HVDC PDF
HVDC PDF
Insulation Co-ordination
TS requirement.
The contractor shall provide surge arresters, surge capacitors, and other devices as required to protect all the equipment within the station from dc, fundamental frequency, harmonic, ferro-resonant, switching surge and lightning impulse overvoltages under all steady state, dynamic and transient conditions.
TS requirement.
The insulation of the equipment and protective levels of arresters connected to the 400 kV and 230kV AC bus bars of the Back-to-Back HVDC stations shall be coordinated with the insulation and surge arrester characteristics of the Employer's 400 kV and 230 kV AC systems to which the back-to-back HVDC station is connected. The Contractor shall take into account the possible ac line discharge energy which could be present in the back-to-back HVDC Station arresters. In addition the Contractor shall ensure that the discharge duty of the Employer's arresters is not increased due to infeed from the back-to-back hvdc station. The Contractor shall coordinate the ac filter bank surge arrester characteristics so that these arresters will discharge the energy in the ac filter and shunt capacitors (if used) and will prevent the capacitors from being charged to a level which can not be discharged by other arresters connected to the 400 kV and 230kV ac system.
Insulation Co-ordination.
The examination and predication of prospective overvoltages and continuous voltage stresses occurring on transmission equipment with respect to determiningOvervoltage Insulation Withstand (ie BIL, BSL) Clearance in Air Creepage across shed surfaces of insulators and bushings Rating and positioning of protective devices to limit Overvoltage Equipment Test Requirements
General Principles
Sources or Overvoltage: Switching Impulse Lightning Impulse FOW (Fast Front of Wave) Power Frequency
General Principles
Switching Impulse Typically defined as: Voltage wavefront Current wavefront Caused by: Circuit breaker operation Protective Switching Equipment Energisation Load Rejections Convertor switching transients 250/2500 micro sec (IEC) 36/90 micro sec
General Principles
Lightning Impulse Definition Voltage wavefront: 1.2/50 micro sec Origins Direct lightning stroke to line - rare on shielded systems Back flashover - lightning strikes pylon sheild wires (IEC60071) Current wavefront: 8/20 micro sec (IEC600990-1)
General Principles
FOW (Front of Wave) Impulse Definition Current wave front: 1/2 micro sec Origin Bushing flashovers within valve hall, causing discharge of stray capacitances through relatively short lengths of conductor
General Principles
AC System SideLightning Impulses Switchyard shielding limits direct strikes <20kA Back flashover on first tower outside switchyard Filter bus flashover may result in 8/20 micro seconds wave fronts of between 30 and 100kA within filter Switching Impulses Load Rejection / Re-energisation 1kA<Ic<3kA
(Typical assumptions for a project)
General Principles
DC System (Valve Hall) side Lightning Impulses Not significant in Valve Hall ; Shielding by Convertor Transformer An arbitrary 1kA nominal LIPL is however considered for determining arrester characteristics Switching Impulses Generally in the range 1kA to 3kA Result from AC system switching events transferred through convertor transformer Convertor commutation overshoots during TOV conditions FOW Impulses Typically of the order of 1kA
(Typical assumptions for a project)
Arrester Protection
Determine Min. SIPL Necessary to Avoid Thermal Runaway Determine Max LIPL or SIPL Permissible ie: Target BIL (BSL) /Safety Margin
Set SA to Min SIPL as first iteration Carry out preliminary studies to estimate arrester energies If necessary, adjust SA SIPL (LIPL) levels upwards to reduce Energy Absorption
The starting point of the insulation co-ordination process within the valve hall is the rating of the valve surge arrester (V) by balancing continuous energy absorption against protective level. Once the valve arrester switching impulse protective level (SIPL) has been determined, all other switching impulse protective levels throughout the system may be established. Lightning impulse protective levels (LIPL) may then be established by applying a typical manufacturer ratio of LIPL to SIPL.
AC arresters are designed to Limit overvoltages on the AC system arising from convertor load rejections Protect AC filter components against overvoltages during filter switching Protect all AC system side components (particularly wound components) against lightning strikes on overhead lines and capacitor back flashovers
DC arresters are designed to Protect the DC convertor equipment from switching voltage transients arising from Convertor blocks TOV conditions Switching events transferred from AC system Bushing flashovers within the DC area
U10ka (P.U)
1.2 1.0 0.8 0.6 0.4 001 0. 20 60 150
AC
10.
0.00001
1000.
0.1
100000
Current (A)
By suitable system design By suitable co-ordination between insulation and surge arrester protection
System Design
On DC side Over Voltages can be reduced by-
Shielding the converter station and Transmission lines Suitable design of the converter control equipment. Selecting system parameters to try and avoid resonance under fault conditions.
System Design
On the AC side. Voltage support equipment is essential to provide voltage control during transient and dynamic system disturbances. Compensating equipments requires detailed studies to determine the relationship between DC system recovery and voltage support equipment and response time
Fundamental Differences Between AC and HVDC Insulation Co-ordination Philosophy AC System consists of parallel connected circuits and apart from some special cases the requirement is to establish the insulation level bet. phase to earth and phase to phase level. HVDC converter stations on the other hand consist of series connected bridges, each bridge requiring a different insulation strength to earth and within each bridge the electric strength is different for the various components.
Arresters on AC side are usually specified by their rated voltage and maximum continuous operating voltage
On DC side rated voltage is not defined and continuous operating voltage is defined differently.
