Booklet On Domestic Wiring
Booklet On Domestic Wiring
Booklet On Domestic Wiring
SRI LANKA
DOMESTIC WIRING
MAY 2009
DOMESTIC WIRING
MAY 2009
Sponsored by:
LANKA ELECTRICITY COMPANY (PRIVATE) LIMITED
411,Galle Road
Colombo 3.
Foreword
Eng. D P Mallawaratchie
President of IESL – Session 2008/2009
CONTENTS
Scope 11
Introduction 12
Different types of final circuits 25
Sequence of supply controls 26
Declared or nominal voltage 27
Accessory 27
Diversity 27
The consumer unit 27
Safety precautions 27
Types of switches 29
Wiring systems – additional protection for cables 30
Looping in system 30
Identification (Colour code) 31
Single line diagram 31
IEE Regulations 33
Fundamental Principles 35
Protection for safety 35
Protection against electric shock 35
Protection against thermal effects 35
Voltage rating 42
Current rating 42
Voltage drop 42
Cross-sectional area of conductors 42
Protection against mechanical damage 42
Identification of conductors 43
Terminations 43
Installation of equipment 43
Lamp holders 43
Lighting points 44
Ceiling roses 44
Lighting fittings 44
Plugs and socket-outlets 44
Switching for safety 46
Cooker circuits in household premises 56
Correction factors for current carrying capacity 56
Selection of a System 59
Conductors 59
Insulation 59
Wiring systems 60
Overcurrent Protection 60
Means of isolation 61
Earth fault protection 62
Distribution boards 62
Layout 62
Type of final circuits 65
Selection of cables 65
Voltage drop calculation 67
Lighting circuits 68
Socket outlet circuits 68
Conduit capacities 69
Testing 95
Tests to be carried out 95
Continuity of earth conductors 97
Continuity of ring final circuits 98
Insulation resistance 100
Earth electrode resistance 102
Operation of residual current devices 103
List of Diagrams
Fig.1 Components of a cable 13
Fig.2 Stranding of conductors 14
Fig.3 Series and parallel circuits 15
Fig.4 Basic domestic circuit 15
Fig.5 A.C. Voltage Wave 16
Fig.6 Electrical faults 17
Fig.7 Direct and indirect contacts 18
Fig.8 Multi pole switches 19
Fig.9 Earth conductor 21
Fig.10 Resistance area 22
Fig.11 Voltage operated earth leakage circuit breaker 23
Fig.12 Residual current circuit breaker 23
Fig.13 Ring and radial circuits 25
Fig.14 Sequence of supply controls 26
Fig.15 Polarity: position of fuses (mcbs) and switches 28
Fig.16 Polarity: connections to screw type lamp holders 28
Fig.17 Polarity: connections to socket outlets 29
Fig.18 Circuits with two-way and intermediate switches 29
Fig.19 Looping in wiring system 30
Fig.20 Single line diagram 31
Fig.21 House – Electrical points 73, 74
Fig.22 Upper floor distribution board 79
Fig.23 Ground floor distribution board 80
Fig.24 House – Electrical layout 81, 82
Fig.25 Conduit junction boxes 83
Fig.26 Sunk box 83
Fig.27 Conduit connections to lamps and a switch 84
Fig.28 Termination for a switch on wall 84
Fig.29 Conduit connection to socket outlets at skirting level 85
Fig.30 Conduit entries to surface mounted distribution boards 86
Fig.31 Method of connecting cable to draw wire 87
Fig.32 Cables entangling in a junction box 87
Fig.33 Wiring points in a house 88
Fig.34 Single line diagram 89
Fig.35 Wiring layout 89
Fig.36 Conduit layout 90
Fig.37 Example wiring using looping in method 91
Fig.38 Connections to switches and ceiling roses 93
Fig.39 Typical layout for 13A socket outlets 94
Fig.40 Continuity test for earth conductor (Method 1) 97
Fig.41 Continuity test for earth conductor (Method 2) 97
Fig.42 Continuity test for ring final circuits (Method 1) 98
Fig.43 Continuity test for ring final circuits (Method 2) 99
Fig.44 Insulation resistance between phase and neutral conductors 101
Fig.45 Measurement of earth electrode resistance 102
Fig.46 Testing RCCB with a lamp 104
Fig.47 Addition and alteration to an existing installation 109
Fig.48 Addition of a socket-outlet using new cables 110
List of Tables
10
Scope:
This Guide is meant for electricians and covers only domestic installations
not exceeding 100 A per phase
11
Introduction
The two main hazards involved with electricity are electric shock
and fire. Both of these could be reduced to negligible proportions by using
suitable materials and correct methods of installation. Because of the vital
need to maintain high standards in carrying out installation work various lists
of regulations, requirements and codes of practices are published, some are
enforceable by law while others are mere recommendations but accepted as
standards to which every installation should be constructed.
