1111 W.

35th Street, Chicago, IL 60609 USA


773.869.1234 (USA) 773.869.1212 (International)
www.tripplite.com
Copyright 2009 Tripp Lite. All rights reserved.
Important Safety Warnings
Mounting
Connection
Features
Operation
Storage, Service, Warranty and Insurance
Specifications
Espaol/Franais/lyccknn
2
3
5
10
21
24
25
26/51/76
Optional Connection 17
Power ON/OFF 18
Manual Bypass Operation 20
Owners Manual
SmartOnline

Single-Phase 5kVA, 6kVA & 10kVA


Intelligent True On-Line UPS Systems (Rackmount/Tower)
For all UPS system modules (power module, transformer module and battery module).
Select UPS system modules may include separate instruction or warning sheets which should be used
in conjunction with this manual.
Not suitable for mobile applications.
W
a
r
r
a
n
t
y


R
e
g
i
s
t
r
a
t
i
o
n
R
e
g
i
s
t
e
r

o
n
-
l
i
n
e

t
o
d
a
y

f
o
r

a


c
h
a
n
c
e

t
o

w
i
n

a

F
R
E
E

T
r
i
p
p

L
i
t
e

p
r
o
d
u
c
t
!

w
w
w
.
t
r
i
p
p
l
i
t
e
.
c
o
m
/
w
a
r
r
a
n
t
y
2
Important Safety Warnings
SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and
maintenance of all Tripp Lite SmartOnline Rackmount/Tower UPS Systems and their batteries.
UPS Location Warnings
Install your UPS indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.
Install your UPS in a structurally sound area. Your UPS is extremely heavy; take care when moving and lifting the unit.
Only operate your UPS at indoor temperatures between 32 F and 104 F (between 0 C and 40 C). For best results, keep indoor
temperatures between 62 F and 84 F (between 17 C and 29 C).
Leave adequate space around all sides of the UPS for proper ventilation.
Do not install the UPS near magnetic storage media, as this may result in data corruption.
Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the units
internal cooling, eventually causing product damage not covered under warranty.
UPS Connection Warnings
The power supply for this unit must be single-phase rated in accordance with the equipment nameplate. It also must be suitably grounded.
Equipment Connection Warnings
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of
the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the
presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
Connect your UPS power modules and/or transformer modules grounding terminal to a grounding electrode conductor.
The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not connected to an AC supply.
Maintenance Warnings
Your UPS power module, transformer module and battery module(s) do not require routine maintenance. Do not open them for any
reason. There are no user-serviceable parts inside.
Battery Warnings
Do not operate your UPS without connecting it to an external battery module.
Connect only Tripp Lite battery modules (of the correct type and voltage) to your UPS power module's external battery connector.
Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose
of the batteries in a fire. Do not open the UPS or batteries. Do not short or bridge the battery terminals with any object. Unplug and
turn off the UPS before performing battery replacement. Use tools with insulated handles. There are no user-serviceable parts inside
the UPS. Battery replacement should be performed only by authorized service personnel using the same number and type of batteries
(sealed Lead-Acid). The batteries are recyclable. Refer to your local codes for disposal requirements or in the USA only call 1-800-
SAV-LEAD or 1-800-8-BATTERY (1-800-822-8837) or visit www.rbrc.com for recycling information. Tripp Lite offers a complete
line of UPS System Replacement Battery Cartridges (R.B.C.).Visit Tripp Lite on the Web at
www.tripplite.com/support/battery/index.cfm to locate the specific replacement battery for your UPS.
Fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number
and type.
Service and repair should be done only by trained personnel. Prior to any service work performed on hardwired power modules, they
should be turned off or manually bypassed via the transformer. Prior to any service work performed on power modules that plug
directly into wall outlets, they should be turned off and unplugged. Note that potentially lethal voltages exist within this unit as long
as the battery supply is connected.
Do not connect or disconnect battery module(s) while the UPS is operating from the battery supply or when the transformer module
is not in bypass mode (if your UPS system includes a transformer module with a bypass switch).
During "hot-swap" battery module replacement your UPS will be unable to provide battery backup in the event of a blackout.
3
Mounting (Rack)
1
4-Post Mounting
1
2
3
A
B
C
F
E
G
4
Connect the two segments of each shelf

A

using the included attached screws and
wing nuts

B
. Leave the screws slightly loose so that the shelves can be adjusted in
the next step.
Adjust each shelf to fit your rack, then mount them in the lowest available space of
your rack with the screws, nuts and washers provided

C
. Note that the support
ledges should face inward. Tighten the wingnuts that connect the shelf segments
D
.
Attach mounting ears

E
to the front mounting holes of your equipment

F
using
the screws provided

G
. The ears should face forward.
Using an assistant, lift your equipment and slide it onto the mounting shelves.
Attach your equipment to the rack by passing the screws, nuts and washers
(user-provided)
H

through its mounting ears and into the rack rails.
To mount your equipment in a 2-post rack, you must purchase a Tripp Lite 2-Post
Rackmount Installation Kit (model: 2POSTRMKIT, sold separately) for each module
installed. See the Installation Kit's owner's manual for complete mounting instructions.
4
Mount your equipment in either a 4-post or 2-post rack or rack enclosure.The user must determine the fitness of hardware and procedures
before mounting. If hardware and procedures are not suitable for your application, contact the manufacturer of your rack or rack enclosure.
The procedures described in this manual are for common rack and rack enclosure types and may not be appropriate for all applications.
WARNING!
All UPS System modules are extremely heavy! Use caution while lifting and mounting! User must properly
stabilize the module while lifting and mounting!
2
3
2-Post (Telecom) Mounting
B
D
H
4
Mounting (Tower)
All modules can be mounted in an upright, tower position when used with optional adjustable base stands, sold separately from Tripp Lite
(model #: 2-9USTAND). When mounting modules on the adjustable base stands, make sure that the power module's control panel is towards
the top. Also, if you are installing a transformer module, place it between the power module and its battery module.
WARNING!
All UPS System modules are extremely heavy! Use caution
while lifting and mounting! User must properly
stabilize the module while lifting and mounting!
Rotate the power modules Control Panel to view it easier while the UPS is tower
mounted. Insert a small screwdriver, or other tool, in the slots on either side of the
Control Panel. Pop the panel out; rotate it; and pop the panel back into place.
5
Features
There are three separate UPS system modules available from Tripp Lite (a power module, a transformer module and a battery module) used
in a variety of combinations. Familiarize yourself with the location and function of the features on each module before installing and oper-
ating your UPS system. The power module is the only module which includes front panel features.
Power Module Front Panel Controls
1. LCD DISPLAY: This backlit (16 2 character) dot matrix display indicates a wide range of UPS operating conditions and diagnostic
data. It also displays UPS settings and options when the UPS is in setup mode.
2. ON/MUTE BUTTON: Press this button and hold it until you hear a beep to turn the UPS systems inverter ON. If the UPSs battery
alarm is sounding, press this button to silence it.
3. SCROLL DOWN/EXIT SETUP BUTTON: This button allows you to browse through different options and power readings on the
LCD display. Momentarily pressing it causes the LCD screen to display a different power reading (see Operation). Pressing it and the
SCROLL UP Button together puts the UPS in setup mode, where this button is used to scroll through setup options and to exit setup
mode.
4. SCROLL UP/SELECT BUTTON: This button allows you to browse through different options and power readings on the LCD display.
Momentarily pressing it causes the LCD screen to display a different power reading (see Operation). Pressing it and the
SCROLL DOWN Button together puts the UPS in setup mode, where this button is used to select setup options.
5. OFF BUTTON: Press this button until you hear a beep to turn the UPS systems inverter OFF.
6. O/P (OUTPUT) LED: This green light will illuminate to indicate your UPS is supplying AC power to connected equipment.
7. DC/AC (INVERTER) LED: This green light will illuminate to indicate the UPSs DC/AC inverter is activated.
8. BYPASS LED: This green light will illuminate when the UPS is providing filtered mains power without engaging its converter or
inverter. If this LED is lit, connected equipment will not receive battery power in the event of a blackout.
9. AC/DC (Converter) LED: This green light will illuminate to indicate the UPSs AC/DC converter is charging the connected battery
pack(s).
10. BATTERY LED: This red light will illuminate when the UPS is discharging the battery to provide connected equipment with AC
power. An alarm will sound which can be silenced by pressing the ON/MUTE Button. This LED will remain lit after the alarm is
silenced.
11. I/P (INPUT) LED: This green light will illuminate to indicate an AC input supply is present.
12. ACCESS SLOTS: To rotate the controls, insert a flathead screwdriver into these slots and gently lever the panel out. Taking care not
to excessively twist or yank the cables connecting the controls to the rest of the UPS, turn the controls to the desired orientation and
reinsert them.
1
2 3 4 5
6 8 7 9 10 11
12 12
6
Features (Rear Panel) see page 9 for feature descriptions
5kVA Power Module
5kVA Transformer Module
5kVA Battery Module*
* The 5kVA Power Module is shipped with a Battery Module
which is not expandable; however, the Power Module is fully
compatible with Tripp Lite Battery Modules which are
expandable (Tripp Lite model # BP240V10RT-3U, sold sepa-
rately) if extended runtime is required.
11
6
7
8 9 10
3
12 12
13 13 14
25
25
24 25 24
26
19
28
7
Features (Rear Panel) see page 9 for feature descriptions
6kVA Power Module
6kVA Transformer Module
6kVA Battery Module*
5 4
6
7
8 9 10
20
20
19
16
27 28
3
1 2
15
17
22 23
* Expandable Battery Module (Tripp Lite model #
BP240V10RT-3U) shown. Depending on the model ordered,
the 6kVA Power Module may have been shipped with an
expandable Battery Module (like the one shown above) or one
which is not expandable. All 6kVA Power Modules, however,
are fully compatible with BP240V10RT-3U Battery Modules
(sold separately) if extended runtime is required.
8
Features (Rear Panel) see page 9 for feature descriptions
10kVA Power Module
4 5 6
7
8 9
10
3
10kVA Battery Module
27
28
10kVA Transformer Module
20 18 15 16
21
1 2
19
22 23
* Expandable Battery Module (Tripp Lite model #
BP240V10RT-3U) shown. Depending on the model ordered,
the 10kVA Power Module may have been shipped with an
expandable Battery Module (like the one shown above) or
one which is not expandable. All 10kVA Power Modules,
however, are fully compatible with BP240V10RT-3U Battery
Modules (sold separately) if extended runtime is required.
9
Features (Rear Panel) continued
Power Module Feature Description
1. Output Terminal Block (6kVA and 10kVA models only): Use these terminals to connect your power module to your equipment or to
the transformer module. Unscrew and remove the cover over the block for access.
2. Input Terminal Block (6kVA and 10kVA models only): Use these terminals to connect your power module to utility power or to the
transformer module. Unscrew and remove the cover over the block for access.
3. External Battery Connector: Use this to connect one or more Tripp Lite battery modules to the power module. Remove the cover for
access. The power module will not start without a connection to a charged battery module. Refer to the battery module owners manual
for connection instructions and safety warnings.
4. AC Input Breaker (6kVA and 10kVA models only): One double-pole circuit breaker controls input power to the power module.
5. AC Output Breaker (6kVA and 10kVA models only): One double-pole circuit breaker controls output power from the power mod-
ule.
6. Exhaust Fan: This cools and ventilates the inside of the power module.
7. Accessory Slot: Remove the small cover panel to install optional accessories to remotely control and monitor your UPS system. Visit
Tripp Lite on the Web (www.tripplite.com) to learn about available SNMP, network management and connectivity products that may be
installed in this slot.
8. EPO (Emergency Power Off) Port: The power module features an EPO port that may be used to connect the power module to a contact
closure switch to enable emergency power off. See Optional Connection section for details.
9. RS-232 Communication Port: This female DB9 serial port may be used to connect your UPS to a workstation or server. It uses RS-232
protocol to communicate with a connected computer. It is used with Tripp Lite software and the included serial cable to monitor and
manage the UPS remotely over a network and to automatically save open files and shut down equipment during a blackout. See
Optional Connection for details.
10. Dry Contact Interface Port: This female DB9 port sends contact-closure signals to indicate line-fail and low-battery status. See
Optional Connection for details.
11. AC Output 1 Breaker (5kVA models only): One double-pole circuit breaker controls output power from the 5kVA power module's
AC receptacles labelled "Output 1."
12. AC Output 1 Receptacles (5kVA models only): Accepts direct plug-in connection of NEMA L6-20P equipment plugs.
13. AC Output 2 Receptacles (5kVA models only): Accepts direct plug-in connection of NEMA L6-30P equipment plugs. Either
receptacle also accepts direct plug-in connection of transformer connector cable (if used).
14. AC Input Cord (5kVA models only): Connects directly to wall receptacle providing 200/208/220/230 or 240V AC utility power.
Transformer Module Feature Description (Transformer Module not included with hardwire (HV) models.)
15. Utility Input Terminal Block (6kVA and 10kVA models only): Use these terminals to connect your transformer module to utility
power. Unscrew and remove the cover over the block for access.
16. Equipment Output Terminal Block (6kVA and 10kVA models only): Use these terminals to connect your equipment to the trans-
former module. Unscrew and remove the cover over the block for access.
17. Cable for Power Module Connection (6kVA models only): Connects the transformer module to the power modules input/output after
the power modules terminal blocks have been removed. See Connection section for details.
18 Hardwire Terminal Block for Power Module Connection (10kVA models only): Use these terminals to connect the transformer
module to the power modules input and output terminal blocks. See Connection section for details.
19. Overtemperature Reset Breaker: This circuit breaker trips if the units temperature climbs too high.
20. AC to UPS Breaker (6kVA and 10kVA models only): One double-pole circuit breaker controls the transformer modules power
output to the UPS.
21. Output Breaker (6kVA and 10kVA models only): One triple-pole circuit breaker controls the transformer modules power output to
connected equipment.
22. Manual Bypass Switch (6kVA and 10kVA models only): This red and yellow dial is used to circumvent the power module while still
supporting connected equipment when performing power module maintenance. While this switch is on BYPASS, connected equipment
will receive filtered AC mains power from the transformer module, but the equipment will not receive battery power in the event of a
blackout. See Manual Bypass Operation section for complete bypass procedure.
WARNING! For qualified service personnel only. Failure to follow the bypass procedure completely will not
adequately power down the UPS power module, resulting in the continued risk of death or injury from potential
contact with high voltage.
10
Features (Rear Panel) continued
Battery Module Feature Description
27. Input Connector (select Battery Modules only): Use this connector to daisy chain additional battery modules onto the first. Remove
the cover panel for access. Refer to the battery module owners manual for connection instructions and safety warnings.
28. Output Cable: Use this cable to connect the battery module to the power module or to another battery module. The power module will not start
without a connection to a charged battery module. Refer to the battery module owners manual for connection instructions and safety
warnings.
23. Input Voltage Select Switch (6kVA and 10kVA models only): Use this switch to set the transformer module's input voltage (either
200V AC, 208V AC or 240V AC). See Connection section for details.
24. AC Output Receptacles (5kVA models only): Accepts direct plug-in connection of NEMA 5-15P or NEMA 5-20P equipment plugs.
25. AC Output Breakers (5kVA models only): Push-button breakers control output power to transformer module's AC Output Receptacles
which are directly adjacent.
26. Cable for Power Module Connection (5kVA models only): Plugs directly into either of the 5kVA power module's AC Output 2
Receptacles. NOTE: this cable should only be plugged into the 5kVA power module.
Connection

Wiring must be done by a qualified electrician.
The UPS power module may be installed on its own or connected to an isolation transformer module. Both applications require the power module
to be connected to a battery module.
When making wiring connections, observe the cable connection regulations appropriate to your area [e.g. National Electrical Code (NEC)
in the U.S.] at all times. Be sure to install an easily accessible disconnect switch in your installation wiring so you may cut off the UPSs
AC input during fires and other emergencies. Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten
connections with a torque of not less than 24-28 inch-pounds (2.7-3.2 NM).
Make sure that your equipment is properly grounded.
Using cables of improper size may damage your equipment and cause fire hazards. Choose appropriate cabling and protection circuits to
make wiring connections (Ground conductors must be the same size and type as the power conductors used):
RATED INPUT CURRENT RATED OUTPUT CURRENT RATED OUTPUT CURRENT OUTPUT PROTECTION
200 - 240 (1, 2-Wire + PE) 200 - 240V (1, 2-Wire + PE) 120V (1, 2-Wire + PE) CIRCUIT
6kVA Models 30A 8 AWG (10mm
2
) 30A 8 AWG (10mm
2
) 2 30A 8 AWG (10mm
2
) 30A
10kVA Models 50A 6 AWG (16mm
2
) 50A 6 AWG (16mm
2
) 2 50A 6 AWG (16mm
2
) 63A
Hardwiring Cautions (6kVA & 10kVA models only)
There are three separate UPS system modules available from Tripp Lite (a power module and a battery module, which are required in all
applications, and a transformer module) used in a variety of combinations. Follow the connection procedure below which matches the combi-
nation of modules which you plan on installing.
Connecting Modules to Each Other and to Utility Power and Equipment
11
Connection continued
Connection Combination #1:
Power Module (5kVA) + Battery Module
Plug your equipment into the power module.
Plug your equipment power cords

A

directly into the power module's AC
Output Receptacles

B
.
Plug the power module into a wall receptacle.
Plug the power module's AC input cord
C
directly into a wall receptacle
D

providing 200/208/220/230 or 240V AC utility power.
Connect the battery module to the power module.
Consult the owner's manual that came with your battery module. Fully insert
the connector on the end of the battery module's cable

E

into the connector
on the rear panel of the power module

F
. Small sparks may occur; this is
normal. NOTE: the power module does not contain internal batteries and will
not start until a battery module is connected. The battery modules are fully
charged prior to shipping. However, before expecting full backup capability
(particularly if the battery module has been stored for an extended period)
after the UPS system is connected to a utility power source, allow the battery
module to recharge for 12 hours. Once the UPS system is in use, it will charge
the batteries and maintain the charge level automatically. NOTE: The 5kVA
Power Module is shipped with a Battery Module which is not expandable;
however, the Power Module is fully compatible with Tripp Lite Battery
Modules which are expandable (Tripp Lite model # BP240V10RT-3U, sold
separately) if extended runtime is required.
1
2
2
3
3
A
B
C
E
F
1
5kVA Power Module Shown
D
12
Connection continued
Connection Combination #2:
Power Module (5kVA) + Transformer Module (5kVA) + Battery Module
Plug the transformer module into the power module.
Plug the transformer module's connector cable

A

directly into either of the
5kVA power module's AC Output 2 Receptacles

B
. NOTE: this cable should
only be plugged into the 5kVA power module.
Plug your equipment into the power module and
transfer module.
Plug your 200/208/220/230/240V AC equipment power cords
C
directly into
the power module's AC Output Receptacles
D
. Plug your 120V AC equipment
power cords
E
directly into the transformer module's AC output receptacles
F
.
Plug the power module into a wall receptacle.
Plug the power module's AC input cord

G

directly into a wall receptacle

H

providing 200/208/220/230 or 240V AC utility power.
Connect the battery module to the power module.
Consult the owner's manual that came with your battery module. Fully insert
the connector on the end of the battery module's cable

I

into the connector
on the rear panel of the power module

J . Small sparks may occur; this is
normal. NOTE: the power module does not contain internal batteries and will
not start until a battery module is connected. The battery modules are fully
charged prior to shipping. However, before expecting full backup capability
(particularly if the battery module has been stored for an extended period)
after the UPS system is connected to a utility power source, allow the battery
module to recharge for 12 hours. Once the UPS system is in use, it will charge
the batteries and maintain the charge level automatically. NOTE: The 5kVA
Power Module is shipped with a Battery Module which is not expandable;
however, the Power Module is fully compatible with Tripp Lite Battery
Modules which are expandable (Tripp Lite model # BP240V10RT-3U, sold
separately) if extended runtime is required.
1
2
2
3
3
A
B
E
H
G
1
5kVA Power Module Shown
4
4
F
D
C
I
J
13
Connection Combination #3:
Power Module (either 6kVA or 10kVA) + Battery Module(s)
Hardwire the power module to your equipment.
Using a screwdriver, remove the top of the box
A
covering the power modules
input and output terminals. Pass a user-supplied cable through the terminal
boxs left knockout
B
and connect it to the power modules output terminals.
Connect the other end of the cable to your equipment.
Hardwire the power module to a utility power source.
Pass a user-supplied cable through the boxs right knockout
C
and connect it
to the power modules input terminals. Replace the top of the terminal box.
Connect the other end of the cable to a utility power source.
Connect the battery module to the power module.
Consult the owners manual that came with your battery module. Fully insert
the connector on the end of the battery modules cable

D

into the connector
on the rear panel of the power module

E
. Small sparks may occur; this is
normal. NOTE: the power module does not contain internal batteries and will not
start until a battery module is connected. The battery modules are fully charged
prior to shipping. However, before expecting full backup capability (particularly
if the battery module has been stored for an extended period) after the UPS system
is connected to a utility power source, allow the battery module to recharge for
12 hours. Once the UPS system is in use, it will charge the batteries and maintain
the charge level automatically. If needed, connect additional battery modules
in a daisy-chain with each modules cable inserted into the previous modules
connector

F
.
connection base step 1
1
connection base step 1
2
2
connection base step 1
3
3
A
B
C
D
E
F
1
6kVA Power Module Shown
Connection continued
14
Connection Combination #4:
Power Module (6kVA) + Transformer Module (6kVA) + Battery Module(s)
Connect the power module to the transformer module.
Using a screwdriver, remove the entire box

A

covering the power modules
input and output terminals. Remove the screws on either side of the terminals.
Grip the terminals

B
and slide them out until you can view the cable connector
release tab

C
. Press the tab down and pull on the cables to release them from
the internal connector
D
. Remove the terminals. Insert the connector cable
from the transformer module
E

into the internal connectors in the power modules
terminal box until the release tab clicks in place. Replace the screws around
the plate. Although they are not needed, retain the power modules terminals
and terminal box cover in case you plan to operate the power module without
the transformer module at a future date.
Hardwire the transformer module to your equipment.
Using a screwdriver, remove the top of the box
F
covering the transformer
modules input and output terminals. Pass a user-supplied cable through the
boxs left knockout
G
and connect it to the transformer modules output ter-
minals. See the AC Output Voltage Diagram
H
to determine which terminal
connections will provide voltage appropriate to your application. Connect the
other end of the cable to your equipment.
Hardwire the transformer module to a utility
power source.
Pass a user-supplied cable through the boxs right knockout

I

and connect it to
the transformer modules input terminals. Replace the top of the box covering
the transformer modules terminals. Connect the other end of the cable to a utility
power source.
connection base step 1
1
1
3
Connection continued
NORMAL
BY PASS
2
2
120V
240V
120V
208V
AC OUTPUT VOLTAGE DIAGRAM
G
NORMAL
BY PASS
3
NORMAL
BY PASS
1
A
B C
E
G
I
F
Connection Combination #4 continued on next page
H
D
15
Select the transformer modules input voltage.
Using a screwdriver, remove the panel covering the transformer modules
Input Voltage Select Switch
J
. Set the switch to match your facilitys input
voltage. Then, use the power modules front panel switches to configure input
voltage on the LCD Display (see Configure your UPSs input and output in
the Power ON/OFF section on page 14).
IMPORTANT NOTE: if your facilitys input voltage is 200V AC, set the trans-
former modules switch to 240V AC, but configure the power module to 200V
AC. If your facilitys input voltage is either 208V AC or 240V AC, the trans-
former module and power module settings must match. The factory default
settings for both modules is 208V. See chart below.
Transformer Module Power Module
Your Facility's Input Voltage Setting Input Voltage Setting
Input Voltage (Rear Panel Switch) (Front Panel Switches/LCD Display)
240V AC 240V AC 240V AC
208V AC 208V AC 208V AC
200V AC 240V AC 200V AC
Connect the battery module to the power module.
Consult the owners manual that came with your battery module. Fully insert
the connector on the end of the battery modules cable
K
into the connector on
the rear panel of the power module
L
. Small sparks may occur; this is normal.
NOTE: the power module does not contain internal batteries and will not start
until a battery module is connected. The battery modules are fully charged prior
to shipping. However, before expecting full backup capability (particularly if
the battery module has been stored for an extended period) after the UPS system
is connected to a utility power source, allow the battery module to recharge for
12 hours. Once the UPS system is in use, it will charge the batteries and maintain
the charge level automatically. If needed, connect additional battery modules in
a daisy-chain with each modules cable inserted into the previous modules
connector
M
.
Connection Combination #5: Power Module (10kVA)
+ Transformer Module (10kVA) + Battery Module(s)
Hardwire the power module to the transformer module.
Using a screwdriver, remove the top of the box
A
covering the power modules input
and output terminals. Remove the top of the box
B
covering the transformer
modules terminals. With supplied cable, connect the power modules input and
output terminals to the corresponding terminals on the transformer modules
Hardwire Terminal Block for Power Module Connection in the boxs right
knockout

C
.
Hardwire the transformer module to your equipment.
Pass a user-supplied cable through the boxs left knockout
D
and connect it to
the transformer modules output terminals. See the AC Output Voltage Diagram
E
to determine which terminal connections will provide voltage appropriate to
your application. Connect the other end of the cable to your equipment.
Connection continued
NORMAL
BY
PASS
240V AC
208V AC
4
5
NORMAL
BY PASS
5
NORMAL
BY PASS
1
1
NORMAL
BY PASS
2
2
4
J
M
L
A
B
C
D
K
Connection Combination #5 continued on next page
120V
240V
120V
208V
AC OUTPUT VOLTAGE DIAGRAM
G
E
16
Connection continued
Hardwire the transformer module to a utility
power source.
Pass a user-supplied cable through the boxs middle knockout
F
and connect
it to the transformer modules input terminals. Connect the other end of the
cable to a utility power source. Replace the top of the boxes covering the power
modules and transformer modules terminals.
Select the transformer modules input voltage.
Using a screwdriver, remove the panel covering the transformer modules
Input Voltage Select Switch
G
. Set the switch to match your facilitys input
voltage. Then, use the power modules front panel switches to configure input
voltage on the LCD Display (see Configure your UPS's input and output in
the Power ON/OFF section).
IMPORTANT NOTE: if your facility's input voltage is 200V AC, set the trans-
former modules switch to 240V AC, but configure the power module to 200V
AC. If your facilitys input voltage is either 208V AC or 240V AC, the trans-
former module and power module settings must match. The factory default
settings for both modules is 208V. See chart below.
Transformer Module Power Module
Your Facilitys Input Voltage Setting Input Voltage Setting
Input Voltage (Rear Panel Switch) (Front Panel Switches/LCD Display)
240V AC 240V AC 240V AC
208V AC 208V AC 208V AC
200V AC 240V AC 200V AC
Connect the battery module to the power module.
Consult the owners manual that came with your battery module. Fully insert
the connector on the end of the battery modules cable

H
into the connector
on the rear panel of the power module
I
. Small sparks may occur; this is normal.
NOTE: the power module does not contain internal batteries and will not supply
power to connected equipment until a battery module is connected. The battery
modules are fully charged prior to shipping. However, if the battery module
has been stored for an extended period, after the UPS system is connected to a
utility power source, allow the battery module to recharge for 12 hours. If
needed, connect additional battery modules in a daisy-chain with each modules
cable inserted into the previous modules connector

J
.
3
NORMAL
BY PASS
3
4
NORMAL
BY PASS
5
5
F
NORMAL
BY
PASS
240V AC
208V AC
4
G
H
I
J
17
The following connections are optional. Your UPS system will function properly without
these connections.
RS-232 Serial Communication Connection
Use the included cable to connect the power modules RS-232 port to the communication
port on your computer. This will allow full network monitoring and control of your UPS
system. Install on your computer the Tripp Lite PowerAlert Software appropriate to
your computers operating system.
Contact-Closure Communication Connection
Use a user-supplied contact-closure DB9 cable to connect the power modules Dry-
Contact port to the communication port on your computer or other equipment. This
will allow basic contact-closure signals to be sent to and from the UPS. Refer to the
following diagram and table to determine the signals carried by this port. Install on your
computer the Tripp Lite PowerAlert Software appropriate to your computers operating sys-
tem.
EPO Port Connection
This optional feature is only for those applications which require connection to a facilitys
Emergency Power Off (EPO) circuit. When the power module is connected to this circuit,
it enables emergency shutdown of the output. Using the included cable, connect the
power modules EPO port to a user-supplied remote switch. The pin assignments for the
EPO port are shown in the following diagram. Note: if there is a short between pins 2
and 3, 2 and 5, 4 and 5, or 3 and 4, the UPS system will power off.
Optional Connection
0
12 V
>2 sec

5 4 3 2 1 9 8 7 6

NO
COM NC
lm in. > 3.3 mA
BACK-UP
REMOTE SHUTDOWN SIGNAL
FROM EXTERNAL
SIGNAL FROM COMPUTER
COM NC
LOWBATTERY
NO
MAXIMUM CAPACITY OF DRY CONTACT: AC250V/3A DC30V/3A
DRY CONTACT INTERFACE DIAGRAM
UPS Operating Pin 8,3 Pin 1,3 Pin 6,3
Mode
Normal OPEN OPEN *
Back Up CLOSE * *
Low Battery CLOSE CLOSE *
Fault * * CLOSE
* Inactive: may be in either state
DRY CONTACT INTERFACE TABLE
1
2
3
4
5
6
X
12V
X
1K

EPO PIN ASSIGNMENT


18
1.To put UPS in BYPASS mode: Press and hold the OFF button
F
until the UPS beeps once.
Put the UPS in SETUP mode by holding down the SCROLL
A
and SELECT
B
buttons simultaneously.
Scroll through setup options (using
A
or
B
) and select the appropriate setting for each of the following options using the
SELECT button
B
.
a. Output Voltage: Select 200, 208, 220, 230 or 240V AC..
b. Output Frequency: Your UPS will auto-select 50 or 60 Hz to match the input.
c. Economy Mode: Your UPS can provide on-line operation with zero transfer-time. It can also operate in a more energy-
efficient, line-interactive mode. Select Economy On to put the UPS in line-interactive mode. Select Economy Off to put
the UPS in on-line mode.
After you have set these options, exit the SETUP mode with the SCROLL button
A
then exit BYPASS mode by holding down
the ON button
C
until you hear the UPS beep once.
2. Turn input to the UPS ON: Press and hold the power module's ON button
C
until you hear a beep to start your UPS in ON BATTERY
mode. Note that some electronic equipment may draw more amps during startup; when starting from battery, consider reducing the initial
load on the UPS. Your UPS will perform a brief self-test and show the results on the LCD Display
D
. See "Startup Self-Test" in the
"Operation" section for the display sequence.
3. To turn the UPS power module and transformer module (if used) OFF: Press the power module's OFF button
F
until you hear a
beep. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display
D
will show
BYPASS MODE. Turn the power module's Output Breaker
E
OFF. Unplug the power module's AC input cord from the wall outlet. If a
transformer module is used, unplug its connector cable from the power module. Your load will no longer be energized, and the LCD
Display
D
will be dark.
Power ON/OFF (5kVA models only)
5kVA Models
5kVA Models
(Front Panel)
D
C A B F
E
19
1. Configure your UPSs input and output: Put your UPS power module into setup mode by holding down both of its scroll buttons (
A

and
B
) at once. Scroll through the setup options (using
A
or
B
) and select the appropriate setting for each of the following options using
the SELECT button

B
.
Input & Output Voltage: Select 200, 208 or 240 VAC.
Output Frequency: Your UPS will autoselect 50 or 60 Hz to match the input.
Economy Mode: Your UPS can provide on-line operation with zero transfer time. It can also operate in a more energy-efficient
line-interactive mode. Select Economy On to put the UPS in line-interactive mode. Select Economy Off to put the UPS in on-line
mode.
After you have set these options, exit the setup mode with the scroll button

A
, then exit bypass mode by holding the ON
button
C
down until you hear a beep.
2. Turn input to the UPS ON: If the UPS power module is connected to a transformer module, turn the tranformer modules AC-to-
UPS and Output Circuit Breakers
D
on. Turn the UPS power modules Input Circuit Breaker
E
on. Press the UPS power modules ON
button
C
until you hear a beep to begin inverter operation. If your AC input is not providing power normally, you may cold start your
UPS from battery. (Your battery must be at least partially charged for this operation to succeed.) Press and hold the ON
C
button until
you hear a beep to start your UPS in ON BATTERY mode. Note that some electronic equipment may draw more amps during startup;
when starting from battery, consider reducing the initial load on the UPS. Your UPS will perform a brief self-test and show the results on
the LCD Display
F
. See Startup Self-Test in the Operation section for the display sequence.
3. Turn UPS output ON: Turn the UPS power modules Output Circuit Breaker
G
ON. If the UPS is connected to a transformer module, turn
the transformer modules Manual Bypass Switch

H
from BYPASS to NORMAL and its Output Circuit Breaker ON. Your UPS will now
provide power to connected equipment.
4. To turn the UPS power module and transformer module OFF: Press the UPS power modules OFF button
I
until you hear a beep.
Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display
F
will show BYPASS
MODE. Turn the UPS power modules Input and Output Circuit Breakers (
E
and
G
) OFF. If the UPS is connected to a transformer module,
turn the transformer modules power AC-to-UPS and Output Circuit Breakers
D
OFF. Your load will no longer be energized, and the
LCD Display
F
will be dark.
Power ON/OFF (6kVA and 10kVA models only)
NORMAL
BY PASS
NORMAL
BY PASS
6kVA Models 10kVA Models
D
E
G
H
E
G
H
6kVA & 10kVA Models
(Front Panel)
D
F
C A B I
20
Manual Bypass Operation
(6kVA and 10kVA models only) (for power module maintenance or replacement)
The following procedure only applies to UPS system configurations that include a 6kVA or 10kVA transformer module. The procedure
details how to service or replace the power module while supplying equipment connected to the transformer module with utility power.
NOTE: since the power module and battery module will be disconnected during the procedure, they will be unable to supply battery backup
support to equipment connected to the transformer module in the event of a blackout.
WARNING! For qualified service personnel only. Failure to follow this procedure completely will not adequately power down the
UPS power module, resulting in the continued risk of death or injury from potential contact with high voltage.
1. Disable PowerAlert Software and disconnect communication cable from the power modules communication ports
A
.
2. Turn transformer modules Bypass Switch

B
to BYPASS.
3. Press power modules OFF Button

C
, if power module is powered, until a beep is heard and a BYPASS MODE message is displayed
in the LCD panel

D
.
4. Turn off the transformer module's double-pole AC to UPS breaker

E
.
5. Turn off the power modules double-pole input breaker

F
and double-pole output breaker
G
.
6. Disconnect battery module cable from the power modules battery connector
H
.
7. FOR 10kVA POWER MODULES ONLY: Use a voltage meter to check the cable connecting the power modules terminal blocks
I
to
the transformer modules terminal blocks
J
to ensure the power module is no longer powered. Once it is no longer powered, remove the
cabling.
The power module is now safely powered down and maintenance/replacement can be performed.
NORMAL
BY PASS
NORMAL
BY PASS
6kVA Models (Rear Panel) 10kVA Models (Rear Panel)
A
B
F
G
A
B
F
G
I
E
D
C
6kVA & 10kVA Models
(Front Panel)
H
E
H
J
21
DIAGNOSTIC MODE
AC/DC OK
DIAGNOSTIC MODE
TESTING INVERTER
ON BATTERY MODE
LOAD = XXX% X.XXKW
Operation
When you turn the UPS ON, it will enter Diagnostic Mode and perform a brief self-test lasting about 15 seconds. The results of the self-test
are shown on the LCD screen in the sequence below.
DIAGNOSTIC MODE
FREQ OUT = XXHz
DIAGNOSTIC MODE
INPUT AC OK
DIAGNOSTIC MODE
INPUT AC OK
DIAGNOSTIC MODE
BATTERY OK
DIAGNOSTIC MODE
CHARGER OK
DIAGNOSTIC MODE
AC/DC OK
DIAGNOSTIC MODE
TESTING INVERTER
ONLINE MODE
LOAD = XXX% X.XXKW
DIAGNOSTIC MODE
FREQ OUT = XXHz
DIAGNOSTIC MODE
INPUT AC BAD
DIAGNOSTIC MODE
INPUT AC BAD
DIAGNOSTIC MODE
BATTERY OK

