Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 OPH England Tel: +44 (0) 1723 890099 Fax: +44 (0) 1723 893303 E-Mail: Sales@Deepseaplc.com
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
INTRODUCTION .................................................................................................... 5
CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION. .....................................5
1. OPERATION ...................................................................................................... 6
1.1 CONTROL .................................................................................................................................6 FIG 1 .....................................................................................................................................6 1.2 AUTOMATIC MODE OF OPERATION ....................................................................................7 1.3 MANUAL OPERATION ............................................................................................................8 MANUAL OPERATION WITH EXTERNAL START AND STOP PUSHBUTTONS ....................9
2. PROTECTIONS ................................................................................................ 10
2.1 WARNINGS ............................................................................................................................11 2.2 SHUTDOWNS .........................................................................................................................12 2.3 ELECTRICAL TRIPS ..............................................................................................................14 2.4 SPECIAL ALARM CONDITIONS ...........................................................................................14
8. FAULT FINDING .............................................................................................. 27 9. TYPICAL WIRING DIAGRAM (3PHASE 4WIRE) ............................................ 28 10. FACTORY DEFAULT CONFIGURATION ..................................................... 29 11. ICONS AND LCD INDENTIFICATION ........................................................... 31
3 560 OPERATING MANUAL ISSUE 5 30/08/2007 MR
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
11.1 ICON DESCRIPTIONS ......................................................................................................... 31 11.2 LCD USER-DEFINED INDICATION IDENTIFICATION DIAGRAM .................................... 32
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
INTRODUCTION
The DSE 560 Module, has been designed to allow the OEM to meet most of the industrys complex specifications. It has been primarily designed to allow the user to start and stop the generator, and if required, transfer the load to the generator either manually (via external pushbuttons) or automatically. The user also has facility to view all the system operating parameters via the LCD display. The DSE 560 module monitors the engine, indicating the operational status and fault conditions; automatically shutting down the engine and giving a true first up fault condition of an engine failure by a flashing COMMON ALARM LED. Exact failure mode information is indicated by the LCD display on the front panel. The powerful Micro-processor contained within the module allows for a range of complex features to be incorporated as standard; Graphical Icon based LCD display (excluding the need for translations and languages). Voltage and Current monitoring. Engine parameter monitoring. Fully configurable inputs for use as alarms or a range of different functions. Extensive range output functions using built in relay outputs or relay expansion available .
Selective operational sequences, timers and alarm trips can be altered by the customer via a PC using the P808 for Window software and 808 interface. Access to critical operational sequences and timers for use by qualified engineers, are barred by a security code. The module is housed in a robust plastic case for the front panel mounting. Connections to the module are via locking plug and sockets.
1.1 1.2
NOTE: CAUTION!:
Highlights an essential element of a procedure to ensure correctness. Indicates a procedure or practice which, if not strictly observed, could result in damage or destruction of equipment. Indicates a procedure or practice which could result in injury to personnel or loss of life if not followed correctly. Deep Sea Electronics Plc owns the copyright to this manual, which cannot be copied, reproduced or disclosed to a third party without prior written permission. Compliant with BS EN 60950 Low Voltage Directive Compliant with BS EN 50081-2 EMC Directive Compliant with BS EN 50082-2 EMC Directive Year 2000 Compliant
WARNING!:
1.2.1
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
2 1. OPERATION
2.1 1.1 CONTROL
Control of the DSE 560 module is via a rotary switch (or Key-switch) mounted on the front of the module with STOP/RESET, MANUAL and AUTO functions. For normal operation this is the only control which needs to be operated. The small push-button is used to access further information such as instrumentation, details of its operation are detailed later in this document. The following descriptions detail the sequences followed by a module containing the standard factory configuration. Always refer to your configuration source for the exact sequences and timers observed by any particular module in the field.
L1 L2 N L2o L3 N L3 L1 N
AV
AUTO
FIG 1
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
2.2
1.2
The module is activated by turning the selector switch to the AUTO position
When a Remote Start signal is applied to the remote start input, the following sequence is initiated:The Remote Start Active indicator illuminates (if configured). To allow for false signals the Start Delay timer is initiated, after this delay, if the pre-heat output option is selected this timer is then initiated, and the corresponding auxiliary output which is selected energises. NOTE:- If the Remote Start signal is removed during the Start Delay timer the unit will return to a stand-by state. After the above delays the Fuel Solenoid is energised, then the Starter Motor is engaged. The engine is cranked for a pre-set time period. If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of attempts, the start sequence will be terminated and Fail to Start fault will be displayed accompanied by a flashing red LED.
When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the Alternator output. Alternatively a Magnetic Pickup mounted on the flywheel housing can be used for speed detection. (This is selected by PC using the 808 interface.) The warning lamp output of the charge alternator can also be used to disconnect the starter motor, however it cannot be used for underspeed or overspeed. After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault. Once the engine is running, the Warm Up timer, if selected is initiated, allowing the engine to stabilise before accepting the load. If an auxiliary output has been selected to give a load transfer signal, this would then activate. NOTE:-A load transfer will not be initiated until the Oil Pressure has risen. Thus preventing excessive wear on the engine. On removal of the Remote Start signal, the Stop delay timer is initiated, once it times out the load Transfer signal is de-energised, removing the load. The Cooling timer is then initiated, allowing the engine a cooling down period off load before shutting down. Once the Cooling timer expires the Fuel Solenoid is de-energised, bringing the generator to a stop. Should the Remote Start signal be re-activated during the cooling down period, the set will return on load.
