Handbook For Solar PV Systems
Handbook For Solar PV Systems
Handbook For Solar PV Systems
Contents
1 2 3 4 5 Solar Photovoltaic (PV) Systems An Overview 1.1 Introduction 1.2 Types of Solar PV System 1.3 Solar PV Technology Crystalline Silicon and Thin Film Technologies Conversion Efficiency Effects of Temperature 1.4 Technical Information Solar PV Systems on a Building 2.1 Introduction 2.2 Installation Angle 2.3 Avoid Shading PV Modules 2.4 Aesthetic and Creative Approaches in Mounting PV Modules 2.5 Solar PV Output Profile 2.6 Solar PV Yield 2.7 Cost of a Solar PV System Appointing a Solar PV System Contractor 3.1 Introduction 3.2 Getting Started Get an Experienced and Licensed Contractor Choosing Between Bids Solar PV System Warranty Regular Maintenance Other Relevant Matters Solar PV System Installation Requirements 4.1 Electrical Installation Licence 4.2 Electrical Safety Standards and Requirements 4.3 Application of Electrical Installation Licence 4.4 Conservation and Development Control Requirements 4.5 Guidelines on Conservation and Development Control 4.6 Structural Safety and Lightning Protection Structural Safety Lightning Protection 4.7 Connection to the Power Grid 4.8 Get Connected to the Power Grid 4.9 Sale of Solar PV Electricity 4.10 Design and Installation Checklist Operations and Maintenance 5.1 Operations of Solar PV Systems 5.2 Recommended Preventive Maintenance Works 4 4 5 6 8 8 9 10 12 12 12 13 14 14 15 15 16 16 17 17 17 17 19 19 20 20 20 21 21 21 22 22 22 22 23 23 27 28 28 29
Appendices
Appendix A Examples of solar pv system on buildings in singapore
A.1 ZERO ENERGY BUILDING @ BCA Academy A.2 POH ERN SHIH (TEMPLE OF THANKSGIVING) A.3 313 SOMERSET CENTRAL A.4 Sentosa Cove A.5 Marina Barrage A.6 Lonza Biologics A.7 Zero Energy House A.8 Tampines Grande 32 34 36 38 40 42 44 46 48 50
A.9 HDB APARTMENT BLOCKS AT Serangoon North Precinct A.10 HDB APARTMENT BLOCKS AT Wellington Circle Precinct
Appendix B
B.1 Engaging a Licensed Electrical Worker 52
Appendix C
C.1 CONTACT INFORMATION 54
Foreword
Cognizant of the growing popularity of solar photovoltaic (PV) installations amongst residential dwellers as well as building developers, and the corresponding demand for a comprehensive set of technical and regulatory information, the Energy Market Authority (EMA) and the Building Construction Authority (BCA) got together earlier this year to work on integrating their respective solar manuals into an all-in-one reference guide for those who are keen on installing solar PV systems in Singapore. The outcome of this joint project, which also saw the involvement of industry partners and stakeholders such as Phoenix Solar Pte Ltd, Grenzone Pte Ltd, Solar Energy Research Institute of Singapore (SERIS) and Singapore Polytechnic, is this Handbook for Solar Photovoltaic (PV) Systems. Through this integrated and revised handbook, we hope to be able to provide a comprehensive guide to the relevant parties, including owners, developers, engineers, architects, Licensed Electrical Workers and electricians on the key issues, requirements and processes pertaining to the installation of solar PV systems. As with the previous edition of the handbooks, this single volume covers and provides information on licensing, market and technical requirements, and building and structural issues that are related to the implementation of solar PV systems in a building environment. In addition, it provides new information on the installation requirements for solar PV systems, operations and recommended preventive maintenance works, and various incentives to promote solar PV systems in Singapore. We have also refreshed the presentation of the handbook to make it more accessible and readerfriendly, as well as to incorporate examples of completed solar PV installations in Singapore. We hope you will find this to be a useful guide.
David Tan Deputy Chief Executive Energy Planning and Development Division Energy Market Authority
Ang Kian Seng Director Centre of Sustainable Building & Construction Building and Construction Authority
Acknowledgements
We would like to thank the following organisations for their support and contributions in the development of this handbook:
1) Grenzone Pte Ltd 2) Phoenix Solar Pte Ltd 3) Singapore Polytechnic 4) Solar Energy Research Institute of Singapore (SERIS) 5) SP PowerGrid 6) Urban Redevelopment Authority
1
1.1 Introduction
4
The sun delivers its energy to us in two main forms: heat and light. There are two main types of solar power systems, namely, solar thermal systems that trap heat to warm up water, and solar PV systems that convert sunlight directly into electricity as shown in Figure 1.
When the PV modules are exposed to sunlight, they generate direct current (DC) electricity. An inverter then converts the DC into alternating current (AC) electricity, so that it can feed into one of the buildings AC distribution boards (ACDB) without affecting the quality of power supply.
A building has two parallel power supplies, one from the solar PV system and the other from the power grid. The combined power supply feeds all the loads connected to the main ACDB. The ratio of solar PV supply to power grid supply varies, depending on the size of the solar PV system. Whenever the solar PV supply exceeds the buildings demand, excess electricity will be exported into the grid. When there is no sunlight to generate PV electricity at night, the power grid will supply all of the buildings demand.
1.3
Solar PV Technology This section gives a brief description of the solar PV technology and the common technical terms used. A solar PV system is powered by many crystalline or thin film PV modules. Individual PV cells are interconnected to form a PV module. This takes the form of a panel for easy installation.