Rated Voltage for Arresters For DC Application are Specified As: PCOV (Peak Continuous Operating Voltage) CCOV (Crest Continuous Operating Voltage) ECOV (Equivalent Continuous Operating Voltage)
Over Voltages
On AC side > Peak value of voltage between phase conductor & earth or between phase conductors having highest system voltage peak. On DC side> PCOV (Peak Continuous Operating Voltage)
Arrester scheme of an HVDC back to back link with one 12 pulse group per side
This arrester protect the top of converter valve structure and also protect the top converter transformer winding against surges entering from dc side.
This arrester may limit overvoltages due to lightning stresses propagating into the valve area.
1. 2. 3.
Earth fault on the dc bus. Earth fault between the valves and converter transformer. Loss of return path during monopolar operation.
These arresters protects filter circuit elements such as reactors and damping resistors against overvoltages when a filter circuit is energized from the dc bus bar or in the event of busbar short circuit to ground. In the later case energy stored in the main capacitor discharges into FD arrester.
Employed to limit the voltage across the winding in the event that voltages of opposite polarity occur on both side of the smoothing reactor. However, because this impairs the protection against in-coming travelling waves from the HVDC overhead line, most system do not employ DR arrester.
Insulation Withstand:
Insulation withstand is the capability of a given item of equipment to withstand applied transient overvoltages (switching, lightning and fast front) and power frequency overvoltages. In terms of transient overvoltage withstand the key parameters are: BIL: Basic Insulation Level: The proven ability of an item of equipment to withstand the lightning impulse voltage transient (typically defined as 1.2/50s wavefront). BSL: Basic Switching Level: The proven ability of an item of equipment to withstand the switching impulse voltage transient (typically defined as a 250/2500s wavefront).
The arrester protective Levels are established by considering system operating parameters and system studies. Insulation withstand levels are established by application of margins detailed in the specification. Once the insulation withstand requirements are established clearance is determined by calculation. Creepages are established from steady state operating voltages and specific creepage distances detailed by Employers Requirement.
2.
3.
4.
Insulation Withstand
Typical Withstand Characteristics
Voltage Equipment withstand voltage 25% 20% 15%
DC side Equipment
1. 2. 3.
SIWL at least 1.20 times the SIPL LIWL at least 1.25 times the SIPL FWWL at least 1.25 times the FWPL
AC side Equipment
India side:
1. 2. 3.
SIWL at least 1.15 times the SIPL LIWL at least 1.25 times the SIPL FWWL at least 1.25 times the FWPL
Bangladesh side:
1. 2.
LIWL at least 1.25 times the SIPL FWWL at least 1.25 times the FWPL
1. 2. 3. 4.
1.40 times the SIPL 1.20 times the LIPL 1300 kV for equipment connected to the 400 kV ac bus. 950 kV for equipment connected to the 230 kV ac bus
5. Air Clearances
A.
AC switchyard
B.
DC side
A. AC switchyard
India Side(400KV) The air clearances shall be equal to or greater than the minimum values used by the employer for equipment with the same withstand level. Within the ac switchyard the air clearances shall not, for 400 kV ac connected equipment, be less than : - Phase to ground 3.5 m - Phase to phase 4.0 m - Section Clearance 6.5 m
A. AC switchyard
Bangladesh side(230KV ) Within the ac switchyard the air clearances shall not, for 230 kV ac connected equipment, be less than : - Phase to ground 2.1 m - Phase to phase 2.1 m - Section Clearance 5.0 m For equipment or insulation where a LIWL other than 1050 kV is applicable the minimum air clearances shall not be less than those given in IEC publications 60071-2, Tables VIA and VIB (phase to ground), and 71-3, Tables V and VI (phase to phase). The relevant
B. DC side
For equipment or insulation on the dc side the minimum air clearances shall not be less than the values given in the CIGRE (application guide 33.83 (SC) 03.21 WD), and arrester protection of HVDC converter station (Electra96) appropriate to and withstand level required in accordance with Clause 4.4.4.4. Outdoor bushings, if used, shall have a flash distance of not less than 12 mm per kV for vertical Bushing as well as horizontal Bushing of applied steady state dc voltage as.
6. Leakage Distances
A.
AC switchyard
B.
DC equipment
A. AC switchyard
The leakage distance for all ac insulators shall not be less than 43 mm per kV of the maximum normal operating phase to ground voltage at the insulator. The maximum normal operating voltage is defined as the crest value of the voltage, including voltage distortion effects divided by the square root of 2. The maximum normal operating fundamental frequency 400 kV ac bus voltage shall be taken as 420 kV rms phase to Phase. The maximum normal operating fundamental frequency 230 kV ac bus voltage shall be taken as 245 kV rms phase to Phase
B. DC equipment
All dc bushings shall be placed indoors. Based on the crest voltage the minimum leakage distance (excluding tolerance) shall not be less than : .1 2.0 cm/kV for indoor porcelain/ silicone rubber insulation in clean surroundings .2 5.0 cm/kV for outdoor silicone rubber insulators mounted vertically*
B. DC equipment
5.0 cm/kV for outdoor silicone rubber insulators mounted horizontally* 5.0 cm/kV for outdoor silicone rubber bushings mounted vertically* 5.0 cm/kV for outdoor silicone rubber bushings mounted other than vertically*.
B. DC equipment
6.0 cm/KV for outdoor porcelain insulators/ bushings. *Outdoor bushings shall be only of silicone rubber type. The requirement of 20 mm/KV within the valve hall applies to all silicone rubber/ porcelain insulators and bushings external to the valve. The definition of valve being as given in IEC 60700-1.