Nuclear Engineering and Design 185 (1998) 153 – 172
Experimental analysis of heat transfer within the AP600
containment under postulated accident conditions
Mark H. Anderson a, Luis E. Herranz b, Michael L. Corradini a,*
b
a
Department of Engineering Physics, Uni6ersity of Wisconsin, 1500 Engineering Dri6e, Madison, WI 53706, USA
Department of Nuclear Fission, Centre for Energy, En6ironment and Technology Research, CIEMAT, A6da. Complutense, 22,
28040 Madrid, Spain
Received 29 July 1997; received in revised form 8 April 1998; accepted 1 May 1998
Abstract
The new AP600 reactor designed by Westinghouse uses a passive safety system relying on heat removal by
condensation to keep the containment within the design limits of pressure and temperature. Even though some research
has been done so far in this regard, there are some uncertainties concerning the behavior of the system under
postulated accident conditions. In this paper, steam condensation onto the internal surfaces of the AP600 containment
walls has been investigated in two scaled vessels with similar aspect ratios to the actual AP600. The heat transfer
degradation in the presence of noncondensable gas has been analyzed for different noncondensable mixtures of air and
helium (hydrogen simulant). Molar fractions of noncondensables/steam ranged from (0.4– 4.0) and helium concentrations in the noncondensable mixture were 0 – 50% by volume. In addition, the effects of the bulk temperatures, the mass
fraction of noncondensable/steam, the cold wall surface temperature, the pressure, noncondensable composition, and
the inclination of the condensing surface were studied. It was found that the heat transfer coefficients ranged from
50 to 800 J s − 1 K − 1 m − 2 with the highest for high wall temperatures at high pressure and low noncondensable molar
fractions. The effect of a light gas (helium) in the noncondensable mixture were found to be negligible for
concentrations less than approximately 35 molar percent but could result in stratification at higher concentrations. The
complete study gives a large and relatively complete data base on condensation within a scaled AP600 containment
structure, providing an invaluable set of data against which to validate models. In addition, specific areas requiring
further investigation are summarized. © 1998 Published by Elsevier Science S.A. All rights reserved.
1. Introduction
Since the inception of the nuclear industry,
nuclear safety has been one of the major issues for
the nuclear fuel cycle. As a result, a large amount
of work has been conducted and significant
* Corresponding author. Tel.: + 1 608 2652001; fax: + 1
608 2626400; e-mail: corradini@engr.wisc.edu
achievements have been realized, particularly in
the area of understanding phenomena during accidents. This work has led to major improvements
in the next generation reactor designs which incorporate new safety features. The improvement
in these safety systems generally involves the use
of natural forces to provide containment cooling
and are referred to as passive containment cooling
systems (PCCS). One of the reactor concepts that
0029-5493/98/$ - see front matter © 1998 Published by Elsevier Science S.A. All rights reserved.
PII S0029-5493(98)00232-5
154
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
Fig. 1. Schematic of the AP600 PCCS configuration. The shaded section shows the portion of the containment modeled in the
experiments.
has been designed which implements PCCS and is
under study is the Westinghouse’s AP600 pressurized water reactor.
This design utilizes a unique system to maintain
the containment atmosphere pressure and temperature within design limits (Spencer et al., 1993).
Fig. 1 shows a schematic of the reactor containment. In the event of a postulated accident where
high pressure cooling water escapes into the con-
tainment, the pressure and temperature will increase as water flashes to steam. The steam will in
turn start to condense on the steel containment
vessel which is initially at ambient temperature.
This results in an increase in the surface temperature of the steel wall. The heating of the steel
containment wall causes air from outside, due to
buoyancy forces, to be drawn in through an air
baffle between the concrete containment and the
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
steel inner wall (not present in current reactors).
This process along with the release of cooling
water, by gravity from reservoirs situated above
the containment, hold the wall temperature well
below that of the internal bulk atmosphere. This
temperature difference along with a concentration
difference created by the condensation of steam in
the presence of noncondensable gases, sets up a
natural circulation flow pattern within containment. Steam condensation, enhanced by the turbulent natural convection, but inhibited by a
noncondensable gas layer formed adjacent to the
wall, should provide sufficient cooling to keep the
ambient conditions within containment under safe
structural limits.
This cooling system performance needs to be
tested by conducting experiments which measure
the heat transfer rate from the containment bulk
to the external atmosphere. Even though there
has been extensive experimental and theoretical
research in the area of condensation (Collier and
Thome, 1994), much less work specifically addressed the condensation process at large scales,
such as reactor containments. Uchida et al. (1965)
and Tagami (1965) provided some of the pioneering work in this area, which has recently been
corroborated by other investigators (Kataoka et
al., 1992). This work has led to the development
of correlations used in containment safety analysis
(Corradini, 1984; Kataoka et al., 1992) that estimate the heat transfer coefficient (HTC) based on
the ratio of Wnc/Wv. Recently, Green and Almenas (1996) carried out a peer review and analysis
of both small and large scale experiments including CVTR (Carolina Virginia tube reactor) and
the E-series of the HDR experiments, along with
others. They concluded that the above mentioned
correlations provide a too simplistic method of
estimating the HTC, missing variables such as
pressure, temperature, and bulk velocity which
are of primary importance in condensing scenarios. With the advent of new PCCS cooling designs
there has been a change in the potential condensing conditions within the containment. The results
of which, significantly increases the temperature
difference between the wall and the containment
compared to those in the current reactors that
have no external cooling. Also the absolute tem-
155
perature of the containment surfaces will be
lower, affecting properties relevant in the condensation process. These issues and other differences
in anticipated accident conditions, along with the
increased importance of the condensation process
of the PCCS, has prompted renewed interest in
performing experiments. These new experiments
should be aimed at confirming the PCCS capability to accomplish its goal and to fully characterize
the condensation scenario outlined by the revised
boundary conditions in the new systems.