STARTED WITH
AC INPUT
COLD
START*
*Note: If the UPS is cold started, its BATTERY LED will be lit.
If a problem is detected during the self-test, the LCD will display a error message. If your UPS displays any of the following messages in
its LCD, call Tripp Lite Technical Support at (773) 869-1234 for service.
BAD BATTERY!
CALL FOR SERVICE
CHARGER FAILURE!
CALL FOR SERVICE
AC/DC FAILURE!
CALL FOR SERVICE
INVERTER FAILURE!
CALL FOR SERVICE
OUTPUT FAILURE!
CALL FOR SERVICE
FAN FAILURE!
CALL FOR SERVICE
Startup Self-Test
Failed Self-Test
22
Operation continued
During normal operation, the first line of your LCD Display shows which operating mode your UPS is in: Online, Economy, On Battery,
or Bypass.
Online mode: The UPS provides AC power while utility power is available and switches to On Battery mode instantly (zero transfer time)
if AC power is interrupted.
Economy mode: The UPS provides AC power at high efficiency while utility power is available and switches to On Battery mode quickly
if AC power is interrupted.
On Battery mode: The UPS provides AC power from battery backup so long as battery power lasts. It switches back to Online or Economy
mode if utility power is available and shuts down if it runs out of battery power.
Bypass mode: The UPS provides AC power while utility power is available. The UPS shuts down if AC power is interrupted.
The second line of the LCD Display shows basic power conditions. Push the SCROLL buttons to browse through these basic power conditions
in the sequence shown below.
XXXX MODE
LOAD = XXX% X.XXKW
XXXX MODE
IN = XXXV XX.X Hz
XXXX MODE
OUT = XXXV XX.X Hz
XXXX MODE
BATTERY = XXXVDC

When in the On Battery mode, the UPS power module will beep to inform you that it is using battery power to support connected equipment.
If its connected batteries are at more than half capacity, it will beep every two seconds. If its connected batteries are below half capacity, it
will beep twice a second. If its connected batteries are nearly depleted, the UPS power module will beep continuously.
To silence the On Battery Alarm, press the ON/MUTE button.
When the UPS detects an output overload, its LCD will switch to the following display:
The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to Bypass
Mode to protect its inverter. The duration of the countdown varies with the severity of the overload, as follows:
OVERLOAD!
LOAD = XXX% X.XXKW
Overload Condition Countdown Duration
102% - 125% 1 minute
125% - 150% 30 seconds
>150% Immediate

Normal Operation
On Battery Alarm
Overload Messages
23
Operation continued
While in Bypass Mode, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not
provide battery backup in Bypass Mode.
If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition
on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power
to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.
>15% Higher
Than Nominal
>20% Lower
Than Nominal
Was Too High,
Now Nominal
Was Too Low,
Now Nominal
BYPASS VOLTAGE
CONDITIONS
LCD DISPLAY
MESSAGES
Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: During all these conditions,
the Input, Output and Bypass LEDs will be illuminated.
Extended
Overload
Output Short
Circuit
Remote Shutdown
Command (Via DB9)
Remote Shutdown
Command (Via EPO)
SHUTDOWN
CONDITIONS
LCD DISPLAY
MESSAGES
Internal
Faults
NO OUTPUT
BYPASS AC TOO HI
NO OUTPUT
BYPASS AC TOO LO
BYPASS MODE
BYPASS AC WAS HI
BYPASS MODE
BYPASS AC WAS LO
SHUT DOWN
OVERLOAD XXX%
SHUT DOWN
O/P SHORT CIRCUIT
SHUT DOWN
REMOTE COMMAND
SHUT DOWN
EMERGENCY STOP!
SHUT DOWN
+ DC BUS HIGH
SHUT DOWN
+ DC BUS LOW
SHUT DOWN
- DC BUS HIGH
SHUT DOWN
- DC BUS LOW
SHUT DOWN
OVERTEMPERATURE
Bypass Messages
Shutdown Messages
24
Storage, Service, Warranty, Warranty Registration and Insurance
Before storing your UPS, turn it completely OFF. If you store your UPS for an extended period of time, recharge the UPS batteries for 4 to
6 hours once every three months. Note: after you connect the UPS to utility power, it will automatically begin charging its batteries. If you
leave your UPS batteries discharged for an extended period of time, they will suffer a permanent loss of capacity.
Your SmartOnline UPS System is covered by the 2-year limited warranty period described below. A variety of Extended Warranty and On-Site
Service Programs are also available from Tripp Lite. For more information on service, call Tripp Lite Customer Support at (773) 869-1234.
Before returning your UPS for service, follow these steps:
1. Review the installation and operation instructions in this manual to ensure that the service problem does not originate from a misreading
of the instructions. Also, check that the UPS System's circuit breaker(s) are not tripped. This is the most common cause of service inquiries
which can be easily remedied by following the resetting instructions in this manual.
2. If the problem continues, do not contact or return the UPS to the dealer. Instead, call Tripp Lite at (773) 869-1233. A service technician
will ask for the UPS's model number, serial number and purchase date and will attempt to correct the problem over the phone.
3. If the problem requires service, the technician will issue you a Returned Material Authorization (RMA) number, which is required for
service. They will also discuss proper packaging and shipping procedures. Any damages (direct, indirect, special, incidental or consequen-
tial) to the UPS incurred during shipment to Tripp Lite or an authorized Tripp Lite service center is not covered under warranty. UPS
Systems shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid. Mark the RMA number
on the outside of the package. If the UPS System is within the 2-year warranty period, enclose a copy of your sales receipt. Return the UPS
for service using an insured carrier to the address given to you by the Tripp Lite service technician.
TRIPP LITE warrants its products including batteries to be free from defects in materials and workmanship for a period of two years from
the date of initial purchase. After 90 days from the date of purchase, TRIPP LITEs obligation under this warranty is limited to replacing
parts on such defective products. To obtain service under this warranty, you must call TRIPP LITE or an authorized TRIPP LITE service
center. Products must be returned to TRIPP LITE or an authorized TRIPP LITE service center with transportation charges prepaid and
must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not
apply to equipment which has been damaged by accident, negligence or misapplication or has been altered or modified in any way. This
warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.
The warranties of all TRIPP LITE surge suppressors are null and void if they have been connected to the output of any UPS system. The
warranties of all TRIPP LITE UPS Systems are null and void if a surge suppressor has been connected to its output receptacles.
EXCEPT AS PROVIDED HEREIN, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied war-
ranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR
CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH
DAMAGE. Specifically, TRIPP LITE is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment,
loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.
The policy of TRIPP LITE is one of continuous improvement. Specifications are subject to change without notice.
FCC RADIO/TV INTERFERENCE NOTICE:
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in accordance with the instruction man-
ual, may cause interference to radio communications. Operation of this equipment is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
The user must use shielded cables and connectors with this product. Any changes or modifications to this product not expressly approved by the party responsible for compliance could void the user's authority
to operate the equipment.
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label,
along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the mark-
ing name or model number of the product.
Storage
Service
2-Year Limited Warranty
Regulatory Compliance Identification Numbers
WARRANTY REGISTRATION
Visit www.tripplite.com/warranty
today to register the warranty for
your new Tripp Lite product. Youll
be automatically entered into a
drawing for a chance to win a
FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions
apply. See website for details.
1111 W. 35th Street, Chicago, IL 60609 USA
773.869.1234 (USA) 773.869.1212 (International)
www.tripplite.com
200907004 932407-EN
25
Specifications
The models listed below include a power module, one or two battery modules, and a transformer module. All models include all three
types of modules, with the exception of hardwired (HV) models, which do not include transformer modules. Depending on the model
ordered, the included battery module may be either expandable or nonexpandable. However, if extended runtime is required, all power
modules are fully compatible with expandable Tripp Lite battery modules (Tripp Lite Model # BP240V10RT-3U, sold separately)
Model Information
Model #(s) SU5000RT3UHV* & SU5000RT3U SU6000RT3UHV* & SU6000RT3U SU6000RT3UXR SU10KRT3UHV* & SU10KRT3U
Package Includes:
Power Module (model: SU5000RT3UPM; (model: SU6000RT3UPM; (model: SU6000RT3UPM; (model: SU10KRT3UPM;
series: AGPS5124) series: AGSU60003U) series: AGSU60003U) series: AGSU100003U)
Battery Module #1 (model: BP240V5RT2U; (model: BP240V7RT3U; (model: BP240V10RT-3U; (model: BP240V10RT-3U;
series: AGBP5161) series: AGBP240V7RT3U) series: AGBP240V7RT3U) series: AGBP240V7RT3U)
Non-expandable Non-expandable Non-expandable EXPANDABLE
Battery Module #2 N/A N/A (model: BP240V7RT3U; N/A
series: AGBP240V7RT3U)
EXPANDABLE
Transformer Module (model: SU5000XFMRT2U; (model: SU6000XFMRRT3U; (model: SU6000XFMRRT3U; (model: SU10KXFMRRT3U;
series: AGAC5125) series: AGSM6000SDRT3U) series: AGSM6000SDRT3U) series: AGSM10KSDRT3U)
Approvals: All power modules (UL, cUL, NOM, CE, GOST, SASO, IRAM, FCC Class A). All battery modules except BP240V5RT2U (UL, cUL, NOM). All transformer modules (UL,
cUL, NOM, FCC Class A) * Transformer module not included with hardwired (HV) models.
Input
Input Connection Type 10 ft. cord with L6-30P plug Hardwire Hardwire Hardwire
Input Voltage Range 156V~276V Single Phase 156V~276V Single Phase 156V~276V Single Phase 156V~276V Single Phase
Module Input Voltage 200/208/240V AC 200/208/240V AC 200/208/240V AC 200/208/240V AC
Input Frequency 50/60 Hz 3 Hz 50/60 Hz 3 Hz 50/60 Hz 3 Hz 50/60 Hz 3 Hz
Input Current 20A 22.6A 22.6A 40A
Inrush Current <150A <150A <150A <200A
Power Factor (Full Load) >0.97 >0.97 >0.97 >0.97
Efficiency (Full Load/On-Line) >87% >87% >87% >88%
Power Module Circuit Breaker N/A 40A (2 pole) 40A (2 pole) 63A (2 pole)
Transformer Module Circuit Breaker N/A 40A (2 pole) 40A (2 pole) 63A (2 pole)
Output
VA 5000 6000 6000 10000
Watts (Power Factor: 0.7) 3500 4200 4200 7000
Output Connection Type 4 receptacles on power module Hardwire Hardwire Hardwire
(2 L6-20R and 2 L6-30R) &
12 receptacles on transformer
module (5-15/20R)

Waveform (On-Line) Sinewave Sinewave Sinewave Sinewave
Waveform (On-Battery) Sinewave Sinewave Sinewave Sinewave
Output Voltage (RMS) 120*/200/208/240V AC 100/120/200/208/240V AC 100/120/200/208/240V AC 100/120/200/208/240V AC
Output Frequency 50/60 Hz ( 0.2 Hz on battery) 50/60 Hz ( 0.2 Hz on battery) 50/60 Hz ( 0.2 Hz on battery) 50/60 Hz ( 0.2 Hz on battery)
Voltage Regulation 3% 3% 3% 3%
Max. Harmonic Distortion
(Linear Full Load) <3% <3% <3% <3%
(Non-Linear Full Load) <6% <6% <6% <6%
Overload Capabilities 102% (continuous) 102% (continuous) 102% (continuous) 102% (continuous)
102%~125% (1 min.) 102%~125% (1 min.) 102%~125% (1 min.) 102%~125% (1 min.)
125%~150% (30 sec.) 125%~150% (30 sec.) 125%~150% (30 sec.) 125%~150% (30 sec.)
>150% (Immediate) >150% (Immediate) >150% (Immediate) >150% (Immediate)
Short Circuit Capability 90A 90A* 90A* 160A*
Power Module Circuit Breaker 20A (2 pole) 40A 40A 63A
Transformer Module* Circuit Breaker Four 20A (single pole) 30A (3 pole) 30A (3 pole) 63A (3 pole)
Crest Factor 3:1 3:1 3:1 3:1
* The short circuit capability at 1 2W 120V for the SU6000RT3U and SU6000RT3UXR is greater than 180A, and for the SU10KRT3U is greater than 320A.
Operation
On-Line Transfer Time
(Line to Battery, Battery to Line) 0 ms. 0 ms 0 ms 0 ms
Audible Noise (Full Load @ 1 m) <50 dBA <50 dBA <55 dBA <55 dBA
Indicators
Includes an LCD Display and LEDs (I/P (input), BATTERY, AC/DC, BYPASS DC/AC, O/P (output)).
Communications
Includes an RS-232 DB9 female connector, a dry contact DB9 female connector and an accessory slot.
Physical Specifications
Unit Dimensions (H x W x D)
Power Module 5.25 (3U) x 17.5 x 26 in. 5.25 (3U) x 17.5 x 22.5 in. 5.25 (3U) x 17.5 x 22.5 in. 5.25 (3U) x 17.5 x 22.5 in.
[13.4 x 44.5 x 66 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.]
Transformer Module* 3.5 (2U) x 17.5 x 20.75 in. 5.25 (3U) x 17.5 x 26 in. 5.25 (3U) x 17.5 x 26 in. 5.25 (3U) x 17.5 x 26 in.
[8.9 x 44.5 x 52.7 cm.] [13.4 x 44.5 x 66.1 cm.] [13.4 x 44.5 x 66.1 cm.] [13.4 x 44.5 x 66.1 cm.]
Battery Module #1 3.5 (2U) x 17.5 x 22.50 in. 5.25 (3U) x 17.5 x 22.5 in. 5.25 (3U) x 17.5 x 22.5 in. 5.25 (3U) x 17.5 x 22.5 in.
[8.9 x 44.5 x 52.7 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.]
Battery Module #2 (if applicable) N/A N/A 5.25 (3U) x 17.5 x 22.5 in. N/A
[13.4 x 44.5 x 57.2 cm.]
Shipping Weight
Power Module 58 lb. [27 kg.] 58 lb. [27 kg.] 58 lb. [27 kg.] 68 lb. [31 kg.]
Transformer Module* 60 lb. [28 kg.] 124 lb. [57 kg.] 124 lb. [57 kg.] 124 lb. [57 kg.]
Battery Module #1 138 lb. [63 kg.] 160 lb. [73 kg.] 160 lb. [73 kg.] 160 lb. [73 kg.]
Battery Module #2 (if applicable) N/A N/A 160 lb. [73 kg.] N/A
* Transformer Module not included with hardwire (HV) models.
Optional corded backplate outlet kits available: SUPDM11
(SU6000RT3UHV); SUPDM12 (SU6000RT3U & SU6000RT3UXR);
SUPDM13 (SU6000RT3U & SU6000RT3UXR); SUPDM15
(SU6000RT3U & SU6000RT3UXR); SUPDM16 (SU6000RT3U
and SU6000RT3UXR)
Manual del propietario
1111 W. 35th Street, Chicago, IL 60609 USA
773.869.1234 (USA) 773.869.1212 (International)
www.tripplite.com
Copyright 2009 Tripp Lite. Todos los derechos reservados
SmartOnline

monofsico de 5 kVA, 6 kVA y 10 kVA


Sistemas UPS inteligentes realmente en lnea
(Montaje en bastidor/torre)
Para todos los mdulos del sistema UPS (mdulo de potencia, mdulo de transformador y mdulo de batera) ven-
didos por separado o combinados. Los mdulos de sistemas UPS exclusivos pueden incluir hojas separadas de
instrucciones o de advertencias que deben usarse junto con este manual.
No conveniente para los usos mviles.
Advertencias de seguridad importantes
Montaje
Conexin
Caractersticas
Operacin
Almacenamiento, Servicio y Garanta
Especificaciones
English/Franais/lyccknn
27
28
30
35
46
49
50
1/51/76
Conexin opcional 42
Encendido y apagado 43
Operacin de derivacin manual 45
27
Advertencias de seguridad importantes
GUARDE ESTAS INSTRUCCIONES. Este manual contiene importantes instrucciones y advertencias que debe seguir durante la instalacin y
el mantenimiento de todos los sistemas UPS SmartOnline de Tripp Lite de montaje en torre o bastidor, y sus bateras.
Advertencias sobre la ubicacin del UPS
Instale su UPS bajo techo, lejos de la humedad, el calor, el polvo, la luz solar directa y los contaminantes conductores.
Instale su UPS en un rea estructuralmente slida. Su UPS es muy pesado; tenga cuidado al mover y levantar la unidad.
Slo opere su UPS a temperaturas bajo techo entre 32 F y 104 F (entre 0 C y 40 C) Para obtener mejores resultados, mantenga
las temperaturas bajo techo entre 62 F y 84 F (entre 17 C y 29 C).
Deje una cantidad adecuada de espacio alrededor de todos los lados del UPS para una adecuada ventilacin.
No instale el UPS cerca de medios de almacenamiento magntico ya que puede daar los datos.
No monte esta unidad con el panel frontal o con el panel trasero hacia abajo (Bajo ningn ngulo o inclinacin). Si lo monta de esta
manera, inhibir seriamente el sistema de enfriamiento interno de la unidad; lo que finalmente causar daos al producto que no
estn cubiertos por la garanta.
Advertencias sobre la conexin del UPS
El suministro de alimentacin elctrica para esta unidad debe ser monofsico y debe estar de acuerdo con la placa del equipo.
Tambin debe estar puesta a tierra apropiadamente.
Advertencias sobre la conexin de equipos
El uso de este equipo en aplicaciones de soporte de vida en donde la falla de este equipo pueda razonablemente hacer suponer que
causar fallas en el equipo de soporte de vida o afecte significativamente su seguridad o efectividad, no est recomendado. No use
este equipo en la presencia de una mezcla anestsica inflamable con aire, oxigeno u xido nitroso.
Conecte el terminal de tierra del mdulo de potencia y/o del mdulo del transformador de su no-break a un conductor del electrodo
de tierra.
El UPS est conectado a una fuente de energa de corriente continua (batera). Los terminales de salida pueden estar con energa
cuando el UPS no est conectado a un suministro de corriente alterna.
Advertencias de mantenimiento
Los mdulos de potencia, del transformador y de la batera de su no-break no requieren ningn mantenimiento de rutina. No los abra
por ninguna razn. No hay partes en su interior que requieran mantenimiento por parte del usuario.
Advertencias sobre la batera
No opere su UPS sin conectarlo a un mdulo de batera externa.
Slo conecte mdulos de batera Tripp Lite (del tipo y voltaje correctos) al conector de batera externa del mdulo de potencia de su
no-break.
Debido a que las bateras presentan un peligro de choque elctrico y quemaduras por las altas corrientes de cortocircuito, tome las
precauciones adecuadas. No deseche las bateras en un incinerador. No abra las bateras. No ponga los terminales de la batera en
corto o en puente con ningn objeto. Apague y desconecte el UPS antes de reemplazar la batera. Slo debe cambiar las bateras
personal tcnico debidamente capacitado. Use herramientas con mangos aislados y reemplace las bateras existentes con el mismo
nmero y tipo de bateras nuevas (plomo-cido selladas). Las bateras del UPS son reciclables. Consulte la reglamentacin local para
los requisitos de disposicin de desechos; para los EE.UU. solamente consulte estas fuentes para informacin sobre reciclaje: 1-800-
SAV-LEAD (1-800-728-5323); 1-800-8-BATTERY (1-800-822-8837); www.rbrc.com. Tripp Lite ofrece una lnea completa de
Cartuchos de reemplazo de batera para UPS (R.B.C.). Visite Tripp Lite en la web en www.tripplite.com/support/battery/index.cfm
para localizar la batera de reemplazo especfica para su UPS.
Los fusibles deben ser reemplazados slo por personal autorizado por la fbrica. Los fusibles quemados slo deben reemplazarse con
fusibles del mismo nmero y tipo.
El servicio y la reparacin slo deben llevarse a cabo por personal entrenado. Antes de cualquier trabajo de servicio realizado en
mdulos de potencia cableados, stos deben apagarse o ser puestos en puente manualmente mediante el transformador. Antes de
cualquier trabajo de servicio realizado en mdulos de potencia conectados directamente en tomas de corriente de pared, stos deben
apagarse y desconectarse. Observe que existen voltajes potencialmente fatales dentro de esta unidad mientras est conectada la
alimentacin a la batera.
No conecte ni desconecte los mdulos de batera mientras el no-break est operando con la alimentacin de batera o cuando el
mdulo de transformador no est en modo bypass (si su no-break incluye un mdulo de transformador con un interruptor de bypass).
Durante un reemplazo de su banco de bateras en operacin (hot-swap), su UPS no podr proporcionar respaldo de bateras en caso
de una falla del servicio elctrico.
28
Montaje (Bastidor)
1
Montaje de 4 postes
Conecte los dos segmentos de cada anaquel

A

usando los tornillos incluidos y las
tuercas de mariposa

B
. Deje los tornillos ligeramente flojos de modo que los
anaqueles puedan ajustarse en el siguiente paso.
Ajuste cada anaquel para que se acomode a su bastidor y luego instlelo en el espacio
ms bajo disponible del bastidor con los tornillos, las tuercas y las arandelas
suministradas
C
. Note que los bordes de apoyo deben mirar hacia adentro. Apriete
las tuercas de mariposa que conectan los segmentos de los anaqueles.
Fije las orejas de montaje
E
a los agujeros de montaje de la parte delantera de su
equipo

F
usando los tornillos suministrados
G
. Las orejas deben mirar hacia
adelante.
Con la ayuda de otra persona levante su equipo y deslcelo en los anaqueles de
montaje. Fije su equipo al bastidor pasando los tornillos, las tuercas y las arandelas
(suministradas por el usuario)

H
a travs de las orejas de montaje y dentro de los
rieles del bastidor.
Para montar su equipo en un bastidor de 2 postes, debe comprar un kit de instalacin
para montaje en bastidor de 2 postes (modelo: 2POSTRMKIT, vendido por separado)
para cada mdulo instalado. Consulte el manual del propietario del kit de instalacin
para obtener completas instrucciones de montaje.
4
Monte su equipo en un bastidor o en una caja de bastidor de 2 o 4 postes. El usuario debe determinar la idoneidad de los materiales y acce-
sorios as como de los procedimientos antes del montaje. Si los materiales y procedimientos no son adecuados para su aplicacin, contacte
con el fabricante de su bastidor. Los procedimientos descritos en este manual son para bastidores y cajas de bastidores comunes y podran
no ser apropiados para todas las aplicaciones.
ADVERTENCIA!
Todos los mdulos de no-break son muy pesados! Tenga cuidado al levantarlos y montarlos! El usuario debe
estabilizar apropiadamente el mdulo al levantarlo y montarlo!
2
3
Montaje de 2 postes (Telecomunicaciones)
1
2
3
A
B
C
F
E
G
4
B
D
H
29
Montaje (en torre)
Todos los mdulos pueden montarse en posicin vertical, de torre, cuando se emplean con bases de soporte ajustables opcionales, vendidas
por separado por Tripp Lite (modelo #: 2-9USTAND). Al montar mdulos en las bases de soporte ajustables asegrese que el panel de control
del mdulo de potencia est hacia la parte superior. Adems, si est instalando un mdulo de transformador, colquelo entre el mdulo de
potencia y su mdulo de batera.
ADVERTENCIA!
Todos los mdulos de no-break son muy pesados! Tenga cuidado al
levantarlos y montarlos! El usuario debe estabilizar apropiadamente el
mdulo al levantarlo y montarlo!
Gire el panel de control del mdulo de potencia para obtener mejor visibilidad mientras
el UPS est montado en torre. Introduzca un pequeo destornillador u otra herramienta
en las ranuras en cualquier lado del panel de control. Saque el panel, grelo y colquelo
en posicin nuevamente.
30
Caractersticas
Hay tres mdulos separados del sistema UPS disponibles de Tripp Lite (mdulo de potencia, mdulo de transformador y mdulo de batera)
usados en varias combinaciones. Familiarcese con la ubicacin y funcin de cada mdulo antes de instalar y operar su sistema UPS. El
mdulo de potencia es el nico que incluye funciones del panel frontal.
Controles del panel frontal del mdulo de potencia
1. PANTALLA LCD: Esta pantalla de matriz de puntos retroiluminada (16 2 caracteres) indica una amplia gama de condiciones de
operacin y datos de diagnstico del UPS. Tambin muestra la configuracin y las opciones del UPS durante el modo de configuracin.
2. BOTN ON/MUTE: Presione y mantenga presionado este botn hasta escuchar un pitido para encender el inversor del UPS. Si la
alarma de batera del UPS est sonando, presione este botn para silenciarla.
3. BOTN DESPLAZAR HACIA ABAJO/SALIR DE CONFIGURACIN: Este botn le permite desplazarse a travs de diferentes
opciones y lecturas de potencia en la pantalla LCD. Presionndolo momentneamente, hace que la pantalla LCD muestre una lectura
de potencia diferente (vea Operacin) Presionndolo junto con el botn DESPLAZAR HACIA ARRIBA, pone al UPS en modo de
configuracin, donde este botn se usa para desplazarse a travs de las opciones y salir del modo de configuracin.
4. BOTN DESPLAZAR HACIA ARRIBA/SELECT: Este botn le permite desplazarse a travs de diferentes opciones y lecturas de
potencia en la pantalla LCD. Presionndolo momentneamente hace que la pantalla LCD muestre una lectura de potencia diferente (vea
Operacin) Presionndolo junto con el botn DESPLAZAR HACIA ABAJO, pone al UPS en modo de configuracin, donde este
botn se usa para seleccionar opciones de configuracin.
5. BOTN OFF: Presione este botn hasta que escuche un pitido para apagar el inversor del UPS.
6. LED O/P (SALIDA): Esta luz verde se encender para indicar que su UPS est suministrando energa de corriente alterna al equipo conectado.
7. LED DC/AC (INVERSOR): Esta luz verde se encender para indicar que el inversor de corriente continua a corriente alterna del UPS
est activado.
8. LED BYPASS: Esta luz verde se encender cuando el UPS est proporcionando energa filtrada desde la red sin emplear su convertidor
o inversor. Si este LED est encendido, el equipo conectado no recibir energa de batera en caso de una falla del servicio elctrico.
9. LED AC/DC (Convertidor): Esta luz verde se encender para indicar que el convertidor de corriente alterna a corriente continua del
UPS est cargando los bancos de bateras conectados.
10. LED BATTERY: Esta luz roja se encender cuando el UPS est descargando la batera para proporcionar energa de corriente alterna
al equipo conectado. Sonar una alarma, la que puede ser silenciada presionando el botn ON/MUTE. Este LED permanecer encendido
despus de que la alarma haya sido silenciada.
11. LED I/P (ENTRADA): Esta luz verde se encender para indicar que existe un suministro de alimentacin de corriente alterna.
12. RANURAS DE ACCESO: Para girar los controles, introduzca un destornillador plano en estas ranuras y palanquee suavemente el
panel hacia afuera. Con cuidado de no torcer o tirar excesivamente de los cables que conectan los controles al resto del UPS, gire los
controles hasta la orientacin deseada y introdzcalos nuevamente.
1
2 3 4 5
6 8 7 9 10 11
12 12
31
Caractersticas (Panel posterior) Vea una descripcin de las caractersticas en la pgina 34
Mdulo de potencia de 5 kVA
Mdulo de transformador de 5 kVA
Mdulo de batera de 5 kVA*
* El mdulo de potencia de 5 kVA se despacha con un mdulo de
batera no extensible; sin embargo, el mdulo de potencia es
totalmente compatible con los mdulos de bateras extensibles de
Tripp Lite (Tripp Lite modelo # BP240V10RT-3U, vendido por
separado) si se requiere tiempo de respaldo extendido.
11
6
7
8 9 10
3
12 12
13 13 14
25
25
24 25 24
26
19
28
32
Caractersticas (Panel posterior) Vea una descripcin de las caractersticas en la pgina 34
Mdulo de potencia de 6 kVA
Mdulo de transformador de 6 kVA
Mdulo de batera para modelo de 6 kVA*
5 4
6
7
8 9 10
20
20
19
16
27 28
3
1 2
15
17
22 23
* Mdulo de batera extensible (Tripp Lite modelo #
BP240V10RT-3U) mostrado. Segn el modelo ordenado, el
mdulo de potencia de 6 kVA puede despacharse con un
mdulo de batera extensible (como el mostrado arriba) o no
extensible. Sin embargo, todos los mdulos de potencia de 6
kVA, son totalmente compatibles con el mdulo de bateras
BP240V10RT-3U (vendido por separado) si se requiere tiem-
po de respaldo extensible.
33
Caractersticas (Panel posterior) Vea una descripcin de las caractersticas en la pgina 34
Mdulo de potencia de 10 kVA
Mdulo de batera para modelo de 10 kVA*
Mdulo de transformador de 10 kVA
4 5 6
7
8 9
10
3
27
28
20 18 15 16
21
1 2
19
22 23
* Mdulo de batera extensible (Tripp Lite modelo #
BP240V10RT-3U) mostrado. Segn el modelo ordenado, el
mdulo de potencia de 10 kVA puede despacharse con un
mdulo de batera extensible (como el mostrado arriba) o no
extensible. Sin embargo, todos los mdulos de potencia de 10
kVA, son totalmente compatibles con el mdulo de bateras
BP240V10RT-3U (vendido por separado) si se requiere tiem-
po de respaldo extensible.
34
Caractersticas (Panel) (continuacin)
Descripcin de caractersticas del mdulo de potencia
1. Bloque de terminales de salida (Slo en modelos de 6 kVA y 10 kVA): Use estos terminales para conectar su mdulo de potencia a
su equipo o al mdulo del transformador. Destornille y retire la cubierta del bloque para tener acceso.
2. Bloque de terminales de entrada (Slo en modelos de 6 kVA y 10 kVA): Use estos terminales para conectar su mdulo de potencia
a la alimentacin de la red o al mdulo del transformador. Destornille y retire la cubierta del bloque para tener acceso.
3. Conector de batera externa: selo para conectar uno o ms mdulos de batera de Tripp Lite al mdulo de potencia. Retire la cubierta
para tener acceso. El mdulo de potencia no arrancar sin una conexin a un mdulo de batera cargada. Consulte el manual del
propietario del mdulo de batera para obtener instrucciones sobre conexin y advertencias de seguridad.
4. Interruptor automtico de entrada de CA (Slo en modelos de 6 kVA y 10 kVA): Un interruptor automtico bipolar controla la
entra da de energa al mdulo de potencia.
5. Interruptor automtico de salida de CA (Slo en modelos de 6 kVA y 10 kVA): Un interruptor automtico bipolar controla la
salida de energa del mdulo de potencia.
6. Ventilador extractor: Enfra y ventila el interior del mdulo de potencia.
7. Ranura auxiliar: Retire el pequeo panel de cubierta para instalar accesorios opcionales para el control y monitoreo de su UPS en forma remota.
Visite Tripp Lite en la web (www.tripplite.com) para conocer sobre los productos SNMP, de administracin de redes y de conectividad
que pueden instalarse en esta ranura.
8. Puerto EPO (Desconexin de emergencia): El mdulo de potencia tiene un puerto EPO que puede usarse para conectar el mdulo
de potencia a un interruptor de cierre de contacto que permita el apagado de emergencia. Consulte la seccin Conexin opcional para
ms detalles.
9. Puerto de comunicaciones RS-232: Este puerto serie DB9 hembra puede usarse para conectar su UPS a una estacin de trabajo o a
un servidor. Usa el protocolo RS-232 para comunicarse con una computadora conectada. Se emplea con el software de Tripp Lite y el
cable serie incluido para monitorear y administrar el UPS en forma remota en una red y para guardar automticamente los archivos
abiertos y apagar el equipo durante una falla del servicio elctrico. Consulte la seccin Conexin opcional para ms detalles.
10. Puerto de interfaz de contacto seco: Este puerto DB9 hembra enva seales de cierre de contacto para indicar una falla en la lnea y
un estado de batera baja. Consulte la seccin Conexin opcional para ms detalles.
11. Interruptor de CA Output 1 (slo en modelos de 5 kVA): Un interruptor automtico bipolar controla la potencia de salida de las
tomas de CA del mdulo de potencia de 5 kVA rotuladas "Output 1."
12. Tomas de CA Output 1 (slo en modelos de 5 kVA): Acepta conexin directa de enchufes de equipo NEMA L6-20P.
13. Tomas de CA Output 2 (slo en modelos de 5 kVA): Acepta conexin directa de enchufes de equipo NEMA L6-30P. Cualquier toma
tambin acepta la conexin directa del cable de conector de transformador (si se emplea).
14. Cordn de entrada de CA (slo en modelos de 5 kVA): Conecta directamente a una toma de pared, proporcionando 200/208/220/230
o 240 VCA de energa de la red.
Descripcin de caractersticas del mdulo del transformador
15. Bloque de terminales de entrada de la red (Slo en modelos de 6 kVA y 10 kVA): Use estos terminales para conectar su mdulo
de transformador a la energa de la red. Destornille y retire la cubierta del bloque para tener acceso.
16. Bloque de terminales de salida de equipo (Slo en modelos de 6 kVA y 10 kVA): Use estos terminales para conectar su equipo al
mdulo de transformador. Destornille y retire la cubierta del bloque para tener acceso.
17. Cable para conexin de mdulo de potencia (slo en modelos de 6 kVA): Conecta el mdulo de transformador a la entrada/salida del
mdulo de potencia despus que el bloque de terminales del mdulo de potencia ha sido retirado. Consulte la seccin Conexin para
ms detalles.
18 Bloque de terminales cableados para conexin del mdulo de potencia (slo en modelos de 10 kVA): Use estos terminales para
conectar el mdulo de transformador a los bloques de terminales de entrada y salida del mdulo de potencia. Consulte la seccin
Conexin para ms detalles.
19. Interruptor de reposicin de sobretemperatura: Este interruptor dispara si la temperatura de la unidad aumenta demasiado.
20. Interruptor automtico de CA a UPS (Slo en modelos de 6 kVA y 10 kVA): Un interruptor automtico bipolar controla la salida de
potencia del mdulo de transformador al UPS.
21. Interruptor de salida (Slo en modelos de 6 kVA y 10 kVA): Un interruptor automtico tripolar controla la salida de potencia del
mdulo de transformador al equipo conectado.
22. Interruptor de derivacin manual (Slo en modelos de 6 kVA y 10 kVA): Este dial rojo y amarillo se emplea para poner en derivacin
(bypass) el mdulo de potencia mientras sigue dando soporte al equipo conectado cuando se realiza mantenimiento al mdulo de potencia.
Mientras este interruptor est en BYPASS, el equipo conectado recibir energa de CA filtrada de la red del mdulo del transformador,
pero el equipo no recibir energa de batera en caso de una falla del servicio elctrico. Consulte todo el procedimiento de derivacin en
la seccin Operacin de derivacin manual.
35
Descripcin de caractersticas del mdulo de batera
27. Conector de entrada (Slo mdulos exclusivos de bateras): Use este conector para encadenar mdulos de batera adicionales con el
primero. Retire el panel de cubierta para tener acceso. Consulte el manual del propietario del mdulo de batera para obtener instrucciones
sobre conexin y advertencias de seguridad.
28. Cable de salida: Use este cable para conectar el mdulo de batera al mdulo de potencia en otro mdulo de batera. El mdulo de
potencia no arrancar sin una conexin a un mdulo de batera cargada. Consulte el manual del propietario del mdulo de batera para
obtener instrucciones sobre conexin y advertencias de seguridad.
ADVERTENCIA! Slo para personal de servicio calificado. Si no sigue el procedimiento de derivacin por
completo, no apagar adecuadamente el mdulo de potencia del UPS, produciendo un permanente riesgo de
muerte o lesiones debido a un contacto potencial con alto voltaje.
23. Interruptor selector de voltaje (Slo en modelos de 6 kVA y 10 kVA): Use este interruptor para determinar el voltaje de entrada del
mdulo del transformador (200, 208 o 240 VCA) Consulte la seccin Conexin para ms detalles.
24. Tomas de CA de salida (slo en modelos de 5 kVA): Acepta conexin directa de enchufes de equipo NEMA 5-15P o NEMA 5-20P.
25. Interruptores automticos de CA (slo en modelos de 5 kVA): Interruptores pulsadores controlan la potencia de salida a las tomas
de salida de CA del mdulo del transformador directamente adyacentes.
26. Cable para conexin de mdulo de potencia (slo en modelos de 5 kVA): Se conecta directamente en cualquiera de las tomas de
CA rotuladas "Output 2" del mdulo de potencia de 5 kVA. NOTA: Este cable slo debe conectarse en el mdulo de potencia de
5 kVA.
Caractersticas (Panel) (continuacin)
Conexin