PV cells are made of light-sensitive semiconductor materials that use photons to dislodge electrons to drive an electric current. There are two broad categories of technology used for PV cells, namely, crystalline silicon, as shown in Figure 4 which accounts for the majority of PV cell production; and thin film, which is newer and growing in popularity. The family tree in Figure 5 gives an overview of these technologies available today and Figure 6 illustrates some of these technologies.
Thin Film
Special
Poly-crystalline
Mono-crystalline
Commercially available product, suitable for Singapore R&D or pilot stage, or unsuitable for Singapore
Dye-sensitised (TiO2)
Mono-crystalline silicon
Poly-crystalline silicon
Crystalline Silicon and Thin Film Technologies Crystalline cells are made from ultra-pure silicon raw material such as those used in semiconductor chips. They use silicon wafers that are typically 150-200 microns (one fifth of a millimetre) thick. Thin film is made by depositing layers of semiconductor material barely 0.3 to 2 micrometres thick onto glass or stainless steel substrates. As the semiconductor layers are so thin, the costs of raw material are much lower than the capital equipment and processing costs. Conversion Efficiency Technology Mono-crystalline Silicon Poly-crystalline Silicon Copper Indium Gallium Selenide (CIGS) Cadmium Telluride (CdTe) Amorphous Silicon (a-Si) Module Efficiency 12.5-15% 11-14% 10-13% 9-12% 5-7%
Table 1. Conversion efficiencies of various PV module technologies Apart from aesthetic differences, the most obvious difference amongst PV cell technologies is in its conversion efficiency, as summarised in Table 1. For example, a thin film amorphous silicon PV array will need close to twice the space of a crystalline silicon PV array because its module efficiency is halved, for the same nominal capacity under Standard Test Conditions1 (STC) rating.
Standard Test Conditions refer to the following testing conditions: 1,000W/m2 of sunlight 250C cell temperature Spectrum at air mass of 1.5
Figure 8. PV String
Figure 9. PV Array
1.4
Technical Information Single-core, double isolated sheathed cables that can withstand the environmental conditions, and minimise the risk of earth faults and short circuits are used to interconnect the PV strings and arrays. The cable connections are protected in enclosures known as junction box that provides the necessary connectors as shown in Figure 10.
Electricity produced by the solar PV installation is in the form of DC. The output of the PV installation is connected through the DC main cables to the DC terminals of the PV inverter where electricity is converted from DC into AC. After conversion, the AC current of the PV inverter is connected through PV supply cable to the buildings electrical installation (AC distribution board). Figure 11 shows a typical PV inverter connected to the electrical installation of a building. Note that the actual configuration of the PV inverter may vary across different systems.
10
DC Side
AC Side
PV Inverter
AC Distribution Board
PV DC Main Cable
PV Supply Cable
Just like any electrical installation in a building, earthing is an important safety requirement for solar PV system. Arrangement must be made for proper connection of the solar PV system to the consumers electrical installation earthing system. In locations susceptible to lightning strikes, a lightning protection system must be provided, and all the exposed metallic structures of the solar PV system must be bound to the lightning earthing system. It is the responsibility of the consumers to have their solar PV systems maintained regularly to ensure safe operation of their solar PV systems and electrical installations. See Figure 12 for a diagram showing the solar PV system forming part of a consumers electrical installation.
2
2.1 Introduction 2.2 Installation Angle
12
There are many examples overseas where PV modules are mounted on the roof and integrated into building faades. They work particularly well in Europe and North America, as south-facing faades in these regions are well exposed to the sun.
In Singapore, we have to consider that the sun passes almost directly overhead. This is because we are located near the Equator, and the path of the sun follows the Equator, o with seasonal variations of up to 23.5 to the north or south. Therefore there are optimal positions to locate the PV modules that have to be taken into consideration. Refer to Appendix A for examples of solar PV systems on buildings in Singapore.
To maximise electricity production for use in Singapore, the best location for the PV modules to be installed is right on top of a building, facing the sky. The possible installation options are shown in Figure 13.
Figure 14. PV module frames trap dirt as water evaporates from a flat-mounted PV module
2.3
Avoid Shading PV Modules PV modules should be free from shade. Shading of any single cell of a crystalline silicon PV module will drastically reduce the output of the entire PV module. Thin film PV modules are more tolerant to partial shading than crystalline silicon PV modules. Typical culprits include shadows cast by tall trees and neighbouring buildings.
13
2.5
Solar PV Output Profile Solar PV only produces electricity when sunlight is available. The output of a solar PV system varies with its rated output, temperature, weather conditions, and time of the day. The power output profile of the PV installation as shown in Figure 17, at a selected test site in Singapore collected over a period from 2002-2004, in terms of its capacity factor2 , shows a high variation of solar PV output.