Westinghouse (Kennedy et al., 1994) has performed some large scale experiments designed to
look at the entire cooling system to evaluate its
performance and provide test data for license
approval by the NRC. These large scale tests give
general information on the pressure, temperature,
and containment responses in the case of a postulated accident as a function of time, along with
some information on the heat transfer rates, but
lack some of the insight given by more closely
controlled facilities on the effects of both primary
and lower order variables. Some past experiments
have been designed to look specifically at these
effects at a smaller scale. Dehbi et al. (1991)
conducted some experimental work on a 3.5 m
long 0.038 m diameter tubular geometry with
different pressures, mass fractions of vapor/noncondensables, and light noncondensable gases (helium as a hydrogen simulant). This led to the
development of correlations that relied on these
variables. Despite the valuable information provided by this data the geometry of the facility is a
drawback due to the questionable non-uniform
conditions in the vessel. Huhtiniemi and Corradini (1993) considered the effects of orientation
and bulk velocity in a smaller rectangular facility.
They improved on the cooling design of Dehbi,
however, the small size required them to impose a
forced velocity flow parallel to the cold wall so
that one could achieve velocities similar to those
anticipated in an actual containment accident.
To bridge the gap between the large time varying simulation of an accident (Westinghouse) and
the smaller separate effects studies (Dehbi et al.,
1991; Huhtiniemi and Corradini, 1993), an experimental program which addresses conditions similar to those expected during an accident in the
156
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
Fig. 2. Key components in the test facility: test vessel, coolant supply system, and gas supply systems.
AP600, at an indepth level has been conducted
(Anderson, 1998). Specifically this experimental
program was aimed at achieving a thorough understanding of the role of both major and minor
variables on the heat transfer rate, along with
providing a valuable data base to validate heat
transfer models. Two experimental facilities have
been constructed with similar features to the actual reactor such as a proper aspect ratio, similar
surface finishes, and the ability to achieve prototypical accident conditions. Qualified experimental results have been gathered by demonstrating
test reproducibility and by using redundant and
accurate measurement techniques for the HTC.
Particular care has been taken to follow a representative test protocol that allows an experimental
test matrix of over 70 tests to span the expected
range of conditions.
2. Experiment description
2.1. Test facility
The test facility consists of three major components (Fig. 2): the test vessel, the coolant system,
and the gas supply system. Two different test
vessels have been used. One of them, called the
‘atmospheric test section’ was constructed to
study the effects of temperature differences between the bulk atmosphere and the wall during
steam– air and steam– air– helium condensation at
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
157
Fig. 3. Schematic of the pressure test vessel. Also shown are the probe hole locations, probes 2 – 8 were used for the mixture
temperature.
158
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
atmospheric pressures and with transparent walls
for visualization. The other, a ‘pressurized test
section’, was designed to withstand more prototypical pressures and temperatures anticipated in
the accident scenarios. The combined usage of
both vessels along with a proper test matrix allowed a thorough understanding of the role of the
major variables involved in the condensation process under realistic conditions and representative
test protocols.
The rectangular test vessels were both 1:12 scale
radial slices of the AP600 containment from the
operating deck to the top of the containment (Fig.
3), resulting in a test vessel with dimensions of 2.8
m tall, 1.7 m wide, and 0.32 m in depth (Anderson
et al., 1998). The atmospheric test vessel had two
O.91 m long condensing plates, one oriented vertically and one horizontally, in the top right hand
corner of the facility. The remainder of the test
section was made of transparent polycarbonate
(Lexan™) sheets to allow visualization of the
condensation process. The pressurized test vessel
was constructed with steel side walls so that a
design pressure of 4.0 bar absolute could be
achieved, characteristic of actual accident conditions. The condensing plate in the pressurized test
section was constructed in seven sections with
various angles which resulted in a 2:1 semi-elliptical structure similar to the upper dome of the
AP600 containment. In both test sections the
aluminum condensing plate was thermally insulated from the rest of the test section to minimize
any conduction from the side walls. There were
access holes cut into the side of each test section
and an injection flange placed on the access panel
so that the injection system could be inserted 0.15
m above the bottom of the test section. After
construction, the entire test vessel was insulated.
The condensing plates consisted of 2024t351
aluminum 0.30 m wide and 0.038 m thick. The
plates were prepared in a manner similar to the
proposed procedure of the walls of the AP600
containment (WCAP, 1992). This consisted in
sand blasting the plates and coating them with
about 0.1 mm thick coating of inorganic zinc
paint, which has a thermal conductivity of 0.0209
W cm − 1 K − 1. Each condensing plate was fitted
with several 0.3048 × 0.1524 m coolant plates,
similar to the construction used by Huhtiniemi
and Corradini (1993), so that the coolant flow
through each plate could be controlled and monitored separately by individual flow meters. A
schematic of a typical cooling plate is shown in
the blow up of Fig. 3. The aluminum condensing
plates were held at a constant temperature by 12
and 14 individual cooling plates, for the atmospheric and pressurized sections, respectively.
