Recip Compressor Capacity Control Methods
Recip Compressor Capacity Control Methods
Engineering
Practice
Reciprocating Compressors
Startup and Capacity
Control Methods
Procedures and guidelines that will help operators
minimize energy consumption and maintenance
requirements of compressor systems
Ali Ghanbariannaeeni
Nargan Engineers
and Constructors
Ghazalehsadat Ghazanfarihashemi
Sazeh Consultants
(1)
(2)
Where:
W
=
m
=
Mw =
p2/p1 =
K
=
Tin =
PD =
Compressor power
Rated mass flow
Gas molecular weight
Compressor ratio
Gas specific-heat ratio
Gas inlet temperature
Compressor piston
displacement
Q
= Compressor flow
C
= Compressor clearance
volume
R
= Ideal gas constant
It must be remembered that a reduction in the flow to the second stage
causes a drop of all inter-stage pressures, and consequently it can lead to
excessively high-pressure ratios and
discharge temperatures in subsequent
stages. Moreover, this pressure shifting may cause an overload in the last
stage. Thus, there should be a limitation on the maximum by-passed flow
in multistage equipment. The minimum capacity that can be obtained
depends on the number of compression stages.
The more stages used for a given
overall compression ratio, the wider
the achievable control range.
Inlet valve unloaders. Valve unload-
51
Engineering Practice
ers are mechanisms that are held open
or bypass one or more cylinders inlet
valves at each end of double-acting
cylinders. This provides complete unloading of one or both ends of the cylinder. For a single-cylinder compressor stage, valve unloaders can achieve
three-step unloading that provides
nominal cylinder capacities of 100, 50
and 0%; and two-step unloading that
provides cylinder capacities of 100
and 0%. Thus, considering two cylinders per compressor, the capacity can
be controlled in five stages 100, 75, 50,
25 and 0%.
Three-step (100, 50 and 0%) capacity
control is used on some general purpose machines, such as air compressors. This method of control requires
more cyclic actuation of the unloaders than five-step control. Therefore,
three-step control is more detrimental
to machine components especially
to valves.
Standard API 618 [6] introduces
three unloader types: finger, plug and
port. The finger type unloader is not
recommended when other types are
viable. Plug type unloaders should
be installed on extra suction ports. A
minimum number of valve unloader
steps should be considered in order to
maximize compressor reliability.
Unloaders should be pneumatically operated by instrument air and
equipped with positioner indication.
The unloader actuator should be sized
to operate on minimum air pressure
as well. Nitrogen purge ports should
be provided for all types. The unloader
stem packing should be provided with
a lantern ring and a nitrogen connection for the purging of leak gas. All
purge and vent connections should be
piped up to a single purge and vent
connection. All lines to and from unloaders are to be AISI 316 L stainless
steel [6, 7].
It should be noted that there are
some restrictions on actuator sizing at
suction pressures higher than 70 barg.
Clearance pockets. Cylinder delivered capacity can be reduced by
increasing the cylinder clearance
volume; this is done by a clearance
pocket. There are two types of pockets:
fixed and variable. Opening the pocket
reduces the cylinders inlet volumetric
flow by trapping additional gas in the
52
mately one minute. When pre-lubrication time has passed, the startup condition Pre-lubrication time passed is
activated and displayed on the DCS.
When neither the low-lube-oil pressure alarm nor the low low-lube-oil
pressure alarm is activated, the hydro
jacking pump and subsequently the
main motor are permitted to start.
During normal operation of the compressor, the standby oil pump should
be in auto mode and start automatically when a low-oil-pressure alarm is
triggered on the DCS.
If the low low-oil-pressure signal
lasts more than a specified time (usually 2 s), the compressor main motor
should be stopped immediately by a
shutdown (trip).
Since the compressor is stopped normally, post lubrication is started; this
means that the lubrication oil pump
will continue to run for a minimum of
approximately 2 min. When post lubrication time has passed and the normal
stop sequence is accomplished, the oil
pump can either be stopped by the operator or continues running. Note that
in maintenance mode, the frame oil
pump can be started individually.