[2] PV Output capacity factor = Ratio of the actual output of the PV installation at time (t) over its output if it had operated at full rated output. 14
Figure 17. Varying daily power output profile of PV installation at a selected test site in Singapore
2.6
Solar PV Yield The amount of electricity you are able to generate from a solar PV system depends not only on the availability of sunshine but also on the technology you choose to install. For example, a typical 10-kW rooftop solar PV system in Singapore would produce about 11,000 to 12,500 kWh annually using crystalline PV modules, and 12,000 to 14,500 kWh annually with amorphous silicon thin film PV modules. Cost of a Solar PV System The cost of your solar PV system will depend on many factors: system configuration, equipment options, labour cost and financing cost. Prices also vary depending on factors such as whether or not your home is new, and whether the PV modules are integrated into the roof or mounted on the roof. The cost also depends on the system size or rating, and the amount of electricity it produces. Generally, solar PV systems entail high capital costs. With solar power, you can save on the purchase of electricity from the grid. But even with these savings, it will take a long time to recover the capital cost of the solar PV installation. The operating costs for solar PV installations are negligible, but the annual maintenance cost beyond the warranty period may amount to 0.5% to 1% of the capital cost of the installation. Therefore on an overall basis, solar PV-derived electricity is still much more expensive than that from the power grid. However, the cost of solar PV has historically been falling by about 4% a year, and if this continues, solar PV may be competitive within the next 10 years. For incentives on solar PV system, please refer to Appendix D.
2.7
15
3
3.1 Introduction
16
You will need to select a contractor to install your solar PV system. If interested, you may check with the following organisations for some solar PV system designers and contractors: The List of Solar PV System companies in Singapore, available from Sustainable Energy Association of Singapore, by calling 6338 8578 or by visiting http://www.seas.org.sg/about-seas/our-committees/cleanenergy/54 The Singapore Sustainable Development Industry Directory 2008/2009, available from the Singapore Business Federation, by calling 6827 6838 or by visiting http://www.sbf.org.sg/public/publications/industrydirectory.jsp Your contractor will appoint a Licensed Electrical Worker (LEW) who will be responsible for the design, installation, testing, commissioning, and maintenance of your solar PV system. In the case of non-residential electrical installations that require an electrical installation licence, the appointed LEW who supervises the electrical work (Design LEW) may not be the one who takes charge of your electrical installation (Installation LEW). The Design LEW will then have to work with the Installation LEW to work out the technical issues. Please refer to Appendix B for details on how you can engage an LEW and the necessary consultation process.
17
Take note that under the limited power warranty, manufacturers seldom offer to replace the PV module itself. Rather, at their sole discretion, they may offer to: Repair the defective PV modules; Supply enough new PV modules to replace the lost power output in a PV array. For example, if your 20kW PV array only produces 16.1kW under STC, six years after installation, the manufacturer may opt to supply you with 1kW of PV modules to make up for the shortfall; or Refund you for the lost power output, after deduction according to the number of years in use. For a 25-year warranty, the annual deduction is normally 4%. For example, if you find that your 20kW PV array only produces 16.1kW under STC, six years after installation, the manufacturer may opt to reimburse your purchase price minus 24% (6 years x 4%).
In all cases, the manufacturer does not cover your costs of dismounting, transporting, and reinstalling the PV modules. The warranty also excludes problems resulting from improper installations; repairs, changes or dismounting by unqualified personnel; accidental breakage or abuse; lightning strikes and other acts of God.
18
19
4
4.1 4.2
20
An electrical installation refers to any electrical wiring, fitting or apparatus used for the conveyance and control of electricity in any premises. A solar PV system installed within such premises forms part of the consumers electrical installation and should comply with the requirements stipulated in the Electricity Act (Cap. 89A), the Electricity (Electrical Installations) Regulations and the Singapore Standard CP5 Code of Practice for Electrical Installations. Under the Electricity Act, the Energy Market Authority (EMA) licenses all nonresidential electrical installations, with demand exceeding 45 kilo volt ampere or kVA. For residential electrical installations and non-residential electrical installations with demand below the threshold 45kVA, no electrical installation licence is required. The licence requires the owner of the electrical installation to engage an LEW to take charge of the electrical installation and comply with the relevant safety standards and requirements. Your appointed LEW shall consult SP PowerGrid Ltd on their technical requirements and procedures, if you wish to operate your solar PV system in parallel with the power grid. The objective is to ensure all electrical installations, including solar PV systems, are safe to use. Electrical Safety Standards and Requirements A grid-connected solar PV system operates in parallel with the power grid supply. The power grid supply is considered the source, and the electrical installation with the solar PV system connected is considered as the load. The technical requirement for installation of a solar PV system is given in Section 612 of the Singapore Standard CP5. There are international product standards on PV modules and electrical components. For example, PV modules should comply with the requirements of IEC 61215 for crystalline silicon terrestrial PV modules or IEC 61646 for thin-film terrestrial PV modules. In addition, PV array junction box, PV generator junction box and switchgear assemblies should comply with the requirements of IEC 60439-1.
4.4
4.5
Should you have further enquiries on whether your installations conflict with the Urban Design or Development Control guidelines, you may submit your enquiries to URA either in person or through a Qualified Person (QP) a QP is either a registered architect or an engineer with the accompanying plans of the structures on which the solar PV system will be installed: Conserved buildings Email: ura_conservation_cso@ura.gov.sg Tel: 6329 3355 Non-conserved buildings Email: ura_dcd@ura.gov.sg Tel: 6223 4811
21
Structural Safety and Lightning Protection Structural Safety To ensure safety, there are measures and steps that need to be taken or considered when installing a solar PV system onto a new or an existing building. For new building developments, the design of the structure must take into consideration the loading of the solar PV system installation, just like any other equipment mounted onto a building structure. For existing buildings, a professional structural engineer may be required to carry out an inspection of the roof structure, and do a calculation on the structural loading. If the roof is unable to withstand the loading of the solar PV system, structural plans will need to be submitted to the Building and Construction Authority (BCA) for approval before a building permit can be issued for commencement of installation works. The application guideline is available at the following BCAs website: http://www.bca.gov.sg/StructuralPlan/structural_plan_application.html
Lightning Protection Given a certain location, solar PV systems are exposed to the threat of lightning strikes. As lightning can cause damage to the PV modules and inverters, extra care must be taken to ensure that proper lightning protection is provided for the solar PV system and the entire structure. The inverters should be protected by appropriately rated surge arrestors on the DC side. It is good practice to also install surge arrestors on the AC side. Structures and PV module frames must be properly grounded. Connection to the Power Grid If a solar PV system is designed to meet only a fraction of the electricity load, the system will need to be interconnected with the power grid to meet the remainder of the consumers needs for electricity. If a solar PV system needs to be grid-connected, interconnection is key to the safety of both consumers and electrical workers, and to the protection of equipment.
