Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

AGMU-Geotechnical Pile Design Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

Design Guide

AGMU Memo 10.2 Geotechnical Pile Design

Axial Geotechnical Resistance Design of Driven Piles


This Design Guide has been developed to provide geotechnical and structural engineers with the
most recent methods and procedures required by the department to determine the nominal and
factored axial geotechnical resistance of a pile to help ensure cost effective foundation design and
construction.
The Geotechnical Engineer must evaluate the subsurface soil/rock profile, develop pile design
table(s) for each substructure, and provide them to the structure designer in the Structure
Geotechnical Report (SGR). Each table shall contain a series of Nominal Required Bearing (R N)
values, the corresponding Factored Resistances Available (RF) for design, and the Estimated Pile
Lengths, for all feasible pile types. The number of pile types and sizes covered as well as the range
of RN values provided must be large enough to allow the designer sufficient selection to determine
the most economical pile type, size and layout such that the factored loading from the LRFD
Strength Limit State and Extreme Event Load Combinations is < RF.

The corresponding RN

provided on the plans will be obtained during driving as indicated by dynamic formula or other
nominal pile resistance field verification method.

To develop the pile design tables, the

geotechnical engineer shall use the IDOT static method of estimating this nominal pile resistance
during driving and provide these values in the SGR as feasible RN values which can be specified by
the designer.
The original IDOT static method was developed over 40 years ago to correspond to the allowable
pile resistance indicated during driving by the ENR dynamic formula. With the change to LRFD and
FHWA Gates formula in 2007, the department completed an extensive research study with Dr.
James Long of the University of Illinois at Urbana-Champaign to evaluate several static methods
and dynamic formulas to determine the most accurate method for estimating pile lengths and
resistances for the soils, piles, and hammers common to our State. The results indicated that the
IDOT static method (with the new Pile Type Correction Factors) was more accurate than all other
static estimating methods studied, including the program DRIVEN.

It was also found to

correspond closest to the most accurate dynamic formula studied which was the WSDOT formula,
developed by Tony Allen of the Washington State DOT in 2005.

Based on this research, the

WSDOT formula will replace the FHWA Gates formula as the standard method of construction
verification and the IDOT static method, described below, shall be used to develop the SGR pile
design tables.

Oct 2011

Page 1

Design Guide

AGMU Memo 10.2 Geotechnical Pile Design

Nominal Required Bearing (RN) represents the nominal pile resistance expected at any specific
length during driving that can be specified by the Designer.

It must be calculated at various

estimated lengths and is the first step in developing the pile design table.
In the case of displacement piles (such as metal shell, precast, and timber piles), RN shall be
calculated as the sum of the side and tip resistance as follows:
RN = (FSqSASA + FPqPAP)*(lG)
Where the nominal side resistance (FSqSASA) is the product of the following:
FS = The pile type correction factor for side resistance (0.758 for displacement piles
in cohesionless soils & 1.174 for displacement piles in cohesive soils)
qS = The nominal unit side resistance
ASA = The surface area of the pile
And the nominal tip resistance (FPqPAP) is the product of the following:
FP = The pile type correction factor for tip resistance (0.758 for displacement piles in
cohesionless soils & 1.174 for displacement piles in cohesive soils)
qP = The nominal unit tip resistance
AP = The tip area of the pile
In the case of non-displacement piles (such as steel H piles), the RN shall be taken as the lesser of
the following:
The fully plugged side and tip resistance defined as:
RN = (FSqSASAp + FPqPAPp)*(lG)
And the fully unplugged side and tip resistance defined as:
RN = (FSqSASAu + FPqPAPu)*(lG)
Where:
FS = The pile type correction factor for side resistance (0.15 for non-displacement
piles in cohesionless soils, 0.75 for non-displacement piles in cohesive soils &
1.0 for non-displacement piles in rock)