Coolant water, supplied by a Neslab HX-150
constant temperature water bath enters two
coolant manifolds. The coolant flow rate is controlled by a series of independent needle valves
(one for each plate) and measured with Dwyer
RMC141 flow meters. After passing through the
cooling plates, the coolant enters two exit manifolds and then returns to the coolant bath.
The steam was supplied by a Sussman model
ES-7L boiler and was injected into the test vessel
through a uniform steam injection configuration.
The 72 kW boiler which is able to produce 0.027
kg s − 1 of steam is equipped with a Mercoid Da
531 Bourdon tube pressure switch, which has a
dead band of 3 psi so that the boiler pressure
fluctuations are minimized resulting in a minimal
variation of the steam temperature. The steam
injection system produced a uniform distribution
of steam across the bottom of the vessel at low
velocities. It was constructed of 1 in. IPS manifold
pipe with 19 evenly spaced nozzles (minimum
opening of 4.8 mm) used to inject the steam into
the test vessel. A small hole was also drilled in the
bottom of the pipe to allow any condensed liquid
to flow out of the tube. Steam was supplied on
both ends of the pipe to create a more uniform
injection from each nozzle.
2.2. Measurement techniques
Two independent methods of determining the
HTC’s were used. The first was a local heat flux
measurement (HFM) using a linear array of thermocouples and the second was an area averaged
heat transfer coefficient that was determined from
a coolant energy balance (CEB).
The heat transfer coefficient on the surface of
the condensing plate can be determined by the
heat flux through the plate and the temperature
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
159
Fig. 4. Schematic of the HFM probe design.
difference between the gas bulk and the plate
surface.
hi =
k(dTi /dx)
Tb,i −Tw,i
(1)
The HFM’s were developed to measure both
the temperature gradient and the surface temperature of the plate. A schematic of one is shown in
Fig. 4. Each consists of a set of four E-type
thermocouples encased in a 4.8 mm o.d. stainless
steel tube. Four 1 mm precision holes were drilled
in the side of the stainless steel sheath with a
separation of 8 mm. Thermocouples were inserted
into the hole and a silicon sealant was injected
into the end of the tube to hold the thermocouples
in place. The thermocouples were individually
calibrated using a platinum thermometer to ensure a proper measurement of small heat fluxes.
To determine the heat flux the HFM’s were
placed in holes drilled through the cooling plates
and into the aluminum condensing plate. A twodimensional analysis with ANSYS (Kohnke,
1995) showed that materials with higher thermal
conductivities than air (such as silicon, for example) between the thermocouples and the aluminum would minimize the possible disruption of
the temperature gradient due to the probes presence. Therefore, the small gap was filled with a
high thermal conductive silicon grease. A linear
least squares equation defining the temperature
distribution of the plate was found from the temperature measurements and the positions of the
thermocouples. The slope of this line is the temperature gradient in the aluminum plate and the
y-intercept is the surface (wall) temperature. To
find the temperature at the surface of the plate a
linear temperature dependence is assumed:
Ti (x) =
dTi
x +Tw,i
dx
(2)
A similar equation governs the temperature distribution in the zinc coating. The existence of the
coating was included in the analysis (however any
contact resistance between the aluminum and the
zinc coating was neglected). With knowledge of
the gradient, surface temperature, and the bulk
mixture temperatures the heat transfer coefficient
could be calculated.
The CEB method relies on the equation:
hi =
rlCpV: i DTcoolant,i
Ai (Tb,i −Tw,i )
(3)
The variables in the above equations were obtained by passing temperature controlled water
through a flow meter and then through the
coolant channels in the coolant plates. The temperature of the water was measured with E-type
thermocouples at the inlet and subsequently at the
160
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
exit of the coolant plate. An energy balance of the
liquid will yield the energy removed from the
condensing plate and, thus, the heat flux associated with the area under the coolant plate could
be found. The surface plate temperature was
taken from the HFM measurements and the bulk
mixture temperatures were measured.
The test section was also equipped with several
temperature probes to measure axial variations in
the test section fluid temperature. Compression
fittings with a minimum opening of 12.7 mm were
used to allow easy installation of a variety of
measurement probes. The probe holes numbered
2 – 8 next to the condensing plates (Fig. 3) were
used as the mixture temperatures in the calculation of the HTC. These probes were located sufficiently outside of the thermal boundary layer but
as close to the condensing plates as possible,
considering the structural integrity of the side
walls. This was done to ensure that the measured
temperature was that of the bulk. The relative
humidity (RH) could also be measured at any of
the compression fitting positions using a Vaisala
series HMP131Y humidity and temperature
probe. It was found that the bulk was saturated
everywhere to within the accuracy of the probe
for all tests. This was also confirmed by gas
sample measurements taken near the center of the
test section approximately 0.76 m from each
coolant plate and analyzed on a mass
spectrometer.
2.3. Test protocol
The scope of the experimental program encompassed the range of possible conditions that could
occur in the AP600 containment after a hypothetTable 1
Ranges of main experimental variables
Variable
Range
P (bar)
Tb (°C)
Tw (°C)
XHe (%)
RH (%)
1.0 – 3.0
60.0– 120.0
25.0– 100.0
0.0–30.0
100.0
Table 2
Typical experimental time sequence
Time (min)
Action items
t=−210
t=−200
t=−190
t=−180
t= 0
t= 10
t= 30
Setting noncondensable conditions
Recording initial conditions
Operation of the coolant flow system
Operation of the steam flow system
Steady state conditions
Data acquisition
Completion of test
ical accident. The range of the key variables are
given in Table 1.