4.7
22
SPPGs handbook, How to Apply for Electricity Connection, is published at SP PowerAssets website: http://www.sppowerassets.com.sg/PDF/howtoapply.pdf
4.9
Sale of Solar PV Electricity The excess electricity generated from a grid-connected solar PV can be sold back to the power grid. The arrangements needed to enable this sale of solar PV electricity vary, depending on whether you are a contestable or non-contestable consumer. Consumers are classified, based on their average monthly electricity consumption, into: Contestable consumers: These consumers are the non-residential consumers who use more than 10,000 kWh of electricity a month. Contestable consumers have a choice of who they wish to buy their electricity from. They may purchase electricity from a retailer, directly from the wholesale market (provided they are registered with the Energy Market Company as market participants) or indirectly from the wholesale market through SP Services. Non-contestable consumers: These consumers comprise all the residential electricity users and non-residential consumers who use less than 10,000 kWh of electricity a month. These consumers are supplied with electricity by SP Services. Contestable Consumers If you are a contestable consumer generating electricity from a solar PV system and wish to sell and get paid for the electricity you inject into the power grid, you will be required to register with the Energy Market Company (EMC) to participate in the wholesale electricity market, which is called the National Electricity Market of Singapore or NEMS.
23
Yes
Yes
Yes
The application procedures to register as a Market Participant with the EMC and for generation facility registration are set out in the Market Manual: Market Administration Registration and Authorisation, which is available at the EMC website: http://www.emcsg.com/MarketRules/MarketManuals
As a Market Participant, you will need to comply with the Market Rules, which is available at EMCs website: http://www.emcsg.com/MarketRules
By selling electricity in the wholesale electricity market, you will be paid the prevailing electricity spot price for the electricity that you inject into the power grid. The electricity spot price varies every half-hour, depending on the demand-supply situation in the wholesale electricity market. The market will also offer services and system resources to you, but you will be subjected to market charges in respect to the gross generation output from your registered PV system, for the provision of the market services and system resources.
24
Non-Contestable Consumers If you are a non-contestable consumer generating electricity of less than 1 MW and wish to sell and get paid for the electricity you inject into the power grid, you need not apply for a Generation or Wholesaler (Generation ) Licence nor register with the EMC as a market participant. You will have to apply to SP Services (SPS) by following the application procedure set out in Appendix B. Non-contestable consumers are compensated by SPS for electricity exported to the power grid by way of a credit adjustment to the consumers monthly electricity bill, based on the prevailing low-tension electricity tariff less the grid charge. The credit adjustment will effectively compensate the non-contestable consumer for the amount of electricity exported into the power grid during that month. This scheme to compensate non-contestable consumers with generation capacity of less than 1MW for the electricity they export into the power grid is not applicable to those consumers whose electricity consumption is metered under the master-sub metering scheme. Master-sub metering schemes refer to metering arrangements where there is a master-meter measuring the overall electricity consumed by the building (i.e. both the individual units and the common services), with sub-meters measuring the usage of the individual units. Such metering schemes are typically used in private condominiums and commercial buildings. Under a master-sub metering arrangement, the electricity that an individual unit attempts to export into the grid may in fact be used up by the common services or by other individual units. As it is not possible to track the actual flow of the electricity exported by the individual units, the credit adjustment scheme cannot be applied to those under the master-sub metering scheme.
25
No. Design and Installation Checklist 1 2 3 4 Set your budget and select a location.
Determine the energy requirement and estimate the size of the system. Perform a site survey for space needed, and access for maintenance. Engage a licensed electrical worker (LEW) if your proposed solar PV system: i) is to be connected to the electrical installation within the premises of the building; and /or ii) to be connected and operated in parallel to the power grid.
The appointed LEW will be responsible for the design and implementation of the connection of your solar PV system to the electrical installation and/or power grid. 5 Select a PV module type and mounting method. 6 Select inverter to match PV array: i) Number of inverters needed; ii) Select inverter type; and iii) Location of inverters (accessible for inspection and maintenance). 7 Finalise the mounting system. 8 Ensure there are fixing and mounting points available. 9 Ensure the structure for mounting is safe: i) Additional loading by solar PV system is considered; ii) Wind loading is considered; and iii) Waterproofing is not compromised during installation. 10 Ensure solar access: i) Ensure location to be mounted will get maximum exposure to sunlight; and ii) Choose a location that is not shaded.