El cableado debe ser realizado por un electricista calificado.
El mdulo de potencia del UPS puede estar instalado slo o conectado a un mdulo de transformador de aislamiento. Ambas aplicaciones
requieren que el mdulo de potencia est conectado a un mdulo de batera.
Al realizar conexiones del cableado, siempre cumpla las reglamentaciones adecuadas para conexin de cables de su rea [por ejemplo, el
Cdigo Elctrico Nacional (NEC) en EE.UU.]. Asegrese de instalar un interruptor de desconexin fcilmente accesible en su cableado
de modo que pueda cortar la entrada de corriente alterna al UPS durante incendios y otras emergencias. Asegrese que los cables estn
dotados de mangas y asegurados por abrazaderas de conectores. Apriete las conexiones con un torque no menor que 24-28 libras-pulgada
(2.7-3.2 Nm)
Asegrese que su equipo est puesto a tierra adecuadamente.
El uso de cables de calibre inadecuado puede daar su equipo y causar riesgos de incendio. Elija los cables y circuitos de proteccin
adecuados para realizar las conexiones del cableado (Los conductores de tierra deben ser del mismo tipo y calibre que los conductores de
energa utilizados):
CORRIENTE DE ENTRADA CORRIENTE DE SALIDA CORRIENTE DE SALIDA
200 - 240 (1, 2 cond. + 200 - 240 V (1, 2 cond. + 120 V (1, 2 cond. + CIRCUITO DE PROTECCIN
forro de polietileno) forro de polietileno) forro de polietileno) DE SALIDA
Modelos de 6 kVA 30A 8 AWG (10 mm
2
) 30A 8 AWG (10mm
2
) 2 30A 8 AWG (10mm
2
) 30A
Modelos de 10 kVA 50A 6 AWG (16mm
2
) 50A 6 AWG (16mm
2
) 2 50A 6 AWG (16mm
2
) 63A
Precauciones del cableado (Slo en modelos de 6 kVA y 10 kVA)
Conexin de mdulos entre s, a la energa de la red y a equipos
Hay tres mdulos separados del UPS disponibles de Tripp Lite (un mdulo de potencia y un mdulo de batera, que son necesarios en todas
las aplicaciones, y un mdulo de transformador) usados en diferentes combinaciones. Siga el procedimiento de conexin indicado a
continuacin de acuerdo con la combinacin de mdulos que planea instalar.
36
Combinacin de conexin #1
Mdulo de potencia (5 kVA) + mdulo de batera
Conecte su equipo en el mdulo de potencia.
Conecte los cordones de alimentacin
A
de su equipo directamente en las
tomas de salida de CA
B
. del mdulo de potencia.
Conecte el mdulo de potencia en una toma de
corriente de pared.
Conecte el cordn de entrada de CA
C
del mdulo de potencia directamente
en una toma de pared
D
proporcionando 200/208/220/230 o 240VCA de
energa de la red.
Conecte el mdulo de batera al mdulo de potencia.
Consulte el manual del propietario incluido con su mdulo de batera.
Introduzca completamente el conector del extremo del cable del mdulo de
batera
E
en el conector de la parte posterior del mdulo de potencia
F
.
Pueden producirse pequeas chispas; esto es normal. NOTA: El mdulo de
potencia no contiene bateras internas y no arrancar si no tiene conectado un
mdulo de batera. Los mdulos de batera son completamente cargados antes
de despacharse. Sin embargo, antes de esperar una completa capacidad de
respaldo (en particular, si el mdulo de batera ha estado almacenado por un
perodo prolongado) despus de conectar el no-break a una fuente de energa
de la red, permita que el mdulo de batera se recargue 12 horas. Luego que
el no-break est en uso, cargar las bateras y mantendr el nivel de carga
automticamente. NOTA: El mdulo de potencia de 5 kVA se despacha con
un mdulo de batera no extensible; sin embargo, el mdulo de potencia es
totalmente compatible con los mdulos de bateras extensibles de Tripp Lite
(Tripp Lite modelo # BP240V10RT-3U, vendido por separado) si se requiere
tiempo de respaldo extendido.
1
2
2
3
3
A
B
C
E
F
1
D
Conexin (continuacin)
Combinacin de conexin #2
Mdulo de potencia (5kVA) + mdulo de transformador (5 kVA) + mdulo de batera
Conecte el mdulo de transformador en el mdulo
de potencia.
Conecte el cable del conector
A
del mdulo del transformador directamente en
cualquiera de las tomas de CA "Output 2"
B
del mdulo de potencia de 5 kVA.
NOTA: Este cable slo debe conectarse en el mdulo de potencia de 5 kVA.
Conecte su equipo en el mdulo de potencia y el
mdulo de transformador.
Conecte los cordones de alimentacin
C
de sus equipos de 200/208/220/230/240
VCA directamente en las tomas de salida de CA
D
del mdulo de potencia.
Conecte los cordones de alimentacin
E
de su equipo de 120 VCA directa-
mente en las tomas de salida de CA
F
del mdulo del transformador.
Conecte el mdulo de potencia en una toma de
corriente de pared.
Conecte el cordn de entrada de CA
G
del mdulo de potencia directamente
en una toma de pared
H
proporcionando 200/208/220/230 o 240VCA de
energa de la red.
Conecte el mdulo de batera al mdulo de potencia.
Consulte el manual del propietario incluido con su mdulo de batera.
Introduzca completamente el conector del extremo del cable del mdulo de
batera
I
en el conector de la parte posterior del mdulo de potencia
J
.
Pueden producirse pequeas chispas, lo que es normal. NOTA: El mdulo de
potencia no contiene bateras internas y no arrancar si no tiene conectado un
mdulo de batera. Los mdulos de batera estn completamente cargados
antes de despacharse. Sin embargo, antes de esperar una completa capacidad
de respaldo (en particular si el mdulo de batera ha estado almacenado por
un perodo prolongado) despus de conectar el no-break a una fuente de ali-
mentacin de la red, permita que el mdulo de batera se recargue 12 horas.
Luego que el no-break est en uso, cargar las bateras y mantendr el nivel
de carga automticamente. NOTA: El mdulo de potencia de 5 kVA se despa-
cha con un mdulo de batera no extensible; sin embargo, el mdulo de poten-
cia es totalmente compatible con los mdulos de bateras extensibles de Tripp
Lite (Tripp Lite modelo # BP240V10RT-3U, vendido por separado) si se
requiere tiempo de respaldo extendido.
37
Conexin (continuacin)
1
2
2
3
3
A
B
E
H
G
1
4
4
F
D
C
I
J
Combinacin de conexin #3: Mdulo de potencia
(de 6 kVA o 10 kVA) + Mdulo(s) de batera
Cablee el mdulo de potencia a su equipo.
Con un destornillador, retire la parte superior de la caja
A
que cubre los terminales
de entrada y salida del mdulo de potencia. Pase un cable suministrado por el
usuario a travs del agujero ciego izquierdo de la caja de terminales
B
y
conctelo a los terminales de salida del mdulo de potencia. Conecte el otro
extremo del cable a su equipo.
Cablee el mdulo de potencia a una fuente de energa
de la red.
Pase un cable suministrado por el usuario a travs del agujero ciego derecho
C
y conctelo a los terminales de entrada del mdulo de potencia. Coloque
nuevamente la tapa de la caja de terminales. Conecte el otro extremo del cable
a una fuente de energa de la red.
Conecte el mdulo de batera al mdulo de potencia.
Consulte el manual del propietario incluido con su mdulo de batera.
Introduzca completamente el conector del extremo del cable del mdulo de
batera
D
en el conector de la parte posterior del mdulo de potencia
E
.
Pueden producirse pequeas chispas; esto es normal. NOTA: El mdulo de
potencia no contiene bateras internas y no arrancar si no tiene conectado un
mdulo de batera. Los mdulos de batera estn completamente cargados
antes de despacharse. Sin embargo, antes de esperar una completa capacidad
de respaldo (en particular si el mdulo de batera ha estado almacenado por
un perodo prolongado) despus de conectar el UPS a una fuente de energa
de la red, permita que el mdulo de batera se cargue 12 horas. Luego de que
el sistema UPS est en uso, cargar las bateras y mantendr el nivel de carga
automticamente. Si es necesario, conecte mdulos de bateras adicionales
encadenados, con el cable de cada mdulo introducido en el conector
F
del
mdulo anterior.
connection base step 1
connection base step 1
connection base step 1
38
1
2
2
3
3
A
B
C
D
E
F
1
Mdulo de potencia de 6 kVA mostrado
Conexin (continuacin)
Combinacin de conexin #4: Mdulo de potencia (6 kVA) +
Mdulo de transformador (6 kVA) + Mdulo(s) de batera
Conecte el mdulo de potencia al mdulo
de transformador.
Con un destornillador, retire la parte superior de la caja
A
que cubre los terminales
de entrada y salida del mdulo de potencia. Retire los tornillos en cualquier
lado de los terminales. Tome los terminales
B
y deslcelos hacia afuera hasta
que pueda ver la lengeta de desenganche
C
del conector del cable. Presione la
lengeta hacia abajo y tire de los cables para soltarlos del conector interno
D
.
Retire los terminales. Introduzca el cable del conector del mdulo de transformador
E
en los conectores internos en la caja de terminales del mdulo de potencia
hasta que la lengeta haga clic. Coloque nuevamente los tornillos alrededor de
la placa. Aunque no son necesarios, conserve los terminales y la cubierta de la
caja de terminales del mdulo de potencia en caso que planee operar el mdulo
de potencia sin el mdulo de transformador posteriormente.
Cablee el mdulo de transformador a su equipo.
Con un destornillador, retire la parte superior de la caja
F
que cubre los terminales
de entrada y salida del mdulo de transformador. Pase un cable suministrado
por el usuario a travs del agujero ciego izquierdo de la caja
G
y conctelo a
los terminales de salida del mdulo de transformador. Vea el Diagrama de
voltaje de salida de CA

H
para determinar las conexiones de terminales que
proporcionarn el voltaje adecuado a su aplicacin. Conecte el otro extremo
del cable a su equipo.
Cablee el mdulo de transformador a una fuente
de energa de la red.
Pase un cable suministrado por el usuario a travs del agujero ciego derecho de
la caja
I
y conctelo a los terminales de entrada del mdulo de transformador.
Coloque nuevamente la parte superior de la caja que cubre los terminales del
mdulo de transformador. Conecte el otro extremo del cable a una fuente de
energa de la red.
connection base step 1
NORMAL
BY PASS
NORMAL
BY PASS
NORMAL
BY PASS
39
1
1
3
Conexin (continuacin)
2
2
120V
240V
120V
208V
DIAGRAMA DE VOLTAJE DE SALIDA DE CA
G
3
1
A
B C
E
G
I
F
Combinacin de conexin #4 (contina en pgina siguiente)
H
D
Seleccione el voltaje de entrada del mdulo
de transformador.
Usando un destornillador, retire el panel que cubre el interruptor selector de
voltaje del mdulo de transformador
J
. Fije el interruptor para que coincida
con el voltaje de entrada de su instalacin. Luego, use los interruptores del
panel frontal del mdulo de potencia para configurar el voltaje de entrada en
la pantalla LCD (consulte Configuracin de la entrada y salida de su UPS en
la seccin Encendido y apagado).
NOTA IMPORTANTE: Si el voltaje de entrada de su instalacin es 200 VCA,
fije el interruptor del mdulo de transformador a 240 VCA, pero configure el
mdulo de potencia a 200 VCA. Si el voltaje de entrada de su instalacin es
208 o 240 VCA, los ajustes del mdulo de transformador y del mdulo de
potencia deben coincidir. El ajuste predeterminado de fbrica para ambos
mdulos es 208 V. Vea la tabla siguiente:
Mdulo de potencia
Mdulo de transformador Ajuste de voltaje de entrada
Voltaje de entrada Ajuste de voltaje de entrada (Interruptores/pantalla
de su instalacin (Interruptor de panel posterior) LCD de panel frontal)
240 VCA 240 VCA 240 VCA
208 VCA 208 VCA 208 VCA
200 VCA 240 VCA 200 VCA
Conecte el mdulo de batera al mdulo de potencia.
Consulte el manual del propietario incluido con su mdulo de batera.
Introduzca completamente el conector del extremo del cable del mdulo de
batera
K
en el conector de la parte posterior del mdulo de potencia
L
.
Pueden producirse pequeas chispas; esto es normal. NOTA: El mdulo de
potencia no contiene bateras internas y no arrancar si no tiene conectado un
mdulo de batera. Los mdulos de batera estn completamente cargados antes
de despacharse. Sin embargo, antes de esperar una completa capacidad de respaldo
(en particular si el mdulo de batera ha estado almacenado por un perodo
prolongado) despus de conectar el UPS a una fuente de energa de la red, permita
que el mdulo de batera se cargue 12 horas. Luego de que el sistema UPS est
en uso, cargar las bateras y mantendr el nivel de carga automticamente. Si
es necesario, conecte mdulos de bateras adicionales encadenados, con el
cable de cada mdulo introducido en el conector
M
del mdulo anterior.
Combinacin de conexin #5: Mdulo de potencia
(10 kVA) + Mdulo de transformador (10 kVA)
+ Mdulo(s) de batera
Cablee el mdulo de potencia al mdulo
de transformador
Con un destornillador, retire la parte superior de la caja
A
que cubre los terminales
de entrada y salida del mdulo de potencia. Coloque nuevamente la parte superior
de la caja
B
que cubre los terminales del mdulo de transformador. Con el
cable suministrado, conecte los terminales de entrada y salida del mdulo de
potencia a los terminales correspondientes en el mdulo del transformador
Hardwire Terminal Block for Power Module Connection en el agujero ciego
derecho de la caja
C
.
NORMAL
BY PASS
NORMAL
BY PASS
NORMAL
BY
PASS
240V AC
208V AC
40
Conexin (continuacin)
4
5
5
1
1
4
J
M
L
A
B
C
K
Combinacin de conexin #5 (contina en pgina siguiente)
Cablee el mdulo de transformador a su equipo.
Pase un cable suministrado por el usuario a travs del agujero ciego izquierdo de
la caja
D
y conctelo a los terminales de salida del mdulo de transformador.
Vea el Diagrama de voltaje de salida de CA

E
para determinar las conexiones
de terminales que proporcionarn el voltaje adecuado a su aplicacin. Conecte
el otro extremo del cable a su equipo.
Cablee el mdulo de transformador a una fuente
de energa de la red.
Pase un cable suministrado por el usuario a travs del agujero ciego central de
la caja

F
y conctelo a los terminales de entrada del mdulo de transformador.
Conecte el otro extremo del cable a una fuente de energa de la red. Coloque
nuevamente la parte superior de la cajas que cubren los terminales de los
mdulos de potencia y del transformador.
Seleccione el voltaje de entrada del mdulo
de transformador.
Usando un destornillador, retire el panel que cubre el interruptor selector de
voltaje del mdulo de transformador
G
. Fije el interruptor para que coincida
con el voltaje de entrada de su instalacin. Luego, use los interruptores del
panel frontal del mdulo de potencia para configurar el voltaje de entrada en
la pantalla LCD (consulte Configuracin de la entrada y salida de su UPS en
la seccin Encendido y apagado en la pgina 36).
NOTA IMPORTANTE: Si el voltaje de entrada de su instalacin es 200 VCA,
fije el interruptor del mdulo de transformador a 240 VCA, pero configure el
mdulo de potencia a 200 VCA. Si el voltaje de entrada de su instalacin es
208 o 240 VCA, los ajustes del mdulo de transformador y del mdulo de
potencia deben coincidir. El ajuste predeterminado de fbrica para ambos
mdulos es 208 V. Vea la tabla siguiente:
Mdulo de transformador Mdulo de potencia
Ajuste de voltaje de Ajuste de voltaje de entrada
Voltaje de entrada entrada (Interruptor de (Interruptores/pantalla
de su instalacin panel posterior) LCD de panel frontal)
240 VCA 240 VCA 240 VCA
208 VCA 208 VCA 208 VCA
200 VCA 240 VCA 200 VCA
Conecte el mdulo de batera al mdulo de potencia.
Consulte el manual del propietario incluido con su mdulo de batera.
Introduzca completamente el conector del extremo del cable del mdulo de
batera
H
en el conector de la parte posterior del mdulo de potencia
I
.
Pueden producirse pequeas chispas; esto es normal. NOTA: El mdulo de
potencia no contiene bateras internas y no suministrar energa al equipo
conectado si no tiene conectado un mdulo de batera. Los mdulos de batera
estn completamente cargados antes de despacharse. Sin embargo, si el mdu-
lo de batera ha estado almacenado por un perodo prolongado, despus de
conectar el UPS a una fuente de energa de la red, permita que el mdulo de
batera se cargue durante 12 horas. Si es necesario, conecte mdulos de bat-
eras adicionales encadenados, con el cable de cada mdulo introducido en el
conector
J
del mdulo anterior.
NORMAL
BY PASS
NORMAL
BY PASS
NORMAL
BY
PASS
240V AC
208V AC
NORMAL
BY PASS
41
3
3
4
5
5
F
4
H
I
J
Conexin (continuacin)
2
D
120V
240V
120V
208V
DIAGRAMA DE VOLTAJE DE SALIDA DE CA
G
E
2
G
42
Las siguientes conexiones son opcionales. Su UPS funcionar correctamente sin ellas.
Conexin de comunicacin serie RS-232
Use el cable incluido para conectar el puerto RS-232 del mdulo de potencia con el
puerto de comunicaciones en su PC. Esto permitir un monitoreo de toda la red y el
control de su sistema UPS. Instale en su computadora el software PowerAlert de Tripp
Lite apropiado para su sistema operativo.
Conexin de comunicaciones de cierre de contacto
Use un cable DB9 de cierre de contacto suministrado por el usuario para conectar el
puerto de contacto seco del mdulo de potencia al puerto de comunicaciones de su PC
u otro equipo. Esto permitir enviar seales bsicas de cierre de contacto al y del UPS.
Consulte el siguiente diagrama y la tabla para determinar las seales transportadas por
este puerto. Instale en su computadora el software PowerAlert de Tripp Lite apropiado
para su sistema operativo.
Conexin de puerto EPO
Esta caracterstica opcional es slo para aquellas aplicaciones que requieran una conexin
al circuito de desconexin de emergencia (EPO) de la instalacin. Cuando el mdulo de
potencia est conectado a este circuito, es posible el apagado de emergencia de la salida.
Usando el cable incluido, conecte el puerto EPO del mdulo de potencia a un interruptor
remoto suministrado por el usuario. La asignacin de los pines para el puerto EPO se
muestra en el diagrama siguiente. Nota: Si hay un corto entre los pines 2 y 3, 2 y 5, 4 y 5,
o 3 y 4, el sistema UPS se apagar.
Conexin opcional
0
12 V
>2 sec

5 4 3 2 1 9 8 7 6

NO
COM NC
lm in. > 3.3 mA
RESPALDO
SEAL EXTERNA PARA
APAGADO REMOTO
SEAL DE COMPUTADORA
COM NC
BATERA BAJA
NO
CAPACIDAD MXIMA DE CONTACTO SECO: CA 250V/3A. CC 30V/3A
DIAGRAMA DE INTERFAZ DE CONTACTO SECO
Modo de Pin 8,3 Pin 1,3 Pin 6,3
operacin
del UPS
Normal ABIERTO ABIERTO *
Respaldo CERRADO * *
Batera baja CERRADO CERRADO *
Falla * * CERRADO
Inactivo: Puede estar en cualquier estado
TABLA DE INTERFAZ DE CONTACTO SECO
ASIGNACIN DE PINES EPO
1
2
3
4
5
6
X
12V
X
1K

43
Encendido y apagado (slo en modelos de 5 kVA)
1.Para poner el UPS en modo BYPASS: Mantenga oprimido el botn OFF (APAGADO)
F
hasta que el UPS emita un pitido.
Ponga el UPS en el modo SETUP (CONFIGURACIN) manteniendo oprimidos los botones SCROLL (DESPLAZAR)
A
y
SELECT (SELECCIONAR)
B
simultneamente.
Desplcese por las opciones de configuracin (usando
A
o
B
) y seleccione la configuracin apropiada para cada una de las
opciones siguientes usando el botn SELECT (SELECCIONAR)
B
.
a. Voltaje de salida: Seleccione 200, 208, 220, 230 o 240V CA.
b. Frecuencia de salida: Su UPS seleccionar automticamente 50 o 60 Hz para que coincida con la entrada.
c. Modo Economa: Su UPS puede proporcionar operacin en lnea con cero tiempo de transferencia. Tambin puede operar
en el modo interactivo, de mayor eficiencia energtica. Seleccione Economy On (Economa s) para configurar el UPS
en el modo interactivo. Seleccione Economy Off (Economa No) para configurar el UPS en el modo en lnea.
Despus de configurar estas opciones, salga del modo SETUP con el botn SCROLL (DESPLAZAMIENTO)
A
, y luego salga
del modo BYPASS (RODEAR) sosteniendo el botn ON (ENCENDIDO)
C
hasta que el UPS emita un pitido.
2. Encienda la entrada al no-break: Presione y mantenga presionado el botn ON
C
del mdulo de potencia hasta que escuche un pitido
para arrancar su no-break en modo ON BATTERY. Note que ciertos equipos electrnicos pueden consumir ms corriente durante el
arranque; al arrancar con batera, considere reducir la carga inicial al no-break. Su no-break realizar una breve auto-prueba y mostrar
los resultados en la pantalla LCD
D
. Consulte "Auto-prueba de arranque" en la seccin "Operacin" para conocer la secuencia en
pantalla.
3. Para apagar el mdulo de potencia y el mdulo del transformador (si se emplea) del no-break: Presione el botn OFF
F
del mdulo
de potencia hasta que escuche un pitido. Su carga todava estar energizada. El inversor ahora est apagado, pero su no-break no est
completamente desactivado. La pantalla LCD
D
indicar BYPASS MODE. Apague el interruptor automtico
E
de la salida del mdulo
de potencia. Desconecte el cordn de alimentacin de CA del mdulo de potencia de la toma de corriente de pared. Si se emplea un
mdulo de transformador, desconecte su cable conector del mdulo de potencia. Su carga ya no estar energizada y la pantalla LCD
D

no estar iluminada.
Modelo de 5 kVA
D
C A B F
E
Modelo de 5 kVA
(Panel frontal)
NORMAL
BY PASS
NORMAL
BY PASS
44
1. Configure la entrada y salida del UPS: Ponga el mdulo de potencia del UPS en modo de configuracin manteniendo presionados
simultneamente ambos botones de desplazamiento (
A
y
B
). Puede desplazarse por las opciones de configuracin (usando
A
o
B
) y
seleccionar el ajuste adecuado para cada una de las siguientes opciones usando el botn SELECT
B
.
Voltaje de entrada y salida: Seleccione 200, 208 o 240 VCA.
Frecuencia de salida: Su UPS seleccionar automticamente 50 o 60 Hz para que corresponda a la frecuencia de entrada.
Modo Economy (Economa): Su UPS puede proporcionar operacin en lnea con un tiempo de transferencia cero. Tambin
puede operar en un modo interactivo con la lnea con mayor eficiencia de energa
Active el modo Economy para poner al UPS en modo interactivo con la lnea. Desactive el modo Economy para poner el UPS
en modo en lnea.
Despus de haber fijado estas opciones, salga del modo de configuracin con el botn de desplazamiento
A
, y salga del modo
Bypass manteniendo presionado el botn ON
C
hasta que escuche un pitido.
2. Encienda la entrada al UPS: Si el mdulo de potencia del UPS est conectado a un mdulo de transformador, encienda los interruptores
automticos
D
CA-a-UPS y de salida del circuito del mdulo del transformador. Encienda el interruptor automtico
E
de entrada del
mdulo de potencia. Presione el botn ON
C
del mdulo de potencia hasta que escuche un pitido para comenzar la operacin del
inversor. Si su entrada de CA no est proporcionando energa en forma normal, puede arrancar en fro su UPS con la batera. (Su batera
debe estar cargada por lo menos parcialmente para que esta operacin tenga resultado) Presione y mantenga presionado el botn ON
C
hasta que escuche un pitido para arrancar su UPS en modo ON BATTERY. Note que ciertos equipos electrnicos pueden consumir
ms corriente durante el arranque; al arrancar con batera, considere reducir la carga inicial al UPS. Su UPS realizar una breve auto-
prueba y mostrar los resultados en la pantalla LCD
F
. Consulte Auto-prueba de arranque en la seccin Operacin para conocer la
secuencia en pantalla.
3. Encienda la salida del UPS: Encienda el interruptor automtico
G
de salida del mdulo de potencia del UPS. Si el UPS est conectado
a un mdulo transformador, cambie el Interruptor de derivacin manual
H
del mdulo de transformador de BYPASS a NORMAL y
encienda su interruptor automtico de salida. Ahora su UPS proporcionar energa al equipo conectado.
4. Para apagar el mdulo de potencia y el mdulo de transformador del UPS: Presione el botn OFF
I
del mdulo de potencia del
UPS hasta que escuche un pitido. Su carga todava estar energizada. El inversor ahora est apagado, pero su UPS no est completamente
desactivado. La pantalla LCD
F
indicar BYPASS MODE. Apague los interruptores automticos de entrada y salida (
E
y
G
) del
mdulo de potencia del UPS. Si el UPS est conectado a un mdulo de transformador, apague los interruptores automticos de
alimentacin CA-a-UPS y de salida del circuito del mdulo del transformador
D
. Su carga ya no estar energizada, y la pantalla LCD
F
no estar iluminada.
Encendido y apagado (Slo en modelos de 6 kVA y 10 kVA)
Modelos de 6 kVA Modelos de 10 kVA
D
E
G
H
E
G
H
Modelos de 6 kVA y 10 kVA
(Panel frontal)
D
F
C A B I
NORMAL
BY PASS
NORMAL
BY PASS
45
Operacin de derivacin manual (Slo en modelos
de 6 kVA y 10 kVA) (para mantenimiento o reemplazo del mdulo de potencia)
El siguiente procedimiento slo se aplica a configuraciones de sistemas UPS que incluyan un mdulo de transformador de 6 kVA o 10 kVA.
El procedimiento explica como dar servicio o reemplazar el mdulo de potencia mientras se suministra energa de la red al equipo conectado
al mdulo de transformador. NOTA: Ya que el mdulo de potencia y el mdulo de batera estarn desconectados durante el procedimiento, no
podrn suministrar soporte de respaldo de batera al equipo conectado al mdulo de transformador en caso de una falla del servicio elctrico.
ADVERTENCIA! Slo para personal de servicio calificado. Si no sigue este procedimiento por completo, no apagar adecuadamente
el mdulo de potencia del UPS, produciendo un permanente riesgo de muerte o lesiones debido a un contacto potencial con alto voltaje.
1. Desactive el software PowerAlert y desconecte el cable de comunicacin de los puertos de comunicaciones
A
del mdulo de potencia.
2. Cambie el interruptor de Bypass
B
del mdulo de transformador a BYPASS.
3. Presione el botn OFF
C
del mdulo de potencia, si el mdulo de potencia estaba activado, hasta que escuche un pitido y se muestre el
mensaje BYPASS MODE en la pantalla LCD

D
.
4. Apague el interruptor automtico bipolar CA a UPS
E
del mdulo del transformador.
5. Apague los interruptores automticos bipolares de entrada
F
y de salida
G
del mdulo de potencia.
6. Desconecte el cable del mdulo de batera del conector de batera
H
del mdulo de potencia.
7. SLO PARA MDULOS DE POTENCIA DE 10 kVA: Use un voltmetro para revisar el cable que conecta los bloques de terminales
I
del mdulo de potencia a los bloques de terminales
J
del mdulo del transformador para asegurarse que el mdulo de potencia ya
no est recibiendo energa. Luego de que ya no est recibiendo energa, retire el cableado.
El mdulo de potencia ahora est apagado en forma segura y pueden realizarse los trabajos de mantenimiento o reemplazo.
Modelos de 6 kVA (Panel posterior) Modelos de 10 kVA (Panel posterior)
A
B
F
G
A
B
F
G
I
E
D
C
Modelos de 6 kVA y 10 kVA
(Panel frontal)
H
E
H
J
46
DIAGNOSTIC MODE
AC/DC OK
DIAGNOSTIC MODE
TESTING INVERTER
ON BATTERY MODE
LOAD = XXX% X.XXKW
Operacin
Cuando enciende el UPS, ingresa al modo de diagnstico y realiza una breve auto-prueba que dura cerca de 15 segundos. Los resultados de la
auto-prueba se muestran en la pantalla LCD en la secuencia indicada a continuacin.
DIAGNOSTIC MODE FREQ
OUT = XXHz
DIAGNOSTIC MODE
INPUT AC OK
DIAGNOSTIC MODE
INPUT AC OK
DIAGNOSTIC MODE
BATTERY OK
DIAGNOSTIC MODE
CHARGER OK
DIAGNOSTIC MODE
AC/DC OK
DIAGNOSTIC MODE
TESTING INVERTER
ONLINE MODE
LOAD = XXX% X.XXKW
DIAGNOSTIC MODE
FREQ OUT = XXHz
DIAGNOSTIC MODE
INPUT AC BAD
DIAGNOSTIC MODE
INPUT AC BAD
DIAGNOSTIC MODE
BATTERY OK

ARRANCADO CON
ENTRADA CA
ARRANQUE
EN FRO*
*Nota: Si el UPS arranca en fro, su LED BATTERY estar encendido.
Si se detecta un problema durante la auto-prueba, la pantalla LCD mostrar un mensaje de error. Si su UPS muestra cualquiera de los
siguientes mensajes en su pantalla LCD, llame al Soporte tcnico de Tripp Lite al (773) 869-1234.
BAD BATTERY!
CALL FOR SERVICE
CHARGER FAILURE!
CALL FOR SERVICE
AC/DC FAILURE!
CALL FOR SERVICE
INVERTER FAILURE!
CALL FOR SERVICE
OUTPUT FAILURE!
CALL FOR SERVICE
FAN FAILURE!
CALL FOR SERVICE
Auto-prueba de arranque
Fallo durante la auto-prueba
MODO DIAGNSTICO
FRECUENCIA
DE SALIDA = XXHz
MODO DIAGNSTICO
ENTRADA CA BIEN
MODO DIAGNSTICO
ENTRADA CA BIEN
MODO DIAGNSTICO
BATERA BIEN
MODO DIAGNSTICO
CARGADOR BIEN
MODO DIAGNSTICO
CA/CC BIEN
MODO DIAGNSTICO
PROBANDO INVERSOR
MODO EN LNEACARGA =
XXX% X.XXKW
MODO DIAGNSTICO
FRECUENCIA
DE SALIDA = XXHz
MODO DIAGNSTICO
ENTRADA CA MAL
MODO DIAGNSTICO
ENTRADA CA MAL
MODO DIAGNSTICO
BATERA BIEN
MODO DIAGNSTICO
CA/CC BIEN
MODO DIAGNSTICO
PROBANDO INVERSOR
MODO CON BATERACARGA =
XXX% X.XXKW
BATERA MAL!
LLAMAR A SERVICIO
FALLA DE CARGADOR!
LLAMAR A SERVICIO
FALLA DE CA/CC!
LLAMAR A SERVICIO
FALLA DE INVERSOR!
LLAMAR A SERVICIO
FALLA DE SALIDA!
LLAMAR A SERVICIO
FALLA DE VENTILADOR
!LLAMAR A SERVICIO
47
Operacin (continuacin)
Durante operacin normal, la primera lnea de su pantalla LCD muestra el modo de operacin de su UPS: Online, Economy, On Battery, o
Bypass.
Modo Online: El UPS proporciona energa de corriente alterna mientras hay disponible energa de la red y cambia a modo On Battery en
forma instantnea (tiempo de transferencia cero) si se interrumpe la energa de CA.
Modo Economy: El UPS proporciona energa de corriente alterna de alta eficiencia mientras hay disponible energa de la red y cambia a
modo On Battery rpidamente si se interrumpe la energa de CA.
Modo On Battery: El UPS proporciona energa de corriente alterna de respaldo de batera por tanto tiempo como dure la energa de la
batera. Regresa a modo Online o Economy si hay energa de la red disponible y se apaga si se agota la energa de batera.
Modo Bypass: El UPS proporciona energa de corriente alterna mientras haya energa de la red disponible. El UPS se apaga si se inter-
rumpe la corriente alterna.
La segunda lnea de la pantalla LCD muestra condiciones bsicas de energa. Presione los botones de desplazamiento para moverse a travs de
estas condiciones en la secuencia siguiente:
XXXX MODE
LOAD = XXX% X.XXKW
XXXX MODE
IN = XXXV XX.X Hz
XXXX MODE
OUT = XXXV XX.X Hz
XXXX MODE
BATTERY = XXXVDC

Cuando est en modo On Battery, el mdulo de potencia del UPS emitir un pitido para informarle que est usando energa de bateras para
dar soporte al equipo conectado. Si sus bateras conectadas estn a ms de la mitad de su capacidad, emitir un pitido cada dos segundos.
Si sus bateras conectadas estn a menos de la mitad de su capacidad, emitir un pitido dos veces por segundo. Si sus bateras conectadas
estn casi agotadas, el mdulo de potencia del UPS emitir pitidos en forma continua.
Para silenciar la alarma On Battery, presione el botn ON/MUTE
Cuando el UPS detecta una sobrecarga de salida, la pantalla LCD cambiar a la siguiente visualizacin:
El UPS luego comenzar una cuenta regresiva. Si el UPS todava est sobrecargado al final del conteo, pasar automticamente a modo Bypass
para proteger su inversor. La duracin del conteo regresivo vara con la gravedad de la sobrecarga, de la manera siguiente:
OVERLOAD!
LOAD = XXX% X.XXKW
Condicin de sobrecarga Duracin del conteo
102% - 125% 1 minuto
125% - 150% 30 segundos
>150% Inmediato

