MITEK ROOF AND FLOOR TRUSS MANUAL

FOR ARCHITECTS AND ENGINEERS

MiTek Industries, Inc. 14515 N. Outer Forty Suite 300 Chesterfield MO 63017 800.325.8075 (Fax) 314.434.5343 www.mii.com
4/05 2.5M

Headquartered in St. Louis, Missouri, MiTek Industries, Inc. is the leading supplier of connector plates, truss manufacturing equipment, design software, and engineering services for the worldwide component industry. For over 35 years MiTek companies have developed and refined their connector plates into the state-of-the-art products they are today...consistent and dependable! With MiTek youre assured of the best quality. MiTek connector plates are manufactured under strict quality control and undergo extensive testing in our R & D facility. MiTeks connector plates meet or exceed all building code and industry association requirements. Acceptances include BOCA, ICBO, HUD/FHA, SBCCI, Dade County, Wisconsin/ DILHR, and LA City.

MiTek also offers the very best in framing layout and engineering software for roof and floor trusses, as well as wall panel design. These programs provide our fabricators with fast and accurate layout and design capabilities. Our engineering department is available to review and seal our customers designs. With offices in NC, Missouri and California, MiTeks professional engineers can furnish seals for all 50 states! Look to a MiTek fabricator for the best the industry has to offer! This brochure reviews the benefits of roof and floor trusses, but MiTek fabricators also offer a full line of builders hardware and a complement of other building components including wall panels and steel framing. At MiTek, we are committed to providing the best products and services in the industry and will continue our tradition of customer support.

TABLE

OF

CONTENTS

PAGE

NO.

Introduction ...........................................................................................................2 Wood Truss Advantages ........................................................................................3 Truss Advantages .................................................................................................. 3 Handling, Installation and Bracing .......................................................................4 Basic Roof Truss Configurations ......................................................................5-6 Construction Details Support Details .................................................................................................7 Joint Details ..................................................................................................... 8 Lateral Bracing Information ............................................................................ 9 Cantilever Framing ........................................................................................ 10 Stairway Framing ...........................................................................................11 Technical Information Architectural Specifications ...........................................................................12 Recommended Depth, Deflection and Camber Limitations ..........................12 Construction Guidelines .................................................................................12 Mechanical Service Guidelines ..................................................................... 13 Cantilever Concentrated Loads ..................................................................... 13 Floor Decking Information ............................................................................ 14 Connector Plate Code Approvals .................................................................. 14 Fire Rating Information ................................................................................. 15 Sound Transmission Ratings ......................................................................... 16 Construction Material Weights ...................................................................... 16 Representative Floor and Roof Loads ........................................................... 16 Floor Loading Max-Span Information ............................................................... 16 Floor Loading Max-Span Tables ........................................................................ 17 Glossary of Terms ..........................................................................................18-19

Joint The intersection of two or more members. (Also referred to as a Panel Point.) Joint Splice A splice of the 4x2 chord member at a chord-and-web joint. Kneewall A short partition stud wall to increase a wall height, typically from the concrete wall plate to the floor decking. Lateral Brace A member placed and connected at right angles to a chord or web member of a truss. Level Return A lumber filler placed horizontally from the end of an overhang to the outside wall to form a soffit. L/D Ratio The ratio of the truss span (L) to its depth (D), both dimensions in inches. Live Load Any temporary applied load to a floor truss chord; typically roof live load is snow, while floor live loads are furniture, human occupancy, storage. Load-Bearing Wall A wall specifically designed to transfer a roof load and/or upper floor load into the foundation. Machine Stress Rated Lumber (MSR) Lumber which has been individually tested by a machine at the lumber mill to determine its structural design properties. MSR Lumber is designated by a flexural (bending) stress and Modulus of Elasticity, e.g., 1650F-1.5E. Moisture Content of Wood The weight of the moisture in wood expressed as a percentage of its oven-dry weight. Moments A structural measure of the effects of bending on a member due to applied loading. Overall Rise Vertical distance from bottommost part of the bottom chord to uppermost point on peak. Overhang The extension of the top chord of a truss beyond the heel measured horizontally. PCT Abbreviation for Parallel Chord Truss, the Truss Plate Institute (TPI) specification designation for trusses with parallel chords and 4x2 chord orientation, titled Design Specification for Metal Plate Connected Parallel Chord 4x2 Wood Trusses. PLF Pounds per lineal foot, acting along a structural member, usually equal to the uniform load (PSF) times the truss spacing. PSF Pounds per square foot of uniform load. Panel Length The distance between the centerlines of two consecutive joints along the top or bottom chord. Panel The chord segment defined by two adjacent joints. Panel Point The point where a web or webs intersect a chord.