12
Basics of Electrical Wiring
Control of supply
In electrical engineering, control generally means the ability to
isolate, connect, disconnect, direct or restrain the flow of electricity.
Protection
Protection in electrical engineering means the protection of cables
and equipment, usually against damage due to overcurrent or earth faults.
Conductor
Any material which allows free passage of electric current is known
as a conductor. Conducting materials vary in the degree to which they can
conduct electricity. Good conductors are required for electric circuits so that
they convey electricity with a minimum loss of voltage.
Insulator
Any material which does not allow free flow of electric current is
known as an insulator. Insulators are used to confine electric current to the
conductors in which they are intended to flow and to prevent leakage of
electricity to adjacent conducting materials which are not intended to become
“live”. Insulators are also needed to prevent unintended interconnections
between various parts of an installation.
Cables:
Major part of the domestic wiring installation involves cables. Cables
consist essentially of conductors to carry electric current and insulation to
prevent leakage of current from conductors. They are usually provided with
some form of protection against mechanical damage.
Conductor
Insulation (Solid or stranded)
Sheath for
mechanical protection
13
Stranding of conductors:
To give flexibility conductors of cables are stranded. The
number of strands in a cable is chosen to have a near circular shape when
all strands are combined. This is done by having layers of 1, 6, 12, 18, …
resulting 1, 1+6, 1+6+12, 1+6+12+18, … stranded conductors. This makes
number of strands making up a cable 1, 7, 19, 37, and so on. Conductors with
3 strands were included in imperial standards but not in metric standards.
Flexible cords
Conductors of flexible cables consist of large number of fine wires.
Smaller flexible cables in which the cross sectional area does not exceed
4 mm2 are known as flexible cords. Flexible cords used normally consist from
16 to 56 strands each from 0.2 to 0.3 mm diameter.
Electric circuits
An electric circuit is an arrangement of conductors for the purpose of
flow of electricity. Before an electric current can flow in a circuit two conditions
must be fulfilled. Everybody is aware that a height difference is required for
water to flow from one point to another. Similarly for electricity to flow from
one point to another an electrical potential difference is required between
the two points. The other condition is that there must be a complete path
of conducting materials through which the current can flow. This potential
difference is known as the voltage and the rate at which the electricity
flows is known as the current. There are two basic types of electric circuits.
Arrangement in which circuit components are connected in series so that the
same current flows through every one of the components is known as a series
circuit. Arrangement in which circuit components are connected in parallel
so that same voltage is applied to each component is known as a parallel
circuit. In a parallel circuit current supplied is shared by each component. In
domestic wiring parallel circuits are used.
14
Lamp 1
Current 1
Current 3 Lamp 3
Total Current
Lamp 1 Lamp 2 Lamp 3
Total Voltage
Total Voltage
Current
Neutral Conductor
Neutral
Transformer neutral
earth point
Flg.4: Basic Domestic Circuit
The basic circuit:
The basic a. c. circuit used in domestic wiring has two conductors
and the current consuming equipment. The equipment is generally known
as the load. The conductors are connected to the transformer at the supply
end. One of the conductors is connected to the earth at the transformer for
safety reasons. It is known as the neutral point as its voltage with respect
to earth is zero. The conductor between the neutral point and load is called
the Neutral Conductor while the other is called the Phase Conductor. (Earlier
the phase conductor was also known as the Live Conductor, but the current
IEE Regulations considers both Phase and Neutral conductors as Live
Conductors).
