Article

Artificial Intelligence-Assisted Heating Ventilation and Air Conditioning Control and the Unmet Demand for Sensors: Part 1. Problem Formulation and the Hypothesis

Department of Energy and Refrigerating Air-Conditioning Engineering, National Taipei University of Technology, Taipei 10608, Taiwan
*
Author to whom correspondence should be addressed.
Sensors 2019, 19(5), 1131; https://doi.org/10.3390/s19051131
Submission received: 12 February 2019 / Revised: 26 February 2019 / Accepted: 28 February 2019 / Published: 6 March 2019
(This article belongs to the Special Issue Artificial Intelligence and Sensors)

Abstract

:
In this study, information pertaining to the development of artificial intelligence (AI) technology for improving the performance of heating, ventilation, and air conditioning (HVAC) systems was collected. Among the 18 AI tools developed for HVAC control during the past 20 years, only three functions, including weather forecasting, optimization, and predictive controls, have become mainstream. Based on the presented data, the energy savings of HVAC systems that have AI functionality is less than those equipped with traditional energy management system (EMS) controlling techniques. This is because the existing sensors cannot meet the required demand for AI functionality. The errors of most of the existing sensors are less than 5%. However, most of the prediction errors of AI tools are larger than 7%, except for the weather forecast. The normalized Harris index (NHI) is able to evaluate the energy saving percentages and the maximum saving rations of different kinds of HVAC controls. Based on the NHI, the estimated average energy savings percentage and the maximum saving rations of AI-assisted HVAC control are 14.4% and 44.04%, respectively. Data regarding the hypothesis of AI forecasting or prediction tools having less accuracy forms Part 1 of this series of research.

1. Introduction

Heating, ventilation, and air conditioning (HVAC) systems provide a suitable living environment with thermal comfort and air quality. These mechanic–electrical systems include several types, such as air conditioners, heat pumps, furnaces, boilers, chillers, and packaged systems [1]. In most of the countries, the building sector accounts for nearly 40% of the total consumed energy [2]. For every building type, HVAC and lighting systems occupy more than half of the energy consumption [3]. A large fraction of the increasing energy expenditure for the buildings was because of the extending HVAC installations for better thermal comfort and air quality [4]. Therefore, the HVAC system plays an important role in the energy efficiency of buildings. Improving the control of HVAC operations and the efficiency of the HVAC system can save significant energy, increase thermal comfort, and contribute to improved indoor environmental quality (IEQ) [5]. Artificial intelligence (AI) was founded as an academic discipline in 1956. In contrast to human intelligence, AI demonstrates machine intelligence and imitates human behaviors through mathematical coding and mechanical works. In 1997, an AI program known as Deep Blue defeated the reigning world chess champion, Garry Kasparov [6]. It was the first time that the chess-playing computer performed better than a human. That moment was a turning point in the development of AI that enabled AI to be utilized more in a wider range of applications.
In this study, how AI could improve the performance of heating, ventilation, and air conditioning (HVAC) systems was investigated. A total of 783 articles, which were related to AI research and its application on HVAC systems, was collected from three databases, including the Science Direct on Line (SDOL), IEEE Xplore (IEL Online), and MDPI. The MDPI database is a publisher of open access journals. Following the preferred reporting items for systematic reviews and meta-analyses (PRISMA) method [7] for reporting, systematic review, and meta-analysis, the collected articles were screened, and only 97 full-text articles met the requirements. All of the selected articles regard theoretical work and practical experiments about HVAC control. Detailed information of these articles, including the study cases, AI tools, or developments, and the improved performance of HVAC systems, are presented in Section 2 and summarized in Table 1. Among the 18 developed AI tools, only two methodologies have become mainstream elements of HVAC controls over the past 20 years, which are the forecasting and optimization and the predictive controls. These two main methodologies will be discussed in Section 3.
Even though the development of AI tools for HVAC systems is more than two decades old, the performance of HVAC systems controlled by AI tools has been unsatisfactory overall. Their energy savings, energy consumption, precision of heating and cooling based on load forecasting, and the predictive ability of the predictive controls, will be discussed in Section 4. Based on [8], from 1976 to 2014, the average energy savings of HVAC systems by applying the scheduling control technique reached 14.07%. The maximum energy savings of HVAC systems was 46.9% after applying smart sensors for smart air conditioners in 2014 [9]. However, from 1997 to 2018, the average energy savings of HVAC systems using AI tools reached 14.02%. The maximum energy savings when applying case-based reasoning (CBR) controlling tools for the HVAC systems in an office building was only 41% in 2014. Therefore, the energy savings of HVAC systems after applying AI tools was less than that of traditional energy management system (EMS) controlling techniques.
This study will be conducted in three parts, including (1) problem formulation and the hypothesis, (2) simulations and verification, and (3) confirmatory experiments. The first part, problem formulation and the hypothesis, will analyze the problem of HVAC systems using AI tools having less accuracy of forecasting, or and a prediction of the tools that result in poor energy savings is hypothesized. If forecast accuracies could be improved and prediction errors could be reduced, the energy savings of HVAC systems would improve. From the 35 collected articles with information regarding sensor specifications, the literature states that the existing sensors are for feedback control, not prediction, and therefore lack the capability to provide priori information notice (PIN). Hence, an innovative PIN sensor design and more precise predictive control is presented in this study as the solution to increase the energy savings of HVAC systems.
The second part of the study covers the simulation and verification of the energy-saving hypothesis and PIN sensor design through numerical simulation. Through numerical simulation, the calculated energy savings of an HVAC system using a PIN sensor will be provided. The third part consists of the confirmatory experiment where the designed PIN sensors are utilized under the various operating conditions of an HVAC system in an environmentally controlled room to measure energy consumption. The energy consumption of the HVAC system utilizing the PIN sensors and AI tools will be compared with those employing the proportional–integral–differential (PID) controllers, and the simulation results are analyzed to give evidence of the hypothesis presented in this study.

2. AI Developments and the Applications for HVAC Systems

In this study, keywords including AI, machine learning, heating, ventilation, and air conditioning, were utilized to conduct a paper survey from the Science Direct on Line (SDOL), IEEE Xplore (IEL Online), and MDPI databases. Initially, 737 papers were found from SDOL fitting the criteria of our paper survey, while 34 were found from IEEE Xplore, and 12 were found from MDPI. After further review, articles that were not related to HVAC control or methods to enhance performance were separated out. A total of 79 articles fit the requirements of either (1) describing the applying factory; (2) developing innovative AI tools and their use involving HVAC control; and (3) depictions describing the overall performance of an HVAC system after applying AI control tools. These articles were chosen for further exploration.

2.1. Study Case

The published year, HVAC system, developed AI technology, and key results of the collected 79 articles are listed in Table 1.

2.2. Developed AI Tools

In the second column of Table 1, there are 18 AI tools for HVAC systems. Among them, the most well-known AI tools are neuro networks (NN), including artificial neuro networks (ANN), recurrent neuro networks (RNN), spiking neuro networks (SNN), and wavelet ANN [15,16,19,22,23,24,27,29,34,35,37,39,40,44,51,52,53,59,60,64,76,79,81,82,85,87,98,99,100,102]. ANN is based on the nervous system, the human brain architecture, and the learning processes. A set of interconnected neurons can be separated into three layers, which are composed of input, output, and hidden layers. The HVAC system inputs, network weights, and the transfer functions of the network lead to the output of ANN. The ANN controller doesn’t need to identify the control model. The weight coefficient can be regulated to minimize the costs. ANN can simulate the working procedure of the human brain; therefore, it has the capability of having insight into a complex system. However, the brain-like controller has disadvantages due to having to take a lot of time for off-line training as well as requiring a large amount of data for the system to make quality predictions.
The second AI tool is used for the predictive control functions of ANN: fuzzy or model-based predictive control (MPC) [32,42,47,48,50,65,72,75,87,92,94,101,103,104]. Predictive control provides feedback of the results of the prediction to the system to allow for the adjustment of a system’s control parameters. The predictive feedback system is different from previous control systems due to the design of the feedback sensor. Collotta etc. created a non-linear autoregressive neural network auto regressive external type (NNARX-type) structure in 2014 for indoor temperature prediction [75]. In addition to enhancing the control performance, the signal of a predictive control system could be discontinuous for a non-linear system. This is different from the continuous signals that are needed for a linear system managed by a traditional PID controller, which is based on the Laplace transform and linear transfer functions. The insight ability of the ANN is similar to the human insight process, and is a smart way to improve the performance of a non-linear system commanded by predictive control.
The third type of AI tool is known as distributed AI and the multi-agent system (MAS) [20,26,31,57,58,62,66,72,73,83]. In addition to strengthening the entire performance of a system using ANN or predictive control, the subsystems, sensors, and actuators of an HVAC system are able to communicate and interact with each other and become an even more intelligent system through the use of MAS.
The fourth type of AI tool is what is known as the genetic algorithm (GA) method, which is based on biological evolution theory [14,45,54,59,61,63,74,82,93]. The GA method utilizes global non-derivative-based optimization to tune the set points of HVAC systems and meet the thermal comfort requirements without the use of a mathematical model of the system. However, the problem with the GA method is that it requires massive calculations and long run times. Therefore, the GA method might be inappropriate for the real-time operation of an HVAC system.
The fifth type of AI tools is employed for fuzzy control [21,32,33,46,51,59,102], support vector machines (SVM), and R [28,30,38,56,79,82,89]. These two AI tools have the same amount of published articles. A fuzzy logic controller (FLC) is similar to human reasoning and can be used to control a complex system by using the rules of the IF–THEN algorithm. The utilization of fuzzy logic grades and rules yields a low real-time response speed. This situation limits the application of the FLC onto HVAC systems. However, SVM and R could be used in conjunction with the FLC for data classification by finding the hard margins of various data sets to determine the proper control methodologies, modeling, or regression for decision making. This method is used mainly for analyzing huge amounts of data, modeling, and decision making, but is rarely used for HVAC system applications.
The seventh AI tools are model-based controls [10,17,18,69,91] and deep learning (DL, or reinforced learning) [36,49,88,97,98]. The model-based control models, when used with the SVM and R tools, collect and analyze data utilizing the distributed AI tool, and communicate and interact with the MAS tool. The advantage of model-based control is its predictive strategy and high capability of observation. However, the model-based control is a feedback control methodology that can only be applied to a time-independent system. It can’t solve problems within a non-linear time-variable system. A deep learning tool could determine a control strategy according to a system’s present conditions and information from previous cases through a learning process without the use of modeling. Deep learning is one of the broader machine learning methods, which is based on learning data representations, as opposed to following task-specific algorithms. The learning types are supervised, semi-supervised, or unsupervised. For an HVAC system, deep learning is a novel methodology to achieve more intelligent control.
The knowledge-based system (KBS) [11,12,13,43] is similar to the DL tool. However, the difference between them is that the DL tool is for controlling the system, and KBS is used for building various SVM and R knowledge databases. KBS could provide an optimal control strategy for various HVAC systems through the expert system. KBS and DL are mostly used for problem-solving procedures and to support human learning, decision making, and actions. Another key tool is case-based reasoning (CBR) [78]. However, there are not many published articles regarding this. CBR is able to analyze a control strategy and provide the most optimal one in conjunction with KBS or model-based control in certain cases. Nevertheless, KBS, DL, and CBR tools all need a large amount of data to learn from, and will require a lot of time to collect the control data, which will increase initial installation costs.
In addition, there are some other AI tools worth mentioning, which include: particle swarm optimization (PSO) [35,77,80] and the artificial fish swarm algorithm (AFSA) [90] for optimizing control strategies, the hidden Markov model (HMM) [70,71,89] for modeling, radial basis function (RBF) [67,68] for data collecting and analyzing, data combining technology [94,95], k-nearest neighbor (KNN) [89] for analyzing the closest data attribute, and the autoregressive exogenous (ARX) technique [65] for regression analysis with an external input and feedback control system.