Typical Floor Truss


30 Panel 60 Panel Modu;e Truss Depth Span No.1 Overall Truss Length Span No. 2 Cantiveler Length

Peak Point on truss where the sloped top chords meet. Pitch Inches of vertical rise for each 12 inches of horizontal run. Plate A horizontal wood framing member, typically the top and bottom 2x4 members of a stud wall and the 2x6 sill plate bolted to a concrete wall for floor structural attachment. Plenum Typically, the use of the entire floor truss cavity formed by the floor above and the ceiling below as a supply or return air duct. Plumb Cut Top chord end cut to provide for vertical (plumb) installation to fascia (face trim board). Plumb Rise Vertical overall measurements at the end of a truss where the top and bottom chords meet. Pre-Splice Plates Connector Plates pressed into the top and bottom 3-1/2" faces of two 4x2 chord members prior to final floor truss assembly to achieve a structural chord splice. Purlins Secondary structural components, spanning between primary structural members and supporting the decking. 1/4 Point point on triangular, Fink or Howe truss where the webs connect to the top chord. 1/3 Point Point on triangular, Fink truss where the webs connect to the bottom chord. Reaction The total load transferred from the uniform load (PSF) applied to the floor truss deck, then into the floor truss, and ultimately, to the floor truss bearing or support. Ridge Line formed by truss apexes. Rim Joist An exterior transition member supporting the decking edge and wall sheathing, usually tying the ends of floor trusses together. (Also referred to as a Ribbon or Band Board.) Rise Vertical distance from bottom most part of the bottom chord to inside of the peak. Scab Additional timber connected to a truss to effect a splice, extension or general reinforcement. Shop Drawing Detailed drawings of a roof truss or roof framing showing critical dimensions such as span, overhang, cantilever, slope, etc.

Slope See Pitch. Spacing The centerline-to-centerline distance between trusses. Span The overall distance between adjacent interior supports or to the outside of supports when at the end of a truss. (See detail above.) Splice Point (Top & Bottom chord splice). The point at which two chord members are joined together to form a single member. It may occur at a panel point or between panel points. Square Cut End of top chord cut perpendicular to slope of the member. Strongback A 2x6 lateral brace, used with its long dimension in a vertical orientation, running perpendicular to the trusses, and attached to the truss vertical web members. Support The structural element resisting the truss, usually a wall or beam. (Also referred to as a Bearing.) Symmetrical Truss Truss with the same configuration of members and design loading occurring on each side of truss centerline. Top Chord The continuous 4x2 member forming the top of the floor truss. Top Chord Bearing A floor truss support condition in which the truss load is transferred to the bearing or support through the top chord and 4x4 block end detail. When the 4x4 block length is extended, this is referred to as Mid-Chord Bearing. Truss A pre-built component that functions as a structural support member. A truss employs one or more triangles in its construction. Truss-clip Metal component designed to provide structural connection of trusses to wall plates to resist wind uplift forces. Visual Grade Lumber Lumber which has been visually rated at the lumber mill for structural properties through rules established by national lumber species associations. Warren Truss A general truss configuration with repetitive web W orientation. For floor truss applications, the top and bottom chord panels are typically 30" length, usually with a 24" wide rectangular chase or duct opening at the centerline. Web A vertical or inclined member connecting the top and bottom chords of a truss.

MITEK INDUSTRIES, INC.

800.325.8075 www.mii.com

GLOSSARY

OF

TERMS

19

4x2 Member A 2x4 lumber section used as a structural component oriented such that its 3-1/2" (4" nominal) face is horizontal. Allowable Stress Income A percentage increase in the stress permitted in a member, based on the length of time that the load causing the stress acts on the member. The shorter the duration of the load, the higher the percent increase in allowable stress. Apez/Peak The uppermost point of a truss. Axial Force A push (compression) or pull (tension) acting along the length of a member. Usually measured in pounds, kips (1,000 lbs.) or tons (2,000 lbs.), or metric equivalent. Axial Stress The axial force acting at a point along the length of a member divided by the cross-sectional area of the member. Usually measured in pounds per square inch. Balcony Cantilever A floor truss cantilever serving only as a balcony with no additional wall loading acting on the cantilever portion. Battens/Purlins Timber sections spanning trusses to support roof covering. Beam Pocket A rectangular opening within a truss to accept a header beam for positive load transfer. Bearing A structural support, usually a wall, that occurs at the top or bottom chord or between the end points of a roof or floor truss. Bending Moment A measure of the bending effect on a member due to forces acting perpendicular to the length of the member. The bending moment at a given point along a member equals the sum of all perpendicular forces, either to the left or right of the point, times their corresponding distances from the point. Bending Stress The force per square inch of area acting at a point along the length of a member, resulting from the bending moment applied at that point. Usually measured in pounds per square inch or metric equivalent. Bottom Chord The continuous 4x2 member forming the bottom of the truss. Bottom Chord Bearing A floor truss support condition in which the truss load is transferred to the bearing or support through the bottom chord sitting on the support. Butt Cut Slight vertical cut at the outside edge of truss bottom chord made to ensure uniform span and tight joints - usually 1/4 inch. Camber An upward curvature built into a truss during fabrication to counteract downward deflection of the loaded truss.