Oct 2011

Page 2

AGMU Memo 10.2 Geotechnical Pile Design

Design Guide
FP

= The pile type correction factor for tip resistance (0.3 for non-displacement
piles in cohesionless soils, 1.5 for non-displacement piles in cohesive soils &
1.0 for non-displacement piles in rock)

ASAu = The unplugged surface area = (4 x flange width + 2 x member depth ) x pile
length
ASAp = The plugged surface area = (2 x flange width + 2 x member depth ) x pile
length
APu = The cross-sectional area of steel member
APp = The flange width x member depth
In the above equations, the term lG is the bias factor ratio (equal to 1.04) and is discussed in further
detail later in the design guide. The Nominal Unit Side Resistance (qS) and Nominal Unit Tip
Resistance (qP) shall be calculated as follows:
Nominal Unit Side Resistance (qS) of granular soils is computed using the equations below:
For Hard Till, the equations below are used for the range of N values indicated:
q s 0.07N
for N < 30

qs

0.00136 N 2

0.00888 N 1.13

for N > 30

Very Fine Silty Sand, the equations below are used for the range of N values indicated:
for N < 30
q s 0.1N

qs
qs

N 175.05
7944

42.58e
0.297N 10.2

for 30 < N < 74


for N > 74

Fine Sand, the equations below are used for the range of N values indicated:
for N < 30
q s 0.11N

qs

qs

182
12.51
N
0.329N 9.91
0.3256 N

for 30 < N < 66


for N > 66

Medium Sand, the equations below are used for the range of N values indicated:
for N < 26
q s 0.117N

qs

0.00404 N 2

qs

0.356N 9.1

0.0697 N

2.13

for 26 < N < 55


for N > 55

Clean Coarse Sand, the equations below are used for the range of N values indicated:
for N < 24
q s 0.128N

qs

Oct 2011

0.00468 N 2

0.0693 N

2.05

for 24 < N < 50

Page 3

AGMU Memo 10.2 Geotechnical Pile Design

Design Guide
qs

0.394N 9.42

for N > 50

Sandy Gravel, the equations below are used for the range of N values indicated:
for N < 20
q s 0.15N

qs

0.00861 N 2

qs

0.6N 15.0

0.217 N

3.91

for 20 < N < 40


for N > 40

Nominal Unit Side Resistance (qS) of cohesive soils, shall be calculated using the equations
below for the range of QU values indicated:

qs

1
Q u3
2500
0.0495Qu3

qs

0.470Qu

qs

2.67 ksf

qs

0.177Q u2

1.09Q u

0.347Qu2 1.278Qu 0.068


0.555

for Qu

1.5 tsf

for 1.5 tsf

Qu

for 2 tsf

Qu
for 4.5 tsf Qu

2 tsf
4.5 tsf

Where QU = Unconfined compression strength of the soil in tsf.


Note that QU is input in tsf and qS is output in ksf.
If QU > 3 tsf and N > 30, treat as granular and use Hard Till equations.
Nominal Unit Side Resistance (qS) of rock, shall be calculated using the equations below for the
type of rock encountered:
qS = 12.0 ksf.

for Shale

qS = 20.0 ksf.

for Sandstone

qS = 24.0 ksf.

for Limestone/Dolomite

Note that actual pile penetration into rock is related to several factors including rock
strength, degree of weathering, hammer energy and pile strength. The IDOT Static Method
represents these by rock type, pile size, and nominal required bearing. The above empirical
side resistance values, when used with the soil side resistance and rock tip resistance,
provide a conservatively accurate representation of pile penetration into rock and thus total
estimated pile length.
Nominal Unit Tip Resistance (qP) of granular soils, shall be calculated as follows:

qp

0.8 N D b
D

Where:

Oct 2011

8N (forsands & gravel) or 6N (forfinesiltysand & hard till)

Page 4

AGMU Memo 10.2 Geotechnical Pile Design

Design Guide
D

= Pile diameter or width (ft.)

Db

= Depth of penetration into soil (ft.)

