Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

PLC Connection Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1158

PLC Connection Guide

PLC Connection Guide


EB Pro Ver.5.04.01
EB8000 Ver.4.66.02

PLC Connection Guide

Table of content
ABB AC500 ................................................................... 1

DELTA DVPEN01-SL (Ethernet)........................... 148

ABB TOTALFLOW FCU ........................................... 5

DL-BCM Server ....................................................... 151

Altus ALNET-I ............................................................. 6

DL/T645 CHUANG HONG ..................................... 155

Arcus DMX-K-SA Series ........................................... 11

DL/T645 Standard.................................................... 162

Artrich Inverter AR100 Series .................................. 16

DL/T645-2007 Standard .......................................... 165

Artrich Inverter AR200/216/600 Series .................... 19

ELSIST MODBUS ASCII ....................................... 168

BACnet/IP ................................................................... 23

ELSIST MODBUS RTU .......................................... 172

BACnet/MSTP ............................................................ 34

ELSIST MODBUS TCP/IP ..................................... 176

Barcode/Keyboard (USB/COM) ............................... 40

EMERSON Charge Module .................................... 178

Baumuller ................................................................... 44

EMERSON ControlWave (Ethernet) Free Tag

Beckhoff ADS/AMS (Ethernet) ................................. 47

Names ........................................................................ 181

Beckhoff Embedded PC ............................................. 56

EMERSON PLC EC20 ............................................ 186

Beckhoff TwinCAT 3 ADS/AMS (Ethernet) ............ 68

Emotiontek MCU Controller................................... 189

Beckhoff TwinCAT PLC (Ethernet) Free Tag

FATEK FB/FBs/B1/B1z Series ................................ 193

Names .......................................................................... 70

Fuji NB Series ........................................................... 201

Bosch Rexroth............................................................. 74

Fuji SPH2000 (Ethernet) ......................................... 204

CAN Bus CANopen Slave (for eMT3000,

GE Fanuc 0i MD....................................................... 206

MT8091/8092XE, cMT3151only) .............................. 80

GE Fanuc CMM ....................................................... 209

CAN Bus General, SAE J1939 (for eMT3000,

GE Fanuc RX3i......................................................... 215

MT8091/8092XE, cMT3151only) .............................. 84

GE Fanuc RX3i (Ethernet) ...................................... 220

CAS CI-1580A ............................................................ 88

GE Fanuc Series 90-30 (Ethernet) .......................... 222

CD MODBUS RTU .................................................... 93

GE Fanuc SNP-X ...................................................... 224

CD MODBUS TCP/IP ............................................... 98

Haiwell PLC .............................................................. 230

Change....................................................................... 100

Hangzhou Maiou MO-TECH .................................. 234

Cimon CM1-CP4A/ECO1A .................................... 102

Hanyoung Controller ............................................... 236

Cimon CM1-SC02A ................................................. 105

HAWE PLVC ........................................................... 239

CoDeSys Automation Alliance ................................ 108

HeFei ShenNong Motor ........................................... 242

CoDeSys V3 (Ethernet) ............................................ 110

Heng Yuan EU series ............................................... 245

Copley Digital Drives ............................................... 114

Hitachi EH-SIO ........................................................ 247

CO-TRUST CTH300-H (Ethernet) ........................ 118

Hitachi EHV Series (Ethernet) ................................ 253

CO-TRUST CTH300-H PPI .................................... 120

Hitachi H/EH/EHV Series ....................................... 255

CROUZET M3 (FBD).............................................. 126

HollySys LE/LM PLC .............................................. 264

CROUZET M3 (LAD) ............................................. 129

HUST H4C ................................................................ 267

Danfoss ECL Apex20 ............................................... 132

HUST H4X ................................................................ 270

Danfoss ECL Apex20 (Ethernet)............................. 136

IAI PCON-C-42PI .................................................... 273

Danfoss FC Series ..................................................... 138

IAI X-SEL CONTROLLER .................................... 279

Danfoss VLT2800 Series .......................................... 141

IAI X-SEL CONTROLLER-SSE ........................... 282

DELTA DVP ............................................................. 144

IDEC Micro .............................................................. 286


1

IDEC MicroSmart .................................................... 291

PLC Connection Guide


LS XGK FEnet (Ethernet) ....................................... 421

Inovance H2U/H1U .................................................. 296

LS Mecapion Metronix AnyPack ............................ 423

Justfi Controller ....................................................... 299

Master-Slave Server ................................................. 425

Kernel sistemi DMX Series ...................................... 302

MEGMEET MC Series ............................................ 428

KEYENCE KV-10/16/24/40/80/Visual KV Series . 304

MEIKONG Metro Safe Server................................ 431

KEYENCE KV-3000 ................................................ 308

Memory Map ............................................................ 437

KEYENCE KV-5000 (Ethernet) ............................. 311

MIKOM MX Series PLC ......................................... 442

KEYENCE KV-L20V/700/1000/3000/5000/Nano

Mitsubishi A1S/A2N ................................................. 446

Series ......................................................................... 313

Mitsubishi A2A/A2U/A2AS/A2USH ....................... 449

KEYENCE KV-L20V/700/1000/3000/5000/Nano

Mitsubishi A2US ....................................................... 452

Series (KV Studio Mode) ......................................... 319

Mitsubishi A3A/A3N/A1SH/A2SH.......................... 455

KONNEX KNXnet/IP .............................................. 326

Mitsubishi AJ71 ........................................................ 458

Korenix 6550 ............................................................. 330

Mitsubishi AJ71 (AnA/AnU CPU) .......................... 463

KOYO CLICK ......................................................... 332

Mitsubishi AJ71 (Format 4) .................................... 468

KOYO CLICK (Ethernet) ....................................... 335

Mitsubishi F930GOT Server ................................... 473

KOYO DIRECT ....................................................... 337

Mitsubishi FX0S/FX0N/FX1S/FX1N/FX2 .............. 476

KOYO Do-more ....................................................... 352

Mitsubishi FX232/485BD ......................................... 481

KOYO Do-more (Ethernet) ..................................... 355

Mitsubishi FX2N ...................................................... 487

KOYO Ethernet ....................................................... 357

Mitsubishi FX2N-10GM/20GM .............................. 490

Lenze ......................................................................... 359

Mitsubishi FX3U (Ethernet) .................................... 493

LingYan BMS ........................................................... 362

Mitsubishi FX3U/FX3G ........................................... 500

LIYAN EX series ...................................................... 364

Mitsubishi FX5U ...................................................... 503

LoXin ......................................................................... 367

Mitsubishi FX5U - ASCII Mode (Ethernet) ........... 508

LS GLOFA Cnet ...................................................... 369

Mitsubishi FX5U - Binary Mode (Ethernet) .......... 511

LS GLOFA FEnet (Ethernet).................................. 375

Mitsubishi L6ADP .................................................... 514

LS GLOFA GM3467 (LOADER) ........................... 376

Mitsubishi MELSEC-Q/L - ASCII Mode (Ethernet)

LS MASTER-K Cnet ............................................... 379

.................................................................................... 517

LS MASTER-K CPU Direct .................................... 382

Mitsubishi MELSEC-Q/L - Binary Mode (Ethernet)

LS MASTER-K MODBUS RTU............................. 385

.................................................................................... 522

LS MASTER-K10S1 ................................................ 388

Mitsubishi MR J3/J4 A ............................................ 526

LS XBM/XBC Cnet .................................................. 391

Mitsubishi MR-MQ100 (Ethernet) ......................... 534

LS XBM/XBC FEnet (Ethernet) ............................. 395

Mitsubishi Q00/Q00UJ/Q01/QJ71 .......................... 536

LS XBM/XBC/XGK CPU DIRECT ....................... 397

Mitsubishi Q00J........................................................ 545

LS XEC Cnet ............................................................ 401

Mitsubishi Q00U/Q01U/Q02U/QnUD/QnUDH ..... 548

LS XEC FEnet (Ethernet) ....................................... 405

Mitsubishi Q00UJ/QnU/QnUD/QnUDH/QnUDEH/L

LS XEC/XGI CPU DIRECT ................................... 407

(mini USB) ................................................................. 552

LS XGI Cnet ............................................................. 410

Mitsubishi Q02/02H ................................................. 554

LS XGI FEnet (Ethernet) ........................................ 415

Mitsubishi Q06H ...................................................... 558

LS XGK Cnet ........................................................... 417

Mitsubishi QJ71E71 (Ethernet) .............................. 562


2

MODBUS ASCII ...................................................... 569

PLC Connection Guide


PATLITE VM/VMS Series...................................... 728

MODBUS ASCII Server .......................................... 574

Rockwell CompactLogix - Free Tag Names ........... 733

MODBUS RTU ......................................................... 579

Rockwell CompactLogix/FlexLogix ........................ 741

MODBUS RTU (0x/1x Range Adjustable) ............. 586

Rockwell DF1 ............................................................ 746

MODBUS RTU (Adjustable)................................... 596

Rockwell DF1 (BCC) ................................................ 750

MODBUS RTU (zero-based addressing)................ 604

Rockwell DH485 ....................................................... 754

MODBUS Server (COM/Ethernet) ........................ 610

Rockwell EtherNet/IP (CompactLogix) .................. 760

MODBUS TCP/IP .................................................... 620

Rockwell EtherNet/IP (CompactLogix) Free Tag

MODBUS TCP/IP (0x/1x Range Adjustable) ........ 622

Names ........................................................................ 763

MODBUS TCP/IP (zero-based addressing) ........... 627

Rockwell EtherNet/IP (ControlLogix) Free Tag

MODBUS TCP/IP 32Bit .......................................... 629

Names ........................................................................ 770

Moeller XC-CPU101 ................................................ 631

Rockwell EtherNet/IP (DF1) ................................... 777

motrona CT-150 ....................................................... 633

Rockwell Micro850 (Ethernet) - Free Tag Names . 780

motrona CT15012B .................................................. 636

Rockwell Micro850 - Free Tag Names .................... 786

motrona MC700 ....................................................... 638

Rockwell PLC5 ......................................................... 794

Nanjing CIGU Controller (for i-Series only) ......... 640

RS Automation OEMAX Series .............................. 798

Nanotec Stepper Motor............................................ 642

RS Automation X8 Series ........................................ 801

NMEA 0183 .............................................................. 645

SAIA PCD PGU Mode ............................................. 804

ODVA EtherNet/IP Explicit Messaging ................. 648

SAIA PCD S-BUS Mode .......................................... 806

OMRON C/CQM1 Series ........................................ 651

SAIA S-BUS (Ethernet) ........................................... 815

OMRON CJ/CS/CP ................................................. 655

Samsung SPC-10 ...................................................... 818

OMRON CJ/CS/CP (Ethernet - FINS/TCP) ......... 660

SCENE6 Controller .................................................. 821

OMRON CP Series (USB) ....................................... 663

Schleicher XCS 20C ................................................. 823

OMRON E5CN/E5EZ/E5ZN .................................. 664

Schleicher XCX 300 ................................................. 826

OMRON Ethernet .................................................... 668

Schneider IMS SERVO............................................ 830

OMRON Ethernet (FINS/TCP) .............................. 671

Schneider MODBUS RTU ....................................... 832

OMRON EtherNet/IP (NJ Series) ........................... 673

Schneider MODBUS TCP/IP .................................. 837

OMRON Host Link .................................................. 678

Schneider SoMachine M Series (Ethernet) ............ 839

OuHua OHJX ........................................................... 683

Schneider UniTelway ............................................... 841

Panasonic Eco-Power Meters .................................. 686

SERVO BLDC (400/750WD) .................................. 844

Panasonic FP/KW .................................................... 691

SEUNGIL AHU ........................................................ 847

Panasonic FP (Ethernet) .......................................... 700

SEW Movilink .......................................................... 850

Panasonic FP2 (Ethernet) ........................................ 702

SEW MOVITRAC LTE .......................................... 852

Panasonic MINAS A4 .............................................. 704

SHIMADEN MR13/FP93 ........................................ 856

Panasonic MINAS A5 .............................................. 709

SHJ-A ........................................................................ 869

Parker ACR9000 ...................................................... 714

SICK FLEXI SOFT ................................................. 871

Parker Compax3 ...................................................... 717

Siemens LOGO (Ethernet) ...................................... 874

Parker Compumotor 6K Series .............................. 723

Siemens S7-1200 (symbolic addressing) (Ethernet)

Parker SLVD Series ................................................. 725

.................................................................................... 879
3

Siemens S7-1200/S7-1500 (absolute addressing)

PLC Connection Guide


XINJE XC Series .................................................... 1092

(Ethernet) .................................................................. 892

YAMAHA ERCD ................................................... 1095

Siemens S7-200 ......................................................... 900

YASKAWA CCMEP ............................................. 1099

Siemens S7-200 (Ethernet)....................................... 905

YASKAWA Memobus (MP Series Controllers) .. 1102

Siemens S7-200 (VD any address) ........................... 913

YASKAWA MP Series Ethernet (Extension) ...... 1109

Siemens S7-200 PPI .................................................. 918

YASKAWA MP Series Memobus (Ethernet) ...... 1113

Siemens S7-200 SMART (Ethernet) ....................... 926

YASKAWA MP Series SIO (Extension) .............. 1115

Siemens S7-200 SMART PPI .................................. 928

YASKAWA MP2300Siec ....................................... 1120

Siemens S7-300 ......................................................... 931

YASKAWA Sigma-5 .............................................. 1130

Siemens S7-300/S7-400 (ISO Ethernet) .................. 939

YASKAWA SMC 3010 .......................................... 1133

Siemens S7-300 MPI ................................................ 942

YASKAWA SMC 3010 (Ethernet) ........................ 1137

Siemens S7-300/ET200S (Ethernet) ........................ 952

YOKOGAWA FA-M3 ........................................... 1140

Siemens S7-400 (Ethernet)....................................... 959

YOKOGAWA FA-M3 (Ethernet) ......................... 1146

Siemens TI505 .......................................................... 966

YUDIAN AIBUS ..................................................... 1148

Siemens TI505 (Ethernet) ........................................ 973

MT6050i/MT8050i/MT8050iE Com Port Pin

Siemens TI565/C400................................................. 975

Assignment .............................................................. 1152

SIGMATEK S-DIAS CPU (Ethernet) .................... 983


SSTC SSD Series ...................................................... 989
TECHSOFT Intelligent Servo ............................... 1001
TECO Inverter ....................................................... 1003
TECO TP02 Series ................................................. 1006
TECO TP03 Series/AP-360BT-A .......................... 1010
TINHAO ................................................................. 1013
Toptek Topvert ....................................................... 1016
TOSHIBA INVERTER VF ................................... 1019
TOSHIBA T Series ................................................. 1022
TOSHIBA MACHINE Provisor TC200 ............... 1028
Trio MODBUS RTU, TCP/IP ............................... 1031
Trio MODBUS RTU, TCP/IP (Mode 7) ............... 1037
VIGOR .................................................................... 1043
VIGOR VS Series ................................................... 1047
VIPA 200 ................................................................. 1051
VIPA 200 (VD any address) .................................. 1054
VIPA 200, for ex. 214-2BT10 (Ethernet) .............. 1057
VIPA 200/300 MPI ................................................. 1059
VIPA 300 ................................................................. 1068
VIPA 300S (Ethernet) ............................................ 1076
VIPA 300S, for ex. 315-4NE12 (Ethernet)............ 1083
WIELAND SAMOS PRO ...................................... 1089
4

PLC Connection Guide

ABB AC500
Supported Series: ABB AC500

HMI Setting:
Parameters

Recommended

PLC type

ABB AC500

PLC I/F

RS485 2W

Baud rate

19200

Data bits

Parity

Even

Stop bits

PLC sta. no.

Port no.

502

Options

Notes

RS232/RS485 2W / Ethernet

Ethernet

Device Address:
Bit/Word

Device type

Format

Range

Memo

MX0

DDDDo

0 ~ 81917

%MX0.0.0 ~ 0.8191.7

MW0

DDDDD

0 ~ 32767

%MW0.0 ~ 0.32767

MW1

DDDDD

0 ~ 32767

%MW0.1 ~ 1.32767

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

PLC COM2 RS232 9P


D-Sub Female

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P

PLC COM2 RS232 9P

D-Sub Female

D-Sub Female

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND
1

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC COM2 RS232 9P


D-Sub Female

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

PLC COM2 RS232 9P


D-Sub Female

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

PLC COM2 RS232 9P


D-Sub Female

9 RX

2 TX

6 TX

3 RX

5 GND

5 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC COM2 RS485 2W


9P D-Sub Female

1 RX-

6 Data-

8 Data-

2 RX+

9 Data+

3 Data+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

PLC COM2 RS485 2W


9P D-Sub Female

7 RX-

4 Data-

8 Data-

6 RX+

1 Data+

3 Data+

5 GND

5 GND

5 GND

cMT/mTV series

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC COM2 RS485 2W


9P D-Sub Female

1 RX-

7 Data-

8 Data-

2 RX+

8 Data+

3 Data+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC COM2 RS485 2W


9P D-Sub Female

1 RX-

6 Data-

8 Data-

2 RX+

9 Data+

3 Data+

5 GND

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC COM2 RS485 2W


9P D-Sub Female

1 RX-

6 Data-

8 Data-

2 RX+

9 Data+

3 Data+

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

PLC COM2 RS485 2W


9P D-Sub Female

1 RX-

7 Data-

8 Data-

2 RX+

8 Data+

3 Data+

5 GND

5 GND

5 GND

PLC Connection Guide

Direct connect (crossover cable):


HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Green

3 RX+

2 TX-

Orange

Green

6 RX-

3 RX+

White/Green

White/Orange

1 TX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Orange

2 TX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Through a hub:

Driver Version:
Version

Date

Description

V1.00

Dec/19/2012

Driver released

PLC Connection Guide

ABB TOTALFLOW FCU


Supported Series: ABB TOTALFLOW FCU
Website: http://new.abb.com/us

HMI Setting:
Parameters

Recommended

PLC type

ABB TOTALFLOW FCU

PLC I/F

Ethernet

Port no.

10000

PLC sta. no.

Options

Notes

Device Address:
Bit/Word Device type

Format

Range

Memo

BIT

DDD.DDD.DDDD

0 ~ 255.255.9999

W_BIT

DDD.DDD.DDDDdd 0 ~ 255.255.999915

Byte

BYTE

DDD.DDD.DDDD

0 ~ 255.255.9999

WORD

DDD.DDD.DDDD

0 ~ 255.255.9999

DW

DWORD

DDD.DDD.DDDD

0 ~ 255.255.9999

STRING

DDD.DDD.DDDD

0 ~ 255.255.9999

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Sep/22/2014

Driver released
5

PLC Connection Guide

Altus ALNET-I
Supported Series: Altus SeriesMode PO3042, PO3142, PO3242, PO3342, PL103 ,PL104,
PL105, QK800, QK801, QK2000.

HMI Setting:
Parameters

Recommended

PLC type

Altus ALNET-I

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Options

Notes

Device Address:
Bit/Word

Device Type

Format

Range

Memo

M_Bit

DDDDh

0 ~ 1023f

Memories

DDDh

0 ~ 511f

Auxiliary Relays

DDDh

0 ~ 511f

Input Relays

D_Bit

DDDDdd

0 ~ 102331

Decimals

F_Bit

DDDDdd

0 ~ 102331

Reals

I_Bit

DDDDdd

0 ~ 102331

Integers

DDDh

0 ~ 511f

Output Relays

DDDD

0 ~ 4096

Memories

DW

DDDD

0 ~ 4096

Decimals

DW

DDDD

0 ~ 1023

Reals

DW

DDDD

0 ~ 1023

Integers

TM

HHHH

0 ~ ffff*

Memory Tables

DW

TD

HHHH

0 ~ ffff*

Decimal Tables

DW

TF

HHHH

0 ~ ffff*

Real Tables

DW

TI

HHHH

0 ~ ffff*

Integer Tables

Note: The formats of TM, TD, TF and TI in PLC software are represented as TXA[B]. X
can be M, D, F, or I.
The address range of B is 0~FF, and A is 0~FF. The device type is AABB, and the range
depends on the PLC settings.
For example: Model PO3242, range of A is 0 and range of B is 0 ~ 7.
6

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 8P RJ45: PLC PO3042, PO3142, PO3242, PO3342
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

PLC RS232 8P RJ45


Male

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

PLC RS232 8P RJ45


Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

PLC RS232 8P RJ45

D-Sub Female

Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

PLC RS232 8P RJ45


Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

PLC RS232 8P RJ45


Male

9 RX

2 TX

6 TX

3 RX

5 GND

5 GND

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 9P D-Sub: PLC PL103, PL104, PL105
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

2 RX

8 RX

7 TX

3 TX

7 TX

1 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

2 RX

7 TX

3 TX

1 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

2 RX

7 TX

3 TX

1 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

PLC RS232 9P D-Sub


Male

2 RX

6 RX

8 RX

7 TX

3 TX

4 TX

7 TX

1 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

9 RX

7 TX

6 TX

1 RX

5 GND

5 GND

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 9P D-Sub: PLC QK800, QK801, QK2000.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

7 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

2 RX

2 TX

3 TX

3 RX

5 GND

7 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

2 RX

2 TX

3 TX

3 RX

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

PLC RS232 9P D-Sub


Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

7 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

9 RX

2 TX

6 TX

3 RX

5 GND

7 GND

PLC Connection Guide

Driver Version:
Version

Date

V1.10

Jul/24/2009

Description

10

PLC Connection Guide

Arcus DMX-K-SA Series


Supported Series: Arcus DMX-K-SA Series.
Website: http://www.arcus-technology.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

Arcus DMX-K-SA Series

PLC I/F

RS232

RS232 / RS485 2W

Baud rate

9600

9600 ~ 115200

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device Type

Format

Range

ABORT

ABS

CLR

CLRS

DI_Bit

1~6

DO_Bit

1~3

EDO

EO

H+

H-

J+

J-

L+

L-

LT

MM

MST

0~9

POL

0~8
11

Memo

PLC Connection Guide

Bit/Word

Device Type

Format

Range

RT

SCV

SL

STORE

SLOAD

STOP

Z+

Z-

ZH+

ZH-

ACC

CUR

CURI

CURR

DB

DI

DN

0~2

DO

DX

EX

HSPD

ID

0~6

LCA

LSPD

LTE

LTP

LTS

PS

PX

SA

DDDD

0 ~ 1275

SASTAT

SLA

SLE

SLS

SLT

SR

SPC

0
12

Memo

PLC Connection Guide

Bit/Word

Device Type

Format

Range

SSPD

SSPDM

DD

0 ~ 99

VER

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

PLC RS232 24P


Connector

2 RX

8 RX

9 TX

3 TX

7 TX

19 RX

5 GND

5 GND

3;24 GND

cMT/mTV series
COM1 RS232 9P

PLC RS232 24P

D-Sub Female

Connector

2 RX

9 TX

3 TX

19 RX

5 GND

3;24 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC RS232 24P


Connector

2 RX

9 TX

3 TX

19 RX

5 GND

3;24 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

PLC RS232 24P


Connector

2 RX

6 RX

8 RX

9 TX

3 TX

4 TX

7 TX

19 RX

5 GND

5 GND

5 GND

3;24 GND

13

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

PLC RS232 24P


Connector

9 RX

9 TX

6 TX

19 RX

5 GND

3;24 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W

COM3 RS485 2W

PLC RS485 2W 24P

9P D-Sub Male

9P D-Sub Male

Connector

1 RX-

6 Data-

6 Data-

2 RX+

9 Data+

4 Data+

5 GND

5 GND

3;24 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

PLC RS485 2W 24P


Connector

7 RX-

4 Data-

6 Data-

6 RX+

1 Data+

4 Data+

5 GND

5 GND

3;24 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W

COM3 RS485 2W

PLC RS485 2W 24P

9P D-Sub Male

9P D-Sub Male

Connector

1 RX-

7 Data-

6 Data-

2 RX+

8 Data+

4 Data+

5 GND

9 GND

3;24 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W 24P


Connector

1 RX-

6 Data-

6 Data-

2 RX+

9 Data+

4 Data+

5 GND

5 GND

3;24 GND

14

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W 24P


Connector

1 RX-

6 Data-

6 Data-

2 RX+

9 Data+

4 Data+

5 GND

5 GND

3;24 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

PLC RS485 2W 24P


Connector

1 RX-

7 Data-

6 Data-

2 RX+

8 Data+

4 Data+

5 GND

5 GND

3;24 GND

Driver Version:
Version

Date

Description

V1.00

Mar/23/2015

Driver released

15

PLC Connection Guide

Artrich Inverter AR100 Series


Supported Series: Artrich Inverter AR100 Series
Website: www.artrich.cn

HMI Setting:
Parameters

Recommended

Options

PLC type

Artrich Inverter AR100 Series

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

F3002_bit

Hh

0 ~ 0f

F3003_bit

Hh

0 ~ 0f

F0-0 ~ F0-1

W/R

F0-2

0~1

W/R *Note1

F0-3 ~ F0-157

W/R

F2-0 ~ F2-16

Read only

F3000 ~ F3001

Write only

F3002 ~ F3003

Read only

FC01 ~ FC12

Read only
Note 1: Value 0 means write to NAND Flash (Data will be saved after power off.) Value 1
means write to RAM (Data will not be saved after power off.)

16

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45

1 RX-

6 Data-

8 Data-

2 RX+

9 Data+

1 Data+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P RJ45

7 RX-

4 Data-

8 Data-

6 RX+

1 Data+

1 Data+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45

1 RX-

7 Data-

8 Data-

2 RX+

8 Data+

1 Data+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45

1 RX-

6 Data-

8 Data-

2 RX+

9 Data+

1 Data+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45

1 RX-

6 Data-

8 Data-

2 RX+

9 Data+

1 Data+

5 GND

5 GND

17

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P RJ45

1 RX-

7 Data-

8 Data-

2 RX+

8 Data+

1 Data+

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Nov/18/2014

Driver released

18

PLC Connection Guide

Artrich Inverter AR200/216/600 Series


Supported Series: Artrich Inverter AR200/216/600 Series
Website: www.artrich.cn

HMI Setting:
Parameters

Recommended

Options

PLC type

Artrich Inverter AR200/216/600 Series

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

F3002_bit

Hh

0 ~ 0f

F3003_bit

Hh

0 ~ 0f

F0-0 ~ F0-1

W/R

F0-2

0~1

W/R *Note1

F0-3 ~ F0-178

W/R

F2-0 ~ F2-16

Read only

F3000 ~ F3001

Write only

F3002 ~ F3003

Read only

FC01 ~ FC12

Read only
Note 1: Value 0 means write to NAND Flash (Data will be saved after power off.) Value 1
means write to RAM (Data will not be saved after power off.)

19

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45

1 RX-

6 Data-

8 Data-

2 RX+

9 Data+

1 Data+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P RJ45

7 RX-

4 Data-

8 Data-

6 RX+

1 Data+

1 Data+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45

1 RX-

7 Data-

8 Data-

2 RX+

8 Data+

1 Data+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45

1 RX-

6 Data-

8 Data-

2 RX+

9 Data+

1 Data+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45

1 RX-

6 Data-

8 Data-

2 RX+

9 Data+

1 Data+

5 GND

5 GND

20

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P RJ45

1 RX-

7 Data-

8 Data-

2 RX+

8 Data+

1 Data+

5 GND

5 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W terminal

1 RX-

6 Data-

RS485-

2 RX+

9 Data+

RS485+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W terminal

7 RX-

4 Data-

RS485-

6 RX+

1 Data+

RS485+

5 GND

5 GND

GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W terminal

1 RX-

7 Data-

RS485-

2 RX+

8 Data+

RS485+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W terminal

1 RX-

6 Data-

RS485-

2 RX+

9 Data+

RS485+

5 GND

5 GND

GND

21

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W terminal

1 RX-

6 Data-

RS485-

2 RX+

9 Data+

RS485+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W terminal

1 RX-

7 Data-

RS485-

2 RX+

8 Data+

RS485+

5 GND

5 GND

GND

Driver Version:
Version

Date

Description

V1.00

Nov/18/2014

Driver released

22

PLC Connection Guide

BACnet/IP
Supported series: BACnet/IP protocol devices

HMI Setting:
Parameters

Recommended

PLC type

BACnet/IP

PLC I/F

Ethernet

Options

Port no.

47808

HMI port no.

47808

47808~47823

Device ID

342566

0~999999

PLC sta. no.

Notes

47808 is the standard


communication port of
BACnet protocol.
Different HMI ports are
required when connecting
multiple
devices.communication
According to device.
port of BACnet protocol.

BACnet/IP to MS/TP Adapter Setting:


1. When using BACnet/IP driver, please correctly set Mode, Maxinum number of
segments accepted, and Maximum APDU length accepted according to the actual
device.

BACnet/IP to
MS/TP adapter

23

PLC Connection Guide

2. As shown above, in BACnet/IP to MS/TP Adapter mode, [Network number] must follow
the factory setting, and enter the device station number in [Device ID].
3. [HMI port no]. default: 47808, can be filled in other effective value.

How to Import Tags:


EasyBuilder Pro provides two ways to gain tag addresses. One is to directly get tag
information via internet, another is to export the generated CSV file via SCADA, and then
import to EasyBuilder Pro. The following introduces how to import tag address information.
Step 1. Add BACnet/IP driver in System Parameters Settings

24

PLC Connection Guide

Step 2. Correctly set the relevant parameters.

Step 3. Get tag address information


Way 1: Click Get Tag Info.

25

PLC Connection Guide

Way 2: Import the CSV file generated by SCADA software.

CSV file content is shown below; users can build the file and import:
a. Object format
b. OBJECT NAME (user defined tag name, EasyBuilder will start reading data from the
6th row of CSV file.), DEVICE ID, OBJECT TYPE(object ID) and INSTANCE(object
address)

26

PLC Connection Guide

Step 4. File imported successfully.

Take (102)File as an example, 10 represents object ID, 2 represents object address, File
represents user defined name or default name.

Default Object Model:


Object ID

Object Name

Object Structure

Analog Input

Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Units
Min Press Value
Max Press Value
Cov Increment
Resolution
High Limit
Low Limit
Dead Band
27

PLC Connection Guide

Object ID

Object Name

Object Structure
Profile Name

Analog Output

Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Units
Relinquish Default
Min Press Value
Max Press Value
Cov Increment
Resolution
High Limit
Low Limit
Dead Band
Profile Name

Analog Value

Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Units
Relinquish Default
Cov Increment
High Limit
Low Limit
Dead Band
Profile Name

Binary Input

Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Polarity
Profile Name
28

PLC Connection Guide

Object ID

Object Name

Object Structure
Notify Type
Alarm Value

Binary Output

Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Polarity
Profile Name
Notify Type

Binary Value

Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Profile Name
Notify Type
Alarm Value

Calendar

Object Name
Object Identifier
Object Type
Present Value

Command

Object Name
Object Identifier
Object Type
Present Value
In Process
All Writes Successful

Device

Object Name
Object Identifier
Object Type
System Status
Vendor Name
Vendor Identifier
Model Name
Firmware Revision
29

PLC Connection Guide

Object ID

Object Name

Object Structure
Application Software Version
Protocol Version
Protocol Revision
Max APDU length Accepted
Segmentation Supported
Apdu Timeout
Number Of APDU retries
Data Base Revision
Max Segments Accepted
Day light Savings Status
Apdu Segment Timeout
Backup Failure Timeout

10

File

Object Name
Object Identifier
Object Type
File Type
File Size
Archive
Read Only

11

Group

Object Name
Object Identifier
Object Type

13

Multi State
Input

Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Reliability
Number Of States
Time Delay
Notification Class
Notify Type
Profile Name

14

Multi State

Object Name

Output

Object Identifier
Object Type
Present Value
30

PLC Connection Guide

Object ID

Object Name

Object Structure
Event State
Out Of Service
Reliability
Number Of States
Time Delay
Notification Class
Notify Type
Profile Name

15

Notification
Class

Object Name
Object Identifier
Object Type
Notification Class
Priority

17

Schedule

Object Name
Object Identifier
Object Type
Present Value
Priority For Writing
Reliability
Out Of Service

18

Averaging

Object Name
Object Identifier
Object Type
Minimum Value
Average Value
Maximum Value
Attempted Samples
Valid Samples
Window Interval
Window Samples

19

Multi State
Value

Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Reliability
Number Of States
31

PLC Connection Guide

Object ID

Object Name

Object Structure
Notification Class
Notify Type
Profile Name
Time Delay

20

Trend Log

Object Name
Object Identifier
Object Type
Enable
Stop When Full
Buffer Size
Record Count
Total Record Count

21

Life Safety

Object Name

Point

Object Identifier
Object Type
Present Value
Tracking Value
Event State
Reliability
Out Of Service
Mode
Silenced

22

Life Safety
Zone

Object Name
Object Identifier
Object Type
Present Value
Tracking Value
Event State
Reliability
Out of Service
Mode
Silenced

23

Accumulator

Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
32

PLC Connection Guide

Object ID

Object Name

Object Structure
Scale
Units
Reliability

24

Pulse
Converter

Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Units
Scale Factor
Adjust Value
High Limit
Low Limit
Dead Band
Cov Increment
Count

Note 1. Object name can not include #.

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Jan/12/2012

Driver released
33

PLC Connection Guide

BACnet/MSTP
Supported series: BACnet/MSTP protocol devices

HMI Setting:
Parameters

Recommended

Options

PLC type

BACnet/MSTP

PLC I/F

RS485-2W

Baud rate

38400

Data bits

Parity

None

Stop bits

MAC

0 ~ 254

HMI MAC

1 ~ 127

Nmax_master

127

2 ~ 127

Npoll

50

1 ~ 255

Notes

9600,19200,38400

How to Import Tags:


1. In EasyBuilder System Parameter Settings add BACnet/MSTP driver, set the
communication parameters, and then click Tag Manager button.

34

PLC Connection Guide

2. Use a RS-232/RS-485 converter to connect the BACnet MS/TP unit with PC. Only one
BACnet MS/TP unit is allowed. Set PC COM and Baud rate, click Scan Device button
to find the MAC address and Device ID of the BACnet MS/TP unit.

3. If the device is found, the following message shows, click OK.

4. After getting the MAC address and Device ID, click Get Tag Info button to get the
address tags.

35

PLC Connection Guide

5. If the tags are obtained successfully, the following message shows, click OK.

6. In the PLC Tags field, the tags with its check box selected can be imported. After
selecting the tags, click Save, and then click Export All, to save the address tags as
CSV file. When finished, click Exit to finish importing address tags.

7. To connect another BACnet/MSTP unit, please add the BACnet/MSTP driver in


EasyBuilder System Parameter Settings again. The communication parameters will
follow the settings of the firstly added unit. The way to get tag information is the same
as illustrated in the preceding steps. Another way to get tag information is to click
[Import form CSV] button in Tag Manager.

Notes:
1. The MAC address and Device ID of certain BACnet MS/TP units can be gained by
clicking [Scan Device] only at the first time the unit is powered up. To get this
information in the same way again, please power up the unit again.

36

PLC Connection Guide

2. Certain BACnet MS/TP units do not support [Scan Device] and [Get Tag Info].
3. If the MAC address gained by clicking [Scan Device] does not match the one specified
in EasyBuilder Pro Device Properties settings, a message shows as a reminder when
[Get Tag Info] is clicked.

Default Object Model:


Object ID

Object Name

Object Structure

Analog Input

Object Name
Object Identifier
Object Type
Present Value
Present Value Array
Units

Analog Output

Object Name
Object Identifier
Object Type
Present Value
Present Valuse Array
Units
Priority
Priority Array
Relinquish Default
SubscribeCovTime

Analog Value

Object Name
Object Identifier
Object Type
Present Value
Present Value Array
Units
Priority
Priority Array
Relinquish Default
SubscribeCovTime

Binary Input

Object Name
Object Identifier
Object Type
Present Value
Present Value Array
37

PLC Connection Guide

Object ID

Object Name

Object Structure
SubscribeCovTime

Binary Output

Object Name
Object Identifier
Object Type
Present Value
Present Value Array
Priority
Priority Array
Polarity
SubscribeCovTime

Binary Value

Object Name
Object Identifier
Object Type
Present Value
Present Value Array
Priority
Priority Array
SubscribeCovTime

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W terminal

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

cMT/mTV series

38

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

Driver Version:
Version

Date

Description

V1.00

Jan/30/2016

Driver released

39

PLC Connection Guide

Barcode/Keyboard (USB/COM)
HMI Setting:
Parameters

Recommended

Options

PLC type

Barcode/Keyboard (USB/COM)

PLC I/F

RS232

RS232/485,USB

Baud rate

9600

9600~115200

Data bits

7,8

Parity

None

None, Even, Odd

Stop bits

Terminator

CR/LF

1,2
CR/LF, STX/ETX,
Other, None

Notes

When setting device properties, select [Barcode device] or [Keyboard] mode.

40

PLC Connection Guide

Device Address:
Bit/Word Device type

Format

Range

Memo

FLAG

DD

Flag

RESET

*Note 1

BARCODE 0

DD

Length

BARCODE 1

DD

1~255

String

RESULT

*Note 2

1. RESET: If set on, clears the data of BARCODE and RESULT, and clears FLAG to
OFF.
2. RESULT:Indicates the result of data reading.
The following values indicate:
0 : Waiting to read BARCODE.
1 : BARCODE is successfully read.
2 : Invalid BARCODE format.
3 : Exceeds the number of bytes specified in [Read byte limit].
4 : The Start Code of the data read does not match the setting.
5 : The Terminator of the data read does not match the setting.

41

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

2 RX

TXD

3 TX

RXD

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

2 RX

TXD

3 TX

RXD

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
FeMale

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

9 RX

TXD

6 TX

RXD

5 GND

GND

42

PLC Connection Guide

Driver Version:
Version

Date

V1.30

Oct/1/2010

Description

43

PLC Connection Guide

Baumuller
Website: http://www.baumuller.com/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Baumuller

PLC I/F

RS485 4W

Baud rate

19200

9600, 19200

Data bits

7 or 8

Parity

Even

Even, Odd, None

Stop bits

1 or 2

HMI sta. no.

PLC sta. no.

Defaults

PLC Setting:
Communication mode

RK 512 Protocol, 19200, 8, 1, Even

Device Address:
Bit/Word Device type

Format Range

DB0_bit ~
DB29_bit

DDDh

0 ~ 255f

DB0 ~ DB29

DDD

0 ~ 255

44

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

Baumuller servo RS422


9P D-Sub Male

1 RX-

1 TXD-

2 RX+

9 TXD+

3 TX-

5 RXD-

4 TX+

6 RXD+

5 GND

8 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

Baumuller servo RS422


9P D-Sub Male

7 RX-

1 TXD-

6 RX+

9 TXD+

9 TX-

5 RXD-

8 TX+

6 RXD+

5 GND

8 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

Baumuller servo RS422


9P D-Sub Male

1 RX-

1 RX-

1 TXD-

2 RX+

2 RX+

9 TXD+

3 TX-

3 TX-

5 RXD-

4 TX+

4 TX+

6 RXD+

5 GND

5 GND

8 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

Baumuller servo RS422


9P D-Sub Male

1 RX-

1 TXD-

2 RX+

9 TXD+

3 TX-

5 RXD-

4 TX+

6 RXD+

5 GND

8 GND

45

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

Baumuller servo RS422


9P D-Sub Male

1 RX-

1 TXD-

2 RX+

9 TXD+

3 TX-

5 RXD-

4 TX+

6 RXD+

5 GND

8 GND

Driver Version:
Version

Date

V1.10

Apr/17/2009

Description

46

PLC Connection Guide

Beckhoff ADS/AMS (Ethernet)


Supported Series: Twincat

HMI Setting:
Parameters

Recommended

Options

PLC type

Beckhoff ADS/AMS (Ethernet)

PLC I/F

Ethernet

Port no.

48898

ADS port

801

PLC sta. no.

801, 811, 821, 831

PLC Setting:
Step1.
Open TwinCat System Properties.

PLC Settings: Set HMI Name, AMS Net ID, and Address.
Ex:
HMI IP: 192.168.1.15
AMS Net ID: Must input 192.168.1.15.1.1
Address: 192.168.1.15
Name: Input HMI or any userdefined name.

47

Notes

PLC Connection Guide

Step2.
Simulate PLC on PC. 2 Twincat drivers must be installed as follows:

48

PLC Connection Guide

Step3.
The following commands can be utilized for Twincat PLC to output the parameters
observed.

49

PLC Connection Guide

PS. Twincat PLC


IX, QX, MX - Must output in BOOL type.
IW, QW, MW - Must output in UINT, WORD, and INT types.
ID, QD, MD - Must output in UDINT, DWORD, and DINT types.
This driver supports variables under STRUCT structure. Click [Data Type] to open
Structure Editor and create the same [Name] and [Data Type] as in Twincat PLC Control.
The standard data types include:
BOOL, WORD, INT, UINT, DINT, UDINT, REAL, DWORD, ARRAY

50

PLC Connection Guide

The syntax of Tag in Twincat software is: Tag Name +AT+%+Type,


as shown in the following figure.

Project -> Rebuild all

Step4. Set PLC IP in EasyBuilder.

51

PLC Connection Guide

Step5.
Click [Import Tag] button in EasyBuilder to open the TPY file compiled by Twincat PLC
Control.
Note: When using Beckhoff driver, if the TPY file cannot be imported, try download and
install MSXML 4.0 in Microsoft - Download Center.

Import tpy to EasyBuilder, the result is shown in the following figure.

52

PLC Connection Guide

Step6.
The following dialog box appears for users to select all or part of the data to import. A
reminding message is shown when import the same data repeatedly.
*EasyBuilder8000 does not support [Comment] setting.

53

PLC Connection Guide

Step7.
Download the project compiled in EasyBuilder to HMI.

Device address:
Bit/Word Device type

Format

Range

Memo

IX

DDDDDo

0 ~ 655357

o : Bit no.(0 ~ 7)

QX

DDDDDo

0 ~ 655357

o : Bit no.(0 ~ 7)

MX

DDDDDo

0 ~ 655357

o : Bit no.(0 ~ 7)

IW

DDDDD

0 ~ 65535

QW

DDDDD

0 ~ 65535

MW

DDDDD

0 ~ 65535

DW

ID

DDDDD

0 ~ 65535

DW

QD

DDDDD

0 ~ 65535

DW

MD

DDDDD

0 ~ 65535

Support Device Type:


data type

EasyBuilder data format

Bool

bit

Word

16-bit

DInt

16-bit BCD, Hex, Binary,


Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Signed

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary,


Unsigned

32-bit

String

ASCII input and ASCII display

Int
UInt
DWord

54

Memo

16-bit
16-bit
32-bit
32-bit

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Dec/08/2010

Driver released.

V1.10

Aug/24/2011

Extended address range up to 65535.

55

PLC Connection Guide

Beckhoff Embedded PC
Supported Series: Intel-CX10x0,CX50x0 and Twincat

HMI Setting:
Parameters

Recommended

Options

PLC type

Beckhoff Embedded PC

PLC I/F

Ethernet

Port no.

48898

ADS port

801

PLC sta. no.

801, 811, 821, 831

PLC Setting:
For Twincat:
a. Confirm PC IP address

56

Notes

PLC Connection Guide

b. Open Twincat, Set IP address 169.254.56.12.1.1

c. Use Twincat to build a Route Table to make sure the system is connected, if PLC
power turns OFF and then ON, please redo this step.
Note: when connected, if X is displayed, the connection succeeded.

57

PLC Connection Guide

d. Open EasyBuilder, set IP address, ADS port and Port no.

e. Run on line simulation.


Note: If the project is downloaded to HMI, please set HMI IP 169.254.56.12 identically
to Twincat IP address setting.
For CERHOST:
a. Execute CERHOST.exe to connect with PLC on PC.

b. Enter PLC IP and Password (default password: 1).

58

PLC Connection Guide

c. Succeeded to connect with PLC, click Start -> click Control Panel.

d. Click [Network and Dial-Up Connections] to display PLC device information; select
the PLC to check its IP.

e. Access PLC system settings, the default directory: \Hard Disk\System, execute
[TcAmsRemoteMgr].

59

PLC Connection Guide

f. AMS Net Id consists of 6 numbers, separated by .. The first 4 numbers stand for IP
and followed by 1.1. The figure below shows the AMS Net Id of Local Computer,
please enter PLC IP plus 1.1. Remote Computers shows the information of the HMI
to connect with. Click [Add] to add the HMI and click [OK] to finish setting.

g. Name: Device name.


AMS Net Id: The IP followed by 1.1 of the device to connect with.
Address: The IP address of the device to connect with.
Transport: The way of connection.
Slow Connection: As shown in the figure below.

60

PLC Connection Guide

h. Return to Control Panel; execute CX Configuration Tool to confirm PLC AMS Net
Id.

i. Confirm settings and click Start -> Reset PLC.

61

PLC Connection Guide

Building Data Structure


Step1. This driver supports variables under STRUCT structure. Click [Data Type] to open
Structure Editor and create the same [Name] and [Data Type] as in Twincat PLC Control.
The standard data types include:
BOOL, WORD, INT, UINT, DINT, UDINT, REAL, DWORD, ARRAY

62

PLC Connection Guide

The syntax of Tag in Twincat software is: Tag Name +AT+%+Type,


as shown in the following figure.

Step2.Project Rebuild all

Step3. Set PLC IP in EasyBuilder.

63

PLC Connection Guide

Step4.
Click [Import Tag] button in EasyBuilder to open the TPY file compiled by Twincat PLC
Control.
Note: When using Beckhoff driver, if the TPY file cannot be imported, try download and
install MSXML 4.0 in Microsoft - Download Center.

Import tpy to EasyBuilder, the result is shown in the following figure.

64

PLC Connection Guide

Step5.
The following dialog box appears for users to select all or part of the data to import. A
reminding message is shown when import the same data repeatedly.
*EasyBuilder8000 does not support [Comment] setting.

65

PLC Connection Guide

Step6.
Download the project compiled in EasyBuilder to HMI.

Device address:
Bit/Word Device type

Format

Range

Memo

IX

DDDDDo

0 ~ 655357

o : Bit no.(0 ~ 7)

QX

DDDDDo

0 ~ 655357

o : Bit no.(0 ~ 7)

MX

DDDDDo

0 ~ 655357

o : Bit no.(0 ~ 7)

IW

DDDDD

0 ~ 65535

QW

DDDDD

0 ~ 65535

MW

DDDDD

0 ~ 65535

DW

ID

DDDDD

0 ~ 65535

DW

QD

DDDDD

0 ~ 65535

DW

MD

DDDDD

0 ~ 65535

Support Device Type:


Data Type

EasyBuilder data format

Bool

bit

Word

16-bit

DInt

16-bit BCD, Hex, Binary,


Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Signed

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary,


Unsigned

32-bit

String

ASCII input and ASCII display

Int
UInt
DWord

66

Memo

16-bit
16-bit
32-bit
32-bit

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Apr/18/2011

Driver released.

V1.10

Aug/24/2011

Extended address range up to 65535.

67

PLC Connection Guide

Beckhoff TwinCAT 3 ADS/AMS (Ethernet)


Supported Series:
CX8000,CX90x0,CX1010,CP62xx,CX5010,CP62xx,CX1020,CX2020,CPxxxx,C6920,CX2
030,CPxxxx,CP6930,CX2040,C65xx,C69xx.
Website: http://infosys.beckhoff.com/

HMI Setting:
Parameters
PLC type

Recommended
Options
Beckhoff TwinCAT 3 ADS/AMS (Ethernet)

PLC I/F

Ethernet

Port no.

48898

PLC sta. no.

No need to set station no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

IX

DDDDDdd

0 ~ 6553515

QX

DDDDDdd

0 ~ 6553515

MX

DDDDDdd

0 ~ 6553515

IW

OOOOOO

0 ~ 65535

QW

DDDDD

0 ~ 65535

MW

DDDDD

0 ~ 65535

ID

DDDDD

0 ~ 65535

QD

DDDDD

0 ~ 65535

MD

DDDDD

0 ~ 65535

68

Memo

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Jun/07/2013

Driver released.

69

PLC Connection Guide

Beckhoff TwinCAT PLC (Ethernet) Free Tag


Names
Supported Series:
CX8000,CX90x0,CX1010,CP62xx,CX5010,CP62xx,CX1020,CX2020,CPxxxx,C6920,CX2
030,CPxxxx,CP6930,CX2040,C65xx,C69xx.
Website: http://infosys.beckhoff.com/

HMI Setting:
Parameters
PLC type

Recommended
Options
Beckhoff TwinCAT PLC (Ethernet) Free Tag Names

PLC I/F

Ethernet

Port no.

48898

PLC sta. no.

No need to set station no.

Support Device Type:


Data Type

EasyBuilder data format

Bool

bit

Word

16-bit

DInt

16-bit BCD, Hex, Binary,


Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Signed

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary,


Unsigned

32-bit

String

ASCII input and ASCII display

Int
UInt
DWord

70

Memo

16-bit
16-bit
32-bit
32-bit

Notes

PLC Connection Guide

How to Import Tags:


The files generated after compilation in TwinCAT2 and TwinCAT3 programming software
can be directly imported to EasyBuilder. The following steps explain how to import address
tags.
1. Go to System Parameter Settings and add Beckhoff TwinCAT PLC (Ethernet) Free
Tag Names to the device list. Click [Settings] and configure the PLC parameters.

2. Go to System Parameter Settings Tag Editor and click [Import].

71

PLC Connection Guide

3. Select PLC Software Version. The standard file type of TwinCAT 2.0 is .typ. The
standard file types of TwinCAT 3.0 are: .TcDUT, .TcGVL, and .TcPOU. The tags to be
imported can be selected by a tag name filter. Select the file type and then click
[Import]. The invalid address types will be displayed in Error Status field. Click [OK] to
leave.
Note. Tag name can not include ..

4. The Import successfully message will be shown upon completion.

72

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Dec/12/2014

Driver released.

73

PLC Connection Guide

Bosch Rexroth
HMI Setting:
Parameters

Recommended

PLC type

Bosch Rexroth

PLC I/F

RS232

Baud rate

115200

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

Support Device Type:


Data type

EasyBuilder data format

Bool

bit

Byte

8-bit

DInt

16-bit BCD, Hex, Binary,


Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Signed

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary,


Unsigned

32-bit

SInt
USInt
Word
Int
UInt
DWord

74

Memo

8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit

PLC Connection Guide

Import Tag:
1. Launch IndraWorks PLC software, click [Global_Variables], and edit the project.

2. Struct can be edited in [Data types] tab, and Global_varaibles can be edited in
[Resources] tab.
[Data types]

[Resources]

75

PLC Connection Guide

3.

After editing the project, click [Project] -> [Export] to export the tags.

4. You may select all, a part of, or a single file to export. Click [OK], enter the file name
and designate the directory to store the file.

76

PLC Connection Guide

5. Launch EasyBuilder, select Bosch Rexroth driver, and import the address tags. The
illegal addresses will be eliminated, and displayed in the [Error status] field. Click [OK]
to leave.

6. Import successfully message will be displayed when successfully import the address
tags.

77

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

PLC RS232 terminal

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

PLC RS232 terminal

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC RS232 terminal

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

PLC RS232 terminal

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

PLC RS232 terminal

9 RX

2 TX

6 TX

3 RX

5 GND

5 GND

78

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Nov/18/2014

Driver released.

79

PLC Connection Guide

CAN Bus CANopen Slave (for eMT3000, MT8091/8092XE, cMT3151only)


Supported series: CAN Bus 2.0a / CAN Bus 2.0B device.

HMI Setting:
Parameters

Recommended

PLC type

CAN Bus CANopen Slave

Node ID

1~127

Baud rate

250K

10K~1M

Online simulator

NO

Options

Notes

Extend address mode NO

Follow the steps to import EDS file.


Step 1. Object Dictionary Settings -> Setting

Step 2. Import EDS file.

80

PLC Connection Guide

Step 3. Select the EDS file to be imported.

Step 4. Successfully import EDS file.

Device Address:
Bit/Word
B

Device type
TxPDOn_BIT

Format
DDDNo

Range

Memo

100 ~ 99977

DDDPDO no.
Naddress (unitbyte).
obit no.

RxPDOn_BIT

DDDNo

100 ~ 99977

DDDPDO no.
Naddress (unitbyte).
obit no.

SDO_8bit_Bit

HHHHHHo

0 ~ FFFFFF7

HHHH(Index)+HH(Sub
-index)+o(Bit no)

SDO_16bit_Bit

HHHHHHdd

0 ~ HHHHHH15

HHHH(Index)+HH(Sub
-index)+dd(Bit no)

TxPDOn

DDDN

10 ~ 9997

DDDPDO no.
Naddress(unitbyte)

81

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

TxPDOn_Byte

DDDN

10 ~ 9997

DDDPDO no.
Naddress(unitbyte)

RxPDOn

DDDN

10 ~ 9997

DDDPDO no.
Naddress(unitbyte)

RxPDOn_Byte

DDDN

10 ~ 9997

DDDPDO no.
Naddress(unitbyte)

SDO_8bit

HHHHHH

0~FFFFFF

SDO_16bit

HHHHHH

0~FFFFFF

SDO_32bit

HHHHHH

0~FFFFFF

HHHH(Index)+HH(Sub
-index)

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000, MT8091/8092XE, cMT3151
CAN Bus 9P
D-Sub Female

CAN Device

7 CAN-

CAN -

8 CAN+

CAN+

5 GND

GND

To minimize signal reflection on the CAN bus network, termination resistors should be
installed at both ends of the network, as shown in the following figure. (eMT3070A has
built-in termination resistor, so it is not required for eMT3070A)

Demo Project Link:

82

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.40

Aug/20/2012

Add device type : SDO_8bit_Bit , SDO_16bit_Bit.

83

PLC Connection Guide

CAN Bus General, SAE J1939 (for eMT3000, MT8091/8092XE,


cMT3151only)

Supported series: CAN Bus SAE J1939.

HMI Setting:
Parameters
PLC type
Baud rate
Online simulator

Recommended

Options

CAN Bus General, SAE J1939


SAE J1939

General / SAE J1939

250K

10K~1M

NO

Extend address mode NO

Address Tags:
1. In EasyBuilder Pro add CAN Bus General, SAE J1939 driver.

84

Notes

PLC Connection Guide

2. Open Address Tag Library, select [User-defined tags] and then click [New].

3. Name: Enter the tag name.


PLC: Select the SAE J1939
Address type: Select Bit or Word.
Transmission rate:
If [Use the default] is selected, then HMI will wait for the reply from CAN device.
If [Request mode] is selected, then HMI will send polling packet.
After entering the above information, click [Settings].

85

PLC Connection Guide

4. Please set the following parameters according to the specification of the CAN device
used.

5. After building the tags click [Exit].

Device Address:
Bit/Word
B

Device type
DATA_Bit

Format

Memo

HHHHHHHHBb

H: ID
B: Byte position (1~8)
b: bit start position (1~8)
H: ID

DATA

HHHHHHHHBbNN

86

B: Byte position (1~8)


b: bit start position (1~8)
NN: bit no. (1~64)

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000, MT8091/8092XE, cMT3151
CAN Bus 9P
D-Sub Female

CAN Device

7 CAN-

CAN -

8 CAN+

CAN+

5 GND

GND

To minimize signal reflection on the CAN bus network, termination resistors should be
installed at both ends of the network, as shown in the following figure. (eMT3070A has
built-in termination resistor, so it is not required for eMT3070A)

Driver Version:
Version

Date

V1.30

Mar/15/2016

Description

87

PLC Connection Guide

CAS CI-1580A
Supported Series : CAS CI-1580A
Website : http://www.globalcas.com/bemarket/main/main.php

HMI Setting:
Parameters

Recommended

PLC type

CAS CI-1580A

PLC I/F

RS232

RS232/RS485 4W

Baud rate

9600

9600 ~ 115200

Data bits

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

1 ~ 99

Parameter1

0,1

Online simulator

Options

Notes

0:BBC not used / 1:BBC used

YES

PLC Setting:
0 No Parity (default)
F30 Parity bit

1 Odd Parity
2 Even Parity
0 115200 bps
1 76800 bps
2 57600 bps
3 38400 bps

F31 Baud rate

4 28800 bps
5 19200 bps
6 14400 bps
7 9600 bps
8 4800 bps
9 2400 bps
0 Unilateral transmission mode

F33 Communication Mode

1 Command mode
2 LCD mode
4 External display mode
88

PLC Connection Guide

F34 ID Number
F36 BCC selection mode

1~99 (default:1)
0 BCC not used
1 BCC used
0 kg

F40 Weight unit

1g
2 ton

Device Address:
Bit/Word Device type

Format

Range

Memo

CURRENT_WEIGHT_HEAD D

OL: OVER/UNDER LOAD

CURRENT_WEIGHT_HEAD D

ST: Stable indicator

CURRENT_WEIGHT_HEAD D

US: Unstable indicator

CURRENT_WEIGHT_HEAD D

NT: NETWEIGHT

CURRENT_WEIGHT_HEAD D

GS: GROSS WEIGHT

TARE

TARE_RESET

ZERO

W
W

HOLD
HOLD_RESET

PACKMODE_START

PACKMODE_STOP

KEY_TARE

CURRENT_WEIGHT

CURRENT_WEIGHT_UNIT

LOWEST_LIMIT

UPPER_LIMIT

SERIAL_NUMBER
CODE_NUMBER

PART_NUMBER

89

0:KG , 1:ton , 2:g (F40)

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

4,5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TXD

3 TX

2 RXD

5 GND

4,5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TXD

3 TX

2 RXD

5 GND

4,5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

4,5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

3 TXD

6 TX

2 RXD

5 GND

4,5 GND

90

PLC Connection Guide

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Female

1 RX-

9 TX-

2 RX+

8 TX+

3 TX-

7 RX-

4 TX+

6 RX+

5 GND

4,5 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Female

7 RX-

9 TX-

6 RX+

8 TX+

9 TX-

7 RX-

8 TX+

6 RX+

5 GND

4,5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Female

1 RX-

1 RX-

9 TX-

2 RX+

2 RX+

8 TX+

3 TX-

3 TX-

7 RX-

4 TX+

4 TX+

6 RX+

5 GND

5 GND

4,5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Female

1 RX-

9 TX-

2 RX+

8 TX+

3 TX-

7 RX-

4 TX+

6 RX+

5 GND

4,5 GND

91

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Female

1 RX-

9 TX-

2 RX+

8 TX+

3 TX-

7 RX-

4 TX+

6 RX+

5 GND

4,5 GND

Driver Version:
Version

Date

Description

V1.00

Dec/11/2015

Driver released.

92

PLC Connection Guide

CD MODBUS RTU
Supported Series : REVO-CL / REVO-M / REVO E / CD3000E / MULTIDRIVE / REVO-TC
/ REVO-PC
Website : http://www.cdautomation.com/

HMI Setting:
Parameters

Recommended

PLC type

CD MODBUS RTU

PLC I/F

RS485

RS232/RS485

Baud rate

9600

9600~115200

Data bits

7, 8

Parity

Even

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

0-255

Online simulator

YES

Options

Notes

Broadcast command YES

Extend address mode YES

[Address Range Limit]


The address range of 0x, 1x, and 0x_multi_coils device types can be set.
[Conversion]
The 3x_Double and 4x_Double address types are added. If [ABCD ->CDAB] check box is
selected, please select 3x_Double and 4x_Double address types.

93

PLC Connection Guide

Device Address:
Bit/Word Device type

Format

Range

Memo

0x

DDDDD

1 ~ 65535

Output bit

1x

DDDDD

1 ~ 65535

Input bit (read only)

3x_Bit

DDDDDdd 100 ~ 6553515

Input Register bit (read only)

4x_Bit

DDDDDdd 100 ~ 6553515

Output Register bit

B
B

6x_Bit
DDDDDdd 100 ~ 6553515
0x_multi_coils DDDDD
1 ~ 65535

Output Register bit


Write multiple coils

3x

DDDDD

1 ~ 65535

Input Register (read only)

3x_MAX1W

DDDDD

1 ~ 65535

Display 32 bits *Note1

DW

3x_MAX2W

DDDDD

1 ~ 65535

*Note1

4x

DDDDD

1 ~ 65535

Output Register

4x_MAX1W

DDDDD

1 ~ 65535

Display 32 bits *Note1

DW

4x_MAX2W

DDDDD

1 ~ 65535

*Note1

DW

5x

DDDDD

1 ~ 65535

4x double word swap

W
W

6x
3x_Double

DDDDD

1 ~ 65535

DDDDD

1 ~ 65535

4x single word write


*Note2

4x_Double

DDDDD

1 ~ 65535

*Note2

4x_32Bit

DDDDD

1 ~ 65535

Output Registerv *Note1

0x_single_coil DDDDD

1 ~ 65535

Note1: MAX1W and 4X_32Bit read/write 1 word for each package and display a 32-bits
value, whereas MAX2W reads/write 2 words for each package.
Note2: Go the [System Parameter Settings] -> [Device Properties] and click [Conversion]
to set the data format of device types 3x, 4x, 6x, 3x_double, 4x double.

94

PLC Connection Guide

NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost the
same as 4x except that 5x swaps double word.
If 4x contains the following information:
Address

Data in word

0x1

0x2

0x3

0x4

0x5

0x6

Data

0x20001

0x40003

0x60005

Address

Data in
word

0x2

0x1

0x4

0x3

0x6

0x5

...

For 5x, it will be:

Data

0x10002

Modbus RTU function code:


0x
0x01 Read coil
0x_multi_coils 0x01 Read coil

0x30004

...

0x50006

0x05 write single coil


0x0f write multiple coils

1x
0x02 Read discrete input
N/A for write operation
3x
0x04 Read input register
N/A for write operation
4x
0x03 Read holding register
0x10 write multiple registers
5x
0x03 Read holding register
0x10 write multiple registers
(Note: reverse word order in double word format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 write single register
(Note: 6x is limited to device of one word only)

95

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

96

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Female

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

Driver Version:
Version

Date

V2.30

Jun/24/2014

Description

97

PLC Connection Guide

CD MODBUS TCP/IP
Supported Series: REVO-CL / REVO-M / REVO E / CD3000E / MULTIDRIVE / REVO-TC /
REVO-PC
Website : http://www.cdautomation.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

CD MODBUS TCP/IP

PLC I/F

Ethernet

Port no.

502

PLC sta. no.

Notes

0~255

Device Address:
Bit/Word Device type

Format

Range

Memo

0x

DDDDD

1 ~ 65535

Output bit

1x

DDDDD

1 ~ 65535

Input bit (read only)

3x_bit

DDDDDdd

100 ~ 6553515

Input Register bit(read only)

4x_bit

DDDDDdd

100 ~ 6553515

Output Register bit

6x_bit

DDDDDdd

100 ~ 6553515

Output Register bit

0x_multi_coils DDDDD

1 ~ 65535

Write multiple coils

3x

DDDDD

1 ~ 65535

Input Register

4x

DDDDD

1 ~ 65535

Output Register

DW

5x

DDDDD

1 ~ 65535

4x double word swap

6x

DDDDD

1 ~ 65535

4x single word write

DW

3x_Double

DDDDD

1 ~ 65535

*Note1

DW

4X_Double
4x string
central
europe
4x string
central
europe (rev)

DDDDD

1 ~ 65535

*Note1

DDDDD

1 ~ 65535

Convert the Central Europe


ASCII to Unicode.

DDDDD

1 ~ 65535

98

PLC Connection Guide

Note1: Go the [System Parameter Settings] -> [Device Properties] and click [Conversion]
to set the data format of device types 3x, 4x, 6x, 3x_double, 4x double.

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V1.90

Feb/18/2014

Description

99

PLC Connection Guide

Change
Supported Series: Compressor controller
Website: http://www.sh-changjia.com/

HMI Setting:
Parameters

Recommended

PLC type

Change

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

1~6

Device Address:
Bit/Word Device type

Format

Range

Memo

CTL

DDD

0 ~ 5, 128, 150

Write only

DW

SET

DDD

0 ~ 57, 128

DW

STATUS

DD

1 ~ 20

Read only

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Change RS485 terminal

1 RX-

6 Data-

15 D-

2 RX+

9 Data+

16 D+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W

COM3 RS485 2W

Change RS485 terminal

9P D-Sub Female

9P D-Sub Female

7 RX-

4 Data-

15 D-

6 RX+

1 Data+

16 D+

5 GND

5 GND
100

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Change RS485 terminal

1 RX-

7 Data-

15 D-

2 RX+

8 Data+

16 D+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Change RS485 terminal

1 RX-

6 Data-

15 D-

2 RX+

9 Data+

16 D+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Change RS485 terminal

1 RX-

6 Data-

15 D-

2 RX+

9 Data+

16 D+

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

Change RS485 terminal

1 RX-

7 Data-

15 D-

2 RX+

8 Data+

16 D+

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Jan/19/2011

Driver released.

101

PLC Connection Guide

Cimon CM1-CP4A/ECO1A
Supported Series: Cimon CM1 series, CP4A module
Website: http://www.kdtsys.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Cimon CM1-CP4A/ECO1A

PLC I/F

RS232

Baud rate

38400

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

DDh

0 ~ 23f

DDh

0 ~ 23f

DDDh

0 ~ 511f

DDDh

0 ~ 127f

DDDh

0 ~ 127f

DDDh

0 ~ 127f

DDDh

0 ~ 102f

DDDh

0 ~ 102f

DDDD

0 ~ 4999

DD

0 ~ 99

TS

DDDD

0 ~ 1023

TC

DDDD

0 ~ 1023

CS

DDDD

0 ~ 1023

CC

DDDD

0 ~ 1023

102

Memo
0-1F Read Only

Read Only

Max. Range: 99

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

CM1-CP4A RS232 6P
RJ11 Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

CM1-CP4A RS232 6P
RJ11 Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

CM1-CP4A RS232 6P
RJ11 Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

CM1-CP4A RS232 6P
RJ11 Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

CM1-CP4A RS232 6P
RJ11 Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

5 GND

103

PLC Connection Guide

Driver Version:
Version

Date

V1.20

Nov/30/2009

Description

104

PLC Connection Guide

Cimon CM1-SC02A
Supported Series: Cimon CM series, SC02A module
Website: http://www.kdtsys.com

HMI Setting:
Parameters

Recommended

PLC type

Cimon CM1-SC02A

PLC I/F

RS232

Baud rate

38400

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

Device Address:
Bit/Word

Device type

Format

Range

DDh

0 ~ 23f

0-1F Read Only

DDh

0 ~ 23f

0-F Read Only

DDDh

0 ~ 511f

DDDh

0 ~ 127f

DDDh

0 ~ 127f

DDDh

0 ~ 127f

DDDh

0 ~ 102f

DDDh

0 ~ 102f

DDDD

0 ~ 4999

DD

0 ~ 99

TS

DDDD

0 ~ 1023

TC

DDDD

0 ~ 1023

CS

DDDD

0 ~ 1023

CC

DDDD

0 ~ 1023

105

Memo

Read Only

Max. Range: 99

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

CM1-SC02A RS232 9P
D-Sub Male

2 RX

8 RX

3 TD

3 TX

7 TX

2 RD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

CM1-SC02A RS232 9P
D-Sub Male

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

CM1-SC02A RS232 9P
D-Sub Male

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

CM1-SC02A RS232 9P
D-Sub Male

2 RX

6 RX

8 RX

3 TD

3 TX

4 TX

7 TX

2 RD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

CM1-SC02A RS232 9P
D-Sub Male

9 RX

3 TD

6 TX

2 RD

5 GND

5 GND

106

PLC Connection Guide

Driver Version:
Version

Date

V1.20

Nov/30/2009

Description

107

PLC Connection Guide

CoDeSys Automation Alliance


Supported Version: CoDeSys V2.2

HMI Setting:
Parameters
PLC type

Recommended
Options
CoDeSys Automation Alliance

PLC I/F

Ethernet

Port no.

1200

PLC sta. no.

No need to set station no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

IX

DDDDDdd

0 ~ 6553515

QX

DDDDDdd

0 ~ 6553515

MX

DDDDDdd

0 ~ 6553515

IW

OOOOOO

0 ~ 65535

QW

DDDDD

0 ~ 65535

MW

DDDDD

0 ~ 65535

ID

DDDDD

0 ~ 65535

QD

DDDDD

0 ~ 65535

MD

DDDDD

0 ~ 65535

Memo

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

108

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Jun/05/2013

Driver released.

109

PLC Connection Guide

CoDeSys V3 (Ethernet)
Supported series: LTI MOTION MO CM-3, MO CM-6
Website: http://www.lti-motion.com/

HMI Setting:
Parameters

Recommended Options

PLC type

CoDeSys V3 (Ethernet)

PLC I/F

Ethernet

Port no.

1740

Source port no.

1742

Notes
Use UDP

How to Import Tags:


1. Under MainTask set POU PLC_PRG.

110

PLC Connection Guide

2. Add Symbol configuration into Devices list.

3. Select PLC_RPG and its tag information is shown, compile the file.

4. A *.xml file is generated in the directory of the project.

111

PLC Connection Guide

5. In System Parameter Settings click [New] to add CoDeSys V3 (Ethernet) driver into
the device list and then click [Tag Manager].

6. In Tag Manager click Get tag -> Import Tag, and then select the tag file (.xml)
generated by the PLC software.

7. When the tags are imported successfully, click [Exit] to leave.

112

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Mar/15/2016

Driver released

113

PLC Connection Guide

Copley Digital Drives


Supported Series: Digital Servo Driver & Controllers, Xenus, Xenus Micro, Accelnet,
Accelnet Micro, Stepnet series.
Website: http://www.copleycontrols.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

Copley Digital Drives

PLC I/F

RS232

Baud rate

9600

9600~115200

Data bits

Parity

None

Even, Odd, None

Stop bits

HMI sta. no.

PLC sta. no.

Notes

0-127

Device Address:
Bit/Word Device type

Format

Range

Memo

Flash INT 16

HHH

0 ~ 999

For Register is INT16 or U16

RAM INT 16

HHH

0 ~ 999

For Register is INT16 or U16

Flash INT 32

HHH

0 ~ 999

For Register is INT32 or U32

RAM INT 32

HHH

0 ~ 999

For Register is INT32 or U32

Register

DDDD

0 ~ 2457

T_command

Reset

114

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P RJ11: Xenus, Xenus Micro, Accelnet, Stepnet
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 6P RJ11 Male

2 RX

8 RX

5 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

3, 4 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

PLC RS232 8P RJ45


Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

PLC RS232 8P RJ45

D-Sub Female

Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 6P RJ11 Male

2 RX

6 RX

8 RX

5 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

3, 4 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 6P RJ11 Male

9 RX

5 TXD

6 TX

2 RXD

5 GND

3, 4 GND

115

PLC Connection Guide

The following is the view from the soldering point of a cable.


Accelnet Micro:
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Accelnet Micro Panel


RS232 J5 Cable
Connector

2 RX

8 RX

29 TXD

3 TX

7 TX

14 RXD

5 GND

5 GND

15 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Accelnet Micro Panel


RS232 J5 Cable
Connector

2 RX

29 TXD

3 TX

14 RXD

5 GND

15 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

Accelnet Micro Panel

D-Sub Female

RS232 J5 Cable
Connector

2 RX

29 TXD

3 TX

14 RXD

5 GND

15 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Accelnet Micro Panel


RS232 J5 Cable
Connector

2 RX

6 RX

8 RX

29 TXD

3 TX

4 TX

7 TX

14 RXD

5 GND

5 GND

5 GND

15 GND

116

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

Accelnet Micro Panel


RS232 J5 Cable
Connector

9 RX

29 TXD

6 TX

14 RXD

5 GND

15 GND

Driver Version:
Version

Date

V1.20

Dec/30/2008

Description

117

PLC Connection Guide

CO-TRUST CTH300-H (Ethernet)


Supported Series: CO-TRUST CTH300-H35
Website: http://www.co-trust.com/cn/index.php

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

CO-TRUST CTH300-H (Ethernet)

PLC I/F

Ethernet

Port no.

1024

PLC sta. no.

Use UDP

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

VW_Bit

DDDDDo

0 ~ 102397

V Memory Bit Address

DDDDo

0 ~ 40957

SCR

SM

DDDDo

0 ~ 40957

Special Memory

T_Bit

DDDD

0 ~ 1023

Timer

C_Bit

DDDD

0 ~ 1023

Counter

DBnBit

FFFDDDDDo 0 ~ 255655357

Byte

VB

DDDDD

0 ~ 10239

VW

DDDDD

0 ~ 10239

V Memory

VW_Odd

DDDDD

0 ~ 10239

V Memory

VW_String

DDDDD

0 ~ 10239

String

VW_String_Odd

DDDDD

0 ~ 10239

String

DW

VD

DDDDD

0 ~ 10239

V Memory Double

DW

VD_Odd

DDDDD

0 ~ 10239

Word
V
Memory Double

DW

VD_String

DDDDD

0 ~ 10239

Word
String

DW

VD_String_Odd

DDDDD

0 ~ 10239

String

Byte

MB

DDDDD

0 ~ 10239

Byte Memory

MW

DDDDD

0 ~ 10239

Word Memory

MW_Odd

DDDDD

0 ~ 10239

Word Memory

DW

MD

DDDDD

0 ~ 10239

Word Memory

118

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

Byte

SB

DDDDD

0 ~ 10239

SCR

SW

DDDDD

0 ~ 10239

SCR

DW

SD

DDDDD

0 ~ 10239

SCR

Byte

SMB

DDDDD

0 ~ 10239

Special Memory

SMW

DDDDD

0 ~ 10239

Special Memory

DW

SMD

DDDDD

0 ~ 10239

Special Memory

DDD

0 ~ 1023

Timer

DDD

0 ~ 1023

Counter

Byte

DBBn

FFFDDDDD

0 ~ 65535

DBn

FFFDDDDD

0 ~ 65535

DW

DBDn

FFFDDDDD

0 ~ 65535

DBn_STRINGCHAR FFFDDDDD

0 ~ 65535

Double Word and floating point value must use VD device type.

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Jan/04/2016

Driver released.

119

PLC Connection Guide

CO-TRUST CTH300-H PPI


Supported Series: CO-TRUST CTH300-H35
Website: http://www.co-trust.com/cn/index.php

HMI Setting:
Parameters

Recommended

PLC type

CO-TRUST CTH300-H PPI

PLC I/F

RS485 2W

RS485 2W

Baud rate

9600

9600, 19200, 187.5K

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1, 2

Turn around delay (ms)

ACK delay time (ms)

30

PLC sta. no.

Online simulator

Options

Notes

Only MT6000/8000V2 support


baud rate 187.5 K

1 ~ 126
YES

Extend address mode YES

Broadcast command NO

PLC Setting:
PLC setting

PLC sta. no. can not be the same as HMI sta. no.

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

VW_Bit

DDDDDo

0 ~ 102397

V Memory Bit Address

DDDDo

0 ~ 40957

SCR

SM

DDDDo

0 ~ 40957

Special Memory

T_Bit

DDDD

0 ~ 1023

Timer

C_Bit

DDDD

0 ~ 1023

Counter

DBnBit

FFFDDDDDo 0 ~ 255655357
120

PLC Connection Guide

Bit/Word

Device type

Format

Range

Byte

VB

DDDDD

0 ~ 10239

VW

DDDDD

0 ~ 10239

V Memory

VW_Odd

DDDDD

0 ~ 10239

V Memory

VW_String

DDDDD

0 ~ 10239

String

VW_String_Odd

DDDDD

0 ~ 10239

String

DW

VD

DDDDD

0 ~ 10239

V Memory Double

DW

VD_Odd

DDDDD

0 ~ 10239

Word
V
Memory Double

DW

VD_String

DDDDD

0 ~ 10239

Word
String

DW

VD_String_Odd

DDDDD

0 ~ 10239

String

Byte

MB

DDDDD

0 ~ 10239

Byte Memory

MW

DDDDD

0 ~ 10239

Word Memory

MW_Odd

DDDDD

0 ~ 10239

Word Memory

DW

MD

DDDDD

0 ~ 10239

Word Memory

Byte

SB

DDDDD

0 ~ 10239

SCR

SW

DDDDD

0 ~ 10239

SCR

DW

SD

DDDDD

0 ~ 10239

SCR

Byte

SMB

DDDDD

0 ~ 10239

Special Memory

SMW

DDDDD

0 ~ 10239

Special Memory

DW

SMD

DDDDD

0 ~ 10239

Special Memory

DDD

0 ~ 1023

Timer

DDD

0 ~ 1023

Counter

Byte

DBBn

FFFDDDDD

0 ~ 65535

DBn

FFFDDDDD

0 ~ 65535

DW

DBDn

FFFDDDDD

0 ~ 65535

DBn_STRINGCHAR FFFDDDDD

0 ~ 65535

Double Word and floating point value must use VD device type.

121

Memo

PLC Connection Guide

Multi-HMIs-Multi-PLCs Communication Setting:

For S7-200 PLC, Multi-HMIs-Multi-PLCs communication can be achieved using S7/200


PPI driver, please refer to the settings below.
IN EasyBuilder COM Port Settings, two important parameters must be set:

1. [High station address (HSA)]:


Setting Max. Station Number of HMI in PPI network.
For the effectiveness of system operation, it is highly recommended that the HMI station
number starts from zero and go on sequentially. If there are 4 HMI in PPI network, set
station no. from 0~3, and [High station address (HSA)] to 3.
Set HMI station number in [System Parameters] / [Model] / [HMI station no.]:

122

PLC Connection Guide

2. [Gap update factor(GUF)]:


The condition to pass a Token. In PPI network only HMI can hold a Token, PLC can only
be controlled.
When the HMI that holds Token communicates with PLC for a number of times that equals
to the value set here, HMI will pass the Token (control of PLC) to the next HMI. For
example, if GUF is set to 1, HMI will pass the control of PLC to the next HMI when read
or write the value in an address.
If GUF is set to a bigger value, the HMI that holds Token will control the PLC for a longer
time and therefore the Token wont be passed to another HMI and cause failure in
communicating with PLC.
A complete communication means HMI reads / writes PLC value for one time.

Note:

HMI sta. no. can not be the same as PLC sta. no.
Highly recommended that HMI sta. no. starts from 0 and go on sequentially for the
effectiveness of operation.
Available for EasyBuilder8000 V4.50 and later.

123

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

8 D-

6 RX+

1 Data+

3 D+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

124

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

5 GND

5 GND

Driver Version
Version

Date

Description

V1.00

Oct/12/2015

Driver released.

125

PLC Connection Guide

CROUZET M3 (FBD)
HMI Setting:
Parameters

Recommended

PLC type

CROUZET M3 (FBD)

PLC I/F

RS232

Baud rate

115200

Data bits

Parity

Even

Stop bits

PLC sta. no.

Options

Notes

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

Memo

DD

1 ~ 99

Input

SLI_Bit

DDh

10 ~ 24f

Serial link input

SLO_Bit

DDh

250 ~ 48f

Serial link output (read only)

State

State in PLC (read only)

AI

DD

1 ~ 99

Analogy input (default: 1 ~ 4)

SL_IN

DD

1 ~ 24

Serial link input

SL_OUT

DD

25 ~ 48

Serial link output (read only)

Time

1~6

Time & Day*

Order

Command** (write only)

* address 1: second, address 2 : minute, address 3 : hour , address 4 : day, address 5 :


month, address 6 : year. The value range for Year is 0~99, entering 0 represents year
2000, entering 99 represents year 2099.
** run mode write 2, stop mode write 1.

126

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)

2 RX

2 TD

3 TX

3 RD

5 GND

5 GND

7 RTS

4 DTR

cMT/mTV series
COM1 RS232 9P
D-Sub Female

CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

0V External Power Supply


+5V External Power Supply

4 DTR

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)

2 RX

2 TD

3 TX

3 RD

5 GND

5 GND

7 RTS

4 DTR

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)

2 RX

2 TD

3 TX

3 RD

5 GND

5 GND

7 RTS

4 DTR

127

PLC Connection Guide

MTx050i/MTx050iP/MTx050iE Series
COM1 RS232 9P
D-Sub Male

CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)

9 RX

2 TD

6 TX

3 RD

5 GND

5 GND

4 TX+

4 DTR

(3m serial link cable)


Note: Please use 3m serial link cable
(Accessories from Millenium 3) and extension
cable (as shown) to communicate with HMI
series.

Driver Version:
Version

Date

Description

V1.10

Oct/26/2010

V1.20

Mar/29/2012

V1.30

May/14/2012

Add device type : State, Time, Order


Time entering is now allowed.

V1.60

Jun/05/2013

Modify device type from IA to AI.

128

PLC Connection Guide

CROUZET M3 (LAD)
HMI Setting:
Parameters

Recommended

PLC type

CROUZET M3 (LAD)

PLC I/F

RS232

Baud rate

115200

Data bits

Parity

Even

Stop bits

PLC sta. no.

Options

Notes

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

Memo

DD

1 ~ 99

Input (default: 1 ~ 4)

DD

1 ~ 99

Output (default: 1 ~ 4)

DD

1 ~ 28

Relay

SLI_Bit

DDh

10 ~ 24f

Serial link input

SLO_Bit

DDh

250 ~ 48f

Serial link output (read only)

State

State in PLC (read only)

DD

1 ~ 12

Timer

DD

1 ~ 16

Counter

AI

DD

1 ~ 99

Analogy input (default: 1 ~ 4)

SL_IN

DD

1 ~ 24

Serial link input

SL_OUT

DD

25 ~ 48

Serial link output (read only)

Time

1~6

Time & Day *

Order

Command (write only) **

* address 1: second, address 2 : minute, address 3 : hour , address 4 : day, address 5 :


month, address 6 : year .The value range for Year is 0~99, entering 0 represents year
2000, entering 99 represents year 2099.
** run mode write 2, stop mode write 1.
129

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)

2 RX

2 TD

3 TX

3 RD

5 GND

5 GND

7 RTS

4 DTR

cMT/mTV series
COM1 RS232 9P
D-Sub Female

CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

0V External Power Supply


+5V External Power Supply

4 DTR

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)

2 RX

2 TD

3 TX

3 RD

5 GND

5 GND

7 RTS

4 DTR

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)

2 RX

2 TD

3 TX

3 RD

5 GND

5 GND

7 RTS

4 DTR

130

PLC Connection Guide

MTx050i/MTx050iP/MTx050iE Series
COM1 RS232 9P
D-Sub Male

CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)

9 RX

2 TD

6 TX

3 RD

5 GND

5 GND

4 TX+

4 DTR

(3m serial link cable)


Note: Please use 3m serial link cable
(Accessories from Millenium 3) and extension
cable (as shown) to communicate with HMI
series.

Driver Version:
Version

Date

Description

V1.20

Oct/26/2010

V1.30

Mar/30/2012

V1.40

May/14/2012

Add device type : State, Time, Order


Time entering is now allowed.

V1.70

Jun/05/2013

Modify device type from IA to AI.

131

PLC Connection Guide

Danfoss ECL Apex20


Website: http://www.danfoss.com/

HMI Setting:
Parameters

Recommended

PLC type

Danfoss ECL Apex20

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

Memo

Device Address:
Bit/Word Device type

Format

Range

Flag

DDDD

0 ~ 8191

Output

DDDD

0 ~ 1023

Input

DDDD

0 ~ 1023

Reg_Bit

DDDDDdd

0 ~ 1638331

DW

Register

DDDDD

0 ~ 16383

DW

Counter

DDDD

0 ~ 1599

DW

Timer

DDDD

0 ~ 1599

DW

Reg_Float

DDDDD

0 ~ 16383

dd: Bit no. (00 ~ 31)

Support 32-bit float format

EasyBuilder device address range may differ from PLC extended mode, please refer to
EasyBuilder address range as above.

132

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

ECL Apex20 Controller


RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

ECL Apex20 Controller


RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

ECL Apex20 Controller


RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

ECL Apex20 Controller


RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

133

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

ECL Apex20 Controller


RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

ECL Apex20 Controller


Port#1 / Port#0

1 RX-

6 Data-

11 / 29

2 RX+

9 Data+

12 / 28

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

ECL Apex20 Controller


Port#1 / Port#0

7 RX-

4 Data-

11 / 29

6 RX+

1 Data+

12 / 28

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

ECL Apex20 Controller


Port#1 / Port#0

1 RX-

7 Data-

11 / 29

2 RX+

8 Data+

12 / 28

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

ECL Apex20 Controller


Port#1 / Port#0

1 RX-

6 Data-

11 / 29

2 RX+

9 Data+

12 / 28

5 GND

5 GND
134

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

ECL Apex20 Controller


Port#1 / Port#0

1 RX-

6 Data-

11 / 29

2 RX+

9 Data+

12 / 28

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

ECL Apex20 Controller


Port#1 / Port#0

1 RX-

7 Data-

11 / 29

2 RX+

8 Data+

12 / 28

5 GND

5 GND

Driver Version:
Version

Date

V1.40

OCT/06/2008

Description

135

PLC Connection Guide

Danfoss ECL Apex20 (Ethernet)


Website: http://www.danfoss.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

Danfoss ECL Apex20 (Ethernet)

PLC I/F

Ethernet

Port no.

5050

PLC sta. no.

Notes

Device Address:
Bit/Word Device type

Format

Range

Flag

DDDD

0 ~ 8191

Output

DDDD

0 ~ 1023

Input

DDDD

0 ~ 1023

Reg_Bit

DDDDDdd

0 ~ 1638331

Register

DDDDD

0 ~ 16383

Counter

DDDD

0 ~ 1599

Timer

DDDD

0 ~ 1599

Reg_Float

DDDDD

0 ~ 16383

Memo

dd: Bit no. (00 ~ 31)

Support 32-bit float format

EasyBuilder device address range may differ from PLC extended mode, please refer to
EasyBuilder address range as above.