Cantilever The portion of a truss extending beyond the exterior face of a support. Chase The opening in some floor trusses or structural components in which the mechanical equipment (ducts, plumbing, etc.) runs, typically a rectangular opening at the centerline. (Also referred to as a Duct Opening.) Check A lengthwise separation of wood fibers, usually extending across the rings of annual growth, caused chiefly by strains produced in seasoning. Chord Splice A splice of the 4x2 chord member between joints, joined by pre-splice connector plates into the 3-1/2" faces and occasionally side plates into the 1-1/2" edges. Clear Span Horizontal distance between interior edges of supports. Combined Stress The combination of axial and bending stresses acting on a member simultaneously, such as occurs in the top chord (compression + bending) or bottom chord (tension + bending) of a truss. Combined Stress Index (CSI) The summation of axial and bending stresses divided by their respective allowable stresses for a specific truss member. This ratio, or index, represents the structural efficiency of the member. The CSI shall not exceed 1.00. Concentrated Load Loading applied at a specific point, such as a load-bearing wall running perpendicular to a truss, or a roofmounted A/C unit hanging from a truss. Connector Plate Pre-punched metal toothed connectors located at the joints and splices of a truss and designed to hold the forces which occur at those locations. Cripple Rafter Infill rafter installed to continue the roof line - fixed to valley board in valley construction. Dead Load Any permanent load such as the weight of roofing, flooring, sheathing, insulation or ceiling material, as well as the weight of the truss itself. Design Loads The dead and live loads which a truss is engineered to support. Deflection The maximum vertical displacement of a structural member due to applied loading. (Live load deflection is the displacement due to live load deflection.) Depth The overall distance from the top of the top chord to the bottom of the bottom chord. Dimensional Adjustment The adjustment necessary to alter standard repetitive floor truss panel modules to achieve the desired overall truss span. Dimensional adjustment

can be made at one end, both ends, or in the center. (Also referred to as Dimensional Take-Up.) Doubled Chords The use of two 4x2 members along specified top or bottom chord panels to achieve added strength. Dropped Cantilever The use of overlapping 4x2 floor truss top chord members to frame a balcony cantilever with a step-down of 1-1/2" or 3" to provide positive drainage or application of concrete deck. End Detail Typically the location for dimensional adjustment. The end detail provides the support condition and necessary web orientation and panel length to create the desired truss span. Engineer Certified Drawing A truss design where loading requirements, lumber species, sizes, grades and connector plate requirements are detailed and a certified engineers seal is affixed. Extended Top Chord Bearing A floor truss support condition in which the truss load is transferred to the support through the single or doubled top chord member extending to sit on the support. Popular for floor trusses used as roof purlins. Fan Truss A floor truss with 30" top chord panels and 16" bottom chord panels and a fan web configuration. Forces Axial compression or tension in structural components due to applied loads. Girder A structural member carrying large loads due to attachment of headers or trusses framing into the girder (commonly called tie-in trusses). Girder Truss Usually a multiple-ply truss designed to carry other trusses over an opening. Header Beam A short beam typically supporting framing adjacent to a stair opening, running perpendicular to the floor trusses. Header Truss A truss with 4x2 chords typically supporting roof, wall and/or upper floor loads, spanning over door or window openings. (For example, a garage door opening header truss.) Heel Point on a truss at which the top and bottom chords intersect. Heel Cut See Butt Cut. Interior Bearing Any intermediate support condition in addition to the two exterior supports. A truss joint must be located above an interior bearing. Jack Rafter Infill rafter installed to continue the roof line - fixed from wall plate to hip board in hip end construction.

WHY USE WOOD TRUSSES? CONTRACTORS AND BUILDERS KNOW!

Contractors and Builders know that a MiTek engineered roof or floor truss system ensures quality and efficiency.

MITEK TRUSSES ARE RELIABLE


Every MiTek truss has been individually designed and that design is checked and approved by certified engineers for structural adequacy.

MITEK TRUSSES SAVE MONEY


Because costs are known in advance, theres no guesswork. Your site erection time is greatly reduced and dollar losses from job site material shortages and pilferage are eliminated.

MITEK TRUSSES Are Versatile


MiTek trusses provide more design flexibility, inside and out, than conventional framing. Offering numerous custom design options, our trusses present an economical and structurally superior method for rapid erection.

ARCHITECTS AND DEVELOPERS


Savings in design costs-one basic

CONTRACTORS/ BUILDERS
Pre-determined, pre-engineered Fewer pieces to handle and Wide 3-1/2 nailing surface for Eliminate notching and boring

ADVANTAGES OF TRUSSES OVER CONVENTIONAL FRAMING

structural design for shell with minor floor plan variations. Better project cost control, with component costs known in advance. Better cash flow with earlier occupancy due to reduced on-site labor. Faster shell completion time. Using trusses of smaller dimension lumber, in place of beams and columns. Greater flexibility in locating plumbing, duct work, and electrical wiring. Floor plan freedom in locating interior partitions often without additional support required.

truss system.

reduced installation time.

easy floor deck application.

joists for electrical wiring and plumbing. Floor trusses offer better availability and less in-place cost than 2x8 or 2x10 joists. Factory-manufactured components to exact span requirements. Reduced HVAC, plumbing, and electrical subcontractor time on job. No column pads to pour, no steel beams and posts to place. Job site material pilferage and cutting waste reduced.

HOMEOWNER
Lower construction costs. Clearspan flexibility. More flexibility in architectural Easier remodeling possibilities in

appearance and floor plans. moving interior walls.