26
13 Ensure sufficient ventilation space behind the PV array for cooling purposes. 14 Ensure: i) Cabling used meet sufficient current-carrying capacity and are suitably rated for usage in the environment; ii) DC cables are single-core and double-insulated; and iii) Cable insulation on outdoor cables must withstand high temperature and UV exposure for an estimated period of more than 20 years. Note that PVC and XLPE cables are inadequate on the DC side and must not be exposed to the weather elements. 15 Determine if a Lightning Protection System is needed. 16 Ensure the PV module frame is earthed. 17 Finalise the Inverter and AC wiring system. 18 During installation: i) PV system should be installed by qualified/experienced installers; ii) Safety rules must be observed; iii) Installer must wear PPE; and iv) Only proper certified safety equipment can be used e.g. scaffolding, stepladders, etc. 19 Cables must be properly connected, secured, and routed. 20 Ensure continuity and insulation tests are done. 21 Completion of testing and system commissioning. 22 Proper system, documentation/manual handover to clients.
27
5
5.1
28
Operations of Solar PV Systems The most practical indicator of the performance of the solar PV systems can be obtained from the remote monitoring and data logging software supplied by most inverter manufacturers. The data logging software will record daily, monthly, and annual output for comparison of the actual system performance against the expected system performance. See Figure 20 for typical performance monitoring displays.
Solar PV systems require minimal maintenance, as they do not usually have moving parts. However, routine maintenance is required to ensure the solar PV system will continue to perform properly. It is a good practice for contractors of solar PV systems to provide an operation & maintenance (O&M) manual for the client. The manual should include basic system data, test and commissioning data, O&M data, and warranty information.
2 PV inverter
Clear dust and dirt in ventilation system Tighten connection Recommend replacement
29
6 Earthing of solar PV system Check earthing cable conditions Check the physical earthing connection
Recommend replacement Retighten connection Troubleshoot or recommend replacement Recommend replacement Tighten connection Troubleshoot or recommend replacement
Check continuity of the cable to electrical earth 7 Bonding of the exposed Check bonding cable metallic structure of solar conditions PV system to lightning earth Check physical bonding connection Check continuity of the bonding to lightning earth
30
Appendices
31
Appendix
Building name Owner Location Building type Completion Working groups Project architects Principal investigators Structural engineers M&E engineers Quantity surveyor Contractors PV design PV manufacturer Type of PV integration Type of PV cell technology PV area (m2) PV system peak power (kWp) Estimated energy output (kWh / yr) PV Yield (kWh / kWp / year) Photographs and information courtesy of
A
: Academic Institution : 2009 : : : : : : : : : 1,540 : 190 : 207,000 : 1,090 : BCA / Grenzone Pte Ltd
: Zero Energy Building @ BCA Academy : Building and Construction Authority (BCA) : 200 Braddell Road, Singapore 579700
DP Architects Pte Ltd National University of Singapore / SERIS Beca Carter Hollings & Ferner (S. E. Asia) Pte Ltd Beca Carter Hollings & Ferner (S. E. Asia) Pte Ltd Davis Langdon & Seah Singapore Pte Ltd ACP Construction Pte Ltd Grenzone Pte Ltd Various (7 manufacturers)
: on Metal Roof, Canopy, Louver, Railing, Faade : Various (mc-Si, pc-Si, a-Si, HIT, CIGS)
32
The Solar Photovoltaic System installed at BCA Academys Zero-Energy Building (ZEB) consists of 12 systems with six systems connected to grid and six standalone systems. Featuring different types of Solar PV technology and mounting techniques, the ZEB @ BCA Academys Solar PV system is designed to achieve zero-energy and for advance academic research on various PV performances.
33
Appendix
Building name Owner Location Building type Completion Working groups Project architects Structural engineers M&E engineers Quantity surveyor Contractors PV design PV manufacturer Type of PV integration
A
: POH ERN SHIH : Religious : 2006 (Phase I) : KTP Consultants Pte Ltd : Squire Mech Pte Ltd : Grenzone Pte Ltd : Uni-Solar, Sharp, Mitsubishi : Standing Mounting Structure : 2.232 : 2,566 : 1,150 5.250 6,036 1,150
Type of PV cell technology : Amorphous Monocrystalline silicon silicon : 36.1 39.2 PV area (m2) PV system peak power (kWp) Estimated energy output (kWh / yr) PV Yield (kWh / kWp / year)
34
The PV arrays are mounted on the rooftop with standing mounting structure, allowing sufficient ventilation to improve PV performance. About 25% of electrical power demand in the building are supplied by the solar PV system.
35
Appendix
Building name Owner Location Building type Completion Working groups Project architects Structural engineers M&E engineers Quantity surveyor Contractors PV design PV manufacturer Type of PV integration Type of PV cell technology PV area (m2) PV system peak power (kWp)
A
: 313 SOMERSET CENTRAL : Shopping Mall : 2009 : Aedas Pte Ltd : WT Partnership Pte Ltd : Bovis Lend Lease Pte Ltd : Grenzone Pte Ltd : Various (4 manufacturers) : on Trellis and Metal Roof : 587 : 76 : 1,150
: Lend Lease Retail Investment 1 Pte Ltd : 313 Orchard Road, Singapore 238895
Estimated energy output (kWh / year) : 87,381 PV Yield (kWh / kWp / year)
36
313 Somerset Central is centrally located in the heart of Singapores famous Orchard Road. The solar photovoltaic system consists of four PV arrays, with a main PV array of 60 kWp mounted on the trellis, and three smaller arrays featuring monocrystalline, polycrystalline and micromorph solar modules that are accessible by visitors.