136

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V1.10

Jan/10/2011

Description

137

PLC Connection Guide

Danfoss FC Series
Supported Series: FC051, FC100, FC200, FC300, VLT Micro Driver.
Website: http://www.danfoss.com/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Danfoss FC Series

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Format

Range

Memo

Device Address:
Bit/Word Device type
W

Parameter

09

DDDD

0 ~ 9999

Set Parameter

DW

Reference

10

0~1

Control Bus Reference

DW

Para_Index

11

DDDDDD

0 ~ 999999

Set Parameter(Index)

Para_Index 310.1=31001, Para_Index310.0=31000

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FC RS485 terminal

1 RX-

6 Data-

69 D-

2 RX+

9 Data+

68 D+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W

COM3 RS485 2W

FC RS485 terminal

9P D-Sub Female

9P D-Sub Female

7 RX-

4 Data-

69 D-

6 RX+

1 Data+

68 D+

5 GND

5 GND
138

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FC RS485 terminal

1 RX-

7 Data-

69 D-

2 RX+

8 Data+

68 D+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FC RS485 terminal

1 RX-

6 Data-

69 D-

2 RX+

9 Data+

68 D+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FC RS485 terminal

1 RX-

6 Data-

69 D-

2 RX+

9 Data+

68 D+

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

FC RS485 terminal

1 RX-

7 Data-

69 D-

2 RX+

8 Data+

68 D+

5 GND

5 GND

*RW100 set PCD1 Control Word of station 1


*RW101 read PCD1 Status Word of station 1
*RW102 set PCD2 Control Word of station 2
*RW103 read PCD2 Status Word of station 2
*RW104 set PCD3 Control Word of station 3
*RW105 read PCD3 Status Word of station 3
*RW106 set PCD4 Control Word of station 4
*RW107 read PCD4 Status Word of station 4

139

PLC Connection Guide

Driver Version:
Version

Date

V1.10

Jan/14/2010

Description

140

PLC Connection Guide

Danfoss VLT2800 Series


Supported Series: VLT2800 series
Website: http://www.danfoss.com/

HMI Setting:
Parameters

Recommended

PLC type

Danfoss VLT2800 Series

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Options

Notes

0-126

According to PLC

PLC Setting:
Communication mode

9600, Even, 8, 1 (default)

Device Address:
Bit/Word
DW

Device type

Format

Range

Memo

Parameter

DDDD

0 ~ 2000

Set Parameter

Reference

0~1

Control Bus Reference

The control word register is set according to the station number.


If the station number is 1, the control word will be RW100 and RW101; if the station
number is 2, the control word will be RW102 and RW103, and so on.

141

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

69 D-

2 RX+

9 Data+

68 D+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

7 RX-

4 Data-

69 D-

6 RX+

1 Data+

68 D+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

7 Data-

69 D-

2 RX+

8 Data+

68 D+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

69 D-

2 RX+

9 Data+

68 D+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

69 D-

2 RX+

9 Data+

68 D+

5 GND

5 GND

142

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

1 RX-

7 Data-

69 D-

2 RX+

8 Data+

68 D+

5 GND

5 GND

Driver Version:
Version

Date

V1.10

Dec/30/2008

Description

143

PLC Connection Guide

DELTA DVP
Supported Series: DELTA DVP series
Website: http://www.deltadriver.com

HMI Setting:
Parameters

Recommended

Options

PLC type

DELTA DVP

PLC I/F

RS232

RS232, RS485

Baud rate

9600

9600, 19200

Data bits

7, 8

Parity

Even

Even, Odd, None

Stop bits

PLC sta. no.

0-255

Notes

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word Device type

Format

Range

Memo

OOOOO

0 ~ 23417 (octal)

Input

OOOOO

0 ~ 23417 (octal)

Output

DDDDD

0 ~ 65536

Auxiliary Relay

DDDD

0 ~ 9999

Step Relay

DDDD

0 ~ 9999

Timer

DDDD

0 ~ 9999

Counter

TV_Bit

DDDDdd 0 ~ 999915

Timer

TV

DDDD

0 ~ 9999

Timer

CV

DDD

0 ~ 127

Counter

CV2

DDD

200 ~ 254

Double Word Counter

DDDD

0 ~ 9999

Data Register

144

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

8 RX

5 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

3/8 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

5 TXD

3 TX

4 RXD

5 GND

3/8 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

5 TXD

3 TX

4 RXD

5 GND

3/8 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 8P Mini-DIN
Male

2 RX

6 RX

8 RX

5 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

3/8 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

9 RX

5 TXD

6 TX

4 RXD

5 GND

3/8 GND
View from the
soldering point
of a cable.

145

PLC Connection Guide

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W port

1 RX-

6 Data-

2 Data-

2 RX+

9 Data+

1 Data+

5 GND

5 GND

3 GND

COM2 RS485 2W

COM3 RS485 2W

RS485 terminal

9P D-Sub Female

9P D-Sub Female

7 RX-

4 Data-

2 Data-

6 RX+

1 Data+

1 Data+

5 GND

5 GND

3 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

7 Data-

2 Data-

2 RX+

8 Data+

1 Data+

5 GND

9 GND

3 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

2 Data-

2 RX+

9 Data+

1 Data+

5 GND

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

2 Data-

2 RX+

9 Data+

1 Data+

5 GND

5 GND

3 GND

146

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

1 RX-

7 Data-

2 Data-

2 RX+

8 Data+

1 Data+

5 GND

5 GND

3 GND

Driver Version:
Version

Date

V1.20

Dec/30/2008

Description

147

PLC Connection Guide

DELTA DVPEN01-SL (Ethernet)


Website: http://www.deltadriver.com

HMI Setting:
Parameters

Recommended

Options

PLC type

DELTA DVPEN01-SL (Ethernet)

PLC I/F

Ethernet

Port no.

502

PLC sta. no.

Notes

Device Address:
Bit/Word Device type

Format

Range

C_Bit

DDD

0 ~ 255

DDDD

0 ~ 4095

DDDD

0 ~ 1023

T_Bit

DDD

0 ~ 255

OOO

0 ~ 571

OOO

0 ~ 571

DDD

0 ~ 199

DW

C_32Bit

DDD

200 ~ 255

DDDDD

0 ~ 11999

DDD

0 ~ 255

148

Memo

PLC Connection Guide

PLC Setting:
1. Communication Setting
Add a new program, click File > New, enter the Program Title and File Name, and select
the correct controller type. Click Setting to configure the communication parameters. Click
OK to confirm the setting. The communication with PLC starts.

2. Transfer Setup
Click Communication and select PC<=>(PLC | HPP), on Transfer Setup dialog box,
select the needed parameters for upload or download, and click OK to start the action.

149

PLC Connection Guide

3. Auto-Search Ethernet Module


Click Auto-Search Ethernet Module to find the PLC modules on the same network. As
shown in the following figure, DVPEN01-SL, IP address 192.168.1.139 is found.

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Jun/11/2012

Driver released.

V1.10

Aug/20/2012

Add device type : C_32Bit.

150

PLC Connection Guide

DL-BCM Server
Website: http://www.hzdelin.com

HMI Setting:
Parameters

Recommended

Options

PLC type

DL-BCM Server

PLC I/F

RS232

RS232, RS485

Baud rate

9600

9600~115200

Data bits

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

0-31

Notes

Device Address:
Bit/Word

Device type

Format

Range

LB

dddd

0 ~ 9998

LW

dddd

0 ~ 9998

RW

ddddd

0 ~ 55536

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND
RTS
CTS

151

short

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P

COM2 RS232 9P

COM3 RS232

RS232 9P D-Sub

D-Sub Female

D-Sub Female

9P D-Sub Male

FeMale

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND
RTS
CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

RS232 9P D-Sub

D-Sub Female

FeMale

9 RX

TXD

6 TX

RXD

5 GND

GND
RTS
CTS

152

short

PLC Connection Guide

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

COM2 RS485 2W

COM3 RS485 2W

RS485 2W 9P D-Sub

9P D-Sub Female

9P D-Sub Female

Male

7 RX-

4 Data-

8 D-

6 RX+

1 Data+

3 D+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

153

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Dec/8/2008

Driver released

154

PLC Connection Guide

DL/T645 CHUANG HONG


Website: http://www.cw180.com

HMI Setting:
Parameters

Recommended

Options

PLC type

DL/T645 CHUANG HONG

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word Device type
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W

B621
B622
B623
zero phase
B611
B612
B613
B631
B632
B633
B630
B641
B642
B643
B640
A-apparentT
B-apparentT
C-apparentT
T-apparentT
B650

Format

Range

0~1

D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D

0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
155

Memo

PLC Connection Guide

Bit/Word Device type


W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W

B651
B652
B653
9010
9020
9110
9120
9130
9140
9150
9160
9410
9420
9510
9520
9530
9540
9550
9560
9810
9820
9910
9920
9930
9940
9950
9960
A010
A020
A110
A120
A130
A140
A150
A160
A410
A420
A510
A520
A530

Format

Range

D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D

0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
156

Memo

PLC Connection Guide

Bit/Word Device type


W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W

A540
A550
A560
A810
A820
A910
A920
A930
A940
A950
A960
B010
B020
B110
B120
B130
B140
B150
B160
B410
B420
B510
B520
B530
B540
B550
B560
B810
B820
B910
B920
B930
B940
B950
B960
B210
B211
B212
B213
B214

Format

Range

D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D

0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
157

Memo

PLC Connection Guide

Bit/Word Device type


W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W

B310
B311
B312
B313
B320
B321
B322
B323
B330
B331
B332
B333
B340
B341
B342
B343
C010
C011
C020
C021
C022
C030
C031
C032
C033
C034
C111
C112
C113
C114
C115
C116
C117
C118
C119
C11A
C211
C212
C310
C311

Format

Range

D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D

0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
158

Memo

PLC Connection Guide

Bit/Word Device type


W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W

C312
C313
C314
C320
C321
C322
C330
C331
C332
C340
C341
C342
C3A0
C3A1
C3A2
C410
C411
C41E
C510
C511
B634
B635

Format

Range

D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D

0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1

159

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

13 RS485B1

2 RX+

9 Data+

12 RS485A1

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

7 RX-

4 Data-

13 RS485B1

6 RX+

1 Data+

12 RS485A1

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

7 Data-

13 RS485B1

2 RX+

8 Data+

12 RS485A1

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

13 RS485B1

2 RX+

9 Data+

12 RS485A1

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

13 RS485B1

2 RX+

9 Data+

12 RS485A1

5 GND

5 GND

160

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

1 RX-

7 Data-

13 RS485B1

2 RX+

8 Data+

12 RS485A1

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Apr/13/2011

Driver released.

161

PLC Connection Guide

DL/T645 Standard
Website: http://www.cw180.com

HMI Setting:
Parameters

Recommended

PLC type

DL/T645 Standard

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Options

PLC Setting:

162

Notes

PLC Connection Guide

System Tag:
LW-10700 (4 words)

DLT_645 operator (COM 1)

LW-10704 (4 words)

DLT_645 password (COM 1)

LW-10708 (6 words)

DLT_645 address (COM 1)

LW-10715 (4 words)

DLT_645 operator (COM 2)

LW-10719 (4 words)

DLT_645 password (COM 2)

LW-10723 (6 words)

DLT_645 address (COM 2)

LW-10730 (4 words)

DLT_645 operator (COM 3)

LW-10734 (4 words)

DLT_645 password (COM 3)

LW-10738 (6 words)

DLT_645 address (COM 3)

Device Address:
Bit/Word Device type
W

Data

Format

Range

Memo

HHHHHHHH 0 ~ 6FFFFFF

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND
163

PLC Connection Guide

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Apr/14/2011

Driver released.

164

PLC Connection Guide

DL/T645-2007 Standard
Website: http://www.cw180.com

HMI Setting:
Parameters

Recommended

Options

PLC type

DL/T645-2007 Standard

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

PLC Setting:

165

Notes

PLC Connection Guide

System Tag:
LW-10700 (4 words)

DLT_645 operator (COM 1)

LW-10704 (4 words)

DLT_645 password (COM 1)

LW-10708 (6 words)

DLT_645 address (COM 1)

LW-10715 (4 words)

DLT_645 operator (COM 2)

LW-10719 (4 words)

DLT_645 password (COM 2)

LW-10723 (6 words)

DLT_645 address (COM 2)

LW-10730 (4 words)

DLT_645 operator (COM 3)

LW-10734 (4 words)

DLT_645 password (COM 3)

LW-10738 (6 words)

DLT_645 address (COM 3)

Device Address:
Bit/Word Device type
W

Data

Format

Range

Memo

HHHHHHHH 0 ~ 6FFFFFF

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND
166

PLC Connection Guide

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

Driver Version:
Version

Date

V1.20

Jul/27/2015

Description

167

PLC Connection Guide

ELSIST MODBUS ASCII


Supported Series: SlimLine & Netsyst controllers RS232/485
Website: http://www.elsist.it

HMI Setting:
Parameters

Recommended

Options

PLC type

ELSIST MODBUS ASCII

PLC I/F

RS485

RS232/RS485

Baud rate

9600

9600~115200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1,2

PLC sta. no.

0-255

Notes

PLC Setting:
Communication mode

Modbus ASCII protocol

Device Address:
Bit/Word Device type

Format

Range

Memo

1x

DDDDD

1 ~ 65535

Input bit (read only)

%MX

DDDDD

1 ~ 65535

0x01 read coil


0x05 write single coil

3x_Bit

DDDDDdd

100 ~ 6553515

Input register bit (read only)

%MW_Bit

DDDDDdd

100 ~ 6553515

0x03 read holding register


0x06 write single register

3x

DDDDD

1 ~ 65535

Input register (read only)

%MW

DDDDD

1 ~ 65535

0x03 read holding register


0x10 write multiple register

6x

DDDDD

1 ~ 65535

168

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

COMx RS232 RJ45


Male

2 RX

8 RX

6 TXD

3 TX

7 TX

5 RXD

5 GND

5 GND

4 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

COMx RS232 RJ45


Male

2 RX

6 TXD

3 TX

5 RXD

5 GND

4 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

COMx RS232 RJ45


Male

2 RX

6 TXD

3 TX

5 RXD

5 GND

4 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

COMx RS232 RJ45


Male

2 RX

6 RX

8 RX

6 TXD

3 TX

4 TX

7 TX

5 RXD

5 GND

5 GND

5 GND

4 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

COMx RS232 RJ45


Male

9 RX

6 TXD

6 TX

5 RXD

5 GND

4 GND

169

PLC Connection Guide

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W
3-Way TB

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

3 GND

COM2 RS485 2W

COM3 RS485 2W

RS485 2W

9P D-Sub Female

9P D-Sub Female

3-Way TB

7 RX-

4 Data-

2 D-

6 RX+

1 Data+

1 D+

5 GND

5 GND

3 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W
3-Way TB

1 RX-

7 Data-

2 D-

2 RX+

8 Data+

1 D+

5 GND

9 GND

3 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W
3-Way TB

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W
3-Way TB

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

3 GND

170

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W
3-Way TB

1 RX-

7 Data-

2 D-

2 RX+

8 Data+

1 D+

5 GND

5 GND

3 GND

Driver Version:
Version

Date

V1.50

Feb/18/2014

Description

171

PLC Connection Guide

ELSIST MODBUS RTU


Supported Series : SlimLine & Netsyst controllers RS232/485
Website : http://www.elsist.it

HMI Setting:
Parameters

Recommended

PLC type

ELSIST MODBUS ASCII

PLC I/F

RS485

RS232/RS485

Baud rate

9600

9600~115200

Data bits

7, 8

Parity

Even

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

0-255

Online simulator

YES

Options

Notes

Broadcast command YES

Extend address mode YES

PLC Setting:
Communication mode

Modbus RTU protocol

Device Address:
Bit/Word Device type

Format

Range

%MX

DDDDD

0 ~ 65535

%MX_Bit

DDDDDdd 0 ~ 6553515

0x03 Read holding register


0x06 write single register

%MW

DDDDD

0 ~ 6553515

0x03 Read holding register


0x10 write multiple registers

%MWD

DDDDD

0 ~ 6553515

0x03 Read holding register


0x10 write multiple registers

172

Memo
0x01 Read coil
0x05 write single coil

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

COMx RS232 RJ45


Male

2 RX

8 RX

6 TXD

3 TX

7 TX

5 RXD

5 GND

5 GND

4 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

COMx RS232 RJ45


Male

2 RX

6 TXD

3 TX

5 RXD

5 GND

4 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

COMx RS232 RJ45


Male

2 RX

6 TXD

3 TX

5 RXD

5 GND

4 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

COMx RS232 RJ45


Male

2 RX

6 RX

8 RX

6 TXD

3 TX

4 TX

7 TX

5 RXD

5 GND

5 GND

5 GND

4 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

COMx RS232 RJ45


Male

9 RX

6 TXD

6 TX

5 RXD

5 GND

4 GND

173

PLC Connection Guide

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W
3-Way TB

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

3 GND

COM2 RS485 2W

COM3 RS485 2W

RS485 2W

9P D-Sub Female

9P D-Sub Female

3-Way TB

7 RX-

4 Data-

2 D-

6 RX+

1 Data+

1 D+

5 GND

5 GND

3 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W
3-Way TB

1 RX-

7 Data-

2 D-

2 RX+

8 Data+

1 D+

5 GND

9 GND

3 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W
3-Way TB

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W
3-Way TB

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

3 GND

174

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W
3-Way TB

1 RX-

7 Data-

2 D-

2 RX+

8 Data+

1 D+

5 GND

5 GND

3 GND

Driver Version:
Version

Date

V2.30

Jun/24/2014

Description

175

PLC Connection Guide

ELSIST MODBUS TCP/IP


Supported Series: SlimLine & Netsyst controllers Ethernet TCP/IP
Website: http://www.elsist.it

HMI Setting:
Parameters

Recommended

Options

PLC type

ELSIST MODBUS TCP/IP

PLC I/F

Ethernet

Port no.

502

PLC sta. no.

Notes

0~255

PLC Setting:
Communication mode

Modbus TCP/IP

Device Address:
Bit/Word Device type

Format

Range

Memo

%MX

DDDDD

0 ~ 65535

0x01 Read coil


0x05 write single coil

%MW_Bit

DDDDDdd

0 ~ 6553515

0x03 Read holding register


0x06 write single register

%MW

DDDDD

0 ~ 65535

0x03 Read holding register


0x10 write multiple registers

DW

%MWD

DDDDD

0 ~ 65535

0x03 Read holding register


0x10 write multiple registers

176

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V1.90

Feb/18/2014

Description

177

PLC Connection Guide

EMERSON Charge Module


Website: http://www.emersonnetworkpower.com.cn/Pages/Default.aspx

HMI Setting:
Parameters

Recommended

Options

PLC type

EMERSON Charge Module

PLC I/F

RS-232

Baud rate

9600

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

Float_Point_Forced

0~1

Average_Point_Forced D

0~1

Switch_Status

0~1

Manual_Status

0~1

Protect_Status

0~1

Failure_Status

0~1

Preset_Voltage

0~1

Preset_Percent

0~1

Output_Voltage

0~1

Output_Current

0~1

High_Limit

0~1

Low_Limit

0~1

Float_Point_Setting

0~1

Average_Point_Setting D

0~1

178

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 terminal

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 terminal

2 RX

TXD

3 TX

RXD

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 terminal

2 RX

TXD

3 TX

RXD

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 terminal

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 terminal

9 RX

TXD

6 TX

RXD

5 GND

GND

179

PLC Connection Guide

Driver Version:
Version

Date

V1.00

Mar/3/2009

Description

180

PLC Connection Guide

EMERSON ControlWave (Ethernet) Free Tag


Names
Supported Series: EMERSON ControlWave MICRO
Website: http://www2.emersonprocess.com/en-US/Pages/Home.aspx

HMI Setting:
Parameters

Recommended

Options

PLC type

EMERSON ControlWave (Ethernet) Free Tag Names Use UDP

PLC I/F

Ethernet

Port no.

1234

Source port no.

1234

181

Notes

PLC Connection Guide

Support Device Type:


Data type

EasyBuilder data format

Bool

bit

Byte

8-bit

DInt

16-bit BCD, Hex, Binary,


Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Signed

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary,


Unsigned

32-bit

SInt
USInt
Word
Int
UInt
DWord

Memo

8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit

* For device types: DWord / DINT / UDINT / Real , error may occur if the value exceeds 7
digits (million).

182

PLC Connection Guide

PLC Setting:
1. Under Global Variables create the tags, a tag name with over 20 words can affect
communicaiton, please avoid it.

2. Open the program from Programs -> OpenBSI Tool -> Common Tools -> Signal
Extractor.

183

PLC Connection Guide

3. Browse for the file name in Load File field, and then the Output File field will
automatically generate the SIG file name. In IEC-61131 Options group box, deselect
Datatype conversion enable and Output MSD Values check boxes, and then click
Start to generate the file for tag import.

4. Import the tags after adding the driver in EasyBuilder.

184

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Nov/12/2015

Driver released

185

PLC Connection Guide

EMERSON PLC EC20


Supported Series: Emerson PLC EC20 Series. (Modbus RTU Protocol)

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

EMERSON PLC EC20

PLC I/F

RS232

Baud rate

9600

9600, 19200, 115200

Data bits

7 or 8

Parity

Even

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

0-255

PLC Setting:
Communication mode

Modbus RTU protocol

Device Address:
Bit/Word Device type

Format

Range

Memo

OOO

0 ~ 377

0000-02550

OOO

0 ~ 377

1200-01455

DDDD

0 ~ 1999

2000-3999

SM

DDD

0~ 255

4400-4655

DDD

0 ~ 991

6000-6991

DDD

0 ~ 255

8000-8255

DDD

0 ~ 255

9200-9455

DDDD

0 ~ 7999

0000-7999

SD

DDD

0 ~ 255

8000-8255

DD

0 ~ 15

8500-8515

DDD

0 ~ 255

9000-9255

DDD

0 ~ 199

9500-9699

DW

C_Double

DDD

200 ~ 255

9700-9811

DW

D_Double

DDDD

0 ~ 7998

0000-7999

186

0000-0255

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Emerson EC20 COM1


terminal

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Emerson EC20 COM1


terminal

2 RX

TXD

3 TX

RXD

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

Emerson EC20 COM1


terminal

2 RX

TXD

3 TX

RXD

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Emerson EC20 COM1


terminal

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

Emerson EC20 COM1


terminal

9 RX

TXD

6 TX

RXD

5 GND

GND

187

PLC Connection Guide

Driver Version:
Version

Date

V1.10

Dec/30/2008

Description

188

PLC Connection Guide

Emotiontek MCU Controller


Supported Series: Emotiontek MCU-XP/XP2 Controller
Website: http://emotiontek.com/sub/index.php

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Emotiontek MCU Controller

PLC I/F

RS232

RS232/RS485 2W

Baud rate

38400

9600 ~ 115200

Data bits

7,8

Parity

None

None,Odd,Even

Stop bits

1,2

PLC sta. no.

0-255

PLC Setting:
Protocol type

1,4

Device Address:
Bit/Word

Device type

Format

Range

X_Bit

Hh

0 ~ 5f

Y_Bit

Hh

0 ~ 4f

F_Bit

Dh

0 ~ 9f

M_Bit

DDDh

0 ~ 199f

T_Bit

Dh

0 ~ 0f

C_Bit

Dh

0 ~ 0f

0~5

0~4

0~9

DDD

0 ~ 199

TP

DD

0 ~ 15

TC

DD

0 ~ 15
189

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

CP

DD

0 ~ 15

CC

DD

0 ~ 15

DW

PD_X

DD

0 ~ 99

DW

PD_Y

DD

0 ~ 99

DW

FD

0~9

DW

DD

0~9

DW

LD

DDDD

0 ~ 1999

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

190

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

7 D+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

8 D-

6 RX+

1 Data+

7 D+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

7 D+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

7 D+

5 GND

5 GND

5 GND

191

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

7 D+

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

7 D+

5 GND

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Sep/04/2015

Driver released

192

PLC Connection Guide

FATEK FB/FBs/B1/B1z Series


Supported Series: FATEK FB/FBs/B1/B1z series, FB MC series, and FB MA series need
FB-DTBR converter.
Website: http://www.fatek.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

FATEK FB/FBs/B1/B1z Series

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Port no.

500

Notes

RS232/RS485/Ethernet

0-255

Must match PLC port setting.


Ethernet only.

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word
B

Device type

Format

Range

Memo

DDDD

0 ~ 9999

Input

DDDD

0 ~ 9999

Output

DDDD

0 ~ 9999

Internal Relay

DDDD

0 ~ 9999

Step Relay

DDDD

0 ~ 9999

Timer

DDDD

0 ~ 9999

PLC_MODE

Counter
PLC mode

R_Bit

DDDDdd

0 ~ 999915

D_Bit

DDDDdd

0 ~ 999915

RT

DDDD

0 ~ 9999

Timer Register

RC

DDDD

0 ~ 9999

Counter Register

DDDD

0 ~ 9999

Data Register

DDDD

0 ~ 9999

Data Register

DRT

DDDD

0 ~ 9999

Double Word Timer Register

DRC

DDD

200 ~ 255

Double Word Counter Register

193

PLC Connection Guide

Bit/Word
W

Device type

Format

Range

WX

DDDD

0 ~ 9999

Memo
Input Word

WY

DDDD

0 ~ 9999

Output Word

WM

DDDD

0 ~ 9999

Internal Relay Word

WS

DDDD

0 ~ 9999

FR

DDDD

0 ~ 9999

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 4P Mini-DIN: FBs Port0
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

FBs RS232 4P Mini-DIN


Male

2 RX

8 RX

3 TX

3 TX

7 TX

4 RX

5 GND

5 GND

2 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

FBs RS232 4P Mini-DIN


Male

2 RX

3 TX

3 TX

4 RX

5 GND

2 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

FBs RS232 4P Mini-DIN


Male

2 RX

3 TX

3 TX

4 RX

5 GND

2 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

FBs RS232 4P Mini-DIN


Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

4 RX

5 GND

5 GND

5 GND

2 GND

194

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

FBs RS232 4P Mini-DIN


Male

9 RX

3 TX

6 TX

4 RX

5 GND

2 GND
View from the
soldering point
of a cable.

The following is the view from the soldering point of a cable.


9P D-Sub to 9P D-Sub: FBs communication module
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

FBs communication
module RS232 9P
D-Sub Male

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

FBs communication
module RS232 9P
D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

FBs communication

D-Sub Female

module RS232 9P
D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

195

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

FBs communication
module RS232 9P
D-Sub Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

FBs communication

D-Sub Female

module RS232 9P
D-Sub Male

9 RX

2 TX

6 TX

3 RX

5 GND

5 GND

The following is the view from the soldering point of a cable.


FBs communication module 3P Terminal Block
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FBs communication
module 3P Terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W

COM3 RS485 2W

FBs communication

9P D-Sub Female

9P D-Sub Female

module 3P Terminal

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FBs communication
module 3P Terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND
196

PLC Connection Guide

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FBs communication
module 3P Terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FBs communication
module 3P Terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

FBs communication
module 3P Terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

The following is the view from the soldering point of a cable.


9P D-Sub to 15P D-Sub: CPU Port
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

FB CPU Port RS232


15P D-Sub Male

2 RX

8 RX

2 TX

3 TX

7 TX

1 RX

5 GND

5 GND

6 GND
3 RTS
4 CTS

197

short

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

FB CPU Port RS232


15P D-Sub Male

2 RX

2 TX

3 TX

1 RX

5 GND

6 GND
3 RTS
4 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

FB CPU Port RS232


15P D-Sub Male

2 RX

2 TX

3 TX

1 RX

5 GND

6 GND
3 RTS
4 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P

COM2 RS232 9P

COM3 RS232 9P

FB CPU Port RS232

D-Sub Female

D-Sub Female

D-Sub Male

15P D-Sub Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

1 RX

5 GND

5 GND

5 GND

6 GND
3 RTS
4 CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

FB CPU Port RS232

D-Sub Female

15P D-Sub Male

9 RX

2 TX

6 TX

1 RX

5 GND

6 GND
3 RTS
4 CTS

198

short

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 15P D-Sub: CPU Port RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FB CPU Port RS485


2W 15P D-Sub Male

1 RX-

6 Data-

7 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

FB CPU Port RS485


2W 15P D-Sub Male

7 RX-

4 Data-

7 D-

6 RX+

1 Data+

5 D+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FB CPU Port RS485


2W 15P D-Sub Male

1 RX-

7 Data-

7 D-

2 RX+

8 Data+

5 D+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FB CPU Port RS485


2W 15P D-Sub Male

1 RX-

6 Data-

7 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

FB CPU Port RS485


2W 15P D-Sub Male

1 RX-

6 Data-

7 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

199

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

FB CPU Port RS485


2W 15P D-Sub Male

1 RX-

7 Data-

7 D-

2 RX+

8 Data+

5 D+

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.60

Feb/17/2011

R_Bit, D_Bit and WS address types are added.

V1.70

Nov/29/2011

FR address types are added.

200

PLC Connection Guide

Fuji NB Series
Website: http://www.fujielectric.com/fcs/index.html

HMI Setting:
Parameters

Recommended

PLC type

Fuji NB Series

PLC I/F

RS485 4W

Baud rate

19200

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Options

Notes

PLC Setting:
Communication mode

NITP Protocol / PLC Password (default is 0)

Device Address:
Bit/Word Device type

Format

Range

Memo

HHH

0 ~ 7ff

Output Relay

HHH

0 ~ 3ff

Input Relay

HHH

0 ~ fff

Internal Relay

HHH

0 ~ fff

Latch Relay

HH

0 - ff

Counter

M_Spe

HHHH

0 ~ 81ff

Special Relay

HHH

0 ~ 1ff

Timer

TV

HHH

0 ~ 3ff

Timer value

CV

HHH

0 ~ 3ff

Counter value

HHHH

0 ~ 1fff

Data Register

D_Spe

HHHH

0 ~ 81ff

Special Register

201

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

Fuji NB Series RS422


8P RJ45 Male

1 RX-

4 TX-

2 RX+

3 TX+

3 TX-

6 RX-

4 TX+

5 RX+

5 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

Fuji NB Series RS422


8P RJ45 Male

7 RX-

4 TX-

6 RX+

3 TX+

9 TX-

6 RX-

8 TX+

5 RX+

5 GND
MT8000iE/MT8000XE series except MT8050iE
COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

Fuji NB Series RS422


8P RJ45 Male

1 RX-

1 RX-

4 TX-

2 RX+

2 RX+

3 TX+

3 TX-

3 TX-

6 RX-

4 TX+

4 TX+

5 RX+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

Fuji NB Series RS422


8P RJ45 Male

1 RX-

4 TX-

2 RX+

3 TX+

3 TX-

6 RX-

4 TX+

5 RX+

5 GND

202

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

Fuji NB Series RS422


8P RJ45 Male

1 RX-

4 TX-

2 RX+

3 TX+

3 TX-

6 RX-

4 TX+

5 RX+

5 GND

Driver Version:
Version

Date

V1.10

May/05/2009

Description

203

PLC Connection Guide

Fuji SPH2000 (Ethernet)


Supported Series:Fuji SPH2000 series PLC.
Website: http://www.fujielectric.com/fcs/index.html

HMI Setting:
Parameters

Recommended Options

PLC type

Fuji SPH2000 (Ethernet)

PLC I/F

Ethernet

Port no.

507

Notes

251 ~ 65531

When setting port number, please add the offset 251. As shown below, the value in the
software is 1024, then the port number should be: 1024+251=1275.

204

PLC Connection Guide

Device Address:
Bit/Word Device type

Format

Range

Memo

DDDDDDh

10 ~ 238511f

DDD(Slot) / DDD(word) / h(bit)

DDDDDDh

10 ~ 238511f

DDD(Slot) / DDD(word) / h(bit)

DDDDh

0 ~ 8191f

DDDDh

0 ~ 4095f

SM

DDDh

0 ~ 511f

DD.DD

0 ~ 99.99

WX

DDDDDD

1 ~ 238511

DDD(Slot) / DDD(word)

WY

DDDDDD

1 ~ 238511

DDD(Slot) / DDD(word)

WM

DDDD

0 ~ 8191

DW

DM

DDDDD

0 ~ 16382

WL

DDDD

0 ~ 4095

DW

DL

DDDD

0 ~ 8190

WSM

DDD

0 ~ 511

DW

DSM

DDD

0 ~ 510

WS

DD

0 ~ 99

DW

DX

DDDDDD

1000 ~ 238511 DDD(Slot) / DDD(word)

DW

DY

DDDDDD

1000 ~ 238511 DDD(Slot) / DDD(word)

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V1.10

May/04/2015

Description
Added registersDX,DY
205

PLC Connection Guide

GE Fanuc 0i MD
Website: http://www.fanucfa.com/welcome_worldwide/

HMI Setting:
Parameters

Recommended

PLC type

GE Fanuc 0i MD

PLC I/F

RS232

Baud rate

19200

Data bits

Parity

Even

Stop bits

PLC sta. no.

On-line simulation

Options

Notes

YES

PLC Setting:
Reader/Puncher interface (2ch.) is used for touch panel interface.
External touch panel interface, S/N: A02B-0320-J685, for Power Mate Series.

Device Address:
Bit/Word

Device type

Format

Range

DDDDo

0 ~ 11277

DDDDo

0 ~ 11277

DDDo

0 ~ 9997

DDDDo

0 ~ 99997

D_Bit

DDDDo

0 ~ 99997

R_Bit

DDDDo

0 ~ 94997

DDDD

0 ~ 9499

Must be a multiple of 2

DDDD

0 ~ 5199

Must be a multiple of 4

D_Byte

DDDD

0 ~ 9999

R_Byte

DDDD

0 ~ 9499

DDDD

0 ~ 9999

Must be a multiple of 2

DDDD

0 ~ 9499

Must be a multiple of 2

206

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 20P JD36B or


JD54 Female

2 RX

8 RX

11 TX

3 TX

7 TX

1 RX

5 GND

5 GND

8(JD36) 4(JD54) GND


15 RTS
05 CTS

short

03 DR
07 CD

short

13 ER
cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 20P JD36B or


JD54 Female

2 RX

11 TX

3 TX

1 RX

5 GND

8(JD36) 4(JD54) GND


15 RTS
05 CTS

short

03 DR
07 CD

short

13 ER
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 20P JD36B or


JD54 Female

2 RX

11 TX

3 TX

1 RX

5 GND

8(JD36) 4(JD54) GND


15 RTS
05 CTS

short

03 DR
07 CD
13 ER

207

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232
9P D-Sub Male

RS232 20P JD36B or


JD54 Female

2 RX

6 RX

8 RX

11 TX

3 TX

4 TX

7 TX

1 RX

5 GND

5 GND

5 GND

8(JD36) 4(JD54) GND


15 RTS
05 CTS

short

03 DR
07 CD

short

13 ER
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 20P JD36B or


JD54 Female

9 RX

11 TX

6 TX

1 RX

5 GND

8(JD36) 4(JD54) GND


15 RTS
05 CTS

short

03 DR
07 CD
13 ER

Driver Version:
Version

Date

Description

V1.00

May/16/2011

Driver released.

208

short

PLC Connection Guide

GE Fanuc CMM
Website: http://www.ge.com

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

GE Fanuc CMM

PLC I/F

RS232

RS232/RS485

Baud rate

19200

9600,19200,38400,5
7600,115200

Data bits

7,8

Parity

Odd

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

0-255

Must set to 8 for this


protocol

Does not apply to this


protocol

PLC Setting:
Refer to the related PLC manual.

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDD

1 ~ 10000

Input relay

DDDDD

1 ~ 10000

Output relay

DDDDD

1 ~ 10000

Auxiliary relay

DDDD

1 ~ 7680

DDD

1 ~ 256

SA

DDD

1 ~ 128

SB

DDD

1 ~ 128

SC

DDD

1 ~ 128

DDD

1 ~ 128

AI

DDDDD

1 ~ 10000

Analog input register

AQ

DDDDD

1 ~ 10000

Analog output register

DDDDD

1 ~ 32640

Data register

209

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
CPU Port 90-30/VersaMax
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

90-30/VersaMax RS485
4W 15P D-Sub Male

1 RX-

12 SDA

2 RX+

13 SDB

5 GND

7 GND

3 TX-

10 RDA

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

short
short
short

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

90-30/VersaMax RS485
4W 15P D-Sub Male

7 RX-

12 SDA

6 RX+

13 SDB

5 GND

7 GND

9 TX-

10 RDA

8 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

210

short
short
short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

90-30/VersaMax RS485
4W 15P D-Sub Male

1 RX-

1 RX-

12 SDA

2 RX+

2 RX+

13 SDB

5 GND

5 GND

7 GND

3 TX-

3 TX-

10 RDA

4 TX+

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

short
short
short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

90-30/VersaMax RS485
4W 15P D-Sub Male

1 RX-

12 SDA

2 RX+

13 SDB

5 GND

7 GND

3 TX-

10 RDA

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

211

short
short
short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

90-30/VersaMax RS485
4W 15P D-Sub Male

1 RX-

12 SDA

2 RX+

13 SDB

5 GND

7 GND

3 TX-

10 RDA

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

short
short
short

The following is the view from the soldering point of a cable.


CPU Port (90-30 series CPU351/352/363/364)
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

90-30/90-70 series
RS232 6P RJ11 Male

2 RX

8 RX

2 TX

3 TX

7 TX

5 RX

5 GND

5 GND

3 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

90-30/90-70 series
RS232 6P RJ11 Male

2 RX

2 TX

3 TX

5 RX

5 GND

3 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

90-30/90-70 series
RS232 6P RJ11 Male

2 RX

2 TX

3 TX

5 RX

5 GND

3 GND

212

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

90-30/90-70 series
RS232 6P RJ11 Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

5 RX

5 GND

5 GND

5 GND

3 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

90-30/90-70 series
RS232 6P RJ11 Male

9 RX

2 TX

6 TX

5 RX

5 GND

3 GND

The following is the view from the soldering point of a cable.


CPU Port (VersaMax series CPU001/002/005/E05)
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

VersaMax series RS232


9P D-Sub Male

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P

VersaMax series RS232

D-Sub Female

9P D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

VersaMax series RS232


9P D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

213

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

VersaMax series RS232


9P D-Sub Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

VersaMax series RS232


9P D-Sub Male

9 RX

2 TX

6 TX

3 RX

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Jul/09/2009

Driver released.

214

PLC Connection Guide

GE Fanuc RX3i
Website: http://www.ge.com

HMI Setting:
Parameters

Recommended

Options

PLC type

GE Fanuc RX3i

PLC I/F

RS232

RS232, RS485

Baud rate

19200

1200~115200

Data bits

Parity

Odd

None, Even, Odd

Stop bits

1 or 2

SNP ID

0~255 (None)

Notes

PLC Setting:
Port Mode

SNP Slave

Device Address:
Bit/Word

Device type

Format

Range

DDDDD

1 ~ 32768

DDDDD

1 ~ 32768

DDDDD

1 ~ 32768

DDDDD

1 ~ 32768

DDDDD

1 ~ 32768

SA

DDDDD

1 ~ 32768

SB

DDDDD

1 ~ 32768

SC

DDDDD

1 ~ 32768

DDDDD

1 ~ 32768

AI

DDDDD

1 ~ 32768

AQ

DDDDD

1 ~ 32768

DDDDD

1 ~ 32768

215

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

GE Fanuc RX3i COM1


RS232 9P D-Sub Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

GE Fanuc RX3i COM1


RS232 9P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

GE Fanuc RX3i COM1


RS232 9P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

GE Fanuc RX3i COM1


RS232 9P D-Sub Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

GE Fanuc RX3i COM1


RS232 9P D-Sub Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

5 GND

216

PLC Connection Guide

The following is the view from the soldering point of a cable.


GE Fanuc RX3i COM2
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

GE Fanuc RX3i COM2


RS232 15P D-Sub Male

1 RX-

12 SDA

2 RX+

13 SDB

5 GND

7 GND

3 TX-

10 RDA

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

short
short
short

cMT/mTV series
COM1 RS485 4W
9P D-Sub Female

GE Fanuc RX3i COM2


RS232 15P D-Sub Male

7 RX-

12 SDA

6 RX+

13 SDB

5 GND

7 GND

9 TX-

10 RDA

8 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

217

short
short
short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

GE Fanuc RX3i COM2


RS232 15P D-Sub Male

1 RX-

1 RX-

12 SDA

2 RX+

2 RX+

13 SDB

5 GND

5 GND

7 GND

3 TX-

3 TX-

10 RDA

4 TX+

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

short
short
short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

GE Fanuc RX3i COM2


RS232 15P D-Sub Male

1 RX-

12 SDA

2 RX+

13 SDB

5 GND

7 GND

3 TX-

10 RDA

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

218

short
short
short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

GE Fanuc RX3i COM2


RS232 15P D-Sub Male

1 RX-

12 SDA

2 RX+

13 SDB

5 GND

7 GND

3 TX-

10 RDA

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

Driver Version:
Version

Date

V1.30

Aug/13/2015

Description

219

short
short
short

PLC Connection Guide

GE Fanuc RX3i (Ethernet)


Website: http://www.ge.com

HMI Setting:
Parameters

Recommended

Options

PLC type

GE Fanuc RX3i (Ethernet)

PLC I/F

Ethernet

Port no.

18245

Notes

Device Address:
Bit/Word

Device type

Format

Range

DDDDD

1 ~ 32768

DDDDD

1 ~ 32768

DDDDD

1 ~ 32768

DDDD

1 ~ 7680

DDDD

1 ~ 1024

SA

DDD

1 ~ 128

SB

DDD

1 ~ 128

SC

DDD

1 ~ 128

DDD

1 ~ 128

AI

DDDDD

1 ~ 32640

AQ

DDDDD

1 ~ 32640

DDDDD

1 ~ 32640

220

Memo

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V1.00

Aug/12/2015

Description

221

PLC Connection Guide

GE Fanuc Series 90-30 (Ethernet)


Supported Series: GE 90-30 series, CPU model 374plus.

HMI Setting:
Parameters

Recommended

Options

PLC type

GE Fanuc Series 90-30 (Ethernet)

PLC I/F

Ethernet

Port no.

18245

PLC sta. no.

Notes

1~99

Device Address:
Bit/Word

Device type

Format

Range

I_bit

DDDDD

1 ~ 32768

Q_bit

DDDDD

1 ~ 32768

M_bit

DDDDD

1 ~ 32768

G_bit

DDDDD

1 ~ 32768

T_bit

DDDDD

1 ~ 32768

SA_bit

DDDDD

1 ~ 32768

Read Only

SB_bit

DDDDD

1 ~ 32768

Read Only

SC_bit

DDDDD

1 ~ 32768

Read Only

S_bit

DDDDD

1 ~ 32768

Read Only

R_bit

DDDDD

1 ~ 32768

DDDDD

1 ~ 32753

DDDDD

1 ~ 32753

DDDDD

1 ~ 32753

DDDDD

1 ~ 32753

DDDD

1 ~ 1024

SA

DDDDD

1 ~ 32753

Read only, the rule is same as above

SB

DDDDD

1 ~ 32753

Read only, the rule is same as above

222

Memo

Address increment by 8 words, ex: I1,


I9, I17, I25..
The rule is same as above, ex:Q1, Q9,
Q17
The rule is same as above, ex:M1,
M9, M17..
The rule is same as above, ex:G1, G9,
G17
The rule is same as above, ex:T1, T9,
T17.

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

SC

DDDDD

1 ~ 32753

Read only, the rule is same as above

DDDDD

1 ~ 32753

Read only, the rule is same as above

DDDDD

1 ~ 32768

AI

DDDDD

1 ~ 32768

AQ

DDDDD

1 ~ 32768

DDDDDDD 1 ~ 5000000

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.70

Apr/09/2010

V1.80

Nov/09/2011

Add device type : R_bit

V1.90

Jan/17/2012

Add device type : W

223

PLC Connection Guide

GE Fanuc SNP-X
Supported Series: GE Fanuc 90-30 , 90 micro and VersaMax series PLC , 90-70 series
with CMM711 module.
Website: http://www.ge.com

HMI Setting:
Parameters

Recommended

Options

PLC type

GE Fanuc SNP-X

PLC I/F

RS485 4W

RS232/RS485

Baud rate

19200

9600 ~ 115200

Data bits

7, 8

Parity

Odd

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

0-255

Notes

Must set to 8 for this protocol

Does not apply to this protocol

PLC Setting:
Refer to the related PLC manual.

Device Address:
Bit/Word Device type Format

Range

Memo

DDDDD

1 ~ 10000

Input relay

DDDDD

1 ~ 10000

Output relay

DDDDD

1 ~ 10000

Auxiliary relay

DDDD

1 ~ 7680

DDD

1 ~ 256

SA

DDD

1 ~ 128

SB

DDD

1 ~ 128

SC

DDD

1 ~ 128

DDD

1 ~ 128

R_bit

DDDDDdd

1 ~ 3264015

Data register bit

AI

DDDDD

1 ~ 10000

Analog input register

AQ

DDDDD

1 ~ 10000

Analog output register

DDDDD

1 ~ 32640

Data register

224

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
CPU Port (90-30/VersaMax)
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

90-30/VersaMax RS422
15P D-Sub Male

1 RX-

12 SDA

2 RX+

13 SDB

5 GND

7 GND

3 TX-

10 RDA

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

short
short
short

cMT/mTV series
COM1 RS485 4W
9P D-Sub Female

90-30/VersaMax RS422
15P D-Sub Male

7 RX-

12 SDA

6 RX+

13 SDB

5 GND

7 GND

9 TX-

10 RDA

8 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

225

short
short
short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

90-30/VersaMax RS422
15P D-Sub Male

1 RX-

1 RX-

12 SDA

2 RX+

2 RX+

13 SDB

5 GND

5 GND

7 GND

3 TX-

3 TX-

10 RDA

4 TX+

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

short
short
short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

90-30/VersaMax RS422
15P D-Sub Male

1 RX-

12 SDA

2 RX+

13 SDB

5 GND

7 GND

3 TX-

10 RDA

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

226

short
short
short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

90-30/VersaMax RS422
15P D-Sub Male

1 RX-

12 SDA

2 RX+

13 SDB

5 GND

7 GND

3 TX-

10 RDA

4 TX+

11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB

short
short
short

The following is the view from the soldering point of a cable.


CPU Port (90-30 series CPU351/352/363/364)
eMT3000 series
COM1 RS232 9P

COM3 RS232 9P

90-30/90-70 series

D-Sub Female

D-Sub Female

RS232 6P RJ11 Male

2 RX

8 RX

2 TX

3 TX

7 TX

5 RX

5 GND

5 GND

3 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

90-30/90-70 series
RS232 6P RJ11 Male

2 RX

2 TX

3 TX

5 RX

5 GND

3 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

90-30/90-70 series
RS232 6P RJ11 Male

2 RX

2 TX

3 TX

5 RX

5 GND

3 GND

227

PLC Connection Guide

MT6000/8000 series excepts MT6050i/MT8050i/MT8050iE


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

90-30/90-70 series
RS232 6P RJ11 Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

5 RX

5 GND

5 GND

5 GND

3 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

90-30/90-70 series
RS232 6P RJ11 Male

9 RX

2 TX

6 TX

5 RX

5 GND

3 GND

The following is the view from the soldering point of a cable.


CPU Port (VersaMax series CPU001/002/005/E05)
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

VersaMax series RS232


8P RJ45 Male

2 RX

8 RX

4 TX

3 TX

7 TX

3 RX

5 GND

5 GND

8 GND

cMT/mTV series
COM1 RS232 9P

VersaMax series RS232

D-Sub Female

8P RJ45 Male

2 RX

4 TX

3 TX

3 RX

5 GND

8 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

VersaMax series RS232


8P RJ45 Male

2 RX

4 TX

3 TX

3 RX

5 GND

8 GND

228

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

VersaMax series RS232


8P RJ45 Male

2 RX

6 RX

8 RX

4 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

8 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

VersaMax series RS232


8P RJ45 Male

9 RX

4 TX

6 TX

3 RX

5 GND

8 GND

Driver Version:
Version

Date

V1.20

Jan/09/2009

V1.40

Dec/25/2012

Description
Add device type : R_bit

229

PLC Connection Guide

Haiwell PLC
Support Series: E series, S series and H series.
Web: http://www.haiwell.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

Haiwell PLC

PLC I/F

RS232

RS232,RS485 2W

Baud rate

19200

19200

Data bits

Parity

None

None

Stop bits

PLC sta. no.

1~247

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDD

0 ~ 1023

Input Switch

DDDD

0 ~ 1023

Output Switch

DDDDD

0 ~ 12287

Internal Relay

DDDD

0 ~ 1023

Timer (Output Coil State)

DDD

0 ~ 255

Timer (Output Coil State)

SM

DDD

0 ~ 215

System Status Bit

DDDD

0 ~ 2047

Step Bit

CR

DD

0 ~ 79

Special Module Parameter


Register

AI

DDD

0 ~ 255

Analog Input Register

AQ

DDD

0 ~ 255

Analog Output Register

DDDDD

0 ~ 14847

Data Register

TCV

DDDD

0 ~ 1023

Timer (current value register)

CCV

DDD

0 ~ 255

Timer (current value register)

SV

DDD

0 ~ 154

System Register

230

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 4P Mini-DIN
Male

2 RX

8 RX

2 TX

3 TX

7 TX

1 RX

5 GND

5 GND

3 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 4P Mini-DIN
Male

2 RX

2 TX

3 TX

1 RX

5 GND

3 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 4P Mini-DIN
Male

2 RX

2 TX

3 TX

1 RX

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 4P Mini-DIN
Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

1 RX

5 GND

5 GND

5 GND

3 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 4P Mini-DIN
Male

9 RX

2 TX

6 TX

1 RX

5 GND

3 GND
View from the
soldering point
of a cable.

231

PLC Connection Guide

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

B- Data+

2 RX+

9 Data+

A+ Data-

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W

COM3 RS485 2W

RS485 2W Terminal

9P D-Sub Female

9P D-Sub Female

7 RX-

4 Data-

B- Data+

6 RX+

1 Data+

A+ Data-

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

7 Data-

B- Data+

2 RX+

8 Data+

A+ Data-

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

B- Data+

2 RX+

9 Data+

A+ Data-

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

B- Data+

2 RX+

9 Data+

A+ Data-

5 GND

5 GND

232

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W Terminal

1 RX-

7 Data-

B- Data+

2 RX+

8 Data+

A+ Data-

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Mar/2/2012

Driver released.

233

PLC Connection Guide

Hangzhou Maiou MO-TECH


Support Series: LS GLOFA series GM3, GM4, GM6, GM7 CPU Port.
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

Hangzhou Maiou MO-TECH

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word Device type

Format

Range

Memo

MWX

DDDdd

0 ~ 25515

MWX_NO_RPS DDDdd

0 ~ 25515

MW

DDD

0 ~ 255

MW_NO_RPS

DDD

0 ~ 255

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 Terminal

2 RX

8 RX

TD

3 TX

7 TX

RD

5 GND

5 GND

GND

234

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 Terminal

2 RX

TD

3 TX

RD

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 Terminal

2 RX

TD

3 TX

RD

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 Terminal

2 RX

6 RX

8 RX

TD

3 TX

4 TX

7 TX

RD

5 GND

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 Terminal

9 RX

TD

6 TX

RD

5 GND

GND

Driver Version:
Version

Date

V1.00

Apr/27/2010

Description

235

PLC Connection Guide

Hanyoung Controller
Supported Series: Temperature Controller.
Website: http://hynux.com/kor/

HMI Setting:
Parameters

Recommended

Options

PLC type

Hanyoung Controller

PLC I/F

RS485 4W

Baud rate

9600

Data bits

7 or 8

Parity

None

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

0-255

Notes

*In System Parameter Settings / Device Settings / COM Settings, set Parameter 1 to 1 to
support Check Sum Mode.

236

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

DDDD

1 ~ 9999

DDDD

1 ~ 9999

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

Han Young RS422


terminal

1 RX-

32 TX-

2 RX+

31 TX+

3 TX-

34 RX-

4 TX+

33 RX+

5 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

Han Young RS422


terminal

7 RX-

32 TX-

6 RX+

31 TX+

9 TX-

34 RX-

8 TX+

33 RX+

5 GND
MT8000iE/MT8000XE series except MT8050iE
COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

Han Young RS422


terminal

1 RX-

1 RX-

32 TX-

2 RX+

2 RX+

31 TX+

3 TX-

3 TX-

34 RX-

4 TX+

4 TX+

33 RX+

5 GND

5 GND

237

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

Han Young RS422


terminal

1 RX-

32 TX-

2 RX+

31 TX+

3 TX-

34 RX-

4 TX+

33 RX+

5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

Han Young RS422


terminal

1 RX-

32 TX-

2 RX+

31 TX+

3 TX-

34 RX-

4 TX+

33 RX+

5 GND

Driver Version:
Version

Date

V1.60

Jun/14/2010

Description

238

PLC Connection Guide

HAWE PLVC
Supported Series: HAWE PLVC
Website: http://www.hawe.de/de/home/

HMI Setting:
Parameters

Recommended

PLC type

HAWE PLVC

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

HHHH

0 ~ ffff

Input Bits

HHHH

0 ~ ffff

Output Bits

DDDDD

0 ~ 65535

Internal Relays

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

TV

DDDDD

0 ~ 65535

Timer Preset Value

CV

DDDDD

0 ~ 65535

Counter Preset Value

DDDDD

0 ~ 65535

Data Registers

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

239

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 terminal

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 terminal

2 RX

TXD

3 TX

RXD

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 terminal

2 RX

TXD

3 TX

RXD

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 terminal

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 terminal

9 RX

TXD

6 TX

RXD

5 GND

GND

240

PLC Connection Guide

Driver Version:
Version

Date

V1.00

Sep/17/2009

Description

241

PLC Connection Guide

HeFei ShenNong Motor


Website: http://www.ahsngd.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

HeFei ShenNong Motor

PLC I/F

RS485 4W

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

ADDR00

1~D

ADDR01

1~D

ADDR02

1~D

ADDR03

1~D

ADDR04

1~D

ADDR05

1~D

ADDR06

1~D

ADDR07

1~D

ADDR08

1~D

ADDR09

1~D

ADDR0a

1~D

ADDR0b

1~D

ADDR0c

1~D

ADDR0d

1~D

ADDR0e

1~D

ADDR0f

1~D

ADDR3f

0~b

DATAn

0~5

242

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS422 terminal

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS422 terminal

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS422 terminal

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS422 terminal

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

243

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS422 terminal

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

Driver Version:
Version

Date

V1.00

Apr/17/2014

Description

244

PLC Connection Guide

Heng Yuan EU series


Supported Series: EU sereis, EU5 series, EU10 series.
Website: http://www.tjhysensor.cn/

HMI Setting:
Parameters

Recommended

PLC type

Heng Yuan EU series

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Options

Notes

1-31

Online simulator

YES

Extend address mode

YES

Device Address:
Bit/Word

Device type

Format

Parameter

DDDD

Range

Memo

0 ~ 2000

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Heng Yuan Sensor


RS485

1 RX-

6 Data-

7 RX- (Yellow)

2 RX+

9 Data+

6 RX+ (Green)

5 GND

5 GND

4 GND (Black)

245

PLC Connection Guide

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

Heng Yuan Sensor


RS485

7 RX-

4 Data-

7 RX- (Yellow)

6 RX+

1 Data+

6 RX+ (Green)

5 GND

5 GND

4 GND (Black)

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Heng Yuan Sensor


RS485

1 RX-

7 Data-

7 RX- (Yellow)

2 RX+

8 Data+

6 RX+ (Green)

5 GND

9 GND

4 GND (Black)

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Heng Yuan Sensor


RS485

1 RX-

6 Data-

7 RX- (Yellow)

2 RX+

9 Data+

6 RX+ (Green)

5 GND

5 GND

4 GND (Black)

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Heng Yuan Sensor


RS485

1 RX-

6 Data-

7 RX- (Yellow)

2 RX+

9 Data+

6 RX+ (Green)

5 GND

5 GND

4 GND (Black)

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W

COM3 RS485 2W

Heng Yuan Sensor

9P D-Sub Female

9P D-Sub Female

RS485

1 RX-

7 Data-

7 RX- (Yellow)

2 RX+

8 Data+

6 RX+ (Green)

5 GND

5 GND

4 GND (Black)

Driver Version:
Version

Date

Description

V1.00

Dec/30/2008

Driver released.
246

PLC Connection Guide

Hitachi EH-SIO
HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Hitachi EH-SIO

PLC I/F

RS232

RS232, RS485

Baud rate

19200

9600, 19200, 38400

Data bits

Parity

Even

Even

Stop bits

PLC sta. no.

PLC Setting:
Communication mode

19200, E, 7, 1 (default)

Device Address:
Bit/Word Device type

Format

Range

Memo

HHHHh

0 ~ fffff

External input-bit (X)

HHHHh

0 ~ fffff

External output-bit (Y)

HHHHh

0 ~ fffff

Data area-bit (M)

HHHHh

0 ~ fffff

Timer (T)

HHHHh

0 ~ fffff

Internal output (R)

HHHHh

0 ~ fffff

Link area-bit (L)

TC

HH

0 ~ ff

Timer/Counter current value

WM

HHHH

0 ~ 270f

Data area-word (M)

WX

HHHH

0 ~ 270f

External input-word (X)

WY

HHHH

0 ~ 270f

External output-word (Y)

WR

HHHH

0 ~ 270f

Internal output-word (R)

WL

HHHH

0 ~ 270f

Link area-word (L)

247

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
EH-SIO port1/port 2 RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 8P RJ45 Male

2 RX

8 RX

5 SD

3 TX

7 TX

6 RD

5 GND

5 GND

1 SG

8 CTS

8 RS
4 PHL
7 DR

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 8P RJ45 Male

2 RX

5 SD

3 TX

6 RD

5 GND

1 SG

8 CTS

8 RS
4 PHL
7 DR

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 8P RJ45 Male

2 RX

6 RX

8 RX

5 SD

3 TX

4 TX

7 TX

6 RD

5 GND

5 GND

5 GND

1 SG

8 CTS

8 RS
4 PHL
7 DR

248

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 8P RJ45 Male

9 RX

5 SD

6 TX

6 RD

5 GND

1 SG
8 RS
4 PHL
7 DR

short

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 4W
9P D-Sub Male

HitachiEH-SIO port2

1 RX-

2 TX-

2 RX+

1 TX+

3 TX-

4 RX-

4 TX+

3 RX+

5 GND

6 SG

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

HitachiEH-SIO port2

7 RX-

2 TX-

6 RX+

1 TX+

9 TX-

4 RX-

8 TX+

3 RX+

5 GND

6 SG

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

HitachiEH-SIO port2

1 RX-

1 RX-

2 TX-

2 RX+

2 RX+

1 TX+

3 TX-

3 TX-

4 RX-

4 TX+

4 TX+

3 RX+

5 GND

5 GND

6 SG
249

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

HitachiEH-SIO port2

1 RX-

2 TX-

2 RX+

1 TX+

3 TX-

4 RX-

4 TX+

3 RX+

5 GND

6 SG

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

HitachiEH-SIO port2

1 RX-

2 TX-

2 RX+

1 TX+

3 TX-

4 RX-

4 TX+

3 RX+

5 GND

6 SG

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Hitachi EH-SIO port2

1 RX-

6 Data-

2 TX4 RX-

2 RX+

9 Data+

1 TX+
3 RX+

5 GND

short
short

5 GND

6 SG

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

Hitachi EH-SIO port2

7 RX-

4 Data-

2 TX-

cMT/mTV series

4 RX6 RX+

1 Data+

1 TX+
3 RX+

5 GND

5 GND

6 SG

250

short
short

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Hitachi EH-SIO port2

1 RX-

7 Data-

2 TX4 RX-

2 RX+

8 Data+

1 TX+
3 RX+

5 GND

9 GND

short
short

6 SG

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Hitachi EH-SIO port2

1 RX-

6 Data-

2 TX4 RX-

2 RX+

9 Data+

1 TX+
3 RX+

5 GND

5 GND

short
short

6 SG

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W

COM3 RS485 2W

9P D-Sub Male

9P D-Sub Male

1 RX-

6 Data-

Hitachi EH-SIO port2


2 TX4 RX-

2 RX+

9 Data+

1 TX+
3 RX+

5 GND

5 GND

short
short

6 SG

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W

COM3 RS485 2W

9P D-Sub Female

9P D-Sub Female

1 RX-

7 Data-

Hitachi EH-SIO port2


2 TX4 RX-

2 RX+

8 Data+

1 TX+
3 RX+

5 GND

5 GND

6 SG

251

short
short

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

May/25/2010

Driver released.

252

PLC Connection Guide

Hitachi EHV Series (Ethernet)


Website: http://www.hitachi-ies.co.jp/english/products/plc/index.htm

HMI Setting:
Parameters

Recommended Options

Notes

PLC type

Hitachi EHV Series (Ethernet)

PLC I/F

Ethernet

Port no.

3004

3004~3007

Device Address:
Bit/Word Device type

Format

Range

HHHHh

0 ~ fffff

External input-bit (X)

HHHHh

0 ~ fffff

External output-bit (Y)

HHHHh

0 ~ fffff

Data area-bit (M)

DDDDD

0 ~ 65535

Timer (T)

HHHHh

0 ~ fffff

Internal output (R)

HHHHh

0 ~ fffff

Link area-bit (L)

TC

DDDD

0 ~ 2559

Timer/Counter current value

WM

HHHH

0 ~ 7fff

Data area-word (M)

WX

HHHH

0 ~ ffff

External Input-word (X)

WY

HHHH

0 ~ ffff

External output-word (Y)

WR

HHHH

0 ~ ffff

Internal output-word (R)

WL

HHHH

0 ~ 73ff

Link area-word (L)

253

Memo

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Jan/12/2010

Driver released

254

PLC Connection Guide

Hitachi H/EH/EHV Series


Supported Series: Hitachi H series, EH-150, Micro-EH, H20, H40, H64, H200, H250, H252,
H300, H302, H700, H702, H1000, H1002, H2000, H4010.
Website: http://www.hitachi-ies.co.jp/english/products/plc/index.htm

HMI Setting:
Parameters

Recommended Options

PLC type

Hitachi H/EH/EHV Series

PLC I/F

RS232

RS232, RS485

Baud rate

19200

9600, 19200, 38400

Data bits

Parity

Even

Even

Stop bits

PLC sta. no.

0-255

Online simulator

Notes

Does not apply to this


protocol.

YES

Broadcast command NO

Extend address mode NO

Device Address:
Bit/Word Device type

Format

Range

Memo

HHHHh

0 ~ fffff

External input-bit (X)

HHHHh

0 ~ fffff

External output-bit (Y)

HHHHh

0 ~ fffff

Data area-bit (M)

HHHHh

0 ~ fffff

Timer (T)

HHHHh

0 ~ fffff

Internal output (R)

HHHHh

0 ~ fffff

Link area-bit (L)

TC

HH

0 ~ ff

Timer/Counter current value

WM

HHHH

0 ~ 270f

Data area-word (M)

WX

HHHH

0 ~ 270f

External input-word (X)

WY

HHHH

0 ~ 270f

External output-word (Y)

WR

HHHH

0 ~ c3ff

Internal output-word (R)

WL

HHHH

0 ~ 270f

Link area-word (L)

255

PLC Connection Guide

Wiring Diagram:
WARNING: If your communication cable is not wired exactly as shown in our cable
assembly instructions, damage to the HMI or loss of communications can be caused.
CPU TYPE

Port 1

Port 2

EH-150/CPU 104A

RS-232

RS-232

EH-150/CPU 208A

RS-232

RS-232

Port 1

EH-150/CPU 308A

RS-232/RS-485 RS-232

Port 2

EH-150/CPU 316A

RS-232/RS-485 RS-232

EH-150/CPU 448A

RS-232/RS-485 RS-232

Switch Number
1

OFF

Normal mode

OFF

TRNS0 operation

3, 4

Port1 transmission speed

ON

ON

4,800 bps

OFF

ON

9,600 bps

ON

OFF

19,200 bps

OFF

OFF

38,400 bps

ON

Dedicated port

PHL

Port2 transmission speed

ON

Low

9,600 bps

Toggle-Switch

ON

High

38,400 bps

OFF

Low

4,800 bps

Doesnt support

PHL
Low

OFF

High

19,200 bps

Default

OFF

(System mode)

Do not turn on.

PHL

OFF

(System mode)

Do not turn on.

High

Doesnt support

Default

256

PLC Connection Guide

The following is the view from the soldering point of a cable.


EH-150 port1/port 2 RS232 / MICRO-EH port1 RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 8P RJ45 Male

2 RX

8 RX

5 SD

3 TX

7 TX

6 RD

5 GND

5 GND

1 SG

8 CTS

8 RS
4 PHL
7 DR

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 8P RJ45 Male

2 RX

5 SD

3 TX

6 RD

5 GND

1 SG
8 RS
4 PHL
7 DR

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 8P RJ45 Male

2 RX

5 SD

3 TX

6 RD

5 GND

1 SG

8 CTS

8 RS
4 PHL
7 DR

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 8P RJ45 Male

2 RX

6 RX

8 RX

5 SD

3 TX

4 TX

7 TX

6 RD

5 GND

5 GND

5 GND

1 SG

8 CTS

8 RS
4 PHL
7 DR
257

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 8P RJ45 Male

9 RX

5 SD

6 TX

6 RD

5 GND

1 SG
8 RS
4 PHL
7 DR

short

The following is the view from the soldering point of a cable.


EH-150 port1 RS485 4W
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 8P RJ45
Male

1 RX-

5 TX-

2 RX+

4 TX+

3 TX-

6 RX-

4 TX+

7 RX+

5 GND

1 SG

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 8P RJ45
Male

7 RX-

5 TX-

6 RX+

4 TX+

9 TX-

6 RX-

8 TX+

7 RX+

5 GND

1 SG

258

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 8P RJ45
Male

1 RX-

1 RX-

5 TX-

2 RX+

2 RX+

4 TX+

3 TX-

3 TX-

6 RX-

4 TX+

4 TX+

7 RX+

5 GND

5 GND

1 SG

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 8P RJ45
Male

1 RX-

5 TX-

2 RX+

4 TX+

3 TX-

6 RX-

4 TX+

7 RX+

5 GND

1 SG

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

RS485 4W 8P RJ45

9P D-Sub Female

Male

1 RX-

5 TX-

2 RX+

4 TX+

3 TX-

6 RX-

4 TX+

7 RX+

5 GND

1 SG

The following is the view from the soldering point of a cable.


EH-150 port1 RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45
Male

1 RX-

6 Data-

4 TX+
7 RX+

2 RX+

9 Data+

5 TX6 RX-

5 GND

5 GND

1 SG
259

short
short

PLC Connection Guide

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P RJ45
Male

7 RX-

4 Data-

4 TX+
7 RX+

6 RX+

1 Data+

5 TX6 RX-

5 GND

5 GND

short
short

1 SG

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45
Male

1 RX-

7 Data-

4 TX+
7 RX+

2 RX+

8 Data+

5 TX6 RX-

5 GND

9 GND

short
short

1 SG

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W

COM3 RS485 2W

RS485 2W 8P RJ45

9P D-Sub Male

9P D-Sub Male

Male

1 RX-

6 Data-

4 TX+
7 RX+

2 RX+

9 Data+

5 TX6 RX-

5 GND

5 GND

short
short

1 SG

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W

COM3 RS485 2W

RS485 2W 8P RJ45

9P D-Sub Male

9P D-Sub Male

Male

1 RX-

6 Data-

4 TX+
7 RX+

2 RX+

9 Data+

5 TX6 RX-

5 GND

5 GND

1 SG

260

short
short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P RJ45
Male

1 RX-

7 Data-

4 TX+
7 RX+

2 RX+

8 Data+

5 TX6 RX-

5 GND

5 GND

short
short

1 SG

The following is the view from the soldering point of a cable.


H Series CPU Port RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 15P D-Sub Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

9 SG
10 SG

8 CTS

short

4 RTS
5 CTS
7 DSR
8 PHL

short

14 PV12
cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 15P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

9 SG
10 SG

short

4 RTS
5 CTS
7 DSR
8 PHL
14 PV12
261

short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 15P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

9 SG
10 SG

8 CTS

short

4 RTS
5 CTS
7 DSR
8 PHL

short

14 PV12
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 15P D-Sub Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

9 SG
10 SG

8 CTS

short

4 RTS
5 CTS
7 DSR
8 PHL
14 PV12

262

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 15P D-Sub Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

9 SG
10 SG

short

4 RTS
5 CTS
7 DSR
8 PHL

short

14 PV12

Driver Version:
Version

Date

Description

V1.10

Oct/22/2009

Fixed HMI occupies the control right of CPU module.

V1.30

Mar/22/2010

263

PLC Connection Guide

HollySys LE/LM PLC


Supported Series: HollySys LE/LM series PLC
Website: http://www.hollysys.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

HollySys LE/LM PLC

PLC I/F

RS485 2W

Baud rate

38400

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word Device type

Format

Range

IX

DDDDo

0 ~ 81907

MX

DDDDo

0 ~ 81907

QX

DDDDo

0 ~ 81907

IW

DDDD

0 ~ 8190

QW

DDDD

0 ~ 8190

MW

DDDD

0 ~ 8190

MD

DDDD

0 ~ 8190

MR

DDDD

0 ~ 8190

264

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

6 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

7 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P Mini-DIN
Male

7 RX-

4 Data-

6 D-

6 RX+

1 Data+

5 D+

5 GND

5 GND

7 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

7 Data-

6 D-

2 RX+

8 Data+

5 D+

5 GND

9 GND

7 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

6 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

6 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

7 GND

265

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P Mini-DIN
Male

1 RX-

7 Data-

6 D-

2 RX+

8 Data+

5 D+

5 GND

5 GND

7 GND
View from the
soldering point
of a cable.

Driver Version:
Version

Date

Description

V1.00

Apr/17/2014

Driver released.

266

PLC Connection Guide

HUST H4C
Supported Series: HUST CNC Controller H4C, H6C Series.
Website: http://www.hust.com.tw/

HMI Setting:
Parameters

Recommended

PLC type

HUST H4C

PLC I/F

RS-232

Baud rate

38400

Data bits

Parity

Even

Stop bits

Options

Notes
CPU port

9600,19200,38400,57600

Turn around delay 5


PLC sta. no.

Device Address:
Bit/Word

Device type

Format

Range

DDD

0 ~ 255

DDD

0 ~ 255

DDD

0 ~ 255

DDD

0 ~ 255

DDD

0 ~ 1023

VM_bit

DDDDDdd 0 ~ 9999931

DW

VM

DDDDD

0 ~ 99999

DW

DDD

0 ~ 255

DW

Cn

DDD

0 ~ 255

DW

Tm

DDD

0 ~ 255
267

Memo
Mapping to VM 10800 ~ 10807 (read
only)
Mapping to VM 10808 ~ 10815 (read
only)
Mapping to VM 10816 ~ 10823 (read
only)
Mapping to VM 10824 ~ 10831 (read
only)
Mapping to VM 10832 ~ 10863 (read
only)
Bit address (dd): 00 ~ 31
Please refer to the controller
specification for register range.
Mapping to VM 10000 ~ 10255 (read
only)
Mapping to VM 10256 ~ 10511 (read
only)
Mapping to VM 10512 ~ 10767 (read
only)

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

HUST CNC Controller


RS232 D-Sub Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

HUST CNC Controller


RS232 D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

HUST CNC Controller


RS232 D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

HUST CNC Controller


RS232 D-Sub Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

268

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

HUST CNC Controller


RS232 D-Sub Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

Driver Version:
Version

Date

Description

V1.00

Oct/09/2013

Driver released.

V1.20

Mar/17/2014

1. Improves communication speed


2. Communication protection

269

short

PLC Connection Guide

HUST H4X
Supported Series: HUST CNC Controller H4 Series.
Website: http://www.hust.com.tw/

HMI Setting:
Parameters

Recommended

PLC type

HUST H4X

PLC I/F

RS-232

Baud rate

38400

Data bits

Parity

Even

Stop bits

Options

Notes
CPU port

9600,19200,38400,57600

Turn around delay 5


PLC sta. no.

Device Address:
Bit/Word

Device type

Format

Range

DDD

0 ~ 255

DDD

0 ~ 255

DDD

0 ~ 255

DDD

0 ~ 255

DDD

0 ~ 255

VM_bit

DDDDDdd 100 ~ 9999931

DW

VM

DDDDD

1 ~ 99999

DW

DDD

0 ~ 255

DW

Cn

DDD

0 ~ 255

DW

Tm

DDD

0 ~ 255
270

Memo
Mapping to VM 10800 ~ 10807 (read
only)
Mapping to VM 10808 ~ 10815 (read
only)
Mapping to VM 10816 ~ 10823 (read
only)
Mapping to VM 10824 ~ 10831 (read
only)
Mapping to VM 10832 ~ 10863 (read
only)
Bit address (dd): 00 ~ 31
Please refer to the controller
specification for register range.
Mapping to VM 10000 ~ 10255 (read
only)
Mapping to VM 10256 ~ 10511 (read
only)
Mapping to VM 10512 ~ 10767 (read
only)

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

HUST CNC Controller


RS232 D-Sub Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

HUST CNC Controller


RS232 D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

HUST CNC Controller


RS232 D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

HUST CNC Controller


RS232 D-Sub Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

271

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

HUST CNC Controller


RS232 D-Sub Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

Driver Version:
Version

Date

V2.01

Sep/29/2009

Description

272

short

PLC Connection Guide

IAI PCON-C-42PI
Supported Series: PCON Controller for RCP2 Series.
Website: http://www.intelligentactuator.com

HMI Setting:
Parameters

Recommended

PLC type

IAI PCON-C-42PI

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

9600 ~ 115200

1 ~ 16

Device Address:
Bit/Word Device type

Format

Range

SFTY

SON

ALRS

BKRL

STP

HOME

CSTR

JISL

MOD

TEAC

JOG+

JOG-

ST0

ST1

ST2

ST3

ST4

ST5

ST6

1
273

Memo

PLC Connection Guide

Bit/Word Device type

Format

Range

ST7

PMSL

STOP

CLBR

DSS1_Bit

Ddd

15

EMGS

DSS1_Bit

Ddd

14

SFTY

DSS1_Bit

Ddd

13

PWR

DSS1_Bit

Ddd

12

SV

DSS1_Bit

Ddd

11

PSFL

DSS1_Bit

Ddd

10

ALMH

DSS1_Bit

Ddd

ALML

DSS1_Bit

Ddd

ABER

DSS1_Bit

Ddd

BKRL

DSS1_Bit

Ddd

STP

DSS1_Bit

Ddd

HEND

DSS1_Bit

Ddd

PEND

DSS1_Bit

Ddd

CEND

DSS1_Bit

Ddd

CLBS

DSS2_Bit

Ddd

15

ENBS

DSS2_Bit

Ddd

13

LOAD

DSS2_Bit

Ddd

12

TRQS

DSS2_Bit

Ddd

11

MODS

DSS2_Bit

Ddd

10

TEAC

DSS2_Bit

Ddd

JOG+

DSS2_Bit

Ddd

JOG-

DSS2_Bit

Ddd

PE7

DSS2_Bit

Ddd

PE6

DSS2_Bit

Ddd

PE5

DSS2_Bit

Ddd

PE4

DSS2_Bit

Ddd

PE3

DSS2_Bit

Ddd

PE2

DSS2_Bit

Ddd

PE1

DSS2_Bit

Ddd

PE0

DSSE_Bit

Ddd

15

EMGP

DSSE_Bit

Ddd

14

MPUV

DSSE_Bit

Ddd

13

RMDS

DSSE_Bit

Ddd

11

GHMS

274

Memo

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo

DSSE_Bit

Ddd

10

PUSH

DSSE_Bit

Ddd

PSNS

DSSE_Bit

Ddd

PMSS

DSSE_Bit

Ddd

MOVE

POSS_Bit

Ddd

PM512

POSS_Bit

Ddd

PM256

POSS_Bit

Ddd

PM128

POSS_Bit

Ddd

PM64

POSS_Bit

Ddd

PM32

POSS_Bit

Ddd

PM16

POSS_Bit

Ddd

PM8

POSS_Bit

Ddd

PM4

POSS_Bit

Ddd

PM2

POSS_Bit

Ddd

PM1

ZONS_Bit

Ddd

14

LS2

ZONS_Bit

Ddd

13

LS1

ZONS_Bit

Ddd

12

LS0

ZONS_Bit

Ddd

ZP

ZONS_Bit

Ddd

Z2

ZONS_Bit

Ddd

Z1

DIPM_Bit

Ddd

0 ~ 15

IN0 ~ IN15

DOPM_Bit

Ddd

0 ~ 15

OUT0 ~ OUT15

SIPM_Bit

Ddd

14

NP

SIPM_Bit

Ddd

12

PP

SIPM_Bit

Ddd

MDSW

SIPM_Bit

Ddd

BLCT

SIPM_Bit

Ddd

HMCK

SIPM_Bit

Ddd

OT

SIPM_Bit

Ddd

CREP

SIPM_Bit

Ddd

LS

EMG

POSR_Bit

Ddd

0 ~ 15

PNOW

ALMC

DIPM

DOPM

DSS1

1
275

PLC Connection Guide

Bit/Word Device type

Format

Range

DSS2

DSSE

STAT

VNOW

CNOW

DEVI

STIM

SIPM

ZONS

POSS

DRG1

DRG2

POSR_NUM

PCMD

INP

VCMD

ACMD

PPOW

CTLF

FBFC

POSR_MOV

PCMD_T

DDD

0 ~ 768

INP_T

DDD

0 ~ 768

VCMD_T

DDD

0 ~ 768

ZNMP_T

DDD

0 ~ 768

ZNLP_T

DDD

0 ~ 768

ACMD_T

DDD

0 ~ 768

DCMD_T

DDD

0 ~ 768

PPOW_T

DDD

0 ~ 768

LPOW_T

DDD

0 ~ 768

CTLF_T

DDD

0 ~ 768

276

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

7 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P Mini-DIN
Male

7 RX-

4 Data-

2 D-

6 RX+

1 Data+

1 D+

5 GND

5 GND

7 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

7 Data-

2 D-

2 RX+

8 Data+

1 D+

5 GND

9 GND

7 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

7 GND

277

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P Mini-DIN
Male

1 RX-

7 Data-

2 D-

2 RX+

8 Data+

1 D+

5 GND

5 GND

7 GND
View from the
soldering point
of a cable.

Driver Version:
Version

Date

Description

V1.00

Apr/17/2014

Driver released.

V1.10

Mar/13/2015

278

PLC Connection Guide

IAI X-SEL CONTROLLER


Website: http://www.iai-robot.co.jp/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

IAI X-SEL CONTROLLER

PLC I/F

RS232

Baud rate

9600

9600~19200

Data bits

7 or 8

Parity

None

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

Device Address:
Bit/Word

Device type

Format

Range

Memo
Address 1~8 represent the corresponding

Servo_On_Off

1~8

axis.
Write 1 means ON and 0 means OFF.
Address 1~8 represent the corresponding

Servo_Origin

1~8

axis.
Back to origin.
For reading current position. The state of

CurrentAxisPos H

1~8

current axis is put in RW axis*100.


i.e., for the state of axis 2, 2*100=200, so it
is in RW200.

RunProgram

Data written indicates which program to

run.

EndProgram

Data written indicates which program to

stop.
Address 1~8 represent the corresponding
axis. The data written indicates which point

PointMove

0~8

to reach. Put parameters ACC, DEC,


SPEED in axis*100+1, axis*100+2 and
axis*100+3 respectively.

279

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo
Jogging. Address 1~8 represent the
corresponding axis. Put parameters ACC,

JoggingMove

0~8

DEC, SPEED and Position in axis*100+11,


axis*100+12, axis*100+13 and
axis*100+14 respectively.
Jog to the set absolute coordinate. Address
1~8 represent the corresponding axis. Put

AbsoluteMove

0~8

parameters ACC, DEC, SPEED and


Position in axis*100+21, axis*100+22,
axis*100+23 and axis*100+24 respectively.
To change the value of the point. Address
1~8 represent the corresponding axis. Put

PointChange

0~8

parameters ACC, DEC, SPEED and


Position in axis*100+31, axis*100+32,
axis*100+33 and axis*100+34 respectively.

SoftWareReset

Reset soft ware.

Note: ddd: Decimal, hhh: Hexadecimal, ooo: Octal.


Each model of CPU is different; it is recommended to refer to PLC Manual Device List.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Host RS232 D-Sub


Female

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Host RS232 D-Sub


Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

280

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

Host RS232 D-Sub


Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Host RS232 D-Sub


Female

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

Host RS232 D-Sub


Female

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Jun/01/2010

Driver released.

281

PLC Connection Guide

IAI X-SEL CONTROLLER-SSE


Website: http://www.iai-robot.co.jp/

HMI Setting:
Parameters

Recommended

Options

PLC type

IAI X-SEL CONTROLLER-SSE

PLC I/F

RS232

Baud rate

9600

9600~19200

Data bits

7 or 8

Parity

None

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

IP_Bit

DDD

0 ~ 299

OP_Bit

DDD

300 ~ 599

FG_Bit

DDDDDD

0 ~ 128999

AX1Status

0~8

AX2Status

0~8

AX3Status

0~8

IP

DDD

0 ~ 272

OP

DDD

300 ~ 572

FG

DDDDDD

0 ~ 128999

PDT

INT

DDDDDDD 0 ~ 1281299

RL

DDDDDDD 0 ~ 1281399

STR

DDDDDD

0 ~ 128998

AX1Sensor

AX2Sensor

AX3Sensor

AX1Error

AX2Error

AX3Error

0
282

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

AX1Encode

AX2Encode

AX3Encode

AX1Positio23

AX2Positio24

AX3Positio25

PGStatus

DDD

0 ~ 255

PGStepNo

DDD

0 ~ 255

PGError

DDD

0 ~ 255

PGErrorNo

DDD

0 ~ 255

SYST

0~6

VR

HHH

0 ~ 3FF

ER0

HHHH

0 ~ FFFF

ER1

HHHH

0 ~ FFFF

ER2

HHHH

0 ~ FFFF

ER3

HHHH

0 ~ FFFF

ER4

HHHH

0 ~ FFFF

ER5

HHHH

0 ~ FFFF

ER6

HHHH

0 ~ FFFF

ER7

HHHH

0 ~ FFFF

SV

RO

0~3

ACM

RCM

JIM

PNM

PD_Set

PCLR

DDDDDD

0 ~ 999999

AR0

PR_253

DDD

0 ~ 128

PR_254

DDD

0 ~ 128

PR_255

DDD

0 ~ 128

PR_256

DDD

0 ~ 128

PR_257

DDD

0 ~ 128

SR0

OPR0

ChSpd

0
283

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

PD2_Value

DDDDD

10 ~ 40960

PD3_Value

DDDDD

10 ~ 40960

Stop_Canl

1~7

PDn1Value

0~7

PDn2Value

0~7

PDn3Value

0~7

PDn4Value

0~7

PDn5Value

0~7

Memo

Note: ddd: Decimal, hhh: Hexadecimal, ooo: Octal.


Each model of CPU is different; it is recommended to refer to PLC Manual Device List.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Host RS232 D-Sub


Female

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Host RS232 D-Sub


Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

Host RS232 D-Sub


Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

284

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Host RS232 D-Sub


Female

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

Host RS232 D-Sub


Female

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Dec/19/2012

Driver released.

285

PLC Connection Guide

IDEC Micro
Supported Series: IDEC Micro3, Micro3C, OpenNet Controller series.
Website: http://www.idec.com

HMI Setting:
Parameters

Recommended

PLC type

IDEC Micro

PLC I/F

RS232

RS232, RS485

Baud rate

9600

9600, 19200

Data bits

7, 8

Parity

Even

Even, Odd, None

Stop bits

PLC sta. no.

255 (for 1:1


connect)

0-255

Online simulator

YES

Extend address mode

YES

Options

Notes

255 or same as the PLC


setting

Do not set the PLC Station No. to 255

PLC Setting:
Communication mode

9600, E, 7, 1 (default), Use Computer Link Protocol

Device Address:
Bit/Word Device type

Format

Range

Memo

DDDDo

0 ~ 20477

Input (I)

DDDDo

0 ~ 20477

Output (Q)

DDDDo

0 ~ 20477

Internal Relay (M)

RT

DDDD

0 ~ 9999

Timer (T)

RC

DDDD

0 ~ 9999

Counter (C)

DDDD

0 ~ 9999

Data Register (D)

286

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
Micro3C, MicroSmart, OpenNet Controller CPU Ladder Port
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Port1 or Port2 8P
Mini-DIN Male

2 RX

8 RX

3 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

7 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Port1 or Port2 8P
Mini-DIN Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

7 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

Port1 or Port2 8P

D-Sub Female

Mini-DIN Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Port1 or Port2 8P
Mini-DIN Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

7 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

Port1 or Port2 8P
Mini-DIN Male

9 RX

3 TXD

6 TX

4 RXD

5 GND

7 GND
View from the
soldering point
of a cable.

287

PLC Connection Guide

The following is the view from the soldering point of a cable.


Micro3 CPU Port, MicroSmart with FC4A-PC2 RS485 Communication Adapter
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 8P Mini-DIN
Male

1 RX-

6 Data-

2 RXD-

2 RX+

9 Data+

1 RXD+

5 GND

5 GND

7 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 8P Mini-DIN
Male

7 RX-

4 Data-

2 RXD-

6 RX+

1 Data+

1 RXD+

5 GND

5 GND

7 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

7 Data-

2 D-

2 RX+

8 Data+

1 D+

5 GND

9 GND

7 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 8P Mini-DIN
Male

1 RX-

6 Data-

2 RXD-

2 RX+

9 Data+

1 RXD+

5 GND

5 GND

7 GND

288

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 8P Mini-DIN
Male

1 RX-

7 Data-

2 RXD-

2 RX+

8 Data+

1 RXD+

5 GND

5 GND

7 GND
View from the
soldering point
of a cable.

The following is the view from the soldering point of a cable.


Micro3C, OpenNet Controller Data Link Terminals,MicroSmart with FC4A-PC3 RS485
Communication Adapter
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Data Link Terminal

1 RX-

6 Data-

A RXD-

2 RX+

9 Data+

B RXD+

5 GND

5 GND

SG GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

Data Link Terminal

7 RX-

4 Data-

A RXD-

6 RX+

1 Data+

B RXD+

5 GND

5 GND

cMT/mTV series

SG GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Data Link Terminal

1 RX-

7 Data-

A RXD-

2 RX+

8 Data+

B RXD+

5 GND

9 GND

SG GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Data Link Terminal

1 RX-

6 Data-

A RXD-

2 RX+

9 Data+

B RXD+

5 GND

5 GND

SG GND
289

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Data Link Terminal

1 RX-

6 Data-

A RXD-

2 RX+

9 Data+

B RXD+

5 GND

5 GND

SG GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

Data Link Terminal

1 RX-

7 Data-

A RXD-

2 RX+

8 Data+

B RXD+

5 GND

5 GND

SG GND

Driver Version:
Version

Date

V1.20

Jun/19/2009

Description

290

PLC Connection Guide

IDEC MicroSmart
Supported Series: IDEC MicroSmart , SmartAxis series.
Website: http://www.idec.com

HMI Setting:
Parameters

Recommended

PLC type

IDEC MicroSmart

PLC I/F

RS232

RS232, RS485

Baud rate

9600

9600, 19200

Data bits

7, 8

Parity

Even

Even, Odd, None

Stop bits

PLC sta. no.

