouded terminals are a useful safeguard.
Other variations and accessories available are bus-section switches, packaged
substations where a Class C transformer is directly connected to the switchboard,
power factor correction equipment including the capacitors, relays, contactors and
fuse-switches for automatic multi-stage operation, together with instrumentation,
metering, protective relaying and control switches. A 400 V switchboard is shown in
Fig. 2.12.
Fuses
The various types of fuses available cannot be easily summarised, but in general
high voltage fuses at substations are current limiting. This means that they will clear
the fault before the prospective current reaches its first peak and thus limit both the
mechanical and thermal stresses on the protected equipment.
Low voltage fuses in substations may be selected either to protect the a.c. electricity supply network or, where appropriate, industrial equipment. Special types are
required for semiconductor devices.
Motor starters
Integral with the switchboard or in a separate panel may be motor starters. The
majority of motor starters are direct-on-line designs for cage induction motors comprising contactors which are electrically held-in when energised and incorporating
simple no-volt release and a thermal overload protection: reversing contactors
are a straightforward variation. Star-delta starters giving a reduced voltage across
the star connections of machines are also standard arrangements. The starters are
normally available as combinations with a disconnecting switch and short-circuit
protection in the form of fuses either mounted on the contactor or separately.
These are compact and yet have good access for maintenance, more room to
accommodate aluminium cables, starters which can be easily removed, boards which
can be easily extended and high rating busbars both in terms of normal thermal
rating and also short-circuit withstand. One important feature available in some
Substations and Control Rooms
53
Fig. 2.12 A 400 V power station distribution switchboard incorporating air circuit-breakers
(Electro-Mechanical Manufacturing Co. Ltd).
designs is a cable box for each starter, each with its own gland plate and metal cover
segregating it completely from other circuits. Another feature which is useful to the
client and his installer is the provision of vertical and horizontal cable trunking to
enable interconnecting wiring to be run from starter to starter. This means that
modifications to sequencing wiring or connections to relays controlling the starters
can easily be made either at commissioning or subsequently. Of course the necessary contacts need to be available in the starter. A starter panel is shown in Fig. 2.13.
Auxiliary control equipment
For the control of the contactors and starters there is a wide range of equipment
available including push buttons, rotary switches, solid-state control modules with
input and output interfaces, logic elements and memories, timers, power supplies,
54
Handbook of Electrical Installation Practice
Fig. 2.13 The swing-out design on this l.v. motor control centre gives easy access to the
components (Arcontrol Ltd).
amplifiers, decimal displays and monitoring lights. The system may be enhanced by
providing adaptability. This is the basis of the programmable logic controller which
enables the user to modify the control sequence for most standard system applications. The program need not be finalised before starting the control system design
and assembly. Complete system change can be undertaken by re-employing the
controller on a new installation if required.
Programming is simple and can be undertaken from a small portable ‘memory
loader’ or other form of programming equipment such as a hand-held keyboard and
display unit or a more sophisticated keyboard and VDU. Programming equipment
can be provided also for on-line or off-line use and with hard copy of the logic
statement and can be accompanied by data logging and management reporting.
Such equipment is of course only required for supplies to process plant, automatic
manufacturing, conveying or sorting and other relatively large or sophisticated
installations where the financial consequences of faulty sequencing justify the
costs involved. A programmable logic controller is shown in Fig. 2.14.
Supplies to electronic devices
With the rise in the number of electronic and digital devices, filters may become
necessary to isolate equipment from transient overvoltages and harmonics. It is particularly important to ensure that electronic protection does not inadvertently trip
essential services for no good reason.
Sequencing equipment and energy management systems installed at central
control points, such as substations, should also be isolated from interference by suitable enclosures and by the use of uninterruptible power supply units (UPS). These
Substations and Control Rooms
55
Fig. 2.14 A programmable logic control system (Texas Instruments Ltd).
can be provided with powers up to several MVA and with output frequencies such
as 50, 60 and 400 Hz.They may also have static and manual bypass switches for maintenance or overload. The basic principle is to rectify the incoming supply, to provide
thereby a direct current for charging a battery and to operate an inverter to the
desired frequency of output. The battery acts as a standby source but also provides
an excellent filter and smoothing circuit. If necessary additional units can be combined to provide redundancy for important computer installations. The units would
also normally be supplied with a status monitor which could energise a remote
control unit.
INSTALLATION
Basic design
Consider the installation of a typical 11 kV/400 V substation feeding a main 400 V
switchboard. The main switchhouse may also contain an mcc and a control board
56
Handbook of Electrical Installation Practice
for energy management.The local supply authority provides power at 11 kV through
its own switchgear but the contractor is responsible for installing the stepdown
transformer, cabling the 400 V switchboard, starters and control panels, together
with the auxiliary systems. The premises are not in a hazardous area and while
the loss of supply is financially serious there is no danger inherent in a failure. The
designers have provided a simple single storey building with a shallow cellar
and with separate rooms for a switchboard associated with the transformer, l.v.
switchgear, the mcc and energy management centre, and the battery.
Cabling is run in trenches inside the building and salt glazed ductwork outside.
Earth conditions are reasonable and therefore the design of an earthing system of
low resistance is obtained by sinking four copper rods, one at each corner of the
building. No special provision against lightning is considered necessary. Small
power, lighting, heating and ventilation, fire protection and a telephone system are
provided. A typical layout of the substation is shown in Fig. 2.9.
Programme
The critical path network system shows the best order for the erection and cabling
of electrical equipment which cannot commence until buildings are more or less
complete and the machinery has been installed. On the other hand, once machinery has been installed the purchaser is anxious to have it operational. The site engineer however will be restricted to a reasonably small team of electricians because
only one or two men can work on a switchboard at one time and on large sites there
are accommodation and messing restrictions.
The programme indicates which items must be received on site first and where
access can be made available by the civil constructors. The resident engineer must
ensure that there is adequate storage for those items which arrive early and for
the consumables which are needed to keep the work progressing in an efficient way.
This includes checking that there are adequate lifting facilities and local transport
aids with rollers or trollies for the items which are to be manhandled into place. The
commonest problem of all is to find that the doors are too small for the cubicles. It
is easy to forget that one needs some clearance for the transporter and the protuberances such as relays and operating handles.
Foundations
The foundations for h.v. switchgear must be capable of withstanding whatever shortcircuit forces can be imposed on them together with the vibration of operating
mechanisms. It is also necessary to have a smooth flat floor to prevent distortion of
the cubicles and easy movement of truck-gear. If inset steel rails are called for they
must be checked level to the limits stipulated by the manufacturer and any holdingdown bolts grouted in well before tightening up becomes necessary.
Cable trenches and ducts should be examined to see that they line up with the
terminating points and that there is adequate room for bending cables and laying
them in an orderly manner. All supporting steelwork must be properly fixed to walls
and ceilings by the recommended size and number of insets. All floors, walls and
Substations and Control Rooms
57
ceilings should be properly finished before commencing the erection of permanent
electrical fittings including lighting fittings. Any chases for cable conduit, boxes and
ducting should be completed.
Good practice also dictates that the buildings should have observation panels in
the doors of control rooms, emergency escape doors should be fitted with power
bolts and latches and external doors should open outwards. In tropical or subtropical locations, fly-screens should be provided to all opening windows and exterior
doors. Switchroom ceiling heights should be not less than 3 m with windows fitted
at a high level to provide maximum inside wall space for equipment. Windows
should not be located above outside transformers. Tubular heaters should be
installed if there is no air conditioning, to avoid moisture deposition on equipment,
also air bricks or ventilators should be provided to maintain two or three air changes
per hour. Adjacent transformers should be separated by a fire wall or spaced from
each other or substation buildings by at least 3 m. All transformers should be fenced
in. Special arrangements are required to prevent the spread of oil spillage from
transformers and oil circuit-breakers.
Cable ducts or conduits between a building and a transformer bay must have
means to prevent ingress of oil. This can be done by ensuring that the transformer
end is raised above the level of the ground or pebble infill and is placed directly
below the cable glands.
The floor and foundations must not only be capable of supporting the weight of
any equipment placed upon it but must also be hard enough not to be damaged by
roll-out switchgear and the handling of equipment. This may be overcome by using
steel channels in the floors.
Location of equipment
It is common to place h.v. switchgear in one chamber with access given only to a
person sanctioned by the supply authority. The switchgear under the control of the
customer is placed in a second chamber. However, this is not always the case.
Where transformers are housed indoors, ventilation must be adequate to dissipate their heat losses. Fire-fighting equipment should be provided wherever a
number of transformers and switchgear units are grouped together. Where liquidfilled transformers are installed, adequate drainage to soakaway pits is needed with
a medium such as granite chips or pebbles to help quench any fire arising from an
electrical fault.
Cables require protection from each other to reduce damage from an electrical
fault and limit the degree of interference in the event of a fire. Complete separation of the lower and higher voltage cables is desirable. All pipes and ducts should
be effectively sealed to prevent the ingress of vermin. Where the installation of a
substation is indoors, the problems of ventilation and transformer cooling conflict
with the reduction of transformer noise to an acceptable level. Some form of compromise may have to be made. For instance, sound attenuators placed in the air inlet
and outlet vents reduce the efficiency of the cooling system and must be allowed
for in the design. A vertical duct provides a chimney effect and may assist air flow
across the transformers. However, on other sites forced cooling with fans may be
58
Handbook of Electrical Installation Practice
the only solution. Transformers should preferably be mounted on anti-vibration
pads and any pipework arranged so that a minimum of vibration is transmitted to
the building structure.
Fire fighting
The layout of the plant and the design of the building play a major part in reducing the spread of fire and the effect of explosions. For example, equipment and
buildings should be arranged to have vents which rupture rather than allowing an
explosion to damage the main fabric. Site supervisors should ensure that these vents
are never obstructed. In the prevention of fire, cleanliness and tidiness are very
important, as is the careful maintenance of tools. Most fires are caused either by
carelessness or faulty equipment.
The choice of fire-fighting equipment is dependent on its suitability for electrical
fires but also on cost and the importance of the electrical supplies at the point in
question. Portable manual types are as follows: halon gas of various kinds, carbon
dioxide chemical foam and powder.
Fixed systems use water sprinklers, carbon dioxide and halon gas. Both halon
gas and carbon dioxide can suffocate personnel trapped in the discharge area.
Strict precautions must therefore be taken to lock-off the equipment when staff
are present. There is also the used of sand, blankets and fire hoses. Fire doors are a
very important means of limiting the spread of fire, and ventilating systems should
also be provided with automatic shut-down if not with automatic dampers in the
event of fire. Fire drill is also important and should not be neglected on a building
site.
Cabling may also be a cause of serious fires with risks of extensive damage to the
installation and danger to personnel. Low smoke and fume (LSF) cables are now
available in a number of forms, most of which will reduce the flammability as well
as causing less poisonous gas to be released when they are heated.
The d.c. supplies are a particularly important and vulnerable part of any installation. They are generally derived from stationary batteries which give off flammable
and toxic gases. Batteries should be in a separate room with an acid-resistant floor,
special lighting fittings, a suitable sink and adequate water supplies. It is wise to have
an acid-resistant drainage system. The room must be properly ventilated but sunlight must not be allowed to shine directly on to the cells.
ERECTION PROCEDURES
Once the equipment is on site there is a need to follow a well-defined procedure
for inspection, erection, testing and commissioning.
High-voltage switchgear
Before commencing erection of h.v. switchgear check that all connections are
tight on busbars and on main and auxiliary circuits. Examine the insulation carefully, because there have been cases of burned out connections due to failure to
Substations and Control Rooms
59
observe this precaution. Obvious faults such as distorted panel work, broken
meter glass and damaged packing cases should be noted and immediate steps taken
to rectify the damage or to return the equipment to the supplier. After erection,
steps must be taken to prevent deterioration of the equipment due to damp,
dust or casual damage. Substations should be cleared out and locked fast and
should not be used as a site office, store or workshop after the equipment has been
installed.
When all erection and jointing work is complete the equipment must be inspected
and thoroughly cleaned to remove cuttings of cable, spare nuts, washers, accumulations of dust or copper filings and tools which may have been left behind. However,
it is dangerous to blow out equipment because dust, filings, light metal scraps, rags
and sawdust can be blown into positions where they become inaccessible and may
pass unnoticed. It is better to clean manually and vacuum the plant. An important
point to remember is the removal of all packing materials particularly in moving
parts, and of course make sure that oil circuit-breakers receive their first filling of
water-free oil.
In the erection of the switchgear the following points should be emphasised.
Where steel channels are used as foundations, ensure that they are correctly laid
to an accuracy of about ±1 mm in 3 m. Use a masking strip to prevent fouling by
the floor materials. Read and apply the manufacturer’s erection instructions and
use the correct tools such as torque spanners to obtain the appropriate tightness of
nuts. Make sure equipment is properly aligned. This means vertically and horizontally in both longitudinal and lateral directions. Incorrect alignment causes
problems during operation of mechanical linkages and connections, difficulty in
removing and replacing circuit-breakers and other withdrawable parts and puts
stress on interpanel connections such as busbars and earth bars. When the floor is
being laid and there are no steel inset channels, it should be level both front to back
and should not vary by more than a millimetre or so between cubicle centres. When
the floor is being laid it is common practice to form pockets at the foundation
hole positions in order to avoid having to cut them out of the solid floor at installation time. The floor should be marked out in accordance with the switchgear assembly drawings usually provided by the manufacturer to ensure that the
switchgear is correctly located with respect to cable trenches, building walls and
other equipment in the room.
A datum line requires to be established usually along the rear foundation bolts,
and using normal geometric methods the switchboard and foundation bolt holes can
be located. The method of positioning the equipment is dependent on a number of
factors such as equipment size, building location, site accessibility and lifting tackle
available. Lifting eyes are often either incorporated into switchboards or can be
screwed into pre-machined holes, but generally slinging is necessary and this should
be done strictly in accordance with the manufacturer’s recommendations. Without
the use of cranes, however, the traditional manual methods utilising jacks and roller
bars are effective. Care must be taken not to exert pressure on weak parts such as
control handles during this manhandling. Positioning of the cubicles should start
near to the centre of the switchboard, installing as early as possible the enclosures
associated with any special chambers or trunking. The first enclosure should be positioned and checked to ensure the side sheets are plumb and that any runner rails
60
Handbook of Electrical Installation Practice
are level in both planes. When the first enclosure panel is correctly set the remaining enclosures should be positioned successively on alternate sides of this panel to
make the front form an unbroken line.
Adjacent enclosures should be bolted together after they have been correctly
aligned using whatever shimming proves necessary to make sure that the cubicles
are vertically and horizontally true. The fixing bolts should be positioned in the
foundation holes and cemented in leaving adequate time for the cement to set
before tightening up.
The equipment may now be connected up and cable joints made. In particular
one must confirm that the earthing of the equipment has been carried out using the
recommended cross-section of material and satisfactory terminations.The l.v. system
must then be proved for continuity, preferably by using a hand generator or other
portable device and with a current of about 1.5 times the design current. A further
examination of all incoming and outgoing circuit and auxiliary cables, including a
test of the correctness of the connections at the remote ends, should be done; this
should include measuring the insulation resistance and continuity of all cables and
wiring including internal and auxiliary connections. Where appropriate, phase rotation checks must be made before three-phase drives are energised. All moving parts
must be inspected to ensure they are all operative. Dashpots must be filled to the
correct level with the right grade of fluid, and the operation and accuracy of meters
and relays by secondary or primary injection tests should be checked. All settings
should be agreed with the client’s engineers.
All cable boxes must be properly topped up and compound filling spouts
capped off. All insulators and spouts must be clean and dry and cover plates
securely bolted up with all screws in position and tightened and breather vents
clear of obstruction. Ensure that the top of the equipment is free from all dirt and
rubbish.
A final check on all incoming and outgoing cable connections to terminals ensures
that they are tight and have adequate clearance. High-voltage testing can then be
carried out to the test figures laid down in the appropriate BS switchgear specification or as specified by the client’s engineers who should witness the tests and sign
the test results.
After testing, precautions must be taken to discharge any static and remove the
test connections before bolting up any covers removed for testing. Before energising, the operation of all circuit-breakers and relays should be confirmed manually
and electrically to ensure that no sticking or malfunction is present, particular attention being given to manual trip and close operations and to the operation of overcurrent relays and residual current devices. When the equipment is ready to make
alive all circuits not in service shall be locked off at each end and safety operation
procedures adopted. All switching operations should be carried out by a competent
person.
The substation’s entry and emergency exist doors must be operative and kept
clear and free from obstruction. All substations should be kept locked when the
equipment is live, and access restricted to authorised personnel only. Danger, safety,
shock cards and any statutory notices must be prominently displayed.Tools required
for operating switchgear should be stored adjacent to the equipment in proper racks
or cabinets. Circuit and interlock keys should also be contained in special cabinets
Substations and Control Rooms
61
under the control of authorised personnel and no spare keys must be allowed to
abort the safety of the system.
Batteries should be examined to ensure that they have received their first charge
and the electrolyte is at the correct level and of appropriate specific gravity. The
fire-fighting requirement should be checked and if it is CO2 it must be confirmed
that the safety lock-off procedure is understood by the personnel authorised to
enter the substation. External warning notices must be fixed to protect any strangers
from inadvertently suffocating.
Transformers
Chapter 13 deals with transformers and their installation so we restrict ourselves
here to the procedures associated with their commissioning. Transformers should
be inspected for internal or external damage, particularly if they have been dropped
or tipped over. This should include such items as drain valves, selector switches, conservator tanks, Buchholz relays and winding temperature indicators. All transformers must be tested for winding insulation resistance and the readings confirmed as
acceptable. However h.v. d.c. tests on a cable connected transformer cannot be done
because the windings of the transformer short out the d.c test set.
If between-core tests are required on transformer feeder cables after installation
then a link box must be provided to disconnect the cable from the transformer
windings. If transformer covers are taken off to achieve internal disconnection
the tools used must be clean and secured externally by white tape so that they
may be recovered if inadvertently dropped. All nuts and washers must be accounted
for and all operatives should be asked to empty their pockets while working
over the open tank. Waterproof covers should be provided during the period when
the transformer tank is open. If it is not possible to disconnect the cables after
jointing they must be tested beforehand. This means that the jointing and testing
programme must be carefully planned to avoid leaving cable ends unsealed for long
periods.
Transformer diagrams should be inspected and the phasing diagram confirmed as
correct. Also before energising, the voltage selector must be set on the appropriate
tapping having regard to the voltage level of the system. Transformers which are to
operate in parallel must be set on the same tapping and they should be checked as
having the same impedance. Voltage selectors should be locked in their set position
and if they are of the ‘off-circuit’ type they must not be adjusted without the supply
being first switched off. Earthing arrangements for the tank and the neutral or other
system earthing must be confirmed and completed before testing and commissioning. Where special tests for losses, ratio, phase angle or winding resistances are specified the assistance of the manufacturer should be sought.
The following points should be checked on the particular type of transformer as
appropriate.
Oil immersed naturally cooled (ON)
Ensure that the oil level is adequate and that breather tubes are clear. Commission
silica gel units by removing the airtight seals from the cannisters and filling the oil
sealing-well to the correct level with transformer oil. The colour of the silica gel
62
Handbook of Electrical Installation Practice
must be checked and the filling changed if it shows dampness (red for wet, blue for
dry).
Dry-type transformers
As dry-type transformers are more susceptible to external damage they must
be carefully handled and stored on site. They must also be kept in a dry, warm
atmosphere until they are put in service, to prevent ingress of moisture. Satisfactory
insulation tests are imperative before commissioning. Because they are wholly
dependent on surface radiation and air convection for cooling, they must be
checked for any accumulation of dust or dirt which can block the air ducts and
reduce the flow of air. Cleanliness is essential, particularly where the connection
leads leave the windings and at the terminal supports. Damp dust leads to tracking
and causes expensive damage. It is particularly important to check such transformers for dust in package substations which may escape the notice of commissioning
staff.
Meters, relays and protection equipment
Because these are precision items they must be treated with care and any broken
glass fronts replaced immediately before dust and damp damage the mechanism
permanently. If the operation of a relay or instrument is unsatisfactory it should not
be adjusted without the proper tools and sound knowledge of its function and construction. It is often possible to improve the operation at one particular setting but
render it completely ineffective over other important parts of its range. A relay
setting study should have been done by the design engineers to provide the setting
instructions for site commissioning staff.
Arbitrary settings are unlikely to be more than a stop gap and can create a dangerous situation which should not be allowed to persist. Fuller details of protective
gear operation are given in Chapter 22.
Motor starters
Before energising motor control equipment ensure that both motor and starter are
correctly earthed. Check that all packing equipment has been removed and that
equipment is free to operate. The starter rating should correspond to that of the
motor. Set the overload protection devices to the correct point for the operation of
the motor and its protection. Check that all dashpots, tanks and oil immersed resistor banks are filled with the correct grade of oil or other filling medium. Confirm
settings of overloads by injection testing for all large or critical drives. Confirm
the insulation resistance readings of starter, main and auxiliary wiring and motor.
Confirm the rating of short-circuit protective fuses against the type of starter
and rating of the motor. Ensure resistor banks are adequately ventilated and not
obstructed either by other equipment or rubbish. Check that the motor drives are
free to operate and that there is no danger to other personnel before starting
up the motors. Check that remote start/stop buttons or emergency stop buttons
are operative before energising the plant, and that the motors rotate in the correct
direction.
Substations and Control Rooms
63
Distribution boards and switch-fuses
After testing all insulation, phasing and earth continuity ensure that the ratings and
types of all fuses are suitable for the circuits before they are energised. Make sure
that the fuses are the right type for the fuse carriers provided, and that the ratings
are correct for the size of the cable or for the load supplied, whichever is the smaller.
This will also confirm that the circuit wiring is correct for the load to be supplied.
HBC fuse carriers must not be fitted with wire elements because the enclosure is
not suitable.
In distribution boards wiring disposition should be examined and all wires dressed
clear of live metal work.
Terminal connections on incoming and outgoing cables must be tested for tightness, correct stripping of insulation and clearances. Where a number of neutrals
enter a distribution board they should be sensibly disposed along the neutral bar in
the same order as that of the live conductors.
Earthing arrangements
The earthing of l.v networks in the UK is largely determined by the l.v. supplies.
However, if the incoming supplies are at 11 kV and the transformers are in the
ownership of the user, the l.v. supplies may be earthed in a less conventional way
using a high impedance. This arrangement is not allowed for public supplies.
However, it is a useful system when it is more important to maintain supplies than
it is to clear the first earth fault. For example, an emergency lighting scheme for the
evacuation of personnel from a hazardous area could use a high impedance system
if it were considered less dangerous to maintain supplies after a first earth fault
than to disconnect the light completely. The Channel Tunnel could be such a case.
Even in these circumstances the original earth fault should be corrected as quickly
as possible.
The more conventional earthing arrangements are TN-C where the earth and
neutral are combined (PEN) and TN-S where they are separated (5 wire) or TN-CS. The latter is very common as it allows the single-phase loads to be supplied by
phase and neutral with a completely separate earth system connecting together all
the exposed conductive parts before connecting them to the PEN conductor via a
main earthing terminal which is also connected to the neutral terminal.
For protective conductors of the same material as the phase conductor the crosssectional area shall be the same size as the phase conductor up to 16 mm2. When
the phase conductor is above 16 mm2 then the protective conductor may remain at
16 mm2 until the phase conductor is 35 mm2, after which the protective conductor
should be half the size of the phase conductor. For conductors which are not of the
same material the cross-sectional area shall be adjusted in the ratios of the factor k
from Table 43A in BS 7671. The k factor takes into account the resistivity, temperature coefficient and heat capacity of the conductor materials and of the initial and
final temperatures.
Lastly there is the TT system which uses mother earth as part of the earth return.
The neutral and the earthed parts are only connected together via an electrode
system back to the source earth (and neutral). To check that conventional systems
64
Handbook of Electrical Installation Practice
are satisfactory, i.e. that the protection operates on the occurrence of an earth fault,
it is necessary to calculate the earth fault loop impedance (Zs) and ensure that the
fault current through it will cause the protection to operate.
This is quite a tedious process, involving as it does the calculation of the impedances afforded not only by the earth return but also by:
(1)
(2)
(3)
(4)
The phase conductor
Supply transformer
Supply network
Any neutral impedance.
This information must be requested early. The Electricity Distributor should be able
to give the fault level or the equivalent impedance of the supply network and
the manufacturer can provide the appropriate impedances for the transformer.
However, time will be required to obtain the answers so enquiries should be made
at the commencement of the project.
The substation will house the circuit-breakers of fuses for the main cable connections to the sub-distribution boards and motor control centres. These protective
devices must discriminate with those further down the line nearer the ultimate
loads. A system study must therefore establish the correct ratings of the substation
equipment to discriminate with the distribution network. This subject is described
in Chapters 3 and 4.
Earthing of equipment should be electrically complete and confirmed mechanically sound and tight. Earthing conductors (previously termed earth leads) must be
checked for compliance with the IEE Regulations, i.e. they must not be aluminium
and they must be not less than 25 mm2 for copper and 50 mm2 for steel, unless they
are protected against corrosion. These conductors are for connection to the earth
electrodes.
The protective conductors previously known as earth continuity conductors must
also comply with BS 7671 (the IEE Regulations) and in general for phase conductors of less than 16 mm2; this means the protective conductors must be the same size
as the phase conductors. When the phase conductor is above 16 mm2 then the protective conductor remains at 16 mm2 until the phase conductor is 35 mm2, after which
the protective conductor should be half the cross-sectional area of the phase
conductor.
Another important point to bring out is that the earthing conductor to the earth
electrode must be clearly and permanently labelled ‘SAFETY ELECTRICAL
CONNECTION – DO NOT REMOVE’ and this should be placed at the connection of conductor to the electrode. Fuse ratings should also be checked in relation
to other fuse ratings in the supply circuit or against the settings of protective relays
to assure correct sequence of operation and discrimination. Circuit charts for distribution boards should be completed and designation labels fitted to ensure safe
operation of switches and isolators. All tests should be carried out as required in BS
7671, Part 7, and an Electrical Installation Certificate given by the contractor to the
person ordering the work.
Many installations now incorporate rcds and fault-current operated protective
devices. These also must be tested using appropriate test equipment, full details of
Substations and Control Rooms
65
which can be found in BS 7671 or for more elaborate apparatus in BS 7430 and
Guidance Notes which are published separately and amplify the requirements in
the British Standard.
The nominal voltages at present are:
230 V + 10% and -6%
400 V + 10% and -6%
Further consideration of the voltage tolerances is expected in 2008.
Record drawings
Site staff should prepare ‘As fitted record drawings’ as a matter of course. The
contractor’s resident engineer should ascertain who in the client’s organisation
is responsible for approving and accepting the completed ‘As fitted’ records. He
should then make sure of the form, size, scales, title block and other information
required before commencing the drawing work. Normally the ‘As fitted’ records are
marked up on a set of prints of the contract drawings and sent back to the drawing
office at the contractor’s headquarters for preparation of the master transparencies.
Frequently it is worthwhile obtaining blank transparencies of building outlines so
that prints can be obtained for marking up with different ‘As fitted’ records such as
lighting, power, earthing, telephones, trenches, cabling equipment arrangements and
so on.
In addition to layouts and arrangements the final schematic and wiring diagrams
will probably be required to assist in fault-finding or subsequent extensions.
Another common requirement is to provide cable routeing and apparatus location records for all special systems such as fire alarms, clocks, bells, telephones,
smoke detection, l.v. systems, public address and music speakers, temperature/
humidity control, instrumentation, emergency lighting, underfloor or wall trunking systems and underfloor heating systems including the positions of all repair
joints and joints to cold tails. Also required are circuit charts for each distribution board showing the correct fuse ratings for each circuit and the names of the
outgoing circuits, lighting fittings schedules, switchgear arrangements, wiring diagrams, connection diagrams and details of instruments relays and protective gear
settings.
For transformers the client requires general arrangements, fittings, cable box
connections, vector diagram and rating plate details, including voltage ratios and
tapping switch range, connections to earth (neutral and tank) temperature gauge
and earth leakage devices. The tap setting on which the tapping switch is locked
should be recorded.
Earthing and lightning protection system records, see Chapters 7 and 9, should
show the location and layout of individual electrodes, the position of test links, a
record of earth resistance readings as installed, connections to water pipes, building
structures, items of plant and other incoming services such as gas or oil and the position of lightning protection filials and down conductors. Incidentally, lightning conductors must never be run inside steel pipes or conduits as the impedance of the
path is very high to typical lightning surges.
66
Handbook of Electrical Installation Practice
Underground cables should have the following information recorded in addition
to the route: tie-in dimensions of all trenches to fixed points on the site layout (these
points should preferably be themselves cross-referred to identifiable permanent features), positions of all marker posts, i.e. joint and route markers, positions of underground ducts through roads into buildings, positions of entries or manholes into
ducts, core connections at through and terminal joints, positions of all underground
joints with tie-in dimensions, schedules of joints giving date and name of jointer,
depth of laying, depth of ducts and of joints, whether cables are protected by tiles
or covers and of what size and type, and positions of cables in trays and ducts to
assist in identification. Maintenance manuals must be supplied for all specialised
equipment.
It is important that the correct procedure for obtaining the client’s approval is
followed and that his representative should be given the master ‘As fitted’ drawing
to be signed only after it has been thoroughly checked both by the site engineer
and the contract engineer.
CHAPTER 3
Site Distribution Systems
M.G. Twitchett, IEng, FIIE, MSOE, MIPlantE
(Consultant, Electrical and Plant Engineer)
The purpose of a site distribution system is to provide a means of economically and
reliably distributing power from one, or occasionally more than one, main location
to a number of geographically dispersed load centres within a defined site boundary. The source of power is usually an intake from the local Distribution Network
Operator (DNO) but may also be from on-site generating plant. The economics of
the system will be largely dependent on the voltage at which it is decided to operate
it. The ability of the system to reliably supply power to where it is needed and
when it is needed will depend initially on the quality of the equipment and the
installation workmanship. In the long term it will depend also on the flexibility available to continue to supply that power to where it is needed, despite the need to
maintain parts of the system and possibly despite the occurrence of faults on
the system. While much that will be discussed may also apply to distribution
systems within buildings (especially buildings with a large electrical demand), such
installations are dealt with in Chapter 4.
If the site is other than very compact or has only low demand, it is likely to prove
economic to distribute power at high voltage rather than at 400 V. (Throughout this
chapter the term ‘high voltage’ is used to mean ‘exceeding 1000 V a.c.’ as is commonly understood in UK practice. It should be noted that the term ‘medium voltage’
meaning ‘exceeding 1000 V but not exceeding 12 000 V’ is used in some other countries and due to the globalisation of markets this meaning is increasingly being
encountered in the UK.)
Most DNO local distribution networks operate at 11 kV or in some localities at
6.6 kV, and in most cases it is usually sensible to distribute power around the site at
this ‘intake voltage’. When the supply is provided at high voltage the DNO does not
have to provide the step-down transformers or pay for the losses in those transformers. The electricity can therefore usually be purchased at lower cost when taken
at high voltage. The level of demand which makes this economically viable must be
assessed in the early stages of design.
This book is confined to systems up to 11 kV but it should be borne in mind
that on some very large, high demand sites it becomes economic to take a supply
at 33 kV or even 132 kV. It is unusual, however, for the consumer to operate the
site network at more than 11 kV.
The capital cost implications of operating at, say, 11 kV become clearer if one
considers as an example the need to transmit 500 kVA over a distance of 500 m. At
67
68
Handbook of Electrical Installation Practice
400 V this would require two 4-core cables of 240 mm2 in parallel (assuming a
requirement for a neutral). The cost of 1000 m of such cable would be in the region
of £14 600. While in theory the same power could be conveyed at 11 kV by a 3-core,
6 mm2 cable, in practice the smallest available cable for this voltage is likely to be
3-core, 25 mm2. Nevertheless the cost of 500 m of this cable would still only be in the
region of £3000. A transformer would be needed at the remote end and a 500 kVA
oil-filled transformer would cost approximately £4700. The 11 kV system would thus
show an approximate saving of almost £7000 over the 400 V system for what is quite
a modest power distribution requirement. (These calculations are based on prices
at December 2001.)
INTAKE ARRANGEMENTS
While low voltage intake arrangements are generally simple single feeders there are
many possible configurations for the interface between the consumer and the DNO
on high voltage supplies. Some of the more common arrangements are described
below.
The exact point of demarcation between the consumer and the DNO should be
the subject of formal agreement. It becomes particularly important, and sometimes
contentious, in the event of faults and the allocation of repair costs and may sometimes be pin-pointed down to the cable lugs and the bolts securing them inside a
cable box. The simplest arrangement is for a single transformer to be owned by the
consumer with the h.v. switchgear supplying it owned and operated by the DNO, as
shown in Fig. 3.1. This arrangement relieves the consumer of any high voltage
switching duties but makes him completely dependent on the DNO for making live
the transformer or isolating it for maintenance. (Facilities are usually provided to
Fig. 3.1 A single high voltage intake with h.v. switchgear under control of the DNO.
Site Distribution Systems
69
Fig. 3.2 Single feeder h.v. DNO supply with consumer’s h.v. switchgear.
enable the consumer to trip the DNO’s switch or circuit-breaker in an emergency,
but not to reclose it.)
Fig. 3.2 depicts a more flexible and more common arrangement for a single feeder
supply from a DNO. Both the DNO’s and the consumer’s circuit-breakers or
switches are effectively connected to one set of busbars, but responsibility for the
busbars changes at the declared point of demarcation. With this arrangement the
consumer has control over his own network ‘downstream’ of his circuit-breakers or
switches but there is mutual dependence for isolation of the busbars.
Where the security of duplicate DNO feeders is required the most common
arrangement is as shown in Fig. 3.3. In this arrangement the DNO’s section of the
busbars often forms a part of a ring main. It may be equipped with either circuitbreakers or fault making/load breaking switches. The consumer’s circuit-breaker
(sometimes referred to as the metering circuit-breaker) is actually configured as a
bus-section switch and is normally the responsibility of the DNO. There is mutual
dependence for isolation of the consumer’s section of the busbars although the
DNO is still able to keep its section of the busbars in service. In some cases the
entire switchboard will be within one room but quite commonly the DNO section
Fig. 3.3 Typical duplicate feeder DNO h.v. intake arrangement.
70
Handbook of Electrical Installation Practice
Fig. 3.4 Duplicate DNO feeders supplying sectioned busbars.
will be partitioned off or in a separate room to the consumer’s gear. In such cases
either a busbar extension chamber or a bus-zone cable is used to carry the busbars
through the dividing wall. In critical cases where a greater degree of supply security and flexibility is required, an arrangement like that shown in Fig. 3.4 may be
necessary. Here the DNO is usually responsible for the centre section of the switchboard and the bus-section circuit-breaker as shown.
The factors that must be carefully assessed before deciding on the intake configuration are as follows:
(1)
(2)
(3)
(4)
(5)
(6)
Effects on the business of partial and total losses of supply
Required availability
Likelihood of faults on either DNO’s or consumer’s equipment
Maintenance requirements
Possibility of and economics of generator usage to cover supply outages
Cost
Consultation with the local DNO is required at an early stage in order to agree on
a mutually acceptable design of intake substation and on the division of ownership
and responsibilities. Accommodation for the DNO’s equipment will be required and
they will require easy access to it at all times. All these aspects should be the subject
of a formal agreement signed by both parties. Provision for metering must also be
made and in this connection it is very probable that the consumer may wish to purchase electricity from a supplier other than the DNO and that provision should be
made to accommodate sophisticated metering with remote monitoring.
SITE DISTRIBUTION NETWORKS
As with the configuration of the intake arrangements, so there are similar decisions
to be made regarding the configuration of the distribution network and its cost.
Local supplies may be required at other than 400 V if large motor drives operating
Site Distribution Systems
71
Fig. 3.5 Single radical feeders supplying load centres.
at high voltage (usually 3.3 kV or 6.6 kV but occasionally at 11 kV) are to be
installed. The simplest arrangement is to supply single transformer substations via
single radial feeders emanating from the intake substation, as shown in Fig. 3.5. The
major disadvantage of this system is that supply to any particular load centre will
be lost if any outage due to a fault or for maintenance occurs on any item on the
single supply route. Increased security of supply can be achieved by providing duplicate radial feeders and transformers, as shown in Fig. 3.6. If the transformers are
each rated to carry the total local load, and bus-section circuit-breakers are installed
on the l.v. switchboard, greater flexibility is afforded to deal with maintenance or
faults.
Probably the most cost effective and common means of providing duplicate
feeders to all the load centre substations is to employ one or more ring mains. Figure
3.7 shows a typical ring main supplying a number of both single and two transformer
substations of various configurations. Such a system enables all substations to be
supplied in the event of an outage of any one leg of cable on the ring.
For economic reasons most ring mains incorporate substations equipped with
fault making/load break switches rather than circuit-breakers on the ring main cable
feeders. Such switches do not provide automatic means of opening in the event of
faults. It is therefore good practice in normal circumstances to operate the ring-main
with one of the switches (at some strategically suitable point) open, so that a fault
anywhere on the system only causes a loss of supply to the substations on that side
of the network.
If the fault is on a cable (which is the most likely event), once it has been located
switching can be carried out to isolate the defective leg and restore supplies to all
the substations. Of course, if a fault occurs on the busbars of one of the substations
72
Handbook of Electrical Installation Practice
Fig. 3.6 Duplicate feeders and duplicate transformers.
(a rare but not unknown occurrence), then that substation (or section of busbars if
provided with a bus-section switch) must be repaired before its supply can be
restored. The location of faults is greatly facilitated by the provision of earth fault
indicators at each cable terminating box around the system. These make unnecessary the practice of repeatedly closing onto a fault in order to locate its whereabouts,
or the time consuming technique of isolating each section in turn in order to conduct
insulation tests.A visual inspection of the earth fault indicators will determine which
section of the ring main is faulty. Earth fault indicators with remote monitoring are
also available at increased cost which must be balanced against the cost of delay in
locating the fault and carrying out the necessary switching to restore supplies.
Where continuity of supply is crucial and even short unplanned outages due to
cable faults cannot be tolerated, it is necessary to provide circuit-breakers throughout the ring main and to operate the system as a closed ring in normal circumstances.
In this mode of operation conventional current and/or time graded protection will
not provide proper discrimination since the direction of power flow around the ring
main is likely to vary under different load conditions. In order to provide continuity of supply to all substations in the event of a cable fault, it is therefore necessary
to employ a differential protection scheme for each leg of the ring main or to install
a suitably graded scheme utilising directional overcurrent and earth fault relays.
ON-SITE GENERATION
Generators may be installed on site for one or more of the following reasons:
Site Distribution Systems
73
Fig. 3.7 A typical h.v. ring-main system.
(1) Standby in the event of loss of DNO supply
(2) Total stand alone system, possibly incorporating combined heat and power
(CHP)
(3) Peak lopping
(4) Utilisation of available process steam through a pass-out turbine.
Site generating plant may be operated in a number of different modes:
(1) ‘Island mode’, i.e. disconnected from any DNO supply
(2) In parallel with the DNO under normal conditions
(3) In parallel with the DNO supply only briefly to permit continuity during
changeovers.
Consultation and formal agreement with the DNO are required if paralleling with
their supply, even briefly, is envisaged. Where generating plant is intended to have
a ‘standby’ role it is essential that the risks that it is intended to cover are fully
assessed and that it is decided in exactly what circumstances its deployment will be
required. For example, in Fig. 3.8 the 11 kV generator provides an alternative in the
74
Handbook of Electrical Installation Practice
Fig. 3.8 Generator connected to h.v. intake substation.
event of a loss of the DNO supplies but cannot be deployed if the intake substation busbars have to be isolated for maintenance.
Generators may be provided at strategic low voltage switchboards in order to
maintain supplies to essential loads in the event of either loss of the high voltage
DNO supply or outages on parts of the site high voltage network. In some cases
such generators are used to ‘backfeed’ the site h.v. network by using the local transformer in a ‘step-up’ mode in order to provide emergency supplies to the entire site,
as shown in Fig. 3.9. (Precautions must of course be taken to avoid backfeeding into
the DNO system.) However, in the majority of cases all the transformers on the h.v.
network will have delta connected h.v. windings, usually vector group Dyn11. It
would be more appropriate to connect a low voltage generator to the high voltage
network via a transformer with star connected h.v. windings, (e.g. vector group
YNd11). If the h.v. network is supplied from delta connected transformer windings
when disconnected from the DNO supply, then the site h.v. network is operating
without any earthed reference point, and normal earth fault protection schemes will
be ineffective. If an earth fault were to occur on the unearthed system it would therefore go undetected. Beside the obvious undesirability of the system continuing to
operate with an earth fault, there is the possibility of damage to any voltage-graded
insulation in machine windings. In order to overcome this problem either a starconnected earthing transformer should be connected to the system or, perhaps
less expensively, the system could be protected by a neutral point displacement
relay supplied from a special voltage transformer and arranged either to disconnect
the system or to initiate an alarm.
SWITCHGEAR
While switching devices with a wide range of capabilities is possible, the devices that
generally have practical application on h.v. site distribution networks are:
Site Distribution Systems
75
Fig. 3.9 Generator connected to l.v. substation.
(1) The circuit-breaker – a device capable of making and interrupting short-circuit
current as well as operating on load current
(2) The fault making/load break switch – capable of operating on load current and
of making short-circuit current but cannot interrupt short-circuit current
(3) The switch-fuse – a fault making switch with series fuses. (Such units are often
provided with ‘striker pin’ fuses arranged to open the switch in the event of any
fuse operating.)
All three of these devices have in the past been used in both fixed and withdrawable extensible patterns but current common practice for site distribution substations is to employ ring main units (RMU). Modern ring main units are often
gas insulated with a single pressure vessel containing sulphur-hexafloride (SF6).
Two ring main switches and either a small SF6 or a vacuum circuit-breaker to supply
the local transformer, are contained within this pressure vessel. Extensible versions
of such switchgear are also available for use where flexibility of the substation
configuration is required. Remote operation of such switchgear can be provided
by compressed gas or low voltage electric actuators controlled via a supervisory
control and data acquisition (SCADA) system. Oil-insulated RMUs and individual
switches and switchfuses have been extensively employed in the past and are still
available.
76
Handbook of Electrical Installation Practice
While circuit-breakers are more expensive, they provide the advantage of being
capable of automatic and remote operation and are generally employed where rapid
action to restore supplies following a fault is necessary, or where it is desirable to
operate a ring main in a closed mode. Both fixed and withdrawable pattern circuitbreakers are available. In the case of the former, off-load isolators are usually provided on either side of the circuit-breaker, whereas in the latter the circuit-breaker
is truck mounted and may be bodily withdrawn from the switchboard. Until recent
years the vast majority of circuit-breakers used in h.v. site distribution systems were
oil-filled, with a small proportion of the air-break type. The current choice will probably lay between vacuum and gas (SF6) types.
When specifying h.v. switchgear it is important to ensure that provision is made
for proper means of isolating and earthing busbars, cables, transformers and any
other connected apparatus on which work will at some time need to be carried out.
Low voltage switchgear is generally of the air-break type and in the rare case of
it forming part of a site distribution system, it is unlikely to need to be essentially
different from its normal application at a l.v. load centre.
CABLES
For h.v. distribution services, cables having polymeric insulation, usually cross-linked
polyethylene (XLPE), are finding favour over PILC types due mainly to the simplicity with which they may be terminated and jointed. The most usual construction
is XLPE/SWA/PVC. For l.v. systems the ubiquitous PVC/SWA/PVC is generally
satisfactory. Where cables are routed through buildings or in cable tunnels, safety
requirements may in some cases dictate the use of low smoke/low fume cable types.
The choice between copper or aluminium conductors and, in the case of aluminium, solid or stranded construction, is influenced by cost and the practicalities
of installation. Aluminium cables, where they are known to be such, are much less
likely to be the subject of theft while awaiting, or during, installation.
As in any installation, conductor sizes must be chosen to meet the requirements
of both current-carrying capacity and acceptable voltage drop. With regard to
current-carrying capacity, decisions should be based on the usual factors and need
not be discussed here. The question of cable size in relation to voltage drop is less
clear. For low voltage systems the requirements of BS 7671 (IEE 16th edition) are
deemed to be satisfied if the voltage drop between the origin of the installation and
the fixed current-using equipment does not exceed 4% of the nominal voltage of
the supply. This can be construed as being applicable to a ‘site distribution system’
operating at low voltage but there is at present no equivalent standard for high
voltage systems. Where a h.v. system is supplying power to be utilised entirely at l.v.,
the voltage drop on the h.v. system may not be as important and can usually be compensated for by tap selection on the transformers at the load centre substations.
(Overvoltage under light load conditions must not then exceed a value that might
be damaging to the connected equipment.) Where loads such as large motors are
supplied directly at the h.v. system voltage, cable sizes should be selected to limit
the voltage drop to a value acceptable to the manufacturers of the equipment in
question.
Site Distribution Systems
77
CABLES INSTALLATION
Since this chapter deals with site distribution it is not intended to describe here cable
installations within buildings, although it should be recognised that some parts of
the site distribution network may well be within buildings either in ducts or cable
trenches or on cable tray or ladder systems.
The major proportion of route cable length is however likely to be laid underground. Where the ground may be easily opened up for subsequent access to the
cables they may be buried directly in the soil. In locations where cables are to pass
beneath roads, railways or large areas of concrete or tarmac, the cost and inconvenience of subsequent excavation (and reinstatement) to gain access to the cables
makes it desirable to run them in suitable ducts, at least beneath these areas. Where
ducts are employed it is necessary to provide draw-pits at all bends and at approximately every 50 m on straight and level runs. Closer intervals may be required in
adverse circumstances. Figure 3.10 illustrates a typical draw-pit. Careful design of
the draw-pit is necessary to ensure that cables can be pulled into it and then drawn
back down into the outgoing duct for the next leg of the run. Any joints that are
required should be positioned in a draw-pit and its dimensions should allow for this.
Suitable access covers should be provided and must be capable of withstanding the
maximum traffic loading to which they will be subjected.
Where cables are buried directly in the ground they should be approximately
750 mm deep for l.v. cables and preferably 1000 mm deep in the case of h.v. The
presence of underground cables, even in ducts, is best indicated by laying proprietary plastic marker tape above the cable and about 150 mm below the final
surface level. Such tape is usually yellow and bears a repeated inscription such as
‘ELECTRICITY CABLES BELOW’. These tapes are reasonably likely to be
observed at an early stage by people digging on the route of the cable, whereas
since the use of mechanical excavators became widespread, the employment of
concrete cable-tiles has been found in practice to offer little protection. Figure 3.11
illustrates a cross-section through a suitable completed cable trench.
PROVISION FOR MAINTENANCE
Modern transformers and switchgear of reputable manufacture are generally
very reliable and maintenance requirements have been steadily reduced over the
years. Nevertheless, all such apparatus at some time, however infrequently, will need
to be isolated for inspection, testing, maintenance or repair. The configuration of
the system and the type of equipment installed will determine how much operational disruption will be caused while such work is undertaken. For example, a
conventional non-extensible RMU has a relatively low first cost but in order to
carry out maintenance involving any of its h.v. components the whole RMU must
be isolated from all sources of supply so that the entire substation is out of service.
On the other hand a withdrawable circuit-breaker can be isolated and maintained
while both its busbar and circuit spouts remain live. It may even be replaced by a
spare circuit-breaker while maintenance is carried out. It does, however, have a
high first cost.
78
Handbook of Electrical Installation Practice
Fig. 3.10 Typical pit for drawing in cables.
Increased security of supply means increased first cost and the degree of system
sophistication to ensure continuity of supply during maintenance must be carefully
weighed against operational requirements and the subsequent operational cost
implications. Such computations are difficult enough when it is known what equipment is to be maintained and when it is to be maintained, but become virtually
impossible if maintenance is left to random forces such as breakdowns.
Site Distribution Systems
79
Fig. 3.11 Cross-section through typical cable trench (not to scale; approximate dimensions
shown in millimetres).
SYSTEM OPERATION
There is often a period, in some cases quite protracted, when the installer is in charge
of a high voltage system that is partially complete and partly live. This responsibility may also continue after completion into warranty periods. As installation continues the installer will need to isolate and gain access to various parts in order to
connect the equipment in the next phase of the work. Properly thought out and well
documented ‘permit-to-work’ procedures are absolutely essential for safety. The
personnel carrying out the procedures must have adequate training, knowledge and
experience of the equipment and the system in order to be able to avoid danger to
themselves and to those who are to carry out the installation work. They should be
formally appointed and their duties clearly defined.
Once the system is handed over to the end user he assumes the same responsibilities and must ensure that similar procedures are adopted and that suitably
qualified persons are appointed to carry them out.
IDENTIFICATION OF SUBSTATIONS AND SWITCHGEAR
Confusion regarding the identity and function of any electrical equipment is
dangerous and never more so than where a complex and geographically dispersed
high voltage distribution network is involved. It is therefore essential for all equipment to be clearly and unambiguously identified both on the plant itself and on all
relevant drawings. Unfortunately, at the design stage several contractors may be
involved and each may identify their particular parts of the overall job by various
configurations of contract names and numbers, etc. It is not unknown for items of
80
Handbook of Electrical Installation Practice
plant to be identified by their height above Ordnance Datum (O.D.), e.g. ‘The 37.2
metre O.D. Switchboard’. While such systems of identification may be adequate for
the purposes of design and installation they are totally unsuited to the needs of
those who are required to operate the system in a safe manner. Discussion should
take place with the end user to decide on a logical scheme for identifying both the
substations, the switchboards and the individual switchgear and circuits.
With regard to the identification of substations, titles based on geographic or plant
references, e.g. ‘East Substation’, ‘Loading Bay Substation’, etc. are much more
likely to convey meaningful information than cryptic numbering systems. A switchboard within a particular substation is probably best identified simply by appending the voltage level at which it operates, e.g. ‘Loading Bay 400 V Switchboard’. If
there is more than one switchboard operating at the same voltage at a particular
location it is usually quite easy to decide on a title based on, for example, its function. When considering the identification of individual items of switchgear the simplest and most sensible practice is to identify a switch or circuit-breaker by what its
‘circuit’ side is connected to, e.g. ‘Transformer T1’, ‘Administration Block’, ‘Pulp
Pump 3’, etc. Figure 3.12 illustrates a typical example.
It is undesirable to include what for this purpose is superfluous information on
the identity plate. A typical gross bad example would be ‘Circuit-Breaker feeding
1000 kVA, 11 kV/433 V, Star-Delta, 4.75% Impedance Transformer Number 2’. In
order to ensure safe operation the title should appear, in full, in every entry on
switching schedules, permits-to-work and log books. If the identification is so protracted, the people operating the equipment will be likely to abbreviate the title and
worse still each operator is likely to abbreviate it differently. The circuit-breaker in
the above example need only bear a plate with the inscription: ‘Transformer T2’. All
the other information should of course be available to the operator but it does not
Fig. 3.12 Identification of switchgear.
Site Distribution Systems
81
Fig. 3.13 Bus-section switches and bus-couplers.
need to be on the identity plate. Expressions such as: ‘Feeder to . . .’, ‘Incomer from
. . .’, etc. are in general unnecessary and may create an impression that the circuit
can only be made live from one direction. This is often not the case.
Bus-section switches and bus-couplers should simply be identified as such unless
there is more than one on the switchboard, in which case it will be necessary to
identify each in some unambiguous manner, e.g. ‘West bus-section switch’ and
‘East bus-section switch’. In this connection there appears to be a widespread
misunderstanding regarding the difference between a ‘bus-section switch’ and a
‘bus-coupler’. A ‘bus-section switch’ is connected between two sections of the same
set of busbars, whereas a ‘bus-coupler’ is connected between two sections of two
different sets of busbars and can therefore only exist on a duplicate busbar
switchboard. Figure 3.13 depicts an example of the correct usage of the titles. It
may be that the extreme rarity of duplicate busbar low voltage switchboards has
led to the widespread misuse of the titles in the low voltage field. It is particularly
galling, and very common, to see a ‘bus-section switch’ correctly identified as such
on an 11 kV switchboard and the corresponding ‘bus-section switch’ on the relevant
low voltage switchboard erroneously identified as a ‘bus-coupler’. Further confusion is liable to occur when North American companies are involved since their
equivalent for a ‘bus-section switch’ is a ‘bus-tie’.
FAULTS LEVEL
In the event of a fault occurring on the system, all equipment that is subjected to
the resulting fault current must be able to carry that current without damage and
without causing danger until such time as the current is cut off by the operation of
a protective device. All the equipment must therefore be rated accordingly. The
circuit-breakers or fuses that are called upon to interrupt the fault current must be
able to do so safely. This requires that their rated breaking capacity is at least equal
to and preferably greater than the maximum fault current that can flow at that point
in the system. Generally, a symmetrical fault imposes the most arduous duty on the
82
Handbook of Electrical Installation Practice
interrupting device and it is therefore the symmetrical breaking capacity that is
normally quoted when specifying the switchgear.
Assessment of ‘prospective short-circuit current’ in l.v. systems is adequately dealt
with in another chapter and also in many explanatory publications relating to BS
7671. In the case of HV systems the term ‘fault level’ is usually employed and is
expressed in MVA. This has the advantage of not being related to any particular
voltage level. The fault current at a particular voltage level may be determined as
follows:
I fault =
fault level (MVA)
1.732 ¥ Vline
A very simple but ‘pessimistic’ method of calculating fault level is to consider only
the percentage impedance of the transformer supplying the system and to assume
infinite fault level upstream of the transformer and negligible cable impedance
downstream:
fault level (MVA) =
trans rating (MVA) ¥ 100
%Z
For example, consider a 1.0 MVA transformer having a percentage impedance of
4.75%. The worst possible fault level downstream of the transformer would be:
fault level (MVA) =
1.0 ¥ 100
= 21.05 MVA
4.75
On an 11 kV system the fault current would be:
I fault =
21.05
= 1.105 kA
1.732 ¥ 11
(which is low compared to the breaking capacity of even the smallest h.v.
switchgear). However, on a 400 V system the fault current would be:
I fault =
21.05
= 30.38 kA
1.732 ¥ 0.400
(which is considerable).
Caution must be exercised if using this method to select switchgear since it might
in some cases result in specifying gear of unnecessarily high rating. The fault level
at the intake should be obtained from the DNO but since they must be careful never
to quote a figure that is even marginally lower than the true value, or a figure that
could, following reinforcement of their system, be exceeded, they will tend to quote
a value that may be higher than the current true value. The present trend seems to
be for the DNO to quote a value equal to the rating of their immediate upstream
switchgear.
Site Distribution Systems
83
The attenuating effect of cable resistance is significant at low voltage but diminishes as the system voltage increases. This is due to the fact that the percentage
impedance is proportional to the reciprocal of the square of the line voltage. The
effect of cable resistance in an 11 kV system will be small and the fault level can in
most cases be assumed to be the same as the intake value throughout the network.
Where cable resistance is to be taken into account it can only be added to the
predominately reactive impedance of the rest of the system vectorially.
A thorough treatment of the subject of fault calculations is beyond the scope of
this chapter but can be found in many textbooks on power engineering theory.
The increasing use of embedded on-site generating plant operating in parallel
with the DNO may result in excessive fault levels on both the consumer’s and the
DNO’s networks. Assessment of this aspect must be carried out at an early stage.
This additional contribution to the fault level may require the installation of
reactors or high impedance transformers or the imposition of restrictive operational practices.
TESTING AND COMMISSIONING
All the normal inspections, compliance checks and tests that would be carried out
on other electrical equipment and installations are required in the case of site
distribution systems. Protection schemes installed on site networks are often
sophisticated and this must be reflected in the calibre of the personnel entrusted to
test and commission them. Where necessary, specialists should be employed for
such work. Similarly, insulation testing on h.v. systems involves the use of potentially lethal voltages and should only be carried out by adequately qualified people
under formal ‘sanction-for-test’ procedures.
Correct phasing of conductors around ring-mains is important. Cases have
occurred of phases being ‘crossed’ during installation, this having gone unnoticed
for several years because the ‘open point’ remained unchanged and all motors were
connected for correct direction of rotation on the ‘normal’ supply. Such an error
would become apparent if the ‘open point’ on the ring was changed. If, of course,
the normally legitimate practice of closing the ring first were employed then a threephase short-circuit would occur. An example of an installation error that should
have been discovered and corrected during inspection but which went unobserved
for several years, was a case of an 11 kV RMU cabled up so that the switch-fuse was
in the ring and the transformer was devoid of protection. Where two or more transformers are connected to a switchboard, even if interlocking is provided to prevent
them being paralleled, they should be correctly phased.
In addition to the customary electrical tests the complexities of site distribution
systems often entail the need to ascertain the correct functioning of such features
as ‘figure lock’ and other interlock systems designed to prevent certain unacceptable operations such as paralleling unsynchronised supplies, paralleling transformers where this would entail excessive fault level, etc. It is not sufficient merely to
check that such interlocks operate correctly in the ‘normal’ mode. Their correct
operation in preventing all the unacceptable modes must be positively ascertained.
CHAPTER 4
Cable Management Systems
M.J. Dyer, DLC, AMIEE, JP
(Building Services Consultant)
INTRODUCTION
The decision as to which cable management system to adopt for any particular
installation needs to be a practical one. With the rapidly developing range of
innovative materials available to manufacturers, this aspect of electrical installation design has become increasingly complex in recent years. Whereas the traditional methods of cable management remain (mostly) still available, and
appropriate, to the designer many new systems exist and must be taken into consideration in the design process. The cables to be accommodated may comprise
low voltage (l.v.) cables supplying building services and points of utilisation within
the building itself, or passing through it, communications cabling (including
telephones, data, fibre-optic networks, etc.), and security wiring (including fire
alarms, emergency lighting and occupancy detection wiring at both mains and
extra low voltage (ELV) levels). Thus consideration has to be given at an early
stage to the segregation of services by the type of service provided, and a philosophy of arranging appropriately grouped cables will evolve. This leads to the initial
derating of power cables where they will need to be grouped and possibly enclosed, for the purpose of the regulations. The routes along which each of the cable
types will run must be established in principle and a layout of the distribution
services thus built up. Input at this stage from the architectural drawings will allow
both a space allocation and a system type decision to begin to emerge. The latter
can be specified for the main cable runs, based on the number and physical size of
the cables for each ‘leg’ of such a network. Where the runs for the various types of
electrical services are similar, a single cable system with segregation for the various
categories is indicated, whereas if one ‘class’ of services (e.g. communications
or security) take widely differing routes from that of the power cables, then completely separate cable management systems for the various categories may be a
more efficient solution.
Having come to a preliminary conclusion as to the main distribution of cabling,
the designer must turn his or her attention to the final distribution cables at the
points of utilisation, whether that be at work stations in an office environment or
at machines or process plants in a factory (or indeed at any other position where
electrical power or lighting is required, or data is to be processed or accessed). In
many new-build environments the final cable distribution will be highly visible and
84
Cable Management Systems
85
if care is not taken it may become intrusive; thus a more aesthetically influenced
decision is called for here. Distribution cabling is an engineering service only,
whereas final circuitry has become an environmental component and must be so
considered. The range of decorative products available for these tasks indicates the
importance, and thus price, placed on such works by the architectural teams and
clients. In the following sections there is no attempt to differentiate between ‘main’
and ‘final’ distribution of cables, but the reader is cautioned to define these terms
in his or her own mind and then add them mentally to each variation of the cable
management system which is available.
The use of the building for which the design is being prepared is also an
important factor to consider. Most large projects fall into the categories of industrial, commercial, or retail/hotel/conference buildings, and this will tend to dictate
the degree of mechanical protection required as well as the appearance criteria and
the requirements of accessibility, later, to the cabling. There may also be requirements to specifically prevent access, or at least unauthorised access, in some
environments where security is paramount. Whichever category the building or
installation may be eventually placed in, the importance of the data and security
cabling cannot be overemphasised. In the current environment these services are
no longer secondary to the power cabling, but the sheer volume of them makes
design consideration critical. They must not only be physically accommodated with
considerable provision for future growth, but the requirements of electromagnetic
compatibility (EMC) for such cables must be studied prior to allocating installation
space, and methods, for them. The method of construction of the building will also
influence the decision as to which method of cable management is most appropriate; the creation of ‘fire zones’ with fire resisting floors and walls and the provision
(or otherwise) of risers, suspended floors and/or ceilings, etc., all affect the designer’s
choice.
A client may have strong ideas or even requirements relating to the relative priority to be attached to these aspects of the system design, in which case matters are
straightforward to deal with. However, in speculative construction work or in buildings where the usage may well change several times within the expected life and
probably within the expected ownership of the building, things are less clear. This
has led to much construction work being undertaken on a ‘core and fit-out’ basis to
separate the changeable requirements from the fixed core of the building, but this
option is not available in traditional construction contractual arrangements. It is
then necessary to make a fundamental decision regarding the priorities, before
design selection can take place; for example, the physical protection aspect may be
vital, and in a factory the physical robustness of the cable enclosures, or the placing
of such enclosures out of the range of mechanical impact (from, say, forklift trucks
in a warehouse), may take precedence. In a commercial building with considerable
multipurpose office accommodation, the availability of all the various electrical
services at each and every work station will probably be the overriding requirement,
and so a system capable of this multicompartment operation will be required. In
every case the possibility of adding cables to an installation after it is theoretically
completed must be considered.
86
Handbook of Electrical Installation Practice
DECISION MAKING
The increased quantity of cables involved in buildings has led to a relatively greater
importance in the design and selection of cable management systems. One of the
interesting results is that whereas there used to be a considerable national preference in such systems, there is now a much more uniform international approach to
the question of installing cables in a well managed way. Cables form a very large
physical part of an electrical installation but are not required to be visible or accessible except for maintenance and alteration purposes. With the increase in IT work
and hence data and telephony cabling in offices and factories, the volume of cables
has already increased considerably and can be expected to continue to do so. Thus
the need to ‘manage’ them has become proportionately more important.
A number of parameters require the attention of the designer when addressing
cable management. It is to be assumed that the electrical requirements have already
been determined, and that an electrical engineering design therefore exists. The
cable types will probably have been selected and the points of utilisation will certainly be known. Certain types of cable such as steel wire armoured (SWA) and
mineral insulated copper covered (MICC) cables mitigate against most systems of
cable management (except for tray and ladders in very large installations) as they
are designed for direct fixing to structural surfaces, but all other cable types will
require to be physically enclosed and ‘managed’ in some way. The building structure will already exist, or in the case of new development work will at least have
been designed, and this will affect the system selected. There may or may not be
specific provision made by the architect for risers and/or cable access areas and it
is not uncommon for distribution points to be determined by the provision of space
rather than by the logical need for such a position. Whatever the physical arrangement of the building, the designer must provide an efficient (and that also means a
cost efficient) method of controlling the cable installation work involved. Throughout the length of the cables they must all be secured and segregated as may be
required. The method selected may be continuous throughout the whole of the
installation, or may vary from place to place within the area served by the installation, but in any case it must, above all, be suitable for the requirements of both the
environment in which it is located and the user’s convenience.
DEFINITIONS
Cable management implies the enclosure, segregation, marshalling and mechanical
protection of the cables within the building, and hence one must identify every cable
and cable type which is required to implement the electrical design.
Design implies the provision of the current (as specified) requirements, also
allowing for the expansion of the installation in the future. This consideration
requires both space provision within the enclosures selected, and also ensuring that
subsequent access to them will be possible and practical when cables have to be
added for possibly innovative new services. Although rewiring is always something
that has exercised the minds of those responsible for electrical installations in buildings, it is now the extension of the installation that is more important.With improved
Cable Management Systems
87
materials in the construction of cables offering longer and longer service life, and
the increased sophistication of electrical circuit protection devices precluding catastrophic failure of cables, rewiring is required infrequently. However, changes to
requirements brought about by new technologies, increasing demand, and opportunities for data exchange networks (and by differing commercial practices due to
these and other factors), do mean that in many cases extra cables are going to be
required. Thus all cable management arrangements must be suitable for cables to
be added to the installation with relative ease, and systems should be designed with
expansion being given priority in size selection. This might mean providing apparently oversized trunkings, etc. at the outset, or it might mean (particularly with
modular enclosure systems) leaving provision for the addition of new cableways in
the future. These can often be attached to the original trunkings or trays, provided
that space has been left at the design stage to accommodate such growth, and provided that the mechanical considerations of the original installation were adequate
for any imposed new loadings. In any case the allocation of such space is often a
contentious issue between the design disciplines in the team, and requires careful
monitoring by the responsible engineer. Problems may occur at distribution boards
and points and are likely to become critical at data distribution centres. The modular
nature of contemporary designs of power distribution boards provides for relatively
simple extension provision, whereas the limited space frequently granted in data
distribution enclosures is a real problem as demand for electronic capacity grows,
technologies requiring differing electronic assemblies at the distribution points are
introduced, and hence more space is required than is available. For this reason it is
now good practice to provide the data hubs inside dedicated rooms or cupboards,
whereas the power boards can be located in normal circulation areas.
Enclosure implies that cables will not merely be directly fixed to the building surfaces. Although some forms of cable installation do not involve the actual enclosure
of the cables (see above), in general when the term is used at least part enclosure
combined with support is implicit.
Segregation is defined by the regulations and by EMC requirements and directives, and is of increasing importance in the selection of systems. More will be said
about this later in this chapter.
Marshalling of cables, with particular emphasis on accessibility of the correct
cable at the correct point of utilisation, is tied closely to the mechanical protection
element of the system design. Both have very similar methods of attainment, but
the robustness of the materials required will depend as much on the anticipated
environment as upon the properties of the cables to be protected.
TYPES OF SYSTEM
The principal systems available fall into three categories. Many installations will use
a combination of such methods at various points throughout the building, but the
systems selected need to be compatible with each other as well as suitable for the
client’s requirements. The principal categories are conduit and trunking, underfloor
systems, and cable tray or basket systems. Each of these has its subdivisions, and
within each of the subdivisions the individual manufacturers in the field offer an
88
Handbook of Electrical Installation Practice
array of solutions to each and every circumstance, but the principles are the same
and are restricted to the main categories. This chapter is not concerned with detailing the use of cable tray and ladders for large and heavy industrial cable installations, as the practice is well established and is strongly indicated wherever
considerable quantities of already mechanically protected cables (MICC, SWA)
require to be fixed to a surface. Such methods are cable fixing rather than cable
management techniques, and as such properly belong in the trade skills area of
installation technology. Likewise the direct fixing or clipping of cables to a surface
can be a satisfactory and adequate method of installation, provided that the necessary criteria of the electrical installation and regulations are complied with, but
details are not thought to be needed in a work of this nature.
UNDERFLOOR SYSTEMS
It should be understood that the generic term ‘underfloor’ applies to products
designed for such use but which may well be used in other environments where the
protection is appropriate. Ducts and risers, and within suspended ceilings are typical
spaces where parts of so-called underfloor systems may be appropriately used.There
are two main types of such systems: those designed for incorporation into the floor
structure itself, such as trunking systems for casting into the screed, etc., and those
designed to be installed below false (computer) floors in commercial buildings. The
principles of the two systems are the same but the strength of the construction is
different, as is the detailing of the designs. Systems for incorporation into the floor
structure itself are customarily of metallic materials, often galvanised steel, and need
to be of high mechanical strength to withstand the rigours of building site conditions at first fix stage. The spine of such systems is usually flat trunking with a top
flange intended to eventually become flush with the floor screed. To this, thin but
robust covers are fitted. A family of flush outlet boxes is necessary to accommodate
the various accessories required, and fittings such as tees and elbows are required
to construct the cable runs on site. As the trunking now invariably needs to be
multicompartment, great care is needed to arrange the compartments at junctions
and crossovers, and this may be an insurmountable difficulty in some circumstances.
Utilisation points can be provided above floor level by the use of power-poles, and
conduit can also be teed off the trunking prior to the screeding of the floor. While
still a widely used system in new buildings, careful planning is needed at the design
stage, not only with the multicompartment arrangements but also with respect to
the termination of the trunking(s) at distribution boards, etc.
The more recent developments are all in the area of systems intended for use
beneath the raised floor, and laid on top of the structural floor. This method of construction is referred to as ‘suspended flooring’ or ‘computer flooring’. Whereas this
was traditionally confined to specialist technical areas such as computer rooms and
control suites, it is now widely used in commercial buildings due to the flexibility it
adds to the building service provisions. The downside of increased height between
the structural slabs in a multistorey building is often accepted as the price the architect must pay for good service provision within. The void so formed between the
structural and the functional floor provides flexibility and accessibility of a high
Cable Management Systems
89
order for developing the cable systems throughout the life of the building. Systems
for this application are numerous and consist of trunking and conduit similar to conventional products, but with adaptations specifically appropriate for the environment proposed. Plastics material is very popular but metallic systems are available
if mechanical, or more likely EMC, protection is important in a specific application.
Usually a number of parallel trunkings are run side by side to provide the segregated circuits, and thus crossovers and junctions become straightforward to understand. Conduits, usually of the flexible type, can be glanded off to outlets, etc. as
required. The trunking is usually fixed to the structural slab floor and access is given
by removing the tiles of the suspended floor with specialist tools provided by the
flooring contractor. Boxes for accommodating accessories in the floor tiles may be
from the flooring specialist or the electrical manufacturer, but as they are connected
to the trunking by flexible conduit, compatibility will not become a problem. Figure
4.1 shows installed underfloor trunking with flexible feeders to desk sockets.
Underfloor voids are useful spaces for the installation of cables that are passing
through the area as part of the distribution system of the whole building. Cable tray
or basket may be provided for these runs, and all the horizontal legs can be accommodated in such spaces with great savings to the electrical contractor, once the flooring system has been agreed. Communication and data cabling in such voids is
perfectly acceptable but must be treated with the same professionalism as all other
Fig. 4.1 Installed underfloor trunking. Note the segregated circuits.
90
Handbook of Electrical Installation Practice
cable installations. The rapid growth in the quantity of such cabling has led in some
instances to the loose installation of them below computer floors in commercial
buildings. This technique, where the cables are loosely bunched by means of cable
ties and then laid on the structural floor, has its origins in the control rooms of the
broadcasting and telecommunications industries. The adoption of the technique in
the electrical installation industry came about as a result of specialist telecom contractors taking work in the construction industry due to their specialist knowledge
of specific types of cabling. However, the system is not satisfactory here and will not
meet the requirements of regulations and standards (and therefore of insurance
companies), regarding a ‘suitable and workman-like’ installation. Whereas in technical businesses the control and maintenance of such cables can confidently be
left in the hands of engineering personnel, in the commercial world access will be
made by unskilled persons and the integrity of such cables will be invalidated. The
proximity of power distribution cabling then introduces a degree of risk that is not
acceptable in the electrical industry.
CABLE TRAY AND CABLE BASKET
The next main type of cable management system is tray, of which basket is a relatively recent variation. I have referred already to cable tray as particularly appropriate where large numbers of cables have to be run for considerable lengths, usually
in both vertical and horizontal directions. It has been thought of as an industrial
product but new designs have made it particularly suitable for commercial installations. The metallic (often slotted) construction of heavy-duty cable tray makes it
appropriate for the support of heavy cables such as SWA mains or large numbers
of MICC circuits in an industrial site. Other types and even categories of cables can
use the same tray for support when appropriate. Cable ladders are a variation for
vertical runs between horizontal trays, and find economic uses in power stations and
factories with particularly dense cable populations. The overall technique allows
excellent simple mechanical support with accessibility and little of the problem from
grouping factors due to bunching of cables. Secondary trays may be installed alongside the main tray to house the final distribution and/or data cables if segregation
is a problem or specific EMC considerations prevail; otherwise the same tray can
often house various cables.
Plastic coated tray is very effective in hostile conditions or outdoors, and is now
widely available. The hot dipped galvanised tray, which was previously the standard
specification item for such work, is expensive and difficult to install without prejudicing the weatherproof qualities of the construction. It is now seldom used unless
specified by a particular client.
Inside industrial buildings, if there are not a great number of heavy cables to
install, some less expensive system of support is indicated, and indeed cables may
often be quite appropriately clipped directly to structural surfaces for no other
reason than to avoid the cost and size of a traditional tray installation.
In many applications, the use of cable basket provides a good solution to the
above difficulties and at a cost-effective price. Basket is a system of cable support
materials which includes all the shapes and accessories expected in a trunking
Cable Management Systems
91
system, but which is constructed from a wire framework (rather like supermarket
shopping baskets, hence the name), which makes it notably lighter and easier to
work with. The reduction in labour costs when using basket systems is considerable
and this is one of the reasons for its popularity in modern installations. Figure 4.2
shows the economic use of cable basket in industry.
The skills required in the installation operatives are not as specialised as those
for the fitting of galvanised tray, and in general skilled electricians are able to fit
and install cable basket at a fast rate. The system also requires less factory produced
fittings and accessories, as the basic basket can easily be bent and adapted on site
(owing to its open wire construction). Gland plates may be fitted to the sidewalls
to accommodate conduit or small trunking tees to feed sockets, etc. The designer
must remember that if using basket systems, the cables will be exposed to the local
environment, and that may mean the more extensive use of low smoke and fume
(LSF) cable sheathing material which could offset some of the initial cost savings.
In many jobs where intrinsically safe cables are a requirement anyway, there is no
cost penalty in moving towards this less enclosed and cheaper to install system.
HYBRID SYSTEMS
With extensive use in commercial buildings of raised floor techniques and the introduction of increasing numbers of cable types, there have been several products
Fig. 4.2 Economic use of cable basket in industry.
92
Handbook of Electrical Installation Practice
brought to the market to combine the benefits of various cable management systems
but without the disadvantages of each of the individual components. Figure 4.3
shows such a system in a commercial installation. The prefabricated underfloor distribution system provides integral busbars for power distribution, with modular teeoff adapters available, together with a cable basket system for local cabled circuits.
Again the use of flexible conduits to feed the floor boxes and desk pedestals ensures
that compatibility between various suppliers’ equipment is maintained.
CONDUIT AND TRUNKING
Conduit and trunking is a traditional British system and developed from the metallic system used in the early days of installations when wooden cable enclosures and
covers were found to be insufficiently fire resisting to provide a guarantee of safety,
and when rewirability was of paramount importance. Conduits may still be metallic (usually steel, or stainless steel if environmental cleanliness is critical) or plastic.
Both materials have been developed into full systems providing fittings and accessories for all eventualities. Conduit is still an ideal way of marshalling a number of
small cables to a point of utilisation or distribution, and is surprisingly cost effective in most situations. Non-metallic conduits are available not only in circular sections but also in ovals for use in restricted depth dry lining walls, or plaster skims.
When using plastics the reduced temperature tolerance of the material must be
taken into account when considering the mechanical support of luminaires and
Fig. 4.3 Hybrid system.
Cable Management Systems
93
other items. With metallic systems galvanised finish is to be preferred unless the
cost limitations, and a certainty of a non-hostile environment, suggest that black
enamelled will suffice. Stainless steel will only be required if demanded by a particular industry, such as food or medical areas. Conduit is the most easily rewirable
system if it is designed correctly, and it provides good mechanical protection;
metallic systems give EMC protection as well. It is good practice not to rely on the
metallic conduit as a circuit protective conductor, but to draw into the conduit the
appropriate (green/yellow insulated) protective conductor(s) for this purpose.
Trunking is available in the same materials as conduit, and in its traditional metallic form is still referred to as ‘industrial trunking’. This is a rectangular enclosure for
cables designed for surface mounting, and may be subdivided for circuit segregation purposes. As it is unsightly it is best kept out of sight except in industrial environments. However, a large range of aesthetically pleasing plastics trunkings are
available for use in visible locations, particularly at skirting or dado heights. These
provide one or more separate enclosures throughout their length to feed all categories of circuit to point of use, e.g. desks, hotel/hospital bedheads, etc. The use of
these systems in refurbishment work has led to their adoption in new construction
because of the ease of rewirability and their pleasant appearance.They are, however,
a costly way of running cables and are at their most effective when also used to
mount socket-outlets, control equipment, telephone points, etc. Figure 4.4 shows
such an application being demonstrated.
Somewhere between these extreme examples of trunking systems is the large
range of ‘mini-trunking’ which accounts for about 50% of all trunking installed in
Fig 4.4. Example of surface trunking for an office.
94
Handbook of Electrical Installation Practice
recent times. This is a plastics extrusion with a simple clip-on lid for enclosing
a small number of cables on the surface. It can be as large as the small sizes of
industrial trunking but has well designed clean lines and simple accessories. It is
easy to decorate and blends into interior decorations in a way that no other low
cost system is able to do. It is widely used for individual final circuits and additions
to installations.
Conduit and trunking are normally used in combination, in order to utilise the
larger sizes of trunking to carry cables away from a distribution board or data hub,
with individual small diameter conduits glanded off from the trunking to feed individual points. Conduit tends to be thought of as rigid, and in such installations it
normally is, but flexible and semi-flexible materials are available in both insulating
and conductive materials and have equivalent properties. The extra cost and difficulty of ensuring a neat and workman-like installation associated with the non-rigid
conduit materials is offset by their ability to be routed through congested areas of
construction with relative ease. In new construction the casting of semi-flexible conduits into screeds or even into structural floor slabs is an effective way of achieving
outlets for lighting and power at fixed positions; dimensional specification is obviously critical in such techniques.
OVERALL CONSIDERATIONS
The value of the cable management system to the installer and beneficial end
user of the installation will be judged by the maintainability and rewirability of the
cabling, including the ability to increase the number of cables employed. However,
the designer must first take a responsible decision regarding the intrinsic safety
of the designs, particularly in terms of electrical requirements. There is also the
need to preserve fire barriers in buildings and to respect the fire zones required.
This may mean that certain methods of cable management cannot be employed, as
effective fire barriers can only be installed in trunking type systems unless structural materials are fused to surround the cables directly. The electrical system must
also respect the building structure, in that there must be no reduction of the structural integrity of the building during the installation of the electrical distribution
system.
In considering the question of cables crossing fire zone barriers, it is first necessary for the designer to have a complete understanding of the fire prevention architecture of the building in question. At the very least each floor of a multistorey
building will form a zone, with specified fire barrier times between each such zone.
In any building of size the floors will be sub-divided into further zones. According
to the activity planned for each zone, a fire barrier time will have been determined;
this is the time for which the progress of a fire must be delayed by the building structure at that point. Where there are specific indications of risk (e.g. the storage
of motor vehicles or radioactive materials), the requirements will become very
stringent, but even in a commercial development 30-minute fire barriers are
required at numerous internal points. Wherever the distribution system, or even
individual cables, cross these zone boundaries, suitable fire breaks must be installed
in the conduits, trunkings or whatever system is employed. If the architect has
Cable Management Systems
95
provided ducts to transport the services and electrical cables from floor to floor, or
transversely across the structure of a building, the maintenance of the integrity of
the firebreaks is a consideration where services leave these ducts. Proprietary products are available to establish such fire breaks, and their correct use is essential if
the installation is to comply with the Building Regulations and appropriate British
Standard.
Multistorey buildings will also contain smoke lobbies that are areas protected
against the ingress of smoke from a fire within the zone in which they are located.
Stairwells are a typical example of such lobbies. Cable management systems passing
through such lobbies must take precautions within their design to prevent the
passing of smoke along the cableways. In fact the avoidance of crossing such lobbies
is good practice. Cables themselves are well known to produce very toxic products
of combustion when exposed to flames or even high temperatures, and it may be
necessary to use cables with low smoke and fume (LSF) emission in certain circumstances. This is when the cables themselves would contribute to the hazard
caused by a fire or explosion within the building. If certain circuits are expected to
function normally under abnormal conditions, then a further consideration of the
cable performance requirements is that of its reliability under such conditions of
environmental disaster. This usually relates particularly to communications cables
and alarm or emergency lighting circuits. These aspects are covered elsewhere in
this handbook.
PARTICULAR CONSIDERATIONS
In all systems there will be a final connection from the cable distribution system to
the point of utilisation, and there will be many thousands of such final circuit connections in a large building. These will require different techniques to those used
for the fixed building wiring. In factories the use of flexible metallic conduits to
enclose cables that feed machines and workstations is perfectly acceptable; in commercial interiors a more elegant method is required. One way is to provide ‘power
poles’ where outlets of various types are mounted on vertical ‘poles’ with the conductors passing within the ‘pole’ to the ceiling or floor void. Such poles are provided
adjacent to each desk, or may even be part of the office furniture contractor’s range
of accessories. They are surplus to requirements in expensively equipped locations
where each workstation has its own outlets built in, and is then connected under
the flooring to the building fixed wiring system. An alternative is to utilise flat undercarpet cables, which contain power and communication cores and which are
constructed to provide safe working in normal office environments. They are not
suitable for data transmission however, so are less frequently employed in commercial interiors. Where used in retail or hotel constructions care must be taken to
ensure that such cables comply with the appropriate British Standard and that the
voltage rating is correct for the application. (Imported cable products of this type
are frequently designed for 110 V centre tapped supplies and hence cannot be used
on 230 V phase to earth circuits.) Appropriate floor boxes must be used to terminate flat cables, and a maintenance and inspection programme must be implemented
as they are particularly prone to damage from unauthorised tampering.
96
Handbook of Electrical Installation Practice
As has been discussed, it is usually the communications cables that represent the
greatest cable density in the built environment. The types of cable can be grouped
as those for voice, those for digital electrical data and those for optically encoded
data. The first group includes telephone cables and although the use of such cables
is rapidly being superseded by the advent of wireless telephony within commercial
premises, there is still a large requirement for multipair cabling of this type. In such
systems spare pairs must be installed at the time of the original work, and up to
300% spare capacity is not considered excessive. Electrical digital data has replaced
analogue data transmission and utilises specialised cable types. The equipment specialist supplier will specify the cable types required, and within many local area networks (LANs) in a building there will be a range of cable types required, all with
specific EMC limitations. Fibre optic cables are employed for the optically encoded
signals, and these require special boxes both to terminate the core(s) and to retain
the cable sheath securely. The cables must be provided with space to set an appropriate radius as they enter termination points, and unless an underfloor void is available, this is a potentially difficult area to design. However, more cables of this type
are now ‘blown fibre optic’ types, where the cores are transported down conduits
on cushions of air, and no difficulty results from onerous conditions for sheathing
restraints or radii.
A feature of large data cable installations is that many of the cables will originate
from positions other than the origin of the electrical installation (i.e. telephone
frame rooms, computer suites, etc.), and this involves a new concept. The cable
distribution system for data now has a unique layout, different from that for the
power cables, and instead of multicompartment systems, two different systems
are required. Where the systems pass over each other EMC considerations become
important, as does access to the overlaid system.
SEGREGATION
The need for segregation has been discussed and defined already. Designers must
consult the Building Regulations and BS 7671 for details of safety requirements as
far as circuits of different voltages and categories are concerned, and must also be
aware of any specific requirements for physical separation of any data or control
circuits in the building. It may be necessary to consult the designers and suppliers
of any LAN installation, or of any other data highway cable system being installed.
It is necessary to remember that the building management system (BMS) is likely
to be an IT based network rather than an electromechanical system, and the BMS
itself may well have EMC and segregation specifications to be met. The general
requirements to avoid EMC problems are set out in publications from respective
trade advisory bodies and learned institutions (such as the IEE) and these should
be regarded as a minimum basic requirement. However, good engineering practice
must also be followed and potential problems can often be avoided by simple measures; for example, the running of data cables down lift-shafts is unlikely to lead to
a good installation and may well have other problems of its own, not least those of
maintaining fire breaks and of maintainability.
Cable Management Systems
97
Although the selection of cable management systems is often dictated by a combination of technical requirements and physical limitations, the overall aesthetic
effect can still be of the highest quality given the range of materials available to
today’s designers.
CHAPTER 5
Electricity on Construction Sites
G. Parvin
Revised by R.A. Hardy
(Electrical Design Engineer)
Revised by Eur Ing Geoffrey Stokes
BSc(Hons), CEng, FIEE, FIBSE
(Principal Engineer, NICEIC)
Electrical installations for constructional purposes are not in many instances
afforded the time and attention warranted. Relative to the main contract the
value of the constructional electrics is low; but if sufficient attention is given to this
discipline prior to the commencement of site works, considerable expense will be
spared.
The term ‘temporary’ is often used for electrical installations for constructional
purposes and this term conjures up visions of a length of twin and earth cable connected into a 30 A single-phase and neutral switch-fuse, trailing across rough ground
eventually disappearing into a 13 A metal-clad socket-outlet mounted on a pattress.
The ‘installation’ is carefully engineered to fulfil all the site electrical requirements
for a modest price!
Fortunately, due to Electricity at Work Regulations 1989 and the efforts of the
Health and Safety Executive, equipment manufacturers and consulting engineers
have greatly reduced the numbers of serious accidents resulting from improper use
of equipment or the use of inferior quality products, thereby ensuring that the
methods we employ in the design and application of products enable the UK to be
proud of the ‘Safety at Work’ situation.
It is the responsibility of the main contractor to ensure that the construction programme is adhered to, and he will require the assurance that the electrical system
is suitable to provide reliable power distribution, whether the contract period is over
six months or six years, and involving a 2 kVA supply or a 2 MW supply.
The equipment and designs discussed in this chapter are for use on low voltage
(l.v.) systems only, although it is realised that occasionally it is necessary to accept
supplies at higher voltages, such as 11 kV and 33 kV. Such intake voltages involve
the use of h.v. switchgear and transformers which are outside the scope of the British
Standards and Codes of Practice mentioned herein.
This chapter has been prepared to assist the electrical designer and contractor
to apply Regulations and Codes of Practice in the compilation of a comprehensive electrical distribution system which will provide power for all of his site
requirements.
98
Electricity on Construction Sites
99
EQUIPMENT DESIGN AND MANUFACTURE
British Standard 4363, Specification for distribution units and electricity supplies for
construction and building sites was published in 1968 and re-written in 1998 and provides an invaluable base against which to manufacture construction site distribution
equipment. It is quite common for supply authorities in the UK to be asked to
provide 500 kVA at l.v. which entails the installation of 800 A switchgear at the
supply intake point.
There are a number of important aspects involved in the general design of
distribution units which are discussed below. BS 7375: 1996: Code of Practice
for Distribution of electricity on construction and building sites provides a wealth of
guidance for engineers, contractors, builders and others involved in provision of
equipment suitable for use is such arduous site conditions.
Mechanical
Robust construction is necessary to enable the equipment to fulfil its on-site requirements, as exposure to rough handling, accidental vehicular nudging and unit repositioning are common occurrences. In addition to this, the environmental conditions
experienced on construction sites require careful consideration. Equipment must be
capable of continuous operation in coastal locations without any additional protection; similarly, tropical climates must be catered for with the humidity and sandstorms that accompany them. Additional measures are necessary for very hostile
environments, such as the use of filters, anti-condensation heaters, etc., but the basic
design of the unit remains unaltered.
Electrical
Prevention of direct contact with live parts is achieved by insulation and barriers or
enclosures. Protection against indirect contact is effected by efficient earthing and
careful selection of protective devices to provide automatic disconnection.
Ruggedness, reliability, versatility and safety of operation are all combined to
provide an assembly which will operate satisfactorily for long periods in onerous
environments.
RANGE OF EQUIPMENT
The range of equipment likely to be found on a typical construction complex is
detailed below.
Incoming supply assembly (ISA)
The purpose of the ISA on a construction site is primarily to accept the Electricity
Distributor’s main cable, afford metering equipment space and consumer’s main
protection. The ISA comprises two compartments each with its own means of
100
Handbook of Electrical Installation Practice
Fig. 5.1 Incoming supply assembly.
access to authorised personnel. The metering compartment houses the supply
authority’s equipment and can be sealed. The consumer’s main switch compartment
comprises the main isolator (lockable in the OFF position) and protective equipment. Sufficient facilities are afforded for the maximum cable size likely to be
terminated.
If the metering equipment is housed within a substation or the authority’s own
enclosure, then the ISA provides the main site protection and control only. Figure
5.1 shows typical forms of ISA.
Incoming supply and distribution assembly (ISDA)
The ISDA comprises a compartment for the incoming feeder cable and metering
equipment; a main/isolation compartment for main control; and an outgoing compartment housing sub-circuit control and protection devices.
Incoming feeder compartment
The incoming feeder compartment provides facilities for the incoming cable termination and the Electricity Distributor’s cut-out. When called for, the facility must
exist for incorporation of current transformers (CTs) and metering equipment, as
well as potential fuses. All the equipment contained in this section belongs to the
supply authority and access is restricted to their authorised personnel.
Electricity on Construction Sites
101
Main switch compartment
The main switch compartment contains a moulded case circuit breaker (mccb), air
circuit-breaker (acb), or a switch-fuse. It is normal practice to interlock the
compartment door with the main switch to prevent access to live equipment. Similarly a lockable dolly is recommended for securing it while in the OFF position.
Termination facilities require particular attention and must be capable of accepting
cables of capacity commensurate with the rating of the ISDA and in line with BS
5372.
Outgoing feeder compartment
The number of outgoing circuits depends on the particular application, but a
minimum quantity of twelve should normally be provided for. Loads from this
section may vary from perimeter lighting to large tower cranes or sub-main distribution units. Another extremely important consideration is the prospective fault
level at the incoming terminals of the ISDA and this information must be known
at an early stage of the contract. It is conceivable that the ISDA will be positioned
adjacent to the substation and therefore the protective devices incorporated should
reflect the high fault level associated with the main supply transformer.
Multisection removable gland plates assist when making provision for outgoing
circuits, and the termination of protective and control devices must be provided
behind a removable cover plate to enable safe connection of equipment to be made
while adjacent circuits are energised. Figure 5.2 shows a typical ISDA.
Fig. 5.2 Incoming supply and distribution assembly.
102
Handbook of Electrical Installation Practice
Mains distribution assembly (MDA)
When metering equipment is installed elsewhere, the ISDA then becomes an MDA
(Fig. 5.3). The assembly consists of two sections, incoming and outgoing. It is not
economically viable to utilise a single size for MDAs, and therefore they are
normally embraced in the following ratings: 100–300 A, 400–600 A, 600–800 A,
800–1250 A and above 1250 A. (IEC recommendations may adjust the foregoing
capacities to 125 A, 315 A, 400 A, 630 A, 800 A and 1250 A.)
The positioning of an MDA within a distribution network generally depends on
its size and application; it may serve as the major distribution device or be supplied
from an ISDA or upstream larger MDA. To this end versatility is of paramount
importance while maintaining safety of operation.
Incoming feeder compartment
Accessibility and ease of termination are prime factors of the MDA incoming feeder
compartment. Distance between gland plate and cable termination point requires
special attention, for, unlike the ISDA, it is more likely that the supply cable will be
PVC/SWA/PVC and ease of glanding and terminating will need the stated space of
BS 5372.
Fig. 5.3 400 A mains distribution assembly.
Electricity on Construction Sites
103
If the incoming feeder compartment door is lockable, the handle of the main isolator should be operable externally to the enclosure, and preferably interlocked with
the access panel or door. As with the ISDA the main isolator handle should be lockable in the OFF position.
Outgoing feeder compartment
It is recommended that provision is made in the outgoing feeder compartment of
an MDA to provide facilities to include at least twelve circuit-breakers, and with
the variety of loads which can be introduced on to a construction site this quantity
is certainly not overspecified. To reduce overall length it is normal practice to fit
mcbs or mccbs in both the back and front of an MDA, and additional breakers can
be incorporated with ease at a later date if space is left for this purpose. A low-level
neutral bar assists when connecting to outgoing circuit-breakers, allowing them to
be installed safely and quickly. When residual current devices (rcds) are fitted as
additional protection against electric shock, it is important to ensure that this neutral
conductor passes through the device to an individual neutral connector. Outgoing supplies utilise armoured or sheathed cables although the use of socket-outlets
should not be discounted and to this end the enterprising manufacturer designs and
builds an MDA which suits both methods of distribution. Figure 5.3 includes two
socket-outlets.
The purpose of the standards relating to construction site electrical distribution
equipment is to provide a system which can be used on another site. A certain MDA
may be suitable for application where fault levels are low, but one must guard
against the possibility of the unit, after it has completed its term of application, being
transported to a larger site with possibly a prospective fault current of 26 kA. The
check list in Table 5.1 highlights the information required to assess the suitability of
an MDA for a particular application.
Table 5.1 Check list/questionnaire for site distribution equipment.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
Location/atmospheric conditions.
Trip rating of devices.
Polarity of devices.
Bolted or switched neutral.
Main supply details, voltage and frequency, system protection, etc.
Full or half size neutral.
If a fault level is not specified try to establish:
(a) transformer rating,
(b) whether the transformer feeds the distribution unit direct,
(c) if the answer to (b) is no, what other switching device is interposed between?
(d) size and type of cable(s) between transformer and distribution unit,
(e) distance between transformer and distribution unit.
Size and type of cables – emphasise if aluminium cable is being used.
Front or rear acces.
Enclosure protection, environmental.
Are glands supplied by cable contractor?
Instrumentation requirements.
Any restrictions on dimensions.
Label details (if known).
104
Handbook of Electrical Installation Practice
Transformer assembly (TA/1/3)
The MDAs distribute the mains voltage direct to the larger electrical loads or to the
TAs which are located at load centres wherever possible. They operate from a 400
V three-phase supply or a 230 V single-phase supply and step down the voltage to
110 V. The standard design of a TA comprises a double-wound transformer housed
in a weatherproof enclosure and fitted with socket-outlets and protective devices.
The star point of the secondary side of the three-phase unit is earthed and the singlephase unit secondary is centre-tapped to earth, reducing the potential to earth to
63.5 V and 55 V respectively. The widespread use of transformers providing power
at 110 V centre or star-point earthed has resulted in a considerable reduction in
injuries due to electric shock since the early 1970s.
There are two main types of TAs: 1 kVA to 25 kVA continuously rated, and 0.5
kVA to 3 kVA power tool rated. It is usual to associate power transformers with
final distribution on a construction complex, and the power tool rated portable
transformers with smaller projects, such as service industries and house building.
Figure 5.4 shows the types of TAs.
The same basic parameters apply to each type of transformer: 110 V centretapped or star-point earthed. Secondary distribution is provided by 110 V socket
outlets to BS EN 60309 (BS 4343). The quantity of socket-outlets available on a
TA can vary slightly, depending on company standards. Table 5.2 identifies the
Fig. 5.4 Typical transformer assemblies.
105
Electricity on Construction Sites
Table 5.2 Number of socket-outlets related to transformer rating with normal protective
arrangements.
Protection
Rating (kVA)
0.5–3 (PTR)*
3
5 (1-phase)
5 (3-phase)
10 (1-phase)
10 (3-phase)
25+ (3-phase)
Socket-outlets
number and rating (A)
2 ¥ 16
2 ¥ 16
4 ¥ 16; 1 ¥ 32
3 ¥ 16 (1-ph) 1¥ 32 (3-ph)
6 ¥ 16; 2 ¥ 32
5 ¥ 16 (1-ph) 1 ¥ 16 (3-ph)
1 ¥ 32 (1-ph)
According to specific
requirements‡
primary
secondary
mcb†
mcb†
mcb†
mcb or fuse
mcb or fuse
mcb†
mcb†
mcb†
mcb†
mcb†
mcb†
mcb†
* Power tool rated.
†
All mcbs are to BS EN 60898. It is permissible to supply two 16A single-phase socket-outlets from
one double-pole circuit breaker of 20A rating, provided that the cable attached to the associated
plug top is suitably sized.
‡
The wide variety of socket-outlets possible prevents a typical arrangement being specified.
more common arrangements currently in use. Full flexibility is important and
the availability of 110 V imperative. When recommending the number of socketoutlets it is better to err on the side of too many, as long as adequate protection is
provided.
Armoured and non-armoured cables
It is important that supplies for construction and building sites meet the requirements of section 604 of BS 7671: Electrical Requirements for Electrical Installations
and BS 7375: 1996: Code of Practice for distribution of electricity on construction and
building sites. It is important to note the requirements peculiar to wiring systems
which include the following.
Wiring systems must be selected and arranged such that terminations are not subjected to strain, unless the terminations are specially designed to accommodate the
likely strains. Cables that transverse roadways or walkways must be adequately
protected against mechanical damage. Cables and flexible cords must be suitable
for their intended use and, where the operating voltage exceeds 63.5 V, must incorporate a continuous metal sheath or armour that must be earthed. Other than for
fixed wiring, the armouring of such cables must be in addition to a protective conductor core within the cable.
Armoured cables operating at a voltage exceeding 12 V but not normally exceeding 63.5 V must have an oversheath of PVC or of an oil-resisting, flame-retardant
(O&FR) compound; for example, non-flexible armoured cables may be of the wirearmoured type with conductors insulated with PVC or XLPE with an oversheath
106
Handbook of Electrical Installation Practice
of PVC. Non-armoured cables operating within this voltage range must be insulated
and sheathed with general purpose (GP) or heat-resisting elastomers such as vulcanised rubber insulated GP cables or O&FR cables, both to BS 6007.
Flexible cords and cables, with a conductor cross-sectional area (csa) of not less
than 1.5 mm2, may be the armoured type with oversheath of heavy-duty O&FR to
BS 6708. Such cables must be suitable for correct anchoring at accessories and
switchgear. Where operating on reduced low voltage, cables and cords must incorporate a tough-rubber or PVC outer sheath that is water, oil, abrasion and impact
resistant and suitable for the ambient temperatures prevailing. Cables with PVC
insulation and sheathing to BS 6004 must not be used as flexible cables or cords. All
cables that are likely to be moved in normal use must be the flexible type.
PVC and XLPE steel-wire armoured cables are suitable for fixed wiring provided
they are properly supported throughout their length and terminated in appropriate
glands. Cable glands play another important role in providing a connection to earth
for the armouring and for this reason, if for no other, the gland must be sufficiently
tightened and kept free of undue strains.
The csa of the circuit protective conductor must be not less than that of the largest
associated phase conductor.
Where cables are laid underground either for site supplies or as part of the permanent installation, their routes must be properly recorded on a map or site plan.
The metal armouring or sheath of cables must be adequately earthed irrespective of whether a protective conductor is provided in the form of a separate core
within the cable. This will normally be achieved by the proper glanding of the cable
together with gland tag, nut, bolt and washers with a short length of suitably-sized
copper protective conductor to the earthing terminal within the switchgear. On no
account should an earthing and bonding clamp to BS 951, or other similar device,
be applied to the metal sheath or armouring for this or any other purpose. Such
misuse of the clamp is likely to damage the cable and would be considered unreliable for earthing purposes.
Where site conditions are particularly arduous, the designer would wish to consider the additional benefits of monitoring the protective conductor (see BS 4444:
Guide to electrical earth monitoring and protective conductor monitoring) of some
or all of the distribution and final circuits.
Transformer supply cabling
It is normal practice to use PVC insulated armoured cables to connect and MDA
to TAs: however, for flexibility some TAs may be fitted with an appliance inlet and
socket-outlet for connection and loop on of a flexible armoured supply cable. This
arrangement enables speedy re-siting of TAs with minimum inconvenience.
110 V distribution equipment
A particularly important aspect of the sub-distribution within the concentrated
working areas of a building under construction is the availability of 110 V socketoutlets. This power is required for general lighting, safety lighting and small tool
operation. It is necessary to provide multiples of socket-outlets for this purpose, and
the following types of equipment are available.
Electricity on Construction Sites
107
Socket-outlet assembly 110 V single-phase (SOA/1)
The single-phase outlet unit is intended to be supplied from a 32 A single-phase
source which in turn is derived from the local TA. The SOA/1/4 has four 16 A socket
outlets, each pair being protected by a 20 A dp mcb; the SOA/1/6 has six socket
outlets similarly protected. The SOA/1 units are in a portable and free-standing
form, the cable being heavy duty TRS or equivalent.
Socket-outlet assembly 110 V three-phase (SOA/3)
The three-phase SOA/3 is not as common as the SOA/1/4–6, but the SOA/3/4–6 is
normally provided with an additional 32 A three-phase and earth socket outlet for
looping to a similar unit on a rising main system. This system of supply is more permanent and the flexibility is achieved by extensions to the system. Main control and
protection is derived from a 32 A tp mcb and socket-outlet on the local TA, and the
attached four-core TRS cable is fitted with a matching plug.
Extension outlet assembly (EOA)
EOAs are available in both single-phase and three-phase designs, and are designated EOA/1 and EOA/3 respectively.
The versatile EOA/1/4 is intended, as the name implies, as an extension to the
main single-phase 110 V distribution system and comprises a portable weatherproof
enclosure fitted with four 16 A dp and earth weatherproof socket-outlets to BS 4343.
The flexible cable is connected via a plug top to an available socket-outlet on the
SOA/1/4–6, the SOA/3/4–6 or directly into the local TA. Some 2 kW is available at
this point and a 20 A mcb protective device affords control.
Extension leads
Re-siting EOAs can be carried out by non-skilled instructed personnel and the use
of extension leads speeds up this operation. Each extension lead comprises a length
of heavy duty rubber insulated and sheathed flexible cable fitted with a 110 V connector (portable socket-outlet), and matching plug.
DESIGN OF SYSTEM
This section provides a practical guide to the design of a distribution scheme for
electrical services to plant, machinery, power tools, lighting and welfare facilities
associated with construction sites.
Consultation with construction personnel
Before commencement of any design work the electrical design engineer needs to
consult the main contractor’s personnel to determine the methods they intend to
use for the project construction. Various drawings should be made available, including an overall site plan detailing adjacent public roads, typical floor plan and an
elevation drawing.
When the electrical designer becomes involved in a project of this nature much
pre-planning by the main contractor will have been carried out. Underground
108
Handbook of Electrical Installation Practice
service and drainage routes will have been planned and the overall site plan will be
suitably marked with this information. Areas to be excavated should be ascertained
in order to plan temporary cable routes.
An initial approach to the supply authority requesting available areas for supply
intake is useful, and armed with this information the electrical engineer and main
contractor can commence design.
The overall site plan should be marked up with major plant positions and equipment sizes, but if actual types of equipment are not decided on at this stage, calculated assessments of loadings need to be made. Table 5.3 details electrical loadings
associated with equipment employed on a construction project. The major electri-
Table 5.3 Typical kVA requirements for plant and machinery. To be
used as guidance when detailed information is not available.
Electricity on Construction Sites
109
cal loads comprise tower cranes, batching plant, hoists, compressors and welfare
facilities. At this stage of a project the position of these items and their expected
arrival on site are more or less known and can be transferred to the site plan. An
important topic for discussion is the proposed programme and whether working
during hours of darkness is envisaged. Phasing of the contract affects the design of
the electrical supply to the extent of load required and siting of equipment.
Calculating peak demands
The peak demand occurs when the constructional work is at its highest level and/or
in the winter months when the more continuous power requirements of light,
heating and building drying must be provided. It is normally necessary to calculate
the maximum load in kW or kVA and the larger loads may require identifying, e.g.,
lighting, heating, motors, etc.
This calculation is important as overestimation results in unnecessarily high
connection charges, and underestimation results in ultimate tripping of the main
protective device causing problems at times of peak production.
To arrive at the peak demand it is necessary to add the ratings of individual appliances/machines together and apply a diversity factor. In the case of lighting and
space heating loads the full connected capacity should be allowed, although office
heating appliances with individual thermostatic control can be subject to a 10%
allowance. Motor loads can be allowed a 50% diversity. The overall power requirement for the contractors’ equipment can be determined and the diversity applied.
The 110 V lighting and power requirements for the internal works can be assessed
by individually measuring lighting routes for each area and deciding on the method
of lighting, thus determining the loads, or allowing 3.5 W/m2 of floor area. In each
case 25% should be added for power tool usage.
Source of supply
The electrical supply can be obtained either from the local Electricity Distributor
or from petrol and/or diesel generating sets installed on site. The decision which to
use is not only one of comparative cost. Other factors involved include operational
requirements of power on site, cost and practical problems associated with distributing power safely and effectively over the site.
In remote areas where the mains supply may be unstable the most cost effective
method of supply is a combination of mains and generated power. In the event of
a mains failure the generating set can be automatically or manually started and
brought on line within a short period of time, thus assuring a constant supply. See
Chapter 1 about this combination.
Arranging for the supply
The Electricity Distributor requires as much time as possible to arrange for connection and should be advised of the peak demand likely to be experienced during
the course of the contract, the contract period, and the position or positions required
for the supply intake. The types of electrical load, e.g. electrical heating, lighting,
110
Handbook of Electrical Installation Practice
motors, etc. will be helpful information to provide to the Electricity Distributor
which may in turn request details of motor types and methods of starting.
The power supply
Power supplies are required in the following forms, and distributed as detailed
earlier in this chapter.
400 V three-phase four-wire
This supply is used for major items of plant including tower cranes, compressors,
goods and passenger hoists and other such equipment having electric motors above
about 3.75 kW. All cables distributing this supply must be of armoured construction,
unless in offices. When supplying semi-fixed plant, additional protection in the form
of rcds is recommended.
230 V single-phase
A 230 V single-phase supply is recommended only for high fixed boundary or area
floodlighting, dewatering pumps, small hoists, concrete mixers and site offices. All
cables distributing this type of supply must be of armoured construction unless in
offices. When supplying semi-fixed plant, additional protection in the form of rcds
is recommended.
110 V single-phase
The safer voltage of 110 V is recommended for machines and hand tools driven by
motors of up to about 2 kW and for all internal or portable lighting equipment. This
supply is available from an isolating transformer which has its secondary centre
tapped and earthed.
110 V three-phase
A three-phase 110 V supply should be used for machines up to about 3.75 kW. This
supply is available from an isolating transformer, the star point of the secondary
being earthed.
25/50 V single-phase
A 25/50 V single-phase supply should be used for dangerous situations, e.g. tunnelling work or inside boilers.
SUPPLY SYSTEMS
The two most commonly used systems currently in operation within the UK are the
TN-S system (Fig. 5.5) and the TN-C-S system (Fig. 5.6).
TN-S system
The TN-S system was the most widespread in use until relatively recently and
comprises separate neutral and protective conductors throughout the system. The
Electricity on Construction Sites
111
Fig. 5.5 TN-S system: separate neutral and protective conductors throughout the system.
Fig. 5.6 TN-C-S system: neutral and protective functions are combined in a single
conductor in a part of the system.
protective conductor (PE) is often the metallic covering of the cable (armouring,
sheathing or conduit) supplying the installations, or a separate conductor. All
exposed-conductive-parts of the installation are connected to this protective
conductor via the main earthing terminal of the installation.
TN-C-S system
The TN-C-S system is more commonly referred to as protective multiple earthing
(PME) with the PEN conductor as the combined neutral and earth (CNE) conductor. The Electricity Distributor’s regulations demand that all exposed metalwork
is bonded to the protective conductor, which in turn is connected to the neutral conductor at the supply intake point. Owing to the impracticality of bonding all exposed
metalwork to form an equipotential cage an rcd is normally necessary at the mains
intake position, together with an installation earth electrode, to form a TT system.
The value of the rcd tripping current is dependent on the earth loop impedance
of the final circuits (back to the Electricity Distributor’s transformer), but values
of less than 250 mA should not be necessary providing that the maximum
112
Handbook of Electrical Installation Practice
disconnection time of the main protection device does not exceed 5 seconds
and the product of the rated residual operating current and the earth fault loop
impedance does not exceed 25.
SELECTION OF EQUIPMENT
It is now possible to decide on the sizes and types of distribution units. Guidance is
given below.
Once the load requirements are known and the supply details ascertained, the
appropriate type of distribution unit can be selected. The siting of this unit is invariably adjacent to the supply intake position and contains the main protection for this
installation. This protective device must be capable of interrupting the relatively
high levels of fault current that one would expect at the mains intake position.
Select for fault level
The Electricity Distributor will on request provide details of the prospective fault
level at the intake terminals, and all the distribution equipment and associated cable
installed in the site system must be sized accordingly. If the supply authority cannot
provide an l.v. supply from the local network, it may install a power transformer,
and it is fairly common for an 11 kV/433 V DY11 transformer to be used on the
larger sites. Table 5.4 details typical transformers, fault level and winding data.
If an ISA is located at the main intake position, only one device has to be capable
of handling the fault level at the incoming terminals. However, if subcircuit distribution is effected from an MDA at this position then each protective device in the MDA
must be capable of interrupting the prospective fault current safely and quickly.
For example, if the supply transformer is rated at 500 kVA, the adjacent distribution board is subject to a prospective fault current of 13.5 kA (the impedance from
transformer to incoming feeder terminals is negligible), and the outgoing feeder protection must be capable of interrupting this current.This can be achieved in a number
of ways, the most economical being to provide mcbs/mccbs of sufficient interrupting
capacity or a combination of mcbs/mccbs and current limiting HBC fuse links.
Upon establishment of the mains position, the sub-mains MDAs require siting.
Load concentration areas affect the positions of sub-mains equipment and the tower
crane positions are likely points. Accommodation and welfare buildings are
Table 5.4 Typical transformers for site supplies.
Electricity on Construction Sites
113
normally located towards the outer perimeter of the complex and can be treated
as an independent sub-mains. After calculation of the area load in the sub-mains
vicinity a suitable MDA can be selected and the output requirements allowed for.
The supply cables to the sub-mains MDAs require careful selection and when the
route has been determined the appropriate cable size can be chosen. Factors governing this selection are current rating of MDA, distance from supply incoming unit,
method of installation, and the type of protection. The voltage drop should not be
more than 4% of the declared voltage.
Table 5.5 details typical conductor and armour resistances for PVC/SWA/PVC
copper cables to BS 6346, and this information can be used to determine the
prospective fault levels at the sub-mains position.
Using the information in Tables 5.4 and 5.5, and assuming a power transformer
is situated adjacent to the main site protection, and a fault of negligible impedance,
the fault current is calculated as follows (Fig. 5.7):
I f = 230
where
[(R + R
1
2
+ R3 ) + ( X 1 + X 2 )
2
2
]
If = fault current
R1 = transformer resistance
R2 = phase conductor resistance
R3 = armour resistance (negligible reactance assumed)
X1 = transformer reactance
X2 = phase conductor reactance.
Table 5.5 Details of copper conductor cables to BS 6346. All values are
based on maximum conductor temperature (70°C).
114
Handbook of Electrical Installation Practice
Fig. 5.7 Calculation of prospective fault current.
If the Electricity Distributor advises on the fault level at the incoming terminals
the prospective line/earth fault current can be determined at any point on the
site.
The values of If and the voltage drop to the sub-mains positions should be noted
as subsequent calculations and material selection involve these values.
The fault level provides the information necessary to select the protective device
at the main intake position. The breaking capacity rating has already been ascertained relative to the prospective fault current and it is now necessary to decide the
speed of operation of the main device.
BS 7671 (the IEE Regulations) stipulates that the maximum disconnection times
under fault conditions are 5 seconds for fixed equipment and 0.4 seconds where the
circuit feeds socket-outlets. However, this latter requirement does not apply to
reduced voltage circuits described in Regulation Group 471-15. Similarly BS 7375:
1996: Distribution of electricity on construction and building sites, advises that protection against earth fault may be obtained in two ways:
(1) By providing a low impedance path to enable the overcurrent device protecting the installation to operate in a short space of time;
(2) By adopting a TT system with residual current device (rcd) and associated
installation earth electrode.
When the earth path is via cable armour as in (1) above and Fig. 5.7, extreme
care is required in protective device selection. The armour impedance may result in
insufficient current flowing to allow the device to trip within the required time, and
changes to specifications do occur; such things as cable routes, equipment positions,
etc. could be revised, and it may be necessary to install a cable with high conductivity armour, use an additional parallel protective conductor, or provide an rcd as
in (2) above.
The types of load can vary enormously, so the area distribution unit needs to be
versatile enough to incorporate a variety of final circuit protection devices. The
largest single load is probably the local tower crane where the motors may total
some 80 kVA. Various factors need to be considered such as motor starting or dampness, and because of these a final circuit device providing protection against earth
leakage in addition to overcurrent is recommended, particularly if the main site protection includes earth leakage protection. Careful selection of rated tripping current
Electricity on Construction Sites
115
Fig. 5.8 Typical distribution network for a large site.
is important wherever an rcd is chosen for final circuit protection as these devices
are obtainable with various tripping characteristics: instantaneous, inverse definite
minimum time lag (idmtl), and time delayed. This variety will enable selection for
discrimination to be achieved while minimizing spurious tripping.
116
Handbook of Electrical Installation Practice
Fig. 5.9 Typical distribution system for a smaller site.
Any socket-outlets operating at voltages above 63 V to earth should also be fitted
with rcds of the sensitive type (i.e. IDn 艋 30 mA) to afford personnel protection.
To reduce unnecessary cash outlay it is not essential to provide earth leakage protection for individual circuits, but care must be employed if a group of circuits is to
be so protected, because a small leakage on one feeder can trip out adjacent healthy
circuits.
All cables from the area MDA should be of armoured construction and flexible
cables should have a separate earth conductor bonded to the earth screen. Additional protection using earth loop impedance monitoring devices requires consideration, particularly on flexible cables and cables subjected to frequent movement,
so that should any increase in earth loop impedance occur, the associated protection devices will trip. Correct protection of cables and loads is afforded by using
mcbs and mccbs combined with back-up fuses to withstand the prospective fault
current as necessary. It is important to ensure that in the event of a short-circuit or
overload, the protective device on the load side of the fault operates. Correct discrimination is confirmed by comparing time/current characteristics of the associated
protective devices under all fault conditions.
Figures 5.8 and 5.9 detail typical distribution networks in block form, and the
relative cable sizes and fault levels can be recorded on the diagrams to assist in
component selection for future additions to the network.
Electricity on Construction Sites
117
CABLE ROUTING
All cables operating at voltages exceeding 63 V to earth (three-phase system)
or 55 V to earth (single-phase system) and routed across a site should be of
armoured construction and buried wherever possible. Further protection should
be afforded by sand and cable tiles. It is important to identify the cable route and
also mark up the site drawings. Where cables are clipped to a wall or fence the distance between supports must not be so great as to cause unnecessary strain on the
cable.
All cables within the construction area should be installed to prevent mechanical damage or frequent moving. Ceiling voids, ducts, risers and lift-shafts are the
most common routing areas of these cables, reducing obstructions at floor level.
Cable terminations
To help maintain a satisfactory earth fault loop impedance it is essential to fit suitable outdoor cable glands with earth tags for earthing to associated gland plate,
equipment earthing terminal and adjacent cables.
Distribution at 110 V
Distribution at 110 V provides supplies for three different types of load
(Fig. 5.10): safety lighting/general movement lighting; task lighting; and power tool
requirements.
The 110 V supplies are obtained from local single-phase or three-phase TAs and
distributed by heavy duty flexible cables. Personnel protection by high sensitivity
rcds is not necessary at this voltage but localized conditions such as confined and
damp situations may require special attention, such as provision of a 25 V supply or
high sensitivity rcds.
Safety lighting/general movement lighting
This is normally associated with access routes, for example stairways and corridors.
Lift shafts are also included in this category because much work takes place in
such locations. The ideal source of supply for this type of lighting is individual
transformers with direct connection points, as opposed to socket-outlet connections.
Once installed, the lighting operates continuously, the transformers being controlled
from a switch on the area MDA. General movement lighting may also be treated
in this manner, although as it is usually installed in open floor areas, it is more
common to see lighting strings fed by plug and socket-outlet systems. If more
than one string is required per floor it is advisable to connect them to separate
transformers.
Task lighting
This is usually in the form of portable floodstands, or handlamps plugged into a
convenient transformer or socket-outlet. The 500 W tungsten halogen type is
among the most popular, the lumen output being 50% more than the equivalent gls
lamp.
118
Handbook of Electrical Installation Practice
Fig. 5.10 110 V distribution system.
Power tool requirements
Whereas there is normally sufficient power available in an area to cater for the
majority of portable tool demands, there is often a shortage of socket-outlets. Work
within a building under construction is periodically concentrated, but movement
lighting requirement is widespread. It is therefore necessary to provide flexibility in
available power points. This is achieved by ensuring that the area transformer has
sufficient socket-outlets for continuous area lighting and local power. For this reason
the smallest transformer normally used for this task is rated at 5 kVA, with the 10
kVA unit probably the most popular. It can be seen from Table 5.2 that a 10 kVA
transformer normally affords a minimum of five 16 A single-phase 110 V socketoutlets, one 16 A three-phase 110 V socket-outlet, and one 32 A single-phase 110 V
socket-outlet. If two of the 16 A socket-outlets are utilised for general lighting
(average 4 kW) the remaining socket-outlets can be used for comprehensive power
tool/task lighting applications, either directly from the transformer or via a socketoutlet and an EOA/1. Sensible positioning of the portable EOA/1s provides comprehensive coverage and reduces the expensive tasks involved in searching for extra
socket-outlets.
Electricity on Construction Sites
119
CONSTRUCTION SITE LIGHTING
There are two main areas of consideration when planning a lighting scheme.
External floodlighting
The larger construction sites normally utilise floodlighting towers, positioned
around the site perimeter to provide general movement, safety and security lighting. These towers take the form of mobile or fixed height static units. The factors
affecting the decision for static or mobile arrangements are (1) duration of contract
and (2) available siting positions.
If the contract is one of relatively short duration, it may be more economic to use
mobile towers. This type of tower is normally available up to 18 m in height and can
be provided either with its own power source (generating set of up to 7 kW), or for
direct connection to the mains. High efficiency luminaries are supported by the
tower (four rated at up to 1500 W) and the illumination available effectively lights
an area of 73 m by 50 m, the illuminance being dependent on the lighting source.
Typically an 18 m tower carrying four 400 W high pressure sodium luminaries illuminates 3600 m2 to an average of about 20 lux, the illuminance normally associated
with clearing sites and handling materials.
The larger and, relatively speaking, more permanent site would probably warrant
a more careful study of the lighting requirements (provided that space is available),
and if there were fairly definite mounting positions, a proper engineering exercise
could be implemented. This would employ lamp data, aiming angles and mounting
heights in order to arrive at an overall illuminance with static towers supporting
high intensity luminaries. The type of equipment now available can light areas to a
level sufficient for evening working in the darker months, and reduce the contract
programme time considerably.
High intensity discharge luminaries are more commonly used on this type of
structure, the high pressure sodium lantern becoming increasingly popular owing to
its high efficacy (about 125 lm/W of 1000 W), compared with the tungsten halogen
(about 22 lm/W). The capital cost of high pressure sodium equipment is considerably higher than tungsten halogen, but many other factors are important, namely
running costs, installation costs and lamp life. Careful dismantling of fixed height
static towers at the end of a contract enables re-use and the only extra material
required on another site are foundation stillages.
Internal lighting
For general movement within a building under construction an illumination level
of 10 lux should be designed for. One festoon lighting string of 100 m fitted with
twenty 100 W lamps at 5 m intervals lights an area of 750 m2 to an approximate level
of 10 lux.
120
Handbook of Electrical Installation Practice
TESTING AND INSPECTION
The IEE Guidance Note 3 advises that a site installation should be periodically
tested and inspected at intervals. As each section of the installation is covered a test
certificate should be completed detailing circuit number, tests carried out and values
of tests obtained. Reference can then be made to original test results when the periodic inspections take place. A typical testing form is shown in Fig. 5.11.
Fig. 5.11 Typical testing form.
Electricity on Construction Sites
121
INSTALLATION MAINTENANCE
The larger installations invariably have a resident electrical supervisor who should
compile an ongoing maintenance programme to be implemented at frequent intervals. Liaison with constructional management enables this operation to be effected
during off-peak periods. The preventive maintenance includes checking cable terminations and glands for security, cables above ground for possible mechanical
damage and lack of support, rcd operation, and weatherproofing of distribution
equipment and socket outlets.
Smaller installations which do not have resident electrical personnel require
frequent visits to effect the foregoing checks.
Maintenance records should be kept and completed regularly giving details of
tests carried out and readings achieved.
CHAPTER 6
Standby Power Supplies
D.E. Barber, CEng, FIEE
M.V.D. Taylor, MCIM
G.A. Lacey, AIEIE, AMIED
(Sales Manager, Gresham Power Electronics)
Revised by G.M. McDowell, BSc, CEng, MIEE
(Power Systems Croup Manager, ERA Technology)
Reliability of electrical supply to industrial and commercial organisations is essential for continuity of production and safety of goods and personnel, and standby
power systems have been in use for many years. The continuous increase in use
of sophisticated electronic equipment particularly computers and digital communications systems, has forced an even greater awareness of the need for standby
power.
In the present context, standby power covers equipment installed specifically to
supply electrical loads during failure of the prime power source, usually the public
a.c. mains supply but occasionally some form of local generation.
This chapter discusses standby diesel generators and uninterruptible power
systems.
For certain critical installations which will not permit any break in supply, the
standby equipment may be used in an on-line configuration, supplying the load normally as well as during failure of the prime power supply. This type of equipment
is covered in this chapter, as well as composite installations using both standby diesel
generators and battery-based equipment.
STANDBY DIESEL GENERATING SETS
Because oil is still a principal source of standby energy, diesel engine driven generating sets are used on a large scale as a back-up to the public electricity supply. Such
sets comprise a diesel engine, coupled to a generator with appropriate control gear
for operation, instrumentation and protection. Usually the sets are electrically
started from 12 V or 24 V batteries and arranged to run up automatically on mains
failure, take over the load and shut down again when the mains supply returns. In
some cases the load is separated into non-essential and essential groups and only
the latter is then supplied from the standby set during mains outage.
122
Standby Power Supplies
123
Range of sizes
Diesel generating sets are rated according to their electrical output expressed in kW
at a load power factor usually assumed to be 0.8 lagging. The smallest units, up to
say 10 kW, are often arranged for l.v. single-phase output but the greater majority,
between say 10 and 1000 kW, have a three-phase output, some of the larger sizes
generating at 3.3–11 kV. The most popular size for general industrial standby use
lies in the 150 to 500 kW range and where greater standby capacity is required, two
or more sets may be operated in parallel. Multiple set schemes frequently involve
less capital outlay than a single larger unit and also provide greater flexibility, easier
maintenance schedules and better system reliability.
To minimise initial cost, diesel sets are generally run at relatively high speeds and
four-pole generators are very common running at 1500 rev/min for 50 Hz output or
1800 rev/min for 60 Hz. Very small sets may use two-pole generators (3000/3600 rev/
min) while larger sets may sometimes use six-pole generators (1000/1200 rev/min).
Continuous and standby ratings
The electrical output is decided by the power available at the engine flywheel.
Engines are usually rated on a continuous basis against Standard Reference Conditions, defined in BS 5514: Part 1 (ISO 3046) as 1000 kN/m2 barometric pressure,
27°C air temperature and 60% relative humidity. Industrial diesel engines built
to standard specifications will handle 10% overload for 1 hour in any 12 hours of
operation at the continuous rated load. This overload rating is frequently used as
a continuous standby rating on the assumption that normal industrial loads are of
a fluctuating nature and standby duty is relatively infrequent. Some engines are
assigned a special standby rating by the manufacturer which may be higher than the
10% overload rating but in such cases a restriction on total engine service life may
be imposed.
Alternators to BS EN 60034–1 do not have an overload rating as operation in
excess of the continuous rating produces a winding temperature rise higher than the
allowed figure. However, the reference temperature for generators is 40°C and BS
5000: Part 3 allows a 10% generator overload rating for 1 hour in 12, providing the
cooling air temperature is not more than 27°C. As in the case of the engine, this
overload rating can be used as a standby rating for fluctuating industrial loads.
The majority of engines used are of the four cycle type (also known as four stroke)
in which each cylinder contributes one power stroke for every two revolutions of
the crankshaft; the two cycle (or two stroke) engine giving one power stroke per
revolution is not much used. In general terms the number of cylinders increases with
the power output of the set and while twin-cylinder engines are frequently used for
small sets, twelve and sixteen cylinder engines are popular for the larger outputs
and six and eight cylinder engines predominate for the most popular middle part of
the output range.
Development of diesel fuel pumps has resulted in the ability to inject increasing
quantities of fuel into the cylinders to give greater power output. To burn this
fuel a corresponding increase in the air input is required, and natural aspiration, in
which the air is injected at atmospheric pressure, severely limits the engine output.
124
Handbook of Electrical Installation Practice
Fig. 6.1 Typical engine performance 200 kW generating set.
Consequently, much development has been done on pressure charging whereby the
mass flow of air is increased by raising its pressure, usually achieved by an exhaust
turbocharger. Turbocharging results in substantial power increase and because of
this most diesel sets are turbocharged engines.
Figure 6.1 shows typical performance graphs for the diesel engine of a 200 kW
generating set, giving figures for the continuous and also the standby ratings, and it
will be seen that fuel consumption per kWh is fairly constant over a wide range of
speed and load, although generating sets operate at a fixed nominal speed which is
maintained by a governor and fuel pump.
Governing and fuel supplies
Engines fitted with standard mechanical or hydraulic governors experience a considerable momentary reduction in speed when load is suddenly applied, but this is
125
Standby Power Supplies
quickly corrected by the governor/fuel pump system. The momentary drop in speed
is load dependent so that where prescribed frequency limits are important (e.g.
standby for computers), it is necessary to ensure that only a partial electrical load
is applied as a single step. Turbocharged engines tend to have lower load acceptance capability than naturally aspirated engines, owing to the response time of the
exhaust turbocharger, and the maximum load step may therefore be restricted to
60% or 80% of rated load.
Standard governors usually give a speed drop of a few per cent between no load
and rated load and this is advantageous in equalisation of load between parallel
running sets. Special governors are available which adjust the no load and full load
speeds to be equal, and such isochronous governing may be specified for certain
critical installations. Parallel running with isochronous governing requires load
sensing input to the governors to ensure proper load sharing between individual
sets.
The characteristic of speed reduction with increasing load is known as speed
droop. If two diesel generators operating in parallel have the same no-load speed
and droop then they will share load in proportion to their rating even if they differ
in rating. If either of these conditions are not achieved or drift with time, then the
full system capacity cannot be achieved.This restriction could be particularly serious
for a standby system since full availability is vital. The use of engine management
systems with load control provides close tolerance load share between parallel running generators and compensates for drift in governor and combustion
characteristics.
Governing performance is defined by BS 5514-4 and different classes of governing accuracy and response can be specified to suit the application.
A typical generating set will consume about 0.3 litres of fuel per kWh generated.
Fire regulations limit the amount of fuel that can be stored in the generator room
and the usual arrangement of fuel supply comprises a small service tank (also
referred to as the day-tank) on or near the set which is topped up from a bulk tank
situated outside.
Cooling and exhaust system
All internal combustion engines are relatively inefficient and Table 6.1 shows how
the energy in the fuel is transformed into useful work and heat loss. Column A shows
the figures relative to 100% fuel energy, while column B bases the figures on 100%
rated set output, after allowing for generator inefficiency.
Table 6.1
Total fuel energy
Heat loss to exhaust
Heat loss to cooling system
Mechanical and radiation losses
Generator losses
Energy to load
A
B
100
30
27
10
3
30
333
100
90
33
10
100
126
Handbook of Electrical Installation Practice
Small engines are frequently air cooled whereby an engine driven fan circulates
atmospheric air around the hot surfaces of the engine. Water cooled engines dissipate heat through an air cooled radiator or in some cases remotely via a heat
exchanger system. A considerable portion of heat loss is discharged through the
exhaust, and installation must be designed to allow free flow of exhaust gases
without restriction.
Derating of engines
It is unlikely that the UK environmental conditions of air temperature, pressure and
humidity would be more adverse than ISO Standard Reference Conditions, and
derating factors will not normally be applicable. Installations abroad will, however,
frequently require reduction of standard ratings to allow for ambient air variations
and BS 5514: Part 1 gives suitable adjustment factors.
Alternating current generators for standby sets
Alternating current generators fall into two broad groups: rotating armature and
rotating field. Rotating armature machines are confined to the smaller ratings due
to limitations of slip rings and brushes and most modern machines over about
20 kW rating are of the rotating field type.
To maintain a constant output voltage the field excitation of a generator must be
adjusted automatically with changes in load. One method, used on many smaller
generators, derives excitation current from the output terminals through an arrangement of current transformers (CTs) and chokes which compensate for changes in
load current and power factor; this is called static excitation because the generator
does not require a rotating exciter. Fig. 6.2 shows the schematic arrangement.
For most generating sets brushless excitation is used as shown in Fig. 6.3 in which
the rotating field is supplied with excitation from a rotating armature exciter and a
shaft mounted rotating rectifier. Adjustment of the exciter stationary field current
by an automatic voltage regulator (AVR) produces the required change in the
Fig. 6.2 A.c. generator with static excitation.
Standby Power Supplies
127
Fig. 6.3 A.c. generator with brushless excitation.
excitation of the main generator to compensate for load variations and maintain the
terminal voltage at nominal value. The AVR is a solid state unit comprising a sensing
input from the generator terminal voltage, a stable reference element, a comparator stage to detect the voltage error and an amplified output stage controlling the
exciter field.
A further refinement is to use a shaft-driven permanent magnet generator (pmg)
in place of the self-excitation unit. A particular advantage of a pmg is the provision
of an excitation supply during a short circuit fault near the generator output. Otherwise, bulky short circuit maintenance CTs are required.
Performance
The performance of an engine driven generator includes factors such as temperature rise of windings, overload capacity, voltage waveform and voltage regulation
under changing load conditions. BS 4999 gives permitted temperature rises for different classes of insulation with a cooling temperature of 40°C. If the cooling air
temperature is less than 40°C a proportionate increase in winding temperature rise
is permitted and this is the basis for the 10% overload allowance in BS 5000: Part
3. Most generators are capable of developing an output considerably in excess
of their continuous rated value and this is frequently exploited for standby duty
where the load is of a variable nature. However, operation for long periods under
overload conditions may produce deterioration of the winding insulation leading
to premature breakdown.
Most generators produce an output voltage waveform which approximates to an
ideal sine wave. Certain types of load, i.e. thyristor loads, draw currents which have
high harmonic content, resulting in distortion of the output voltage waveforms of
standard generators which may affect the operation of other equipment fed from
the same supply (see section on non-linear loads).
The voltage regulating system of modern generators will hold the terminal voltage
within quite tight limits (typically ±2%) for any load from zero to rated value.
128
Handbook of Electrical Installation Practice
Fig. 6.4 Transient voltage recovery following application of full load on a brushless
generator.
However, at the instant of applying or removing load there will be a momentary
voltage change which is outside these steady state limits and this is known as transient voltage regulation and is due to the transient reactance of the generator windings. Figure 6.4 shows a typical voltage change following sudden application of rated
load. Initially, the AVR maintains the output voltage within the steady state limits,
but at the instant of applying load the current produces an internal reactance drop
which subtracts from the terminal voltage causing the initial transient dip. The AVR
immediately responds to this change and produces a large increase in field current
which rapidly restores the voltage to steady state tolerances. The time required to
reach the lower tolerance limit is known as the recovery time and is usually in the
order of 0.3 to 0.7 seconds depending on the size of the machine.