= Field measured SPT blow count (blows/ft.)

= Effective vertical soil pressure (ksf.) calculated using soil unit weight
approximated (in kcf.) as follows:
Above water table:
Below water using:

granular

= 0.095N0.095

cohesive

= 0.1215QU0.095

granular

= 0.105N0.07 0.0624

cohesive

= 0.1215QU0.095 0.0624

Nominal Unit Tip Resistance (qP) of cohesive soils, shall be calculated as follows:
qP = 9 QU
Note that QU is input in tsf. and qP is output in ksf.
Nominal Unit Tip Resistance (qP) of rock, shall be calculated using the equations below for the
type of rock encountered:
qP = 120.0 ksf.

for Shale

qP = 200.0 ksf.

for Sandstone

qP = 240.0 ksf.

for Limestone/Dolomite

Note that actual pile penetration into rock is related to several factors including rock
strength, degree of weathering, hammer energy and pile strength. The IDOT Static Method
represents these by rock type, pile size, and nominal required bearing. The above empirical
tip resistance values, when used with the soil side resistance and rock side resistance,
provide a conservatively accurate representation of pile penetration into rock and thus total
estimated pile length.
Maximum Nominal Required Bearing (RN MAX) is the maximum RN value that can be specified on the
plans to avoid dynamic stresses during driving which would cause damage to the pile. The value
may be determined by use of a wave equation analysis considering the site specific soils and

Oct 2011

Page 5

AGMU Memo 10.2 Geotechnical Pile Design

Design Guide

driving equipment to permit more cost effective designs. In the absence of a site specific drivability
analysis, the RN MAX may be conservatively approximated using the following empirical relationships:
Metal Shell Piles: RN MAX = 0.85xFYAS
Where:

FY = yield strength of the steel shell (45 ksi)


AS = the steel shell cross-sectional area (in.2)

Steel Piles:
Where:

RN MAX = 0.54xFYAS
FY = yield strength of the steel (50 ksi)
AS = the steel cross-sectional area (in.2)

Precast Piles:

RN MAX = 0.3xfcxAg
fc = compressive strength of concrete (4.5 or 5 ksi)

Where:

Ag = gross concrete cross sectional area of pile (in.2)


Timber Piles:
Where:

RN MAX = 0.5xFcoxAP
Fco = resistance in compression parallel to grain (2.7 ksi)
AP = cross-sectional timber area at top of pile (in.2)

Factored Resistance Available (RF) represents the net long term axial factored geotechnical
resistance available at the top of the pile to support factored structure loadings. It accounts for
losses in geotechnical resistance that occurs after driving due to scour, downdrag (DDR), or
liquefaction (Liq.), resistance required to support downdrag loads (DDL) and reflects the resistance
factor used to verify RN. RF shall be calculated using the following equation:
RF= RN(

G)

- (DDR+Scour+Liq.)x(

G)

x(lG) DDLx( p)x(

IS)

Where:
Scour = nominal side resistance (loss) of soil above the design scour elevation.

Oct 2011

Liq.

= nominal side resistance (loss) of soil within liquefiable layers.

DDR

= nominal side resistance (loss) of soil expected to settle > 0.4 in.

DDL

= nominal side resistance (load) of soil expected to settle > 0.4 in.

Page 6

AGMU Memo 10.2 Geotechnical Pile Design

Design Guide

= the Geotechnical Resistance Factor for the construction verification of RN

lG

= the Bias Factor Ratio relating the IDOT static method to the construction
verification method used.

= the DDL Load Factor for the downdrag soil loading on the pile

IS

= the Bias Factor related to the IDOT static method

Applying the geotechnical resistance factor (

G)

to the geotechnical losses may appear

unconservative. However, AASHTO LRFD Article 10.7.3.7 requires the factored loads (RF +
pDDL)

be the factored resistance below the downdrag layers. Thus, the pile must be driven to

a RN equal to the nominal downdrag resistance (DDR) to install the pile through the downdrag
layer plus (RF +
by

DDL)/

which results in both the geotechnical losses and RN being multiplied

G.

