PLC Connection Guide
PLC Connection Guide
PLC Connection Guide
Table of content
ABB AC500 ................................................................... 1
BACnet/IP ................................................................... 23
BACnet/MSTP ............................................................ 34
Baumuller ................................................................... 44
Names .......................................................................... 70
Bosch Rexroth............................................................. 74
Change....................................................................... 100
KEYENCE KV-L20V/700/1000/3000/5000/Nano
KEYENCE KV-L20V/700/1000/3000/5000/Nano
.................................................................................... 517
.................................................................................... 522
Mitsubishi Q00UJ/QnU/QnUD/QnUDH/QnUDEH/L
.................................................................................... 879
3
ABB AC500
Supported Series: ABB AC500
HMI Setting:
Parameters
Recommended
PLC type
ABB AC500
PLC I/F
RS485 2W
Baud rate
19200
Data bits
Parity
Even
Stop bits
Port no.
502
Options
Notes
RS232/RS485 2W / Ethernet
Ethernet
Device Address:
Bit/Word
Device type
Format
Range
Memo
MX0
DDDDo
0 ~ 81917
%MX0.0.0 ~ 0.8191.7
MW0
DDDDD
0 ~ 32767
%MW0.0 ~ 0.32767
MW1
DDDDD
0 ~ 32767
%MW0.1 ~ 1.32767
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
1
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TX
6 TX
3 RX
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
8 Data-
2 RX+
9 Data+
3 Data+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
8 Data-
6 RX+
1 Data+
3 Data+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
8 Data-
2 RX+
8 Data+
3 Data+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
8 Data-
2 RX+
9 Data+
3 Data+
5 GND
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
8 Data-
2 RX+
9 Data+
3 Data+
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
1 RX-
7 Data-
8 Data-
2 RX+
8 Data+
3 Data+
5 GND
5 GND
5 GND
Wire Color
Wire Color
1 TX+
White/Orange
White/Green
3 RX+
2 TX-
Orange
Green
6 RX-
3 RX+
White/Green
White/Orange
1 TX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Orange
2 TX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Through a hub:
Driver Version:
Version
Date
Description
V1.00
Dec/19/2012
Driver released
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
Ethernet
Port no.
10000
Options
Notes
Device Address:
Bit/Word Device type
Format
Range
Memo
BIT
DDD.DDD.DDDD
0 ~ 255.255.9999
W_BIT
DDD.DDD.DDDDdd 0 ~ 255.255.999915
Byte
BYTE
DDD.DDD.DDDD
0 ~ 255.255.9999
WORD
DDD.DDD.DDDD
0 ~ 255.255.9999
DW
DWORD
DDD.DDD.DDDD
0 ~ 255.255.9999
STRING
DDD.DDD.DDDD
0 ~ 255.255.9999
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Sep/22/2014
Driver released
5
Altus ALNET-I
Supported Series: Altus SeriesMode PO3042, PO3142, PO3242, PO3342, PL103 ,PL104,
PL105, QK800, QK801, QK2000.
HMI Setting:
Parameters
Recommended
PLC type
Altus ALNET-I
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
Even
Stop bits
Options
Notes
Device Address:
Bit/Word
Device Type
Format
Range
Memo
M_Bit
DDDDh
0 ~ 1023f
Memories
DDDh
0 ~ 511f
Auxiliary Relays
DDDh
0 ~ 511f
Input Relays
D_Bit
DDDDdd
0 ~ 102331
Decimals
F_Bit
DDDDdd
0 ~ 102331
Reals
I_Bit
DDDDdd
0 ~ 102331
Integers
DDDh
0 ~ 511f
Output Relays
DDDD
0 ~ 4096
Memories
DW
DDDD
0 ~ 4096
Decimals
DW
DDDD
0 ~ 1023
Reals
DW
DDDD
0 ~ 1023
Integers
TM
HHHH
0 ~ ffff*
Memory Tables
DW
TD
HHHH
0 ~ ffff*
Decimal Tables
DW
TF
HHHH
0 ~ ffff*
Real Tables
DW
TI
HHHH
0 ~ ffff*
Integer Tables
Note: The formats of TM, TD, TF and TI in PLC software are represented as TXA[B]. X
can be M, D, F, or I.
The address range of B is 0~FF, and A is 0~FF. The device type is AABB, and the range
depends on the PLC settings.
For example: Model PO3242, range of A is 0 and range of B is 0 ~ 7.
6
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 8P RJ45: PLC PO3042, PO3142, PO3242, PO3342
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
D-Sub Female
Male
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TX
6 TX
3 RX
5 GND
5 GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
7 TX
3 TX
7 TX
1 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
7 TX
3 TX
1 RX
5 GND
5 GND
2 RX
7 TX
3 TX
1 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
7 TX
3 TX
4 TX
7 TX
1 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
7 TX
6 TX
1 RX
5 GND
5 GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
7 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
7 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TX
6 TX
3 RX
5 GND
7 GND
Driver Version:
Version
Date
V1.10
Jul/24/2009
Description
10
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
RS232 / RS485 2W
Baud rate
9600
9600 ~ 115200
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word
Device Type
Format
Range
ABORT
ABS
CLR
CLRS
DI_Bit
1~6
DO_Bit
1~3
EDO
EO
H+
H-
J+
J-
L+
L-
LT
MM
MST
0~9
POL
0~8
11
Memo
Bit/Word
Device Type
Format
Range
RT
SCV
SL
STORE
SLOAD
STOP
Z+
Z-
ZH+
ZH-
ACC
CUR
CURI
CURR
DB
DI
DN
0~2
DO
DX
EX
HSPD
ID
0~6
LCA
LSPD
LTE
LTP
LTS
PS
PX
SA
DDDD
0 ~ 1275
SASTAT
SLA
SLE
SLS
SLT
SR
SPC
0
12
Memo
Bit/Word
Device Type
Format
Range
SSPD
SSPDM
DD
0 ~ 99
VER
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
9 TX
3 TX
7 TX
19 RX
5 GND
5 GND
3;24 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
Connector
2 RX
9 TX
3 TX
19 RX
5 GND
3;24 GND
2 RX
9 TX
3 TX
19 RX
5 GND
3;24 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
9 TX
3 TX
4 TX
7 TX
19 RX
5 GND
5 GND
5 GND
3;24 GND
13
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
9 TX
6 TX
19 RX
5 GND
3;24 GND
COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male
Connector
1 RX-
6 Data-
6 Data-
2 RX+
9 Data+
4 Data+
5 GND
5 GND
3;24 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
6 Data-
6 RX+
1 Data+
4 Data+
5 GND
5 GND
3;24 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male
Connector
1 RX-
7 Data-
6 Data-
2 RX+
8 Data+
4 Data+
5 GND
9 GND
3;24 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
6 Data-
2 RX+
9 Data+
4 Data+
5 GND
5 GND
3;24 GND
14
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
6 Data-
2 RX+
9 Data+
4 Data+
5 GND
5 GND
3;24 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
1 RX-
7 Data-
6 Data-
2 RX+
8 Data+
4 Data+
5 GND
5 GND
3;24 GND
Driver Version:
Version
Date
Description
V1.00
Mar/23/2015
Driver released
15
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
F3002_bit
Hh
0 ~ 0f
F3003_bit
Hh
0 ~ 0f
F0-0 ~ F0-1
W/R
F0-2
0~1
W/R *Note1
F0-3 ~ F0-157
W/R
F2-0 ~ F2-16
Read only
F3000 ~ F3001
Write only
F3002 ~ F3003
Read only
FC01 ~ FC12
Read only
Note 1: Value 0 means write to NAND Flash (Data will be saved after power off.) Value 1
means write to RAM (Data will not be saved after power off.)
16
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
1 RX-
6 Data-
8 Data-
2 RX+
9 Data+
1 Data+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P RJ45
7 RX-
4 Data-
8 Data-
6 RX+
1 Data+
1 Data+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
1 RX-
7 Data-
8 Data-
2 RX+
8 Data+
1 Data+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
1 RX-
6 Data-
8 Data-
2 RX+
9 Data+
1 Data+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
1 RX-
6 Data-
8 Data-
2 RX+
9 Data+
1 Data+
5 GND
5 GND
17
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P RJ45
1 RX-
7 Data-
8 Data-
2 RX+
8 Data+
1 Data+
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Nov/18/2014
Driver released
18
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
F3002_bit
Hh
0 ~ 0f
F3003_bit
Hh
0 ~ 0f
F0-0 ~ F0-1
W/R
F0-2
0~1
W/R *Note1
F0-3 ~ F0-178
W/R
F2-0 ~ F2-16
Read only
F3000 ~ F3001
Write only
F3002 ~ F3003
Read only
FC01 ~ FC12
Read only
Note 1: Value 0 means write to NAND Flash (Data will be saved after power off.) Value 1
means write to RAM (Data will not be saved after power off.)
19
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
1 RX-
6 Data-
8 Data-
2 RX+
9 Data+
1 Data+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P RJ45
7 RX-
4 Data-
8 Data-
6 RX+
1 Data+
1 Data+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
1 RX-
7 Data-
8 Data-
2 RX+
8 Data+
1 Data+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
1 RX-
6 Data-
8 Data-
2 RX+
9 Data+
1 Data+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
1 RX-
6 Data-
8 Data-
2 RX+
9 Data+
1 Data+
5 GND
5 GND
20
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P RJ45
1 RX-
7 Data-
8 Data-
2 RX+
8 Data+
1 Data+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W terminal
1 RX-
6 Data-
RS485-
2 RX+
9 Data+
RS485+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W terminal
7 RX-
4 Data-
RS485-
6 RX+
1 Data+
RS485+
5 GND
5 GND
GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W terminal
1 RX-
7 Data-
RS485-
2 RX+
8 Data+
RS485+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W terminal
1 RX-
6 Data-
RS485-
2 RX+
9 Data+
RS485+
5 GND
5 GND
GND
21
COM3 RS485 2W
9P D-Sub Male
RS485 2W terminal
1 RX-
6 Data-
RS485-
2 RX+
9 Data+
RS485+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W terminal
1 RX-
7 Data-
RS485-
2 RX+
8 Data+
RS485+
5 GND
5 GND
GND
Driver Version:
Version
Date
Description
V1.00
Nov/18/2014
Driver released
22
BACnet/IP
Supported series: BACnet/IP protocol devices
HMI Setting:
Parameters
Recommended
PLC type
BACnet/IP
PLC I/F
Ethernet
Options
Port no.
47808
47808
47808~47823
Device ID
342566
0~999999
Notes
BACnet/IP to
MS/TP adapter
23
2. As shown above, in BACnet/IP to MS/TP Adapter mode, [Network number] must follow
the factory setting, and enter the device station number in [Device ID].
3. [HMI port no]. default: 47808, can be filled in other effective value.
24
25
CSV file content is shown below; users can build the file and import:
a. Object format
b. OBJECT NAME (user defined tag name, EasyBuilder will start reading data from the
6th row of CSV file.), DEVICE ID, OBJECT TYPE(object ID) and INSTANCE(object
address)
26
Take (102)File as an example, 10 represents object ID, 2 represents object address, File
represents user defined name or default name.
Object Name
Object Structure
Analog Input
Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Units
Min Press Value
Max Press Value
Cov Increment
Resolution
High Limit
Low Limit
Dead Band
27
Object ID
Object Name
Object Structure
Profile Name
Analog Output
Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Units
Relinquish Default
Min Press Value
Max Press Value
Cov Increment
Resolution
High Limit
Low Limit
Dead Band
Profile Name
Analog Value
Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Units
Relinquish Default
Cov Increment
High Limit
Low Limit
Dead Band
Profile Name
Binary Input
Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Polarity
Profile Name
28
Object ID
Object Name
Object Structure
Notify Type
Alarm Value
Binary Output
Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Polarity
Profile Name
Notify Type
Binary Value
Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Profile Name
Notify Type
Alarm Value
Calendar
Object Name
Object Identifier
Object Type
Present Value
Command
Object Name
Object Identifier
Object Type
Present Value
In Process
All Writes Successful
Device
Object Name
Object Identifier
Object Type
System Status
Vendor Name
Vendor Identifier
Model Name
Firmware Revision
29
Object ID
Object Name
Object Structure
Application Software Version
Protocol Version
Protocol Revision
Max APDU length Accepted
Segmentation Supported
Apdu Timeout
Number Of APDU retries
Data Base Revision
Max Segments Accepted
Day light Savings Status
Apdu Segment Timeout
Backup Failure Timeout
10
File
Object Name
Object Identifier
Object Type
File Type
File Size
Archive
Read Only
11
Group
Object Name
Object Identifier
Object Type
13
Multi State
Input
Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Reliability
Number Of States
Time Delay
Notification Class
Notify Type
Profile Name
14
Multi State
Object Name
Output
Object Identifier
Object Type
Present Value
30
Object ID
Object Name
Object Structure
Event State
Out Of Service
Reliability
Number Of States
Time Delay
Notification Class
Notify Type
Profile Name
15
Notification
Class
Object Name
Object Identifier
Object Type
Notification Class
Priority
17
Schedule
Object Name
Object Identifier
Object Type
Present Value
Priority For Writing
Reliability
Out Of Service
18
Averaging
Object Name
Object Identifier
Object Type
Minimum Value
Average Value
Maximum Value
Attempted Samples
Valid Samples
Window Interval
Window Samples
19
Multi State
Value
Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Reliability
Number Of States
31
Object ID
Object Name
Object Structure
Notification Class
Notify Type
Profile Name
Time Delay
20
Trend Log
Object Name
Object Identifier
Object Type
Enable
Stop When Full
Buffer Size
Record Count
Total Record Count
21
Life Safety
Object Name
Point
Object Identifier
Object Type
Present Value
Tracking Value
Event State
Reliability
Out Of Service
Mode
Silenced
22
Life Safety
Zone
Object Name
Object Identifier
Object Type
Present Value
Tracking Value
Event State
Reliability
Out of Service
Mode
Silenced
23
Accumulator
Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
32
Object ID
Object Name
Object Structure
Scale
Units
Reliability
24
Pulse
Converter
Object Name
Object Identifier
Object Type
Present Value
Event State
Out Of Service
Units
Scale Factor
Adjust Value
High Limit
Low Limit
Dead Band
Cov Increment
Count
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Jan/12/2012
Driver released
33
BACnet/MSTP
Supported series: BACnet/MSTP protocol devices
HMI Setting:
Parameters
Recommended
Options
PLC type
BACnet/MSTP
PLC I/F
RS485-2W
Baud rate
38400
Data bits
Parity
None
Stop bits
MAC
0 ~ 254
HMI MAC
1 ~ 127
Nmax_master
127
2 ~ 127
Npoll
50
1 ~ 255
Notes
9600,19200,38400
34
2. Use a RS-232/RS-485 converter to connect the BACnet MS/TP unit with PC. Only one
BACnet MS/TP unit is allowed. Set PC COM and Baud rate, click Scan Device button
to find the MAC address and Device ID of the BACnet MS/TP unit.
4. After getting the MAC address and Device ID, click Get Tag Info button to get the
address tags.
35
5. If the tags are obtained successfully, the following message shows, click OK.
6. In the PLC Tags field, the tags with its check box selected can be imported. After
selecting the tags, click Save, and then click Export All, to save the address tags as
CSV file. When finished, click Exit to finish importing address tags.
Notes:
1. The MAC address and Device ID of certain BACnet MS/TP units can be gained by
clicking [Scan Device] only at the first time the unit is powered up. To get this
information in the same way again, please power up the unit again.
36
2. Certain BACnet MS/TP units do not support [Scan Device] and [Get Tag Info].
3. If the MAC address gained by clicking [Scan Device] does not match the one specified
in EasyBuilder Pro Device Properties settings, a message shows as a reminder when
[Get Tag Info] is clicked.
Object Name
Object Structure
Analog Input
Object Name
Object Identifier
Object Type
Present Value
Present Value Array
Units
Analog Output
Object Name
Object Identifier
Object Type
Present Value
Present Valuse Array
Units
Priority
Priority Array
Relinquish Default
SubscribeCovTime
Analog Value
Object Name
Object Identifier
Object Type
Present Value
Present Value Array
Units
Priority
Priority Array
Relinquish Default
SubscribeCovTime
Binary Input
Object Name
Object Identifier
Object Type
Present Value
Present Value Array
37
Object ID
Object Name
Object Structure
SubscribeCovTime
Binary Output
Object Name
Object Identifier
Object Type
Present Value
Present Value Array
Priority
Priority Array
Polarity
SubscribeCovTime
Binary Value
Object Name
Object Identifier
Object Type
Present Value
Present Value Array
Priority
Priority Array
SubscribeCovTime
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W terminal
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
cMT/mTV series
38
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
Driver Version:
Version
Date
Description
V1.00
Jan/30/2016
Driver released
39
Barcode/Keyboard (USB/COM)
HMI Setting:
Parameters
Recommended
Options
PLC type
Barcode/Keyboard (USB/COM)
PLC I/F
RS232
RS232/485,USB
Baud rate
9600
9600~115200
Data bits
7,8
Parity
None
Stop bits
Terminator
CR/LF
1,2
CR/LF, STX/ETX,
Other, None
Notes
40
Device Address:
Bit/Word Device type
Format
Range
Memo
FLAG
DD
Flag
RESET
*Note 1
BARCODE 0
DD
Length
BARCODE 1
DD
1~255
String
RESULT
*Note 2
1. RESET: If set on, clears the data of BARCODE and RESULT, and clears FLAG to
OFF.
2. RESULT:Indicates the result of data reading.
The following values indicate:
0 : Waiting to read BARCODE.
1 : BARCODE is successfully read.
2 : Invalid BARCODE format.
3 : Exceeds the number of bytes specified in [Read byte limit].
4 : The Start Code of the data read does not match the setting.
5 : The Terminator of the data read does not match the setting.
41
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
FeMale
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
FeMale
2 RX
TXD
3 TX
RXD
5 GND
GND
RS232 9P D-Sub
FeMale
2 RX
TXD
3 TX
RXD
5 GND
GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
FeMale
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
FeMale
9 RX
TXD
6 TX
RXD
5 GND
GND
42
Driver Version:
Version
Date
V1.30
Oct/1/2010
Description
43
Baumuller
Website: http://www.baumuller.com/
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
Baumuller
PLC I/F
RS485 4W
Baud rate
19200
9600, 19200
Data bits
7 or 8
Parity
Even
Stop bits
1 or 2
Defaults
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format Range
DB0_bit ~
DB29_bit
DDDh
0 ~ 255f
DB0 ~ DB29
DDD
0 ~ 255
44
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
1 RX-
1 TXD-
2 RX+
9 TXD+
3 TX-
5 RXD-
4 TX+
6 RXD+
5 GND
8 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
1 TXD-
6 RX+
9 TXD+
9 TX-
5 RXD-
8 TX+
6 RXD+
5 GND
8 GND
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
1 TXD-
2 RX+
2 RX+
9 TXD+
3 TX-
3 TX-
5 RXD-
4 TX+
4 TX+
6 RXD+
5 GND
5 GND
8 GND
1 RX-
1 TXD-
2 RX+
9 TXD+
3 TX-
5 RXD-
4 TX+
6 RXD+
5 GND
8 GND
45
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
1 TXD-
2 RX+
9 TXD+
3 TX-
5 RXD-
4 TX+
6 RXD+
5 GND
8 GND
Driver Version:
Version
Date
V1.10
Apr/17/2009
Description
46
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
48898
ADS port
801
PLC Setting:
Step1.
Open TwinCat System Properties.
PLC Settings: Set HMI Name, AMS Net ID, and Address.
Ex:
HMI IP: 192.168.1.15
AMS Net ID: Must input 192.168.1.15.1.1
Address: 192.168.1.15
Name: Input HMI or any userdefined name.
47
Notes
Step2.
Simulate PLC on PC. 2 Twincat drivers must be installed as follows:
48
Step3.
The following commands can be utilized for Twincat PLC to output the parameters
observed.
49
50
51
Step5.
Click [Import Tag] button in EasyBuilder to open the TPY file compiled by Twincat PLC
Control.
Note: When using Beckhoff driver, if the TPY file cannot be imported, try download and
install MSXML 4.0 in Microsoft - Download Center.
52
Step6.
The following dialog box appears for users to select all or part of the data to import. A
reminding message is shown when import the same data repeatedly.
*EasyBuilder8000 does not support [Comment] setting.
53
Step7.
Download the project compiled in EasyBuilder to HMI.
Device address:
Bit/Word Device type
Format
Range
Memo
IX
DDDDDo
0 ~ 655357
o : Bit no.(0 ~ 7)
QX
DDDDDo
0 ~ 655357
o : Bit no.(0 ~ 7)
MX
DDDDDo
0 ~ 655357
o : Bit no.(0 ~ 7)
IW
DDDDD
0 ~ 65535
QW
DDDDD
0 ~ 65535
MW
DDDDD
0 ~ 65535
DW
ID
DDDDD
0 ~ 65535
DW
QD
DDDDD
0 ~ 65535
DW
MD
DDDDD
0 ~ 65535
Bool
bit
Word
16-bit
DInt
Real
32-bit Float
32-bit
UDInt
32-bit
String
Int
UInt
DWord
54
Memo
16-bit
16-bit
32-bit
32-bit
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Dec/08/2010
Driver released.
V1.10
Aug/24/2011
55
Beckhoff Embedded PC
Supported Series: Intel-CX10x0,CX50x0 and Twincat
HMI Setting:
Parameters
Recommended
Options
PLC type
Beckhoff Embedded PC
PLC I/F
Ethernet
Port no.
48898
ADS port
801
PLC Setting:
For Twincat:
a. Confirm PC IP address
56
Notes
c. Use Twincat to build a Route Table to make sure the system is connected, if PLC
power turns OFF and then ON, please redo this step.
Note: when connected, if X is displayed, the connection succeeded.
57
58
c. Succeeded to connect with PLC, click Start -> click Control Panel.
d. Click [Network and Dial-Up Connections] to display PLC device information; select
the PLC to check its IP.
e. Access PLC system settings, the default directory: \Hard Disk\System, execute
[TcAmsRemoteMgr].
59
f. AMS Net Id consists of 6 numbers, separated by .. The first 4 numbers stand for IP
and followed by 1.1. The figure below shows the AMS Net Id of Local Computer,
please enter PLC IP plus 1.1. Remote Computers shows the information of the HMI
to connect with. Click [Add] to add the HMI and click [OK] to finish setting.
60
h. Return to Control Panel; execute CX Configuration Tool to confirm PLC AMS Net
Id.
61
62
63
Step4.
Click [Import Tag] button in EasyBuilder to open the TPY file compiled by Twincat PLC
Control.
Note: When using Beckhoff driver, if the TPY file cannot be imported, try download and
install MSXML 4.0 in Microsoft - Download Center.
64
Step5.
The following dialog box appears for users to select all or part of the data to import. A
reminding message is shown when import the same data repeatedly.
*EasyBuilder8000 does not support [Comment] setting.
65
Step6.
Download the project compiled in EasyBuilder to HMI.
Device address:
Bit/Word Device type
Format
Range
Memo
IX
DDDDDo
0 ~ 655357
o : Bit no.(0 ~ 7)
QX
DDDDDo
0 ~ 655357
o : Bit no.(0 ~ 7)
MX
DDDDDo
0 ~ 655357
o : Bit no.(0 ~ 7)
IW
DDDDD
0 ~ 65535
QW
DDDDD
0 ~ 65535
MW
DDDDD
0 ~ 65535
DW
ID
DDDDD
0 ~ 65535
DW
QD
DDDDD
0 ~ 65535
DW
MD
DDDDD
0 ~ 65535
Bool
bit
Word
16-bit
DInt
Real
32-bit Float
32-bit
UDInt
32-bit
String
Int
UInt
DWord
66
Memo
16-bit
16-bit
32-bit
32-bit
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Apr/18/2011
Driver released.
V1.10
Aug/24/2011
67
HMI Setting:
Parameters
PLC type
Recommended
Options
Beckhoff TwinCAT 3 ADS/AMS (Ethernet)
PLC I/F
Ethernet
Port no.
48898
Notes
Device Address:
Bit/Word
Device type
Format
Range
IX
DDDDDdd
0 ~ 6553515
QX
DDDDDdd
0 ~ 6553515
MX
DDDDDdd
0 ~ 6553515
IW
OOOOOO
0 ~ 65535
QW
DDDDD
0 ~ 65535
MW
DDDDD
0 ~ 65535
ID
DDDDD
0 ~ 65535
QD
DDDDD
0 ~ 65535
MD
DDDDD
0 ~ 65535
68
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Jun/07/2013
Driver released.
69
HMI Setting:
Parameters
PLC type
Recommended
Options
Beckhoff TwinCAT PLC (Ethernet) Free Tag Names
PLC I/F
Ethernet
Port no.
48898
Bool
bit
Word
16-bit
DInt
Real
32-bit Float
32-bit
UDInt
32-bit
String
Int
UInt
DWord
70
Memo
16-bit
16-bit
32-bit
32-bit
Notes
71
3. Select PLC Software Version. The standard file type of TwinCAT 2.0 is .typ. The
standard file types of TwinCAT 3.0 are: .TcDUT, .TcGVL, and .TcPOU. The tags to be
imported can be selected by a tag name filter. Select the file type and then click
[Import]. The invalid address types will be displayed in Error Status field. Click [OK] to
leave.
Note. Tag name can not include ..
72
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Dec/12/2014
Driver released.
73
Bosch Rexroth
HMI Setting:
Parameters
Recommended
PLC type
Bosch Rexroth
PLC I/F
RS232
Baud rate
115200
Data bits
Parity
None
Stop bits
Options
Notes
Bool
bit
Byte
8-bit
DInt
Real
32-bit Float
32-bit
UDInt
32-bit
SInt
USInt
Word
Int
UInt
DWord
74
Memo
8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit
Import Tag:
1. Launch IndraWorks PLC software, click [Global_Variables], and edit the project.
2. Struct can be edited in [Data types] tab, and Global_varaibles can be edited in
[Resources] tab.
[Data types]
[Resources]
75
3.
After editing the project, click [Project] -> [Export] to export the tags.
4. You may select all, a part of, or a single file to export. Click [OK], enter the file name
and designate the directory to store the file.
76
5. Launch EasyBuilder, select Bosch Rexroth driver, and import the address tags. The
illegal addresses will be eliminated, and displayed in the [Error status] field. Click [OK]
to leave.
6. Import successfully message will be displayed when successfully import the address
tags.
77
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TX
6 TX
3 RX
5 GND
5 GND
78
Driver Version:
Version
Date
Description
V1.00
Nov/18/2014
Driver released.
79
HMI Setting:
Parameters
Recommended
PLC type
Node ID
1~127
Baud rate
250K
10K~1M
Online simulator
NO
Options
Notes
80
Device Address:
Bit/Word
B
Device type
TxPDOn_BIT
Format
DDDNo
Range
Memo
100 ~ 99977
DDDPDO no.
Naddress (unitbyte).
obit no.
RxPDOn_BIT
DDDNo
100 ~ 99977
DDDPDO no.
Naddress (unitbyte).
obit no.
SDO_8bit_Bit
HHHHHHo
0 ~ FFFFFF7
HHHH(Index)+HH(Sub
-index)+o(Bit no)
SDO_16bit_Bit
HHHHHHdd
0 ~ HHHHHH15
HHHH(Index)+HH(Sub
-index)+dd(Bit no)
TxPDOn
DDDN
10 ~ 9997
DDDPDO no.
Naddress(unitbyte)
81
Bit/Word
Device type
Format
Range
Memo
TxPDOn_Byte
DDDN
10 ~ 9997
DDDPDO no.
Naddress(unitbyte)
RxPDOn
DDDN
10 ~ 9997
DDDPDO no.
Naddress(unitbyte)
RxPDOn_Byte
DDDN
10 ~ 9997
DDDPDO no.
Naddress(unitbyte)
SDO_8bit
HHHHHH
0~FFFFFF
SDO_16bit
HHHHHH
0~FFFFFF
SDO_32bit
HHHHHH
0~FFFFFF
HHHH(Index)+HH(Sub
-index)
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000, MT8091/8092XE, cMT3151
CAN Bus 9P
D-Sub Female
CAN Device
7 CAN-
CAN -
8 CAN+
CAN+
5 GND
GND
To minimize signal reflection on the CAN bus network, termination resistors should be
installed at both ends of the network, as shown in the following figure. (eMT3070A has
built-in termination resistor, so it is not required for eMT3070A)
82
Driver Version:
Version
Date
Description
V1.40
Aug/20/2012
83
HMI Setting:
Parameters
PLC type
Baud rate
Online simulator
Recommended
Options
250K
10K~1M
NO
Address Tags:
1. In EasyBuilder Pro add CAN Bus General, SAE J1939 driver.
84
Notes
2. Open Address Tag Library, select [User-defined tags] and then click [New].
85
4. Please set the following parameters according to the specification of the CAN device
used.
Device Address:
Bit/Word
B
Device type
DATA_Bit
Format
Memo
HHHHHHHHBb
H: ID
B: Byte position (1~8)
b: bit start position (1~8)
H: ID
DATA
HHHHHHHHBbNN
86
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000, MT8091/8092XE, cMT3151
CAN Bus 9P
D-Sub Female
CAN Device
7 CAN-
CAN -
8 CAN+
CAN+
5 GND
GND
To minimize signal reflection on the CAN bus network, termination resistors should be
installed at both ends of the network, as shown in the following figure. (eMT3070A has
built-in termination resistor, so it is not required for eMT3070A)
Driver Version:
Version
Date
V1.30
Mar/15/2016
Description
87
CAS CI-1580A
Supported Series : CAS CI-1580A
Website : http://www.globalcas.com/bemarket/main/main.php
HMI Setting:
Parameters
Recommended
PLC type
CAS CI-1580A
PLC I/F
RS232
RS232/RS485 4W
Baud rate
9600
9600 ~ 115200
Data bits
Parity
None
Stop bits
1 ~ 99
Parameter1
0,1
Online simulator
Options
Notes
YES
PLC Setting:
0 No Parity (default)
F30 Parity bit
1 Odd Parity
2 Even Parity
0 115200 bps
1 76800 bps
2 57600 bps
3 38400 bps
4 28800 bps
5 19200 bps
6 14400 bps
7 9600 bps
8 4800 bps
9 2400 bps
0 Unilateral transmission mode
1 Command mode
2 LCD mode
4 External display mode
88
F34 ID Number
F36 BCC selection mode
1~99 (default:1)
0 BCC not used
1 BCC used
0 kg
1g
2 ton
Device Address:
Bit/Word Device type
Format
Range
Memo
CURRENT_WEIGHT_HEAD D
CURRENT_WEIGHT_HEAD D
CURRENT_WEIGHT_HEAD D
CURRENT_WEIGHT_HEAD D
NT: NETWEIGHT
CURRENT_WEIGHT_HEAD D
TARE
TARE_RESET
ZERO
W
W
HOLD
HOLD_RESET
PACKMODE_START
PACKMODE_STOP
KEY_TARE
CURRENT_WEIGHT
CURRENT_WEIGHT_UNIT
LOWEST_LIMIT
UPPER_LIMIT
SERIAL_NUMBER
CODE_NUMBER
PART_NUMBER
89
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
4,5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
4,5 GND
RS232 9P D-Sub
Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
4,5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
4,5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
4,5 GND
90
RS485 4W 9P D-Sub
Female
1 RX-
9 TX-
2 RX+
8 TX+
3 TX-
7 RX-
4 TX+
6 RX+
5 GND
4,5 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Female
7 RX-
9 TX-
6 RX+
8 TX+
9 TX-
7 RX-
8 TX+
6 RX+
5 GND
4,5 GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Female
1 RX-
1 RX-
9 TX-
2 RX+
2 RX+
8 TX+
3 TX-
3 TX-
7 RX-
4 TX+
4 TX+
6 RX+
5 GND
5 GND
4,5 GND
RS485 4W 9P D-Sub
Female
1 RX-
9 TX-
2 RX+
8 TX+
3 TX-
7 RX-
4 TX+
6 RX+
5 GND
4,5 GND
91
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Female
1 RX-
9 TX-
2 RX+
8 TX+
3 TX-
7 RX-
4 TX+
6 RX+
5 GND
4,5 GND
Driver Version:
Version
Date
Description
V1.00
Dec/11/2015
Driver released.
92
CD MODBUS RTU
Supported Series : REVO-CL / REVO-M / REVO E / CD3000E / MULTIDRIVE / REVO-TC
/ REVO-PC
Website : http://www.cdautomation.com/
HMI Setting:
Parameters
Recommended
PLC type
CD MODBUS RTU
PLC I/F
RS485
RS232/RS485
Baud rate
9600
9600~115200
Data bits
7, 8
Parity
Even
Stop bits
1, 2
0-255
Online simulator
YES
Options
Notes
93
Device Address:
Bit/Word Device type
Format
Range
Memo
0x
DDDDD
1 ~ 65535
Output bit
1x
DDDDD
1 ~ 65535
3x_Bit
4x_Bit
B
B
6x_Bit
DDDDDdd 100 ~ 6553515
0x_multi_coils DDDDD
1 ~ 65535
3x
DDDDD
1 ~ 65535
3x_MAX1W
DDDDD
1 ~ 65535
DW
3x_MAX2W
DDDDD
1 ~ 65535
*Note1
4x
DDDDD
1 ~ 65535
Output Register
4x_MAX1W
DDDDD
1 ~ 65535
DW
4x_MAX2W
DDDDD
1 ~ 65535
*Note1
DW
5x
DDDDD
1 ~ 65535
W
W
6x
3x_Double
DDDDD
1 ~ 65535
DDDDD
1 ~ 65535
4x_Double
DDDDD
1 ~ 65535
*Note2
4x_32Bit
DDDDD
1 ~ 65535
0x_single_coil DDDDD
1 ~ 65535
Note1: MAX1W and 4X_32Bit read/write 1 word for each package and display a 32-bits
value, whereas MAX2W reads/write 2 words for each package.
Note2: Go the [System Parameter Settings] -> [Device Properties] and click [Conversion]
to set the data format of device types 3x, 4x, 6x, 3x_double, 4x double.
94
NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost the
same as 4x except that 5x swaps double word.
If 4x contains the following information:
Address
Data in word
0x1
0x2
0x3
0x4
0x5
0x6
Data
0x20001
0x40003
0x60005
Address
Data in
word
0x2
0x1
0x4
0x3
0x6
0x5
...
Data
0x10002
0x30004
...
0x50006
1x
0x02 Read discrete input
N/A for write operation
3x
0x04 Read input register
N/A for write operation
4x
0x03 Read holding register
0x10 write multiple registers
5x
0x03 Read holding register
0x10 write multiple registers
(Note: reverse word order in double word format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 write single register
(Note: 6x is limited to device of one word only)
95
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
96
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Female
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
Driver Version:
Version
Date
V2.30
Jun/24/2014
Description
97
CD MODBUS TCP/IP
Supported Series: REVO-CL / REVO-M / REVO E / CD3000E / MULTIDRIVE / REVO-TC /
REVO-PC
Website : http://www.cdautomation.com/
HMI Setting:
Parameters
Recommended
Options
PLC type
CD MODBUS TCP/IP
PLC I/F
Ethernet
Port no.
502
Notes
0~255
Device Address:
Bit/Word Device type
Format
Range
Memo
0x
DDDDD
1 ~ 65535
Output bit
1x
DDDDD
1 ~ 65535
3x_bit
DDDDDdd
100 ~ 6553515
4x_bit
DDDDDdd
100 ~ 6553515
6x_bit
DDDDDdd
100 ~ 6553515
0x_multi_coils DDDDD
1 ~ 65535
3x
DDDDD
1 ~ 65535
Input Register
4x
DDDDD
1 ~ 65535
Output Register
DW
5x
DDDDD
1 ~ 65535
6x
DDDDD
1 ~ 65535
DW
3x_Double
DDDDD
1 ~ 65535
*Note1
DW
4X_Double
4x string
central
europe
4x string
central
europe (rev)
DDDDD
1 ~ 65535
*Note1
DDDDD
1 ~ 65535
DDDDD
1 ~ 65535
98
Note1: Go the [System Parameter Settings] -> [Device Properties] and click [Conversion]
to set the data format of device types 3x, 4x, 6x, 3x_double, 4x double.
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V1.90
Feb/18/2014
Description
99
Change
Supported Series: Compressor controller
Website: http://www.sh-changjia.com/
HMI Setting:
Parameters
Recommended
PLC type
Change
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
None
Stop bits
Options
Notes
1~6
Device Address:
Bit/Word Device type
Format
Range
Memo
CTL
DDD
0 ~ 5, 128, 150
Write only
DW
SET
DDD
0 ~ 57, 128
DW
STATUS
DD
1 ~ 20
Read only
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
15 D-
2 RX+
9 Data+
16 D+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
COM3 RS485 2W
9P D-Sub Female
9P D-Sub Female
7 RX-
4 Data-
15 D-
6 RX+
1 Data+
16 D+
5 GND
5 GND
100
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
15 D-
2 RX+
8 Data+
16 D+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
15 D-
2 RX+
9 Data+
16 D+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
15 D-
2 RX+
9 Data+
16 D+
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
1 RX-
7 Data-
15 D-
2 RX+
8 Data+
16 D+
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Jan/19/2011
Driver released.
101
Cimon CM1-CP4A/ECO1A
Supported Series: Cimon CM1 series, CP4A module
Website: http://www.kdtsys.com
HMI Setting:
Parameters
Recommended
Options
PLC type
Cimon CM1-CP4A/ECO1A
PLC I/F
RS232
Baud rate
38400
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
DDh
0 ~ 23f
DDh
0 ~ 23f
DDDh
0 ~ 511f
DDDh
0 ~ 127f
DDDh
0 ~ 127f
DDDh
0 ~ 127f
DDDh
0 ~ 102f
DDDh
0 ~ 102f
DDDD
0 ~ 4999
DD
0 ~ 99
TS
DDDD
0 ~ 1023
TC
DDDD
0 ~ 1023
CS
DDDD
0 ~ 1023
CC
DDDD
0 ~ 1023
102
Memo
0-1F Read Only
Read Only
Max. Range: 99
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
CM1-CP4A RS232 6P
RJ11 Male
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
CM1-CP4A RS232 6P
RJ11 Male
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
CM1-CP4A RS232 6P
RJ11 Male
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
CM1-CP4A RS232 6P
RJ11 Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
CM1-CP4A RS232 6P
RJ11 Male
9 RX
2 TXD
6 TX
3 RXD
5 GND
5 GND
103
Driver Version:
Version
Date
V1.20
Nov/30/2009
Description
104
Cimon CM1-SC02A
Supported Series: Cimon CM series, SC02A module
Website: http://www.kdtsys.com
HMI Setting:
Parameters
Recommended
PLC type
Cimon CM1-SC02A
PLC I/F
RS232
Baud rate
38400
Data bits
Parity
None
Stop bits
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
DDh
0 ~ 23f
DDh
0 ~ 23f
DDDh
0 ~ 511f
DDDh
0 ~ 127f
DDDh
0 ~ 127f
DDDh
0 ~ 127f
DDDh
0 ~ 102f
DDDh
0 ~ 102f
DDDD
0 ~ 4999
DD
0 ~ 99
TS
DDDD
0 ~ 1023
TC
DDDD
0 ~ 1023
CS
DDDD
0 ~ 1023
CC
DDDD
0 ~ 1023
105
Memo
Read Only
Max. Range: 99
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
CM1-SC02A RS232 9P
D-Sub Male
2 RX
8 RX
3 TD
3 TX
7 TX
2 RD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
CM1-SC02A RS232 9P
D-Sub Male
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
CM1-SC02A RS232 9P
D-Sub Male
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
CM1-SC02A RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TD
3 TX
4 TX
7 TX
2 RD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
CM1-SC02A RS232 9P
D-Sub Male
9 RX
3 TD
6 TX
2 RD
5 GND
5 GND
106
Driver Version:
Version
Date
V1.20
Nov/30/2009
Description
107
HMI Setting:
Parameters
PLC type
Recommended
Options
CoDeSys Automation Alliance
PLC I/F
Ethernet
Port no.
1200
Notes
Device Address:
Bit/Word
Device type
Format
Range
IX
DDDDDdd
0 ~ 6553515
QX
DDDDDdd
0 ~ 6553515
MX
DDDDDdd
0 ~ 6553515
IW
OOOOOO
0 ~ 65535
QW
DDDDD
0 ~ 65535
MW
DDDDD
0 ~ 65535
ID
DDDDD
0 ~ 65535
QD
DDDDD
0 ~ 65535
MD
DDDDD
0 ~ 65535
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
108
Driver Version:
Version
Date
Description
V1.00
Jun/05/2013
Driver released.
109
CoDeSys V3 (Ethernet)
Supported series: LTI MOTION MO CM-3, MO CM-6
Website: http://www.lti-motion.com/
HMI Setting:
Parameters
Recommended Options
PLC type
CoDeSys V3 (Ethernet)
PLC I/F
Ethernet
Port no.
1740
1742
Notes
Use UDP
110
3. Select PLC_RPG and its tag information is shown, compile the file.
111
5. In System Parameter Settings click [New] to add CoDeSys V3 (Ethernet) driver into
the device list and then click [Tag Manager].
6. In Tag Manager click Get tag -> Import Tag, and then select the tag file (.xml)
generated by the PLC software.
112
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Mar/15/2016
Driver released
113
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
9600
9600~115200
Data bits
Parity
None
Stop bits
Notes
0-127
Device Address:
Bit/Word Device type
Format
Range
Memo
Flash INT 16
HHH
0 ~ 999
RAM INT 16
HHH
0 ~ 999
Flash INT 32
HHH
0 ~ 999
RAM INT 32
HHH
0 ~ 999
Register
DDDD
0 ~ 2457
T_command
Reset
114
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P RJ11: Xenus, Xenus Micro, Accelnet, Stepnet
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
5 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
3, 4 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
D-Sub Female
Male
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
5 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
3, 4 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
5 TXD
6 TX
2 RXD
5 GND
3, 4 GND
115
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
29 TXD
3 TX
7 TX
14 RXD
5 GND
5 GND
15 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
29 TXD
3 TX
14 RXD
5 GND
15 GND
D-Sub Female
RS232 J5 Cable
Connector
2 RX
29 TXD
3 TX
14 RXD
5 GND
15 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
29 TXD
3 TX
4 TX
7 TX
14 RXD
5 GND
5 GND
5 GND
15 GND
116
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
29 TXD
6 TX
14 RXD
5 GND
15 GND
Driver Version:
Version
Date
V1.20
Dec/30/2008
Description
117
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
Ethernet
Port no.
1024
Use UDP
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
VW_Bit
DDDDDo
0 ~ 102397
DDDDo
0 ~ 40957
SCR
SM
DDDDo
0 ~ 40957
Special Memory
T_Bit
DDDD
0 ~ 1023
Timer
C_Bit
DDDD
0 ~ 1023
Counter
DBnBit
FFFDDDDDo 0 ~ 255655357
Byte
VB
DDDDD
0 ~ 10239
VW
DDDDD
0 ~ 10239
V Memory
VW_Odd
DDDDD
0 ~ 10239
V Memory
VW_String
DDDDD
0 ~ 10239
String
VW_String_Odd
DDDDD
0 ~ 10239
String
DW
VD
DDDDD
0 ~ 10239
V Memory Double
DW
VD_Odd
DDDDD
0 ~ 10239
Word
V
Memory Double
DW
VD_String
DDDDD
0 ~ 10239
Word
String
DW
VD_String_Odd
DDDDD
0 ~ 10239
String
Byte
MB
DDDDD
0 ~ 10239
Byte Memory
MW
DDDDD
0 ~ 10239
Word Memory
MW_Odd
DDDDD
0 ~ 10239
Word Memory
DW
MD
DDDDD
0 ~ 10239
Word Memory
118
Bit/Word
Device type
Format
Range
Memo
Byte
SB
DDDDD
0 ~ 10239
SCR
SW
DDDDD
0 ~ 10239
SCR
DW
SD
DDDDD
0 ~ 10239
SCR
Byte
SMB
DDDDD
0 ~ 10239
Special Memory
SMW
DDDDD
0 ~ 10239
Special Memory
DW
SMD
DDDDD
0 ~ 10239
Special Memory
DDD
0 ~ 1023
Timer
DDD
0 ~ 1023
Counter
Byte
DBBn
FFFDDDDD
0 ~ 65535
DBn
FFFDDDDD
0 ~ 65535
DW
DBDn
FFFDDDDD
0 ~ 65535
DBn_STRINGCHAR FFFDDDDD
0 ~ 65535
Double Word and floating point value must use VD device type.
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Jan/04/2016
Driver released.
119
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485 2W
RS485 2W
Baud rate
9600
Data bits
7,8
Parity
Even
Stop bits
1, 2
30
Online simulator
Options
Notes
1 ~ 126
YES
Broadcast command NO
PLC Setting:
PLC setting
PLC sta. no. can not be the same as HMI sta. no.
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
VW_Bit
DDDDDo
0 ~ 102397
DDDDo
0 ~ 40957
SCR
SM
DDDDo
0 ~ 40957
Special Memory
T_Bit
DDDD
0 ~ 1023
Timer
C_Bit
DDDD
0 ~ 1023
Counter
DBnBit
FFFDDDDDo 0 ~ 255655357
120
Bit/Word
Device type
Format
Range
Byte
VB
DDDDD
0 ~ 10239
VW
DDDDD
0 ~ 10239
V Memory
VW_Odd
DDDDD
0 ~ 10239
V Memory
VW_String
DDDDD
0 ~ 10239
String
VW_String_Odd
DDDDD
0 ~ 10239
String
DW
VD
DDDDD
0 ~ 10239
V Memory Double
DW
VD_Odd
DDDDD
0 ~ 10239
Word
V
Memory Double
DW
VD_String
DDDDD
0 ~ 10239
Word
String
DW
VD_String_Odd
DDDDD
0 ~ 10239
String
Byte
MB
DDDDD
0 ~ 10239
Byte Memory
MW
DDDDD
0 ~ 10239
Word Memory
MW_Odd
DDDDD
0 ~ 10239
Word Memory
DW
MD
DDDDD
0 ~ 10239
Word Memory
Byte
SB
DDDDD
0 ~ 10239
SCR
SW
DDDDD
0 ~ 10239
SCR
DW
SD
DDDDD
0 ~ 10239
SCR
Byte
SMB
DDDDD
0 ~ 10239
Special Memory
SMW
DDDDD
0 ~ 10239
Special Memory
DW
SMD
DDDDD
0 ~ 10239
Special Memory
DDD
0 ~ 1023
Timer
DDD
0 ~ 1023
Counter
Byte
DBBn
FFFDDDDD
0 ~ 65535
DBn
FFFDDDDD
0 ~ 65535
DW
DBDn
FFFDDDDD
0 ~ 65535
DBn_STRINGCHAR FFFDDDDD
0 ~ 65535
Double Word and floating point value must use VD device type.
121
Memo
122
Note:
HMI sta. no. can not be the same as PLC sta. no.
Highly recommended that HMI sta. no. starts from 0 and go on sequentially for the
effectiveness of operation.
Available for EasyBuilder8000 V4.50 and later.
123
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
3 D+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
124
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
5 GND
5 GND
Driver Version
Version
Date
Description
V1.00
Oct/12/2015
Driver released.
125
CROUZET M3 (FBD)
HMI Setting:
Parameters
Recommended
PLC type
CROUZET M3 (FBD)
PLC I/F
RS232
Baud rate
115200
Data bits
Parity
Even
Stop bits
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
DD
1 ~ 99
Input
SLI_Bit
DDh
10 ~ 24f
SLO_Bit
DDh
250 ~ 48f
State
AI
DD
1 ~ 99
SL_IN
DD
1 ~ 24
SL_OUT
DD
25 ~ 48
Time
1~6
Order
126
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)
2 RX
2 TD
3 TX
3 RD
5 GND
5 GND
7 RTS
4 DTR
cMT/mTV series
COM1 RS232 9P
D-Sub Female
CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
4 DTR
CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)
2 RX
2 TD
3 TX
3 RD
5 GND
5 GND
7 RTS
4 DTR
CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)
2 RX
2 TD
3 TX
3 RD
5 GND
5 GND
7 RTS
4 DTR
127
MTx050i/MTx050iP/MTx050iE Series
COM1 RS232 9P
D-Sub Male
CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)
9 RX
2 TD
6 TX
3 RD
5 GND
5 GND
4 TX+
4 DTR
Driver Version:
Version
Date
Description
V1.10
Oct/26/2010
V1.20
Mar/29/2012
V1.30
May/14/2012
V1.60
Jun/05/2013
128
CROUZET M3 (LAD)
HMI Setting:
Parameters
Recommended
PLC type
CROUZET M3 (LAD)
PLC I/F
RS232
Baud rate
115200
Data bits
Parity
Even
Stop bits
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
DD
1 ~ 99
Input (default: 1 ~ 4)
DD
1 ~ 99
Output (default: 1 ~ 4)
DD
1 ~ 28
Relay
SLI_Bit
DDh
10 ~ 24f
SLO_Bit
DDh
250 ~ 48f
State
DD
1 ~ 12
Timer
DD
1 ~ 16
Counter
AI
DD
1 ~ 99
SL_IN
DD
1 ~ 24
SL_OUT
DD
25 ~ 48
Time
1~6
Order
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)
2 RX
2 TD
3 TX
3 RD
5 GND
5 GND
7 RTS
4 DTR
cMT/mTV series
COM1 RS232 9P
D-Sub Female
CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
4 DTR
CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)
2 RX
2 TD
3 TX
3 RD
5 GND
5 GND
7 RTS
4 DTR
CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)
2 RX
2 TD
3 TX
3 RD
5 GND
5 GND
7 RTS
4 DTR
130
MTx050i/MTx050iP/MTx050iE Series
COM1 RS232 9P
D-Sub Male
CROUZET M3 RS232
9P D-Sub Male
(Extension Cable)
9 RX
2 TD
6 TX
3 RD
5 GND
5 GND
4 TX+
4 DTR
Driver Version:
Version
Date
Description
V1.20
Oct/26/2010
V1.30
Mar/30/2012
V1.40
May/14/2012
V1.70
Jun/05/2013
131
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
None
Stop bits
Options
Notes
Memo
Device Address:
Bit/Word Device type
Format
Range
Flag
DDDD
0 ~ 8191
Output
DDDD
0 ~ 1023
Input
DDDD
0 ~ 1023
Reg_Bit
DDDDDdd
0 ~ 1638331
DW
Register
DDDDD
0 ~ 16383
DW
Counter
DDDD
0 ~ 1599
DW
Timer
DDDD
0 ~ 1599
DW
Reg_Float
DDDDD
0 ~ 16383
EasyBuilder device address range may differ from PLC extended mode, please refer to
EasyBuilder address range as above.
132
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
133
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
11 / 29
2 RX+
9 Data+
12 / 28
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
11 / 29
6 RX+
1 Data+
12 / 28
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
11 / 29
2 RX+
8 Data+
12 / 28
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
11 / 29
2 RX+
9 Data+
12 / 28
5 GND
5 GND
134
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
11 / 29
2 RX+
9 Data+
12 / 28
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
1 RX-
7 Data-
11 / 29
2 RX+
8 Data+
12 / 28
5 GND
5 GND
Driver Version:
Version
Date
V1.40
OCT/06/2008
Description
135
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
5050
Notes
Device Address:
Bit/Word Device type
Format
Range
Flag
DDDD
0 ~ 8191
Output
DDDD
0 ~ 1023
Input
DDDD
0 ~ 1023
Reg_Bit
DDDDDdd
0 ~ 1638331
Register
DDDDD
0 ~ 16383
Counter
DDDD
0 ~ 1599
Timer
DDDD
0 ~ 1599
Reg_Float
DDDDD
0 ~ 16383
Memo
EasyBuilder device address range may differ from PLC extended mode, please refer to
EasyBuilder address range as above.
136
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V1.10
Jan/10/2011
Description
137
Danfoss FC Series
Supported Series: FC051, FC100, FC200, FC300, VLT Micro Driver.
Website: http://www.danfoss.com/
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
Danfoss FC Series
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
Even
Stop bits
Format
Range
Memo
Device Address:
Bit/Word Device type
W
Parameter
09
DDDD
0 ~ 9999
Set Parameter
DW
Reference
10
0~1
DW
Para_Index
11
DDDDDD
0 ~ 999999
Set Parameter(Index)
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
FC RS485 terminal
1 RX-
6 Data-
69 D-
2 RX+
9 Data+
68 D+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
COM3 RS485 2W
FC RS485 terminal
9P D-Sub Female
9P D-Sub Female
7 RX-
4 Data-
69 D-
6 RX+
1 Data+
68 D+
5 GND
5 GND
138
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
FC RS485 terminal
1 RX-
7 Data-
69 D-
2 RX+
8 Data+
68 D+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
FC RS485 terminal
1 RX-
6 Data-
69 D-
2 RX+
9 Data+
68 D+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
FC RS485 terminal
1 RX-
6 Data-
69 D-
2 RX+
9 Data+
68 D+
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
FC RS485 terminal
1 RX-
7 Data-
69 D-
2 RX+
8 Data+
68 D+
5 GND
5 GND
139
Driver Version:
Version
Date
V1.10
Jan/14/2010
Description
140
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
Even
Stop bits
Options
Notes
0-126
According to PLC
PLC Setting:
Communication mode
Device Address:
Bit/Word
DW
Device type
Format
Range
Memo
Parameter
DDDD
0 ~ 2000
Set Parameter
Reference
0~1
141
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
69 D-
2 RX+
9 Data+
68 D+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
7 RX-
4 Data-
69 D-
6 RX+
1 Data+
68 D+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
7 Data-
69 D-
2 RX+
8 Data+
68 D+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
69 D-
2 RX+
9 Data+
68 D+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
69 D-
2 RX+
9 Data+
68 D+
5 GND
5 GND
142
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
1 RX-
7 Data-
69 D-
2 RX+
8 Data+
68 D+
5 GND
5 GND
Driver Version:
Version
Date
V1.10
Dec/30/2008
Description
143
DELTA DVP
Supported Series: DELTA DVP series
Website: http://www.deltadriver.com
HMI Setting:
Parameters
Recommended
Options
PLC type
DELTA DVP
PLC I/F
RS232
RS232, RS485
Baud rate
9600
9600, 19200
Data bits
7, 8
Parity
Even
Stop bits
0-255
Notes
Device Address:
Bit/Word Device type
Format
Range
Memo
OOOOO
0 ~ 23417 (octal)
Input
OOOOO
0 ~ 23417 (octal)
Output
DDDDD
0 ~ 65536
Auxiliary Relay
DDDD
0 ~ 9999
Step Relay
DDDD
0 ~ 9999
Timer
DDDD
0 ~ 9999
Counter
TV_Bit
DDDDdd 0 ~ 999915
Timer
TV
DDDD
0 ~ 9999
Timer
CV
DDD
0 ~ 127
Counter
CV2
DDD
200 ~ 254
DDDD
0 ~ 9999
Data Register
144
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
8 RX
5 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
3/8 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
5 TXD
3 TX
4 RXD
5 GND
3/8 GND
RS232 8P Mini-DIN
Male
2 RX
5 TXD
3 TX
4 RXD
5 GND
3/8 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 8P Mini-DIN
Male
2 RX
6 RX
8 RX
5 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
3/8 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
9 RX
5 TXD
6 TX
4 RXD
5 GND
3/8 GND
View from the
soldering point
of a cable.
145
COM3 RS485 2W
9P D-Sub Male
RS485 2W port
1 RX-
6 Data-
2 Data-
2 RX+
9 Data+
1 Data+
5 GND
5 GND
3 GND
COM2 RS485 2W
COM3 RS485 2W
RS485 terminal
9P D-Sub Female
9P D-Sub Female
7 RX-
4 Data-
2 Data-
6 RX+
1 Data+
1 Data+
5 GND
5 GND
3 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
7 Data-
2 Data-
2 RX+
8 Data+
1 Data+
5 GND
9 GND
3 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
2 Data-
2 RX+
9 Data+
1 Data+
5 GND
5 GND
3 GND
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
2 Data-
2 RX+
9 Data+
1 Data+
5 GND
5 GND
3 GND
146
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
1 RX-
7 Data-
2 Data-
2 RX+
8 Data+
1 Data+
5 GND
5 GND
3 GND
Driver Version:
Version
Date
V1.20
Dec/30/2008
Description
147
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
502
Notes
Device Address:
Bit/Word Device type
Format
Range
C_Bit
DDD
0 ~ 255
DDDD
0 ~ 4095
DDDD
0 ~ 1023
T_Bit
DDD
0 ~ 255
OOO
0 ~ 571
OOO
0 ~ 571
DDD
0 ~ 199
DW
C_32Bit
DDD
200 ~ 255
DDDDD
0 ~ 11999
DDD
0 ~ 255
148
Memo
PLC Setting:
1. Communication Setting
Add a new program, click File > New, enter the Program Title and File Name, and select
the correct controller type. Click Setting to configure the communication parameters. Click
OK to confirm the setting. The communication with PLC starts.
2. Transfer Setup
Click Communication and select PC<=>(PLC | HPP), on Transfer Setup dialog box,
select the needed parameters for upload or download, and click OK to start the action.
149
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Jun/11/2012
Driver released.
V1.10
Aug/20/2012
150
DL-BCM Server
Website: http://www.hzdelin.com
HMI Setting:
Parameters
Recommended
Options
PLC type
DL-BCM Server
PLC I/F
RS232
RS232, RS485
Baud rate
9600
9600~115200
Data bits
Parity
None
Stop bits
0-31
Notes
Device Address:
Bit/Word
Device type
Format
Range
LB
dddd
0 ~ 9998
LW
dddd
0 ~ 9998
RW
ddddd
0 ~ 55536
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
FeMale
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
RTS
CTS
151
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
FeMale
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
RS232 9P D-Sub
FeMale
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
COM2 RS232 9P
COM3 RS232
RS232 9P D-Sub
D-Sub Female
D-Sub Female
9P D-Sub Male
FeMale
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
RTS
CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
RS232 9P D-Sub
D-Sub Female
FeMale
9 RX
TXD
6 TX
RXD
5 GND
GND
RTS
CTS
152
short
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
COM3 RS485 2W
RS485 2W 9P D-Sub
9P D-Sub Female
9P D-Sub Female
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
3 D+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
153
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Dec/8/2008
Driver released
154
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
Even
Stop bits
Notes
Device Address:
Bit/Word Device type
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
B621
B622
B623
zero phase
B611
B612
B613
B631
B632
B633
B630
B641
B642
B643
B640
A-apparentT
B-apparentT
C-apparentT
T-apparentT
B650
Format
Range
0~1
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
155
Memo
B651
B652
B653
9010
9020
9110
9120
9130
9140
9150
9160
9410
9420
9510
9520
9530
9540
9550
9560
9810
9820
9910
9920
9930
9940
9950
9960
A010
A020
A110
A120
A130
A140
A150
A160
A410
A420
A510
A520
A530
Format
Range
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
156
Memo
A540
A550
A560
A810
A820
A910
A920
A930
A940
A950
A960
B010
B020
B110
B120
B130
B140
B150
B160
B410
B420
B510
B520
B530
B540
B550
B560
B810
B820
B910
B920
B930
B940
B950
B960
B210
B211
B212
B213
B214
Format
Range
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
157
Memo
B310
B311
B312
B313
B320
B321
B322
B323
B330
B331
B332
B333
B340
B341
B342
B343
C010
C011
C020
C021
C022
C030
C031
C032
C033
C034
C111
C112
C113
C114
C115
C116
C117
C118
C119
C11A
C211
C212
C310
C311
Format
Range
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
158
Memo
C312
C313
C314
C320
C321
C322
C330
C331
C332
C340
C341
C342
C3A0
C3A1
C3A2
C410
C411
C41E
C510
C511
B634
B635
Format
Range
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
0~1
159
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
13 RS485B1
2 RX+
9 Data+
12 RS485A1
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
7 RX-
4 Data-
13 RS485B1
6 RX+
1 Data+
12 RS485A1
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
7 Data-
13 RS485B1
2 RX+
8 Data+
12 RS485A1
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
13 RS485B1
2 RX+
9 Data+
12 RS485A1
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
13 RS485B1
2 RX+
9 Data+
12 RS485A1
5 GND
5 GND
160
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
1 RX-
7 Data-
13 RS485B1
2 RX+
8 Data+
12 RS485A1
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Apr/13/2011
Driver released.
161
DL/T645 Standard
Website: http://www.cw180.com
HMI Setting:
Parameters
Recommended
PLC type
DL/T645 Standard
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
Even
Stop bits
Options
PLC Setting:
162
Notes
System Tag:
LW-10700 (4 words)
LW-10704 (4 words)
LW-10708 (6 words)
LW-10715 (4 words)
LW-10719 (4 words)
LW-10723 (6 words)
LW-10730 (4 words)
LW-10734 (4 words)
LW-10738 (6 words)
Device Address:
Bit/Word Device type
W
Data
Format
Range
Memo
HHHHHHHH 0 ~ 6FFFFFF
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
163
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Apr/14/2011
Driver released.