The transient reactance of the generator is usually much greater than the source
impedance of a mains supply. It therefore follows that the transient voltage dips
which occur when supplying the load from the standby system will be greater than
when mains powered, and the effect of this increased voltage depression on other
running equipment may be significant even though recovery is rapid. For general
industrial installations the transient voltage dip should be restricted to about 20%
but, for more critical loads, 15% or even 10% is frequently specified. To meet these
tighter requirements an oversize generator may be required, but the alternative
approach is to reduce the magnitude of the load steps by suitable arrangement of
the installation. For instance, direct-on-line started cage induction motors might
be equipped with reduced voltage starters, or multiple load elements might be
arranged to start in sequence rather than all at the same time.
Mechanical construction
Most generators used in standby sets are horizontal, foot mounted, self-ventilated
machines. In two-bearing machines the rotor is self-supported by ball and roller
bearings and the shaft extension at the drive end then carries a flexible coupling
driven from the engine flywheel, often with a spigoted coupling ring to ensure concentricity between the generator frame and the engine flywheel housing.
Standby Power Supplies
129
Single-bearing generators, common in the US for many years, are now also
common in Europe. The drive end of the rotor shaft carries a number of flexible
steel discs, the outer diameter of which fits closely into a recess in the engine flywheel and this arrangement provides positive radial location of the rotor, a smooth
drive and a degree of axial flexibility to take care of the tolerances. The generator
stator frame and flywheel housing are positively located by a spigoted couping
ring.
Control systems
The primary function of the control system for a standby generating set is to detect
a mains failure situation, start up the set, transfer the load to the generator, supply
the load for the duration of the outage, detect the restoration of the mains supply,
transfer the load back and shut down the generating set. These functions may be
carried out manually or automatically in accordance with pre-programmed instructions, usually contained in some form of solid state logic circuit.
The mains failure detection system comprises solid state devices which monitor
the voltage on the individual phases on the mains supply to detect loss (or abnormal reduction) of voltage. It is customary to delay the activation of the run-up of a
mains failure set for a second or two to prevent a momentary loss of mains voltage
being interpreted as a genuine power failure.
The next stage in the sequence is the starting of the standby generator set. It has
often been considered desirable to have up to three timed attempts to start, but
many manufacturers are now changing the starting sequence. The first stage comprises part energising of the starter motor system so that, at say one-second intervals, the starter pinion attempts to engage and as soon as this has been achieved,
the second stage of starting, i.e. actual full power cranking, commences. An engine
speed detection circuit indicates when the engine has fired and has started to run
up to speed and at this point the starter motor is de-energised and locked out.
Acceleration of the engine to full speed is comparatively rapid, typically a few
seconds, in which time the generator voltage and engine oil pressure build up, and
as soon as speed, voltage and oil pressure are within acceptable limits the generating set is deemed to be ready for load transfer.
The load is fed from the mains supply system through one of a pair of changeover
contactors or circuit-breakers interlocked so that they cannot both be closed at the
same time. When the generating set is ready the load is transferred from the mains
to the generating set which supplies the load for the duration of the mains outage.
The changeover system must ensure that in no circumstances can the generator be
inadvertently connected in parallel with the mains, and four-pole switching, isolating the neutral, are frequently specified.
Sometimes restoration of mains supply is momentary in duration and several
attempts may be made to re-establish supply before becoming permanent. For this
reason, many standby generating sets are fitted with some form of mains return
delay circuit which ensures that mains voltage is within acceptable limits for a prearranged period before actual transfer of load back to mains. Small sets are then
usually shut down immediately, but the larger engines may be run for a few minutes
on a no-load cooling run which allows a degree of equalisation of heat in the engine
parts and prevents thermal stresses after shutdown. Most standby control circuits
130
Handbook of Electrical Installation Practice
allow for the immediate repetition of the operation sequence should a second mains
failure occur before the complete shutdown cycle has finished.
In some installations it is desirable to parallel the standby supply following mains
restoration in order to achive a smooth handover of supply without subjecting the
distribution system to further disturbance. If the short period of parallel operation
is limited to less than 10 minutes, and provided power export is not intended, the
system need not adapt the protection requirements normally required for embedded generators and detailed in Engineering Recommendation G59/1. However, the
public electricity supply company should always be consulted.
It will be apparent that from a functional operational point of view, the successful activation of the standby generating set and the takeover of load depends
entirely on getting a good start and this depends on the reliability of the battery
system. For this reason, all modern standby installations are fitted with automatically controlled battery chargers which keep the batteries in good condition, and
service schedules should make due allowance for proper maintenance of batteries
to avoid deterioration (as discussed later in this chapter). Most service problems
involving standby sets arise from a battery problem of one sort or another.
Instrumentation and protection
Some instrumentation is desirable even on unattended standby sets, as from time
to time it is necessary to monitor conditions and check operating levels. Sets are
therefore equipped with basic instrumentation such as engine oil pressure, engine
temperature, engine speed and the usual electrical outputs. Measurement of engine
speed is often based on digital techniques involving the counting of pulses obtained
from a flywheel tooth magnetic pick-up device and these pulses can then be used
in the mains failure control module for activating operational sequences and the
overspeed protection circuit.
Serious faults such as loss of engine oil pressure, excessive engine temperature
and overspeed require immediate shutdown of the set to avoid damage. Electrical
overload requires disconnection of the load from the generator and other optional
protective circuits may be added such as overvoltage, frequency out of limits, loss
of engine battery charge current, etc. and signal lamps are used to indicated operational status.
Parallel operation
The use of parallel running sets as a standby service complicates the control equipment considerably because in addition to the normal mains failure sequences, the
separate sets must be synchronised and adjusted for load sharing. Most automatic
paralleling systems operate on the basis that on mains failure all sets start up, synchronise and take the load for the duration of the outage. As the loads are usually
of a variable nature, the system must monitor the total load and the individual share
taken from each set, so that automatic adjustment of the fuelling can take place to
achieve satisfactory load sharing. The generators are equipped for good sharing
of the reactive component of the total load as this is not affected by engine fuel
adjustment.
Standby Power Supplies
131
In some cases it may be considered advantageous to shut down some of the paralleled sets if the load falls to a very low level. The automatic removal of generating sets from the parallel running group and their re-introduction should load levels
increase further, complicates the control system and is normally only justified in
special cases.
The triplen harmonic content in the output of modern low voltage generators is
usually sufficiently small to allow the line and neutral connections to be paralleled.
Therefore the once common practice of employing contactors to select only one
generator neutral is unnecessary unless recommended by the manufacturer or
where generators of different age, rating or design are to be operated in parallel.
Peak lopping system
The capital investment in a standby generating set is sometimes offset by using the
equipment for peak lopping duty whereby the highest electrical tariff charges can
be avoided by running the set in parallel with the mains supply during peak periods.
There are certain minimum requirements concerning standard of equipment and
safety associated with this form of operation and Electricity Distributors vary in
their attitude towards the idea, some allowing it readily while others forbid it completely. This is dealt with more fully in Chapter 1.
Non-linear loads
The general term non-linear applies to loads which do not have a constant impedance to the sinusoidally varying voltage. Variations in impedance may be due to the
natural non-linear characteristics of the load, or may be due to the switching action
of circuit components such as occurs in rectifiers or thyristors. The essential characteristic of non-linear loads is that the current waveform is not sinusoidal, even
when the supply voltage is of ideal sine-wave shape. When the load current is not
sinusoidal the internal reactance drop in the generator windings will follow the nonsinusoidal shape of the current, so that the actual terminal voltage of the generator
will be the basic sine-wave voltage generated by the machine less the non-sinusoidal
voltage drop, and the result of this will be a non-sinusoidal terminal voltage which
may adversely affect the operation of other equipment fed from the same supply.
The amount of harmonic distortion of the output voltage will depend on how
much of the applied load is non-linear and on the internal reactance of the generator windings. The acceptability of harmonic distortion will depend on how critical
the total load is to supply voltage waveform. If the load on the generator is totally
non-linear then, although maximum distortion of the voltage waveform will occur,
this may be acceptable as a working condition. As a broad general rule, non-linear
loads should represent no more than about 40% of the total load on conventional
generators of normal reactance.
The adverse effects of any type of non-linear load can always be reduced by
selecting an oversize generator and this is frequently specified by the generating set
manufacturer. The effect of increasing the kVA rating of the machine is to reduce
the per-unit reactance in the same proportion, and in this way voltage distortion can
be minimised to any required extent. Some reduction in the reactance of standard
132
Handbook of Electrical Installation Practice
generators can often by achieved by simple engineering changes and some generator manufacturers are prepared to undertake this work, which then leads to a lesser
increase in frame size than otherwise required.
Many non-linear loads include their own closed loop control system with a high
degree of amplification in the electronic circuits. It is well known that interconnection of two separate closed loop systems may produce interaction causing system
instability or ‘hunting’ even though the two systems are individually stable. An automatically controlled thyristor system fed from a brushless alternator having the
usual type of electronic AVR constitutes such an arrangement, and an unfortunate
combination of time constants may produce this form of instability. However, the
system can usually be stabilised quite simply by adjusting the time constant of one
of the control loops. In the case of the generator the main time constants are in the
machine itself and are therefore not easy to change, so it is customary to solve the
problem of instability by adjusting the load time constants.
An uninterruptible power supply (UPS) having a phase controlled input rectifier
is a common form of non-linear load that is found in standby power supply systems.
The voltage control or current control loops associated with the UPS input rectifier
are an example of control loops that can dynamically interact with engine governor
and generator voltage controls. In practice the adjustment of these control loops
is not within the capability of many suppliers or manufacturer’s agents. The simple
expedient of limiting the total UPS capacity to less than 70% of generator capacity is a typical ratio that can be effective.
Battery charging loads
There is an increasing use of thyristor circuits in large automatic battery chargers.
These use a thyristor circuit, frequently a three-phase bridge, with a closed loop controller which monitors the output current into the battery and adjusts it to a particular charging rate. Where such a battery charger constitutes the main load on the
generator the harmonic distortion previously discussed will be present and there
may be a risk of instability between the control system of the charger and the AVR.
The effective impedance of the battery load is relatively high as it includes the back
e.m.f. of the battery, but in dynamic terms, when the output of the charger is undergoing change, the effective impedance of the load is very low and a small change in
the generator voltage will produce large changes in current. The handling of such
instability problems is usually carried out by fairly simple adjustments to the battery
charger control time constants.
Fluorescent lighting loads
For large areas of illumination it is normal practice on three-phase mains installations to power groups of fluorescent lights from different phases and this practice
should be retained for installations supplied by three-phase generating sets.
Although most fluorescent lighting fittings have their own power factor correction capacitors incorporated in them, this point should be checked when the installation is to be fed from a generator because without the capacitor the power factor
of the fitting may be as low as 0.4 lagging, which would be unacceptable for normal
generators if the lighting installation is the main load.
Standby Power Supplies
133
Capacitive loads
Most industrial loads operate at a power factor which is less than unity and is most
frequently lagging. It is generally agreed that a power factor less than 0.8 lagging is
disadvantageous and steps are then taken to correct the power factor to a value in
excess of this figure. The usual procedure is to connect capacitors across the load
circuits which then draw a leading current which partially cancels out the lagging
current of the main load, thus raising the overall power factor to the required value.
In some installations arrangements are made to adjust the value of the capacitors
automatically with changing loads, and this is the ideal situation as the overall power
factor is then retained at its desired value.
However, in some commercial installations the capacitor is fixed at an average
level of compensation based on the load expectations of the equipment, and if the
actual reactive pattern of the load does not match this assumed value, overcompensation will occur and the total load on the supply will operate at a leading power
factor. Two examples of such situations could occur with welding transformers and
fluorescent lighting installations where the power factor correction capacitor are
arranged for total correction and are not split into individual units to match the
separate load elements.
The field excitation current requirement for a loaded generator depends very much
on the power factor of the load current and in the usual case of lagging power factor
the field current increases as the power factor reduces. On the other hand, with
leading power factor loads the effect is the opposite and as the power factor reduces,
the field current requirement for a given output will go down. If the leading power
factor of the load circuit is reduced sufficiently, a condition may be reached in which
the field current requirement becomes zero and this is known as self-excitation. At
this critical point the AVR sensing the generator output voltage would lose control,
and any further reduction of the leading power factor would cause overexcitation
and the voltage would rise without any corrective action from the AVR. Such a condition is obviously most undesirable and could cause damage to the connected load.
Because self-excitation depends on armature reaction effects from the stator
winding, modern a.c. generators which have high synchronous reactance will reach
this point of voltage instability at a lower level of reactive load than older type
machines which tended to have lower synchronous reactance values. Circuits which
have any risk of self-excitation should be carefully examined before arranging to
feed them from a generating set supply and in doubtful cases it may be necessary
to adjust the values of the power factor correction capacitors.
To prevent voltage instability and voltage transients it is recommended that
power factor correction capacitor banks should be disabled when only the standby
generation is running.
Unbalanced loads
Ideally the phase currents of an a.c. generator should be equal, as in this way the
line-to-line and line-to-neutral voltages are held within their normal tolerances.
Large differences in the individual phase currents may cause voltage values outside
normal limits and because of this it is recommended that efforts should be made to
balance the loads to within about 20%.
134
Handbook of Electrical Installation Practice
The maximum load which is connected to any one phase of a three-phase generator should not exceed one third of the nominal kVA rating.
Large motor loads
As with all motor starting applications it is essential that the kVA rating of the generating set is sufficient to start and run the largest motor while still supplying the
maximum other loads likely to be connected to the system.
In a few cases, however, the generating set is installed solely to operate a lift or
crane and a problem might occur when the lift or crane is descending with a heavy
load. This is due to the regenerative action of the lift or crane motor when energy
is fed back to the generator which then acts as a motor and tends to drive the generating set. If the energy transferred exceeds the losses in the engine and generator, the speed of the generating set will rise since the engine governor can no longer
exercise its normal control. If there is a risk of this situation occurring, one solution
is to fit equipment on the generating set which will detect the reverse power situation and connect a resistive load element across the generator to absorb it.
Monitoring and control
The effectiveness of a standby system depends entirely on the reliability of the components used to monitor and operate the set. The modern tendency is to use programmable controllers to control the start and run sequence together with other
functions such as alarms, interlocking, monitoring, synchronising, rundown, etc. The
quality and reliability of the control and monitoring system has a direct influence
on the reliability of the generator system and should be selected with care.
Linear and torsional vibrations
By its nature a diesel engine produces a pronounced degree of linear vibration
which is transmitted through its structure to the generator and other parts of the
equipment, and due allowance for this has to be taken at the design stage. The construction of the generator should conform to BS 5000: Part 3, which lays down vibration levels which it must be capable of withstanding. Resilient mountings may be
used to isolate the vibration sources from vulnerable equipment such as control gear
and instruments. Pipe systems and cable runs should be sufficiently flexible to withstand the vibration without damage.
Torsional vibration of the engine crankshaft is produced by the firing of the
engine cylinders and this is transmitted to the generator shaft through the coupling.
The torsional system is complicated and requires detailed analysis by the engine
manufacturer to ensure that no critical torsional frequencies are generated at or
near normal operating speeds.
Enclosures
Although many standby generating sets operate indoors there are situations where,
owing to space restrictions, the set is installed outside and manufacturers offer a
Standby Power Supplies
135
Fig. 6.5 A cut-away view of a 200 kW diesel generating set.
range of enclosures designed to protect the set from weather conditions. The generator control gear and the mains changeover equipment are usually mounted
indoors in free-standing control cubicles.
If an outside generating set is operated close to offices or residential areas, some
form of soundproofing will certainly be required and in such cases the weatherproof
enclosure can be lined with some form of sound attenuation material. To achieve
low noise levels (85 dBA at 1 m is a common standard) the air inlet and outlet
from the set require special attention to achieve the required sound attenuation without restricting air flow. The cost of soundproofing generating sets increases
dramatically as the degree of attenuation is increased and it may be more economical to construct a special soundproof building rather than complicate the actual
enclosure of the set.
Figure 6.5 shows a cut-away view of a 200 kW diesel generating set.
Assessing the load
There are three main factors which determine the choice of generating set for a
standby installation. These are the value of the maximum continuous load, the
maximum kW which can be applied in a single step and the maximum value of
applied kVA in a single step relative to a given transient voltage dip. Clearly the
two main types of load, i.e. passive loads such as heating and lighting and dynamic
136
Handbook of Electrical Installation Practice
Table 6.2 Load analysis.
loads such as induction motors, need to be considered individually so that their
effect on the generator when connection is made can be properly assessed.
Generating set manufacturers can quickly determine the most economical size of
set providing they are given the basic data, and one convenient way of laying out
the load analysis is using the form illustrated in Table 6.2 which is a typical example
of a mixed load comprising heating, lighting and motors. In this example the loads
are assumed to be applied in sequence, but frequently the total load can be applied
as a single step.
In the tabulation the final load, i.e. 365 kW, represents the minimum standby rating
for the generating set but because the maximum peak kW exceeds this an adjustment of engine size is needed. Similarly the maximum starting kVA, i.e. 419 kVA, is
used to determine whether the transient dip is acceptable and in critical cases this
could lead to an oversize generator. It may be noted that the starting kW for the
cage motor is taken as 0.5 times the starting kVA, whereas for the slip ring motor
the factor becomes 0.9 due to the high power factor of the starting arrangements
normally used with slip ring machines.
Installation
The plant room must be large enough to accommodate the sets with sufficient space
around them to carry out proper servicing routines with some arrangements to
permit lifting out sections of the plant for external repair. The ventilation of the
Standby Power Supplies
137
plant room is vitally important in view of the large amount of radiated heat from
generating sets and the need to circulate large volumes of cooling air through
radiators. Ideally, radiators are mounted as close to an outside wall aperture as
possible and if for any reason this cannot be done then a suitable ducting system
should be provided. An additional extraction system may be provided to keep
the plant room cool, particularly in the case of installations with heat exchanger
systems or remote radiators.
If the plant room is at ground level or in a basement, the foundations are probably adequate to carry the set. It is recommended that concrete plinths are erected
to lift the set above ground level to provide for drip trays and access beneath. If the
set is installed above ground level the question of floor loading needs careful consideration and discussion with the architect and it may be necessary to fit resilient
mountings so that vibration is not transmitted to the building. The height of the set
also determines the fuelling supply arrangements. Bulk storage tanks are normally
installed at ground level and circulation of oil to the generating set service tank may
require fuel transfer pumps as an alternative to gravity feed.
Exhaust systems should be short with the minimum number of bends and the
bend radius maximised to avoid back pressure. If a long exhaust run is necessary
the cross-sectional area of the pipe must be increased to compensate. The connection between the exhaust run and the engine manifold must always include a
flexible section, otherwise vibration from the engine will damage the exhaust
installation. For multiple set installations each engine must be provided with its own
exhaust system and in no circumstances should exhausts be paralleled at any point.
Exhaust pipe temperatures can reach 500°C close to the engine and exhaust system
runs should be lagged to prevent radiated heat from raising the temperature of the
plant room. Normal industrial silencers are usually satisfactory but for residential
areas a special additional silencer may be required.
Safety codes must be strictly observed in the operation of standby sets and display
notices should be erected giving the usual precautions against fire and electric shock.
A special notice is also required advising personnel that a standby generating set
can start automatically at any time without warning.
The electrical cable run from the generator terminal box should ideally use a
flexible type cable to withstand vibration from the generator. Free-standing control
panels should be mounted close to the set. Mains standby installations should
include bypass switches to allow the load transfer contactors to be made dead for
safe maintenance work.
Commissioning
Following familiarisation with the plant by study of operating manuals, instruction books, diagrams, etc., preparation for the first run includes checking batteries,
filling with oil and fuel, bleeding the injection system, checking air cleaners, fitting
guards, etc.
The initial run should be short, for a minute or two, to check for leaks in the fuel
and water systems followed by a 15 minute run ideally at about one-third load, under
close observation. During this run the water temperature should reach normal value
controlled by the thermostat. Following examination and oil check, the set can then
138
Handbook of Electrical Installation Practice
be run up again and full load applied in 25% steps with a 5 minute run between
each change. Full load can be continued for about 1 hour after which the set should
be shut down and all joints tightened and a final inspection made for leaks or any
other peculiarities. If a test load is not available the period of light load running
should be limited to a few minutes and long enough only to check the essentials.
A check can then be made on the standby changeover functions and this, if possible, should be carried out when the service load is minimal. Disconnection of the
electrical supply at the consumer’s mains switch simulates a mains failure and should
result in the automatic run up of the standby set and operation of the changeover
contactor.
The commissioning procedure should also include a measurement of the supply
quality produced by the generators, both singly and in parallel, on no-load and when
supporting the rated system load to check that it is compatible with the connected
load. It is also vital to operate the final system with all plant (including UPS) fully
loaded and to test the mains failure performance under these conditions. In particular, this checks that the system can handle the load acceptance of the actual plant
and that UPS and other plant remain stable. If normal system load is not available
then load banks should be used.
Service and maintenance of standby sets
Manufactures’ handbooks describe standard service and maintenance schedules and
these should be followed strictly. The peculiarity of standby set operation is that the
active service life in running hours is usually low and this makes it essential that a
test run is carried out at regular intervals, say monthly. Simulation of mains failure
during the test run is highly desirable and should be done whenever possible, but
the engine starting system and general mechanical checks should be carried out on
each occasion. Starting batteries must be well maintained and kept in a fully charged
condition.
BATTERIES FOR STATIC SYSTEMS
The storage battery is the stored energy source of every static standby power system.
The choice of battery type for standby systems is between lead-acid and nickelcadmium cells.
Table 6.3 summarises the most important features of the main battery types. The
lead-acid Plante cell was the preferred type for many years, offering a working life
of 15 to 25 years when correctly maintained. Cell condition can be visually checked,
and the storage state can be easily checked with a hydrometer.
Not all sites require the long working life of a lead-acid Plante type cell, and in
more recent years there was first a swing towards flat-plate (also known as pasted
plate) technology, offering a service lift of up to 12 years, at approximately 80% of
the cost, size and weight of Plante. However, with the introduction of gas recombination valve regulated lead-acid (URLA) standby batteries, even further benefits
arose.
Table 6.3 Comparison of the main features of lead-acid and nickel-cadmium cells.
Standby Power Supplies
* Guide figures only.
139
140
Handbook of Electrical Installation Practice
As URLA batteries are in essence sealed and designed not to emit gas or electrolyte vapour under normal operating conditions, they can be built into or placed
in close proximity to the equipment they operate. This has obviated the need for
separate battery rooms and expensive cabling. URLA batteries are classified as
maintenance free, which in turn reduces operating costs because there is no need
for electrolyte sampling or topping up with water.
Because of these major savings in cost, weight, size and resources, URLA technology is employed in a high proportion of new static power systems.
There is no real reason why lead-acid tubular cells should not be used with battery
standby systems, although they are designed for repetitive charge/discharge duties
such as providing the tractive power for electric vehicles. They do, however, have
a relatively high internal resistance, which militates against high rate discharge
applications.
The main benefit of nickel-cadmium cells is that they are not damaged if left discharged for long periods – although leaving the cells discharged for long periods is
not recommended in standby power systems. They are not affected by extremes of
heat or cold, or by vibration. There are some applications in the standby field where
these considerations are important, although for many standby power applications
the high cost of nickel-cadmium cells effectively rules them out.
Automotive type batteries should not be used in standby power systems, except
perhaps in a short-term emergency situation. These batteries are designed for high
current discharge for very short durations. Their working life would be reduced if
used in longer-duration standby applications.
It may be tempting on the grounds of cost to install automotive type batteries for
starting duties on a standby diesel generating set. This too is ill-advised. A standby
diesel will typically be started up only a few times each year, and reliability is allimportant.
D.C. STANDBY SYSTEMS
Figure 6.6 shows a d.c. system of the kind that is used for many industrial and commercial applications. Incoming a.c. power is converted to d.c. in a charger/rectifier.
Fig. 6.6 Typical d.c. system.
Standby Power Supplies
141
Under normal circumstances (that is, when the mains supply is present), this d.c.
power performs two functions: it meets the power requirements of emergency lighting, switchgear, controls and other d.c. loads, and it float-charges a battery.
If the mains fails, these d.c. loads draw their power from the battery until the
mains is restored, a standby generator is started, or the battery becomes fully discharged. The d.c. system is designed to recharge the discharged battery and continue supplying the standby loads.
Battery chargers
Unsuitable battery and charger combinations account for the majority of problems
encountered by users, while inadequate maintenance accounts for many of the rest.
To a large extent these two aspects are linked because the maintenance requirements of a standby battery installation are greatly influenced by the choice of the
battery charger.
It is important that the charger is accurately set to the voltage levels appropriate
to the type of cell in use (Table 6.3). For sealed lead-acid batteries, typical float voltages are:
2.275 V/cell for 5-year design life types
2.23 V/cell for 10-year design life types.
In flooded-cell types, a charger voltage of 10–15% above the recommended level
can dissipate electrolyte within days, leaving the battery at best temporarily useless,
and possibly with only a fraction of its nominal capacity recoverable. For recombination batteries this overcharging will cause gassing and shorten service life. Conversely, a charger voltage of 10% below the recommended level means that the
battery will not be fully recharged.
If the charger output is poorly regulated, and unpredictable, and has no metering or alarm facilities, very frequent – perhaps daily – checks of charger voltage and
current, and topping up of electrolyte, are required.
Temperature management is more important for sealed lead-acid cells. Placement
near or above heat sources should be avoided, and where necessary, temperature
compensation of float voltage should be used (Figs 6.7 and 6.8).
The simplest form of charger is the taper charger, for which a typical circuit
diagram is shown in Fig. 6.9. It should be noted that this type of charger is not suitable or recommended for use with URLA or nickel-cadmium cells. In this type of
circuit, the components are selected so that the battery is trickle-charged to balance
any losses. An electromechanical switch (manual or automatic) connects a lower
resistance to give the higher current needed for boosted charging.
The taper charger is a relatively simple and low-cost device, but it does have some
serious disadvantages. If the mains varies, the unit has to be reset, otherwise underor overcharge will damage the battery. Electrolyte consumption varies, so the level
must be examined at regular intervals and topped up when necessary.
If switching from trickle-charge to boost charge is automatic, the control unit must
be 100% reliable or there is a risk of not switching to boost charge after the battery
has discharged. Worse still, there is also the risk of the charger not switching back
142
Handbook of Electrical Installation Practice
Fig. 6.7 Relationship between float service life and ambient temperature.
Fig. 6.8 Relationship between temperature and charging voltage.
Standby Power Supplies
143
Fig. 6.9 Circuit and waveform of a typical taper charger.
to the trickle charge after a boost charge, so that the electrolyte will rapidly be boiled
off.
A far better approach to battery charging is to use a constant-voltage charger. In
this type of charger, the voltage applied to the battery is controlled automatically
and kept constant, independent of any mains or load fluctuations. Constant-voltage
charging is recommended for both sealed lead-acid and nickel-cadmium cells.
Constant-voltage chargers use a power electronic regulator, with a currentlimiting circuit to protect the components in the event of an excessive overload. The
circuit of a constant-voltage charger with series regulator is shown in Fig. 6.10.
From a practical viewpoint, the main benefit of the constant-voltage charger is its
ability to compensate automatically for variations in load and mains voltage. The
battery is kept is a healthy state and maintenance intervals are extended. There is
no need to incorporate a battery load test circuit in order to check that the battery
is fully charged.
Another benefit is that the size of the charger does not depend on the size of the
battery installation. So extra battery capacity may be added to meet changing
requirements without necessarily incurring the cost of a replacement charger (as
would be the case with a taper charger). The constant-voltage charger automatically
compensates for the increased charge requirements of some batteries as they age.
Meters and alarms
Some meters and alarms are desirable on any battery charger, although it is not
uncommon for users to request far more complex metering than is strictly justified.
For most users, alarms are more useful than meters.
A charge-fail alarm is probably the most valuable alarm because there are conditions where the charger can be working satisfactorily within current limits, but the
battery is discharging. A high-voltage alarm, which indicates if the charger is left in
144
Handbook of Electrical Installation Practice
Series
regulator
Set
point
+ –
Regulator with
battery voltage
sensing
regulator
Fig. 6.10 Circuit and waveform of a typical transistor constant-voltage charger.
the boost charge position, enables positive action to be taken to prevent possible
permanent damage to the battery.
Boost charging is not usually required with sealed lead-acid cells. However, if
external requirements call for this facility, care should be taken to follow the battery
manufacturer’s specifications.
A low-voltage alarm, set at a level towards the end-of-discharge voltage, reveals
that the battery is approaching the end of its design performance. Other alarms
that may be useful are an earth-fault alarm, and for flooded cell type batteries
an electrolyte level-low alarm, which indicates that the electrolyte needs topping up.
As far as meters are concerned, a voltmeter indicates that the system is operating correctly; an ammeter, however, is an unnecessary expense in most cases.
Current levels in constant-voltage chargers are factory preset, and in any case during
the final float stage, the current would typically be only 0.005 the rated capacity of
the battery.
Charger techniques for regulated d.c. loads
Where the load includes telecommunications equipment and instrumentation, and
the d.c. standby supply must be regulated to within 5–10% of the nominal voltage,
problems may arise unless precautions are taken to boost charge the battery in such
a way that the system voltage does not rise to an unacceptable level.
Standby Power Supplies
145
Fig. 6.11 End-cell tapping.
Fig. 6.12 Duplicate/split battery.
There are several ways of achieving this. The cheapest and simplest approach is
to use a technique known as end-cell tapping.
This involves arranging the system so that, during boost charging, the load is supplied from less than the full number of cells, by automatically switching out a certain
number of cells using a voltage-sensing relay and contactor. Figure 6.11 shows this
arrangement. An alternative approach is to switch a diode into the load circuit so
as to introduce a voltage drop to compensate for the increased boost charge voltage.
It may be that by deliberately oversizing the battery, so that it achieves its desired
performance with only an 80% charge, the need for boost charging can be eliminated. Whether or not it is acceptable to provide an extra 20% battery capacity that
will never be used depends on the particular application. Apart from considerations
of cost, the size and weight of the battery may be a problem – especially in restricted
locations such as offshore platforms.
Another alternative, which avoids the voltage fluctuations caused by boost charging, is a split battery with a charger for each half. By ensuring that the boost charge
only takes place on the battery that is off-load, a very closely regulated supply
is assured. With this arrangement, shown in Fig. 6.12, it is necessary for each
battery/charger to have sufficient capacity to supply the load on its own.
Valve regulated lead-acid batteries
With valve regulated lead-acid batteries, end-cell tapping and similar techniques are
not required because:
(1) Maintenance boost charges are redundant, and
(2) Normal operating characteristics of valve regulated lead-acid batteries cover a
much narrower voltage band.
Figure 6.13 illustrates the performance of these batteries.
146
Handbook of Electrical Installation Practice
Fig. 6.13 Discharge performance (CA is the rated capacity in amperes).
This narrower band complies with the equipment regulation and as an additional
benefit removes the problems associated with possible switching spikes corrupting
stored and transmitted digital data.
ALTERNATING CURRENT SYSTEMS
A wide range of equipment in industrial and commercial premises requires a secure
a.c. power supply, and with the increasing use of computers and other sophisticated
electronic equipment, the demands placed on the quality and continuity of the a.c.
supply have grown correspondingly.
Even in the industrialised nations, where the a.c. mains supply is very reliable, it
is estimated that a computer will on average suffer from approximately 130 power
surges, sags or minor interruptions per month. In addition, between 80 and 90% of
users will be subjected to voltage drops greater than 10% of the nominal. In developing countries, mains outages of three or four hours a day are not uncommon.
Uninterruptible power supplies (UPSs) allow a critical or sensitive electrical load
to operate reliably in spite of mains disturbances or outages. Battery-based UPSs
use static inverters or rotary converters to convert the d.c. supply from a battery
into a.c. at the voltage and frequency required by the load. Diesel rotary UPSs are
also available and use inertia energy storage to maintain supplies until the engine
starts.
A range of UPS configurations are available to suit the sensitivity, criticality and
demands of the critical load.
Standby Power Supplies
147
Fig. 6.14 Simple standby static inverter supply for non-critical a.c. coads.
Off-line UPS
Figure 6.14 shows an off-line (or standby) UPS using a simple electromechanical
changeover device to select the source of supply for the maintained load. Static
switching devices can be used to achieve the same function but with a shorter interruption. The inherent energy storage of power supply units within computers and
other information technology equipment allows continuous operation provided the
changeover is less than 20 ms. Under normal circumstances, the load is supplied
direct from the a.c. mains. The mains also supplies a charger/rectifier which float
charges the storage battery.
If the mains fails, the load is switched automatically to the a.c. output of an operating but unloaded static inverter, which gives the prerequisite voltage, frequency
and output rating for the load. During mains failure, the static inverter powers the
load, drawing its imput from the rechargeable battery, until either the mains is
restored, an alternative primary source is switched in, or the battery becomes fully
discharged.
Figure 6.15 shows a standby unit designed for non-critical desktop equipment
such as personal computers and word processors.
The storage time required for the off-line UPS depends on the application. For
emergency lighting requirements in public buildings such as cinemas, regulations
dictate that the discharge time shall have a minimum period of 3 hours. Office equipment tends to require no more than 10 minutes duration.
In addition, the power supply module within the computer is more generally of
the switch mode type. These can tolerate short periods of fairly crude input waveforms such as square-wave (quasi) or step-wave configurations with their resultant
high harmonic contents.As the control circuitry for these types of inverters is simple,
the overall cost of producing these units is kept to a minimum thus offering the
various markets a cheap, if not crude, UPS system.
148
Handbook of Electrical Installation Practice
Fig. 6.15 A standby unit designed to protect non-critical desktop equipment, such as
personal computers and word processors, from mains-borne hazards like
electrical noise, overvoltage spikes and blackouts.
Some standby UPS systems have been designed with faster and more sophisticated static transfer switching arrangements to meet the needs of less critical computer and telecomms applications. However, the various manufacturers of standby
UPS all carry one common flaw within their designs. This type of unit is not strictly
uninterruptible as the output will have a break of at least 2 ms whilst the unit detects
a mains failure and switches to inverter mode and battery back-up.
In order to counter this effect and still produce cost effective units, manufacturers have utilised the latest innovations to produce line-interactive UPS which has
the capability of supplying no-break power with off-line technology.
Line interactive UPS
As with all significant changes the concept of line-interactive UPS was born of a
market requiring cheaper alternatives to the more traditional on-line designs while
maintaining the integrity of no-break principles. Thus older more established and,
in some cases, forgotten designs such as constant voltage transformers (CVTs) and
ferro-resonant transformers were given a new lease of life and incorporated within
the modern UPS packages.
In principle a CVT or ferro-resonant transformer provides the heart of the UPS,
as clearly defined in Fig. 6.16. This acts as a full time power conditioner filtering out
Standby Power Supplies
149
Fig. 6.16 Typical on-line interactive UPS system.
any harmful spikes, surges or sags with the additional benefit of providing isolation
between input and output sources. A rectifier ensures the battery is maintained
during normal conditions with the inverter synchronised but not conducting.
When the mains fails, the off-line inverter is switched on and supplies the load
via the CVT. This in turn discharges its residual energy during the few milliseconds
it takes for the inverter to become active, thus achieving an effective no-break transfer from supply failure to inverter mode. The inverter itself can be a simple squarewave system as the CVT will condition the waveform to provide a sinusoidal output.
This concept can be known as single conversion as well as line interactive.
The static inverter on the input stage ensures there is no back-feed on to the mains
through the transformer.
Several problems exist in this type of design. The CVT will not correct for any
significant frequency deviations in excess of ±1 Hz without reverting to its inverter
and free running on the output. While this effectively deals with the immediate
problem, this condition cannot be sustained as it is limited by the amount of available battery back-up and therefore actual running time. Some manufacturers overcome this difficulty by widening the input frequency tolerance to ±3 Hz. However,
as there is no effective control of the input stages, the output from the UPS
and subsequently the load will be subjected to the same levels of variation. It is
therefore necessary to check equipment tolerances before selecting this mode of
operation.
This transformer centred line interactive approach is currently offered by several
manufacturers, although not using a CVT in all cases. The non-CVT based variants
offer higher efficiency than on-line UPS and can impose lower harmonic current
distortion on the mains supply even if the UPS load is harmonic rich.
Equally, some designs have difficulty in discriminating between mains failure and
some other faults on the line. For example, motors can induce a back e.m.f. into the
circuit at the point of mains failure. The CVT seeing the back e.m.f. as a valid
voltage may continue to try and function as normal, thus the detection circuit and
transfer mechanism would be delayed. By the time the back e.m.f. has diminished
and been recognised as a loss of supply, the load would be dropped. Other types of
150
Handbook of Electrical Installation Practice
Fig. 6.17 Typical on-line UPS system.
line interactive designs use a multitap auto-transformer on the input stage and
replace the CVT with a capacitive reservoir. This allows the input voltage to be
boosted under low voltage conditions with typical tolerances of 164 V to 264 V and
the output regulated between 187 V to 264 V. When the mains fails, the capacitive
reservoir discharges in the same manner as the previous CVT system, thus providing a no-break transfer.
The alternative to standby inverter configurations is on-line operation, where the
load is powered by the static inverter at all times. In the event of a mains power
failure, the battery charging function ceases, but the inverter continues to drive the
load without interruption. These systems are usually referred to as double conversion or continuous mode on-line.
Continuous mode on-line
This design topology is ideally suited for more sensitive operational environments;
for example, ultra-critical computer systems require a much higher degree of input
to output isolation in order to avoid transference of power disturbance such as
common and normal mode line noise in addition to providing a totally secure
output.
Figure 6.17 shows a schematic of a typical on-line UPS system, which provides
continuous, conditioned a.c. power for the computer. Incoming a.c. from the public
supply (or other prime power source) is rectified by a rectifier/charger. The d.c.
output serves two purposes: it float charges a storage battery, and it supplies a highperformance static inverter. The output of the static inverter, at appropriate voltage
and frequency, supplies the load directly.
This arrangement means that the quality of the a.c. supply to the load is determined solely by the characteristics of the static inverter. Any transients or mainsborne interference on the a.c. supply does not reach the computer load due to the
principle feature of the continuous mode design, which is the full time operation of
its static inverter. This negates the need for any switchover mechanism as required
by standby UPSs or the use of residual energy sources for fly-wheel effects as
required by line interactive UPSs. As discussed previously, the line interactive
concept is unable to deal with excessive frequency fluctuations. However, the double
conversion UPS can sustain tolerances of ±5 Hz without switching to battery as the
rectifier absorbs such variations.
Standby Power Supplies
151
Fig. 6.18 An on-line static UPS system.
In the event of an interruption to the a.c. supply, the load continues to draw its
power from the static inverter, which in turn draws its d.c. input requirements from
the storage battery. The capacity of the battery is chosen at the design stage to
suit the power requirements of the load and the standby duration it must provide.
When the supply is restored, the rectifier/charger once again takes over as the source
of d.c. power for the static inverter.
UPS systems above 1 kVA usually employ a static switch to transfer the critical
load in the event of inverter failure (Fig. 6.18).
If the sensing circuitry in the static transfer switch detects that the output from
the static inverter is about to exceed its limits, the switch transfers the load to an
auxiliary a.c. supply. In many installations, this auxiliary supply is in fact the a.c.
mains.
The possible risk of the static inverter experiencing a fault at the same time as a
mains power failure is regarded as small enough to ignore. Where extra levels of
security are required, the auxiliary a.c. supply could be another static inverter which
would probably be maintained on active standby.
Battery rotary UPS
Modern battery rotary UPS tends to use a similar topology to the continuous mode
on-line static UPS but with an inverter fed rotary motor generator (MG) set in
place of the inverter fed output transformer. Although this may at first seem like
an unnecessary added complication, the use of a MG set allows certain enhancements to be claimed by the designers of such options compared with static UPS.
These include:
(1) An internal bypass that allows the MG set to draw most of its power direct from
the input supply. This leads to lower harmonic pollution on the input supply
compared with power flow via an input rectifier.
(2) A simpler naturally commutated inverter.
152
Handbook of Electrical Installation Practice
(3) Stored energy in the MG set rotor that gives added time to counter internal
failure modes and to introduce features such as off-line battery charging.
(4) Greater potential for fault current delivery to assist downstream protection
devices to clear faults.
Disadvantages include greater size and cost compared with static UPS.
Diesel rotary UPS
Diesel rotary UPS offers the attraction of not requiring batteries. Instead, kinetic
energy stored in the rotating parts is used to support the critical load until the diesel
engine starts and couples to the generator. From then onwards all the power
demand is supplied by the diesel generator directly. The system requires engines
that can reliably and rapidly start and accept load quickly. Fast and accurate supply
failure detection is also essential. Several manufacturers have developed such
systems and have proven them in service in many prestigious installations.
The advantages claimed for diesel rotary UPS are:
•
•
•
The elimination of large battery banks. Only small engine starter batteries are
required.
Low harmonic loading on the input supply because input rectifiers are not
required as with static and rotary UPS systems.
The potential for large peak fault current delivery to assist downstream protection devices to clear faults.
Disadvantages include:
•
•
A longer diesel generator set length compared with a simple diesel generator of
equivalent rating. Of course this is balanced by the overall saving of battery space.
No reserve storage should the engine fail to start, although the introduction of
redundancy can offset this eventuality.
Matching the UPS to the load
Most of the problems experienced with static UPS systems arise because certain
aspects of the load to be supplied by the system have not been fully understood at
the time the system was specified. Apart from the voltage, number of phases, frequency and power rating of the load, the following characteristics are important.
Steady-state voltage tolerance
Most equipment designed for mains operation will tolerate a 6–10% swing in
voltage, although if computers form part of the load, only 1% or 2% may be specified, depending on the transient load response required.
Transient load response
Time constants associated with the filter circuits in the inverter mean that the
voltage regulating system cannot react immediately when a load is suddenly applied.
Standby Power Supplies
153
The tolerance of the load in this respect varies considerably. Tungsten and fluorescent emergency lighting, for example, can tolerate complete loss of power for a few
seconds, provided that a visible blink is acceptable. On the other hand, some major
computer manufacturers specify a voltage deviation limit of +8% and -10% for a
few milliseconds only, provided that the steady-state voltage limits are closely controlled, say to within 2%.
Load linearity
Resistive loads including tungsten lighting are linear loads. Switched-mode power
supplies (often used in the power input circuits of computers) constitute non-linear
loads, and as such can pose a problem for the UPS system.They draw current from the
static inverter only in short pulses.The inverter must therefore be able to supply these
spiky currents,high in harmonics,without producing unacceptable harmonic voltages.
Voltage distortion
The static inverter must provide a sinusoidal waveform of sufficient accuracy to
meet the requirements of the load. The general industry standard for total harmonic
distortion (THD) is 5% of the fundamental sine-wave voltage. Inverter specifications usually demand this for linear loads – non-linear loads can increase the harmonic content.
Frequency tolerance
It is relatively easy to achieve an inverter frequency tolerance of 1%, controlled by
an electronic oscillator, independent of load or input voltage. Some computer loads
require an accuracy of 0.05%, in which case crystal control is required.
Load inrush
Many loads take several times their rated current when first switched on to a power
supply. The duration of this inrush may be a few cycles (as with tungsten lamps) or
a few seconds (as with electric motors). A static inverter normally tolerates an
output current only 25% to 30% above the rated figure, so this characteristic of the
load needs careful consideration.
In most large installations, where the system is switched on rarely and normally
runs for prolonged periods, it is usually acceptable to allow the UPS to behave as
if it were sensing an out-of-tolerance output from the static inverter. The static
switch transfers the load to the auxiliary a.c. supply, which delivers the required
current until the load settles down to its steady state, at which point the static switch
transfers the load back to the inverter.
Dynamic loads
Some types of load, notably those containing constant-voltage transformers, exhibit
a dynamic impedance characteristic, and from the viewpoint of the static inverter
behave like a negative impedance. This can cause the voltage control loop of the
inverter to become unstable, resulting in severe oscillations at a few hertz. In practice, this is not usually a problem if the dynamic portion of the load does not constitute more than 10% of the total load. Some types of output filter are more tolerant
of dynamic loads than others.
154
Handbook of Electrical Installation Practice
Selecting a UPS
The revolution in personal computers and their increased use in networked form
to do the job previously achieved with small mainframes or minicomputers has accelerated the demand for UPSs, particularly below 5 kVA. Since privatisation of
the electricity supply industry there has been an upsurge in the number of suppliers and the variety of systems available. This can make the selection of a UPS somewhat bewildering.
One of the most important decisions to make is whether to go for a single, large
UPS to protect all critical loads in an office or building, or to install a number of
smaller systems to protect individual loads or groups of loads.
Using a single, high-power UPS to supply all the critical loads in a building means
that the ‘clean’ power has to be distributed to those loads. The UPS would provide
power to the central processing system(s) and to remote units via dedicated, clean
power feeds.
There are a number of potential problems with this arrangement. First, induced
interference in the dedicated power feeds in the form of noise and spikes caused
by the switching and operation of nearby electrical equipment – for example, lifts,
power tools and even photocopiers – can cancel out the benefits of a conditioned
power supply.
Another problem is ensuring that the clean power socket-outlet do not get used
for unintended purposes, for example during cleaning and maintenance of a building. The office cleaner or contractor may be looking for a socket-outlet for a floor
cleaner or welding equipment at a time when computers are unmanned but performing important search and sort or communications routines.
The centralised option also means that the failure or accidental disconnection of
the UPS could mean the failure or malfunction of all the equipment connected to it.
A decentralised arrangement, involving several lower-power UPS units, usually
offers increased security. The distance between the load and the UPS can be kept
to a minimum so the risk of induced interference is greatly reduced. The failure of
one UPS in a decentralised system affects only the equipment connected, and spare
capacity in the other UPS units could be used to get the equipment up and running
again while any faults are rectified.
The ‘office cleaner’ problem can be solved by installing UPS systems that have
only specialised or polarised sockets, so there is no risk of a vacuum cleaner or drill
corrupting the power supply. The decentralised approach is more flexible than the
centralised one. Because the UPS units are smaller, they can more easily be moved
around if necessary, and the system is easily expandable and can be tailored to individual load requirements (power rating, support time, and so on).
Size and design
Generally, UPS units are getting smaller and smaller. Their size is dictated by the
voltage and back-up time to be provided by the batteries, the full-load and continuous overload power rating, and the type of inverter employed. Off-line units are
usually smaller than on-line ones, and square-wave systems are smaller than sinewave ones.
Standby Power Supplies
155
Fig. 6.19 Modern UPS systems need to be designed for the office environment. They need
to be compact, easy to use, quiet and stylishly designed. The unit shown is a
500 VA on-line UPS, which at full load provides 15 minutes back-up power –
enough time to complete important tasks, save data and perform an orderly
shutdown. Battery extension packs can be added to extend the duty period up
to several hours running time.
The floor area, or footprint, of the unit is an important aspect. In the lower-power
market, the newer systems employ a ‘tower’ design and are small enough to sit conveniently under a desk (Fig. 6.19). For larger systems, the weight and hence the floor
pressure exerted by the units is an important considerattion – some floors may
require strengthening with steel joists to prevent the UPS and batteries falling
through them.
Manufacturers of low-power UPS units have benefited from improved, lower-cost
power transistors and more reliable sealed, rechargeable batteries.
UPS systems are coming out of the plant room and are used more and more in
the place of work. This means they ought to blend in with the ‘high-tech’ image of
modern offices and not look like a smaller version of an industrial plant UPS. A
range of on-line UPS systems ranging from 1 kVA to 5 kVA output rating is shown
in Fig. 6.20.
156
Handbook of Electrical Installation Practice
Fig. 6.20 An on-line modular UPS system with parallel connected power boards for
system expansion or redundant configuration from 800 VA to 6.4 kVA.
Ease of use
The number of switches and controls actually needed on a UPS is fairly small – an
output on/off switch should suffice. Any controls and indicators should be clearly
labelled.
A UPS should include some form of audible and, in noisy environments visual
alarm and status indicators. The absolute minimum warning that should be given by
the UPS is that the mains has failed and reserve power is being used.
Almost as essential is an indication that a certain amount of back-up battery time
(say 10% of total full load support time) remains. Such an alarm allows the user to
switch off any unnecessary loads when the mains supply fails, to extend support
time, and gives the certainty that an alarm will signal when an orderly shutdown (as
opposed to a sudden and catastrophic one) should be performed.
Computer interfaces
In many cases the element of manual control has become obsolete with the increasing use of computer software interfaces to ensure real-time monitoring of the
various UPS parameters as well as providing a fully automatic and controlled shutdown of the user’s equipment.
Standby Power Supplies
157
UPS designs have therefore taken on board the necessary elements in which to
communicate on such a level with the incorporation of RS232 digitised outputs and
LAN interface ports. These in turn are used with comprehensive software packages
supplied in the various local area network environments such as UNIX, NOVELL,
DOS and WINDOWS to name a few.
A further advantage to this type of communication is the increased use of microprocessor control circuitry in modern day designs. This can provide vital information concerning historical data on the UPS performance and its environment. With
the addition of some minor equipment such as a modem, this information can be
accessed and used either for service and maintenance reasons or for analytical
purposes by a computer manager. With the use of a Simple Network Management
Protocol (SNMP) module for reporting purposes the UPS will act as a normal
proprietry item on the network and provide information to the management station
such as mains failures, low battery warnings and general alarms on an automatic
basis, thus allowing pro-active control of the UPS from any given location on the
network.
Safety
Ingress protection to IP31 is sufficient to protect the unit from common office
hazards such as spilt coffee, paper clips and other foreign matter. Virtually all lowpower systems now have sealed, maintenance-free batteries, with no restrictions on
proximity to naked lights, etc.
Acoustic noise
Larger UPS systems tend to be used in noisy environments – large control rooms,
computer rooms or plant rooms – so the acoustic noise generated by the unit is not
important. However, with the trend towards ‘office-compatible’ UPS systems, a
quiet unit is desirable.
As a rough guide, 45 dBA measured at one metre would be virtually imperceptible in a quiet office atmosphere with some other electronic equipment in use. Noise
levels of 60 dBA and over would be uncomfortable.
Expandibility
With the advances of modern technology a limited number of manufacturers have
made it possible to obtain low powered UPSs from 800 VA through to 6.4 kVA
which have the capacity of running their inverter outputs in parallel. This type of
configuration allows the user to purchase a basic UPS for his immediate needs, with
the flexibility to increase the output power as and when load requirements are
increased. This is simply achieved by the addition of complete UPS power boards
fitted together in a modular format as seen in Fig. 6.21.
Another benefit of this type of system is the ability to configure the UPS for
redundant operation. This means simply that the load can be engineered to be supplied from two boards but at a level not exceeding the rating of one powerboard,
158
Handbook of Electrical Installation Practice
Fig. 6.21 A modular UPS schematic showing parallel power modules or boards.
for example 800 VA/420 W. The two boards have their outputs coupled together
in parallel, equally sharing the load at 50%. In the event of one board failing, the
remaining healthy board would immediately continue to supply the load without
break at 100% capacity.
This type of configuration is also used by a number of manufacturers who produce three-phase high-powered UPS systems. Though the actual mechanics differ
between designs the principles of operation remain unchanged. It is therefore
possible to install UPS in the region of 2.4 kVA or higher, based upon a parallel
redundant configuration.
Battery extensions
For small UPS it is generally felt that for the type of application the unit will be
used for, i.e. personal computers, a battery back-up time of between 5 and 10
minutes will be sufficient to meet most user requirements. This has naturally led
to compact designs and low production costs. However, when larger UPSs are
employed, i.e. with critical network installations, longer battery runtimes may be
needed to maintain system integrities. Therefore, we see UPS autonomies between
30 minutes and several hours as the norm. When such configurations are used it is
important to ensure that the UPS rectifier or charger has sufficient current to effect
a speedy recharge of the battery following its normal discharge period. In some
Standby Power Supplies
159
cases it may be necessary to use an additional charger in parallel with the UPS rectifier to undertake this purpose. Thus, the amount of battery back-up time one can
use is not generally restricted other than through normal engineering constraints
and manufacturers’ technical specifications.
Versatility
If a UPS is to be used to drive several load types, care should be taken to ensure
that the UPS is compatible with the loads. The output waveform from the UPS
inverter can be distorted when non-linear, usually highly capacitive loads are being
operated, such as input power factor corrected power supplies. Under these circumstances a sine-wave output is preferable, as it can cope with a wider range of
load types.
EMC
UPSs must conform to EMC requirements for radiated and conducted emissions
and must meet appropriate immunity standards as set out in BSEN 50091–2.
COMPOSITE STANDBY SYSTEMS
The larger the electrical load, the more significant the financial implications of providing battery storage. The alternatives are either to use diesel rotary UPS and
remove the need for batteries or limit the time (referred to as battery autonomy)
for which the batteries must support the UPS.
It is common practice to use a standby diesel generator as a substitute supply for
the battery until the public a.c. supply is restored. The role of the storage batteries
then becomes that of supplying the various loads until the standby generator starts
up. In practice, it is usual to specify a storage battery capable of meeting full load
for 10 minutes. The cost savings associated with the smaller battery usually cover
the cost of a standby diesel set.
Figure 6.22 shows a composite standby power system with a computer-grade static
UPS, a battery d.c. system, and a standby diesel. The a.c. loads are divided into essential and non-essential, and it is important to segregate them so that the UPS does
not supply non-essential loads that can tolerate mains interruptions.
Interfacing the static UPS to the standby generating set can pose some problems
and the comments made earlier in the section on non-linear loading should be consulted. These problems can be overcome by careful system design, and close collaboration between the manufacturers of the diesel generator set and the battery
UPS.
A facility sometimes requested when standby sets are used with battery UPS
systems is inhibition of battery charging when the diesel generator set is on-line.
This avoids unnecessary load on the diesel generator in the event of the battery
becoming fully discharged, for example after a standby duty.
Where both a.c. and b.c. battery-based power systems are installed on the same
site, it is desirable to insist on separate storage batteries for each system.
160
Handbook of Electrical Installation Practice
Fig. 6.22 A composite standby power system with standby diesel generator, on-line UPS and d.c. supplies.
Standby Power Supplies
161
In some applications, there is no alternative but to install a single battery for both
systems. If a shared battery is implemented, the user must accept an increased risk
of a fault on the d.c. line affecting a vital a.c. load. An additional limitation with a
shared battery is the fact that in some applications a d.c. supply is needed at a different voltage to the d.c. input to the static inverter. If a shared battery is unavoidable, then the expert advice of a specialist in battery systems engineering should be
sought.
It is increasingly common to see dual charger arrangements implemented as a
means of enhancing the integrity of the standby power system. As well as greatly
reducing the chances of a charger fault putting the system at risk, a dual charger
arrangement also means that one charger can be isolated for maintenance.
The battery/charger arrangements for starting duties on standby diesel are vital
to the successful operation of the entire system, and the same comments made on
battery chargers earlier in this chapter apply to chargers used for engine starting
batteries. For maximum security, the battery should be charged by its own charger
rather than by an alternator on the machine.
CHAPTER 7
Ground Earthing
T.E. Charlton, BEng, CEng, MIEE, MBA
(Director, Strategy and Solutions Ltd)
J.R. Wales, DFH, CEng, MIEE
(Consultant, Stemet Earthing Co. Ltd)
INTRODUCTION
Earthing of electrical installations is primarily concerned with ensuring safety. In
power networks the earthing system helps to maintain the voltage of any part of the
network within a predetermined range with respect to earth under steady state and
fault conditions. If designed correctly, it should allow enough current to flow under
fault conditions to operate the protective devices installed.The rise in potential experienced during the fault combined with the speed of fault clearance, should be such
as to minimise both the risk of electrocution to individuals near the site of fault and
damage to equipment. The widespread use of electrical appliances, both in the
factory and the home, also introduces many situations where efficient earthing is of
paramount importance, especially to prevent electric shock under fault conditions.
The two main components of an earthing system are equipotential bonding and
formal earth electrodes. Equipotential bonds seek to minimise the potential difference experienced across exposed metallic conductive parts by connecting them
together. The formal earth electrodes normally consist of metallic components in
direct contact with the soil. They are required to disperse any fault current to ground
in a safe, controlled and effective manner.
The installation of an earth electrode is an important factor in achieving a satisfactory earthing system. It involves burying conductive material which is in direct
contact with soil or the general mass of the earth. Soil conditions can vary enormously from site to site and directly affect the resistance value of a given electrode.
It is thus necessary to consider the soil and other factors which affect the actual
resistance of the earth electrode at the design stage.
The earthing system consists of conductive material above ground, and metal electrodes within the soil and the surrounding soil itself. Each of these will contribute
towards the overall resistance value. There are contact resistances, for example at
joints and at material interfaces. The contact resistance of joints must be kept to a
minimum by using appropriate materials and installation practice. In a new installation, the most significant contact resistance is likely to be at the interface between
electrodes and soil. This arises mainly because the soil has not yet consolidated.
162
Ground Earthing
163
To understand the influence of soil on the resistance of an earth electrode, consider a vertical electrode of one metre length inserted vertically into the ground.
The soil immediately adjacent to the rod will influence its contact resistance, which
will form an important part of the overall resistance. Let us first assume that the
soil is in perfect contact with the rod and is made up of an infinite number of cylindrical shells of equal thickness surrounding it. In uniform soil the shells nearest the
rod will have most influence on the rod’s resistance value. Each subsequent shell
will affect the resistance but will have progressively less influence. In practice, the
shells will not have the same resistivity value, so their effect will be a combination
of their resistivity and distance away. An extreme case is if the natural soil is of low
resistivity, but the rod is surrounded by soil which has dried out and has a high resistivity.The rod will have a high resistance dictated by the nearby high resistivity layer.
A rod installed in a cavity in rock may be surrounded by low resistivity soil. It will
still have a high resistance. This is because the shells some distance away have a
much higher resistivity value than those close to the rod. This resistivity factor overwhelms the effect of distance. As the size of the cavity increases, so the effect of the
surrounding rock will fall, but it will always affect the resistance value. Possibly the
best way to appreciate this effect is that the earth currents will flow many kilometres, so the effect of localised effects will be limited.
SOIL RESISTIVITY
It is important to know a little more about the electrical properties of soil because
it is so critical to the eventual resistance value of the rod or electrode system. We
are interested in its resistivity value, which is expressed in ohm metres (W m). This
is, in effect, the resistance between the two opposite faces of a one metre cube of
material. Some typical resistivity values of soils are shown in Table 7.1.
The two main factors which influence soil resistivity are the porosity of the material and the water content. Porosity is a term which describes the size and number
of voids within the material, which is related to its particle size and the pore
Table 7.1 Typical values of resistivity for
different soils.
164
Handbook of Electrical Installation Practice
diameter. It varies between 80 and 90% in the silt of lakes, from 30 to 40% in sands
and unconsolidated clay and by a few per cent in consolidated limestone.
An increase in water content causes a steep reduction in resistivity, until the 20%
level is reached, when the effect begins to level out. Dissolved minerals and salts in
the water may help further reduce the resistance, particularly where these are naturally occurring and do not become diluted over time. The effect of water content
is clearly shown in the resistivity values of concrete in Table 7.1. This has a high
resistivity when dry, which falls dramatically when wet to a value close to that of
the surrounding soil.
Moisture has so great an influence that it is sensible to make use of this property
if possible in the earthing system design, for example by inserting earth electrodes
into the water table to provide a consistently low resistivity. Site surveys seek to find
such information.
RESISTIVITY SURVEYING
Some geophysical prospecting techniques based on electrical measurements of the
subsoil to various depths, have been adapted to suit requirements of electrical earthing systems. The method devised by Dr F. Wenner in 1915 has proved to be particularly suitable for the calculation of soil resistivity for use in earthing calculations.
Equipment necessary
The necessary equipment comprises:
(1) An earth resistance/resistivity tester, having four terminals and a built-in source
of power (Fig. 7.1)
(2) Four metal test electrodes
(3) Four lengths of single insulated cable – used for connecting the test electrodes
to the tester.
The leads should be as long as necessary, commensurate with the size of the earth
grid to be installed, the length of ground available, and the accuracy of the instrument. For single vertical electrodes the test electrode separation (i.e. between each
pair of test electrodes) would need to be several times the maximum depth anticipated. For earth grids, the separation should be at least the same as the diagonal
across the site. Lengths of 20 m for voltage leads and 60 m for current leads should
be sufficient for most rods and small grids. Usually operators prefer to develop their
own cable reel equipment for this operation. For example, the cables can be of
different colours, wound on reels and mounted on a stand. Often the cables are
multicore, marked or have tee connections when a practice of taking measurements
at a set number of spacings is adopted. This can save much time on site.
Method of use
The tester is positioned at a convenient point, often coincident with the location for
a vertical earth rod or the centre of a proposed earth grid. The four test probes are
Ground Earthing
165
Fig. 7.1 Megger DET2/2 auto earth tester. For accurate measurements of earth electrode
resistance or soil resistivity.
positioned in as straight a line as practically possible and at equal distance from one
another, as in Fig. 7.2. The probes do not have to be driven too deeply, normally no
more than 0.25 m. The voltage probes need only be 5–15 cm deep. The probe depth
should never exceed 1/20th of the spacing or a revised formula for the soil resistivity calculation must be used.
Fig. 7.2 Diagram of connections for an earth tester when used for resistivity surveying.
166
Handbook of Electrical Installation Practice
The probes are then connected to the tester as shown in Fig. 7.2. Some of the
modern instruments can be used to check that the test probe and lead resistances
are acceptable prior to each measurement. To overcome polarisation and interference effects, the polarity of the current source is normally reversed several
times during the test. With older equipment this used to be a manual process,
but in modern equipment the d.c. supply is converted into a switched waveform whose frequency can be varied to improve accuracy if necessary.
The current produced by the instrument passes through the two end electrodes
and the voltage between the two inner electrodes is measured. The relation
voltage/current is read directly as ohms (R) from the tester. This reading represents
the resistance presented by a hemispherical volume of soil beneath the tester.
As a practical approximation on site of the depth of soil being measured, Stemet
assume that the Wenner method is examining the properties of the soil to a
depth of 75% of the probe separation; for example, if the spacing is 4 m, the depth
examined is 3 m.
For a more accurate estimate in uniform soil, a graph is available. This
shows the percentage of the total current flowing through a vertical plane beneath
the tester. Approximately 50% flows through a plane of depth equal to half the
electrode separation, 70% through a plane equal to the electrode separation, and
so on.
From the resistance figure obtained we are able to calculate the apparent resistance of the material contained within the hemisphere. This is via the following
formula for resistivity (r):
r = 2 pRA W m
where R = earth tester readings (W)
A = spacing used (m).
The above equation assumes that the soil is of consistent structure, i.e. consistent
grain size, type and water content throughout the whole volume. This is very rarely
the case and the reason why the calculation provides the apparent resistivity and
not the true resistivity. In fact the soil is likely to have several horizontal, sloping or
vertical layers. Each layer will have a different real resistivity and the volume of
each layer within the measured hemisphere will contribute towards the apparent
resistivity.
This measurement technique can be used to examine how the real soil resistivity
is changing with depth. To achieve this a series of resistance measurements are
taken, each at a different probe spacing. It follows that the depth of material investigated at each spacing will differ and will consist of different layers of soil. Typically the probe spacing would start at about 0.5 m and increase in stages to 30 or
50 m. The results of a typical survey are set out in Table 7.2.
Ground Earthing
167
Table 7.2 Results of a typical survey.
INTERPRETING MEASUREMENTS
Normally the apparent resistivity readings from column 4 of Table 7.2 would be
plotted against the Wenner probe spacing (column 1) on log/log graph paper. By
examining the shape of the curve, much can be deduced about the type of soil
structure. Normally each significant change in direction or gradient indicates a
change in soil resistivity at a certain depth. Figure 7.3 is such a plot for a threelayer soil structure. For effective vertical earthing we are trying to identify
layers where the soil resistivity is low, for example in layers below the water table.
Figure 7.3 illustrates that there is a low resistivity layer some distance beneath the
surface. Software facilities are available which can derive a fairly accurate soil model
from test data; for example, the soil model derived from the same data used in
Fig. 7.3 is:
Surface layer: 105 W m, 1.1 m thick
Central layer: 265 W m, 2.5 m thick
Lower layer: 85 W m, at least 16 m thick.
This soil model would be used as the basis of accurate computer modelling of the
proposed earthing system, if this is required. In multilayer soil the actual depth of
the hemisphere of soil being tested can vary substantially, owing to the natural preference of the current to seek a route through low resistivity layers. It is only really
possible to account for this by using computer packages or experience to derive the
soil model.
Stemet Earthing have developed a graphical method as a first approximation of
computer based techniques. The readings from Table 7.2 are plotted as diagonals
across logarithmic scaled graph paper, as shown in Fig. 7.4. From this an approximation of the rod resistance can be read directly off the vertical scale. If the resistivity value is required, this can either be calculated (as shown in Table 7.2) or
assessed graphically (Fig. 7.5). Diagonals have been superimposed on the grid to
show the theoretical resistance of an earth rod driven into uniform soils of different resistivities.
168
Handbook of Electrical Installation Practice
Fig. 7.3 Plot of apparent resistivity against Wenner probe spacing for a three layer soil.
Rod resistance formula
The next stage is to convert the resistivity figures obtained into a resistance value
for the earth electrodes. For example, it is useful to able to predict in advance the
resistance value of a single earth electrode in order to optimise its length.
The simplified formula is:
r = 0.366 ¥ r log10
where r
r
D
d
3D
W
d
= resistance of the rod (W)
= resistivity measurement taken at certain spacings (W m)
= depth of rod (m)
= diameter of rod (m).
Example from Table 7.2
Taking a reading from Table 7.2, the approximate resistance of a rod driven to a
depth of 3 m is calculated as follows:
Ground Earthing
169
Fig. 7.4 Traditional site chart: earth tester readings for different spacings enabling rod
resistance values to be read directly off the vertical scale.
r = 0.366 ¥
538
3¥3
¥ log10
W
3
0.016
= 180 W
In general, if the curve showing the calculated resistance drops off at least as sharply
as the diagonals in Fig. 7.5, it is more advantageous to carry on driving a single rod
rather than use a number of shorter rods connected in parallel. However, it must
not be assumed that deep driven rods are the answer in every case. Some sub-soils
are quite unsuitable and it is not worth continuing to drive into these. For example,
the underlying soil may be rocky and have an increasing resistivity with depth. In
170
Handbook of Electrical Installation Practice
Fig. 7.5 Curves of specific resistivity and electrode resistance plotted on a logarithmic grid.
such cases, it is better to use a multiple number of rods connected in parallel, each
of which is driven to about 4 m depth. Rods should always be at sufficient depth
such that their resistance value is not significantly affected by seasonal changes
which may change the soil resistivity. As discussed earlier, the variation in the water
table is important in this respect and advice on this may be obtained via geotechnical studies or local knowledge. Generally, the deeper parts of the rod
(i.e. beyond 1.5 m depth) are not prone to significant seasonal variation. Ideally, the
separation of these earth electrodes should not be less than their depth; for example,
if an electrode is driven 10 m deep, then the earth electrode nearest to it should be
positioned at least 10 m away, otherwise the interaction between them will reduce
the overall effectiveness.
Where multiple earth rods are used, they are normally connected together with
bare copper tape or cable. A bare interconnection acts as an additional electrode
and helps to reduce further the overall resistance value. The depth at which
interconnecting tape or cable is installed should be sufficient to afford protection
and mechanical strength, and maintain contact with damp soil. This is normally
0.6–1.0 m deep. In areas subject to extremely low winter temperatures, greater depth
may be necessary. The top ends of the vertical earth electrodes are installed to the
Ground Earthing
171
Fig. 7.6 Total resistance of multiple earth rods expressed as a percentage of a single rod.
same depth (0.6–1.0 m) to reduce voltage gradients on the soil surface. Large electrode networks should have facilities for testing either individual rods or groups of
rods. Contactless testers are used for the measurements so that the electrode
remains intact and in service.
The improvement in the earth resistance that can be expected from the installation of additional rods in terms of the percentage improvement each additional rod
produces, is approximately as follows:
Second rod 60%
Third rod
45%
Fourth rod 35%.
Clearly, increasing the number of rods has a diminishing benefit, as illustrated in
Fig. 7.6.
The above method of calculating the resistance is limited to straightforward structures and conditions. For more complex earthing arrangements and soils which have
several layers (particularly where one is rock), more detailed estimates or computer
modelling is required. New standards require calculation of touch and step potentials across a substation site. The earthing installation directly affects these potentials and computer modelling enables them to be calculated accurately throughout
the site. It is also possible to measure these potentials. To illustrate the power of the
computational modelling tools available, Fig. 7.7 shows the potential on the soil
surface above an earth grid, in three dimensions. The results obtained can also be
presented in two dimensions, as in Fig. 7.7b. The two-dimensional facility is often
172
Handbook of Electrical Installation Practice
Ground Earthing
173
used to produce the 430 V or 650 V hot zone contours required by telecommunication authorities.
Artificial method of reducing earth resistivity
Low resistivity materials
It is widely thought that adding low resistivity materials to the soil in the immediate vicinity of the earthing system or rod will have a dramatic effect on reducing its
resistance. This is not normally true. There is always a contact resistance between
the electrode and the soil. Where a new rod has been driven into the ground, the
sideways movement will have increased the width of the hole in which the rod lies.
The gap between the rod surface and the compressed soil to its side will introduce
a large contact resistance which will be apparent when testing the resistance of the
rod. However, experience shows that this resistance falls over time as the soil
becomes consolidated around the rod due to rainfall, etc. One way to accelerate this
is to add a low resistivity material, such as bentonite slurry, as the rod is driven in.
Bentonite is a fine, naturally occurring clay powder. It is mixed with water to form
a slurry. As the earth electrode is driven into the soil the bentonite is drawn down
by the rod. By continuously pouring the mixture into the hole as driving proceeds,
a sufficient quantity is dragged down to fill most of the voids around the rod and
lower its resistance. Bentonite is thixotropic in character and therefore gels when
in an inert state, so should not leach out. It has a low resistivity and does not dry
out under normal conditions. However, its use in this manner does not necessarily
produce a significantly lower earth resistance than that which would occur naturally
over time. In some cases, installing the rods a little deeper can achieve a better result
than using low resistivity material.
Adding bentonite and similar material, such as marconite, in a trench or larger
drilled hole around the electrode has the effect of increasing the surface area of
the earth conductor, assuming its resistance is lower than that of the surrounding
soil. Figure 7.8 shows the effect on the resistance value of one rod when its radius
(and hence surface area) is increased. Clearly there is an improvement, but this falls
off rapidly with increasing radius, and the cost quickly becomes prohibitive. Additional reasons for increasing the surface area may include a requirement to reduce
the build up of electrochemical deposits on the electrodes which may reduce their
efficiency, or for high frequency earthing (lightning protection, etc.).
Chemical treatment
Treating the soil surrounding the earth electrode with chemicals normally only provides a temporary improvement as the chemicals will usually be dispersed over time
by rainwater. The environmental effects may also mitigate against this undesirable
practice. In addition, one must ensure that the chemicals used do not have any
corrosive effect on the electrode material.
One interesting technique used in rocky sites in Hungary was to drill a hole
several metres deep into the rock. Explosives were introduced and when detonated,
Fig. 7.7 (a) Potential rise on the soil surface above an earth grid and terminal tower; (b)
touch voltage contours above a buried substation earth grid.
174
Handbook of Electrical Installation Practice
Fig. 7.8 Curves of rod resistance with increasing rod radius.
formed a cavity and fissures. Low resistivity material was then introduced into the
cavity and fissures and the earth electrode installed within it. This forms a relatively
large electrode at a lower cost than drilling.
Marconite, concrete or similar materials are also now increasingly used around
structures where these are to be used as part of the earthing system.
RESISTANCE MEASUREMENT OF ELECTRODE SYSTEMS
Provided it has sufficient noise immunity (or filtration), the same instrument that is
used for soil resistivity surveys can also be used for measuring the resistance of an
earth electrode system. The most common technique used is the ‘fall of potential’
test. It should be noted that safety precautions are necessary while carrying out this
test if the earth system is connected to live equipment; for example, fused leads and
an appropriate isolation routine are necessary. This is to ensure that an earth fault
occurring while testing does not subject the individual handling the test probes to
a transferred potential.
Potential and current terminals on the tester are connected to the earth electrode
under test. The remaining current terminal is connected to a current probe which is
inserted into the ground some distance away. The remaining potential terminal is
connected to a voltage probe which is situated at 61.8% of the distance between
the current probe and the rod (or centre of the earth grid). Current is circulated
between the electrode under test and the current probe, via the current circuit and
the ground. From the voltage detected at the 61.8% position, the apparent resistance is displayed on the tester. Under ideal conditions, this apparent resistance
reading corresponds to the actual resistance value of the earth electrode. The reason
for choosing this position is based on mathematical theory applied to uniform soil.
However, the test electrode and current probe must be sufficiently far away from
the electrode under test that they do not interact. For earth rods the current lead
would be about 100 m long and the voltage lead 61.8 m. For longer leads the same
ratio must be maintained.
The most common cause of error arises from placing the current electrode too
close to the electrode under test. The effects of the two electrodes overlap and the
Ground Earthing
175
measured resistance will give a lower value than the real one. The second most
common mistake is placing the voltage probe too close to the test electrode, which
normally produces a much lower reading than the true value.
The theory (and hence the 61.8% rule) does not hold if the soil is not uniform,
the grid is large or (as stated above) the current electrode is too close. Computer
simulation can again assist here, by predicting the distance from the grid at
which the real resistance will be measured for the test arrangement and electrode
dimensions.
The fall of potential method can be used on larger grids, but it is suggested
that the current electrode is positioned at a minimum distance of ten times that
of the diagonal distance across the grid. This is not normally practical, so several
derivatives of the fall of potential method have been developed. These include
the slope method (where the gradients between adjacent measurement points are
computed) and the intersecting curves method. In another derivative of the test,
the voltage probe is moved out at right angles to the grid/current probe traverse.
The distance of the probe from the grid is progressively increased until the resistance figure barely changes. This figure should then be just below the actual grid
resistance.
There must be no metallic underground pipes or cables running in the same direction as the test route as this will again produce an incorrect earth reading.
Where the earth grid is large or has long radial connections, e.g. to cables or tower
line earth wires, the resulting size of the earth grid is so large that the fall of potential may be impractical. Measurement can then be made via current injection
techniques, which require specialist equipment.
TYPES OF EARTH ELECTRODES
Earth electrodes are made from a number of materials which include cast iron,
steel, copper and stainless steel. They may be in the form of plates, tubes, rods or
strips. The most favoured material is copper. It has good conductivity, is corrosion
resistant to most of the chemicals that exist in soil and it is a material that is easily
worked. Earth plates are normally of cast iron or copper, typically one metre or
more square, with surface ridges to increase the surface area in contact with the soil.
They have good current-carrying properties, but as they are often buried at a relatively shallow depth, their resistance tends to be high, thus increasing the number
needed.
An alternative method, which is particularly suitable for hard ground with a
shallow layer of top soil, is to install lengths of copper tape in predug trenches. This
method is used both in power installations and in communication networks where
it has a wider application.
The most versatile type of earth electrode is the driven rod.This may be of copper,
copper clad steel, galvanised steel or austenitic iron. Standard sizes are 1.0–2.5 m in
length and 16 mm diameter. The rods are extensible and are joined together by
either an internal stud or an external sleeve.
While copper rods are an excellent material for earth electrodes, they do not have
sufficient strength or hardness to enable them to be driven to great depths. If copper
176
Handbook of Electrical Installation Practice
is used the rods are normally inserted in predrilled holes to overcome this problem.
Copper clad steel rods are more suitable for driving and will penetrate most types
of soil to a depth of 10–15 m. It is important when using copper clad steel rods to
ensure that the copper is actually bonded to the steel. If the copper covering is only
extruded onto the steel core, then it has no adhesion and damage may occur during
installation, and corrosion will inevitably follow.
Criticism has been made of the external sleeve type of coupling used for joining
the rods. This has a larger diameter than the rod and it increases the size of the
driven hole. This increases the difficulty of installation and makes the initial earth
resistance high. The latter may be overcome by time or by driving the rods through
a puddle of bentonite, thus assisting consolidation in the hole. Internal couplings are
a better option, when available.
Another method to alleviate the problem of mechanical force from the ground,
is to use a stranded bare copper cable which is pulled into the ground giving very
Fig. 7.9 Deep earthing system manufactured by Elpress.
Ground Earthing
177
good contact as ‘the installation slot’ does not enlarge. The copper cable is fitted in
a driving head and a leading steel tube holds it in position. This tube is driven into
the ground and extension tubes are added as required. The conductor is continuous
and may be taken direct to an earth busbar without introducing any joints. The
method of installation is shown in Fig. 7.9. The steel tubes may corrode away over
time but the copper cable remains as the earth electrode.
There are examples of more ‘exotic’ earth rod designs used for special applications; for example, a cylindrical copper/alloy casing which contains hydroscopic
chemicals to attract water to the vicinity of the rod. These have limited application,
mainly to overcome seasonal effects at shallow depths.
INSTALLATION
Some form of power hammer is needed to install impact driven rods. Electric, petrol,
hydraulic oil, or air type driven tools have all been used successfully, as shown in
Figs 7.10 and 7.11. Air tools are the lightest but require a large compressor to
operate them. A petrol driven road breaker, with a special head to go over the end
of the rod, is extremely efficient for this work. It is entirely self-contained and can
be used in cramped conditions.
While impact tools can be hand-held for a short period, it is more usual to support
them with a rig which will take their weight while they are hammering the rod. On
compacted ground, installation can take some time, especially after the electrode
has been driven some 10 m or so. Rigs vary from simple tripods to more elaborate
Fig. 7.10 New method showing a copper-weld earth rod driven by hydraulic ‘mole’
Grundomat (T T. UK Ltd).
178
Handbook of Electrical Installation Practice
Fig. 7.11 Standard method showing copper-clad earth rod driven by a compressed air tool
with compressor, as used by Stemet Earthing Co. Ltd.
Fig. 7.12 Reversible pole hammer (Elpress).
Ground Earthing
179
vehicle-mounted models. A rig which can be easily assembled and dismantled is
the most practical to use, as it is often impossible to manoeuvre a vehicle to the
position in which an earth electrode has to be installed.
Site conditions dictate the layout of the earth electrode system, but it has been
found that many earthing problems can be solved by impact driven earth rods. A
hand-held electric pole hammer may suffice on small installations where high resistance values are adequate (Fig. 7.12). A note of caution however: make a thorough
investigation of structures or utility equipment in the area before installing vertical
rods.
STANDARDS APPLICABLE TO EARTHING PRACTICE
Some of the main authoritative documents setting out the principles, rules and
guidance are listed in Appendix 1 at the end of the handbook. In addition to these
there are codes of practice. In particular, those applicable to the quarrying, mining,
petrochemical or chemical industries should be referred to. The Health and Safety
Executive can normally assist in providing details of the most up-to-date,
specific practices required.
CHAPTER 8
Cathodic Protection
J.D. Thirkettle, MICorr, MNACE
G. Clapp, MA, MSc
Revised by J.D. Thirkettle, MICorr, MNACE
(Senior Corrosion Technologist, ACEL/NECE)
INTRODUCTION
Cathodic protection is a dynamic electrochemical process for the prevention of
metallic structures which are buried, immersed or otherwise in contact with an electrolyte. Structures to which cathodic protection may be typically applied include
pipelines, tank farms, plant pipework, steel work, well casings, sheet and tubular pile
systems, jetties, piers, offshore facilities, production platforms, and ships. In addition
to the above, cathodic protection is now commonly used for corrosion prevention
of above ground structural steel and reinforcing steel in concrete.
Standards and normative documentation
Cathodic protection in the UK is generally carried out in accordance with the appropriate British Standards. These are:
•
•
BS 7361, Cathodic protection: Part I: Code of practice for land and marine
applications
BS 5493: Code of practice for the coating of iron and steel structures against
corrosion.
Other normative documentation is available from:
•
•
•
•
•
Institute of Corrosion (UK)
National Association of Corrosion Engineers (USA)
Society for the Cathodic Protection of Reinforced Concrete (UK)
European Standards
Corporate standards issued by operating organisations.
European Standards are currently in draft or more advanced stages of preparation.
These are likely, in some cases, to replace or supplement British Standards. The
British Standards Institute will advise whether European standards will replace
British Standards or Codes of Practice.
180
Cathodic Protection
181
Theory of corrosion
Corrosion of a metallic substrate in contact with an electrolyte is fundamentally an
electrochemical process. The corrosion process involves anodic areas (anodes) at
which metal is converted to positive ions and cathodic areas (cathodes) at which an
oxidising species, usually oxygen, is reduced. An electric current flows from the
anode to the cathode through the electrolyte, and the species formed at the anodic
and cathodic areas combine to form the corrosion product. The circuit is completed
by current flow within the metal between the cathodic areas and the anodic areas.
A particular area of metal is determined as anodic or cathodic by the reactions
taking place on it. The following must be present for corrosion to occur: anode,
cathode, electrolyte and return current path.
Electrochemical and galvanic series
When two different metals are in metallic contact and in the same electrolyte, in
general one metal will have a greater tendency to go into solution than the other.
The electrochemical and galvanic series are attempts to make this predictable. The
two series are the potentials adopted by different metals in an electrolyte. The electrochemical series comprises the potentials adopted by metals when in a solution
of their own ions, thus it does not have much practical application. The galvanic
series comprises the potentials adopted by metals when in seawater or soil, thus corresponding to a real situation. It is only possible to measure potential differences,
as absolute values of potential cannot be obtained. In order to standardise potential measurements a particular potential value is taken to be zero. One such standard is the potential of the standard hydrogen electrode.
When two metals are in metallic contact in the same electrolyte the metal with
the more negative potential in the galvanic series will be made more anodic and
suffer accelerated corrosion; the other metal will become more cathodic and have
reduced corrosion. Tables 8.1 and 8.2 show the electrochemical and galvanic series
of some metals of interest in corrosion control and cathodic protection work.
The two series do not indicate the magnitude of the change in corrosion rate
which will occur when two metals are connected together in the same electrolyte,
but only the direction of any change.
Corrosion cell
There are two basic cell arrangements in which corrosion takes place, known as
galvanic and electrolytic cells.
Galvanic cell
A galvanic cell comprises anode, cathode, electrolyte and return current path where
the corrosion current flows spontaneously. The anode is negative with respect to the
cathode. Galvanic cells exist not only when dissimilar metals are in contact but may
be caused by one or more of the following conditions: dissimilar surface conditions;
differences in heat treatment; differences in local stresses within metal; differences
in concentrations of ionic species; differences in oxygen concentrations; differences
182
Handbook of Electrical Installation Practice
Table 8.1 Electrochemical series of
some metals.
Table 8.2 Galvanic series of metals. This table provides a practical
guide to galvanic couples when subject to immersion in the same
electrolyte.
* Typical potential, normally observed in neutral soils and water, measured
with respect to a copper/copper sulphate reference electrode.
in soil conditions. Examples where galvanic cells are created by dissimilar surface
conditions and differential aeration are shown in Fig. 8.1.
Electrolytic cell
An electrolytic cell comprises anode, cathode and electrolyte, where the corrosion
current flows as a result of the application of an external electromotive force. The
external potential causes current to flow into the electrolyte from the anode and
Cathodic Protection
183
Fig. 8.1 Galvanic corrosion.
back to the power source through the cathode. The anode is made positive with
respect to the cathode by the externally applied e.m.f.
This reversal of polarity of the external terminals of an electrolyte cell, as compared with a galvanic cell, is a source of confusion; this confusion can be avoided if
it is remembered that in all types of electrochemical cells, current always enters the
electrolyte from the anode and leaves the electrolyte at the cathode.
PRINCIPLES OF CATHODIC PROTECTION
In all corrosion cells, corrosion normally occurs only at anodes or anodic sites. There
are, however, exceptions; these include copper and aluminium, which are amphoteric. If an entire structure buried in the soil, or immersed in water, is made the
cathode of an electrochemical cell so that the entire surface receives current from
the electrolyte, the structure will not corrode. Under these conditions, the structure
is said to be cathodically protected.
The cell, of which the protected structure is the cathode, may be either galvanic,
with current entering the electrolyte from the galvanic anodes more electronegative than the protected structure, or electrolytic, with the anode electrically connected to the positive terminal of an external power source. In any cathodic
184
Handbook of Electrical Installation Practice
Fig. 8.2 Sacrificial cathodic protection system.
Fig. 8.3 Impressed current cathodic protection system.
protection system, the structure to be protected is made more negative with respect
to the surrounding medium so that it receives current from the electrolyte, and this
current is conducted through an external circuit to an anode system where it enters
the electrolyte. The principles of protection by the galvanic (sacrificial) and electrolytic (impressed current) system of cathodic protection are illustrated in Figs 8.2
and 8.3.
Mechanism of cathodic protection
To understand cathodic protection one needs to consider both general and electrical concepts.
General concept
On the surface of any corroding structure there are cells consisting of anodic and
cathodic areas. Current is discharged from the metal surface to the electrolyte at
Cathodic Protection
185
the anodic areas and returned to the metal structure in the cathodic areas. Qualitatively, it can be seen that when an external current is impressed on the structure,
the current from an external anode tends to oppose the current leaving the structure at the anodic areas. If sufficient current is forced on to the structure to oppose
completely the current leaving the surface at all anodic areas, the structure is cathodically protected and corrosion prevented.
In practice, a structure is deemed to be protected when a minimum negative
structure/electrolyte potential of 850 mV is achieved at all points of the structure.
Where anaerobic conditions exist, a minimum potential of 950 mV must be achieved.
The above values relate to measurements where a copper/copper sulphate reference
electrode is used, generally in the case of buried or onshore applications.Adjustments
in potential value should be made when other reference electrodes are used for measurements. Protective criteria values should take account of errors caused by electrical currents flowing in the electrolyte known commonly as IR Drop error. Potential
levels vary, depending on where the potential is measured and in practice the reference electrode should be placed as close as possible to the structure under test. It is
common practice for the IR Drop error to be quantified as far as possible by the measurement of polarised (instant off) potentials where an interrupter is placed in the
cathodic protection circuit and the current flow interrupted for a brief time.
Electrical concept
In order to understand more fully the mechanism of cathodic protection, consider
an anode and a cathode immersed in a solution and connected in such a manner
that the potentials and currents involved in the corrosion reaction can be measured.
Such a condition exists in the circuit indicated in Fig. 8.4.
The potentials of the anode and cathode exist when no corrosion current flows.
These values can be measured directly against a reference electrode. If switch S1 is
closed and the corrosion current Ia is varied, the anode and cathode potentials (Ea
and Ec) vary accordingly with the flow of corrosion current, due to polarisation of
the electrodes. The polarisation voltage always acts in the direction opposing the
flow of current.
The steady-state corrosion current is that current which flows when the external
resistance (R1) is reduced to zero; this occurs when the sum of the polarisation
potential drops at the anode and cathode equals the open circuit potential difference between the anode and cathode. Under these conditions, the polarised anode
and cathode potential are equal.
If switch S2 is closed, protective current will be applied to the system through the
cathodic protection anode. As the protective current is increased, the corrosion
current Ia will gradually decrease until it finally reaches zero. In the freely corroding condition, the cathodic current Ic is equal to the anode current Ia. When a small
protective current is applied, the cathode current is increased but the anode current
is decreased; under these conditions, the cathode current equals the sum of the
anode current Ia and the protective current Ip. When complete protection has just
been achieved, Ia is equal to zero and the protective current Ip just equals the
cathode current. This condition exists when the cathode potential is made equal to
the anode open-circuit potential, i.e. cathodic protection is adequate when the
cathode had been polarised to the open-circuited potential of the anode.
186
Handbook of Electrical Installation Practice
Fig. 8.4 Electrical concepts of cathodic protection.
CATHODIC PROTECTION SYSTEMS
There are two types of cathodic protection systems which are used: sacrificial and
impressed current systems.
Sacrificial cathodic protection
Sacrificial cathodic protection involves the use of a galvanic cell so that corrosion
takes place away from the structure being protected. This is achieved by connecting the structure to be protected to a sacrificial anode. The sacrificial anode material is a metal which is more active in the galvanic series, i.e. it adopts a more
negative potential than the metal of the structure to be protected.
Impressed current cathodic protection
Impressed current cathodic protection is an application of the electrolytic cell. An
external source of e.m.f. is used to make the structure to be protected entirely
cathodic. The current which must be passed through the electrolyte on to the
Cathodic Protection
187
structure comes from an electrode which is placed in the electrolyte. This electrode
is the anode or a series of anodes collectively known as a groundbed.
From the viewpoint of the structure, the sacrificial and impressed current cathodic
protection systems are very similar. In both cases current flows on to the surface
of the structure from the electrolyte and this current has the effect of making the
structure more cathodic and thus mitigating corrosion on the structure. There are,
however, differences between the two types of system such that under different circumstances one or other method of application of cathodic protection is preferable.
Measurements
In practical terms the performance and effectiveness of a cathodic protection system
are determined by electrical measurements. These generally comprise voltage and
current measurement in the case of impressed current systems, current in the case
of sacrificial anodes and in both cases structure/electrolyte potentials.
It is to be noted, however, that voltage/current measurements cannot be determined where sacrificial anodes are attached directly to immersed steelwork. In these
cases the effectiveness of the cathodic protection system can only be quantified by
structure/electrolyte potential measurement.
Structure/electrolyte potential measurements are required to determine the effectiveness of cathodic protection. They are necessary because in the field it is not possible to determine by current measurements when the current due to the anodic
processes is totally suppressed by the cathodic protection current. Potential measurements are taken utilising a reference electrode, the potential of which is constant, and which is robust enough for field use. The potentials measured may be
converted to the Standard Hydrogen Electrode Scale. Reference electrodes in
common use are: land-based structures – copper/copper sulphate; marine/undersea
structures – silver/silver chloride; other electrode types are calomel and zinc. Potential measurements are recorded by placing the reference electrode into the electrolyte close to the structure and connected to the structure via a high resistance
voltmeter. When potentials are thus recorded the reference electrode that has been
used should always be stated. Potential measurement reference electrodes are generally used singly but in certain locations multiple reference electrodes may be used
for dual potential measurement or as calibration devices. This particularly applies
to locations where access is difficult, e.g. within concrete structures, within industrial
plant or in the case of deep immersed/buried locations. Routine maintenance of
portable reference electrodes is essential to avoid measurement error, and procedures in respect of cleaning and recharging electrodes should be followed in a
meticulous manner.
Isolation
The design of a cathodic protection system will always be based on the surface area
that is required to be protected. It is essential, therefore, that only the surface area
to be protected should be connected to the cathodic protection system.
The isolation of the structure may be obtained by the use of electrically isolated
joints in the case of pipelines, and by other insulating materials. Certain installation
188
Handbook of Electrical Installation Practice
practices may provide short circuit connections across otherwise insulated joints;
examples include metal conduit and fittings, cable tray, non-insulating pipe supports,
and earthing systems. These should be avoided. If the structure is not isolated electrically from all other buried or immersed metallic structures the cathodic protection system suffers from reduced effectiveness.
Earthing systems
When considering the provision of cathodic protection systems special attention
should be given to the earthing system that will be installed. Such systems often
comprise bare copper wire which is connected to the structure at numerous points.
Apart from the risk that the earth system may electrically connect the protected
structure to other buried structures, it may itself constitute an increase in surface
area and receive cathodic protection current.
It should be noted that cathodic protection is only achieved to the face of the
structure that is designated. Thus a system designed for the external surfaces of the
buried pipeline will not protect the internal pipe wall. Similarly a system designed
for one side of sheet piling will not protect the other side.
INSTALLATION PRACTICE
Cathodic protection systems are always installed according to specified requirements. The installation work is of an electrical nature. The major items of equipment installed are described in the following sections.
Sacrificial anode systems
Sacrificial anode systems represent the simplest form of cathodic protection and
involve the connection of sacrificial anodes to the structure and the placing of these
anodes close to the structure.
Directly fitted sacrificial anodes
In certain cases the sacrificial anodes are directly connected to the structure (e.g.
offshore platforms). The anode has a steel core which is welded or bolted to the
structure. It is important to ensure a satisfactory low resistance electrical contact
with the structure. The anodes may be zinc, aluminium (for offshore use) or magnesium alloy (for onshore use). The shape and size of the anodes depend on
the structure to be protected. Thus a tubular structure (e.g. a submarine pipeline)
being externally protected may have bracelet type anodes. Anodes may be
flush mounting or they may stand-off from the structure. Anodes will be flush
mounting when streamlining is of importance, for example on ship hulls. Where
streamlining is of less importance stand-off anodes are preferred since they provide
a better distribution of cathodic protection. The anode material and quantities
selected depend on surface areas, coating quality (if applied) and electrolyte
resistivity.
Cathodic Protection
189
Indirectly connected sacrificial anodes
Anodes for pipelines, pipework, tanks and other structures are cast generally from
magnesium although in specific instances zinc or aluminium may be used. Magnesium anodes are cast in rod form with a cable attached to facilitate connection to
the structure. Such anodes are usually buried alongside the structure and it is usual
for the anodes to be prepackaged in a cotton sack containing specially prepared
backfill of bentonite (75%), gypsum (20%) and sodium sulphate (5%). The purpose
of this backfill is to provide a homogeneous, rapid wetting, low-resistance electrolyte
in which the anode can be activated. Selective electrolyte materials should also be
used when placing anodes.
A cable is routed from a brazed connection in the anode through the top of the
cotton sack and is accessible for connection purposes. The anode(s) is laid in the
soil close to the structure and connected to the structure by the cable. Anodes
should be installed at the same depth as the structure and no closer than 1.5 m
(ref. BS 7361). No other metallic structure should pass between the anode and the
structure. Anode cables should not be placed above anodes as gas emission from
anode operation may damage cable insulation.
The cable from the anode is always taken to a test facility (see p. 192) and two
cables taken from the test facility to the structure unless otherwise specified. One
cable is for the anode current and the other for test purposes. Cables should be connected to the structure in an approved manner (see p. 192). It is normal for such
anodes to be installed at numerous locations and connected to the structure to
ensure full and effective protection. On land-based systems anodes should not be
installed by direct connection to the structure. All anodes should be connected via
a test point so that measurements can be recorded in respect of current output and
potential and the position of all anodes should be recorded on sketches or drawings for future reference.
Impressed current systems
The installation of impressed current systems is more complex but fewer are generally required. The configurations of impressed current systems are numerous and
it is not practical to detail each possible variation. The following sections therefore
describe the more common installation methods in use.
Marine applications
Anodes for protecting jetties, platforms, vessels, etc. are generally of platinised titanium, niobium or mixed metal oxides; other materials may also be used such as leadsilver alloys. They may take the form of rod or ‘shield’ fabrications and are usually
supplied by manufacturers ready for installation on to or close to the structures.
Shield anodes are either bolted or welded to the structure and rod anodes attached
to the structures as a cantilever or suspended in the electrolyte. Cables are taken
from the anodes via a distribution cable network and connected to the positive terminal of the transformer-rectifier.
A distribution control system is necessary as a number of anodes are connected
in this way to numerous locations throughout the structure. It is also usual for
190
Handbook of Electrical Installation Practice
anodes at different locations to be fitted with cables of varying cross-sectional areas
to compensate for the voltage drop on differing lengths.
In these networks distribution and resistance boxes are generally used. The function of the resistor is to provide adjustment in the amount of current supplied to
each anode during operation. It is important when such structures are protected to
ensure electrical continuity between all parts of the structure where protection is
required. This is often inherent in the design, e.g., welded structures, but must in any
event be accomplished during construction.
A cable capable of carrying the total return current of the system is connected
between the structure and the negative terminal of the transformer-rectifier. In
many cases these installations are required in potentially explosive areas and
equipment must be approved by the relevant authorities such as British Approvals
Service for Electrical Equipment in Flammable Atmosphere (BASEEFA).
The precise method and location of cable fixing and routing and distribution/
junction box positions are invariably specified.
Onshore applications
Impressed current anodes for protection of onshore pipelines, pipework, tanks and
other structures are generally manufactured from high silicon iron, graphite, magnetite or mixed metal oxides. In some cases short-life anodes may be constructed
from scrap steel. A number of anodes are installed in a single position known as a
groundbed. In order to increase the current capacity of a groundbed, anodes are
installed in a carbonaceous backfill generally of coke or calcined petroleum coke
granules.
A structure may be protected by a single groundbed or a number of distributed
groundbeds. The groundbeds should be located at positions electrically remote from
the structure, generally some 50–100 m away (ref. BS 7361). No other metallic structure should pass between the anode and the protected structure.
A groundbed may be installed in a shallow horizontal trench, or vertically in
a shallow borehole, or a single borehole arrangement. The precise location of
the groundbed is specified together with the manner of its installation. In the
case of a horizontal groundbed a trench is excavated for the anodes. The anodes are
laid on a bed of carbonaceous backfill and covered with the same. They are provided with cable tails which are routed to a feeder cable which may be a single
feeder or part of a ring main. Cable connections between the anode cable tails
and the feeder cable are achieved using cable splicing kits and line tap connectors.
The cable is buried, or laid along with other cables in ducting or cable tray and
connected to the positive terminal of the transformer-rectifier. Cables should not
be placed above the anodes as gases emitted from the anodes may damage cable
insulation.
It is usual for the transformer-rectifier to be located close to the structure to minimise d.c. cable lengths and facilitate adjustment and measurements.
All buried cathodic protection cables are installed at least 1 m deep and are protected by tiles, conduit or warning tape. Groundbeds are generally installed such
that the anodes are between 1.23 and 1.5 m deep. It is important to ensure adequate
depth of cable as the ground may be subject to further disturbance for agricultural
or constructional reasons.
Cathodic Protection
191
Test points
It is usual on structures which are buried for considerable lengths, e.g. pipelines, to
provide test points. These are located at predetermined intervals along the length
of the structure. They comprise a cable connected to the structure and brought to
an accessible point on the surface. The cable is then terminated and housed in a test
facility. Methods of termination are specified and include crimped lugs, sweated lugs
or a glanded box with terminals.
EQUIPMENT
The equipment used for cathodic protection installation work is manufactured by
specialists. Their major features are described.
Transformer-rectifiers
A transformer-rectifier comprises a mains transformer and full-wave bridge rectifier. The rectifier elements are generally silicon diodes. The assembly may be oil or
air-cooled and housed in a steel or glass fibre case. It is fitted with a voltmeter and
ammeter, step or continuous d.c. output controllers and equipment with fuses, oilcooled unit breathers and other ancillary items. A transformer-rectifier is manufactured for wall, plinth or pole mounting and designed to operate continuously.
Generally transformer-rectifier units provide a fixed constant current output controlled by manually set switches or autotransformers. In certain circumstances a
variable output automatic unit with thyristor control may be installed.
Anodes
Cathodic protection anodes, with the exception of platinised titanium and niobium,
are manufactured by a casting process and are generally rod shaped. The weight of
an anode varies according to design but typically it would weigh approximately
50 kg. The cast anodes are brittle and great care should be taken when storing, transporting or installing them. When installed the anodes are in intimate contact with
the electrolyte or backfill and cables are routed away from the anode for connection purposes. Cathodic protection cables should not be routed over the top of
anodes, and the length of cable in carbonaceous backfill should be minimised.
Cable
Cable for cathodic protection purposes is usually single core and is insulated and
sheathed (with armouring where necessary) with chemical resistant materials, e.g.
cross-linked polyethylene. Cable is sized not only for electrical capacity but also for
mechanical strength and therefore large diameter cable may be used in certain
instances. Cables are generally laid in continuous lengths, but where cable joints are
necessary they usually take the form of crimped or line tap splice joints which should
be housed in a cable splicing kit filled with epoxy resin.
192
Handbook of Electrical Installation Practice
Carbonaceous backfill
Carbonaceous backfill is manufactured as coke breeze or calcined fluid petroleum
coke. The material comprises chips of coke which must conform to sizing as specified. A maximum amount of ‘fines’ is permitted by specification and it may sometimes be mixed with slaked lime (usually 10% by weight). Carbonaceous backfill
must be carefully installed around the anodes and tamped lightly so that satisfactory electrical contact is achieved to the electrolyte. The calcined fluid petroleum
coke is a round grained material. In all cases the electrical resistivity of the material should be 50 W cm or less.
Distribution boxes
Distribution boxes are manufactured of steel or glass fibre, and where located in
flameproof zones they must meet relevant classification requirements. Each box
is equipped with terminals, resistance control and other facilities as required by
specification.
Cable connections to structures
Several methods are used to attach the d.c. negative or test cables to the structure.
A summary of the common types of cable attachment methods is indicated.
Direct connection
Cables are attached directly to the structure using pin brazing or thermit welding
techniques. Thermit welding systems are not favoured by all users as damage to
high-strength materials may occur. Brazing systems are now widely accepted as a
direct connection method.
Cable attachment plates
A steel plate approximately 50 mm square is attached to the structure. The plate is
welded direct to the metal surface. A bolt is welded to the plate to accept a crimped
or sweated lug cable connection.
Collar/bracelet connections
In the case of pipelines or pipework a collar or bracelet may be attached to the pipe
to facilitate a cable connection.
Test stations
Test stations may be of concrete (in the form of a location designation post), glass
fibre, steel, cast iron or plastics materials. They contain the necessary terminals,
resistors and other items of equipment.
Safety and security
In certain applications the use of security or safety equipment may be required.
These would include:
Cathodic Protection
•
•
•
•
193
Surge diverters to protect cathodic protection transformer rectifiers and other
cathodic protection equipment.
Polarisation cells and similar current shorting devices to protect isolation joints
or other pipeline equipment. These are generally connected to earth beds.
Zinc cells or earth beds where a.c. or d.c. stray earth currents are present or
suspected.
Rectifier bonding where stray earth currents are present and not flowing in a
controlled manner.
The above equipment is designed to protect the installed cathodic protection equipment or structure equipment in respect of operation. The use of such equipment
does not necessarily provide protection to personnel and additional safety equipment may be required for this purpose.
Test equipment
Test equipment needed includes multimeters, which should have a high internal
resistance, with voltage, current and resistance measuring facilities, low-resistance
earth testers, reference electrodes, test cable and hand tools and associated equipment. Other more specialist equipment may be required in specific instances.
The quality of measuring equipment for cathodic protection purposes has shown
significant advance in recent years. Digital instruments and microprocessor-based
and computer-assisted measurement systems are now in general use. The advent of
such instrumentation has allowed the cost effective collection of vast amounts of
data which may be used to assess the operating performance of the system. It is
likely that further advances will be made in this respect as measurement systems
become more sophisticated, accurate and portable.
MONITORING, INSPECTION AND MAINTENANCE
Every installed cathodic protection system requires monitoring and maintenance.
Monitoring will generally take the form of routine voltage, current and potential
measurements to ensure the satisfactory performance of the system.
Specialised inspection procedures include close interval potential surveys (CIPS)
and current density and voltage gradient surveys to analyse applied cathodic protection performance. External coating systems are evaluated by Pearson, current
attenuation and direct current voltage gradient (DCVG) surveys. The purpose of all
monitoring systems is to provide the owner with detailed information with respect
to the effectiveness of an external coating system and applied cathodic protection.
Any deviation from required criteria or other defects that are determined are generally corrected under a maintenance programme. Maintenance will also include the
physical and electrical inspection of installed equipment, with remedial measures
taken as appropriate to maintain the system in perfect working order. The importance of properly executed monitoring and maintenance schemes for cathodic
protection systems to ensure continued integrity performance is generally regarded
194
Handbook of Electrical Installation Practice
as of prime importance by most owners and operators as an integral part of their
corrosion control programme.
INTERACTION
Interaction is the presence of stray earth or other external d.c. or a.c. currents in
the electrolyte which may affect the performance of installed cathodic protection
systems. The installation of a cathodic protection system itself, particularly of the
impressed current type, may cause corrosion interaction on neighbouring or adjacent structures. The effect of such interaction may be to increase the corrosion rate
thus leading to shorter service life. All newly installed cathodic protection systems
should therefore be subject to interaction notification and testing. Where tests show
unacceptable levels of interaction, safeguard measures should be taken to correct
the situation. Where cathodic protection systems are installed close to low-voltage
d.c. circuits (e.g. railway track signalling systems), serious disruption of circuit
balance and operation can occur.
Stray current leading to accelerated corrosion effects may also be detected as a
result of natural geomagnetic effects. In all cases a test programme is required
so that appropriate mitigating actions can be taken. Any subsequent changes in
operating circumstances of the cathodic protection system will necessitate repeat
interaction testing.
Reference should be made to British Standard Code of Practice 7361: Part 1 for
interaction testing and other requirements regarding installation.
PROTECTION OF STEEL IN CONCRETE
The application of cathodic protection systems as a corrosion prevention measure
is being extended to structures hitherto not considered appropriate. Significant areas
of development have included the protection of steel in concrete and metallic structures which are not continuously in contact with an electrolyte but operate in corrosive conditions. Protection of steel in concrete is now widely used to ensure
structural integrity whereby cathodic protection impressed currents are applied to
reinforcing steel within concrete where chlorides are likely to be present. Anode
systems generally comprise titanium or mixed metal oxide mesh or electrically conductive paint/coating systems laid on the external concrete surface so that current
may flow uniformly to the reinforcing bars within the structure. Testing and monitoring are carried out via fixed reference electrodes installed at representative sites
throughout the protected structure. These may be connected permanently to a centralised data logger or alternatively used with portable measurement equipment.
The application of cathodic protection to steel within concrete is of a specialist
nature and does not accord with the criteria set out in this chapter. Further information is available from the Society for the Cathodic Protection of Reinforced
Concrete.
Cathodic Protection
195
RECENT DEVELOPMENTS
Cathodic protection is also applied to metallic structures which are intermittently
in contact with an electrolyte of corrosive or potentially corrosive nature. This
includes above-ground metallic structures subject to wetting by either natural electrolytes (e.g. rain or salt water) or artificial electrolytes from process manufacturing. Impressed current anodes are attached to the structure via insulated pads, and
current is applied when the electrical resistance between the anode and cathode
allows these currents to flow. This form of cathodic protection is not subject to the
testing and monitoring procedures previously mentioned but is visually inspected
on a frequent and regular basis. Recent evidence gathered from long term testing
of such structures indicates that the method is effective for continued operating
integrity.
It is expected that cathodic protection will continue to find new applications
with the development of new materials and methods to ensure technical and
fiscal viability. In all cases, however, installation of cathodic protection equipment
remains an electrical discipline and subject to electrical installation practice and
procedures.
CONCLUSIONS
Cathodic protection is a specialist technology used for corrosion control, but the
installation of cathodic protection equipment conforms to the appropriate engineering standards. Specialist advice should be sought, however, where no clear or
adequate specification exists.
FURTHER INFORMATION
Further information with respect to cathodic protection is available from the following organisations:
Institute of Corrosion
Corrosion House
Vimy Court
Vimy Road
Leighton Buzzard
LU7 1FG
National Association of Corrosion Engineers
PO Box 218340
Houston
Texas
TX 77218–8340
196
Handbook of Electrical Installation Practice
Society for the Cathodic Protection of Reinforced Concrete (SCPRC)
PO Box 72
Leighton Buzzard
Bedfordshire
LU7 7EJ
Pipeline Industries Guild
14/15 Belgrave Square
London
SW1X 8PS
CHAPTER 9
Lightning Protection
J. Sherlock
(Technical Manager, Furse/Thomas & Betts)
P. Woods
(Marketing Manager, Furse/Thomas & Betts)
INTRODUCTION
Traditionally, the subject of lightning protection has developed in two directions:
(1) Protecting structures
(2) Protecting electronic systems.
It will be appreciated that, although the topics are related, the sensitivity of the two
elements to lightning strikes differs considerably.
It is essential that there should be no confusion as to the precautions that need
to be taken for each condition. For this reason this chapter has been divided into
two stand-alone parts, which in some instances duplicate important data.
PART 1. PROTECTION OF STRUCTURES
Characteristics of lightning
Lightning strokes are the visible discharge of static electricity accumulated in storm
clouds created by meteorological conditions. Strokes may occur within the cloud,
between clouds, or from the cloud base to earth or earthed structures.
Lightning is formed as a result of a natural build-up of electrical charge separation in storm clouds. The base of a storm cloud is commonly 5–10 km above
the earth’s surface, with the cloud 12 km high. The charge at the base of the cloud
is usually negative and induces an equal and opposite charge on the earth’s surface
and earthed objects beneath the cloud. Buildings of masonry, concrete and timber
are sufficiently conductive to reach the same potential as the earth’s surface.
The earth’s atmosphere contains drifting pockets of ionised air, which also take
on a charge of opposite polarity to the cloud base, and the presence of such a pocket
near the cloud can create a potential difference sufficient to cause electrical breakdown of the air, and a downward leader stroke develops from the cloud, having a
current of a few hundred amperes. A step progression can then develop from pocket
to pocket of the leader stroke towards the earth in a few microseconds until the tip
of the leader is within a distance of 50–100 m from some point on the earth. At this
197
198
Handbook of Electrical Installation Practice
Fig. 9.1 Development of the downward stepped leader and upward streamer.
stage the potential difference is sufficient to initiate an upward discharge or
streamer from the earth or some object on it (Fig. 9.1). The distance at which this
occurs is the striking distance of the stroke. The downward stepped leader and
upward streamer rapidly advance until they meet, forming a continuous ionised path
from cloud to earth, initiating the full visible discharge.
The fast rise time and large peak amplitude of the stroke can produce severe
mechanical effects. Long-duration currents can cause fire, while short-duration highcurrent peaks tend to tear or bend metal parts when they make contact. A typical
current amplitude against time waveform is illustrated in Fig. 9.2.
Current magnitudes can range from several kA up to 200 kA. Fortunately super
bolts of over 100 kA are rare, the statistical average being 20 kA.
The core of the discharge may reach a temperature of 30 000 K causing explosive
expansion of the air and the typical sound of thunder. The resulting shock wave
close to this stroke readily dislodges tiles from roofs.
The ‘rolling sphere’ concept
Given the lightning process already described, it is logical to assume that a lightning strike terminates on the ground (or on structures) at the point where the
upward streamer was originally launched.
Lightning Protection
199
Fig.9.2 Current amplitude against discharge time of a typical lightning strike.
These streamers are launched at points of greatest electric field intensity and can
move in any direction towards the approaching downward leader. It is for this
reason that lightning can strike the side of tall structures rather than at their highest
point.
The position of the greatest field intensity on the ground and on structures will
be at those points nearest to the end of the downward leader prior to the last step.
The distance of the last step is termed the striking distance and is determined by
the amplitude of the lightning current. For example, points on a structure equidistant from the last step of the downward leader are equally likely to receive a
lightning strike, whereas points further away are less likely to be struck (Fig. 9.3).
This striking distance can be represented by a sphere with a radius equal to the
striking distance.
Lightning frequency
Lightning is nothing more than a long spark. However, it is estimated that about
2000 storms exist at any one time in the world, hurling 30 to 100 flashes to the ground
every second. If these estimates are correct, then each year over 3 billion lightning
bolts bombard the earth.
STRIKE PROBABILITY
The route of a downward leader, the striking distance and the point where an
upward streamer starts are all unpredictable, but hilly or mountainous areas naturally provide a shorter discharge path, as do tall, isolated structures. There is, therefore, a reasonable probability that taller structures are struck more often than low
structures. If a structure is sufficiently conductive in itself, or is provided with a low-
200
Handbook of Electrical Installation Practice
Fig. 9.3 Striking distance (last step).
resistance conducting path to earth, and is strong enough at the point of strike to
withstand the impact of the expanding air, the lightning is discharged without
damage to the structure.
Those structures that are non-conductive will require the installation of lightning
conductors. A lightning conductor is incapable of discharging a thundercloud
without a lightning flash. Its function is to divert to itself a lightning discharge which
might otherwise strike a vulnerable part of the structure to be protected and to
convey the current safely to earth. The British Standards Institution has published
a code of practice, BS 6651: 1999, Protection of structures against lightning. This code
gives sound practical advice on how to protect a structure from lightning.
The need for protection
Before proceeding to design a detailed lightning protection system, first carefully
consider if the structure needs protection.
In many cases, it is obvious that some form of protection is required. High-risk
structures, i.e. explosives factories, oil refineries, etc., will require the highest possible class of lightning protection to be provided. In many other cases the need for
protection is not so evident.
Lightning Protection
201
BS 6651 provides a simple mathematical overall risk factor analysis for assessing
whether a structure needs protection. It suggests that an acceptable lightning strike
risk factor is 10-5 per year, i.e. 1 in 100 000 per year. Therefore, having applied the
mathematical analysis to a particular set of parameters, the scheme designer will
achieve a numerical solution. If the risk factor is less than 10-5 (1 in 100 000), for
example 10-6 (1 in 1 000 000), then in the absence of other overriding considerations,
protection is deemed unnecessary. If, however, the risk factor is greater than 10-5,
for example 10-4, then protection would seem necessary.
A suitable analogy could be made with the odds in horse racing. The shorter the
odds (e.g. 5 : 1), the more likely it is that the horse will win the race. The longer the
odds (e.g. 100 : 1), the less likely it is that the horse will win.
The shorter the risk factor (e.g. 1 in 10 000) the greater the risk that a structure
will be hit by lightning. The longer the risk factor (e.g. 1 in 1 000 000) the less likely
it is that the structure will be hit by lightning.
It is acknowledged that certain factors cannot be assessed in this way and these
may override all other considerations. For example, if there is a requirement that
there should be no avoidable risk to life or a requirement for occupants of a building always to feel safe, then this will favour the installation of protection, even
though it would normally be accepted that protection is unnecessary.
The factors which should be considered for determining an overall risk factor can
be summarised as follows.
The geographical location of the structure
This pinpoints the average lightning flash density or the number of flashes to ground
per km2 per year. For structures sited within the UK this figure can be taken from
the map in Fig. 9.4.
The effective collection area of the structure
This is the plan area, projected in all directions taking account of the structure’s
height. The significance is that the larger the structure, the more likely it is to be
struck (Fig. 9.5).
For a simple rectangular box shaped structure as illustrated in Fig. 9.5, the collection area (symbol Ac) is simply the product of:
Ac = LW + 2LH + 2WH + pH 2
where: L = length
W = width
H = height.
The probable number of strikes to the structure per year (P) is the product of the
flash density and the collection area, thus
P = Ac ¥ N g ¥ 10 -6
where Ng = the number of flashes to ground per km2 per year. (The number 10-6 is
included because Ac is in m2 whereas Ng is per km2.)
202
Handbook of Electrical Installation Practice
NOTE 1 This lightning density map was compiled by E.A.Technology Ltd from data accumulated over 10 years.
NOTE 2 A linear interpolation should be used to determine the value of the lighning flash density, Ng, for a location
between two contour lines.
Fig. 9.4 Lightning flash density to ground (Ng) per square kilometre per year for the British
Isles.
Lightning Protection
203
Fig. 9.5 Details of structures and collection areas.
The intended use of the structure
Is it a factory or an office block, a church or perhaps a hospital?
The type of construction
Is it built of brick or concrete? Does it have a steel frame or a reinforced concrete
frame? Does it have a metal roof?
The contents of the structure
Does it contain valuable paintings, or a telephone exchange with important equipment, or is it maybe an old people’s home?
The location of the structure
Is it located in a large town or forest or on an isolated hillside?
The topography of the country
Is the structure located in generally flat countryside or in a mountainous area?
The last five factors can be interpreted from Tables 9.1–9.5 and are termed ‘the
weighting factor values’. They denote a relative degree of importance in each case.
These tables are taken from BS 6651.
A sample calculation of overall risk factor
A school building in the east of England with brick walls and a metal roof, and
located close to similar types of buildings in a wooded area. The dimensions of the
school are shown on page 206.
204
Handbook of Electrical Installation Practice
Table 9.1 Weighting factor A (use of structure).
Table 9.2 Weighting factor B (type of construction).
Type of construction
Value of
factor B
Steel frame encased or reinforced concrete with metal roof
0.1
Steel frame encased with any roof other than metal*
0.2
Reinforced concrete with any roof other than metal
0.4
Brick, plain concrete or masonry with any roof other than
metal or thatch
1.0
Timber framed or clad with any roof other than metal or
thatch
1.4
Brick, plain concrete, masonry, timber framed but with
metal roofing
1.7
Any building with a thatched roof
2.0
* A structure of exposed metal which is continuous down to ground level is excluded from the table
as it requires no lightning protection beyond adequate earthing arrangements.
Lightning Protection
Table 9.3 Weighting factor C (contents or consequential effects).
* This means specially valuable plant or materials vulnerable to fire or the
results of fire.
Table 9.4 Weighting factor D (degree of isolation).
Table 9.5 Weighting factor E (type of country).
205
206
Handbook of Electrical Installation Practice
L = 60 m
W = 60 m
H = 15 m.
The risk factor can be calculated as follows using the map in Fig. 9.4 and Tables
9.1–9.5.
•
•
Determine the number of flashes to ground per km2 per year, Ng. From the map
in Fig. 9.4 this is 0.7.
Determine the collection area, Ac, of the school building.
Ac = LW + 2LH + 2WH + pH 2
= (60 ¥ 60) + 2(60 ¥ 15) + 2(60 ¥ 15) + p ¥ 15 2
= 3600 + 1800 + 1800 + 707
•
= 7907 m 2 .
Determine the probability of being struck, P.
P = Ac ¥ N g ¥ 10 -6
= 7907 ¥ 0.7 ¥ 10 -6
•
•
= 5.535 ¥ 10 -3 (or 0.005535)
Applying the relevant weighting factors from Tables 9.1–9.5:
A = 1.7
B = 1.7
C = 1.7
D = 1.0
E = 0.3
The overall weighting factor = A ¥ B ¥ C ¥ D ¥ E = 1.4739.
Therefore, the overall risk factor
= probability of being struck ¥ overall weighting factor
= 5.535 ¥ 10 -3 ¥ 1.4739
= 8.16 ¥ 10 -3 (or 0.00816)
Or expressing this answer as a reciprocal we obtain 1 in 122.
As 10-5 (1 in 100 000) is the criteria for determining whether protection is necessary, we can see that 1 in 122 is ‘shorter odds’ and so protection is necessary.
Having determined that lightning protection is necessary, we must now consider
the actual design of the installation. To do this we must understand the principles
of the zone of protection.
Zones of protection
BS 6651 qualifies, in detail, the meaning of ‘zones of protection’ and the ‘protective
angle’. It is sufficient to say that the ‘zone of protection’ is simply that volume within
which a lightning conductor provides protection against a direct lightning strike by
attracting the strike itself (Figs 9.6–9.8).
As can be seen in Fig. 9.6, structures below 20 m are regarded as offering a 45°
protection angle. For structures greater than 20 m in height (Fig. 9.7), the protection
Lightning Protection
Fig. 9.6 Zones of protection.
Fig. 9.7 Zones of protection.
Fig. 9.8 Zones of protection.
207
208
Handbook of Electrical Installation Practice
angle of any installed lightning protection conductors up to the height of 20 m would
be similar to the structures in Fig. 9.6. For tall structures above 20 m in height (Fig.
9.8), BS 6651 recommends the use of the rolling sphere for determining the areas
where lightning protection may be advisable.
Lightning protection design
There are available proprietary devices of air terminations where claims are made
that they ionise the air, which in thunderstorm conditions could initiate the upward
streamer and, in effect, attract the downward leader, hence determining the point
of strike.
The foreword of BS 6651 carefully words strict adherence to the geometry of conventional lightning protection systems throughout its pages – to the total exclusion
of any other device or system which claims to provide enhanced protection. This is
based on research that has been unable to substantiate the enhanced performance
these devices or systems are claimed to give.
This view is supported by the draft IEC and CENELEC documents on lightning
protection currently being compiled.
If it has been established that a structure requires lightning protection, certain
general design features need to be considered.
Could, for instance, any of the metallic components in or on the structure be incorporated into the lightning protection scheme? Could the metal in and on the roof
be used? Should window cleaning rails, window frames and handrails surrounding
the structure be incorporated in the protection network? The reinforcing bars or
the steel frame of a structure may well provide a natural conductive path within the
lightning protection system.
If metallic components in a building are not used, then the structure will require
externally fitted conductors. A lightning protection system can incorporate all
natural conductors, all externally fitted conductors, or a combination of both. BS
6651 does not, however, recommend the routing of conductors inside the structure.
The principal components of a lightning protection system comprise the following:
(1) An air termination network to collect the lightning discharge
(2) A down conductor, or series of down conductors, which provide a safe path from
the air termination network to the earth
(3) An earth termination, which dissipates the charge into the earth
(4) Bonds and clamps, which connect all of the three segments together and prevent
side flashing.
Air termination networks
The simplest form of air termination is the air rod, or terminal projecting above the
structure, invented by Benjamin Franklin. It is intended to be a point from which
an upward streamer can start, and should be sufficiently robust to intercept the full
stroke current. It is most applicable to a tall structure of small cross-section, such
as a church spire, but a number of rods, correctly spaced and interconnected, protects a greater cross-section.
Lightning Protection
209
Fig. 9.9 Lightning protection scheme to BS 6651 using the reinforced concrete within the
structure for down conductors.
The air rod is not essential to the design of air terminations, and horizontal conductors of copper or aluminium, forming a ring round the top of a structure or developed
as a grid network on larger areas, are equally effective and reflect current practice.
As stated earlier it is now accepted that lightning can strike the upper part of tall
structures. BS 6651 introduces the concept of air termination networks on all sides of
tall buildings (i.e. vertical air termination networks). No part of the roof within the
air termination network should be more than 5 m from a conductor. For large flat
roofs, this will be achieved typically by a network mesh of 10 m ¥ 20 m. For high risk
structures, e.g. explosives factories, the air termination mesh is reduced to 5 m ¥ 10 m.
If a building’s metal reinforcing bars are to be used as down conductors, these
should be connected to the air termination network as shown in Fig. 9.9.
BS 6651 advises the use of a rolling sphere to determine zones of protection. To
minimise the likelihood of a lightning strike damaging the side of a building, it is
suggested that the rolling sphere method should be applied to identify those areas
where an extension of the air termination network should be considered. Where the
sphere touches the structure determines the extent of the air termination network.
BS 6651 advocates the use of a 20 m radius sphere for all high risk structure
categories and 60 m for all other types of structure.
Where structures vary in height and have more than one roof termination
network, the lower roof network should not only be joined to its down conductors,
but also joined to the down conductors of the taller portions of the structure. This
will ensure that a lightning strike to a lower portion of the structure will not lead
to side-flashing to other ‘remote’ down conductors and will provide a multi down
conductor path for the lightning current to disperse.
210
Handbook of Electrical Installation Practice
Fig. 9.10 Re-entrant loops.
Down conductors
The function of a down conductor is to provide a low impedance path from the air
termination network to the earth termination network, to allow the lightning
current to be safely conducted to earth.
BS 6651 advocates the use of various types of down conductors. A combination
of strip and rod conductors, reinforcing bars, structural steel stanchions, etc. can be
used as all or part of the down conductor system – providing they are appropriately
connected to the air and earth termination networks and are known to offer good
electrical conductivity.
External down conductors are usually copper or aluminium in tape or circular
solid form.
They should, where possible, take the most direct route from the air termination
network to the earth termination network. Ideally they should be symmetrically
installed around the outside walls of the structure starting from the corners. Routing
to avoid side-flashing should always be given particular attention in designing any
installation.
Down conductors should be positioned no more than 20 m apart around the
perimeter at roof or ground level, whichever is the greater. If the structure is over
20 m in height, then the spacing is reduced to every 10 m or part thereof.
Sharp bends in down conductors at the edge of the roofs are unavoidable and are
permitted in BS 6651; however, re-entrant loops in a conductor can produce high
inductive voltage drops which could lead to the lightning discharge jumping across
the side of the loop. To minimise this problem, BS 6651 recommends that the length
of the conductor forming the loop should not exceed eight times the width of the
open side of the loop (Fig. 9.10).
For persons standing under a building with cantilevered upper floors, the risk is
unacceptable if the height h of the overhang is less than 3 m. For overhangs equal
to or greater than 3 m the width w of the overhang should be less than or equal (in
metres) to that given by
Lightning Protection
211
w £ 15(0.9 h - 2.5)
if down conductors are to be routed externally (Fig. 9.10(d)).
Down conductors must never be routed down lift shafts. If an external route is not
available, an internal continuous, non-conducting, non-flammable duct may be used.
Each external down conductor must incorporate a test clamp installed approximately 3 m from the ground. This enables the continuity of the system to be checked
as well as isolating each local earth network for testing purposes.The section of down
conductor from the ground to the test clamp should have a non-metallic guard to
protect from unauthorised interference. To minimise surface voltage gradients the
down conductor should ideally be insulated for the first metre of entry into the soil.
Earth termination networks
Each down conductor should have its own local earth electrode. Copper conductor
should be used as the connection from the test clamp to the earth electrode. Copperbonded steel-cored rods are by far the most popular form of earth electrode. These
may be driven to considerable depths. Alternatively shallower driven rods interconnected by copper conductor can be used.
Aluminium and copper, the two metals most commonly used in lightning protection systems, are not compatible, so great care must be taken when both are used
in a system – particularly where they come into contact with each other.
If aluminium is selected as the material for air termination networks and down
conductors, it has to be converted to copper at or around the test clamp. This is
because both BS 6651 and the Earthing Code BS 7430 do not permit aluminium to
be buried underground due to the likelihood of corrosion.
A simple and effective means of joining the aluminium and copper conductors is
with a friction-welded bi-metal clamp. This termination, if used in conjunction with
an inhibitor grease, minimises the effect of corrosion.
The contact surfaces of dissimilar metals should be kept completely dry and protected against the ingress of moisture, otherwise corrosion will occur. A particularly
effective means of excluding moisture is to use inhibitor pastes, bitumastic paint, or
approved protective wrappings.
As aluminium is prone to corrosion when in contact with Portland cement and
mortar mixes, aluminium conductors need to be fixed away from the offending
surface with an appropriate fixing.
There are two stages in testing an earth network for satisfactory resistance:
(1) With the test link removed from the down conductor and without any bonding
to other services, etc., the earth resistance of each individual earth electrode
should be measured. The resistance, in ohms, should not exceed 10 times the
number of down conductors on the structure. For example, if there are 15 down
conductors equally spaced around a building, then the resistance of each electrode with the test link removed should not exceed 10 ¥ 15 = 150 W.
(2) With the test links replaced, the resistance to earth of the complete lightning
protection system is measured at any point on the system. The reading from this
test should not exceed 10 W. This is still without any bonding to other services.
212
Handbook of Electrical Installation Practice
BS 6651 provides a guide to the minimum dimensional requirements of various electrode systems; for example, where earth rods are chosen, the minimum combined
rod length to complete an earth electrode system should be 9 m – therefore a small
structure with only two down conductors would have a minimum requirement of
4.5 m for each electrode. Each local earth rod electrode should be a minimum length
of 1.5 m.
On rock foundations with shallow earth covering, it may be necessary to drill vertical holes, usually 75–100 mm in diameter, and using earth rod electrodes, fill the drilled
hole with a suitable soil conditioning agent such as bentonite or conductive concrete.
For further recommendations on earthing see BS 7430: 1998 Earthing, and
Chapter 7 in this book.
There is an increasing trend, encouraged by BS 6651, to use the foundation
reinforcement of a structure as the earth electrode system whenever possible. The
depths of the foundations usually ensure that there is more than sufficient electrodes
available to satisfy the test criteria. Care must be taken to ensure that there is electrical continuity between the reinforcement foundations and the down conductors.
Purpose-made mechanical clamps are available to suit this application.
Bonds
All metalwork on or around a structure must be bonded to the lightning protection
system if side-flashing is to be avoided. When a lightning protection system is struck,
its electrical potential with respect to earth is significantly raised, and unless suitable precautions are taken, the discharge may seek alternative paths to earth by
side-flashing to other metalwork in or on the structure.
Typically, water pipes, gas pipes, metal sheaths and electrical installations which
are in contact with earth, remain at earth potential during a lightning discharge.
Even metal parts that are not in contact with earth will see a potential difference
between them and the lightning protection system during a discharge, even if
this potential is smaller in magnitude to the metal parts in direct contact with
earth.
All exposed metalwork should be bonded into the lightning protection installation (Fig. 9.11).
There are two ways of preventing side-flashing: to isolate nearby metal from the
lightning protection system, or if that is not possible, to connect the metalwork to
the lightning protection system with an appropriate bond.
To determine whether the distance between the suspect metalwork and the lightning protecting system is large enough for the metalwork to be considered ‘isolated’
or close enough to be ‘bonded’, BS 6651 provides a mathematical means of determining the minimum isolation distance for a given set of parameters.
Internal bonds need only be half the cross-sectional area of external bonds
as they are, at most, only likely to carry a proportion of the total lightning
current.
The general view held by both the technical committee of BS 6651 and BS 7430
is the need to bond the lightning protection scheme to all metal services entering
or leaving a structure. This connection, which includes the electrical power earth,
should normally be made at the main earth terminal point. Permission should be
sought from the appropriate authority before such a connection is made.
Lightning Protection
213
Fig. 9.11 Bonding to prevent side-flashing.
Material specification
The correct choice of material for a lightning protection system and the installation
method adopted should ensure a satisfactory life span of at least 30 years.
To ensure an effective system and a satisfactory long-term performance, all
fittings need to be mechanically robust and provide good corrosion resistance
qualities in widely differing environments.
In addition, the system should provide a low electrical resistance path to earth
and have the ability to carry high currents repeatedly over the lifetime of the
installation.
Table 9.6 recommends the materials to be used for the manufacture of lightning
protection components and Table 9.7 recommends the minimum dimensions of
component parts. Both tables are taken from BS 6651: 1999.
214
Handbook of Electrical Installation Practice
Table 9.6 Recommended materials for the manufacture of lightning protection
components.
Materials and processes
BS No.