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
2.3
1.3
MANUAL OPERATION
NOTE:- The following sequence is only applicable to controllers not using external start/stop push-button control.
To initiate a start sequence in MANUAL, turn the selector switch to MANUAL NOTE:- There is no Start Delay in this mode of operation.
If the pre-heat output option is selected this timer is then initiated, and the auxiliary output selected is energised. After the above delay the Fuel Solenoid is energised, then the Starter Motor is engaged. The engine is cranked for a pre-set time period. If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of attempts, the start sequence will be terminated and Fail to Start fault will be displayed accompanied by a flashing red LED.
When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the Alternator output. Alternatively a Magnetic Pickup mounted on the flywheel housing can be used for speed detection. (This is selected by PC using the 808 interface.) The warning lamp output of the charge alternator can also be used to disconnect the starter motor, however it cannot be used for underspeed or overspeed. After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault. Once the engine is running, the Warm Up timer, if selected is initiated, allowing the engine to stabilise before it can be loaded. The generator will run off load, unless a Remote Start signal is applied, and if Load Transfer has been selected as a control source, the appropriate auxiliary output selected will activate. NOTE:- It is possible to have a manual run on-load by using Load Transfer (Always) Refer to the P808 for windows manual for further details. If the Remote Start signal is removed, the generator will continue to run On load until the selector switch is turned to Auto. The Remote Stop Delay Timer will time out, the load is then disconnected. The generator will then run off load allowing the engine a cooling down period. Turning the selector to STOP de-energises the FUEL SOLENOID, bringing the generator to a stop.
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
3.1.1
If the module has been configured to use external Start and Stop pushbuttons the normal Manual mode of operation is over-ridden and the following sequence is observed; Turn the selector switch to MANUAL .
To start the set operate the external Start Pushbutton, the pre-heat output (if selected) will energise and the timer is initiated. Once the above delay has expired the Fuel Solenoid is energised, then the Starter Motor is engaged. The engine is cranked for a pre-set time period. If the engine fails to fire during this cranking attempt then the starter motor is disengaged for the pre-set rest period. Should this sequence continue beyond the set number of attempts, the start sequence will be terminated and Fail to Start fault will be displayed accompanied by a flashing red LED.
When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency from the Alternator output. Alternatively a Magnetic Pickup mounted on the flywheel housing can be used for speed detection. (This is selected by PC using the 808 interface.) The warning lamp output of the charge alternator can also be used to disconnect the starter motor, however it cannot be used for underspeed or overspeed. After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault. Once the engine is running, the Warm Up timer, if selected is initiated, allowing the engine to stabilise before it can be loaded. The generator will run off load, unless a Remote Start signal is applied, and if Load Transfer has been selected as a control source, the appropriate auxiliary output selected will activate. NOTE:- It is possible to have a manual run on-load by using Load Transfer (Always) Refer to the P808 for windows manual for further details. If the Remote Start signal is removed, the generator will continue to run On load until the selector switch is turned to Auto. The Stop Delay Timer will time out, the load is then disconnected. The generator will then run off load allowing the engine a cooling down period. Turning the selector to STOP or pressing the Stop Pushbutton de-energises the FUEL SOLENOID, bringing the generator to a stop. NOTE:- A version of the module is available which has the start button built into the front fascia of the module. Operation of this module is as detailed above.
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
4 2. PROTECTIONS
The module will indicate that an alarm has occurred in several ways; The Common alarm LED will illuminate (Warning = Amber, Shutdown = Red Flashing)
0.0
0.0
If no alarms are present the LCD will extinguish any alarm icons.
Hz RPM
51.0 1530
In the event of a warning alarm the LCD will display the appropriate icon. If a shutdown then occurs the module will display the appropriate icon. The original warning alarm icon will remain displayed. Example:-
BAR
PSI
0.8 11.0
Charge Fail Warning Amber LED, Charge Fail and Warning alarm Icon all displayed steady. Followed by.
Hz
RPM
0.0
0
Over-speed shutdown
Red LED, Over-speed and Shutdown alarm Icon all displayed flashing. The original warning will remain displayed as long at the triggering conditions remain. Any subsequent warnings or shutdowns which occur will be displayed steady, therefore only the first-up shutdown will appear flashing.
10
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
4.1
2.1
WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to draw the operators attention to an undesirable condition. In the event of a warning alarm the LCD will display:-
The COMMON ALARM LED will also illuminate (amber). BATTERY CHARGE FAILURE, if the module does not detect a voltage from the warning light terminal on the auxiliary charge alternator, the module will display:The COMMON ALARM LED will also illuminate (amber). BATTERY LOW VOLTAGE, if the module detects that the plant DC supply has fallen below the low volts setting level , the module will display:-
V
The COMMON ALARM LED will also illuminate (amber). The Battery Low Voltage alarm is delayed by the Low DC Volts Delay timer. BATTERY HIGH VOLTAGE, if the module detects that the plant DC supply has risen above the high volts setting level , the module will display:-
V
The COMMON ALARM LED will also illuminate (amber). FAIL TO STOP, If the module detects the engine is still running when the Fail to stop timer expires, then the module will display:-
The COMMON ALARM LED will also illuminate flashing red. NOTE:- Fail to Stop could indicate a faulty oil pressure sender - If engine is at rest check oil sender wiring and configuration. GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the pre-set trip a warning is initiated. The LCD will indicate:-
A
The COMMON ALARM LED will illuminate (amber). AUXILIARY INPUTS, if an auxiliary input has been configured as a warning the appropriate LCD segment will be displayed:-
!