Operacin normal
Alarma On Battery
Mensajes de sobrecarga
MODO XXXX
CARGA = XXX% X.XXKW
MODO XXXX
ENTRADA = XXXV XX.X Hz
MODO XXXX
SALIDA = XXXV XX.X Hz
MODO XXXX
BATERA = XXXVDC
SOBRECARGA!
CARGA = XXX% X.XXKW
48
Operacin (continuacin)
Durante modo Bypass, el UPS vigila su voltaje de entrada y pasa esa energa de entrada al equipo conectado. El UPS no proporcionar
respaldo de batera en modo Bypass.
Si el voltaje de salida se desva de un rango aceptable (entre 15% mayor y 20% menor que el nominal), el UPS indica la condicin en su
LCD y deja de suministrar energa de salida a su carga. Si los niveles de energa regresan a un nivel aceptable, el UPS reanuda el suministro
de energa a la carga, y su pantalla LCD informa que el voltaje de salida era demasiado alto o demasiado bajo, pero que ha regresado a su
valor nominal.
>15% mayor que
el nominal
>20% menor que
el nominal
Era muy alto,
ahora nominal
Era muy bajo,
ahora nominal
CONDICIONES DE
VOLTAJE DE BYPASS
MENSAJES DE
PANTALLA LCD
Su UPS se apagar y la pantalla LCD mostrar un mensaje si detecta una de las siguientes condiciones. Nota: Durante todas estas condiciones,
los LEDs Input, Output y Bypass estarn encendidos.
Sobrecarga prolongada
Cortocircuito en salida
Comando de apagado
remoto (Va DB9)
Comando de apagado
remoto (Va EPO)
CONDICIONES DE
APAGADO
MENSAJES DE
PANTALLA LCD
Fallas internas
NO OUTPUT BYPASS
AC TOO HI
NO OUTPUT BYPASS
AC TOO LO
BYPASS MODE BYPASS
AC WAS HI
BYPASS MODE BYPASS
AC WAS LO
SHUT DOWN
OVERLOAD XXX%
SHUT DOWN
O/P SHORT CIRCUIT
SHUT DOWN
REMOTE COMMAND
SHUT DOWN
EMERGENCY STOP!
SHUT DOWN
+ DC BUS HIGH
SHUT DOWN
+ DC BUS LOW
SHUT DOWN
- DC BUS HIGH
SHUT DOWN
- DC BUS LOW
SHUT DOWN
OVERTEMPERATURE
Mensajes Bypass
Mensajes de apagado
SIN SALIDA DE BYPASSVCA
MUY ALTO
SIN SALIDA DE BYPASSVCA
MUY BAJO
MODO BYPASSVCA
ERA ALTO
MODO BYPASSVCA
ERA BAJO
APAGADO
SOBRECARGA XXX%
APAGADO CORTO
CIRCUITO EN SALIDA
APAGADO
COMANDO REMOTO
APAGADO PARADA DE
EMERGENCIA!
APAGADO BARRA
+ VCC ALTO
APAGADO BARRA
+ VCC BAJO
APAGADO BARRA
+ VCC ALTO
APAGADO BARRA
+ VCC BAJO
APAGADO
SOBRETEMPERATURA
49
Almacenamiento, Servicio y Garanta
Antes de almacenar su no-break, apguelo completamente. Si va a almacenar su no-break por un tiempo prolongado, recargue sus bateras
durante 4 a 6 horas cada tres meses. Nota: Despus de conectar el no-break a la energa de la red, comenzar automticamente a cargar sus
bateras. Si deja descargadas las bateras del no-break durante un tiempo prolongado, sufrirn una prdida de capacidad permanente.
Su no-break SmartOnline est cubierto con la garanta limitada de 2 aos descrita ms adelante. Tripp Lite tiene disponibles varios
programas de Garanta extendida y Servicio en el sitio. Para mayor informacin sobre el servicio, llame al Soporte al cliente de Tripp Lite
al (773) 869-1234.
Antes de enviar su no-break para que le presten servicio, siga los siguientes pasos:
1. Verifique las instrucciones de instalacin y operacin en este manual para asegurarse que el problema de servicio no sea causado por una
mala interpretacin de las instrucciones. Adems, verifique que los interruptores automticos del no-break no hayan disparado. Esta es la
causa ms comn de pedidos de servicio que pueden ser solucionados fcilmente siguiendo las instrucciones de restablecimiento en este
manual.
2. Si el problema contina, no contacte con el distribuidor ni devuelva el no-break. En su lugar, llame a Tripp Lite al (773) 869-1233. Un
tcnico de servicio le pedir el modelo, nmero de serie y fecha de compra del no-break y tratar de resolver el problema a travs del
telfono.
3. Si el problema requiere servicio, el tcnico le emitir un nmero de Autorizacin de devolucin de mercadera (RMA), necesario para
que le presten servicio. Tambin le explicar los procedimientos adecuados de embalaje y despacho. Cualquier dao (directo, indirecto,
especial, accidental o resultante) al no-break producido durante el despacho a Tripp Lite o a un centro autorizado de servicio Tripp Lite no
est cubierto por la garanta. Los no-break enviados a Tripp Lite o a algn centro de servicio autorizado de Tripp Lite deben tener los cargos
de transporte prepagados. Marque el nmero RMA en la parte externa del paquete embalado. Si el no-break est dentro del perodo de
garanta de 2 aos, adjunte una copia de su recibo de compra. Devuelva el no-break para servicio a la direccin dada por el tcnico de Tripp
Lite utilizando un transportista asegurado.
TRIPP LITE garantiza que sus productos que incluyen bateras estn libres de defectos en materiales y mano de obra por un perodo de dos aos a partir de la fecha de compra. Despus de 90 das
de la fecha de compra, la obligacin de TRIPP LITE de acuerdo con esta garanta est limitada a reemplazar componentes en los productos defectuosos. Para obtener servicio de acuerdo con esta
garanta, debe llamar a TRIPP LITE o a un centro de servicio autorizado de TRIPP LITE. Los productos deben ser devueltos a TRIPP LITE o a un centro de servicio autorizado de TRIPP LITE con los
cargos de transporte pagados por adelantado, acompaados de una breve descripcin del problema encontrado y un comprobante de la fecha y el lugar de compra. Esta garanta no se aplica al
equipo que ha sido daado por accidente, negligencia o uso inadecuado, o que ha sido alterado o modificado en alguna forma. Esta garanta solamente se aplica al comprador original que debe haber
registrado correctamente el producto dentro de los 10 das de la compra.
Las garantas de todos los supresores de sobretensiones de TRIPP LITE son nulas si han estado conectados a la salida de cualquier sistema UPS. Las garantas de todos los sistemas UPS de TRIPP
LITE son nulas si un supresor de sobretensiones ha estado conectado a sus tomas de salida.
SALVO POR LO ESTABLECIDO EN ESTE DOCUMENTO, TRIPP LITE NO EXPRESA NINGUNA GARANTA, EXPRESA O IMPLCITA, INCLUYENDO GARANTAS DE COMERCIABILIDAD O
IDONEIDAD PARA UN PROPSITO PARTICULAR. Algunos estados no permiten limitaciones o exclusiones de las garantas implcitas; por lo tanto, las limitaciones o exclusiones mencionadas ante-
riormente pueden no aplicarse al comprador.
SALVO POR LO ESTABLECIDO ANTERIORMENTE, EN NINGN CASO TRIPP LITE SER RESPONSABLE POR DAOS DIRECTOS, INDIRECTOS, ESPECIALES, INCIDENTALES O EMERGENTES,
RESULTANTES DEL USO DE ESTE PRODUCTO, INCLUSO EN EL CASO DE HABERSE INFORMADO DE LA POSIBILIDAD DE DICHOS DAOS. Especficamente, TRIPP LITE no es responsable
por ningn costo, como prdida de ingresos o beneficios, prdida de equipos, prdida de uso de equipos, prdida de software, prdida de datos, costo por reemplazos, reclamaciones de terceras partes,
o lo que corresponda.
TRIPP LITE tiene una poltica de mejoramiento continuo. Las especificaciones estn sujetas a cambio sin previo aviso.
Cumplimiento de las normas de los nmeros de identificacin
Para fines de identificacin y certificacin del cumplimiento de las normas, su producto Tripp Lite tiene asignado un nmero de serie nico. Puede encontrar el nmero de serie en la etiqueta de la
placa de identificacin del producto, junto con los smbolos de aprobacin e informacin requeridos. Al solicitar informacin sobre el cumplimiento de las normas para este producto, siempre men-
cione el nmero de serie. El nmero de serie no debe ser confundido con el nombre de identificacin ni con el nmero de modelo del producto.
Servicio
Garanta limitada de 2 aos
Almacenamiento
1111 W. 35th Street, Chicago, IL 60609 USA
773.869.1234 (USA) 773.869.1212 (International)
www.tripplite.com
200907004 932407-SP
50
Especificaciones
Los modelos indicados a continuacin incluyen un mdulo de potencia, uno o dos mdulos de bateras y un mdulo de transformador.
Segn el modelo ordenado, el mdulo de batera incluido puede ser extensible o no-extensible. Sin embargo, si se requiere tiempo de
respaldo extendido, todos los mdulos de potencia son completamente compatibles con los mdulos de batera extensibles de Tripp Lite
(Tripp Lite modelo # BP240V10RT-3U, vendido por separado).
Informacin del modelo
Modelo #(s) SU5000RT3UHV* y SU5000RT3U SU6000RT3UHV* y SU6000RT3U SU6000RT3UXR SU10KRT3UHV* y SU10KRT3U
Los paquetes incluyen:
Mdulo de potencia (Modelo: SU5000RT3UPM; (Modelo: SU6000RT3UPM; (Modelo: SU6000RT3UPM; (Modelo: SU10KRT3UPM;
Serie: AGPS5124) Serie: AGSU60003U) Serie: AGSU60003U) Serie: AGSU100003U)
Mdulo de batera #1 (Modelo: BP240V5RT2U; (Modelo: BP240V7RT3U; (Modelo: BP240V7RT3U; (Modelo: BP240V10RT-3U;
Serie: AGBP5161) Serie: AGBP240V7RT3U) Serie: AGBP240V7RT3U) Serie: AGBP240V7RT3U)
No extensible No extensible No extensible EXTENSIBLE
Mdulo de batera #2 N/D N/D (Modelo: BP240V10RT3U; N/D
Serie: AGBP240V7RT3U)
EXTENSIBLE
Mdulo del transformador (Modelo: SU5000XFMRT2U; (Modelo: SU6000XFMRRT3U; (Modelo: SU6000XFMRRT3U; (Modelo: SU10KXFMRRT3U;
Serie: AGAC5125) Serie: AGSM6000SDRT3U) Serie: AGSM6000SDRT3U) Serie: AGSM10KSDRT3U)
Aprobado por: Todos los mdulos de potencia (UL, cUL, NOM, CE, GOST, SASO, IRAM, FCC Clase A). Todos los mdulos de batera excepto BP240V5RT2U (UL, cUL, NOM). Todos los mode-
los de transformador (UL, cUL, NOM, FCC Clase A)
Entrada
Tipo de conexin de entrada Cordn de 3 m (10 pies) con enchufe L6-30P Cableado Cableado Cableado
Rango de voltaje de entrada 156V~276V monofsico 156V~276V monofsico 156V~276V monofsico 156V~276V monofsico
Voltaje de entrada del mdulo 200/208/240VCA 200/208/240VCA 200/208/240VCA 200/208/240VCA
Frecuencia de entrada 50/60 Hz 3 Hz 50/60 Hz 3 Hz 50/60 Hz 3 Hz 50/60 Hz 3 Hz
Corriente de entrada 20 A 22.6 A 22.6 A 40 A
Corriente de arranque <150 A <150 A <150 A <200 A
Factor de potencia (plena carga) >0.97 >0.97 >0.97 >0.97
Eficiencia (plena carga/en lnea) >87% >87% >87% >88%
Interruptor automtico del mdulo de potencia N/D 40A (bipolar) 40A (bipolar) 63A (bipolar)
Interruptor automtico del mdulo del transformador N/D 40A (bipolar) 40A (bipolar) 63A (bipolar)
Salida
VA 5000 6000 6000 10000
Vatios (Factor de potencia: 0.7) 3500 4200 4200 7000
Tipo de conexin de salida 4 tomas en mdulo de potencia Cableado Cableado Cableado
(2 L6-20R y 2 L6-30R) y Juegos opcionales con toma de corriente y cordn en placa posterior
12 tomas en mdulo de disponibles: SUPDM11 (SU6000RT3UHV); SUPDM12 (SU6000RT3UHV
transformador (5-15/20R) y SU6000RT3UXR); SUPDM13 (SU6000RT3U y SU6000RT3UXR);
SUPDM15 (SU6000RT3U y SU6000RT3UXR);
SUPDM16 (SU6000RT3U y SU6000RT3UXR)
Forma de onda (con lnea) Onda sinusoidal Onda sinusoidal Onda sinusoidal Onda sinusoidal
Forma de onda (con batera) Onda sinusoidal Onda sinusoidal Onda sinusoidal Onda sinusoidal
Voltaje de salida (RMS) 120*/200/208/240VCA 100/120/200/208/240VCA 100/120/200/208/240VCA 100/120/200/208/240VCA
Frecuencia de salida 50/60 Hz ( 0.2 Hz con batera) 50/60 Hz ( 0.2 Hz con batera) 50/60 Hz ( 0.2 Hz con batera) 50/60 Hz ( 0.2 Hz con batera)
Regulacin de voltaje 3% 3% 3% 3%
Distorsin mxima de armnicos
(Plena carga lineal) <3% <3% <3% 3%
(Plena carga no lineal) <6% <6% <6% 6%
Capacidad de sobrecarga 102% (continua) 102% (continua) 102% (continua) 102% (continua)
102%~125% (1 min.) 102%~125% (1 min.) 102%~125% (1 min.) 102%~125% (1 min.)
125%~150% (30 seg.) 125%~150% (30 seg.) 125%~150% (30 seg.) 125%~150% (30 seg.)
>150% (inmmediato) >150% (inmmediato) >150% (inmmediato) >150% (inmmediato)
Capacidad de cortocircuito 90A 90A* 90A* 160A*
Interruptor automtico del mdulo de potencia 20A (bipolar) 40A 40A 63A
Interruptor automtico de mdulo
de transformador* Cuatro de 20A (unipolar) 30A (tripolar) 30A (tripolar) 63A (tripolar)
Factor de cresta 3:1 3:1 3:1 3:1
* La capacidad de cortocircuito en 2 hilos, monofsico, 120 V para modelos SU6000RT3U y SU6000RT3UXR es mayor que 180 A, y para el SU10KRT3U es mayor que 320 A..
Operacin
Tiempo de transferencia en lnea
(Lnea a batera, batera a lnea) 0 ms 0 ms 0 ms 0 ms
Ruido audible (Plena carga @ 1 m) <50 dBA <50 dBA <55 dBA <55 dBA
Indicadores
Incluye una pantalla LCD y LEDs (I/P (entrada), BATTERY, AC/DC, BYPASS DC/AC, O/P (salida)).
Comunicaciones
Incluye un conector RS-232 hembra, un conector DB9 hembra de contacto seco y una ranura auxiliar.
Especificaciones fsicas
Dimensiones de la unidad (Alt. x ancho x prof., pulg.)
Mdulo de potencia 5.25 (3U) x 17.5 x 26 pulg. 5.25 (3U) x 17.5 x 22.5 pulg. 5.25 (3U) x 17.5 x 22.5 pulg. 5.25 (3U) x 17.5 x 22.5 pulg.
[13.4 x 44.5 x 66 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.]
Mdulo de transformador 3.5 (2U) x 17.5 x 20.75 pulg. 5.25 (3U) x 17.5 x 26 pulg. 5.25 (3U) x 17.5 x 26 pulg. 5.25 (3U) x 17.5 x 26 pulg.
[8.9 x 44.5 x 52.7 cm.] [13.4 x 44.5 x 66.1 cm.] [13.4 x 44.5 x 66.1 cm.] [13.4 x 44.5 x 66.1 cm.]
Mdulo de batera #1 3.5 (2U) x 17.5 x 20.75 pulg. 5.25 (3U) x 17.5 x 22.5 pulg. 5.25 (3U) x 17.5 x 22.5 pulg. 5.25 (3U) x 17.5 x 22.5 pulg.
[8.9 x 44.5 x 52.7 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.]
Mdulo de batera #2 (si es aplicable) N/D N/D 5.25 (3U) x 17.5 x 22.5 pulg. N/D
[13.4 x 44.5 x 57.2 cm.]
Peso de embarque
Mdulo de potencia 58 lb. [27 kg.] 58 lb. [27 kg.] 58 lb. [27 kg.] 68 lb. [31 kg.]
Mdulo de transformador 60 lb. [28 kg.] 124 lb. [57 kg.] 124 lb. [57 kg.] 124 lb. [57 kg.]
Mdulo de batera #1 95 lb. [43 kg.] 160 lb. [73 kg.] 160 lb. [73 kg.] 160 lb. [73 Kg.]
Mdulo de batera #2 (si es aplicable) N/D N/D 160 lb. [73 kg.] N/D
AVISO DE FCC SOBRE INTERFERENCIA DE RADIO / TV:
Nota: Este equipo ha sido probado y cumple con los lmites para un dispositivo digital Clase A, de acuerdo con la Parte 15 de las Reglas FCC. Estos lmites estn diseados para proporcionar una proteccin razonable
contra interferencia perjudicial durante la operacin en un ambiente comercial. Este equipo genera, usa y puede radiar, energa de radio frecuencia, y si no se instala y usa de acuerdo con el manual de instrucciones,
puede causar interferencia a las comunicaciones por radio. Es probable que la operacin de este equipo produzca interferencia perjudicial en cuyo caso el usuario deber corregir la interferencia por su cuenta. El usuario
debe utilizar cables y conectores blindados con este producto. Cualquier cambio o modificacin a este producto no expresamente autorizado por la parte responsable del cumplimiento de las normas, podra anular la
autoridad del usuario para operar el equipo.
Manuel de l'utilisateur
1111 W. 35th Street, Chicago, IL 60609 USA
773.869.1234 (USA) 773.869.1212 (International)
www.tripplite.com
Copyright 2009 Tripp Lite. Tous droits rservs.
SmartOnline

Monophas 5kVA, 6kVA & 10kVA


Intelligent True On-Line UPS Systems
(Montage dans baie/Tour)
Pour tous les Systmes d'alimentation continue sans coupure (module d'alimentation, module de transformateur et
module piles) vendus sparment ou combins. Les modules de Systme d'alimentation continue sans coupure de
slection peuvent inclure des instructions spares ou des fiches d'avertissement qui doivent tre utilises en con-
jonction avec ce manuel.
Non appropri aux applications mobiles.
Consignes de Scurit Importantes
Montage
Connexion
Caractristiques
Fonctionnement
Entreposage, Entretien, Garantie et Assurance
Spcifications
English/Espaol/lyccknn
52
53
55
60
71
74
75
1/26/76
Connexion en Option 67
Alimentation en Marche/Arrte 68
Opration Bypass Manuelle 70
52
Consignes de Scurit Importantes
CONSERVEZ CES INSTRUCTIONS. Ce manuel contient des instructions importantes et avertissements qui doivent tre suivis durant l'installation
et la maintenance de tous les Systmes d'alimentation continue sans coupure Montage dans baie/Tour Tripp Lite SmartOnline et leurs batteries.
Avertissements pour Emplacement de Systme d'alimentation continue sans coupure
Installer votre Systme d'alimentation continue sans coupure l'intrieur, l'abri d'humidit ou de chaleur excessive, lumire directe du soleil,
poussire et contaminateurs conducteurs.
Installer votre Systme d'alimentation continue sans coupure dans un zone structurellement saine. Votre Systme d'alimentation
continue sans coupure est trs lourd ; prendre toutes prcautions pour dplacer et lever l'unit.
Utiliser votre Systme d'alimentation continue sans coupure seulement des tempratures l'intrieur entre 32 F et 104 F (entre 0 C et 40 C).
Pour obtenir les meilleures performances, garder les tempratures l'intrieur entre 62 F et 84 F (entre 17 C et 29 C).
Laisser un espace suffisant autour de tous les cts de votre Systme d'alimentation continue sans coupure pour une ventilation approprie.
Ne pas installer le Systme d'alimentation continue sans coupure prs de moyens de stockage magntiques, pour viter tout risque de corruption de
donnes.
Ne pas monter lunit avec son panneau avant ou arrire lenvers (quelque soit langle). Monter de cette faon va entraver srieusement le
refroidissement interne de lunit, endommageant le produit non couvert sous garantie.
Avertissements pour Connexion de Systme d'alimentation continue sans coupure
L'alimentation lectrique pour cette unit doit tre monophase conformment la plaque d'identification de l'quipement. Elle doit aussi tre mise
terre correctement.
Avertissements pour Connexion de l'Equipement
Il est dconseill dutiliser cet quipement dans des applications mdicales o une panne de cet quipement pourrait normalement provoquer la
panne de lquipement de survie ou altrer notablement sa scurit ou son efficacit. Ne pas utiliser cet quipement en prsence dun mlange
anesthtique inflammable avec de lair, de loxygne ou de loxyde nitreux.
Branchez la borne de mise la terre de votre module d'alimentation UPS et/ou module de transformateur une lectrode de mise la terre.
Le Systme d'alimentation continue sans coupure est connect une source d'nergie CC (batterie). Les bornes de sortie peuvent tre actives quand
le Systme d'alimentation continue sans coupure n'est pas connect une alimentation CA.
Avertissements pour Maintenance
Votre module d'alimentation UPS, module de transformateur et module(s) de piles ne requirent aucun entretien routinier. Ne les ouvrez en aucun
cas. Ils ne contiennent aucune pice ncessitant un entretien de la part de l'utilisateur.
Avertissements pour Batterie
Ne pas utiliser votre Systme d'alimentation continue sans coupure sans le connecter un module de batterie externe.
Ne branchez, au connecteur de piles externe de votre module d'alimentation UPS, que les modules piles Tripp Lite (de type et de tension adquats).
Parce que les batteries prsentent un risque de choc lectrique et de courant de court-circuit lev, prenez les prcautions ncessaires. Ne pas jeter
les batteries au feu. Ne pas ouvrir les batteries. Ne pas tablir de court-circuit ou de pont entre les bornes de la batterie avec un quelqconque objet.
Dbrancher et teindre l'UPS avant de remplacer la batterie. Le remplacement de la batterie doit tre confi du personnel de service qualifi.
Utiliser des outils ayant des poignes isoles et remplacer les batteries existantes par des batteries neuves du mme numro et du mme type
(batterie sans entretien). Les batteries UPS sont recyclables. Consultez les codes locaux concernant les exigences d'limination des dchets, ou au
E.-U.seulement, consultez ces sources pour des renseignements concernant le recyclage: 1-800-SAV-LEAD (1-800-728-5323); 1-800-8-BATTERY
(1-800-822-8837); www.rbrc.com. Tripp Lite offre une gamme complte decartouches de batterie de remplacement de systme UPS (R.B.C.).
Rendez visite Tripp Lite sur le Web www.tripplite.com/support/battery/index.cfm pour trouver la batterie de remplacement spcifique votre UPS.
Les fusibles doivent tre remplacs seulement par le personnel en usine agr. Les fusibles brls doivent tre remplacs seulement par le mme
nombre et type de fusibles.
L'entretien et les rparations doivent tre effectus seulement par le personnel qualifi. Avant d'effectuer toute opration d'entretien sur un module
cbl, celui-ci doit avoir t teint ou driv manuellement vers le transformateur. Avant d'effectuer toute opration d'entretien sur un module
d'alimentation se connectant directement une prise murale, celui-ci doit avoir t teint et dbranch. Noter que des tensions potentiellement
mortelles existent dans cette unit quand l'alimentation de la batterie est connecte.
Ne branchez ou ne dbranchez pas le(s) module(s) de piles lorsque le UPS fonctionne partir de l'alimentation piles ou lorsque le module de
transformateur n'est pas en mode de drivation (si votre systme UPS comprend un module de transformateur avec un interrupteur de drivation).
Durant le remplacement du pack de batteries " chaud", votre Systme d'alimentation continue sans coupure ne pourra pas assurer une alimentation
de secours de la batterie en cas de coupure de courant.
53
Montage (Baie)
1
Montage 4 supports
1
2
3
A
B
C
F
E
G
4
H
Connecter les deux segments de chaque tagre
A en utilisant les vis et crous oreilles
B.
Laisser les vis lgrement desserres de manire ce que les tagres puissent tre ajustes
la procdure suivante.
Ajuster chaque tagre pour fixer votre baie, puis les monter dans l'espace disponible le plus bas
de votre baie avec les vis, crous et rondelles fournis
C. Noter que les arceaux de support
doivent tre dirigs vers l'intrieur. Serrer les vis qui relient les segments d'tagre
D.
Fixer les oreilles de montage
E aux trous de montage avant de votre quipement
F en
utilisant les vis fournies
G. Les oreilles doivent tre diriges vers l'avant.
Avec l'aide d'un assistant, lever votre quipement et le faire coulisser sur les tagres de
montage. Fixer votre quipement sur la baie en faisant passer les vis, crous et rondelles
(fournis par l'utilisateur)
H par ses oreilles de montage et dans les rails de la baie.
Pour monter votre quipement dans une baie 2 supports, vous devez acqurir un Kit d'Installation
de Montage de Baie 2 Supports Tripp Lite (modle : 2POSTRMKIT, vendu sparment) pour
chaque module install. Voir le manuel de l'utilisateur de Kit d'Installation pour toutes instruc-
tions de montage.
4
Monter votre quipement dans une baie 4 supports ou 2 supports ou une enceinte de baie. L'utilisateur doit dterminer l'aptitude du matriel et les pro-
cdures avant le montage. Si le matriel et les procdures ne sont pas appropris pour votre application, contacter le fabricant de votre baie ou de votre
enceinte de baie. Les procdures dcrites dans ce manuel sont pour les types de baie et d'enceinte de baie ordinaires et peuvent ne pas tre appropries pour
toutes les applications.
AVERTISSEMENT!
Tous les modules de systme UPS sont extrmement lourds ! Faites attention lorsque vous les soulevez ou les installez!
L'utilisateur doit stabiliser adquatement le module lorsqu'il le soulve ou l'installe.
2
3
Montage 2 supports (Telecom)
B
D
54
Montage (Tour)
AVERTISSEMENT!
Tous les modules de systme UPS sont extrmement lourds ! Faites
attention lorsque vous les soulevez ou les installez! L'utilisateur doit
stabiliser adquatement le module lorsqu'il le soulve ou l'installe.
Faire tourner le Panneau de Commande du module d'alimentation pour le voir plus facilement
quand le Systme d'alimentation continue sans coupure est mont en tour. Insrer un petit tourn-
evis, ou un autre outil, dans les slots de chaque ct du Panneau de Commande. Dgager le pan-
neau ; le faire tourner ; et remettre en place le panneau.
Tous les modules doivent tre installs en position debout lorsque utiliss avec une base ajustable optionnelle, vendue sparment par Tripp Lite (modle
no. 2-9USTAND). Lorsque vous installez un module sur une base ajustable, assurez-vous que le panneau de contrle du module d'alimentation se trouve
sur le cot suprieur. Si vous installez aussi un module de transformateur, placez-le entre le module d'alimentation et son module piles.
55
Caractristiques
Trois modules de Systme d'alimentation continue sans coupure spars sont disponibles chez Tripp Lite (module d'alimentation, module de transformateur
et module piles) utiliss dans une varit de combinaisons. Familiarisez-vous avec l'emplacement et la fonction des caractristiques de chaque module
avant d'installer et d'utiliser votre Systme d'alimentation continue sans coupure. Le module d'alimentation est le seul module qui inclut les caractristiques
du panneau avant.
Commandes de Panneau Avant de Module d'Alimentation
1. AFFICHAGE LCD : Cet affichage de matrice points (16x2 caractres) clairage arrire indique une large chelle de conditions de fonctionnement
du Systme d'alimentation continue sans coupure et de donnes de diagnostic. Il affiche aussi les rglages du Systme d'alimentation continue sans
coupure et les options quand le Systme d'alimentation continue sans coupure est en mode configuration.
2. BOUTON ON/SILENCE: Appuyer sur ce bouton et le maintenir enfonc jusqu' ce que vous entendiez un bip pour mettre en fonction l'inverseur du
Systme d'alimentation continue sans coupure. Si l'alarme sonore de la batterie du Systme d'alimentation continue sans coupure se dclenche, appuyez
sur ce bouton pour l'arrter.
3. BOUTON DEFILEMENT BAS/QUITTER CONFIGURATION: Ce bouton vous permet de visualiser rapidement diffrentes options et lectures
d'alimentation sur l'affichage LCD. Quand il est press momentanment, l'cran LCD affiche une lecture d'alimentation diffrente (voir
Fonctionnement). Quand il est press en mme temps que le bouton DEFILEMENT HAUT, le Systme d'alimentation continue sans coupure passe
en mode configuration, o ce bouton est utilis pour faire dfiler les options de configuration et pour quitter le mode configuration.
4. BOUTON DEFILEMENT HAUT/SELECTION : Ce bouton vous permet de visualiser rapidement diffrentes options et lectures d'alimentation. sur
l'affichage LCD. Quand il est press momentanment, l'cran LCD affiche une lecture d'alimentation diffrente (voir Fonctionnement). Quand il est
press en mme temps que le bouton DEFILEMENT BAS, le Systme d'alimentation continue sans coupure passe en mode configuration, o ce bouton
est utilis pour slectionner les options de configuration.
5. BOUTON OFF : Appuyer sur ce bouton jusqu' ce que vous entendiez un bip pour mettre hors fonction l'inverseur du Systme d'alimentation continue
sans coupure.
6. LED O/P (SORTIE) : Ce voyant vert s'allume pour indiquer que votre Systme d'alimentation continue sans coupure dlivre une alimentation CA
l'quipement connect.
7. LED CC/CA (INVERSEUR) : Ce voyant vert s'allume pour indiquer que l'inverseur CC/CA du Systme d'alimentation continue sans coupure est activ.
8. LED BYPASS : Ce voyant vert s'allume quand le Systme d'alimentation continue sans coupure dlivre une alimentation secteur filtre sans mettre
en fonction son convertisseur ou inverseur. Si cette LED est allume, l'quipement connect ne recevra pas l'alimentation de la batterie en cas de
coupure de courant.
9. LED CA/CC (Convertisseur) : Ce voyant vert s'allume pour indiquer que le convertisseur CA/CC du Systme d'alimentation continue sans coupure
est en train de charger le(s) pack(s) de batteries connect(s).
10. LED BATTERIE : Ce voyant rouge s'allume quand le Systme d'alimentation continue sans coupure est en train de dcharger la batterie pour dlivrer
une alimentation CA l'quipement connect. Une alarme sonore se dclenchera, qui peut tre arrte en appuyant sur le bouton ON/SILENCE. Cette
LED restera allume aprs l'arrt de l'alarme.
11. LED I/P (ENTREE) : Ce voyant vert s'allume pour indiquer qu'une alimentation d'entre CA est prsente.
12. SLOTS ACCES : Pour tourner les commandes, insrer un tournevis tte plate dans ces slots et dgager le panneau avec prcautions. En veillant
ne pas tordre ou tirer d'un coup sec de manire excessive les cbles connectant les commandes au reste du Systme d'alimentation continue sans
coupure, tourner les commandes vers l'orientation voulue et les rinsrer.
1
2 3 4 5
6 8 7 9 10 11
12 12
56
Caractristiques (panneau arrire) voir la page 59 pour descriptions de caractristiques
Module d'alimentation 5kVA
Module de transformateur 5kVA
Module piles* 5kVA
* Le module d'alimentation 5kVA est livr avec un module piles
non extensible, cependant, le module d'alimentation est totalement
compatible avec les modules piles Tripp Lite qui eux sont exten-
sibles (modle Tripp Lite no. BP240V10RT-3U, vendu sparment)
si vous dsirez prolonger votre autonomie.
11
6
7
8 9 10
3
12 12
13 13 14
25
25
24 25 24
26
19
28
57
Caractristiques (Panneau Arrire) voir la page 59 pour descriptions de caractristiques
Module Alimentation 6kVA
Module Transformateur 6kVA
Module Batterie pour Modle 6kVA*
5 4
6
7
8 9 10
16
17
15
12
20
21
3
1 2
11
13
18 19
* Module piles extensible (modle Tripp Lite no.
BP240V10RT-3U) montr. Selon le modle command, le
module d'alimentation 6kVA peut avoir t livr avec un
module piles extensible (comme celui montr ci-dessus) ou
avec un module non extensible. Tous les modules
d'alimentation 6kVA, cependant, sont totalement compatibles
avec les modules piles BP240V10RT-3U (vendus spar-
ment) si vous dsirez prolonger votre autonomie.
58
Caractristiques (Panneau Arrire) voir la page 59 pour descriptions de caractristiques
Module Alimentation 10kVA
4 5 6
7
8 9
10
3
Module Batterie pour Modle 10kVA*
20
21
Module Transformateur 10kVA
16 14 11 12
17
1 2
15
18 19
* Module piles extensible (modle Tripp Lite no.
BP240V10RT-3U) montr. Selon le modle command, le
module d'alimentation 10kVA peut avoir t livr avec un
module piles extensible (comme celui montr ci-dessus)
ou avec un module non extensible. Tous les modules
d'alimentation 10kVA, cependant, sont totalement compati-
bles avec les modules piles BP240V10RT-3U (vendus
sparment) si vous dsirez prolonger votre autonomie.
59
Caractristiques (Panneau Arrire) suite
Description des Caractristiques de Module d'Alimentation
1. Bloc de Bornes de Sortie (Modles 6kVA et 10kVA seulement) : Utiliser ces bornes pour connecter votre module d'alimentation votre quipement
ou au module du transformateur. Dvisser et enlever le couvercle sur le bloc pour accs.
2. Blocs de Bornes d'Entre (Modles 6kVA et 10kVA seulement) : Utiliser ces bornes pour connecter votre module d'alimentation l'alimentation de
service ou au module du transformateur. Dvisser et enlever le couvercle sur le bloc pour accs.
3. Connecteur de Batterie Externe : L'utiliser pour connecter un ou plusieurs modules de batterie Tripp Lite au module d'alimentation. Enlever le
couvercle pour accs. Le module d'alimentation ne dmarrera pas sans une connexion un module de batterie charge. Se rfrer au manuel de
l'utilisateur de module de batterie pour les instructions de connexion et les consignes de scurit.
4. Disjoncteur d'Entre CA (Modles 6kVA et 10kVA seulement) : Un disjoncteur de circuit bipolaire contrle l'alimentation d'entre au module
d'alimentation.
5. Disjoncteur de Sortie CA (Modles 6kVA et 10kVA seulement) : Un disjoncteur de circuit bipolaire contrle l'alimentation de sortie du module
d'alimentation.
6. Ventilateur d'Echappement : Il refroidit et ventile l'intrieur du module d'alimentation.
7. Slot Accessoires : Enlever le petit panneau couvercle pour installer les accessoires en option pour commander et contrler distance votre Systme
d'alimentation continue sans coupure. Visiter Tripp Lite sur le Web (www.tripplite.com) pour informations sur SNMP, gestion de rseau et produits de
connectivit qui peuvent tre installs dans ce slot.
8. Port EPO (Alimentation de Secours Off) : Le module d'alimentation comporte un port EPO qui peut tre utilis pour connecter le module
d'alimentation un interrupteur de fermeture de contact pour couper l'alimentation de secours. Voir la section "Connexion en Option" pour tous dtails.
9. Port de Communication RS-232 : Ce port srie femelle DB9 peut tre utilis pour connecter votre Systme d'alimentation continue sans coupure
une station de travail ou un serveur. Il utilise le protocole RS-232 pour communiquer avec un ordinateur connect. Il est utilis avec le logiciel Tripp
Lite et le cble srie inclus pour contrler et grer distance le Systme d'alimentation continue sans coupure sur un rseau et pour sauvegarder
automatiquement les fichiers ouverts et fermer l'quipement durant une coupure de courant. Voir "Connexion en Option" pour tous dtails.
10. Port Interface de Contact Sec : Ce port DB9 femelle envoie des signaux de fermeture de contact pour indiquer la condition de dfaillance de ligne
et de batterie faible. Voir Connexion en Option pour tous dtails.
11. Disjoncteur de sortie 1 c.a. (modles 5kVA seulement) : un disjoncteur de circuit bipolaire contrle l'alimentation de sortie partir des prises c.a.
des modules d'alimentation 5kVA tiquetes "Output 1" (sortie 1).
12. Prises de sortie 1 c.a. (modles 5kVA seulement) : accepte les connexions directement enfichables des prises d'quipement NEMA L6-20P.
13. Prises de sortie 2 c.a. (modles 5kVA seulement) : accepte les connexions directement enfichables des prises d'quipement NEMA L6-30P. L'une ou
l'autre des prises acceptent aussi la connexion directement enfichable du cble du connecteur du transformateur (si utilis).
14. Cordon d'alimentation c.a. (modles 5kVA seulement) : se branche directement dans une prise murale procurant une alimentation de service de
200/208/220/230 ou 240V c.a.
Description des caractristiques du module de transformateur
15. Bloc de Bornes d'Entre de Service (Modles 6kVA et 10kVA seulement) : Utiliser ces bornes pour connecter votre module de transformateur
l'alimentation de service. Dvisser et enlever le couvercle sur le bloc pour accs.
16. Bloc de Bornes de Sortie d'Equipement (Modles 6kVA et 10kVA seulement) : Utiliser ces bornes pour connecter votre quipement au module du
transformateur. dvisser et enlever le couvercle sur le bloc pour accs.
17. Cble pour Connexion de Module d'Alimentation (modles 6kVA seulement) : Connecte le module du transformateur l'entre/sortie du module
d'alimentation aprs l'enlvement des blocs de bornes du module d'alimentation. Voir la section "Connexion" pour tous dtails.
18. Bloc de Bornes Cbles pour Connexion de Module d'Alimentation (modles 10kVA seulement) : Utiliser ces bornes pour connecter le module
du transformateur aux blocs de bornes d'entre et sortie du module d'alimentation. Voir la section "Connexion" pour tous dtails.
19. Disjoncteur de Remise l'Etat Initial pour Temprature Excessive : Ce disjoncteur de circuit se dclenche si la temprature de l'unit devient trop
leve.
20. CA Disjoncteur de Systme d'alimentation continue sans coupure (Modles 6kVA et 10kVA seulement) : Un disjoncteur de circuit bipolaire
contrle la sortie d'alimentation du module du transformateur au Systme d'alimentation continue sans coupure.
21. Disjoncteur de Sortie (Modles 6kVA et 10kVA seulement) : Un disjoncteur de circuit tripolaire contrle la sortie d'alimentation du module du
transformateur l'quipement connect.
22. Commutateur Bypass Manuel (Modles 6kVA et 10kVA seulement) : Ce cadran rouge et jaune est utilis pour viter le module d'alimentation tout
en supportant encore l'quipement connect lors d'opration de maintenance du module d'alimentation. Quand ce commutateur est sur BYPASS,
l'quipement connect recevra l'alimentation secteur CA filtre depuis le module du transformateur, mais l'quipement ne recevra pas d'alimentation de
batterie en cas de coupure de courant. Voir la section "Opration Bypass Manuelle" pour la procdure complte de bypass.
AVERTISSEMENT ! Pour le personnel d'entretien qualifi seulement. La non-observation de toute la procdure de bypass ne
diminuera pas de manire adquate l'alimentation du module d'alimentation du Systme d'alimentation continue sans coupure,
entranant des risques continuels de mort ou de blessures du fait de contact potentiel avec une haute tension.
23. Commutateur de Slection de Tension d'Entre (Modles 6kVA et 10kVA seulement) : Utiliser ce commutateur pour rgler la tension d'entre du
module du transformateur (soit 200V AC, 208V AC ou 240V AC). Voir la section Connexion pour tous dtails.
60
Description des Caractristiques de Module de Batterie
27. Connecteur d'Entre (Slectionnez les modules piles seulement) : Utiliser ce connecteur pour relier en chane boucle des modules de batterie
supplmentaires sur le premier. Enlever le panneau couvercle pour accs. se rfrer au manuel de l'utilisateur de module de batterie pour les instructions
de connexion et les consignes de scurit.
28. Cble de Sortie : Utiliser ce cble pour connecter le module de la batterie au module d'alimentation sur un autre module de batterie. Le module
d'alimentation ne dmarrera pas sans une connexion un module de batterie charge. Se rfrer au manuel de l'utilisateur de module de batterie pour
les instructions de connexion et les consignes de scurit.
Caractristiques (Panneau Arrire) suite
24. Prises de sortie c.a. (modles 5kVA seulement) : accepte les connexions directement enfichables des prises d'quipement NEMA 5-15P ou NEMA
5-20P.
25. Disjoncteur de sortie c.a. (modles 5kVA seulement) : des disjoncteurs bouton poussoir contrlent l'alimentation de sortie vers les prises de sortie
c.a du module du transformateur adjacent.
26. Cble de connexion du module d'alimentation (modles 5kVA seulement) : se branche directement dans l'une ou l'autre des prises de sortie 2 c.a
du module d'alimentation 5kVA. NOTE: ce cble doit uniquement tre branch dans un module d'alimentation 5kVA.
Connexion