Grade or type
Ingots for cast components
Leaded gunmetal
Aluminium silicon bronze
Aluminium alloy
Cast iron
Malleable iron
Aluminium alloy
BS 1400
BS 1400
BS 1490
BS 1452
BS 6681
BS 1490
LG1, LG2
AB1, AB3
LM6M
220, 260
–
LM25
Forgings and stampings (hot or
cold formed)
Copper
Naval brass
Aluminium
Steel
BS 2872
BS 2872
BS 1474
BS 970: Part 1
C101, C102, C103, C106
CZ112
6082TF
All grades
Pressings and fabrication (from
strip, coil, foil and sheet)
Annealed copper
BS 2879
Aluminium
Naval brass
Stainless steel
BS 1474
BS 2870
BS 1449: Part 2
Steel (for galvanising)
BS 1449: Part 1
C101, C102, C103,
C104, C106
6082TF
CZ112
316S12,
325S21
–
BS 2874, BS 2871
BS 2874
BS 2874
BS 2871: Part 3
BS 1474
BS 2874
BS 970
BS 970
BS 970: Part 1
BS 970: Part 1
C101, C102, C103, C106
CS101
PB102-M
CA102
6082TF
CZ112
All grades
All grades
325S21
316S12
BS 2874
BS 2874
BS 2874
BS 2873
PB102-M
CZ112, CZ132
CS101
C101
Bars, rods and tubes (for
machined components and fittings)
Hard drawn copper or annealed
Copper silicon
Phosphor bronze
Aluminium bronze
Aluminium
Naval brass
Steel (general use)
Steel (for galvanising)
Stainless steel (general use)
Stainless steel (austenitic)
Nuts, bolts, washers, screws and
rivet fixings for use on copper
Phosphor bronze
Naval brass
Copper silicon
Copper rivets
215
Lightning Protection
Table 9.6 (Cont)
Materials and processes
Nuts, bolts, washers, screws
and rivet fixings for use on
aluminium
Aluminium alloy
Stainless steel
Galvanized steel, galvanised to
BS 729
Solid rounds, flats and
stranded conductors
Copper
Annealed copper
Hard drawn copper
Copper (stranded)
Copper (flexible)
Hard drawn copper strand and
copper cadmium
Aluminium
Aluminium strip/rod
Aluminium strip/rod
Aluminium
Aluminium (steel reinforced)
Aluminium alloy
Aluminium
Steel
Galvanised steel
Galvanised strip (see note 1)
BS No.
Grade or type
BS 1473
BS 3111-2
BS 3111-1
6082-T6
BS 1432
BS 1433
BS 6360
BS 6360
C101, C102, C103
C101, C102, C103
Insulated
–
BS 7884 or BS 2873
C108
BS 2897
BS 2898
BS 3988
BS 215: Part 2
BS 2898
BS 215: Part 1
1350
1350, 6101A
Insulated
–
–
–
–
–
–
BS 3242, BS 215-1
BS 1449: Part 1; BS 302-2
Notes
(1) The recommended finish is galvanised in accordance with BS 729, which has to be done after
manufacture or fabrication.
(2) Stainless steel in contact with aluminium or aluminium alloys is likely to cause additional
corrosion to the latter materials (see PD 6484). In these cases, it is important to take protective
measures, e.g. the use of inhibitors.
(3) Copper alloys, other than these listed above, are permissible as long as they have a minimum
copper content of 75% and similar tensile properties.
Although the tables permit the use of galvanised conductors, their popularity,
particularly in the UK, is very restricted. It is more common in Europe, particularly
Germany.
As mentioned previously, copper and aluminium in solid circular or tape form are
the preferred types of conductor. Their particular choice is usually governed by
factors such as overall comparative cost, the corrosive nature of the environment,
and a requirement to blend in with the colour of the structure. Mainly to assist
with the latter requirement, there are PVC-covered conductors available in various
216
Handbook of Electrical Installation Practice
Table 9.7 Minimum dimensions of component parts.
Component
Air terminations:
aluminium, copper and galvanised steel strip
aluminium, aluminium alloy, copper,
phosphor bronze and galvanised steel rods
Suspended conductors:
stranded aluminium
stranded copper
stranded aluminium (steel reinforced)
stranded galvanised steel
Down conductors:
aluminium, copper and galvanised steel strip
aluminium, aluminium alloy, copper and
galvanised steel rods
Dimensions
(mm)
Area
(mm2)
20 ¥ 2.5
50.0
8.0 dia.
50.0
7/3.0
19/1.8
7/3.0
7/3.0
50.0
50.0
50.0
50.0
20 ¥ 2.5
50.0
8.0 dia.
50.0
14.0 dia.
20 ¥ 2.5
8.0 dia.
153.0
50.0
50.0
8.0 dia.
50.0
Earth terminations:
austenitic iron
copper and galvanised steel strip
copper and galvanised steel rods
hard drawn copper rods for direct
driving into soft ground
hard drawn or annealed copper
rods or solid wires for indirect
driving or laying in ground
rods for hard ground
copper-clad or galvanised steel rods (see
notes to table) for harder ground
8.0 dia.
12.0 dia.
50.0
113.0
14.0 dia.
153.0
Fixed connections (bonds) in aluminium,
aluminium alloy, copper and galvanised steel:
external strip
external rods
internal strip
internal rods
20 ¥ 2.5
8.0 dia.
20 ¥ 1.5
6.5 dia.
50.0
50.0
30.0
33.0
Flexible or laminated connections (bonds):
external, aluminium
external, annealed copper
internal, aluminium
internal, annealed copper
20 ¥ 2.5
20 ¥ 2.5
20 ¥ 1.5
20 ¥ 1.5
50.0
50.0
30.0
30.0
Lightning Protection
217
Notes to Table 9.7
(1) For copper-clad steel rods, the core should be of low carbon steel with a tensile strength of
approximately 600 N/mm2. The cladding should be of 99.9% pure electrolytic copper molecularly
bonded to the steel core. The radial thickness of the copper should be not less than 0.25 mm.
(2) Couplings for copper-clad steel rods should be made from copper silicon alloy or aluminium
bronze alloy with a minimum copper content of 75%.
(3) The use of internal phosphor bronze dowels may give a lower resistance than the external
couplings of diameter greater than the rod.
(4) For galvanised steel rods, steel specified in BS 5970–1 should be used, the threads being cut before
hot-dip galvanising to BS 729.
(5) Stranded conductors are not normally used for down conductors or earths.
(6) Greater dimensions are required for the following:
(a) structures exceeding 20 m in height;
(b) special classes of structure;
(c) mechanical or corrosive reasons.
colours. These can be used, and are equally effective as the bare conductor, as air
termination networks and as down conductors.
Lightning protection design
In order to provide a lightning protection scheme for a structure, certain parameters need to be available to the designer. These can be summarised as:
(1) Drawings of the structure requiring protection, showing the roof plan and at
least two elevations. These drawings should be clear, precise and have the scale
shown.
(2) The materials used in the construction of the structure should be stated, along
with information on the type of fixings permissible (e.g. can the roof be drilled
to take screw plugs?).
(3) For what purpose the structure is being used (its use will determine the risk
category of the structure).
(4) The proximity of other structures, trees and the general locality.
(5) Information regarding any unusual features, such as aerial masts on the roof of
buildings, which may not be shown on the drawings.
(6) At what stage of construction is the structure (i.e. complete, partly built, etc.)?
(7) Notification of code that the scheme is to be designed to, e.g. BS 6651: 1999.
(8) Is there any soil resistivity data available?
Future standards
The national standard for lightning protection of structures (BS 6651) will ultimately
be replaced by a series of CENELEC (European) standards. These in turn will
have been influenced to a large degree by the IEC (world) standards. These IEC
standards, albeit at the time of writing in draft form, are in a mature stage of finalisation. Due to the long bureaucratic process of adopting an IEC standard, it is
anticipated that the main standards will be published late 2004, early 2005.
218
Handbook of Electrical Installation Practice
What is evident today though is the far more comprehensive nature of these standards, reflecting the more recent understanding and research on the phenomenon
that is lightning. One of the main changes in the new standards is the focus on the
management of risk. A complete section will be devoted to this topic.
The new and agreed format for the future IEC standards on lightning protection
will be:
IEC 62305-1 General principles
IEC 62305-2 Management of risk
IEC 62305-3 Physical damages to structures and life hazard
IEC 62305-4 Electrical and electronic systems within structures
IEC 62305-5 Services
It is anticipated that the CENELEC standards will follow a very similar format.
INSTALLATION OF LIGHTNING PROTECTION
On new buildings and structures it should be possible for the installation of the
lightning protection to progress with the building work. This can give cost reduction in the provision of scaffolding and in eliminating the need to break through
masonry or concrete when all the civil work is complete.
Down conductors should follow the most direct path possible between the air
termination and the earth termination. Right-angle bends when necessary are permissible, but deep re-entrant loops should be avoided.
The magnetic forces induced by a lightning strike on a conductor try to straighten a
right-angled bend. It is impossible not to have such bends in a system, but where
possible they should be avoided.The radius of such bends should not be less than 200
mm and should be firmly anchored at either side. A well-formed bend only stuck down
by felt pads onto a bitumen roof would probably not hold in the event of a strike.
The earth rod electrode should be installed close to its down conductor wherever
possible. This offers a direct path for the lightning discharge in the event of a strike.
Modern buildings have roofs and wall structures constructed of metal cladding.
Provided they are of adequate thickness (guidance is given in BS 6651) and are
electrically continuous, then they can be used as, or form part of, the lightning protection system.
Supporting stanchions of steel-framed buildings can be utilised as the down conductors.They should be adequately earthed and correctly bonded to the roof network.
This type of building normally contains many supporting stanchions in parallel, each
of which has a very large cross-sectional area. The resulting impedance seen by the
lightning strike is, therefore, low and the danger of side-flashing is greatly reduced.
When a structure is being erected, all large and prominent masses of steelwork
should be effectively connected to earth. This applies to all metal items including
steel framework, scaffolding and on-site cranes.
Due to its unique nature, the installation of lightning protection schemes should
preferably by carried out by a company specialising in this branch of electrical
engineering.
Lightning Protection
219
There is a federation within the industry – The National Federation of Master
Steeplejack and Lightning Conductor Engineers (NFMSLCE) – that offers this
service.
INSPECTION AND TESTING OF A SYSTEM
All parts of a lightning protection system should be visually inspected on a regular
basis. This is particularly relevant after alterations or extensions to the structure, to
ensure that the system still complies with the recommendations of BS 6651. Particular attention should be paid to the mechanical condition of all conductors and
fittings.
Each local earth electrode should be tested in accordance with BS 7430: 1998 (see
Chapter 7 for more details) to ensure that it still complies with the requirements
of BS 6651. Tests should be repeated at fixed intervals, preferably not more than
12 months. Ideally, testing every 11 months (or 13 months) would vary the season
in which tests are made, which would give a more accurate reflection of the earth
electrode resistance.
PART 2. PROTECTING ELECTRONIC SYSTEMS FROM LIGHTNING
As well as posing a threat to the building itself, lightning also threatens damage
to the building’s electronic contents. Lightning activity, anything up to a kilometre
away, can cause transient overvoltages capable of destroying electronic equipment.
To counter this threat, additional and complementary protection measures are
required. A number of measures can be taken at the project design stage to
mitigate the threat, though these will need to be supported by suitable transient
overvoltage (or ‘surge’) protectors.
Transient overvoltages caused by lightning
A transient overvoltage is a very short duration increase in voltage measured
between two or more conductors. Although only lasting from microseconds to a few
milliseconds in length, this increase in voltage may be of several thousand volts.
Lightning can cause transient overvoltages through direct strikes to incoming
electrical services or, most commonly, through ‘indirect’ strikes which are coupled
into electrical services through resistive, inductive and capacitive effects.
Direct strikes to h.v. power cables
Strikes to high voltage (h.v.) overhead power lines are quite common. It is often
thought that the high voltage to low voltage transformer action eliminates transient
overvoltages. This is not so. Although transformers protect against transient overvoltages between line and earth, line to line transients pass through unattenuated.
When h.v. lines are struck by lightning they flashover to earth. One line will
flashover before the others, converting a line to earth transient into one between
line and line – these will easily pass through the transformer.
Also, capacitance between the transformer’s windings provides transients between
any combination of conductors with a high frequency path through the transformer.
220
Handbook of Electrical Installation Practice
This could have the effect of increasing the size of existing line to line transients,as well
as providing a path through the transformer for line to earth transients.
Direct strikes to l.v. power or telephone lines
When lightning hits low voltage (l.v.) overhead power or telephone lines, most of
the current travels to earth as a result of line flashover to ground. A relatively small
(but devastating) portion of the lightning current is transmitted along the line to
electronic equipment.
Resistive coupling
This is the most common cause of transient overvoltages and it will affect both
underground and overhead lines. Resistively coupled transients occur when a lightning strike raises the electrical potential of one or more of a group of electrically
interconnected buildings (or structures).
Common examples of electrical interconnections are:
•
•
•
•
•
•
•
Power feeds from substation to building
Building to building power feeds
Power supplies from the building to external lighting, CCTV or security equipment
Telephone lines from the exchange to the building
Between building telephone lines
Between building LAN’s or data communication lines
Signal or power lines from a building to external or field based sensors.
Figure 9.12 shows two buildings. Each contains electronic equipment, which is
connected to earth through its mains power supply. A data communication line
connects the two pieces of equipment and hence the two separate earths.
A nearby lightning strike will inject a massive current into the ground.The current
flows away from the strike point – preferentially through the path of least resistance. The earth electrode, electrical cables and the circuitry of the electronic equipment (once damaged) are all better conductors than soil. As the current attempts
to flow, devastating transient overvoltages can be recorded across the sensitive
components of the equipment.
Figure 9.13 provides an example of how resistively coupled transient overvoltages can occur on a mains power supply. Resistively coupled transients can occur
when separately earthed structures are only metres apart. Resistive coupling will
affect both underground and overhead cables.
Inductive coupling
This is a magnetic field transformer effect between lightning and cables.
A lightning discharge is an enormous current flow and whenever a current flows,
an electromagnetic field is created around it. If power or data cabling passes through
this magnetic field, then a voltage will be picked up by, or induced on to it. This frequently occurs when lightning discharges close to overhead power or telephone
lines (Fig. 9.14). Much the same thing happens when a building’s lightning protection scheme is struck. The lightning current flows to earth through the building’s
Lightning Protection
221
Fig. 9.12 Resistive coupling through a data line.
Fig. 9.13 Resistive coupling through a mains power supply.
down conductors. The resulting magnetic field may well encroach upon cabling
within the building, inducing transient overvoltages on to it.
Capacitive coupling
Where long lines are well isolated from earth (e.g. via transformers or optoisolators) they can be pulled up to high voltages by capacitance between them and
222
Handbook of Electrical Installation Practice
Fig. 9.14 Inductive coupling.
the charged thunder clouds. If the voltage on the line rises beyond the breakdown strength of the devices at each end (e.g. the opto-isolators), they will be
damaged.
Size of transient overvoltages caused by lightning
The American Institute of Electrical and Electronic Engineers (IEEE) has collated
extensive research into transient overvoltages caused by lightning. The American
Standard IEEE C62.41 states:
•
•
A typical worst case of 6000 V for transient overvoltages within a building’s
power distribution system – its sparkover clearance ratings will ensure that the
transient does not generally exceed 6000 V
On mains power supplies within a building, secondary lightning currents are
unlikely to be more than 3000 A and are certainly no greater than 10 000 A.
Worst case transient overvoltages for data communication, signal and telephone
lines are less easy to quantify with certainty. However, we seem to be dealing with
a worst case of 5000 V, or so, and hundreds of amps (based on the test recommendations of the ITU).
Characteristics of lightning
Lightning has a tendency preferentially to strike taller structures and objects. Strikes
to ground are, however, quite common where there is a distance between structures
of more than twice their individual height.
223
Lightning Protection
10.3
7.3
10.3
6.2
3.1
5.4
6.2
2.3
6.2
5.4
3.1
6.2
10.3
7.5
10.3
Fig. 9.15 Distribution (%) of lightning current in a 15 stanchion structure.
For lightning protection purposes an all conducting building, with metal cladding
and roof, is an ideal structure. It effectively provides electronic equipment within
it with a ‘screened room’ environment. Many steel framed or reinforced concrete
buildings with metal cladding will approximate to this ideal. If lightning strikes the
building, a ‘sheet’ of current will flow all over the surface and down to earth,
provided that the cladding and roofing is correctly bonded together. Any small
differences in resistance will have little effect on current flow – flow paths are dictated by inductance and not resistance, owing to the fast impulsive nature of the
lightning return stroke and restrikes.
Current flows in steel framed or reinforced concrete structures show a similar
preference towards external conductors. Figure 9.15 shows that even when lightning
strikes the centre of a building’s roof, the majority of the current will flow down
external conductors rather than the nearer internal conductors. The current flow
through the three internal stanchions is relatively small, creating small magnetic
fields within the building.
Thus, buildings with large numbers of down conductors around the edge of the
building will have greatly reduced magnetic fields inside the building, minimising
the risk of transient interference to electronic equipment from the building’s lightning protection system, provided, of course, that power and data cables are routed
away from the down conductors.
Problems that transient overvoltages cause
The effects that transient overvoltages have on unprotected equipment depend
on the size of the transient and the sensitivity of equipment. Transient overvoltages
224
Handbook of Electrical Installation Practice
manifest themselves as disruption, degradation, damage and downtime. Generally,
the larger the transient the worse are its consequences.
Disruption
Although no physical damage is caused, the logic or analogue levels of the systems
are upset, causing data loss, data and software corruption, unexplained computer
crashes, lock-ups, and the spurious tripping of residual current devices (RCDs). The
system can be reset (often just by switching off and on) and will then function
normally. Much of this nuisance may go unreported.
Degradation
Long-term exposure to lower level transient overvoltages will, unknown to the user,
degrade electronic components and circuitry, reducing equipment lifetime and
increasing the likelihood of failures.
Damage
Large transient overvoltges can cause damage to components, circuit boards
and I/O cards. Severe transient overvoltages can manifest themselves through
burnt-out circuit boards, destroying equipment. Ordinarily, damage is less spectacular.
Downtime
Unnecessary disruption, component degradation and damage all result in equipment and systems downtime, which means:
•
•
•
•
•
•
Staff unable to work
Staff overtime
Senior managers and technical specialists unnecessarily tied-up problem solving
Lost productivity
Delays to customers
Lost business.
Equipment sensitivity
There is no absolute level of vulnerability which can be applied to all pieces of
electronic equipment. Much depends on the sensitivity of differing components
and circuit designs. Susceptibility levels will therefore vary with different equipment
and manufacturers. At present the transient susceptibility of particular pieces of
equipment can often only be guessed at.
As a general rule ‘few solid state devices can tolerate much more than twice their
normal rating’ (IEEE 1100–1999, The Emerald Book). A single phase 230 V power
supply has a maximum normal rating of 230 V ¥ ÷2 ¥ 1.1 (10% supply tolerance).
This gives us a maximum normal rating of 358 V and hence susceptibility level of
700 V or so.
This is, of course, a rule of thumb only, and should be disregarded where equipment has a known susceptibility level. Ethernet systems, although having a signalling
voltage of a few volts, have a susceptibility level of many times this. (ECMA 97
Lightning Protection
225
details a minimum susceptibility level of 400 V for Ethernet communication
ports.)
Is protection required?
This depends on the importance of the electronic systems at the site in question.
Consider:
•
•
•
•
•
•
•
The cost of replacing damaged equipment
The cost of repair work, especially for remote or unmanned installations
The cost of lost or destroyed data
The financial implications of extended stoppages – sales lost to competitors, lost
production, deterioration or spoilage of work in progress
Potential health and safety hazards caused by plant instability, after loss of control
The need to safeguard the operation of fire alarms, security systems, building
management systems and other essential services
The need to minimise fire risks and electric shock hazards.
Thus, the decision whether and what to protect will be heavily influenced by the
associated costs of repair and the criticality of system operation. However, where
uncertainty exists a risk assessment may prove helpful. BS 6651: 1999 outlines the
basis on which the risk of lightning disruption to electronic equipment can be
calculated. It is important to note that this risk assessment differs markedly from
the risk assessment for buildings and structures contained in BS 6651 and discussed
near the beginning of this chapter.
The threat to electronic equipment from the secondary effects of lightning
depends on the probable number of lightning strikes to the area of influence, and
the vulnerability of the system configuration.
Probable number of lightning strikes
The probable number of lightning strikes is derived by multiplying ‘lightning flash
density’ (the probable number of lightning strikes per square kilometre per year)
by the effective collection area. It is given by the formula:
P = Ae ¥ N g ¥ 10 -6
where
Ae = total effective collection area (m2)
Ng = lightning flash density per km2 per year
10-6 = a conversion factor to take account of the fact that Ng and Ae are in
different units of area – multiplying square metre values (m2) by
10-6 (1/1 000 000) gives square kilometres (km2).
Lightning flash density (Ng)
Details of lightning flash densities are contained in a number of national standards.
Figure 9.16 shows a map of lightning flash density for the UK, derived from BS 6651:
1999.
226
Handbook of Electrical Installation Practice
NOTE 1 This lightning density map was compiled by E.A.Technology Ltd from data accumulated over 10 years.
NOTE 2 A linear interpolation should be used to determine the value of the lighning flash density, Ng, for a location
between two contour lines.
Fig. 9.16 Lightning flash density to ground (Ng) per square kilometre per year for the British
Isles.
227
Lightning Protection
Effective collection area (Ae)
The effective collection area Ae (in m2) is given by:
Ae = AS + CSG + C AS + C MP + CDL
where
As = the plan area of the structure (m2)
CSG = the collection area of the surrounding ground (m2)
CAS = the collection area of adjacent associated structures and their
surrounding ground (m2)
CMP = the collection area of incoming/outgoing mains power supplies (m2)
CDL = the collection area of data lines leaving the earth reference of the
building (m2).
Thus the overall collection area has a number of constituent elements, which we will
consider separately.
Plan area of the structure (AS). This is often a simple length by width calculation,
requiring little further explanation. In practice this is often calculated together with
the collection area of the surrounding ground (CSG).
Collection area of the surrounding ground (CSG). Lightning strikes to earth or
structures cause large local increases in earth potential. The effect of a nearby
ground strike on a building’s earth potential will diminish the further this strike is
from the building. Thus, beyond a certain distance a ground strike will not significantly increase the building’s earth potential. This is the collection distance D, measured in metres.
The distance D should be taken to be numerically equal to the soil resistivity
value – up to a maximum value of D = 500 m for a soil resistivity of 500 W m or more.
Where the soil resistivity is not known, a typical 100 W m resistivity soil should be
assumed giving D = 100 m. The collection area of the surrounding ground is an area
extending D m all around the building. Figure 9.17 shows this area for a rectangular building. This area is therefore calculated as follows:
CSG = 2 (a ¥ D) + 2 (b ¥ D) + pD 2
D
D
b
a
Fig. 9.17 The collection area of the surrounding ground for a rectangular building.
228
Handbook of Electrical Installation Practice
Note, the four quarter circle areas have been combined to give a circular area which
can be calculated using pr 2 where the radius r is equal to D. If the structures height
h exceeds D, the collection distance is assumed to be h. Where a complex shaped
building is being assessed, approximations and rough graphical methods will allow
the area to be calculated with sufficient accuracy.
Collection area of adjacent associated structures and their surrounding ground (CAS).
Where there is a direct or indirect electrical connection to an adjacent structure,
the collection area of this structure should be taken into account. Typical examples
are lighting towers (supplied from the main building), radio transmission
towers, and other buildings with computer control and instrumentation equipment.
Structures within a distance of 2D from the main building are considered to be
adjacent. As before, the collection area is calculated as the area of the structure plus
the area extending D m all around the building. Once again if the height of the
structure h exceeds D, the collection distance is assumed to be h. Any part of
this area which falls within the collection area of the main structure CSG should
be disregarded.
Collection area of incoming/outgoing mains power supplies (CMP). The effective
collection areas of all incoming and outgoing power supplies should be considered.
This includes outgoing supplies to neighbouring buildings, CCTV equipment,
lighting towers, remote equipment and the like. The effective collection areas of
different types of mains power supplies are shown in Table 9.8.
Collection area of data lines leaving the earth reference of the building (CDL). The
effective collection areas of all incoming and outgoing data lines should be considered. This includes data lines to other buildings, security equipment, remote data
logging equipment and the like. The effective collection areas of different types of
data lines are shown in Table 9.9.
Vulnerability of system configuration
The overall risk to electronic equipment from the secondary effects of lightning will
therefore depend on P (the probability of a strike) and the type of structure F, the
degree of isolation G, the type of terrain H. Weighting factors based on the relative
degrees of risk are assigned for F, G and H in Tables 9.10, 9.11 and 9.12,
respectively.
Calculation of overall risk
We described earlier how the threat to electronic equipment from the secondary
effects of lightning depends on the probable number of lightning strikes to the area
of influence, and the vulnerability of the system configuration. We have now seen
how the former can be calculated from P = Ae ¥ Ng ¥ 10-6 and how the latter is given
by the weighting factors F, G, and H.
Thus, the risk R of a lightning strike coupling into electrical or electronic systems
through incoming/outgoing mains power supplies or data lines is:
R=P ¥ F ¥G ¥ H
Lightning Protection
Table 9.8 Effective collection area of incoming/outgoing
power supplies.
Reproduced from BS 6651: 1999.
Note 1: D is the collection distance in metres (see above). Under
no circumstances should h be used in place of D.
Note 2: L is the length, in metres, of the power cable up to a
maximum value of 1000 m. If the value of L is unknown 1000 m
should be used.
Note 3: Where there is more than one power line/cable, they
should be considered separately and the collection areas
summated. Multicore cables are treated as a single cable and not
as individual circuits.
Table 9.9 Effective collection area of incoming/outgoing
data lines.
Reproduced from BS 6651: 1999.
Note 1: D is the collection distance in metres. Under no
circumstances should h be used in place of D.
Note 2: L is the length, in metres, of the data line up to a
maximum value of 1000 m. If the value of L is unknown 1000 m
should be used.
Note 3: Fibre-optic is a non-conductive means of data
transmission. It therefore has a collection area of zero.
Note 4: Where there is more than one data line/cable, they
should be considered separately and the collection areas
summated. Multicore cables are treated as a single cable and not
as individual circuits.
229
230
Handbook of Electrical Installation Practice
Table 9.10 Type of structure (Factor F ).
Reproduced from BS 6651: 1999.
Table 9.11 Degree of isolation (Factor G).
Reproduced from BS 6651: 1999
Table 9.12 Type of terrain (Factor H).
Reproduced from BS 6651: 1999.
Lightning Protection
231
Table 9.13 Classification of structures and contents.
Reproduced from BS 6651: 1999.
Note: the examples of structure usage are only intended to give greater
meaning to the descriptions of consequential effect – they should not be
seen as binding.
The average number of years between transient overvoltages caused by lightning is
given by 1/R. It should be noted that average values such as these are based on
periods of many years. This risk assessment R is intended only to guide the user’s
protection decision. Both the commercial impact of systems damage and downtime
and the health and safety implications should be considered (see earlier). Often
the decision to protect will be based on a simple comparison of the cost of damage
and downtime to computers and plant systems, with the cost of protection and
prevention.
Protector exposure levels
This risk assessment can also be used to indicate the type of protector required at
different types of installation. BS 6651 provides a four tier classification of installations based on the consequential effects of damage to the installations’ contents.
This is shown in Table 9.13. Combining together the risk R with the consequential
232
Handbook of Electrical Installation Practice
Table 9.14 Classification of exposure level.
Reproduced from BS 6651: 1999.
Note: Where the exposure level is negligible, protection is not normally necessary.
loss rating we can determine the exposure level for which transient overvoltage
protectors should be designed (see Table 9.14).
These exposure level categories are based on a lightning risk assessment only.
Where transients of another cause are likely to be present, you should consider
upgrading the protectors. Mains power supplies are susceptible to switching transients, also. Where the presence of switching transients is anticipated, a protector
from the next highest exposure level should be used (unless a high exposure level
protector is already required). Protector exposure levels are explained in greater
detail later.
Protection techniques and basic considerations
There are a number of techniques which can be used to minimise the lightning threat
to electronic systems. Like all security measures they should, wherever possible, be
viewed as cumulative and not as a list of alternatives. The use of transient overvoltage protectors is covered in detail below.
BS 6651: 1999 describes a number of other measures to minimise the severity of
transient overvoltages caused by lightning. These tend to be of greatest practical relevance for new installations. These measures are:
•
•
•
•
•
Extensions to the structural lightning protection system
Earthing and bonding
Equipment location
Cable routing and screening
Use of fibre-optic cables.
Extending structural lightning protection
We saw in Fig. 9.15 how lightning currents preferentially flow down external conductors. Thus, a building’s lightning protection is enhanced by having many down
conductors around the edge of the building. The greater the number of down conductors around the sides of the building, the smaller the magnetic fields inside the
Lightning Protection
233
Fig. 9.18 CCTV cameras located within the 45° zone of protection provided by an air
termination point (left) or flat roof-top conductor (right).
building, and the lower the likelihood of transient interference into electronic equipment. It follows from this that extra down conductors should be installed on buildings containing important installations of electronic equipment.
Many systems incorporate elements installed outside or on the building. Common
examples of external system components include:
•
•
•
•
•
Aerials or antennae
Measurement sensors
Parts of the air conditioning system
CCTV equipment
Roof mounted clocks.
Exposed equipment, such as this, is not only at risk from transient overvoltages caused by the secondary effects of lightning, but also from direct strikes. A
direct lightning strike must be prevented, if at all possible.This can be done by ensuring that external equipment is within a zone of protection and where necessary
bonded to the structural lightning protection. Figure 9.18 shows CCTV cameras
safely positioned within the 45° zone of protection provided by an air termination
point.
It may be necessary to include additional air termination points in the building’s
lightning protection scheme, in order to ensure that all exposed equipment is protected. For exposed parts of the air-conditioning system, it is possible to bond just
its metal casing on to the roof top lightning conductor grid. Where air termination
points cannot be used, for example with whip aerials, the object should be designed
to withstand a direct lightning strike or be expendable. Exposed wiring should be
installed in bonded metallic conduit or routed such that suitable screening is
provided by the structure itself. For steel lattice towers the internal corners of
234
Handbook of Electrical Installation Practice
Lightning protection
to main earth bond
Lightning conductor
Earth bar
Connecting clamp
Meter
Test joint
Lightning protection earth
termination network
Telephone
service
Electricity
cable
Water
Gas
Fig. 9.19 Bonding of incoming services.
the L-shaped support girders should be used. Cables attached to masts should be
routed within the mast (as opposed to on the outside) to prevent direct current
injection.
Earthing and bonding
Detailed guidance on earthing is beyond the scope of this chapter. Additional and
complementary guidance is given here to improve earthing, and to achieve an area
of equal potential, ensuring that electronic equipment is not exposed to differing
earth potentials and hence resistive transients.
All incoming services (water and gas pipes, power and data cables) should be
bonded to a single earth reference point. This equipotential bonding bar may be the
power earth, a metal plate, or an internal ring conductor/partial ring conductor
inside the outer walls. Whatever form it takes, this equipotential bonding bar should
be connected to the electrode(s) of the earthing system. All metal pipes, power and
data cables should, where possible, enter or leave the building at the same point, so
that extraneous metalwork and armouring can be bonded to the main earth terminal at this single point (Fig. 9.19). This will minimise lightning currents within the
building.
Lightning Protection
235
If power or data cables pass between adjacent buildings, the earthing systems
should be interconnected, creating a single earth reference for all equipment. A
large number of parallel connections, between the two building’s earths, are desirable – reducing the currents in each individual connection cable. This can be
achieved with the use of a meshed earthing system. Power and data cables between
adjacent buildings should also be enclosed in metal conduits, trunking, ducts or
similar. This should be bonded to both the meshed earthing system and also to the
common cable entry and exit point, at both ends.
Equipment location
Electronic equipment should not be located where it will be close to large current
flows and the threat of induced transient overvoltages.
(1) Equipment should not be located on the top floor of the building where it is
adjacent to the roof-top air terminations and conductor mesh of the building’s
lightning protection system.
(2) Similarly, equipment should not be located near to outside walls and especially corners of the building, where lightning currents will preferentially
flow.
(3) Equipment should not be located in buildings close to tall, lightning attractive structures, such as masts, towers or chimneys. These tend to have a single
route to ground, causing very large current flows and hence very large magnetic
fields.
The issue of equipment location can only be ignored if the building corresponds
to the screened room ideal (bonded metal clad roof and walls), described earlier.
Cable routing and screening
Power, data communication, signal and telephone cabling may also be at risk from
induced transient overvoltages within the building. Equipment cabling should avoid
possible lightning carrying conductors such as those on the roof and, within or on,
the building (see equipment location above). Large area loops between mains
power and data communication cabling are, as a result of inductive coupling, effective at capturing lightning energy, and should therefore be avoided. To minimise
loop areas, mains power supply cables and data communication, signal, or telephone
wiring should be run side by side, though segregated. The cables can be installed
either in adjacent ducts or separated from each other by a metal partition inside the
same duct.
For a screened room type building the routing and location of cabling is not as
critical; however, adoption of the above is good practice. For buildings made from
non-conducting materials the above practices are essential in order to minimise
damage to equipment or data corruption. Cable screening or shielding is another
useful technique which helps to minimise the pick-up and emission of electromagnetic radiation. Power cables can be shielded by metallic conduit or cable trays, while
data cables often incorporate a screening outer braid. The screen acts as a barrier
to electric and magnetic fields. Its effectiveness is determined by its material and
236
Handbook of Electrical Installation Practice
construction as well as by the frequency of the impinging electromagnetic wave. For
transient protection purposes the screen should be bonded to earth at both ends,
although there are instances, particularly in data comms, where single-end earthing
is preferred to help minimise earth loops.
Use of fibre-optic cable on building to building data links
Special care should be taken with the protection of data lines which:
•
•
Pass between separate buildings; or
Which travel between separate parts of the same building (i.e. not structurally
integral) and which are not bonded across. Examples include parts of a building
which are separated by settlement gaps, or new wings which are linked by brick
corridors.
Fibre-optic cable is the optimum method of protection for building to building data
links. This will completely isolate the electronic circuits of one building from the
other, preventing all sorts of EMC problems including transient overvoltages. The
use of fibre-optic cable for data transmission does not diminish the need for the protection of the mains power supply to equipment.
Many fibre-optic cables incorporate metal draw-wires or moisture barriers and
steel armouring. This can establish a conductive link between buildings, defeating the object of using a fibre-optic link. If this cannot be avoided the conductive draw-wire, moisture barrier or armouring should be bonded to the main
cable entry bonding bar as it enters each building, or stripped well back. No
further bonding should be made to the fibre-optic cables ‘metal’. Lightning protection for fibre cable is considered in greater detail by ITU IX K25. The cost of
fibre-optic cable may make it unattractive for low traffic data links and single data
lines.
Where conductive data lines, such as unshielded twisted pairs or coaxial cables,
are required, precautions should be taken to prevent transients from flowing along
the line, threatening equipment at each end:
•
•
Install transient overvoltage protectors/lightning barriers (see below)
Interconnect the earthing systems of the buildings.
The earthing systems of the buildings can be interconnected via cable armouring,
metal trunking, raceways or conduits. These should be bonded, at each end, to each
building’s earth system, thus providing an electrically continuous link. If many parallel data links exist between buildings a good interconnection of earths will be
achieved, producing very low induced voltages. Also, it is beneficial to install earth
cables linking each structure’s earth.
Certain types of coaxial and screened cable should only be bonded to earth once
(ECMA 97 details types of LAN for which this is the case). The use of transient
overvoltage protectors will provide additional bonding, while retaining the integrity
of the system’s screening.
Lightning Protection
237
Deployment of transient overvoltage protectors
Transient overvoltage protectors should be used to supplement and support the protection techniques outlined above. When deploying transient overvoltage protectors, the objective is always to install the transient protection between the source of
the threat and the equipment that is to be protected.
We saw earlier that transient overvoltages can be conducted into electronic equipment via:
•
•
Mains power supplies
Data communication, signal and telephone lines.
We must therefore look at protecting both power and data communication/signal/
telephone inputs.
Protecting mains power supplies against lightning
Both overhead and underground cables can be affected by lightning. Underground
cables, which provide a link between two different earth references, are subject to
resistively coupled transients. Overground or overhead cables are susceptible to
resistive, inductive and capacitive transients.
Mains power supplies entering the building should be protected, to control large
externally generated transients before they enter the building’s power distribution
system. A suitable protector should be installed on the main l.v. incomer or at the
main l.v. distribution board. Some buildings have more than one main incomer or
main distribution board – all should be protected. Mains power supplies leaving the
building may also need to be protected.
(1) Protection as the supply leaves the building will prevent transients from outside
being injected back into the building’s power distribution system – often there
will be a local distribution board or auxiliary services board feeding this external equipment, at which protection can be installed.
(2) Sensitive external or on-site equipment, such as CCTV cameras, should also be
protected locally – although the equipment will share the same power earth as
the main building, it is likely to be inadvertently connected to a local earth
(a pole-mounted camera may be earthed locally via its support mast) and hence
vulnerable to resistive transients.
Mains power supplies between buildings should be protected at both ends. Supplies
between buildings should be considered as an outgoing supply (from one building)
and an incoming supply (to the other building).
We saw earlier how transient overvoltages can be induced on to power lines
from the electromagnetic field caused by a large current, such as lightning. In a
similar fashion, when the building’s lightning protection system carries a current to
earth, it creates a magnetic field. If electronic equipment or its power supply is
located near to these current-carrying conductors, then an induced transient will
result.
238
Handbook of Electrical Installation Practice
In new building it may be possible to ensure that this risk is eradicated. However,
for most existing installations this particular source of transients is a very real threat.
It is therefore advisable to install protection locally to important pieces of equipment in order to control lightning induced transients inside the building.
Protecting uninterruptible power supplies (UPS)
An uninterruptible power supply (UPS) is essentially a large battery providing
several minutes of back-up power. Many UPSs incorporate a small filter, and on this
basis many UPS manufacturers have loosely claimed that their devices provide transient overvoltage protection. Some manufacturers have gone as far as to suggest
that their UPSs protect against transient overvoltages caused by lightning. However,
the type of filters used provide protection only against quite low level transients and
not against the larger transients which cause the disruption, degradation, damage
and downtime we are trying to avoid.
Where equipment is connected to a UPS, good lightning and transient protection
should still be used, first to protect the equipment against transient disturbances on
the power supply, while the UPS is on bypass. Secondly, the modern electronic UPS
is itself a sophisticated piece of electronic equipment and can be prone to the effects
of transient overvoltages – though more traditional motor-generator (or rotary)
designs are less prone to this problem. Thirdly, some UPSs have their neutral connected straight through from input to output, potentially allowing the unhindered
passage of neutral to earth transients. Finally, where the UPS is in an external
building separate from its load, its output, its input and the load will require
protection.
The protector should be installed at the local power distribution panel, feeding
the UPS. On large UPSs the protector can be installed within the UPS cabinet, on
the power incomer. Some larger UPSs are supplied with protectors built in and
therefore provide effective protection against transient overvoltages caused by
lightning.
Protecting data communication, signal and telephone lines
Inside the building, screened cables can offer protection against voltages induced
from current-carrying lightning conductors. Most data cables incorporate a metallic screen. Outside the building, data lines can be susceptible to inductively, capacitively or resistively coupled transients. Underground cabling, between separate
earth references, will be susceptible to resistively coupled transients. Overground or
overhead cables may be susceptible to resistive, capacitive and inductive transients.
Thus, as a general rule, transient protectors should be installed on all incoming and
outgoing data communication, signal and telephone lines. Spare cores and unutilised
cables should be connected to an electrical earth, at both ends.
Most sizeable businesses and organisations have their own telephone exchange
or private branch exchange (PBX). This is the link between the telephone
company’s incoming lines and the customers’ own internal extension lines. Just like
other communication lines, telephone lines which travel into the building or
between buildings should be protected. PBXs can be protected against transient
overvoltages with two tier (gas discharge tube plus semiconductor) protection. This
Lightning Protection
239
typically consists of semiconductor protection installed at board level and gas discharge tubes installed on the main distribution frame. Certainly this is hardly ever
done in the UK nor, we think, in most other parts of the world. If lines are correctly
protected this tends to be true of the incoming (PTO) telephone lines only and not
extension lines. These often travel from building to building and are therefore very
much at risk from lightning.
The use of gas discharge tubes alone does not provide adequate protection. The
PBX should be properly protected by devices with a suitably low let-through
voltage. The PBX is an excellent place to install protection because all incoming and
outgoing lines meet at this point.
Choosing and specifying transient overvoltage protectors
In selecting a transient overvoltage protector it is important that the device selected
survives, has a suitable transient control level, and is compatible with the system
it is protecting. It is vital that the protector chosen is capable of surviving the
worst case transients expected at its intended installation point. Also, as lightning is
a multiple pulse event, the protector should not fail after exposure to the first
transient.
The protector should be able to control transients to level below the susceptibility and vulnerability of the equipment to be protected; for example, if a computer’s
operation is unhindered by transients of up to 700 V, then the let-through voltage
or transient control level of the protector should be less than 700 V. Allowing a
suitable safety margin, the worst case let-through voltage of the protector should
be 600 V, or less. (Note, the connecting leads of a correctly installed protector will
cause an increase in the let-through voltage.) Also the protector should not impair
or interfere with the protected system’s normal operation – something which
communication systems and intrinsically safe circuits are particularly susceptible to.
Location categories
The protector’s ability to survive and to achieve a suitable ‘let-through’ voltage
clearly depends on the size of transient to which it will be subjected. This in turn
may depend on the protector’s location. The American Standard IEEE C62.41 and
subsequently BS 6651 outline three location categories.
As a mains-borne transient travels through a building, the amount of current it
can source grows smaller (owing to the impedance of mains cables and current division). This is based on the assumption that a typical mains transient caused by lightning has a 1.2/50 ms waveshape.
Location Category C is defined as either:
•
•
•
Outside the building, or
The supply side of the main, incoming, l.v. distribution board, i.e. the board bringing the power supply into the building from the electricity supply authority, l.v.
transformer or from another building, or
The load side of distribution boards providing an outgoing power supply to other
buildings or to on-site equipment.
240
Handbook of Electrical Installation Practice
Location Category B is defined as either:
•
•
•
•
On the power distribution system, downstream of Category C and upstream of
Category A, or
Within apparatus which is not fed from a wall socket, or
Sub-distribution boards located within a 20 m cable run of Category C, or
Plug-in equipment located within a 20 m cable run of Category C.
Location Category A is defined as either:
•
•
Sub-distribution boards located more than a 20 m cable run away from Category
C, or
Plug-in equipment located more than a 20 m cable run away from Category
C.
Transient overvoltages on data lines are not significantly attenuated by the cable
and so are always rated for Location Category C. Regardless of where they are
installed in the building, the worst case will be similar. This is based on a 10/700 ms
waveform transient.
Exposure levels
Transient overvoltage protectors are designed to protect against the probable worst
case transient overvoltage. In high transient exposure level area, very large transients (perhaps only occurring once in every few thousand events) can be anticipated over much shorter time-scales than in a low transient exposure level area.
Thus, the probable worst case transient will be much smaller in a low transient exposure level area, than in a high exposure area.
The transient exposure level can be derived from the risk assessment – see
earlier. However, if a risk assessment has not been done, it is probably wise to
assume a risk, R = 0.6. This can be combined with the consequential loss rating
(in Table 9.13) in order to derive the protector exposure level from Table 9.14.
Probable worst case mains transients for high, medium and low exposure levels
are tabulated in Table 9.15 for all location categories. All data line protectors fall
within Category C and probable worst case data line transients are tabulated in
Table 9.16.
Protector performance
These location categories and their probable worst case transients, provide us
with a yardstick with which to evaluate protectors. Subjecting the protector to an
appropriate transient test enables us to determine whether it will survive. The
protectors let-through voltage for this test tells us its transient control level. Letthrough voltage is a measure of the amount of the transient overvoltage which gets
past, or is let-through, the protector. Thus, if a protector is required for a mains
241
Lightning Protection
Table 9.15 Mains power supply – Category C, B and A.
Location category
System exposure level
Peak voltage (kV)
Peak current (kA)
C
C
C
High
Medium
Low
20
10
6
10
5
3
B
B
B
High
Medium
Low
6
4
2
3
2
1
A
A
A
High
Medium
Low
6
4
2
0.5
0.333
0.167
Derived from IEEE C62.41, UL 1449 and BS 6651: 1999.
Table 9.16 Data lines – Category C.
Derived from ITU IX K17 and BS 6651: 1999.
power distribution board (Category B) in a high exposure level, it should be able
repeatedly to survive a transient of 6 kA and 3 kA. Its let-through voltage when
injected with this 6 kV, 3 kA transient, should be no greater than the desired transient control level.
The let-through voltage of a protector also takes into account its response time.
Protectors with slow response times will have consequently higher let-through voltages. Response times are only of significant importance when dealing with very fast
transients such as NEMP.
BS 6651: 1999 Appendix C, suggests that manufacturers of transient protectors
should provide the following information about their products. The protectors letthrough voltage should be quoted against a given test, e.g. 600 V (live–neutral,
neutral–earth, live–earth), 6 kV 1.2/50 ms, 3 kA 8/20 ms, BS 6651: 1999 Category BHigh.
The let-through value should be the result of tests conducted on the complete
protective circuit – it should not be a theoretical value derived from the performance of one or more components.
242
Handbook of Electrical Installation Practice
Table 9.17 High impulse current tests.
Derived from ITU IX K17 and BS 6651: 1999.
Transients can occur between any combination of conductors. Manufacturers
should therefore make quite clear which modes of transient propagation let-through
performances relate to, e.g.:
•
•
Live/phase(s) to earth, live/phase(s) to neutral and neutral to earth for mains
power supplies
Line to line and line(s) to earth for data lines.
The maximum transient current the protector can withstand should be clearly
stated, e.g., 20 000 A, 8/20 ms.Again, this is a test value for the whole protector and not
a theoretical value. The maximum transient current of the protector also takes
account of its energy handling capability. Energy ratings, as a sole indicator of protective performance, are misleading, as the energy deposited in a protector by a transient current source depends on the suppression level (i.e. let-through voltages).Thus,
lower energy ratings do not necessarily mean that the protector is less likely to
survive.
The international telecommunication standard also calls for high impulse current
testing of data line protectors for telephone lines. This test (within ITU IX K12) is
intended to test the capability of gas discharge tube(s) present in most data line protectors. Test levels are shown in Table 9.17.
Any factor that may interfere with the system during normal operation should
be quoted. These may include the following:
•
•
•
•
•
•
•
•
•
Nominal operating voltage
Maximum operating voltage
Leakage current
Nominal current rating
Maximum continuous current rating
In-line impedance (or resistance)
Shunt capacitance
Bandwidth
Votage standing wave ratio (VSWR) or reflection coefficient.
Table 9.18 summarises potential causes of incompatibility or system impairment for
different types of power and data line protectors. Protector manufacturers should
243
Lightning Protection
Table 9.18 General indication of potential system impairments which manufacturers of
transient overvoltage protectors should provide.
Protectors for mains
supplies
Protectors for data lines
Parallel
protectors
In-line
protectors
Low
frequency
protectors
Network
protectors
Radio
frequency
protectors
Nominal operating
voltage
✓
✓
✓
✓
✓
Maximum operating
voltage
✓
✓
✓
✓
✓
Leakage current
✓
✓
✓
✓
✓
Nominal current rating
✗
✓
✓
✓
✓
Max continuous current
rating
✗
✓
✓
✓
✓
In-line impedance
✗
✗
✓
✓
✓
Shunt capacitance
✗
✗
✗
✓
✓
Bandwidth
✗
✗
✓
✓
✓
Voltage standing wave
ratio
✗
✗
✗
✓
✓
Derived from Furse Electronic Systems Protection Handbook, 1994.
therefore document values for their protector for all the characteristics indicated.
The question of the protector being incompatible with the system it is trying to
protect most commonly arises with data communication, signal and telephone
systems. However, when a mains power protector is based on a gas-discharge tube
connected across the supply, operation of the gas-discharge tube can short-circuit
the supply. The large mains current flowing through the tube is likely to destroy the
tube and disrupt the power supply.
Specifying lightning and transient overvoltage protection
A number of products are available which claim to protect electronic equipment
against lightning and transient overvoltages. However, testing shows many of these
244
Handbook of Electrical Installation Practice
to have an unacceptably high let-through voltage. This can prove disruptive and
harmful to electronic equipment. Use of the specification which follows will reduce
the likelihood of ending up with ineffective protection.
Key requirements
In order to provide effective protection, a transient overvoltage protector should:
•
•
•
•
•
Be compatible with the system it is protecting
Survive
Have a low let-through voltage, for all combinations of conductors
Not leave the user unprotected, as a result of failure
Be properly installed.
Compatibility. It is important that the protector does not interfere with or restrict
the system’s normal operation.
(1) It is undesirable for mains power supply protectors to disrupt or corrupt the
continuity of power supply and for them to introduce high earth leakage
currents.
(2) Protectors for data communication, signal and telephone lines should not impair
or restrict the systems data or signal transmission.
Survival. Although lightning discharges can have currents of 200 kA, transient
overvoltages caused by the secondary effects of lightning are unlikely to have currents exceeding 10 kA. The protector should therefore be rated for a peak discharge
current not less than 10 kA.
Let-through voltage. The larger the transient overvoltage reaching the electronic equipment, the greater the risk of interference, physical damage and
hence system downtime. Thus, the transient overvoltage let through the protector
should be lower than the level at which interference or component degradation may
occur.
Modes of protection. A transient overvoltage can exist between any pair of conductors: phase and neutral, phase and earth, neutral and earth on mains power supplies; line to line, line to screen/earth on data communication, signal and telephone
lines.Thus, the transient overvoltage protector should have a low let-through voltage
for all combinations of conductors.
Protection failure. When in-line protectors (such as those for data communication,
signal and telephone lines) fail, they take the line out of commission, thereby preventing damage to the system. However, it is unacceptable for protectors on mains
Lightning Protection
245
power distribution systems to fail short-circuit. If these protectors fail sudden death
they will leave the system unprotected. It is therefore important that protectors for
mains power distribution systems have a properly indicated pre-failure warning,
while protection is still present.
Installation. The performance of transient overvoltage protectors is heavily
dependent on their correct installation (e.g. the length and configuration of connecting cables). Thus, the transient overvoltage protector must be supplied with
documentation detailing the installation practice. The installer is required to
conform with these installation instructions.
Specification for protection on mains power distribution systems
(1) Transient overvoltage protectors should be installed on all power cables entering or leaving the building, in order to protect equipment connected to the
power distribution system against transient overvoltages coming into the
building from outside.
(2) Protectors should also be installed at local power distribution boards feeding
vulnerable equipment, in order to protect these against transients generated
downstream of the protectors in (1), above. (These transients may be the result
of inductive coupling or electrical switching.)
(3) Protectors shall be tested in accordance with the requirements of: BS 6651:
1999, Protection of structures against lightning (Appendix C),
BS EN 60099-1: 1994, Specification for surge diverters for alternating current
power circuits.
IEEE C62.41: 1991, Guide for surge voltages in low voltage AC power circuits.
(4) Protectors for a given Location Category shall be rated for a High
Exposure Level (as defined by BS 6651: 1999), unless contrary information is
available.
(5) The protector must not interfere with or restrict the system’s normal operation. It should not:
• Corrupt the normal mains power supply
• Break or shutdown the power supply during operation
• Have an excessive earth leakage current.
(6) The protector shall be rated for a peak discharge current of no less than 10 kA
(8/20 ms waveform).
(7) The protector shall limit the transient voltage to below equipment susceptibility levels. Unless otherwise stated, the peak transient let-through voltage
shall not exceed 600 V, for protectors with a nominal working voltage of 230
or 240 V, when tested in accordance with BS 6651: 1999 Category B – High
(6 kV 1.2/50 ms open circuit voltage, 3 kA 8/20 ms short-circuit current).
(8) This peak transient let-through voltage shall not be exceeded for all combinations of conductors:
• Phase to neutral
• Phase to earth
• Neutral to earth.
246
Handbook of Electrical Installation Practice
(9) The protector should have continuous indication of its protection status. Status
indication should clearly show:
• Full protection present
• Reduced protection – replacement required
• No protection – failure of protector.
(10) Remote indication of status should also be possible via a volt free contact.
(11) The status indication should warn of protection failure between all combinations of conductors, including neutral to earth. (Otherwise a potentially dangerous short circuit between neutral and earth could go undetected for some
time.)
(12) The protector shall be supplied with detailed installation instructions. The
installer must comply with the installation practice detailed by the protector
manufacturer.
Specification for data communication, signal and telephone line protection
(1) Transient overvoltage protectors shall be installed on all data communication/signal/telephone lines entering or leaving the building, in order to protect
equipment connected to the line against transient overvoltages. (Where data
lines link equipment in separate buildings, transient overvoltage protectors
should be installed at both ends of the line in order to protect both pieces of
equipment.)
(2) Protectors shall be tested in accordance with the requirements of:
BS 6651: 1999, Protection of structures against lightning (Appendix C).
ITU IX K17, Tests on power fed repeaters using solid-state devices in order to
check the arrangements for protection from external interference.
(3) Protectors shall be rated for Location Category C – High exposure level, unless
contrary information dictates a lower exposure level.
(4) The protector must not impair the system’s normal operation. It should
not:
• Suppress the system’s normal signal voltage
• Restrict the system’s bandwidth or signal frequency
• Introduce excessive in-line resistance
• Cause signal reflections or impedance mismatches (high frequency systems
only).
(5) The protector will have a low transient let-through voltage for tests conducted in accordance with BS 6651: 1999, Category C – High (5 kV 10/700 ms
test).
(6) This let-through performance will be provided for all combinations of
conductors:
• Signal line to signal line
• Signal line to screen/earth.
(7) The protector shall be rated for a peak discharge current of 10 kA.
(8) The protector shall be supplied with detailed installation instructions. The
installer must comply with the installation practice detailed by the protector
manufacturer.
Lightning Protection
247
(9) The protector manufacturer should allow for the facility to mount and earth
large numbers of protectors through an accessory combined mounting and
earthing kit.
ACKNOWLEDGEMENT
Extracts from BS 6651: 1999 are reproduced with the permission of BSI. Complete
copies can be obtained from BSI Customer Services, 389 Chiswick High Road,
London W4 4AL, telephone: 020 8996 9001, fax: 020 8996 7001.
CHAPTER 10
Special Installations or Locations
G.G. Willard, DipEE, CEng, MIEE
(Consulting Electrical Engineer)
Revised by Eur Ing L.D. Markwell, BSc, CEng, MIEE, MCIBSE
(Consulting Electrical Engineer)
The IEE Wiring Regulations, (issued since 1992 as a British Standard and now revised
to BS 7671: 2001 Requirements for Electrical Installations) make specific reference
to electrical installations in certain locations identified as ‘special locations’. Apart
from the need to meet the general requirements of the British Standard, additional
requirements or restrictions apply to these installations. This chapter expands and
explains the main additional requirements of BS 7671: 2001. Particular Regulations
are called up where necessary and referred to by their BS 7671 numbers.
In general, ‘special locations’ involve one or more of the following environmental conditions or different risks, which, in the absence of special arrangements,
would give rise to an increased risk of electric shock:
•
•
•
•
Wetness or condensation, i.e. reduced skin resistance
Absence of clothing, i.e. greater opportunity to make direct or indirect contact
through increased area of bare skin and bare feet
Proximity of earthed metalwork, i.e. increased risk of indirect contact
Arduous or onerous site conditions, i.e. conditions of use that may impair the
effectiveness of the protective measures.
The extra requirements for these ‘special locations’ have been devised by assessing
the relevant risks under each of the above categories and making adjustments to
the protective measures accordingly. The intention is to remove or minimise the
additional risks to users presented by the electrical installations within these ‘special
locations’. Designers, installers and operators of such installations must consider the
particular requirements of the installation and design, install or operate the installation to reduce or protect against risks from these requirements. It must be recognised, however, that all installations require adequate regular periodic inspection
and testing, and any necessary maintenance or repair works properly carried out.
The designer and installer must also be aware of current legislation and statutory
requirements, as well as local bylaws and local authority requirements (e.g. the Fire
Officer) in respect of buildings, construction works and electrical installations, and
any requirements for the continued operation of installations (for example, requirements for periodic inspection and testing of installations.)
248
Special Installations or Locations
249
Designers and installers should also be aware of the legal relationship and obligations that may be created between themselves and the ultimate user of an installation. The design and installation work creates what is legally termed a ‘duty of
care’ on the part of designers – to exercise skill and care in the design and selection
of materials and installation techniques and specified requirements, and on the part
of installers and maintainers – to follow strictly the best practices of the profession
and actually achieve a safe and workable end product. These obligations are not
unusual to special locations; however, the inherently greater risks associated with
such installations underscore the need for particular care and attention to detail.
There are also obligations under the CDM Regulations for all parties to design
installations for safe installation working, and provide information to allow for the
safe construction and maintenance of the installation.
Installations such as in explosive atmospheres or for lightning protection are not
referred to here because these are not covered extensively by BS 7671: 2001 but
either by a separate British Standard or they are the subject of special HSE guidance. Furthermore, marinas have not yet been included in BS 7671 because although
guidance exists through the International Electrotechnical Commission, this has yet
to be agreed in Europe and accepted in the UK.
In respect of ‘restrictive conductive locations’ and ‘earthing requirements for the
installation of equipment having high earth leakage currents’, these installation
types are covered in a prescriptive format within BS 7671.
As further work is done at international level, and applications develop, it is likely
that more installation types will be categorised as ‘special locations’, although there
is significant debate whether some other installation types – such as external lighting – are really ‘special’ in the terms of the requirements of the Wiring Regulations.
The list covered here should therefore be regarded as subject to further future
amendment.
Reference has generally been made to the content of BS 7671; however, IT
distribution systems have not been considered here in particular as it remains a
specific UK requirement that low voltage systems fed from the public supply
network should be connected with earth.
LOCATIONS CONTAINING A BATH TUB OR A SHOWER BASIN
The risks
The risks are from:
•
•
•
•
Wet skin
Absence of clothing
Proximity of earthed metal
Splashing and ingress of water.
The protective measures
Users of baths for medical treatment will potentially be subject to additional risks
associated with infirmity and reduced tolerance to electric shock. Such installations
250
Handbook of Electrical Installation Practice
will require further specialised treatment, and full consultation with the client’s
advisers and equipment suppliers is essential.
The design of electrical installations in locations containing a bath tub or shower
has undergone a considerable change with the introduction of the zoning concept
introduced by Amendment 3 to BS 7671: 1992. This allows the location of electrical
equipment and accessories in locations in rooms containing a fixed bath or shower
based on their IP rating. Unfortunately many items of electrical equipment and
accessories do not have stated IP ratings, but manufacturers would normally be
pleased to provide guidance in the selection of their products. (An alternative, older
rating schedule is also given in regulation 601-06-01.)
Figure 10.1 details the dimensions and spacing of the zones in plan and section,
but only illustrates typical arrangements; it is for the designer to assess the implications in a particular installation. Generally it can be seen that Zone 0 is the interior
of the bath tub or shower basin, and electrical accessories or switchgear are not to
be installed in this area. Certain fixed equipment may be allowable if it is designed
to be suitable for the location. Zone 1 encloses a space above the bathtub or shower
basin, and only some types of SELV switching can be installed. Some specific fixed
equipment may be allowable if it is designed to be suitable for the location (e.g. a
water heater) or can only reasonably be located in that zone and supplementary
protection is provided by an RDC with a rated residual operating current of 30 mA
b) Bath tub, with permanently fixed partition
a) Bath tub
Zone 2
Window
recess
Zone 1
Zone 1
Zone 2
Zone 3
Zone 2
Zone 3
0.6 m
2.4 m
Zone 0
Zone 0
0.6 m
2.4 m
s
Window recess
(0.6–s) m
Zone 2
Zone 3
S = thickness of partition
Ceiling
Outside Zones
Zone 2
Zone 3
Window
Recess
Zone 2
3.0 m
Outside Zones
Zone 3
Zone 1
2.25 m
Zone 2
Zone 0
*
0.6 m
2.4 m
Fig. 10.1 Zones of dimensions for bathrooms (from BS 7671: 2001).
Special Installations or Locations
251
or less. Zones 2 and 3 are further defined spaces around the bathtub or shower
basin, or spaces above a certain height, and the installation of SELV switch or control
gear equipment, or a shaver socket-outlet with double wound isolating transformer
(to BS EN 60742) is acceptable. Fixed equipment suitable for the location and
complying with relevant British Standards may also be installed.
Areas outside the zones, but still within the room, are not expressly covered by
the Regulations, but the electrical installation and protection must meet the general
requirements of the Regulations, and the use of RCDs to provide supplementary
protection against electric shock must be considered.
The protective measures
BS 7671 does not allow for socket-outlets in bathrooms unless they are part of a separated extra low voltage (SELV) circuit, or a shaver socket-outlet to BS EN 607422 with a double wound isolating transformer (electrical separation), and they must
be installed in the relevant zones (601-08-01). The thinking behind this is undoubtedly the very real concern that persons using a bathroom cannot be made safe from
the effects of direct or indirect contact from portable equipment brought into the
room and supplied at low voltage. Some portable equipment – such as hair dryers in
hotel bathrooms – can be installed using a fixed connection (not a plug and socketoutlet) and keeping the flexible cable as short as practical, if the equipment is really
required, but it is for the designer in every case to make an appraisal and assessment
of the risks involved in the provision of the equipment. A relaxation is permitted in
rooms other than a bathroom or shower room, where a shower cubicle is installed,
(e.g. a bedroom) provided that any socket-outlet, other than a SELV device or shaver
outlet to BS EN 60742-2, is installed at least 2.5 m from the shower cubicle. It should
be remembered here that in the case of a bath tub, adults tending the bathing of
others are potentially placed at risk by hand-to-hand indirect contact with metalwork that may become live in the event of an earth fault.The 2.5 m referred to therefore provides for a restriction of access to items of substantial risk.
This ‘inaccessibility’ principle extends to electrical equipment generally and only
switches using insulated linkages or pull cords to operate BS 3676 devices, or specially designed controls to BS 3456 (instantaneous water heaters), are permitted
within this zone. It is accepted, however, that a shaver supply unit with a BS EN
60742-2 transformer may be installed, as may switches supplied by SELV where the
nominal voltage does not exceed 12 V r.m.s.
Fixed equipment within the 2.5 m zone must be selected and erected according
to foreseen risks, and its likely duty. The likelihood is for splashing water to be
present and this requires an IP rating dependent on its location in the room. Power
showers can generate penetrating jets of water and may require a minimum of IPX5
equipment.
BS 7671 does not actually prohibit the use of Class I fixed equipment, but stationary appliances with heating elements which can be touched should preferably
be mounted outside the 2.5 m arm’s reach zone. Similarly, luminaires to be fixed
within this zone should preferably be either totally enclosed, or if of Type B22,
should be fitted with a BS 5042 (Home Office) shield.
In general, those responsible for selection and erection of equipment will find that
Class II devices more readily satisfy the requirements for such rooms. However,
252
Handbook of Electrical Installation Practice
consideration should be given to the possible deterioration of the Class II insulation due to the prolonged effects of moisture and heat. Furthermore, eventual use
cannot be controlled and inadvertent replacement by a Class 1 device in service
must be considered a possibility.
With the increased use of pumped water in bathrooms for spa-baths, power
showers, etc. there is a need, on occasions, to provide for motive power within the
area of the bath. In order to protect against direct and indirect contact, supplies for
such equipment must be by SELV with the nominal voltage not exceeding 12 V r.m.s.
Where it is necessary to mount the SELV source within the bath enclosure, then it
may only be accessible by means of a tool. The reason for this is concerned with the
now familiar definition of skilled person, i.e. it is assumed that persons using a tool
to access the SELV source under a bath will be sufficiently informed and skilled to
avoid danger and that the circuit will be dead and isolated before work is commenced.
A fundamental point which gives rise to considerable confusion is supplementary
equipotential bonding. It is a requirement to supplementary bond all simultaneously
accessible exposed and extraneous-conductive-parts. This should include all incoming metallic services (including metal wastes) and any structural metalwork –
including a metallic floor grid, if provided. The definition of ‘extraneous-conductivepart’ has changed over the years and is now recognised as ‘a conductive part liable
to introduce a potential, and not forming part of the electrical installation’.
Installers should note that it is acceptable to employ the protective conductor
within a short length of flexible cord as a supplementary bonding conductor for an
appliance, provided that connection is by a flex outlet.
BS 7671 does not make specific requirements regarding wiring systems for
bathrooms, but systems employing exposed surface metalwork such as metal
conduit should preferably not be used. Apart from introducing unnecessarily large
areas of exposed-conductive-parts, surface metal would also attract considerable
condensation in use.
Installers who are aware of current European practice will know that socketoutlets in bathrooms are permitted on the continent. This issue is one where there
remains disagreement at international level with no alignment in IEC or CENELEC
at this time. Because of this, this ‘special location’ should be regarded as subject to
continuing review. It is unlikely that general purpose socket-outlets will ever be
acceptable in UK bathrooms, and as other methods of supply and connection of
equipment are available it may not be perceived as a significant problem.
SWIMMING POOLS
Swimming pools are similar in some respects to domestic baths; however, the scale,
and the possibility of vigorous games and inevitable use of electrical equipment
require a more rigorous approach.
The risks
The risks are from:
•
•
Wet skin
Absence of clothing
Special Installations or Locations
•
•
253
Proximity of earthed metal
Arduous conditions (possible corrosive effects of chemicals).
The protective measures
Three volumetric zones, A, B and C, are defined by BS 7671 in order to provide
an analytical basis for the design and erection of the electrical installation. It also
recognises the need in a swimming pool environment for portable cleaning equipment and the desirability of fittings such as special pool luminaires. The zones are
shown in Figs 10.2 and 10.3. As with rooms containing a bath or shower tray, the
2.5 m inaccessibility limitation applies.
General requirements in all zones extend to the local supplementary bonding of
all extraneous and exposed-conductive-parts. Requirements for an equipotential
grid changed with the first Amendments to BS 7671: 1992. Where a grid is installed
within the solid floor, in order to ensure that the equipotential principle is maintained over what could be a substantial area of the building, it is to be supplementary bonded as any other extraneous-conductive-part. The connections (at remote
ends of the grid) should be accessible for inspection and testing.
Requirements within the zones
Zone A
•
•
Socket-outlets are not permitted
SELV system may be employed, but subject to 12 V maximum nominal voltage
and the provision of additional protection against direct contact, comprising:
䊊 Barriers or enclosures to IP2X or IPXXB; or
Fig. 10.2 Zone of dimensions for basin above ground level. The dimensions are measured
taking account of walls and fixed partitions (from BS 7671: 2001).
254
Handbook of Electrical Installation Practice
Fig. 10.3 Zone of dimensions of swimming pools and paddling pools. The dimensions are
measured taking account of walls and fixed partitions (from BS 7671: 2001).
A wiring system capable of withstanding a test voltage of 500 V a.c. r.m.s. for
1 minute. The safety source must not be installed within Zones A, B, or C
Floodlights must be supplied from individual transformers, mounted outside
Zones A and B, with a maximum open circuit voltage of 18 V
Equipment must have a degree of protection of at least IPX8
Equipment must be specifically intended for use in swimming pools.
䊊
•
•
•
Although requirements for swimming pools are aligned through Europe by
CENELEC standards, this does not mean that swimming pool equipment can be
incorporated into UK swimming pool installations and it is necessary for the
designer to check that the country of origin is a signatory to CENELEC in
addition to checking and satisfying himself of the specific safety of the equipment
and the standard to which the equipment is manufactured.
•
•
•
Only wiring necessary to supply equipment in Zone A may be run in Zone A
No accessible metallic junction boxes are permitted
Surface wiring systems must not employ metallic sheaths or enclosures.
Underwater illumination is sometimes utilised in modern pools, but the designer
must ensure the luminaires are suitable for the location, comply with relevant
standards, and that adequate protection is provided against the risk of electric shock.
Zone B.
•
•
The above items apply except:
IPX8 is relaxed to IPX5 and permits water jets to be used for cleaning purposes
– IPX4 applies where water jets are unlikely to be used.
It is recognised that due to constructional limitations, it might not be possible to
mount socket-outlets outside Zone B. As a relaxation, BS EN 60309-2 (was BS
4343) socket-outlets may be installed, but at least 1.25 m from the Zone A border
(single arm’s reach restriction of access) and 0.3 m above the floor. However, they
Special Installations or Locations
•
•
255
must be protected by an appropriate residual current device (RCD). (It would
also be a reasonable precaution to provide socket-outlets with a lockable cover
to prevent their unauthorised use.)
An electric heating element may be laid into the floor. This must incorporate a
metallic sheath, which is to be bonded to the metallic grid (if supplied). Alternatively, if a grid is not supplied, the metallic sheath should be connected to the
equipotential bonding.
Water heaters are permitted.
Zone C
•
•
•
•
Electrical equipment must have minimum degrees of protection of IPX4 for
outdoor pools and IPX2 for indoor pools – but this must be increased to a
minimum of IPX5 where water jets are likely to be used for cleaning purposes.
Alternatives for providing protection against indirect contact for electrical equipment are the use of RCDs, SELV or individual electrical separation.
A heating element with a metallic sheath may be laid into the floor. Bonding
arrangements are to be as in Zone B.
Installers should be particularly careful over the selection and erection of equipment in Zone C. It is likely to be used by persons who are soaking wet, having
just emerged from the pool. Although the environs of Zone C will seem mainly
dry and apparently give rise to little risk, the bather’s wet skin would otherwise
create a risk when using electrical equipment. Instantaneous water heaters to BS
3456 are permitted without special earth fault protection; however, hand dryers,
sun-beds, etc. will require additional protection as above.
As well as the forgoing, designers and installers must be aware of their duty under
the CDM Regulations to provide a design and installation that is safe to maintain
and demolish at the end of its life. Maintenance access to general lighting luminaires
in a large swimming pool hall is of specific concern, and the design must allow for
safe access.
HOT AIR SAUNAS
The risks
The risks are from:
•
•
•
•
Wet skin/high humidity
Absence of clothing
Proximity of earthed metal
Arduous conditions of service, particularly at high temperatures.
The protective measures
The various areas of hot air saunas are classified by volumetric zones, as with
swimming pools but with limits also defined by maximum temperatures. These zones
are illustrated in Fig. 10.4.
256
Handbook of Electrical Installation Practice
Fig. 10.4 Hot air saunas – zones of ambient temperature (from BS 7671: 2001).
Zone A. Only the sauna and equipment directly associated with it may be installed
here, i.e. heater, flexible cord and junction box to fixed wiring.
Zone B. There are no special heat resistance requirements, due to thermal
gradient within the sauna enclosure.
Zone C.
Equipment should be suitable for ambient temperatures of 125°C.
Zone D. Equipment should be suitable for ambient temperatures of 125°C and
must be restricted to sauna control devices (e.g. thermostat, cut-out), luminaires, and
their associated wiring. Care should be taken in the selection and erection of
luminaires to avoid overheating due to the accumulation of hot air combined with
the heating effect of the luminaire itself.
Wiring systems within the sauna must employ 180°C flexible thermosetting (rubber)
cords, and the cord must be protected from mechanical damage.
CONSTRUCTION SITE INSTALLATIONS
The risks
The risks are from:
Special Installations or Locations
•
•
•
•
257
Wetness/wet skin
Proximity of earthed metalwork
Arduous conditions and the possibility of physical damage
Temporary nature of connections.
It is important to remember that temporary installations on construction sites,
demolition sites, major building renovations and works of a similar nature can
greatly accelerate deterioration of wiring systems, through the arduous nature of
the works. The protective measures indicated below should therefore be supported
by regular and frequent formal inspection and testing and reports on the installation. Of particular importance in such reporting is the physical and electrical condition of enclosures, cable sheaths and terminations. A detailed examination should
be carried out to establish whether these have been subject to damage or excess
physical strain in service. The scope of BS 7671: 2001 does not include portable electrical equipment or tools or their associated flexible cords, but there are other statutory requirements covering their use and care.
The Regulations for Construction Sites apply to the site main switchgear and the
installation that is moveable or demountable, but not the fixed installation in the
site accommodation, which is covered by the general requirements of BS 7671: 2001.
The protective measures
The Regulations allow for the use of the following methods of electrical protection.
Supplies for general use
(1) Automatic disconnection and reduced low voltage, i.e. earthed centre-tapped
110 V secondary or earthed star point 110 V secondary transformers.
Note: BS 7671 requires a maximum disconnection time of 5 seconds and
0.2 seconds for fixed and moveable equipment respectively, at 230V. Moveable
equipment supplied at 400V must be disconnected in 0.05 seconds. Maximum
values of earth loop impedance to achieve these times, for 230V, are tabulated
in BS 7671 and should be ascertained by reference to the earth loop impedance
for the system and the characteristics of the particular protective device.
(2) The use of a 30 mA residual current device – provided the inequality
ZsID £ 25 V can be satisfied, i.e. the touch voltage which could be experienced
in the event of an earth fault would be restricted to lower limits.
(3) SELV.
(4) Electrical separation – but on the basis of individual socket outlets protected
by individual separated sources.
(5) Automatic disconnection – applies only to 400 V three-phase and 230 V
single-phase supplies to the fixed installation and movable equipment such as
floodlights.
It is understood that it is common continental practice to use RCDs on construction sites. However, the UK safety record with reduced low voltage systems is very
good and it should be borne in mind that the very nature of construction sites is
258
Handbook of Electrical Installation Practice
potentially damaging to delicate devices such as RCDs. These should be regularly
checked for physical damage and to confirm their electrical characteristics.
If the required disconnection times are not achievable by this method, then supplementary equipotential bonding can be applied and the inequality R £ 25/Ia may
be used to calculate the impedance of supplementary bonding to ensure that contact
with exposed conductive parts does not give rise to potentials that are considered
dangerous in the circumstances. R is the resistance of the supplementary bonding
conductor between simultaneously accessible exposed-conductive-parts and extraneous-conductive-parts and Ia is the operating current of the protective device. This
is not considered to be a satisfactory means of achieving compliance with BS 7671,
due to the changing circumstances that prevail on construction sites and the danger
of disconnection of, or damage to, the bonding connection.
Supplies for portable hand lamps in confined or damp conditions
(1) SELV is suitable but the extra low voltage must be no greater than 50 V.
However, lower voltages have been considered to be better (e.g. 25 V).
(2) Reduced low voltage using single-phase and earthed centre tapped transformers. Voltages up to 110 V single-phase centre point earthed are allowed in
BS 7671 but lower voltages should be considered depending on the risk. A risk
analysis should be carried out and the special requirements of section 606 of
BS 7671: 2001 should be considered where the risks include restriction of
movement in locations.
Standards for equipment
•
•
•
Distribution assemblies should be to BS 4363 and BS EN 60439-4 (was BS 5486)
All other equipment should have an Index of Protection appropriate to the external influence, but a minimum of at least IP44 should be utilised in open areas
All plugs, sockets and cable couplers must be to BS EN 60309-2 (was BS 4343).
Electricity supply arrangements
Installers should note that Distribution Network Operators (DNOs) may be unwilling to make available a PME earthing terminal to construction sites. This means
that in the event of a conventional TN-S system, or a dedicated local transformer,
not being available, it will be necessary to establish a reliable connection with the
general mass of earth through the use of earth rods, or other independent means
of earthing.
AGRICULTURAL AND HORTICULTURAL PREMISES
The risks
The risks are from:
•
•
•
Wetness/wet skin
Proximity of earthed metal
Arduous conditions of service
Special Installations or Locations
259
plus
•
•
Fire
Rodent attack on wiring systems.
The risks associated with agricultural premises are accentuated where livestock are
concerned, owing to their apparently greater sensitivity to electric shock. This has
long been held to be due to their more intimate contact with earth, and the distance
apart of the limbs of a quadruped, which can give it access to a greater substantial
touch voltage in the event of an earth fault. A voltage gradient across the soil in the
vicinity of an earth rod can easily approach levels that are fatal to livestock. An
earth stake or other extraneous-conductive-part will set up concentric lines of
constant potential in the soil under earth fault conditions, with maximum voltage
gradient (and therefore touch voltage) at the earth rod, and reducing to zero many
metres away.
The plastic used in modern cable systems is subject to attack by rodents. Apart
from causing functional failure, this can contribute to risk of shock and fire.
The protective measures
Installations for general use
SELV may be used to provide protection against direct and indirect contact.
However, supplementary protection against direct contact must be provided by
barriers or enclosures to IP2X – or insulation capable of withstanding a test voltage
of 500 V for 60 seconds.
Measures for protection against direct contact such as the use of enclosures,
obstacles and placing out of reach, are not excluded, although it is a requirement
that all socket-outlets should be further protected by an appropriate residual
current device.
In respect of protection against indirect contact, maximum disconnection times
are reduced and in these installations, disconnection must occur within 0.2 seconds
for a nominal system voltage of 230 V. This should be achieved by designing and
constructing within stated earth loop impedance maxima for a given protective
device. For distribution circuits and circuits supplying fixed equipment, a disconnection time of 5 seconds is permitted.
Where a residual current device is installed, BS 7671 gives limiting values for
circuit parameters such that the product of earth loop impedance and the rated
residual operating current for the device should not exceed 25 V.
The above comments for indirect contact apply to TN systems. Where TT systems
are concerned, there is a further requirement for each circuit that:
RA I a £ 25 V
RA is the sum of the resistances of the earth electrode and the protective conductors connecting it to the exposed conductive parts, IA is the current causing the
automatic operation of the protective device within 5 seconds. In practical terms,
this will frequently be a residual current device and the current should then be taken
as the rated residual operating current.
260
Handbook of Electrical Installation Practice
Installations for the management of livestock
SELV may be used to provide protection against direct and indirect contact.
However, where livestock is to be protected, the nominal extra low voltage of 50 V
may be too high and will require reduction according to the type of livestock. In
order to protect livestock against the effects of indirect contact where low voltage
is distributed, earthed equipotential bonding and automatic disconnection of supply
should be employed, as described above, together with supplementary bonding of
all exposed and extraneous-conductive-parts accessible to livestock. The resistance
of a supplementary bonding conductor is given by R £ 25/Ia to again effectively
reduce the touch voltage.
Protection against fire
For some protection against fires of electrical origin, a residual current device with
a rated residual operating current not exceeding 0.5 A should be installed to protect
all equipment other than installations essential to the welfare of livestock. This
should be regarded as an absolute minimum standard of protection against fire
caused by earth fault currents, and the buildings may require to be supplemented
with smoke and heat detection systems, according to the type of installation.
Installers should note here the use of two residual current devices in series, and
Regulation 531-02-09 requires the characteristics of the devices to be coordinated
in order to achieve discrimination. It is usual that such discrimination would require
the installation of a time delayed RCD (S type) as the upstream device.
Wiring systems
Vermin may attack and seriously damage PVC wiring systems. In addition, urine
from livestock and some agricultural chemicals can cause rapid corrosion and failure
of steel enclosures, either by direct contact or corrosive fumes. Poor ventilation of
animal buildings can also lead to excessive condensation, and consequently water
resistant equipment may be required. Wiring systems must therefore be carefully
selected in relation to the risk of damage from agricultural-type external influences.
Animals can also cause physical damage.
Switchgear and accessories
Class II equipment should be used wherever practicable in this environment, but
care should be taken over enclosure ratings because the prolonged effects of animal
urine, damp and dusty conditions may reduce the effectiveness of the Class II
insulation. Also, due to the arduous nature of agricultural activities, substantial
equipment should be selected. Individual circumstances will dictate standards, but
as a guide a minimum rating of IP44 will give adequate protection against ingress
of solid bodies and liquids, unless dust or jets of water are present (such as in
washing down animal areas) when IP55 or IP56 should be used.
Arrangements for isolation and switching
It should be remembered that agricultural installations are, in many respects,
industrial installations with the additional hazard of livestock. Great care should
therefore be given to the provision and location of emergency switches for
machinery. Animals can move or panic and impede access to emergency switches.
Special Installations or Locations
261
Electricity supply arrangements
As with construction site electricity supplies, DNOs may be reluctant to provide a
PME earthing terminal to agricultural and horticultural installations. This will be
mainly due to the difficulty in maintaining the equipotential zone throughout the
installation and the rare but potentially serious situation that could arise from a loss
of neutral conductor.
Electric fences
Electric fences are to be in accordance with the requirements of BS EN 61011, and
controllers properly located away from interference and damage, and away from
other equipment and conductors.
EQUIPMENT HAVING HIGH PROTECTIVE CONDUCTOR CURRENTS
Electronic equipment can have significant current flowing to earth continuously as
a part of its normal operation (functional earth current) due to power supplies,
filters, etc. Normally a current flow to a properly designed earth system is not dangerous, but a higher integrity of earth connection is required to assist in preventing
dangerous touch voltages if an earth connection becomes disconnected.
The risks
The risks are from:
•
Shock risk from fault voltages due to damaged earth connections.
The protective measures
The basic requirements are for the provision of a duplicate earth connection on a
circuit protective conductor, and high integrity connections.
Some equipment has functional protective conductor leakage current in accordance with the relevant British Standard for the equipment. Single items where
the functional earth current does not exceed 3.5 mA need no special considerations,
but where a number of such items are connected on the same final circuit their
cumulative earth current must be considered, and the extra requirements of section
607 may become necessary, as they are to the installation of single items with functional protective conductor currents exceeding 3.5 mA.
The protective conductors are to be designed to carry the normal circuit earth
fault currents as calculated by the requirements of Parts 4 and 5 of BS 7671: 2001.
It must also be recognised that the installation must be regularly inspected and
tested and properly maintained to prevent deterioration of the installation.
CARAVANS AND MOTOR CARAVANS
These notes are intended to be applied to caravans and motor caravans. They are
not applicable to mobile homes and other moveable structures supplied through the
use of a permanent electrical connection.
262
Handbook of Electrical Installation Practice
The risks
The risks are from:
•
•
•
•
Wetness
Minimal clothing
Arduous conditions
Temporary nature of connections.
The protective measures
General
BS 7671 disallows certain protective measures for caravans and, in practical terms,
installations will usually employ insulation and enclosures as protective measures
against direct contact, and earthed equipotential bonding and automatic disconnection of supply (with supplementary protection by residual current device) as
the most likely protective measure against indirect contact.
Because a caravan may require to be fully functional when low voltage is not
available, extra low voltage battery circuits are normally also employed. The
separation of low voltage and extra low voltage, and the temporary nature of the
electricity supply connection arrangements within a potentially metallic structure,
require special consideration in relation to the design of systems and the protective
measures to be employed.
The provision of a residual current device in the caravan gives the user protection against indirect and direct contact, irrespective of the caravan park supply
arrangements. Without this independence the user relies on the caravan park operator to provide and maintain an essential protective measure on his behalf and this,
in some circumstances, may not be acceptable.
It is a requirement that extraneous-conductive-parts of the caravan should be
bonded to the circuit protective conductor. However, on the basis of the definition
of an extraneous-conductive-part being that which is ‘. . . liable to introduce a potential etc.’, metal sheets forming part of the structure of the caravan are not required
to be bonded.
Selection and erection of equipment
Wiring systems are required to be of flexible or stranded conductor construction,
with a minimum cross-section area of 1.5 mm2. Furthermore, cables are to be supported at intervals of not more than 0.4 m vertically and 0.25 m horizontally. Special
attention is drawn to the need to bush or similarly protect cables where they pass
through metalwork. These requirements are all due to the movement and vibration
likely to be incurred by a caravan in motion. Generally, there may not be any wiring
accessories with accessible conductive parts excepting fixing screws.There is concern
Special Installations or Locations
263
in caravan installations in that due to the modern thin wall caravan construction the
wiring cannot readily meet the installation requirements of Regulation 522-06 of
BS 7671: 2001 without further mechanical protection on the other side of the wall
to the cable route. The industry is currently considering the use of other cable types
with integral earthed metal protection.
Extra low voltage circuit arrangements are required to conform to the BS 7671
requirements for SELV. This places restrictions on the type and nominal voltage of
the ELV source, and the selection and erection of ELV conductors. SELV nominal
voltages are restricted to the preferred values of 12 V d.c., 24 V d.c. or 48 V d.c. with
a dispensation to allow a.c. sources of the same (r.m.s) voltages in ‘exceptional
cases’. In order to secure the satisfactory electrical separation of low voltage and
extra low voltage systems, cables of these two systems should be run physically
segregated. Extra low voltage and low voltage sockets must not be compatible.
Furthermore, extra low voltage sockets are required, as added security, to have
their nominal voltage clearly and indelibly marked.
In respect of some accessories, such as dual voltage luminaires, special requirements are prescribed in BS 7671 to ensure the separation is maintained. In addition, specifiers should consider carefully the functional needs of the caravan user
when planning the installation. Many caravan users are practical people who would
encounter little difficulty in altering an existing installation by the addition of nonstandard luminaires, without realising the potential hazard that may be introduced.
In recognition of the fact that continual movement could damage pendant flexible cords, BS 7671 actually recommends luminaires to be fixed direct to the body
of the caravan. Where it is necessary to fit pendant luminaires, the practitioner is
required to ensure that the means of suspension of the luminaire is sufficiently
robust for the mass to be supported and to provide adequate anchoring of the
luminaire, to prevent damage while in motion.
As is to be expected, the means of connection of caravans is standardised, and
plugs, sockets and connectors are all to be to BS 4343 standard (now renumbered
as BS EN 60309-2), with the inlet socket not more than 1.8 m above ground level
but in a readily accessible position and mounted in an enclosure with a suitable
cover to the outside of the caravan. The flexible cord or cable must not be longer
than 25 m and BS 7671 requires it to be in accordance with BS 6007 or BS 6500.
Recent convention has expected a cable rated capacity of 16 A; however, modern
caravans and motor caravans are fitted with substantial electrical appliances and in
recognition of this, BS 7671 provides for cables of up to 100 A capacity.
Vital to the safety of caravan users is the condition of the electrical installation,
bearing in mind the arduous conditions and the potential for do-it-yourself
additions. BS 7671 recognises this and prescribes a standard format notice to users
advising that the installation should be inspected and tested at least once every
three years.
CARAVAN SITE SUPPLY ARRANGEMENTS
The following notes will apply equally to caravans, motor caravans and tents where
temporary connections are made to moveable leisure accommodation.
264
Handbook of Electrical Installation Practice
It is expected that the supply will be via underground cable, where practicable,
and suitably protected or distant from areas of potential damage from ground
anchors, etc. The individual supply terminal equipment or distribution unit is to be
adjacent to each site pitch and BS 7671 makes specific requirements in terms of the
terminal equipment in so far as the enclosure positioning, socket-outlet specification and related overcurrent protection are concerned. It also recognises that supplies in excess of 16 A may be required. It is required that the pitch supply position
is located so that it is accessible for the caravan to connect to with normally a 25 m
flexible cable.
It is a requirement to provide protection against indirect and direct contact by
means of a suitable residual current device. It is convention to group pitches
together electrically; if this is done then groups of up to three socket outlets may
be protected by the same device. Groups of caravans must be fed from the same
phase.
A network that feeds a large caravan site will normally be an underground
system that will require considerable care in design. The use of small distribution
pillars can allow for a main distributor system on either a ring or radial system
which can be combined with smaller service-type cables to individual groups of
pitches.
It should be noted that in the event of a PME supply being provided for a caravan
site, the caravan sockets must not be connected to the PME terminal. Instead, earthing arrangements should be as with a TT system with the protective conductors of
caravan supply sockets connected back to an earth rod. This is underscored by a
special reference to caravans in the statutory regulations, which instructs that where
PME systems are employed, the supply neutral conductor must not be connected
to any metalwork in any caravan.
HIGHWAY POWER SUPPLIES AND STREET FURNITURE
The risks
The risks are from:
•
•
•
•
•
•
Wetness
Proximity of earthed metal
Proximity of live parts
Arduous conditions
Potential for working at high level
Potential for working amidst traffic.
The protective measures
Normally electrical equipment used for highway power supplies shall have a
minimum IP rating of IP33, but most equipment is rated IP 65.
In view of the traditional means employed of mounting some items of street furniture on DNO poles, BS 7671 makes some concessions as to the use of protection
Special Installations or Locations
265
against direct contact by placing out of reach. It is, however, a requirement that
operatives shall be skilled, specially trained persons where items of street furniture
to be maintained are within 1.5 m of a low voltage line. Furthermore, placing out
of reach may only be employed where the low voltage line is constructed to the
standard required by the statutory regulations. The designer must therefore
consider safe means of maintenance and a suitable working methodology. The
Electricity at Work Regulations 1989 place considerable obligation on designers and
operators of systems requiring work to be carried out on or near live conductors.
The Supply Authority will in any case have local requirements regarding design,
operation and maintenance of systems to be erected in the vicinity of live low
voltage conductors.
Measures may not include the use of non-conducting locations, earth free equipotential bonding or electrical separation as protection against indirect contact. Street
furniture must survive in an arduous environment and is often subjected to harsh
treatment through road traffic accidents or vandalism. Protective measures should
therefore be provided on the basis of a low maintenance, robust system. It is most
likely that these will be a combination of insulation, barriers and enclosures as
protection against direct contact, with earthed equipotential bonding and automatic
disconnection of supply as protection against indirect contact.
Doors are generally intended to provide access for skilled persons and do incorporate the use of a tool. However, such doors are sometimes seen in a dilapidated
state of repair in service and doors in street furniture are not to be regarded as a
barrier or enclosure and do not in any case generally provide sufficient protection
against ingress of moisture. Intermediate barriers are required by BS 7671, to
prevent contact with live parts and an intermediate barrier to at least IP2X or
IPXXB must be present to protect from direct contact with any live parts when a
door is open. Such accessories as street lighting cut-out fuse units are designed to
provide this secondary protection as an integral part of their design, and live parts
are not accessible when the fuse is withdrawn.
The metal door to a street lighting column, etc. does not require to have a separate bonding conductor connecting to the column as when fixed into place it is an
integral metal part of the column with intimate contact with the column, and when
removed for access it is isolated.
A maximum disconnection time of 5 seconds is stipulated for fixed equipment
and this should be determined through calculation of earth fault current from
maximum earth fault loop impedances. Disconnection times may then be interpolated from time/current curves for the particular protective device.
Extraneous-conductive-parts are to be bonded back to the main earthing terminal, but this should not include metallic structures not connected to, or a part of,
the highway electrical equipment. (This includes such items as metal fences, etc.)
If the supply authority gives permission to allow the cut-out in an item of equipment to be operated by others during maintenance, then such operation will require
skilled or trained persons. It is likely that the supply authority will make requirements as to the level of skill to be employed and may wish to exercise some screening of personnel. If the Supply Authority does not allow others to operate their
cut-out in an item of equipment for isolation purposes then a separate isolator will
be necessary.
266
Handbook of Electrical Installation Practice
Where highway street furniture feeds out to other equipment, or the maximum
load exceeds 16 A, a double-pole isolator (four-pole in the case of three-phase
equipment) shall be installed as a switching device.
Underground highway cables should be marked or colour coded either by means
of marker tape or other identification on ducts or tiles. This is to ensure they are
identified separately from other services.
Accurate drawings and records should accompany the Electrical Installation
Certificate. This is to provide a sound basis for maintenance and to help ensure
that accidental excavation of live cables is prevented.
CHAPTER 11
Electrical Safety
K. Oldham Smith, CEng, MIEE, MCIBSE
(Electrical safety consultant and formerly an HM Senior
Electrical Inspector of Factories)
Revised by
R.T.R. Pilling, DipEE, CEng, MIEE
(Electrical safety consultant, formerly an HM Principal
Electrical Inspector)
The electrical risks of shock, burn, fire and explosion, exact an annual toll of accidents ranging from electrocutions (i.e. deaths from electric shock) to minor burn
injuries. Fires and explosions account for most of those dangerous occurrences
which do not involve personal injury but destroy plant and property. Yet safety,
which should be of paramount importance to everyone, is often treated with indifference and is hardly a popular subject, except perhaps with safety officers, the
enforcement authorities and others with a professional interest in it.
Since 1833 when the Factory Inspectorate began, various Acts and Regulations for safety, health and welfare, have been promulgated to require safe working practices and conditions and to impose on all at work a duty of care for the
safety of themselves and other people. Non-compliance with Regulations is a
criminal offence, the penalties are severe and ignorance of the law is not an
excuse.
The comments in this chapter relate specifically to UK installations and those following British practice.
LEGISLATION
Electrical work is subject to the following legal requirements:
(1) The Health and Safety at Work etc. Act 1974 (HSW). This Act is applicable
to everyone at work except those in domestic employment. It also protects
others in the vicinity of the work. There are no specific electrical requirements but section 6 is considered to be applicable to electrical installation
work and imposes onerous duties on designers and constructors. In Schedule
3 of the 1987 Consumer Protection Act, section 6 was made applicable to
fairgrounds.
267
268
Handbook of Electrical Installation Practice
(2) The Equipment and Protective Systems for Use in Potentially Explosive Atmospheres Regulations 1996. Only equipment which has been constructed to these
Regulations, or an appropriate British, harmonised European or equivalent
International Standard, should be used in hazardous areas. Such areas include
those where flammable liquids are stored, which includes petrol stations. Equipment which has been constructed to the Regulations meets the essential safety
requirements of the ATEX Directive.
(3) The Low Voltage Electrical Equipment (Safety) Regulations 1994. These cover
almost all electrical equipment operating on low voltage (i.e. less than 1000 V).
(4) The Electricity Safety, Quality and Continuity Regulations 2002 (ESQCR)
came into force on 31 January 2003. These new statutory Regulations revoke:
•
•
•
•
•
•
The Electricity Supply Regulations 1988
The Electricity Supply (Amendment) Regulations 1990
The Electricity Supply (Amendment) Regulations 1992
The Electricity Supply (Amendment) Regulations 1994
The Electricity Supply (Amendment) (No. 2) Regulations 1994
The Electricity Supply (Amendment) Regulations 1998.
The Regulations impose duties on generators, distributors, suppliers and meter
operators, and in certain respects on their agents, contractors and subcontractors. The statutory requirements are laid out in eight parts:
I Introductory
II Protection and Earthing
III Substations
IV Underground Cables and Equipment
V Overhead Lines
VI Generation
VII Suppliers to Installations and to Other Networks
VIII Miscellaneous
Regulation 28 provides for the supplier or distributor to provide the following information in writing to any person who can show reasonable cause for
requiring it:
•
•
•
•
•
•
The maximum prospective short circuit current at the supply terminals
For low voltage connections, the maximum earth fault loop impedance of the
earth fault path outside the installation
The type and rating of the distributor’s protective device or devices nearest
to the supply terminals
The type of earthing system applicable to the connection
The declaration of the number of phases
The voltage and frequency.
The Engineering Inspectorate of the Department of Trade and Industry has
published detailed guidance on the application of the Regulations.
Electrical Safety
269
(5) The Building Standards (Scotland) Regulations 1990. These replace the Building Standards (Scotland) Regulations with Amendment Regulations 1971–80.
Electrical installations have to meet ‘Technical Standards’, e.g. British Standards
and/or CENELEC harmonisation documents.
(6) The Cinematograph (Safety) Regulations 1955. The special requirements
include separate circuits for the general and safety lighting and the projection
room installation. A separate power source has to be provided for the safety
lighting.
(7) Electricity at Work Regulations 1989 (EAW). These took the place of the
Electricity (Factories Act) Special Regulations 1908 and 1944 on 1 April 1990.
Whereas the latter applied essentially to work in factories, the former were
made under the provisions of the HSW Act and protect everyone at work
(except in domestic employment) and others in the vicinity of the work place.
They extend to mines and quarries and superseded the Coal and Other Mines
(Electricity) Regulations 1956, the Quarries (Electricity) Regulations 1956 and
Regulation 44 – Electricity of the Construction (General Provisions) Regulations 1961.
Other legislation
In the last few years, there have been a number of EC Directives on worker safety
and there are more to come. The member states have to implement them by introducing their own legislation. Although they are not electrical, contractors need to
be familiar with these new Regulations. Some of the more relevant ones are:
Management of Health and Safety at Work Regulations 1999
Provision and Use of Work Equipment Regulations 1998
Personal Protective Equipment (PPE) Regulations 1992
Health and Safety (Display Screen Equipment) Regulation 1992
The Construction (Design and Management) Regulations 1994.
Non-statutory regulations
The electrical contractors’ ‘bible’ is BS 7671: Requirements for Electrical Installations, commonly called the IEE Wiring Regulations. The fourth amendment to the
sixteenth edition of these was published in June 2001. These Regulations are based
on IEC Publication 364 and some parts are CENELEC harmonised. Compliance is
required by most specifications for installation work, to meet the requirements of
the Electricity at Work Regulations 1989 and for approval by the National Inspection Council for Electrical Installation Contracting (NICEIC).
Guidance for the Design, Construction, Modification and Maintenance of Petrol
Filling Stations – Electrical Installations is published by the Association for Petroleum and Explosives Administration (APEA) and the Institute of Petroleum (IP)
and was produced in consultation with the Health and Safety Executive. It replaces
the electrical content of HSE Guidance Note HS(G)41 Petrol filling stations – Construction and operation. The new guidance adopts a risk-based approach to electrical safety at petrol filling stations and describes various control measures and
270
Handbook of Electrical Installation Practice
procedures representative of good practice. This list is not comprehensive but it
covers the principal legislation affecting electrical work in the UK. Electrical safety
for transport, aviation and marine applications is outside the scope of this book.
Enforcement authorities
Most of the safety legislation is enforced by the Health and Safety Executive (HSE)
but certain work is delegated by HSE to the local authorities which are, for example,
responsible for enforcing the Offices, Shops and Railway Premises Act and for small
workshops attached to retailers.The local authorities are also responsible for enforcing Part 1 of the Petroleum Consolidation Act which applies to fuel dispensing on
garage forecourts.
The work of the HSE is divided on an industry basis, so an inspector for a given
industry is unlikely to have in-depth electrical knowledge. However, electrical specialist inspectors can be consulted and they often give detailed, electrical safety
advice to a wide range of industries (e.g. from batteries to power stations).
The delegated inspection work is usually handled by local authorities’ Environmental Health Departments whence advice may be obtained. Enforcement of the
Low Voltage Electrical Equipment (Safety) Regulations 1994 is carried out by
the local authorities’ Trading Standards Officers and by the HSE Inspectorate. The
former deal with consumer equipment, i.e. apparatus used in domestic premises, and
the latter with equipment for use at work. The Trading Standards Officers are not
likely to be electrically qualified and so refer suspected apparatus for test and report
to an approved testing laboratory.
The Electricity Safety, Quality and Continuity Regulations are enforced by the
DTI’s Engineering Inspectorate from whom advice may be obtained.
Although the enforcement authorities provide some advice, they are limited by
the statutes which brought them into existence and which define their powers, and
also by their financial and manpower resources. Independent safety consultants are
available to provide more detailed advice and their help should always be sought
in the event of a prosecution by the enforcement authorities.
Application of the regulations
Some authorities have issued guidance notes on the regulations to enable the public
to better understand them. One of the most helpful of these publications is HSE’s
Memorandum of Guidance on the Electricity at Work Regulations 1989. See also
DTI’s Guide to the Low Voltage Electrical Equipment (Safety) Regulations 1994 and
HSE’s Essentials of Health and Safety at Work which deals, inter alia, with the
Regulations listed above under ‘Other legislation’.
HSE have also issued an Approved Code of Practice on the Construction (Design
and Management) Regulations 1994 entitled Managing construction for health and
safety. The Regulations came into force on 31 March 1995. These Regulations are
of major importance to all construction industry contractors including electrical contractors who need to understand them and implement their provisions. Every contractor should acquire the IEE’s Guidance Notes on BS 7671 which are published
as separate documents and entitled:
Electrical Safety
(1)
(2)
(3)
(4)
(5)
(6)
(7)
271
Inspection and testing
Isolation and switching
Selection and erection of equipment
Protection against fire
Protection against electric shock
Protection against over currents
Special installations and locations.
Also, the On-site guide which deals with small installations (up to 100 A, singlephase). Regulations and the DTI guide are obtainable from HMSO. HSE publications are available from HSE Books, PO Box 1999, Sudbury, Suffolk CO10 6FS
or from some bookstores. IEE publications are obtainable from the Institution of
Electrical Engineers, PO Box 96, Stevenage, Herts SG1 2SD.
The Construction (Design & Management) Regulations 1994
These Regulations detail and extend the requirements of the Health and Safety at
Work etc. Act 1974 for the construction industry. The onus for safety begins with
the designer who has to provide a design which can be safely constructed. He has
to co-operate with the planning supervisor, who can be the principal contractor, to
ensure safety during construction.
The planning supervisor has to prepare a health and safety plan, incorporating
safety rules, prior to the start of the work on site, and ensure that it is understood
by the principal contractor who has to implement it. The planning supervisor has to
maintain a health and safety file.
The principal contractor has overall responsibility for safety and to ensure this
gives directions to sub-contractors and sees that they co-operate with each other.
On a development, the electrical contractor is usually a sub-contractor but would
be the principal contractor for a rewiring project, for example, where no builder is
employed.
Safety policy statement
Under Section 2(3) of the HSW Act, an employer has to prepare a statement of his
health and safety at work policy and the organisation and arrangements for carrying it out. This entails the same risk assessment which is required in the 1992 Management of Health and Safety at Work Regulations. In both cases, reassessments are
required to cater for hazard changes consequent, for example, on new business practices or the introduction of new equipment. If the safety policy statement is written
on the form provided for the purpose by HSE, entitled ‘Our health and safety policy
statement’, it should be sufficiently comprehensive to satisfy the Act and the
Regulations. HSE have a number of guidance booklets which are helpful to the
compiler of the statement.
Safety rules
A copy of the firm’s safety rules should be attached to and be part of the statement.
During the required safety training, employees should be made conversant with
272
Handbook of Electrical Installation Practice
these rules and provided with a personal copy of them. Electrical contractors are
confronted with two types of hazard: those endemic to the trade and those due to
site conditions. The safety rules should cater for the former. To provide for the latter,
which are mainly the responsibility of the occupier or main contractor on construction sites, the contractor’s safety officer should ascertain what the hazards are
and agree the appropriate safety precautions with the occupier/main contractor and
then instruct his workforce.
Although senior management bears the ultimate responsibility for safety, the
senior executive concerned should not concoct the rules himself and then impose
them on the employees. He would be better advised to chair a small committee,
comprising the safety officer, electrical engineer, an electrician (preferably the
EETPU shop steward) and in the case of large concerns with their own electrical
installation and maintenance staff, technologists familiar with the processes and
associated hazards. It is also suggested that a manager from the production team
sits on the committee in order to minimise potential conflicts between safety and
production output.
The rules should start by stating the objective, which is to have an electrical installation which is safely constructed, maintained and used and which complies with the
law, and that those concerned are suitably trained to avoid danger and injury. The
rules should also state who is responsible for safety and safety training and
the duties of employees and others working in the premises, self-employed or
employed by someone else, to observe them. It may be convenient to sectionalise
the content by grouping the rules which apply to users, on the one hand, and to
those responsible for installation and maintenance, on the other. The rules should
cover inter alia:
(1) The duty to know and observe any relevant statutory regulations such as those
already listed and the non-statutory BS 7671 requirements
(2) Prohibition of the use of defective equipment and its removal from duty
(3) Reporting accidents
(3) Training in artificial resuscitation
(5) Appointment of persons authorised to issue permits to work (PTW)
(6) Prohibition of ‘live’ working, unless strictly controlled
(7) The 110 V, centre tapped to earth (CTE) system for portable tools
(8) Planned preventive (PP) maintenance
(9) Use of suitable and adequate gloves, boots, mats, screens, insulated tools, etc.
(10) Safe test procedures
(11) Suitable and appropriate test instruments
(12) Properly written and controlled permits to work
(13) Emergency procedures.
Guidance on safe working practices from the HSE (Booklet HS(G)85) covers some
of the above requirements. The above list covers items common to contracting work
and factory installations but does not purport to be comprehensive.Additional items
will be needed to cater for non-electrical hazards and hazards peculiar to the
processes and type of work involved in a particular organisation.
Electrical Safety
273
SAFE DESIGN AND INSTALLATION
Section 6 of the Health and Safety at Work etc. Act refers to articles for use at work
but in the definitions ‘article’ means any plant or component of such plant. ‘Plant’
is defined as any machinery, equipment or appliance. So, it would seem that
electrical installations are covered by the term ‘article for use at work’ and are,
therefore, subject to section 6 which imposes onerous requirements on designers
and installers. They are required to design and construct the installation so that it
is safe at all times, test to prove its safety and provide the user with adequate information so that he can use it without risks to safety and health. There is also an obligation to ensure that components supplied for use in the installation are safe and
to warn the user should any hazardous defect be discovered subsequently in any of
them.
Conditions of use
In order to comply with the design safety requirements, the designer must ascertain
the conditions of use and foreseeable misuse and should consider the following:
Environmental conditions
Is the installation or any part of it subject to damp, dusty, corrosive or flammable
atmospheres, extremes of temperature, high altitude, vibration, impact, infestation
by mould growth or insects, any type of radiation, wind, lightning, floods, earthquake
or situated in a subsidence or high fire risk location? If so, the installation must be
designed to be safe under these conditions.
Other legal requirements
Adverse environmental conditions may be the subject of other legislation so the
designer must have regard to them. For example, Regulation 6 of the EAW Regulations has a similar list of adverse environmental conditions for which the equipment has to be suitable in order to avoid danger. The designer must also be aware
of non-electrical regulations which may have electrical requirements such as the
Highly Flammable Liquids and Liquified Petroleum Gases Regulations 1972. In
Regulation 10(8), for example, axial flow fan motors in exhaust ducts are prohibited. The designer should, therefore, specify a centrifugal fan with an external motor.
Human factors
Human factors also have to be considered. Is the installation likely to be subject to
rough use or vandalism or does it have to be suitable for use by unskilled or handicapped persons or made child-proof? It must be as safe as is practicable. Proper
training of the workforce is most important in this respect.
Suitability of equipment
When specifying the equipment for the installation, the designer has to ensure its
suitability and for this purpose should nominate the relevant standard (BS, IEC,
CENELEC, etc.) and/or detail the appropriate safety requirements, e.g. equipment
for use in a flammable atmosphere must be of the explosion protected type and
274
Handbook of Electrical Installation Practice
comply with the appropriate standard or be intrinsically safe, purged or pressurised.
It must also be suitable for the prospective fault level. See Chapters 1, 4 and 5. The
contractor, or whoever is responsible for the construction of the installation, is also
responsible for the safety of the equipment which he supplies and for ensuring that
it has been tested to prove its safety. If there is any doubt about this, the installer
should obtain copies of the test certificates from the maker or an assurance that the
equipment has been tested and meets the requirements of section 6 of the HSW
Act or he will have to test it himself.
Safe construction
Adequate supervision of the installation work is essential to comply with the
requirement that the installation shall be constructed so as to be safe.The completed
installation must be tested to prove its safety. UK installations, designed and constructed and tested in accordance with the BS 7671 should meet the requirements
of section 6 and should also satisfy the employer’s obligation under Regulation 4 of
the EAW, to provide a safe electrical installation.
User’s instructions
There is a requirement in section 6 of the HSW Act to provide adequate information about the installation, so that it can be used safely. The installer needs to consider this requirement carefully and will probably find that, except for the simplest
installations, it will be necessary to provide a schematic and/or wiring diagram and
to label all controls so that the user can identify them on the drawing. For most
items of equipment, there will be a maker’s instruction leaflet or manual, and in
most cases it will only be necessary to hand this to the user. Supplementary instructions may be necessary sometimes, e.g. where sequence switching is used. The user
should be notified of the need for periodic inspection, testing and repair, in accordance with the BS 7671, to fulfil the requirement to maintain the installation in a
safe condition.
Alterations
If there are alterations in the conditions of use, e.g. a change in a manufacturing
process whereby a flammable solvent is introduced, then corresponding alterations
are required to the electrical installation to preserve its safety. Any part of the installation, located within the flammable zone, would either have to be removed, explosion protected, pressurised, purged or made intrinsically safe. Procedures should
also exist to cater for changes of personnel.
MAINTENANCE
There is a provision in section 2 of the HSW Act and in Regulation 4 of the EAW
which imposes a duty on employers to provide and maintain plant in a safe condition and without risks to health, so maintenance of the installation must be adequate to ensure it remains safe. The ‘fire party’ system of maintenance, whereby the
repair party rush from one breakdown to the next and effect hasty repairs, does not
satisfy the requirement. Planned preventive maintenance is the best way not only
Electrical Safety
275
of meeting the legal requirements but also of limiting breakdowns. It is suggested
that all electrical equipment should be numbered and listed in a register and the
frequency of maintenance decided for each item. There should be a schedule of
inspection for the maintenance staff so that each item is regularly inspected and
tested and any necessary maintenance and/or repairs effected. A record of the work
done and the test results provide the data which enables the maintenance engineer
to decide on any changes needed in the frequency of inspection, maintenance
procedure or replacement time for a component or item. Planned maintenance is
particularly important for portable equipment since it is very often hand-held and
it is generally used in more arduous conditions.
TRAINING AND SYSTEMS OF WORK
Under section 2 of the HSW Act, there is an employer’s duty to provide a safe
system of work and to train and supervise his employees and so ensure their safety,
health and welfare. There is also a requirement in Regulation 16 of the EAW which
limits dangerous work to competent persons.
There is an established system of training in the electrical industry for electricians, whereby the apprentice is trained in both practical and theoretical work
before becoming a skilled electrician. However, training in safe working practices
should always be part of this system.
‘Danger’ in the electrical context refers, mainly, to electric shock or burn from
contact with ‘live’ conductors, so work which can be carried out on a ‘dead’ installation is electrically safe. Most new installation work is in this category. Where,
however, extensions or alterations to a ‘live’ installation are required then danger
arises at the interface between the ‘live’ and ‘dead’ parts of the installation; for
example, a new circuit fed from an existing distribution board with bare busbars. In
this case, EAW Regulation 14 requires adequate precautions to be taken to prevent
danger, and a competent person would have to isolate and lock off the supply to
the board so that the new circuit could be connected safely.
Regulation 14 permits ‘live’ working up to 1000 V but only in exceptional circumstances and when suitable precautions are taken to prevent injury. The suitable
precautions would include the use of insulating stands, screens, boots, gloves, tools,
instruments etc., and where the danger merits it, the presence of a second person
to render assistance in the event of an accident. The precautions must prevent electric shock from direct contact with ‘live’ parts and must also prevent an accidental
short-circuit which could cause arcing and burn injuries to the operator. It should
be emphasised that an important precaution is that the persons carrying out the
work have been trained specifically for that type of work.
Testing
Some testing, such as fault finding, often requires working ‘live’ and under pressure
to find the fault, repair it and get the system back into operation as soon as possible. The urgency, however, does not justify relaxing safety precautions and the
employer should have already assessed the risks of such work and have devised a
safe system of work for it. As it is not likely that he can anticipate exactly the degree
276
Handbook of Electrical Installation Practice
of danger which might arise, he would probably be well advised to stipulate that
accompanied working is required and that the protective safety equipment has to
be readily available for immediate use. How and when it is used is a matter for decision by the person in charge of the work, who could decide, for example, that to
check the voltage at an isolating switch, it is sufficient to use shrouded probes on
the instrument leads with HBC fuse protection but it is not safe to do the same thing
on the back panel inside a deep cubicle with ‘live’ components on the side panels.
In this case, temporary insulating screens would be needed for each side panel.
During ‘live’ testing at potentially dangerous voltages, non-authorised persons
should be excluded from the test site for their own safety and to avoid distracting the test personnel. For this purpose, barriers, with warning notices, should be
provided.
Permits to work
Because of the enhanced danger when working on h.v. systems, it is necessary to
take additional precautions to minimise the hazard. In the electricity supply industry (ESI) where there is a great deal of such work, the safety precautions are set
out in their safety rules which include prescribed forms for limitations of access,
sanctions for test and permits to work. In those plants where there is h.v. equipment,
the permit to work system should be employed and the ESI safety rules observed
whenever the h.v. apparatus is inspected, tested and overhauled and maintained.
Appropriate guidance is available in BS 6626: 1985 and BS 6867: 1987, which are
the codes of practice for the maintenance of h.v. switchgear and controlgear. The
use of permits to work is also advocated for the more complex l.v. switchboards and
control panels where, for example, they have more than one supply source and/or
have double busbars and/or section switches.
The permits to work should be in triplicate and numbered. One copy is for the
person in charge of the work on site, one copy is for the authorised engineer and
the third is the office record.
For maintenance work the procedure is for the authorised engineer to:
(1) Perform the necessary switching operations, apply the temporary earths and
where applicable, tape off the safe zone, erect warning signs and prove the
equipment worked on to be dead
(2) Record the details on the permit and illustrate with a diagram if needed
(3) Instruct the workers on the site and obtain the supervisor’s signature in the
receipt section of the permit which acknowledges that he understands what has
to be done and which parts of the apparatus are ‘dead’ and safe to work on and
which are not. The supervisor retains one copy of the permit.
On completion of the work, the supervisor withdraws his labour, instruments, tools
and materials, signs the permit in the clearance section and returns it to the authorised engineer who cancels the permit and then removes the tape, warning signs and
safety earths, and restores the supply.
It is advisable to appoint more than one authorised engineer so that there is
always cover available to exercise the necessary authority where ‘live’ working is
required and/or permits to work have to be issued.
Electrical Safety
277
Other safe systems of work on l.v. systems
Apart from permits to work, there are a number of other safety precautions which
can be employed. For example, an electrician may want to work on a circuit fed
from a remote source of supply. If the circuit is fed from an isolator, switch or switchfuse, he should padlock the switch in the ‘off’ position and pocket the key so that
no-one else can operate the switch. He should also put a caution notice on the
switchgear so that others will know the circuit is out of operation.
For multiple circuits fed from distribution fuseboards, he should at least remove
and pocket the fuses to isolate the relevant circuit and again, display a warning
notice. It is also advisable to padlock the door but if this is done, the warning notice
should indicate the whereabouts of the electrician in case the fuses of another circuit
operate.
If there is no provision for locking off, some switches which are interlocked with
the hinged cover can be switched off and the cover tied open to prevent the switch
being closed. Again, a warning notice is necessary and in this case, barriers are
required to keep people out of reach of the exposed ‘live’ parts. Some modern
switchboards can be used with lockable, blanking pieces inserted in a fuse carrier
to prevent access to a fuseway.
Less elaborate precautions may be taken where the control switchgear is at hand
and within sight of the electrician.
Electricians should be wary of relying on single-pole isolation in the case of lighting circuits, as Fig. 11.1 shows. If an electrician opens the switch in room B to work
on the lighting point and disconnects the looped-in neutral, operating the switch in
Fig. 11.1 Remove fuse for safe isolation of lighting points.
278
Handbook of Electrical Installation Practice
room C would make the broken return conductor ‘live’ at 240 V to the neutral and
to the protective conductor. If the line conductor is looped at the ceiling rose instead
of at the switch, as shown in room C, there is an additional risk from the ‘live’ loopin terminal.
All these precautions are necessary to comply with EAW Regulation 13
which calls for adequate precautions to be taken to prevent any conductor or
apparatus from being accidentally electrically charged when persons are working
on it.
TOOLS
Electricians use a range of portable tools which can be obtained for operation on
mains voltage or 110 V. Portable mains voltage apparatus is more likely to cause
electric shock accidents than fixed apparatus because it is often hand-held and is
also used in more arduous environments. Although not mandatory, it is advisable
to counter this risk by using 110 V portable tools, supplied from a circuit which eliminates the possibility of a dangerous electric shock. This is done by transforming the
mains voltage supply to 110 V single- or three-phase and earthing the mid-point or
star point of the secondary winding. See Chapter 5. As this system has been successful in virtually eliminating portable apparatus shock accidents on building sites,
it is being adopted to an increasing extent in factories where the transformers are
located at appropriate load centres and feed a 110 V distribution system of socket
outlets.
Confined, conductive and/or wet locations enhance the risk of electric shock and
in these places additional precautions are needed. The risk can be avoided altogether by using pneumatic, battery or hydraulic tools but if these are not available
and 110 V tools have to be used, further protection can be afforded by using Class
II tools (double or all insulated) and/or by protecting the circuit with a residual
current device (rcd), with a rated residual operating current of not more than
30 mA. Some locations require voltages of 25 V, or lower, to be used.
As tungsten filament lamps are readily available for very low voltages, handlamps should be supplied, at not more than 50 V, from a single-phase transformer
with the secondary winding centre tapped to earth or from an unearthed safety extra
low voltage (SELV) circuit.
Electric arc welding sets should be fitted with an l.v. device so that the electrode holder is never energised at a voltage exceeding the maximum arc voltage of
about 40 V (Fig. 11.2). On open circuit, the control circuit transformer (1) provides
a signal voltage of about 20 V on the electrode (2). To start welding, the operator
touches the workpiece (3) with the electrode, thus completing the control circuit.
The contactor (4) closes and completes the welding circuit, enabling the arc to
be struck. Breaking the arc de-energises the contactor control circuit and the
contactor opens and the signal voltage is restored by the auxiliary contacts (5) on
the contactor.
Operators working in these potentially dangerous locations, i.e. confined, conductive and/or wet places, should be accompanied.
Electrical Safety
279
Fig. 11.2 Low voltage device.
BURIED CABLES
Over half the accidents in the construction industry are burn injuries, from the
arcing consequent on damage to underground cables. Damage occurs during excavation work, usually from pneumatic drills and hammers but also from picks, forks,
the steel rods used in bar-holing and even from the sharp edges of shovels.
When excavating trenches for cable laying, the contractor is obliged to take adequate precautions to avoid danger from cables already there, for compliance with
section 2 of the HSW Act and Regulation 14 of the EAW Regulations. The precautions are detailed in HSE publication HS(G)47 Avoidance of danger from underground services and are summarised below.
Before excavating:
(1) Obtain from the local authority the maps of buried services in the highway
including cables. If, however, this information is not available or incomplete,
the contractor will have to get it from the service owners.
Note: Under the New Roads and Street Works Act 1991 local authorities have
to keep a register of information of underground services in the highway and
are supposed to co-ordinate the activities of excavators.
(2) On private property, contact the site owner for the information.
(3) Mark the ground surface to indicate the locations of the buried services.
(4) Use a cable and pipe locator as a further and more precise check having regard
to the limitations of the instrument. Unloaded cables are more difficult to
detect so lack of a reading does not necessarily mean that there is no cable
there.
Excavating:
(5) Do not use power tools within 0.5 m of any indicated cable except with short
bits to break up hard surfaces.
(6) Dig trial holes to expose the cable(s) using careful manual methods.
280
Handbook of Electrical Installation Practice
(7) Use the cable locator as each layer of material is removed.
(8) Where existing cables clash with the excavation, expose them, using careful
hand methods, working from the trial holes along the route.
(9) Support the exposed cables where necessary and protect them against damage
while they are exposed.
(10) Before backfilling, contact the cable owner and agree on the procedure for
protecting his cables.
(11) The contractor has a duty to safeguard others, apart from his own employees,
and should therefore take suitable precautions when laying the new cables, to
avoid creating a trap for unwary future excavators.
(12) If the location is likely to be subject to frequent re-excavation, as on developing estates, all possible precautions should be taken, i.e. armoured cables
should be used, protected by cable tiles and further protected by marker tape.
(13) At other locations, less elaborate precautions are needed but unarmoured
cables should always be protected by cable tiles.
(14) The location of the cable should be shown on the installation ‘as fitted’ drawing
and handed to the customer and to the local authority on completion of the
work.
Apart from underground locations, cables are concealed elsewhere, such as in wall
chases which are subsequently plastered over. Such cables could be a shock and/or
burn hazard if damaged, so before drilling or cutting into walls, floors or ceilings,
enquiries should be made as to the location of any wiring and a cable locator used
as a check. Again, when concealing cables in walls, floors and ceilings, their position
should be shown on the record drawings.
OVERHEAD LINES
Every year, overhead lines are the cause of a number of electrocutions in the construction and agricultural industries. A typical case might be when the victims are
handling loads suspended from cranes and are electrocuted when the crane jibs
touch an overhead line conductor and the victim becomes a conductor between the
line and earth. A similar type of accident occurs when the victim is standing on the
ground and touching the metalwork of a piece of civil engineering plant, such as an
excavator, which becomes live when the jib is accidentally swung into contact with
an overhead line conductor. Most of these accidents occur on construction sites.
When designing the temporary distribution system for a construction site, the
temptation to economise by using an overhead line system should be resisted if
possible and an armoured cable system used instead in accordance with the recommendations of BS 7375: 1991, Code of practice for distribution of electricity on
construction and building sites. See also Chapter 5.
There may be, however, special circumstances which justify an overhead line distribution system. An example might be a chemical works on a large site with considerable distances between the load centres and where it is economical to install
the permanent distribution system for use both during construction and subsequently after completion. In these circumstances, the design and construction should
Electrical Safety
281
Fig. 11.3. Fencing-off overhead lines on construction sites.
meet the requirements of the relevant parts of the ESQCR to ensure compliance
with the EAW Regulations and the HSW Act. The contractor is also under the obligation of section 6(1)(c) of the HSW Act to make available adequate information
about any conditions necessary to ensure safety and should, therefore, advise the
occupier, usually the main contractor, of the need for barriers to fence-off the overhead lines as shown in Fig. 11.3 and keep the civil engineering mobile plant at a safe
distance from them. See also HSE Guidance Note GS6, Avoidance of danger from
overhead electrical lines.
ELECTRIC SHOCK
The number of electrocutions (i.e. deaths from electric shock) per annum of people
at work is, fortunately, small and has never yet attained three figures, but electric
shock accidents are common and are frequently accompanied by burn injuries at
the point(s) of contact.
282
Handbook of Electrical Installation Practice
Shock parameters
Electric shock data have been compiled by a number of researchers who have
experimented mainly on animals. Their results are not entirely satisfactory because
of the difficulty of relating animal responses to humans. Some work, up to ‘let go’
current severities, has been carried out on human volunteers and has been useful
but there are still unexplored areas and the data is incomplete. What follows, therefore, is based on present knowledge and logical probability.
The body is a non-linear resistor with an inverse characteristic with respect to the
applied voltage. The resistance varies also with sex, state of health and between individuals. Most of the resistance is in the skin. Under dry conditions, point contacts
and safety extra low voltages, the resistance may be thousands of ohms and there
may be no shock sensation but a wet skin considerably reduces the resistance and
a slight shock may be felt if sufficient current flows between the contact points. The
shock sensation is frequency dependent and is at a maximum at about the mains
frequency of 50 Hz and diminishes at higher or lower frequencies. The shock sensation disappears at frequencies exceeding about 1.0 MHz and also on a ripple-free
d.c. However, contact with a d.c. conductor produces an initial shock as the current
rises from zero to a steady-state value and another when contact is broken and the
current again drops to zero. Any sudden change in current produces a shock sensation, so shocks are experienced from pulsating or oscillating currents but not from
a pure d.c. and not anomalously from very high frequency a.c.
There is a considerable difference in response to body currents between individuals but in general and for mains frequency, i.e. 50 Hz in the UK, the responses to
sustained currents are as follows: 0.5 to 2.0 mA is the threshold of perception with
no deleterious effect or unpleasant sensation. Over 2.0 mA the shock sensation
increases with increases in current from a mild to a painful shock and at about 9.0
mA for a man and 6.0 mA for a woman, it begins to become difficult to break
contact, due to partial muscular paralysis. At 20 mA and over, muscular paralysis
inhibits the ability to ‘let go’ and the victim is liable to become unconscious through
paralysis of the motor nerves. He may stop breathing and/or his heart may stop
beating. At currents in excess of about 50 mA ventricular fibrillation, i.e. uncoordinated operation of the heart valves, may occur and the victim’s chances of
survival are poor as this condition needs immediate specialised treatment.
Time is the other factor in electric shock danger. It is known that considerable
shock currents can be tolerated for a very short time and it is possible to produce
safety curves of shock currents plotted against time. These will be found in BS PD
6519: 1988, Guide to the effects of current passing through the human body, and are
used by the designers of rcds to determine the performance characteristics of their
products.
Harmless momentary shocks, however, can cause accidents because of the involuntary reaction of the victim; for example, a momentary shock can cause the victim
to fall off a ladder and injure himself.
Rescue
To render assistance to a person undergoing an electric shock, a rescuer should
first interrupt the circuit by switching off the supply or pulling out the plug. If he
Electrical Safety
283
can do neither, he should try to break the victim’s contact with the ‘live’ apparatus
by either dragging him clear, using insulating material, e.g. his clothing, gloves, a
rope or plank, or if the ‘live’ apparatus is portable, by pulling it away from him by
the insulating sheath of the cable. On no account should the rescuer touch the
victim’s skin or he may become a victim himself.
Next, if the victim is unconscious, the rescuer should send someone else for
medical help and immediately start artificial resuscitation and keep it up until the
victim revives or medical help arrives and takes over the task.
As electricians are most vulnerable to and suffer from more electrical accidents
than other people, they should be trained in simple resuscitation techniques so that
in an emergency, they can render skilled assistance.
The techniques are described and illustrated on display placards which are available from a number of sources, such as the HSE poster Emergency procedures
for an electric shock casualty. Such placards however, are a poor substitute for the
services of a trained person. Success is dependent on time and it is vital to commence the correct treatment as soon as possible and preferably without the delay
engendered to peruse and absorb the placard’s instructions. There are various resuscitation methods; the most favoured is the mouth-to-mouth method with heart
massage.
PROTECTION FROM ELECTRIC SHOCK
Supply systems
In the UK, the l.v. distribution system, i.e. 400 V three-phase 50 Hz, has a neutral
which is earthed at the source, usually the star point of the secondary winding of
the supply transformer.
The declared voltage was changed in January 1995 to a new EU standard of
400 V three-phase, 230 V single-phase, within the limits of +10% to -6% but the
actual statutory variation permitted in the UK was ±6% and the supply authorities
can maintain the actual voltage within the EU limits without changing present practice and will do so for the present.
In urban areas, most of the systems are TN-S, i.e. separate neutral and protective
conductors, but since the inception of PME (protective multiple earthing of the
neutral) TN-C-S systems are coming into use and superseding the TN-S systems. In
TN-C-S systems the supply authority uses CNE (combined neutral and earth)
cables. The CNE conductor is earthed at several points including the star point
of the transformer. In some rural areas, TT systems are used, having no protective
conductor between the substation and consumer, but the neutral is earthed at
the transformer star point and each consumer has to provide an independent earth
electrode for his own installation. These systems are being replaced by TN-C-S
systems.
However, irrespective of the supply, the consumer’s installation relies on the same
safety principle for protection against electric shock, which is that ‘live’ conductors,
i.e. phases and neutral, are insulated from earth and from each other and that touchable metal parts are earthed. This ensures that in the event of an earth fault, there
will be a minimum potential difference between the metalwork and any other
284
Handbook of Electrical Installation Practice
conductive metalwork in the vicinity at earth potential, thus minimising the possibility of an electric shock. A further safety precaution is provided by the automatic
operation of the fuse or circuit-breaker, rendering the faulty circuit dead.
Earth faults
In the event of an earth fault, the two main safety requirements are (1) to protect
persons from electric shock and burns and (2) to minimise damage to the installation and avoid a fire.
When a fault occurs, the metalwork of the installation attains a potential with
respect to the star point of the transformer and the main body of the earth to which
it is connected. These potentials are not the same because of the value of the volt
drop, due to the resistance of the earthing electrodes of the star point, at the substation and the equipotential bonding at the fault location. The potential attained
by the metalwork is dependent on the volt drops in the circuit between the supply
transformer and the fault and these are proportional to the circuit impedance.
Figures 11.4 and 11.6 show typical circuits for TN-S and TN-C-S systems and Figs
11.5 and 11.7 the corresponding impedance diagrams.
If, for example, the line impedance, i.e. Z1 + Z2, is the same as the return
impedance, i.e. the resultant of the series and parallel impedances between the
fault and the star point, then the potential on the case of the equipment will be half
the supply voltage, say 115 V. If, however, the line impedance is greater than the
return impedance, the case potential will be less and vice versa. The shock voltage
should be only a fraction of the case potential and is represented by the volt
drop between the equipment case and the building steelwork. This volt drop is
proportional to the impedance of Z5 and ZM in parallel. The determining factor is
Z5 which should be a fraction of an ohm, whereas ZM will be in excess of the
asymptotic value of 650 W. Provided that the equipotential bonding, the earthing
contacts of the plug and socket and the several connections are making effective
contact, the value of Z5 should be low and the corresponding shock voltage
harmless.
If the appliance were to lose its protective conductor, however, the case would
attain a potential approaching that of the supply and the victim would receive a
dangerous shock.
The shock duration and damage to the installation, consequent on the fault, are
dependent on the operation of the overcurrent protective device, fuse or circuitbreaker, which in turn is dependent on the value of the earth loop impedance. For
example, the earth loop impedance at the socket-outlet in Fig. 11.4 consists of the
sum of the impedances of the phase conductor from the socket to the transformer,
the source impedance and the impedance of the earth return, made up of the cable
armour and/or metal sheath in parallel with the impedance of the ground and
bonded metalwork to the earth terminal and thence to the socket outlet, i.e. Z2 +
Z1 + ZS + the impedance of Z6 in parallel with Z7, Z8, Z9, and Z10 + Z5. The actual
earth loop impedance is slightly less because ZL + Z3 + Z4 is in parallel with Z2 + Z1
+ ZS and ZM is in parallel with Z5.
If an earth fault occurs at the socket-outlet, the loop impedance must be low
enough to ensure the distribution board fuse will interrupt in not more than 0.40
Electrical Safety
285
Fig. 11.4 TN-S system (using the notation outlined in Fig. 11.5).
seconds. Where, however, it is not possible to attain a sufficiently low earth fault
loop impedance, the interruption time may be increased to a maximum of 5 seconds
so long as additional bonding is provided to ensure that, in the event of an earth
fault, no dangerous potential differences can occur between items of touchable metalwork within the equipotential zone. See BS 7671, Regulations 413–02–13 to 16.
To determine the earth loop impedance, the usual practice is to ignore the fault
impedance (which is unknown anyway) and the parallel circuits referred to in the
preceding paragraph, and use the reading of the earth loop impedance tester for
existing installations, and for new installations obtain the earth loop impedance
figure, at the intake, from the supply authority and add the calculated value for the
internal circuit.