The COMMON ALARM LED will also illuminate (amber).
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
4.2
2.2
SHUTDOWNS
Shutdowns are latching and stop the Generator. The alarm must be accepted and cleared, and the fault removed to reset the module. In the event of a shutdown alarm the LCD will display:-
The COMMON ALARM LED will also illuminate (Red Flashing). The appropriate LCD icon will also be displayed flashing NOTE:- The alarm condition must be rectified before a reset will take place. If the alarm condition remains it will not be possible to reset the unit (The exception to this is the Low Oil Pressure alarm and the like, as the oil pressure will be low with the engine at rest). Any subsequent warnings or shutdowns which occur will be displayed steady, therefore only the first-up shutdown will appear flashing. FAIL TO START, if the engine does not fire after the pre-set number of attempts has been made a shutdown will be initiated. The LCD will indicate:The COMMON ALARM and LED will flash (Red). EMERGENCY STOP, removal of the +ve DC Supply from the Emergency Stop input initiates the following sequence, firstly it will initiate a controlled shutdown of the Generator and prevent any attempt to restart the Generator until the Emergency Stop push-button has been reset. Secondly it removes the +ve DC supply from both the Fuel Solenoid and Starter Solenoid. The LCD will indicate:The COMMON ALARM LED will flash (Red). NOTE:- The Emergency Stop +Ve signal must be present otherwise the unit will shutdown. LOW OIL PRESSURE, if the module detects that the engine oil pressure has fallen below the low oil pressure trip setting level after the Safety On timer has expired, a shutdown will occur. The LCD will indicate:The COMMON ALARM LED will flash (Red). HIGH ENGINE TEMPERATURE, if the module detects that the engine coolant temperature has exceeded the high engine temperature trip setting level after the Safety On timer has expired, a shutdown will occur. The LCD will indicate:The COMMON ALARM LED will flash (Red). OVERSPEED, if the engine speed exceeds the pre-set trip a shutdown is initiated. The LCD will indicate:The COMMON ALARM LED will flash (Red). Overspeed is not delayed, it is an immediate shutdown.
12
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
NOTE:-However, during the start-up sequence the overspeed trip logic can be configured to allow an extra trip level margin, this is used to prevent nuisance tripping on start-up - Refer to the 808 For Windows Software Manual under heading Overspeed Overshoot for details. UNDERSPEED, if the engine speed falls below the pre-set trip after the Safety On timer has expired, a shutdown is initiated. The LCD will indicate:The COMMON ALARM LED will flash (Red). GENERATOR HIGH FREQUENCY, if the module detects a generator output frequency in excess of the pre-set trip a shutdown is initiated. The LCD will indicate:The COMMON ALARM LED will flash (Red). Generator High Frequency is not delayed, it is an immediate shutdown. GENERATOR LOW FREQUENCY, if the module detects a generator output frequency below the pre-set trip after the Safety On timer has expired, a shutdown is initiated. The LCD will indicate:The COMMON ALARM LED will flash (Red). GENERATOR HIGH VOLTAGE, if the module detects a generator output voltage in excess of the pre-set trip a shutdown is initiated. The LCD will indicate:-
V
The COMMON ALARM LED will flash (Red). High voltage is not delayed, it is an immediate shutdown. GENERATOR LOW VOLTAGE, if the module detects a generator output voltage below the below the pre-set trip after the Safety On timer has expired, a shutdown is initiated. The LCD will indicate
V
The COMMON ALARM LED will flash (Red). OIL PRESSURE SENDER OPEN CIRCUIT, if the module detects a loss of signal from the oil pressure sender (open circuit) a shutdown is initiated. The LCD will indicate:(steady) (and ----- on the engine oil pressure instrument), the COMMON ALARM LED will flash (Red). Sender failure is not delayed, it is an immediate shutdown. AUXILIARY INPUTS, if an auxiliary input has been configured as a shutdown the appropriate LCD segment will be displayed:-
!
The COMMON ALARM LED will flash (Red). LOSS OF SPEED SIGNAL, if the speed sensing signal is lost during cranking, a shutdown is initiated. The LCD will indicate:(steady) (and ----- on the engine RPM instrument), the COMMON ALARM LED will flash (Red). NOTE:- This will only occur if the speed sensing signal is lost during cranking or during the safety on timer. If the signal is lost during normal operation the Generator will shutdown with an Under-speed alarm.
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
4.3
2.3
ELECTRICAL TRIPS
Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip condition the module will de-energise the Load Transfer Output to remove the load from the generator. Once this has occurred the module will start the Cooling timer and allow the engine to cool, off-load before shutting down the engine. The alarm must be accepted and cleared, and the fault removed to reset the module. In the event of a shutdown alarm the LCD will display:-
The COMMON ALARM LED will also illuminate (Red steady) and the generator will be removed from the load. Once the cooling timer has expired the COMMON ALARM LED will flash (Red). AUXILIARY INPUTS, if an auxiliary input has been configured as an electrical trip the appropriate LCD segment will be displayed:-
!