Moreover, the operator can enable
the oil heater by pushing a button in
the DCS. If the heater is enabled, the
temperature of the frame lubrication
oil is controlled by the switch controller inside the heater. Note that the
crankcase oil temperature should not
exceed 70C (160F).
For safety reasons, the heater is
interlocked and must be switched off
when the low low oil level is activated. It should be noted that during
compressor operation, the heater shall
always be stopped.
Compressor cylinder lubrication
system. The cylinder lubrication
system is pressurized by electrically
driven multiple-plunger-type oil
pumps (plunger per point) or by the
divider block method. However, using
a divider block system is not recommended because of complexity and
low reliability.
The cylinder lubrication system will
be started locally if the cylinder oiltank level is fulfilled (above low level).
When the pre-lubrication time (approximately 2 min) has elapsed, the
compressor start condition cylinder
53
Engineering Practice
pre lubrication time passed is fulfilled and displayed in the DCS, and
the over lubrication time starts. The
total time of the cylinder lubrication
pumps running without the main
motor running is cumulative via cylinder lubrication time.
The compressor main motor must
be started within the over lubrication
time (approximately 5 min) to prevent
accumulation of oil in the cylinder.
If the total over-lubrication time has
elapsed and the main motor is still not
running, a compressor main-motorstart inhibit will be activated and an
alarm remove oil collected in cylinders
before re-start appears on the DCS.
Resetting the over lubrication
time alarm will be done by slowly rotating the compressor for a number of
revolutions (usually two or three) by a
barring device to distribute the accumulated lube oil among the compressor cylinders. At this time, the alarm
can be reset in the DCS manually.
During cylinder barring-over or
maintenance operations, the cylinder
lubrication should not be activated.
At compressor normal stop, post
lubrication time starts for approximately 2 min, and the cylinder oil
pump switches off automatically afterwards. By pressing the emergency
stop, the cylinder oil pump stops immediately and no post lubrication is
carried out. The cylinder lubricationoil pumps should run while the compressor main motor is running. In the
event of low flow, an alarm will be triggered in the DCS and in the case of
low low-flow, compressor trip action
will be activated.
Moreover, the operator can enable
the oil heater by pushing a button in
the DCS. If the heater is enabled, the
temperature of the cylinder lubrication oil is controlled by a switch controller inside the heater body. The heat
density of the heater should be limited
to 2.3 W/cm2 (15 W/in.2). A temperature switch prevents overheating. An
over temperature switch activates
an alarm and switches off the heater.
For safety reasons, the heater is interlocked and must be switched off when
the low low-oil level is activated.
Compressor cooling water system.
Minimum cooling water flow to the
cylinders and packings is one of the al54
55
Engineering Practice
Bypass valves
Time (min)
Cylinder A
Cylinder B
HE
CE
CE
HE
PCV1
PCV2
PT1
Environmental
PT2
Cooler 1
Stage 1
Cooler 2
Applications
Stage 2
FIGURE 1. Shown here is a typical setup for capacity control in a two-stage reciprocating compressor using bypass valves (PCV = pressure control valve; PT =
pressure transmitter)
50%
75%
100%
Upstep A
Upstep B
Upstep B
Upstep B
50%
Upstep A
Upstep A
Upstep B
Upstep B
75%
Upstep A
Upstep A
Upstep A
Upstep B
100%
Upstep A
Upstep A
Upstep A
No Action
Down-stepping:
Compress or
load B (Slave)
25%
50%
75%
100%
No Action
Downstep A
Downstep A
Downstep A
50%
Downstep B
Downstep B
Downstep A
Downstep A
75%
Downstep B
Downstep B
Downstep B
Downstep A
100%
Downstep B
Downstep B
Downstep B
Downstep A
Wasnteey
o
to m
for example:
Sludge drying
Glycol recovery
Used oil recovery
Lubricant recycling
system solutions
for evaporation and biopharma
Processing Partners:
www.gigkarasek.at
www.incontech.com
Circle 15 on p. 72 or go to adlinks.che.com/40271-15
57
Engineering Practice
duration, the suction pressure will
reach stability again and restore the
suction pressure to its normal value.