15
Waveform:
The voltage between the phase conductor and the neutral rapidly
alternates between two values Vm and -Vm. (Vm is known as the Peak Voltage).
Time taken to travel from a particular value to the two extremities and returning
to the original value is known as a cycle. Number of such cycles per second
is called the frequency of the supply. Voltage, current and resistance are
measured in volt, ampere and ohm respectively and frequency is measured
in hertz or cycles per second.
1 Cycle
VOLTAGE
TIME
fault
Earthed
metal
parts
fault
Earth faults:
Earth is a very good conductor offering practically no resistance to
flow of current. Since the neutral point is already earthed, if a phase conductor
accidentally makes contact with earth, the current will flow through the earth
to the neutral point bypassing the load. Metal parts in contact with earth will
also help to carry these currents. The value of current varies depending on the
resistances of the contacts. Therefore if a current carrying conductor makes
contact with such metals fault currents could result. Such fault currents are
called earth fault currents. When contact between the metal part and earth is
not perfect (where the resistance between the two is more than zero) metal
part could gain a voltage due to the earth fault current. If a person touches
such a metal part he could get an electric shock.
17
Direct and indirect contacts:
Electric shock is caused by touch. It can be divided into two main
groups. If a person touches a current carrying component direct, it is called
direct contact. An example would be a person removing a switch plate and
accidentally touching the phase conductor. If a person touches an exposed
metal which is not normally live, but has become so under fault conditions,
it is called indirect contact. An example would be contact with the metal
case of an electric iron having both a phase to earth fault and a significant
resistance to earth.
conductor
Phase
To lamp
Phase
Neutral
Earth
(High
Switch
Impedance)
Earth
Fault
Switching:
It must be evident now that there should be a complete path of
conducting materials from the phase point to the neutral point of the
transformer for a current to flow. Any discontinuity of the arrangement of
conductors would stop the flow of current. This fact is utilised to control
electric circuits. The simplest device used to achieve this function is called
a switch while switchgear is a broad term applied to equipment used for
controlling the flow of electricity.
18
Switches
The switch is used to manually open or close a circuit carrying a
normal current. It is capable of closing and opening a circuit under specified
overload conditions also. There are two types of switches employed in electric
wiring. One type opens only one conductor (known as single pole switches)
and the other opens all the conductors (2 pole, 3 pole and 4 pole switches).
A switch in which it is arranged to open all the conductors together is known
as a linked switch.
Phase 1
Phase 2
Phase Phase 3
Fuse:
This is a device inserted in a circuit to interrupt an overcurrent flowing
in it. It opens the circuit by melting the fuse-element by such overcurrent. A fuse
element is a conductor designed to melt when an overcurrent flows. Thus a
fuse can be used to automatically open the circuit when an overcurrent flows,
but it has to be replaced (after eliminating the fault) to restore the supply. If
it is necessary to open and close the circuit a switch is also required. Thus a
commonly used device to control circuits is a switchfuse which incorporates
a switch and a fuse (or fuses) together.
Circuit breaker:
This is a mechanical device for making and breaking a circuit, both
under normal conditions and abnormal conditions, such as those of a short
circuit. It can be used to open and close a circuit in normal use as well as
19
to automatically open a circuit in case of faults. There are many types of
circuit breakers such as oil circuit breakers (OCB), air circuit breakers (ACB),
moulded case circuit breakers (MCCB), miniature circuit breakers (MCB) etc.
in use.
Emergency disconnection:
The device to cut off the supply in case of an emergency could be
a switchfuse or a circuit breaker. Fuses or circuit breakers could be used to
automatically disconnect the supply in cases of overloads and short circuits.
The same devices could be used for earth faults as well when the earth fault
current is high, but some other device need to be employed to automatically
disconnect earth faults when the earth resistance is high.