The COMMON ALARM LED will illuminate (red Steady) until the engine is shutdown (red flashing).
4.4
2.4
The microprocessor has a watchdog facility which continually monitors the operation of the module. Should an error occur and the microprocessor is still functioning, an alarm will be indicated by the LCD back-light flashing and the common alarm LED being illuminated RED (steady). If the module is being configured and does not receive the correct information via the 808 interface the watchdog will halt the module operation and signal a corrupt user configuration by flashing the LCD back-light and illuminating the common alarm LED GREEN (steady). Attempting to re-send the configuration should rectify the alarm unless a problem exists with the configuration transfer (such as a broken cable, etc). If in doubt please refer Deep Sea Electronics PLC.
14
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
5 3. DECRIPTION OF CONTROLS
The following section details the function and meaning of the various controls on the module.
L1 L2 N L2o L3 N L3 L1 N
AV
Auto Mode
AUTO
Stop/Reset
Selector Switch
Manual Mode
FIG2
3.1 TYPICAL LCD DISPLAY SCREENS
INSTRUMENTS
L1- L2 L2- L3 L3- L1
The LCD displays the various engine parameters such as ENGINE SPEED, OIL PRESSURE, HOURS RUN, etc. Each instrument is displayed with the appropriate units of measure.
0.0
0.0
The LCD also displays the exact nature of any alarm condition which have occurred such as LOW OIL PRESSURE using appropriate icons. This allows very specific alarm conditions to be brought to the operators attention. Refer to the Protections section of this manual for details of the alarms. The LCD displays the user defined indications when configured and active. The icons will illuminate and point to the appropriate text insert label. These indications can be used to indicate the operation of external equipment (i.e. Battery Charger On, Breaker Closed etc) or to indicate internal states (i.e. Engine Running, Safety On, etc).
! !
The LCD displays the user defined alarms when configured and active. The icons will illuminate and point to the appropriate text insert label. These alarms can be used to indicate the operation of external alarms (i.e. Low Fuel Level, Low Coolant level etc) or to indicate internal alarms (i.e. Fail to Stop, MPU fault, etc).
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
5.1
Alarm Icons
5.2
NOTE:- The Engine Hours Run counter will only display the accumulated hours to the nearest 12 Minutes Hour (0.2Hr). The accumulated time will be recorded in HH:MM however. [Pre V1.4 Modules recorded hours run to the nearest Hour (0.5)] CAUTION!:-If the DC supply to the module is interrupted the hours run counter will not remember any un-displayed minutes accumulated since the last 12 Minute display update. i.e. 10 Hours 38 Minutes accumulated before DC supply is removed (10.6 Hours displayed) would become 10 Hours 36Minutes on restoration of DC supply. (10.6 Hours still displayed) This will only occur in the event of a total DC supply break and will NOT occur if the module is simply switched to the Stop/Reset position.
16
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
It is possible to manually scroll to display the different instruments by repeatedly operating the scroll button, once selected the instrument will remain on the LCD display until the user selects a different instrument or after a period of inactivity the module will revert to the initial display.
Instrument Page Order: Frequency / RPM AC Voltage Line-Neutral AC Voltage Line-Line AC Line Current Oil Pressure Coolant temperature Engine Hours Run DC Battery Voltage
>>>>>>> >
Hz
RPM
51.0 1530
Pressing the DOWN button the LCD will then show
L1- N
L2- N
L3- N
L1- L2
L2- L3
L3- L1
button again will scroll through each individual instrument eventually returning Pressing the to the original instrument displayed.
NOTE:-Once selected the instrument will remain on the LCD display until the user selects a different instrument or after a period of inactivity the module will revert to the initial display.
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
5.6
3.2 INDICATORS
COMMON ALARM LED This LED indicates when an alarm condition is present. The Alarms Page on the LCD will detail the exact nature of the alarm. OFF - no alarm active. STEADY AMBER - A warning alarm is present. FLASHING RED - A shutdown alarm is present. STEADY RED - An Electrical trip alarm is present. USER CONFIGURABLE LCD INDICATIORS These LCDs can be configured by the user to indicate any on of the different functions based around the following: INDICATIONS - Monitoring of a digital input and indicating associated functioning users equipment Such as Battery Charger On or Louvers Open, etc. WARNINGS and SHUTDOWNS - Specific indication of a particular warning or shutdown condition, backed up by LCD indication (!)- Such as Low Oil Pressure Shutdown, Low Coolant level, etc. STATUS INDICATIONS - Indication of specific functions or sequences derived from the modules operating state - Such as Safety On, Pre-heating, Generator Available, etc.
5.7 5.8
3.3 CONTROLS
STOP/RESET This position places the module into its Stop/reset mode. This will clear any alarm conditions for which the triggering criteria have been removed. If the engine is running and this position is selected, the module will automatically instruct the change-over device to un-load the generator (Load transfer becomes in-active (if used)). The fuel supply will be removed and engine will be brought to a standstill. Should a remote start signal be present while operating in this mode, a remote start will not occur. AUTO This position places the module into its Automatic mode. This mode allows the module to control the function of the generator automatically. The module will monitor the remote start input and once a start condition is signalled the set will be automatically started and placed on load (Load transfer becomes active (if used)). If the starting signal is removed the module will automatically transfer the load from the generator and shut the set down observing the stop delay timer and cooling timer as necessary. The module will then await the next start event. For further details please see the more detailed description of Auto Operation earlier in this manual. MANUAL This position is used to allow manual control of the generator functions. Once in Manual mode the module will start the engine and run off load. If the engine is running off-load in the Manual mode and a remote start signal becomes present, the module will automatically instruct the change-over device to place the generator on load (Load transfer becomes active (if used)). Should the remote start signal then be removed the generator will remain on load until either the STOP/RESET or AUTO positions is selected.
