A-ISOMETER IRDH275

Insulation monitoring device for grounded AC, AC/DC and DC power supplies (Floating Systems)

106 015 en / 05.2003

A-ISOMETER IRDH275

Insulation monitoring device for grounded AC, AC/DC and DC power supplies Floating Systems)

Product description The IRDH275-series A-ISOMETER monitors the insulation resistance of grounded AC, AC/DC 0 . . . 793 V and DC 0 . . . 650 V power circuits (Floating systems). Due to the AMPPLUS-measuring principle the devices are particularly suitable for modern power supply systems frequently containing converters, power converters, thyristor controls and directly connected DC components. Due to interference suppression methods (EMC), high leakage capacitances often exist in these systems. The IRDH275 adapts itself automatically to the respective system conditions and optimizes the measuring time. The voltage range can be expanded with coupling devices. A separate supply voltage enables monitoring of the system in the de-energized state. For installation in distribution box doors, see type IRDH375(B). Applications
IRDH275

AC,DC or AC/DC main circuits AC/DC main circuits with directly connected DC components such as converters, power converters, and thyristor-controlled DC drives UPS (uninterruptible power supply) systems, battery systems

heaters with phase controllers systems with switched-mode power supplies Floating systems with high leakage capacitances coupled Floating systems

Characteristics of the device insulation monitoring for AC, AC/DC Floating systems 0. . . 793 V AC and DC Floating systems 0...650V.

nominal voltage expandable by using of an appropriate coupling unit two separately adjustable response values 1 k . . . 10 M AMPPLUS measuring principle automatic adaptation to system leakage capacitances info button for displaying the device settings and system leakage capacitance self check with automatic signalling automatic self test, selectable connection for external clear text display test and reset button connection for external test and reset button two separate alarm relays with two floating changeover contacts N/O or N/C operation, selectable illuminated clear text display RS485 interface transparent dust cover for ingress protection

Functions If the insulation resistance between the conductors and ground falls below the set response values, the alarm relays are switched and the alarm LEDs light up.Through the use of separately adjustable alarm relays it is possible to make a distinction between a Prewarning and a main warning. The measured value is shown on the LC display or on an externally connected measuring instrument. This makes it easy to detect changes, such as when load circuits are cut in. The fault message can be stored. To clear the fault memory, press the RESET button. The TEST button can be used to verify the functions of the unit, including the connections to the mains and to ground. By pressing the INFO button, important information, such as the system leakage capacitance and device settings, will be displayed.The functions of the unit and connections to the mains and to ground are monitored continuously. If a fault occurs, the system fault relay is switched and the System error alarm LED lights up. The device parameters are set by using the control buttons on the front of the unit and the LC display. IRDH275B version The IRDH275B version includes the following additional functions: memory to store all alarm messages with date and time stamp electrically isolated RS485 interface (BMS protocol) for exchange of data with other Bender components Isometer disconnecting relay for the operation of multiple A-ISOMETERs in coupled Floating systems current output 0(4) . . . 20 mA (electrically isolated)

Use in coupled Floating systems Due to the Isometer disconnecting relay included in the IRDH275B version and the F1/F2 control inputs, this unit can also be used in coupled Floating systems. It is thus ensured that only one A-ISOMETER is actively measuring at any given time. Measuring principle

AMPPlus
Standards

The IRDH275(B) series uses the patented AMPPlus measuring principle. This ensures exact monitoring of modern power supply systems, even with extensive, directly connected DC components and high system leakage capacitances.

The IRDH275(B) series conforms to the following equipment standards: DIN EN 61557-8 (VDE 0413 part 8): 1998-05, EN 61557-8: 1997-03, IEC 61557-8: 1997-02, ASTM F1669M 1996-00

106 015 en / 05.2003

A-ISOMETER IRDH275

Front panel of the IRDH275

Wiring diagram

A-ISOMETER

IRDH275
k

ESC

INFO

TEST

RESET

MENU

1
12345678-

2 1

5 6

INFO button: for calling up standard information/ESC button: back to the menu function TEST button: Call up self test/Up arrow button: changing parameters, scrolling display RESET button: deleting installation and fault messages (A-Isometer only) Down arrow button: changing parameters, scrolling Menu button: calling up the system menu/Return button: confirming changed parameters Alarm LED1 lights up: Insulation fault, 1st warning level reached Alarm LED2 lights up: Insulation fault, 2nd warning level reached LED lights up: System fault is present

Characteristic of the IRDH275 12345678A-ISOMETER response times as a function of leakage capacitance: Ce = 1 . . . 500 F, Un = 0 . . . 793 V / 50 Hz 9-

10

11

12

13

Us supply voltage (see nameplate) via fuse Connection of the 3AC system to be monitored: terminals Connect L1, L2 with neutral conductor N or terminals L1, L2 with conductors L1, L2 Connection of the AC system to be monitored: connect terminals L1, L2 with conductors L1, L2 Connection of the DC system to be monitored: connect terminal L1 with conductor L+, terminal L2 with conductor LConnect equipotential bonding to External test button (make contact) External reset button (break contact or wire jumper); if terminals are open, no fault message will be saved STANDBY via function input F1/F2; when F1/F2 contact is closed,no insulation fault measurement; isolation from mains and KE separately

10 - IRDH275: current output, electrically isolated: 0 . . . 400 A, IRDH275B: current output, electrically isolated: 0 . . . 20 mA or 4 . . . 20 mA 11 - Serial interface RS485 12 - Alarm relay: Alarm 1 13 - Alarm relay: Alarm 2 or system fault

106 015 en / 05.2003

A-ISOMETER IRDH275

Wiring diagrams IRDH275 with various coupling units A-ISOMETER IRDH275 with coupling unit AGH150W-4