It is evident that as the rating of the protective fuse or circuit-breaker increases,
the permissible value of the earth loop impedance, to ensure operation in the event
of a fault, decreases. The other factor to be taken into account is the time/current
operating characteristics of the fuse or circuit-breaker. So the earth loop impedance
286
Handbook of Electrical Installation Practice
Fig .11.5 TN-S system impedance diagram:
ZS = source; Z1 = source phase to main switch; Z2 = main switch to appliance;
ZL = load; Z3 = appliance neutral to main switch; Z4 = main switch to neutral to
source; Z5 = appliance case to earth terminal; Z6 = earth terminal to source;
ZF = fault; ZM = victim; Z7 = victim to central heating to source*; Z8 = victim to
water pipe to source*; Z9 = victim to gas pipe to source*; Z10 victim to building
steelwork to source*. (*Through the ground.)
must be low enough to ensure that in the event of an earth fault the protective
device operates quickly.
The maximum disconnection time should, ideally, ensure circuit interruption
before the victim suffers a harmful shock. Taking the worst case, a 230 V shock and
a body resistance of say 1000 W, the shock current is 230 mA and the curve in BS
PD 6519 would require a disconnection time of about 30 ms. However, 230 V shocks
due to earth faults are unlikely, so for most applications a much longer disconnection time is compatible with safety and the time/current operating characteristics of
conventional fuses and circuit-breakers (Table 11.1).
The required earth loop impedance value may be unattainable for heavy current
circuits exceeding about 300 A and in these cases it is necessary to use earth leakage
protection. A residual tripping current value should be selected to avoid nuisance
tripping, complying with BS 7671, whereby the product of the earth loop impedance
and the residual tripping current does not exceed 50. A time delay may be employed
to avoid tripping on transients but the tripping time should not exceed the values
in Table 11.1.
The required earth loop impedance may also not be attainable where TT systems
are used, particularly in rocky areas and other high impedance ground conditions.
Again, earth leakage protection is necessary, as the high earth loop impedances
usually found in these conditions preclude protection by overcurrent devices. Only
residual current-operated devices should be used as BS 7671 has been amended to
omit the use of the fault voltage operated devices with effect from 1 January 1986.
Electrical Safety
Fig. 11.6 TN-C-S system (using the notation outlined in Fig. 11.7).
Table 11.1 Maximum disconnection time for electric shock protection at
mains voltage.
Note: Abnormal conditions exist where there is an increased risk of electric shock as
in confined, conductive or wet locations.
287
288
Handbook of Electrical Installation Practice
Fig. 11.7 TN-C-S system impedance diagram:
ZS = source; Z1 = source phase to main switch; Z2 = main switch to appliance;
ZL = load; Z3 = appliance neutral to main switch; Z4 = main switch to neutral to
source; ZF = fault; Z5 = appliance case to CNE terminal; ZM = victim; Z7 = victim
to central heating to ZE1, ZE2, ZE3 to source*; Z8 = victim to water pipe to ZE1, ZE2,
ZE3 to source*; Z9 = victim to gas pipe to ZE1, ZE2, ZE3 to source*; Z10 victim to
building steelwork to ZE1, ZE2, ZE3 to source*. (*Through the ground.)
The maximum permissible disconnection times in Table 11.1 include those recommended in BS 7671 and are determined by the degree of risk. For example, a
fixed installation is unlikely to lose its earth connection completely and the fault
potential on the metalwork is usually substantially less than 230 V. Moreover, the
metalwork is not being constantly handled so the permissible disconnecting times
can be longer. Portable equipment, however, connected to the supply via a flexible
cable, is more likely to lose its earth connection and is subject to more handling, so
a shorter disconnecting time is required.
As a safeguard against the simultaneous occurrence of an earth fault and loss of
earth continuity which sometimes occurs, for example, when the protective conductor is detached from its terminal in the plug and touches the line terminal, sensitive earth leakage protection is necessary.An RCD, tripping on earth fault currents
through the body down to about 30 mA, should be used (Fig. 11.8).
To safeguard Class I portable equipment against losing its earth connection, circulating current earth monitoring protection may be employed. The circuit is shown
in Fig. 11.9. An open-circuit in the pilot or protective conductor of the flexible cable,
connecting the equipment to the monitoring unit, trips the circuit-breaker or contactor and cuts off the supply to the equipment. The diode and slugged relay are
used on some designs to guard against a short-circuit between the protective and
pilot conductors, which might occur if the flexible cable is damaged. The slugged
relay will not remain closed on a.c.
The protection is limited to the circuit shown, i.e. between the monitoring unit
and the portable equipment, and does not cover a loss of earth continuity between
the supply transformer star point and the monitor.
Electrical Safety
289
Fig. 11.8 Sensitive residual current device protection.
Fig. 11.9 (a) Circulating current earth monitoring protection; (b) with slugged relay and
diode in the apparatus protected.
This type of protection is not as popular as protection by RCDs, mainly because
the plug and socket need an extra way to cater for the pilot conductor. If one monitoring unit is used to control a number of socket-outlets, it is necessary to provide
for the pilot circuit to be maintained at each unused socket-outlet.
It is possible to obtain a combined earth leakage and circulating current monitoring device which can be employed where additional safety precautions are
needed to cater for dangerous conditions. Two examples are the control of mains
voltage supplies to the wet grinding machines used on terrazzo floors, and to the
steam/water pressure cleaners used to prepare vehicles for plating inspection and/or
corrosion resistance treatment and for a variety of other uses in industry and agriculture where wet conditions enhance the shock danger.
An alternative safeguard is to use Class II equipment which is available in two
categories: double insulated and all insulated. As it is unearthed, enclosed ventilated
Class II equipment should never be used in wet environments or where there is conductive dust. IP54 or IP6X enclosures are necessary. Class II equipment has a very
290
Handbook of Electrical Installation Practice
good record and there have been practically no shock accidents from the apparatus
itself, but at mains voltage there remains the hazard from a damaged flexible cable.
The use of equipment operating at a lower voltage is a better way of reducing the
shock hazard, and for portable tools and other low power apparatus, 110 V, 50 V or
25 V is recommended, as described in the ‘Tools’ section earlier in this chapter.
There is also another 1.v. system which is used in conjunction with Class III
(unearthed functionally insulated) equipment. In the UK it is used for special applications where an earthed system would be technically impracticable, such as supplies to wire feeding devices on MIG/MAG welding sets. The system comprises a
safety transformer which feeds the Class III equipment at separated extra low
voltage (SELV).
A somewhat similar system is known as ‘safety by separation’. In this case, the
safety isolating transformer or equivalent provides an unearthed supply of up to
500 V to the equipment. There has to be good insulation between live parts and
earth, flexible cables have to be visible wherever they are vulnerable to damage and
there must be no contact between the exposed metalwork of the separated circuit
and the protective conductor and exposed conductive parts of other circuits. If more
than one piece of equipment is supplied, the exposed metalwork has to be bonded
together by means of an equipotential bonding conductor in the flexible cables.
Some of these requirements make the system impracticable for use in most circumstances but it could have applications for certain temporary installations such
as location lighting and power supplies, fed from mobile generators, used by television and film companies and the rescue services and where it may be difficult to
arrange for satisfactory earthing. Other safety precautions are outlined below.
Safety by position
Bare conductors may be made safe by locating them out of reach. Overhead lines
and trolley wires are examples. In the latter case, however, it should be recognised
that maintenance personnel may need access to various high-level services or may
need to carry out building repairs or redecoration in the vicinity of the trolley wires.
To safeguard them, temporary portable screens would have to be provided or the
trolley wires made ‘dead’. This could be a nuisance and/or affect production if it
occurs frequently, so for these situations the exposed trolley wires should be
replaced by the enclosed type where access to the conductors is through a slot
designed to prevent anyone touching them.
Interlocking
Selection of the most appropriate system is dependent on the degree of risk, type
of personnel to be protected, efficiency and facilities for maintenance and testing.
The following examples indicate the various systems available.
Entry into an h.v. switchgear cubicle is a high-risk situation and in this case a
trapped key system is appropriate to operate the interlock between the external
remote isolator and the cubicle door.
Trapped key systems are also useful when non-electrical production personnel
need access to equipment where there is an electrical shock hazard. For example,
Electrical Safety
291
poultry stunning cabinets, particularly the wet variety, have to be accessible for
cleaning. If the cabinet is within an enclosure, the access door can be interlocked
with the isolator in the same way as the switchgear cubicle, thus making it impossible for operatives to gain access when the stunner is energised.
If it is necessary to ‘lock off’ a number of isolators to make a system safe to work
on, this should be done by an authorised competent person. He then puts the keys
in the key safe, locks it and retains its key or lodges it in a secure place, accessible
only to him or other responsible persons. None of the isolators can then be unlocked
and operated until a responsible person has satisfied himself that it is safe to do so
and has unlocked the key safe and made the isolators’ padlock keys available.
Multiple padlocking is appropriate when there is only one isolator controlling a
scattered system which is made ‘dead’ so that a number of electricians can work on
it simultaneously. The isolator is secured in the ‘off’ position by a caliper-shaped
device with a number of holes in it, for the insertion of a padlock by each operative. Each operative has to unlock and remove his own padlock before the device
can be withdrawn and the isolator reclosed.
Production line testing of domestic, electrical product, part-assemblies is a
common application of interlocking using interlock switches. In these cases, the test
personnel are likely to be relatively unskilled and are not competent persons and
so they must not be able to touch exposed parts when ‘live’ or have access to ‘live’
terminals, yet the testing must be simple and quick to avoid disrupting production
efficiency. If the test piece has exposed ‘live’ conductors, the testing should take
place inside an interlocked box or enclosure. The operator inserts the test piece
which is automatically connected or is connected by the operator who then
closes the door or lid and, in so doing, automatically operates the test supply switch
which is interlocked with it. The switch is ‘on’ only when the door or lid is closed.
The interlock switch must be of the ‘fail safe’ type, as shown in Fig. 11.10, where
the circuit is made by the operation of the spring but is positively broken by the
Fig. 11.10 Interlocked enclosure for production line testing.
292
Handbook of Electrical Installation Practice
actuator. Care is required to ensure there will be no mechanical failure of the
cam plunger mechanism and that failure is limited to a spring breakage or loss
of temper. It must not be possible to defeat the interlock without the use of tools.
Positive make switches are not suitable because the interlock can be defeated by
operating the switch plunger and, moreover, such a switch can fail to danger if the
spring breaks. Two interlock switches, connected in series, are sometimes used as an
additional precaution.
Test pieces, having no exposed conductors, apart from the ends of the leads to be
connected, can be tested on the bench. In this case, the test supply terminals are
enclosed in a box with a hinged lid. When the lid is open, an integral switch opens
the supply circuit, enabling the leads to be connected to the supply terminals which
are usually spring loaded clamps. Closing the lid automatically operates the integral
switch and connects the equipment to the supply. Again, a positive break interlock
switch must be used with a suitable actuating mechanism, to prevent defeat of the
interlock feature and to ensure mechanical reliability.
Interlock switches are often used on doors and the removable panels of control
gear where access is required for maintenance and test purposes by electrically
skilled persons. The necessity for this is dubious as such panels should not be openable without the use of a key or tools and so access is restricted to authorised and
competent persons who are well aware of the hazards and who will have to defeat
the interlock if they need to carry out ‘live’ testing. However, if such switches are
used, they should preferably be of the ‘fail safe’, positive break type and be provided with a ‘lock off’ facility which can be used if the switch is in a position where
it could be accidentally operated during maintenance or testing.
Other systems
There are two earth free systems called ‘Protection by non-conducting location’ and
‘Protection by earth free local equipotential bonding’, which depend on their locations being earth free. As it is virtually impossible to guarantee that an earth free
location is always likely to remain so, there is not much scope for these systems in
the UK except for special applications such as the testing of radio and television
equipment. However, even then additional precautions are still necessary.
For electronic equipment encased in earthed metal, there is a special highresistance earthing system for testing, designed to eliminate the shock hazard when
a ‘live’ conductor and the earthed metal case are both touched. The system comprises a safety isolating transformer, feeding a socket-outlet via a circuit-breaker.
The test piece is connected to the socket-outlet. A centre tapped high resistance is
connected across the circuit-breaker output terminals. The centre point is earthed
via a rectifier bridge and relay coil. If either pole of the test circuit is touched when
in contact with the metal case, the fault current is limited by the high resistance to
say 0.50 mA which, although insufficient to produce a shock, is enough to operate
the sensitive relay and trip the circuit-breaker (Fig. 11.11).
The principal application of energy limitation is in h.v. circuits used in: (1)
TIG welding to ionise the air gap between the electrode tip and the workpiece,
for arc initiation; (2) static elimination, also to ionise the air gap between the
electrode and workpiece and to provide a conducting path for static dispersal; (3)
Electrical Safety
293
Fig. 11.11 Testing earthed electronic apparatus.
electrostatic paint and powder spraying where the h.v. is used to charge the particles of material and induce them to adhere to the workpiece. By means of a series
impedance, the potential shock current can be limited to a value below the threshold of perception.
BURNS
There are sometimes more reportable accidents from burns than from electric
shock. There are, however, more shock incidents but unless the shock is accompanied by a burn injury, the victim usually recovers spontaneously and is unlikely to
be off work or need medical attention and so the incident does not become a
reportable accident. The burns are caused by contact or near contact with an electric arc and the victim may or may not receive a shock at the same time. Many
victims claim that they received an electric shock which, when investigated, proves
to have been a combination of fright and pain from the burn, i.e. a physical rather
than an electric shock.
Radiation burns arise from the non-ionising radiation produced by a variety of
electrical equipment and in the electromagnetic spectrum, range from radio frequencies to ultraviolet. Internal tissue damage can arise from the heating effect of
microwave radiation exceeding 10 mW/cm2. Infrared radiation is not considered dangerous as it produces surface heating of the body and is perceptible as sensible heat
and so is readily avoided in excess. Intensive coherent radiation, however, whether
infrared or visible light, in high-energy beams, can inflict damage, particularly to
294
Handbook of Electrical Installation Practice
the eyes. Ultraviolet radiation produces surface burning of the skin and conjunctivitis of the eyes.
Causation and avoidance of burn injury
The worst injuries, including one or two fatalities per annum, occur when there is a
low-impedance short-circuit on systems having very high prospective fault energy
levels, such as the public supply transmission and distribution networks.
Underground cables are often damaged during excavation work by a pneumatic
drill, pick fork or shovel. The tool penetrates until it contacts a phase conductor,
causing a short-circuit with the earthed armouring or outer CNE conductor. This
low-impedance fault causes arcing which may burn the operator. High voltage
cables are sometimes less hazardous than l.v. because the protection system often
clears the fault before arcing develops, whereas on l.v. systems, protected by excess
current fuses, the arcing may continue until the fault burns itself clear, as the loop
impedance may well be too high for the fuses to operate. The appropriate precautions are detailed under ‘Buried cables’ earlier in this chapter.
The use of unsuitably insulated probes and crocodile clips, when carrying out ‘live’
testing, causes short-circuit accidents when the probe or clip bridges between ‘live’
conductors of different polarity or phase or between a ‘live’ conductor and earthed
metal. The insulating covering should shroud the probe or clip so that only the probe
tip or clip teeth are exposed. HSE Guidance Note GS38 Electrical test equipment
for use by electricians gives further details.
Incorrectly switched multimeters can cause accidents. For example, if the instrument is switched to measure current when voltage is required, arcing will occur
when the probes are applied to the ‘live’ conductors. The obvious remedy is to
restrict such work to competent persons, have a checking system to ensure the
instrument is correctly switched, insist on the use of properly shrouded probes and
connectors and use fused leads for voltage measuring.
Maintenance and other work on ‘live’ equipment can cause arcing and burn
injuries when short-circuits are caused by tools bridging between ‘live’ conductors
of different polarity or phase or between such conductors and earthed metalwork.
The tools should be coated with a tough insulating material with the minimum of
bare metal exposed.
Short-circuits also occur when components are being fitted or removed. For
example, when adding or removing a fuse assembly on a distribution fuseboard, the
bolts, nuts and washers used to secure the busbar connections can be accidently
dropped inside and will frequently cause short-circuits and arcing. Magnetised and
purpose-made tools to handle components are useful safety aids. Flexible plastics
sheets are useful, not only for screening off ‘live’ parts that are not being worked
on, but as barriers to prevent components falling into dangerous areas. The sheets
can be cut to shape on site and taped in position.
Plugs, sockets, connectors and appliance inlets cause hand burn injuries when
portable equipment is being connected and the component is damaged or a conductor has become detached from its terminal and is in contact with another terminal or the appliance or flexible lead is short-circuited. Under these circumstances,
arcing may occur when the plug or connector is inserted into the socket or appliance
Electrical Safety
295
inlet. Similar accidents occur when disconnecting if the cable is pulled and a conductor parts from its terminal and makes contact with another. The remedy is
improved inspection and maintenance procedures to detect damage and incipient
faults before danger can arise.
The sheaths of flexible cables often get damaged so that a ‘live’ conductor is
exposed which can cause hand burn injuries to anyone handling the cable when in
contact with earth. Again, the remedy is an adequate inspection and maintenance
programme. Further information on inspection and maintenance of portable equipment and its associated connectors and cables can be found in HSE Guidance Note
HS(G)104 Maintaining portable and transportable electrical equipment.
Burn injuries, on safety l.v. circuits, are usually caused by carelessness and
thoughtlessness. Such circuits are often handled ‘live’ unnecessarily because operatives know there is no shock hazard and forget that short-circuits on such systems
can be the cause of unpleasant and sometimes severe burn injuries. The remedy is
to ensure operatives are aware of the hazard, make the circuit ‘dead’ when ‘live’
working is not necessary and take similar precautions as would be employed when
working on higher voltage circuits.
Radiation burns arise from the leakage radiation from microwave heating and
cooking equipment. The remedy is to prevent such leakage by the use of seals and
wave traps at doors and other openings, careful maintenance to preserve their
integrity and frequent checking with a leakage detector.
Intense coherent beam radiation is produced by lasers. To avoid burns, personnel must be kept out of the beam path by suitable guarding. To permit safe access
for maintenance or other purposes, the guards should be interlocked with the
supply.
Ultraviolet radiation, produced by certain types of drawing office printing
machinery and arc welding, for example, should be screened or filtered to prevent
irradiation of exposed skin or eyes.
FIRES
The Home Office’s annual fire statistics attribute about one third of all fires to electricity, but this includes electrical cooking equipment where the food is ignited but
the cooker is not faulty. If cookers are excluded, about 12% of fires are caused by
defective equipment and 6% are due to a faulty wiring installation (mostly flexible
cables since they are usually exposed).
Design defects in a new installation, likely to cause a fire are fortunately few
because most installations are designed to comply with BS 7671 which ensures
safety. Subsequently, however, DIY modifications, misuse and failure to maintain,
may render the installation unsafe and result in a fire.
Causes and avoidance measures
There are still pre-war installations in use, using natural rubber insulted cables.
The most dangerous utilise rubber-insulated conductors, tough rubber sheathed
296
Handbook of Electrical Installation Practice
(TRS), usually two-core and earth and of rectangular section. Many of these cables
were used, without further protection, for wiring dwellings and small commercial
properties. In most cases, the rubber has hardened, perished and cracked and when
disturbed falls away exposing the conductors. Short-circuits are then likely to occur
between ‘live’ conductors or to earth and the arcing will sometimes ignite the
remains of the insulation and/or anything else flammable nearby.
Other installations have vulcanised rubber insulated (VRI) conductors, taped,
braided and compounded and run in steel conduit. Again the rubber will have perished but is sometimes retained by the outer covering of tape and braid. The hardened material tends, however, to crack when bent, exposing the conductor. The
conduit protects most of the wiring but the exposed ends which are sometimes in
wooden switch boxes or in wooden pattresses supporting switches, socket-outlets or
ceiling roses, are vulnerable and again a short-circuit may occur and the arcing cause
a fire. This old wiring should be replaced by the PVC insulated or insulated and
sheathed equivalents.
Severely overloaded circuits are a fire hazard as the hot conductors damage
the insulation, which will eventually fail and permit a short-circuit to occur.
Examples are sometimes found in old radial socket-outlet circuits where the
DIY operator has sought to increase the supply capacity by replacing old 2 and
5 A by double 13 A socket-outlets or by adding additional socket-outlets to a
circuit by looping without regard to the size of the cable. He then finds that the
protective rewireable fuse on the distribution board is inadequate, and so increases
the size of the fuse wire so that the inadequately sized conductors are no longer
protected.
Again, where there are insufficient socket-outlets, adaptors are used and loads, in
excess of the rating of the socket-outlet, connected. The multiple plugs and
adaptor(s) assembly may not only overload the socket but very often the socket
receptacles are damaged by the adaptor pins when the assembly is subjected to
lateral pressure from mishandling or a blow. The result is a bad connection, minor
arcing at the contacts, corrosion of the surfaces and overheating which ignites the
insulation and anything else flammable nearby. The remedy is to eschew the use of
adaptors and install an adequate number of socket-outlets.
Conductor overheating, resulting in fires, can also occur from loose connections.
Pinch screw terminals in plugs and switches are prone to slacken in time, probably
due to vibration, resulting in bad connections and an eventual fire. Checking terminal screw tightness should be part of the maintenance schedule.
EXPLOSIONS
Electrical explosions occur when there is a short-circuit between conductors on different phases or between a phase conductor and the neutral or earthed metal and
sufficient energy is expended to cause an audible bang. In domestic installations
where the line/neutral and line/earth loop impedances are comparatively high,
usually around 0.3 W to 0.5 W, the short-circuit current will be 230/0.3 or 230/0.5 ⯝
766 or 460 A, which is enough to cause an audible bang at the fault location and
at the fuse or circuit-breaker protecting the circuit which clears the fault. Such
Electrical Safety
297
explosions do not usually cause any significant damage but if someone is close
enough to the fault, a minor burn from the momentary arcing is a possibility.
At the location of the short-circuit, the arcing vaporises the metal conductors
and their insulation and these hot gases cause an immediate, local pressure rise.
In a confined space, the pressure rise is more than in the open because the gases
cannot disperse so readily and a more audible explosion results. In an HBC
fuse, the fault is interrupted rapidly and the energy release curtailed so that the
bursting pressure of the hot gases does not break the container. Where, however,
the fault persists, more energy is released and the resultant explosion may burst
the container. Some of the worst explosions occur from street excavations when
a tool accidentally penetrates a low-voltage distribution main causing a shortcircuit between phases and to the earthed metal cable armouring or sheath. Very
often, a fault of several megawatts causes an arc to be emitted which burns the tool
operator.
A short-circuit between turns in an oil-insulated power transformer or between
a ‘live’ conductor and the metal core, will cause arcing and vaporisation of the
metal and oil at the fault. The pressure rise is likely to burst the tank with a loud
explosion if the pressure operated relay is ineffective. Oil circuit-breakers and
oil-immersed control gear are susceptible to explosions from carbonised oil.
Arcing, at the contacts when on load and during operation, causes oil contamination and when this is excessive the carbon is deposited on the surfaces of internal
insulators and tank and can form a tracking path between phases and/or between
a phase and the earthed metal tank. A flashover can then occur across the contaminated surfaces or sometimes through the oil when the insulating value is sufficiently
impaired by this contamination. In either event, the arcing causes a rapid pressure
rise and may burst the tank with a loud explosion. The spilt oil is usually ignited and
can then involve flammable materials nearby and spread the fire or set the operator on fire.
Remedies
There is much to be said for avoiding oil-filled equipment altogether, but if it is used,
equipment with pressure relief vents is preferable to minimise explosion damage
together with regular inspection and testing to ensure that the equipment is maintained in a serviceable condition. Connections should be clean and tight and contacts kept clean, adjusted and replaced when worn or damaged to ensure that arcing
does not occur when on load. Some arcing, at the contacts of transformer tap changers, oil switches, circuit-breakers and controllers, takes place in normal operation
and contaminates the oil – hence the need for regular maintenance. For heavy-duty
operation, it may be worthwhile considering the use of a filter through which the
oil is passed continuously, to remove the carbon. Alternatively, samples of the oil
should be inspected and tested periodically to ascertain when the oil needs changing or reconditioning. The tank housing the contacts should be opened whenever
the oil is changed, the contacts maintained and contaminated surfaces cleaned. The
maintenance procedures for switchgear are detailed in Codes of Practice BS 6423,
6626 and 6867 for the maintenance of switchgear for voltages up to and including
145 kV and are applicable also to on-load tap changers and controllers. Equipment
298
Handbook of Electrical Installation Practice
containing large quantities of oil should be situated in a fire-resistant location over
a soakaway and surrounded by dwarf walls so that any spillage is contained and
dispersed.
The procedure for avoiding the hazard from buried cables is described earlier in
this chapter.
To minimise explosion hazards from the wiring installation and other equipment,
ensure the protective devices are of adequate rating for the fault level, that their
operation is as rapid as possible, and that they and the installation and equipment
are regularly inspected, tested and repaired.
FLAMMABLE ATMOSPHERES
Flammable atmospheres are part of the electrical fire and explosion hazards. They
are dealt with separately because of the complexities and problems peculiar to the
subject. They occur when flammable gas, vapour, mist, aerosol or dust is present in
a concentration in air between the upper (UEL) and lower (LEL) explosive limits.
Such mixtures ignite if there is a source of ignition also present, such as incendive
arcs or sparks from electrical equipment. The risk areas are divided into zones. For
flammable gases/vapours:
Zone 0
Zone 1
Zone 2
Where the flammable atmosphere is always present
Where the flammable material is present during normal operations and
a flammable atmosphere is likely to occur
Where the flammable atmosphere is unlikely during normal operation
and if it occurs it will exist only for a short time.
Where flammable dusts are involved, the corresponding zones for dust are labelled
Zones 20, 21 and 22. Dust Zone 20 is equivalent to Zone 0 for gases, dust Zone 21
is equivalent to Zone 1 for gases and dust Zone 22 is equivalent to Zone 2 for gases.
Zonal boundaries
Zonal boundaries have to be determined by the occupier’s specialist staff and
marked on the site drawing in plan and elevation. It is a difficult task and requires
a knowledge of the characteristics of the material and how it disperses from the
source of emission. Guidance on zonal classification is given in BS EN 60079 part 1.
Pits, trenches and ceilings, within flammable zones, should not be overlooked. If
unventilated, pits and trenches are Zone 1, because heavier than air gases can enter
and remain, as are also coffered ceilings for lighter than air gases such as hydrogen.
Garage pits, where petrol may be spilt, are an example of the former and battery
rooms of the latter.
Zone 2 boundaries are particularly difficult to decide because they have to cater
for accidental discharges from leakage, spillage or a burst container.
For dusts the problem is easier as Zone 21 usually occurs within 1 m of the point
of release, e.g. emptying bags of material into hoppers, and Zone 22 within about
15 m from the release point. Of course if the housekeeping is bad and a layer of dust
Electrical Safety
299
is allowed to settle, Zone 21 would have to include such locations as those where
the flammable hazard would arise from contact of the layer with hot equipment or
from the dust cloud if the layer is disturbed during normal operations.
Installation design
Location of equipment
Armed with the zonal boundary plans, the next step is to determine the position of
the electrical equipment. Wherever possible, the risk should be avoided or minimised by locating the electrical equipment outside the risk areas or in Zone 2 areas
rather than in Zones 0 and 1.
Zone 0 is usually inside reaction vessels or storage tanks. There is not much
electrical equipment available for use in Zone 0 and as the risk is high it should
be avoided by locating the equipment outside, e.g. a container can have glazed
port-holes so that the interior can be viewed through one and lit from a luminaire
shining through another. Zone 1 areas often occur only in the immediate vicinity
of where the flammable material is processed. They are invariably surrounded by
Zone 2 areas where the electrical apparatus should preferably be situated. It is
sometimes possible to light outside site zones by luminaires located at high level
in safe areas above the vertical zone boundaries. For flammable interiors, lighting
can often be provided by positioning the luminaires outside in a safe location
and shining the light through glazed panels in the roof or walls. Again, motors
can be outside and drive an internal machine through a long shaft extension
passing through a gas-tight seal in the wall. In some plants, it is convenient to locate
the motor starters together on a starter panel in a motor control room. This room
could either be in a safe area or if within the flammable zone, fed with clean air,
from outside the zone, maintained at a positive pressure to ensure that gas cannot
enter.
Equipment selection
Within the flammable zones, the equipment has to be explosion protected and
matched to the zone as shown in Table 11.2.
Higher risk zone equipment may be used in a lower risk zone. For each category
there is an appropriate BS and/or BS EN and equipment which may be tested and
certified accordingly by an approved testing house. To be safe, only certified equipment should be employed.
For dusts, the present position is that when the standards are revised dust protected equipment will be marked as follows:
DIP
1D, 2D or 3D
A or B
20 or 21 or 22
Ta or Tb
Dust ignition protected (for equipment constructed to IEC
Standards)
Dust ignition protected (for equipment constructed to EN
Standards)
European or American practice
Zone
Maximum permissible equipment surface temperatures.
300
Handbook of Electrical Installation Practice
Table 11.2 Zones for gases and vapours.
The protection method is to have a dust-tight or dust protected enclosure to IP6X
or IP5X and limit the exterior temperature of the equipment casing when under a
dust layer to prevent ignition.
Wiring
The installation work should comply with BS 7671 and BS 5345: Part 1 for gases
and vapours and BS 7537 for dusts. Conduits should be solid drawn or seam welded
with screwed joints. Where flammable gases have to be excluded from equipment,
barrier seals may be necessary. Flexible metallic conduit should be lined to prevent
abrasion of the cable insulation. Aluminium and aluminium alloy conduits and
accessories should not be used where frictional contact with oxygen-rich items such
as rusty steel might occur and cause sparking.
Gas detectors
Gas detectors are devices that sample the atmosphere in their vicinity, and in the
event of the presence of the relevant flammable gas can be used to provide a
warning signal and/or operate a relay to trip the supply to electrical equipment
and/or start a ventilation fan. They are of particular use in unattended areas where
a leak may not otherwise be detected, allowing the flammable material to spread
perhaps into an otherwise safe area and be ignited by a source of ignition therein.
Lightning
Certain vulnerable installations may need lightning protection which should be
installed to BS 6651: 1992 together with surge suppressors to prevent possible
flashovers from any associated high voltage transients.
RF induction
The risk of sparking from radio frequency induction is relatively small and will be
minimised by any suppressors fitted for EMC and lightning protection, but if there
Electrical Safety
301
Fig. 11.12 Elevation of flammable solvent storage tank in factory yard showing the zonal
boundaries, Key:
(1) Zone 2 boundary,
(2) earthing clip,
(3) earthing flexible lead,
(4) earthing switch,
(5) remote push button control for intake pump motor starter,
(6) local light switch,
(7) road tanker hard standing,
(8) intake pump,
(9) intake pump motor,
(10) Zone 1 boundary,
(11) local light,
(12) limit switches,
(13) area floodlight luminaire,
(14) factory wall,
(15) tank indicator lights,
(16) floodlight switch,
(17) float,
(18) flammable solvent tank (Zone 0),
(19) sight glass,
(20) intake pump motor starter,
(21) float counterweight,
(22) off-take pump motor,
(23) off-take pump,
(24) gas detector sensor,
(25) gas detector control,
(26) gas detector siren,
(27) off-take pump motor starter,
(28) trench (Zone 1),
(29) gland seal,
(30) vent pipe,
(31) safe area.
302
Handbook of Electrical Installation Practice
Fig. 11.13 Plan of flammable solvent storage tank in factory yard to show the zonal
boundaries. Key: (1) Zone 2 boundary, (10) Zone 1 boundary, (31) safe area.
are any RF transmitters in the vicinity, the installation should be checked to BS
6656.
An application of zoning
Figures 11.12 and 11.13 show a factory yard where there is an unattended flammable solvent storage tank. The solvent vapour is heavier than air. The tank is replenished by a road tanker through a hose connected to the intake pump. The tank
contents are dispensed via the off-take pump. When the road tanker visits, any static
charge is safely discharged to earth via the earthing clip, which is secured to the
tanker metalwork, the flexible cable and earthing switch which is closed after the
clip is applied. This has to be done before any flammable liquid is transferred.
The storage tank interior is Zone 0. There are two Zone ls which are in the immediate vicinity of the vent and in the pipe trench. The Zone 2 boundary extends from
the factory wall to the other side of the road tanker hardstanding. To avoid gas leaks,
the float wire rope passes through a gland seal in the tank lid and the off-take pipe
is in a sealed duct where it passes through the factory wall.
To minimise costs and maximise safety, the security floodlight is mounted in the
safe area above the Zone 2 vertical boundary; its switch together with the pump
motor starters, the liquid level indicator and the gas detector control panel and
alarm are inside the factory which is also a safe area. The rest of the equipment is
all in a Zone 2 area and has to be non-sparking so the local light and the squirrel
cage pump motors can be EEx n. As the earthing and limit switches, the remote
control push buttons for the intake pump motor starter, the local light switch and
gas detector sensor are not non-sparking devices, they should be type EEx d, except
the sensor which should be a type Ex s.
Electrical Safety
303
CONCLUSION
Electrical engineers, technicians, electricians and electrical operatives have a legal
reponsibility to ensure that their installations are properly designed, constructed,
maintained and used. If they conscientiously fulfill this responsibility, the present
trend for a decline in the annual electrical accident figures should continue and be
a beneficial contribution by the electrical industry to the well-being of society.
CHAPTER 12
Standards, Specifications and Codes of
Practice
J.M. Faller, BA, IEng, MIEIE
(British Standards Institution)
Revised by M.H. Graham
(Secretary, British Electrotechnical Committee (BEC)
British Standards Institution)
Throughout the other chapters of this handbook on installation practice, there are
numerous references to British Standard specifications, British Standard codes of
practice and (in the legal sense) Regulations. It is the purpose of this chapter to
explain in rather general terms the significance of standards (at national, regional
and international levels), their relationship with legislation (both British and
European) and the philosophy of the preparation of standard-type documents.
The general principles will be illustrated by examples from the subject area covered
by the handbook. In preparation it is necessary to understand clearly the difference
between a ‘standard’ and a ‘regulation’. The formal definitions of the two words are:
•
•
Standard A document, established by consensus and approved by a recognised
body, that provides, for common and repeated use, rules, guidelines or characteristics for activities or their results, aimed at the achievement of the optimum
degree of order in a given context. Note: Standards should be based on the
consolidated results of science, technology and experience, and aimed at the
promotion of optimum community benefits.
Regulation A document providing binding legislative rules, that is adopted by an
authority.
These two definitions taken together point to the fundamental difference between
standards and regulations. The former are established essentially by voluntary
co-operation and consensus between interested parties, and their use is, in most
cases, also voluntary. On the other hand, regulations have legal force such that
failure to comply with them leaves the transgressor open to whatever penalties the
law provides.
It is nevertheless important to realise that, once a standard has (albeit voluntarily) been written into a contract, its provisions become binding on the parties to
that contract. In such a case, failure to comply with the standard may make the
304
Standards, Specifications and Codes of Practice
305
offending party liable to damages in a civil action. The question of the status of those
standards to which reference is made in the law, which results in them becoming
more than purely voluntary, is dealt with later in this chapter.
As can be seen from its definition, the term ‘standard’ covers a wide (even openended) range of documents designed for use in a variety of circumstances. Almost
all standards bodies (whether they are recognised at national, regional or international level) have found it necessary to distinguish between various types of standard according to the purpose for which they are intended. The two major classes
of standard, and those which are of greatest interest to those concerned with electrical installations, are standard specifications (which describe a particular product
or range of products in terms of dimensions, performance or safety) and standard
codes of practice (which describe recommended techniques of design, installation,
maintenance, etc.). Both of these types of standard inevitably include or rely on
more basic types, such as glossaries, classifications, methods of testing, methods of
measurement, methods of sampling, etc.
BRITISH ELECTROTECHNICAL COMMITTEE (BEC)
Working as an integral part of BSI, the British Electrotechnical Committee draws
its membership from industry, government, professional organisations, the consumer
and user communities, and a range of other stakeholders. The BEC is the UK
member of the International Electrotechnical Commission (IEC) and the European
Committee for Electrotechnical Standardisation (CENELEC). Technical aspects of
product standardisation are handled by BSI Technical Committees, which interface
with their IEC and CENELEC counterparts. BEC representatives also attend key
policy and management meetings, including IEC Council and Committee of Action,
and CENELEC General Assembly and Technical Board.
BRITISH STANDARDS INSTITUTION (BSI)
Within the UK, national standards are prepared and published by the British
Standards Institution (BSI), an independent non-profit making association incorporated by a Royal Charter granted originally in 1929 and now operating under the
provisions of a consolidated Charter dated 1981, as amended in 1989, 1992 and 1994.
In fact, the origins of BSI can be found as long ago as 1901 as the Engineering
Standards Committee, set up as a co-operative joint venture by the leading professional engineering bodies, including the Institution of Electrical Engineers (IEE).
The objectives of BSI, as laid down in the Royal Charter, are to:
(1) Co-ordinate the efforts of producers and users for the improvement, standardisation and simplification of materials, products and processes, so as to simplify
production and distribution, and to eliminate the national waste of time and
material involved in the production of an unnecessary variety of patterns and
sizes of articles for one and the same purpose
306
Handbook of Electrical Installation Practice
(2) Set up standards of quality for goods and services, and prepare and promote the general adoption of British Standards and schedules in connection
therewith and from time to time to revise, alter and amend such standards and
schedules as experience and circumstances may require
(3) Register, in the name of the Institution, marks of all descriptions, and to prove
and affix or license the affixing of such marks or other proof, letter, name,
description or device
(4) Take such action as may appear desirable or necessary to protect the objects or
interests of the Institution.
Stripped of the solemnity of this legal prose, it will be seen that BSI’s main functions are to facilitate the development of voluntary standards by consensus among
all the interests concerned, and to promote their use.
One indication of the independence of BSI is given by the breakdown of the
major sources of income that funds standards work. Approximately 76% is derived
from sales of BSI standards and other publications, approximately 15% from subscriptions paid by some 20 000 firms, trade associations, local authorities, professional institutions, etc. and the remaining 9% from a Government grant-in-aid.
In accordance with the Royal Charter and the Bylaws created under it, the Board
of BSI is responsible for the policies of the Institution, subject always to the ultimate authority of the subscribing members of BSI exercised at a general meeting.
The members of the Board together represent a broad range of national interests,
all of which are in some way affected by the results of standards work. As permitted in the Bylaws, the Board has delegated its responsibility for the preparation of
British Standards to a Standards Executive, which has divided its activities into five
functions:
(1) Business development, which markets British Standards products
(2) International, to lobby and to co-ordinate all international standards related
policy issues
(3) Sales, which combines ordering and delivery
(4) Standards development, which contains all the technical departments
(5) Planning and co-ordination, which manages all stakeholder relationships.
Eight technical departments, organised into separate business streams, exist within
the standards development function:
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Electrotechnical
Building and civil engineering
Engineering
Materials and chemicals
Health and the environment
Management systems
Consumer products and services
Disc, the information technology specialist department.
Standards, Specifications and Codes of Practice
307
Of these departments, the one of major interest to electrical engineers is the Electrotechnical Business Sector that is responsible to the Electrotechnical Sector Policy
Committee for the preparation of British Standards within its subject area.The Electrotechnical Sector Policy Committee is fully representative of all interests likely to
be affected by standardisation in the electrical and electronic engineering fields.
Responsibility for the technical content of standards, and for participation in corresponding international work, is in turn delegated to technical committees, each
responsible for a specific product area. Care is taken to ensure that no two technical committees have overlapping terms of reference. Depending on the size of the
area of work involved, technical committees may in turn establish sub-committees
and working groups.
A detailed description of all the procedures used by BSI committees to develop
standards is included in BS 0, which can be found on the British Standards website
at www.bsi-global.com. It is important to emphasise that all of these procedures are
aimed at underpinning the two fundamental safeguards of BSI standards work,
which between them ensure that the resulting standards satisfy the rigorous criteria implied by the definition of ‘standard’ given at the beginning of this chapter.
These two safeguards are consultation and consensus.
When a new technical committee is established, every effort is made to involve
all those whose interests are likely to be affected by its work. Thus the constitution
of each technical committee is intended to bring together all those with a substantial interest in the subject being discussed, wherever possible through organisations
representing manufacturers, users, professional institutions, government departments, research organisations, certification bodies, trade unions, and so on. Once the
committee is established, a secretary and an independent chairman are appointed.
At a suitable stage, its work is exposed to public consultation by the issue, for
each British Standard, of a draft for public comment. The availability of all drafts
for public comment is announced in BSI’s monthly journal and any organisation or
individual may obtain a copy of any draft for a nominal fee. Any comment, from
whatever source received, must be properly considered by the responsible technical committee. Thus, by means of this double consultation (of a representative
committee and of the public), every effort is made to ensure that the views of all
interested parties are canvassed.
The other formal safeguard on the content of British Standards is provided by
the system of decision-making by consensus. This implies that differences of opinion
within a technical committee on the content of the standard are never resolved by
means of a formal voting procedure; rather, discussion continues until all significant
objections have been met or withdrawn. In the rare event that this process of compromise fails to produce an agreed text, recourse can be had to a formal appeal
procedure, through all intermediate committees right up to the Standards Policy
Committee itself. If no other solution can be found, the Board will establish a small
panel of its members to recommend a decision, which will be binding on all parties
to the dispute.
The purpose of these twin safeguards (consultation and consensus) is to ensure
that, once the responsible technical committee has approved it, a British Standard
will have been drawn up with the co-operation and general approval of all interests
affected by it.
308
Handbook of Electrical Installation Practice
While the foregoing may explain the preparation and resulting status of British
Standards, it gives no impression of the breadth or scale of the operation. Suffice it
to say that there are some 3000 technical committees (of which about 1000 are likely
to be active at any one time). There are more than 20 000 British Standards, covering almost the whole range of industrial products from steam turbines to microprocessors, and of industrial processes from deep-sea diving to tea tasting.
Subjecting each British Standard to review by the responsible technical committee at least once every five years ensures its continuing applicability; it must be
confirmed, revised, amended or withdrawn. In fast-moving areas of technology, this
review may be carried out much more frequently, as and when the need arises.
Further, new projects concerning areas not previously standardised are continually
being added to the programme of work. Proposals for new work are considered by
the appropriate technical committee in response to requests from any individual
or organisation having an interest in the topic in question. In fact, planning the work
is the major task of the Sector Policy Committee, and the allocation of resources is
its prime responsibility.
THE INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)
There are two worldwide standardisation bodies. The older (dating from 1906) is
the International Electrotechnical Commission (IEC) responsible for standardisation in the fields of electrical and electronic engineering, while the younger (postwar) International Organization for Standardisation (ISO) is responsible for
standardisation in all other fields of science and technology. In view of the subject
matter of this handbook, only the former body will be discussed here.
The IEC is an international non-governmental organisation whose members
are the national electrotechnical committees (like the British Electrotechnical Committee in the UK) of over 50 countries. Between them, these countries represent
more than 85% of the world’s population and account for more than 95% of the
world’s total electricity generating capacity. Located in Geneva, Switzerland,
the IEC central office consists of the General Secretary and his staff of some 100.
A Council and a Council Board govern the activities of the IEC. The Council meets
annually at a General Meeting, consisting of representatives of all of the member
national committees. The day-to-day running of the organisation is delegated to
a Council Board which meets on average three times a year. The Committee of
Action, whose members are elected by all IEC members for six-year terms, manages
the technical work.
The essential constitutional duties of the IEC Council are the election of its officers (President, Vice President(s), Treasurer and Auditor) and the approval of the
annual expenditure budget. This in turn determines the subscriptions payable by
each national committee, distributed according to a formula based on population
and gross national product, which ensures that the greater portion of the financial
burden is borne by those countries most able to do so.
Because they are responsible for overall IEC policy, Council and the Committee
of Action may establish committees and working groups to study and provide
advice on particular questions. Among the standing committees set up in this way
Standards, Specifications and Codes of Practice
309
are the Advisory Committee on Safety (ACOS), the Advisory Committee on
Electronics and Telecommunications (ACET), the Advisory Committee on Electromagnetic Compatibility (ACEC) and the Advisory Committee on the Environment (ACEA). However, the main work of the IEC is carried out in more than
90 technical committees, each charged by the Committee of Action with the
preparation of international standards in a specific field of electrical or electronic
engineering. Each national committee has the right of participation in the work
of every technical committee, so that the principle of consultation enunciated
above applies equally to the international standardisation work of the IEC. It is
important to note that the technical work of the IEC is, in fact, decentralised as
the secretariat of each technical committee is allocated to one of the national
committees.
In order to carry out the work in the most efficient manner, technical committees may establish sub-committees to deal with specific parts of their work programme. At present, over 80 sub-committees are active and, as with the technical
committees, each national committee has the right of participation. Most projects
are started in preparatory working groups consisting of individually appointed
experts charged with the task of preparing a first draft international standard
for discussion. When such a draft has been completed, it is circulated (as a ‘secretariat’ document) to all national committees for comment. All comments
received are discussed at the next available meeting of the parent technical committee or sub-committee and, if a sufficient measure of support is indicated, a revised
draft is circulated by central office to all national committees as a ‘committee draft
for voting’. The document is approved as suitable for circulation as a ‘draft international standard’ if a two-thirds majority of the participating members voting are
in favour and not more than one-quarter of the total number of votes cast are negative. Editorial and minor technical comments are allowed at this stage. If sufficient
support is indicated, the document, amended as necessary, is formally circulated
for voting as a draft international standard under the six-month rule. The criteria
for acceptance are as before; however, comments at this stage are not allowed.
Approved final drafts are edited and published as international standards by the
IEC.
Moreover, it is important to recognise the status of IEC standards as a record of
the best technical solution that can be achieved by majority agreement between the
member national committees spread all over the world and with their different economic and technological stages of development. In fact, the foreword of each IEC
standard explains that it is recommended to national committees as a basis for the
preparation of national standards on the same subject. This question leads naturally to that of the use (or in formal language, ‘implementation’) of IEC standards.
Although their direct use as such is not unknown, particularly by reference in contracts between manufacturers and customers in different countries, the more usual
route to implementation is the indirect one, whereby use is made of a national standard whose content mirrors that of the IEC standard. It is for this reason, as well
as for the more obvious practical ones, that participation in the work of an IEC technical committee on a particular subject is delegated by the British Electrotechnical
Committee to that BSI technical committee which is responsible for national work
on the same subject.
310
Handbook of Electrical Installation Practice
As far as the implementation of international standards is concerned, it has been
customary to adopt, wherever practicable without change, the results of IEC work
as British Standards. When approved by the responsible BSI technical committee,
the resulting British Standard has identical text and incorporates the identification
number of the IEC Standard, e.g. BS IEC 60780, Nuclear power plants. Electrical
equipment of the safety system. Qualification. However, the majority of IEC standards are first adopted as European standards (EN), then subsequently adopted as
British Standards (see section on CENELEC).
To give some idea of the extent of IEC work in the area covered by this handbook, it is necessary only to list the titles of a handful of IEC technical committees
whose standards are of particular relevance to electrical installation practice:
TC 8
TC 16
TC 23
TC 64
TC 71
Standard voltages, current ratings and frequencies
Terminal markings and other identifications
Electrical accessories
Electrical installations and protection against electric shock
Electrical installations for outdoor sites under heavy conditions (including
open-cast mines and quarries).
EUROPEAN COMMITTEE FOR ELECTROTECHNICAL
STANDARDISATION (CENELEC)
In recent times European standardisation has become increasingly important as
the European Commission has extended its New Approach model. This successful instrument for the establishment of the single market has lead to a great increase
in the number of standards developed in support of the various European Directives.
CENELEC, the European Committee for Electrotechnical Standardisation, is a
non-profit-making technical association constituted under Belgian law and composed of the National Electrotechnical Committees of 19 countries. They currently
are the 15 member states of the European Union plus the EFTA Members Iceland,
Norway and Switzerland and the Czech Republic. CENELEC is governed by a
General Assembly of all its member national committees, which has complete power
of decision within the organisation. The Technical Board (BT) co-ordinates all technical activities, including the selection of international standards for consideration
as reference documents, and sets up and monitors the activities of CENELEC technical committees. The BT consists of one permanent delegate from each national
committee (in most cases the secretary of the national committee) and a number of
observers.
The main purpose of CENELEC is to remove, by mutual agreement between the
CENELEC member committees, any technical differences between their national
standards so that these national standards can become ‘harmonised’. The process of
harmonisation of national standards is deemed to have been achieved when equipment manufactured in one country in conformity with the national standard of that
country also conforms with the requirements of the national standards of the
other member committees, and vice versa. It will be seen that this rather formal
Standards, Specifications and Codes of Practice
311
definition of ‘harmonisation’ permits editorial differences (particularly of language)
between national standards, but requires that they be technically equivalent. In this
respect, the UK is perhaps fortunate in having as its mother tongue one of the three
official languages of CENELEC (English, French and German), so that no difficulties of translation are encountered.
From this it can be seen that the underlying aim of the work is the removal of
technical obstacles to trade in electrotechnical products within the whole of the
European Union (the New Approach). However, as this objective has largely been
achieved, the emphasis is moving towards more socio-economic issues such as protection of the environment. Two other European Standards bodies also exist, CEN
and ETSI. CEN, the European Committee for Standardisation, is responsible for
standardisation in fields other than those of electrical and electronic engineering.
ETSI is responsible for standardisation in the field of telecommunications. The prevention of technical barriers to trade by CENELEC, CEN and ETSI is obviously
supportive of the objective of Article 100 of the Treaty of Rome, which governs
the European Union. Nevertheless, the process extends further than the current
members of the EU, as it includes the countries of the European Free Trade
Association (EFTA), each of which has a reciprocal trade agreement with the
EU and the accessing countries applying to join the European Union.
As most electrotechnical products are traded globally, CENELEC at its inception decided as a matter of policy to adopt the international solutions provided by
the IEC. Therefore, CENELEC for most of its harmonisation work utilises the
results of international (IEC) standardisation work unless there are overriding
reasons of impracticability usually due to regional regulatory or technical infrastructure reasons.
In order to optimise the standards-making process, a co-operation agreement was
reached between IEC and CENELEC on the planning of new work and parallel
voting. Known as the Dresden Agreement its objectives are to:
(1) Expedite the publication and common adoption of International Standards, i.e.
timely results prevail over an excessive degree of perfection
(2) Ensure rational use of available resources. Full technical consideration of the
standard should therefore preferably take place at international level
(3) Accelerate drastically the standards preparation process in response to market
demands.
New work items approved by the CENELEC Technical Board are offered initially
to the IEC in order that the work is done at international level. However, if the
time scale in the IEC exceeds CENELEC’s planning requirements, the work is
given to a CENELEC committee or working group. At the other end of the
standards-making process, ‘mature texts’ produced by IEC committees are submitted concurrently for parallel vote in both IEC and CENELEC. If the IEC and
CENELEC results are both positive, the draft is published by the IEC and formally
ratified as a European Standard by the CENELEC Technical Board. If the IEC
result is positive and the CENELEC result is negative, the Technical Board will
decide on what action to take – the adoption of common modifications, for example.
312
Handbook of Electrical Installation Practice
Only in exceptional circumstances does CENELEC embark on the preparation of
a standard in anticipation of, or in contradiction to, an IEC standard. If this process
becomes necessary, a CENELEC technical committee is established; as with IEC
work, each CENELEC member is entitled to membership, and one national committee undertakes secretariat duties. The resulting standard is then offered to IEC
under the terms of the Dresden Agreement as a potential International Standard.
If finally accepted at IEC level it then undergoes a parallel vote in both organizations, as described above. This is known locally as the ‘boomerang procedure’. By
this process CENELEC endeavours to continue to fully support the activities of
IEC.
The situation is complicated slightly by the fact that CENELEC harmonisation agreements are published in two different forms, either as Harmonisation
Documents (HDs) or as European Standards (ENs). In either case, the existence
of a harmonisation agreement imposes an obligation on each national committee
to withdraw any conflicting national standard, so that any existing technical barrier
to trade is removed.
The appearance of new technical barriers to trade is prevented by the obligation
on all national committees to inform CENELEC of the intention to start purely
national work. This is known as the Vilamoura Procedure and ensures that if
sufficient support exists, the work must be done at European level only – called
standstill.
It is extremely important to recognise the fact that within CENELEC, once a
European Standard has been approved it must be adopted nationally by all
members, with the withdrawal of any conflicting national standard.
The further implications for standards work of Directives of the European Union,
in so far as they relate to those CENELEC member committees representing
member states of the EU, are discussed later.
THE INSTITUTION OF ELECTRICAL ENGINEERS (IEE)
Of particular importance to the subject matter of this handbook are the Wiring
Regulations, published by the Institution of Electrical Engineers (IEE). Since the
publication of the first edition of the Regulations in 1882, this authoritative set of
requirements for the design and installation of electrical systems in buildings has
been amended and revised from time to time to keep it up to date. In 1981 the 15th
edition of the Regulations was published, under the new title Regulations for Electrical Installations, and marked a significant step towards the alignment of installation practices in the UK with those of the rest of the world. Its structure and detailed
requirements were based closely on IEC Publication 364, Electrical installations of
buildings. The various parts and sections of this large IEC standard have been the
subject of harmonisation agreements between the CENELEC member committees,
although in many cases it has been found necessary to include common CENELEC
modifications designed to make the requirements suitable for application within
Western Europe.
It is important at this stage to clear up a potential misunderstanding. The use of
the word ‘Regulations’ in the title of the document, although it is long standing, does
Standards, Specifications and Codes of Practice
313
not indicate that it contains legal regulations in the formal sense implied by the definition given in the introductory section of this chapter. The use of the word
precedes the international agreement on its meaning by almost a century. Indeed,
the publication of its 1st edition preceded the formulation of the precursor of the
British Standards Institution by almost a quarter-century.
On 2 October 1991, a formal agreement was signed between the British Standards
Institution and the IEE establishing the IEE Wiring Regulations as British Standard BS 7671 Requirements for electrical installations. The British Standard also
bears the original title, IEE Wiring Regulations. The technical authority for the new
standard is vested in the BSI Standards Policy Committee and the Council of
the IEE. The technical work is assigned to a joint committee whose constitution and
procedures are consistent with the practices of both BSI and the IEE. This joint
committee has an IEE staff member as secretary and is fully representative of all
appropriate interests, including contractors, manufacturers, users, government
departments, inspection authorities and research associations.
The British Electrotechnical Committee has also delegated the task of participation in international work within IEC TC 64 and CENELEC TC 64 on the subject
to the joint committee. To summarise, the joint committee is directly analogous in
its functions and responsibilities, both national and international, to a BSI technical committee.
The close relationship between BS 7671 and the catalogue of British Standards
is demonstrated by the fact that it makes reference to 75 British Standard specifications and codes of practice. The suitability of the content of these British
Standards for the purpose of reference in BS 7671, and the co-ordination of their
various requirements, is ensured by the fact that all interested organisations, including the IEE itself, have a voice in the appropriate BSI technical committees.
It is not the purpose of this chapter to discuss the implications or implementation of BS 7671, subjects that are covered extensively in other chapters of this
handbook.
STANDARDS AND THE LAW
Although it was stated in the introductory section of this chapter that the application of most British Standards is purely voluntary, resting usually on a decision by
contracting parties, exceptions do occur when standards are referred to explicitly in
the law. This technique is usually adopted by the legislature as a device to avoid the
inclusion of detailed technical requirements in the body of the law. Thus an Act of
Parliament (or a Statutory Instrument or Regulation made under an empowering
Act) may make a particular standard part of the law, in the sense that it must be
followed in order to obey the statutory requirement. In such a case, the use of the
standard becomes mandatory rather than voluntary.
This technique has not often been used within the UK, although the legal systems
of certain other European countries have forms that enable them to exploit it extensively. Mandatory reference to standards in British law is restricted almost entirely
to cases in which the personal safety of a large section of the population needs
to be protected. Examples include the legal references to British Standards for
314
Handbook of Electrical Installation Practice
automobile seat belts, motorcyclists’ crash helmets and childproof containers for
analgesic drugs.
An alternative, and much commoner, technique is that used when the Act,
Regulation or Statutory Instrument embodies a generalised technical provision
supplemented by an indication that compliance with a particular British Standard
or Standards is one (but not the only) way of fulfilling the legal obligation. In such
a case, alternative designs which comply with the general legal provision are not
precluded, but a solution which does comply with the standard in question is
deemed to satisfy the legal requirement. It is important to realise that, although
compliance with standards to which ‘deemed-to-satisfy’ reference is made in the law
is voluntary, anyone choosing another route may be required to offer proof in court
that his product, system or installation complies with the Regulation despite its
non-compliance with the appropriate standard.
Although there is at present no legislation in the field of electrical installations
which makes any particular standard mandatory, there are many ‘deemed-to-satisfy’
references to standards in relevant legislation. The most important such reference
is made in the Electricity Safety, Quality and Continuity Regulations 1988 as
amended, for securing the safety of the public and for ensuring a proper and sufficient supply of electrical energy. The effect of section (2) of the Regulations is to
confer on BS 7671, by reference to the IEE Wiring Regulations, ‘deemed-to-satisfy’
status, in that under closely constrained circumstances the supply of energy to a customer whose installation complies with the provisions of BS 7671 cannot be refused
by the electricity supply authority on grounds of safety alone.
This reference to BS 7671 provides further confirmation of the status as a
national standard. In order to avoid the delegation of law-making powers to a body
which is not subject to direct parliamentary authority (in this case, the Institution
of Electrical Engineers), the Regulations provide for the approval of any amendment or addition to BS 7671 by the Secretaries of State for Energy and for
Scotland. As a matter of record, this approval has been granted by both Secretaries
of State for all editions of the Wiring Regulations since 1937 up to and including
the 16th edition.
Another example of the use of British Standards in the law relevant to electrical
installations is provided by the Low Voltage Electrical Equipment (Safety) Regulations of 1989, made under the Consumer Protection Act of 1987. In part, the
purpose of these Regulations is to implement the EEC Directive on low-voltage
electrical equipment. Although the regulations do not in themselves include references to equipment standards, Regulation 6 states that electrical equipment which
satisfies the safety provisions of harmonised standards shall be taken to satisfy the
requirement that the equipment is safe and constructed in accordance with the principles generally accepted within the member states of the European Economic
Community as constituting good engineering practice in relation to safety matters.
To clarify the Regulation, the Department of Trade and Industry – Consumer Safety
Unit has issued Guide to the Low Voltage Electrical Equipment (Safety) Regulations
1989. The guide is intended to assist suppliers of electrical equipment and enforcement authorities to understand the effects of the regulations. Although not an
authoritative interpretation of the Regulation, which is a matter for the courts, the
guide seeks to explain the Regulations in general terms and does not attempt to
Standards, Specifications and Codes of Practice
315
address detailed issues. The guide gives the following order of precedence for the
conformance of equipment to the Directive:
(1) Conformance with the safety requirements of a harmonised European standard
(2) Where a harmonised European standard has not been drawn up or published,
conformance with the safety provisions of an IEC publication which has been
published in the Official Journal of the European Communities
(3) Where no European or International standard exists, conformance to the safety
provisions of a British Standard (i.e. a purely national standard).
While it is not mandatory for electrical equipment to conform to any published standard, perhaps because it is an innovative product, this equipment must nevertheless
comply with the basic requirement to be safe, paying due regard to the principal
elements of the safety objectives. There will be no presumption of conformity, hence
these products will be open to challenge by the enforcement authorities, at any stage
in the supply chain.
A third legal requirement of interest to those concerned with electrical installations stems from the Health and Safety at Work etc. Act 1974 as amended, which is
applicable to all places of employment. This Act lays a general duty (every employer
to ensure the health, safety and welfare at work of his employees and not to expose
members of the public to health or safety risks). An employer can go a long way
towards satisfying the law by ensuring that all equipment on his premises is manufactured, installed and maintained in accordance with appropriate British Standard
specifications and codes of practice. Proof of this fact would be powerful defence
against any prosecution under the Act. Indeed, it is commonly considered to be most
unlikely that the Health and Safety Executive would bring such a case before the
courts. Indeed, to do so could be regarded as illogical as the constitutions of the BSI
committees responsible for all of the relevant standards include representation from
the Health and Safety Executive.
EUROPEAN UNION (EU)
The final link in the chain which binds standards and regulations together arises
from the fact that British law is, to a specific and carefully controlled extent, subject
to the law of the EU. One of the fundamental purposes of the EU is that expressed
by Article 100A of the Treaty of Rome, aimed at the development of a true Single
European Market.
After preparatory work by civil servants, the governments of member states of
the community may agree by qualified majority to issue Directives intended
to abolish or prevent technical barriers to trade (the New Approach). The obligations of such Directives rest with the governments of the member states that have
to take whatever legal action necessary to comply with the requirements of the
Directive in question. The principle of reference to standards in European legislation is well established, and a number of Directives make reference to European
standards published by CEN and CENELEC, either on a mandatory or ‘deemedto-satisfy’ basis.
316
Handbook of Electrical Installation Practice
In the area of electrotechnical products, harmonisation of national legal requirements was achieved in 1973 by Directive 73/23/EEC on the harmonisation of the
laws of member states relating to electrical equipment designed for use within
certain voltage limits – commonly known as the Low Voltage Directive (LVD).
Although the LVD has no direct bearing on legislative requirements for electrical
installations, it does have an indirect effect. It is concerned with the removal of barriers to community trade in any electrical equipment designed for use with a voltage
rating of between 50 and 1000 V (for alternating current) and between 75 and 1500
V (for direct current), with only the very limited exceptions of electrical equipment
for use in explosive atmospheres, medical equipment, electrical parts for goods and
passenger lifts, electricity meters, domestic plugs and socket-outlets, electric fence
controllers and specialised electrical equipment for use on ships, aircraft and
railways. Also excluded is radio-frequency interference.
The central provision of the LVD (contained in Article 2), is that ‘the Member
States shall take all appropriate measures to ensure that electrical equipment may
be placed on the market only if, having been constructed in accordance with good
engineering practice in safety matters in force in the Community, it does not endanger the safety of persons, domestic animals or property when properly installed and
maintained and used in applications for which it was made’.
Although the Directive includes (in Annex 1) eleven very basic safety objectives,
it effectively established formal criteria for the definition of the concept of safety
by reference to harmonised standards drawn up by common agreement between
the national electrotechnical committees meeting together in CENELEC. The LVD
contains many other administrative provisions, particularly those relating to the
legal burden of proof that equipment is safe. Its essential condition is that no
member state may by administrative action raise a technical barrier to the import
of electrical goods manufactured within the EU in compliance with an appropriate
CENELEC harmonisation agreement.
One consequence of the rules of procedure of CENELEC is that this protection
extends to manufacturers whose goods comply with harmonised national standards.
Thus, in the field of electrotechnical products, the LVD has created a true ‘common
market’, resting on the foundation of agreements between the national electrotechnical committees of the Community countries meeting together in
CENELEC. In fact, the practical consequences of the LVD run wider than the EU
members, as the CENELEC member committees also include those from EFTA
and other countries.
This New Approach model is now being actively promoted globally by the
European Commission, member states and European and national standards
bodies, as an effective tool in the promotion of free trade.
CONCLUSION
The purpose of this chapter has been to explain the importance of standards and
their crucial relationship with legislative requirements. It has been demonstrated
that national, European and international standards are closely intertwined, and
that those affected by these standards have an obligation to participate in their
Standards, Specifications and Codes of Practice
317
preparation. Further, it has been explained that the provisions of standards are
subject to and often supportive of the overriding requirements of both British
and European laws. As no part of modern life remains untouched by standards, it
follows that all sections of the community have a self interest in participating in
their development.
CHAPTER 13
Distribution Transformers
G.P. Harvey, CEng, MIEE
Revised by K. Frewin, CEng, MIEE
(Power Engineering Services)
Power distribution throughout most of the world, before the final consumer voltage,
is at voltages usually between 10 and 13.8 kV, and although some old systems of 5.0,
5.5 and 6.6 kV still remain, these are rapidly being replaced with a higher voltage
on economic grounds. The declared no-load voltage of the low voltage distribution
network in Great Britain has been subject to harmonisation with the European
Union, and was redeclared as 230 V phase to neutral, +10% and -6% on 1 January
1995, and is likely to be revised in the year 2008 to 230 V ±10%.
Oil-immersed distribution transformers, for use by British electricity supply
authorities, are usually designed to comply with Electricity Supply Industry
Standard 35–1. This specification covers ratings from 16 kVA to 1000 kVA, but
ratings of up to 2500 kVA are not uncommon. Distribution transformers may
be suitable for ground mounting, or pole mounting in rural electrification schemes.
The rating of pole-mounted designs is limited by weight considerations, but units
of up to 315 kVA have been supplied for use by Electricity Distributors. In order
to retain simplicity of design, the majority of liquid-immersed distribution transformers are naturally cooled. Forced air cooling, when required, is applied to
liquid-immersed transformers having ratings in excess of 5000 kVA and occasionally to dry-type transformers, particularly resin encapsulated types. It is
possible to increase the ratings of certain dry-type transformers by up to 50% by
the application of forced air cooling. For transformers supplying loads which
have occasional peaks, this type of design can offer advantages in both cost and
physical size.
TYPES OF TRANSFORMER
All transformers covered by this chapter should comply with the requirements of
BS EN 60076, which is equivalent to IEC 76: 1976, for liquid-immersed types and
IEC 726: 1982 for dry types. The British Standard defines a transformer as a static
piece of apparatus which by electromagnetic induction transforms alternating
voltage and current between two or more windings at the same frequency and
usually at different values of voltage and current.
318
Distribution Transformers
319
Table 13.1 Preferred values of
rated power for three-phase
transformers.
There are two basic types of distribution transformer in common use today: one
in which the core and windings are enclosed in a liquid-filled tank which provides
cooling and insulation, and the other where the core and windings are cooled
directly by air. Liquid-filled transformers can again be sub-divided into units using
flammable substance (mineral oil) and those using various types of fire-resistant
liquid (silicone liquid or synthetic hydrocarbon).
Dry-type transformers are also available in two distinct types: those with the insulated turns of the winding directly in contact with the cooling air, and those with
the complete windings encapsulated within a moisture-resistant cladding of epoxy
resin. Preferred ratings are listed in Table 13.1, but dry-type distribution transformers are rarely used in ratings much below 500 kVA. The ratings of individual
transformers within installations are determined by load requirements, the physical
space available, the distribution system voltage regulation, and the high voltage
switchgear fault rating.
The heart of the conventional three-phase distribution transformer is a laminated
electrical sheet steel core of three limbs. Each limb carries two concentrically wound
coils: the secondary (low voltage) inside nearest the core and the primary (high
voltage) on the outside, the whole being contained within an enclosure of steel. In
the case of the liquid-filled transformer the enclosure consists of a leak-proof
tank while the dry-type transformer merely requires a ventilated casing to enclose
the live parts. Some designs of dry-type transformer are totally enclosed in nonventilated sheet steel housings, and have an IP rating of 55 to BS EN 60529. These
transformers are used in installations where environmental contamination would
preclude the use of conventional dry-type designs, but their superior resistance to
fire is required.
Tappings are usually included on the h.v. windings of distribution transformers
to alter the turns ratio between the high- and low-voltage windings and thereby
to compensate for variations in primary supply voltage in order to maintain the consumer voltage within the statutory limits. On distribution transformers taps are
selected by means of an off-circuit device; the transformer must be disconnected
from the supply before the taps can be changed. The normal variation in supply
voltage provided for by high voltage tappings is ± 2.5% and 5%. Dry-type
320
Handbook of Electrical Installation Practice
distribution transformers are normally provided with bolted link arrangements for
primary tapping selection. It is not recommended that tapping switches are used for
the adjustment of high voltage tapping on dry-type transformers, as they are subject
to contamination, which has led to failures in service.
Winding conductors are usually copper strip, or round wire. Some designs of distribution transformer use copper sheet, sometimes called foil windings, for the l.v.
coils. Aluminium sheet is used for both the l.v. and h.v. windings of some designs of
resin encapsulated transformer. Conductor insulation materials are chosen for the
particular application, ranging from cellulose papers for liquid-immersed types, to
synthetic materials, capable of withstanding continuous high temperatures, for drytype designs.
Mineral oil-filled transformers
This is the most common type of distribution transformer. It can be found on electrical supply systems in every country of the world. Although the insulating oil is a
flammable liquid, the reliability of the oil-immersed transformer has been proven
over many years on supply systems where security of supply is of the utmost importance. However, mineral oil is flammable and although most fault conditions that
occur within the windings of a transformer result in no more than a discharge of
oil, it is possible, particularly when an electrical arc occurs just below the surface of
the oil, for it to be ignited. For this reason oil-immersed distribution transformers
are usually positioned outside buildings within a suitable fence enclosure or in separate brick-built buildings away from personnel.
Where transformers filled with mineral oil are sited within an occupied area, it is
usual to find some type of safety provision. This may take the form of bund walls,
soak-away pits, or automatic fire-extinguishing equipment. However, the additional
costs of the civil engineering work required can make the installation of a mineral
oil-filled transformer uneconomic. In these instances, a dry-type transformer, or a
transformer filled with a high fire-point liquid, is often selected for the installation.
The integrity of the insulation system of an oil-immersed transformer relies partly
on the condition of the oil. It has been common practice on most established supply
networks in the world to let transformers breath naturally as the insulating liquid
expands and contracts with load. However, it has also been recognised that some
form of protection system that prevents the contamination of the liquid by air-borne
pollutants has the advantage of a longer insulation life, particularly when load
factors are high.
The simplest form of oil protection system, which is perfectly adequate for most
installations of distribution transformers below 500 kVA installed in the temperate
zones of the world, is a silica-gel dehydrating breather. Here, the air drawn into the
transformer tank during reduced load conditions is passed through an oil bath, to
reduce solid contaminants, and then through the dehydrating crystals of silica-gel
to remove the moisture. It is essential, however, that the silica-gel crystals are maintained dry and replaced as soon as the colour changes from blue to pink.
Probably the most common form of oil protection system is found with the conservator or expansion vessel; this has a sump which traps most air-borne pollutants
(Fig. 13.1).
Distribution Transformers
321
Fig. 13.1 A 500 kVA 11 kV/380 V mineral oil-filled transformer with conservator
(Bonar Long Ltd).
The most obvious method of eliminating oil contamination is to seal the tank from
the outside air and design it to tolerate the pressures developed by the expanding
liquid coolant (Fig. 13.2).
Because of gas solubility in oil these pressures are never very high and rarely
exceed 0.43 kg/cm2 under steady load conditions.
The development of special machinery which automatically folds and welds the
steel plate into deep corrugations to form the transformer tank side, has allowed
the corrugated tank to become more cost effective.The steel plate is usually between
1.2 and 1.5 mm thick, resulting in a tank which is both light and compact,
the mechanical strength being obtained by the deep closely-spaced corrugations.
Plate widths of up to 2000 mm and depths of 400 mm allow transformers of up to
5000 kVA to be cooled by this method, but their general application is in distribution ratings of up to 1600 kVA. The ability of the corrugated panels to flex has
322
Handbook of Electrical Installation Practice
Fig. 13.2 A sealed oil-filled transformer rated at 1600 kVA for use in a cement works
(Parsons Peebles Distribution Transformers).
enabled the development of the fully sealed corrugated tank design. In this instance
the tank is completely filled, expansion of the liquid being accommodated by flexing
of the tank walls. The liquid within the tank has no contact with the atmosphere,
which assists with the preservation of the transformer insulation system, as well as
reducing the maintenance requirements. Corrugated transformer tank designs have
been in service for in excess of 30 years and are now established as a reliable method
of tank construction.
Askarel-filled transformers
Askarel-filled transformers were introduced about 50 years ago when the demand
arose for a fire-resistant liquid to replace the mineral oil in units that were to be
installed in occupied buildings. The increasing concern for the safety of people
should a fire occur in a mineral oil-filled transformer placed pressure on manufacturers to find an alternative coolant.
Askarels appeared on the market under a variety of names such as Pyroclor,
Inerteen,Aroclor and Pyranol.They comprise a mixture of polychlorinated biphenyl
(pcb) and trichlorobenzene (tcb), the latter being used to reduce the viscosity of
the pcb. Basically, apart from a few synthetic resin products, the design of the
transformer remained unaltered from the mineral oil-filled unit, but the use of this
liquid has introduced hazards not appreciated at the time. The implementation of
EEC Council Directive 85/467/EEC banned the sale of electrical equipment containing greater than 0.01% by weight of pcb. This Directive became operative in
1986 and effectively stopped the sale of askarel-filled distribution transformers
within the EU.
Distribution Transformers
323
During the last few years it has become widely realised that pcbs are toxic and
are also resistant to biological and chemical degradation. Research has shown that
if ingested they can persist in the fatty tissues and cause damage to organs of the
body. In the event of a fire involving an askarel-filled transformer, any of the coolant
subject to partial combustion at low temperatures will form toxic by-products, which
will contaminate the surrounding area.
Many of the transformers that were filled with pcbs have been in service for
more than 15 years. Some of the older ones have developed slight leaks, usually at
gasketted joints, and are easily repaired. There have been reports of welds leaking
after 15 to 20 years of service and although there is no substantive evidence to show
that pcbs attack metal, it is of concern that so many tanks have started to leak. To
guard against the danger of spillage due to leaks and internal faults some transformer users are having the pcbs removed and replaced by an alternative fireresistant liquid. Special techniques have been adopted to carry out this replacement,
the operation being termed retrofilling (Fig. 13.3). Because this is a specialist
function requiring a high degree of expertise, it must be performed only by organisations trained and equipped to do it.
Once removed the pcb has to be taken to an incinerator for destruction and again
this is a specialist operation requiring skills and plant available from only a few
organisations. The toxicity of pcbs and their handling are described in the UK
Department of Environment publication Waste Management Paper No. 6.
Another school of thought insists that the pcbs cannot be completely removed
by any retrofilling process and that the only sure way of removing pcbs from the
environment is for the transformer to be completely replaced by one containing a
harmless liquid.
A number of countries have banned the use of pcb in any form. Others continue
with its use in transformers and capacitors. All recognise the potential danger that
exists if a large local spillage does occur.
Other fire-resistant types
There are a number of liquids on the market for which suitability as a transformer
coolant and resistance to fire is claimed. It is not possible to examine these liquids
in detail but one is described as a synthesised ester and is marketed under the trade
name of Midel 7131.
Another is described as a highly saturated paraffin oil and is marketed under the
name of Rtemp.
Probably the most well known, because of its long time use in other industries, is
silicone fluid. This is marketed by a number of companies under their own trade
names. Other fluids that are available for use in transformers, but which are nonflammable, include Formel, Wecasol and Ugilec T. These materials contain solvents,
such as trichlorobenzene and perchloroethylene, and have not found such ecological acceptability as silicone or synthetic ester (Midel) materials. The general criteria
for a low fire-point fluid, as defined by Factory Mutual Research Corporation, is that
the fire point be at least 300°C. All the above-mentioned fluids meet this requirement, but other aspects of fire performance, such as heat of combustion, etc., must
also be considered when selecting a high fire-point fluid for use in transformers.
324
Handbook of Electrical Installation Practice
Fig. 13.3 Retrofilling of an askarel-filled unit in situ by R.F. Winder Ltd. The liquid is being
replaced by silicone under carefully controlled conditions. Protective clothing is
being worn by the operators.
The most favoured high fire-point fluids, at present, are the silicone based materials and the synthetic ester types (Midel). The silicone fluids used in transformers
have a viscosity of approximately twice that of mineral transformer oils at 20°C;
other characteristics make their performance not dissimilar to transformer oil.
Accordingly, there is very little difference in the external appearance of a silicone
fluid cooled transformer, or synthetic ester-cooled designs with their equivalent
mineral oil-filled units (Fig. 13.4).
The cellulosic insulation materials commonly used in the manufacture of oilimmersed transformers are in general compatible with silicone and synthetic ester
fluids. When impregnated with these materials they can be operated at higher temperatures than is associated with mineral oil-filled transformers before thermal
degradation takes place, but this feature has yet to be recognised by the relevant
specification-producing bodies. Care should be taken when specifying gaskets and
Distribution Transformers
325
Fig. 13.4 Silicone-cooled distribution transformer; 2200 kVA complete with output
circuit-breakers (Goodyear Transformers Ltd).
fittings for synthetic fluid cooled transformers, as materials and components used
with mineral based oils may not be compatible.
Transformer manufacturers are looking at the future designs of synthetic fluidfilled transformers in order to take advantage of the high temperature capabilities
of these transformer coolants. Such transformers may well result in savings in
weight, size and cost, as it will be possible to make better economic use of these
expensive materials.
Dry-type transformers
Dry-type transformers are defined by IEC 726 as designs where the core and windings are not immersed in an insulating liquid. Cooling is usually by natural air circulation through the windings. Permissible winding temperature rise depends on the
type of insulation used on the winding conductors and between the windings.
Transformer windings with Class A insulation are limited to a temperature rise
of 60°C. When Class C insulation is used 150°C is the limit. All dry-type transformers with Class B insulation and above are considered to be fire resistant to
326
Handbook of Electrical Installation Practice
some degree because the volume of combustible material is small and it does not
maintain combustion. The modern Class C transformer (Fig. 13.5) is almost completely fire proof because the Nomex insulation used is self-extinguishing. Temperature rise limits are discussed in detail later.
Two types of dry transformer are available. The conventional arrangement was
developed from the old Class B transformer. It uses high-temperature aromatic
Polyaramid paper both for conductor covering and solid insulation. Large air
cooling ducts between the windings and between the layers of the windings provide
the cooling. This arrangement has the advantage of low cost and many years of satisfactory service close to load centres in the normally dry environment of an indoor
installation.
It is not advisable, however, to leave this type of dry transformer unexcited for
long periods of time in a damp atmosphere without some form of warm air circulation through the windings. Impulse voltage levels of 60 and 75 kV are available
for the modern Class C transformer.
Because of the large cooling ducts between windings and the subsequently high
surge impedance, the current chopping characteristics of some vacuum circuit-
Fig. 13.5 A 1000 kVA 11 kV/433 V Class C dry-type transformer (Parsons Peebles
Distribution Transformers).
Distribution Transformers
327
breakers can produce very high transient voltages in dry-type transformers. It is
advisable that transformer manufacturers are made aware of the intention to use
vacuum circuit-breakers.
The newer development of dry-type transformer employs windings that have
been completely encapsulated in epoxy resin (Figs 13.6 and 13.7). Designs are impervious to the ingress of moisture to the windings, and damp environments have
very little effect. Cast-resin transformers can be manufactured by several different
methods. Coils may be cast in a mineral-filled resin system, the wall thickness of
the casting being in the order of 5–8 mm, which gives the winding considerable
Fig. 13.6 A 1000 kVA resin-cast transformer (Goodyear Transformers Ltd).
328
Handbook of Electrical Installation Practice
Fig. 13.7 A 1600 kVA fan-cooled resin-cast transformer (Goodyear Transformers Ltd).
mechanical strength. Modern practice with cast resin transformers of this design is
to incorporate coarse weave glass fibre matt reinforcing material into the inner and
outer walls of the coils, thus allowing the thickness of resin to be reduced, hence
reducing the resin content and improving both the heat dissipation and fire resistance of the transformer. Another commonly used manufacturing method is to wind
glass fibre sheet and rovings into the coils and to impregnate the complete assembly with a low-viscosity non-filled resin system. Both methods of manufacture
produce robust windings, well able to withstand the effects of short-circuit forces.
It is important in the winding design of resin encapsulated transformers that the
Distribution Transformers
329
conductor material and the resin system have very similar rates of thermal expansion. This is achieved by the mineral filler added to the resin, or by the effect of the
glass fibre materials wound into the coils prior to impregnation. The epoxy resin
encapsulated transformer is generally more costly to manufacture than the conventional dry-type transformer, and therefore in many indoor installations the additional cost may be difficult to justify.
Both types of dry transformer need to be housed within a waterproof building
and sited within an enclosure to prevent physical contact with any live parts, in order
to comply with the IEE Wiring Regulations for safety.
It has become practice in America and the UK to build dry-type transformers as
self-contained units within a metal casing with h.v. and l.v. cable boxes mounted on
to the sides as with the liquid-immersed type.
The development of the resin-encapsulated transformer in Europe led to these
transformers being positioned inside wire mesh enclosures without any casing.
When costs of these two units are considered, the form of protection for the general
public must be taken into account.
The windings of the Class C dry-type transformer are usually quite conventional,
although with the introduction of newer and more sophisticated winding machinery, l.v. windings wound with wide strip aluminium or copper are becoming more
popular with manufacturers.
The windings of cast resin transformers may be of copper or aluminium; where
aluminium is used it is generally in the form of thin sheet, generally termed foilwindings. Many designs of l.v. winding, either copper or aluminium, are of the foilwound type, but the designs using glass fibre as the filling material for the resin are
usually wound with copper strip conductors for both l.v. and h.v. windings.
PERFORMANCE
When a transformer is selected for a particular application, prime cost should never
be the only consideration. In many cases it plays a very small part in the overall cost.
Factors which also govern choice of a particular transformer should include load
factor, cost of losses and efficiency, maintenance costs, fire-resistant qualities and
associated building costs, space limitations and ambient temperature, as well as prime
cost. These matters are discussed below but not necessarily in order of importance.
Prime cost is always a consideration. The amount of capital available for an electrical distribution network often governs the type of equipment that is purchased,
irrespective of the many advantages and long-term financial benefits accruing from
buying more expensive plant. The first cost of the various transformers discussed is
shown by the nomogram (Fig. 13.8) in which it will be seen that the mineral oil unit
is the cheapest and the cast-resin design the most expensive at some 80% more.
Locating the mineral oil-filled unit close to load centres inevitably involves the
installation of pits and drains and automatic fire protection. Special floor, roof and
door construction are necessary. Even so, the cost of mineral oil-filled transformers
is so low relative to the fire-resistant alternatives that the decision to have the risk
and limit the effect is taken over eradicating the risk. In any event there is some
risk, even with fire-resistant transformers.
330
Handbook of Electrical Installation Practice
Fig. 13.8 A nomogram showing comparative capital costs of various types of distribution
transformers.
Losses
No-load and load losses in a transformer result in loss of efficiency. They are the
reason for the major running cost of a transformer. They have to be paid for, yet
result in heat which is normally dissipated to the atmosphere.
The comparison between various manufacturers’ liquid-immersed transformers
can be made quite simply. It will be obvious that a transformer with a no-load loss
of 700 W consumes 2628 units of electricity in a year less than a similar transformer
with a no-load loss of 1000 W, if they are both excited continuously.
The cost of load losses of course depends on the load factor (LF) and does not
vary greatly between manufacturers for the same transformer rating.
Quite large differences in losses do occur, however, between the various types of
fire-resistant transformer, and running costs could well be a deciding factor in the
choice of a particular fire-resistant transformer.
Table 13.2 gives a comparison of losses between two types of fire-resistant transformer. The cast-resin values were taken from European manufacturers’ published
literature. The liquid-immersed losses are those which are available from a number
of companies in the UK. It is quite evident that load factor and tariff structure play
a most important part in any economic comparisons.
When examining this table the importance of the iron loss is more obvious at low
load factors. For example, at 50% load factor lower iron loss of the silicone liquidfilled designs compared with the cast-resin makes them much more attractive than
at higher load factors. At 80% there is not much to choose between the designs,
while at 100% load factor the cast-resin transformers are more cost effective. In the
UK the average industrial load factor on a transformer is probably between 50 and
60%, but where security of supply is of supreme importance the use of two transformers reduces this value to below 50%. Even lower load factors can apply where
both load growth and supply security have to be taken into account.
Distribution Transformers
331
Table 13.2 Comparison of losses of cast-resin and silicone liquid-filled transformers.
The life of a transformer is an essential part of the overall cost equation. Mineral
oil-filled transformers have been in use on electrical supply networks for a great
many years and the life expectancy of the average distribution transformer is known
to exceed 30 years.
The silicone liquid-filled transformer with normal temperature rise characteristics has an insulation system virtually identical to mineral oil-filled transformers and
the viscosity of the fluid is not significantly different. The transformer life of the
silicone-filled transformer can be assumed to be very similar.
The insulation system of the modern dry-type Class C transformer dates back to
about 1960 in the UK. More than 40 years’ experience have shown this to be a very
reliable unit.
The resin-encapsulated transformer was first introduced more than 25 years ago
and its life has been favourably assessed.
A Canadian manufacturer (Polygon Industries) has produced figures of electrical losses for all types of distribution transformers considered in this chapter and
they are given as Table 13.3. While it must be remembered that these values apply
to the American 60 Hz system, it will be seen that no difference is made between
the losses of any of the liquid-filled types and that these are considerably lower than
the dry-types at all loads between 25% and 100%.
It is interesting to note the difference between the values given in Tables 13.2 and
13.3 for the cast-resin and silicone liquid-filled 1000 kVA transformer with regard
to no-load and load losses. The 60 Hz system has a significant effect on the no-load
loss.
The importance of assessing the value of the losses of the transformers for any
contract cannot be over-emphasised. Most British manufacturers are in a position
to offer low-loss designs as standard because of their familiarity with those parts of
the world where losses are highly capitalised.
These low-loss units do have a higher prime cost but it may well be an economic
proposition to pay a higher cost and take greater advantages in reduced running costs.
There are two sides to every story and although it may be proved that paying
20% more for low-loss transformers can be justified by lower running costs, 20%
fewer customers may be reached or the system may have a 20% lower capacity for
332
Handbook of Electrical Installation Practice
Table 13.3 Electrical losses comparison of 15 kV 1000 kVA transformers with a BIL* of
95 kV.
* BIL = Basic insulation impulse level.
revenue earning. In areas with a high rate of growth this second consideration may
be of greater importance.
Temperature rise
In temperate climates the differences in allowable temperature rise of liquid-filled
and dry-type transformers are not important for most installations. There are
instances, however, where the high ambient in which the transformer is sited may
well limit the rating of a standard transformer to something below the nameplate
value. There are also instances where the heat of the losses of a transformer could
affect the functioning of sensitive electronic equipment. An example of both applications can be found in the first case where an oil-immersed transformer is used to
supply power to an induction furnace or an annealing furnace. An arc furnace transformer must, because of the very low voltage, be close to the furnace where ambient
temperatures are very high.
An example of the heat of a transformer affecting the operation of sensitive
equipment can be found when power supplies to computers are considered. A
large dry-type transformer in an open installation might well produce enough
heat to create difficulties. Even power diodes and thyristors have a very limited
temperature range and care is needed when transformers are sited for these
applications.
Tables 13.4 and 13.5 indicate the permissible limits of temperature rise for the
two types of transformer. Where ambient temperatures are very high and transformers are to be mounted indoors, one might look favourably on the dry-type Class
C transformer with its capacity for operation at high temperatures. But in making
such judgement other factors need to be taken into account.
Table 13.4 Temperature rise limits for dry-type transformers.
Distribution Transformers
Note: Insulating materials may be used separately or in combination provided that in any application each material will not be subjected to
a temperature in excess of that for which it is suitable, if operated under rated conditions.
* In accordance with IEC Publication 85, Recommendations for the Classification of Materials for the Insulation of Electrical Machinery and
Apparatus in Relation to their Thermal Stability in Service.
†
For certain insulating materials, temperature rises in excess of 150°C may be adopted by agreement between the manufacturer and the
purchaser.
333
334
Table 13.5 Temperature rise limits for oil-immersed type transformers.
Handbook of Electrical Installation Practice
Note: The temperature rise limits of the windings (measured by the resistance method) are chosen to give the same hot-spot temperature
rise with different types of oil circulation. The hot-spot temperature rise cannot normally be measured directly. Transformers with
forced-directed oil flow have a difference between the hot-spot and the average temperature rise in the windings which is smaller
than that in transformers with natural or forced but not directed oil flow. For this reason, the windings of transformers with forced-directed
oil flow can have temperature rise limits (measured by the resistance method) which are 5°C higher than in other transformers.
Distribution Transformers
335
The susceptibility of the dry-types to dust-laden atmospheres and the exclusion
of vermin, therefore requiring frequent maintenance checks, might well exclude drytypes from overseas installations.
It should also be borne in mind that the temperature rise limitations specified in
BS 171 assume the use of cellulosic materials with a Class A limitation in mineral
oil to BS 148.Tests on standard solid insulating materials normally used with mineral
oil-immersed transformers have shown that when these materials are impregnated
with silicone fluid they can operate for longer periods of time at elevated temperatures without loss of transformer life, and short time overloads without thermal
expansion problems.
Where transformers are situated in areas of very high ambient temperature, or
where compact dimensions are essential, it is possible to design suitable transformers to suit these circumstances. By using special high-temperature insulation, and
taking advantage of the high-temperature withstand properties of silicone or synthetic ester fluids, transformers having high-temperature withstand properties, as
well as very compact dimensions, can be produced.
Loading guide
The British Code of Practice BS 7735: 1994 Guide to loading of oil-immersed transformers indicates how oil-immersed transformers may be operated in different conditions of ambient temperature and service, without exceeding the acceptable limit
of deterioration of insulation through thermal effects. Although specifically related
to oil-filled units, similar reasoning can be applied to transformers cooled by other
liquids.
The object of the guide is to give the permissible loadings, under certain defined
conditions, in terms of the IEC Publication 76 rated power of the transformer, so
that planners can choose the required rated power for new installations. Basically,
the cooling-medium temperature is 20°C, but deviations from this are provided for,
in such a way that the increased use of life when operating with a cooling-medium
temperature above 20°C is balanced by the reduced use of life when it is below
20°C.
In practice, uninterrupted continuous operation at full rated power is unusual,
and the guide gives recommendations for cyclic daily loads, taking into account seasonal variations of ambient temperature. The daily use of life due to thermal effects
is indicated by comparison with the ‘normal’ use of life corresponding to operation
at rated power in an ambient temperature of 20°C.
Two examples of the use of the curves are given in the Code and are reproduced
in Table 13.6. It is necessary to define the four symbols used in the tables in order
to understand the examples. These symbols are:
K1 = initial load power as a fraction of rated power
K2 = permissible load power as a fraction of rated power (usually greater than
unity)
t = duration of K2 (h)
qa = temperature of cooling medium (air or water) (°C).
336
Handbook of Electrical Installation Practice
Table 13.6 Loading guide for oil-immersed transformers (CP 1010).
ONAN and ONAF transformers: qa = 20°C. Values of K2 for given values of K1 and t.
Note: In normal cyclic duty the value of K2 should not be greater than 1.5. The values of K2 greater
than 1.5, underlined, apply to emergency duties. (See Clause 3.)
The + sign indicates that K2 is higher than 2.0.
Note that K1 = S1/Sr and K2 = S2/Sr where S1 is the initial load power, S2 is the
permissible load power and Sr is the rated power.
Example 1
A 1000 kVA ONAN transformer has initial load power 500 kVA. It is required to
find permissible load power for 2 h at an ambient temperature of 20°C.
Cooling: ONAN qa = 20∞C, K = 0.5, t = 2 h.
From Table 13.6, K2 = 1.53 but the guide limit is 1.5. Therefore permissible load
power for 2 h is 1500 kVA (then returning to 500 kVA).
Example 2
With qa = 20°C an ONAN transformer is required for 1400 kVA for 6 h and 800 kVA
for the remaining 18 h each day.
1400 800 (S2 S1 ) = 1.75
From the curve drawn, using the data of Table 13.6, on the t = 6 line, the values of
K2 and K1 giving K2/K1 = 1.75 are K2 = 1.18 and K1 = 0.68 (Fig. 13.9). Therefore the
rated power is:
Sr = 1400 1.18 = 800 0.68 = 1180 kVA
It must be pointed out that the preceding examples relate entirely to the
transformer and the effect of cyclic loading on transformers. If cyclic loading is anticipated, however, at the time of installation, consideration must be given to the
extra demand put on the switchgear. Mention must also be made that if settings of
Distribution Transformers
337
Fig. 13.9 Illustration of Example 2.
protective relays are to be adjusted to account for cyclic loading, then the degree
of protection against continuous overloads or faults is very much reduced.
Fire resistance
Dry-type and liquid-filled units already mentioned (except mineral oil), are designated fire-resistant designs, but that does not mean that the materials used will
not burn. Rather it refers to their high fire point (the temperature at which the
material continues to burn when subject to a flame on the surface). This is the significant figure when considering fire resistance; it must be well above the maximum
temperature reached by a transformer operating at its maximum overload condition in a high ambient. For reasons stated earlier, askarel-filled units are not acceptable and so one is left with designs incorporating other fire-resistant liquids and the
two dry-types.
338
Handbook of Electrical Installation Practice
Table 13.7 indicates the fire point temperature of some fire-resistant designs and
shows that there is not much to choose between the different materials. But one
must also consider the nature and toxicity of the smoke given off by materials when
they are burning, together with other characteristics, to form a judgement as to the
best to select.
The rate of heat release of a burning substance is also important, for it governs
the size and nature of the enclosure surrounding the transformer.
Most fire officers agree that smoke is the most serious hazard to life in any
fire for it blinds, confuses and suffocates and can cause deaths well away from the
centre of the fire. Epoxy resins, like most solid polymers, produce thick black smoke
when burning, while silicone liquid generates a white vapour less dangerous in
content and much easier to see through. Midel 7131 contains petroleum oils and
certain synthetic oxyhydrocarbons but these are classed as of negligible toxicity
when burning.
The rate of heat release of burning materials consists of two components, convective and radiative, the former being the higher value. The convective value provides a measure of the damage the burning material can do to a roof or any structure
above the fire; the radiative indicates how much damage a fire could do to the walls
and surrounding equipment. Table 13.8 shows these values for some fire-resistant
materials.
Table 13.7 Fire-point
temperature of some fire-resistant
transformers.
* For comparison purposes mineral oil
is 170°C. Askarel is non-flammable.
†
These designs are virtually fireproof
Table 13.8 Values of rate of heat release (RHR) for some
fire-resistant materials.
Distribution Transformers
339
Also important is how a material reacts when burning. Silicone liquid forms a
silica crust and this assists in extinguishing flames. Some tests on the burning characteristics of epoxy resin showed that when heated with a bunsen burner, the material continued to burn when the flame was removed but did not when a welding
torch was the medium of the heat. Manufacturers of cast-resin transformers claim
that their designs do not make any appreciable contribution to the fire hazard
because of the very high non-flammable filler content. Many have been installed
within the past few years and are giving satisfactory service.
Class H dry-type transformers generally have superior fire resistance to most
other types, the use of suitable flame-retardant grades of insulation giving further
improvements in safety. The utilisation of an open winding construction, in conjunction with flame-retardant insulation materials, has resulted in the development
of the Securamid design of dry-type transformer (Fig. 13.10). Combustion tests, conducted on sample windings, have shown this type of transformer to have the best
fire-resistant properties of all the available dry-types.
TAPPINGS AND CONNECTIONS
This chapter, dealing as it does entirely with distribution transformers, will consider
only tappings normally selected with the transformer disconnected from the supply.
Fig. 13.10 A 500 kVA dry-type Securamid distribution transformer
(Goodyear Transformers Ltd).
340
Handbook of Electrical Installation Practice
A few years ago the standard distribution transformer had no tappings. It is
argued that, with a fully regulated 10 or 11 kV supply system as exists in most
western countries, tappings on distribution transformers are entirely unnecessary.
However, tappings on the h.v. windings have become part of the distribution
scene and in areas where long feeders remain, adjustment for h.v. variation can be
useful.
The standard off-circuit tapping range is 10% with two taps of 21/2 % above normal
and two taps of 21/2% below normal. In especially difficult areas most transformer
manufacturers would be quite happy to supply this range as all negative taps.
It is generally agreed that there should be some movement toward voltage standardisation within the EU. Inevitably the recommendations for the standard voltage
are almost as numerous as the countries involved and any rationalisation may well
involve an extended tapping range.
Off-circuit taps on distribution transformers are normally selected by a switch on
liquid-immersed transformers and links on dry-type transformers. Three- and fiveposition tapping switches are the most common in Europe. In certain difficult areas
of the world it is not unusual to see off-circuit tapping ranges of 15% or even 20%
specified. The costs of the special tapping switch and tapping arrangement make
these non-standard arrangements very expensive and they should be avoided if at
all possible.
Connections
Most 10, 11 or 13.8 kV distribution systems are supplied through system or network
transformers where the l.v. winding is star connected. The system is therefore
earthed via the neutral of the network or system transformer. For the satisfactory
elimination of triple frequency harmonics it follows that the 10, 11 or 13.8 kV
winding of distribution transformers should be delta connected. It is necessary on
l.v. domestic distribution systems that phase-to-neutral voltages are available and
that the neutral operates at or near to earth potential.
The most common winding connections are therefore either Dy 11, Dy 1, Dy 5
or Dy 7 with Dy 11 or its equivalent being widely used throughout the world. These
connections are shown in Fig. 13.11. This diagram also includes other winding connections including the delta zigzag which is discussed below. The vector relating to
the h.v. winding is taken as the vector of origin and the secondary phase relationship is related to the clock face. For example, Dy 1 where the secondary star lags
the primary by 30° corresponds to one o’clock.
The choice of phase relationship between the primary and secondary windings is
unimportant if only one transformer is used for a given site network. However, if
more than one transformer is involved then they must all have the same phase relationship or else it is impossible to parallel them or to switch over the supply to the
network from one transformer to another. More is said about parallel operation
below.
Delta/zigzag connections
There are a number of special applications where other winding connections are
important.
Distribution Transformers
341
Fig. 13.11 Designation of connections of some separate winding three-phase transformers
by connection symbols.
342
Handbook of Electrical Installation Practice
Local power supplies are often obtained from diesel engine or gas turbine generating sets. Voltages generated are often too low for economic power distribution,
and transformers are used to raise the generated voltage to a satisfactory value for
distribution, then reduce it back to domestic levels. Contractors often order two
identical delta-star transformers for this application, which results in an unearthed
and floating distribution system and a phase displacement between generated
voltage and user voltage of 60°.
It is necessary in this case to arrange for the generator-transformer to have a
delta-connected winding connected to the generator and a star connection for the
transmission voltage. With the connection Yd 1 there would be no phase displacement between the generated voltage and the user voltage, and the higher voltage
distribution system would have a star point for earthing.
There are still occasionally cases where unusual phase relationships exist from
old privately owned systems. Linking these into modern networks can be made
easier with the delta-interconnected star transformer or the star/interconnected-star
transformer. The interconnected star winding, by varying the values of the winding
sections, can be made to produce any phase relationship between primary and
secondary windings.
Large supplies of d.c. are essential for certain industrial application. Furthermore
12- and 24-phase systems of rectifier supply are necessary if harmonics in the supply
are to be kept to a minimum. The interconnected star transformer winding provides
the solution.
Terminations
Electrical connections to transformers are made with cable which is either carried
overhead on poles or pylons or buried in trenches in the ground. The former uses
fairly simple steel reinforced copper or aluminium conductors and relies on air
spacing between conductors for insulation.
Electrical cable for underground power distribution has solid insulating material
between conductors and usually has a metal protection on the outer surface which
is again protected against corrosion by an outer covering. At system voltage above
3300 V the underground cable becomes very much more complex and is beyond the
scope of this chapter.
Generally speaking, distribution systems above 33 kV are by the overhead system
and require bushing terminations on transformers. Distribution voltages of below 600
V in most of the cities and towns of Western Europe are by the underground method.
Underground cables have to be terminated by a method which does not expose
the inner conductor insulation of the cable to the elements and this inevitably means
some form of cable terminating box.
In the early days of power distribution the insulation most common to l.v. underground cables usually consisted of paper, cotton, jute, wax and hemp, etc. Although
thoroughly impregnated with wax and oil these materials were quite prone to moisture absorption. Cable terminating boxes were compound filled. Cable jointing and
cable box filling was a fairly complicated business which required considerable skill.
In spite of every effort failures in cable boxes were fairly common.
Distribution Transformers
343
The development of modern plastics such as polyvinylchloride and polyethylene,
etc. and their use in the cable industry has done much to simplify cable manufacture, cabling systems and termination. Almost all l.v. cable boxes are now air-filled
with a simple compression gland securing the metal sheath of the cable. Low-voltage
transformer terminations are usually an ‘all-in-one’ epoxy resin bushing plate
assembly with bolt-on connections.
The compound filling of 6.6, 10 and 11 kV cable boxes on distribution transformers has remained in many areas of the UK because the most common 6.6 and 11
kV cable is still paper insulated. Developments in the field of plastics have produced
cross-linked polyethylene cables where air-filled boxes with heat shrinkable sleevings eliminate the need for compound filling and greatly simplify the cable termination to transformers.
Dry-type transformers supplied in their own ventilated enclosures are generally
treated as liquid-immersed transformers and have cable boxes mounted on the
outside of the ventilated enclosure. Where the dry-type transformer forms part of
a complete installation on h.v. and l.v. switchgear, it is often required for the transformer to be supplied without an enclosure; h.v. winding connections are terminated
in bolted connections just above the core and windings and l.v. connections are generally terminated on busbars.
Cable-end terminations for installations of this type can still follow the same form
as the tankside cable box but with the three-phase bushings arranged and spaced
for copper connections in air.
The resin-encapsulated transformer was developed originally in Germany where
open installations are more commonplace. Special plug-in epoxy or moulded
polymer connectors and bushings, incorporating electrical stress relief screens, have
been developed by some companies and the incoming h.v. cable is simply laid into
a moulded cable holder and the bared conductor bolted to metallic inserts.
COOLING
Transformers are identified according to the cooling method employed and the
letter symbols used are indicated in Table 13.9. The simplest form is where the windings are cooled by natural air flow over the heated surface of the windings and core.
These are heated by the load and no-load losses respectively and the heat is transferred to the surrounding air by convection and radiation. This type of cooling is
described as air natural or AN by reference to Table 13.9.
The natural movement of air over heated coil surfaces is not particularly efficient.
Winding conductors, disc- and coil-separator winding shapes, and the roughness of
conductor insulation all help to create eddies in the air flow over the windings and
reduce the heat transfer from the winding to the air. Even a small amount of forcedirected air flow over the windings improves the heat flow, and ratings are increased
significantly.
A dry-type transformer cooled by direct forced air is designated as AF. A drytype transformer which has natural cooling and the facility for automatic fan operation should the temperature of the windings increase beyond normal limits has two
344
Handbook of Electrical Installation Practice
Table 13.9 Letter symbols.
ratings specified followed by AN/AF; for example, 1000/1250 kVA AN/AF dry-type
Class C transformer.
The oil- or liquid-immersed transformer must, by this definition, have two sets of
letters: one which describes the cooling of the winding and one which describes the
cooling of the surface of the liquid. Hence the most common distribution transformer in which the windings and core are naturally cooled by oil and the oil is subsequently naturally cooled by air has the designation ONAN.
Forced-cooling equipment and its control are costly additions to any transformer
and this cost can rarely be justified on distribution transformers of the ratings
covered in this chapter. However, the same ruling that applies to forced cooling of
dry-type transformers also applies to the oil in an oil-filled transformer or the silicone fluid in a fire-resistant transformer. Ratings can be increased significantly if air
is forced over the cooling surface of the tank.An oil-immersed transformer arranged
to have fans automatically switched on when the oil exceeds a certain temperature
level would have the dual designation of ONAN/ONAF. Yet a third condition of
forced cooling is obtained when an oil pump is built into the oil flow system of the
transformer. The designation becomes ONAN/ONAF/OFAF.
The naturally cooled ONAN or LNAN distribution transformer above the rating
of approximately 50 kVA requires cooling surfaces in addition to the tank surface
that would normally contain the core and windings. At one time this additional
cooling surface was provided by tubes welded into the tank wall and theoretically
carried the hot oil from the top to the bottom of the tank. In more recent years it
has become fashionable to manufacture plate radiators from pressings similar in
pattern to the domestic hot water radiator and arrange these in banks on the tank
side. The plate radiator has the advantage of reduced oil content and possibly results
in lower manufacturing cost.
At early as 1925 manufacturers produced oil-immersed transformer tanks with
the tank walls made from deep corrugations of thin steel plate. It was not until very
many years later that machines were developed to form deep corrugations into
a continuous strip of plate automatically, weld the edges of the corrugations
Distribution Transformers
345
automatically, insert and weld corrugation strengthening strips and shear to a predetermined length.
The transformer tank with all four sides formed from thin (1.2 mm) corrugated
steel plate with terminations and tapping switch all mounted on the cover, has
become the most standard arrangement throughout Europe and the USA, although
standard supply industry terminations in the UK make this cooling arrangement
less advantageous than the tank with radiators.
Ventilation of transformer enclosures
Transformers operating within an enclosed area inevitably reach a higher temperature for the same loading conditions than they would when operating in free air.
It is important to the life of the transformer that this fact is appreciated and that
substations or enclosures are designed so that this excess temperature is limited.
The problem of substation ventilation when fan extractors are used is very much
more simplified than for naturally ventilated enclosures. Natural ventilation does
not rely on the functioning and maintenance (or lack of it) of fans and is therefore
preferred.
The excess temperature of the substation or enclosure is a function of:
(1) The total losses of the transformer
(2) The net area of the inlet and outlet ventilation areas
(3) The effective vertical distance between the inlet and outlet ventilation areas.
The inlet ventilation area is positioned ideally low down, below the centre line of
the transformer radiators with the transformer fairly close. The outlet ventilation
area is required to be high, not immediately above the transformer, but on a wall
remote from the inlet so that cooling air passes over the transformer.
The minimum height of the outlet above the inlet area should ideally be equal to
1.5 times the height of the transformer.
The net area of the inlet or outlet has been shown by empirical means to be
approximately:
A = 0.06 P
where P is the total loss dissipated from the transformer in kilowatts and A is in
square metres.
With these conditions met the temperature of the substation air should not be
more than 7–8°C above the outside ambient.
IMPULSE WITHSTAND
The main three-phase 11 kV distribution system in the UK is by underground cables,
and ground-mounted distribution transformers connected to this system are not
subjected to high-level transient voltages of atmospheric origin because of the attenuating effect of the cable to steep-fronted waves. However, it is recognised that for
346
Handbook of Electrical Installation Practice
a variety of reasons transient voltages do occur in cabled systems. Transformers can
also be connected very close to an overhead system and an agreed system of impulse
voltage testing and impulse voltage levels does indicate that a level of insulation
strength has been achieved in the basic design.
Table II of IEC 76, Part 3 gives the impulse voltage withstand levels agreed by
most countries of the world. Distribution voltages of 3.6, 7.2 and 12 kV are covered
by two values of impulse withstand level. List I is for the transformer that is considered to be electrically not exposed to high voltage transients and list II with a
higher level for the electrically exposed. The 11 kV system of the UK is considered
by the supply authorities to require the 75 kV level, while pole-mounted transformers connected to overhead lines are usually tested to a higher level of 95 kV.
Europe and Middle Eastern countries standardise generally on the 75 kV level for
distribution systems between 10 and 11 kV.
At one time it was considered that dry-type Class C transformers could be classified as electrically unexposed to transient voltages because they could never be
operated out of doors close to an overhead distribution system.
The increasing use of vacuum circuit-breakers and their current-chopping characteristics produce exceptionally high voltages in the low-capacitance, high-surge
impedance windings of the dry-type transformer. Impulse levels therefore became
necessary for the dry-type transformer and the list I level has been accepted as
satisfactory for the unexposed transformer.
OPERATION IN TROPICAL CLIMATES
A number of special problems exist when transformers are operated in tropical climates. The effects of increased ambient temperature are well documented and
require little elaboration in this chapter. If the average ambient temperature at site
is 10°C higher than that specified in normal operating conditions given in BS 171,
then the temperature rise of the transformer would either need to be designed for
10°C lower or the transformer would need to be derated to a level which produced
a temperature rise 10°C lower. Other hazards exist which are, perhaps, not so well
documented. High isoceraunic levels exist in some tropical countries and electrical
storms can persist for long periods of time. Standard impulse voltage levels may well
be insufficient for these areas and the added protection of surge arresters considered to be advisable. Standard bushings may again give insufficient creep and a
higher voltage class considered necessary in these areas.
Temperature, intensity of solar radiation, rainfall, high wind, dust storms and
humidity, all affect the life of paint applied as a protection against corrosion to the
tank surface of liquid-immersed transformers. A standard paint finish generally
consists of three coats. The first, the priming coat, is applied to the prepared metal.
The second, the undercoat, provides the key for the main protective top coat. This
final coat is usually long lasting high gloss, the gloss providing the main protection. Generally this three-coat system provides adequate protection for a reasonable time, and is easy to maintain and replace when it has been damaged or worn.
Thicker coatings can give extended life to any paint system. Special top coatings
are available which again give extended life. It must be pointed out, however, that
Distribution Transformers
347
the more complicated the protective system, usually the more difficult it is to maintain, and the integrity of any surface coating relies on adequate pretreatment of the
metal.
Dry-type transformers can be vulnerable to inadequate maintenance in tropical
countries. Dust and sand are a natural hazard in many areas and in countries where
the temperature drops to quite low values at night, the warmth of a transformer
installation probably seems to be quite a haven to a host of small creatures. Extra
maintenance and vermin proofing of enclosures might, therefore, militate against
their use.
PARALLEL OPERATION
Satisfactory operation of transformers in parallel means that each transformer will
carry its share of the load according to its rating; and for this condition to be met
the voltage ratio, phase displacement and impedance must all be the same. Transformers in parallel must have the same secondary voltage for a common primary
input.
The importance of phase displacement is obvious from Fig. 13.11. A pair of threephase transformers of similar characteristics and having the same connection
symbols can be operated both physically and alphabetically. For example, Dy 1 and
Yd 1 can be safely connected together. The impedance (which governs the regulation) decides the proportion of the total load which is taken by each transformer.
The resistances of each unit must be similar.
When connecting units in parallel or paralleling supplies from two separate transformers, the phase rotation must be the same.
Other points to remember when parallel operation of transformers is being
considered are:
(1) The tested impedance of transformers can vary by ±10% of the guaranteed
value. Two transformers to the same guaranteed value of impedance can have
test values which vary by as much as 20%.
(2) The length and type of cable connections must be considered if additional
transformer capacity is added to an existing system and sited away from the
original unit(s).
(3) Transformers that have tapping ranges larger than 10% need to have the
impedance variation throughout the tapping range considered. Very large
variations between manufacturers can occur owing to different winding
arrangements.
PACKAGED SUBSTATIONS
A distribution substation consists essentially of h.v. switchgear (in many cases a ring
main unit), a transformer and a fused l.v. distribution panel. Until recent years these
were always supplied by different manufacturers as individual components. They
were often sited in a small compound or building, and each component had its own
348
Handbook of Electrical Installation Practice
termination system, usually cable boxes.The three equipments were electrically connected by short lengths of cable. Lack of available space, particularly in city areas,
rationalisation in the electrical supply industry and manufacturing industries and
growth in demand for electrical power all gave effect to the development of the
British unit substation. The three equipments are still separate components, which
can be purchased separately from different suppliers, each with its own particular
characteristics, and can be brought together to form a substation because of the
standardisation of terminal heights and flanges. Although a unit substation is often
supplied with a ventilated steel or glass-fibre housing, each equipment is of weatherproof design and requires no more than a wire fence surround. Ventilated housings are preferred by many authorities at home and abroad and can be of very
pleasing appearance. Lockable doors afford access to l.v. distribution panels and h.v.
switchgear. As many as 12 three-phase fused outlets are available on the l.v. distribution panel. Housing doors can be interlocked with the h.v. switchgear.
The packaged substation is described in greater detail in Chapter 2.
PROTECTION
Transformer protection is described more fully in Chapter 22 but for completeness
the various systems available are enumerated. Two systems of protection, peculiar
to transformers, are described in more detail: gas and oil relays and winding
temperature indication.
Differential protection
Differential protection is based on the principle of comparing the primary and secondary currents of the transformer and if these balance any fault is external to the
unit. The winding connection of the transformer primary and secondary are usually
different (delta-star for the most part in the power range we are considering) and
have to be compensated for by connecting the appropriate CTs in star-delta. Both
balanced current and balanced voltage systems are used.
Restricted earth fault
The three CT secondaries on each side of the transformer are paralleled together
with a relay connected across them. A fourth CT is connected in the neutral of a
star-connected winding. The relays only operate for an internal earth fault as it is
only under these conditions that the CT outputs do not sum to zero, causing an
unbalanced current to flow in the relay circuit.
Unrestricted earth fault
A single CT in the neutral of a star-connected transformer provides a measure of
protection against earth fault but the relay also operates for earth faults outside the
transformer.
Distribution Transformers
349
Overcurrent
A standard idmtl relay can be used to provide overcurrent protection but it will of
course cover the whole of the network beyond the transformer. Overload settings
can be adjusted to discriminate with protection on the load side of the transformer.
This type of relay is often installed to act as back-up protection.
Gas and oil relay
The double-float gas and oil relay is fitted in the pipe between the main tank of the
transformer and the conservator and is more commonly found on oil-immersed
transformers above 2.0 MVA. The two pivoted floats carry switches which can be
normally open or normally closed. One float is actuated when the oil level in the
conservator and hence the relay falls to an unacceptably low level. The switch on
the low-level float is usually connected to an alarm circuit that gives warning of
low oil level in the transformer. The other float operates when there is a sudden
production of gas within the transformer. The float then operates on surge. Switch
contacts on this float are usually connected to the trip circuit on the associated
switchgear, which then disconnects the transformer from the supply. A sudden production of gas is usually indicative of serious fault conditions, hence the need for
shutdown.
Flashover between connections, flashover to earth, breakdown between parts
of the same windings, etc. produce different mixtures of gases. The most significant gases generated by the electrical breakdown of the oil are hydrogen, methane,
ethylene and acetylene. Cellulose insulating materials, when broken down by an
electric arc, produce mainly carbon dioxide and carbon monoxide. An analysis of
the gas collected from the gas and oil relay can give a very good indication of the
materials involved in a gas-producing fault which initiated the operation of the
relay.
It has been known for small quantities of gas to be released within a transformer
immediately following installation, and over a period of time the gas collects in the
gas relay and eventually an alarm is given of low oil level. In this case an analysis
of the gas will often show it to be no more than trapped air.
Pressure-relief device
One of the most useful developments in recent years is the ‘snap-action’ pressurerelief device. Manufactured by Qualitrol, and since copied by various other
companies, this device, which is mounted on the tank, wall or cover, operates
when a predetermined pressure is exceeded within the tank. The seal snaps open
and the large orifice allows gas to be discharged at the rate of 283 m3/min. The
Qualitrol pressure-relief device was developed for the oil-immersed sealed transformer but it has become widely accepted as a reliable explosion vent and has
almost replaced the old-fashioned diaphragm type. The Qualitrol device can be supplied with two single-pole double-throw switches. A brightly coloured plastics pin,
located in the centre of the device, gives mechanical indication that the device
has operated.
350
Handbook of Electrical Installation Practice
Winding temperature indicators
Unless the temperature of a winding can be measured by direct contact with the
winding conductors, winding temperature indication can be no more than a close
approximation and accurate over only a fairly narrow band of transformer loading.
The two main methods used by manufacturers in the UK to give indication of
winding temperature are:
(1) A direct method whereby the temperature sensor of the instrument is held in
close proximity to the l.v. winding
(2) An indirect method whereby a ‘thermal image’ device simulates the windingto-top-oil temperature differential.
Method (1) is used almost exclusively on dry-type transformers where large
cooling ducts allow for the positioning of the instrument’s temperature sensor and
where the integrity of the winding insulation system is not impaired.The most recent
practice is to fit standard platinum resistance sensing devices into the low voltage
windings, and feed the output to electronic control devices. The instrument
measures the resistance of the sensing device, which changes directly with the
winding temperature. These devices are able to display the actual winding hot-spot
temperature; some are able to store highest temperature values for future retrieval
and display.
The indirect method of the thermal image device uses the standard mechanism
of a dial-type temperature indicator. A current transformer mounted in the live connection to one winding supplies a proportion of the live current to a heater coil
wound on to the operating bellows of the instrument. A calibrating resistor adjusts
the current in the heater coil to a value that produces the correct winding-to-oil
differential.
All winding temperature indicators can be fitted with contacts to operate alarms
and trip mechanisms. The instrument in common use can be fitted with three or
four switches to operate fans and pumps for forced-air and forced-oil circulation;
sometimes they are connected into a building or installation management system,
so that any untoward operating conditions may be noted and corrective action
taken.
SHIPMENT OF TRANSFORMERS
The preparation of a transformer for transportation depends on its size, type,
destination, the distance and method of transport and the length of time the
transformer is to remain in store before installation.
Liquid-filled transformers
Liquid-filled outdoor distribution transformers fitted with cable boxes and for
delivery within the UK are invariably dispatched by road transport, securely
Distribution Transformers
351
anchored to open-backed vehicles with no more packing than perhaps some protection for the cooling radiators or corrugations. These, being of thin steel plate, are
easily damaged in transit if vehicles are not carefully loaded. Smaller, pole-mounted
transformers, with exposed porcelain bushings, require some protection if damage
to terminals is to be avoided during transport. A careful arrangement of identical
units with packing pieces spacing one unit from another is normally sufficient for
UK road conditions.
Larger units, even for delivery within the UK, require more consideration. The
removal of conservators, bushings and radiators is advised if the total load exceeds
the width of a low loader. The route to be taken by the vehicle, sharp bends (particularly at the bottom of hills), road camber and low bridges are all hazards which
have to be considered when units larger than 5.0 MVA have to be transported. It is
advisable to cover and protect dial-type instruments, gas and oil relays, etc. from
damage.
All transformers manufactured to BS EN 60076 have lifting lugs as a standard
fitting. The weight of an 11 kV industrial ground-mounted oil-filled transformer with
standard fittings is very approximately 0.022 (kVA)0.75 tonnes and requires lifting
capacity of 6 tonnes or less for units of 1600 kVA or lower. Removal from the vehicle
to site or store in the UK or anywhere within the industrialised west should not
present problems.
When oil-immersed transformers are shipped to overseas locations, particularly
where handling arrangements are restricted and long distances have to be travelled
overland on poor roads, the type of packing employed and the method of transportation have to be given much more consideration.
The single isolated unit is the most vulnerable because most distribution transformers and unit substations, supplied in large numbers to the high growth areas of
the world, are transported from manufacturers to users by containerised shipping.
Many units are packed and sealed into 10 m long 40 m3 volume containers by
packing experts and the complete container is transported direct to site.
Larger transformers require the vulnerability of components, bushings, radiators,
conservators, etc. to be considered and it is often advisable to remove them and
pack them separately in wooden crates.
Weight and freight restrictions often demand that oil-immersed transformers
are dispatched dry with the oil packed in drums and shipped separately. No great
problems exist here if the transformers are sealed with dry air or nitrogen and
moisture is prevented from entering the tank and affecting the windings.
Sealed transformers are of course filled with oil and sealed at the manufacturer’s
works and are always dispatched filled with oil.
Dry-type transformers
Due consideration must be given to the shipment of dry-type transformers. Class C,
and similar types, are susceptible to the ingress of moisture and must be suitably
protected during shipment. Cast-resin transformers are moisture resistant to a far
greater degree than conventional dry-type transformers, but will still require appropriate protection during shipment. For dry-type transformers housed in sheet metal
352
Handbook of Electrical Installation Practice
enclosures, it is possible for transportation to be by road, with the units covered by
waterproof sheeting. For export, or where the transformers will not be immediately
placed under cover, it is usual for close-boarded crates, lined with polythene, to be
used. A quantity of moisture-absorbing silica-gel desiccant is often placed within
the enclosure as an extra precaution.
INSTALLATION
It is important to note that before installation, transformers should be checked
for any damage that may have been caused during transit. Liquid-filled units dispatched fully filled should be checked for correct oil level and for any leaks that
may have occurred. The paint finish should be examined carefully for signs of
damage. The cores and windings of Class H and C transformers should be
examined for signs of mechanical damage to leads, connections and risers. Coils
should be examined for signs of insulation damage. The cast-resin of encapsulated
transformers can be easily chipped or cracked by being knocked and thus needs to
be examined very carefully.
Liquid-filled transformers
It is usual to have some form of containment and soakaway for all liquid-filled
transformers, be they mineral oil, silicone liquid or any other design, irrespective of
whether they are installed indoors or in the open. In some countries this is required
by law. The soakaway is usually a pebble base contained within a low brick wall
enclosure. When installed in a building or substation without additional fire protection it may take the form of a catch pit, designed as a pitched or lowered floor,
pit or trench, as shown in Fig. 13.12. It should be large enough to contain all the
liquid to cater for the possibility of a severe rupture of the tank. The American
Factory Mutual Research organisation has detailed this information in its Factory
Mutual Loss Prevention Data Sheet 5–4A/14–85.
The shape, size and materials used for the building should be based on the rate
of heat release of the transformer liquid when on fire and discussion of these is
outside the scope of this chapter. The above-mentioned Data Sheet also gives
guidance on this aspect of the subject.
Dry-type transformers
All dry-type transformers must be installed indoors with an earthed metal enclosure around them. In the UK this usually takes the form of a substantial metal
framework, but there is no reason why the lightweight mesh-screened panels, as
used by the European continental countries, should not be employed. This reduces
the overall cost of the installation.
Class C or H designs are generally not as tall as their cast-resin counterparts,
although other dimensions are similar. This slight difference in headroom might be
important if the unit is to be installed in an existing substation. The larger dry-type
transformers, 500 kVA and above, are usually built on a framework of metal
Distribution Transformers
353
Fig. 13.12 Some different arrangements of soakaways in a building or substation housing a
liquid-filled transformer.
channels and are usually provided with wheels to allow movement of the unit for
cleaning and maintenance.
CABLING
For the distribution transformers covered in this book, cabling is usually PVC
insulated and sheathed, although in special cases EPR or other forms of insulation may be employed. Copper or aluminium conductors are available. Armouring is usual for outdoor installations or where onerous soil conditions exist. A
three-core design of h.v. cable is normal for both dry-type and liquid-filled design.
Termination is by cable box, either compound-filled or air-insulated, with suitable heat-shrink termination kits; the choice is dependent on the cable type and
the preference of the transformer purchaser. Moulded plug-in type connectors
are finding increasing application, particularly on cast-resin and other dry-type
transformers.
Depending on the rating of the transformer, l.v. cables may be single-core or
three-core. Termination methods are similar to those appertaining to the h.v. side,
possibly using heat shrink connections for dry-type units.
354
Handbook of Electrical Installation Practice
COMMISSIONING
Before proceeding with commissioning tests a careful examination of the transformer and its surrounds must be carried out, particularly if the unit has been
installed for some time. It is not unusual to find tools and other extraneous matter
lying on the unit in a position that could be highly dangerous if a high voltage were
applied to the transformer. For dry-type transformers, particularly those of Class C
or H designs, the windings should be checked with an IR tester and then dried out
as necessary. The drying out can be done electrically by passing a small current at
l.v. through the windings or by the application of a ‘gentle’ external source of heat.
Where it is known that the dry-type Class C transformer is to remain in store for
a long period or is to remain unexcited for long periods, it is advisable for the unit
to be fitted with small heaters on the core and windings to circulate warm air during
the time that the transformer remains inactive.
For liquid-filled units sent overseas it is important to ensure that the unit has in
fact been filled with the correct fluid if the transformer was dispatched unfilled.
Depending on the circumstances it may also be necessary to institute some form
of winding drying-out procedure. In any case the fluid should be checked for electrical strength before commissioning.
Where relays or instruments are associated with transformers they should be
examined to make sure there is no packing or safety lock incorporated as a protection against damage during transit. This should be removed. The position of the
off-load tap change device must be set to correspond to the network conditions. If
there is a conservator valve, ensure that it is open. If there are plastics caps covering breather pipes, ensure that they are removed.
When all the connections and other matters have been checked, the transformer
can be energised and allowed to run on no-load for a period long enough to ensure
safe operation. Gradual loading can then be introduced until full load is reached.
During the commissioning procedure instruments and protective relays should be
observed for correct functioning and it should be checked that readings are of the
expected order.
MAINTENANCE
It is not the intention to give full and detailed maintenance instructions here but to
highlight the more important features related to the various types of transformer
included in the chapter.
Mineral oil-filled units
Oil is subject to deterioration or contamination in storage, in the course of handling
or in service. Accordingly it requires periodic examination and possibly treatment
to maintain it in a good condition. After many years in service it may even require
replacement. BS 5730: 2001 Monitoring and maintenance guide for mineral insulated
oils in electrical equipment gives specific advice relating to the testing of oil in order
to determine its fitness for further service.
Distribution Transformers
355
Provision is usually made on all mineral oil-filled transformers for samples of the
oil to be drawn off, and this operation should be done while the oil is warm. A
limited but useful amount of information can be obtained from the colour and odour
of the oil. Cloudiness may be due to suspended moisture or suspended solid matter
such as iron oxide or sludge. Moisture can be detected by the crackle test. If the oil
is dark brown it may contain dissolved asphaltenes; if green the presence of copper
salts is indicated, and it may be expected that further deterioration will be rapid.
An acrid smell is often indicative of volatile acids which can cause corrosion and
which may render the oil unsuitable for treatment on site. A petrol-like or acetylene odour may indicate a low flashpoint due to a fault or some other cause.
Tests are laid down in BS 5730 to determine free water, acidity, electric strength,
sludge, flashpoint and resistivity and suggested minimum safe limits are indicated.
Frequency of testing is also indicated; it varies from 6 months up to 2 years depending on the test concerned and the environmental conditions. It is important that the
oil level is maintained.
At regular intervals it is strongly recommended that breathers and breather pipes
are checked. If a silica-gel dehydrator is fitted then the condition of the oil bath and
crystals should be checked. An oil-immersed transformer should never be allowed
to breathe through silica-gel crystals supersaturated in moisture. Breathers should
be changed, or re-activated, when two thirds of the silica-gel crystals have changed
colour from blue to pink.
The Code also recommends that the protective paint finish of the tank is checked
for damage and that there are no leaks.
If oil temperature and winding temperature indicators are fitted, operation of the
switches should be checked. Gas and oil relays and pressure-relief devices fitted with
switches should also be checked occasionally for ease of movement.
Fire-resistant liquid-filled transformers
For reasons stated earlier, askarels are being replaced in transformers and so the
maintenance of these units will not be discussed. If an askarel-filled transformer is
found to be leaking, advice should be sought from the manufacturer as to how the
situation is to be dealt with. It is important that askarel-type materials are not
allowed to contaminate the environment around the transformer, or to enter any
water drainage systems.
Of the available range of fire-resistant liquids, silicone fluid and synthetic esters
(Midel) are the most commonly used types. These materials possess superior
thermal stability to mineral oils and will consequently degrade at a slower rate. This
implies a reduction in the amount of maintenance required by transformers filled
with these fluids, but the recommendations made by manufacturers with respect to
maintenance procedures are to be followed. IEC Specifications 836–1 and 837–1
give general information relating to the use of silicone fluids and synthetic esters
(Midel) for electrical purposes.
In the event of silicone or synthetic ester fluids requiring to be cleaned, similar
equipment to that used for the treatment of mineral oil may be used. It is important that synthetic fluids are not cross-contaminated, or contaminated with mineral
oil. A very low level of mineral oil contamination in a high fire-point fluid will
356
Handbook of Electrical Installation Practice
Table 13.10 Recommended maintenance tests for high fire-point fluids.
Acceptable values
Test
Minimum
Visual
Synthetic ester
(Midel)
Silicone fluid
Unacceptable values
indicate
Clear strawcoloured liquid,
free of particles
Faintly sweet
Crystal clear,
free of particles
Particulates, free water
colour change
Odourless
50 kV new
50 kV new (first test)
Arced or burned
insulation, volatile
contamination (solvent
pcb)
Particulates,
contamination, water
25 kV in
transformer
25 kV in
transformer
Additional
Water content
Viscosity
200 ppm maximum
95 cSt at 20°C
100 ppm maximum
50 cSt at 25°C
Fire-point
310°C minimum
350°C minimum
Permittivity
3.2 at 20°C
2.7 at 25°C
Odour
Dielectric
breakdown
BS 148: test cell
Excessive water
Fluid degradation,
contamination
Contamination of fluid by
volatile materials
Polar/ionic contamination
significantly reduce the fire-point. It is preferable that separate pumping and handling equipment is used for different fluids. Silicone fluids have minimal lubricating
properties and care must be taken in selecting the appropriate pumping equipment
to handle these materials. Solid contaminants may be removed from these fluids by
cartridge filters or by filter presses, moisture being extracted by conventional
degassing equipment.
Table 13.10 details physical and electrical properties of silicone and synthetic ester
fluids that can be checked as part of maintenance operations. Transformers containing these fluids are normally of hermetically sealed construction, thus contamination by air-borne pollutants is prevented and the amount of maintenance required
is reduced. As with mineral oil-filled transformers, synthetic liquid cooled types
should be checked for leaks and to ensure that deterioration of the paint finish has
not occurred.
Dry-type transformers
The most important aspect of maintenance is that of ensuring that all cooling air
ducts are kept free of foreign objects and contaminating dirt. A vacuum cleaner
can be used for this purpose. Any blockage can cause the winding temperature to
Distribution Transformers
357
rise to levels that could affect the performance and life characteristics of the insulation. If a transformer is taken out of service for any length of time, and heaters
have not been fitted, it is a wise precaution to dry out the unit by the means suggested earlier under ‘Commissioning’. This is particularly true of the Class C or H
designs. Before connecting any supply to the transformer for this purpose the terminations at both ends of the h.v. windings, the pressure rings and the insulators
should be dried with a cloth. The l.v. winding can then be short-circuited and a low
current passed through the h.v. winding. The whole drying-out operation should not
take more than 5 hours. Alternatively, fan heaters can be employed to circulate
warm air through the windings.
In the event of a minor winding fault, where the damage is restricted, it is possible to repair both conventional dry-type and cast-resin transformers on site. Major
electrical breakdowns will require replacement of the winding subject to fault. This
may be accomplished on site with a cast-resin type of transformer, but it is usual to
return a conventional dry-type transformer to the factory or suitably equipped
workshop. Any repairs are best carried out by the manufacturer of the transformer,
or by a reputable repair organisation.
Future development
The development of distribution transformers tends to be an evolutionary process
rather than a revolutionary one. Most developments are aimed at reducing the
manufacturing costs, as well as improving the overall efficiency, without reducing
the inherent reliability of the modern distribution transformer. Improvement in the
performance of the magnetic materials used for transformer core laminations has
led to a reduction in the no-load losses and this trend will continue as the cost of
energy increases. Advances in coil manufacturing methods have enabled the production of windings possessing superior short-circuit strength in conjunction with
compact dimensions. The introduction of high fire-point liquids, and the various
types of dry-type transformer, have given the potential purchaser the opportunity
to choose a suitable design for almost any situation. It is anticipated that these types
of transformer will undergo further development in order to improve their costeffectiveness. The use of synthetic cooling fluids at elevated temperatures, in conjunction with suitable insulating materials, will produce dimensional and cost
reductions in this type of transformer. The manufacturers of insulation materials
also improve their products and these improved materials are then incorporated into distribution transformers by manufacturers as part of the evolutionary
development.