18
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
6 4. INSTALLATION INSTRUCTIONS
The model DSE 560 Module has been designed for front panel mounting. Fixing is by 4 spring loaded clips for easy assembly.
6.1
4.1
PANEL CUT-OUT
138.00mm
185.00mm
FIG 3
In conditions of excessive vibration the module should be mounted on suitable anti-vibration mountings.
6.2
4.2
COOLING
The module has been designed to operate over a wide temperature range -30 to +70 C. However allowances should be made for the temperature rise within the control panel enclosure. Care should be taken NOT to mount possible heat sources near the module unless adequate ventilation is provided. The relative humidity inside the control panel enclosure should not exceed 95%.
6.3
4.3
UNIT DIMENSIONS
137mm
144.0mm
CE
110.0mm
FIG 4
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
6.4
4.4
L1 L2 N L2o L3 N L3 L1 N
AV
AUTO
FIG 5
6.5 4.5 REAR PANEL LAYOUT
CE
FIG 6
20
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
7 5. ELECTRICAL CONNECTIONS
Connections to the Module are via plug and sockets.
7.1
7.1.1
PIN No 1 2 3
5.1
CONNECTION DETAILS
The following describes the connections and recommended cable sizes to the 3 (or 4) plugs and sockets on the rear of the Module. See rear panel layout FIG 5.
PLUG A 13 WAY
DESCRIPTION DC Plant Supply Input (-ve) DC Plant Supply Input (+ve) Emergency Stop Input CABLE SIZE 2.5mm 2.5mm 2.5mm NOTES
(Recommended Maximum Fuse 21A) Plant Supply +ve. Also supplies fuel & start outputs. (Recommended Maximum Fuse 32A) Plant Supply +ve from pin 3. 16 Amp rated. Plant Supply +ve from pin 3. 16 Amp rated. Plant Supply +ve. 5 Amp rated. Plant Supply +ve. 5 Amp rated. Must NOT be connected to plant supply -ve. Switch to -ve Switch to -ve Switch to -ve Switch to -ve Switch to -ve NOTES Spare Spare Spare Spare Plant Supply +ve. 5 Amp rated. Spare Connect to Magnetic Pickup device Connect to Magnetic Pickup device Connect to Oil pressure sender Connect to Coolant Temperature sender Return feed for senders*. Connect to secondary of L1 monitoring CT Connect to secondary of L2 monitoring CT Connect to secondary of L3 monitoring CT Spare Connect to secondary of all monitoring CTs Connect to a good clean earth point
4 5 6 7 8 9 10 11 12 13
Fuel relay Output Start relay Output Auxiliary Output relay 1 Auxiliary Output relay 2 Charge Fail Input/ Excitation Output Auxiliary Input 1 Auxiliary Input 2 Auxiliary Input 3 Auxiliary Input 4 Auxiliary Input 5
2.5mm 2.5mm 1.0mm 1.0mm 1.0mm 0.5mm 0.5mm 0.5mm 0.5mm 0.5mm CABLE SIZE
7.1.2
PIN No 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
PLUG B 17 WAY
DESCRIPTION Not Used Not Used Not Used Not Used Auxiliary Output relay 3 Not Used Magnetic Pickup Input (+ve) Magnetic Pickup Input (-ve) Oil Pressure Input Coolant Temperature Input Sender Common Return CT secondary for L1 CT secondary for L2 CT secondary for L3 Not Used CT secondary common Functional Earth
1.0mm 0.5mm 0.5mm 0.5mm 0.5mm 0.5mm 2.5mm 2.5mm 2.5mm 2.5mm 2.5mm
NOTE*:- If using single terminal senders refer to connection diagram. If using earth return type senders connect return terminals to pin 24 and earth pin 24.
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
7.1.3
PIN No 31 32 33 34
PLUG C 4 WAY
DESCRIPTION Generator L1 Voltage Monitoring Input Generator L2 Voltage Monitoring Input Generator L3 Voltage Monitoring Input Generator Neutral Input CABLE SIZE 1.0mm 1.0mm 1.0mm 1.0mm NOTES Connect to generator L1 output (AC) (Recommend 2A Fuse) Connect to generator L2 output (AC) (Recommend 2A Fuse) Connect to generator L3 output (AC) (Recommend 2A Fuse) Connect to generator Neutral output (AC)
NOTES:Screened cable must be used for connecting the Magnetic Pickup, ensuring that the screen is earthed at one end ONLY. A version of the module is available which allows connection to a 3 phase 3 wire system with no neutral (Delta). If using such a module then no connection should be made to terminal 34.
7.2
7.2.1 PC CONFIGURATION INTERFACE CONNECTOR
7.3
4-way connector allows connection to PC via the 808 configuration interface. Module can then be re-configured utilising the P808 for Windows software. The connector also allows connection to the 157 relay expansion module or to the 548 LED Remote annunciator module.