37
Appendix
Building name Owner Location Building type Completion Working groups Project architects M&E consultant PV design Main contractors Roofing contractor PV manufacturer Type of PV integration Type of PV cell technology PV area (m2) PV system peak power (kWp) Estimated energy output kWh / yr) PV Yield (kWh / kWp / yr) Photographs and information courtesy of
A
: Private : Private : Sentosa Cove, Singapore : Two-storey bungalow with basement : July 2008 : Guz Architects : Herizal Fitri Pte Ltd : Phoenix Solar Pte Ltd : Sunho Construction Pte Ltd Sheet Metal International : Uni-Solar : Glued onto approved Fazonal metal roof : Flexible amorphous silicon : 92 : 5.712 : 7,100 : 1,250 : Phoenix Solar Pte Ltd, Guz Architects, and Sheet Metal International
38
This striking house stands out for its open layout, capped with twin curved roofs. The rear roof has a turf lawn to keep it cool, while the front roof generates electricity with flexible solar laminates, bonded unobtrusively on top. This configuration meets Sentosa Resort Managements strict guidelines for roof aesthetics, which do not generally permit bare metal roofs on bungalow developments. Thanks to the laminates light weight (less than 4kg/m2), the roof can make do with a lighter and lower substructure cost than if it had to carry conventional clay tiles.
39
Appendix
Building name Owner Location Building type Completion Working groups Project architects Structural engineers PV design Building services Contractors PV manufacturer Type of PV integration Type of PV cell technology PV area (m2) PV system peak power (kWp) Estimated energy output (kWh / yr) PV Yield (kWh / kWp/ yr)
A
: Marina Barrage : Singapore : Flood Control : 2008 : Architects Team 3 Pte Ltd : Cegelec Pte Ltd : Roof Top : Monocrystalline silicon : 1200 : 70 : 76,650 : 1,095
: Koh Brothers Building & Civil Engineering Contractor (Pte) Ltd : Renewpowers Technologies Pte Ltd
: Koh Brothers Building & Civil Engineering Contractor (Pte) Ltd : SolarWorld Asia Pacific Pte Ltd
40
Marina Barrage spans the mouth of the Marina Channel, creating Singapores 15th reservoir, and its first in the city. The barrage creates a freshwater lake to boost Singapores water supply, acts as a tidal barrier to prevent flooding in low-lying city areas, and keeps the water level consistent, offering a venue for water-based activities in the heart of the city. But more than an engineering showpiece, the barrage exemplifies the national water agencys commitment towards environmental and water sustainability. One of Singapores largest commissioned solar PV system at a single site to date, Marina Barrages solar park houses one of the largest collection of solar panels 405 panels in all currently in operation in Singapore. Its 70kWp DC grid-tied solar PV system is the first to be employed on such a large scale locally, and it comes with aesthetically arranged solar panels (panels are arranged in nine arrays of 15 by three panels) on the barrages green roof. The solar panels generate 50% of utility grade electricity for lighting and general power in the visitor centre, control room and offices. The environmentally-friendly gridtied solar PV system does not require batteries, hence eliminating the costs for battery replacement.
Appendix
Building name Owner Location Building type Completion Working groups Project architects M&E engineers PV design Contractors PV manufacturer Type of PV integration Type of PV cell technology PV area (m2) PV system peak power (kWp) Estimated energy output (kWh/yr) PV Yield (kWh/kWp/yr) Photographs and information courtesy of
A
: LBXS2 : Lonza Biologics Tuas Pte Ltd : Tuas, Singapore : Biotech factory and laboratory : May 2009 : RSP Architects Planners & Engineers Pte Ltd : Jacobs Engineering Singapore Pte Ltd : Phoenix Solar Pte Ltd : Bovis Lend Lease Pharmaceutical Pte Ltd : REC (framed modules) and Solar-Fabrik (frameless laminates) : Roof mounted on Bluescope Lysaght KlipLok metal roof : Polycrystalline silicon : 1,330 : 181 : 217,000 : 1,200 : Phoenix Solar Pte Ltd and Lonza Biologics Tuas Pte Ltd
42
Figure A.6.1. Building exterior (Rendering by RSP Architects Planners & Engineers Pte Ltd)
The curved laboratory roof of the Lonza Biologics LBXS2 factory offers prominent visibility to maximise public awareness for a 181kWp solar PV system on an industrial building. The bulk of the PV array consists of 744 pieces of REC210 modules, while the flatter upper section of the roof is covered with 104 SF130/2 frameless laminates from Solar-Fabrik. Without frames to trap water at shallow installation angles, these laminates will avoid dirt accumulation. Roof clamps were specially engineered to attach the PV module rails to the KlipLok roof seams without any penetrations. Lonza Biologics was a recipient of one of the inaugural Solar Pioneer grants under EDBs Solar Capability Scheme.
43
Appendix
Building name Owner Location Building type Completion (renovation) Working groups Project architects Structural engineers PV design Contractors PV manufacturer Type of PV integration Type of PV cell technology PV area (m )
2
A
: Zero Energy House : Private : District 15, Singapore : Residential, 21/2-storey semi-detached house : April 2008 : Art & Architecture Collaborative : Portwood & Associates : Phoenix Solar Pte Ltd : MCL Construction & Engineering Pte Ltd : Mitsubishi Heavy Industries and Phoenix Solar : Roof mounted on metal roof : amorphous silicon and micromorph silicon thin films : 120 : 8.58 : 1,400
44
This 1960s semi-detached house was converted into Singapores first modern zero-energy home by reducing solar heat gain, improving natural ventilation and adding a rooftop solar PV system, which generates more electricity than the 6-person household consumes. The PV modules are mounted on rails that are clamped to the seams of the aluminium Kalzip roof without any roof penetrations. As an important added benefit, the PV modules shade the roof, keeping the attic rooms much cooler than they would be under a roof fully exposed to the sun.