18

GLOSSARY

OF

TERMS

800.325.8075 www.mii.com

ROOF

AND

FLOOR TRUSS ADVANTAGES

HANDLING INSTALLATION AND BRACING*


It is the responsibility of the installer to select the most suitable method and sequence of installation available to him which is consistent with the owners (architectural) plans and specifications and such other information which may be furnished to him prior to installation. Trusses may be installed either by hand or by mechanical means. The method generally depends upon the span of the trusses, their installed height above grade, and/or the accessibility or availability of mechanical installation equipment (such as a crane or forklift).

The installer should be knowledgeable about the truss design drawings, truss placement plans, and all notes and cautions thereon.

40/10/0/5 = 55 PSF @ 0%
Depth (inches) 12 13 14 15 16 17 18 20 22 24 24" o.c. 19.2" o.c. 16" o.c. 17-11 18-09 19-17 20-04 21-01 21-09 22-06 23-10 25-01 26-03 20-03 21-02 22-01 22-11 23-09 24-07 25-04 26-10 28-03 29-07 20-06 22-02 23-11 25-03 26-02 27-01 27-11 29-07 31-02 32-07 12" o.c. 20-06 22-02 23-11 25-07 27-04 29-00 30-09 34-02 36-03 37-11

40/10/0/10 = 60 PSF @ 0%
Depth (inches) 12 13 14 15 16 17 18 20 22 24 24" o.c. 19.2" o.c. 16" o.c. 16-04 17-02 17-11 18-07 19-03 19-11 20-06 21-09 22-11 24-00 18-08 19-06 20-04 21-02 21-11 22-08 23-05 24-09 26-01 27-04 20-06 21-08 22-07 23-06 24-04 25-02 25-11 27-06 28-11 30-04 12" o.c. 20-06 22-02 23-11 25-07 27-03 29-00 30-05 32-03 33-11 35-06

TEMPORARY BRACING
Temporary or installation bracing is the responsibility of the installer. Temporary bracing should remain in place as long as necessary for the safe and acceptable completion of the roof or floor and may remain in place after permanent bracing is installed.

50/10/0/10 = 70 PSF @ 0%
Depth (inches) 12 13 14 15 16 17 18 20 22 24 24" o.c. 19.2" o.c. 16" o.c. 15-02 15-10 16-06 17-02 17-10 18-05 19-00 20-02 21-02 22-02 17-03 18-01 18-10 19-07 20-04 21-00 21-08 22-11 24-02 25-04 19-02 20-00 20-11 21-09 22-06 23-03 24-00 25-05 26-09 28-01 12" o.c. 20-06 22-02 23-11 25-06 26-05 27-04 28-02 29-10 31-05 32-11

40/25/0/10 = 75 PSF @ 0%
Depth (inches) 12 13 14 15 16 17 18 20 22 24 24" o.c. 19.2" o.c. 16" o.c. 14-08 15-04 16-00 16-07 17-02 17-09 18-04 19-05 20-06 21-05 16-08 17-06 18-02 18-11 19-07 20-03 20-11 22-02 23-04 24-05 18-06 19-04 20-02 21-00 21-09 22-06 23-03 24-07 25-11 27-01 12" o.c. 20-06 22-02 23-08 24-07 25-06 26-04 27-03 28-10 30-04 31-09

STORAGE
Trusses should be stored in a stable position to prevent toppling and/or shifting. If trusses are stored horizontally, the blocking should be eight to ten foot centers to prevent lateral bending. If the truss bundle is to be stored for more than one week, the solidblocking, generally provided by the receiving party, should be at a sufficient height to lessen moisture gain from the ground. During long-term storage, trusses should be protected from the elements in a manner that provides for adequate ventilation of the trusses. If tarpaulins or other water resistant materials are used, the ends should be left open for ventilation. If trusses are made with interior rated fire retardant lumber, extreme care should be taken to limit outside exposure.

FIELD ASSEMBLY
In some cases, the size or shape of wood trusses is such that some field assembly is required. The installer is responsible for proper field assembly. Complete details on handling, installing and bracing can be found in the Truss Plate Institute (TPI) publications HIB-91 and DSB 89, available from TPI, 583 DOnofrio Drive, Suite 200, Madison, WI 53719.
*Reprinted from the Commentary & Recommendation for Handling, Installing & Bracing, Metal Plate Connected Wood Trusses, HIB-91, by permission of Truss Plate Institute, Inc.

50/20/0/10 = 85 PSF 0%
Depth (inches) 12 13 14 15 16 17 18 20 22 24 24" o.c. 19.2" o.c. 16" o.c. 13-09 14-05 15-00 15-07 16-02 16-08 17-03 18-03 19-03 20-02 15-08 16-05 17-01 17-09 18-05 19-00 19-08 20-10 21-11 22-11 17-05 18-02 19-00 19-09 20-05 21-02 21-10 23-01 24-04 25-06 12" o.c. 20-05 21-04 22-03 23-02 23-11 24-09 25-07 27-01 28-06 29-10

50/35/0/10 = 95 @ 0%
Depth (inches) 12 13 14 15 16 17 18 20 22 24 24" o.c. 19.2" o.c. 16" o.c. 13-00 13-07 14-02 14-09 15-03 15-10 16-04 17-03 18-02 19-00 14-10 15-06 16-02 16-10 17-05 18-00 18-07 19-08 20-09 21-09 16-05 17-02 17-11 18-08 19-04 20-00 20-07 21-10 23-00 24-01 12" o.c. 19-03 20-02 21-00 21-11 22-08 23-05 24-02 25-07 26-11 28-03

Note: Above max-spans are valid for lumber design only. Plating or other considerations may further limit the truss design.