Le cblage doit tre effectu par un lectricien qualifi.
Le module d'alimentation du Systme d'alimentation continue sans coupure peut tre install indpendamment ou connect un module de transformateur
d'isolation. Les deux applications ncessitent que le module d'alimentation soit connect un module de batterie.
Lors d'excution de connexions de cblage, toujours observer les rglementations sur connexions de cbles appropries pour votre zone [par ex. National Electrical
Code (NEC) aux Etats-Unis]. Veiller installer un interrupteur de dconnexion facile d'accs dans votre cblage d'installation afin que vous puissiez couper l'entre
CA du Systme d'alimentation continue sans coupure en cas d'incendie et autres cas d'urgence. S'assurer que les cbles sont quips de manchons de cbles et sont
fixs correctement avec des brides de fixation de connecteurs. Serrer les connexions avec un couple non infrieur 24-28 pouce-livres (2.7-3.2 NM).
S'assurer que votre quipement est correctement mis la terre.
L'utilisation de cbles de taille non approprie peut endommager votre quipement et entraner des risques d'incendie. Choisir le cblage et les circuits de protection
appropris pour effectuer les connexions de cblage (Les conducteurs de mise la terre doivent avoir la mme taille et le mme type que ceux des conducteurs
d'alimentation utiliss) :
COURANT ENTRE NOMINAL COURANT SORTIE NOMINAL COURANT SORTIE NOMINAL CIRCUIT PROTECTION
200 - 240 (1, 2-Cble + PE) 200 - 240V (1, 2-Cble + PE) 120V (1, 2-Cble + PE) SORTIE
Modles 6kVA 30A 8 AWG (10mm
2
) 30A 8 AWG (10mm
2
) 2 30A 8 AWG (10mm
2
) 30A
Modles 10kVA 50A 6 AWG (16mm
2
) 50A 6 AWG (16mm
2
) 2 50A 6 AWG (16mm
2
) 63A
Prcautions pour Cblage (Modles 6kVA et 10kVA seulement)
Trois modules de Systme d'alimentation continue sans coupure spars sont disponibles chez Tripp Lite (un module d'alimentation et un module de batte-
rie, qui sont requis pour toutes les applications, et un module de transformateur) utiliss dans une varit de combinaisons. Suivre la procdure de connexion
ci-dessous qui correspond la combinaison de modules que vous prvoyez d'installer.
Connexion des Modules les Uns aux Autres et l'Alimentation de Service et l'Equipement
Combinaison de connexion no. 1
Module d'alimentation (5kVA) + module piles
Branchez votre quipement dans le module
d'alimentation.
Branchez les cordons d'alimentation
A de votre quipement directement dans les prises
de sortie c.a.
B de votre module.
Branchez le module d'alimentation dans une prise
murale.
Branchez le cordon d'alimentation
C du module directement dans une prise murale
D
qui fournit une alimentation de service de 200/208/220/230 ou 240V c.a.
Branchez le module piles au module d'alimentation.
Consultez le manuel de l'utilisateur qui vous est fourni avec votre module piles.
Insrez au complet le connecteur de l'extrmit du cble
E du module piles dans le
connecteur du panneau arrire du module d'alimentation
F . Des petites tincelles
peuvent se produire ; c'est normal. REMARQUE : le module d'alimentation ne con-
tient aucune pile interne et ne dmarrera pas jusqu' ce que le module piles soit
branch. Les modules piles sont entirement chargs avant l'expdition. Toutefois,
avant de s'attendre des capacits de sauvegarde de secours compltes (en particulier
si le module piles a t entrepos pour une longue dure), une fois le systme UPS
branch une source d'alimentation de service, laissez le module piles se recharger
pendant 12 heures. Une fois le systme UPS en utilisation, les piles se rechargeront et
maintiendront automatiquement le niveau de charge. * Le module d'alimentation 5kVA
est livr avec un module piles non extensible, cependant, le module d'alimentation
est totalement compatible avec les modules piles Tripp Lite qui eux sont extensibles
(modle Tripp Lite no. BP240V10RT-3U, vendu sparment) si vous dsirez prolonger
votre autonomie.
61
Connexion suite
1
2
2
3
3
A
B
C
E
F
1
D
Combinaison de connexion no. 2
Module d'alimentation (5kVA) + module de transformateur (5kVA) + module piles
Branchez le module de transformateur dans le module
d'alimentation.
Branchez le cble du connecteur
A du module de transformateur directement dans
l'une ou l'autre des 2 prises
B de sortie c.a. du module d'alimentation 5kVA. NOTE:
ce cble doit uniquement tre branch dans un module d'alimentation 5kVA.
Branchez votre quipement dans le module
d'alimentation et le module de transformateur.
Branchez les cordons d'alimentation
D de votre quipement c.a. 200/208/220/230/240V
directement dans les prises de sortie c.a.
D du module d'alimentation. Branchez les
cordons d'alimentation
E de votre quipement 120 V c.a. directement dans les prises
de sortie c.a.
F de votre module de transformateur.
Branchez le module d'alimentation dans une prise
murale.
Branchez le cordon d'alimentation c.a.
C du module directement dans une prise
murale
H qui fournit une alimentation de service de 200/208/220/230 ou 240V c.a.
Branchez le module piles au module d'alimentation.
Consultez le manuel de l'utilisateur qui vous est fourni avec votre module piles.
Insrez au complet le connecteur de l'extrmit du cble
I du module piles dans le
connecteur du panneau arrire du module d'alimentation
J . Des petites tincelles
peuvent se produire ; c'est normal. REMARQUE : le module d'alimentation ne con-
tient aucune pile interne et ne dmarrera pas jusqu' ce que le module piles soit
branch. Les modules piles sont entirement chargs avant l'expdition. Toutefois,
avant de s'attendre des capacits de sauvegarde de secours compltes (en particulier
si le module piles a t entrepos pour une longue dure), une fois le systme UPS
branch une source d'alimentation de service, laissez le module piles se recharger
pendant 12 heures. Une fois le systme UPS en utilisation, les piles se rechargeront et
maintiendront automatiquement le niveau de charge. * Le module d'alimentation 5kVA
est livr avec un module piles non extensible, cependant, le module d'alimentation
est totalement compatible avec les modules piles Tripp Lite qui eux sont extensibles
(modle Tripp Lite no. BP240V10RT-3U, vendu sparment) si vous dsirez prolonger
votre autonomie.
62
1
2
2
3
3
A
B
E
H
G
1
4
4
F
D
C
I
J
Connexion suite
Combinaison de Connexion N3 : Module d'Alimentation
(soit 6kVA ou 10kVA) + Module(s) de Batterie
Cbler le module d'alimentation votre quipement
En utilisant un tournevis, enlever la partie suprieure de la bote
A couvrant les bornes
d'entre et de sortie du module d'alimentation. Passer un cble fourni par l'utilisateur
dans la partie d'jection gauche
B de la bote de bornes et le connecter aux bornes de
sortie du module d'alimentation. Connecter l'autre extrmit du cble votre
quipement.
Cbler le module d'alimentation une source
d'alimentation de service.
Passer un cble fourni par l'utilisateur dans la partie d'jection droite
C de la bote et
le connecter aux bornes d'entre du module d'alimentation. Remettre en place la partie
suprieure de la bote de bornes. Connecter l'autre extrmit du cble une source
d'alimentation de service.
Connecter le module de batterie au module d'alimentation.
Consulter le manuel de l'utilisateur accompagnant votre module de batterie. Insrer
entirement le connecteur sur l'extrmit du cble
D du module de batterie dans le
connecteur sur le panneau arrire du module d'alimentation
E . Des petites tincelles
peuvent se produire ; ceci est normal. REMARQUE : le module d'alimentation ne
contient pas de batteries internes et ne dmarrera pas avant la connexion d'un module
de batterie. Les modules de batterie sont compltement chargs avant expdition.
Cependant, avant de prvoir une pleine capacit de secours (en particulier si le module
de batterie a t emmagasin pendant une priode de temps prolonge) aprs la
connexion du Systme d'alimentation continue sans coupure une source d'alimentation
de service, laisser le module de batterie se recharger pendant 12 heures. Ds que le
Systme d'alimentation continue sans coupure est en fonction, il chargera les batteries
et maintiendra automatiquement le niveau de charge. Si ncessaire, connecter des
modules de batterie supplmentaires en chane boucle chaque cble de module
insr dans le connecteur
F du module prcdent.
connection base step 1
connection base step 1
connection base step 1
63
1
2
2
3
3
A
B
C
D
E
F
1
Module d'Alimentation 6kVA Reprsent
Connexion suite
Combinaison de Connexion N4 : Module d'Alimentation (6kVA)
+ Module de Transformateur (6kVA) + Module(s) de Batterie
Connecter le module d'alimentation au module
du transformateur.
En utilisant un tournevis, enlever la bote entire
A couvrant les bornes d'entre et de
sortie du module d'alimentation. Enlever les vis sur chaque ct des bornes. Saisir les
bornes
B et les faire coulisser vers l'extrieur jusqu' ce que vous puissiez voir la patte
de libration du connecteur de cble
C. Presser vers le bas la patte et tirer sur les cbles
pour les librer du connecteur interne
D. Enlever les bornes. Insrer le cble de con-
necteur du module du transformateur
E dans les connecteurs internes dans la bote de
bornes du module d'alimentation jusqu' ce que la patte de libration s'enclenche sur sa
position. Remettre en place les vis autour du plateau. Bien qu'elles ne soient pas nces-
saires, conserver les bornes du module d'alimentation et le couvercle de la bote de
bornes au cas o vous prvoyez d'utiliser le module d'alimentation sans le module du
transformateur ultrieurement.
Cbler le module du transformateur votre quipement.
En utilisant un tournevis, enlever la partie suprieure de la bote
F couvrant les bornes
d'entre et de sortie du module du transformateur. Passer un cble fourni par l'utilisateur
dans la partie d'jection gauche
G de la bote de bornes et le connecter aux bornes de
sortie du module du transformateur. Voir le Diagramme de Tension de Sortie CA
H
pour dterminer quelles connexions de bornes assurera une tension approprie pour
votre application. Connecter l'autre extrmit du cble votre quipement.
Cbler le module du transformateur une source
d'alimentation de service
Passer un cble fourni par l'utilisateur dans la partie d'jection droite de la bote
I
et
le connecter aux bornes d'entre du module du transformateur. Remettre en place la
partie suprieure de la bote couvrant les bornes du module du transformateur.
Connecter l'autre extrmit du cble une source d'alimentation de service.
connection base step 1
NORMAL
BY PASS
NORMAL
BY PASS
NORMAL
BY PASS
64
1
1
3
Connexion suite
2
2
120V
240V
120V
208V
DIAGRAMME DE TENSION DE SORTIE CA
G
3
1
A
B C
E
G
I
F
Combinaison de Connexion N4 suite la page suivante
H
D
Slectionner la tension d'entre du module du
transformateur.
En utilisant un tournevis, enlever le panneau couvrant le Commutateur de Slection de
Tension d'Entre
J
du module du transformateur. Rgler le commutateur sur la position
correspondant la tension d'entre de votre installation. Ensuite, utiliser les commuta-
teurs du panneau avant du module d'alimentation pour configurer la tension d'entre sur
l'Affichage LCD (voir Configurer l'entre et la sortie de votre Systme d'alimentation
continue sans coupure dans la section Alimentation ON/OFF).
REMARQUE IMPORTANTE : si la tension d'entre de votre installation est de 200V
AC, rgler le commutateur du module du transformateur sur 240V AC, mais configurer
le module d'alimentation sur 200V AC. Si la tension d'entre de votre installation est de
208V AC ou 240V AC, les rglages du module du transformateur et du module
d'alimentation doivent correspondre. Les rglages par dfaut en usine pour les deux
modules est de 208V. Voir le tableau ci-dessous.
Module du Transformateur Module d'Alimentation
Rglage de Tension Rglage de Tension d'Entre
Tension d'Entre d'Entre(Commutateur (Commutateurs Panneau
de votre Installation Panneau Arrire) Avant/Affichage LCD)
240V AC 240V AC 240V AC
208V AC 208V AC 208V AC
200V AC 240V AC 200V AC
Connecter le module de batterie au module d'alimentation.
Consulter le manuel de l'utilisateur accompagnant votre module de batterie. Insrer
entirement le connecteur sur l'extrmit du cble
K du module de batterie dans le
connecteur sur le panneau arrire du module d'alimentation
L . Des petites tincelles
peuvent se produire ; ceci est normal. REMARQUE : le module d'alimentation ne con-
tient pas de batteries internes et ne dmarrera pas avant la connexion d'un module de
batterie. Les modules de batterie sont compltement chargs avant expdition.
Cependant, avant de prvoir une pleine capacit de secours (en particulier si le module
de batterie a t emmagasin pendant une priode de temps prolonge) aprs la con-
nexion du Systme d'alimentation continue sans coupure une source d'alimentation de
service, laisser le module de batterie se recharger pendant 12 heures. Ds que le
Systme d'alimentation continue sans coupure est en fonction, il chargera les batteries
et maintiendra automatiquement le niveau de charge. Si ncessaire, connecter des mod-
ules de batterie supplmentaires en chane boucle chaque cble de module insr
dans le connecteur
M du module prcdent.
Combinaison de Connexion N5 : Module
d'Alimentation (10kVA) + Module du Transformateur
(10kVA) + Module(s) de Batterie
Cbler le module d'alimentation au module du
transformateur.
En utilisant un tournevis, enlever la partie suprieure de la bote
A couvrant les bornes
d'entre et de sortie du module d'alimentation. Enlever la partie suprieure de la bote
B
couvrant les bornes du module du transformateur. Avec un cble fourni, connecter
les bornes d'entre et de sortie du module d'alimentation aux bornes correspondantes
sur Cbler le Bloc de Bornes pour Connexion du Module d'Alimentation du module
du transformateur dans la partie d'jection
C de la bote.
NORMAL
BY
PASS
240V AC
208V AC
NORMAL
BY PASS
NORMAL
BY PASS
65
Connexion suite
4
5
5
1
1
4
J
M
L
A
B
C
K
Combinaison de Connexion N5 suite la page suivante
Cbler le module du transformateur votre quipement.
Passer un cble fourni par l'utilisateur dans la partie d'jection gauche de la bote
D et
le connecter aux bornes de sortie du module du transformateur. Voir le Diagramme de
Tension de Sortie CA
E pour dterminer quelles connexions de bornes dlivreront la
tension approprie pour votre application. Connecter l'autre extrmit du cble votre
quipement.
Cbler le module du transformateur une source
d'alimentation de service
Passer un cble fourni par l'utilisateur dans la partie d'jection du milieu de la bote
F
et le connecter aux bornes d'entre du module du transformateur. Connecter l'autre
extrmit du cble une source d'alimentation de service. Remettre en place la partie
suprieure des botes couvrant les bornes du module d'alimentation et du module du
transformateur.
Slectionner la tension d'entre du module
du transformateur.
En utilisant un tournevis, enlever le panneau couvrant le Commutateur de Slection de
Tension d'Entre
G du module du transformateur. Rgler le commutateur sur la posi-
tion correspondant la tension d'entre de votre installation. Ensuite, utiliser les com-
mutateurs du panneau avant du module d'alimentation pour configurer la tension
d'entre sur l'Affichage LCD (voir Configurer l'entre et la sortie de votre Systme
d'alimentation continue sans coupure dans la section Alimentation ON/OFF la
page 58).
REMARQUE IMPORTANTE : si la tension d'entre de votre installation est de 200V
AC, rgler le commutateur du module du transformateur sur 240V AC, mais configurer
le module d'alimentation sur 200V AC. Si la tension d'entre de votre installation est de
208V AC ou 240V AC, les rglages du module du transformateur et du module
d'alimentation doivent correspondre. Les rglages par dfaut en usine pour les deux
modules est de 208V. Voir le tableau ci-dessous.
Module du Transformateur Module d'Alimentation
Rglage de Tension Rglage de Tension d'Entre
Tension d'Entre d'Entre(Commutateur (Commutateurs Panneau
de votre Installation Panneau Arrire) Avant/Affichage LCD)
240V AC 240V AC 240V AC
208V AC 208V AC 208V AC
200V AC 240V AC 200V AC
Connecter le module de batterie au module d'alimentation.
Consulter le manuel de l'utilisateur accompagnant votre module de batterie. Insrer
entirement le connecteur sur l'extrmit du cble
H du module de batterie dans le
connecteur sur le panneau arrire du module d'alimentation
I . Des petites tincelles
peuvent se produire ; ceci est normal. REMARQUE : le module d'alimentation ne
contient pas de batteries internes et ne dmarrera pas avant la connexion d'un module
de batterie. Les modules de batterie sont compltement chargs avant expdition.
Cependant, si le module de batterie a t emmagasin pendant une priode de temps
prolonge aprs la connexion du Systme d'alimentation continue sans coupure une
source d'alimentation de service, laisser le module de batterie se recharger pendant 12
heures. Si ncessaire, connecter des modules de batterie supplmentaires en chane
boucle chaque cble de module insr dans le connecteur
J
du module prcdent.
NORMAL
BY PASS
NORMAL
BY PASS
NORMAL
BY PASS
NORMAL
BY
PASS
240V AC
208V AC
66
Connexion suite
3
3
4
5
5
F
4
G
H
I
J
2
D
120V
240V
120V
208V
DIAGRAMME DE TENSION DE SORTIE CA
G
E
2
67
Les connexions suivantes sont en option. Votre Systme d'alimentation continue sans coupure fonc-
tionnera correctement sans ces connexions.
Connexion Communication Srie RS-232
Utiliser le cble inclus pour connecter le port du module d'alimentation RS-232 au port de
communication de votre ordinateur. Ceci permettra le contrle et la commande complets de votre
Systme d'alimentation continue sans coupure. Installer sur votre ordinateur le Logiciel d'Alerte
Alimentation Tripp Lite appropri pour le Systme d'exploitation de votre ordinateur.
Connexion Communication Fermeture de Contact
Utiliser un cble DB9 de fermeture de contact fourni par l'utilisateur pour connecter le port
Contact Sec du module d'alimentation au port de communication de votre ordinateur ou autre
quipement. Ceci permettra d'envoyer des signaux de fermeture de contact vers et depuis le
Systme d'alimentation continue sans coupure. Se rfrer au diagramme et au tableau suivants
pour dterminer les signaux ports par ce port. Installer sur votre ordinateur le Logiciel d'Alerte
Alimentation Tripp Lite appropri pour le Systme d'exploitation de votre ordinateur.
Connexion Port EPO
Cette caractristique en option est prvue seulement pour les applications qui ncessitent une connexion
un circuit d'Alimentation d'Urgence Off (EPO) d'une installation. Quand le module d'alimentation
est connect ce circuit, il permet la fermeture d'urgence de la sortie. En utilisant le cble inclus,
connecter le port EPO du module d'alimentation un interrupteur distance fourni par l'utilisateur.
Les fonctions de broches pour le port EPO sont reprsentes dans le diagramme suivant. Remarque
: en cas de court-circuit entre les broches 2 et 3, 2 et 5, 4 et 5, ou 3 et 4, le Systme d'alimentation
continue sans coupure sera dsactiv.
Connexion en Option
0
12 V
>2 sec

5 4 3 2 1 9 8 7 6

NO
COM NC
lm in. > 3.3 mA
SECOURS
SIGNAL FERMETURE A
DISTANCE DEPUIS EXTERNE
SIGNAL D'ORDINATEUR
COM NC
BATTERIE FAIBLE
NO
CAPACITE MAXIMUM DE CONTACT SEC : CA250V/3A . CC30V/3A
DIAGRAMME INTERFACE CONTACT SEC
Systme d'alimentation continue sans
coupure en Fonction
Broche 8,3 Broche 1,3 Broche 6,3
Mode
Normal OUVERT OUVERT *
Secours FERME * *
Batterie faible FERME FERME *
Dfaillance * * FERME
* Inactif : peut tre dans l'une des conditions
TABLEAU INTERFACE CONTACT SEC
FONCTION DE BROCHE EPO
1
2
3
4
5
6
X
12V
X
1K

68
1. Pour mettre lUPS en mode DRIVATION : Appuyer et maintenir enfonc le bouton ARRT
F jusqu ce que lUPS mette un bip.
Mettre lUPS en mode CONFIGURATION en maintenant les boutons DFILEMENT
A et SLECTION
B enfoncs simultanment.
Faire dfiler les options de configuration ( laide de
A ou
B) et slectionner le paramtre appropri pour chacune des options suivantes laide
du bouton SLECTION
B.
a. Tension de sortie : Choisir parmi 200, 208, 220, 230 ou 240 V c.a.
b. Frquence de sortie : Votre UPS slectionnera automatiquement 50 ou 60 Hz pour correspondre lentre.
c. Mode conomie : Votre UPS vous offre un fonctionnement en ligne avec un temps de transfert de zro. Il fonctionne aussi en mode
interactif de ligne qui consomme moins d'nergie. Slectionner Avec conomie pour faire passer lUPS au mode interactif de ligne.
Slectionner Sans conomie pour faire passer lUPS au mode en ligne..
Aprs avoir dfini ces options, quitter le mode CONFIGURATION laide du bouton DFILEMENT
A, puis quitter le mode DVIATION
en maintenant enfonc le bouton MARCHE
C jusqu ce que lUPS mette un bip.
2. Mettez en marche le UPS : appuyez et maintenez enfonc le bouton d'alimentation ON
C jusqu' ce que vous entendiez un bip pour dmarrer votre
UPS en mode ON BATTERY (sur pile). Prenez note que certains quipements lectroniques tirent plus d'amprage au dmarrage ; lorsque vous dmar-
rez partir des piles, pensez rduire la charge initiale sur le UPS. Votre UPS effectuera un bref essai automatique et affichera les rsultats sur l'afficheur
D. Consultez "Startup Self-Test" (essai automatique de dmarrage) dans la section "Operation" pour la squence de l'afficheur.
3. Pour teindre le module d'alimentation UPS et le module de transformateur (si utilis) : appuyez sur le bouton OFF du module d'alimentation
F
jusqu' ce que vous entendiez un bip. Votre charge sera encore sous tension. L'inverseur est prsent teint mais votre UPS n'est pas entirement dsac-
tiv. L'afficheur
D affichera BYPASS MODE (mode de drivation). teignez le disjoncteur de sortie
E du module d'alimentation. Dbranchez le
cordon d'entre c.a. du module d'alimentation de la prise murale. Si un module de transformateur est utilis, dbranchez son cble connecteur du module
d'alimentation. Votre charge ne sera plus sous tension et l'cran de l'afficheur
D deviendra noir.
Alimentation en Marche/Arrte
(modles 5kVA seulement)
D
C A B F
E
Modles 5kVA
Modles 5kVA
(Panneau Avant)
NORMAL
BY PASS
NORMAL
BY PASS
69
1. Configurer l'entre et la sortie de votre Systme d'alimentation continue sans coupure. Mettre le module d'alimentation de votre Systme d'alimentation
continue sans coupure en mode configuration en maintenant enfoncs ses deux boutons de dfilement
A et
B immdiatement. Faire dfiler les options
de configuration en utilisant
A ou
B et slectionner le rglage appropri pour chacune des options suivantes en utilisant le bouton,
B SELECT.
Tension d'Entre & Sortie : Slectionner 200, 208 ou 240 VAC.
Frquence de Sortie :Votre Systme d'alimentation continue sans coupure slectionnera automatiquement 50 ou 60 Hz pour correspondre l'entre.
Mode Economie : Votre Systme d'alimentation continue sans coupure peut assurer un opration en ligne avec temps de transfert zro. Il peut
aussi fonctionner en mode ligne interactive avec une nergie plus efficace. Slectionner Economy On pour mettre le Systme d'alimentation
continue sans coupure en mode ligne interactive. Slectionner Economy Off pour mettre le Systme d'alimentation continue sans coupure en
mode en ligne.
Aprs avoir rgl ces options, quitter le mode configuration avec le bouton de dfilement
A, puis quitter le mode bypass en maintenant
enfonc le bouton ON
C jusqu' ce que vous entendiez un bip.
2. Mettre en fonction l'entre au Systme d'alimentation continue sans coupure : Si le module d'alimentation du Systme d'alimentation continue sans
coupure est connect un module de transformateur, mettre en fonction l'alimentation CA au Systme d'alimentation continue sans coupure du module
du transformateur et les Disjoncteurs de Circuit de Sortie
D. Mettre en fonction le Disjoncteur de Circuit d'Entre
E
du module d'alimentation du
Systme d'alimentation continue sans coupure. Appuyer sur le bouton ON
C du module d'alimentation du Systme d'alimentation continue sans coupure
jusqu' ce que vous entendiez un bip pour commencer l'opration de l'inverseur. Si votre entre CA ne dlivre pas une alimentation normalement, vous
pouvez dmarrer froid votre Systme d'alimentation continue sans coupure avec la batterie. (Votre batterie doit tre au moins partiellement charge
pour pouvoir excuter cette opration.) Presser et maintenir enfonc le bouton ON
C jusqu' ce que vous entendiez un bip pour dmarrer votre
Systme d'alimentation continue sans coupure en mode SUR BATTERIE. Noter que certains quipements lectroniques peuvent tirer plus d'amps durant
le dmarrage ; lors de dmarrage avec la batterie, envisager de rduire la charge initiale sur le Systme d'alimentation continue sans coupure. Votre
Systme d'alimentation continue sans coupure excutera un autotest bref et indiquera les rsultats sur l'affichage LCD
F . Voir Autotest de Dmarrage
dans la section Fonctionnement pour la squence d'affichage.
3 Mettre en fonction la sortie du Systme d'alimentation continue sans coupure : Mettre en fonction le Disjoncteur de Circuit de Sortie
G du module
d'alimentation du Systme d'alimentation continue sans coupure. Si le Systme d'alimentation continue sans coupure est connect un module de trans-
formateur, tourner le Commutateur Bypass Manuel
H du module du transformateur de BYPASS NORMAL et mettre en fonction son Disjoncteur de
Circuit de Sortie. Votre Systme d'alimentation continue sans coupure dlivrera alors l'alimentation l'quipement connect.
4. Pour mettre hors fonction le module d'alimentation et le module du transformateur du Systme d'alimentation continue sans coupure : Appuyer
sur le bouton OFF
I du module d'alimentation du Systme d'alimentation continue sans coupure jusqu' ce que vous entendiez un bip. Votre charge
restera active. L'inverseur est maintenant hors fonction, mais votre Systme d'alimentation continue sans coupure n'est pas compltement dsactiv.
L'affichage LCD
F indiquera BYPASS MODE. Mettre hors fonction les Disjoncteurs de Circuit d'Entre et de Sortie
E ) et
G du module d'alimentation.
Si le Systme d'alimentation continue sans coupure est connect un module de transformateur, mettre hors fonction l'alimentation CA au Systme
d'alimentation continue sans coupure du module du transformateur et les Disjoncteurs de Circuit de Sortie
D. Votre charge ne sera plus active, et
l'affichage LCD
F sera noir.
Alimentation ON/OFF
(Modles 6kVA et 10kVA seulement)
Modles 6kVA Modles 10kVA
D
E
G
H
E
G
H
Modles 6kVA & 10kVA (Panneau Avant)
D
F
C A B I
NORMAL
BY PASS
NORMAL
BY PASS
70
Opration Bypass Manuelle (Modles 6kVA et
10kVA seulement) (pour maintenance ou remplacement de module d'alimentation)
La procdure suivante s'applique seulement aux configurations de Systme d'alimentation continue sans coupure qui incluent un module de transformateur
de 6kVA ou 10kVA. La procdure dtaille les oprations d'entretien ou de remplacement du module d'alimentation pendant la dlivrance d'alimentation de
service l'quipement connect au module du transformateur. REMARQUE : du fait que le module d'alimentation et le module de la batterie seront dcon-
nects durant la procdure, ils ne pourront pas assurer le support de batterie de secours l'quipement connect au module du transformateur en cas de
coupure de courant.
AVERTISSEMENT ! Pour le personnel d'entretien qualifi seulement. La non-observation de suivre cette procdure entirement ne diminuera
pas de manire adquate l'alimentation du module d'alimentation du Systme d'alimentation continue sans coupure, entranant des risques con-
tinuels de mort ou de blessures du fait de contact potentiel avec une haute tension.
1. Dsactiver le Logiciel d'Alerte Alimentation et dconnecter le cble de communication des ports de communication
A du module d'alimentation.
2. Tourner le Commutateur Bypass
B
du module du transformateur sur BYPASS.
3. Appuyer sur le Bouton OFF
C du module d'alimentation, si le module d'alimentation est aliment, jusqu' l'mission d'un bip et l'affichage d'un message
BYPASS MODE sur le panneau LCD
D.
4. Mettre hors fonction l'alimentation CA bipolaire du module du transformateur au disjoncteur
E du Systme d'alimentation continue sans coupure.
5. Mettre hors fonction le disjoncteur d'entre bipolaire
F et le disjoncteur de sortie bipolaire
G du module d'alimentation.
6. Dconnecter le cble du module de la batterie du connecteur de la batterie
H du module d'alimentation.
7. POUR LES MODULES D'ALIMENTATION 10kVA SEULEMENT : Utiliser un indicateur de tension pour vrifier le cble connectant les blocs de
bornes
I du module d'alimentation aux blocs de bornes
J du module du transformateur pour s'assurer que le module d'alimentation n'est plus ali-
ment. Ds qu'il n'est plus aliment, enlever le cblage.
L'alimentation du module d'alimentation est maintenant rduite en toute scurit et la maintenance/le remplacement peuvent tre excuts.
Modles 6kVA (Panneau Arrire) Modles 10kVA (Panneau Arrire)
A
B
F
G
A
B
F
G
I
E
D
C
Modles 6kVA & 10kVA
(Panneau Avant)
H
E
H
J
71
DIAGNOSTIC MODE
AC/DC OK
DIAGNOSTIC MODE
TESTING INVERTER
ON BATTERY MODE
LOAD = XXX% X.XXKW
Fonctionnement
Quand vous mettez en fonction le Systme d'alimentation continue sans coupure, il entrera le Mode Diagnostic et excutera un autotest bref durant 15
secondes environ. Les rsultats de l'autotest sont indiqus sur l'cran LCD dans la squence ci-dessous..
DIAGNOSTIC MODE
FREQ OUT = XXHz
DIAGNOSTIC MODE
INPUT AC OK
DIAGNOSTIC MODE
INPUT AC OK
DIAGNOSTIC MODE
BATTERY OK
DIAGNOSTIC MODE
CHARGER OK
DIAGNOSTIC MODE
AC/DC OK
DIAGNOSTIC MODE
TESTING INVERTER
ONLINE MODE
LOAD = XXX% X.XXKW
DIAGNOSTIC MODE
FREQ OUT = XXHz
DIAGNOSTIC MODE
INPUT AC BAD
DIAGNOSTIC MODE
INPUT AC BAD
DIAGNOSTIC MODE
BATTERY OK