2.3. AI Applications for HVAC Systems

The control methodologies of AI development can be observed by comparing columns one and two of Table 1, which outline the AI tools and related HVAC systems, respectively. There are four main HVAC system applications for AI tools, including (1) medium to large-scale utilities for commercial buildings [10,13,17,20,22,24,27,29,35,43,44,53,57,63,64,66,71,72,73,76,78,80,82,84,87,91,96,100,105], (2) air conditioners or chillers for residential buildings [11,15,18,19,21,36,37,38,39,42,51,52,60,61,62,65,67,68,69,70,72,75,79,83,86,88,92,94,97,98,99,101,102], (3) air conditioning systems for composite buildings [25,28,30,34,40,45,50,54,56,58,59,74,77,81,85,90,93,95,103,104], and (4) specific systems, such as a greenhouse, a regenerating power system, a power system, etc. [12,14,16,23,26].
The use of AI tools applied onto commercial and residential buildings will be discussed, due to the different occupant behavior patterns between the two building types. The occupants of commercial buildings operate within the confines of working in the numerous companies within a commercial building with a fixed office schedule, and therefore have more predictive air-conditioning demands. The HVAC systems of most commercial buildings are operated by professional energy managers under certain routines and energy-saving targets. Yet, the occupants of residential buildings, being residents, have different air-conditioning behaviors and demands. In general, the HVAC systems of most residential buildings are not operated by professional energy managers.
As mentioned in the previous section, ANN + fuzzy tools are the most widely utilized AI tools for commercial and residential buildings. The adoption ratios for these two types of buildings are 34.5% (10/29) and 24.2% (8/33), respectively. The ANN tool can imitate the operating model of the human brain to implement complex control strategies by learning and analyzing large amounts of data. This is suitable for commercial buildings due to the predictive nature of the occupants. Unfortunately, the ANN tool is not suitable for use in residential buildings. The ANN tool combined with DL, reinforced learning, or deep reinforcement learning (DFL) equips the system with the capability of feature extraction to analyze data and make control decisions, which replaces the need for a professional energy manager.
For commercial buildings, CBR and KBS tools operate alongside ANN + fuzzy tools. CBR and KBS tools can practice model base control and forecast several conditions, including weather, occupancy, and energy consumption, optimize control set points, improve the energy efficiency of an HVAC system, and ensure thermal comfort [13,22,24,27,29,35,43,44,53,64,76,78,84,100,105]. Based on the cases utilizing ANN, CBR, and KBS tools, the ability to make predictions is the most significant function of these AI tools. For residential buildings, DL, distributed AI, and MAS tools function alongside ANN + fuzzy tools. If the fundamental devices of HVAC systems are equipped with distributed AI tools for saving energy and ensuring the thermal comfort, and are able to interact with each other through an MAS tool, then predictive control and the prediction of future environmental conditions for enhancing a system’s overall performance could be achieved.
Finally, the most recent development of AI tools applied onto composite buildings is predictive control [50,103,104], which improves the control performance of an HVAC system by having the ability to make predictions. Composite building systems are a mix of residential commercial building systems.

3. Theoretical Analysis of AI Assisted HVAC Control

In this section, the control performance differences between typical HVAC controls and AI-assisted HVAC controls are analyzed quantitatively. The control outputs were calculated by the common analytic solutions of the AI-assisted HVAC controls in Table 1, which were then compared with those of the on–off and proportional–differential–integral (PID) controls.

3.1. Typical HVAC Control

Typical HVAC controls for residential and commercial buildings utilize on–off and PID control algorithms [106] in addition to sensor feedback controls to have the ability to control parameters such as a system’s temperature, humidity, and ventilation. The controllable structure is presented in Figure 1.
The control block diagram in Figure 1 runs PID or an on–off algorithm by comparing the set point values and sensor feedback values, and then providing the subsequent output control signals to an HVAC system.
The on–off control output values are calculated according to the following Equation:
σ [ S ( t ) SP ] { 1 if   S ( t ) SP > T h r e s h o l d   V a l u e 0 if   S ( t ) SP = 0 ± Var [ S ( t ) ]
where σ is the step function corresponding to the difference reading of the sensor feedback, S(t), and the set point, SP, of an HVAC system. If the difference value is larger than the designed threshold value, the value of σ is one. If the difference value of S(t) and SP is within the standard variation of S(t), the value of σ is zero. The modification of on–off control is that, instead of being zero, the value of σ is located within the range of 0.5~0.7 when the difference value is within the standard variation of S(t). This is the so-called floating control to avoid the large oscillation of a control signal of the HVAC system. However, no matter how the typical on–off control or floating control is utilized, the final control signal is determined by the difference of S(t) and SP, as shown in Equation (1).
The output of PID control, as shown in Figure 1, is calculated according to the following equation:
K P · [ S ( t ) SP ] + K I · [ S ( t ) SP ] dt + K D · d [ S ( t ) SP ] dt
where K P is the proportional constant, K I is the integral constant, and K D is the differential constant. The differentiation between S ( t ) SP is able to predict the controlling oscillation of the next stage and eliminate it within a short period. The integration of S ( t ) SP is capable of providing a stable output of PID control and reaching the final state of S ( t ) SP 0 after a longer period.

3.2. AI-Assisted HVAC Control

The block diagram of AI-assisted HVAC control resulting from the collected articles is shown in Figure 2.
The core of AI assisted HVAC control is the ANN tool illustrated as controller #1 in Figure 2. The output, y, of the ANN tool is produced through many processes, or neurons, and these neurons interconnect with each other by multiplying with the weights, ω, as shown in the following equation [9,15,16,22,23,24,27,29,44,47,51,52,64,75,81,85,87,99]:
y ( x ) = g ( i = 0 n ω i x i )
where ω 0 , ω 1 , … and ω n are the weighting coefficients, and g is a non-linear activation function, which is usually a step or a sigmoid function, as illustrated by the following equation:
g ( x ) = 1 1 + e β x   β > 0
The neuron output, y, is unidirectional both for feedback or feedforward control. The ANN tool is skilled at solving data-intensive problems within the categories of pattern classification, clustering, function approximation, prediction, optimization, content retrieval, and process control. It is similar to the human ability to make a single decision based on multiple inputs. Therefore, the main characteristic of AI-assisted HVAC control is its multiple sensor feedback, as shown in Figure 2. The multiple feedback sensor collects several sensor inputs, including controllable and uncontrollable parameters, to build a database. AI tools are not only in the central control port, as shown in controller #1 of Figure 2, but they are also applied in the sensor port, as shown in controller #2 of Figure 2, for more intelligent control.
The most utilized intelligent control functions are the optimized setting and predictive control functions, as shown in Figure 2. First, the optimized setting function utilizes the KBS [11,12,13,43,67,68,84] or CBR [34,78,105] tools from the database block to determine the set point (SP). The similarity index (SI) is employed during the calculation process, as shown in the following equation:
SI i = f ( | y ic y ip MV i | )
where y ic and y ip are the neuro outputs of the variable i for the control and past case, respectively. MV i is the mean difference of the variable i in the database. The function f maps the control case to the whole case difference. Based on SI, the global similarity (GS) is calculated according to the following equation:
  GS = i ( SI i × ω i ) i ω i ,   i = 1 ,   2 , ,   n
where n is the number of the controlled case and ω i is the weighting coefficient.
The proportion P j of the prediction from the past case j is:
P j = GS j GS T ,   j = 1 ,   2 , ,   m
where GS T is the sum of the global similarities between the selected m cases. Then, the optimized setting point (SPopm) can be determined by the following equation:
SP opm =   j ( P j × SP j ) / N ( j )
where SP j is the set point of past case j. The optimized set point is determined from the built database, including the previous controllable and uncontrollable parameters, and the desired SP value.
In addition to the optimized settings, other intelligent control functions are the predictive controls, which utilize the ANN + fuzzy tool as the central controller, as shown in controller #1 of Figure 2. This tool employs an IF–THEN algorithm to enhance the control performance by predicting the likelihood of future errors effectively and providing proper feedback. The SVM and R tool [28,30,38,56,79,82,89] and autoregressive with exogenous terms (ARX) tool [65] are also suitable for central and edge computing ports, respectively.
The first step of predictive control is to determine probability. After comparing the calculation methods of several articles, the suggested equation is shown in the following:
Prob i ( t + 1 ) = k θ [ τ i , k ] α · [ S i , k ( t ) ] β k [ τ i , k ] α · [ S i , k ( t ) ] β N ( k )
where i indicates the ith sensor for detecting controllable or uncontrollable parameters. S i , k ( t ) is the ith sensor value, τ i , k is the pheromone intensity, and α and β are the experience parameters. In addition to the probability value, a Guess value is also necessary for predictive control. It is calculated after the ANN runs [9,15,16,22,23,24,27,29,44,47,51,52,64,75,81,85,87,99] according to the following equation:
Guess i ( t + 1 ) = g ( k ϵ θ ω k S i , k ( t ) )
where ω 0 , ω 1 , … and ω n are the weighting coefficients, and g is the non-linear activation function, as illustrated above. The following equation is able to predict the sensor output of the next stage.
S ( t + 1 ) = a · S ( t ) + b · R 1 · i   =   0 n MAX [ Prob i ( t + 1 ) ] + c · R 2 · i   =   0 n Guess i ( t + 1 )
where a is the momentum parameter, b is the self-influence parameter, and c is the measure insight. R1 and R2 are the random numbers within [0,1] for predictive control.