CHAPTER 14
Switchgear
A. Headley, BSc, PhD, AFF
(Reyrolle Ltd)
R.W. Blower, BSc(Eng), FIEE
DEFINITIONS
Switchgear
A general term covering switching devices and their combination with associated
control, measuring, protective and regulating equipment, and also assemblies of
such devices and equipment with associated interconnections, accessories, enclosures and supporting structures, intended in principle for use in connection with generation, transmission, distribution and conversion of electric power.
Metal enclosed switchgear
Switchgear assemblies with an external metal enclosure intended to be earthed, and
complete except for external connections.
Metal-clad switchgear
Metal enclosed switchgear in which components are arranged in separate compartments with metal enclosures intended to be earthed. There will be separate compartments at least for the following components: each main switching device;
components connected to one side of a main switching device, e.g. feeder circuit; and
components connected to the other side of the main switching device, e.g. busbars.
In the UK, circuit-breaker switchgear is expected to be metal-clad, which is an
extension of metal-enclosed through the use of internal metal partitions. In addition, since the majority of faults on distribution switchgear tend to be cable faults,
at least in origin, there is a demand for the cable compartment to be closed off from
the circuit compartment, either by a metal partition or, if clearances require it, by
an insulating partition.
Circuit-breaker
A mechanical switching device, capable of making, carrying and breaking currents
under normal circuit conditions, and also making, carrying for a specified time and
breaking currents under specified abnormal circuit conditions such as those of
short-circuit. Almost everywhere in the world except the UK requires that the ‘short
time rating’ be for one second. Due to the number of protection stages and the use
358
Switchgear
359
of many older style relays, faults in the UK can exist for longer than this if there is
a failure of the first stage protection. For this reason, most UK switchgear has a
three second short time rating.
Indoor circuit-breaker
A circuit-breaker designed solely for installation within a building or other housing,
where the circuit-breaker is protected against wind, rain, snow, abnormal dirt
deposits, abnormal condensation, ice and hoar frost.
Outdoor circuit-breaker
A circuit-breaker suitable for installation in the open air, i.e. capable of withstanding rain, snow, dirt deposits, condensation, ice and hoar frost.
Switch
A mechanical switching device capable of making, carrying and breaking currents
under normal circuit conditions, which may include specified operating overload
conditions, and also carrying for a specified time (three seconds in the UK) currents
under specified abnormal circuit conditions such as those of short-circuit. It must
also be capable of making, but not breaking, short-circuit currents.
Disconnector (isolator)
A mechanical switching device which provides in the open position an isolating distance in accordance with specified requirements.
A disconnector is capable of opening and closing a circuit when negligible current
is broken or made, or when no significant change in voltage across the terminals of
each of the poles of the disconnector occurs. It is also capable of carrying currents
under normal circuit conditions and carrying for a specified time currents under
abnormal conditions such as those of short-circuit.
Note: Negligible currents imply currents such as the charging current of busbars,
bushings, etc. and a current not exceeding 0.5 A is deemed to be a negligible current
for the purpose of this definition.
Summary
As will be seen from the above definitions, the most versatile switching device is the
circuit-breaker, as this is the only equipment capable of interrupting short-circuit
currents and then restoring supply a number of times without requiring maintenance or the replacement of any parts. The least versatile device is the disconnector, which is only capable of carrying short-circuit currents and has to be operated
off-load.
Because of the need to interrupt short-circuit currents, the design and mode of
operation of a circuit-breaker tend to be dominated by this requirement and it is
usually categorised by the arc extinguishing medium used for this purpose. In this
chapter we consider only a.c. circuit-breakers, as the interruption of d.c. is a very
limited specialist requirement.
360
Handbook of Electrical Installation Practice
CIRCUIT-BREAKING
An essential element in the operation of any a.c. circuit-breaker is the electric arc,
which permits the current in the circuit to continue flowing after the contacts have
parted, until a suitable current zero occurs. This is illustrated in Fig. 14.1. As will be
described below, the sudden cessation of current flow at any time, other than very
close to a natural current zero, has undesirable consequences in all normal distribution systems, so the existence of the arc as a natural commutating device is a very
important factor in the operation of a.c. circuit-breakers.
An ideal circuit-breaker is one which acts as a perfect conductor until current
zero is reached, at which point it becomes a perfect insulator. As no practical circuitbreaker meets this condition, the result is modified to a greater or lesser degree by
the circuit-breaker characteristics. The objective of the circuit-breaker designer is
to create the necessary conditions to sweep away the ionisation products in the
contact gap at current zero and replace them by a medium which will withstand the
application of a very rapidly rising voltage of considerable amplitude, the transient
recovery voltage. This is shown at H in Fig. 14.1.
MEDIUM VOLTAGE SWITCHGEAR
The term medium voltage is usually used to describe switchgear rated from 3.6 kV
to 52 kV. In the UK it is general practice for m.v. distribution switchgear manufacturers to supply completely factory-assembled switchgear. This means switchgear
equipment containing busbars and all circuit components up to the cable terminations, including any switching devices (circuit-breakers, switches, etc.) and their
isolating means. It is, therefore, almost equally general for the switchgear to be
type tested in its completely assembled form. This is not always the case for l.v.
switchgear, since a thriving business exists in this area for the manufacture of l.v.
switchboards incorporating circuit-breakers and other l.v. switching devices made
by a small number of specialist manufacturers. Also, m.v. circuit-breaker switchgear
is designed principally for use with separately protective relays and therefore has a
short time rating, usually equal to the breaking current rating for three seconds,
unless where very heavy fault levels exist, the operating conditions permit a one
second short time rating. The switch or circuit-breaker also has to be able to close
fully against a short-circuit making current peak equal to 2.5 times the rated breaking current, and to be able to interrupt that breaking current with a degree of asymmetry which will depend on the opening time of the circuit-breaker being
considered. With some of the modern high speed circuit-breakers using vacuum or
sulphur hexafluoride (SF6), this time can be quite short and the d.c. component correspondingly large. A figure of 35% d.c. component is not uncommon under these
circumstances.
All circuit-breakers have to be able to close and open satisfactorily under all conditions of service. In particular they must interrupt all currents from zero to full
rated breaking current with all possible combinations of power factor, current asymmetry and recovery voltage that occur. Figure 14.1 illustrates the typical form of the
current and recovery voltage which occurs when a fault current is interrupted. The
Switchgear
361
Fig. 14.1 Typical fault current and recovery voltage diagram.
AA1 and BB1 envelope of current wave
CC1 displacement of current wave zero line
DD1 typical contact separation point for asymmetrical breaking duty
EE1 rms value of symmetrical current wave measured from CC1
FF1 typical contact separation point for symmetrical breaking duty
G
peak value of 50 Hz recovery voltage
H
peak value of high frequency transient recovery voltage
J
assumed contact separation point to illustrate typical voltage
across circuit-breaker contact gap
K
arcing voltage.
asymmetry which is illustrated in this single-phase example arises as a function of
the instantaneous value of the system voltage when the fault occurs, and the power
factor of the system voltage under fault conditions.This reduces from the usual operating figure in excess of 0.8 to a much lower figure such as 0.1–0.3. This creates much
more severe conditions for arc interruption as the current zero now occurs at a time
when the supply voltage is closer to its peak. The high frequency transient recovery
voltage is a function of the system inductance and capacitance.
In addition to the fault condition, circuit-breakers and switches often need to be
able to switch low currents of a highly inductive nature (low lagging power factor)
362
Handbook of Electrical Installation Practice
or of a capacitive nature (low leading power factor). Special conditions attend these
operations.
Low inductive currents
As illustrated in Fig. 14.2, the available arc extinguishing effort may tend to force
the current to zero prematurely. When this happens energy is trapped in the inductance of the load and subsequently transferred into capacitive energy stored in the
leakage capacitance of the system. This process continues in an oscillatory manner
as part of an augmented transient recovery voltage and eventually dies away as the
energy is dissipated as heat in the resistive circuit elements. Some of the energy
(maybe as much as 30%) is also lost by iron losses if the load has an iron core as is
Fig. 14.2 Conditions occurring when interrupting small inductive currents
(cos q ⯝ q lagging).
L
inductive load
C
leakage capacitance
AA1 current interruption point with ‘current-chopping’
BB1 current interruption at natural current zero
CC1 recovery voltage with ‘current-chopping’
DD1 recovery voltage with interruption at natural zero.
Switchgear
363
usually the case, since these conditions normally arise when switching transformers
and motors on no-load. It is a necessary part of the circuit-breakers designer’s job
to ensure that the degree of ‘current-chopping’ (as this phenomenon is often called)
is not allowed to reach a level capable of generating dangerous overvoltages.
Capacitive currents
Conditions here are again special, because a d.c. charge is trapped in the capacitance once the current flow ceases, and the contact gap is quickly stressed to a value
of double the peak phase voltage as the polarity of the a.c. recovery voltage changes.
This is illustrated in Fig. 14.3, and again the circuit-breaker or switch designer has
Fig. 14.3 Conditions occurring when interrupting capacitance currents (cos q ⯝ q leading).
364
Handbook of Electrical Installation Practice
to ensure that the contact gap does not break down under these conditions, however
early the initial clearance occurs, as this could lead to the build-up of even higher
voltage stresses.
TYPES OF SWITCHING DEVICE
Circuit-breakers
An important feature in considering the application of any form of circuit-breaker
is the behaviour of its operating mechanism. Because of its protective duty, it is essential that a circuit-breaker is always in a condition to open even if the power supply
to the mechanism closing device has been interrupted. This is achieved by biasing
the circuit-breaker towards the open position by springs in various ways. The circuitbreaker is then held in the closed position by some form of catch which can either
be released manually or, more usually, by an electrical solenoid or trip coil.
Because circuit-breakers could at any time find themselves being closed onto a
faulty network, it is forbidden for them to be closed by direct manual means. Therefore all circuit-breaker closing mechanisms require some form of stored energy to
operate them. The two most common devices in use have either a solenoid and
armature providing the necessary closing force, or springs which may be either
hand-charged or charged by an electric motor. The spring close mechanism has the
advantage that it can always be operated even if the source of supply has been disconnected. The solenoid requires a heavy duty d.c. source, usually a secondary
battery. Where such a source exists for other purposes, such as emergency lighting,
then the solenoid operating mechanism has certain advantages.
The vast majority of modern circuit-breakers are supplied with either hand- or
motor-charged spring mechanisms. The latter is increasingly demanded for remoter
operation applications. At the distribution voltages considered here, up to 11 kV, by
far the most common arc extinguishing media used until recently were oil, and air
at atmospheric pressure. For particularly heavy duty there have been a limited
number of circuit-breakers made using compressed air as the interrupting medium,
but this was more usually confined to designs of circuit-breaker for use at transmission voltages. Today, vacuum and SF6 are the dominant interrupting media in
circuit-breakers.
Oil circuit-breakers
The oil used in oil circuit-breakers complies with BS 148 and is a hydrocarbon oil
of fairly low viscosity and good insulating properties. When the contacts part considerable heat is generated and this not only vaporises the oil but disassociates it
into its hydrogen and carbon constituents. The hydrogen is then thermally ionised,
which generates the electrons and positive ions that carry the current across the
space between the contacts in the form of an electric arc. To control the flow of gases
in the arc region the contacts are normally enclosed by an arc control device
(Fig. 14.4). The intense heating of the hydrogen gas and the dissociation of the oil
generates pressure which is utilised within the arc control device to improve the
efficiency of operation.
Switchgear
365
Fig. 14.4 Contacts and arc control device of an oil circuit-breaker.
During the arcing period the presence of the arc tends to prevent the exhaust of
gases from the arc control device through its side vents, but as the current reaches
current zero these gases are released and sideways displacement of the ionisation
products occurs due to the high pressure gas which surrounds the arcing zone. The
replacement of the ionisation in the contact gap by clean hydrogen ensures a dielectric strength sufficient to withstand the rapidly rising transient recovery voltage. In
an oil circuit-breaker of this type the effort required to extinguish the arc increases
as the current rises, but so does the energy injected into the electric arc. Consequently, the extinguishing effort rises to match the increasing fault current.
The arc voltage (see Fig. 14.1) is important for two basic reasons. First, the arc
voltage controls the amount of energy being generated in the arc and this has an
important effect on the mechanical design of the enclosure. Second, the arc voltage
plays a part in modifying some of the electrical parameters concerned with the
366
Handbook of Electrical Installation Practice
circuit-breaking operation, such as the power factor and the high frequency transient recovery voltage, by adding resistance to the circuit.
Bulk oil circuit-breakers
There are very many bulk oil circuit-breakers in service in the UK, but fewer and
fewer are being ordered today as the new technologies of vacuum and SF6 continually increase their share of the market. Since both the oil and the gases released
during arcing are flammable, there is a desire to use safer designs today, even though
the safety record of the oil circuit-breaker has been exemplary. The longer life
without maintenance of the new technologies is another attractive feature. Much
the same arguments apply to the continental minimum oil designs which are also
being replaced by oil-less circuit-breakers. New designs of oil circuit-breakers are
extremely rare and supply to existing designs relates to special local conditions (e.g.
manufacturing and maintenance technology).
Magnetic air circuit-breaker
The basic principle of the magnetic air circuit-breaker consists of so manipulating
the arc that a very high arc voltage is generated, eventually exceeding the supply
voltage. Under these conditions current flow cannot be maintained and the arc is
extinguished.
This is usually achieved either by forcing the arc to extend itself close to solid
materials which extract heat from the arc, or by breaking the arc up into a series of
arcs in which case the anode and cathode voltage drops are added to the total arc
voltage to assist in achieving the objective. Designs exist where both methods are
used in combination. A typical air circuit-breaker is shown diagrammatically in Fig.
14.5 and it will be seen that the arc extension means is contained in the arc chute.
The arc is encouraged to enter this device by the arc runners to which the arc roots
transfer when the contacts open. Magnetic circuits are provided to generate a field
within the arc chute which will cause the arc to move into the plates of that chute.
A typical arrangement has moulded plates with ribs which are arranged so that the
ribs on one of the parallel plates interlock with the ribs on the other plate gradually causing the arc to take a more and more serpentine path as it is driven deeper
into the arc chute.
Figure 14.6 illustrates the arcing and extinction process and shows how the arc
voltage rises to quite high values during this process. It should be compared with
Fig. 14.1 which shows the same condition for the oil circuit-breaker.
At very low currents of the order of 100 A the magnetic field may be inadequate
to cause the necessary arc entry into the chute. To assist this operation at such low
currents it is usual to fit an air ‘puffer’ comprising a piston operating within a cylinder connected to a nozzle under the contacts. This gives the necessary impetus to
the low current arc to ensure its early extinction.
Magnetic air circuit-breakers are particularly advantageous for applications
where frequent switching took place, because of the long life of the interruption
unit (i.e. between maintenance). It was typical for this technology to be used for
power station auxiliary supply switchgear.
Vacuum circuit-breakers now find favour in this application because of a lower
cost interruption element.
Switchgear
367
Fig. 14.5 Sketch to illustrate the principle of magnetic air circuit-breaker.
Vacuum circuit-breaker
In the vacuum circuit-breaker the contacts and arc control devices of the traditional
circuit-breaker are replaced by a vacuum interrupter. The vacuum interrupter is a
sealed vessel with insulating walls, which contains two contacts. One of the contacts
is fixed to one of the end shields and the other contact is free to travel in an axial
direction; the vacuum is maintained by metallic bellows connected between the
moving contact and the other end shield. Inside the vacuum interrupter are metallic screens between the contacts and the inside walls of the insulating tube. The
performance of the vacuum interrupter is dependent on three factors: the existence
of a sufficiently hard vacuum within the device; the selection of a suitable contact
material for the contacts; and the provision of some form of magnetic control for
the arc.
The vacuum circuit-breaker has a contact gap of the order of 10 mm for voltage
ratings up to 12 kV. Therefore the necessary operating power is much reduced
from that needed in the traditional designs considered earlier. When operating
within its designed breaking current limit, the contact gap in the vacuum interrupter
368
Handbook of Electrical Installation Practice
Fig. 14.6 Arc extinction process in a magnetic air circuit-breaker.
recovers its full dielectric strength within one microsecond of current zero.
This makes for an extremely efficient interrupting device. With the high
contact opening speed and short travel the contacts are usually fully open in 10 ms,
leading to maximum three-phase arcing times of the order of 13 ms. Due to the
small contact gap and the physical characteristics of the vacuum arc, the arc voltage
is very low, leading to much lower energy generation than exists in oil or air
circuit-breakers.
A modern 12 kV vacuum circuit-breaker equipment is shown in Fig. 14.7a.
Sulphur hexafluoride circuit-breakers
SF6 is a heavy, chemically inert, non-toxic and non-flammable gas, which is odourless and colourless. Its outstanding insulating and arc extinguishing properties have
made it the automatic choice for transmission applications to the highest voltages
(52–800 kV). At atmospheric pressure its dielectric strength is between two and
Switchgear
369
Fig. 14.7 (a) A modern 12 kV vacuum circuit-breaker equipment (left & centre).
(b) A modern ‘ring main unit’ equipment using SF6 technology (right).
370
Handbook of Electrical Installation Practice
three times that of air, while at an absolute pressure of about three bars it equals
the dielectric strength of insulating oil. The superior arc quenching ability of this
gas is partly attributable to the fact that it is electronegative, which means that its
molecules rapidly absorb the free electrons in the arc path between the circuitbreaker contacts to form negatively charged ions, which are relatively ineffective as
charge carriers due to their much greater mass compared with that of the free electrons. This electron gathering action results in a rapid build up of dielectric strength
at current zero.
In order to interrupt fault currents of the magnitudes found in today’s distribution systems its necessary to cause significant relative movement between
the arc and the gas. In typical distribution circuit-breakers of the ratings being
considered here, this can be achieved in two or three ways. Until comparatively
recently the most used technique was to have a piston connected to the moving
contact, which generated a blast of gas through a nozzle surrounding the contact
gap.
In this type of gas-blast circuit-breaker, usually referred to as a ‘puffer’ circuitbreaker, the arc extinguishing energy is supplied from the operating mechanism.
At the highest ratings this makes for a powerful mechanism, but this technique
still has to be used for the highest ratings. It is in fact the same technique that is
used in very high voltage circuit-breakers, which have very high energies indeed.
This type of SF6 circuit-breaker has ratings up to 50 kA at 12 kV and is suitable for
use in power stations and large industrial sites, where this sort of fault level can
arise.
Two other techniques have now come on the scene for use at more moderate
ratings. The first, now well introduced into the market, is the rotating arc design.
This is suitable for use up to about 25 kA fault level, and employs a magnetic field
to create the rotation of the arc between suitable electrodes and hence produce the
relative motion required for arc extinction. The movement of the contact and the
subsequent path of the arc is used to bring a coil circuit into play, so that the coil is
only in circuit during the arc extinction process. Several versions of this technique
exist, due to individual manufacturers needing to avoid the restrictions imposed by
the other manufacturers’ patents. In all cases, however, the basic principle is followed of establishing a magnetic field in the arc region which causes the arc to rotate
at high speed between two electrodes.
As in all cases where the arc extinguishing effort is derived from the breaking
current, the designer has to ensure a correct balance between the current to be interrupted and the effort available. At the low-current end, the field may have little
effect on the arc, so the principal arc extinguishing effort comes from the properties of the gas. The efficiency in this region can be adjusted by varying the gas pressure. For this reason, the standing gas pressure in a rotating arc SF6 circuit-breaker
tends to be higher than for the puffer type, where the extinction energy is supplied
mechanically.
At the limiting breaking current, the arc rotates so fast that the gas into which it
is travelling has not had time to fully de-ionise. This effect can be adjusted by the
dimensions of the contact structure and the number of turns in the magnetising coil.
It can be seen that these adjustments at the ends of the current scale can be interactive, which makes for an interesting design exercise.
Switchgear
371
The other recent development in arc extinction technique uses the thermal energy
of the arc to create an increase in gas pressure. Typically, the contacts part in a
chamber of which the only opening is blocked by the moving contact at the early
part of the opening travel. Thus the pressure inside the chamber rises until the tip
of the moving contact passes through the opening and the gas flow is released. A
strong deionising action is created along the arc path, causing interruption at the
next current zero. An arcing contact of small diameter is better for this type of interruption, so the normal current carrying is via a set of parallel main contacts.
This type of circuit-breaker is usually limited to voltages up to about 15 kV and
breaking currents up to 20 kA.
In addition to the virtual elimination of fire risk in the new technologies of
vacuum and SF6 circuit-breakers, these devices are sealed-for-life equipments, where
it is not expected to make repairs or to replace the contact system during a normal
service life. This makes the effectiveness of the sealing almost the most important
aspect of performance. The vacuum interrupter is usually sealed by a brazing or
welding technique, the most difficult part being the seal between the metal parts
and the insulating enclosure. Many years of experience show that this is very
reliable.
One of the original ‘advantages’ claimed for the SF6 circuit-breaker was the
facility that a pressurised device gave for the checking of its contents for leakage.
Today, the emphasis on a sealed-for-life enclosure leads to efforts to omit pressure
measuring devices so as to reduce possible leakage sites.
Switches
In many distribution systems there exist situations where a simpler and cheaper
switching device than the circuit-breaker would be adequate for control purposes.
The switch does everything that the circuit-breaker can do except interrupt fault
currents. The breaking capacity is limiting to rated load current at a power factor
of 0.7.
Until recent years switches used oil or air as the insulating medium. In the
case of the oil switch, the oil also served as the interrupting medium, but with
air insulated switches some help was required for the interruption of the load
currents. Various techniques were used from air ‘puffers’ to gas producing plastics
materials.
Now, this field has also been changed through the introduction of SF6 gas and
vacuum. On the whole, the vacuum interrupter is too expensive for use when the
objective is a cheap device, and at present there are very few vacuum switches on
the market. On the other hand SF6 lends itself to very simple arc control devices
when limited to load currents, and a large number of manufacturers have introduced
this type of equipment.
In application, the protection of the circuit controlled by the switch relies on some
other fault interrupting device, usually either an upstream circuit-breaker or a highvoltage fuse. It is common to incorporate high-voltage fuses with the load-break
switch to give a protective equipment particularly suitable for connecting distribution transformers to the network. Many thousands of such fuse-switches are
installed and working very well in this application. In the UK these were all oil
372
Handbook of Electrical Installation Practice
switches until the late 1980s when a number of competing designs of SF6 switches
appeared on the scene. The associated fuse switches almost always had the fuses
immersed in the oil. This gave two advantages, firstly by making the insulation of
the fuses and their supports independent of the ambient conditions, and secondly
by giving good cooling to the fuse, enabling high current ratings to be achieved.
Close discrimination with the low-voltage fuses on the transformer secondary was
also facilitated.
The introduction of gas-filled switches meant that the fuses had to be in external
chambers filled with ambient air, to make it possible to change them conveniently
after operation. This usually led to them being in insulating housings to achieve the
required dielectric integrity. As high voltage fuses have a relatively high resistance,
this enclosure by insulation created the need to de-rate the fuse to avoid premature
operation and nuisance blowing. Hence the change to gas-filled switches with their
advantages has also had an influence on maximum fuse ratings and in some cases
consequent discrimination.
These issues have led to the review of the concept of the protection of transformers ‘teed-off’ a ring main distribution system, and in some cases involving high
ratings or switching automation schemes a circuit-breaking element has replaced
the fuse switch. In particular, the SF6 rotating arc circuit-breaking element with its
low energy demand mechanism has found favour.
However, the ‘ring main unit’ concept of two switches and a fuse switch still
remains the dominant equipment worldwide.
A modern ‘ring main unit’ equipment using SF6 technology is shown in
Fig. 14.7b.
COMPARISON OF CIRCUIT-BREAKER TYPES
Table 14.1 compares some of the main characteristics of the five different types
of h.v. circuit-breakers discussed. The oil and air circuit-breakers are now in the
minority for new business, but there are still many thousands of them in service, so
they are kept in the tables for comparison purposes, since they are well known to
most switchgear users. Most users accept that the two new technologies are generally equal in performance, but for certain applications there are differences in
behaviour that may make the choice of one preferable to the other. These differences are mentioned in the table.
By 1995, the supply of new circuit-breakers became dominated by those using the
technologies of vacuum and SF6.
SPECIFICATION AND TESTING
The general characteristics of all forms of switchgear are guided by the existence
of a considerable number of international and national standards. These are
under continuous review and changes are always being considered in the light of
changes to the technology of switching devices and to the techniques of control and
protection.
Table 14.1 Comparison of h.v. switchgear characteristics with various interrupting media.
Switchgear
373
Table 14.1 (contd)
374
Handbook of Electrical Installation Practice
Switchgear
375
Table 14.1 (contd)
376
Handbook of Electrical Installation Practice
Switchgear
377
Table 14.1 (contd)
378
Handbook of Electrical Installation Practice
Switchgear
379
380
Handbook of Electrical Installation Practice
British Standards tend to be closely related to the corresponding IEC documents
because of a process of harmonisation agreed by the European Union (the body
responsible for the electrical standardisation process in Europe is CENELEC). In
practice there can be differences, often arising because of differences in the dates
of issue of documents and continuous development to meet technological needs,
but also to reflect different local technical or legal requirements in Britain. When a
British Standard departs from its corresponding IEC Standard a listing of differences is included in the Standard. These standards lay down a number of criteria
for the rating of switchgear and the conditions of use for which it is intended. Also,
a considerable amount of space is given to the subject of testing.
It is obviously impractical to subject every switching device produced to a series
of tests simulating all the likely switching conditions that it might meet in service,
in order to prove to the purchaser that it meets its specification. Therefore the
quality control policy is followed of subjecting a sample piece of equipment (very
often a prototype) to a comprehensive series of major type tests, and then carrying
out routine tests on each production equipment of that type to ensure that it
matches the type tested article in all essential characteristics.
The major type tests are: short-circuit proving up to full-rated breaking current
at rated voltage; high-voltage (h.v.) tests; temperature-rise tests at rated normal
current; and mechanical endurance tests.
HIGH-VOLTAGE CIRCUIT-BREAKER SWITCHBOARDS
As mentioned earlier, typical British distribution switchgear units are metal-clad, in
that they have separate compartments for the circuit-breaker, the busbars and the
circuit components (Fig. 14.8).
The busbars are customarily insulated copper bars and mounted on connections
which terminate in an insulated housing with plugs onto which the withdrawable
circuit-breaker is engaged when in the service location. All these components are
in a metal compartment.
The circuit side also has an insulated housing with plugs for the circuit-breaker
bushing contacts, and connects these contacts through a bushing, on which the protective current transformers are mounted, and then through a partition into the
cable termination compartment.
The two insulated housings described above open into the circuit-breaker
compartment, the openings being protected by metal shutters when the circuitbreaker is not plugged in. This circuit-breaker compartment may have a door
which encloses it and gives access to the circuit-breaker for operational purposes.
In other designs, the front plate of the circuit-breaker carriage serves this
purpose.
A further compartment, usually mounted above the circuit-breaker compartment,
contains the auxiliary low-voltage components, such as relays, control switches,
meters, instruments and fuses. Those components requiring access for reading, resetting or operation are usually mounted on the front panel of this compartment.
Typical metal-enclosed switchgear units incorporating vacuum and SF6 circuitbreakers are shown in Figs 14.7 and 14.9–14.11.
Switchgear
381
Fig. 14.8 Typical UK switchgear unit with vertically isolated withdrawable bulk oil
circuit-breaker.
The cable compartment was traditionally designed for the termination of paper
insulated cables, and made provision for filling with bitumastic compound as insulant for the completed termination. Nowadays there is increasing use of elastomeric
cables terminated in air-filled cable compartments, or sometimes even paper insulated cables are terminated in this way. The introduction of heat shrinkable plastics,
or elastic ‘cold-shrink’ sleevings, has facilitated the adoption of this technique.
Some of these sleeves can be made semiconducting, which facilitates the grading of
the electrical stress along insulation between the cable core and the sheath at the
termination.
Another technique for the termination in air of polymeric cables involves the use
of proprietary cable connectors. These have two forms. One has an inner and outer
semiconducting sheath which allows for the earthing of the outer coating, and which
uses termination components that also deal with the problem of stress grading of
the exposed cable insulation. The other type is unscreened and just takes care of
382
Handbook of Electrical Installation Practice
Fig. 14.9 Typical vacuum switchgear unit with withdrawable circuit-breaker.
the right-angle joint which occurs in the majority of switchgear cable compartments,
and provides the demountable jointing feature. The final step of the cable preparation is the completion with the proprietary sleeves described above.
The cable compartment is often the chosen location for the connections to the
voltage transformer, where this is required. In most parts of the world these are
required to be fuse-protected, which brings in its train a requirement for the provision of facilities for safely changing these fuses with the circuit energised.
Switchgear
383
Fig. 14.10 Typical SF6 switchgear unit.
As the switchgear usually forms the most convenient point at which access can
be gained to the main conductors of a distribution network, it is usual to provide
safe facilities for making connections to those main conductors. When the circuitbreaker is withdrawable, then access to either the busbars or circuit side conductors
can be obtained through the orifices into which the circuit-breaker is normally
plugged. When the circuit-breaker is of the fixed type then separate orifices for
testing and access to circuit conductors are provided.
384
Handbook of Electrical Installation Practice
Fig. 14.11 SF6 switchgear unit with horizontal withdrawal.
Interlocking and padlocking
In order to ensure safe operation of switchgear, particularly when obtaining access
to conductors for such operations as cable fault detection, phasing out, testing of
cables, etc., it is usual to provide mechanical interlocks or padlocks to control
access. The first interlocking requirement on all forms of withdrawal switchgear is
to ensure that the circuit-breaker cannot be withdrawn or plugged in while it is
closed. Generally, metallic shutters are provided, which automatically cover the
plugging orifices when withdrawable circuit-breakers are removed from the switch
Switchgear
385
cubicle. Similarly, facilities are made available so that these shutters can be padlocked in the closed position to maintain the full safety of the metal-enclosed
equipment.
Operation and maintenance
The most common position of the circuit-breaker is in the normal service location
so that when it is closed it connects the circuit to the switchboard busbars. It is usual
for metal-enclosed switchgear to incorporate secondary connections between the
cubicle and the circuit-breaker which are automatically made when the circuitbreaker is racked into the service location. To ensure correct operation in service
the interlock used to prevent the withdrawal of a closed circuit-breaker must be in
the correct position for circuit-breaker operation.
Earthing
It is standard British practice for earths to be applied to distribution systems by
using a proven fault-making device such as the circuit-breaker itself. The application of an earth to any system is normally controlled through a permit-to-work
system. This ensures that all the necessary switching operations to make the relevant circuit dead have been carried out before the system is earthed.
With vertically isolated switchgear it is convenient to use the facility of moving
the circuit-breaker into and out of the unit to provide earthing locations. These are
illustrated in the case of a typical bulk oil switchgear unit in Fig. 14.8. This shows
typically the disposition of the VTs, CTs, instrument panel, etc.
The selection of the correct location in which to raise the circuit-breaker into
either the service, circuit earth or busbar earth position is under padlock control.
Other methods in use for providing earthing facilities with proven fault-making
capability are the provision of extension plugs for the circuit-breaker itself so
that it can be used in the service location with an earth connection to the other
side of the circuit-breaker. A further way is the provision of a special fault-making
earthing switch which is interlocked with the circuit-breaker so that the circuitbreaker must be removed from service before the switch is used. Finally, the most
expensive way of achieving fault-making earthing is by the provision of an alternative device which replaces the circuit-breaker and its carriage and is so designed as
to contain a fault-making earth switch, usually with facilities for carrying out tests
as well.
Maintenance
The maintenance of electrical switchgear is covered in detail by two British standards: BS 6423 for switchgear up to 650 V; and BS 6626 for switchgear above 650 V
and up to and including 36 kV. There is a third for switchgear above 36 kV, but that
is outside the scope of this book.
These standards contain a substantial section on safety precautions and on the
use of permit-to-work systems for ensuring safe access to the plant to be maintained.
The maintenance itself for the high-voltage equipment is divided into four
sections: servicing; inspection; examination; and overhaul. BS 6626 differentiates
for the first time between the oil and air types of circuit-breaker which require
386
Handbook of Electrical Installation Practice
regular examination and overhaul, and vacuum and SF6 circuit-breakers which
usually do not.
This standard also makes it clear that it is the manufacturer’s responsibility to
inform the user when and how to maintain switchgear, and contains and appendix
listing the required content of the manufacturer’s handbook for this purpose.
As the names imply, the servicing and inspection procedures involve a visual study
of the switchgear and could include an operational check to ensure that all is in
working order. The serving includes such items as the lubrication of operating mechanisms and possibly cleaning of accessible parts. Neither operation is supposed to
need the use of any tools, although it will probably be necessary to take the circuitbreaker out of service to obtain the required access.
Examination means the dismantling of certain parts of the equipment to give
access to internal components. Usually this would follow an inspection that had
given rise to doubts concerning the condition of such components.
Overhaul means the replacement or refurbishment of components which have
been shown by inspection or examination to require such attention.
With vacuum and SF6 equipment, the manufacturer is strongly urged to provide
facilities and advice for diagnostic testing techniques which will indicate the need
for examination. As mentioned earlier, these types of sealed-for-life switching
devices should require no internal maintenance over periods of the order of 20
years.
ERECTION OF SWITCHGEAR
The switchgear cannot always be assembled in the factory and shipped to site as a
complete plant, so it is usually necessary to pack the equipment in its individual
cubicles, ship to site and eventually erect it. Erection includes the setting in place
of these cubicles, their interconnection both mechanically and electrically, and the
fitting of any extra relays together with the power and control cables. The chambers
may have to be filled with insulating media of different types.
Once the equipment has been erected it needs to be commissioned, which is
defined as the work of testing and finally placing in service of the installed apparatus. Before being put into service tests must be carried out on the complete equipment to prove that it meets the required specification.
Storage
It is best to deliver the switchgear cubicles at a time convenient for their immediate erection. However, it sometimes happens that the site works are delayed, in
which case the switchgear must be stored carefully until it is needed.
On delivery it is important to check that all items are present and correct in accordance with the delivery note and then to store these components carefully to ensure
that no parts go astray. At all times, care must be taken to maintain the condition
of the stored items; precautions must be taken to ensure that the equipment is
properly stacked, for example, and that it is kept clean and dry. If possible,
Switchgear
387
arrangements should be made to keep the building temperature in excess of the
dew point so that condensation on the equipment is prevented and thereby the plant
is protected from corrosion.
Erection
Before commencing erection it must be ensured that the workforce is in possession
of all the drawings and instructions required to erect the equipment, which are normally provided by the manufacturer. The substation in which the switchgear is to
be erected should be as clean and dry as possible and all debris should have been
cleared away.
During erection particular attention should be paid to a number of points:
•
•
•
•
•
Dirt and debris should be excluded from partially erected cubicles.
All openings that are not in immediate use should be blanked off or covered by
clean sheets.
All electrical insulation should be kept clean and dry by being kept covered and,
if necessary, heated.
Materials which have been issued from stores and not yet used on erection should
be stored safely and tidily.
When handling the cubicles and major components care should be taken to
observe the correct lifting arrangements and to make certain that slings are
attached to the manufacturer’s designated lifting points. This ensures that no
parts are subjected to undue strains or sudden stresses which could result in
disturbed settings or other damage.
Foundations
The successful erection and operation of the switchboard depends very largely on
the accuracy of the foundations. The most useful form of fixing medium for the type
of switchboard considered here is some form of proprietary channel embedded in
the floor, containing captive adjustable nuts. These channels should be assembled
truly parallel and level and should project slightly above the surrounding floor. This
is so that the switchgear can be clamped to the channels themselves which are then
known to be at the correct level. Less commonly nowadays, holes may be cast in
the floor in which suitable foundation blots can be grouted after the switchgear has
been erected carefully.
General assembly
It is normal to commence the assembly of a distribution switchboard from the centre
unit. This minimises any effect of a build-up of errors as the equipment is erected.
Any inter-unit tie-bolts are loosely positioned as erection proceeds, and all units
lined up onto the centre unit. Plumb lines should be used on each unit to ensure
good alignment. When all units have been placed in position and checked for alignment, the inter-unit bolts may be tightened and checks may be made that any withdrawable portions can be entered or withdrawn smoothly. Instrument panels and
any other component details should then be added to the switchboard.
388
Handbook of Electrical Installation Practice
Busbar and circuit chamber assembly
The actual section of the busbars to be used should be quoted on the manufacturer’s
drawings and care must be taken to ensure that the appropriate section is used for
a particular unit.
Some general guidelines on preparation of contact surfaces are given below, but
it cannot be overstressed that at all times the manufacturer’s instructions must be
followed.
Contact surfaces must be cleaned carefully before assembly, using fine emery
cloth where the surface of the contact is of natural finish, and using a proprietary
silver polish if the surfaces are plated. Where the connections have threads these
should be cleaned with a fine scratch brush. After cleaning, the joint faces must be
wiped with a clean lint-free cloth to remove any dust, and the joints assembled as
soon as possible.
Normally, the lower busbar is connected up first, with the joints insulated as
required, ensuring that a good electrical connection is made between all copper
faces and that all securing nuts are tight. The next bar to be assembled will be the
centre one and, finally, the top one.
The same treatment of joint faces must be carried out on all other connection
joints within the circuit chamber, such as connections for VTs.
The manufacturer’s instructions should be checked carefully to see whether any
or all of the joints that have been made on site are required to be insulated. If this
is the case then the components needed should have been supplied with the equipment and the instructions given by the manufacturer should be followed carefully,
particularly in respect of any recommended safety precautions, with special attention to the chemical reagents that may be used.
Cabling
The preparation of the cables for connection to the switchgear is a specialist occupation and an experienced jointer should be employed for this purpose. The cable
has to be laid carefully to avoid tight bends and the length to the cable lug
measured very carefully to avoid any stress on the cable once the joint has finally
been made. Minimum bending radii for cables are specified in BS 6480.
Insulation of the exposed cable and of the joint is frequently provided by means
of heat shrinkable plastics sleeves. These should be applied and terminated in
accordance with the manufacturer’s specific instructions. Where proprietary cable
connectors are supplied for the termination of the cables, apply these with careful
reference to the termination maker’s instructions, or employ a specialist contractor.
Where crimping is employed for the attachment of lugs or thimbles to the cable
core, it is vitally important only to use the type and size specified by the maker for
the core size in use.
Occasionally, paper cables are still terminated in compound-filled boxes and
where this is the case care should be taken to ensure that the compound used is
continually stirred during the melting period, to avoid excessive heating and possible burning of the compound at the bottom of the boiler. Care must be taken to
ensure cleanliness of the cable box and all utensils associated with this operation.
The cable box itself, and any buckets or ladles which are used in the operation, must
be pre-heated before use and the compound at the appropriate temperature should
Switchgear
389
be poured slowly to avoid splashing and the inclusion of air bubbles. When the cable
box is filled to its indicated level, the compound should be allowed to cool slowly,
avoiding draughts. If the compound falls below the indicated level on cooling, it
should be topped up while still warm to ensure a good bond between the main mass
and the topping layer.
Earthing
Each unit forming part of any installation must be earthed by means of a copper
strip fastened by a bolt or stud connection. This earth strip must be continuous and
connected to all units and fastened to the main earth. All joints must be cleaned
and treated as busbar joints. Special attention should be paid to the earthing of cable
sheaths at cable glands.
Oil filling
Where chambers have to be filled with insulating oil on site it should first be checked
that the oil supplied is in accordance with the manufacturer’s recommended grade.
All electrical oils must conform with BS 148 and the oils must be tested for electrical breakdown before filling, as described in BS 148 and BS 5730. The equipment
must be filled to the indicated level, and it is advisable to fill VTs after they have
been positioned on the switchgear. The indicated level is usually based on an
ambient temperature of 15°C, and if the actual site temperature differs significantly
from this, then due allowance should be made.
Gas filling
Gas-filled circuit-breakers or switchgear compartments are usually shipped filled.
Where the design pressure is relatively high the manufacturer may avoid shipping
problems by filling only to just above atmospheric pressure and topping up to
the recommended filling pressure on site. In this connection it is necessary to
understand the two defined pressure levels used in the standards for gas-filled
switchgear. These are the filling pressure, which is the pressure to which the enclosure is filled before being put into service, and the minimum functional pressure,
which is the lowest pressure at which the switchgear retains all its ratings. It is
important to determine the filling pressure recommended by the manufacturer for
the particular switchgear being erected, so that it can be checked to ensure that
it is filled to this level before commissioning. In some cases it may be recommended to take a sample of the gas for test before energising the switchgear. If this
is the case, then the manufacturer’s instructions must be very carefully followed, to
avoid loss or contamination of the gas. BS 5209, Guide for checking SF6 gas, is also
helpful.
Vacuum interrupters
It is often recommended that the integrity of the vacuum in the interrupters be
checked before putting into service to ensure that no damage has been done during
the shipping process. The manufacturer’s handbook should be consulted for guidance on this point, since it usually involves applying a high voltage across the open
contacts of the (or each) interrupter. Precautions should be taken to safeguard
personnel from the possible generation of X-rays during this procedure. The
390
Handbook of Electrical Installation Practice
manufacturer will have given guidance on this point also. Generally it is possible
to apply this voltage without exposing the vacuum interrupter, so that the metal
enclosure can act as a screen. In such a case there will be no possibility of radiation,
external to the enclosure.
Small wiring
It is usually necessary to complete small wiring connections between the instrument
panels on adjacent cubicles and to connect external multicore cables to the control
cable terminating boxes, which are usually mounted at the rear of the switchgear
units. If it is not already contained on the wiring diagram, a useful aid to ensure
correct connection for multicore cables is to list the cores in order and record the
appropriate connection to be made to each core at each end of the cable.
Final inspection
After the switchboard has been finally erected, all securing bolts tightened, all
busbars and other connections completed, all insulation finished, cables connected
and small wiring completed, a final inspection should be made. The following is a
typical, but by no means exhaustive, check list:
(1) Before fitting covers, all chambers should be checked for complete cleanliness
and the absence of all foreign matter.
(2) Once the covers have been fitted, it should be checked that all fixing screws are
in place, and secure.
(3) All labels, where required, should be fitted and visible.
(4) Any mechanical interlocks should be checked; safety shutters, where fitted, must
be checked to be operative.
(5) All withdrawable items should be proved to be capable of extraction and
isolation as required.
(6) All fuses and links of the correct current rating should be inserted into the
appropriate holders.
(7) All exposed insulation surfaces must be clean and dry.
(8) A final check should be made for continuity of earthing.
(9) All tools used in the erection of the switchboard should be carefully accounted
for.
ELECTRICAL TESTING AND COMMISSIONING
Routine factory tests will have been carried out during manufacture in order
to check design criteria and the maintenance of the supplier’s standards. These
tests provide a valuable reference when any query is made concerning the apparatus during its commissioning tests and operational life. Commissioning tests are
conducted on site after installation of the equipment. These are to ensure that
the apparatus will perform its duties in service, that interconnection with other
equipment is correct and to provide data for future maintenance and service work.
The conducting of these tests also provides valuable training for the purchaser’s
Switchgear
391
operating staff. Normally, such tests are carried out once only, after installation,
prior to putting the apparatus into service. The most common form of commissioning test is to simulate operating conditions using portable voltage and current
sources. A test log should be maintained listing all tests carried out, the results and
objectives.
Typical commissioning tests include: visual checks, earth impedance measurements, insulation resistance checks, current and voltage transformer checks, portable
primary current injection testing, circuit-breaker operation checks, control and
scheme tests, secondary current injection testing and load testing.
Visual checks
The object of such a check is firstly to ensure the mechanical integrity of the equipment. Then all electrical connections made on site should be checked to the appropriate diagram to ensure their correctness. Check that all fuses and links are in place
and have been fitted with the appropriate fuse wire or cartridge.
Insulation resistance checks
Insulation resistance measurements on all small wiring should be carried out at
500 V d.c. This test is to ensure that such wiring is in good condition. Any apparatus
which may be damaged by application of such a voltage, e.g. static protective devices,
should have the appropriate terminals short-circuited for the duration of this test.
When measuring the insulation resistance to earth of the individual circuit, all other
circuits should be normal, i.e. earth links closed and d.c. circuits normal. This ensures
that the insulation of the particular circuit is satisfactory both to earth and to all
other circuits.
It is impractical to give a definitive lower limit for the resistance measurement
from this test. Such readings are dependent on the cable length, the size of cores
and the number of parallel paths. As a guide, any reading of less than 1 MW at
500 V d.c. should be investigated.
Current and voltage transformer checks
Normally the VT and CT wiring will have been completed at the manufacturer’s
works and only if this wiring has been disturbed is it necessary to carry out any tests
on site. Should this be the case then one essential test to be carried out is to ensure
that the CT secondary winding has been connected correctly in relation to the
primary winding. Should this have been reversed in any phase then the operation
of the protection will be seriously affected.
All CTs have some means of identifying the primary and secondary terminals:
common practice is to identify as P1–P2 (primary 1 and 2) and S1–S2 (secondary 1
and 2) as recommended by BS EN 60044, with test windings identified as T1–T2.
The following test is recommended to prove these relative polarities (Fig. 14.12).
A low reading d.c. voltmeter is connected across the CT secondary winding
terminals and a battery across the primary. If relative polarities are correct, on
closing the circuit a positive ‘flick’ is observed on the voltmeter, and on opening the
392
Handbook of Electrical Installation Practice
Fig. 14.12 Circuit required to test for CT terminal polarity.
circuit a negative ‘flick’ is seen. Where CTs are mounted in transformer bushings it
is necessary to short-circuit the main transformer l.v. winding, thus reducing the
equivalent impedance of the transformer to give a good deflection of the instrument
needle. Voltage transformers may be checked in similar fashion.
Proving of protection
The operation of the various forms of protection which can be fitted to distribution
switchgear is covered in Chapter 22. Suffice it to say that the operation can be
simulated either by injecting heavy currents through the CT primaries or by the
injection of suitably chosen currents into the CT secondary circuits. In some
instances the CTs may be fitted with a special tertiary winding intended for test purposes in this way. Whichever method is adopted, the intent is to inject currents that
represent fault conditions of various types, and to check that the relevant relays
operate correctly and that any auxiliary relays that are called upon to perform do
so also in a correct manner.
To adjust the current settings it is normal to use a variable autotransformer to
provide the supply. As the waveshape of the test current can have an influence on
the behaviour of the relay it is recommended that as much series resistance as
possible should be included in the injection circuit.
High-voltage tests
If called for in the contract documents h.v. tests can now be applied to the insulation. The test values should be those be those laid down in the appropriate standard
Switchgear
393
for site testing and should be applied by an a.c.h.v. test set or, particularly if the
cables have been connected, at equivalent d.c. test set. Where vacuum circuitbreakers are in use it is usually recommended that a commissioning voltage test
be applied across the open interrupter as a check that the vacuum is still in perfect
condition.
Circuit-breaker operation tests
Following the completion of insulation testing the circuit-breaker should be checked
for operation. These checks should cover tripping and closing operations from both
local and remote postitions, and should preferably be carried out at minimum and
maximum supply voltages. It should be checked that correct indication of the closed
and open position is given by both the mechanical and any electrical indicators that
are fitted. The correct operation of the interlocks should be checked. Not only
should one ensure that the permitted operations can be undertaken but that the
interlocks prevent the carrying out of prohibited operations as intended.
Before carrying out these tests care must be taken to ensure that the circuit is
isolated from any source of power supply.
Load testing
Once all the checks on the equipment have been carried out, the operational tests
are satisfactory, the voltage tests passed, and all the functional tests on relays, etc.
completed to the customer’s satisfaction, the equipment can be energised. Once the
circuit is on-load it can be checked that all the instruments and indicators are
reading correctly.
If test blocks are available or the relays have test plug connections, it may be
worthwhile doing a final check to see that the CT polarity is correct and the instrumentation is giving correct readings.
CHAPTER 15
Rotating Machines
D.B. Manning, CEng, MIEE
(Mawdsley’s Ltd)
Reviewed by G. Walton, MIETE
(Internal Sales Engineer, Eurotherm Drives Ltd)
Electricity is a particularly attractive form of energy in that it can easily be produced, transmitted and converted into some other form. The commonest form of
energy into which electricity is converted is mechanical driving energy and more
than 60% of electrical energy produced is utilised in this way. Conversion of energy
from its electrical to mechanical form is achieved using electric motors. The vast
bulk of industrial electric motors is used to drive pumps, fans and compressors. All
industrial installations, whether manufacturing units or complex process plants,
include electric motors, often of many types, sizes and voltages to suit a wide variety
of applications.
Often much abused, electric motors are expected to perform efficiently and
reliably for many years with the minimum of maintenance. In relation to the cost
of the energy they convert they are extremely inexpensive. Typically, the electrical
energy costs of supplying a motor can equal the prime cost of the motor in only two
months of operation. Installation, cabling and control gear costs will perhaps double
or even treble this period but this is still a small cost in the normal expected machine
life. Many motors supplied over 50 years ago are still performing well in plants
around the world.
Therefore, selection of the right type of machine for the application and duty, and
correct installation and maintenance of the machine, are as important as the
machine design itself.
This chapter concentrates on motors but does make reference where appropriate to alternators. Similarly, reference is limited to machines up to 11 kV and
10 MW.
MOTOR TYPES
All motors fall into one of two classes: those suitable for use on a.c. supply and those
suitable for d.c. systems.
Alternating current motors
There is a large range of a.c. motors available, the most widely used being the cage
design.
394
Rotating Machines
395
Cage motors
Three-phase cage rotor induction motors are available in ratings up to 10 MW.
Essentially simple and robust in construction, the ubiquitous cage motor has a distributed stator winding which establishes a rotating field and a rotor comprising
copper or aluminium bars welded or brazed at each end to a short-circuiting ring.
It is the ‘cage’ appearance of the rotor which gives rise to the name by which the
machines are known. In smaller motors the cage may be cast in aluminium alloy
such as LM6.
The rate at which the field rotates is determined by the number of poles on
the distributed stator winding and on the supply frequency. The more common
rates or synchronous speeds are given in Table 15.1. The synchronous speed Ns is
given by
Ns =
f
¥ 60 rev min
P
where f is the supply frequency (Hz) and p is the number of pole pairs.
Cage induction motors do not run at a synchronous speed, because the torque
they produce depends on the speed difference or slip between the speed of the
rotating field (synchronous speed) and the lower speed of the rotor. The slip
however is quite small, can be predetermined within limits by motor design, and will
be about 5% on a small 10 kW motor reducing to less than 1% on motors above
the 100 kW.
The speed/torque relationship of Fig. 15.1 is typical in shape for a cage motor
started direct-on-line. The motor operates at the point where its speed/torque curve
intercepts the load characteristic at speed N. Slip rev/min = Ns - N (where Ns is the
synchronous speed and N is the rotor speed). The vertical difference between motor
and load speed/torque characteristics is the accelerating torque. Clearly therefore
Table 15.1 Synchronous speeds.
396
Handbook of Electrical Installation Practice
Fig. 15.1 Cage motor speed/torque curve.
the motor torque available must always exceed the load requirement up to the
operating speed if the load is ever to reach full speed.
The induction motor designer can influence the shape of the speed/torque characteristic to achieve, say, a higher torque at start. He must however strike a balance
between conflicting requirements. With a cage motor it is not possible to insert additional rotor resistance. A compromise then has to be made between high starting
torque (and high rotor copper loss and on-load slip) and higher efficiency low slip
operation.
Where high starting torque and low on-load slip are necessary, a double cage rotor
may be used. This has two separate cages – one close to the surface of the rotor producing its maximum torque near standstill and the other ‘inner’ cage which has a
lower resistance (and higher reactance) for maximum torque closer to synchronous
speed.The speed/torque curve of a double cage motor is the sum of the speed/torque
curves of each of the two cages (Fig. 15.2).
Induction motors may be designed to operate at more than one discrete speed
by pole changing. That is by having tappings in the stator winding to allow selection
Rotating Machines
397
Fig. 15.2 Torque/speed curve of double cage induction motor.
of say four- or eight-pole speeds. Alternatively the stator may have two separate
windings to permit the motor to run at say four- or six-pole speeds. Pole changing
complicates the control gear, which sees the motor as two separate differently rated
machines.
Three or four different pole numbers can be accommodated in one motor but
this is not common bearing in mind the fact that continuously or infinitely variable
speed drives are so freely available and are relatively inexpensive.
Starting currents
Starting currents are quite high and are up to eight times full load current
for machines up to 30 kW and up to six times for larger motors. Except at the
extremities of supply lines the system capacity is normally adequate to supply
these currents without too much voltage drop. Where the starting currents are
likely to be an embarrassment, special high resistance or deep slot rotor bars
can be used which reduce the starting current to below five times full load
current. These are by definition special machines and more costly so that reduced
voltage starting is a more usual method of restricting the starting current (Chapter
17).
Whether star-delta or auto-transformer reduced voltage starting is employed, it
is important to remember that while the starting current will be proportional to the
applied voltage, the starting torque will theoretically be proportional to the square
of the applied voltage (Table 15.2). In practice, the effect of stray losses reduces
further the available starting torque at reduced voltage.
If reduced voltage starting is used, then a careful check must be made to ensure
that accelerating torque is available.
398
Handbook of Electrical Installation Practice
Table 15.2 Nominal starting currents and torques.
Soft starters are becoming a common method of starting induction motors. They
are thyristor-controlled a.c. voltage regulators which ramp up the voltage applied
to the motor during starting. The ramp rate or starting time can be adjusted while
at the same time a current-limiting circuit limits the maximum current drawn by the
motor during starting.
As with other forms of reduced-voltage starting the starting current is restricted
at the expense of staring torque. Soft starters therefore are particularly useful for
motors driving centrifugal loads and, because of their infinitely variable voltage
range between zero and system voltage, for minimising the starting current depending on the motor speed torque characteristic and load requirements.
Slip-ring induction motors
Much less widely used are slip-ring induction motors where the cage rotor is
replaced by a distributed wound rotor, the three-phase rotor winding being connected to slip rings mounted on the shaft. Except during starting the slip rings are
short-circuited and the rotor behaves exactly as a cage rotor. The advantage of the
wound rotor slip-ring machine lies in the possibility of inserting external rotor
circuit resistances during the starting period.
The rotor control gear can be arranged to be switched sequentially, automatically
reducing the values of resistance in the rotor circuit as the motor runs up to speed.
A family of speed/torque characteristics, one for each resistance value, is generated
as shown in Fig. 15.3. Note that changing the value of externally connected rotor
resistance does not change the value of maximum torque – only the speed or slip
at which it occurs.
The number of resistance steps can be chosen appropriate to the starting
torque requirements and starting current limitations. The external resistors usually
take the form of metallic grids and if appropriately rated, allow the motor to
run for long periods at reduced speeds. Very large slip-ring motors may still from
time to time employ liquid rotor resistors for starting. These are better able to
dissipate the heat generated, and the speed variation during start up is stepless.
The high losses appearing as heat in the rotor circuit resistances prevent this
system being more widely used for economic continuous reduced or variable speed
running.
Rotating Machines
399
Fig. 15.3 Family of speed/torque curves for different external rotor resistances on a
slip-ring induction motor.
The principal disadvantages of the wound rotor motor compared with the cage
machine are higher prime cost of motor and starting equipment and increased maintenance due to the slip rings and brushes.
Synchronous machines
Synchronous machines are most commonly encountered as alternators in the range
up to 5 MVA as standby power generators or even as main base load generators in
remote areas. As motors, synchronous machines above 5 MVA are used mostly
where their ability to generate reactive power and so improve the power factor of
the installation, coupled with their slightly higher efficiency, offset their higher cost
when compared with the cage motor.
Synchronous machines are almost always brushless. The increased availability in
recent years of thyristors and diodes has enabled design engineers to dispense with
slip rings and to opt for static excitation and brushless systems.
The construction of the majority of brushless synchronous machines comprises a
stator with a distributed winding and a rotor with salient pole field windings. These
are supplied through a rotating diode rectifier assembly fed by a shaft mounted
exciter, as shown in Fig. 15.4. For economic reasons, the exciter for larger power
ratings is itself controlled using a pilot exciter or static excitation regulator.
400
Handbook of Electrical Installation Practice
Fig. 15.4 Three-phase brushless alternator with automatic voltage regulator.
Although the machine runs at synchronous speed without any slip, the rotor lags
behind the rotating field by a variable angle, known as the load angle. This is
approximately proportional to the load imposed on the motor. The starting of
synchronous motors depends on the size and rating. Smaller machines, say up to
10 MW, are usually started as cage motors utilising pole face damping windings or
linked solid pole faces as the cage. Above that rating they may employ pony motors
or even variable frequency power sources to accelerate from rest to almost synchronous speed.
High-speed (two-pole) synchronous machines almost certainly have cylindrical
rotors due to the problems of centrifugal forces on salient poles although, in general,
turbo-type machines are available only at powers in excess of 10 MW.
Synchronous reluctance motors
The majority of fixed-speed drive applications tolerate the slip rev/min associated
with induction motors. Nevertheless some applications do require a precise known
drive speed. Synchronous reluctance motors, available up to about 250 kW, fulfil this
need. An example of their application is as a drive machine on a buffer or uninterruptible power supply where the output frequency of the alternator must remain
the same as the input frequency to the motor alternator set.
Essentially the synchronous reluctance motor has a stator with a distributed
winding for the appropriate number of poles of speed. A shaped laminated rotor
with a cage winding follows the rotating field at exactly the same speed but with a
variable load angle. A typical machine is shown in Fig. 15.5.
Started as cage induction motors, they draw large starting currents and run at
relatively low power factor. On the other hand, they are extremely robust and
inexpensive.
Rotating Machines
401
Fig. 15.5 A typical Mawdsley synchronous reluctance motor rated at 15 kW and
1500 rev/min.
Direct current motors
Far from being old fashioned, d.c. motors continue to be widely even though
few factories have a d.c. power distribution system. Once again it is the thyristor
regulator which, in conjunction with one or more d.c. motors, provides a very
formidable and flexible variable speed drive system. Direct current motors have
apparently changed little over the years and still retain a salient pole stator to
accommodate the field or excitation windings and interpoles. The rotor is a
distributed winding in slots soldered, brazed or welded to the segments of a
commutator.
In fact the construction has changed to recognise the particular characteristics of
thyristor regulators. Modern d.c. motors have laminated poles and even laminated
yokes. The laminated construction helps to improve commutation by allowing the
magnetic circuit to respond more quickly to flux changes occasioned by thyristor
regulators. Square frame designs on the market have much improved power/weight
ratios together with other advantages (Fig. 15.6).
One outstanding advantage of d.c. over a.c. motors is the electrical accessibility
of the field winding and the possibility therefore to influence the excitation by field
forcing to achieve very fast response drives.
The speed and torque characteristics of a d.c. motor are very easily controlled.
In general, for constant flux in a shunt-wound separately-excited machine, its
speed and output power is approximately proportional to the applied armature
voltage. (The speed is actually proportional to the back e.m.f. which is less than
the applied voltage by the amount of the armature voltage drop due to its
resistance.)
402
Handbook of Electrical Installation Practice
Fig. 15.6 A Mawdsley’s square frame industrial d.c. motor rated at 250 kW with forced
ventilation.
For constant armature voltage its speed and output power are inversely proportional to field voltage (flux). The speed range over which the motor operates by field
voltage control is known as the shunt range (Fig. 15.7).
Most d.c. motors used are separately-excited shunt-wound machines with interpoles. Figure 15.8 shows the connection of such a motor and includes a series compounding winding which may sometimes be fitted to produce a drooping speed
torque characteristic.
To avoid excessive flux distortion and maximise output the motors have interpoles as well as main poles. The interpoles carry the armature current and influence
the flux as the load and hence armature current changes to minimise the effect of
armature reaction. They significantly reduce the flux appearing in the regions
between the main poles where the brushes are located to reduce sparking between
brushes and commutator.
Figure 15.9 illustrates the section of a four-pole square frame d.c. motor. Tucking
the interpoles up into the corners gives maximum utilisation of field space and
allows the use of a larger diameter armature than would be the case with a conventional round frame four-pole motor.
On larger d.c. motors, say above 500 kW, it is common to achieve the flux necessary with minimum distortion by employing a six-pole construction when the square
frame gives way to a conventional round shape.
Certainly on these larger motors, and often at much smaller ratings, pole face
compensating windings will be incorporated. As their name suggests, they are
accommodated in slots in the main pole face and are closed coils. They produce a
flux under the main poles to cancel out the effect of the flux produced by the current
Rotating Machines
403
Fig. 15.7 Speed control of separately excited d.c. motor.
Fig. 15.8 Separately excited shunt-wound d.c. motor.
in the armature conductors. Sudden changes in load cause corresponding flux distortions due to armature reaction. By cancelling these out the compensating windings prevent large voltage surges in the armature conductors which might otherwise
result in flashover.
Separately-excited shunt motors have a fairly flat speed/torque curve for constant
excitation (Fig. 15.10) although some highly stressed motors will have a characteristic which rises with load. This is not necessarily disadvantageous since almost all
d.c. motors form part of a closed loop speed-control system with tachogenerator
feedback. Providing that the maximum speed can be achieved off-load with
maximum applied armature voltage and with a cold shunt field the speed-control
system is capable of regulating the motor speed over the load range by armature
voltage and in some cases by additional field voltage control.
404
Handbook of Electrical Installation Practice
Fig. 15.9 Round and square frame d.c. motors of the same height.
Fig. 15.10 Comparison of d.c. motor speed/torque characteristics.
Compounding, that is the provision of an armature current-carrying winding on
and assisting the main pole winding, has the effect of increasing the flux and reducing the speed with increasing load, resulting in a more stable drooping speed/torque
curve (Fig. 15.10). This can be useful and assists load sharing if several motors are
to operate in parallel from a single thyristor regulator. If, however, a compound
motor is to be reversible the compound winding connections must also be reversible
by external control gear, so that its flux is always assisting that of the main pole.
Series wound d.c. motors derive their excitation only from a field system connected in series with the armature (Fig. 15.11). This means that at no-load the flux
Rotating Machines
405
Fig. 15.11 Series-wound d.c. motor.
is weak and the motor tends to run fast. As the load increases so does the flux with
large speed reduction and high torque capability. For this reason series-wound d.c.
motors are used only where they cannot run unloaded and are found particularly
in applications such as traction.
Motor generator sets
Motors are invariably used to convert electrical to mechanical energy and vice versa
in the case of generators. Motor generator sets, on the other hand, are used to
convert one form of electrical energy to another.
This may be d.c. to a.c. such as in traction auxiliaries applications (Fig. 15.12)
or when battery power is required in an a.c. system (e.g. uninterruptible power
supplies). Battery charging, welding and Ward Leonard drive systems are typical
applications for a.c. to d.c. converters.
Both d.c. to d.c. and a.c. to a.c. sets may be required, the former for voltage raising,
lowering or regulation of a d.c. power source, and the latter for frequency changers.
Fig. 15.12 Unit construction motor alternator set. Input 600 V d.c., output 6 kVA, 240 V,
single-phase 50 Hz.
406
Handbook of Electrical Installation Practice
Machines changing 50 to 60 Hz and 60 to 50 Hz allow equipment from one part of
the world to be used in another and for shore-to-ship power supplies.
A wide range of computer, telecommunications, radar and military equipment
operates at 400 Hz and therefore demands motor generator sets for frequency
changing.
Machines operating at 50/50 Hz and 60/60 Hz are commonly used as buffer sets
or load isolation sets in order to protect sensitive loads from mains-borne spikes,
noise and brown-outs. They will also prevent confidential computer data entering
the supply system in the form of noise where it could be received and decoded by
unauthorised personnel. Owing to their rotational inertia, the sets will provide ridethrough for several cycles.
Two individual appropriate machines can be coupled together and mounted on a
bedplate to form a motor generator set, but often weight and size restrictions
encourage the dedicated design of two machines in a single frame supported
between two bearings. Figures 15.12 and 15.13 illustrate two examples of unit construction sets of this nature.
Conversion of one form of electrical energy to another can often be achieved
using static equipment, but the rotating motor generator set is still generally much
less expensive without being larger or heavier and offers three major advantages:
(1) Ride-through The inherent inertia of a rotating system gives it stored energy
and the ability to continue delivering power, albeit with some loss of speed and
output frequency, during short duration losses of input supply.
(2) Load isolation No electrical coupling can occur between the load and the
supply. The only connection between the two is a mechanical one in the shaft
between the two machines of the set.
Fig. 15.13 250 kVA 50/400 Hz frequency converter.
Rotating Machines
407
(3) Short-circuit current maintenance Rotating machines have the ability to
deliver up to five times full load current. Thus if a short-circuit fault develops
in the load the set will continue to feed the fault with sufficient capacity to cause
the short-circuit protection to operate. In the case of uninterruptible power
supplies, static equipment would transfer to bypass, if it is available, to provide
the energy to clear the fault. When the load requires a frequency different from
the supply (or bypass) this transfer option is not available to static equipment.
VARIABLE-SPEED DRIVES
A variable-speed drive comprises a motor and some form of speed regulator.
Increasing energy costs are resulting in a widening acceptance of variable speed
drives. Particularly on centrifugal pump and fan drive applications, large energy cost
savings are possible by adopting variable-speed drives in preference to throttling by
valves or dampers (Fig. 15.14). The energy cost savings can quickly repay the capital
cost of the speed control equipment.
Most pumps and compressors have a centrifugal characteristic. In other words,
while volume is proportional to speed and pressure to the square of the speed, the
power requirements are proportional to the cube of the speed. Centrifugal loads
are thus normally associated with a short speed range and derive large benefits from
a variable speed drive.
Fig. 15.14 Variable-speed drives provide significant energy sayings.
408
Handbook of Electrical Installation Practice
In the example given in Fig. 15.14 a pump running at 100% speed is delivering
40 m3/min and operates at point A where its head/volume characteristic, 1,
intercepts the system characteristic, 3, and is driven by a 400 kW motor. The pump
flow is to be reduced to 30 m3/min. Two possibilities exist:
(1) The pump flow may be restricted or throttled which produces a new system
characteristic, 4, and the pump then runs at intercept B.
(2) The pump speed may be reduced by 16% which gives a new pump head/volume
characteristic, 2, and the pump then operates at intercept C.
The power absorbed by the pump at B is approximately 330 kW and at point C,
220 kW. Thus in this example the power saving possible by pump speed adjustment
rather than by throttling is 110 kW.
For process and process line control, for example in continuous production
processes such as rubber, plastics, paper and metals, variable speed drives are
essential. The ability to control motor speeds means that other process variables
can be accommodated and that product quality and production rates can be
optimised.
Alternating current variable speed drives
There are a number of a.c. variable speed drives available, the choice often being
dictated by the requirements of the application. Gaining in popularity are variable
speed inverter-controlled cage motors, especially for single motor pumps and fan
drives having centrifugal load characteristics.
Variable frequency inverters
Apart from single motor drives, variable frequency inverters have for some time
been employed on multiple motor drives such as steel mill run-out table applications. The advantage here is that several usually identical motors can be supplied in
parallel from a single inverter in order that they all run at the same speed at any
time and the speed of the group can be controlled as a whole.
Thyristor regulators are presently in use which provide controlled adjustable frequency outputs up to 15 MW. Depending on rating, the regulators may comprise one
of two predominant systems:
(1) Fixed voltage d.c. link The link is supplied from a free running diode bridge
which in turn feeds a thyristor or transistor chopper unit. The chopper output
is a series of pulses which build up an alternating current (Fig. 15.15). This is
known as a pulse width modulated (pwm) system in which the voltage output
is controlled normally in proportion to frequency output so that the motors they
supply receive constant flux conditions.
(2) Variable voltage d.c. link These are current or voltage fed inverters which
have a conventional thyristor regulator as the input. The chopper unit is more
simple, its output frequency being determined by the d.c. link voltage. Known as
quasi square-wave inverters they also maintain constant output voltage to frequency ratio and commutate or switch only at output frequency rate (Fig. 15.16).
Rotating Machines
409
Fig. 15.15 Output waveforms of pulse width modulated (pwm) inverter.
Fig. 15.16 Output waveforms of quasi square-wave inverter.
Force commutated variable frequency inverters are used to control the speed of
cage motors up to 800 kW. Above 800 kW the machines used are synchronous
motors because they are able to provide the reactive kVA necessary for commutation and so avoid the components and complexity associated with forced commutation. The inductance of the drive motor distributed stator windings has a profound
smoothing effect on the current in the stator. The current thus approximates closely
to a sine wave. Obviously any harmonic currents present produce heat without
contributing to the output torque of the motor. In general, the harmonic currents present require derating of both cage and synchronous motors by between
10 and 15%.
Additional motor derating is probably necessary if they are to run below normal
full speed for extended periods unless the cooling system is independent of speed.
410
Handbook of Electrical Installation Practice
Static Kramer drives
Based upon the slip-ring induction motor, the static Kramer drive relies on extracting energy from the rotor and recovering it either electrically or mechanically.
The rotor energy at slip frequency is rectified and fed via a line commutated
inverter back into the a.c. supply (Fig. 15.17). A transformer is usually necessary to
match the recovered and supply voltages. Alternatively, the rectified rotor energy
and supply a d.c. motor mounted on the a.c. motor shaft (Fig. 15.18).
The speed control is stepless and is from sub-synchronous speeds down to zero.
However, the rating of the energy recovery equipment is proportional to the speed
range and the system is therefore economical only for short speed range applications such as pump drives. The ratings of static Kramer drives can be anything
between 50 and 5000 kW.
Static Scherbuis drives
When the energy recovery equipment associated with static Kramer drives is arranged to inject power into the slip-ring induction motor rotor, as well as to extract
it, then the drive is known as a static Scherbuis system and although more complex
than the Kramer, it is capable of speeds above synchronous.
Fig. 15.17 Electrical slip energy recovery of static Kramer drive.
Fig. 15.18 Mechanical slip energy recovery.
Rotating Machines
411
Alternating current commutator motors
The rotating brush arm Schrage and regulated NS motors are Scherbuis drives from
which the static Scherbuis has been developed.
All the a.c. drives described, except the inverter-fed cage motors, are not now so
common owing largely to their costs and maintenance requirements.
Eddy current couplings
The attraction of eddy current couplings is their ability, in conjunction with conventional cage motors, to provide a variable speed output by control of the coupling
excitation. Subsynchronous speeds only are possible since they operate effectively
as slipping clutches. They also at reduced speeds dissipate energy in the form of heat
and are usually limited to ratings below 15 kW. Much larger couplings are available
up to several hundred kW but these require water cooling to dissipate the heat
generated and are therefore not popular or economical.
Direct current variable speed drives
Variable speed d.c. drives have been widely used for many years, in particular for
process line speed control. They provide excellent dynamic performance and wide
speed range and have always proved to be very reliable in service. Planned maintenance techniques have successfully increased mean times between failure due to
the fundamentally simple commutator and brush assembly, to periods much longer
than associated control equipment.
The original Ward Leonard systems were superseded by magnetic amplifiers and
mercury arc rectifiers and then, in the early 1960s, by thyristor regulators for the
speed control of d.c. motors.
Switched reluctance drives
This type of drive uses a reluctance motor which has salient poles on both rotor and
stator. The distributed three-phase winding on the stator is replaced by a number
of salient pole d.c. field windings. The number of poles, as in the case of d.c. motors,
does not determine motor speed. The rotor is built up of castellated laminations and
carries no winding at all.
Unidirectional current pulses are applied sequentially to the field poles at a rate
determined by the required speed and rotor position. Control of the pulse timing is
derived from a position transducer mounted on the motor shaft. By appropriate
pulse timing either positive or negative torques can be achieved and full four quandrant control is available over a wide speed range, and both constant torque or constant power characteristics can be provided. The motor and its regulator are each
dedicated and can only be used together as a drive system.
Thyristor controlled d.c. drives
The development of thyristors having increasing current carrying capacity and
reliability permits d.c. motors to retain predominance as the most popular form of
variable speed drive. Almost all present designs are for fully controlled thyristor
regulators.
Anti-parallel connected suppressed half or circulating current regulators in
conjunction with d.c. motors allow full four quadrant control. Armature control
412
Handbook of Electrical Installation Practice
provides a d.c. motor with constant torque characteristics and field control provides
constant power characteristics. Combined armature and field control is common on
winder and coiler drives.
The thyristor controlled d.c. motor is usually fitted with a tachogenerator which
provides a speed related signal for comparison with the reference signal. It is the
error or difference between these signals which advances or retards the firing angle
of the thyristors in the regulator to correct the d.c. voltage and hence speed of the
motor (Figs 15.19 and 15.20). In addition to, or instead of using the motor speed,
other parameters such as current, load sharing, web or strip tension and level may
be employed.
Fig. 15.19 A three-phase six-pulse thyristor bridge and d.c. motor.
Fig. 15.20 Delayed firing of thyristor reduces mean d.c. voltage.
Rotating Machines
413
MOTOR APPLICATION
For reliable performance, the correct motor must be selected for the application.
Torque and starting requirements can easily be identified. The choice of motor type
is largely determined by rating and whether fixed or variable speed is necessary.
Voltages
On a.c. motors, the supply voltage is determined by motor rating. It is difficult to
lay down hard and fast rules when relating voltages to motor outputs. Up to 150 kW
it is usually l.v. There is a grey area between 150 and 750 kW when the supply voltage
can be from 380 V to 6.6 kV. Higher voltages of around 11 kV would be expected on
ratings above 750 kW.
Mounting
Mechanically, the type of load determines whether the motor shaft is to be horizontal or vertical and the particular mounting necessary. The mounting designations
are covered in BS 4999 and IEC 34–7; some of the more common ones are shown
in Fig. 15.21.
Bearings
The types of bearing incorporated depend on rotational speeds and radial and axial
shaft loadings. Designers pay particular attention to bearings to maintain the highest
level of operational reliability. Modern anti-friction bearings, of the ball and roller
Fig. 15.21 Four common mounting arrangements.
414
Handbook of Electrical Installation Practice
type, are selected to give an L10 life of 100 000 hours. This means that, given lubrication in accordance with manufacturer’s recommendations, fewer than 10% of the
bearings will fail within the 100 000 hour life. Re-greasing of bearings should be at
intervals of about 4000 running hours, unless they are of the ‘sealed-for-life’ type
commonly used on machines rated below 40 kW.
The larger and high speed motors incorporate oil lubricated sleeve bearings.
Typical threshold ratings for sleeve bearings are for two-pole machines, 2000 kW
and for lower speed machines, 5000 kW. Oil lubrication may be of the oil bath type
or, for higher bearing loadings, forced oil circulation.
Enclosure
A motor installed outside in a coastal situation must have a different form of enclosure from that of a motor installed down a coal mine or in a computer room.
The degrees of protection to which motors are constructed are specified in
National and European standards such as BS 4999: Part 105 and IEC 34–5. For a
clean environment an ‘open’ machine may be perfectly acceptable. Screen protected, drip proof, splash proof and totally enclosed machines are commonplace.
The degrees of protection, or IP numbers, most commonly met are:
IP 21 Screen protected against solids greater than 15 mm and against vertically
falling dripping water.
IP 22 Protected against solids greater than 15 mm and against dripping water
falling at any angle up to 15° from the vertical.
IP 23 Protected against solids greater than 15 mm and against water falling as a
spray at any angle up to 60° from the vertical.
IP 44 Protected against solids greater than 1 mm and against water splashing from
any direction.
IP 54 Protected against dust and against water splashing from any direction.
IP 55 protected against dust and against water jets from any direction.
The letter ‘W’ inserted between IP and the designation numbers indicates that the
machine is also weather protected to limit the ingress of rain, snow and airborne
particles.
Ventilation and cooling
Some heat is produced in all electrical machines as a result of copper, iron, friction
and windage losses. The main loss and therefore greatest heat produced is in
the windings as a consequence of copper losses. These equate to the I 2R in the
windings. Improved winding and slot insulation allow motors to run hotter without
necessarily shortening the machine life. A hotter machine provides greater kW/unit
volume, i.e. smaller machine for a given output. Smaller motors are less able in
general to dissipate the heat produced and often incorporate some external method
of heat removal. The accepted forms of cooling are specified in BS 4999: Part
106, and IEC 34–6. Some of the methods most often encountered are indicated
below.
Rotating Machines
415
Self-ventilating (IC 01)
A fan is mounted on the rotor shaft which draws surrounding air through the
motor from one end to the other and discharges it to the atmosphere. This method
cannot be used in a dirty or moist environment without adversely affecting machine
life.
Force ventilated (IC 06)
An independent separately driven fan is mounted on the machine which forces air
through the machine. The separately driven fan can be fitted with filters to remove
dirt in the air, although if the environment is dirty the filters would quickly become
choked and the motor overheat. Where filters are fitted it is usual to provide
protection in the form of a differential pressure switch to measure the pressure
drop across the filters and to shut down the plant, or at least raise an alarm when
the pressure drop becomes excessive.
Force ventilation is used in particular for variable speed drives where a shaft
driven fan becomes ineffective at reduced speeds.
Totally enclosed fan cooled (IC 0141)
Here the motor is totally enclosed and the fan mounted on a shaft extension external to the machine. It draws air from the surrounding atmosphere and a simple cowl
directs the air over the surface of the motor along its length. The body of the motor
normally incorporates cooling fins to increase the surface area exposed to the
cooling air. An internal shaft driven fan is fitted to move the air inside the motor to
minimise hot spots in the windings.
This method of cooling is particularly common on cage induction motors up to
about 500 kW, which are produced in vast quantities.
Closed air circuit, air cooled (IC 0161)
Usually encountered on machines above 500 kW which are required to operate in
dirty or difficult environments, the motor has a shaft driven fan which circulates
cooling air through the machine and around a closed circuit. An air-to-air heat
exchanger, itself cooled by a separate fan, shaft or more usually separately driven,
extracts the heat from the closed air circuit. This cooling system is usually referred
to as CACA.
Closed air circuit, water cooled (ICW 37A81)
In this case the heat exchanger of the CACA machine is replaced by an air-to-water
heat exchanger. The material from which the water tubes are made depends on
water quality. This method of cooling is more efficient than the air-to-air exchanger
so that, for the same output, a closed air circuit water cooled (CACW) motor tends
to be smaller than one which is CACA. However, water is not always available and
when it is, the attendant pipework, valves, pumps and installation costs do not always
favour CACW.
In order to extract the heat within the motor, air is forced through axial holes
in the rotor core and often also through radial slots in the rotor. Design of the
machine cooling is exacting, requiring that temperatures within the machine are
kept as even as possible from one part to another so avoiding hot spots. Keeping
416
Handbook of Electrical Installation Practice
the temperatures even increases the utilisation of material and minimises size and
cost. Typically the temperature variation from one part of the winding to another is
about 15°C. It is of course the highest temperature which determines the motor
rating.
Noise
The ventilation system is a major contributor to the noise generated by a motor.
For effective cooling the air has to be turbulent within the motor and heat exchanger
with a good scrubbing action. This applies also to totally enclosed fan-cooled
machines which generate additional noise due to the air being directed by a cowl
and rudimentary fan.
Larger and more modern motors often incorporate sound-absorbing material into
their construction.
A two-pole cage motor with CACA ventilation may produce a noise level of
95 dBA if not acoustically treated while a lower speed CACW motor with acoustic
treatment may produce only 75 dBA. Because the dB scale is logarithmic a noise
level of 95 dBA is ten times greater than one of 75 dBA.
Noise levels in industry are becoming important considerations and the subject
of various codes and standards such as BS 4999: Part 109. This is due to the
permanent damage to hearing resulting from excessive exposure to high noise
levels.
Insulation
Improvements in insulation materials and techniques permit higher temperatures.
Insulation materials do not suddenly break down at some threshold temperature;
they gradually age and deteriorate. The temperatures permitted by British (BS 2757:
1986) and European standards for each class of insulation are such as to give an
insulation system life of 20 000 running hours. This equates to, say, 15 years at 6 hours
per day, 5 days per week, 45 weeks per year. In practice the life is much longer,
because a machine is unlikely to operate always at its maximum temperature rise
in maximum ambient temperature. Exceeding the allowed temperature reduces the
insulation life by about half for each additional 10°C. Conversely, the insulation life
is doubled for each 10°C working temperature below the stated limit. The absolute
temperature of the windings and insulation is the criterion but these are always
expressed in terms of a temperature rise above an ambient temperature, normally
of 40°C. It is rare in the UK and many other countries to find an ambient temperature of 40°C, even though the ambient is the air immediately surrounding
the motor rather than the outside temperature. For water-cooled machines the accepted datum for water temperature is 30°C.
Insulation materials and in particular insulation systems, are classified by type.
The most common classifications of insulation system in current use and as defined
in BS 2757: 1986 (IEC 85: 1984) are:
Class B
Permitting a winding temperature rise of 80°C above a 40°C ambient, or
120°C maximum.
Rotating Machines
417
Class F
Permitting a winding temperature rise of 100°C above a 40°C ambient, or
140°C maximum.
Class H Permitting a winding temperature rise of 110°C above a 40°C ambient, or
150°C maximum.
The winding temperature rises quoted in each case assume that hot spots in the
winding may be 10°C hotter. For continuous operation it would be prudent and
extend the machine life if the temperature rise was limited to a figure of 10°C or
even 20°C lower than the maximum permitted by the class of insulation used.
Clearly the temperature rating of a motor is more of an art than a precise science
and it may be perfectly acceptable to exceed allowable temperatures for short
periods, such as during starting, providing that subsequent running is at a lower temperature level. The insulation life can then be estimated, and provided that it is not
less than 15 years there may be no need to use a larger and more expensive motor.
However, it is obviously essential to determine the frequency of starting, starting
currents and other duty cycle data in order to size a machine correctly.
Winding temperature protection can be provided by motor makers in the form
of thermostats or thermistors embedded in the stator windings. Unfortunately it is
not possible to fit them in the rotor windings but the motor designer is aware of the
temperature gradients in the machine and is able to select a protection operating
temperature which is appropriate. On d.c. machines the temperature detectors can
be fitted in the interpole windings. While not in the armature windings, they are at
least in the armature circuit and do more accurately monitor the armature temperature. The protection is usually arranged to shut down the plant, although on
some essential duties additional protection may be fitted which operates at a lower
temperature in order to give an advanced warning of an impending shutdown. At
least the warning will give the operator an opportunity of initiating a controlled
plant shutdown.
EFFICIENCY
Motor and generator manufactures produce machines which perform reliably and
well. Pressures exist, however, due to the consideration by many buyers only of first
cost. These compel manufacturers to minimise the amount of active material
(copper and iron) and to take advantage of the maximum temperature rise permitted by the class of insulation used. The cost of the machine is related to the
amount of materials used, while the buyer may be interested only in kW/rev/min or
torque. The pressures are therefore to increase the power-to-weight ratio and significant advances have been made over the last 20 years. Usually these advances
have been made at the expense of high efficiency.
With the increasing cost of electrical energy, and the fact that motors consume
the value of their first cost in electrical energy in only a few weeks, there is good
economic reason to consider the effect on running cost of higher efficiency.
A higher efficiency motor will cost more but not only will the premium quickly
be recovered, the entire first cost of the motor can be recovered in energy savings
in less than one year depending on the motor type, loading and utilisation.
418
Handbook of Electrical Installation Practice
To achieve higher machine efficiency the designer will incorporate more copper
in the windings to reduce the I 2R copper loss. This may mean some increase in
machine size to accommodate the additional copper.
Iron losses also will be reduced by utilising more expensive lower loss and possibly thinner electrical sheet steel for the laminations and by specially treating the
laminations to improve the stacking factor.
Fewer losses mean less heat generated and therefore less cooling, with consequent
reduction in windage losses.
Some companies already offer, at a premium, motors having an efficiency 2–3%
higher than a normal commercially available machine. That is, efficiencies of 93%
compared with 90% for 100 kW motors are readily available. One UK company is
consistently achieving an efficiency of 97% on specialised 100 kW cage motors. The
lower cooling demands of a high efficiency motor will also reduce the associated
noise level.
STORAGE
Efforts should be made to minimise the deterioration of the machine during storage
on site or in a warehouse. Dry conditions, protected from damp and condensation
and from extremes of temperature, are obviously desirable. Ingress of dust to a
machine on site should be avoided, especially of concrete dust which may be present
if building and civil work are still going on. Machines should not be stored in an
area which is subject to vibration because this could cause damage to the bearings.
If some degree of vibration cannot be avoided, the shaft should be turned by hand
every few weeks to load different parts of the bearings.
Where doubt exists about the dryness of the storage area, and the machine is
fitted with anti-condensation heaters, it may well be worth considering using
the heaters during storage. If the heaters are used for this purpose the safety
aspects should be borne in mind and terminal box covers be replaced and warning
notices attached. It is important to inspect the machine in storage every six months
or so and to maintain protective coatings on bright parts which may be liable to
rust.
INSTALLATION
Careless installation can affect the life and operation of a machine. Contractors and
users are urged to follow the machine manufacture’s instructions. General considerations are indicated below.
Checking
Machine manufacturers are not always made aware of any need to pack machines
specially for prolonged storage. Storage, for however long, may have been under
unsuitable conditions and it is essential to check before installation that the motors
have not deteriorated. While signs of rusting are obvious, the insulation resistance
Rotating Machines
419
may have been affected by moisture. If, on checking, the insulation is found to be
less than 1 MW the machine must be thoroughly dried out.
However careful the manufacturer may have been to pack the machine for difficult storage conditions, damage can occur in transit. The storage period may be
considerably longer than was envisaged at the time the machine was dispatched.
Close inspection of the machine prior to installation is therefore essential. Included
in the check should be the nameplate data to ensure that the machine is appropriate for the actual site supply and other operating conditions. Machines should certainly not operate in flammable, dangerous or corrosive conditions unless they have
been specifically designed and supplied for the purpose.
Any dust should be blown out of the machine and a detailed inspection, particularly of any machines fitted with commutator or slip rings, should be undertaken to
ensure that no damage has resulted from exposure to chemical and corrosive fumes.
Bearing grease, except in the case of sealed-for-life bearings, must be checked and
if necessary replaced if it has deteriorated during storage. Shaft clamps which may
have been fitted to minimise the risk of brinelling during storage should also be
removed.
Erection
The machine must be mounted on a solid and level foundation in order to avoid
vibration. For a foot-mounted machine design the foundation is often a bedplate of
fabricated steel on a reinforced concrete plinth. Where this is the case the bedplate
foundation bolts must be adequately proportioned and the bedplate packed so that
when it is finally pulled down on to the plinth it is flat and correctly aligned. Only
when flatness and alignment are established should the bedplate be grouted down
to provide a solid homogeneous base for the machine.
The cost of manufacture and installation of bedplates is high and machines are
now often bolted down directly on to a concrete foundation using foundation pads
set into the concrete (Fig. 15.22). Foundation pads are usually cast iron with a top
machined face and longitudinal tapped hole. The body is normally fluted for the best
possible bond in the concrete. The pads are bolted on to the machine feet and the
machine itself packed up on the concrete foundation for correct alignment. When
the machine has been aligned the foundation pads are permanently grouted into
pockets in the concrete. After final alignment and level have been satisfactorily
established, dowel holes are drilled through diagonally opposite motor feet into the
foundation pads and dowel pins inserted (Fig. 15.23). The use of dowel pins greatly
facilitates any subsequent reinstallation of the machine on its foundation. Once the
foundation pads have been permanently grouted in they behave and function in
exactly the same way as a conventional fabricated or cast bedplate.
Minor alignment or height adjustments or a change of machine are accommodated by the use of shims under the machine feet. On metric machines, the height
of the shaft centre line above the underside of the feet has been standardised
and that dimension in millimetres incorporated into the frame size nomenclature.
Thus a 400 frame size machine has a shaft centre line height of 400 mm. The only
tolerance on this dimension is negative to allow one machine to be replaced by
another of the same shaft height dimension with only feet shim changes. Bedplate
420
Handbook of Electrical Installation Practice
Fig. 15.22 Cast iron foundation pad.
Fig. 15.23 Dowel pin in place.
mounted machines are also dowelled after grouting and final machine alignment
adjustments.
Large machines with pedestal mounted bearings are usually built on and supplied
with a cast iron subframe or bedplate for mounting directly on to prepared reinforced concrete foundations.
Rotating Machines
421
Flange mounted or vertical machines are usually erected on a specially designed
subframe or machined facing which itself forms the baseplate or foundation. Vertical motors are often mounted on fabricated skirts, especially for pump drives, and
the skirts are treated as bedplates described above.
Alignment
Accurate alignment is an essential requirement if damage to bearings and flexible
couplings is to be avoided. Alignment between an electrical machine and its
prime mover or driven machine has to be established before the coupling may be
connected.
The faces of the coupling must be parallel and any separation dimension between
the faces established in accordance with coupling manufacturer’s recommendation.
The final coupling alignment would normally be established and checked using a
dial gauge (Fig. 15.24). If the machine is to be coupled to an internal combustion
engine it is necessary to remove engine spark plugs or injectors to facilitate alignment so that the set may be turned easily by hand.
Two-bearing electrical machines are usually coupled to their prime mover or
driven machine by means of a flexible coupling. The purpose of a flexible coupling
is not to permit any misalignment but to minimise transmission of bearing shock
loadings.
Single-bearing electrical machines are coupled to their prime mover or driven
machine using a solidly bolted coupling. They cannot be connected by flexible couplings because these are not designed for, or capable of, supporting the downward
thrust due to the weight of the machine rotor.
Mechanical erection is completed when the coupling halves are connected, but
some further checks are necessary before power can be applied. These should
include ensuring that cooling air flows are not restricted by obstructions to air
intakes or exhausts. Insufficient space between air intakes and adjacent walls can
cause overheating. Ensure that covers have been replaced and that any doors which
Fig. 15.24 Using a dial gauge to check the alignment of a flexible coupling.
422
Handbook of Electrical Installation Practice
have to remain open while the machine is running are clearly marked. Check that
auxiliary equipment such as blowers, tachogenerators, external coolers, filters,
bearing vibration or temperature sensors and bearing oil circulation equipment has
been satisfactorily fitted.
On machines fitted with air/water heat exchangers the water flow rate must be
measured by means of a separate flow meter to ensure that it is in accordance with
the flow rate specified on the rating plate of the machine. If a separate flow meter
is not available the flow rate can be calculated by measuring the volume of water
leaving the outlet over a set period.
Cabling and protection
Power and control cables to any machine should be of adequate current-carrying
capacity and voltage grade. Specially rated cables are necessary for 400 Hz and other
high frequencies. Effective and positive termination of cables onto machine terminals is necessary for good and lasting electrical contact. The machine is provided
with earthing studs and it is essential that a proper earth is made in accordance with
local regulations prevailing on site. Special regulations apply to increased safety
Ex(e) and flameproof or explosion proof Ex(d) machines. These require special
attention to earthing and to the use only of copper cables.
The power supply to which the machine is connected must have an appropriate
fault clearance level in relation to the fuses and other protection devices being used
in the system. Thermal protection relays are necessary to protect the machine
against overtemperature resulting from overcurrent. However, excessive temperature may also result from obstruction of the cooling medium or operation at an
excessively high ambient temperature. An overcurrent protection device will not of
course recognise this. A protection device which directly monitors winding temperature, such as thermistors or thermostats if fitted, detects high temperatures
whatever the cause. Current-dependent thermal protection relays must be provided
in addition to any winding temperature detectors.
Current relays should be selected to provide thermal protection under shortcircuit, single-phasing, locked rotor or other fault conditions. The protection device
should isolate the machine from the supply and, for an Ex(e) machine, within the
te temperature-rise time of the appropriate ignition group.
The te time is the time in seconds taken for the hottest surface of the machine
and its windings to reach the ignition group temperature under stall conditions after
it has reached its steady state full load temperature in an ambient temperature
of 40°C.
COMMISSIONING
Once the machine has been installed and cabled up correctly, a further inspection
should be made to ensure that bearings are appropriately lubricated, cooling
systems functioning properly and that cooling air inlets or exhausts are not
obstructed in any way. Power may be applied to any separately driven ventilating
fan in order to confirm that it is rotating in the correct direction. This is normally
Rotating Machines
423
indicated by an arrow on the fan casing. Providing that the fan motor has been connected with the correct phase rotation as specified in the connection diagrams, this
test should be just a formality but nevertheless an important formality because
wrong fan rotation will almost certainly significantly reduce its effectiveness with
consequent overheating of the main machine. This overheating would not be
detected by any overcurrent relay as already stated and damage to the main
machine windings could result.
Direction of rotation should similarly be checked on the main machine itself.
Again, the correct direction is indicated or specified on the nameplate or elsewhere.
Often machines, particularly the larger ones, are designed for rotation in only
one direction. Reversing the direction of rotation therefore may require some
mechanical alteration, albeit only a change to the shaft driven fan. Unidirectional
fans are more common on larger motors because they are both more efficient and
less noisy.
Alternators which have been in storage for some time may have insufficient
residual magnetism to allow proper excitation to build up. Larger alternators having
a permanent magnet pilot exciter should not suffer this problem. Some manufacturers provide the normal exciter with pole face permanent magnets embedded to
eliminate the possibility of failure to excite.
When failure to excite is experienced and a maximum voltage regulator setting
is not successful and any rotating diodes have been examined for correct functioning, flashing of the exciter field winding is necessary. This can be achieved by running
the alternator up to speed and by touching the leads from a 6 or 12 V battery across
the exciter field terminals in the correct polarity.
Checking of a rotating rectifier system requires each diode in turn being removed
from its mounting plate and its forward and reverse resistances being measured.
The forward resistance should be low and its reverse resistance high. If both resistances are approximately equal a failed diode is indicated and this should be replaced
by an identical unit.
When refitting a diode a silicon heat sink compound should be lightly smeared
on the diode seating to improve heat transfer and inhibit corrosion. A torque
spanner to the correct setting must always be used when tightening semiconductors
to their mounting plates or heat sinks.
Insulation resistance tests can be made on a brushless alternator using a 500 V or
1000 V instrument but not on the rectifiers themselves. Similarly, high voltage flash
tests should not be attempted unless the rectifiers have first been short-circuited and
any auxiliary equipment such as the voltage regulator disconnected.
Once the preliminary tests have been completed and the machine is running and
loaded it is desirable to check for vibration and to monitor and log all meter readings and speed.
MAINTENANCE
Rotating electrical machines are inherently robust and reliable and require little
maintenance. Generally, maintenance involves maintaining standards of cleanliness
and regular inspection. A machine which is running within its design parameters is
424
Handbook of Electrical Installation Practice
likely to need very little attention. The areas to be given most attention are, obviously enough, the bearing and, if fitted, the brushgear and associated slip rings or
commutator.
Bearings
Large machines which are fitted with anti-friction ball and roller bearings normally
have bearings which require relubrication. Grease is forced into the bearing through
grease nipples while the machine is running. A grease gun may be used or sometimes bearings are fitted with Stauffer greasing facilities. In both cases, air bubbles
in the grease should be avoided if lubrication is to be effective and the grease must
be of the recommended type. Cleanliness is essential to avoid dirt and grit being
forced into the bearings. Some bearings have grease escape valves to prevent overfilling the bearing and consequent overheating. The excess grease can be cleaned
away periodically without adverse effect on horizontal shaft machines. On vertical
shaft machines this excess grease is sometimes led to a container located below the
bearing and this must be emptied at the recommended intervals to prevent grease
entering the windings. The interval between relubrication depends on rotational
speed, bearing size and loading and whether the machine is horizontal or vertical.
Typically, the period is 4000 running hours for a ball bearing and approximately half
that period for a roller bearing of similar size. Specific recommendations will be
given for each machine by the manufacturer but the period between relubrications
should not exceed one year.
At longer intervals of about 8000–12 000 running hours the bearings should be
inspected by removing the outboard bearing cap and noting any serious discolouration of the grease. If serious discolouration is evident, the bearing should be removed
from the shaft, cleaned and examined more closely. Replacement of the bearing is
indicated if it shows signs of blueing, cracking, brinelling or excessive wear.
Small machines are often fitted with sealed-for-life anti-friction bearings which
do not require relubrication. Inspection of a sealed-for-life bearing is not possible
so where malfunction is suspected it should be replaced. Listening to a bearing
through a sounding rod or stethoscope can give a useful indication of its condition
but some experience is necessary before drawing too many conclusions. A highpitched whistling sound may indicate defective lubrication while a low-pitched
rumbling probably results from dirt or damage.
Removal of anti-friction bearings from a shaft involves some dismantling of the
machine although it may not be necessary to remove the rotor from the stator. Bearings are an interference fit on to the shaft so that correct withdrawing tackle, which
can apply even pressure round the bearing, should be used. Tapping or hammering
of the outer race will almost certainly damage the track. Preheating of the new
bearing to about 95°C in an oven assists in pressing it on to the shaft, and a lightly
tapped drift assists in pressing the bearing home squarely on to its seating. The drift
should be applied to the inner race if the bearing is being fitted on to a shaft and
to the outer race if into a housing.
Oil-lubricated sleeve bearings require an oil viscosity appropriate to the ambient
temperature. The oil level in the bearings must be maintained and the oil replaced
completely at regular intervals or at any sign of overheating.
Rotating Machines
425
Brushgear
Machines fitted with slip rings or a commutator have brushgear. To be effective the
slip rings or commutator must be in gook condition and free from surface defects.
Slip rings which are badly scored need to be skimmed in a lathe. For removal of
minor grooves a commutator stone can be used, rested on a brush arm as the rotor
is slowly driven round. Finally, the surface can be polished using a piece of 00 grade
glasspaper wrapped around the square end of a piece of wood as the rotor is turned
by hand.
A similar technique can be applied to commutators but ‘stoning’ is a dangerous
operation which should be carried out only by someone experienced in this
work. A commutator which is in good condition should have developed a smooth
brown surface patina. When this low friction patina is present the commutator
surface should not be stoned or polished. Raised commutator bars or mica are indicated by heavy and uneven blackening and then skimming and undercutting are
required. When the commutator is uniformly black, cleaning and polishing should
be considered.
Longitudinal undercutting of the mica insulating between commutator segments
is always necessary after skimming in a lathe (Fig. 15.25). Although the bars of the
commutator should be chamfered lightly, the bar width must not be reduced.
It is sometimes impossible to achieve the brown surface patina which provides
long brush life. The cause is usually light load running and insufficient brush current
density. So often margins are built into the specified machine rating that light loadings are inevitable. However, where this is the case, it is worth considering the
removal of some of the brushes. An equal number of brushes may be removed from
the same track on each brush arm so increasing the current density of the remaining brushes. The machine manufacturer is always willing to give advice as to the
number of brushes required per arm for the actual loadings on site.
Inspection of the brushgear will show up excessive or uneven brush wear and the
presence of carbon dust. All carbon dust should be vacuumed out of the machine
at each inspection. The brushes should be checked for wear and for freedom of
movement in the brush holder. Although brushes may be allowed to wear down
almost to the metal of the pigtail, it is worthwhile replacing them much earlier. If
replaced when they are only reduced 50% in length the brushes are most unlikely
to require attention, or cause an unscheduled plant stoppage, before the next
routine inspection. Many d.c. motor manufacturers now offer brush wear detection
Fig. 15.25 Correct and incorrect undercutting of the mica.
426
Handbook of Electrical Installation Practice
facilities which provide early warning of advanced brush wear and reduce the possibility of an unscheduled stoppage for maintenance.
Coolers
After a time any heat exchanger whether air/air or air/water will have developed
some dirt build-up which reduces the cooling effectiveness. Cleaning of the air passages, tubes and water tubes is therefore necessary from time to time. Filters fitted
to force ventilating blowers need to be inspected and, if necessary, cleaned or
replaced depending on the type.
If the machine is to be shut down in freezing conditions any water circuits should
be drained. Condensation forms and accumulates in the air/water heat exchanger
and could be drawn into the machine through the air passages and enter the windings. When a machine is to be shut down for any time, the cooling water flow should
also be stopped to limit the build-up of condensation. Even under normal operation this condensation can be significant and justify raising the water temperature
in the cooler and reducing the ambient humidity to reduce the quantity of condensation formed.
Windings and insulation
A machine which has been out of service for a long period could have too low an
insulation resistance to allow it to return to operation. If the resistance is less than
1 MW on an l.v. machine, or equivalent value on h.v. machines, the windings need to
be dried out. The machine can be placed in an oven or dried using a hot air blower.
In either case the temperature should not exceed 90°C or damage could result to
rotating diodes for example. Initially, the insulation resistance will fall and then
slowly increase to a maximum level. The resistance readings should be monitored
as the drying out process proceeds and, to avoid misleading readings, the temperature should be kept as constant as possible.
Before taking any insulation resistance measurements, any diodes or capacitors
should be disconnected or short-circuited. High-voltage insulation breakdown tests
should be avoided as they have a progressive effect in causing deterioration of the
winding insulation.
CHAPTER 16
HBC Fuses and Fusegear in
Low Voltage Systems
J. Feenan, MBE, CEng, FIMechE
(Electrical Consultant and formerly Technical Director, Fusegear
Division, GEC Installation Equipment Ltd)
Revised by P.G. Newbery, BSc, CEng, MIEE
(Technical Director, Cooper Bussmann, Cooper (UK) Ltd)
A major change in the UK Wiring Regulations occurred in 1981 with the introduction of the 15th edition of the IEE Wiring Regulations. These regulations differed
considerably from the 14th and previous editions in that they were aligned with
the wiring regulations of the International Electrotechnical Commission (IEC)
which were more specific on many aspects of electrical protection, including overcurrent protection and protection against electric shock.
The 16th edition of the IEE Wiring Regulations, which contained amendments
arising from further agreements reached in CENELEC, was introduced in 1991 and
this in turn was accepted by BSI as BS 7671 Regulations for electrical installations
in 1992.
When the first set of Wiring Regulations was issued in 1882 by the Society of
Telegraph Engineers and Electricians, mention was made of the fuse as an ideal
device for ‘the protection of wires’. Over a century later the fuse, in the form of the
hbc fuse, is still a major protective device. In fact, BS 7671 gives precise regulations
regarding overcurrent protection in which the l.v. hbc fuse emerges as a unique
device for fault current protection as well as providing the necessary overload protection to PVC insulated cables which are acknowledged to be the most difficult to
protect under overload conditions.
The design of the hbc fuse has progressed during the last 60 years until it has
become a highly sophisticated protective device with very precise characteristics.
The British and International Standards covering l.v. fuses have also progressed
during these years and in June 1981 agreement was finally reached in the committee of the International Electrotechnical Commission dealing with l.v. fuses
(SC32B), for one set of time-current ‘gates’ within which the time-current characteristics of all fuses for general purpose applications must fall. This decision was the
culmination of many years of intense activity in IEC and it is significant to note that
the time/current characteristics of the modern British hbc fuse-link fall within these
agreed ‘gates’, thus indicating that British practice with regard to hbc fuse-link
design has been the correct one. It is therefore an opportune time to consider the
427
428
Handbook of Electrical Installation Practice
Fig. 16.1 Component part of a fuse.
modern hbc fuse from the viewpoints of design and performance, application in
general purpose circuits and in motor circuits, and its effect on the design of associated fuse switchgear and motor starter combinations.
HBC FUSELINKS DESIGN AND PERFORMANCE
The performance requirements of hbc fuse-links, for voltages up to 1000 V a.c. or
1500 V d.c., are covered by BS 88, Low voltage fuses. BS 88 defines a fuse as consisting of a fuse-link and fuse-holder. The fuse-holder consists of a fuse-base and in
most cases a fuse-carrier. A diagrammatic representation of a typical fuse is shown
in Fig. 16.1. It also defines types of fuse-links including type gG for general purpose
applications, and type aM as an alternative for motor circuit applications.
These symbols signify the breaking range and utilisation category of the fuses.
The symbol ‘g’ represents full range breaking capacity. A gG fuse-link is one with
a full range breaking capacity for general application, a gM fuse-link is one with a
full range breaking capacity for the protection of motor circuits. BS 88 also refers
to types of fuses used in other countries, example aM, since BS 88 is aligned to
CENELEC (EN) and International (IEC) Standards.
The specification gives detailed requirements for each type, which are
summarised below.
Type gG fuses
The minimum performance requirements which must be met by gG hbc fuses,
complying with BS 88: Part 2, sections 2.1 and 2.2 are:
(1) A breaking capacity of not less than 80 kA at 415 V a.c. 0.2 pf. Fuses to this
standard can successfully interrupt any fault current from the minimum fusing
current of the fuse up to the rated breaking capacity at the specified power
factor.
HBC Fuses and Fusegear in Low Voltage Systems
429
(2) The temperature rise of the fuse when carrying rated current must not exceed
70°C at the fuse terminals. (Lower values are specified if the terminal is not
silver plated.) In addition, maximum permitted power losses are specified for
each fuse-link size and these are such that for the majority of fuse ratings the
terminal temperature rises attained are very much less than the permitted
maximum.
(3) The ability to protect PVC-insulated cables from damage due to overload currents. The specification determines this by requiring a general purpose fuse-link
(type gG), to have a fusing current not exceeding 160% of rated current (In)
and a non-fusing current (Inf) not less than the 125% In. It must also comply
with the requirements specified in the conventional cable overload protection
test. Fuse-links meeting these requirements are deemed to provide overload
protection to PVC insulated cables when the rated current of the fuse is equal
to or less than the continuous rating of the cable for a given installation
condition.
It should be noted that the reference to fusing factor, contained in all previous
editions of BS 88, has now disappeared and is no longer applicable.
(4) The time–current characteristics of a fuse must fall within the specified time
current zones given in the Standard. Here again, it should be noted that BS 88:
Part 2, section 2.2 contains much narrower time–current zones than the previous edition of BS 88: Part 2, and these zones fall within the time–current gates
specified in BS 88: Part 1 for all general purpose fuses.
Figure 16.2 illustrates the test requirements of BS 88 and it can be seen that for
verification of breaking capacity, the gG fuse-links are submitted to five test currents, I1, I2, I3, I4 and I5, covering a range of prospective currents from a breaking
capacity of 80 kA down to a current equal to 1.25If (If is equal to 1.6In)
Type gM fuse-links
As these fuse-links are for the protection of motor circuits, they cannot in that role
provide overload protection to the associated cables, which are usually rated on the
basis of the full load current of the motor. Nevertheless the same tests for breaking
capacity and compliance with the time–current zones, as that specified for gG fuselinks, are applicable to gM fuse-links. This ensures that the fuse-links will interrupt
any current from rated breaking capacity down to minimum fusing current safely,
and allows great flexibility of co-ordination with the associated overload devices.
Type aM fuse-links
These fuse-links by their designation ‘a’ are a back-up type, having a partial range
breaking capacity and have a minimum breaking current approximately equal to
6.3In. The In of the aM fuse-link is not related to the rated current of the fuse, but
signifies the rated current of the motor which it can protect. They do not provide
overload protection and must be co-ordinated with a suitable device which, while
430
Handbook of Electrical Installation Practice
Fig. 16.2 BS 88: 1988, principal test requirements.
providing overload protection, ensures that this fuse is not subjected to low overcurrents below its minimum breaking current.
Tests
The principal requirements are shown in Fig. 16.2. Proof of compliance with parts
(1) and (2) of this figure necessitates testing at a high power test laboratory in closely
controlled test conditions required by BS 88.
The high power laboratory is accredited by ASTA Certification Services, and an
ASTA certificate of rating can be issued as proof of compliance with the breaking
capacity clauses of the standard. Test conditions for breaking capacity are as
HBC Fuses and Fusegear in Low Voltage Systems
431
indicated in Fig. 16.2, arranged to ensure that the fuse interrupts all possible combinations of voltage, current and inductance which would occur in practice on
systems having fault levels up to the breaking capacity of the fuse.
A requirement concerns verification of the pre-arcing I 2t limits of the fuse at
a time of 10 ms. This is to ensure that the fuse will meet a discrimination ratio of
1.6 : 1, which is now also required by the revised standard.
The discrimination ratio of 1.6 : 1, which is based on comparison of pre-arcing I 2t
values at 10 ms, has been included in the standard at the request of the IEC Wiring
Regulations Committee, in order to ensure that with fuse-protected systems, an
improved degree of discrimination can be provided.
BS 88 includes additional verification tests which are related to safety. These are:
•
•
•
•
•
Protection against electric shock
Resistance to heat
Mechanical strength
Resistance to corrosion
Resistance to abnormal heat and fire.
It also includes, with respect to fuse-holders, verification of non-deterioration of
contacts.
These additional safety tests reflect the growing demands by inspection and test
authorities in many countries, that any performance claims in a specification must
have a test requirement which is deemed to verify that claim.
DESIGN OF CARTRIDGE FUSE-LINKS
Although the fuse-link complying with BS 88 has a similar outward appearance to
a fuse-link complying with earlier editions of the British Standard, changes in
element design and element configurations within the fuse-link have achieved significant improvements in breaking capacity and time–current characteristics within
existing dimensions.
The modern cartridge fuse-link consists of a ceramic body, one or more fuse elements depending on the current rating, an inert arc quenching filler such as granulated quartz, tin-plated copper or brass endcaps and, usually, tin-plated copper tag
terminations, A typical fuse-link is shown in Fig. 16.3. The fuse elements used in
modern l.v. fuse-links are made from tape or strip. Different fuse manufacturers
have different ideas on the precise form of the element but all of them employ a
number of reduced sections along the length of the element in order to promote
multiple arcing under short-circuit conditions (i.e. creating a number of arcs in series
which burn simultaneously).
When arcing commences in a modern hbc fuse-link, a high transient pressure is
set up within the fuse body due to the vaporisation of parts of the element which
can only expand to a limited extent in the interstices in the quartz filler. This high
pressure, combined with the high temperature generated in the arc column, necessitates the use of special ceramic material for the body. The joints between endcaps
and body must also be strong enough to withstand the stresses created. Granulated
432
Handbook of Electrical Installation Practice
(
)
Fig. 16.3 Sectioned view of typical hbc fuse-link.
quartz is chosen as the filler because it is inert and has excellent heat-absorbing
properties which make it an ideal arc quenching medium. Its purity and grain size
are also very important factors in obtaining a high breaking capacity. The design of
the fuse element controls both the mode of operation on short-circuit and the shape
of the time–current characteristics of the fuse.
The number and lengths of the reduced sections of the element govern the arc
voltage of the fuse. Arc voltage is the voltage which appears across the terminals
of the fuse during the arcing time of the fuse-link and it is the result of four
components:
(1) The voltage dropped across the arcs in series
(2) The resistive voltage drop of the rest of the circuit due to the passage of a large
fault current
(3) The circuit e.m.f.
(4) The inductive voltage, L(di/dt), produced in the circuit due to the dissipation of
its inductive energy (1/2Li2) within the fuse arcs.
Components (1) and (2) tend to reduce the current while (3) and (4) try to maintain its flow. The generation of an adequate arc voltage ensures that current ceases
to rise after the commencement of arcing and the subsequent variation in arc
voltage controls the rate at which the current reduces to zero.
HBC Fuses and Fusegear in Low Voltage Systems
433
Fig. 16.4 Fuse-element manufactured from silver strip.
A major factor affecting the arc voltage is the grain size of the quartz filler because
this in turn can affect the pressure generated within the fuse body when the element
vaporises during the arcing period. An arc burning under pressure requires a higher
voltage to maintain it than an arc in free air. It is therefore possible to design a fuselink which will produce a predetermined maximum value of arc voltage. BS 88
stipulates an upper limit of 2.5 kV for the arc voltage produced by fuse-links rated
up to 690 V but in a good design this value is never reached. The range of fuse-links
using the type of element illustrated in Fig. 16.4 produces arc voltages in the region
of 1 kV.
An indication of the speed of operation and current limiting ability of the hbc
fuse is given in the oscillogram shown in Fig. 16.5. This is the record of a 400 A fuse
interrupting a prospective current of 80 kA r.m.s. symmetrical at 415 V a.c. with a
lagging power factor of 0.15. BS 88 specifies that the fault shall be initiated such
that arcing commences in the fuse at approximately 65° after voltage zero. This produces an asymmetrical fault current with a peak prospective value of 180 kA.
The limitation of thermal and electromagnetic stresses achieved by the fuse is
better appreciated when it is remembered that both vary as the square of the
current. An examination of the oscillogram serves to illustrate this point.
The peak or cut-off current permitted to flow by the 400 A fuse is 40 kA, i.e. 22%
of the possible peak current. The electromagnetic force produced is therefore only
about 5% of that which would otherwise have occurred. Similarly the thermal stress
has been reduced to less than 1% of that which would have occurred if a circuitbreaker having a speed of operation of 0.02 s had been the protective device. The
combination of current limitation and rapid operation enables this high degree of
434
Handbook of Electrical Installation Practice
Fig. 16.5 Oscillogram of the operation of a 400 A 415 V fuse on a large fall circuit. Key:
(A) Asymmetrical peak value of prospective current, 182.5 kA ∫ 81.1kA r.m.s.
sym; (B) cut-off current, 39.5 kA; (C) pre-arcing time, 1.6 ms; (D) arcing time,
3.4 ms; (E) arc voltage, 930 V; (F) recovery voltage, 461 V r.m.s.
protection to be obtained. Figure 16.6 shows the cut-off currents of a range of fuses,
having current ratings from 2 A to 800 A on a prospective current of 80 kA. This
illustrates the reduction in electromagnetic stresses which can be achieved with hbc
fuses.
On high short-circuit currents the energy required to melt a fuse is a minimum
and constant value because there is no time for heat to be dissipated from it to its
surroundings. The magnitude of this energy, known as the pre-arcing energy of the
fuse, can be determined from the oscillograms of fuse operations on high shortcircuit currents. Similarly the arc energy, which is the energy liberated in the fuse
during its arcing time, can also be determined.
Unlike the pre-arcing energy, however, the arc energy can vary between wide
limits depending on the circuit conditions, but the maximum value is obtained
during the breaking capacity tests to BS 88. In effect the arc energy of a fuse is the
energy stored in the circuit at the commencement of arcing, which must be dissipated in the fuse before the circuit is finally opened. It must, however, be appreciated that the energy dissipated in the fuse is a function of I 2t ¥ RF where RF is the
resistance of the fuse during its pre-arcing and arcing periods.
When considering the short-circuit protection the fuse provides to equipment and
cables in the circuit, the information of interest is the cut-off current and the I 2t
value (A2s). The cut-off current, as stated earlier, is a direct indication of the limitation of electromagnetic stresses achieved by the fuse. The thermal stresses in the
circuit can be expressed in terms of I 2t because this is the common factor between
HBC Fuses and Fusegear in Low Voltage Systems
435
Fig. 16.6 Relationship between prospective current and cut-off current for a range of fuses.
the fuse and other components in the circuit. Obviously in a cable the energy is a
function of I 2t ¥ RC where RC is the resistance of the cable.
It is common practice, however, for manufacturers and designers of associated
apparatus such as fuse-switches, contactors, busbars and cables to express the short
time thermal ratings of the equipment in terms of I 2t. This enables the manufacturers of such equipment to state in a simple manner the degree of thermal protection required by various items of equipment under short-circuit conditions.
A fuse manufacturer can determine the I 2t of a fuse on large short-circuit currents
from the relevant oscillograms and usually presents the minimum pre-arcing I 2t (i.e.
the I 2t from the commencement of the fault until the arcing commences) and the
maximum arcing I 2t (from commencement of arcing until circuit interruption) under
worst fault conditions in the manner shown in Fig. 16.7. This shows the pre-arcing
and total (pre-arcing plus arcing) I 2t values for a range of fuses from 2 A up to
800 A under short-circuit conditions on prospective currents up to 80 kA. Figures
16.6 and 16.7 represent a comprehensive picture of the short-circuit protection provided by this range of fuse-links.
436
Handbook of Electrical Installation Practice
Fig. 16.7 Traditional ‘Bull-Rush’ I 2t characteristics for a range of fuses showing pre-arcing
and total values. (Another approach is to tabulate values for ease of data
transfer.)
OVERLOAD CHARACTERISTICS
The method of achieving compliance with the conventional fusing current mentioned earlier has traditionally been achieved by including an overload zone in the
element. This is done by adding a precise amount of low melting point metal (tin)
to the element, which was traditionally silver. Under overload conditions the temperature of the fuse element gradually increases until a temperature is reached at
which the tin becomes molten and a metallurgical phenomenon, commonly known
as ‘M’ effect, takes place. A eutectic alloy is formed at this temperature between the
tin (melting temperature 230°C) and silver (melting temperature 960°C) and
the alloy thus formed has the same melting temperature as that of tin (230°C). This
ensures that the element will melt in the overload zone at the desired current of
1.6IN without excessive temperatures being reached.All modern designs of cartridge
fuse utilise this ‘M’ effect in one form or another.
HBC Fuses and Fusegear in Low Voltage Systems
437
Fig. 16.8 Silverbond element, showing that the ‘M’ effect zone is placed at a full section.
Today fuse elements generally use copper as a more economic material and have
been developed employing modern design techniques. These copper elements also
use the ‘M’ effect principle. An early design, bridging the transition from silver to
copper, is shown in Fig. 16.8.
FUSE-HOLDER
The fuse-holder (i.e. the fuse-carrier and base) also plays an important part in the
design of a cool running fuse. Robust contacts ensure a low temperature rise by
helping to dissipate the heat from the fuse-link when carrying rated current. The
method chosen for connecting the cable to the fuse terminals must be carefully considered to avoid the danger of a bad connection which could nullify an otherwise
satisfactory design. Most of the front-connected fuse-holders to BS 88 employ
tunnel-type terminals which are ideally suited for the connection of unprepared
stranded copper conductors. This form of terminal is, however, not normally suitable for the direct connection of aluminium conductors. When aluminium conductors are used, it is preferable to terminate the conductor with a suitable cable lug
and utilise a back-connected fuse-holder which provides a stud connection suitable
for connecting the cable lug. High quality moulding materials are widely used in
modern designs of fuse-carriers and bases which permit compact dimensions and
extensive shrouding of current-carrying parts. These features are highlighted in
Fig. 16.9, which illustrates a widely used design of fuse-holder.
APPLICATION OF HBC FUSES
BS 7671 clearly states the requirements which must be met when providing cables
with both overload protection and short-circuit protection. These two terms are
438
Handbook of Electrical Installation Practice
Fig. 16.9 Sectioned fuse-holder showing how extensive shrouding of live parts is achieved.
covered by a more general term, overcurrent protection. With regard to protection
against overload, the Wiring Regulations state that the protective device must
operate within a stated conventional time when carrying a current equal to 1.45IZ
(the current rating of the associated cable).
Type gG fuses to BS 88 provide the necessary degree of protection and both BS
7671 and the International Wiring Regulations recognise this fact. If the current
rating of a gG fuse to BS 88 is not greater than IZ, the rating of the associated
cable, compliance with the requirements of BS 7671 for overload protection of
cables, is achieved. This rule confirms a practice which has existed in the UK for
many years and it is interesting to note that this practice is now internationally
accepted.
With regard to the protection of cables against short-circuit (the other form of
overcurrent), the hbc fuse is indisputably the best device for the purposes, particularly if the fuse has a current rating not exceeding that of the cable. Even when the
fuse has a greater rating than the cable, it gives adequate short-circuit protection.
The limiting parameter specified in BS 7671 with regard to the maximum size of
fuse which can give short-circuit protection to a cable, depends on the minimum
value of the short-circuit current which can occur (Fig. 16.10).
In BS 7671 protection must be provided for cables for short-circuits of durations
up to 5 s and Regulation 434–03–03 gives an adiabatic formula t = k2S2/I 2 (where S
is the cross-sectional area of the conductor and k is a constant for each type of
cable), which can be used to calculate the I2t withstand capability of various types
of cables at 5 s. It is therefore a relatively simple job to determine from the published information the maximum size of cable which can be protected by a given
size of fuse on a short-circuit current of 5 s duration.
Table 16.1 shows, by utilising the formula mentioned above, the appropriate
maximum size of cable which can be protected against short-circuit in a motor
circuit for both open and enclosed installation conditions. It can be seen that the
old rule of twice the cable rating still applies in the majority of cases. An important
point to appreciate is that if a fuse protects a cable under short-circuit conditions
at 5 s, it will, because of its unique current limiting ability, protect that cable on all
HBC Fuses and Fusegear in Low Voltage Systems
439
Fig. 16.10 Short-circuit protection of 10 mm2 PVC-insulated cable by hbc fuses.
Table 16.1 Short circuit protection of PVC-insulated cables in motor circuits.
Application of Regulation 434–03–03 of BS 7671.
fault currents in excess of the 5 s value up to the breaking capacity rating of the
fuse-link. This cannot be assumed for other types of protective devices such as
circuit-breakers of the non-current limiting type where it is necessary to check
whether protection is afforded at the maximum prospective fault current likely
440
Handbook of Electrical Installation Practice
Fig. 16.11 Comparison of protection provided to PVC-insulated cable by hbc fuses and
circuit-breakers.
to occur at that point in the circuit (Fig. 16.11). This illustrates how effectively
the modern hbc fuse can provide overload and short-circuit protection in
accordance with BS 7671 without sacrificing any of its ability to permit maximum
utilisation of the other components of the circuit it is protecting, e.g. cable, motor
starter, etc.
DISCRIMINATION AND CO-ORDINATION
In any well-planned electrical system, discrimination between overcurrent protective devices throughout the system is essential. Regulation 533–01–06 of BS 7671
states this as a requirement for compliance, to avoid danger, and Regulation
314–01–02 draws attention to the need to consider the consequencies likely to be
caused.
Discrimination
Discrimination between any two devices in series is achieved when on the occurrence of a fault in the circuit protected by the minor device, only that device operates leaving the major device intact. Where hbc fuses are used as the protective
device throughout the system, the degree of discrimination which can be achieved
is unequalled by any other form of protective device.
To achieve discrimination on the worst fault conditions, i.e. on high prospective
fault currents, it must be ensured that the pre-arcing I2t of the major fuse is in excess
of the total I2t of the minor fuse. The discrimination ratio of 1.6 : 1, mentioned earlier,
HBC Fuses and Fusegear in Low Voltage Systems
441
is based on comparison of pre-arcing I2t at 10 ms. The assumption made is that in
practice, particularly on final circuits, the fault conditions are such that the arcing
I2t can be ignored. While this may well be true for such circuits, which are usually
single-phase circuits where the prospective current is not very high, it is not a reasonable assumption for industrial applications, where high fault levels and lowpower factors occur on three-phase systems. It is, however, agreed that the breaking
capacity test conditions specified in BS 88 are unlikely to occur in practice. Thus the
arcing I2t values obtained on such tests, indicated in Fig. 16.7, are unlikely to occur,
even under worst practical fault conditions, on 415 V a.c. three-phase systems. Tests
on such circuits have established that a 1.6 : 1 ratio can be achieved with the modern
design of fuse to BS 88: Part 2.
Co-ordination
In the modern electrical installation, there are a number of devices such as miniature circuit breakers (mcb) and contactors which although they are overcurrent protective devices, have a limited breaking capacity. In situations where the fault levels
exceed their breaking capacity, it is necessary to provide back-up protection which
will take over from the mcb or contactor on a fault current not exceeding its breaking capacity.
Such a back-up device must not only protect the circuit, but ideally it should not
allow the mcb or contactor to be damaged by letting too much energy flow through
them.This energy is related to the let-through I2t of the device, and the unique ability
of the hbc fuse under fault conditions to keep the let-through I2t to very low values,
explains why it is the most effective means of back-up protection for these devices.
When selecting the fuse as a back-up device in a motor circuit, further objectives
must be achieved. In addition to the ability to interrupt the fault current successfully and protect the associated contactor and cable under short-circuit fault conditions, it must be capable of withstanding the motor starting current for the starting
period. The generally accepted method of determining the capability of a fuse to
withstand motor starting conditions is to refer to the 10 s withstand current. Usually
it is assumed that the starting current is approximately six times the motor full load,
and that such a current would exist for up to 10 s.
One further aspect of correct protection of motor circuits has received considerable attention in recent times. This concerns the degree of co-ordination required
between the back-up protective device and the starter. The standard covering motor
starters is BS EN 60947–4–1, Low voltage switchgear and controlgear. Part 4–1: Contactors and motor-starters – Electromechanical contactors and motor-starters. This
permits two types of co-ordination, type ‘1’ and type ‘2’:
Type ‘1’ co-ordination requires that, under short-circuit conditions, the contactor or
starter shall cause no danger to persons or installation and may not be suitable for
further service without repair and replacement of parts.
Type ‘2’ co-ordination requires that, under short-circuit conditions, the contactor or
starter shall cause no danger to persons or installation and shall be suitable for
442
Handbook of Electrical Installation Practice
further use. The risk of contact welding is recognised, in which case the manufacturer shall indicate the measures to be taken as regards the maintenance of the
equipment.
Type ‘2’ ensures no damage to the starter, particularly with respect to the characteristics of the overload relay. If, as is normal, the cable from the starter to the motor
is chosen on the basis of the full load current of the motor, then the back-up device is
only providing short-circuit protection to that cable.The overload relay of the starter
is providing the desired overload protection to the cable as well as to the motor.
Thus in order to comply with the requirements of BS 7671 in such an installation,
type ‘2’ co-ordination is necessary.
Tests have shown that the hbc fuse to BC 88 provides the most economic method
of achieving this degree of protection. The modern motor starter is a very compact
device and even when hbc fuses are used it is necessary to refer to the manufacturer of the starter to ensure that the correct fuse is chosen.
Tests have shown that the hbc fuse plays a unique role in achieving type ‘2’
co-ordination. Further information is given in an IEC Technical Report IEC 1459,
Low-voltage fuses – Co-ordination between fuses and contactors/motor-starters –
Application Guide.
Type gM motor circuit fuse-links
This type of fuse-link provides the necessary degree of back-up protection for motor
circuits, but in a smaller physical package than that of the equivalent current rating
of standard fuse-link. Its inclusion in BS 88 recognises the fact that, when a fuse is
used as back-up protection to another protective device (motor starter), the same
degree of short-circuit protection is provided by either a standard fuse-link or the
physically smaller motor circuit fuse-link of the appropriate current rating. For
example, the 32M63 fuse-link in the A2 dimensions to BS 88 provides the same
back-up protection as the 63 A fuse-link in the larger A3 dimensions for the same
voltage rating and breaking capacity.
The dual rating or the gM fuse-link is characterised by two current values. The
first value In denotes both the rated current of the fuse-link and the rated current
of the fuse-holder. The second value Ich denotes the time–current characteristic of
the fuse-link. Therefore the 32M63 A fuse-link has a continuous rating of 32 A
because of the limitation of the fuse-holder or fuse-switch in which it is installed,
and has the same time–current characteristics as that of the standard 63 A fuse-link.
This type of fuse-link permits full utilisation of the make–break capabilities of the
modern fuse switch; for example, a 200 A fuse-switch with a 200M315 fuse-link fitted
can be used on a motor circuit having a load current up to approximately 200 A,
whereas with a standard 200 A fuse-link fitted it would be limited to a circuit of
125 A, because of the reduced motor starting capability of the 200 A fuse-link. As
will be discussed later, the make–break performance of the 200 A fuse-switch is such
that it can safely break the stalled motor current of a motor, having a 200 A full load
current. Thus, the motor circuit fuse-link has been an important contribution to the
achievement of the compact dimensions of a modern fuse-switch.
It is important to note that the motor circuit fuse-link type gM is a generalpurpose type and is tested to the same breaking capacity requirements as that of
HBC Fuses and Fusegear in Low Voltage Systems
443
the gG type. The reduction in equipment dimensions which can be achieved by using
motor circuit fuse-links is appreciable and has now been internationally recognised.
Type aM motor circuit fuse-links
This type of fuse-link, which is of continental European origin, has considerably different characteristics from those of the standardised time–current zones, and as
stated earlier, the current rating assigned to such a fuse-link is related to the full
load current of the motor it is designed to protect rather than to the fuse-link itself.
Because the minimum breaking current is a significant multiple of current rating, it
is essential where such fuse-links are used, that its characteristics are co-ordinated
with an overload device which will ensure that both the circuit and the aM fuse-link
are protected against overload conditions. This fuse-link cannot safely interrupt
overcurrents below its specified minimum breaking current.
FUSES IN HIGH AMBIENT TEMPERATURES
A fuse can carry its rated current continuously in ambient temperatures up to 35°C
but if it is required to carry its rated current at higher ambient temperatures or in
enclosures where the inside air temperature is more than 15°C in excess of this
value, it is necessary to apply a derating factor, and most manufacturers give such
information in their publications. If, however, a fuse is providing back-up protection
in a motor circuit employing direct-on-line starting, derating is not usually required at these higher temperatures because in such an application the fuse is only
carrying approximately 50% of its rated current, producing only 25% of the
temperature-rise normally achieved at rated current. Therefore unless the local air
temperature is excessively high (above 60°C) there is no need to derate in such
motor circuit applications.
PROTECTION AGAINST ELECTRIC SHOCK
The biggest difference between the 15th and earlier editions of the IEE Wiring Regulations and BS 7671 concerns the rules which are included in BS 7671 regarding
protection against electric shock. As fuses figure significantly in certain measures of
protection, it is opportune to comment on those aspects of BS 7671 where fuses can
be used to good effect in achieving protection against electric shock. The most
popular measure of protection against indirect contact (contact with exposed
conductive parts made live by a fault) is ‘earthed equipotential bonding and automatic disconnection of supply’. The Regulations in BS 7671, notably Regulations
413–02–02 and a number of Regulations in section 547, give details regarding the
steps to be taken to achieve the necessary earthed equipotential bonding which is
the first part of the requirement.The second part, automatic disconnection of supply,
is covered by Regulations 413–02–04 to 413–02–28, specifying the requirements for
final circuits supplying socket outlets and for final circuits supplying only fixed
equipment.
444
Handbook of Electrical Installation Practice
Table 16.2 Gates for ‘gG’ and ‘gM’ fuses, extract from Table III of BS 88:
Part 1. Limits of pre-arcing time of fuse-links.
Regulations 413–02–10 and 413–02–14 give specific rules for the protection of circuits having a nominal voltage to earth, Uo, of 230 V r.m.s. a.c. when protection is
provided by means of a fuse. They state that in order to comply with the requirements for electric shock the earth fault loop impedance Zs shall not exceed values
given in Table 41B1 for final circuits supplying socket outlets, where the disconnecting time of the protective device under fault conditions must not exceed 0.4 s,
and Table 41D for final circuits supplying fixed equipment, where the appropriate
disconnection time shall not exceed 5 s. Among the devices mentioned in the tables
are cartridge fuses to BS 88: Parts 2 and 6, BS 1361 and BS 1362. The earth fault
loop impedances given against each rating of fuse in each table have been determined from the time–current characteristics of these fuses, and Appendix 3 of the
Regulations shows the upper limit of the time–current zone for appropriate ratings
of fuse-link and the use of Uoc in the calculations.