255 (for 1:1


connect)

0-255

Online simulator

YES

Extend address mode

YES

Options

Notes

255 or same as the PLC


setting

Do not set the PLC Station No. to 255

PLC Setting:
Communication mode

9600, E, 7, 1 (default), Use Computer Link Protocol

Device Address:
Bit/Word Device type

Format

Range

Memo

DDDDo

0 ~ 20477

Input (I)

DDDDo

0 ~ 20477

Output (Q)

DDDDo

0 ~ 20477

Internal Relay (M)

DDDD

0 ~ 2047

Shift Register (R)

DDDD

0 ~ 2047

Timer (T)

DDDD

0 ~ 2047

Counter (C)

TP

DDDD

0 ~ 9999

Timer Preset

CP

DDDD

0 ~ 9999

Counter Preset

DDDD

0 ~ 9999

Data Register (D)

TC

DDDD

0 ~ 9999

Timer Current

CC

DDDD

0 ~ 9999

Counter Currnet

291

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
MicroSmart , SmartAxis CPU Ladder Port
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Port1 or Port2 8P
Mini-DIN Male

2 RX

8 RX

3 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

7 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Port1 or Port2 8P
Mini-DIN Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

7 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

Port1 or Port2 8P

D-Sub Female

Mini-DIN Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Port1 or Port2 8P
Mini-DIN Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

7 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

Port1 or Port2 8P
Mini-DIN Male

9 RX

3 TXD

6 TX

4 RXD

5 GND

7 GND
View from the
soldering point
of a cable.

292

PLC Connection Guide

The following is the view from the soldering point of a cable.


MicroSmart , SmartAxis with FC4A-PC2 RS485 Communication Adapter
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 8P Mini-DIN
Male

1 RX-

6 Data-

2 RXD-

2 RX+

9 Data+

1 RXD+

5 GND

5 GND

7 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 8P Mini-DIN
Male

7 RX-

4 Data-

2 RXD-

6 RX+

1 Data+

1 RXD+

5 GND

5 GND

7 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 8P Mini-DIN
Male

1 RX-

7 Data-

2 RXD-

2 RX+

8 Data+

1 RXD+

5 GND

9 GND

7 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 8P Mini-DIN
Male

1 RX-

6 Data-

2 RXD-

2 RX+

9 Data+

1 RXD+

5 GND

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 8P Mini-DIN
Male

1 RX-

6 Data-

2 RXD-

2 RX+

9 Data+

1 RXD+

5 GND

5 GND

7 GND

293

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 8P Mini-DIN
Male

1 RX-

7 Data-

2 RXD-

2 RX+

8 Data+

1 RXD+

5 GND

5 GND

7 GND
View from the
soldering point
of a cable.

The following is the view from the soldering point of a cable.


MicroSmart , SmartAxis with FC4A-PC3 RS485 Communication Adapter
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Data Link Terminal

1 RX-

6 Data-

A RXD-

2 RX+

9 Data+

B RXD+

5 GND

5 GND

SG GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

Data Link Terminal

7 RX-

4 Data-

A RXD-

6 RX+

1 Data+

B RXD+

5 GND

5 GND

cMT/mTV series

SG GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Data Link Terminal

1 RX-

7 Data-

A RXD-

2 RX+

8 Data+

B RXD+

5 GND

9 GND

SG GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Data Link Terminal

1 RX-

6 Data-

A RXD-

2 RX+

9 Data+

B RXD+

5 GND

5 GND

SG GND

294

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Data Link Terminal

1 RX-

6 Data-

A RXD-

2 RX+

9 Data+

B RXD+

5 GND

5 GND

SG GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

Data Link Terminal

1 RX-

7 Data-

A RXD-

2 RX+

8 Data+

B RXD+

5 GND

5 GND

SG GND

Ethernet cable:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Mar/23/2015

Driver released.

295

PLC Connection Guide

Inovance H2U/H1U
Website: http://www.inovance.cn/

HMI Setting:
Parameters

Recommended

Options

PLC type

Inovance H2U/H1U

PLC I/F

RS485 4W

Baud rate

9600

9600~19200

Data bits

7 or 8

Parity

Even

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

OOO

0 ~ 377

Input Bits

OOO

0 ~ 377

Output Bits

DDDD

0 ~ 7999

Auxiliary Relay

DDD

0 ~ 255

Timer Relay

DDD

0 ~ 255

Counter Relay

SM

DDDD

8000 ~ 9999

Special Auxiliary Relay

D_Bit

DDDDdd

0 ~ 799915

DDDD

0 ~ 4095

TV

DDD

0 ~ 255

Timer Memory

CV

DDD

0 ~ 199

Counter Memory

DDDD

0 ~ 7999

Data Registers

DW

CV2

DDD

200 ~ 255

Counter Memory (32bit)

SD

DDDD

8000 ~ 9999

Special Data Register

Note: ddd: Decimal, hhh: Hexadecimal, ooo: Octal.


Each model of CPU is different, it is recommended to refer to PLC Manual Device List.

296

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

H2U/H1U RS422 8P
Mini-DIN Male

1 RX-

4 TX-

2 RX+

7 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

3 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

H2U/H1U RS422 8P
Mini-DIN Male

7 RX-

4 TX-

6 RX+

7 TX+

9 TX-

1 RX-

8 TX+

2 RX+

5 GND

3 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

H2U/H1U RS422 8P
Mini-DIN Male

1 RX-

1 RX-

4 TX-

2 RX+

2 RX+

7 TX+

3 TX-

3 TX-

1 RX-

4 TX+

4 TX+

2 RX+

5 GND

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

H2U/H1U RS422 8P
Mini-DIN Male

1 RX-

4 TX-

2 RX+

7 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

3 GND

297

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

H2U/H1U RS422 8P
Mini-DIN Male

1 RX-

4 TX-

2 RX+

7 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

3 GND
View from the
soldering point
of a cable.

Driver Version:
Version

Date

Description

V1.00

May/19/2010

Driver released.

298

PLC Connection Guide

Justfi Controller
Supported Series: Justfi weighing instruments, Industrial Batching Controller supports
XK31CB4, XK31CB6.
Website: http://www.justfi.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Justfi controller

PLC I/F

RS232

Baud rate

9600

9600, 19200

Data bits

7 or 8

Parity

Even

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

Notes

Device Address:
Bit/Word
W
DW
W
W
W
W
W
W
W
W
W
W
W
W
W
W

Device type
Func
Func_DW
RW
RF
RT
RG
RC
RB
MZ
MT
CT
DT
BB
HB
BD
RP1t
.
RP6F

Format
DD
DD
H
H
H
H
H
H
H
H
H
H
H
H
H

Range
0 ~ 99
0 ~ 99
0
0
0
0
0
0
0
0
0
0
0
0
0

Memo
Read / Write
Read / Write
Weight (read only)
Read result (read only)
Read total (read only)
Read prescription group
Circle
Read status (read only)
Zero (write only)
Tare (write only)
Clear tare (write only)
Clear total (write only)
Start (write only)
Stop (write only)
Discharge (write only)

Read/Write recipe

299

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

CB4 RS232

2 RX

8 RX

TD

3 TX

7 TX

RD

5 GND

5 GND

GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

CB4 RS232

2 RX

TD

3 TX

RD

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

CB4 RS232

2 RX

TD

3 TX

RD

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

CB4 RS232

2 RX

6 RX

8 RX

TD

3 TX

4 TX

7 TX

RD

5 GND

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

CB4 RS232

9 RX

TD

6 TX

RD

5 GND

GND

300

PLC Connection Guide

Driver Version:
Version

Date

V1.40

Nov/04/2009

Description

301

PLC Connection Guide

Kernel sistemi DMX Series


Supported Series: Kernel systemi DMX 30
Website: http://www.kernelgroup.it/

HMI Setting:
Parameters

Recommended

Options

PLC type

Kernel sistemi DMX Series

PLC I/F

RS232

RS485

Baud rate

19200

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Must match the PLC port


setting

Device Address:
Bit/Word

Device type

Format

Range

HHHH

0 ~ ffff

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

DMX30 RS232 9P
D-Sub Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P

DMX30 RS232 9P

D-Sub Female

D-Sub Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND
302

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

DMX30 RS232 9P
D-Sub Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

DMX30 RS232 9P
D-Sub Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

DMX30 RS232 9P
D-Sub Male

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Feb/06/2010

Driver releasesd.

303

PLC Connection Guide

KEYENCE KV-10/16/24/40/80/Visual KV Series


Supported Series: KEYENCE KV series, KV16~80
Website: http://www.keyence.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

KEYENCE KV-10/16/24/40/80/Visual KV Series

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Notes

RS232

Device Address:
Bit/Word Device type

Format

Range

Memo

RLY

DDDdd0*

0 ~ 655150*

dd:0 ~ 15

DM_Bit

DDDDDh

0 ~ 65535f

DM

DDDDD

0 ~ 65535

TM

DDDD

0 ~ 8999

DDDD

0 ~ 9999

T_Curr

DDDD

0 ~ 9999

T_Preset

DDDD

0 ~ 9999

DDDD

0 ~ 9999

C_Curr

DDDD

0 ~ 9999

C_Preset

DDDD

0 ~ 9999

Timer_Current

Counter_Current

Note:*
If Relay (bit) register is used, please place a zero at the end of the address.
For example, to read Relay (bit) 100, the address is written as 1000.

304

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
RS232 CPU Port:
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

OP-26486 9P D-Sub
Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

OP-26486 9P D-Sub
Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

OP-26486 9P D-Sub

D-Sub Female

Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

OP-26486 9P D-Sub
Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

OP-26486 9P D-Sub
Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

305

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 6P RJ11:
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 6P RJ11 Male

2 RX

8 RX

2 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

3 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 6P RJ11 Male

2 RX

2 TXD

3 TX

4 RXD

5 GND

3 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 6P RJ11 Male

2 RX

2 TXD

3 TX

4 RXD

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 6P RJ11 Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

3 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 6P RJ11 Male

9 RX

2 TXD

6 TX

4 RXD

5 GND

3 GND

306

PLC Connection Guide

Driver Version:
Version

Date

V1.40

Apr/17/2009

Description

307

PLC Connection Guide

KEYENCE KV-3000
Supported Series: KEYENCE KV-3000
Website: http://www.keyence.com/

HMI Setting:
Parameters

Recommended

PLC type

KEYENCE KV-3000

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Options

Notes

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

PLC Setting:
Communication mode

KV STUDIO mode

Device Address:
Bit/Word Device type

Format

Range

Memo

MR

DDDdd

0 ~ 99915

Intenal auxiliary relay

LR

DDDdd

0 ~ 99915

Latch relay

CR

DDDdd

0 ~ 99915

Control relay

DDDdd

0 ~ 99915

Relay

HHHh

0 ~ 3FFF

Link Relay

DDDD

0 ~ 9999

Timer

DDDD

0 ~ 9999

Counter

DM_Bit

DDDDDdd

0 ~ 6553515

TM_Bit

DDDDdd

0 ~ 999915

CM_Bit

DDDDDdd

0 ~ 6553515

EM_Bit

DDDDDdd

0 ~ 6553515
308

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo

B
W

FM_Bit

DDDDDdd

0 ~ 6553515

DM

DDDDD

0 ~ 65535

Data memory

TM

DDDD

0 ~ 9999

Temp data momory

CM

DDDDD

0 ~ 65535

Control memory

EM

DDDDD

0 ~ 65535

Data memory

FM

DDDDD

0 ~ 65535

File register

MR_Word

DDD

0 ~ 999

LR_Word

DDD

0 ~ 999

CR_Word

DDD

0 ~ 999

HHHH

0 ~ 3FFF

Link register

ZF

DDDDDD

0 ~ 131071

File register

DW

TC

DDDD

0 ~ 9999

Timer current value

DW

TS

DDDD

0 ~ 9999

Timer set value

DW

CC

DDDD

0 ~ 9999

Counter current value

DW

CS

DDDD

0 ~ 9999

Counter set value

DW

DD

1 ~ 12

DW

TRM

0~7

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P RJ11:
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 4P RJ11 Male

2 RX

8 RX

1 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

2 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 4P RJ11 Male

2 RX

1 TXD

3 TX

3 RXD

5 GND

2 GND

309

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 4P RJ11 Male

2 RX

1 TXD

3 TX

3 RXD

5 GND

2 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 4P RJ11 Male

2 RX

6 RX

8 RX

1 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

2 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 4P RJ11 Male

9 RX

1 TXD

6 TX

3 RXD

5 GND

2 GND

Driver Version:
Version

Date

Description

V1.00

May/28/2014

Driver released.

310

PLC Connection Guide

KEYENCE KV-5000 (Ethernet)


Supported series: KV5000, 3000, 1000 series.
Website: http://www.keyence.com/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

KEYENCE KV-5000 (Ethernet)

PLC I/F

Ethernet

Port no.

8501

PLC sta. no.

Device Address:
Bit/Word

Device type

Format

Range

MR

DDDdd

0 ~ 99915

LR

DDDdd

0 ~ 99915

CR

DDDdd

0 ~ 99915

RLY

DDDdd

0 ~ 99915

DM

DDDDD

0 ~ 65535

TM

DDDD

0 ~ 9999

DDDD

0 ~ 9999

T_Curr

DDDD

0 ~ 9999

Timer Current

T_Preset

DDDD

0 ~ 9999

Timer Preset

DDDD

0 ~ 9999

C_Curr

DDDD

0 ~ 9999

C_Preset

DDDD

0 ~ 9999

CM

DDDDD

0 ~ 65535

EM

DDDDD

0 ~ 65535

FM

DDDDD

0 ~ 65535

311

Memo

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Dec/25/2009

Driver released.

312

PLC Connection Guide

KEYENCE KV-L20V/700/1000/3000/5000/Nano
Series
Supported series: KV-L20V,700,1000,3000,5000 series, KV Nano series
Website: http://www.keyence.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

KEYENCE KV-L20V/700/1000/3000/5000/Nano Series

PLC I/F

RS232

RS232,RS485 2W,RS485 4W

Baud rate

115200

9600 ~ 115200

Data bits

Parity

Even

Stop bits

PLC sta. no.

Online simulator YES

Notes

Extend address mode NO

PLC Setting:
Communication mode

KV mode (host link)

Device Address:
Bit/Word

Device type

Format

Range

MR

DDDdd

0 ~ 99915

LR

DDDdd

0 ~ 99915

CR

DDDdd

0 ~ 99915

RLY

DDDdd

0 ~ 99915

DM

DDDDD

0 ~ 65535

TM

DDDD

0 ~ 9999

DDDD

0 ~ 9999

T_Curr

DDDD

0 ~ 9999

T_Preset

DDDD

0 ~ 9999

DDDD

0 ~ 9999

C_Curr

DDDD

0 ~ 9999
313

Memo

Timer_Current

Counter_Current

PLC Connection Guide

Bit/Word

Device type

Format

Range

C_Preset

DDDD

0 ~ 9999

CM

DDDDD

0 ~ 65535

EM

DDDDD

0 ~ 65535

FM

DDDDD

0 ~ 65535

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

OP-26486 9P D-Sub
Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

OP-26486 9P D-Sub
Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

OP-26486 9P D-Sub
Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

OP-26486 9P D-Sub
Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

314

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

OP-26486 9P D-Sub
Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

KV-L20V Port2 RS232


terminal

2 RX

8 RX

3 TXD

3 TX

7 TX

5 RXD

5 GND

5 GND

1 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

KV-L20V Port2 RS232


terminal

2 RX

3 TXD

3 TX

5 RXD

5 GND

1 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

KV-L20V Port2 RS232


terminal

2 RX

3 TXD

3 TX

5 RXD

5 GND

1 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

KV-L20V Port2 RS232


terminal

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

5 RXD

5 GND

5 GND

5 GND

1 GND

315

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

KV-L20V Port2 RS232


terminal

9 RX

3 TXD

6 TX

5 RXD

5 GND

1 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W

COM3 RS485 2W

KV-L20V Port2 R485

9P D-Sub Male

9P D-Sub Male

2W terminal

1 RX-

6 Data-

3 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

1 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

KV-L20V Port2 R485


2W terminal

7 RX-

4 Data-

3 D-

6 RX+

1 Data+

5 D+

5 GND

5 GND

1 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W

COM3 RS485 2W

KV-L20V Port2 R485

9P D-Sub Male

9P D-Sub Male

2W terminal

1 RX-

7 Data-

3 D-

2 RX+

8 Data+

5 D+

5 GND

9 GND

1 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

KV-L20V Port2 R485


2W terminal

1 RX-

6 Data-

3 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

1 GND

316

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

KV-L20V Port2 R485


2W terminal

1 RX-

6 Data-

3 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

1 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

KV-L20V Port2 R485


2W terminal

1 RX-

7 Data-

3 D-

2 RX+

8 Data+

5 D+

5 GND

5 GND

1 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 4W
9P D-Sub Male

KV-L20V Port2 R485


4W terminal

1 RX-

3 TX-

2 RX+

5 TX+

3 TX-

2 RX-

4 TX+

4 RX+

5 GND

1 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

KV-L20V Port2 R485


4W terminal

7 RX-

3 TX-

6 RX+

5 TX+

9 TX-

2 RX-

8 TX+

4 RX+

5 GND

1 GND

317

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

KV-L20V Port2 R485


4W terminal

1 RX-

1 RX-

3 TX-

2 RX+

2 RX+

5 TX+

3 TX-

3 TX-

2 RX-

4 TX+

4 TX+

4 RX+

5 GND

5 GND

1 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

KV-L20V Port2 R485


4W terminal

1 RX-

3 TX-

2 RX+

5 TX+

3 TX-

2 RX-

4 TX+

4 RX+

5 GND

1 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

KV-L20V Port2 R485

9P D-Sub Female

4W terminal

1 RX-

3 TX-

2 RX+

5 TX+

3 TX-

2 RX-

4 TX+

4 RX+

5 GND

1 GND

Driver Version:
Version

Date

V2.20

Jul/28/2009

V2.30

Oct/5/2012

Description
Support KV-L20V module

318

PLC Connection Guide

KEYENCE KV-L20V/700/1000/3000/5000/Nano
Series (KV Studio Mode)
Supported series: KV-L20V,700,1000,3000,5000 series, KV Nano series
Website: http://www.keyence.com/

HMI Setting:
Parameters

Recommended

Options

Notes

KEYENCE KV-L20V/700/1000/3000/5000/Nano Series

PLC type

(KV Studio Mode)

PLC I/F

RS232

RS232,RS485 2W,RS485 4W

Baud rate

115200

9600 ~ 115200

Data bits

Parity

Even

Stop bits

PLC sta. no.

Online simulator YES

Extend address mode NO

PLC Setting:
Communication mode

KV STUDIO mode

Device Address:
Bit/Word

Device type

Format

Range

MR

DDDdd

0 ~ 99915

LR

DDDdd

0 ~ 99915

CR

DDDdd

0 ~ 99915

DDDdd

0 ~ 99915

HHHh

0 ~ 3FFF

DDDD

0 ~ 9999

DDDD

0 ~ 9999

DM_Bit

DDDDDdd

0 ~ 6553515

TM_Bit

DDDDdd

0 ~ 999915

CM_Bit

DDDDDdd

0 ~ 6553515
319

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

CTC_Bit

Ddd

0 ~ 315

W_Bit

HHHHh

0 ~ 3FFFF

VM_Bit

DDDDDdd

0 ~ 6553515

VB_Bit

HHHh

0 ~ 3FFF

DM

DDDDD

0 ~ 65535

TM

DDDD

0 ~ 9999

CM

DDDDD

0 ~ 65535

EM

DDDDD

0 ~ 65535

FM

DDDDD

0 ~ 65535

MR_Word

DDD

0 ~ 999

LR_Word

DDD

0 ~ 999

CR_Word

DDD

0 ~ 999

HHHH

0 ~ 3FFF

VM

DDDDD

0 ~ 65535

VB

HHH

0 ~ 3FFF

R_Word

DDD

0 ~ 999

B_Word

HHH

0 ~ 3FF

TC

DDDD

0 ~ 9999

TS

DDDD

0 ~ 9999

CC

DDDD

0 ~ 9999

CS

DDDD

0 ~ 9999

DW

CTH

0~1

DW

CTC

0~3

DW

Z_DWORD

DD

1 ~ 12

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

OP-26486 9P D-Sub
Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

320

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

OP-26486 9P D-Sub
Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

OP-26486 9P D-Sub
Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

OP-26486 9P D-Sub
Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

OP-26486 9P D-Sub
Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

KV-L20V Port2 RS232


terminal

2 RX

8 RX

3 TXD

3 TX

7 TX

5 RXD

5 GND

5 GND

1 GND

321

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

KV-L20V Port2 RS232


terminal

2 RX

3 TXD

3 TX

5 RXD

5 GND

1 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

KV-L20V Port2 RS232


terminal

2 RX

3 TXD

3 TX

5 RXD

5 GND

1 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

KV-L20V Port2 RS232


terminal

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

5 RXD

5 GND

5 GND

5 GND

1 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

KV-L20V Port2 RS232


terminal

9 RX

3 TXD

6 TX

5 RXD

5 GND

1 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

KV-L20V Port2 R485


2W terminal

1 RX-

6 Data-

3 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

1 GND

322

PLC Connection Guide

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

KV-L20V Port2 R485


2W terminal

7 RX-

4 Data-

3 D-

6 RX+

1 Data+

5 D+

5 GND

5 GND

1 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

KV-L20V Port2 R485


2W terminal

1 RX-

7 Data-

3 D-

2 RX+

8 Data+

5 D+

5 GND

9 GND

1 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

KV-L20V Port2 R485


2W terminal

1 RX-

6 Data-

3 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

1 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

KV-L20V Port2 R485


2W terminal

1 RX-

6 Data-

3 D-

2 RX+

9 Data+

5 D+

5 GND

5 GND

1 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W

COM3 RS485 2W

KV-L20V Port2 R485

9P D-Sub Female

9P D-Sub Female

2W terminal

1 RX-

7 Data-

3 D-

2 RX+

8 Data+

5 D+

5 GND

5 GND

1 GND

323

PLC Connection Guide

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 4W
9P D-Sub Male

KV-L20V Port2 R485


4W terminal

1 RX-

3 TX-

2 RX+

5 TX+

3 TX-

2 RX-

4 TX+

4 RX+

5 GND

1 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

KV-L20V Port2 R485


4W terminal

7 RX-

3 TX-

6 RX+

5 TX+

9 TX-

2 RX-

8 TX+

4 RX+

5 GND

1 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

KV-L20V Port2 R485


4W terminal

1 RX-

1 RX-

3 TX-

2 RX+

2 RX+

5 TX+

3 TX-

3 TX-

2 RX-

4 TX+

4 TX+

4 RX+

5 GND

5 GND

1 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

KV-L20V Port2 R485


4W terminal

1 RX-

3 TX-

2 RX+

5 TX+

3 TX-

2 RX-

4 TX+

4 RX+

5 GND

1 GND

324

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

KV-L20V Port2 R485


4W terminal

1 RX-

3 TX-

2 RX+

5 TX+

3 TX-

2 RX-

4 TX+

4 RX+

5 GND

1 GND

Driver Version:
Version

Date

Description

V1.00

May/19/2016

Driver released.

325

PLC Connection Guide

KONNEX KNXnet/IP
Supported series: WAGO 750-849

HMI Setting:
Parameters

Recommended

Options

PLC type

KONNEX KNXnet/IP

PLC I/F

Ethernet

Multi. Cast IP address

224.0.23.12

Port no.

3671

Notes
USE UDP

Support Device Type:


Data type

EasyBuilder data format

Bool

bit

Byte

8-bit

DInt

16-bit BCD, Hex, Binary,


Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Signed

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary,


Unsigned

32-bit

Array

String

SInt
USInt
Word
Int
UInt
DWord

326

Memo

8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit

PLC Connection Guide

PLC Setting:
1. Export Tag file using ETS3 software.

2. In EasyBuilder open System Parameter Settings, add KONNEX KNXnet/IP and then
click [Import Tag].

327

PLC Connection Guide

3. In Tag Manager dialog box click [Import].

4. Select .esf file and then click [OK] to finish importing tags.

328

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Sep/04/2015

Driver released.

329

PLC Connection Guide

Korenix 6550
Website: http://www.korenix.com/

HMI Setting:
Parameters

Recommended

PLC type

Korenix 6550

PLC I/F

Ethernet

Port no.

502

PLC sta. no.

Options

Notes
Modbus protocol

Device Address:
Bit/Word

Device type

Format

Range

1x

DDDDD

1 ~ 65535

0x

DDDDD

1 ~ 65535

3x_Bit

DDDDDdd

100 ~ 6553515

4x_Bit

DDDDDdd

100 ~ 6553515

6x_Bit

DDDDDdd

100 ~ 6553515

3x

DDDDD

1 ~ 65535

4x

DDDDD

1 ~ 65535

5x

DDDDD

1 ~ 65535

6x

DDDDD

1 ~ 65535

330

Memo

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V1.61

Apr/17/2009

Description

331

PLC Connection Guide

KOYO CLICK
Supported Series: KOYO CLICK PLC series
Website: http://www.automationdirect.com

HMI Setting:
Parameters

Recommended

Options

PLC type

KOYO CLICK

PLC I/F

RS232

Baud rate

38400

Data bits

Parity

Odd

Odd,Even,None

Stop bits

1,2

PLC sta. no.

1~247

Notes

1200~115200

Device Address:
Bit/Word Device type Format

Range

Memo

Ddd

001 ~ 816

Input Status (Read Only)

Ddd

001 ~ 816

Output Status

DDDD

1 ~ 2000

Control Bit

DDD

1 ~ 500

Timer Status (Read Only)

CT

DDD

1 ~ 250

Counter Status (Read Only)

SC

DDDD

1 ~ 1000

System Control Bit (Read Only)

DS

DDDD

1 ~ 4500

Data Registers

DD

DDDD

1 ~ 1000

Data Registers (Double Word)

DH

DDD

1 ~ 500

Data Registers

DF

DDD

1 ~ 500

Data Registers (Double Word)

XD

0~8

Input Status Registers (Read Only)

YD

0~8

Output Status Registers

TD

DDD

1 ~ 500

Timer Current Values (Read Only)

CTD

DDD

1 ~ 250

Counter Current Values


(Double Word/Read Only)

SD

DDDD

1 ~ 1000

System Data Registers


(Read Only)

TXT

DDDD

1 ~ 1000

Text Data Registers

332

PLC Connection Guide

Wiring Diagram:
KOYO CLICK PLC Com Port:

The following is the view from the soldering point of a cable.


Driver eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 6P RJ12 Male

2 RX

8 RX

4 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

1 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 6P RJ12 Male

2 RX

4 TXD

3 TX

3 RXD

5 GND

1 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 6P RJ12 Male

2 RX

4 TXD

3 TX

3 RXD

5 GND

1 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 6P RJ12 Male

2 RX

6 RX

8 RX

4 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

1 GND

333

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 6P RJ12 Male

9 RX

4 TXD

6 TX

3 RXD

5 GND

1 GND

Version:
Version

Date

V1.50

Jun/22/2010

V1.70

Oct/20/2014

Description
Fixed the problem where TXT address type 500 and later
cannot be used.

334

PLC Connection Guide

KOYO CLICK (Ethernet)


Supported Series: KOYO CLICK PLC series
Website: http://www.automationdirect.com

HMI Setting:
Parameters
PLC type

Recommended
KOYO CLICK (Ethernet)

PLC I/F

Ethernet

Port no.

25425

Turn around delay

0
No need to set station no.

(ms)
PLC

Options

Notes
USE UDP

100~

*Note

sta. no.
*NoteWhen the communication is not stable, please adjust the parameter of [turn around
delay] till the communication is normal.

Device Address:
Bit/Word

Device type

Format

Range

Ddd

1 ~ 816

Ddd

1 ~ 816

DDDD

1 ~ 2000

DDD

1 ~ 500

CT

DDD

1 ~ 250

SC

DDDD

1 ~ 1000

DS

DDDD

1 ~ 4500

DW

DD

DDDD

1 ~ 1000

DH

DDD

1 ~ 500

DW

DF

DDD

1 ~ 500

XD

0~8

YD

0~8

TD

DDD

1 ~ 500

DW

CTD

DDD

1 ~ 250

SD

DDDD

1 ~ 1000

TXT

DDDD

1 ~ 1000

335

Memo

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Feb/26/2016

Driver released.

336

PLC Connection Guide

KOYO DIRECT
Supported Series: KOYO DirectLogic series PLC DL05, DL06, DL105, DL205, DL305, and
DL405 series.
Website: http://www.automationdirect.com

HMI Setting:
Parameters

Recommended

Options

PLC type

KOYO DIRECT

PLC I/F

RS232

RS232, RS485

Baud rate

9600

9600, 19200, 38400

Data bits

7, 8

Parity

Odd

Even, Odd, None

Stop bits

PLC sta. no.

1-90

Notes

PLC Setting:
1.
2.
3.
4.
5.
6.

The PLC must not have a password.


PLC must be set for Full Duplex operation.
PLC must be set for No Hardware Handshaking.
The PLC must be set to use the K Sequence Protocol.
Set the mode switch to the TERM mode.
When using the D4-440 CPU, the station number must be set to 1.

337

PLC Connection Guide

Device Address:
Bit/Word Device type

Format

Range

Memo

OOOO

0 ~ 4000

Input Bits

OOOO

0 ~ 4000

Output Bits

OOOOO 0 ~ 10000

Control Relays

OOOO

0 ~ 1000

Timer Status Bits

CT

OOOO

0 ~ 1000

Counter Status Bits

OOOO

0 ~ 2000

SP

OOOO

0 ~ 2000

GX

OOOOO 0 ~ 10000

GY

OOOOO 0 ~ 10000

OOOOO 0 ~ 77777

Timer

OOOO

0 ~ 1000

Counter

OOOO

0 ~ 1000

V Memory

Wiring Diagram:
The following is the view from the soldering point of a cable.
DL05/DL06/DL105/DL230/DL240/DL250/DL350/DL450 RS232 port
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

KOYO DirectLogic PLC


RS232 6P RJ12 Male

2 RX

8 RX

4 TX

3 TX

7 TX

3 RX

5 GND

5 GND

1 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

KOYO DirectLogic PLC


RS232 6P RJ12 Male

2 RX

4 TX

3 TX

3 RX

5 GND

1 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

KOYO DirectLogic PLC


RS232 6P RJ12 Male

2 RX

4 TX

3 TX

3 RX

5 GND

1 GND
338

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

KOYO DirectLogic PLC


RS232 6P RJ12 Male

2 RX

6 RX

8 RX

4 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

1 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

KOYO DirectLogic PLC


RS232 6P RJ12 Male

9 RX

4 TX

6 TX

3 RX

5 GND

1 GND

The following is the view from the soldering point of a cable.


CPU unit: DL06/DL250 CPU Port2 RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 Port2 15P


D-Sub Male

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

7 GND
4 RTC
5 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 Port2 15P


D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

7 GND
4 RTC
5 CTS

339

short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 Port2 15P


D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

7 GND
4 RTC
5 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 Port2 15P


D-Sub Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

7 GND
4 RTC
5 CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

RS232 Port2 15P

D-Sub Female

D-Sub Male

9 RX

2 TX

6 TX

3 RX

5 GND

7 GND
4 RTC
5 CTS

340

short

PLC Connection Guide

The following is the view from the soldering point of a cable.


CPU unit: DL06/DL250 CPU Port2 RS422
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS422 Port2 15P


D-Sub Male

1 RX-

10 TX-

2 RX+

9 TX+

3 TX-

6 RX-

4 TX+

13 RX+

5 GND

7 GND
11 RTS+
14 CTS+
12 RTS15 CTS-

Short
Short

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS422 Port2 15P


D-Sub Male

7 RX-

10 TX-

6 RX+

9 TX+

9 TX-

6 RX-

8 TX+

13 RX+

5 GND

7 GND
11 RTS+
14 CTS+
12 RTS15 CTS-

Short
Short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS422 Port2 15P


D-Sub Male

1 RX-

1 RX-

10 TX-

2 RX+

2 RX+

9 TX+

3 TX-

3 TX-

6 RX-

4 TX+

4 TX+

13 RX+

5 GND

5 GND

7 GND
11 RTS+
14 CTS+
12 RTS15 CTS341

Short
Short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS422 Port2 15P


D-Sub Male

1 RX-

10 TX-

2 RX+

9 TX+

3 TX-

6 RX-

4 TX+

13 RX+

5 GND

7 GND
11 RTS+
14 CTS+
12 RTS15 CTS-

Short
Short

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS422 Port2 15P


D-Sub Male

1 RX-

10 TX-

2 RX+

9 TX+

3 TX-

6 RX-

4 TX+

13 RX+

5 GND

7 GND
11 RTS+
14 CTS+
12 RTS15 CTS-

Note: DL06/DL250 CPU Port2 include RS232 and RS422

342

Short
Short

PLC Connection Guide

The following is the view from the soldering point of a cable.


DL430/DL440/DL450 CPU unit Port0 RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 Port0 15P


D-Sub Male

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

13 GND
1 YOP
7 CTS

short

2 YOM
4 ONLINE
14 GND

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 Port0 15P


D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

13 GND
1 YOP
7 CTS

short

2 YOM
4 ONLINE
14 GND

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

RS232 Port0 15P

D-Sub Female

D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

13 GND
1 YOP
7 CTS

short

2 YOM
4 ONLINE
14 GND

343

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 Port0 15P


D-Sub Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

13 GND
1 YOP
7 CTS

short

2 YOM
4 ONLINE
14 GND

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 Port0 15P


D-Sub Male

9 RX

2 TX

6 TX

3 RX

5 GND

13 GND
1 YOP
7 CTS

short

2 YOM
4 ONLINE
14 GND

344

short

PLC Connection Guide

The following is the view from the soldering point of a cable.


CPU unit: DL430/DL440/DL450 CPU unit Port1 & DL350 CPU unit Port2 RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 Port1 25P


D-Sub Male

2 RX

RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

7 GND
4 RTC
5 CTS

Short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 Port1 25P


D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

7 GND
4 RTC
5 CTS

Short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 Port1 25P


D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

7 GND
4 RTC
5 CTS

345

Short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 Port1 25P


D-Sub Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

7 GND
4 RTC
5 CTS

Short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 Port1 25P


D-Sub Male

9 RX

2 TX

6 TX

3 RX

5 GND

7 GND
4 RTC
5 CTS

346

Short

PLC Connection Guide

The following is the view from the soldering point of a cable.


CPU unit: DL430/DL440/DL450 CPU unit Port1 & DL350 CPU unit Port2 RS422
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS422 Port 25P D-Sub


Male

1 RX-

16 TX-

2 RX+

14 TX+

3 TX-

10 RX-

4 TX+

9 RX+

5 GND

7 GND
19 RTS+
11 CTS+
18 RTS23 CTS-

Short
Short

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS422 Port 25P D-Sub


Male

7 RX-

16 TX-

6 RX+

14 TX+

9 TX-

10 RX-

8 TX+

9 RX+

5 GND

7 GND
19 RTS+
11 CTS+
18 RTS23 CTS-

Short
Short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS422 Port 25P D-Sub


Male

1 RX-

1 RX-

16 TX-

2 RX+

2 RX+

14 TX+

3 TX-

3 TX-

10 RX-

4 TX+

4 TX+

9 RX+

5 GND

5 GND

7 GND
19 RTS+
11 CTS+
18 RTS23 CTS347

Short
Short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS422 Port 25P D-Sub


Male

1 RX-

16 TX-

2 RX+

14 TX+

3 TX-

10 RX-

4 TX+

9 RX+

5 GND

7 GND
19 RTS+
11 CTS+
18 RTS23 CTS-

Short
Short

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS422 Port 25P D-Sub


Male

1 RX-

16 TX-

2 RX+

14 TX+

3 TX-

10 RX-

4 TX+

9 RX+

5 GND

7 GND
19 RTS+
11 CTS+
18 RTS23 CTS-

Short
Short

The following is the view from the soldering point of a cable.


CPU unit: DL450 CPU unit Port3 RS422
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS422 Port3 25P


D-Sub Male

1 RX-

13 TX-

2 RX+

12 TX+

3 TX-

25 RX-

4 TX+

24 RX+

5 GND

7 GND
348

PLC Connection Guide

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS422 Port3 25P


D-Sub Male

7 RX-

13 TX-

6 RX+

12 TX+

9 TX-

25 RX-

8 TX+

24 RX+

5 GND

7 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS422 Port3 25P


D-Sub Male

1 RX-

1 RX-

13 TX-

2 RX+

2 RX+

12 TX+

3 TX-

3 TX-

25 RX-

4 TX+

4 TX+

24 RX+

5 GND

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W

RS422 Port3 25P

9P D-Sub Male

D-Sub Male

1 RX-

13 TX-

2 RX+

12 TX+

3 TX-

25 RX-

4 TX+

24 RX+

5 GND

7 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

RS422 Port3 25P

9P D-Sub Female

D-Sub Male

1 RX-

13 TX-

2 RX+

12 TX+

3 TX-

25 RX-

4 TX+

24 RX+

5 GND

7 GND

349

PLC Connection Guide

The following is the view from the soldering point of a cable.


Communication unit: DL205 series D2-DCM and DL405 series D4-DCM RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 Port 25P D-Sub


Male

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

7 GND
4 RTC
5 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 Port 25P D-Sub


Male

2 RX

2 TX

3 TX

3 RX

5 GND

7 GND
4 RTC
5 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 Port 25P D-Sub


Male

2 RX

2 TX

3 TX

3 RX

5 GND

7 GND
4 RTC
5 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 Port 25P D-Sub


Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

7 GND
4 RTC
5 CTS

350

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 Port 25P D-Sub


Male

9 RX

2 TX

6 TX

3 RX

5 GND

7 GND
4 RTC
5 CTS

Driver Version:
Version

Date

V1.30

Nov/08/2010

Description

351

short

PLC Connection Guide

KOYO Do-more
Supported Series: Do-more H2 Series PLC
Website: http://www.automationdirect.com

HMI Setting:
Parameters

Recommended

PLC type

KOYO Do-more

PLC I/F

RS232

Baud rate

115200

Data bits

Parity

None

Stop bits

PLC sta. no.

Online simulation

Options

Notes

9600 ~ 115200

YES

Extend address mode NO

PLC Setting:
Serial Port Mode

Do-more programming

Device Address:
toBit/Word

Device type

Format

Range

ST

DDDD

0 ~ 1023

rB

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

MI

DDDDD

0 ~ 65535

MC

DDDDD

0 ~ 65535

T.Done

DDDDD

0 ~ 32766

Read only

CT.Done

DDDDD

0 ~ 32766

Read only

DLX

OOOOOO

0 ~ 177777

DLY

OOOOOO

0 ~ 177777

DLC

OOOOOO

0 ~ 177777

DLV

OOOOOO

0 ~ 177777

SDT

D.D

0 ~ 7.6

352

Memo

*Note 1

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

WX

DDDDD

0 ~ 65535

WY

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

SS

DDDD.DD

0 ~ 3854.34

Read only *Note 2

SL

DDDD.DDD

0 ~ 1007.130

Read only *Note 2

UDT

DDDDD.D

0 ~ 32767.6

*Note 1

PL

DDD

0 ~ 255

MIR

DDDDD

0 ~ 65535

MHR

DDDDD

0 ~ 65535

DST

DDD

0 ~ 511

DDDDD

0 ~ 65534

DDDDD

0 ~ 65534

T.ACC

DDDDD

0 ~ 32766

Real Number (float)

W
CT.ACC
DDDDD
0 ~ 32766
*Note 1SDT , UDT: xxx.0 = Year, xxx.1 = Month, xxx.2 = Day, xxx.3 = DayOfWeek,
xxx.4 = Hour, xxx.5 = Minute, xxx.6 = Second.
*Note 2SS , SL: xxx.0 = MaxLen, xxx.1 = Length, xxx.2 ~ 34 = String(SS)
xxx.2 ~ 130 = String (SL)

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Koyo Direct Logic 205


RS-232 6P RJ12

2 RX

8 RX

4 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

1 GND

7 RTS

6 CTS

8 CTS

5 RTS

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Koyo Direct Logic 205


RS-232 6P RJ12

2 RX

4 TXD

3 TX

3 RXD

5 GND

1 GND

353

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

Koyo Direct Logic 205


RS-232 6P RJ12

2 RX

4 TXD

3 TX

3 RXD

5 GND

1 GND

7 RTS

6 CTS

8 CTS

5 RTS

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Koyo Direct Logic 205


RS-232 6P RJ12

2 RX

6 RX

8 RX

4 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

1 GND

7 RTS

6 CTS

8 CTS

5 RTS

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

Koyo Direct Logic 205

D-Sub Female

RS-232 6P RJ12

9 RX

4 TXD

6 TX

3 RXD

5 GND

1 GND

Driver Version:
Version

Date

Description

V1.00

Apr/03/2013

Driver released.

354

PLC Connection Guide

KOYO Do-more (Ethernet)


Supported Series: Do-more H2 Series PLC Ethernet port
Website: http://www.automationdirect.com

HMI Setting:
Parameters
PLC type

Recommended
Options
KOYO Do-more (Ethernet)

Notes

PLC I/F

Ethernet

USE UDP

Port no.

28784

PLC sta. no.

No need to set station no.

PLC Setting:
Serial Port Mode

Do-more programming

Device Address:
Bit/Word

Device type

Format

Range

ST

DDDD

0 ~ 1023

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

MI

DDDDD

0 ~ 65535

MC

DDDDD

0 ~ 65535

T.Done

DDDDD

0 ~ 32766

Read only

CT.Done

DDDDD

0 ~ 32766

Read only

DLX

OOOOOO

0 ~ 177777

DLY

OOOOOO

0 ~ 177777

DLC

OOOOOO

0 ~ 177777

DLV

OOOOOO

0 ~ 177777

SDT

D.D

0 ~ 7.6

WX

DDDDD

0 ~ 65535

WY

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535
355

Memo

*Note 1

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

SS

DDDD.DD

0 ~ 3854.34

Read only *Note 2

SL

DDDD.DDD

0 ~ 1007.130

Read only *Note 2

UDT

DDDDD.D

0 ~ 32767.6

*Note 1

PL

DDD

0 ~ 255

MIR

DDDDD

0 ~ 65535

MHR

DDDDD

0 ~ 65535

DST

DDD

0 ~ 511

DDDDD

0 ~ 65534

DDDDD

0 ~ 65534

T.ACC

DDDDD

0 ~ 32766

Real Number (float)

W
CT.ACC
DDDDD
0 ~ 32766
*Note 1SDT , UDT: xxx.0 = Year, xxx.1 = Month, xxx.2 = Day, xxx.3 = DayOfWeek,
xxx.4 = Hour, xxx.5 = Minute, xxx.6 = Second.
*Note 2SS , SL: xxx.0 = MaxLen, xxx.1 = Length, xxx.2 ~ 34 = String(SS)
xxx.2 ~ 130 =String (SL)

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Apr/03/2013

Driver released.

356

PLC Connection Guide

KOYO Ethernet
Supported Series: KOYO DirectLogic series, model H0-ECOM100, H2-ECOM100.
Website: http://www.automationdirect.com

HMI Setting:
Parameters
PLC type

Recommended
KOYO Ethernet

Options

PLC I/F

Ethernet

Port no.

28784

PLC sta. no.

No need to set station no.

Notes
UDP/IP

Device Address:
Bit/Word

Device type

Format

Range

Memo

GX

OOOO

0 ~ 3777

Global I/O

OOOO

0 ~ 1777

Real Word Inputs

SP

OOOO

0 ~ 1777

Special Purpose Relays

GY

OOOO

0 ~ 3777

More Global I/O

OOOO

0 ~ 1777

Real Word Outputs

OOOO

0 ~ 3777

Control Relays

OOOO

0 ~ 1777

Stage Status Bits

OOO

0 ~ 377

Timer Status Bits

CT

OOO

0 ~ 377

Counter Status Bits

OOOOO

0 ~ 41237

V-memory

CCM_32

HHH

1 ~ 200

GX, X, SP

CCM_33

HHH

1 ~ 340

GY,Y,C,S,T,CT

CCM_31

HHHH

1 ~ 42a0

ddd:Decimal, hhh:Hexadecimal, ooo:Octal

357

PLC Connection Guide

The mapping of CCM32, CCM33, and CCM31 with other addresses.


Device type

Range

Device type Range

CCM_31

1~42A0

0~41237

CCM_32

1~FF

GX

0~3777

CCM_32

101~17F

0~1777

CCM_32

181~1FF

SP

0~1777

CCM_33

1~FF

GY

0~3777

CCM_33

101~17F

0~1777

CCM_33

181~27F

0~3777

CCM_33

281~2FF

0~1777

CCM_33

301~31F

0~377

CCM_33

321~33F

CT

0~377

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V1.10

Jul/03/2009

Description

358

PLC Connection Guide

Lenze
Supported Series: PLC Model No.: 9300/8200 series, and EPL10200
Pass-through 2102IB fieldbus module: RS485 (LECOM B)
Website: http://www.lenze.de

HMI Setting:
Parameters

Recommended

Options

PLC type

Lenze

PLC I/F

RS232

Baud rate

9600

9600, 19200

Data bits

7,8

Parity

None

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

0-255

Notes

PLC Setting:
Communication mode

Same as the MT500 setting

Device Address:
Bit/Word

Device type

Format

Range

CNB

DDDDdd

0 ~ 999915

CB

DDDDddxx

0 ~ 81920015

CI

DDDDdd

0 ~ 819200

CD

DDDDdd

0 ~ 819200

CF

DDDDdd

0 ~ 819200

CNI

DDDD

0 ~ 9999

CND

DDDD

0 ~ 9999

CNF

DDDD

0 ~ 9999
359

Memo
Subcode not supported.
Can only read/write CNI
Word Type.
Subcode supported.
Can only read/write CI
Word Type.
Subcode supported.
Integer
Subcode supported.
DWord
Subcode supported.
DWord (float point)
Subcode not supported.
Integer
Subcode not supported.
DWord
Subcode not supported.
DWord (float point)

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole

1 RX-

6 Data-

72 T/R (A)

2 RX+

9 Data+

71 T/R (B)

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole

7 RX-

4 Data-

72 T/R (A)

6 RX+

1 Data+

71 T/R (B)

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole

1 RX-

7 Data-

72 T/R (A)

2 RX+

8 Data+

71 T/R (B)

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole

1 RX-

6 Data-

72 T/R (A)

2 RX+

9 Data+

71 T/R (B)

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole

1 RX-

6 Data-

72 T/R (A)

2 RX+

9 Data+

71 T/R (B)

5 GND

5 GND
360

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole

1 RX-

7 Data-

72 T/R (A)

2 RX+

8 Data+

71 T/R (B)

5 GND

5 GND

Driver Version:
Version

Date

V1.20

Sep/6/2011

Description

361

PLC Connection Guide

LingYan BMS
Website: http://www.lyeda.com/Project_file/bms01.htm

HMI Setting:
Parameters

Recommended

PLC type

LingYan BMS

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

Device Address:
Bit/Word

Device type

Format

Range

Battery_Unit

Insulator_Unit D

Switch_Unit

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 4P Terminal

2 RX

8 RX

1 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

4 GND

cMT/mTV series
COM1 RS232 9P

RS232 4P Terminal

D-Sub Female
2 RX

1 TXD

3 TX

3 RXD

5 GND

4 GND
362

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 4P Terminal

2 RX

1 TXD

3 TX

3 RXD

5 GND

4 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 4P Terminal

2 RX

6 RX

8 RX

1 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

4 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 4P Terminal

9 RX

1 TXD

6 TX

3 RXD

5 GND

4 GND

Driver Version:
Version

Date

V1.10

Nov/12/2009

Description

363

PLC Connection Guide

LIYAN EX series
Supported Series: LIYAN PLC Ex/Ex1s/Ex1n/Ex2n series
Website: http://www.liyanplc.com/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Mitsubishi FX0s/FX0n/FX1s/FX1n/FX2

PLC I/F

RS232

RS232

Baud rate

9600

9600~115200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1,2

PLC sta. no.

0-255

Must match the PLC port


setting.

Device Address:
Bit/Word

Device type

Format

Range

Memo

ooo

0 ~ 377

Input Relay

ooo

0 ~ 377

Output Relay

ddd

0 ~ 9999

Internal Bit Memory

ddd

0 ~ 255

Timer Bit Memory

ddd

0 ~ 255

Counter Bit Memory

TV

ddd

0 ~ 255

Timer Register

CV

ddd

0 ~ 199

Counter Register

ddd

0 ~ 9999

Data Register

CV2

ddd

200 ~ 255

Counter Register (Double Word)

SD

ddd

8000 ~ 9999 Special Data Register

364

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 8P Mini-DIN: Ex, Ex1s, Ex1n, Ex2n series
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

8 RX

2 TXD

3 TX

7 TX

7 RXD

5 GND

5 GND

6 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

2 TXD

3 TX

7 RXD

5 GND

6 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

RS232 8P Mini-DIN

D-Sub Female

Male

2 RX

2 TXD

3 TX

7 RXD

5 GND

6 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 8P Mini-DIN
Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

7 RXD

5 GND

5 GND

5 GND

6 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

9 RX

2 TXD

6 TX

7 RXD

5 GND

6 GND
View from the
soldering point
of a cable.

365

PLC Connection Guide

Driver Version:
Version

Date

V1.20

Oct/26/2011

Description

366

PLC Connection Guide

LoXin
Website: http://www.loxin-china.com

HMI Setting:
Parameters

Recommended

PLC type

LoXin

PLC I/F

RS-485 2W

Baud rate

9600

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Options

Notes

Device Address:
Bit/Word

Device type

Format

Range

Battery_Unit

Insulator_Unit D

Switch_Unit

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W

COM3 RS485 2W

RS485 terminal

9P D-Sub Female

9P D-Sub Female

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND
367

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

Driver Version:
Version

Date

V1.00

Oct/16/2008

Description

368

PLC Connection Guide

LS GLOFA Cnet
Supported Series: LS GLOFA GM6/GM7 CPU port. G7L-CUEB / G6L-CUEB / G4L-CUEA
/ G3L-CUEA Cnet module
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

LS GLOFA Cnet

PLC I/F

RS232

RS232/RS485 2W/4W

Baud rate

9600

9600~115200

Data bits

7, 8

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

0~31

PLC Setting:
Communication mode

9600,N,8,1 (default), Cnet protocol

Communication module

Applicable mode: 1 dedicated communication

Device Address:
Bit/Word

Device type

Format

Range

Memo

MX

DDDDD

0 ~ 32767

Internal Relay

IX

ddDdd

0 ~ 63763

Input

QX

ddDdd

0 ~ 63763

Output

MW

DDDDD

0 ~ 32767

Data Register

DW

MD

DDDDD

0 ~ 16383

Double Word

Device explanation:
IX and QX format: dd D dd
Module Contact Number (0 to 63)
Slot Number (0 to 7)
Base Number (0 to 63)

369

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

7 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

7 TXD

3 TX

4 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

7 TXD

3 TX

4 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

7 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

7 TXD

6 TX

4 RXD

5 GND

5 GND

370

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 9P D-Sub: Communication Module (G7L-CUEB / G6L-CUEB / G4L-CUEA /
G3L-CUEA Cnet RS232)
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
1 CD
7 RTS

short

8 CTS
4 DTR
6 DSR

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
1 CD
7 RTS

short

8 CTS
4 DTR
6 DSR

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
1 CD
7 RTS

short

8 CTS
4 DTR
6 DSR

371

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
1 CD
7 RTS

short

8 CTS
4 DTR
6 DSR

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
1 CD
7 RTS

short

8 CTS
4 DTR
6 DSR

short

The following is the view from the soldering point of a cable.


Communication Module (G7L-CUEC / G6L-CUEC / G4L-CUEA / G3L-CUEA Cnet RS422)
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS422 terminal

1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

GND

372

PLC Connection Guide

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS422 terminal

7 RX-

SDB

6 RX+

SDA

9 TX-

RDB

8 TX+

RDA

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS422 terminal

1 RX-

1 RX-

SDB

2 RX+

2 RX+

SDA

3 TX-

3 TX-

RDB

4 TX+

4 TX+

RDA

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W

RS422 terminal

9P D-Sub Male
1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

RS422 terminal

9P D-Sub Female
1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

GND

373

PLC Connection Guide

Driver Version:
Version

Date

V1.80

Jun/08/2010

Description

374

PLC Connection Guide

LS GLOFA FEnet (Ethernet)


Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS GLOFA FEnet (Ethernet)

PLC I/F

Ethernet

Port no.

2004

PLC sta. no.

Notes

0~31

Device Address:
Bit/Word

Device type

Format

Range

Memo

MX

DDDDDD

0 ~ 131056

Internal Relay

IX

ddDdd

0 ~ 63763

Input

QX

ddDdd

0 ~ 63763

Output

MW

DDDD

0 ~ 8191

Data Register

DW

MD

DDDD

0 ~ 4095

Double Word

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Apr/02/2009

Driver released.
375

PLC Connection Guide

LS GLOFA GM3467 (LOADER)


Supported Series: LS GLOFA series GM3, GM4, GM6, GM7 CPU port.
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS GLOFA GM3467 (LOADER)

PLC I/F

RS232

Baud rate

38400

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

MX

DDDDDD

0 ~ 524272

IX

ddDdd

0 ~ 63763

00.0.0 ~ 63.7.63
(dd.D.dd)

QX

ddDdd

0 ~ 63763

00.0.0 ~ 63.7.63
(dd.D.dd)

IW

HHH

0 ~ 273

QW

HHH

0 ~ 273

MW

DDDDD

0 ~ 32767

MD

DDDDD

0 ~ 16383

376

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

LS GLOFA series
RS232 9P D-Sub Male

2 RX

8 RX

3 TD

3 TX

7 TX

2 RD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

LS GLOFA series
RS232 9P D-Sub Male

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

LS GLOFA series
RS232 9P D-Sub Male

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

LS GLOFA series
RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TD

3 TX

4 TX

7 TX

2 RD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

LS GLOFA series
RS232 9P D-Sub Male

9 RX

3 TD

6 TX

2 RD

5 GND

5 GND

377

PLC Connection Guide

Driver Version:
Version

Date

V1.30

Mar/08/2010

Description

378

PLC Connection Guide

LS MASTER-K Cnet
Supported Series: LS MASTER-K series: K80S, K200S, K300S, and K1000S
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

PLC type

LS MASTER-K Cnet

PLC I/F

RS232

RS232/RS485

Baud rate

38400

9600, 19200, 38400

Data bits

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

0-31

Online simulator

Options

Notes

Must match the PLC port


setting.

YES

Device Address:
Bit/Word

Device type

Format

Range

Memo

PW_Bit

DDDh

0 ~ 255f

I/O Relay (P)

KW_Bit

DDDh

0 ~ 255f

Keep Relay (K)

MW_Bit

DDDh

0 ~ 255f

Auxiliary Relay (M)

LW_Bit

DDDh

0 ~ 255f

Link Relay (L)

FW_Bit

DDDh

0 ~ 255f

Special Relay (F)

TX

DDDh

0 ~ 255

CX

DDDh

0 ~ 255

DW_bit

DDDDh

0 ~ 9999f

SX

DD.DD

0 ~ 99.99

MW

DDD

0 ~ 255

Word type for M

LW

DDD

0 ~ 255

Word type for L

FW

DDD

0 ~ 255

Word type for F

PW

DD

0 ~ 63

KW

DD

0 ~ 63

TW

DDD

0 ~ 255

Timer Present Value

CW

DDD

0 ~ 255

Counter Present Value

DW

DDDD

0 ~ 9999

Data Register (D)

379

D_bit

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

CPU Port Cnet I/F


RS232 9P D-Sub Male

2 RX

8 RX

7 TX

3 TX

7 TX

4 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

CPU Port Cnet I/F


RS232 9P D-Sub Male

2 RX

7 TX

3 TX

4 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

CPU Port Cnet I/F


RS232 9P D-Sub Male

2 RX

7 TX

3 TX

4 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

CPU Port Cnet I/F


RS232 9P D-Sub Male

2 RX

6 RX

8 RX

7 TX

3 TX

4 TX

7 TX

4 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

CPU Port Cnet I/F


RS232 9P D-Sub Male

9 RX

7 TX

6 TX

4 RX

5 GND

5 GND

If connected with Cnet module, please refer to Cnet module document.

380

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Apr/19/2010

Driver released.

V1.10

May/11/2011

Added registers: D_bit, M_word, F_word, L_word

V1.20

Mar/23/2015

Added registers: TX, CX, SX, PW,KW

381

PLC Connection Guide

LS MASTER-K CPU Direct


Supported Series: LS MASTER-K series: K80S, K120S, K200S, K300S, K1000S, K7M.
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

PLC type

LG MASTER-K CPU Direct

PLC I/F

RS232

RS232/RS485

Baud rate

38400

9600, 19200, 38400

Data bits

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

0-31

Online simulator

Options

Notes

Must match the PLC port


setting.

YES

Device Address:
Bit/Word

Device type

Format

Range

Memo

PW_Bit

DDDh

0 ~ 255f

I/O Relay (P)

KW_Bit

DDDh

0 ~ 255f

Keep Relay (K)

MW_Bit

DDDh

0 ~ 255f

Auxiliary Relay (M)

LW_Bit

DDDh

0 ~ 255f

Link Relay (L)

FW_Bit

DDDh

0 ~ 255f

Special Relay (F)

TX

DDD

0 ~ 255

CX

DDD

0 ~ 255

SX

DD.DD

0 ~ 99.99

DW_bit

DDDDh

0 ~ 9999f

D_bit

MW

DDD

0 ~ 255

Word type for M

LW

DDD

0 ~ 255

Word type for L

FW

DDD

0 ~ 255

Word type for F

PW

DD

0 ~ 63

KW

DD

0 ~ 31

TW

DDD

0 ~ 255

Timer Present Value

CW

DDD

0 ~ 255

Counter Present Value

DW

DDDD

0 ~ 9999

Data Register (D)

382

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

383

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.20

May/11/2011

Added registers: D_bit, M_word, F_word, L_word

V1.30

Feb/10/2015

Changed the naming method of LS registers.

384

PLC Connection Guide

LS MASTER-K MODBUS RTU


Supported Series: LS MASTER-K MODBUS RTU
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS MASTER-K MODBUS RTU

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

Even

Even

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

PW_Bit

DDDDh

0 ~ 9999f

I/O Relay (P)

KW_Bit

DDDDh

0 ~ 9999f

Keep Relay (K)

MW_Bit

DDDDh

0 ~ 9999f

Auxiliary Relay (M)

LW_Bit

DDDDh

0 ~ 9999f

Link Relay (L)

FW_Bit

DDDDh

0 ~ 9999f

Special Relay (F)

DW_Bit

DDDDh

0 ~ 9999f

MW

DDDD

0 ~ 9999

LW

DDDD

0 ~ 9999

FW

DDDD

0 ~ 9999

TW

DDDD

0 ~ 9999

Timer (T)

CW

DDDD

0 ~ 9999

Counter (C)

SW

DDDD

0 ~ 9999

DW

DDDD

0 ~ 9999

DW

TD

DDDD

0 ~ 9999

DW

CD

DDDD

0 ~ 9999

DW

SD

DDDD

0 ~ 9999

DW

DD

DDDD

0 ~ 9999
385

Data Register (D)

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

386

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.10

May/11/2011

Added registers: D_bit, M_word, F_word, L_word

V1.20

Feb/10/2015

Changed the naming method of LS registers.

387

PLC Connection Guide

LS MASTER-K10S1
Supported Series: LS MASTER-K10S1
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS MASTER-K10S1

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

None

None

Stop bits

PLC sta. no.

Notes

RS232/RS485

Device Address:
Bit/Word

Device type

Format

Range

Memo

PW_Bit

DDDh

0 ~ 255f

I/O Relay (P)

KW_Bit

DDDh

0 ~ 255f

Keep Relay (K)

MW_Bit

DDDh

0 ~ 255f

Auxiliary Relay (M)

LW_Bit

DDDh

0 ~ 255f

Link Relay (L)

FW_Bit

DDDh

0 ~ 255f

Special Relay (F)

TX

DDD

0 ~ 255

Timer (T)

CX

DDD

0 ~ 255

Counter (C)

TW

DDD

0 ~ 255

Timer Present Value

CW

DDD

0 ~ 255

Counter Present Value

DW

DDDD

0 ~ 9999

Data Register (D)

388

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
Driver eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

389

PLC Connection Guide

Version:
Version

Date

Description

V1.00

Sep/08/2009

Driver released.

V1.10

Feb/10/2015

Changed the naming method of LS registers.

390

PLC Connection Guide

LS XBM/XBC Cnet
Supported Series: LS XGB Series XBM/XBC CPU with communication module
XGL-CH2A.
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS XBM/XBC Cnet

PLC I/F

RS232

RS232/RS485

Baud rate

115200

9600~115200

Data bits

7, 8

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

0-31

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

PW_Bit

DDDDh

0 ~ 2047f

I/O device Bit

MW_Bit

DDDDh

0 ~ 2047f

Internal device Bit

LW_Bit

DDDDDh

0 ~ 11263f

Communication device Bit

KW_Bit

DDDDh

0 ~ 2559f

Preservation device Bit

FW_Bit

DDDDh

0 ~ 2047f

DW_Bit

DDDDDh

0 ~ 32767f

UW_Bit

DH.DDh

0 ~ 7f.31f

RW_Bit

DDDDDh

0 ~ 32767f

SX

DDDDD

0 ~ 12799

Relay for step control Bit

TX

DDDD

0 ~ 2047

Timer device Bit

CX

DDDD

0 ~ 2047

Counter device Bit

PW

DDDD

0 ~ 2047

I/O device_2,048 points

MW

DDDD

0 ~ 2047

Internal device_4,096 points

LW

DDDDD

0 ~ 11263

Communication device_20,480 points

391

Special device Bit( write available


from 1025)
Data register_Bit expression
(D0000.0)
XGK-CPUE : hh(0~1f)

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

KW

DDDD

0 ~ 2559

Preservation device_4,096 points

FW

DDDD

0 ~ 2047

Special device_4,096 point

DW

DDDDD

0 ~ 32767

Data register_5120 words

UW

DH.DD

0.00 ~ 7f.31

Analog data register_256 words

RW

DDDDD

0 ~ 32767

SW

DDDDD

0 ~ 127

Relay for step control

TW

DDDD

0 ~ 2047

Timer current value register_256 words

CW

DDDD

0 ~ 2047

Counter current value register_256 words

NW

DDDDD

0 ~ 21503

Communication data register_3,936 words

ZW

DDD

0 ~ 127

Index register_128 words

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

392

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

485-

2 RX+

9 Data+

485+

5 GND

5 GND

GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W Terminal

7 RX-

4 Data-

485-

6 RX+

1 Data+

485+

5 GND

5 GND

GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

7 Data-

485-

2 RX+

8 Data+

485+

5 GND

9 GND

GND

393

PLC Connection Guide

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

485-

2 RX+

9 Data+

485+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

485-

2 RX+

9 Data+

485+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W Terminal

1 RX-

7 Data-

485-

2 RX+

8 Data+

485+

5 GND

5 GND

GND

Driver Version:
Version

Date

Description

V1.50

Mar/07/2011

Added registers: P_Bit, M_Bit, L_Bit, K_Bitetc

V1.70

Jun/28/2012

Change the way to read/write S_Bit.

V1.80

Mar/10/2014

Added registers: R_Bit, R

V2.00

Feb/10/2015

Changed the naming method of LS registers.

394

PLC Connection Guide

LS XBM/XBC FEnet (Ethernet)


Supported Series: LS XGB series XBM/XBC CPU with XBL-EFMT ethernet module.
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS XBM/XBC FEnet (Ethernet)

PLC I/F

Ethernet

Port no.

2004

PLC sta. no.

Notes

0~255

PLC Setting:
Communication mode

FEnet Protocol

Device Address:
Bit/Word

Device type

Format

Range

Memo

PW_Bit

DDDDh

0 ~ 2047f

I/O device Bit

MW_Bit

DDDDh

0 ~ 2047f

Internal device Bit

LW_Bit

DDDDDh

0 ~ 11263f

Communication device Bit

KW_Bit

DDDDh

0 ~ 2559f

Preservation device Bit

FW_Bit

DDDDh

0 ~ 2047f

Special device Bit( write available from 1025)

DW_Bit

DDDDDh

0 ~ 32767f

Data register_Bit expression

UW_Bit

DH.DDh

0 ~ 7f.31f

XGK-CPUE : hh(0~1f)

RW_Bit

DDDDDf

0 ~32767f

SX

DDDDD

0 ~ 12799

Relay for step control Bit

TX

DDDD

0 ~ 2047

Timer device Bit

CX

DDDD

0 ~ 2047

Counter device Bit

PW

DDDD

0 ~ 2047

I/O device_2,048 points

MW

DDDD

0 ~ 2047

Internal device_4,096 points

LW

DDDDD

0 ~ 11263

Communication device_20,480

KW

DDDD

0 ~ 2559

points
Preservation
device_4,096 points

FW

DDDD

0 ~ 2047

Special device_4,096 point

DW

DDDDD

0 ~ 32767

Data register_5120 words

UW

DH.DD

0.00 ~ 7f.31

Analog data register_256 words

395

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

RW

DDDDD

0 ~ 32767

SW

DDDDD

0 ~ 127

Relay for step control

TW

DDDD

0 ~ 2047

Timer current value register_256 words

CW

DDDD

0 ~ 2047

Counter current value register_256 words

NW

DDDDD

0 ~ 21503

Communication data register_3,936 words

ZW

DDD

0 ~ 127

Index register_128 words

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.50

Aug/16/2011

Added registers: P_Bit, M_Bit, L_Bit, K_Bitetc

V1.60

Jun/28/2012

Change the way to read/write S_Bit.

V1.70

Mar/10/2014

Added registers: R_Bit, R

V1.80

Feb/10/2015

Changed the naming method of LS registers.

396

PLC Connection Guide

LS XBM/XBC/XGK CPU DIRECT


Supported Series: LS XBM/XBC/XGK CPU RS232 port.
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS XBM/XBC/XGK CPU DIRECT

PLC I/F

RS232

RS232

Baud rate

115200

9600~115200

Data bits

7, 8

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

PW_Bit

DDDDh

0 ~ 2047f

I/O device Bit

MW_Bit

DDDDh

0 ~ 2047f

Internal device Bit

LW_Bit

DDDDDh

0 ~ 11263f

Communication device Bit

KW_Bit

DDDDh

0 ~ 2559f

Preservation device Bit

FW_Bit

DDDDh

0 ~ 2047f

Special device Bit( write available from

DW_Bit

DDDDDh

0 ~ 32767f

1025)
Data

UW_Bit

DH.DDh

0 ~ 3f.31f

XGK-CPUE : hh(0~1f)

RW_Bit

DDDDDh

0 ~ 32767f

SX

DDDDD

0 ~ 12799

Relay for step control Bit

TX

DDDD

0 ~ 2047

Timer device Bit

CX

DDDD

0 ~ 2047

Counter device Bit

PW

DDDD

0 ~ 2047

I/O device

MW

DDDD

0 ~ 2047

Internal device

LW

DDDDD

0 ~ 11263

Communication device

KW

DDDD

0 ~ 2559

Preservation device

FW

DDDD

0 ~ 2047

SW

DDDDD

0 ~ 127

Special device( write available


from 1025)
Relay
for step control

DW

DDDDD

0 ~ 32767

Data register

397

register_Bit expression

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

UW

DH.DD

0.00 ~ 3f.31

Analog data register XGK-CPUE : hh(0~1f)

NW

DDDDD

0 ~ 21503

Communication data register

ZW

DDD

0 ~ 127

Index register_128 words

TW

DDDD

0 ~ 2047

Timer current value register

CW

DDDD

0 ~ 2047

Counter current value register

RW

DDDDD

0 ~ 32767

ZRW

DDDDD

0 ~ 32767

TSW

DDDD

0 ~ 2047

Setup value

CSW

DDDD

0 ~ 2047

Setup value

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

XGB RS232 6P
Mini-DIN

2 RX

8 RX

6 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

3 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

XGB RS232 6P
Mini-DIN

2 RX

6 TXD

3 TX

2 RXD

5 GND

3 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

XGB RS232 6P

D-Sub Female

Mini-DIN

2 RX

6 TXD

3 TX

2 RXD

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

XGB RS232 6P
Mini-DIN

2 RX

6 RX

8 RX

6 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

3 GND

398

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

XGB RS232 6P
Mini-DIN

9 RX

6 TXD

6 TX

2 RXD

5 GND

3 GND
View from the
soldering point
of a cable.

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P

COM3 RS232 9P

XGK RS232 9P D-Sub

D-Sub Female

D-Sub Female

Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

XGK RS232 9P D-Sub


Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

XGK RS232 9P D-Sub

D-Sub Female

Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

XGK RS232 9P D-Sub


Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

399

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

XGK RS232 9P D-Sub


Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.40

Mar/10/2011

Added registers: P_Bit, M_Bit, L_Bit, K_Bitetc

V1.60

Jun/18/2012

Change the way to read/write S_Bit.

V1.70

Mar/10/2014

Added registers: R_Bit

V1.80

Feb/10/2015

Changed the naming method of LS registers.

400

PLC Connection Guide

LS XEC Cnet
Supported Series: LS XGB Series XEC CPU with communication module XGL-CH2A.
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS XEC Cnet

PLC I/F

RS232

RS232/RS485

Baud rate

115200

9600 ~ 115200

Data bits

7, 8

Parity

None

Even, Odd, None

Stop bits

1,2

PLC sta. no.

0 ~ 32

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

AW_Bit

DDDDDDh

0 ~ 262143f

Automatic variable bit

IW_Bit

DDD.DD.Dh

0 ~ 127.15.3f

Input device bit

QW_Bit

DDD.DD.Dh

0 ~ 127.15.3f

Output device bit

MW_Bit

DDDDDDh

0 ~ 131071f

Direct variable bit

RW_Bit

DDDDDh

0 ~ 32767f

Direct variable bit

WW_Bit

DDDDDh

0 ~ 65535f

Direct variable bit

FW_Bit

DDDDh

0 ~ 2047f

System flag bit

KW_Bit

DDDDh

0 ~ 8399f

Built-in special flag bit

LW_Bit

DDDDDh

0 ~ 11263f

High speed link flag bit

NW_Bit

DDDDDh

0 ~ 25087f

P2P flag bit

UW_Bit

DD.DD.DDh

0 ~ 31.15.31f

Analog flag bit

AX

DDDDDDD

0 ~ 4194303

IX

DDD.DD.DD

0 ~ 127.15.63

QX

DDD.DD.DD

0 ~ 127.15.63

MX

DDDDDDD

0 ~ 2097151

RX

DDDDDD

0 ~ 524287

WX

DDDDDDD

0 ~ 1048575

FX

DDDDD

0 ~ 32767

KX

DDDDDD

0 ~ 134399
401

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

LX

DDDDDDD

0 ~ 1880223

NX

DDDDDD

0 ~ 401407

UX

DD.DD.DDD

31.15.511

AW

DDDDDD

0 ~ 262143

Automatic variable

IW

DDD.DD.D

0 ~ 127.15.3

Input device

QW

DDD.DD.D

0 ~ 127.15.3

Output device

MW

DDDDDD

0 ~ 131071

Direct variable

RW

DDDDD

0 ~ 32767

Direct variable

WW

DDDDD

0 ~ 65535

Direct variable

FW

DDDD

0 ~ 2047

System flag

KW

DDDD

0 ~ 8399

Built-in special flag

LW

DDDDD

0 ~ 11263

High speed link flag

NW

DDDDD

0 ~ 25087

P2P flag

UW

DD.DD.DD

0 ~ 31.15.31

Analog flag

DW

MD

DDDDD

0 ~ 65535

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 Terminal

2 RX

8 RX

TX

3 TX

7 TX

RX

5 GND

5 GND

SG

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 Terminal

2 RX

TX

3 TX

RX

5 GND

SG

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 Terminal

2 RX

TX

3 TX

RX

5 GND

SG
402

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 Terminal

2 RX

6 RX

8 RX

TX

3 TX

4 TX

7 TX

RX

5 GND

5 GND

5 GND

SG

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 Terminal

9 RX

TX

6 TX

RX

5 GND

SG

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

485-

2 RX+

9 Data+

485+

5 GND

5 GND

GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W Terminal

7 RX-

4 Data-

485-

6 RX+

1 Data+

485+

5 GND

5 GND

GND

403

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

7 Data-

485-

2 RX+

8 Data+

485+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

485-

2 RX+

9 Data+

485+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

485-

2 RX+

9 Data+

485+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W Terminal

1 RX-

7 Data-

485-

2 RX+

8 Data+

485+

5 GND

5 GND

GND

Driver Version:
Version

Date

Description

V1.00

Aug/27/2012

Driver released.

Sep/18/2014

1. UX, IX, QX, MD device types are added.


2. Renamed the bit addresses by adding an uppercase letter
X. Ex: M->MX.

V1.30

3. Renamed the word addresses by adding an uppercase


letter X. Ex: M-> MW.
V1.50

Feb/10/2015

Changed the naming method of LS registers.


404

PLC Connection Guide

LS XEC FEnet (Ethernet)


Supported Series: LS XGB Series XEC CPU with XGL-EFMT ethernet module.
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS XEC FEnet (Ethernet)

PLC I/F

Ethernet

Port no.

2004

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

AW_Bit

DDDDDh

0 ~ 16383f

Automatic variable bit

IW_Bit

DD.DD.Df

0 ~ 15.15.3f

Input device bit

QW_Bit

DD.DD.Df

0 ~ 15.15.3f

Output device bit

MW_Bit

DDDDh

0 ~ 8191f

Direct variable bit

RW_Bit

DDDDDh

0 ~ 10239f

Direct variable bit

WW_Bit

DDDDDh

0 ~ 10239f

Direct variable bit

FW_Bit

DDDDh

0 ~ 1023f

System flag bit

KW_Bit

DDDDh

0 ~ 4095f

Built-in special flag bit

LW_Bit

DDDDh

0 ~ 2047f

High speed link flag bit

NW_Bit

DDDDh

0 ~ 5119f

P2P flag bit

UW_Bit

DD.DD.DDf

0 ~ 31.15.31f

Analog flag bit

AX

DDDDDD

0 ~ 262143

IX

DDD.DD.DD

0 ~ 127.15.63

QX

DDD.DD.DD

0 ~ 127.15.63

MX

DDDDDD

0 ~ 131071

RX

DDDDDD

0 ~ 163839

WX

DDDDDD

0 ~ 163839

FX

DDDDD

0 ~ 16383

KX

DDDDD

0 ~ 65535

LX

DDDDD

0 ~ 32767

NX

DDDDD

0 ~ 81919

UX

DD.DD.DDD

0 ~ 31.15.511

AW

DDDDD

0 ~ 16383
405

Automatic variable

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

IW

DDD.DD.D

0 ~ 15.15.3

Input device

QW

DDD.DD.D

0 ~ 15.15.3

Output device

MW

DDDD

0 ~ 8191

Direct variable

RW

DDDDD

0 ~ 10239

Direct variable

WW

DDDDD

0 ~ 10239

Direct variable

FW

DDDD

0 ~ 1023

System flag

KW

DDDD

0 ~ 4095

Built-in special flag

LW

DDDD

0 ~ 2047

High speed link flag

NW

DDDD

0 ~ 5119

P2P flag

UW

DD.DD.DD

0 ~ 31.15.31

Analog flag

DW

MD

DDDD

0 ~ 4095

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Aug/28/2012

Driver released.

Sep/18/2014

1. UX, IX, QX, MD device types are added.


2. Renamed the bit addresses by adding an uppercase letter
X. Ex: M->MX.

V1.20

3. Renamed the word addresses by adding an uppercase


letter X. Ex: M-> MW.
V1.40

Feb/10/2015

Changed the naming method of LS registers.


406

PLC Connection Guide

LS XEC/XGI CPU DIRECT


Supported Series: LS XEC/XGI CPU RS232 port.
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS XEC/XGI CPU DIRECT

PLC I/F

RS232

RS232

Baud rate

115200

9600~115200

Data bits

7, 8

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

Notes

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

AW_Bit

DDDDDDh

0 ~ 262143f

IW_Bit

DDD.DD.Dh

0 ~ 127.15.3f

QW_Bit

DDD.DD.Dh

0 ~ 127.15.3f

MW_Bit

DDDDDDh

0 ~ 131071f

RW_Bit

DDDDDh

0 ~ 32767f

WW_Bit

DDDDDh

0 ~ 65535f

FW_Bit

DDDDh

0 ~ 2047f

KW_Bit

DDDDh

0 ~ 8399f

LW_Bit

DDDDDh

0 ~ 11263f

NW_Bit

DDDDDh

0 ~ 25087f

UW_Bit

DD.DD.DDh

0 ~ 31.15.31f

AX

DDDDDDD

0 ~ 4194303

IX

DDD.DD.DD

0 ~ 127.15.63

QX

DDD.DD.DD

0 ~ 127.15.63

MX

DDDDDDD

0 ~ 2097151

RX

DDDDDD

0 ~ 524287
407

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

WX

DDDDDDD

0 ~ 1048575

FX

DDDDD

0 ~ 32767

KX

DDDDDD

0 ~ 134399

LX

DDDDDDD

0 ~ 1880223

NX

DDDDDD

0 ~ 401407

UX

DD.DD.DDD

0 ~ 31.15.511

AW

DDDDDD

0 ~ 262143

IW

DDD.DD.D

0 ~ 127.15.3

QW

DDD.DD.D

0 ~ 127.15.3

MW

DDDDDD

0 ~ 131071

RW

DDDDD

0 ~ 32767

WW

DDDDD

0 ~ 65535

FW

DDDD

0 ~ 2047

KW

DDDD

0 ~ 8399

LW

DDDDD

0 ~ 11263

NW

DDDDD

0 ~ 25087

UW

DD.DD.DD

0 ~ 31.15.31

DW

MD

DDDDD

0 ~ 65535

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

XGI CPU RS232 9P


D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

XGI CPU RS232 9P


D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

408

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

XGI CPU RS232 9P


D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

XGI CPU RS232 9P


D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

XGI CPU RS232 9P


D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

May/17/2012

Driver released.

V1.10

Mar/22/2014

V1.30

Sep/18/2014

1. UX, IX, QX, MD device types are added.


2. Renamed the bit addresses by adding an uppercase letter
X. Ex: M->MX.
3. Renamed the word addresses by adding an uppercase
letter X. Ex: M-> MW.

V1.50

Feb/10/2015

Changed the naming method of LS registers.

409

PLC Connection Guide

LS XGI Cnet
Supported Series: LS XGT series XGI CPU series with communication module XGL-CH2A
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

LS XGI Cnet

PLC I/F

RS232

RS232/RS485 4W

Baud rate

115200

9600~115200

Data bits

7, 8

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

0~32

Device Address:
Bit/Word

Device type

Format

Range

AW_Bit

DDDDDDh

0 ~ 262143f

IW_Bit

DDD.DD.Dh

0 ~ 127.15.3f

QW_Bit

DDD.DD.Dh

0 ~ 127.15.3f

MW_Bit

DDDDDDh

0 ~ 131071f

RW_Bit

DDDDDh

0 ~ 32767f

WW_Bit

DDDDDh

0 ~ 65535f

FW_Bit

DDDDh

0 ~ 2047f

KW_Bit

DDDDh

0 ~ 8399f

LW_Bit

DDDDDh

0 ~ 11263f

NW_Bit

DDDDDh

0 ~ 25087f

UW_Bit

DD.DD.DDh

0 ~ 31.15.31f

AX

DDDDDDD

0 ~ 4194303

IX

DDD.DD.DD

0 ~ 127.15.63

QX

DDD.DD.DD

0 ~ 127.15.63

MX

DDDDDDD

0 ~ 2097151

RX

DDDDDD

0 ~ 524287

WX

DDDDDDD

0 ~ 1048575

FX

DDDDD

0 ~ 32767
410

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

KX

DDDDDD

0 ~ 134399

LX

DDDDDDD

0 ~ 1880223

NX

DDDDDD

0 ~ 401407

UX

DD.DD.DDD

0 ~ 31.15.511

AW

DDDDDD

0 ~ 262143

IW

DDD.DD.D

0 ~ 127.15.3

QW

DDD.DD.D

0 ~ 127.15.3

MW

DDDDDD

0 ~ 131071

RW

DDDDD

0 ~ 32767

WW

DDDDD

0 ~ 65535

FW

DDDD

0 ~ 2047

KW

DDDD

0 ~ 8399

LW

DDDDD

0 ~ 11263

NW

DDDDD

0 ~ 25087

UW

DD.DD.DD

0 ~ 31.15.31

DW

MD

DDDDD

0 ~ 65535

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

XGL-CH2A CH1 RS232


9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

XGL-CH2A CH1 RS232


9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

411

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

XGL-CH2A CH1 RS232


9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

XGL-CH2A CH1 RS232


9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

XGL-CH2A CH1 RS232


9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

The following is the view from the soldering point of a cable.


9P D-Sub to Terminals:
eMT3000 series
COM1 RS485 4W

XGL-CH2A CH2 5P

9P D-Sub Male

Terminal

1 RX-

TXD-

2 RX+

TXD+

3 TX-

RXD-

4 TX+

RXD+

5 GND

GND

412

PLC Connection Guide

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

XGL-CH2A CH2 5P
Terminal

7 RX-

TXD-

6 RX+

TXD+

9 TX-

RXD-

8 TX+

RXD+

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

XGL-CH2A CH2 5P
Terminal

1 RX-

1 RX-

TXD-

2 RX+

2 RX+

TXD+

3 TX-

3 TX-

RXD-

4 TX+

4 TX+

RXD+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W

XGL-CH2A CH2 5P

9P D-Sub Male

Terminal

1 RX-

TXD-

2 RX+

TXD+

3 TX-

RXD-

4 TX+

RXD+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

XGL-CH2A CH2 5P

9P D-Sub Female

Terminal

1 RX-

TXD-

2 RX+

TXD+

3 TX-

RXD-

4 TX+

RXD+

5 GND

GND

413

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

May/23/2012

Driver released

V1.20

Sep/18/2014

1. UX, IX, QX, MD device types are added.


2. Renamed the bit addresses by adding an uppercase letter
X. Ex: M->MX.
3. Renamed the word addresses by adding an uppercase
letter X. Ex: M-> MW.

V1.30

Feb/10/2015

Changed the naming method of LS registers.

414

PLC Connection Guide

LS XGI FEnet (Ethernet)


Supported Series: LS XGT series XGI CPU with XGL-EFMT ethernet module.
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS XGI FEnet (Ethernet)

PLC I/F

Ethernet

Port no.

2004

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

AW_Bit

DDDDDDh

0 ~ 262143f

IW_Bit

DDD.DD.Dh

0 ~ 127.15.3f

QW_Bit

DDD.DD.Dh

0 ~ 127.15.3f

MW_Bit

DDDDDDh

0 ~ 131071f

RW_Bit

DDDDDh

0 ~ 32767f

WW_Bit

DDDDDh

0 ~ 65535f

FW_Bit

DDDDh

0 ~ 2047f

KW_Bit

DDDDh

0 ~ 8399f

LW_Bit

DDDDDh

0 ~ 11263f

NW_Bit

DDDDDh

0 ~ 25087f

UW_Bit

DD.DD.DDh

0 ~ 31.15.31f

AX

DDDDDDD

0 ~ 4194303

IX

DDD.DD.DD

0 ~ 127.15.63

QX

DDD.DD.DD

0 ~ 127.15.63

MX

DDDDDDD

0 ~ 2097151

RX

DDDDDD

0 ~ 524287

WX

DDDDDDD

0 ~ 1048575

FX

DDDDD

0 ~ 32767

KX

DDDDDD

0 ~ 134399

LX

DDDDDDD

0 ~ 1880223

NX

DDDDDD

0 ~ 401407

UX

DD.DD.DDD

0 ~ 31.15.511
415

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

AW

DDDDDD

0 ~ 262143

IW

DDD.DD.D

0 ~ 127.15.3

QW

DDD.DD.D

0 ~ 127.15.3

MW

DDDDDD

0 ~ 131071

RW

DDDDD

0 ~ 32767

WW

DDDDD

0 ~ 65535

FW

DDDD

0 ~ 2047

KW

DDDD

0 ~ 8399

LW

DDDDD

0 ~ 11263

NW

DDDDD

0 ~ 25087

UW

DD.DD.DD

0 ~ 31.15.31

DW

MD

DDDDD

0 ~ 65535

Memo

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

May/21/2012

Driver released.

Sep/18/2014

1. UX, IX, QX, MD device types are added.


2. Renamed the bit addresses by adding an uppercase letter
X. Ex: M->MX.

V1.20

3. Renamed the word addresses by adding an uppercase


letter X. Ex: M-> MW.
V1.40

Feb/10/2015

Changed the naming method of LS registers.


416

PLC Connection Guide

LS XGK Cnet
Supported Series: LS XGT series XGK CPU with communication module XGL-CH2A
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS XGK Cnet

PLC I/F

RS232

RS232/RS485 4W

Baud rate

115200

9600~115200

Data bits

7, 8

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

0~32

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

PW_Bit

DDDDh

0 ~ 2047f

I/O device Bit

MW_Bit

DDDDh

0 ~ 2047f

Internal device Bit

LW_Bit

DDDDDh

0 ~ 11263f

Communication device Bit

KW_Bit

DDDDh

0 ~ 2559f

Preservation device Bit

FW_Bit

DDDDh

0 ~ 2047f

Special device Bit( write


available from 1025)

DW_Bit

DDDDDh

0 ~ 32767f

Data register_Bit expression (D0000.0)

UW_Bit

DH.DDh

0 ~ 3f.31f

XGK-CPUE : hh(0~1f)

SX

DDDDD

0 ~ 12799

Relay for step control Bit

TX

DDDD

0 ~ 2047

Timer device Bit

CX

DDDD

0 ~ 2047

Counter device Bit

PW

DDDD

0 ~ 2047

I/O device

MW

DDDD

0 ~ 2047

Internal device

LW

DDDDD

0 ~ 11263

Communication device

KW

DDDD

0 ~ 2559

Preservation device

FW

DDDD

0 ~ 2047

Special device( write available from 1025)

DW

DDDDD

0 ~ 32767

Data register

UW

DH.DD

0.00 ~ 3f.31

Analog data register XGK-CPUE : hh(0~1f)

417

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

RW

DDDDD

0 ~ 32767

ZRW

DDDDD

0 ~ 32767

NW

DDDDD

0 ~ 21503

Communication data register

ZW

DDD

0 ~ 127

Index register_128 words

SW

DDDDD

0 ~ 127

Relay for step control

TW

DDDD

0 ~ 2047

Timer current value register

CW

DDDD

0 ~ 2047

Counter current value register

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

XGL-CH2A CH1 RS232


9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

XGL-CH2A CH1 RS232


9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

XGL-CH2A CH1 RS232


9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

XGL-CH2A CH1 RS232


9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

418

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

XGL-CH2A CH1 RS232


9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

The following is the view from the soldering point of a cable.


