Broadcrown 50Hz Diesel Generators Technical Data

Product Reference Specifications PERKINS RANGE 650kVA to 2500kVA Generator Sets


Genset Model #

Prime Rating (PRP) or


Standby (ESP)

Rating at
400/230V

Alternator
Model

Engine Specifications
Fuel Cons
100% Load
(l/h)
132

Open Set Version


Dimensions
Length x Width x Height
(mm)
3850 1540 2020

Weight
(wet)
(kg)
5850

Fuel Tank
Capacity
(litres)
720

BCP 650P-50

PRP

650

520

2806A-E18TAG2 (FO)

6 inline

Cubic
Capacity
(litres)
18.13

BCP 700S-50

ESP

700

560

2806A-E18TAG2 (FO)

6 inline

18.13

143

HCI 534 F

3850 1540 2020

5850

720

BCP 750P-50

PRP

750

600

4006-23TAG2A (FO)

6 inline

22.92

157

HCI 634 G

4400 1832 2166

6754

720
720

kVA

kWe

Engine
Model

Cylinder
Arrangement

HCI 534 F

BCP 800S-50

ESP

800

640

4006-23TAG2A (FO)

6 inline

22.92

173

HCI 634 G

4400 1832 2166

6754

BCP 800P-50

PRP

800

640

4006-23TAG3A (FO)

6 inline

22.92

172

HCI 634 G

4400 1832 2166

6754

720

BCP 850S-50

ESP

850

680

4006-23TAG3A (FO)

6 inline

22.92

194

HCI 634 G

4400 1832 2166

6754

720

BCP 900P-50

PRP

900

720

4008-TAG1A (FO)

8 inline

30.6

194

HCI 634 H

4920 1930 2330

8230

BCP 1000S-50

ESP

1000

800

4008-TAG1A (FO)

8 inline

30.6

217

HCI 634 H

4920 1930 2330

8230

BCP 1000P-50

PRP

1000

800

4008-TAG2A (FO)

8 inline

30.6

220

HCI 634 J

4920 1930 2330

8230

BCP 1100S-50

ESP

1100

880

4008-TAG2A (FO)

8 inline

30.6

248

HCI 634 J

4920 1930 2330

8230

BCP 1250P-50

PRP

1250

1000

4012-46TWG2A (FO)

12 Vee

45.48

258

PI 734 A

4790 1810 2550

9590

BCP 1380S-50

ESP

1380

1104

4012-46TWG2A (FO)

12 Vee

45.48

287

PI 734 B

4790 1810 2550

9590

BCP 1350P-50

PRP

1350

1080

4012-46TAG1A (FO)

12 Vee

45.84

224

PI 734 B

5490 1810 2540

9995

BCP 1480S-50

ESP

1480

1184

4012-46TAG1A (FO)

12 Vee

45.84

308

PI 734 B

5490 1810 2540

9995

BCP 1500P-50

PRP

1500

1200

4012-46TAG2A (FO)

12 Vee

45.84

301

PI 734 C

5490 1810 2540

9995

BCP 1650S-50

ESP

1650

1320

4012-46TAG2A (FO)

12 Vee

45.84

335

PI 734 C

5490 1810 2540

9995

BCP 1725P-50

PRP

1725

1380

4012-46TAG3A (FO)

12 Vee

45.84

370

PI 734 E

5490 1810 2540

10535

BCP 1890S-50

ESP

1890

1512

4012-46TAG3A (FO)

12 Vee

45.84

405

PI 734 E

5490 1810 2540

10535

BCP 1850P-50

PRP

1850

1480

4016-TAG1A (FO)

16 Vee

61.12

383

PI 734 E

6000 2290 2890

13210

BCP 2000S-50

ESP

2000

1600

4016-TAG1A (FO)

16 Vee

61.12

424

PI 734 E

6000 2290 2890

13210

BCP 2050P-50

PRP

2050

1640

4016-TAG2A (FO)

16 Vee

61.12

434

PI 734 F

6000 2290 2890

16577

BCP 2250S-50

ESP

2250

1800

4016-TAG2A (FO)

16 Vee

61.12

483

PI 734 F

6000 2290 2890

16577

BCP 2250P-50

PRP

2250

1800

4016-61TRG3A (FO)

16 Vee

61.12

473

LVSI 804 R2

6400 x 2320 x 2965

14900

BCP 2500S-50

ESP

2500

2000

4016-61TRG3A (FO)

16 Vee

61.12

528

LVSI 804 R2

6400 x 2320 x 2965

14900

Product Reference Specifications JOHN DEERE RANGE 14.5kVA to 330kVA Generator Sets
Genset Model #

Prime Rating (PRP)

Standby Rating (ESP)