It follows from these disconnecting time requirements and those mentioned
earlier for short-circuit protection, that the current to cause operation of the fuse
in 5 s is now of great importance and BS 88: 1988: Part 1 includes maximum values
for the 5 s operating current for all rated currents of general purpose fuses. Furthermore, in order to provide information on currents causing the fuses to operate in 0.4 s, the time–current characteristics must also comply with minimum and
maximum values of current at 0.1 s.
Typical requirements are shown in Table 16.2, and Fig. 16.12 illustrates the
time–current ‘gates’ which are included in BS 88: Part 2.
Another important requirement of BS 7671 is the need for electrical installations
to have an overall voltage drop not exceeding 4% of the system voltage under normal
service conditions – see Regulation 525–01–02. It has been established during consideration of this particular problem, that in the vast majority of cases compliance
with the 4% overall voltage drop limit automatically ensures, in a TN system (an
earthed neutral system), compliance with the values of Zs given in the appropriate
tables. In fact it can be shown that where a fuse is giving complete overcurrent
protection to a circuit supplying fixed equipment installed in accordance with the
requirements of BS 7671, the disconnecting time in the event of a negligible fault
to earth is considerably less than 5 s and in the vast majority of applications less than
HBC Fuses and Fusegear in Low Voltage Systems
445
Fig. 16.12 Time–current gates in BS 88: Part 1.
1 s. It can also be seen from the values of earth loop impedance given in Table 41B1
(of the Regulations) that in TN systems the hbc fuse is suitable for the protection of
all socket-outlet circuits except socket outlets supplying equipment outside the
equipotential bonding zone. Here the Regulations make the fitting of a residual
current device of 30 mA sensitivity a mandatory requirement and forbid the use of
an overcurrent protective device for protection against electric shock for these particular socket outlets. It can still provide overcurrent protection to this circuit and
back-up protection to the rcd.
In addition to the foregoing, the energy-limiting ability of the hbc fuse can be
used to good effect in achieving economies in the size of the circuit protective conductor. Regulation 543–01–01 states two methods of selecting the size of this conductor. The first method is by calculation of the cross-sectional area using an
adiabatic equation S = ÷(I 2t/k2) which is applicable for disconnecting times not
exceeding 5 s, and the second method relates the cross-sectional area of the circuit
protective conductor to the associated phase conductor, the details of which are
given in Table 54G of Regulation 543–01–04.
If the adiabatic equation is used, which takes into account the I2t let-through by
the fuse, a much smaller size of protective conductor can be used, particularly when
446
Handbook of Electrical Installation Practice
account is taken of the foregoing statement that in the vast majority of applications
the fuse disconnects in times less than 1 s. The other important point is that, if protection is afforded to the protective conductor by a fuse under these conditions, it
is assured on higher fault currents.
Even in motor circuits where the fuse is providing back-up protection and is
therefore usually about twice the rating of the phase conductor, it can be shown that
the use of the adiabatic formula results in smaller sizes of protective conductor than
those specified in Table 54G.
One of the difficulties is applying the adiabatic formula is that it requires a knowledge of Ze which is the value of earth loop impedance external to the installation.
Where this value is known it is a simple matter to use the adiabatic formula. In those
situations where the precise value of Ze is not known, it can be shown that even
where the value of Ze is as high as 50% of Zs, appreciable economies can be gained
by using the adiabatic formula.
The foregoing confirms that on fuse-protected installations on TN systems, existing practice usually achieves compliance with the requirements for protection
against electric shock by equipotential bonding and automatic disconnection of
supply. This is applicable for fixed circuits, where the fuse is either giving complete
overcurrent protection to a circuit or back-up protection to motor circuits, and also
to circuits feeding socket oulets, except those socket outlets feeding equipment
outside the equipotential bonded zone.
DOMESTIC FUSE APPLICATIONS
The fuse-links used in domestic installations are those complying with BS 1361 and
BS 1362. Their characteristics are included in BS 7671 together with those of semienclosed fuses to BS 3036.
Fuse-links to BS 1362 for use in the 13 A plug are well established and widely
used both in the UK and overseas, and the type II fuse-links of BS 1361 are the
standard house service cut-out fuse-links used by the Electricity Association (EA).
The BS 1361 fuse-link type I range (5 A to 45 A), provides a non-interchangeable
range of fuse-links for use in domestic consumer units. They were initially launched
in 1947 but due to lack of availability of replacement fuse-links, and the lack of effort
in educating the general public, who had previously only been used to semi-enclosed
fuses, the system was abused and the anticipated growth of this type of consumer
unit was never achieved. It is interesting to note, however, that the fuse-links to BS
1361 which are used in domestic consumer units, have a breaking capacity of
16.5 kA which is the maximum fault level specified for domestic installations in the
UK and discriminates with the 100 A house service cut-out fuse.
Furthermore, the BS 1362 fuse-link which is fitted in the BS 1363 plug is apparently used without any noticeable abuse, because the general public is now well
educated in the use of cartridge fuse-links. The requirements of BS 7671 may well
see an increase in the use of domestic consumer units incorporating cartridge
fuse-links.
With the introduction of BS 7671, which required the determination of the fault
level at the terminals of an installation, the EA declared that the fault level at the
HBC Fuses and Fusegear in Low Voltage Systems
447
terminals of a 240 V single-phase supply in a domestic installation, could reach 16
kA. This posed an immediate problem for consumer units containing semi-enclosed
fuse-links or mcbs, because their breaking capacities are considerably less than 16.5
kA at 240 V a.c.
Furthermore, the EA requirements at that time were that the final circuit protective devices should discriminate with the house service cut-out fuse. The impossible and impractical situation, created by the EA statement, has now been resolved
by the EA permitting co-ordination between the cut-out fuse and downstream
devices, and the modification of the time–current characteristics of the type II fuselinks of BS 1361. These two changes, coupled with an introduction of a test circuit
representing typical domestic installations into BS 5486: Part 13, Consumer units,
has solved the problem. It is now relatively easy to demonstrate that the combination of the house service cut-out fuse with its modified characteristics, with semienclosed fuses or mcbs of modest breaking capacity, can satisfy the requirements of
BS 7671 with regard to short-circuit protection.
BS 5486: Part 13 is now covered by BS 60439–3, and the tests described above
can be found in annex ZA.
The dimensions and performance characteristics of BS 1361 and BS 1362
fuse-links are included in the requirements of IEC 60269–3 and IEC 60296–3–1
covering fuse-links for domestic and similar purposes.
SEMICONDUCTOR FUSE-LINKS
BS 88: Part 4 covers semiconductor fuse-links. The basic requirements for such fuselinks (breaking capacity, etc.) are similar to those specified for industrial fuses.
Because the main attributes of semiconductor fuse-links are their very low values
of let-through I2t and cut-off current, there are additional tests which must be made
to ensure that the manufacturer’s statements regarding such information as prearcing I2t, total I2t, cut-off current, arc voltage, etc. are verified.
The application of such fuse-links requires a knowledge of the semiconductor
device and the type of circuit to be protected. Because of the precise nature of the
application, more information is provided with regard to the performance of semiconductor fuse-links than for the conventional industrial or domestic types. These
include variation of pre-arcing I2t with prospective current, variation of total I2t with
voltage and power factor and variation of arc voltage with applied voltage. This
information is required in order to optimise the capability of the semiconductor
devices.
FUSE-LINKS FOR ELECTRICITY AUTHORITY NETWORKS
BS 88: Part 5 covers the range of l.v. fuse-links used by the supply authorities. As
these fuse-links are dimensionally standardised, the specification includes these
dimensions together with standardised time–current characteristics. The breaking
capacity of these fuse-links is typically 80 kA at 415 V a.c. and the method of shortcircuit testing is similar to that for industrial fuse-links although the time–current
448
Handbook of Electrical Installation Practice
characteristics are somewhat faster at the short time end of the characteristic than
the equivalent rating of fuse-links to BS 88: Part 2. Electricity Authority Standard
EA 12-8 also contains these characteristics as well as information on the coordination achieved between these fuse-links and the h.v. fuse-links used in the
11 kV and 6.6 kV ring-main units.
A novel feature is the arrangement of the fuse tags. The fuse-links are accommodated in fuse-carriers which engage with the fixed contacts of the supply
authority feeder pillar by means of a wedge action.
COMPACT FUSES TO BS 88: PART 6
With the international agreement now reached regarding standardised fuse characteristics, an innovation which has been introduced into the UK is a range of compact
fuse-links and fuse-holders for applications up to 415 V a.c. for use in industrial and
commercial applications.
This range of fuses extends up to ratings of 63 A for applications on both 240 V
a.c. and 415 V a.c. circuits with a breaking capacity up to 80 kA. The characteristics
align with the requirements of BS 88: Part 1 and they provide an economically
attractive alternative to fuses to BS 88: Part 2 and to mcbs, for commercial and light
industrial applications.
Figure 16.13 illustrates the dimensional benefits obtained from these compact
designs.
Consideration is being given to the introduction of a larger size of fuse-link and
fuse-holder with a current rating of 125 A. This will form part of a revision to BS
88.
FUSE SWITCHGEAR
The combination of a switch and a fuse as a means of providing short-circuit protection, the switching of loads (both steady and fluctuating) and means of isolation,
dates back as far as the introduction of the fuse itself, but obviously the design of
the modern types of such combinations meets the most onerous service conditions.
The standard covering these products is BS EN 60947–3. It is therefore worth examining the relevant definitions from these documents.
•
•
Switch (mechanical) A mechanical switching device capable of making, carrying and breaking currents under normal circuit conditions which may include
specified operating overload conditions and also carrying, for a specified time,
currents under specified abnormal circuit conditions such as those of shortcircuit. It should be noted that a switch may also be capable of making but not
breaking short-circuit currents.
Disconnector A mechanical switching device which, in the open position, complies with the requirements specified for the isolating function. It should be noted
that a disconnector is capable of opening and closing a circuit when either a negligible current is broken or made, or when no significant change in the voltage
HBC Fuses and Fusegear in Low Voltage Systems
449
Fig. 16.13 Dimensional comparison of fuses to BS 88: Parts 2 and 6.
•
•
•
•
•
•
across the terminals of each of the poles of the disconnector occurs. A disconnector is also capable of carrying currents under normal circuit conditions and
carrying for a specified time currents under abnormal conditions such as those
of short-circuit.
Isolation (isolating function) Function intended to cut off the supply from all
or a discrete section of the installation by separating the installation or section
from every source of electrical energy for reasons of safety.
Switch-disconnector A switch which in the open position satisfies the isolating
requirements specified for a disconnector.
Switch-fuse A switch in which one or more poles have a fuse in series in a composite unit.
Disconnector-fuse A disconnector in which one or more poles have a fuse in
series in a composite unit.
Fuse-switch A switch it which a fuse-link or a fuse-carrier with fuse-link forms
the moving contact.
Fuse-disconnector (fuse-isolator) A disconnector in which a fuse-link or a fusecarrier with a fuse-link forms the moving contact of the disconnector.
All of the foregoing combinations of a fuse and switch or disconnector are covered
by another definiton:
450
•
Handbook of Electrical Installation Practice
Fuse-combination unit A combination of a switch, a disconnector or a switch
disconnector and one or more fuses in a composite unit made by the manufacturer or in accordance with his instructions.
A number of important points emerge from these definitions. There is a definite
distinction drawn between a device which performs the functional switching, i.e.
making and breaking the circuit, and one which provides isolation. This is highlighted in BS 7671 in which Chapter 46 deals with isolation and switching, section
476 of Chapter 47 describes the applications measures for isolation and switching,
and section 537 of Chapter 53 specifies the type of devices to be used.
Chapter 46 considers separately the functions of isolation, switching off for
mechanical maintenance, and emergency switching. Section 537 states that for isolators the isolating distance between contacts or other means of isolation when in
the open position shall not be less than those specified for isolators according to BS
EN 60947–3 and that the position of the contacts or other means of isolation shall
either be externally visible or clearly and reliably indicated. An indication of the
isolated position shall occur only when the specified isolating distance has been
attained in each pole. The same requirements are specified for devices for switching off for mechanical maintenance. It is also necessary in order to comply with the
requirements of BS 7671 that such devices be provided with means for padlocking
in the OFF position.
Section 463, Emergency switching, requires that for every part of an installation
which it may be necessary to disconnect rapidly from the supply in order to prevent
or remove a hazard, a means of emergency switching shall be provided.
Regulation 537–04–01 states that the device shall be capable of cutting off the full
load current on the relevant part of the installation. Where appropriate due account
shall be taken of stalled motor conditions.
Regulation 476–01–01 includes a statement that when more than one of these
functions, i.e. isolation, or switching off for mechanical maintenance, are to be performed by a common device, the arrangement and characteristics of the device shall
satisfy all requirements of these Regulatons for the various functions concerned.
The test requirements of BS EN 60947–3 for these products are very rigorous.
They include making on to a fault test where the switch shall be capable of making
on to prospective r.m.s. currents as high as 80 kA, the peak current and energy letthrough being limited by the fuse-link of maximum rating which can be associated
with the switch. The switch itself must be able to withstand twelve times its thermal
rating for 1 s. With regard to the overload make–break performance, there are
various categories of duty, the most onerous of which is AC23, and this requires the
switch to make and break up to ten times rated current at a power factor of 0.35
and 105% rated voltage. There is also a requirement for mechanical and electrical
endurance where the switch has successfully to withstand up to 10 000 make–break
operations with 15% of the operations being made at rated current and a power
factor of 0.65.
There are many modern combinations of fuse and switch which can readily
provide this performance up to 690 V a.c., having very compact dimensions. The full
capability of the overload make–break performance can be utilised when motor
circuit fuse-links are fitted. It can also provide all of the requirements for isolation
HBC Fuses and Fusegear in Low Voltage Systems
451
Fig. 16.14 A typical 100 A fuse combination unit.
by giving clear indication of the position of the contacts, adequate isolating distance
and a padlocking-off facility. They are therefore ideal for use either adjacent to the
equipment they are protecting or in a switchboard supplying a number of circuits.
Figure 16.14 illustrates a very popular arrangement.
THERMAL RATINGS
One of the problems which has been encountered is the fact that both the IEC and
British Standards permit the thermal rating to be determined without an enclosure.
This is known as a conventional temperature-rise test and can produce misleading
results, particularly with the larger size of fuse-switch. British practice has always
been based on thermal tests conducted using the minimum size of enclosure, and
recent amendments of the IEC Specification make it mandatory for the manufacturer of the fuse-switch to state the enclosed current rating for his product. As this
has been common practice in the UK the amendment will be welcomed by the user
as it eliminates a misunderstanding which could create overheating problems in
service. There is some safeguard in the requirements of BS EN 60439, Low-voltage
switchgear and controlgear assemblies, where it is necessary for the manufacturer to
452
Handbook of Electrical Installation Practice
ensure when designing the switchboard that no item of included equipment is subjected to a condition which could result in higher temperature rises than those specified in its relevant specification. The above-mentioned amendment requiring a
statement of the enclosed rating further emphasises the need for close attention to
this particular aspect.
The fact that such a compact relatively simple device as the modern fuse-switch
can offer such a range of protection firmly establishes its future role in the design,
installation and utilisation of electrical systems.
CHAPTER 17
Motor Control Gear
T. Fairhall, IEng, MIIE
Senior Engineer, Allenwest Electrical Ltd
Motor control gear and associated circuitry are fundamental parts of electrical distribution and utilisation systems. Motor control gear in its simplest form may be a
direct on-line starter consisting of a switching device (contactor) and tripping device
(overload relay) mounted within an appropriate enclosure.
Motor control gear has two main functions. It must make and break the connections between the motor and the supply and it must also automatically disconnect
the motor (a) in the event of excessive current being passed which would overheat
and ultimately destroy the windings, (b) if the supply fails, or (c) in combination
with its external short-circuit protective devices (fuses or circuit-breakers), in the
event of an earth fault.
In addition to the main functions described above, motor control gear may
also be required to: limit the starting current to a value consistent with the requirements of the drive; apply braking when rapid stopping is required, reverse rotation or vary speed as necessary; and carry out automatic operating cycles or
sequences.
It follows that the control gear must be appropriately selected to suit the characteristics of the motor and the drive.
Control devices for manual operation are normally pushbuttons or selector
switches, alternatively automatic control of a starter may be achieved by use of a
float switch, pressure switch, thermostat or other similar device; these are usually
covered by the generic term ‘pilot switch’ on starter diagrams.
Actuation of the contactor (switching device) may be by a number of different
methods, the most usual being electromagnetic, where the energisation of a coil and
magnetic system provides the force to close the spring-loaded contacts which switch
the motor current, although some hand-operated starters are available where finger
pressure on the start pushbutton directly closes the switching device and others were
available where the changeover from ‘start’ to ‘run’ was carried out manually. It
should be remembered that these starters could not be remotely controlled,
although in some instances the option of a remote stop was offered; also, they may
not provide no-volt protection so were unsuitable for machine-tool or machine
control applications.
In order to provide a ‘no-volt’ release function and be able to provide remote
control, an electromagnetic contactor is used in the majority of industrial
applications.
453
454
Handbook of Electrical Installation Practice
Before considering in detail the different types of motor starter available and the
criteria for choice, it is worthwhile examining the major components utilised in
motor control.
CONTACTOR
The most widespread switching device used in a starter is the a.c. air-break contactor which consists of contact assemblies actuated by electromagnetic action. An
operating coil is enclosed by the magnetic yoke, and when energised attracts an
armature to which is attached a set of moving contacts which make with a set of
stationary contacts. The rating of the contactor depends on the size, shape and material of the contacts and on the efficiency of the arc extinction method used. Modern
contactors use a silver alloy contact tip, normally silver–cadmium oxide or silver–tin
oxide alloy attached to a brass or copper backing strip. The choice of tip material
is critical, and is normally established after many type tests. The contact materials
are selected primarily for their weld and erosion resistance – the suitability of the
material chosen is then confirmed by a sequence of type tests and special tests, such
as contact life tests.
The silver alloy typically contains 10–12% cadmium oxide or tin oxide; the use of
silver–tin alloys is now the first choice at the design stage as the cadmium can require
special precautions during manufacture, and ultimately in the disposal of the
contacts.
Modern contactors use double-break main contacts, usually of butt-type design,
with either circular or rectangular contact tips. It must always be remembered that
the attachment to the backing strip requires a silver enriched backing – this means
that older maintenance techniques such as filing of contact faces actually reduce
contact service life and will eventually expose the silver backing; this may permit
contact welding.
The method of arc control is also critical in determining the performance of the
contactor; generally, smaller a.c. contactors of up to 22 kW rating do not require
complex arc chamber design – the combination of the natural current zeros of the
a.c. supply and the ‘stretching’ of the arc by the opening of the contacts gives adequate performance.
Larger sizes of contactor usually require the use of cooling devices inside the arc
chamber to assist with arc extinction. These may take the form of cooling plates or
shrouds which simply enclose the contacts, or an array of de-ion plates similar to
those in a circuit breaker. The cooling plates or de-ion plates do not need to be
selected for their electrical conducting properties; in most cases the material used
should have a relatively high melting point and mild steel can be used.
In all cases the objective is to put the arc out within typically 10–20 ms when
breaking currents of eight times the rated AC3 value under type test conditions, and
5–10 ms in normal service. The relatively fast arc extinction is a major consideration
where long service life (termed durability in British and International standards) is
a design objective; an AC3 contact life of 1–2 million operations can be achieved
with modern designs.
Motor Control Gear
455
Another choice the designer must make is that of insulating materials. These not
only act as a mounting base but as the mechanical slides and guides and also the
wall of the arc chamber within the contactor. A rule of thumb is that most moulded
components in contact with current-carrying parts will be produced from thermoset
materials, usually a polyester glass material stable up to at least 160°C, but the use
of high temperature thermoplastic materials is increasing. The use of asbestos has
now been phased out by all manufacturers with replacement materials being
adopted for the continued production of existing designs.
The contactor is magnetically held closed by maintaining the current flow through
the coil. If the voltage to the coil fails or falls below a defined level, the contactor
opens, thus disconnecting the motor from the supply. The coil must be constantly
energised in order to keep the contactor closed. Alternatively, contactors can be
fitted with a mechanical latch which does not require continuous energisation.
In order to provide quiet operation, a.c. magnets are fitted with shading rings
which normally consist of a single short-circuited loop of copper alloy. They fulfil
the basic function of providing a secondary magnetic flux to prevent the magnetic
pole faces parting and reclosing when the flux produced by the operating coil passes
through zero. If a shading ring should be omitted when reassembling some types of
contactor after maintenance, the omission will be obvious as the magnet will ‘hum’
loudly when energised. This same situation may also arise if a shading ring should
break in service, although this is unlikely as modern contactors have captive shading
rings of proven design.
A further advantage of well-designed shading rings is the reduction or elimination of magnet bounce which contributes to contact bounce during closing of the
contactor; if a contactor has severe magnet bounce, short contact life in service will
result.
The remaining design parameters such as the ability of terminals to accept cables,
service temperature rise limits, the ability to switch currents under defined conditions and the performance under short circuit conditions, are now determined by
British and International standards.
The standards applicable to low voltage motor controlgear are mandated
CENELEC publications. Compliance with these satisfies the requirements of the
Low Voltage Directive and the Electromagnetic Compatibility Directive and
permits the use of the CE mark after drawing up the appropriate Technical
Construction File and Declaration of Conformity.
These British Standards publications are essentially the English text of a comprehensive document, IEC 947, which is published in the UK as BS EN 60947 under
CENELEC rules. IEC 947 and BS EN 60947 are published in several parts which
are to be read in conjunction with Part 1, the ‘General Rules’ document. In the case
of the devices under consideration in this chapter, the applicable parts of the
document are:
IEC 947–1
IEC 947–4
BS EN 60947–1
Low Voltage Switchgear and Controlgear:
Part 1. General Rules.
1–BS EN 60947–4–1 Low Voltage Switchgear and Controlgear:
Part 4. Section 1. Electromechanical Contactors and Motor Starters
456
Handbook of Electrical Installation Practice
IEC 947–4–2 BS EN 60947–4–2
Low Voltge Switchgear and Controlgear:
Part 4. Section 2. A.C. Semiconductor Motor
Controllers and Starters
And also (for motor control centres and switchgear assemblies):
IEC 439–1
BS EN 60439–1
Low Voltage Switchgear and Controlgear
assemblies: Part 1. Specification for TypeTested and Partially Type-Tested Assemblies.
CONTACTOR SELECTION
Contactors for use in direct on-line starters are normally selected by their AC3
rating, that is the switching on of a cage type induction motor and switching off the
supply to the motor after the motor has run up to full speed. The other most
common utilisation categories are AC4, the switching on and off of a cage type
induction motor before it has run up to full speed, sometimes termed ‘inching’ or
‘jogging’ the drive, and category AC2, the switching of the stator supply to a wound
rotor motor where the starter circuit automatically inserts resistance into the rotor
circuit for each start. Figure 17.1 shows a star-delta starter.
The catalogued ratings are published on the basis of known service conditions,
typically:
•
•
•
•
•
•
•
•
Ambient temperature outside the starter enclosure between -5° and 35°C
average (with a maximum not exceeding 40°C).
Rate of operation to be specified by the manufacturer, typically 120 starts per
hour.
The duty cycle or utilisation category – see Table 17.1 for typical values of current
to be switched during type testing and in service, e.g. is the starter a reversing
type which must reverse a motor which is already run up to speed, or does the
reversing only occur after allowing the motor to come to rest? In the latter case
only AC3 rated contactors could be used.
The acceleration time of the drive, the ability of the contactor to carry the starting current, must be considered. AC3 rated contactors are able to carry eight
times rated current for a minimum of 10 s (this applies to ratings of up to 630 A;
above this the value is six times rated current).
Any special contact life requirement.
The type of short-circuit protective device to be installed in series with the supply
to the starter, and the classification of type of protection to be obtained.
Any special co-ordination requirement, e.g. are there any residual current
devices, which on detecting a fault condition may attempt to open the contactor
on a current in excess of its breaking capacity.
Any special requirement to attach cables of other than copper cored, PVC or
rubber insulated types to the contactor terminals, e.g. the use of some types of
high temperature insulation such as XLPE allows the cable to run much hotter
than the manufacture expected. The normal practice is to design for use with
400 V 50 Hz
SUPPLY
CF1
C1
L1
L2
L3
97
95
STOP
&
RESET
33
L
ISOLATOR
(IF FITTED)
96
OL
OL
98
34
1
REMOVE WIRE LINK BETWEEN
1 AND 2 WHEN CONNECTING
STOP
REMOTE PUSHBUTTONS
A
2
23
23
START
STAR AND DELTA CONTACTORS
ARE MECHANICALLY INTERLOCKED
L
S
START
Motor Control Gear
AMMETER
(IF FITTED)
24
24
3
C1
11
C3
D
65
L
12
66
L
11
L
OL
A1
U2
V2
U1
V1
TO MOTOR
C3
CF2
A2
34
A1
T
A2
12
A1
D
A2
A1
L
A2
PILOT LAMPS (IF FITTED)
457
Fig. 17.1 Wiring diagram of star-delta starter.
W1
11
S
12
S
W2
33
S
RUNNING (RED)
D
TRIPPED (AMBER)
S
458
Handbook of Electrical Installation Practice
Table 17.1 Contactor utilisation categories.
Current as multiples of operational current (Ie)
Normal operation
Utilisation category
make
break
Proving operation
make
break
AC1 Non-inductive or
slightly inductive loads
such as furnaces and
heating loads
1
1
1.5
1.5
AC2 Starting of slip
ring motors. Plugging
with rotor resistance
in circuit
2.5
2.5
4
4
AC3 Starting of cage
motors, switching of
motors during running
6
1*
10
8
AC4 Starting of cage
motors, plugging
inching
6
6
12
10
All tests carried out at supply voltage for normal operation except as indicated below and at 105%
voltage for proving operations. For full details and power factors, etc. refer to specification IEC
947/BS EN60947.
* At 17% supply voltage.
70°C cable so the possible economies of using XLPE may be not be exploited as
the core temperature may be as high as 250°C, consequently the cabling would
act as a heat source, not a heat sink.
Any of the above may need special consideration and may necessitate the selection
of a contactor of a higher AC3 rating than catalogued values would initially suggest.
Final or run contactors used in auto-transformer starters (Fig. 17.2) should be
selected using AC3 ratings; star and intermediate contactors should be selected in
accordance with catalogue recommendations.
For stator-rotor starters, the stator contactors should be selected using AC2
ratings. Rotor contactor ratings are normally specified by the contactor manufacturer as enhanced ratings based on them being in circuit only during starting.
Another important consideration when selecting contactors is to ensure that the
proposed cable conductor can be accommodated by the contactor terminals. Most
manufacturers supply this information in their catalogue together with the different types of termination that are available. A range of contactors is illustrated in
Fig. 17.3.
Motor Control Gear
Fig. 17.2 Simplified wiring diagram of stator-rotor (or rotor resistance) starter.
459
460
Handbook of Electrical Installation Practice
Fig. 17.3 Typical range of contactors covering three-phase AC3 ratings 4–400 kW.
PRODUCT STANDARDS FOR CONTACTORS
Previously, contactors were marketed as meeting IEC 158, BS 5424, or even BS 775.
The current product standard is IEC 947 published in the UK as BS EN 60947.
These standards all laid down general design and performance requirements for the
products and included various design or ‘type’ tests to verify the ability of a device
to perform the duty for which it is sold. The test currents and typical service switching currents for industrial motor control applications are summarised in Table 17.1.
An individual sample contactor must be able to complete a test sequence in order
to confirm its rating. For a contactor intended to be used in an AC3 application, the
test sequence would consist of:
•
•
•
50 operations making ten times the rated current, 25 operations to be performed
with the coil energised at 85% of rated voltage followed by 25 operations with
the coil energised at 110% rated voltage; followed by:
50 operations making and breaking eight times the rated current at 105% of rated
voltage; followed by:
6000 operations making and breaking two times the rated current, followed by a
dielectric test.
Any failure of the test item during this test sequence would mean that the complete
test sequence must be repeated on a new test sample.
The test currents, voltages, power factors and time intervals between test operations, together with the test sequence requirements for other utilisation categories,
are specified in IEC 947 or BS EN 60947 which should be consulted for full details
of test requirements.
Motor Control Gear
461
Fig. 17.4 Typical compact vacuum contactor.
Vacuum contactors
Modern power switching equipment usually includes a double-break air-break contactor. An alternative to this is the vacuum contactor, which is frequently used below
1000 V where the switching duty is arduous and is very widely specified for 3.3 kV
and above, as it is more compact than an air-break device of equivalent rating.
Figure 17.4 shows a typical unit, and it is constructed with three vacuum bottles
and a d.c. magnet on the reverse side. The construction of the bottle (Fig. 17.5) consists of a ceramic envelope with a metal top and bottom. The bottom is the fixed
contact and the top the moving contact with bellows attached. There are collector
shields for any splutter which may arise. The contact tips, shown hatched, contain
annular rings of impurity, the introduction of this impurity reducing the current chop
level. Early vacuum contactors gave a fairly high current chop level of 1–2 A. This
high current chop level generated h.v. spikes and surges, so certain impurities were
introduced into the contacts which allowed the current chop level to be brought
down to about 0.5 A. This is very important, and the reason for this in a vacuum
contactor of the hard vacuum type is that when the contacts start to part, and despite
462
Handbook of Electrical Installation Practice
Fig. 17.5 Section of vacuum contactor bottle.
the hard vacuum, an arc is formed. This arc is stretched by the operation of the
moving contact to create an envelope containing a cloud of ionised gas between the
two contacts. In due course that envelope is stretched, and through a magnetic
thermal effect conducts until such point that it snaps and the electrons are then diffused on to the cold face of the anode. Once the ionised gas path snaps, the current
flow stops very quickly without persisting until a current zero, consequently current
chopping is severe. By introducing an impurity on to the contact face when the arc
is formed, the cloud of gas is thickened by the impurity and allows the conduction
of current to carry on almost down to current zero. It is only when current zero is
approached that the arc extinguishes and a very low current chop level is attained.
This is the principle which has been used in the design of vacuum contactors for
some time now, and avoids the fitting of any form of suppression devices.
The control circuit is slightly different from the normal air-break contactor circuit,
in so much that there is a relay to drive the contactor, and the contactor is operated
through a tap-changing system. To attain the required pick-up and drop-off characteristics, the contactor is run at a lower voltage than the pick-up voltage. The
driving relay has contacts in both the input and output circuit of the bridge rectifier, to give faster drop-off characteristics, otherwise free-wheeling effects within the
circuit itself would reduce the opening speed of the electromagnet.
Motor Control Gear
463
It is not possible to design a contactor where every contact opens at the same
time. When the first contact opens, leaving the other two contacts a single-phase
circuit, one of these will then open the circuit completely. The chances of a failure
of the vacuum contactor are remote but contamination is one of the big problems,
and for safety reasons a loss-of-vacuum detector or a resistance leakage detector is
used, i.e. a common unit monitors the three outgoing lines and feeds into the detector unit, which latches and trips the circuit-breaker supplying the contactor. A
leakage of approximately 100 kW will cause the unit to operate and trip the backup protection.
The vacuum contactor gives long life with minimal maintenance. The only preventive maintenance required is to check the setting of the device. There are no contacts to replace.
OVERLOAD PROTECTION
Together with the contactor(s) the second major component of any motor starter is
the overload relay. The widespread use of CMR motors having a limited overload
capacity makes selection of the correct type of overload relay a major consideration for a motor starter.
The types of relay available are: thermal, electronic, magnetic, and thermistor. The
characteristics of thermal, electronic and magnetic relays normally comply with
the requirements of IEC 947 and BS EN 60947. The performance criteria are not
the subject of an individual product standard but are included in the ‘motor starters’
standards.
Thermal relays
A thermal relay normally consists of three bimetallic elements, one in each phase,
each of which is heated by the motor current. The method of heating the bimetals
may be direct where the bimetal element carries the motor current, or indirect
where the motor current is carried by a heater element and the heat transferred to
the bimetal through an insulating sleeve or small air gap.
Ambient temperature compensation is provided by a fourth bimetal, usually
having the same deflection sensitivity as those which are heated, placed in air inside
the relay body and adjusted so that the same deflection of the heated bimetals is
required to cause a trip whether the starter is in a high or low ambient temperature. It also compensates for the temperature rise of the air inside the starter case
and means that the user does not have to calculate derating factors and set the overloads accordingly.
Most modern thermal overload relays incorporate protection against loss of a
phase, a faster trip being obtained by the use of a differential trip mechanism which
trips as the de-energised bimetal cools and moves back to its rest position. An inherent feature of all thermal relays is a thermal memory which provides shorter tripping times when an overload is applied following a period of normal running than
the tripping time starting from cold. A typical time–current characteristic curve is
shown in Fig. 17.6 and a typical relay is shown in Fig. 17.7.
464
Handbook of Electrical Installation Practice
Fig. 17.6 Typical time–current characteristic for tripping of thermal overload relay.
A second function of this thermal memory is that the relay cannot be instantly
reset upon removal of the current; a cooling period must always be allowed to
elapse. This delay in resetting is typically 3–5 minutes.
Thermal overload relays are usually suitable for operation by current transformers, as specified by the manufacture; these enable isolation from the incoming
supply voltage, operation over a wider current range and some modification of the
time–current characteristic, for example to increase the run-up time available
without the overload relay tripping.
Motor Control Gear
465
Fig. 17.7 Typical small thermal overload relay covering FLC range of 0.14–40 A direct
connected.
Electronic relays
Electronic overload relays offer several advantages over conventional thermal or
magnetic overload relays, including:
•
•
•
•
•
Faster responses to three-phase overloads
Faster response to phase loss
Trip time–current settings are user adjustable
Other features such as visual indication of overload current are available on
mid-priced units.
Some models incorporate RS 485 communication ports.
A further advantage of electronic overload relays is that they dissipate less power
than an equivalent thermal or magnetic relay so there will be a lower temperature
rise in a starter enclosure where an electronic relay is fitted.
Magnetic relays
A magnetic relay employs a coil of wire in each pole of the motor supply; when
current is passed through these coils the resulting magnetic field attracts plungers
which when lifted actuate a trip switch. In order to cater for the starting current of
a motor a restraint device such as an oil dashpot is provided. When installing a magnetic overload relay, care should be taken that the dashpots are filled to the recommended level with the fluid provided by the manufacturer. If nuisance tripping
466
Handbook of Electrical Installation Practice
should occur in practice, the manufacturer should be consulted with regard to the
use of an alternative fluid in the dashpots. In general, vegetable or mineral oils
should not be used; silicone fluids only are recommended. It should also be remembered that magnetic relays lack a differential trip mechanism and so will not provide
such a high level of protection against loss of a phase as an electronic or thermal
relay. Magnetic overload relays do not have a thermal memory, so may be reset
immediately following a trip. This is an advantage in cranes and lifts where a
minimum delay before restarting is required. It is essential that regular maintenance
checks of dashpot fluid level and cleanliness are made.
Thermistor relays
Thermistors are used to detect the temperature of the motor windings. A thermistor is a thermally sensitive semiconductor resistor, which exhibits a significant
change in electrical resistance with a change in temperature. A detector monitors
the sudden increase in resistance of the thermistor at the critical temperature. Thermistors must be fitted by the machine manufacturer, who knows the positions where
hot spots occur on the machine.
It should be remembered that thermistor protection has the following
disadvantages:
(1) Special motors required; thermistors cannot be retrofitted
(2) Additional control cables required between starter and motor
(3) Limited protection for cables between starter and motor. They do not provide
close excess current protection as with a current sensing overload relay.
STARTER TYPES
A knowledge of starter types is required to enable one to select the correct unit for
a specific application. Choice of the right starter is important because failure to do
this can drastically reduce the working life of a drive and result in uneconomical
operation. A modern range of starters is shown in Fig. 17.8.
Direct-on-line starter
The simplest and least expensive form of starting is direct-on-line (dol) and this is
generally the standard choice for motors up to 7.5 kW. Subject to supply company
agreement, larger motors may be dol started.
The switch-on current is quite high, typically eight to ten times the motor full load
current, falling off as the motor accelerates to normal running speed. As well as the
current, the initial torque is also high, of the order of 125% of the full load torque.
This high level of starting torque can produce rapid acceleration and may be detrimental with belt or chain driven loads or if starting is frequent.
Motor Control Gear
467
Fig. 17.8 Typical range of small starters in deep drawn steel enclosures to IP 55.
Star-delta starter
If direct switching is not allowed, a method of reduced voltage starting may be used
in order to limit the motor starting current. The most popular method of reduced
voltage starting is star-delta. The starting current is approximately one third the
value of dol starting current (about twice full load current) and the starting torque
is one third of that with dol starting. A six-terminal motor must be used to enable
the winding connections to be changed during the starting sequence.
The connection of the overload relay in a star-delta starter is important. Consider
the relationship of currents during starting and running of a typical motor, having
a full load current of say 10 A and taking twice full load current (flc) in star at start.
An overload relay connected in the line and selected on a basis of 10 A flc would
experience a current of 20 A or 200% during starting. However, the motor windings
are rated at only 5.8 A and are subjected to a current of around 350%. It follows
that for correct motor protection during starting the overload should be connected
in series with the motor windings during both starting and running.
Occasionally, tripping times may prove to be too short at start with the overload
relay phase connected as recommended above; reverting to line connected may
solve this problem. Any deviation from the theoretically correct method of protection should only be undertaken if it has been established that the motor can withstand the more onerous conditions placed on it. If very long accelerating times are
experienced, the use of saturable current transformers may be necessary. As an
alternative, the overload relay can be connected in series with the delta contactor,
but this will provide no protection during starting. This disadvantage can be overcome by fitting a second overload relay in series with the line contactor, but rated
at the higher current.
468
Handbook of Electrical Installation Practice
Auto-transformer starter
Another reduced voltage motor starting method is that of using an autotransformer, which has significant benefits but is relatively expensive. It is particularly useful where progressive control of accelerating torque is required, for
example with large fans or mixers, and is often used with submersible borehole
pumps.
The starting voltage at the motor terminals (and therefore the starting torque)
can be selected to suit the load by means of tappings on the auto-transformer – the
usual values being 50, 65 and 80%. By using the Korndorfer system, the motor is
not disconnected from the supply during the transition period in which the autotransformer winding acts as a choke, thus eliminating the surge currents that would
otherwise occur.
The above starting methods are summarised in Table 17.2 and it will be seen that
the reduced voltage starters provide a reduction in starting torque.
Stator-rotor starter
The slip-ring motor has the advantage that, while developing approximately the
same starting torque as an equivalent size cage induction motor, the starting current
Table 17.2 Summary of starting methods for cage motors.
Motor Control Gear
469
is much lower. This type of motor is therefore largely used for applications where
starting current restriction is essential and a relatively long time is taken to reach
full speed due to the high inertia of the load. A stator-rotor starter is used only with
a slip-ring motor. With this method the stator is switched direct to the full supply
voltage but the current drawn from the supply is limited to typically between 125
and 200% of full load current by external resistors connected to the rotor windings.
In addition to limiting the starting current, the resistors improve the power factor
so that the current values given above produce starting torques of between 100 and
175% of full load value. As the motor accelerates, resistor sections are progressively
cut out by rotor contactors closing in sequence under time control. The more
rotor contactors, the lower the demand on the power supply and the smoother the
acceleration.
Soft starters
Soft starters are reduced voltage starters for a.c. cage rotor induction motors, which
can replace traditional star-delta or auto transformer starters in many applications.
Soft starters utilise a pair of back-to-back thyristors in each phase of the supply to
the motor and control the acceleration of the motor by varying the voltage applied
by phase control. Soft starters differ from variable speed drives as they do not vary
the frequency of the voltage applied to the motor.
In common with conventional reduced voltage starting techniques, they provide
reduced starting torque with respect to direct on line starting, but the starting torque
is not fixed as with a star-delta starter and is adjustable over a wider range than is
normally available from an auto transformer starter. A typical soft starter will be
able to apply values between 20% and 80% of line voltage to the motor as the
‘pedestal’ (the initial switch on voltage) and the starter will then ‘ramp up’
(smoothly increase the applied voltage) over a preset (adjustable) time period or
under current feedback control until the full value of line voltage is reached. Use
of the current feedback facility will ensure that the starting current will not exceed
a preset limit and the ramp up period may be automatically extended by the control
circuit electronics to ensure that a smooth start is achieved.
When full voltage is reached, the starter may be by-passed (the thyristors shorted
out by a contactor). This is the usual method of application as it reduces the heat
losses in the soft starter and does not normally required forced cooling of the
enclosure. The alternative is to leave the thyristors in circuit and operate the
starter in energy saving mode where the r.m.s. voltage applied to the motor is
reduced to the minimum required to maintain output power and rotational
speed. It should be noted that operation in energy saving mode will generate substantial heat losses in the thyristor heatsinks which will require the application
of forced cooling to the enclosure. Energy saving operation will also require the
fitting of harmonic filters as the drive produces harmonics continuously while
running. The current edition of BS EN 60947-4-2 permits soft starters to produce
harmonics while starting as the period will be relatively short, but requires that
harmonics produced during running be limited – refer to BS EN 60947-4-2 for the
full requirements.
470
Handbook of Electrical Installation Practice
Soft starters can also provide a ‘soft stop’ where the voltage applied to the motor
is reduced to a preset value, typically 60% of line voltage, and then smoothly
reduced (ramped down) for a preset period before the motor is disconnected from
the supply. This can be very useful in pumping applications where soft stopping can
help prevent ‘water hammer’, but will not be able to be used in any application
where emergency stopping is necessary.
Soft starters can be used with wound rotor induction motors but resistance must
still be inserted into the rotor circuit of the motor. The starting torque delivered will
be reduced in the same proportion as for a cage rotor induction motor starting on
reduced voltage.
Variable speed drives
In many industrial processes it is necessary to vary the speed of the machine
depending on the conditions prevailing at a specific time. Traditionally for lowpower machines this has been achieved by running the mains connected motor
at a fixed speed and interposing some device, such as slipping clutch, variable belt,
or gearbox between the motor and the load, or for higher kW drives by schemes
such as Ward Leonard. This can be achieved by using a variable speed drive which
can provide an optimum process speed, and may introduce an element of energy
saving.
The more widespread types of drive are a.c. and d.c. thyristor systems. The
most usual application of thyristors is in a.c. drives where the thyristor provides a
variable conduction angle which enables the amplitude of the output to be controlled between a maximum and zero. Thyristors can be connected in various converter configurations depending on the requirements of the load and electrical
network.
When connected to an electrical network, a thyristor drive equipment loads the
system in a manner that is different from conventional loads such as motors and
lighting circuits. This difference is primarily associated with the following two characteristics of these converters, which both contribute to a distorted load current
waveform:
(1) High reactive power consumption
(2) Harmonic currents arising owing to the non-linear impedance characteristic of
the converter; these may give rise to electromagnetic interference problems in
service.
With large converter power ratings both the nature of the supply network and the
duty of the converter must be thoroughly studied so that the most suitable type of
power factor correction or harmonic filtering can be selected. It should also be
remembered that fuse selection for thyristor drives is more critical than contactor
switchgear and that only fast acting ‘semiconductor’ fuses or other fuses specifically
approved by the drive manufacturer can be used.
Motor Control Gear
471
ISOLATION
It is a requirement of the Electricity at Work Regulations that equipment must be
effectively isolated from its power supply before any maintenance, fault finding or
modification is made.
The regulations also contain the ‘essential requirement’ that precautions are
taken to prevent accidental reconnection of the supply while work is in progress.
This is normally achieved by locking off the isolating device of the equipment
receiving attention; it must be remembered that it is not simply a matter of attaching a padlock to the isolator handle – the locking must be verified by attempting to
turn the isolator on with the lock in place. Where a number of persons are engaged
in the work, each must hold their own padlock and if necessary an adapter must be
fitted to accept the appropriate number of padlocks simultaneously.
The isolating device within a starter may typically be a triple-pole switch, a
moulded case circuit-breaker, a fuse switch combination or an air circuit-breaker.
The most common device is the air break triple-pole switch which will be mechanically interlocked with the front door or cover of the starter. Where an isolating
device is not fitted within the starter, the Regulations may be satisfied by locking
out the switching devices feeding the starter. It is important to ensure that in addition to the isolation and locking off of the main power supply to the starter, consideration is given to any remote control, signalling or sequencing connections
between the starter and any external equipment. Modern starters will incorporate
auxiliary poles on the isolating switch to remove any potentially dangerous voltages
from the control circuit at the same time as the main circuit, but it is important to
verify the lack of power by means of a voltmeter prior to actually touching the internal components. If it is necessary to work on an existing starter of an older design,
it may be that the differing regulations in force at the time of installation did not
require the same level of isolation, so extra care should be taken prior to working.
It is current practice to fit shrouding to IP 20 minimum on all incoming terminals
on isolators, and possibly over the main poles on contactors, overload relays and
fuse-holders.
A further difference in design practice is that of the door interlock function
between the isolator handle and door opening – the established practice in all cases
is that the door cannot be opened with the isolator in the on position, but subject
to the age of the equipment, it may be possible to insert the padlock in the isolator
handle and lock the handle in this position but still open the starter door; modern
practice is for the locking off to also lock the starter door closed.
Motor control centres
Modern installations and process plant require many motor starters and it is therefore often convenient to group these together in a single cubicle switchboard known
as a motor control centre (mcc), typically shown in Fig. 17.9.
Motor control centres will have been type tested by the manufacturer to confirm
compliance with BS EN 60439–1.
The general arrangement of most mccs consists of a horizontal air-insulated,
copper (or possibly aluminium) busbar system with vertical droppers to the various
472
Handbook of Electrical Installation Practice
Fig. 17.9 Motor control centres form a compact means of housing many starters.
components. Cable entry may be available from the top, or bottom with front and
rear access.
Incoming supply cables may be connected to the busbar system via air circuitbreakers, moulded case circuit-breakers or switch-fuses. In association with any of
these devices, mccs sometimes include bus-section switchgear, interlocking and
metering systems to meet specific customer requirements.
The starter units are contained in standard sized cubicles which may be of a fixed
pattern, for larger drives or withdrawable for drives up to around 160 kW.
A withdrawable starter has the advantage of being readily removed from service
and replaced by another starter of suitable type and rating, thus ensuring minimum
shutdown time on vital drives in the event of a failure. A further feature of the withdrawable starter is that the make up of the mcc (depending on the design) can be
readily modified to suit changing process requirements.
Short circuit co-ordination
The behaviour of a combination of short-circuit protective device (SCPD) and
starter under short-circuit conditions are specified in BS EN 60947–1.
Two categories of damage to starter were accepted:
Type ‘1’ Starter interior may need total replacement after a fault.
Type ‘2’ No damage to starter components, starter to be reusable after the occurrence of a short circuit.
Motor Control Gear
473
For all categories of pass the case of the starter must not become live during the
fault, i.e. must not present an electrical shock hazard to an operator, and the enclosure must be intact, i.e. displacement or opening of doors or covers is not permitted. For type 2 the contacts of the contactor(s) can be lightly welded, provided
the welds can be broken.
It is therefore essential that after a short-circuit the installation is inspected and
the mechanical movement of all switching devices is checked with the supply isolated prior to replacing fuses or reclosing the mccb feeding the starter.
Most manufacturers have carried out tests to demonstrate type 2 co-ordination
of starters with their recommended fuses or circuit breakers; in order to maintain
the level of protection the recommended fuse ratings or mccb setting should not be
exceeded without the manufacturer’s approval.
These standards define the test method to a two part short-circuit test sequence
where the performance of, typically, the starter and fuse combination is checked
at two fault levels referred to test currents r and q. In common with the other
tests specified in these standards the short-circuit tests must be performed as a
sequence; all parts of the test sequence must be ‘passed’ for certification to be
possible.
The values of test current are derived from a table; in the case of test current r,
the selection is based on the rated current of the starter being tested. As an example,
devices of rated currents up to and including 16 A are tested at a prospective fault
current of 1 kA and then the test repeated at test current q which is the full fault
level; the value is typically 50 kA, but actually subject to agreement between the
manufacturer and user.
The starter must still satisfy the same operator safety criteria as above. The
standards give detailed guidance on the evaluation of the test samples after the tests,
and the post-test checks to demonstrate the suitability of the devices for further
service also apply.
The pass or fail criteria are generally as in the old BS 4941 and IEC 292 types ‘a’
and ‘c’ co-ordination; as an approximation type 1 is equivalent to type ‘a’ and type
2 is equivalent to type ‘c’. It should be noted that a type ‘b’ pass is no longer recognised; this is now a form of type 1 pass. The possibility of contacts tack welding
during these tests is still recognised, so the recommendation to examine contactors
after any operation of main fuses or tripping of main circuit breakers must be
observed.
ENCLOSURES
Electrical equipment must be constructed to prevent electric shocks to users caused
by accidental contact with live parts; it must also be protected against environmental influences such as ingress of foreign bodies, dust and moisture. This is normally
achieved by some form of enclosure which may be metallic or non-metallic.
The degree of protection afforded by an enclosure is classified according to the
IP coding defined in BS EN 60529 (which also appears as an appendix to BS EN
60947-1). Extracts from the appendix of BS EN 60947-1 are given in Appendix II
of this book.
474
Handbook of Electrical Installation Practice
The classification is based on the letters ‘IP’ followed by two numerals, the first
defining the degree of protection against ingress of solid bodies or dust, and the
second defining the degree of protection afforded against the ingress of moisture.
In both cases, the numeral 0 is used to indicate the lowest degree of protection, i.e.
no protection; a supplementary letter may also be added to indicate suitability for
a specific application.
It should be noted that the IP codes assigned to an enclosure will have been confirmed by type tests, and that when installing enclosed equipment, consideration
must be given to the use of suitable glands in order to maintain the degree of protection. The IP codes assigned as the result of the type tests on an enclosure do not
indicate or imply the corrosion resistance of that enclosure.
CHAPTER 18
Lighting
R.L.C. Tate, FCIBS
Revised by H.R. King, BA(Hons)
(Thorn Lighting Ltd)
THE NATURE OF LIGHT
The electromagnetic spectrum
Light is a form of electromagnetic radiation. It is basically the same thing as the
radiations used in radio and television, as radiant heat and as ultraviolet radiation
and the still shorter X-rays, gamma rays, etc. Visible light is radiation in that part of
the spectrum between 380 and 760 nm, to which the human eye is sensitive. A
nanometre is a wavelength of one millionth (10-6) of a millimetre. Within these
limits, differences of wavelength produce the effect of colour, blue light being at the
short-wave and red at the long-wave ends of the visible spectrum. Because the
human eye is more sensitive to the yellow and green light in the middle of the spectrum, more power must be expended to produce the same effect from colours at
the ends of it. This is why the monochromatic low-pressure sodium lamps which
emit all their visible energy in two narrow bands in the yellow region are more efficient in terms of light output than ‘Northlight’ fluorescent tubes that imitate natural
daylight pretty closely and emit approximately equal packets of energy in each
spectral band.
The areas of radiation on each side of the visible spectrum are important to the
lamp maker. Wavelengths shorter than those of violet light are designated ‘ultraviolet’ or UV and have the property of exciting fluorescence in certain phosphors.
That is, when irradiated with UV, they themselves produce visible light. Infrared
radiation, at the other end of the spectrum, produces heating effects and may be
considered simply as radiant heat. Where, as in the case of a filament lamp, light
is produced by heating a coil of wire to incandescence, far more infrared radiation is
produced than visible light, and this is radiated and may be reflected with the light.
Reflection
Light is reflected from a polished surface at the same angle to the normal that it
strikes the surface. A truly matt surface scatters light in all directions, while a semimatt surface behaves in a manner between the two. It must not be forgotten that
475
476
Handbook of Electrical Installation Practice
Fig. 18.1 Concentrating specular reflectors are used in the design of various types of spot
lights, film projectors and high-bay industrial reflectors. Light (R) reflected from
a reflector of parabolic cross-section will produce a parallel beam when the
source is at the focus of the parabola (a), a divergent beam if behind the focal
position (b), and a crossing beam if it is in front of it (c). Spill light (S) is not
controlled by the reflector.
all reflectors absorb some of the light that falls on them, transforming it into heat.
Even super-purity polished aluminium absorbs about 5% of the light, while a whitepainted semi-matt reflector will absorb as much as 20% or more.
Concentrating specular reflectors are usually parabolic or elliptical in crosssection. If a compact light-source is placed at the focal point of a parabola, its light
will be reflected as a parallel beam, that from a source placed at one focus of an
ellipse will be reflected through the second focus, while a hemispherical reflector
will reflect light back through its own centre. These principles are made use of in
the design of various types of spotlights, film projectors and high-bay industrial
reflectors (Fig. 18.1).
Refraction
When light passes from one clear translucent medium to another, e.g. from air to
water or air to glass, it is ‘bent’ or refracted at the surface. This can be observed by
dipping a straight rod into water, which will appear to be bent at the point of entry.
This property is made use of in lenses and refracting panels in lighting fittings.Again,
it is important to remember that some light will be lost in passing through the
medium and some will be reflected from its upper surface, to a greater or lesser
degree according to the angle at which it strikes that surface.
Diffusion
If light passes through a surface that is partially opaque, it will be scattered or diffused in all directions. Typical diffusers are sand-blasted or acid-etched glass, flashed
opal glass or opal acrylic sheet. The distance the light-source is mounted from the
diffuser, the opacity of the latter and the nature of the background or reflecting
surface will determine whether the light-source appears as a bright spot of light or
its light is evenly diffused over the surface. Light losses in a ‘near perfect’ diffuser
are greater than those in a partial diffuser or a prismatic panel.
Lighting
477
Fig. 18.2 The relationship between the candela and the lumen. If the shaded area = r 2 and
a source of one candela is at the centre C, the light contained within the solid
angle q is one lumen.
UNITS OF LIGHT MEASUREMENT
The unit of luminous intensity is the candela. This is the amount of light emitted in
a given direction by a source of one candle power. From it is derived the lumen, the
unit of light flux. This is quite simply defined as the amount of light contained in
one steradian from a source of one candela at its focus (Fig. 18.2). The light output
of all electric lamps is measured in lumens and their luminous efficiency (efficacy)
is expressed in lumens per watt.
The unit of illuminance (measured illumination) is the lux. This is the illumination produced over an area of one square metre by one lumen. The ‘foot-candle’ or
lumen per square foot has long been an obsolete term in the UK, but is still used
in America.
Measured brightness is termed ‘luminance’ and should not be confused with
‘illuminance’. Its units are the candela per square metre and the apostilb, the lumens
emitted by a luminous surface of one square metre. Imperial units, now obsolete
but still occasionally quoted, are the candela per square foot and the foot-lambert.
Two other terms that are easily confused are ‘luminance’ and ‘luminosity’. The
first is measured brightness expressed in apostilbs or candelas per square metre, the
second the apparent brightness as seen by the eye. A simple example is the appearance of motor-car headlamps by day and by night. Their luminance is the same in
both conditions but their luminosity is far greater at night than when they are seen
in daylight.
ELECTRIC LAMPS
Lamps produce light in four ways: by incandescence, by the excitation of metallic
vapours in an electrical discharge, by fluorescence initiated by a discharge in
mercury vapour causing radiation in the ultraviolet region of the spectrum, and by
induction.
478
Handbook of Electrical Installation Practice
All modern filament lamps consist basically of a coil of tungsten wire enclosed in
a glass bulb generally filled with an inert gas. Tungsten is used because of its high
melting point; most filaments operate at temperatures in the region of 2700°C. At
this temperature the surface of the filament evaporates slowly, until a point is
reached where it cannot support its own weight and fractures. The rate of evaporation is controlled by the gas filling, usually a mixture of argon and nitrogen, which
in general service (gls) lamps exerts a pressure of about half an atmosphere on the
surface of the filament. Evaporated tungsten settles on the inner surface of the glass
bulb, discolouring it and reducing the amount of light emitted by the lamp throughout its life. The filament is coiled to reduce heat losses by convection currents in the
gas; coiling substantially reduces the area exposed to them.
In the case of all standard mains voltage lamps made to BS 161: 1976, the life of
the filament is 1000 h. Lamps made for special purposes, such as projector lamps
often have a shorter life.
Reflector lamps
Blown glass reflector lamps were first introduced in the late 1940s and are now
made in sizes ranging from 40 to 150 W. Pressed glass lamps with a more accurately
profiled reflecting surface followed in the mid-1950s. The greater efficiency of the
reflector allowed the filaments to be slightly underrun without loss of light in
the beam so that these lamps have a rated life of 2000 h. Lamps are available
with a dichroic reflecting surface which reduces radiant heat in the beam, but
care should be exercised not to mount them in enclosed luminaires, which would
overheat.
Tungsten-halogen lamps
The use of a small quartz bulb allows the gas pressure to be substantially increased,
thus lengthening the life of the lamp by reducing the rate of evaporation of the
filament. Heavy blackening of the bulb by the tungsten deposited on it is avoided
by the application of the tungsten-halogen principle. The addition of a small amount
of a halogen, usually iodine, to the gas filling results in an unstable compound being
formed with the evaporated tungsten, which is maintained at temperatures between
about 200 and 2500°C. As the bulb wall temperature is in excess of 250°C, no tungsten is deposited on it. The tungsten halide is carried into the filament by the convection currents in the gas, where it separates into its original components, the
tungsten being deposited on the cooler parts of the filament and the halogen being
released to repeat the cycle. Note that the longer life and higher light-output of
these lamps is entirely dependent on the increase of gas pressure and has nothing
to do with the redeposition of the tungsten on the filament.
Mains voltage tungsten-halogen lamps have from double to four times the life of
GLS lamps of equivalent type and give up to 20% more light.
Recently the lighting industry has developed the miniature low voltage (12 V)
lamp. Such lamps are used in capsule form, or more commonly are set into a metal
or dichroic reflector. The combination of a tiny tungsten-halogen lamp set into a
Lighting
479
Fig. 18.3 A typical discharge lamp, in this case an MBF lamp. All modern lamps operate in
a translucent enclosure containing the appropriate metals or metal halides.
dichroic-coated mirror (diameter is only 50 mm for the 50 W rating) gives great
optical benefits, particularly for the display world. The reflector produces a precise,
uniform beam resulting in intense, efficient light of high colour rendering and good
appearance. The dichroic mirror allows most of the heat to pass backward while
reflecting a relatively cool beam of light forward. This resulting ‘cool-lightstream’ is
most important in displays as a wide range of merchandise may suffer from heat.
Owing to the efficiency, a 50 W lamp compares with a 150 W PAR 38 spot and thus
leading retailers are now utilising the benefits. Low-voltage tungsten-halogen lamps
require a transformer to operate.
Discharge lamps
When an arc is struck in a gas or metallic vapour it radiates energy in characteristic wavebands. For example, neon gives red light, sodium yellow and mercury vapour
four distinct lines in the visible and two in the ultraviolet region of the spectrum.
All modern discharge lamps operate in a translucent enclosure (Fig. 18.3) containing the appropriate metals or metal halides; the initial discharge is usually struck
in argon or neon. As the metal or metal halide evaporates, it takes over the discharge from the starter gas and emits light at its characteristic wavelengths.
Because more light and less heat is radiated by these lamps, they are more
efficient in terms of lumens per watt than filament lamps, but where a line spectrum
is emitted there is a marked distortion of colours seen under their light.
Low-pressure sodium lamps
These are the most efficient lamps in terms of lumens per watt, because the
monochromatic yellow light they produce is in the area near the peak of the eye
480
Handbook of Electrical Installation Practice
sensitivity curve. Because only yellow light is emitted, however, objects are seen in
tones of black and yellow only and colours cannot be perceived. They are extensively used for highway lighting and in situations where no colour discrimination is
necessary.
High-pressure sodium lamps
If the internal vapour pressure of a sodium vapour lamp is increased, the sodium
spectrum will broaden to include colours on both sides of the original yellow lines.
Although this will result in a slight reduction of efficacy, it allows colours to be discriminated. High-pressure sodium lamps are rated in sizes from 1 kW down to 50 W
and have taken over from mercury discharge lamps in side streets, industrial and
commercial applications. The efficacy of these lamps is in the order of 100 lm/W
compared with 150 lm/W for low-pressure sodium and 45 lm/W for mercury lamps.
Most manufacturers have increased their high-pressure sodium lamp offers with
increased output and improved colour versions, the latter opening up applications
into commercial interiors.
Mercury vapour lamps
Mercury vapour lamps emit a considerable amount of energy in two wavebands in
the UV region, the proportion of visible to invisible radiation being closely related
to the gas pressure in the discharge tube. This is used to excite fluorescence in
phosphors coating the inside of the outer bulb to add some of the missing red to
their spectrum.
Metal halide lamps
Metal halide lamps use mercury vapour and the halides of a number of chemically
active metals which are released as the temperature in the arc tube increases, producing a virtually continuous spectrum in which colours can readily be distinguished and
seen with very little distortion. Their main advantage is that they provide a compact
source of light with good colour-rendering properties at efficacies in the order of
80 lm/W. Initially available in high wattages, suitable for floodlighting and industrial
applications, they are now available in lower wattages, typically 150 W, 70 W and 35 W,
and can thus provide high-quality white light for commercial interiors.
Recently ceramic metal halide lamps have been developed giving better colour
consistency. Here quartz has been replaced with ceramic poly crystalline alumina to
eliminate sodium loss, the principle cause of colour shift towards blue/green.
The main characteristics of discharge lamps are summarised in Table 18.1.
Run-up time
All the discharge lamps so far referred to have a ‘run-up’ period varying from a few
minutes to a quarter of an hour. They also require time for the vapour to cool and
its pressure to drop before they will restrike after they have been extinguished,
except for low-pressure sodium lamps which restrike immediately current is
Table 18.1 Basic characteristics of discharge lamps.
Lumens per watt
(initial)
Colour
appearance
Colour
rendering
Mercury
50
Bluish white
Metal halide
double ended compact
80
Metal halide
double ended
Average life
(h)
Poor
50–1000
16 000–24 000
White
Very good
70–250
6 000
80
White
Very good
750–2000
6 000
Metal halide
single ended compact
80
White
Very good
35–150
6 000
Metal halide
eliptical coated
80
White
Very good
70–1000
14 000
Metal halide
tubular clear (horz mounted)
85
White
Very good
70–1000
6 000
140
Orange
None
18–180
16 000
Low-pressure sodium
economy
180
Orange
None
26–131
16 000
High-pressure sodium
96
Yellow
Very poor
50–1000
24 000
High-pressure sodium
increased output
100
Yellow
Very poor
50–600
24 000
High-pressure sodium
improved colour
90
Golden
Good
150–400
12 000–16 000
481
Low-pressure sodium
Lighting
Power range
(W)
Lamp type
482
Handbook of Electrical Installation Practice
restored. High-pressure sodium lamps recover a great deal more quickly than
other types.
Fluorescent tubes
A fluorescent tube is a low-pressure mercury discharge lamp. At this pressure, the
mercury arc emits very little visible light and a considerable amount of UV radiation in two distinct wavebands, one in the harmless near-visible region and the other
in the shorter-wave therapeutic area. This emission is used to excite fluorescence in
the phosphors coating the inner surface of the tube, which may be typically up to
2400 mm long and 38 mm (T12) or 26 mm (T8) in diameter according to the power
rating.
Recently a new range of lamps (T5s in ratings from 14–54 W) have been introduced. These operate only from special electronic control gear and are slimmer than
standard tubes (16 mm). Lamp efficacy is much improved. Data for the majority of
types of tube are shown in Table 18.2.
Two recent developments are the introduction of high efficacy fluorescent tubes
utilising the rare earths developed for colour television as well as the conventional
halophosphates, and krypton gas to facilitate starting. Because the light from the
phosphors is produced mainly in the three areas of the spectrum, blue, red and
green, which combine to give the effect of white light, instead of having a virtually
continuous spectrum like the conventional type of tube, they may occasionally give
rise to the effect of ‘metametric mismatching’ of colours. In situations where
accurate colour-matching is essential, therefore, the standard halophosphate tubes
should be used.
In 1981 compact fluorescent lamps, such as GE’s 2D and Philip’s PL and SL, were
introduced as an energy-saving replacement for the gls lamp. The 2D lamp is a
520 mm long by 13 mm outside diameter tube bent into a tight, double ‘D’ shape
and supported by a central mounting plate which incorporates the starter. Consuming only 21 circuit watts, the 16 W 2D lamp has a light output approaching that
of a 75 W lamp, but saves around 70% of the energy. Substantial savings are possible, especially where lights are in continuous use. But energy saving is not its only
feature. It has a life ten times longer than a filament lamp, is comparatively cool
running and is similar in colour appearance to an incandescent lamp (Table 18.3).
Improvements are growing all the time and while breaking away from the 2D shape,
but still utilising the principle, two limb, four limb and six limb lamps are available
in ratings from 5 W to 55 W. They have become a compact alterative to conventional
linear fluorescent tubes.
Induction principle
An induction lamp is somewhat like a fluorescent. It contains a low pressure of
mercury which, when excited, radiates UV, which in turn is absorbed by a phosphor
coating and reradiated as visible light. However, the induction lamp has no electrodes and the discharge is created by a magnetic field generated externally to the
bulb. Lamp life can be 60 000 hours and the lamps operate at high frequency so there
Table 18.2 Initial lumens for fluorescent tubes.
Length (mm)
Watts
Tube-Dia.
1800
70
T8
1500
58
T8
1450
35
T5
1200
36
T8
1150
28
T5
900
30
T8
850
21
T5
600
18
T8
550
14
T5
450
15
T8
Ra
White
3450
54
5800
4800
–
3000
–
2300
–
1225
–
950
Warm-white
2950
51
–
4800
–
3000
–
2300
–
1255
–
950
Cool-white
4000
58
5700
4700
–
3000
–
2250
–
1200
–
900
Natural
4000
73
–
4100
–
2600
–
–
–
1100
–
–
Daylight
6500
76
–
3580
–
2400
–
1700
–
950
–
730
Tri-phosphor
2700
85
–
5400
3300
3450
2600
2500
1900
1450
1200
1050
Tri-phosphor
3000
85
6550
5400
3300
3450
2600
2500
1900
1450
1200
1050
Tri-phosphor
3500
85
6550
5400
3300
3450
2600
2500
1900
1450
1200
–
Tri-phosphor
4000
85
6550
5400
3300
3450
2600
2500
1900
1450
1200
1050
Lighting
CCT
483
484
Handbook of Electrical Installation Practice
Table 18.3 Initial lumens for a selection of compact
fluorescent lamps.
Type
16 W 2 D
28 W 2 D
38 W 2 D
18 W 2 limb
24 W 2 limb
36 W 4 limb
42 W 6 limb
Lumens (initial)
Rated life (h)
1 050
2 050
2 850
1 250
1 800
2 800
3 200
10 000
10 000
10 000
10 000
10 000
10 000
10 000
is no flicker. 55 W and 85 W ratings are available. Colours are the same as fluorescent tubes.
CONTROL GEAR AND STARTING
All arc lamps require a current limiting device to prevent them taking more and
more current until they destroy themselves. In most cases a starting device is also
necessary to strike the arc.
A high-pressure mercury lamp is operated in series with a choke having a laminated iron core. The starting device consists of a secondary electrode within the arc
tube, connected through a resistor to one electrode and in close proximity to the
other. When the lamp is switched on an arc is struck between the adjacent electrodes, ionising the argon filling of the arc tube so that the main discharge is struck
between the cathodes. The secondary electrode then ceases to function because of
the resistor in series with it.
Metal halide and high-pressure sodium lamps require an external ignitor in addition to the choke, although some manufacturers sell SON lamps with an internal
starter like that of a mercury lamp, so that they can be operated from a choke
designed for approximately the same sized mercury lamp. The separate ignitor,
however, is more reliable. It must be placed as close to the lamp as possible to avoid
voltage drop in the lead to the lamp; the position of the choke is not critical.
Fluorescent tubes, being essentially low-pressure mercury lamps, also need a
current limiting and starting device. The former usually takes the form of a choke,
but occasionally a resistor is used. A starter switch, wired in parallel with the tube,
is commonly installed.
In all cases where an inductive current limiting device is used, a capacitor is
included in the circuit for power factor correction. This is usually housed in the luminaire with the rest of the controlgear, but bulk power factor correction at a central
point is occasionally used. Starters are always housed in the luminaire, but in some
cases, as for example street-lighting lanterns and floodlights using metal halide
lamps, the choke may be mounted elsewhere.
Lighting
485
Since 1985 electronics have been used to start fluorescent lamps. The highfrequency electronic ballast provides instant, flicker-free starting for single and
twin standard fluorescent lamps up to 1800 mm in length. It takes advantage of a
characteristic of fluorescent lamps whereby greater efficacy is obtained at high
frequency, typically 32 kHz. The overall achievement in a suitable luminaire is an
energy reduction of 20–30% while still maintaining the lighting level. This is due to
improved lamp efficacy at high frequency operation and reduced circuit power
losses as the new solid-state unit contains no conventional copper windings. The
quality benefits are no flicker, instant start, no stroboscopic effects and silent operation. In addition, the ballast is a complete gear unit requiring no additional power
factor correction capacitor or starting device, thus allowing fittings to be lighter in
weight and more compact.
LUMINAIRES (LIGHTING FITTINGS)
Most of the light from a bare lamp is likely to be wasted; in addition, a bare
unshielded lamp gives rise to glare which can hinder vision, so the use of a luminaire to house the lamp(s) and direct or diffuse its light is essential. The detailed
design of luminaires is outside the scope of this book, but some knowledge of the
principles involved is needed if satisfactory lighting schemes are to be produced.
Luminaires may be classified by their light distributing qualities and their choice
governed by the quality of light required. It may also be influenced by special safety
considerations, such as where lamps are used in explosive or corrosive atmospheres
or are liable to mechanical damage or excessive vibration.
There is an abundance of luminaire and control gear terms in common use. The
following list does not attempt to provide precise definitions, but rather to suggest
the most common meaning and where appropriate to point out the areas or potential confusion.
Air terminal devices
The means by which air is supplied or extracted from a
room.
Ballast
Control gear inserted between the mains supply and one or more discharge lamps, which by means of inductance, capacitance or resistance, singly
or in combination, serves mainly to limit the current of the lamp(s) to the
required value.
Barn doors
Four independently hinged flaps that serve to cut off spill light for
spotlights.
Batten
A fluorescent luminaire with no attachments; just the control gear
channel and a bare tube.
Bulkhead
A compact enclosed luminaire designed for horizontal or vertical
mounting outdoors or indoors.
Ceiling system
A grid and panel system providing a false ceiling to incorporate
lighting and other building services.
Choke
A simple low power factor inductive ballast.
Columns
Poles for mounting road lanterns or floodlights.
486
Handbook of Electrical Installation Practice
Controller
A clear plastic or glass with prism shapes in the surface; the overall
shape may be flat or formed.
Diffuser
An attachment intended to reduce the lamp brightness by spreading
the brightness over the surface of the diffuser.
Downlighters
This term is frequently misused to refer to any luminaire which
produces no upward light, whereas the object of a downlighter is to provide
illumination without any apparent source of light. They are therefore extremely
‘low brightness’ luminaires referring particularly to small recessed, semirecessed or surface ‘can’ luminaires.
Emergency lights
Lighting provided for use when the mains lighting fails for
whatever reason. There are two types: (1) escape lighting and (2) standby
lighting.
Escape lighting
See Emergency lights.
Eyeball
A recessed adjustable display spotlight.
Flameproof
An enclosure capable of withstanding the pressure of an internal
explosion and preventing transmission of the explosion to gases and vapours
outside the luminaire.
Floodlight
General term applied to exterior fittings housing all types of lamps
and producing beams from very narrow to very wide. Floodlights usually
employ a specular parabolic reflector and their size is determined by the light
source employed and distribution required. The term also applies to interior
fittings providing a fairly wide beam which could not be described as a
‘spotlight’.
High bay
As the name implies, these are for use when mounting heights of
around 8–10 m or above are encountered. They have a controlled light distribution to ensure that as much light as possible reaches the working plane.
Although primarily intended for industrial areas they also find applications in
lofty shopping areas and exhibition halls.
Hood
A baffle projecting forward from the top of a floodlight or display spotlight to improve the cut-off spill light above the horizontal to reduce glare and
light pollution.
Ignitor
A starting device, intended to generate voltage pulses to start discharge
lamps, which does not provide for the pre-heating of electrodes.
Inverter
Electronic device for operating discharge lamps (usually fluorescent)
on a d.c. supply obtained either from batteries or generators.
Lantern
Apart from reproduction period lighting units, this is an alternative
term for a luminaire usually restricted to roadlighting or stage lighting
equipment.
Louvres
Vertical or angled fins of metal, plastic or wood arranged at right angles
to linear lamps or in two directions. The object is to increase the cut-off of the
luminaire and so reduce glare from critical angles. Louvres can also form ceiling
panels with lighting equipment placed in the void above.
Low bay
Luminaires housing high-pressure discharge lamps (usually mounted
horizontally) to provide a wide distribution with good cut-off at mounting
heights around 4–8 m. Apart from industrial applications, these are used in
many sports halls and public concourses.
Lighting
487
Low brightness
Term usually applied to commercial fluorescent luminaires
where, by the use of louvres, the brightness is limited. These are particularly
appropriate for offices with VDTs.
Mast
Mounting columns higher than 12–15 m are generally referred to as masts
and are used to support floodlighting for large areas.
Optic
The reflector and/or refractor system providing the light control for the
luminaire.
Post top
Road or amenity lighting luminaire which mounts directly on to the
top of a column without a bracket or out-reach arm.
Profile spotlight
Luminaire with focusable front (objective) lens producing a
hard edge beam. By a set of adjustable shutters or masks at the gate of the projector, the beam can be shaped or ‘gobos’ (cut-out metal slides) can be used to
project patterns or pictures.
Projector
Term for floodlight or profile spotlight.
Proof
Applied to all types of luminaires which have a higher degree of protection from the ingress of solids and liquids than standard interior lighting
luminaires.
Recessed
The luminaire mounting arrangement where the whole or part (semirecessed) of the luminaire body is set into a ceiling or wall or floor surface.
Refractor
Clear glass or plastic, panel or bowl where an array of prisms is
designed to redirect the light of the lamp into the required distribution.
Semi-recessed
See Recessed.
Spine
See Batten.
Spotlight
An adjustable interior luminaire with controlled beam using a reflector lamp or optical system.
Stand by lighting
See Emergency lights.
Starter
A starting device usually for fluorescent tubes which provides the necessary preheating of the electrodes and, in combination with the series impedance of the ballast, causes a surge in the voltage applied to the lamp.
Tower
Lattice, steel or concrete structure from 15 m to 50 m to support area
floodlighting equipment.
Track system
A linear busbar system providing one to three main circuits or a
low voltage supply to which display lighting can be connected and disconnected
at will along the length of the system. The luminaires must be fitted with an
adapter to suit the particular track system in use.
Transformer
A wire-wound or electronic unit which steps-up or down its supply
voltage. Often fitted integrally into low voltage spotlights.
Troffer
Fluorescent or discharge luminaire designed to recess into suspended
ceilings and fit the module size of the ceiling. See Recessed.
Trunking
Apart from standard wireway systems in ceilings and floor, trunking
associated specifically with lighting usually provides mechanical fixings for the
luminaires as well as electrical connection.
Uplights
Indirect lighting system where task illuminance is provided by lighting
reflected from the ceiling. The luminaires can either be floor standing, wall
mounted or suspended and can be arranged to provide either general or
localised lighting.
488
Handbook of Electrical Installation Practice
Visor
Clear or diffused glass or plastic, bowl or flat panel closing the mouth of
a luminance.
Wall washer
Interior floodlight or spotlight with asymmetric distribution
intended to provide uniform lighting of walls from a close offset distance.
Wellglass
These consist of a lamp surrounded by an enclosure of transparent or
translucent glass or plastic. They are usually proof luminaires and often used
outdoors fixed to a bracket.
Zone 0, 1 and 2 fittings
Classification of various hazardous areas.
Lighting safety
The following provides explanations of some of the most common classifications
applied to luminaires:
Class I
luminaires in this class are electrically insulated and provided with connection with earth. Exposed metal parts that could become live in the event of
basic insulation failure are protected by earthing.
Class II
luminaires are designed and constructed so that protection against electric shock does not rely on basic insulation only. This can be achieved by means
of reinforced or double insulation. No provision for earthing is provided.
Class III
protection against electric shock relies on supply at safety extra-low
voltage (SELV) and in which voltages higher than those of SELV are not
generated (max. 50 V a.c. r.m.s.).
F Mark
luminaires suitable for mounting on normally combustible surfaces
(ignition temperature at least 200°C) are marked with the ‘F’ symbol.
Ta Classification
this denotes the maximum ambient temperature that the luminaire is suitable for use in max. 25°C ambients.
British Standards
Lighting products should be designed and manufactured to the standards given in
Table 18.4. European equivalents are also listed.
Table 18.4 Standards for lighting products.
Subject
British Standard
European standard
Luminaires – general types
Luminaires – recessed
Luminaires – roadlighting
Luminaires – floodlights
Luminaires – with transformers
Luminaires – air-handling
Luminaires – emergency
Luminaires – track
EMC emissions – lighting
Emergency lighting
BS 4533: 102.1
BS 4533: 102.2
BS 4533: 102.3
BS 4533: 102.5
BS 4533: 102.6
BS 4533: 102.19
BS 4533: 102.22
BS 4533: 102.57
BS EN 55015
BS 5266
EN60 598 2.1
EN60 598 2.2
EN60 598 2.3
EN60 598 2.5
EN60 598 2.6
EN60 598 2.19
EN60 598 2.22
EN60 570
EN55 015
EN 1838
Lighting
489
Wherever possible, luminaires should be purchased that are marked with a third
party approval, such as the BSI Kitemark. The ENEC mark has been introduced
following European harmonisation of standards. The ENEC mark indicates that a
luminaire is suitable for use throughout Europe and that all of the most onerous
special national conditions of EN 60 598 have been complied with.
Ingress protection
The ingress protection (IP) code denotes the protection against dust, solid objects
and moisture provided by the luminaire enclosure. If no code is marked, the luminaire is deemed to be IP20. The first digit of code denotes protection against dust
and solid objects, the second against moisture, for example IP65 is a dust-tight and
jet-proof luminaire.
Atex Directive
In 2003 the Atex Directive becomes a mandatory requirement for all hazardous
area equipment sold in the EU. Equipment must have an applicable Atex certificate. Zoning references are amended and gas, vapour, mist and dust categories are
combined under a single classification.
Pre-Atex
Zone 0 + 20
Zone 1 + 21
Zone 2 + 22
Atex
Category 1
Category 2
Category 3
OUTDOOR LIGHTING EQUIPMENT
Floodlights
Floodlights commonly employ either tungsten-halogen or discharge lamps.
Tungsten-halogen floods are found in a number of industrial and commercial
situations, especially where an immediate flood of light is needed.
The use of high-pressure sodium and metal halide lamps is popular for such applications as the floodlighting of pubs and sports grounds, and for the lighting of the
yards and loading bays of industrial premises. In addition to the longer life and
higher light output of these sources, the type of floodlight described is more energy
efficient; for example, a 70 W high-pressure sodium lamp (88 circuit watts) produces
more light then a 300 W tungsten-halogen lamp.
Specialised floodlights for football stadia
Floodlights using metal halide linear lamps specially designed for football stadia in
which matches are covered by coloured TV are usually intended for comparatively
low mounting heights, on the roofs of the stadia or just above them. The 2000 W
type is very compact and may be fitted with an internal baffle or flat glass to prevent
490
Handbook of Electrical Installation Practice
direct light from the arc tube dazzling spectators on the opposite side of the pitch.
Control gear is housed separately from the floodlight.
FLOODLIGHTING CALCULATIONS
Floodlights mounted on poles are extensively used for lighting areas such as loading
docks, parking lots and so forth. The calculation of the illuminance is not difficult,
but it varies from the method used in the interior of buildings in certain respects
and other terms are introduced.
Beam angle
This is the width or spread of the beam and is defined as the total angle over which
the intensity drops to a fixed percentage, 50%, 10% and 1% of its peak value. A
single figure is given for a floodlight with a symmetrical distribution, two for a unit
with an asymmetric distribution.
Beam flux and beam factor
Beam flux is the total flux contained within the beam angle to 10% of peak intensity and is usually expressed as the proportion of lamp lumens contained within the
beam (beam factor). It is usually presented in tabular form by the manufacturers.
Instead of the usual ‘utilisation factor’ a ‘waste-light factor’ multiplied by the
‘beam factor’ is used. The waste light factor is usually taken as about 0.9, but in
awkward shaped areas may be as high as 0.5. It is influenced by the width of the
floodlight beam.
Illuminance diagrams
A number of manufacturers publish illuminance diagrams which provide an easy
method of calculating the illuminance over an area from a specific floodlight at a
known mounting height and aiming angle. These can be superimposed to calculate
the illuminance from an array of floodlights. A typical diagram is shown in Fig. 18.4.
Conversion factors are used to adapt the figure for different mounting heights.
Zonal flux diagrams
Another method, which is very adaptable, is the use of ‘zonal flux diagrams’, a typical
example of which is shown in Fig. 18.5. It is divided through the plane of symmetry
with isocandela lines plotted on the angular grid and figures denoting the flux per
1000 lamp lumens in each angular zone on the right. It can either be used to calculate point values of illuminance or the flux intercepted by the area to be lit, which
can be drawn as an overlay using the same angular scale. Elevation of the floodlight
can be shown by moving the diagram up and down the vertical grid line, but a fresh
diagram must be drawn for adjustments in azimuth. The beam factor of the floodlight is expressed by the dotted line on the diagram. The beam lumens per 1000 lamp
lumens is twice the value of the flux values enclosed within it.
Lighting
491
Fig. 18.4 Data sheet for a typical floodlight showing area illuminance.
Street-lighting lanterns
The basic principle of highway lighting is to achieve a bright road surface against
which vehicles can be seen in silhouette. The non-specialist lighting engineer can
usually ignore highway lighting techniques since he is only likely to be concerned
with lighting subsidiary road and parking areas within a factory complex or similar
location. Recommendations for exterior lighting are given in BS 5489, Road lighting and the CIBSE lighting guide: Outdoor environment. A number of lanterns
mounted on top of a pole can be suitable for this purpose. They are usually designed
to take any suitable light-source and the control gear may be mounted in the
housing or in a chamber at the foot of the pole.
LIGHTING DESIGN FOR INTERIORS
Recommended task illuminance
The amount of light needed to perform a visual task satisfactorily varies according to the size of the object being handled and the contrast between it and the
background, either in terms of brightness or of colour or both. For example, fine
492
Handbook of Electrical Installation Practice
Fig. 18.5 Data sheet for a typical floodlight showing angular beam features.
Lighting
493
Table 18.5 Recommended maintained illuminance (CIBSE Code 1994).
Note: Adjustments to increase or reduce these values may be justified on the basis of
task difficulty, task duration and where error can have serious consequences.
assembly, as in watch-making may require an illuminance of about 1000 lux. Insufficient light may lead to eye-strain and slow down production, causing mistakes to
be made or faulty workmanship to be overlooked.
CIBSE Code
The CIBSE in its Code for Interior Lighting give recommendations for good lighting practice (Table 18.5). Having ‘ sufficient’ light is only one aspect of many. Illumination values are, in the Code, recommended as maintained illuminance, at a
value below which the average illuminance should not fall during the life of the
installation. This can be fulfilled by carrying out an appropriate maintenance regime
on the lamps, luminaire and room. The Code is an essential tool for the lighting engineer and, indeed, for anyone concerned with lighting design.
Photometric data
To plan a lighting installation to give a specified illuminance on a working surface
or plane, the engineer must know how to use photometric data published by reputable luminaire manufacturers and be familiar with such terms as ‘light-output
ratio’ (LOR) of luminaires. The significance of the utilisation factor in calculating
the illuminance from an array of luminaires by the ‘lumen method’ of design must
also be understood. Such matters as the relationship between the spacing to mounting-height ratio of luminaires, the evenness of the illumination on the task area and
discomfort glare from the luminaires, must also be borne in mind.
494
Handbook of Electrical Installation Practice
Light-output ratio
The LOR is the proportion of the total lumen output of the lamp that is emitted
from the luminaire. It must be understood that all reflecting and diffusing media
absorb a certain amount of light when controlling light from the lamp(s).
The LOR of a luminaire is of little use by itself. For example, a bare fluorescent
single ‘batten’ may have an LOR as high as 0.95, but in most cases will be less effective overall visually than one fitted with a reflector with a total LOR of 0.84. It is
normal to specify upward and downward LOR. For example, a bare tube might have
an upward LOR of 0.29 and downward of 0.66, and the reflector unit 0.02 upward
but 0.82 downward, an improvement where light delivered on the working plane
and control of glare from the luminaires is concerned. This is especially important
where luminaires are mounted under a glass or dark-coloured roof, a common situation in industrial interiors.
Luminous intensity and polar curves
Most manufacturers publish luminous intensity tables, giving the intensity in candelas per 1000 lamp lumens on a single vertical plane for symmetrical (tungsten or
discharge lamp luminaires) or on a transverse and axial plane for fluorescent luminaires and those using linear sources. Most of the lighting data for the luminaires
are derived from these measurements, although in some cases more than two planes
are measured.
From the table of luminous intensities the ‘polar curve’ for the luminaire can be
derived (Fig. 18.6). Polar curves are a useful indication of the general light distri-
Fig. 18.6 Polar curves are a useful indication of the general light distribution of a
luminaire. This is shown as axial and transverse where appropriate.
Lighting
495
Fig. 18.7 A polar diagram must not be misread, in that the amount of lumens contained in
the horizontal plane may be greater than in the vertical plane: (A) all light in
equatorial area; (B) all light in polar area. Actual lumens delivered at A is considerably in excess of B.
bution of a luminaire. The point where the horizontal and vertical lines cross corresponds to the optical centre of the luminaire. The direct distance from this point
to the curve shown is proportional to the luminous intensity at that angle. The lefthand side of the curve corresponds to the transverse plane (T) and the right-hand
side of the curve corresponds to the axial plane (A). The tabular values of intensity
are valuable if accurate calculations of the illuminance at a given point are required.
It must be clearly understood that the area enclosed in a polar curve does not give
an indication of the amount of light emitted by the luminaire in that direction.
Figure 18.7 shows that although the downward component of the polar curve illustrated covers a greater area than the horizontal one, the actual lumens contained in
the latter, which represents a circular zone of light around the luminaire, is considerably greater.
Utilisation factors and room index
Where a general area has to be lit fairly uniformly over the working plane, as
opposed to situations where a considerable variation in illuminance may be permissible or desirable, it is usual to use the ‘lumen method of design’. In order to do
this, a ‘room index’ based on the proportions of the room has to be used.
Figure 18.8 makes it clear that in a tall, narrow room more light is absorbed by
the walls, assuming the same mounting height for the luminaires than in one of more
generous proportions. It must also be bore in mind that a glass roof can be considered as a black area, reflecting no appreciable light into the room, and that uncurtained windows must be regarded as absorbing areas too.
The formula for obtaining the room index is:
k=
LW
H m (L + W )
where L = length of the room (m)
W = width of the room (m)
Hm = mounting height of luminaires above the working plane (m).
The utilisation factor can then be obtained by reference to the photometric tables
published by the manufacturer using the room index and an average room
reflectance.
496
Handbook of Electrical Installation Practice
Fig. 18.8 Room dimensions affect illumination of room surfaces.
Spacing to mounting-height ratios
Where an array of luminaires is designed to give an even illuminance on the
‘working plane’, sometimes assumed to be 0.85 m above the floor, the recommended
spacing to mounting-height ratio (SHRMAX) shown in the data must not be
exceeded. This is S/Hm where S is the distance between fittings and Hm their mounting height above the working plane. Too wide a spacing will result in a serious falling
off in illuminance between the luminaires.
In practice, the number and spacing of the luminaires are often determined by
the ceiling height, the beam structure, or modular size of a suspended ceiling. The
recommended spacing can be exceeded if the luminaires are mounted above workbenches or rows of desks, but this presupposes a permanent layout which may not
be considered when the lighting scheme is designed.
Discomfort glare
Luminaires in a large room can be a serious source of direct glare, especially if they
contain fluorescent tubes and are mounted at right angles to the principal line of
view. Glare from luminaires can cause discomfort to people using and working in
an interior. This is known as discomfort glare. The CIBSE code gives limits to a glare
index. Luminaire data often include uncorrected glare indices for the luminaire
which after correction can be compared with the limiting value to establish whether
the luminaire is a suitable choice.
Lighting
497
Designing an installation
Lumen method of design
For hand calculations the lumen method of design is the easiest available and is
always recommended where the precise use of a room and dispositions of workbenches or desks are not known. It provides a general illuminance over the whole
of the working area and is generally employed in planning the lighting of speculative office blocks or factories where future requirements are not known.
After the task illuminance has been settled and the type of lamp and luminaires
decided on, the method starts with a simple calculation of the number of luminaires
required, based on the formula:
N=
E¥A
n ¥ UF ¥ F ¥ MF
where F = initial lumen output of the lamp or tube(s)
E = average maintained illuminance (lx)
A = area to be lit in (m2)
UF = utilisation factor
MF = the maintenance factor
N = number of luminaires required
n = number of lamps per luminaire.
With the introduction of maintained illuminance in the 1994 CIBSE Interior Lighting Code the maintenance factor is derived from four factors associated with the
lamp, luminaire and room surfaces. For a comprehensive explanation of the method
it is suggested that the Code is referred to.
The utilisation factor is derived from the photometric data provided by the luminaire manufacturer and a luminaire maintenance category may be provided. Lamp
data would be sourced from lamp manufacturers.
The value of N seldom comes out as a whole number and may produce difficulties
in the arrangement of the luminaires. In such a case, the smallest whole number of
these that can be installed at adequate spacing can be calculated from the formula:
L¥W
MS ¥ MS
where L = length of the room (m)
W = width of the room (m)
MS = maximum permitted spacing between luminaires.
Further modifications may be imposed by the beam structure of the room and by
obstructions in the space. The spacing to mounting-height ratio of the luminaires
should not be exceeded.
The final scheme must be checked for glare index, and if it falls outside the recommended limits, a type of luminaire with a lower glare index must be substituted
and the calculations repeated.
498
Handbook of Electrical Installation Practice
Low energy installations
The need to conserve electrical energy has led to Part L of the 1995 Building Regulations for England and Wales, which lays down a limit on the fuel consumed for
electric lighting in domestic and non-domestic buildings. The limit is expressed
in terms of the efficacy of the lighting circuits: ‘initial’ lamp lumens per ‘circuit’
watt.
Part L was amended from April 2002 as follows. Approved Document L1 states
that new dwellings must have efficient lighting (greater than 40 Lm/w) in a number
of rooms/locations, dependent on the total number of rooms (as defined in L1)
within the premises. This will require the use of linear or compact fluorescent
lamps.
Approved Document L2 includes a new method of calculation. It requires the
general lighting of office, industrial and storage premises to have an initial efficacy,
averaged over the whole building, of at least 40 luminaire Lm/w (luminaire’s light
output ratio (LOR) ¥ lamp circuit efficacy). Lighting controls are detailed and
methods of provision made for some easement (up to 25%) of the lighting efficacy
requirement when specified types of control are installed. Efficacy requirements in
other types of non-domestic buildings are satisfied if the average efficacy is not less
than 50 Lm/w, or at least 95% of the installed lighting capacity uses lamps with
circuit efficacies no worse than a stated list of lamp types. Display lighting is detailed
individually.
Lighting for visual display terminal (VDT) areas
Many people spend long periods of time using computers and display screens. The
provision of suitable conditions for these users is a matter of good sense and a legal
requirement as the EC Directive (90/270/EEC) for display screen equipment is now
law. Also, the Display Screen (VDU) Regulations 1992 are in force. These make it
a legal obligation for employers to fulfil minimum requirements to provide suitable
and adequate conditions for users of workstations with VDTs. The regulations
came into force on 1 January 1993 and apply now to all new or modified
workstations.
These regulations are deemed to have been met, as far as lighting is concerned,
if the advice in CIBSE Lighting Guide 3 (LG3) is followed. Options include direct
lighting (provided by an overhead lighting system where the brightness or luminance of equipment is limited above critical angles to the downward vertical),
indirect lighting (uplighting) or a combination of both.
The Society of Light and Lighting (SLL) has recently published an addendum to
the Lighting Guide 3: 1996. This specifies significant changes to the criteria requirements for direct lighting (recessed downlights/categorised louvred fittings) and
introduces a new certificate of conformity. For these the Categories 1, 2 and 3 have
been replaced with new maximum luminance limits. The limits are based on three
screen classes:
Class I (with good anti-reflective properties)
Class II (moderate)
Class III (poor)
499
Lighting
Table 18.6 New maximum luminance limits.
Screen type
class
Max. luminance cd/m2
Negative software
Max. luminance cd/m2
Positive software
≥65°
≥65°
I and II
III
1000 (Cat. 2.3)
200 (Cat. 2.1)
1500
500
≥55°
≥55°
I and II
III
1000 (Cat. 1.3)
200 (Cat. 1.1)
1500
500
Elevation
angle
The equivalent categorisations are given in brackets.
and LG3 for the UK includes relaxed limits for positive polarity software. The new
limits are applied at elevation angles of 65° and above and at 55° and above in
special circumstances, as shown in Table 18.6.
The luminaire should be chosen after consideration of the screen type and software polarity used in the areas. If the scheme designer is unable to obtain information about the display screens in use in the area, the fall back choice is a luminaire
with luminance limit of 200 cd/m2 at 65° (Cat. 2.1) or at 55° (Cat. 1.1) in special circumstances as is current practice. All the luminance limits are based on average
value at elevation angles radially around the luminaire, but with the patch measure
abandoned.
The new standard for direct lighting by downlights specifies additional quantified
criteria in terms of illuminance ratios. The average illuminance on the wall should
be at least 50%, and on the ceiling at least 30%, of that on the task. This means illuminance must be calculated not just on the work plane but also around the walls
and the ceiling. These ratios will require that the installation has a high reflectance
floor cavity 0.2 to 0.4 and walls 0.5 to 0.7, or will have to direct light onto ceiling
and walls – maybe by separate wall washers, uplights or direct-indirect systems.
There is no uniformity limit but in the spirit of the guide the odd splash of light onto
the walls and ceiling should be avoided.
The new LG3 requires that the scheme designer completes and signs a Certificate of Conformity.
EMERGENCY LIGHTING
Of all the uses to which lighting design can be put, the exercise of its skills in the
provision of suitable and efficient emergency lighting is perhaps the most important, as ultimately good emergency lighting can save lives.
But why should anyone bother to spend money on a lighting system that hopefully will never be used? Apart from the moral obligation that we have to the occupants of a building to ensure their safety, The Fire Precautions Act, The Health and
Safety at Work etc. Act and Building Regulations of 2000 make it obligatory to
provide suitable means of escape during an emergency, and lighting is obviously an
essential part of this requirement.
500
Handbook of Electrical Installation Practice
But what do we mean by ‘emergency lighting’? There are two types of emergency
lighting: escape lighting and standby lighting. Escape lighting is provided to ensure
the safe and effective evacuation of the building and has special requirements.
Standby lighting is provided to enable some activities to continue for a period
after the mains lighting fails, for example in a hospital operating theatre. Standby
lighting can be regarded as a special form of conventional lighting and dealt with
accordingly.
There are two main types of system available for powering emergency lighting:
self-contained or central. For the former, in the event of an emergency the luminaires operate from their own batteries. Each luminaire is fully equipped with
battery, charger, charge indicator and changeover device. This can be within the
luminaire of in a separate unit less than one metre from the luminaire. The normal
unswitched lighting circuit, which charges the batteries and provides mains failure
detection, is the only extra connection required for a self-contained emergency luminaire. With central systems, the power is provided by batteries or generators and
the output is distributed through sub-circuits to feed a number of slave luminaires.
These systems require comparatively large battery/generator rooms. Sub-circuit
monitoring is used to protect against local failure, and high integrity wiring must be
used between power source and luminaire. Due allowance must be made for voltage
drops.
Types of emergency lighting luminaire are classified according to modes of operation and duration. The battery is always being charged when the mains supply is
present.
Non-maintained
In this mode the lamp(s) is only lit when the mains fails and is
operated by an emergency power source.
Maintained
In this mode the lamp(s) is lit at all times. It is powered by the mains
supply under normal conditions and under emergency conditions operates
from an emergency power source.
Combined/sustained
This is a variant of the maintained luminaire in which one
lamp is powered by the mains supply during normal conditions. A second lamp
only operates under emergency conditions or by an emergency power source.
This type of luminaire provides light at all times.
Duration is the period that the emergency luminaire remains lit to the minimum
design output, after a mains failure. Various premises require different durations, as
set out in BS 5266, from 1–3 h.
The European committee CENELEC has published a common European standard, entitled ‘Lighting applications – Emergency lighting’ and dual numbered as
BS 5266 Pt 7: 1999/EN 1838: 1999. Major changes are as follows.
Emergency escape route illumination
On the whole there are two types of routes to be considered for the purposes of
escape lighting requirements:
(1) Clearly defined routes – corridors and gangways. Here the lighting should
ensure that the horizontal illuminace at the floor on the centre line of the escape
Lighting
501
route is not less than 1 lux and that 50% of the route width up to 2 m wide is lit
to a minimum of 50% of that value. Although the UK has a dispensation of
0.2 lux on those routes, this applies only to those that will be permanently unobstructed. In addition, hazards along the routes or special places need to be
emphasised to 1 lux; included are exit doors, changes of direction and level,
stairs, intersections of corridors, etc.
(2) Large open areas over 60 m2 – offices, supermarkets, dining halls, conference
rooms, laboratories, multipurpose rooms. These places will not have defined
routes and the layout of furnishing can change from time to time. To recognise
the increased difficulty in these spaces the illuminance at floor level over the
central core area should be at least 0.5 lux with a diversity of 40 : 1, but excluding the last 0.5 m to the wall.
High risk areas
In laboratories and certain control rooms or work places the activity may involve
hazardous tasks not dependent on electricity supply or may present a hazard if left
in operation. These need to be made safe before evacuating the area. In these situations the immediate area containing the task should be illuminated to 10% of
the required maintained illuminance for the task or 15 lux, whichever is greater,
with a uniformity not less than 0.1. To avoid panic, fast response of the emergency
lighting is important, therefore the lighting should provide illuminance within
0.5 seconds of the failure of the normal lighting.
Signage
Signage is an important element of emergency lighting. Standards are following the
pictogram route but without wording – that is, a man running towards a solid door
with a pointing arrow in-between. These are now essential for new buildings and
are gradually replacing the interim format, detailed in BS 5499, of the mixture of a
running man inside a box, arrow and text. Note that it is not permitted to have signs
of these two different formats in an installation. The old BS 5260 signs – the green
word ‘Exit’ on a white background – are now obsolete and should have been
replaced by the end of 1998.
CHAPTER 19
Mains Cables
G.A. Bowie, DFH, CEng, FIEE
S.E. Philbrick, CEng, MIEE
Revised by T.L. Journeaux, BSc
(Technical Manager, Pirelli Cables Ltd)
Mains cables are used to supply electricity to complete electrical installations and
as the electrical loadings of such cables must take account of the total loading of
the electrical installation, mains cables are generally of larger sizes than the wiring
cables dealt with in Chapter 20.
For most installations mains cables operate on low voltage, that is about 440 V,
but for very large installations, particularly where the site is extensive and large
loads are carried over long distances, mains cables operating at higher voltages are
used. In these cases the h.v. source might be provided from the public electricity
supply or from a private generating station on the site.
This chapter deals with systems for operating at voltages up to and including
11 kV and requiring conductor sizes generally larger than 16 mm2.
CABLE SPECIFICATIONS
All cables are fundamentally similar in that they contain conductors for carrying
current, insulation for surrounding the conductors and some form of overall covering having metallic and non-metallic components to provide mechanical and possible corrosion protection to ensure that the insulation may continue to operate
satisfactorily throughout the life of the cable once the cable has been installed.
The majority of mains cables used in UK industrial installations comply with British
Standards Specifications (BS) while those intended for use by the regional electricity
companies (RECs) are either covered by BSs or by standards issued by the electricity
supply industry (ESI), Electricity Association (EA) or individual RECs.
Table 19.1 lists the more important BS types dealt with in this chapter. All these
standards make reference to other BSs for the various materials and components
used in the construction of the cables.
British standards for electric cables are expressed in metric terms and wherever
possible they align with applicable internationally agreed standards. Such international standardisation includes harmonisation documents agreed by the European
Committee for Electrotechnical Standardisation (CENELEC) and publications
502
503
Mains Cables
Table 19.1 British Standard types of cables used for mains cabling.
Specification
Title
Voltage ranges
for mains uses
BS 4553-1
BS 4553-2
BS 4553-3
Single phase split concentric electric cables
600/1 000
BS 5467
Armoured electric cables having thermosetting
insulation
600/1 000
1 900/3 300
BS 6346
Armoured electric cables having PVC insulation
600/1 000
1 900/3 300
BS 6480
Impregnated paper-insulated lead or lead alloy
sheathed electric cables of rated voltages up to
and including 33 kV
600/1 000
1 900/3 300
3 300/3 300
3 800/6 600
6 600/6 600
6 350/11 000
8 700/11 000
8 700/15 000
12 700/22 000
19 000/33 000
BS 6622
Cables with extruded cross-linked polyethylene
or ethylene propylene rubber insulation for
rated voltages from 3 800/11 000 up to
1 900/33 000 V
3 800/6 600
6 350/11 000
8 700/15 000
12 700/22 000
19 000/33 000
BS 6724
Armoured electric cables having thermosetting
insulation and low emission of smoke and
corrosive gases when affected by fire
600/1 000
1 900/3 300
BS 7835
Armoured cables with extruded cross-linked
polyethylene or ethylene propylene rubber
insulation for rated voltages from 3.8/6.6 kV
up to 19/33 kV having low emission of smoke
and corrosive gases when affected by fire
BS 7870
l.v. and m.v. polymeric insulated cables for
use by distribution and generation utilities
Various parts
1 kV
6.6 kV
11 kV
33 kV
BS 7889
Single core unarmoured electric cables
having thermosetting insulation
600/1 000
3 800/6 600
6 350/11 000
8 700/15 000
12 700/22 000
1 900/33 000
504
Handbook of Electrical Installation Practice
prepared by the International Electrotechnical Commission (IEC). UK manufacturers, users and the electricity supply industry take an active part in the work of
international standardisation.
Following the publication of the EEC Public Procurement Directive (PPD), all
cables falling under its requirements have to be in accordance with harmonised standards. Thus the BS 7870 series, based on the PPD HDs, is being issued covering l.v.
and m.v. cables used for electricity distribution. These replace the existing standards
but do not introduce significant technical changes.
CABLE CONDUCTORS
Conductors for all voltage ranges covered may be of copper or aluminium. The
supply industry prefers aluminium for economic reasons in the context of large
quantities of cable. Although aluminium cables are lighter for equal current rating,
the copper conductor is smaller because of its better conductivity and is preferred
by the contracting industry because of its easier termination.
BS 6360, Conductors in insulated cables and cords, specifies the sizes and constructions of standard conductors used in a wide variety of cables but the individual cable specifications lay down particular requirements for each type of cable.
Copper conductors
Sizes larger than 16 mm2 are normally only of stranded construction. They are made
up from a number of smaller circular copper wires twisted together. The wires are
in the annealed condition to provide adequate flexibility to the cable to allow for
handling during installation.
Most stranded conductors are compacted by various means using wires of the
same or different size. The compacting process can be applied entirely to the outer
layer or partially to all layers. A smaller conductor diameter results from this –
approximately 8% reduction. The removal of the interstices between wires in the
outer layer reduces the penetration of material when an extruded insulation is
applied.
For multicore power cables, except in the case of smaller conductor sizes, stranded
copper conductors are shaped to result in the overall cable dimensions being
reduced, thus saving on materials and weight. Figure 19.1 illustrates how cable
dimensions are reduced by the use of shaped conductors.
Copper conductors are occasionally composed of tinned wires, the thin coating
of tin on each wire serving as a barrier to prevent chemical interaction between
certain constituents of elastomeric insulation materials and the copper of the conductor. Tinned copper conductors have a slightly higher electrical resistance than
plain copper wires.
Aluminium conductors
Solid circular aluminium conductors, because of the rather more ductile nature of
aluminium, can be used in sizes considerably greater than with solid copper but in
sizes larger than 300 mm2, the circular cross-section made up from four solid seg-
Mains Cables
505
Fig. 19.1 Cable dimensions reduced by shaped conductors.
ments, as shown in Fig. 19.2. This form of construction provides a conductor which
can be bent by normal cable handling techniques and is also within the handling
capabilities of cable manufacturing plant.
Where greater ease of bending is required, use is made of stranded circular aluminium conductors which are generally available in sizes up to 1000 mm2.
Solid shaped aluminium conductors provide a compact form of conductor for
multicore cables and are generally used in larger sizes up to and including 300 mm2.
Stranded shaped aluminium conductors provide rather more flexibility for
easier handling than solid shaped conductors but produce a cable having slightly
larger dimensions because small spaces exist between the wires of the stranded
construction.
While copper conductors for mains cables are produced from annealed copper
wire it is normal for aluminium conductors to have their individual wires in the
semihard condition before stranding.While fully annealed aluminium provides good
conductivity it is very soft and can create problems at conductor terminations of the
mechanical clamping type.
506
Handbook of Electrical Installation Practice
Fig. 19.2 Large solid circular aluminium conductor made from four segments, used in a
paper insulated and lead sheathed cable.
INSULATION
Conductor insulating materials used in cables operating at system voltages up to
and including 11 kV include impregnated paper, thermosetting synthetic insulation
and thermoplastic synthetic insulation.
Impregnated paper-insulation
Cables with impregnated paper have been used successfully since towards the end
of the 19th century and this form of insulation can provide a cable service life of
upwards of 50 years, some of the earliest power cables still being in service. BS 6480
is the most widely used standard for paper-insulated cables for industrial use and
gives constructional details and test requirements for a wide range of cables. For
new industrial installations, paper insulated cable types have been almost totally
replaced by the easier-to-use types employing extruded insulation.
Cable conductors are lapped with layers of thin narrow paper tapes to the
required total radial thickness. Cables for 11 kV operation have two layers of semiconducting carbon paper tape applied first to the conductor; this is known as conductor screening and its purpose is to reduce electrical stresses at the interface
between the outside surface of the conductor and the insulation.
Multicore belted cables have their cores laid up together, any spaces between the
cores being filled with paper or jute strings,with the whole assembly being lapped with
further paper tapes to provide the belt insulation. Cables for 11 kV operation include
a semiconducting carbon paper tape in the outer layer of belt papers for the purpose
of providing an equipotential screen for controlling electrical stresses and minimising
the effect of any gap occurring beneath the lead sheath during load cycling.
Single-core cables for 11 kV operation have the outer surface of the core insulation lapped with a screening tape, which may be semiconducting carbon paper or
metallised paper, or even thin copper or aluminium tape. This screening is for the
purpose of controlling electrical stress distribution. Three-core 11 kV cables can be
Mains Cables
507
of the ‘screened’ type where each individual insulated core is screened with metallised paper or non-ferrous metal tape and the whole assembly of laid-up three
cores is lapped with a binder of fabric tape incorporating interwoven copper wire
in order to ensure electrical contact between the screens of all cores and the overall
metal sheath. These copper-woven fabric tapes are also applied over the screening
of large single-core screened cables for the same purpose of maintaining good electrical contact between screen and metal sheath.
The paper tape insulation is dried under vacuum and heat to remove moisture
and is then impregnated with a special insulating compound based on oil. Conventional impregnating compounds were based on mineral oil containing about 20%
of rosin, the rosin making the compound viscous. Cables impregnated with such
compounds are entirely suitable in situations where the cable is laid in virtually
horizontal runs but they have the disadvantage of tending to drain to lower points
in runs where cables are laid vertically or on gradients. This results in higher parts
of the cable becoming partially drained of impregnated compound with a resultant
lowering of dielectric strength. Also, oil at lower levels tends to leak out of terminations or, at worst, can burst the metal sheath at the bottom of long vertical runs.
The most satisfactory solution for overcoming the drainage problems is to employ
compounds composed of mixtures of oils and microcrystalline waxes with other
substances which result in impregnating compounds which are virtually solid at the
normal operating temperatures of cables, yet are sufficiently fluid at the impregnating temperature during manufacture to allow the paper tapes to become properly saturated. Cables having this type of insulating compound are known as
mass-impregnated non-draining (MIND) types. While such cables present no
drainage problems over their range of normal operating temperatures, it has to be
appreciated that at excessive temperatures due to overloads the compound may
become sufficiently fluid to drain from higher to lower levels. Virtually all mains
cables with impregnated paper-insulation are of the MIND type.
Impregnated paper-insulation must be enclosed within a metal sheathing to
ensure that the insulation remains free from moisture. Ends must also be sealed
from the atmosphere with a metallic or adherent synthetic cap.
Thermosetting synthetic insulation
These insulations include ethylene propylene rubbers (EPR) and cross-linked polyethylene (XLPE). Such materials are applied to cable conductors by extrusion techniques while in a hot thermoplastic state and once on the conductor the materials
are subjected to a curing process which causes cross-linking of the molecules, resulting in a tough elastic material which does not soften again over the normal range
of operating temperatures of the cable conductor.
Both ordinary EPR and a tougher material known as HEPR are suitable for use
in cables having conductor continuous operating temperatures of 90°C and under
short-circuit conditions 250°C, as is XLPE insulation.
Ethylene propylene rubbers have excellent electrical properties, their good ozone
resistance making them suitable for high voltages. Like natural rubber, the material
burns and is not particularly oil resistant, therefore the insulated cable cores must
be provided with some form of external protection.
508
Handbook of Electrical Installation Practice
Before it is cross-linked, ordinary polyethylene has a somewhat sharp melting
point of around 100°C, so one of the important tests ensures that the XLPE removed
from the finished cable is properly cross-linked and is thus capable of withstanding
high temperatures resulting from short-circuit conditions. The requirements for
EPR and XLPE for m.v. applications are similar and are given in BS 6622, and those
for l.v. applications in BS 5467.
Ethylene propylene rubbers and XLPE will burn without releasing significant
quantities of corrosive gases and are suitable for use in low smoke halogen-free
cables.
For low voltages, both insulants will survive in wet conditions but EPR has the
better potential for survival at higher voltages should moisture come into contact
with the insulation, and is particularly favoured for submarine cable use.
Using the continuous vulcanisation (CV) process the insulation is applied by
extrusion which is followed by the passage of the insulated core through the section
of the manufacturing machine where the material is subjected to the cross-linking,
or curing, operation. Afterwards the insulated cores are assembled into complete
cables of the required design.
As the CV method of manufacture is a long length process, an alternative, more
flexible approach is to use the ‘Silane’ process where the cable is first extruded and
then cross-linked in a controlled ambient while still on the drum, which is then used
for the assembly of the cores into complete cables. This method is generally used
for l.v. cables, and sometimes for 11 kV cables.
For m.v. cables it is necessary for the electrical stresses at the inside surface of the
insulation adjacent to the conductor and at the outside surface of the core to be
carefully controlled so that no points of concentrated high stresses develop during
the operation of the cable. This screening is achieved by the use of layers of semiconducting materials immediately over the conductor and over the outside surface
of the insulated core, both layers being in intimate contact with the insulation.
Positive and efficient screening is achieved by extruding a thin layer of semiconducting rubber-like material over the conductor and also over the outside surface
of the core. These materials are applied on the same machine and at the same time
as the main insulation is extruded on to the cable conductor.
Thermoplastic synthetic insulation
For l.v. power cables polyvinylchloride (PVC) was the most widely used thermoplastic insulation, polyethylene being used infrequently and then only for high voltages. As already stated, polyethylene has a sharp melting point around 100°C and
is thus prone to cause failures where cable conductors exceed this temperature due
to overloads or short-circuits.
PVC compounds are composed of mixtures of the basic resin and plasticisers
together with small amounts of other compounding ingredients, such as fillers,
stabilisers, lubricants and pigments. The plastics technologist, by selection of
varying quantities of different ingredients, can produce a very wide range of
PVC compounds having an extremely wide range of physical and electrical
properties.
Mains Cables
509
PVC insulating compounds have excellent electrical properties suited to power
cables used up to and including 3.3 kV, but at higher voltages the material is not so
suitable, mainly because it has a relatively high dielectric constant and dielectric
losses become high. One electrical characteristic of PVC which is often not appreciated is the fact that its insulation resistance varies quite considerably with temperature. At 70°C a PVC-insulated cable has an insulation resistance some 700 to
1000 times lower than the value at 20°C.
Being a thermoplastic material, PVC is harder at lower temperatures and becomes progressively softer with increasing temperature. Unless PVC compounds
are specially formulated for low temperatures (it is possible to produce compounds
which can be bent at -40°C), it is usual to limit the temperature at which PVC cables
are bent during installation to about 0°C otherwise there is a risk of the PVC compound cracking.
The grades of PVC used for mains cables are designed for conductor continuous
operating temperatures of 70°C and under short-circuit conditions the conductor
temperature should never exceed 160°C, otherwise the core insulation would flow
and the cable would become permanently damaged.
When PVC is excessively heated the polymer suffers chemical degradation and
at continuous temperatures above about 115°C serious chemical break-down begins
to occur with corrosive hydrochloric acid forming in association with damp conditions. Standard PVC compounds are self-extinguishing when the source of ignition
is removed but the material will continue to burn when subjected to fire from adjacent burning material and noxious and corrosive gases are produced. Special PVC
compounds are available which have less tendency to burn and which produce lower
levels of corrosive gases.
While polyethylene is little used for power cables it may be noted that it burns
exceedingly well and, while burning, has the undesirable characteristics of dripping
burning molten material which can easily cause spread of fire. By incorporating
special additives into polyethylene the material can be made more flame retardant,
but these additives seriously affect the electrical properties, resulting in an insulation not much better than PVC.
PVC insulation is applied to cable conductors by means of extrusion at elevated
temperature and on leaving the extrusion die the hot material in a soft plastic state
is run through cooling water so that by the time the insulated core is wound on to
the collection drum the PVC has become sufficiently hard.
For reasons associated with the burning performance referred to above and the
higher operating and short circuit temperatures associated with XLPE and EPR,
PVC has been largely replaced by XLPE for l.v. insulation, although it is still widely
used as a sheathing material.
CABLE CONSTRUCTION
The manufacture of cable is carried out under carefully controlled conditions which
include quality control procedures on the individual constituents. All manufacturing lengths are subjected to the electrical tests required by the specification.
510
Handbook of Electrical Installation Practice
Impregnated paper-insulated cables with lead sheathing for l.v.
and m.v. applications
Paper-insulated cables to BS 6480 have a continuous sheathing of lead or lead alloy
applied over the assembled cores. Lead alloys have their compositions specified in
BS 801, Lead and lead alloy sheaths of electric cables, and for unarmoured cables
Alloy E or Alloy B are generally used. Both alloys are more resistant than lead to
the effects of vibration. Alloy B is used in cases where severe conditions of vibration are to be experienced. It may be noted that lead can develop a crystalline structure when subjected to vibration, and cracks can then develop through the wall of
the sheath on the cable with the ultimate result that moisture or water can enter
and cause electrical breakdown of the insulation. Armoured cables may have lead,
Alloy E or Alloy B sheaths.
The lead or alloy sheathing is generally provided with some form of outer protection. Single-core and unarmoured multicore cables are generally provided with
an oversheath of PVC or medium density polythene (MDPe) but the majority of
multicore cables are of the armoured type. Armour, for mechanical protection of
the lead sheath, can be in the form of double steel tape armour or wire armour.
Steel tape armour provides a certain degree of mechanical protection against sharp
objects penetrating the cable from outside and consists of two helical lappings of
tape, applied with gaps between convolutions, the outer tape covering centrally the
gaps in the underlying tape. The tapes are applied with gaps to allow bending of the
cable.
For protection giving longitudinal mechanical strength and a certain degree of
protection from penetrating objects, single-wire armouring is used, consisting of
a helical layer of galvanised steel wires. For additional longitudinal strength,
for example for cables which need to be suspended vertically, double-wire armouring, consisting of two layers of galvanised steel-wires, is applied, the outer layer of
wires being applied in the reverse direction from the inner layer. A separator of
waterproof compounded textile tape is applied between the two layers of wires to
allow the wires a certain free movement in relation to one another when the cable
is bent.
Armoured cables have a bedding applied first to the lead or lead alloy sheath
and this may consist of lappings of compounded paper and textile tapes, all adequately coated with waterproof compound, or if the cable is to have an overall
extruded PVC on MDPe sheath the bedding may also consist of an extruded
covering.
Unless cables are to be left with the wire armour in the bright condition, it is usual
for the armouring to have an overall protection in the form of serving applied in
the form of compounded textile tapes or as an extruded sheathing.
If single-core lead sheathed cables are required to be armoured for mechanical
reasons, the armouring must be composed of wires of non-magnetic material, such
as aluminium alloy, otherwise considerable electrical losses and heating effects occur
due to magnetic hysteresis in steel wires with alternating current loads of more than
about 50 A.
Cables to BS 6480 have been largely superseded by extruded insulation types,
particularly for l.v. applications.
Mains Cables
511
Impregnated paper-insulated cables with aluminium sheathing
for m.v. applications
Instead of a lead or lead alloy sheath for providing the moisture-proof covering for
protecting the impregnated paper-insulation, an alternative design uses aluminium
sheathing. Aluminium sheathing is mechanically tougher than lead and aluminium
sheathed cables generally do not require any further armouring for mechanical
protection.
Aluminium sheathing is also more rigid than lead sheathing and large diameter
cables having smooth aluminium sheaths are more difficult to handle during laying,
especially at bends. To overcome this problem corrugated sheathing is used, the
annular corrugations being formed after the sheathing has been extruded on to the
cable cores in smooth form. The result is a cable having equivalent bending performance to that of lead covered wire armoured cable. Figure 19.3 illustrates the
design of a PICAS (paper insulated corrugated aluminium sheath) cable to EA TS
09–12.
Should the corrugated sheath become damaged there could be the possibility of
moisture movement from the local damage moving along under the sheath, resulting in a long length of cable becoming unserviceable, so to avoid this possibility the
annular corrugations are substantially filled with a suitable compound. The quantity of compound has to be carefully controlled so that when the cable is operating
at its full load temperature the internal pressure within the sheath due to thermal
expansion does not create undue pressure.
Aluminium sheathing, whether smooth or corrugated, must be adequately protected from corrosion when laid in the ground and the usual protection consists
of a good coating of bitumen compound applied directly to the aluminium sheath
followed by an extrusion of PVC.
The above types of aluminium sheathed cables are generally used only on 11 kV
systems by regional electricity companies who have the necessary skills for installation of such cables.
CONSAC cables for l.v. CNE applications
Because aluminium sheathing provides a good electrical conductor there is one
type of cable which makes use of this sheathing as the neutral conductor. This is
CONSAC cable in accordance with BS 5593 (now withdrawn) which has been used
by some UK electricity boards for l.v. mains. The word CONSAC is derived from
‘concentric aluminium cable’. Figure 19.4 shows the general construction which consists of three shaped aluminium conductors for the three phases, each paper insulated and then having an overall belt, the whole insulation being impregnated with
non-draining compound, then encased in a smooth aluminium sheath which is
liberally coated with bitumen compound and finally sheathed overall with PVC.
As with all aluminium sheathed cables, the bitumen compound shall adhere to
both sheath and PVC.
CONSAC cables were used in systems where it is permitted to employ combined
protective and neutral conductors (CNE). One advantage claimed for CONSAC
cables over other CNE types having extruded synthetic insulation is that should the
512
Handbook of Electrical Installation Practice
Fig. 19.3 6350/11 000 V PICAS paper-insulated cable with corrugated aluminium sheath
(Pirelli Cables Ltd).
aluminium sheath become corroded there is every possibility that the cable insulation would fail because of ingress of moisture through the corroded sheath and
the circuit protection would isolate the cable long before the neutral conductor
became completely corroded away with the loss of the earthing connection. Other
types of CNE cables could lose their neutral and earth continuity yet would still
provide the phase voltage and thus could present a hazard to the electricity
consumer.
CONSAC cables were made in sizes up to and including 300 mm2 but their stiffness meant they were difficult to handle. The procedure for cutting the sheath to
open a flap was also difficult and this design has now been replaced by alternative
CNE types of the wavefrom design.
Mains Cables
513
Fig. 19.4 600/1000 V CONSAC cable (Pirelli Cables Ltd).
Cables with thermosetting insulation for m.v. applications
Cables with EPR and particularly XLPE insulation are replacing impregnated
paper-insulated cables because of easier handling and terminating techniques.
A typical 11 kV three-core cable is shown in Fig. 19.5. This has heavily compacted
stranded aluminium conductors with semiconducting screening and extruded EPR
insulation. The insulated cores are covered with semiconducting material or lapped
with metal tapes in order to ensure longitudinal electrical continuity. The three
screened cores are laid up together, filled circular, then wire armoured and sheathed
overall with PVC. This, and other designs for industrial use are covered in BS 6622.
A similar range of cables, but having low emission of smoke and corrosive gases
when affected by fire, may be found in BS 7835.
Similarly, the RECs are increasingly using designs of m.v. cables with XLPE and
EPR insulation, in place of the paper insulated designs historically used. These
designs are either of single core or three core construction and utilise a copper
514
Handbook of Electrical Installation Practice
Fig. 19.5 Elastomeric cable for 6350/11 000 V operation (Pirelli Cables Ltd).
wire screen over the insulated core, or collectively over the laid-up cores on a three
core design. The sheathing material generally specified is medium density polyethylene (MDPE) as this offers good robustness, suitable for installation directly in the
ground or pulled into ducts. These designs, for REC use, are covered in BS 7870.
Waveform cables for l.v. CNE applications
As an alternative to CONSAC cables extensive use was made in electricity distribution at low voltages of Waveconal cables to ESI Standard 09–9, which have solid
shaped aluminium conductors insulated with XLPE. The three-phase cores are laid
up together and lapped with an open spiral of clear plastic tape.The assembled cores
Mains Cables
515
Fig. 19.6 600/1000 V Waveconal cable (Pirelli Cables Ltd).
are then covered with an extrusion of rubber-like material which acts as a bedding
for the concentric neutral conductor, and the same material also completely covers
the wires of the neutral conductor.
The aluminium wires forming the neutral conductor (Fig. 19.6) are applied in an
oscillatory manner instead of in a helical form and this enables the cores to be
exposed when making tee-joints under live conditions without the need to cut the
neutral wires, and thus break the return path of the combined protective and neutral
conductor of a TN-C-S system.
The aluminium neutral wires are carefully segregated so that they are individually surrounded by the rubber-like filling material in order to prevent moisture
transference around the neutral in the event of mechanical damage.
The cable is finally sheathed with PVC to provide mechanical protection to the
rubber-like covering around the neutral wires.
516
Handbook of Electrical Installation Practice
A similar construction of cable (copper waveform) is available which uses copper
wires forming the neutral conductor and is particularly used where there are concerns of possible corrosion of aluminium wires. This design has largely superseded
the Waveconal type.
Cables with synthetic thermoplastic insulation (PVC) for l.v. applications
Many low-voltage cables in and around buildings have PVC insulation, and BS 6346,
PVC-insulated cables for electricity supply, fully specifies a large range of cables
having both copper and aluminium conductors, with armouring.
For vertical risers and some submains, single-core unarmoured designs would be
used but in general it is more normal to employ wire armoured or aluminium strip
armoured cables for the mains supply.
All the cables in BS 6346 have their PVC insulation applied to the copper or aluminium conductors by extrusion; multicore cables with shaped conductors have
their insulation applied in sectoral shape so that the complete cable is compact and
thus overall dimensions are kept to a minimum. Figure 19.7 shows examples of
cross-sections of typical solid sector-shaped aluminium conductor cables.
Cables have a bedding for the armour of either an extruded covering of PVC or
a lapping of two or more plastic tapes.
Armouring on copper conductor and some aluminium conductor cables consists
of a conventional layer of galvanised steel wires, although single-core cables, requiring armouring, have wires of non-magnetic material if the cables are to be used in
a.c. circuits.
Aluminium conductor cables can also have aluminium strip armouring, consisting of a single layer of aluminium strips. This form of armouring is useful where low
armour resistances are required; aluminium strip armouring has a much lower resistance than galvanised steel wire armouring. For smaller cables the strip armouring
resistance is approximately half that of steel wire while for larger sizes the aluminium strip has only one quarter of the resistance.
All BS 6346 cables have an overall extruded sheathing of PVC.
Cables to the above specification are also available for operation on 3.3 kV circuits. Such cables are similar to those for use at l.v. but the thickness of core insulation is somewhat greater. At 3.3 kV there is no necessity for conductor or core
screening as is required for higher voltage cables.
Concentric neutral-and-earth service cables are made in a variety of combinations having copper or aluminium phase conductors and concentric neutral conductors of aluminium or copper wires. These cables are generally not used in sizes
greater than 35 mm2 and can have one or three phase conductors.
Where a concentric cable is required with separate neutral and earth-continuity
conductors, there is a design available in accordance with BS 4553 or BS 7870. These
cables, in sizes up to and including 35 mm2, have the central circular stranded copper
phase conductor insulated. The neutral conductor is made from a number of single
copper wires, each covered by an extruded layer to a diameter the same as the wires
forming the earth-continuity conductor.
For new installations, cables with thermosetting insulation to BS 5467 or BS 6724
has largely replaced the BS 6346 types.
Mains Cables
517
Fig. 19.7 Cross-sections of typical 600/1000 V solid aluminium conductor PVC-insulated
cables.
Cables with thermosetting insulation for l.v. application
BS 5467 provides requirements for wire armoured cables having EPR or XLPE
insulation for operating at voltages up to 3.3 kV. The specification covers a wide
range of conductor sizes in both copper and aluminium conductors. As well as wire
armouring composed of circular wires the specification also includes aluminium
strip armour consisting of a layer of strips of fairly hard aluminium. The bedding
under the armour and overall sheath are of a grade of PVC suitable for the 90°C
operating temperature.
518
Handbook of Electrical Installation Practice
BS 6724 gives requirements for a range of cables similar to those in BS 5467, using
the same insulation materials but special sheathing materials such that the cables
have low emission of smoke and corrosive gases when affected by fire. Modern low
smoke sheathing materials have mechanical properties similar to PVC and so the
cables may be handled and installed in a similar manner to their PVC sheathed
equivalents.
Concentric service cables
Concentric neutral and earth service cables are manufactured with PVC or thermosetting insulation and with standard or low smoke halogen-free reaction to fire
properties.A range of single phase split concentric designs for industrial use are given
in the BS 4553 series, while designs for REC use are given in Part 3 of BS 7870.
The earth-continuity conductor wires are bare and not individually covered.
The covered neutral wires and the bare earth-continuity wires are applied around
the central phase core as a concentric layer, the neutral wires being together as a
band and the earth-continuity wires as a separate band. String separators, about the
same diameter as the bare copper wires, are laid either side of the group of earthcontinuity wires to separate the group from the covered wires forming the neutral
conductor.
A binder of non-hygroscopic tape is applied immediately over the concentric
layer and the whole assembly is sheathed with PVC.
There is now a marked preference for XLPE as an insulation instead of PVC for
a wide range of l.v. cables. While the dimensions and handling characteristics of
both cables are similar, XLPE has a much better rating for continuous, emergency
and short-circuit conditions. Even when these are not required, the margin of safety
is enhanced compared with PVC.
INSTALLATION
General care in handling
Cables can be perfectly manufactured and meet all the required specification tests
at the cable factory and then be made unfit for service if not handled with care
during installation.
Unlike building wiring cables, mains cables are generally large and are on heavy
drums, so in designing an installation careful thought must be given to the method
by which the drum of cable is to be delivered to site and removed from the delivery vehicle. Dropping a drum of cable from a lorry tail board not only causes
possible damage to the cable but can cause collapse of the wooden drum and
subsequent severe damage to the cable when attempting to remove the tangled
turns from the broken drum.
If drums of cables have to be rolled any distance over the ground the battens
should be left in their fixed position so that some protection can be given to the
outside turns on the drum. Many cables have been damaged by rolling over a
removed batten on the ground with the sharp ends of the nails pointing upwards
and penetrating the cable passing over it.
Mains Cables
519
Where drums are rolled it is important that the direction of rotation should be in
accordance with the arrow on the side of the drum. If this is not observed the turns
of cable on the drum can work loose and very large longitudinal forces set up which
either push the inner end out of the flange or, if it is rigidly secured, may damage
the cable itself.
When pulling a cable off a drum a spindle of adequate size and strength should
pass through the central holes in the flanges and proper drum jacks should be used
to support the spindle. A person should be stationed at the drum position to stop
the drum unwinding as soon as cable pulling is stopped, otherwise the drum can
overrun and a damaging kink form in the cable when it becomes bent too sharply.
With long pulls, especially with heavy cable and also where straight-pulls are not
possible, cable rollers should be placed at frequent intervals to support and guide
the cable. Care should be taken to ensure that the cable runs in the centre of each
roller and does not become wedged at roller edges.
Where cables are cut or where factory seals are removed during the laying
operation, the exposed ends should be quickly sealed.This applies not only to impregnated paper insulated cables which are quickly damaged by ingress of moisture but
to all types of insulation. If cut ends are left exposed to the elements, or worse, left in
the ground, water can penetrate even along elastomeric and thermoplastic cables,
leading to untold problems later during jointing or terminating operations.
Methods of installation
The method of installing a cable obviously depends on where the cable has to run
but the shortest route is not necessarily the most economic route. Rocky ground
can be expensive to excavate and corrosive ground can call for expensive anticorrosion finishes to the cable.
Conventional methods of installing mains cables are: laid direct in the ground;
pulled through ducts in the ground; laid in troughs; or installed in the air on supports such as cable trays or cable ladders.
Laying cable directly in the ground involves expensive excavation and cables must
be laid at a sufficient depth to ensure that no disturbance or damage to the cable can
take place under normal circumstances.The soil immediately around the cable should
contain no sharp stones or similar objects; ideally it should be sifted. In order to
comply with the IEE Wiring Regulations (BS 7671) cables buried in the ground should
be marked with tiles or by some other suitable means so that persons excavating
the ground later have some warning of the presence of the cable before reaching it.
If several cables are laid side by side in the trench the spacing between them
should be carefully maintained, otherwise their current-carrying capacities may be
seriously affected.