The nominal values of the downdrag (DDR and DDL), Scour and Liquefaction (Liq.) shall be
calculated using the IDOT static method side resistance equations provided above and as
described below.
Downdrag is considered twice to represent the loss in side resistance (DDR) and again to
account for the added loading (DDL) applied to the pile. The LRFD load groups specify that the
portion of downdrag which applies a loading to the pile be included with loadings from other
applicable sources. However, it is IDOTs policy to require that the downdrag loading (DD L) and
downdrag reduction in resistance (DDR) for a pile be taken into account by the geotechnical
engineer so it can be incorporated in the SGR pile design tables. Thus they should not be
included by the structural engineer in calculating the factored loadings.
Scour protection is provided by accounting for the loss in side resistance of soil layers above the
design scour elevation in determining the RF available to designers. The Scour term shall be
taken as zero when calculating the RF to resist Extreme Event I seismic loadings.
Liquefaction is the loss of side resistance in layers expected to liquefy (Liq.) due to the design
seismic event.

Since liquefied soil of sufficient thickness consolidates, any non-liquefiable

layers above such soils will settle and produce downdrag effects which must also be taken into
account. Thus, in addition to Liq., losses from DDR and DDL for the layers above the liquefied
soils shall be calculated and included in the RF equation. However Liq. and downdrag caused
by liquefaction shall only be considered when calculating the RF to resist Extreme Event I
seismic loadings.

Oct 2011

Page 7

AGMU Memo 10.2 Geotechnical Pile Design

Design Guide

The values of geotechnical losses (Scour, DDR, DDL, and Liq.) for non-displacement steel H-piles
shall be calculated using the surface area assumption, (ASAp representing plugged conditions),
regardless of whether the controlling value of RN used plugged or unplugged side resistance.
Values for the Geotechnical Resistance Factor, Bias Factor and Bias Factor Ratio, and DDL Load
Factor, shall be selected as follows:
The Geotechnical Resistance Factor (

G)

shall be selected to represent the reliability of the

construction method used to verify that the RN has been developed. Our analysis using both
national and local driving records and load tests indicated a

of 0.55 should be used to

compute RF if the WSDOT formula is specified for construction verification.

When more

accurate construction verification methods are proposed, such as with static load test or a Pile
Driving Analyzer (PDA), the resistance factor used may be increased to the values provided in
the AASHTO specifications.
The Bias Factor (

IS)

is a statistical parameter that reflects the general tendency of the IDOT

static method to over or under-predict the nominal pile resistance when compared to the results
of static pile load tests. The IDOT static method contains revisions that improve the bias of the
method, however it is typically not possible to entirely eliminate all bias. Research indicates that
the IDOT static method has a bias factor of 1.09 indicating that the method has a tendency to
under-predict pile resistances.

When using the IDOT static method to estimate downdrag

effects, DDL shall be multiplied by a

IS

factor of 1.09.

The Bias Factor Ratio (lG), shall be included in the calculation for the nominal pile resistance
(RN) and also be applied to the geotechnical losses (Scour, DDR, and Liq.) to account for
differences in bias between the method used to estimate these values (using the IDOT static
method) and the construction method used to verify the RN (typically the WSDOT formula).
Similar to that previously described for the IDOT static method, research indicated that the
WSDOT formula used for construction verification has a bias factor of 1.05. The

of 0.55 that

is specified for computing RF when the WSDOT formula is being specified for construction
verification is a function of the statistical parameters resulting from a comparison of the WSDOT
formula results and static load tests.