7.2.2 7.2.3
22
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
7.4
7.4.1 7.4.2
PIN No 1 2 3
5.2
The following describes the functions of the 3 connectors on the rear of the module. See rear panel layout FIG 5.
PLUG A 13 WAY
DESCRIPTION DC Supply -ve. System DC negative input. (Battery Negative). DC Supply +ve. System DC positive input. (Battery Positive). Emergency Stop input. Internally linked to Starter and Fuel outputs. If this input is not connected to positive the module will be locked out, and if the engine is running it will shutdown immediately. The Positive Supply is also removed from Starter and Fuel outputs, therefore only a single pole Emergency Shutdown button is required. Fuel Relay output. Plant Supply +ve from pin 3. Used to control the fuel solenoid or engine fuel control system. Starter Relay output. Plant Supply +ve from pin 3. Used to control the Starter Motor. Auxiliary Relay output 1. Plant Supply +ve. Configurable output, see Calibration Manual for options available. Auxiliary Relay output 2. Plant Supply +ve. Configurable output, see Calibration Manual for options available. Charge Fail input / Excitation output. Supplies excitation to the Plant Battery Charging Alternator, also an input for the Charge Fail detection circuitry. Auxiliary input 1. This is a negative switched configurable input, see Calibration Manual for options available. It is possible to configure the input to be a normally closed signal or a normally open signal. Auxiliary input 2. This is a negative switched configurable input, see Calibration Manual for options available. It is possible to configure the input to be a normally closed signal or a normally open signal. Auxiliary input 3. This is a negative switched configurable input, see Calibration Manual for options available. It is possible to configure the input to be a normally closed signal or a normally open signal. Auxiliary input 4. This is a negative switched configurable input, see Calibration Manual for options available. It is possible to configure the input to be a normally closed signal or a normally open signal. Auxiliary input 5. This is a negative switched configurable input, see Calibration Manual for options available. It is possible to configure the input to be a normally closed signal or a normally open signal.
4 5 6 7 8 9
10
11
12
13
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
7.4.3
PIN No 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
PLUG B 17 WAY
DESCRIPTION DO NOT USE DO NOT USE DO NOT USE DO NOT USE Auxiliary Relay output 3. Plant Supply +ve. Configurable output, see Calibration Manual for options available. DO NOT USE Magnetic Input +ve. An AC signal from the magnetic pickup +ve for speed sensing. Magnetic Input -ve. An AC signal from the magnetic pickup -ve for speed sensing. Oil Pressure sensing input. Connect to resistive type oil pressure sender. Refer to connection diagram for details. Coolant Temperature sensing input. Connect to resistive type coolant temperature sender. Refer to connection diagram for details. Sender Common connection. Return feed from sender units - refer to connection diagram for details. Generator L1 current transformer connection. Generator L2 current transformer connection. If single phase is used do not connect this pin. Generator L3 current transformer connection. If single phase is used do not connect this pin. DO NOT USE Generator current transformer common connection and CT earth connection. Functional Earth - Ensure connection to a good clean earth point.
7.4.4
PIN No 31 32 33 34
PLUG C 4 WAY
DESCRIPTION Generator L1 sensing input. Connect to alternator L1 output. Generator L2 sensing input. Connect to alternator L2 output. If using single phase only do not connect this terminal. Generator L3 sensing input. Connect to alternator L3 output. If using single phase only do not connect this terminal. Generator N sensing input. Connect to alternator N output.
7.4.5
NOTE:- A version of the module is available which allows connection to a 3 phase 3 wire system with no neutral (Delta). If using such a module then no connection should be made to terminal 34. Check the serial number label if in doubt.
24
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
7.4.6
8 6. SPECIFICATION
DC Supply Cranking Dropouts
Max. Operating Current Max. Standby Current Alternator Input Range 3Phase 4Wire System () 3Phase 3Wire System (U) Alternator Input Frequency Magnetic Input Range (if fitted) Magnetic Input Frequency Start Relay Output Fuel Relay Output Auxiliary Relay Outputs Dimensions Charge Fail / Excitation Range Operating Temperature Range CT Burden CT Secondary CT Class Electromagnetic Compatibility Electrical Safety Cold Temperature Hot Temperature Humidity Vibration
9.0 to 35 V Continuous. Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5V .This is achieved without the need for internal batteries. 390mA at 12 V. 250mA at 24 V. 220mA at 12 V. 120mA at 24 V. 15V - 277 (ph-N) 3 Phase 4wire AC (+20%) 30V - 480 (ph-ph) 3 Phase 3wire AC (+20%) 50 - 60 Hz at rated engine speed +/- 0.5 V to 70 V Peak 10,000 Hz (max) at rated engine speed. 16 Amp DC at supply voltage. 16 Amp DC at supply voltage. 5 Amp DC at supply voltage. 192 X 144 X 138 0 V to 35 V -30 to +70C 2.5VA 5A Class 1 Recommended BS EN 50081-2 EMC Generic Emission Standard (Industrial) BS EN 50082-2 EMC Generic Emission Standard (Industrial) BS EN 60950 BS EN 60068-2-1 to -30 oC BS EN 60068-2-2 to +70oC BS2011-2-1 to 93% RH@40oC for 48 Hours BS EN60068-2-6 10 sweeps at 1 octave/minute in each of 3 major axes. 5Hz to 8Hz @ +/-7.5mm constant displacement 8Hz to 500Hz @ 2gn constant acceleration BS EN 60068-2-27 3 Half sine shocks in each of 3 major axes 15gn amplitude, 11mS duration
Shock
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
10 7. COMMISSIONING
10.1.1 7.1 PRE-COMMISSIONING
Before the system is started, it is recommended that the following checks are made:-
7.1. The unit is adequately cooled and all the wiring to the module is of a standard and rating compatible with the system. 7.2. The unit DC supply is fused and connected to the battery and that it is of the correct polarity. 7.3. The Emergency Stop input is wired to an external normally closed switch connected to DC positive.