DEMARRAGE AVEC
ENTRE CA
DEMARRAGE A
FROID*
*Remarque: Si le Systme d'alimentation continue sans coupure est dmarr froid, sa LED BATTERIE sera allume.
Si un problme est dtect durant l'autotest, le LCD affichera un message d'erreur. Si votre Systme d'alimentation continue sans coupure affiche l'un des
messages suivants dans son LCD, appeler le Support Technique Tripp Lite au (773) 869-1234 pour service.
BAD BATTERY!
CALL FOR SERVICE
CHARGER FAILURE!
CALL FOR SERVICE
AC/DC FAILURE!
CALL FOR SERVICE
INVERTER FAILURE!
CALL FOR SERVICE
OUTPUT FAILURE!
CALL FOR SERVICE
FAN FAILURE!
CALL FOR SERVICE
Autotest de Dmarrage
Echec de l'Autotest
SORTIE FREQ MODE
DIAGNOSTIC = XXHz
ENTREE MODE
DIAGNOSTIC CA OK
ENTREE MODE
DIAGNOSTIC CA OK
BATTERIE MODE
DIAGNOSTIC OK
CHARGEUR MODE
DIAGNOSTIC OK
CA/CC MODE
DIAGNOSTIC OK
INVERSEUR TEST MODE
DIAGNOSTIC
CHARGE MODE EN LIGNE
= XXX% X.XXKW
SORTIE FREQ MODE
DIAGNOSTIC = XXHz
CA ENTREE MODE
DIAGNOSTIC MAUVAISE
BATTERIE MODE
DIAGNOSTIC OK
CA/CC MODE
DIAGNOSTIC OK
CHARGEUR MODE
DIAGNOSTIC OK
INVERSEUR TEST
MODE DIAGNOSTIC
CHARGE MODE SUR
BATTERIE = XXX% X.XXKW
MAUVAISE BATTERIE !
APPELER POUR SERVICE
DEFAILLANCE DE
CHARGEUR ! APPELER
POUR SERVICE
DEFAILLANCE CA/CC !
APPELER POUR SERVICE
DEFAILLANCE INVERSEUR !
APPELER POUR SERVICE
DEFAILLANCE SORTIE !
APPELER POUR SERVICE
DEFAILLANCE VENTILATEUR !
APPELER POUR SERVICE
72
Fonctionnement suite
Durant un fonctionnement normal, la premire ligne de votre Affichage LCD indique le mode de fonctionnement en cours de votre Systme d'alimentation
continue sans coupure : En ligne, Economie, Sur Batterie, ou Bypass.
Mode En ligne : Le Systme d'alimentation continue sans coupure dlivre une alimentation CA quand l'alimentation de service est disponible et passe
immdiatement au mode Sur Batterie (temps de transfert zro) si l'alimentation CA est interrompue.
Mode Economie : Le Systme d'alimentation continue sans coupure dlivre une alimentation de haute efficacit quand l'alimentation de service est
disponible et passe rapidement en mode Sur batterie si l'alimentation CA est interrompue.
Mode Sur Batterie : Le Systme d'alimentation continue sans coupure dlivre une alimentation CA depuis la batterie de secours tant que l'alimentation
de la batterie dure. Il retourne en mode En ligne ou Economie si l'alimentation de service est disponible et se ferme quand l'alimentation de la batterie est
puise.
Mode Bypass : Le Systme d'alimentation continue sans coupure dlivre une alimentation CA quand l'alimentation de service est disponible. Le Systme
d'alimentation continue sans coupure se ferme si l'alimentation CA est interrompue.
La deuxime ligne de l'Affichage LCD indique les conditions d'alimentation basiques. Appuyer sur les boutons DEFILEMENT pour visualiser rapidement
ces conditions d'alimentation basiques dans la squence indique ci-dessous.
XXXX MODE
LOAD = XXX% X.XXKW
XXXX MODE
IN = XXXV XX.X Hz
XXXX MODE
OUT = XXXV XX.X Hz
XXXX MODE
BATTERY = XXXVDC

Quand il est en mode Sur Batterie, le module d'alimentation du Systme d'alimentation continue sans coupure mettra un bip pour vous informer qu'il
utilise l'alimentation de la batterie pour supporter l'quipement connect. Si ses batteries connectes sont plus de la moiti de leur capacit, il mettra un
bip toutes les deux secondes. Si ses batteries connectes sont au-dessous de la moiti de leur capacit, il mettra deux bips par seconde. Si ses batteries
connectes sont presque puises, le module d'alimentation du Systme d'alimentation continue sans coupure mettra un bip continuel.
Pour arrter l'Alarme Sur Batterie, appuyer sur le bouton ON/SILENCE.
Quand le Systme d'alimentation continue sans coupure dtecte une surcharge de sortie, son LCD passera l'affichage suivant :
Le Systme d'alimentation continue sans coupure commencera alors un compte rebours. Si le Systme d'alimentation continue sans coupure est toujours
surcharg la fin du compte rebours, le Systme d'alimentation continue sans coupure passera automatiquement au Mode Bypass pour protger son
inverseur. La dure du compte rebours varie avec l'importance de la surcharge, comme suit :
OVERLOAD!
LOAD = XXX% X.XXKW
Condition de Surcharge Dure du Compte rebours
102% - 125% 1 minute
125% - 150% 30 secondes
>150% Immdiat

Fonctionnement Normal
Alarme Sur Batterie
Messages de Surcharge
CHARGE MODE
XXXX = XXX% X.XXKW
MODE ENTREE
XXXX = XXXV XX.X Hz
MODE SORTIE
XXXX = XXXV XX.X Hz
MODE BATTERIE
XXXX = XXXVCC
OVERLOAD!
LOAD = XXX% X.XXKW
73
En Mode Bypass, le Systme d'alimentation continue sans coupure contrle sa tension d'entre et transmet cette alimentation d'entre l'quipement con-
nect. Le Systme d'alimentation continue sans coupure n'assurera pas d'alimentation de batterie de secours en Mode Bypass.
Si la tension de sortie dvie de l'chelle acceptable (entre 15% suprieure et 20% infrieure la valeur nominale), le Systme d'alimentation continue sans
coupure affiche la condition sur son LCD et arrte de dlivrer l'alimentation de sortie sa charge. Si les niveaux d'alimentation retournent un niveau
acceptable, le Systme d'alimentation continue sans coupure reprend la dlivrance d'alimentation la charge, et son LCD indique que la tension de sortie
tait trop leve ou trop basse un moment, mais est retourne sa valeur nominale.
>15% Plus Eleve que la
Valeur Nominale
>20% Plus Basse que la
Valeur Nominale
Etait Trop Eleve, Maintenant
Valeur Nominale
Etait Trop Basse, Maintenant
Valeur Nominale
CONDITIONS DE
TENSION BYPASS
MESSAGES
D'AFFICHAGE LCD
Votre Systme d'alimentation continue sans coupure se fermera et le LCD affichera un message s'il dtecte une des conditions suivantes. Remarque : Durant
toutes ces conditions, les LED Entre, Sortie et Bypass seront allumes.
Surcharge Prolonge
Court-circuit Sortie
Commande Fermeture
Distance (Via DB9)
Commande Fermeture
Distance (Via EPO)
CONDITIONS DE
FERMETURE
MESSAGES
D'AFFICHAGE LCD
Dfaillances Internes
NO OUTPUT BYPASS
AC TOO HI
NO OUTPUT BYPASS
AC TOO LO
BYPASS MODE BYPASS
AC WAS HI
BYPASS MODE BYPASS
AC WAS LO
SHUT DOWN
OVERLOAD XXX%
SHUT DOWN
O/P SHORT CIRCUIT
SHUT DOWN
REMOTE COMMAND
SHUT DOWN
EMERGENCY STOP!
SHUT DOWN
+ DC BUS HIGH
SHUT DOWN
+ DC BUS LOW
SHUT DOWN
- DC BUS HIGH
SHUT DOWN
- DC BUS LOW
SHUT DOWN
OVERTEMPERATURE
Messages de Bypass
Messages de Fermeture
Fonctionnement suite
PAS DE SORTIE CA
BYPASS TROP HAUT
PAS DE SORTIE CA
BYPASS TROP BAS
CA BYPASS MODE BYPASS
ETAIT HAUT
CA BYPASS MODE BYPASS
ETAIT BAS
SURCHARGE
FERMETURE XXX%
FERMETURE
COURT-CIRCUIT O/P
COMMANDE A DISTANCE
FERMETURE
ARRET D'URGENCE
FERMETURE !
FERMETURE
+ BUS CC HAUT
FERMETURE
+ BUS CC BAS
FERMETURE
- BUS CC HAUT
FERMETURE
- BUS CC BAS
FERMETURE TEMPERATURE
TROP ELEVEE
74
Entreposage, Entretien, Garantie et Assurance
Avant d'entreposer votre UPS, teignez-le compltement. Si vous entreposez votre UPS pendant une longue priode, rechargez les piles UPS pendant 4-6
heures une fois tous les trois mois. Remarque : une fois votre UPS branch l'alimentation de service, il commencera automatiquement recharger ses
piles. Si vous laissez les piles UPS dcharges pendant une longue priode, elles souffriront d'une perte de capacit permanente.
Votre systme UPS SmartOnline est couvert par une garantie limite de 2 ans dcrite ci-dessous. Une gamme de programmes de garantie tendue et de
service sur le site est galement disponible chez Tripp Lite. Pour de plus amples informations sur le service, contactez le soutien la clientle de Tripp Lite
au numro (773) 869-1234.
Avant de retourner votre UPS pour entretien, procdez comme suit :
1. Rvisez les instructions d'installation et de fonctionnement de ce manuel pour vous assurer que le problme ne provient pas d'une mauvaise interprtation
des instructions. Vrifiez galement que le(s) disjoncteur(s) du systme UPS ne sont pas dclenchs. C'est la cause la plus courante de demande de service
et on peut facilement y remdier en se conformant aux instructions de remise en tat de ce manuel.
2. Si le problme se poursuit, ne contactez pas et ne retournez pas le UPS au vendeur. Appelez plutt Tripp Lite au numro (773) 869-1233. Un technicien
de service vous demandera le numro du modle du UPS, le numro de srie et la date d'achat et essaiera de corriger le problme par tlphone.
3. Si le problme demande rparation, le technicien vous fournira un numro d'autorisation de matriel retourn (RMA), lequel est obligatoire lors des
rparations. Il vous expliquera galement les procdures adquates d'emballage et d'expdition. Tout dommage (direct, indirect, spcial, accessoire ou
conscutif) au UPS s'tre produit durant l'expdition Tripp Lite ou un centre autoris de Tripp Lite n'est pas couvert par la garantie. Les systmes UPS
expdis Tripp Lite ou un centre de service autoris Tripp Lite doivent tre envoys tout frais de transport pr-pays. Inscrivez le no. RMA l'extrieur
du paquet. Si le systme UPS est encore dans sa priode de garantie de 2 ans, incluez une copie de votre reu d'achat. Retournez le UPS pour rparation
par transporteur assur l'adresse qui vous a t donne par le technicien de service de Tripp Lite.
TRIPP LITE garantit que ses produits incluant les batteries sont exempts de tous dfauts de matriels et de vices de fabrication pendant une priode de deux ans partir de la date
de l'achat initial. Aprs les 90 jours suivant la date d'achat, les obligations de TRIPP LITE dans le cadre de cette garantie sont limites au remplacement des pices de ces produits
dfectueux. Pour obtenir des services dans le cadre de cette garantie, vous devez appeler TRIPP LITE ou un centre de services TRIPP LITE agr. Les produits doivent tre
retourns TRIPP LITE ou un centre de services TRIPP LITE agr avec les frais d'expdition prpays et doivent tre accompagns par une brve description du problme ren-
contr et la preuve de la date et du lieu de l'achat. Cette garantie ne s'applique pas aux quipements qui ont t endommags par accident, ngligence ou application errone ou
qui ont t changs ou modifis d'une manire quelconque. Cette garantie s'applique seulement l'acheteur original qui doit avoir enregistr correctement le produit dans les 10
jours suivant l'achat.
Les garanties pour tous les suppresseurs de surtension TRIPP LITE sont nulles et non avenues si ils ont t connects la sortie de tout Systme d'alimentation continue sans
coupure. Les garanties de tous les Systmes d'alimentation continue sans coupure TRIPP LITE sont nulles et non avenues si un suppresseur de surtension a t connect ses
prises de sortie.
SAUF SI STIPULE DANS LA PRESENTE, TRIPP LITE N'ACCORDE AUCUNES GARANTIES, EXPRESSES OU IMPLICITES, INCLUANT LES GARANTIES DE
COMMERCIALISATION ET ADAPTATION POUR UN BUT PARTICULIER. Certains tats ne permettent pas la limitation ou l'exclusion des garanties implicites ; en consquence,
le(s) limitation(s) ou exclusion(s) peuvent ne pas s'appliquer l'acheteur.
SAUF SI STIPULE CI-DESSUS, EN AUCUN CAS TRIPP LITE NE SERA RESPONSABLE POUR TOUS DOMMAGES DIRECTS, INDIRECTS, SPECIAUX, ACCIDENTELS OU
PROVOQUES RESULTANT DE L'UTILISATION DE CE PRODUIT, MEME SI INFORME DE LA POSSIBILITE D'UN TEL ENDOMMAGEMENT. En particulier, TRIPP LITE n'est pas
responsable de tous cots, tels que perte de profits ou revenus, perte d'quipement, perte d'utilisation d'quipement, perte de logiciel, perte de donnes, cots de substituts, rcla-
mations de tierces parties, ou autre.
La politique de TRIPP LITE est celle d'une amlioration continuelle. Les spcifications peuvent tre modifies sans pravis.
AVIS D'INTERFRENCE FCC RADIO/TV
Remarque : cet quipement a t mis l'essai et trouv conforme aux limites pour un dispositif numrique de catgorie B, en vertu de la partie 15 des rglements FCC. Ces lim-
ites sont conues pour procurer une protection raisonnable contre une interfrence nuisible lorsque en opration dans un environnement commercial. Cet quipement gnre, util-
ise et peut diffuser des frquences radio et, s'il n'est pas install et utilis conformment au manuel d'instructions, peut causer des interfrences avec les communications radio.
L'opration de cet quipement est susceptible de causer une interfrence nuisible auquel cas l'utilisateur devra corriger l'interfrence ses frais. L'utilisateur doit utiliser des
cbles et connecteurs arms avec ce produit. Tout changement ou modification ce produit non expressment approuve par la partie responsable de la conformit pourrait
annuler l'autorit de l'utilisateur faire fonctionner l'quipement.
Numros d'identification de conformit aux rglements
des fins de certification et d'identification de conformit aux rglements, votre produit Tripp Lite a reu un numro de srie unique. Ce numro se retrouve sur la plaque signal-
tique du produit, avec les inscriptions et informations d'approbation requises. Lors d'une demande d'information de conformit pour ce produit, utilisez toujours le numro de srie.
Il ne doit pas tre confondu avec le nom de la marque ou le numro de modle du produit.
Entreposage
Garantie Limite 2 Ans
Entretien
1111 W. 35th Street, Chicago, IL 60609 USA
773.869.1234 (USA) 773.869.1212 (International)
www.tripplite.com
200907004 932407-FR
75
Spcifications
Les modles numrs ci-dessous comprennent un module d'alimentation, un ou deux modules de batteries et un module transducteur. Selon le modle
command, le module de batterie pourra tre non-rutilisable ou rutilisable.Cependant si une dure d'utilisation prolonge est requise, tous les modules
d'alimentation sont compatibles avec les modules de batterie Tripp Lite non-rutilisables (Modles Tripp Lite No BP240V10RT-3U, vendus sparment).
Information sur le modle
No(s) de modle SU5000RT3UHV* et SU5000RT3U SU6000RT3UHV* et SU6000RT3U SU6000RT3UXR SU10KRT3UHV* et SU10KRT3U
L'ensemble comprend :
Module d'alimentation (modle : SU5000RT3UPM; (modle : SU6000RT3UPM; (modle : SU6000RT3UPM; (modle : SU10KRT3UPM;
srie : AGPS5124) srie : AGSU60003U) srie : AGSU60003U) srie : AGSU100003U)
Module piles no. 1 (modle : BP240V5RT2U; (modle : BP240V7RT3U; (modle : BP240V7RT3U; (modle : BP240V10RT-3U;
srie: AGBP5161) srie: AGBP240V7RT3U) srie: AGBP240V7RT3U) srie: AGBP240V7RT3U)
Non extensible Non-extensible Non-extensible EXTENSIBLE
Module piles no. 2 N/A N/A (modle : BP240V10RT3U; N/A
srie: AGBP240V7RT3U)
EXTENSIBLE
Module de transformateur (modle : SU5000XFMRT2U; (modle : SU6000XFMRRT3U; (modle : SU6000XFMRRT3U; (modle : SU10KXFMRRT3U;
srie: AGc.a.5125) srie: AGSM6000SDRT3U) srie: AGSM6000SDRT3U) srie: AGSM10KSDRT3U)
Approbations : tous les modules d'alimentation (UL, cUL, NOM, CE, GOST, SASO, IRAM, FCC catgorie A). Tous les modules de batterie except BP240V5RT2U (UL, cUL, NOM). Tous les mod-
ules transducteurs.(UL, cUL, NOM, FCC Class A).
Entre
Type de connexion d'entre 10 pi. cordon avec prise L6-30P cblage cblage cblage
Plage de tension d'entre 156V~276V monophas 156V~276V monophas 156V~276V monophas 156V~276V monophas
Tension d'entre du module 200/208/240V c.a. 200/208/240V c.a. 200/208/240V c.a. 200/208/240V c.a.
Frquence d'entre 50/60 Hz 3 Hz 50/60 Hz 3 Hz 50/60 Hz 3 Hz 50/60 Hz 3 Hz
Courant d'entre 20A 22.6A 22.6A 40A
Courant d'appel <150A <150A <150A <200A
Facteur d'alimentation (charge pleine) >0.97 >0.97 >0.97 >0.97
Efficacit (charge pleine/en ligne) >87% >87% >87% >88%
Disjoncteur du module d'alimentation N/A 40A (2 ple) 40A (2 ple) 63A (2 ple)
Disjoncteur du module de transformateur N/A 40A (2 ple) 40A (2 ple) 63A (2 ple)
Sortie
VA 5000 6000 6000 10000
Watts (facteur d'alimentation : 0,7) 3500 4200 4200 7000
Type de connexion de sortie 4 prises sur le module d'alimentation cblage cblage cblage
(2 L6-20R et 2 L6-30R) et quipements cbls de sortie de plaque de fond en option : SUPDM11
12 prises sur le transformateur (SU6000RT3UHV); SUPDM12 (SU6000RT3UHV et SU6000RT3UXR);
module (5-15/20R) SUPDM13 (SU6000RT3U et SU6000RT3UXR); SUPDM15 (SU6000RT3U
et SU6000RT3UXR); SUPDM16 (SU6000RT3U et SU6000RT3UXR)
Forme d'onde (en ligne) sinusodale sinusodale sinusodale sinusodale
Forme d'onde (en ligne) sinusodale sinusodale sinusodale sinusodale
Tension d'entre (RMS) 120*/200/208/240V c.a. 100/120/200/208/240V c.a. 100/120/200/208/240V c.a. 100/120/200/208/240V c.a.
Frquence de sortie 50/60 Hz ( 0.2 Hz sur pile) 50/60 Hz ( 0.2 Hz sur pile) 50/60 Hz ( 0.2 Hz sur pile) 50/60 Hz ( 0.2 Hz sur pile)
Rgulation de tension 3% 3% 3% 3%
Max. Distorsion harmonique
(charge linaire entire) <3% <3% <3% <3%
(charge entire non-linaire) <6% <6% <6% <6%
Capacits de surtension 102% (continu) 102% (continu) 102% (continu) 102% (continu)
102%~125% (1 min.) 102%~125% (1 min.) 102%~125% (1 min.) 102%~125% (1 min.)
125%~150% (30 sec.) 125%~150% (30 sec.) 125%~150% (30 sec.) 125%~150% (30 sec.)
>150% (immdiat) >150% (immdiat) >150% (immdiat) >150% (immdiat)
Capacit de court-circuit 90A 90A* 90A* 160A*
Disjoncteur du module d'alimentation 20A (2 ple) 40A 40A 63A
Disjoncteur du module de transformateur* quatre 20A (ple simple) 30A (3 ple) 30A (3 ple) 63A (3 ple)
Facteur de crte 3:1 3:1 3:1 3:1
* La capacit de court circuit 1 2W 120V pour le SU6000RT3U et le SU6000RT3UXR est suprieure 180A et pour le SU10KRT3U, elle est suprieure 320A.
Opration
Temps de transfert en ligne
(Ligne pile, pile ligne) 0 ms. 0 ms 0 ms 0 ms
Bruit audible (charge @ 1 m) <50 dBA <50 dBA <55 dBA <55 dBA
Indicateurs
Comprend un afficheur et des tmoins lumineux (entre), PILE, C.A./C.C., C.C./C.A. CONTOURNEMENT, ENTRE/SORTIE (sortie)).
Communications
Comprend un connecteur femelle RS-232 DB9, un connecteur femelle contact sec DB9 et une fente accessoire.
Spcifications physiques
Dimensions de l'appareil (H x W x D)
Module d'alimentation 5,25 (3U) x 17,5 x 26 po. 5,25 (3U) x 17,5 x 22,5 po. 5,25 (3U) x 17,5 x 22,5 po. 5,25 (3U) x 17,5 x 22,5 po.
[13,4 x 44,5 x 66 cm.] [13,4 x 44,5 x 57,2 cm.] [13,4 x 44,5 x 57,2 cm.] [13,4 x 44,5 x 57,2 cm.]
Module de transformateur 3,5 (2U) x 17,5 x 20,75 in. 5,25 (3U) x 17,5 x 26 po. 5,25 (3U) x 17,5 x 26 po. 5,25 (3U) x 17,5 x 26 po.
[8,9 x 44,5 x 52,7 cm.] [13,4 x 44,5 x 66,1 cm.] [13,4 x 44,5 x 66,1 cm.] [13,4 x 44,5 x 66,1 cm.]
Module piles no. 1 3,5 (2U) x 17,5 x 20,75 in. 5,25 (3U) x 17,5 x 22,5 po. 5,25 (3U) x 17,5 x 22,5 po. 5,25 (3U) x 17,5 x 22,5 po.
[8,9 x 44,5 x 52,7 cm.] [13,4 x 44,5 x 57,2 cm.] [13,4 x 44,5 x 57,2 cm.] [13,4 x 44,5 x 57,2 cm.]
Module piles no. 2 (si applicable) N/A N/A 5,25 (3U) x 17,5 x 22,5 po. N/A
[13,4 x 44,5 x 57,2 cm.]
Poids l'expdition
Module d'alimentation 58 lbs. [27 kg.] 58 lbs. [27 kg.] 58 lbs. [27 kg.] 68 lbs. [31 kg.]
Module de transformateur 60 lbs. [28 kg.] 124 lbs. [57 kg.] 124 lbs. [57 kg.] 124 lbs. [57 kg.]
Module piles no. 1 95 lbs. [43 kg.] 160 lbs. [73 kg.] 160 lbs. [73 kg.] 160 lbs. [73 kg.]
Module piles no. 2 (si applicable) N/A N/A 160 lbs. [73 kg.] N/A
lncpykun enupensuu
1111 W. 35th Street, Chicago, IL 60609 USA
773.869.1234 (USA) 773.869.1212 (International)
www.tripplite.com
Hn+ennex+yaninan co6c+nennoc+i 2009 Tripp Lite. Bce npana samnmeni.
3martOn||ne
'
opnouansn 6| B^ n 10|B^
luayvnse, onnunnoese cncevs lconnka Lecnepeonnoro lnunn (lLl)
(konnrypuun uunn)
nn ncex cnc+exnix xopynen HBH (6nox nn+annn, nsonnpymmnn +pancqopxa+opnin xopyni n 6a+apen),
npopannix nn6o o+penino, nn6o nxec+e. Hexo+opie cnc+exnie xopynn HBH xoiy+ nxnmna+i o+peninym
nnc+pyxnnm nnn npepoc+epexennn, xo+opie ponxni 6i+i ncnonisonani conxec+no c +on nnc+pyxnnen.
.
Bu+nu nncpykun no eaonucnocn
vcunoeku
Ooepnnenne
Oeonceu
lpuennu nonsaoeunn
Oepenc/lupunn
Oneunnkuunn
English/Espaol/Franais
77
78
80
84
91
94
95
1/26/51
[ononnnensnoe Ooepnnenne 88
Oes BlIl-L|/BLlIl-L| 89
lpuennu luos Bpyny| 90
77
Bu+nu nncpykun no eaonucnocn
COXPAHHTE 3TH HHCTPYKHHH. 3+o+ poxyxen+ copepxn+ nnc+pyxnnn n npepynpexpennn, xo+opix pexoxenpye+cn cnepona+i
no npexn nnc+annnnn, ncnonisonannn n xpanennn HBH cnc+ex Tripp Lite SmartOnline 6amennon xonqniypannn, a +axxe nx
6a+apen.
lpepynpe+penne no puaveuenn| lLl
Yc+anonn+e nam HBH n noxemennn, n cyxox npoxnapnox xec+e, nne nonapannn nponopnmnx saipnsnn+enen, ninn nnn
npnxoio connennoio cne+a.
Yc+anonn+e nam HBH n ypo6nox xec+e. Bam HBH npepenino +nxenin; 6ypi+e oc+opoxni nepepnnian nnn nopnnxan eio.
Honisyn+eci HBH +onixo npn xoxna+nix +exnepa+ypax xexpy 32 F n 104 F (xexpy 0 C n 40 C). nn nynmnx
pesyni+a+on, noppepxnnan+e xoxna+nym +exnepa+ypy xexpy 62 F n 84 F (xexpy 17 C n 29 C).
Oc+ani+e apexna+noe npoc+panc+no co ncex c+opon HBH pnn nen+nnnnnn.
He yc+anannnnan+e HBH nosne xainn+nix cpepc+n xpanennn nnqopxannn, +ax xax +o xoxe+ npnnec+n x no+epe
nnqopxannn.
, ( ).
,
, .
lpepynpe+penne no nopcoepnnenn| lLl
Bnox nn+annn pnn +oio npn6opa ponxen 6i+i opnoqasnix n coo+ne+c+nnn c 6npxon na npn6ope.
On uk+e pon+en ss npuennsno auaevnen
,

.
, .
Hopcoepnnn+e nam 6nox nn+annn HBH n/nnn +epxnnan nsonnpymmeio +pancqopxa+opa x nponopnnxy nex+popa.
HBH nopcoepnnne+cn x nc+onnnxy noc+onnnoio +oxa (6a+apen). Binopi xoiy+ 6i+i xnnixn, xoipa HBH ne nopcoepnnn x
nc+onnnxy nepexennoio +oxa.
lpepynpe+penne no ocny+neunn|
Bam 6nox nn+annn, nsonnpymmnn +pancqopxa+opnin xopyni n 6a+apen HBH ne +pe6ym+ peiynnpnoio yxopa. He
o+xpinan+e nam HBH.Bny+pn HBH ne+ nac+en, +pe6ymmnx pexon+a.
lpepynpe+penne o uupee
He ncnonisyn+e nam HBH 6es nopcoepnnennn x nnemnen 6a+apee.
Hopcoepnnn+e +onixo xopyni 6a+apen Tripp Lite x coepnnn+enm nnemnen 6a+apen HBH.
Ba+apen HBH nopnexa+ nepepa6o+xe. O6pa+n+eci x xec+nix cnopax npannn no nepepa6o+xe, pnn nnqopxannn n npepenax
CBA nosnonn+e no +eneqonnoxy noxepy 1800SAVLEAD (180082285323) pnn +oio, n+o6i nonynn+i nnqopxannm no
nepepa6o+xe. BHHMAHHE: He 6pocan+e 6a+apen n oioni +o xoxe+ npnnec+n x nspiny.
Hocxonixy 6a+apen npepc+annnm+ pncx nex+pnnecxoio moxa n oxoia n pesyni+a+e xopo+xoio saxixannn, 6a+apen ponxni
saxenn+icn +onixo o6ynennix nepconanox, co6nmpammnx napnexamne xepi npepoc+opoxnoc+n. O6pa+n+eci x
nnc+pyxnnnx, nepep +ex xax +ex xax npnc+ynn+i. Cnnxn+e naci, xonina, n ppyine xe+annnnecxne npepxe+i. Hcnonisyn+e
nnc+pyxen+i c nsonnponannixn pyxon+xaxn. Openi+e pesnnonie nepna+xn n 6o+nnxn. He xnapn+e nnc+pyxen+i nnn
xe+annnnecxne pe+ann na 6a+apem. He saxixan+e 6a+apem noc+oponnnxn npepxe+axn. O+coepnnn+e nc+onnnx
nanpnxennn, nepep +ex xax coepnnn+i nnn o+coepnnn+i nnopi 6a+apen. Onpepenn+e, sasexnena nn 6a+apen. Ecnn 6a+apen
sasexnena, ypann+e nc+onnnx sasexnennn. Kon+ax+ c nm6on nac+im sasexnnnon 6a+apen xoxe+ npnnec+n x
nex+pnnecxoxy moxy. Bepon+noc+i +axoio moxa 6ype+ cnnxena, +axne ocnonannn ypannm+cn no npexn nnc+annnnn n
pexon+a.
He o+xpinan+e n ne pas6npan+e 6a+apem. 3nex+ponn+ npepen pnn xoxn n inas, n xoxe+ 6i+i +oxcnnen
Tonixo canxnnonnponannin nepconan xoxe+ xenn+i npepoxpann+enn. Hepeiopenmne npepoxpann+enn cnepye+ xenn+i
+onixo na npepoxpann+enn +oio xe noxepa n +nna.
Cepnnc n pexon+ ponxen nponsnopn+icn +onixo o6ynennix nepconanox. Bo npexn o6cnyxnnannn HBH ponxen 6i+i
o+xnmnn nnn npynnym nepexnmnen na +pancqopxa+op. Bnnxanne: nny+pn +oio 6noxa cymec+nye+ no+ennnanino
cxep+eninin yponeni nanpnxennn, ecnn 6a+apen nopcoepnnena.
He coepnnnn+e n ne pas+epnnnn+e xopyni 6a+apen, noxa HBH pa6o+ae+ o+ 6a+apen nnn xoipa xopyni +pancqopxa+opa ne
nepexnmnen na nepexinxy (ecnn nama cnc+exa HBH npepnonaiae+ xopyni +pancqopxa+opa).
Bo npexn saxeni 6a+apen nam HBH ne cxoxe+ o6ecnenn+i nn+anne, n cnynae o+xnmnennn nex+pnnec+na.
78
vcunoeku (Oennu+)
1
vcunoeku 4-konuknoro cennu+u
1
2
3
A
B
C
F
E
G
4
H
Coepnnn+e pna ceixen+a xaxpon nonxn

A
ncnonisyn npnnaiammnecn nnn+i
n ianxn
B
. He saxpynnnan+e nnn+i nno+no,n+o6i nonxn xoxno 6ino
npncnoco6n+i na cnepymmex +ane.
Apan+npyn+e xaxpym nonxy, n+o6i ona nopomna x c+ennaxy, sa+ex
npnxpenn+e nonxn nnnsy nameio c+ennaxa npn noxomn nnn+on n iaex

C
.
Bnnxanne: yionxn ponxni 6i+i o6pameni nonny+pi. 3a+nnn+e ianxn,
n+o6i coepnnn+i ceixen+i nonxn
D
.
Hpncoepnnn+e saxpenn+enn
E
x nnnenon c+opone o+nepc+nn nameio
o6opyponannn

F
ncnonisyn npepnoxennie nnn+i
G
. 3axpenn+enn ponxni
6i+i nnnenon c+oponon nnepp.
Hpn noxomn accnc+en+a, nopnnxn+e nam npn6op n noc+ani+e eio na nonxy.
Hpncoepnnn+e name o6opyponanne x c+ennaxy npn noxomn nnn+on n iaex
(o6ecnenennin nonisona+enex)