164
DL/T645-2007 Standard
Website: http://www.cw180.com
HMI Setting:
Parameters
Recommended
Options
PLC type
DL/T645-2007 Standard
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
Even
Stop bits
PLC Setting:
165
Notes
System Tag:
LW-10700 (4 words)
LW-10704 (4 words)
LW-10708 (6 words)
LW-10715 (4 words)
LW-10719 (4 words)
LW-10723 (6 words)
LW-10730 (4 words)
LW-10734 (4 words)
LW-10738 (6 words)
Device Address:
Bit/Word Device type
W
Data
Format
Range
Memo
HHHHHHHH 0 ~ 6FFFFFF
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
166
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
Driver Version:
Version
Date
V1.20
Jul/27/2015
Description
167
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485
RS232/RS485
Baud rate
9600
9600~115200
Data bits
7,8
Parity
Even
Stop bits
1,2
0-255
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
1x
DDDDD
1 ~ 65535
%MX
DDDDD
1 ~ 65535
3x_Bit
DDDDDdd
100 ~ 6553515
%MW_Bit
DDDDDdd
100 ~ 6553515
3x
DDDDD
1 ~ 65535
%MW
DDDDD
1 ~ 65535
6x
DDDDD
1 ~ 65535
168
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
6 TXD
3 TX
7 TX
5 RXD
5 GND
5 GND
4 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
6 TXD
3 TX
5 RXD
5 GND
4 GND
2 RX
6 TXD
3 TX
5 RXD
5 GND
4 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
6 TXD
3 TX
4 TX
7 TX
5 RXD
5 GND
5 GND
5 GND
4 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
6 TXD
6 TX
5 RXD
5 GND
4 GND
169
COM3 RS485 2W
9P D-Sub Male
RS485 2W
3-Way TB
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
3 GND
COM2 RS485 2W
COM3 RS485 2W
RS485 2W
9P D-Sub Female
9P D-Sub Female
3-Way TB
7 RX-
4 Data-
2 D-
6 RX+
1 Data+
1 D+
5 GND
5 GND
3 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W
3-Way TB
1 RX-
7 Data-
2 D-
2 RX+
8 Data+
1 D+
5 GND
9 GND
3 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W
3-Way TB
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
3 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W
3-Way TB
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
3 GND
170
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W
3-Way TB
1 RX-
7 Data-
2 D-
2 RX+
8 Data+
1 D+
5 GND
5 GND
3 GND
Driver Version:
Version
Date
V1.50
Feb/18/2014
Description
171
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485
RS232/RS485
Baud rate
9600
9600~115200
Data bits
7, 8
Parity
Even
Stop bits
1, 2
0-255
Online simulator
YES
Options
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
%MX
DDDDD
0 ~ 65535
%MX_Bit
DDDDDdd 0 ~ 6553515
%MW
DDDDD
0 ~ 6553515
%MWD
DDDDD
0 ~ 6553515
172
Memo
0x01 Read coil
0x05 write single coil
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
6 TXD
3 TX
7 TX
5 RXD
5 GND
5 GND
4 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
6 TXD
3 TX
5 RXD
5 GND
4 GND
2 RX
6 TXD
3 TX
5 RXD
5 GND
4 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
6 TXD
3 TX
4 TX
7 TX
5 RXD
5 GND
5 GND
5 GND
4 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
6 TXD
6 TX
5 RXD
5 GND
4 GND
173
COM3 RS485 2W
9P D-Sub Male
RS485 2W
3-Way TB
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
3 GND
COM2 RS485 2W
COM3 RS485 2W
RS485 2W
9P D-Sub Female
9P D-Sub Female
3-Way TB
7 RX-
4 Data-
2 D-
6 RX+
1 Data+
1 D+
5 GND
5 GND
3 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W
3-Way TB
1 RX-
7 Data-
2 D-
2 RX+
8 Data+
1 D+
5 GND
9 GND
3 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W
3-Way TB
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
3 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W
3-Way TB
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
3 GND
174
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W
3-Way TB
1 RX-
7 Data-
2 D-
2 RX+
8 Data+
1 D+
5 GND
5 GND
3 GND
Driver Version:
Version
Date
V2.30
Jun/24/2014
Description
175
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
502
Notes
0~255
PLC Setting:
Communication mode
Modbus TCP/IP
Device Address:
Bit/Word Device type
Format
Range
Memo
%MX
DDDDD
0 ~ 65535
%MW_Bit
DDDDDdd
0 ~ 6553515
%MW
DDDDD
0 ~ 65535
DW
%MWD
DDDDD
0 ~ 65535
176
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V1.90
Feb/18/2014
Description
177
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS-232
Baud rate
9600
Data bits
Parity
Odd
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
Float_Point_Forced
0~1
Average_Point_Forced D
0~1
Switch_Status
0~1
Manual_Status
0~1
Protect_Status
0~1
Failure_Status
0~1
Preset_Voltage
0~1
Preset_Percent
0~1
Output_Voltage
0~1
Output_Current
0~1
High_Limit
0~1
Low_Limit
0~1
Float_Point_Setting
0~1
Average_Point_Setting D
0~1
178
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 terminal
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 terminal
2 RX
TXD
3 TX
RXD
5 GND
GND
RS232 terminal
2 RX
TXD
3 TX
RXD
5 GND
GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 terminal
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 terminal
9 RX
TXD
6 TX
RXD
5 GND
GND
179
Driver Version:
Version
Date
V1.00
Mar/3/2009
Description
180
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
1234
1234
181
Notes
Bool
bit
Byte
8-bit
DInt
Real
32-bit Float
32-bit
UDInt
32-bit
SInt
USInt
Word
Int
UInt
DWord
Memo
8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit
* For device types: DWord / DINT / UDINT / Real , error may occur if the value exceeds 7
digits (million).
182
PLC Setting:
1. Under Global Variables create the tags, a tag name with over 20 words can affect
communicaiton, please avoid it.
2. Open the program from Programs -> OpenBSI Tool -> Common Tools -> Signal
Extractor.
183
3. Browse for the file name in Load File field, and then the Output File field will
automatically generate the SIG file name. In IEC-61131 Options group box, deselect
Datatype conversion enable and Output MSD Values check boxes, and then click
Start to generate the file for tag import.
184
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Nov/12/2015
Driver released
185
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
RS232
Baud rate
9600
Data bits
7 or 8
Parity
Even
Stop bits
1 or 2
0-255
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
OOO
0 ~ 377
0000-02550
OOO
0 ~ 377
1200-01455
DDDD
0 ~ 1999
2000-3999
SM
DDD
0~ 255
4400-4655
DDD
0 ~ 991
6000-6991
DDD
0 ~ 255
8000-8255
DDD
0 ~ 255
9200-9455
DDDD
0 ~ 7999
0000-7999
SD
DDD
0 ~ 255
8000-8255
DD
0 ~ 15
8500-8515
DDD
0 ~ 255
9000-9255
DDD
0 ~ 199
9500-9699
DW
C_Double
DDD
200 ~ 255
9700-9811
DW
D_Double
DDDD
0 ~ 7998
0000-7999
186
0000-0255
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
TXD
3 TX
RXD
5 GND
GND
2 RX
TXD
3 TX
RXD
5 GND
GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
TXD
6 TX
RXD
5 GND
GND
187
Driver Version:
Version
Date
V1.10
Dec/30/2008
Description
188
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
RS232
RS232/RS485 2W
Baud rate
38400
9600 ~ 115200
Data bits
7,8
Parity
None
None,Odd,Even
Stop bits
1,2
0-255
PLC Setting:
Protocol type
1,4
Device Address:
Bit/Word
Device type
Format
Range
X_Bit
Hh
0 ~ 5f
Y_Bit
Hh
0 ~ 4f
F_Bit
Dh
0 ~ 9f
M_Bit
DDDh
0 ~ 199f
T_Bit
Dh
0 ~ 0f
C_Bit
Dh
0 ~ 0f
0~5
0~4
0~9
DDD
0 ~ 199
TP
DD
0 ~ 15
TC
DD
0 ~ 15
189
Memo
Bit/Word
Device type
Format
Range
CP
DD
0 ~ 15
CC
DD
0 ~ 15
DW
PD_X
DD
0 ~ 99
DW
PD_Y
DD
0 ~ 99
DW
FD
0~9
DW
DD
0~9
DW
LD
DDDD
0 ~ 1999
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
190
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
7 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
7 D+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
7 D+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
7 D+
5 GND
5 GND
5 GND
191
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
7 D+
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
7 D+
5 GND
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Sep/04/2015
Driver released
192
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
Even
Stop bits
Port no.
500
Notes
RS232/RS485/Ethernet
0-255
Device Address:
Bit/Word
B
Device type
Format
Range
Memo
DDDD
0 ~ 9999
Input
DDDD
0 ~ 9999
Output
DDDD
0 ~ 9999
Internal Relay
DDDD
0 ~ 9999
Step Relay
DDDD
0 ~ 9999
Timer
DDDD
0 ~ 9999
PLC_MODE
Counter
PLC mode
R_Bit
DDDDdd
0 ~ 999915
D_Bit
DDDDdd
0 ~ 999915
RT
DDDD
0 ~ 9999
Timer Register
RC
DDDD
0 ~ 9999
Counter Register
DDDD
0 ~ 9999
Data Register
DDDD
0 ~ 9999
Data Register
DRT
DDDD
0 ~ 9999
DRC
DDD
200 ~ 255
193
Bit/Word
W
Device type
Format
Range
WX
DDDD
0 ~ 9999
Memo
Input Word
WY
DDDD
0 ~ 9999
Output Word
WM
DDDD
0 ~ 9999
WS
DDDD
0 ~ 9999
FR
DDDD
0 ~ 9999
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 4P Mini-DIN: FBs Port0
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
4 RX
5 GND
5 GND
2 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
4 RX
5 GND
2 GND
2 RX
3 TX
3 TX
4 RX
5 GND
2 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
4 RX
5 GND
5 GND
5 GND
2 GND
194
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
4 RX
5 GND
2 GND
View from the
soldering point
of a cable.
COM3 RS232 9P
D-Sub Female
FBs communication
module RS232 9P
D-Sub Male
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
FBs communication
module RS232 9P
D-Sub Male
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
FBs communication
D-Sub Female
module RS232 9P
D-Sub Male
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
195
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
FBs communication
module RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
FBs communication
D-Sub Female
module RS232 9P
D-Sub Male
9 RX
2 TX
6 TX
3 RX
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
FBs communication
module 3P Terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
COM3 RS485 2W
FBs communication
9P D-Sub Female
9P D-Sub Female
module 3P Terminal
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
FBs communication
module 3P Terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
196
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
FBs communication
module 3P Terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
FBs communication
module 3P Terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
FBs communication
module 3P Terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
1 RX
5 GND
5 GND
6 GND
3 RTS
4 CTS
197
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TX
3 TX
1 RX
5 GND
6 GND
3 RTS
4 CTS
short
2 RX
2 TX
3 TX
1 RX
5 GND
6 GND
3 RTS
4 CTS
short
COM2 RS232 9P
COM3 RS232 9P
D-Sub Female
D-Sub Female
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
1 RX
5 GND
5 GND
5 GND
6 GND
3 RTS
4 CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TX
6 TX
1 RX
5 GND
6 GND
3 RTS
4 CTS
198
short
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
7 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
7 D-
6 RX+
1 Data+
5 D+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
7 D-
2 RX+
8 Data+
5 D+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
7 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
7 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
199
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
1 RX-
7 Data-
7 D-
2 RX+
8 Data+
5 D+
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.60
Feb/17/2011
V1.70
Nov/29/2011
200
Fuji NB Series
Website: http://www.fujielectric.com/fcs/index.html
HMI Setting:
Parameters
Recommended
PLC type
Fuji NB Series
PLC I/F
RS485 4W
Baud rate
19200
Data bits
Parity
Odd
Stop bits
Options
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
HHH
0 ~ 7ff
Output Relay
HHH
0 ~ 3ff
Input Relay
HHH
0 ~ fff
Internal Relay
HHH
0 ~ fff
Latch Relay
HH
0 - ff
Counter
M_Spe
HHHH
0 ~ 81ff
Special Relay
HHH
0 ~ 1ff
Timer
TV
HHH
0 ~ 3ff
Timer value
CV
HHH
0 ~ 3ff
Counter value
HHHH
0 ~ 1fff
Data Register
D_Spe
HHHH
0 ~ 81ff
Special Register
201
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
1 RX-
4 TX-
2 RX+
3 TX+
3 TX-
6 RX-
4 TX+
5 RX+
5 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
4 TX-
6 RX+
3 TX+
9 TX-
6 RX-
8 TX+
5 RX+
5 GND
MT8000iE/MT8000XE series except MT8050iE
COM1 RS485 4W
9P D-Sub Male
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
4 TX-
2 RX+
2 RX+
3 TX+
3 TX-
3 TX-
6 RX-
4 TX+
4 TX+
5 RX+
5 GND
5 GND
1 RX-
4 TX-
2 RX+
3 TX+
3 TX-
6 RX-
4 TX+
5 RX+
5 GND
202
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
4 TX-
2 RX+
3 TX+
3 TX-
6 RX-
4 TX+
5 RX+
5 GND
Driver Version:
Version
Date
V1.10
May/05/2009
Description
203
HMI Setting:
Parameters
Recommended Options
PLC type
PLC I/F
Ethernet
Port no.
507
Notes
251 ~ 65531
When setting port number, please add the offset 251. As shown below, the value in the
software is 1024, then the port number should be: 1024+251=1275.
204
Device Address:
Bit/Word Device type
Format
Range
Memo
DDDDDDh
10 ~ 238511f
DDDDDDh
10 ~ 238511f
DDDDh
0 ~ 8191f
DDDDh
0 ~ 4095f
SM
DDDh
0 ~ 511f
DD.DD
0 ~ 99.99
WX
DDDDDD
1 ~ 238511
DDD(Slot) / DDD(word)
WY
DDDDDD
1 ~ 238511
DDD(Slot) / DDD(word)
WM
DDDD
0 ~ 8191
DW
DM
DDDDD
0 ~ 16382
WL
DDDD
0 ~ 4095
DW
DL
DDDD
0 ~ 8190
WSM
DDD
0 ~ 511
DW
DSM
DDD
0 ~ 510
WS
DD
0 ~ 99
DW
DX
DDDDDD
DW
DY
DDDDDD
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V1.10
May/04/2015
Description
Added registersDX,DY
205
GE Fanuc 0i MD
Website: http://www.fanucfa.com/welcome_worldwide/
HMI Setting:
Parameters
Recommended
PLC type
GE Fanuc 0i MD
PLC I/F
RS232
Baud rate
19200
Data bits
Parity
Even
Stop bits
On-line simulation
Options
Notes
YES
PLC Setting:
Reader/Puncher interface (2ch.) is used for touch panel interface.
External touch panel interface, S/N: A02B-0320-J685, for Power Mate Series.
Device Address:
Bit/Word
Device type
Format
Range
DDDDo
0 ~ 11277
DDDDo
0 ~ 11277
DDDo
0 ~ 9997
DDDDo
0 ~ 99997
D_Bit
DDDDo
0 ~ 99997
R_Bit
DDDDo
0 ~ 94997
DDDD
0 ~ 9499
Must be a multiple of 2
DDDD
0 ~ 5199
Must be a multiple of 4
D_Byte
DDDD
0 ~ 9999
R_Byte
DDDD
0 ~ 9499
DDDD
0 ~ 9999
Must be a multiple of 2
DDDD
0 ~ 9499
Must be a multiple of 2
206
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
11 TX
3 TX
7 TX
1 RX
5 GND
5 GND
short
03 DR
07 CD
short
13 ER
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
11 TX
3 TX
1 RX
5 GND
short
03 DR
07 CD
short
13 ER
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P
D-Sub Female
2 RX
11 TX
3 TX
1 RX
5 GND
short
03 DR
07 CD
13 ER
207
short
COM2 RS232 9P
D-Sub Female
COM3 RS232
9P D-Sub Male
2 RX
6 RX
8 RX
11 TX
3 TX
4 TX
7 TX
1 RX
5 GND
5 GND
5 GND
short
03 DR
07 CD
short
13 ER
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
11 TX
6 TX
1 RX
5 GND
short
03 DR
07 CD
13 ER
Driver Version:
Version
Date
Description
V1.00
May/16/2011
Driver released.
208
short
GE Fanuc CMM
Website: http://www.ge.com
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
GE Fanuc CMM
PLC I/F
RS232
RS232/RS485
Baud rate
19200
9600,19200,38400,5
7600,115200
Data bits
7,8
Parity
Odd
Stop bits
1, 2
0-255
PLC Setting:
Refer to the related PLC manual.
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDD
1 ~ 10000
Input relay
DDDDD
1 ~ 10000
Output relay
DDDDD
1 ~ 10000
Auxiliary relay
DDDD
1 ~ 7680
DDD
1 ~ 256
SA
DDD
1 ~ 128
SB
DDD
1 ~ 128
SC
DDD
1 ~ 128
DDD
1 ~ 128
AI
DDDDD
1 ~ 10000
AQ
DDDDD
1 ~ 10000
DDDDD
1 ~ 32640
Data register
209
Wiring Diagram:
The following is the view from the soldering point of a cable.
CPU Port 90-30/VersaMax
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
90-30/VersaMax RS485
4W 15P D-Sub Male
1 RX-
12 SDA
2 RX+
13 SDB
5 GND
7 GND
3 TX-
10 RDA
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
short
short
short
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
90-30/VersaMax RS485
4W 15P D-Sub Male
7 RX-
12 SDA
6 RX+
13 SDB
5 GND
7 GND
9 TX-
10 RDA
8 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
210
short
short
short
COM2 RS485 4W
9P D-Sub Male
90-30/VersaMax RS485
4W 15P D-Sub Male
1 RX-
1 RX-
12 SDA
2 RX+
2 RX+
13 SDB
5 GND
5 GND
7 GND
3 TX-
3 TX-
10 RDA
4 TX+
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
short
short
short
90-30/VersaMax RS485
4W 15P D-Sub Male
1 RX-
12 SDA
2 RX+
13 SDB
5 GND
7 GND
3 TX-
10 RDA
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
211
short
short
short
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
90-30/VersaMax RS485
4W 15P D-Sub Male
1 RX-
12 SDA
2 RX+
13 SDB
5 GND
7 GND
3 TX-
10 RDA
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
short
short
short
COM3 RS232 9P
D-Sub Female
90-30/90-70 series
RS232 6P RJ11 Male
2 RX
8 RX
2 TX
3 TX
7 TX
5 RX
5 GND
5 GND
3 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
90-30/90-70 series
RS232 6P RJ11 Male
2 RX
2 TX
3 TX
5 RX
5 GND
3 GND
90-30/90-70 series
RS232 6P RJ11 Male
2 RX
2 TX
3 TX
5 RX
5 GND
3 GND
212
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
90-30/90-70 series
RS232 6P RJ11 Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
5 RX
5 GND
5 GND
5 GND
3 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
90-30/90-70 series
RS232 6P RJ11 Male
9 RX
2 TX
6 TX
5 RX
5 GND
3 GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
9P D-Sub Male
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
213
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TX
6 TX
3 RX
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Jul/09/2009
Driver released.
214
GE Fanuc RX3i
Website: http://www.ge.com
HMI Setting:
Parameters
Recommended
Options
PLC type
GE Fanuc RX3i
PLC I/F
RS232
RS232, RS485
Baud rate
19200
1200~115200
Data bits
Parity
Odd
Stop bits
1 or 2
SNP ID
0~255 (None)
Notes
PLC Setting:
Port Mode
SNP Slave
Device Address:
Bit/Word
Device type
Format
Range
DDDDD
1 ~ 32768
DDDDD
1 ~ 32768
DDDDD
1 ~ 32768
DDDDD
1 ~ 32768
DDDDD
1 ~ 32768
SA
DDDDD
1 ~ 32768
SB
DDDDD
1 ~ 32768
SC
DDDDD
1 ~ 32768
DDDDD
1 ~ 32768
AI
DDDDD
1 ~ 32768
AQ
DDDDD
1 ~ 32768
DDDDD
1 ~ 32768
215
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
3 RXD
5 GND
5 GND
216
1 RX-
12 SDA
2 RX+
13 SDB
5 GND
7 GND
3 TX-
10 RDA
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
short
short
short
cMT/mTV series
COM1 RS485 4W
9P D-Sub Female
7 RX-
12 SDA
6 RX+
13 SDB
5 GND
7 GND
9 TX-
10 RDA
8 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
217
short
short
short
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
12 SDA
2 RX+
2 RX+
13 SDB
5 GND
5 GND
7 GND
3 TX-
3 TX-
10 RDA
4 TX+
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
short
short
short
1 RX-
12 SDA
2 RX+
13 SDB
5 GND
7 GND
3 TX-
10 RDA
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
218
short
short
short
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
12 SDA
2 RX+
13 SDB
5 GND
7 GND
3 TX-
10 RDA
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
Driver Version:
Version
Date
V1.30
Aug/13/2015
Description
219
short
short
short
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
18245
Notes
Device Address:
Bit/Word
Device type
Format
Range
DDDDD
1 ~ 32768
DDDDD
1 ~ 32768
DDDDD
1 ~ 32768
DDDD
1 ~ 7680
DDDD
1 ~ 1024
SA
DDD
1 ~ 128
SB
DDD
1 ~ 128
SC
DDD
1 ~ 128
DDD
1 ~ 128
AI
DDDDD
1 ~ 32640
AQ
DDDDD
1 ~ 32640
DDDDD
1 ~ 32640
220
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V1.00
Aug/12/2015
Description
221
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
18245
Notes
1~99
Device Address:
Bit/Word
Device type
Format
Range
I_bit
DDDDD
1 ~ 32768
Q_bit
DDDDD
1 ~ 32768
M_bit
DDDDD
1 ~ 32768
G_bit
DDDDD
1 ~ 32768
T_bit
DDDDD
1 ~ 32768
SA_bit
DDDDD
1 ~ 32768
Read Only
SB_bit
DDDDD
1 ~ 32768
Read Only
SC_bit
DDDDD
1 ~ 32768
Read Only
S_bit
DDDDD
1 ~ 32768
Read Only
R_bit
DDDDD
1 ~ 32768
DDDDD
1 ~ 32753
DDDDD
1 ~ 32753
DDDDD
1 ~ 32753
DDDDD
1 ~ 32753
DDDD
1 ~ 1024
SA
DDDDD
1 ~ 32753
SB
DDDDD
1 ~ 32753
222
Memo
Bit/Word
Device type
Format
Range
Memo
SC
DDDDD
1 ~ 32753
DDDDD
1 ~ 32753
DDDDD
1 ~ 32768
AI
DDDDD
1 ~ 32768
AQ
DDDDD
1 ~ 32768
DDDDDDD 1 ~ 5000000
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.70
Apr/09/2010
V1.80
Nov/09/2011
V1.90
Jan/17/2012
223
GE Fanuc SNP-X
Supported Series: GE Fanuc 90-30 , 90 micro and VersaMax series PLC , 90-70 series
with CMM711 module.
Website: http://www.ge.com
HMI Setting:
Parameters
Recommended
Options
PLC type
GE Fanuc SNP-X
PLC I/F
RS485 4W
RS232/RS485
Baud rate
19200
9600 ~ 115200
Data bits
7, 8
Parity
Odd
Stop bits
1, 2
0-255
Notes
PLC Setting:
Refer to the related PLC manual.
Device Address:
Bit/Word Device type Format
Range
Memo
DDDDD
1 ~ 10000
Input relay
DDDDD
1 ~ 10000
Output relay
DDDDD
1 ~ 10000
Auxiliary relay
DDDD
1 ~ 7680
DDD
1 ~ 256
SA
DDD
1 ~ 128
SB
DDD
1 ~ 128
SC
DDD
1 ~ 128
DDD
1 ~ 128
R_bit
DDDDDdd
1 ~ 3264015
AI
DDDDD
1 ~ 10000
AQ
DDDDD
1 ~ 10000
DDDDD
1 ~ 32640
Data register
224
Wiring Diagram:
The following is the view from the soldering point of a cable.
CPU Port (90-30/VersaMax)
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
90-30/VersaMax RS422
15P D-Sub Male
1 RX-
12 SDA
2 RX+
13 SDB
5 GND
7 GND
3 TX-
10 RDA
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
short
short
short
cMT/mTV series
COM1 RS485 4W
9P D-Sub Female
90-30/VersaMax RS422
15P D-Sub Male
7 RX-
12 SDA
6 RX+
13 SDB
5 GND
7 GND
9 TX-
10 RDA
8 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
225
short
short
short
COM2 RS485 4W
9P D-Sub Male
90-30/VersaMax RS422
15P D-Sub Male
1 RX-
1 RX-
12 SDA
2 RX+
2 RX+
13 SDB
5 GND
5 GND
7 GND
3 TX-
3 TX-
10 RDA
4 TX+
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
short
short
short
90-30/VersaMax RS422
15P D-Sub Male
1 RX-
12 SDA
2 RX+
13 SDB
5 GND
7 GND
3 TX-
10 RDA
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
226
short
short
short
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
90-30/VersaMax RS422
15P D-Sub Male
1 RX-
12 SDA
2 RX+
13 SDB
5 GND
7 GND
3 TX-
10 RDA
4 TX+
11 RDB
9 RT
6 RTSA
15 CTSA
8 RTSB
14 CTSB
short
short
short
COM3 RS232 9P
90-30/90-70 series
D-Sub Female
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
5 RX
5 GND
5 GND
3 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
90-30/90-70 series
RS232 6P RJ11 Male
2 RX
2 TX
3 TX
5 RX
5 GND
3 GND
90-30/90-70 series
RS232 6P RJ11 Male
2 RX
2 TX
3 TX
5 RX
5 GND
3 GND
227
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
90-30/90-70 series
RS232 6P RJ11 Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
5 RX
5 GND
5 GND
5 GND
3 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
90-30/90-70 series
RS232 6P RJ11 Male
9 RX
2 TX
6 TX
5 RX
5 GND
3 GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
4 TX
3 TX
7 TX
3 RX
5 GND
5 GND
8 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
8P RJ45 Male
2 RX
4 TX
3 TX
3 RX
5 GND
8 GND
2 RX
4 TX
3 TX
3 RX
5 GND
8 GND
228
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
4 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
8 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
4 TX
6 TX
3 RX
5 GND
8 GND
Driver Version:
Version
Date
V1.20
Jan/09/2009
V1.40
Dec/25/2012
Description
Add device type : R_bit
229
Haiwell PLC
Support Series: E series, S series and H series.
Web: http://www.haiwell.com/
HMI Setting:
Parameters
Recommended
Options
PLC type
Haiwell PLC
PLC I/F
RS232
RS232,RS485 2W
Baud rate
19200
19200
Data bits
Parity
None
None
Stop bits
1~247
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDD
0 ~ 1023
Input Switch
DDDD
0 ~ 1023
Output Switch
DDDDD
0 ~ 12287
Internal Relay
DDDD
0 ~ 1023
DDD
0 ~ 255
SM
DDD
0 ~ 215
DDDD
0 ~ 2047
Step Bit
CR
DD
0 ~ 79
AI
DDD
0 ~ 255
AQ
DDD
0 ~ 255
DDDDD
0 ~ 14847
Data Register
TCV
DDDD
0 ~ 1023
CCV
DDD
0 ~ 255
SV
DDD
0 ~ 154
System Register
230
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 4P Mini-DIN
Male
2 RX
8 RX
2 TX
3 TX
7 TX
1 RX
5 GND
5 GND
3 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 4P Mini-DIN
Male
2 RX
2 TX
3 TX
1 RX
5 GND
3 GND
RS232 4P Mini-DIN
Male
2 RX
2 TX
3 TX
1 RX
5 GND
3 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 4P Mini-DIN
Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
1 RX
5 GND
5 GND
5 GND
3 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 4P Mini-DIN
Male
9 RX
2 TX
6 TX
1 RX
5 GND
3 GND
View from the
soldering point
of a cable.
231
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
B- Data+
2 RX+
9 Data+
A+ Data-
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
COM3 RS485 2W
RS485 2W Terminal
9P D-Sub Female
9P D-Sub Female
7 RX-
4 Data-
B- Data+
6 RX+
1 Data+
A+ Data-
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
7 Data-
B- Data+
2 RX+
8 Data+
A+ Data-
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
B- Data+
2 RX+
9 Data+
A+ Data-
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
B- Data+
2 RX+
9 Data+
A+ Data-
5 GND
5 GND
232
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W Terminal
1 RX-
7 Data-
B- Data+
2 RX+
8 Data+
A+ Data-
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Mar/2/2012
Driver released.
233
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word Device type
Format
Range
Memo
MWX
DDDdd
0 ~ 25515
MWX_NO_RPS DDDdd
0 ~ 25515
MW
DDD
0 ~ 255
MW_NO_RPS
DDD
0 ~ 255
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 Terminal
2 RX
8 RX
TD
3 TX
7 TX
RD
5 GND
5 GND
GND
234
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 Terminal
2 RX
TD
3 TX
RD
5 GND
GND
RS232 Terminal
2 RX
TD
3 TX
RD
5 GND
GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 Terminal
2 RX
6 RX
8 RX
TD
3 TX
4 TX
7 TX
RD
5 GND
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 Terminal
9 RX
TD
6 TX
RD
5 GND
GND
Driver Version:
Version
Date
V1.00
Apr/27/2010
Description
235
Hanyoung Controller
Supported Series: Temperature Controller.
Website: http://hynux.com/kor/
HMI Setting:
Parameters
Recommended
Options
PLC type
Hanyoung Controller
PLC I/F
RS485 4W
Baud rate
9600
Data bits
7 or 8
Parity
None
Stop bits
1 or 2
0-255
Notes
*In System Parameter Settings / Device Settings / COM Settings, set Parameter 1 to 1 to
support Check Sum Mode.
236
Device Address:
Bit/Word
Device type
Format
Range
DDDD
1 ~ 9999
DDDD
1 ~ 9999
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
1 RX-
32 TX-
2 RX+
31 TX+
3 TX-
34 RX-
4 TX+
33 RX+
5 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
32 TX-
6 RX+
31 TX+
9 TX-
34 RX-
8 TX+
33 RX+
5 GND
MT8000iE/MT8000XE series except MT8050iE
COM1 RS485 4W
9P D-Sub Male
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
32 TX-
2 RX+
2 RX+
31 TX+
3 TX-
3 TX-
34 RX-
4 TX+
4 TX+
33 RX+
5 GND
5 GND
237
1 RX-
32 TX-
2 RX+
31 TX+
3 TX-
34 RX-
4 TX+
33 RX+
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
32 TX-
2 RX+
31 TX+
3 TX-
34 RX-
4 TX+
33 RX+
5 GND
Driver Version:
Version
Date
V1.60
Jun/14/2010
Description
238
HAWE PLVC
Supported Series: HAWE PLVC
Website: http://www.hawe.de/de/home/
HMI Setting:
Parameters
Recommended
PLC type
HAWE PLVC
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
None
Stop bits
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
HHHH
0 ~ ffff
Input Bits
HHHH
0 ~ ffff
Output Bits
DDDDD
0 ~ 65535
Internal Relays
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
TV
DDDDD
0 ~ 65535
CV
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
Data Registers
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
239
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 terminal
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 terminal
2 RX
TXD
3 TX
RXD
5 GND
GND
RS232 terminal
2 RX
TXD
3 TX
RXD
5 GND
GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 terminal
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 terminal
9 RX
TXD
6 TX
RXD
5 GND
GND
240
Driver Version:
Version
Date
V1.00
Sep/17/2009
Description
241
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485 4W
Baud rate
9600
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
ADDR00
1~D
ADDR01
1~D
ADDR02
1~D
ADDR03
1~D
ADDR04
1~D
ADDR05
1~D
ADDR06
1~D
ADDR07
1~D
ADDR08
1~D
ADDR09
1~D
ADDR0a
1~D
ADDR0b
1~D
ADDR0c
1~D
ADDR0d
1~D
ADDR0e
1~D
ADDR0f
1~D
ADDR3f
0~b
DATAn
0~5
242
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
RS422 terminal
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS422 terminal
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
RS422 terminal
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
RS422 terminal
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
243
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS422 terminal
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
Driver Version:
Version
Date
V1.00
Apr/17/2014
Description
244
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
Even
Stop bits
Options
Notes
1-31
Online simulator
YES
YES
Device Address:
Bit/Word
Device type
Format
Parameter
DDDD
Range
Memo
0 ~ 2000
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
7 RX- (Yellow)
2 RX+
9 Data+
6 RX+ (Green)
5 GND
5 GND
4 GND (Black)
245
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
7 RX- (Yellow)
6 RX+
1 Data+
6 RX+ (Green)
5 GND
5 GND
4 GND (Black)
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
7 RX- (Yellow)
2 RX+
8 Data+
6 RX+ (Green)
5 GND
9 GND
4 GND (Black)
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
7 RX- (Yellow)
2 RX+
9 Data+
6 RX+ (Green)
5 GND
5 GND
4 GND (Black)
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
7 RX- (Yellow)
2 RX+
9 Data+
6 RX+ (Green)
5 GND
5 GND
4 GND (Black)
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
COM3 RS485 2W
9P D-Sub Female
9P D-Sub Female
RS485
1 RX-
7 Data-
7 RX- (Yellow)
2 RX+
8 Data+
6 RX+ (Green)
5 GND
5 GND
4 GND (Black)
Driver Version:
Version
Date
Description
V1.00
Dec/30/2008
Driver released.
246
Hitachi EH-SIO
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
Hitachi EH-SIO
PLC I/F
RS232
RS232, RS485
Baud rate
19200
Data bits
Parity
Even
Even
Stop bits
PLC Setting:
Communication mode
19200, E, 7, 1 (default)
Device Address:
Bit/Word Device type
Format
Range
Memo
HHHHh
0 ~ fffff
HHHHh
0 ~ fffff
HHHHh
0 ~ fffff
HHHHh
0 ~ fffff
Timer (T)
HHHHh
0 ~ fffff
HHHHh
0 ~ fffff
TC
HH
0 ~ ff
WM
HHHH
0 ~ 270f
WX
HHHH
0 ~ 270f
WY
HHHH
0 ~ 270f
WR
HHHH
0 ~ 270f
WL
HHHH
0 ~ 270f
247
Wiring Diagram:
The following is the view from the soldering point of a cable.
EH-SIO port1/port 2 RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
5 SD
3 TX
7 TX
6 RD
5 GND
5 GND
1 SG
8 CTS
8 RS
4 PHL
7 DR
short
2 RX
5 SD
3 TX
6 RD
5 GND
1 SG
8 CTS
8 RS
4 PHL
7 DR
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
5 SD
3 TX
4 TX
7 TX
6 RD
5 GND
5 GND
5 GND
1 SG
8 CTS
8 RS
4 PHL
7 DR
248
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
5 SD
6 TX
6 RD
5 GND
1 SG
8 RS
4 PHL
7 DR
short
HitachiEH-SIO port2
1 RX-
2 TX-
2 RX+
1 TX+
3 TX-
4 RX-
4 TX+
3 RX+
5 GND
6 SG
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
HitachiEH-SIO port2
7 RX-
2 TX-
6 RX+
1 TX+
9 TX-
4 RX-
8 TX+
3 RX+
5 GND
6 SG
COM2 RS485 4W
9P D-Sub Male
HitachiEH-SIO port2
1 RX-
1 RX-
2 TX-
2 RX+
2 RX+
1 TX+
3 TX-
3 TX-
4 RX-
4 TX+
4 TX+
3 RX+
5 GND
5 GND
6 SG
249
HitachiEH-SIO port2
1 RX-
2 TX-
2 RX+
1 TX+
3 TX-
4 RX-
4 TX+
3 RX+
5 GND
6 SG
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
HitachiEH-SIO port2
1 RX-
2 TX-
2 RX+
1 TX+
3 TX-
4 RX-
4 TX+
3 RX+
5 GND
6 SG
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
2 TX4 RX-
2 RX+
9 Data+
1 TX+
3 RX+
5 GND
short
short
5 GND
6 SG
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
2 TX-
cMT/mTV series
4 RX6 RX+
1 Data+
1 TX+
3 RX+
5 GND
5 GND
6 SG
250
short
short
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
2 TX4 RX-
2 RX+
8 Data+
1 TX+
3 RX+
5 GND
9 GND
short
short
6 SG
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
2 TX4 RX-
2 RX+
9 Data+
1 TX+
3 RX+
5 GND
5 GND
short
short
6 SG
COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male
1 RX-
6 Data-
2 RX+
9 Data+
1 TX+
3 RX+
5 GND
5 GND
short
short
6 SG
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
COM3 RS485 2W
9P D-Sub Female
9P D-Sub Female
1 RX-
7 Data-
2 RX+
8 Data+
1 TX+
3 RX+
5 GND
5 GND
6 SG
251
short
short
Driver Version:
Version
Date
Description
V1.00
May/25/2010
Driver released.
252
HMI Setting:
Parameters
Recommended Options
Notes
PLC type
PLC I/F
Ethernet
Port no.
3004
3004~3007
Device Address:
Bit/Word Device type
Format
Range
HHHHh
0 ~ fffff
HHHHh
0 ~ fffff
HHHHh
0 ~ fffff
DDDDD
0 ~ 65535
Timer (T)
HHHHh
0 ~ fffff
HHHHh
0 ~ fffff
TC
DDDD
0 ~ 2559
WM
HHHH
0 ~ 7fff
WX
HHHH
0 ~ ffff
WY
HHHH
0 ~ ffff
WR
HHHH
0 ~ ffff
WL
HHHH
0 ~ 73ff
253
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Jan/12/2010
Driver released
254
HMI Setting:
Parameters
Recommended Options
PLC type
PLC I/F
RS232
RS232, RS485
Baud rate
19200
Data bits
Parity
Even
Even
Stop bits
0-255
Online simulator
Notes
YES
Broadcast command NO
Device Address:
Bit/Word Device type
Format
Range
Memo
HHHHh
0 ~ fffff
HHHHh
0 ~ fffff
HHHHh
0 ~ fffff
HHHHh
0 ~ fffff
Timer (T)
HHHHh
0 ~ fffff
HHHHh
0 ~ fffff
TC
HH
0 ~ ff
WM
HHHH
0 ~ 270f
WX
HHHH
0 ~ 270f
WY
HHHH
0 ~ 270f
WR
HHHH
0 ~ c3ff
WL
HHHH
0 ~ 270f
255
Wiring Diagram:
WARNING: If your communication cable is not wired exactly as shown in our cable
assembly instructions, damage to the HMI or loss of communications can be caused.
CPU TYPE
Port 1
Port 2
EH-150/CPU 104A
RS-232
RS-232
EH-150/CPU 208A
RS-232
RS-232
Port 1
EH-150/CPU 308A
RS-232/RS-485 RS-232
Port 2
EH-150/CPU 316A
RS-232/RS-485 RS-232
EH-150/CPU 448A
RS-232/RS-485 RS-232
Switch Number
1
OFF
Normal mode
OFF
TRNS0 operation
3, 4
ON
ON
4,800 bps
OFF
ON
9,600 bps
ON
OFF
19,200 bps
OFF
OFF
38,400 bps
ON
Dedicated port
PHL
ON
Low
9,600 bps
Toggle-Switch
ON
High
38,400 bps
OFF
Low
4,800 bps
Doesnt support
PHL
Low
OFF
High
19,200 bps
Default
OFF
(System mode)
PHL
OFF
(System mode)
High
Doesnt support
Default
256
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
5 SD
3 TX
7 TX
6 RD
5 GND
5 GND
1 SG
8 CTS
8 RS
4 PHL
7 DR
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
5 SD
3 TX
6 RD
5 GND
1 SG
8 RS
4 PHL
7 DR
short
2 RX
5 SD
3 TX
6 RD
5 GND
1 SG
8 CTS
8 RS
4 PHL
7 DR
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
5 SD
3 TX
4 TX
7 TX
6 RD
5 GND
5 GND
5 GND
1 SG
8 CTS
8 RS
4 PHL
7 DR
257
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
5 SD
6 TX
6 RD
5 GND
1 SG
8 RS
4 PHL
7 DR
short
RS485 4W 8P RJ45
Male
1 RX-
5 TX-
2 RX+
4 TX+
3 TX-
6 RX-
4 TX+
7 RX+
5 GND
1 SG
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 8P RJ45
Male
7 RX-
5 TX-
6 RX+
4 TX+
9 TX-
6 RX-
8 TX+
7 RX+
5 GND
1 SG
258
COM2 RS485 4W
9P D-Sub Male
RS485 4W 8P RJ45
Male
1 RX-
1 RX-
5 TX-
2 RX+
2 RX+
4 TX+
3 TX-
3 TX-
6 RX-
4 TX+
4 TX+
7 RX+
5 GND
5 GND
1 SG
RS485 4W 8P RJ45
Male
1 RX-
5 TX-
2 RX+
4 TX+
3 TX-
6 RX-
4 TX+
7 RX+
5 GND
1 SG
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
RS485 4W 8P RJ45
9P D-Sub Female
Male
1 RX-
5 TX-
2 RX+
4 TX+
3 TX-
6 RX-
4 TX+
7 RX+
5 GND
1 SG
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
Male
1 RX-
6 Data-
4 TX+
7 RX+
2 RX+
9 Data+
5 TX6 RX-
5 GND
5 GND
1 SG
259
short
short
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P RJ45
Male
7 RX-
4 Data-
4 TX+
7 RX+
6 RX+
1 Data+
5 TX6 RX-
5 GND
5 GND
short
short
1 SG
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
Male
1 RX-
7 Data-
4 TX+
7 RX+
2 RX+
8 Data+
5 TX6 RX-
5 GND
9 GND
short
short
1 SG
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
COM3 RS485 2W
RS485 2W 8P RJ45
9P D-Sub Male
9P D-Sub Male
Male
1 RX-
6 Data-
4 TX+
7 RX+
2 RX+
9 Data+
5 TX6 RX-
5 GND
5 GND
short
short
1 SG
COM3 RS485 2W
RS485 2W 8P RJ45
9P D-Sub Male
9P D-Sub Male
Male
1 RX-
6 Data-
4 TX+
7 RX+
2 RX+
9 Data+
5 TX6 RX-
5 GND
5 GND
1 SG
260
short
short
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P RJ45
Male
1 RX-
7 Data-
4 TX+
7 RX+
2 RX+
8 Data+
5 TX6 RX-
5 GND
5 GND
short
short
1 SG
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
9 SG
10 SG
8 CTS
short
4 RTS
5 CTS
7 DSR
8 PHL
short
14 PV12
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
9 SG
10 SG
short
4 RTS
5 CTS
7 DSR
8 PHL
14 PV12
261
short
2 RX
2 TXD
3 TX
3 RXD
5 GND
9 SG
10 SG
8 CTS
short
4 RTS
5 CTS
7 DSR
8 PHL
short
14 PV12
MT6000/8000 series except MT6050i/MT8050i
COM1 RS232 9P
D-Sub Female
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
9 SG
10 SG
8 CTS
short
4 RTS
5 CTS
7 DSR
8 PHL
14 PV12
262
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
3 RXD
5 GND
9 SG
10 SG
short
4 RTS
5 CTS
7 DSR
8 PHL
short
14 PV12
Driver Version:
Version
Date
Description
V1.10
Oct/22/2009
V1.30
Mar/22/2010
263
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485 2W
Baud rate
38400
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word Device type
Format
Range
IX
DDDDo
0 ~ 81907
MX
DDDDo
0 ~ 81907
QX
DDDDo
0 ~ 81907
IW
DDDD
0 ~ 8190
QW
DDDD
0 ~ 8190
MW
DDDD
0 ~ 8190
MD
DDDD
0 ~ 8190
MR
DDDD
0 ~ 8190
264
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
6 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
7 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P Mini-DIN
Male
7 RX-
4 Data-
6 D-
6 RX+
1 Data+
5 D+
5 GND
5 GND
7 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
7 Data-
6 D-
2 RX+
8 Data+
5 D+
5 GND
9 GND
7 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
6 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
7 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
6 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
7 GND
265
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P Mini-DIN
Male
1 RX-
7 Data-
6 D-
2 RX+
8 Data+
5 D+
5 GND
5 GND
7 GND
View from the
soldering point
of a cable.
Driver Version:
Version
Date
Description
V1.00
Apr/17/2014
Driver released.
266
HUST H4C
Supported Series: HUST CNC Controller H4C, H6C Series.
Website: http://www.hust.com.tw/
HMI Setting:
Parameters
Recommended
PLC type
HUST H4C
PLC I/F
RS-232
Baud rate
38400
Data bits
Parity
Even
Stop bits
Options
Notes
CPU port
9600,19200,38400,57600
Device Address:
Bit/Word
Device type
Format
Range
DDD
0 ~ 255
DDD
0 ~ 255
DDD
0 ~ 255
DDD
0 ~ 255
DDD
0 ~ 1023
VM_bit
DDDDDdd 0 ~ 9999931
DW
VM
DDDDD
0 ~ 99999
DW
DDD
0 ~ 255
DW
Cn
DDD
0 ~ 255
DW
Tm
DDD
0 ~ 255
267
Memo
Mapping to VM 10800 ~ 10807 (read
only)
Mapping to VM 10808 ~ 10815 (read
only)
Mapping to VM 10816 ~ 10823 (read
only)
Mapping to VM 10824 ~ 10831 (read
only)
Mapping to VM 10832 ~ 10863 (read
only)
Bit address (dd): 00 ~ 31
Please refer to the controller
specification for register range.
Mapping to VM 10000 ~ 10255 (read
only)
Mapping to VM 10256 ~ 10511 (read
only)
Mapping to VM 10512 ~ 10767 (read
only)
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
short
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
268
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
Driver Version:
Version
Date
Description
V1.00
Oct/09/2013
Driver released.
V1.20
Mar/17/2014
269
short
HUST H4X
Supported Series: HUST CNC Controller H4 Series.
Website: http://www.hust.com.tw/
HMI Setting:
Parameters
Recommended
PLC type
HUST H4X
PLC I/F
RS-232
Baud rate
38400
Data bits
Parity
Even
Stop bits
Options
Notes
CPU port
9600,19200,38400,57600
Device Address:
Bit/Word
Device type
Format
Range
DDD
0 ~ 255
DDD
0 ~ 255
DDD
0 ~ 255
DDD
0 ~ 255
DDD
0 ~ 255
VM_bit
DW
VM
DDDDD
1 ~ 99999
DW
DDD
0 ~ 255
DW
Cn
DDD
0 ~ 255
DW
Tm
DDD
0 ~ 255
270
Memo
Mapping to VM 10800 ~ 10807 (read
only)
Mapping to VM 10808 ~ 10815 (read
only)
Mapping to VM 10816 ~ 10823 (read
only)
Mapping to VM 10824 ~ 10831 (read
only)
Mapping to VM 10832 ~ 10863 (read
only)
Bit address (dd): 00 ~ 31
Please refer to the controller
specification for register range.
Mapping to VM 10000 ~ 10255 (read
only)
Mapping to VM 10256 ~ 10511 (read
only)
Mapping to VM 10512 ~ 10767 (read
only)
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
short
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
271
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
Driver Version:
Version
Date
V2.01
Sep/29/2009
Description
272
short
IAI PCON-C-42PI
Supported Series: PCON Controller for RCP2 Series.
Website: http://www.intelligentactuator.com
HMI Setting:
Parameters
Recommended
PLC type
IAI PCON-C-42PI
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
None
Stop bits
Options
Notes
9600 ~ 115200
1 ~ 16
Device Address:
Bit/Word Device type
Format
Range
SFTY
SON
ALRS
BKRL
STP
HOME
CSTR
JISL
MOD
TEAC
JOG+
JOG-
ST0
ST1
ST2
ST3
ST4
ST5
ST6
1
273
Memo
Format
Range
ST7
PMSL
STOP
CLBR
DSS1_Bit
Ddd
15
EMGS
DSS1_Bit
Ddd
14
SFTY
DSS1_Bit
Ddd
13
PWR
DSS1_Bit
Ddd
12
SV
DSS1_Bit
Ddd
11
PSFL
DSS1_Bit
Ddd
10
ALMH
DSS1_Bit
Ddd
ALML
DSS1_Bit
Ddd
ABER
DSS1_Bit
Ddd
BKRL
DSS1_Bit
Ddd
STP
DSS1_Bit
Ddd
HEND
DSS1_Bit
Ddd
PEND
DSS1_Bit
Ddd
CEND
DSS1_Bit
Ddd
CLBS
DSS2_Bit
Ddd
15
ENBS
DSS2_Bit
Ddd
13
LOAD
DSS2_Bit
Ddd
12
TRQS
DSS2_Bit
Ddd
11
MODS
DSS2_Bit
Ddd
10
TEAC
DSS2_Bit
Ddd
JOG+
DSS2_Bit
Ddd
JOG-
DSS2_Bit
Ddd
PE7
DSS2_Bit
Ddd
PE6
DSS2_Bit
Ddd
PE5
DSS2_Bit
Ddd
PE4
DSS2_Bit
Ddd
PE3
DSS2_Bit
Ddd
PE2
DSS2_Bit
Ddd
PE1
DSS2_Bit
Ddd
PE0
DSSE_Bit
Ddd
15
EMGP
DSSE_Bit
Ddd
14
MPUV
DSSE_Bit
Ddd
13
RMDS
DSSE_Bit
Ddd
11
GHMS
274
Memo
Format
Range
Memo
DSSE_Bit
Ddd
10
PUSH
DSSE_Bit
Ddd
PSNS
DSSE_Bit
Ddd
PMSS
DSSE_Bit
Ddd
MOVE
POSS_Bit
Ddd
PM512
POSS_Bit
Ddd
PM256
POSS_Bit
Ddd
PM128
POSS_Bit
Ddd
PM64
POSS_Bit
Ddd
PM32
POSS_Bit
Ddd
PM16
POSS_Bit
Ddd
PM8
POSS_Bit
Ddd
PM4
POSS_Bit
Ddd
PM2
POSS_Bit
Ddd
PM1
ZONS_Bit
Ddd
14
LS2
ZONS_Bit
Ddd
13
LS1
ZONS_Bit
Ddd
12
LS0
ZONS_Bit
Ddd
ZP
ZONS_Bit
Ddd
Z2
ZONS_Bit
Ddd
Z1
DIPM_Bit
Ddd
0 ~ 15
IN0 ~ IN15
DOPM_Bit
Ddd
0 ~ 15
OUT0 ~ OUT15
SIPM_Bit
Ddd
14
NP
SIPM_Bit
Ddd
12
PP
SIPM_Bit
Ddd
MDSW
SIPM_Bit
Ddd
BLCT
SIPM_Bit
Ddd
HMCK
SIPM_Bit
Ddd
OT
SIPM_Bit
Ddd
CREP
SIPM_Bit
Ddd
LS
EMG
POSR_Bit
Ddd
0 ~ 15
PNOW
ALMC
DIPM
DOPM
DSS1
1
275
Format
Range
DSS2
DSSE
STAT
VNOW
CNOW
DEVI
STIM
SIPM
ZONS
POSS
DRG1
DRG2
POSR_NUM
PCMD
INP
VCMD
ACMD
PPOW
CTLF
FBFC
POSR_MOV
PCMD_T
DDD
0 ~ 768
INP_T
DDD
0 ~ 768
VCMD_T
DDD
0 ~ 768
ZNMP_T
DDD
0 ~ 768
ZNLP_T
DDD
0 ~ 768
ACMD_T
DDD
0 ~ 768
DCMD_T
DDD
0 ~ 768
PPOW_T
DDD
0 ~ 768
LPOW_T
DDD
0 ~ 768
CTLF_T
DDD
0 ~ 768
276
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
7 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P Mini-DIN
Male
7 RX-
4 Data-
2 D-
6 RX+
1 Data+
1 D+
5 GND
5 GND
7 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
7 Data-
2 D-
2 RX+
8 Data+
1 D+
5 GND
9 GND
7 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
7 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
7 GND
277
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P Mini-DIN
Male
1 RX-
7 Data-
2 D-
2 RX+
8 Data+
1 D+
5 GND
5 GND
7 GND
View from the
soldering point
of a cable.
Driver Version:
Version
Date
Description
V1.00
Apr/17/2014
Driver released.
V1.10
Mar/13/2015
278
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
RS232
Baud rate
9600
9600~19200
Data bits
7 or 8
Parity
None
Stop bits
1 or 2
Device Address:
Bit/Word
Device type
Format
Range
Memo
Address 1~8 represent the corresponding
Servo_On_Off
1~8
axis.
Write 1 means ON and 0 means OFF.
Address 1~8 represent the corresponding
Servo_Origin
1~8
axis.
Back to origin.
For reading current position. The state of
CurrentAxisPos H
1~8
RunProgram
run.
EndProgram
stop.
Address 1~8 represent the corresponding
axis. The data written indicates which point
PointMove
0~8
279
Bit/Word
Device type
Format
Range
Memo
Jogging. Address 1~8 represent the
corresponding axis. Put parameters ACC,
JoggingMove
0~8
AbsoluteMove
0~8
PointChange
0~8
SoftWareReset
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
280
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Jun/01/2010
Driver released.
281
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
9600
9600~19200
Data bits
7 or 8
Parity
None
Stop bits
1 or 2
Notes
Device Address:
Bit/Word
Device type
Format
Range
IP_Bit
DDD
0 ~ 299
OP_Bit
DDD
300 ~ 599
FG_Bit
DDDDDD
0 ~ 128999
AX1Status
0~8
AX2Status
0~8
AX3Status
0~8
IP
DDD
0 ~ 272
OP
DDD
300 ~ 572
FG
DDDDDD
0 ~ 128999
PDT
INT
DDDDDDD 0 ~ 1281299
RL
DDDDDDD 0 ~ 1281399
STR
DDDDDD
0 ~ 128998
AX1Sensor
AX2Sensor
AX3Sensor
AX1Error
AX2Error
AX3Error
0
282
Memo
Bit/Word
Device type
Format
Range
AX1Encode
AX2Encode
AX3Encode
AX1Positio23
AX2Positio24
AX3Positio25
PGStatus
DDD
0 ~ 255
PGStepNo
DDD
0 ~ 255
PGError
DDD
0 ~ 255
PGErrorNo
DDD
0 ~ 255
SYST
0~6
VR
HHH
0 ~ 3FF
ER0
HHHH
0 ~ FFFF
ER1
HHHH
0 ~ FFFF
ER2
HHHH
0 ~ FFFF
ER3
HHHH
0 ~ FFFF
ER4
HHHH
0 ~ FFFF
ER5
HHHH
0 ~ FFFF
ER6
HHHH
0 ~ FFFF
ER7
HHHH
0 ~ FFFF
SV
RO
0~3
ACM
RCM
JIM
PNM
PD_Set
PCLR
DDDDDD
0 ~ 999999
AR0
PR_253
DDD
0 ~ 128
PR_254
DDD
0 ~ 128
PR_255
DDD
0 ~ 128
PR_256
DDD
0 ~ 128
PR_257
DDD
0 ~ 128
SR0
OPR0
ChSpd
0
283
Memo
Bit/Word
Device type
Format
Range
PD2_Value
DDDDD
10 ~ 40960
PD3_Value
DDDDD
10 ~ 40960
Stop_Canl
1~7
PDn1Value
0~7
PDn2Value
0~7
PDn3Value
0~7
PDn4Value
0~7
PDn5Value
0~7
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
284
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Dec/19/2012
Driver released.
285
IDEC Micro
Supported Series: IDEC Micro3, Micro3C, OpenNet Controller series.
Website: http://www.idec.com
HMI Setting:
Parameters
Recommended
PLC type
IDEC Micro
PLC I/F
RS232
RS232, RS485
Baud rate
9600
9600, 19200
Data bits
7, 8
Parity
Even
Stop bits
0-255
Online simulator
YES
YES
Options
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
DDDDo
0 ~ 20477
Input (I)
DDDDo
0 ~ 20477
Output (Q)
DDDDo
0 ~ 20477
RT
DDDD
0 ~ 9999
Timer (T)
RC
DDDD
0 ~ 9999
Counter (C)
DDDD
0 ~ 9999
286
Wiring Diagram:
The following is the view from the soldering point of a cable.
Micro3C, MicroSmart, OpenNet Controller CPU Ladder Port
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
Port1 or Port2 8P
Mini-DIN Male
2 RX
8 RX
3 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
7 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
Port1 or Port2 8P
Mini-DIN Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
7 GND
Port1 or Port2 8P
D-Sub Female
Mini-DIN Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
7 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
Port1 or Port2 8P
Mini-DIN Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
7 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
Port1 or Port2 8P
Mini-DIN Male
9 RX
3 TXD
6 TX
4 RXD
5 GND
7 GND
View from the
soldering point
of a cable.
287
COM3 RS485 2W
9P D-Sub Male
RS485 8P Mini-DIN
Male
1 RX-
6 Data-
2 RXD-
2 RX+
9 Data+
1 RXD+
5 GND
5 GND
7 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 8P Mini-DIN
Male
7 RX-
4 Data-
2 RXD-
6 RX+
1 Data+
1 RXD+
5 GND
5 GND
7 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
7 Data-
2 D-
2 RX+
8 Data+
1 D+
5 GND
9 GND
7 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
7 GND
COM3 RS485 2W
9P D-Sub Male
RS485 8P Mini-DIN
Male
1 RX-
6 Data-
2 RXD-
2 RX+
9 Data+
1 RXD+
5 GND
5 GND
7 GND
288
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 8P Mini-DIN
Male
1 RX-
7 Data-
2 RXD-
2 RX+
8 Data+
1 RXD+
5 GND
5 GND
7 GND
View from the
soldering point
of a cable.
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
A RXD-
2 RX+
9 Data+
B RXD+
5 GND
5 GND
SG GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
A RXD-
6 RX+
1 Data+
B RXD+
5 GND
5 GND
cMT/mTV series
SG GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
A RXD-
2 RX+
8 Data+
B RXD+
5 GND
9 GND
SG GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
A RXD-
2 RX+
9 Data+
B RXD+
5 GND
5 GND
SG GND
289
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
A RXD-
2 RX+
9 Data+
B RXD+
5 GND
5 GND
SG GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
1 RX-
7 Data-
A RXD-
2 RX+
8 Data+
B RXD+
5 GND
5 GND
SG GND
Driver Version:
Version
Date
V1.20
Jun/19/2009
Description
290
IDEC MicroSmart
Supported Series: IDEC MicroSmart , SmartAxis series.
Website: http://www.idec.com
HMI Setting:
Parameters
Recommended
PLC type
IDEC MicroSmart
PLC I/F
RS232
RS232, RS485
Baud rate
9600
9600, 19200
Data bits
7, 8
Parity
Even
Stop bits
0-255
Online simulator
YES
YES
Options
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
DDDDo
0 ~ 20477
Input (I)
DDDDo
0 ~ 20477
Output (Q)
DDDDo
0 ~ 20477
DDDD
0 ~ 2047
DDDD
0 ~ 2047
Timer (T)
DDDD
0 ~ 2047
Counter (C)
TP
DDDD
0 ~ 9999
Timer Preset
CP
DDDD
0 ~ 9999
Counter Preset
DDDD
0 ~ 9999
TC
DDDD
0 ~ 9999
Timer Current
CC
DDDD
0 ~ 9999
Counter Currnet
291
Wiring Diagram:
The following is the view from the soldering point of a cable.
MicroSmart , SmartAxis CPU Ladder Port
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
Port1 or Port2 8P
Mini-DIN Male
2 RX
8 RX
3 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
7 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
Port1 or Port2 8P
Mini-DIN Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
7 GND
Port1 or Port2 8P
D-Sub Female
Mini-DIN Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
7 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
Port1 or Port2 8P
Mini-DIN Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
7 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
Port1 or Port2 8P
Mini-DIN Male
9 RX
3 TXD
6 TX
4 RXD
5 GND
7 GND
View from the
soldering point
of a cable.
292
COM3 RS485 2W
9P D-Sub Male
RS485 8P Mini-DIN
Male
1 RX-
6 Data-
2 RXD-
2 RX+
9 Data+
1 RXD+
5 GND
5 GND
7 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 8P Mini-DIN
Male
7 RX-
4 Data-
2 RXD-
6 RX+
1 Data+
1 RXD+
5 GND
5 GND
7 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 8P Mini-DIN
Male
1 RX-
7 Data-
2 RXD-
2 RX+
8 Data+
1 RXD+
5 GND
9 GND
7 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 8P Mini-DIN
Male
1 RX-
6 Data-
2 RXD-
2 RX+
9 Data+
1 RXD+
5 GND
5 GND
7 GND
COM3 RS485 2W
9P D-Sub Male
RS485 8P Mini-DIN
Male
1 RX-
6 Data-
2 RXD-
2 RX+
9 Data+
1 RXD+
5 GND
5 GND
7 GND
293
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 8P Mini-DIN
Male
1 RX-
7 Data-
2 RXD-
2 RX+
8 Data+
1 RXD+
5 GND
5 GND
7 GND
View from the
soldering point
of a cable.
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
A RXD-
2 RX+
9 Data+
B RXD+
5 GND
5 GND
SG GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
A RXD-
6 RX+
1 Data+
B RXD+
5 GND
5 GND
cMT/mTV series
SG GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
A RXD-
2 RX+
8 Data+
B RXD+
5 GND
9 GND
SG GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
A RXD-
2 RX+
9 Data+
B RXD+
5 GND
5 GND
SG GND
294
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
A RXD-
2 RX+
9 Data+
B RXD+
5 GND
5 GND
SG GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
1 RX-
7 Data-
A RXD-
2 RX+
8 Data+
B RXD+
5 GND
5 GND
SG GND
Ethernet cable:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Mar/23/2015
Driver released.
295
Inovance H2U/H1U
Website: http://www.inovance.cn/
HMI Setting:
Parameters
Recommended
Options
PLC type
Inovance H2U/H1U
PLC I/F
RS485 4W
Baud rate
9600
9600~19200
Data bits
7 or 8
Parity
Even
Stop bits
1 or 2
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
OOO
0 ~ 377
Input Bits
OOO
0 ~ 377
Output Bits
DDDD
0 ~ 7999
Auxiliary Relay
DDD
0 ~ 255
Timer Relay
DDD
0 ~ 255
Counter Relay
SM
DDDD
8000 ~ 9999
D_Bit
DDDDdd
0 ~ 799915
DDDD
0 ~ 4095
TV
DDD
0 ~ 255
Timer Memory
CV
DDD
0 ~ 199
Counter Memory
DDDD
0 ~ 7999
Data Registers
DW
CV2
DDD
200 ~ 255
SD
DDDD
8000 ~ 9999
296
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
H2U/H1U RS422 8P
Mini-DIN Male
1 RX-
4 TX-
2 RX+
7 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
3 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
H2U/H1U RS422 8P
Mini-DIN Male
7 RX-
4 TX-
6 RX+
7 TX+
9 TX-
1 RX-
8 TX+
2 RX+
5 GND
3 GND
COM2 RS485 4W
9P D-Sub Male
H2U/H1U RS422 8P
Mini-DIN Male
1 RX-
1 RX-
4 TX-
2 RX+
2 RX+
7 TX+
3 TX-
3 TX-
1 RX-
4 TX+
4 TX+
2 RX+
5 GND
5 GND
3 GND
H2U/H1U RS422 8P
Mini-DIN Male
1 RX-
4 TX-
2 RX+
7 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
3 GND
297
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
H2U/H1U RS422 8P
Mini-DIN Male
1 RX-
4 TX-
2 RX+
7 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
3 GND
View from the
soldering point
of a cable.
Driver Version:
Version
Date
Description
V1.00
May/19/2010
Driver released.
298
Justfi Controller
Supported Series: Justfi weighing instruments, Industrial Batching Controller supports
XK31CB4, XK31CB6.
Website: http://www.justfi.com
HMI Setting:
Parameters
Recommended
Options
PLC type
Justfi controller
PLC I/F
RS232
Baud rate
9600
9600, 19200
Data bits
7 or 8
Parity
Even
Stop bits
1 or 2
Notes
Device Address:
Bit/Word
W
DW
W
W
W
W
W
W
W
W
W
W
W
W
W
W
Device type
Func
Func_DW
RW
RF
RT
RG
RC
RB
MZ
MT
CT
DT
BB
HB
BD
RP1t
.
RP6F
Format
DD
DD
H
H
H
H
H
H
H
H
H
H
H
H
H
Range
0 ~ 99
0 ~ 99
0
0
0
0
0
0
0
0
0
0
0
0
0
Memo
Read / Write
Read / Write
Weight (read only)
Read result (read only)
Read total (read only)
Read prescription group
Circle
Read status (read only)
Zero (write only)
Tare (write only)
Clear tare (write only)
Clear total (write only)
Start (write only)
Stop (write only)
Discharge (write only)
Read/Write recipe
299
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
CB4 RS232
2 RX
8 RX
TD
3 TX
7 TX
RD
5 GND
5 GND
GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
CB4 RS232
2 RX
TD
3 TX
RD
5 GND
GND
CB4 RS232
2 RX
TD
3 TX
RD
5 GND
GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
CB4 RS232
2 RX
6 RX
8 RX
TD
3 TX
4 TX
7 TX
RD
5 GND
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
CB4 RS232
9 RX
TD
6 TX
RD
5 GND
GND
300
Driver Version:
Version
Date
V1.40
Nov/04/2009
Description
301
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
RS485
Baud rate
19200
9600
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
HHHH
0 ~ ffff
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
DMX30 RS232 9P
D-Sub Male
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
DMX30 RS232 9P
D-Sub Female
D-Sub Male
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
302
DMX30 RS232 9P
D-Sub Male
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
DMX30 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
DMX30 RS232 9P
D-Sub Male
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Feb/06/2010
Driver releasesd.
303
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
Even
Stop bits
Notes
RS232
Device Address:
Bit/Word Device type
Format
Range
Memo
RLY
DDDdd0*
0 ~ 655150*
dd:0 ~ 15
DM_Bit
DDDDDh
0 ~ 65535f
DM
DDDDD
0 ~ 65535
TM
DDDD
0 ~ 8999
DDDD
0 ~ 9999
T_Curr
DDDD
0 ~ 9999
T_Preset
DDDD
0 ~ 9999
DDDD
0 ~ 9999
C_Curr
DDDD
0 ~ 9999
C_Preset
DDDD
0 ~ 9999
Timer_Current
Counter_Current
Note:*
If Relay (bit) register is used, please place a zero at the end of the address.
For example, to read Relay (bit) 100, the address is written as 1000.
304
Wiring Diagram:
The following is the view from the soldering point of a cable.
RS232 CPU Port:
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
OP-26486 9P D-Sub
Male
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
OP-26486 9P D-Sub
Male
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
OP-26486 9P D-Sub
D-Sub Female
Male
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
OP-26486 9P D-Sub
Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
OP-26486 9P D-Sub
Male
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
305
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
3 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
4 RXD
5 GND
3 GND
2 RX
2 TXD
3 TX
4 RXD
5 GND
3 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
3 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
4 RXD
5 GND
3 GND
306
Driver Version:
Version
Date
V1.40
Apr/17/2009
Description
307
KEYENCE KV-3000
Supported Series: KEYENCE KV-3000
Website: http://www.keyence.com/
HMI Setting:
Parameters
Recommended
PLC type
KEYENCE KV-3000
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
Even
Stop bits
Options
Notes
PLC Setting:
Communication mode
KV STUDIO mode
Device Address:
Bit/Word Device type
Format
Range
Memo
MR
DDDdd
0 ~ 99915
LR
DDDdd
0 ~ 99915
Latch relay
CR
DDDdd
0 ~ 99915
Control relay
DDDdd
0 ~ 99915
Relay
HHHh
0 ~ 3FFF
Link Relay
DDDD
0 ~ 9999
Timer
DDDD
0 ~ 9999
Counter
DM_Bit
DDDDDdd
0 ~ 6553515
TM_Bit
DDDDdd
0 ~ 999915
CM_Bit
DDDDDdd
0 ~ 6553515
EM_Bit
DDDDDdd
0 ~ 6553515
308
Format
Range
Memo
B
W
FM_Bit
DDDDDdd
0 ~ 6553515
DM
DDDDD
0 ~ 65535
Data memory
TM
DDDD
0 ~ 9999
CM
DDDDD
0 ~ 65535
Control memory
EM
DDDDD
0 ~ 65535
Data memory
FM
DDDDD
0 ~ 65535
File register
MR_Word
DDD
0 ~ 999
LR_Word
DDD
0 ~ 999
CR_Word
DDD
0 ~ 999
HHHH
0 ~ 3FFF
Link register
ZF
DDDDDD
0 ~ 131071
File register
DW
TC
DDDD
0 ~ 9999
DW
TS
DDDD
0 ~ 9999
DW
CC
DDDD
0 ~ 9999
DW
CS
DDDD
0 ~ 9999
DW
DD
1 ~ 12
DW
TRM
0~7
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P RJ11:
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
1 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
2 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
1 TXD
3 TX
3 RXD
5 GND
2 GND
309
2 RX
1 TXD
3 TX
3 RXD
5 GND
2 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
1 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
2 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
1 TXD
6 TX
3 RXD
5 GND
2 GND
Driver Version:
Version
Date
Description
V1.00
May/28/2014
Driver released.
310
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
Ethernet
Port no.
8501
Device Address:
Bit/Word
Device type
Format
Range
MR
DDDdd
0 ~ 99915
LR
DDDdd
0 ~ 99915
CR
DDDdd
0 ~ 99915
RLY
DDDdd
0 ~ 99915
DM
DDDDD
0 ~ 65535
TM
DDDD
0 ~ 9999
DDDD
0 ~ 9999
T_Curr
DDDD
0 ~ 9999
Timer Current
T_Preset
DDDD
0 ~ 9999
Timer Preset
DDDD
0 ~ 9999
C_Curr
DDDD
0 ~ 9999
C_Preset
DDDD
0 ~ 9999
CM
DDDDD
0 ~ 65535
EM
DDDDD
0 ~ 65535
FM
DDDDD
0 ~ 65535
311
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Dec/25/2009
Driver released.
312
KEYENCE KV-L20V/700/1000/3000/5000/Nano
Series
Supported series: KV-L20V,700,1000,3000,5000 series, KV Nano series
Website: http://www.keyence.com/
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
RS232,RS485 2W,RS485 4W
Baud rate
115200
9600 ~ 115200
Data bits
Parity
Even
Stop bits
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
MR
DDDdd
0 ~ 99915
LR
DDDdd
0 ~ 99915
CR
DDDdd
0 ~ 99915
RLY
DDDdd
0 ~ 99915
DM
DDDDD
0 ~ 65535
TM
DDDD
0 ~ 9999
DDDD
0 ~ 9999
T_Curr
DDDD
0 ~ 9999
T_Preset
DDDD
0 ~ 9999
DDDD
0 ~ 9999
C_Curr
DDDD
0 ~ 9999
313
Memo
Timer_Current
Counter_Current
Bit/Word
Device type
Format
Range
C_Preset
DDDD
0 ~ 9999
CM
DDDDD
0 ~ 65535
EM
DDDDD
0 ~ 65535
FM
DDDDD
0 ~ 65535
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
OP-26486 9P D-Sub
Male
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
OP-26486 9P D-Sub
Male
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
OP-26486 9P D-Sub
Male
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
OP-26486 9P D-Sub
Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
314
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
OP-26486 9P D-Sub
Male
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
5 RXD
5 GND
5 GND
1 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
5 RXD
5 GND
1 GND
2 RX
3 TXD
3 TX
5 RXD
5 GND
1 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
5 RXD
5 GND
5 GND
5 GND
1 GND
315
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
5 RXD
5 GND
1 GND
COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male
2W terminal
1 RX-
6 Data-
3 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
1 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
3 D-
6 RX+
1 Data+
5 D+
5 GND
5 GND
1 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male
2W terminal
1 RX-
7 Data-
3 D-
2 RX+
8 Data+
5 D+
5 GND
9 GND
1 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
3 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
1 GND
316
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
3 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
1 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
1 RX-
7 Data-
3 D-
2 RX+
8 Data+
5 D+
5 GND
5 GND
1 GND
1 RX-
3 TX-
2 RX+
5 TX+
3 TX-
2 RX-
4 TX+
4 RX+
5 GND
1 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
3 TX-
6 RX+
5 TX+
9 TX-
2 RX-
8 TX+
4 RX+
5 GND
1 GND
317
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
3 TX-
2 RX+
2 RX+
5 TX+
3 TX-
3 TX-
2 RX-
4 TX+
4 TX+
4 RX+
5 GND
5 GND
1 GND
1 RX-
3 TX-
2 RX+
5 TX+
3 TX-
2 RX-
4 TX+
4 RX+
5 GND
1 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
4W terminal
1 RX-
3 TX-
2 RX+
5 TX+
3 TX-
2 RX-
4 TX+
4 RX+
5 GND
1 GND
Driver Version:
Version
Date
V2.20
Jul/28/2009
V2.30
Oct/5/2012
Description
Support KV-L20V module
318
KEYENCE KV-L20V/700/1000/3000/5000/Nano
Series (KV Studio Mode)
Supported series: KV-L20V,700,1000,3000,5000 series, KV Nano series
Website: http://www.keyence.com/
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
RS232
RS232,RS485 2W,RS485 4W
Baud rate
115200
9600 ~ 115200
Data bits
Parity
Even
Stop bits
PLC Setting:
Communication mode
KV STUDIO mode
Device Address:
Bit/Word
Device type
Format
Range
MR
DDDdd
0 ~ 99915
LR
DDDdd
0 ~ 99915
CR
DDDdd
0 ~ 99915
DDDdd
0 ~ 99915
HHHh
0 ~ 3FFF
DDDD
0 ~ 9999
DDDD
0 ~ 9999
DM_Bit
DDDDDdd
0 ~ 6553515
TM_Bit
DDDDdd
0 ~ 999915
CM_Bit
DDDDDdd
0 ~ 6553515
319
Memo
Bit/Word
Device type
Format
Range
CTC_Bit
Ddd
0 ~ 315
W_Bit
HHHHh
0 ~ 3FFFF
VM_Bit
DDDDDdd
0 ~ 6553515
VB_Bit
HHHh
0 ~ 3FFF
DM
DDDDD
0 ~ 65535
TM
DDDD
0 ~ 9999
CM
DDDDD
0 ~ 65535
EM
DDDDD
0 ~ 65535
FM
DDDDD
0 ~ 65535
MR_Word
DDD
0 ~ 999
LR_Word
DDD
0 ~ 999
CR_Word
DDD
0 ~ 999
HHHH
0 ~ 3FFF
VM
DDDDD
0 ~ 65535
VB
HHH
0 ~ 3FFF
R_Word
DDD
0 ~ 999
B_Word
HHH
0 ~ 3FF
TC
DDDD
0 ~ 9999
TS
DDDD
0 ~ 9999
CC
DDDD
0 ~ 9999
CS
DDDD
0 ~ 9999
DW
CTH
0~1
DW
CTC
0~3
DW
Z_DWORD
DD
1 ~ 12
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
OP-26486 9P D-Sub
Male
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
320
cMT/mTV series
COM1 RS232 9P
D-Sub Female
OP-26486 9P D-Sub
Male
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
OP-26486 9P D-Sub
Male
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
OP-26486 9P D-Sub
Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
OP-26486 9P D-Sub
Male
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
5 RXD
5 GND
5 GND
1 GND
321
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
5 RXD
5 GND
1 GND
2 RX
3 TXD
3 TX
5 RXD
5 GND
1 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
5 RXD
5 GND
5 GND
5 GND
1 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
5 RXD
5 GND
1 GND
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
3 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
1 GND
322
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
3 D-
6 RX+
1 Data+
5 D+
5 GND
5 GND
1 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
3 D-
2 RX+
8 Data+
5 D+
5 GND
9 GND
1 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
3 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
1 GND
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
3 D-
2 RX+
9 Data+
5 D+
5 GND
5 GND
1 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
COM3 RS485 2W
9P D-Sub Female
9P D-Sub Female
2W terminal
1 RX-
7 Data-
3 D-
2 RX+
8 Data+
5 D+
5 GND
5 GND
1 GND
323
1 RX-
3 TX-
2 RX+
5 TX+
3 TX-
2 RX-
4 TX+
4 RX+
5 GND
1 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
3 TX-
6 RX+
5 TX+
9 TX-
2 RX-
8 TX+
4 RX+
5 GND
1 GND
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
3 TX-
2 RX+
2 RX+
5 TX+
3 TX-
3 TX-
2 RX-
4 TX+
4 TX+
4 RX+
5 GND
5 GND
1 GND
1 RX-
3 TX-
2 RX+
5 TX+
3 TX-
2 RX-
4 TX+
4 RX+
5 GND
1 GND
324
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
3 TX-
2 RX+
5 TX+
3 TX-
2 RX-
4 TX+
4 RX+
5 GND
1 GND
Driver Version:
Version
Date
Description
V1.00
May/19/2016
Driver released.
325
KONNEX KNXnet/IP
Supported series: WAGO 750-849
HMI Setting:
Parameters
Recommended
Options
PLC type
KONNEX KNXnet/IP
PLC I/F
Ethernet
224.0.23.12
Port no.
3671
Notes
USE UDP
Bool
bit
Byte
8-bit
DInt
Real
32-bit Float
32-bit
UDInt
32-bit
Array
String
SInt
USInt
Word
Int
UInt
DWord
326
Memo
8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit
PLC Setting:
1. Export Tag file using ETS3 software.
2. In EasyBuilder open System Parameter Settings, add KONNEX KNXnet/IP and then
click [Import Tag].
327
4. Select .esf file and then click [OK] to finish importing tags.
328
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Sep/04/2015
Driver released.
329
Korenix 6550
Website: http://www.korenix.com/
HMI Setting:
Parameters
Recommended
PLC type
Korenix 6550
PLC I/F
Ethernet
Port no.
502
Options
Notes
Modbus protocol
Device Address:
Bit/Word
Device type
Format
Range
1x
DDDDD
1 ~ 65535
0x
DDDDD
1 ~ 65535
3x_Bit
DDDDDdd
100 ~ 6553515
4x_Bit
DDDDDdd
100 ~ 6553515
6x_Bit
DDDDDdd
100 ~ 6553515
3x
DDDDD
1 ~ 65535
4x
DDDDD
1 ~ 65535
5x
DDDDD
1 ~ 65535
6x
DDDDD
1 ~ 65535
330
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V1.61
Apr/17/2009
Description
331
KOYO CLICK
Supported Series: KOYO CLICK PLC series
Website: http://www.automationdirect.com
HMI Setting:
Parameters
Recommended
Options
PLC type
KOYO CLICK
PLC I/F
RS232
Baud rate
38400
Data bits
Parity
Odd
Odd,Even,None
Stop bits
1,2
1~247
Notes
1200~115200
Device Address:
Bit/Word Device type Format
Range
Memo
Ddd
001 ~ 816
Ddd
001 ~ 816
Output Status
DDDD
1 ~ 2000
Control Bit
DDD
1 ~ 500
CT
DDD
1 ~ 250
SC
DDDD
1 ~ 1000
DS
DDDD
1 ~ 4500
Data Registers
DD
DDDD
1 ~ 1000
DH
DDD
1 ~ 500
Data Registers
DF
DDD
1 ~ 500
XD
0~8
YD
0~8
TD
DDD
1 ~ 500
CTD
DDD
1 ~ 250
SD
DDDD
1 ~ 1000
TXT
DDDD
1 ~ 1000
332
Wiring Diagram:
KOYO CLICK PLC Com Port:
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
4 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
1 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
4 TXD
3 TX
3 RXD
5 GND
1 GND
2 RX
4 TXD
3 TX
3 RXD
5 GND
1 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
4 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
1 GND
333
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
4 TXD
6 TX
3 RXD
5 GND
1 GND
Version:
Version
Date
V1.50
Jun/22/2010
V1.70
Oct/20/2014
Description
Fixed the problem where TXT address type 500 and later
cannot be used.
334
HMI Setting:
Parameters
PLC type
Recommended
KOYO CLICK (Ethernet)
PLC I/F
Ethernet
Port no.
25425
0
No need to set station no.
(ms)
PLC
Options
Notes
USE UDP
100~
*Note
sta. no.
*NoteWhen the communication is not stable, please adjust the parameter of [turn around
delay] till the communication is normal.
Device Address:
Bit/Word
Device type
Format
Range
Ddd
1 ~ 816
Ddd
1 ~ 816
DDDD
1 ~ 2000
DDD
1 ~ 500
CT
DDD
1 ~ 250
SC
DDDD
1 ~ 1000
DS
DDDD
1 ~ 4500
DW
DD
DDDD
1 ~ 1000
DH
DDD
1 ~ 500
DW
DF
DDD
1 ~ 500
XD
0~8
YD
0~8
TD
DDD
1 ~ 500
DW
CTD
DDD
1 ~ 250
SD
DDDD
1 ~ 1000
TXT
DDDD
1 ~ 1000
335
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Feb/26/2016
Driver released.
336
KOYO DIRECT
Supported Series: KOYO DirectLogic series PLC DL05, DL06, DL105, DL205, DL305, and
DL405 series.
Website: http://www.automationdirect.com
HMI Setting:
Parameters
Recommended
Options
PLC type
KOYO DIRECT
PLC I/F
RS232
RS232, RS485
Baud rate
9600
Data bits
7, 8
Parity
Odd
Stop bits
1-90
Notes
PLC Setting:
1.
2.
3.
4.
5.
6.
337
Device Address:
Bit/Word Device type
Format
Range
Memo
OOOO
0 ~ 4000
Input Bits
OOOO
0 ~ 4000
Output Bits
OOOOO 0 ~ 10000
Control Relays
OOOO
0 ~ 1000
CT
OOOO
0 ~ 1000
OOOO
0 ~ 2000
SP
OOOO
0 ~ 2000
GX
OOOOO 0 ~ 10000
GY
OOOOO 0 ~ 10000
OOOOO 0 ~ 77777
Timer
OOOO
0 ~ 1000
Counter
OOOO
0 ~ 1000
V Memory
Wiring Diagram:
The following is the view from the soldering point of a cable.
DL05/DL06/DL105/DL230/DL240/DL250/DL350/DL450 RS232 port
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
4 TX
3 TX
7 TX
3 RX
5 GND
5 GND
1 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
4 TX
3 TX
3 RX
5 GND
1 GND
2 RX
4 TX
3 TX
3 RX
5 GND
1 GND
338
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
4 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
1 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
4 TX
6 TX
3 RX
5 GND
1 GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
7 GND
4 RTC
5 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
4 RTC
5 CTS
339
short
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
4 RTC
5 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
7 GND
4 RTC
5 CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
D-Sub Male
9 RX
2 TX
6 TX
3 RX
5 GND
7 GND
4 RTC
5 CTS
340
short
1 RX-
10 TX-
2 RX+
9 TX+
3 TX-
6 RX-
4 TX+
13 RX+
5 GND
7 GND
11 RTS+
14 CTS+
12 RTS15 CTS-
Short
Short
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
10 TX-
6 RX+
9 TX+
9 TX-
6 RX-
8 TX+
13 RX+
5 GND
7 GND
11 RTS+
14 CTS+
12 RTS15 CTS-
Short
Short
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
10 TX-
2 RX+
2 RX+
9 TX+
3 TX-
3 TX-
6 RX-
4 TX+
4 TX+
13 RX+
5 GND
5 GND
7 GND
11 RTS+
14 CTS+
12 RTS15 CTS341
Short
Short
1 RX-
10 TX-
2 RX+
9 TX+
3 TX-
6 RX-
4 TX+
13 RX+
5 GND
7 GND
11 RTS+
14 CTS+
12 RTS15 CTS-
Short
Short
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
10 TX-
2 RX+
9 TX+
3 TX-
6 RX-
4 TX+
13 RX+
5 GND
7 GND
11 RTS+
14 CTS+
12 RTS15 CTS-
342
Short
Short
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
13 GND
1 YOP
7 CTS
short
2 YOM
4 ONLINE
14 GND
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
13 GND
1 YOP
7 CTS
short
2 YOM
4 ONLINE
14 GND
short
D-Sub Female
D-Sub Male
2 RX
2 TX
3 TX
3 RX
5 GND
13 GND
1 YOP
7 CTS
short
2 YOM
4 ONLINE
14 GND
343
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
13 GND
1 YOP
7 CTS
short
2 YOM
4 ONLINE
14 GND
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TX
6 TX
3 RX
5 GND
13 GND
1 YOP
7 CTS
short
2 YOM
4 ONLINE
14 GND
344
short
COM3 RS232 9P
D-Sub Female
2 RX
RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
7 GND
4 RTC
5 CTS
Short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
4 RTC
5 CTS
Short
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
4 RTC
5 CTS
345
Short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
7 GND
4 RTC
5 CTS
Short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TX
6 TX
3 RX
5 GND
7 GND
4 RTC
5 CTS
346
Short
1 RX-
16 TX-
2 RX+
14 TX+
3 TX-
10 RX-
4 TX+
9 RX+
5 GND
7 GND
19 RTS+
11 CTS+
18 RTS23 CTS-
Short
Short
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
16 TX-
6 RX+
14 TX+
9 TX-
10 RX-
8 TX+
9 RX+
5 GND
7 GND
19 RTS+
11 CTS+
18 RTS23 CTS-
Short
Short
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
16 TX-
2 RX+
2 RX+
14 TX+
3 TX-
3 TX-
10 RX-
4 TX+
4 TX+
9 RX+
5 GND
5 GND
7 GND
19 RTS+
11 CTS+
18 RTS23 CTS347
Short
Short
1 RX-
16 TX-
2 RX+
14 TX+
3 TX-
10 RX-
4 TX+
9 RX+
5 GND
7 GND
19 RTS+
11 CTS+
18 RTS23 CTS-
Short
Short
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
16 TX-
2 RX+
14 TX+
3 TX-
10 RX-
4 TX+
9 RX+
5 GND
7 GND
19 RTS+
11 CTS+
18 RTS23 CTS-
Short
Short
1 RX-
13 TX-
2 RX+
12 TX+
3 TX-
25 RX-
4 TX+
24 RX+
5 GND
7 GND
348
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
13 TX-
6 RX+
12 TX+
9 TX-
25 RX-
8 TX+
24 RX+
5 GND
7 GND
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
13 TX-
2 RX+
2 RX+
12 TX+
3 TX-
3 TX-
25 RX-
4 TX+
4 TX+
24 RX+
5 GND
5 GND
7 GND
9P D-Sub Male
D-Sub Male
1 RX-
13 TX-
2 RX+
12 TX+
3 TX-
25 RX-
4 TX+
24 RX+
5 GND
7 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
D-Sub Male
1 RX-
13 TX-
2 RX+
12 TX+
3 TX-
25 RX-
4 TX+
24 RX+
5 GND
7 GND
349
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
7 GND
4 RTC
5 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
4 RTC
5 CTS
short
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
4 RTC
5 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
7 GND
4 RTC
5 CTS
350
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TX
6 TX
3 RX
5 GND
7 GND
4 RTC
5 CTS
Driver Version:
Version
Date
V1.30
Nov/08/2010
Description
351
short
KOYO Do-more
Supported Series: Do-more H2 Series PLC
Website: http://www.automationdirect.com
HMI Setting:
Parameters
Recommended
PLC type
KOYO Do-more
PLC I/F
RS232
Baud rate
115200
Data bits
Parity
None
Stop bits
Online simulation
Options
Notes
9600 ~ 115200
YES
PLC Setting:
Serial Port Mode
Do-more programming
Device Address:
toBit/Word
Device type
Format
Range
ST
DDDD
0 ~ 1023
rB
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
MI
DDDDD
0 ~ 65535
MC
DDDDD
0 ~ 65535
T.Done
DDDDD
0 ~ 32766
Read only
CT.Done
DDDDD
0 ~ 32766
Read only
DLX
OOOOOO
0 ~ 177777
DLY
OOOOOO
0 ~ 177777
DLC
OOOOOO
0 ~ 177777
DLV
OOOOOO
0 ~ 177777
SDT
D.D
0 ~ 7.6
352
Memo
*Note 1
Bit/Word
Device type
Format
Range
Memo
WX
DDDDD
0 ~ 65535
WY
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
SS
DDDD.DD
0 ~ 3854.34
SL
DDDD.DDD
0 ~ 1007.130
UDT
DDDDD.D
0 ~ 32767.6
*Note 1
PL
DDD
0 ~ 255
MIR
DDDDD
0 ~ 65535
MHR
DDDDD
0 ~ 65535
DST
DDD
0 ~ 511
DDDDD
0 ~ 65534
DDDDD
0 ~ 65534
T.ACC
DDDDD
0 ~ 32766
W
CT.ACC
DDDDD
0 ~ 32766
*Note 1SDT , UDT: xxx.0 = Year, xxx.1 = Month, xxx.2 = Day, xxx.3 = DayOfWeek,
xxx.4 = Hour, xxx.5 = Minute, xxx.6 = Second.
*Note 2SS , SL: xxx.0 = MaxLen, xxx.1 = Length, xxx.2 ~ 34 = String(SS)
xxx.2 ~ 130 = String (SL)
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
4 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
1 GND
7 RTS
6 CTS
8 CTS
5 RTS
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
4 TXD
3 TX
3 RXD
5 GND
1 GND
353
2 RX
4 TXD
3 TX
3 RXD
5 GND
1 GND
7 RTS
6 CTS
8 CTS
5 RTS
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
4 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
1 GND
7 RTS
6 CTS
8 CTS
5 RTS
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS-232 6P RJ12
9 RX
4 TXD
6 TX
3 RXD
5 GND
1 GND
Driver Version:
Version
Date
Description
V1.00
Apr/03/2013
Driver released.
354
HMI Setting:
Parameters
PLC type
Recommended
Options
KOYO Do-more (Ethernet)
Notes
PLC I/F
Ethernet
USE UDP
Port no.
28784
PLC Setting:
Serial Port Mode
Do-more programming
Device Address:
Bit/Word
Device type
Format
Range
ST
DDDD
0 ~ 1023
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
MI
DDDDD
0 ~ 65535
MC
DDDDD
0 ~ 65535
T.Done
DDDDD
0 ~ 32766
Read only
CT.Done
DDDDD
0 ~ 32766
Read only
DLX
OOOOOO
0 ~ 177777
DLY
OOOOOO
0 ~ 177777
DLC
OOOOOO
0 ~ 177777
DLV
OOOOOO
0 ~ 177777
SDT
D.D
0 ~ 7.6
WX
DDDDD
0 ~ 65535
WY
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
355
Memo
*Note 1
Bit/Word
Device type
Format
Range
Memo
SS
DDDD.DD
0 ~ 3854.34
SL
DDDD.DDD
0 ~ 1007.130
UDT
DDDDD.D
0 ~ 32767.6
*Note 1
PL
DDD
0 ~ 255
MIR
DDDDD
0 ~ 65535
MHR
DDDDD
0 ~ 65535
DST
DDD
0 ~ 511
DDDDD
0 ~ 65534
DDDDD
0 ~ 65534
T.ACC
DDDDD
0 ~ 32766
W
CT.ACC
DDDDD
0 ~ 32766
*Note 1SDT , UDT: xxx.0 = Year, xxx.1 = Month, xxx.2 = Day, xxx.3 = DayOfWeek,
xxx.4 = Hour, xxx.5 = Minute, xxx.6 = Second.
*Note 2SS , SL: xxx.0 = MaxLen, xxx.1 = Length, xxx.2 ~ 34 = String(SS)
xxx.2 ~ 130 =String (SL)
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Apr/03/2013
Driver released.
356
KOYO Ethernet
Supported Series: KOYO DirectLogic series, model H0-ECOM100, H2-ECOM100.
Website: http://www.automationdirect.com
HMI Setting:
Parameters
PLC type
Recommended
KOYO Ethernet
Options
PLC I/F
Ethernet
Port no.
28784
Notes
UDP/IP
Device Address:
Bit/Word
Device type
Format
Range
Memo
GX
OOOO
0 ~ 3777
Global I/O
OOOO
0 ~ 1777
SP
OOOO
0 ~ 1777
GY
OOOO
0 ~ 3777
OOOO
0 ~ 1777
OOOO
0 ~ 3777
Control Relays
OOOO
0 ~ 1777
OOO
0 ~ 377
CT
OOO
0 ~ 377
OOOOO
0 ~ 41237
V-memory
CCM_32
HHH
1 ~ 200
GX, X, SP
CCM_33
HHH
1 ~ 340
GY,Y,C,S,T,CT
CCM_31
HHHH
1 ~ 42a0
357
Range
CCM_31
1~42A0
0~41237
CCM_32
1~FF
GX
0~3777
CCM_32
101~17F
0~1777
CCM_32
181~1FF
SP
0~1777
CCM_33
1~FF
GY
0~3777
CCM_33
101~17F
0~1777
CCM_33
181~27F
0~3777
CCM_33
281~2FF
0~1777
CCM_33
301~31F
0~377
CCM_33
321~33F
CT
0~377
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V1.10
Jul/03/2009
Description
358
Lenze
Supported Series: PLC Model No.: 9300/8200 series, and EPL10200
Pass-through 2102IB fieldbus module: RS485 (LECOM B)
Website: http://www.lenze.de
HMI Setting:
Parameters
Recommended
Options
PLC type
Lenze
PLC I/F
RS232
Baud rate
9600
9600, 19200
Data bits
7,8
Parity
None
Stop bits
1, 2
0-255
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
CNB
DDDDdd
0 ~ 999915
CB
DDDDddxx
0 ~ 81920015
CI
DDDDdd
0 ~ 819200
CD
DDDDdd
0 ~ 819200
CF
DDDDdd
0 ~ 819200
CNI
DDDD
0 ~ 9999
CND
DDDD
0 ~ 9999
CNF
DDDD
0 ~ 9999
359
Memo
Subcode not supported.
Can only read/write CNI
Word Type.
Subcode supported.
Can only read/write CI
Word Type.
Subcode supported.
Integer
Subcode supported.
DWord
Subcode supported.
DWord (float point)
Subcode not supported.
Integer
Subcode not supported.
DWord
Subcode not supported.
DWord (float point)
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole
1 RX-
6 Data-
72 T/R (A)
2 RX+
9 Data+
71 T/R (B)
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole
7 RX-
4 Data-
72 T/R (A)
6 RX+
1 Data+
71 T/R (B)
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole
1 RX-
7 Data-
72 T/R (A)
2 RX+
8 Data+
71 T/R (B)
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole
1 RX-
6 Data-
72 T/R (A)
2 RX+
9 Data+
71 T/R (B)
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole
1 RX-
6 Data-
72 T/R (A)
2 RX+
9 Data+
71 T/R (B)
5 GND
5 GND
360
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
Lenze 2102IB
LECOM-B RS485
plug-in terminal 4-pole
1 RX-
7 Data-
72 T/R (A)
2 RX+
8 Data+
71 T/R (B)
5 GND
5 GND
Driver Version:
Version
Date
V1.20
Sep/6/2011
Description
361
LingYan BMS
Website: http://www.lyeda.com/Project_file/bms01.htm
HMI Setting:
Parameters
Recommended
PLC type
LingYan BMS
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
None
Stop bits
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
Battery_Unit
Insulator_Unit D
Switch_Unit
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 4P Terminal
2 RX
8 RX
1 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
4 GND
cMT/mTV series
COM1 RS232 9P
RS232 4P Terminal
D-Sub Female
2 RX
1 TXD
3 TX
3 RXD
5 GND
4 GND
362
RS232 4P Terminal
2 RX
1 TXD
3 TX
3 RXD
5 GND
4 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 4P Terminal
2 RX
6 RX
8 RX
1 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
4 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 4P Terminal
9 RX
1 TXD
6 TX
3 RXD
5 GND
4 GND
Driver Version:
Version
Date
V1.10
Nov/12/2009
Description
363
LIYAN EX series
Supported Series: LIYAN PLC Ex/Ex1s/Ex1n/Ex2n series
Website: http://www.liyanplc.com/
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
Mitsubishi FX0s/FX0n/FX1s/FX1n/FX2
PLC I/F
RS232
RS232
Baud rate
9600
9600~115200
Data bits
7,8
Parity
Even
Stop bits
1,2
0-255
Device Address:
Bit/Word
Device type
Format
Range
Memo
ooo
0 ~ 377
Input Relay
ooo
0 ~ 377
Output Relay
ddd
0 ~ 9999
ddd
0 ~ 255
ddd
0 ~ 255
TV
ddd
0 ~ 255
Timer Register
CV
ddd
0 ~ 199
Counter Register
ddd
0 ~ 9999
Data Register
CV2
ddd
200 ~ 255
SD
ddd
364
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 8P Mini-DIN: Ex, Ex1s, Ex1n, Ex2n series
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
8 RX
2 TXD
3 TX
7 TX
7 RXD
5 GND
5 GND
6 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
2 TXD
3 TX
7 RXD
5 GND
6 GND
RS232 8P Mini-DIN
D-Sub Female
Male
2 RX
2 TXD
3 TX
7 RXD
5 GND
6 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 8P Mini-DIN
Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
7 RXD
5 GND
5 GND
5 GND
6 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
9 RX
2 TXD
6 TX
7 RXD
5 GND
6 GND
View from the
soldering point
of a cable.
365
Driver Version:
Version
Date
V1.20
Oct/26/2011
Description
366
LoXin
Website: http://www.loxin-china.com
HMI Setting:
Parameters
Recommended
PLC type
LoXin
PLC I/F
RS-485 2W
Baud rate
9600
Data bits
Parity
Odd
Stop bits
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
Battery_Unit
Insulator_Unit D
Switch_Unit
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
COM3 RS485 2W
RS485 terminal
9P D-Sub Female
9P D-Sub Female
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
367
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
Driver Version:
Version
Date
V1.00
Oct/16/2008
Description
368
LS GLOFA Cnet
Supported Series: LS GLOFA GM6/GM7 CPU port. G7L-CUEB / G6L-CUEB / G4L-CUEA
/ G3L-CUEA Cnet module
Website: http://www.lgis.com/
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
LS GLOFA Cnet
PLC I/F
RS232
RS232/RS485 2W/4W
Baud rate
9600
9600~115200
Data bits
7, 8
Parity
None
Stop bits
0~31
PLC Setting:
Communication mode
Communication module
Device Address:
Bit/Word
Device type
Format
Range
Memo
MX
DDDDD
0 ~ 32767
Internal Relay
IX
ddDdd
0 ~ 63763
Input
QX
ddDdd
0 ~ 63763
Output
MW
DDDDD
0 ~ 32767
Data Register
DW
MD
DDDDD
0 ~ 16383
Double Word
Device explanation:
IX and QX format: dd D dd
Module Contact Number (0 to 63)
Slot Number (0 to 7)
Base Number (0 to 63)
369
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
7 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
7 TXD
3 TX
4 RXD
5 GND
5 GND
D-Sub Female
2 RX
7 TXD
3 TX
4 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
7 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
7 TXD
6 TX
4 RXD
5 GND
5 GND
370
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
1 CD
7 RTS
short
8 CTS
4 DTR
6 DSR
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
1 CD
7 RTS
short
8 CTS
4 DTR
6 DSR
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
1 CD
7 RTS
short
8 CTS
4 DTR
6 DSR
371
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
1 CD
7 RTS
short
8 CTS
4 DTR
6 DSR
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
1 CD
7 RTS
short
8 CTS
4 DTR
6 DSR
short
RS422 terminal
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
GND
372
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS422 terminal
7 RX-
SDB
6 RX+
SDA
9 TX-
RDB
8 TX+
RDA
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
RS422 terminal
1 RX-
1 RX-
SDB
2 RX+
2 RX+
SDA
3 TX-
3 TX-
RDB
4 TX+
4 TX+
RDA
5 GND
5 GND
GND
RS422 terminal
9P D-Sub Male
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
RS422 terminal
9P D-Sub Female
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
GND
373
Driver Version:
Version
Date
V1.80
Jun/08/2010
Description
374
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
2004
Notes
0~31
Device Address:
Bit/Word
Device type
Format
Range
Memo
MX
DDDDDD
0 ~ 131056
Internal Relay
IX
ddDdd
0 ~ 63763
Input
QX
ddDdd
0 ~ 63763
Output
MW
DDDD
0 ~ 8191
Data Register
DW
MD
DDDD
0 ~ 4095
Double Word
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Apr/02/2009
Driver released.
375
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
38400
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
MX
DDDDDD
0 ~ 524272
IX
ddDdd
0 ~ 63763
00.0.0 ~ 63.7.63
(dd.D.dd)
QX
ddDdd
0 ~ 63763
00.0.0 ~ 63.7.63
(dd.D.dd)
IW
HHH
0 ~ 273
QW
HHH
0 ~ 273
MW
DDDDD
0 ~ 32767
MD
DDDDD
0 ~ 16383
376
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
LS GLOFA series
RS232 9P D-Sub Male
2 RX
8 RX
3 TD
3 TX
7 TX
2 RD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
LS GLOFA series
RS232 9P D-Sub Male
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
LS GLOFA series
RS232 9P D-Sub Male
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
LS GLOFA series
RS232 9P D-Sub Male
2 RX
6 RX
8 RX
3 TD
3 TX
4 TX
7 TX
2 RD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
LS GLOFA series
RS232 9P D-Sub Male
9 RX
3 TD
6 TX
2 RD
5 GND
5 GND
377
Driver Version:
Version
Date
V1.30
Mar/08/2010
Description
378
LS MASTER-K Cnet
Supported Series: LS MASTER-K series: K80S, K200S, K300S, and K1000S
Website: http://www.lgis.com/
HMI Setting:
Parameters
Recommended
PLC type
LS MASTER-K Cnet
PLC I/F
RS232
RS232/RS485
Baud rate
38400
Data bits
Parity
None
Stop bits
0-31
Online simulator
Options
Notes
YES
Device Address:
Bit/Word
Device type
Format
Range
Memo
PW_Bit
DDDh
0 ~ 255f
KW_Bit
DDDh
0 ~ 255f
MW_Bit
DDDh
0 ~ 255f
LW_Bit
DDDh
0 ~ 255f
FW_Bit
DDDh
0 ~ 255f
TX
DDDh
0 ~ 255
CX
DDDh
0 ~ 255
DW_bit
DDDDh
0 ~ 9999f
SX
DD.DD
0 ~ 99.99
MW
DDD
0 ~ 255
LW
DDD
0 ~ 255
FW
DDD
0 ~ 255
PW
DD
0 ~ 63
KW
DD
0 ~ 63
TW
DDD
0 ~ 255
CW
DDD
0 ~ 255
DW
DDDD
0 ~ 9999
379
D_bit
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
7 TX
3 TX
7 TX
4 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
7 TX
3 TX
4 RX
5 GND
5 GND
2 RX
7 TX
3 TX
4 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
7 TX
3 TX
4 TX
7 TX
4 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
7 TX
6 TX
4 RX
5 GND
5 GND
380
Driver Version:
Version
Date
Description
V1.00
Apr/19/2010
Driver released.
V1.10
May/11/2011
V1.20
Mar/23/2015
381
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS232
RS232/RS485
Baud rate
38400
Data bits
Parity
None
Stop bits
0-31
Online simulator
Options
Notes
YES
Device Address:
Bit/Word
Device type
Format
Range
Memo
PW_Bit
DDDh
0 ~ 255f
KW_Bit
DDDh
0 ~ 255f
MW_Bit
DDDh
0 ~ 255f
LW_Bit
DDDh
0 ~ 255f
FW_Bit
DDDh
0 ~ 255f
TX
DDD
0 ~ 255
CX
DDD
0 ~ 255
SX
DD.DD
0 ~ 99.99
DW_bit
DDDDh
0 ~ 9999f
D_bit
MW
DDD
0 ~ 255
LW
DDD
0 ~ 255
FW
DDD
0 ~ 255
PW
DD
0 ~ 63
KW
DD
0 ~ 31
TW
DDD
0 ~ 255
CW
DDD
0 ~ 255
DW
DDDD
0 ~ 9999
382
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
383
Driver Version:
Version
Date
Description
V1.20
May/11/2011
V1.30
Feb/10/2015
384
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
Even
Even
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
PW_Bit
DDDDh
0 ~ 9999f
KW_Bit
DDDDh
0 ~ 9999f
MW_Bit
DDDDh
0 ~ 9999f
LW_Bit
DDDDh
0 ~ 9999f
FW_Bit
DDDDh
0 ~ 9999f
DW_Bit
DDDDh
0 ~ 9999f
MW
DDDD
0 ~ 9999
LW
DDDD
0 ~ 9999
FW
DDDD
0 ~ 9999
TW
DDDD
0 ~ 9999
Timer (T)
CW
DDDD
0 ~ 9999
Counter (C)
SW
DDDD
0 ~ 9999
DW
DDDD
0 ~ 9999
DW
TD
DDDD
0 ~ 9999
DW
CD
DDDD
0 ~ 9999
DW
SD
DDDD
0 ~ 9999
DW
DD
DDDD
0 ~ 9999
385
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
386
Driver Version:
Version
Date
Description
V1.10
May/11/2011
V1.20
Feb/10/2015
387
LS MASTER-K10S1
Supported Series: LS MASTER-K10S1
Website: http://www.lgis.com/
HMI Setting:
Parameters
Recommended
Options
PLC type
LS MASTER-K10S1
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
None
None
Stop bits
Notes
RS232/RS485
Device Address:
Bit/Word
Device type
Format
Range
Memo
PW_Bit
DDDh
0 ~ 255f
KW_Bit
DDDh
0 ~ 255f
MW_Bit
DDDh
0 ~ 255f
LW_Bit
DDDh
0 ~ 255f
FW_Bit
DDDh
0 ~ 255f
TX
DDD
0 ~ 255
Timer (T)
CX
DDD
0 ~ 255
Counter (C)
TW
DDD
0 ~ 255
CW
DDD
0 ~ 255
DW
DDDD
0 ~ 9999
388
Wiring Diagram:
The following is the view from the soldering point of a cable.
Driver eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
389
Version:
Version
Date
Description
V1.00
Sep/08/2009
Driver released.
V1.10
Feb/10/2015
390
LS XBM/XBC Cnet
Supported Series: LS XGB Series XBM/XBC CPU with communication module
XGL-CH2A.
Website: http://www.lgis.com/
HMI Setting:
Parameters
Recommended
Options
PLC type
LS XBM/XBC Cnet
PLC I/F
RS232
RS232/RS485
Baud rate
115200
9600~115200
Data bits
7, 8
Parity
None
Stop bits
0-31
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
PW_Bit
DDDDh
0 ~ 2047f
MW_Bit
DDDDh
0 ~ 2047f
LW_Bit
DDDDDh
0 ~ 11263f
KW_Bit
DDDDh
0 ~ 2559f
FW_Bit
DDDDh
0 ~ 2047f
DW_Bit
DDDDDh
0 ~ 32767f
UW_Bit
DH.DDh
0 ~ 7f.31f
RW_Bit
DDDDDh
0 ~ 32767f
SX
DDDDD
0 ~ 12799
TX
DDDD
0 ~ 2047
CX
DDDD
0 ~ 2047
PW
DDDD
0 ~ 2047
MW
DDDD
0 ~ 2047
LW
DDDDD
0 ~ 11263
391
Bit/Word
Device type
Format
Range
Memo
KW
DDDD
0 ~ 2559
FW
DDDD
0 ~ 2047
DW
DDDDD
0 ~ 32767
UW
DH.DD
0.00 ~ 7f.31
RW
DDDDD
0 ~ 32767
SW
DDDDD
0 ~ 127
TW
DDDD
0 ~ 2047
CW
DDDD
0 ~ 2047
NW
DDDDD
0 ~ 21503
ZW
DDD
0 ~ 127
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
392
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
485-
2 RX+
9 Data+
485+
5 GND
5 GND
GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W Terminal
7 RX-
4 Data-
485-
6 RX+
1 Data+
485+
5 GND
5 GND
GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
7 Data-
485-
2 RX+
8 Data+
485+
5 GND
9 GND
GND
393
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
485-
2 RX+
9 Data+
485+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
485-
2 RX+
9 Data+
485+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W Terminal
1 RX-
7 Data-
485-
2 RX+
8 Data+
485+
5 GND
5 GND
GND
Driver Version:
Version
Date
Description
V1.50
Mar/07/2011
V1.70
Jun/28/2012
V1.80
Mar/10/2014
V2.00
Feb/10/2015
394
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
2004
Notes
0~255
PLC Setting:
Communication mode
FEnet Protocol
Device Address:
Bit/Word
Device type
Format
Range
Memo
PW_Bit
DDDDh
0 ~ 2047f
MW_Bit
DDDDh
0 ~ 2047f
LW_Bit
DDDDDh
0 ~ 11263f
KW_Bit
DDDDh
0 ~ 2559f
FW_Bit
DDDDh
0 ~ 2047f
DW_Bit
DDDDDh
0 ~ 32767f
UW_Bit
DH.DDh
0 ~ 7f.31f
XGK-CPUE : hh(0~1f)
RW_Bit
DDDDDf
0 ~32767f
SX
DDDDD
0 ~ 12799
TX
DDDD
0 ~ 2047
CX
DDDD
0 ~ 2047
PW
DDDD
0 ~ 2047
MW
DDDD
0 ~ 2047
LW
DDDDD
0 ~ 11263
Communication device_20,480
KW
DDDD
0 ~ 2559
points
Preservation
device_4,096 points
FW
DDDD
0 ~ 2047
DW
DDDDD
0 ~ 32767
UW
DH.DD
0.00 ~ 7f.31
395
Bit/Word
Device type
Format
Range
Memo
RW
DDDDD
0 ~ 32767
SW
DDDDD
0 ~ 127
TW
DDDD
0 ~ 2047
CW
DDDD
0 ~ 2047
NW
DDDDD
0 ~ 21503
ZW
DDD
0 ~ 127
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.50
Aug/16/2011
V1.60
Jun/28/2012
V1.70
Mar/10/2014
V1.80
Feb/10/2015
396
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
RS232
Baud rate
115200
9600~115200
Data bits
7, 8
Parity
None
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
PW_Bit
DDDDh
0 ~ 2047f
MW_Bit
DDDDh
0 ~ 2047f
LW_Bit
DDDDDh
0 ~ 11263f
KW_Bit
DDDDh
0 ~ 2559f
FW_Bit
DDDDh
0 ~ 2047f
DW_Bit
DDDDDh
0 ~ 32767f
1025)
Data
UW_Bit
DH.DDh
0 ~ 3f.31f
XGK-CPUE : hh(0~1f)
RW_Bit
DDDDDh
0 ~ 32767f
SX
DDDDD
0 ~ 12799
TX
DDDD
0 ~ 2047
CX
DDDD
0 ~ 2047
PW
DDDD
0 ~ 2047
I/O device
MW
DDDD
0 ~ 2047
Internal device
LW
DDDDD
0 ~ 11263
Communication device
KW
DDDD
0 ~ 2559
Preservation device
FW
DDDD
0 ~ 2047
SW
DDDDD
0 ~ 127
DW
DDDDD
0 ~ 32767
Data register
397
register_Bit expression
Bit/Word
Device type
Format
Range
Memo
UW
DH.DD
0.00 ~ 3f.31
NW
DDDDD
0 ~ 21503
ZW
DDD
0 ~ 127
TW
DDDD
0 ~ 2047
CW
DDDD
0 ~ 2047
RW
DDDDD
0 ~ 32767
ZRW
DDDDD
0 ~ 32767
TSW
DDDD
0 ~ 2047
Setup value
CSW
DDDD
0 ~ 2047
Setup value
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
XGB RS232 6P
Mini-DIN
2 RX
8 RX
6 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
3 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
XGB RS232 6P
Mini-DIN
2 RX
6 TXD
3 TX
2 RXD
5 GND
3 GND
XGB RS232 6P
D-Sub Female
Mini-DIN
2 RX
6 TXD
3 TX
2 RXD
5 GND
3 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
XGB RS232 6P
Mini-DIN
2 RX
6 RX
8 RX
6 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
3 GND
398
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
XGB RS232 6P
Mini-DIN
9 RX
6 TXD
6 TX
2 RXD
5 GND
3 GND
View from the
soldering point
of a cable.
COM3 RS232 9P
D-Sub Female
D-Sub Female
Male
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
D-Sub Female
Male
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
399
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.40
Mar/10/2011
V1.60
Jun/18/2012
V1.70
Mar/10/2014
V1.80
Feb/10/2015
400
LS XEC Cnet
Supported Series: LS XGB Series XEC CPU with communication module XGL-CH2A.
Website: http://www.lgis.com/
HMI Setting:
Parameters
Recommended
Options
PLC type
LS XEC Cnet
PLC I/F
RS232
RS232/RS485
Baud rate
115200
9600 ~ 115200
Data bits
7, 8
Parity
None
Stop bits
1,2
0 ~ 32
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
AW_Bit
DDDDDDh
0 ~ 262143f
IW_Bit
DDD.DD.Dh
0 ~ 127.15.3f
QW_Bit
DDD.DD.Dh
0 ~ 127.15.3f
MW_Bit
DDDDDDh
0 ~ 131071f
RW_Bit
DDDDDh
0 ~ 32767f
WW_Bit
DDDDDh
0 ~ 65535f
FW_Bit
DDDDh
0 ~ 2047f
KW_Bit
DDDDh
0 ~ 8399f
LW_Bit
DDDDDh
0 ~ 11263f
NW_Bit
DDDDDh
0 ~ 25087f
UW_Bit
DD.DD.DDh
0 ~ 31.15.31f
AX
DDDDDDD
0 ~ 4194303
IX
DDD.DD.DD
0 ~ 127.15.63
QX
DDD.DD.DD
0 ~ 127.15.63
MX
DDDDDDD
0 ~ 2097151
RX
DDDDDD
0 ~ 524287
WX
DDDDDDD
0 ~ 1048575
FX
DDDDD
0 ~ 32767
KX
DDDDDD
0 ~ 134399
401
Bit/Word
Device type
Format
Range
Memo
LX
DDDDDDD
0 ~ 1880223
NX
DDDDDD
0 ~ 401407
UX
DD.DD.DDD
31.15.511
AW
DDDDDD
0 ~ 262143
Automatic variable
IW
DDD.DD.D
0 ~ 127.15.3
Input device
QW
DDD.DD.D
0 ~ 127.15.3
Output device
MW
DDDDDD
0 ~ 131071
Direct variable
RW
DDDDD
0 ~ 32767
Direct variable
WW
DDDDD
0 ~ 65535
Direct variable
FW
DDDD
0 ~ 2047
System flag
KW
DDDD
0 ~ 8399
LW
DDDDD
0 ~ 11263
NW
DDDDD
0 ~ 25087
P2P flag
UW
DD.DD.DD
0 ~ 31.15.31
Analog flag
DW
MD
DDDDD
0 ~ 65535
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 Terminal
2 RX
8 RX
TX
3 TX
7 TX
RX
5 GND
5 GND
SG
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 Terminal
2 RX
TX
3 TX
RX
5 GND
SG
RS232 Terminal
2 RX
TX
3 TX
RX
5 GND
SG
402
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 Terminal
2 RX
6 RX
8 RX
TX
3 TX
4 TX
7 TX
RX
5 GND
5 GND
5 GND
SG
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 Terminal
9 RX
TX
6 TX
RX
5 GND
SG
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
485-
2 RX+
9 Data+
485+
5 GND
5 GND
GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W Terminal
7 RX-
4 Data-
485-
6 RX+
1 Data+
485+
5 GND
5 GND
GND
403
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
7 Data-
485-
2 RX+
8 Data+
485+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
485-
2 RX+
9 Data+
485+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
485-
2 RX+
9 Data+
485+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W Terminal
1 RX-
7 Data-
485-
2 RX+
8 Data+
485+
5 GND
5 GND
GND
Driver Version:
Version
Date
Description
V1.00
Aug/27/2012
Driver released.
Sep/18/2014
V1.30
Feb/10/2015
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
2004
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
AW_Bit
DDDDDh
0 ~ 16383f
IW_Bit
DD.DD.Df
0 ~ 15.15.3f
QW_Bit
DD.DD.Df
0 ~ 15.15.3f
MW_Bit
DDDDh
0 ~ 8191f
RW_Bit
DDDDDh
0 ~ 10239f
WW_Bit
DDDDDh
0 ~ 10239f
FW_Bit
DDDDh
0 ~ 1023f
KW_Bit
DDDDh
0 ~ 4095f
LW_Bit
DDDDh
0 ~ 2047f
NW_Bit
DDDDh
0 ~ 5119f
UW_Bit
DD.DD.DDf
0 ~ 31.15.31f
AX
DDDDDD
0 ~ 262143
IX
DDD.DD.DD
0 ~ 127.15.63
QX
DDD.DD.DD
0 ~ 127.15.63
MX
DDDDDD
0 ~ 131071
RX
DDDDDD
0 ~ 163839
WX
DDDDDD
0 ~ 163839
FX
DDDDD
0 ~ 16383
KX
DDDDD
0 ~ 65535
LX
DDDDD
0 ~ 32767
NX
DDDDD
0 ~ 81919
UX
DD.DD.DDD
0 ~ 31.15.511
AW
DDDDD
0 ~ 16383
405
Automatic variable
Bit/Word
Device type
Format
Range
Memo
IW
DDD.DD.D
0 ~ 15.15.3
Input device
QW
DDD.DD.D
0 ~ 15.15.3
Output device
MW
DDDD
0 ~ 8191
Direct variable
RW
DDDDD
0 ~ 10239
Direct variable
WW
DDDDD
0 ~ 10239
Direct variable
FW
DDDD
0 ~ 1023
System flag
KW
DDDD
0 ~ 4095
LW
DDDD
0 ~ 2047
NW
DDDD
0 ~ 5119
P2P flag
UW
DD.DD.DD
0 ~ 31.15.31
Analog flag
DW
MD
DDDD
0 ~ 4095
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Aug/28/2012
Driver released.
Sep/18/2014
V1.20
Feb/10/2015
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
RS232
Baud rate
115200
9600~115200
Data bits
7, 8
Parity
None
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
AW_Bit
DDDDDDh
0 ~ 262143f
IW_Bit
DDD.DD.Dh
0 ~ 127.15.3f
QW_Bit
DDD.DD.Dh
0 ~ 127.15.3f
MW_Bit
DDDDDDh
0 ~ 131071f
RW_Bit
DDDDDh
0 ~ 32767f
WW_Bit
DDDDDh
0 ~ 65535f
FW_Bit
DDDDh
0 ~ 2047f
KW_Bit
DDDDh
0 ~ 8399f
LW_Bit
DDDDDh
0 ~ 11263f
NW_Bit
DDDDDh
0 ~ 25087f
UW_Bit
DD.DD.DDh
0 ~ 31.15.31f
AX
DDDDDDD
0 ~ 4194303
IX
DDD.DD.DD
0 ~ 127.15.63
QX
DDD.DD.DD
0 ~ 127.15.63
MX
DDDDDDD
0 ~ 2097151
RX
DDDDDD
0 ~ 524287
407
Memo
Bit/Word
Device type
Format
Range
WX
DDDDDDD
0 ~ 1048575
FX
DDDDD
0 ~ 32767
KX
DDDDDD
0 ~ 134399
LX
DDDDDDD
0 ~ 1880223
NX
DDDDDD
0 ~ 401407
UX
DD.DD.DDD
0 ~ 31.15.511
AW
DDDDDD
0 ~ 262143
IW
DDD.DD.D
0 ~ 127.15.3
QW
DDD.DD.D
0 ~ 127.15.3
MW
DDDDDD
0 ~ 131071
RW
DDDDD
0 ~ 32767
WW
DDDDD
0 ~ 65535
FW
DDDD
0 ~ 2047
KW
DDDD
0 ~ 8399
LW
DDDDD
0 ~ 11263
NW
DDDDD
0 ~ 25087
UW
DD.DD.DD
0 ~ 31.15.31
DW
MD
DDDDD
0 ~ 65535
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
408
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
May/17/2012
Driver released.
V1.10
Mar/22/2014
V1.30
Sep/18/2014
V1.50
Feb/10/2015
409
LS XGI Cnet
Supported Series: LS XGT series XGI CPU series with communication module XGL-CH2A
Website: http://www.lgis.com/
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
LS XGI Cnet
PLC I/F
RS232
RS232/RS485 4W
Baud rate
115200
9600~115200
Data bits
7, 8
Parity
None
Stop bits
0~32
Device Address:
Bit/Word
Device type
Format
Range
AW_Bit
DDDDDDh
0 ~ 262143f
IW_Bit
DDD.DD.Dh
0 ~ 127.15.3f
QW_Bit
DDD.DD.Dh
0 ~ 127.15.3f
MW_Bit
DDDDDDh
0 ~ 131071f
RW_Bit
DDDDDh
0 ~ 32767f
WW_Bit
DDDDDh
0 ~ 65535f
FW_Bit
DDDDh
0 ~ 2047f
KW_Bit
DDDDh
0 ~ 8399f
LW_Bit
DDDDDh
0 ~ 11263f
NW_Bit
DDDDDh
0 ~ 25087f
UW_Bit
DD.DD.DDh
0 ~ 31.15.31f
AX
DDDDDDD
0 ~ 4194303
IX
DDD.DD.DD
0 ~ 127.15.63
QX
DDD.DD.DD
0 ~ 127.15.63
MX
DDDDDDD
0 ~ 2097151
RX
DDDDDD
0 ~ 524287
WX
DDDDDDD
0 ~ 1048575
FX
DDDDD
0 ~ 32767
410
Memo
Bit/Word
Device type
Format
Range
KX
DDDDDD
0 ~ 134399
LX
DDDDDDD
0 ~ 1880223
NX
DDDDDD
0 ~ 401407
UX
DD.DD.DDD
0 ~ 31.15.511
AW
DDDDDD
0 ~ 262143
IW
DDD.DD.D
0 ~ 127.15.3
QW
DDD.DD.D
0 ~ 127.15.3
MW
DDDDDD
0 ~ 131071
RW
DDDDD
0 ~ 32767
WW
DDDDD
0 ~ 65535
FW
DDDD
0 ~ 2047
KW
DDDD
0 ~ 8399
LW
DDDDD
0 ~ 11263
NW
DDDDD
0 ~ 25087
UW
DD.DD.DD
0 ~ 31.15.31
DW
MD
DDDDD
0 ~ 65535
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
411
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
XGL-CH2A CH2 5P
9P D-Sub Male
Terminal
1 RX-
TXD-
2 RX+
TXD+
3 TX-
RXD-
4 TX+
RXD+
5 GND
GND
412
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
XGL-CH2A CH2 5P
Terminal
7 RX-
TXD-
6 RX+
TXD+
9 TX-
RXD-
8 TX+
RXD+
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
XGL-CH2A CH2 5P
Terminal
1 RX-
1 RX-
TXD-
2 RX+
2 RX+
TXD+
3 TX-
3 TX-
RXD-
4 TX+
4 TX+
RXD+
5 GND
5 GND
GND
XGL-CH2A CH2 5P
9P D-Sub Male
Terminal
1 RX-
TXD-
2 RX+
TXD+
3 TX-
RXD-
4 TX+
RXD+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
XGL-CH2A CH2 5P
9P D-Sub Female
Terminal
1 RX-
TXD-
2 RX+
TXD+
3 TX-
RXD-
4 TX+
RXD+
5 GND
GND
413
Driver Version:
Version
Date
Description
V1.00
May/23/2012
Driver released
V1.20
Sep/18/2014
V1.30
Feb/10/2015
414
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
2004
Notes
Device Address:
Bit/Word
Device type
Format
Range
AW_Bit
DDDDDDh
0 ~ 262143f
IW_Bit
DDD.DD.Dh
0 ~ 127.15.3f
QW_Bit
DDD.DD.Dh
0 ~ 127.15.3f
MW_Bit
DDDDDDh
0 ~ 131071f
RW_Bit
DDDDDh
0 ~ 32767f
WW_Bit
DDDDDh
0 ~ 65535f
FW_Bit
DDDDh
0 ~ 2047f
KW_Bit
DDDDh
0 ~ 8399f
LW_Bit
DDDDDh
0 ~ 11263f
NW_Bit
DDDDDh
0 ~ 25087f
UW_Bit
DD.DD.DDh
0 ~ 31.15.31f
AX
DDDDDDD
0 ~ 4194303
IX
DDD.DD.DD
0 ~ 127.15.63
QX
DDD.DD.DD
0 ~ 127.15.63
MX
DDDDDDD
0 ~ 2097151
RX
DDDDDD
0 ~ 524287
WX
DDDDDDD
0 ~ 1048575
FX
DDDDD
0 ~ 32767
KX
DDDDDD
0 ~ 134399
LX
DDDDDDD
0 ~ 1880223
NX
DDDDDD
0 ~ 401407
UX
DD.DD.DDD
0 ~ 31.15.511
415
Memo
Bit/Word
Device type
Format
Range
AW
DDDDDD
0 ~ 262143
IW
DDD.DD.D
0 ~ 127.15.3
QW
DDD.DD.D
0 ~ 127.15.3
MW
DDDDDD
0 ~ 131071
RW
DDDDD
0 ~ 32767
WW
DDDDD
0 ~ 65535
FW
DDDD
0 ~ 2047
KW
DDDD
0 ~ 8399
LW
DDDDD
0 ~ 11263
NW
DDDDD
0 ~ 25087
UW
DD.DD.DD
0 ~ 31.15.31
DW
MD
DDDDD
0 ~ 65535
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
May/21/2012
Driver released.
Sep/18/2014
V1.20
Feb/10/2015
LS XGK Cnet
Supported Series: LS XGT series XGK CPU with communication module XGL-CH2A
Website: http://www.lgis.com/
HMI Setting:
Parameters
Recommended
Options
PLC type
LS XGK Cnet
PLC I/F
RS232
RS232/RS485 4W
Baud rate
115200
9600~115200
Data bits
7, 8
Parity
None
Stop bits
0~32
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
PW_Bit
DDDDh
0 ~ 2047f
MW_Bit
DDDDh
0 ~ 2047f
LW_Bit
DDDDDh
0 ~ 11263f
KW_Bit
DDDDh
0 ~ 2559f
FW_Bit
DDDDh
0 ~ 2047f
DW_Bit
DDDDDh
0 ~ 32767f
UW_Bit
DH.DDh
0 ~ 3f.31f
XGK-CPUE : hh(0~1f)
SX
DDDDD
0 ~ 12799
TX
DDDD
0 ~ 2047
CX
DDDD
0 ~ 2047
PW
DDDD
0 ~ 2047
I/O device
MW
DDDD
0 ~ 2047
Internal device
LW
DDDDD
0 ~ 11263
Communication device
KW
DDDD
0 ~ 2559
Preservation device
FW
DDDD
0 ~ 2047
DW
DDDDD
0 ~ 32767
Data register
UW
DH.DD
0.00 ~ 3f.31
417
Bit/Word
Device type
Format
Range
Memo
RW
DDDDD
0 ~ 32767
ZRW
DDDDD
0 ~ 32767
NW
DDDDD
0 ~ 21503
ZW
DDD
0 ~ 127
SW
DDDDD
0 ~ 127
TW
DDDD
0 ~ 2047
CW
DDDD
0 ~ 2047
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
418
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
XGL-CH2A CH2 5P
Terminal
1 RX-
TXD-
2 RX+
TXD+
3 TX-
RXD-
4 TX+
RXD+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
XGL-CH2A CH2 5P
Terminal
7 RX-
TXD-
6 RX+
TXD+
9 TX-
RXD-
8 TX+
RXD+
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
XGL-CH2A CH2 5P
Terminal
1 RX-
1 RX-
TXD-
2 RX+
2 RX+
TXD+
3 TX-
3 TX-
RXD-
4 TX+
4 TX+
RXD+
5 GND
5 GND
GND
419
XGL-CH2A CH2 5P
Terminal
1 RX-
TXD-
2 RX+
TXD+
3 TX-
RXD-
4 TX+
RXD+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
XGL-CH2A CH2 5P
Terminal
1 RX-
TXD-
2 RX+
TXD+
3 TX-
RXD-
4 TX+
RXD+
5 GND
GND
Driver Version:
Version
Date
Description
V1.30
Feb /25/2011
V1.40
Jun/20/2012
V1.60
Feb/10/2015
420
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
2004
Notes
Device Address:
Bit/Word
Range
Memo
PW_Bit
DDDDh
0 ~ 2047f
MW_Bit
DDDDh
0 ~ 2047f
LW_Bit
DDDDDh
0 ~ 11263f
KW_Bit
DDDDh
0 ~ 2559f
FW_Bit
DDDDh
0 ~ 2047f
DW_Bit
DDDDDh
0 ~ 32767f
UW_Bit
DH.DDh
0 ~ 3f.31f
XGK-CPUE : hh(0~1f)
SX
DDDDD
0 ~ 12799
TX
DDDD
0 ~ 2047
CX
DDDD
0 ~ 2047
PW
DDDD
0 ~ 2047
I/O device
MW
DDDD
0 ~ 2047
Internal device
LW
DDDDD
0 ~ 11263
Communication device
KW
DDDD
0 ~ 2559
Preservation device
FW
DDDD
0 ~ 2047
SW
DDDDD
0 ~ 127
DW
DDDDD
0 ~ 32767
Data register
UW
DH.DD
0.00 ~ 3f.31
NW
DDDDD
0 ~ 21503
ZW
DDD
0 ~ 127
421
Bit/Word
Range
Memo
TW
DDDD
0 ~ 2047
CW
DDDD
0 ~ 2047
RW
DDDDD
0 ~ 32767
ZRW
DDDDD
0 ~ 32767
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.30
Mar/10/2011
V1.40
Jun/19/2012
V1.50
Feb/10/2015
422
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word
Device Type
Format
Range
Memo
MX_L16bit
DDDDDdd
0 ~ 9999915
MD Low 16bit
MX_H16bit
DDDDDdd
0 ~ 9999915
MD High 16bit
DW
MD
DDDD
0 ~ 9999
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
COM3 RS232 9P
D-Sub Female
D-Sub Female
2 RX
8 RX
6 TX
3 TX
7 TX
5 RX
5 GND
5 GND
11 GND
12 GND
423
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
6 TX
3 TX
5 RX
5 GND
11 GND
12 GND
short
D-Sub Female
2 RX
6 TX
3 TX
5 RX
5 GND
11 GND
12 GND
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
6 TX
3 TX
4 TX
7 TX
5 RX
5 GND
5 GND
5 GND
11 GND
12 GND
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
6 TX
6 TX
5 RX
5 GND
11 GND
12 GND
Driver Version:
Version
Date
V1.00
Jul/1/2008
Description
424
short
Master-Slave Server
For more information, please refer to Users Manual CH28.
HMI Setting:
Parameters
Recommended
Options
PLC type
Master-Slave Server
PLC I/F
RS232
RS232/RS485
Baud rate
115200
9600~115200
Data bits
7,8
Parity
Even
None,Even,Odd,Mark,Space
Stop bits
1,2
Notes
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
115200
Data bits
Parity
Even
Stop bits
Parameter 1
MT500 PLC ID
Notes
38400, 115200
425
PLC Setting:
Communication mode
426
Device Address:
Bit/Word MT500
MT8000
Range
Memo
Ms_RB
RW_Bit
dddd: 0 ~ 4095
(h): 0 ~ f
Ms_LB
LB
dddd:0 ~ 9999
Ms_RW
RW
ddddd:0 ~ 65535
Ms_LW
LW
dddd:0 ~ 9999
Driver Version:
Version
Date
Description
V1.00
Dec/30/2008
Driver released.
427
MEGMEET MC Series
Supported Series: MEGMEET MC Series (Modbus RTU Protocol)
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
MEGMEET MC Series
PLC I/F
RS232
Baud rate
9600
Data bits
7 or 8
Parity
Even
Stop bits
1 or 2
0-255
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
OOO
0 ~ 377
1200~01455 0000~0255
OOO
0 ~ 377
0000~0255
DDDDD
0 ~ 10239
2000~2047 12000~20191
SM
DDD
0 ~ 511
4400~4655 30000~30255
DDDD
0 ~ 4095
6000~7023 31000~34071
T_Bit
DDD
0 ~ 511
8000~8255
C_Bit
DDD
0 ~ 306
9200~9455 10000~10050
D_Bit
DDDDdd
0 ~ 799915
R_Bit
DDDDDdd
0 ~ 3276715
DDDD
0 ~ 7999
0000~7999
DW
D_Double
DDDD
0 ~ 7998
0000~7999
SD
DDD
0 ~ 255
8000~8255 12000~12255
DW
SD_Double
DDD
0 ~ 510
8000~8255 12000~12255
DD
0 ~ 15
8500~8515
DDD
0 ~ 511
9000~9255 11000~11255
428
Format
Range
Memo
DDD
0 ~ 199
9500~9699
DW
C_Double
DDD
200 ~ 306
9700~10101
DDDDD
0 ~ 32767
13000~45767
DW
R_Double
DDDDD
0 ~ 32766
13000~45767
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
MC Series COM1
terminal
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
MC Series COM1
terminal
2 RX
TXD
3 TX
RXD
5 GND
GND
MC Series COM1
terminal
2 RX
TXD
3 TX
RXD
5 GND
GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
429
MC Series COM1
terminal
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
MC Series COM1
terminal
9 RX
TXD
6 TX
RXD
5 GND
GND
Driver Version:
Version
Date
Description
V1.00
Nov/16/2012
Driver released.
V1.10
May/06/2014
V1.20
May/19/2014
430
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS4852W
RS232/RS485
Baud rate
9600
9600~115200
Data bits
7,8
Parity
None
Even,Odd,None
Stop bits
1,2
0~252
Notes
In COM Port Settings, the data read will be stored in 25 consecutive addresses start from
[Data save address (LW)] as shown below. Data will be stored in LW-100 to LW-124.
431
Protocol:
Byte
Description
AA
E0
2
3
C5 (The first 3 bytes are fixed, which represents the start of the
message.)
Addressrange 0-252
10
11
12
Time -Minute
tens digit
13
Time -Minute
unit digit
14
15
16
17
18
19
20
21
00
22
00
23
EE
24
BB(The last 4 bytes are fixed, which represents the end of the
message.)
432
Wiring Diagram:
The following represents the view of HMI & PLC.
[RS232]
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
FeMale
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
RTS
CTS
short
cMT/mTV series
COM1 RS232 9P
RS232 9P D-Sub
D-Sub Female
FeMale
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
RS232 9P D-Sub
FeMale
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
FeMale
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
RTS
CTS
433
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
FeMale
9 RX
TXD
6 TX
RXD
5 GND
GND
RTS
CTS
short
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
434
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Female
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
cMT/mTV series
435
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Female
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
Driver Version:
Version
Date
Description
V1.00
Oct/24/2012
Driver released.
436
Memory Map
Memory Map protocol is similar to IBM 3764R communication protocol. EasyBuilder
reserves 512 words of data memory to use with this protocol. EasyBuilder must update the
values in these words. EasyBuilder uses these words to display data and control parts
status on screen. When touch actions are taken, data is sent to the others once, and then
update the memory in it. The HMI should always update the data memory.
HMI Setting:
Parameters
Recommended Options
PLC type
Memory Map
PLC I/F
RS232
Baud rate
115200
Data bits
Parity
Even
Stop bits
Notes
RS232, RS485
4W, 2W
9600~115200
RS232 default
Device Address:
Bit/Word
Device type
Format
Range
MB
DDDDh
0 ~ 4095f
MW
DDDD
0 ~ 9999
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
437
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
1 RX-
2 RX+
9 Data+
2 RX+
5 GND
5 GND
5 GND
438
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
1 RX-
6 RX+
1 Data+
2 RX+
5 GND
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
1 RX-
2 RX+
8 Data+
2 RX+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
1 RX-
2 RX+
9 Data+
2 RX+
5 GND
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
1 RX-
2 RX+
9 Data+
2 RX+
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
COM3 RS485 2W
9P D-Sub Female
9P D-Sub Female
9P D-Sub Female
1 RX-
7 Data-
1 RX-
2 RX+
8 Data+
2 RX+
5 GND
5 GND
5 GND
439
1 RX-
3 TX-
2 RX+
4 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
5 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
3 TX-
6 RX+
4 TX+
9 TX-
1 RX-
8 TX+
2 RX+
5 GND
5 GND
1 RX-
3 TX-
2 RX+
4 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
5 GND
1 RX-
3 TX-
2 RX+
4 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
5 GND
440
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
3 TX-
2 RX+
4 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
5 GND
Note:
For Memory map information, please refer to Users Manual Chapter 31 Memory Map
Communication.
Driver Version:
Version
Date
Description
V1.00
Mar/19/2009
Driver released.
441
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS232
RS232/485/Ethernet
Baud rate
19200
9600~115200
Data bits
Even
None,Even,Odd
Parity
Stop bits
1,2
0~31
Online simulator
Options
YES
PLC Setting:
PORT 0(RS232 Setting)
442
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDD
0~777
Output Relay
DDD
0~777
Input Relay
DDDD
0~4095
Auxiliary Relay
SM
DDD
0-511
DDDD
0~1535
Step Relay
DDD
0~511
Timer Relay
DDD
0~511
Counter Relay
DDDDD
0~32767
Data Register
SD
DDD
0~511
DDD
0~255
DDD
0~511
Timer
DDD
0~199
Counter
U0
DDD
0~199
U1
DDD
0~199
U2
DDD
0~199
U3
DDD
0~199
U4
DDD
0~199
U5
DDD
0~199
U6
DDD
0~199
U7
DDD
0~199
DW
C-32bit
DDD
200~511
32 Bit Counter
443
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
RS232 8P Mini-DIN
Male
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 8P Mini-DIN
Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
View from the
soldering point
of a cable.
444
Driver Version:
Version
Date
Description
V1.00
May/3/2012
Driver released.
445
Mitsubishi A1S/A2N
Supported Series: Mitsubishi A1S/A2N
Website: http://www.mitsubishi-automation.com/
HMI Setting:
Parameters
Recommended
PLC type
Mitsubishi A1S/A2N
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
Odd
Stop bits
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
HHHH
0 ~ ffff
Input Relay
HHHH
0 ~ ffff
Output Relay
DDDDD
0 ~ 65535
Auxiliary Relay
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
TV
DDDDD
0 ~ 65535
Timer Memory
CV
DDDDD
0 ~ 65535
Counter Memory
DDDDD
0 ~ 65535
Data Register
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
446
Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
MITSUBISHI AnS CPU
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
447
17 DSR-
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
17 DSR-
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
Driver Version:
Version
Date
Description
V1.00
Sep/18/2009
Driver released.
448
17 DSR-
Mitsubishi A2A/A2U/A2AS/A2USH
Supported Series: Mitsubishi A2A,A2U,A2AS,A2USH
Website: http://www.mitsubishi-automation.com/
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
Mitsubishi A2A/A2U/A2AS/A2USH
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
Odd
Stop bits
Parameter 1
0~8
Parameter 2
0~1
Device Address:
Bit/Word
Device type
Format
Range
Memo
HHHH
0 ~ 270f
Input Relay
HHHH
0 ~ 270f
Output Relay
DDDD
0 ~ 9999
Auxiliary Relay
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
TV
DDD
0 ~ 255
Timer Memory
CV
DDD
0 ~ 255
Counter Memory
DDDD
0 ~ 9999
Data Register
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
449
Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
MITSUBISHI AnS CPU
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
450
17 DSR-
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
17 DSR-
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
Driver Version:
Version
Date
Description
V1.00
Aug/12/2009
Driver released.
451
17 DSR-
Mitsubishi A2US
Supported Series: Mitsubishi A2US
Website: http://www.mitsubishi-automation.com/
HMI Setting:
Parameters
Recommended
PLC type
Mitsubishi A2US
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
Odd
Stop bits
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
HHHH
0 ~ 270f
Input Relay
HHHH
0 ~ 270f
Output Relay
DDDD
0 ~ 9999
Auxiliary Relay
TV
DDD
0 ~ 255
Timer Memory
CV
DDD
0 ~ 255
Counter Memory
DDDD
0 ~ 9999
Data Register
452
Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
MITSUBISHI AnS CPU
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
453
17 DSR-
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
17 DSR-
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
Driver Version:
Version
Date
Description
V1.00
Mar/20/2009
Driver released.
454
17 DSR-
Mitsubishi A3A/A3N/A1SH/A2SH
Supported Series: Mitsubishi A3A,A3N,A1SH,A2SH
Website: http://www.mitsubishi-automation.com/
HMI Setting:
Parameters
Recommended
Options
PLC type
Mitsubishi A3A/A3N/A1SH/A2SH
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
Odd
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
HHHH
0 ~ ffff
Input Relay
HHHH
0 ~ ffff
Output Relay
DDDDD
0 ~ 65535
Auxiliary Relay
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
TV
DDDDD
0 ~ 65535
Timer Memory
CV
DDDDD
0 ~ 65535
Counter Memory
DDDDD
0 ~ 65535
Data Register
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
455
Wiring Diagram:
Use the RS422 to RS232 PLC programming cable (shown as follows)
MITSUBISHI AnS CPU
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
456
17 DSR-
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
17 DSR-
2 RX
TX
TX+
2 RX+
3 TX
RX
RX+
3 TX+
5 GND
GND
DTR+
4 DSR+
7 RTS
CTS
GND
7 GND
8 CTS
RTS
TX-
15 RX-
RX-
16 TX-
DTR-
Driver Version:
Version
Date
Description
V1.00
Oct/20/2009
Driver released.
457
17 DSR-
Mitsubishi AJ71
Supported Series: Mitsubishi A series PLC with AJ71C24 communication module using
the Computer Link protocol.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
Mitsubishi AJ71
PLC I/F
RS485 4W
Baud rate
19200
9600, 19200
Data bits
Parity
Even
Stop bits
PLC Setting:
Communication mode
Format 1
Parity check
Enable
Sum check
Enable
Device Address:
Bit/Word
Device type
Format
Range
Memo
HHHH
0 ~ ffff
Input Bits
HHHH
0 ~ ffff
Output Bits
DDDDD
0 ~ 65535
Internal Relays
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
458
Bit/Word
Device type
Format
Range
Memo
TV
DDDDD
0 ~ 65535
CV
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
Data Registers
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
Wiring Diagram:
The following is the view from the soldering point of a cable.
AJ71C24 RS422
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
AJ71C24 RS422
Terminal
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
AJ71C24 RS422
Terminal
7 RX-
SDB
6 RX+
SDA
9 TX-
RDB
8 TX+
RDA
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
AJ71C24 RS422
Terminal
1 RX-
1 RX-
SDB
2 RX+
2 RX+
SDA
3 TX-
3 TX-
RDB
4 TX+
4 TX+
RDA
5 GND
5 GND
GND
459
AJ71C24 RS422
Terminal
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
AJ71C24 RS422
Terminal
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
460
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
461
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
Driver Version:
Version
Date
V1.60
Nov/30/2012
Description
462
short
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485 4W
Baud rate
19200
9600, 19200
Data bits
Parity
Even
Stop bits
Notes
PLC Setting:
Communication mode
Format 1
Parity check
Enable
Sum check
Enable
Device Address:
Bit/Word
Device type
Format
Range
Memo
HHHH
0 ~ ffff
Input Bits
HHHH
0 ~ ffff
Output Bits
DDDDD
0 ~ 65535
Internal Relays
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
TV
DDDDD
0 ~ 65535
CV
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
Data Registers
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
463
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
RS422 Terminal
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS422 Terminal
7 RX-
SDB
6 RX+
SDA
9 TX-
RDB
8 TX+
RDA
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
RS422 Terminal
1 RX-
1 RX-
SDB
2 RX+
2 RX+
SDA
3 TX-
3 TX-
RDB
4 TX+
4 TX+
RDA
5 GND
5 GND
GND
RS422 Terminal
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
GND
464
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS422 Terminal
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
465
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
466
short
Driver Version:
Version
Date
Description
V1.00
Oct/31/2011
Driver released.
467
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
RS485 4W
Baud rate
19200
9600, 19200
Data bits
Parity
Even
Stop bits
PLC Setting:
Communication mode
Format 4
Parity check
Enable
Sum check
Enable
Device Address:
Bit/Word
Device type
Format
Range
Memo
HHHH
0 ~ ffff
Input Bits
HHHH
0 ~ ffff
Output Bits
DDDDD
0 ~ 65535
Internal Relays
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
TV
DDDDD
0 ~ 65535
CV
DDDDD
0 ~ 65535
DDDDD
0 ~ 65535
Data Registers
HHHH
0 ~ ffff
DDDDD
0 ~ 65535
468
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
AJ71C24 RS422
Terminal
1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series
SDB
SDA
RDB
RDA
GND
COM2 RS485 4W
9P D-Sub Female
AJ71C24 RS422
Terminal
7 RX-
SDB
6 RX+
SDA
9 TX-
RDB
8 TX+
RDA
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
AJ71C24 RS422
Terminal
1 RX-
1 RX-
SDB
2 RX+
2 RX+
SDA
3 TX-
3 TX-
RDB
4 TX+
4 TX+
RDA
5 GND
5 GND
GND
AJ71C24 RS422
Terminal
1 RX2 RX+
3 TX4 TX+
5 GND
SDB
SDA
RDB
RDA
GND
469
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
AJ71C24 RS422
Terminal
1 RX2 RX+
3 TX4 TX+
5 GND
SDB
SDA
RDB
RDA
GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
470
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
471
short
Driver Version:
Version
Date
V1.00
Mar/08/2010
Description
472
HMI Setting:
Parameters
Recommended
Options
PLC type
F930GOT Server
PLC I/F
RS232
Baud rate
38400
9600, 115200
Data bits
7 or 8
Parity
None
Stop bits
1 or 2
Notes
Device Address:
Bit/Word
Device type
Format
Range
RB
DDDD
0 ~ 2047
RW
DDDDD
0 ~ 65535
Memo
Note: In PLC name drop - down menu dont select F930GOT Server.
Please select Local HMI, Device Type=RW.
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TD
3 TX
7 TX
2 RD
5 GND
5 GND
5 GND
473
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TD
3 TX
4 TX
7 TX
2 RD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TD
6 TX
2 RD
5 GND
5 GND
474
Protocol:
Read Command:
PC HMI
Read address
02 0
Size
CR
02 30 30 30 30 30 30 32 0D
Read RW0 1 word (2 bytes) STX = 0x02, 0 = Read command, CR = 0x0D
Read address (hexadecimal)
0 ~ FFFF = RW0 ~ 65535
Size (hexadecimal)
2 ~ FE = 2 ~ 254 bytes = 1 ~ 127 word.
Size must be even.
HMI PC (response)
Data1 Data2 . CR
02
02 30 30 31 30 0D
RW0 = 0x0010 = 16
Write Command:
PC HMI
Read address
02 1
Size
Data1
Data2
CR
.
02 31 30 30 30 30 30 32 12
34 0D
Driver Version:
Version
Date
Description
V1.00
Aug/14/2009
Driver released.
475
Mitsubishi FX0S/FX0N/FX1S/FX1N/FX2
Supported Series: Mitsubishi FX0S/FX0N/FX1S/FX1N/FX2/FX3S
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
Options
PLC type
Mitsubishi FX0S/FX0N/FX1S/FX1N/FX2
PLC I/F
RS485 4W
RS232/RS485
Baud rate
9600
9600/19200/38400/57600/115200
Data bits
7,8
Parity
Even
Stop bits
1,2
0-255
Notes
476
Device Address:
Bit/Word
Device type
Format
Range
Memo
OOO
0 ~ 377
Input Relay
OOO
0 ~ 377
Output Relay
DDDD
0 ~ 9999
Auxiliary Relay
DDD
0 ~ 255
Timer Relay
DDD
0 ~ 255
Counter Relay
SM
DDDD
8000 ~ 9999
D_Bit
DDDDdd
0 ~ 999915
DDDD
0 ~ 4095
States
TV
DDD
0 ~ 255
Timer Memory
CV
DDD
0 ~ 199
Counter Memory
DDDD
0 ~ 9999
Data Register
DW
CV2
DDD
200 ~ 255
SD
DDDD
8000 ~ 9999
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
RS422 Port 8P
Mini-DIN Male
1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series
4 TX7 TX+
1 RX2 RX+
3 GND
COM2 RS485 4W
9P D-Sub Female
RS422 Port 8P
Mini-DIN Male
7 RX-
4 TX-
6 RX+
7 TX+
9 TX-
1 RX-
8 TX+
2 RX+
5 GND
3 GND
477
COM2 RS485 4W
9P D-Sub Male
RS422 Port 8P
Mini-DIN Male
1 RX-
1 RX-
4 TX-
2 RX+
2 RX+
7 TX+
3 TX-
3 TX-
1 RX-
4 TX+
4 TX+
2 RX+
5 GND
5 GND
3 GND
RS422 Port 8P
Mini-DIN Male
1 RX2 RX+
3 TX4 TX+
5 GND
MT6050i/MT8050i/MT8050iE
4 TX7 TX+
1 RX2 RX+
3 GND
COM1 RS485 4W
RS422 Port 8P
9P D-Sub Female
Mini-DIN Male
1 RX2 RX+
3 TX4 TX+
5 GND
4 TX7 TX+
1 RX2 RX+
3 GND
View from the
soldering point
of a cable.
478
1 RX-
16 TXD-
2 RX+
3 TXD+
3 TX-
15 RXD-
4 TX+
2 RXD+
5 GND
7 GND
4 DSR+
Short
8 GND
13 +5V
17 DSR-
Short
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
16 TXD-
6 RX+
3 TXD+
9 TX-
15 RXD-
8 TX+
2 RXD+
5 GND
7 GND
4 DSR+
Short
8 GND
13 +5V
17 DSR-
Short
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
16 TXD-
2 RX+
2 RX+
3 TXD+
3 TX-
3 TX-
15 RXD-
4 TX+
4 TX+
2 RXD+
5 GND
5 GND
7 GND
4 DSR+
Short
8 GND
13 +5V
17 DSR479
Short
1 RX-
16 TXD-
2 RX+
3 TXD+
3 TX-
15 RXD-
4 TX+
2 RXD+
5 GND
7 GND
4 DSR+
short
8 GND
13 +5V
17 DSR-
short
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
16 TXD-
2 RX+
3 TXD+
3 TX-
15 RXD-
4 TX+
2 RXD+
5 GND
7 GND
4 DSR+
short
8 GND
13 +5V
17 DSR-
Driver Version:
Version
Date
V1.20
Oct/26/2011
Description
480
short
Mitsubishi FX232/485BD
Supported Series: Mitsubishi FX0N/FX2/FX2N COM for Communication Module BD
FX2N-485-BD, FX2N-232-BD, FX1N-485-BD, FX1N-232-BD & FX3U-485ADP.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
Mitsubishi FX232/485BD
PLC I/F
RS232/RS485
RS232/RS485 2w/4w
Baud rate
19200
9600/19200/38400
Data bits
7,8
Parity
Even
Stop bits
1,2
0-15
PLC Setting:
Communication mode
FX2N-485-BD, FX1N-485-BD
FX2N-232-BD, FX1N-232-BD
481
Device Address:
Bit/Word Device type
Format
Range
Memo
OOO
0 ~ 377
Input Relay
OOO
0 ~ 377
Output Relay
DDDD
0 ~ 7999
Auxiliary Relay
DDD
0 ~ 511
Timer Relay
DDD
0 ~ 255
Counter Relay
SM
DDDD
8000 ~ 9999
D_Bit
DDDDh
0 ~ 7999f
DDDD
0 ~ 4095
State Relay
TV
DDD
0 ~ 511
Timer Memory
CV
DDD
0 ~ 199
Counter Memory
DDDD
0 ~ 7999
Data Register
CV2
DDD
200 ~ 255
SD
DDDD
8000 ~ 9999
DDDDD 0 ~ 32767
Extended Register
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub: Communication Module RS232BD
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
482
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
485BD Module 5P
9P D-Sub Male
Termanal
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
SG
483
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
485BD Module 5P
Termanal
7 RX-
SDB
6 RX+
SDA
9 TX-
RDB
8 TX+
RDA
5 GND
SG
COM2 RS485 4W
9P D-Sub Male
485BD Module 5P
Termanal
1 RX-
1 RX-
SDB
2 RX+
2 RX+
SDA
3 TX-
3 TX-
RDB
4 TX+
4 TX+
RDA
5 GND
5 GND
SG
485BD Module 5P
9P D-Sub Male
Termanal
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
SG
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
485BD Module 5P
9P D-Sub Female
Termanal
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
SG
484
COM3 RS485 2W
9P D-Sub Male
485BD Module 5P
Termanal
1 RX-
6 Data-
SDB
RDB
2 RX+
9 Data+
SDA
RDA
5 GND
short
short
5 GND
SG
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
SDB
cMT/mTV series
RDB
6 RX+
1 Data+
SDA
RDA
5 GND
5 GND
short
short
SG
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
SDB
RDB
2 RX+
8 Data+
SDA
RDA
5 GND
9 GND
short
short
SG
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
SDB
RDB
2 RX+
9 Data+
SDA
RDA
5 GND
5 GND
SG
485
short
short
COM3 RS485 2W
9P D-Sub Male
485BD Module 5P
Termanal
1 RX-
6 Data-
SDB
RDB
2 RX+
9 Data+
SDA
RDA
5 GND
5 GND
short
short
SG
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
485BD Module 5P
Termanal
1 RX-
7 Data-
SDB
RDB
2 RX+
8 Data+
SDA
RDA
5 GND
5 GND
SG
Driver Version:
Version
Date
Description
V1.40
Jul/26/2011
V1.50
Sep/10/2012
Added register: R.
486
short
short
Mitsubishi FX2N
Supported Series: Mitsubishi FX2N series PLC
Website http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
PLC type
Mitsubishi FX2N
PLC I/F
RS485 4W
RS232/RS485
Baud rate
19200
9600/19200/38400
/57600/115200
Data bits
Parity
Even
Stop bits
Online simulator
Options
YES
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
OOO
0 ~ 377
Input Relay
OOO
0 ~ 377
Output Relay
DDDD
0 ~ 7999
Auxiliary Relay
DDD
0 ~ 255
Timer Relay
DDD
0 ~ 255
Counter Relay
SM
DDDD
D_Bit
DDDDdd
0 ~ 799915
DDDD
0 ~ 4095
TV
DDD
0 ~ 255
Timer Memory
CV
DDD
0 ~ 199
Counter Memory
DDDD
0 ~ 7999
Data Register
DW
CV2
DDD
200 ~ 255
SD
DDDD
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
RS422 Port 8P
Mini-DIN Male
1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series
4 TX7 TX+
1 RX2 RX+
3 GND
COM2 RS485 4W
9P D-Sub Female
RS422 Port 8P
Mini-DIN Male
7 RX-
4 TX-
6 RX+
7 TX+
9 TX-
1 RX-
8 TX+
2 RX+
5 GND
3 GND
COM2 RS485 4W
9P D-Sub Male
RS422 Port 8P
Mini-DIN Male
1 RX-
1 RX-
4 TX-
2 RX+
2 RX+
7 TX+
3 TX-
3 TX-
1 RX-
4 TX+
4 TX+
2 RX+
5 GND
5 GND
3 GND
RS422 Port 8P
Mini-DIN Male
1 RX2 RX+
3 TX4 TX+
5 GND
4 TX7 TX+
1 RX2 RX+
3 GND
488
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS422 Port 8P
Mini-DIN Male
1 RX2 RX+
3 TX4 TX+
5 GND
4 TX7 TX+
1 RX2 RX+
3 GND
View from the
soldering point
of a cable.
Driver Version:
Version
Date
V1.60
Sep/10/2009
Description
489
Mitsubishi FX2N-10GM/20GM
Supported Series: Mitsubishi FX2N -10GM/20GM PLC.
Website http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
PLC type
Mitsubishi FX2N-10GM/20GM
PLC I/F
RS485 4W
Baud rate
9600
Data bits
Parity
Even
Stop bits
Online simulator
YES
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
OOO
0 ~ 103
Input Relay
OOO
0 ~ 103
Output Relay
DDD
0 ~ 511
Auxiliary Relay
SM
DDDD
9000 ~ 9175
X_W
OOO
0 ~ 103
Y_W
OOO
0 ~ 103
M_W
DDD
0 ~ 511
SM_W
DDDD
9000 ~ 9175
DDDD
0 ~ 6999
Data Register
SD
DDDD
9000 ~ 9599
0~7
Index register
DW
0~7
Index register
490
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
RS422 Port 8P
Mini-DIN Male
1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series
4 TX7 TX+
1 RX2 RX+
3 GND
COM2 RS485 4W
9P D-Sub Female
RS422 Port 8P
Mini-DIN Male
7 RX-
4 TX-
6 RX+
7 TX+
9 TX-
1 RX-
8 TX+
2 RX+
5 GND
3 GND
COM2 RS485 4W
9P D-Sub Male
RS422 Port 8P
Mini-DIN Male
1 RX-
1 RX-
4 TX-
2 RX+
2 RX+
7 TX+
3 TX-
3 TX-
1 RX-
4 TX+
4 TX+
2 RX+
5 GND
5 GND
3 GND
RS422 Port 8P
Mini-DIN Male
1 RX2 RX+
3 TX4 TX+
5 GND
4 TX7 TX+
1 RX2 RX+
3 GND
491
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS422 Port 8P
Mini-DIN Male
1 RX2 RX+
3 TX4 TX+
5 GND
4 TX7 TX+
1 RX2 RX+
3 GND
View from the
soldering point
of a cable.
Driver Version:
Version
Date
Description
V1.00
May/30/2013
Driver released.
492
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
Ethernet
Port no.
5001(default)
0 (default)
PLC Setting:
Fx3u-ENET module setting:
Before using Ethernet module, use GX Developer / FX Configurator-EN to set the Ethernet
module, the FX3u-ENET module setting steps are shown below.
Step1. Open GX Developer, select Read from PLC in Online list.
493
Step3. Connect PLC via serial port for setting IP address first.
494
Step4. After finishing the PLC settings, select Tools/FX special function utility/FX
Configurator-EN.
495
Step6. In Ethernet operational settings, select the related parameters and IP address and
then press End to finish setting.
Step7. In Ethernet open settings, press End after setting the parameters below.
(The first Protocol means using GX Developer to communicate with module, the max.
Fixed buffer communication preocedure is 4 units.)
496
Or
497
Step8. After setting the parameters of PLC, restart for Ethernet communication.
Device Address:
Bit/Word
Device type
Format
Range
Memo
OOO
0 ~ 571
Input
OOO
0 ~ 571
Output Relay
DDDD
0 ~ 7999
Internal Relay
DDD
0 ~ 511
Timer Contacts
DDD
0 ~ 255
Counter Contacts
SM
DDDD
8000 ~ 8511
D_Bit
DDDDDdd
0 ~ 1799915
DDDD
0 ~ 4095
Step Relays
TV
DDD
0 ~ 511
Timer Value
CV
DDD
0 ~ 199
Counter Value
DDDD
0 ~ 7999
Data Registers
CV2
DDD
200 ~255
Counter Value
SD
DDDD
8000 ~ 8511
DDDDD
0 ~ 32767
File Register
498
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Feb/12/2009
Driver released.
499
Mitsubishi FX3U/FX3G
Supported Series: Mitsubishi FX3U/FX3UC/FX3G/FX3S.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
PLC type
Mitsubishi FX3U/FX3G
PLC I/F
RS485 4w
Baud rate
38400
Data bits
Parity
Even
Stop bits
Online simulator
Options
Notes
RS232 / RS485
2w/4w / USB
9600/19200
Device Address:
Bit/Word Device type
Format
Range
Memo
OOO
0 ~ 764
Input Relay
OOO
0 ~ 764
Output Relay
DDDD
0 ~ 7999
Auxiliary Relay
DDD
0 ~ 511
DDD
0 ~ 255
SM
DDDD
8000 ~ 9999
D_Bit
DDDDdd
0 ~ 799915
DDDD
0 ~ 4095
TV
DDD
0 ~ 511
CV
DDD
0 ~ 199
DDDD
0 ~ 7999
DW
CV2
DDD
200 ~ 255
SD
DDDD
8000 ~ 9999
DDDDD
0 ~ 32767
0~7
Index register
500
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
RS422 Port 8P
Mini-DIN Male
1 RX-
4 TX-
2 RX+
7 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
3 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS422 Port 8P
Mini-DIN Male
7 RX-
4 TX-
6 RX+
7 TX+
9 TX-
1 RX-
8 TX+
2 RX+
5 GND
3 GND
COM2 RS485 4W
9P D-Sub Male
RS422 Port 8P
Mini-DIN Male
1 RX-
1 RX-
4 TX-
2 RX+
2 RX+
7 TX+
3 TX-
3 TX-
1 RX-
4 TX+
4 TX+
2 RX+
5 GND
5 GND
3 GND
RS422 Port 8P
Mini-DIN Male
1 RX-
4 TX-
2 RX+
7 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
3 GND
501
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS422 Port 8P
Mini-DIN Male
1 RX-
4 TX-
2 RX+
7 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
3 GND
View from the
soldering point
of a cable.
Driver Version:
Version
Date
V1.80
Feb/18/2014
Description
502
Mitsubishi FX5U
Supported Series: Mitsubishi FX5U/FX5UC
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
Options
PLC type
Mitsubishi FX5U
PLC I/F
RS485 4w
Baud rate
19200
9600 ~ 115200
Data bits
7,8
Parity
None
None/Odd/Even
Stop bits
1,2
0 ~ 15
Parameter 1
1,4,5
Notes
*Note1:
Pattern1 = ASCII Mode
Pattern4 = ASCII Mode (CR,LF)
Pattern5 = Binary Mode
Online simulator
YES
503
NO
PLC Setting:
Communication Protocol Type MC Protocol
Sum Check Code
Added
Device Address:
Bit/Word Device type
Format
Range
Memo
LCS
DD
0 ~ 63
LCC
DD
0 ~ 63
SM
DDDD
0 ~ 9999
Special Relay
OOOO
0 ~ 1777
Input Relay
OOOO
0 ~ 1777
Output Relay
DDDD
0 ~ 7679
Internal Relay
DDDD
0 ~ 7679
Latch Relay
DDD
0 ~ 127
Annunciator
HH
0 ~ ff
Link Relay
TS
DDD
0 ~ 511
Timer Contact
TC
DDD
0 ~ 511
Timer Coil
SS
DD
0 ~ 15
SC
DD
0 ~ 15
CS
DDD
0 ~ 255
Counter Contact
504
Format
Range
Memo
CC
DDD
0 ~ 255
Counter Coil
SB
HH
0 ~ ff
DDDD
0 ~ 4095
Step relay
D_Bit
DDDDh
0 ~ 7999f
SD_bit
DDDDDh
0 ~ 11999f
R_bit
DDDDDh
0 ~ 32767f
SW_bit
HHHh
0 ~ 1fff
W_bit
HHHh
0 ~ 1fff
DW
LCN
DD
0 ~ 63
DW
LZ
0~1
SD
DDDDD
0 ~ 11999
Special register
DDDD
0 ~ 7999
Data Register
DDDDD
0 ~ 32767
File Register
HHH
0 ~ 1ff
Link Register
TN
DDD
0 ~ 511
SN
DD
0 ~ 15
CN
DDD
0 ~ 255
SW
HHH
0 ~ 1ff
DD
0 ~ 19
Index Register
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
SG
505
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
SDB
6 RX+
SDA
9 TX-
RDB
8 TX+
RDA
5 GND
SG
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
SDB
2 RX+
2 RX+
SDA
3 TX-
3 TX-
RDB
4 TX+
4 TX+
RDA
5 GND
5 GND
SG
9P D-Sub Male
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
SG
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
SDB
2 RX+
SDA
3 TX-
RDB
4 TX+
RDA
5 GND
SG
506
Driver Version:
Version
Date
Description
V1.80
Aug/17/2015
Driver released.
507
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
Notes
PLC Setting:
Communication Data Code
ASCII
[Ethernet Configuration]
To connect PLC with multiple HMIs, Port No. must be set.
In GX WORK 3, the setting steps are: Project -> Parameter -> FX5UCPU -> Module
Parameter -> Ethernet Port -> Setting Item -> External Device Configuration -> Detailed
Setting
508
Device Address:
Bit/Word
Device type
Format
Range
Memo
SM
DDDD
0 ~ 9999
Special Relay
OOOO
0 ~ 1777
Input Relay
OOOO
0 ~ 1777
Output Relay
DDDD
0 ~ 7679
Internal Relay
DDDD
0 ~ 7679
Latch Relay
DDD
0 ~ 127
Annunciator
HH
0 ~ ff
Link Relay
TS
DDD
0 ~ 511
Timer Contact
TC
DDD
0 ~ 511
Timer Coil
SS
DD
0 ~ 15
SC
DD
0 ~ 15
CS
DDD
0 ~ 255
Counter Contact
CC
DDD
0 ~ 255
Counter Coil
SB
HH
0 ~ ff
DDDD
0 ~ 4095
Step relay
D_Bit
DDDDh
0 ~ 7999f
SD_bit
DDDDDh
0 ~ 11999f
R_bit
DDDDDh
0 ~ 32767f
SW_bit
HHHh
0 ~ 1fff
W_bit
HHHh
0 ~ 1fff
DW
LZ
0~1
SD
DDDDD
0 ~ 11999
Special register
DDDD
0 ~ 7999
Data Register
DDDDD
0 ~ 32767
File Register
HHH
0 ~ 1ff
Link Register
TN
DDD
0 ~ 511
SN
DD
0 ~ 15
CN
DDD
0 ~ 255
SW
HHH
0 ~ 1ff
DD
0 ~ 19
Index Register
509
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Feb/22/2016
Driver released.
510
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
Notes
PLC Setting:
Communication Data Code
Binary
[Ethernet Configuration]
To connect PLC with multiple HMIs, Port No. must be set.
In GX WORK 3, the setting steps are: Project -> Parameter -> FX5UCPU -> Module
Parameter -> Ethernet Port -> Setting Item -> External Device Configuration -> Detailed
Setting
511
Device Address:
Bit/Word
Device type
Format
Range
Memo
LCS
DD
0 ~ 63
LCC
DD
0 ~ 63
SM
DDDD
0 ~ 9999
Special Relay
OOOO
0 ~ 1777
Input Relay
OOOO
0 ~ 1777
Output Relay
DDDD
0 ~ 7679
Internal Relay
DDDD
0 ~ 7679
Latch Relay
DDD
0 ~ 127
Annunciator
HH
0 ~ ff
Link Relay
TS
DDD
0 ~ 511
Timer Contact
TC
DDD
0 ~ 511
Timer Coil
SS
DD
0 ~ 15
SC
DD
0 ~ 15
CS
DDD
0 ~ 255
Counter Contact
CC
DDD
0 ~ 255
Counter Coil
SB
HH
0 ~ ff
DDDD
0 ~ 4095
Step relay
D_Bit
DDDDh
0 ~ 7999f
SD_bit
DDDDDh
0 ~ 11999f
R_bit
DDDDDh
0 ~ 32767f
SW_bit
HHHh
0 ~ 1fff
W_bit
HHHh
0 ~ 1fff
DW
LCN
DD
0 ~ 63
DW
LZ
0~1
SD
DDDDD
0 ~ 11999
Special register
DDDD
0 ~ 7999
Data Register
DDDDD
0 ~ 32767
File Register
HHH
0 ~ 1ff
Link Register
TN
DDD
0 ~ 511
SN
DD
0 ~ 15
CN
DDD
0 ~ 255
SW
HHH
0 ~ 1ff
DD
0 ~ 19
Index Register
512
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Jul/15/2015
Driver released.
513
Mitsubishi L6ADP
Supported Series: Mitsubishi L6ADP CPU RS232 Series Port
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
PLC type
Mitsubishi L6ADP
PLC I/F
RS232
Baud rate
115200
Data bits
Parity
Odd
Stop bits
Online simulator
YES
Pass-Through
YES
Options
Extend address
mode
Notes
NO
*Communications between HMI and PLC in pass-through mode are not supported.
*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode
Device Address:
Bit/Word Device type
Format
Range
Memo
SM
DDDD
0 ~ 2047
HHHH
0 ~ 1FFF
Input Relay
HHHH
0 ~ 1FFF
Output Relay
DDDD
0 ~ 8191
Internal Relay
DDDD
0 ~ 8191
Latch Relay
DDDD
0 ~ 2047
Annunciator
DDDD
0 ~ 2047
Edge Relay
HHHH
0 ~ 1FFF
Link Relay
SB
HHH
0 ~ 7FF
D_Bit
DDDDDDh
0 ~ 143359F
SD
DDDD
0 ~ 2047
Special register
DDDDDD
0 ~ 143359
Data Register
HHHH
0 ~ 1FFF
Link Register
SW
HHH
0 ~ 7FF
514
Format
Range
Memo
DD
0 ~ 19
Index Register
DDDD
0 ~ 2047
Counter
DDDD
0 ~ 1023
Timer
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P Mini-DIN RS232 Port
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male socket
2 RX
8 RX
3 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male socket
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
RS232 6P Mini-DIN
Male socket
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 6P Mini-DIN
Male socket
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
5 GND
515
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male socket
9 RX
3 TXD
6 TX
4 RXD
5 GND
5 GND
View from the
soldering point
of a cable.
Driver Version:
Version
Date
Description
V1.00
Nov/19/2013
Driver released.
516
HMI Setting:
Parameters
PLC type
PLC I/F
Recommended
Options
Notes
Port no.
Parameter 1
0~255
255
PLC Setting:
MITSUBISHI Q/L series Ethernet module setting:
Note: If using QJ71E71 module, please refer to MITSUBISHI QJ71E71 connection guide.
517
518
519
Device Address:
Bit/Word
Device type
Format
Range
Memo
SM
DDDD
0 ~ 2047
Special Relay
HHHH
0 ~ 1fff
Input Relay
HHHH
0 ~ 1fff
Output Relay
DDDDD
0 ~ 61439
Internal Relay
DDDDD
0 ~ 32767
Latch Relay
DDDDD
0 ~ 32767
Annunciator
DDDDD
0 ~ 32767
Edge Relay
HHHH
0 ~ efff
Link Relay
TS
DDDDD
0 ~ 25471
Timer Contact
TC
DDDDD
0 ~ 25471
Timer Coil
SS
DDDDD
0 ~ 25471
SC
DDDDD
0 ~ 25471
CS
DDDDD
0 ~ 25471
Counter Contact
CC
DDDDD
0 ~ 25471
Counter Coil
SB
HHHH
0 ~ 7fff
DDDD
0 ~ 8191
Step relay
DX
HHHH
0 ~ 1fff
Direct Input
DY
HHHH
0 ~ 1fff
Direct Output
D_Bit
DDDDDDh
0 ~ 999999f
SD_bit
DDDDh
0 ~ 2047f
ZR_bit
DDDDDDh
0 ~ 999999f
R_bit
DDDDDh
0 ~ 32767f
SW_bit
HHHh
0 ~ 7fff
W_bit
HHHHHHh
0 ~ 3fd7fff
SD
DDDD
0 ~ 2047
Special register
DDDDDD
0 ~ 999999
Data Register
HHHHHH
0 ~ 3fd7ff
Link Register
TN
DDDDD
0 ~ 25471
SN
DDDDD
0 ~ 25471
CN
DDDDD
0 ~ 25471
SW
HHH
0 ~ 7ff
DD
0 ~ 20
Index Register
DDDDD
0 ~ 32767
File Register
ZR
DDDDDD
0 ~ 999999
File Register
520
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Jul/10/2012
Driver released.
521
HMI Setting:
Parameters
PLC type
PLC I/F
Recommended
Options
Notes
Port no.
Parameter 1
0~255
255
PLC Setting:
MITSUBISHI Q/L series Ethernet module setting:
Note: If using QJ71E71 module, please refer to MITSUBISHI QJ71E71 connection guide.
522
1.
2.
3.
4.
523
Device Address:
Bit/Word
Device type
Format
Range
Memo
SM
DDDD
0 ~ 2047
Special Relay
HHHH
0 ~ 1fff
Input Relay
HHHH
0 ~ 1fff
Output Relay
DDDDD
0 ~ 61439
Internal Relay
DDDDD
0 ~ 32767
Latch Relay
DDDDD
0 ~ 32767
Annunciator
DDDDD
0 ~ 32767
Edge Relay
HHHH
0 ~ efff
Link Relay
TS
DDDDD
0 ~ 25471
Timer Contact
TC
DDDDD
0 ~ 25471
Timer Coil
SS
DDDDD
0 ~ 25471
SC
DDDDD
0 ~ 25471
CS
DDDDD
0 ~ 25471
Counter Contact
CC
DDDDD
0 ~ 25471
Counter Coil
SB
HHHH
0 ~ 7fff
DDDD
0 ~ 8191
Step relay
DX
HHHH
0 ~ 1fff
Direct Input
DY
HHHH
0 ~ 1fff
Direct Output
D_Bit
DDDDDDDh 0 ~ 4184063f
SD_bit
DDDDh
0 ~ 2047f
ZR_bit
HHHHHHh
0 ~ 3fd7fff
524
Bit/Word
Device type
Format
Range
Memo
R_bit
DDDDDh
0 ~ 32767f
SW_bit
HHHh
0 ~ 7fff
W_bit
HHHHHHh
0 ~ 3fd7fff
SD
DDDD
0 ~ 2047
Special register
DDDDDDD
0 ~ 4184063
Data Register
HHHHHH
0 ~ 3fd7ff
Link Register
TN
DDDDD
0 ~ 25471
SN
DDDDD
0 ~ 25471
CN
DDDDD
0 ~ 25471
SW
HHH
0 ~ 7ff
DD
0 ~ 20
Index Register
DDDDD
0 ~ 32767
File Register
ZR
HHHHHH
0 ~ 3fd7ff
File Register
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V1.30
Jan/14/2011
Description
525
Mitsubishi MR J3/J4 A
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
Mitsubishi MR J3/J4 A
PLC I/F
RS485 4W
RS232/RS485
Baud rate
9600
9600~115200
Parity
Even
Data bits
Stop bits
0~31
Device Address:
Bit/Word
Device type
Format
Range
Memo
EIP
DD
0 ~ 31
EOP
DD
0 ~ 31
PA
DD
1 ~ 32
Basic Setting *4
PB
DD
1 ~ 64
PC
DD
1 ~ 80
Extension Setting *4
PD
DD
1 ~ 48
Status
DD
0 ~ 41
Amplifier Status *1
Alarm
0~6
Alarm
Alarm_T
0~6
Mode
1~4
Speed
0~1
Acc
0~1
Rotation
0~1
End
0~1
M_dist
0~1
Rot_P
0~1
P_start
0~1
Cur_Alarm
0~1
Current Alarm
PE
DD
1 ~ 64
Extension Setting 2 *4
PF
DD
1 ~ 48
Extension Setting 3 *4
526
Item
EIP
1
Droop pulse
10
Instantaneous torque
11
12
ABS conter
13
14
Bus voltage
15
16
17
18
22
23
24
Electrical angle
30
31
32
33
Setting time
34
35
40
41
Note2 represents the write-only registers. The usage of this kind of registers is to run Jog
Mode and Positioning Mode.
Note3represents the read-only registers.
Note4The data in address 1~XX is written to RAM, and the data in address 1001~10XX is
written to ROM.
527
EIP:
EOP:
528
b. End Macro
macro_command main()
short stop
stop = 1 // See Note 2.
SetData(stop, "MITSUBISHI MR J3 A", End, 1, 1)
end macro_command
Note 2. Original Factory Manual:
530
*Positioning Mode
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
1 RX-
4 TX-
2 RX+
5 TX+
3 TX-
6 RX-
4 TX+
3 RX+
5 GND
7 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
Male
7 RX-
4 TX-
6 RX+
5 TX+
9 TX-
6 RX-
8 TX+
3 RX+
5 GND
7 GND
532
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
4 TX-
2 RX+
2 RX+
5 TX+
3 TX-
3 TX-
6 RX-
4 TX+
4 TX+
3 RX+
5 GND
5 GND
7 GND
1 RX-
4 TX-
2 RX+
5 TX+
3 TX-
6 RX-
4 TX+
3 RX+
5 GND
7 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
Male
1 RX-
4 TX-
2 RX+
5 TX+
3 TX-
6 RX-
4 TX+
3 RX+
5 GND
7 GND
Driver Version:
Version
Date
Description
V1.00
Sep/01/2011
Driver released.
V1.10
Jan/13/2012
V1.40
Apr/14/2014
Support MRJ4
533
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
Parameter1
Network No.
255
PLC Setting:
534
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
SM
DDDD
0 ~ 2255
Special Relay
HHHH
0 ~ 1fff
Input
HHHH
0 ~ 1fff
Output
DDDDD
0 ~ 61439
Internal Relay
DDDDD
0 ~ 32767
Annunciator
HHHH
0 ~ efff
Link Relay
D_Bit
DDDDDDDh
0 ~ 4184063f
SD
DDDD
0 ~ 2255
Special Register
DDDDDDD
0 ~ 4184063
Data Register
HHHHHH
0 ~ 3fd7ff
Link Register
DDDDD
0 ~ 12287
Motion Register
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.10
Jun/08/2011
535
Mitsubishi Q00/Q00UJ/Q01/QJ71
Supported Series: Mitsubishi Q series PLC with QJ71C24 communication module, Q00,
Q00J, Q00UJ, Q01, Q02H, Q06H, Q12H, Q25H, Q12PH, Q25PH CPU port.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
PLC type
Mitsubishi Q00/Q00UJ/Q01/QJ71
PLC I/F
RS232
Baud rate
9600
9600~115200
Data bits
Parity
Odd
Stop bits
Online simulator
Yes
Options
Notes
PLC Setting:
Q00, Q01 CPU port setting:
1. In GX Developer PLC data list click [PLC parameter].
2. In PLC parameter go to [Serial] page.
3. Select [Use serial communication].
4. Set [Transmission speed] to 9600~115200.
5. Select [Sum check].
6. Set [Transmission wait time] to 10ms.
7. Permit [RUN write setting].
8. Click [End] to close the dialog.
9. Write the PLC Parameter to PLC.
10. Reset PLC, the parameter will be actived.
536
QJ71 setting:
537
Device Address:
Bit/Word Device type
Format
Range
Memo
HHHH
0 ~ 1fff
Input Relay
HHHH
0 ~ 1fff
Output Relay
DDDDD
0 ~ 61439
Internal Relay
DDDD
0 ~ 8191
Latch Relay
DDDD
0 ~ 2047
Annunciator
DDDD
0 ~ 2047
Edge Relay
HHHH
0 ~ efff
Link Relay
TC
DDDD
0 ~ 2047
Timer Coil
SS
DDDD
0 ~ 2047
SC
DDDD
0 ~ 2047
CS
DDDD
0 ~ 1023
Counter Contact
CC
DDDD
0 ~ 1023
Counter Coil
SB
HHH
0 ~ 7ff
DDDD
0 ~ 8191
Step Relay
DX
HHHH
0 ~ 1fff
Direct Input
DY
HHHH
0 ~ 1fff
Direct Output
TS
DDDD
0 ~ 2047
Timer Contact
SM
DDDD
0 ~ 2047
D_Bit
DDDDDDDh 0 ~ 4212735f
W_Bit
HHHHh
0 ~ 2ffff
ZR_Bit
HHHHHh
0 ~ fe7fff
ZR_Dec_Bit
DDDDDDDh 0 ~ 1042431f
HHHH
0 ~ 2fff
Link Register
TN
DDDD
0 ~ 2047
SN
DDDD
0 ~ 2047
CN
DDDD
0 ~ 1023
FFDDDDD
0 ~ 3132767
SW
HHH
0 ~ 7ff
DD
0 ~ 15
Index Register
ZR
HHHHH
0 ~ fe7a5
File Register
ZR_decimal_addr DDDDDDD
0 ~ 1042341
DDDDDDD
0 ~ 4212735
SD
DDDD
0 ~ 2047
538
Data Register
Wiring Diagram:
The following is the view from the soldering point of a cable.
QJ71C24 CH.2 RS422 Terminal
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series
SDB
SDA
RDB
RDA
GND
COM2 RS485 4W
9P D-Sub Female
7 RX-
SDB
6 RX+
SDA
9 TX-
RDB
8 TX+
RDA
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
SDB
2 RX+
2 RX+
SDA
3 TX-
3 TX-
RDB
4 TX+
4 TX+
RDA
5 GND
5 GND
GND
1 RX2 RX+
3 TX4 TX+
5 GND
SDB
SDA
RDB
RDA
GND
539
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX2 RX+
3 TX4 TX+
5 GND
SDB
SDA
RDB
RDA
GND
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
540
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
1 DCD
4 DTR
short
6 DSR
7 RTS
8 CTS
541
short
COM3 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
2 RX
8 RX
3 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
RS232 6P Mini-DIN
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 6P Mini-DIN
Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
9 RX
3 TXD
6 TX
4 RXD
5 GND
5 GND
View from the
soldering point
of a cable.
542
COM3 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
2 RX
8 RX
3 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
1 RTS
6 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
RS232 6P Mini-DIN
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 6P Mini-DIN
Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
5 GND
1 RTS
6 CTS
543
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
9 RX
3 TXD
6 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
View from the
soldering point
of a cable.
Driver Version:
Version
Date
Description
V1.80
Jun/08/2011
V1.90
Sep/23/2011
V2.00
Nov/12/2012
V2.30
Nov/07/2014
V2.50
Jan/09/2015
544
Mitsubishi Q00J
Supported Series: Mitsubishi Q00J CPU
HMI Setting:
Parameters
Recommended
PLC type
Mitsubishi Q00J
PLC I/F
RS232
Baud rate
115200
Data bits
Parity
Odd
Stop bits
Options
Notes
CPU port
9600,19200,38400,
57600,115200
NO
Device Address:
Bit/Word
Device type
Format
Range
SM
DDDD
0 ~ 1023
HHH
0 ~ 7ff
HHH
0 ~ 7ff
DDDDD
0 ~ 61439
DDDD
0 ~ 2047
DDDD
0 ~ 1023
DDDD
0 ~ 1023
HHH
0 ~ 7ff
SB
HHH
0 ~ 3ff
D_Bit
DDDDDDDh 0 ~ 4212735f
SD
DDDD
0 ~ 1023
DDDDDDD
0 ~ 4212735
HHH
0 ~ 7ff
SW
HHH
0 ~ 3ff
545
Memo
Bit/Word
Device type
Format
Range
0~9
DDD
0 ~ 511
DDD
0 ~ 511
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P Mini-DIN: Q00 CPU port RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
2 RX
8 RX
3 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
RS232 6P Mini-DIN
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 6P Mini-DIN
Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
5 GND
546
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
9 RX
3 TXD
6 TX
4 RXD
5 GND
5 GND
View from the
soldering point
of a cable.
Driver Version:
Version
Date
Description
V1.20
Jun/08/2011
V1.30
Nov/12/2012
547
Mitsubishi Q00U/Q01U/Q02U/QnUD/QnUDH
Supported Series: Mitsubishi Q00U, Q01U, Q02U, Q03UD, Q04UDH, Q06UDH, Q10UDH,
Q13UDH, Q20UDH, Q26UDH, Q00UJ CPU.
HMI Setting:
Parameters
Recommended
PLC type
Mitsubishi Q00U/Q01U/Q02U/QnUD/QnUDH
PLC I/F
RS232
Baud rate
115200
115200 only
Data bits
Parity
Odd
Stop bits
No
Online simulator
NO
Options
Notes
CPU port direct connect
9600,19200,38400,57600,115200
For Q00UJ, only 9600 is available
PLC Setting:
Please do not select [Use Serial Communication]. If this is selected the communication
method will be the same as QJ71, please refer to Mitsubishi Q00/Q00UJ/Q01/QJ71 driver.
548
Device Address:
Bit/Word Device type
Format
Range
Memo
SM
DDDD
0 ~ 2047
HHHH
0 ~ 1fff
Input Relay
HHHH
0 ~ 1fff
Output Relay
DDDDD
0 ~ 61439
Internal Relay
DDDDD
0 ~ 32767
Latch Relay
DDDDD
0 ~ 32767
Annunciator
DDDDD
0 ~ 32767
Edge Relay
HHHH
0 ~ efff
Link Relay
SB
HHHH
0 ~ 7fff
TC
DDDDD
0 ~ 2047
Timer Coil
CC
DDDDD
0 ~ 1023
Counter Coil
D_Bit
DDDDDDDh 0 ~ 4212735f
W_Bit
HHHHHHh
0 ~ 4047fff
ZR_Bit
HHHHHh
0 ~ fe7fff
ZR_Dec_Bit
DDDDDDDh 0 ~ 1042431f
SD
DDDD
0 ~ 2047
DDDDDDD
0 ~ 4212735
Data Register
HHHHHH
0 ~ 4047ff
Link Register
SW
HHHH
0 ~ 6dff
DD
0 ~ 19
Index Register
FFDDDDD
0 ~ 3132767
ZR
HHHHHH
0 ~ fe7ff
File Register
ZR_decimal_addr DDDDDDD
0 ~ 1042341
DDDDD
0 ~ 25471
DDDDD
0 ~ 25471
Note:
EasyBuilder doesnt support MITSUBISHI Q02U CPU to do on-line simulation on PC.
When using Q02U driver, HMI needs 10 seconds to initiate PLC Q02U driver. Before the
completion of initiation, it is recommended not to write data to PLC, this could cause PLC
no response Incorrect wiring or data could cause PLC to be locked. If PLC is locked,
please restart PLC or reinstall PLC module.
549
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P Mini-DIN: Q02 CPU port RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
2 RX
8 RX
3 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
1 RTS
6 CTS
short
cMT/mTV series
COM1 RS232 9P
RS232 6P Mini-DIN
D-Sub Female
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
RS232 6P Mini-DIN
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 6P Mini-DIN
Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
5 GND
1 RTS
6 CTS
550
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
9 RX
3 TXD
6 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
View from the
soldering point
of a cable.
Driver Version:
Version
Date
Description
V1.60
Jun/08/2011
V2.10
Nov/21/2012
V2.30
Nov/07/2014
V2.40
Jan/09/2015
551
Mitsubishi Q00UJ/QnU/QnUD/QnUDH/QnUDEH/L
(mini USB)
Supported Series: Mitsubishi Q00UJ, Q00U, Q01U, Q02U, Q03UDE, Q03UD, Q04UDEH,
Q04UDH, Q06UDEH, Q06UDH, Q10UDEH, Q10UDH, Q13UDEH, Q13UDH, Q20UDEH,
Q20UDH, Q26UDEH, Q26UDH, L02, L26-BT USB Port.
HMI Setting:
Parameters Recommended
Options
Notes
PLC type
PLC I/F
USB
Device Address:
Bit/Word
Device type
Format
Range
SM
DDDD
0 ~ 2047
HHHH
0 ~ 1fff
Input Relay
HHHH
0 ~ 1fff
Output Relay
DDDDD
0 ~ 61439
Internal Relay
DDDD
0 ~ 8191
Latch Relay
DDDD
0 ~ 2047
Annunciator
DDDD
0 ~ 2047
Edge Relay
HHHH
0 ~ 1fff
Link Relay
SB
HHH
0 ~ 7ff
D_Bit
DDDDDDDh 0 ~ 4212735f
ZR_Bit
HHHHh
0 ~ fffff
ZR_Dec_Bit
DDDDDh
0 ~ 65535f
SD
DDDD
0 ~ 2047
DDDDDDD
0 ~ 4212735
Data Register
HHHH
0 ~ 1fff
Link Register
SW
HHH
0 ~ 7ff
DD
0 ~ 19
Index Register
FFDDDDD
0 ~ 132767
ZR
HHHH
0 ~ ffff
ZR_decimal_addr DDDDD
0 ~ 65535
552
Memo
File Register
Bit/Word
Device type
Format
Range
Memo
DDDD
0 ~ 1023
DDDD
0 ~ 2047
Note:
EasyBuilder doesnt support MITSUBISHI Q02U CPU to do on-line simulation on PC.
When using Q02U driver, HMI needs 10 seconds to initiate PLC Q02U driver. Before the
completion of initiation, it is recommended not to write data to PLC, this could cause PLC
no response Incorrect wiring or data could cause PLC to be locked. If PLC is locked,
please restart PLC or reinstall PLC module.
Driver Version:
Version
Date
Description
V1.30
Jun/08/2011
V1.50
Nov/12/2012
V1.60
Nov/07/2014
553
Mitsubishi Q02/02H
Supported Series; Mitsubishi Q02/Q02H CPU port.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
PLC type
Mitsubishi Q02/02H
PLC I/F
RS232
Baud rate
115200
115200 only
Data bits
Parity
Odd
Stop bits
Online simulator
YES
Broadcast command
NO
Options
Notes
Device Address:
Bit/Word Device type
Format
Range
Memo
HHHH
0 ~ 1fff
Input Relay
HHHH
0 ~ 1fff
Output Relay
DDDDD
0 ~ 61439
Internal Relay
DDDDD
0 ~ 32767
Latch Relay
DDDDD
0 ~ 32767
Annunciator
DDDDD
0 ~ 32767
Edge Relay
HHHH
0 ~ 7fff
Link Relay
TC
DDDDD
0 ~ 23087
Timer Coil
SS
DDDDD
0 ~ 23087
SC
DDDDD
0 ~ 23087
CS
DDDDD
0 ~ 23087
Counter Contact
CC
DDDDD
0 ~ 23087
Counter Coil
554
Format
Range
Memo
SB
HHH
0 ~ 7ff
DDDD
0 ~ 8191
Step Relay
DX
HHHH
0 ~ 1fff
Direct Input
DY
HHHH
0 ~ 1fff
Direct Output
TS
DDDD
0 ~ 2047
Timer Contact
D_Bit
DDDDDDDh 0 ~ 4212735f
ZR_Bit
HHHHHh
ZR_Dec_Bit
DDDDDDDh 0 ~ 1042431f
HHHH
0 ~ 657f
Link Register
TN
DDDDD
0 ~ 23087
SN
DDDDD
0 ~ 23087
CN
DDDDD
0 ~ 23087
FFDDDDD
0 ~ 3132767
SW
HHH
0 ~ 7ff
DD
0 ~ 15
Index Register
ZR
HHHHH
0 ~ fe7ff
File Register
ZR_decimal_addr DDDDDDD
0 ~ 1042431
0 ~ 4212735
0 ~ fe7fff
DDDDDDD
Data Register
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P Mini-DIN: Q02 CPU port RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
2 RX
8 RX
3 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
1 RTS
6 CTS
555
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
RS232 6P Mini-DIN
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
COM2 RS232 9P
COM3 RS232 9P
RS232 6P Mini-DIN
D-Sub Female
D-Sub Female
D-Sub Male
Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
5 GND
1 RTS
6 CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
RS232 6P Mini-DIN
D-Sub Female
Male
9 RX
3 TXD
6 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
View from the
soldering point
of a cable.
556
Driver Version:
Version
Date
Description
V1.60
Jun/08/2011
V1.80
Nov/12/2012
V2.00
Nov/07/2014
557
Mitsubishi Q06H
Supported Series: Mitsubishi Q06H CPU port.
Website: http://www.mitsubishi-automation.com
HMI Setting:
Parameters
Recommended
PLC type
Mitsubishi Q06H
PLC I/F
RS232
Baud rate
115200
115200 only
Data bits
Parity
Odd
Stop bits
Online simulator
Options
YES
Notes
Broadcast command NO
*Support communications between HMI and PLC in pass-through mode
*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode
Device Address:
Bit/Word
Device type
Format
Range
Memo
HHHH
0 ~ 1fff
Input Relay
HHHH
0 ~ 1fff
Output Relay
DDDDD
0 ~ 61439
Internal Relay
DDDDD
0 ~ 32767
Latch Relay
DDDDD
0 ~ 32767
Annunciator
DDDDD
0 ~ 32767
Edge Relay
HHHH
0 ~ 7fff
Link Relay
TC
DDDDD
0 ~ 23087
Timer Coil
SS
DDDDD
0 ~ 23087
SC
DDDDD
0 ~ 23087
Retentive Timer
Contact Timer Coil
Retentive
CS
DDDDD
0 ~ 23087
Counter Contact
CC
DDDDD
0 ~ 23087
Counter Coil
558
Bit/Word
Device type
Format
Range
Memo
SB
HHH
0 ~ 7ff
DDDD
0 ~ 8191
Step Relay
DX
HHHH
0 ~ 1fff
Direct Input
DY
HHHH
0 ~ 1fff
Direct Output
TS
DDDD
0 ~ 2047
Timer Contact
D_Bit
DDDDDDDh
0 ~ 4212735f
ZR_Bit
HHHHHh
0 ~ fe7fff
ZR_Dec_Bit
DDDDDDDh
0 ~ 1042431f
HHHH
0 ~ 657f
Link Register
TN
DDDDD
0 ~ 23087
SN
DDDDD
0 ~ 23087
CN
DDDDD
0 ~ 23087
Retentive Timer
Current Value
Counter
Current
FFDDDDD
0 ~ 3132767
SW
HHH
0 ~ 7ff
DD
0 ~ 15
Index Register
ZR
HHHHH
0 ~ fe7ff
File Register
ZR_decimal_addr DDDDDDD
0 ~ 1042431
0 ~ 25983
DDDDD
File
Register (FF:File No.
Value
0~31) (DDDDD:0~32767)
Data Register
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 6P Mini-DIN : Q02 CPU port RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
2 RX
8 RX
3 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
1 RTS
6 CTS
559
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 6P Mini-DIN
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
RS232 6P Mini-DIN
Male
2 RX
3 TXD
3 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
COM2 RS232 9P
COM3 RS232 9P
RS232 6P Mini-DIN
D-Sub Female
D-Sub Female
D-Sub Male
Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
5 GND
1 RTS
6 CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
RS232 6P Mini-DIN
D-Sub Female
Male
9 RX
3 TXD
6 TX
4 RXD
5 GND
5 GND
1 RTS
6 CTS
short
View from the
soldering point
of a cable.
560
Driver Version:
Version
Date
Description
V1.60
Jun/08/2011
V1.80
Nov/12/2012
V2.00
Nov/07/2014
561
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
5002
1~99
Network
1~999
Notes
PLC Setting:
QJ71E71-100 Ethernet module settings:
1. Use USB or RS232 of Q-CPU for setting PLC parameters.
562
2.
563
3.
4.
564
5.
6.
Restart PLC software and select [READ FROM PLC], select [QCPU(Qmode)]
and press [OK].
7.
In [PC side I/F Ethernet board setting] set Network No. and Station No.
(Station No.1 is PC Station No. not Ethernet module Station No., ranged
from 2~64, the Network No. can not be the same as that of PC)
565
8.
9.
For Other station, click [Other station(Single network)] for setting [Check
at communication time] and [Retry times].
10. After finishing the settings above, click [Connection test] for testing the
communication and sending the PLC program.
566
Device Address:
Bit/Word Device type
Format
Range
Memo
SM
DDDD
0 ~ 2047
HHHH
0 ~ 1fff
Input Relay
HHHH
0 ~ 1fff
Output Relay
DDDDD
0 ~ 61439
Internal Relay
DDDD
0 ~ 8191
Latch Relay
DDDD
0 ~ 2047
Annunciator
DDDD
0 ~ 2047
Edge Relay
HHHH
0 ~ 1fff
Link Relay
TS
DDDD
0 ~ 2047
Timer Contact
TC
DDDD
0 ~ 2047
Timer Coil
SS
DDDD
0 ~ 2047
SC
DDDD
0 ~ 2047
CS
DDDD
0 ~ 1023
Counter Contact
CC
DDDD
0 ~ 1023
Counter Coil
SB
HHH
0 ~ 7ff
DDDD
0 ~ 8191
Step Relay
DX
HHHH
0 ~ 1fff
Direct Input
DY
HHHH
0 ~ 1fff
Direct Output
D_Bit
DDDDDDDh 0 ~ 4212735f
ZR_Bit
HHHHHh
ZR_Dec_Bit
DDDDDDDh 0 ~ 1042431f
SD
DDDD
0 ~ 2047
DDDDDDD
0 ~ 4212735
Data Register
HHHH
0 ~ 1fff
Link Register
TN
DDDD
0 ~ 2047
SN
DDDD
0 ~ 2047
CN
DDDD
0 ~ 1023
SW
HHH
0 ~ 7ff
DD
0 ~ 15
Index Register
FFDDDDD
0 ~ 3132767
ZR
HHHHH
0 ~ fe7ff
ZR_decimal_addr DDDDDDD
0 ~ fe7fff
0 ~ 1042341
567
File Register
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V2.20
Jun/08/2011
V2.30
Nov/12/2012
V2.50
Nov/07/2014
568
MODBUS ASCII
Supported Series: MODBUS ASCII CONTROLLER
Website: http://www.modbus.org
HMI Setting:
Parameters
Recommended
PLC type
MODBUS ASCII
PLC I/F
RS485
RS232/RS485
Baud rate
9600
9600/19200/38400/
57600/115200
Data bits
7,8
Parity
Even
Stop bits
1,2
0-255
Online simulator
Options
YES
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
1x
DDDDD
1 ~ 65535
0x
DDDDD
1 ~ 65535
Output bit
3x_Bit
DDDDDdd
100 ~ 6553515
4x_Bit
DDDDDdd
100 ~ 6553515
3x
DDDDD
1 ~ 65535
4x
DDDDD
1 ~ 65535
Output Register
6x
DDDDD
1 ~ 65535
569
Wiring Diagram:
The following is the view from the soldering point of a cable.
Modbus ASCII Controller : RS232
eMT3000 series
COM1 RS232 9P
COM3 RS232 9P
RS232 9P D-Sub
D-Sub Female
D-Sub Female
Female
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
RTS
CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
RS232 9P D-Sub
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
570
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
RTS
CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
TXD
6 TX
RXD
5 GND
GND
RTS
CTS
short
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
571
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
RS485 4W 9P D-Sub
9P D-Sub Female
Female
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
572
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
COM3 RS485 2W
RS485 2W 9P D-Sub
9P D-Sub Female
9P D-Sub Female
Female
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
Driver Version:
Version
Date
V1.40
Apr/17/2009
Description
573
Recommended
PLC type
PLC I/F
RS232
RS232, RS485
Baud rate
9600
9600~115200
Data bits
7,8
Parity
Even
Stop bits
1-31
Online simulator
Options
Notes
YES
Broadcast command NO
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
Memo
LB
dddd
0 ~ 9998
LW
dddd
0 ~ 9998
RW
ddddd
0 ~ 55536
1x
3x
4x
574
Wiring Diagram:
The following is the view from the soldering point of a cable.
RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
RTS
CTS
short
cMT/mTV series
COM1 RS232 9P
RS232 9P D-Sub
D-Sub Female
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
RS232 9P D-Sub
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
RTS
CTS
575
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
TXD
6 TX
RXD
5 GND
GND
RTS
CTS
short
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
576
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Female
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
cMT/mTV series
577
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
Note: Setting more than one Modbus ASCII Server in HMI Device List is of no effect.
Driver Version:
Version
Date
Description
V1.00
Feb/19/2009
Driver released
578
MODBUS RTU
Supported Series : MODBUS RTU CONTROLLER
Website : http://www.modbus.org
HMI Setting:
Parameters
Recommended
PLC type
MODBUS RTU
PLC I/F
RS485
RS232/RS485
Baud rate
9600
9600~115200
Data bits
7, 8
Parity
Even
Stop bits
1, 2
0-255
Online simulator
YES
Options
Notes
PLC Setting:
Communication mode
579
Device Address:
Bit/Word Device type
Format
Range
Memo
0x
DDDDD
1 ~ 65535
Output bit
0x_single_bit
DDDDD
1 ~ 65535
*Note4
1x_single_bit
DDDDD
1 ~ 65535
*Note4
1x
DDDDD
1 ~ 65535
3x_Bit
4x_Bit
B
B
6x_Bit
DDDDDdd 100 ~ 6553515
0x_multi_coils DDDDD
1 ~ 65535
3x
DDDDD
1 ~ 65535
3x_MAX1W
DDDDD
1 ~ 65535
DW
3x_MAX2W
DDDDD
1 ~ 65535
*Note1
4x
DDDDD
1 ~ 65535
Output Register
4x_MAX1W
DDDDD
1 ~ 65535
DW
4x_MAX2W
DDDDD
1 ~ 65535
*Note1
DW
5x
DDDDD
1 ~ 65535
W
W
6x
3x_Double
DDDDD
1 ~ 65535
DDDDD
1 ~ 65535
4x_Double
DDDDD
1 ~ 65535
*Note2
4x_32Bit
DDDDD
1 ~ 65535
0x_single_coil DDDDD
1 ~ 65535
*Note3
Note1: MAX1W and 4X_32Bit read/write 1 word for each package and display a 32-bits
value, whereas MAX2W reads/write 2 words for each package.
Note2: Go the [System Parameter Settings] -> [Device Properties] and click [Conversion]
to set the data format of device types 3x, 4x, 6x, 3x_double, 4x double.
580
Note3: Read/write a Bit at a time. Value 0 and 1 are used to represent ON or OFF status
where 0 means set OFF and 1 means set ON.
Note4: The number of bits to read can be set in Macro, therefore, it is recommended to
use 0x address type for functions such as GetData() and SetData(), in order to increase
reading speed.
To read/write multiple 0x address type in macro, use 0x_multi_coils to increase write
speed.
NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost the
same as 4x except that 5x swaps double word.
If 4x contains the following information:
Address
Data in word
0x1
0x2
0x3
0x4
0x5
0x6
Data
0x0201
0x0403
0x0605
Address
Data in word
0x1
0x2
0x3
0x4
0x5
0x6
...
Data
0x0102
0x0304
...
0x0506
4x
0x03 Read holding register
0x10 write multiple registers
5x
0x03 Read holding register
0x10 write multiple registers
(Note: reverse word order in double word format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 write single register
(Note: 6x is limited to device of one word only)
0x_single_coil 0x01 Read coil
0x05 write single coil
581
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
FeMale
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
RTS
CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
FeMale
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
RS232 9P D-Sub
FeMale
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
FeMale
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
RTS
CTS
582
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
FeMale
9 RX
TXD
6 TX
RXD
5 GND
GND
RTS
CTS
short
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
583
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Female
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
cMT/mTV series
584
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Female
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
Driver Version:
Version
Date
Description
V1.90
May/05/2010
V2.50
Dec/03/2014
585
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485
RS232/RS485
Baud rate
9600
9600~115200
Data bits
7,8
Parity
Even
Stop bits
1,2
0-255
Online simulator
YES
YES
Options
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
0x
DDDDD
1 ~ 65535
Output bit
1x
DDDDD
1 ~ 65535
3x_Bit
DDDDDdd
100 ~ 6553515
4x_Bit
DDDDDdd
100 ~ 6553515
B
B
6x_Bit
DDDDDdd
0x_multi_coils DDDDD
100 ~ 6553515
1 ~ 65535
3x
DDDDD
1 ~ 65535
4x
DDDDD
1 ~ 65535
Output Register
DW
5x
DDDDD
1 ~ 65535
W
W
6x
4x_32Bit*
DDDDD
1 ~ 65535
DDDDD
1 ~ 65535
4x_32Bit will only read / write 2 words for each package, for continuous addresses, it will
be divided into several packages.
586
NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost
the same as 4x except that 5x swaps double words.
If 4x contains the following information:
Address
Data in word
0x1
0x2
0x3
0x4
0x5
0x6
Data
0x0201
0x0403
0x0605
Address
Data in word
0x1
0x2
0x3
0x4
0x5
0x6
...
Data
0x0102
0x0304
...
0x0506
3x
0x04 Read input register
N/A for writing operation
4x
0x03 Read holding register
0x10 Write multiple registers
5x
0x03 Read holding register
0x10 Write multiple registers
(Note: reverse word order in double words format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 Write single register
(Note: 6x is limited to device of one word only)
587
Setting Instructions:
1.
2.
After adding Modbus RTU (0x 1x Range Adjustable) driver, [Add Address Range Limit]
button will be enabled as below. Users can set maximum read/write command size
here.
Note: Setting [Add Address Range Limit] is enabled only when bit address is not a multiple
of 16bit.
588
3.
Click [Add Address Range Limit] button, Users can define 0x , 1x and 0x_multi_coils
address range in [0x 1x Address Range] dialog box, referring to bit range of the
device used.
589
AddSet [Station No.], [Device Type], [Min. Address], [Max. Address] then click [OK] to
finish adding as below:
Example
Take D2 and D8 of SCON as example, the settings depend on bit range of different PLC
types. Set [Station No.] and address first.
For D2, set [Station No.] to 20, [Device Type] 0x, [Max. Address] 36.
For D8, set [Station No.] to 2, [Device Type] 0x, [Max. Address] 51.
590
Note: If communicating with a RS-485 2W PLC, the [Turn around delay] setting may need
to be adjusted according to the reply speed of the device. Please click [Settings] in [Device
Properties], and set the [Turn around delay (ms)] parameter as shown:
591
Wiring Diagram:
The following is the view from the soldering point of a cable.
MODBUS RTU CONTROLLER : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
RTS
CTS
short
cMT/mTV series
COM1 RS232 9P
RS232 9P D-Sub
D-Sub Female
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
RS232 9P D-Sub
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
RTS
CTS
592
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
TXD
6 TX
RXD
5 GND
GND
RTS
CTS
short
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
593
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Female
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
cMT/mTV series
594
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Female
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
Driver Version:
Version
Date
V1.10
Aug/25/2010
V1.20
Mar/2/2012
Description
Allow modifying the Minimum address of 0x1x Address Range.
595
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485
RS232/RS485
Baud rate
9600
9600/19200/3840
0/57600/115200
Data bits
7,8
Parity
Even
Stop bits
1,2
0-255
Online simulator
YES
YES
Options
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
0x
DDDDD
1 ~ 65535
Output bit
1x
DDDDD
1 ~ 65535
3x_Bit
DDDDDdd
100 ~ 6553515
B
B
4x_Bit
DDDDDdd
0x_multi_coils DDDDD
100 ~ 6553515
1 ~ 65535
3x
DDDDD
1 ~ 65535
4x
DDDDD
1 ~ 65535
Output Register
5x
DDDDD
1 ~ 65535
DW
5x (32-bit)
DDDDD
1 ~ 65535
4x double word
6x
DDDDD
1 ~ 65535
596
NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost
the same as 4x except that 5x swaps double words.
If 4x contains the following information:
Address
Data in word
0x1
0x2
0x3
0x4
0x5
0x6
Data
0x0201
0x0403
0x0605
Address
Data in word
0x1
0x2
0x3
0x4
0x5
0x6
...
Data
0x0102
0x0304
...
0x0506
3x
0x04 Read input register
N/A for writing operation
4x
0x03 Read holding register
0x10 Write multiple registers
5x
0x03 Read holding register
0x10 Write multiple registers
(Note: reverse word order in double words format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 Write single register
(Note: 6x is limited to device of one word only)
597
Setting Instructions:
1.
2.
After adding MODBUS RTU (Adjustable) driver, [Add Address Range Limit] button will
be enabled as below. Users can set maximum read/write command size here.
598
Note:
MODBUS RTU (adjustable) usage
Users can decide the address range via setting value on Parameter 1. For example, when
users set 5 to Parameter 1, the address range will be 5 ~ 65535.
599
Wiring Diagram:
The following is the view from the soldering point of a cable.
MODBUS RTU CONTROLLER : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
RTS
CTS
short
cMT/mTV series
COM1 RS232 9P
RS232 9P D-Sub
D-Sub Female
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
RS232 9P D-Sub
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
RTS
CTS
600
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
TXD
6 TX
RXD
5 GND
GND
RTS
CTS
short
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
601
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Female
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
cMT/mTV series
602
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Female
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
Driver Version:
Version
Date
V1.40
Jun/14/2011
Description
603
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485
RS232/RS485
Baud rate
9600
9600~115200
Data bits
7,8
Parity
Even
Stop bits
1,2
0-255
Online simulator
Options
YES
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
0x
DDDDD
0 ~ 65535
Output bit
1x
DDDDD
0 ~ 65535
3x_Bit
DDDDDdd
0 ~ 6553515
B
B
4x_Bit
DDDDDdd
0x_multi_coils DDDDD
0 ~ 6553515
0 ~ 65535
3x
DDDDD
0 ~ 65535
4x
DDDDD
0 ~ 65535
Output Register
DW
5x
DDDDD
0 ~ 65535
6x
DDDDD
0 ~ 65535
604
NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost the
same as 4x except that 5x swaps double words.
If 4x contains the following information:
Address
Data in word
0x1
0x2
0x3
0x4
0x5
0x6
Data
0x0201
0x0403
0x0605
Address
Data in word
0x1
0x2
0x3
0x4
0x5
0x6
...
Data
0x0102
0x0304
...
0x0506
3x
0x04 Read input register
N/A for write operation
4x
0x03 Read holding register
0x10 write multiple registers
5x
0x03 Read holding register
0x10 write multiple registers
(Note: reverse word order in double word format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 write single register
(Note: 6x is limited to device of one word only)
605
Wiring Diagram:
The following is the view from the soldering point of a cable.
MODBUS RTU CONTROLLER : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
RTS
CTS
short
cMT/mTV series
COM1 RS232 9P
RS232 9P D-Sub
D-Sub Female
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
RS232 9P D-Sub
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
RTS
CTS
606
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
TXD
6 TX
RXD
5 GND
GND
RTS
CTS
short
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
607
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Female
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
cMT/mTV series
608
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Female
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
Driver Version:
Version
Date
V1.30
Aug/26/2009
Description
609
Recommended
PLC type
PLC I/F
RS232
RS232, RS485
Baud rate
9600
9600~115200
Ethernet
Data bits
Parity
Even
Stop bits
Even, Odd,
None
1
1-31
Port no.
Online simulator
Options
Notes
502
YES
Broadcast command NO
If HMI is Modbus Server, connecting two or more Modbus Servers with one Modbus RTU
via RS485 4W is not supported. To do so, use RS485 2W instead.
610
PLC Setting:
Communication mode
611
Note:
A maximum of 64 Clients can be connected simultaneously.
Modbus Server Port No. cant be identical to HMI Port No.
612
For Modbus Server TCP/IP, HMI Port No. is the same as Modbus Server Port No. To
change Prot No. go to [System Parameter Settings] / [Model], the default Port No. is
8000, and it is allowed to change Modbus Server Port No. here.
613
Note the following two points when enabling the [MODBUS TCP/IP Gateway]:
a. The original mapping between the MODBUS Server and the HMI address will be
canceled.
b. The SCADA cannot read from or write in the addresses defined in different Address
Mapping Table at one time.
For more information about this, see Chapter37 MODBUS TCPIP Gateway.
Device Address:
Bit/Word
Device type
Format
Range
Memo
LB
dddd
0 ~ 9998
LW
dddd
0 ~ 9998
RW
ddddd
0 ~ 55536
Condition
01
02
03
Incorrect data
Error Code
Definition
Condition
251
Incorrect data
252
Incorrect data
253
Incorrect data
Wiring Diagram:
The following is the view from the soldering point of a cable.
MODBUS SERVER : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
RTS
CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
RS232 9P D-Sub
Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
615
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
RTS
CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
TXD
6 TX
RXD
5 GND
GND
RTS
CTS
short
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
616
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
RS485 4W 9P D-Sub
9P D-Sub Female
Female
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
617
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
COM3 RS485 2W
RS485 2W 9P D-Sub
9P D-Sub Female
9P D-Sub Female
Female
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
618
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Note: Setting more than one Modbus Server in HMI Device List is of no effect.
Driver Version:
Version
Date
Description
V1.00
Dec/30/2008
Driver released
619
MODBUS TCP/IP
Supported Series: Modbus RTU TCP/IP device.
Website: http://www.modbus.org
HMI Setting:
Parameters
Recommended
PLC type
MODBUS TCP/IP
PLC I/F
Ethernet
Port no.
502
Options
Notes
0~255
Device Address:
Bit/Word Device type
Format
Range
Memo
0x
DDDDD
1 ~ 65535
Output bit
1x
DDDDD
1 ~ 65535
0x_single_Bit
DDDDD
1 ~ 65535
1x_single_Bit
DDDDD
1 ~ 65535
3x_bit
DDDDDdd
100 ~ 6553515
4x_bit
DDDDDdd
100 ~ 6553515
6x_bit
DDDDDdd
100 ~ 6553515
0x_multi_coils DDDDD
1 ~ 65535
3x
DDDDD
1 ~ 65535
Input Register
4x
DDDDD
1 ~ 65535
Output Register
DW
5x
DDDDD
1 ~ 65535
6x
DDDDD
1 ~ 65535
DW
3x_Double
DDDDD
1 ~ 65535
*Note1
DW
4X_Double
4x string
central
europe
4x string
central
europe (rev)
DDDDD
1 ~ 65535
*Note1
DDDDD
1 ~ 65535
DDDDD
1 ~ 65535
620
Note1: Go the [System Parameter Settings] -> [Device Properties] and click [Conversion]
to set the data format of device types 3x, 4x, 6x, 3x_double, 4x double.
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V2.00
Mar/23/2015
Description
621
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
502
Notes
0~255
Online simulator
YES
YES
Device Address:
Bit/Word Device type
Format
Range
Memo
0x
DDDDD
1 ~ 65535
Output bit
1x
DDDDD
1 ~ 65535
3x_Bit
DDDDDdd
100 ~ 6553515
4x_Bit
DDDDDdd
100 ~ 6553515
B
B
6x_Bit
DDDDDdd
0x_multi_coils DDDDD
100 ~ 6553515
1 ~ 65535
3x
DDDDD
1 ~ 65535
4x
DDDDD
1 ~ 65535
Output Register
DW
5x
DDDDD
1 ~ 65535
6x
4x string
central
europe rev
DDDDD
1 ~ 65535
DDDDD
1 ~ 65535
622
NOTE:
Address type 5x is mapping to Hold Reg. The communication protocol of 5x is almost
the same as 4x except that 5x swaps double words.
If 4x contains the following information:
Address
Data in word
0x1
0x2
0x3
0x4
0x5
0x6
Data
0x0201
0x0403
0x0605
Address
Data in word
0x1
0x2
0x3
0x4
0x5
0x6
...
Data
0x0102
0x0304
...
0x0506
3x
0x04 Read input register
N/A for writing operation
4x
0x03 Read holding register
0x10 Write multiple registers
5x
0x03 Read holding register
0x10 Write multiple registers
(Note: reverse word order in double words format)
3xbit is equivalent to 3x
4xbit is equivalent to 4x
6x
0x03 Read holding register
0x06 Write single register
(Note: 6x is limited to device of one word only)
623
Setting Instructions:
1.
2.
Click [Add Address Range Limit] button, Users can define 0x and 1x address range in
[0x 1x Address Range] dialog box, referring to bit range of the device used.
624
AddSet [Station No.], [Device Type], [Max. Address] then click [OK] to finish adding as
below:
625
Example
Take 0x and 1x as example, the settings depend on bit range of different PLC types.
For 0x, [Device Type] 0x, [Min. Address]5,[Max. Address] 20.
For 1x, [Device Type] 0x, [Min. Address]1,[Max. Address] 10.
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
NOV/2/2011
V1.10
MAR/14/2012
Driver released.
Allow modifying the Minimum address of 0x1x Address Range.
626
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
502
Notes
0~255
Device Address:
Bit/Word Device type
Format
Range
Memo
0x
DDDDD
0 ~ 65535
Output bit
1x
DDDDD
0 ~ 65535
3x_Bit
DDDDDdd
0 ~ 6553515
4x_Bit
DDDDDdd
0 ~ 6553515
6x_Bit
DDDDDdd
0 ~ 6553515
0x_multi_coils DDDDD
0 ~ 65535
3x
DDDDD
0 ~ 65535
Input Register
4x
DDDDD
0 ~ 65535
Output Register
DW
5x
DDDDD
0 ~ 65535
6x
DDDDD
0 ~ 65535
627
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V1.40
Aug/27/2009
Description
628
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
502
Notes
0~255
Device Address:
Bit/Word
Device type
Format
Range
Memo
0x
DDDDD
1 ~ 65535
Output bit
1x
DDDDD
1 ~ 65535
3x_Bit
DDDDDdd
100 ~ 6553515
4x_Bit
DDDDDdd
100 ~ 6553515
6x_Bit
DDDDDdd
100 ~ 6553515
0x_multi_coils
DDDDD
1 ~ 65535
3x
DDDDD
1 ~ 65535
Input Register
4x
DDDDD
1 ~ 65535
Output Register
DW
5x
DDDDD
1 ~ 65535
6x
DDDDD
1 ~ 65535
4x_32Bit*
DDDDD
1 ~ 65535
4x_32Bit will only read / write 2 words for each package, for continuous addresses, it will
be divided into several packages.
629
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.10
Aug/27/2009
Driver released.
630
Moeller XC-CPU101
Supported Series: MOELLER XC100/200 series
Website: http://www.moeller.net
HMI Setting:
Parameters
Recommended
PLC type
Moeller XC-CPU101
PLC I/F
RS232
Baud rate
38400
Data bits
Parity
None
Stop bits
Options
Notes
4800 ~ 57600
Device Address:
Bit/Word
Device type
Format
Range
IX
DDo
0 ~ 157
QX
DDo
0 ~ 157
MX
DDDDo
0 ~ 40957
IW
DD
0 ~ 15
QW
DD
0 ~ 15
MW
DDDD
0 ~ 4095
Note
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
5 TD
3 TX
7 TX
8 RD
5 GND
5 GND
4 GND
631
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
5 TD
3 TX
8 RD
5 GND
4 GND
2 RX
5 TD
3 TX
8 RD
5 GND
4 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
5 TD
3 TX
4 TX
7 TX
8 RD
5 GND
5 GND
5 GND
4 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
5 TD
6 TX
8 RD
5 GND
4 GND
Driver Version:
Version
Date
Description
V1.00
Apr/01/2010
Driver released.
632
motrona CT-150
Supported Series: motrona CT-150
Website: http://motrona.net/index.html
HMI Setting:
Parameters
Recommended
Options
PLC type
motrona CT-150
PLC I/F
RS232
RS232/RS485
Baud rate
9600
1200 ~ 38400
Data bits
Even,Odd,None
Parity
Even
7,8
Stop bits
1,2
11
11 ~ 99
Notes
Device Address:
Bit/Word
Device type
Format
Range
An
4~8
W
W
Bn
1~9
Cn
DD
0 ~ 99
An_32Bit
4~8
Bn_32Bit
1~9
Cn_32Bit
DD
0 ~ 99
ERR_CNT
LV_VAL
PRTMARK_ERR
BAT_CNT
WASTE_CNT
LINE_SPD
ACT_CUT_LEN
ACT_CUT_ERR_M D
ACT_CUT_ERR_L D
633
Note
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
RS232 9P D-Sub
Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
634
Driver Version:
Version
Date
Description
V1.00
Oct/11/2012
Driver released.
Jun/20/2014
V1.10
635
motrona CT15012B
Supported Series: motrona CT15012B
Website: http://motrona.net/index.html
HMI Setting:
Parameters
Recommended
PLC type
motrona CT15012B
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
Even
Stop bits
11
Options
Notes
Note
Device Address:
Bit/Word
Device type
Format
Range
Cn
DD
0 ~ 99
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
COM3 RS232 9P
RS232 9P D-Sub
D-Sub Female
D-Sub Female
Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
636
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Dec/19/2012
Driver released.
637
motrona MC700
Supported Series: motrona MC700
Website: http://motrona.net/index.html
HMI Setting:
Parameters
Recommended
PLC type
motrona MC700
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
Even
Stop bits
11
Options
Notes
Note
Device Address:
Bit/Word
Device type
Format
Range
ERCD
HHHH
0 ~ FFFF
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
COM3 RS232 9P
RS232 9P D-Sub
D-Sub Female
D-Sub Female
Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
638
RS232 9P D-Sub
Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Dec/19/2012
Driver released.
639
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word Device type
Format
Range
DDD
1 ~ 107
4x
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
7 D-
2 RX+
9 Data+
8 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
7 D-
6 RX+
1 Data+
8 D+
5 GND
5 GND
5 GND
cMT/mTV series
640
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
7 D-
2 RX+
8 Data+
8 D+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
7 D-
2 RX+
9 Data+
8 D+
5 GND
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
7 D-
2 RX+
9 Data+
8 D+
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
7 D-
2 RX+
8 Data+
8 D+
5 GND
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Jan/15/2014
Driver released.
641
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485 2W
Baud rate
115200
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word Device type
Format
Range
A1 ~ A14
DD
1 ~ 32
B1 ~ B17
B18
DD
1 ~ 32
B19 ~ B24
B25 ~ B26
DD
1~8
B27 ~ B46
C1 ~ C6
D1 ~ D13
E1 ~ E6
F1 ~ F41
G1
G2
DD
1 ~ 10
G3 ~ G5
DD
1~7
H1 ~ H10
J1 ~ J6
642
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Female
1 RX-
6 Data-
7 Out 9 In -
2 RX+
9 Data+
2 Out +
4 In +
5 GND
short
short
5 GND
8 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Female
7 RX-
4 Data-
7 Out -
cMT/mTV series
9 In 6 RX+
1 Data+
2 Out +
4 In +
5 GND
5 GND
short
short
8 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Female
1 RX-
7 Data-
7 Out 9 In -
2 RX+
8 Data+
2 Out +
4 In +
5 GND
9 GND
short
short
8 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Female
1 RX-
6 Data-
7 Out 9 In -
2 RX+
9 Data+
2 Out +
4 In +
5 GND
5 GND
8 GND
643
short
short
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Female
1 RX-
6 Data-
7 Out 9 In -
2 RX+
9 Data+
2 Out +
4 In +
5 GND
5 GND
short
short
8 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Female
1 RX-
7 Data-
7 Out 9 In -
2 RX+
8 Data+
2 Out +
4 In +
5 GND
5 GND
8 GND
Driver Version:
Version
Date
Description
V1.00
Aug/24/2012
Driver released.
644
short
short
NMEA 0183
Supported Series: NMEA 0183 Interface Standard.
HMI Setting:
Parameters
Recommended
Options
PLC type
NMEA 0183
PLC I/F
RS232
Baud rate
4800
4800 ~ 115200
Data bits
7,8
Parity
None
None,Even,Odd
Stop bits
1,2
Notes
NMEA Sentences:
Support sentences
AAM
ACK
ADS
AKD
ALA
ALM
ALR
APB
BEC
BOD
BWC
BWR
BWW
COP
CUR
DBT
DCR
DDC
DOR
DPT
DSC
DTM
ETL
EVE
FIR
FSI
GBS
GGA
GLC
GLL
GMP
GNS
GRS
GSA
GST
GSV
HDG
HMR
HMS
HSC
HSS
HTC
HTD
LCD
MLA
MSK
MSS
MTW
MWD
MWV
NAK
NRM
OSD
PRC
RMA
RMB
RMC
ROR
ROT
RPM
RSA
RSD
RST
SFI
SID
STN
THS
TLL
TRD
TTM
TUT
TXT
UID
VBW
VDR
VER
VHW
VLW
VPW
VTG
WAT
WCV
WNC
WPL
XTE
XTR
ZDA
ZDL
ZFO
ZTG
645
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
SD
3 TX
7 TX
RD
5 GND
5 GND
GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
SD
3 TX
RD
5 GND
GND
2 RX
SD
3 TX
RD
5 GND
GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
SD
3 TX
4 TX
7 TX
RD
5 GND
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
SD
6 TX
RD
5 GND
GND
646
Driver Version:
Version
Date
Description
V1.00
Mar/24/2016
Driver releasesd.
647
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
44818
Notes
Please click [Tag Editor] when adding this driver to initiate tag information. To edit address
tag, please see the factory manual.
648
The following is an example of how to add Vendor ID in Tag Editor. See 3.2.3 Identity
Object in factory manual for the detail of this ID.
Under Struct-Defined select Identity to add Vendor_ID. {1,1,1} represents {Class code ,
Instance ID , Attribute ID}. Enter UINT in Data Type field according to the factory
manual. When finished, this data member can be found in Identity Object.
649
Memo
Bool
bit
Byte
8-bit
SInt
8-bit
USInt
8-bit
Word
16-bit
Int
16-bit
UInt
16-bit
DWord
32-bit
DInt
32-bit
Real
32-bit Float
32-bit
UDInt
32-bit
Array
Length=word
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Apr/29/2013
Driver released.
650
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS232
Baud rate
9600
9600, 19200
Data bits
7 or 8
Parity
Even
Stop bits
1 or 2
0-31
Online simulator
Options
YES
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
IR
DDDDdd
HR
DDDDdd
LR
DDDDdd
IR (Force Set/Reset)
DDDDdd
0 ~ 409515
0 ~ 409515
LR (Force Set/Reset)
DDDDdd
0 ~ 409515
AR
DDDDdd
AR_W
DDDD
0 ~ 4095
IR_W
DDDD
0 ~ 4095
651
Memo
Bit/Word
Device type
Format
Range
HR_W
DDDD
0 ~ 4095
LR_W
DDDD
0 ~ 4095
TC
DDD
0 ~ 255
DM
DDDD
0 ~ 9999
Memo
Data Register
Wiring Diagram:
The following is the view from the soldering point of a cable.
CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
Communication Module:
CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series)
CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 SD
3 TX
7 TX
3 RD
5 GND
5 GND
9 GND
4 RS
5 CS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 SD
3 TX
3 RD
5 GND
9 GND
4 RS
5 CS
short
2 RX
2 SD
3 TX
3 RD
5 GND
9 GND
4 RS
5 CS
652
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 SD
3 TX
4 TX
7 TX
3 RD
5 GND
5 GND
5 GND
9 GND
4 RS
5 CS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 SD
6 TX
3 RD
5 GND
9 GND
4 RS
5 CS
short
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 SD
3 TX
7 TX
3 RD
5 GND
5 GND
7 GND
4 RS
5 CS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 SD
3 TX
3 RD
5 GND
7 GND
4 RS
5 CS
653
short
2 RX
2 SD
3 TX
3 RD
5 GND
7 GND
4 RS
5 CS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 SD
3 TX
4 TX
7 TX
3 RD
5 GND
5 GND
5 GND
7 GND
4 RS
5 CS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 SD
6 TX
3 RD
5 GND
7 GND
4 RS
5 CS
Driver Version:
Version
Date
V1.80
Apr/14/2010
Description
654
short
OMRON CJ/CS/CP
Supported Series: OMRON CP1E,CP1L, CP1H, CJ1M, CJ2M, CJ1H, CJM1G, CS1H and
CS1G. (Host Link Protocol FINS command), this driver supports Extend Addressing Mode.
Website: http://www.omron.com/
HMI Setting:
Parameters
Recommended
PLC type
OMRON CJ/CS/CP
PLC I/F
RS232
Baud rate
9600
9600~115200
Data bits
7 or 8
Parity
Even
Stop bits
1 or 2
0-31
Online simulator
Options
YES
Notes
Broadcast command NO
*Support communications between HMI and PLC in pass-through mode
*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in
pass-through mode
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
CIO_Bit
DDDDDdd
W_Bit
DDDDDdd
H_Bit
DDDDDdd
D_Bit
DDDDDdd
A_Bit
DDDDDdd
T_Bit
DDDDDdd
C_Bit
DDDDDdd
Memo
Bit/Word
Device type
Format
Range
C_flag
DDDD
0 ~ 4095
T_flag
DDDD
0 ~ 4095
LR_Bit
DDDdd
0 ~ 19915
EM0_Bit
EMC_Bit
DDDDDdd
0 ~3276715
Extend Memory
DDDDD
0 ~ 32767
Timer (TIM)
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
Counter (CNT)
CIO
DDDDD
0 ~ 32767
EM0 ~ EMC
DDDDD
0 ~ 32767
Extend Memory
LR
DDD
0 ~ 199
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 SD
3 TX
7 TX
3 RD
5 GND
5 GND
9 GND
4 RS
5 CS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 SD
3 TX
3 RD
5 GND
9 GND
4 RS
5 CS
656
short
2 RX
2 SD
3 TX
3 RD
5 GND
9 GND
4 RS
5 CS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 SD
3 TX
4 TX
7 TX
3 RD
5 GND
5 GND
5 GND
9 GND
4 RS
5 CS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 SD
6 TX
3 RD
5 GND
9 GND
4 RS
5 CS
short
CP1W-CIF11 RS485
4W Terminal
1 RX-
SDA
2 RX+
SDB
3 TX-
RDA
4 TX+
RDB
5 GND
FG
657
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
CP1W-CIF11 RS485
4W Terminal
7 RX-
SDA
6 RX+
SDB
9 TX-
RDA
8 TX+
RDB
5 GND
FG
COM2 RS485 4W
9P D-Sub Male
CP1W-CIF11 RS485
4W Terminal
1 RX-
1 RX-
SDA
2 RX+
2 RX+
SDB
3 TX-
3 TX-
RDA
4 TX+
4 TX+
RDB
5 GND
5 GND
FG
CP1W-CIF11 RS485
9P D-Sub Male
4W Terminal
1 RX-
SDA
2 RX+
SDB
3 TX-
RDA
4 TX+
RDB
5 GND
FG
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
CP1W-CIF11 RS485
9P D-Sub Female
4W Terminal
1 RX-
SDA
2 RX+
SDB
3 TX-
RDA
4 TX+
RDB
5 GND
FG
658
Driver Version:
Version
Date
Description
V1.90
Feb/01/2011
V2.00
Dec/05/2012
659
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
9600
PLC Setting:
Communication mode
660
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
CIO_Bit
DDDDDdd
W_Bit
DDDDDdd
H_Bit
DDDDDdd
A_Bit
DDDDDdd
D_Bit
DDDDDdd
T_Bit
DDDDDdd
C_Bit
DDDDDdd
C_Flag
DDDD
0 ~ 4095
T_Flag
DDDD
0 ~ 4095
EM0_Bit ~
EMC_Bit
DDDDDdd
CIO
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
Counter (CNT)
DDDDD
0 ~ 32767
Timer (TIM)
DDDDD
0 ~ 32767
EM0 ~ EMC
DDDDD
0 ~ 32767
Extend Memory
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
661
Driver Version:
Version
Date
Description
V1.80
Dec/05/2012
662
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
USB
Online simulator
Options
Notes
USB Host
No
Device Address:
Bit/Word
Device type
Format
Range
Memo
CIO_Bit
DDDdd
0 ~ 28915
A_Bit
DDDdd
0 ~ 75315
T_Bit
DDDdd
0 ~ 25515
Timer (TIM)
C_Bit
DDDdd
0 ~ 25515
Counter (CNT)
D_Bit
DDDDdd
0 ~ 204715
H_Bit
DDdd
0 ~ 4915
W_Bit
DDdd
0 ~ 9915
CIO
DDD
0 ~ 289
DDD
0 ~ 753
DDD
0 ~ 255
Timer (TIM)
DDD
0 ~ 255
Counter (CNT)
DDDD
0 ~ 2047
DD
0 ~ 49
DD
0 ~ 99
Driver Version:
Version
Date
Description
V1.00
Jan/20/2015
Driver released.
663
OMRON E5CN/E5EZ/E5ZN
Supported Series: OMRON E5CN series temperature controller with communication
options. E5EN/CN/GN/EZ/ZN series.
Website: http://oeiweb.omron.com
HMI Setting:
Parameters
Recommended
PLC type
OMRON E5CN
PLC I/F
RS485 2W
Baud rate
9600
9600/19200/38400/
57600/115200
Data bits
7,8
Parity
Even
Stop bits
1,2
0-99
Online simulator
Options
YES
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
Status_CH1 DD
0 ~ 31
Page40
Status_CH2 DD
0 ~ 31
DW
C0
HHHH
0 ~ 270f
DW
C1
HHHH
0 ~ 270f
DW
C2
HHHH
0 ~ 270f
DW
C3
HHHH
0 ~ 270f
Code00_00
Code00_01
Code01_00
Run
Code01_01
Stop
664
Bit/Word
Device type
Format
Range
Memo
Code02_00
Code02_01
Code02_02
Code02_03
Code03_00
AT cancel
Code03_01
AT execute
Code04_00
Code04_01
Code05_00
Code06_00
Software reset
Code07_00
Code08_00
Code01_10
Code01_11
Code01_F0
Code01_F1
Code02_10
Code02_11
Code02_F0
Code02_F1
Code03_10
Code03_11
Code03_F0
Code03_F1
Code09_00
Code09_01
Code09_10
Code09_11
Code09_F0
Code09_F1
Code0A_00
Code0B_00
Code0C_00
Code0C_01
Code0C_02
Code0C_0F H
Code0C_10
665
Bit/Word
Device type
Format
Range
Code0C_11
Code0C_12
Code0C_1F H
Code0C_F0 H
Code0C_F1 H
Code0C_F2 H
Code0C_FF H
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
COM3 RS485 2W
OMRON E5CN
9P D-Sub Male
9P D-Sub Male
Terminal
1 RX-
6 Data-
12 B
2 RX+
9 Data+
11 A
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
OMRON E5CN
Terminal
7 RX-
4 Data-
12 B
6 RX+
1 Data+
11 A
5 GND
5 GND
GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
COM3 RS485 2W
OMRON E5CN
9P D-Sub Male
9P D-Sub Male
Terminal
1 RX-
7 Data-
12 B
2 RX+
8 Data+
11 A
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
OMRON E5CN
Terminal
1 RX-
6 Data-
12 B
2 RX+
9 Data+
11 A
5 GND
5 GND
GND
666
COM3 RS485 2W
9P D-Sub Male
OMRON E5CN
Terminal
1 RX-
6 Data-
12 B
2 RX+
9 Data+
11 A
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
OMRON E5CN
Terminal
1 RX-
7 Data-
12 B
2 RX+
8 Data+
11 A
5 GND
5 GND
GND
Note:
For communication with OMRON E5EZ, please set communication settings to 9600, E, 7,
2, station no. 1.
Driver Version:
Version
Date
V1.21
Dec/21/2010
Description
667
OMRON Ethernet
Supported Series: OMRON CJ Series, CS Series, CP Series +Ethernet Module. (Ethernet
FINS)
Website: http://www.omron.com/
*On initialization, switch from RUN MODE to MONITOR MODE.
HMI Setting:
Parameters
Recommended
PLC type
OMRON Ethernet
PLC I/F
Ethernet (UDP)
Port no.
9600
Options
PLC Setting:
Communication mode
668
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
CIO_Bit
DDDDDdd
W_Bit
DDDDDdd
H_Bit
DDDDDdd
A_Bit
DDDDDdd
D_Bit
DDDDDdd
T_Bit
DDDDDdd
C_Bit
DDDDDdd
C_Flag
DDDD
0 ~ 4095
T_Flag
DDDD
0 ~ 4095
DDDDDdd
DDDDD
0 ~ 32767
EM0_Bit ~
EMC_Bit
CIO
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
Counter (CNT)
DDDDD
0 ~ 32767
Timer (TIM)
DDDDD
0 ~ 32767
EM0 ~ EMC
DDDDD
0 ~ 32767
Extend Memory
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
669
Driver Version:
Version
Date
Description
V1.00
Oct/4/2012
Driver released.
V1.40
Dec/11/2015
670
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
9600
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
CIO_Bit
DDDDDdd
W_Bit
DDDDDdd
H_Bit
DDDDDdd
A_Bit
DDDDDdd
D_Bit
DDDDDdd
T_Bit
DDDDDdd
C_Bit
DDDDDdd
C_Flag
DDDD
0 ~ 4095
T_Flag
DDDD
0 ~ 4095
CIO
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
DDDDD
0 ~ 32767
Counter (CNT)
DDDDD
0 ~ 32767
Timer (TIM)
DDDDD
0 ~ 32767
EM0 ~ EMC
DDDDD
0 ~ 32767
Extend Memory
671
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
May/26/2011
Driver released.
672
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
Ethernet
Port no.
44818
On-line simulator
Yes
Options
Notes
Multi-HMI connect
Yes
Instructions:
Note:
1. In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting
address tag.
2. When [Do not publish] is selected for a tag, different import methods may lead to
different results. When import tags by [Get Tags from Device], the tag will be
eliminated. If [Import tags] is selected, the tags will be imported, but the
communication will not succeed.
673
3. The Import Status field shows the result, click [Exit] to finish importing address
tags.
674
4. Click [Get Tags] [Import Tags] and then select the file exported in step 1.
675
5. The Import Status field shows the result, click [Exit] to finish importing address
tags.
Supported data types include: BOOL, SINT, BYTE, USINT, INT, WORD, UINT,
DINT, REAL, UDINT and DWORD. These data types support one-dimensional
array.
Bool
bit
Byte
8-bit
DInt
Real
32-bit Float
32-bit
UDInt
32-bit
SInt
USInt
Word
Int
UInt
DWord
Array
676
Memo
8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit
Length=word
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Dec/14/2012
Driver released.
677
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS232
Baud rate
9600
9600, 19200
Data bits
7 or 8
Parity
Even
Stop bits
1 or 2
0-31
Online simulator
Options
YES
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
IR
DDDDdd
HR
DDDDdd
LR
DDDDdd
IR (Force Set/Reset)
DDDDdd
0 ~ 409515
0 ~ 409515
LR (Force Set/Reset)
DDDDdd
0 ~ 409515
AR
DDDDdd
AR_W
DDDD
0 ~ 4095
IR_W
DDDD
0 ~ 4095
HR_W
DDDD
0 ~ 4095
LR_W
DDDD
0 ~ 4095
TC
DDD
0 ~ 255
DM
DDDD
0 ~ 9999
678
Memo
Data Register
Wiring Diagram:
The following is the view from the soldering point of a cable.
CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
Communication Module:
CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series)
CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
eMT3000 series
COM1 RS232 9P
COM3 RS232 9P
D-Sub Female
D-Sub Female
2 RX
8 RX
2 SD
3 TX
7 TX
3 RD
5 GND
5 GND
9 GND
4 RS
5 CS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 SD
3 TX
3 RD
5 GND
9 GND
4 RS
5 CS
short
2 RX
2 SD
3 TX
3 RD
5 GND
9 GND
4 RS
5 CS
679
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 SD
3 TX
4 TX
7 TX
3 RD
5 GND
5 GND
5 GND
9 GND
4 RS
5 CS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 SD
6 TX
3 RD
5 GND
9 GND
4 RS
5 CS
short
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 SD
3 TX
7 TX
3 RD
5 GND
5 GND
7 GND
4 RS
5 CS
680
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 SD
3 TX
3 RD
5 GND
7 GND
4 RS
5 CS
short
2 RX
2 SD
3 TX
3 RD
5 GND
7 GND
4 RS
5 CS
short
COM2 RS232 9P
COM3 RS232 9P
D-Sub Female
D-Sub Female
D-Sub Male
2 RX
6 RX
8 RX
2 SD
3 TX
4 TX
7 TX
3 RD
5 GND
5 GND
5 GND
7 GND
4 RS
5 CS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 SD
6 TX
3 RD
5 GND
7 GND
4 RS
5 CS
681
short
Driver Version:
Version
Date
V1.30
OCT/21/2010
Description
682
OuHua OHJX
Website: http://www.ohjx.com/
HMI Setting:
Parameters
Recommended
PLC type
OuHua OHJX
PLC I/F
RS-232
Baud rate
9600
Data bits
Parity
Odd
Stop bits
Options
Notes
9600,19200
Device Address:
Bit/Word
Device type
Format
Range
R100
Dh
0 ~ 1f
R101
Dh
0 ~ 1f
R102
Dh
0 ~ 1f
R103
Dh
0 ~ 1f
R104
Dh
0 ~ 1f
R105
Dh
0 ~ 1f
R106
Dh
0 ~ 1f
R107
Dh
0 ~ 1f
R108
Dh
0 ~ 1f
R109
Dh
0 ~ 1f
R110
Dh
0 ~ 1f
R210
Dh
0 ~ 1f
R310
Dh
0 ~ 1f
SV
DDDD
0 ~ 9999
EV
DDDDD
0 ~ 65535
DT
DDDDD
0 ~ 9999
LD
DDDD
0 ~ 8447
WX
DDDD
0 ~ 9999
683
Memo
Bit/Word
Device type
Format
Range
WY
DDDD
0 ~ 9999
WR
DDDD
0 ~ 9999
WL
DDDD
0 ~ 9999
FL
DDDDD
0 ~ 99999
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
4P Mini-DIN Male
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
1 GND
4 GND
short
cMT/mTV series
COM1 RS232 9P
4P Mini-DIN Male
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
1 GND
4 GND
short
4P Mini-DIN Male
2 RX
3 TX
3 TX
2 RX
5 GND
1 GND
4 GND
684
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
4P Mini-DIN Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
1 GND
4 GND
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
4P Mini-DIN Male
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
1 GND
4 GND
short
View from the
soldering point
of a cable.
Driver Version:
Version
Date
Description
V1.00
Nov/22/2011
Driver released.
685
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
Odd
Stop bits
Notes
9600 ~ 115200
Bool
bit
Byte
8-bit
SInt
8-bit
USInt
8-bit
Word
16-bit
Int
16-bit
UInt
16-bit
DWord
32-bit
DInt
32-bit
Real
32-bit Float
32-bit
UDInt
32-bit
686
Memo
Import Tags:
1. The file for import must be built in Easy Build Pro\Data Type\PanasonicPowerMeter
folder. The user can build the file according to the device types in advance, as shown
below.
Name : User-defined tag name.
Data :Type: Define according to the data length and range.
Address : The address of the device.
Description : The description about the address.
Data type
BOOL
Bit
BYTE
8-bits Unsigned
WORD
16-bits Unsigned
DWORD
32-bits Unsigned
UDINT
32-bits Unsigned
UINT
16-bits Unsigned
USINT
8-bits Unsigned
SINT
8-bits Signed
INT
16-bits Signed
DINT
32-bits Signed
REAL
32-bits Float
2. In EasyBuilder select [Panasonic Eco-Power Meters] driver, and then click [Station
No. and Device Model].
687
3. [Station no.]: Set the station number according to the device, the range is 1~99.
[Name]: The name of the device.
[Model]: The models with their address tag files saved in Easy Build Pro\Data
Type\PanasonicPowerMeter can be found in the drop down list.
[Add]: Add a new model.
[Delete]: Delete a model. (At least one model should exist in the list.)
[Import]: Import the .dat file of the model.
[Export]: Export the .dat file of the model.
[OK]: Save and leave.
[Cancel]: Dont save and leave.
688
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W
Terminal
1 RX-
6 Data-
B-
2 RX+
9 Data+
A+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
PLC RS485 2W
Terminal
7 RX-
4 Data-
B-
6 RX+
1 Data+
A+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W
Terminal
1 RX-
7 Data-
B-
2 RX+
8 Data+
A+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W
Terminal
1 RX-
6 Data-
B-
2 RX+
9 Data+
A+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W
Terminal
1 RX-
6 Data-
B-
2 RX+
9 Data+
A+
5 GND
5 GND
689
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P RJ45
1 RX-
7 Data-
8 Data-
2 RX+
8 Data+
1 Data+
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Apr/13/2016
Driver released
690
Panasonic FP/KW
Supported Series: NAIS (Matsushita) FP/KW series include FP-X, FP-, FP0, FP1, FP2,
FP2SH, FP10SH and FP3 Ethernet support FP-X with AFPX-COM5.
Website:http://pewa.panasonic.com/
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
Panasonic FP/KW
PLC I/F
RS232
RS232/RS485
Baud rate
9600
Data bits
Parity
Odd
Stop bits
1 or 2
1-32
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDh
0 ~ 9999f
Input (X)
DDDDh
0 ~ 9999f
Output (Y)
DDDDh
0 ~ 9999f
DDDD
0 ~ 9999
L_Bit
DDDDh
0 ~ 9999f
DDDD
0 ~ 9999
Timer (T)
DDDD
0 ~ 9999
Counter (C)
SV
DDDD
0 ~ 9999
EV
DDDDD
0 ~ 65535
DT
DDDDD
0 ~ 99999
LD
DDDD
0 ~ 8447
WX
DDDD
0 ~ 9999
WY
DDDD
0 ~ 9999
Output (WY)
WR
DDDD
0 ~ 9999
691
Bit/Word
Device type
Format
Range
Memo
WL
DDDD
0 ~ 9999
FL
DDDDD
0 ~ 99999
Wiring Diagram:
The following is the view from the soldering point of a cable.
FP0, FP2, FP2SH, FPM CPU : 9P D-Sub to 5P Mini-DIN
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 5P Mini-DIN
Male
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
1 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 5P Mini-DIN
Male
2 RX
2 TXD
3 TX
3 RXD
5 GND
1 GND
RS232 5P Mini-DIN
Male
2 RX
2 TXD
3 TX
3 RXD
5 GND
1 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 5P Mini-DIN
Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
1 GND
692
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 5P Mini-DIN
Male
9 RX
2 TXD
6 TX
3 RXD
5 GND
1 GND
View from the
soldering point
of a cable.
COM3 RS232 9P
D-Sub Female
RS232 3P Terminal
2 RX
8 RX
3 TX
7 TX
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 3P Terminal
2 RX
3 TX
5 GND
RS232 3P Terminal
D-Sub Female
2 RX
3 TX
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 3P Terminal
2 RX
6 RX
8 RX
3 TX
4 TX
7 TX
5 GND
5 GND
5 GND
693
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 3P Terminal
9 RX
6 TX
5 GND
COM3 RS232 9P
D-Sub Female
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
7 GND
4 RTS
5 CTS
8 CD
9 ER
short
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
7 GND
4 RTS
5 CTS
8 CD
9 ER
694
short
short
2 RX
2 TXD
3 TX
3 RXD
5 GND
7 GND
4 RTS
5 CTS
8 CD
9 ER
short
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
7 GND
4 RTS
5 CTS
8 CD
9 ER
short
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
3 RXD
5 GND
7 GND
4 RTS
5 CTS
8 CD
9 ER
695
short
short
RS485 4W 8P Hirose
Female socket
1 RX-
2 TXDA
2 RX+
5 TXDB
3 TX-
3 RXDA
4 TX+
6 RXDB
5 GND
1 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 8P Hirose
Female socket
7 RX-
2 TXDA
6 RX+
5 TXDB
9 TX-
3 RXDA
8 TX+
6 RXDB
5 GND
1 GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 8P Hirose
Female socket
1 RX-
1 RX-
2 TXDA
2 RX+
2 RX+
5 TXDB
3 TX-
3 TX-
3 RXDA
4 TX+
4 TX+
6 RXDB
5 GND
5 GND
1 GND
RS485 4W 8P Hirose
Male
1 RX-
2 TXDA
2 RX+
5 TXDB
3 TX-
3 RXDA
4 TX+
6 RXDB
5 GND
1 GND
696
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 8P Hirose
Male
1 RX-
2 TXDA
2 RX+
5 TXDB
3 TX-
3 RXDA
4 TX+
6 RXDB
5 GND
1 GND
View from the
soldering point
of a cable.
1 RX-
9 TXDA
2 RX+
2 TXDB
3 TX-
10 RXDA
4 TX+
3 RXDB
5 GND
7 GND
4 RTS+
5 CTS+
11 RTS12 CTS-
short
short
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
9 TXDA
6 RX+
2 TXDB
9 TX-
10 RXDA
8 TX+
3 RXDB
5 GND
7 GND
4 RTS+
5 CTS+
11 RTS12 CTS697
short
short
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
9 TXDA
2 RX+
2 RX+
2 TXDB
3 TX-
3 TX-
10 RXDA
4 TX+
4 TX+
3 RXDB
5 GND
5 GND
7 GND
4 RTS+
5 CTS+
11 RTS12 CTS-
short
short
1 RX-
9 TXDA
2 RX+
2 TXDB
3 TX-
10 RXDA
4 TX+
3 RXDB
5 GND
7 GND
4 RTS+
5 CTS+
11 RTS12 CTS-
698
short
short
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
9 TXDA
2 RX+
2 TXDB
3 TX-
10 RXDA
4 TX+
3 RXDB
5 GND
7 GND
4 RTS+
5 CTS+
11 RTS12 CTS-
Driver Version:
Version
Date
Description
V1.80
Apr/09/2010
Added registers: FL
699
short
short
Panasonic FP (Ethernet)
Supported Series: NAIS (Matsushita) FP series include FP-X, FP-, FP0, FP1, FP2,
FP2SH, FP10SH and FP3 Ethernet support FP-X with AFPX-COM5.
Website: http://pewa.panasonic.com/
HMI Setting:
Parameters
Recommended
Options
PLC type
Panasonic FP (Ethernet)
PLC I/F
Ethernet
Port no.
9094
Notes
0~255
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDh
0 ~ 9999f
Input (X)
DDDDh
0 ~ 9999f
Output (Y)
DDDDh
0 ~ 9999f
DDDD
0 ~ 9999
L_Bit
DDDDh
0 ~ 9999f
DDDD
0 ~ 9999
Timer (T)
DDDD
0 ~ 9999
Counter (C)
SV
DDDD
0 ~ 9999
EV
DDDDD
0 ~ 65535
DT
DDDDD
0 ~ 99999
LD
DDDD
0 ~ 8447
WX
DDDD
0 ~ 9999
WY
DDDD
0 ~ 9999
Output (WY)
WR
DDDD
0 ~ 9999
WL
DDDD
0 ~ 9999
FL
DDDDD
0 ~ 99999
700
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Ethernet
RS232
FP-X
MT8000
AFPX-COM5
Driver Version:
Version
Date
V1.80
Apr/12/2010
Description
701
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
8500
Notes
0~255
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDh
0 ~ 9999f
Input (X)
DDDDh
0 ~ 9999f
Output (Y)
DDDDh
0 ~ 9999f
DDDD
0 ~ 9999
L_Bit
DDDDh
0 ~ 9999f
DDDD
0 ~ 9999
Timer (T)
DDDD
0 ~ 9999
Counter (C)
SV
DDDD
0 ~ 9999
EV
DDDDD
0 ~ 65535
DT
DDDDD
0 ~ 99999
LD
DDDD
0 ~ 8447
WX
DDDD
0 ~ 9999
WY
DDDD
0 ~ 9999
Output (WY)
WR
DDDD
0 ~ 9999
WL
DDDD
0 ~ 9999
702
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Mar/11/2010
Driver released.
703
Panasonic MINAS A4
Supported Series: Panasonic MINAS A4 series Servo Drive.
HMI Setting:
Parameters
Recommended
PLC type
Panasonic MINAS A4
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
None
Stop bits
Axis no.
Options
Notes
2400 ~ 57600
0 ~ F (slave)
Device Address:
Bit/Word
Device type
Format
Range
Memo
Command 20
0~7
States (Note 3)
Command 27
DD
0 ~ 31
Command 28
DD
0 ~ 31
Command 01
Command 05
DD
0 ~ 11
Command 06
DD
0 ~ 11
Command 21
0~1
Command 22
0~1
Command 24
present speed
(Numeric format: 16-bit Unsigned)
Command 25
present torque
(Numeric format: 16-bit Unsigned)
Command 26
0~1
Command 84
704
Bit/Word
Device type
Format
Range
Memo
Command 90
Command 91
DD
1 ~ 14
Command 92
DD
1 ~ 14
Command 93
Command 94
Command 9B
Parameter
HH
0 ~ 7f
Comm2D_S
0~1
Comm2D_M
0~1
Note:
1. Command 84, Command 93, Command 94, and Command 9B are write only. (These
commands are able to use Set Bit Object and execute the write command after
triggering Set Bit Object.). Commands other than these four are read only.
2. Parameter read/write: Use device type to define address control from 00~7F.
For example: address_00 is mapping to Parameter_00.
(Please refer to Panasonic MINAS A4 Series User Manual.)
3. Device address type can define MINAS A4 Drivers command list.
Command 20, Command 27, and Command 28 are Bit type, use Operating range to
map communication order status.
For example: Command 20_3 means Read state_CCW.
(Please refer to Panasonic MINAS A4 Series User Manual.)
4. Command 91 and Command 92 are word type, use Operating range to map the
record of 14 alarms.
For example: Command 91_1 means Read alarm data_First alarm.
705
Wiring Diagram:
The following is the view from the soldering point of a cable.
MINAS A4 Driver CNX4 Port
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
8 RX
3 TXD
3 TX
7 TX
5 RXD
5 GND
5 GND
4 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
3 TXD
3 TX
5 RXD
5 GND
4 GND
RS232 8P Mini-DIN
D-Sub Female
Male
2 RX
3 TXD
3 TX
5 RXD
5 GND
4 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 8P Mini-DIN
Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
5 RXD
5 GND
5 GND
5 GND
4 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
9 RX
3 TXD
6 TX
5 RXD
5 GND
4 GND
View from the
soldering point
of a cable.
706
MINAS A4 Driver
CNX4 Port
3 TX
8P Mini-Din Male
MINAS A4 Driver
CNX3 / CNX4 Port
RX
GND
GND
D-
D-
D+
D+
MINAS A4 Driver
8p Mini-DIN Male
D-
D-
D+
D+
GND
GND
MINAS A4 Driver
8p Mini-DIN Male
RXD
RXD
TXD
TXD
GND
GND
707
Driver Version:
Version
Date
V1.10
Jan/11/2010
V1.20
Jul/25/2012
Description
Added registersComm2D_S and Comm2D_M.
708
Panasonic MINAS A5
Supported Series: Panasonic MINAS A5 series Servo Drive.
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
Panasonic MINAS A5
PLC I/F
RS232
RS232/RS485 2W
Baud rate
9600
2400~115200
Data bits
Parity
None
Stop bits
Axis no.
0 ~ 127 (slave)
* When connecting with more than two devices, it is recommended to set timeout to more
than 4 seconds. Set a longer timeout when connecting with more devices to maintain good
communication.
Device Address:
Bit/Word
Device type
Format
Range
Memo
Command 20
0~7
States (Note 3)
Command 27
DD
0 ~ 31
Command 28
DD
0 ~ 31
Command 01
Command 05
DD
0 ~ 11
Command 06
DD
0 ~ 11
Command 21
0~1
Command 22
0~1
Command 24
present speed
(Numeric format: 16-bit Unsigned)
Command 25
present torque
(Numeric format: 16-bit Unsigned)
709
Bit/Word
Device type
Format
Range
Memo
Command 26
0~1
Command2D_S
0~1
Command2D_M D
0~1
Parameter
HHH
0 ~ 639
Command 72
Command 90
Command 92
DD
1 ~ 14
Command 93
Command 94
Command 9B
Note:
1.
2.
Command 72, Command 93, Command 94, and Command 9B are write only. (These
commands are able to use Set Bit Object and execute the write command after
triggering Set Bit Object.). Commands other than these four are read only.
Parameter read/write: Use device type to define address control from 000~639.
710
Wiring Diagram:
The following is the view from the soldering point of a cable.
MINAS A5 Driver X2 Port RS232 Signal
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 8P Connector
2 RX
8 RX
3 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
1 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 8P Connector
2 RX
3 TXD
3 TX
4 RXD
5 GND
1 GND
RS232 8P Connector
D-Sub Female
2 RX
3 TXD
3 TX
4 RXD
5 GND
1 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 8P Connector
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
1 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 8P Connector
9 RX
3 TXD
6 TX
4 RXD
5 GND
1 GND
711
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P
Connector
1 RX-
6 Data-
5,7 485-
2 RX+
9 Data+
6,8 485+
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P
Connector
7 RX-
4 Data-
5,7 485-
6 RX+
1 Data+
6,8 485+
5 GND
5 GND
GND
cMT/mTV series
GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P
Connector
1 RX-
7 Data-
5,7 485-
2 RX+
8 Data+
6,8 485+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P
Connector
1 RX-
6 Data-
5,7 485-
2 RX+
9 Data+
6,8 485+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P
Connector
1 RX-
6 Data-
5,7 485-
2 RX+
9 Data+
6,8 485+
5 GND
5 GND
712
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P
Connector
1 RX-
7 Data-
5,7 485-
2 RX+
8 Data+
6,8 485+
5 GND
5 GND
GND
Driver Version:
Version
Date
Description
V1.00
May/23/2012
V1.10
Jul/13/2013
Driver released.
Added registersComm2D_S and Comm2D_M.
V1.20
Mar/10/2014
713
Parker ACR9000
Supported Series: Parker ACR9000.
Website: http://www.parkermotion.com
HMI Setting:
Parameters
Recommended
PLC type
Parker ACR9000
PLC I/F
RS232
RS485 4W / RS232/Ethernet
Baud rate
38400
1200 - 38400
Data bits
7,8
Parity
None
Stop bits
1,2
Port no.
5006
Online simulator
Options
YES
Notes
Device Address:
Bit/Word Device type
Format
Range
P_Low16bit
DDDDDdd
0 ~ 9999915
P_High16bit
DDDDDdd
0 ~ 9999915
P_Int32
DDDDD
0 ~ 99999
P_Float
DDDDD
0 ~ 99999
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
714
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
715
Ethernet cable:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Dec/30/2008
Driver released.
V1.20
Sep/09/2015
716
Parker Compax3
Supported Series: Parker Compax3 Servo Drive.
Website: http://www.parker.com
HMI Setting:
RS232
Parameters
Recommended
Options
Notes
PLC type
Parker Compax3
PLC I/F
RS232
Baud rate
115200
Data bits
7 or 8
Parity
None
Stop bits
1 or 2
Parameters
Recommended
Options
Notes
PLC type
Parker Compax3
PLC I/F
RS485 2W
Baud rate
9600
Data bits
7 or 8
Parity
None
Stop bits
1 or 2
RS485
1-99
717
PLC Setting:
How to set Compax 3 servo to RS485 mode?
1. Open C3 ServoManager2, select Communication => RS-485 Settings.
718
Device Address:
Bit/Word
Device type
Format
Range
Memo
R_Low16bit
DDDDDDDDh
0 ~ 99999999f
R_High16bit
DDDDDDDDh
0 ~ 99999999f
DW
Register_Int
DDDDDD
0 ~ 999999
DW
Register_float
DDDDDD
0 ~ 999999
Register_Short
DDDDDD
0 ~ 999999
The range of the address that can be operated depends on the address type.
(For more information, please see PLC Connection Guide)
For example:
If the read / write address is: 1901.2, please enter 190102
If the read / write address is: 400.1, please enter 40001
Wiring Diagram:
The following is the view from the soldering point of a cable.
Parker Compax3 PLC X10 : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
719
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
COM3 RS485 2W
RS485 2W 9P D-Sub
9P D-Sub Male
9P D-Sub Male
Male
1 RX-
6 Data-
3 Data-
2 RX+
9 Data+
7 Data+
5 GND
5 GND
5 GND
1 Enable RS485
9 +5V
720
short
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
3 Data-
6 RX+
1 Data+
7 Data+
5 GND
5 GND
5 GND
1 nable RS485
9 +5V
short
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
3 Data-
2 RX+
8 Data+
7 Data+
5 GND
9 GND
5 GND
1 Enable RS485
9 +5V
short
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
COM3 RS485 2W
RS485 2W 9P D-Sub
9P D-Sub Male
9P D-Sub Male
Male
1 RX-
6 Data-
3 Data-
2 RX+
9 Data+
7 Data+
5 GND
5 GND
5 GND
1 Enable RS485
9 +5V
short
COM3 RS485 2W
RS485 2W 9P D-Sub
9P D-Sub Male
9P D-Sub Male
Male
1 RX-
6 Data-
3 Data-
2 RX+
9 Data+
7 Data+
5 GND
5 GND
5 GND
1 Enable RS485
9 +5V
721
short
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
3 Data-
2 RX+
8 Data+
7 Data+
5 GND
5 GND
5 GND
1 Enable RS485
9 +5V
Driver Version:
Version
Date
V1.70
Mar/30/2009
Description
722
short
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word
Range
Memo
VARB(L)
DDDdd
1 ~ 125
VARB(H)
DDDdd
1 ~ 125
RUN_PRG
DW
VARI
DDD
1 ~ 125
DW
VAR
DDD
1 ~ 125
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
723
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Apr/7/2011
Driver released.
724
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485 4W
Baud rate
9600
9600/19200
Data bits
7,8
Parity
Even
Stop bits
1,2
Online simulator
Options
Notes
0-31
YES
Device Address:
Bit/Word
Device type
Format
Range
Memo
Par_Binary
DDDDdd
0 ~ 999915
Par_One_Word
DDDD
0 ~ 9999
DW
Par_Two_Word
DDDD
0 ~ 9999
Par_One_Byte
DDDD
0 ~ 9999
RESET
RUN
725
Wiring Diagram:
The following is the view from the soldering point of a cable.
Parker SLVD Servo Serial Link X1
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
1 RX-
7 TX-
2 RX+
12 TX+
3 TX-
2 RX-
4 TX+
1 RX+
6 TER
5 GND
short
3 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
7 TX-
6 RX+
12 TX+
9 TX-
2 RX-
8 TX+
1 RX+
6 TER
5 GND
short
3 GND
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
7 TX-
2 RX+
2 RX+
12 TX+
3 TX-
3 TX-
2 RX-
4 TX+
4 TX+
1 RX+
6 TER
5 GND
5 GND
3 GND
726
short
1 RX-
7 TX-
2 RX+
12 TX+
3 TX-
2 RX-
4 TX+
1 RX+
6 TER
5 GND
short
3 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
7 TX-
2 RX+
12 TX+
3 TX-
2 RX-
4 TX+
1 RX+
6 TER
5 GND
3 GND
Driver Version:
Version
Date
Description
V1.00
Jan/27/2010
Driver released.
727
short
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
RS232
RS232 / RS485 2W /
RS485 4W/ Ethernet
Baud rate
38400
9600 ~ 115200
Data bits
7,8
Parity
Even
Stop bits
1,2
0 ~ 31
Port no.
10600
Device Address:
Bit/Word
Device type
Format
Range
LAW_bit
HHHHh
1 ~ 7FFE
LAW
HHHH
1 ~ 7FFE
LAW6Mode
LAW6Style
LAW6Scale
LAW6BG_c
LAW6Chr_c
UNI2sJIS
HHHH
1 ~ 7FFE
LAWUnicode to shift-JIS
UNI2BIG5
HHHH
1 ~ 7FFE
LAWUnicode to BIG5
728
Memo
hBit no.(0 ~ f)
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
729
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W
Terminal
1 RX-
6 Data-
11 Data-
2 RX+
9 Data+
10 Data+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
COM3 RS485 2W
PLC RS485 2W
9P D-Sub Female
9P D-Sub Female
Terminal
7 RX-
4 Data-
11 Data-
6 RX+
1 Data+
10 Data+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W
Terminal
1 RX-
7 Data-
11 Data-
2 RX+
8 Data+
10 Data+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W
Terminal
1 RX-
6 Data-
11 Data-
2 RX+
9 Data+
10 Data+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W
Terminal
1 RX-
6 Data-
11 Data-
2 RX+
9 Data+
10 Data+
5 GND
5 GND
730
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
PLC RS485 2W
Terminal
1 RX-
7 Data-
11 Data-
2 RX+
8 Data+
10 Data+
5 GND
5 GND
PLC RS485 4W
9P D-Sub Male
Terminal
1 RX-
12 TX-
2 RX+
13 TX+
3 TX-
11 RX-
4 TX+
10 RX+
5 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
PLC RS485 4W
Terminal
7 RX-
12 TX-
6 RX+
13 TX+
9 TX-
11 RX-
8 TX+
10 RX+
5 GND
MT8000iE/MT8000XE series except MT8050iE
COM1 RS485 4W
9P D-Sub Male
COM2 RS485 4W
9P D-Sub Male
PLC RS485 4W
Terminal
1 RX-
1 RX-
12 TX-
2 RX+
2 RX+
13 TX+
3 TX-
3 TX-
11 RX-
4 TX+
4 TX+
10 RX+
5 GND
5 GND
731
PLC RS485 4W
Terminal
1 RX-
12 TX-
2 RX+
13 TX+
3 TX-
11 RX-
4 TX+
10 RX+
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
PLC RS485 4W
Terminal
1 RX-
12 TX-
2 RX+
13 TX+
3 TX-
11 RX-
4 TX+
10 RX+
5 GND
Etehernet cable:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Jan/25/2013
Driver released
732
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
19200
Data bits
Parity
None
Stop bits
10
10 ~ 100
Notes
*Note
PLC Setting:
Communication mode
1.
733
2.
Export Tag data to CSV file. ( [Tools] [Export] [Tags and Logic Comments] )
Note: The separator character in CSV file must be a comma , otherwise the file is invalid.
The directory of changing system settings: [Control Panel] [Date, Time, Language,
and Regional Options] [Change the format of numbers, dates, and times]
[Customize] [List separator]. Please select , and export CSV file after setting.
734
3.
Open EasyBuilder project file, select the driver and set communication parameter.
Click [Data Type] to open [Structure Editor] and edit the data type of the tags.
735
4.
Step 1
Right click on [Structure Editor] [User-Defined] to add a [new data type].
736
Step 2
After adding all Program Tags, click [OK] [Save] [Exit] to leave the editor dialog.
737
5.
In [System Parameter Settings], click [Import Tag], select the csv file. After
importing a message window is displayed.
6.
738
Device Address:
PLC Data Type Name
Bit/Word
Memo
BOOL
Boolean
Bit object
INT
Integer
-32768 ~ 32767
DINT
Double Integer
32-bit signed
-231 ~ (231-1)
REAL
32-bit Float
IEEE 754
BitArray
SINT
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TD
3 TX
7 TX
2 RD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TD
3 TX
4 TX
7 TX
2 RD
5 GND
5 GND
5 GND
5 GND
739
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TD
6 TX
2 RD
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
June/2/2011
Driver released.
740
Rockwell CompactLogix/FlexLogix
Supported Series: Rockwell ControlLogix, CompactLogix, FlexLogix CH0 DF1.
Website: http://www.ab.com
HMI Setting:
Parameters
Recommended
Options
PLC type
Rockwell CompactLogix/FlexLogix
PLC I/F
RS232
Baud rate
19200
Data bits
Parity
None
Stop bits
Notes
1-31
PLC Setting:
Communication mode
741
Create a Tag:
The name format must be 4 chars. For example: B003, T004, C005, N007, and F008.
Two or three chars are not available. For example: B03 or B3.
742
Device Address:
Bit/Word
Device type
Format
Range
Memo
B_BOOL
FFFDDDdd
0 ~ 25525515
N_BOOL
FFFDDDdd
0 ~ 25525515
DW
Tx.ACC
FFFDDD
0 ~ 255255
DW
Tx.PRE
FFFDDD
0 ~ 255255
DW
Nx_INT
FFFDDD
0 ~ 255255
Bx_INT
FFFDDD
0 ~ 255255
DW
Cx.ACC
FFFDDD
0 ~ 255255
DW
Cx.PRE
FFFDDD
0 ~ 255255
F8_REAL
DDD
0 ~ 255
Fx_REAL
FFFDDD
0 ~ 255255
743
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TD
3 TX
7 TX
2 RD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TD
3 TX
4 TX
7 TX
2 RD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TD
6 TX
2 RD
5 GND
5 GND
744
Driver Version:
Version
Date
V1.50
Dec/30/2008
Description
745
Rockwell DF1
Supported Series: Rockwell MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5/01, 5/02,
5/03, 5/04, 5/05.
Website: http://www.ab.com
Note: Allen-Bradley DF1 driver uses CRC checksum.
HMI Setting:
Parameters
Recommended
Options
PLC type
Rockwell DF1
PLC I/F
RS232
Baud rate
19200
Data bits
Parity
None
Stop bits
Notes
1-31
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
I1
0 ~ 25515
Input (I)
O0
DDDdd
DDDdd
0 ~ 25515
Output (O)
B3
DDDdd
0 ~ 25515
B10 ~ 13
DDDdd
0 ~ 25515
S_Bit
DDDdd
0 ~ 25515
Bfn
FFFDDDdd
0 ~ 25525515
NfnBit
FFFDDDdd
0 ~ 25525515
T4SV
DDD
0 ~ 255
T4PV
DDD
0 ~ 255
C5SV
DDD
0 ~ 255
746
Format
Range
Memo
C5PV
DDD
0 ~ 255
TfnSV
FFFDDD
0 ~ 255255
TfnPV
FFFDDD
0 ~ 255255
CfnSV
FFFDDD
0 ~ 255255
CfnPV
FFFDDD
0 ~ 255255
N7
DDD
0 ~ 255
N10 ~ 15
DDD
0 ~ 255
Nfn
FFFDDD
0 ~ 255255
DDD
0 ~ 255
Status (S)
F8
DDD
0 ~ 255
Ffn
FFFDDD
0 ~ 255255
Lfn
FFFDDD
0 ~ 255255
String
STfn
DDD.DDD.DD
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 8P Mini-DIN: MicroLogix 1000, 1100, 1200, 1400, 1500
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
MicroLogix RS232 8P
Mini-DIN Male
2 RX
8 RX
7 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
2 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
MicroLogix RS232 8P
Mini-DIN Male
2 RX
7 TXD
3 TX
4 RXD
5 GND
2 GND
MicroLogix RS232 8P
Mini-DIN Male
2 RX
7 TXD
3 TX
4 RXD
5 GND
2 GND
747
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
MicroLogix RS232 8P
Mini-DIN Male
2 RX
6 RX
8 RX
7 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
2 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
MicroLogix RS232 8P
Mini-DIN Male
9 RX
7 TXD
6 TX
4 RXD
5 GND
2 GND
View from the
soldering point
of a cable.
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TD
3 TX
7 TX
2 RD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
D-Sub Female
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
748
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TD
3 TX
4 TX
7 TX
2 RD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TD
6 TX
2 RD
5 GND
5 GND
Driver Version:
Version
Date
Description
V2.20
Jan/05/2010
V2.50
Oct/14/2012
V2.70
Jun/27/2013
749
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
19200
Data bits
Parity
None
Stop bits
Notes
1-31
PLC Setting:
Communication mode
Device Address:
Bit/Word
Range
Memo
I1
DDDdd
0 ~ 25515
Input (I)
O0
DDDdd
0 ~ 25515
Output (O)
B3
DDDdd
0 ~ 25515
B10 ~ 13
DDDdd
0 ~ 25515
S_Bit
DDDdd
0 ~ 25515
Bfn
FFFDDDdd
0 ~ 25525515
NfnBit
FFFDDDdd
0 ~ 25525515
T4SV
DDD
0 ~ 255
T4PV
DDD
0 ~ 255
750
Bit/Word
Range
Memo
C5SV
DDD
0 ~ 255
C5PV
DDD
0 ~ 255
TfnSV
FFFDDD
0 ~ 255255
TfnPV
FFFDDD
0 ~ 255255
CfnSV
FFFDDD
0 ~ 255255
CfnPV
FFFDDD
0 ~ 255255
N7
DDD
0 ~ 255
N10~15
DDD
0 ~ 255
Nfn
FFFDDD
0 ~ 255255
DDD
0 ~ 255
Status (S)
F8
DDD
0 ~ 255
Ffn
FFFDDD
0 ~ 255255
Lfn
FFFDDD
0 ~ 255255
STfn
DDD.DDD.DD
0 ~ 255.255.40
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 8P Mini-DIN: MicroLogix 1000, 1100, 1200, 1500
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
MicroLogix RS232 8P
Mini-DIN Male
2 RX
8 RX
7 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
2 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
MicroLogix RS232 8P
Mini-DIN Male
2 RX
7 TXD
3 TX
4 RXD
5 GND
2 GND
MicroLogix RS232 8P
Mini-DIN Male
2 RX
7 TXD
3 TX
4 RXD
5 GND
2 GND
751
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
MicroLogix RS232 8P
Mini-DIN Male
2 RX
6 RX
8 RX
7 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
2 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
MicroLogix RS232 8P
Mini-DIN Male
9 RX
7 TXD
6 TX
4 RXD
5 GND
2 GND
View from the
soldering point
of a cable.
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TD
3 TX
7 TX
2 RD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
D-Sub Female
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
752
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TD
3 TX
4 TX
7 TX
2 RD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TD
6 TX
2 RD
5 GND
5 GND
Driver Version:
Version
Date
Description
V2.70
Sep/05/2013
753
Rockwell DH485
Supported Series: Rockwell MicroLogix 1000, 1100, 1200, 1400, 1500, SLC 5/01, 5/02,
5/03, 5/04, 5/05.
Website: http://www.ab.com
HMI Setting:
Parameters
Recommended
PLC type
Rockwell DH485
PLC I/F
RS485 2W
RS232
Baud rate
19200
9600, 19200
Data bits
Parity
Even
Stop bits
1-31
Online simulation
YES
NO
Options
Notes
PLC Setting:
Communication mode
754
Device Address:
Bit/Word Device type
Format
Range
Memo
I1
DDDdd
0 ~ 25515
Input (I)
O0
DDDdd
0 ~ 25515
Output (O)
B3
DDDdd
0 ~ 25515
B10 ~ 13
DDDdd
0 ~ 25515
Bfn
FFFDDDdd 0 ~ 25525515
NfnBit
FFFDDDdd 0 ~ 25525515
S_Bit
DDDdd
0 ~ 25515
Status file
T4SV
DDD
0 ~ 255
T4PV
DDD
0 ~ 255
C5SV
DDD
0 ~ 255
C5PV
DDD
0 ~ 255
TfnSV
FFFDDD
0 ~ 255255
TfnPV
FFFDDD
0 ~ 255255
CfnSV
FFFDDD
0 ~ 255255
CfnPV
FFFDDD
0 ~ 255255
F8
DDD
0 ~ 255
N7
DDD
0 ~ 255
N10 ~ 15
DDD
0 ~ 255
Nfn
FFFDDD
0 ~ 255255
DDD
0 ~ 255
Wiring Diagram:
The following is the view from the soldering point of a cable.
RS-485: SLC500 Fixed type, SLC5/01, 02, 03 CH1.
HMI cant connect to 1747-AIC peripheral port.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
AB SLC500 DH485
RJ45 Male
1 RX-
6 Data-
2 SDB
2 RX+
9 Data+
1 SDA
5 GND
5 GND
7 GND
755
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
AB SLC500 DH485
RJ45 Male
7 RX-
4 Data-
2 SDB
6 RX+
1 Data+
1 SDA
5 GND
5 GND
7 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
AB SLC500 DH485
RJ45 Male
1 RX-
7 Data-
2 SDB
2 RX+
8 Data+
1 SDA
5 GND
9 GND
7 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
AB SLC500 DH485
RJ45 Male
1 RX-
6 Data-
2 SDB
2 RX+
9 Data+
1 SDA
5 GND
5 GND
7 GND
COM3 RS485 2W
9P D-Sub Male
AB SLC500 DH485
RJ45 Male
1 RX-
6 Data-
2 SDB
2 RX+
9 Data+
1 SDA
5 GND
5 GND
7 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
COM3 RS485 2W
AB SLC500 DH485
9P D-Sub Female
9P D-Sub Female
RJ45 Male
1 RX-
7 Data-
2 SDB
2 RX+
8 Data+
1 SDA
5 GND
5 GND
7 GND
756
COM3 RS232 9P
D-Sub Female
MicroLogix RS232 8P
Mini-DIN Male
2 RX
8 RX
7 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
2 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
MicroLogix RS232 8P
Mini-DIN Male
2 RX
7 TXD
3 TX
4 RXD
5 GND
2 GND
MicroLogix RS232 8P
Mini-DIN Male
2 RX
7 TXD
3 TX
4 RXD
5 GND
2 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
MicroLogix RS232 8P
Mini-DIN Male
2 RX
6 RX
8 RX
7 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
2 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
MicroLogix RS232 8P
Mini-DIN Male
9 RX
7 TXD
6 TX
4 RXD
5 GND
2 GND
View from the
soldering point
of a cable.
757
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TD
3 TX
7 TX
2 RD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TD
3 TX
4 TX
7 TX
2 RD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TD
6 TX
2 RD
5 GND
5 GND
758
Driver Version:
Version
Date
V1.20
Apr/17/2009
Description
759
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
44818
Notes
PLC Setting:
RSLogix 5000 setting
Create a Tag:
The name format must be 4 chars. For example: B003, T004, C005, N007, and F008.
Two or three chars are not available. For example: B03 or B3.
760
Device Address:
Bit/Word Device type Format
Range
Memo
Bx_BOOL
FFFDDDdd 0 ~ 25525515
Nx_BOOL
FFFDDDdd 0 ~ 25525515
Bx_INT
FFFDDD
0 ~ 255255
Nx_INT
FFFDDD
0 ~ 255255
DW (F)
F8_REAL
DDD
0 ~ 255
DW (F)
Fx_REAL
FFFDDD
0 ~ 255255
DW
Cx.ACC
FFFDDD
0 ~ 255255
DW
Cx.PRE
FFFDDD
0 ~ 255255
DW
Tx.ACC
FFFDDD
0 ~ 255255
DW
Tx.PRE
FFFDDD
0 ~ 255255
DW
Lx.DINT
FFFDDD
0 ~ 255255
761
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V1.30
Dec/30/2008
V1.50
Mar/6/2012
Description
Added register: Lx.DINT
762
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
44818
PLC Setting:
1.
763
Notes
2.
3.
Export Tag data to CSV file. ( [Tools] [Export] [Tags and Logic Comments] )
Note: The separator character in CSV file must be a comma , otherwise the file is invalid.
The directory of changing system settings: [Control Panel] [Date, Time, Language,
and Regional Options] [Change the format of numbers, dates, and times]
[Customize] [List separator]. Please select , and export CSV file after setting.
764
4.
Open EasyBuilder project file, select the driver and set IP address. Click [Data Type]
to open [Structure Editor] and edit the data type of the tags.
765
5.
Step 1
Right click on [Structure Editor] [User-Defined] to add a [new data type].
766
Step 2
After adding all Program Tags, click [OK] [Save] [Exit] to leave the editor dialog.
767
6.
In [System Parameter Settings], click [Import Tag], select the csv file. After
importing a message window is displayed.
7.
768
Device Address:
PLC data type name
Bit/Word
Memo
BOOL
Boolean
Bit object
INT
Integer
-32768 ~ 32767
DINT
Double Integer
32-bit signed
REAL
32-bit Float
-231 ~ (231-1)
IEEE 754
BitArray
SINT
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
V1.10
Aug/25/2010
Description
769
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
44818
PLC Setting:
1.
770
Notes
2.
3.
Export Tag data to CSV file. ( [Tools] [Export] [Tags and Logic Comments] )
Note: The separator character in CSV file must be a comma , otherwise the file is invalid.
The directory of changing system settings: [Control Panel] [Date, Time, Language,
and Regional Options] [Change the format of numbers, dates, and times]
[Customize] [List separator]. Please select , and export CSV file after setting.
771
4.
Open EasyBuilder project file, select the driver and set IP address. Click [Data Type]
to open [Structure Editor] and edit the data type of the tags.
772
5.
Step 1
Right click on [Structure Editor] [User-Defined] to add a [new data type].
773
Step 2
After adding all Program Tags, click [OK] [Save] [Exit] to leave the editor dialog.
774
6.
In [System Parameter Settings], click [Import Tag], select the csv file. After
importing a message window is displayed.
7.
775
Device Address:
PLC data type name
Bit/Word
Memo
BOOL
Boolean
Bit object
INT
Integer
DINT
Double Integer
32-bit signed
REAL
32-bit Float
BitArray
SINT
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
V1.10
Oct/05/2010
Description
776
-231 ~ (231-1)
IEEE 754
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
44818
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
Memo
I1
DDDdd
0 ~ 25515
Input (I)
O0
DDDdd
0 ~ 25515
Output (O)
I1n_Bit
SSEEdd
0 ~ 303115
O0n_Bit
SSEEdd
0 ~ 303115
B3
DDDdd
0 ~ 25515
S_Bit
DDDDDDdd
0 ~ 25525515
Status file
Bfn
FFFDDDdd
0 ~ 25525515
NfnBit
FFFDDDdd
0 ~ 25525515
I1n
SSEE
0 ~ 3031
O0n
SSEE
0 ~ 3031
T4SV
DDD
0 ~ 255
T4PV
DDD
0 ~ 255
C5SV
DDD
0 ~ 255
C5PV
DDD
0 ~ 255
777
Bit/Word
Device type
Format
Range
Memo
TfnSV
FFFDDD
0 ~ 255255
TfnPV
FFFDDD
0 ~ 255255
CfnSV
FFFDDD
0 ~ 255255
CfnPV
FFFDDD
0 ~ 255255
DDD
0 ~ 255
N7
DDD
0 ~ 255
Nfn
FFFDDD
0 ~ 255255
DW (F)
F8
DDD
0 ~ 255
DW (F)
Ffn
FFFDDD
0 ~ 255255
DW
Lfn
FFFDDD
0 ~ 255255
STfn
DDD.DDD.DD 0 ~ 255.255.40
Wiring Diagram:
Direct connect (crossover cable):
COM
CPU
PWR
RS232 DF1
Ethernet
Crossover cable
MT8000
1761-NET-ENI
Wire Color
Wire Color
1 TX+
White/Orange
White/Green
3 RX+
2 TX-
Orange
Green
6 RX-
3 RX+
White/Green
White/Orange
1 TX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Orange
2 TX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
778
Through a hub:
Switch Hub
MT8000
SLC 500
SLC 500
SLC 500
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V2.00
Dec/21/2009
V2.10
Oct/14/2012
V2.20
Set/06/2013
779
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
Ethernet
Port no.
44818
Bool
bit
Byte
8-bit
DInt
Real
32-bit Float
32-bit
UDInt
32-bit
String
ASCII Object
Length=word
SInt
USInt
Word
Int
UInt
DWord
780
Memo
8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit
3. Click [Paste].
781
4. Launch Connected Components Workbench software, select and copy the tags
under [Global Variables]. Note that the IO address cannot be copied and can only be
manually created.
6. Enter [Name], click [OK], and then click [Save to default]. The tags are now
successfully created.
782
Building Struct:
1. After importing the tags, the data type of Struct is shown as in the following figure,
please build the corresponding tag under Struct-Defined.
3. Enter the [Data type] in the [Name] field, and then click [Add].
783
4. Enter the same information in the [Name] and [Data Type] fields as shown in the
original factory software, and then click [OK].
5. Upon completion click [OK] and then click [Save to default] to finish building Struct.
784
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Jun/08/2014
Driver released.
785
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
38400
Data bits
Parity
None
Stop bits
1200 ~ 38400
None,Even,Odd
0 ~ 254
PLC Setting:
786
Notes
Bool
bit
Byte
8-bit
SInt
8-bit
USInt
8-bit
Word
16-bit
Int
16-bit
UInt
16-bit
DWord
32-bit
DInt
32-bit
Real
32-bit Float
32-bit
UDInt
32-bit
String
ASCII Object
Length=word
787
Memo
3. Click [Paste].
788
4. Launch Connected Components Workbench software, select and copy the tags
under [Global Variables]. Note that the IO address cannot be copied and can only be
manually created.
6. Enter [Name], click [OK], and then click [Save to default]. The tags are now
successfully created.
789
Building Struct:
1. After importing the tags, the data type of Struct is shown as in the following figure,
please build the corresponding tag under Struct-Defined.
3. Enter the [Data type] in the [Name] field, and then click [Add].
790
4. Enter the same information in the [Name] and [Data Type] fields as shown in the
original factory software, and then click [OK].
5. Upon completion click [OK] and then click [Save to default] to finish building Struct.
791
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
8 RX
7 TXD
3 TX
7 TX
4 RXD
5 GND
5 GND
2 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
7 TXD
3 TX
4 RXD
5 GND
2 GND
RS232 8P Mini-DIN
Male
2 RX
7 TXD
3 TX
4 RXD
5 GND
2 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 8P Mini-DIN
Male
2 RX
6 RX
8 RX
7 TXD
3 TX
4 TX
7 TX
4 RXD
5 GND
5 GND
5 GND
2 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
9 RX
7 TXD
6 TX
4 RXD
5 GND
2 GND
View from the
soldering point
of a cable.
792
Driver Version:
Version
Date
Description
V1.00
Aug/29/2014
Driver released.
793
Rockwell PLC5
Website: http://www.ab.com
Note: Rockwell PLC5 driver uses CRC checksum.
HMI Setting:
Parameters
Recommended
Options
PLC type
Rockwell PLC5
PLC I/F
RS232
Baud rate
19200
9600, 19200
Data bits
Parity
Even
Stop bits
Notes
1-31
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type Format
Range
Memo
I1
DDDdd
0 ~ 25515
Input (I)
O0
DDDdd
0 ~ 25515
Output (O)
B3
DDDdd
0 ~ 99915
B10 ~ 13
DDDdd
0 ~ 99915
S_Bit
DDDDDDdd 0 ~ 25599915
Bfn
FFFDDDdd
0 ~ 25599915
NfnBit
FFFDDDdd
0 ~ 25599915
T4SV
DDD
0 ~ 999
794
Range
Memo
T4PV
DDD
0 ~ 999
C5SV
DDD
0 ~ 999
C5PV
DDD
0 ~ 999
TfnSV
FFFDDD
0 ~ 255999
TfnPV
FFFDDD
0 ~ 255999
CfnSV
FFFDDD
0 ~ 255999
CfnPV
FFFDDD
0 ~ 255999
N7
DDD
0 ~ 999
N10 ~ 15
DDD
0 ~ 999
Nfn
FFFDDD
0 ~ 255999
DDD
0 ~ 255
F8
DDD
0 ~ 999
Ffn
FFFDDD
0 ~ 255999
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 25P D-Sub: PLC5 CPU CH0
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TD
3 TX
7 TX
3 RD
5 GND
5 GND
7 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TD
3 TX
3 RD
5 GND
7 GND
2 RX
2 TD
3 TX
3 RD
5 GND
7 GND
795
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TD
3 TX
4 TX
7 TX
3 RD
5 GND
5 GND
5 GND
7 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TD
6 TX
3 RD
5 GND
7 GND
Note:
The default error checking of Rockwell PLC5 is BCC, whereas our driver is CRC.
796
Access [Channel Configuration] from RSLogix5, under Channel 0 tab, please select CRC
for [Error Detect].
Driver Version:
Version
Date
V1.20
Apr/17/2009
Description
797
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
None
Stop bits
225
0 ~ 255
Notes
Device Address:
Bit/Word
Device type
Format
Range
DDDdd
0 ~ 25515
DDDdd
0 ~ 25515
DDDDdd
0 ~ 199915
DDDdd
0 ~ 25515
Keep Contact
DDDdd
0 ~ 99115
Special Contact
TC
DDD
0 ~ 255
Timer/Counter
DDDD
0 ~ 7999
Data Register
SV
DDD
0 ~ 255
PV
DDD
0 ~ 255
SR
DDD
0 ~ 255
Special Register
WR
DDD
0 ~ 255
WL
DDD
0 ~ 255
WM
DDDD
0 ~ 1999
WK
DDD
0 ~ 255
WF
DDD
0 ~ 991
798
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
3 RXD
5 GND
5 GND
799
Driver Version:
Version
Date
Description
V1.00
Dec/30/2008
Driver released.
V1.20
Jun/27/2012
800
RS Automation X8 Series
Supported Series: RS-X8 Series PLC
Website: http://www.rsautomation.biz/
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
RS Automation X8 Series
PLC I/F
RS232/Ethernet
RS232/ Ethernet
Baud rate
115200
9600~115200
Data bits
7,8
Parity
None
None,Even,ODD
Stop bits
1,2
Port no.
50000
0 ~ 255
PLC Setting:
Communication mode
Xnet Slave
Device Address:
Bit/Word Device type
Format
Range
Memo
Y_bit
DD.DDDdd
0 ~ 96.25515
Output
X_bit
DD.DDDdd
0 ~ 96.25515
Input
SR_bit
DDDdd
0 ~ 12715
Status
B_bit
DDDD.DDDDdd 0 ~ 1535.153515
Bit
N_bit
DDDD.DDDDdd 0 ~ 1535.153515
Integer
A_bit
DDDD.DDDDdd 0 ~ 1535.153515
ASCII
TM_Done
DDDD.DDDDdd 0 ~ 1535.153515
Timer_Done
CT_Done
DDDD.DDDDdd 0 ~ 1535.153515
Counter_Done
CR_Done
DDDD.DDDDdd 0 ~ 1535.153515
Control_Done
DD.DDD
0 ~ 96.255
Output
DD.DDD
0 ~ 96.255
Input
SR
DDD
0 ~ 127
Status
DDDD.DDDD
0 ~ 1535.1535
Bit
DDDD.DDDD
0 ~ 1535.1535
Integer
801
Format
Range
Memo
DDDD.DDDD
0 ~ 1535.1535
ASCII
ST_Length
DDDD.DDD
0 ~ 1535.779
String_Length
ST_Data
DDDD.DDD.DD
0 ~ 1535.779.42
String_Data
CR_Length
DDDD.DDDD
0 ~ 1535.1535
Control_Length
CR_Pos
DDDD.DDDD
0 ~ 1535.1535
Control_Postion
DDDD.DDDD
0 ~ 1535.1535
Float
DDDD.DDDD
0 ~ 1535.1535
Long
TM_Preset
DDDD.DDDD
0 ~ 1535.1535
Timer_Preset
TM_Acc
DDDD.DDDD
0 ~ 1535.1535
Timer_Accumulator
CT_Preset
DDDD.DDDD
0 ~ 1535.1535
Counter_Preset
CT_Acc
DDDD.DDDD
0 ~ 1535.1535
Counter_Accumulator
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
COM3 RS232 9P
RS232 9P D-Sub
D-Sub Female
D-Sub Female
Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
RS232 9P D-Sub
Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
802
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
Etehernet cable:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Oct/3/2012
Driver released.
803
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
RS232, RS485
Baud rate
9600
9600, 19200
Data bits
7,8
Parity
Even
Stop bits
0-255
Notes
PDS driver
Device Address:
Bit/Word
Device type
Format
Range
Flag
DDDD
0 ~ 8191
Output
DDD
0 ~ 511
Input
DDD
0 ~ 511
Register
DDDD
0 ~ 4095
Counter
DDDD
0 ~ 1599
Timer
DDDD
0 ~ 1599
Reg_Float
DDDD
0 ~ 4095
Reg_Word
DDDD
0 ~ 4095
804
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
6 DSR
7 RTS
8 CTS
short
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
6 DSR
7 RTS
8 CTS
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
6 DSR
7 RTS
8 CTS
Driver Version:
Version
Date
V1.02
Dec/30/2008
Description
805
short
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
RS232, RS485
Baud rate
9600
Data bits
7,8
Parity
None
Stop bits
0-255
Notes
PDS driver
PLC Setting:
Communication mode
9600,N,8,1 (default)
RS232
RS485 2W
1.
806
2.
3.
4.
Go to Online Setting.
807
5.
Select PGU.
6.
Go to Device Configurator.
808
7.
8.
Select RS232 (PGU) in Type and then right click mouse on Onboard
Communications and select Properties.
809
9.
10. Set parameters in S-Bus Mode and Timing then upload to PLC.
810
11. Go to Online Settings >> Open to select S-Bus for finishing the PLC settings.
Device Address:
Bit/Word Device type
Format
Range
Flag
DDDD
0 ~ 8191
Output
DDDD
0 ~ 1023
Input
DDDD
0 ~ 1023
Reg_Bit
DDDDdd
0 ~ 1638331
DW
Register
DDDDD
0 ~ 16383
DW
Counter
DDDD
0 ~ 1599
DW
Timer
DDDD
0 ~ 1599
DW
Reg_Float
DDDDD
0 ~ 16383
DW
DBn
DDDDDDDDD 0 ~ 536016383
811
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
SAIA PCD PGU Port
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
812
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
11 (29)
2 RX+
9 Data+
12 (28)
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
11 (29)
6 RX+
1 Data+
12 (28)
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
11 (29)
2 RX+
8 Data+
12 (28)
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
11 (29)
2 RX+
9 Data+
12 (28)
5 GND
5 GND
813
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
11 (29)
2 RX+
9 Data+
12 (28)
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
1 RX-
7 Data-
11 (29)
2 RX+
8 Data+
12 (28)
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.40
Jun/21/2012
814
HMI Setting:
Parameters
Recommended Options
PLC type
PLC I/F
Ethernet
Port no.
5050
Notes
PLC Setting:
815
Device Address:
Bit/Word Device type
Format
Range
Flag
DDDD
0 ~ 8191
Output
DDDD
0 ~ 1023
Input
DDDD
0 ~ 1023
Reg_Bit
DDDDdd
0 ~ 1638331
DBn_Bit
DDDDDDDdd
0 ~ 399938331
DW
Register
DDDDD
0 ~ 16383
DW
Counter
DDDD
0 ~ 1599
DW
Timer
DDDD
0 ~ 1599
DW
Reg_Float
DDDDD
0 ~ 16383
DW
DBn
DDDDDDDDD 0 ~ 536016383
DW
DB_String
DDDDDDDDD 0 ~ 536016383
DW
R_String
DDDDD
DW
DB_Float
DDDDDDDDD 0 ~ 536016383
0 ~ 16383
816
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.40
Jun/21/2012
V1.50
Sep/24/2012
817
Samsung SPC-10
Supported Series: Samsung SPC-10
Website: http://www.samsungelectronics.com/factory_automation/controller/plc/
HMI Setting:
Parameters
Recommended
PLC type
Samsung SPC-10
PLC I/F
RS485 2W
Baud rate
9600
Data bits
None
Parity
Stop bits
192
Options
Notes
Device Address:
Bit/Word Device type
Format
Range
DDDDdd
0 ~ 999915
DDDDdd
0 ~ 999915
DDDDdd
0 ~ 999915
DDDDdd
0 ~ 999915
DDDD
0 ~ 9999
818
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
6 TR-
2 RX+
9 Data+
7 TR+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P Mini-DIN
Male
7 RX-
4 Data-
6 TR-
6 RX+
1 Data+
7 TR+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
7 Data-
6 TR-
2 RX+
8 Data+
7 TR+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
6 TR-
2 RX+
9 Data+
7 TR+
5 GND
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
6 TR-
2 RX+
9 Data+
7 TR+
5 GND
5 GND
5 GND
819
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P Mini-DIN
Male
1 RX-
7 Data-
6 TR-
2 RX+
8 Data+
7 TR+
5 GND
5 GND
5 GND
View from the
soldering point
of a cable.
Driver Version:
Version
Date
V1.00
May/19/2009
Description
820
SCENE6 Controller
HMI Setting:
Parameters
Recommended
PLC type
SCENE6 Controller
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
None
Stop bits
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
Word
DD
0 ~ 99
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 Terminal
2 RX
8 RX
TD
3 TX
7 TX
RD
5 GND
5 GND
GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 Terminal
2 RX
TD
3 TX
RD
5 GND
GND
821
RS232 Terminal
2 RX
TD
3 TX
RD
5 GND
GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 Terminal
2 RX
6 RX
8 RX
TD
3 TX
4 TX
7 TX
RD
5 GND
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 Terminal
9 RX
TD
6 TX
RD
5 GND
GND
Driver Version:
Version
Date
V1.00
Aug/24/2009
Description
822
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS232
Baud rate
38400
Data bits
Parity
Stop bits
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
IX
DDDDDo
0 ~ 655357
Input %IX
QX
DDDDDo
0 ~ 655357
Output %QX
MX
DDDDDo
0 ~ 655357
%MX
IW
DDDDD
0 ~ 65535
%IW
QW
DDDDD
0 ~ 65535
%QW
MW
DDDDD
0 ~ 65535
%MW
DW
ID
DDDDD
0 ~ 65535
%ID
DW
QD
DDDDD
0 ~ 65535
%QD
DW
MD
DDDDD
0 ~ 65535
%WD
823
Wiring Diagram:
COM3 RS232 9P
D-Sub Female
Schleicher XCS20
RS232 9P D-Sub Male
2 RX
8 RX
3 TD
3 TX
7 TX
2 RD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
Schleicher XCS20
RS232 9P D-Sub Male
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
Schleicher XCS20
D-Sub Female
2 RX
3 TD
3 TX
2 RD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
Schleicher XCS20
RS232 9P D-Sub Male
2 RX
6 RX
8 RX
3 TD
3 TX
4 TX
7 TX
2 RD
5 GND
5 GND
5 GND
5 GND
824
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
Schleicher XCS20
RS232 9P D-Sub Male
9 RX
3 TD
6 TX
2 RD
5 GND
5 GND
Driver Version:
Version
Date
V1.10
Feb/26/2010
Description
825
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
Ethernet
Port no.
20547
Options
Notes
PLC Setting:
A variable must be created for HMI access.
Device Address:
Bit/Word
Device type
Format
Range
Memo
IX
DDDDDo
0 ~ 655357
Input %IX
QX
DDDDDo
0 ~ 655357
Output %QX
MX
DDDDDo
0 ~ 655357
%MX
IW
DDDDD
0 ~ 65535
%IW
QW
DDDDD
0 ~ 65535
%QW
MW
DDDDD
0 ~ 65535
%MW
DW
ID
DDDDD
0 ~ 65535
%ID
DW
QD
DDDDD
0 ~ 65535
%QD
DW
MD
DDDDD
0 ~ 65535
%WD
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
RS232 9P D-Sub
Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
827
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 9P D-Sub
Female
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
RS485 4W Terminal
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W Terminal
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
828
COM2 RS485 4W
9P D-Sub Male
RS485 4W Terminal
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
RS485 4W Terminal
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
RS485 4W Terminal
9P D-Sub Female
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
Driver Version:
Version
Date
Description
V1.00
Nov/30/2009
Driver released.
V1.10
Jun/28/2010
829
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
9600
Data bits
Parity
Even
Stop bits
Notes
Device Address:
Bit/Word Device type
Format
Range
BIT
HHHHo
0 ~ FFFF7
WORD
HHHH
0 ~ FFFF
DW
DWORD
HHHH
0 ~ FFFF
Byte
BYTE
HHHH
0 ~ FFFF
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
830
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
RS232 9P D-Sub
Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
Driver Version:
Version
Date
V1.10
Apr/04/2012
Description
831
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485
RS232/RS485
Baud rate
9600
9600~115200
Data bits
7,8
Parity
Even
Stop bits
1,2
0-255
Online simulator
Options
YES
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
%M
DDDDD
0 ~ 65535
Output bit
1x
DDDDD
0 ~ 65535
3x_Bit
DDDDDdd
0 ~ 6553515
B
B
4x_Bit
DDDDDdd
0x_multi_coils DDDDD
0 ~ 6553515
0 ~ 65535
3x
DDDDD
0 ~ 65535
%MW
DDDDD
0 ~ 65535
Output Register
DW
5x
DDDDD
0 ~ 65535
6x
DDDDD
0 ~ 65535
832
Wiring Diagram:
The following is the view from the soldering point of a cable.
RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 9P D-Sub
Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
RS232 9P D-Sub
D-Sub Female
Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
833
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
2 B-
2 RX+
9 Data+
1 A+
5 GND
5 GND
5 DTP
7 GND
short
cMT/mTV series
COM2 RS485 2W COM3 RS485 2W
9P D-Sub Female 9P D-Sub Female
RS485 2W 8P Mini-DIN
Male
7 RX-
4 Data-
2 B-
6 RX+
1 Data+
1 A+
5 GND
5 GND
5 DTP
7 GND
short
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W COM3 RS485 2W
RS485 2W 8P Mini-DIN
9P D-Sub Male
9P D-Sub Male
Male
1 RX-
7 Data-
2 B-
2 RX+
8 Data+
1 A+
5 GND
9 GND
5 DTP
7 GND
short
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
2 B-
2 RX+
9 Data+
1 A+
5 GND
5 GND
5 DTP
7 GND
short
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
2 B-
2 RX+
9 Data+
1 A+
5 GND
5 GND
5 DTP
7 GND
834
short
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P Mini-DIN
Male
1 RX-
7 Data-
2 B-
2 RX+
8 Data+
1 A+
5 GND
5 GND
5 DTP
7 GND
short
View from the
soldering point
of a cable.
COM3 RS485 2W
9P D-Sub Male
RS485 2W 3P Terminal
1 RX-
6 Data-
B-
2 RX+
9 Data+
A+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 3P Terminal
7 RX-
4 Data-
B-
6 RX+
1 Data+
A+
5 GND
5 GND
GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male
RS485 2W 3P Terminal
1 RX-
7 Data-
B-
2 RX+
8 Data+
A+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male
RS485 2W 3P Terminal
1 RX-
6 Data-
B-
2 RX+
9 Data+
A+
5 GND
5 GND
GND
835
COM3 RS485 2W
9P D-Sub Male
RS485 2W 3P Terminal
1 RX-
6 Data-
B-
2 RX+
9 Data+
A+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 3P Terminal
1 RX-
7 Data-
B-
2 RX+
8 Data+
A+
5 GND
5 GND
GND
Driver Version:
Version
Date
V1.30
Aug/26/2009
Description
836
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
502
Notes
0~255
PLC Setting:
Ethernet frame format
Ethernet II format
Device Address:
Bit/Word Device type
Format
Range
Memo
%M
DDDDD
0 ~ 65535
Input bit
1x
DDDDD
0 ~ 65535
Output bit
3x_Bit
DDDDDdd
0 ~ 6553515
4x_Bit
DDDDDdd
0 ~ 6553515
6x_Bit
DDDDDdd
0 ~ 6553515
0x_multi_coils DDDDD
0 ~ 65535
3x
DDDDD
0 ~ 65535
Input Register
%MW
DDDDD
0 ~ 65535
Output Register
DW
5x
DDDDD
0 ~ 65535
6x
DDDDD
0 ~ 65535
837
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
V1.40
Aug/27/2009
Description
838
HMI Setting:
Parameters
Recommended Options
PLC type
PLC I/F
(Ethernet)
Ethernet
Port no.
1740
1742
Notes
Use UDP
9. In Tag Manager click Get tag -> Import Tag, and then select the tag file (.xml)
generated by the PLC software.
839
10. When the tags are imported successfully, click [Exit] to leave.
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Mar/15/2016
Driver released
840
Schneider UniTelway
Supported Series: Modicon TSX Micro&Nano&Neza series PLC.
Website: http://www.modicon.com
HMI Setting:
Parameters
Recommended
PLC type
Schneider UniTelway
PLC I/F
RS485 2W
RS232/RS485
Baud rate
19200
9600~115200
Data bits
7,8
Parity
Odd
Stop bits
1, 2
1-8
0-3
Online simulator
Options
YES
Notes
Broadcast command NO
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDD
0 ~ 32767
Internal relay
DDDDD
0 ~ 32767
Auxiliary relay
MW.B
DDDDDdd
MW
DDDDD
0 ~ 32767
841
Data register
Wiring Diagram:
The following is the view from the soldering point of a cable.
TSX37-XX/TSX07-XX CPU : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
7 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P Mini-DIN
Male
7 RX-
4 Data-
2 D-
6 RX+
1 Data+
1 D+
5 GND
5 GND
7 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
COM3 RS485 2W
RS485 2W 8P Mini-DIN
9P D-Sub Male
9P D-Sub Male
Male
1 RX-
7 Data-
2 D-
2 RX+
8 Data+
1 D+
5 GND
9 GND
7 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
7 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P Mini-DIN
Male
1 RX-
6 Data-
2 D-
2 RX+
9 Data+
1 D+
5 GND
5 GND
7 GND
842
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P Mini-DIN
Male
1 RX-
7 Data-
2 D-
2 RX+
8 Data+
1 D+
5 GND
5 GND
7 GND
View from the
soldering point
of a cable.
Driver Version:
Version
Date
V1.30
Sep/24/2009
Description
843
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
19200
Data bits
Parity
None
Stop bits
Notes
Device Address:
Bit/Word Device type
Format
Range
SET_SERVO
SET_DIRECTION
SET_BERAK
RESET
DRIVER_FAULT
SERVO_OFF_ERROR D
BREAK_ON_ERROR
SET_RPM
RPM
CUR_RPM
CUR_ERROR
PARAMETER1_W
0~7
PARAMETER1_R
0~7
844
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
845
Driver Version:
Version
Date
Description
V1.00
Jul/09/2014
Driver released.
846
SEUNGIL AHU
Supported Series: SENUGIL AVDP-NH-K1
Website : http://seungil.en.ec21.com/
HMI Setting:
Parameters
Recommended
PLC type
SEUNGIL AHU
PLC I/F
RS-485 2W
Baud rate
9600
9600 ~ 115200
Data bits
7,8
Parity
None
Stop bits
0 ~ 99
Online simulator
Options
YES
Notes
Device Address:
Bit/Word
Device type
Format
Range
BIT
DDD.DDD.DDDdd
0 ~ 255.255.25515
WORD
DDD.DDD.DDD
0 ~ 255.255.255
847
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 Data-
6 Data-
8 Data-
2 Data+
9 Data+
1 Data+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W Terminal
1 Data-
6 Data-
8 Data-
2 Data+
9 Data+
1 Data+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 Data-
6 Data-
8 Data-
2 Data+
9 Data+
1 Data+
5 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 Data-
6 Data-
8 Data-
2 Data+
9 Data+
1 Data+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 Data-
6 Data-
8 Data-
2 Data+
9 Data+
1 Data+
5 GND
5 GND
848
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W Terminal
1 Data-
6 Data-
Data-
2 Data+
9 Data+
Data+
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
May/31/2016
Driver released.
849
SEW Movilink
Supported Series: SEW Eurodrive series, model MOVITRAC-07 inverter, MovitracB.
Website: http://sg.sew-eurodrive.com/
HMI Setting:
Parameters
Recommended
PLC type
SEW Movilink
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
Even
Stop bits
Options
Notes
0~255
Device Address:
Bit/Word
Device type
Format
Range
INDEX_Bit
DDDDDDDDdd
0 ~ 2552500031
INDEX
DDDDDDDD
0 ~ 25525000
Memo
The MOVITRAC-07 doesnt support Sub indexother series may support, please input 000.
When input D and d, the correct formatSub index 15, Index 8359, Format is 01508359.
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
Movitrac-07 RS485 2W
1 RX-
6 Data-
D- (Green)
2 RX+
9 Data+
D+ (Red)
5 GND
5 GND
850
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
Movitrac-07 RS485 2W
7 RX-
4 Data-
D- (Green)
6 RX+
1 Data+
D+ (Red)
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
Movitrac-07 RS485 2W
1 RX-
7 Data-
D- (Green)
2 RX+
8 Data+
D+ (Red)
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
Movitrac-07 RS485 2W
1 RX-
6 Data-
D- (Green)
2 RX+
9 Data+
D+ (Red)
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
Movitrac-07 RS485 2W
1 RX-
6 Data-
D- (Green)
2 RX+
9 Data+
D+ (Red)
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
COM3 RS485 2W
Movitrac-07 RS485 2W
9P D-Sub Female
9P D-Sub Female
1 RX-
7 Data-
D- (Green)
2 RX+
8 Data+
D+ (Red)
5 GND
5 GND
Driver Version:
Version
Date
V1.31
Jun/25/2010
Description
851
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS-485 2W
Baud rate
115200
Data bits
Parity
None
Stop bits
Online simulator
YES
Options
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
P-1
0~1
P-2
0~1
P-3
0~1
P-4
0~1
P-5
0~1
P-6
0~1
Energy optimizer
P-7
0~1
P-8
0~1
P-9
0~1
P-10
0~1
P-11
0~1
Voltage boost
P-12
0~1
P-13
0~1
Trip log
P-14
0~1
P-15
0~1
P-16
0~1
Analog input V / mA
P-17
0~1
852
Bit/Word
Device type
Format
Range
Memo
P-18
0~1
P-19
0~1
P-20
0~1
Preset speed 1
P-21
0~1
Preset speed 2
P-22
0~1
Preset speed 3
P-23
0~1
Preset speed 4
P-24
0~1
P-25
0~1
P-26
0~1
P-27
0~1
Skip frequency
P-28
0~1
P-29
0~1
P-30
0~1
P-31
0~1
P-32
0~1
P-33
0~1
Spin start
P-34
0~1
P-35
0~1
P-36
0~1
P-37
0~1
P-38
0~1
P-39
0~1
P-40
0~1
P-00-01
0~1
P-00-02
0~1
P-00-03
0~1
P-00-04
0~1
P-00-05
0~1
Reserved
P-00-06
0~1
Reserved
P-00-07
0~1
P-00-08
0~1
P-00-09
0~1
Heatsink temperature
P-00-10
0~1
P-00-11
0~1
P-00-12
0~1
P-00-13
0~1
853
Bit/Word
Device type
Format
Range
Memo
P-00-14
0~1
Reserved
P-00-15
0~1
P-00-16
0~1
P-00-17
0~1
Motor current
P-00-18
0~1
P-00-19
0~1
P-00-20
0~1
Drive identifier
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W 8P
RJ45 Male
1 RX-
6 Data-
4-
2 RX+
9 Data+
5+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
PLC RS485 2W 8P
RJ45 Male
7 RX-
4 Data-
4-
6 RX+
1 Data+
5+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W 8P
RJ45 Male
1 RX-
7 Data-
4-
2 RX+
8 Data+
5+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W 8P
RJ45 Male
1 RX-
6 Data-
4-
2 RX+
9 Data+
5+
5 GND
5 GND
854
COM3 RS485 2W
9P D-Sub Male
PLC RS485 2W 8P
RJ45 Male
1 RX-
6 Data-
4-
2 RX+
9 Data+
5+
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
PLC RS485 2W 8P
RJ45 Male
1 RX-
7 Data-
4-
2 RX+
8 Data+
5+
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
May/19/2011
Driver released.
855
SHIMADEN MR13/FP93
Supported Series: MR13, FP93 devices
Website: http://www.shimaden.co.jp
HMI Setting:
Parameters
Recommended
Options
PLC type
SHIMADEN MR13/FP93
PLC I/F
RS485
Baud rate
9600
1200-19200
Data bits
7 or 8
Parity
None/Even
Stop bits
1~255
Notes
0, 1 : STX_ETX_CR
Start Character Mode
Select 3@_:_CR
Select 3XOR
2 : STX_ETX_CR LF
3 : @_:_CR
0, 1 : Addition
2 : Addition +2s
complement
3 : XOR
4 : None
Note
Address 018C is a communication control register, only when it is set to 1 can this register
be allowed to write to other registers.
856
Device Address:
Bit/Word Device type Format
Range
Memo
Channel 1
HHHH
0 ~ ffff
Channel 2
HHHH
0 ~ ffff
Channel 3
HHHH
0 ~ ffff
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
MR13/FP93 RS485 2W
Terminal
1 RX-
6 Data-
25
2 RX+
9 Data+
24
5 GND
5 GND
23 GND
COM2 RS485 2W
COM3 RS485 2W
MR13/FP93 RS485 2W
9P D-Sub Female
9P D-Sub Female
Terminal
7 RX-
4 Data-
25
6 RX+
1 Data+
24
5 GND
5 GND
23 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
MR13/FP93 RS485 2W
Terminal
1 RX-
7 Data-
25
2 RX+
8 Data+
24
5 GND
9 GND
23 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
MR13/FP93 RS485 2W
Terminal
1 RX-
6 Data-
25
2 RX+
9 Data+
24
5 GND
5 GND
23 GND
857
COM3 RS485 2W
9P D-Sub Male
MR13/FP93 RS485 2W
Terminal
1 RX-
6 Data-
25
2 RX+
9 Data+
24
5 GND
5 GND
23 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
MR13/FP93 RS485 2W
Terminal
1 RX-
7 Data-
25
2 RX+
8 Data+
24
5 GND
5 GND
23 GND
Parameter
Details of Parameter
R /W
0100
PV Value
0101
E_SV Execution
SV Value
0102
OUT Control
Output Value
0103
Reserved
0104
Action Flag
0105
0106
Reserved
0107
Reserved
0108
REM Value
0109
Reserved
010A
Reserved
010B
DI
(hex)
Data Address
Parameter
Details of Parameter
R /W
0111
RANGE
0112
Reserved
(hex)
858
DP
Decimal Point
PV Sc_L
Lower Limit
Higher Limit
Parameter
Details of Parameter
R/W
0120
E_PRG
0121
Reserved
0122
Reserved
E_PRT
E_STP
E_TIM
E_PID
Parameter
Details of Parameter
R/W
0184
AT
0:No execution
018C
Operation
0:Local
0190
PROG RUN/RST
Program Run/Reset
0RST, 1RUN
Writing is possible only in CH1
0113
0114
0115
Data Address
(hex)
0123
0124
0125
0126
Data Address
(hex)
PV Sc_H
Auto Tuning
859
1:Execution
1:COM
W
W
0191
0300
Data
Address
PROG HLD
Program Hold
0Release, 1HLD
Writing is possible only in CH1
SV
R/W
Parameter
Details of Parameter
R/W
(hex)
030A
SV Limt_L
Lower Limit
030B
SV Limt_h
Higher Limit
0314
REM SC_L
0315
REM SC_H
SC_H
0316
REM Bias
R/W
0317
REM Filt
R/W
031A
REM-CH
Parameter
Details of Parameter
0320
SV Follow SW
0321
SV Follow
0400
FIX P
R/W
0401
FIX I
R/W
0402
FIX D
R/W
Data Address
(hex)
860
R/W
R/W
R/W
R/W
0403
FIX MR
R/W
0404
FIX DF
R/W
0405
R/W
0406
R/W
0407
FIX SF
R/W
0408
Prog P1
R/W
0409
Prog I1
R/W
040A
Prog D1
040B
Prog MR1
040C
Prog DF1
040D
Prog O_Lmt_L1
(0.0:OFF)
R/W
(0.0:OFF)
R/W
R/W
040E
Prog O_Lmt_H1
040F
Prog SF1
R/W
0410
Prog P2
R/W
0411
Prog I2
(0.0:OFF)
R/W
0412
Prog D2
(0.0:OFF)
0413
Prog MR2
R/W
0414
Prog DF2
R/W
0415
Prog O_Lmt_L2
0416
Prog O_Lmt_H2
Range: 0.1100.0%
Range: 0.1100.0%
861
R/W
R/W
R/W
0417
Prog SF2
R/W
0418
Prog P3
R/W
(0.0:OFF)
R/W
(0.0:OFF)
0419
041A
041B
041C
041D
041E
041F
Prog I3
Prog D3
Prog MR3
Prog DF3
R/W
R/W
R/W
Prog O_Lmt_L3
Prog O_Lmt_H3
Range: 0.1100.0%
Prog SF3
R/W
R/W
0500
EV1_MODE
862
R/W
0501
R/W
limit
absolute
value
alarm:
Within
value
alarm:
Within
measuring range
6. Lower
limit
absolute
measuring range
Only when Subaddress=EV1_CH.
0502
EV1 Diffrnt
0503
EV1 Inhibit
0504
EV1 Delay
0506
EV1_CH
R/W
R/W
R/W
R/W
0510
EV2_MODE
863
R/W
0511
R/W
limit
absolute
value
alarm:
Within
value
alarm:
Within
measuring range
6. Lower
limit
absolute
measuring range
Only when Subaddress=EV2_CH.
0512
EV2 Diffrnt
0513
EV2 Inhibit
0514
EV2 Delay
0516
EV2_CH
R/W
R/W
R/W
R/W
0520
EV3_MODE
864
R/W
0521
limit
absolute
value
alarm:
Within
value
alarm:
Within
R/W
measuring range
6. Lower
limit
absolute
measuring range
Only when Subaddress=EV3_CH
0522
EV3 Diffrnt
0523
EV3 Inhibit
0524
EV3 Delay
0526
EV3_CH
0580
05B0
DI
MEM
2:RUN 3:HLD
R/W
R/W
R/W
R/W
R/W
R/W
R/W
0600
Out Actn
0601
Out Cyc
0602
Reserved
0603
SOFTSW
865
0610
AT Point
R/W
0611
Key Lock
R/W
When Out_Cyc is written, writing data is adjusted to 0.5 sec as one unit.
The write command lock by keylock is the same as the screen lock. (Refer to the
manual of the instrument.)
If there is a change in EV1_CH,EV2_CH,EV3_CH, the related parameters are
initialized.
0701
PV Bias
R/W
0702
PV Filt
R/W
0710
PFLW
R/W
0711
CH_P
0: Without
0800
FP_MOD
0801
PV_ST
0882
STP
R/W
0-0 Window
1: With
0:OFF 1:ON
0883
RPT
0884
ST_SV
Start SV
(Writing possible only in CH1)
R/W
R/W
R/W
R/W
R/W
For CH1, PFLW (window 1~30), CH_P (window1-29display- - - -.The read value is:
7FFEH, To a write command, error0BHis returned.
866
08A0
Step1 SV
08A1
Step1 Time
R/W
08A2
Step1 PID No
R/W
08A3
Reserved
08A4
Step2 SV
08A5
Step2 Time
R/W
08A6
Step2 PID No
R/W
08A7
Reserved
08A8
Step3 SV
08A9
Step3 Time
R/W
08AA
Step3 PID No
R/W
08AB
Reserved
08AC
Step4 SV
08AD
Step4 Time
R/W
08AE
Step4 PID No
R/W
08AF
Reserved
08B0
Step5 SV
08B1
Step5 Time
R/W
08B2
Step5 PID No
R/W
08B3
Reserved
08B4
Step6 SV
08B5
Step6 Time
R/W
08B6
Step6 PID No
R/W
08B7
Reserved
867
R/W
R/W
R/W
R/W
R/W
R/W
08B8
Step7 SV
08B9
Step7 Time
R/W
08BA
Step7 PID No
R/W
08BB
Reserved
08BC
Step8 SV
08BD
Step8 Time
08BE
Step8 PID No
08BF
Reserved
08C0
Step9 SV
08C1
Step9 Time
R/W
08C2
Step9 PID No
R/W
Driver Version:
Version
Date
V1.20
Apr/08/2011
Description
868
R/W
R/W
R/W
R/W
R/W
SHJ-A
HMI Setting:
Parameters
Recommended
PLC type
SHJ-A
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
None
Stop bits
Options
Notes
Device Address:
Bit/Word Device type
Format
Range
DD
0 ~ 89
Word
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
869
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Oct/18/2011
Driver released.
870
Recommended
PLC type
PLC I/F
RS232
Baud rate
115200
Data bits
Parity
None
Stop bits
Options
Notes
9600,19200,3840
0,57600,115200
Device Address:
Bit/Word
B
Device type
Format
Range
Memo
DDo
0 ~ 967
Input
DDo
0 ~ 487
Output
Logic result
DDo
0 ~ 327
Logic Result
RS-232
DDo
0 ~ 327
RS-232
DDo
0 ~ 997
DDo
0 ~ 597
Do
0 ~ 97
Configuration CRCs_Bit
DDo
0 ~ 197
DDo
0 ~ 177
B
W
DDDo
0 ~ 3377
0~2
DD
0 ~ 98
DD
0 ~ 58
0~8
Configuration CRCs
DD
0 ~ 18
DD
0 ~ 16
DDD
0 ~ 336
871
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
CPU0 Port0 4P
Mini-DIN Male
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
4 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
CPU0 Port0 4P
Mini-DIN Male
2 RX
3 TX
3 TX
2 RX
5 GND
4 GND
CPU0 Port0 4P
Mini-DIN Male
2 RX
3 TX
3 TX
2 RX
5 GND
4 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
CPU0 Port0 4P
Mini-DIN Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
4 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
CPU0 Port0 4P
Mini-DIN Male
9 RX
3 TX
6 TX
2 RX
5 GND
4 GND
View from the
soldering point
of a cable.
872
Driver Version:
Version
Date
Description
V1.00
Apr/6/2011
Driver released.
V1.10
May/15/2013
873
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
Ethernet
Port no.
102
Local TSAP
1000
Remote TSAP
2100
Range:2000~2700
1~99
PLC Setting:
Siemens LOGO! multi connection setting requires LOGO! Soft Comfort software to set
PLC to identify the connected devices. The following introduces LOGO! Soft Comfort
settings.
Step 1. Tools -> Ethernet Connections
874
Step 2. Right click on Ethernet Connections and click Add connections to add a
connection, up to eight connections are allowed.
Note: The value of Local TSAP and Remote TSAP must be set oppositely in EasyBuilder
for communication.
875
Device Address:
Bit/Word
Device type
Format
Range
Memo
Read Only
DD
1~64
DD
1~64
DD
1~112
NI
DDD
1~128
NQ
DDDDo
0~14697
AI
1~16
AQ
1~16
AM
DD
1~64
NAI
1~64
NAQ
1~32
VW
DDDD
0~1468
DW
VD
DDDD
0~1466
1~128
876
VW_Bit
VW
VW
VW
AI
VW
AQ
VW
AM
VW
I1
V923.0
Q1
V942.0
M1
V948.0
AI1
VW926
AQ1
VW944
AM1
VW952
I2
V923.1
Q2
V942.1
M2
V948.1
AI2
VW928
AQ2
VW946
AM2
VW954
I3
V923.2
Q3
V942.2
M3
V948.2
AI3
VW930
AM3
VW956
I4
V923.3
Q4
V942.3
M4
V948.3
AI4
VW932
AM4
VW958
I5
V923.4
Q5
V942.4
M5
V948.4
AI5
VW934
AM5
VW960
I6
V923.5
Q6
V942.5
M6
V948.5
AI6
VW936
AM6
VW962
I7
V923.6
Q7
V942.6
M7
V948.6
AI7
VW938
AM7
VW964
I8
V923.7
Q8
V942.7
M8
V948.7
AI8
VW940
AM8
VW966
I9
V924.0
Q9
V943.0
M9
V949.0
AM9
VW968
I10
V924.1
Q10
V943.1
M10
V949.1
AM10
VW970
I11
V924.2
Q11
V943.2
M11
V949.2
AM11
VW972
I12
V924.3
Q12
V943.3
M12
V949.3
AM12
VW974
I13
V924.4
Q13
V943.4
M13
V949.4
AM13
VW976
I14
V924.5
Q14
V943.5
M14
V949.5
AM14
VW978
I15
V924.6
Q15
V943.6
M15
V949.6
AM15
VW980
I16
V924.7
Q16
V943.7
M16
V949.7
AM16
VW982
I17
V925.0
M17
V950.0
I18
V925.1
M18
V950.1
I19
V925.2
M19
V950.2
I20
V925.3
M20
V950.3
I21
V925.4
M21
V950.4
I22
V925.5
M22
V950.5
I23
V925.6
M23
V950.6
I24
V925.7
M24
V950.7
M25
V951.0
M26
V951.1
M27
V951.2
877
VM (From)
VM (To)
Range
1024
1031
8 Bytes
AI
1032
1063
32 Bytes
1064
1071
8 Bytes
AQ
1072
1103
32 Bytes
1104
1117
14 Bytes
AM
1118
1245
128 Bytes
NI
1246
1261
16 Bytes
NAI
1262
1389
128 Bytes
NQ
1390
1405
16 Bytes
NAQ
1406
1469
64 Bytes
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
DEC/7/2011
Driver released.
V1.40
Mar/10/2015
878
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
Ethernet
Port no.
102
Rack
CPU slot
On-line simulator
Yes
Options
Notes
Multi-HMI connect
*EasyBuilder8000 does note support Siemens S7-1200 firmware V4.0 and later versions.
PLC Setting:
1.
2.
In S7-1200 program software create PLC program and tag and then download to
PLC.
Select Go offline, EasyBuilder will connect to PLC and get tag data. In PLC type
select SIEMENS S7-1200 (Ethernet).
879
3.
4.
Check the PLC that is not connected to any PC. Click Get tag info.
5.
Supported by firmware V3.X and previous versions. For V4.0 or later, please see How
to Connect With S7-1200 Firmware V4.0)
880
6.
If the software used is a version later than TIA Portal V11SP2, a dialog of
FunctionBlock directory will be shown, users have to define the mapping from FB to
DB in this directory then click Check OK. The tag information will be gained and
a successful message is shown.
881
7.
When opening an existing project and get the tag information again, if the PLC
software used is TIA Portal V12 and later versions, the DB name must be entered
again in order to compile the project.
8. Added Tag Manager that allows selecting the Siemens S7-1200 PLC tags to be
imported.
882
9.
883
Select [Protection], and then select [Permit access with PUT/GET communication
from remote partner (PLC,HMI,OPC,].
884
The following part introduces how to export S7-1200 PLC Tags and Program Blocks.
Exporting PLC Tags (I,Q,M tags)
1. Under [PLC tags] select [Show all tags].
3. Browse for the directory to save the exported file and then click [OK].
885
2. Right click on DB, click [Generate source from blocks], and then enter the file name
to save.
886
After building and importing PLC Tags and Program Blocks, click [Download to device].
887
3. Select the PLC Tags and Program Blocks to be imported. Please remember to change
DB number, and select [Use S7-1200 firmware version 4.0 or later versions]. Click
[Import] to import the files. The I, Q, and M addresses will be checked, if an error
occurs, the communication will fail. If this happens, please check your communication
environment, and try to import again.
4. The Import status field will display the result, click [OK].
888
[OK].
889
Bool
bit
Byte
8-bit
DInt
Real
32-bit Float
32-bit
UDInt
32-bit
SInt
USInt
Word
Int
UInt
DWord
Array
Char
8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit
Length=word
USInt
Struct
CREF
Date
Memo
UInt
DTL
Struct
ErrorStruct
Struct
IEC_COUNTER
Struct
IEC_DCOUNTER
Struct
IEC_SCOUNTER
Struct
IEC_TIMER
Struct
IEC_UCOUNTER
Struct
890
Memo
IEC_UDCOUNTER
Struct
IEC_USCOUNTER
Struct
NREF
Struct
Time
Time_Of_Day
DWord
DWord
Bool, Byte, SINT, USInt, Word,
Int, UInt, DWord, Dint, Real,
UDInt
Struct
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.70
Oct/7/2011
V1.90
Apr/26/2012
V2.40
Aug/04/2014
V2.50
Aug/29/2014
Support cMT-SVR
891
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
Ethernet
Port no.
102
Rack
CPU slot
On-line simulator
Yes
Options
Notes
Multi-HMI connect
Bool
bit
Byte
8-bit
SInt
8-bit
USInt
8-bit
Word
16-bit
Int
16-bit
UInt
16-bit
DWord
32-bit
DInt
32-bit
Real
32-bit Float
32-bit
UDInt
32-bit
Array
Length=word
String
Length=word
892
Memo
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
DBnBit
FFFFFDDDDo
0 ~ 6553599997
DB1Bit-DB99Bit DDDDDo
0 ~ 655327
IW
DDDD
0 ~ 4095
Input (I)
QW
DDDD
0 ~ 4095
Output (O)
MW
DDDD
0 ~ 4095
Bit Memory
DW
MD
DDDD
0 ~ 4094
DBn
FFFFFDDDD
0 ~ 655359999
DW
DBDn
FFFFFDDDD
0 ~ 655359999
DBn_String
FFFFFDDDD
0 ~ 655359999
(must
be multiple of 4)
Char array
DBn_String1
FFFFFDDDD
0 ~ 655359999
String
DW
DBDn_String
FFFFFDDDD
0 ~ 655359999
Char array
DB1 ~ DB99
DDDDD
0 ~ 65532
Byte
MB
DDDD
0 ~ 4095
Byte
DBBn
FFFFFDDDD
0 ~ 655359999
DW
ID
DDDD
0 ~ 4094
Byte
IB
DDDD
0 ~ 9095
DW
QD
DDDD
0 ~ 4094
Byte
QB
DDDD
0 ~ 4095
DW
S5TIME_10Ms
FFFFFDDDD
0 ~ 655359999
DW
S5TIME_100Ms FFFFFDDDD
0 ~ 655359999
DW
S5TIME_10S
FFFFFDDDD
0 ~ 655359999
DW
S5TIME_10S
FFFFFDDDD
0 ~ 655359999
Data Register
(must be even)
Data Register Double
Word
Data Register(must be
even)
Double word and floating point value must use DBDn device type.
893
PLC Setting:
Note: Please follow the settings below, or the communication may fail.
1. Do not check [DB UTILITAIRES] -> [Attributes] -> [Optimized block access]
2. Check [General] -> [Protection] -> [Permit access with PUT/GET communication from
remote partner]
894
1.2 Designate the directory to save the file and click OK button.
895
896
3. In EasyBuilder click [New PLC], select Siemens S7-1500 (Ethernet) PLC type, and
then click [Settings] to set the parameters.
897
5. Select the PLC Tags and Program Blocks to be imported, click [Import] button, and then
click [OK] to leave when the tags are imported successfully.
898
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
May/02/2014
Driver released.
899
Siemens S7-200
Supported Series: Siemens S7-200 series PLC
(CPU212/214/215/216/221/222/224/226/226XM)
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters
PLC type
Recommend Options
ed
SIEMENS S7-200
PLC I/F
RS485 2w
Notes
RS485 2w
The HMI which has a sticker
Baud rate
9600
Data bits
7,8
Parity
Even
Stop bits
1, 2
1 ~ 126
30
Online simulator
YES
Broadcast command NO
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
VW_Bit
DDDDDo
0 ~ 102397
DDDDo
0 ~ 40957
SCR
SM
DDDDo
0 ~ 40957
Special Memory
T_Bit
DDD
0 ~ 255
Timer
900
Format
Range
Memo
C_Bit
DDD
0 ~ 255
Counter
Byte
VB
DDDDD
0 ~ 10239
V Memory
VW
DDDDD
0 ~ 10239
V Memory
VW_Odd
DDDDD
0 ~ 10239
V Memory
DW
VD
DDDDD
0 ~ 10239
DW
VD_Odd
DDDDD
0 ~ 10239
VW_String
DDDDD
0 ~ 10239
String
VW_String_Odd DDDDD
0 ~ 10239
String
DW
VD_String
DDDDD
0 ~ 10239
String
DW
VD_String_Odd
DDDDD
0 ~ 10239
String
Byte
MB
DDDDD
0 ~ 10239
Byte Memory
MW
DDDDD
0 ~ 10239
Word Memory
MW_Odd
DDDDD
0 ~ 10239
Word Memory
DW
MD
DDDDD
0 ~ 10239
Word Memory
Byte
SB
DDDDD
0 ~ 10239
SCR
SW
DDDDD
0 ~ 10239
SCR
DW
SD
DDDDD
0 ~ 10239
SCR
Byte
SMB
DDDDD
0 ~ 10239
Special Memory
SMW
DDDDD
0 ~ 10239
Special Memory
DW
SMD
DDDDD
0 ~ 10239
Special Memory
DDD
0 ~ 255
Timer
DDD
0 ~ 255
Counter
Double word and floating point value must use VD device type.
901
2. Launch EasyBuilder, add the driver in the device list in System Parameter Settings,
and then click Import Tag button.
902
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
3 D+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
903
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
5 GND
5 GND
Driver Version:
Version
Date
Description
V2.30
Aug/17/2009
V2.40
Nov/01/2011
V2.60
Jan/03/2013
V2.90
Set/06/2013
904
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
102
Notes
0-31
PLC Setting:
S7/200 Ethernet Multi-Connection Settings
Step 1: Launching the Ethernet Wizard
1. In the Micro/WIN main menu, click Tools / Ethernet Wizard.
905
906
2. To view the results of Read Modules, select the Ethernet module. Click Next.
907
2. Enter the number of desired available connections for this device. If 0 is entered,
the only connection available will be the PG mode. The image below shows there
are 4 connections for this module.
908
5. Upon completion of the settings above, set parameters in EasyBuilder. Set the
value of Local TSAP here to the value of Remote TSAP in Micro/WIN and vice
versa to realize multi-connection.
909
2. Launch EasyBuilder, add the driver in the device list in System Parameter Settings,
and then click Import Tag button.
910
Device Address:
Bit/Word
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
VW_Bit
DDDDDo
0 ~ 102397
DDDDo
0 ~ 40957
SCR
SM
DDDDo
0 ~ 40957
Special Memory
VW
DDDDD
0 ~ 10239
V Memory
DW
VD
DDDDD
0 ~ 10239
VW_String
DDDDD
0 ~ 10239
String
DW
VD_String
DDDDD
0 ~ 10239
String
DW
MD
DDDDD
0 ~ 10239
Word Memory
Byte
VB
DDDDD
0 ~ 10239
V Memory Byte
Byte
SB
DDDDD
0 ~ 10239
SCR
SW
DDDDD
0 ~ 10239
SCR
DW
SD
DDDDD
0 ~ 10239
SCR
Byte
SMB
DDDDD
0 ~ 10239
Special Memory
SMW
DDDDD
0 ~ 10239
Special Memory
DW
SMD
DDDDD
0 ~ 10239
Special Memory
Double word and floating point value must use VD device type.
911
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.20
Dec/30/2008
V1.40
Nov/15/2011
V1.60
Jan/07/2013
V1.80
Mar/23/2015
912
HMI Setting:
Parameters
PLC type
Recommend Options
ed
Siemens S7-200 (VD any address)
PLC I/F
RS485 2w
Notes
RS485 2w
The HMI which has a sticker
Baud rate
9600
Data bits
7,8
Parity
Even
Stop bits
1, 2
1 ~ 126
Reserved 1
30
Online simulator
YES
Broadcast command NO
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
VW_Bit
DDDDDo
0 ~ 102397
DDDDo
0 ~ 40957
SCR
SM
DDDDo
0 ~ 40957
Special Memory
913
Bit/Word
Device type
Format
Range
Memo
VW
DDDDD
0 ~ 10239
V Memory
DW
VD
DDDDD
0 ~ 10239
VW_String
DDDDD
0 ~ 10239
String
DW
VD_String
DDDDD
0 ~ 10239
String
MW
DDDDD
0 ~ 10239
Word Memory
DDD
0 ~ 255
Timer
DDD
0 ~ 255
Counter
DW
MD
DDDDD
0 ~ 10239
Word Memory
Byte
SB
DDDDD
0 ~ 10239
SCR
SW
DDDDD
0 ~ 10239
SCR
DW
SD
DDDDD
0 ~ 10239
SCR
Byte
SMB
DDDDD
0 ~ 10239
Special Memory
SMW
DDDDD
0 ~ 10239
Special Memory
DW
SMD
DDDDD
0 ~ 10239
Special Memory
Double word and floating point value must use VD device type.
VD register can set to any value, not necessarily a multiple of 4.
914
2. Launch EasyBuilder, add the driver in the device list in System Parameter Settings,
and then click Import Tag button.
915
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
3 D+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
916
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.20
Nov/16/2011
V1.40
Jan/07/2013
917
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485 2w
RS485 2w
Baud rate
9600
Data bits
7,8
Parity
Even
Stop bits
1, 2
30
Online simulator
Options
Notes
1 ~ 126
YES
Broadcast command NO
PLC Setting:
PLC setting
PLC sta. no. can not be the same as HMI sta. no.
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
VW_Bit
DDDDDo
0 ~ 102397
DDDDo
0 ~ 40957
SCR
SM
DDDDo
0 ~ 40957
Special Memory
T_Bit
DDD
0 ~ 255
Timer
C_Bit
DDD
0 ~ 255
Counter
918
Bit/Word
Device type
Format
Range
Memo
Byte
VB
DDDDD
0 ~ 10239
VW
DDDDD
0 ~ 10239
V Memory
VW_Odd
DDDDD
0 ~ 10239
V Memory
DW
VD
DDDDD
0 ~ 10239
DW
VD_Odd
DDDDD
0 ~ 10239
VW_String
DDDDD
0 ~ 10239
String
VW_String_Odd DDDDD
0 ~ 10239
String
DW
VD_String
DDDDD
0 ~ 10239
String
DW
VD_String_Odd
DDDDD
0 ~ 10239
String
Byte
MB
DDDDD
0 ~ 10239
Byte Memory
MW
DDDDD
0 ~ 10239
Word Memory
MW_Odd
DDDDD
0 ~ 10239
Word Memory
DDD
0 ~ 255
Timer
DDD
0 ~ 255
Counter
DW
MD
DDDDD
0 ~ 10239
Word Memory
Byte
SB
DDDDD
0 ~ 10239
SCR
SW
DDDDD
0 ~ 10239
SCR
DW
SD
DDDDD
0 ~ 10239
SCR
Byte
SMB
DDDDD
0 ~ 10239
Special Memory
SMW
DDDDD
0 ~ 10239
Special Memory
DW
SMD
DDDDD
0 ~ 10239
Special Memory
Double Word and floating point value must use VD device type.
919
920
If GUF is set to a bigger value, the HMI that holds Token will control the PLC for a longer
time and therefore the Token wont be passed to another HMI and cause failure in
communicating with PLC.
A complete communication means HMI reads / writes PLC value for one time.
Note:
HMI sta. no. can not be the same as PLC sta. no.
Highly recommended that HMI sta. no. starts from 0 and go on sequentially for the
effectiveness of operation.
2. Launch EasyBuilder, add the driver in the device list in System Parameter Settings,
and then click Import Tag button.
921
922
Pass-Through Settings:
[Designate client IP]: In Pass-through mode designate the client IP address to connect
HMI. The client usually refers to Siemens Step 7 application.
The following lists the system registers relevant to Siemens S7-200 PPI and
Siemens S7-300 MPI Pass-through feature.
[LW-10850: disable/enable (0 : disable, 1 : normal, 2 : IP limited) (siemens
pass-through)]
[LW-10851: destination COM port (siemens pass-through)]: Generally refers to the
COM port connected with PLC.
[LW-10852: destination PLC station no. (siemens pass-through)]
[LW-10853: communication protocol (0 : invalid, 1 : PPI, 2 : MPI) (siemens
pass-through)]
[LW-10854 to LW-10857: IP of connecting client (siemens pass-through)]: Displays
current client IP address connected with HMI.
[LW-10858 to LW-10861: IP of designated client (siemens pass-through)]: If
LW-10850 is set to 1, the system registers can be used to designate the client IP
connected with HMI.
[LW-10862: connection status (0 : ready, 1 : client connecting) (siemens
pass-through)]
[LW-10863: execution status (0 : normal, 1 : error) (siemens pass-through)]
[LW-10864: the last error (siemens pass-through)]
923
The following table lists the error codes, the description of each code, and the
possible reason.
Error Code
Description
Possible Reason
Successfully executed
Invalid communication
protocol
Delayed communication
Busy communication
settings.
7
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
COM3 RS485 2W
RS485 2W 9P D-Sub
9P D-Sub Male
9P D-Sub Male
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
3 D+
5 GND
5 GND
5 GND
cMT/mTV series
924
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
5 GND
5 GND
Driver Version
Version
Date
Description
V1.00
Aug/15/2011
Driver released.
V1.10
Nov/17/2011
V1.50
Jan/07/2013
V2.00
Set/06/2013
925
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
Ethernet
Port no.
102
Online simulator
Yes
Options
Notes
Device Address:
Bit/Word
Range
Memo
DDo
0 ~ 317
Input
DDo
0 ~ 317
Output
DDo
0 ~ 317
Bit Memory
DDDDDo
0 ~ 204797
V Memory bit
DDo
0 ~ 317
SCR
SM
DDDDo
0 ~ 15357
Timer
DDD
0 ~ 255
Timer
Counter
DDD
0 ~ 255
Counter
MW
DD
0 ~ 30
Word Memory
VW
DDDDD
0 ~ 20478
V Memory
SMW
DDDD
0 ~ 1534
Special Memory
DDD
0 ~ 255
Timer
DDD
0 ~ 255
Counter
AIW
DDD
0 ~ 110
Analog input
AQW
DDD
0 ~ 110
Analog Output
DW
VD
DDDDD
0 ~ 20476
Double word and floating point value must use VD device type.
926
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Oct/5/2012
Driver released.
V1.20
Jun/14/2013
927
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485 2W
RS485 2W
Baud rate
9600
9600, 19200,
187.5K
Data bits
7,8
Parity
Even
Stop bits
1, 2
30
Online simulator
Options
Notes
1 ~ 126
YES
Broadcast command NO
PLC Setting:
PLC setting
PLC sta. no. can not be the same as HMI sta. no.
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDo
0 ~ 317
Input
DDo
0 ~ 317
Output
DDo
0 ~ 317
Bit Memory
DDDDDo
0 ~ 204797
V Memory bit
DDo
0 ~ 317
SCR
SM
DDDDo
0 ~ 15357
Timer
DDD
0 ~ 255
Timer
Counter
DDD
0 ~ 255
Counter
MW
DD
0 ~ 30
Word Memory
928
Bit/Word
Device type
Format
Range
Memo
VW
DDDDD
0 ~ 20478
V Memory
SMW
DDDD
0 ~ 1534
Special Memory
DDD
0 ~ 255
Timer
DDD
0 ~ 255
Counter
AIW
DDD
0 ~ 110
Analog input
AQW
DDD
0 ~ 110
Analog Output
DW
VD
DDDDD
0 ~ 20476
Double Word and floating point value must use VD device type.
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
3 D+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
929
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
5 GND
5 GND
Driver Version
Version
Date
Description
V1.00
Oct/5/2012
Driver released.
930
Siemens S7-300
Supported Series: Siemens S7-300 series PLC
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters
Recommended Options
PLC type
SIEMENS S7-300
PLC I/F
RS232
Baud rate
19200
Data bits
Parity
Odd
Stop bits
Notes
9600,19200
Device Address:
Bit/Word Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
DBnBit
FFFFDDDDo
0 ~ 409681927
DDDDo
0 ~ 81927
DB1Bit ~
DB99Bit
IW
DDDD
0 ~ 4095
Input (I)
QW
DDDD
0 ~ 4095
Output (O)
MW
DDDD
0 ~ 4095
Bit Memory
DW
MD
DDDD
0 ~ 4094
Byte
MB
DDDD
0 ~ 4095
Byte
DBBn
FFFFDDDD
0 ~ 40968192
DBn
FFFFDDDD
0 ~ 40968192
DW
DBDn
FFFFDDDD
0 ~ 40968192
DBn_String
FFFFDDDD
0 ~ 40968192
931
Format
Range
DW
DBDn_String FFFFDDDD
0 ~ 40968192
DB1-DB99
0 ~ 8192
DDDD
Memo
Data Register Double Word
(must be multiple of 4)
Data Register
(must be even)
* Double word and floating point value must use DBDn device type.
932
933
c Select Sources as storage path, specify the file name then click OK.
934
e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
935
Wiring Diagram:
The following is the view from the soldering point of a cable.
Siemens S7-300 PC Adapter : 9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
936
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
4 DTR
6 DSR
short
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
4 DTR
6 DSR
937
short
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
4 DTR
6 DSR
short
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
4 DTR
6 DSR
short
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
4 DTR
6 DSR
Driver Version:
Version
Date
Description
V3.10
May/24/2011
short
short
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
Ethernet
Local TSAP
100
Remote TSAP
103
Online simulator
Options
No
939
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
DBnBit
FFFFDDDDo
0 ~ 409699997
DB0Bit-DB99Bit DDDDDo
0 ~ 655327
IW
DDDD
0 ~ 4095
Input (I)
QW
DDDD
0 ~ 4095
Output (O)
MW
DDDD
0 ~ 4095
Bit Memory
DW
MD
DDDD
0 ~ 4094
DW
MD_Anyaddr
DDDD
0 ~ 4094
DBn
FFFFDDDD
0 ~ 40969999
DW
DBDn
FFFFDDDD
0 ~ 40969999
DW
DBDn_Anyaddr
FFFFDDDD
0 ~ 40969999
DBn_String
FFFFDDDD
0 ~ 40969999
DW
DBDn_String
FFFFDDDD
0 ~ 40969999
DB0 ~ DB99
DDDDD
0 ~ 65532
Byte
MB
DDDD
0 ~ 4095
Byte
DBBn
FFFFDDDD
0 ~ 40969999
Double word and floating point value must use DBDn device type.
940
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Jan/15/2014
Driver released.
V1.10
Feb/21/2014
V1.70
Sep/09/2015
941
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS-485 2W
Baud rate
187.5K
Data bits
Parity
Even
Stop bits
Online simulator
Options
Notes
19200,187.5K
2 ~ 31
NO
Broadcast command NO
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
DBnBit
DB1Bit ~
FFFFDDDDo
0 ~ 409699997
DDDDDo
0 ~ 655327
DB99Bit
IW
DDDD
0 ~ 4095
Input (I)
QW
DDDD
0 ~ 4095
Output (O)
MW
DDDD
0 ~ 4095
Bit Memory
DW
MD
DDDD
0 ~ 4094
Byte
MB
DDDD
0 ~ 4095
Byte
DBBn
FFFFDDDD
0 ~ 40969999
Data Register
DBn
FFFFDDDD
0 ~ 40969999
DW
DBDn
FFFFDDDD
0 ~ 40969999
942
Bit/Word
Device type
Format
Range
DBn_String
FFFFDDDD
0 ~ 40969999
DW
DBDn_String FFFFDDDD
0 ~ 40969999
DB1 ~ DB99
0 ~ 65532
DDDDD
Memo
Double word and floating point value must use DBDn device type.
943
For the effectiveness of communication, users may set PLC device in STEP 7 as shown
below. In Properties MPI / Network Settings, set Highest MPI address to the number
closest to the actual device station number.
HMI sta. no. can not be the same as PLC sta. no.
Highly recommended that the device station numbers start from 0 sequentially and
correctly set [Max. station no. (MPI network)].
Available for EasyBuilder V4.50 and later.
X Series does not support multiple-HMI-to-multiple-PLC communication, and supports
only 1-HMI-to-1-PLC communication.
944
945
c Select Sources as storage path, specify the file name then click OK.
946
e Under Sources there will be names of the saved files, select Export
Source to build *.AWL file.
947
Pass-Through Settings:
[Designate client IP]: In Pass-through mode designate the client IP address to connect
HMI. The client usually refers to Siemens Step 7 application.
948
The following lists the system registers relevant to Siemens S7-200 PPI and
Siemens S7-300 MPI Pass-through feature.
[LW-10850: disable/enable (0 : disable, 1 : normal, 2 : IP limited) (siemens
pass-through)]
[LW-10851: destination COM port (siemens pass-through)]: Generally refers to the
COM port connected with PLC.
[LW-10852: destination PLC station no. (siemens pass-through)]
[LW-10853: communication protocol (0 : invalid, 1 : PPI, 2 : MPI) (siemens
pass-through)]
[LW-10854 to LW-10857: IP of connecting client (siemens pass-through)]: Displays
current client IP address connected with HMI.
[LW-10858 to LW-10861: IP of designated client (siemens pass-through)]: If
LW-10850 is set to 1, the system registers can be used to designate the client IP
connected with HMI.
[LW-10862: connection status (0 : ready, 1 : client connecting) (siemens
pass-through)]
[LW-10863: execution status (0 : normal, 1 : error) (siemens pass-through)]
[LW-10864: the last error (siemens pass-through)]
The following table lists the error codes, the description of each code, and the
possible reason.
Error Code
Description
Possible Reason
Successfully executed
Invalid communication
protocol
Delayed communication
Busy communication
949
Wiring Diagram:
The following is the view from the soldering point of a cable.
S7-200 PPI , S7-300 MPI :RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
3 D+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
COM3 RS485 2W
RS485 2W 9P D-Sub
9P D-Sub Male
9P D-Sub Male
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
950
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.90
May/26/2011
V2.00
Aug/19d/2011
951
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
102
Notes
0-31
In V3.00 and later versions, setting [Interval of block pack] to 0 can optimize efficiency.
952
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
DBnBit
FFFFDDDDo
0 ~ 409699997
DB1Bit-DB99Bit DDDDDo
0 ~ 655327
IW
DDDD
0 ~ 4095
Input (I)
QW
DDDD
0 ~ 4095
Output (O)
MW
DDDD
0 ~ 4095
Bit Memory
DW
MD
DDDD
0 ~ 4094
DW
MD_Anyaddr
DDDD
0 ~ 4094
DBn
FFFFDDDD
0 ~ 40969999
DW
DBDn
FFFFDDDD
0 ~ 40969999
DW
DBDn_Anyaddr
FFFFDDDD
0 ~ 40969999
DBn_String
FFFFDDDD
0 ~ 40969999
DW
DBDn_String
FFFFDDDD
0 ~ 40969999
DB1 ~ DB99
DDDDD
0 ~ 65532
Byte
MB
DDDD
0 ~ 4095
Byte
DBBn
FFFFDDDD
0 ~ 40969999
Double word and floating point value must use DBDn device type.
953
954
955
c Select Sources as storage path, specify the file name then click OK.
956
e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
957
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V2.10
May/21/2011
V2.20
Apr/25/2012
958
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
102
Link type
PG
PC, OP
Rack
0-7
CPU slot
1-31
0-31
Notes
Device Address:
Bit/Word Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
DBnBit
FFFFFDDDDo 0 ~ 6553599997
DB1Bit-DB99Bit DDDDDo
0 ~ 655327
IW
DDDD
0 ~ 4095
Input (I)
QW
DDDD
0 ~ 4095
Output (O)
MW
DDDD
0 ~ 4095
Bit Memory
DW
MD
DDDD
0 ~ 4094
DBn
FFFFFDDDD
0 ~ 655359999
DW
DBDn
FFFFFDDDD
0 ~ 655359999
DBn_String
FFFFFDDDD
0 ~ 655359999
DW
DBDn_String
FFFFFDDDD
0 ~ 655359999
DB1 ~ DB99
DDDDD
0 ~ 65532
Byte
MB
DDDD
0 ~ 4095
Byte
DBBn
FFFFFDDDD
0 ~ 655359999
Data Register
(must be even)
Data Register Double Word
(must be multiple of 4)
Data Register
(must be even)
* Double word and floating point value must use DBDn device type.
959
2.
3.
4.
Press [Settings].
960
5.
Set S7-400 IP, Port no., Link type, Rack and CPU slot. (must match PLC settings)
6.
961
962
c Select Sources as storage path, specify the file name then click OK.
963
e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
964
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.40
May/25/2011
V1.50
Aug/03/2012
Siemens TI505
Supported Series: SIMATIC TI505 Series PLCs: TI520, TI525, TI530, TI535, TI545, TI555,
TI560, TI565, TI575. Use NITP protocol in a point-to-point, single master, single slave
format.
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters
Recommended
Options
PLC type
SIMATIC TI505
PLC I/F
RS232
Baud rate
19200
RS232,
RS485(4W)
19200
Data bits
Parity
Odd
Odd
Stop bits
Notes
NITP protocol
Device Address:
Bit/Word Device type
Format
Range
Memo
CR
DDDDD
1 ~ 65535
Internal Relay
DDDDD
1 ~ 65535
DDDDD
1 ~ 65535
V_Bit
DDDDD
1 ~ 65535
DW
VD
DDDDD
1 ~ 65536
STW
DDDDD
1 ~ 65535
TCP
DDDDD
1 ~ 65535
TCC
DDDDD
1 ~ 65535
WX
DDDDD
1 ~ 65535
WY
DDDDD
1 ~ 65535
966
Wiring Diagram:
The following is the view from the soldering point of a cable.
SIMATIC TI505 RS232 : 9P D-Sub to 25P D-Sub
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
7 GND
4 RTS
5 CTS
short
6 DSR
8 DCD
short
20 DTR
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
7 GND
4 RTS
5 CTS
short
6 DSR
8 DCD
short
20 DTR
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
7 GND
4 RTS
5 CTS
short
6 DSR
8 DCD
20 DTR
967
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
7 GND
4 RTS
5 CTS
short
6 DSR
8 DCD
short
20 DTR
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
3 RXD
5 GND
7 GND
4 RTS
5 CTS
short
6 DSR
8 DCD
20 DTR
968
short
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
1 DCD
4 DTR
short
6 DSR
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
1 DCD
4 DTR
short
6 DSR
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
1 DCD
4 DTR
6 DSR
969
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
7 RTS
8 CTS
1 DCD
1 DCD
4 DTR
4 DTR
6 DSR
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
1 DCD
4 DTR
short
6 DSR
RS485 4W 9P D-Sub
Male
1 RX-
7 DO (-)
2 RX+
1 DO (+)
3 TX-
8 DI (-)
4 TX+
5 DI (+)
5 GND
6 GND
970
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
7 DO (-)
6 RX+
1 DO (+)
9 TX-
8 DI (-)
8 TX+
5 DI (+)
5 GND
6 GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
7 DO (-)
2 RX+
2 RX+
1 DO (+)
3 TX-
3 TX-
8 DI (-)
4 TX+
4 TX+
5 DI (+)
5 GND
5 GND
6 GND
RS485 4W 9P D-Sub
9P D-Sub Male
Male
1 RX-
7 DO (-)
2 RX+
1 DO (+)
3 TX-
8 DI (-)
4 TX+
5 DI (+)
5 GND
6 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
RS485 4W 9P D-Sub
9P D-Sub Female
Male
1 RX-
7 DO (-)
2 RX+
1 DO (+)
3 TX-
8 DI (-)
4 TX+
5 DI (+)
5 GND
6 GND
971
Driver Version:
Version
Date
Description
V1.10
Apr/22/2009
V1.40
Jun/08/2014
Added register: VD
V1.50
Nov/18/2014
972
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
1505
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
CR
DDDDD
1 ~ 65536
Internal Relay
DDDDD
1 ~ 65536
DDDDD
1 ~ 65536
V_Bit
DDDDDdd
101 ~ 6553616
DDDDD
1 ~ 65536
DW
VD
DDDDD
1 ~ 65535
STW
DDDDD
1 ~ 65536
TCP
DDDDD
1 ~ 65536
TCC
DDDDD
1 ~ 65536
Timer/Counter Current
WX
DDDDD
1 ~ 65536
ValuesDiscrete Inputs
Word
WY
DDDDD
1 ~ 65536
973
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Feb/10/2014
Driver released.
V1.20
Jun/08/2014
Added register: VD
V1.30
Nov/18/2014
974
Siemens TI565/C400
Supported Series: CTI565-C400,CTI 2500-C200
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters
Recommended
Options
PLC type
SIMATIC TI565/C400
PLC I/F
RS232
RS232, RS485(4W)
Baud rate
19200
19200
Data bits
Parity
Odd
Odd
Stop bits
Notes
Device Address:
Bit/Word Device type
Format
Range
Memo
CR
DDDDD
1 ~ 65535
Internal Relay
DDDDD
1 ~ 65535
DDDDD
1 ~ 65535
V_Bit
DDDDDdd
101 ~ 6553616
DDDDD
1 ~ 65535
DW
VD
DDDDD
1 ~ 65535
STW
DDDDD
1 ~ 65535
TCP
DDDDD
1 ~ 65535
TCC
DDDDD
1 ~ 65535
WX
DDDDD
1 ~ 65535
WY
DDDDD
1 ~ 65535
975
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 25P D-Sub: RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
7 GND
4 RTS
5 CTS
short
6 DSR
8 DCD
short
20 DTR
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
7 GND
4 RTS
5 CTS
short
6 DSR
8 DCD
short
20 DTR
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
7 GND
4 RTS
5 CTS
short
6 DSR
8 DCD
20 DTR
976
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
7 GND
4 RTS
5 CTS
short
6 DSR
8 DCD
short
20 DTR
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
3 RXD
5 GND
7 GND
4 RTS
5 CTS
short
6 DSR
8 DCD
20 DTR
977
short
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
1 DCD
4 DTR
short
6 DSR
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
1 DCD
4 DTR
short
6 DSR
MT8000iE/MT8000XE series except MT8050iE
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
1 DCD
4 DTR
6 DSR
978
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
1 DCD
4 DTR
short
6 DSR
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
1 DCD
4 DTR
6 DSR
979
short
RS485 4W 9P D-Sub
Male
1 RX-
7 DO (-)
2 RX+
1 DO (+)
3 TX-
8 DI (-)
4 TX+
5 DI (+)
5 GND
6 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
7 DO (-)
6 RX+
1 DO (+)
9 TX-
8 DI (-)
8 TX+
5 DI (+)
5 GND
6 GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
7 DO (-)
2 RX+
2 RX+
1 DO (+)
3 TX-
3 TX-
8 DI (-)
4 TX+
4 TX+
5 DI (+)
5 GND
5 GND
6 GND
RS485 4W 9P D-Sub
Male
1 RX-
7 DO (-)
2 RX+
1 DO (+)
3 TX-
8 DI (-)
4 TX+
5 DI (+)
5 GND
6 GND
980
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
1 RX-
7 DO (-)
2 RX+
1 DO (+)
3 TX-
8 DI (-)
4 TX+
5 DI (+)
5 GND
6 GND
COM3 RS232 9P
D-Sub Female
CTI2500-C200 RS232
9P D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
CTI2500-C200 RS232
9P D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
CTI2500-C200 RS232
9P D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
CTI2500-C200 RS232
9P D-Sub Female
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
981
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
CTI2500-C200 RS232
9P D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Aug/31/2011
Driver released.
V1.20
Jun/08/2014
Added register: VD
V1.30
Nov/18/2014
982
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
Ethernet
Port no.
1956
On-line simulator
Yes
Options
Notes
Multi-HMI connect
Yes
983
2. Switch to Class View tab and drag the object to the editing area.
3. In the editing area select the object, and in Properties tab select true for
Visualized.
984
5. After editing, the MaeExp.txt file will be generated under the project folder, and
the file can be imported to EasyBuilder. If false was selected for Visualized in step
3, then the file will not be imported to EasyBuilder.
6. Launch EasyBuilder, select SIGMATEK driver and set the parameters, and then
select Import Tag.
985
7.
Click Get Tag Verifying tags with PLC, and then select the MaeExp.txt file
generated in step 5. Please check that the PLC is on line for verification. The
address tags can also be imported by clicking Get Tag Import Tag, and then run
off-line simulation. Please note that on-line simulation and download cannot be
carried out using this method.
986
Bool
bit
Byte
8-bit
DInt
Real
32-bit Float
32-bit
UDInt
32-bit
BitArray
bit
SInt
USInt
Word
Int
UInt
DWord
Memo
8-bit
8-bit
16-bit
16-bit
16-bit
32-bit
32-bit
Wiring Diagram:
HMI RJ45 Male
Wire Color
Wire Color
1 TX+
White/Orange
White/Orange
1 TX+
2 TX-
Orange
Orange
2 TX-
3 RX+
White/Green
White/Green
3 RX+
4 BD4+
Blue
Blue
4 BD4+
5 BD4-
White/Blue
White/Blue
5 BD4-
6 RX-
Green
Green
6 RX-
7 BD3+
White/Brown
White/Brown
7 BD3+
8 BD3-
Brown
Brown
8 BD3-
987
Driver Version:
Version
Date
Description
V1.00
Jan/28/2016
Driver released.
988
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
RS232
RS232/RS485 2W
Baud rate
19200
9600~115200
Data bits
Parity
None
None,Odd
Stop bits
1~32
Device Address:
Bit/Word
Device Type
Format
Range
Memo
ID
DDDDD
0 ~ 99999
ID_30
DDDDD
30
Use Unicode
ID_35000
DDDDD
35000
String
ID_35001
DDDDD
35001
String
ID Address List:
ID No.
Data Length
Data Type
Write / Read
Decimal Place*
BYT2
UDEC
Yes/Yes
30
BYT4
HEX
No/Yes
Hex
36
BYT4
SDEC
Yes/Yes
0.0001
38
BYT4
UDEC
Yes/Yes
0.0001
39
BYT4
SDEC
Yes/Yes
0.0001
40
BYT4
SDEC
No/Yes
0.0001
41
BYT4
SDEC
No/Yes
0.0001
43
BYT2
UDEC
Yes/Yes
47
BYT4
SDEC
Yes/Yes
48
BYT4
SDEC
Yes/Yes
989
ID No.
Data Length
Data Type
Write / Read
Decimal Place*
49
BYT4
SDEC
Yes/Yes
50
BYT4
SDEC
Yes/Yes
51
BYT4
SDEC
Yes/Yes
53
BYT4
SDEC
Yes/Yes
55
BYT2
UDEC
Yes/Yes
57
BYT4
UDEC
Yes/Yes
80
BYT2
SDEC
Yes/Yes
0.1
82
BYT2
UDEC
Yes/Yes
0.1
83
BYT2
SDEC
Yes/Yes
0.1
84
BYT2
SDEC
No/Yes
0.1
85
BYT2
UDEC
Yes/Yes
100
BYT2
UDEC
Yes/Yes
101
BYT2
UDEC
Yes/Yes
0.1
102
BYT2
UDEC
Yes/Yes
0.1
103
BYT4
SDEC
Yes/Yes
104
BYT2
UDEC
Yes/Yes
109
BYT4
UDEC
Yes/Yes
0.001
110
BYT4
UDEC
No/Yes
0.001
111
BYT4
UDEC
Yes/Yes
0.001
112
BYT4
UDEC
No/Yes
0.001
113
BYT4
UDEC
Yes/Yes
0.0001
116
BYT4
UDEC
Yes/Yes
124
BYT4
SDEC
Yes/Yes
0.0001
125
BYT4
SDEC
Yes/Yes
0.0001
126
BYT2
SDEC
Yes/Yes
0.1
136
BYT4
SDEC
Yes/Yes
137
BYT4
SDEC
Yes/Yes
147
BYT2
HEX
Yes/Yes
Hex
150
BYT4
SDEC
Yes/Yes
153
BYT4
SDEC
Yes/Yes
154
BUT2
HEX
Yes/Yes
Hex
157
BYT4
SDEC
Yes/Yes
0.0001
159
BYT4
UDEC
Yes/Yes
173
BYT4
SDEC
Yes/Yes
990
ID No.
Data Length
Data Type
Write / Read
Decimal Place*
193
BYT2
UDEC
Yes/Yes
209
BYT4
UDEC
Yes/Yes
0.0001
210
BYT4
UDEC
Yes/Yes
0.0001
211
BYT2
UDEC
Yes/Yes
0.1
212
BYT2
UDEC
Yes/Yes
0.1
222
BYT4
SDEC
Yes/Yes
225
BYT2
HEX
Yes/Yes
Hex
228
BYT4
UDEC
Yes/Yes
230
BYT4
UDEC
Yes/Yes
268
BYT4
UDEC
Yes/Yes
278
BYT4
UDEC
Yes/Yes
32768
BYT2
UDEC
Yes/Yes
0.1
32769
BYT4
UDEC
Yes/Yes
0.001
32770
BYT4
UDEC
Yes/Yes
0.001
32771
BYT2
UDEC
Yes/Yes
0.1
32772
BYT4
UDEC
Yes/Yes
0.0001
32773
BYT4
HEX
Yes/Yes
Hex
32774
BYT2
UDEC
Yes/Yes
0.1
32775
BYT2
UDEC
Yes/Yes
32776
BYT2
UDEC
Yes/Yes
32777
BYT2
SDEC
Yes/Yes
0.1
32778
BYT4
SDEC
Yes/Yes
0.0001
32779
BYT4
SDEC
Yes/Yes
0.0001
32780
BYT4
UDEC
Yes/Yes
0.1
32781
BYT4
UDEC
Yes/Yes
0.1
32782
BYT4
UDEC
Yes/Yes
0.1
32783
BYT2
UDEC
Yes/Yes
32784
BYT4
SDEC
Yes/Yes
32785
BYT2
UDEC
Yes/Yes
32786
BYT4
SDEC
Yes/Yes
32787
BYT4
UDEC
Yes/Yes
32788
BYT4
SDEC
Yes/Yes
32789
BYT4
UDEC
Yes/Yes
32790
BYT4
SDEC
Yes/Yes
991
ID No.
Data Length
Data Type
Write / Read
Decimal Place*
32791
BYT4
UDEC
Yes/Yes
32792
BYT4
SDEC
Yes/Yes
32793
BYT4
UDEC
Yes/Yes
32794
BYT4
SDEC
Yes/Yes
32797
BYT4
HEX
No/Yes
Hex
32798
BYT4
HEX
No/No
Hex
32799
BYT4
HEX
No/No
Hex
32800
BYT4
HEX
Yes/Yes
Hex
32801
BYT4
HEX
Yes/Yes
Hex
32802
BYT4
HEX
Yes/Yes
Hex
32803
BYT4
HEX
Yes/Yes
Hex
32804
BYT4
HEX
Yes/Yes
Hex
32805
BYT4
HEX
Yes/Yes
Hex
32806
BYT4
UDEC
Yes/Yes
32807
BYT4
UDEC
Yes/Yes
32808
BYT4
UDEC
Yes/Yes
32809
BYT4
UDEC
Yes/Yes
32836
BYT2
UDEC
No/Yes
32845
BYT2
UDEC
Yes/Yes
32846
BYT2
SDEC
Yes/Yes
32847
BYT2
SDEC
Yes/Yes
32848
BYT2
UDEC
Yes/Yes
32849
BYT2
SDEC
Yes/Yes
32850
BYT2
SDEC
Yes/Yes
32851
BYT2
SDEC
Yes/Yes
32852
BYT2
SDEC
Yes/Yes
32853
BYT2
SDEC
Yes/Yes
32854
BYT2
SDEC
Yes/Yes
32865
BYT2
UDEC
Yes/Yes
32866
BYT2
UDEC
Yes/Yes
32867
BYT2
UDEC
Yes/Yes
32868
BYT2
UDEC
Yes/Yes
32874
BYT2
UDEC
Yes/Yes
32875
BYT2
UDEC
Yes/Yes
992
ID No.
Data Length
Data Type
Write / Read
Decimal Place*
32876
BYT2
UDEC
Yes/Yes
32877
BYT2
UDEC
Yes/Yes
32880
BYT2
UDEC
Yes/Yes
32881
BYT2
UDEC
Yes/Yes
32882
BYT2
UDEC
Yes/Yes
32883
BYT2
UDEC
Yes/Yes
32891
BYT2
UDEC
Yes/Yes
32892
BYT4
UDEC
Yes/Yes
32893
BYT4
UDEC
Yes/Yes
32922
BYT2
UDEC
Yes/Yes
32925
BYT2
HEX
Yes/Yes
Hex
32926
BYT2
HEX
Yes/Yes
Hex
32927
BYT2
HEX
Yes/Yes
Hex
32928
BYT2
UDEC
Yes/Yes
0.1
32929
BYT2
UDEC
Yes/Yes
0.1
32934
BYT2
UDEC
Yes/Yes
32935
BYT2
UDEC
Yes/Yes
0.1
32936
BYT4
HEX
Yes/Yes
Hex
32940
BYT4
SDEC
Yes/Yes
32947
BYT4
UDEC
Yes/Yes
32952
BYT4
UDEC
Yes/Yes
32953
BYT2
HEX
Yes/Yes
Hex
32956
BYT2
UDEC
Yes/Yes
32958
BYT2
UDEC
Yes/Yes
32959
BYT2
UDEC
Yes/Yes
32964
BYT2
UDEC
Yes/Yes
32966
BYT2
SDEC
Yes/Yes
32967
BYT2
UDEC
Yes/Yes
32968
BYT2
UDEC
Yes/Yes
0.1
32978
BYT2
UDEC
Yes/Yes
32979
BYT2
UDEC
Yes/Yes
32980
BYT2
UDEC
Yes/Yes
32981
BYT2
UDEC
Yes/Yes
32992
BYT2
UDEC
Yes/Yes
0.1
993
ID No.
Data Length
Data Type
Write / Read
Decimal Place*
32993
BYT2
UDEC
Yes/Yes
0.1
33700
BYT2
UDEC
Yes/Yes
33701
BYT2
UDEC
Yes/Yes
33702
BYT2
UDEC
Yes/Yes
33703
BYT2
UDEC
Yes/Yes
33704
BYT2
UDEC
Yes/Yes
33705
BYT2
UDEC
Yes/Yes
33706
BYT2
UDEC
Yes/Yes
33707
BYT2
UDEC
Yes/Yes
33708
BYT2
UDEC
Yes/Yes
33709
BYT2
UDEC
Yes/Yes
33710
BYT2
UDEC
Yes/Yes
33711
BYT2
UDEC
Yes/Yes
33712
BYT2
UDEC
Yes/Yes
33713
BYT2
UDEC
Yes/Yes
33714
BYT2
UDEC
Yes/Yes
33721
BYT2
UDEC
Yes/Yes
33722
BYT2
UDEC
Yes/Yes
33724
BYT2
UDEC
Yes/Yes
33725
BYT2
UDEC
Yes/Yes
33729
BYT2
UDEC
Yes/Yes
33730
BYT2
UDEC
Yes/Yes
33731
BYT2
UDEC
Yes/Yes
33732
BYT2
UDEC
No/Yes
33800
BYT2
UDEC
Yes/Yes
33801
BYT2
UDEC
Yes/Yes
33802
BYT2
UDEC
Yes/Yes
33803
BYT2
UDEC
Yes/Yes
33804
BYT2
UDEC
Yes/Yes
33805
BYT2
UDEC
Yes/Yes
33806
BYT2
UDEC
Yes/Yes
33807
BYT2
UDEC
Yes/Yes
33808
BYT2
UDEC
Yes/Yes
33809
BYT2
UDEC
Yes/Yes
994
ID No.
Data Length
Data Type
Write / Read
Decimal Place*
33810
BYT2
UDEC
Yes/Yes
33811
BYT2
UDEC
Yes/Yes
33812
BYT2
UDEC
Yes/Yes
33813
BYT2
UDEC
Yes/Yes
33814
BYT2
UDEC
Yes/Yes
33815
BYT2
UDEC
Yes/Yes
33816
BYT2
UDEC
Yes/Yes
33817
BYT2
UDEC
Yes/Yes
33818
BYT2
UDEC
Yes/Yes
33819
BYT2
UDEC
Yes/Yes
33820
BYT2
UDEC
Yes/Yes
33839
BYT2
UDEC
Yes/Yes
33840
BYT2
UDEC
Yes/Yes
33859
BYT2
UDEC
Yes/Yes
33860
BYT2
UDEC
Yes/Yes
33869
BYT2
UDEC
Yes/Yes
33880
BYT2
UDEC
Yes/Yes
33889
BYT2
UDEC
Yes/Yes
33890
BYT2
UDEC
Yes/Yes
33899
BYT2
UDEC
Yes/Yes
34000
BYT2
UDEC
Yes/Yes
34001
BYT2
UDEC
Yes/Yes
34002
BYT2
UDEC
Yes/Yes
34003
BYT2
UDEC
Yes/Yes
34004
BYT2
UDEC
Yes/Yes
34005
BYT2
UDEC
Yes/Yes
34006
BYT2
UDEC
Yes/Yes
34007
BYT2
UDEC
Yes/Yes
34008
BYT2
UDEC
Yes/Yes
34009
BYT2
UDEC
Yes/Yes
34010
BYT2
UDEC
Yes/Yes
34011
BYT2
UDEC
Yes/Yes
34012
BYT2
UDEC
Yes/Yes
34013
BYT2
UDEC
Yes/Yes
995
ID No.
Data Length
Data Type
Write / Read
Decimal Place*
34014
BYT2
UDEC
Yes/Yes
34015
BYT2
UDEC
Yes/Yes
34016
BYT2
UDEC
Yes/Yes
34017
BYT2
UDEC
Yes/Yes
34018
BYT2
UDEC
Yes/Yes
34019
BYT2
UDEC
Yes/Yes
34023
BYT2
UDEC
Yes/Yes
34025
BYT2
UDEC
Yes/Yes
34042
BYT2
UDEC
Yes/Yes
34043
BYT2
UDEC
Yes/Yes
0.01
34044
BYT2
UDEC
Yes/Yes
0.01
34045
BYT2
UDEC
Yes/Yes
0.01
34046
BYT2
UDEC
Yes/Yes
0.01
34047
BYT2
UDEC
Yes/Yes
0.01
34048
BYT2
UDEC
Yes/Yes
0.01
34049
BYT2
UDEC
Yes/Yes
0.01
34050
BYT2
UDEC
Yes/Yes
0.1
34051
BYT2
UDEC
Yes/Yes
0.01
34052
BYT2
UDEC
Yes/Yes
0.1
34053
BYT2
UDEC
Yes/Yes
34054
BYT2
UDEC
Yes/Yes
0.1
34055
BYT2
UDEC
Yes/Yes
0.1
34056
BYT2
UDEC
Yes/Yes
34070
BYT2
UDEC
Yes/Yes
34148
BYT2
UDEC
Yes/Yes
0.001
34149
BYT2
UDEC
Yes/Yes
0.1
34164
BYT2
UDEC
Yes/Yes
0.01
34167
BYT2
UDEC
Yes/Yes
0.01
34177
BYT2
UDEC
Yes/Yes
34178
BYT2
UDEC
Yes/Yes
34179
BYT2
UDEC
Yes/Yes
34180
BYT2
UDEC
Yes/Yes
34182
BYT4
SDEC
Yes/Yes
35000
/* Depends on Text */ 0
ASCI
No/Yes
ASCII
996
ID No.
Data Length
Data Type
Write / Read
Decimal Place*
35001
/* Depends on Text */ 0
ASCI
No/Yes
ASCII
35002
BYT4
HEX
No/Yes
35003
BYT2
HEX
No/Yes
Hex
35004
BYT2
UDEC
No/Yes
0.1
35005
BYT2
UDEC
No/Yes
0.1
35006
BYT2
UDEC
No/Yes
0.1
35007
BYT2
UDEC
No/Yes
0.1
35008
BYT2
UDEC
No/Yes
0.1
35009
BYT2
UDEC
No/Yes
0.1
35010
BYT2
UDEC
No/Yes
0.1
35011
BYT2
UDEC
No/Yes
36000
BYT2
UDEC
No/Yes
36001
BYT2
UDEC
No/Yes
36002
BYT4
SDEC
No/Yes
36003
BYT4
SDEC
No/Yes
36004
BYT4
UDEC
No/Yes
36005
BYT4
UDEC
No/Yes
36006
BYT2
UDEC
No/Yes
36007
BYT2
UDEC
No/Yes
36008
BYT2
UDEC
No/Yes
36009
BYT2
UDEC
No/Yes
36010
BYT2
UDEC
No/Yes
36011
BYT2
UDEC
No/Yes
36012
BYT4
UDEC
No/Yes
36013
BYT4
UDEC
No/Yes
36019
BYT2
UDEC
Yes/Yes
36020
BYT2
UDEC
Yes/Yes
36021
BYT2
UDEC
Yes/Yes
36022
BYT2
UDEC
Yes/Yes
36023
BYT2
UDEC
Yes/Yes
36100
BYT4
UDEC
Yes/Yes
36101
BYT4
UDEC
Yes/Yes
36102
BYT4
UDEC
Yes/Yes
36103
BYT4
UDEC
Yes/Yes
997
ID No.
Data Length
Data Type
Write / Read
Decimal Place*
36104
BYT4
UDEC
Yes/Yes
*Note: If the decimal place of ID is 0.0001, please set [Right of decimal Pt.] of the object to
4.
Wiring Diagram:
The following is the view from the soldering point of a cable.
RS-232
eMT3000 series
COM1 RS232 9P
COM3 RS232 9P
X5 Port RS232 9P
D-Sub Female
D-Sub Female
D-Sub Male
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
X5 Port RS232 9P
D-Sub Male
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
X5 Port RS232 9P
D-Sub Male
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
998
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
X5 Port RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
X5 Port RS232 9P
D-Sub Male
9 RX
2 TX
6 TX
3 RX
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
X5 Port RS485 2W 9P
D-Sub Male
1 RX-
6 Data-
4 RS485-
2 RX+
9 Data+
1 RS485+
5 GND
5 GND
5 GND
COM2 RS485 2W
COM3 RS485 2W
X5 Port RS485 2W 9P
9P D-Sub Female
9P D-Sub Female
D-Sub Male
7 RX-
4 Data-
4 RS485-
6 RX+
1 Data+
1 RS485+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
X5 Port RS485 2W 9P
D-Sub Male
1 RX-
7 Data-
4 RS485-
2 RX+
8 Data+
1 RS485+
5 GND
9 GND
5 GND
999
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
X5 Port RS485 2W 9P
D-Sub Male
1 RX-
6 Data-
4 RS485-
2 RX+
9 Data+
1 RS485+
5 GND
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
X5 Port RS485 2W 9P
D-Sub Male
1 RX-
6 Data-
4 RS485-
2 RX+
9 Data+
1 RS485+
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
X5 Port RS485 2W 9P
D-Sub Male
1 RX-
7 Data-
4 RS485-
2 RX+
8 Data+
1 RS485+
5 GND
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Mar/27/2012
Driver released.
V1.10
Jul/20/2012
1000
HMI Setting:
Parameters
Recommended
Options
PLC type
Intelligent Servo
PLC I/F
RS232
Baud rate
9600
9600~115200
Data bits
7 or 8
Parity
None
Stop bits
1 or 2
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
Register_32bit
HHHH
0 ~ 270f
32bit signed
DW
Register_H
HHHH
0 ~ 270f
32bit Hex
UPD
HHHHH
0 ~ 1869f
STOP
HHHHH
0 ~ 1869f
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TD
3 TX
7 TX
3 RD
5 GND
5 GND
5 GND
1001
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TD
3 TX
3 RD
5 GND
5 GND
2 RX
2 TD
3 TX
3 RD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TD
3 TX
4 TX
7 TX
3 RD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TD
6 TX
3 RD
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Nov/06/2009
Driver released.
1002
TECO Inverter
Supported Series: TECO Inverter series, 7300CV model.
HMI Setting:
Parameters
Recommended
PLC type
TECO Inverter
PLC I/F
RS232
Baud rate
38400
Data bits
Parity
None
Stop bits
Options
Notes
RS232/RS485
Device Address:
Bit/Word Device type Format
Range
Memo
0x
DDDDD
1 ~ 65535
Output Bit
1x
DDDDD
1 ~ 65535
3x_Bit
4x_Bit
6x_Bit
0x (0x0f)
DDDDD
1 ~ 65535
3x
DDDDD
1 ~ 65535
4x
DDDDD
1 ~ 65535
Output Register
DW
5x
DDDDD
1 ~ 65535
6x
DDDDD
1 ~ 65535
1003
Wiring Diagram:
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
7 RTS
7 VCC
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
7 RTS
7 VCC
1004
2 RX
2 TX
3 TX
3 RX
5 GND
5 GND
7 RTS
7 VCC
Driver Version:
Version
Date
Description
V1.00
Jul/27/2009
Driver released.
1005
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
PLC I/F
RS485 4W/2W
RS485 4W/2W
Baud rate
19200
Data bits
7, 8
Parity
Even
Stop bits
1, 2
0-255
PLC Setting:
RS422 port: WS041=120, WS042=1;
RS485 terminals: WS044=120, WS045=1.
Device Address:
Bit/Word
B
Device type
X
Format
DDD
Range
1 ~ 384
Memo
Input relay
DDD
1 ~ 384
Output relay
DDDD
1 ~ 2048
Auxiliary relay
DDD
1 ~ 369
DDD
1 ~ 369
W
W
DDDD
1 ~ 1024
DDDD
1 ~ 2048
Auxiliary register
WS
DDD
1 ~ 128
System register
DDDD
1 ~ 2033
WC
DDD
1 ~ 912
1006
Wiring Diagram:
The following is the view from the soldering point of a cable.
TP02 Series MMI RS422 port : 9P D-Sub to 9P D-Sub
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
8 TX-
2 RX+
3 TX+
3 TX-
7 RX-
4 TX+
2 RX+
5 GND
cMT/mTV series
COM2 RS485 4W
RS485 4W 9P D-Sub
9P D-Sub Female
Male
7 RX-
8 TX-
6 RX+
3 TX+
9 TX-
7 RX-
8 TX+
2 RX+
5 GND
MT8000iE/MT8000XE series except MT8050iE
COM1 RS485 4W
9P D-Sub Male
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
8 TX-
2 RX+
2 RX+
3 TX+
3 TX-
3 TX-
7 RX-
4 TX+
4 TX+
2 RX+
5 GND
5 GND
RS485 4W 9P D-Sub
Male
1 RX-
8 TX-
2 RX+
3 TX+
3 TX-
7 RX-
4 TX+
2 RX+
5 GND
1007
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
1 RX-
8 TX-
2 RX+
3 TX+
3 TX-
7 RX-
4 TX+
2 RX+
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
T/R-
2 RX+
9 Data+
T/R+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W Terminal
7 RX-
4 Data-
T/R-
6 RX+
1 Data+
T/R+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
7 Data-
T/R-
2 RX+
8 Data+
T/R+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
T/R-
2 RX+
9 Data+
T/R+
5 GND
5 GND
1008
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
T/R-
2 RX+
9 Data+
T/R+
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W Terminal
1 RX-
7 Data-
T/R-
2 RX+
8 Data+
T/R+
5 GND
5 GND
Driver Version:
Version
Date
V1.10
Jan/25/2010
Description
1009
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485 4W
Baud rate
19200
9600, 19200
Data bits
Parity
None
Stop bits
1-255
Notes
Device Address:
Bit/Word
B
Device type
C
Format
DDDD
Range
0 ~ 9999
C256
DDDD
256 ~ 9999
DDDD
0 ~ 9999
DDDD
0 ~ 9999
DDDD
0 ~ 9999
OOO
0 ~ 377
B
W
OOO
0 ~ 377
DDDD
0 ~ 9999
DDDD
0 ~ 9999
DDDD
0 ~ 9999
T_Curent
DDDD
0 ~ 9999
C_Curent
DDDD
0 ~ 9999
T_Preset
DDDD
0 ~ 9999
C_Preset
DDDD
0 ~ 9999
DW
C200_Curent DDDD
C200_Preset DDDD
200 ~ 9999
C256_Curent DDDD
C256_Preset DDDD
256 ~ 9999
DW
DW
DW
200 ~ 9999
256 ~ 9999
1010
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
RS485 4W 8P Mini-DIN
Male
1 RX-
4 TX-
2 RX+
7 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
3 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 8P Mini-DIN
Male
7 RX-
4 TX-
6 RX+
7 TX+
9 TX-
1 RX-
8 TX+
2 RX+
5 GND
3 GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 8P Mini-DIN
Male
1 RX-
1 RX-
4 TX-
2 RX+
2 RX+
7 TX+
3 TX-
3 TX-
1 RX-
4 TX+
4 TX+
2 RX+
5 GND
5 GND
3 GND
RS485 4W 8P Mini-DIN
Male
1 RX-
4 TX-
2 RX+
7 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
3 GND
1011
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 8P Mini-DIN
Male
1 RX-
4 TX-
2 RX+
7 TX+
3 TX-
1 RX-
4 TX+
2 RX+
5 GND
3 GND
View from the
soldering point
of a cable.
Driver Version:
Version
Date
V1.10
Nov/13/2009
V1.20
Sep/18/2015
Description
Added register: C256/ C200_Curent/ C200_Preset/
C256_Curent/ C256_Preset
1012
TINHAO
Website: www.chinastrand.com
HMI Setting:
Parameters
Recommended
PLC type
TINHAO
PLC I/F
RS485 2W
Baud rate
19200
Data bits
Parity
None
Stop bits
Options
Notes
Device Address:
Bit/Word Device type
Format
Range
Commend1
DDD
0 ~ 255
Commend2
DDD
0 ~ 255
Commend3
DDD
0 ~ 255
Commend4
DDD
0 ~ 255
Commend5
DDD
0 ~ 255
Commend6
DDD
0 ~ 255
Commend7
DDD
0 ~ 255
Commend8
DDD
0 ~ 255
Commend9
DDD
0 ~ 255
Commend10
DDD
0 ~ 255
Commend11
DDD
0 ~ 255
Commend12
DDD
0 ~ 255
Commend13
DDD
0 ~ 255
Commend14
DDD
0 ~ 255
Commend15
DDD
0 ~ 255
Commend16
DDD
0 ~ 255
Commend17
DDD
0 ~ 255
Commend18
DDD
0 ~ 255
1013
Memo
Format
Range
Commend19
DDD
0 ~ 255
Commend20
DDD
0 ~ 255
Commend21
DDD
0 ~ 255
Commend22
DDD
0 ~ 255
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
COM3 RS485 2W
RS485 terminal
9P D-Sub Female
9P D-Sub Female
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
1014
COM3 RS485 2W
9P D-Sub Male
RS485 terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Oct/14/2011
Driver released.
1015
Toptek Topvert
Supported Series: TOPVERT G1/H1/P1 series.
Website: http://www.toptek.biz/
HMI Setting:
Parameters
Recommended
PLC type
Toptek Topvert
PLC I/F
RS485 2W
Baud rate
9600
Data bits
Parity
None
Stop bits
Options
Notes
Online simulator
YES
Broadcast command
YES
YES
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
PR_Bit
DDDDDdd
PR
DDDDD
0 ~ 65535
1016
Memo
Note:
Max.read-command size (words): 16
Max.write-command size (words): 1
For G1/H1/P1 Series Inverter, if standard parameter address is in decimal= 100*G+F:
G=Group (parameter group code0~9); F=Function no. (parameter number 0~99)
For example: Pr5-20 (decimal Dec.) parameter address is expressed as 100*5+20=520.
Parameter (PrX-XX)
Address (decimal)
0-00
0*100+0=0
0-14
0*100+14=14
1-00
1*100+0=100
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
COM3 RS485 2W
RS485 2W Terminal
9P D-Sub Male
9P D-Sub Male
1 RX-
6 Data-
SG-
2 RX+
9 Data+
SG+
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W Terminal
7 RX-
4 Data-
SG-
6 RX+
1 Data+
SG+
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
7 Data-
SG-
2 RX+
8 Data+
SG+
5 GND
9 GND
1017
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
SG-
2 RX+
9 Data+
SG+
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W Terminal
1 RX-
6 Data-
SG-
2 RX+
9 Data+
SG+
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W Terminal
1 RX-
7 Data-
SG-
2 RX+
8 Data+
SG+
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.00
Dec/08/2010
Driver released.
1018
TOSHIBA INVERTER VF
Supported Series: Toshiba Invertor Protocol (ASCII code).
HMI Setting:
Parameters
Recommended
PLC type
TOSHIBA INVERTER VF
PLC I/F
RS485 2W
RS422, RS485
Baud rate
9600
9600, 19200
Data bits
7 or 8
Parity
Even
Stop bits
1 or 2
0-99
Online simulator
YES
Options
Notes
Device Address:
Bit/Word Device type
Format
Range
Cmd. No B
HHHHdd
0 ~ 270f15
Cmd. No
HHHH
0 ~ ffff
Memo
Parameters and data memory
Wiring Diagram:
Note:
Before connecting with TOSHIBA INVERTER VF, make sure the SW1 of both sides are in
the correct position. (SW1: wiring method selector switch)
1019
RS-485
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
Male
1 RX-
6 Data-
5 Data-
2 RX+
9 Data+
4 Data+
5 GND
5 GND
8 Gnd
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P RJ45
Male
7 RX-
4 Data-
5 Data-
6 RX+
1 Data+
4 Data+
5 GND
5 GND
8 Gnd
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
Male
1 RX-
7 Data-
5 Data-
2 RX+
8 Data+
4 Data+
5 GND
9 GND
8 Gnd
1020
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
Male
1 RX-
6 Data-
5 Data-
2 RX+
9 Data+
4 Data+
5 GND
5 GND
8 Gnd
COM3 RS485 2W
9P D-Sub Male
RS485 2W 8P RJ45
Male
1 RX-
6 Data-
5 Data-
2 RX+
9 Data+
4 Data+
5 GND
5 GND
8 Gnd
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 8P RJ45
Male
1 RX-
7 Data-
5 Data-
2 RX+
8 Data+
4 Data+
5 GND
5 GND
8 Gnd
Driver Version:
Version
Date
V1.20
Apr/03/2013
Description
TOSHIBA VF-S11 driver is renamed to TOSHIBA
INVERTER VF.
1021
TOSHIBA T Series
Supported Series: Toshiba T series, S2E.
Website: http://www.tic.toshiba.com
HMI Setting:
Parameters
Recommended Options
PLC type
TOSHIBA T Series
PLC I/F
RS232
RS232/RS485
Baud rate
9600
Data bits
7,8
Parity
Odd
Stop bits
1, 2
0-255
Online simulator
YES
Notes
In accordance with PLC port
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDh
0 ~ 4095f
Input Bit
DDDDh
0 ~ 4095f
Output Bit
DDDDh
0 ~ 8191f
Auxiliary Bit
DDDDh
0 ~ 4095f
Special Bit
DDDDh
0 ~ 4095f
DDDDh
0 ~ 8191f
DDD
0 ~ 999
Timer Register
DDD
0 ~ 511
Counter Register
DDDD
0 ~ 8191
Data Memory
SW
DDD
0 ~ 255
Special Register
XW
DDD
0 ~ 255
Input Register
1022
Bit/Word
Device type
Format
Range
Memo
YW
DDD
0 ~ 255
Output Register
RW
DDD
0 ~ 999
Auxiliary Register
LW
DDD
0 ~ 255
DDDD
0 ~ 1023
DDDD
0 ~ 8191
Wiring Diagram:
The following is the view from the soldering point of a cable.
Toshiba T1 PRG RS232 : 9P D-Sub to 8P Mini- DIN
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
8 RX
6 TXD
3 TX
7 TX
8 RXD
5 GND
5 GND
5 GND
4 RTS
7 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
6 TXD
3 TX
8 RXD
5 GND
5 GND
4 RTS
7 CTS
short
RS232 8P Mini-DIN
Male
2 RX
6 TXD
3 TX
8 RXD
5 GND
5 GND
4 RTS
7 CTS
1023
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 8P Mini-DIN
Male
2 RX
6 RX
8 RX
6 TXD
3 TX
4 TX
7 TX
8 RXD
5 GND
5 GND
5 GND
5 GND
4 RTS
7 CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
9 RX
6 TXD
6 TX
8 RXD
5 GND
5 GND
4 RTS
7 CTS
short
View from the
soldering point
of a cable.
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
1024
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
1025
short
1 RX-
11 TXB
2 RX+
3 TXA
3 TX-
10 RXB
4 TX+
2 RXA
5 GND
7 SG
5 RTSA
4 CTSA
13 RTSB
12 CTSB
short
short
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
11 TXB
6 RX+
3 TXA
9 TX-
10 RXB
8 TX+
2 RXA
5 GND
7 SG
5 RTSA
4 CTSA
13 RTSB
12 CTSB
short
short
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
11 TXB
2 RX+
2 RX+
3 TXA
3 TX-
3 TX-
10 RXB
4 TX+
4 TX+
2 RXA
5 GND
5 GND
7 SG
5 RTSA
4 CTSA
13 RTSB
12 CTSB
1026
short
short
1 RX-
11 TXB
2 RX+
3 TXA
3 TX-
10 RXB
4 TX+
2 RXA
5 GND
7 SG
5 RTSA
4 CTSA
13 RTSB
12 CTSB
short
short
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
11 TXB
2 RX+
3 TXA
3 TX-
10 RXB
4 TX+
2 RXA
5 GND
7 SG
5 RTSA
4 CTSA
13 RTSB
12 CTSB
short
short
Driver Version:
Version
Date
Description
V1.20
May/13/2011
1027
HMI Setting:
Parameters
Recommended Options
PLC type
PLC I/F
RS232
RS232
Baud rate
9600
9600, 19200
Data bits
7,8
Parity
None
Stop bits
1, 2
Notes
In accordance with PLC port
Device Address:
Bit/Word
Range
Memo
R_bit
HHHh
0 ~ ffff
h : Bit no.(0~f)
X_bit
HHHh
0 ~ ffff
h : Bit no.(0~f)
Y_bit
HHHh
0 ~ ffff
h : Bit no.(0~f)
L_bit
HHHh
0 ~ ffff
h : Bit no.(0~f)
G_bit
HHHh
0 ~ ffff
h : Bit no.(0~f)
H_bit
HHHh
0 ~ ffff
h : Bit no.(0~f)
T_bit
HHHh
0 ~ ffff
h : Bit no.(0~f)
C_bit
HHHh
0 ~ ffff
h : Bit no.(0~f)
S_bit
HHHh
0 ~ ffff
h : Bit no.(0~f)
E_bit
HHHh
0 ~ ffff
h : Bit no.(0~f)
HHH
0 ~ fff
HHH
0 ~ fff
HHH
0 ~ fff
HHH
0 ~ fff
HHH
0 ~ fff
HHH
0 ~ fff
HHH
0 ~ fff
HHH
0 ~ fff
HHH
0 ~ fff
1028
Bit/Word
Range
HHH
0 ~ fff
HHH
0 ~ fff
HHH
0 ~ fff
HHH
0 ~ fff
HHH
0 ~ fff
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
short
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
1029
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
Driver Version:
Version
Date
Description
V1.10
Aug/17/2012
1030
short
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485
RS232/RS485/Ethernet
Baud rate
9600
9600~115200
Data bits
7, 8
Parity
Even
Stop bits
1, 2
Port no.
502
Online simulator
Options
Notes
0-255
YES
PLC Setting:
Communication mode
PLC mode
Device Address:
Bit/Word
B
Device type
VR_Bit
Format
Range
DDDDdd
0 ~ 409615
Table_Bit
DDDDDdd
0 ~ 3199915
W
W
VR
Table
DDDD
0 ~ 4096
DDDDD
0 ~ 31999
1031
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.3
Trio : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
RTS
CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
RTS
CTS
1032
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
TXD
6 TX
RXD
5 GND
GND
RTS
CTS
short
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
1033
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
cMT/mTV series
1034
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
1035
Etehernet cable:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
May/27/2011
Driver released.
V1.20
Oct/29/2014
1036
HMI Setting:
Parameters
Recommended
PLC type
PLC I/F
RS485
RS232/RS485/Ethernet
Baud rate
9600
9600~115200
Data bits
7, 8
Parity
Even
Stop bits
1, 2
Port no.
502
Online simulator
Options
Notes
0-255
YES
PLC Setting:
Communication mode
PLC mode
Device Address:
Bit/Word
B
Device type
VR_Bit
Format
Range
DDDDdd
0 ~ 409631
VR_INT_Bit
DDDDdd
0 ~ 409631
Table_Bit
DDDDDdd
0 ~ 3199931
VR
DDDD
0 ~ 4096
W
W
VR_INT
Table
DDDD
0 ~ 4096
DDDDD
0 ~ 31999
Table_INT
DDDDD
0 ~ 31999
1037
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.3
Trio : RS232
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
TXD
3 TX
7 TX
RXD
5 GND
5 GND
GND
RTS
CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
2 RX
TXD
3 TX
RXD
5 GND
GND
RTS
CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
TXD
3 TX
4 TX
7 TX
RXD
5 GND
5 GND
5 GND
GND
RTS
CTS
1038
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
TXD
6 TX
RXD
5 GND
GND
RTS
CTS
short
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 9P D-Sub
Male
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
GND
1039
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 9P D-Sub
Male
1 RX-
TX-
2 RX+
TX+
3 TX-
RX-
4 TX+
RX+
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
GND
cMT/mTV series
1040
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
GND
1041
Ethernet cable:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Apr/20/2012
Driver released.
V1.30
Oct/29/2014
1042
VIGOR
Supported Series: VIGOR M Series, VB Series, VH Series.
Website: http://www.vigorplc.com.tw/
HMI Setting:
Parameters
Recommended
PLC type
VIGOR
PLC I/F
RS485 2W
Baud rate
19200
Data bits
Parity
None
Stop bits
Options
Notes
RS232, RS485 4W
Select "7' for V1.10 and
previous versions.
Select "Even" for V1.10 and
previous versions.
Device Address:
Bit/Word
Device type
Format
Range
OOO
0 ~ 377
OOO
0 ~ 377
DDDD
0 ~ 7999
DDD
0 ~ 255
DDD
0 ~ 255
SM
DDDD
9000 ~ 9255
DDD
0 ~ 999
TV
DDD
0 ~ 255
CV
DDD
0 ~ 199
DDDD
0 ~ 9255
CV2
DDD
200 ~ 255
SD
DDDD
9000 ~ 9255
1043
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
RS485 4W 6P Terminal
1 RX2 RX+
3 TX4 TX+
5 GND
cMT/mTV series
TXTX+
RXRX+
SG
COM2 RS485 4W
9P D-Sub Female
RS485 4W 6P Terminal
7 RX-
TX-
6 RX+
TX+
9 TX-
RX-
8 TX+
RX+
5 GND
SG
COM2 RS485 4W
9P D-Sub Male
RS485 4W 6P Terminal
1 RX-
1 RX-
TX-
2 RX+
2 RX+
TX+
3 TX-
3 TX-
RX-
4 TX+
4 TX+
RX+
5 GND
5 GND
SG
RS485 4W 6P Terminal
1 RX2 RX+
3 TX4 TX+
5 GND
TXTX+
RXRX+
SG
1044
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
RS485 4W 6P Terminal
1 RX2 RX+
3 TX4 TX+
5 GND
TXTX+
RXRX+
SG
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
1045
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
Driver Version:
Version
Date
V1.10
Dec/30/2008
V1.20
Mar/26/2014
Description
1.Added register: S
2.Supports Pass-Through feature.
1046
VIGOR VS Series
Supported Series: VIGOR VS Series.
Website: http://www.vigorplc.com.tw/
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
VIGOR VS Series
PLC I/F
RS485 2W
Baud rate
19200
300 ~ 115200
Data bits
Parity
None
Stop bits
0 ~ 254
Device Address:
Bit/Word
Device type
Format
Range
OOO
0 ~ 571
OOO
0 ~ 571
DDDD
0 ~ 8191
DDDD
0 ~ 4095
SM
DDDD
9000 ~ 9511
D_Bit
DDDDh
0 ~ 8999f
R_Bit
DDDDDh
0 ~ 25999f
T_Coil
DDD
0 ~ 511
T_Contact
DDD
0 ~ 511
C_Coil
DDD
0 ~ 255
C_Contact
DDD
0 ~ 255
XW
OO
0 ~ 21
YW
OO
0 ~ 21
MW
DDD
0 ~ 511
SW
DDD
0 ~ 255
DDDD
0 ~ 8999
1047
Memo
Bit/Word
Device type
Format
Range
SD
DDDD
9000 ~ 9511
DDDDD
0 ~ 25999
DDD
0 ~ 511
DDD
0 ~ 199
DW
C_32Bit
DDD
200 ~ 255
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
CP1 RS485 2W
terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
SG
COM2 RS485 2W
COM3 RS485 2W
CP1 RS485 2W
9P D-Sub Female
9P D-Sub Female
terminal
7 RX-
4 Data-
D-
6 RX+
1 Data+
D+
5 GND
5 GND
SG
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
CP1 RS485 2W
terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
9 GND
SG
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
CP1 RS485 2W
terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
SG
1048
COM3 RS485 2W
9P D-Sub Male
CP1 RS485 2W
terminal
1 RX-
6 Data-
D-
2 RX+
9 Data+
D+
5 GND
5 GND
SG
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
CP1 RS485 2W
terminal
1 RX-
7 Data-
D-
2 RX+
8 Data+
D+
5 GND
5 GND
SG
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
TX
3 TX
7 TX
RX
5 GND
5 GND
SG
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
TX
3 TX
RX
5 GND
SG
2 RX
TX
3 TX
RX
5 GND
SG
1049
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
TX
3 TX
4 TX
7 TX
RX
5 GND
5 GND
5 GND
SG
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
TX
6 TX
RX
5 GND
SG
Driver Version:
Version
Date
Description
V1.00
Jul/22/2014
Driver released.
1050
VIPA 200
HMI Setting:
Parameters
Options
PLC type
Recommend
ed
VIPA 200
PLC I/F
RS485 2w
RS485 2w
Notes
Baud rate
9600
Data bits
7,8
Parity
Even
Stop bits
1, 2
1 ~ 126
Reserved 1
30
Online simulator
YES
Broadcast command NO
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
VW_Bit
DDDDDo
0 ~ 102397
Byte
VB
DDDDD
0 ~ 10239
VW
DDDDD
0 ~ 10239
V Memory
VW_Odd
DDDDD
0 ~ 10239
V Memory
DW
VD
DDDDD
0 ~ 10239
DW
VD_Odd
DDDDD
0 ~ 10239
VW_String
DDDDD
0 ~ 10239
String
1051
Format
Range
Memo
VW_String_Odd DDDDD
0 ~ 10239
String
DW
VD_String
DDDDD
0 ~ 10239
String
DW
VD_String_Odd
DDDDD
0 ~ 10239
String
Byte
MB
DDDDD
0 ~ 10239
Byte Memory
MW
DDDDD
0 ~ 10239
Word Memory
DW
MD
DDDDD
0 ~ 10239
Word Memory
MW_Odd
DDDDD
0 ~ 10239
Word Memory
DDD
0 ~ 127
Timer
DDD
0 ~ 127
Counter
Double word and floating point value must use VD device type.
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
COM3 RS485 2W
RS485 2W 9P D-Sub
9P D-Sub Male
9P D-Sub Male
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
3 D+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
9 GND
5 GND
1052
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
5 GND
5 GND
Driver Version:
Version
Date
V2.30
Aug/17/2009
V2.40
Nov/1/2011
Description
Add device type : MD
1053
Recommended
Options
PLC type
PLC I/F
RS485 2w
Notes
RS485 2w
The HMI which has a sticker
Baud rate
9600
Data bits
7,8
Parity
Even
Stop bits
1, 2
1 ~ 126
Reserved 1
30
Online simulator
YES
Broadcast command NO
PLC Setting:
Communication mode
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
VW_Bit
DDDDDo
0 ~ 102397
VW
DDDDD
0 ~ 10239
V Memory
DW
VD
DDDDD
0 ~ 10239
VW_String
DDDDD
0 ~ 10239
String
DW
VD_String
DDDDD
0 ~ 10239
String
MW
DDDDD
0 ~ 10239
Word Memory
DDD
0 ~ 127
Timer
1054
Bit/Word
Device type
Format
Range
Memo
DDD
0 ~ 127
Counter
DW
MD
DDDDD
0 ~ 10239
Word Memory
Double word and floating point value must use VD device type.
VD register can set to any value, not necessarily a multiple of 4.
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
3 D+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
1055
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.20
Nov/16/2011
1056
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
102
Notes
0-31
Device Address:
Bit/Word
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
VW_Bit
DDDDDo
0 ~ 102397
VW
DDDDD
0 ~ 10239
V Memory
DW
VD
DDDDD
0 ~ 10239
VW_String
DDDDD
0 ~ 10239
String
DW
VD_String
DDDDD
0 ~ 10239
String
DW
MD
DDDDD
0 ~ 10239
Word Memory
Double word and floating point value must use VD device type.
1057
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
V1.20
Dec/30/2008
V1.40
Nov/15/2011
Description
Add device type : MD
1058
Recommended
PLC type
PLC I/F
RS-485 2W
Baud rate
187.5K
Data bits
Parity
Even
Stop bits
Online simulator
Options
Notes
2 ~ 31
NO
Broadcast command NO
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
DBnBit
DB0Bit ~
FFFFDDDDo 0 ~ 409699997
DDDDDo
0 ~ 655327
DB99Bit
IW
DDDD
0 ~ 4095
Input (I)
QW
DDDD
0 ~ 4095
Output (O)
MW
DDDD
0 ~ 4095
Bit Memory
DW
MD
DDDD
0 ~ 4094
Byte
MB
DDDD
0 ~ 4095
Byte
DBBn
FFFFDDDD
0 ~ 40969999
Data Register
DBn
FFFFDDDD
0 ~ 40969999
DW
DBDn
FFFFDDDD
0 ~ 40969999
DBn_String
FFFFDDDD
0 ~ 40969999
DW
DBDn_String
FFFFDDDD
0 ~ 40969999
DB0 ~ DB99
DDDDD
0 ~ 65532
* Double word and floating point value must use DBDn device type.
1059
1060
For the effectiveness of communication, users may set PLC device in STEP 7 as shown
below. In Properties MPI / Network Settings, set Highest MPI address to the number
closest to the actual device station number.
Note:
HMI sta. no. can not be the same as PLC sta. no.
Highly recommended that the device station numbers start from 0 sequentially and
correctly set [Max. station no. (MPI network)].
Available for EasyBuilder V4.50 and later.
1061
1062
c Select Sources as storage path, specify the file name then click OK.
1063
e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
1064
1065
Wiring Diagram:
The following is the view from the soldering point of a cable.
S7-200 PPI , S7-300 MPI :RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
3 D+
5 GND
5 GND
5 GND
cMT/mTV series
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
COM3 RS485 2W
RS485 2W 9P D-Sub
9P D-Sub Male
9P D-Sub Male
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
9 GND
5 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
1066
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
5 GND
5 GND
Driver Version:
Version
Date
Description
V1.90
May/26/2011
V2.00
Aug/19d/2011
1067
VIPA 300
HMI Setting:
Parameters
Recommended Options
PLC type
VIPA 300
PLC I/F
RS232
Baud rate
19200, 38400,
187.5K
Data bits
Parity
Odd
Stop bits
Notes
9600~187.5K
Device Address:
Bit/Word Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
DBnBit
FFFFDDDDo
0 ~ 409681927
DB0Bit ~
DB99Bit
DDDDo
0 ~ 81927
IW
DDDD
0 ~ 4095
Input (I)
QW
DDDD
0 ~ 4095
Output (O)
MW
DDDD
0 ~ 4095
Bit Memory
DW
MD
DDDD
0 ~ 4094
Byte
MB
DDDD
0 ~ 4095
Byte
DBBn
FFFFDDDD
0 ~ 40968192
DBn
FFFFDDDD
0 ~ 40968192
DW
DBDn
FFFFDDDD
0 ~ 40968192
DBn_String
FFFFDDDD
0 ~ 40968192
1068
Data Register
(must be even)
Data Register Double Word
(must be multiple of 4)
Data Register Double Word
(must be multiple of 4)
Format
Range
DW
DBDn_String FFFFDDDD
0 ~ 40968192
DB0-DB99
0 ~ 8192
DDDD
Memo
Data Register Double Word
(must be multiple of 4)
Data Register
(must be even)
* Double word and floating point value must use DBDn device type.
1069
1070
c Select Sources as storage path, specify the file name then click OK.
1071
e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
1072
Wiring Diagram:
The following is the view from the soldering point of a cable.
Siemens S7-300 PC Adapter : 9P D-Sub to 9P D-Sub:
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
1073
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
4 DTR
6 DSR
short
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
4 DTR
6 DSR
1074
short
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
4 DTR
6 DSR
short
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
4 DTR
6 DSR
short
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
4 DTR
6 DSR
Driver Version:
Version
Date
Description
V3.10
May/24/2011
short
short
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
102
Link type
PG
PC, OP
Rack
0-7
CPU slot
2-31
0-31
Notes
Device Address:
Bit/Word Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
DBnBit
FFFFFFDDDDo 0 ~ 6553599997
DB0Bit-DB99Bit DDDDDo
0 ~ 655327
IW
DDDD
0 ~ 4095
Input (I)
QW
DDDD
0 ~ 4095
Output (O)
MW
DDDD
0 ~ 4095
Bit Memory
DW
MD
DDDD
0 ~ 4094
DBn
FFFFFDDDD
0 ~ 655359999
DW
DBDn
FFFFFDDDD
0 ~ 655359999
DBn_String
FFFFFDDDD
0 ~ 655359999
DW
DBDn_String
FFFFFDDDD
0 ~ 655359999
DB0 ~ DB99
DDDDD
0 ~ 65532
Data Register
Byte
MB
DDDD
0 ~ 4095
(must
be even)
Bit
Memory
Byte
Byte
DBBn
FFFFFDDDD
0 ~ 655359999
* Double word and floating point value must use DBDn device type.
1076
Data Register
(must be even)
Data Register Double
Word
(must be multiple of 4)
1.
2.
2.
3.
4.
5.
Press [Settings].
Set S7-400 IP, Port no., Link type, Rack and CPU slot. (must match PLC settings)
1077
6.
1078
1079
c Select Sources as storage path, specify the file name then click OK.
1080
e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
1081
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.50
Aug/03/2012
1082
Recommended
Options
Notes
PLC type
PLC I/F
Ethernet
Port no.
102
0-31
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
DBnBit
FFFFDDDDo
0 ~ 409699997
DB0Bit-DB99Bit DDDDDo
0 ~ 655327
IW
DDDD
0 ~ 4095
Input (I)
QW
DDDD
0 ~ 4095
Output (O)
MW
DDDD
0 ~ 4095
Bit Memory
DW
MD
DDDD
0 ~ 4094
DBn
FFFFDDDD
0 ~ 40969999
DW
DBDn
FFFFDDDD
0 ~ 40969999
DBn_String
FFFFDDDD
0 ~ 40969999
DW
DBDn_String
FFFFDDDD
0 ~ 40969999
DB0 ~ DB99
DDDDD
0 ~ 65532
Byte
MB
DDDD
0 ~ 4095
Byte
DBBn
FFFFDDDD
0 ~ 40969999
Data Register
(must be even)
Data Register Double Word
(must be multiple of 4)
Data Register
(must be even)
Double word and floating point value must use DBDn device type.
1083
1084
1085
c Select Sources as storage path, specify the file name then click OK.
1086
e Under Sources there will be names of the saved files, select Export Source
to build *.AWL file.
1087
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V2.10
May/21/2011
1088
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
115200
Data bits
Parity
None
Stop bits
Notes
9600,19200,38400,57600,115200
Device Address:
Bit/Word
B
Device type
Format
Range
Memo
DDo
0 ~ 967
Input
DDo
0 ~ 487
Output
Logic result
DDo
0 ~ 327
Logic Result
RS-232
DDo
0 ~ 327
RS-232
DDo
0 ~ 997
DDo
0 ~ 597
Do
0 ~ 97
Configuration CRCs_Bit
DDo
0 ~ 197
DDo
0 ~ 177
B
W
DDDo
0 ~ 3377
0~2
DD
0 ~ 98
DD
0 ~ 58
0~8
Configuration CRCs
DD
0 ~ 18
DD
0 ~ 16
DDD
0 ~ 336
1089
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
CPU0 Port0 4P
Mini-DIN Male
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
4 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
CPU0 Port0 4P
Mini-DIN Male
2 RX
3 TX
3 TX
2 RX
5 GND
4 GND
CPU0 Port0 4P
Mini-DIN Male
2 RX
3 TX
3 TX
2 RX
5 GND
4 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
CPU0 Port0 4P
Mini-DIN Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
4 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
CPU0 Port0 4P
Mini-DIN Male
9 RX
3 TX
6 TX
2 RX
5 GND
4 GND
View from the
soldering point
of a cable.
1090
Driver Version:
Version
Date
V1.20
Mar/14/2014
Description
1091
XINJE XC Series
Supported Series: XINJE XC Series
Website: http://www.xinje.com
HMI Setting:
Parameters
Recommended
PLC type
XINJE XC Series
PLC I/F
RS232
Baud rate
19200
Data bits
Parity
Even
Stop bits
Options
Notes
RS232
0-255
Device Address:
Bit/Word
Device type
Format
Range
DDDD
0 ~ 8511
OOOO
0 ~ 1037
OOOO
0 ~ 1037
DDDD
0 ~ 1023
DDD
0 ~ 618
DDD
0 ~ 634
DDDD
0 ~ 8511
TD
DDD
0 ~ 618
CD
DDD
0 ~ 634
FD_1
DDDD
0 ~ 5000
FD_2
DDDD
8000 ~ 8511
1092
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
Driver Version: eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
8 RX
5 TX
3 TX
7 TX
4 RX
5 GND
5 GND
8 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
2 RX
5 TX
3 TX
4 RX
5 GND
8 GND
RS232 8P Mini-DIN
Male
2 RX
5 TX
3 TX
4 RX
5 GND
8 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
RS232 8P Mini-DIN
Male
2 RX
6 RX
8 RX
5 TX
3 TX
4 TX
7 TX
4 RX
5 GND
5 GND
5 GND
8 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
RS232 8P Mini-DIN
Male
9 RX
5 TX
6 TX
4 RX
5 GND
8 GND
View from the
soldering point
of a cable.
1093
Driver Version:
Version
Date
Description
V1.00
Jul/02/2009
Driver released.
1094
YAMAHA ERCD
HMI Setting:
Parameters
Recommended
Options
Notes
PLC type
YAMAHA ERCD
PLC I/F
RS232
Baud rate
9600
1200-19200
Data bits
7 or 8
Parity
Odd
None/Even/Odd
Stop bits
1 or 2
Device Address:
Bit/Word Device type
Format
Range
Memo
Bit
DI
DD
0 ~ 15
Bit
DO
0~7
Bit
EMG
Bit
SRVO
Bit
ORG_Sensor D
Bit
RESET
Bit
RUN
Bit
X_ADD
Bit
X_SUB
Word
DDD
0 ~ 999
Word
PRM
DD
0 ~ 99
Parameters (Read/Write)
Switches program number to run
Word
SWI
Word
MOVD
(Write only)
Set the parameter of RW register, and then
enter any value in this register.
1095
Format
Range
Memo
Return to original activity (Enter any value) ,
Word
ORG
Word
MODE
Word
POS
Word
NO
Word
SNO
Word
TNO
Word
PNO
The value read in address types P and POS is timed by 100, therefore, in the object setting
in EasyBuilder, set to the second place after the decimal point to get the correct value.
1096
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TX
3 TX
7 TX
2 RX
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
7 RTS
8 CTS
short
2 RX
3 TX
3 TX
2 RX
5 GND
5 GND
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TX
3 TX
4 TX
7 TX
2 RX
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
1097
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TX
6 TX
2 RX
5 GND
5 GND
7 RTS
8 CTS
short
Driver Version:
Version
Date
V1.30
Jan/04/2010
V1.40
Dec/13/2012
Description
Added registers: DIDOEMGSRVOORG_Sensor
PPRMMODEPOSNOSNOTNOPNO.
1098
YASKAWA CCMEP
Supported Series: YASKAWA CCMEP-100/ CCMEP-200
Website: http://www.yaskawa-control.co.jp/english/jigyo/mechotronics.html
HMI Setting:
Parameters
Recommended
Options
PLC type
YASKAWA CCMEP
PLC I/F
RS485 4W
Baud rate
38400
Data bits
Parity
Even
Stop bits
Notes
Device Address:
Bit/Word
Device type
Format
Range
Memo
4_Bit
DDDDDdd
100 ~ 6553515
DDDDD
1 ~ 65535
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 4W
9P D-Sub Male
RS485 4W 8P RJ45
Male
1 RX-
4 TX-
2 RX+
3 TX+
3 TX-
2 RX-
4 TX+
1 RX+
5 GND
8 GND
1099
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
RS485 4W 8P RJ45
Male
7 RX-
4 TX-
6 RX+
3 TX+
9 TX-
2 RX-
8 TX+
1 RX+
5 GND
8 GND
COM2 RS485 4W
9P D-Sub Male
RS485 4W 8P RJ45
Male
1 RX-
1 RX-
4 TX-
2 RX+
2 RX+
3 TX+
3 TX-
3 TX-
2 RX-
4 TX+
4 TX+
1 RX+
5 GND
5 GND
8 GND
RS485 4W 8P RJ45
9P D-Sub Male
Male
1 RX-
4 TX-
2 RX+
3 TX+
3 TX-
2 RX-
4 TX+
1 RX+
5 GND
8 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
RS485 4W 8P RJ45
9P D-Sub Female
Male
1 RX-
4 TX-
2 RX+
3 TX+
3 TX-
2 RX-
4 TX+
1 RX+
5 GND
8 GND
1100
Driver Version:
Version
Date
Description
V1.00
Jun/14/2012
Driver released.
1101
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485/Ethernet
RS232/RS485 2w/4w,
Ethernet
Baud rate
19200
9600~57600
Data bits
Parity
Even
Stop bits
Port no.
502
default
1-31
Notes
PLC Setting:
Communication mode
1102
1103
Note:
1. Only CNO 01 can auto communicate with one HMI. Other CNO need a ladder program
created for communication.
2. DIP SW2-2 of MP2300S must be set to OFF position during normal communication,
otherwise, IP address will be erased after reset power, and it will be unable to
communicate with HMI when set to ON position.
Device Address:
Bit/Word Device type
Format
Range
Memo
MB_1
DDDDh
0 ~ 9999f
MB 0 ~ 9999
MB_2
MB 10000 ~ 65535
IB
HHHHH
0 ~ a7ff0
Read only
IW_Bit
HHHHdd
0~ a7ff15
IW
HHHH
0 ~ a7ff
Read only
DW
IL
HHHH
0 ~ a7ff
Read only
DW (F)
IF
HHHH
0 ~ a7ff
Read only
MW
DDDDD
0 ~ 65534
Holding register
DW
ML
DDDDD
0 ~ 65533
Double word
DW (F)
MF
DDDDD 0 ~ 65533
Floating point
*: When connect via Ethernet interface the max range of IW, IL and IF would be restricted.
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub: 217IF-01, 218IF-01
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
7 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
1104
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
7 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TX
6 TX
3 RX
5 GND
7 GND
COM3 RS485 2W
9P D-Sub Male
9P D-Sub Male
Connector
1 RX-
6 Data-
2, 4 D-
2 RX+
9 Data+
1, 3 D+
5 GND
5 GND
14 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
2, 4 D-
6 RX+
1 Data+
1, 3 D+
5 GND
5 GND
cMT/mTV series
14 GND
1105
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
2, 4 D-
2 RX+
8 Data+
1, 3 D+
5 GND
9 GND
14 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
2, 4 D-
2 RX+
9 Data+
1, 3 D+
5 GND
5 GND
14 GND
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
2, 4 D-
2 RX+
9 Data+
1, 3 D+
5 GND
5 GND
14 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
1 RX-
7 Data-
2, 4 D-
2 RX+
8 Data+
1, 3 D+
5 GND
5 GND
14 GND
1 RX-
2 TX-
2 RX+
1 TX+
3 TX-
4 RX-
4 TX+
3 RX+
5 GND
14 GND
1106
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
2 TX-
6 RX+
1 TX+
9 TX-
4 RX-
8 TX+
3 RX+
5 GND
14 GND
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
2 TX-
2 RX+
2 RX+
1 TX+
3 TX-
3 TX-
4 RX-
4 TX+
4 TX+
3 RX+
5 GND
5 GND
14 GND
9P D-Sub Male
Connector
1 RX-
2 TX-
2 RX+
1 TX+
3 TX-
4 RX-
4 TX+
3 RX+
5 GND
14 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
Connector
1 RX-
2 TX-
2 RX+
1 TX+
3 TX-
4 RX-
4 TX+
3 RX+
5 GND
14 GND
1107
Ethernet cable:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
V1.70
Dec/20/2010
Description
1108
Recommended
Options
Notes
PLC type
PLC I/F
Ethernet (UDP)
Port no.
10000
PLC Setting:
Yaskawa PLC Communication Parameter Settings
(1) PLC Factory Communication Parameter Settings:
Item
Set
IP Address
192.168.1.1
Subnet Mask
255.255.255.0
Gateway IP Address
0.0.0.0
10000 (UDP)
3 (s)
500 (ms)
60 (s)
IP Assemble Time
30 (s)
1500 (bytes)
1109
3. Go to Module Details and select [218IFA] for setting relevant parameters for Ethernet
transmission.
1110
1111
Device Address:
Bit/Word
Device type
Format
Range
SB
DDDDh
0 ~ 8191f
IB
HHHHh
0 ~ fffff
OB
HHHHh
0 ~ fffff
MB
DDDDDh
0 ~ 65534f
SW
DDDD
0 ~ 8191
IW
HHHH
0 ~ ffff
OW
HHHH
0 ~ ffff
MW
DDDDD
0 ~ 65534
DW
ML
DDDDD
0 ~ 65534
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.10
Jul/21/2011
Driver released.
V1.30
Apr/17/2013
1112
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
502
Notes
PLC Setting:
How to connect one Yaskawa Ethernet device with multiple HMIs?
http://www.weintek.com/Download/MT8000/eng/FAQ/FAQ_61_How_to_connect_Yaskaw
a_Ethernet.pdf
Device Address:
Bit/Word Device type
Format
Range
MB
DDDDDh
0 ~ 65534F
IB
HHHHH
0 ~ A7FFF
Read only
IW_Bit
HHHHdd
0 ~ A7FF15
Read only
IW
HHHH
0 ~ A7FF
Read only
DW
IL
HHHH
0 ~ A7FF
Read only
DW
IF
HHHH
0 ~ A7FF
MW
DDDDD
0 ~ 65534
DW
ML
DDDDD
0 ~ 65533
DW
MF
DDDDD
0 ~ 65533
1113
Memo
Float
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Mar/19/2013
Driver released.
1114
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS485
RS232/RS485 2w/4w
Baud rate
19200
9600~57600
Data bits
Parity
Even
Stop bits
Notes
1-31
Device Address:
Bit/Word Device type
Format
Range
SB
DDDDh
0 ~ 8191F
IB
HHHHh
0 ~ FFFFF
OB
HHHHh
0 ~ FFFFF
MB
DDDDDh
0 ~ 65534F
SW
DDDD
0 ~ 8191
IW
HHHH
0 ~ FFFF
OW
HHHH
0 ~ FFFF
MW
DDDDD
0 ~ 65534
1115
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub: 217IF-01, 218IF-01
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TX
3 TX
7 TX
3 RX
5 GND
5 GND
7 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
D-Sub Female
2 RX
2 TX
3 TX
3 RX
5 GND
7 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TX
3 TX
4 TX
7 TX
3 RX
5 GND
5 GND
5 GND
7 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TX
6 TX
3 RX
5 GND
7 GND
1116
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
2, 4 D-
2 RX+
9 Data+
1, 3 D+
5 GND
5 GND
14 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
7 RX-
4 Data-
2, 4 D-
6 RX+
1 Data+
1, 3 D+
5 GND
5 GND
cMT/mTV series
14 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
7 Data-
2, 4 D-
2 RX+
8 Data+
1, 3 D+
5 GND
9 GND
14 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
2, 4 D-
2 RX+
9 Data+
1, 3 D+
5 GND
5 GND
14 GND
COM3 RS485 2W
9P D-Sub Male
1 RX-
6 Data-
2, 4 D-
2 RX+
9 Data+
1, 3 D+
5 GND
5 GND
14 GND
1117
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
1 RX-
7 Data-
2, 4 D-
2 RX+
8 Data+
1, 3 D+
5 GND
5 GND
14 GND
1 RX-
2 TX-
2 RX+
1 TX+
3 TX-
4 RX-
4 TX+
3 RX+
5 GND
14 GND
cMT/mTV series
COM2 RS485 4W
9P D-Sub Female
7 RX-
2 TX-
6 RX+
1 TX+
9 TX-
4 RX-
8 TX+
3 RX+
5 GND
14 GND
COM2 RS485 4W
9P D-Sub Male
1 RX-
1 RX-
2 TX-
2 RX+
2 RX+
1 TX+
3 TX-
3 TX-
4 RX-
4 TX+
4 TX+
3 RX+
5 GND
5 GND
14 GND
1118
1 RX-
2 TX-
2 RX+
1 TX+
3 TX-
4 RX-
4 TX+
3 RX+
5 GND
14 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 4W
9P D-Sub Female
1 RX-
2 TX-
2 RX+
1 TX+
3 TX-
4 RX-
4 TX+
3 RX+
5 GND
14 GND
Driver Version:
Version
Date
Description
V1.00
Jun/25/2013
Driver released.
1119
YASKAWA MP2300Siec
Website: http://www.yaskawa.com/site/home.nsf/home/home.html
HMI Setting:
Parameters
Recommended
Options
PLC type
YASKAWA MP2300Siec
PLC I/F
Ethernet
Port no.
44818
Assembly
instance
Input::101
Output:111
Notes
Input::101~106
Output:111~116
PLC Setting:
MP2300Siec-Motion Works IEC Express (YASKAWA) Settings:
Step 1. Before HMI communicates with MP2300Siec using Ethernet/IP, the Instance Input
and Instance Output of MP2300Siec device must be set correctly. Multiple Instances are
allowed to be built at one time, please click [Save] after setting.
1120
Step 2.Global Variables will automatically add in E/IP Input and Output data, Input and
Output data name and address type can be user-defined.
1121
1122
You may use one of the two drivers to connect Yaskawa MP2300Siec:
1. Yaskawa MP2300Siec driver.
2. Rockwell EtherNet/IP (CompactLogix) Free Tag Names driver.
(1) Yaskawa MP2300Siec driver.
Step 1. System Parameter Settings
Open EasyBuilder project, as shown in Fig. 7, Assembly Instance and Size must match
the software default factory settings, and please dont select UDP. Fig.8 below shows how
HMI Input / Output address is mapped to MP2300Siec device.
1123
1124
Fig. 10 RSLogix 5000 (Rockwell Software) Export Free Tag CSV File
1125
Step 2. As in Fig 12, in Structure Editor add Name of the new data type. The Name must
be set identically to the Data Type in Free Tag CSV file. As in Fig 14, Data Member Name
must be set identically to the Rockwell software (as Data in Fig. 13), then click [Save] (Fig.
15).
1126
1127
Step 3. Import CSV file, Tag Information can be viewed from object address.
Device Address:
Bit/Word
Device type
Format
Range
Input_Bit
DDDDDdd 0 ~ 6553515
Output_Bit
DDDDDdd 0 ~ 6553515
DW
Input
DDDDD
0 ~ 65535
DW
Output
DDDDD
0 ~ 65535
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Note: The wiring diagrams above are drawn based on MT8100i structure, the actual
placement of pins may vary according to HMI module.
1128
Driver Version:
Version
Date
Description
V1.00
Aug/24/2011
Driver released.
1129
YASKAWA Sigma-5
Supported Series: YASKAWA -V Series
Website: http://www.yaskawa.co.jp/
HMI Setting:
Parameters
Recommended
PLC type
YASKAWA Sigma-5
PLC I/F
RS232
Baud rate
19200
Data bits
Parity
Even
Stop bits
Options
Notes
RS232/RS485
0 ~ 127
Device Address:
Bit/Word
Device type
Format
Range
Note
0_bit
HHHh
0 ~ FFFF
E_bit
HHHh
0 ~ FFFF
Monitor Area
HHH
0 ~ FFF
HHH
0 ~ FFF
Monitor Area
*The following addresses are 32 bit parameters. Please use two words when reading or
writing.
Normal Parameters area
020AH / 020EH / 0210H / 0212H / 0282H / 051BH / 0520H / 0522H / 0524H / 0526H /
0531H
Monitor Area
E003H / E009H / E00EH / E010H / E012H / E016H / E01BH / E084H / E52AH /
E52CH / E52EH / E530H / E532H / E534H / E536H / E538H / E53AH / E53CH /
E601H / E603H / E605H / E705H / E707H / E110H / E120H / E130H
1130
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TD (Gray/Black)
3 TX
7 TX
4 RD (Purple/Black)
5 GND
5 GND
14 GND (Coffee)
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TD (Gray/Black)
3 TX
4 RD (Purple/Black)
5 GND
14 GND (Coffee)
2 RX
2 TD (Gray/Black)
3 TX
4 RD (Purple/Black)
5 GND
14 GND (Coffee)
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TD (Gray/Black)
3 TX
4 TX
7 TX
4 RD (Purple/Black)
5 GND
5 GND
5 GND
14 GND (Coffee)
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TD (Gray/Black)
6 TX
4 RD (Purple/Black)
5 GND
14 GND (Coffee)
1131
Driver Version:
Version
Date
Description
V1.00
Nov/21/2012
Driver released.
1132
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
RS232
Baud rate
19200
Data bits
Parity
None
Stop bits
Notes
9600, 19200
Device Address:
Bit/Word
Device type
Format
Range
AF
0~1
BN
0~1
Write only
BP
0~1
Write only
BV
0~1
Write only
CB
DDDD
0 ~ 9999
Write only
CM
0~1
Read only
DV
0~1
EB
0~1
OE
0~1
RS
0~1
Write only
ST
0~1
Write only
TB
Do
0 ~ 17
Read only
V_Bit
DDDdd
0 ~ 99931
*2
D_arr_Bit
DDDdd
0 ~ 99931
DW
AC
0~4
DW
DC
0~4
DW
BL
0~4
CD
0~2
CE
0~2
DW
DE
0~4
DW
DP
0~4
1133
Memo
Write only
Bit/Word
Device type
Format
Range
DT
0~2
EC
0~2
DW
EM
0~4
ER
0~2
FA
0~2
DW
FL
0~4
FV
0~2
DW
GR
0~4
DW
JG
0~4
DW
MM
0~4
MT
0~2
NA
0~2
OP
0~2
DW
PA
0~4
DW
PR
0~4
DW
SP
0~4
TC
0~2
TM
0~2
TW
0~2
DW
VA
0~4
DW
VD
0~4
DW
VS
0~4
DW
IL
0~4
DW
IT
0~4
DW
KD
0~4
DW
KI
0~4
DW
KP
0~4
DW
OF
0~4
DW
TL
0~4
DW
VR
0~4
DW
VT
0~4
DW
PF
0~4
DW
VF
0~4
DW
DDD
0 ~ 999
*2
DDD
0 ~ 999
*2
D_array
DDD
0 ~ 999
R_array
DDD
0 ~ 999
1134
Memo
Write only
Read only
*1
Note:
*1 PF is the communication parameter of SMC_3010, the default is 10.4, if the value is not 10.4, all values
will be displayed incorrectly.
*2 User defined integer variable V000~V999, floating point variable F000~F999.
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
short
D-Sub Female
9P D-Sub Male
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
1135
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
3 RXD
5 GND
5 GND
7 RTS
8 CTS
Driver Version:
Version
Date
V1.30
Mar/29/2010
Description
1136
short
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
23
Notes
Device Address:
Bit/Word Device type
Format
Range
AF
0~1
BN
0~1
Write only
BP
0~1
Write only
BV
0~1
Write only
CB
DDDD
0 ~ 9999
Write only
CM
0~1
Read only
DV
0~1
EB
0~1
OE
0~1
RS
0~1
Write only
ST
0~1
Write only
TB
Do
0 ~ 17
Read only
V_Bit
DDDdd
0 ~ 99931
*2
D_arr_Bit
DDDdd
0 ~ 99931
DW
AC
0~4
DW
DC
0~4
DW
BL
0~4
CD
0~2
CE
0~2
DW
DE
0~4
DW
DP
0~4
DT
0~2
EC
0~2
1137
Memo
Write only
Format
Range
DW
EM
0~4
ER
0~2
FA
0~2
DW
FL
0~4
FV
0~2
DW
GR
0~4
DW
JG
0~4
DW
MM
0~4
MT
0~2
NA
0~2
OP
0~2
DW
PA
0~4
DW
PR
0~4
DW
SP
0~4
TC
0~2
TM
0~2
TW
0~2
DW
VA
0~4
DW
VD
0~4
DW
VS
0~4
DW
IL
0~4
DW
IT
0~4
DW
KD
0~4
DW
KI
0~4
DW
KP
0~4
DW
OF
0~4
DW
TL
0~4
DW
VR
0~4
DW
VT
0~4
DW
PF
0~4
DW
VF
0~4
DW
DDD
0 ~ 999
*2
DDD
0 ~ 999
*2
D_array
DDD
0 ~ 999
R_array
DDD
0 ~ 999
1138
Memo
Write only
Read only
*1
Note:
*1 PF is the communication parameter of SMC_3010, the default is 10.4, if the value is not
10.4, all values will be displayed incorrectly.
*2 User defined integer variable V000~V999, floating point variable F000~F999.
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
V1.10
Mar/29/2010
Description
1139
YOKOGAWA FA-M3
Supported Series : FA-M3 CPU SP35-5N, SP55-5N CPU port, F3LC11 Computer Link
module.
Website : http://www.yokogawa.com/itc/itc-index-en.htm
HMI Setting:
Parameters
Recommended
Options
PLC type
YOKOGAWA FA-M3
PLC I/F
RS232
Baud rate
19200
9600 ~ 115200
Data bits
7, 8
Parity
Even
Stop bits
1, 2
1-32
Notes
PLC Setting:
Communication mode
1140
P.S Since Personal Computer link is used, when connecting to PLC it will delay about
20sec for testing communication.
1141
Device Address:
Bit/Word Device type Format
Range
DDDDD
0 ~ 71664
DDDDD
0 ~ 71664
DDDDD
1 ~ 65535
DDDD
1 ~ 9984
DDDDD
0 ~ 78192
DDDDD
1 ~ 65535
DDDDDD
1 ~ 262144
DDD
1 ~ 256
DDDDD
1 ~ 78192
DDDD
1 ~ 1024
DDDDDD
1 ~ 524288
1142
Memo
Wiring Diagram:
The following is the view from the soldering point of a cable.
9P D-Sub to 9P D-Sub: Cable KM11
eMT3000 series
COM1 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
2 TXD
3 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
D-Sub Female
2 RX
2 TXD
3 TX
3 RXD
5 GND
5 GND
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
2 TXD
3 TX
4 TX
7 TX
3 RXD
5 GND
5 GND
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
2 TXD
6 TX
3 RXD
5 GND
5 GND
1143
COM3 RS232 9P
D-Sub Female
2 RX
8 RX
3 TXD
3 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
7 RTS
8 CTS
short
cMT/mTV series
COM1 RS232 9P
D-Sub Female
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
2 RX
3 TXD
3 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
short
COM2 RS232 9P
D-Sub Female
COM3 RS232 9P
D-Sub Male
2 RX
6 RX
8 RX
3 TXD
3 TX
4 TX
7 TX
2 RXD
5 GND
5 GND
5 GND
5 GND
7 RTS
8 CTS
1144
short
MT6050i/MT8050i/MT8050iE
COM1 RS232 9P
D-Sub Female
9 RX
3 TXD
6 TX
2 RXD
5 GND
5 GND
7 RTS
8 CTS
Driver Version:
Version
Date
V1.20
Oct/23/2009
V1.30
May/31/2012
V1.50
Apr/07/2014
Description
Extended address L range up to 78192.
1. Extended I, D, B register range.
2. Added register: F.
1145
short
HMI Setting:
Parameters
Recommended
Options
PLC type
PLC I/F
Ethernet
Port no.
12289
Notes
PLC Setting:
Communication mode
Device Address:
Bit/Word Device type
Format
Range
DDDDD
0 ~ 71664
DDDDD
0 ~ 71664
DDDDD
1 ~ 65535
DDDD
1 ~ 9984
DDDDD
0 ~ 78192
DDDDD
1 ~ 65535
DDDDDD
1 ~ 262144
DD
1 ~ 256
DDDDD
1 ~ 78192
DDDD
1 ~ 1024
DDDDDD
1 ~ 524288
1146
Memo
Wiring Diagram:
HMI RJ45 Male
Wire Color
1 TX+
White/Orange
1 TX+
2 TX-
Orange
2 TX-
3 RX+
White/Green
3 RX+
4 BD4+
Blue
4 BD4+
5 BD4-
White/Blue
5 BD4-
6 RX-
Green
6 RX-
7 BD3+
White/Brown
7 BD3+
8 BD3-
Brown
8 BD3-
Driver Version:
Version
Date
Description
V1.00
Dec/30/2008
Driver released.
V1.10
May/31/2012
V1.30
Apr/01/2014
1147
YUDIAN AIBUS
Supported Series: UDIAN Automation AI-501, AI-518, AI-519, AI-701, AI-702M, AI-704M,
AI-706M, AI-719.
Website: http://www.yudian.us
HMI Setting:
Parameters
Recommended
PLC type
AIBUS
PLC I/F
RS485 2W
RS232
Baud rate
9600
9600, 19200
Data bits
Parity
None
Stop bits
On-line simulation
Options
Notes
0-100
YES
Device Address:
AI-518
Bit/Word Device type
Format
Range
Memo
00H
DD
01H
DD
-1999 ~ 9999
HIAL
02H
DD
-1999 ~ 9999
LoAL
03H
DD
0 ~ 9999
dHAL
04H
DD
0 ~ 9999
dLAL
05H
DD
0 ~ 2000
dF
06H
DD
0~4
CtrL
07H
DD
0 ~ 9999
M5
08H
DD
1 ~ 9999
09H
DD
0 ~ 2000
SV/STEP
1148
Format
Range
Memo
10
0AH
DD
0 ~ 125
CtI
11
0BH
DD
0 ~ 37
Sn (read only)
12
0CH
DD
0~3
13
0DH
DD
-1999 ~ 9999
dIL
14
0EH
DD
-1999 ~ 9999
dIH
15
0FH
DD
0 ~ 9999
ALP
16
10H
DD
-1999 ~ 4000
0.1
Sc
17
11H
DD
0 ~ 48
Op1
18
12H
DD
-110 ~ 110%
oPL
19
13H
DD
0 ~ 110%
oPH
20
14H
DD
0 ~ 127
CF (read only)
Baud ratebAud
/808Pstatus word:
run: 0 suspend: 4 stop: 12
(read only)
21
15H
DD
0 ~ 19.2K
22
16H
DD
0 ~ 100
ADDR
23
17H
DD
0 ~ 20
dL
24
18H
DD
0 ~ 127
Run
25
19H
DD
0 ~ 9999
Loc
Format
Range
Memo
01H
DD
-9990 ~ 30000
HIAL
02H
DD
-9990 ~ 30000
LoAL
03H
DD
-9990 ~ 30000
HdAL
04H
DD
-9990 ~ 30000
LdAL
05H
DD
0 ~ 2000
AHYS
11
0BH
DD
0 ~ 37
12
0CH
DD
0~3
dPt
13
0DH
DD
-9999 ~ 30000
SCL
14
0EH
DD
-9999 ~ 30000
SCH
15
0FH
DD
0 ~ 4444
AOP
16
10H
DD
-1999 ~ 4000
0.1
Scb
17
11H
DD
0 ~ 48
Opt
AI-701
1149
Format
Range
Memo
Baud ratebAud
/808P status word
run: 0 suspend: 4 stop: 12
(read only)
21
15H
DD
0 ~ 19.2K
22
16H
DD
0 ~ 80
ADDR
23
17H
DD
0 ~ 40
FILt
25
19H
DD
0 ~ 255
Loc
Wiring Diagram:
The following is the view from the soldering point of a cable.
eMT3000 series
COM1 RS485 2W
COM3 RS485 2W
RS485 2W terminal
9P D-Sub Male
9P D-Sub Male
1 RX-
6 Data-
4 COMM A
2 RX+
9 Data+
3 COMM B
5 GND
5 GND
cMT/mTV series
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W terminal
7 RX-
4 Data-
4 COMM A
6 RX+
1 Data+
3 COMM B
5 GND
5 GND
MTx070iE/MT8100iE/MT8121iE/MT8150iE/MT8121XE/MT8150XE
COM1 RS485 2W
COM3 RS485 2W
RS485 2W terminal
9P D-Sub Male
9P D-Sub Male
1 RX-
7 Data-
4 COMM A
2 RX+
8 Data+
3 COMM B
5 GND
9 GND
MTx071iE/MTx072iE/MT8101iE/MT8090XE/MT8091XE
COM2 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W terminal
1 RX-
6 Data-
4 COMM A
2 RX+
9 Data+
3 COMM B
5 GND
5 GND
1150
COM3 RS485 2W
9P D-Sub Male
RS485 2W terminal
1 RX-
6 Data-
4 COMM A
2 RX+
9 Data+
3 COMM B
5 GND
5 GND
MT6050i/MT8050i/MT8050iE
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W terminal
1 RX-
7 Data-
4 COMM A
2 RX+
8 Data+
3 COMM B
5 GND
5 GND
Driver Version:
Version
Date
V1.20
Dec/30/2008
Description
1151
C O M C P U P W R
Bottom View
Front View
MT6050i/MT8050i/MT8050iE
Pin assignment of the 9 Pin, Male,
Pin assignment of the 9 Pin, Male, SUB-D, COM1 [RS-232]/ [RS-485], COM3 [RS-485] Port. Only
Com1[RS485 2W] support MPI 187.5K.
Pin#
Symbol
Com1[RS485]
4 wire
Rx-
Rx-
Data-
Rx+
Rx+
Data+
Tx-
Tx-
---
Com3[RS485]
2 wire
R e s e t
D I P S W
Com1[RS232]
Cutout dimensions:
MT-6050i:
119mm [4.685"] W x 93mm [3.661"] H
C O M
Tx+
Tx+
GND
GND
TxD
Transmit
Data-
Data-
Data+
Data+
RxD
Rear View
Receive
1152
Wiring Diagram:
MT6050i COM1 [RS-232]
PLC RS-232
9P D-SUB Female
RXD
TXD
TXD
RXD
GND
GND
PLC RS-485 2w
9P D-SUB Female
Data-
Data-
Data+
Data+
PLC RS-485 2w
9P D-SUB Female
Data-
Data-
Data+
Data+
PLC RS-485 2w
9P D-SUB Female
RX-
TX-
RX
TX+
TX-
RX-
TX+
RX+
1153