NOTE:- If Emergency Stop feature is not required link this input to the DC Positive. The module will not operate unless either the Emergency Stop is fitted correctly OR Pin 3 is connected to DC positive (+ve)
7.4. To check the start cycle operation take appropriate measures to prevent the engine from starting (disable the operation of the fuel solenoid). After a visual inspection to ensure it is safe to proceed, connect the battery supply. Select MANUAL, the unit start sequence will commence. 7.5. The starter will engage and operate for the pre-set crank period. After the starter motor has attempted to start the engine for the pre-set number of attempts the LCD will display its icon indicating; Shutdown Failed to start. Select the STOP/RESET position to reset the unit. 7.6. Restore the engine to operational status (reconnect the fuel solenoid), again select MANUAL, this time the engine should start and the starter motor should disengage automatically. If not then check that the engine is fully operational (fuel available, etc.) and that the fuel solenoid is operating. The engine should now run up to operating speed. If not, and an alarm is present, check the alarm condition for validity, then check input wiring. The engine should continue to run for an indefinite period. It will be possible at this time to view the engine and alternator parameters - refer to the Description of Controls section of this manual. 7.7. Select AUTO on the front panel, the engine will run for the pre-set cooling down period, then stop. The generator should stay in the standby mode. If not check that there is not a signal present on the Remote Start input. 7.8. Initiate an automatic start by supplying the remote start signal. The start sequence will commence and the engine will run up to operational speed. Once the generator is available a load transfer will take place, the Generator will accept the load. If not, check the wiring to the Generator Contactor Coil (if used). Check the Warming timer has timed out. 7.9. Remove the remote start signal, the return sequence will start. After the pre-set time period, the load will be removed from the generator. The generator will then run for the pre-set cooling down period, then shutdown into its standby mode. 7.10. If despite repeated checking of the connections between the 560 and the customers system, satisfactory operation cannot be achieved, then the customer is requested to contact the factory for further advice on:-
INTERNATIONAL TEL: +44 (0) 1723 890099 INTERNATIONAL FAX: +44 (0) 1723 893303 E-mail: Support@Deepseaplc.com
26
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
POSSIBLE REMEDY
Check the battery and wiring to the unit. Check the DC supply. Check the DC fuse. Check DC supply voltage is not above 35 Volts or below 9 Volts Check the operating temperature is not above 70 C. Check the DC fuse. If an Emergency Stop Switch is not fitted, ensure that a positive is connected to the Emergency Stop input. Check emergency stop switch is functioning correctly. Check Wiring is not open circuit. Ensure that Magnetic pick-up screen is only connected at one end, if connected at both ends this enables the screen to act as an aerial and will pick up random voltages. Check engine oil pressure. Check oil pressure switch/sender and wiring. Check configured polarity (if applicable) is correct (i.e. Normally Open or Normally Closed) or that sender is compatible with the 560 Module and is correctly configured. Check engine temperature. Check switch/sender and wiring. Check configured polarity (if applicable) is correct (i.e. Normally Open or Normally Closed) or that sender is compatible with the 560 Module. Check relevant switch and wiring of fault indicated on LCD display. Check configuration of input. Check relevant switch and wiring of fault indicated on LCD display. Check configuration of input. Check wiring of fuel solenoid. Check fuel. Check battery supply. Check battery supply is present on the Fuel output of the module. Check the speed sensing signal is present on the 560 inputs. Refer to engine manual. Check that there is no signal present on the Remote Start input. Check configured polarity is correct. Check Start Delay timer has timed out. If remote start fault, check signal is on Remote Start input. Confirm input is configured to be used as Remote Start. Check wiring to engine heater plugs. Check battery supply. Check battery supply is present on the Pre-heat output of module. Check pre-heat has been selected in your configuration. Check wiring to starter solenoid. Check battery supply. Check battery supply is present on the Starter output of module. Ensure that the Emergency Stop input is at +Ve. Check Warm up timer has timed out. Ensure generator load inhibit signal is not present on the module inputs. Check engine is operating correctly. Check sender and wiring paying particular attention to the wiring to terminal 24 (refer to appendix). Check that sender is compatible with the 560 Module and is correctly configured.
Intermittent Magnetic Pick-up sensor fault Low oil Pressure fault operates after engine has fired
Shutdown fault operates Warning fault operates Fail to Start is activated after pre-set number of attempts to start
Continuous starting of generator when in AUTO Generator fails to start on receipt of Remote Start signal. Pre-heat inoperative
Engine runs but generator will not take load Incorrect reading on Engine gauges
NOTE:- The above fault finding is provided as a guide check-list only. As it is possible for the module to be configured to provide a wide range of different features always refer to the source of your module configuration if in doubt.