20
Method adopted in domestic wiring to minimise shock risk is to
earth all accessible metal parts and arrange to cut off the supply when the
metalwork is liable to be dangerously live due to a fault. For this purpose a
separate conductor is run throughout the installation along with the phase
and the neutral conductor. One end of this is earthed and it is known as the
earthing conductor.
L
Phase (Line) Conductor
Phase R
Main L Protected
Supply Earthing O Metal
Transformer Terminal A Work
Earthing Conductor
D
Phase B Phase Y
Neutral Conductor
Transformer
neutral Circuit Protective Conductor
earth (cpc)
point
21
Soil
Fault Layers
Current
Ground
Earth
Electrode
Paths of
Fault
Current
Soil
Layers
(a) Sectional Elevation (b) Plan View
Fig. 10: Resistance Area
Earth loop impedance:
The earth electrode is only one part of the earth fault current loop
which determines the value of the current drawn. The fault current flows from
the transformer through the phase conductor to the fault and back to the
transformer neutral point through the earth conductor, earthing terminal,
earthing lead, earth electrode and soil path to neutral earth. The overall
resistance of this path will determine the magnitude of the fault current. Since
the voltage applied is alternating, it will depend not only on the resistance, but
also on the overall inductance and capacitance as well. The overall impedance
of the path that determines the magnitude of the earth fault current is called
the earth loop impedance.
Insulated
Earth
Lead
Consumer’s Auxiliary
Earth Earth
Electrode Electrode
(Note: It should be noted that the current IEE Regulations do not permit the
use of voltage operated e.l.c.b. s and therefore they shall not be incorporated
to new installations.)
Supply Multiplier
Search Test
Coil Button Protected
L Metal
Trip Test O
Coil Resistance Work
A
D
Distribution board:
This is an assembly of parts including one or more fuses (or other
protective devices) arranged for the distribution of electrical energy to
final circuits or other distribution boards. Every distribution board must be
connected to and controlled by the main switchgear controlling the supply or
a separate way on a larger distribution board.
Final circuit:
The portion of the circuit between the distribution board fuse and the
neutral terminal is known as the final circuit. Every final circuit is connected
either to one way of a distribution board or to a switchfuse. The sizes of
the circuit fuses in a distribution board depend upon the ratings of the final
circuits.
Fixed wiring
Electricity consuming equipment in a household can be broadly
divided into two categories. Items like lights, ceiling fans etc. which generally
need not be moved about are known as fixed equipment. Other items like
table lamps, table fans, immersion heaters, electric irons, refrigerators etc.
which are moved around are called movable equipment. (Out of these items
which are not heavy and frequently moved items are known as portable
equipment). Usually fixed equipment are directly connected to the wiring
system while movable equipment are wired up to a certain point and are
provided a means to connect and disconnect the movable portion at will.
24
Radial
Circuit
Ring
Circuit
Distribution
Board
Spur
Socket-outlet
The part of the facility to connect and disconnect the movable
equipment connected to the fixed wiring portion is known as a socket-
outlet. A socket-outlet is usually provided with protected contacts to make
connections for line, neutral and earth conductors. The part of the facility
connected to the movable equipment is known as a plug. It has protruded
pins to make connections with the line, neutral and earth contacts of the
socket-outlet. The plug is usually connected to the movable equipment by
a flexible cable or flexible cord. The movable equipment is usually required
to be used at different locations at different times. Therefore socket-outlets
need to be provided at all those different locations.
As there is a wide range of equipment drawing varying currents there
are socket-outlets of different capacities to choose from. The most common
socket-outlets found in domestic wiring in Sri Lanka are either 5A or 15A.
Also there are 13 A socket-outlets and fused plugs which can be used in
place of both 5A and 15A socket-outlets with suitable selection of the fuse in
the plug. In a ring circuit components of the circuit are arranged in a ring and
both ends of the ring are connected to a single point of supply. If the socket-
outlets are arranged in a chain with only one point connected to the supply
point, it is known as a radial circuit.
Electrical point:
Termination of the fixed wiring intended for the attachment of a
lighting fitting or of a device for connecting to the supply a current-using-
appliance is known as a point.