HANDLING, INSTALLATION

AND

BRACING

800.325.8075 www.mii.com

FLOOR TRUSS MAX-SPANS

17

REPRESENTATIVE FLOOR AND ROOF APPLIED LOADS

Residential Flooring
40 psf Tc live Load 10 psf TC Dead Load (3/4" plywood decking) 0 psf BC Live Load 5 psf BC Dead Load (1/2" to 5/8" drywall) 55 psf Total Load (If heavy insulation or 2-ply drywall ceiling, BC Dead Load = 10 psf and 40/10/0/10 = 60 psf Total Load)

Commercial Floors
(Concrete deck)
50 psf TC Live Load (commercial use) 35 psf TC Deal Load (3" concrete floor) 0 psf BC Live Load 10 psf BC Dead Load 95 psf Total Load

TRUSS TYPES

KINGPOST

DOUBLE FINK

Residential and Commercial Roofing


20, 25, 30, 40, 50 psf TC Live Load (dependent on local building code requirements) 10 psf TC Dead Load (includes future re-roofing) 0 psf BC Live Load 10 psf BC Dead Load 40 to 70 psf Total Load (dependent on TC Live Load)

Commercial
(Also Multi-Family Dwellings)
40 psf TC Live Load 25 psf TC Dead Load (1-1/2" to 2" thick lightweight concrete cap) 0 psf BC Live Load 10 psf BC Dead Load 75 psf Total Load

QUEENPOST

DOUBLE HOWE

Notes: Above representative loads are typical loading requirements for many regions in the country.
However, the required applied loading for design purposes is the responsibility of the building designer, within the limitations of the prevailing local, state, or regional building code specifications. Roof trusses to be checked for local wind loadings. Commercial floors may require additional load cases.

FINK

HIP

MITEK FLOOR TRUSS MAX-SPANS


The chord max-spans shown on the next page are intended for use in bidding, estimating, and preliminary design applications. They are presented for six representative floor loadings. For proper interpretation of these max-spans, note the following: The max-spans are valid for the following (or better) species grades: No. 1 KD Southern Yellow Pine No. 1 and better Douglas Fir 2100Fb-1.8E Machine Stress Rated (MSR) lumber. Shorter spans will be achieved using lesser grade 4x2 lumber, while longer spans are generally possible with higher grade lumber. The max-spans represent truss overall lengths, assuming 3-1/2" bearing at each end. The spans are equally valid for top chord-bearing and bottom chord-bearing support conditions. The minimum truss span-to-live load deflection is 360 for floor application. For example, the maximum permissible live load deflection for a 20' span floor truss is (20 x 12)/360=0.67". In addition to the consideration of lumber strength and deflection limitations, the maximum truss span-to-depth ratio is limited to 20 for floor loadings. For example the maximum span of a floor application truss 15" deep is 15" x 20' = 300" span = 25' - 0" span. Floor loadings have included 1.00 Load Duration Increase and 1.15 Repetitive Stress Increase.

HOWE

SCISSORS

FAN

MONOPITCH

MODIFIED QUEENPOST

CAMBERED

16

TECHNICAL INFORMATION

800.325.8075 www.mii.com

BASIC ROOF TRUSS CONFIGURATIONS

SOUND TRANSMISSION RATINGS

DUAL PITCH

INVERTED

Various floor-ceiling systems exhibit different abilities to reduce sound transfer from one room to another. This sound transmission resistance is measured by two indices - the Sound Transmission Class (STC) which rates airborne sounds to evaluate the comfortability of a particular living space and the Impact Insulation Class (IIC) which rates the impact sound transmission performance of
Description

an assembly. These ratings are used by regional building codes to regulate permissible sound transfer. For more detailed information reference the Metal Plate Connected Wood Truss Handbook, 1993 Wood Truss Council of America, Section 18.0 - Transitory Floor Vibration and Sound Transmission.