Ordering details for A-ISOMETER IRDH275 and accessory equipment Ordering details for A-ISOMETER IRDH275 Type Operating range UN Supply voltage US Art. no

AK160

IRDH275-435 AC 0 ... 793 V/DC 0 ... 650 V AC 88 ... 264/DC77 ... 286V B 9106 5100 IRDH275B-435 AC 0 ... 793 V/DC 0 ... 650 V AC 88 ... 264/DC77 ... 286V B 9106 5101

AK

KE

AGH150W-4
Achtung Danger Hochspannung High Voltage

Accessories External clear text measuring instruments, 400 A Type Art. no. B 986 763 B 986 764

IRDH275
+

7204-1421 9604-1421

External clear text measuring instruments, 20 mA Type 9620-1421 A-ISOMETER IRDH275 with coupling unit AGH520S Coupling units Type AGH150W AGH204S-4 AGH520S Nominal voltage UN DC 0 ... 1760 V AC 0 ... 1300 V/DC 0 ... 150 V AC 0 ... 7200 V Art. no. B 9801 8006 B 914 013 B 913 033 Art. no. B 986 841

AGH520S
5 4 3

A-ISOMETER IRDH275 with coupling unit AGH204S-4

1 2

1 - without power converter UN = 3AC 0 . . . 1650 V(DC max. 1000 V) 2 - with power converter UN = 3AC 0 . . . 1300 V (peak voltage downstream of the rectifier or intermediate circuit voltage max. 1840 V) 106 015 en / 05.2003

A-ISOMETER IRDH275

Technical data A-ISOMETER IRDH275 Insulation coordination acc. to IEC 60664-1 Rated voltage Rated impulse voltage/pollution degree Voltage ranges Nominal voltage range Un Nominal frequency fn Supply voltage Us Frequency range Us Max. power consumption Switching components Switching components Operating principle Factory setting (Alarm 1/Alarm 2) Electrical endurance Contact class Rated contact voltage Making capacity Breaking capacity Minimum contact current at DC 24 V

AC 800 V 8 kV / 3

1 AC / 3 AC 0 ...793 V, DC 0 ...650 V 0,1 ... 400 Hz AC 88 ... 264 V, DC 77 ... 286 V 20 ... 400 Hz 14 VA

Response values Response value Ran1 (Alarm 1) 1 k ... 10 M Response value Ran2 (Alarm 2) 1 k ... 10 M Absolute error (1 k ... 10 k) + 2 k Relative percentage error (10 k ... 10 M) 0% ... +20% Response time tan at RF = 0.5 x Ran and Ce = 1 F <5s Measuring time see characteristic curve (TGH page 69) Hysteresis (1 k ... 10 k)/(10 k ... 10 M) +2 k/ 25 % Measuring circuit Measuring voltage Um (peak value) Measuring current Im max. (at RF = 0 ) Internal DC resistance Ri Internal impedance Zi, at 50 Hz Max. permissible extraneous DC voltage Ufg Max. permissible system leakage capacitance Ce Factory setting Displays Display, illuminated Characters (number of characters) Display range, measuring value Relative percentage error (1 k ... 10 k) Relative percentage error (1 k ... 10 k) 50 V < 278 A > 180 k > 180 k DC 1200 V max. 500 F 150 F

2 changeover contacts N/O or N/C operation N/O operation 12 000 switching operations IIB acc. to DIN IEC 60255 part 0-20 AC 250 V / DC 300 V UC 5 A 2 A,AC 230 V,cos phi = 0.4 0.2 A,DC 220 V,L/R = 0,04 s 2 mA (50 mW)

double-line display 2x 16 1 k ... 10 M 1 k 20 %

General data Shock resistance IEC 60068-2-27 (device in operation) 15 g / 11 ms Bumping IEC 60068-2-29 (during transport) 40 g /6 ms Vibration resistance IEC 60068-2-6 (device in operation) 1 g / 10 ... 150 Hz Vibration resistance IEC 60068-2-6 (during transport) 2 g / 10 ... 150 Hz Ambient temperature (during operation) -10 C ... + 55 C Storage temperature range -40 C ... + 70 C Climatic class acc. to IEC 60721-3-3 3K5 Operating mode continuous operation Mounting as indicated on the display Connection screw terminals Connection, rigid, flexible 0.2 ... 4 mm2/ 0.2 ... 2.5 mm2 Connection,flexible with connector sleeve,without/with plastic sleeve 0.25 mm2 ... 2.5 mm2 Conductor sizes (AWG) 24-12 Protection class, internal components (DIN EN 60529) IP30 Protection class, terminals (DIN EN 60529) IP20 Type of enclosure X112, free from halogen DIN rail mounting IEC 60715 Flammability class UL94V-0 Weight approx. ca. 150 g Option W Shock resistance IEC 60068-2-27 (Device in operation) 30 g / 11 ms Bumping IEC 60068-2-29 (during transport) 40 g / 6 ms Vibration resistance IEC 60068-2-6 1.6 mm/10 ...25 Hz,4 g/25 ...150 Hz Ambient temperature (during operation) -25 C ... +70 C Storage temperature range -40 C ... +85 C Screw mounting 2x M4

Outputs TEST / RESET button internal/external Current output for measuring instrument SKMP (scale centre point = 120 ) Current output IRDH275/IRDH275B (max. load) 400 A (12.5 k)/20 mA (500 ) Accuracy current output (1 k ... 1 M) 10 %, 1 k Serial interface IRDH275 IRDH275B Max. cable length Recommended cable (screened, screen one site connected to PE) Terminating resistor RS485 / ASCII RS485 / BMS 1200 m J(Y)STY 2x 0,6 120 (0,5 W)

106 015 en / 05.2003