Sub
Distribution
Board
Sub-main Cables
to another
Sub-distribution board
Final
Circuits
Service
Fuse
Main Switchfuse
Meter or
DP MCB
Consumer’s
Supply Terminals ORIGIN OF THE
Authority’s INSTALLATION
Terminals
Consumer’s
Load Cables Earth
Electrode
Supply Authority’s Equipment Consumer’s Terminals
26
Declared or nominal voltage:
As in the case of any conductor there will be a drop of voltage along
the service line from the transformer to the supply authority’s terminals. As
the distance from the transformer varies from house to house, the voltage
available at the consumer’s terminal varies due to this voltage drop. In order
to overcome this problem service lines are designed to maintain the voltage
within a reasonable range rather than at a constant value. The voltage
expected at the origin of the installation is known as the Declared Voltage
(or Nominal Voltage). The declared voltage in Sri Lanka is 230 V Single phase
and 400 V three phase. The voltage between any two phases is 400 V and
between any of the phases and the neutral is 230 V.
Accessory:
Any device other than a lighting fitting, associated with the wiring of
the installation, e.g. a switch, a fuse, a plug, a socket-outlet, a lamp holder or
a ceiling rose is known as an accessory.
Diversity:
In normal use it is very unlikely to switch on all the lamps and other
current consuming appliances (such as electric oven, hot plate, kettle, water
heater, iron, toaster, water pump, etc.) at the same time. Therefore it is not
necessary to provide cables and switchgear large enough to supply the
maximum possible load. Thus, it is possible to reduce the size of cables and
switchgear to cater to the maximum likely load. This is known as allowing for
diversity.
Safety precautions
If a fuse or a circuit breaker is fitted on the neutral side of a distribution
board it will interrupt the supply in case of an overload, but it will not be
effective for other faults. Even when the circuit is disconnected at the neutral
fuse, the wiring and fittings will be live and there is a danger of receiving a
27
shock by anyone attempting to repair an electrical item. Therefore fuses or
single pole circuit breakers are never connected on the neutral side. However
there was a practice long ago to have fuses on the neutral side for additional
safety. But it has been discontinued now because sometimes the neutral
fuse blows without affecting the fuse on the live side creating the dangerous
condition described above.
A switch connected in any position in a lamp circuit can be used to
switch on and off the lamp. But if the switch is on the neutral side from the
lamp, the wiring and the fitting will remain “live” even when the switch is off
although the lamp will also be off. Therefore there would be a considerable
risk of electric shock if any one attempts to replace the lamp with only the
switch off. On the other hand, if the switch is on the live side of the lamp the
circuit will be dead when the switch is in off position and it will be possible
to replace the lamp or do other work on the circuit without electric shock.
Therefore switches are always connected on the live side (phase conductor)
in the interest of safety.
Phase to
centre contact
Neutral to
Screw
28
Fig. 17: Polarity: Connections to socket outlets
Type of switches
Lighting circuits are generally controlled by ( i ) One way switches,
( ii ) Two way switches and ( iii) Intermediate switches. One way switch is the
most commonly used item. This has a single contact point which makes (on)
and breaks (off) depending on the position of the toggle. Two way switches
have three contact points with one point making or braking contact with other
points depending on the position of the toggle. These are used to control
lamps from two different positions such as from either floor of a two-storied
building (Usually located at the entrance to the staircase). Intermediate
switches have four contact points which changes contact position from two
parallel lines to a cross (see figure) as the toggle is operated. They are used
to control lamps from three or more points in association with two, two way
switches.
Lamp
Intermediate
switch
Two
way
SWITCHING switch
POSITIONS Lamp
29
Wiring systems – additional protection for cables
There are many types of wiring systems that can be used to provide
safe, efficient and economical installations. The principal types in use are:
Screwed metal (Steel, Copper or Aluminium) conduit, Plain unscrewed metal
conduit, Non-metallic (PVC,PE) conduit, Armoured cable, Mineral insulated
copper sheathed cable, Cable duct, Bus-bar and Wood casing systems.