Cable trenches should be filled in again as quickly as possible after cables have been
laid in order to reduce possible damage to the cable at the bottom of the trench.
Where cables pass under busy roads it is useful for ducts to be used, spare ways
being left so that additional cables can be later drawn through without the need to
excavate the road again.
Where cables are laid in troughs thought has to be given to the possible effects
of adding more cables at a later date, as these can adversely affect the current ratings
of all the cables.
520
Handbook of Electrical Installation Practice
Cables installed in air must be supported at intervals sufficiently close so that no
mechanical strain is exerted on them. Cable manufacturers are able to give necessary guidance. Where cables are run on trays or cables ladders the positioning of
the trays or ladders requires careful consideration as they are often used by other
trades for walking on to gain access to adjacent areas, and the cables can become
damaged.
The installation of single-core armoured cables requires care because generally
there is a considerable current circulating in the armouring. The rating of the circuit
depends on how the cables are laid, i.e. in trefoil, flat touching or flat separated. The
use of two cables per phase is not unusual and these should be laid in accordance
with the manufacturer’s instructions to avoid overheating within a cable or at the
terminations.
For all methods of installation, cables should not be bent in radii close to terminations less than those given in the manufacturer’s recommendations, but during
the actual operation of pulling the cables into position every effort should be made
to ensure that cables are only bent into somewhat large radii.
In cold weather conditions cables having PVC components should not be installed
when the cable or ambient temperatures are at 0°C or lower. Installation should not
commence until the temperature has been above 0°C for at least 24 h unless the
cable can be stored in a warm atmosphere to ensure that it is well above freezing
point and it can be taken out and laid quickly. In freezing conditions there is a
chance that the PVC may shatter. The same care must be taken with any cables
having bituminous compounded coverings because these also can crack.
Precautions against spread of fire
In all installations precautions should be taken to ensure that cables cannot spread
fire. Where cables pass through walls or partitions the holes should be made good
with fire-resisting material.
Where vertical risers pass upwards through floors, fire barriers must be fitted at
each floor. Not only does this restrict spread of fire but alleviates a build-up of heat at
the top of the cable run, which would otherwise affect the current rating of the cable.
Where cables run together in large groups there is always a risk that one burning
cable may ignite adjacent cables and eventually the whole group can be involved in
a major cable fire. Special PVC compounds and compounds having low emission of
smoke and corrosive gases, having better flame-retardant properties than standard
grades, are available for cables in fire risk areas.
Cables without continuous metal sheathing should not be run in ground liable to be
saturated with hydrocarbons, such as from the petrochemical industry, because some
liquids, while not attacking PVC and some other elastomers, are able to penetrate
through cable coverings and insulation and flow along the cables into switchgear
and apparatus to which the cables are connected, thus creating a dangerous fire and
explosion risk. Where cables have to be run through such ground the cable design
should include a lead sheathing as this is impermeable to such liquids. Precautions
might have to be taken to protect the lead sheath from corrosion.
Problems with electric cables involved in fires have led to several improvements
in cable design and their all-round fire performance. The first of these involved
Mains Cables
521
fire propagation to avoid the effects arising from bunches of cable installed close
together. BS EN 50266 (formerly BS 4066–3) specifies test methods for various
levels of cable loading known as Categories NMV 7 (A), NMV 3.5 (B) and NMV
1.5 (C) and should be invoked where the possibility of fire propagation exists.
Secondly, the location of the fire source, escape and fire fighting are greatly
hampered by smoke, and the presence of corrosive gases in the smoke can result in
damage to electrical equipment and structures as well as being injurious to the
health of personnel. Cables having low emission of smoke and corrosive gases when
affected by fire are widely available and overcome these problems. Test methods for
smoke emission and corrosive gas emission are given in BS EN 50268 (formerly BS
7622) and BS EN 50276 (formerly BS 6425) respectively.
JOINTING AND TERMINATING
Jointing and terminating mains cables of any type involves making adequate electrical connections to conductors, ensuring continued satisfactory functioning of the
cable insulation and providing adequate electrical continuity to the metal sheath,
armouring or other metallic covering.
Conductor connections
Any joints or terminations in conductors must be capable of carrying any load
current to be expected during the life of the cable and also very heavy currents
which may occur as a result of faults and short-circuits. All conductors expand when
they become heated by the passage of currents and contract when the current is
reduced or removed. This expansion and contraction is both longitudinal and radial;
thus cable conductors become longer when hot from the passage of the normal load
current and much longer from the passage of short-circuit currents. On cooling, the
conductor tries to return to its original length. These longitudinal movements can
create considerable forces which must be taken into account in joint and termination design.
The radial expansion and contraction has to be accommodated in the device for
making the electrical connection to the conductor; the electrical resistance of the
connection must remain very low throughout the life of the connection and this
requires that the conductor metal must remain in constant intimate contact with the
connecting device at all times. The passage of current through any increased resistance will result in the generation of additional heat which may lead to the ultimate
failure of the connection and its insulation.
For copper conductors soft-soldering into lugs or ferrules has been the traditional
method for terminating or jointing for many years and is still considered the most
reliable method when properly carried out but it involves the use of heat and certain
skills. The alternative is to use crimping methods where lugs or ferrules having
sufficient wall thickness are compressed, usually by hydraulic means, on to the conductor. Many designs of compression-type joints are available but the user should
always first ensure that the one selected has been fully type tested under all conditions. The most reliable tools for undertaking the compression operation are those
522
Handbook of Electrical Installation Practice
which cannot be removed from the joint until the pressure device has travelled the
whole distance of its compression stroke. In all cases the sequence of operations
recommended by the manufacturer must be followed.
Aluminium conductors can be soldered; there are satisfactory solders and fluxes
available from a large number of sources, but such soldering requires more skill than
for copper conductors. It is well known that aluminium develops a thin oxide layer
on its surface which is difficult to break down and therefore special techniques are
necessary in order to obtain satisfactory alloying between the aluminium and the
solder. In the case of stranded conductors it is not only necessary to make a good electrical connection to the outside layer of wires but the inner layers in large strands must
also be jointed so that they may carry their full share of the load current.
The jointing of solid aluminium conductors is more usefully undertaken by crimping methods, using specially designed hydraulically operated tools. Again, only
systems which have satisfactorily withstood type tests involving long-term cyclic
testing, should be used.
Mechanical connectors using a clamping screw or bolt are used for both copper
and aluminium over a wide range of conductor sizes. The need for the application
of a correct torque is particularly important for aluminium conductors and this has
led to the development where the clamping screws are designed to shear at predetermined torque levels.
The much wider use of thermosetting insulants having much higher temperature
capabilities has reduced the use of soldering techniques owing to their restricted
temperature range.
Insulation at joints and terminations
Impregnated paper insulated cables must have their insulation protected from
ingress of moisture, and conventional joints involve making good the insulation over
the conductor joints by lapping with impregnated paper tapes then enclosing the
whole joint in a metal sleeve which is plumbed or soldered to the ends of the existing metal sheathing, the whole sleeve then being filled carefully with special compound which is generally poured in hot. Conventional terminations are dealt with
in a similar manner, the end of the cable being enclosed in a suitable case which is
filled with special compound to maintain it air- and moisture-tight.
These conventional methods have withstood the test of time, but changes in
switchgear and transformer cable boxes and changes in cable design have resulted
in the rapid growth of ‘dry’ terminations and joints, particularly for m.v. cables.
Terminations of paper insulated cables are now ‘sleeved’ either with heat shrink or
cold shrink techniques. These sleeves are fitted on to an extended crutch cap for 3
core cables and, where the cable has a screened insulation, an additional stress
control tube is also applied. The heat shrink materials must be adequately and
evenly heated while the cold shrink technique involves no heat but utilises expanded
tubes on removeable carriers. A typical termination is shown in Fig. 19.8.
These features can also be applied to straight-through and other joints for paper
insulated cables. While acrylic or polyurethane resin is widely used, the more
modern sleeved type of joints are becoming popular. Resin joints have a shelf-life
limitation and may be affected by ambient temperature. While the principle is
simple, the mixing of resin and hardener must be undertaken conscientiously and
Mains Cables
523
Fig. 19.8 Outdoor termination with cold shrink protection for 11 kV polymeric- and paperinsulated cables (Pirelli Cables Ltd).
the pouring must ensure that no air bubbles exist as these become potential breakdown areas. Adhesion to the cable sheaths is essential to prevent the entry of moisture and, in addition with polymeric m.v. cables, good adhesion to the core insulation
is essential to avoid introducing a breakdown path under the influence of lightning
impulse voltages. Figure 19.9 shows a typical profile of a modern straight-through
joint in an 11 kV polymeric insulated cable.
Low voltage polymeric cables having EPR, XLPE and PVC insulation can have
their outer coverings just trimmed back for sufficient distance to ensure no surface
tracking at terminations and there is no need for the ends of the cores to be enclosed
in any sort of compound in normal dry situations. At joints for these l.v. cables it
is necessary to seal the jointed cores from ingress of moisture from the ground in
the case of buried joints and the usual manner is to enclose the whole joint in
524
Handbook of Electrical Installation Practice
Fig. 19.9 Typical profile of modern straight through joint in 11 kV polymeric-insulated
cables (Pirelli Cables Ltd).
compound or resin. In pouring hot compound into PVC cable joints the temperature of the compound must not, of course, be so high as to cause softening of the
insulation. As with paper insulated cables, polyurethane and similar resins must be
mixed and poured so that no air bubbles remain after the material has hardened.
Medium voltage polymeric cables normally have a screen around each core consisting of a non-metallic and a metallic part.The former is generally an extruded layer
of semiconducting material which is designed to be stripped in the cold condition with
the assistance of specialised tools which are commercially available. Removal of the
screen is a critical step in jointing, especially where a knife is used. It is useful to practise stripping the screen from a scrap end of the cable before actually jointing.
At the point where the screens are removed from the core an area of high
electrical stress exists, requiring special precautions. To overcome these problems,
Mains Cables
525
stress-relieving devices are applied. They may be in the form of a moulded cone,
heat-shrinkable or cold-shrink tubes.These devices must be carefully fitted to ensure
that no air pockets exist in the area of high stress.
Continuity of metal sheath or armouring
The metal sheath, armouring or other metallic covering of any cable must be capable
of carrying fault currents which may flow through it and where such metal is relied
on as an earth-continuity conductor it must provide a low resistance path at all times.
This means that at any joints or terminations the continuity must be efficiently maintained throughout the life of the installation.
Over the years conventional joints and terminations with paper insulation have
proved satisfactory because the metal sheathing has been plumbed or soldered to
whatever it is connected and armour wires have been adequately connected into
massive metal joint box enclosures or glands. With the advent of more modern jointing techniques the continuity of metal sheathings and armouring has depended
more on various forms of metal clamps. Tests with overload and fault currents and
with cyclic loadings, also under damp corrosive conditions, have been conducted on
many new designs of jointing methods for metal sheaths and armour wires and many
have been found to be unreliable, developing into high resistance connections with
passage of time.
Before any jointing or terminating methods are selected for use in a particular
cable installation, the suppliers of the system should be requested to produce evidence to show that the technique for providing continuity has satisfactorily withstood appropriate tests when used in conjunction with the particular type of cable
to be installed.
In general, for resin-type joints, armour wires are best connected from one side
of the joint to the other by means of crimped joints, a bunch of wires from one side
being carried over and joined by a crimped ferrule to a bunch of wires from the
other side.
At terminations the wire armouring or metal strips of polymeric cables are most
efficiently secured in glands to BS 6121, Mechanical cable glands. This standard
covers a wide range of glands and the correct type for a particular cable must be
selected. It is important that full details of the cable to be accommodated are stated
at the time of ordering.
Copper wire screens are a common feature with m.v. extruded cables. When
bonding them at joints or terminations, it is usual to twist them into a pigtail with
a crimped connector, but in areas of high ambient temperature this could become
a hot spot unless additional copper wires are inserted.
In corrosive conditions all types of metal sheath, armour and metal strip connections should be well encased in suitable material to reduce risk of corrosion of
the electrical connection.
CABLE RATINGS
The passage of current through a cable conductor raises its temperature. In the case
of sustained current an equilibrium is eventually established and the heat generated
526
Handbook of Electrical Installation Practice
Table 19.2 Temperature limits of mains cable insulants
* 60°C for unarmoured lead sheathed cables laid in ducts.
†
50°C for unarmoured lead sheathed cables laid in ducts.
is equal to the heat dissipated through the insulation, sheathing and other coverings
and finally into the surrounding ground or air. The highest value of current a cable
can carry continuously depends on the highest safe operating temperature applicable to the insulation or other parts of the cable. Table 19.2 gives the maximum
temperatures for continuous operation for a range of insulants and these values are
used for the calculation of sustained current ratings.
Current ratings may be determined from practical field tests for and size and type
of cable installed in a particular manner by making sufficient temperature measurements at appropriate values of current in association with relevant ambient temperature conditions. Alternatively, ratings may be calculated from first principles or
may be more easily obtained from published tables.
Methods for calculating ratings have been standardised on a world-wide basis and
are given in IEC Publication 287, Calculation of the continuous current rating of
cables (100% load factor). In order to calculate current ratings one must have
detailed information of the cable construction as dimensions and properties of the
components enter into the calculations.
The usual method is to obtain ratings from published tables which cover standard
cable types and cater for a variety of installation conditions. For l.v. cables the tables
of current ratings included in BS 7671 (IEE Wiring Regulations) relate generally to
cables installed above ground and mostly in air. These ratings are based on an
ambient air temperature of 30°C. Ratings for power cables are provided in more
detail in the 69–30 series of reports issued by ERA Technology Ltd and cover installation methods for cables in the ground, in underground ducts and in air. These
ratings are tabulated for a standard ground temperature of 15°C and an ambient
air temperature of 25°C; the different air temperature results in slightly different
tabulated current ratings from the IEE values. Factors in both documents allow
adjustments to be made for particular ambient temperatures.
Current rating tables are also included in catalogues of many cable makers.
In using published ratings tables it is most important to take cognisance of all the
notes and footnotes in order that the correct factors are applied to the standard
ratings to take account of the actual installation conditions. In particular, attention
must be paid to the temperature of the surroundings in which the cable is to be
installed, the precise method of installation and the effects of grouping.
Mains Cables
527
If the temperature of the air or the ground surrounding the cable is higher than
the standard value appropriate to the published rating, the temperature-rise applicable to that rating would result in the cable conductor temperature exceeding the
maximum permitted operating temperature for the conductor insulation. For this
reason the rating must be reduced by the application of the appropriate factor. Only
in cases where it can safely be assumed that the surrounding temperature will always
be lower than the standard value is it possible to take advantage of a slight increase
in rating.
The manner in which a cable is installed in relation to its surroundings and any
other cables affects its ability to dissipate heat. For this reason the factors appropriate to such matters as depth of laying, grouping and type of soil, must be applied
to the published ratings.
For cables laid in the ground the ERA reports provide tabulated ratings based
on a solid thermal resistivity of 1.2°C m/W which can be a fair average value for
much of the UK, but the type of soil affects its thermal resistivity considerably and
it is strongly recommended that the information regarding different types of soil
provided by ERA is studied. In some areas of the world very dry conditions for long
periods can result in high values of soil resistivity which can reduce the safe ratings
of cables.
Care should be taken when selecting the conductor size for medium voltage cables
as the smallest possible size does not necessarily provide the lowest system cost. This
is due to the cost of I2R losses when they are used to evaluate a system cost.
TESTING AND FAULT FINDING
After mains cables have been installed, jointed and terminated they should be subjected to electrical tests to ensure that they have not become damaged and that
joints and terminations have been properly made.
The essential test is a h.v. test which is more conveniently carried out with d.c.
than a.c. as long lengths of cables having high capacitances would require an unacceptably large size of testing transformer for a.c. tests (due to the high charging
currents involved).
Table 19.3 shows the values of applied voltages which should be increased
gradually to the full value and maintained continuously for 15 minutes between
Table 19.3 Test voltages for cables after installation.
528
Handbook of Electrical Installation Practice
conductors and between each conductor and sheath. No breakdown should
occur.
The test voltages given are intended for cables immediately after installation and
not for cables that have been in service. When testing is required for cables that
have been in service, the cable manufacturers should be consulted for appropriated
test conditions which will depend on the individual circumstances. A lower voltage
should be applied taking in account the age, environment, history of breakdowns
and purpose of the test.
If switchgear or other apparatus cannot be disconnected from the ends of the
cable during the test, the value of test voltage must be the subject of agreement with
all parties concerned.
During the testing period special precautions must be taken to keep all persons
away from any exposed parts which may be charged at the high voltage.
If cables with special anti-corrosion sheathing have been used and it is thought
that the sheathing could have become damaged during cable laying operations it is
sometimes beneficial to apply a voltage test between the cable sheath and the
ground before the cable is terminated. The value of test voltage should be no more
than 4 kV per mm of oversheath thickness, with a maximum value of 10 kV applied
for 1 minute.
If a cable should break down as a result of h.v. testing, the position of the breakdown must obviously be found so that a repair or replacement can be carried out.
If the test set can provide sufficient power the fault can often develop into a low
resistance path which may be located after the removal of the h.v. by conventional
methods using resistance bridge techniques. More often than not, the fault of high
resistance remains, which can involve problems of location. Sometimes the position
of the fault can easily be detected by ear if the test voltage is left connected, preferably at a lower value than the full test value.
Various makes of sophisticated fault location gear are available for finding high
resistance faults and most cable manufacturers offer a fault location service.
One quite effective method is to charge a large capacitance by the h.v. test set
through a resistance and then discharge it into the faulty cable core through a spark
gap. The voltage and size of spark gap are arranged so that the capacitor discharges
every few seconds. By walking along the cable the position of the fault can usually
be heard as the insulation breads down each time the capacitor discharges. A stethoscope, consisting of microphone, amplifier and earphone, is useful for detecting the
fault position in buried cables.
CHAPTER 20
Selection of Wiring Systems
R.G. Parr, ACGI, CEng, MIEE
(Consultant)
D.W.M. Latimer, MA(Cantab), CEng, MIEE
(Consulting Electrical Engineer)
Revised by M. Coates, BEng
(ERA Technology)
INTRODUCTION
This chapter deals with the selection of wiring systems for voltages up to and including 1 kV. It provides a survey of the more frequently used systems and comments
on the electrical and environmental duties for which each is suitable. Systems for
alarm and control circuits are included.
BS 7671, Requirements for electrical installations (the IEE Wiring Regulations)
requires at clause 512–02–01 that every item of equipment shall be suitable for the
design current and the current likely to flow under abnormal conditions. The term
equipment includes wiring systems. Clause 311–01–01 goes on to say that in determining the maximum demand of an installation, diversity may be taken into account.
The starting point for selection is an assessment of the load, considering both the
number, location and size of power consuming outlets, required to fulfil the purpose
of the installation, and the total load to be taken from the supply. Guidance on the
determination of maximum demand from connected loads in domestic and commercial installations is given in the IEE Guidance note No. 1 to BS 7671; the guidance given is of a general nature and experience of particular types of equipment
and of installations may allow the designer to adopt different values. For industrial
installations, methods used to establish demands differ with the type of industry and
must be based mainly on past experience with particular industrial processes.
Once the expected maximum demand has been determined, a meeting with the
supplier can decide the type of supply, earthing arrangements and the prospective
fault-currents at the origin of the installation. This information will have an important bearing on the selection of wiring system(s) for the installation.
Division of the installation into circuits and the routing of each circuit are matters
which concerns both safety and convenience.Attention is drawn to the requirements
of BS 7671: Part 3, Assessment of general characteristics, which are relevant at
this stage.
529
530
Handbook of Electrical Installation Practice
Some types of circuits such as emergency lighting and fire alarms have particular
requirements for wiring systems laid down in standards, see BS 5839 and BS 5266,
and are also required to be segregated.
When the number of circuits, loads, routes, lengths and environmental conditions
have been decided, consideration can be given to selection of appropriate wiring
systems.
Fuses or circuit-breaker ratings are initially selected on the basis of the load which
the circuit is designed to carry. There are situations in which the fuse rating is
selected on the basis, not of the load in the circuit, but of the necessity of ensuring
that in the case of a short-circuit or earth fault, an upstream protective device does
not operate before the device intended to protect the faulty circuit.
In the case of two fuses or two MCBs this can usually be achieved by ensuring
that the rating of the upstream device is two or more rating steps higher than that
of the downstream device.
In the case of a combination of MCBs and fuses, the difference in ratings may
need to be substantial. Figure 20.1 shows typical characteristics for a 63 A Type C
MCB and various BS 88 fuses and indicates that to be certain of discrimination it
is necessary to select a 315 A or possibly a 400 A fuse upstream of the MCB.
While failure to discriminate is an inconvenience to the user (and to the electricity supplier if the upstream device is his cut-out fuse) as far as the designer of the
installation is concerned it is necessary to select the cable on the basis of the rating
of the fuse or circuit-breaker selected to achieve discrimination, and not the load.
Fig. 20.1 Discrimination between a 63 A MCB and various BS 88 fuses: (A) 63 A MCB;
(B) 250 A fuse; (C) 315 A fuse; (D) 400 A fuse.
Selection of Wiring Systems
531
WIRING SYSTEMS
A wiring system is defined in BS 7671 as ‘an assembly made up of cable or busbars
and parts which secure, and if necessary enclose, the cable or busbars’. A description of a wiring system includes the type of cable (or busbar) and how it is supported and protected. Most systems relate to cables and these are the types mainly
dealt with here. Systems involving busbars are usually factory assembled items and
are covered later in the chapter.
It is conventional to recognise three types of circuit: mains, submains and final,
with which experience tends to associate certain types of wiring system. A main
circuit feeds a distribution board located at the centre of a group of loads or it may
feed a single large load. Where the demand is high the main circuit may operate at
a voltage higher than 1 kV. Conductors in such systems are usually in the form of
cables, as described in Chapter 19.
In extensive installations it may be appropriate to divide the circuits further
using submains which connect a main distribution board to smaller boards more
convenient to load groups. In very large installations the main switch board
may feed one or more section boards which in turn feed further distribution
boards. Final or wiring circuits connect distribution boards to individual points of
utilisation.
For small installations, such as in most domestic and small commercial premises,
it is usual for a distribution board to be located at the supply intake, when it
takes the form of a consumer unit, with final circuits going directly to points of
utilisation.
Some types of cable are suitable for use in either mains or wiring circuits (e.g. the
1 kV cables in BS 5467), while others are used almost exclusively in final distribution circuits and are regarded as wiring types. Popular examples of the latter are
cables containing a protective conductor and the insulated conductors used with
conduit or trunking. On the other hand mineral-insulated cable, while generally
regarded as a wiring type, can be used in the larger sizes for submains circuits, as
may the larger sizes of BS 6004 or BS 7211 cables run in trunking.
Cable types most commonly used for main circuits are the larger sizes of single
or multicore XLPE insulated, wire armoured and PVC (or low smoke and fume)
sheathed cables in BS 5467 and BS 6724. These types of cable are generally used in
preference to the similar PVC insulated cables of BS 6346.
Table 20.1 lists the types of cables available for wiring purposes and gives brief
indications of the main features of their applications. More detail is given later and
there are useful guides on the applications of the various types in the relevant
British Standard specifications.
The British Standards for most cables reflect the requirements laid down in the
European Standards. The process of achieving this throughout the Common Market
is called harmonisation and such cables are referred to as harmonised cables. Some
cables used in the UK, such as flat twin and earth, are not included in this
European Standard and are therefore not harmonised and may not be acceptable
in other EU countries, even though they are fully recognised in BS 7671 and other
national standards.
Where a manufacturer wishes to have a cable of new and novel design recognised, he may have it assessed by the British Approvals Service for Electric Cables,
BS no.
Insulation
532
Table 20.1 Types of cable and flexibles.
Construction
Conductor
Application
PVC
Unsheathed single-core
Copper, solid,
stranded or flexible
In conduit, trunking or similar
enclosures where mechanical
protection is provided. Above
ground. Cable should not be
immersed in water. Not directly in
plaster, etc.
6004
PVC
Sheathed single- and
multicore
Copper, solid,
stranded or flexible
On trays, ladder supports, cleats,
wiring surface where mechanical
damage is unlikely. Single-core
cables without armour for a.c.
circuits. In the ground if provided
with additional mechanical
protection. Can be embedded in
plaster in defined zones
6346
PVC
Steel wire or
aluminium strip
armour with PVC
covering, single- and
multicore
Copper or
aluminium, solid or
stranded
No restrictions except in cases
where severe mechanical impact is
expected. Can be used directly in
the ground without additional
mechanical protection.
Single-core cables must have
aluminium armour when used on
a.c.
4553
PVC
XLPE
or EPR
Split concentric singlephase + earth
Copper, stranded
General use including underground
without further protection. Should
not be installed where mechanical
damage is a likely hazard.
Handbook of Electrical Installation Practice
6004
Non-sheathed
single-core
Copper
High temperature locations in
control and equipment wiring, may
be useful in restricted wiring
applications.
7211
Thermosetting, low
smoke and fire type
Non-sheathed
single-core
Copper
Suitable for use in above-ground
installations such as conduit and
trunking or with similar protection.
7211
Thermosetting,
low smoke and
fire type
Sheathed single
and multi-core
Copper solid,
stranded or
flexible
Similar to BS 6004 cables
but where it is important to
minimise the amount of
smoke and corrosive gases
in the event of fire.
5467
Elastomeric: crosslinked polyethylene or
EP rubber
Armoured
Copper or
aluminium, stranded
As for BS 6346 cables. Caution
should be exercised where these
higher temperature cables are run
together with PVC-insulated cables.
6724
Elastomeric: crosslinked polyethylene or
ethylene propylene
rubber
Single- and multicore,
armoured
Copper or
aluminium
For installation
where it is important to minimise
the amount of smoke and corrosive
gases in the event of fire.
6007
Elastomeric:
vulcanised rubber,
butyl or EP rubber,
silicone rubber
Unarmoured singlecore with various
coverings.
Multicore, flat or
circular with
elastomeric sheath
Copper, aluminium
as an alternative,
stranded or flexible
Butyl, EP rubber and silicone
insulated cables used for high
ambient temperatures. Braided
coverings in dry situations only.
Entry to luminaires.
Sheathed cables resistant to some
oils and solvents. Can be obtained
with a lead sheath where pollution is
severe.
533
90°C PVC
Selection of Wiring Systems
6231
BS no.
534
Table 20.1 (contd)
Insulation
Construction
Conductor
Application
Rubber or PVC,
capable of operating at
high temperatures
up to 150°C
Non-sheathed singlecore cables.
Sheathed two- and
three-core flexible
cords
Copper plain, tinned
or plated, stranded
or flexible, only
small sizes
Zones having high ambient
temperatures, such as in the vicinity
of hot process plant, boiler houses.
Non-sheathed versions must be
protected mechanically by being
enclosed.
Wiring inside and into (high
temperature tails) hot equipment
such as luminaires and immersion
heaters.
Considerable variety of types, see
BS for details.
6500 (flexible
cords)
Rubber, PVC or
glass fibre
Multicore, unsheathed
and sheathed
Copper flexible or
tinsel
Large variety of types of flexible
cords with working temperature up
to 150°C. Some types are similar to
those in BS 6141.
Includes all general purpose
flexibles and the high temperature
varieties for use in or into hot equipment.
Rubber or PVC sheathed
varieties can be used out of doors or
for industrial applications. See
extensive guide in Appendix of
Specification.
6883
Thermosetting
Sheathed single and
multicore cables.
Unarmoured or wire
braid armoured
Copper
Intended for use in ships
and off-shore installations.
More flexible than cables to
BS 5467.
Handbook of Electrical Installation Practice
6141
Thermosetting
Sheathed two, three and
four-core with circuit
protective
conductor
Copper
Particularly for use in alarm
and emergency lighting
circuits which require some
circuit integrity when
affected by fire.
6207
Mineral
Plain copper sheathed
or with additional PVC
covering
Copper (solid), rigid
General wiring; larger sizes are used
for rising mains and distribution
circuits, especially where
continuously high temperatures are
expected. Excellent fire resistance
(alarm and safety circuits). Looks
well as surface wiring, not affected
by most contaminants. Unlikely to
need further mechanical protection.
Limited overvoltage withstand
capability.
Excellent for use in very low
temperatures.
Weather resistance excellent.
Limitations depend on seals at
terminations and joints and on
material used to insulate conductor
tails.
Selection of Wiring Systems
7629
535
536
Handbook of Electrical Installation Practice
who, if they consider the cable is suitable, will issue a certificate to the effect that
the cable, if used in the manner indicated in the certificate, will provide a degree of
safety not less than that required by BS 7671.
Such cables may be described as BASEC certified but do not totally comply with
a British Standard for cables and may not be described as complying with BS 7671.
Their use must be recorded, as a departure, in the Electrical Installation Certificate.
CONSTRUCTION OF WIRING CABLES AND FLEXIBLES
When selecting a wiring cable there are three components that must be considered:
conductor material, insulation and protective covering.
Conductors
Conductors of wiring cables are made of annealed copper, and for sizes of 16 mm2
and above, also of aluminium. Apart from solid or single-wire conductors, which are
available up to 2.5 mm2 in copper and for all sizes in aluminium, conductors are built
up from several wires twisted together to impart various degrees of flexibility to the
conductor. (Note: All sizes of conductor in mineral-insulated cables are of solid
annealed copper.) The wires used in ordinary cables are of such a diameter that the
cable is sufficiently pliable for convenient installation, but in no case should they be
subjected to continuous movement. Excessive vibration can cause breakage of the
wires, usually at or near terminations. Flexible conductors are built up of fine wires
and are available for applications where continuous movement or vibration occurs.
Where a cable route includes frequent bends or room for installation is limited, the
flexibility of stranded conductors is an advantage.
Insulation
Thermosetting compounds such as cross-linked polyethylene (XLPE) or ethlyene
propylene rubber (EPR) are now the most commonly used insulation materials for
normal uses. These materials have higher continuous operating temperatures than
PVC – 90°C rather than 70°C. PVC insulation is still used for some common types
of wiring cable and flexible cords. Mineral insulation and special types of rubber are
available where higher temperatures are expected.
Mechanical properties are usually the most important ones for insulation
of cables up to 1 kV, and loss of strength and brittleness are the best signs to
look for when judging the state of a cable. This applies also to the insulation on
the tails of mineral-insulated cables, but not of course to the insulation of the cable
itself.
The higher temperatures permitted for thermosetting materials cannot always be
utilised if the choice of conductor size is dictated by considerations other than
current-carrying capacity, e.g. voltage drop. In such cases the higher temperatures
are of value where part of a cable route passes through a thermally adverse location (groups, thermal insulation, high ambient temperature). In addition, these
Selection of Wiring Systems
537
materials offer the advantage of high permissible short-circuit temperature and are
useful where high fault-currents are expected.
High temperature cables should not be grouped with others having lower permissible temperatures. Either the cable types should be grouped separately or care
should be taken to confirm that the actual operating temperature of the whole group
does not exceed that permissible for the lowest temperature material present.
It should be noted that terminals of some equipment may not be intended for use
with conductors operating at temperatures higher than 70°C, although high temperature cables may be useful if not essential for connections to equipment which
itself operates at a high temperature such as heating equipment, luminaire control
gear or even electric motors.
Sheaths and coverings
Cable and cord insulation have been designed and tested to provide adequate electrical strength and any additional coverings are required only in order to protect
the insulation against environmental hazards. Thermosetting insulation is tough
enough to withstand pulling into conduits without further protection.
Coverings can consist of a simple sheath of PVC or rubber which provides good
protection against abrasion and liquids and modest resistance to impact. Because
some hydrocarbon solvents leach out the plasticiser of PVC compounds and creosote softens and destroys them, it is best to avoid routes where such contaminants
are likely. Otherwise a lead sheath is generally used, but the type of metal/polymeric
laminate used on cables such as the Pirelli FP 200 could be suitable. Mineralinsulated cables have a solid-drawn copper sheath and are resistant to water and
oils. However the sheath is attacked by some chemicals and a covering of PVC is
advisable.
One disadvantage of PVC is that it generates smoke and corrosive gases
(chlorides) when it burns. Sheath materials with low emissions of smoke and corrosive gases when affected by fire have been developed. These materials are
generally termed LSF (low smoke and fume) or LS0H (low smoke, zero halogen)
and have mechanical properties which are similar to PVC.
Where a cable is likely to be subject to impact, or installation conditions are difficult, a cable having steel or aluminium wire or strip armour should be chosen. Such
cables can be used without further protection against mechanical damage. They are
available with PVC or LSF sheaths. If such a cable is to be installed in waterlogged
conditions a polyethylene sheath material should be used to reduce the rate at which
water will permeate into the cable.
MI cable is not suitable for general use underground. In an exceptional case a
short length may be so used, provided that it is protected against corrosion and
mechanical damage. The PVC covering is not robust enough to withstand being
pulled into a pipe or duct unless the run is short and there are no bends.
The remark above on the care necessary with groups containing cables of different types includes consideration of the temperature limits of sheath and covering
materials. Cables designed for lower conductor operating temperatures are likely
to be sheathed with low temperature material which might deteriorate at temperatures permissible in groups of high temperature cables.
538
Handbook of Electrical Installation Practice
CABLE ENCLOSURE AND SUPPORT SYSTEMS
Cable enclosure
Unsheathed cables are intended to be installed in a cable enclosure which provides
protection against mechanical damage. Such enclosures are either conduit or trunking, although there are minor variations of each. Both are available manufactured
either from steel or plastic with some of the variants being manufactured from
aluminium extrusions. Conduit and trunking should be manufactured to the
relevant standard.
Steel conduit
This is the most common type of conduit for commercial and industrial applications
and is electrically and mechanically continuous, with screw joints between lengths
and into suitable boxes and fittings; conduit can be connected into trunking systems.
The conduit itself must be earthed and therefore must be mechanically and electrically sound so that it can act as its own protective conductor; it can therefore be
used as a circuit protective conductor.
The most common finishes are black enamelled or a variety of zinc coatings; either
may need further protection against corrosion.
Conduits can be mounted on the surface of a building structure, screeded or plastered in, or cast into the structure of a building.
Guidance on the number of cables which may be drawn into a conduit is available from the IEE Guidance Note No. 1, Selection and erection, the requirement of
BS 7671 merely being that ‘other mechanical stresses’ should not damage the cables.
These stresses include those arising from drawing in; minor damage to cables frequently occurs during the drawing in process, particularly when additional cables
are drawn into a conduit already containing cables. Particular care must be taken
to avoid scuffing cables on sharp edges when drawing them into steel conduit.
Plastic conduit
Conduit is also available manufactured from PVC. It is cheaper than steel conduit
and is easy to install. However, it has a number of disadvantages. First, it is not as
strong as steel conduit, secondly there are upper and lower temperature limits
within which it must be used and thirdly its high rate of expansion makes it necessary to fit expansion joints. These features make it necessary to give attention to
mechanical damage, to the weight of the cables installed, their operating temperature and to fixing distances.
Flexible conduit
For connections between fixed installations and equipment which either vibrates or
which is required to be moved from time to time (for belt adjustment), flexible conduits can be used. They vary in construction from a simple helically wrapped galvanised steel strip to more elaborate arrangements of plastic linings and sheaths
with either helical interlocking strip or plain steel strip or steel wire. Such flexible
conduits are not suitable for use as a circuit protective conductor; a separate conductor must always be provided.
Selection of Wiring Systems
539
Trunking
Trunking is available manufactured out of folded sheet steel, extruded plastic or
extruded aluminium. By definition, trunking has a detachable lid and is intended to
have the cables laid in; it is not intended that cables should be drawn in.
Standard cable trunking is installed fixed to the structure of a building; it may
be installed flush with a wall, but in all cases its removable cover makes for great
flexibility in wiring. In long vertical lengths, steps must be taken to provide
arrangements at suitable intervals to relieve the cables of stress arising from
their own weight.
If it is suitably electrically connected, it may be used as a protective conductor;
the cross-sectional area of the interconnections is subject to the requirements of
Chapter 54 of BS 7671.
Trunking is available divided into compartments to allow for the segregation of
various categories of circuit. The same restrictions which apply to the use of PVC
conduit also apply to PVC trunking. There are a number of variants on the trunking theme.
Skirting trunking
Skirting or dado trunking, commonly manufactured out of steel, aluminium or PVC,
provides a ready means of both distributing cables around an office and providing
ready access to them. Accessories can be mounted on, or flush with, the surface of
such trunking. This type of trunking often has separate compartments for wiring,
communications and data cables.
Floor ducting and trunking
Where it is necessary to provide supplies in open plan offices, floor ducting is available; it can be provided with compartments for segregation purposes. Floor ducting
and trunking are manufactured in sheet steel, plastic or mixed fibre and are cast
into the floor finish screed, with interconnecting outlet boxes at intervals as
required. Once cast in, alterations cannot be made without difficulty.
Some floor trunking systems have a removable cover allowing access to the whole
of the wiring system.
Service post and poles
Alternatively, electrical services can be brought down to user positions from above
the working area by use of service poles or posts. These are essentially vertical
self-supporting trunking, divided into compartments into which the various
categories of circuits can be placed. They are commonly used in association with
lighting trunking.
Lighting trunking
Lighting trunking is in many ways similar to standard trunking but incorporates
flanges and other features enabling it to be used either in association with a false
ceiling structure or as a structural part of the false ceiling. It is intended to provide
accommodation for cable and to support luminaires. It is sometimes, but not commonly, available in compartmented form for segregation purposes.
540
Handbook of Electrical Installation Practice
Cable support systems
Cable support systems are used for the installation of sheathed or sheathed and
armoured cables where the mechanical protection of a full enclosure is not required.
Some slight mechanical protection is provided by tray or ladder racking which, if
suitably electrically connected, may be used as a circuit protective conductor,
making it possible to dispense with a protective conductor in sheathed cables.
However, it is not a requirement that either ladder racking or tray should be electrically continuous and where the cables have adequate intrinsic strength, elbows,
tees, offsets, etc. can be dispensed with. BS 7671, Requirements for electrical installations, recognises that sheathed cables, although not to be described as being
double insulated, provide an equivalent degree of safety and therefore can be
regarded as providing protection against direct and indirect contact, in which case
isolated lengths of tray or ladder racking do not need to be earthed.
However, where there is an electrically continuous system throughout a building,
it must be bonded to the main earthing terminal.
Cable tray
Light gauge cable tray is most suitable for small cables, and a well-designed system
will allow access to the cables so that redundant cables can be removed and cables
added.
Attention must be paid, particularly in the case of plastic trays carrying cables
operating at higher temperatures, to the span permitted for a given weight of cable
which must not be exceeded otherwise sagging occurs.
Where larger numbers of cables or longer spans are necessary, heavy gauge return
flange tray should be used.
Basket tray
This type of open wire cable support is suitable for small cables and can be particularly useful for supporting data cable systems.
Ladder racking
Ladder racking is used mainly in industrial premises for the support of larger cables
over longer spans. Cables can be laid on the ladder racking or can be fixed with
cable cleats. These are essential for vertical runs but for horizontal runs plastic cable
ties are often sufficient to locate the cables.
Both tray and racking are commonly made of mild steel or aluminium.
Aluminium does not require additional protection for normal environments; steel
tray may be painted but it is more commonly galvanised. For severe environmental conditions, PVC coating, epoxy coating, nylon coating and other protective
finishes are applied. In extreme cases stainless steel may be used.
TEMPERATURE LIMITS
Insulating materials must be used within certain temperature limits if a satisfactory
performance and an adequate service life are to be obtained. Upper limits of
Selection of Wiring Systems
541
Table 20.2 Temperature limits of wiring cable materials.
* Refer to manufacturers.
†
The second figure refers to conductor sizes larger than 300 mm2.
temperature are determined by the thermal sensitivity of each material; the higher
the temperature, the shorter the period for which the necessary electrical and
mechanical properties are retained. The values in Table 20.2 are based on extensive
experimental work and field experience and are recognised internationally.
Temperature limits for MI cables are the exception in Table 20.2 in that they are
not based on insulation performance. Their limits are related to the temperature
capability of the oversheath material, or to a maximum cable surface temperature
where they are exposed to touch, or can be in contact with thermally sensitive
materials. Where neither of these limitations applies, the temperature at which MI
cables operate is not critical except that it must not exceed the maximum value set
by the end seals or by the material used for insulating the tails.
CABLE RATINGS
The size of a conductor used must be large enough for it to carry the expected
load current without exceeding the temperature limit appropriate to the insulating
material involved. Factors affecting the current that a cable can carry are discussed
below.
Sustained current carrying capacities
The highest value of current a cable can carry continuously without exceeding its
maximum insulation temperature given in Table 20.2 is referred to as its currentcarrying capacity and can be derived either by calculation or by experiment. This
current is dependent on the rate at which heat can be dissipated from a cable.
Clearly a cable mounted by itself on a wall can dissipate much more heat than one
542
Handbook of Electrical Installation Practice
which is in a bunch of cables or is enclosed in conduit. As a consequence the rating
depends on the installation conditions. UK cables are made to internationally
accepted specifications and as a consequence their ratings are comparable with
those used in other countries. Methods for calculating current-carrying capacities
are given in IEC Standard 60287 and ratings for the more frequently used types of
cable and methods of installation are provided in IEC 60364–5–523 and have been
harmonised by CENELEC.
Tabulated ratings, such as those given in BS 7671 and in the 69–30 series of reports
issued by ERA Technology Ltd, are calculated using methods given in IEC 60287
and care is taken to ensure that, where appropriate, they harmonise with those
issued by IEC and CENELEC. The major differences between the BS 7671 ratings
and those issued by ERA lie in the types of installation methods covered and the
ambient temperatures for which the ratings are calculated. The 69–30 reports
include ratings for cables laid in the ground. To keep the individual tables within
reasonable limits of size, ratings are given for single-circuits only (i.e. two singlecore cables or one twin cable in a single-phase or d.c. circuit and three or four singlecore cables or one multicore cable in a three-phase circuit). Where more than one
circuit is installed close together or in the same enclosure, thus forming a group,
mutual heating occurs between the cables and their rating must be reduced by
multiplying by an appropriate group factor.
Where cable current-carrying capacities other than those provided in BS 7671 are
used, or where derating for groups has been calculated using methods other than
those provided, it is advisable that this should be quoted on the IEE Electrical
Installation Certificate. The use of current-carrying capacities other than those given
in BS 7671 does not form a departure from the Regulations as the requirement of
the regulations is that the maximum temperature shall not be exceeded (Regulation 523–01–01).
The sustained current-carrying capacity of a cable is affected by its thermal environment. The most important environmental influences are ambient temperature,
grouping with other cables, enclosure affecting heat dissipation and partial or total
enclosure in thermal insulating material. A less frequent influence, but of equal
importance, is that of solar radiation or radiation from nearby heated surfaces such
as those associated with industrial processes. Although solar radiation is not usually
expected inside a building, it should not be forgotten that cables running underneath roof lights are subject to considerable heating, both from direct radiation and
also due to the significant increase in ambient air temperature. Comments on the
influence of solar radiation are given in a later section.
The effects of the more common types of cable support or enclosure are dealt
with by publishing tables of current-carrying capacity for each method of installation, e.g. in conduit, trunking (and its derivatives) and in thermally insulated walls.
Such ratings are refered to as ‘Reference ratings’ because the capacities have been
determined by extensive tests. Capacities for other methods of installation are
then obtained by the application of theoretically or experimentally derived
factors. Factors are also needed where the cable capacity is affected by the size of
the enclosure or the thermal properties of the enclosing material (e.g. cables in
thermal insulation).
Selection of Wiring Systems
543
Where environmental conditions differ from those assumed for the published
tables of current-carrying capacities, appropriate factors should be applied to obtain
effective capacities for the particular installation.
Ambient temperature
The rating of a cable is derived directly from the amount of heat it can liberate when
it is running at its maximum operating temperature and dissipating that heat into
surroundings which are at a stated ambient temperature. Given that the installation
conditions are the same as those assumed for the determination of the ratings, there
is no margin on the conductor temperature-rise. If anything changes to reduce the
amount of heat which can be dissipated, the cable will become overheated and its
expected life reduced. The most likely causes of overheating in practice are high
ambient temperatures and installation of cables in groups.
Tables of cable ratings for wiring installations are generally based on an ambient
temperature of 30°C. This is sufficiently high to include most general installations,
so it is possible in many cases to use the values in the tables directly without
correction.
However, there are situations where the ambient temperature does exceed 30°C,
such as in boiler houses, in the vicinity of industrial processes and in domestic airing
cupboards. Unless there is an accepted value of ambient temperature for the particular situation, an estimate or a measurement must be made, if necessary referring to a similar type of installation. The measurement can be made using any
suitable type of thermometer, and appropriate instructions are given in Appendix
4 of BS 7671. It is important to observe that the measurement must take into account
all sources of heat, but should not be influenced by heat from the cable under
consideration; that is, if the cable is in place then it should not be loaded or the
thermometer should be appropriately shielded.
Ambient temperature correction factors are given with tables of cable ratings and
the correct rating is obtained by multiplying the tabulated rating by the appropriate correction factor. Where it is known that ambient temperatures will be
consistently lower than 30°C it is possible to take advantage of this fact and to
increase a rating. Here again appropriate factors are usually provided.
Groups of cables
Where more than one circuit or cable run together in conduit or trunking, or on the
surface, the mutual heating between them reduces their current-carrying capacities.
For most arrangements of cables in general use factors are issued with the rating
tables whereby the maximum current-carrying capacity of cables in groups can be
calculated.
Appendix 4 of BS 7671, Requirements for electrical installations, provides such
factors together with guidance and formulae for selecting suitable conductor sizes.
A method for checking that the selected sizes are capable of carrying expected overloads is included.
544
Handbook of Electrical Installation Practice
Because they have to deal with the subject in a general way, these factors must
be derived on the assumption that all the cables in a group are of the same size and
are equally loaded. This situation does not often arise in practice, but it is usually
assumed that the application of such factors to a practical group of mixed sizes of
cables would be on the safe side. In fact, this is not true.
A simple example will illustrate the degree of overheating which can arise with
the smaller conductor sizes. Consider a group of mixed sizes of cable which contains a small bundle of seven 1.5 mm2 cables and a 25 mm2 cable. The seven 1.5 mm2
cables occupy approximately the same space in the group as the 25 mm2 cable and
present about the same surface area for heat dissipation. However, if they are rated
using a common grouping factor, the 1.5 mm2 cables would have a temperature rise
of about 3.4 times that of the 25 mm2 cable. This would lead to the smaller cables
running hot. Overheating of smaller cables is accompanied by oversizing of the
larger ones.
Extensive work on this matter has resulted in the issue of several new ERA
reports in the 69–30 series, which provide ratings for cables in groups of mixed sizes
carrying different loads. These reports deal with cables made to BS 6004 and BS
7211 installed in trunking, and to BS 6346, BS 5467 and BS 6724 installed in multilayer groups (groups where the cables are in contact with each other) on trays and
ladder racks.
It is obvious that, because the ratings for cables in such groups are specific to the
cable and load content of each group, rating factors and current-carrying capacities
cannot be tabulated in the usual way. In fact, a cable ceases to have a specific rating
under these circumstances and, dependent on the size of the group and the loading
of the other cables, its permissible load may be even greater than that for the cable
in isolation. The method of conductor size selection given in the ERA reports provides for the adjustment of individual sizes (subject to other constraints such as
voltage drop) so that the most economical mix of sizes can be selected.
Overcurrent protection is also influenced by the thermal effect of such groups
and the ERA reports include formulae for checking that each conductor will meet
the requirements of BS 7671.
The ERA reports on methods for designing groups with mixed loads use the well
documented and proven uniform heat generation (UHG) principle. Design based
on UHG allocates correctly the permitted power losses between small and large
cables, generally provides a more economical combination of cable sizes and
may permit the addition of further circuits later without requiring a change in the
original circuits.
The following descriptions of applications to groups in conduit, trunking and on
a tray illustrate the method and its advantages. The procedures described are applicable to circuits which must comply with given voltage-drop requirements. If this is
not the case reference should be made to the ERA reports.
Cables in conduit and trunking
The procedure starts by selecting conductor sizes to comply with voltage drop
requirements. These sizes are minima and the size of a conductor will be increased
only if it is thermally too small. An application of the UHG principle checks that
Selection of Wiring Systems
545
individual cables are thermally adequate and that the total power loss is within the
capability of the enclosure.
An optimisation technique is described which augments the current-carrying
capacity of certain circuits, thus improving the economy of the installation.
The procedure for conduit and trunking is outlined in Fig. 20.2 and examples are
provided in Tables 20.3 and 20.5.
Fig. 20.2 Cable size selection for enclosures.
546
Handbook of Electrical Installation Practice
The cable type used in the examples, is single-core PVC insulated to BS 6004, in
steel conduit to BS 4568 or steel trunking to BS 4678. The relevant cable and trunking data required to effect the designs are given in Tables 20.6 and 20.7.
Example 1 Group of cables in conduit
Table 20.3 Group of cables in conduit, first selection.
Ambient temperature 30°C, Ca = 1.00.
(Note: For any other ambient temperature
Ca =
Ê 70 - Amb ˆ
Ë
¯
40
where Amb = ambient temperature, °C.)
Voltage-drop limit = 6000 mV single-phase.
Suitable conduit size could be 32 mm, for which C = 5.3 W/m (Table 20.7).
Conduit internal area = 615 mm2.
Fill-factor = 223.5 ¥ 100/615 = 36.8%.
Maximum permitted total power loss = 5.3 ¥ 36.80.36 = 19.41 W/m.
The sizes determined by voltage drop are adequate, except for circuit No. 2, marked
(*), where the power loss is greater than that permitted for uniform heating. Further,
the total power loss Wt is higher than the permissible value Wp. This would suggest
that either larger cables or a larger size of conduit is needed.
In this example, the fill-factor is below the maximum recommended so an increase
in the size of one circuit could be acceptable. This would reduce the power loss and
increase the permitted power capacity of the group.
Examine the effect of increasing the size of cables for circuit No. 2 by one size.
The result is shown in Table 20.4.
Selection of Wiring Systems
547
Table 20.4 Group of cables in conduit, final selection.
All conductor sizes are now thermally adequate.
Comparison with the last column, which shows the sizes determined by conventional use of an across the board group rating factor, shows that the UHG procedure permits circuit Nos 1 and 2 to be wired with conductors one size smaller than
that indicated by the conventional procedure. This is in line with the expected result
from UHG ratings mentioned above.
Example 2 Group of cables in steel trunking
Table 20.5 Group of cables in trunking.
Ambient temperature 25°C, Ca = 1.061.
Voltage-drop limit = 6000 mV single-phase.
The first stages of selection are given in Table 20.5.
Suitable size of trunking would be 100 mm ¥ 100 mm.
The internal area of which is 9448 mm2.
548
Handbook of Electrical Installation Practice
The fill-factor, FF 1758 ¥ 100/9448 = 18.6%.
For 110 ¥ 100 trunking C = 16.25 W/m (Table 20.7).
Maximum permitted power for trunking = 16.25 ¥ 18.60.345 W/m.
= 44.59 W/m.
The losses for circuits Nos 2, 7 and 9, marked (*), are too high. This could be put
right by increasing this conductor sizes for those circuits. However, as the total
power loss Wt is well within the maximum permitted value Wp it is feasible to try
the optimising procedure on these circuits.
Wt 35.77
=
= 0.803
Wp 44.54
M 2 = 3.95 - 2.95 ¥ 0.803 = 1.58
For circuit Nos 2, 7 and 9, Wa ¥ M2 is greater than Wc, hence these sizes can be
retained.
The optimising procedure is based on experimental work which showed that a
limited number of circuits can dissipate a certain amount more than the average
UHG power, provided that the overall losses of the group are less than the permitted maximum. It can be seen that, as the total power loss of the group increases
towards its maximum permitted value, the optimising factor M2 decreases to
unity.
The maximum permissible value for M2 is 2.4, irrespective of the ratio Wt/Wp.
The optimisation procedure is applicable only to groups in conduit or trunking.
Increasing the conductor sizes of circuit Nos 2, 7 and 9 would also provide a
thermally acceptable design, but the cost would be higher.
Comparison with sizes derived by an across the board application of a conventional group rating factor, Cg = 0.48, would show, as before, that savings can be
made on some of the larger conductors. Voltage-drop limitations tend to mask the
comparison for smaller conductors but, where a direct comparison is available, the
conventional group factor may lead to sizes which are thermally inadequate.
Groups on trays
The procedure, given in Fig. 20.3, is initially much the same as that for conduits and
trunking, with the width and depth of the group replacing the size of the enclosure
and the fill-factor. Because a group on a tray may be of such a width that heat losses
from the edges do not affect the temperature rise at the centre, the initial calculations are therefore based on the assumption that there is no heat loss from the sides
of the group.
On the other hand, a shape factor Cs may be applied which corrects for the effect
of added heat loss from the edges of a group. This tends to compensate, at least in
part, for the rapid decrease in cable current-carrying capacity as the depth of a group
increases. Further comment on this is made when discussing the example.
A further difference is introduced, due to the fact that groups on trays and racks
are laid in an orderly manner so as to facilitate fixing with binders or clips. This
usually results in an approximately rectangular cross-section for the group and the
Selection of Wiring Systems
Table 20.6 Cable data for singlecore unsheathed PVC cable in
conduit or trunking.
†
549
Table 20.7 Trunking and conduit data
for groups of cables.
Note: All values apply to one singlecore PVC cable to BS 6004, at 70°C.
rectangular outline of the cables is the outline of the heat-dissipating surface of the
group.
Under these circumstances it is convenient to assume that each cable occupies a
square area with sides equal to the diameter of the cable. The total cross-sectional
area of the group is then equal to the sum of these squares. The depth, calculated
by dividing this area by the width, approximates to the visual depth. The unit system,
used to calculate the area occupied by each circuit, differs therefore from that
used for cables in conduit and trunking by being based on the square of the cable
diameter and not on p/4 times that value.
Example 3 Group of SWA cables on a perforated steel tray
Ambient temperature 25°C, Ca = 1.
(Note: The reference ambient temperature for cables on trays is 25°C, this
being a more usual temperature for industrial installations. For any other ambient
temperature:
Ca =
Ê 70 - Amb ˆ
Ë
¯
45
550
Handbook of Electrical Installation Practice
Fig. 20.3 Cable size selection for cables on trays (single and multi-core cables to
BS 6346).
where Amb = ambient temperature, °C.)
Voltage-drop limit = 6000 mV single-phase.
For cable data see Table 20.8. The circuit schedule is given in Table 20.9. A tray
width of 450 mm has been chosen.
Depth of group is then 25916/450 = 57.6 mm.
Selection of Wiring Systems
551
Table 20.8 Armoured cable data for use with groups of cables
on trays.
†
Note: Values apply to one-core of a multicore cable, at 70°C.
A wider tray would be desirable because the depth of the group would be less, and
smaller conductor sizes would be needed. On the other hand the supporting steelwork would be more expensive and space available might be limited. A smaller
width would require very much larger conductors and would not be practicable
except for installations where space is extremely limited.
Depth coefficient Cd = 0.9098, Cs = 1.0.
Conductor size adjustment
Conductors Nos 1, 2, 3, 4 and 9 are too small and should be increased in size. While
some conductors, No. 1 for example, need increasing by one size step, others, such
as No. 3, will clearly need more than one size increment. It is useful to have a simple
guide relating the value of Wc/Wa to the likely number of size increments.
Two features must be taken into account at this stage:
552
Handbook of Electrical Installation Practice
Table 20.9 Group of three-phase, four-wire circuits on a perforated tray, brackets or
ladder support.
•
•
•
As conductor, and hence cable, sizes are increased they occupy a greater area
and the group depth for a fixed width increases. This in turn decreases the load
carrying capacity of conductors (see the depth factor, Cd) so that a size increase
greater than that originally thought suitable may become necessary.
The increase in depth and reduction in current-carrying capacity affects all cables
in the group, so that cables which were just adequate before are now too small.
It is not feasible to provide a precise guide because the changes in size and the
effect of group enlargement are unique to each load schedule. Further, it is difficult to test for an oversized conductor, so it is preferable to underestimate the
size increases needed and, if necessary, use a second stage of increases. The guide
provided in Fig. 20.3, based on a study of groups of armoured multicore cables,
may be found helpful.
Application of this guide to the two last columns of Table 20.9 produces
Table 20.10.
These increases are successful for circuit Nos 1 and 3 and almost so for circuit
No. 2. The general effect of increasing the group depth has made circuit 12, previously adequate, now marginally too small.
A second stage, increasing circuit Nos 2, 4, 9 and 10 by one size, is successful for
all circuits.
When the width of the group is less than about six times the depth of
the group, some advantage can be taken of the heat dissipated from the sides
Selection of Wiring Systems
553
Table 20.10 Types of cables and flexibles, UHG increases in conductor size.
of the group. The calculated UHG rating may be increased by the factor Fw derived
from the following equation, where A is the aspect or width/depth ratio of the
group:
Fw =
0.36
+ 0.97, for A > 6
A 1.39
Because the position of any cable in the group is not usually known, it is not
possible to take full advantage of the ‘spare capacity’ in a group where the total
losses are less than the total permitted losses. This is because all of the heavily
loaded cables may be concentrated at the centre of the group. However, a partial
advantage may be taken of such under utilisation of the total permitted losses.
The curves shown in Fig. 20.4 can be used to determine the factor by which the
UHG rating of any individual cable can be increased. This rating factor is a
function of the total area occupied by cables carrying more than their maximum
calculated UHG rating and the overall utilisation of the group. The utilisation
of the group, X, is the ratio of the total circuit losses over the total permitted
losses.
If the utilisation of the group is less than 80%, the rating factor for an 80%
utilisation should be used unless the position of the heavily loaded cables within the
group is known.
For the larger cables, which may be mounted on supports so that the cables are
spaced apart to permit better heat dissipation, information for calculating rating
factors is given in ERA Reports 74–27 and 74–28. Rating factors for certain specific
cases have been derived from such information and are given in BS 7671 and in
554
Handbook of Electrical Installation Practice
2
UHG rating factor
1.8
1.6
X=0.8
1.4
X=0.9
1.2
1
0
500
1000
1500
2000
2500
3000
Total area occupied by cables carrying more than their UHG rating, mm2
Fig. 20.4 UHG rating factor for under utilised groups.
IEC 60364–5–523. However, these factors are subject to the limitation that all the
cables are presumed to be of the same size and equally loaded.
A point worth making here is that, except for MI cable, a wiring cable which is
continuously loaded to even 10% more than its maximum permissible value has its
expectation of life reduced by about 50%. Where a large number of simultaneously
loaded cables must be accommodated, it can be preferable to split them into several
small groups so as to avoid the economic penalties of the low ratings required for
large groups.
Overcurrent protection and selection of cable size
For circuits of practical length, voltage drop may be the decisive factor when choosing conductor sizes. This has been recognised in the previous section on the selection of conductor sizes for groups. The calculation of voltage drop is dealt with later
in the chapter.
One of the functions of circuit protection is to prevent currents greater than
the rating of a cable flowing for a duration long enough to cause damage. There
are two types of such overcurrents: those which arise in a healthy circuit because of an excessive load, and those resulting from a faulty condition such as a
short-circuit.
Overloads
A properly designed circuit will be capable of safely carrying the highest expected
load. In general, however, there will be a small unquantifiable risk that, under exceptional and unpredictable circumstances, the design load could be exceeded. It is a
general requirement, therefore, that all circuits (apart from a few exceptions noted
in BS 7671) must have overload protection, chosen so that an excess current cannot
persist long enough to cause damage.
Selection of Wiring Systems
555
As a result of considerable experimental work and field experience it has been
concluded that a PVC or XLPE insulated cable can safely withstand overload currents up to 1.45 times its continuous rating. However, it is essential to realise that
such currents can only be tolerated if they occur for a strictly limited duration and
only very occasionally, say no more than a few times during the life of the installation. Most other cable materials can withstand this treatment, so the rule limiting
overload to not more than 1.45 times the cable rating has been adopted generally
for all wiring.
Circuit design must aim to avoid such overloads by taking into account the nature
of the loads likely to be imposed on the circuit and their frequency. Some guidance
on load diversity is provided in IEE Guidance Note No. 1, but care must be taken
to anticipate reasonable exceptions. The overload capability of cables is intended
only to cover unforeseeable circumstances, generally arising from faulty conditions
and not from a characteristic of the load. Overload protection should be carefully
matched to the load, taking into account the magnitude and duration of any peaks.
For cases like starting currents and varying loads in motor circuits it is feasible to
take advantage of the intermittent load capability of cables, where thermal inertia
enables them to carry a current higher than their steady state rating for a short
period. This example also illustrates the situation where the thermal effect of exceptional overload may be taken care of by protective features built into equipment
associated with the cable, e.g. in the starter or a thermal trip in the motor.
Selection of an appropriate combination of protective device and cable is illustrated in Fig. 20.5. Having estimated the maximum sustained load (design value) IB,
a circuit protection device is chosen which has a rating of In, equal to or greater than
IB. A cable size is then chosen so that its rating, corrected for ambient temperature
and for grouping, IZ is equal to or greater than IB, and furthermore 1.45 times IZ is
equal to or greater than the long duration operating current of the device, I2. The
cable will then be capable of carrying the design load safely and can also withstand
infrequent overloads which will be cut off by the protective device. This selection
process is a requirement of clause 433 of the IEE Regulations.
Recognising the need for devices which can provide suitable overload protection,
fuses to BS 88: Part 2 or Part 6 or to BS 1361 and circuit-breakers to BS EN 61009
or BS EN 60898 Part 1, are made with characteristics such that under practical installation conditions their long duration operating currents are not greater than 1.45
times their rating In. This greatly simplifies the process of selection as it is then only
necessary to follow the simple rule given in the IEE Regulations, that:
I B ⭐ In ⭐ Iz
In the case of semi-enclosed fuses to BS 3036 the long duration operating current,
I2, is equal to 2In. It is therefore necessary to match the cable with a fuse having a
rating such that 2In < 1.45IZ, or In < 0.725IZ.
As IB < In, the above requirement effectively limits the circuit to 72.5% of the full
thermal rating of the cable. It is convenient, when semi-enclosed fuses are frequently
installed, to tabulate these reduced ratings, IZ so that a direct comparison can be
made with values of load current and fuse ratings. If this is done, then the simple
relationship IB < In < IZ holds once more. For example, see Table 20.11.
556
Handbook of Electrical Installation Practice
Fig. 20.5 Overload protection: (a) general situation; (b) situation possible with certain
protective devices; (c) the load IB can be as high as In and IZ.
Short-circuit
Cables are able to withstand quite high conductor temperatures providing these are
of very short duration and only occur very infrequently. The short-circuit conductor temperatures given in Table 20.2, which are based on both experimental evidence and field experience, can be used to determine the combinations of current
and time which a conductor can carry without a significant reduction in operating
life or in insulating capability (Table 20.12). (Actually a quantity (I 2t) is used which
is proportional to the energy liberated during the fault and hence to the conductor
temperature-rise.) A similar relationship can be determined for the capability of
protective conductors to carry earth-fault currents (Tables 20.13 to 20.15) based on
the maximum temperatures that cable insulation or covering materials can tolerate.
Tables 20.12 to 20.15 can be used to check whether a cable chosen to meet the
requirements for voltage drop, current-carrying capacity and protection against
557
Selection of Wiring Systems
Table 20.11 Single-phase current ratings for cables provided with coarse protection by
fuses to BS 3036 (ratings adjusted to take account of protection, see text on overload
protection).
Single-core insulated non-armoured cables to BS 6004.
Non-sheathed
Area
(mm2)
Sheathed
2 cables enclosed in
conduit in a
thermally insulating
wall
(A)
2 cables enclosed in
conduit or trunking
on a wall
(A)
2 cables clipped
direct to a wall
(A)
8
10.5
14
19
25
33
44
10
12.5
17.5
23
30
41
55
11
14.5
19.5
27
34
47
63
1
1.5
2.5
4
6
10
16
Two-core circular cable PVC insulated and sheathed.
Clipped direct to a wall.
Area
(mm2)
1
1.5
2.5
4
6
10
16
Non-armoured
to BS 6004
(A)
Armoured to
BS 6346
(A)
11
14
19.5
26
33
46
62
–
15
20
28
36
49
65
Light duty mineral-insulated, two-core cables,
exposed to touch or having an overall
covering of PVC clipped direct to a wall.
Area
(mm2)
1
1.5
2.5
4
Current
(A)
13.5
16.5
22
29
558
Handbook of Electrical Installation Practice
Table 20.12 Short-circuit withstand of conductors and protective conductors incorporated
in a cable (for initial and final temperatures see BS 7671).
electric shock will be adequate for short-circuit and earth-fault conditions using the
following procedure. For each fault path and its appropriate conductors:
(1) Calculate the short-circuit and/or earth-fault currents:
• For a live conductor protected against short-circuit by a device of a type listed
in Appendix 3 of BS 7671, the fault current is calculated using its resistance
Table 20.13 Earth-fault capacity for separate protective
conductors (for initial and final temperatures in BS 7671 Table
54B).
560
Handbook of Electrical Installation Practice
Table 20.14 Earth-fault current withstand for steel wire armour on multicore cables to
BS 5467.
Fault current withstand, kA for 1 s
Copper conductor cable
Cond.
Size
(mm2)
2-core
3-core
1.5
2.5
4
6
10
0.69
0.78
0.87
1.01
1.20
16
25
35
50
70
Aluminium conductor
cable
4-core
4-core
reduced
neutral
5-core
2-core
3-core
4-core
0.74
0.87
0.92
1.06
1.79
0.78
0.92
1.01
1.66
1.93
–
–
–
–
–
0.87
1.01
1.15
1.84
2.12
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
1.93
1.93
2.76
3.13
3.68
2.07
2.85
3.13
3.59
4.14
2.30
3.22
3.59
4.14
6.03
–
3.22
3.50
3.96
5.89
3.31
4.05
4.60
6.62
7.64
1.79
17.5
2.48
2.76
3.22
1.89
2.67
2.94
3.31
3.86
2.12
3.04
3.31
3.77
5.61
95
120
150
185
240
5.20
5.75
6.35
8.79
9.89
5.89
6.49
9.25
10.12
11.50
6.76
9.48
10.58
11.73
13.29
6.62
7.50
10.12
11.50
12.83
–
–
–
–
–
4.60
–
–
–
–
5.47
6.03
8.33
9.48
10.58
6.21
8.79
9.71
10.81
12.19
300
400
10.81
12.19
12.37
13.98
14.67
20.79
13.98
15.78
–
–
–
–
11.50
–
13.29
–
These figures assume that the cable is installed so that there is no significant crushing pressure on the
insulation such as may arise under fixings or over the edges of objects.
•
at the normal operating temperature. Where the protective device is of a different type the resistance of the conductor at a temperature midway between
its maximum operating temperature and the maximum permissible final temperature is used in the calculation.
For a protective conductor where protection is provided by a device of a type
listed in Appendix 3 of BS 7671, the fault current is calculated using its resistance at the normal operating temperature. Where the protective device is of
a different type the resistance of the conductor at a temperature midway
between its initial temperature and the maximum permissible final temperature is used in the calculation.
Further detail on calculation of short-circuit and earth-fault current can be
found in the IEE Guidance Note No. 6, Protection against overcurrent, particularly section 4, Determination of fault current.
561
Selection of Wiring Systems
Table 20.15 Earth-fault current withstand for aluminium
wire armour on single-core cables to BS 5467.
Copper conductor cables
Conductor
size
(mm2)
Aluminium conductor
cables
Fault current
withstand
(kA) for 1 s
Conductor
size
(mm2)
Fault current
withstand
(kA) for 1 s
50
70
95
120
150
2.21
3.57
4.00
4.42
6.46
50
70
95
120
150
2.04
3.23
3.57
3.91
5.78
185
240
300
400
500
7.14
7.99
8.84
12.50
13.86
185
240
300
380
480
6.46
7.14
7.82
11.14
12.50
630
800
1000
15.47
22.10
24.14
600
740
960
1200
13.60
19.13
21.25
23.72
These figures assume that the cable is installed so that there is no
significant crushing pressure on the insulation such as may arise
under fixings or over the edges of objects.
(2) Determine the operating time from the characteristic of the appropriate protective device (time current characteristics of some devices are given in Appendix 3 of BS 7671, or information may be obtained from manufacturers).
(3) Divide the fault-current capacity given for the cable in Tables 20.12 to 20.15 by
the calculated fault current in kA.
(4) Square the ratio so obtained and compare it with the appropriate operating
time.
(5) If the ratio is equal to or greater than the operating time of the protective
device, the conductor size is adequate. If not, then a larger conductor is required
or a protective device having a shorter operating time must be chosen.
Assessment of fault-current capacity of a cable
Consider a 50 A/400 V motor circuit where the fault-current protection is provided by a 100 A BS 88 fuse. The supply impedance at the distribution board is
0.018 + j0.03 W.
The motor circuit consists of 50 m of 16 mm2 three-core XLPE insulated cable.
562
Handbook of Electrical Installation Practice
The resistance of the 16 mm2 cable at 90°C is 2.5 mV/A/m – see Table 4E4B of
Appendix 4 of BS 7671.
Because the protective device is of a type listed in Appendix 3 of BS 7671, correction of the resistance for a different temperature is not necessary.
For the 50 m run the resistance is 50 ¥ 2.5/1000 = 0.125 W.
This is the line to line value; for a three-phase fault the line to neutral value is
required, or:
0.125
3 = 0.0722 W.
The total fault loop impedance is:
(Supply) 0.018 + j0.03
(Cable) 0.0722
Total
0.0902 + j0.03
= 0.0951 W.
The three-phase symmetrical fault current = 230/0.0951 = 2419 A.
From the characteristics of a BS 88 100 A fuse, the circuit will be interrupted in
less than 0.1 seconds.
From Table 20.12, the 16 mm2 conductor can withstand 2290 A for a duration of
1 s without exceeding 250°C.
At 2419 A the duration should be reduced to (2290/2419)2 = 0.90 seconds. The fuse
will operate well within this time limit.
In the case of circuits with separate devices providing protection against overload
and fault current, in this example the overload trips of the motor starter and a fuse,
it is important to check that the energy let through by the fault protecting device
does not damage the overload device. For example, motor starters are not intended
to interrupt fault currents, though they may be able to close on to currents of such
magnitudes.
In the example given above the fault current at the switch board, where the motor
starter might be located, is 230/(0.018 + j0.03) = 6574 A; the fuse would be expected
to interrupt the current in less than 0.01 seconds. The starter trips are unlikely to
open the contacts as quickly as this and damage is unlikely. Even if the starter were
to be located at the motor end of the cable, the speed of operation of the fuse is
probably adequate. It is advisable to check with starter manufacturers whether the
proposed fault-current protection is suitable.
Calculation of the maximum likely value (prospective value) of fault-current,
both for short-circuits and sometimes for earth-faults, is required in order to
check that the fault-current protective device is capable of operating safely and
reliably.
To calculate prospective fault-currents, details of the impedance at the supply
terminals is needed; for the smaller installations the Electricity Association’s
Engineering Recommendations P23/1, P25 and P26 should be consulted. For the
larger installation it is advisable also to consult the supplier.
Fault levels can be up to 30 kA at 11/15 kV and 50 kA on 400 V, so that the level
should be checked before switchgear and cables are selected. Current limiting
Selection of Wiring Systems
563
protective devices, such as high breaking capacity (HBC) fuses or current limiting
breakers will limit the energy (I 2t) let through and prevent damage to switchgear
and cables.
Regulations remove the need to check the fault-current protection of conductors
provided that the circuit protective device has adequate fault-current breaking
capacity and complies with section 433. In general, this means that calculation of
fault-currents is required where short-circuit protection is provided by a device not
complying with section 433; such may be the case in motor circuits, and for earth
faults.
Voltage drop
The energy loss involved in distributing electrical power takes the form of a reduction in voltage at the receiving end of each cable run. This reduction is dependent
on the impedance of the cable, values of which are given in mV/A/m (i.e. mW/m) in
BS 7671 or can be calculated. For cable sizes up to about 35 mm2 the impedance, at
50 Hz, is practically equal to the d.c. resistance of the conductors, but above this size,
especially with single-core cables, the inductance becomes increasingly important
and at the largest sizes is the dominant component. As the inductance decreases
only logarithmically with conductor diameter, it becomes more and more difficult
at these large sizes to reduce the voltage drop by increasing the size of conductor,
and splitting the circuit into two or more independent parallel limbs may be necessary. Circuit inductance increases as conductors are separated, so that from the
point of view of voltage drop it is best to keep single-core cables as close together
as possible.
Although it is general practice to use tabulated values of voltage drop directly
without any adjustment, they are in reality vectorial values and in a.c. circuits
neglecting the effect of their phase angles amounts to taking the worst case. Actual
circuits may have a lower voltage drop than is given by such a simple approach. The
effective voltage drop depends on both the power factor of the load and the phase
angle of the cable impedance. The 16th edition provides a method for calculating
values of voltage drop which takes both of these factors into account and the tables
of cable impedance include both resistive and reactive components. Application
of the method is straightforward for multicore cables and for single-core cables
installed in trefoil.
Single-core cables in trefoil have slightly lower ratings than those laid in flat
formation but have the advantage, which is important at the load currents for
which single-core cables are commonly used, of presenting a lower impedance; in
addition this impedance is balanced between the lines. As a general rule for 400 V
circuits it is usually better to obtain a high current-carrying capacity by paralleling more than one run of cables in trefoil than to employ larger cables in flat
formation.
For three-phase circuits having single-core cables installed in flat formation, the
apparent impedances of the three conductors are unequal and the impedance
between the two outer conductors is tabulated, this being the one having the greatest magnitude. This will yield the highest value of voltage drop for all sizes of
armoured cable with all values of load power factor. However, when using the
564
Handbook of Electrical Installation Practice
voltage drop equations in Appendix 4, section 7, it is not a matter of the largest magnitude of impedance voltage but of the largest component of that voltage in phase
with the line-to-line load end voltage. For non-armoured cables the impedance
across the outer conductors does not yield the highest voltage drop, as defined in
Appendix 4, when the load power factor is higher than about 0.9 and may be seriously low for the larger single-core conductors. Under these conditions the highest
voltage drop occurs between the centre and an outer conductor. The matter is
somewhat complicated and designers of installations with very large unarmoured
cables are recommended to consult a paper by A.H.M. Arnold in JIEE, Vol. 67,
1929, p. 90.
The unbalanced nature of the impedances of single-core cables in flat formation
introduces considerable difficulties when cables are connected in parallel. Of all
the available combinations of phase positions only a few offer the possibility of
reasonable current sharing between cables in parallel in the same phase. With
three cables per phase there is no arrangement of cables which will give equal current sharing; however, with a few arrangements balance within about 5% can be
obtained.
It should be noted that the problem is not confined to the line conductors; neutral
and protective conductors run with the phase conductors may be subject to considerable circulating currents. A summary of a few of the more suitable circuits is
given in the IEE Guidance Note No. 6, Protection against overcurrent.
Especially with shorter runs, the arrangement at the terminations where cables
break formation in order to connect to equipment terminals can seriously affect
current balance between parallel conductors. Suitable terminal positions can reduce
this difficulty and it may be advisable to use larger conductor sizes to provide for
inevitable poor current sharing.
If materials which either surround or are close to cables (e.g. conduits, trunking,
trays, structural items) are magnetic the effect on current ratings is small but the
voltage drop can be increased. Unfortunately the general situation is too complicated to deal with in a simple manner as it is critically dependent on the disposition
of the cables in relation to the steel. However, variation in cable disposition in conduits is limited and it is possible to tabulate values of voltage drop figures in rating
tables for ‘enclosed cables’ which are based on experimental data. The impedance
of multicore cables and of single-core cables up to and including 25 mm2 is not
affected to any practical extent when they are run in contact with steel.
Where single-core cables are used to feed large discharge lamp loads the neutral
conductor carries a considerable third harmonic current which results in a significant voltage drop unless the neutral conductor is laid close to the phase conductors.
The loaded neutral must then be taken into account when considering the effect of
grouping on the rating of the cables.
FACTORS AFFECTING THE SELECTION OF TYPES OF CABLE
Cable selection is based on a considerable number of factors including regulations
in force in the locality concerned, the environment and other matters discussed
below.
Selection of Wiring Systems
565
Statutory regulations
Certain statutory regulations, referred to in the IEE Wiring Regulations, limit the
range of cables from which the choice may be made, without removing the necessity for taking into account other factors such as environmental conditions.
In the UK the Electricity at Work Regulations 1989, which apply to all places of
work, require that:
All conductors in a system which may give rise to danger shall either:
(1) Be suitably covered with insulating material and as necessary protected so as
to prevent, so far as is reasonably practicable, danger; or
(2) Have such precautions taken in respect of them (including, where appropriate,
their being suitably placed) as will prevent, so far as is reasonably practicable,
danger.
The Memorandum of Guidance produced by the Health and Safety Executive
refers the user to the IEE Wiring Regulations as giving guidance in installations up
to 1000 V.
The guidance given in the Memorandum to the now repealed Factories Act (Electrical) Special Regulations 1908–1944, that in most cases ‘protected’ meant surrounded by earthed metal, has been replaced by the offering of the use of steel
trunking and conduit or the use of steel armoured cables as an example only. The
Electricity at Work Regulations allow lightly protected cables, such as PVC/PVC or
XLPE/PVC to be used in situations where the risk of damage is low, but the burden
of decision is on the specifier.
Coal mines have very special requirements and are not considered here. The Miscellaneous Mines (Electricity) Regulations and the Quarry (Electricity) Regulations
have been replaced by the Electricity at Work Regulations and an approved Code
of Practice. This lays down that all cables operating at a voltage of 125 V a.c. to earth
or between conductors should be entirely surrounded by earthed metal, which
should have a conductance to earth of not less than half the conductance of the
phase conductors. PVC/SWA/PVC cables are permitted to be used and are an excellent choice in such situations, but in the smaller sizes the armour may not have the
necessary conductance. Cables with a copper strand in the armour may be specially
ordered, if the quantity is sufficient. Otherwise a cable with an extra core may be
used. In quarries, but not in mines, the lead sheath of a cable may be taken into
account.
Flexes should have a protective conductor with the same conductance as the
phase conductors and should be surrounded by earthed wire with a conductance of
half that of the phase conductor. Smaller protective conductors are permitted if a
suitable and reliable residual current device initiates disconnection.
The Cinematograph Regulations require cables for safety circuits, i.e. secondary
lighting, emergency lighting and alarms to be in a separate enclosure from ordinary
circuits and in particular from projection circuits. Cables must be enclosed in metal
or other rigid non-ignitable enclosures or have a rigid metal sheath. It is doubtful
whether PVC conduit complies with the former requirement; lead does not comply
with the latter although copper does.
566
Handbook of Electrical Installation Practice
Before commencing the design of any installation which is covered by these
regulations, it is recommended that copies be obtained from The Stationery Office
(formerly HMSO) and their contents studied in detail.
Environmental conditions
The relationship of the various environmental influences on the selection of cables
and cords is given below.
Aesthetics
The aesthetic considerations governing the selection of cables are not really
environmental conditions, nor are they considered in the BS 7671 unless it is
under the heading of ‘Workmanship’. Nevertheless, they are sometimes very important in the choice of a suitable cable, particularly in domestic and some commercial
installations.
It is obvious that a flush system, i.e. one in which the cables are hidden beneath
the plaster or within partitions, presents no difficulty; in situations where additions
are to be made and decorations or wall finishes are not to be renewed, the problem
is more acute. The choice falls on a cable which is small in diameter (for its currentcarrying capacity) and which will dress well, i.e. is sufficiently easily bent to be
accommodated, where necessary, to curves, etc. and yet which is stiff enough not to
sag between clips. In these cases MI cable or cables with an aluminium screen are
likely choices, with PVC/PVC as a possibility. However, the advantage to be gained
from the small diameter of MI cables may be offset where brass glands have to be
used.
Temperature
The question of derating of cables for high ambient temperature is dealt with
earlier in this chapter. All cables are suitable for the normal range of temperatures,
i.e. the IEC Classification AA5; it is the extremes of temperature which cause problems. All cables are suitable for handling and installation in the normal range of
temperatures, from 5°C to 40°C, the average temperature over 24 hours not to
exceed 35°C; this range is classified by the IEC as AA5. The problem is less serious
when no movement is involved, and specially formulated PVCs are available
where the additional cost is considered worthwhile. XLPE and PVC cables should
not be installed during cold conditions; even a shock (such as may be caused by
rough handling of a drum of cable) at low temperatures has been known to cause
damage. It is best to store cables at temperatures above 0°C for at least 24 hours
prior to handling. It can be some time before heat penetrates thoroughly into the
insulation, so while a cable may appear externally to have survived handling when
cold, it could be damaged internally. As far as flexibles are concerned, insulation
and sheathing of rubber retain their flexibility to lower temperatures than those of
PVC compounds.
Higher temperatures present different problems; the derating applicable to all
cables when operating at high temperatures is prohibitive, although when their seals
are outside the hot zone, MI cables can operate at very elevated temperatures. Table
Selection of Wiring Systems
567
20.1 gives an indication of suitable cables for higher temperatures; for extreme temperatures where flexing is minimal, such as in luminaires, glass fibre insulation is
suitable.
Fire as an environmental condition is not considered by BS 7671. However, circuits which are required to continue operating during a fire must rely on either MI
cable which will continue to operate up to the melting point of the copper (this does
not apply to the termination) or on a cable complying with BS 7629. The latter is
destroyed by fire but the insulation is reduced to silica which still provides a degree
of insulation, allowing the circuit to continue operating.
Presence of water
All rubber and PVC sheathed cables are reasonably resistant to the presence of
water and it is their terminations which require protection. However, if continued
operation in wet conditions is envisaged, it is necessary to use either unsheathed
cables in a watertight enclosure or MI cable with a PVC oversheath or an armoured
cable with a polyethylene sheath. Cables with an aluminium content are not
suitable.
Presence of dust and foreign bodies
Dust and foreign bodies, unless presenting hazards of corrosion or mechanical
damage, do not affect the choice of cable, although accumulations of dust may
reduce the cable’s current carrying capacity. The effect on cable choice and installation methods of stored materials (and dust arising therefrom) are considered later
in this chapter. Where dust is present, busbar trunking systems having an IP rating
of at least IP5* should be selected.
Presence of corrosive or polluting substances
There are substances which have a deleterious effect on steel, aluminium, copper,
PVC and rubber, all of which are used in cable construction. The choice of a cable
must depend on the nature of the corrosive substance. Water, as a corrosive substance, is resisted by paints or galvanising, provided that these are continuous and
not liable to damage. For more actively corrosive agents, galvanising may not be
adequate and either black enamel conduit with protective grease tapes, or PVC, may
be necessary to provide protection.
The copper sheath of MI cables in damp and mildly corrosive situations will form
a patina and corrosion will not proceed beyond that point, unless the patina is
removed. However, the effect is to reduce the thickness of the copper sheath and
so, if the sheath is relied on as a protective conductor, the design calculations may
be invalidated. For this reason, MICC cables used in damp and mildly corrosive conditions must be provided with a sheath of PVC (which is available in a variety of
colours) and glands must be provided with PVC shrouds. Connection boxes should
be made of plastics or of hot dip galvanised, cast or malleable iron rather than zincelectroplated mild steel.
Besides the more obvious sources of corrosive chemicals in cements and plastics,
care should be taken in the selection of cables to be fixed to oak and similar woods,
568
Handbook of Electrical Installation Practice
some kinds of stone if damp, and to metals which are dissimilar to the sheath.
Organic liquids, particularly creosote or petroleum products, can seriously damage
PVC and rubber; cables insulated or sheathed with these materials should be routed
so as to avoid contact with such substances. Where this is not possible, cables with
a lead sheath should be used.
Mechanical stresses
Nail and screw damage
No cable can resist penetration by nails and screws; even steel conduit can be
penetrated. For this reason cables must be so located that penetration is unlikely.
Regulations define zones in which cables must be run and in which screw and nail
fixings should not be made. Alternatively, cables must be protected by an earthed
metallic sheath or armour or enclosed in earthed metallic conduit so that, if penetration occurs and the screw or nail makes contact with a live conductor, the circuitbreaker will trip or the fuse will blow.
Impact
Cables should be installed to minimise the possibility of impact but this is not
always possible and so an assessment of the likelihood of impact must be made. In
domestic and office installations, all cables and cable systems provide adequate
resistance to impact, but at points of particular likelihood of damage (at skirting
boards for instance) further protection should be provided for unarmoured
cables.
Although MI cables can be shown to continue to operate satisfactorily when hammered flat, this characteristic should not be relied on where damage of this nature
is thought likely to occur.
XLPE/SWA/PVC cables provide an adequate degree of protection for most
industrial applications, but do not have the same degree of resistance to impact as
steel conduit. PVC cables in steel conduit provide a system which is most resistant
to impact; any impact of such severity as to damage cables in conduit is likely to
destroy the conduit system.
Flexible cables and cords have a very limited resistance to impact and should be
so installed as to render impact unlikely; where such a possibility remains, flexible
cables and cords with metallic braids are available.
Vibration
Vibration of the fixed installation of a building is unlikely except at final connections to motors or other equipment. While conduit cables themselves are reasonably resistant to vibration, particularly if stranded, steel conduit is not and is likely
to fracture, particularly at box spouts. Patent flexible or semiflexible conduit systems
or PVC conduit do not suffer from this defect.
Copper work hardens and fractures under vibration; to guard against slight vibration a loop of cable adjacent to the equipment will be adequate but for installations
where continuous vibration is experienced, XLPE/SWA/PVC cables are to be preferred. All flexibles except glass fibre types are resistant to vibration. Where there
is sustained movement, appropriate types of flexible cable must be used. However,
569
Selection of Wiring Systems
for very occasional limited movement, for example when starting long running
process plant mounted on anti-vibration mountings, extruded insulation armoured
cables may be used provided that an adequate length of free cable is arranged to
drop down vertically to the equipment. The weak point is likely to be where the
cable enters the equipment, and well-proportioned armour clamps and glands are
essential.
Animal damage
Animals, in relation to electrical installations, fall into two classes: those which are
intended to be present and those which it is feared may be present. The first class
occurs in agricultural installations and BS 7671 states that all fixed wiring systems
shall be suitably protected from livestock.
The second category, of which rats and mice are the most usual, is vermin. Insects
are not known to attack cables in the UK, but may be a problem elsewhere.
Rats have been known to chew lead, copper, PVC and even to attack wire
armouring; to be absolutely certain of resisting attack, steel conduit or XLPE/
SWA/PVC cables should be selected. It must be said, however, that there is little or
no evidence that rats or mice attack PVC conduit or trunking. This may be because
of the different grades of PVC used for conduit and trunking as opposed to that
used for cable sheaths.
Solar radiation
The ultraviolet component of solar radiation can have deleterious effects on PVC.
Where cables are to be exposed to sunshine, a metallic sheathed cable, cables in
steel conduit or cables with a black PVC oversheath should be used.
Figure 20.6 illustrates the reduction in rating due to direct solar radiation on
armoured XLPE-insulated cables installed in free air and lying at right angles to the
Solar radation reduction factor
0.95
0.9
0.85
0.8
10
20
30
40
50
60
70
Cable diameter (mm)
Fig. 20.6 Effect of solar radiation on rating of three-core BS 5467 armoured cable at a
radiation intensity of 1000 W/m2.
570
Handbook of Electrical Installation Practice
sun’s rays. The percentage reduction in rating is approximately proportional to the
intensity of solar radiation. Local values of intensity depend on latitude and, above
all, clarity of the atmosphere. The intensity at or above 3000 m height is about
1200 W/m2. At sites with a clear atmosphere this is reduced to about 1000 W/m2 at
sea level at UK latitudes. In and around towns and industrial sites the intensity is
reduced to about 800 W/m2. If the cable rating is critical, it is advisable to seek guidance on local values of solar radiation intensity. IEC Publication 60287 provides a
method for calculating the effect of radiation. These figures apply to times of
maximum radiation, i.e. around midday in the summer. If the cable load is greatest
at other times of the day or year the effect of solar radiation is likely to be unimportant.
It is often overlooked that cables installed under transparent roofs can be subject
to solar radiation. Although direct radiation received by the cable may be reduced
by the roof material, there is an important increase in the effective ambient temperature, not only of the air in the roof space but of the general radiative ambient
due to the surrounding surfaces of the building. Effective ambients could well reach
40°C, without taking into account the effect of heat from any processes in the building. Such ambients introduce a reduction in rating in addition to that due to direct
solar radiation.
Utilisation
BS 7671 includes utilisation as a class of external influence and lists a number of
categories which may influence the choice of cable.
Capability of persons
This would not seem at first glance to affect the choice of cable, but if extended to
the action of persons, particularly of children, there is the problem of deliberate
damage. No system can totally resist deliberate attack, but in places where it is envisaged that such attack may take place and where a surface installation is concerned,
there is no doubt that the most resistant system is steel conduit and that PVC/PVC
sheathed cables are the most vulnerable. MI cables have an increased resistance.
The use of flexible cords should be avoided wherever possible.
Contact of persons with earth potential
All metallic sheathed cables propagate potentials whether earth or higher. BS 7671
seeks to limit these potentials, particularly by equipotential bonding; in certain situations of high risk, such as bathrooms, extra supplementary bonding is required of
all exposed conductive parts and extraneous conductive parts. Since the exposed
conductive parts of an installation are primarily sources of raised potentials, it seems
sensible in bathrooms and similar situations to use either PVC conduit or PVC
sheathed cables. PVC sheathed MI and PVC/SWA/PVC cables require metallic terminating glands, although these can and should be either shrouded or contained
within a non-conducting enclosure.
Conditions of evacuation
The only consideration likely to affect the choice of a cable has been dealt with
under ‘Fire’.
Selection of Wiring Systems
571
Nature of processed or stored materials
Processed or stored materials can produce three environments which may affect the
choice of cable: explosive vapours and gases, dust and stacked materials.
Hazardous atmospheres Guidance on the selection and installation of electrical
equipment in potentially flammable atmospheres is given in BS EN 60079-14; this
replaces BS 5345. The guidance given is over and above the requirements of BS
7671; the selection and sizing of cables must comply with the requirements of both
documents. Reference to further documents is made in Appendix 2 of BS 7671.
Cables appropriate to hazardous atmospheres are single-core cables to BS 6004
when enclosed in suitable conduit systems, or MI cables, or XLPE/SWA/PVC cables,
or XLPE/LS/SWA/PVC cables, provided that all these are terminated with suitable
glands.
Dust Dust in universally present, but in some installations it is a considerable
problem. The explosion risk arising from dust is covered by a number of standards
and guidance documents, including BS 6467 (superseded), BS 7535, BS EN 50014
and BS EN 50281. These documents are concerned with the design and installation
of equipment for use in dusty atmospheres. All cable entries must be sealed, thus
requiring gasketted conduit boxes and grometted glands. The standard offers little
guidance to the cable installer, but then, cables themselves offer little hazard unless
mechanically damaged. For this reason cables in conduit or armoured cables should
be selected.
Accumulations of dust are a different matter. All factory occupiers are required
under the Factories Act to keep their premises clean. The cabling designer and
installer has, however, to decide whether this prescription will invariably mean that
accumulations of dust will not occur. If dust does accumulate it can be of significant
thickness (50 to 70 mm is not unknown).
Cables should therefore be so installed as to facilitate cleaning and to reduce the
accumulation of dust. Where practicable, cable trays should be installed on edge or
a screen should be provided to reduce the dust accumulation.
Accumulations of dust do not affect the selection of the type of cable, unless the
dust has a deleterious effect on the sheath, but cable ratings are affected because
of the thermal insulating effect of the dust. Damage to PVC insulation is likely and
in the extreme with MICC cables temperatures sufficient to ignite the dust could
be reached.
The precise effect of dust accumulation has not been studied, but the effect is not
dissimilar to that of installing the cable in an insulating wall. The current-carrying
capacities given by the Regulations for this situation are reduced from the clippeddirect value by approximately 30% and all cables including MICC should be derated
by this amount in situations where dust is likely to accumulate. In any case, when
dust is present, MICC cables should be selected on the basis of their exposed to
touch ratings.
Stacked materials Where the building or structure within which the cables are to
be installed is intended for the storage of materials in stacks or heaps, cables should
be installed outside of the zones in which the materials are likely to be kept. If this
572
Handbook of Electrical Installation Practice
is not practicable, provision should be made so as to ensure that the circulation of
air will be maintained around the cables.
Fires can be and are caused by surrounding loaded cables with stored materials;
it is not possible to calculate a derating factor to allow for this possibility. Where
personnel can climb on to stacked materials, any conduits should be installed in such
a way as to ensure that they cannot be used as hand or foot holds.
Commercial considerations
Consideration of the environmental influences to which the installation, or any
part of the installation may be exposed, may reduce the range of choice of suitable
cables, but rarely does it eliminate choice entirely. From the remaining possible cables it is the duty of the designer to select the most economical type. Table
20.16 gives the relative costs per metre installed of various types of cable for a 5 m
run of a single-phase 16 A circuit, protected by hbc fuses and run at normal working
height on plaster, in a normal 25°C ambient. It includes the cost of necessary
terminations.
To arrive at the figures in Table 20.16 the labour content was based on published
data and the material at trade prices. Table 20.16 is not, nor is it intended to be,
definitive. It seems to indicate that for an installation in which the environmental
influences are not severe, the aesthetic considerations low (i.e. the cable is
Table 20.16 Relative cost of 5 m of cable to carry a 16 A single-phase load, including
terminations where necessary.
Type of cable
1.5 mm2 PVC twin + CPC*
2 ¥ 1.5 mm2 singles in steel
conduit
2 ¥ 2.5 mm2 singles in steel
conduit with two other
circuits
2 ¥ 1.5 mm2 singles + 1 mm
CPC in PVC conduit
Two-core 1 mm2 light duty MI
One pair in a seven-core
2.5 mm2 heavy-duty MI
Two-core 1 mm2 light-duty
MI/PVC
One pair in a seven-core
2.5 mm2 heavy-duty MI/PVC
Two-core 1.5 mm2 PVC/SWA/PVC
Three-core 1.5 mm2 screened
cable
* CPC = circuit protective conductor.
Relative cost
1
8.2
Notes
Nailed clips
3.0
6.5
5.2
3.2
5.5
4.3
6.8
2.2
Sheath used as CPC,
screw on seals
Sheath used as CPC,
screw on seals
Sheath used as CPC,
screw on seals
Sheath used as CPC,
screw on seals
Selection of Wiring Systems
573
concealed) and the customer is not prepared to pay for a long life or rewireability,
PVC/PVC cables are the only choice, hence the widespread use in domestic and
small offices. It indicates that a single circuit of cable in steel conduit is marginally
more expensive than a two-core PVC/SWA/PVC. It also indicates that two circuits
of cable in steel conduit are cheaper than two PVC/SWA/PVC cables.
Table 20.16 takes no account of the ability of conduit (and trunking) to span wider
gaps than any other system, and its ability (in certain circumstances) to support
luminaires. Nor does it take account of the neatness of MI cables or screened cables,
of the relatively shallow chases needed (if at all) for MI cable, or of its long life. It
does not take account of the ability of PVC/SWA/PVC to stand a certain amount
of vibration and movement. Neither does it take into account the third factor affecting the selection of cable, namely thermal considerations.
Thermal considerations
The choice of a cable to carry a given current is determined from the tables in
Appendix 4 of BS 7671 applying where necessary the relevant correction factors for
grouping and ambient temperature and the presence of thermal insulation. It should
be noted that these factors are cumulative only where more than one condition
calling for a factor is present; so that if a cable is grouped in one place, is in a high
ambient in another and in thermal insulation at yet another, each factor is applied
once and the cable is selected to meet the worst condition. For large cables, jointing of different sizes of cable may be worthwhile; the cost of jointing must be
assessed against savings in cable and installation costs.
A cable protected against overload is also protected against short-circuit, but the
size of the protective conductor incorporated in a cable may not be adequate to
withstand the thermal effect of the current flowing through it at the time of a fault.
Of the wiring systems under consideration the following form the protective
conductors:
PVC/PVC cable
PVC cables in metal conduit
PVC cables in PVC conduit
MI cable
PVC/SWA/PVC cable
Screened cable
Flexible cables and cords
Copper protective conductor incorporated
Conduit
Separate conductor drawn in (size to suit)
Sheath
Armouring
Copper protective conductor incorporated
Copper protective conductor incorporated
Tables 20.17 and 20.18 indicate that in the range of cable sizes considered, the protective conductor incorporated in a cable, be it a separate copper conductor, cable
sheath or armouring, has a cross-sectional area which is adequate for the energy letthrough demands of semi-enclosed fuses to BS 3036, which will also protect the
circuit conductors against overload.
BS 88 fuses may at first sight appear marginally to fail to protect the protective
conductors of PVC twin and earth cables; before rejecting this combination of fuse
and cable the actual disconnecting time should be calculated. The circuit impedance
is often limited by voltage drop, and a small reduction in impedance could reduce
574
Handbook of Electrical Installation Practice
Table 20.17 Cross-sectional area of protective conductor protected by a BS 88 fuse.
Type of protective conductor*
PVC insulated
single-core
(mm2)
Protective conductor in
PVC two-core + earth cable
(mm2)
5 s disconnecting time
6
10
16
20
25
32
40
50
63
1
1
1
1.5
2.5
2.5
4
4
6
1
1
1.5
2.5
2.5
2.5
4
6
6
0.4 s disconnecting time
6
10
16
20
25
32
40
50
63
1
1
1
1
1
1
1.5
2.5
2.5
1
1
1
1
1
1.5
2.5
2.5
4
Fuse rating
(A)
* The armour of XLPE/SWA/PVC cables and the sheath of heavy-duty MI cables for the above
circuits are adequate as protective conductors.
the disconnecting time to a value which enables a BS 88 fuse to protect such protective conductors.
With all fuses, shorter disconnection times give lower I 2t let-through. In the case
of Type B, Type C and Type D mcbs to BS EN 60898, whose characteristics are given
in BS 7671, this is not so for all disconnection times. This is because of the ‘straight’
portion of their time/current characteristics.This straight portion indicates that there
are circumstances where the tripping time may be any time between the start and
finish of the straight portion of the characteristic. Because of this, tables such as
Tables 20.17 and 20.18 cannot be prepared and the manufacturers should be consulted concerning the I 2t let-through of their devices.
Steel conduit has an adequate cross-sectional area for the size of fuse which
will protect the cables drawn into it. The continued adequacy of steel conduit as
a protective conductor is dependent on its having been properly installed in the
first place. Good threads must be cut on the conduit and the screwed joints must
be tight. Damaged paint or galvanising must be made good and, in those cases
575
Selection of Wiring Systems
Table 20.18 Cross-sectional area of protective conductor protected by BS 3036 (semienclosed) fuses.
Type of protective conductor*
PVC insulated
single-core
(mm2)
Protective conductor in
PVC two-core + earth cable
(mm2)
5 s disconnecting time
5
15
20
30
45
60
100
1
1
1
1.5
2.5
4
6
1
1
1.5
2.5
4
4
10
0.4 s disconnecting time
5
15
20
30
45
60
100
1
1
1
1
2.5
2.5
6
1
1
1
1.5
2.5
4
10
Fuse rating
(A)
* The armour of XLPE/SWA/PVC cables and the sheath of heavy-duty MI cables for the above
circuits are adequate as protective conductors.
where corrosion as opposed to moisture is likely, special protective tapes must be
used.
If, because of poor installation practice, it cannot be guaranteed that the joints in
the conduit will remain sound, it is no answer to draw in a separate protective conductor into the conduit. Even if the protective conductor is connected to every box
(which would not be possible) there is no way of bonding a length of conduit to it,
and so, while the equipment supplied by the circuit in the conduit would be protected, lengths of conduit themselves may become and remain alive.
Attention is drawn to the minimum sizes required by BS 7671 for protective conductors not enclosed in a wiring system and to the requirements for buried earthing conductors.
Voltage drop
It is usually found that the choice of a cable size for any particular circuit is influenced more by voltage drop than by any other factor and often the advantage of
the higher current ratings of some cables is lost. Information on the voltage drop
576
Handbook of Electrical Installation Practice
of cables is given in Appendix 4 of BS 7671 in the form of millivolt drop per amp
per metre (mV/A/m), taking into account all the conditions of a circuit.
For larger cables separate figures for the voltage drop arising from the resistive
(mV/A/mr) and reactive (mV/A/mx) components are given, together with that
arising from their impedance (mV/A/mz). The use of these values without adjustment for power factor or operating temperature may lead to the selection of an
unnecessarily large cable; advice on the effect of power factor on the voltage drop
of larger cables and of temperature of all cables is given in BS 7671. While the
savings to be had in the selection of the larger sizes of cable may be considerable,
particularly where the run is long, for most final circuits the effort involved in
making this adjustment may not be worthwhile.
Because voltage drop in most cases governs the choice of cable size it is advantageous to arrive at the cable size from voltage drop considerations first and then
to ascertain whether the cable size arrived at will carry the design current. The
method is shown by the following example.
Load current 20 A; circuit length 16 m.
Permitted voltage drop, 21/2% of 230 V = 5750 mV
Maximum mV/A/m is 5750/(20 ¥ 16) = 17.97 mV/A/m.
All of the cables listed in Table 20.19, except the MICC cable, initially appear to fail
the voltage drop requirement by between 0.03 mV/A/m and 1.03 mV/A/m. However,
in all cases the load is less than the current-carrying capacity of the cable, hence the
Table 20.19 Voltage drop for different cables.
Size
(mm2)
Voltage
drop
(mV/A/m)
Current-carrying
capacity
(A)
Single-core PVC in conduit
2.5
18
24
PVC/PVC two-core + earth, clipped direct
2.5
18
27
XLPE/SWA/PVC, clipped direct
2.5
19
36
Single-core 85°C rubber in conduit
2.5
18
30
Light duty MICC two-core PVC covered
2.0
17
31
Single-core thermosetting in conduit
2.5
19
30
Cable
Notes
(1) Judged by current-carrying capacity only 1.5 mm2 PVC/SWA/PVC or 1.5 mm2 85°C rubber singles
or 1.5 mm2 two-core MICC would be adequate.
(2) In marginal cases the running of an oversized cable below its rated operating temperature might
reduce the voltage drop slightly, allowing a smaller cable to be used than indicated by the above
type of calculation. In sub-circuits the relationship between the calculated to installed length of
cable is not usually that accurate.
577
Selection of Wiring Systems
Table 20.20 Maximum length of circuits.
Size
(mm2)
Voltage
drop
(mV/A/m)
Single-core PVC in conduit
2.5
18
16
PVC/PVC two-core + earth, clipped direct
2.5
18
16
XLPE/SWA/PVC, clipped direct
1.5
31
9.3
Single-core 85°C rubber in conduit
1.5
31
9.3
Light duty MICC two-core PVC covered
1.5
28
10.3
Single-core thermosetting in conduit
1.5
31
9.3
Cable
Length for 2.5%
voltage drop
(m)
cable will not be running at its maximum permitted temperature. The lower operating temperature will reduce the voltage drop to the extent that all of the cables
will be suitable.
It is clear that the apparent advantage of the higher current-carrying capacities
of certain cables is lost under voltage drop considerations. However, voltage drop
is not subject to grouping or ambient temperature correction factors and for
groups of cables the advantages of higher temperature cables once more become
apparent.
Table 20.20 shows the maximum lengths of certain different cables which will give
a 21/2% voltage drop on a 230 V system with a 20 A load, single-phase, selected on
their current-carrying capacities. Similar tables can be prepared from BS 7671 for
other types of load and 4% voltage drop.
It can be seen that voltage drop is in many cases more limiting than current rating
and that advantages gained in current rating are lost in voltage drop penalties.
Earth-loop impedance
For any voltage to earth, fuse and disconnecting time, there is a maximum earthloop impedance. Some of that impedance is external to the circuit or installation
concerned; a typical value for a TN-C-S (PME) service from the public supply
network is 0.35 W. For a circuit at 230 V to earth a 20 A Type C mcb requires a current
of 200 A to disconnect either socket outlet or fixed apparatus circuits so that the
maximum earth-loop impedance cannot exceed 1.15 W. If the external impedance is
0.35 W then the total impedance of the phase and protective conductors in the circuit
must not exceed 0.8 W. Table 20.21 shows the length of various types of cable to give
a phase and circuit protective conductor resistance of 0.8 W (assuming a circuit load
of 20 A). It is based on the resistance of conductors at their maximum permitted
operating temperature. Similar tables can be prepared for other types of protective
devices and ratings.
578
Handbook of Electrical Installation Practice
Table 20.21 Length of circuits to give a total impedance of 0.8 W.
Size
(mm2)
Line +
protective
conductor
(W/m)
Length for
0.8 W
(m)
Single-core PVC + equal sized protective
conductor
2.5
0.018
44
PVC/PVC two-core + earth
2.5
0.021
38
XLPE/SWA/PVC, clipped direct
1.5
0.027
30
Single-core 85°C rubber + equal sized protective
conductor
1.5
0.031
26
Light duty MICC two-core PVC covered
1.5
0.018
44
Single-core thermosetting + equal sized
protective conductor
2.5
0.019
42
Cable
INSTALLATION METHODS
Guidance is given in the IEE Guidance Note No. 1, Selection and erection, on
methods of installation including spacing of supports for conduit and trunking and
current-carrying capacities of cables housed in them.
Conduit and trunking capacities
The cable capacity of conduit is dependent not only on the percentage cross-section
of the conduit which is occupied by the cables, but on the number of cables which
can be pulled in without excessive force. The length between draw boxes and the
number of bends also affects the drawing-in tension required. Excessive force
damages the insulation, or in extreme cases stretches the cable and so reduces its
cross-sectional area. Hence to IEE Guidance Note provides two sets of cable and
conduit factors, one for short straight runs (less than 3 m) and one for long runs or
runs incorporating bends; the total of the cable factors must be less than the conduit
factor.
For instance, 20 mm conduit, with a factor of 460 for short straight runs, can
accommodate 16 ¥ 1.5 mm2 PVC single cables. However, eight circuits must be
derated by a group factor to 0.51 times their full rated current, so that 6 mm2 cables
are required to carry 20 A. These need 25 mm conduit. This is still more economical
than the alternative of 2.5 mm2 cables in three separate 20 mm diameter conduits. If
a 3 m run with two bends of 20 mm conduit is used, only ten 1.5 mm2 cables can be
accommodated.
Selection of Wiring Systems
579
There are therefore major economic advantages in maintaining straight runs and
in keeping 3 m distances between draw boxes. This usually can only be a site decision and most drawings do not provide sufficient detail to be certain of the bends
or sets required. Factors for trunking installations are also provided and the cable
factors are different from those for use with conduit because no pulling in is
required. The factors should be strictly adhered to even though it is possible to force
a greater number of cables into trunking than the factors allow but at the cost of
pressure on the cables. Although the IEE Guidance Note allows a 45% space factor,
care should be taken during installation to ensure that the cables do not press excessively on the trunking, particularly at bends.
Cable supports
Unsheathed plastics and rubber cables need to be enclosed in conduit or trunking.
Plastics or metal-sheathed cables may be supported on clips or saddles. The spacing
of supports for conduit and trunking is based on the loads and spans that can be
supported without undue sag. The requirement for supports within 300 mm of bends
acknowledges the additional stresses imposed by thermal expansion. Closer spacing
of supports is called for where the installation may be expected to receive mechanical shocks. Fixings may be by way of screws through the back of boxes. Cables in
vertical conduits and trunking must be supported at intervals to prevent undue pressure on the insulation at the top.
The internal edges in trunking at bends, etc. must be well rounded and the use of
site constructed adaptations in place of factory-made fittings should be avoided
unless care is exercised to avoid sharp edges. The top of vertical runs exceeding
5 m length should be fitted with a bend and not with an elbow or with a box. One
of the most frequent causes of high mechanical pressure on wiring cable is the treatment it receives when pushed back into a box behind an accessory. All incoming
holes in the box must be properly bushed and good workmanship exercised to
arrange the cables as smoothly as possible.
Sheathed cables may be fixed directly to a surface or to tray or ladder supports.
Spacings given in the IEE Guidance Note are those which will not impose undue
stresses on the cables at the point of support. Pressure may arise when supporting
the weight of a vertical run of cable; clamps should be distributed uniformly and
sharp bends at the top of the run must be avoided. In order to get satisfactory dressing of cables, closer fixing centres may be required.
Fixing clips may be metal or plastics; when fixing MI cables, caution should be
exercised if the cables are rated ‘not exposed to touch’ as their temperature may be
sufficient to distort the clip.
Terminations and connections
Insulation should be stripped back only just far enough to permit complete insertion of the conductor into an appropriate terminal. Care must be exercised not to
nick or damage the conductor and proper wire strippers are desirable; sharp knives
are not recommended. If a knife is used then a glancing action, as though sharpening a pencil, is best. All the strands of a conductor should be securely fixed in or
580
Handbook of Electrical Installation Practice
under the terminal and, where appropriate, suitable tag washers should be used.
Crimped connections should be made only with lugs or connectors of a size intended
for the conductors concerned and with a tool recommended by the manufacturer
of the connector.
Where cables enter into terminating boxes or equipment, the sheath is taken
through into the box and is stripped off inside. If the box or cover is made of metal
the sheath must be protected from sharp edges by the use of a grommet, and for
surface work or where foreign substances might enter the box, the cable should be
mechanically anchored and the entrance hole properly filled by using a suitably
shaped gland which grips the cable.
If the cable is armoured, the gland must be of a type which provides adequate
mechanical anchorage for the wires or strips. As the armour is often used as a protective conductor the gland must also provide good electrical contact and in turn
be reliably connected to the enclosure or other earthed metal work. On installations out of doors or in wet environments the whole gland should be protected
against corrosion by a watertight covering which goes well back over the outer
sheath.
The ends of MI cables must be completely sealed against the entry of moisture.
This is effected by screwing a small brass pot on to the end of the sheath and filling
it with a special non-setting water-resistant compound, as shown in Fig. 20.7 or by
using heat-shrink seals (see BS 6207–2). The conductors, where they emerge from
the seal, are covered with insulating sleeving. The materials used for the seal and
the sleeving must be selected to suit the expected working temperature of the cable.
Where MI cable enters terminal boxes and equipment it should be anchored by
the use of a gland, which also provides electrical continuity for the copper sheath
and, if required, watertightness. Here again it is often appropriate to cover the entire
gland with a heat-shrink sleeve which goes well down over the outer PVC covering
of the cable.
Terminating the sheath of MI cables calls for the same care to ensure adequate
electrical continuity as with the armour of other cables, as both are generally used
as protective conductors and must carry the earth-fault current of the circuit. Singlecore MI cables involve a further consideration in that a small voltage is induced in
them during normal operation which can be much higher during a short-circuit. It
is normal practice to avoid danger from these voltages by bonding all the sheaths
of each circuit together at each end and earthing them. As a result current circulates continually around the sheath even during normal operation. Providing care
has been taken to ensure that bonding connections are sound and adequately robust
no harm can arise.
Fig. 20.7 MI cable termination (BICC).
Selection of Wiring Systems
581
The individual cables or conductors of single-core cables must not be separated by magnetic material; all the glands belonging to each circuit should be
mounted on a non-magnetic plate (or an air gap must be formed in the plate) and
glands should not be mounted on steel extensions formed by steel sockets or
couplers, etc.
Busbar systems
Busbar systems can be divided into three main types: busbar trunking systems
with frequent tap-off points, high-current low-impedance busbar systems and spaced
bars mounted on insulators. All of these systems are manufactured off-site and supplied in convenient lengths that are assembled on site using joints and accessories
specifically designed for each system. The manufacturers are responsible for providing electrical data such as current-carrying capacity, fault current capacity and
impedance.
Busbar trunking systems with current-carrying capacities up to about 100 A with
tap-off points at 0.5 m to 1 m intervals are a convenient way of distributing power
to numerous small loads in large open plan office areas. Such systems are usually
manufactured in lengths of 1.5 m to 3 m and have either aluminium or steel enclosures. They are available with a range of accessories including end-feed units and
both fused and unfused tap-offs. Tap-offs incorporating mcbs, standard socketoutlets and other accessories are also available. These systems may be installed
under raised floors or above suspended ceilings. When installed under a raised floor
the tap-off points can be used to feed accessories mounted in flush floor boxes
mounted directly on desks or workstations. Systems installed above suspended ceilings are frequently used to feed lighting systems and other small loads. Where
unfused tap-offs are used, attention has to be given to Regulation 473–02 of BS
7671. Similar systems are available as skirting or dado trunking systems fitted with
standard socket-outlets and other accessories. The impedance of these systems is
generally greater than that of a cable with a similar current-carrying capacity, but
the system flexibility offered by the numerous tap-off positions gives an advantage
that could not be economically obtained using cables.
Similar busbar systems with current-carrying capacities up to about 800 A and
less frequent tap-off points are used as main risers or overhead systems in industrial installations. The conductors in these systems are either copper or plated aluminium and are often arranged so as to minimise the impedance of the systems.
Higher current systems with current-carrying capacities up to 5000 A are used as
main risers where the power demand is high. These systems use flat bars separated
by thin layers of insulation and are often referred to as low impedance busbars.
These systems usually have aluminium housings but systems are available where the
busbars are encased in a synthetic resin to provide better resistance against moisture ingress. High current busbars are usually manufactured in lengths of about
3 m; longer lengths would be difficult to handle on-site. Any short lengths and bends
required in an installation will be manufactured as required after the busbar route
has been finalised. If the busbar has to follow a difficult route between two fixed
points, e.g. transformer and switchgear, the final pieces may not be manufactured
until after the majority of the busbar has been installed. This allows the final pieces
582
Handbook of Electrical Installation Practice
Fig. 20.8 Sketch showing how busbar phases can become reversed during installation.
to be ‘manufactured to fit’ thus avoiding the cumulative effect of measurement
errors along the route. These systems do not generally have numerous tap-offs along
their length. The number and position of tap-offs is usually specified and busbar
lengths are manufactured to meet the specified requirements. In many cases these
busbars will be used as interconnectors and will not include tap-offs. When a busbar
has to negotiate a number of bends the position of the phase and neutral bars may
appear to have reversed (Fig. 20.8). Because of this it is prudent to allow for changing the order of the bars at a panel.
Spaced busbars mounted on insulators are used in specialist applications and
within switchgear and transformer enclosures. These systems would be specifically
designed and manufactured for each application. Spaced busbars have relatively
high impedance, which will be unequal between phases. Because of this they are
usually only used for short runs or on d.c. systems.
Long lengths of bar should include expansion joints to absorb their change in
length due to temperature variations. Where bars pass through fire-rated walls or
floors fire barriers must be reinstated to meet local authority requirements. The construction of low impedance busbars is such that internal fire-stopping is not
required.
A smaller size of busbar can be selected if the feed is at or near the centre of a
distributed load, in which case the busbar can be about half the cross-section of an
end fed system (Fig. 20.9).
Selection of Wiring Systems
583
Fig. 20.9 Busbar systems with either centre- or end-feed units.
The different busbar systems have a greater or lesser degree of protection against
the ingress of moisture. Busbar trunking systems with frequent tap-off positions
should not be used where there is a risk of flooding. It is prudent to space such
systems off the floor slab where they are installed under a raised floor and there is
a risk of accidental flooding. If a busbar system is installed outdoors the manufacturer should be consulted and particular care must be taken to seal all joints. The
addition of a ‘roof’ over the busbar is advised in some circumstances. Busbar systems
are not suitable for direct burial in the ground or in undrained trenches which are
liable to flooding. Where resin encapsulated busbars are used in wet environments,
particular care has to be taken to exclude moisture when the cast resin joints are
made on-site. When busbars are used as interconnectors they will have many more
joints than a cable system.
Cable management
The increasing and widening use of data-processing equipment has led to the installation of substantial quantities of data cables. This chapter is not concerned with the
installation of such cables, which are the subject of cable management programmes.
However, the performance of mains voltage cables may be adversely affected if they
are covered by banks of data cables. Similarly, there may be electromagnetic interference between the power cables and the data cables. The latter commonly lie on
the bottom of cable voids, and power cables which are to be installed beneath a
raised floor or in a cable way carrying data cables should follow separate routes
from the data cables.
Fire spread
The PVC sheath of cables can contribute to the spread of fire and potentially to the
production of poisonous smoke. This is a particularly serious problem in designated
escape routes and in cable routes where there are substantial numbers of cables.
Where the installation of cables in escape routes or in places from which smoke and
584
Handbook of Electrical Installation Practice
fumes can travel into those routes is unavoidable, low smoke and fume cables should
be used.
Problems
Properly selected and installed cables have few problems but the most common are
low insulation resistance and breakdown under overvoltage.
Persistent low insulation resistance in MI cables is usually due to defective seals
at terminations and can only be cured by driving the moisture out of the cable with
heat and resealing. However, low insulation resistance immediately after sealing an
MICC cable is not uncommon and usually disappears within 24 hours. MICC cables
should therefore not be tested for 24 hours after sealing; cables then having a low
insulation resistance should be resealed. Low insulation resistance can occur
because of surface tracking over the insulation at terminations due to damp or dust
or in the case of braided cables to the trapping of the braid in the connection. This
can also affect PVC and rubber-insulated cables and is cured by cleaning the cables.
Low resistance also appears to be caused by excessive pressure of PVC cables on
earthed metal and is cured by relieving the pressure.
Any cable will break down under overvoltage if the voltage is sufficiently high.
In this respect transient voltages in 1.v. networks can be as high as 4 kV. This can be
withstood by most types of cable, but MI cable can be adversely affected, particularly at sharp bends. Such overvoltages either occur by design (such as lamp ignitor
circuits) or result from the rapid collapse of magnetic fields such as those in control
equipment coils or fluorescent lighting chokes when the coil circuit is interrupted.
This situation is often made worse by chattering contacts.
In the case of ignitor circuits, MI cables should not be used; to do so is wrongly
selecting the cable.
In the case of surges from equipment, the first action should be to ensure that
there are no intermittent contacts and secondly, to fit surge diverters, available from
the manufacturers, either across the terminals of the offending equipment or across
the terminals to which the cable is connected. It is often only one length of cable in
an installation which is affected.
CHAPTER 21
Control and Protection of
Low Voltage Installations
H.R. Lovegrove, IEng, FIIE
(Consultant)
ISOLATION AND SWITCHING
General
An essential part of every electrical installation is the means of control, both of the
circuits and the current-using equipment.
There are four requirements for switching, three of which are safety requirements:
(1)
(2)
(3)
(4)
Isolation
Switching-off for mechanical maintenance
Emergency switching
Functional switching.
One of the fundamental requirements for safety listed in BS 7671 (the IEE Wiring
Regulations) calls for effective means to be provided in a suitable position, to cut
off all voltages from every installation and every part of an installation in order to
prevent or remove danger. More importantly, the law in the form of Regulation 12
of the Electricity at Work Regulations 1989 requires suitable means to be provided
to cut off the supply to equipment, and to isolate equipment from the supply in
order to prevent danger.
The purpose of these requirements is to ensure that any person working on parts
of an electrical system or electrical equipment that is normally live, or may become
live, is protected from the effects of electric shock or injury from mechanical movement caused by equipment being unintentionally or accidentally energised. Also,
persons operating equipment must be protected from injury in the event of the
equipment malfunctioning.
Isolation
The international definition of ‘isolation’ is ‘A function intended to cut off for
reasons of safety the supply from all, or a discrete section of, the installation by
separating the installation or section from every source of electrical energy’.
585
586
Handbook of Electrical Installation Practice
An isolator, also known as a disconnecter, is a device which disconnects the supply
to the system, or parts of the system, in the off-load condition. Generally, this should
be accessible to skilled persons only.
An isolating switch, or switch disconnecter, should be capable of disconnecting
the supply to the system under all possible conditions, i.e. operating, overload and
fault conditions. This is intended for use by unskilled persons.
Isolators are often confused with isolating switches so when selecting isolation
devices it is essential that the correct application is known and the appropriate
device is selected. Isolators should be situated in a readily accessible position having
regard to the use of the installation and premises, the capabilities of personnel and
the nature of the activity.
An isolating device should comply with BS EN 60974–3 which sets out the creepage and clearance requirements when in the open condition. It should have a positive indication of the ‘off’ or ‘open’ position which should not be displayed until
the gap between the contacts has been achieved. The purpose of the device, and if
necessary the parts of the installation it controls, need clearly marking on or adjacent to it so that there is no possibility of confusion. Access to the contacts and
terminals should not be possible whilst the device contacts are closed. Provision for
securing in the open position is required wherever it is likely that inadvertent or
unintentional operation could cause danger.
Switching off for mechanical maintenance
This term is used to indicate the need to be able to disconnect equipment from the
supply to enable non-electrical maintenance, repairs or replacements to equipment
to be carried out safely by persons who may not necessarily be electrically skilled.
The intention is to provide a means of local control for the person doing maintenance work so as to ensure that the equipment being worked on cannot start up
while this work is in progress.
The switch does not necessarily have to have the same characteristics required of
the isolator and does not have to be connected to the loaded conductors. However,
if connected into the load conductors it must be able to switch off the load current
under full operating conditions. Particular regard should be given to inductive and
capacitive loads. Where the switch is connected to a control circuit it should be so
arranged that a fault on the circuit will not have the effect of bypassing the control
switch and thus allowing the equipment to operate.
Where switches provide for mechanical maintenance work, these should be positioned so as to be under the complete control of the person(s) carrying out the work.
They should be sited away from the equipment but must be positioned so that they
can either be secured in the ‘off’ or ‘open’ position, or be in a lockable enclosure.
In the latter situation, the equipment must be clearly labelled to indicate the position of the disconnecting switch.
Emergency switching
The definition of emergency switching is ‘Rapid cutting-off of electrical energy to
remove any unexpected hazard to persons, livestock or property. The hazard may
be either electrical or mechanical’.
Control and Protection of Low Voltage Installations
587
Do not confuse emergency switching with emergency stopping which provides a
means of stopping any dangerous movement.
Emergency switching devices should act directly on loaded conductors to disconnect the supply as quickly as possible. This device may be connected to the load
conductors although it is more commonly connected to the control circuit. The
switch again should be positioned as close to the equipment operating position or
within easy reach and line-of-sight of the operator. Where this is not possible
or practical, the position of the device should be clearly indicated and in sight of
the operator.
Some installations, such as machine workshops, may require emergency switching to disconnect supplies to all equipment simultaneously. In this case the device(s)
should be sited in a prominent position near to walkways and access points. BS 7671
states the particular requirements for fireman’s emergency switching for high
voltage discharge lighting.
Functional switching
A functional switch is a device that controls the operation of the equipment in its
normal working mode. The requirements for the device are usually contained in the
British Standards relating to the equipment.
Applications
A single switching device complying with BS EN60947–3 may be able to perform
all of the required switching functions provided it is capable of interrupting the
supply on load. Other devices may be used for individual or multiple functions but
may not necessarily be able to perform all functions, in which event more devices
should be used. Table 21.1 indicates the applications for some devices; the list is not
exhaustive.
Detailed requirements
The detailed requirements for isolation and switching are contained in BS 7671 (the
IEE Wiring Regulations) and the associated IEE Guidance Note No. 2. The installation designer needs to consider all of the relevant Regulations in formulating its
design. In particular, consideration should be given to:
•
•
•
The type of building, i.e. domestic, commercial, industrial, etc.
The type of user, i.e. adult, children, elderly, disabled
The environment, i.e. inside, outside, wet, dry, explosive, etc.
Isolation
It is necessary to provide for the isolation of all circuits from all supplies at the origin
of an installation. The means of isolation must be such that it interrupts all live conductors of the system, except in three-phase supplies connected to TN earthing
588
Handbook of Electrical Installation Practice
Table 21.1 Applications for switching devices.
* Provided it is capable of breaking the full load current.
systems where the neutral conductor need not be isolated if it can be assured that
it is connected to earth.
Notwithstanding the above condition, provision must be made on all installations
for disconnection of the neutral conductor from earth for testing purposes. So, in
practice, it is normally necessary to provide facilities for isolating all live conductors regardless of the earthing system.
Installations with supplies from more than one source must have isolating facilities provided for all supply sources. This may be by means of separate, linked or
interlocked devices. Isolating devices must be clearly marked indicating the supply
source so that there can be no possibility of confusion.
Domestic types of installation, or installations controlled by a single distribution
board, may only require a single isolating device incorporated either in the consumer
unit or distribution board. In larger and more complex installations a single isolating device will prove to be very inconvenient for the user. It is, therefore, necessary
to provide a number of isolators to control different sections of the premises and
different operating systems. In such installations the designer should consider the
various aspects of control, use and system maintenance; and, in addition to the main
isolator, provide for isolation of small circuit groups and even individual circuits.The
minimum standard should be for every distributor and submain to be controlled by
an isolator. If the isolation requirements are not properly considered and thus not
properly planned, switching off live parts for maintenance or repair is likely to cause
considerable disruption and inconvenience and can result in persons taking chances
and working on live equipment without first isolating the supply – a dangerous practice which is virtually prohibited under the Electricity at Work Regulations.
Where an earthing system is either TN-S or TN-C-S, isolators fitted downstream
from the main isolator need only interrupt phase conductors. Where the earthing
system is TT or IT, all isolators must interrupt all live conductors.
Control and Protection of Low Voltage Installations
589
Switching off for mechanical maintenance
This function of switching off for mechanical maintenance is restricted to maintenance which does not involve access to live parts.
Where mechanical maintenance may involve a risk of burns or injury from
mechanical movement, provision must be made for the equipment to be switched
off while the maintenance is carried out. This type of maintenance may be done by
a person who is not electrically skilled and who has no understanding of the control
systems for the equipment. It is, therefore, essential that the switch is positioned
within easy access of and as close as possible to the equipment.
Care must be taken to ensure that the switch cannot be unintentionally or inadvertently operated and it must be under the control or supervision of the person
doing the work, at all times. If it is not possible for the switch to be under such
control then facilities must be provided for securing the switch in the ‘off’ or ‘open’
position. This is normally effected by a locking device fitted to the switch but may
also be effected by siting the switch in a locked room where access is restricted to
authorised personnel only.
The switch should directly interrupt the load conductors if and where practical.
When this is not practical, as in the situation of a motor controlled by a star/delta
starter, the switch may operate on the control circuit of the starter unit. In this case
the switch must be of the stop/lock type and the control circuit wiring must be
designed and arranged to ensure that the switch cannot be overridden, either unintentionally or by a fault occurring in the control circuit.
When designing an installation it may be advantageous to the user to select a
single device that will perform the functions of both isolation and switching off for
mechanical maintenance.
Emergency switching
Emergency switching is necessary where a possible danger may arise from equipment while it is performing its normal function. Such equipment may be heating,
cooling or rotating machinery and machinery where there may be of necessity
exposed live parts constituting a shock risk.
The emergency switch must act directly on the supply conductors by a single
operation of the device. It must be readily accessible, clearly visible, have its
purpose marked on or adjacent to it and, for additional identification, be coloured
red.
Switching devices may be:
•
•
•
Inserted directly into the supply circuit
A push switch in the control circuit
An electro-sensitive safety control system incorporated into a machine.
Where a push switch in the control circuit is used it should be capable of being
latched or locked in the ‘open’ position. A plug and socket arrangement should not
be selected as an emergency switching device.
590
Handbook of Electrical Installation Practice
Emergency switching devices should disconnect all conductors of single-phase circuits, d.c. circuits, and three-phase circuits of TT and IT earthing systems, but only
phase conductors of TN-S and TN-C-S systems need to be disconnected. A switching device or system must act as quickly as is possible on the supply conductors but,
at the same time, must not introduce further dangers.
The designer of the installation should have an understanding of the working and
operating controls of the equipment prior to selecting the means of emergency
switching. For example, in an industrial plant a single operation on the supply to
one section may cause danger in other parts of the plant, and similarly, switchingoff the whole plant may give rise to further danger; in which case the emergency
switching may have to start a sequential or partial shut-down process rather than
simply switch it off completely.
Some equipment may continue to run on its own inertia after the supply has been
switched off and the dangerous condition may continue until the machine stops. This
may necessitate the use of emergency stopping devices and procedures in addition
to the switching devices.
In workshops where there are a number of machines being used simultaneously,
i.e. training establishments, it is more likely to be necessary to have the emergency
switching acting on the machines collectively rather than individually. This can be
effected by siting, at strategic positions in the area, a number of emergency stop
switches which will release a contactor wired into the supply conductors to the
controlling distribution board.
Fireman’s switches
The application for a fireman’s switch is for both isolation and emergency switching so these devices need to meet the requirements for both functions. Their main
use is in connection with high voltage discharge lighting. The positioning of these
devices is important and it is, therefore, advisable to consult the local fire authority
at the design stage of the proposed installation to ascertain the most suitable and
convenient positions.
Fireman’s switches should be coloured red, marked ‘FIREMAN’S SWITCH’,
have the ‘on’ and ‘off’ positions clearly indicated (with the top being the ‘off’ position), and have the facility to prevent being inadvertently switched to the ‘on’
position. These requirements are fully detailed in BS 7671.
PROTECTION
This section is concerned with devices that provide excess current, earth leakage
and electric shock protection for circuits and equipment of low voltage installations.
Other sections deal with the requirements and applications of other methods for
providing protection for safety in respect of electric shock, thermal effects, overcurrent and mechanical damage.
The Electricity at Work Regulations state ‘effective means, suitably located, shall
be provided for protecting from excess current every part of a system as may be
necessary to prevent danger’.
Control and Protection of Low Voltage Installations
591
Excess current can be in the form of either overload current or fault current. An
overcurrent occurs when a conductor’s load current is greater than its installed
current rating. A fault current occurs when there is a short-circuit between live conductors or when there is an insulation breakdown or failure between a phase
conductor and an earthed conductor.
Generally, all circuits and equipment have to be protected against the effects of
overload and fault currents, earth leakage and conditions that may cause dangerous electric shocks. Under certain conditions, it is possible to dispense with overload protection if the equipment connected to the circuit is unable to create an
overload condition.
In many installations overcurrent devices can provide protection against all of
the conditions. With other installations, essentially those with TT or IT earthing
systems, residual current devices (rcds) have to be used for earth leakage and shock
protection.
The effectiveness of the protective device is measured by the time it takes to
operate under overload or fault conditions. The operating time is dependent on the
impedances of the system’s circuit conductors and protective conductors.