3.3. Control Performance Index

The Harris index (H) and normalized Harris index (NHI) [107,108] are utilized for evaluating the performances of typical and AI-assisted HVAC control outputs, as shown in the following equations:
H = lim t η t = lim t V 1 Var [ y ( t + 1 ) ]
NHI = 1 − 1/H
where V 1 = Var [ y | initial   condition ] . The Harris index compares the variations between the initial control y(0) and y(t + 1). There are several articles discussing the effect of rising time, settling time, and overshooting [32] on the control performance of the linear system. However, the Harris index and NHI are able to assess the performance of linear, non-linear, feedforward, and feedback control systems [109], as well as thermal comfort and energy efficiency, etc.

4. Results and Discussions

In this study, the Harris index and NHI are employed to estimate the performance of HVAC systems in Table 1 managed by On–Off, PID, and AI-assisted control. The sensor signal outputs of the On–Off and PID controls, as shown in Equations (1) and (2), have a positive linear relationship with the Harris index. Therefore, the sensor types mentioned in the articles in Table 2 will be indicated and, then, the sensor errors will be calculated.
In addition, one commercialized product, Ambi Climate, with a geolocation sensor and applied sensors for the academic cases are analyzed in Table 2. The sensor types and the individual sensor errors are illustrated in Figure 3.
The performance indexes of On–Off and PID controls are calculated by the sensor errors, as shown in Figure 3. However, instead of sensor errors, the Harris indexes of the optimized settings and predictive controls are determined by the predictive errors, as shown in Equations (8) and (11). The collected prediction or forecast errors of AI-assisted HVAC controls in Table 1 are shown in Figure 4.
For the On–Off control variables of V 1 and Var [ y ( t + 1 ) ] , both are directly proportional to any sensor errors. Therefore, the calculated H is equal to one, and it becomes the comparison reference. For PID control, when the damping ratio is located in a lower damping ratio range from 0.5 to 1.5, the Var [ y ( t + 1 ) ] is able to reduce sensor errors by up to 30%, which will in turn enhance the H index value. Due to the reduction of the steady-state error by the integral (KI) control, a PID control has a better control ability than that of an On–Off control system, when the damping ratio is located within normal to lower value ranges. For higher damping ratio systems, the initial stage V 1 , the final stage Var [ y ( t + 1 ) ] , and the NHI value of the PID control will fluctuate due to variations of the proportional (KP) and differential (KD) control within a range of [0.2–0.69]. For AI-assisted HVAC control, the Var [ y ( t + 1 ) ] is estimated from the sensor output S(t+1), and the assumption is that the NHI is equal to one, as illustrated in Equations (12) and (13). However, the prediction or forecast errors of the AI controls fluctuate at certain ranges and cause variations of the NHI. This occurs particularly when the AI control utilizes human behavior algorithms or thermal comfort prediction algorithms, and the NHI is even lower than that of the PID control. The NHIs of On–Off, PID, and AI-assisted HVAC controls are shown in Figure 5.
The NHI is utilized to evaluate the performance of the control tools, and especially focuses on the energy-saving percentages, because of its capability to estimate the performance of linear and non-linear control systems. In Table 1, there are only 24 cases [11,12,14,19,21,44,50,57,58,62,63,72,73,83,84,92,93,94,97,98,101,103,105] that have references to the energy-saving percentages of AI-assisted HVAC controls. The average energy saving percentages of these 24 cases are shown in Figure 6, and a maximum energy savings of 41% is achieved by decision making through the MAS and CBR tools.
In Figure 6, the average energy savings percentage when using AI-assisted HVAC control is 14.02%. Of the 24 cases, 83% were comprised of On–Off control, and 17% were comprised of PID control. Based on the NHI, the estimated average energy savings percentage, variations in energy savings, and the maximum energy savings of AI-assisted HVAC control are 14.4%, 22.32%, and 44.04%, respectively. Comparing these results with the experimental data of 14.02%, 24.52%, and 41.0% in Figure 6, the errors are 3%, 9%, and 7%, respectively.

5. Conclusions

The presented NHI in this research can be used to evaluate the performance of AI-assisted HVAC control effectively, especially for non-linear control systems assisted by the optimized setting with CBR or KBS tools, or predictive control with the distributed AI and fuzzy algorithm. In order to calculate the NHI, the following hypotheses are made:
(1)
If the prediction/forecast accuracy could reach 3.5%, which approaches the thresholds of weather forecast accuracy and the accuracies of several types of sensors, including the thermistor, chip type temperature sensor, and humidity sensor, the performance of AI-assisted HVAC control will be enhanced. When compared with the On–Off and PID control strategies, the performance of the AI-assisted HVAC control had an increase of 57.0% and 44.64%, respectively. The increased energy saving percentages are above the average, and even above the maximum energy savings that were found in any of the published articles from 1997 to 2018.
(2)
In this study, the lower accuracy of the prediction tools and the resulting poor energy savings of HVAC systems are hypothesized. This hypothesis is from the collected articles, and forms the qualitative research in this paper. In the future, based on the hypothesis, the performance improvement of AI-assisted HVAC control will depend on the prediction accuracy of the sensors, which will be evidenced through the numerical simulation in Part 2 and the confirming experiments in Part 3.
(3)
The existing sensors are designed for accurate sensing, but not for accurate prediction, and this causes an unmet demand of the sensors. Improved sensors for AI-assisted HVAC controls should be able to provide the ability of more accurate prediction. Based on Bayes’ theorem, accurate prediction depends on the conditional probability. The priori probability can be utilized to determine the posterior possibility, and the consistent prediction can be achieved by aggregation. The priori information notice (PIN) design for sensors are provided in this study to decrease the prediction errors to as low as 3.5% or less. The details of the PIN sensor will be discussed in Part 2 of the serial research.

Author Contributions

D.L. initiated the idea, provided the draft, and completed the theoretical calculation. C.-C.C. completed the writing, translation, and revision of the paper.