Since the

indicated above is based on statistical

variables relative to the WSDOT formula, lG is being applied to the results from the IDOT static
method in an effort to try and further equate the two methods. lG is equal to 1.04 and is the ratio

Oct 2011

Page 8

AGMU Memo 10.2 Geotechnical Pile Design

Design Guide

of the bias factors for the two methods (the bias factor for the IDOT static method divided by the
bias factor for the WSDOT formula).
The DDL Load Factor ( p) shall be equal to 1.05 for DDL caused by cohesive or granular soil
layers for piles in compression. For cohesive soil layers, it is believed that the research results
and enhancements employed with the IDOT static method offers a reliability closer to that
associated with the

method of estimating side resistances contained in the AASHTO LRFD

code. As such, the

method load factor reflected in LRFD Table 3.4.1-2 is specified for use

with cohesive soil layers. The side resistances estimated by the IDOT static method for
cohesionless soils is considered to be more consistent with an effective stress analysis (which is
used with the above mentioned

method) and long term drained conditions. Subsequently, the

same load factor has been chosen for use with granular soil layers for piles in compression.

shall be equal to 0.30 for DDL caused by cohesive or granular soil layers when the pile is

required to provide pullout or uplift resistance.


If it becomes clear during the planning process that earthquake forces may govern the pile design,
the SGR pile tables should include both the RF to support Extreme Event I Limit State loadings by
setting the

to 1.0, as well as the RF to support Strength Limit State loadings by setting

to 0.55.

In load cases requiring piles to provide uplift resistance, the factored tension or pullout resistance of
the pile shall be determined using the nominal side resistance equations provided above and
applying a geotechnical resistance factor (

G)

of 0.20 for uplift under Strength Limit State loadings

and 0.8 for uplift under Extreme Event I Limit State loadings. For non-displacement steel H-piles,
pullout resistance shall be computed using the surface area assumption (ASAp) for a plugged
condition only. This calculation will provide the minimum tip elevation which must be specified on
the plans ensure pullout resistance.
Estimated Pile Lengths shall be provided in the pile design tables corresponding to the RN and RF
values computed using the equations above. Since calculating these values requires assumption
of the pile length, the procedures and guidance provided below shall be used in determining how
these lengths should be selected and which should be provided in the pile design tables in the
SGR:

Oct 2011

Page 9

AGMU Memo 10.2 Geotechnical Pile Design

Design Guide

The geotechnical engineer should contact the structural engineer to obtain preliminary
substructure locations and their total factored vertical loading as well as the ground surface, pile
cutoff, and bottom of footing/substructure excavation elevations.
The geotechnical engineer shall evaluate the subsurface soil and rock boring data to develop
the profile of pile design parameters (N and Qu) at each substructure.
Compute the relationship between RN and pile penetration expected as the pile is driven from
the footing/substructure excavation elevation through the various soil design profile for each
possible pile type at every substructure. This is typically done by breaking up the soil profile into
smaller (2.5 to 7.5 thick) layers and selecting pile lengths corresponding to the bottom of each
layer. This provides the RN consisting of the cumulative side resistance of all layers above the
bottom of the layer in question and the tip resistance of the layer just below the bottom of the
layer in question.
Determine the maximum nominal required bearing feasible to specify without causing damage
to the pile.

This is most often done using the empirical relationships provided above for

approximating RN

MAX

but using of wave equations analysis may also be used to determine if

higher values of RN can be provided in the pile design tables.


Use the total vertical factored substructure loadings divided by the maximum and minimum pile
spacing to provide an initial estimate of the range of RF to provide in the tables.
Discuss this initial range of RF and the corresponding estimated lengths with the structural
engineer to help finalize the range to be included in the SGR. It is preferred that the tables
contain too many, rather than too few values to allow the designer the most data upon which to
determine the most economical pile type and foundation design layout.
It is important to again verify the preliminary information and adjust the pile design tables if any
elevations or loads have changed.

The estimated pile length contained in the design tables

(and shown on the plans) must include the portions of the pile which will be incorporated in the
substructure, footing, and pile encasement. Thus, the ground surface adjacent to the pile during
driving and proposed pile cutoff elevations must be accurately determined.

Oct 2011

Page 10

You might also like