The lowest automatic down-step
will be to 25%. The 0% performance
step is only used in compressor startup and shutdown sequences.
Compressor parallel working. Generally, 10% increasing flowrate is performed by increasing suction pressure,
but in many applications, two compressors are needed to send out enough
flowrate downstream of the system.
For this purpose, one of the compressor
controllers will be master and the other
the slave. The master takes the control
decisions about suction pressure control and up- and down-stepping of the
capacity. A slave compressor always
follows the master decisions.
To start two compressors, when the
master machine is stable at 100% capacity, the slave machine should be
started in 0% load. Then, during several
steps, performance of both are equaled
as much as possible. In this regard, in
each stage, 25% of master compressor
capacity (one step) will be decreased
and 25% capacity of slave machine will
be increased subsequently. Meanwhile,
enough time delay (approximately
1 min) between each step should be
considered so that flow stability is obtained at suction of compressors.
The conditions for up- and downstep criteria are the same as for single
compressor operation and are shown
in Table 2.
If the operator decides to take out
one of the two running compressors, the selected compressor will be
stopped with the following automatic
steps with a time delay (approximately 1 min):
The load of the selected compressor will be decreased by 25%. At the
same moment, the load of the compressor that is intended to remain in
operation will be increased by 25%.
This method will be repeated until the
selected compressor is completely unloaded (at 0% capacity).
Final remarks
58
References
1. Bloch, Heinz and Soares, Claire, Process
Plant Machinery, 2nd ed., Elsevier Science
& Technology Books, November 1998.
2. Bloch, Heinz P. and John J. Hoefner, Reciprocating Compressors Operation & Maintenance, Gulf Publishing Co., 1996.
3. Bloch, Heinz P., A Practical Guide To Compressor Technology, 2nd ed., John Wiley and
Sons, 2006.
4. Hanlon, Paul C., Compressor Handbook,
McGraw-Hill, N.Y., 2001.
5. Chlumsky, Vladamir, Reciprocating and Rotary Compressors, SNTL- Publisher of technical Literature, 1965.
6. Reciprocating Compressor for Petroleum,
Chemical and Gas Service Industries, API
618 5th ed., December 2007.
7. Southwest Research Institute, Advanced
Reciprocating Compressor Technology, December 2005.
8. Leonard, Stephen M., Fugitive Emissions
Control Technology For Reciprocating Compressor Cylinders, Dresser-Rand, Painted
Post, N.Y.
9. Giampaolo, Tony, Compressor Handbook:
Principles and Practice, the Fairmont Press,
2010.
10. Forsthoffer, W.E., Forsthoffers Best Practice
Handbook for Rotating Machinery, Elsevier
Science & Technology Books, 2011.
11. Forsthoffer, W.E., Forsthoffers Rotating
Equipment Handbooks, Vol. 3, Elsevier Science & Technology Books, 2005.
12. Pichot, Pierre, Compressor Application Engineering, Gulf Publishing Co. 1986.
Authors
Ali Ghanbariannaeeni is a
rotating equipment engineer
at Nargan Engineers and
Constructors Co. (Tehran CO
15 98 98 3116, Iran; Phone:
+98-21-88-908-104-8;
Fax
+98-21-88-91-0173;
Email:
a.ghanbarian@nargan.com
and
alighanbariannaeeni@
gmail.com). He is specialized
in reciprocating, centrifugal
and screw compressors, gas
and steam turbines, process pumps, engines and
electric machines. He obtained a B.S.M.E. degree
from Iran University of Science and Technology
(Tehran, Iran).
Ghazalehsadat
Ghazanfarihashemi is a rotating
equipment engineer at Sazeh
Consultants Co. (Tehran CO
1587657413, Iran; Phone:
+98-21-88-532-156-7;
Fax
+98-21-88-731-503;
Email:
gh.ghazanfari@sazeh.co.ir
and
ghazanfari.gh@gmail.
com). She is specialized in
reciprocating and centrifugal
compressors, process pumps,
engines and electric machines. She obtained
B.S.ME. and M.S.M.E. degrees from Sharif University of Technology (Tehran, Iran).