Funding

This research was funded by Ministry of Science and Technology, R.O.C. through the contract MOST 106-2622-E-027-025-CC2 and 107-2622-E-027-001-CC2, and the industrial cooperating project between the National Taipei University of Technology (NTUT) and Hitachi Taiwan Company.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Shukla, A.; Sharma, A. Sustainability through Energy-Efficient Buildings; CRC Press: Boca Raton, FL, USA, 2018; ISBN 9781138066755. [Google Scholar]
  2. Martinopoulos, G.; Serasidou, A.; Antoniadou, P.; Papadopoulos, A.M. Building Integrated Shading and Building Applied Photovoltaic System Assessment in the Energy Performance and Thermal Comfort of Office Buildings. Sustainability 2018, 10, 4670. [Google Scholar] [CrossRef]
  3. Martinopoulos, G.; Papakostas, K.T.; Papadopoulos, A.M. A comparative review of heating systems in EU countries, based on efficiency and fuel cost. Renew. Sustain. Energy Rev. 2018, 90, 687–699. [Google Scholar] [CrossRef]
  4. Yang, L.; Yan, H.; Lam, J.C. Thermal comfort and building energy consumption implications—A review. Appl. Energy 2014, 115, 164–173. [Google Scholar] [CrossRef]
  5. Belic, F.; Hocenski, Z.; Sliskovic, D. HVAC Control Methods—A review. In Proceedings of the 19th International Conference on System Theory, Control and Computing (ICSTCC), Cheile Gradistei, Romania, 14–16 October 2015; pp. 679–686. [Google Scholar]
  6. WikipediaArtificial Intelligence. Available online: https://en.wikipedia.org/wiki/Artificial_intelligence_1 (accessed on 6 November 2018).
  7. Swartz, M.K. A look back at research synthesis. J. Pediatr. Heal. Care 2010, 24, 355. [Google Scholar] [CrossRef] [PubMed]
  8. Lee, D.; Cheng, C.-C. Energy savings by energy management systems: A review. Renew. Sustain. Energy Rev. 2016, 56, 760–777. [Google Scholar] [CrossRef]
  9. Chen, S.H.; Jakeman, A.J.; Norton, J.P. Artificial Intelligence techniques: An introduction to their use for modelling environmental systems. Math. Comput. Simul. 2008, 78, 379–400. [Google Scholar] [CrossRef]
  10. Bann, J.J.; Irisarri, G.D.; Mokhtari, S.; Kirschen, D.S.; Miller, B.N. Integrating AI applications in an energy management system. IEEE Expert 1997, 12, 53–59. [Google Scholar] [CrossRef]
  11. Clark, G.; Mehta, P. Artificial intelligence and networking in integrated building management systems. Autom. Constr. 1997, 6, 481–498. [Google Scholar] [CrossRef]
  12. Sigrimis, N.; Anastasiou, A.; Vogli, V. An open system for the management and control of greenhouses. In Proceedings of the IFAC Proceedings Volumes; Elsevier: Amsterdam, The Netherlands, 1998; Volume 31, pp. 67–72. [Google Scholar]
  13. Lara-Rosano, F.; Valverde, N.K. Knowledge-based systems for energy conservation programs. Expert Syst. Appl. 1998, 14, 25–35. [Google Scholar] [CrossRef]
  14. Wang, S.; Jin, X. Model-based optimal control of VAV air-conditioning system using genetic algorithm. Build. Environ. 2000, 35, 471–487. [Google Scholar] [CrossRef]
  15. Kalogirou, S.; Florides, G.; Neocleous, C.; Schizas, C. Estimation of daily heating and cooling loads using artificial Neural Networks. In Proceedings of the CLIMA 2000 International Conference, Naples, Italy, 15–18 September 2001; pp. 1–11. [Google Scholar]
  16. Kalogirou, S.A. Artificial neural networks in renewable energy systems applications: A review. Renew. Sustain. Energy Rev. 2001, 5, 373–401. [Google Scholar] [CrossRef]
  17. Kummert, M.; André, P.; Nicolas, J. Optimal heating control in a passive solar commercial building. Sol. Energy 2000, 69, 103–116. [Google Scholar] [CrossRef]
  18. Intille, S.S. Designing a home of the future. IEEE Pervasive Comput. 2002, 1, 76–82. [Google Scholar] [CrossRef]
  19. Mihalakakou, G.; Santamouris, M.; Tsangrassoulis, A. On the energy consumption in residential buildings. Energy Build. 2002, 34, 727–736. [Google Scholar] [CrossRef]
  20. Penya, Y.K. Last-generation applied artificial intelligence for energy management in building automation. In Proceedings of the IFAC Proceedings Volumes; Elsevier: Amsterdam, The Netherlands, 2003; Volume 36, pp. 73–77. [Google Scholar]
  21. Kolokotsa, D. Comparison of the performance of fuzzy controllers for the management of the indoor environment. Build. Environ. 2003, 38, 1439–1450. [Google Scholar] [CrossRef]
  22. Yang, I.H.; Yeo, M.S.; Kim, K.W. Application of artificial neural network to predict the optimal start time for heating system in building. Energy Convers. Manag. 2003, 44, 2791–2809. [Google Scholar] [CrossRef]
  23. Liao, G.C.; Tsao, T.P. Application of fuzzy neural networks and artificial intelligence for load forecasting. Electr. Power Syst. Res. 2004, 70, 237–244. [Google Scholar] [CrossRef]
  24. Yang, J.; Rivard, H.; Zmeureanu, R. On-line building energy prediction using adaptive artificial neural networks. Energy Build. 2005, 37, 1250–1259. [Google Scholar] [CrossRef]
  25. Wong, J.K.W.; Li, H.; Wang, S.W. Intelligent building research: A review. Autom. Constr. 2005, 14, 143–159. [Google Scholar] [CrossRef]
  26. Mozer, M. The adaptive house. In Proceedings of the the IEE Seminar on Intelligent Building Environments, Colchester, UK, 28 June 2005; pp. 39–79. [Google Scholar]
  27. González, P.A.; Zamarreño, J.M. Prediction of hourly energy consumption in buildings based on a feedback artificial neural network. Energy Build. 2005, 37, 595–601. [Google Scholar] [CrossRef]
  28. Dong, B.; Cao, C.; Lee, S.E. Applying support vector machines to predict building energy consumption in tropical region. Energy Build. 2005, 37, 545–553. [Google Scholar] [CrossRef]
  29. Yao, R.; Steemers, K. A method of formulating energy load profile for domestic buildings in the UK. Energy Build. 2005, 37, 663–671. [Google Scholar] [CrossRef]
  30. Abbas, S.R.; Arif, M. Electric load forecasting using support vector machines optimized by genetic algorithm. In Proceedings of the 2006 IEEE International Multitopic Conference, Islamabad, Pakistan, 23–24 December 2006; pp. 395–399. [Google Scholar]
  31. Hadjiski, M.; Sgurev, V.; Boishina, V. Multi agent intelligent control of centralized HVAC systems. In Proceedings of the IFAC Proceedings Volumes; IFAC: New York, NY, USA, 2006; pp. 195–200. [Google Scholar]
  32. Terziyska, M.; Todorov, Y.; Petrov, M. Fuzzy-Neural model predictive control of a building heating system. In Proceedings of the IFAC Proceedings Volumes; IFAC: New York, NY, USA, 2006; Volume 39, pp. 69–74. [Google Scholar]
  33. Kolokotsa, D.; Saridakis, G.; Pouliezos, A.; Stavrakakis, G.S. Design and installation of an advanced EIBTM fuzzy indoor comfort controller using MatlabTM. Energy Build. 2006, 38, 1084–1092. [Google Scholar] [CrossRef]
  34. Hou, Z.; Lian, Z.; Yao, Y.; Yuan, X. Cooling-load prediction by the combination of rough set theory and an artificial neural-network based on data-fusion technique. Appl. Energy 2006, 83, 1033–1046. [Google Scholar] [CrossRef]
  35. Subbaraj, P.; Rajasekaran, V. Short term hourly load forecasting using combined artificial Neural Networks. In Proceedings of the International Conference on Computational Intelligence and Multimedia Applications (ICCIMA 2007), Sivakasi, Tamil Nadu, India, 13–15 December 2007; pp. 155–163. [Google Scholar]
  36. Dalamagkidis, K.; Kolokotsa, D.; Kalaitzakis, K.; Stavrakakis, G.S. Reinforcement learning for energy conservation and comfort in buildings. Build. Environ. 2007, 42, 2686–2698. [Google Scholar] [CrossRef]
  37. Neto, A.H.; Fiorelli, F.A.S. Comparison between detailed model simulation and artificial neural network for forecasting building energy consumption. Energy Build. 2008, 40, 2169–2176. [Google Scholar] [CrossRef]
  38. Catalina, T.; Virgone, J.; Blanco, E. Development and validation of regression models to predict monthly heating demand for residential buildings. Energy Build. 2008, 40, 1825–1832. [Google Scholar] [CrossRef]
  39. Kato, K.; Sakawa, M.; Ishimaru, K.; Ushiro, S.; Shibano, T. Heat load prediction through recurrent neural network in district heating and cooling systems. In Proceedings of the 2008 IEEE International Conference on Systems, Man and Cybernetics, Singapore, 12–15 October 2008; pp. 1401–1406. [Google Scholar]
  40. Smith, B.A.; Hoogenboom, G.; McClendon, R.W. Artificial neural networks for automated year-round temperature prediction. Comput. Electron. Agric. 2009, 68, 52–61. [Google Scholar] [CrossRef]
  41. Gao, M.; Sun, F.; Zhou, S.; Shi, Y.; Zhao, Y.; Wang, N. Performance prediction of wet cooling tower using artificial neural network under cross-wind conditions. Int. J. Therm. Sci. 2009, 48, 583–589. [Google Scholar] [CrossRef]
  42. Huang, G.; Wang, S.; Xu, X. A robust model predictive control strategy for improving the control performance of air-conditioning systems. Energy Convers. Manag. 2009, 50, 2650–2658. [Google Scholar] [CrossRef]
  43. Kofler, M.J.; Kastner, W. A knowledge base for energy-efficient smart homes. In Proceedings of the 2010 IEEE International Energy Conference and Exhibition, Manama, Bahrain, 18–22 December 2010; pp. 85–90. [Google Scholar]
  44. Li, M.; Ren, Q. Optimization for the Chilled Water System of HVAC Systems in an Intelligent Building. In Proceedings of the 2010 International Conference on Computational and Information Sciences, Chengdu, China, 17–19 December 2010; pp. 889–891. [Google Scholar]
  45. Vale, Z.A.; Morais, H.; Khodr, H. Intelligent multi-player smart grid management considering distributed energy resources and demand response. In Proceedings of the IEEE PES General Meeting, PES 2010, Providence, RI, USA, 25–29 July 2010; pp. 1–7. [Google Scholar]
  46. Kolokotsa, D.; Saridakis, G.; Dalamagkidis, K.; Dolianitis, S.; Kaliakatsos, I. Development of an intelligent indoor environment and energy management system for greenhouses. Energy Convers. Manag. 2010, 51, 155–168. [Google Scholar] [CrossRef]
  47. Dombayci, Ö.A. The prediction of heating energy consumption in a model house by using artificial neural networks in Denizli-Turkey. Adv. Eng. Softw. 2010, 41, 141–147. [Google Scholar] [CrossRef]
  48. Girardin, L.; Marechal, F.; Dubuis, M.; Calame-Darbellay, N.; Favrat, D. EnerGis: A geographical information based system for the evaluation of integrated energy conversion systems in urban areas. Energy 2010, 35, 830–840. [Google Scholar] [CrossRef]
  49. Qela, B.; Mouftah, H. An adaptable system for energy management in intelligent buildings. In Proceedings of the IEEE International Conference on Computational Intelligence for Measurement Systems and Applications Proceedings, Ottawa, ON, Canada, 19–21 September 2011; pp. 1–7. [Google Scholar]
  50. Paris, B.; Eynard, J.; Grieu, S.; Polit, M. Hybrid PID-fuzzy control scheme for managing energy resources in buildings. Appl. Soft Comput. 2011, 11, 5068–5080. [Google Scholar] [CrossRef] [Green Version]
  51. Kiran, T.R.; Rajput, S.P.S. An effectiveness model for an indirect evaporative cooling (IEC) system: Comparison of artificial neural networks (ANN), adaptive neuro-fuzzy inference system (ANFIS) and fuzzy inference system (FIS) approach. Appl. Soft Comput. 2011, 11, 3525–3533. [Google Scholar] [CrossRef]
  52. Moon, J.W.; Jung, S.K.; Kim, Y.; Han, S.H. Comparative study of artificial intelligence-based building thermal control methods—Application of fuzzy, adaptive neuro-fuzzy inference system, and artificial neural network. Appl. Therm. Eng. 2011, 31, 2422–2429. [Google Scholar] [CrossRef]
  53. Eynard, J.; Grieu, S.; Polit, M. Wavelet-based multi-resolution analysis and artificial neural networks for forecasting temperature and thermal power consumption. Eng. Appl. Artif. Intell. 2011, 24, 501–516. [Google Scholar] [CrossRef] [Green Version]