9P D-Sub to Terminals:
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

XGL-CH2A CH2 5P
Terminal

1 RX-

TXD-

2 RX+

TXD+

3 TX-

RXD-

4 TX+

RXD+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

XGL-CH2A CH2 5P
Terminal

7 RX-

TXD-

6 RX+

TXD+

9 TX-

RXD-

8 TX+

RXD+

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

XGL-CH2A CH2 5P
Terminal

1 RX-

1 RX-

TXD-

2 RX+

2 RX+

TXD+

3 TX-

3 TX-

RXD-

4 TX+

4 TX+

RXD+

5 GND

5 GND

GND

419

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

XGL-CH2A CH2 5P
Terminal

1 RX-

TXD-

2 RX+

TXD+

3 TX-

RXD-

4 TX+

RXD+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

XGL-CH2A CH2 5P
Terminal

1 RX-

TXD-

2 RX+

TXD+

3 TX-

RXD-

4 TX+

RXD+

5 GND

GND

Driver Version:
Version

Date

Description

V1.30

Feb /25/2011

Added registers: P_Bit, M_Bit, L_Bit, K_Bitetc

V1.40

Jun/20/2012

Change the way to read/write S_Bit.

V1.60

Feb/10/2015

Changed the naming method of LS registers.

420

PLC Connection Guide

LS XGK FEnet (Ethernet)


Supported Series: LS XGT series XGK CPU with XGL-EFMT ethernet module.
Website: http://www.lgis.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

LS XGK FEnet (Ethernet)

PLC I/F

Ethernet

Port no.

2004

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type Format

Range

Memo

PW_Bit

DDDDh

0 ~ 2047f

I/O device Bit

MW_Bit

DDDDh

0 ~ 2047f

Internal device Bit

LW_Bit

DDDDDh

0 ~ 11263f

Communication device Bit

KW_Bit

DDDDh

0 ~ 2559f

Preservation device Bit

FW_Bit

DDDDh

0 ~ 2047f

DW_Bit

DDDDDh

0 ~ 32767f

Data register_Bit expression (D0000.0)

UW_Bit

DH.DDh

0 ~ 3f.31f

XGK-CPUE : hh(0~1f)

SX

DDDDD

0 ~ 12799

Relay for step control Bit

TX

DDDD

0 ~ 2047

Timer device Bit

CX

DDDD

0 ~ 2047

Counter device Bit

PW

DDDD

0 ~ 2047

I/O device

MW

DDDD

0 ~ 2047

Internal device

LW

DDDDD

0 ~ 11263

Communication device

KW

DDDD

0 ~ 2559

Preservation device

FW

DDDD

0 ~ 2047

Special device( write available from 1025)

SW

DDDDD

0 ~ 127

Relay for step control

DW

DDDDD

0 ~ 32767

Data register

UW

DH.DD

0.00 ~ 3f.31

Analog data register XGK-CPUE : hh(0~1f)

NW

DDDDD

0 ~ 21503

Communication data register

ZW

DDD

0 ~ 127

Index register_128 words

421

Special device Bit( write available


from 1025)

PLC Connection Guide

Bit/Word

Device type Format

Range

Memo

TW

DDDD

0 ~ 2047

Timer current value register

CW

DDDD

0 ~ 2047

Counter current value register

RW

DDDDD

0 ~ 32767

ZRW

DDDDD

0 ~ 32767

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.30

Mar/10/2011

Added registers: P_Bit, M_Bit, L_Bit, K_Bitetc

V1.40

Jun/19/2012

Change the way to read/write S_Bit.

V1.50

Feb/10/2015

Changed the naming method of LS registers.

422

PLC Connection Guide

LS Mecapion Metronix AnyPack


HMI Setting:
Parameters

Recommended

Options

PLC type

LS Mecapion Metronix AnyPack

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device Type

Format

Range

Memo

MX_L16bit

DDDDDdd

0 ~ 9999915

MD Low 16bit

MX_H16bit

DDDDDdd

0 ~ 9999915

MD High 16bit

DW

MD

DDDD

0 ~ 9999

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P

COM3 RS232 9P

PLC RS232 Terminal

D-Sub Female

D-Sub Female

2 RX

8 RX

6 TX

3 TX

7 TX

5 RX

5 GND

5 GND

11 GND
12 GND

423

short

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

PLC RS232 Terminal

2 RX

6 TX

3 TX

5 RX

5 GND

11 GND
12 GND

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

PLC RS232 Terminal

D-Sub Female
2 RX

6 TX

3 TX

5 RX

5 GND

11 GND
12 GND

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

PLC RS232 Terminal

2 RX

6 RX

8 RX

6 TX

3 TX

4 TX

7 TX

5 RX

5 GND

5 GND

5 GND

11 GND
12 GND

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

PLC RS232 Terminal

9 RX

6 TX

6 TX

5 RX

5 GND

11 GND
12 GND

Driver Version:
Version

Date

V1.00

Jul/1/2008

Description

424

short

PLC Connection Guide

Master-Slave Server
For more information, please refer to Users Manual CH28.

HMI Setting:
Parameters

Recommended

Options

PLC type

Master-Slave Server

PLC I/F

RS232

RS232/RS485

Baud rate

115200

9600~115200

Data bits

7,8

Parity

Even

None,Even,Odd,Mark,Space

Stop bits

1,2

HMI sta. no.

PLC sta. no.

Notes

FOR MT500 HMI Setting:


Parameters

Recommended

Options

PLC type

Master (Master-Slave Protocol)

PLC I/F

RS232

Baud rate

115200

Data bits

Parity

Even

Stop bits

HMI sta. no.

PLC sta. no.

Parameter 1

MT500 PLC ID

Notes

38400, 115200

Use PLCAddressView.exe to find PLC ID.

425

PLC Connection Guide

To connect HMI with MT500, MT500 has to be set as [Slave].

PLC Setting:
Communication mode

MT500 Multiple HMI set Slave.

426

PLC Connection Guide

Device Address:
Bit/Word MT500

MT8000

Range

Memo

Ms_RB

RW_Bit

dddd: 0 ~ 4095
(h): 0 ~ f

Ms_LB

LB

dddd:0 ~ 9999

Ms_RW

RW

ddddd:0 ~ 65535

Ms_LW

LW

dddd:0 ~ 9999

Driver Version:
Version

Date

Description

V1.00

Dec/30/2008

Driver released.

427

PLC Connection Guide

MEGMEET MC Series
Supported Series: MEGMEET MC Series (Modbus RTU Protocol)

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

MEGMEET MC Series

PLC I/F

RS232

Baud rate

9600

9600, 19200, 115200

Data bits

7 or 8

Parity

Even

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

0-255

PLC Setting:
Communication mode

Modbus RTU protocol

Device Address:
Bit/Word Device type

Format

Range

Memo

OOO

0 ~ 377

1200~01455 0000~0255

OOO

0 ~ 377

0000~0255

DDDDD

0 ~ 10239

2000~2047 12000~20191

SM

DDD

0 ~ 511

4400~4655 30000~30255

DDDD

0 ~ 4095

6000~7023 31000~34071

T_Bit

DDD

0 ~ 511

8000~8255

C_Bit

DDD

0 ~ 306

9200~9455 10000~10050

D_Bit

DDDDdd

0 ~ 799915

R_Bit

DDDDDdd

0 ~ 3276715

DDDD

0 ~ 7999

0000~7999

DW

D_Double

DDDD

0 ~ 7998

0000~7999

SD

DDD

0 ~ 255

8000~8255 12000~12255

DW

SD_Double

DDD

0 ~ 510

8000~8255 12000~12255

DD

0 ~ 15

8500~8515

DDD

0 ~ 511

9000~9255 11000~11255

428

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo

DDD

0 ~ 199

9500~9699

DW

C_Double

DDD

200 ~ 306

9700~10101

DDDDD

0 ~ 32767

13000~45767

DW

R_Double

DDDDD

0 ~ 32766

13000~45767

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

MC Series COM1
terminal

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

MC Series COM1
terminal

2 RX

TXD

3 TX

RXD

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

MC Series COM1
terminal

2 RX

TXD

3 TX

RXD

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND

429

MC Series COM1
terminal

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

MC Series COM1
terminal

9 RX

TXD

6 TX

RXD

5 GND

GND

Driver Version:
Version

Date

Description

V1.00

Nov/16/2012

Driver released.

V1.10

May/06/2014

Added register: D_Bit

V1.20

May/19/2014

Added register: R_Bit

430

PLC Connection Guide

MEIKONG Metro Safe Server


Supported Series: MEIKONG Metro Safe Server
Website: http://www.xiemaowang.com/detail/2079110.html

HMI Setting:
Parameters

Recommended

Options

PLC type

MEIKONG Metro Safe Server

PLC I/F

RS4852W

RS232/RS485

Baud rate

9600

9600~115200

Data bits

7,8

Parity

None

Even,Odd,None

Stop bits

1,2

PLC sta. no.

0~252

Notes

In COM Port Settings, the data read will be stored in 25 consecutive addresses start from
[Data save address (LW)] as shown below. Data will be stored in LW-100 to LW-124.

431

PLC Connection Guide

Protocol:
Byte

Description

AA

E0

2
3

C5 (The first 3 bytes are fixed, which represents the start of the
message.)
Addressrange 0-252

Date-Year tens digit

Date-Year unit digit

Date-Month tens digit

Date-Month unit digit

Date-Day tens digit

Date-Day unit digit

10

Time-Hour tens digit

11

Time -Hour unit digit

12

Time -Minute

tens digit

13

Time -Minute

unit digit

14

Time -Second tens digit

15
16

Time -Second unit digit


1-Manual2-Automatic

17

The number of slaves.

18
19

The sequence number of slave.


Slave status1-Normal2-Warning3-Emergency4-Disconnected

20

Backup power1-normal2-abnormal voltage3- disconnect


4-short

21

00

22

00

23

EE

24

BB(The last 4 bytes are fixed, which represents the end of the
message.)

432

PLC Connection Guide

Wiring Diagram:
The following represents the view of HMI & PLC.
[RS232]
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND
RTS
CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub

D-Sub Female

FeMale

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
FeMale

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND
RTS
CTS

433

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

9 RX

TXD

6 TX

RXD

5 GND

GND
RTS
CTS

short

The following represents the view of HMI & PLC.


[RS485 4W]
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND
434

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Female

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

The following represents the view of HMI & PLC.


[RS485 2W]
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

cMT/mTV series

435

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Female

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

Driver Version:
Version

Date

Description

V1.00

Oct/24/2012

Driver released.

436

PLC Connection Guide

Memory Map
Memory Map protocol is similar to IBM 3764R communication protocol. EasyBuilder
reserves 512 words of data memory to use with this protocol. EasyBuilder must update the
values in these words. EasyBuilder uses these words to display data and control parts
status on screen. When touch actions are taken, data is sent to the others once, and then
update the memory in it. The HMI should always update the data memory.

HMI Setting:
Parameters

Recommended Options

PLC type

Memory Map

PLC I/F

RS232

Baud rate

115200

Data bits

Parity

Even

Stop bits

Notes

RS232, RS485
4W, 2W
9600~115200

RS232 default

Even, Odd, None

Device Address:
Bit/Word

Device type

Format

Range

MB

DDDDh

0 ~ 4095f

MW

DDDD

0 ~ 9999

Memo

MB and MW share the same data storage.


MW 0 = MB 00000 ~ MB 0000f, MW 1 = MB 00010 ~ MB 0001f

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

HMI COM1 RS232 9P


D-Sub Female

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

437

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

HMI COM1 RS232 9P


D-Sub Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

HMI COM1 RS232 9P


D-Sub Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

HMI COM1 RS232 9P


D-Sub Female

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

HMI COM1 RS232 9P


D-Sub Female

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

HMI COM1 RS485 2W


9P D-Sub Male

1 RX-

6 Data-

1 RX-

2 RX+

9 Data+

2 RX+

5 GND

5 GND

5 GND

438

PLC Connection Guide

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

HMI COM1 RS485 2W


9P D-Sub Male

7 RX-

4 Data-

1 RX-

6 RX+

1 Data+

2 RX+

5 GND

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

HMI COM1 RS485 2W


9P D-Sub Male

1 RX-

7 Data-

1 RX-

2 RX+

8 Data+

2 RX+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

HMI COM1 RS485 2W


9P D-Sub Male

1 RX-

6 Data-

1 RX-

2 RX+

9 Data+

2 RX+

5 GND

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

HMI COM1 RS485 2W


9P D-Sub Male

1 RX-

6 Data-

1 RX-

2 RX+

9 Data+

2 RX+

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W

COM3 RS485 2W

HMI COM1 RS485 2W

9P D-Sub Female

9P D-Sub Female

9P D-Sub Female

1 RX-

7 Data-

1 RX-

2 RX+

8 Data+

2 RX+

5 GND

5 GND

5 GND

439

PLC Connection Guide

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 4W
9P D-Sub Male

HMI COM1 RS485 4W


9P D-Sub Male

1 RX-

3 TX-

2 RX+

4 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

5 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

HMI COM1 RS485 4W


9P D-Sub Male

7 RX-

3 TX-

6 RX+

4 TX+

9 TX-

1 RX-

8 TX+

2 RX+

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

HMI COM1 RS485 4W


9P D-Sub Male

1 RX-

3 TX-

2 RX+

4 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

HMI COM1 RS485 4W


9P D-Sub Male

1 RX-

3 TX-

2 RX+

4 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

5 GND

440

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

HMI COM1 RS485 4W


9P D-Sub Female

1 RX-

3 TX-

2 RX+

4 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

5 GND

Note:
For Memory map information, please refer to Users Manual Chapter 31 Memory Map
Communication.

Driver Version:
Version

Date

Description

V1.00

Mar/19/2009

Driver released.

441

PLC Connection Guide

MIKOM MX Series PLC


Support series: MIKOM MX series PLC
Web: http://www.mikom.com.cn/

HMI Setting:
Parameters

Recommended

PLC type

MIKOM MX Series PLC

PLC I/F

RS232

RS232/485/Ethernet

Baud rate

19200

9600~115200

Data bits

Even

None,Even,Odd

Parity

Stop bits

1,2

PLC sta. no.

0~31

Online simulator

Options

YES

PLC Setting:
PORT 0(RS232 Setting)

442

Notes

PLC Connection Guide

PORT 1(RS485 Setting)

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDD

0~777

Output Relay

DDD

0~777

Input Relay

DDDD

0~4095

Auxiliary Relay

SM

DDD

0-511

Special Auxiliary Relay

DDDD

0~1535

Step Relay

DDD

0~511

Timer Relay

DDD

0~511

Counter Relay

DDDDD

0~32767

Data Register

SD

DDD

0~511

Special Data Register

DDD

0~255

Indexed Addressing Register

DDD

0~511

Timer

DDD

0~199

Counter

U0

DDD

0~199

Special Module Register

U1

DDD

0~199

Special Module Register

U2

DDD

0~199

Special Module Register

U3

DDD

0~199

Special Module Register

U4

DDD

0~199

Special Module Register

U5

DDD

0~199

Special Module Register

U6

DDD

0~199

Special Module Register

U7

DDD

0~199

Special Module Register

DW

C-32bit

DDD

200~511

32 Bit Counter

443

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 8P Mini-DIN
Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND
View from the
soldering point
of a cable.

444

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

May/3/2012

Driver released.

445

PLC Connection Guide

Mitsubishi A1S/A2N
Supported Series: Mitsubishi A1S/A2N
Website: http://www.mitsubishi-automation.com/

HMI Setting:
Parameters

Recommended

PLC type

Mitsubishi A1S/A2N

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Options

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

HHHH

0 ~ ffff

Input Relay

HHHH

0 ~ ffff

Output Relay

DDDDD

0 ~ 65535

Auxiliary Relay

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

TV

DDDDD

0 ~ 65535

Timer Memory

CV

DDDDD

0 ~ 65535

Counter Memory

DDDDD

0 ~ 65535

Data Register

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

446

PLC Connection Guide

Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
MITSUBISHI AnS CPU

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

447

17 DSR-

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

17 DSR-

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

Driver Version:
Version

Date

Description

V1.00

Sep/18/2009

Driver released.

448

17 DSR-

PLC Connection Guide

Mitsubishi A2A/A2U/A2AS/A2USH
Supported Series: Mitsubishi A2A,A2U,A2AS,A2USH
Website: http://www.mitsubishi-automation.com/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Mitsubishi A2A/A2U/A2AS/A2USH

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Parameter 1

0~8

File register (0~8) K

Parameter 2

0~1

Set A2A and A2USH to 1

Device Address:
Bit/Word

Device type

Format

Range

Memo

HHHH

0 ~ 270f

Input Relay

HHHH

0 ~ 270f

Output Relay

DDDD

0 ~ 9999

Auxiliary Relay

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

TV

DDD

0 ~ 255

Timer Memory

CV

DDD

0 ~ 255

Counter Memory

DDDD

0 ~ 9999

Data Register

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

449

PLC Connection Guide

Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
MITSUBISHI AnS CPU

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

450

17 DSR-

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

17 DSR-

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

Driver Version:
Version

Date

Description

V1.00

Aug/12/2009

Driver released.

451

17 DSR-

PLC Connection Guide

Mitsubishi A2US
Supported Series: Mitsubishi A2US
Website: http://www.mitsubishi-automation.com/

HMI Setting:
Parameters

Recommended

PLC type

Mitsubishi A2US

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Options

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

HHHH

0 ~ 270f

Input Relay

HHHH

0 ~ 270f

Output Relay

DDDD

0 ~ 9999

Auxiliary Relay

TV

DDD

0 ~ 255

Timer Memory

CV

DDD

0 ~ 255

Counter Memory

DDDD

0 ~ 9999

Data Register

452

PLC Connection Guide

Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
MITSUBISHI AnS CPU

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

453

17 DSR-

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

17 DSR-

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

Driver Version:
Version

Date

Description

V1.00

Mar/20/2009

Driver released.

454

17 DSR-

PLC Connection Guide

Mitsubishi A3A/A3N/A1SH/A2SH
Supported Series: Mitsubishi A3A,A3N,A1SH,A2SH
Website: http://www.mitsubishi-automation.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

Mitsubishi A3A/A3N/A1SH/A2SH

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Notes

Note: This driver is not available for On-line Simulation.

Device Address:
Bit/Word

Device type

Format

Range

Memo

HHHH

0 ~ ffff

Input Relay

HHHH

0 ~ ffff

Output Relay

DDDDD

0 ~ 65535

Auxiliary Relay

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

TV

DDDDD

0 ~ 65535

Timer Memory

CV

DDDDD

0 ~ 65535

Counter Memory

DDDDD

0 ~ 65535

Data Register

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

455

PLC Connection Guide

Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
MITSUBISHI AnS CPU

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

456

17 DSR-

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

17 DSR-

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

PLC Programming Converter

Mitsubishi RS422 25P


D-Sub Male

2 RX

TX

TX+

2 RX+

3 TX

RX

RX+

3 TX+

5 GND

GND

DTR+

4 DSR+

7 RTS

CTS

GND

7 GND

8 CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

Driver Version:
Version

Date

Description

V1.00

Oct/20/2009

Driver released.

457

17 DSR-

PLC Connection Guide

Mitsubishi AJ71
Supported Series: Mitsubishi A series PLC with AJ71C24 communication module using
the Computer Link protocol.
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Mitsubishi AJ71

Mitsubishi AJ71 (AnA/AnU


CPU), Mitsubishi AJ71
(Format 4)

PLC I/F

RS485 4W

RS485 4W, RS232

Baud rate

19200

9600, 19200

Data bits

Parity

Even

Even, Odd, None

Stop bits

PLC sta. no.

PLC Setting:
Communication mode

Computer Link protocol 9600, Even, 8, 1 (default)

Mode setting switch

Format 1

Parity check

Enable

Sum check

Enable

Device Address:
Bit/Word

Device type

Format

Range

Memo

HHHH

0 ~ ffff

Input Bits

HHHH

0 ~ ffff

Output Bits

DDDDD

0 ~ 65535

Internal Relays

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

HHHH

0 ~ ffff

DDDDD

0 ~ 65535
458

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

TV

DDDDD

0 ~ 65535

Timer Preset Value

CV

DDDDD

0 ~ 65535

Counter Preset Value

DDDDD

0 ~ 65535

Data Registers

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

Wiring Diagram:
The following is the view from the soldering point of a cable.
AJ71C24 RS422
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

AJ71C24 RS422
Terminal

1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

AJ71C24 RS422
Terminal

7 RX-

SDB

6 RX+

SDA

9 TX-

RDB

8 TX+

RDA

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

AJ71C24 RS422
Terminal

1 RX-

1 RX-

SDB

2 RX+

2 RX+

SDA

3 TX-

3 TX-

RDB

4 TX+

4 TX+

RDA

5 GND

5 GND

GND

459

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

AJ71C24 RS422
Terminal

1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

AJ71C24 RS422
Terminal

1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

GND

The following is the view from the soldering point of a cable.


A1SJ71UC24-R2
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

460

short

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

461

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

Driver Version:
Version

Date

V1.60

Nov/30/2012

Description

462

short

PLC Connection Guide

Mitsubishi AJ71 (AnA/AnU CPU)


Supported Series: Mitsubishi AJ71 (AnA/AnU CPU)
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Mitsubishi AJ71 (AnA/AnU CPU)

PLC I/F

RS485 4W

RS485 4W, RS232

Baud rate

19200

9600, 19200

Data bits

Parity

Even

Even, Odd, None

Stop bits

PLC sta. no.

Notes

PLC Setting:
Communication mode

Computer Link protocol 9600, Even, 8, 1 (default)

Mode setting switch

Format 1

Parity check

Enable

Sum check

Enable

Device Address:
Bit/Word

Device type

Format

Range

Memo

HHHH

0 ~ ffff

Input Bits

HHHH

0 ~ ffff

Output Bits

DDDDD

0 ~ 65535

Internal Relays

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

TV

DDDDD

0 ~ 65535

Timer Preset Value

CV

DDDDD

0 ~ 65535

Counter Preset Value

DDDDD

0 ~ 65535

Data Registers

HHHH

0 ~ ffff

DDDDD

0 ~ 65535
463

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS422 Terminal

1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS422 Terminal

7 RX-

SDB

6 RX+

SDA

9 TX-

RDB

8 TX+

RDA

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS422 Terminal

1 RX-

1 RX-

SDB

2 RX+

2 RX+

SDA

3 TX-

3 TX-

RDB

4 TX+

4 TX+

RDA

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS422 Terminal

1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

GND

464

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS422 Terminal

1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

465

short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

466

short

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Oct/31/2011

Driver released.

467

PLC Connection Guide

Mitsubishi AJ71 (Format 4)


Supported Series: Mitsubishi A series PLC with AJ71C24 communication module using
the Computer Link protocol.
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Mitsubishi AJ71 (Format 4)

PLC I/F

RS485 4W

RS485 4W, RS232

Baud rate

19200

9600, 19200

Data bits

Parity

Even

Even, Odd, None

Stop bits

PLC sta. no.

PLC Setting:
Communication mode

Computer Link protocol 9600, Even, 8, 1 (default)

Mode setting switch

Format 4

Parity check

Enable

Sum check

Enable

Device Address:
Bit/Word

Device type

Format

Range

Memo

HHHH

0 ~ ffff

Input Bits

HHHH

0 ~ ffff

Output Bits

DDDDD

0 ~ 65535

Internal Relays

DDDDD

0 ~ 65535

DDDDD

0 ~ 65535

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

TV

DDDDD

0 ~ 65535

Timer Preset Value

CV

DDDDD

0 ~ 65535

Counter Preset Value

DDDDD

0 ~ 65535

Data Registers

HHHH

0 ~ ffff

DDDDD

0 ~ 65535

468

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

AJ71C24 RS422
Terminal

1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series

SDB
SDA
RDB
RDA
GND

COM2 RS485 4W
9P D-Sub Female

AJ71C24 RS422
Terminal

7 RX-

SDB

6 RX+

SDA

9 TX-

RDB

8 TX+

RDA

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

AJ71C24 RS422
Terminal

1 RX-

1 RX-

SDB

2 RX+

2 RX+

SDA

3 TX-

3 TX-

RDB

4 TX+

4 TX+

RDA

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

AJ71C24 RS422
Terminal

1 RX2 RX+
3 TX4 TX+
5 GND

SDB
SDA
RDB
RDA
GND

469

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

AJ71C24 RS422
Terminal

1 RX2 RX+
3 TX4 TX+
5 GND

SDB
SDA
RDB
RDA
GND

The following is the view from the soldering point of a cable.


A1SJ71UC24-R2
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

470

short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

471

short

PLC Connection Guide

Driver Version:
Version

Date

V1.00

Mar/08/2010

Description

472

PLC Connection Guide

Mitsubishi F930GOT Server


Supported Series: F930GOT general-purpose communication Type 1.

HMI Setting:
Parameters

Recommended

Options

PLC type

F930GOT Server

PLC I/F

RS232

Baud rate

38400

9600, 115200

Data bits

7 or 8

Parity

None

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

RB

DDDD

0 ~ 2047

RW

DDDDD

0 ~ 65535

Memo

Note: In PLC name drop - down menu dont select F930GOT Server.
Please select Local HMI, Device Type=RW.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Micro Computer Board


RS232 Female

2 RX

8 RX

3 TD

3 TX

7 TX

2 RD

5 GND

5 GND

5 GND

473

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Micro Computer Board


RS232 Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

Micro Computer Board


RS232 Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Micro Computer Board


RS232 Female

2 RX

6 RX

8 RX

3 TD

3 TX

4 TX

7 TX

2 RD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

Micro Computer Board


RS232 Female

9 RX

3 TD

6 TX

2 RD

5 GND

5 GND

474

PLC Connection Guide

Protocol:
Read Command:
PC HMI
Read address
02 0

Size

CR

02 30 30 30 30 30 30 32 0D
Read RW0 1 word (2 bytes) STX = 0x02, 0 = Read command, CR = 0x0D
Read address (hexadecimal)
0 ~ FFFF = RW0 ~ 65535
Size (hexadecimal)
2 ~ FE = 2 ~ 254 bytes = 1 ~ 127 word.
Size must be even.
HMI PC (response)
Data1 Data2 . CR
02
02 30 30 31 30 0D
RW0 = 0x0010 = 16
Write Command:
PC HMI
Read address
02 1

Size

Data1

Data2

CR
.

02 31 30 30 30 30 30 32 12

34 0D

Write RW0 = 0x1234


Read address (hexadecimal)
0 ~ FFFF = RW0 ~ 65535
Size (hexadecimal)
2 ~ FE = 2 ~ 254 bytes = 1 ~ 127 word.
Size must be even.
HMI PC (response)
06
ACK = 0x06

Driver Version:
Version

Date

Description

V1.00

Aug/14/2009

Driver released.
475

PLC Connection Guide

Mitsubishi FX0S/FX0N/FX1S/FX1N/FX2
Supported Series: Mitsubishi FX0S/FX0N/FX1S/FX1N/FX2/FX3S
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Mitsubishi FX0S/FX0N/FX1S/FX1N/FX2

PLC I/F

RS485 4W

RS232/RS485

Baud rate

9600

9600/19200/38400/57600/115200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1,2

PLC sta. no.

0-255

Notes

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode
*[Send RESET when power on] selection is provided in PLC COM Port Settings. If enabled,
PLC can be reset when HMI is powered ON.

476

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

Memo

OOO

0 ~ 377

Input Relay

OOO

0 ~ 377

Output Relay

DDDD

0 ~ 9999

Auxiliary Relay

DDD

0 ~ 255

Timer Relay

DDD

0 ~ 255

Counter Relay

SM

DDDD

8000 ~ 9999

Special Aux. Relays

D_Bit

DDDDdd

0 ~ 999915

Data Register Bit (D)

DDDD

0 ~ 4095

States

TV

DDD

0 ~ 255

Timer Memory

CV

DDD

0 ~ 199

Counter Memory

DDDD

0 ~ 9999

Data Register

DW

CV2

DDD

200 ~ 255

Counter Memory(D Word)

SD

DDDD

8000 ~ 9999

Special Data Register

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series

4 TX7 TX+
1 RX2 RX+
3 GND

COM2 RS485 4W
9P D-Sub Female

RS422 Port 8P
Mini-DIN Male

7 RX-

4 TX-

6 RX+

7 TX+

9 TX-

1 RX-

8 TX+

2 RX+

5 GND

3 GND

477

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX-

1 RX-

4 TX-

2 RX+

2 RX+

7 TX+

3 TX-

3 TX-

1 RX-

4 TX+

4 TX+

2 RX+

5 GND

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX2 RX+
3 TX4 TX+
5 GND
MT6050i/MT8050i/MT8050iE

4 TX7 TX+
1 RX2 RX+
3 GND

COM1 RS485 4W

RS422 Port 8P

9P D-Sub Female

Mini-DIN Male

1 RX2 RX+
3 TX4 TX+
5 GND

4 TX7 TX+
1 RX2 RX+
3 GND
View from the
soldering point
of a cable.

478

PLC Connection Guide

The following is the view from the soldering point of a cable..


9P D-Sub to 25P D-Sub:
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS422 Port 25P D-Sub


Male

1 RX-

16 TXD-

2 RX+

3 TXD+

3 TX-

15 RXD-

4 TX+

2 RXD+

5 GND

7 GND
4 DSR+

Short

8 GND
13 +5V
17 DSR-

Short

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS422 Port 25P D-Sub


Male

7 RX-

16 TXD-

6 RX+

3 TXD+

9 TX-

15 RXD-

8 TX+

2 RXD+

5 GND

7 GND
4 DSR+

Short

8 GND
13 +5V
17 DSR-

Short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS422 Port 25P D-Sub


Male

1 RX-

1 RX-

16 TXD-

2 RX+

2 RX+

3 TXD+

3 TX-

3 TX-

15 RXD-

4 TX+

4 TX+

2 RXD+

5 GND

5 GND

7 GND
4 DSR+

Short

8 GND
13 +5V
17 DSR479

Short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS422 Port 25P D-Sub


Male

1 RX-

16 TXD-

2 RX+

3 TXD+

3 TX-

15 RXD-

4 TX+

2 RXD+

5 GND

7 GND
4 DSR+

short

8 GND
13 +5V
17 DSR-

short

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS422 Port 25P D-Sub


Male

1 RX-

16 TXD-

2 RX+

3 TXD+

3 TX-

15 RXD-

4 TX+

2 RXD+

5 GND

7 GND
4 DSR+

short

8 GND
13 +5V
17 DSR-

Driver Version:
Version

Date

V1.20

Oct/26/2011

Description

480

short

PLC Connection Guide

Mitsubishi FX232/485BD
Supported Series: Mitsubishi FX0N/FX2/FX2N COM for Communication Module BD
FX2N-485-BD, FX2N-232-BD, FX1N-485-BD, FX1N-232-BD & FX3U-485ADP.
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Mitsubishi FX232/485BD

PLC I/F

RS232/RS485

RS232/RS485 2w/4w

Baud rate

19200

9600/19200/38400

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1,2

PLC sta. no.

0-15

in accordance with the BD


module

Note: It is recommended to set turn around delay to 8. (For RS485 2W)


Online simulator YES

Extend address mode YES

PLC Setting:
Communication mode

Must set PLC station when useing BD Module.

Register D8120 setting: set b9 and b8 of BFM#0 to 0.

FX2N-485-BD, FX1N-485-BD

FX2N-232-BD, FX1N-232-BD

481

PLC Connection Guide

Device Address:
Bit/Word Device type

Format

Range

Memo

OOO

0 ~ 377

Input Relay

OOO

0 ~ 377

Output Relay

DDDD

0 ~ 7999

Auxiliary Relay

DDD

0 ~ 511

Timer Relay

DDD

0 ~ 255

Counter Relay

SM

DDDD

8000 ~ 9999

Special Auxiliary Relay

D_Bit

DDDDh

0 ~ 7999f

Data Register Bit

DDDD

0 ~ 4095

State Relay

TV

DDD

0 ~ 511

Timer Memory

CV

DDD

0 ~ 199

Counter Memory

DDDD

0 ~ 7999

Data Register

CV2

DDD

200 ~ 255

Counter Memory(D Word)

SD

DDDD

8000 ~ 9999

Special Data Register

DDDDD 0 ~ 32767

Extended Register

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub: Communication Module RS232BD
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

482

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

The following is the view from the soldering point of a cable.


Communication Module RS485BD: RS485 4W
eMT3000 series
COM1 RS485 4W

485BD Module 5P

9P D-Sub Male

Termanal

1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

SG

483

PLC Connection Guide

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

485BD Module 5P
Termanal

7 RX-

SDB

6 RX+

SDA

9 TX-

RDB

8 TX+

RDA

5 GND

SG

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

485BD Module 5P
Termanal

1 RX-

1 RX-

SDB

2 RX+

2 RX+

SDA

3 TX-

3 TX-

RDB

4 TX+

4 TX+

RDA

5 GND

5 GND

SG

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W

485BD Module 5P

9P D-Sub Male

Termanal

1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

SG

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

485BD Module 5P

9P D-Sub Female

Termanal

1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

SG

484

PLC Connection Guide

The following is the view from the soldering point of a cable.


Communication Module RS485BD: RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

485BD Module 5P
Termanal

1 RX-

6 Data-

SDB
RDB

2 RX+

9 Data+

SDA
RDA

5 GND

short
short

5 GND

SG

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

Change RS485 terminal

7 RX-

4 Data-

SDB

cMT/mTV series

RDB
6 RX+

1 Data+

SDA
RDA

5 GND

5 GND

short
short

SG

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Change RS485 terminal

1 RX-

7 Data-

SDB
RDB

2 RX+

8 Data+

SDA
RDA

5 GND

9 GND

short
short

SG

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Change RS485 terminal

1 RX-

6 Data-

SDB
RDB

2 RX+

9 Data+

SDA
RDA

5 GND

5 GND

SG

485

short
short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

485BD Module 5P
Termanal

1 RX-

6 Data-

SDB
RDB

2 RX+

9 Data+

SDA
RDA

5 GND

5 GND

short
short

SG

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

485BD Module 5P
Termanal

1 RX-

7 Data-

SDB
RDB

2 RX+

8 Data+

SDA
RDA

5 GND

5 GND

SG

Driver Version:
Version

Date

Description

V1.40

Jul/26/2011

Added registers: D_Bit and S.

V1.50

Sep/10/2012

Added register: R.

486

short
short

PLC Connection Guide

Mitsubishi FX2N
Supported Series: Mitsubishi FX2N series PLC
Website http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

PLC type

Mitsubishi FX2N

PLC I/F

RS485 4W

RS232/RS485

Baud rate

19200

9600/19200/38400
/57600/115200

Data bits

Parity

Even

Stop bits

PLC sta. no.

Online simulator

Options

YES

Notes

Extend address mode NO

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

Memo

OOO

0 ~ 377

Input Relay

OOO

0 ~ 377

Output Relay

DDDD

0 ~ 7999

Auxiliary Relay

DDD

0 ~ 255

Timer Relay

DDD

0 ~ 255

Counter Relay

SM

DDDD

8000 ~ 9999 Special Auxiliary Relay

D_Bit

DDDDdd

0 ~ 799915

Data Register Bit (D)

DDDD

0 ~ 4095

State Relay (S)

TV

DDD

0 ~ 255

Timer Memory

CV

DDD

0 ~ 199

Counter Memory

DDDD

0 ~ 7999

Data Register

DW

CV2

DDD

200 ~ 255

Counter Memory(D Word)

SD

DDDD

8000 ~ 9999 Special Data Register


487

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series

4 TX7 TX+
1 RX2 RX+
3 GND

COM2 RS485 4W
9P D-Sub Female

RS422 Port 8P
Mini-DIN Male

7 RX-

4 TX-

6 RX+

7 TX+

9 TX-

1 RX-

8 TX+

2 RX+

5 GND

3 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX-

1 RX-

4 TX-

2 RX+

2 RX+

7 TX+

3 TX-

3 TX-

1 RX-

4 TX+

4 TX+

2 RX+

5 GND

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX2 RX+
3 TX4 TX+
5 GND

4 TX7 TX+
1 RX2 RX+
3 GND

488

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS422 Port 8P
Mini-DIN Male

1 RX2 RX+
3 TX4 TX+
5 GND

4 TX7 TX+
1 RX2 RX+
3 GND
View from the
soldering point
of a cable.

Driver Version:
Version

Date

V1.60

Sep/10/2009

Description

489

PLC Connection Guide

Mitsubishi FX2N-10GM/20GM
Supported Series: Mitsubishi FX2N -10GM/20GM PLC.
Website http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

PLC type

Mitsubishi FX2N-10GM/20GM

PLC I/F

RS485 4W

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Online simulator

YES

Options

Notes

Extend address mode NO

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

Memo

OOO

0 ~ 103

Input Relay

OOO

0 ~ 103

Output Relay

DDD

0 ~ 511

Auxiliary Relay

SM

DDDD

9000 ~ 9175

Special Auxiliary Relay

X_W

OOO

0 ~ 103

Y_W

OOO

0 ~ 103

M_W

DDD

0 ~ 511

SM_W

DDDD

9000 ~ 9175

DDDD

0 ~ 6999

Data Register

SD

DDDD

9000 ~ 9599

Special Data Register

0~7

Index register

DW

0~7

Index register

490

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series

4 TX7 TX+
1 RX2 RX+
3 GND

COM2 RS485 4W
9P D-Sub Female

RS422 Port 8P
Mini-DIN Male

7 RX-

4 TX-

6 RX+

7 TX+

9 TX-

1 RX-

8 TX+

2 RX+

5 GND

3 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX-

1 RX-

4 TX-

2 RX+

2 RX+

7 TX+

3 TX-

3 TX-

1 RX-

4 TX+

4 TX+

2 RX+

5 GND

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX2 RX+
3 TX4 TX+
5 GND

4 TX7 TX+
1 RX2 RX+
3 GND

491

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS422 Port 8P
Mini-DIN Male

1 RX2 RX+
3 TX4 TX+
5 GND

4 TX7 TX+
1 RX2 RX+
3 GND
View from the
soldering point
of a cable.

Driver Version:
Version

Date

Description

V1.00

May/30/2013

Driver released.

492

PLC Connection Guide

Mitsubishi FX3U (Ethernet)


Supported Series: Mitsubishi FX SERIES, Module: FX3U-ENET.
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Mitsubishi FX3U (Ethernet)

PLC I/F

Ethernet

Port no.

5001(default)

Refer to Module Setting

PLC sta. no.

0 (default)

Refer to Module Setting

PLC Setting:
Fx3u-ENET module setting:
Before using Ethernet module, use GX Developer / FX Configurator-EN to set the Ethernet
module, the FX3u-ENET module setting steps are shown below.
Step1. Open GX Developer, select Read from PLC in Online list.

493

PLC Connection Guide

Step2. Select FXCPU in PLC series.

Step3. Connect PLC via serial port for setting IP address first.

494

PLC Connection Guide

Step4. After finishing the PLC settings, select Tools/FX special function utility/FX
Configurator-EN.

Step5. Select Module 0 in Ethernet Module settings.


(If more than one module needed, please set modules step by step)

495

PLC Connection Guide

Step6. In Ethernet operational settings, select the related parameters and IP address and
then press End to finish setting.

Step7. In Ethernet open settings, press End after setting the parameters below.

(The first Protocol means using GX Developer to communicate with module, the max.
Fixed buffer communication preocedure is 4 units.)

496

PLC Connection Guide

Or

497

PLC Connection Guide

Step8. After setting the parameters of PLC, restart for Ethernet communication.

Device Address:
Bit/Word

Device type

Format

Range

Memo

OOO

0 ~ 571

Input

OOO

0 ~ 571

Output Relay

DDDD

0 ~ 7999

Internal Relay

DDD

0 ~ 511

Timer Contacts

DDD

0 ~ 255

Counter Contacts

SM

DDDD

8000 ~ 8511

Special Int. Relays

D_Bit

DDDDDdd

0 ~ 1799915

Data Register Bit Access

DDDD

0 ~ 4095

Step Relays

TV

DDD

0 ~ 511

Timer Value

CV

DDD

0 ~ 199

Counter Value

DDDD

0 ~ 7999

Data Registers

CV2

DDD

200 ~255

Counter Value

SD

DDDD

8000 ~ 8511

Special Data Registers

DDDDD

0 ~ 32767

File Register

498

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Feb/12/2009

Driver released.

499

PLC Connection Guide

Mitsubishi FX3U/FX3G
Supported Series: Mitsubishi FX3U/FX3UC/FX3G/FX3S.
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

PLC type

Mitsubishi FX3U/FX3G

PLC I/F

RS485 4w

Baud rate

38400

Data bits

Parity

Even

Stop bits

PLC sta. no.

Online simulator

Options

Notes

RS232 / RS485
2w/4w / USB
9600/19200

Does not apply to this protocol

YES (9600 baud rate only) Extend address mode NO

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word Device type

Format

Range

Memo

OOO

0 ~ 764

Input Relay

OOO

0 ~ 764

Output Relay

DDDD

0 ~ 7999

Auxiliary Relay

DDD

0 ~ 511

Timer Relay (T)

DDD

0 ~ 255

Counter Relay (C)

SM

DDDD

8000 ~ 9999

Special Relay (M)

D_Bit

DDDDdd

0 ~ 799915

Data Register Bit (D)

DDDD

0 ~ 4095

State Relay (S)

TV

DDD

0 ~ 511

Timer Memory (T)

CV

DDD

0 ~ 199

Counter Memory (C)

DDDD

0 ~ 7999

Data Register (D)

DW

CV2

DDD

200 ~ 255

Counter Memory(D Word)

SD

DDDD

8000 ~ 9999

Special Data Register (D)

DDDDD

0 ~ 32767

Extended Register (R)

0~7

Index register

500

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX-

4 TX-

2 RX+

7 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

3 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS422 Port 8P
Mini-DIN Male

7 RX-

4 TX-

6 RX+

7 TX+

9 TX-

1 RX-

8 TX+

2 RX+

5 GND

3 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX-

1 RX-

4 TX-

2 RX+

2 RX+

7 TX+

3 TX-

3 TX-

1 RX-

4 TX+

4 TX+

2 RX+

5 GND

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS422 Port 8P
Mini-DIN Male

1 RX-

4 TX-

2 RX+

7 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

3 GND

501

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS422 Port 8P
Mini-DIN Male

1 RX-

4 TX-

2 RX+

7 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

3 GND
View from the
soldering point
of a cable.

Driver Version:
Version

Date

V1.80

Feb/18/2014

Description

502

PLC Connection Guide

Mitsubishi FX5U
Supported Series: Mitsubishi FX5U/FX5UC
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Mitsubishi FX5U

PLC I/F

RS485 4w

Baud rate

19200

9600 ~ 115200

Data bits

7,8

Parity

None

None/Odd/Even

Stop bits

1,2

PLC sta. no.

0 ~ 15

Parameter 1

1,4,5

Notes

Message Pattern *Note1

*Note1:
Pattern1 = ASCII Mode
Pattern4 = ASCII Mode (CR,LF)
Pattern5 = Binary Mode
Online simulator

YES

Extend address mode

503

NO

PLC Connection Guide

PLC Setting:
Communication Protocol Type MC Protocol
Sum Check Code

Added

Device Address:
Bit/Word Device type

Format

Range

Memo

LCS

DD

0 ~ 63

Long counter Contact

LCC

DD

0 ~ 63

Long counter Coil

SM

DDDD

0 ~ 9999

Special Relay

OOOO

0 ~ 1777

Input Relay

OOOO

0 ~ 1777

Output Relay

DDDD

0 ~ 7679

Internal Relay

DDDD

0 ~ 7679

Latch Relay

DDD

0 ~ 127

Annunciator

HH

0 ~ ff

Link Relay

TS

DDD

0 ~ 511

Timer Contact

TC

DDD

0 ~ 511

Timer Coil

SS

DD

0 ~ 15

Retentive Timer Contact

SC

DD

0 ~ 15

Retentive Timer Coil

CS

DDD

0 ~ 255

Counter Contact

504

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo

CC

DDD

0 ~ 255

Counter Coil

SB

HH

0 ~ ff

Special Link Relay

DDDD

0 ~ 4095

Step relay

D_Bit

DDDDh

0 ~ 7999f

Data Register bit

SD_bit

DDDDDh

0 ~ 11999f

Special register Bit

R_bit

DDDDDh

0 ~ 32767f

File Register Bit

SW_bit

HHHh

0 ~ 1fff

Special Link Register Bit

W_bit

HHHh

0 ~ 1fff

Link Register Bit

DW

LCN

DD

0 ~ 63

Long counter Current Value

DW

LZ

0~1

Long Index Register

SD

DDDDD

0 ~ 11999

Special register

DDDD

0 ~ 7999

Data Register

DDDDD

0 ~ 32767

File Register

HHH

0 ~ 1ff

Link Register

TN

DDD

0 ~ 511

Timer Current value

SN

DD

0 ~ 15

Retentive Timer Current value

CN

DDD

0 ~ 255

Counter Current value

SW

HHH

0 ~ 1ff

Special Link Register

DD

0 ~ 19

Index Register

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W

FX5U RS422 Terminal

9P D-Sub Male
1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

SG

505

PLC Connection Guide

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

FX5U RS422 Terminal

7 RX-

SDB

6 RX+

SDA

9 TX-

RDB

8 TX+

RDA

5 GND

SG

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

FX5U RS422 Terminal

1 RX-

1 RX-

SDB

2 RX+

2 RX+

SDA

3 TX-

3 TX-

RDB

4 TX+

4 TX+

RDA

5 GND

5 GND

SG

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W

FX5U RS422 Terminal

9P D-Sub Male
1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

SG

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

FX5U RS422 Terminal

9P D-Sub Female
1 RX-

SDB

2 RX+

SDA

3 TX-

RDB

4 TX+

RDA

5 GND

SG

506

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.80

Aug/17/2015

Driver released.

507

PLC Connection Guide

Mitsubishi FX5U - ASCII Mode (Ethernet)


Supported Series: Mitsubishi FX5U ethernet module
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Mitsubishi FX5U - ASCII Mode (Ethernet)

PLC I/F

Ethernet

Port no.

Set identically to the PLC setting

PLC sta. no.

Set identically to the PLC setting 255

Notes

Adviced to set port no. to 4999

PLC Setting:
Communication Data Code

ASCII

[Ethernet Configuration]
To connect PLC with multiple HMIs, Port No. must be set.
In GX WORK 3, the setting steps are: Project -> Parameter -> FX5UCPU -> Module
Parameter -> Ethernet Port -> Setting Item -> External Device Configuration -> Detailed
Setting

508

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

Memo

SM

DDDD

0 ~ 9999

Special Relay

OOOO

0 ~ 1777

Input Relay

OOOO

0 ~ 1777

Output Relay

DDDD

0 ~ 7679

Internal Relay

DDDD

0 ~ 7679

Latch Relay

DDD

0 ~ 127

Annunciator

HH

0 ~ ff

Link Relay

TS

DDD

0 ~ 511

Timer Contact

TC

DDD

0 ~ 511

Timer Coil

SS

DD

0 ~ 15

Retentive Timer Contact

SC

DD

0 ~ 15

Retentive Timer Coil

CS

DDD

0 ~ 255

Counter Contact

CC

DDD

0 ~ 255

Counter Coil

SB

HH

0 ~ ff

Special Link Relay

DDDD

0 ~ 4095

Step relay

D_Bit

DDDDh

0 ~ 7999f

Data Register bit

SD_bit

DDDDDh

0 ~ 11999f

Special register Bit

R_bit

DDDDDh

0 ~ 32767f

File Register Bit

SW_bit

HHHh

0 ~ 1fff

Special Link Register Bit

W_bit

HHHh

0 ~ 1fff

Link Register Bit

DW

LZ

0~1

Long Index Register

SD

DDDDD

0 ~ 11999

Special register

DDDD

0 ~ 7999

Data Register

DDDDD

0 ~ 32767

File Register

HHH

0 ~ 1ff

Link Register

TN

DDD

0 ~ 511

Timer Current value

SN

DD

0 ~ 15

Retentive Timer Current value

CN

DDD

0 ~ 255

Counter Current value

SW

HHH

0 ~ 1ff

Special Link Register

DD

0 ~ 19

Index Register

509

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Feb/22/2016

Driver released.

510

PLC Connection Guide

Mitsubishi FX5U - Binary Mode (Ethernet)


Supported Series: Mitsubishi FX5U ethernet module
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Mitsubishi FX5U - Binary Mode (Ethernet)

PLC I/F

Ethernet

Port no.

Set identically to the PLC setting

PLC sta. no.

Set identically to the PLC setting 255

Notes

Adviced to set port no. to 4999

PLC Setting:
Communication Data Code

Binary

[Ethernet Configuration]
To connect PLC with multiple HMIs, Port No. must be set.
In GX WORK 3, the setting steps are: Project -> Parameter -> FX5UCPU -> Module
Parameter -> Ethernet Port -> Setting Item -> External Device Configuration -> Detailed
Setting

511

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

Memo

LCS

DD

0 ~ 63

Long counter Contact

LCC

DD

0 ~ 63

Long counter Coil

SM

DDDD

0 ~ 9999

Special Relay

OOOO

0 ~ 1777

Input Relay

OOOO

0 ~ 1777

Output Relay

DDDD

0 ~ 7679

Internal Relay

DDDD

0 ~ 7679

Latch Relay

DDD

0 ~ 127

Annunciator

HH

0 ~ ff

Link Relay

TS

DDD

0 ~ 511

Timer Contact

TC

DDD

0 ~ 511

Timer Coil

SS

DD

0 ~ 15

Retentive Timer Contact

SC

DD

0 ~ 15

Retentive Timer Coil

CS

DDD

0 ~ 255

Counter Contact

CC

DDD

0 ~ 255

Counter Coil

SB

HH

0 ~ ff

Special Link Relay

DDDD

0 ~ 4095

Step relay

D_Bit

DDDDh

0 ~ 7999f

Data Register bit

SD_bit

DDDDDh

0 ~ 11999f

Special register Bit

R_bit

DDDDDh

0 ~ 32767f

File Register Bit

SW_bit

HHHh

0 ~ 1fff

Special Link Register Bit

W_bit

HHHh

0 ~ 1fff

Link Register Bit

DW

LCN

DD

0 ~ 63

Long counter Current Value

DW

LZ

0~1

Long Index Register

SD

DDDDD

0 ~ 11999

Special register

DDDD

0 ~ 7999

Data Register

DDDDD

0 ~ 32767

File Register

HHH

0 ~ 1ff

Link Register

TN

DDD

0 ~ 511

Timer Current value

SN

DD

0 ~ 15

Retentive Timer Current value

CN

DDD

0 ~ 255

Counter Current value

SW

HHH

0 ~ 1ff

Special Link Register

DD

0 ~ 19

Index Register

512

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Jul/15/2015

Driver released.

513

PLC Connection Guide

Mitsubishi L6ADP
Supported Series: Mitsubishi L6ADP CPU RS232 Series Port
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

PLC type

Mitsubishi L6ADP

PLC I/F

RS232

Baud rate

115200

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Online simulator

YES

Pass-Through

YES

Options

Extend address
mode

Notes

NO

*Communications between HMI and PLC in pass-through mode are not supported.
*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word Device type

Format

Range

Memo

SM

DDDD

0 ~ 2047

Special Int. Relays

HHHH

0 ~ 1FFF

Input Relay

HHHH

0 ~ 1FFF

Output Relay

DDDD

0 ~ 8191

Internal Relay

DDDD

0 ~ 8191

Latch Relay

DDDD

0 ~ 2047

Annunciator

DDDD

0 ~ 2047

Edge Relay

HHHH

0 ~ 1FFF

Link Relay

SB

HHH

0 ~ 7FF

Special Link Relay

D_Bit

DDDDDDh

0 ~ 143359F

Data Register bit

SD

DDDD

0 ~ 2047

Special register

DDDDDD

0 ~ 143359

Data Register

HHHH

0 ~ 1FFF

Link Register

SW

HHH

0 ~ 7FF

Special Link Register

514

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo

DD

0 ~ 19

Index Register

DDDD

0 ~ 2047

Counter

DDDD

0 ~ 1023

Timer

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P Mini-DIN RS232 Port
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male socket

2 RX

8 RX

3 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male socket

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male socket

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 6P Mini-DIN
Male socket

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

5 GND

515

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male socket

9 RX

3 TXD

6 TX

4 RXD

5 GND

5 GND
View from the
soldering point
of a cable.

Driver Version:
Version

Date

Description

V1.00

Nov/19/2013

Driver released.

516

PLC Connection Guide

Mitsubishi MELSEC-Q/L - ASCII Mode (Ethernet)


Supported Series: Mitsubishi Q series (Q03UDE, Q04UDEH, Q06UDEH, Q10UDEH,
Q13UDEH, Q20UDEH, Q26UDEH), Mitsubishi L series(L02, L26-BT), MELSEC-Q/L
protocol application to CPU of Ethernet interface or Ethernet module.
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters
PLC type
PLC I/F

Recommended

Options

Notes

Mitsubishi MELSEC-Q/L - ASCII Mode


(Ethernet)
Ethernet

Port no.

Set identically to the PLC


setting

Adviced to set port no. to


4999

Parameter 1

Networking no. (Set


identically to PLC setting)

0~255

Q13UDEH has to be set to


0

PLC sta. no.

Set identically to the PLC


setting

255

Q13UDEH has to be set to


255

PLC Setting:
MITSUBISHI Q/L series Ethernet module setting:
Note: If using QJ71E71 module, please refer to MITSUBISHI QJ71E71 connection guide.

517

PLC Connection Guide

1. Click [PLC parameter].


2. [Built-in Ethernet port].
3. Click [Open settings] and then set the IP address and communication data code
4. Set the MC protocol-TCP Port No.1387 (Hex) and in EasyBuilder, TCP port is 4999
(Dec).

518

PLC Connection Guide

*If not using an ethernet module, skip the following settings.


Note: In EasyBuilder, please fill in [Network No.] in Parameter 1 as PLC setting.
For example below, the Network No. is 2.

Set to 2 for Parameter 1 in EasyBuilder.

PLC Network No.

519

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

Memo

SM

DDDD

0 ~ 2047

Special Relay

HHHH

0 ~ 1fff

Input Relay

HHHH

0 ~ 1fff

Output Relay

DDDDD

0 ~ 61439

Internal Relay

DDDDD

0 ~ 32767

Latch Relay

DDDDD

0 ~ 32767

Annunciator

DDDDD

0 ~ 32767

Edge Relay

HHHH

0 ~ efff

Link Relay

TS

DDDDD

0 ~ 25471

Timer Contact

TC

DDDDD

0 ~ 25471

Timer Coil

SS

DDDDD

0 ~ 25471

Retentive Timer Contact

SC

DDDDD

0 ~ 25471

Retentive Timer Coil

CS

DDDDD

0 ~ 25471

Counter Contact

CC

DDDDD

0 ~ 25471

Counter Coil

SB

HHHH

0 ~ 7fff

Special Link Relay

DDDD

0 ~ 8191

Step relay

DX

HHHH

0 ~ 1fff

Direct Input

DY

HHHH

0 ~ 1fff

Direct Output

D_Bit

DDDDDDh

0 ~ 999999f

Data Register bit

SD_bit

DDDDh

0 ~ 2047f

Special register Bit

ZR_bit

DDDDDDh

0 ~ 999999f

File Register Bit

R_bit

DDDDDh

0 ~ 32767f

File Register Bit

SW_bit

HHHh

0 ~ 7fff

Special Link Register Bit

W_bit

HHHHHHh

0 ~ 3fd7fff

Link Register Bit

SD

DDDD

0 ~ 2047

Special register

DDDDDD

0 ~ 999999

Data Register

HHHHHH

0 ~ 3fd7ff

Link Register

TN

DDDDD

0 ~ 25471

Timer Current value

SN

DDDDD

0 ~ 25471

Retentive Timer Current


value

CN

DDDDD

0 ~ 25471

Counter Current value

SW

HHH

0 ~ 7ff

Special Link Register

DD

0 ~ 20

Index Register

DDDDD

0 ~ 32767

File Register

ZR

DDDDDD

0 ~ 999999

File Register

520

PLC Connection Guide

Note: Each model of CPU is different, it is recommended to refer to MITSUBISHI


MELSEC-Q Manual Device List.

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Jul/10/2012

Driver released.

521

PLC Connection Guide

Mitsubishi MELSEC-Q/L - Binary Mode (Ethernet)


Supported Series: Mitsubishi Q series (Q03UDE, Q04UDEH, Q06UDEH, Q10UDEH,
Q13UDEH, Q20UDEH, Q26UDEH), Mitsubishi L series(L02, L26-BT), MELSEC-Q/L
protocol application to CPU of Ethernet interface or Ethernet module.
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters
PLC type
PLC I/F

Recommended

Options

Notes

Mitsubishi MELSEC-Q/L - Binary Mode


(Ethernet)
Ethernet

Port no.

Set identically to the PLC


setting

Adviced to set port no. to


4999

Parameter 1

Networking no. (Set


identically to PLC setting)

0~255

Q13UDEH has to be set to


0

PLC sta. no.

Set identically to the PLC


setting

255

Q13UDEH has to be set to


255

PLC Setting:
MITSUBISHI Q/L series Ethernet module setting:
Note: If using QJ71E71 module, please refer to MITSUBISHI QJ71E71 connection guide.

522

PLC Connection Guide

1.
2.
3.
4.

Click [PLC parameter].


[Built-in Ethernet port].
Click [Open settings] and then set the IP address and communication data code
Set the MC protocol-TCP Port No.1387 (Hex) and in EasyBuilder, TCP port is 4999
(Dec).

*If not using an ethernet module, skip the following settings.


Note: In EasyBuilder, please fill in [Network No.] in Parameter 1 as PLC setting.
For example below, the Network No. is 2.

523

PLC Connection Guide

Set to 2 for Parameter 1 in EasyBuilder.

PLC Network No.

Device Address:
Bit/Word

Device type

Format

Range

Memo

SM

DDDD

0 ~ 2047

Special Relay

HHHH

0 ~ 1fff

Input Relay

HHHH

0 ~ 1fff

Output Relay

DDDDD

0 ~ 61439

Internal Relay

DDDDD

0 ~ 32767

Latch Relay

DDDDD

0 ~ 32767

Annunciator

DDDDD

0 ~ 32767

Edge Relay

HHHH

0 ~ efff

Link Relay

TS

DDDDD

0 ~ 25471

Timer Contact

TC

DDDDD

0 ~ 25471

Timer Coil

SS

DDDDD

0 ~ 25471

Retentive Timer Contact

SC

DDDDD

0 ~ 25471

Retentive Timer Coil

CS

DDDDD

0 ~ 25471

Counter Contact

CC

DDDDD

0 ~ 25471

Counter Coil

SB

HHHH

0 ~ 7fff

Special Link Relay

DDDD

0 ~ 8191

Step relay

DX

HHHH

0 ~ 1fff

Direct Input

DY

HHHH

0 ~ 1fff

Direct Output

D_Bit

DDDDDDDh 0 ~ 4184063f

Data Register bit

SD_bit

DDDDh

0 ~ 2047f

Special register Bit

ZR_bit

HHHHHHh

0 ~ 3fd7fff

File Register Bit

524

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

R_bit

DDDDDh

0 ~ 32767f

File Register Bit

SW_bit

HHHh

0 ~ 7fff

Special Link Register Bit

W_bit

HHHHHHh

0 ~ 3fd7fff

Link Register Bit

SD

DDDD

0 ~ 2047

Special register

DDDDDDD

0 ~ 4184063

Data Register

HHHHHH

0 ~ 3fd7ff

Link Register

TN

DDDDD

0 ~ 25471

Timer Current value

SN

DDDDD

0 ~ 25471

Retentive Timer Current value

CN

DDDDD

0 ~ 25471

Counter Current value

SW

HHH

0 ~ 7ff

Special Link Register

DD

0 ~ 20

Index Register

DDDDD

0 ~ 32767

File Register

ZR

HHHHHH

0 ~ 3fd7ff

File Register

Note: Each model of CPU is different, it is recommended to refer to MITSUBISHI


MELSEC-Q Manual Device List.

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V1.30

Jan/14/2011

Description

525

PLC Connection Guide

Mitsubishi MR J3/J4 A
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Mitsubishi MR J3/J4 A

PLC I/F

RS485 4W

RS232/RS485

Baud rate

9600

9600~115200

Parity

Even

Data bits

Stop bits

PLC sta. no.

0~31

Device Address:
Bit/Word

Device type

Format

Range

Memo

EIP

DD

0 ~ 31

External input pin status read *3

EOP

DD

0 ~ 31

External output pin status read *3

PA

DD

1 ~ 32

Basic Setting *4

PB

DD

1 ~ 64

Gain / Filter Setting *4

PC

DD

1 ~ 80

Extension Setting *4

PD

DD

1 ~ 48

Input / Output Setting *4

Status

DD

0 ~ 41

Amplifier Status *1

Alarm

0~6

Alarm

Alarm_T

0~6

Alarm Time (Hour) *2

Mode

1~4

Write Only, Mode Setting *2

Speed

0~1

Write Only, Set Current Speed *2

Acc

0~1

Write Only, Set Acceleration *2

Rotation

0~1

Write Only, Rotation Direction *2

End

0~1

Write Only, End *2

M_dist

0~1

Write Only, Moving Distance *2

Rot_P

0~1

Write Only, Rotation Position *2

P_start

0~1

Write Only, Start Positioning *2

Cur_Alarm

0~1

Current Alarm

PE

DD

1 ~ 64

Extension Setting 2 *4

PF

DD

1 ~ 48

Extension Setting 3 *4

526

PLC Connection Guide

Note1 Status information


Address
Device type
0

Item

EIP
1

Servo motor speed

Droop pulse

Cumulative cmd. Pulses

Command pulse frequency

Analog speed command voltage

Analog torque command voltage

Regenerative load ratio

Effective load ratio

Peak load ratio

10

Instantaneous torque

11

Within one-revolution position

12

ABS conter

13

Load inertia moment ratio

14

Bus voltage

15

Load-side cumulative feedback pulses

16

Load-side droop pulses

17

Load-side encoder information 1

18

Load-side encoder information 2

22

Motor thermistor temperature

23

Motor-side cumu.feedback pulses(before gear)

24

Electrical angle

30

Motor-side / load side position deviation

31

Motor-side / load side speed diviation

32

Encoder inside temperature

33

Setting time

34

Oscillation detection frequency

35

Number of tough drive operations

40

Unit power consumption

41

Unit total power consumption

Cumulative feedback pulses

Note2 represents the write-only registers. The usage of this kind of registers is to run Jog
Mode and Positioning Mode.
Note3represents the read-only registers.
Note4The data in address 1~XX is written to RAM, and the data in address 1001~10XX is
written to ROM.
527

PLC Connection Guide

EIP:

EOP:

528

PLC Connection Guide

How to use EasyBuilder8000/Easy BuilderPro to run Jog and Positioning Mode


*Jog Mode
To run Jog Mode, please follow the steps listed sequentially:
(1) Set Jog Mode
(2) Set rotation speed
(3) Set acceleration
(4) Set forward / reverse rotation direction
(5) End
The following shows how to run the steps above using Macro in
EasyBuilder8000/Easy BuilderPro.

On the editing window of EasyBuilder8000/Easy BuilderPro, the write address of


speed is set to Local HMI LW0 (the address can be user-defined), and set Acc
(Acceleration) to LW1.
To run Jog Mode, the communication with the device must be continuous which only
allows an interval less than 0.5 seconds, otherwise the motor will be locked. Therefore,
in this example, only one register PA_1 is set to read device value.
Macro Demonstration:
a. Start Macro
macro_command main()
short speed
short acc
short mode
mode = 1 // This represents Jog Mode.
SetData(mode, "MITSUBISHI MR J3 A", Mode, 1, 1) // Set driver mode to Jog.
GetData(speed, "Local HMI", LW, 0, 1) // Save LW0 value to speed.
SetData(speed, "MITSUBISHI MR J3 A", Speed, 0, 1) // Set motor operating speed.
529

PLC Connection Guide

GetData(acc, "Local HMI", LW, 1, 1) //


SetData(acc, "MITSUBISHI MR J3 A", Acc, 0, 1) // Set motor acceleration.
short motion
motion = 0x0801

// Special code, see Note 1.

SetData(motion, "MITSUBISHI MR J3 A", Rotation, 0, 1) // Rotate.


end macro_command
Note 1. Original Factory Manual:

b. End Macro
macro_command main()
short stop
stop = 1 // See Note 2.
SetData(stop, "MITSUBISHI MR J3 A", End, 1, 1)
end macro_command
Note 2. Original Factory Manual:

530

PLC Connection Guide

*Positioning Mode

On the editing window of EasyBuilder8000/Easy BuilderPro, the write address of


Speed is set to Local HMI LW2 (the address can be user-defined), and set Acc
(Acceleration) to LW3, Move distance to LW4 (DW format).
Macro Demonstration:
macro_command main()
short mode
mode = 0x2 // Positioning Mode
SetData(mode, "MITSUBISHI MR J3 A", Mode, 1, 1)
short speed
GetData(speed, "Local HMI", LW, 2, 1)
SetData(speed, "MITSUBISHI MR J3 A", Speed, 0, 1)
short acc
GetData(acc, "Local HMI", LW, 3, 1)
SetData(acc, "MITSUBISHI MR J3 A", Acc, 0, 1)
short dist
GetData(dist, "Local HMI", LW, 4, 1)
SetData(dist, "MITSUBISHI MR J3 A", M_dist, 0, 1)
short rot_P
rot_P = 1
// Set to 0: Forward Rotation 1: Reverse Rotation
SetData(rot_P, "MITSUBISHI MR J3 A", Rot_P, 0, 1)
short rotat
rotat = 1
// See Note 3.
531

PLC Connection Guide

SetData(rotat, "MITSUBISHI MR J3 A", Rotation, 0, 1)


SetData(rot_P, "MITSUBISHI MR J3 A", P_start, 0, 1) // Start Positioning.
end macro_command
Note 3. Original Factory Manual

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

CN3 RS485 4W RJ45


Male

1 RX-

4 TX-

2 RX+

5 TX+

3 TX-

6 RX-

4 TX+

3 RX+

5 GND

7 GND

cMT/mTV series
COM2 RS485 4W

CN3 RS485 4W RJ45

9P D-Sub Female

Male

7 RX-

4 TX-

6 RX+

5 TX+

9 TX-

6 RX-

8 TX+

3 RX+

5 GND

7 GND

532

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

CN3 RS485 4W RJ45


Male

1 RX-

1 RX-

4 TX-

2 RX+

2 RX+

5 TX+

3 TX-

3 TX-

6 RX-

4 TX+

4 TX+

3 RX+

5 GND

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

CN3 RS485 4W RJ45


Male

1 RX-

4 TX-

2 RX+

5 TX+

3 TX-

6 RX-

4 TX+

3 RX+

5 GND

7 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

CN3 RS485 4W RJ45

9P D-Sub Female

Male

1 RX-

4 TX-

2 RX+

5 TX+

3 TX-

6 RX-

4 TX+

3 RX+

5 GND

7 GND

Driver Version:
Version

Date

Description

V1.00

Sep/01/2011

Driver released.

V1.10

Jan/13/2012

Added register: EIP and EOP.

V1.40

Apr/14/2014

Support MRJ4

533

PLC Connection Guide

Mitsubishi MR-MQ100 (Ethernet)


Supported Series: Mitsubishi MR-MQ100-Ethernet
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Mitsubishi MR-MQ100 (Ethernet)

PLC I/F

Ethernet

Port no.

Set identically to the PLC


setting

Adviced to set port no. to


4999

Parameter1

Network No.

PLC sta. no.

255

PLC Setting:

534

Notes

PLC Connection Guide

1. Click [Basic Setting].


2. [Built-in Ethernet Port Setting].
3. Click [Open Setting] and then set the IP address and communication data code.
4. Set the MC Protocol-TCP Port No. (Hex)

Device Address:
Bit/Word

Device type

Format

Range

Memo

SM

DDDD

0 ~ 2255

Special Relay

HHHH

0 ~ 1fff

Input

HHHH

0 ~ 1fff

Output

DDDDD

0 ~ 61439

Internal Relay

DDDDD

0 ~ 32767

Annunciator

HHHH

0 ~ efff

Link Relay

D_Bit

DDDDDDDh

0 ~ 4184063f

SD

DDDD

0 ~ 2255

Special Register

DDDDDDD

0 ~ 4184063

Data Register

HHHHHH

0 ~ 3fd7ff

Link Register

DDDDD

0 ~ 12287

Motion Register

Note: ddd: Decimal, hhh: Hexadecimal, ooo: Octal.

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.10

Jun/08/2011

Added register: D_Bit

535

PLC Connection Guide

Mitsubishi Q00/Q00UJ/Q01/QJ71
Supported Series: Mitsubishi Q series PLC with QJ71C24 communication module, Q00,
Q00J, Q00UJ, Q01, Q02H, Q06H, Q12H, Q25H, Q12PH, Q25PH CPU port.
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

PLC type

Mitsubishi Q00/Q00UJ/Q01/QJ71

PLC I/F

RS232

RS485 2W/4W, RS232

Baud rate

9600

9600~115200

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Online simulator

Yes

Options

Notes

Extend address mode NO

PLC Setting:
Q00, Q01 CPU port setting:
1. In GX Developer PLC data list click [PLC parameter].
2. In PLC parameter go to [Serial] page.
3. Select [Use serial communication].
4. Set [Transmission speed] to 9600~115200.
5. Select [Sum check].
6. Set [Transmission wait time] to 10ms.
7. Permit [RUN write setting].
8. Click [End] to close the dialog.
9. Write the PLC Parameter to PLC.
10. Reset PLC, the parameter will be actived.

536

PLC Connection Guide

QJ71 setting:

537

PLC Connection Guide

Device Address:
Bit/Word Device type

Format

Range

Memo

HHHH

0 ~ 1fff

Input Relay

HHHH

0 ~ 1fff

Output Relay

DDDDD

0 ~ 61439

Internal Relay

DDDD

0 ~ 8191

Latch Relay

DDDD

0 ~ 2047

Annunciator

DDDD

0 ~ 2047

Edge Relay

HHHH

0 ~ efff

Link Relay

TC

DDDD

0 ~ 2047

Timer Coil

SS

DDDD

0 ~ 2047

Retentive Timer Contact

SC

DDDD

0 ~ 2047

Retentive Timer Coil

CS

DDDD

0 ~ 1023

Counter Contact

CC

DDDD

0 ~ 1023

Counter Coil

SB

HHH

0 ~ 7ff

Special Link Relay

DDDD

0 ~ 8191

Step Relay

DX

HHHH

0 ~ 1fff

Direct Input

DY

HHHH

0 ~ 1fff

Direct Output

TS

DDDD

0 ~ 2047

Timer Contact

SM

DDDD

0 ~ 2047

D_Bit

DDDDDDDh 0 ~ 4212735f

W_Bit

HHHHh

0 ~ 2ffff

ZR_Bit

HHHHHh

0 ~ fe7fff

ZR_Dec_Bit

DDDDDDDh 0 ~ 1042431f

HHHH

0 ~ 2fff

Link Register

TN

DDDD

0 ~ 2047

Timer Current Value

SN

DDDD

0 ~ 2047

Retentive Timer Current Value

CN

DDDD

0 ~ 1023

Counter Current Value

FFDDDDD

0 ~ 3132767

File Register (FF:File No.


0~31) (DDDDD:0~32767)

SW

HHH

0 ~ 7ff

Special Link Register

DD

0 ~ 15

Index Register

ZR

HHHHH

0 ~ fe7a5

File Register

ZR_decimal_addr DDDDDDD

0 ~ 1042341

DDDDDDD

0 ~ 4212735

SD

DDDD

0 ~ 2047

538

Data Register

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
QJ71C24 CH.2 RS422 Terminal
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

QJ71C24 CH.2 RS422


Terminal

1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series

SDB
SDA
RDB
RDA
GND

COM2 RS485 4W
9P D-Sub Female

QJ71C24 CH.2 RS422


Terminal

7 RX-

SDB

6 RX+

SDA

9 TX-

RDB

8 TX+

RDA

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

QJ71C24 CH.2 RS422


Terminal

1 RX-

1 RX-

SDB

2 RX+

2 RX+

SDA

3 TX-

3 TX-

RDB

4 TX+

4 TX+

RDA

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

QJ71C24 CH.2 RS422


Terminal

1 RX2 RX+
3 TX4 TX+
5 GND

SDB
SDA
RDB
RDA
GND

539

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

QJ71C24 CH.2 RS422


Terminal

1 RX2 RX+
3 TX4 TX+
5 GND

SDB
SDA
RDB
RDA
GND

The following is the view from the soldering point of a cable.


QJ71C24 CH.2 RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

QJ71C24 CH.1 RS232


9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

QJ71C24 CH.1 RS232


9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

540

short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

QJ71C24 CH.1 RS232


9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

QJ71C24 CH.1 RS232


9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

QJ71C24 CH.1 RS232


9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
1 DCD
4 DTR

short

6 DSR
7 RTS
8 CTS

541

short

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 6P Mini-DIN: Q00, Q01 CPU port RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

8 RX

3 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 6P Mini-DIN
Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

9 RX

3 TXD

6 TX

4 RXD

5 GND

5 GND
View from the
soldering point
of a cable.

542

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 6P Mini-DIN: Q00UJ CPU port RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

8 RX

3 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

5 GND
1 RTS
6 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 6P Mini-DIN
Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

5 GND
1 RTS
6 CTS

543

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

9 RX

3 TXD

6 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short
View from the
soldering point
of a cable.

Driver Version:
Version

Date

Description

V1.80

Jun/08/2011

Added register: D_Bit

V1.90

Sep/23/2011

Fixed bit communication incorrect.

V2.00

Nov/12/2012

Added register: ZR_decimal_addr.


Supports extended address range of device types M,D,R,ZR.

V2.30

Nov/07/2014

Added register: ZR_Bit, ZR_Dec_Bit

V2.50

Jan/09/2015

1.Extended the range of B device type to 0x1FFF.


2.Added register: W_Bit

544

PLC Connection Guide

Mitsubishi Q00J
Supported Series: Mitsubishi Q00J CPU

HMI Setting:
Parameters

Recommended

PLC type

Mitsubishi Q00J

PLC I/F

RS232

Baud rate

115200

Data bits

Parity

Odd

Stop bits

Options

Notes
CPU port

9600,19200,38400,
57600,115200

PLC sta. no.


Online simulator

NO

Extend address mode NO

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

SM

DDDD

0 ~ 1023

HHH

0 ~ 7ff

HHH

0 ~ 7ff

DDDDD

0 ~ 61439

DDDD

0 ~ 2047

DDDD

0 ~ 1023

DDDD

0 ~ 1023

HHH

0 ~ 7ff

SB

HHH

0 ~ 3ff

D_Bit

DDDDDDDh 0 ~ 4212735f

SD

DDDD

0 ~ 1023

DDDDDDD

0 ~ 4212735

HHH

0 ~ 7ff

SW

HHH

0 ~ 3ff
545

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

0~9

DDD

0 ~ 511

DDD

0 ~ 511

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P Mini-DIN: Q00 CPU port RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

8 RX

3 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 6P Mini-DIN
Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

5 GND

546

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

9 RX

3 TXD

6 TX

4 RXD

5 GND

5 GND
View from the
soldering point
of a cable.

MT8-Mitsubishi-Q-3M cable can connect MT8000 with Mitsubishi Q series directly.

Driver Version:
Version

Date

Description

V1.20

Jun/08/2011

Added register D_bit

V1.30

Nov/12/2012

Supports extended address range of device types M , D.

547

PLC Connection Guide

Mitsubishi Q00U/Q01U/Q02U/QnUD/QnUDH
Supported Series: Mitsubishi Q00U, Q01U, Q02U, Q03UD, Q04UDH, Q06UDH, Q10UDH,
Q13UDH, Q20UDH, Q26UDH, Q00UJ CPU.

HMI Setting:
Parameters

Recommended

PLC type

Mitsubishi Q00U/Q01U/Q02U/QnUD/QnUDH

PLC I/F

RS232

RS485 4W, RS232

Baud rate

115200

115200 only

Data bits

Parity

Odd

Stop bits

PLC sta. no.

No

Online simulator

NO

Options

Notes
CPU port direct connect
9600,19200,38400,57600,115200
For Q00UJ, only 9600 is available

Extend address mode NO

PLC Setting:
Please do not select [Use Serial Communication]. If this is selected the communication
method will be the same as QJ71, please refer to Mitsubishi Q00/Q00UJ/Q01/QJ71 driver.

548

PLC Connection Guide

Device Address:
Bit/Word Device type

Format

Range

Memo

SM

DDDD

0 ~ 2047

HHHH

0 ~ 1fff

Input Relay

HHHH

0 ~ 1fff

Output Relay

DDDDD

0 ~ 61439

Internal Relay

DDDDD

0 ~ 32767

Latch Relay

DDDDD

0 ~ 32767

Annunciator

DDDDD

0 ~ 32767

Edge Relay

HHHH

0 ~ efff

Link Relay

SB

HHHH

0 ~ 7fff

Special Link Relay

TC

DDDDD

0 ~ 2047

Timer Coil

CC

DDDDD

0 ~ 1023

Counter Coil

D_Bit

DDDDDDDh 0 ~ 4212735f

W_Bit

HHHHHHh

0 ~ 4047fff

ZR_Bit

HHHHHh

0 ~ fe7fff

ZR_Dec_Bit

DDDDDDDh 0 ~ 1042431f

SD

DDDD

0 ~ 2047

DDDDDDD

0 ~ 4212735

Data Register

HHHHHH

0 ~ 4047ff

Link Register

SW

HHHH

0 ~ 6dff

Special Link Register

DD

0 ~ 19

Index Register

FFDDDDD

0 ~ 3132767

File Register (FF:File No.


0~31) (DDDDD:0~32767)

ZR

HHHHHH

0 ~ fe7ff

File Register

ZR_decimal_addr DDDDDDD

0 ~ 1042341

DDDDD

0 ~ 25471

Counter Current Value

DDDDD

0 ~ 25471

Timer Current Value

Note:
EasyBuilder doesnt support MITSUBISHI Q02U CPU to do on-line simulation on PC.
When using Q02U driver, HMI needs 10 seconds to initiate PLC Q02U driver. Before the
completion of initiation, it is recommended not to write data to PLC, this could cause PLC
no response Incorrect wiring or data could cause PLC to be locked. If PLC is locked,
please restart PLC or reinstall PLC module.

549

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P Mini-DIN: Q02 CPU port RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

8 RX

3 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

5 GND
1 RTS
6 CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 6P Mini-DIN

D-Sub Female

Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 6P Mini-DIN
Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

5 GND
1 RTS
6 CTS

550

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

9 RX

3 TXD

6 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short
View from the
soldering point
of a cable.

Driver Version:
Version

Date

Description

V1.60

Jun/08/2011

Added register D_bit

V2.10

Nov/21/2012

V2.30

Nov/07/2014

Added register: ZR_Bit, ZR_Dec_Bit

V2.40

Jan/09/2015

1.Extended the range of B device type to 0x1FFF.


2.Added register: W_Bit

Supports extended address range of device types


M,D,R,ZR.

551

PLC Connection Guide

Mitsubishi Q00UJ/QnU/QnUD/QnUDH/QnUDEH/L
(mini USB)
Supported Series: Mitsubishi Q00UJ, Q00U, Q01U, Q02U, Q03UDE, Q03UD, Q04UDEH,
Q04UDH, Q06UDEH, Q06UDH, Q10UDEH, Q10UDH, Q13UDEH, Q13UDH, Q20UDEH,
Q20UDH, Q26UDEH, Q26UDH, L02, L26-BT USB Port.

HMI Setting:
Parameters Recommended

Options

Notes

PLC type

Mitsubishi Q00UJ/QnU/QnUD/QnUDH/QnUDEH/L (mini USB)

PLC I/F

USB

CPU port direct connect

* X Series HMI not supported

Device Address:
Bit/Word

Device type

Format

Range

SM

DDDD

0 ~ 2047

HHHH

0 ~ 1fff

Input Relay

HHHH

0 ~ 1fff

Output Relay

DDDDD

0 ~ 61439

Internal Relay

DDDD

0 ~ 8191

Latch Relay

DDDD

0 ~ 2047

Annunciator

DDDD

0 ~ 2047

Edge Relay

HHHH

0 ~ 1fff

Link Relay

SB

HHH

0 ~ 7ff

Special Link Relay

D_Bit

DDDDDDDh 0 ~ 4212735f

ZR_Bit

HHHHh

0 ~ fffff

ZR_Dec_Bit

DDDDDh

0 ~ 65535f

SD

DDDD

0 ~ 2047

DDDDDDD

0 ~ 4212735

Data Register

HHHH

0 ~ 1fff

Link Register

SW

HHH

0 ~ 7ff

Special Link Register

DD

0 ~ 19

Index Register

FFDDDDD

0 ~ 132767

ZR

HHHH

0 ~ ffff

ZR_decimal_addr DDDDD

0 ~ 65535
552

Memo

File Register (FF:File No.


0~31) (DDDDD:0~32767)

File Register

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

DDDD

0 ~ 1023

Counter Current Value

DDDD

0 ~ 2047

Timer Current Value

Note:
EasyBuilder doesnt support MITSUBISHI Q02U CPU to do on-line simulation on PC.
When using Q02U driver, HMI needs 10 seconds to initiate PLC Q02U driver. Before the
completion of initiation, it is recommended not to write data to PLC, this could cause PLC
no response Incorrect wiring or data could cause PLC to be locked. If PLC is locked,
please restart PLC or reinstall PLC module.

Driver Version:
Version

Date

Description

V1.30

Jun/08/2011

Added register D_bit

V1.50

Nov/12/2012

Supports extended address range of device types M,D,R,ZR.

V1.60

Nov/07/2014

Added register: ZR_Bit, ZR_Dec_Bit

553

PLC Connection Guide

Mitsubishi Q02/02H
Supported Series; Mitsubishi Q02/Q02H CPU port.
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

PLC type

Mitsubishi Q02/02H

PLC I/F

RS232

RS485 4W, RS232

Baud rate

115200

115200 only

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Online simulator

YES

Broadcast command

NO

Options

Notes

Extend address mode NO

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word Device type

Format

Range

Memo

HHHH

0 ~ 1fff

Input Relay

HHHH

0 ~ 1fff

Output Relay

DDDDD

0 ~ 61439

Internal Relay

DDDDD

0 ~ 32767

Latch Relay

DDDDD

0 ~ 32767

Annunciator

DDDDD

0 ~ 32767

Edge Relay

HHHH

0 ~ 7fff

Link Relay

TC

DDDDD

0 ~ 23087

Timer Coil

SS

DDDDD

0 ~ 23087

Retentive Timer Contact

SC

DDDDD

0 ~ 23087

Retentive Timer Coil

CS

DDDDD

0 ~ 23087

Counter Contact

CC

DDDDD

0 ~ 23087

Counter Coil

554

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo

SB

HHH

0 ~ 7ff

Special Link Relay

DDDD

0 ~ 8191

Step Relay

DX

HHHH

0 ~ 1fff

Direct Input

DY

HHHH

0 ~ 1fff

Direct Output

TS

DDDD

0 ~ 2047

Timer Contact

D_Bit

DDDDDDDh 0 ~ 4212735f

ZR_Bit

HHHHHh

ZR_Dec_Bit

DDDDDDDh 0 ~ 1042431f

HHHH

0 ~ 657f

Link Register

TN

DDDDD

0 ~ 23087

Timer Current Value

SN

DDDDD

0 ~ 23087

Retentive Timer Current Value

CN

DDDDD

0 ~ 23087

Counter Current Value

FFDDDDD

0 ~ 3132767

SW

HHH

0 ~ 7ff

Special Link Register

DD

0 ~ 15

Index Register

ZR

HHHHH

0 ~ fe7ff

File Register

ZR_decimal_addr DDDDDDD

0 ~ 1042431

0 ~ 4212735

0 ~ fe7fff

DDDDDDD

File Register (FF:File No. 0~31)


(DDDDD:0~32767)

Data Register

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P Mini-DIN: Q02 CPU port RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

8 RX

3 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

5 GND
1 RTS
6 CTS

555

short

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P

COM2 RS232 9P

COM3 RS232 9P

RS232 6P Mini-DIN

D-Sub Female

D-Sub Female

D-Sub Male

Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

5 GND
1 RTS
6 CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

RS232 6P Mini-DIN

D-Sub Female

Male

9 RX

3 TXD

6 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short
View from the
soldering point
of a cable.

556

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.60

Jun/08/2011

Added register D_bit

V1.80

Nov/12/2012

Supports extended address range of device types M,D,R,ZR.