Circuit protective devices may be either fuses or circuit-breakers. A fuse is
designed to be destroyed by the element melting at a current in excess of its rated
current, without given time parameters. A circuit-breaker is a mechanical device
with switching contacts designed to open at a current in excess of its rated current,
or under certain conditions, when there is imbalance between live conductors, again
within given time parameters. For these devices to be effective they must operate
rapidly to cut off the current before danger can arise.
Types of protective devices
The following types of protective devices can be used:
•
•
•
Overcurrent and earth leakage: fuses and circuit-breakers
Earth leakage only: residual current circuit-breakers (rccbs)
Combination units: combined overcurrent and residual current circuit-breakers.
(rccbs)
All protective devices have to comply with the relevant British Standards. British
Standards set out the requirements to which a supplier must design, build and test
the equipment. This includes:
•
•
•
•
•
Conditions for in-service operation
Classification
Characteristics:
rated voltage, current and frequency, rated power dissipation, rated power
acceptance of fuse holders
Limits of time–current characteristics:
breaking range and breaking capacity, cut-off current and I2t characteristics
Markings
592
•
•
Handbook of Electrical Installation Practice
Construction
Testing.
Fuses
There are two types of fuse in general use:
(1) Enclosed fuses in the form of cartridges that have the fuse element sealed
within
(2) Semi-enclosed (rewirable) which have a copper wire element bridging the fuse
holder contacts.
The relevant British Standards for fuses are:
•
•
BS 88 and BS 1361 for enclosed fuses
BS 3036 for semi-enclosed fuses.
BS 88 fuses have a far greater range of current ratings, connecting arrangements,
and dimensions. They will break higher fault currents than both BS 1361 and 3036
fuses. BS 88 fuses provide for two categories, G and M, and a number of different
types. Category G fuses are for general circuit protection, typically non-inductive
loads. Category M are slower operating devices which withstand higher in-rush
currents, as in motor starting.
BS 1361 fuses are, again, slower operating devices and have a lower fault rating
than BS 88 fuses. The physical dimensions of the 5–30 A range are such that they
are non-interchangeable, which is a safety consideration where they are likely to be
replaced by non-electrical persons.
BS 3036 (rewirable fuses) are slower to operate and have a much lower fault
current rating than the cartridge type fuse. They should not be used in situations
where there is a prospective fault current greater than 2 kA, without additional
back-up protection. Being considerably less expensive to buy and replace, the
main advantage of the device is cost. Also, because it is slower in operation it will
handle higher in-rush currents. The disadvantage of the device is its susceptibility
to abuse. The element can be easily replaced with one of a higher rating than is
suitable for the circuit wiring. When rewirable fuses are used the circuit cable’s
current-carrying capacity has to be reduced using a multiplying factor of 0.727.
This may mean increasing the cable size which will, in turn, increase the cost of the
installation.
Circuit breakers
There are two standards which apply to the manufacture of circuit breakers:
(1) BS EN 60898: 1991 Specification for overcurrent protection for household and
similar installations;
(2) BS EN 60947: 1992 Low voltage switchgear and control gear and Part 2, Circuitbreakers.
Control and Protection of Low Voltage Installations
593
These standards have replaced BS 3871 and BS 4752 which applied to miniature
circuit-breakers (mcbs), and moulded case circuit-breakers (mccbs).
BS EN 60898: 1991 is applicable to circuit-breakers with a nominal current rating
range of 6–125 A and with a fault current rating range up to 25 kA.
BS EN 60947: 1992 applies to circuit-breakers with nominal current rating range
of 100–2500 A. The fault current rating range is not specified but the devices have
to be tested at 50 kA. This type of circuit-breaker is intended for industrial and
commercial applications.
As with fuses, their characteristics vary considerably. It is, therefore, important
that the circuit-breaker is matched to the characteristics of the load and the impedances of the earthing system.
Circuit-breakers that are manufactured to BS EN 60898 are available in three
types: B, C, and D. The type is determined by reference to multiples of nominal
current at which the device operates instantaneously (within 0.1 s). See Table II of
BS EN 60898.
All of the types may be produced with a fault current handling capacity as indicated in Table 21.2.
Circuit-breakers manufactured to BS EN 60947–2 are in two categories:
(1) Category A: not intended for discrimination with devices on the load side
(2) Category B: intended to be selective with load-side devices and normally incorporate a time delay facility.
The characteristics of the devices are not dictated by the Standard and are obtained
by reference to the manufacturer’s technical data publications.
Table 21.2 Fault current
capacities included in
BS EN 60947.
Table 21.3 Ranges of instantaneous tripping
characteristics as shown in BS EN 60947.
594
Handbook of Electrical Installation Practice
Residual current circuit breakers (rccbs)
An rccb is a particular type of residual current device (rcd). Not all rcds are rccbs.
The current British Standard for rcds is BS EN 61008, therefore rccbs have to be
manufactured to meet the requirements of this Standard.
Rcds are identified by the out-of-balance sensitivity of the tripping components.
The tripping current is referred to as the IDn of the device. The important feature of
an RCD is its ability to operate rapidly when it senses a leakage current.
The British Standard requires that an RCD operates as follows:
•
•
•
At the rated IDn trips within 300 ms
At five times the rated IDn trips within 40 ms
At half the rated IDn it must not trip.
The main use of rccbs is to provide for protection against electric shock. It is, therefore, essential that the device maintains its sensitivity and speed of operation
throughout the life of an installation. To facilitate this maintenance of the rcd
sensing circuit it must incorporate a test switch circuit for the user and it is important that this test switch is operated every 3 months.
Combination units
Combination units are composed of a combined overcurrent and residual current
circuit-breaker. These are currently manufactured to the relevant requirements of
both IEC 1008 and BS EN 60898. These devices are a simple and compact means
of providing additional protection where there is a high shock risk.
Applications
There are a number of factors affecting the selection of the method and type of
protective device to be used in a given situation. These are important and need
to be given careful consideration.
Environment and utilisation
These factors include:
•
•
•
•
Type of installation: industrial, commercial, domestic
Is it subject to the EAW Regulations?
The occupancy: are the protective devices going to be replaced or reset by
electrically skilled persons?
The cost of the devices.
Electrical
These factors include:
•
The maximum disconnection time allowed for the circuit, the type of utilisation
of the circuit and the load characteristics, including starting or inrush currents
Control and Protection of Low Voltage Installations
•
•
595
The circuit earth loop impedance
The prospective fault current at the point of installation.
The main advantage fuses have over circuit-breakers is:
•
•
Cost
BS 88 fuses can be used where there is a high prospective fault current.
The main disadvantages are:
•
•
They are costly to replace after a fault
Because fuses can readily be replaced and easily interchanged a person may, by
fitting the wrong type of fuse, compromise the safety of the installation.
The main advantage of circuit-breakers is they are easy to reset after a fault and
cannot be tampered with.
Circuit-breaker types
Type B circuit-breakers are mainly suitable for domestic and commercial installations where there are few or no switching surges, and where multicore cables with
reduced size protective conductors are used.
Type C circuit-breakers are for use in commercial and industrial applications
where there are inductive lighting motor loads with switching surges. For these much
lower circuit earth fault loop impedances are needed to achieve the required disconnection time and all insulated wiring systems may not be able to achieve the
disconnection time without an rccb.
Type D circuit-breakers are for use in applications with abnormally high inrush
currents, such as main frame computers, welding equipment, transformers and Xray equipment. Again, all insulated wiring systems may not be able to achieve the
disconnection times.
Allowing for the constraints of prospective fault current at the point of installation and circuit impedances, fuses and circuit-breakers offer the same quality of
protection and are, therefore, equally safe. As a rule, circuit-breakers are preferable to fuses where operation, maintenance and replacement is likely to be by
unskilled persons. It is important that the correct circuit-breaker type is selected for
the load and installation conditions but the choice is very often a matter of personal
preference.
Rccbs
These devices should be used where the circuit earth loop impedances are too
high for the required disconnection times, in places where there is an increased risk
of electric shock (damp/wet situations) and where there are TT or IT earthing
systems. Rccbs are often required in addition to fuses or circuit-breakers to provide
shock protection and where high surge currents require slow-acting overcurrent
protection.
596
Handbook of Electrical Installation Practice
When selecting rccbs consideration has to be given to the standing earth leakage
current in the circuit or equipment being protected. Any inherent leakage current
will effectively increase the sensitivity of the device which may be detrimental to its
functioning and cause nuisance tripping.
CHAPTER 22
Protective Systems
B. Dakers, BSc, CEng, MIEE
D. Robertson, CEng, MIEE
Revised by P.R. Rosen, BSc(Eng)
(Electrical Consultant)
The term ‘protective systems’ refers to the electrical protection of plant associated
with industrial systems and power systems such as alternators, motors, transformers
and cables. Although this chapter is predominantly concerned with protective
systems applicable to industrial systems and distribution systems up to 11 kV, the
basic principles and requirements apply equally to power systems operating at
higher voltages.
A power system is designed to deliver electrical energy without interruption to
the points where it is utilised. By definition, therefore, a fundamental requirement
in the design of a system is flexibility. If one part of the system becomes faulty it
should be disconnected quickly and ideally without affecting other parts of the
system. Switchgear and protective gear provide this isolation flexibility and thus can
be considered in the context of an insurance against loss of supply. The switchgear
must be designed to be capable of interrupting the current resulting from a fault
while the protective gear must be capable of recognising a fault condition and
initiating the switchgear to disconnect the faulty part of the power system with
minimum disturbance to the rest of the system.
PROTECTIVE SYSTEM REQUIREMENTS
Protective gear is the collective name given to all the components necessary
for recognising,locating and initiating the removal of a faulty part of the power system.
The most important qualities of a protection scheme are reliability and
selectivity, with other important qualities being speed, stability and sensitivity,
none of which, however, is acceptable unless they are provided in such a way that reliability and selectivity are maintained, and the equipment is within reasonable cost.
Although total reliability is impossible, duplicate schemes, alarm supervision
circuits and regular maintenance have resulted in the number of incorrectly cleared
faults being less than 5%.
Selectivity, or discrimination as it is more commonly known, may be defined
as the quality of a protective system whereby it detects and responds to a fault
597
598
Handbook of Electrical Installation Practice
condition so that only the faulty part of the circuit is disconnected. To improve
overall reliability, protective schemes are arranged with back-up and overlapping
zones. Because of this, selectivity is of the utmost importance to ensure that only
the correct ‘zone’ is disconnected.
To avoid unnecessary damage to plant, protection must operate quickly;
thus, speed of recognition and disconnection of a fault are very important. This
is becoming more important with the increased size of plant and the resultant
increase in fault current where widespread damage to plant can occur much more
quickly.
Stability may be defined as the quality of the protective system whereby it remains
unaffected by all power system conditions, faulty or otherwise, other than those for
which it is designed to operate. The stability limit of protection can be quoted as
the ratio of the maximum through-fault current which may cause maloperation
against the relay setting current. If a protection system is to be completely satisfactory, the relay setting must ensure operation under minimum fault conditions. This,
however, is not just a question of setting a relay as low as possible, since the resultant relay burden may cause saturation of the current transformers (CTs) under
external fault conditions, resulting in instability of the protection. A compromise
must therefore be found between stability and sensitivity.
For the most part, the problems existing can be solved by the application of standard equipment. When considering the choice of a protective system for a particular application, two questions arise: how much protection is required and which type
of protection system to use.
In deciding how much protection should be used, a number of facts need to be
considered including system fault statistics; type, nature and importance of plant to
be protected; and degree of complexity compared with level of maintenance staff
and risk of possible mal-operation.
The greatest assistance one can obtain in reaching a final decision on how much
protection should be applied is to draw on experience. If experience dictates,
for example, that the number of faults on a pilot cable over a few years has been
negligible, there is little reason for applying supervisory equipment.
There are a number of possible solutions to known problems and the choice of
system is determined by assessing the required performance, and matching these
protection requirements to that of the available protective systems in relation to
cost, maintenance and installation.
Having chosen the type to protection system based on the factors above, it
must be confirmed that the chosen system is suitable for a particular application.
This involves investigating a set of facts which broadly can be divided into two
groups:
(1) The behaviour of the components of the power system and the limits within
which they may be operated; for example, permissible fault clearance time and
available fault current during internal and external fault conditions.
(2) The characteristics of the protection system and the limits between which the
protection system will perform correctly; for example, operating time, fault
settings and stability.
Protective Systems
599
Fig. 22.1 Non-unit protection.
UNIT AND NON-UNIT PROTECTION
Protection systems can be broadly defined in two categories: unit and non-unit
protection. Economics dictate that protection systems cannot always be fully discriminative and the simpler forms of protection tend to disconnect more of the power
system than just the faulted unit. This characterises the fundamental difference
between unit protection, which is concerned only with determining whether the
fault is within or external to the power system unit it is protecting, and non-unit
protection which disconnects the minimum amount of plant by tripping only the
circuit-breakers nearest to the fault.
Because power system faults are fairly rare, the concept of reliability in protection is very much related to stability (i.e. mechanical or electrical interference must
not cause mal-operation). On the other hand, when a fault does occur it is vital that
operation is ensured and protection is always applied with at least one back-up
system. The arrangement of non-unit protection (Fig. 22.1) allows primary protection for a power system unit and back-up protection for an adjacent unit to be
obtained from one set of relay equipment, i.e. a fault between relays 2 and 1 has
relay 2 as primary protection and relay 3 as back-up protection. Figure 22.2 shows
that the fundamental principles of unit protection dictate that it will not provide
back-up protection for adjacent units so that separate back-up protection must
be provided. Unit protection is not always universally applied throughout a power
system so that some power system units rely on the back-up protection as their
primary protection. Busbars are typically in this category because the low incidence
of busbar faults indicates that this is a reasonable risk. However, the catastrophic
nature of a busbar fault means that the clearance times of back-up protection should
be reviewed as a power system develops so that the rare event of a busbar fault and
its predictable serious effects are constantly appreciated.
Discrimination
Discrimination with load current is perhaps the most fundamental requirement and
thus phase-fault settings in simple protection have to be set above maximum load
current, which therefore limits the protection obtainable for phase faults. Fortunately, with earth faults, a residual connection of the CTs (Fig. 22.3) can be used
which eliminates all current except earth-fault current from the relay so that low
earth-fault settings are possible and this enables coverage to be given to power
systems which have earth-fault current deliberately limited by earthing impedances.
Settings must always be related to the required stability level because errors in CTs
600
Handbook of Electrical Installation Practice
Fig. 22.2 Unit protection in overlapped zones.
Fig. 22.3 Residual connection of earth-fault (E-F) relay with phase-fault (P-F) relays.
increase with energisation level, and the out-of-balance currents between CTs
having different errors will be fed to residually connected earth-fault relays thus
affecting discrimination if the earth-fault relay settings are not above the expected
steady out-of-balance current.
To achieve the requirement that only the minimum of plant is disconnected
during a fault, it is necessary that protection schemes discriminate with each other
accurately in the presence of fault conditions. Two fundamental types of discrimination exist. First, in the case of non-unit schemes (Fig. 22.1) discrimination is
obtained by ensuring that the circuit-breaker nearest to the fault operates
while those further from the fault remain stable. This is achieved by current or time
grading, or more generally, a combination of both. Thus in this case discrimination
Protective Systems
601
is dependent on the intrinsic accuracy of the CTs, the relays and the circuit-breaker
clearance times.
The second type of discrimination is obtained by the through-fault stability of
unit protection. In Fig. 22.2, each unit protection involved in a fault must measure
end-to-end and decide to trip or stabilise depending on whether the fault is found
to be external or internal to the zone bounded by the CTs feeding that protection.
With unit protection, the accuracy requirements are therefore to ensure correct
comparison and in this case, intrinsic accuracy is not important but comparative
accuracy is vital. This has required the establishment of a special category of CTs
(BS 7626, Chapter 3, Clause 33) for unit protection where the turns ratio is specified to close limits and the output capability is specified in terms directly related to
the requirements of unit protection (i.e. knee point voltage and winding resistance).
In general,protection should be as fast as possible to avoid too much damage and/or
disturbance to the power system. However, in non-unit schemes time is often used, at
least partially, to provide discrimination so that longer clearance times than may be
desirable are involved.Also, it is fundamental to the nature of graded time protection
that longer times of operation will be at the source end of radial or ring systems, i.e. in
Fig. 22.1 relay 4 must be the slowest relay, where the fastest time of clearance is preferable and this is the basic objection to simple graded protection schemes.
With unit protection, each unit has the same basic speed of operation so that a
fault anywhere within the power system is cleared in the very fast times obtained
by unit protection.
Distance protection is perhaps the most complex form of non-unit protection but
the most widely used non-unit protection in distribution power systems is graded
protection which is used as primary and back-up protection in radial power systems
and as back-up to unit protection in interconnected power systems. The relays used
to provide graded time protection are generally current-dependent time-lag relays
with an inverse definite minimum time-lag characteristic (idmtl relays).
Inverse time relays
An inverse time characteristic is an attractive feature because high levels of fault
are cleared quickly and low levels of fault cleared relatively slowly, allowing differentiation between faults and discrimination to be achieved. The relay characteristic
has developed with a definite minimum time at high levels where the circuit-breaker
operating time dominates the clearance time and if all the relays in a power system
are subject to high levels of fault current, discrimination is obtained virtually on a
definite time basis.
Some power systems use definite time-lag relays, controlled by overcurrent
starting elements, to provide discrimination and this can have advantages because
definite-time-lag (dtl) relays can be made much more accurate than idmtl relays. In
the general case, however, the advantage of variable time with current level can be
exploited because the magnitude of fault current varies with fault position and also
with the amount of generation plant connected. Thus the idmtl relay is a combination of the requirement for definite-time-lag discrimination when the circuitbreaker time is dominant and inverse time lag at low levels where fault position can
influence the current and hence the time of operation.
602
Handbook of Electrical Installation Practice
The concept of fault position giving different fault levels can be exploited by
current grading in a radial system where maximum possible fault current for each
relay position is easily calculated.Thus a fast overcurrent relay may be set to operate
at high levels and when this is combined with idmtl relays closer grading can be
obtained because the high current end of the overall characteristic is current graded
and the idmtl curve is only required to ensure discrimination below this level.
However, fast overcurrent relays may operate at much lower currents than their
setting when an offset transient is present in the energising current. This is referred
to as transient overreach because they are operating for a fault current magnitude
which is the calculated level for a fault position further away from the source than
the relay setting indicates. Specially designed fast overcurrent relays are available
which maintain their setting (within declared limits) in the presence of the offset
transient; they are referred to as transient free. Numeric overcurrent and earth-fault
faults generally include transient free high set elements as standard.
Because continuity of supply is one of the prime requirements in power system
design, the radial power system develops naturally into a closed-ring type of circuit
so that any feeder can be switched out without loss of supply to any busbar. Protection of this type of power system requires that discrimination must be obtained
along both paths to the fault. This is achieved by directional control of the idmtl
relays so that only the relays nearest to and either side of the fault operate. A typical
arrangement is shown in Fig. 22.4 where it can be seen that the first circuit-breaker
to trip opens the ring which then becomes a radial system allowing the fault to be
cleared by the circuit-breaker nearest the fault.
The directional relay determines the direction of the fault current in relation
to the voltage at the relay point, and is chosen with a maximum torque angle
Fig. 22.4 Directional overcurrent relays.
Protective Systems
603
appropriate to the angle between fault current and energising voltages. In general,
the faulted phase voltages are not used but the relay is nevertheless compensated
to give correct directional operation at low voltages because all voltages collapse
during three-phase faults.
Earth-fault directional relays are fed from residual current and residual voltage.
The directional elements are in effect reverse current relays which are generally
arranged to have a maximum torque angle appropriate to the phase angle of the
fault current. Overcurrent directional elements have a relay characteristic angle of
0° or 45° lead and obtain an overall lagging maximum torque angle by using appropriate phase-to-phase or phase-to-neutral voltages. Earth-fault directional elements
are generally connected to residual current and residual voltage and may have a
characteristic angle between 0° and about 75° lag.
Directional relays should not be confused with reverse power relays which are
not voltage compensated and are used to detect unusual power flow conditions
subsequent to power system disturbances. The power relay is not normally required
to respond to fault conditions and its output contacts are therefore time lagged.
Unit protection is characterised by its sensitivity and speed of operation, both of
which make it susceptible to transient out-of-balance between the input and output
signals which should theoretically sum to zero during through-fault conditions. Each
type of power system unit has characteristics which affect the design of its unit
protection. These are discussed later.
GRADED PROTECTION
In order to apply time-graded protection the relays must be in a radial configuration, as shown in Fig. 22.1. Consideration of Fig. 22.1 illustrates how the principles
of time-graded protection depend on the fault current in each relay being uniquely
identifiable so that the relay response can be determined from its chosen settings.
When a common source feeds several radial feeders it is worthwhile to separate and
identify each set of relays clearly, and the impedances between them. This will show
how the relay at the source must be co-ordinated to suit the feeder giving the longest
times.
Where the circuit between two relay positions has parallel paths it is necessary
to identify the worst conditions for grading each pair of relays. Worst-case load and
fault conditions could be determined by computer studies of the full spectrum of
power system running and outage conditions. Engineering judgement is generally
used to limit the power system studies to critical conditions. Thus grading must
include power system analysis and sometimes requires compromise decisions.
The current in each relay is determined by its CT ratio and the relay response is
determined by its current setting (plug setting) and its time setting (time multiplier).
Discrimination is ensured by the inverse relationship between current and relay
time of operation and the applied specified limits. BS 142 specifies the standard
inverse curve for idmtl relays by the check points as illustrated in Fig. 22.5. The
allowable errors are also specified in BS 142 and these have to be assessed when
deciding the time that will be used as the grading step between each adjacent pair
of relays.
604
Handbook of Electrical Installation Practice
Fig. 22.5 Standard idmtl curve.
Numeric overcurrent and earth-fault relays generally have less error and provide
choice of characteristics. This is an additional setting which complicates the grading
procedure but is a great advantage when relays have to be provided in advance of
finalisation of the power system data.
Effect of impedance
The magnitude of the fault current is determined by the impedances of the power
system feeding the fault and in the simplest form can be represented by source
impedance (Zs) and the impedance between the two relays being considered (ZL),
as shown in Fig. 22.6. Assuming that Zs is much greater than ZL, the fault current at
each relay position is approximately the same, i.e. IF = V/Zs = V/(ZS + ZL). If, in
addition, the load current and CT ratio are the same for each relay position, discrimination could be obtained by time multiplier setting only.
The consideration of load current is important because the plug setting of overcurrent relays, which have a current setting range of typically 50–200% of rating,
determine the basic pick-up and reset levels of the relay. Thus for discrimination
with load conditions, the relay current setting must be related to the CT ratio and
the maximum possible load current to ensure that the relay resets when clearance
of a fault may leave the circuit with increased loading due to an outage.
Protective Systems
605
Fig. 22.6 Basic circuit for grading.
When ZL is significant in relation to Zs, the fault current at the two relay points
is different and the current setting adjustment and/or CT ratio can be used in
combination with the time multiplier setting to give discrimination.
In the general case, Zs is determined by the plant running condition and therefore is variable between minimum and maximum plant limits, hence the reason why
idmtl relays are used. At very high levels of fault current the CT output may be
limited by steady-state saturation of its core material. This limits the effective output
of the CT to approximately a current level whose average value is that given by the
knee point voltage of the CT’s excitation curve divided by the CT winding resistance plus the relay winding resistance. Thus the combined performance of the CT
and relay gives the inverse time curve up to the point of CT saturation and a
definite time above the current at which the CT saturates. If the standard idmtl
curve is used, CT saturation above twenty times the plug setting does not change
the overall characteristic. However, very inverse and extremely inverse relay characteristics are modified by CT saturation so this should be taken into account if high
levels of energisation are expected.
The effective burden of some types of relay varies with setting and thus when low
settings are used, the possibility of CT saturation is increased. Thus with earth-fault
relays and high multiples of setting, the guidance on application of CTs as detailed
in BS 7626: 1993 should be taken into account.
Numeric overcurrent and earth-fault relays have extremely low burdens. This
allows low settings to be used without increasing the possibility of CT saturation.
However the time–current curves of some relays do not follow their theoretical
characteristic at high multiples of setting so their use with low settings may require
this discontinuity in their curves to be included in the grading procedure.
Grading procedure
The procedure for grading a set of relays is first to establish a common base on
which to compare the curve of each relay with each adjacent relay. This common
base is generally primary current referred to the base voltage of the power system.
Settings have to be chosen for each relay to maintain the grading step at the highest
606
Handbook of Electrical Installation Practice
possible fault current and also to ensure operation at the lowest possible fault
current. Thus power system data must be available for maximum and minimum
plant condition.
The grading step must take into account maximum circuit-breaker clearance time,
CT errors, relay errors and relay overshoot. Generally, 0.4 s has been used as a
minimum but lower values are feasible, e.g. 0.25 s, with fast circuit-breakers and
accurate relays.
Relay overshoot is related to the inertia of an electromechanical relay and is the
time difference between the operate time for a specified level of current and the
time the relay has to be energised at this level of current to obtain operation. In
other words, the relay will operate (and its time of operation is unimportant in this
case) if it is energised for a time less than its operate time because the movement
has stored energy which will cause it to continue to move after the energising
current ceases. It is tempting to believe that because semiconductor designs have
no mechanical inertia in their measuring circuits, static relays will not have any
overshoot. However, trapped charge in smoothing and timing circuits gives much
the same effect and although special circuits can obviously be designed to minimise
this, economics may dictate that a static relay has as much overshoot as an
electromechanical relay.
Having established current settings for each overcurrent relay to ensure nonoperation during maximum load conditions, the multiple of the current setting of
the relay furthest from the source (relay 1 in Fig. 22.1) for maximum through-fault
conditions will determine the required time multiplier setting for this relay. Often
relay 1 can be set at 0.1 time multiplier because it is known that other protective
systems, fuses, motor protective relays, etc. have such lower relative current settings
that co-ordination is not required. Sometimes a minimum time multiplier is specified by the authority controlling the protection in the circuits being fed by relay 1.
If relay 1 has to be co-ordinated with other protection the time curve of this protection must be included in the grading exercise.
With the plug settings of each relay set to suit load currents, the calculated plug
setting multiple for the fault level at each relay is determined. The relay curve is
only specified up to twenty times the plug setting and it is possible that CT saturation will affect time of operation at levels higher than this so that the current setting
should be increased if necessary until the fault current is below twenty times the
current setting. If a setting above the 200% limit is called for, the current setting
multiple and relay burden must be assessed against CT output.
Having decided the setting of relay 1, by one means or another, its time of operation for maximun fault level at its location can be established; this is the point
of grading with relay 2. The multiple of relay 2 current setting for this fault condition and the time of operation of relay 1 plus the grading step give the required
time multiplier for relay 2. Figure 22.7 shows grading between two relays, illustrating the way in which the two curves obtained from current settings and time
multipliers are drawn to a common base to show the overall protection obtained.
The alternative settings for relay 2 which give the same grading step between the
two curves show the improved fault coverage obtained for relay 2 if current settings
are held to the lowest value needed to ensure discrimination against maximum load
conditions.
Protective Systems
607
Fig. 22.7 Grading between two relays.
High-set relays
If high-set relays are used they must be set so that they can be included in the
co-ordination of the relays. Setting of the high-set relays must take account of the
stability requirements for a fault at the next relay point with due allowance made
for the 50% overreach of simple electromechanical high-set elements. If twice
the setting requirement for operate current is also introduced, it is often difficult to
achieve viable settings for the high-set elements.
Having selected the high-set settings, the operation point of the relays for grading
is obtained using the lowest value of current multiple as determined by the highset setting or the fault current. If the value is less than twice the current setting the
relay current is too low to ensure operation and a change in CT rating should be
considered.
The high-set setting of relay 1 or the fault level at relay 1 is then chosen to
determine the grading on the basis of which the lowest multiple of the plug setting
at relay 2 is obtained. With the lowest multiple of plug setting for relay 2 given by
the high-set setting of relay 1 or a fault at relay 1, the time multiplier or relay 2 is
determined. If a time multiplier setting of greater than 1 is called for, the plug
setting must be increased.
Grading by computer
The grading of relays is a relatively simple task which can easily be done by a computer; however, the problem of collecting data and authenticating the data remains.
608
Handbook of Electrical Installation Practice
Often data are only questioned when engineering judgement indicates that the final
result is unusual. This means that the computer should be used to assist and not
replace the engineer.
Graphics workstations provide interactive means of grading by displaying the
relay co-ordination curves and thus allowing the engineer to study options and
compromises. If the workstation is interfaced with a CAD/CAM system, hard copy
of the final results may be produced for protection audits.
UNIT PROTECTION
Unit protection operates for faults which it measures as being within the protected
unit and is stable for faults which it measures as being external to the protected
unit. Differential protection, which forms the majority of unit protection, can be
classified by the means used to obtain stability. In the current balance system,
current is circulated in the secondaries between the sets of CTs at each end of the
protected zone and the relay is fed by the summation of the currents which is
theoretically zero under external fault conditions. The voltage balance system has
voltages derived from and proportional to the currents which are balanced under
external fault conditions, so that theoretically no current flows in the relays which
are connected in series between ends. The basic arrangement of both systems is
shown in Figs 22.8 and 22.9.
Each type of balance has limitations and the means of overcoming these limitations characterises relay design. Originally, the use of distributed air-gap CTs
favoured the voltage balance scheme because this type of CT naturally produced a
voltage output proportional to current. However, as can be seen in Fig. 22.9, significant pilot capacitance causes spill current in the relays of a voltage balance pilot
wire differential scheme and thus provision must be made for this in the relay
design. Similarly, in a current balance scheme (Fig. 22.8) the voltage drop due to the
circulating current dictates that the relays must be connected at the electrical centre
point.
Fig. 22.8 Current balance stability.
Protective Systems
609
Fig. 22.9 Voltage balance stability.
In pilot wire differential schemes it is not practical to connect relays at the electrical centre point because this would be geographically in the centre of the feeder.
Thus the design of a feeder protective scheme must arrange for tripping contacts at
each end and the relay equipment is therefore duplicated at each end, with both
ends and the communication channel between ends forming the measuring circuit.
Steady-state out-of-balance spill currents are overshadowed by the severe out-ofbalance during unequal saturation of the CTs caused by the offset transient in the
primary current and the remanence left in the CTs from previous fault conditions. Considering that these effects are transient in nature, they are related to the
dynamic performance of a protection which must therefore be established in
relation to the primary transient and its effect on the combination of relays, CTs
and connections between them which make up the protective scheme.
These effects are best understood and analysed by computer simulation.
Comprehensive dynamic representation of the power system, CTs and relay circuit
can be set up using standard software packages (e.g. EMTP) which will allow stepby-step calculation and graphical display of the currents, voltages and fluxes in the
circuits. This is essential for design and development but also allows special
applications and unexplained field experiences to be analysed.
Low and high impedance schemes
Current balance schemes are classified as low or high impedance by the relative
impedance of the relay used. The high impedance differential circulating current
scheme allows for transient unbalance more definitely than any other type of
protection because it assumes complete saturation of the CTs at one end with the
CTs at the other end producing full output. With correct relay design in a high
impedance protection system it should be possible to remove the CT at one end
and replace it by its winding resistance only and still obtain stability.
Low impedance current balance differential schemes can be considered basically
as two CTs feeding an effective short-circuit which is the low impedance relay.
Thus assuming the relay has zero impedance, the excitation current of each CT is
610
Handbook of Electrical Installation Practice
determined by the through-fault current, the CT winding resistance and the lead
burden resistance. The excitation currents are not equal if different CTs or lead
burden resistance are used and the difference between the excitation currents flows
in the relay giving a tendency to operate during the through-fault condition.
In contrast to the low impedance differential scheme, the high impedance current
balance scheme can be regarded as two CTs connected back-to-back so that the
current from one secondary is absorbed by the current in the other secondary.
Assuming a voltage-operated relay of infinite impedance there is no other path for
current to flow and the excitation currents at each end must be equal. Thus, in this
case, with unbalanced CTs or lead burdens, the total voltage produced by both CTs
has a magnitude determined by the total loop burden of both CT winding resistance and both lead burden resistance and this total voltage is shared between the
two CTs in proportion to the appropriate points on their respective excitation curve,
with each CT having the same excitation current.
Practical high impedance differential schemes have relays with significant impedance values with respect to the excitation impedance of CTs so that spill current
flows in the relay due to unbalance between CTs and this tends to reduce the
fundamental voltage unbalance. The steady-state unbalance spill currents must be
considered in relation to the sensitivity of the relay which has an operation level of
typically 30 mA so that small levels of ratio error in the CTs can be significant, particularly when 5 A CTs are used and the prospective circulating secondary current
will therefore be 250 A for a fifty times through-fault. Ratio error in CTs introduces
additional error to that produced by unequal excitation currents and thus must be
minimised by correct choice of CTs. CTs to BS 7626 which have special requirements as detailed in Chapter 3, Clause 33, should be used for differential protection
but other classes of protection CTs have been successfully used.
The practice of using class 5P CTs (IEC 185) in differential protection has developed due to the fact that some CT manufacturers make them physically to be the
same as special class CTs and thus the only difference is in the specified limits.
However, the CT specification allows a broader approach and in general terms the
only suitable CTs for differential protection remain the special class. As stated in
BS 7626, class 5P CTs may be suitable for differential protection but this depends
on the difference between the CTs at the two ends rather than the protective scheme
and the crucial factors are stated in Appendix A of BS 7626. These steady-state
considerations must be remembered when settings are being chosen even though
the basic stability requirements of high impedance protection are calculated for
transient unbalance conditions.Thus steady-state stability requirements may require
settings to be higher than transient stability requirements.
High impedance protection is limited to those applications where the lead length
between CTs is less than about 1000 m and where CTs can be low reactance and
have the same ratio. Pilot wire differential protection and transformer differential
protection are therefore based on low impedance principles.
Differential protection using low impedance relays requires some means to overcome the unbalance between ends during through-faults. Errors in CTs, both steady
state and transient, produce differential current which appears to the relay as an
internal fault and consequently there is always a limit to the sensitivity that can be
used.
Protective Systems
611
Fig. 22.10 Overall bias characteristic.
Transient unbalance between ends is generally much higher than steady-state
unbalance and early low impedance differential schemes used slow relays to
withstand these transient conditions. This technique is still used in very sensitive
earth-fault protection and in simple differential schemes which may use idmtl
relays as measuring elements.
However, speed of operation is one of the basic advantages of differential protection so that some means other than time delay is preferable to allow for transient unbalance and in low impedance differential schemes this has been generally
achieved by biasing the relays.
The concept of bias is best understood by observing the change in relay setting
with through-fault current in relation to spill current, as shown in the idealised
composite characteristics of Fig. 22.10.
The step in the current required to operate the relay curves is deliberately introduced into the design so that the operating current setting level during internal
faults is not affected by the bias current. This gives a reduction in the ratio between
spill current and current required to operate, causing a potentially unstable condition at a relatively low level of energisation; hence the requirement to type test
low impedance biased schemes stability at levels of through-fault current below
maximum. The different slopes of the ‘current required to operate’ curves for internal and external fault are generally due to only half the bias circuit being energised
by an internal fault fed from one end.
Power system units take many different forms which dictate the design of the protection that will be applied. Thus each type of unit has unique features related to
612
Handbook of Electrical Installation Practice
the particular problems of that type of unit and are each subjects in their own right.
However, the salient points are summarised below.
Feeder differential protection
The basic unit protection for feeders is differential protection using pilot wires
between ends to effect the end-to-end comparison. The limitations imposed by the
pilot wires dictate that sensitive measuring relays are required and the steady-state
and transient unbalance between ends is generally catered for by biasing the relay.
For economy of pilots, the CT outputs are combined in such a way that all faults
can be measured by comparison across one pair of pilots. British practice is to use
a simple summation transformer to combine the fault currents but the alternative
of sequence networks is used in some areas.
In common with all circuits which run in parallel with the power system, the pilot
wires are subject to induced voltages when zero sequence current is flowing in the parallel path. Thus earth-fault conditions can cause relatively high induced voltages
depending on the length of common path between the pilots and zero sequence fault
current, the coupling coefficient between the two circuits and the magnitude of the
zero sequence current. Pilot wire protection must therefore be designed to cater for
this induced voltage. Unfortunately, the simple approach used in telecommunication
circuits of by-passing the induced energy to earth by surge suppressors cannot be used
with pilot wire protection because the pilot wires are required to be active during the
fault condition to stabilise the protection or to enable tripping. The approach has
always been to float the pilots so that they cannot be affected by the flow of longitudinal zero sequence current and thus very high voltage withstand levels are required on
the pilot circuits and these have been standardised as 5 kV or 15 kV. The 5 kV level is
applicable to distribution cable networks where the effective coupling coefficient
between pilots and zero sequence current path is relatively low. The 15 kV level is
required where the coupling coefficient between the two paths is relatively high or at
transmission voltage levels where induced voltages are generally higher. The development of differential protection using, for example, rented telephone circuits also
means that surge suppressors cannot be used, and again, 15 kV isolation transformers
must always be connected between the relay and the telephone system.
Solkor R system
A pilot wire protection is characterised by the way in which the comparison of the
two ends is done and the way in which the transient unbalance between ends is
catered for. A typical scheme is shown in Fig. 22.11. This is Solkor R protection and
uses the principle of current balance to obtain stability during through-fault conditions. The basic current balance scheme requires connection of the relay at the electrical centre point of the pilots.This theoretically ensures that the secondary currents
will cancel because the CT excitation currents will be equal. In practice, dissimilar
CTs and CT transient saturation mean that the excitation currents can be different
during steady-state and considerably different during transient conditions leading
to substantial spill currents.
The physical siting of the relay in the middle of the pilots is not practical and
the scheme requires a relay at each end. Diode switching is arranged so that the
electrical centre of the pilots is moved end-to-end in response to the polarity of the
summation transformer output, thus keeping both relays stable.
Protective Systems
613
Fig. 22.11 Solkor R pilot wire protection.
Although Solkor R is in essence a current balance scheme, a current-to-voltage
conversion is made by the summation transformer and pilot voltage limiting nonlinear resistance. This voltage is then used to drive current around the pilot circuit
which is fixed in ohmic value by having pilot padding resistors. The diodes in this
pilot loop ensure that the relays are always at the negative end of the voltage divider
created by the fixed resistor and the pilot resistance. By making the fixed resistor
1750 W and padding the pilots to 1000 W the relays have a negative bias which is
effective because they are positively polarised by diodes connected in series with
them. The important factor to note is the absolute and instant application of the
bias. In biased relays generally the smoothing sometimes required (e.g. when biasing
is arranged within magnetic circuits) causes delay in the establishment of the bias
and hence the requirement to use a relatively slow measuring relay to avoid
transient instability.
Solkor Rf system
This protection is a development of the Solkor R range but utilises a double output
on summation transformer to produce a sine wave current flowing through the pilots
composed of alternative positive and negative pulses. Solkor R has half wave unidirectional pulses current in the pilots. The advantage of the Rf system is that for
internal faults the protection operation is faster. Also, the effective a.c. pilot current
enables interposing transformers to be inserted in the pilot circuit. These transformers are used to provide 15 kV barriers between the pilot and relay circuits for
those conditions where the possibility exists of high voltages being induced into the
pilots.
Figure 22.12 shows the Solkor Rf connections.
Solkor N system
This is a modern numeric protection which utilises either RS485 twisted pair cable
(up to 1.2 km) or optical fibre cable (up to 49 km) for the end-to-end signalling
channel. Because it exploits the processing power of modern microprocessor chips,
614
Handbook of Electrical Installation Practice
D1
D2
Rp
Ra
PILOT CABLE
Rp
Ra
D4
D3
N1
N1
N
N
B
Y
R
B
Y
R
D8
D7
Ra
PILOT CABLE
Ra
SOLKOR Rf BASIC CIRCUIT
D5
D6
Fig. 22.12 Solkor Rf protection schematic.
it offers numerous integral features that are either not available on SolkorR/Rf, or
require much additional equipment. Solkor N incorporates selectable intertrip facilities between ends and also incorporates back-up overcurrent and earth fault
inverse or definite time protection. These features can be selected to either operate
if the differential protection fails (due to, say, a faulty signalling channel) or to be
always operational. The differential comparison is performed on a phase-by-phase
basis by two-stage comparators. The lower stage compares the magnitudes of the
currents entering and leaving the protected circuit and gives sensitive settings to
detect low-level faults. The higher stage compares the phase angle difference
between the entering and leaving currents and thus overcomes measurement errors
at high fault levels. The relays operate if either stage differential comparators
operate. Because of the phase-by-phase comparison, the sensitivities are the same
on all phases and no summation transformers are used.
The protection monitors the end-to-end communication channels and the differential protection will not trip for any received data in which an error is detected.
As with all modern numeric relays, the equipment provides the facility for oscillographic fault recording as well as digital indication of local and remote currents.
These features can be accessed either via a lap-top computer plugged into a relay
port or remotely via a substation SCADA or LAN system.
Transformer differential protection
Transformer differential protection compares the primary and secondary currents
of a transformer and is stable when these indicate that a fault is external to the
transformer. The problem is complicated by the variable ratio of the power transformer (due to tap change) and the transformer winding configuration and earthing which can cause different fault current distribution each side of the transformer.
In general, the transformer winding configuration is allowed for by using starconnected CTs with power transformer delta windings, and delta-connected CTs
with power transformer star windings.This also excludes zero sequence current from
the differential relay which avoids the problems caused by different earthing
Protective Systems
615
Fig. 22.13 Restricted earth-fault protection.
arrangements of the two power systems linked by the power transformer. Transformer protection is dealt with in detail later.
Restricted earth-fault protection
Restricted earth-fault protection uses the high impedance principle which gives
extremely good stability with low settings because the settings are determined by
characteristics of the CTs which are not directly related to the characteristics of the
CTs which determine stability (Fig. 22.13).Thus low settings with high stability levels
can be obtained and this gives very good earth-fault coverage.
The stability criterion of a high impedance system is that the relay setting voltage
is higher than that calculated by assuming that the maximum current is flowing in
the saturated CT and thus producing a voltage equal to the maximum secondary
current times the CT winding resistance plus lead burden resistance. The setting is
determined by the secondary current required to energise the CTs and the relay at
the relay setting voltage, plus the current taken by a setting resistor which is
generally connected in parallel with the relay in order to increase the setting to a
value reasonably above the steady-state unbalance that may be expected from the
CTs. Details of restricted earth-fault protection are discussed later.
Busbar zone protection
The requirements of busbar zone protection are dominated by the stability requirements because the incidence of busbar faults is so low and the incorrect operation
of busbar zone protection can have such wide ranging effects.
With fully enclosed metal-clad switchgear, simple busbar protection is possible by
lightly insulating the switchgear enclosing frame and connecting it to earth through
a CT feeding a simple relay. This system of frame-leakage protection only detects
earth fault so that the possibility of phase-to-phase faults free from earth is an
important factor in deciding whether this scheme is suitable.
Most modern numeric relays have programmable low-set starters, which can be
mapped to selected output contacts. Also, status input is provided that can be
616
Handbook of Electrical Installation Practice
selected to block any relay function.The availability of these features has given users
the possibility of a very low cost logic busbar protection called busbar blocking.
As an example, consider a switchboard with all the circuits fitted with Argus
numeric overcurrent and earth fault relays. These relays incorporate low-set starters
as well as transient-free high-set elements.The incoming panel should have the highset elements set so that they will operate for any busbar fault under all plant conditions. These elements should be programmed to operate after a short time delay,
typically 100 ms. The outgoing panel relays should have their starters mapped to a
selected output contact on each relay. These contacts should be wired in parallel
and connected to block the high-set element on the incomer. In the event of a fault
on any outgoing feeder panel, the relevant starter will operate and block the highset elements on the incomer so that only the faulted feeder panel trips. If a busbar
fault occurs, none of the outgoing feeders will detect the fault and the incomer will
trip in the set 100 ms time and clear the fault. The time delay is incorporated to
ensure stability during transient conditions.
This system is normally only applicable to radial systems where there is no possibility of a back-feed into a busbar fault from an outgoing feeder. If this condition
can arise then directional relays must be fitted to these panels. This busbar blocking protection is becoming increasingly popular on new MV switchgear installations
and has an excellent operating record.
With important busbars, the advent of a busbar fault, although an unlikely occurrence, generally causes so much disruption to the power system that high speed
differential protection is applied.
The problems of differential busbar protection are: the through-fault current has
the same magnitude as internal faults because the busbars have virtually no impedance; the through-fault current may be shared by several circuits feeding into
the busbar and leave the busbar by only one circuit thus creating conditions for
unbalance in the combination of the CT outputs; and complex busbar arrangements require circuits to be switched from one busbar to another which creates the
potentially hazardous requirement of switching CT secondary circuits. This later
problem is overcome by using an overall check zone and applying sensitive alarm
relays which detect the unbalance caused by load current when a CT is not
connected.
The problem of high through-fault currents coupled with the sharing of the input
current is overcome by using the high impedance circulating current differential
scheme, i.e. busbar zone protection uses the same basic scheme as that used in
restricted earth-fault protection.
Circulating current protection
There is a tendency to use mesh and breaker and a half substation arrangements
and in these the circuits are not switched, so that check zones are not required and
the high impedance scheme is used as a plain circulating current scheme. It is used
whenever possible because of its good performance and simplicity. Reactors, interconnectors, auto-transformers and generator stators may be protected by high
impedance circulating current protection, the only limitation being the capability of
the CTs (which must be low reactance type) to support the lead burden.
Protective Systems
617
TRANSFORMER PROTECTION
Protective schemes applied to transformers play a vital role in the economics and
operation of a power system. Their percentage cost is extremely small, making it
totally uneconomic to apply anything less than a complete scheme of protection
especially to large transformer units. On smaller transformers where their loss may
not be so important to system operation, the protection applied must be balanced
against economic considerations.
To design a protective scheme for a transformer it is necessary to have a knowledge of faults that have to be detected.
Figure 22.14 shows the types of fault that can be experienced, on a transformer.
These are earth-fault on h.v. external connections; phase-to-phase on h.v. external
connections; internal earth-fault on h.v windings; internal phase-to-phase fault on
h.v. windings; short-circuit between turns h.v. windings; earth-fault on l.v. external
connections; phase-to phase fault on l.v. external connections; internal earth-fault
on l.v. windings; internal phase-to-phase fault on l.v. windings; short-circuit between
turns l.v. windings; earth-fault on tertiary winding; short-circuit between turns
tertiary winding; sustained system earth-fault; and sustained system phase-tophase fault.
Under fault conditions, current in the transformer windings is distributed in different ways and is of varying quantity depending on the transformer winding connections and, in to case of earth-faults, the method of earthing. An understanding
of these is essential for the design of protection schemes, particularly balanced differential schemes, the performance of directional relays and setting of overcurrent
and earth-fault relays.
A detailed analysis is outside the scope of this chapter. A full treatise is given in
Fault Calculations by C.H.W. Lackey, published by Oliver and Boyd Ltd.
Current balance schemes
Most protective schemes applied to transformers are based on the current balance
principle of magnitude comparison of currents flowing into and out of the transformer (Fig. 22.10). This principle can be used to protect the transformer winding
separately or as an overall unit. However, in the latter case certain refinements are
necessary.
Separate winding protection
Relating the current balance principle to each winding of the transformer separately
it can be seen (Fig. 22.13) that under magnetising, normal load and through-fault
conditions the current circulates between the CTs which, provided they have similar
characteristics, results in no current flowing in the relay. Stability is therefore
ensured under all external conditions. If, however, an earth fault occurs within the
zone of the CTs an out-of-balance condition exists whereby current flows through
the relay.
The main problem experienced in first applying a current balance scheme was
retaining stability on through-faults accompanied by unequal saturation of the CTs
during the first few cycles after the fault zero. This was overcome by using a relay
Handbook of Electrical Installation Practice
Fig. 22.14 Types of transformer fault.
618
Protective Systems
619
of high impedance which has a large value stabilising resistor connected in the relay
circuit.
This scheme using high impedance relays has now been in use for many years,
the simplicity in application being that the performance of the protection on both
stability and fault setting can be calculated with certainty. For a given through-fault
current (Ia) the maximum voltage that can occur across the relay circuits is given
by:
VR =
Ia
(R + X )
N
where VR = maximum voltage across relay circuit
R = maximum lead resistance
X = CT secondary resistance
N = CT ratio.
This is based on the assumption of the worst condition when one CT completely
saturates and ceases to transform any part of the primary fault current, while the
other CTs continue to transform accurately.
If the setting voltage of the relay is made equal to or greater than this voltage the
protection will be stable for currents above the maximum through-fault current
level. In practice, the knee point voltage of the CTs is designed to be at least twice
this value.
The fault setting of the protection is calculated from:
I FS = N (I R + I A + I B )
where IFS = fault setting
IR
= ralay circuit current at relay setting voltage
IA, IB = CT magnetising currents at relay setting voltage
N
= CT ratio.
The primary fault setting should be adjusted to the level required by the addition
of resistors connected across the relay circuit to increase the relay circuit current
IR.
The circuit of a typical high impedance restricted earth-fault realy is shown in Fig.
22.15. The operating element is an attracted-armature relay energised from a fullwave rectifier. The capacitor C in conjunction with the resistors form a low-pass
filter circuit. The function of this is to increase the setting at harmonic frequencies,
thus retaining stability when high frequency currents are produced in certain installations during switching.
The links enable the voltage setting to be adjusted and non-linear resistor M1
limits the peak voltage output from the CTs during internal faults and so protects
the relay and secondary wiring.
Summarising, separate winding current balance schemes are unaffected by load
current, external fault or magnetising inrush currents; and unaffected by the ratio
620
Handbook of Electrical Installation Practice
Fig. 22.15 High impedance relay.
of transformer. The complete winding can be protected with solidly earthed neutral
but not when resistance earthed, and it will not detect phase faults (three-phase
protection), shorted turns or open-circuits.
Overall differential protection
The current balance principle can also be applied to cover both primary and secondary windings. However, an overall scheme is affected by magnetising current,
although it remains balanced under normal load or through-faults providing CT
ratios are matched; mismatch in CTs causes spill current to flow in the relay circuit.
As most transformers are equipped with tap-changing the design of an overall
scheme for three-phase transformers must also take account of this mismatch under
through-fault conditions.
Thus the application of an overall scheme to three-phase transformers requires
a biased relay with characteristics as illustrated in Fig. 22.10 to maintain stability on
tap-changing and during magnetising inrush currents.
In both cases the out-of-balance current flowing through the relay circuit may be
several times the basic fault setting. A bias winding ensures that the relay remains
stable under these conditions, as explained on p. 611. Usual practice is to arrange
the bias characteristic with a slope of at least twice the slope of the expected steadystate spill current characteristic.
During internal faults the whole of the available CT secondary current passes
through the relay operating circuit giving the rapid rise in operating current.
The second reason, already mentioned, for using a biased relay for overall transformer protention is that spill current may flow during a magnetising surge. This
spill current contains a large percentage of second and higher harmonics and it is
convenient to convert these harmonics into bias current, thereby preventing the
relay from operating during magnetising inrush conditions.
One thing to be considered with ‘harmonic bias’ is that harmonics are also present
during internal faults due to CT saturation. To ensure that the relay will operate
under all internal fault conditions the harmonic bias unit should preferably be
Protective Systems
621
designed to use only second harmonic which predominates in a magnetising
surge.
Buchholz relay
On all but the smallest transfomers it is usual practice to install a Buchholz gas relay.
This device detects severe faults from the resultant surge in the oil and low level
faults by the measurement of accumulation of gas. It consists of two pivoted floats
carrying mercury switches contained in a chamber which is connected in the pipe
between the top of the transformer tank and the oil conservator. Under normal conditions the Buchholz relay is full of oil, the floats are fully raised and the mercury
switches are open.
An electrical fault inside the transformer tank is accompanied by the generation
of gas and, if the fault current is high enough, by a surge of oil from the tank to the
conservator. Gas bubbles due to a core fault are generated slowly and collect in the
top of the relay. As they collect, the oil level drops and the upper float turns on its
pivot until the mercury switch closes. This generates an alarm. Similarly, incipient
windings insulation faults and interturn faults which produce gas by decomposition
of insulation material and oil will be detected. Such faults are of very low current
magnitude and the Buchholz relay is the only satisfactory method of detection. As
these faults are not serious, operation of the relay generates an alarm but does not
trip out the transformer.
Serious electrical faults, such as a flashover between connections inside the main
tank, generate gas rapidly and produce a surge of oil which forces the lower float
to rotate about its pivot, causing the lower mercury switch to close. This is arranged
to trip both h.v. and l.v. circuit-breakers. In addition to the above, serious oil leakage
is detected initially by the upper float which gives an alarm and finally, by the lower
float, which disconnects the transformer before dangerous electrical faults result.
Application of two-winding transformer
It is common practice to apply both overall differential relays and restricted earthfault relays to transformers over about 5 MVA. The amount of protection must be
assessed against the importance to the system and economic considerations. A
typical scheme of protection for a star/delta transformer is shown in Fig. 22.16. The
reason for applying both types of relays is to obtain maximum coverage of earthfault and phase faults.
Consider a transformer that is resistance-earthed. The current available on an
internal earth-fault for operation of a differential form of protection could be inadequate because of the transformer action. This is the reason why a separate form
of earth-fault protection is added even when solid earthing is employed.
Some care must also be exercised in choosing the CT ratios and connections. The
CT ratio must compensate for the difference in primary and secondary currents of
the transformer and their connections must compensate for the phase difference.
The restricted earth-fault relay can be operated from a completely separate set
of line CTs or it can be combined as shown in Fig. 22.16 with the overall protection
by incorporating it into the interposing CT circuit. A CT is required, of course, in
622
Handbook of Electrical Installation Practice
Fig. 22.16 Differential protection with supplementary earth-fault protection.
the neutral-to-earth connection. The advantage of the restricted earth-fault relay is
that it is energised from a CT which ‘sees’ the whole of the fault current and not
just the primary side equivalent of it. Where the system is solidly earthed an overall
transformer protection with a setting of about 30% gives complete phase-to-earth
fault protection of the delta winding and about 80% of the star winding. In that case
additional restricted earth-fault protection is not required for the delta winding, but
if it is fitted to the start winding it will detect faults much nearer to the neutral end
of the winding.
In addition to overall protection it is usual practice to protect all but the smallest transformers against interturn faults using a Buchholz relay. Back-up protection is normally provided by idmtl overcurrent relays. In applying restricted
earth-fault (REF) protection to distribution networks such as 415 V, three-phase,
four-wire systems care must be taken in the primary connection of the neutral CT,
which is dependent on the earthing position. Two neutral transformers may be
required in order to detect the total zero sequence current flowing as a result of a
fault.
Protective Systems
623
Table 22.1 Transformer protection.
* Standby earth fault.
Table 22.1 gives a general guide as to the protection suitable for different transformer ratings, although it should be noted that modern relays such as Duobias M
allow economical protection over the complete range.
Duobias M system
Although Duobias protection, using transductor type relays described above, is used
throughout the world in great numbers, advances in technology have allowed the
development of a microprocessor version known as Duobias M (Figs 22.17 and
22.18). This protection incorporates within software two restricted earth-fault elements, models of interposing CTs for almost every primary transformer configuration and inherent phase angle change compensation. The algorithms also include
operation and indication for additional inputs such as Buchholz and winding temperature protection, and the data storage and fault recording is included. This development allows an extremely economic but very comprehensive system to be applied
to a full range of power transformers.
ROTATING PLANT
The operation of rotating machines can be affected by faults within or by external
disturbances on the network. The protection of a machine must therefore be
designed to be highly discriminative to react efficiently on internal faults and external disturbances.
The number and type of protective relays applied to a machine is a function of
the machine characteristics such as size, driving device, single of parallel operation,
624
Handbook of Electrical Installation Practice
a
A
C
A
+10%
90MVA 132/33kV –20% Yd11
B
b
c
400/1
1600/1
a
B
b
C
c
Earth
Trans.
400/1
1600/1
17 18
18 17
21 22
22 21
25 26
26 25
13 14
14 13
ANI
HV Interposing C.T. settings
Con = Yd11,30°
Mult = 0.95
AN2
HV Interposing C.T. settings
Con = Ydy0,0°
Mult = 1.0
Fig. 22.17 Duobias M system.
short-circuit withstand current (and that of the network), and type and protection
of network earthing. It is also related to economics such as cost of protection in relation to that of machine and the consequences resulting from a breakdown.
Alternators
On occurrence of a short-circuit at the terminals of an alternator the short-circuit
current is initially between five and ten times that of full load of the machine because
the initial stator current is limited only by the subtransient leakage reactance. This
is related to the flux set up by the stator mmf which fails to cross the air gap. The
increase in stator current causes a demagnetising effect by opposing the air gap flux
but it is an appreciable time before a major change in the air gap flux can be effected.
The net effect is a gradual decrease in the short-circuit current over a period
of seconds to a value which may be considerably below full load current of the
machine.
Possible faults on alternators
An alternator may experience various types of faults, the most common being stator
faults which consist of earth-faults, phase-to-phase short-circuits, short-circuits
between turns, open-circuits in windings and overheating. These failures are usually
caused by overvoltage and/or deterioration of the insulation.
Protective Systems
Fig. 22.18 Duobias measuring points.
625
626
Handbook of Electrical Installation Practice
Protection against external faults
This type of alternator fault can be detected by an impedance relay or by an overcurrent relay capable of responding to the fall-off in fault current caused by the
impedance change described above, while having under normal operating conditions a pick-up above the nominal current and a time-delay characteristic that will
co-ordinate with other relays.
This is achieved by using the voltage on the machine terminals to determine the
time–current characteristics of the relay. Under normal or near normal voltage conditions such as might occur on overload the relay has a long inverse time characteristic. However, under short-circuit conditions when the terminal voltage falls,
the time–current characteristic is automatically selected to a normal time–current
characteristic.
Unbalanced loads
Alternators can usually only support a small percentage of unbalanced loading permanently and must be disconnected from the system before it reaches too high a
level. This condition is detected by a negative phase sequence relay with a time–
current characteristic of the form I 22t where I2 = negative phase sequence current in
terms of full load rating, and t = time.
This from of protection is usually only applied to the higher rated machines.
Overloads
Overloads causing heating of the stator windings must be eliminated before a temperature dangerous for the machine is reached. Depending on the rating of the
machine the overload protection may take the form of an overcurrent relay, a
thermal relay or temperature sensors. For small machines (i.e. hundreds of VA)
there are relays which simultaneously provide overload protection by means of lowset elements and external phase-to-phase fault protection by means of high-set
elements. For machines above 2 MVA platinum temperature sensors are generally
provided. These are embedded in the stator windings and a decision to use these
must be made before the machine is manufactured.
Reverse power conditions
It is usual practice to apply protection against failure of the prime on back-pressure
turbine sets and this usually takes the form of a sensitive reverse power relay, having
a setting of 0.5%. This type of relay can also be used as a low forward power interlock relay to prevent circuit-breaker tripping causing turbine runaway.
As a general rule all alternators, if they may be operating in parallel with other
sources, should also be provided with reverse power protection which, depending
on type of machine, may not have to be extremely sensitive; for example, on diesel
generators a setting of 5–10% is quite adequate.
Protection against internal faults
There are a number of different types of internal faults requiring specific protective
systems.
Protective Systems
627
Stator sensitive earth-fault protection. The type of earth-fault protection applied
depends on the type of earthing of the machine. There are two forms generally
employed – resistor earthing or an earthing transformer.
An earth-fault occurring at the terminals of the alternator with resistor earthing
causes full load current to flow. However, should the fault occur closer to the neutral
point the voltage available to drive fault current is reduced and therefore its magnitude is reduced. Eventually a point in the winding is reached where the voltage
is just sufficient to drive current equal to the fault setting of the protection. The
remainder of the winding between this point and the neutral is thus not protected
against earth-faults. Care must therefore be taken when selecting the value of the
neutral resistor and the setting of the relay to ensure that this unprotected section
is as small as practical. The protection consists of a current relay fed from a ring CT
in the neutral connection to erath.
Where a distribution or earthing transformer is used a voltage operated relay
is connected across the secondary side of the transformer associated with the
earthing impedance.
Stator, phase and earth-fault. The standard scheme of protection for the stator
windings is the simple overall current balance scheme using a high impedance relay.
This employs similar CTs at the line and neutral end of each phase of the alternator, as explained earlier in this chapter. It is possible, although not strictly necessary,
to apply an overall biased differential relay for this purpose such as that described
for transformers.
Rotor earth-fault. Modern alternators operate with their field winding system
unearthed but it is still necessary to protect against breakdown of insulation. A
number of schemes are available to provide this protection, the most common being
a relay which applies a d.c. voltage between the circuit rotor and earth to detect any
circulating d.c. current.
A similar scheme using a.c. injection is also available.
Failure of field system. Protection against loss of field is provided by an impedance
relay with an offset circular characteristic (called ‘offset mho’). Care must be taken
in the setting of the relay to ensure that it is not affected by power swings. This protection is usually only applied to larger turbo-alternators.
Application of protection to alternators
In considering which of the foregoing types of protection to apply one must, as
already stated, look at rating, importance and cost.
As a general guide, if considering the protection of a diesel alternator with rating
up to hundreds of VA, one would recommend the following schemes as minimum:
overall phase and earth-fault; stator earth-fault; voltage restrained overcurrent; and
reverse power.
For a turbo-alternator rated at tens of MVA all of the schemes described would
be applied.
Modern practice is to incorporate all or a selected variety of the above protection elements in a single multifunction relay, such as the Gamma range.
628
Handbook of Electrical Installation Practice
Motors
Motors, both synchronous and asynchronous, form an important part of every industrial plant or power system network. The usual faults experienced by motors are:
sustained overloads; single-phasing; and phase faults and earth-faults on motor
windings and connections.
Overloads and single-phasing
The most generally applied motor protection relay is a thermal relay. To be effective the relay must have a setting slightly in excess of the motor full load current
but also remain stable under motor starting conditions which can result, depending
on method of starting, in currents of many times full load for several seconds.
Several types of thermal relays are available but generally they are based either
on a bimetallic strip principle of on a static thermal image principle.
It is usual to have, in the same relay, an unbalanced load-detecting circuit to
prevent operation of the motor under single-phasing conditions. This is necessary
for although a motor will continue to run on only two phases it may overheat.
Phase and earth-faults
All motors above 75 kW should be provided with instantaneous relays to detect the
above faults. These relay elements can also be incorporated in the thermal relay.
In addition an REF system should be provided for earth-faults, using a similar
arrangement to that for transformers.
The use of instantaneous elements depends also on the controlling circuitry of the
motor. If a motor is controlled by a contactor which incorporates fuses, it is normal
practice not to include instantaneous elements, allowing the fuses to cover multiphase
faults. However some form of earth-fault protection is still recommended.
As far as relays performing other functions are concerned no definite rule can be
given to decide above what rating they should be applied. Economic considerations,
principally the cost of protection including the necessary CTs, must be compared
with the cost of the motor as well as the importance of the motor in the operation
of an industrial process, and the consequences of it being out of service.
The use of a starting device incorporating either resistors, an auto-transformer
or inductance in the stator circuit does not modify the protection requirements.
However, the relay characteristics and settings must be defined in relation to the
starting current and time corresponding to the use of the starting device.
Other forms of essential protection which may be used depending on the type of
motor, in addition to those described, are: undervoltage; loss of field; negative
sequence; locked rotor; and undercurrent.
The use of static components has made a big impact on the protection of machines.
It is now possible to incorporate many of the protective relays described into an overall
protection module using the international 483 mm rack mounted principle.
RELAY ACCOMMODATION
As well as changes in the technology of relay circuits with the introduction of microprocessors, there has been a significant change in the types of cases housing the relay
elements.
Protective Systems
629
Fig. 22.19 Modular case system.
For a number of years relay elements have been housed in separate cases for
mounting on sheet steel panels or switchgear top plates.
Relays are now smaller and a modular form of case has been developed which is
suitable for rack mounting or traditional panel mounting. The case is of uniform
height (international standard 4 U) and is available in a number of case widths, sizes
2, 3, 4, 6 and 8. They have the facility of being grouped horizontally or vertically in
tiers giving great flexibility to layout design within a rack.
This enables several relays of different types to be grouped together to provide
a system of protection for a particular application.The modular case system is shown
in Fig. 22.19.
For front of panel testing, a test block is available housed in a size 2 case which
provides the link between the test supplies and the relay as scheme wiring. Removal
of the test block cover can be made to isolate the auxiliary d.c. supply to all connected relays automatically. Insertion of a test plug into the test block can be
arranged to short-circuit the CT circuits and enable injection testing by external test
equipment through the test sockets on the plug front face and also link the d.c.
supply as required. The test block and plug are shown in Fig. 22.20.
The basic construction of a relay should not affect commissioning because relay
specifications ensure that relays are constructed to allow for these procedures.
630
Handbook of Electrical Installation Practice
Fig. 22.20 Test plug and block (simplified).
However, if for some reason the covers of a relay need to be removed, suitable precautions will be needed dependent on the relay construction.
Relays with sensitive moving parts and magnetic circuits will need to be kept
clean with particular avoidance of ferrous metal particles.
Microprocessor relays will require special precautions against static discharge as
outlined in the following section.
Handling of static sensitive devices/subassemblies
All components can be said to be static sensitive, some being more sensitive than
others.The degree of sensitivity is much greater in individual devices than when these
same devices are mounted on a pcb. However, static awareness and precautionary
handling procedures are essential to ensure that even pcb subassemblies carrying
static sensitive devices (SSD) are not stressed by exposure to static discharge.
Static discharge
The charge which can build up on the human body due to normal movement is more
than enough to cause irreparable damage to SSDs. This static charge can be made
much worse, and build up much more quickly, if the person is wearing, for example,
clothes made from man-made fibres or plastics-soled shoes. To ensure that the
danger of damage to SSDs is kept to a minimum, they should only be handled by
Protective Systems
631
persons who are aware of the nature of static discharge, and only in a static protective workstation.
Static protective workstation
This is an area which has been specially prepared to reduce the risk of damage to
SSDs and it is constructed as follows: clean the surface of the bench to be used;
place on this a metal plate; cover the plate with a sheet of conducting plastics; and
on top place an area of anti-static polyethylene.
Firmly fix the last mentioned item to the worktop and connect it to a good earth
via a resistor in the range 200 kW to 500 kW. This is now the anti-static work surface.
Use of the workstation
The operator should not wear nylon or synthetic overgowns and should endeavour
to ensure that his clothing does not come into contact with any SSD, i.e. roll-up
sleeves. The operator must make sure that the personal grounding system, such as
grounding wrist straps, are attached electrically to the anti-static work surface. Note
that the operator should be connected to the grounding system for at least 10 s
before handling the SSD.
Handling of pcbs
Do not remove or insert pcbs with SSD on them with the power on as transient
voltages can damage the devices. Switch off all supplies, remove/insert the pcb with
the minimum of handling and on pcb edges only, and only place the pcb on the antistatic work surface.
COMMISSIONING TESTS
Commissioning tests are required to check that the relays are correctly connected
to the appropriate instrument transformers and that their operation is within reasonable limits. Generally, commissioning tests are limited by the need to transport
the necessary equipment to site and the site conditions which may include temporary power supplies; thus the commissioning test instructions have to take this into
account.
In preparing a test instruction, there is a dilemma in deciding the level of basic
knowledge of the engineer receiving it. In general, information more appropriate
to national standards and text books is not included in a particular test instruction
because these are available to supplement the manufacturer’s test instructions.
Because protective relays are generally measuring current, the concept of the
current source is very important. A voltage source is characterised by the fact that
a load applied to it does not cause the voltage to change in any way. Conversely, a
current source is characterised by the fact that a load introduced into the current
circuit does not change the current in any way. The character of a CT fed by a power
system dictates that protective relays in service are energised by very good current
sources.
Test equipment based on mains supply is obviously fundamentally more a voltage source than a current source, so unless precautions are taken, the inservice
632
Handbook of Electrical Installation Practice
condition is not correctly represented by simple test arrangements and incorrect
results will be obtained.
For example, when timing an overcurrent relay, the inductance and resistance of
the coil dictate the time constant of current build-up within the coil if it is fed from
a voltage source. Thus a slower time of operation can be obtained to the true inservice condition where with the current source of power system feeding a CT, the
current is established in the coil at full magnitude without any delay.
However, the most common problem with using a poor current source is due to
the non-linear nature of relay impedance. An induction disc idmtl relay obtains its
current–time characteristic by saturation of the core material of the induction disc
motor. This means that at an energising level above the point at which the definite
minimum time is obtained (twenty times the plug setting) the relay impedance is
virtually the winding resistance of the coil, whereas at lower levels the inductance
of the coil has significant value. Typically, a 5 A relay impedance varies from 0.12 to
0.5 W and a 1 A relay from 3.2 to 1.5 V at 100% tap over its working range. Other
taps give higher or lower impedance and generally at the higher percentage taps
the variation between impedance at low currents and high currents is not so marked.
Of course, the impedance of the relay varies with instantaneous values of current
so that the impedances quoted are somewhat fictitious because they represent a
combination of a sinusoidal current and a non-linear voltage. Also, the voltage is
processed by an instrument giving a value appropriate to the type of instrument and
its calibration, generally the r.m.s. equivalent of the average value, i.e. a moving coil
type of a.c. instrument.
Once the non-linearity of the relay impedance is understood, the requirement for
a suitable current source is evident. Obviously it is not practical to produce a perfect
current source and it is therefore necessary to establish the rules for determining
the suitability of the various degrees of perfection in a current source. In the laboratory, it is possible to establish very good current sources by the use of heavy
current rigs feeding CTs. The next level below this is to use phase-to-neutral mains
voltage with resistance to limit the current and below that to use phase-to-neutral
mains voltage with resistance to limit the current. Tests on site are generally done
with a fixed resistor fed by a constantly variable autotransformer which is used for
fine control. If the same value of resistor has to be used for all currents, the autotransformer may be at a very low voltage for some current levels, which immediately questions the suitability of the current source. The first check on the suitability
of a current source is to observe the ammeter feeding the relay from the current
source while short-circuiting the relay. Obviously with a perfect current source the
ammeter should show no change whether the relay is in circuit or not. If significant
change is detected in the current, then the linearity of the relay impedance should
be checked before settings and timings obtained with that particular test rig are
agreed.
The requirement for fundamental accuracy in non-unit protection leads to a
necessity to prove that the current source is suitable to determine the true setting
or timing of a relay. This can be achieved by repeating the test with an improved
current source until no change is apparent in the result between, say, maximum
resistance fed by phase-to-neutral voltage and the equivalent maximum resistance
fed by phase-to-phase voltage. In some cases, or when absolute assurance is required,
Protective Systems
633
the heavy current rig is the only recourse but, even in this case, care must be taken
that saturation of the various current limiting reactors or impedance changing transformers does not distort the current feeding the primary of the CT. This is particularly important in high impedance schemes where, for an internal fault, the CT is
virtually unloaded and thus the impedance reflected into the primary, although
extremely small, may still be significant if the heavy current machine is not carefully
matched to the CT and the relay combination. It should also be appreciated that with
a distorted waveshape the ammeter is unlikely to have the same relative response as
the relay, so that the only true measurement is when the current is completely sinusoidal because relay and ammeter are both calibrated using sine-wave current.
In some critical relays, the harmonic content in the driving voltage can cause
incorrect measurement and this must then be reduced by using inductance to
provide a current source simulating the power system conditions more accurately
than the more commonly used resistance current limiting.
Another common problem is the determination of direction of current. This is
important in a relative sense for establishing the residual connection of CTs, and in
a fundamental sense for setting up the operate direction of directional relays.
Fig. 22.21 Ratio and directional tests with neutral CT.
Fig. 22.22 Ratio and directional tests without neutral CT.
634
Handbook of Electrical Installation Practice
In a REF arrangement, using four CTs, each phase CT may be connected to give
minimum spill current with the neutral CT, as shown in Fig. 22.21, but with only
three CTs the phasing-out must be done by phase-to-phase primary injection as
shown in Fig. 22.22 and observation of the out-of-balance current obtained between
each pair of CTs. In each case, ammeters should be available as shown for the energised CTs so that the CT ratios can be checked coincidentally.
Because conventions are not universally standardised for windings, it is not possible to be precise about whether connecting start to start and finish to finish will
give a reversal of polarity or not. Thus the direction of a directional element should
be confirmed in relation to an independent quantity. This quantity is generally load
current, for which the direction, in relation to the power system, is clearly known.
In some cases the load may have a low power factor and thus the phase angle
between load current and voltage at the relay terminals may not be decisive in defining the direction. If the relay has a variable characteristic angle, study of the vectors
may allow direction to be checked at a different relay angle before finally setting
the relay back to the setting required for fault current conditions.
Directional earth-fault relays are particularly difficult to check for polarity
because they are fed from residual voltage which gives a reversal of the effective
voltage signal, which can be confusing. Again, load current gives the best overall
check on direction and a red phase-to-earth fault is represented by disconnecting
and short-circuiting the yellow and blue CTs to provide only red load current as a
residual current to the relay, and disconnecting the red phase winding of the VT to
represent the total collapse of the red phase voltage which occurs due to a close-up
red earth-fault. The red phase main secondary winding should be short-circuited to
provide the correct in-fault loading on the directional element.
An important aspect in all testing is to take account of the heat generated in a
relay when subject to relatively long energisation times at currents in excess of
rating. Apart from the possibility of damage to the relay by excessive heat, lower
levels of heat could affect the performance if the relay is susceptible to self-heating.
Finally, it is worthwhile considering the accuracy of basic test equipment and
simple cross-checks that can be done if some doubt exists with results. With multirange meters it is simple to change their role or cross-check them against each other.
Fundamental instrument accuracy (which is related to full scale) can be of the same
order as relay accuracy, so some thought is necessary in establishing the true accuracy of settings even when supplies, waveshape, temperature and frequency are
within reference conditions. British protective relays are generally made to BS 142
which prescribes the reference conditions for which the various aspects of relay performance shall be declared.
CHAPTER 23
Power Factor Correction and Tariffs
T. Longland, CEng, MIEE
(Technical Manager, Johnson & Phillips (Capacitors) Ltd)
Power capacitors have been employed in many and varied ways in industry over
the past 60 years, but their increasing use is often limited by the apparent lack of
practical information on their application. This chapter provides information and
guidance on the selection and use of capacitors for power factor correction.
With increasing electricity charges, and the need to save energy, it is of paramount
importance to both industrial and commercial users of electricity to ensure that their
plant operates at maximum efficiency. This implies that the plant power factor must
be at an economic level.
IMPORTANCE OF POWER FACTOR
Most a.c. electrical machines draw from the supply apparent power in terms of kilovolt amperes (kVA) which is in excess of the useful power, measured in kilowatts
(kW), required by the machine. The ratio of these quantities is known as the power
factor of the load, and is dependent on the type of machine in use. Assuming a constant supply voltage this implies that more current is drawn from the electricity
authority than is actually required.
Power factor =
true power
kW
=
apparent power kVA
A large proportion of the electrical machinery used in industry has an inherently
low power factor, which means that the supply authorities have to generate much
more current than is theoretically required. This excess current flows through generators, cables and transformers in the same manner as the useful current. It is
understood that there are resitive loads such as lighting and heating but these are
generally outweighed by the motive power requirements.
If steps are not taken to improve the power factor of the load all the equipment
from the power station to the factory subcircuit wiring has to be larger than necessary. This results in increased capital expenditure and higher transmission and
distribution losses throughout the whole supply network.
To overcome this problem, and at the same time ensure that generators and cables
are not overloaded with wattless current (as this excess current is termed), the
635
636
Handbook of Electrical Installation Practice
supply authorities often offer reduced terms to consumers whose power factor is
high, or impose penalties for those with low power factor.
THEORY OF POWER FACTOR CORRECTION
The kVA in an a.c. circuit can be resolved into two components: the in-phase component which supplies the useful power (kW), and the wattless component (kvar)
which does no useful work. The phasor sum of the two is the kVA drawn from the
supply. The cosine of the phase angle f1 between the kVA and the kW components
represents the power factor of the load.
The phasor diagram for this is shown in Fig. 23.1. The load current is in phase
with the kVA so that it lags the supply voltage by the same phase angle.
To improve the power factor, equipment drawing kvar of approximately the same
magnitude as the load kvar, but in phase opposition (leading), is connected in parallel with the load. The resultant kVA is now smaller and the new power factor, cos
f2 is increased. Thus any value of cos f2 can be obtained by controlling the magnitude of the leading kvar added. This is shown in Fig. 23.2.
POWER FACTOR IMPROVEMENT
In practice two types of equipment are available to produce leading kvar:
(1) Rotary equipment
Phase advancers, synchronous motors and synchronous
condensers. Where auto-synchronous motors are employed the power factor
correction may be a secondary function.
(2) Static equipment
Capacitors.
Fig. 23.1 Phasor diagram of plant operating at a lagging power factor.
Power Factor Correction and Tariffs
637
Fig. 23.2 Power factor improvement by adding leading kvar to a lagging power factor.
When installing equipment, the following points are normally considered: reliability of the equipment to be installed, probable life of such equipment, capital cost,
maintenance cost, running costs and space required, and ease of installation.
Generally, the capital cost of rotating machinery, both synchronous and phase
advancing, makes its use uneconomical, except where one is using rotating plant
for a dual function-drive and power factor correction. In addition, the wear and
tear inherent in all rotary machines involves additional expense for upkeep and
maintenance.
Capacitors have none of these disadvantages. Compared with other forms of correction, the initial cost is very low, upkeep costs are minimal and they can be used
with the same high efficiency on all sizes of installation. They are compact, reliable,
highly efficient, convenient to install and lend themselves to individual, group or
automatic methods of correction. These facts indicate that, generally speaking,
power factor correction by means of capacitors is the most satisfactory and economical method.
The static capacitor, owing to its low losses, simplicity and high efficiency, is now
used almost universally for power factor correction.
ECONOMIC CONSIDERATIONS
When considering the economics of power factor correction it is important to
remember that any plant used for this purpose does, in general, compensate for
638
Handbook of Electrical Installation Practice
losses and lower the loadings on supply equipment such as cables, transformers,
switchgear and generators.
The rating of the capacitor required to improve the power factor and the saving
achieved depend largely on the electricity tariff. Charges can be related to kVAh,
kvarh, or to md kVA, all of which can be reduced by installing power factor correction capacitors.
As a result of the Electricity Act 1989, the electricity supply industry has become
more fragmented with suppliers and electricity distributors being more diverse and
competitive.
Commercial tariffs include penalty clauses for low power factor and the most economic power factor is assessed on the same basis as for industrial tariffs. Domestic
tariffs are not affected because the power factor is of the order of unity.
A further result of deregulation of the electricity supply market has been the
intercompany mergers and the more widespread selling of electricity to end users
on a contract basis. These contracts often have no apparent power factor penalties.
The net effect of this in the UK has been a 25% reduction in the size of the UK
market for power factor correction capacitors. This is at variance with the rest of
Europe where penalty charges for low power factor are avidly charged and markets
have strengthened.
Power factor correction should always be regarded as an investment with two
opposing considerations. First, the expenditure incurred in the overheads charged
against the capacitor installation, and second, the income brought about by the
saving in the cost of electricity, together with the reduction of losses in the electrical system. The main capacitor overheads are depreciation, interest on capital, electrical losses and maintenance costs. The last two items, in most cases, are covered
by the savings on the losses in the electrical system.
The efficiency of a capacitor installation remains almost constant throughout the
10–12 year life of the capacitor. It is, therefore, usually estimated that an overhead
allowance of approximately 8% to 10% of the installed cost of the equipment be
used.
Where tariffs are based on a standing charge per kVA, plus a charge for each unit
(kWh) supplied, the most economical degree of correction is found when the final
power factor is appoximately 0.97/0.98. It is never economic to attempt to improve
the power factor to unity, as the nearer the approach to unity the more is the kvar
that must be installed for a given improvement. This can be seen from Fig. 23.3.
In the average power factor tariff, where there is a bonus or penalty clause if the
power factor is above or below some datum figure, the most economic power factor
is the datum one.
Table 23.1 indicates how the most economic power factor depends on the type of
tariff. The table has been confined to tariffs applied by the UK electricity companies.
Three worked examples of savings to be made are shown in Table 23.2.
CALCULATION OF CAPACITOR SIZE
There are number of methods of calculating the capacitor size required. Figures 23.4
and 23.5 together with Table 23.3 have been prepared with the object of providing
Power Factor Correction and Tariffs
639
Fig. 23.3 Graph showing how the kvar to be connected varies with the power factor to be
achieved. The curve is based on an initial load at 100 kW at a power factor of 0.65.
speedy and simple methods of ascertaining if any benefit can be derived from
improving the power factor of an industrial or commercial a.c. load.
PRACTICAL POWER FACTOR IMPROVEMENT
Figures 23.4 and 23.5 and Table 23.3 enable the capacitor requirements to be calculated knowing the initial power factor. In practice the problem is to determine
this initial power factor.
The type of tariff that a consumer is charged not only determines the level of correction, but also the method by which the capacitor size is determined.
Maximum demand tariffs
Under an md tariff the md value is recorded on an appropriate meter which measures it either in kW or kVA. This meter usually measures twice the largest number
of kVA (or kW) of md supplied during any half hour period, in any month.
640
Handbook of Electrical Installation Practice
Table 23.1 The most economic power factor previously required by the various UK
electricity companies.
REC
Eastern
East Midlands
London
Merseyside and
North Wales
Midlands
North Eastern
Scottish Hydro Electric
Hydro
North Western
South Eastern
Southern
Scottish Power
South Wales
South Western
Yorkshire
Maximum
demand
charge
based on
Power factor
should be
improved to
Type of
power factor
penalised
kVA
kVA
kW
kW
0.97/0.98
0.97/0.98
0.95
0.93
Maximum demand
Maximum demand
Average
Maximum demand
kVA
kW
kW
0.97/0.98
0.90
0.90
Maximum demand
Average
Average
kW
kW
kVA
kVA
kW
kW
kVA
0.90
0.90
0.97/0.98
0.97/0.98
0.95
0.90
0.97/0.98
Average
Average
Maximum demand
Average
Average
Average
Maximum demand
Table 23.2 Examples of savings to be made by power factor improvement.
Table 23.2 (contd)
642
Handbook of Electrical Installation Practice
Table 23.3 Table of factors for calculating size of capacitor for power factor
improvement.
Power Factor Correction and Tariffs
643
Table 23.3 (contd)
This table gives values of tan f for various of power factor, cos f, and therefore provides a simple
method of calculating values of kvar, and the size of capacitor required to improve the power factor.
Example:
Given 100 kW load to be improved from 0.77 to 0.95 power factor. Factor from table is 0.5.
Capacitor (kvar) = load (kW) ¥ factor to improve from existing to proposed power factor
= 100 ¥ 0.5 = 50 kvar
With these tariffs, therefore, it is only necessary to ensure that the capacitors are
in circuit at the time the md is being reached, if the prime function of the capacitor
installation is to save money by reduced md charges.
Average power factor tariffs
Average power factor tariffs incorporate a power factor penalty clause based on the
average power factor determined from the kWh and kVAh recorded in any metering period.
With this type of tariff, therefore, it is necessary to reduce the number of kvar
hours recorded during the metering period. To do this the capacitor must be in
circuit whenever reactive units are being recorded.
A refinement on this type of tariff, usually found on the continent, penalises
all reactive units, be they leading or lagging. With this type of tariff small steps of
644
Handbook of Electrical Installation Practice
Fig. 23.4 Reduction of kVA loading for constant kW loading by improvement of power
factor.
capacitors are required to ensure that there is no reactive power recorded at any
loading condition.
CAPACITOR SIZE RELATED TO TARIFF
A different calculation is necessary for ascertaining the correct capacitor rating
depending on the particular tariff applicable.
Power Factor Correction and Tariffs
645
Fig. 23.5 Nomogram for determining size of capacitor for power factor improvement.
Instructions
Place a ruler to join the value of the initial power factor (column 1) to that of the
improved power factor required (column 3).
Read the multiplying factor where the ruler crosses column 2. For example, a
100 kW load is to be improved from 0.65 to 0.85 power factor.
Using the chart, the multiplying factor is 0.55.
\ capacitor (kvar) = 100 kW ¥ 0.55 = 55 kvar
Maximum demand tariff
The first step is to obtain past md records over a period of several years if possible.
These normally indicate either md kVA, or md kVA and kW. In large systems
recorders as well as instruments and meters are usually installed close to the point
of metering, thus simplifying the calculations. If the meter records indicate both kVA
and kW it is easy to obtain the md power factor from the relationship between kVA
and kW outlined earlier. If, however, the md records only indicate kVA it is then
necessary to estimate a power factor.
646
Handbook of Electrical Installation Practice
Prior to this, however, the md records should be studied to see if there is any pattern
to the demands, or if there is any marked variation in demand from month to month.
If such a pattern, or variation, is found the reason for it should be established.
If only the kVA demand is known the power factor has to be obtained from site
measurements. The kWh and kVAh meters are read at the beginning and end of a
known time period. The difference between the readings at the start and end of the
period enables the relevant kW, kVA, and kvar components of the load during the
test period to be calculated.
Ideally these tests should be performed at the same time as the md occurs, although in practice this very rarely happens. It is necessary, therefore, to determine
what plant is in use at periods of md, which was not in use during the test period,
and make allowance for this in the calculations.
Example
A study of a consumer’s electricity bill indicated an average md of 288 kVA. A test
carried out at the plant provided the following load figures: 240 kVA, 168 kW, 0.7
power factor, 171 kvar.
It was noted, however, that at the time of the test there was 20 kW of resistive
load not in circuit, together with some 31 kW of fluorescent lighting. Both items
could be in use at times of md. The md power factor can be calculated as shown in
Table 23.4.
Utilising the tables already referred to, it will be seen that to improve the md
power factor of 0.76 to an economic level of 0.97 requires 132 kvar of capacitor correcting equipment.
Average power factor tariff
The following information is required to enable a capacitor size to be arrived at:
md records; kWh consumed during the month; kvarh consumed during the month;
and working hours of the plant during the month.
The example below shows how this information is used to calculate a capacitor
size.
Example
A consumer is charged on a tariff which imposes a penalty charge when the average
lagging power factor falls below 0.9. From a study of the electricity accounts and a
Table 23.4 Calculations of md from known operating conditions.
Power Factor Correction and Tariffs
647
knowledge of the plant, the following information was obtained: kWh consumed
during the month 48 000; kvarh used during the month 56 000; average power factor
(calculated from the above) 0.65; working hours 160 per month.
To improve the average lagging power factor from a level of 0.65 to an economic
level of 0.90 some 33 300 kvarh must be removed from circuit by means of capacitors. Therefore:
capacitor size required = 33300 160 = 206 kvar
In practice this capacitor size would probably be increased by 5 or 10% to ensure
that the average power factor was kept above 0.90. The capacitor size arrived at in
the above example is the minimum possible size. It does not necessarily follow that
the installation of this capacitor would, in fact, give the required value of average
power factor, as a number of other factors have to be considered. If load variations
occur so that the capacitor gives a leading power at times, then the full kvar rating
of the capacitor is not available for the reduction of kvarh during these periods. It
will prevent, during such periods, the recording of any kvarh units, so that the difference between the reactive component of the uncorrected load and the capacitor
kvar is lost. This is based on the assumption that the kvarh meters are fitted with
devices to prevent ‘unwinding’ under leading power factor conditions. It therefore
follows that the actual capacity required must be increased over and above the
minimum value to allow for this.
During periods when the factory is not in production, kWh and kvarh, may still
be recorded due to small items of plant that run continuously, or to transformer
magnetising currents (this fact is discussed later). It may, therefore, be necessary to
provide for a portion of the total capacity to be left in circuit during light load
periods. It is reasonable to assume that the supply authority will object to the whole
capacity being in circuit 24 hours a day.
DETERMINATION OF LOAD CONDITIONS
The first step in designing any practical power factor correction scheme must be to
obtain accurate details of the load conditions with values of kW, kVA and power
factor at light, average and full load, together with type and details of the loads.
This may be achieved in one of the following ways: measurement of kW and kvar;
measurement of voltage, current and kW; measurement of kVA and kvar; or use of
a power factor indicating instrument, voltmeter and ammeter.
Use of tariff metering
In many instances it is possible to use the supply authority’s meter to arrive at a
plant loading condition. On the disc of the meter will be found a small mark, usually
a red or black band, which can be watched. Count the number of revolutions of the
disc for about one minute, note the number of revolutions made and the time in
seconds to make the revolutions, then:
648
Handbook of Electrical Installation Practice
X = 3600 N Rt
where X
N
t
R
= instantaneous reading in kWh (kvarh)
= number of revolutions of the disc in t seconds
= time in seconds for N revolutions
= meter constant in revolutions per kWh (kvarh).
The meter constant is stamped on the rating plate of the meter and is in revolutions
per kWh or kvarh.
Where the meter constant is shown as units per revolution U, then the formula
becomes:
X = 3600 NU 1000 t
The meter constant in this case is in either Wh or var per revolution.
It should be appreciated that the readings obtained by this method are instantaneous so that they should be taken when load conditions are normal.
Most tariff meters are now solid state. With these meters the kWh, kvarh and
kVAh readings are recorded at time T1 and again at time T2.The difference between
T1 and T2 is noted as M minutes. (Ideally M should have a value between 20 and
40 minutes.) The value of kW, kVA or kvar is then calculated as:
(Reading T2 - Reading T1) ¥ 60
M
REDUCED CO2 EMISSIONS
One important, and often overlooked, point is that the installation of power factor
correction capacitors will reduce current and hence kW losses throughout the whole
of the transmission and distribution system. If losses are reduced, the load on power
stations is reduced leading to a reduction in CO2 emissions. The BEAMA Capacitor Manufacturers’ Association has calculated that every kvar of low voltage
capacitors installed results in a reduction of 160 kg of CO2 generated per annum.
METHODS OF CORRECTION
Each power factor correction scheme requires individual consideration and, as the
successful operation of a scheme depends largely on the correct positioning of the
capacitors in the network, the importance of studying all relevant factors is emphasised. The relevant factors are: tariff in force; metering point; details of light, average
and full load kVA, kW and power factor; position of motors, welding equipment,
transformers or other large plant causing bad power factor; and supply system problems such as harmonics.
Capacitors themselves do not generate harmonics, but they can either reduce or
increase them, depending on particular circumstances. The major sources of harmonics are such things as thyristors, rectifiers and arc furnaces.
Power Factor Correction and Tariffs
649
The siting of the capacitors does, to some extent, depend on whether each piece
of equipment, e.g. a motor or a transformer, is being individually corrected, or the
plant as a whole, or part, is being corrected as a block (generally known as bulk or
group correction). In the first case the capacitor and motor, or capacitor and transformer, are as close together as possible; in the second case the capacitor is located
at some convenient point in the system, such as a substation.
On small installations individual correction can be applied to motors which are
constantly in operation or, in the case of kVA md tariffs, on certain motors known
to be in operation at the time of md. This method reduces the current loading on
the distribution system with consequent improvement in voltage regulation and,
generally speaking, is more economic. No additional switchgear is required as the
capacitor is connected directly to the piece of equipment it is correcting and can
therefore be switched with that piece of plant.
Where a capacitor is connected to motor it is connected directly across the motor
terminals and is switched with the motor starter, resulting in complete automatic
control. The balance of the correction required can then be connected to the main
busbars of the supply system and controlled by a fuse-switch. It should be noted,
however, that some supply authorities stipulate the maximum amount of kvar which
may be switched in this manner.
Automatic switching of capacitors is recognised as an ideal method of obtaining
the full electrical and financial benefits from a capacitor installation, the resulting
economics and convenience far outweighing the initial cost. Optimum power factor
is achieved under all conditions and there is no possibility of the equipment being
inadvertently left out of commission. A bank of capacitors with the required total
capacitor kvar controlled in equal stages by a multistep relay and air bread contactors connected to the main busbars is used in many applications.
Large industrial sites involving different kinds of manufacturing processes often
require a combination of bulk and individual correction to provide the most economic means of power factor correction.
In providing for power factor correction it should be remembered that distribution boards and circuits can carry a greater useful load if the capacitors are installed
as near as possible to the source of low power factor. For this reason either bulk or
individual correction, rather than correction at the intake point, can almost invariably be justified.
Individual correction of motors
The practice of connecting a capacitor across the starter of an induction motor,
and switching the motor and capacitor as one unit, is now universally established
and is to be recommended where there are not objections on technical and
economic grounds. One size of capacitor gives an almost constant value of power
factor over the normal load range since variations in motor kvar are comparatively
small.
Care should be taken in deciding the kvar rating of the capacitor in relation to
the magnetising kVA of the machine. If the rating is too high damage may result to
both motor and capacitor, because the motor, while still revolving after disconnection from the supply, may act as a generator by self-excitation and produce a voltage
650
Handbook of Electrical Installation Practice
higher than the supply voltage. If the motor is switched on again before the speed
has fallen to about 80% of the normal running speed, the high voltage will again be
superimposed on the supply circuit and there may be a risk of damage to other types
of equipment. As a general rule the correct size of capacitor for individual correction of a motor should have a kvar rating not exceeding 90% of the no-load magnetising kVA of the machine.
Connecting a capacitor direct to a motor results in a lower load current under all
load conditions and, therefore, the overload settings on the starter must be reduced
in order to obtain the same degree of protection.
Correction of individual motors is to be recommended where they are used
for group drives, or where they are used continuously during maximum load
conditions, but it should not be applied where the motors are used for haulage,
cranes or colliery winders, or where ‘inching’ or ‘plugging’ and direct reversal takes
place. Individual correction of tandem or two-speed motors should be avoided.
If correction of a two-speed machine is necessary, the capacitor should never be
connected directly to the low speed component but a contactor arrangement
installed using one capacitor for both windings. Care should also be taken when
offering capacitors for direct connection to motors whose braking system is
intended to be operated by loss of voltage, as the voltage remaining across the
capacitor when the main supply is removed, may be such as to prevent operation
of the braking system.
Where capacitors are connected direct to motors it is not usual to provide
the capacitor with any protection or isolating gear other than that afforded by
the control gear of the machine. Separate protection of the capacitor is usually
only provided when the drive is of such importance that it is undesirable for a failure
of the capacitor to put the motor out of service. For the individual correction of
h.v. motors, hbc fuses should be placed in the circuit between the motor and the
capacitor.
Where star-delta starting is used, a standard three-terminal delta-connected
capacitor should be employed, which gives maximum power factor correction at the
start when the power factor of the motor is low. The capacitor is connected as shown
in Fig. 23.6.
Typical capacitor size for individual connection of standard motors is given in
Table 23.5.
Individual correction of transformers
In any electrical distribution system the one item of plant in circuit continuously is
the transformer. It is often convenient, therefore, to connect a capacitor directly
across the transformer terminals. The benefit of this to a consumer charged on an
average power factor tariff is that the size of capacitor required to correct all the
other plant can be reduced considerably.Where a tariff penalises lagging kVA, transformer correction is a necessity. If the site has numerous transformers, and a high
diversity of l.v. load, improving the power factor of the transformers often dispenses
with the need for a central automatically controlled bank of capacitors.
The size of capacitor to be connected to the transformer depends on its no-load
kVA. As a general rule up to 10% of the transformer rating, in kVA, is acceptable
Power Factor Correction and Tariffs
Fig. 23.6 Use of a three-terminal capacitor with a motor fitted with a star-delta starter.
Table 23.5 Standard capacitor kvar ratings for direct connection to 415 V three-phase
50 Hz induction motors.
651
652
Handbook of Electrical Installation Practice
for the capacitor rating, e.g. the maximum size of capacitor for use with a 1000 kVA
transformer is 100 kvar.
Bulk power factor correction
It is sometimes impossible to connect capacitors in the desired location owing to
high temperature, restricted space, or the presence of explosive gases. Alternatively,
it may not be economic to correct individually each piece of electrical equipment because they are small items in terms of electrical load. For these reasons, or
when an installation operates with a high diversity factor, bulk correction may be
employed.
Capacitors used for bulk power factor correction may be controlled manually or
automatically. The manual type of scheme utilised fuse-switches, circuit-breakers or
other switching devices to control the capacitors.
Manually controlled capacitors are normally employed for factory loads which
are too small to warrant splitting the total capacitance required, or where high diversity of motor load makes individual correction uneconomic. Manual control can only
be justified technically for continuous process work where minimum switching is
required and where there is sufficient reactive kVA available in the circuit continuously to warrant the capacitor being connected all the time.
In the UK manual control of capacitors is limited to capacitor less than 40 kvar.
Automatic power factor correction
In larger installations, automatic power factor correction is being increasingly recognised as the ideal method of obtaining the full electrical and financial benefits from
a capacitor installation; the resulting economies and convenience far overweigh the
initial cost. Optimum power factor is achieved under all conditions and there is no
possibility of the equipment being inadvertently left out of commission.
The equipment normally consists of a capacitor bank subdivided into a number
of equal steps, each step being controlled by a contactor. The contactors, in turn, are
controlled by a relay responding to reactive kVA, of which there are several reliable makes available. The relay consists of a voltage coil connected across two
phases of the load supply system, and the current coil, normally rated at 5 A, connected, through a current transformer, to the remaining phase.
The number of stages installed is usually a compromise between the technical
requirements and cost. The aim of the automatic system is to have each contactor
switching its maximum rated capacitance and, at the same time, have the capacitor
bank divided into the most economic sub-sections, so that all meaningful variations
in load can be corrected.
LOCATION OF CAPACITORS
Mention has, so far, only been made of the point of connection of the capacitor to
the system to achieve the required, corrected power factor. In addition, care must
Power Factor Correction and Tariffs
653
Table 23.6 Limits of ambient temperature for
capacitor installations (taken from IEC 871-1,
Shunt capacitors for a.c. power systems having a
rated voltage above 1000 V and IEC 831-1, Shunt
capacitors of the self healing type for a.c. systems
having a rated voltage up to and including 1000 V).
be taken as to the physical location of the capacitor to avoid problems that could
lead to malfunction of the equipment.
As the maximum working temperature of capacitors is lower than that of other
electrical equipment, any conditions which give rise to unacceptable overloads must
be avoided. This, therefore, stipulates ambient temperature, maximum voltage and
overload current.
Care should be taken in choosing a site for the capacitor to minimise the ambient
temperature. If the site is outdoors, the direct rays of the sun should be avoided,
especially in tropical climates. Rooms housing capacitor assemblies must be adequately ventilated.
If there are harmonic producers on site, such as thyristor-controlled machines,
then the capacitors need to be located well away from the source of such harmonics, or designed to cope with any overloads produced in the capacitor by harmonic
currents or voltages.
Because the ambient temperature is an important consideration in the life of any
capacitor installation it is important that it is correctly specified by the purchaser
to the supplier. Three temperature categories are available, as will be seen from
Table 23.6.
Capacitors can be supplied for either indoor or outdoor use. It should be appreciated, however, that while an outdoor capacitor can be installed indoors, the reverse
is not true.
CAPACITORS AND HARMONICS
Harmonic distortion in electrical power systems is becoming more and more
prevalent with the ever increasing use of devices having non-linear operating
654
Handbook of Electrical Installation Practice
characteristics. Such devices include power diodes, thyristors and other semiconductor devices found in UPS systems, variable speed AC and DC drives and
switched mode power supplies.
It is usual to regard the harmonic producer as a generator of harmonic current.
The harmonic current flowing into a capacitor connected in parallel with the system
will depend on the relative impedances of both the system and the capacitor. The
system is inductive and so its impedance, varying directly with frequency, will
increase as the frequency increases. Conversely, the impedance of the capacitor
varies inversely with frequency and so will decrease with increased frequency. The
effect of this is that a greater proportion of the harmonic current will be absorbed
by the capacitor. In the worst case a point may be reached when the impedance of
the system equals the impedance of the capacitor. If this happens at or near to a
generated harmonic current, a resonant condition is created resulting in excessively
magnified currents flowing in both the capacitor and the system. The effect of these
harmonic currents flowing into the capacitor is to increase the voltage across the
capacitor dielectric and increase the capacitor losses. This leads to thermal instability and premature failure of the capacitor.
The solution is to connect a reactor in series with each capacitor switching section.
This reactor is chosen such that the capacitor/reactor combination is capacitive at
fundamental frequency but is inductive at or near to the resonant frequency. This is
achieved by selecting a tuning frequency below the lowest order of harmonic being
produced. The selection of tuning frequency is of paramount importance. The tuning
range chosen for most applications is in the frequency range 175 Hz to 230 Hz. The
actual value chosen will depend on the specific needs of each installation and the
amounts of harmonic current flowing. The nearer the tuning frequency is to 175 Hz
the larger the reactor and the smaller the harmonic current flow into the capacitor.
The nearer the frequency is to 230 Hz the smaller the reactor but the greater the
current flow into the capacitor.
The addition of the series reactor increases the fundamental voltage across the
capacitor. This, together with the harmonic current flow into the capacitor, needs to
be taken into account when designing a suitable capacitor for this duty.This arrangement of a reactor in series with a capacitor to reduce or ‘block’ harmonic current
flow into the capacitor is referred to as a ‘detuned’ capacitor bank.
INSTALLATION OF CAPACITORS
Installation and maintenance of capacitors should be carried out generally as
specified in BS 1650: 1971, IEC 813 and IEC 871.
The cable supplying either an automatic capacitor bank or a permanently connected capacitor should be fitted with some form of protection such as hbc fuses
for capacitors up to 660 V, and thermal overloads and earth-fault protection for
capacitors up to 11 kV and a means of isolating both capacitor and supply cable.
In selecting suitable switchgear or fusegear for capacitor duty it must be appreciated that the duty imposed on such equipment is more onerous then when used
with other equipment of equivalent kVA loadings. The reasons for this can be summarised as:
Power Factor Correction and Tariffs
655
(1) At the instant of switching a large transient current flows.
(2) High overvoltage transients can occur when capacitors are disconnected by
switching devices which allow restriking of the arc.
(3) The switchgear has to carry continuously the full rated current of the capacitor
whenever it is in circuit, i.e. there is no allowance for diversity.
(4) At light loads, when the voltage may be higher than normal, the capacitor
current is increased.
(5) If harmonics are present in the supply voltage the capacitor current is
increased.
In view of these factors the following limitations are imposed on the capacitor by
the manufacturer:
(1) The capacitor must be suitable for operation under abnormal conditions with
overvoltage of 1.1 times rated voltage.
(2) The capacitor must be suitable for continuous operation with a current of 1.3
times normal current.
In addition to these factors the capacitor manufacturer is permitted a manufacturing tolerance on output of -0 + 10% and in some cases +15%.
In view of these conditions it is naormal practice to derate switchgear and fuses
used with capacitors. Tables 23.7 to 23.9 give recommended hbc fuse and switch
sizes, together with cable sizes for low voltage capacitor applications. For systems
not covered by the tables the advice of the capacitor manufacturer should be sought.
Table 23.7 Recommended sizes of fuses and cables for use with capacitors; PVC insulated
cables to BS 6004/6346 having copper conductors (ambient temperature 30°C, conductor
operating temperature 70°C).
656
Handbook of Electrical Installation Practice
Table 23.8 Recommended sizes of fuses and cables for use with capacitors; cables with
copper conductors having thermosetting insulation to BS 5467 (ambient temperature 30°C,
conductor operating temperature 90°C).
Table 23.9 Recommended fuse-switch ratings for use with capacitors at various voltages.
This is especially important in the case of capacitors used above 660 V where large
derating factors are required. At voltages of 3.3 kV and 11 kV it is not unusual to
find fuses rated at three or four times capacitor current. With such large fuses it
becomes important to ensure that the energy required for correct operation of the
fuse is considerably less than the energy required to cause the capacitor tank to
657
Power Factor Correction and Tariffs
Table 23.10 Routine test voltages between capacitor
terminals and container.
Rated insulation level
(kV r.m.s.)
0.6
1.2
2.4
3.6
7.2
12.0
Test voltage
(kV r.m.s.)
3
6
8
10
20
28
burst. It is also important to ensure that there is adequate discrimination between
fuses used for capacitor protection and fuses further back in the system.
In addition to precautions when connecting the capacitor bank, it is also necessary, in the case of automatic equipment, to supply a current and voltage signal to
the reactive relay.
In the past, reactive sensing relays were supplied as separate items and it was
therefore necessary to provide both voltage and current signals. Modern practice,
however, is to mount the relay within the automatic capacitor bank, thus only a
current signal has to be provided. This is normally obtained by means of a current
transformer having a 5 A secondary current. It is important, however, to ensure that
the CT monitors the total load, including the capacitors, if the equipment is to work
correctly. It is also important to note that there has to be a phase displacement
between voltage and current signals to the relay. This phase displacement is dependent on the type of relay used.
After completing a capacitor installation the insulation resistance should be
tested. This is done by shorting together all the capacitor terminals and applying a
voltage between terminals and container. The value of this voltage, which must
be maintained for 10 s, is given in Table 23.10 which is taken from IEC 831 and
IEC 871.
It is important to note that such a test cannot be made between capacitor terminals as this will only result in the capacitor being charged and will not give an indication of insulation resistance.
CAPACITOR MAINTENANCE
Capacitors, being static apparatus, do not need the same attention as rotating
machinery, but nevertheless require regular maintenance. Normally a power factor
correction capacitor should be inspected at least every twelve months and preferably every six months. The time interval between inspections is, however, governed
mainly by the conditions on site. Where capacitors are installed in a humid atmosphere, or are subjected to chemical fumes or exposed to dirt and dust, more frequent attention should be given.
658
Handbook of Electrical Installation Practice
Before any examination always ensure that the capacitor has been disconnected
from the supply, and then wait for at least one minute (capacitors up to 660 V) or
five minutes (capacitors operating at voltages higher than 660 V) and then ensure
discharge is complete by measuring the voltage between terminals. Finally, short all
terminals together before testing. Shorting the terminals to earth is not effective for
adequate discharge.
The following points should be observed when carrying out any capacitor
maintanance.
Physical examination
(1) Examine externally that there is no damage or leakage of impregnant.
(2) Check that all cables are securely fixed and that all earth bonds are tight.
(3) Measure, if possible, the running temperature of the capacitor.
Testing
(1) Examine all insulators for signs of tracking, clean terminals and check for
tightness.
(2) Ensure that discharge resistors, where fitted, are in order.
(3) Check all connections for tightness.
(4) Measure insulation resistance of the terminals to case.
(5) If a capacitance bridge is available measure the capacitance prior to energising. If such a device is not available the capacitor should be energised and
the line current measured by means of a ‘clip-on’ ammeter. The current
measured should be compared with the current obtained from the following
equation:
I=
kvar
3V
where V is line-to-line voltage.
In considering the question of maintenance it is important to know that most
capacitors lose output during the course of their life. Some capacitors fail completely
after a number of years of operation. The failure mode of most capacitors is
a gradual loss of output without any noticeable signs of defect. Some capacitors, however, especially of the bulk oil-filled variety, can fail with disastrous
consequences.
Many capacitors manufactured between the early 1950s and the late 1970s are
filled with a liquid whose chemical name is polychlorinated biphenyl. It has a variety
of trade names, such as, Aroclor, Biclor, Pyraclor, Askarel etc. The use and disposal
of this fluid is covered by stringent regulations, including the ‘Disposal of Poisonous
Wastes Act’. Legislation was introduced under section 100 of the Control of
Pollution Act 1974, to implement the sixth amendment (85/467 EEC) to directive
76/769 EEC, such that from 30 June 1986 it was illegal to manufacture, buy, sell or
install pcb capacitors. Existing pcb filled capacitors could continue to remain in use
only while they remained in a serviceable condition without leakage.
Power Factor Correction and Tariffs
659
New Regulations – The Environmental Protection (Disposal of Polychlorinated
Biphenyls and other Dangerous Substances) Regulations 2000 – came into force on
4 May 2000. These regulations required the following action:
(1) Registration by 31 July 2000 if holding any PCB impregnated equipment
(2) Disposal of any PCB contaminated equipment above 500 ppm by 31 December
2000
(3) Disposal of any PCB contaminated equipment 500 ppm to 50 ppm at the end of
its useful life
(4) Reregistration each year by 31 July for PCB holdings until all holdings have
been disposed of
(5) Disposal of all PCBs by 1 January 2008.
The Environment Agency was to publish its enforcement policy but at the time of
writing this has not happened. The problem with capacitors is that most users are
unaware that they have equipment containing PCB and an awareness campaign is
required if all PCB equipment is to be disposed of by 2008.
It is important both from an economic point of view and in order to comply
with the Health and Safety at Work etc. Act, that capacitor installations are checked
periodically.
APPENDIX I
Main Authoritative Documents
Supply industry standards
(1) EA Technical Standard 41-24 Guidelines for the Design, Installation, Testing and
Maintenance of Main Earthing Systems in Substations.
(2) ER S34 A Guide for Assessing the Rise of Earth Potential at Substation Sites.
British Standards
(1) BS 7354: 1990 Design of High Voltage Open Terminal Substations. There is a
special section giving guidance on the design of EHV substation earthing.
(2) BS 7430: 1998 (formerly CP. 1013: 1965) Code of Practice for Earthing.
European Standards
(1) prHN 50179 Power Installations Exceeding 1 kV a.c., Common Rules. This is a
harmonisation document and Chapter 9 deals with Earthing.
(2) CCITT/ITU (International Telegraph and Telephone Consultative Committee).
Directives concerning the protection of telecommunication lines against
harmful effects from electric power and electrified railway lines.
North American Standards
(1) IEEE Standard 81, 1991 Testing of Soil, Soil Resistivity and Electrode Resistance.
(2) IEEE Standard 80, 1986 Guide for Safety in AC Substation Grounding.
(3) IEEE/ANSI Standard 655, 1987 Guide for Generating Station Grounding.
International Standards
(1) IEC 479 The Effects of current and human beings and livestock. This standard
is internationally recognised and forms the basis of calculation for estimating
safe touch, step and transfer potentials.
(2) IEC 61936-1 Power Installations exceeding 11 kV a.c. and 1.5 kV d.c. System
engineering and erection of electrical power installation, particularly concerning safety aspects. Draft being developed.
Relevant legislative documents
(1) HSE booklet Memorandum of guidance on the Electricity at Work Regulations
1989.
(2) The Construction (Design and Management) Regulations 1994 (known as the
CDM Regulations).
660
APPENDIX II
IP Codes of Ingress Protection
(BS EN 60947–1: 1998)
These extracts from BS EN 60947-1: 1998 are reproduced with the permission of
BSI under licence number 2001SK/0405. British Standards can be obtained from
BSI Customer Services, 389 Chiswick High Road, London W4 4AL. Tel +44 (0) 20
8996 9001.
661
662
Handbook of Electrical Installation Practice
IP Codes of Ingress Protection
663
664
Handbook of Electrical Installation Practice
APPENDIX III
British Standards
Reference lists of applicable standards are given in the following chapters:
Chapter
9
18
19
20
Lighting protection
Lighting
Mains Cables
Selection of Wiring Systems
Table
9.6
18.4
19.1
20.1
Reference is made in most chapters to BS 7671, Requirements for Electrical Installations (the IEE Wiring Regulations). A list of applicable British and European
Standards is given in Appendix 1 of BS 7671.
There are references to the following standards throughout this book.
BRITISH STANDARDS
Standard
BS 88
Subject
Cartridge fuses
BS 142
BS 148
Electrical protection relays
Transformer and switchgear
mineral insulating oils
Tungsten filament lamps
Power transformers
Galvanised coatings
Contactors
Cables
Earthing and bonding clamps
Cartridge fuses
Fuse links
13A accessories
Capacitors
Thermal classification of electrical
insulation
Semi-enclosed fuses
Instantaneous water heaters
BS 161
BS 171
BS 729
BS 775
BS 801
BS 951
BS 1361
BS 1362
BS 1363
BS 1650
BS 2757
BS 3036
BS 3456
665
Page no. or chapter
428–431, 434, 437, 438, 441,
442, 447, 448, 530, 555, 561,
562, 573, 574, 592
634
335, 356, 364, 389
478
335, 346
215, 217
460
510
106
444, 446, 447, 555, 592
444, 446, 447
446
654
416
446, 555, 557, 573, 575, 592
251
666
Standard
BS 3535
BS 3676
BS 4066
BS 4343
BS 4363
BS 4444
BS 4533
BS 4553
BS 4568
BS 4678
BS 4941
BS 4999
BS 5000
BS 5209
BS 5266
BS 5345
BS 5372
BS 5424
BS 5467
BS 5486
BS 5489
BS 5499
BS 5493
BS 5514
BS 5593
BS 5730
BS 5839
BS 5970
BS 6004
BS 6007
BS 6121
BS 6207
BS 6425
BS 6346
BS 6423
BS 6467
BS 6480
BS 6500
BS 6651
Handbook of Electrical Installation Practice
Subject
Shaver sockets
Switches
Test on electric cables under fire
conditions
Socket-outlets
Distribution units and electricity
supplies for construction sites
Earth monitoring
Luminaires
Split concentric cables
Steel conduit
Steel trunking
Motor starters
Rotating electrical machines
Generator rating
Checking SF6 gas
Emergency lighting
Electrical equipment in explosive
atmospheres
Cables
Contactors
Cables
Switchgear
Road lighting
Fire safety signs
Corrosion
Generators
Cables
Mineral insulating oils in electrical
equipment
Fire detection and alarm systems
in buildings
Steel
Cables
Flexible cables and cords
Mechanical cable glands
Mineral-insulated cables
Combustion tests on cables
Cables
Maintenance of switchgear up
to 1 kV
Electrical apparatus in combustible
dusts
Paper-insulated cables
Flexible cables and cords
Lightning protection
Page no. or chapter
251
251
521
104, 258, 263
99, 258
106
488, 516
518
546
546
473
127, 413, 414, 416
123, 127, 134
389
488, 500, 530
300, 571
101
460
508, 516, 517, 518, 531, 544,
569, 656
447
491
501
180
125, 126
511
355, 389
530
217
106, 531, 544, 546, 549, 557
263
525
580
521
113, 516, 531, 544, 550, 557
297, 385
571
388, 506, 510
263
Chapter 9
667
British Standards
Standard
BS 6622
BS 6626
BS 6656
BS 6724
BS 6708
BS 6867
BS 7211
BS 7361
BS 7375
BS 7430
BS 7535
BS 7622
BS 7626
BS 7629
BS 7735
BS 7870
BS PD 6519
Subject
Cables
Maintenance of switchgear from
1 kV up to 36 kV
Inadvertent ignition of flammable
atmospheres by radio-frequency
radiation
Cables
Cables
Maintenance of switchgear above
36 kV
Cables
Cathodic protection
Distribution of electricity on
construction and building sites
Earthing
Electrical equipment suitable for
dust atmospheres
Measurement of smoke density
from cables
Current transformers
Fire resistant electric cables
Oil-immersed transformers
Cables
Effects of current through a
human body
Page no. or chapter
508, 513
276, 297, 385
302
516, 518, 531, 544
106
276
531, 544
180, 189, 190, 194
99, 105, 114, 380
211, 212, 219
300, 571
521
601, 605, 610
567
335, 513
504, 514, 516, 518
282
EUROPEAN HARMONISED STANDARDS
BS EN 50014
BS EN 50281
BS EN 50266
BS EN 50267
BS EN 50268
BS EN 50091
BS EN 60073
BS EN 60034
BS EN 60044
BS EN 60076
BS EN 60079
BS EN 60099
BS EN 60269
Electrical equipment in potentially
explosive atmospheres
Electrical equipment in combustible
dusts
Test methods for cables under fire
conditions
Test methods for cables under fire
conditions
Test methods for cables under fire
conditions
EMC
Colour codes for indicator lamps
Alternators
Instrument transformers
Power transformers
Electrical equipment in potentially
explosive atmospheres
Surge diverters
Low voltage fuse
571
571
521
521
521
159
48
123
391
318
298, 571
245
447
668
Handbook of Electrical Installation Practice
Standard
BS EN 60287
BS EN 60309
BS EN 60439
BS EN 60529
BS EN 60488
BS EN 60742
BS EN 60898
BS EN 60947
Subject
Current-carrying capacity of cables
Socket-outlets
Switchgear
Degrees of ingress protection
Luminaires
Shaver sockets
Circuit-breakers
Low voltage switchgear and
controlgear
BS EN 61008
BS EN 61009
BS EN 61011
Residual current devices
Residual current devices
Electric fences
Page no. or chapter
542
104, 258, 263
258, 447, 456
319, 473
488
251
105, 555, 593, 594
441, 448, 450, 451, 455, 456,
460, 463, 469, 471–473,
586–588, 593, App. II
594
555
261
EUROPEAN STANDARDS
EN 1838
EN 61000
EN 60570
EN 55015
EN 60598
Emergency lighting
Limits voltage fluctuations
emissions from equipment
Luminaires
EMC emissions – lighting
Luminaires
488, 500
10, 11
488
488
489
INTERNATIONAL STANDARDS
IEC 34
IEC 56
IEC 76
IEC 158
IEC 287
IEC 292
IEC 726
IEC 831
IEC 871
IEC 947
IEC 1008
IEC 1459
IEC 60287
IEC 60364
IEC 62305
IEC TR 61000
Mounting of rotating machines
Switchgear ratings
Transformers
Contactors
Current ratings of cables
Motor starters
Transformers
Capacitors
Capacitors
Low voltage switchgear and
controlgear
Residual current devices
LV fuse co-ordination with
contactors and motor starters
Solar radiation
Electrical installations
Lightning protection
Limits harmonic equipment
emissions from equipment
413, 414
8
318, 346
460
526
473
318, 325
653, 654, 657
653, 654, 657
455, 460, 463
594
442
570
542, 554
218
11
Index
a.c. motors, 394
a.c. systems
composite, 159
interactive UPS, 148
standby supplies, 122
agricultural installations, 258
air termination of lighting networks, 208
askarel filled transformers, 322
auto-transformer starter, 468
bathrooms, 247
batteries for standby power supplies, 138
battery chargers, 141
bonding, 234
burns, 293
busbar assembly
protection, 615
selection, 581
switchgear, 388
cable management
cable basket, 90
cable tray, 90
conduit and trunking, 92, 544
decision making, 86
definitions, 86
hybrid systems, 91
overall considerations, 94
particular considerations, 95
segregation, 96
selection of equipment, 112
types, 87
underfloor systems, 88
cable tray, 90
cables
buried, 279
busbar systems, 581
conductors, 504, 536
CONSAC, 511
construction, 509, 536
construction sites, 105
continuity of sheath, 525
distribution transformers, 353
enclosures, 538
installation, 518, 578
insulation, 506, 536
jointing and terminating, 521
mineral insulated, 580
overcurrent protection, 554
overhead, 280
ratings, 525, 541
selection, 529
site distribution, 67
specifications, 502, 503
supports, 538
temperature limits, 540
testing and fault finding, 527
voltage drop, 575
waveconal, 514
caravan
installations, 261
site supplies, 263
carbonaceous backfill, 192
cartridge fuses, 427
cathodic protection
corrosion cell, 181
earthing, 188
electrochemical and galvanic series, 181
electrolytic cell, 182
equipment, 191
galvanic cell, 181
impressed current, 186, 189
installation, 188
isolation, 187
maintenance, 188
measurements, 187
mechanisms, 184
principles, 183
references, 195
sacrificial anode protection, 188
sacrificial cathodic protection, 186
systems, 186
test points, 191
theory of corrosion, 181
CENELEC
cables, 502
standards, 310
characteristics of fuses, 436
CIBSE code, 493
circuit-breakers, 592, 595
comparison, 372
gas-filling, 389
high voltage, 380
magnetic air circuit-breaker, 366
669
670
Index
oil, 364, 366
oil filling, 389
SF6 sulphur hexafluoride circuit-breaker, 368
specification, 373
standards, 592
switchgear, 360
types, 592
vacuum, 367
commissioning, see testing and commissioning
computer interface with UPS, 156
conduit and trunking, 92, 544
CONSAC cables, 511
Construction (Design & Management)
Regulations, 271
construction sites
armoured and non-armoured cables, 105
cable routing, 117
cable terminations, 117
calculating peak demands, 109
consultation, 107
equipment design, 99
incoming supply and distribution assembly, 100
incoming supply assembly, 99
lighting, 117, 119
mains distribution assembly, 102
maintenance, 121
selection of equipment, 112
supply systems, 110
system design, 107
test and inspection, 120
transformer assembly, 104
110 V distribution equipment, 106
contactor
standards, 460
vacuum, 367
control panels
maintenance, 129
substation, 48
d.c. systems
battery chargers, 141
meters and alarms, 143
motors, 401
systems for standby supplies, 137
diesel generating sets, 122–138
discrimination
fuses, 440
system, 599
distribution boards, substation, 63
Distribution Network Operators (DNO), 3,
67–70, 73, 74, 82, 83
distribution transformers
askarel filled, 322
cabling, 353
commissioning, 354
connections, 340
cooling, 343
dry-types, 62, 325, 351, 352, 356
fire resistance, 323, 337
impulse withstand, 345
installation, 352
loading guide, 335
losses, 330
maintenance, 354
oil-filled, 320, 350, 352, 354, 355
packaged substations, 347
parallel operation, 347
performance, 329
preferred values, 319
protection, 348
shipment, 350
tappings, 339
temperature rise, 332
tropical climates, 346
types, 318
ventilation, 345
earth electrodes, 174–177
earth faults, 284
earthing
rod resistance, 168
soil resistivity, 163
system, 14
earth loop impedance, 8, 577
earth terminating of lightning networks, 211
efficiency of motors, 417
Electricity Pool, 6
Electricity Safety, Quality and Continuity
Regulations, 2–4, 14
electric shock, 281, 283, 443
electrochemical series, 181
EMC, 159
emergency lighting, 499
emergency switching, 586, 589
enclosures
cables, 538
substation, 42
erection procedures
earthing, 63
meters and relays, 62
substations, 55
transformers, 61
European Union, 315
explosions, 296
fault clearance, substation, 41
fault level, 112
fireman’s switch, 590
fire resistance, distribution transformers, 323
fires, 295
flammable atmospheres, 298
floodlighting calculations, 489
Index
functional switching, 587
fuses see also HBC fuses
cartridge, 431
domestic, 21, 446
HBC, 431
semiconductor, 447
gas-filled circuit breakers, 389
generation
embedded, 19
graded protection, 603
Grid Code, 4
harmonics, supply, 10
harmonisation, voltage and frequency, 6
HBC fuses and fusegear
ambient temperatures, 443
aM type fuse links, 429, 443
applications, 437
cartridge fuses, 431
compact fuses to BS 88-6, 448
co-ordination, 441
discrimination, 440
domestic, 446
electricity authority fuses, 447
fuse-holder, 437
gG type fuse links, 428
gM type fuse links, 429, 442
overload characteristics, 436
protection against electric shock, 443
semiconductor, 447
switchgear, 448
thermal ratings, 451
Health and Safety, 33
Health and Safety at Work etc. Act, 267
high voltage
circuit breakers, 380
earthing, 15
substation switchgear, 50
highway power supplies, 264
hot air saunas, 255
lEC standards, 308
lEE standards, 312
incoming supply and distribution assembly,
100
incoming supply assembly, 99
inspection and testing, see testing and
commissioning
intake arrangements
high voltage, 25
low voltage, 24
interlocking, 290
International Electrotechnical Committee,
308
isolation
general, 585, 587
motor control, 471
short circuit co-ordination, 472
isolation and switching, 585
emergency switching, 586, 589
fireman’s switch, 590
functional switching, 587
switching off for mechanical maintenance,
586, 589
lamps see lighting
lighting, 475
ATEX Directive, 489
British Standards, 488
calculations (floodlighting), 490
control gear, 484
diffusion, 476
discharge lamps, 479
electromagnetic spectrum, 475
emergency lighting, 499
floodlighting, 489
fluorescent tubes, 482
high pressure sodium lamps, 480
induction principle, 482
ingress protection, 489
interior lighting, 491
low pressure sodium lamps, 479
luminaires, 485
measurement, 477
mercury vapour lamps, 480
metal halide lamps, 480
outdoor equipment, 489
reflection, 475
reflector lamps, 478
refraction, 476
run-up time, 480
safety, 488
sodium lamps, 479, 480
street lighting, 264, 489
tungsten halogen lamps, 478
lighting design
ClBSE code, 493
discomfort glare, 496
light output ratio, 494
luminous intensity and polar curves, 494
photometric data, 493
spacing to mounting-height ratio, 496
task illuminance, 491
utilisation factor and room index, 495
lightning protection
air terminations, 208
bonding, 234
bonds, 212
design, 208, 216
down conductors, 210
671
672
earthing, 234
earth termination networks, 211
electronic systems, 219
inspection and testing, 219
installation, 218
material specifications, 213
rolling sphere concept, 198
strike probability, 199
termination networks, 208, 234
transient overvoltages, 219, 223, 237, 239–
243
zones, 206
loads on diesel generators, 131–134
low voltage, substation switchgear, 50
luminaires, see lighting
mains distribution assembly, 102
maintenance
capacitors, 657
cathodic protection systems, 188
distribution transformers, 354
motors, 138, 423
safety, 274
measurement of light, 477
metering,
accuracy of metering, 32
bulk supplies, 28
development of meter services, 31
end customers, 29
larger customers, 29
small customers, 29
mineral insulated cables, 580
motor applications, 413
motor control gear
auto-transformer starters, 468
contactors, 454, 456, 461
direct-on-line starters, 466
electronic relays, 465
enclosures, 473
isolation, 471
magnetic relays, 465
motor control centres, 471
overload protection, 463
product standards for contactors, 460
short-circuit co-ordination, 472
soft starters, 469
star delta starters, 467
starter types, 466
stator-rotor starters, 468
thermal relays, 463
thermistor relays, 466
variable speed drives, 470
motor generator sets, 405
motors, see rotating machines
motor starters, 52, 62 466
Index
NETA, 6
new technology, 34
Office of the Gas and Electricity Markets
(Ofgem), 4
oil-filled transformers, 61, 320
overcurrent protection of cables, 554
overhead lines, 280
parallel operation
diesel generators, 130
distribution transformers, 347
permits to work, 276
power factor
calculation, 638
economic considerations, 637
improvement, 636
supply, 9
tariffs, 639
theory, 636
power supplies, 1
privatisation, 33
protection system, 16
reactive power, 34
record drawings, substations, 65
Regional Electricity Company, 1
relays inverse time, 601
residual current circuit-breaker, 594
resistivity of soil, 163
rotating machines
a.c. motors, 394
bearings, 424
brushgear, 425
cage motors, 395
commissioning, 422
coolers, 426
d.c. motors, 401
efficiency, 417
enclosures, 414
installation, 136, 418
insulation, 416
maintenance, 138, 423
motor applications, 413
motor generator sets, 405
mounting, 413
noise, 416
slip ring motors, 398
starting currents, 397
storage, 418
switched reluctance drives, 411
synchronous motors, 399
synchronous reluctance motors, 400
synchronous speeds, 395
thyristor drives, 411
Index
types, 394
variable speed drives, 407
ventilation and cooling, 414
voltages, 413
safety
buried cables, 279
burns, 293
design, 299
design and installation, 273
earth faults, 284
electric shock, 281, 283, 443
enforcement, 270
explosions, 296
fires, 295
flammable atmospheres, 298
interlocking, 290
legislation, 267
maintenance, 274
overhead lines, 280
permits to work, 276
policy statement, 271
rescue, 282
rules, 271
tools, 278
training and systems of work, 275
saunas, hot air, 255
segregation, 96
short-circuit levels, 8
showers, 251
site distribution testing and commissioning, 83
soil resistivity, 163
special installations
agricultural installations, 258
baths and showers, 249
caravan sites, 263
caravans, 261
construction sites, 257
highway power supplies, 264
hot-air saunas, 255
installations having high protective conductor
currents, 261
swimming pools, 252
standards
British Standards, 304
cables, 503
CENELEC, 310
IEC, 308
IEE, 312
luminaires, 488
standards and the law, 313
standby power supplies
acoustic noise, 157
alternating current systems, 146
batteries, 138
673
battery extensions, 158
battery rotary UPS, 151
charger techniques for regulated d.c. loads, 144
composite standby systems, 159
computer interfaces, 156
continuous mode on-line, 150
d.c. systems, 140
diesel generating sets, 122–138
diesel rotary UPS, 152
ease of use, 156
EMC, 159
expandibility, 157
line interactive UPS, 148
matching the UPS to the load, 152
off-line UPS, 147
safety, 157
selecting a UPS, 154
size and design, 154
value regulated lead-acid batteries, 145
versatility, 159
standby systems, 122–161
star-delta, 467
street lighting, 264, 489
strike, probability of lightning, 199
structure of the UK electricity industry, 2
substations
cabling, 45
consumers, 28
duplicate supply, 39
enclosures, 42
fault clearance, 41
fire fighting, 58
foundations, 56
fuses, 52
high voltage, 38
h.v. switchgear, 46, 58
indoor, 44
installation, 55
location of equipment, 57
low voltage, 40
outdoor, 42
outdoor/indoor, 43
procedural planning, 34, 58
programme (of installation), 56
ring main unit, 38
single-supply, 39
transformers, 46
superimposed signals, 11
supply arrangements
commercial, 23
domestic, 21
industrial, 24
supply systems
construction sites, 110
shock protection, 281
674
swimming pools, 252
switchgear
busbar assembly, 388
cabling, 388
circuit-breakers, 358, 364, 372, 592, 595
definitions, 358
earthing, 385, 389
erection, 386, 387
gas filling, 389
high voltage, 58, 380
interlocking and padlocking, 290, 384
low voltage, 50
magnetic air circuit-breaker, 366
maintenance, 385
medium voltage, 360
oil circuit-breakers, 364, 366
oil filling, 389
site distribution, 67
storage, 386
sulphur hexafluoride circuit-breaker, 368
switches, 371
testing and commissioning, 372, 390
types of device, 364
vacuum circuit-breaker, 367
vacuum interrupters, 389
switching off for mechanical maintenance, 586,
589
switching transients, 10
system
design, 107
earthing, 14
fault level, 112
impedance, 8
loading, 9
Index
reliability, 17, 18
urban, 17
teleswitching, 12
testing and commissioning
cable, 527
construction sites, 120
distribution transformers, 354
site distribution systems, 83
standby power supplies, 137
thermosetting insulation, 507
tools, safety, 278
training, 275
transformer
assembly, 104
power factor correction, 635
protection, 614
transient overvoltages, 219, 223, 237, 239–243
transients, 10
tropical climates
distribution transformers, 346
parallel operation, 347
unbalanced loads, 9
underfloor systems, 88
uninterrupted power supplies, 147
variable speed drives, 470
voltage drop in cables, 563
waveconal cables, 514
wiring systems, 529
zones of protection, lightning, 206