  54. Jahedi, G.; Ardehali, M.M. Genetic algorithm-based fuzzy-pid control methodologies for enhancement of energy efficiency of a dynamic energy system. Energy Convers. Manag. 2011, 52, 725–732. [Google Scholar] [CrossRef]
  55. Ahmed, A.; Korres, N.E.; Ploennigs, J.; Elhadi, H.; Menzel, K. Mining building performance data for energy-efficient operation. Adv. Eng. Inform. 2011, 25, 341–354. [Google Scholar] [CrossRef]
  56. Wan, K.K.W.; Li, D.H.W.; Liu, D.; Lam, J.C. Future trends of building heating and cooling loads and energy consumption in different climates. Build. Environ. 2011, 46, 223–234. [Google Scholar] [CrossRef]
  57. Kim, J.; Cho, W.-H.; Jeong, Y.; Song, O. Intelligent energy management system for smart offices. In Proceedings of the 2012 IEEE International Conference on Consumer Electronics (ICCE), Las Vegas, NV, USA, 13–16 January 2012; pp. 668–669. [Google Scholar]
  58. Byun, J.; Kim, Y.; Hwang, Z.; Park, S. An intelligent cloud-based energy management system using machine to machine communications in future energy environments. In Proceedings of the 2012 IEEE International Conference on Consumer Electronics (ICCE), Las Vegas, NV, USA, 13–16 January 2012; pp. 664–665. [Google Scholar]
  59. Huang, H.; Chen, L.; Mohammadzaheri, M.; Hu, E. A new zone temperature predictive modeling for energy saving in buildings. Procedia Eng. 2012, 49, 142–151. [Google Scholar] [CrossRef]
  60. Marvuglia, A.; Messineo, A. Using recurrent artificial neural networks to forecast household electricity consumption. Energy Procedia 2012, 14, 45–55. [Google Scholar] [CrossRef]
  61. Ferreira, P.M.; Silva, S.M.; Ruano, A.E. Model based predictive control of HVAC systems for human thermal comfort and energy consumption minimisation. IFAC Proc. Vol. 2012, 45, 236–241. [Google Scholar] [CrossRef]
  62. Klein, L.; Kwak, J.Y.; Kavulya, G.; Jazizadeh, F.; Becerik-Gerber, B.; Varakantham, P.; Tambe, M. Coordinating occupant behavior for building energy and comfort management using multi-agent systems. Autom. Constr. 2012, 22, 525–536. [Google Scholar] [CrossRef]
  63. Čongradac, V.; Kulić, F. Recognition of the importance of using artificial neural networks and genetic algorithms to optimize chiller operation. Energy Build. 2012, 47, 651–658. [Google Scholar] [CrossRef]
  64. Jahedi, G.; Ardehali, M.M. Wavelet based artificial neural network applied for energy efficiency enhancement of decoupled HVAC system. Energy Convers. Manag. 2012, 54, 47–56. [Google Scholar] [CrossRef]
  65. Yun, K.; Luck, R.; Mago, P.J.; Cho, H. Building hourly thermal load prediction using an indexed ARX model. Energy Build. 2012, 54, 225–233. [Google Scholar] [CrossRef]
  66. Wim, Z.; Timilehin, L.; Kennedy, A. Towards multi-agent systems in building automation and control for improved occupant comfort and energy efficiency—State of the art, challenges. In Proceedings of the 2013 Fourth International Conference on Intelligent Systems Design and Engineering Applications, Zhangjiajie, China, 6–7 November 2013; pp. 718–722. [Google Scholar]
  67. Ciabattoni, L.; Grisostomi, M.; Ippoliti, G.; Longhi, S. Neural networks based home energy management system in residential PV scenario. In Proceedings of the 2013 IEEE 39th Photovoltaic Specialists Conference, Tampa, FL, USA, 16–21 June 2013; pp. 1721–1726. [Google Scholar]
  68. Ciabattoni, L.; Ippoliti, G.; Benini, A.; Longhi, S.; Pirro, M. Design of a home energy management system by online neural networks. IFAC Proc. Vol. 2013, 46, 677–682. [Google Scholar] [CrossRef]
  69. Fernandes, F.; Morais, H.; Faria, P.; Vale, Z.; Ramos, C. SCADA house intelligent management for energy efficiency analysis in domestic consumers. In Proceedings of the 2013 IEEE PES Conference on Innovative Smart Grid Technologies, Sao Paulo, Brazil, 15–17 April 2013; pp. 1–8. [Google Scholar]
  70. Huang, D.; Thottan, M.; Feather, F. Designing customized energy services based on disaggregation of heating usage. In Proceedings of the 2013 IEEE PES Innovative Smart Grid Technologies Conference, Sao Paulo, Brazil, 15–17 April 2013; pp. 1–6. [Google Scholar]
  71. Milenkovic, M.; Amft, O. Recognizing energy-related activities using sensors commonly installed in office buildings. Procedia Comput. Sci. 2013, 19, 669–677. [Google Scholar] [CrossRef]
  72. Yang, R.; Wang, L. Development of multi-agent system for building energy and comfort management based on occupant behaviors. Energy Build. 2013, 56, 1–7. [Google Scholar] [CrossRef]
  73. Nguyen, T.A.; Aiello, M. Energy intelligent buildings based on user activity: A survey. Energy Build. 2013, 56, 244–257. [Google Scholar] [CrossRef] [Green Version]
  74. Arabali, A.; Ghofrani, M.; Etezadi-Amoli, M.; Fadali, M.S.; Baghzouz, Y. Genetic-algorithm-based optimization approach for energy management. IEEE Trans. Power Deliv. 2013, 28, 162–170. [Google Scholar] [CrossRef]
  75. Collotta, M.; Messineo, A.; Nicolosi, G.; Pau, G. A dynamic fuzzy controller to meet thermal comfort by using neural network forecasted parameters as the input. Energies 2014, 7, 4727–4756. [Google Scholar] [CrossRef]
  76. Mena, R.; Rodríguez, F.; Castilla, M.; Arahal, M.R. A prediction model based on neural networks for the energy consumption of a bioclimatic building. Energy Build. 2014, 82, 142–155. [Google Scholar] [CrossRef]
  77. Paliwal, P.; Patidar, N.P.; Nema, R.K. Determination of reliability constrained optimal resource mix for an autonomous hybrid power system using Particle Swarm Optimization. Renew. Energy 2014, 63, 194–204. [Google Scholar] [CrossRef]
  78. Monfet, D.; Corsi, M.; Choinière, D.; Arkhipova, E. Development of an energy prediction tool for commercial buildings using case-based reasoning. Energy Build. 2014, 81, 152–160. [Google Scholar] [CrossRef]
  79. Chou, J.S.; Bui, D.K. Modeling heating and cooling loads by artificial intelligence for energy-efficient building design. Energy Build. 2014, 82, 437–446. [Google Scholar] [CrossRef]
  80. El-Zonkoly, A. Intelligent energy management of optimally located renewable energy systems incorporating PHEV. Energy Convers. Manag. 2014, 84, 427–435. [Google Scholar] [CrossRef]
  81. Rodrigues, F.; Cardeira, C.; Calado, J.M.F. The daily and hourly energy consumption and load forecasting using artificial neural network method: A case study using a set of 93 households in Portugal. Energy Procedia 2014, 62, 220–229. [Google Scholar] [CrossRef]
  82. Fumo, N. A review on the basics of building energy estimation. Renew. Sustain. Energy Rev. 2014, 31, 53–60. [Google Scholar] [CrossRef]
  83. Petri, I.; Li, H.; Rezgui, Y.; Yang, C.; Yuce, B.; Jayan, B. A modular optimisation model for reducing energy consumption in large scale building facilities. Renew. Sustain. Energy Rev. 2014, 38, 990–1002. [Google Scholar] [CrossRef]
  84. Stavropoulos, T.G.; Kontopoulos, E.; Bassiliades, N.; Argyriou, J.; Bikakis, A.; Vrakas, D.; Vlahavas, I. Rule-based approaches for energy savings in an ambient intelligence environment. Pervasive Mob. Comput. 2015, 19, 1–23. [Google Scholar] [CrossRef]
  85. Macedo, M.N.Q.; Galo, J.J.M.; De Almeida, L.A.L.; de C. Lima, A.C. Demand side management using artificial neural networks in a smart grid environment. Renew. Sustain. Energy Rev. 2015, 41, 128–133. [Google Scholar] [CrossRef]
  86. Moon, J.W. Comparative performance analysis of the artificial-intelligence-based thermal control algorithms for the double-skin building. Appl. Therm. Eng. 2015, 91, 334–344. [Google Scholar] [CrossRef]
  87. Lazrak, A.; Leconte, A.; Chèze, D.; Fraisse, G.; Papillon, P.; Souyri, B. Numerical and experimental results of a novel and generic methodology for energy performance evaluation of thermal systems using renewable energies. Appl. Energy 2015, 158, 142–156. [Google Scholar] [CrossRef]
  88. El-Baz, W.; Tzscheutschler, P. Short-term smart learning electrical load prediction algorithm for home energy management systems. Appl. Energy 2015, 147, 10–19. [Google Scholar] [CrossRef]
  89. Ortega, J.L.G.; Han, L.; Whittacker, N.; Bowring, N. A machine-learning based approach to model user occupancy and activity patterns for energy saving in buildings. In Proceedings of the 2015 Science and Information Conference, London, UK, 28–30 July 2015; pp. 474–482. [Google Scholar]
  90. Cai, H.; Huang, J.H.; Xie, Z.J.; Littler, T. Modelling the benefits of smart energy scheduling in micro-grids. In Proceedings of the IEEE Power and Energy Society General Meeting, Denver, CO, USA, 26–30 July 2015; pp. 1–5. [Google Scholar]
  91. Olatomiwa, L.; Mekhilef, S.; Ismail, M.S.; Moghavvemi, M. Energy management strategies in hybrid renewable energy systems: A review. Renew. Sustain. Energy Rev. 2016, 62, 821–835. [Google Scholar] [CrossRef]
  92. Salakij, S.; Yu, N.; Paolucci, S.; Antsaklis, P. Model-Based Predictive Control for building energy management. I: Energy modeling and optimal control. Energy Build. 2016, 133, 345–358. [Google Scholar] [CrossRef]
  93. Shaikh, P.H.; Nor, N.B.M.; Nallagownden, P.; Elamvazuthi, I.; Ibrahim, T. Intelligent multi-objective control and management for smart energy efficient buildings. Electr. Power Energy Syst. 2016, 74, 403–409. [Google Scholar] [CrossRef]
  94. Aki, H.; Wakui, T.; Yokoyama, R. Development of a domestic hot water demand prediction model based on a bottom-up approach for residential energy management systems. Appl. Therm. Eng. 2016, 108, 697–708. [Google Scholar] [CrossRef]
  95. Jiang, P.; Ma, X. A hybrid forecasting approach applied in the electrical power system based on data preprocessing, optimization and artificial intelligence algorithms. Appl. Math. Model. 2016, 40, 10631–10649. [Google Scholar] [CrossRef]
  96. Brøgger, M.; Wittchen, K.B. Estimating the energy-saving potential in national building stocks—A methodology review. Renew. Sustain. Energy Rev. 2018, 82, 1489–1496. [Google Scholar] [CrossRef]
  97. Wei, T.; Wang, Y.; Zhu, Q. Deep Reinforcement Learning for Building HVAC Control. In Proceedings of the 2017 54th ACM/EDAC/IEEE Design Automation Conference (DAC), Austin, TX, USA, 18–22 June 2017; pp. 1–6. [Google Scholar]
  98. Wang, Y.; Velswamy, K.; Huang, B. A long-short term memory recurrent neural network based reinforcement learning controller for office heating ventilation and air conditioning systems. Processes 2017, 5, 1–18. [Google Scholar]
  99. DiSanto, K.G.; DiSanto, S.G.; Monaro, R.M.; Saidel, M.A. Active demand side management for households in smart grids using optimization and artificial intelligence. Meas. J. Int. Meas. Confed. 2018, 115, 152–161. [Google Scholar] [CrossRef]
  100. Ruiz, L.G.B.; Rueda, R.; Cuéllar, M.P.; Pegalajar, M.C. Energy consumption forecasting based on Elman neural networks with evolutive optimization. Expert Syst. Appl. 2018, 92, 380–389. [Google Scholar] [CrossRef]
  101. Godina, R.; Rodrigues, E.M.G.; Pouresmaeil, E.; Matias, J.C.O.; Catal, J.P.S. Model predictive control home energy management and optimization strategy with demand response. Appl. Sci. 2018, 8, 408. [Google Scholar] [CrossRef]
  102. Behrooz, F.; Mariun, N.; Marhaban, M.H.; Radzi, M.A.M.; Ramli, A.R. Review of control techniques for HVAC systems—nonlinearity approaches based on Fuzzy cognitive maps. Energies 2018, 11, 495. [Google Scholar] [CrossRef]
  103. Serale, G.; Fiorentini, M.; Capozzoli, A.; Bernardini, D.; Bemporad, A. Model predictive control (MPC) for enhancing building and HVAC system energy efficiency: Problem formulation, applications and opportunities. Energies 2018, 11, 631. [Google Scholar] [CrossRef]