H
nepes saxpenn+enn n penici c+ennaxa.
H+o6i cxon+npona+i name o6opyponanne na 2x ocnonnox c+ennaxe, ni ponxni
npno6pec+n 2x ocnonnin nnc+annnnonnin na6op o+ Tripp Lite (xopeni: 2
POSTRMKIT, npopa+cn o+penino) pnn xaxpoio yc+anonnennoio xopynn.
O6pa+n+eci x nnc+annnnonnoxy cnpanonnnxy nnapenina sa nnc+pyxnnnxn x
xon+axy.
4
Bxon+npyn+e name o6opyponanne n c+ennax na 4x nnn 2x ocnonax nnn c+ennax c nonxon. Honisona+eni ponxen onpepenn+i
npniopnoc+i npn6opon n nponecc nepep yc+anonxon. Ecnn npn6opi n nnc+pyxnnn ne nopxopn+ pnn namen annnnxannn, o6pa+n+eci
x nsio+onn+enm nameio c+ennaxa nnn xopnyca c+ennaxa. Hnc+pyxnnn, onncannie n +ox poxyxen+e, npniopni pnn c+anpap+noio
c+ennaxa n +nnon xopnyca c+ennaxa n xoiy+ coo+ne+c+nona+i ne ncex npnnoxennnx.
2
3
vcunoeku (enekov) nu 2x ocnoeux
B
D
79
vcunoeku (Luun)
Honepnn+e Haneni Ynpannennn 6noxa nn+annn, n+o6i e 6ino nynme nnpno no
npexn 6amennon yc+anonxn HBH. Bc+ani+e xanenixym o+np+xy, nnn ppyion
nnc+pyxen+, n nipesi na nm6on c+opone Hanenn Ynpannennn. Bi+amn+e naneni;
nonepnn+e naneni n noc+ani+e e na xec+o.
Cxon+npyn+e nce xopynn n nep+nxaninon, 6amennon nosnnnn, npnnaiaexym ocnony. (xopeni: 29USTAND, npopa+cn o+penino)
Honisona+eni ponxen onpepenn+i npniopnoc+i npn6opon n nponecca nepep +ex, xax yc+anannnna+i.
80
Oeonceu
Tripp Lite npepnaiae+ +pn o+peninix cnc+exnix xopynn HBH ( 6nox nn+annn, nsonnpymmnn +pancqopxa+opnin xopyni n
6a+apen) ncnonisyexix n pasnoo6pasnix xox6nnannnx. Osnaxoxi+eci c pasxemennex n qynxnnnxn xaxpoio xopynn, nepep +ex,
xax +ex xax yc+anannnna+i n ncnonisona+i nam HBH. Bnox nn+annn epnnc+nennin xopyni, xo+opin nxnmnae+ cnonc+na nepepnen
nanenn.
lepepn lunens Lnoku lnunn
1. HHKOKPHCTAJJHHECKHH (HK) HCHJEH: 3+o+ +onennin pncnnen c nopcne+xon (16 x 2 cnxnona) noxasinae+
mnpoxnn pnanason pexnxa pa6o+i HBH n pnainoc+nnecxnx pannix. On +axxe noxasinae+ napaxe+pi nac+ponxn HBH n
onnnn, xoipa HBH naxopn+cn n pexnxe yc+anonxn.
2. BKJKHHTB/OBE33BYHHTB KHOHKA: Haxxn+e +y xnonxy n pepxn+e, noxa ne ycnimn+e snyxonon cninan, nop+nepxpammnn
nxnmnenne nnnep+epa HBH. Ecnn 6a+apen HBH npoponxae+ snyna+i, naxxn+e +y xnonxy, n+o6i e o6essnynn+i.
3. KHOHKA BHH3/HOKHHYTB PEHHM HACTPOHKH: 3+a xnonxa nosnonne+ nax npocxo+pe+i pasnnnnie onnnn n
noxasa+enn cnn+inannn nanpnxennn na HK pncnnee. Haxa+ne +on xnonxn nisinae+ nonin noxasa+eni cnn+inannn
nanpnxennn na HK pncnnee (cx. Hpannna Honisonannn). Haxa+ne +on xnonxn opnonpexenno c xnonxon BBEPX npnnopn+
HBH n pexnx nac+ponxn, ipe +a xnonxa ncnonisye+cn pnn +oio, n+o6i npocxo+pe+i onnnn nac+ponxn n nin+n ns pexnxa
nac+ponxn.
4. KHOHKA BBEPX/BBBOP: 3+a xnonxa nosnonne+ nax npocxo+pe+i pasnnnnie onnnn n noxasa+enn cnn+inannn nanpnxennn
na HK pncnnee. Haxa+ne +on xnonxn nisinae+ nonin noxasa+eni cnn+inannn nanpnxennn na HK pncnnee (cx. Hpannna
Honisonannn). Haxa+ne +on xnonxn opnonpexenno c xnonxon BHH3 npnnopn+ HBH n pexnx nac+ponxn, ipe +a xnonxa
ncnonisye+cn pnn +oio, n+o6i npocxo+pe+i onnnn nac+ponxn n ni6npa+i pasnie onnnn nac+ponxn.
5. KHOHKA BBKJKHHTB: Haxxn+e +y xnonxy noxa ni ne ycnimn+e snyxonon cninan, yxasinammnn na nixnmnenne
nnnep+opa HBH.
6. CH BBBO: 3+o+ senenin nnpnxa+op saiopn+cn, yxasinan na +o, n+o HBH nopae+ nex+ponn+anne x nopcoepnnnnoxy
o6opyponannm.
7. CH HEPEMEHHOIO/HOCTOZHHOIO TOKA: +o+ sennin nnpnxa+op saiopn+cn, n+o6i yxasa+i, n+o nnnep+op
ax+nnnponan.
8. CH HEPEMBHKA: +o+ sennin nnpnxa+op saiopn+cn, xoipa HBH o6ecnennnae+ qnni+ponannoe nn+anne 6es +oio, n+o6i
sapenc+nona+i eio npeo6pasona+eni nnn nnnep+op. Ecnn +o+ CH iopn+, nopcoepnnnnoe o6opyponanne ne nonynn+ nn+anne
o+ 6a+apen n cnynae no+epn nex+ponepinn.
9. CH HPZMOIO/HEPEMEHHOIO TOKA (Hpeo6pasona+eni): 3+o+ senenin nnpnxa+op saiopn+cn, yxasinan na +o, n+o
npeo6pasona+eni HPZMOIO/HEPEMEHHOIO TOKA sapnxae+ nopcoepnnnnin 6nox 6a+apen.
10. CH BATAPEZ: +o+ xpacnin cne+ saiopn+cn, yxasinan na +o, n+o HBH paspnxae+ 6a+apem, n+o6i o6ecnenn+i nopcoepnnnnoe
o6opyponanne nex+ponn+annex. Hposnynn+ npepynpexpammnn cninan, xo+opin xoxno o+xnmnn+i ny+ex naxa+nn xnonxn
BKJKHHTB/OBE33BYHHTB. Hnpnxa+op npoponxn+ iope+i nocne o+xnmnennn npepynpexpammeio cninana.
11. CH BXO: 3+o+ senenin nnpnxa+op saiopn+cn, yxasinan na +o, n+o nc+onnnx nepexennoio +oxa npncy+c+nye+.
12. OTBEPCTHE OCTYHA: H+o6i nonepny+i pynxn xon+ponn, nc+ani+e nnocxym o+np+xy n +o o+nepc+ne n nnanno ni+amn+e
naneni. Hoc+apan+eci ne cnnmxox nonepny+i +n pynxn xon+ponn n ne nipepny+i xa6enn coepnnnmmne +o xon+poninoe
cpepc+no c HBH, nonepnn+e pynxn xon+ponn n nyxnox nanpannennn n nc+ani+e sanono.
1
2 3 4 5
6 8 7 9 10 11
12 12
81
Oeonceu (3upn lunens) cx. c+p 83 pnn onncannn cnonc+n
6lB^ Lnok lnunn
6lB^ Mopyns laonnpy|unn 1puncopvuop
Mopyns Luupen pn vopenen 6lB^ n 10lB^
5 4
6
7
8 9 10
16
17
15
12
20 21
3
1 2
11
13
18 19
82
10lB^ Lnok nnunn
4 5 6
7
8 9
10
3
Mopyns Luupen pn vopenen 6lB^ n 10lB^
20
21
10lB^ Mopyns laonnpy|unn 1puncopvuop
16 14 11 12
17
1 2
15
18 19
Oeonceu (3upn lunens) cx. c+p 83 pnn onncannn cnonc+n
83
Oeonceu (3upn lunens) npoponxenne
Onncunne Oeonce Lnoku nnunn (vopenn 6lB^ n 10lB^ )
1. Bnox Binop Tepxnnana: Hcnonisyn+e +n nnopi, n+o6i nopcoepnnn+i nam 6nox nn+annn x namexy o6opyponannm nnn x
xopynm +pancqopxa+opa. O+nnn+n+e n ypann+e noxpi+ne 6noxa pnn poc+yna.
2. Bnox Bnop Tepxnnana: Hcnonisyn+e +n nnopi, n+o6i nopcoepnnn+i nam 6nox nn+annn x namexy nc+onnnxy nn+annn nnn
xopynm +pancqopxa+opa. O+nnn+n+e n ypann+e noxpi+ne 6noxa pnn poc+yna.
3. Coepnnn+eni Bnemnen Ba+apen: Hcnonisyn+e +o, n+o6i nopcoepnnn+i opnn nnn 6onee xopynen 6a+apen x 6noxy nn+annn.
Ypann+e noxpi+ne pnn poc+yna. Bnox nn+annn ne nann+ pa6o+a+i 6es nopcoepnnennn x xopynm sapnxennon 6a+apen.
O6pa+n+eci x nnc+pyxnnn nnapenina xopynn 6a+apen sa nnc+pyxnnnxn x nopcoepnnennm n nnc+pyxnnnxn no 6esonacnoc+n.
4. Bxop Hepexnmna+eni Hepexennoio Toxa: 1 pnyxnonmcnin nepexnmna+eni xon+ponnpye+ nopany nn+annn x x 6noxy nn+annn.
5. Bixop Hepexnmna+eni Hepexennoio Toxa: 1 pnyxnonmcnin nepexnmna+eni xon+ponnpye+ pac xop nepinn o+ 6noxa nn+annn.
6. Ben+nnn+op: Oxnaxpae+ n nen+nnnpye+ 6nox nn+annn nsny+pn.
7. O+nepc+ne pnn Axceccyapon: Ypann+e xanenixym naneni pnn +oio, n+o6i yc+anonn+i pononnn+eninie axceccyapi pnn
ypannnoio ynpannennn n xon+ponn sa namnx HBH. Hoce+n+e Tpnnn Jan+ n nn+epne+e www.tripplite.com pnn nonynennn 6onee
noppo6non nnqopxannn o6 SNMP, npopyx+ax no ynpannennm ce+nxn n nopcoepnnennex, xo+opie xoiy+ 6i+i yc+anonneni n
+ox o+nepc+nn.
8. Anapnnnoe O+xnmnenne (AO): Bnox nn+annn nxee+ nop+ AO, xo+opin xoxe+ 6i+i nopxnmnen x xon+poninoxy nixnmna+enm
pnn anapnnnoio nixnmnennn. 3a noppo6noc+nxn o6pa+n+eci x paspeny ononnn+eninoe Hopxnmnenne
9. Cnnsi nepes Ynnnepcaninin Cepnnnin Hop+ (USB) RS232: 3+o+ cepnnnin nop+ DB2 xoxe+ ncnonisona+icn, n+o6i
nopcoepnnn+i nam HBH x nac+oninoxy xoxnim+epy nnn cepnepy. ncnonisye+ npo+oxon RS232 pnn cnnsn c xoxnim+epox.
Hcnonisye+cn c npoipaxxnix o6ecnenennex Tpnnn Jan+ n cepnnnix xa6enex, pnn +oio, n+o6i na6nmpa+i n peiynnpona+i
HBH nepes ce+n n, pnn +oio, n+o6i coxpann+i o+xpi+ie qanni n nixnmna+i o6opyponanne no npexn o+xnmnennn
nex+ponn+annn. Cxo+pn+e ononnn+eninoe Coepnnenne.
10. Cyxon xon+ax+nin nn+epqencnin nop+: 3+o+ nop+ +nna DB9 o+npannne+ cninani o npexpamennn xon+ax+a, n+o6i yxasa+i
na c6on na nnnnn n c+a+yc nnsxoio yponnn 6a+apen. Cxo+pn+e ononnn+eninoe Coepnnenne.
Mopyns laonnpy|unn 1puncopvuop- Onncunne Oeonce (vopenn 6lB^ n 10lB^)
11. Bnox Tepxnnan Bnop Hn+annn : Hcnonisyn+e +n +epxnnani pnn nopcoepnnennn nameio xopynn +pancqopxa+opa x nc+onnnxy
nn+annn. O+xpy+n+e n ypann+e noxpi+ne 6noxa pnn poc+yna.
12. Bnox Tepxnnan Binop O6opyponannn: Hcnonisyn+e +n +epxnnani pnn coepnnennn nameio o6opyponannn c xopynex
+pancqopxa+opa. O+xpy+n+e n ypann+e noxpi+ne 6noxa pnn poc+yna.
13. Ka6eni pnn Coepnnennn Bnoxa Hn+annn (+onixo 6KBA xopenn ): Coepnnne+ xopyni +pancqopxa+opa n nnop/ninop nn+annn
nocne +oio, xax +epxnnani 6noxa nn+annn 6inn ypaneni. Cxo+pn+e paspen Coepnnenne.
14. Hec+xnn Bnox Tepxnnan pnn Coepnnennn Bnoxa Hn+annn (+onixo 10KBA xopenn ): Hcnonisyn+e +n +epxnnani pnn
nopcoepnnennn xopynn +pancqopxa+opa x xopynm 6noxa nn+annn, 6noxax nxopa n ninopa. Cxo+pn+e paspen Coepnnenne.
15. Hepexnmna+eni Hepeipena: +o+ nepexnmna+eni cpa6a+inae+, ecnn +exnepa+ypa +oio yc+ponc+na nopnnxae+cn cnnmxox nicoxo.
16. Hepexnmna+eni Hepexennoio Toxa na HBH: opnn pnyxnonmcnin nepexnmna+eni xon+ponnpye+ nixop nanpnxennn na HBH.
17. Hepexnmna+eni Bixop: +pxc+oponnnn nepexnmna+eni xon+ponnpye+ nixop nanpnxennn x nopcoepnnnnoxy
o6opyponannm.
18. Hepexnmna+eni ns an+oxa+nnecxoio pexnxa: 3+o+ xpacnin n xen+in pncx ncnonisye+cn pnn +oio, n+o6i o+xnmna+i 6nox
nn+annn, no npexn pexon+a 6noxa nn+annn. B +o npexn, xoipa nixnmna+eni noxasinae+ HEPEMBHKA, nopcoepnnnnoe
o6opyponanne nonynae+ qnni+ponannym nn+anne o+ xopynn +pancqopxa+opa, no o6opyponanne ne nonynn+ nn+anne o+
6a+epen n cnynae o+xnmnennn nex+ponepinn. Cxo+pn+e Hpannna Honisonannn Bpynnym, n+o6i nonynn+i noppo6nym
nnqopxannm o nponecce nepexopa.
BHHMAHHE! Tonixo pnn xnannqnnnponannoio o6cnyxnnammeio nepconana. B cnynae neco6nmpennn npannn, xopyni 6a+apen HBH
xoxe+ ne o+xnmnn+i nn+anne n npnnec+n x onacnoxy xon+ax+y c nicoxnx nanpnxennex n nosxoxnoxy cxep+eninoxy ncxopy.
19. Hepexnmna+eni Bnopa Hanpnxennn: ncnonisyn+e +o+ nixnmna+eni pnn +oio, n+o6i ni6pa+i nanpnxenne na xopyne
+pancqopxa+opa (200 B, 208B, 240B). Cxo+pn+e paspen Coepnnenne.
Onncunne Oeonce Mopyn Luupen (6lB^ n 10lB^)
20. Coepnnn+eni nxopa: Hcnonisyn+e +o+ coepnnn+eni pnn nopcoepnnennn pononnn+eninix xopynen 6a+apen x nepnoxy xopynm.
Ypann+e naneni pnn poc+yna. O6pa+n+eci x nnc+pyxnnnx nnapenina xopynn 6a+apen sa nnc+pyxnnnxn no nopxnmnennm n
6esonacnoc+n.
21. Ka6eni Binopa. Hcnonisyn+e +o+ xa6eni pnn nopcoepnnennn xopynn 6a+apen nepes 6nox nn+annn x ppyioxy xopynm 6a+apen.
Bnox nn+annn ne nann+ pa6o+a+i 6es nopcoepnnennn x xopynm sapnxennon 6a+apen. O6pa+n+eci x nnc+pyxnnnx nnapenina
xopynn 6a+apen sa nnc+pyxnnnxn no nopxnmnennm n 6esonacnoc+n.
Tripp Lite npepnaiae+ 3 o+peninie cnc+exi HBH (6nox nn+annn, xopyni 6a+apen, xo+opin +pe6ye+cn pnn ncex annnnxannn, n
xopyni nsonnpymmeio +pancqopxa+opa), ncnonisyexie n pasnix xox6nnannnx. Cnepyn+e nponepype coepnnennn, npnnepennon
nnxe, xo+opan nopxopn+ xox6nnannn xopynen, xo+opie ni nnannpye+e nnc+annpona+i.
lovnnuun Ooepnnennn - 1: Lnok lnunn
(6lB^ nno 10lB^)+ vopyns uupen
Ooepnnne euu vopyns nnunn c oopypoeunnev.
Hcnonisyn o+np+xy, cnnxn+e nepx xopo6xn
A
, noxpinammnn
+epxnnani nxopa ninopa 6noxa nn+annn. Hponepn+e xa6eni
(npepc+annennin nonisona+enex) nepes nenym c+opony +epxnnana
B
n
coepnnn+e eio c +epxnnanox ninopa 6noxa nn+annn. Coepnnn+e ppyion
xonen xa6enn c namnx o6opyponannex.
Ooepnnne nok nnunn c nconnkov snekposneprnn.
Hponepn+e xa6eni nepes npanym c+opony
C
n coepnnn+e eio c
+epxnnanaxn nnopa 6noxa nn+annn. 3axpon+e nepx xopo6xn +epxnnana.
Coepnnn+e ppyiym c+opony xa6enn c nc+onnnxox nex+ponepinn.
Ooepnnne vopyns uupen c vopynvn noku nnunn.
O6pa+n+eci x nnc+pyxnnn nnapenina x namexy xopynm 6a+apen.
Honnoc+im nnepn+e coepnnn+eni xa6enn co c+oponi 6a+apen
D
n
coepnnn+eni na sapnen nanenn 6noxa nn+annn
E
. Bosxoxni ne6onimne
ncxpi +o nopxanino. BHHMAHHE: 6nox nn+annn ne copepxn+
nny+pennen 6a+apen n ne nann+ pa6o+a+i, noxa xopyni 6a+apen ne
nopcoepnnn. Mopynn 6a+apen nonnoc+im sapnxam+cn nepep o+ipysxon.
Opnaxo, pnn +oio, n+o6i nonynn+i nonnym sapnpxy (oco6enno, ecnn
xopyni 6a+apen naxopnncn na pnn+eninox xpanennn) nocne +oio, xax
HBH 6in nopcoepnnn x nc+onnnxy nex+ponepinn, nosnoni+e xopynm
6a+apen sapnpn+icn n +enenne 12 nacon. Kax +onixo HBH noc+ynn+ n
nonisonanne, on sapnpn+ 6a+apen n 6ype+ noppepxnna+i yponeni sapnpa
an+oxa+nnecxn. Hpn neo6xopnxoc+n nopcoepnnn+e pononnn+eninie
xopynn 6a+apen n cnepymmym +ononoinm ce+n xa6eni xaxpoio xopynn
nnopn+cn n coepnnn+eni npepipymeio xopynn
F
.
connection base step 1
connection base step 1
connection base step 1
84
1
2
2
Ooepnnenne

Hpepoc+epexenne no xec+xoxy coepnnennm
3nex+ponponopxa ponxna 6i+i cpenana xnannqnnnponannix nex+pnxox. Bnox nn+annn HBH xoxe+ 6i+i yc+anonnen cax no
ce6e nnn nopcoepnnn x xopynm nsonnpymmeio +pancqopxa+opa. O6e annnnxannn +pe6ym+ nopcoepnnennn 6noxa nn+annn x
xopynm 6a+apen.
Hpn pa6o+e c nex+ponponopxon, nceipa co6nmpan+e npannna no xa6eninix coepnnennnx, npniopnie pnn nameio peinona
(nanpnxep, Hannonaninin 3nex+pnnecxnn Kopexc n CBA). O6nsa+enino yc+anonn+e neixo poc+ynnin nixnmna+eni n namen
nponopxe, pnn +oio n+o6i xoxno 6ino o+xnmnn+i nopany nepexennoio +oxa HBH no npexn noxapon, n.+.p. Y6epn+eci, n+o xa6enn
nopxopn+ x noxpi+nm xa6enn n samnmeni coepnnn+eninixn samnxaxn. 3axpenn+e coepnnennn, ncnonisyn cnny npamennn ne
xenee, nex 2428 pmnxon/qyn+ (2.73.2 nx)
Y6epn+eci, n+o name o6opyponanne sasexneno ponxnix o6pasox.
Hcnonisonanne xa6enen nenepnoio pasxepa xoxe+ nonpepn+i name o6opyponanne n nisna+i onacnoc+i noxapa. Bi6epn+e
coo+ne+c+nymmne xa6enn n coepnnennn pnn nponopxn (coepnnn+enn ponxni 6i+i opnoio pasxepa n +axoio xe +nna, xax n
nponopnnxn nepinn, ncnonisyexie n pannox cnynae).
BBO TOKA BBO TOKA BBO TOKA 3ABHTA BBXOA
200 240 (1B, 2nponopa PE) 200 240V (1B, 2 nponopa PE) 120V (1B, 2 nponopa PE) HEHB
6 KBA xopenn 30A 8 (10 2) 30A 8 (10 2) 2 30A 8 (10 2) 30A
10 KBA xopenn 50A 6 (16 2) 50A 6 (16 2) 2 50A 6 (16 2) 63A
Ooepnnenne vopynen ppyr c ppyrov n c nconnkov snekposneprnn n oopypoeunnev
OOXl^|l1L O1l l|O1lvlll
3
3
A
B
C
D
E
F
1
Bnox nn+annn 6 KBA
lovnnuun coepnnenn -2
Lnok nnunn (6lB^) + vopyns puncopvuopu (6lB^)+ vopyns uupen
Ooepnnne vopyns noku nnunn c vopynev
puncopvuopu.
Hcnonisyn o+np+xy, cnnxn+e nepx xopo6xn
A
, noxpinammnn +epxnnani
nnopa ninopa 6noxa nn+annn. Ypann+e nnn+i c o6onx c+opon +epxnnanon.
Bosixn+e +epxnnani
B
n npopnnni+e nx, noxa ni ne ynnpn+e xonen
coepnnn+enn
C
. Haxxn+e na xonen n no+nnn+e xa6enn, n+o6i
nicno6opn+i nx ns nny+penneio coepnnn+enn
D
. Bini+e +epxnnani.
Bc+ani+e xa6eni coepnnn+enn o+ xopynn +pancqopxa+opa

E
no nny+pennne
coepnnn+enn xopo6xn +epxnnana 6noxa nn+annn, noxa ne ycnimn+e
mennox. 3axenn+e nnn+i noxpyi nnac+nni. Xo+n onn noxa ne
no+pe6ym+cn, coxpann+e +epxnnani 6noxa nn+annn n noxpi+ne xopo6xn,
ecnn ni nnannpye+e ncnonisona+i 6nox nn+annn 6es xopynn
+pancqopxa+opa n 6ypymex.
Ooepnnne vopyns puncopvuopu c euunv
oopypoeunnev.
Hcnonisyn o+np+xy, cnnxn+e nepx xopo6xn
F
, noxpinammnn +epxnnani
nxopa ninopa xopynn +pancqopxa+opa. Hponepn+e xa6eni,
npepoc+annennin nonisona+enex nepes nenym c+opony xopo6xn
G
n
coepnnn+e e c +epxnnanaxn ninopa xopynn +epxnnana. Cxo+pn+e
pnaipaxxy

H
ninopa nanpnxennn nepexennoio +oxa, pnn +oio, n+o6i
onpepenn+i coepnnennn xo+opoio +epxnnana npepoc+ann+ nanpnxenne,
nopxopnmee namen annnnxannn. Coepnnn+e ppyion xonen xa6enn c
namnx o6opyponannex.
Ooepnnne vopyns puncopvuopu c nconnkov
snekposneprnn.
Hponepn+e xa6eni, npepoc+annennin nonisona+enex nepes xopo6xy
I
cnpana n nopcoepnnn+e eio x +epxnnanax nnopa xopynn +pancqopxa+opa.
3axenn+e nepx xopo6xn, saxpinammnn +epxnnani xopynn
+pancqopxa+opa. Hopcoepnnn+e ppyion xonen xa6enn x nc+onnnxy
nex+ponepinn.
connection base step 1
NORMAL
BY PASS
NORMAL
BY PASS
NORMAL
BY PASS
85
1
1
3
Ooepnnenne npopon+enne
2
2
120V
240V
120V
208V
[nurpuvvu Bseopu |unp+enn lepevennoro 1oku
G
3
1
A
B C
D
E
G
I
F
lpopon+enne lovnnuunn Ooepnnenn 2 nu cnepy|uen cpunnue
H
Bsepne nunp+enne eeopu nu vopyne puncopvuopu.
Hcnonisyn o+np+xy, cnnxn+e naneni, noxpinammym nepexnmna+eni
ni6opa nanpnxennn nnopa
J
Yc+anonn+e nepexnmna+eni na noxasanne,
coo+ne+c+nymmee nanpnxennm nnopa n namex noxemennn. 3a+ex,
ncnonisyn nepexnmna+eni nepepnen nanenn 6noxa nn+annn, ni6epn+e
nanpnxenne nnopa na HK pncnnee (cxo+pn+e Konqniypannn nnopa
ninopa nameio HBH n cexnnn n BKJKHHTB/BBKJKHHTB).
BAHHOE HPHMEHAHHE: Ecnn name noxemenne nxee+ nanpnxenne
na nnope 200B, yc+anonn+e nepexnmna+eni xopynn +pancqopxa+opa na
240 B, no cxonqniypnpyn+e 6nox nn+annn na 200B. Ecnn name noxemenne
nxee+ nanpnxenne nnopa 208B nnn 240B, yc+anonxn xopynn
+pancqopxa+opa n xopynn 6noxa nn+annn ponxni connapa+i. 3anopcxne
c+anpap+i pnn o6onx xopynen 208B. Cxo+pn+e cxexy nnxe.
MOYJB TPAHCHOPMATOPA MOYJB BATAPEH
HAHPZHEHHE BBOA HAHPZHEHHE BBOA
BABE HOMEBEHHE HEPEKJKHATEJi 3apnen Hanenn Hepexnmna+eni Hepepnen Hanenn
240 B Hpnxon Tox 240B Hepexennin Tox 240 B Hepexennin Tox
208 B Hpnxon Tox 208B Hepexennin Tox 208 B Hepexennin Tox
208 B Hpnxon Tox 208 Hepexennin Tox 208 B Hepexennin Tox
Ooepnnne vopyns uupen c vopynvn noku nnunn.
O6pa+n+eci x nnc+pyxnnn nnapenina x namexy xopynm 6a+apen.
Honnoc+im nnepn+e coepnnn+eni xa6enn co c+oponi 6a+apen
K
n
coepnnn+eni na sapnen nanenn 6noxa nn+annn

L
. Bosxoxni ne6onimne
ncxpi +o nopxanino. BHHMAHHE: 6nox nn+annn ne copepxn+
nny+pennen 6a+apen n ne nann+ pa6o+a+i, noxa xopyni 6a+apen ne
nopcoepnnn. Mopynn 6a+apen nonnoc+im sapnxam+cn nepep o+ipysxon.
Opnaxo, pnn +oio, n+o6i nonynn+i nonnym sapnpxy (oco6enno, ecnn
xopyni 6a+apen naxopnncn na pnn+eninox xpanennn) nocne +oio, xax
HBH 6in nopcoepnnn x nc+onnnxy nex+ponepinn, nosnoni+e xopynm
6a+apen sapnpn+icn n +enenne 12 nacon. Kax +onixo HBH noc+ynn+ n
nonisonanne, on sapnpn+ 6a+apen n 6ype+ noppepxnna+i yponeni sapnpa
an+oxa+nnecxn. Hpn neo6xopnxoc+n nopcoepnnn+e pononnn+eninie
xopynn 6a+apen n cnepymmym +ononoinm ce+n xa6eni xaxpoio xopynn
nnopn+cn n coepnnn+eni npepipymeio xopynn
M
lovnnuun coepnnenn -3: Lnok lnunn (10lB^) +
Mopyns puncopvuopu (10lB^) + Mopyns Luupen
Ooepnnne vopyns uupen c vopynev puncopvuopu.
Hcnonisyn o+np+xy, cnnxn+e nepx xopo6xn
A
, noxpinammnn +epxnnani
nxopa ninopa 6noxa nn+annn. Cnnxn+e nepx xopo6xn
B
, noxpinammnn
+epxnnani xopynn +pancqopxa+opa. Coepnnn+e +epxnnani nxopa n
nixopa c coo+ne+c+nymmnxn +epxnnanaxn na xopyne +pancqopxa+opa
Hopcoepnnenne Bnoxa Tepxnnana x Bnoxy Hn+annn c npanon c+oponi
xopo6xn
C
NORMAL
BY
PASS
240V AC
208V AC
NORMAL
BY PASS
NORMAL
BY PASS
86
Ooepnnenne npopon+enne
4
5
5
1
1
4
J
M
L
A
B
C
K
lovnnuun coepnnenn - 3 npopon+uec nu cnepy|uen cpunnue
Ooepnnne euu vopyns puncopvuopu c
oopypoeunnev.
Hponepn+e xa6eni, npepoc+annennin nonisona+enex nepes nenym c+opony
xopo6xn
D
n nopcoepnnn+e eio x +epxnnanax ninopa xopynn
+pancqopxa+opa. Cxo+pn+e pnaipaxxy nanpnxennn nixopa nepexennoio
+oxa
E
, pnn +oio, n+o6i onpepenn+i, xo+opie coepnnennn +epxnnana
o6ecnena+ nanpnxenne n coo+ne+c+nnn c namnx npnnoxennex.
Hopcoepnnn+e ppyion xonen xa6enn x namexy o6opyponannm.
lopcoepnnne vopyns puncopvuopu k
nconnky snekposneprnn.
Hponepn+e xa6eni, npepoc+annennin nonisona+enex nepes nen+p
xopo6xn F n nopcoepnnn+e eio x +epxnnanax ninopa xopynn
+pancqopxa+opa. Coepnnn+e ppyiym c+opony xa6enn c nc+onnnxox
nex+ponepinn. 3axenn+e nepx xopo6ox, noxpinammnx +epxnnani
xopynn 6noxa nn+annn n xopynn +pancqopxa+opa.
Bsepne nunp+enne eeopu nu vopyne puncopvuopu.
Hcnonisyn o+np+xy, cnnxn+e naneni, noxpinammym nepexnmna+eni
ni6opa nanpnxennn nnopa

G
Yc+anonn+e nepexnmna+eni na noxasanne,
coo+ne+c+nymmee nanpnxennm nnopa n namex noxemennn. 3a+ex,
ncnonisyn nepexnmna+eni nepepnen nanenn 6noxa nn+annn, ni6epn+e
nanpnxenne nnopa na HK pncnnee (cxo+pn+e Konqniypannn nnopa
ninopa nameio HBH n cexnnn n BKJKHHTB/BBKJKHHTB).
BAHHOE HPHMEHAHHE: Ecnn name noxemenne nxee+ nanpnxenne
na nnope 200B, yc+anonn+e nepexnmna+eni xopynn +pancqopxa+opa na
240 B, no cxonqniypnpyn+e 6nox nn+annn na 200B. Ecnn name noxemenne
nxee+ nanpnxenne nnopa 208B nnn 240B, yc+anonxn xopynn
+pancqopxa+opa n xopynn 6noxa nn+annn ponxni connapa+i. 3anopcxne
c+anpap+i pnn o6onx xopynen 208B. Cxo+pn+e cxexy nnxe.
MOYJB TPAHCHOPMATOPA MOYJB BATAPEH
HAHPZHEHHE BBOA HAHPZHEHHE BBOA
BABE HOMEBEHHE HEPEKJKHATEJi 3apnen Hanenn Hepexnmna+eni Hepepnen Hanenn
240 B Hpnxon Tox 240B Hepexennin Tox 240 B Hepexennin Tox
208 B Hpnxon Tox 208B Hepexennin Tox 208 B Hepexennin Tox
208 B Hpnxon Tox 208 Hepexennin Tox 208 B Hepexennin Tox
Ooepnnne vopyns uupen c vopynvn noku nnunn.
O6pa+n+eci x nnc+pyxnnn nnapenina x namexy xopynm 6a+apen.
Honnoc+im nnepn+e coepnnn+eni xa6enn co c+oponi 6a+apen
H
n
coepnnn+eni na sapnen nanenn 6noxa nn+annn
I
. Bosxoxni ne6onimne
ncxpi +o nopxanino. BHHMAHHE: 6nox nn+annn ne copepxn+
nny+pennen 6a+apen n ne nann+ pa6o+a+i, noxa xopyni 6a+apen ne
nopcoepnnn. Mopynn 6a+apen nonnoc+im sapnxam+cn nepep o+ipysxon.
Opnaxo, pnn +oio, n+o6i nonynn+i nonnym sapnpxy (oco6enno, ecnn
xopyni 6a+apen naxopnncn na pnn+eninox xpanennn) nocne +oio, xax
HBH 6in nopcoepnnn x nc+onnnxy nex+ponepinn, nosnoni+e xopynm
6a+apen sapnpn+icn n +enenne 12 nacon. Hpn neo6xopnxoc+n nopcoepnnn+e
pononnn+eninie xopynn 6a+apen n cnepymmym +ononoinm ce+n xa6eni
xaxpoio xopynn nnopn+cn n coepnnn+eni npepipymeio xopynn
J
NORMAL
BY PASS
NORMAL
BY PASS
NORMAL
BY
PASS
240V AC
208V AC
NORMAL
BY PASS
87
3
3
4
5
5
F
4
G
H
I
J
Ooepnnenne npopon+enne
2
2
D
120V
240V
120V
208V
[nurpuvvu Bseopu |unp+enn lepevennoro 1oku
G
E
88
Cnepymmne coepnnennn nnnnm+cn pononnn+eninixn. Bam HBH 6ype+ npannnino
qynxnnonnpona+i 6es +nx coepnnennn.
Oeas epea vnneepcunsnsn Oepnnnsn lop
(U3B) P3-232
3axpi+in Kon+ax+ Koxxynnxannn Coepnnennn. Hopcoepnnn+e npepoc+annennin
nonisona+enex xa6eni o+ nop+a Cyxon Kon+ax+ x xoxxynnxannonnoxy nop+y
nameio xoxnim+epa nnn ppyioio o6opyponannn.
Oo noaeonn lLl nocsnus ocnoense cnrnuns
konukoe nu aukpsne.
O6pa+n+eci x cnepymmen pnaipaxxe n +a6nnne pnn +oio, n+o6i onpepenn+i
cninani, nepepanaexie +nx nop+ox. Yc+anonn+e na namex xoxnim+epe
npoipaxxnoe o6ecnenenne PowerAlert o+ Tpnnn Jan+ n coo+ne+c+nnn c
onepannonnon cnc+exon nameio xoxnim+epa.3+o+ cepnnnin nop+ DB2 xoxe+
ncnonisona+icn, n+o6i nopcoepnnn+i nam HBH x nac+oninoxy xoxnim+epy. 3+o
nosnonn+ nonnoc+im xon+ponnpona+i ce+i n nam HBH. Yc+anonn+e na namex
xoxnim+epe npoipaxxnoe o6ecnenenne PowerAlert o+ Tpnnn Jan+.
Ooepnnenne lopu ^O
3+a pononnn+eninan qynxnnn +onixo pnn +ex annnnxannn, xo+opie +pe6ym+
nopcoepnnennn x anapnnnoxy o+xnmnennm (AO) nenn noxemennn. Koipa 6nox
nn+annn nopxnmnen x +on nenn, on penae+ nosxoxnix anapnnnoe o+xnmnenne
ninopa. Hcnonisyn npnnaiaexin xa6eni, nopcoepnnn+e AO nop+ xopynn 6noxa
nn+annn x ypannnoxy nixnmna+enm, noc+annennoxy nonisona+enex.
Pacnpepenenne iononox pnn AO noxasano na cnepymmen pnaipaxxe.Bnnxanne:
ecnn xexpy iononxaxn 2 n 3, 2 n 5, 4 n 5, 3 n 4 nponsonp+ saxixanne, HBH
o+xnmnn+ nn+anne.
[ononnnensnoe coepnnenne
0
12 V
>2 sec

