Specifications
NOMINAL VOLTAGE: 12V NOMINAL CAPACITY:
20 hr. rate of 5.0A to 10.5V 100.0Ah

Sealed Rechargeable Lead-Acid Battery


CHARGE RETENTION (shelf life) at 68F (20C): 1 month 97% 3 months 91% 6 months 85% LIFE EXPECTANCY: STANDBY USE 3 to 5 years CYCLE USE (approx.): 100% depth of discharge 250 cycles 50% depth of discharge 550 cycles 30% depth of discharge 1200 cycles SEALED CONSTRUCTION: Can be operated in any position without leakage. STANDARD TERMINAL: Receptacle terminal HOUSING MATERIAL: PP Resin OPTIONAL: Container and cover made from Flame Retardant PP (UL94-V0/L.O.I.>28%)

12V, 100Ah
Terminal
M6

10 hr. rate of 9.0A to 10.5V 90.0Ah 5 hr. rate of 16.0A to 10.2V 80.0Ah 1 hr. rate of 60.0A to 9.60V 60.0Ah WEIGHT (approx.): 68 pounds (30.8kgs) ENERGY DENSITY (20 hr. rate): 1.62 WH/cubic inch (99.4 WH/liter) SPECIFIC ENERGY (20 hr. rate): 17.6 WH/pound (38.9 WH/kg) INTERNAL RESISTANCE OF CHARGED BATTERY: 6.5 milliohms (approx.) MAXIMUM DISCHARGE CURRENT WITH STANDARD TERMINALS: 150 amperes MAXIMUM SHORT-DURATION DISCHARGE CURRENT: 500 amperes OPERATING TEMPERATURE RANGE: CHARGE 50F to 1220F (-150C to 500C) DISCHARGE -40F to 1400F (-200C to 600C)

20 (0.79)

DIMENSIONS: MM (INCHES)

Dimensions
6.77 (172.0)
8.43 (214.0)

12.95 (329.0)

DIMENSIONS: INCHES (MM) UL listing pending - File No MH14328

Publication No: EN-NP100-12R-01 June 2005

DISCHARGE CHARACTERISTIC CURVES AT 250C (770F)


PERCENTAGE OF CAPACITY AVAILABLE

TEMPERATURE EFFECTS IN RELATION TO BATTERY CAPACITY

TERMINAL VOLTAGE

SELF DISCHARGE CHARACTERISTICS


(%) 100 (V) 14.0

OPEN CIRCUIT VOLTAGE VS REMAINING CAPACITY


AT 250C (770F) OPEN CIRCUIT VOLTAGE
18

REMAINING CAPACITY

75

13.0

50 200C (680F) 400C (1040F) 25 30 C (86 F)


0 0

12.0

11.0

12

15

10.0

20

40

60

80

100

STORAGE TIME (MONTHS)

REMAINING CAPACITY (%)

CYCLE SERVICE LIFE IN RELATION TO DEPTH OF DISCHARGE


PERCENTAGE OF CAPACITY AVAILABLE
TESTING CONDITIONS: DISCHARGE CURRENT: 0.17C AMP. (F.V. 1.7V/CELL) CHARGING CURRENT: 0.09C AMP. CHARGING VOLUME: 125% OF DISCHARGED CAPACITY AMBIENT TEMPERATURE: 200C TO 250C (680F TO 770F)

FLOAT SERVICE LIFE


PERCENTAGE OF CAPACITY AVAILABLE

(AH%) 120 100 80 60

TESTING CONDITIONS: FLOATING VOLTAGE 2.25 TO 2.30V/CELL AMBIENT TEMPERATURE: 200C TO 220C (640F TO 720F) (AH%) 120 100 80

40 20 0 1 2 3 4 5 5.5

100% D.O.D. 40 20 0 200

50% D.O.D.

30% DEPTH OF DISCHARGE

LIFE (YEARS)
400 600 800 1000 1200 1400

NUMBER OF CYCLES

When the battery will be used by current in excess of 3C, consult with EnerSys prior to use. CHARGING METHODS (At 20C) CAUTION Maximum charging current 0.25C Charging voltage 14.4 to 15.0V Standby use: Float charging voltage 13.50 to 13.80V Cycle use:

Avoid short circuit Do not charge in a sealed container.

EnerSys P.O. Box 14145 Reading, PA 19612-4145 USA Tel:+1-610-208-1991 +1-800-538-3627