V2.00

Nov/07/2014

Added register: ZR_Bit, ZR_Dec_Bit

557

PLC Connection Guide

Mitsubishi Q06H
Supported Series: Mitsubishi Q06H CPU port.
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

PLC type

Mitsubishi Q06H

PLC I/F

RS232

RS485 4W, RS232

Baud rate

115200

115200 only

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Online simulator

Options

YES

Notes

Extend address mode NO

Broadcast command NO
*Support communications between HMI and PLC in pass-through mode
*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

Memo

HHHH

0 ~ 1fff

Input Relay

HHHH

0 ~ 1fff

Output Relay

DDDDD

0 ~ 61439

Internal Relay

DDDDD

0 ~ 32767

Latch Relay

DDDDD

0 ~ 32767

Annunciator

DDDDD

0 ~ 32767

Edge Relay

HHHH

0 ~ 7fff

Link Relay

TC

DDDDD

0 ~ 23087

Timer Coil

SS

DDDDD

0 ~ 23087

SC

DDDDD

0 ~ 23087

Retentive Timer
Contact Timer Coil
Retentive

CS

DDDDD

0 ~ 23087

Counter Contact

CC

DDDDD

0 ~ 23087

Counter Coil

558

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

SB

HHH

0 ~ 7ff

Special Link Relay

DDDD

0 ~ 8191

Step Relay

DX

HHHH

0 ~ 1fff

Direct Input

DY

HHHH

0 ~ 1fff

Direct Output

TS

DDDD

0 ~ 2047

Timer Contact

D_Bit

DDDDDDDh

0 ~ 4212735f

ZR_Bit

HHHHHh

0 ~ fe7fff

ZR_Dec_Bit

DDDDDDDh

0 ~ 1042431f

HHHH

0 ~ 657f

Link Register

TN

DDDDD

0 ~ 23087

Timer Current Value

SN

DDDDD

0 ~ 23087

CN

DDDDD

0 ~ 23087

Retentive Timer
Current Value
Counter
Current

FFDDDDD

0 ~ 3132767

SW

HHH

0 ~ 7ff

Special Link Register

DD

0 ~ 15

Index Register

ZR

HHHHH

0 ~ fe7ff

File Register

ZR_decimal_addr DDDDDDD

0 ~ 1042431

0 ~ 25983

DDDDD

File
Register (FF:File No.
Value
0~31) (DDDDD:0~32767)

Data Register

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P Mini-DIN : Q02 CPU port RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

8 RX

3 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

5 GND
1 RTS
6 CTS

559

short

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 6P Mini-DIN
Male

2 RX

3 TXD

3 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P

COM2 RS232 9P

COM3 RS232 9P

RS232 6P Mini-DIN

D-Sub Female

D-Sub Female

D-Sub Male

Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

5 GND
1 RTS
6 CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

RS232 6P Mini-DIN

D-Sub Female

Male

9 RX

3 TXD

6 TX

4 RXD

5 GND

5 GND
1 RTS
6 CTS

short
View from the
soldering point
of a cable.

560

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.60

Jun/08/2011

Added register D_bit

V1.80

Nov/12/2012

Supports extended address range of device types M,D,R,ZR.

V2.00

Nov/07/2014

Added register: ZR_Bit, ZR_Dec_Bit

561

PLC Connection Guide

Mitsubishi QJ71E71 (Ethernet)


Supported Series ; Mitsubishi Q type, MELSEC-Q series PLC (Q00J, Q00, Q01, Q02,
Q02H, Q06H, Q12H, Q25H, Q12PH, Q25PH) QJ71E71-100 Ethernet module.
Website: http://www.mitsubishi-automation.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Mitsubishi QJ71E71 (Ethernet)

PLC I/F

Ethernet

Port no.

5002

PLC sta. no.

1~99

Network

1~999

Notes

PLC Setting:
QJ71E71-100 Ethernet module settings:
1. Use USB or RS232 of Q-CPU for setting PLC parameters.

562

PLC Connection Guide

2.

Click [Operational settings] to set IP information.

563

PLC Connection Guide

3.

Select Ethernet (2.0) for communicating with HMI.

4.

Click [Open settings] to set the system.

564

PLC Connection Guide

5.

Press [END] to finish settings.

6.

Restart PLC software and select [READ FROM PLC], select [QCPU(Qmode)]
and press [OK].

7.

In [PC side I/F Ethernet board setting] set Network No. and Station No.
(Station No.1 is PC Station No. not Ethernet module Station No., ranged
from 2~64, the Network No. can not be the same as that of PC)

565

PLC Connection Guide

8.

Select Ethernet module in PLC Side I/F to set QJ71E71 IP address.(IP


address

9.

= Network Parameter IP address)

For Other station, click [Other station(Single network)] for setting [Check
at communication time] and [Retry times].

10. After finishing the settings above, click [Connection test] for testing the
communication and sending the PLC program.

566

PLC Connection Guide

Device Address:
Bit/Word Device type

Format

Range

Memo

SM

DDDD

0 ~ 2047

HHHH

0 ~ 1fff

Input Relay

HHHH

0 ~ 1fff

Output Relay

DDDDD

0 ~ 61439

Internal Relay

DDDD

0 ~ 8191

Latch Relay

DDDD

0 ~ 2047

Annunciator

DDDD

0 ~ 2047

Edge Relay

HHHH

0 ~ 1fff

Link Relay

TS

DDDD

0 ~ 2047

Timer Contact

TC

DDDD

0 ~ 2047

Timer Coil

SS

DDDD

0 ~ 2047

Retentive Timer Contact

SC

DDDD

0 ~ 2047

Retentive Timer Coil

CS

DDDD

0 ~ 1023

Counter Contact

CC

DDDD

0 ~ 1023

Counter Coil

SB

HHH

0 ~ 7ff

Special Link Relay

DDDD

0 ~ 8191

Step Relay

DX

HHHH

0 ~ 1fff

Direct Input

DY

HHHH

0 ~ 1fff

Direct Output

D_Bit

DDDDDDDh 0 ~ 4212735f

ZR_Bit

HHHHHh

ZR_Dec_Bit

DDDDDDDh 0 ~ 1042431f

SD

DDDD

0 ~ 2047

DDDDDDD

0 ~ 4212735

Data Register

HHHH

0 ~ 1fff

Link Register

TN

DDDD

0 ~ 2047

Timer Current Value

SN

DDDD

0 ~ 2047

Retentive Timer Current Value

CN

DDDD

0 ~ 1023

Counter Current Value

SW

HHH

0 ~ 7ff

Special Link Register

DD

0 ~ 15

Index Register

FFDDDDD

0 ~ 3132767

ZR

HHHHH

0 ~ fe7ff

ZR_decimal_addr DDDDDDD

0 ~ fe7fff

0 ~ 1042341

567

File Register (FF:File No. 0~31)


(DDDDD:0~32767)

File Register

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V2.20

Jun/08/2011

Added register: D_bit

V2.30

Nov/12/2012

Supports extended address range of device types M,D,Z,ZR.

V2.50

Nov/07/2014

Added register: ZR_Bit, ZR_Dec_Bit

568

PLC Connection Guide

MODBUS ASCII
Supported Series: MODBUS ASCII CONTROLLER
Website: http://www.modbus.org

HMI Setting:
Parameters

Recommended

PLC type

MODBUS ASCII

PLC I/F

RS485

RS232/RS485

Baud rate

9600

9600/19200/38400/
57600/115200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1,2

PLC sta. no.

0-255

Online simulator

Options

YES

Notes

Broadcast command YES

Extend address mode YES

PLC Setting:
Communication mode

Modbus ASCII protocol

Device Address:
Bit/Word Device type

Format

Range

Memo

1x

DDDDD

1 ~ 65535

Input bit (read only)

0x

DDDDD

1 ~ 65535

Output bit

3x_Bit

DDDDDdd

100 ~ 6553515

Input Register bit (read only)

4x_Bit

DDDDDdd

100 ~ 6553515

Output Register bit

3x

DDDDD

1 ~ 65535

Input Register (read only)

4x

DDDDD

1 ~ 65535

Output Register

6x

DDDDD

1 ~ 65535

569

PLC Connection Guide

Modbus RTU function code:


0x
0x01 Read coil
1x
0x02 Read discrete input
3x
0x04 Read input register
4x
0x03 Read holding register
3xbit is equivalent to 3x
4xbit is equivalent to 4x

0x05 write single coil


N/A for write operation
N/A for write operation
0x10 write multiple registers

Wiring Diagram:
The following is the view from the soldering point of a cable.
Modbus ASCII Controller : RS232
eMT3000 series
COM1 RS232 9P

COM3 RS232 9P

RS232 9P D-Sub

D-Sub Female

D-Sub Female

Female

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND
RTS
CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

570

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND
RTS
CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

TXD

6 TX

RXD

5 GND

GND
RTS
CTS

short

The following is the view from the soldering point of a cable.


Modbus ASCII Controller : RS485 4W
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND
571

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

RS485 4W 9P D-Sub

9P D-Sub Female

Female

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

The following is the view from the soldering point of a cable.


Modbus ASCII Controller : RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

572

PLC Connection Guide

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W

COM3 RS485 2W

RS485 2W 9P D-Sub

9P D-Sub Female

9P D-Sub Female

Female

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

Driver Version:
Version

Date

V1.40

Apr/17/2009

Description

573

PLC Connection Guide

MODBUS ASCII Server


HMI Setting:
Parameters

Recommended

PLC type

MODBUS ASCII Server

PLC I/F

RS232

RS232, RS485

Baud rate

9600

9600~115200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

PLC sta. no.

1-31

Online simulator

Options

Notes

HMI Modbus Station No.

YES

Extend address mode NO

Broadcast command NO

PLC Setting:
Communication mode

Modbus ASCII protocol

Device Address:
Bit/Word

Device type

Format

Range

Memo

LB

dddd

0 ~ 9998

Mapping to 0x/1x 1 ~ 9999

LW

dddd

0 ~ 9998

Mapping to 3x/4x 1 ~ 9999

RW

ddddd

0 ~ 55536

Mapping to 3x/4x 10000 ~ 65536

LB0 = 0x0001, LB1 = 0x0002, LW0 = 3x0001, LW1 = 3x0002


Modbus RTU Server doesnt support function code 06(preset single register), please use
function code 16(0x10, preset multiple registers).
Modbus Server Function Code:
0x
0x01 Read coil
0x_multi_coils 0x01 Read coil

0x05 write single coil


0x0f write multiple coils

1x
3x
4x

N/A for write operation


N/A for write operation
0x10 write multiple registers

0x02 Read discrete input


0x04 Read input register
0x03 Read holding register

574

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND
RTS
CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub

D-Sub Female

Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND
RTS
CTS

575

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

TXD

6 TX

RXD

5 GND

GND
RTS
CTS

short

The following is the view from the soldering point of a cable.


RS485 4W
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND
576

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Female

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

The following is the view from the soldering point of a cable.


RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

cMT/mTV series

577

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

Note: Setting more than one Modbus ASCII Server in HMI Device List is of no effect.

Driver Version:
Version

Date

Description

V1.00

Feb/19/2009

Driver released

578

PLC Connection Guide

MODBUS RTU
Supported Series : MODBUS RTU CONTROLLER
Website : http://www.modbus.org

HMI Setting:
Parameters

Recommended

PLC type

MODBUS RTU

PLC I/F

RS485

RS232/RS485

Baud rate

9600

9600~115200

Data bits

7, 8

Parity

Even

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

0-255

Online simulator

YES

Options

Notes

Broadcast command YES

Extend address mode YES

[Address Range Limit]


The address range of 0x, 1x, and 0x_multi_coils device types can be set.
[Conversion]
The 3x_Double and 4x_Double address types are added. If [ABCD ->CDAB] check box is
selected, please select 3x_Double and 4x_Double address types.

PLC Setting:
Communication mode

Modbus RTU protocol

579

PLC Connection Guide

Device Address:
Bit/Word Device type

Format

Range

Memo

0x

DDDDD

1 ~ 65535

Output bit

0x_single_bit

DDDDD

1 ~ 65535

*Note4

1x_single_bit

DDDDD

1 ~ 65535

*Note4

1x

DDDDD

1 ~ 65535

Input bit (read only)

3x_Bit

DDDDDdd 100 ~ 6553515

Input Register bit (read only)

4x_Bit

DDDDDdd 100 ~ 6553515

Output Register bit

B
B

6x_Bit
DDDDDdd 100 ~ 6553515
0x_multi_coils DDDDD
1 ~ 65535

Output Register bit


Write multiple coils

3x

DDDDD

1 ~ 65535

Input Register (read only)

3x_MAX1W

DDDDD

1 ~ 65535

Display 32 bits *Note1

DW

3x_MAX2W

DDDDD

1 ~ 65535

*Note1

4x

DDDDD

1 ~ 65535

Output Register

4x_MAX1W

DDDDD

1 ~ 65535

Display 32 bits *Note1

DW

4x_MAX2W

DDDDD

1 ~ 65535

*Note1

DW

5x

DDDDD

1 ~ 65535

4x double word swap

W
W

6x
3x_Double

DDDDD

1 ~ 65535

DDDDD

1 ~ 65535

4x single word write


*Note2

4x_Double

DDDDD

1 ~ 65535

*Note2

4x_32Bit

DDDDD

1 ~ 65535

Output Registerv *Note1

0x_single_coil DDDDD

1 ~ 65535

*Note3

Note1: MAX1W and 4X_32Bit read/write 1 word for each package and display a 32-bits
value, whereas MAX2W reads/write 2 words for each package.
Note2: Go the [System Parameter Settings] -> [Device Properties] and click [Conversion]
to set the data format of device types 3x, 4x, 6x, 3x_double, 4x double.

580

PLC Connection Guide

Note3: Read/write a Bit at a time. Value 0 and 1 are used to represent ON or OFF status
where 0 means set OFF and 1 means set ON.
Note4: The number of bits to read can be set in Macro, therefore, it is recommended to
use 0x address type for functions such as GetData() and SetData(), in order to increase
reading speed.
To read/write multiple 0x address type in macro, use 0x_multi_coils to increase write
speed.

NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost the
same as 4x except that 5x swaps double word.
If 4x contains the following information:
Address

Data in word

0x1

0x2

0x3

0x4

0x5

0x6

Data

0x0201

0x0403

0x0605

Address

Data in word

0x1

0x2

0x3

0x4

0x5

0x6

...

For 5x, it will be:

Data

0x0102

Modbus RTU function code:


0x
0x01 Read coil
0x_multi_coils 0x01 Read coil
1x
0x02 Read discrete input
3x
0x04 Read input register

0x0304

...

0x0506

0x05 write single coil


0x0f write multiple coils
N/A for write operation
N/A for write operation

4x
0x03 Read holding register
0x10 write multiple registers
5x
0x03 Read holding register
0x10 write multiple registers
(Note: reverse word order in double word format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 write single register
(Note: 6x is limited to device of one word only)
0x_single_coil 0x01 Read coil
0x05 write single coil

581

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND
RTS
CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
FeMale

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND
RTS
CTS

582

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
FeMale

9 RX

TXD

6 TX

RXD

5 GND

GND
RTS
CTS

short

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND

583

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Female

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

cMT/mTV series

584

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Female

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

Driver Version:
Version

Date

Description

V1.90

May/05/2010

Fixed when receiving data over 8 bytes from MODBUS RTU,


LW-9570 fails to calculate correctly.

V2.50

Dec/03/2014

Add device types : 0x_single_bit

585

PLC Connection Guide

MODBUS RTU (0x/1x Range Adjustable)


Supported Series : MODBUS RTU CONTROLLER
Website : http://www.modbus.org

HMI Setting:
Parameters

Recommended

PLC type

MODBUS RTU (0x/1x Range Adjustable)

PLC I/F

RS485

RS232/RS485

Baud rate

9600

9600~115200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1,2

PLC sta. no.

0-255

Online simulator

YES

Extend address mode

YES

Options

Notes

PLC Setting:
Communication mode

Modbus RTU protocol

Device Address:
Bit/Word Device type

Format

Range

Memo

0x

DDDDD

1 ~ 65535

Output bit

1x

DDDDD

1 ~ 65535

Input bit (read only)

3x_Bit

DDDDDdd

100 ~ 6553515

Input Register bit (read only)

4x_Bit

DDDDDdd

100 ~ 6553515

Output Register bit

B
B

6x_Bit
DDDDDdd
0x_multi_coils DDDDD

100 ~ 6553515
1 ~ 65535

Output Register bit


Write multiple coils

3x

DDDDD

1 ~ 65535

Input Register (read only)

4x

DDDDD

1 ~ 65535

Output Register

DW

5x

DDDDD

1 ~ 65535

4x double word swap

W
W

6x
4x_32Bit*

DDDDD

1 ~ 65535

DDDDD

1 ~ 65535

4x single word write


Output Register

4x_32Bit will only read / write 2 words for each package, for continuous addresses, it will
be divided into several packages.
586

PLC Connection Guide

NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost
the same as 4x except that 5x swaps double words.
If 4x contains the following information:
Address

Data in word

0x1

0x2

0x3

0x4

0x5

0x6

Data

0x0201

0x0403

0x0605

Address

Data in word

0x1

0x2

0x3

0x4

0x5

0x6

...

For 5x, it will be:

Data

0x0102

Modbus RTU function code:


0x
0x01 Read coil
0x_multi_coils 0x01 Read coil
1x
0x02 Read discrete input

0x0304

...

0x0506

0x05 Write single coil


0x0f Write multiple coils
N/A for writing operation

3x
0x04 Read input register
N/A for writing operation
4x
0x03 Read holding register
0x10 Write multiple registers
5x
0x03 Read holding register
0x10 Write multiple registers
(Note: reverse word order in double words format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 Write single register
(Note: 6x is limited to device of one word only)

587

PLC Connection Guide

Setting Instructions:
1.

Go to [System Parameter Settings]

click [New] to add a new device -Modbus

RTU (0x 1x range adjustable)as shown below:

2.

After adding Modbus RTU (0x 1x Range Adjustable) driver, [Add Address Range Limit]
button will be enabled as below. Users can set maximum read/write command size
here.

Max.read-command size (words): Pull down to select PLC reading range.

Max.write-command size (words): Pull down to select PLC writing range.

Note: Setting [Add Address Range Limit] is enabled only when bit address is not a multiple
of 16bit.

588

PLC Connection Guide

3.

Click [Add Address Range Limit] button, Users can define 0x , 1x and 0x_multi_coils
address range in [0x 1x Address Range] dialog box, referring to bit range of the
device used.

589

PLC Connection Guide

AddSet [Station No.], [Device Type], [Min. Address], [Max. Address] then click [OK] to
finish adding as below:

DeleteThe selected items will be deleted.


SettingsSet [Station No.], [Device Type], [Min. Address], [Max. Address] then click [OK]
to finish adding as below:

Example
Take D2 and D8 of SCON as example, the settings depend on bit range of different PLC
types. Set [Station No.] and address first.
For D2, set [Station No.] to 20, [Device Type] 0x, [Max. Address] 36.
For D8, set [Station No.] to 2, [Device Type] 0x, [Max. Address] 51.

590

PLC Connection Guide

Note: If communicating with a RS-485 2W PLC, the [Turn around delay] setting may need
to be adjusted according to the reply speed of the device. Please click [Settings] in [Device
Properties], and set the [Turn around delay (ms)] parameter as shown:

After completing all settings above, the communication is enabled.

591

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
MODBUS RTU CONTROLLER : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND
RTS
CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub

D-Sub Female

Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND
RTS
CTS

592

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

TXD

6 TX

RXD

5 GND

GND
RTS
CTS

short

The following is the view from the soldering point of a cable.


MODBUS RTU CONTROLLER : RS485 4W
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND
593

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Female

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

The following is the view from the soldering point of a cable.


MODBUS RTU CONTROLLER : RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

cMT/mTV series

594

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Female

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

Driver Version:
Version

Date

V1.10

Aug/25/2010

V1.20

Mar/2/2012

Description
Allow modifying the Minimum address of 0x1x Address Range.

595

PLC Connection Guide

MODBUS RTU (Adjustable)


Supported Series : MODBUS RTU CONTROLLER
Website : http://www.modbus.org

HMI Setting:
Parameters

Recommended

PLC type

MODBUS RTU (Adjustable)

PLC I/F

RS485

RS232/RS485

Baud rate

9600

9600/19200/3840
0/57600/115200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1,2

PLC sta. no.

0-255

Online simulator

YES

Extend address mode

YES

Options

Notes

PLC Setting:
Communication mode

Modbus RTU protocol

Device Address:
Bit/Word Device type

Format

Range

Memo

0x

DDDDD

1 ~ 65535

Output bit

1x

DDDDD

1 ~ 65535

Input bit (read only)

3x_Bit

DDDDDdd

100 ~ 6553515

Input Register bit (read only)

B
B

4x_Bit
DDDDDdd
0x_multi_coils DDDDD

100 ~ 6553515
1 ~ 65535

Output Register bit


Write multiple coils

3x

DDDDD

1 ~ 65535

Input Register (read only)

4x

DDDDD

1 ~ 65535

Output Register

5x

DDDDD

1 ~ 65535

4x double word swap

DW

5x (32-bit)

DDDDD

1 ~ 65535

4x double word

6x

DDDDD

1 ~ 65535

4x single word write

596

PLC Connection Guide

NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost
the same as 4x except that 5x swaps double words.
If 4x contains the following information:
Address

Data in word

0x1

0x2

0x3

0x4

0x5

0x6

Data

0x0201

0x0403

0x0605

Address

Data in word

0x1

0x2

0x3

0x4

0x5

0x6

...

For 5x, it will be:

Data

0x0102

Modbus RTU function code:


0x
0x01 Read coil
0x_multi_coils 0x01 Read coil
1x
0x02 Read discrete input

0x0304

...

0x0506

0x05 Write single coil


0x0f Write multiple coils
N/A for writing operation

3x
0x04 Read input register
N/A for writing operation
4x
0x03 Read holding register
0x10 Write multiple registers
5x
0x03 Read holding register
0x10 Write multiple registers
(Note: reverse word order in double words format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 Write single register
(Note: 6x is limited to device of one word only)

597

PLC Connection Guide

Setting Instructions:
1.

Go to [System Parameter Settings]

click [New] to add a new device - MODBUS

RTU (Adjustable)as shown below:

2.

After adding MODBUS RTU (Adjustable) driver, [Add Address Range Limit] button will
be enabled as below. Users can set maximum read/write command size here.

Max.read-command size (words): Pull down to select PLC reading range.

Max.write-command size (words): Pull down to select PLC writing range.

598

PLC Connection Guide

Note:
MODBUS RTU (adjustable) usage
Users can decide the address range via setting value on Parameter 1. For example, when
users set 5 to Parameter 1, the address range will be 5 ~ 65535.

599

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
MODBUS RTU CONTROLLER : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND
RTS
CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub

D-Sub Female

Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND
RTS
CTS

600

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

TXD

6 TX

RXD

5 GND

GND
RTS
CTS

short

The following is the view from the soldering point of a cable.


MODBUS RTU CONTROLLER : RS485 4W
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND
601

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Female

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

The following is the view from the soldering point of a cable.


MODBUS RTU CONTROLLER : RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

cMT/mTV series

602

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Female

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

Driver Version:
Version

Date

V1.40

Jun/14/2011

Description

603

PLC Connection Guide

MODBUS RTU (zero-based addressing)


Supported Series : MODBUS RTU CONTROLLER
Website : http://www.modbus.org

HMI Setting:
Parameters

Recommended

PLC type

MODBUS RTU (zero-based addressing)

PLC I/F

RS485

RS232/RS485

Baud rate

9600

9600~115200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1,2

PLC sta. no.

0-255

Online simulator

Options

YES

Notes

Broadcast command YES

Extend address mode YES

PLC Setting:
Communication mode

Modbus RTU protocol

Device Address:
Bit/Word Device type

Format

Range

Memo

0x

DDDDD

0 ~ 65535

Output bit

1x

DDDDD

0 ~ 65535

Input bit (read only)

3x_Bit

DDDDDdd

0 ~ 6553515

Input Register bit (read only)

B
B

4x_Bit
DDDDDdd
0x_multi_coils DDDDD

0 ~ 6553515
0 ~ 65535

Output Register bit


Write multiple coils

3x

DDDDD

0 ~ 65535

Input Register (read only)

4x

DDDDD

0 ~ 65535

Output Register

DW

5x

DDDDD

0 ~ 65535

4x double word swap

6x

DDDDD

0 ~ 65535

4x single word write

604

PLC Connection Guide

NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost the
same as 4x except that 5x swaps double words.
If 4x contains the following information:
Address

Data in word

0x1

0x2

0x3

0x4

0x5

0x6

Data

0x0201

0x0403

0x0605

Address

Data in word

0x1

0x2

0x3

0x4

0x5

0x6

...

For 5x, it will be:

Data

0x0102

Modbus RTU function code:


0x
0x01 Read coil
0x_multi_coils 0x01 Read coil
1x
0x02 Read discrete input

0x0304

...

0x0506

0x05 write single coil


0x0f write multiple coils
N/A for write operation

3x
0x04 Read input register
N/A for write operation
4x
0x03 Read holding register
0x10 write multiple registers
5x
0x03 Read holding register
0x10 write multiple registers
(Note: reverse word order in double word format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 write single register
(Note: 6x is limited to device of one word only)

605

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
MODBUS RTU CONTROLLER : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND
RTS
CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub

D-Sub Female

Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND
RTS
CTS

606

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

TXD

6 TX

RXD

5 GND

GND
RTS
CTS

short

The following is the view from the soldering point of a cable.


MODBUS RTU CONTROLLER : RS485 4W
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND
607

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Female

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

The following is the view from the soldering point of a cable.


MODBUS RTU CONTROLLER : RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

cMT/mTV series

608

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Female

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

Driver Version:
Version

Date

V1.30

Aug/26/2009

Description

609

PLC Connection Guide

MODBUS Server (COM/Ethernet)


HMI Setting:
Parameters

Recommended

PLC type

MODBUS Server (COM/Ethernet)

PLC I/F

RS232

RS232, RS485

Baud rate

9600

9600~115200
Ethernet

Data bits

Parity

Even

Stop bits

Even, Odd,
None
1

PLC sta. no.

1-31

Port no.
Online simulator

Options

Notes

Ethernet supports UDP or TCP/IP


protocol

HMI Modbus Station No.

502
YES

Extend address mode NO

Broadcast command NO

If HMI is Modbus Server, connecting two or more Modbus Servers with one Modbus RTU
via RS485 4W is not supported. To do so, use RS485 2W instead.

610

PLC Connection Guide

PLC Setting:
Communication mode

Modbus RTU protocol

Modbus Server UDP Protocol Setting:


MODBUS Server (Ethernet) supports UDP communication protocol. To use UDP mode,
go to [System Parameter Settings] in editing software, in [Device list] click [New], for [PLC
type] select Modbus Server, [PLC I/F] set to [Ethernet], and select [Use UDP (User
Datagram Protocol)] to finish setting.

Modbus Server Port No. can be changed by clicking [Settings].


Modbus Server Port No. can not be set identically to HMI Port No. When doing so, the
warning message below will be shown requesting users to change setting.

611

PLC Connection Guide

Note:
A maximum of 64 Clients can be connected simultaneously.
Modbus Server Port No. cant be identical to HMI Port No.

Modbus Server TCP/IP Protocol Setting:


MODBUS Server (Ethernet) supports TCP/IP communication protocol. Go to [System
Parameter Settings] in editing software, in [Device list] click [New], for [PLC type] select
Modbus Server, [PLC I/F] set to [Ethernet] to finish setting.

612

PLC Connection Guide

For Modbus Server TCP/IP, HMI Port No. is the same as Modbus Server Port No. To
change Prot No. go to [System Parameter Settings] / [Model], the default Port No. is
8000, and it is allowed to change Modbus Server Port No. here.

MODBUS TCP/IP Gateway:


By adding MODBUS Server with [Ethernet] interface, the [MODBUS TCP/IP Gateway] feature
can be enabled by selecting the [Enable] check box.

613

PLC Connection Guide

Note the following two points when enabling the [MODBUS TCP/IP Gateway]:
a. The original mapping between the MODBUS Server and the HMI address will be
canceled.
b. The SCADA cannot read from or write in the addresses defined in different Address
Mapping Table at one time.
For more information about this, see Chapter37 MODBUS TCPIP Gateway.

Device Address:
Bit/Word

Device type

Format

Range

Memo

LB

dddd

0 ~ 9998

Mapping to 0x/1x 1 ~ 9999

LW

dddd

0 ~ 9998

Mapping to 3x/4x 1 ~ 9999

RW

ddddd

0 ~ 55536

Mapping to 3x/4x 10000 ~ 65536

LB0 = 0x0001, LB1 = 0x0002, LW0 = 3x0001, LW1 = 3x0002

Modbus Server Function Code:


0x
0x01 Read coil
0x_multi_coils 0x01 Read coil
1x
0x02 Read discrete input
3x
0x04 Read input register
4x
0x03 Read holding register

0x05 write single coil


0x0f write multiple coils
N/A for write operation
N/A for write operation
0x10 write multiple registers

Modbus Server Error Code:


Error Code
Definition

Condition

01

Incorrect function code

The function code is not supported.

02

Incorrect read address

The read address is not within the range.

03

Incorrect data

The data read is incorrect, for example, the


data length is 0.
614

PLC Connection Guide

Error Code

Definition

Condition

251

Incorrect data

Read/Write exceeding number of words


from/to the register of the Modbus device.

252

Incorrect data

Modbus device replies incorrect data format.

253

Incorrect data

Modbus device checksum error.

Wiring Diagram:
The following is the view from the soldering point of a cable.
MODBUS SERVER : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND
RTS
CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

615

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND
RTS
CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

TXD

6 TX

RXD

5 GND

GND
RTS
CTS

short

The following is the view from the soldering point of a cable.


MODBUS SERVER : RS485 4W
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND
616

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

RS485 4W 9P D-Sub

9P D-Sub Female

Female

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

The following is the view from the soldering point of a cable.


MODBUS SERVER : RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

617

PLC Connection Guide

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W

COM3 RS485 2W

RS485 2W 9P D-Sub

9P D-Sub Female

9P D-Sub Female

Female

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

618

PLC Connection Guide

MODBUS SERVER : Ethernet


HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Note: Setting more than one Modbus Server in HMI Device List is of no effect.

Driver Version:
Version

Date

Description

V1.00

Dec/30/2008

Driver released

619

PLC Connection Guide

MODBUS TCP/IP
Supported Series: Modbus RTU TCP/IP device.
Website: http://www.modbus.org

HMI Setting:
Parameters

Recommended

PLC type

MODBUS TCP/IP

PLC I/F

Ethernet

Port no.

502

PLC sta. no.

Options

Notes

0~255

Device Address:
Bit/Word Device type

Format

Range

Memo

0x

DDDDD

1 ~ 65535

Output bit

1x

DDDDD

1 ~ 65535

Input bit (read only)

0x_single_Bit

DDDDD

1 ~ 65535

1x_single_Bit

DDDDD

1 ~ 65535

3x_bit

DDDDDdd

100 ~ 6553515

Input Register bit(read only)

4x_bit

DDDDDdd

100 ~ 6553515

Output Register bit

6x_bit

DDDDDdd

100 ~ 6553515

Output Register bit

0x_multi_coils DDDDD

1 ~ 65535

Write multiple coils

3x

DDDDD

1 ~ 65535

Input Register

4x

DDDDD

1 ~ 65535

Output Register

DW

5x

DDDDD

1 ~ 65535

4x double word swap

6x

DDDDD

1 ~ 65535

4x single word write

DW

3x_Double

DDDDD

1 ~ 65535

*Note1

DW

4X_Double
4x string
central
europe
4x string
central
europe (rev)

DDDDD

1 ~ 65535

*Note1

DDDDD

1 ~ 65535

Convert the Central Europe


ASCII to Unicode.

DDDDD

1 ~ 65535

620

PLC Connection Guide

Note1: Go the [System Parameter Settings] -> [Device Properties] and click [Conversion]
to set the data format of device types 3x, 4x, 6x, 3x_double, 4x double.

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V2.00

Mar/23/2015

Description

621

PLC Connection Guide

MODBUS TCP/IP (0x/1x Range Adjustable)


Supported Series : Modbus RTU TCP/IP device.
Website : http://www.modbus.org

HMI Setting:
Parameters

Recommended

Options

PLC type

MODBUS TCP/IP (0x/1x Range Adjustable)

PLC I/F

Ethernet

Port no.

502

PLC sta. no.

Notes

0~255

Online simulator

YES

Extend address mode

YES

Device Address:
Bit/Word Device type

Format

Range

Memo

0x

DDDDD

1 ~ 65535

Output bit

1x

DDDDD

1 ~ 65535

Input bit (read only)

3x_Bit

DDDDDdd

100 ~ 6553515

Input Register bit (read only)

4x_Bit

DDDDDdd

100 ~ 6553515

Output Register bit

B
B

6x_Bit
DDDDDdd
0x_multi_coils DDDDD

100 ~ 6553515
1 ~ 65535

Output Register bit


Write multiple coils

3x

DDDDD

1 ~ 65535

Input Register (read only)

4x

DDDDD

1 ~ 65535

Output Register

DW

5x

DDDDD

1 ~ 65535

4x double word swap

6x
4x string
central
europe rev

DDDDD

1 ~ 65535

4x single word write

DDDDD

1 ~ 65535

622

PLC Connection Guide

NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost
the same as 4x except that 5x swaps double words.
If 4x contains the following information:
Address

Data in word

0x1

0x2

0x3

0x4

0x5

0x6

Data

0x0201

0x0403

0x0605

Address

Data in word

0x1

0x2

0x3

0x4

0x5

0x6

...

For 5x, it will be:

Data

0x0102

Modbus RTU function code:


0x
0x01 Read coil
0x_multi_coils 0x01 Read coil
1x
0x02 Read discrete input

0x0304

...

0x0506

0x05 Write single coil


0x0f Write multiple coils
N/A for writing operation

3x
0x04 Read input register
N/A for writing operation
4x
0x03 Read holding register
0x10 Write multiple registers
5x
0x03 Read holding register
0x10 Write multiple registers
(Note: reverse word order in double words format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 Write single register
(Note: 6x is limited to device of one word only)

623

PLC Connection Guide

Setting Instructions:
1.

Go to [System Parameter Settings]

click [New] to add a new device -MODBUS

TCP/IP (0x/1x Range Adjustable)as shown below:

2.

Click [Add Address Range Limit] button, Users can define 0x and 1x address range in
[0x 1x Address Range] dialog box, referring to bit range of the device used.

624

PLC Connection Guide

AddSet [Station No.], [Device Type], [Max. Address] then click [OK] to finish adding as
below:

DeleteThe selected items will be deleted.


SettingsSet [Station No.], [Device Type], [Max. Address] then click [OK] to finish adding
as below:

625

PLC Connection Guide

Example
Take 0x and 1x as example, the settings depend on bit range of different PLC types.
For 0x, [Device Type] 0x, [Min. Address]5,[Max. Address] 20.
For 1x, [Device Type] 0x, [Min. Address]1,[Max. Address] 10.

After completing all settings above, the communication is enabled.

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

NOV/2/2011

V1.10

MAR/14/2012

Driver released.
Allow modifying the Minimum address of 0x1x Address Range.
626

PLC Connection Guide

MODBUS TCP/IP (zero-based addressing)


Supported Series : Modbus RTU TCP/IP device.
Website: http://www.modbus.org

HMI Setting:
Parameters

Recommended

Options

PLC type

MODBUS TCP/IP (zero-based addressing)

PLC I/F

Ethernet

Port no.

502

PLC sta. no.

Notes

0~255

Device Address:
Bit/Word Device type

Format

Range

Memo

0x

DDDDD

0 ~ 65535

Output bit

1x

DDDDD

0 ~ 65535

Input bit (read only)

3x_Bit

DDDDDdd

0 ~ 6553515

Input Register bit (read only)

4x_Bit

DDDDDdd

0 ~ 6553515

Output Register bit

6x_Bit

DDDDDdd

0 ~ 6553515

Output Register bit

0x_multi_coils DDDDD

0 ~ 65535

Write multiple coils

3x

DDDDD

0 ~ 65535

Input Register

4x

DDDDD

0 ~ 65535

Output Register

DW

5x

DDDDD

0 ~ 65535

4x double word swap

6x

DDDDD

0 ~ 65535

4x single word write

627

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V1.40

Aug/27/2009

Description

628

PLC Connection Guide

MODBUS TCP/IP 32Bit


Supported Series: Modbus RTU TCP/IP device.
Website: http://www.modbus.org

HMI Setting:
Parameters

Recommended

Options

PLC type

MODBUS TCP/IP 32Bit

PLC I/F

Ethernet

Port no.

502

PLC sta. no.

Notes

0~255

Device Address:
Bit/Word

Device type

Format

Range

Memo

0x

DDDDD

1 ~ 65535

Output bit

1x

DDDDD

1 ~ 65535

Input bit (read only)

3x_Bit

DDDDDdd

100 ~ 6553515

Input Register bit (read only)

4x_Bit

DDDDDdd

100 ~ 6553515

Output Register bit

6x_Bit

DDDDDdd

100 ~ 6553515

Output Register bit

0x_multi_coils

DDDDD

1 ~ 65535

Write multiple coils

3x

DDDDD

1 ~ 65535

Input Register

4x

DDDDD

1 ~ 65535

Output Register

DW

5x

DDDDD

1 ~ 65535

4x double word swap

6x

DDDDD

1 ~ 65535

4x single word write

4x_32Bit*

DDDDD

1 ~ 65535

4x_32Bit will only read / write 2 words for each package, for continuous addresses, it will
be divided into several packages.

629

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.10

Aug/27/2009

Driver released.

630

PLC Connection Guide

Moeller XC-CPU101
Supported Series: MOELLER XC100/200 series
Website: http://www.moeller.net

HMI Setting:
Parameters

Recommended

PLC type

Moeller XC-CPU101

PLC I/F

RS232

Baud rate

38400

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

4800 ~ 57600

Device Address:
Bit/Word

Device type

Format

Range

IX

DDo

0 ~ 157

QX

DDo

0 ~ 157

MX

DDDDo

0 ~ 40957

IW

DD

0 ~ 15

QW

DD

0 ~ 15

MW

DDDD

0 ~ 4095

Note

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 8P RJ45 Male

2 RX

8 RX

5 TD

3 TX

7 TX

8 RD

5 GND

5 GND

4 GND

631

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 8P RJ45 Male

2 RX

5 TD

3 TX

8 RD

5 GND

4 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 8P RJ45 Male

2 RX

5 TD

3 TX

8 RD

5 GND

4 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 8P RJ45 Male

2 RX

6 RX

8 RX

5 TD

3 TX

4 TX

7 TX

8 RD

5 GND

5 GND

5 GND

4 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 8P RJ45 Male

9 RX

5 TD

6 TX

8 RD

5 GND

4 GND

Driver Version:
Version

Date

Description

V1.00

Apr/01/2010

Driver released.

632

PLC Connection Guide

motrona CT-150
Supported Series: motrona CT-150
Website: http://motrona.net/index.html

HMI Setting:
Parameters

Recommended

Options

PLC type

motrona CT-150

PLC I/F

RS232

RS232/RS485

Baud rate

9600

1200 ~ 38400

Data bits

Even,Odd,None

Parity

Even

7,8

Stop bits

1,2

PLC sta. no.

11

11 ~ 99

Notes

The station number


must not contain 0.

Device Address:
Bit/Word

Device type

Format

Range

An

4~8

W
W

Bn

1~9

Cn

DD

0 ~ 99

An_32Bit

4~8

Bn_32Bit

1~9

Cn_32Bit

DD

0 ~ 99

ERR_CNT

LV_VAL

PRTMARK_ERR

BAT_CNT

WASTE_CNT

LINE_SPD

ACT_CUT_LEN

ACT_CUT_ERR_M D
ACT_CUT_ERR_L D

633

Note

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

634

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Oct/11/2012

Driver released.

Jun/20/2014

Device types are added


32 bit address: An_32Bit, Bn_32Bit, Cn_32Bit
Parameter address: ERR_CNT, LV_VAL, PRTMARK_ERR,
BAT_CNT, WASTE_CNT, LINE_SPD, ACT_CUT_LEN,
ACT_CUT_ERR_M, ACT_CUT_ERR_L

V1.10

635

PLC Connection Guide

motrona CT15012B
Supported Series: motrona CT15012B
Website: http://motrona.net/index.html

HMI Setting:
Parameters

Recommended

PLC type

motrona CT15012B

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

11

Options

Notes

Note

Device Address:
Bit/Word

Device type

Format

Range

Cn

DD

0 ~ 99

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P

COM3 RS232 9P

RS232 9P D-Sub

D-Sub Female

D-Sub Female

Female

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

PLC RS232 8P RJ45


Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

636

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC RS232 8P RJ45


Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Dec/19/2012

Driver released.

637

PLC Connection Guide

motrona MC700
Supported Series: motrona MC700
Website: http://motrona.net/index.html

HMI Setting:
Parameters

Recommended

PLC type

motrona MC700

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

11

Options

Notes

Note

Device Address:
Bit/Word

Device type

Format

Range

ERCD

HHHH

0 ~ FFFF

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P

COM3 RS232 9P

RS232 9P D-Sub

D-Sub Female

D-Sub Female

Female

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

638

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Dec/19/2012

Driver released.

639

PLC Connection Guide

Nanjing CIGU Controller (for i-Series only)


Website: http://www.cigu.org.cn/

HMI Setting:
Parameters

Recommended

Options

PLC type

Nanjing CIGU Controller

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word Device type

Format

Range

DDD

1 ~ 107

4x

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

7 D-

2 RX+

9 Data+

8 D+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

7 D-

6 RX+

1 Data+

8 D+

5 GND

5 GND

5 GND

cMT/mTV series

640

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

7 D-

2 RX+

8 Data+

8 D+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

7 D-

2 RX+

9 Data+

8 D+

5 GND

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

7 D-

2 RX+

9 Data+

8 D+

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

7 D-

2 RX+

8 Data+

8 D+

5 GND

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Jan/15/2014

Driver released.

641

PLC Connection Guide

Nanotec Stepper Motor


Supported Series: Nanotec Stepper Motor
Website: http://en.nanotec.com/start.html

HMI Setting:
Parameters

Recommended

Options

PLC type

Nanotec Stepper Motor

PLC I/F

RS485 2W

Baud rate

115200

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word Device type

Format

Range

A1 ~ A14

DD

1 ~ 32

B1 ~ B17

B18

DD

1 ~ 32

B19 ~ B24

B25 ~ B26

DD

1~8

B27 ~ B46

C1 ~ C6

D1 ~ D13

E1 ~ E6

F1 ~ F41

G1

G2

DD

1 ~ 10

G3 ~ G5

DD

1~7

H1 ~ H10

J1 ~ J6

642

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Female

1 RX-

6 Data-

7 Out 9 In -

2 RX+

9 Data+

2 Out +
4 In +

5 GND

short
short

5 GND

8 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Female

7 RX-

4 Data-

7 Out -

cMT/mTV series

9 In 6 RX+

1 Data+

2 Out +
4 In +

5 GND

5 GND

short
short

8 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Female

1 RX-

7 Data-

7 Out 9 In -

2 RX+

8 Data+

2 Out +
4 In +

5 GND

9 GND

short
short

8 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Female

1 RX-

6 Data-

7 Out 9 In -

2 RX+

9 Data+

2 Out +
4 In +

5 GND

5 GND

8 GND

643

short
short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Female

1 RX-

6 Data-

7 Out 9 In -

2 RX+

9 Data+

2 Out +
4 In +

5 GND

5 GND

short
short

8 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Female

1 RX-

7 Data-

7 Out 9 In -

2 RX+

8 Data+

2 Out +
4 In +

5 GND

5 GND

8 GND

Driver Version:
Version

Date

Description

V1.00

Aug/24/2012

Driver released.

644

short
short

PLC Connection Guide

NMEA 0183
Supported Series: NMEA 0183 Interface Standard.

HMI Setting:
Parameters

Recommended

Options

PLC type

NMEA 0183

PLC I/F

RS232

Baud rate

4800

4800 ~ 115200

Data bits

7,8

Parity

None

None,Even,Odd

Stop bits

1,2

Notes

NMEA Sentences:
Support sentences
AAM

ACK

ADS

AKD

ALA

ALM

ALR

APB

BEC

BOD

BWC

BWR

BWW

COP

CUR

DBT

DCR

DDC

DOR

DPT

DSC

DTM

ETL

EVE

FIR

FSI

GBS

GGA

GLC

GLL

GMP

GNS

GRS

GSA

GST

GSV

HDG

HMR

HMS

HSC

HSS

HTC

HTD

LCD

MLA

MSK

MSS

MTW

MWD

MWV

NAK

NRM

OSD

PRC

RMA

RMB

RMC

ROR

ROT

RPM

RSA

RSD

RST

SFI

SID

STN

THS

TLL

TRD

TTM

TUT

TXT

UID

VBW

VDR

VER

VHW

VLW

VPW

VTG

WAT

WCV

WNC

WPL

XTE

XTR

ZDA

ZDL

ZFO

ZTG

645

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

SD

3 TX

7 TX

RD

5 GND

5 GND

GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

SD

3 TX

RD

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

SD

3 TX

RD

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

SD

3 TX

4 TX

7 TX

RD

5 GND

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

SD

6 TX

RD

5 GND

GND

646

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Mar/24/2016

Driver releasesd.

647

PLC Connection Guide

ODVA EtherNet/IP Explicit Messaging


Supported Series: Crevis EtherNet/IP NA-9188
Website: http://www.crevis.co.kr/

HMI Setting:
Parameters

Recommended

Options

PLC type

ODVA EtherNet/IP Explicit Messaging

PLC I/F

Ethernet

Port no.

44818

PLC sta. no.

Notes

Please click [Tag Editor] when adding this driver to initiate tag information. To edit address
tag, please see the factory manual.

648

PLC Connection Guide

The following is an example of how to add Vendor ID in Tag Editor. See 3.2.3 Identity
Object in factory manual for the detail of this ID.

Under Struct-Defined select Identity to add Vendor_ID. {1,1,1} represents {Class code ,
Instance ID , Attribute ID}. Enter UINT in Data Type field according to the factory
manual. When finished, this data member can be found in Identity Object.

649

PLC Connection Guide

Support Device Type:


Data type

EasyBuilder data format

Memo

Bool

bit

Byte

16-bit BCD, Hex, Binary, Unsigned

8-bit

SInt

16-bit BCD, Hex, Binary, Signed

8-bit

USInt

16-bit BCD, Hex, Binary, Unsigned

8-bit

Word

16-bit BCD, Hex, Binary, Unsigned

16-bit

Int

16-bit BCD, Hex, Binary, Signed

16-bit

UInt

16-bit BCD, Hex, Binary, Unsigned

16-bit

DWord

32-bit BCD, Hex, Binary, Unsigned

32-bit

DInt

32-bit BCD, Hex, Binary, Signed

32-bit

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary, Unsigned

32-bit

Array

Word array for ASCII input and display

Length=word

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Apr/29/2013

Driver released.
650

PLC Connection Guide

OMRON C/CQM1 Series


Supported Series: OMRON C, CPM, CPL, CQM Series (Host Link Protocol)
Website: http://www.omron.com/

HMI Setting:
Parameters

Recommended

PLC type

OMRON C/CQM1 Series

PLC I/F

RS232

RS232, RS422, RS485

Baud rate

9600

9600, 19200

Data bits

7 or 8

Parity

Even

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

0-31

Online simulator

Options

YES

Notes

Host Link Station No.


Broadcast command YES

Extend address mode YES


*Support communications between HMI and PLC in pass-through mode
*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

PLC Setting:
Communication mode

Host Link Protocol / PLC must be set to monitor mode

Device Address:
Bit/Word

Device type

Format

Range

IR

DDDDdd

0 ~ 409515 I/O and Internal Relay

HR

DDDDdd

0 ~ 409515 Hold Relay

LR

DDDDdd

0 ~ 409515 Link Relay

IR (Force Set/Reset)

DDDDdd

0 ~ 409515

HR (Force Set/Reset) DDDDdd

0 ~ 409515

LR (Force Set/Reset)

DDDDdd

0 ~ 409515

AR

DDDDdd

0 ~ 409515 Auxiliary Relay

AR_W

DDDD

0 ~ 4095

IR_W

DDDD

0 ~ 4095
651

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

HR_W

DDDD

0 ~ 4095

LR_W

DDDD

0 ~ 4095

TC

DDD

0 ~ 255

DM

DDDD

0 ~ 9999

Memo

Data Register

Wiring Diagram:
The following is the view from the soldering point of a cable.
CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
Communication Module:
CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series)
CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

2 SD

3 TX

7 TX

3 RD

5 GND

5 GND

9 GND
4 RS
5 CS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 SD

3 TX

3 RD

5 GND

9 GND
4 RS
5 CS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 SD

3 TX

3 RD

5 GND

9 GND
4 RS
5 CS

652

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

2 SD

3 TX

4 TX

7 TX

3 RD

5 GND

5 GND

5 GND

9 GND
4 RS
5 CS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

2 SD

6 TX

3 RD

5 GND

9 GND
4 RS
5 CS

short

The following is the view from the soldering point of a cable.


C200h-LK201,3G2A6-LK201 communication module
C200HW-COM02/03/04/05/06 communication module
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

2 SD

3 TX

7 TX

3 RD

5 GND

5 GND

7 GND
4 RS
5 CS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 SD

3 TX

3 RD

5 GND

7 GND
4 RS
5 CS
653

short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 SD

3 TX

3 RD

5 GND

7 GND
4 RS
5 CS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

2 SD

3 TX

4 TX

7 TX

3 RD

5 GND

5 GND

5 GND

7 GND
4 RS
5 CS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
9 RX

2 SD

6 TX

3 RD

5 GND

7 GND
4 RS
5 CS

Driver Version:
Version

Date

V1.80

Apr/14/2010

Description

654

short

PLC Connection Guide

OMRON CJ/CS/CP
Supported Series: OMRON CP1E,CP1L, CP1H, CJ1M, CJ2M, CJ1H, CJM1G, CS1H and
CS1G. (Host Link Protocol FINS command), this driver supports Extend Addressing Mode.
Website: http://www.omron.com/

HMI Setting:
Parameters

Recommended

PLC type

OMRON CJ/CS/CP

PLC I/F

RS232

RS232, RS422, RS485

Baud rate

9600

9600~115200

Data bits

7 or 8

Parity

Even

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

0-31

Online simulator

Options

YES

Notes

Host Link Station No.


Extend address mode YES

Broadcast command NO
*Support communications between HMI and PLC in pass-through mode
*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

PLC Setting:
Communication mode

Host Link Protocol

Device Address:
Bit/Word

Device type

Format

Range

CIO_Bit

DDDDDdd

0 ~ 3276715 Channel I/O (CIO)

W_Bit

DDDDDdd

0 ~ 3276715 Work Area (WR)

H_Bit

DDDDDdd

0 ~ 3276715 Holding Area (HR)

D_Bit

DDDDDdd

0 ~ 3276715 Data Memory (DM)

A_Bit

DDDDDdd

0 ~ 3276715 Auxiliary Relay (AR)

T_Bit

DDDDDdd

0 ~ 3276715 Timer (TIM)

C_Bit

DDDDDdd

0 ~ 3276715 Counter (CNT)


655

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

C_flag

DDDD

0 ~ 4095

T_flag

DDDD

0 ~ 4095

LR_Bit

DDDdd

0 ~ 19915

EM0_Bit
EMC_Bit

DDDDDdd

0 ~3276715

Extend Memory

DDDDD

0 ~ 32767

Timer (TIM)

DDDDD

0 ~ 32767

Holding Area (HR)

DDDDD

0 ~ 32767

Data Memory (DM)

DDDDD

0 ~ 32767

Auxiliary Relay (AR)

DDDDD

0 ~ 32767

Work Area (WR)

DDDDD

0 ~ 32767

Counter (CNT)

CIO

DDDDD

0 ~ 32767

Channel I/O (CIO)

EM0 ~ EMC

DDDDD

0 ~ 32767

Extend Memory

LR

DDD

0 ~ 199

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

2 SD

3 TX

7 TX

3 RD

5 GND

5 GND

9 GND
4 RS
5 CS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 SD

3 TX

3 RD

5 GND

9 GND
4 RS
5 CS

656

short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 SD

3 TX

3 RD

5 GND

9 GND
4 RS
5 CS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

2 SD

3 TX

4 TX

7 TX

3 RD

5 GND

5 GND

5 GND

9 GND
4 RS
5 CS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
9 RX

2 SD

6 TX

3 RD

5 GND

9 GND
4 RS
5 CS

short

The following is the view from the soldering point of a cable.


CP1H/CP1L CP1W-CIF11 RS485 4W : 9P D-Sub to Termainals:
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

CP1W-CIF11 RS485
4W Terminal

1 RX-

SDA

2 RX+

SDB

3 TX-

RDA

4 TX+

RDB

5 GND

FG
657

PLC Connection Guide

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

CP1W-CIF11 RS485
4W Terminal

7 RX-

SDA

6 RX+

SDB

9 TX-

RDA

8 TX+

RDB

5 GND

FG

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

CP1W-CIF11 RS485
4W Terminal

1 RX-

1 RX-

SDA

2 RX+

2 RX+

SDB

3 TX-

3 TX-

RDA

4 TX+

4 TX+

RDB

5 GND

5 GND

FG

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W

CP1W-CIF11 RS485

9P D-Sub Male

4W Terminal

1 RX-

SDA

2 RX+

SDB

3 TX-

RDA

4 TX+

RDB

5 GND

FG

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

CP1W-CIF11 RS485

9P D-Sub Female

4W Terminal

1 RX-

SDA

2 RX+

SDB

3 TX-

RDA

4 TX+

RDB

5 GND

FG

CP1W-CIF11: SW1 ON, others OFF.

658

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.90

Feb/01/2011

Added registers: LR, LR_Bit

V2.00

Dec/05/2012

Added register: EM_Bit

659

PLC Connection Guide

OMRON CJ/CS/CP (Ethernet - FINS/TCP)


Supported Series: OMRON CJ Series, CS Series, CP Series +Ethernet Module. (Ethernet
FINS)
Website: http://www.omron.com/
*On initialization, switch from RUN MODE to MONITOR MODE.

HMI Setting:
Parameters

Recommended

Options

PLC type

OMRON CJ/CS/CP (Ethernet - FINS/TCP)

PLC I/F

Ethernet

Port no.

9600

PLC sta. no.

PLC Setting:
Communication mode

Ethernet (FINS/TCP) protocol

660

Notes

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

Memo

CIO_Bit

DDDDDdd

0 ~ 3276715 Channel I/O (CIO)

W_Bit

DDDDDdd

0 ~ 3276715 Work Area (WR)

H_Bit

DDDDDdd

0 ~ 3276715 Holding Area (HR)

A_Bit

DDDDDdd

0 ~ 3276715 Auxiliary Relay (AR) (Read only)

D_Bit

DDDDDdd

0 ~ 3276715 Data Memory (DM)

T_Bit

DDDDDdd

0 ~ 3276715 Timer (TIM)

C_Bit

DDDDDdd

0 ~ 3276715 Counter (CNT)

C_Flag

DDDD

0 ~ 4095

T_Flag

DDDD

0 ~ 4095

EM0_Bit ~
EMC_Bit

DDDDDdd

0 ~ 3276715 Extend Memory

CIO

DDDDD

0 ~ 32767

Channel I/O (CIO)

DDDDD

0 ~ 32767

Work Area (WR)

DDDDD

0 ~ 32767

Holding Area (HR)

DDDDD

0 ~ 32767

Auxiliary Relay (AR) (Read only)

DDDDD

0 ~ 32767

Counter (CNT)

DDDDD

0 ~ 32767

Timer (TIM)

DDDDD

0 ~ 32767

Data Memory (DM)

EM0 ~ EMC

DDDDD

0 ~ 32767

Extend Memory

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

661

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.80

Dec/05/2012

Added register: EM_Bit

662

PLC Connection Guide

OMRON CP Series (USB)


Supported Series: OMRON CP1E CPU Module USB Port.
Website: http://www.omron.com/

HMI Setting:
Parameters

Recommended

PLC type

OMRON CP Series (USB)

PLC I/F

USB

Online simulator

Options

Notes
USB Host

No

Device Address:
Bit/Word

Device type

Format

Range

Memo

CIO_Bit

DDDdd

0 ~ 28915

Channel I/O (CIO)

A_Bit

DDDdd

0 ~ 75315

Auxiliary Relay (AR)

T_Bit

DDDdd

0 ~ 25515

Timer (TIM)

C_Bit

DDDdd

0 ~ 25515

Counter (CNT)

D_Bit

DDDDdd

0 ~ 204715

Data Memory (DM)

H_Bit

DDdd

0 ~ 4915

Holding Area (HR)

W_Bit

DDdd

0 ~ 9915

Work Area (WR)

CIO

DDD

0 ~ 289

Channel I/O (CIO)

DDD

0 ~ 753

Auxiliary Relay (AR)

DDD

0 ~ 255

Timer (TIM)

DDD

0 ~ 255

Counter (CNT)

DDDD

0 ~ 2047

Data Memory (DM)

DD

0 ~ 49

Holding Area (HR)

DD

0 ~ 99

Work Area (WR)

Driver Version:
Version

Date

Description

V1.00

Jan/20/2015

Driver released.

663

PLC Connection Guide

OMRON E5CN/E5EZ/E5ZN
Supported Series: OMRON E5CN series temperature controller with communication
options. E5EN/CN/GN/EZ/ZN series.
Website: http://oeiweb.omron.com

HMI Setting:
Parameters

Recommended

PLC type

OMRON E5CN

PLC I/F

RS485 2W

Baud rate

9600

9600/19200/38400/
57600/115200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1,2

PLC sta. no.

0-99

Online simulator

Options

YES

Notes

Broadcast command YES

Extend address mode YES


*Support communications between HMI and PLC in pass-through mode
*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

Memo

Status_CH1 DD

0 ~ 31

Page40

Status_CH2 DD

0 ~ 31

DW

C0

HHHH

0 ~ 270f

Read only (Hex) Page34

DW

C1

HHHH

0 ~ 270f

Read/Write (Hex) Page35

DW

C2

HHHH

0 ~ 270f

Read/Write (Hex) Page35

DW

C3

HHHH

0 ~ 270f

Read/Write (Hex) Page36

Code00_00

Communications writing OFF (disabled)

Code00_01

Communications writing ON(enabled)

Code01_00

Run

Code01_01

Stop
664

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

Code02_00

Multi-SP Set point 0

Code02_01

Multi-SP Set point 1

Code02_02

Multi-SP Set point 2

Code02_03

Multi-SP Set point 3

Code03_00

AT cancel

Code03_01

AT execute

Code04_00

Write mode (Backup)

Code04_01

Write mode (Ram)

Code05_00

Save RAM data

Code06_00

Software reset

Code07_00

Move to setup area 1

Code08_00

Move to protect level

Code01_10

Code01_11

Code01_F0

Code01_F1

Code02_10

Code02_11

Code02_F0

Code02_F1

Code03_10

Code03_11

Code03_F0

Code03_F1

Code09_00

Code09_01

Code09_10

Code09_11

Code09_F0

Code09_F1

Code0A_00

Code0B_00

Code0C_00

Code0C_01

Code0C_02

Code0C_0F H

Code0C_10

665

PLC Connection Guide

Bit/Word

Device type

Format

Range

Code0C_11

Code0C_12

Code0C_1F H

Code0C_F0 H

Code0C_F1 H

Code0C_F2 H

Code0C_FF H

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W

COM3 RS485 2W

OMRON E5CN

9P D-Sub Male

9P D-Sub Male

Terminal

1 RX-

6 Data-

12 B

2 RX+

9 Data+

11 A

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

OMRON E5CN
Terminal

7 RX-

4 Data-

12 B

6 RX+

1 Data+

11 A

5 GND

5 GND

GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W

COM3 RS485 2W

OMRON E5CN

9P D-Sub Male

9P D-Sub Male

Terminal

1 RX-

7 Data-

12 B

2 RX+

8 Data+

11 A

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

OMRON E5CN
Terminal

1 RX-

6 Data-

12 B

2 RX+

9 Data+

11 A

5 GND

5 GND

GND

666

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

OMRON E5CN
Terminal

1 RX-

6 Data-

12 B

2 RX+

9 Data+

11 A

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

OMRON E5CN
Terminal

1 RX-

7 Data-

12 B

2 RX+

8 Data+

11 A

5 GND

5 GND

GND

Note:
For communication with OMRON E5EZ, please set communication settings to 9600, E, 7,
2, station no. 1.

Driver Version:
Version

Date

V1.21

Dec/21/2010

Description

667

PLC Connection Guide

OMRON Ethernet
Supported Series: OMRON CJ Series, CS Series, CP Series +Ethernet Module. (Ethernet
FINS)
Website: http://www.omron.com/
*On initialization, switch from RUN MODE to MONITOR MODE.

HMI Setting:
Parameters

Recommended

PLC type

OMRON Ethernet

PLC I/F

Ethernet (UDP)

Port no.

9600

PLC sta. no.

Options

PLC Setting:
Communication mode

Ethernet (UDP) protocol

668

Notes

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

Memo

CIO_Bit

DDDDDdd

0 ~ 3276715 Channel I/O (CIO)

W_Bit

DDDDDdd

0 ~ 3276715 Work Area (WR)

H_Bit

DDDDDdd

0 ~ 3276715 Holding Area (HR)

A_Bit

DDDDDdd

0 ~ 3276715 Auxiliary Relay (AR) (Read only)

D_Bit

DDDDDdd

0 ~ 3276715 Data Memory (DM)

T_Bit

DDDDDdd

0 ~ 3276715 Timer (TIM)

C_Bit

DDDDDdd

0 ~ 3276715 Counter (CNT)

C_Flag

DDDD

0 ~ 4095

T_Flag

DDDD

0 ~ 4095

DDDDDdd

0 ~ 3276715 Extend Memory Bit

DDDDD

0 ~ 32767

Channel I/O (CIO)

EM0_Bit ~
EMC_Bit
CIO

DDDDD

0 ~ 32767

Work Area (WR)

DDDDD

0 ~ 32767

Holding Area (HR)

DDDDD

0 ~ 32767

Auxiliary Relay (AR) (Read only)

DDDDD

0 ~ 32767

Counter (CNT)

DDDDD

0 ~ 32767

Timer (TIM)

DDDDD

0 ~ 32767

Data Memory (DM)

EM0 ~ EMC

DDDDD

0 ~ 32767

Extend Memory

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

669

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Oct/4/2012

Driver released.

V1.40

Dec/11/2015

Added registers: EM and EM_Bit

670

PLC Connection Guide

OMRON Ethernet (FINS/TCP)


Supported Series: Non OMRON PLC . (Ethernet FINS)

HMI Setting:
Parameters

Recommended

Options

PLC type

OMRON Ethernet (FINS/TCP)

PLC I/F

Ethernet

Port no.

9600

PLC sta. no.

Notes

PLC Setting:
Communication mode

Ethernet (FINS/TCP) protocol

Device Address:
Bit/Word

Device type

Format

Range

CIO_Bit

DDDDDdd

0 ~ 3276715 Channel I/O (CIO)

W_Bit

DDDDDdd

0 ~ 3276715 Work Area (WR)

H_Bit

DDDDDdd

0 ~ 3276715 Holding Area (HR)

A_Bit

DDDDDdd

0 ~ 3276715 Auxiliary Relay (AR) (Read only)

D_Bit

DDDDDdd

0 ~ 3276715 Data Memory (DM)

T_Bit

DDDDDdd

0 ~ 3276715 Timer (TIM)

C_Bit

DDDDDdd

0 ~ 3276715 Counter (CNT)

C_Flag

DDDD

0 ~ 4095

T_Flag

DDDD

0 ~ 4095

CIO

DDDDD

0 ~ 32767

Channel I/O (CIO)

DDDDD

0 ~ 32767

Work Area (WR)

DDDDD

0 ~ 32767

Holding Area (HR)

DDDDD

0 ~ 32767

Auxiliary Relay (AR) (Read only)

DDDDD

0 ~ 32767

Counter (CNT)

DDDDD

0 ~ 32767

Timer (TIM)

DDDDD

0 ~ 32767

Data Memory (DM)

EM0 ~ EMC

DDDDD

0 ~ 32767

Extend Memory

671

Memo

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

May/26/2011

Driver released.

672

PLC Connection Guide

OMRON EtherNet/IP (NJ Series)


Supported Series: OMRON EtherNet/IP NJ Series PLC
Website: http://www.omron.com/

HMI Setting:
Parameters

Recommended

PLC type

OMRON EtherNet/IP (NJ Series)

PLC I/F

Ethernet

Port no.

44818

PLC sta. no.

On-line simulator

Yes

Options

Notes

Multi-HMI connect

Yes

Instructions:
Note:
1. In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting
address tag.
2. When [Do not publish] is selected for a tag, different import methods may lead to
different results. When import tags by [Get Tags from Device], the tag will be
eliminated. If [Import tags] is selected, the tags will be imported, but the
communication will not succeed.

673

PLC Connection Guide

Get Tags from Network


1. In EasyBuilder, open System Parameter Settings, and add Omron EtherNet/IP (NJ
series). Set communication parameters, and then click [Tag Manager].

2. Click [Get Tags] [Get Tags from Device].

3. The Import Status field shows the result, click [Exit] to finish importing address
tags.

674

PLC Connection Guide

Export Tags from Sysmac Studio


1. Launch Sysmac Studio, under Global Variables create the address tags, and then
select [Tools] [Export Global Variables].

2. Launch EasyBuilder, in System Parameter Settings add Omron EtherNet/IP (NJ


series).
3. Click [Tag Manager].

4. Click [Get Tags] [Import Tags] and then select the file exported in step 1.

675

PLC Connection Guide

5. The Import Status field shows the result, click [Exit] to finish importing address
tags.

Supported data types include: BOOL, SINT, BYTE, USINT, INT, WORD, UINT,
DINT, REAL, UDINT and DWORD. These data types support one-dimensional
array.

Support Device Type:


Data type

EasyBuilder data format

Bool

bit

Byte

8-bit

DInt

16-bit BCD, Hex, Binary,


Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Signed

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary,


Unsigned
Word array for ASCII input
and ASCII display

32-bit

SInt
USInt
Word
Int
UInt
DWord

Array

676

Memo

8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit

Length=word

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Dec/14/2012

Driver released.

677

PLC Connection Guide

OMRON Host Link


Supported Series: OMRON C, CPM, CPL, CQM Series (Host Link Protocol)
Website: http://www.omron.com/

HMI Setting:
Parameters

Recommended

PLC type

OMRON Host Link

PLC I/F

RS232

RS232, RS422, RS485

Baud rate

9600

9600, 19200

Data bits

7 or 8

Parity

Even

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

0-31

Online simulator

Options

YES

Notes

Host Link Station No.


Broadcast command YES

Extend address mode YES

PLC Setting:
Communication mode

Host Link Protocol

Device Address:
Bit/Word

Device type

Format

Range

IR

DDDDdd

0 ~ 409515 I/O and Internal Relay

HR

DDDDdd

0 ~ 409515 Hold Relay

LR

DDDDdd

0 ~ 409515 Link Relay

IR (Force Set/Reset)

DDDDdd

0 ~ 409515

HR (Force Set/Reset) DDDDdd

0 ~ 409515

LR (Force Set/Reset)

DDDDdd

0 ~ 409515

AR

DDDDdd

0 ~ 409515 Auxiliary Relay

AR_W

DDDD

0 ~ 4095

IR_W

DDDD

0 ~ 4095

HR_W

DDDD

0 ~ 4095

LR_W

DDDD

0 ~ 4095

TC

DDD

0 ~ 255

DM

DDDD

0 ~ 9999
678

Memo

Data Register

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
Communication Module:
CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series)
CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
eMT3000 series
COM1 RS232 9P

COM3 RS232 9P

RS232 9P D-Sub Male

D-Sub Female

D-Sub Female

2 RX

8 RX

2 SD

3 TX

7 TX

3 RD

5 GND

5 GND

9 GND
4 RS
5 CS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 SD

3 TX

3 RD

5 GND

9 GND
4 RS
5 CS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 SD

3 TX

3 RD

5 GND

9 GND
4 RS
5 CS

679

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

2 SD

3 TX

4 TX

7 TX

3 RD

5 GND

5 GND

5 GND

9 GND
4 RS
5 CS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

2 SD

6 TX

3 RD

5 GND

9 GND
4 RS
5 CS

short

The following is the view from the soldering point of a cable.


C200h-LK201,3G2A6-LK201 communication module
C200HW-COM02/03/04/05/06 communication module
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

2 SD

3 TX

7 TX

3 RD

5 GND

5 GND

7 GND
4 RS
5 CS

680

short

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 SD

3 TX

3 RD

5 GND

7 GND
4 RS
5 CS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 SD

3 TX

3 RD

5 GND

7 GND
4 RS
5 CS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P

COM2 RS232 9P

COM3 RS232 9P

RS232 9P D-Sub Male

D-Sub Female

D-Sub Female

D-Sub Male

2 RX

6 RX

8 RX

2 SD

3 TX

4 TX

7 TX

3 RD

5 GND

5 GND

5 GND

7 GND
4 RS
5 CS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
9 RX

2 SD

6 TX

3 RD

5 GND

7 GND
4 RS
5 CS

681

short

PLC Connection Guide

Driver Version:
Version

Date

V1.30

OCT/21/2010

Description

682

PLC Connection Guide

OuHua OHJX
Website: http://www.ohjx.com/

HMI Setting:
Parameters

Recommended

PLC type

OuHua OHJX

PLC I/F

RS-232

Baud rate

9600

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Options

Notes

9600,19200

Device Address:
Bit/Word

Device type

Format

Range

R100

Dh

0 ~ 1f

R101

Dh

0 ~ 1f

R102

Dh

0 ~ 1f

R103

Dh

0 ~ 1f

R104

Dh

0 ~ 1f

R105

Dh

0 ~ 1f

R106

Dh

0 ~ 1f

R107

Dh

0 ~ 1f

R108

Dh

0 ~ 1f

R109

Dh

0 ~ 1f

R110

Dh

0 ~ 1f

R210

Dh

0 ~ 1f

R310

Dh

0 ~ 1f

SV

DDDD

0 ~ 9999

EV

DDDDD

0 ~ 65535

DT

DDDDD

0 ~ 9999

LD

DDDD

0 ~ 8447

WX

DDDD

0 ~ 9999
683

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

WY

DDDD

0 ~ 9999

WR

DDDD

0 ~ 9999

WL

DDDD

0 ~ 9999

FL

DDDDD

0 ~ 99999

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

4P Mini-DIN Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

1 GND
4 GND

short

cMT/mTV series
COM1 RS232 9P

4P Mini-DIN Male

D-Sub Female
2 RX

3 TX

3 TX

2 RX

5 GND

1 GND
4 GND

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

4P Mini-DIN Male

2 RX

3 TX

3 TX

2 RX

5 GND

1 GND
4 GND

684

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

4P Mini-DIN Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

1 GND
4 GND

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

4P Mini-DIN Male

D-Sub Female
9 RX

3 TX

6 TX

2 RX

5 GND

1 GND
4 GND

short
View from the
soldering point
of a cable.

Driver Version:
Version

Date

Description

V1.00

Nov/22/2011

Driver released.

685

PLC Connection Guide

Panasonic Eco-Power Meters


Supported Series: KW1M , KW1M-A , KW9M , KW9M-A
Website: https://www.panasonic-electric-works.com/eu/

HMI Setting:
Parameters

Recommended

Options

PLC type

Panasonic Eco-Power Meters

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Notes

9600 ~ 115200

Support Device Type:


Data type

EasyBuilder data format

Bool

bit

Byte

16-bit BCD, Hex, Binary, Unsigned

8-bit

SInt

16-bit BCD, Hex, Binary, Signed

8-bit

USInt

16-bit BCD, Hex, Binary, Unsigned

8-bit

Word

16-bit BCD, Hex, Binary, Unsigned

16-bit

Int

16-bit BCD, Hex, Binary, Signed

16-bit

UInt

16-bit BCD, Hex, Binary, Unsigned

16-bit

DWord

32-bit BCD, Hex, Binary, Unsigned

32-bit

DInt

32-bit BCD, Hex, Binary, Signed

32-bit

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary, Unsigned

32-bit

686

Memo

PLC Connection Guide

Import Tags:
1. The file for import must be built in Easy Build Pro\Data Type\PanasonicPowerMeter
folder. The user can build the file according to the device types in advance, as shown
below.
Name : User-defined tag name.
Data :Type: Define according to the data length and range.
Address : The address of the device.
Description : The description about the address.
Data type

Data length and range

BOOL

Bit

BYTE

8-bits Unsigned

WORD

16-bits Unsigned

DWORD

32-bits Unsigned

UDINT

32-bits Unsigned

UINT

16-bits Unsigned

USINT

8-bits Unsigned

SINT

8-bits Signed

INT

16-bits Signed

DINT

32-bits Signed

REAL

32-bits Float

2. In EasyBuilder select [Panasonic Eco-Power Meters] driver, and then click [Station
No. and Device Model].

687

PLC Connection Guide

3. [Station no.]: Set the station number according to the device, the range is 1~99.
[Name]: The name of the device.
[Model]: The models with their address tag files saved in Easy Build Pro\Data
Type\PanasonicPowerMeter can be found in the drop down list.
[Add]: Add a new model.
[Delete]: Delete a model. (At least one model should exist in the list.)
[Import]: Import the .dat file of the model.
[Export]: Export the .dat file of the model.
[OK]: Save and leave.
[Cancel]: Dont save and leave.

4. The imported address tags can be selected in object settings window.

688

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W
Terminal

1 RX-

6 Data-

B-

2 RX+

9 Data+

A+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

PLC RS485 2W
Terminal

7 RX-

4 Data-

B-

6 RX+

1 Data+

A+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W
Terminal

1 RX-

7 Data-

B-

2 RX+

8 Data+

A+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W
Terminal

1 RX-

6 Data-

B-

2 RX+

9 Data+

A+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W
Terminal

1 RX-

6 Data-

B-

2 RX+

9 Data+

A+

5 GND

5 GND

689

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P RJ45

1 RX-

7 Data-

8 Data-

2 RX+

8 Data+

1 Data+

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Apr/13/2016

Driver released

690

PLC Connection Guide

Panasonic FP/KW
Supported Series: NAIS (Matsushita) FP/KW series include FP-X, FP-, FP0, FP1, FP2,
FP2SH, FP10SH and FP3 Ethernet support FP-X with AFPX-COM5.
Website:http://pewa.panasonic.com/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Panasonic FP/KW

PLC I/F

RS232

RS232/RS485

Baud rate

9600

Data bits

9600, 19200, 38400,


57600,
7 or 8 115200

Parity

Odd

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

1-32

Must match the PLC port setting.


FP3 must set to 0.

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDh

0 ~ 9999f

Input (X)

DDDDh

0 ~ 9999f

Output (Y)

DDDDh

0 ~ 9999f

Internal Relay (R)

DDDD

0 ~ 9999

Link Relay (L)

L_Bit

DDDDh

0 ~ 9999f

DDDD

0 ~ 9999

Timer (T)

DDDD

0 ~ 9999

Counter (C)

SV

DDDD

0 ~ 9999

Timer/Counter Set Value (SV)

EV

DDDDD

0 ~ 65535

Timer/Counter Elapse Value (EV)

DT

DDDDD

0 ~ 99999

Data Register (DT)

LD

DDDD

0 ~ 8447

Link Register (LD)

WX

DDDD

0 ~ 9999

Input (WX) (read only)

WY

DDDD

0 ~ 9999

Output (WY)

WR

DDDD

0 ~ 9999

Internal Relay (WR)

691

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

WL

DDDD

0 ~ 9999

Link Relay (WL)

FL

DDDDD

0 ~ 99999

File Register (FL)

Wiring Diagram:
The following is the view from the soldering point of a cable.
FP0, FP2, FP2SH, FPM CPU : 9P D-Sub to 5P Mini-DIN
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 5P Mini-DIN
Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

1 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 5P Mini-DIN
Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

1 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 5P Mini-DIN
Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

1 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 5P Mini-DIN
Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

1 GND

692

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 5P Mini-DIN
Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

1 GND
View from the
soldering point
of a cable.

The following is the view from the soldering point of a cable.


FP0 CPU : 9P D-Sub to 3P Terminal:
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 3P Terminal

2 RX

8 RX

3 TX

7 TX

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 3P Terminal

2 RX

3 TX

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

RS232 3P Terminal

D-Sub Female
2 RX

3 TX

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 3P Terminal

2 RX

6 RX

8 RX

3 TX

4 TX

7 TX

5 GND

5 GND

5 GND

693

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 3P Terminal

9 RX

6 TX

5 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P

COM3 RS232 9P

RS232 9P D-Sub Male

D-Sub Female

D-Sub Female

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

7 GND
4 RTS
5 CTS
8 CD
9 ER

short
short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

7 GND
4 RTS
5 CTS
8 CD
9 ER

694

short
short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

7 GND
4 RTS
5 CTS
8 CD
9 ER

short
short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

7 GND
4 RTS
5 CTS
8 CD
9 ER

short
short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

7 GND
4 RTS
5 CTS
8 CD
9 ER

695

short
short

PLC Connection Guide

The following is the view from the soldering point of a cable.


FP1 CPU : 9P D-Sub to 8P MiniDIN
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 8P Hirose
Female socket

1 RX-

2 TXDA

2 RX+

5 TXDB

3 TX-

3 RXDA

4 TX+

6 RXDB

5 GND

1 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 8P Hirose
Female socket

7 RX-

2 TXDA

6 RX+

5 TXDB

9 TX-

3 RXDA

8 TX+

6 RXDB

5 GND

1 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 8P Hirose
Female socket

1 RX-

1 RX-

2 TXDA

2 RX+

2 RX+

5 TXDB

3 TX-

3 TX-

3 RXDA

4 TX+

4 TX+

6 RXDB

5 GND

5 GND

1 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 8P Hirose
Male

1 RX-

2 TXDA

2 RX+

5 TXDB

3 TX-

3 RXDA

4 TX+

6 RXDB

5 GND

1 GND

696

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 8P Hirose
Male

1 RX-

2 TXDA

2 RX+

5 TXDB

3 TX-

3 RXDA

4 TX+

6 RXDB

5 GND

1 GND
View from the
soldering point
of a cable.

The following is the view from the soldering point of a cable.


FP3 CPU : 9P D-Sub to 15P D-Sub
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 15P D-Sub


Male

1 RX-

9 TXDA

2 RX+

2 TXDB

3 TX-

10 RXDA

4 TX+

3 RXDB

5 GND

7 GND
4 RTS+
5 CTS+
11 RTS12 CTS-

short
short

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 15P D-Sub


Male

7 RX-

9 TXDA

6 RX+

2 TXDB

9 TX-

10 RXDA

8 TX+

3 RXDB

5 GND

7 GND
4 RTS+
5 CTS+
11 RTS12 CTS697

short
short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 15P D-Sub


Male

1 RX-

1 RX-

9 TXDA

2 RX+

2 RX+

2 TXDB

3 TX-

3 TX-

10 RXDA

4 TX+

4 TX+

3 RXDB

5 GND

5 GND

7 GND
4 RTS+
5 CTS+
11 RTS12 CTS-

short
short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 15P D-Sub


Male

1 RX-

9 TXDA

2 RX+

2 TXDB

3 TX-

10 RXDA

4 TX+

3 RXDB

5 GND

7 GND
4 RTS+
5 CTS+
11 RTS12 CTS-

698

short
short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 15P D-Sub


Male

1 RX-

9 TXDA

2 RX+

2 TXDB

3 TX-

10 RXDA

4 TX+

3 RXDB

5 GND

7 GND
4 RTS+
5 CTS+
11 RTS12 CTS-

Driver Version:
Version

Date

Description

V1.80

Apr/09/2010

Added registers: FL

699

short
short

PLC Connection Guide

Panasonic FP (Ethernet)
Supported Series: NAIS (Matsushita) FP series include FP-X, FP-, FP0, FP1, FP2,
FP2SH, FP10SH and FP3 Ethernet support FP-X with AFPX-COM5.
Website: http://pewa.panasonic.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

Panasonic FP (Ethernet)

PLC I/F

Ethernet

Port no.

9094

PLC sta. no.

Notes

0~255

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDh

0 ~ 9999f

Input (X)

DDDDh

0 ~ 9999f

Output (Y)

DDDDh

0 ~ 9999f

Internal Relay (R)

DDDD

0 ~ 9999

Link Relay (L)

L_Bit

DDDDh

0 ~ 9999f

DDDD

0 ~ 9999

Timer (T)

DDDD

0 ~ 9999

Counter (C)

SV

DDDD

0 ~ 9999

Timer/Counter Set Value (SV)

EV

DDDDD

0 ~ 65535

Timer/Counter Elapse Value (EV)

DT

DDDDD

0 ~ 99999

Data Register (DT)

LD

DDDD

0 ~ 8447

Link Register (LD)

WX

DDDD

0 ~ 9999

Input (WX) (read only)

WY

DDDD

0 ~ 9999

Output (WY)

WR

DDDD

0 ~ 9999

Internal Relay (WR)

WL

DDDD

0 ~ 9999

Link Relay (WL)

FL

DDDDD

0 ~ 99999

File Register (FL)

700

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Ethernet Connection TCP Port: 9094

Ethernet

RS232
FP-X

MT8000

AFPX-COM5

Driver Version:
Version

Date

V1.80

Apr/12/2010

Description

701

PLC Connection Guide

Panasonic FP2 (Ethernet)


Supported Series: NAIS (Matsushita) FP2 series include FP2, FP2SH, and FP10SH CPU.
Website: http://pewa.panasonic.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

Panasonic FP2 (Ethernet)

PLC I/F

Ethernet

Port no.

8500

PLC sta. no.

Notes

0~255

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDh

0 ~ 9999f

Input (X)

DDDDh

0 ~ 9999f

Output (Y)

DDDDh

0 ~ 9999f

Internal Relay (R)

DDDD

0 ~ 9999

Link Relay (L)

L_Bit

DDDDh

0 ~ 9999f

DDDD

0 ~ 9999

Timer (T)

DDDD

0 ~ 9999

Counter (C)

SV

DDDD

0 ~ 9999

Timer/Counter Set Value (SV)

EV

DDDDD

0 ~ 65535

Timer/Counter Elapse Value (EV)

DT

DDDDD

0 ~ 99999

Data Register (DT)

LD

DDDD

0 ~ 8447

Link Register (LD)

WX

DDDD

0 ~ 9999

Input (WX) (read only)

WY

DDDD

0 ~ 9999

Output (WY)

WR

DDDD

0 ~ 9999

Internal Relay (WR)

WL

DDDD

0 ~ 9999

Link Relay (WL)

702

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Mar/11/2010

Driver released.

703

PLC Connection Guide

Panasonic MINAS A4
Supported Series: Panasonic MINAS A4 series Servo Drive.

HMI Setting:
Parameters

Recommended

PLC type

Panasonic MINAS A4

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

None

Stop bits

Axis no.

0 (master station only)

Options

Notes

2400 ~ 57600

0 ~ F (slave)

Device Address:
Bit/Word

Device type

Format

Range

Memo

Command 20

0~7

States (Note 3)

Command 27

DD

0 ~ 31

Input Signal (Note 3)

Command 28

DD

0 ~ 31

Output Signal (Note 3)

Command 01

CPU Version (Numeric


format:16-bit Hex)

Command 05

DD

0 ~ 11

Driver Version (ASCII / 12 words)

Command 06

DD

0 ~ 11

Motor Version (ASCII / 12 words)

Command 21

0~1

command pulse counter


(Numeric format: 32-bit Signed)

Command 22

0~1

feedback pulse counter


(Numeric format: 32-bit Signed)

Command 24

present speed
(Numeric format: 16-bit Unsigned)

Command 25

present torque
(Numeric format: 16-bit Unsigned)

Command 26

0~1

Command 84

present deviation counter


(Numeric format: 32-bit Signed)
write parameter to EEPROM
(Note 1)

704

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

Command 90

present Alarm Data


(Numeric format: 16-bit Unsigned)

Command 91

DD

1 ~ 14

Alarm History (Note 4)


(Numeric format: 16-bit Unsigned)

Command 92

DD

1 ~ 14

Batch Alarm (Note 4)


(Numeric format: 16-bit Unsigned)

Command 93

clear Alarm History (include


EEPROM) (Note 1)

Command 94

Alarm Clear (Note 1)

Command 9B

Absolute Clear (Note 1)

Parameter

HH

0 ~ 7f

Individual Parameter (range: 0x00


~ 0x7F) (Note 2)

Comm2D_S

0~1

Comm2D_M

0~1

Command 2D Signle turn data


(Numeric format: 32-bit Signed)
Command 2D Multi-turn data
(Numeric format: 32-bit Signed)

Note:
1. Command 84, Command 93, Command 94, and Command 9B are write only. (These
commands are able to use Set Bit Object and execute the write command after
triggering Set Bit Object.). Commands other than these four are read only.
2. Parameter read/write: Use device type to define address control from 00~7F.
For example: address_00 is mapping to Parameter_00.
(Please refer to Panasonic MINAS A4 Series User Manual.)
3. Device address type can define MINAS A4 Drivers command list.
Command 20, Command 27, and Command 28 are Bit type, use Operating range to
map communication order status.
For example: Command 20_3 means Read state_CCW.
(Please refer to Panasonic MINAS A4 Series User Manual.)
4. Command 91 and Command 92 are word type, use Operating range to map the
record of 14 alarms.
For example: Command 91_1 means Read alarm data_First alarm.

705

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
MINAS A4 Driver CNX4 Port
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

8 RX

3 TXD

3 TX

7 TX

5 RXD

5 GND

5 GND

4 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

3 TXD

3 TX

5 RXD

5 GND

4 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

RS232 8P Mini-DIN

D-Sub Female

Male

2 RX

3 TXD

3 TX

5 RXD

5 GND

4 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 8P Mini-DIN
Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

5 RXD

5 GND

5 GND

5 GND

4 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

9 RX

3 TXD

6 TX

5 RXD

5 GND

4 GND
View from the
soldering point
of a cable.

706

PLC Connection Guide


MINAS A4 Driver
CNX3 Port

MINAS A4 Driver
CNX4 Port
3 TX

8P Mini-Din Male
MINAS A4 Driver
CNX3 / CNX4 Port

RX

GND

GND

D-

D-

D+

D+

RS485 cable / DVOP1970-005


MINAS A4 Driver
8p Mini-DIN Male

MINAS A4 Driver
8p Mini-DIN Male

D-

D-

D+

D+

GND

GND

RS232 cable / DVOP1960


MINAS A4 Driver
9P D-SUB Female

MINAS A4 Driver
8p Mini-DIN Male

RXD

RXD

TXD

TXD

GND

GND

HMI connect with one Device

HMI connect with multi devices

707

PLC Connection Guide

Driver Version:
Version

Date

V1.10

Jan/11/2010

V1.20

Jul/25/2012

Description
Added registersComm2D_S and Comm2D_M.

