AC Input Input Voltage, Nominal Input Voltage, Permitted Variation Line Frequency Max Input Current Power Factor THD (Total Harmonic Distortion)
DC Output Output Voltage, Adjustment Range Output Power Output Power, Derated for Input Voltage Output Current Efficiency Psophometric Noise (System) Temperature Derating
For R48-1000
Temperature (C)
-42 to -58 V DC 1000W@Vout >48VDC See Diagram 20.83 A @ -48 VDC 92% 1mV; 32dBrnc See Diagram
% of output power
Alarm and status reported via CAN bus to system controller Green LED: Normal Operation Yellow LED: Alarm Red LED: Failure Flashing Red LED: Fan Failure
For R48-1000
Environmental Temperature Range, Operating Temperature Range, Storage Relative Humidity Altitude EMC Safety
-40 to +75C, -40 to +167F -40 to +75C, -40 to +167F 0 to 95% 2000 m, 6560 ft at full power ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B, Telcordia GR-1089-CORE class B IEC 60950, EN 60950, UL 60950