A Study on Strengthening Standards for Fire Prevention of Anti-freeze Electric Heating Cable
As per the fire statistics survey of 2019, 56.5% (152 cases) of the entire fire accidents (269 cases) caused by heating cables were due to electrical factors. Therefore, in the present work, the electrical factors responsible for heating cable fire have been analyzed, and fire prevention measures have been demonstrated through related reproduction experiments. According to heating cable fire statistics, the fire in anti-freezing appliances (heating cables), except for fires caused by electric cable arcing and other unknown factors, can be classified into four types based on installation configurations. These configurations have been classified and tested according to the Technical Regulations for Electrical and Telecommunications Products and Components (K 10013). The results of a comparative experiment on anti-freezing appliances (heating cable) revealed that the configuration “a type of water pipe with a heating cable wrapped around the water pipe and insulation on the outside” showed the highest temperature among the four installation arrangements. Additionally, the maximum difference between the test temperature (K 10013) and the actual temperature was 40 ℃.