Alternator
Model

Engine Specifications
Fuel Cons
100% Load
(l/h)
5.7

PI 144 D

Open Set Version


Dimensions
Length x Width x Height
(mm)
1630 650 1370

Weight
(wet)
(kg)
820

Fuel Tank
Capacity
(litres)
95

kVA

kWe

kVA

kWe

BCJD 22-50

20

16

22

17.6

3029 DF128

3 inline

Cubic
Capacity
(litres)
2.9

BCJD 30-50

28

22

30

24

3029 DF128

3 inline

2.9

4.6

PI 144 F

1630 650 1370

820

95

BCJD 42-50 E2

38

30

42

34

3029 HFU70

3 inline

2.9

10.1

PI 144 J

2080 670 1370

1235

150

BCJD 44-50

40

32

44

35

3029 TF158

3 inline

2.9

9.7

PI 144 J

2080 670 1370

880

155

BCJD 64-50 E2

60

48

64

51.2

4045 TFU70

4 inline

4.5

14.8

UCI 224 E

2300 850 1550

1250

225

BCJD 65-50

60

48

65

52

4045 TF158

4 inline

4.5

15.9

UCI 224 E

2080 670 1450

1272

150

BCJD 88-50 E2

80

64

88

70.4

4045 HFU72

4 inline

4.5

19.8

UCI 224 G

2300 850 1620

1350

225

BCJD 90-50

80

64

90

72

4045 TF258

4 inline

4.5

22.9

UCI 224 G

2300 850 1570

1280

230

BCJD 110-50

100

80

110

88

4045 HF158

4 inline

4.5

27.5

UCI 274 C

2300 850 1620

2330

225

BCJD 110-50 E2

100

80

110

88

4045 HFU79

4 inline

4.5

23.8

UCI 274 C

2300 850 1570

2200

225

BCJD 130-50

120

96

130

104

6068 TF258

6 inline

6.8

26.6

UCI 274 E

2700 800 1580

1675

275

BCJD 150-50

140

112

150

120

6068 HF158

6 inline

6.8

31.5

UCI 274 E

2700 800 1650

1770

275

BCJD 150-50 E2

140

112

150

120

6068 HFU79

6 inline

6.8

31.2

UCI 274 E

2700 800 1580

1850

260

BCJD 165-50

150

120

165

132

6068 HF158

6 inline

6.8

33.8

UCI 274 F

2700 800 1650

1770

275

BCJD 165-50 E2

150

120

165

132

6068 HFU79

6 inline

6.8

32.8

UCI 274 F

2700 800 1580

1850

260

BCJD 200-50

180

144

200

160

6068 HF258

6 inline

6.8

40.7

UCI 274 H

2700 800 1650

1770

275

BCJD 220-50 E2

200

160

220

176

6068 HFU74

6 inline

6.8

40.1

UCI 274 H

3050 1030 1790

2140

380

BCJD 275-50 E2

250

200

275

220

6090 HF475

6 inline

53.8

UCDI 274 K

3420 1140 2080

3125

710

BCJD 330-50 E2

300

240

330

264

6090 HF475

6 inline

64.1

HCI 444 D

3420 1140 2080

3345

710

Engine
Model

Cylinder
Arrangement

Product Reference Specifications VOLVO RANGE 3 PHASE 275kVA TO 700kVA Generator Sets
Genset Model #

BCV 275-50 E2
BCV 300-50 E2
BCV 360-50 E2
BCV 385-50 E2
BCV 415-50 E2
BCV 440-50 E2
BCV 500-50 E2
BCV 550-50 E2
BCV 660-50
BCV 700-50

Prime Rating (PRP)

Standby Rating (ESP)

Alternator
Model

Engine Specifications

kVA

kWe

kVA

kWe

Engine
Model

250
275
325
350
375
400
450
500
600
635

200
220
260
280
300
320
360
400
480
508

275
300
360
385
415
440*
500
550
660
700

220
240
288
308
332
352
400
440
528
560

TAD734GE
TAD940GE
TAD941GE
TAD1342GE
TAD1343GE
TAD1344GE
TAD1345GE
TAD1641GE
TAD1642GE
TWD1643GE

Cylinder
Arrangement
6 inline
6 inline
6 inline
6 inline
6 inline
6 inline
6 inline
6 inline
6 inline
6 inline

Cubic
Capacity
(litres)
7.15
9.36
9.36
12.78
12.78
12.78
12.78
16.12
16.12
16.12

Fuel Cons
100% Load
(l/h)
53.8
59.4
69.6
70.1
75.4
82.8
91.5
102.9
119.3
129

UCDI 274 K
HCI 444 D
HCI 444 E
HCI 444 E
HCI 444 F
HCI 444 F
HCI 544 C
HCI 544 D
HCI 544 E
HCI 544 F

Open Set Version


Dimensions
Length x Width x Height
(mm)
3050 1030 1590
3420 1140 1920
3420 1140 1920
3420 1140 2030
3420 1140 2030
3420 1140 2030
3710 1187 2030
3710 1187 2270
3710 1187 2270
3870 1490 2110

Weight
(wet)
(kg)
2280
3855
3940
4300
4440
4460
4915
5250
5400
5500

*425kVA At 380V
RATING DEFINITIONS
Prime Power (PRP)
These ratings are suitable for continuous operation in a variable load application in lieu of the
main power network. There is no limitation to the annual hours of operation. A 10% overload is
available for 1 hour in every 12 hours of operation.
Standby Power (ESP)
These ratings are suitable for the supply of emergency power in a variable load application in the
event of a main power network failure for a limited number of hours per year.
No overload is available. All 3 phase ratings at 0.8 Power Factor.

Tel : +44 1 889 272200


Broadcrown Ltd (Group Headquarters)
Fax : +44 1 889 272220
Airfield Industrial Estate
Hixon
Stafford
Staffs ST18 0PF
Email : info@broadcrown.co.uk

Standby Reference Conditions


Output ratings are based on gensets operating at: 25C (77F) air inlet temperature,
100kPa barometric pressure [110m (361ft) altitude] and 30% relative humidity.
For de-rating, please contact Broadcrown Sales Department.
Notes
All data in accordance with ISO3046, DIN6271, ISO8528 standards. Other voltages
available, please refer to Data Sheet or consult Broadcrown Sales Department.
Specifications and design subject to change without notice.
For updates refer to our website, www.broadcrown.com

Fuel Tank
Capacity
(litres)
394
711
711