Appendix
Building name Owner Location Building type Completion Working groups Project architects M&E engineers PV design Contractors PV manufacturer Type of PV integration Type of PV cell technology PV area (m )
2
A
: Tampines Grande : City Developments Ltd : Tampines, Singapore : Office building : May 2009 : Architects 61 Pte Ltd : Conteem Engineers Pte Ltd : Phoenix Solar Pte Ltd : Dragages Singapore Pte Ltd / BYME Singapore : Suntech (rooftop) and Schott Solar (BIPV) : Roof mounted and Building Integrated faade : Monocrystalline silicon and amorphous silicon thin film BIPV : 934 : 107 : 120,000 : 1,200 : Phoenix Solar Pte Ltd and City Developments Ltd
PV system peak power (kWp) Estimated energy output (kWh/yr) PV Yield (kWh/kWp/yr) Photographs and information courtesy of
46
101kWp of monocrystalline PV modules form the main rooftop PV array on Towers 1 and 2, while the west faade of Tower 2 has 6kWp of BIPV comprising 40 large, custom-built amorphous silicon thin film modules. At the time of completion, this was Singapores largest PV system, and the first commercial application of a thin film BIPV faade. The building also boasts a solar air-conditioning system powered by solar thermal collectors. Tampines Grande was a recipient of one of the inaugural Solar Pioneer grants under EDBs Solar Capability Scheme.
47
Appendix
Building Name Owner Location Building type Completion Working groups Contractors PV manufacturer Type of PV integration Type of PV cell technology Precinct PV area (m2)
A
: Residential : 2008 : Roof top : Mono-crystalline silicon : 667.61 : 80,300 : 1,060
: HDB Apartment Blocks at Serangoon North Precinct : Ang Mo Kio- Yio Chu Kang Town Council : Serangoon North Avenue 3 Block 548 to 554 and 550A (Multi-storey Carpark)
: King Wan Construction Pte Ltd & Asiatic Engineering Pte Ltd : Sunset Energietechnik GmbH
Precinct PV system peak power (kWp) : 75.75 Estimated energy output (kWh / yr) PV Yield (kWh / kWp/yr)
48
The Serangoon North Precinct consists of five blocks of 16 storey and two blocks of nine storey residential apartments and a multi storey car park (MSCP). Sixty-nine pieces of solar PV panels are mounted at the rooftop of each residential block and 22 pieces of the panel at the staircase roof of the MSCP.
49
Appendix
Building Name Owner Location Building type Completion Working groups Contractors PV manufacturer Type of PV integration Type of PV cell technology Precinct PV area (m2)
A
: Sembawang Town Council : Residential : 2008 : Roof top : Mono-crystalline silicon : 667.61 : 80,300 : 1,060
: King Wan Construction Pte Ltd & Asiatic Engineering Pte Ltd : Sunset Energietechnik GmbH
Precinct PV system peak power (kWp) : 75.75 Estimated energy output (kWh / yr) PV Yield (kWh / kWp/ yr)
50
The Wellington Circle Precinct consists of seven blocks of 12 storey residential apartments and a MSCP. Sixty-nine pieces of solar PV panels are mounted at the rooftop of each residential block and 22 pieces of the panel at the staircase roof of the MSCP.
51
Appendix
1.
B
Approved Load Not exceeding 45 kVA Voltage Level 1000V & below 1000V & below No limit Subject to license conditions
1.1 There are three classes of LEWs: Licensed Electrician, Licensed Electrical Technician, and Licensed Electrical Engineer. The various classes of LEWs are authorised to design, install, repair, maintain, operate, inspect and test electrical installations according to the conditions stated below: Class of LEW Electrician
Electrical Technician Not exceeding 150 kVA (Design); not exceeding 500 kVA (Operation) Electrical Engineer
1.2 The Singapore Standard for electrical safety applicable to solar PV Systems is set out in the Code of Practice for Electrical Installations (Singapore Standard CP5:2008), which is published by SPRING Singapore. The LEW whom you appoint to carry out or supervise the electrical works associated with your PV system will be responsible for the compliance with the relevant safety standards and requirements. 1.3 You can search for LEWs and their contact particulars at the following EMA website: http://elise.ema.gov.sg 1.4 For enquiries on LEWs, you can contact EMAs Electricity Inspectorate Branch at: Tel: 6835 8060 Email: ema_enquiry@ema.gov.sg
52
53
Appendix
For enquiries on the following matters pertaining to Solar PV systems, please contact: (1) Buildings issues Building And Construction Authority (BCA) Email: bca_equiry@bca.gov.sg Tel: 1800-3425222 (1800-DIAL BCA) (2) (3) (4) (5) (6) (7) (8) Development Planning Control Conserved Buildings Development Planning Control Non-conserved Buildings Electricity Generation Licences Licensed Electrical Workers (LEWs) Electricity market rules, market registration process, and market charges Connection to the power grid Connection to the power grid Urban Redevelopment Authority (URA) Building Conservation Email: ura_conservation_cso@ura.gov.sg Tel: 6329 3355 Urban Redevelopment Authority (URA) Non-conserved buildings Email: ura_dcd@ura.gov.sg Tel: 6223 4811 Energy Market Authority (EMA) Economic Regulation & Licensing Department Email: ema_enquiry@ema.gov.sg Tel: 6835 8000 Energy Market Authority (EMA) Electricity Inspectorate Branch Email: ema_enquiry@ema.gov.sg Tel: 6835 8060 Energy Market Company (EMC) Market Administration Team Email: MPregistration@emcsg.com Tel: 6779 3000 SP Services Ltd (SPS) Email: install@singaporepower.com.sg Tel: 6823 8283 / 6823 8284 SP PowerGrid Ltd (SPPG) Email: dgconnection@singaporepower.com.sg Tel: 6823 8572
54
Appendix
The Economic Development Board (EDB) unveiled the Solar Capability Scheme to spur demand and build up expertise for this young but growing field. The scheme the latest by Clean Energy Programme Office (CEPO) seeks to strengthen critical capabilities of companies engaged in activities such as engineering, architecture and system integration through increased implementation of solar energy technologies by lead users in Singapore.