708

PLC Connection Guide

Panasonic MINAS A5
Supported Series: Panasonic MINAS A5 series Servo Drive.

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Panasonic MINAS A5

PLC I/F

RS232

RS232/RS485 2W

Baud rate

9600

2400~115200

Data bits

Parity

None

Stop bits

Axis no.

0 (master station only)

0 ~ 127 (slave)

* When connecting with more than two devices, it is recommended to set timeout to more
than 4 seconds. Set a longer timeout when connecting with more devices to maintain good
communication.

Device Address:
Bit/Word

Device type

Format

Range

Memo

Command 20

0~7

States (Note 3)

Command 27

DD

0 ~ 31

Input Signal (Note 3)

Command 28

DD

0 ~ 31

Output Signal (Note 3)

Command 01

CPU Version (Numeric


format:16-bit Hex)

Command 05

DD

0 ~ 11

Driver Version (ASCII / 12 words)

Command 06

DD

0 ~ 11

Motor Version (ASCII / 12 words)

Command 21

0~1

command pulse counter


(Numeric format: 32-bit Signed)

Command 22

0~1

feedback pulse counter


(Numeric format: 32-bit Signed)

Command 24

present speed
(Numeric format: 16-bit Unsigned)

Command 25

present torque
(Numeric format: 16-bit Unsigned)

709

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

Command 26

0~1

present deviation counter


(Numeric format: 32-bit Signed)

Command2D_S

0~1

Command 2D Signle turn data


(Numeric format: 32-bit Signed)

Command2D_M D

0~1

Command 2D Multi-turn data


(Numeric format: 32-bit Signed)

Parameter

HHH

0 ~ 639

Individual Parameter (range: 0x000


~ 0x639) (Note 2)

Command 72

write parameter to EEPROM


(Note 1)

Command 90

present Alarm Data


(Numeric format: 16-bit Unsigned)

Command 92

DD

1 ~ 14

Batch Alarm (Note 4)


(Numeric format: 16-bit Unsigned)

Command 93

clear Alarm History (include


EEPROM) (Note 1)

Command 94

Alarm Clear (Note 1)

Command 9B

Absolute Clear (Note 1)

Note:
1.

2.

Command 72, Command 93, Command 94, and Command 9B are write only. (These
commands are able to use Set Bit Object and execute the write command after
triggering Set Bit Object.). Commands other than these four are read only.
Parameter read/write: Use device type to define address control from 000~639.

For example: address_000 is mapping to Parameter_000.


(Please refer to Panasonic MINAS A5 Series User Manual.)
3. Device address type can define MINAS A5 Drivers command list.
Command 20, Command 27, and Command 28 are Bit type, use Operating range to
map communication order status.
For example: Command 20_3 means Read state_CCW.
(Please refer to Panasonic MINAS A5 Series User Manual.)
4. Command 92 are word type, use Operating range to map the record of 14 alarms.

710

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
MINAS A5 Driver X2 Port RS232 Signal
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 8P Connector

2 RX

8 RX

3 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

1 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 8P Connector

2 RX

3 TXD

3 TX

4 RXD

5 GND

1 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

RS232 8P Connector

D-Sub Female
2 RX

3 TXD

3 TX

4 RXD

5 GND

1 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 8P Connector

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

1 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 8P Connector

9 RX

3 TXD

6 TX

4 RXD

5 GND

1 GND

711

PLC Connection Guide

The following is the view from the soldering point of a cable.


MINAS A5 Driver X2 Port RS485 Signal
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P
Connector

1 RX-

6 Data-

5,7 485-

2 RX+

9 Data+

6,8 485+

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P
Connector

7 RX-

4 Data-

5,7 485-

6 RX+

1 Data+

6,8 485+

5 GND

5 GND

GND

cMT/mTV series

GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P
Connector

1 RX-

7 Data-

5,7 485-

2 RX+

8 Data+

6,8 485+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P
Connector

1 RX-

6 Data-

5,7 485-

2 RX+

9 Data+

6,8 485+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P
Connector

1 RX-

6 Data-

5,7 485-

2 RX+

9 Data+

6,8 485+

5 GND

5 GND

712

GND

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P
Connector

1 RX-

7 Data-

5,7 485-

2 RX+

8 Data+

6,8 485+

5 GND

5 GND

GND

Driver Version:
Version

Date

Description

V1.00

May/23/2012

V1.10

Jul/13/2013

Driver released.
Added registersComm2D_S and Comm2D_M.

V1.20

Mar/10/2014

Fixed th problem where RS485 cannot communicate.

713

PLC Connection Guide

Parker ACR9000
Supported Series: Parker ACR9000.
Website: http://www.parkermotion.com

HMI Setting:
Parameters

Recommended

PLC type

Parker ACR9000

PLC I/F

RS232

RS485 4W / RS232/Ethernet

Baud rate

38400

1200 - 38400

Data bits

7,8

Parity

None

Even, Odd, None

Stop bits

1,2

Port no.

5006

PLC sta. no.

Online simulator

Options

YES

Notes

Extend address mode

Device Address:
Bit/Word Device type

Format

Range

P_Low16bit

DDDDDdd

0 ~ 9999915

P_High16bit

DDDDDdd

0 ~ 9999915

P_Int32

DDDDD

0 ~ 99999

P_Float

DDDDD

0 ~ 99999

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Parker AC9000 RS232


9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
714

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Parker AC9000 RS232


9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

Parker AC9000 RS232


9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Parker AC9000 RS232


9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

Parker AC9000 RS232


9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

715

PLC Connection Guide

Ethernet cable:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Dec/30/2008

Driver released.

V1.20

Sep/09/2015

Support ethernet communication

716

PLC Connection Guide

Parker Compax3
Supported Series: Parker Compax3 Servo Drive.
Website: http://www.parker.com

HMI Setting:
RS232
Parameters

Recommended

Options

Notes

PLC type

Parker Compax3

PLC I/F

RS232

Baud rate

115200

Data bits

7 or 8

Parity

None

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

Must be 0 for RS232

Parameters

Recommended

Options

Notes

PLC type

Parker Compax3

PLC I/F

RS485 2W

Baud rate

9600

Data bits

7 or 8

Parity

None

Even, Odd, None

Stop bits

1 or 2

RS485

PLC sta. no.

1-99

717

Range from 1 to 99 for


RS485, according to the
PLC setting.

PLC Connection Guide

PLC Setting:
How to set Compax 3 servo to RS485 mode?
1. Open C3 ServoManager2, select Communication => RS-485 Settings.

2. Click to Configure RS-485/POP Settings.

3. Set parameters as below:

718

PLC Connection Guide

4. Download settings to Compax3 Servo.


5. Set EasyBuilder system parameter and connect with PLC for communication of HMI
and Servo.

Device Address:
Bit/Word

Device type

Format

Range

Memo

R_Low16bit

DDDDDDDDh

0 ~ 99999999f

R_High16bit

DDDDDDDDh

0 ~ 99999999f

DW

Register_Int

DDDDDD

0 ~ 999999

For Register INT32, U32

DW

Register_float

DDDDDD

0 ~ 999999

For Register INT32, U32

Register_Short

DDDDDD

0 ~ 999999

For Register INT16, U16

The range of the address that can be operated depends on the address type.
(For more information, please see PLC Connection Guide)
For example:
If the read / write address is: 1901.2, please enter 190102
If the read / write address is: 400.1, please enter 40001

Wiring Diagram:
The following is the view from the soldering point of a cable.
Parker Compax3 PLC X10 : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

719

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

The following is the view from the soldering point of a cable.


Parker Compax3 PLC X10 : RS485 2W
eMT3000 series
COM1 RS485 2W

COM3 RS485 2W

RS485 2W 9P D-Sub

9P D-Sub Male

9P D-Sub Male

Male

1 RX-

6 Data-

3 Data-

2 RX+

9 Data+

7 Data+

5 GND

5 GND

5 GND
1 Enable RS485

9 +5V

720

short

PLC Connection Guide

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

3 Data-

6 RX+

1 Data+

7 Data+

5 GND

5 GND

5 GND
1 nable RS485

9 +5V

short

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

3 Data-

2 RX+

8 Data+

7 Data+

5 GND

9 GND

5 GND
1 Enable RS485

9 +5V

short

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W

COM3 RS485 2W

RS485 2W 9P D-Sub

9P D-Sub Male

9P D-Sub Male

Male

1 RX-

6 Data-

3 Data-

2 RX+

9 Data+

7 Data+

5 GND

5 GND

5 GND
1 Enable RS485

9 +5V

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W

COM3 RS485 2W

RS485 2W 9P D-Sub

9P D-Sub Male

9P D-Sub Male

Male

1 RX-

6 Data-

3 Data-

2 RX+

9 Data+

7 Data+

5 GND

5 GND

5 GND
1 Enable RS485

9 +5V

721

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

3 Data-

2 RX+

8 Data+

7 Data+

5 GND

5 GND

5 GND
1 Enable RS485

9 +5V

Driver Version:
Version

Date

V1.70

Mar/30/2009

Description

722

short

PLC Connection Guide

Parker Compumotor 6K Series


HMI Setting:
Parameters

Recommended

Options

PLC type

Parker Compumotor 6K Series

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type Format

Range

Memo

VARB(L)

DDDdd

1 ~ 125

The lower 16 bits data of VARB

VARB(H)

DDDdd

1 ~ 125

The higher 16 bits data of VARB

RUN_PRG

DW

VARI

DDD

1 ~ 125

DW

VAR

DDD

1 ~ 125

Must select single float data


mode.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

723

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

PLC RS232 9P D-Sub


Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Male

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Apr/7/2011

Driver released.

724

PLC Connection Guide

Parker SLVD Series


Supported Series : Parker SLVD Servo, SLVD1N, SLVD2N, SLVD5N, SLVD7N,
SLVD10N, SLVD15N, SLVD17N.
Website: http://www.parker.com/portal/site/PARKER/

HMI Setting:
Parameters

Recommended

PLC type

Parker SLVD Series

PLC I/F

RS485 4W

Baud rate

9600

9600/19200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1,2

PLC sta. no.

Online simulator

Options

Notes

0-31
YES

Extend address mode

Device Address:
Bit/Word

Device type

Format

Range

Memo

Par_Binary

DDDDdd

0 ~ 999915

Set bit parameter

Par_One_Word

DDDD

0 ~ 9999

Set 2 bytes parameter

DW

Par_Two_Word

DDDD

0 ~ 9999

Set 4 bytes parameter

Par_One_Byte

DDDD

0 ~ 9999

Set 1 byte prarmeter

RESET

RUN

725

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
Parker SLVD Servo Serial Link X1
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 15P D-Sub


Male

1 RX-

7 TX-

2 RX+

12 TX+

3 TX-

2 RX-

4 TX+

1 RX+
6 TER

5 GND

short

3 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 15P D-Sub


Male

7 RX-

7 TX-

6 RX+

12 TX+

9 TX-

2 RX-

8 TX+

1 RX+
6 TER

5 GND

short

3 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 15P D-Sub


Male

1 RX-

1 RX-

7 TX-

2 RX+

2 RX+

12 TX+

3 TX-

3 TX-

2 RX-

4 TX+

4 TX+

1 RX+
6 TER

5 GND

5 GND

3 GND

726

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 15P D-Sub


Male

1 RX-

7 TX-

2 RX+

12 TX+

3 TX-

2 RX-

4 TX+

1 RX+
6 TER

5 GND

short

3 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 15P D-Sub


Male

1 RX-

7 TX-

2 RX+

12 TX+

3 TX-

2 RX-

4 TX+

1 RX+
6 TER

5 GND

3 GND

Driver Version:
Version

Date

Description

V1.00

Jan/27/2010

Driver released.

727

short

PLC Connection Guide

PATLITE VM/VMS Series


Supported Series: PATLITE VM/VMS Series
Website: http://www.patlite.co.jp

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

PATLITE VM/VMS Series

PLC I/F

RS232

RS232 / RS485 2W /
RS485 4W/ Ethernet

Baud rate

38400

9600 ~ 115200

Data bits

7,8

Parity

Even

Even , Odd , None

Stop bits

1,2

PLC sta. no.

0 ~ 31

Port no.

10600

Device Address:
Bit/Word

Device type

Format

Range

LAW_bit

HHHHh

1 ~ 7FFE

LAW

HHHH

1 ~ 7FFE

LAW6Mode

LAW6Style

LAW6Scale

LAW6BG_c

LAW6Chr_c

UNI2sJIS

HHHH

1 ~ 7FFE

LAWUnicode to shift-JIS

UNI2BIG5

HHHH

1 ~ 7FFE

LAWUnicode to BIG5

728

Memo
hBit no.(0 ~ f)

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Female

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

PLC RS232 9P D-Sub


Female

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

PLC RS232 9P D-Sub


Female

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

729

PLC Connection Guide

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W
Terminal

1 RX-

6 Data-

11 Data-

2 RX+

9 Data+

10 Data+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W

COM3 RS485 2W

PLC RS485 2W

9P D-Sub Female

9P D-Sub Female

Terminal

7 RX-

4 Data-

11 Data-

6 RX+

1 Data+

10 Data+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W
Terminal

1 RX-

7 Data-

11 Data-

2 RX+

8 Data+

10 Data+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W
Terminal

1 RX-

6 Data-

11 Data-

2 RX+

9 Data+

10 Data+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W
Terminal

1 RX-

6 Data-

11 Data-

2 RX+

9 Data+

10 Data+

5 GND

5 GND

730

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

PLC RS485 2W
Terminal

1 RX-

7 Data-

11 Data-

2 RX+

8 Data+

10 Data+

5 GND

5 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS485 4W

PLC RS485 4W

9P D-Sub Male

Terminal

1 RX-

12 TX-

2 RX+

13 TX+

3 TX-

11 RX-

4 TX+

10 RX+

5 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

PLC RS485 4W
Terminal

7 RX-

12 TX-

6 RX+

13 TX+

9 TX-

11 RX-

8 TX+

10 RX+

5 GND
MT8000iE/MT8000XE series except MT8050iE
COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

PLC RS485 4W
Terminal

1 RX-

1 RX-

12 TX-

2 RX+

2 RX+

13 TX+

3 TX-

3 TX-

11 RX-

4 TX+

4 TX+

10 RX+

5 GND

5 GND

731

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

PLC RS485 4W
Terminal

1 RX-

12 TX-

2 RX+

13 TX+

3 TX-

11 RX-

4 TX+

10 RX+

5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

PLC RS485 4W
Terminal

1 RX-

12 TX-

2 RX+

13 TX+

3 TX-

11 RX-

4 TX+

10 RX+

5 GND

Etehernet cable:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Jan/25/2013

Driver released
732

PLC Connection Guide

Rockwell CompactLogix - Free Tag Names


Rockwell ControlLogix, CompactLogix, FlexLogix CH0 DF1.
Website: http://www.ab.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Rockwell CompactLogix - Free Tag Names

PLC I/F

RS232

Baud rate

19200

9600, 19200, 38400

Data bits

Parity

None

Even, Odd, None

Stop bits

Turn around delay (ms)

10

10 ~ 100

HMI sta. no.

Notes

*Note

PLC sta. no.


1
1-31
*NoteWhen the communication is not stable, please adjust the parameter of [turn around
delay] till the communication is normal.

PLC Setting:
Communication mode

1.

DF1 No Handshake protocol 19200, None, 8, 1 (default)


Error Check: BCC, Station Address: 1

Create new tags (Controller Tags and Program Tags supported).

733

PLC Connection Guide

2.

Export Tag data to CSV file. ( [Tools] [Export] [Tags and Logic Comments] )

Note: The separator character in CSV file must be a comma , otherwise the file is invalid.

The directory of changing system settings: [Control Panel] [Date, Time, Language,
and Regional Options] [Change the format of numbers, dates, and times]
[Customize] [List separator]. Please select , and export CSV file after setting.

734

PLC Connection Guide

3.

Open EasyBuilder project file, select the driver and set communication parameter.
Click [Data Type] to open [Structure Editor] and edit the data type of the tags.

735

PLC Connection Guide

4.

In [Structure Editor] edit the data type of [Program Tag].


The imported csv file is shown below:
Note: The Program Tag can directly be imported in EasyBuilder Pro V3.00.05, EasyBuilder
8000 V4.65.08, and the later versions. Please go to step 5 without editing manually.

Step 1
Right click on [Structure Editor] [User-Defined] to add a [new data type].

736

PLC Connection Guide

Step 2
After adding all Program Tags, click [OK] [Save] [Exit] to leave the editor dialog.

737

PLC Connection Guide

5.

In [System Parameter Settings], click [Import Tag], select the csv file. After
importing a message window is displayed.

6.

In the object property dialog, select PLC Tag address.

738

PLC Connection Guide

Device Address:
PLC Data Type Name

Bit/Word

EasyBuilder Data Format

Memo

BOOL

Boolean

Bit object

INT

Integer

16-bit signed, ASCII

-32768 ~ 32767

DINT

Double Integer

32-bit signed

-231 ~ (231-1)

REAL

Single Precision Float

32-bit Float

IEEE 754

BitArray
SINT

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

8 RX

3 TD

3 TX

7 TX

2 RD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

6 RX

8 RX

3 TD

3 TX

4 TX

7 TX

2 RD

5 GND

5 GND

5 GND

5 GND

739

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

9 RX

3 TD

6 TX

2 RD

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

June/2/2011

Driver released.

740

PLC Connection Guide

Rockwell CompactLogix/FlexLogix
Supported Series: Rockwell ControlLogix, CompactLogix, FlexLogix CH0 DF1.
Website: http://www.ab.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Rockwell CompactLogix/FlexLogix

PLC I/F

RS232

Baud rate

19200

9600, 19200, 38400

Data bits

Parity

None

Even, Odd, None

Stop bits

HMI sta. no.

PLC sta. no.

Notes

1-31

PLC Setting:
Communication mode

DF1 No Handshake protocol 19200, None, 8, 1 (default)


Error Check: BCC, Station Address: 1

741

PLC Connection Guide

ControlLogix, CompactLogix CPU CH0 setting:

Create a Tag:
The name format must be 4 chars. For example: B003, T004, C005, N007, and F008.
Two or three chars are not available. For example: B03 or B3.

742

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

Memo

B_BOOL

FFFDDDdd

0 ~ 25525515

Bit data file

N_BOOL

FFFDDDdd

0 ~ 25525515

DW

Tx.ACC

FFFDDD

0 ~ 255255

DW

Tx.PRE

FFFDDD

0 ~ 255255

DW

Nx_INT

FFFDDD

0 ~ 255255

Bx_INT

FFFDDD

0 ~ 255255

DW

Cx.ACC

FFFDDD

0 ~ 255255

DW

Cx.PRE

FFFDDD

0 ~ 255255

F8_REAL

DDD

0 ~ 255

Fx_REAL

FFFDDD

0 ~ 255255

743

Integer data file bit level (N7, 10 ~


255)
Timer Accumulator Value (T4, T10
~ 255)
Timer Preset Value
(T4, T10 ~ 255)
Integer data file
(N7, 10 ~ 255)
Bit data file word level
Counter Accumulator Value (C5,
C10 ~ 255)
Counter Preset Value
(C5, C10 ~ 255)
Floating point data file
(F8)
Floating point data file (F008, F010
~ F255)

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

8 RX

3 TD

3 TX

7 TX

2 RD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

6 RX

8 RX

3 TD

3 TX

4 TX

7 TX

2 RD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

9 RX

3 TD

6 TX

2 RD

5 GND

5 GND

744

PLC Connection Guide

Driver Version:
Version

Date

V1.50

Dec/30/2008

Description

745

PLC Connection Guide

Rockwell DF1
Supported Series: Rockwell MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5/01, 5/02,
5/03, 5/04, 5/05.
Website: http://www.ab.com
Note: Allen-Bradley DF1 driver uses CRC checksum.

HMI Setting:
Parameters

Recommended

Options

PLC type

Rockwell DF1

PLC I/F

RS232

Baud rate

19200

9600, 19200, 38400

Data bits

Parity

None

Even, Odd, None

Stop bits

HMI sta. no.

PLC sta. no.

Notes

1-31

PLC Setting:
Communication mode

DF1 Full Duplex protocol 19200, None, 8, 1 (default)


Error Check: CRC

Device Address:
Bit/Word Device type

Format

Range

Memo

I1

0 ~ 25515

Input (I)

O0

DDDdd
DDDdd

0 ~ 25515

Output (O)

B3

DDDdd

0 ~ 25515

Bit data file (B3)

B10 ~ 13

DDDdd

0 ~ 25515

Bit data file (B10 ~ 13)

S_Bit

DDDdd

0 ~ 25515

Status (S) bit level

Bfn

FFFDDDdd

0 ~ 25525515

Bit data file (B3, 10 ~ 254)

NfnBit

FFFDDDdd

0 ~ 25525515

Integer data file bit level


(N7, 10 ~ 254)

T4SV

DDD

0 ~ 255

Timer Preset Value (T4)

T4PV

DDD

0 ~ 255

Timer Accumulator Value (T4)

C5SV

DDD

0 ~ 255

Counter Preset Value (C5)

746

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo

C5PV

DDD

0 ~ 255

TfnSV

FFFDDD

0 ~ 255255

Counter Accumulator Value


(C5)
Timer Preset Value

TfnPV

FFFDDD

0 ~ 255255

Timer Accumulator Value

CfnSV

FFFDDD

0 ~ 255255

Counter Preset Value

CfnPV

FFFDDD

0 ~ 255255

Counter Accumulator Value

N7

DDD

0 ~ 255

Integer data file (N7)

N10 ~ 15

DDD

0 ~ 255

Integer data file (N10 ~ 15)

Nfn

FFFDDD

0 ~ 255255

Integer data file (N7,10 ~ 254)

DDD

0 ~ 255

Status (S)

F8

DDD

0 ~ 255

Floating point data file (F8)

Ffn

FFFDDD

0 ~ 255255

Lfn

FFFDDD

0 ~ 255255

String

STfn

DDD.DDD.DD

0 ~ 255.255.40 File no.Element no.Data no.

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 8P Mini-DIN: MicroLogix 1000, 1100, 1200, 1400, 1500
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

2 RX

8 RX

7 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

2 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

2 RX

7 TXD

3 TX

4 RXD

5 GND

2 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

2 RX

7 TXD

3 TX

4 RXD

5 GND

2 GND

747

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

MicroLogix RS232 8P
Mini-DIN Male

2 RX

6 RX

8 RX

7 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

2 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

9 RX

7 TXD

6 TX

4 RXD

5 GND

2 GND
View from the
soldering point
of a cable.

The following is the view from the soldering point of a cable.


9P D-Sub to 9P D-Sub: SLC5/03, 04, 05 CH0
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

8 RX

3 TD

3 TX

7 TX

2 RD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P

AB CPU CH0 RS232 9P

D-Sub Female

D-Sub Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

748

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

6 RX

8 RX

3 TD

3 TX

4 TX

7 TX

2 RD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

9 RX

3 TD

6 TX

2 RD

5 GND

5 GND

Driver Version:
Version

Date

Description

V2.20

Jan/05/2010

V2.50

Oct/14/2012

Add device type : I1n,O0n.

V2.70

Jun/27/2013

Add device type : STfn

749

PLC Connection Guide

Rockwell DF1 (BCC)


Supported Series: Rockwell MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5/01, 5/02,
5/03, 5/04, 5/05.
Website: http://www.ab.com
Note: Allen-Bradley DF1 (BCC) and Allen-Bradley DF1 are the same; the only difference is
the use of BCC checksum.

HMI Setting:
Parameters

Recommended

Options

PLC type

Rockwell DF1 (BCC)

PLC I/F

RS232

Baud rate

19200

9600, 19200, 38400

Data bits

Parity

None

Even, Odd, None

Stop bits

HMI sta. no.

PLC sta. no.

Notes

1-31

PLC Setting:
Communication mode

DF1 Full Duplex protocol 19200, None, 8, 1 (default)


Error Check: BCC

Device Address:
Bit/Word

Device type Format

Range

Memo

I1

DDDdd

0 ~ 25515

Input (I)

O0

DDDdd

0 ~ 25515

Output (O)

B3

DDDdd

0 ~ 25515

Bit data file (B3)

B10 ~ 13

DDDdd

0 ~ 25515

Bit data file (B10 ~ 13)

S_Bit

DDDdd

0 ~ 25515

Status (S) bit level

Bfn

FFFDDDdd

0 ~ 25525515

Bit data file (B3, 10 ~ 254)

NfnBit

FFFDDDdd

0 ~ 25525515

Integer data file bit level (N7, 10


~ 254)

T4SV

DDD

0 ~ 255

Timer Preset Value (T4)

T4PV

DDD

0 ~ 255

Timer Accumulator Value (T4)

750

PLC Connection Guide

Bit/Word

Device type Format

Range

Memo

C5SV

DDD

0 ~ 255

Counter Preset Value (C5)

C5PV

DDD

0 ~ 255

TfnSV

FFFDDD

0 ~ 255255

Counter Accumulator Value


(C5)
Timer Preset Value

TfnPV

FFFDDD

0 ~ 255255

Timer Accumulator Value

CfnSV

FFFDDD

0 ~ 255255

Counter Preset Value

CfnPV

FFFDDD

0 ~ 255255

Counter Accumulator Value

N7

DDD

0 ~ 255

Integer data file (N7)

N10~15

DDD

0 ~ 255

Integer data file (N10 ~ 15)

Nfn

FFFDDD

0 ~ 255255

Integer data file (N7, 10 ~ 254)

DDD

0 ~ 255

Status (S)

F8

DDD

0 ~ 255

Floating point data file (F8)

Ffn

FFFDDD

0 ~ 255255

Lfn

FFFDDD

0 ~ 255255

STfn

DDD.DDD.DD

0 ~ 255.255.40

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 8P Mini-DIN: MicroLogix 1000, 1100, 1200, 1500
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

2 RX

8 RX

7 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

2 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

2 RX

7 TXD

3 TX

4 RXD

5 GND

2 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

2 RX

7 TXD

3 TX

4 RXD

5 GND

2 GND
751

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

MicroLogix RS232 8P
Mini-DIN Male

2 RX

6 RX

8 RX

7 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

2 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

9 RX

7 TXD

6 TX

4 RXD

5 GND

2 GND
View from the
soldering point
of a cable.

The following is the view from the soldering point of a cable.


9P D-Sub to 9P D-Sub: SLC5/03, 04, 05 CH0
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

8 RX

3 TD

3 TX

7 TX

2 RD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P

AB CPU CH0 RS232 9P

D-Sub Female

D-Sub Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

752

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

6 RX

8 RX

3 TD

3 TX

4 TX

7 TX

2 RD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

9 RX

3 TD

6 TX

2 RD

5 GND

5 GND

Driver Version:
Version

Date

Description

V2.70

Sep/05/2013

Added register: STfn.

753

PLC Connection Guide

Rockwell DH485
Supported Series: Rockwell MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5/01, 5/02,
5/03, 5/04, 5/05.
Website: http://www.ab.com

HMI Setting:
Parameters

Recommended

PLC type

Rockwell DH485

PLC I/F

RS485 2W

RS232

Baud rate

19200

9600, 19200

Data bits

Parity

Even

Stop bits

HMI sta. no.

PLC sta. no.

1-31

Online simulation

YES

Extend address mode

NO

Options

Notes

PLC Setting:
Communication mode

DH485 protocol 19200 (default)


Set the Max. Node Address to the number of PLCs in use.

754

PLC Connection Guide

Device Address:
Bit/Word Device type

Format

Range

Memo

I1

DDDdd

0 ~ 25515

Input (I)

O0

DDDdd

0 ~ 25515

Output (O)

B3

DDDdd

0 ~ 25515

Bit data file (B3)

B10 ~ 13

DDDdd

0 ~ 25515

Bit data file (B10 ~ 13)

Bfn

FFFDDDdd 0 ~ 25525515

NfnBit

FFFDDDdd 0 ~ 25525515

S_Bit

DDDdd

0 ~ 25515

Status file

T4SV

DDD

0 ~ 255

Timer Preset Value (T4)

T4PV

DDD

0 ~ 255

Timer Accumulator Value (T4)

C5SV

DDD

0 ~ 255

Counter Preset Value (C5)

C5PV

DDD

0 ~ 255

Counter Accumulator Value (C5)

TfnSV

FFFDDD

0 ~ 255255

Timer Preset Value

TfnPV

FFFDDD

0 ~ 255255

Timer Accumulator Value

CfnSV

FFFDDD

0 ~ 255255

Counter Preset Value

CfnPV

FFFDDD

0 ~ 255255

Counter Accumulator Value

F8

DDD

0 ~ 255

Floating point data file (F8)

N7

DDD

0 ~ 255

Integer data file (N7)

N10 ~ 15

DDD

0 ~ 255

Integer data file (N10 ~ 15)

Nfn

FFFDDD

0 ~ 255255

DDD

0 ~ 255

Bit data file (B3, 10 ~ 254)


Integer data file bit level (N7,10 ~
254)

Integer data file


(N7,10 ~ 254)
Status file

Wiring Diagram:
The following is the view from the soldering point of a cable.
RS-485: SLC500 Fixed type, SLC5/01, 02, 03 CH1.
HMI cant connect to 1747-AIC peripheral port.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

AB SLC500 DH485
RJ45 Male

1 RX-

6 Data-

2 SDB

2 RX+

9 Data+

1 SDA

5 GND

5 GND

7 GND

755

PLC Connection Guide

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

AB SLC500 DH485
RJ45 Male

7 RX-

4 Data-

2 SDB

6 RX+

1 Data+

1 SDA

5 GND

5 GND

7 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

AB SLC500 DH485
RJ45 Male

1 RX-

7 Data-

2 SDB

2 RX+

8 Data+

1 SDA

5 GND

9 GND

7 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

AB SLC500 DH485
RJ45 Male

1 RX-

6 Data-

2 SDB

2 RX+

9 Data+

1 SDA

5 GND

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

AB SLC500 DH485
RJ45 Male

1 RX-

6 Data-

2 SDB

2 RX+

9 Data+

1 SDA

5 GND

5 GND

7 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W

COM3 RS485 2W

AB SLC500 DH485

9P D-Sub Female

9P D-Sub Female

RJ45 Male

1 RX-

7 Data-

2 SDB

2 RX+

8 Data+

1 SDA

5 GND

5 GND

7 GND

756

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 8P Mini-DIN: MicroLogix 1000, 1100, 1200, and 1500 must set DH485
protocol.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

2 RX

8 RX

7 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

2 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

2 RX

7 TXD

3 TX

4 RXD

5 GND

2 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

2 RX

7 TXD

3 TX

4 RXD

5 GND

2 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

MicroLogix RS232 8P
Mini-DIN Male

2 RX

6 RX

8 RX

7 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

2 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

MicroLogix RS232 8P
Mini-DIN Male

9 RX

7 TXD

6 TX

4 RXD

5 GND

2 GND
View from the
soldering point
of a cable.

757

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 9P D-Sub: SLC5/03, 04, 05 CH0 must set DH485 protocol.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

8 RX

3 TD

3 TX

7 TX

2 RD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

AB CPU CH0 RS232 9P


D-Sub Female

2 RX

6 RX

8 RX

3 TD

3 TX

4 TX

7 TX

2 RD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232 9P


D-Sub Female

9 RX

3 TD

6 TX

2 RD

5 GND

5 GND

758

PLC Connection Guide

Driver Version:
Version

Date

V1.20

Apr/17/2009

Description

759

PLC Connection Guide

Rockwell EtherNet/IP (CompactLogix)


Supported Series: Rockwell ControlLogix, CompactLogix, FelxLogix Ethernet.
Website: http://www.ab.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Rockwell EtherNet/IP (CompactLogix)

PLC I/F

Ethernet

Port no.

44818

PLC sta. no.

Notes

PLC Setting:
RSLogix 5000 setting
Create a Tag:
The name format must be 4 chars. For example: B003, T004, C005, N007, and F008.
Two or three chars are not available. For example: B03 or B3.

760

PLC Connection Guide

Device Address:
Bit/Word Device type Format

Range

Memo

Bx_BOOL

FFFDDDdd 0 ~ 25525515

Nx_BOOL

FFFDDDdd 0 ~ 25525515

Bx_INT

FFFDDD

0 ~ 255255

Nx_INT

FFFDDD

0 ~ 255255

DW (F)

F8_REAL

DDD

0 ~ 255

Floating point data file (F8)

DW (F)

Fx_REAL

FFFDDD

0 ~ 255255

Floating point data file (F8)

DW

Cx.ACC

FFFDDD

0 ~ 255255

DW

Cx.PRE

FFFDDD

0 ~ 255255

DW

Tx.ACC

FFFDDD

0 ~ 255255

DW

Tx.PRE

FFFDDD

0 ~ 255255

DW

Lx.DINT

FFFDDD

0 ~ 255255

761

Bit data file


Integer data file bit level (N7, 10
~ 99)
Bit data file word level
Integer data file
(N7, 10 ~ 99)

Counter Accumulator Value (C5,


C10 ~ 255)
Counter Preset Value
(C5, C10 ~ 255)
Timer Accumulator Value (T4,
T10 ~ 255)
Timer Preset Value
(T4, T10 ~ 255)

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V1.30

Dec/30/2008

V1.50

Mar/6/2012

Description
Added register: Lx.DINT

762

PLC Connection Guide

Rockwell EtherNet/IP (CompactLogix) Free Tag


Names
Supported Series: Rockwell CompactLogix, FelxLogix Ethernet
Website: http://www.ab.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Rockwell EtherNet/IP (CompactLogix)


Free Tag Names

PLC I/F

Ethernet

Port no.

44818

PLC sta. no.

PLC Setting:
1.

Set PLC IP address.

763

Notes

PLC Connection Guide

2.

Create new tags (Controller Tags and Program Tags supported).

3.

Export Tag data to CSV file. ( [Tools] [Export] [Tags and Logic Comments] )

Note: The separator character in CSV file must be a comma , otherwise the file is invalid.

The directory of changing system settings: [Control Panel] [Date, Time, Language,
and Regional Options] [Change the format of numbers, dates, and times]
[Customize] [List separator]. Please select , and export CSV file after setting.

764

PLC Connection Guide

4.

Open EasyBuilder project file, select the driver and set IP address. Click [Data Type]
to open [Structure Editor] and edit the data type of the tags.

765

PLC Connection Guide

5.

In [Structure Editor] edit the data type of [Program Tag].


The imported csv file is shown below:
Note: The Program Tag can directly be imported in EasyBuilder Pro V3.00.05, EasyBuilder
8000 V4.65.08, and the later versions. Please go to step 6 without editing manually.

Step 1
Right click on [Structure Editor] [User-Defined] to add a [new data type].

766

PLC Connection Guide

Step 2
After adding all Program Tags, click [OK] [Save] [Exit] to leave the editor dialog.

767

PLC Connection Guide

6.

In [System Parameter Settings], click [Import Tag], select the csv file. After
importing a message window is displayed.

7.

In the object property dialog, select PLC Tag address.

768

PLC Connection Guide

Device Address:
PLC data type name

Bit/Word

EasyBuilder data format

Memo

BOOL

Boolean

Bit object

INT

Integer

16-bit signed, ASCII

-32768 ~ 32767

DINT

Double Integer

32-bit signed

REAL

Single Precision Float

32-bit Float

-231 ~ (231-1)
IEEE 754

BitArray
SINT

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

V1.10

Aug/25/2010

Description

769

PLC Connection Guide

Rockwell EtherNet/IP (ControlLogix) Free Tag


Names
Supported Series: Rockwell ControlLogix, CompactLogix, FelxLogix Ethernet,
CompactLogix 1768-L43 1768-L45 with 1768-ENBT/A Ethernet module
Website: http://www.ab.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Rockwell EtherNet/IP (ControlLogix) Free Tag


Names

PLC I/F

Ethernet

Port no.

44818

PLC sta. no.

The same as CPU Slot No.

PLC Setting:
1.

Set PLC IP address.

770

Notes

PLC Connection Guide

2.

Create new tags (Controller Tags and Program Tags supported).

3.

Export Tag data to CSV file. ( [Tools] [Export] [Tags and Logic Comments] )

Note: The separator character in CSV file must be a comma , otherwise the file is invalid.

The directory of changing system settings: [Control Panel] [Date, Time, Language,
and Regional Options] [Change the format of numbers, dates, and times]
[Customize] [List separator]. Please select , and export CSV file after setting.

771

PLC Connection Guide

4.

Open EasyBuilder project file, select the driver and set IP address. Click [Data Type]
to open [Structure Editor] and edit the data type of the tags.

772

PLC Connection Guide

5.

In [Structure Editor] edit the data type of [Program Tag].


The imported csv file is shown below:
Note: The Program Tag can directly be imported in EasyBuilder Pro V3.00.05, EasyBuilder
8000 V4.65.08, and the later versions. Please go to step 6 without editing manually.

Step 1
Right click on [Structure Editor] [User-Defined] to add a [new data type].

773

PLC Connection Guide

Step 2
After adding all Program Tags, click [OK] [Save] [Exit] to leave the editor dialog.

774

PLC Connection Guide

6.

In [System Parameter Settings], click [Import Tag], select the csv file. After
importing a message window is displayed.

7.

In the object property dialog, select PLC Tag address.

775

PLC Connection Guide

Device Address:
PLC data type name

Bit/Word

EasyBuilder data format

Memo

BOOL

Boolean

Bit object

INT

Integer

16-bit signed, ASCII -32768 ~ 32767

DINT

Double Integer

32-bit signed

REAL

Single Precision Float

32-bit Float

BitArray
SINT

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

V1.10

Oct/05/2010

Description

776

-231 ~ (231-1)
IEEE 754

PLC Connection Guide

Rockwell EtherNet/IP (DF1)


Supported Series: Rockwell MicroLogix 1100, 1400, SLC5/05 Ethernet port.
MicroLogix1000, 1200, 1500, SLC 5/03, 5/04 with 1761-NET-ENI
Website: http://www.ab.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Rockwell EtherNet/IP (DF1)

PLC I/F

Ethernet

Port no.

44818

HMI sta. no.

PLC sta. no.

Notes

PLC Setting:
Communication mode

Port Setting: 10/100 Mbps Full Duplex/Half Duplex

Device Address:
Bit/Word

Device type

Format

Range

Memo

I1

DDDdd

0 ~ 25515

Input (I)

O0

DDDdd

0 ~ 25515

Output (O)

I1n_Bit

SSEEdd

0 ~ 303115

SS: slot, EE: sub element, dd:bit

O0n_Bit

SSEEdd

0 ~ 303115

SS: slot, EE: sub element, dd:bit

B3

DDDdd

0 ~ 25515

Bit data file (B3)

S_Bit

DDDDDDdd

0 ~ 25525515

Status file

Bfn

FFFDDDdd

0 ~ 25525515

Bit data file (B3, 10 ~ 254)

NfnBit

FFFDDDdd

0 ~ 25525515

I1n

SSEE

0 ~ 3031

SS: slot, EE: sub element

O0n

SSEE

0 ~ 3031

SS: slot, EE: sub element

T4SV

DDD

0 ~ 255

Timer Preset Value (T4)

T4PV

DDD

0 ~ 255

Timer Accumulator Value (T4)

C5SV

DDD

0 ~ 255

Counter Preset Value (C5)

C5PV

DDD

0 ~ 255

Counter Accumulator Value (C5)

777

Integer data file bit level (N7, 10 ~


254)

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

TfnSV

FFFDDD

0 ~ 255255

TfnPV

FFFDDD

0 ~ 255255

CfnSV

FFFDDD

0 ~ 255255

CfnPV

FFFDDD

0 ~ 255255

DDD

0 ~ 255

N7

DDD

0 ~ 255

Integer data file (N7)

Nfn

FFFDDD

0 ~ 255255

Integer data file (N7, 10 ~ 254)

DW (F)

F8

DDD

0 ~ 255

Floating point data file (F8)

DW (F)

Ffn

FFFDDD

0 ~ 255255

Floating point data file (F8, 10 ~ 254)

DW

Lfn

FFFDDD

0 ~ 255255

Driver version 2.00 or later supported

STfn

DDD.DDD.DD 0 ~ 255.255.40

Wiring Diagram:
Direct connect (crossover cable):
COM

CPU

PWR

RS232 DF1
Ethernet
Crossover cable
MT8000

1761-NET-ENI

MicroLogix 1000, 1200,


1500, SLC 5/03, 5/04

HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Green

3 RX+

2 TX-

Orange

Green

6 RX-

3 RX+

White/Green

White/Orange

1 TX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Orange

2 TX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

778

PLC Connection Guide

Through a hub:
Switch Hub

MT8000

SLC 500

SLC 500

SLC 500

HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V2.00

Dec/21/2009

Add Lfn register.

V2.10

Oct/14/2012

Added register: I1n,O0n.

V2.20

Set/06/2013

Added register: STfn.

779

PLC Connection Guide

Rockwell Micro850 (Ethernet) - Free Tag Names


Supported Series: Rockwell Micro820/850 Ethernet Module.
Website: http://www.ab.com

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Rockwell Micro850 (Ethernet) - Free Tag Names

PLC I/F

Ethernet

Port no.

44818

HMI sta. no.

PLC sta. no.

Support Device Type:


Data type

EasyBuilder data format

Bool

bit

Byte

8-bit

DInt

16-bit BCD, Hex, Binary,


Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Signed

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary,


Unsigned

32-bit

String

ASCII Object

Length=word

SInt
USInt
Word
Int
UInt
DWord

780

Memo

8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit

PLC Connection Guide

How to Import Tags:


1. Click [Tag Editor].

2. Right-click [Global-Variables] and select [New data type].

3. Click [Paste].

781

PLC Connection Guide

4. Launch Connected Components Workbench software, select and copy the tags
under [Global Variables]. Note that the IO address cannot be copied and can only be
manually created.

5. Paste the copied tags and click [OK].

6. Enter [Name], click [OK], and then click [Save to default]. The tags are now
successfully created.

782

PLC Connection Guide

Building Struct:
1. After importing the tags, the data type of Struct is shown as in the following figure,
please build the corresponding tag under Struct-Defined.

2. Right click on [Struct-Definded] and then select [New data type].

3. Enter the [Data type] in the [Name] field, and then click [Add].

783

PLC Connection Guide

4. Enter the same information in the [Name] and [Data Type] fields as shown in the
original factory software, and then click [OK].

5. Upon completion click [OK] and then click [Save to default] to finish building Struct.

784

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Jun/08/2014

Driver released.

785

PLC Connection Guide

Rockwell Micro850 - Free Tag Names


Supported Series: Rockwell Micro820/850 Ethernet Module.
Website: http://www.ab.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Rockwell Micro850 - Free Tag Names

PLC I/F

RS232

Baud rate

38400

Data bits

Parity

None

Stop bits

PLC sta. no.

1200 ~ 38400
None,Even,Odd
0 ~ 254

PLC Setting:

786

Notes

PLC Connection Guide

Support Device Type:


Data type

EasyBuilder data format

Bool

bit

Byte

16-bit BCD, Hex, Binary,


Unsigned

8-bit

SInt

16-bit BCD, Hex, Binary,


Signed

8-bit

USInt

16-bit BCD, Hex, Binary,


Unsigned

8-bit

Word

16-bit BCD, Hex, Binary,


Unsigned

16-bit

Int

16-bit BCD, Hex, Binary,


Signed

16-bit

UInt

16-bit BCD, Hex, Binary,


Unsigned

16-bit

DWord

32-bit BCD, Hex, Binary,


Unsigned

32-bit

DInt

32-bit BCD, Hex, Binary,


Signed

32-bit

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary,


Unsigned

32-bit

String

ASCII Object

Length=word

787

Memo

PLC Connection Guide

How to Import Tags:


1. Click [Tag Editor].

2. Right-click [Global-Variables] and select [New data type].

3. Click [Paste].

788

PLC Connection Guide

4. Launch Connected Components Workbench software, select and copy the tags
under [Global Variables]. Note that the IO address cannot be copied and can only be
manually created.

5. Paste the copied tags and click [OK].

6. Enter [Name], click [OK], and then click [Save to default]. The tags are now
successfully created.

789

PLC Connection Guide

Building Struct:
1. After importing the tags, the data type of Struct is shown as in the following figure,
please build the corresponding tag under Struct-Defined.

2. Right click on [Struct-Definded] and then select [New data type].

3. Enter the [Data type] in the [Name] field, and then click [Add].

790

PLC Connection Guide

4. Enter the same information in the [Name] and [Data Type] fields as shown in the
original factory software, and then click [OK].

5. Upon completion click [OK] and then click [Save to default] to finish building Struct.

791

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

8 RX

7 TXD

3 TX

7 TX

4 RXD

5 GND

5 GND

2 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

7 TXD

3 TX

4 RXD

5 GND

2 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

7 TXD

3 TX

4 RXD

5 GND

2 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 8P Mini-DIN
Male

2 RX

6 RX

8 RX

7 TXD

3 TX

4 TX

7 TX

4 RXD

5 GND

5 GND

5 GND

2 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

9 RX

7 TXD

6 TX

4 RXD

5 GND

2 GND
View from the
soldering point
of a cable.

792

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Aug/29/2014

Driver released.

793

PLC Connection Guide

Rockwell PLC5
Website: http://www.ab.com
Note: Rockwell PLC5 driver uses CRC checksum.

HMI Setting:
Parameters

Recommended

Options

PLC type

Rockwell PLC5

PLC I/F

RS232

Baud rate

19200

9600, 19200

Data bits

Parity

Even

Even, Odd, None

Stop bits

HMI sta. no.

PLC sta. no.

Notes

1-31

PLC Setting:
Communication mode

DF1 Full Duplex protocol 19200, None, 8, 1 (default)

Allen-Bradley PLC-5 Family PLCs use DF1 Full Duplex protocol.


For PLC-5/10, PLC-5/15 and PLC-5/25, MT8000 should be connected to the DF1 port on
the 1785-KE module.
For PLC-5/11, PLC-5/20, PLC-5/30 and PLC-5/40, MT8000 should be connected to the
Channel 0 Port on the PLC.

Device Address:
Bit/Word Device type Format

Range

Memo

I1

DDDdd

0 ~ 25515

Input (I)

O0

DDDdd

0 ~ 25515

Output (O)

B3

DDDdd

0 ~ 99915

Bit data file (B3)

B10 ~ 13

DDDdd

0 ~ 99915

Bit data file (B10 ~ 13)

S_Bit

DDDDDDdd 0 ~ 25599915

Bfn

FFFDDDdd

0 ~ 25599915

NfnBit

FFFDDDdd

0 ~ 25599915

T4SV

DDD

0 ~ 999
794

Timer Preset Value (T4)

PLC Connection Guide

Bit/Word Device type Format

Range

Memo

T4PV

DDD

0 ~ 999

Timer Accumulator Value (T4)

C5SV

DDD

0 ~ 999

Counter Preset Value (C5)

C5PV

DDD

0 ~ 999

Counter Accumulator Value (C5)

TfnSV

FFFDDD

0 ~ 255999

TfnPV

FFFDDD

0 ~ 255999

CfnSV

FFFDDD

0 ~ 255999

CfnPV

FFFDDD

0 ~ 255999

N7

DDD

0 ~ 999

Integer data file (N7)

N10 ~ 15

DDD

0 ~ 999

Integer data file (N10 ~ 15)

Nfn

FFFDDD

0 ~ 255999

Integer data file (V2.5.0 or newer)

DDD

0 ~ 255

F8

DDD

0 ~ 999

Ffn

FFFDDD

0 ~ 255999

Floating point data file (F8)


Floating point data file
(V2.5.0 or newer)

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 25P D-Sub: PLC5 CPU CH0
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

AB CPU CH0 RS232


25P D-Sub Male

2 RX

8 RX

2 TD

3 TX

7 TX

3 RD

5 GND

5 GND

7 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232


25P D-Sub Male

2 RX

2 TD

3 TX

3 RD

5 GND

7 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232


25P D-Sub Male

2 RX

2 TD

3 TX

3 RD

5 GND

7 GND
795

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

AB CPU CH0 RS232


25P D-Sub Male

2 RX

6 RX

8 RX

2 TD

3 TX

4 TX

7 TX

3 RD

5 GND

5 GND

5 GND

7 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

AB CPU CH0 RS232


25P D-Sub Male

9 RX

2 TD

6 TX

3 RD

5 GND

7 GND

Note:
The default error checking of Rockwell PLC5 is BCC, whereas our driver is CRC.

796

PLC Connection Guide

Access [Channel Configuration] from RSLogix5, under Channel 0 tab, please select CRC
for [Error Detect].

Driver Version:
Version

Date

V1.20

Apr/17/2009

Description

797

PLC Connection Guide

RS Automation OEMAX Series


Supported Series: OEMax NX7/NX7s Controllers.
Website: http://www.oemax.co.kr

HMI Setting:
Parameters

Recommended

Options

PLC type

RS Automation OEMAX Series

PLC I/F

RS232

Baud rate

9600

9600, 19200, 38400

Data bits

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

HMI sta. no.

225

0 ~ 255

Notes

*Please correctly set


HMI station number.

Device Address:
Bit/Word

Device type

Format

Range

DDDdd

0 ~ 25515

DDDdd

0 ~ 25515

DDDDdd

0 ~ 199915

DDDdd

0 ~ 25515

Keep Contact

DDDdd

0 ~ 99115

Special Contact

TC

DDD

0 ~ 255

Timer/Counter

DDDD

0 ~ 7999

Data Register

SV

DDD

0 ~ 255

Timer/Counter Set Value

PV

DDD

0 ~ 255

Timer/Counter Preset Value

SR

DDD

0 ~ 255

Special Register

WR

DDD

0 ~ 255

WL

DDD

0 ~ 255

WM

DDDD

0 ~ 1999

WK

DDD

0 ~ 255

WF

DDD

0 ~ 991
798

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Port1 RS232 9P D-Sub


Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Port1 RS232 9P D-Sub


Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

Port1 RS232 9P D-Sub


Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Port1 RS232 9P D-Sub


Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

Port1 RS232 9P D-Sub


Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

5 GND

799

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Dec/30/2008

Driver released.

V1.20

Jun/27/2012

Support more station numbers.

800

PLC Connection Guide

RS Automation X8 Series
Supported Series: RS-X8 Series PLC
Website: http://www.rsautomation.biz/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

RS Automation X8 Series

PLC I/F

RS232/Ethernet

RS232/ Ethernet

Baud rate

115200

9600~115200

Data bits

7,8

Parity

None

None,Even,ODD

Stop bits

1,2

Port no.

50000

PLC sta. no.

0 ~ 255

PLC Setting:
Communication mode

Xnet Slave

Device Address:
Bit/Word Device type

Format

Range

Memo

Y_bit

DD.DDDdd

0 ~ 96.25515

Output

X_bit

DD.DDDdd

0 ~ 96.25515

Input

SR_bit

DDDdd

0 ~ 12715

Status

B_bit

DDDD.DDDDdd 0 ~ 1535.153515

Bit

N_bit

DDDD.DDDDdd 0 ~ 1535.153515

Integer

A_bit

DDDD.DDDDdd 0 ~ 1535.153515

ASCII

TM_Done

DDDD.DDDDdd 0 ~ 1535.153515

Timer_Done

CT_Done

DDDD.DDDDdd 0 ~ 1535.153515

Counter_Done

CR_Done

DDDD.DDDDdd 0 ~ 1535.153515

Control_Done

DD.DDD

0 ~ 96.255

Output

DD.DDD

0 ~ 96.255

Input

SR

DDD

0 ~ 127

Status

DDDD.DDDD

0 ~ 1535.1535

Bit

DDDD.DDDD

0 ~ 1535.1535

Integer

801

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo

DDDD.DDDD

0 ~ 1535.1535

ASCII

ST_Length

DDDD.DDD

0 ~ 1535.779

String_Length

ST_Data

DDDD.DDD.DD

0 ~ 1535.779.42

String_Data

CR_Length

DDDD.DDDD

0 ~ 1535.1535

Control_Length

CR_Pos

DDDD.DDDD

0 ~ 1535.1535

Control_Postion

DDDD.DDDD

0 ~ 1535.1535

Float

DDDD.DDDD

0 ~ 1535.1535

Long

TM_Preset

DDDD.DDDD

0 ~ 1535.1535

Timer_Preset

TM_Acc

DDDD.DDDD

0 ~ 1535.1535

Timer_Accumulator

CT_Preset

DDDD.DDDD

0 ~ 1535.1535

Counter_Preset

CT_Acc

DDDD.DDDD

0 ~ 1535.1535

Counter_Accumulator

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P

COM3 RS232 9P

RS232 9P D-Sub

D-Sub Female

D-Sub Female

Female

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

802

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

Etehernet cable:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Oct/3/2012

Driver released.

803

PLC Connection Guide

SAIA PCD PGU Mode


Supported Series : SAIA PCD series PGU mode.
Website :http://www.saia-burgess.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

SAIA PCD PGU Mode

PLC I/F

RS232

RS232, RS485

Baud rate

9600

9600, 19200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

PLC sta. no.

0-255

Notes
PDS driver

Device Address:
Bit/Word

Device type

Format

Range

Flag

DDDD

0 ~ 8191

Output

DDD

0 ~ 511

Input

DDD

0 ~ 511

Register

DDDD

0 ~ 4095

Counter

DDDD

0 ~ 1599

Timer

DDDD

0 ~ 1599

Reg_Float

DDDD

0 ~ 4095

Reg_Word

DDDD

0 ~ 4095

804

Memo

support single float point

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

7 RTS

6 DSR
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

7 RTS

6 DSR
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

7 RTS

6 DSR
7 RTS
8 CTS

6 DSR (Of PGU Port): PGU connected.

Driver Version:
Version

Date

V1.02

Dec/30/2008

Description

805

short

PLC Connection Guide

SAIA PCD S-BUS Mode


Supported Series: SAIA PCD series S-Bus mode.
Website: http://www.saia-burgess.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

SAIA PCD S-BUS Mode

PLC I/F

RS232

RS232, RS485

Baud rate

9600

9600, 19200, 38400

Data bits

7,8

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

0-255

Notes
PDS driver

PLC Setting:
Communication mode

9600,N,8,1 (default)

RS232

Port 0-Type: RS232

RS485 2W

S-BUS Mode: Data(S2), Port 1-Type: RS485

1.

Open Saia Project Manager SP2.0.150 and create a new project.

806

PLC Connection Guide

2.

Give a project name.

3.

Create a new project as below.

4.

Go to Online Setting.

807

PLC Connection Guide

5.

Select PGU.

6.

Go to Device Configurator.

808

PLC Connection Guide

7.

Click Change Device Type to select your PLC model.

8.

Select RS232 (PGU) in Type and then right click mouse on Onboard
Communications and select Properties.

809

PLC Connection Guide

9.

Select Yes in Series S-Bus Port: Enabled.

10. Set parameters in S-Bus Mode and Timing then upload to PLC.

810

PLC Connection Guide

11. Go to Online Settings >> Open to select S-Bus for finishing the PLC settings.

Device Address:
Bit/Word Device type

Format

Range

Flag

DDDD

0 ~ 8191

Output

DDDD

0 ~ 1023

Input

DDDD

0 ~ 1023

Reg_Bit

DDDDdd

0 ~ 1638331

DW

Register

DDDDD

0 ~ 16383

DW

Counter

DDDD

0 ~ 1599

DW

Timer

DDDD

0 ~ 1599

DW

Reg_Float

DDDDD

0 ~ 16383

DW

DBn

DDDDDDDDD 0 ~ 536016383
811

Memo

dd: Bit no. (00~31)

support single float point

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
SAIA PCD PGU Port
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

812

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

The following is the view from the soldering point of a cable.


SAIA PCD1 Port #1 (Port #0) Terminal
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

SAIA PCD1 Port #1


(Port #0) Terminal

1 RX-

6 Data-

11 (29)

2 RX+

9 Data+

12 (28)

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

SAIA PCD1 Port #1


(Port #0) Terminal

7 RX-

4 Data-

11 (29)

6 RX+

1 Data+

12 (28)

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

SAIA PCD1 Port #1


(Port #0) Terminal

1 RX-

7 Data-

11 (29)

2 RX+

8 Data+

12 (28)

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

SAIA PCD1 Port #1


(Port #0) Terminal

1 RX-

6 Data-

11 (29)

2 RX+

9 Data+

12 (28)

5 GND

5 GND
813

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

SAIA PCD1 Port #1


(Port #0) Terminal

1 RX-

6 Data-

11 (29)

2 RX+

9 Data+

12 (28)

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

SAIA PCD1 Port #1


(Port #0) Terminal

1 RX-

7 Data-

11 (29)

2 RX+

8 Data+

12 (28)

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.40

Jun/21/2012

DBn address types are added.

814

PLC Connection Guide

SAIA S-BUS (Ethernet)


Supported Series : SAIA PCD series Ethernet-TCP/IP.
Website : http://www.saia-burgess.com/

HMI Setting:
Parameters

Recommended Options

PLC type

SAIA S-BUS (Ethernet)

PLC I/F

Ethernet

Port no.

5050

PLC sta. no.

Notes

PLC Setting:

815

PLC Connection Guide

Device Address:
Bit/Word Device type

Format

Range

Flag

DDDD

0 ~ 8191

Output

DDDD

0 ~ 1023

Input

DDDD

0 ~ 1023

Reg_Bit

DDDDdd

0 ~ 1638331

DBn_Bit

DDDDDDDdd

0 ~ 399938331

DW

Register

DDDDD

0 ~ 16383

DW

Counter

DDDD

0 ~ 1599

DW

Timer

DDDD

0 ~ 1599

DW

Reg_Float

DDDDD

0 ~ 16383

DW

DBn

DDDDDDDDD 0 ~ 536016383

DW

DB_String

DDDDDDDDD 0 ~ 536016383

DW

R_String

DDDDD

DW

DB_Float

DDDDDDDDD 0 ~ 536016383

0 ~ 16383

816

Memo

dd: Bit no. (00 ~ 31)

support single float point

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.40

Jun/21/2012

DBn address types are added.

V1.50

Sep/24/2012

R_String , DB_Float , DBn_Bit and DB_String address types


are added.

817

PLC Connection Guide

Samsung SPC-10
Supported Series: Samsung SPC-10
Website: http://www.samsungelectronics.com/factory_automation/controller/plc/

HMI Setting:
Parameters

Recommended

PLC type

Samsung SPC-10

PLC I/F

RS485 2W

Baud rate

9600

Data bits

None

Parity

Stop bits

PLC sta. no.

192

Options

Notes

Device Address:
Bit/Word Device type

Format

Range

DDDDdd

0 ~ 999915

DDDDdd

0 ~ 999915

DDDDdd

0 ~ 999915

DDDDdd

0 ~ 999915

DDDD

0 ~ 9999

818

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

6 TR-

2 RX+

9 Data+

7 TR+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P Mini-DIN
Male

7 RX-

4 Data-

6 TR-

6 RX+

1 Data+

7 TR+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

7 Data-

6 TR-

2 RX+

8 Data+

7 TR+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

6 TR-

2 RX+

9 Data+

7 TR+

5 GND

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

6 TR-

2 RX+

9 Data+

7 TR+

5 GND

5 GND

5 GND

819

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P Mini-DIN
Male

1 RX-

7 Data-

6 TR-

2 RX+

8 Data+

7 TR+

5 GND

5 GND

5 GND
View from the
soldering point
of a cable.

Driver Version:
Version

Date

V1.00

May/19/2009

Description

820

PLC Connection Guide

SCENE6 Controller
HMI Setting:
Parameters

Recommended

PLC type

SCENE6 Controller

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

Device Address:
Bit/Word

Device type

Format

Range

Word

DD

0 ~ 99

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 Terminal

2 RX

8 RX

TD

3 TX

7 TX

RD

5 GND

5 GND

GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 Terminal

2 RX

TD

3 TX

RD

5 GND

GND

821

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 Terminal

2 RX

TD

3 TX

RD

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 Terminal

2 RX

6 RX

8 RX

TD

3 TX

4 TX

7 TX

RD

5 GND

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 Terminal

9 RX

TD

6 TX

RD

5 GND

GND

Driver Version:
Version

Date

V1.00

Aug/24/2009

Description

822

PLC Connection Guide

Schleicher XCS 20C


Supported Series: Schleicher XCx-Systems Ethernet port. Schleicher XCS series, 20C
model.
Website: http://www.schleicher-electronic.com

HMI Setting:
Parameters

Recommended

PLC type

Schleicher XCS 20C

PLC I/F

RS232

Baud rate

38400

Data bits

Parity

Stop bits

PLC sta. no.

Options

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

IX

DDDDDo

0 ~ 655357

Input %IX

QX

DDDDDo

0 ~ 655357

Output %QX

MX

DDDDDo

0 ~ 655357

%MX

IW

DDDDD

0 ~ 65535

%IW

QW

DDDDD

0 ~ 65535

%QW

MW

DDDDD

0 ~ 65535

%MW

DW

ID

DDDDD

0 ~ 65535

%ID

DW

QD

DDDDD

0 ~ 65535

%QD

DW

MD

DDDDD

0 ~ 65535

%WD

Word address must be even.

823

PLC Connection Guide

Wiring Diagram:

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Schleicher XCS20
RS232 9P D-Sub Male

2 RX

8 RX

3 TD

3 TX

7 TX

2 RD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Schleicher XCS20
RS232 9P D-Sub Male

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

Schleicher XCS20

D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TD

3 TX

2 RD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Schleicher XCS20
RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TD

3 TX

4 TX

7 TX

2 RD

5 GND

5 GND

5 GND

5 GND

824

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

Schleicher XCS20
RS232 9P D-Sub Male

9 RX

3 TD

6 TX

2 RD

5 GND

5 GND

Driver Version:
Version

Date

V1.10

Feb/26/2010

Description

825

PLC Connection Guide

Schleicher XCX 300


Website: http://www.schleicher-electronic.com

HMI Setting:
Parameters

Recommended

PLC type

Schleicher XCX 300

PLC I/F

Ethernet

Port no.

20547

PLC sta. no.

Options

Notes

RS232, RS422, Ethernet

PLC Setting:
A variable must be created for HMI access.

Device Address:
Bit/Word

Device type

Format

Range

Memo

IX

DDDDDo

0 ~ 655357

Input %IX

QX

DDDDDo

0 ~ 655357

Output %QX

MX

DDDDDo

0 ~ 655357

%MX

IW

DDDDD

0 ~ 65535

%IW

QW

DDDDD

0 ~ 65535

%QW

MW

DDDDD

0 ~ 65535

%MW

DW

ID

DDDDD

0 ~ 65535

%ID

DW

QD

DDDDD

0 ~ 65535

%QD

DW

MD

DDDDD

0 ~ 65535

%WD

Word address must be even.


826

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

The following is the view from the soldering point of a cable.


Schleicher XCX300 RS232 Port
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

827

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub
Female

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

The following is the view from the soldering point of a cable.


Schleicher XCX300 RS485 4W Terminal
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W Terminal

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W Terminal

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND

828

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W Terminal

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W Terminal

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

RS485 4W Terminal

9P D-Sub Female
1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

Driver Version:
Version

Date

Description

V1.00

Nov/30/2009

Driver released.

V1.10

Jun/28/2010

Support RS232, RS422 interface connection.

829

PLC Connection Guide

Schneider IMS SERVO


Supported Series : Schneider IMS SERVO
Website: http://www.schneider-electric.com/site/home/index.cfm/ww/

HMI Setting:
Parameters

Recommended

Options

PLC type

Schneider IMS SERVO

PLC I/F

RS232

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word Device type

Format

Range

BIT

HHHHo

0 ~ FFFF7

WORD

HHHH

0 ~ FFFF

DW

DWORD

HHHH

0 ~ FFFF

Byte

BYTE

HHHH

0 ~ FFFF

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

830

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Female

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Female

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

Driver Version:
Version

Date

V1.10

Apr/04/2012

Description

831

PLC Connection Guide

Schneider MODBUS RTU


Supported Series : Schneider MODBUS RTU CONTROLLER
Website: http://www.schneider-electric.com/site/home/index.cfm/ww/

HMI Setting:
Parameters

Recommended

PLC type

Schneider MODBUS RTU

PLC I/F

RS485

RS232/RS485

Baud rate

9600

9600~115200

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1,2

PLC sta. no.

0-255

Online simulator

Options

YES

Notes

Broadcast command YES

Extend address mode YES

PLC Setting:
Communication mode

Modbus RTU protocol

Device Address:
Bit/Word Device type

Format

Range

Memo

%M

DDDDD

0 ~ 65535

Output bit

1x

DDDDD

0 ~ 65535

Input bit (read only)

3x_Bit

DDDDDdd

0 ~ 6553515

Input Register bit (read only)

B
B

4x_Bit
DDDDDdd
0x_multi_coils DDDDD

0 ~ 6553515
0 ~ 65535

Output Register bit


Write multiple coils

3x

DDDDD

0 ~ 65535

Input Register (read only)

%MW

DDDDD

0 ~ 65535

Output Register

DW

5x

DDDDD

0 ~ 65535

4x double word swap

6x

DDDDD

0 ~ 65535

4x single word write

832

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub
Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

RS232 9P D-Sub

D-Sub Female

Female

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Female

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Female

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

833

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 8P Mini-DIN : RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

2 B-

2 RX+

9 Data+

1 A+

5 GND

5 GND

5 DTP
7 GND

short

cMT/mTV series
COM2 RS485 2W COM3 RS485 2W
9P D-Sub Female 9P D-Sub Female

RS485 2W 8P Mini-DIN
Male

7 RX-

4 Data-

2 B-

6 RX+

1 Data+

1 A+

5 GND

5 GND

5 DTP
7 GND

short

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W COM3 RS485 2W

RS485 2W 8P Mini-DIN

9P D-Sub Male

9P D-Sub Male

Male

1 RX-

7 Data-

2 B-

2 RX+

8 Data+

1 A+

5 GND

9 GND

5 DTP
7 GND

short

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

2 B-

2 RX+

9 Data+

1 A+

5 GND

5 GND

5 DTP
7 GND

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

2 B-

2 RX+

9 Data+

1 A+

5 GND

5 GND

5 DTP
7 GND

834

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P Mini-DIN
Male

1 RX-

7 Data-

2 B-

2 RX+

8 Data+

1 A+

5 GND

5 GND

5 DTP
7 GND

short
View from the
soldering point
of a cable.

The following is the view from the soldering point of a cable.


9P D-Sub to Terminal : RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 3P Terminal

1 RX-

6 Data-

B-

2 RX+

9 Data+

A+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 3P Terminal

7 RX-

4 Data-

B-

6 RX+

1 Data+

A+

5 GND

5 GND

GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male

RS485 2W 3P Terminal

1 RX-

7 Data-

B-

2 RX+

8 Data+

A+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male

RS485 2W 3P Terminal

1 RX-

6 Data-

B-

2 RX+

9 Data+

A+

5 GND

5 GND

GND

835

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 3P Terminal

1 RX-

6 Data-

B-

2 RX+

9 Data+

A+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 3P Terminal

1 RX-

7 Data-

B-

2 RX+

8 Data+

A+

5 GND

5 GND

GND

Driver Version:
Version

Date

V1.30

Aug/26/2009

Description

836

PLC Connection Guide

Schneider MODBUS TCP/IP


Supported Series : Schneider Modbus RTU TCP/IP Device.
Website: http://www.schneider-electric.com/site/home/index.cfm/ww/

HMI Setting:
Parameters

Recommended

Options

PLC type

Schneider MODBUS TCP/IP

PLC I/F

Ethernet

Port no.

502

PLC sta. no.

Notes

0~255

PLC Setting:
Ethernet frame format

Ethernet II format

Device Address:
Bit/Word Device type

Format

Range

Memo

%M

DDDDD

0 ~ 65535

Input bit

1x

DDDDD

0 ~ 65535

Output bit

3x_Bit

DDDDDdd

0 ~ 6553515

Input Register bit (read only)

4x_Bit

DDDDDdd

0 ~ 6553515

Output Register bit

6x_Bit

DDDDDdd

0 ~ 6553515

Output Register bit

0x_multi_coils DDDDD

0 ~ 65535

Write multiple coils

3x

DDDDD

0 ~ 65535

Input Register

%MW

DDDDD

0 ~ 65535

Output Register

DW

5x

DDDDD

0 ~ 65535

4x double word swap

6x

DDDDD

0 ~ 65535

4x single word write

837

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

V1.40

Aug/27/2009

Description

838

PLC Connection Guide

Schneider SoMachine M Series (Ethernet)


Supported series: Schneider SoMachine M238/M241/M251

HMI Setting:
Parameters

Recommended Options

PLC type

Schneider SoMachine M Series

PLC I/F

(Ethernet)
Ethernet

Port no.

1740

Source port no.

1742

Notes
Use UDP

How to Import Tags:


8. In System Parameter Settings click [New] to add Schneider SoMachine M Series
driver into the device list and then click [Import Tag].

9. In Tag Manager click Get tag -> Import Tag, and then select the tag file (.xml)
generated by the PLC software.

839

PLC Connection Guide

10. When the tags are imported successfully, click [Exit] to leave.

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Mar/15/2016

Driver released

840

PLC Connection Guide

Schneider UniTelway
Supported Series: Modicon TSX Micro&Nano&Neza series PLC.
Website: http://www.modicon.com

HMI Setting:
Parameters

Recommended

PLC type

Schneider UniTelway

PLC I/F

RS485 2W

RS232/RS485

Baud rate

19200

9600~115200

Data bits

7,8

Parity

Odd

Even, Odd, None

Stop bits

1, 2

HMI sta. no.

1-8

PLC sta. no.

0-3

Online simulator

Options

YES

Notes

Must set to 8 for this protocol

Extend address mode YES

Broadcast command NO

PLC Setting:
Communication mode

UniTelWay protocol, set PLC as master

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDD

0 ~ 32767

Internal relay

DDDDD

0 ~ 32767

Auxiliary relay

MW.B

DDDDDdd

0 ~ 3276715 Data register bit

MW

DDDDD

0 ~ 32767

841

Data register

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
TSX37-XX/TSX07-XX CPU : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

7 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P Mini-DIN
Male

7 RX-

4 Data-

2 D-

6 RX+

1 Data+

1 D+

5 GND

5 GND

7 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W

COM3 RS485 2W

RS485 2W 8P Mini-DIN

9P D-Sub Male

9P D-Sub Male

Male

1 RX-

7 Data-

2 D-

2 RX+

8 Data+

1 D+

5 GND

9 GND

7 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P Mini-DIN
Male

1 RX-

6 Data-

2 D-

2 RX+

9 Data+

1 D+

5 GND

5 GND

7 GND

842

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P Mini-DIN
Male

1 RX-

7 Data-

2 D-

2 RX+

8 Data+

1 D+

5 GND

5 GND

7 GND
View from the
soldering point
of a cable.

Driver Version:
Version

Date

V1.30

Sep/24/2009

Description

843

PLC Connection Guide

SERVO BLDC (400/750WD)


Supported Series: BLDC(400/750WD)
Website: http://www.servoind.net/

HMI Setting:
Parameters

Recommended

Options

PLC type

SERVO BLDC (400/750WD)

PLC I/F

RS232

Baud rate

19200

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word Device type

Format

Range

SET_SERVO

SET_DIRECTION

SET_BERAK

RESET

DRIVER_FAULT

SERVO_OFF_ERROR D

BREAK_ON_ERROR

SET_RPM

RPM

CUR_RPM

CUR_ERROR

PARAMETER1_W

0~7

PARAMETER1_R

0~7

844

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

CN3 RS232 9P D-Sub


Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

CN3 RS232 9P D-Sub


Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

CN3 RS232 9P D-Sub


Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

CN3 RS232 9P D-Sub


Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

CN3 RS232 9P D-Sub


Male

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND

845

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Jul/09/2014

Driver released.

846

PLC Connection Guide

SEUNGIL AHU
Supported Series: SENUGIL AVDP-NH-K1
Website : http://seungil.en.ec21.com/

HMI Setting:
Parameters

Recommended

PLC type

SEUNGIL AHU

PLC I/F

RS-485 2W

RS232, RS485 2W/4W

Baud rate

9600

9600 ~ 115200

Data bits

7,8

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

0 ~ 99

Online simulator

Options

YES

Notes

Extend address mode NO

Device Address:
Bit/Word

Device type

Format

Range

BIT

DDD.DDD.DDDdd

0 ~ 255.255.25515

WORD

DDD.DDD.DDD

0 ~ 255.255.255

847

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 Data-

6 Data-

8 Data-

2 Data+

9 Data+

1 Data+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W Terminal

1 Data-

6 Data-

8 Data-

2 Data+

9 Data+

1 Data+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 Data-

6 Data-

8 Data-

2 Data+

9 Data+

1 Data+

5 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 Data-

6 Data-

8 Data-

2 Data+

9 Data+

1 Data+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 Data-

6 Data-

8 Data-

2 Data+

9 Data+

1 Data+

5 GND

5 GND

848

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W Terminal

1 Data-

6 Data-

Data-

2 Data+

9 Data+

Data+

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

May/31/2016

Driver released.

849

PLC Connection Guide

SEW Movilink
Supported Series: SEW Eurodrive series, model MOVITRAC-07 inverter, MovitracB.
Website: http://sg.sew-eurodrive.com/

HMI Setting:
Parameters

Recommended

PLC type

SEW Movilink

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Options

Notes

0~255

Device Address:
Bit/Word

Device type

Format

Range

INDEX_Bit

DDDDDDDDdd

0 ~ 2552500031

INDEX

DDDDDDDD

0 ~ 25525000

Memo

The MOVITRAC-07 doesnt support Sub indexother series may support, please input 000.
When input D and d, the correct formatSub index 15, Index 8359, Format is 01508359.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Movitrac-07 RS485 2W

1 RX-

6 Data-

D- (Green)

2 RX+

9 Data+

D+ (Red)

5 GND

5 GND

850

PLC Connection Guide

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

Movitrac-07 RS485 2W

7 RX-

4 Data-

D- (Green)

6 RX+

1 Data+

D+ (Red)

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Movitrac-07 RS485 2W

1 RX-

7 Data-

D- (Green)

2 RX+

8 Data+

D+ (Red)

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Movitrac-07 RS485 2W

1 RX-

6 Data-

D- (Green)

2 RX+

9 Data+

D+ (Red)

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

Movitrac-07 RS485 2W

1 RX-

6 Data-

D- (Green)

2 RX+

9 Data+

D+ (Red)

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W

COM3 RS485 2W

Movitrac-07 RS485 2W

9P D-Sub Female

9P D-Sub Female

1 RX-

7 Data-

D- (Green)

2 RX+

8 Data+

D+ (Red)

5 GND

5 GND

Driver Version:
Version

Date

V1.31

Jun/25/2010

Description

851

PLC Connection Guide

SEW MOVITRAC LTE


Website : http://www.seweurodrive.com/index.php

HMI Setting:
Parameters

Recommended

PLC type

SEW MOVITRAC LTE

PLC I/F

RS-485 2W

Baud rate

115200

Data bits

Parity

None

Stop bits

PLC sta. no.

Online simulator

YES

Options

Notes

Extend address mode NO

Device Address:
Bit/Word

Device type

Format

Range

Memo

P-1

0~1

Max. speed limit

P-2

0~1

Min. speed limit

P-3

0~1

Acceleration ramp time

P-4

0~1

Deceleration ramp time

P-5

0~1

Stop mode select

P-6

0~1

Energy optimizer

P-7

0~1

Motor rated voltage

P-8

0~1

Motor rated current

P-9

0~1

Motor rated frequency

P-10

0~1

Motor rated speed

P-11

0~1

Voltage boost

P-12

0~1

Terminal / Keypad control

P-13

0~1

Trip log

P-14

0~1

Extended menu access code

P-15

0~1

Digital input function set

P-16

0~1

Analog input V / mA

P-17

0~1

Output switching frequency

852

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

P-18

0~1

User relay output select

P-19

0~1

User relay output limit

P-20

0~1

Preset speed 1

P-21

0~1

Preset speed 2

P-22

0~1

Preset speed 3

P-23

0~1

Preset speed 4

P-24

0~1

Deceleration ramp time 2

P-25

0~1

Analog output function select

P-26

0~1

Skip frequency hysteris band

P-27

0~1

Skip frequency

P-28

0~1

V/F characteristic adjustment voltage

P-29

0~1

V/F characteristic adjustment frequency

P-30

0~1

Terminal mode restart function

P-31

0~1

Keypad mode restart function

P-32

0~1

DC injection enable / duration

P-33

0~1

Spin start

P-34

0~1

Brake chopper enable

P-35

0~1

Analog input scaling factor

P-36

0~1

P-37

0~1

Access code definition

P-38

0~1

Parameter access lock

P-39

0~1

Analog input off-set

P-40

0~1

Display speed scaling factor

P-00-01

0~1

Analog input 1 value

P-00-02

0~1

Analog input 2 value

P-00-03

0~1

Speed reference input

P-00-04

0~1

Digital input status

P-00-05

0~1

Reserved

P-00-06

0~1

Reserved

P-00-07

0~1

Applied motor voltage

P-00-08

0~1

DC bus voltage log

P-00-09

0~1

Heatsink temperature

P-00-10

0~1

Hours run meter

P-00-11

0~1

Run time since last trip (1)

P-00-12

0~1

Run time since last trip (2)

P-00-13

0~1

Run time since last disable

853

Comms address; SBus enable/baudrate


select; Trip enable / delay

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

P-00-14

0~1

Reserved

P-00-15

0~1

DC bus voltage log

P-00-16

0~1

Thermistor temperature log

P-00-17

0~1

Motor current

P-00-18

0~1

Software ID,IO and motor control

P-00-19

0~1

Drive serial number

P-00-20

0~1

Drive identifier

P-00-01 ~ P-00-20 read only.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W 8P
RJ45 Male

1 RX-

6 Data-

4-

2 RX+

9 Data+

5+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

PLC RS485 2W 8P
RJ45 Male

7 RX-

4 Data-

4-

6 RX+

1 Data+

5+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W 8P
RJ45 Male

1 RX-

7 Data-

4-

2 RX+

8 Data+

5+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W 8P
RJ45 Male

1 RX-

6 Data-

4-

2 RX+

9 Data+

5+

5 GND

5 GND

854

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

PLC RS485 2W 8P
RJ45 Male

1 RX-

6 Data-

4-

2 RX+

9 Data+

5+

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

PLC RS485 2W 8P
RJ45 Male

1 RX-

7 Data-

4-

2 RX+

8 Data+

5+

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

May/19/2011

Driver released.

855

PLC Connection Guide

SHIMADEN MR13/FP93
Supported Series: MR13, FP93 devices
Website: http://www.shimaden.co.jp

HMI Setting:
Parameters

Recommended

Options

PLC type

SHIMADEN MR13/FP93

PLC I/F

RS485

Baud rate

9600

1200-19200

Data bits

7 or 8

Parity

None/Even

Stop bits

PLC sta. no.

1~255

Notes

0, 1 : STX_ETX_CR
Start Character Mode

BCC Operation Method

Select 3@_:_CR

Select 3XOR

2 : STX_ETX_CR LF
3 : @_:_CR

For FP93, select 0,1

0, 1 : Addition
2 : Addition +2s
complement
3 : XOR
4 : None

Note
Address 018C is a communication control register, only when it is set to 1 can this register
be allowed to write to other registers.

856

PLC Connection Guide

Device Address:
Bit/Word Device type Format

Range

Memo

Channel 1

HHHH

0 ~ ffff

Read/Write 1st Channel Register

Channel 2

HHHH

0 ~ ffff

Read/Write 2nd Channel Register

Channel 3

HHHH

0 ~ ffff

Read/Write 3rd Channel Register

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

MR13/FP93 RS485 2W
Terminal

1 RX-

6 Data-

25

2 RX+

9 Data+

24

5 GND

5 GND

23 GND

COM2 RS485 2W

COM3 RS485 2W

MR13/FP93 RS485 2W

9P D-Sub Female

9P D-Sub Female

Terminal

7 RX-

4 Data-

25

6 RX+

1 Data+

24

5 GND

5 GND

23 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

MR13/FP93 RS485 2W
Terminal

1 RX-

7 Data-

25

2 RX+

8 Data+

24

5 GND

9 GND

23 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

MR13/FP93 RS485 2W
Terminal

1 RX-

6 Data-

25

2 RX+

9 Data+

24

5 GND

5 GND

23 GND

857

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

MR13/FP93 RS485 2W
Terminal

1 RX-

6 Data-

25

2 RX+

9 Data+

24

5 GND

5 GND

23 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

MR13/FP93 RS485 2W
Terminal

1 RX-

7 Data-

25

2 RX+

8 Data+

24

5 GND

5 GND

23 GND

MR13 Communication Parameter Settings


Data Address

Parameter

Details of Parameter

R /W

0100

PV Value

Within measuring range

0101

E_SV Execution
SV Value

Within setting range

0102

OUT Control
Output Value

Within range 0.0100.0%

0103

Reserved

0104

Action Flag

See detailed explanation below.

0105

Event Output Flag

See detailed explanation below.

0106

Reserved

0107

Reserved

0108

REM Value

Within setting range

0109

Reserved

010A

Reserved

010B

DI

(hex)

Data Address

Input State Flag See detailed explanation below.

Parameter

Details of Parameter

R /W

0111

RANGE

Refer to the measuring range code list.

0112

Reserved

(hex)

858

PLC Connection Guide

DP

Position of decimal point 0:Without

Decimal Point

decimal point 1:With decimal point

PV Sc_L

Lower Limit

For Linear Imput:-19999999 unit

Higher Limit

For Thermocouple, and RTD Input:


Measuring range to be displayed.

Parameter

Details of Parameter

R/W

0120

E_PRG

Program Action Flag

0121

Reserved

0122

Reserved
E_PRT

The number of execution patterns


When program is reset,
value=7FFEH

E_STP

Execution step number


When program is reset,
value=7FFEH

E_TIM

Remaining time of execution step


When program is reset,
value=7FFEH

E_PID

Execution PID number


When program is reset,
value=7FFEH

Parameter

Details of Parameter

R/W

0184

AT

0:No execution

018C

Operation

0:Local

0190

PROG RUN/RST
Program Run/Reset

0RST, 1RUN
Writing is possible only in CH1

0113
0114
0115

Data Address
(hex)

0123

0124

0125

0126

Data Address
(hex)

PV Sc_H

Auto Tuning

859

1:Execution

1:COM

W
W

PLC Connection Guide

0191

0300
Data
Address

PROG HLD
Program Hold

0Release, 1HLD
Writing is possible only in CH1

SV

Local SV Value, within set value limiter

R/W

Parameter

Details of Parameter

R/W

(hex)
030A

SV Limt_L

Lower Limit

Within measuring range,

030B

SV Limt_h

Higher Limit

On condition that SV Limt_L<SV


Limt_H

0314

REM SC_L

Within measuring range


R/W
On condition that REM SC_L REM

0315

REM SC_H

SC_H

0316

REM Bias

Range: -19995000 unit

R/W

0317

REM Filt

Range: 0100 seconds

R/W

031A

REM-CH

Remote channel assignment


0OFF1CH12CH23CH3

Parameter

Details of Parameter

0320

SV Follow SW

CH2 & CH3 SV follow setting flag 1:


R/W
Follow 0:No

0321

SV Follow

Follow type deviation SV set value:


19995000 unit

0400

FIX P

Control Output Proportional Baud


Range: 0.0999.9%(0.0:OFF)

R/W

0401

FIX I

Control Output Integral Time


Range: 06000 Seconds (0.0:OFF)

R/W

0402

FIX D

Control Output Derivative Time


Range 03600 Seconds (0.0:OFF)

R/W

Data Address

(hex)

860

R/W

R/W

R/W

R/W

PLC Connection Guide

0403

FIX MR

Manual Reset Range: -50.050.0%

R/W

0404

FIX DF

Hysteresis Range: 1999 unit

R/W

0405

FIX OUT Limt_L

Control Output Lower Limit Output


Limiter Range: 0.099.9%

R/W

0406

FIX OUT Limt_H

Control Output Higher Limit Output


Limiter Range: 0.1100.0%

R/W

0407

FIX SF

Control Output Target Value Function


Range: OFF0.011.00

R/W

0408

Prog P1

PROG mode PB1


Range: 0.0999.9% (0.0:OFF)

R/W

0409

Prog I1

PROG mode IT1


Range: 06000 seconds

R/W

040A

Prog D1

040B

Prog MR1

040C

Prog DF1

040D

Prog O_Lmt_L1

PROG mode DT1


Range: 03600 seconds

(0.0:OFF)
R/W
(0.0:OFF)

PROG mode MR1


Range: -50.050.0%

R/W

PROG mode DF1


Range: 1999 unit

R/W

PROG mode lower limit side output


R/W
limiter 1 Range: 0.099.9%
PROG mode higher limit side output limiter 1

040E

Prog O_Lmt_H1

040F

Prog SF1

PROG mode target value function 1


Range: OFF,0.011.00

R/W

0410

Prog P2

PROG mode PB2


Range: 0.0999.9% (0.0:OFF)

R/W

0411

Prog I2

PROG mode IT2


Range: 06000 seconds

(0.0:OFF)

R/W

0412

Prog D2

PROG mode DT2


Range: 03600 seconds

(0.0:OFF)

0413

Prog MR2

PROG mode MR2


Range: -50.050.0%

R/W

0414

Prog DF2

PROG mode DF2


Range: 1999 unit

R/W

0415

Prog O_Lmt_L2

PROG mode lower limit side output


R/W
limiter 2 Range: 0.099.9%

0416

Prog O_Lmt_H2

Range: 0.1100.0%

PROG mode higher limit side output limiter 2

Range: 0.1100.0%
861

R/W

R/W

R/W

PLC Connection Guide

0417

Prog SF2

PROG mode target value function 2


Range: OFF,0.011.00

R/W

0418

Prog P3

PROG mode PB3


Range: 0.0999.9% (0.0:OFF)

R/W

PROG mode IT3


Range: 06000 seconds

(0.0:OFF)

R/W

PROG mode DT3


Range: 03600 seconds

(0.0:OFF)

0419
041A
041B
041C
041D
041E
041F

Prog I3

Prog D3
Prog MR3

Prog DF3

R/W

PROG mode MR3


Range: -50.050.0%

R/W

PROG mode DF3


Range: 1999 unit

R/W

Prog O_Lmt_L3

PROG mode lower limit side output


R/W
limiter 3 Range: 0.099.9%

Prog O_Lmt_H3

PROG mode higher limit side output limiter 3

Range: 0.1100.0%
Prog SF3

PROG mode target value function 3


Range: OFF,0.011.00

R/W
R/W

0:Not assigned 1:Higher limit deviation value


2:Lower limit deviation value
3:Out of range between higher & lower limits
4:Within range between higher & lower limits

0500

EV1_MODE

5:Higher limit absolute value


6:Lower limit absolute value
7:Scaleover
8:Program RUN
9:Program END
10:Program STEP
Only when Subaddress=EV1_CH.