5 4 3 2 1 9 8 7 6

NO
COM NC
lm in. > 3.3 mA
BACK-UP
Oll|^I v[^IL|l lO[lIl-L|l O1
B|LL|Ll OlO1LML lO[[Lll^
Oll|^I O1 lOMlLl1Ll^
COM NC
|l3lll vlOBL|L L^1^lLl
NO
M^lOlMvM MO|OO1l OvXOlO lO|1^l1^: lLlLML||Ll 1Ol 20B/3^,
lOO1O||Ll 1Ol 30B/3^
[l^ll^MM^ OvXOl l|1Ll4LlO|Ll lO|1^l1
lLl B [LlO1Bll lOIOBll 8,3 lOIOBll 1,3 lOIOBll6,3
Ouyc
|opvunsnsn O1llL1O O1llL1O *
loppep+ku 3^llL1O * *
Low Battery 3^llL1O 3^llL1O *
|naknn vpoeens
Luupen Oon * * 3^llL1O
* |euknenpoeunnsn: Mo+e ss e n|ov nono+ennn
1^LIl^ OvXOlO l|1Ll4LlO|OlO lO|1^l1^
l^OllL[LIL|lL lOIOBOl ^O
1
2
3
4
5
6
X
12V
X
1K

NORMAL
BY PASS
NORMAL
BY PASS
89
1. Cxonqniypnpyn+e nnop n ninop nameio HBH: nepenepn+e nam 6nox nn+annn HBH n c+a+yc nac+ponxn ny+x opnonpexennoio
naxa+nn xnonox ( A
n
B). Hpocxo+pn+e onnnn nac+ponxn (ncnonisyn
A nnn
B n ni6epn+e coo+ne+c+nymmym nac+ponxy pnn
xaxpon ns cnepymmnx onnnn, ncnonisyn xnonxy BBBOP
B
Bnop n ninop nanpnxennn: ni6epn+e 200, 208 nnn 240B nepexennoio +oxa
Hac+o+a ninopa: Bam HBH ni6epe+ 50 nnn 60 In pnn +oio, n+o6i coo+ne+c+nona+i yponnm nnopa
Pexnx xonoxnn: nam HBH xoxe+ pa6o+a+i n pexnxe onnann c nynenix npexenex nepexopa. On +axxe xoxe+
pa6o+a+i n c+a+yce coxpanennn nepinn.
Jnnennonn+epax+nnnin pexnx: ni6epn+e Bxnmnn+i pexnx xonoxnn pnn +oio, n+o6i nepexnmnn+i HBH n
nnnennonn+epax+nnnin pexnx. Bi6epn+e Bixnmnn+i pexnx xonoxnn pnn +oio, n+o6i nepexnmnn+i HBH n onnannonin
pexnx.
Hocne +oio, xax ni ni6pann +n onnnn, noxnni+e pexnx nac+ponxn npn noxomn xnonxn ni6opa
A, no+ox noxnni+e
pexnx nepexinxn ny+x naxa+nn xnonxn BKJKHHTB
C, noxa ni ne ycnimn+e snyxonon cninan.
2. Bxnmnn+i nnop HBH: Ecnn 6nox nn+annn HBH nopxnmnen x xopynm +pancqopxa+opa, nxnmnn+e nepexnmna+enn nenn
nepexennin +ox x HBH n Binop
D
. Bxnmnn+e nepexnmna+eni nenn nnopa 6noxa nn+annn
E
Haxxn+e xnonxy BKJKHHTB
C
6noxa nn+annn HBH, noxa ni ne ycnimn+e snyxonon cninan, osnanammnn nanano pa6o+i nnnep+epa. Ecnn nnop
nex+pnnecxoio +oxa ne nponopn+ nn+anne o6innix o6pasox, ni xoxe+e nponsnec+n xonopnin c+ap+ nameio HBH o+
6a+apen (nama 6a+apen ponxna 6i+i sapnxena xo+n 6i nac+nnno, pnn +oio n+o6i onepannn 6ina ycnemno nponepena. Haxxn+e
n pepxn+e xnonxy BKJKHHTB
C
,
noxa ni ne ycnimn+e snyxonon cninan, osnanammnn, n+o nam HBH nanan pa6o+a+i n
pexnxe BATAPEZ BKJKHEHA. O6pa+n+e nnnxanne na +o, n+o nexo+opoe nex+ponnoe o6opyponanne xoxe+ no+pe6ona+i
6onime axnep no npexn c+ap+a; n cnynae c+ap+a o+ 6a+apen, nonpo6yn+e yxenimn+i nananinym naipysxy na HBH. Bam HBH
nponsnep+ xpa+xnn caxoc+on+eninin nponeponnin +ec+ n noxaxe+ pesyni+a+i na HK pncnnee
F
. Cxo+pn+e Caxoc+on+eninin
nponeponnin +ec+ c+ap+a n paspene Hpannna Honisonannn
3. Bxnmnn+e ninop HBH: Bxnmnn+e nepexnmna+eni nenn ninop

G
. Ecnn HBH nopxnmnen x xopynm +pancqopxa+opa, nxnmnn+e
nepexnmna+eni Hepenopa na Pa6o+y Bpynnym

H
ns pexnxa HEPEMBHKA n HOPMAJBHBH n nxnmnn+e nepexnmna+eni
nenn nixop. Bam HBH nopac+ nn+anne x nopcoepnnnnoxy o6opyponannm.
4. nn +oio, n+o6i nxnmnn+i 6nox nn+annn n xopyni +pancqopxa+opa HBH: naxxn+e xnonxy BBKJKHHTB I xopynn 6noxa
nn+annn HBH, noxa ne ycnimn+e snyxonon cninan. Hponsonp+ saipysxa. Hnnep+ep o+xnmnn. HK pncnnen
F
noxaxe+
PEHHM HEPEMBHKH. Bixnmnn+e nepexnmna+enn nenn nnopa n ninopa (
E

n
G
) xopynn 6noxa nn+annn HBH. Ecnn nam
HBH nopcoepnnn x xopynm +pancqopxa+opa, nixnmnn+e nepexnmna+enn nepexennin +ox x HBH n nepexnmna+eni ninopa
D
. 3aipysxa nponsonp+ n HK pncnnen ne saiopn+cn
F
.
BlIl-l1L/BLlIl-l1L
Mopenn 6 KBA Mopenn 10 KBA
D
E
G
H
E
G
H
Mopenn 6 KBA n 10 KBA
(Hepepnnn naneni)
D
F
C A B I
NORMAL
BY PASS
NORMAL
BY PASS
90
lpuennu puos epyny| (pn pevonu nnn auvens vopyn noku nnunn).
Cnepymman nponepypa nxee+ o+nomenne +onixo x xonqniypannnx HBH, xo+opie nxnmnam+ xopyni +pancqopxa+opa 6KBA nnn
10 KBA. 3+a nponepypa noppo6no onncinae+ xax o+pexon+npona+i nnn saxenn+i xopyni 6noxa nn+annn, n +o xe npexn noc+annnn
nn+anne x xopynm +pancqopxa+opa. Bnnxanne: nocxonixy xopynn 6noxa nn+annn n 6a+apen 6ypy+ o+xnmneni 6o npexn +on
nponepypi, onn ne 6ypy+ n coc+onnnn noc+annn+i noppepxxy 6a+apen x o6opyponannm, nopxnmnennoxy x xopynm +pancqopxa+opa
n cnynae o+xnmnennn nex+ponepinn.
BHHMAHHE:Tonixo pnn xnannqnnnponannoio o6cnyxnnammeio nepconana. B cnynae nenpannninoio ninonnennn +on
nponepypi, HBH xoxe+ 6i+i ne o+xnmnen nonnoc+im, n pesyni+a+e neio nosnnxae+ pncx cxep+eninoio nc xopa nnn +panxi o+
no+ennnaninoio xon+ax+a c nicoxnx nanpnxennex.
1. O+xnmnn+e npoipaxxnin npopyx+ PowerAlert n o+xnmnn+e xoxxynnxannonnin xa6eni o+ xoxxynnxannonnix nop+on

A

xopynn 6noxa nn+annn.
2. Hoc+ani+e nepexnmna+eni nepexinxn
B
xopynn +pancqopxa+opa n nonoxenne HEPEMBHKA.
3. Haxxn+e xnonxy BBKJKHHTB

C
xopynn 6noxa nn+annn n pepxn+e noxa ne ycnimn+e snyxonon cninan n coo6menne
PEHHM HEPEMBHKH ne nonnn+cn na HK pncnnee

D
4. Bixnmnn+e pnyxnonmcnin nepexnmna+eni nepexennoio +oxa xopynn +pancqopxa+opa na HBH
E
5. Bixnmnn+e pnyxnonmcnin nepexnmna+eni nnopa
F
n pnyxnonmcnin nepexnmna+eni ninopa G xopynn +pancqopxa+opa.
6. O+xnmnn+e xa6eni xopynn 6a+apen o+ coepnnn+enn
H
6a+apen 6noxa nn+annn.
7. TOJBKO JZ 10KBA MOYJEH BJOKA HHTAHHZ: ncnonisyn+e nsxepn+eni nanpnxennn pnn +oio, n+o6i nponepn+i
xa6eni, coepnnnmmnn 6noxn +epxnnana

I
xopynn 6noxa nn+annn c 6noxox +epxnnana

J
xopynn +pancqopxa+opa, n+o6i
y6epn+icn n +ox, n+o 6nox nn+annn o6ec+onen. Ypann+e xa6eni nocne o6ec+onnnannn 6noxa nn+annn.
Mopyni 6noxa nn+annn +enepi o6ec+onen n xoxno nponsnopn+i pexon+/saxeny
Mopenn 6KBA (3apnnn Haneni) Mopenn 10 KBA (3apnnn Haneni)
A
B
F
G
A
B
F
G
I
E
D
C
Mopenn 6KBA n 10 KBA
(Hepepnnn Haneni)
H
E
H
J
91
lLlM [l^l|OO1lll
lLlLML||Ll 1Ol/lOO1O||Ll
1Ol Ol
lLlM [l^l|OO1lll
1LO1llvlll l|BLl1Ll
3^llv3l^ B O|I^l|OBOM
lLlML ``` `.``lw
lpuennu lonsaoeunn
Hocne +oio, xax ni nxnmnnnn HBH, on nxopn+ n Pexnx nainoc+nxn n nponopn+ xpa+xnn +ec+, npoponxammnncn npnxepno 15
cexynp. Pesyni+a+i nponeponnoio +ec+a noxasani na HK pncnnee n cnepymmex nopnpxe.
3^lvOl O BBO[OM
lLlLML||OlO 1Ol^
llLlM [l^l|OO1lll
-^O1O1^ XX l
lLlM [l^l|OO1lll BBO[
lLlLML||OlO 1Ol^ Ol
lLlM [l^l|OO1lll
L^1^lL Ol
lLlM [l^l|OO1lll
3^l[ Ol
lLlM [l^l|OO1lll
lLlLML||Ll 1Ol/lOO1O||Ll
1Ol Ol
lLlM [l^l|OO1lll
1LO1llvlll l|BLl1Ll
3^llv3l^ B O|I^l|OBOM
lLlML ``` `.``lw
lLlM [l^l|OO1lll
-^O1O1^ XX l
lLlM [l^l|OO1lll BBO[
lLlLML||OlO 1Ol^ l^B|OO1L
lLlM [l^l|OO1lll
L^1^lL Ol
lLlM [l^l|OO1lll
3^l[ Ol

3^lvOl O BBO[OM
lLlLML||OlO 1Ol^
XOIO[|Ll
O1^l1*
*Hpnxenanne: Ecnn HBH npnnopn+cn n penc+nne c xonopnoio c+ap+a, CH BATAPEZ saiopn+cn.
Ecnn no npexn nponeponnoio +ec+a saxenena npo6nexa, HK pncnnen noxaxe+ coo6menne o6 omn6xe. Ecnn nam HBH noxasinae+
nm6oe ns cnepymmnx coo6mennn na HK pncnnee, nosnonn+e n +exnnnecxym noppepxxy Tpnnn Jan+ no noxepy (773) 8691234.
|LlOll^B|^
L^1^lL!lO3BO|l1L [I
OLOIvlB^|l
3^l[l^ |L
llOl3OLI^!lO3BO|l1L
[I OLOIvlB^|l
|L1 lO[^-l
lLlLML||OlO/lOO1O||OlO
1Ol^!lO3BO|l1L [I
OLOIvlB^|l
|LlOll^B|Ll
l|BLl1Ll!lO3BO|l1L [I
OLOIvlB^|l
O1Ov1O1BlL BLBO[^!
lO3BO|l1L [I
OLOIvlB^|l
|LlOll^B|Ll
BL|1lI1Ol!lO3BO|l1L
[I OLOIvlB^|l
Ouvocoensnsn lpoeeponsn 1ec Oupu
Ouvocoensnsn npoeeponsn ec ne nponpen.
DIAGNOSTIC MODE
AC/DC OK
DIAGNOSTIC MODE
TESTING INVERTER
ON BATTERY MODE
LOAD = XXX% X.XXKW
DIAGNOSTIC MODE
FREQ OUT = XXHz
DIAGNOSTIC MODE
INPUT AC OK
DIAGNOSTIC MODE
INPUT AC OK
DIAGNOSTIC MODE
BATTERY OK
DIAGNOSTIC MODE
CHARGER OK
DIAGNOSTIC MODE
AC/DC OK
DIAGNOSTIC MODE
TESTING INVERTER
ONLINE MODE
LOAD = XXX% X.XXKW
DIAGNOSTIC MODE
FREQ OUT = XXHz
DIAGNOSTIC MODE
INPUT AC BAD
DIAGNOSTIC MODE
INPUT AC BAD
DIAGNOSTIC MODE
BATTERY OK
BAD BATTERY!
CALL FOR SERVICE
CHARGER FAILURE!
CALL FOR SERVICE
AC/DC FAILURE!
CALL FOR SERVICE
INVERTER FAILURE!
CALL FOR SERVICE
OUTPUT FAILURE!
CALL FOR SERVICE
FAN FAILURE!
CALL FOR SERVICE
92
lpuennu lonsaoeunn, npopon+enne
Bo npexn nopxaninoio ncnonisonannn HBH, nepnan nnnnn nameio HK pncnnen noxasinae+ n xaxox onepannonnox pexnxe
naxopn+cn nam HBH: Onnann, 3xonoxnn, O+ Ba+apen nnn Hepexinxn.
Onnannonin pexnx: HBH o6ecnennnae+ nn+anne nepexennoio +oxa, n +o npexn, xoipa nex+ponepinn nopa+cn n nepexnmnae+cn
nexepnenno (c nynenix npexenex nepexopa) n pexnx O+ Ba+apen, ecnn nn+anne nepexennoio +oxa npexpameno.
Pexnx 3xonoxnn: HBH o6ecnennnae+ nn+anne nepexennoio +oxa c nicoxon qqex+nnnoc+im, xoipa nex+ponepinn nopa+cn
n nepexnmnae+cn 6ic+po na pexnx o+ 6a+apen, xoipa nn+anne nepexennoio +oxa npexpameno..
Pexnx O+ Ba+apen: HBH o6ecnennnae+ nn+anne nepexennoio +oxa o+ noppepxxn 6a+apen, noxa 6a+apen xoxe+ o6ecnennna+i
nn+anne. On nepexnmnae+cn nasap n onnannonin pexnx nnn pexnx xonoxnn, ecnn nex+ponepinn nopa+cn n o+xnmnae+cn,
ecnn nn+anne o+ 6a+apen 6onime ne nopa+cn.
Pexnx Hepexinxn: HBH nopa+ nn+anne nepexennoio +oxa, xoipa nex+ponepinn nopa+cn. HBH o+xnmnae+cn, xoipa nopana
nepexennoio +oxa npexpamena.
B+opan nnnnn HK pncnnen noxasinae+ ocnonnie ycnonnn nn+annn. Haxxn+e xnonxn BBEPX/BHH3, n+o6i npocxo+pe+i +n
6asncnie ycnonnn nn+annn n nocnepona+eninoc+n, npnnepennon nnxe.
XXXX lLlM 3^llv3ll
``` `.``lB^
XXXX lLlM BBO[
```v ``.` lu
XXXX lLlM BLBO[
```v ``.` lu
XXXX lLlM L^1^lLl
``` B loconnoro 1oku

Haxopnci n pexnxe o+ 6a+apen, xopyni 6noxa nn+annn HBH nopac+ snyxonon cninan, yxasinammnn na +o, n+o on ncnonisye+
nn+anne 6a+apen pnn noppepxxn nopcoepnnnnoio o6opyponannn. Ecnn nopcoepnnnnie 6a+apen sapnxeni 6onee, nex
nanononnny, npn6op 6ype+ nopana+i snyxonon cninan pna pasa n cexynpy. Ecnn nopcoepnnnnie 6a+apen sapnxeni xenee, nex
nanononnny, npn6op 6ype+ nopana+i snyxonon cninan pna pasa n cexynpy. Ecnn nopcoepnnnnie 6a+apen non+n ncnepnani, 6nox
nn+annn HBH 6ype+ noc+onnno nspana+i snyxonon cninan.
nn +oio, n+o6i o+xnmnn+i snyxonon cninan o+ 6a+apen, naxxn+e xnonxy BKJKHHTB/ OBE33BYHHTB
Koipa HBH o6napyxn+ nepeipysxy ninopa, HK pncnnen nepexnmnn+cn na cnepymmee coo6menne:
HBH sa+ex nann+ o+cn+. Ecnn HBH nc em nepeipyxen n xonne o+cn+a, HBH an+oxa+nnecxn nepenp+ n Pexnx Hepexinxn,
pnn +oio, n+o6i npepoxpann+i nnnep+ep. Hpoponxenne o+cn+a napinpye+cn n sanncnxoc+n o+ yponnn nepeipysxn cnepymmnx
o6pasox:
lLlLllv3l^! 3^llv3l^
``` `.``lB^
vcnoen neperpyakn lpopon+enne Oceu
102 - 125 1 vnnyu
125 - 150 30 cekynp
150 |evepnenno

|opvunsnoe lonsaoeunne
3eykoeon Onrnun O Luupen
Ooouenn o leperpyake
XXXX MODE
LOAD = XXX% X.XXKW
XXXX MODE
IN = XXXV XX.X Hz
XXXX MODE
OUT = XXXV XX.X Hz
XXXX MODE
BATTERY = XXXVDC
OVERLOAD!
LOAD = XXX% X.XXKW
93
lpuennu lonsaoeunn, npopon+enne
Haxopnci n pexnxe nepexinxn, HBH, xon+ponnpye+ nanpnxenne nnopa n nepenopn+ nn+anne nnopa x nopcoepnnnnoxy
o6opyponannm. HBH ne o6ecnennnae+ noppepxxy 6a+apen n pexnxe Hepexinxn.
Ecnn nanpnxenne ninopa o+xnonne+cn o+ npnexnexoio pnanasona (xexpy 15/ nime n 20/ nnxe noxnnana), HBH pexonc+pnpye+
coc+onnne na cnox HK pncnnee n npexpamae+ nopana+i nn+anne ninopa. Ecnn yponeni nn+annn nosnpamae+cn na npnexnexin
yponeni, HBH noso6nonnne+ nopany nn+annn, n eio HK pncnnen noxasinae+, n+o nanpnxenne ninopa 6ino cnnmxox nicoxnx
nnn cnnmxox nnsxnx, n nepnynoci x noxnnany.
15 esue novnnunu
20 nn+e novnnunu
Lsno cnnukov escoknv,
cenuc novnnunsno
Lsno cnnukov nnaknv,
cenuc novnnunsno
vOIOBl |^llL|l
B lLlML lLlLML-ll
OOOLL|l l
[lOlIL
Bam HBH o+xnmnn+cn n HK noxaxe+ coo6menne, ecnn opno ns cnepymmnx ycnonnn 6ype+ saxeneno. Bnnxanne: no npexn ncex
+nx ycnonnn, CH Bnop, Binop n Hepexinxa 6ypy+ iope+i.
lpopon+nensnu
neperpyaku
Bseop auvskunn uenn
lovunpu ypunennoro
okn|enn (epea DB9)
lovunpu ypunennoro
okn|enn (epea LPO)
vOIOBl
O1lIl-L|l
OOOLL|l |^
l [lOlILL
Bnypennne con
|L1 BLBO[^ lLlLML-l^
lLlLML||OlO 1Ol^
OIlLlOM BLOOl^
|L1 BLBO[^ lLlLML-l^
lLlLML||OlO 1Ol^
OIlLlOM |l3l^
lLlM lLlLML-ll
lLlLML||Ll 1Ol LLI
OIlLlOM BLOOl
lLlM lLlLML-ll
lLlLML||Ll 1Ol LLI
OIlLlOM |l3Ol
O1lIl-l1L
lLlLllv3l^ ```
O1lIl-l1L
3^MLl^|lL
O1lIl-l1L
v[^IL||^ lOM^|[^
O1lIl-l1L ^B^lll|^
OO1^|OBl^!
O1lIl-l1L
+lOO1O||Ll 1Ol BLOOl
O1lIl-l1L
+lOO1O||Ll 1Ol |l3Ol
O1lIl-l1L -lOO1O||Ll
1Ol BLOOl
O1lIl-l1L -lOO1O||Ll
1Ol |l3Ol
O1lIl-l1L
lLlLllLB
Ooouenne o le+nve lepevskn
Ooouenn no okn|enn|
NO OUTPUT
BYPASS AC TOO HI
NO OUTPUT
BYPASS AC TOO LO
BYPASS MODE
BYPASS AC WAS HI
BYPASS MODE
BYPASS AC WAS LO
SHUT DOWN
OVERLOAD XXX%
SHUT DOWN
O/P SHORT CIRCUIT
SHUT DOWN
REMOTE COMMAND
SHUT DOWN
EMERGENCY STOP!
SHUT DOWN
+ DC BUS HIGH
SHUT DOWN
+ DC BUS LOW
SHUT DOWN
- DC BUS HIGH
SHUT DOWN
- DC BUS LOW
SHUT DOWN
OVERTEMPERATURE
94
Oepenc/lupunn
Bam SmartOnline HBH nxee+ oipannnennym iapan+nm na 2 iopa, xax onncano nnxe. Tripp LIte +axxe npepnaiae+ pasnnnnie
cepnncnie xon+pax+i, nxnmnan cepnncnie xon+pax+i na xoxen+ npno6pe+ennn n 3x n 5+n ne+nne SafeSure xon+pax+i na xec+e
pacnonoxennn HBH. nn nonynennn paninenmen nnqopxannn, nosnonn+e n cnyx6y noppepxxn xnnen+on Tpnnn Jan+ no noxepy
(773) 8691234.
Tripp Lite iapan+npye+, n+o npopyx+i Tripp Lite ne nxem+ peqex+on xa+epnanon nnn c6opxn. Iapan+nn pacnpoc+panne+cn na 2 iopa c xoxen+a noxynxn. Hepes 90 pnen c xoxen+a
noxynxn, Tripp Lite o6nsye+cn, n coo+ne+c+nnn c oipannnennon iapan+nen, +onixo saxenn+i pe+ann na npopyx+ax c peqex+axn. nn +oio, n+o6i nonynn+i o6cnyxnnanne na
iapan+nn, ni ponxni nosnonn+i n Tripp Lite nnn canxnnonnponannin nen+p o6cnyxnnannn Tripp Lite. Hpopyx+i ponxni 6i+i nosnpameni Tripp Lite nnn canxnnonnponannin
nen+p o6cnyxnnannn Tripp Lite, +pancnop+nie pacxopi ponxni 6i+i npeponnaneni, npnnoxn+e xpa+xoe onncanne npo6nexi n nop+nepxpenne pa+i n xec+a noxynxn. 3+a
iapan+nn ne pacnpoc+panne+cn na o6opyponanne, xo+opoe 6ino nonpexpeno n cnynae nenpannninoio nnn ne6pexnoio ncnonisonannn nnn necnac+noio cnynan, a +axxe ecnn npn6op
6in nsxenn nm6ix o6pasox. 3+a iapan+nn noxpinae+ +onixo opninnaninoio nnapenina, xo+opin ponxen sapeinc+pnpona+i npopyx+ ponxnix o6pasox n +enenne 10 pnen c
xoxen+a noxynxn.
Iapan+nn na nm6ie npepoxpann+enn pnn nopannennn nanpnxennn o+ Tripp Lite anynnpye+cn, ecnn onn 6inn nopxnmneni x ninopy nm6on cnc+exi HBH. Iapan+nn na nm6ie
HBH cnc+exi Tripp Lite anynnpye+cn, ecnn npepoxpann+eni pnn nopannennn nanpnxennn 6in nopxnmnen x nanenixe ninopa.
HOMHMO YKA3AHHOIO BBBE, TRIPP LITE HE AT IAPAHTHH, HPZMO HJH KOCBEHHO, BKJKHAZ IAPAHTHH JZ COOTBETCTBHZ OHPEEJHHOH HEJH
HOKYHKH. Hexo+opie m+a+i ne nosnonnm+ oipannnnna+i nnn ncxnmna+i xocnennie iapan+nn; cnepona+enino, npnnepennie nime ncxnmnennn, xoiy+ ne o+nocn+icn x
noxyna+enm.
KPOME KAK YKA3AHO BBBE, TRIPP LITE, HH B KOEM CJYHAE HE OTBETCTBEHEH 3A HPZMBE, KOCBEHHBE, CHEHHAJH3HPOBAHHBE, CJYHAHHBE, HJH
JOIHHECKH BBTEKAKBHE HOBPEHEHHZ, ZBJZKBHECZ PE3YJBTATOM HCHOJB3OBAHHZ 3TOIO HPOYKTA, AHE B CJYHAE, ECJH BO3MOHHOCTB
TAKHX HOBPEHEHHH BYET YKA3AHA.
Bonee xonxpe+no, TRIPP LITE ne nec+ o+ne+c+nennoc+n sa nspepxxn, +axne xax: no+epnnnan npn6ini o+ ioponoio poxopa, no+epn o6opyponannn, no+epn o+ ncnonisonannn
o6opyponannn, no+epn npoipaxxnoio o6ecnenennn, no+epn nnqopxannn, c+onxoc+i saxeni, npe+ensnn +pe+inx c+opon, n.+.n.
Honn+nxa Tripp Lite coc+on+ n noc+onnnox conepmenc+nonannn. Cnennqnxannn xoiy+ 6i+i nsxeneni n nm6oe npexn 6es npepynpexpennn.
Hpen+nqnxannonnie noxepa, cnnpe+enic+nymmne o coo+ne+c+nnn nopxa+nnnix +pe6onannnx
C nenim npen+nqnxannn, a +axxe cep+nqnxannn coo+ne+c+nnn nopxa+nnnix +pe6onannnx, npno6pe+ennoxy Baxn nspennm xoxnannn Tripp Lite npncnoen ynnxaninin cepnnnin
noxep. Cepnnnin noxep, nxec+e co ncen neo6xopnxon nnqopxannen n xapxnponxaxn o6 opo6pennn, yxasan na npnixe nsio+onn+enn, npnxpennennox x nspennm . Hpn sanpoce
nnqopxannn o coo+ne+c+nnn nopxa+nnnix +pe6onannnx nceipa coo6man+e cepnnnin noxep nspennn. He cnepye+ ny+a+i cepnnnin noxep c xapxon nnn noxepox xopenn
nspennn.
Hspenne cnpoex+nponano n nsio+onneno n CBA.
lpennnkuunonnse novepu, cenpeenscey|une o cooeecenn nopvunensv peoeunnv
O uens| npennnkuunn, u uk+e cepnnkuunn cooeecen nopvunensv peoeunnv, npnopeennovy Buvn napenn| kovnunnn 1r|pp L|te npnceoen ynnkunsnsn cepnnnsn novep. Oepnnnsn novep, evece
co ecen neoxopnvon nnopvuunen n vupknpoekuvn o opopennn, ykuaun nu pnske narooenen, npnkpennennov k napenn| . lpn aunpoce nnopvuunn o cooeecenn nopvunensv peoeunnv ecerpu
coouune cepnnnsn novep napenn. |e cnepye nyus cepnnnsn novep c vupkon nnn novepov vopenn napenn.
Oepenc
Orpunnennu 2x nen rupunn
95
Oneunnkuunn
Hepenncnennie nnxe xopenn copepxa+: 6nox nn+annn, opnn nnn pna 6a+apennix xopynn n +pancqopxa+opnin xopyni. B sanncnxoc+n o+
saxasannon xopenn, npepoc+annnexin n xoxnnex+e c nen 6a+apennin xopyni xoxe+ 6i+i xax ynnnepcaninix (pacmnpnexix, +.e.
noppepxnnammnx nosxoxnoc+i nopxnmnennn pononnn+eninix 6a+apen), +ax n nepacmnpnexix. Hpn neo6xopnxoc+n o6ecnenn+i ypnnnennym
xnsni 6a+apen, naxno nxe+i nnnpy, n+o nce cnnonie xopynn nonnoc+im conxec+nxi c pacmnpnexixn 6a+apennixn xopynnxn Tripp Lite
(Tripp Lite xopeni # BP240V10RT3U, npopae+cn o+penino).
lnopvuun o vopenn 3U6000P13UHv n 3U6000P13U 3U6000P13U`P 3U10lP13UHv n 3U10lP13U
Mopens -
B kovnnek exopn:
Lnok nnunn (vopens: 3U6000P13UPV, (vopens: 3U6000P13UPV, (vopens: 3U10lP13UPV,
cepn ^O3U60003U) cepn ^O3U60003U) cepn ^O3U100003U)
Luupennsn vopyns -1 (vopens: BP240v7P13U, (vopens: BP240v7P13U, (vopens: BP240v10P1-3U,
cepn ^OBP240v7P13U) cepn ^OBP240v7P13U) cepn ^OBP240v7P13U)
nepucunpevsn ocyceye nepucunpevsn pucunpevsn ocyceye
Luupennsn vopyns -2 N/^ (vopens: BP240v10P1-3U, N/^
cepn ^OBP240v7P13U)
pucunpevsn
1puncopvuopnsn vopyns (vopens: 3U6000`lVPP13U, (vopens: 3U6000`lVPP13U, (vopens: 3U10l`lVPP13U,
cepn: ^O3V60003DP13U) cepn: ^O3V60003DP13U) cepn: ^O3V10l3DP13U)
Bce uupennse vopynn, au nckn|ennev BP240v5P12U (UL, cUL, NOV). Bce puncopvuopnse vopenn (UL, cUL, NOV, lOO lnucc ^).
Bseop
B^ 6000 6000 10000
Bu (4ukop lnunn: 0.7) 4200 4200 7000
4opvu Bonns (Onnunn) Onnyconpu Onnyconpu Onnyconpu
4opvu Bonns (O Luupen) Onnyconpu Onnyconpu Onnyconpu
|unp+enne Bseopu (PV3) 100/120/200/208/240v 100/120/200/208/240v 100/120/200/208/240v
-ucou Bseopu 50/60 Hz ( 0.2 lu O Luupen) 50/60 Hz ( 0.2 lu O Luupen) 50/60 Hz ( 0.2 lu O Luupen)
lerynnpoeunne |unp+enn 3 3 3
Mukc. lupvonnnoe Oknonenne
(Innennu lonnu |urpyaku) 3 3 3
(|ennnennu lonnu |urpyaku) 6 6 6
Boavo+nocs leperpyakn 102 (npopon+nensnocs) 102 (npopon+nensnocs) 102 (npopon+nensnocs)
102125 (1 vnn.) 102125 (1 vnn.) 102125 (1 vnn.)
125150 (30 cek.) 125150 (30 cek.) 125150 (30 cek.)
150 (|evepnenno) 150 (|evepnenno) 150 (|evepnenno)
Boavo+nocs lopokon enn 90^* 90^* 160^*
lepekn|uens enn Mopyn Lnoku lnunn 40^ 40^ 63^
lepekn|uens enn Mopyn 1puncopvuopu 30^ (3 non|cu) 30^ (3 non|cu) 63^ (3 non|cu)
4ukop lnku 3:1 3:1 3:1
* Boavo+nocs kopokon uenn nu nnakov ypoene 2 Bu 120 B pn 3U6000P13U n 3U6000P13U`P onee, ev 180 ^, n
lcnonsaoeunne
Bpev nepexopu onnunn (Innn k Luupee, Luupe k Innnn )
0 vc 0 vc 0 vc
luannnvsn Lyv (lonnu 3urpyaku1v) 50 dB^ 55 dB^ 55 dB^
1nnnnoe Bpev loppep+kn (c nopcoepnnennsv vopynev uupen)
(lonnu 3urpyaku) 15 vnn. + 37 vnn. + 8 vnn. +
(3urpyaku |unonoenny) 37 vnn. + 79 vnn. + 20 vnn. +
lnpnkuops
Bkn|ue l [ncnnen n Ol[ (eeop), L^1^lL, lLlLML||Ll/lOO1O||Ll 1Ol, lLlLML-l^ lOO1O||Ll/lLlL ML||Ll 1Ol, (eseop).
lovvynnkuunn
Bkn|ue P3-232 DB9 coepnnnens, cyxon konuk DB9 coepnnnens n oeepcne pn ukceccyupoe.
4naneckne Oneunnkuunn
luaveps lpnopu (B x L x [)
Lnok lnunn 5.25 (3U) x 17.5 x 22.5 pv. 5.25 (3U) x 17.5 x 22.5 pv. 5.25 (3U) x 17.5 x 22.5 pv.
13.4 x 44.5 x 57.2 cm.] 13.4 x 44.5 x 57.2 cm.] 13.4 x 44.5 x 57.2 cm.]
Mopyns 1puncopvuopu 5.25 (3U) x 17.5 x 26 pv. 5.25 (3U) x 17.5 x 26 pv. 5.25 (3U) x 17.5 x 26 pv.
13.4 x 44.5 x 66.1 cm.] 13.4 x 44.5 x 66.1 cm.] 13.4 x 44.5 x 66.1 cm.]
Mopyns Luupen -1 5.25 (3U) x 17.5 x 22.5 pv. 5.25 (3U) x 17.5 x 22.5 pv. 5.25 (3U) x 17.5 x 22.5 pv.
13.4 x 44.5 x 57.2 cm.] 13.4 x 44.5 x 57.2 cm.] 13.4 x 44.5 x 57.2 cm.]
Mopyns Luupen -2 (ecnn cyueceye) -/- 5.25 (3U) x 17.5 x 22.5 pv. -/-
13.4 x 44.5 x 57.2 cm.]
Bec Orpyakn
Lnok lnunn 58 ynoe 58 ynoe 68 ynoe
27 kr.] 27 kr.] 31 kr.]
Mopyns 1puncopvuopu 124 ynoe 124 ynoe 124 ynoe
57 kr.] 57 kr.] 57 kr.]
Mopyns Luupen -1 160 ynoe 160 ynoe 160 |ynoe
73 kr.] 73 kr.] 73 kr.]
Mopyns Luupen -2 (ecnn cyueceye) -/- 160 ynoe -/-
73 kr.]
+Bpev noppep+kn vo+e ss yeenneno npn novoun pononnnensnsx Mopynen Luupen
(vopens:BP240v10P1-3U) npopuec opensno.
1111 W. 35th Street, Chicago, IL 60609 USA
773.869.1234 (USA) 773.869.1212 (International)
www.tripplite.com
200907004 932407-RU

You might also like