Agency
: EDB
Quantum : $20 Million (Overall); $1 Million per project or up to 40% of total capital cost of solar technology. Target Group : For Reading For Details Engineering; Architecture; System Integration (With implementation of solar energy technologies)
: http://www.edb.gov.sg/etc/medialib/downloads/industries. Par.98811.File.tmp/Solar%20Capability%20Scheme%20Factsheet.pdf
55
Appendix
The MDF seeks to incentivise the use of clean and renewable energy resources among non-residential consumers and developers by offsetting the market charges and related costs associated with selling clean and renewable energy into the power grid. This will help to promote energy efficiency as well as help in the market integration of innovative clean and renewable energy resources.
: Energy Market Authority (EMA) : $5 million; $50,000 over a span of 5 years or 90% of incurred market charges for approved projects, whichever is lower. : Non-residential consumers and developers who choose to sell excess electricity generated from clean and renewable energy technologies to the power grid.
: http://www.ema.gov.sg/index.php?option=com_content&view=artic le&id=125&Itemid=141
56
Appendix
The Green Mark Scheme was launched to promote environmental awareness in the construction and real estate sectors. It is a benchmarking scheme that aims to achieve a sustainable built environment by incorporating best practices in environmental design and construction, and the adoption of green building technologies.
: Building and Construction Authority (BCA) : Developers Designers Builders : http://www.greenmark.sg http://www.bca.gov.sg/GreenMark/green_mark_buildings.html
: http://www.bca.gov.sg/greenmark/others/gmtc.pdf
57
Appendix
: BCA and URA : All new private developments, redevelopments and reconstruction developments submitted on or after the effective date. : http://www.bca.gov.sg/GreenMark/gmgfa.html
58
Appendix
D.5 $100 million Green Mark Incentive Scheme for existing buildings (GMIS-EB)
The GMIS-EB aims to encourage private building owners of existing buildings to undertake improvements and/or retrofits to achieve substantial improvement in energy efficiency. It provides a cash incentive that cofunds up to 35% (capped at $1.5 million) of the upgrading/retrofitting costs for energy efficiency improvement in their existing buildings.
Agency
: BCA
Target Group : Building owners/developers of private existing non- residential developments that is centrally air-conditioned, with gross floor area of 2,000 sqm above e.g. energy intensive buildings such as shopping malls, hotels, office buildings, hospitals, and other centrally air-conditioned buildings. For Details : http://www.bca.gov.sg/GreenMark/gmiseb.html
59
Appendix
D.6 Enhanced $20 million Green Mark Incentive Scheme for new buildings (GMIS-NB)
The GMIS-NB is to help accelerate the adoption of environmentallyfriendly green building technologies and building design practices. The enhanced scheme offers cash incentives.
: BCA : Developers, building owners, project architects and M&E engineers who make efforts to achieve at least a BCA Green Mark Gold rating or higher in the design and construction of new buildings.
: http://www.bca.gov.sg/GreenMark/GMIS.html
60
Disclaimer The information in this handbook is subject to change or revision, to adapt to the continual development and evolvement of the electricity and building and construction industries and is not a substitute for any law, regulation, code of practice, standard of performance, Market Rules or Building Control Act which may apply to the said industries in Singapore. It does not in any way bind the Energy Market Authority (EMA) and the Building and Construction Authority (BCA) to grant any approval or official permission for any matters, including but not limited to the grant of any exemption nor to the terms of any exemption. Both EMA and BCA reserve the right to change its policies and/or to amend any information in this handbook without prior notice. Persons who may be in doubt about how the information in this handbook may affect them or their commercial activities are advised to seek independent legal advice or any other professional advice as they may deem appropriate. Both Authorities assume no responsibility or liability for any consequences (financial or otherwise) suffered directly or indirectly by persons who have entered into commercial activities upon reliance on any information in this document.
61
Energy Market Authority 991G Alexandra Road, #01-29 Singapore 119975 Tel: (65) 6835 8000 Fax: (65) 6835 8020
Building and Construction Authority 5 Maxwell Road #16-00 Tower Block MND Complex Singapore 069110 Main Line: 1800-3425222 (1800-DIAL BCA)
ISBN: 978-981-08-4462-2 62