STC High Frequency

IIC Low Frequency

GAMBREL

PIGGYBACK

Calculation Example
Description STC
0 7 36 10 53

IIC
20 1 33 8 62

POLYNESIAN

STUDIO

Carpet and Padding 3/4 Gypcrete Wood Truss Floor Resilient Channel Total

Basic Wood Floor - consisting of wood joist (I-joist, solid-sawn, or truss), 3/4 decking and 5/8 gypsum wallboard directly attached to ceiling Cushioned Vinyl or Linoleum Non-cushioned Vinyl of Linoleum 1/2 Parquet Flooring 3/4 Gypcrete or Elastizel 1-1/2 Lightweight Concrete 1/2 Sound Deadening Board (USG)* Quiet-Cor Underlayment by Tarkett, Inc* Enkasonic by American Enka Company* Sempafloor by Laminating Services, Inc.* R-19 Batt Insulation R-11 Batt Insulation 3 Mineral Wood Insulation Resilient Channel Resilient with Insulation Extra Layer of 5/8 Gypsum Wallboard Carpet and Padding

36 0 0 0 7-8 7-8 1 1 4 1 2 1 1 10 13 0-2 0

33 2 0 1 1 1 5 8 13 11 0 0 0 8 15 2-4 20-25

*Estimates base on proprietary literature. Verify with individual companies. The above chart information was excerpted from the Construction Guide for Southern Pine Joist & Rafters. Southern Pine Council, 1993.

ATTIC

CATHEDRAL TYPICAL CONSTRUCTION MATERIAL WEIGHTS


Floors
Hardwood (1 in. thick)............. 3.8 psf Concrete Regular (1 in. thick) ............ 12.0 psf Lightweight (1 in. thick) ....... 8.0 psf Linoleum ................................. 1.5 psf 3/4" ceramic or quarry tile .... 10.0 psf Ductwork (24g) ............. 3.0 to 5.0 psf Rigid fiberglass (1 in. thick) .... 1.5psf Roll or batt insulation (1 in.) .. 0.3 psf Glass or rock wool (1 in. thick) .. 0.3 psf 3/4 in. plywood ....................... 2.3 psf 1-1/8 in. plywood .................... 3.4 psf 1 in. sheating (nominal) ........... 2.3 psf 2 in. decking ............................ 4.3 psf Tectum (1 in. thick) ................. 2.0 psf Poured gypsum (1 in. thick) ... 6.5 psf Vermiculite concrete (1 in. thick) ....... ............................................... 2.7 psf

Floors Truss Weights


Single chord ............. 5.5 plf (approx.) @ 24" o.c. spacing .. 2.75 psf (approx.) Double chord ............ 8.5 plf (approx.) @ 24" o.c. spacing .. 4.25 psf (approx.)

BOWSTRING

SLOPING FLAT

Composition Roofing
235 lb. shingles and paper ...... 2.5 psf 2-15 lb. and 1-90 lb. ................ 1.7 psf 3-15 lb. and 1-90 lb. ................. 2.2 psf 3-ply and gravel ........................ 5.6 psf 4-ply and gravel ........................ 6.0 psf

Partition Wall Weights (8' Nominal Height)


Interior partition - (studs @ 16" o.c.).. ................................ 50 plf (approx.) Exterior partition - (studs @ 16" o.c.). and composition exterior).................... ................................ 85 plf (approx.) Exterior partition - (studs @ 16" o.c. and brick exterior) .. 180 plf (approx.)

Ceilings
Acoustical fiber tile ................. 1.0 psf 1/2 in. gypsum board .............. 2.0 psf 5/8 in. gypsum board 2.5 ........ 2.5 psf Plaster (1 in. thick) .................. 8.0 psf Metal suspension system ......... 0.5 psf Wood suspension system ........ 2.0 psf

Roof and Floor Sheathing And Decking


1/2 in. plywood ....................... 1.5 psf 5/8 in. plywood ........................ 1.8 psf

STUB

FLAT

Miscellaneous
Sprinkling system ......... 1.0 to 1.5 psf

BASIC ROOF TRUSS CONFIGURATIONS

800.325.8075 www.mii.com

TECHNICAL INFORMATION

15

SUPPORT DETAILS FLOOR TRUSS ONE-HOUR FIRE RATING


The Truss Plate Institute has authorized fire tests be conducted to achieve a one-hour fire rating for a typical floor and ceiling assembly. Copies of those reports are available from the issuing agencies.
4x2 Wood Block Z-clip

ICBO* Design No. 4431


3/4 T&G plywood, glued and nailed with alt. lightweight concrete

2x4 or 4x2 Roof or Floor Trusses @ max. 24 o.co

Bottom Chord Bearing on Exterior Frame or Masonry Wall

Bottom Chord Bearing on Exterior Frame Wall with Masonry Fascia Wall

Additional information regarding onehour fire ratings using wood trusses with gypsum board ceiling may be obtained from ICBO Research Reports No. 1632 and 1352. Fire rating test results are summarized in the adjacent illustrations.

1 layer 5/8 thick USG Firecode C, Type C gypsum wallboard fastened with 1-7/8 Type S screws @ 8 o.c.

UL** Design No. L528


3/4 T&G plywood, glued and nailed with alt. lightweight concrete

2x4 or 4x2 Parallel Chord Trusses @ max. 24 o.c. Furring Channels 1 layer 5/8 thick Type C, USG gypsum wallboard secured with screws, joints finished

Intermediate Bearing - Simple Span Trusses

Intermediate Bearing - Continuous Floor Truss (Special Engineering Required)

UL** Design No. L529


3/4 T&G plywood, glued and nailed with alt. lightweight concrete

2x4 or 4x2 Parallel Chord Trusses @ max. 24 o.c.