  104. Zhang, X.; Wang, R.; Bao, J. A novel distributed economic model predictive control approach for building air-conditioning systems in microgrids. Mathematics 2018, 6, 60. [Google Scholar] [CrossRef]
  105. González-Briones, A.; Prieto, J.; Prieta, F.D.L.; Herrera-Viedma, E.; Corchado, J.M. Energy optimization using a case-based reasoning strategy. Sensors 2018, 18, 865. [Google Scholar] [CrossRef] [PubMed]
  106. ASHRAE. Fundamentals of HVAC Control Systems; I-P; Elsevier Science: Amsterdam, The Netherlands, 2011; ISBN 9781933742915. [Google Scholar]
  107. Harris, T.J. Assessment of Control Loop Performance. Can. J. Chem. Eng. 1989, 67, 856–861. [Google Scholar] [CrossRef]
  108. Harris, T.J.; Boudreau, F.; Macgregor, J.F. Performance assessment of multivariable feedback controllers. Automatica 1996, 32, 1505–1518. [Google Scholar] [CrossRef]
  109. Wang, Z.; Chen, J. Feedforward and feedback control performance assessment for nonlinear systems. Abstr. Appl. Anal. 2014, 2014, 1–12. [Google Scholar] [CrossRef]
  110. Ambi-LabsAI-Enhanced Air Conditioning Comfort. Available online: https://www.ambiclimate.com/en/features/ (accessed on 5 November 2018).
Figure 1. Typical HVAC controls for residential or commercial buildings.
Figure 1. Typical HVAC controls for residential or commercial buildings.
Sensors 19 01131 g001
Figure 2. AI-assisted HVAC controls for residential and commercial buildings.
Figure 2. AI-assisted HVAC controls for residential and commercial buildings.
Sensors 19 01131 g002
Figure 3. Sensor errors with respect to different type of sensors employed by AI-assisted HVAC control.
Figure 3. Sensor errors with respect to different type of sensors employed by AI-assisted HVAC control.
Sensors 19 01131 g003
Figure 4. Prediction or forecast errors of AI-assisted HVAC control.
Figure 4. Prediction or forecast errors of AI-assisted HVAC control.
Sensors 19 01131 g004
Figure 5. Normalized Harris index (NHI) of different kinds of HVAC controls and the expected performance improvements for energy savings.
Figure 5. Normalized Harris index (NHI) of different kinds of HVAC controls and the expected performance improvements for energy savings.
Sensors 19 01131 g005
Figure 6. The average energy savings of the 24 cases and the maximum energy savings achieved by AI-assisted HVAC control.
Figure 6. The average energy savings of the 24 cases and the maximum energy savings achieved by AI-assisted HVAC control.
Sensors 19 01131 g006
Table 1. Artificial intelligence (AI) developments for heating, ventilation, and air conditioning (HVAC) systems and the obtained key results.
Table 1. Artificial intelligence (AI) developments for heating, ventilation, and air conditioning (HVAC) systems and the obtained key results.
YearHVAC SystemAI DevelopmentKey ResultsRef.
1997Case #1. A medium-sized utility from the Midwestern United States (US); Case #2. A large utility from the Midwestern US Operation decision environment (ODE) architectureModel-based control and fault diagnosis[10]
1997HVAC system for occupant comfort and efficient running costsKnowledge-based system (KBS) for predictive controlBased on pre-programmed load priorities, 20% electricity savings was achieved [11]
1998MACQU software applied to a greenhouseNative fuzzy KBS at the supervisory levelControl loop optimization and 12% energy savings[12]
1998Expert system in commercial buildingsKBS for energy conservation programsCost savings up to 60%[13]
2000HVAC system with variable air volume (VAV) coils and constant air volume (CAV) coilsGenetic algorithm (GA), cost estimation and model-based predictorSimulation results show that the overall energy savings were 0.1%, 0.2%, 1.8% and 1.9% less than the original status [14]
2001Prediction of heating and cooling loads at residential buildingsStatic neuro network (SNN) development for predictionLoad curve fitting with an R-square value up to 0.9887
Prediction error ranges from 2.5% to 8.7%
[15]
2001Use of artificial neuro networks (ANNs) in solar radiation and wind speed prediction, photovoltaic systems, building services, and load forecasting and predictionANNs for modeling a solar steam generator, modeling of solar domestic water heating systems, and forecasting the building thermal loadsR-square value of load fitting ranges from 0.9733 to 0.9940.
The prediction errors are within 1.9–5.5%.
[16]
2001Optimal heating control of a passive solar commercial buildingSmart heating controller with the cost function can combine comfort level and energy consumptionEnergy savings of maintaining or improving a thermal comfort are about 9%[17]
2002House_n demonstration at Massachusetts Institute of TechnologySaving energy, maintaining air quality and thermal comfort using data analysisEnergy savings are about 14%[18]
2002SNN for analyzing energy consumption in residential buildingsModel-based control for energy savingsEnergy savings range from 5% to 15%[19]
2003Building automation and energy management using AIDistributed AI development for demand-side management (DSM) and scheduling energy consumption according to energy tariff DSM-abled devices can save up to 40% on energy costs based on 24-h analysis[20]
2003Fuzzy controller for the management of an indoor environmentFive fuzzy controllers include fuzzy P, fuzzy proportional–integral–differential (PID), fuzzy PI, fuzzy PD and adaptive fuzzy PDWhile maintaining predicted mean vote (PMV) within 0–0.1 and indoor CO2 ppm increased less than 20 ppm, fuzzy P controller had the best performance, heating and cooling energy can be reduced up to 20.1%.[21]
2003ANNs in the optimal operation of HVAC equipmentANN was developed for predicting the optimal start times of a heating system in a buildingIn 27 instances, a clear linear relationship between prediction and real data was shown by the R-square values ranging from 0.968 to 0.996.[22]
2004ANNs for load forecasting of Taiwan power systemAn integrated, evolving fuzzy neuro network and simulated annealing (AIFNN) developed for load forecastingCompared with traditional ANNs, AIFNN can reduce prediction errors up to 3%[23]
2005On-line building energy consumption prediction through adaptive ANN Adaptive ANN model fits the unexpected pattern changes of the incoming data of chillers at a Laval building operated from 7:30 to 23:00, Monday to FridayThe prediction accuracy is measured by the coefficient of variation (CV) and the root mean square error (RMSE). For the Laval building case, the CV is 0.20 and the RMSE = 27.0 kW. With respect to the total power consumption ~180 kw, the prediction error is 15%.[24]
2005Energy forecast of intelligent buildings located at US and United Kingdom (UK)Increased return on investment (ROI) by using fuzzy multi-criteria decision-making method (DMM) 3% cost savings can be achieved with AI-assisted decision making.[25]
2005Adaptive control of home environment (ACHE) at ColoradoDistributed AI development and integrated with sensorsSensors of electrical consumption with ANN adapt to the habits of inhabitants[26]
2005Predicting hourly energy consumption in buildingsANN development for predicting short-term energy consumption and feedback controlFeedback ANN for highly efficient energy supply[27]
2005Prediction of building energy consumption in tropical regionsSupport vector machine (SVM) development for accurate prediction based on weather forecast dataSummertime energy consumption can be accurately predicted within an error rate of less than 4.5%[28]
2005Prediction of daily heating loads of UK buildingsSNN development for daily heating load predictions based on one year of sensor dataPrediction error rate of less than 3.0%[29]
2006Electric load forecasting through the use of data from the East-Slovakia Power Distribution CompanySVM model development for the forecasting of a test set in January 1999 Mean average percent error (MAPE) rate of 1.93% [30]
2006Centralized HVAC systemMulti-agent structure development for thermal comfort control Control accuracy of around 89% to 92.5%. That indicates a 7.5–11% prediction error rate related to occupants’ thermal comfort levels.[31]
2006Predictive control system development for a building heating systemFuzzy + proportional–integral–differential (PID) controller development for improving control performanceFor a heater control, temperature increase times can be reduced from 12.7 sec to 4.3 sec; the settling time can be reduced from 16.3 sec to 6.9 sec; overshooting can be reduced to 0%.[32]
2006Indoor thermal comfort controller developmentFuzzy logic controller development The measuring period was from 15 September 2004 until 17 September 2004 at a 2-sec sample rate. The indoor air quality was kept between 600–800 ppm. The predicted mean vote (PMV) fluctuates around one[33]
2006Cooling prediction of an existing HVAC system in ChinaCombination of rough set (RS) theory and ANN for cooling load predictionThe HVAC system has 11 air-handling units (AHU) and operates 24 h a day. The prediction error rate of cooling energy during a 24-h period in summer time ranged from 3.45% to 9.27%[34]
2007Hourly load demand forecastCombining evolutionary program (EP) and particle swarm optimization (PSO), combined with an artificial neural network (CANN) was developed for short-term hourly load forecastingHourly loads of a 6000-kW utility were predicted during the first week of December 2005. Using the best trained CANN tool, MAPE can reach 2.24% to 3.25%.[35]
2007Achieving thermal comfort in two simulated buildings Development of a linear reinforcement learning controller instead of using a traditional on/off controllerController development for saving energy while maintaining thermal comfort; over a period of four years, the annual energy consumption increased marginally from 4.77 MWh to 4.85 MWh. However, the dissatisfaction index, predicted percentage of dissatisfied (PPD), was decreased from 13.4% to 12.1%.[36]
2008Forecasting building energy consumption based on simulation models and ANN Comparison between detailed model simulations and ANN for forecasting building energy consumption Difference between the detailed model and ANN is less than 2.1% [37]
2008Predicting monthly heating loads of residential buildings Regression model development for prediction MAPE ranges from 2.3% to 5.5% [38]
2008Heat load prediction of a district’s heating and cooling system Recurrent neural network (RNN) development for heating load prediction During a four-month period in winter, daily prediction errors rates ranged from 5.3% to 15.5%[39]
2009Year-round temperature prediction of the southeastern United States Ward-type ANNs development for the prediction of air temperature during the entire year based on near real-time data Using detailed weather data collected by the Georgia Automated Environmental Monitoring Network, ANNs were trained to provide prediction throughout the year. The prediction mean absolute error rate (MAE) ranged from 0.516 °C to 1.873 °C[40]
2009Measuring the prediction performance of a wet cooling tower ANN development for the prediction of cooling tower approaching temperatures The prediction means square error rate (MSE) of around 0.064 °C[41]
2009Control performance improvement of a typical AHU variable air volume (VAV) air-conditioning systemModel-based predictive control (MPC) development based on a first-order plus time-delay modelFor an air-conditioned area of about 1200 m2 in Hong Kong, cooling air can track the set point with an error rate of around 0.13 °C[42]
2010KBS applications in smart homesAutonomous caretaker to create an environmentally-friendly and comfortable ambienceSmart home ontology has the potential to save on labor costs[43]
2010A chiller system in an intelligent buildingOptimization by RNN7.4% energy savings[44]