Looping in system
An opening in cable insulation always makes a weak point and
reduces the insulation resistance. It is also necessary to minimise the number
of joints in an electrical installation since in addition to the aforementioned,
the effective current carrying capacity of the cable reduces at the joint. In
practise this is achieved by avoiding midway joints and making them only at
switches, socket-outlets, ceiling roses, lamp holders and similar accessories.
This will require more length of cables than if midway joints are allowed, but
extra cost is justifiable in the long run. This is called the looping in system.
The term, looping in, gives the erroneous impression that one length of cable
is bared at intervals and looped in at switch and lamp terminals. It is not
practicable. In practice, when wiring in conduit, necessary numbers of cables
are drawn through the conduits and the joints are made at the switches,
lamps or other terminals. (Note: In ring circuits it is necessary to keep the
loops avoiding joints as much as possible, in order not to reduce the current
carrying capacity of the cables.)
To Upper
Floor
Circuit
Distribution
Board
30
Identification (Colour code).
There are three kinds of conductors involved in electrical installations
described earlier. They are the phase (line), the neutral and the earth
conductors. When there are a large number of cables involved, it is useful,
if these can be readily identified. This is achieved in practice by having a
different colour for each type of conductor. The colours used at present are
Red (Phase or Line), Black (Neutral) and Green or Green-and-Yellow (Earth).
In the case of flexible cables Brown (Phase), Blue (Neutral) and Green-and-
Yellow (Earth) is adopted. (The latest amendments to IEE Regulations have
changed the colour coding as Brown (phase), Blue (neutral) and Green-and-
Yellow (Earth) for rigid cables as well, effective from 1st April 2006.)
2x6
30 A DP
MCB
40 A DP
30 mA
RCCB
2x1
Lamps
2 x 2.5 Ring
Socket Outlets
31
STANDARD SYMBOLS
Symbol Description
Switch (General)
Triple Pole Switch
Circuit Breaker
Single Pole MCB
Fuse
Link ( Neutral)
On Push Button
Off Push Button
Filament Lamp
Distribution Board
Residual Current Device
Electricity Meter
Pendent or Ceiling Lamp
Wall Bracket
Single Fluorescent Lamp
Twin Fluorescent Lamp
Ceiling Fan
13A Socket Outlet
5A Socket Outlet
15A Socket Outlet
One way Switch
Two way Switch
Electric Bell
Bell Push
Earth Connection
32
I.E.E. Regulations
Note: The IEE Regulations have been revised and 17th Edition has
been issued after this monograph was drafted but before it was printed. The
current edition is referred to as BS7671 (2008), Requirements for Electrical
Installations IEE wiring Regulations. 17th Edition.
34
Summary of Regulations Relevant to Domestic Wiring
Fundamental Principles
35
Good workmanship and proper materials shall be used.
Connection All fuses and single pole control devices such as switches,
of switches circuit-breakers, thermostats etc. shall be connected in the
phase conductor only.
36
Control, Distribution and Overcurrent Protection
37
Where an installation is supplied from two sources and one
of them requires independent earthing and it is necessary to
ensure that only one means of earthing is applied at anytime,
a switch may be inserted between the neutral point and the
earthing, provided that the switch is a linked switch
arranged to disconnect and connect the earthing conductor
for the appropriate source at the same time as the live
conductors.
38
conductor, or in environmental conditions. This requirement
does not apply for a conductor of length not exceeding 3m,
when the overload protective device is placed along the run
of the conductor, provided there is no branch circuit or a
current using outlet between the point where the current
carrying capacity of the conductor is reduced and the
position of the protective device.
39
One or more of the following types of protective devices
shall be used:
i. residual current device
ii. an overcurrent protective device
(Residual current device is preferred)
40
Cross sectional area Cross sectional area of
of phase conductor circuit protective conductor
(S) (Sp)
mm2 mm2
S ≤ 16 S
16 < S < 35 16
S ≥ 35 S/2
41
Final circuits Where an installation has more than one final circuit, each
final circuit shall be connected to a separate way of the
distribution board. The wiring of each final circuit shall be
electrically separate from that of every other final circuit.