Header Beam Pocket - Floor Truss Supporting Header Beam (Special Engineering Required)
Steel Cross Tees and Runners 1 layer 5/8 thick Type C, USG gypsum wallboard secured with screws, joints finished

Intermediate Bearing - Floor Truss Supported by Steel or Wood Beam (Special Engineering Required)

Factory Mutual*** Design FC214


3/4: T&G plywood, glued and nailed

International Conference of Building Officials 1313 East 60th Street Chicago, IL 60637 ** Underwriters Laboratory, Inc. 333 Pfingsten Road Northbrook, IL 60062 *** Factory Mutual Research 1151 Boston-Providence Road Norwood, MA 02062

2x4 or 4x2 Parallel Chord Trusses @ max. 24 o.c.

Top Chord Bearing on Frame Wall


2 layers 1/2 thick Type FSW-1, NGC gypsum wallboard, secured with screws, joints finished

Top Chord Bearing on Masonry Wall

14

TECHNICAL INFORMATION

800.325.8075 www.mii.com

FLOOR TRUSS CONSTRUCTION DETAILS

FLOOR DECKING INFORMATION


Virtually all decking systems may be easily applied to MiTek floor trusses. The wide 3-1/2 nailing surface assures that floor decks are installed accurately and quickly. The adjacent table is a summary of plywood deck requirements presented by various American Plywood Association publications.

Floor Construction
Conventional Double-Layer Plywood Underlayment over Plywood Sub-Flooring Wood Strip Flooring over Plywood Sub Flooring (installed at right angles) 1-1/2 to 2 Lightweight Concrete Cap over Plywood Subflooring

Panel Indent 48/24 40/20 32/16 24/16 32/16 40/20

Thickness
23/32, 3/4, 7/8 19/32, 5/8, 3/4, 23/32 15/32, 1/2, 5/8, 19/32 7/16, 15/32, 1/2 15/32, 1/2, 5/8, 19/32 19/32, 5/8, 3/4, 23/32

Floor Truss Spacing


24 Spacing 19.2 Spacing 16 Spacing 16 o.c. Spacing 24 Spacing Permitted 24 Spacing Permitted (Spacing equal to Panel Indent.) Panels must either be Tongue-andGroove or blocked Between Trusses.

Extended Top Chord Bearing (Span Limited by Engineering)

Extended Top Chord Bearing (Span Limited by Engineering)

40/20

19/32, 5/8, 3/4, 23/32

APA Sturd 1-Floor (must be nailed or glued and nailed according to APA)

24 20 16 32 48

23/32, 3/4, 7/8 19/32, 5/8 19/32, 5/8 7/8, 1 1-1/8

APA Glued Floor System (must be glued according to APA Spec. AFG-01 and nailed)

(Available thickness 24 Spacing for either conventional 19.2 Spacing subflooring plywood or 16 Spacing for Sturd-I-Floor Panels.)

Balcony Cantilever

Load-Bearing Wall Cantilever

CONNECTOR PLATE CODE APPROVALS

MiTek connector plates have been approved by all recognized national and regional model building code groups, based on extensive structural testing. The following approvals may be referenced for more detailed information:

Dropped Chord Balcony Cantilever

JOINT DETAILS

BOCA National Building Code Building Officials and Code Administrators, International (BOCA) Research Report No. 96-31, 96-67 Uniform Building Code (UBC) International Conference of Building Officials (ICBO) Report No. 3907 and 4922. Standard Building Code (SBC) Southern Building Code Congress International (SBCCI) Report No. 9667 and 9432A.

Federal Housing Administration (FHA/HUD) U.S. Department of Housing and Urban Development (HUD) Truss Connector Bulletin No. TCB 17.08. Wisconsin State Code Wisconsin Department of Industry. Labor and Human Relations (DILHR) Approval No. 960022-W, 970036-N.

Chord Joint Splice

Chord Pre-Splice

FLOOR TRUSS CONSTRUCTION DETAILS

800.325.8075 www.mii.com

TECHNICAL INFORMATION

13

MAXIMUM MECHANICAL SERVICE CLEARANCES - FLOOR TRUSSES

Overall Truss Depth (Inches) 12 13 14 15 16 17 18

Width (W) (Inches) When Height (H) Equals: 3 4 5 6 7 8 32 34 36 38 40 41 42 43 44 44 45 46 46 25 28 31 33 35 37 38 39 40 41 42 43 43 19 23 26 28 31 32 34 36 37 38 39 40 41 12 17 20 23 26 28 30 32 33 35 36 37 38 6 11 15 19 22 24 26 28 30 31 33 34 35 5 10 14 17 20 22 25 26 28 30 31 32 Diameter (D) (Inches) 7 8 9 10 11 12 13 14 15 16 17 18 18-1/2

LATERAL BRACING SUGGESTIONS


2x6 Strongback lateral supports should be located on edge approximately every 10 feet along the floor truss. They should be securely fastened to vertical webs. Blocking behind the vertical web is recommended while nailing the strongback. The strongbacks should either be secured to adjacent partition walls or alternate X-bridging should be used to terminate the bracing member.