862

R/W

PLC Connection Guide


1. Higher limit deviation value alarm: 01999 unit
2. Lower limit deviation value alarm: 0-1999 unit
3. Out of range between higher & lower limits value
alarm: 01999 unit

0501

EV1 Set Point

4. Within range between higher and lower limits

R/W

value alarm: 01999 unit


5. Higher

limit

absolute

value

alarm:

Within

value

alarm:

Within

measuring range
6. Lower

limit

absolute

measuring range
Only when Subaddress=EV1_CH.

0502

EV1 Diffrnt

0503

EV1 Inhibit

0504

EV1 Delay

0506

EV1_CH

Alarm hysteresis 1999 unit


Only when Subaddress=EV1_CH.
Alarm stand by 14
Only when Subaddress=EV1_CH.
Alarm delay time 09999 seconds
Only when Subaddress=EV1_CH.
Channel number setting
1:CH1, 2:CH2, 3:CH3

R/W
R/W
R/W

R/W

0:Not assigned 1:Higher limit deviation value


2:Lower limit deviation value
3:Out of range between higher & lower limits
4:Within range between higher & lower limits
5:Higher limit absolute value

0510

EV2_MODE

6:Lower limit absolute value


7:Scaleover
8:Program RUN
9:Program END
10:Program STEP
Only when Subaddress=EV2_CH.

863

R/W

PLC Connection Guide


1. Higher limit deviation value alarm: 01999 unit
2. Lower limit deviation value alarm: 0-1999 unit
3. Out of range between higher & lower limits value
alarm: 01999 unit
4. Within range between higher and lower limits

0511

EV2 Set Point

R/W

value alarm: 01999 unit


5. Higher

limit

absolute

value

alarm:

Within

value

alarm:

Within

measuring range
6. Lower

limit

absolute

measuring range
Only when Subaddress=EV2_CH.

0512

EV2 Diffrnt

0513

EV2 Inhibit

0514

EV2 Delay

0516

EV2_CH

Alarm hysteresis 1999 unit


Only when Subaddress=EV2_CH.
Alarm stand by 14
Only when Subaddress=EV2_CH.
Alarm delay time 09999 seconds
Only when Subaddress=EV2_CH.
Channel number setting
1:CH1, 2:CH2, 3:CH3

R/W
R/W
R/W

R/W

0:Not assigned 1:Higher limit deviation value


2:Lower limit deviation value
3:Out of range between higher & lower limits
4:Within range between higher & lower limits
5:Higher limit absolute value

0520

EV3_MODE

6:Lower limit absolute value


7:Scaleover
8:Program RUN
9:Program END
10:Program STEP
Only when Subaddress=EV3_CH.

864

R/W

PLC Connection Guide


1. Higher limit deviation value alarm: 01999 unit
2. Lower limit deviation value alarm: 0-1999 unit
3. Out of range between higher & lower limits value
alarm: 01999 unit
4. Within range between higher and lower limits

0521

EV3 Set Point

value alarm: 01999 unit


5. Higher

limit

absolute

value

alarm:

Within

value

alarm:

Within

R/W

measuring range
6. Lower

limit

absolute

measuring range
Only when Subaddress=EV3_CH

0522

EV3 Diffrnt

0523

EV3 Inhibit

0524

EV3 Delay

0526

EV3_CH

0580

05B0

DI

MEM

Alarm hysteresis 1999 unit


Only when Subaddress=EV3_CH.
Alarm stand by 14
Only when Subaddress=EV3_CH.
Alarm delay time 09999 seconds
Only when Subaddress=EV3_CH.
Channel number setting
1:CH1, 2:CH2, 3:CH3
DI setting flag
0:NON 1:FLW
4:ADV

2:RUN 3:HLD

R/W
R/W
R/W

R/W

R/W

1:EEP Program Memory


0:RAM Random Memory

R/W

R/W

0600

Out Actn

Output characteristic setting flag


0:Rev Act. 1:Dir Act

0601

Out Cyc

Control output cycle (Unit:0.5 seconds)


R/W
Range: 0.5120.0 seconds

0602

Reserved

0603

SOFTSW

Soft start setting flag


0:OFF 1:ON

865

PLC Connection Guide

0610

AT Point

AT pointer Range: 05000 unit

R/W

0611

Key Lock

0:OFF 1:LOCK1 2:LOCK2


3:LOCK3

R/W

When Out_Cyc is written, writing data is adjusted to 0.5 sec as one unit.
The write command lock by keylock is the same as the screen lock. (Refer to the
manual of the instrument.)
If there is a change in EV1_CH,EV2_CH,EV3_CH, the related parameters are
initialized.

0701

PV Bias

PV bias Range: -19991999 unit

R/W

0702

PV Filt

PV filter Range: 0100 seconds

R/W

0710

PFLW

Setting of CH2, CH3 PV input follow


0:OFF 1:ON

R/W

Selection of CH2, CH3 PV display or not

0711

CH_P

0: Without

0800

FP_MOD

0801

PV_ST

0882

STP

R/W

0-0 Window
1: With

Selection between FIX and PROG


0:FIX 1:PROG
(Writing possible only in CH1)
Setting of PV start

0:OFF 1:ON

(Writing possible only in CH1)


The number of steps 19
(Writing possible only in CH1)

0883

RPT

0884

ST_SV

The number of execution repetitions 19999


(Writing possible only in CH1)

Start SV
(Writing possible only in CH1)

R/W

R/W

R/W
R/W
R/W

For CH1, PFLW (window 1~30), CH_P (window1-29display- - - -.The read value is:
7FFEH, To a write command, error0BHis returned.
866

PLC Connection Guide

Step No. 1 SV Value

08A0

Step1 SV

08A1

Step1 Time

Step No. 1 Step Time


(Writing possible only in CH1)

R/W

08A2

Step1 PID No

Step No. 1 PID No.

R/W

08A3

Reserved

08A4

Step2 SV

08A5

Step2 Time

Step No. 2 Step Time


(Writing possible only in CH1)

R/W

08A6

Step2 PID No

Step No. 2 PID No.

R/W

08A7

Reserved

08A8

Step3 SV

08A9

Step3 Time

Step No. 3 Step Time


(Writing possible only in CH1)

R/W

08AA

Step3 PID No

Step No. 3 PID No.

R/W

08AB

Reserved

08AC

Step4 SV

08AD

Step4 Time

Step No. 4 Step Time


(Writing possible only in CH1)

R/W

08AE

Step4 PID No

Step No. 4 PID No.

R/W

08AF

Reserved

08B0

Step5 SV

08B1

Step5 Time

Step No. 5 Step Time


(Writing possible only in CH1)

R/W

08B2

Step5 PID No

Step No. 5 PID No.

R/W

08B3

Reserved

08B4

Step6 SV

08B5

Step6 Time

Step No. 6 Step Time


(Writing possible only in CH1)

R/W

08B6

Step6 PID No

Step No. 6 PID No.

R/W

08B7

Reserved

(Writing possible only in CH1)

Step No. 2 SV Value


(Writing possible only in CH1)

Step No. 3 SV Value


(Writing possible only in CH1)

Step No. 4 SV Value


(Writing possible only in CH1)

Step No. 5 SV Value


(Writing possible only in CH1)

Step No. 6 SV Value


(Writing possible only in CH1)

867

R/W

R/W

R/W

R/W

R/W

R/W

PLC Connection Guide

Step No. 7 SV Value

08B8

Step7 SV

08B9

Step7 Time

Step No. 7 Step Time


(Writing possible only in CH1)

R/W

08BA

Step7 PID No

Step No. 7 PID No.

R/W

08BB

Reserved

08BC

Step8 SV

08BD

Step8 Time

08BE

Step8 PID No

08BF

Reserved

08C0

Step9 SV

08C1

Step9 Time

Step No. 9 Step Time


(Writing possible only in CH1)

R/W

08C2

Step9 PID No

Step No. 9 PID No.

R/W

(Writing possible only in CH1)

Step No. 8 SV Value


(Writing possible only in CH1)
Step No. 8 Step Time
(Writing possible only in CH1)
Step No. 8 PID No.
Step No. 9 SV Value
(Writing possible only in CH1)

Driver Version:
Version

Date

V1.20

Apr/08/2011

Description

868

R/W

R/W
R/W
R/W

R/W

PLC Connection Guide

SHJ-A
HMI Setting:
Parameters

Recommended

PLC type

SHJ-A

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

Device Address:
Bit/Word Device type

Format

Range

DD

0 ~ 89

Word

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

869

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Oct/18/2011

Driver released.

870

PLC Connection Guide

SICK FLEXI SOFT


HMI Setting:
Parameters

Recommended

PLC type

SICK FLEXI SOFT

PLC I/F

RS232

Baud rate

115200

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

9600,19200,3840
0,57600,115200

Device Address:
Bit/Word
B

Device type

Format

Range

Memo

DDo

0 ~ 967

Input

DDo

0 ~ 487

Output

Logic result

DDo

0 ~ 327

Logic Result

RS-232

DDo

0 ~ 327

RS-232

Flexi soft to RS-232_Bit

DDo

0 ~ 997

Module Status Bit Array_Bit

DDo

0 ~ 597

Operating Data Block_Bit

Do

0 ~ 97

Configuration CRCs_Bit

DDo

0 ~ 197

CPU Module Type Key_Bit

DDo

0 ~ 177

B
W

Extension Modules Type_Bit

DDDo

0 ~ 3377

RS-232 to Flexi soft

0~2

Flexi soft to RS-232

DD

0 ~ 98

Module Status Bit Array

DD

0 ~ 58

Operating Data Block

0~8

Configuration CRCs

DD

0 ~ 18

CPU Module Type Key

DD

0 ~ 16

Extension Modules Type

DDD

0 ~ 336

871

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

CPU0 Port0 4P
Mini-DIN Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

4 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

CPU0 Port0 4P
Mini-DIN Male

2 RX

3 TX

3 TX

2 RX

5 GND

4 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

CPU0 Port0 4P
Mini-DIN Male

2 RX

3 TX

3 TX

2 RX

5 GND

4 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

CPU0 Port0 4P
Mini-DIN Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

4 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

CPU0 Port0 4P
Mini-DIN Male

9 RX

3 TX

6 TX

2 RX

5 GND

4 GND
View from the
soldering point
of a cable.

872

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Apr/6/2011

Driver released.

V1.10

May/15/2013

Supports importing tags of external modules and V1.4 .csv


files.

873

PLC Connection Guide

Siemens LOGO (Ethernet)


Supported Series: Siemens LOGO! 0BA7,0BA8
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

Siemens S7/200 (Ethernet)

PLC I/F

Ethernet

Port no.

102

PLC sta. no.

Local TSAP

1000

Must be greater than 1000

Remote TSAP

2100

Range:2000~2700

1~99

For TSAP settings please refer to PLC Setting below.

PLC Setting:
Siemens LOGO! multi connection setting requires LOGO! Soft Comfort software to set
PLC to identify the connected devices. The following introduces LOGO! Soft Comfort
settings.
Step 1. Tools -> Ethernet Connections

874

PLC Connection Guide

Step 2. Right click on Ethernet Connections and click Add connections to add a
connection, up to eight connections are allowed.

Step 3. Setting Server


I.
Double click on Connection1, then select Server Connection.
II.
Local TSAP is system default and cant be modified. Tick Accept all connection
requests to connect to any IP.
III. Remote TSAP set to 10.00.
IV. Connection 2~8 can all be set as above.

Note: The value of Local TSAP and Remote TSAP must be set oppositely in EasyBuilder
for communication.

875

PLC Connection Guide

Step 4. Complete settings, download connection to Siemens LOGO!

Device Address:
Bit/Word

Device type

Format

Range

Memo
Read Only

DD

1~64

DD

1~64

DD

1~112

NI

DDD

1~128

NQ

DDDDo

0~14697

AI

1~16

AQ

1~16

AM

DD

1~64

NAI

1~64

NAQ

1~32

VW

DDDD

0~1468

DW

VD

DDDD

0~1466

1~128

876

VW_Bit

See Table 1&2 Address Mapping

PLC Connection Guide

Table 1 Address Mapping (LOGO! 0BA7)


I

VW

VW

VW

AI

VW

AQ

VW

AM

VW

I1

V923.0

Q1

V942.0

M1

V948.0

AI1

VW926

AQ1

VW944

AM1

VW952

I2

V923.1

Q2

V942.1

M2

V948.1

AI2

VW928

AQ2

VW946

AM2

VW954

I3

V923.2

Q3

V942.2

M3

V948.2

AI3

VW930

AM3

VW956

I4

V923.3

Q4

V942.3

M4

V948.3

AI4

VW932

AM4

VW958

I5

V923.4

Q5

V942.4

M5

V948.4

AI5

VW934

AM5

VW960

I6

V923.5

Q6

V942.5

M6

V948.5

AI6

VW936

AM6

VW962

I7

V923.6

Q7

V942.6

M7

V948.6

AI7

VW938

AM7

VW964

I8

V923.7

Q8

V942.7

M8

V948.7

AI8

VW940

AM8

VW966

I9

V924.0

Q9

V943.0

M9

V949.0

AM9

VW968

I10

V924.1

Q10

V943.1

M10

V949.1

AM10

VW970

I11

V924.2

Q11

V943.2

M11

V949.2

AM11

VW972

I12

V924.3

Q12

V943.3

M12

V949.3

AM12

VW974

I13

V924.4

Q13

V943.4

M13

V949.4

AM13

VW976

I14

V924.5

Q14

V943.5

M14

V949.5

AM14

VW978

I15

V924.6

Q15

V943.6

M15

V949.6

AM15

VW980

I16

V924.7

Q16

V943.7

M16

V949.7

AM16

VW982

I17

V925.0

M17

V950.0

I18

V925.1

M18

V950.1

I19

V925.2

M19

V950.2

I20

V925.3

M20

V950.3

I21

V925.4

M21

V950.4

I22

V925.5

M22

V950.5

I23

V925.6

M23

V950.6

I24

V925.7

M24

V950.7

M25

V951.0

M26

V951.1

M27

V951.2

877

PLC Connection Guide

Table 2 Address Mapping (LOGO! 0BAB)


Device Type

VM (From)

VM (To)

Range

1024

1031

8 Bytes

AI

1032

1063

32 Bytes

1064

1071

8 Bytes

AQ

1072

1103

32 Bytes

1104

1117

14 Bytes

AM

1118

1245

128 Bytes

NI

1246

1261

16 Bytes

NAI

1262

1389

128 Bytes

NQ

1390

1405

16 Bytes

NAQ

1406

1469

64 Bytes

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

DEC/7/2011

Driver released.

V1.40

Mar/10/2015

Support LOGO! 0BA8

878

PLC Connection Guide

Siemens S7-1200 (symbolic addressing)


(Ethernet)
Supported Series: Siemens S7-1200 series Ethernet.
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

PLC type

Siemens S7-1200 (symbolic addressing) (Ethernet)

PLC I/F

Ethernet

Port no.

102

PLC sta. no.

Rack

CPU slot

On-line simulator

Yes

Options

Notes

Multi-HMI connect

Yes (Max:3 HMI)

*EasyBuilder8000 does note support Siemens S7-1200 firmware V4.0 and later versions.

PLC Setting:
1.
2.

In S7-1200 program software create PLC program and tag and then download to
PLC.
Select Go offline, EasyBuilder will connect to PLC and get tag data. In PLC type
select SIEMENS S7-1200 (Ethernet).

879

PLC Connection Guide

3.

Click Settings, input PLC IP address.

4.

Check the PLC that is not connected to any PC. Click Get tag info.

5.

Supported by firmware V3.X and previous versions. For V4.0 or later, please see How
to Connect With S7-1200 Firmware V4.0)

880

PLC Connection Guide

6.

If the software used is a version later than TIA Portal V11SP2, a dialog of
FunctionBlock directory will be shown, users have to define the mapping from FB to
DB in this directory then click Check OK. The tag information will be gained and
a successful message is shown.

881

PLC Connection Guide

7.

When opening an existing project and get the tag information again, if the PLC
software used is TIA Portal V12 and later versions, the DB name must be entered
again in order to compile the project.

8. Added Tag Manager that allows selecting the Siemens S7-1200 PLC tags to be
imported.

882

PLC Connection Guide

9.

Create an object and click read address Setting

10. In PLC name select S7-1200 then click Tag.

11. Select PLC tag.

883

PLC Connection Guide

How to Connect With S7-1200 Firmware V4.0


There are certain restrictions in S7-1200 firmware V4.0, therefore, to avoid communication
errors, please follow the steps to set up.( EasyBuilder8000 does not support Siemens
S7-1200 firmware V4.0 and later versions).
Right click on the PLC program, and then click [Properties].

Select [Protection], and then select [Permit access with PUT/GET communication
from remote partner (PLC,HMI,OPC,].

884

PLC Connection Guide

The following part introduces how to export S7-1200 PLC Tags and Program Blocks.
Exporting PLC Tags (I,Q,M tags)
1. Under [PLC tags] select [Show all tags].

2. Click [Export] to export the tags.

3. Browse for the directory to save the exported file and then click [OK].

885

PLC Connection Guide

Exporting Program Blocks(DB)


1. When the database contains Struct data type, please note the following restrictions.
Please at least add one data member that doesnt belong to Struct data type into DB,
otherwise, the data cannot be imported to EasyBuilder.
Multidimensional Arrays and Multilayer Structs are not supported.
After building DB, please do the following actions for Struct address:
(1) Copy the complete Struct data.
(2) Delete data.
(3) Add a new row.
(4) Paste data.

2. Right click on DB, click [Generate source from blocks], and then enter the file name
to save.

886

PLC Connection Guide

After building and importing PLC Tags and Program Blocks, click [Download to device].

Importing PLC Tags and Program Blocks(DB)


1. Launch EasyBuilder and set the IP address.

2. Click [Import Tag].

887

PLC Connection Guide

3. Select the PLC Tags and Program Blocks to be imported. Please remember to change
DB number, and select [Use S7-1200 firmware version 4.0 or later versions]. Click
[Import] to import the files. The I, Q, and M addresses will be checked, if an error
occurs, the communication will fail. If this happens, please check your communication
environment, and try to import again.

4. The Import status field will display the result, click [OK].

888

PLC Connection Guide

5. Select the tags to be imported and then click

[OK].

6. The following message is displayed when the import has succedded.

889

PLC Connection Guide

Support Device Type:


S7-1200 data type

EasyBuilder data format

Bool

bit

Byte

8-bit

DInt

16-bit BCD, Hex, Binary,


Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Signed

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary,


Unsigned
Word array for ASCII input
and ASCII display
16-bit BCD, Hex, Binary,
Unsigned

32-bit

SInt
USInt
Word
Int
UInt
DWord

Array
Char

8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit

Length=word
USInt
Struct

CREF
Date

Memo

16-bit BCD, Hex, Binary,


Unsigned

UInt

DTL

Struct

ErrorStruct

Struct

IEC_COUNTER

Struct

IEC_DCOUNTER

Struct

IEC_SCOUNTER

Struct

IEC_TIMER

Struct

IEC_UCOUNTER

Struct

890

PLC Connection Guide

S7-1200 data type

EasyBuilder data format

Memo

IEC_UDCOUNTER

Struct

IEC_USCOUNTER

Struct

NREF

Struct

Time
Time_Of_Day

32-bit BCD, Hex, Binary,


Unsigned
32-bit BCD, Hex, Binary,
Unsigned

DWord
DWord
Bool, Byte, SINT, USInt, Word,
Int, UInt, DWord, Dint, Real,
UDInt

Struct

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.70

Oct/7/2011

Add data type: Byte,SInt,UInt,UDInt

V1.90

Apr/26/2012

Add data type: USInt

V2.40

Aug/04/2014

Support firmware V4.0

V2.50

Aug/29/2014

Support cMT-SVR

891

PLC Connection Guide

Siemens S7-1200/S7-1500 (absolute addressing)


(Ethernet)
Supported Series: Siemens S7-1500/1200 series Ethernet.
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

PLC type

Siemens S7-1200/S7-1500 (absolute addressing) (Ethernet)

PLC I/F

Ethernet

Port no.

102

PLC sta. no.

Rack

CPU slot

On-line simulator

Yes

Options

Notes

Multi-HMI connect

Yes (Max:3 HMI)

Support Device Type:


S7-1200 data type

EasyBuilder data format

Bool

bit

Byte

16-bit BCD, Hex, Binary, Unsigned

8-bit

SInt

16-bit BCD, Hex, Binary, Signed

8-bit

USInt

16-bit BCD, Hex, Binary, Unsigned

8-bit

Word

16-bit BCD, Hex, Binary, Unsigned

16-bit

Int

16-bit BCD, Hex, Binary, Signed

16-bit

UInt

16-bit BCD, Hex, Binary, Unsigned

16-bit

DWord

32-bit BCD, Hex, Binary, Unsigned

32-bit

DInt

32-bit BCD, Hex, Binary, Signed

32-bit

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary, Unsigned

32-bit

Array

Word array for ASCII input and display

Length=word

String

Word array for ASCII input and display

Length=word

892

Memo

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

DBnBit

FFFFFDDDDo

0 ~ 6553599997

DB1Bit-DB99Bit DDDDDo

0 ~ 655327

Data Register Bit

IW

DDDD

0 ~ 4095

Input (I)

QW

DDDD

0 ~ 4095

Output (O)

MW

DDDD

0 ~ 4095

Bit Memory

DW

MD

DDDD

0 ~ 4094

Bit Memory Double Word

DBn

FFFFFDDDD

0 ~ 655359999

DW

DBDn

FFFFFDDDD

0 ~ 655359999

DBn_String

FFFFFDDDD

0 ~ 655359999

(must
be multiple of 4)
Char array

DBn_String1

FFFFFDDDD

0 ~ 655359999

String

DW

DBDn_String

FFFFFDDDD

0 ~ 655359999

Char array

DB1 ~ DB99

DDDDD

0 ~ 65532

Byte

MB

DDDD

0 ~ 4095

Bit Memory Byte

Byte

DBBn

FFFFFDDDD

0 ~ 655359999

Data Register Byte

DW

ID

DDDD

0 ~ 4094

Byte

IB

DDDD

0 ~ 9095

DW

QD

DDDD

0 ~ 4094

Byte

QB

DDDD

0 ~ 4095

DW

S5TIME_10Ms

FFFFFDDDD

0 ~ 655359999

DW

S5TIME_100Ms FFFFFDDDD

0 ~ 655359999

DW

S5TIME_10S

FFFFFDDDD

0 ~ 655359999

DW

S5TIME_10S

FFFFFDDDD

0 ~ 655359999

Data Register
(must be even)
Data Register Double
Word

Data Register(must be
even)

Double word and floating point value must use DBDn device type.

893

PLC Connection Guide

PLC Setting:
Note: Please follow the settings below, or the communication may fail.
1. Do not check [DB UTILITAIRES] -> [Attributes] -> [Optimized block access]

2. Check [General] -> [Protection] -> [Permit access with PUT/GET communication from
remote partner]

894

PLC Connection Guide

How to import address tags using TIA portal?


1. Exporting PLC Tags (.xlsx file format).
1.1 Under [PLC tags] create the address tags and then click the Export icon.

1.2 Designate the directory to save the file and click OK button.

895

PLC Connection Guide

2. Exporting Program Blocks (.scl file format).


2.1 Under [Program blocks] create Data_block_1 [DB1] as shown in the following figure.
Click the right mouse button on [DB1] and then click [Generate source from blocks].

2.2 Designate the directory to save the file.

896

PLC Connection Guide

3. In EasyBuilder click [New PLC], select Siemens S7-1500 (Ethernet) PLC type, and
then click [Settings] to set the parameters.

4. Click [Import Tag] button.

897

PLC Connection Guide

5. Select the PLC Tags and Program Blocks to be imported, click [Import] button, and then
click [OK] to leave when the tags are imported successfully.

6. The following message window is shown if the import has succeeded.

898

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

May/02/2014

Driver released.

899

PLC Connection Guide

Siemens S7-200
Supported Series: Siemens S7-200 series PLC
(CPU212/214/215/216/221/222/224/226/226XM)
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters
PLC type

Recommend Options
ed
SIEMENS S7-200

PLC I/F

RS485 2w

Notes

RS485 2w
The HMI which has a sticker

Baud rate

9600

9600, 19200, 187.5K

MPI187.5 on the rear cover


supports 187.5K

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

1 ~ 126

Turn around delay (ms)

Send ACK delay(ms)

30

Online simulator

YES

Extend address mode NO

Broadcast command NO

PLC Setting:
Communication mode

Set station number to 2

Device Address:
Bit/Word Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

VW_Bit

DDDDDo

0 ~ 102397

V Memory Bit Address

DDDDo

0 ~ 40957

SCR

SM

DDDDo

0 ~ 40957

Special Memory

T_Bit

DDD

0 ~ 255

Timer

900

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo

C_Bit

DDD

0 ~ 255

Counter

Byte

VB

DDDDD

0 ~ 10239

V Memory

VW

DDDDD

0 ~ 10239

V Memory

VW_Odd

DDDDD

0 ~ 10239

V Memory

DW

VD

DDDDD

0 ~ 10239

V Memory Double Word

DW

VD_Odd

DDDDD

0 ~ 10239

V Memory Double Word

VW_String

DDDDD

0 ~ 10239

String

VW_String_Odd DDDDD

0 ~ 10239

String

DW

VD_String

DDDDD

0 ~ 10239

String

DW

VD_String_Odd

DDDDD

0 ~ 10239

String

Byte

MB

DDDDD

0 ~ 10239

Byte Memory

MW

DDDDD

0 ~ 10239

Word Memory

MW_Odd

DDDDD

0 ~ 10239

Word Memory

DW

MD

DDDDD

0 ~ 10239

Word Memory

Byte

SB

DDDDD

0 ~ 10239

SCR

SW

DDDDD

0 ~ 10239

SCR

DW

SD

DDDDD

0 ~ 10239

SCR

Byte

SMB

DDDDD

0 ~ 10239

Special Memory

SMW

DDDDD

0 ~ 10239

Special Memory

DW

SMD

DDDDD

0 ~ 10239

Special Memory

DDD

0 ~ 255

Timer

DDD

0 ~ 255

Counter

Double word and floating point value must use VD device type.

How to Import Tag:


The tags created in the Symbol Table in Step7-MicroWIN software can be imported to
EasyBuilder.
1. In Symbol Table create the tags. Select all the tags and click the right mouse button
then copy the tags.

901

PLC Connection Guide

2. Launch EasyBuilder, add the driver in the device list in System Parameter Settings,
and then click Import Tag button.

3. Paste the tags copied in step 1 and then click OK.

4. Select all the tags and then click OK.

902

PLC Connection Guide

5. If succeeded, the following message window shows.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

8 D-

6 RX+

1 Data+

3 D+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

903

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

5 GND

5 GND

Driver Version:
Version

Date

Description

V2.30

Aug/17/2009

V2.40

Nov/01/2011

Add device type : MD

V2.60

Jan/03/2013

Add device types : S,SB,SW,SD,SM,SMB,SMW,SMD

V2.90

Set/06/2013

Add device types : T_Bit,C_Bit

904

PLC Connection Guide

Siemens S7-200 (Ethernet)


Supported Series: Siemens S7/200 Ethernet Series PLC
(CPU212/214/215/216/221/222/224/226/226XM) with CP243-1 Ethernet module
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

Options

PLC type

SIEMENS S7-200 (Ethernet)

PLC I/F

Ethernet

Port no.

102

PLC sta. no.

Notes

0-31

PLC Setting:
S7/200 Ethernet Multi-Connection Settings
Step 1: Launching the Ethernet Wizard
1. In the Micro/WIN main menu, click Tools / Ethernet Wizard.

905

PLC Connection Guide

2. Then, click Next.

3. Click Yes to proceed.

Step 2: Setting CP243-1 Module Position


1. Click Read Modules.

906

PLC Connection Guide

2. To view the results of Read Modules, select the Ethernet module. Click Next.

Step 3: Assigning Module Address


1. Click Next.

907

PLC Connection Guide

2. Enter the number of desired available connections for this device. If 0 is entered,
the only connection available will be the PG mode. The image below shows there
are 4 connections for this module.

3. Connection0 -> Select This is a Server Connection....


Notice the Local TSAP automatically incremented to 10.00.

908

PLC Connection Guide

4. Connection1Select This is a Server Connection....


Notice the Local TSAP automatically incremented to 11.00.

5. Upon completion of the settings above, set parameters in EasyBuilder. Set the
value of Local TSAP here to the value of Remote TSAP in Micro/WIN and vice
versa to realize multi-connection.

How to Import Tag:


The tags created in the Symbol Table in Step7-MicroWIN software can be imported to
EasyBuilder.
1. In Symbol Table create the tags. Select all the tags and click the right mouse button
then copy the tags.

909

PLC Connection Guide

2. Launch EasyBuilder, add the driver in the device list in System Parameter Settings,
and then click Import Tag button.

3. Paste the tags copied in step 1 and then click OK.

4. Select all the tags and then click OK.

910

PLC Connection Guide

5. If succeeded, the following message window shows.

Device Address:
Bit/Word

Device type Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

VW_Bit

DDDDDo

0 ~ 102397

V Memory Bit Address

DDDDo

0 ~ 40957

SCR

SM

DDDDo

0 ~ 40957

Special Memory

VW

DDDDD

0 ~ 10239

V Memory

DW

VD

DDDDD

0 ~ 10239

V Memory Double Word

VW_String

DDDDD

0 ~ 10239

String

DW

VD_String

DDDDD

0 ~ 10239

String

DW

MD

DDDDD

0 ~ 10239

Word Memory

Byte

VB

DDDDD

0 ~ 10239

V Memory Byte

Byte

SB

DDDDD

0 ~ 10239

SCR

SW

DDDDD

0 ~ 10239

SCR

DW

SD

DDDDD

0 ~ 10239

SCR

Byte

SMB

DDDDD

0 ~ 10239

Special Memory

SMW

DDDDD

0 ~ 10239

Special Memory

DW

SMD

DDDDD

0 ~ 10239

Special Memory

Double word and floating point value must use VD device type.

911

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.20

Dec/30/2008

V1.40

Nov/15/2011

Add device type : MD

V1.60

Jan/07/2013

Add device types : S,SB,SW,SD,SM,SMB,SMW,SMD

V1.80

Mar/23/2015

Add device type : VB

912

PLC Connection Guide

Siemens S7-200 (VD any address)


Supported Series: Siemens S7-200 series PLC
(CPU212/214/215/216/221/222/224/226/226XM)
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters
PLC type

Recommend Options
ed
Siemens S7-200 (VD any address)

PLC I/F

RS485 2w

Notes

RS485 2w
The HMI which has a sticker

Baud rate

9600

9600, 19200, 187.5K

MPI187.5 on the rear cover


supports 187.5K

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

1 ~ 126

Turn around delay (ms)

Reserved 1

30

Online simulator

ACK delay time

YES

Extend address mode NO

Broadcast command NO

PLC Setting:
Communication mode

Set station number to 2

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

VW_Bit

DDDDDo

0 ~ 102397

V Memory Bit Address

DDDDo

0 ~ 40957

SCR

SM

DDDDo

0 ~ 40957

Special Memory

913

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

VW

DDDDD

0 ~ 10239

V Memory

DW

VD

DDDDD

0 ~ 10239

V Memory Double Word

VW_String

DDDDD

0 ~ 10239

String

DW

VD_String

DDDDD

0 ~ 10239

String

MW

DDDDD

0 ~ 10239

Word Memory

DDD

0 ~ 255

Timer

DDD

0 ~ 255

Counter

DW

MD

DDDDD

0 ~ 10239

Word Memory

Byte

SB

DDDDD

0 ~ 10239

SCR

SW

DDDDD

0 ~ 10239

SCR

DW

SD

DDDDD

0 ~ 10239

SCR

Byte

SMB

DDDDD

0 ~ 10239

Special Memory

SMW

DDDDD

0 ~ 10239

Special Memory

DW

SMD

DDDDD

0 ~ 10239

Special Memory

Double word and floating point value must use VD device type.
VD register can set to any value, not necessarily a multiple of 4.

How to Import Tag:


The tags created in the Symbol Table in Step7-MicroWIN software can be imported to
EasyBuilder.
1. In Symbol Table create the tags. Select all the tags and click the right mouse button
then copy the tags.

914

PLC Connection Guide

2. Launch EasyBuilder, add the driver in the device list in System Parameter Settings,
and then click Import Tag button.

3. Paste the tags copied in step 1 and then click OK.

4. Select all the tags and then click OK.

915

PLC Connection Guide

5. If succeeded, the following message window shows.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

8 D-

6 RX+

1 Data+

3 D+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

916

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.20

Nov/16/2011

Add device type : MD

V1.40

Jan/07/2013

Add device types : S,SB,SW,SD,SM,SMB,SMW,SMD

917

PLC Connection Guide

Siemens S7-200 PPI


Supported Series: Siemens S7-200 series PLC
(CPU212/214/215/216/221/222/224/226/226XM)
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

PLC type

SIEMENS S7-200 PPI

PLC I/F

RS485 2w

RS485 2w

Baud rate

9600

9600, 19200, 187.5K

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1, 2

Turn around delay (ms)

ACK delay time (ms)

30

PLC sta. no.

Online simulator

Options

Notes

Only MT6000/8000V2 support


baud rate 187.5 K

1 ~ 126
YES

Extend address mode YES

Broadcast command NO

PLC Setting:
PLC setting

PLC sta. no. can not be the same as HMI sta. no.

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

VW_Bit

DDDDDo

0 ~ 102397

V Memory Bit Address

DDDDo

0 ~ 40957

SCR

SM

DDDDo

0 ~ 40957

Special Memory

T_Bit

DDD

0 ~ 255

Timer

C_Bit

DDD

0 ~ 255

Counter

918

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

Byte

VB

DDDDD

0 ~ 10239

VW

DDDDD

0 ~ 10239

V Memory

VW_Odd

DDDDD

0 ~ 10239

V Memory

DW

VD

DDDDD

0 ~ 10239

V Memory Double Word

DW

VD_Odd

DDDDD

0 ~ 10239

V Memory Double Word

VW_String

DDDDD

0 ~ 10239

String

VW_String_Odd DDDDD

0 ~ 10239

String

DW

VD_String

DDDDD

0 ~ 10239

String

DW

VD_String_Odd

DDDDD

0 ~ 10239

String

Byte

MB

DDDDD

0 ~ 10239

Byte Memory

MW

DDDDD

0 ~ 10239

Word Memory

MW_Odd

DDDDD

0 ~ 10239

Word Memory

DDD

0 ~ 255

Timer

DDD

0 ~ 255

Counter

DW

MD

DDDDD

0 ~ 10239

Word Memory

Byte

SB

DDDDD

0 ~ 10239

SCR

SW

DDDDD

0 ~ 10239

SCR

DW

SD

DDDDD

0 ~ 10239

SCR

Byte

SMB

DDDDD

0 ~ 10239

Special Memory

SMW

DDDDD

0 ~ 10239

Special Memory

DW

SMD

DDDDD

0 ~ 10239

Special Memory

Double Word and floating point value must use VD device type.

Multi-HMIs-Multi-PLCs Communication Setting:

919

PLC Connection Guide

For S7-200 PLC, Multi-HMIs-Multi-PLCs communication can be achieved using S7/200


PPI driver, please refer to the settings below.
IN EasyBuilder COM Port Settings, two important parameters must be set:

3. [High station address (HSA)]:


Setting Max. Station Number of HMI in PPI network.
For the effectiveness of system operation, it is highly recommended that the HMI station
number starts from zero and go on sequentially. If there are 4 HMI in PPI network, set
station no. from 0~3, and [High station address (HSA)] to 3.
Set HMI station number in [System Parameters] / [Model] / [HMI station no.]:

4. [Gap update factor(GUF)]:


The condition to pass a Token. In PPI network only HMI can hold a Token, PLC can only
be controlled.
When the HMI that holds Token communicates with PLC for a number of times that equals
to the value set here, HMI will pass the Token (control of PLC) to the next HMI. For
example, if GUF is set to 1, HMI will pass the control of PLC to the next HMI when read
or write the value in an address.

920

PLC Connection Guide

If GUF is set to a bigger value, the HMI that holds Token will control the PLC for a longer
time and therefore the Token wont be passed to another HMI and cause failure in
communicating with PLC.
A complete communication means HMI reads / writes PLC value for one time.

Note:

HMI sta. no. can not be the same as PLC sta. no.
Highly recommended that HMI sta. no. starts from 0 and go on sequentially for the
effectiveness of operation.

Available for EasyBuilder V4.50 and later.

How to Import Tag:


The tags created in the Symbol Table in Step7-MicroWIN software can be imported to
EasyBuilder.
1. In Symbol Table create the tags. Select all the tags and click the right mouse button
then copy the tags.

2. Launch EasyBuilder, add the driver in the device list in System Parameter Settings,
and then click Import Tag button.

921

PLC Connection Guide

3. Paste the tags copied in step 1 and then click OK.

4. Select all the tags and then click OK.

5. If succeeded, the following message window shows.

922

PLC Connection Guide

Pass-Through Settings:
[Designate client IP]: In Pass-through mode designate the client IP address to connect
HMI. The client usually refers to Siemens Step 7 application.

The following lists the system registers relevant to Siemens S7-200 PPI and
Siemens S7-300 MPI Pass-through feature.
[LW-10850: disable/enable (0 : disable, 1 : normal, 2 : IP limited) (siemens

pass-through)]
[LW-10851: destination COM port (siemens pass-through)]: Generally refers to the
COM port connected with PLC.
[LW-10852: destination PLC station no. (siemens pass-through)]
[LW-10853: communication protocol (0 : invalid, 1 : PPI, 2 : MPI) (siemens
pass-through)]
[LW-10854 to LW-10857: IP of connecting client (siemens pass-through)]: Displays
current client IP address connected with HMI.
[LW-10858 to LW-10861: IP of designated client (siemens pass-through)]: If

LW-10850 is set to 1, the system registers can be used to designate the client IP
connected with HMI.
[LW-10862: connection status (0 : ready, 1 : client connecting) (siemens
pass-through)]
[LW-10863: execution status (0 : normal, 1 : error) (siemens pass-through)]
[LW-10864: the last error (siemens pass-through)]

923

PLC Connection Guide

The following table lists the error codes, the description of each code, and the
possible reason.
Error Code

Description

Possible Reason

Successfully executed

HMI is already running pass-through


Prohibit client from connecting
and wont accept any request from
HMI
other client.

When LW-10850 is set to 1, the


Prohibit client from connecting client IP for connecting HMI is
HMI

different from the IP specified in


LW-10858 ~ LW-10861.

Invalid communication
protocol

Invalid setting in LW-10853.

Invalid PLC station number

The PLC station number specified in


LW-10852 does not exist.

Delayed communication

PLC connection failure.

Busy communication

PLC does not accept pass-through


request, please confirm PLC

settings.
7

Invalid pass-through request

Environment setup failure.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W

COM3 RS485 2W

RS485 2W 9P D-Sub

9P D-Sub Male

9P D-Sub Male

Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

8 D-

6 RX+

1 Data+

3 D+

5 GND

5 GND

5 GND

cMT/mTV series

924

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

5 GND

5 GND

Driver Version
Version

Date

Description

V1.00

Aug/15/2011

Driver released.

V1.10

Nov/17/2011

Add device type : MD

V1.50

Jan/07/2013

Add device types : S,SB,SW,SD,SM,SMB,SMW,SMD

V2.00

Set/06/2013

Add device type : T_Bit,C_Bit

925

PLC Connection Guide

Siemens S7-200 SMART (Ethernet)


Supported Series: Siemens S7/200 SMART Series Ethernet Module.
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

PLC type

Siemens S7-200 SMART (Ethernet)

PLC I/F

Ethernet

Port no.

102

PLC sta. no.

Online simulator

Yes

Options

Notes

Mutiple HMI connection Yes

*At most four HMIs can be connected with PLC simultaneously.

Device Address:
Bit/Word

Device type Format

Range

Memo

DDo

0 ~ 317

Input

DDo

0 ~ 317

Output

DDo

0 ~ 317

Bit Memory

DDDDDo

0 ~ 204797

V Memory bit

DDo

0 ~ 317

SCR

SM

DDDDo

0 ~ 15357

Special Memory Bit

Timer

DDD

0 ~ 255

Timer

Counter

DDD

0 ~ 255

Counter

MW

DD

0 ~ 30

Word Memory

VW

DDDDD

0 ~ 20478

V Memory

SMW

DDDD

0 ~ 1534

Special Memory

DDD

0 ~ 255

Timer

DDD

0 ~ 255

Counter

AIW

DDD

0 ~ 110

Analog input

AQW

DDD

0 ~ 110

Analog Output

DW

VD

DDDDD

0 ~ 20476

V Memory (Double Word)

Double word and floating point value must use VD device type.

926

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Oct/5/2012

Driver released.

V1.20

Jun/14/2013

The function of connecting multiple HMIs simultaneously is


added.

927

PLC Connection Guide

Siemens S7-200 SMART PPI


Supported Series: Siemens S7-200 SMART series PLC
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

PLC type

Siemens S7-200 SMART PPI

PLC I/F

RS485 2W

RS485 2W

Baud rate

9600

9600, 19200,
187.5K

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1, 2

Turn around delay (ms)

ACK delay time (ms)

30

PLC sta. no.

Online simulator

Options

Notes

Only MT6000/8000V2 support


baud rate 187.5 K

1 ~ 126
YES

Extend address mode NO

Broadcast command NO

PLC Setting:
PLC setting

PLC sta. no. can not be the same as HMI sta. no.

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDo

0 ~ 317

Input

DDo

0 ~ 317

Output

DDo

0 ~ 317

Bit Memory

DDDDDo

0 ~ 204797

V Memory bit

DDo

0 ~ 317

SCR

SM

DDDDo

0 ~ 15357

Special Memory Bit

Timer

DDD

0 ~ 255

Timer

Counter

DDD

0 ~ 255

Counter

MW

DD

0 ~ 30

Word Memory

928

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

VW

DDDDD

0 ~ 20478

V Memory

SMW

DDDD

0 ~ 1534

Special Memory

DDD

0 ~ 255

Timer

DDD

0 ~ 255

Counter

AIW

DDD

0 ~ 110

Analog input

AQW

DDD

0 ~ 110

Analog Output

DW

VD

DDDDD

0 ~ 20476

V Memory (Double Word)

Double Word and floating point value must use VD device type.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

8 D-

6 RX+

1 Data+

3 D+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

929

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

5 GND

5 GND

Driver Version
Version

Date

Description

V1.00

Oct/5/2012

Driver released.

930

PLC Connection Guide

Siemens S7-300
Supported Series: Siemens S7-300 series PLC
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended Options

PLC type

SIEMENS S7-300

PLC I/F

RS232

Baud rate

19200

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Notes

9600,19200

Must be same as the PLC setting.

Device Address:
Bit/Word Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

DBnBit

FFFFDDDDo

0 ~ 409681927

Data Register Bit

DDDDo

0 ~ 81927

DB1Bit ~
DB99Bit

IW

DDDD

0 ~ 4095

Input (I)

QW

DDDD

0 ~ 4095

Output (O)

MW

DDDD

0 ~ 4095

Bit Memory

DW

MD

DDDD

0 ~ 4094

Byte

MB

DDDD

0 ~ 4095

Bit Memory Byte

Byte

DBBn

FFFFDDDD

0 ~ 40968192

Data Register Byte

DBn

FFFFDDDD

0 ~ 40968192

Data Register (must be even)

DW

DBDn

FFFFDDDD

0 ~ 40968192

DBn_String

FFFFDDDD

0 ~ 40968192
931

Data Register Double Word


(must be multiple of 4)
Data Register Double Word
(must be multiple of 4)

PLC Connection Guide

Bit/Word Device type

Format

Range

DW

DBDn_String FFFFDDDD

0 ~ 40968192

DB1-DB99

0 ~ 8192

DDDD

Memo
Data Register Double Word
(must be multiple of 4)
Data Register
(must be even)

* Double word and floating point value must use DBDn device type.

How to Import Tag:


SIEMENS STEP 7 program allows building files of user-defined tag (*.dif file and *.AWL
file), and import these files in EasyBuilder8000/EasyBuilderPro -> System Parameter
Settings. The following describes how to build and import these two types of files.
1. Building *.dif File
a In Symbols create user-defined tag.

932

PLC Connection Guide

b Click Export to export the edited file and click Save.

2. Building *.AWF File


a In Blocks create items as shown below:

b Open LAD/STL, FBD Programming S7 Blocks, click File -> Generate


Source.

933

PLC Connection Guide

c Select Sources as storage path, specify the file name then click OK.

d Select the objects to be exported then click OK.

934

PLC Connection Guide

e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.

The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro


System Parameter Settings, by clicking Import Tag.

Tag information successfully imported.

935

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
Siemens S7-300 PC Adapter : 9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

936

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

The following is the view from the soldering point of a cable.


Systeme Helmholz SSW7-TS : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS
4 DTR
6 DSR

short
short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS
4 DTR
6 DSR

937

short
short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS
4 DTR
6 DSR

short
short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS
4 DTR
6 DSR

short
short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS
4 DTR
6 DSR

Driver Version:
Version

Date

Description

V3.10

May/24/2011

Added registers: MB & DBBn.


938

short
short

PLC Connection Guide

Siemens S7-300/S7-400 (ISO Ethernet)


Supported Series: Siemens S7-300 Ethernet Series PLC, Ethernet module CP-343-1,
CPU315-2 PN/DP, CPU317-2 PN/DP, CPU319-3 PN/DP, ET200S, CP-443-1.
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

PLC type

Siemens S7-300/S7-400 (ISO Ethernet)

PLC I/F

Ethernet

Local TSAP

100

Remote TSAP

103

Online simulator

Options

No

939

Notes

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

DBnBit

FFFFDDDDo

0 ~ 409699997

DB0Bit-DB99Bit DDDDDo

0 ~ 655327

Data Register Bit

IW

DDDD

0 ~ 4095

Input (I)

QW

DDDD

0 ~ 4095

Output (O)

MW

DDDD

0 ~ 4095

Bit Memory

DW

MD

DDDD

0 ~ 4094

Bit Memory Double Word

DW

MD_Anyaddr

DDDD

0 ~ 4094

DBn

FFFFDDDD

0 ~ 40969999

DW

DBDn

FFFFDDDD

0 ~ 40969999

DW

DBDn_Anyaddr

FFFFDDDD

0 ~ 40969999

DBn_String

FFFFDDDD

0 ~ 40969999

DW

DBDn_String

FFFFDDDD

0 ~ 40969999

DB0 ~ DB99

DDDDD

0 ~ 65532

Data Register(must be even)

Byte

MB

DDDD

0 ~ 4095

Bit Memory Byte

Byte

DBBn

FFFFDDDD

0 ~ 40969999

Data Register Byte

Bit Memory Double Word


(must be even)
Data Register
(must be even)
Data Register Double Word
(must be multiple of 4)
Data Register Double Word
(must be even)

Double word and floating point value must use DBDn device type.

940

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Jan/15/2014

Driver released.

V1.10

Feb/21/2014

1. Fixed the problem where the value will be cleared to 0 first


when writing a value in the register.
2. Supports Multi-HMI connection.

V1.70

Sep/09/2015

Support Siemens S7-400 series PLC

941

PLC Connection Guide

Siemens S7-300 MPI


Supported Series: Siemens S7-300 series PLC
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

PLC type

SIEMENS S7-300 MPI

PLC I/F

RS-485 2W

Baud rate

187.5K

Data bits

Parity

Even

Stop bits

PLC sta. no.

Online simulator

Options

Notes

19200,187.5K

2 ~ 31
NO

Extend address mode Yes

Broadcast command NO

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

DBnBit
DB1Bit ~

FFFFDDDDo

0 ~ 409699997

Data Register Bit

DDDDDo

0 ~ 655327

Data Register Bit

DB99Bit

IW

DDDD

0 ~ 4095

Input (I)

QW

DDDD

0 ~ 4095

Output (O)

MW

DDDD

0 ~ 4095

Bit Memory

DW

MD

DDDD

0 ~ 4094

Byte

MB

DDDD

0 ~ 4095

Bit Memory Byte

Byte

DBBn

FFFFDDDD

0 ~ 40969999

Data Register

DBn

FFFFDDDD

0 ~ 40969999

Data Register (must be even)

DW

DBDn

FFFFDDDD

0 ~ 40969999
942

Data Register Double Word


(multiple of 4)

PLC Connection Guide

Bit/Word

Device type

Format

Range

DBn_String

FFFFDDDD

0 ~ 40969999

DW

DBDn_String FFFFDDDD

0 ~ 40969999

DB1 ~ DB99

0 ~ 65532

DDDDD

Memo

Data Register (must be even)

Double word and floating point value must use DBDn device type.

Multi-HMIs-Multi-PLCs Communication Setting:

For SIEMENS S7-300 MPI driver in Multi-HMIs-Multi-PLCs communication, [Max. station


no. (MPI network)] parameter must be correctly set. This setting is relevant to the station
no. of the devices, as shown, two HMI (station no. 0, 1) and two PLC (station no. 2, 3) are
in MPI network, Max. Station No. should be set to 3.

943

PLC Connection Guide

For the effectiveness of communication, users may set PLC device in STEP 7 as shown
below. In Properties MPI / Network Settings, set Highest MPI address to the number
closest to the actual device station number.

HMI sta. no. can not be the same as PLC sta. no.
Highly recommended that the device station numbers start from 0 sequentially and
correctly set [Max. station no. (MPI network)].
Available for EasyBuilder V4.50 and later.
X Series does not support multiple-HMI-to-multiple-PLC communication, and supports
only 1-HMI-to-1-PLC communication.

How to Import Tag:


SIEMENS STEP 7 program allows building files of user-defined tag (*.dif file and *.AWL
file), and import these files in EasyBuilder8000/EasyBuilderPro -> System Parameter
Settings. The following describes how to build and import these two types of files.

944

PLC Connection Guide

1. Building *.dif File


a In Symbols create user-defined tag.

b Click Export to export the edited file and click Save.

945

PLC Connection Guide

2. Building *.AWF File


a In Blocks create items as shown below:

b Open LAD/STL, FBD Programming S7 Blocks, click File -> Generate


Source.

c Select Sources as storage path, specify the file name then click OK.

946

PLC Connection Guide

d Select the objects to be exported then click OK.

e Under Sources there will be names of the saved files, select Export
Source to build *.AWL file.

947

PLC Connection Guide

The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro


System Parameter Settings, by clicking Import Tag.

Tag information successfully imported.

Pass-Through Settings:
[Designate client IP]: In Pass-through mode designate the client IP address to connect
HMI. The client usually refers to Siemens Step 7 application.

948

PLC Connection Guide

The following lists the system registers relevant to Siemens S7-200 PPI and
Siemens S7-300 MPI Pass-through feature.
[LW-10850: disable/enable (0 : disable, 1 : normal, 2 : IP limited) (siemens
pass-through)]
[LW-10851: destination COM port (siemens pass-through)]: Generally refers to the
COM port connected with PLC.
[LW-10852: destination PLC station no. (siemens pass-through)]
[LW-10853: communication protocol (0 : invalid, 1 : PPI, 2 : MPI) (siemens
pass-through)]
[LW-10854 to LW-10857: IP of connecting client (siemens pass-through)]: Displays
current client IP address connected with HMI.
[LW-10858 to LW-10861: IP of designated client (siemens pass-through)]: If
LW-10850 is set to 1, the system registers can be used to designate the client IP
connected with HMI.
[LW-10862: connection status (0 : ready, 1 : client connecting) (siemens
pass-through)]
[LW-10863: execution status (0 : normal, 1 : error) (siemens pass-through)]
[LW-10864: the last error (siemens pass-through)]
The following table lists the error codes, the description of each code, and the
possible reason.
Error Code

Description

Possible Reason

Successfully executed

HMI is already running pass-through


Prohibit client from connecting
and wont accept any request from
HMI
other client.
When LW-10850 is set to 1, the

Prohibit client from connecting client IP for connecting HMI is


HMI
different from the IP specified in
LW-10858 ~ LW-10861.

Invalid communication
protocol

Invalid setting in LW-10853.

Invalid PLC station number

The PLC station number specified in


LW-10852 does not exist.

Delayed communication

PLC connection failure.

Busy communication

PLC does not accept pass-through


request, please confirm PLC
settings.

Invalid pass-through request

Environment setup failure.

949

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
S7-200 PPI , S7-300 MPI :RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

8 D-

6 RX+

1 Data+

3 D+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W

COM3 RS485 2W

RS485 2W 9P D-Sub

9P D-Sub Male

9P D-Sub Male

Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

950

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.90

May/26/2011

Added registers: MB & DBBn

V2.00

Aug/19d/2011

i Series HMI support Multi HMIs-Multi PLCs


communication.

951

PLC Connection Guide

Siemens S7-300/ET200S (Ethernet)


Supported Series: Siemens S7-300 Ethernet Series PLC, Ethernet module CP-343-1,
CPU315-2 PN/DP, CPU317-2 PN/DP, CPU319-3 PN/DP, and ET200S.
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

Options

PLC type

SIEMENS S7-300/ET200S (Ethernet)

PLC I/F

Ethernet

Port no.

102

PLC sta. no.

Notes

0-31

In V3.00 and later versions, setting [Interval of block pack] to 0 can optimize efficiency.

952

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

DBnBit

FFFFDDDDo

0 ~ 409699997

DB1Bit-DB99Bit DDDDDo

0 ~ 655327

Data Register Bit

IW

DDDD

0 ~ 4095

Input (I)

QW

DDDD

0 ~ 4095

Output (O)

MW

DDDD

0 ~ 4095

Bit Memory

DW

MD

DDDD

0 ~ 4094

Bit Memory Double Word

DW

MD_Anyaddr

DDDD

0 ~ 4094

DBn

FFFFDDDD

0 ~ 40969999

DW

DBDn

FFFFDDDD

0 ~ 40969999

DW

DBDn_Anyaddr

FFFFDDDD

0 ~ 40969999

DBn_String

FFFFDDDD

0 ~ 40969999

DW

DBDn_String

FFFFDDDD

0 ~ 40969999

DB1 ~ DB99

DDDDD

0 ~ 65532

Data Register(must be even)

Byte

MB

DDDD

0 ~ 4095

Bit Memory Byte

Byte

DBBn

FFFFDDDD

0 ~ 40969999

Data Register Byte

Bit Memory Double Word


(must be even)
Data Register
(must be even)
Data Register Double Word
(must be multiple of 4)
Data Register Double Word
(must be even)

Double word and floating point value must use DBDn device type.

953

PLC Connection Guide

How to Import Tag:


SIEMENS STEP 7 program allows building files of user-defined tag (*.dif file and *.AWL
file), and import these files in EasyBuilder8000/EasyBuilderPro -> System Parameter
Settings. The following describes how to build and import these two types of files.
1. Building *.dif File
a In Symbols create user-defined tag.

954

PLC Connection Guide

b Click Export to export the edited file and click Save.

2. Building *.AWF File


a In Blocks create items as shown below:

b Open LAD/STL, FBD Programming S7 Blocks, click File -> Generate


Source.

955

PLC Connection Guide

c Select Sources as storage path, specify the file name then click OK.

d Select the objects to be exported then click OK.

956

PLC Connection Guide

e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.

The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro


System Parameter Settings, by clicking Import Tag.

Tag information successfully imported.

957

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V2.10

May/21/2011

Added registers: MB & DBBn.

V2.20

Apr/25/2012

Added registers: MD_Anyaddr & DBDn_Anyaddr.

958

PLC Connection Guide

Siemens S7-400 (Ethernet)


Supported Series: Siemens S7-400/1200 Ethernet PLC.
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

Options

PLC type

Siemens S7-400 (Ethernet)

PLC I/F

Ethernet

Port no.

102

Link type

PG

PC, OP

Rack

0-7

CPU slot

1-31

PLC sta. no.

0-31

Notes

To Connect with S7-1200,slot 1


must be selected.

Device Address:
Bit/Word Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

DBnBit

FFFFFDDDDo 0 ~ 6553599997

DB1Bit-DB99Bit DDDDDo

0 ~ 655327

Data Register Bit

IW

DDDD

0 ~ 4095

Input (I)

QW

DDDD

0 ~ 4095

Output (O)

MW

DDDD

0 ~ 4095

Bit Memory

DW

MD

DDDD

0 ~ 4094

DBn

FFFFFDDDD

0 ~ 655359999

DW

DBDn

FFFFFDDDD

0 ~ 655359999

DBn_String

FFFFFDDDD

0 ~ 655359999

DW

DBDn_String

FFFFFDDDD

0 ~ 655359999

DB1 ~ DB99

DDDDD

0 ~ 65532

Byte

MB

DDDD

0 ~ 4095

Bit Memory Byte

Byte

DBBn

FFFFFDDDD

0 ~ 655359999

Data Register Byte

Data Register
(must be even)
Data Register Double Word
(must be multiple of 4)

Data Register
(must be even)

* Double word and floating point value must use DBDn device type.
959

PLC Connection Guide

EasyBuilder Device Setting Steps


1.

Open EasyBuilder, File/NEW, select HMI model and press [OK].

2.

System Parameter Settings window is shown, click [New].

3.

Select SIEMENS S7-400(ETHERNET).

4.

Press [Settings].

960

PLC Connection Guide

5.

Set S7-400 IP, Port no., Link type, Rack and CPU slot. (must match PLC settings)

6.

The setting will be finished as below.

961

PLC Connection Guide

How to Import Tag:


SIEMENS STEP 7 program allows building files of user-defined tag (*.dif file and *.AWL
file), and import these files in EasyBuilder8000/EasyBuilderPro -> System Parameter
Settings. The following describes how to build and import these two types of files.
1. Building *.dif File
a In Symbols create user-defined tag.

b Click Export to export the edited file and click Save.

962

PLC Connection Guide

2. Building *.AWF File


a In Blocks create items as shown below:

b Open LAD/STL, FBD Programming S7 Blocks, click File -> Generate


Source.

c Select Sources as storage path, specify the file name then click OK.

963

PLC Connection Guide

d Select the objects to be exported then click OK.

e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.

964

PLC Connection Guide

The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro


System Parameter Settings, by clicking Import Tag.

Tag information successfully imported.

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.40

May/25/2011

Added registers: MB & DBBn

V1.50

Aug/03/2012

Device types DBn, DBDn is extended to 655359999.


965

PLC Connection Guide

Siemens TI505
Supported Series: SIMATIC TI505 Series PLCs: TI520, TI525, TI530, TI535, TI545, TI555,
TI560, TI565, TI575. Use NITP protocol in a point-to-point, single master, single slave
format.
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

Options

PLC type

SIMATIC TI505

PLC I/F

RS232

Baud rate

19200

RS232,
RS485(4W)
19200

Data bits

Parity

Odd

Odd

Stop bits

PLC sta. no.

Does not apply

Notes
NITP protocol

Device Address:
Bit/Word Device type

Format

Range

Memo

CR

DDDDD

1 ~ 65535

Internal Relay

DDDDD

1 ~ 65535

Discrete Input Coils

DDDDD

1 ~ 65535

Discrete Output Coils

V_Bit

DDDDDdd 101 ~ 6553616

DDDDD

1 ~ 65535

User Data Registers

DW

VD

DDDDD

1 ~ 65536

User Data Registers (32bit)

STW

DDDDD

1 ~ 65535

Status Word Registers

TCP

DDDDD

1 ~ 65535

Timer/Counter Preset Values

TCC

DDDDD

1 ~ 65535

Timer/Counter Current Values

WX

DDDDD

1 ~ 65535

Word Discrete Inputs

WY

DDDDD

1 ~ 65535

Word Discrete Outputs

966

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
SIMATIC TI505 RS232 : 9P D-Sub to 25P D-Sub
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 25P D-Sub Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

7 GND
4 RTS
5 CTS

short

6 DSR
8 DCD

short

20 DTR
cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 25P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

7 GND
4 RTS
5 CTS

short

6 DSR
8 DCD

short

20 DTR
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 25P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

7 GND
4 RTS
5 CTS

short

6 DSR
8 DCD
20 DTR

967

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 25P D-Sub Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

7 GND
4 RTS
5 CTS

short

6 DSR
8 DCD

short

20 DTR
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 25P D-Sub Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

7 GND
4 RTS
5 CTS

short

6 DSR
8 DCD
20 DTR

968

short

PLC Connection Guide

The following is the view from the soldering point of a cable.


SIMATIC TI505 RS232 : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

1 DCD
4 DTR

short

6 DSR
cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

1 DCD
4 DTR

short

6 DSR
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

1 DCD
4 DTR
6 DSR

969

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

7 RTS
8 CTS

1 DCD

1 DCD

4 DTR

4 DTR

6 DSR
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

1 DCD
4 DTR

short

6 DSR

The following is the view from the soldering point of a cable.


SIMATIC TI505 RS485 4W : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

7 DO (-)

2 RX+

1 DO (+)

3 TX-

8 DI (-)

4 TX+

5 DI (+)

5 GND

6 GND

970

PLC Connection Guide

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

7 DO (-)

6 RX+

1 DO (+)

9 TX-

8 DI (-)

8 TX+

5 DI (+)

5 GND

6 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

7 DO (-)

2 RX+

2 RX+

1 DO (+)

3 TX-

3 TX-

8 DI (-)

4 TX+

4 TX+

5 DI (+)

5 GND

5 GND

6 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W

RS485 4W 9P D-Sub

9P D-Sub Male

Male

1 RX-

7 DO (-)

2 RX+

1 DO (+)

3 TX-

8 DI (-)

4 TX+

5 DI (+)

5 GND

6 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

RS485 4W 9P D-Sub

9P D-Sub Female

Male

1 RX-

7 DO (-)

2 RX+

1 DO (+)

3 TX-

8 DI (-)

4 TX+

5 DI (+)

5 GND

6 GND

971

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.10

Apr/22/2009

V1.40

Jun/08/2014

Added register: VD

V1.50

Nov/18/2014

Added register: V_Bit

972

PLC Connection Guide

Siemens TI505 (Ethernet)


Supported Series: SIMATIC TI505 Series PLCs: TI520, TI525, TI530, TI535, TI545, TI555,
TI560, TI565, TI575 with ethernet module.
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

Options

PLC type

Siemens TI505 (Ethernet)

PLC I/F

Ethernet

Port no.

1505

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

CR

DDDDD

1 ~ 65536

Internal Relay

DDDDD

1 ~ 65536

Discrete Input Coils

DDDDD

1 ~ 65536

Discrete Output Coils

V_Bit

DDDDDdd

101 ~ 6553616

DDDDD

1 ~ 65536

User Data Registers

DW

VD

DDDDD

1 ~ 65535

User Data Registers (32bit)

STW

DDDDD

1 ~ 65536

Status Word Registers

TCP

DDDDD

1 ~ 65536

Timer/Counter Preset Values

TCC

DDDDD

1 ~ 65536

Timer/Counter Current

WX

DDDDD

1 ~ 65536

ValuesDiscrete Inputs
Word

WY

DDDDD

1 ~ 65536

Word Discrete Outputs

973

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Feb/10/2014

Driver released.

V1.20

Jun/08/2014

Added register: VD

V1.30

Nov/18/2014

Added register: V_Bit

974

PLC Connection Guide

Siemens TI565/C400
Supported Series: CTI565-C400,CTI 2500-C200
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters

Recommended

Options

PLC type

SIMATIC TI565/C400

PLC I/F

RS232

RS232, RS485(4W)

Baud rate

19200

19200

Data bits

Parity

Odd

Odd

Stop bits

PLC sta. no.

Does not apply

Notes

Device Address:
Bit/Word Device type

Format

Range

Memo

CR

DDDDD

1 ~ 65535

Internal Relay

DDDDD

1 ~ 65535

Discrete Input Coils

DDDDD

1 ~ 65535

Discrete Output Coils

V_Bit

DDDDDdd

101 ~ 6553616

DDDDD

1 ~ 65535

User Data Registers

DW

VD

DDDDD

1 ~ 65535

User Data Registers (32bit)

STW

DDDDD

1 ~ 65535

Status Word Registers

TCP

DDDDD

1 ~ 65535

Timer/Counter Preset Values

TCC

DDDDD

1 ~ 65535

Timer/Counter Current Values

WX

DDDDD

1 ~ 65535

Word Discrete Inputs

WY

DDDDD

1 ~ 65535

Word Discrete Outputs

975

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 25P D-Sub: RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 25P D-Sub Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

7 GND
4 RTS
5 CTS

short

6 DSR
8 DCD

short

20 DTR
cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 25P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

7 GND
4 RTS
5 CTS

short

6 DSR
8 DCD

short

20 DTR
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 25P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

7 GND
4 RTS
5 CTS

short

6 DSR
8 DCD
20 DTR

976

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 25P D-Sub Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

7 GND
4 RTS
5 CTS

short

6 DSR
8 DCD

short

20 DTR
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 25P D-Sub Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

7 GND
4 RTS
5 CTS

short

6 DSR
8 DCD
20 DTR

977

short

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 9P D-Sub: RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

1 DCD
4 DTR

short

6 DSR
cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

1 DCD
4 DTR

short

6 DSR
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

1 DCD
4 DTR
6 DSR

978

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

1 DCD
4 DTR

short

6 DSR
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

1 DCD
4 DTR
6 DSR

979

short

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 9P D-Sub: RS-485 4W
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

7 DO (-)

2 RX+

1 DO (+)

3 TX-

8 DI (-)

4 TX+

5 DI (+)

5 GND

6 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

7 DO (-)

6 RX+

1 DO (+)

9 TX-

8 DI (-)

8 TX+

5 DI (+)

5 GND

6 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

7 DO (-)

2 RX+

2 RX+

1 DO (+)

3 TX-

3 TX-

8 DI (-)

4 TX+

4 TX+

5 DI (+)

5 GND

5 GND

6 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

7 DO (-)

2 RX+

1 DO (+)

3 TX-

8 DI (-)

4 TX+

5 DI (+)

5 GND

6 GND

980

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

1 RX-

7 DO (-)

2 RX+

1 DO (+)

3 TX-

8 DI (-)

4 TX+

5 DI (+)

5 GND

6 GND

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

CTI2500-C200 RS232
9P D-Sub Female

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

CTI2500-C200 RS232
9P D-Sub Female

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

CTI2500-C200 RS232
9P D-Sub Female

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

CTI2500-C200 RS232
9P D-Sub Female

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

981

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

CTI2500-C200 RS232
9P D-Sub Female

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Aug/31/2011

Driver released.

V1.20

Jun/08/2014

Added register: VD

V1.30

Nov/18/2014

Added register: V_Bit

982

PLC Connection Guide

SIGMATEK S-DIAS CPU (Ethernet)


Supported Series: SIGMATEK S-DIAS Digital Mix DM162
Website: http://www.sigmatek-automation.com/en/

HMI Setting:
Parameters

Recommended

PLC type

SIGMATEK S-DIAS CPU (Ethernet)

PLC I/F

Ethernet

Port no.

1956

PLC sta. no.

On-line simulator

Yes

Options

Notes

Multi-HMI connect

Yes

How to Import Tag:


1. Launch LASAL Class 2, click Network View tab, and the software editing area
opens.

983

PLC Connection Guide

2. Switch to Class View tab and drag the object to the editing area.

3. In the editing area select the object, and in Properties tab select true for
Visualized.

4. Build the file.

984

PLC Connection Guide

5. After editing, the MaeExp.txt file will be generated under the project folder, and
the file can be imported to EasyBuilder. If false was selected for Visualized in step
3, then the file will not be imported to EasyBuilder.

6. Launch EasyBuilder, select SIGMATEK driver and set the parameters, and then
select Import Tag.

985

PLC Connection Guide

7.

Click Get Tag Verifying tags with PLC, and then select the MaeExp.txt file
generated in step 5. Please check that the PLC is on line for verification. The
address tags can also be imported by clicking Get Tag Import Tag, and then run
off-line simulation. Please note that on-line simulation and download cannot be
carried out using this method.

8. See the result in Import Status field.

986

PLC Connection Guide

Support Device Type:


Data type

EasyBuilder data format

Bool

bit

Byte

8-bit

DInt

16-bit BCD, Hex, Binary,


Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Unsigned
16-bit BCD, Hex, Binary,
Signed
16-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Unsigned
32-bit BCD, Hex, Binary,
Signed

Real

32-bit Float

32-bit

UDInt

32-bit BCD, Hex, Binary,


Unsigned

32-bit

BitArray

bit

SInt
USInt
Word
Int
UInt
DWord

Memo

8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit

Wiring Diagram:
HMI RJ45 Male

Wire Color

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

White/Orange

1 TX+

2 TX-

Orange

Orange

2 TX-

3 RX+

White/Green

White/Green

3 RX+

4 BD4+

Blue

Blue

4 BD4+

5 BD4-

White/Blue

White/Blue

5 BD4-

6 RX-

Green

Green

6 RX-

7 BD3+

White/Brown

White/Brown

7 BD3+

8 BD3-

Brown

Brown

8 BD3-

987

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Jan/28/2016

Driver released.

988

PLC Connection Guide

SSTC SSD Series


Supported Series: SSTC SSD Series

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

SSTC SSD Series

PLC I/F

RS232

RS232/RS485 2W

Baud rate

19200

9600~115200

Data bits

Parity

None

None,Odd

Stop bits

PLC sta. no.

1~32

X Series does not support RS-485 2W communication.

Device Address:
Bit/Word

Device Type

Format

Range

Memo

ID

DDDDD

0 ~ 99999

ID_30

DDDDD

30

Use Unicode

ID_35000

DDDDD

35000

String

ID_35001

DDDDD

35001

String

ID Address List:
ID No.

Data Length

Data Type

Write / Read

Decimal Place*

BYT2

UDEC

Yes/Yes

30

BYT4

HEX

No/Yes

Hex

36

BYT4

SDEC

Yes/Yes

0.0001

38

BYT4

UDEC

Yes/Yes

0.0001

39

BYT4

SDEC

Yes/Yes

0.0001

40

BYT4

SDEC

No/Yes

0.0001

41

BYT4

SDEC

No/Yes

0.0001

43

BYT2

UDEC

Yes/Yes

47

BYT4

SDEC

Yes/Yes

48

BYT4

SDEC

Yes/Yes

989

PLC Connection Guide

ID No.

Data Length

Data Type

Write / Read

Decimal Place*

49

BYT4

SDEC

Yes/Yes

50

BYT4

SDEC

Yes/Yes

51

BYT4

SDEC

Yes/Yes

53

BYT4

SDEC

Yes/Yes

55

BYT2

UDEC

Yes/Yes

57

BYT4

UDEC

Yes/Yes

80

BYT2

SDEC

Yes/Yes

0.1

82

BYT2

UDEC

Yes/Yes

0.1

83

BYT2

SDEC

Yes/Yes

0.1

84

BYT2

SDEC

No/Yes

0.1

85

BYT2

UDEC

Yes/Yes

100

BYT2

UDEC

Yes/Yes

101

BYT2

UDEC

Yes/Yes

0.1

102

BYT2

UDEC

Yes/Yes

0.1

103

BYT4

SDEC

Yes/Yes

104

BYT2

UDEC

Yes/Yes

109

BYT4

UDEC

Yes/Yes

0.001

110

BYT4

UDEC

No/Yes

0.001

111

BYT4

UDEC

Yes/Yes

0.001

112

BYT4

UDEC

No/Yes

0.001

113

BYT4

UDEC

Yes/Yes

0.0001

116

BYT4

UDEC

Yes/Yes

124

BYT4

SDEC

Yes/Yes

0.0001

125

BYT4

SDEC

Yes/Yes

0.0001

126

BYT2

SDEC

Yes/Yes

0.1

136

BYT4

SDEC

Yes/Yes

137

BYT4

SDEC

Yes/Yes

147

BYT2

HEX

Yes/Yes

Hex

150

BYT4

SDEC

Yes/Yes

153

BYT4

SDEC

Yes/Yes

154

BUT2

HEX

Yes/Yes

Hex

157

BYT4

SDEC

Yes/Yes

0.0001

159

BYT4

UDEC

Yes/Yes

173

BYT4

SDEC

Yes/Yes

990

PLC Connection Guide

ID No.

Data Length

Data Type

Write / Read

Decimal Place*

193

BYT2

UDEC

Yes/Yes

209

BYT4

UDEC

Yes/Yes

0.0001

210

BYT4

UDEC

Yes/Yes

0.0001

211

BYT2

UDEC

Yes/Yes

0.1

212

BYT2

UDEC

Yes/Yes

0.1

222

BYT4

SDEC

Yes/Yes

225

BYT2

HEX

Yes/Yes

Hex

228

BYT4

UDEC

Yes/Yes

230

BYT4

UDEC

Yes/Yes

268

BYT4

UDEC

Yes/Yes

278

BYT4

UDEC

Yes/Yes

32768

BYT2

UDEC

Yes/Yes

0.1

32769

BYT4

UDEC

Yes/Yes

0.001

32770

BYT4

UDEC

Yes/Yes

0.001

32771

BYT2

UDEC

Yes/Yes

0.1

32772

BYT4

UDEC

Yes/Yes

0.0001

32773

BYT4

HEX

Yes/Yes

Hex

32774

BYT2

UDEC

Yes/Yes

0.1

32775

BYT2

UDEC

Yes/Yes

32776

BYT2

UDEC

Yes/Yes

32777

BYT2

SDEC

Yes/Yes

0.1

32778

BYT4

SDEC

Yes/Yes

0.0001

32779

BYT4

SDEC

Yes/Yes

0.0001

32780

BYT4

UDEC

Yes/Yes

0.1

32781

BYT4

UDEC

Yes/Yes

0.1

32782

BYT4

UDEC

Yes/Yes

0.1

32783

BYT2

UDEC

Yes/Yes

32784

BYT4

SDEC

Yes/Yes

32785

BYT2

UDEC

Yes/Yes

32786

BYT4

SDEC

Yes/Yes

32787

BYT4

UDEC

Yes/Yes

32788

BYT4

SDEC

Yes/Yes

32789

BYT4

UDEC

Yes/Yes

32790

BYT4

SDEC

Yes/Yes

991

PLC Connection Guide

ID No.

Data Length

Data Type

Write / Read

Decimal Place*

32791

BYT4

UDEC

Yes/Yes

32792

BYT4

SDEC

Yes/Yes

32793

BYT4

UDEC

Yes/Yes

32794

BYT4

SDEC

Yes/Yes

32797

BYT4

HEX

No/Yes

Hex

32798

BYT4

HEX

No/No

Hex

32799

BYT4

HEX

No/No

Hex

32800

BYT4

HEX

Yes/Yes

Hex

32801

BYT4

HEX

Yes/Yes

Hex

32802

BYT4

HEX

Yes/Yes

Hex

32803

BYT4

HEX

Yes/Yes

Hex

32804

BYT4

HEX

Yes/Yes

Hex

32805

BYT4

HEX

Yes/Yes

Hex

32806

BYT4

UDEC

Yes/Yes

32807

BYT4

UDEC

Yes/Yes

32808

BYT4

UDEC

Yes/Yes

32809

BYT4

UDEC

Yes/Yes

32836

BYT2

UDEC

No/Yes

32845

BYT2

UDEC

Yes/Yes

32846

BYT2

SDEC

Yes/Yes

32847

BYT2

SDEC

Yes/Yes

32848

BYT2

UDEC

Yes/Yes

32849

BYT2

SDEC

Yes/Yes

32850

BYT2

SDEC

Yes/Yes

32851

BYT2

SDEC

Yes/Yes

32852

BYT2

SDEC

Yes/Yes

32853

BYT2

SDEC

Yes/Yes

32854

BYT2

SDEC

Yes/Yes

32865

BYT2

UDEC

Yes/Yes

32866

BYT2

UDEC

Yes/Yes

32867

BYT2

UDEC

Yes/Yes

32868

BYT2

UDEC

Yes/Yes

32874

BYT2

UDEC

Yes/Yes

32875

BYT2

UDEC

Yes/Yes

992

PLC Connection Guide

ID No.

Data Length

Data Type

Write / Read

Decimal Place*

32876

BYT2

UDEC

Yes/Yes

32877

BYT2

UDEC

Yes/Yes

32880

BYT2

UDEC

Yes/Yes

32881

BYT2

UDEC

Yes/Yes

32882

BYT2

UDEC

Yes/Yes

32883

BYT2

UDEC

Yes/Yes

32891

BYT2

UDEC

Yes/Yes

32892

BYT4

UDEC

Yes/Yes

32893

BYT4

UDEC

Yes/Yes

32922

BYT2

UDEC

Yes/Yes

32925

BYT2

HEX

Yes/Yes

Hex

32926

BYT2

HEX

Yes/Yes

Hex

32927

BYT2

HEX

Yes/Yes

Hex

32928

BYT2

UDEC

Yes/Yes

0.1

32929

BYT2

UDEC

Yes/Yes

0.1

32934

BYT2

UDEC

Yes/Yes

32935

BYT2

UDEC

Yes/Yes

0.1

32936

BYT4

HEX

Yes/Yes

Hex

32940

BYT4

SDEC

Yes/Yes

32947

BYT4

UDEC

Yes/Yes

32952

BYT4

UDEC

Yes/Yes

32953

BYT2

HEX

Yes/Yes

Hex

32956

BYT2

UDEC

Yes/Yes

32958

BYT2

UDEC

Yes/Yes

32959

BYT2

UDEC

Yes/Yes

32964

BYT2

UDEC

Yes/Yes

32966

BYT2

SDEC

Yes/Yes

32967

BYT2

UDEC

Yes/Yes

32968

BYT2

UDEC

Yes/Yes

0.1

32978

BYT2

UDEC

Yes/Yes

32979

BYT2

UDEC

Yes/Yes

32980

BYT2

UDEC

Yes/Yes

32981

BYT2

UDEC

Yes/Yes

32992

BYT2

UDEC

Yes/Yes

0.1

993

PLC Connection Guide

ID No.

Data Length

Data Type

Write / Read

Decimal Place*

32993

BYT2

UDEC

Yes/Yes

0.1

33700

BYT2

UDEC

Yes/Yes

33701

BYT2

UDEC

Yes/Yes

33702

BYT2

UDEC

Yes/Yes

33703

BYT2

UDEC

Yes/Yes

33704

BYT2

UDEC

Yes/Yes

33705

BYT2

UDEC

Yes/Yes

33706

BYT2

UDEC

Yes/Yes

33707

BYT2

UDEC

Yes/Yes

33708

BYT2

UDEC

Yes/Yes

33709

BYT2

UDEC

Yes/Yes

33710

BYT2

UDEC

Yes/Yes

33711

BYT2

UDEC

Yes/Yes

33712

BYT2

UDEC

Yes/Yes

33713

BYT2

UDEC

Yes/Yes

33714

BYT2

UDEC

Yes/Yes

33721

BYT2

UDEC

Yes/Yes

33722

BYT2

UDEC

Yes/Yes

33724

BYT2

UDEC

Yes/Yes

33725

BYT2

UDEC

Yes/Yes

33729

BYT2

UDEC

Yes/Yes

33730

BYT2

UDEC

Yes/Yes

33731

BYT2

UDEC

Yes/Yes

33732

BYT2

UDEC

No/Yes

33800

BYT2

UDEC

Yes/Yes

33801

BYT2

UDEC

Yes/Yes

33802

BYT2

UDEC

Yes/Yes

33803

BYT2

UDEC

Yes/Yes

33804

BYT2

UDEC

Yes/Yes

33805

BYT2

UDEC

Yes/Yes

33806

BYT2

UDEC

Yes/Yes

33807

BYT2

UDEC

Yes/Yes

33808

BYT2

UDEC

Yes/Yes

33809

BYT2

UDEC

Yes/Yes

994

PLC Connection Guide

ID No.

Data Length

Data Type

Write / Read

Decimal Place*

33810

BYT2

UDEC

Yes/Yes

33811

BYT2

UDEC

Yes/Yes

33812

BYT2

UDEC

Yes/Yes

33813

BYT2

UDEC

Yes/Yes

33814

BYT2

UDEC

Yes/Yes

33815

BYT2

UDEC

Yes/Yes

33816

BYT2

UDEC

Yes/Yes

33817

BYT2

UDEC

Yes/Yes

33818

BYT2

UDEC

Yes/Yes

33819

BYT2

UDEC

Yes/Yes

33820

BYT2

UDEC

Yes/Yes

33839

BYT2

UDEC

Yes/Yes

33840

BYT2

UDEC

Yes/Yes

33859

BYT2

UDEC

Yes/Yes

33860

BYT2

UDEC

Yes/Yes

33869

BYT2

UDEC

Yes/Yes

33880

BYT2

UDEC

Yes/Yes

33889

BYT2

UDEC

Yes/Yes

33890

BYT2

UDEC

Yes/Yes

33899

BYT2

UDEC

Yes/Yes

34000

BYT2

UDEC

Yes/Yes

34001

BYT2

UDEC

Yes/Yes

34002

BYT2

UDEC

Yes/Yes

34003

BYT2

UDEC

Yes/Yes

34004

BYT2

UDEC

Yes/Yes

34005

BYT2

UDEC

Yes/Yes

34006

BYT2

UDEC

Yes/Yes

34007

BYT2

UDEC

Yes/Yes

34008

BYT2

UDEC

Yes/Yes

34009

BYT2

UDEC

Yes/Yes

34010

BYT2

UDEC

Yes/Yes

34011

BYT2

UDEC

Yes/Yes

34012

BYT2

UDEC

Yes/Yes

34013

BYT2

UDEC

Yes/Yes

995

PLC Connection Guide

ID No.

Data Length

Data Type

Write / Read

Decimal Place*

34014

BYT2

UDEC

Yes/Yes

34015

BYT2

UDEC

Yes/Yes

34016

BYT2

UDEC

Yes/Yes

34017

BYT2

UDEC

Yes/Yes

34018

BYT2

UDEC

Yes/Yes

34019

BYT2

UDEC

Yes/Yes

34023

BYT2

UDEC

Yes/Yes

34025

BYT2

UDEC

Yes/Yes

34042

BYT2

UDEC

Yes/Yes

34043

BYT2

UDEC

Yes/Yes

0.01

34044

BYT2

UDEC

Yes/Yes

0.01

34045

BYT2

UDEC

Yes/Yes

0.01

34046

BYT2

UDEC

Yes/Yes

0.01

34047

BYT2

UDEC

Yes/Yes

0.01

34048

BYT2

UDEC

Yes/Yes

0.01

34049

BYT2

UDEC

Yes/Yes

0.01

34050

BYT2

UDEC

Yes/Yes

0.1

34051

BYT2

UDEC

Yes/Yes

0.01

34052

BYT2

UDEC

Yes/Yes

0.1

34053

BYT2

UDEC

Yes/Yes

34054

BYT2

UDEC

Yes/Yes

0.1

34055

BYT2

UDEC

Yes/Yes

0.1

34056

BYT2

UDEC

Yes/Yes

34070

BYT2

UDEC

Yes/Yes

34148

BYT2

UDEC

Yes/Yes

0.001

34149

BYT2

UDEC

Yes/Yes

0.1

34164

BYT2

UDEC

Yes/Yes

0.01

34167

BYT2

UDEC

Yes/Yes

0.01

34177

BYT2

UDEC

Yes/Yes

34178

BYT2

UDEC

Yes/Yes

34179

BYT2

UDEC

Yes/Yes

34180

BYT2

UDEC

Yes/Yes

34182

BYT4

SDEC

Yes/Yes

35000

/* Depends on Text */ 0

ASCI

No/Yes

ASCII

996

PLC Connection Guide

ID No.

Data Length

Data Type

Write / Read

Decimal Place*

35001

/* Depends on Text */ 0

ASCI

No/Yes

ASCII

35002

BYT4

HEX

No/Yes

35003

BYT2

HEX

No/Yes

Hex

35004

BYT2

UDEC

No/Yes

0.1

35005

BYT2

UDEC

No/Yes

0.1

35006

BYT2

UDEC

No/Yes

0.1

35007

BYT2

UDEC

No/Yes

0.1

35008

BYT2

UDEC

No/Yes

0.1

35009

BYT2

UDEC

No/Yes

0.1

35010

BYT2

UDEC

No/Yes

0.1

35011

BYT2

UDEC

No/Yes

36000

BYT2

UDEC

No/Yes

36001

BYT2

UDEC

No/Yes

36002

BYT4

SDEC

No/Yes

36003

BYT4

SDEC

No/Yes

36004

BYT4

UDEC

No/Yes

36005

BYT4

UDEC

No/Yes

36006

BYT2

UDEC

No/Yes

36007

BYT2

UDEC

No/Yes

36008

BYT2

UDEC

No/Yes

36009

BYT2

UDEC

No/Yes

36010

BYT2

UDEC

No/Yes

36011

BYT2

UDEC

No/Yes

36012

BYT4

UDEC

No/Yes

36013

BYT4

UDEC

No/Yes

36019

BYT2

UDEC

Yes/Yes

36020

BYT2

UDEC

Yes/Yes

36021

BYT2

UDEC

Yes/Yes

36022

BYT2

UDEC

Yes/Yes

36023

BYT2

UDEC

Yes/Yes

36100

BYT4

UDEC

Yes/Yes

36101

BYT4

UDEC

Yes/Yes

36102

BYT4

UDEC

Yes/Yes

36103

BYT4

UDEC

Yes/Yes

997

PLC Connection Guide

ID No.

Data Length

Data Type

Write / Read

Decimal Place*

36104

BYT4

UDEC

Yes/Yes

*Note: If the decimal place of ID is 0.0001, please set [Right of decimal Pt.] of the object to
4.

Wiring Diagram:
The following is the view from the soldering point of a cable.
RS-232
eMT3000 series
COM1 RS232 9P

COM3 RS232 9P

X5 Port RS232 9P

D-Sub Female

D-Sub Female

D-Sub Male

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

X5 Port RS232 9P
D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

X5 Port RS232 9P
D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

998

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

X5 Port RS232 9P
D-Sub Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

X5 Port RS232 9P
D-Sub Male

9 RX

2 TX

6 TX

3 RX

5 GND

5 GND

The following is the view from the soldering point of a cable.


RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

X5 Port RS485 2W 9P
D-Sub Male

1 RX-

6 Data-

4 RS485-

2 RX+

9 Data+

1 RS485+

5 GND

5 GND

5 GND

COM2 RS485 2W

COM3 RS485 2W

X5 Port RS485 2W 9P

9P D-Sub Female

9P D-Sub Female

D-Sub Male

7 RX-

4 Data-

4 RS485-

6 RX+

1 Data+

1 RS485+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

X5 Port RS485 2W 9P
D-Sub Male

1 RX-

7 Data-

4 RS485-

2 RX+

8 Data+

1 RS485+

5 GND

9 GND

5 GND

999

PLC Connection Guide

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

X5 Port RS485 2W 9P
D-Sub Male

1 RX-

6 Data-

4 RS485-

2 RX+

9 Data+

1 RS485+

5 GND

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

X5 Port RS485 2W 9P
D-Sub Male

1 RX-

6 Data-

4 RS485-

2 RX+

9 Data+

1 RS485+

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

X5 Port RS485 2W 9P
D-Sub Male

1 RX-

7 Data-

4 RS485-

2 RX+

8 Data+

1 RS485+

5 GND

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Mar/27/2012

Driver released.

V1.10

Jul/20/2012

The newly supported software SSTS_PAS_V2.3 supports ID


address.

1000

PLC Connection Guide

TECHSOFT Intelligent Servo


Supported Series: Intelligent Servo supports IDM640, IDM240.
Website: http://www.techsoftmotion.com

HMI Setting:
Parameters

Recommended

Options

PLC type

Intelligent Servo

PLC I/F

RS232

Baud rate

9600

9600~115200

Data bits

7 or 8

Parity

None

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

Register_32bit

HHHH

0 ~ 270f

32bit signed

DW

Register_H

HHHH

0 ~ 270f

32bit Hex

UPD

HHHHH

0 ~ 1869f

Send UDP command

STOP

HHHHH

0 ~ 1869f

Send STOP command

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

Servo RS232 D-Sub


Male

2 RX

8 RX

2 TD

3 TX

7 TX

3 RD

5 GND

5 GND

5 GND

1001

PLC Connection Guide

cMT/mTV series
COM1 RS232 9P
D-Sub Female

Servo RS232 D-Sub


Male

2 RX

2 TD

3 TX

3 RD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

Servo RS232 D-Sub


Male

2 RX

2 TD

3 TX

3 RD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

Servo RS232 D-Sub


Male

2 RX

6 RX

8 RX

2 TD

3 TX

4 TX

7 TX

3 RD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

Servo RS232 D-Sub


Male

9 RX

2 TD

6 TX

3 RD

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Nov/06/2009

Driver released.

1002

PLC Connection Guide

TECO Inverter
Supported Series: TECO Inverter series, 7300CV model.

HMI Setting:
Parameters

Recommended

PLC type

TECO Inverter

PLC I/F

RS232

Baud rate

38400

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

RS232/RS485

Device Address:
Bit/Word Device type Format

Range

Memo

0x

DDDDD

1 ~ 65535

Output Bit

1x

DDDDD

1 ~ 65535

Input Bit (read only)

3x_Bit

DDDDDdd 100 ~ 6553515

Input Register Bit (read only)

4x_Bit

DDDDDdd 100 ~ 6553515

Output Register Bit

6x_Bit

DDDDDdd 100 ~ 6553515

0x (0x0f)

DDDDD

1 ~ 65535

Write Multiple Coils

3x

DDDDD

1 ~ 65535

Input Register (read only)

4x

DDDDD

1 ~ 65535

Output Register

DW

5x

DDDDD

1 ~ 65535

4x Double Word Swap

6x

DDDDD

1 ~ 65535

4x Single Word Write

1003

PLC Connection Guide

Wiring Diagram:

The following is the view from the soldering point of a cable.


9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

7 RTS

7 VCC

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

7 RTS

7 VCC

1004

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

5 GND

7 RTS

7 VCC

Driver Version:
Version

Date

Description

V1.00

Jul/27/2009

Driver released.

1005

PLC Connection Guide

TECO TP02 Series


Supported Series: TAIAN TP02 series
Website: http://www.taian-technology.com

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

TECO TP02 Series

PLC I/F

RS485 4W/2W

RS485 4W/2W

MMI 422 port: 4W; RS485


terminals: 2W

Baud rate

19200

9600, 19200, 38400

Data bits

7, 8

Parity

Even

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

0-255

PLC Setting:
RS422 port: WS041=120, WS042=1;
RS485 terminals: WS044=120, WS045=1.

Device Address:
Bit/Word
B

Device type
X

Format
DDD

Range
1 ~ 384

Memo
Input relay

DDD

1 ~ 384

Output relay

DDDD

1 ~ 2048

Auxiliary relay

DDD

1 ~ 369

DDD

1 ~ 369

W
W

DDDD

1 ~ 1024

Input register (must be 1 or a


multiple of plus 1)
Output register (must be 1 or
a multiple of plus 1)
Auxiliary register

DDDD

1 ~ 2048

Auxiliary register

WS

DDD

1 ~ 128

System register

DDDD

1 ~ 2033

WC

DDD

1 ~ 912
1006

Auxiliary relay register (must


be 1 or a multiple of plus 1)
Constant register

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
TP02 Series MMI RS422 port : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

8 TX-

2 RX+

3 TX+

3 TX-

7 RX-

4 TX+

2 RX+

5 GND
cMT/mTV series
COM2 RS485 4W

RS485 4W 9P D-Sub

9P D-Sub Female

Male

7 RX-

8 TX-

6 RX+

3 TX+

9 TX-

7 RX-

8 TX+

2 RX+

5 GND
MT8000iE/MT8000XE series except MT8050iE
COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

8 TX-

2 RX+

2 RX+

3 TX+

3 TX-

3 TX-

7 RX-

4 TX+

4 TX+

2 RX+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

8 TX-

2 RX+

3 TX+

3 TX-

7 RX-

4 TX+

2 RX+

5 GND

1007

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

1 RX-

8 TX-

2 RX+

3 TX+

3 TX-

7 RX-

4 TX+

2 RX+

5 GND

The following is the view from the soldering point of a cable.


TP02 Series RS485 Terminal : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

T/R-

2 RX+

9 Data+

T/R+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W Terminal

7 RX-

4 Data-

T/R-

6 RX+

1 Data+

T/R+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

7 Data-

T/R-

2 RX+

8 Data+

T/R+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

T/R-

2 RX+

9 Data+

T/R+

5 GND

5 GND
1008

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

T/R-

2 RX+

9 Data+

T/R+

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W Terminal

1 RX-

7 Data-

T/R-

2 RX+

8 Data+

T/R+

5 GND

5 GND

Driver Version:
Version

Date

V1.10

Jan/25/2010

Description

1009

PLC Connection Guide

TECO TP03 Series/AP-360BT-A


Supported Series: TECO TP03 Series/AP-360BT-A
Website: http://www.teco.com.tw/sa/en/

HMI Setting:
Parameters

Recommended

Options

PLC type

TECO TP03 Series/AP-360BT-A

PLC I/F

RS485 4W

Baud rate

19200

9600, 19200

Data bits

Parity

None

Even, Odd, None

Stop bits

PLC sta. no.

1-255

Notes

Device Address:
Bit/Word
B

Device type
C

Format
DDDD

Range
0 ~ 9999

C256

DDDD

256 ~ 9999

DDDD

0 ~ 9999

DDDD

0 ~ 9999

DDDD

0 ~ 9999

OOO

0 ~ 377

B
W

OOO

0 ~ 377

DDDD

0 ~ 9999

DDDD

0 ~ 9999

DDDD

0 ~ 9999

T_Curent

DDDD

0 ~ 9999

C_Curent

DDDD

0 ~ 9999

T_Preset

DDDD

0 ~ 9999

C_Preset

DDDD

0 ~ 9999

DW

C200_Curent DDDD
C200_Preset DDDD

200 ~ 9999

C256_Curent DDDD
C256_Preset DDDD

256 ~ 9999

DW
DW
DW

200 ~ 9999
256 ~ 9999
1010

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 8P Mini-DIN
Male

1 RX-

4 TX-

2 RX+

7 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

3 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 8P Mini-DIN
Male

7 RX-

4 TX-

6 RX+

7 TX+

9 TX-

1 RX-

8 TX+

2 RX+

5 GND

3 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 8P Mini-DIN
Male

1 RX-

1 RX-

4 TX-

2 RX+

2 RX+

7 TX+

3 TX-

3 TX-

1 RX-

4 TX+

4 TX+

2 RX+

5 GND

5 GND

3 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 8P Mini-DIN
Male

1 RX-

4 TX-

2 RX+

7 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

3 GND

1011

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 8P Mini-DIN
Male

1 RX-

4 TX-

2 RX+

7 TX+

3 TX-

1 RX-

4 TX+

2 RX+

5 GND

3 GND
View from the
soldering point
of a cable.

Driver Version:
Version

Date

V1.10

Nov/13/2009

V1.20

Sep/18/2015

Description
Added register: C256/ C200_Curent/ C200_Preset/
C256_Curent/ C256_Preset

1012

PLC Connection Guide

TINHAO
Website: www.chinastrand.com

HMI Setting:
Parameters

Recommended

PLC type

TINHAO

PLC I/F

RS485 2W

Baud rate

19200

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

Device Address:
Bit/Word Device type

Format

Range

Commend1

DDD

0 ~ 255

Commend2

DDD

0 ~ 255

Commend3

DDD

0 ~ 255

Commend4

DDD

0 ~ 255

Commend5

DDD

0 ~ 255

Commend6

DDD

0 ~ 255

Commend7

DDD

0 ~ 255

Commend8

DDD

0 ~ 255

Commend9

DDD

0 ~ 255

Commend10

DDD

0 ~ 255

Commend11

DDD

0 ~ 255

Commend12

DDD

0 ~ 255

Commend13

DDD

0 ~ 255

Commend14

DDD

0 ~ 255

Commend15

DDD

0 ~ 255

Commend16

DDD

0 ~ 255

Commend17

DDD

0 ~ 255

Commend18

DDD

0 ~ 255
1013

Memo

PLC Connection Guide

Bit/Word Device type

Format

Range

Commend19

DDD

0 ~ 255

Commend20

DDD

0 ~ 255

Commend21

DDD

0 ~ 255

Commend22

DDD

0 ~ 255

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W

COM3 RS485 2W

RS485 terminal

9P D-Sub Female

9P D-Sub Female

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

1014

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Oct/14/2011

Driver released.

1015

PLC Connection Guide

Toptek Topvert
Supported Series: TOPVERT G1/H1/P1 series.
Website: http://www.toptek.biz/

HMI Setting:
Parameters

Recommended

PLC type

Toptek Topvert

PLC I/F

RS485 2W

Baud rate

9600

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

Online simulator

YES

Broadcast command

YES

Extend address mode

YES

Broadcast station no.

PLC Setting:
Communication mode

Pr 7-15 = 0 (7, N, 2 ASCII)

Device Address:
Bit/Word

Device type

Format

Range

PR_Bit

DDDDDdd

G=Groups, F=Function no.


0 ~ 6553515 dd=0~15 bit no.

PR

DDDDD

0 ~ 65535

1016

Memo

G=Groups, F=Function no.

PLC Connection Guide

Note:
Max.read-command size (words): 16
Max.write-command size (words): 1
For G1/H1/P1 Series Inverter, if standard parameter address is in decimal= 100*G+F:
G=Group (parameter group code0~9); F=Function no. (parameter number 0~99)
For example: Pr5-20 (decimal Dec.) parameter address is expressed as 100*5+20=520.
Parameter (PrX-XX)

Address (decimal)

0-00

0*100+0=0

0-14

0*100+14=14

1-00

1*100+0=100

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W

COM3 RS485 2W

RS485 2W Terminal

9P D-Sub Male

9P D-Sub Male

1 RX-

6 Data-

SG-

2 RX+

9 Data+

SG+

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W Terminal

7 RX-

4 Data-

SG-

6 RX+

1 Data+

SG+

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

7 Data-

SG-

2 RX+

8 Data+

SG+

5 GND

9 GND

1017

PLC Connection Guide

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

SG-

2 RX+

9 Data+

SG+

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W Terminal

1 RX-

6 Data-

SG-

2 RX+

9 Data+

SG+

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W Terminal

1 RX-

7 Data-

SG-

2 RX+

8 Data+

SG+

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.00

Dec/08/2010

Driver released.

1018

PLC Connection Guide

TOSHIBA INVERTER VF
Supported Series: Toshiba Invertor Protocol (ASCII code).

HMI Setting:
Parameters

Recommended

PLC type

TOSHIBA INVERTER VF

PLC I/F

RS485 2W

RS422, RS485

Baud rate

9600

9600, 19200

Data bits

7 or 8

Parity

Even

Even, Odd, None

Stop bits

1 or 2

PLC sta. no.

0-99

Online simulator

YES

Options

Notes

Extend address mode YES

Broadcast command YES

Device Address:
Bit/Word Device type

Format

Range

Cmd. No B

HHHHdd

0 ~ 270f15

Cmd. No

HHHH

0 ~ ffff

Memo
Parameters and data memory

Wiring Diagram:
Note:
Before connecting with TOSHIBA INVERTER VF, make sure the SW1 of both sides are in
the correct position. (SW1: wiring method selector switch)

1019

PLC Connection Guide

RS-485
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45
Male

1 RX-

6 Data-

5 Data-

2 RX+

9 Data+

4 Data+

5 GND

5 GND

8 Gnd

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P RJ45
Male

7 RX-

4 Data-

5 Data-

6 RX+

1 Data+

4 Data+

5 GND

5 GND

8 Gnd

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45
Male

1 RX-

7 Data-

5 Data-

2 RX+

8 Data+

4 Data+

5 GND

9 GND

8 Gnd
1020

PLC Connection Guide

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45
Male

1 RX-

6 Data-

5 Data-

2 RX+

9 Data+

4 Data+

5 GND

5 GND

8 Gnd

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 8P RJ45
Male

1 RX-

6 Data-

5 Data-

2 RX+

9 Data+

4 Data+

5 GND

5 GND

8 Gnd

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 8P RJ45
Male

1 RX-

7 Data-

5 Data-

2 RX+

8 Data+

4 Data+

5 GND

5 GND

8 Gnd

Driver Version:
Version

Date

V1.20

Apr/03/2013

Description
TOSHIBA VF-S11 driver is renamed to TOSHIBA
INVERTER VF.

1021

PLC Connection Guide

TOSHIBA T Series
Supported Series: Toshiba T series, S2E.
Website: http://www.tic.toshiba.com

HMI Setting:
Parameters

Recommended Options

PLC type

TOSHIBA T Series

PLC I/F

RS232

RS232/RS485

Baud rate

9600

9600, 19200, 38400,


57600, 115200

Data bits

7,8

Parity

Odd

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

0-255

Online simulator

YES

Notes
In accordance with PLC port

Must be same as the PLC setting

Extend address mode YES

PLC Setting:
Communication mode

Must set PLC node ID

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDh

0 ~ 4095f

Input Bit

DDDDh

0 ~ 4095f

Output Bit

DDDDh

0 ~ 8191f

Auxiliary Bit

DDDDh

0 ~ 4095f

Special Bit

DDDDh

0 ~ 4095f

DDDDh

0 ~ 8191f

DDD

0 ~ 999

Timer Register

DDD

0 ~ 511

Counter Register

DDDD

0 ~ 8191

Data Memory

SW

DDD

0 ~ 255

Special Register

XW

DDD

0 ~ 255

Input Register

1022

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

YW

DDD

0 ~ 255

Output Register

RW

DDD

0 ~ 999

Auxiliary Register

LW

DDD

0 ~ 255

DDDD

0 ~ 1023

DDDD

0 ~ 8191

Wiring Diagram:
The following is the view from the soldering point of a cable.
Toshiba T1 PRG RS232 : 9P D-Sub to 8P Mini- DIN
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

8 RX

6 TXD

3 TX

7 TX

8 RXD

5 GND

5 GND

5 GND
4 RTS
7 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

6 TXD

3 TX

8 RXD

5 GND

5 GND
4 RTS
7 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

6 TXD

3 TX

8 RXD

5 GND

5 GND
4 RTS
7 CTS

1023

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 8P Mini-DIN
Male

2 RX

6 RX

8 RX

6 TXD

3 TX

4 TX

7 TX

8 RXD

5 GND

5 GND

5 GND

5 GND
4 RTS
7 CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

9 RX

6 TXD

6 TX

8 RXD

5 GND

5 GND
4 RTS
7 CTS

short
View from the
soldering point
of a cable.

The following is the view from the soldering point of a cable.


Toshiba T2 PRG RS232 : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS
1024

short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

1025

short

PLC Connection Guide

The following is the view from the soldering point of a cable.


Toshiba T2 LINK Port RS485 4W : 9P D-Sub to 15P D-Sub
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 15P D-Sub


Male

1 RX-

11 TXB

2 RX+

3 TXA

3 TX-

10 RXB

4 TX+

2 RXA

5 GND

7 SG
5 RTSA
4 CTSA
13 RTSB
12 CTSB

short
short

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 15P D-Sub


Male

7 RX-

11 TXB

6 RX+

3 TXA

9 TX-

10 RXB

8 TX+

2 RXA

5 GND

7 SG
5 RTSA
4 CTSA
13 RTSB
12 CTSB

short
short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 15P D-Sub


Male

1 RX-

1 RX-

11 TXB

2 RX+

2 RX+

3 TXA

3 TX-

3 TX-

10 RXB

4 TX+

4 TX+

2 RXA

5 GND

5 GND

7 SG
5 RTSA
4 CTSA
13 RTSB
12 CTSB
1026

short
short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 15P D-Sub


Male

1 RX-

11 TXB

2 RX+

3 TXA

3 TX-

10 RXB

4 TX+

2 RXA

5 GND

7 SG
5 RTSA
4 CTSA
13 RTSB
12 CTSB

short
short

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 15P D-Sub


Male

1 RX-

11 TXB

2 RX+

3 TXA

3 TX-

10 RXB

4 TX+

2 RXA

5 GND

7 SG
5 RTSA
4 CTSA
13 RTSB
12 CTSB

short
short

Driver Version:
Version

Date

Description

V1.20

May/13/2011

TOSHIBA T Series driver can now correctly read and write


L, LW, F address types.

1027

PLC Connection Guide

TOSHIBA MACHINE Provisor TC200


Supported Series: TOSHIBA MACHINE CO., JAPAN
WebSite: http://www.toshiba-machine.co.jp

HMI Setting:
Parameters

Recommended Options

PLC type

TOSHIBA MACHINE Provisor TC200

PLC I/F

RS232

RS232

Baud rate

9600

9600, 19200

Data bits

7,8

Parity

None

Even, Odd, None

Stop bits

1, 2

Notes
In accordance with PLC port

Device Address:
Bit/Word

Device type Format

Range

Memo

R_bit

HHHh

0 ~ ffff

h : Bit no.(0~f)

X_bit

HHHh

0 ~ ffff

h : Bit no.(0~f)

Y_bit

HHHh

0 ~ ffff

h : Bit no.(0~f)

L_bit

HHHh

0 ~ ffff

h : Bit no.(0~f)

G_bit

HHHh

0 ~ ffff

h : Bit no.(0~f)

H_bit

HHHh

0 ~ ffff

h : Bit no.(0~f)

T_bit

HHHh

0 ~ ffff

h : Bit no.(0~f)

C_bit

HHHh

0 ~ ffff

h : Bit no.(0~f)

S_bit

HHHh

0 ~ ffff

h : Bit no.(0~f)

E_bit

HHHh

0 ~ ffff

h : Bit no.(0~f)

HHH

0 ~ fff

HHH

0 ~ fff

HHH

0 ~ fff

HHH

0 ~ fff

HHH

0 ~ fff

HHH

0 ~ fff

HHH

0 ~ fff

HHH

0 ~ fff

HHH

0 ~ fff
1028

PLC Connection Guide

Bit/Word

Device type Format

Range

HHH

0 ~ fff

HHH

0 ~ fff

HHH

0 ~ fff

HHH

0 ~ fff

HHH

0 ~ fff

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

TC mini series RS232


9P D-Sub Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

TC mini series RS232


9P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

TC mini series RS232


9P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

1029

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

TC mini series RS232


9P D-Sub Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

TC mini series RS232


9P D-Sub Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

Driver Version:
Version

Date

Description

V1.10

Aug/17/2012

Added register: B,G,H,T,C,S,F.

1030

short

PLC Connection Guide

Trio MODBUS RTU, TCP/IP


Website : http://www.triomotion.com

HMI Setting:
Parameters

Recommended

PLC type

Trio MODBUS RTU, TCP/IP

PLC I/F

RS485

RS232/RS485/Ethernet

Baud rate

9600

9600~115200

Data bits

7, 8

Parity

Even

Even, Odd, None

Stop bits

1, 2

Port no.

502

PLC sta. no.

Online simulator

Options

Notes

0-255
YES

Broadcast command YES

Extend address mode YES

PLC Setting:
Communication mode

Modbus RTU protocol

PLC mode

4 (16bit signed integer)

Device Address:
Bit/Word
B

Device type
VR_Bit

Format

Range

DDDDdd

0 ~ 409615

Table_Bit

DDDDDdd

0 ~ 3199915

W
W

VR
Table

DDDD

0 ~ 4096

DDDDD

0 ~ 31999

1031

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.3
Trio : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND
RTS
CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND
RTS
CTS

1032

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

TXD

6 TX

RXD

5 GND

GND
RTS
CTS

short

The following is the view from the soldering point of a cable.


Trio : RS485 4W
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND
1033

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

The following is the view from the soldering point of a cable.


Trio : RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

cMT/mTV series

1034

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

1035

PLC Connection Guide

Etehernet cable:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

May/27/2011

Driver released.

V1.20

Oct/29/2014

Device types VR is extended to 4096.

1036

PLC Connection Guide

Trio MODBUS RTU, TCP/IP (Mode 7)


Website : http://www.triomotion.com

HMI Setting:
Parameters

Recommended

PLC type

Trio MODBUS RTU, TCP/IP (Mode 7)

PLC I/F

RS485

RS232/RS485/Ethernet

Baud rate

9600

9600~115200

Data bits

7, 8

Parity

Even

Even, Odd, None

Stop bits

1, 2

Port no.

502

PLC sta. no.

Online simulator

Options

Notes

0-255
YES

Broadcast command YES

Extend address mode YES

PLC Setting:
Communication mode

Modbus RTU protocol

PLC mode

7 (IEEE floating point)

Device Address:
Bit/Word
B

Device type
VR_Bit

Format

Range

DDDDdd

0 ~ 409631

VR_INT_Bit

DDDDdd

0 ~ 409631

Table_Bit

DDDDDdd

0 ~ 3199931

VR

DDDD

0 ~ 4096

W
W

VR_INT
Table

DDDD

0 ~ 4096

DDDDD

0 ~ 31999

Table_INT

DDDDD

0 ~ 31999

1037

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.3
Trio : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

TXD

3 TX

7 TX

RXD

5 GND

5 GND

GND
RTS
CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

TXD

3 TX

RXD

5 GND

GND
RTS
CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

TXD

3 TX

4 TX

7 TX

RXD

5 GND

5 GND

5 GND

GND
RTS
CTS

1038

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

TXD

6 TX

RXD

5 GND

GND
RTS
CTS

short

The following is the view from the soldering point of a cable.


Trio : RS485 4W
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

GND
1039

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 9P D-Sub
Male

1 RX-

TX-

2 RX+

TX+

3 TX-

RX-

4 TX+

RX+

5 GND

GND

The following is the view from the soldering point of a cable.


Trio : RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

GND

cMT/mTV series

1040

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

GND

1041

PLC Connection Guide

Ethernet cable:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Apr/20/2012

Driver released.

V1.30

Oct/29/2014

Device types VR is extended to 4096.

1042

PLC Connection Guide

VIGOR
Supported Series: VIGOR M Series, VB Series, VH Series.
Website: http://www.vigorplc.com.tw/

HMI Setting:
Parameters

Recommended

PLC type

VIGOR

PLC I/F

RS485 2W

Baud rate

19200

Data bits

Parity

None

Stop bits

PLC sta. no.

Options

Notes

RS232, RS485 4W
Select "7' for V1.10 and
previous versions.
Select "Even" for V1.10 and
previous versions.

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

OOO

0 ~ 377

OOO

0 ~ 377

DDDD

0 ~ 7999

DDD

0 ~ 255

DDD

0 ~ 255

SM

DDDD

9000 ~ 9255

DDD

0 ~ 999

TV

DDD

0 ~ 255

CV

DDD

0 ~ 199

DDDD

0 ~ 9255

CV2

DDD

200 ~ 255

SD

DDDD

9000 ~ 9255

1043

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 6P Terminal

1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series

TXTX+
RXRX+
SG

COM2 RS485 4W
9P D-Sub Female

RS485 4W 6P Terminal

7 RX-

TX-

6 RX+

TX+

9 TX-

RX-

8 TX+

RX+

5 GND

SG

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 6P Terminal

1 RX-

1 RX-

TX-

2 RX+

2 RX+

TX+

3 TX-

3 TX-

RX-

4 TX+

4 TX+

RX+

5 GND

5 GND

SG

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

RS485 4W 6P Terminal

1 RX2 RX+
3 TX4 TX+
5 GND

TXTX+
RXRX+
SG

1044

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

RS485 4W 6P Terminal

1 RX2 RX+
3 TX4 TX+
5 GND

TXTX+
RXRX+
SG

The following is the view from the soldering point of a cable.


Buy MWPC-200 Vigor VH VB Series PLC Programming Cable.(USB Host<->RS232)
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND

1045

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND

Driver Version:
Version

Date

V1.10

Dec/30/2008

V1.20

Mar/26/2014

Description
1.Added register: S
2.Supports Pass-Through feature.

1046

PLC Connection Guide

VIGOR VS Series
Supported Series: VIGOR VS Series.
Website: http://www.vigorplc.com.tw/

HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

VIGOR VS Series

PLC I/F

RS485 2W

RS232, RS485 2W, USB

Baud rate

19200

300 ~ 115200

Data bits

Parity

None

Stop bits

PLC sta. no.

0 ~ 254

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

OOO

0 ~ 571

OOO

0 ~ 571

DDDD

0 ~ 8191

DDDD

0 ~ 4095

SM

DDDD

9000 ~ 9511

D_Bit

DDDDh

0 ~ 8999f

R_Bit

DDDDDh

0 ~ 25999f

T_Coil

DDD

0 ~ 511

T_Contact

DDD

0 ~ 511

C_Coil

DDD

0 ~ 255

C_Contact

DDD

0 ~ 255

XW

OO

0 ~ 21

YW

OO

0 ~ 21

MW

DDD

0 ~ 511

SW

DDD

0 ~ 255

DDDD

0 ~ 8999
1047

Memo

PLC Connection Guide

Bit/Word

Device type

Format

Range

SD

DDDD

9000 ~ 9511

DDDDD

0 ~ 25999

DDD

0 ~ 511

DDD

0 ~ 199

DW

C_32Bit

DDD

200 ~ 255

Memo

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

CP1 RS485 2W
terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

SG

COM2 RS485 2W

COM3 RS485 2W

CP1 RS485 2W

9P D-Sub Female

9P D-Sub Female

terminal

7 RX-

4 Data-

D-

6 RX+

1 Data+

D+

5 GND

5 GND

SG

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

CP1 RS485 2W
terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

9 GND

SG

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

CP1 RS485 2W
terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

SG

1048

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

CP1 RS485 2W
terminal

1 RX-

6 Data-

D-

2 RX+

9 Data+

D+

5 GND

5 GND

SG

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

CP1 RS485 2W
terminal

1 RX-

7 Data-

D-

2 RX+

8 Data+

D+

5 GND

5 GND

SG

The following is the view from the soldering point of a cable.


eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

CP2 RS232 terminal

2 RX

8 RX

TX

3 TX

7 TX

RX

5 GND

5 GND

SG

cMT/mTV series
COM1 RS232 9P

CP2 RS232 terminal

D-Sub Female
2 RX

TX

3 TX

RX

5 GND

SG

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

CP2 RS232 terminal

2 RX

TX

3 TX

RX

5 GND

SG

1049

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

CP2 RS232 terminal

2 RX

6 RX

8 RX

TX

3 TX

4 TX

7 TX

RX

5 GND

5 GND

5 GND

SG

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

CP2 RS232 terminal

9 RX

TX

6 TX

RX

5 GND

SG

Driver Version:
Version

Date

Description

V1.00

Jul/22/2014

Driver released.

1050

PLC Connection Guide

VIPA 200
HMI Setting:
Parameters

Options

PLC type

Recommend
ed
VIPA 200

PLC I/F

RS485 2w

RS485 2w

Notes

The HMI which has a sticker

Baud rate

9600

9600, 19200, 187.5K

MPI187.5 on the rear cover


supports 187.5K

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

1 ~ 126

Turn around delay (ms)

Reserved 1

30

Online simulator

ACK delay time

YES

Extend address mode NO

Broadcast command NO

PLC Setting:
Communication mode

Set station number to 2

Device Address:
Bit/Word Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

VW_Bit

DDDDDo

0 ~ 102397

V Memory Bit Address

Byte

VB

DDDDD

0 ~ 10239

VW

DDDDD

0 ~ 10239

V Memory

VW_Odd

DDDDD

0 ~ 10239

V Memory

DW

VD

DDDDD

0 ~ 10239

V Memory Double Word

DW

VD_Odd

DDDDD

0 ~ 10239

V Memory Double Word

VW_String

DDDDD

0 ~ 10239

String

1051

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo

VW_String_Odd DDDDD

0 ~ 10239

String

DW

VD_String

DDDDD

0 ~ 10239

String

DW

VD_String_Odd

DDDDD

0 ~ 10239

String

Byte

MB

DDDDD

0 ~ 10239

Byte Memory

MW

DDDDD

0 ~ 10239

Word Memory

DW

MD

DDDDD

0 ~ 10239

Word Memory

MW_Odd

DDDDD

0 ~ 10239

Word Memory

DDD

0 ~ 127

Timer

DDD

0 ~ 127

Counter

Double word and floating point value must use VD device type.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W

COM3 RS485 2W

RS485 2W 9P D-Sub

9P D-Sub Male

9P D-Sub Male

Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

8 D-

6 RX+

1 Data+

3 D+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

9 GND

5 GND

1052

PLC Connection Guide

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

5 GND

5 GND

Driver Version:
Version

Date

V2.30

Aug/17/2009

V2.40

Nov/1/2011

Description
Add device type : MD

1053

PLC Connection Guide

VIPA 200 (VD any address)


HMI Setting:
Parameters

Recommended

Options

PLC type

VIPA 200 (VD any address)

PLC I/F

RS485 2w

Notes

RS485 2w
The HMI which has a sticker

Baud rate

9600

9600, 19200, 187.5K

MPI187.5 on the rear cover


supports 187.5K

Data bits

7,8

Parity

Even

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

1 ~ 126

Turn around delay

Reserved 1

30

Online simulator

ACK delay time

YES

Extend address mode NO

Broadcast command NO

PLC Setting:
Communication mode

Set station number to 2

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

VW_Bit

DDDDDo

0 ~ 102397

V Memory Bit Address

VW

DDDDD

0 ~ 10239

V Memory

DW

VD

DDDDD

0 ~ 10239

V Memory Double Word

VW_String

DDDDD

0 ~ 10239

String

DW

VD_String

DDDDD

0 ~ 10239

String

MW

DDDDD

0 ~ 10239

Word Memory

DDD

0 ~ 127

Timer

1054

PLC Connection Guide

Bit/Word

Device type

Format

Range

Memo

DDD

0 ~ 127

Counter

DW

MD

DDDDD

0 ~ 10239

Word Memory

Double word and floating point value must use VD device type.
VD register can set to any value, not necessarily a multiple of 4.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

8 D-

6 RX+

1 Data+

3 D+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

1055

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.20

Nov/16/2011

Add device type : MD

1056

PLC Connection Guide

VIPA 200, for ex. 214-2BT10 (Ethernet)


HMI Setting:
Parameters

Recommended

Options

PLC type

VIPA 200, for ex. 214-2BT10 (Ethernet)

PLC I/F

Ethernet

Port no.

102

PLC sta. no.

Notes

0-31

Device Address:
Bit/Word

Device type Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

VW_Bit

DDDDDo

0 ~ 102397

V Memory Bit Address

VW

DDDDD

0 ~ 10239

V Memory

DW

VD

DDDDD

0 ~ 10239

V Memory Double Word

VW_String

DDDDD

0 ~ 10239

String

DW

VD_String

DDDDD

0 ~ 10239

String

DW

MD

DDDDD

0 ~ 10239

Word Memory

Double word and floating point value must use VD device type.

1057

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

V1.20

Dec/30/2008

V1.40

Nov/15/2011

Description
Add device type : MD

1058

PLC Connection Guide

VIPA 200/300 MPI


HMI Setting:
Parameters

Recommended

PLC type

VIPA 200/300 MPI

PLC I/F

RS-485 2W

Baud rate

187.5K

Data bits

Parity

Even

Stop bits

PLC sta. no.

Online simulator

Options

Notes

Only HMI with a sticker MPI 187.5K on the


rear cover supports MPI communication.

2 ~ 31
NO

Extend address mode Yes

Broadcast command NO

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

DBnBit
DB0Bit ~

FFFFDDDDo 0 ~ 409699997

Data Register Bit

DDDDDo

0 ~ 655327

Data Register Bit

DB99Bit

IW

DDDD

0 ~ 4095

Input (I)

QW

DDDD

0 ~ 4095

Output (O)

MW

DDDD

0 ~ 4095

Bit Memory

DW

MD

DDDD

0 ~ 4094

Byte

MB

DDDD

0 ~ 4095

Bit Memory Byte

Byte

DBBn

FFFFDDDD

0 ~ 40969999

Data Register

DBn

FFFFDDDD

0 ~ 40969999

Data Register (must be even)

DW

DBDn

FFFFDDDD

0 ~ 40969999

Data Register Double Word

DBn_String

FFFFDDDD

0 ~ 40969999

DW

DBDn_String

FFFFDDDD

0 ~ 40969999

DB0 ~ DB99

DDDDD

0 ~ 65532

Data Register (must be even)

* Double word and floating point value must use DBDn device type.
1059

PLC Connection Guide

Multi-HMIs-Multi-PLCs Communication Setting:

For SIEMENS S7-300 MPI driver in Multi-HMIs-Multi-PLCs communication, [Max. station


no. (MPI network)] parameter must be correctly set. This setting is relevant to the station
no. of the devices, as shown, two HMI (station no. 0, 1) and two PLC (station no. 2, 3) are
in MPI network, Max. Station No. should be set to 3.

1060

PLC Connection Guide

For the effectiveness of communication, users may set PLC device in STEP 7 as shown
below. In Properties MPI / Network Settings, set Highest MPI address to the number
closest to the actual device station number.

Note:
HMI sta. no. can not be the same as PLC sta. no.
Highly recommended that the device station numbers start from 0 sequentially and
correctly set [Max. station no. (MPI network)].
Available for EasyBuilder V4.50 and later.

1061

PLC Connection Guide

How to Import Tag:


SIEMENS STEP 7 program allows building files of user-defined tag (*.dif file and *.AWL
file), and import these files in EasyBuilder8000/EasyBuilderPro -> System Parameter
Settings. The following describes how to build and import these two types of files.
1. Building *.dif File
a In Symbols create user-defined tag.

b Click Export to export the edited file and click Save.

1062

PLC Connection Guide

2. Building *.AWF File


a In Blocks create items as shown below:

b Open LAD/STL, FBD Programming S7 Blocks, click File -> Generate


Source.

c Select Sources as storage path, specify the file name then click OK.

1063

PLC Connection Guide

d Select the objects to be exported then click OK.

e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.

1064

PLC Connection Guide

The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro


System Parameter Settings, by clicking Import Tag.

Tag information successfully imported.

1065

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
S7-200 PPI , S7-300 MPI :RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

7 RX-

4 Data-

8 D-

6 RX+

1 Data+

3 D+

5 GND

5 GND

5 GND

cMT/mTV series

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W

COM3 RS485 2W

RS485 2W 9P D-Sub

9P D-Sub Male

9P D-Sub Male

Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

9 GND

5 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W 9P D-Sub
Male

1 RX-

6 Data-

8 D-

2 RX+

9 Data+

3 D+

5 GND

5 GND

5 GND

1066

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W 9P D-Sub
Male

1 RX-

7 Data-

8 D-

2 RX+

8 Data+

3 D+

5 GND

5 GND

5 GND

Driver Version:
Version

Date

Description

V1.90

May/26/2011

Added registers: MB & DBBn

V2.00

Aug/19d/2011

i Series HMI support Multi HMIs-Multi PLCs


communication.

1067

PLC Connection Guide

VIPA 300
HMI Setting:
Parameters

Recommended Options

PLC type

VIPA 300

PLC I/F

RS232

Baud rate

19200, 38400,
187.5K

Data bits

Parity

Odd

Stop bits

PLC sta. no.

Notes

Must be same as the PLC setting.

9600~187.5K

The HMI which has a sticker MPI187.5


on the rear cover supports 187.5K.

Must be same as the PLC setting.

Device Address:
Bit/Word Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

DBnBit

FFFFDDDDo

0 ~ 409681927

Data Register Bit

DB0Bit ~
DB99Bit

DDDDo

0 ~ 81927

IW

DDDD

0 ~ 4095

Input (I)

QW

DDDD

0 ~ 4095

Output (O)

MW

DDDD

0 ~ 4095

Bit Memory

DW

MD

DDDD

0 ~ 4094

Byte

MB

DDDD

0 ~ 4095

Bit Memory Byte

Byte

DBBn

FFFFDDDD

0 ~ 40968192

Data Register Byte

DBn

FFFFDDDD

0 ~ 40968192

DW

DBDn

FFFFDDDD

0 ~ 40968192

DBn_String

FFFFDDDD

0 ~ 40968192
1068

Data Register
(must be even)
Data Register Double Word
(must be multiple of 4)
Data Register Double Word
(must be multiple of 4)

PLC Connection Guide

Bit/Word Device type

Format

Range

DW

DBDn_String FFFFDDDD

0 ~ 40968192

DB0-DB99

0 ~ 8192

DDDD

Memo
Data Register Double Word
(must be multiple of 4)
Data Register
(must be even)

* Double word and floating point value must use DBDn device type.

How to Import Tag:


SIEMENS STEP 7 program allows building files of user-defined tag (*.dif file and *.AWL
file), and import these files in EasyBuilder8000/EasyBuilderPro -> System Parameter
Settings. The following describes how to build and import these two types of files.
1. Building *.dif File
a In Symbols create user-defined tag.

1069

PLC Connection Guide

b Click Export to export the edited file and click Save.

2. Building *.AWF File


a In Blocks create items as shown below:

b Open LAD/STL, FBD Programming S7 Blocks, click File -> Generate


Source.

1070

PLC Connection Guide

c Select Sources as storage path, specify the file name then click OK.

d Select the objects to be exported then click OK.

1071

PLC Connection Guide

e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.

The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro


System Parameter Settings, by clicking Import Tag.

Tag information successfully imported.

1072

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
Siemens S7-300 PC Adapter : 9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

1073

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

The following is the view from the soldering point of a cable.


Systeme Helmholz SSW7-TS : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS
4 DTR
6 DSR

short
short

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS
4 DTR
6 DSR

1074

short
short

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS
4 DTR
6 DSR

short
short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS
4 DTR
6 DSR

short
short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS
4 DTR
6 DSR

Driver Version:
Version

Date

Description

V3.10

May/24/2011

Added registers: MB & DBBn.


1075

short
short

PLC Connection Guide

VIPA 300S (Ethernet)


HMI Setting:
Parameters

Recommended

Options

PLC type

VIPA 300S (Ethernet)

PLC I/F

Ethernet

Port no.

102

Link type

PG

PC, OP

Rack

0-7

CPU slot

2-31

PLC sta. no.

0-31

Notes

Device Address:
Bit/Word Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

DBnBit

FFFFFFDDDDo 0 ~ 6553599997

DB0Bit-DB99Bit DDDDDo

0 ~ 655327

Data Register Bit

IW

DDDD

0 ~ 4095

Input (I)

QW

DDDD

0 ~ 4095

Output (O)

MW

DDDD

0 ~ 4095

Bit Memory

DW

MD

DDDD

0 ~ 4094

DBn

FFFFFDDDD

0 ~ 655359999

DW

DBDn

FFFFFDDDD

0 ~ 655359999

DBn_String

FFFFFDDDD

0 ~ 655359999

DW

DBDn_String

FFFFFDDDD

0 ~ 655359999

DB0 ~ DB99

DDDDD

0 ~ 65532

Data Register

Byte

MB

DDDD

0 ~ 4095

(must
be even)
Bit
Memory
Byte

Byte

DBBn

FFFFFDDDD

0 ~ 655359999

Data Register Byte

* Double word and floating point value must use DBDn device type.

1076

Data Register
(must be even)
Data Register Double
Word
(must be multiple of 4)

PLC Connection Guide

EasyBuilder Device Setting Steps


1.

Open EasyBuilder, File/NEW, select HMI model and press [OK].

1.

2.
2.
3.

System Parameter Settings window is shown, click [New].


Select SIEMENS S7-400(ETHERNET).

4.
5.

Press [Settings].
Set S7-400 IP, Port no., Link type, Rack and CPU slot. (must match PLC settings)

1077

PLC Connection Guide

6.

The setting will be finished as below.

How to Import Tag:


SIEMENS STEP 7 program allows building files of user-defined tag (*.dif file and *.AWL
file), and import these files in EasyBuilder8000/EasyBuilderPro -> System Parameter
Settings. The following describes how to build and import these two types of files.
1. Building *.dif File
a In Symbols create user-defined tag.

1078

PLC Connection Guide

b Click Export to export the edited file and click Save.

2. Building *.AWF File


a In Blocks create items as shown below:

b Open LAD/STL, FBD Programming S7 Blocks, click File -> Generate


Source.

1079

PLC Connection Guide

c Select Sources as storage path, specify the file name then click OK.

d Select the objects to be exported then click OK.

1080

PLC Connection Guide

e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.

The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro


System Parameter Settings, by clicking Import Tag.

Tag information successfully imported.

1081

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.50

Aug/03/2012

Device types DBn, DBDn is extended to 655359999.

1082

PLC Connection Guide

VIPA 300S, for ex. 315-4NE12 (Ethernet)


HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

VIPA 300S, for ex. 315-4NE12 (Ethernet)

PLC I/F

Ethernet

Port no.

102

PLC sta. no.

0-31

Device Address:
Bit/Word

Device type

Format

Range

Memo

DDDDo

0 ~ 40957

Input (I)

DDDDo

0 ~ 40957

Output (O)

DDDDo

0 ~ 40957

Bit Memory

DBnBit

FFFFDDDDo

0 ~ 409699997

DB0Bit-DB99Bit DDDDDo

0 ~ 655327

Data Register Bit

IW

DDDD

0 ~ 4095

Input (I)

QW

DDDD

0 ~ 4095

Output (O)

MW

DDDD

0 ~ 4095

Bit Memory

DW

MD

DDDD

0 ~ 4094

Bit Memory Double Word

DBn

FFFFDDDD

0 ~ 40969999

DW

DBDn

FFFFDDDD

0 ~ 40969999

DBn_String

FFFFDDDD

0 ~ 40969999

DW

DBDn_String

FFFFDDDD

0 ~ 40969999

DB0 ~ DB99

DDDDD

0 ~ 65532

Byte

MB

DDDD

0 ~ 4095

Bit Memory Byte

Byte

DBBn

FFFFDDDD

0 ~ 40969999

Data Register Byte

Data Register
(must be even)
Data Register Double Word
(must be multiple of 4)

Data Register
(must be even)

Double word and floating point value must use DBDn device type.

1083

PLC Connection Guide

How to Import Tag:


SIEMENS STEP 7 program allows building files of user-defined tag (*.dif file and *.AWL
file), and import these files in EasyBuilder8000/EasyBuilderPro -> System Parameter
Settings. The following describes how to build and import these two types of files.
1. Building *.dif File
a In Symbols create user-defined tag.

1084

PLC Connection Guide

b Click Export to export the edited file and click Save.

2. Building *.AWF File


a In Blocks create items as shown below:

b Open LAD/STL, FBD Programming S7 Blocks, click File -> Generate


Source.

1085

PLC Connection Guide

c Select Sources as storage path, specify the file name then click OK.

d Select the objects to be exported then click OK.

1086

PLC Connection Guide

e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.

The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro


System Parameter Settings, by clicking Import Tag.

Tag information successfully imported.

1087

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V2.10

May/21/2011

Added registers: MB & DBBn.

1088

PLC Connection Guide

WIELAND SAMOS PRO


Supported Series: Samos Pro controllers SP-SCON-P1-K, SP-SCON-NET-PA-K
Website: http://www.wieland-electric.com/en/products/safety-technology

HMI Setting:
Parameters

Recommended

Options

PLC type

WIELAND SAMOS PRO

PLC I/F

RS232

Baud rate

115200

Data bits

Parity

None

Stop bits

PLC sta. no.

Notes

9600,19200,38400,57600,115200

Device Address:
Bit/Word
B

Device type

Format

Range

Memo

DDo

0 ~ 967

Input

DDo

0 ~ 487

Output

Logic result

DDo

0 ~ 327

Logic Result

RS-232

DDo

0 ~ 327

RS-232

Samos Pro to RS-232_Bit

DDo

0 ~ 997

Module Status Bit Array_Bit

DDo

0 ~ 597

Operating Data Block_Bit

Do

0 ~ 97

Configuration CRCs_Bit

DDo

0 ~ 197

CPU Module Type Key_Bit

DDo

0 ~ 177

B
W

Extension Modules Type_Bit

DDDo

0 ~ 3377

RS-232 to Samos Pro

0~2

Samos Pro to RS-232

DD

0 ~ 98

Module Status Bit Array

DD

0 ~ 58

Operating Data Block

0~8

Configuration CRCs

DD

0 ~ 18

CPU Module Type Key

DD

0 ~ 16

Extension Modules Type

DDD

0 ~ 336

1089

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

CPU0 Port0 4P
Mini-DIN Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

4 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

CPU0 Port0 4P
Mini-DIN Male

2 RX

3 TX

3 TX

2 RX

5 GND

4 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

CPU0 Port0 4P
Mini-DIN Male

2 RX

3 TX

3 TX

2 RX

5 GND

4 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

CPU0 Port0 4P
Mini-DIN Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

4 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

CPU0 Port0 4P
Mini-DIN Male

9 RX

3 TX

6 TX

2 RX

5 GND

4 GND
View from the
soldering point
of a cable.

1090

PLC Connection Guide

Driver Version:
Version

Date

V1.20

Mar/14/2014

Description

1091

PLC Connection Guide

XINJE XC Series
Supported Series: XINJE XC Series
Website: http://www.xinje.com

HMI Setting:
Parameters

Recommended

PLC type

XINJE XC Series

PLC I/F

RS232

Baud rate

19200

Data bits

Parity

Even

Stop bits

PLC sta. no.

Options

Notes

RS232

0-255

*Support communications between HMI and PLC in pass-through mode


*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode

Device Address:
Bit/Word

Device type

Format

Range

DDDD

0 ~ 8511

OOOO

0 ~ 1037

OOOO

0 ~ 1037

DDDD

0 ~ 1023

DDD

0 ~ 618

DDD

0 ~ 634

DDDD

0 ~ 8511

TD

DDD

0 ~ 618

CD

DDD

0 ~ 634

FD_1

DDDD

0 ~ 5000

FD_2

DDDD

8000 ~ 8511

1092

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
Driver Version: eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

8 RX

5 TX

3 TX

7 TX

4 RX

5 GND

5 GND

8 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

5 TX

3 TX

4 RX

5 GND

8 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

2 RX

5 TX

3 TX

4 RX

5 GND

8 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 8P Mini-DIN
Male

2 RX

6 RX

8 RX

5 TX

3 TX

4 TX

7 TX

4 RX

5 GND

5 GND

5 GND

8 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 8P Mini-DIN
Male

9 RX

5 TX

6 TX

4 RX

5 GND

8 GND
View from the
soldering point
of a cable.

1093

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Jul/02/2009

Driver released.

1094

PLC Connection Guide

YAMAHA ERCD
HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

YAMAHA ERCD

PLC I/F

RS232

Baud rate

9600

1200-19200

Data bits

7 or 8

Parity

Odd

None/Even/Odd

Stop bits

1 or 2

PLC sta. no.

Neednt to set the station No.

Device Address:
Bit/Word Device type

Format

Range

Memo

Bit

DI

DD

0 ~ 15

Sequence Input (Read only)

Bit

DO

0~7

Sequence Output (Read only)

Bit

EMG

Emergency stop status (Read only)

Bit

SRVO

Servo Status (Read/Write)

Bit

ORG_Sensor D

Original sensor status (Read only)

Bit

RESET

Set on to reset program (Write only)

Bit

RUN

Set on to execute a program (Write only)

Bit

X_ADD

Set on to move robot to + side (Write only)

Bit

X_SUB

Set on to move robot to - side (Write only)

Word

DDD

0 ~ 999

PNT point data (Read/Write) *Note

Word

PRM

DD

0 ~ 99

Parameters (Read/Write)
Switches program number to run

Word

SWI

RW0=program number (Write only)

Set the parameter of RW register, and then


enter any value in this register.
Directly moves to specified position
RW1=X-axis position(mm), RW2=speed

Word

MOVD

(Write only)
Set the parameter of RW register, and then
enter any value in this register.
1095

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo
Return to original activity (Enter any value) ,

Word

ORG

Return to original status


(Read/Write)

Word

MODE

Word

POS

Current position (Read only) *Note

Word

NO

Current program number (Read only)

Word

SNO

Current step number (Read only)

Word

TNO

Current task number (Read only)

Word

PNO

Current selected point number (Read only)

The value read in address types P and POS is timed by 100, therefore, in the object setting
in EasyBuilder, set to the second place after the decimal point to get the correct value.

1096

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TX

3 TX

7 TX

2 RX

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TX

3 TX

2 RX

5 GND

5 GND
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TX

3 TX

4 TX

7 TX

2 RX

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

1097

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TX

6 TX

2 RX

5 GND

5 GND
7 RTS
8 CTS

short

Driver Version:
Version

Date

V1.30

Jan/04/2010

V1.40

Dec/13/2012

Description
Added registers: DIDOEMGSRVOORG_Sensor
PPRMMODEPOSNOSNOTNOPNO.

1098

PLC Connection Guide

YASKAWA CCMEP
Supported Series: YASKAWA CCMEP-100/ CCMEP-200
Website: http://www.yaskawa-control.co.jp/english/jigyo/mechotronics.html

HMI Setting:
Parameters

Recommended

Options

PLC type

YASKAWA CCMEP

PLC I/F

RS485 4W

Baud rate

38400

Data bits

Parity

Even

Stop bits

PLC sta. no.

Notes

Device Address:
Bit/Word

Device type

Format

Range

Memo

4_Bit

DDDDDdd

100 ~ 6553515

DDDDD

1 ~ 65535

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

RS485 4W 8P RJ45
Male

1 RX-

4 TX-

2 RX+

3 TX+

3 TX-

2 RX-

4 TX+

1 RX+

5 GND

8 GND

1099

PLC Connection Guide

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

RS485 4W 8P RJ45
Male

7 RX-

4 TX-

6 RX+

3 TX+

9 TX-

2 RX-

8 TX+

1 RX+

5 GND

8 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

RS485 4W 8P RJ45
Male

1 RX-

1 RX-

4 TX-

2 RX+

2 RX+

3 TX+

3 TX-

3 TX-

2 RX-

4 TX+

4 TX+

1 RX+

5 GND

5 GND

8 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W

RS485 4W 8P RJ45

9P D-Sub Male

Male

1 RX-

4 TX-

2 RX+

3 TX+

3 TX-

2 RX-

4 TX+

1 RX+

5 GND

8 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

RS485 4W 8P RJ45

9P D-Sub Female

Male

1 RX-

4 TX-

2 RX+

3 TX+

3 TX-

2 RX-

4 TX+

1 RX+

5 GND

8 GND

1100

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Jun/14/2012

Driver released.

1101

PLC Connection Guide

YASKAWA Memobus (MP Series Controllers)


Supported Series: YASKAWA MP2200, MP2300, MP2300S, MP9xx communication
module.
Website: http://www.yaskawa.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

YASKAWA Memobus (MP Series Controllers)

PLC I/F

RS485/Ethernet

RS232/RS485 2w/4w,
Ethernet

Baud rate

19200

9600~57600

Data bits

Parity

Even

Stop bits

Port no.

502

default

PLC sta. no.

1-31

Notes

Ethernet Module Only

PLC Setting:
Communication mode

MEMOBUS, Slave, RTU

PLC Ethernet Setting:


1. Use MPE720 program software, open Module Configuration, double click 218IFA.

1102

PLC Connection Guide

2. In Transmision Parameters input MP2300S IP address, Subnet Mask, Gateway IP.


In Connection Parameter, CNO -1 input: Local Port=502, Node IP
address=000.000.000.000, Node Port=00000, Connect Type=TCP, Protocol
Type=MEMOBUS, Code=RTU.

3. Click MECHATROLINK to set up MP2300S PLC as Master.

4. Close all dialogs and save to MP2300S.

1103

PLC Connection Guide

Note:
1. Only CNO 01 can auto communicate with one HMI. Other CNO need a ladder program
created for communication.
2. DIP SW2-2 of MP2300S must be set to OFF position during normal communication,
otherwise, IP address will be erased after reset power, and it will be unable to
communicate with HMI when set to ON position.

Device Address:
Bit/Word Device type

Format

Range

Memo

MB_1

DDDDh

0 ~ 9999f

MB 0 ~ 9999

MB_2

DDDDDh 100000 ~ 65534f

MB 10000 ~ 65535

IB

HHHHH

0 ~ a7ff0

Read only

IW_Bit

HHHHdd

0~ a7ff15

IW

HHHH

0 ~ a7ff

Read only

DW

IL

HHHH

0 ~ a7ff

Read only

DW (F)

IF

HHHH

0 ~ a7ff

Read only

MW

DDDDD

0 ~ 65534

Holding register

DW

ML

DDDDD

0 ~ 65533

Double word

DW (F)
MF
DDDDD 0 ~ 65533
Floating point
*: When connect via Ethernet interface the max range of IW, IL and IF would be restricted.

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub: 217IF-01, 218IF-01
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

7 GND

cMT/mTV series
COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

2 TX

3 TX

3 RX

5 GND

7 GND
1104

PLC Connection Guide

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

7 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

2 TX

6 TX

3 RX

5 GND

7 GND

The following is the view from the soldering point of a cable.


217IF-01 RS485 2W:
eMT3000 series
COM1 RS485 2W

COM3 RS485 2W

217IF-01 RS485 14P

9P D-Sub Male

9P D-Sub Male

Connector

1 RX-

6 Data-

2, 4 D-

2 RX+

9 Data+

1, 3 D+

5 GND

5 GND

14 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

217IF-01 RS485 14P


Connector

7 RX-

4 Data-

2, 4 D-

6 RX+

1 Data+

1, 3 D+

5 GND

5 GND

cMT/mTV series

14 GND

1105

PLC Connection Guide

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

217IF-01 RS485 14P


Connector

1 RX-

7 Data-

2, 4 D-

2 RX+

8 Data+

1, 3 D+

5 GND

9 GND

14 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

217IF-01 RS485 14P


Connector

1 RX-

6 Data-

2, 4 D-

2 RX+

9 Data+

1, 3 D+

5 GND

5 GND

14 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

217IF-01 RS485 14P


Connector

1 RX-

6 Data-

2, 4 D-

2 RX+

9 Data+

1, 3 D+

5 GND

5 GND

14 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

217IF-01 RS485 14P


Connector

1 RX-

7 Data-

2, 4 D-

2 RX+

8 Data+

1, 3 D+

5 GND

5 GND

14 GND

The following is the view from the soldering point of a cable.


217IF-01 RS4854W:
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

217IF-01 RS422 14P


Connector

1 RX-

2 TX-

2 RX+

1 TX+

3 TX-

4 RX-

4 TX+

3 RX+

5 GND

14 GND
1106

PLC Connection Guide

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

217IF-01 RS422 14P


Connector

7 RX-

2 TX-

6 RX+

1 TX+

9 TX-

4 RX-

8 TX+

3 RX+

5 GND

14 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

217IF-01 RS422 14P


Connector

1 RX-

1 RX-

2 TX-

2 RX+

2 RX+

1 TX+

3 TX-

3 TX-

4 RX-

4 TX+

4 TX+

3 RX+

5 GND

5 GND

14 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W

217IF-01 RS422 14P

9P D-Sub Male

Connector

1 RX-

2 TX-

2 RX+

1 TX+

3 TX-

4 RX-

4 TX+

3 RX+

5 GND

14 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W

217IF-01 RS422 14P

9P D-Sub Female

Connector

1 RX-

2 TX-

2 RX+

1 TX+

3 TX-

4 RX-

4 TX+

3 RX+

5 GND

14 GND

1107

PLC Connection Guide

Ethernet cable:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

V1.70

Dec/20/2010

Description

1108

PLC Connection Guide

YASKAWA MP Series Ethernet (Extension)


HMI Setting:
Parameters

Recommended

Options

Notes

PLC type

YASKAWA MP Series Ethernet (Extension)

PLC I/F

Ethernet (UDP)

Port no.

10000

PLC sta. no.

PLC Setting:
Yaskawa PLC Communication Parameter Settings
(1) PLC Factory Communication Parameter Settings:
Item

Set

IP Address

192.168.1.1

Subnet Mask

255.255.255.0

Gateway IP Address

0.0.0.0

System Port No.

10000 (UDP)

TCP Zero Window Timer Value

3 (s)

TCP Retry Time

500 (ms)

TCP Close Time

60 (s)

IP Assemble Time

30 (s)

Max. Packet Length

1500 (bytes)

(2) Setting Steps:


1. Set IP for PLC.

1109

PLC Connection Guide

2. Communication parameter setting.

3. Go to Module Details and select [218IFA] for setting relevant parameters for Ethernet
transmission.

4. The settings are shown below, PLC IP cant be repeated.

1110

PLC Connection Guide

5. Download PLC communication parameters to PLC, and restart the controller.

(3) HMI Settings:


1. Select Ethernet for PLC I/F.
2. Tick [UDP].
3. Set PLC IP and Port, the default Port is 10000.

1111

PLC Connection Guide

Device Address:
Bit/Word

Device type

Format

Range

SB

DDDDh

0 ~ 8191f

IB

HHHHh

0 ~ fffff

OB

HHHHh

0 ~ fffff

MB

DDDDDh

0 ~ 65534f

SW

DDDD

0 ~ 8191

IW

HHHH

0 ~ ffff

OW

HHHH

0 ~ ffff

MW

DDDDD

0 ~ 65534

DW

ML

DDDDD

0 ~ 65534

Memo

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.10

Jul/21/2011

Driver released.

V1.30

Apr/17/2013

Fixed the error in data transfer.

1112

PLC Connection Guide

YASKAWA MP Series Memobus (Ethernet)


Supported Series: YASKAWA MP2200, MP2300, MP2300S, MP9xx with 218IF-02
ethernet module.
Website: http://www.yaskawa.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

YASKAWA MP Series Memobus (Ethernet)

PLC I/F

Ethernet

Port no.

502

Notes

PLC Setting:
How to connect one Yaskawa Ethernet device with multiple HMIs?
http://www.weintek.com/Download/MT8000/eng/FAQ/FAQ_61_How_to_connect_Yaskaw
a_Ethernet.pdf

Device Address:
Bit/Word Device type

Format

Range

MB

DDDDDh

0 ~ 65534F

IB

HHHHH

0 ~ A7FFF

Read only

IW_Bit

HHHHdd

0 ~ A7FF15

Read only

IW

HHHH

0 ~ A7FF

Read only

DW

IL

HHHH

0 ~ A7FF

Read only

DW

IF

HHHH

0 ~ A7FF

Float , Read only

MW

DDDDD

0 ~ 65534

DW

ML

DDDDD

0 ~ 65533

DW

MF

DDDDD

0 ~ 65533

1113

Memo

Float

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Mar/19/2013

Driver released.

1114

PLC Connection Guide

YASKAWA MP Series SIO (Extension)


Supported Series: YASKAWA MP2200, MP2300, MP2300S, MP9xx communication
module.
Website: http://www.yaskawa.com/

HMI Setting:
Parameters

Recommended

Options

PLC type

YASKAWA MP Series SIO (Extension)

PLC I/F

RS485

RS232/RS485 2w/4w

Baud rate

19200

9600~57600

Data bits

Parity

Even

Stop bits

PLC sta. no.

Notes

1-31

Device Address:
Bit/Word Device type

Format

Range

SB

DDDDh

0 ~ 8191F

IB

HHHHh

0 ~ FFFFF

OB

HHHHh

0 ~ FFFFF

MB

DDDDDh

0 ~ 65534F

SW

DDDD

0 ~ 8191

IW

HHHH

0 ~ FFFF

OW

HHHH

0 ~ FFFF

MW

DDDDD

0 ~ 65534

1115

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub: 217IF-01, 218IF-01
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

2 TX

3 TX

7 TX

3 RX

5 GND

5 GND

7 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 TX

3 TX

3 RX

5 GND

7 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

2 TX

3 TX

3 RX

5 GND

7 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

2 TX

3 TX

4 TX

7 TX

3 RX

5 GND

5 GND

5 GND

7 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

2 TX

6 TX

3 RX

5 GND

7 GND

1116

PLC Connection Guide

The following is the view from the soldering point of a cable.


217IF-01 RS485 2W:
eMT3000 series
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

217IF-01 RS485 14P


Connector

1 RX-

6 Data-

2, 4 D-

2 RX+

9 Data+

1, 3 D+

5 GND

5 GND

14 GND

COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

217IF-01 RS485 14P


Connector

7 RX-

4 Data-

2, 4 D-

6 RX+

1 Data+

1, 3 D+

5 GND

5 GND

cMT/mTV series

14 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

217IF-01 RS485 14P


Connector

1 RX-

7 Data-

2, 4 D-

2 RX+

8 Data+

1, 3 D+

5 GND

9 GND

14 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

217IF-01 RS485 14P


Connector

1 RX-

6 Data-

2, 4 D-

2 RX+

9 Data+

1, 3 D+

5 GND

5 GND

14 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

217IF-01 RS485 14P


Connector

1 RX-

6 Data-

2, 4 D-

2 RX+

9 Data+

1, 3 D+

5 GND

5 GND

14 GND

1117

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

217IF-01 RS485 14P


Connector

1 RX-

7 Data-

2, 4 D-

2 RX+

8 Data+

1, 3 D+

5 GND

5 GND

14 GND

The following is the view from the soldering point of a cable.


217IF-01 RS4854W:
eMT3000 series
COM1 RS485 4W
9P D-Sub Male

217IF-01 RS422 14P


Connector

1 RX-

2 TX-

2 RX+

1 TX+

3 TX-

4 RX-

4 TX+

3 RX+

5 GND

14 GND

cMT/mTV series
COM2 RS485 4W
9P D-Sub Female

217IF-01 RS422 14P


Connector

7 RX-

2 TX-

6 RX+

1 TX+

9 TX-

4 RX-

8 TX+

3 RX+

5 GND

14 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS485 4W
9P D-Sub Male

COM2 RS485 4W
9P D-Sub Male

217IF-01 RS422 14P


Connector

1 RX-

1 RX-

2 TX-

2 RX+

2 RX+

1 TX+

3 TX-

3 TX-

4 RX-

4 TX+

4 TX+

3 RX+

5 GND

5 GND

14 GND

1118

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 4W
9P D-Sub Male

217IF-01 RS422 14P


Connector

1 RX-

2 TX-

2 RX+

1 TX+

3 TX-

4 RX-

4 TX+

3 RX+

5 GND

14 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female

217IF-01 RS422 14P


Connector

1 RX-

2 TX-

2 RX+

1 TX+

3 TX-

4 RX-

4 TX+

3 RX+

5 GND

14 GND

Driver Version:
Version

Date

Description

V1.00

Jun/25/2013

Driver released.

1119

PLC Connection Guide

YASKAWA MP2300Siec
Website: http://www.yaskawa.com/site/home.nsf/home/home.html

HMI Setting:
Parameters

Recommended

Options

PLC type

YASKAWA MP2300Siec

PLC I/F

Ethernet

Port no.

44818

Assembly
instance

Input::101
Output:111

PLC sta. no.

Notes

Input::101~106
Output:111~116

PLC Setting:
MP2300Siec-Motion Works IEC Express (YASKAWA) Settings:
Step 1. Before HMI communicates with MP2300Siec using Ethernet/IP, the Instance Input
and Instance Output of MP2300Siec device must be set correctly. Multiple Instances are
allowed to be built at one time, please click [Save] after setting.

Fig. 1 Assembly Instances

1120

PLC Connection Guide

Step 2.Global Variables will automatically add in E/IP Input and Output data, Input and
Output data name and address type can be user-defined.

Fig. 2 Global Variables


Step 3. When download Project to device (MP2300Siec), please go to (Fig. 3)
Resource->Settings to access setting dialog (Fig. 4) for setting MP2300Siec IP address.

Fig. 3 Motion Works IEC Express Settings

1121

PLC Connection Guide

Fig. 4 Resource Settings


Step 4. Start compilation.

Fig. 5 Editing Screen

1122

PLC Connection Guide

Step 5. Download project to device- MP2300Siec, and execute Cold.

Fig. 6 Project Downloading

You may use one of the two drivers to connect Yaskawa MP2300Siec:
1. Yaskawa MP2300Siec driver.
2. Rockwell EtherNet/IP (CompactLogix) Free Tag Names driver.
(1) Yaskawa MP2300Siec driver.
Step 1. System Parameter Settings
Open EasyBuilder project, as shown in Fig. 7, Assembly Instance and Size must match
the software default factory settings, and please dont select UDP. Fig.8 below shows how
HMI Input / Output address is mapped to MP2300Siec device.

Fig. 7 Instance Setting

1123

PLC Connection Guide

Fig.8 HMI and MP2300Siec I/O Mapping


Step 2. Address Setting:
Instance 101 and Instance 111 are defined as 128Bytes, on the project window , WORD
objects can be used, with data typed defined as 32-Bit Unsigned, Input addresses set to
0246..62 for reading Instance 101 data.

Fig. 9 Address Setting

1124

PLC Connection Guide

(2) Rockwell EtherNet/IP (CompactLogix) Free Tag Names driver.


Step 1. In EasyBuilder8000/EasyBuilder Pro project, when using Rockwell EIP driver to
import CSV file (as in Fig. 10), please open Structure Editor (Fig. 11), and right click on
Module Defined to add New Data Type.

Fig. 10 RSLogix 5000 (Rockwell Software) Export Free Tag CSV File

Fig.11 Structure Editor

1125

PLC Connection Guide

Step 2. As in Fig 12, in Structure Editor add Name of the new data type. The Name must
be set identically to the Data Type in Free Tag CSV file. As in Fig 14, Data Member Name
must be set identically to the Rockwell software (as Data in Fig. 13), then click [Save] (Fig.
15).

Fig.12 Structure Editor

Fig.13 Tag Information

1126

PLC Connection Guide

Fig.14 Add Data Member - Name Tag Information

Fig. 15 Add Data Member-Settings - Save

1127

PLC Connection Guide

Step 3. Import CSV file, Tag Information can be viewed from object address.

Fig.16 Tag Information

Device Address:
Bit/Word

Device type

Format

Range

Input_Bit

DDDDDdd 0 ~ 6553515

Output_Bit

DDDDDdd 0 ~ 6553515

DW

Input

DDDDD

0 ~ 65535

DW

Output

DDDDD

0 ~ 65535

Memo

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Note: The wiring diagrams above are drawn based on MT8100i structure, the actual
placement of pins may vary according to HMI module.
1128

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Aug/24/2011

Driver released.

1129

PLC Connection Guide

YASKAWA Sigma-5
Supported Series: YASKAWA -V Series
Website: http://www.yaskawa.co.jp/

HMI Setting:
Parameters

Recommended

PLC type

YASKAWA Sigma-5

PLC I/F

RS232

Baud rate

19200

Data bits

Parity

Even

Stop bits

PLC sta. no.

Options

Notes

RS232/RS485

0 ~ 127

Device Address:
Bit/Word

Device type

Format

Range

Note

0_bit

HHHh

0 ~ FFFF

Normal Parameters Area

E_bit

HHHh

0 ~ FFFF

Monitor Area

HHH

0 ~ FFF

Normal Parameters Area

HHH

0 ~ FFF

Monitor Area

*The following addresses are 32 bit parameters. Please use two words when reading or
writing.
Normal Parameters area

020AH / 020EH / 0210H / 0212H / 0282H / 051BH / 0520H / 0522H / 0524H / 0526H /
0531H
Monitor Area
E003H / E009H / E00EH / E010H / E012H / E016H / E01BH / E084H / E52AH /
E52CH / E52EH / E530H / E532H / E534H / E536H / E538H / E53AH / E53CH /
E601H / E603H / E605H / E705H / E707H / E110H / E120H / E130H

1130

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

SGDV CN3 RS232 14P


Male Connector

2 RX

8 RX

2 TD (Gray/Black)

3 TX

7 TX

4 RD (Purple/Black)

5 GND

5 GND

14 GND (Coffee)

cMT/mTV series
COM1 RS232 9P
D-Sub Female

SGDV CN3 RS232 14P


Male Connector

2 RX

2 TD (Gray/Black)

3 TX

4 RD (Purple/Black)

5 GND

14 GND (Coffee)

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

SGDV CN3 RS232 14P


Male Connector

2 RX

2 TD (Gray/Black)

3 TX

4 RD (Purple/Black)

5 GND

14 GND (Coffee)

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

SGDV CN3 RS232 14P


Male Connector

2 RX

6 RX

8 RX

2 TD (Gray/Black)

3 TX

4 TX

7 TX

4 RD (Purple/Black)

5 GND

5 GND

5 GND

14 GND (Coffee)

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

SGDV CN3 RS232 14P


Male Connector

9 RX

2 TD (Gray/Black)

6 TX

4 RD (Purple/Black)

5 GND

14 GND (Coffee)

1131

PLC Connection Guide

Driver Version:
Version

Date

Description

V1.00

Nov/21/2012

Driver released.

1132

PLC Connection Guide

YASKAWA SMC 3010


Supported Series: YASKAWA SMC Series Servo Motor Controller.

HMI Setting:
Parameters

Recommended

Options

PLC type

YASKAWA SMC 3010

PLC I/F

RS232

Baud rate

19200

Data bits

Parity

None

Stop bits

Notes

9600, 19200

Device Address:
Bit/Word

Device type

Format

Range

AF

0~1

BN

0~1

Write only

BP

0~1

Write only

BV

0~1

Write only

CB

DDDD

0 ~ 9999

Write only

CM

0~1

Read only

DV

0~1

EB

0~1

OE

0~1

RS

0~1

Write only

ST

0~1

Write only

TB

Do

0 ~ 17

Read only

V_Bit

DDDdd

0 ~ 99931

*2

D_arr_Bit

DDDdd

0 ~ 99931

DW

AC

0~4

DW

DC

0~4

DW

BL

0~4

CD

0~2

CE

0~2

DW

DE

0~4

DW

DP

0~4
1133

Memo

Write only

PLC Connection Guide

Bit/Word

Device type

Format

Range

DT

0~2

EC

0~2

DW

EM

0~4

ER

0~2

FA

0~2

DW

FL

0~4

FV

0~2

DW

GR

0~4

DW

JG

0~4

DW

MM

0~4

MT

0~2

NA

0~2

OP

0~2

DW

PA

0~4

DW

PR

0~4

DW

SP

0~4

TC

0~2

TM

0~2

TW

0~2

DW

VA

0~4

DW

VD

0~4

DW

VS

0~4

DW

IL

0~4

DW

IT

0~4

DW

KD

0~4

DW

KI

0~4

DW

KP

0~4

DW

OF

0~4

DW

TL

0~4

DW

VR

0~4

DW

VT

0~4

DW

PF

0~4

DW

VF

0~4

DW

DDD

0 ~ 999

*2

DDD

0 ~ 999

*2

D_array

DDD

0 ~ 999

R_array

DDD

0 ~ 999
1134

Memo

Write only

Read only

*1

PLC Connection Guide

Note:
*1 PF is the communication parameter of SMC_3010, the default is 10.4, if the value is not 10.4, all values
will be displayed incorrectly.
*2 User defined integer variable V000~V999, floating point variable F000~F999.

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

SMC3010 CN6 RS232


9P D-Sub Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

SMC3010 CN6 RS232


9P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

SMC3010 CN6 RS232

D-Sub Female

9P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

1135

short

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

SMC3010 CN6 RS232


9P D-Sub Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

SMC3010 CN6 RS232


9P D-Sub Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

5 GND
7 RTS
8 CTS

Driver Version:
Version

Date

V1.30

Mar/29/2010

Description

1136

short

PLC Connection Guide

YASKAWA SMC 3010 (Ethernet)


Supported Series: YASKAWA SMC Series Servo Motor Controller.

HMI Setting:
Parameters

Recommended

Options

PLC type

YASKAWA SMC 3010 (Ethernet)

PLC I/F

Ethernet

Port no.

23

Notes

Device Address:
Bit/Word Device type

Format

Range

AF

0~1

BN

0~1

Write only

BP

0~1

Write only

BV

0~1

Write only

CB

DDDD

0 ~ 9999

Write only

CM

0~1

Read only

DV

0~1

EB

0~1

OE

0~1

RS

0~1

Write only

ST

0~1

Write only

TB

Do

0 ~ 17

Read only

V_Bit

DDDdd

0 ~ 99931

*2

D_arr_Bit

DDDdd

0 ~ 99931

DW

AC

0~4

DW

DC

0~4

DW

BL

0~4

CD

0~2

CE

0~2

DW

DE

0~4

DW

DP

0~4

DT

0~2

EC

0~2
1137

Memo

Write only

PLC Connection Guide

Bit/Word Device type

Format

Range

DW

EM

0~4

ER

0~2

FA

0~2

DW

FL

0~4

FV

0~2

DW

GR

0~4

DW

JG

0~4

DW

MM

0~4

MT

0~2

NA

0~2

OP

0~2

DW

PA

0~4

DW

PR

0~4

DW

SP

0~4

TC

0~2

TM

0~2

TW

0~2

DW

VA

0~4

DW

VD

0~4

DW

VS

0~4

DW

IL

0~4

DW

IT

0~4

DW

KD

0~4

DW

KI

0~4

DW

KP

0~4

DW

OF

0~4

DW

TL

0~4

DW

VR

0~4

DW

VT

0~4

DW

PF

0~4

DW

VF

0~4

DW

DDD

0 ~ 999

*2

DDD

0 ~ 999

*2

D_array

DDD

0 ~ 999

R_array

DDD

0 ~ 999

1138

Memo

Write only

Read only

*1

PLC Connection Guide

Note:
*1 PF is the communication parameter of SMC_3010, the default is 10.4, if the value is not
10.4, all values will be displayed incorrectly.
*2 User defined integer variable V000~V999, floating point variable F000~F999.

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

V1.10

Mar/29/2010

Description

1139

PLC Connection Guide

YOKOGAWA FA-M3
Supported Series : FA-M3 CPU SP35-5N, SP55-5N CPU port, F3LC11 Computer Link
module.
Website : http://www.yokogawa.com/itc/itc-index-en.htm

HMI Setting:
Parameters

Recommended

Options

PLC type

YOKOGAWA FA-M3

PLC I/F

RS232

Baud rate

19200

9600 ~ 115200

Data bits

7, 8

Parity

Even

Even, Odd, None

Stop bits

1, 2

PLC sta. no.

1-32

Notes

PLC Setting:
Communication mode

Use Personal Communication Link


Use checksum
Use End Character

WideField communication setting:


For WideField communication setting, select [Tool]/ [Set Environment], the default is
[Automatic]. Using the Automatic Recognition, WideField software will connect the current
PLC and get the PLC communication setting. If the PLC communication configuration is
already known, select the [Fixed] mode, It will connect with the PLC quickly.

1140

PLC Connection Guide

P.S Since Personal Computer link is used, when connecting to PLC it will delay about
20sec for testing communication.

YOKOGAWA PLC Communcation Setting:


YOKOGAWA FA-M3
CPU SP55-5N (same SP35-5N)
[File] /[New Project] to create a new project.

1141

PLC Connection Guide

Click [Configuration] to set up communication.

Device Address:
Bit/Word Device type Format

Range

DDDDD

0 ~ 71664

DDDDD

0 ~ 71664

DDDDD

1 ~ 65535

DDDD

1 ~ 9984

DDDDD

0 ~ 78192

DDDDD

1 ~ 65535

DDDDDD

1 ~ 262144

DDD

1 ~ 256

DDDDD

1 ~ 78192

DDDD

1 ~ 1024

DDDDDD

1 ~ 524288

1142

Memo

PLC Connection Guide

Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub: Cable KM11
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

2 TXD

3 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P

RS232 9P D-Sub Male

D-Sub Female
2 RX

2 TXD

3 TX

3 RXD

5 GND

5 GND

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

2 TXD

3 TX

4 TX

7 TX

3 RXD

5 GND

5 GND

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

2 TXD

6 TX

3 RXD

5 GND

5 GND

1143

PLC Connection Guide

The following is the view from the soldering point of a cable.


9P D-Sub to 9P D-Sub: LC11
eMT3000 series
COM1 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

8 RX

3 TXD

3 TX

7 TX

2 RXD

5 GND

5 GND

5 GND
7 RTS
8 CTS

short

cMT/mTV series
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT8000iE/MT8000XE series except MT8050iE


COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

2 RX

3 TXD

3 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

short

MT6000/8000 series except MT6050i/MT8050i


COM1 RS232 9P
D-Sub Female

COM2 RS232 9P
D-Sub Female

COM3 RS232 9P
D-Sub Male

RS232 9P D-Sub Male

2 RX

6 RX

8 RX

3 TXD

3 TX

4 TX

7 TX

2 RXD

5 GND

5 GND

5 GND

5 GND
7 RTS
8 CTS

1144

short

PLC Connection Guide

MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female

RS232 9P D-Sub Male

9 RX

3 TXD

6 TX

2 RXD

5 GND

5 GND
7 RTS
8 CTS

Driver Version:
Version

Date

V1.20

Oct/23/2009

V1.30

May/31/2012

V1.50

Apr/07/2014

Description
Extended address L range up to 78192.
1. Extended I, D, B register range.
2. Added register: F.

1145

short

PLC Connection Guide

YOKOGAWA FA-M3 (Ethernet)


Supported Series : FA-M3 CPU SP35-5N, SP55-5N with F3LE01-5T/F3LE11-0T Ethernet
module.
Website: http://www.yokogawa.com/itc/itc-index-en.htm

HMI Setting:
Parameters

Recommended

Options

PLC type

YOKOGAWA FA-M3 (Ethernet)

PLC I/F

Ethernet

Port no.

12289

PLC sta. no.

Notes

PLC Setting:
Communication mode

Set IP Address, and set all condition setup switch to OFF.

Device Address:
Bit/Word Device type

Format

Range

DDDDD

0 ~ 71664

DDDDD

0 ~ 71664

DDDDD

1 ~ 65535

DDDD

1 ~ 9984

DDDDD

0 ~ 78192

DDDDD

1 ~ 65535

DDDDDD

1 ~ 262144

DD

1 ~ 256

DDDDD

1 ~ 78192

DDDD

1 ~ 1024

DDDDDD

1 ~ 524288
1146

Memo

PLC Connection Guide

Wiring Diagram:
HMI RJ45 Male

Wire Color

PLC RJ45 Male

1 TX+

White/Orange

1 TX+

2 TX-

Orange

2 TX-

3 RX+

White/Green

3 RX+

4 BD4+

Blue

4 BD4+

5 BD4-

White/Blue

5 BD4-

6 RX-

Green

6 RX-

7 BD3+

White/Brown

7 BD3+

8 BD3-

Brown

8 BD3-

Driver Version:
Version

Date

Description

V1.00

Dec/30/2008

Driver released.

V1.10

May/31/2012

Extended address L range up to 78192.

V1.30

Apr/01/2014

1. Extended I, D, B register range.


2. Added register: F.

1147

PLC Connection Guide

YUDIAN AIBUS
Supported Series: UDIAN Automation AI-501, AI-518, AI-519, AI-701, AI-702M, AI-704M,
AI-706M, AI-719.
Website: http://www.yudian.us

HMI Setting:
Parameters

Recommended

PLC type

AIBUS

PLC I/F

RS485 2W

RS232

Baud rate

9600

9600, 19200

Data bits

Parity

None

Stop bits

HMI sta. no.

PLC sta. no.

On-line simulation

Options

Notes

0-100
YES

Extend address mode NO

Device Address:
AI-518
Bit/Word Device type

Format

Range

Memo

00H

DD

01H

DD

-1999 ~ 9999

HIAL

02H

DD

-1999 ~ 9999

LoAL

03H

DD

0 ~ 9999

dHAL

04H

DD

0 ~ 9999

dLAL

05H

DD

0 ~ 2000

dF

06H

DD

0~4

CtrL

07H

DD

0 ~ 9999

M5

08H

DD

1 ~ 9999

09H

DD

0 ~ 2000

SV/STEP

1148

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo

10

0AH

DD

0 ~ 125

CtI

11

0BH

DD

0 ~ 37

Sn (read only)

12

0CH

DD

0~3

dIP (read only)

13

0DH

DD

-1999 ~ 9999

dIL

14

0EH

DD

-1999 ~ 9999

dIH

15

0FH

DD

0 ~ 9999

ALP

16

10H

DD

-1999 ~ 4000
0.1

Sc

17

11H

DD

0 ~ 48

Op1

18

12H

DD

-110 ~ 110%

oPL

19

13H

DD

0 ~ 110%

oPH

20

14H

DD

0 ~ 127

CF (read only)
Baud ratebAud
/808Pstatus word:
run: 0 suspend: 4 stop: 12
(read only)

21

15H

DD

0 ~ 19.2K

22

16H

DD

0 ~ 100

ADDR

23

17H

DD

0 ~ 20

dL

24

18H

DD

0 ~ 127

Run

25

19H

DD

0 ~ 9999

Loc

Bit/Word Device type

Format

Range

Memo

01H

DD

-9990 ~ 30000

HIAL

02H

DD

-9990 ~ 30000

LoAL

03H

DD

-9990 ~ 30000

HdAL

04H

DD

-9990 ~ 30000

LdAL

05H

DD

0 ~ 2000

AHYS

11

0BH

DD

0 ~ 37

InP (read only)

12

0CH

DD

0~3

dPt

13

0DH

DD

-9999 ~ 30000

SCL

14

0EH

DD

-9999 ~ 30000

SCH

15

0FH

DD

0 ~ 4444

AOP

16

10H

DD

-1999 ~ 4000
0.1

Scb

17

11H

DD

0 ~ 48

Opt

AI-701

1149

PLC Connection Guide

Bit/Word Device type

Format

Range

Memo
Baud ratebAud
/808P status word
run: 0 suspend: 4 stop: 12
(read only)

21

15H

DD

0 ~ 19.2K

22

16H

DD

0 ~ 80

ADDR

23

17H

DD

0 ~ 40

FILt

25

19H

DD

0 ~ 255

Loc

Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W

COM3 RS485 2W

RS485 2W terminal

9P D-Sub Male

9P D-Sub Male

1 RX-

6 Data-

4 COMM A

2 RX+

9 Data+

3 COMM B

5 GND

5 GND

cMT/mTV series
COM2 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W terminal

7 RX-

4 Data-

4 COMM A

6 RX+

1 Data+

3 COMM B

5 GND

5 GND

MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W

COM3 RS485 2W

RS485 2W terminal

9P D-Sub Male

9P D-Sub Male

1 RX-

7 Data-

4 COMM A

2 RX+

8 Data+

3 COMM B

5 GND

9 GND

MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W terminal

1 RX-

6 Data-

4 COMM A

2 RX+

9 Data+

3 COMM B

5 GND

5 GND

1150

PLC Connection Guide

MT6000/8000 series except MT6050i/MT8050i


COM1 RS485 2W
9P D-Sub Male

COM3 RS485 2W
9P D-Sub Male

RS485 2W terminal

1 RX-

6 Data-

4 COMM A

2 RX+

9 Data+

3 COMM B

5 GND

5 GND

MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female

COM3 RS485 2W
9P D-Sub Female

RS485 2W terminal

1 RX-

7 Data-

4 COMM A

2 RX+

8 Data+

3 COMM B

5 GND

5 GND

Driver Version:
Version

Date

V1.20

Dec/30/2008

Description

1151

PLC Connection Guide

MT6050i/MT8050i/MT8050iE Com Port Pin


Assignment

C O M C P U P W R

Bottom View
Front View

MT6050i/MT8050i/MT8050iE
Pin assignment of the 9 Pin, Male,
Pin assignment of the 9 Pin, Male, SUB-D, COM1 [RS-232]/ [RS-485], COM3 [RS-485] Port. Only
Com1[RS485 2W] support MPI 187.5K.
Pin#

Symbol

Com1[RS485]
4 wire

Rx-

Rx-

Data-

Rx+

Rx+

Data+

Tx-

Tx-

---

Com3[RS485]

2 wire

R e s e t
D I P S W

Com1[RS232]

Cutout dimensions:
MT-6050i:
119mm [4.685"] W x 93mm [3.661"] H

C O M

Tx+

Tx+

GND

GND

TxD

Transmit

Data-

Data-

Data+

Data+

RxD

Rear View

Receive

1152

PLC Connection Guide

Wiring Diagram:
MT6050i COM1 [RS-232]

PLC RS-232

9P D-SUB Female

Communication Com Port interface

RXD

TXD

TXD

RXD

GND

GND

MT6050i COM1 [RS-485 2w]

PLC RS-485 2w

9P D-SUB Female

Communication Com Port interface

Data-

Data-

Data+

Data+

MT6050i COM3* [RS-485 2w]

PLC RS-485 2w

9P D-SUB Female

Communication Com Port interface

Data-

Data-

Data+

Data+

*RS485 2W COM3 is only available for MT6050iv2

MT6050i COM1 [RS-485 4w]

PLC RS-485 2w

9P D-SUB Female

Communication Com Port interface

RX-

TX-

RX

TX+

TX-

RX-

TX+

RX+

1153