2010Intelligent multi-player grid management for reducing energy costEvolutionary computation development for cost saving1 kwh of energy cost can be reduced from 0.773 € to 0.313 €.
Cost saving is around 62.4%
[45]
2010Fuzzy logic controller for greenhouse applicationsFuzzy controller design for universal purposeThe controller can be used in any cultivation with different environmental variables’ set points.[46]
2010Prediction of heating energy consumption in a model house at Denizli, TurkeyModel-based predictionPrediction errors range from 2.3% to 5.5%[47]
2010Prediction of annual heating and cooling loads for 80 residential buildingsModel-based predictionPrediction errors range from 7.5% to 22.4%[48]
2011Adaptive learning system at intelligent buildingsSmart scheduling control based on deep learning1.33 °C shift close to occupants’ custom settings[49]
2011Hybrid controller for energy management at a simulated one-floor building of 128 m2, with a bay window at the University of Perpignan Via Domitia, south of FranceFuzzy-PID schema development for model predictive control (MPC)While maintaining thermal comfort, 1 °C exceeding the set point can be controlled to save 6% energy, but occupants will feel warm. PMV can be ensured by an 0.2 °C temperature increment. The energy saving is less than 0.3%[50]
2011Predicting air outlet temperature of an indirect evaporative cooling systemSoft computing tools include the fuzzy interference system (FIS), ANN, and adaptive neuro fuzzy inference (ANFIS)ANN trained by the Levenbergy–Marquardt algorithm provides the best prediction performance. R2 value can be as high as 0.9999. Predicted temperature deviation is less than 1 °C, and the error ranges from 1.1% to 3.2%[51]
2011AI-based thermal control method for a typical US single family houseANFIS development and the control performance comparison with ANNANFIS control can save 0.3% more energy than the ANN in the winter. In the summertime, ANFIS can save 0.7% more energy[52]
2011Predicting temperature and power consumption of a district boilerWavelet-based ANN development for accurate predictionPrediction errors range from 4.17% to 9.01%[53]
2011Controller development for a heating and cooling systemGA-based fuzzy PID controller developmentLowering equipment initial and operating cost up to 20%[54]
2011Mining building performance data for energy-efficient operationEnergy-efficient mining model development for predicting environmental variablesThe model is used to predict the environmental variables of a 4500 m2 south-facing low-energy building consisting of 70 rooms. The confidence of room temperature prediction is 84.63%; that of radiant temperature prediction is 90.34%; the CO2 concentration prediction confidence is 64.68%; and that of relative humidity is 86.76%[55]
2011Regression model development for predicting heating and cooling loads of buildings in different climatesPrincipal components analysis (PCA) development for predicting outdoor temperaturePrediction errors range from 5.5% to 7.9%[56]
2012Intelligent energy management system (EMS) for smart officesDistributed AI development for optimized scheduling control of office equipment12% energy saving[57]
2012Cloud-based EMS and future energy environmentDistributed AI and machine to machine (M2M) communication development22.5% energy saving[58]
2012Zone temperature prediction in buildingsPredicting indoor temperature by traditional thermal dynamic model, ANN, GA, and fuzzy logic approachesMAE of prediction by traditional model is 0.422 °C; ANN is 0.42 °C; GA is 0.753 °C, and fuzzy logic is 0.741 °C[59]
2012Forecasting household electricity consumptionRNN development for the short-term (one hour ahead) forecasting of the household electric consumptionThe house is located in a suburban area in the neighbors of the town of Palermo, Italy. The prediction errors range from 1.5% to 4.6%[60]
2012Model-based control of a HVAC system in a single zone of a buildingMulti-objective GA development for predicting air temperature and relative humidityMAE of temperature prediction is 0.1–0.6 °C. Relative humidity is 0.5–3.0%[61]
2012Coordinating occupants’ behaviors for building energy and comfort managementDistributed AI development to achieve multi-agent comfort managementReducing 12% energy consumption while keeping thermal comfort with the variation less than 0.5%[62]
2012Optimization of chiller operation at the office building of the company Imel in New BelgradeGA development for the optimization of chiller operation2% energy saving during warmest summer days, and up to 13% during the transition period at lower average external temperatures[63]
2012Energy efficiency enhancement of a decoupled HVAC systemWavelet-based ANN development for optimization of scheduling controlIn mid-season operation, daily operation cost can be saved from 5.88% to 11.16%[64]
2012Hourly thermal load prediction Autoregressive with exogenous terms (ARX) model development for thermal load predictionMAPE ranges from 9.5% to 17.5%[65]
2013Multi-agent system (MAS) application in a commercial building owned by Xerox Palo Alto Research Center (PARC) in the USMAS development for constructing a building comfort and energy management system (BECMS)Constructing a hierarchical function decomposition to provide user solution[66]
2013Three typical residential buildings with 3.3-kWp photovoltaic (PV) plant located at Ripatransone (AP), ItalyRadial basic function (RBF) network development for monitoring home loads, detecting and forecasting PV energy production and home consumptions, informs and influences users on their energy choicesMAPE of home load prediction for next three hours is 9.70%, eight hours is 12.20%, and 18 h is 16.30%.
MAPE of PV energy production for the next three hours is 7.70%, eight hours is 9.30%, and 18 h is 11.80%.
[67]
[68]
2013Smart homes in a smart gridSupervisory control and data acquisition + house intelligent management system = SHIM for charge and discharge of the electric or plug-in hybrid vehicles, and the participation in demand response (DR) programsConsidering the energy consumption data of a Portuguese house over 30 days in June 2012, the energy cost can be saved up to 12.1% [69]
2013Designing customized energy service based on disaggregation of heating usageEstimating heat usage by hidden Markov model (HMM)Heating usage can be predicted, and the errors range from 4.64% to 8.74%[70]
2013Using sensors commonly installed in office buildings to recognize energy-related activitiesLayered HMM development for recognizing occupants’ behaviorsPeople counting can have the accuracy of 87% in the single-person room and 78% in the multi-person room. The away and present activity can be identified with the accuracy of 97.7% in the single-person room, but only 61% accuracy can be achieved in the multi-person room. The prediction of other activities has accuracy ranges from 98.7% to 61%[71]
2013MAS for BECMS based on occupants’ behaviorsUser-oriented control based on behavior predictionIndoor thermal comfort is considered to be highly satisfactory to occupants while maintaining a PMV of around 0.6065[72]
2013Predictive control of vapor compression cycle systemMPC development for multi-variable controlEnergy saving by MPC can reach 25.31%. With the prediction by AI, energy cost can be reduced up to 28.52%. Comparing the traditional prediction by linear regression, energy-saving performance is improved by 65.53% and cost-saving can be increased up to 63%[72]
2013A survey of energy-intelligent buildings based on user activityMAS for gathering real-time occupancy information, predicting occupancy patterns and decision making Energy saving of HVAC equipment can reach 12%[73]
2013Optimal energy management by load shiftGA development for load shift control35% load shift is possible under a reasonable storage capacity[74]
2014Dynamic fuzzy controller development to meet thermal comfortANN performs indoor temperature forecasts to deed a fuzzy logic controllerThermal comfort is very subjective, and may vary even in the same object [75]
2014Electricity demand prediction of the center of investigation on energy solar (CIESOL) bioclimatic buildingShort-term predictive neural network model development With a short-term prediction horizon equal to 60 min, the mean error is 11.48%[76]
2014An autonomous hybrid power systemPSO development for predicting weather conditionsTechno-socio-economic criterion for the optimum mix of renewable energy resources[77]
2014Energy consumption prediction of a commercial building that has a total floor area of 34,568 m2 and is located in Montreal, QuebecCase-based reasoning (CBR) model development for predicting following three-hour weather conditions and indoor thermal loadsDuring occupancy, 07:00–18:00, the coefficient of variation of the root mean square error (CV-RMSE) is below 13.2%, the normalized mean bias error (NMBE) is below 5.8%, and the root mean square error (RMSE) is below 14 kW[78]
2014Simulated 12 building types have the same volume, ~771.75 m3SVR + ANN development for predicting heating and cooling loads with eight input parameters Prediction error is less than 4%. Compared with the traditional model prediction, the SVR + ANN model can improve the prediction error by 39.0%[79]
2014Intelligent energy management at 45 bus stations at AlexandriaPSO development for occupancy prediction and the control of renewable energy sourcesDuring four-hour operation, power imported from the grid can be limited by only 42%[80]
201493 households in PortugalANN development for energy consumption and load forecastingMAPE is 4.2%[81]
2014AI development for estimating building energy consumptionGA, ANN, and SVM development for building estimation modelsPeak difference in hourly prediction of different models can be as high as 90%. Monthly prediction is 40% and annual variation is 7%[82]
2014Energy management optimization of a building that has wooden external walls of 9 cm and a wooden external roof of 9 cm. Distributed AI developmentDistributed AI in the end control devices can save up to 39% energy through the generation of optimal set points[83]
2015Real-world application for energy savings in a smart building at a Greek universityRule-based approach development for optimized scheduling controlDaily energy saving can reach up to 4%[84]
2015100 load curves in a smart gridANN development for DSMPrediction error is less than 5.5%[85]
2015Five AI algorithms conducted in a one-story test building with a double skin; the building is 4.2 m wide, 4.5 m deep, and 3.05 m high.AI theory-based optimal control algorithm development for improving the indoor temperature conditions and heating energy efficiencyCompared with the transitional algorithm, this novel algorithm can increase thermal comfort by around 2.27%[86]
2015Solar combi-system combined with a gas boiler or a heat pumpANN model development for predicting thermal loadBased on a learning sequence lasting only 12 days, the annual prediction errors are less than 10%[87]
2015Home energy management system in 25 households in AustriaShort-term smart learning electrical load algorithm development to increase flexibility to fit more the generation from renewable energies and micro co-generation devicesPrediction error is less than 8.2%[88]
2015Three houses with wireless sensors for detecting use occupancy and activity patternsNon-linear multiclass SVM, HMM, and k-nearest neighbor (kNN) model development to deal with the complex nature of data collected from various sensorsAI algorithm development can increase 25% performance for predicting occupants’ behaviors[89]