Overall Truss Depth

19 20 21 22 23 24

Floor Cantilevered Perpendicular to Floor Truss Span

Floor Cantilevered Perpendicular and Parallel to Floor Truss Span

FLOOR TRUSS CANTILEVER CONCENTRATED LOADS


Floor truss cantilevers often support load-bearing walls carrying roof live loads and wall material dead loads. The adjacent chart provides a convenient means of determining an equivalent concentrated load for representative roof loads which incorporate a 15% load duration factor for the roof load only.

Roof Span (Feet)

Concentrated Load at End of Cantilver (lbs.) Roof Load (at 1.15) Plus Wall Load 20/10/0/10 = 40 psf 865 965 1005 1075 1145 1215 1285 30/10/0/10 = 50 psf 1040 1125 1215 1300 1385 1475 1560 40/10/0/10 = 60 psf 1215 1320 1425 1530 1630 1735 1840

20 22 24 26 28 30 32

CONCENTRATED LOAD SAMPLE CALCULATION


Roof Loading = 20/10/0/10 = 40 psf @ 1.15 Roof Load (Roof Truss Reaction) = 40 psf x (30'/2) x 2'-0" o.c. - 1200 lbs. 8' Stud Wall Weight (@ 85 lbs./lineal ft.) = 85 plf x 2'-0" o.c. = 170 lbs. Equivalent Floor Truss Load = (1200/1.15) + 170 = 1215 lbs. Concentrated Load Note: Also check floor truss for dead load only at end of cantilever.
Roof Load

Section AA - Floor Truss Jacks

Floor Joist Scab Cantilever

30-0

Notes
Wall Load
(Varies)

Special engineering required for girder floor trusses. Slope for drainage, as required. Cantilever span controlled by lumber size and grade deflection limitations.

12

TECHNICAL INFORMATION

800.325.8075 www.mii.com

FLOOR TRUSS CONSTRUCTION DETAILS

STAIRWAY FRAMING
Built-up Beam with Strap Hanger Stairwell Opening without Stud Walls

ARCHITECTURAL SPECIFICATION

Header Beam Pocket

Trusses shall be fabricated by a MiTek truss manufacturer in accordance with MiTek floor truss engineering specifications. MiTek engineering design drawings bearing the seal of the Registered Engineer preparing the design shall be provided to the Project Architect for his approval. Truss designs shall be in accordance with the latest version of ANSI/TPI1 National Design Standard for Metal Plates Converted Wood Construction, a publication of Truss Plate Institute and generally accepted engineering practice. In addition to allowable lumber stress limitations, floor truss designs are also regulated by maximum permissible deflection-to-span and depth-to-span limitations, as shown in the chart below. The suggested camber to be built into the truss during fabrication is also included. The truss deflection is calculated by

Delivery, handling, and erection of MiTek trusses shall be in accordance with the TPI Quality Standard for Metal Plate Connected Wood Trusses, published by Truss Plate Institute. Truss hangers, anchorage, permanent bracing, and required design loads shall be the responsibility of the Project Architect. MiTek truss connector plates are manufactured under rigid quality control using structural Grade C hot-dipped, galvanized steel meeting ASTM Specifications A653.

Stairwell Opening Carried by Stud Wall

RECOMMENDED DEPTH, DEFLECTION, AND CAMBER LIMITATIONS

Header Beam with Strap Hanger

complex engineering methods and verified by extensive full-scale load tests. The floor span-to-depth limitation is intended to prevent objectionable floor vibration. All of the following recommended limitations should be achieved to provide a quality floor system and assure complete customer satisfaction.
Roof Span/24 Span/240 (Live Load) Dead Load Deflection*

Floor Minimum Depth Maximum Deflection Recommended Camber Span/20 Span/360 (Live Load) Dead Load Deflection

* Provide slope of 1/4 per foot of span for proper drainage to prevent water ponding.

Stairwell Opening Perpendicular to Floor Trusses, Carried by Stud Wall Typical Basement Stair Framing CrossSection
ROOFS DONT Unload trusses on rough terrain or uneven surfaces, which could cause damage to the trusses. DO support trusses that are stored horizontally on blocking to prevent excessive lateral bending and lessen moisture gain. DONT break banding until installation begins and the trusses are in a stable, horizontal position. DONT lift bundled trusses by the bands and do not use damaged trusses. DO brace trusses that are stored vertically, to prevent toppling or tipping. DONT walk on trusses that are lying flat. This is a dangerous practice.
800.325.8075 www.mii.com

CONSTRUCTION GUIDELINES
FLOORS DO color-code floor truss ends for correct non-symmetrical installations. DO locate trusses to allow for plumbing or duct riser clearances. DO assure that trusses are installed with a joint located over an interior bearing. DO use warning tags on floor trusses to provide proper installation orientation and to warn against cutting or modifying trusses. DONT permit stacking of drywall or plywood sheathing during construction on floor truss balcony cantilevers or at truss mid-span without proper shoring. DONT use floor trusses when exposed to weather, chemically corrosive environment, or extremely high humidity. DONT cut truss chords or webs or modify them in any way during construction.

Note: Framing opening between header beams must usually be increased beyond conventional framing opening to permit necessary headroom.

10

FLOOR TRUSS CONSTRUCTION DETAILS

TECHINICAL INFORMATION