The test protocol was kept as similar as possible
to the sequence of events in a postulated accident.
Table 2 summaries the major steps of the test
procedure. Air – steam experiments required air at
atmospheric conditions in the test section prior to
steam injection. The steam– air– helium experiments conducted at 1 atm were carried out by
mixing helium with air in a specific ratio by
measuring the flow rate of both the air and helium with a Dwyer RMA122 and a Dwyer RMA8
flow meter, respectively. The mixing was done in a
tee which was connected to the steam injection
system. To obtain the appropriate mixture of
noncondensables the test vessel was flushed with
several volumes of the air– helium mixture. A gas
sample was taken at the midsection of the vessel
and analyzed on a mass spectrometer to ensure
the correct noncondensable mixture was attained.
A more prototypical introduction of helium was
used in the pressurized facility. This was done by
introducing steam into the facility which originally contained air. After a steady state at a given
pressure was achieved, helium was slowly introduced at a known flow rate along with the steam
until the proper fraction was attained and confirmed by mass spectrometer measurement.
The desired temperature and pressure of the
test section was set by allowing steam from the
boiler to enter the test section through the steam
injection system. The flow rate was adjusted manually until the appropriate conditions were
reached. To perform atmospheric tests a valve to
a suppression pool was opened, which allowed the
mixture of steam and noncondensables to escape
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
161
Fig. 5. Local heat transfer coefficient measurement reproducibility for both test vessels (P= 1 bar, Tw = 30°C, Tb = 80°C, saturated
conditions).
from the test section. This valve was kept open
until enough of the noncondensables had been
released so that they remained saturated at a
pressure of one atmosphere and the desired bulk
temperature (the suppression pool was necessary
so that during any slight bulk temperature fluctuations outside air would not enter the test section
and change the noncondensable concentration).
The coolant temperature and flow rate was also
adjusted while the test section was reaching a
steady state condition. This was done so that the
surface temperature of the entire condensing plate
was approximately constant and at the desired
temperature. A quasi-steady state is achieved
when the energy introduced by the steam is equal
to the energy removed by the coolant water. This
is determined when there are no significant
changes in the temperatures of the coolant flow,
condensing plate or the bulk test section.
Once the steady state was achieved the thermocouple data was collected at a rate of 0.1 Hz. One
hundred temperature measurements for each ther-
mocouple were recorded. The RH was measured
over the period of the data acquisition with the
humidity probe and also a gas sample was taken
and analyzed on a mass spectrometer to determine the fraction of vapor– air– helium within the
test section at the time of the test.
3. Experiment results
In each set of experiments there were 14 and 12
local HTC measurements conducted by both the
CEB and HFM method for the pressurized and
atmospheric test sections, respectively. The error
in the local measurements was found to be approximately 10% for both the CEB and HFM,
which was determined by the S.D. in the temperature measurements along with a propagation of
errors for the different methods (Anderson, 1998).
The agreement between the two methods was
within the error band of the individual measurements, and the relative error between them was
162
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
approximately 15% for both the atmospheric and
pressurized vessels.
Several tests were conducted under the same
conditions to verify the test reproducibility and
this is shown in Fig. 5 for a few series of atmospheric tests. In this figure experimental values
taken from both of the two independent test
vessels are shown. As can be seen not only are the
tests in the individual vessels reproducible but
there is an outstanding similarity between the two
facilities even with the differences in the geometry
of the condensing plates. The slightly higher differences between the CEB and HFM measurements of the pressurized vessel as compared to the
atmospheric vessel were attributed to an increase
in the conduction heat transfer from the steel side
walls and the connecting bolts to the aluminum
condensing plates and the fact that the bulk and
wall temperatures differed slightly between tests.
In any case these differences are small enough to
consider the heat flux measurements in both vessels to be in good agreement.
In the atmospheric facility there was little variation in the local measurements, even between the
horizontal and vertical plates. Such a similarity is
surprising given the dramatically different behavior of the condensate depending upon the surface
orientation. The vertical plate produced a uniform
film of condensate, while on the horizontal plate
‘cosine shaped’ droplets of approximately 5 – 10
mm diameter were formed, similar to those described by Gerstmann and Griffith (1967) and
Yanadori et al. (1985). The unexpectedly small
increase of only 20% between the horizontal and
the vertical surface is thought to be due to the
presence of noncondensables which decrease the
importance of the film structure because of the
relatively high resistance of the noncondensable
boundary layer. The increase that was observed is
thought to be a consequence of the disruption of
this gaseous boundary layer due to the departure
of the droplets from the horizontal plate. Such an
effect would increase the turbulence within the
boundary layer and reduce the local thickness,
decreasing the gas resistance to heat transfer.
In the case of the pressurized vessel, with a
smoother transition from horizontal to vertical no
effect of orientation was seen, except in some
circumstances where the plate attained a pure
vertical position. Fig. 5 shows the local values as
a function of the angle of the plate to the horizontal along with the plate number This observation
can be explained by the formation of ‘rolling
waves’. Fig. 6 shows a picture of the tracks of the
liquid film. The top of the figure shows the horizontal plate and as you move down the picture
the angle changes as indicated. The tracks of the
droplets can be seen on the purely horizontal
plate but as the angle changes to 5° from the
horizontal the droplets roll across the surface and
form ridges called rolling waves. With a further
increase in the inclination the ridges become even
more developed increasing in size until a drop
departs from the ridge. This phenomena was also
observed by Gerstmann and Griffith (1967) who
saw the formation of similar ridges at angles
greater than 2.75°. They observed that at even
these small inclinations drop like disturbances are
formed and they become elongated and grow in
thickness as they move downstream until the
drops fall from the interface. It is thought that the
combination of the formation of the rolling
waves, the steady droplet departure from the entire inclined surface, uniform turbulent convective
velocities (no sharp discontinuities as in the atmospheric vessel) along with the high heat transfer
resistance of the noncondensable layer resulted in
the uniform HTC relatively independent of the
film. The slight decrease in the HTC observed in
some experiments at the purely vertical portion of
the test vessel is due to the fact that there was
enough liquid to form a complete film instead of
the rolling waves and there was no droplet departure with a perpendicular component to the plate
which would alter the noncondensable boundary
layer.
Since the individual local measurements were
quite similar it was possible to average them
without adding significant errors. This was done
separately for the horizontal and vertical plates in
the atmospheric test section due to the more
extreme differences in the condensation modes
and observed differences of 20%. All 14 plates for
the pressurized test section were averaged together, since there did not seem to be a clear
difference in the condensation mode. The S.D. in
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
163
Fig. 6. The condensate particle tracks within the pressurized vessel. The top of the figure shows the horizontal section and the
formation of 5 – 10 mm droplets. As you move down the plate the angle changes causing ‘rolling waves’.
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
164
the average of the HTC measurements was
slightly higher than the error in the local measurements (15– 20%), but this allowed an overall measure of the heat transfer rate in the entire test
section enabling a simpler comparison with the
models and a better understanding of the overall
effects of the variables studied, therefore the remainder of the paper will deal primarily with the
averages of the local measurements. The average
value was also compared with an overall energy
balance on the steam entering the test section and
the condensate drained from the vessel and found
to be within the error of the average HTC measurement for most tests, thus further validating
the measurements and confirming that a steady
state was achieved.
The averaging of the HTC also allowed a comparison with some previous data. Dehbi et al.
(1991) conducted some experiments of condensation in the presence of noncondensables on a 3.5
m long, 0.038 m diameter, vertical tube within a
4.5 m long, 0.45 m diameter, vessel. Although the
temperature of the condensing surface changed
significantly as a function of position, due to
heating of the coolant as it passed through the
condensing tube, it was possible to compare their
average HTC measurements with the current investigation. Table 3 shows a sampling of data
from Dehbi’s empirical correlation along with our
data under various pressures and different noncondensable concentrations (Wnc/Wv). As can be
seen the magnitude and trends are consistent between the two data bases. The highest discrepanTable 3
Comparison to Dehbi’s experimental results
Experimental conditions
Tb (°C)
Tw (°C)
P (bar)
Wnc
Wnc/Wv
70
30
1.0
0.78
3.52
73.7
33.7
1.5
0.83
5.02
93.5
53.5
2.0
0.71
2.42
106.2
66.2
2.5
0.61
1.59
115.7
75.7
3.0
0.54
1.19
420.3
326.4
22.3
584.0
428.1
26.7
Heat transfer coefficients (SI)
hT,expt
hT,Dehbi
Error (%)
99.9
130.0
−30.0
131.8
115.8
12.1
275.5
221.8
19.5
cies were with low Wnc/Wv ratios (HTC’s
approximately 25% lower) which may be due to
the configuration of Dehbi’s apparatus. To create
the steam they had a heated water pool at the
bottom of the test section. The condensing tube
was 0.3 m above the water level and the cold
water entered at this location. This arrangement
resulted in a distillation of the bulk atmosphere
which caused higher noncondensable concentrations in the upper portion of the vessel. Since the
degradation to heat transfer is not linear with
noncondensable concentration and slight amounts
in pure steam decrease the HTC significantly it is
possible that at these low noncondensable concentrations the averaging of the HTC over the entire
surface of the tube resulted in a low measurement.
As the noncondensable concentration increased
the effect on the HTC of more noncondensables
was less important and thus the averaging could
introduce negligible errors in their measurements.
The discrepancy in the low pressure test (1 bar) is
most likely a result of using this correlation outside of their actual data range.
3.1. Effects of bulk temperature 6ariations
The majority of experiments designed to measure the effects of noncondensable concentration
on the steam condensation were conducted under
atmospheric conditions. This was done to remove
the effects of pressure and allow a more thorough
grasp of the inhibiting effect of the noncondensable boundary layer. Fig. 7 shows the effects of
changing the bulk temperature from 60 to 90°C
within the test section (at atmospheric pressure)
while maintaining an approximately constant wall
temperature of 30°C.
As the bulk temperature rises, the heat transfer
coefficient also increases. Such an increase is a
direct consequence of the amount of steam in the
vessel (Wair/Wv). Given the test protocol detailed
in Section 2.3, a bulk temperature rise is achieved
by injecting hot steam into the vessel until reaching the saturation conditions at the desired temperature. Then, as the wall temperature is kept
constant, the driving force of the condensation,
which is dependent upon the steam concentration
difference between the gas bulk and the wall, is
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
165
Fig. 7. Evolution of the heat transfer coefficients with bulk temperature and steam mass fraction changes. As Tb increases the molar
fraction of steam increases, resulting in higher HTC measurements.
subsequently increased, resulting in more steam
condensing onto the wall. In addition, the density
difference between the bulk and the wall (rgi −
rbg) becomes larger, since an increase in the
amount of steam causes a smaller bulk gas density. This results in an enhancement of the natural
convection motion of the gas, which in turn, and
along with the increase in the concentration gradient, enhances the condensation heat transfer.