2015Modeling for smart energy scheduling in micro-gridsOperation policy and artificial fish swarm algorithm (AFSA) for suggesting operation policy (scheduling control) of a micro-grid with V2G (Vehicle to Grid)5.81% energy cost saving[90]
2016Hybrid renewable Energy systemsAI development for tariff control10% reduction of unit energy price[91]
2016Model-based predictive control for building energy managementModel-based predictive controller developmentSet point optimization by occupants’ activities can save 34.1% energy[92]
2016Multi-objective control and management for smart energy buildingsHybrid multi-objective GA development31.6% energy savings can be achieved for a smart building. Compared with traditional optimization methods, thermal comfort can be improved by 71.8%[93]
2016Hot water demand prediction model development for residential energy management systemsBottom–up approach developmentTotal energy savings of 18.25%. Among them, 1.46% of that is attributed to the use of AI tools, compared with linear-up prediction.[94]
2016Hybrid forecasting model based on data preprocessing, optimization, and AI algorithms AI-assisted data fusionMAPE ranges from 4.57% to 5.69%[95]
2017Estimation of the energy savings potential in national building stocks AI for analyzing user behaviors User-behavior trends were taken into account and up to a 10% improvement of prediction accuracy resulted[96]
2017Deep reinforcement learning for building HVAC controlDeep reinforcement learning (DFL)-based algorithm 11% energy savings[97]
2017Office heating ventilation and air conditioning systemsReinforcement learning (RL) and long/short-term memory RNN2.5% energy savings while improving thermal comfort by an average of 15%[98]
2018Manager’s decision-making system for household energy savingsANN-based decision making system (DMS) developmentElectricity bills could be reduced by around 10%[99]
2018Energy consumption forecasting for building energy management systemsElman neuro networkMean square error rate (MSE) ranges from 0.004413 to 0.005085[100]
2018Home air conditioner energy management and optimization strategy with demand responseMPC for demand response and air conditioning control9.2% energy savings when compared to conventional On/Off control and 1.8% energy savings compared with PID control [101]
2018Non-linear control techniques for HVAC systemsFuzzy controlSmoothly reaches to set point values. The steady state error rates range from 0.2% to 3.3%[102]
2018Enhancing building and HVAC system energy efficiencyMPCMost cases have an energy-savings rations range from 10% to 15%[103]
2018Building air conditioning systems in micro-gridsDistributed economic model predictive control (DEMPC)Predictions of energy prices are within 3%[104]
2018HVAC systems at an office building MAS and CBR for energy management and decision making41% energy savings[105]
Table 1 lists all the articles related to the application of AI technologies on the HVAC systems from 1997 to 2018 according to the PRISMA method. The results of the qualitative analysis of Table 1 are described in the following sections.
Table 2. Different sensors employed by AI-assisted HVAC control.
Table 2. Different sensors employed by AI-assisted HVAC control.
YearAcademic CaseAI Application ScenarioSensor DeploymentRef.
1997Heating, ventilation, and air conditioning (HVAC) system for improving occupant comfort and saving running costsOptimized setting
  • CO2 sensor
  • Fire sensor
  • Occupancy sensor
  • Temperature sensor
[11]
2000HVAC system with variable air volume (VAV) coils and constant air volume (CAV) coilsPredictive control
  • CO2 sensor
  • Flow rate sensor
  • Pressure sensor
  • Humidity sensor
  • Temperature sensor
  • Volatile organic compounds (VOCs) concentration sensor
[14]
2001Optimal heating control in a passive solar commercial buildingOptimized setting
  • Thermal comfort sensor module includes the ambient temperature sensors and solar radiation sensors
  • Water temperature sensor
  • Energy consumption meter
[17]
2002House_n demonstration at Massachusetts Institute of TechnologyOptimized setting
  • A fixed, wide-color camera, a microphone, and a temperature sensor
[18]
2003Fuzzy controller development for energy conservation and users’ indoor comfort requirementsFuzzy control for improving control performance
  • Hybrid sensor module consists of temperature humidity, air velocity, CO2, mean radiant temperature gauge, etc.
  • Outdoor temperature and humidity sensors
  • Indoor illuminance sensor
  • Indoor temperature sensor
  • Power meter
[21]
2003Artificial neuro network (ANN) development for optimal operation of heating system in buildingPredictive control
  • Simulation based on temperature sensor data, thermal resistances, and indoor heat gains
[22]
2005Predicting chiller energy consumption at a Laval building operated from 7:30 to 23:00, Monday to FridayModel-based predictive control
  • Outdoor dry-bulb temperature sensor
  • Wet-bulb temperature sensor
  • Horizontal solar flux sensor
  • Status detector of chiller
  • Water temperature sensor
  • Flow meter
  • Electric power meter
[24]
2005Internet-based HVAC system allows authorized users to keep in close contact with a building automation systemOptimized setting
  • Web-enabled controller with pressure, temperature, and flow sensors
[25]
2006Centralized HVAC system with multi-agent structureDistributed AI
  • Simulation based on thermal comfort related sensors
[31]
2006Predictive control system development for a building heating systemPredictive control
  • Temperature sensor
[32]
2006Indoor thermal comfort controller developmentFuzzy indoor thermal comfort controller development by simulation software
  • Simulation based on inputs from light sensor, outdoor temperature sensor, relative humidity sensor, air flow/hotwire anemometer, and CO2 sensor
[33]
2006Cooling load prediction of an existing HVAC system in ChinaLoad prediction
  • Multiple sensor data input includes temperature, relative humidity, and pressure
[34]
2007Linear reinforcement learning controller Machine learning and the adaptive occupant satisfaction simulatorThree different configurations include:
  • Indoor temperature; outdoor temperature; relative humidity; CO2
  • Indoor temperature; outdoor temperature; time; CO2
  • Indoor temperature; outdoor temperature; CO2
[36]
2008Heating load prediction of a district heating and cooling systemLoad prediction
  • Temperature sensor
  • Weather meter
[39]
2009Controller development for a typical variable air volume (VAV) air conditioning systemModel-based predictive control
  • Pressure sensor
  • Temperature sensor
  • Humidity sensor
  • Flow station
  • CO2 sensor
[42]
2010Chiller development for an intelligent buildingPredictive control and optimized setting
  • Temperature sensor
  • Power meter
[44]
2011Controller development for air conditioning system of one-floor buildingFuzzy PID
  • Temperature sensor
  • Relative humidity sensor
  • Solar radiation sensor
  • Power meter
[50]
2011Thermal control of a typical US single family houseFuzzy logic and adaptive neuro fuzzy inference system (ANFIS)
  • Temperature sensor
[52]
2011Controller development for a heating and cooling energy systemPredictive control
  • Temperature sensor
[54]
2012Zone temperature prediction and control in buildingsPredictive control and optimized setting
  • Chilled water valve opening level
  • Chilled water flow rate sensor
  • Chilled temperature sensor
  • Outdoor temperature sensor
  • Indoor temperature sensor
[59]
2012Model-based predictive control of HVAC systems for ensuring thermal comfort and energy consumption minimizationPredictive control and optimized setting
  • Wireless sensor network with activity detector, temperature sensor, humidity sensor, mean radiant temperature sensor, doors/windows state detector
  • Weather station includes solar radiation, temperature, and relative humidity
[61]
2012Coordinating occupant behavior for saving energy consumption of an HVAC system and improving thermal comfortDistributed AI
  • Real-world feedback data
  • Building/occupant data
  • Occupant suggestions
[62]
2012Optimization of chiller operation at the office building of the Imel company in New BelgradeOptimized setting
  • The outlet temperature from the chiller (evaporator outlet temperature sensor)
  • The return temperature sensor
  • The external temperature sensor
[63]
2012Energy-efficiency enhancement of decoupled HVAC systemWavelet-based artificial neuro network (WNN)—Infinite impulse response (IIR)—PID-based control
  • Temperature sensor
  • Humidity sensor
  • Air flow meter
  • Water flow meter
[64]
2013Building energy and comfort management system developmentDistributed AISensors provide
  • Environmental data
  • Occupancy data
  • Energy data
[72]
2013Energy intelligent building based on user activityDistributed AI and predictive controlWireless sensor networks include PIR sensors and magnetic reed switch door sensor[73]
2013Predictive control of a cooling plantModel-based predictive control
  • Temperature sensor
[71]
2014Dynamic fuzzy controllerPredictive control
  • ANN forecasted parameters
[75]
2014Energy management optimization of a buildingDistributed AI
  • Indoor temperature sensor
  • Water temperature sensor
  • Supplied air flow rate meter
  • Inlet air temperature sensor
  • Motion sensor
[83]
2014Optimal chiller loading problem solved by swarm intelligence techniqueOptimized setting
  • Power meter
[85]
2015AI theory-based optimal control for improving the indoor temperature conditions and heating energy efficiencyFive control algorithms include
  • Rule + ANN
  • ANN + ANN
  • Fuzzy + ANN
  • ANFIS with two inputs + ANN
  • ANFIS with one input + ANN
  • Temperature sensor
  • Surface opening status detector
[86]
2015Three houses with wireless sensors for detecting use occupancy and activity patternsOptimized setting and predictive control
  • Thermocouple array
  • Microphone
  • Hygro sensor
  • CO2 and air quality detector
  • Ultrasonic sensor
[89]
2016Model-based predictive control for the set point optimization of an HVAC system Model-based predictive control
  • Temperature sensor
  • Building energy analysis model with heat and moisture transfer through a wall
[92]
2016Multi-objective control and management of a smart buildingOptimized setting
  • Temperature sensor
  • CO2 concentration detector
  • Power meter
[93]
2017Deep reinforcement learning for building HVAC controlOptimized setting
  • Temperature sensor
  • Energy plus building model
[97]
2018AI enhanced air conditioning comfort by Ambi ClimateOptimized setting
  • Temperature sensor
  • Humidity sensor
  • Sunlight sensor
  • Geolocation by users’ mobile phone
[110]

Share and Cite

MDPI and ACS Style

Cheng, C.-C.; Lee, D. Artificial Intelligence-Assisted Heating Ventilation and Air Conditioning Control and the Unmet Demand for Sensors: Part 1. Problem Formulation and the Hypothesis. Sensors 2019, 19, 1131. https://doi.org/10.3390/s19051131

AMA Style

Cheng C-C, Lee D. Artificial Intelligence-Assisted Heating Ventilation and Air Conditioning Control and the Unmet Demand for Sensors: Part 1. Problem Formulation and the Hypothesis. Sensors. 2019; 19(5):1131. https://doi.org/10.3390/s19051131

Chicago/Turabian Style

Cheng, Chin-Chi, and Dasheng Lee. 2019. "Artificial Intelligence-Assisted Heating Ventilation and Air Conditioning Control and the Unmet Demand for Sensors: Part 1. Problem Formulation and the Hypothesis" Sensors 19, no. 5: 1131. https://doi.org/10.3390/s19051131

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop