Insulation Strength Characteristics
Insulation Strength Characteristics
Insulation Strength Characteristics
[IEC 60071-1]
Fachgebiet Hochspannungstechnik
-1-
[IEC 60071-1]
Fachgebiet Hochspannungstechnik
-2-
-3-
Fachgebiet Hochspannungstechnik
-4-
Fachgebiet Hochspannungstechnik
-5-
-6-
dry band
enlargement of the dry band by arc heating (max. temperature at foot points)
Fachgebiet Hochspannungstechnik
-7-
-8-
Layer conductivity K is the most important parameter! Layer conductivity K is the most important parameter! K = ds
K = 5 S K = 10 S K = 40 S
Fachgebiet Hochspannungstechnik
-9-
general:
G=
V
l
2 r d s K dG = = dl d l / 2 r
Fachgebiet Hochspannungstechnik
- 10 -
G=
K
lk
dl 2 r 0
dl F = 2 r 0
K = FG K = FG
lk
(IEC 60507*)) form factor to be determined by graphical procedure, described in IEC 60507
*) IEC 60507, 2nd Ed. 1991-04: "Artificial pollution tests on high-voltage insulators to be used on a.c. systems"
Fachgebiet Hochspannungstechnik
- 11 -
An overhead line insulator must be desigend about five times as long as An overhead line insulator must be desigend about five times as long as required to withstand operating stresses under dry conditions! required to withstand operating stresses under dry conditions!
- 12 -
Sheds Sheds Terms ... s ... flashover or arcing distance lk ... creepage distance li ... insulator length p ... shed overhang t ... shed spacing
Fachgebiet Hochspannungstechnik
- 13 -
Reference value is Um, ,i.e. Reference value is Um i.e. the phase to-phase-voltage! the phase to-phase-voltage! li derived from required standard lightning impulse voltage strength (ud, LI ca. 5.5 kV/cm) lk from requirement on specific creepage distance (IEC 60815*))
Note: IEC 60815 applicable to porcelain insulators; so far no standard on polymeric insulators available
= 20%
for very heavy" pollution severity (IV) for very heavy" pollution severity (IV) for heavy" pollution severity (III) for heavy" pollution severity (III) for "medium" pollution severity (II) for "medium" pollution severity (II) for "light" pollution severity (I) for "light" pollution severity (I)
*) IEC 60815, 1st Ed. 1986: "Guide for the selection of insulators in respect of polluted conditions"
Fachgebiet Hochspannungstechnik
- 14 -
Correction of these values necessary depending on insulator's average diameter Dm *) Correction factor kD (derived from service experience):
kD 1 1.1 1.2
- 15 -
Fachgebiet Hochspannungstechnik
- 16 -
I - Light
II - Medium
III - Heavy
IV - Very heavy
1) Use of fertilizers by spraying, or the burning of crop residues, can lead to a higher pollution level due to dispersal by wind. 2) Distances from sea coast depend on the topography of the coastal area and on the extreme wind conditions.
Fachgebiet Hochspannungstechnik
- 17 -
Some typical shed profiles (from IEC 60815; explanation of the parameters see there). Some typical shed profiles (from IEC 60815; explanation of the parameters see there). From left to right: normal shed profile, alternating shed profile, underrib sheds (fog profile), From left to right: normal shed profile, alternating shed profile, underrib sheds (fog profile), cap-and-pin insulators cap-and-pin insulators
Fachgebiet Hochspannungstechnik
- 18 -
IEC 60815
Fachgebiet Hochspannungstechnik
- 19 -
5 specified No specification for bottom side angle; however, 2 "advisable" in case of sheds without underribs
IEC 60815
Fachgebiet Hochspannungstechnik
- 20 -
From: Raouf Znaidi: "Service Experience and Maintenance Requirements for Different Types of Insulators in Tunisia", World Congress on Insulators, Arresters and Bushings, Hong Kong, Nov. 27-30, 2005
Fachgebiet Hochspannungstechnik
- 21 -
- 22 -
- 23 -
-varistors
Fachgebiet Hochspannungstechnik
- 24 -
introduced in the beginning of the 1970s today virtually" state of the art problems": long time performance not yet clear, "brittle fracture", animal attacks
Fachgebiet Hochspannungstechnik
- 25 -
Fachgebiet Hochspannungstechnik
- 26 -
Fachgebiet Hochspannungstechnik
- 27 -
compare this with the "bathtub curve"of failure no evidence for aging
Fachgebiet Hochspannungstechnik
- 28 -
Fachgebiet Hochspannungstechnik
- 29 -
Fachgebiet Hochspannungstechnik
- 30 -
Fachgebiet Hochspannungstechnik
- 31 -
Advancing angle
actual research!
Fachgebiet Hochspannungstechnik
- 32 -
- 33 -
Excellent service record so far (only few exceptions where silicone rubber is not optimal, Excellent service record so far (only few exceptions where silicone rubber is not optimal, e.g. under extreme coastal conditions, i.e. heavy salt layers) e.g. under extreme coastal conditions, i.e. heavy salt layers)
Fachgebiet Hochspannungstechnik
- 34 -
*)
*) NOTE: often the term NCI = non ceramic insulators is being used
- 35 -
- 36 -
Similar test procedures specified e.g. for surge arresters (IEC 60099-4) and for polymeric insulators (IEC document 36/213/CDV: Project IEC 62217)
Fachgebiet Hochspannungstechnik
- 37 -
- 38 -
Tracking Erosion
Fachgebiet Hochspannungstechnik
- 39 -
Practical test problem: rain and solar radiation at the same time!
Fachgebiet Hochspannungstechnik
- 41 -
Fachgebiet Hochspannungstechnik
- 42 -
Fachgebiet Hochspannungstechnik
- 43 -
The test specimens shall be cleaned with de-ionized water before starting the test. The test specimens are mounted on the wheel as shown in Figure A.1 below. They go through four positions in one cycle. Each test specimen remains stationary for about 40 s in each of the four positions. The 90 rotation from one position to the next takes about 8 s. In the first part of the cycle the insulator is dipped into a saline solution. The second part of the test cycle permits the excess saline solution to drip off the specimen ensuring that the light wetting of the surface gives rise to sparking across dry bands that will form during the third part of the cycle. In that part the specimen is submitted to a power frequency voltage. In the last part of the cycle the surface of the specimen that had been heated by the dry band sparking is allowed to cool.
Electrical stress: NaCl content of de-ionized water: Ambient temperature: Test duration: The power frequency test voltage in kV is determined by dividing the actual creepage distance in millimetres by 28,6. 1,40 kg/m 0,06 kg/m 20 5 K C 30 000 cycles
The test is regarded as passed, if on both test specimens: no tracking occurs for composite insulators: erosion depth is less than 3 mm and does not reach the core; if applicable for resin insulators: erosion depth is less than 3 mm; no shed, housing or interface is punctured.
Fachgebiet Hochspannungstechnik
- 44 -
Fachgebiet Hochspannungstechnik
- 45 -
Class 1 : : 70 % 75 % of C.D. of ceramic insulators Class 1 70 % 75 % of C.D. of ceramic insulators Class 2 : : 80 % of C.D. of ceramic insulators (not applicable in coastal areas!) Class 2 80 % of C.D. of ceramic insulators (not applicable in coastal areas!) Class 3 : : same C.D. as for ceramic insulators Class 3 same C.D. as for ceramic insulators Class 4 : : in general, application of NCI should be carefully checked for each Class 4 in general, application of NCI should be carefully checked for each individual application individual application
Fachgebiet Hochspannungstechnik
- 46 -
Moss, algea
Fachgebiet Hochspannungstechnik
- 47 -
Fachgebiet Hochspannungstechnik
- 48 -
Fachgebiet Hochspannungstechnik
- 49 -
From: M. Kuhl: "FRP Rods for Brittle Fracture Resistant Composite Insulators", http://www.lappinsulator.com/downloadcenter/technical.asp Fachgebiet Hochspannungstechnik
- 50 -
Fachgebiet Hochspannungstechnik
- 51 -
Fachgebiet Hochspannungstechnik
- 52 -
Test specimen must not flash over within a specified time of exposure Test specimen must not flash over within a specified time of exposure Classification by withstand layer conductivity or withstand salt deposit density Classification by withstand layer conductivity or withstand salt deposit density
Fachgebiet Hochspannungstechnik
- 53 -
Fachgebiet Hochspannungstechnik
- 54 -
Risk of partial Risk of partial heating of internal heating of internal active elements active elements
Fachgebiet Hochspannungstechnik
- 56 -
From: Claude de Tourreil: "New IEC standards: their Impact on future Selection of Composite Insulators", World Congress on Insulators, Arresters and Bushings, Hong Kong, Nov. 2730, 2005 Fachgebiet Hochspannungstechnik
- 57 -