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
808 Configuration
Optional 157 Relay Expansion Board
25 26 27
29 34 33
32
31
30
FCC68 - 4 Way
20 21
22
24
23
9 10 11 12 13
18
Oil Sender
Temp Sender
MPU
This Ground connection must be on the engine block and must be a sound electrical connection to the sender bodies. The wire to Terminal 24 must not be used to provide a ground connection to any other device 5
Configurable inputs
28
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
MISCELLANEOUS ITEMS Item Magnetic pickup input present Flywheel teeth Alternator frequency input present Alternator poles Start attempts AC System Enable Fast Loading Check Oil Pressure for engine at rest CT Primary Enable High Current Warning High Current Warning
Value No 190 Yes 4 3 Three Phase, Four Wire Yes Yes 500 Yes 125%
INPUTS Low oil pressure Low oil pressure Shutdown (PSI) High engine temp. High engine temp. Shutdown (oC) Input channel Polarity Auxiliary input 1 Close to activate Auxiliary input 2 Close to activate Auxiliary input 3 Close to activate Auxiliary input 4 Close to activate Auxiliary input 5 Close to Activate OUTPUTS Output channel Auxiliary output 1 Auxiliary output 2 Auxiliary output 3 Expansion output 1 Expansion output 2 Expansion output 3 Expansion output 4 Expansion output 5 Expansion output 6 Expansion output 7 Expansion output 8 LCD Indicators LCD LCD 1 LCD 2 LCD 3 LCD 4
VDO 0-10Bar 20 VDO 120 deg C 110 Type Remote Start Indication Shutdown Warning Warning
Activation time Always Active Active from Safety On Active from Safety On Always active
Polarity Energise Energise Energise Energise Energise Energise Energise Energise Energise Energise Energise
Control source 1 Pre-heat 35 Common alarm 4 Load transfer 00 Unused 00 Unused 00 Unused 00 Unused 00 Unused 00 Unused 00 Unused 00 Unused
Control source 39 Remote start present 43 Auxiliary IP 2 active 44 Auxiliary IP 3 active 45 Auxiliary IP 4 active
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
SYSTEM TIMERS Timer Remote start delay time Remote stop delay time Cranking time Crank rest time Safety on delay time Warm up time Cooling time Fail to stop time ETS solenoid hold time Pre-heat time Sensor fail delay time Smoke limiting time Smoke limiting ramp time Low DC Volts Delay
Mins:secs 0:05 0:30 0:10 0:10 0:10 0:00 0:30 0:30 0:00 0:00 0:02 0:00 0:00 01:00
Speed / Frequency Level Over frequency Overspeed on magnetic pickup Overspeed overshoot during safety on delay Under frequency Under-speed on magnetic pickup Crank disconnect on alternator frequency Crank disconnect on magnetic pickup Voltage Settings Level Undervolts trip Overvolts trip Under Volts Alarm Charge Fail Crank disconnect charge alternator voltage Over Volts Alarm
Value 57.0 Hz 1750 RPM 2% 30.0 Hz 1250 RPM 21.0 Hz 600 RPM
30
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
Display Symbol
Description
Phase - Phase Phase - Phase Phase - Phase Phase - Neutral Phase - Neutral Phase -Neutral Pressure Frequency Temperature Pressure Temperature Speed Phase Phase Phase Voltage Amperes Hours Run Common Alarm
BAR Hz
o
PSI
o
A
V V V V
!
High Current Warning Over Voltage (AC) Under Voltage (AC) Over Voltage (DC) Under Voltage (DC) Auxiliary Indication Auxiliary Alarm (Warning or Shutdown) AC DC
RPM
L1 L2 L3
V A
i
Auto
Stop/Reset Manual
HPA
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
L1 L2 N L2o L3 N L3 L1 N
AV
LCD 4
AUTO
O
Deep Sea Electronics plc
Model 560
32
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
12. APPENDIX
13.5 12.1 SENDER WIRING RECOMMENDATIONS
Using Earth return (single wire) senders
Terminal 22 23 24
23
NOTE:- . It is important that terminal 24 ( sender common ) is soundly connected to an earth point on the ENGINE BLOCK, not within the control panel, and must be a sound electrical connection to the sender bodies.
NOTE:- . If you use PTFE insulating tape on the sender thread when using earth return senders, ensure you do not insulate the entire thread as this will prevent the sender body from being earthed via the engine block.
Terminal 22 23 24
23
NOTE:- . It is important that terminal 24 ( sender common ) is soundly connected to an earth point on the ENGINE BLOCK, not within the control panel .
14 15
33 560 OPERATING MANUAL ISSUE 5 30/08/2007 MR
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
15.1 12.2
The 560 module can be calibrated by using PC with Interface Module 808 . The PC interface 808 kit comprises the following: 808 Interface Module 25 to 9 way adapter FCC 68 (4 Pin) Connecting Lead Floppy disc or CD with configuration software
Refer to technical data sheet on the 157 relay module for further details.
L1 L2 N L2o L3 N L3 L1 N
AV
AUTO
Refer to technical data sheet on the 548 LED module for further details. It is possible to use a mix of 157 and 548 modules to give both relay and LED expansion if required (Please refer to our Technical Support department for details.). 34
560 OPERATING MANUAL ISSUE 5 30/08/2007 MR
DSE Model 560 Automatic Start Engine Management and Instrumentation System Operators Manual
Model 500