3.2. Effects of wall temperature 6ariations
The wall temperature is an important variable
in the AP600 PCCS because it is held at a low
semi-constant temperature, as opposed to current
reactor containment walls which are allowed to
evolve freely with the bulk temperature (no external cooling). This new concept was not investigated in the data bases of Tagami or Uchida as a
variable of the system. Thus, there is still a need
to understand how this variable will effect the
heat transfer rate.
The driving potential is a function of both the
density difference between the bulk and the interface and the concentration gradient. In this set of
experiments the aim was to study how changes in
the wall temperature, and thus changes in the
density and steam concentration at the liquid gas
interface, would alter the HTC. Fig. 8 shows the
variation of the HTC with wall temperatures for
both atmospheric and pressurized experiments.
The atmospheric tests were conducted with a constant bulk temperature of 90°C and wall temperatures that varied from 30 to 80°C. The pressurized
tests were conducted at a pressure of 3 bar with 1
atm of noncondensables (air) and a bulk temperature of 115.7°C with various wall temperatures.
This figure shows that the HTC decreases with
166
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
Fig. 8. Evolution of the heat transfer coefficients with constant bulk and varying wall temperatures (Tb # 90°C for P= 1 bar, and
Tb # 116°C for P= 3 bar). A decrease in the HTC is observed as the wall temperature is reduced since the increase in the heat flux
is overwhelmed by the increase in DT.
increasing temperature difference between the
bulk and the wall (approximately 25% with a
change in DT from 10 to 60°C), although the heat
flux increases the increase in the subcooling, DT is
larger than the increase in the heat flux, thus
resulting in a lower HTC measurement. The trend
is the same at both pressures although the curve
for the higher pressures is elevated due to the
enhancement of HTC with pressure.
As the wall temperature is increased the concentration of steam at the wall will increase while
remaining constant in the bulk. This will reduce
the condensation driving force due to the concentration gradient (Xvb − Xvi). Along with a reduction in the concentration gradient there will be a
reduction in the natural gas motion which is a
function of the density difference between the
bulk and the interface (rgi − rbg). This is due to a
decrease in the density at the interface as a result
of the increased temperature (ideal gas law). Since
the density at the interface is closer to the bulk
density there is a decrease in the convection driving force. Therefore, as the wall temperature increases the heat flux decrease substantially. The
HTC which is directly proportional to the heat
flux but inversely proportional to the temperature
difference (Tb −Ti ) increases slightly with an increase in wall temperature because the reduction
in the heat flux is overwhelmed by the large
decrease in the DT.
3.3. Effects of increases in bulk pressure
As mentioned in Section 2.3, the test protocol
followed the events sequence during postulated
accidents: initially there was 1 atm of air in the
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
167
Fig. 9. Evolution of the heat transfer coefficient with pressure. This increase is caused not only by the increase in pressure but also
the increase in the molar fraction of the steam.
vessel then steam was injected until the desired
pressure was reached at a saturated state. As can
be observed in Fig. 9, the HTC increases with
pressure, showing a quasi-linear trend for pressure
greater than 1.5 bar. This increase can be attributed to the rise in steam concentration that
accompanies the increase in the system pressure.
Namely, the condensation flux is enhanced by the
enlargement of the gradient of steam concentration due to the fact that the steam content in the
gas bulk is higher at higher pressures. This reinforcement of the steam concentration gradient is
only partially compensated by the reduction that
higher pressures cause on the diffusion coefficient
(inversely proportional to pressure). With these
effects one should add that the pressure rise indirectly involves a minimization of the noncondensable contribution to the gas molar fraction.
3.4. Effect of helium in the noncondensable
mixture
Experiments were conducted with helium gas
mixed with air in molar concentrations of the
total noncondensable ranging from 0 to 50%,
which corresponds to total helium concentrations
between 0 and 30%. In the atmospheric experiments the helium was added to the air prior to the
injection of steam. Therefore if 30% of the noncondensable was originally helium this would remain constant for the various bulk temperatures,
however the total helium molar fraction would
decrease with an increase in the bulk temperature.
Several experiments were done with concentrations ranging from 0 to 30% molar fraction of
helium in the noncondensable and no noticeable
effect was observed. Fig. 10 shows the HTC as a
168
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
Fig. 10. Heat transfer coefficients with varying helium concentrations (P= 1 bar, Tw = 30°C).
function of Tb −Tw, for a constant wall temperature of 30°C and various bulk temperatures for
helium concentrations in this range. As can be
seen there are no significant effects on the HTC
caused by the introduction of helium. These findings are consistent with those observed by Pernsteiner et al. (1992) and were thoroughly
explained by Herranz et al. (1998) based on the
compensating effects that helium has on the buoyancy driving force and on the diffusion coefficient
of steam for helium concentrations up to about
35% or of the noncondensables.
Experiments were also conducted with helium
at more prototypical pressures with the same
range of helium in the noncondensable mixture.
These tests were performed by first attaining a
steady state condition at 3 bar and a saturation
temperature of 115.7°C. Helium was then slowly
injected through a Dwyer RMA122 flow meter
into the same line that the steam was entered
through. This allowed the helium to be heated as
it entered the vessel. This procedure is similar to
how the hydrogen would be introduced in an
accident scenario (ie. metal – water reactions in the
core produce hydrogen which is carried along
with steam into the containment). As the helium
was injected it was necessary to reduce the steam
flow rate so that the total flow rate was constant
and maintained at a pressure of 3 bar. This resulted in an increase in the total noncondensable
concentration and a reduction in the temperature
of the vessel (saturated conditions were maintained). After a certain concentration of helium
was injected a gas sample was taken to obtain a
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
169
Table 4
Helium in the noncondensable mixture at 3 bar
Test
Tbulk (°C)
Twall (°C)
PHe (bar)
Pair (bar)
Pv (bar)
PT (bar)
HFM
CEB
T5000
T5001
T5002
T5003
T5004
117.69
114.57
104.63
105.75
91.89
77.07
71.13
59.89
61.30
45.87
0.00
0.13
0.27
0.40
0.83
1.16
1.20
1.54
1.36
1.41
1.84
1.67
1.19
1.24
0.76
3.0
3.0
3.0
3.0
3.0
593.67
503.51
315.81
335.83
187.62
574.09
493.07
323.05
302.33
183.58
secondary measure of the helium molar fraction.
Table 4 shows the results and key parameters of
the experiments for pressures of 3 bar and concentrations below 40% molar fraction of the
noncondensable.
A few experiments were conducted with concentrations greater than 40% and it was found
that as the noncondensable gas density approaches that of the steam, stratification can occur where a noncondensable gas layer is stable
above a steam rich layer. Fig. 11 shows the bulk
temperature profiles along with the heat transfer
coefficients for the individual plates for a test with
53% molar fraction of helium and 47% molar
fraction of air in the noncondensable gas mixture
(Pair =0.147, PHe = 0.166, Pv =0.687) along with
a test consisting of 100% air (Pair = 0.313, Pv =
0.687) as the noncondensable. Both tests were
performed under the same conditions (e.g. steam
flow rate and coolant flow rate) except for the
replacement of the air with a mixture of air and
helium. In this test the helium was injected after
reaching steady state and taking data with the
air– steam mixture. The helium was introduced
along with the steam at a rate of 5.29e−4 m3 s − 1
until approximately 50% of the noncondensable
was helium (air – steam was allowed to escape
through the suppression pool maintaining a total
pressure of 1 atm. The helium concentration was
verified by mass spectrometer measurement at the
time of the test). The temperature profile clearly
shows the stratification of a noncondensable rich
layer of gas above a steam rich region. This effect
is also observed in the HTC measurements. Plates
1 – 8 which are in the upper portion of the test
section show a dramatically lower HTC then
plates 9 – 14 which are lower in elevation and are
adjacent to the steam rich layer. The HTC’s for
plates 9 – 14 with high helium concentrations are
similar, quantitatively, to those with no helium
present, however they seem to increase slightly
with a decrease in the elevation of the plate.
This stratification effect was seen at lower helium concentrations down to about 45% helium in
the noncondensable mixture, however the pocket
of the noncondensable rich layer is slightly reduced in size with the lower helium concentrations. It is also slightly less stable. This is due to
the fact that as the helium concentration reaches
this level it is approximately the same density as
the steam but as steam is continually added the
temperature of the steam rich region can increase
and become less dense than the noncondensable.
This along with the convective motion within the
test section can result in a break down of the
stratification layer allowing a more thoroughly
mixed bulk atmosphere with approximately constant bulk temperatures and much more uniform
HTC measurements.
In summary, the amount of helium in the total
mixture is not as important as the amount of
helium in the noncondensables. If the fraction of
helium in the noncondensable is high enough and
the noncondensable mixture density becomes
close to (or less than) the steam density, stratification is possible and was observed.
4. Summary and final remarks
An experimental investigation of the condensation phenomena anticipated to occur in a possible
accident within Westinghouse’s AP600 nuclear reactor has been conducted. The in-depth study has
170
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
Fig. 11. The existence of stratification at high helium concentrations in the bulk noncondensable mixture (P = 1 bar). The upper
portion of this figure shows the temperature distribution within the test vessel. This indicates a stratification of noncondensable gas
for high helium concentrations. The lower portion of this figure confirms the existence of the stratification by showing the local heat
transfer coefficients.
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
generated a valuable data base to validate models
and has pointed out several interesting phenomena that should be considered when modeling
condensation under this range of conditions. (1)
At inclinations of greater than 5° from the horizontal droplets will start to roll and coalesce
forming ridges called rolling waves. This along
with a noncondensable layer results in a fairly
uniform heat transfer rate across the surface
which is slightly higher than a pure vertical surface. At angles less than 5° droplets can form
changing the mode of condensation. The enhancement to the HTC is however of the second order,
because the resistance to heat transfer due to the
noncondensable boundary layer dominates making variations in the film resistance a secondary
effect. (2) Differences in both the wall temperature and the bulk temperature effect the HTC and
may be relevant in predicting the heat transfer
rate. Therefore, if, as in the AP600, the primary
heat removal is from the condensation of steam in
the containment it is necessary to use a more
complex model than the simple correlations which
depend only on the ratio Wnc/Wv. (3) The increase
in pressure causes an increase in the HTC, however it is necessary to realize that as the pressure
changes there is a significant affect due to concentration changes that will also increase the HTC.
These changes may perhaps be even more significant than the pressure enhancement itself. (4) The
addition of light noncondensable gases has little
effect on the HTC up to concentrations of approximately 40% molar fraction added to the air.
At this point the density of the noncondensable is
approximately the same as the steam and buoyancy forces (rgi − rgb) will tend to zero. At higher
helium concentrations when the noncondensable
mixture is less dense than the steam there can
exist a stable pocket of noncondensables above
the steam rich bulk which prohibits condensation
and can result in as much as a 50% reduction in
the heat transfer.
Further work is under way to examine the
effects of high concentrations of helium under
both atmospheric and pressure conditions. The
concentrations needed to effect the HTC and
form stratification are above that which can exist
in the bulk of the containment since they will be
171
above the detonation limit, however there are
sub-compartments where these concentrations
might exist. If one wishes to model condensation
in these areas the amount of helium and level of
stratification could be important.
5. Nomenclature
A
Cp
D
h
k
M
Mw
P
RB
q
V
t
T
W
X
x
area
specific heat
diffusion coefficient
heat transfer coefficient
thermal conductivity
reduced mass
steam molecular weight
pressure
relative humidity
heat flux
volume flow rate
time
temperature
mass fraction
molar fraction
axial coordinate
Greek symbols
D
difference between appropriate
quantities
r
density
Subscripts
a,b
components in binary system
air
air
b
bulk
bg
bulk gas
coolant cooling plate water
conv
convection
cond
condensation
g
gas
gi
gas at the liquid interface
He
helium
i
index for plates
l
liquid phase
nc
noncondensable gas at system
temperatures
T
total
w
wall
v
vapor phase
172
M.H. Anderson et al. / Nuclear Engineering and Design 185 (1998) 153–172
References
Anderson, M.H., 1998. Steam Condensation on Cold Walls of
Advanced PWR Containments. PhD Thesis, University of
Wisconsin, Madison, 1998.
Anderson, M.H., Herranz, L.E., Corradini, M.L., 1998. Evaluation of condensation modeling based on mass transfer
analogy. National Heat Transfer Conference, Baltimore,
MD.
Collier, J.G., Thome, J.R., 1994. Convective Boiling and Condensation, 3rd ed., chap. 10. Oxford University Press,
Oxford, 1994.
Corradini, M.L., 1984. Turbulent condensation on a cold wall
in the presence of a noncondensable gas. Nucl. Technol.
64, 186 – 195.
Dehbi, A.A., Golay, M.W., Kazimi, M.S., 1991. Condensation
experiments in steam – air and steam – air-helium mixtures
under turbulent natural convection. National Conference
of Heat Transfer, AIChE Symp. Ser., pp. 19 – 28.
Green, J., Almenas, K., 1996. An overview of the primary
parameters and methods for determining condensation
heat transfer to containment structures. Nucl. Saf. 37 (1),
26 – 47.
Gerstmann, J., Griffith, P., 1967. Laminar film condensation
of the underside of horizontal and inclined surfaces. Int. J.
Heat Mass Transf. 10, 567 – 680.
Herranz, L.E., Anderson, M.H., Corradini, M.L., 1998. The
effect of light gases in noncondensable mixtures on condensation heat transfer. Int. Heat Transfer Conf., 1998Kyongju, Korea.
Huhtiniemi, I.K., Corradini, M.L., 1993. Condensation in the
presence of noncondensable gases. Nucl. Eng. Des. 141 pp.
429 – 446 (1993).
.
Kataoka, Y., Fukni, T., Hatamiya, S., Nakao, T., Naitoh, M.,
Sumida, I., 1992. Experiments on convection heat transfer
along a vertical flat between pools with different temperatures. Nucl. Technol. 99, 386 – 396.
Kennedy, M.D., Peters, F.E., Carelli, M.D., Pieczynski, A.T.,
1994. Advanced PWR passive containment cooling system
testing. Proc. ARS’94 Int. Topical Meet. on Advanced
Reactor Safety, April 1994, vol. 1, pp. 249 – 256.
Kohnke, P.E., 1995. ANSYS User’s Manual, Revision 5.2.
ANSYS Inc., 1995.
Pernsteiner, A., Huhtiniemi, I.K., Corradini, M.L., 1992. Condensation in the presence of noncondensable gases: effect
of helium. Proc. NURETH-5 Conf. Salt Lake City, UT,
USA. Sept. 21 – 24, 1992, pp. 1071 – 1078.
Spencer, D.R., Woodcock, J., Wright, R.F., Gresham, J.A.,
1993. Westinghouse— gothic comparison with passive containment cooling system tests scaling evaluation and analysis. ASME/JSME Nuclear Engineering Conf., 1, ASME.
Tagami, T., 1965. Interim Report on Safety Assessments and
Facilities Establishment Project for June 1965, No. 1.
Japanese Atomic Energy Research Agency, unpublished
work.
Uchida, H., Oyama, A., Togo, Y., 1965. Evaluation of postincident cooling systems of light-water power reactors.
Proc. Int. Conf. on Peaceful Uses of Atomic Energy,
Geneva, Switzerland, 13, pp. 93 – 102.
Class 2 WCAP, 1992. AP600 1/8th large scale passive containment cooling system heat transfer test baseline data report.
WCAP-13566.
Yanadori, M., Hijikata, K., Mori, Y., Uchida, M., 1985.
Fundamental study of laminar film condensation heat
transfer on a downward horizontal surface. Int. J. Heat
Mass Transf. 28 (10), 1937 – 1944.