Voltage rating The voltage rating of every cable shall be not less than the
declared or nominal voltage of the circuit.
Current rating The current rating of every cable shall be suitable for the
design current and the current which will likely to flow
through it in abnormal conditions, for such periods of time
as are determined by the characteristics of the protective
devices concerned.
Voltage drop The size of every conductor shall be such that the drop
in voltage from the consumer’s terminal to any point in
the installation does not exceed 4 % of the declared or
nominal voltage when the conductors are carrying the full
load current.
42
Identification Every single core cable and every core of a twin or multi core
of conductors cable shall be identifiable at its terminations and preferably
throughout its length as prescribed in Table 1.
TABLE 1. Identification of conductors
The latest amendments to the Regulations have changed the colour coding
as indicated in Table 1A. It will be mandatory to follow this new colour code
for installations commencing on site after 31st March 2006.
Installation of Equipment
43
TABLE 2. Overcurrent protection of lampholders
Lighting At each of the fixed lighting point one of the following shall
points be used:
i. a ceiling rose
ii. a luminaire supporting coupler
iii. a batten lampholder
iv. a luminaire designed to be connected directly to the
circuit wiring
Plugs and Every plug and socket-outlet shall confirm with the
socket-outlets applicable British Standard listed in Table 3.
44
TABLE 3. Plugs and socket-outlets
46
Excerpts from Previous Editions
th th
The Regulations listed below were in the 14 /15 Editions but cannot be
th
directly referred to a clause in the 16 Edition. But these can be considered
still applicable to domestic wiring in Sri Lanka, when the Regulations in the
16th Edition are studied in detail.
47
Exemptions:
i. circuits in which omission of overcurrent protection
is required to prevent damage: e.g. the shunt trip
circuit of a circuit-breaker
ii. auxiliary circuits of equipment contained entirely
within the equipment
iii. radial or ring circuits and spurs installed in accordance
with the Regulations
iv. 0.5 mm2 flexible cord protected by a 5A fuse or
circuit-breaker in a distribution board
v. 0.75 mm2 or 1.0 mm2 flexible cord protected by a
13A fuse in a 13A fused plug or a fused spur-box
2
vi. 1.0 mm flexible cord protected by a 20A circuit-
breaker in a distribution board
Final circuits The circuits shall not supply more than one point, with the
of rating following exceptions:
exceeding 15A
Final circuits of ratings in the range of 15 to 30A may
be used to supply a number of 13A socket-outlets with
fused plugs
48
socket-outlet or joint box and shall remain unbroken
throughout its length or, alternatively, if the conductor is
cut its electrical continuity shall be ensured by appropriate
joints complying with the regulations.
49
All burrs shall be removed from the ends of lengths of
conduits and outlets must be bushed to guard against the
possibility of abrasion of the cables.
Metal conduit In metal conduit systems all phase conductors, the neutral
systems conductor and the circuit protective (earth) conductor of
each circuit must be drawn into the same conduit.
50
Suspensions Where a non-metallic outlet box of thermo plastic material
from non- (e.g. PVC) is used for suspension of a lighting fitting, care
metallic shall be taken to ensure that the temperature of the box
boxes: 0
does not exceed 60 C. The mass suspended from the box
shall not exceed 3 kg.
51
Room The latest amendments to the 16th Edition of the
containing a Regulations have changed the requirements apply to
bath rooms containing baths, showers and cabinets containing
shower and/or bath. The areas are divided into four zones
basically containing the bath or shower basin, immediate
vicinity and two outer areas, allowing some submersible,
jet-proof and waterproof equipment and accessories to
be installed in these areas. However, for domestic wiring
utilising normal accessories the previous requirements
stated below could be considered valid:
52
From the “On-site Guide”
Note:
* For ring and radial final circuits with many 13A socket-outlets current
demand to be assumed is the rating of the fuse or m. c. b. of that
particular circuit.
2. Cooking appliances 10 amperes + 30% 100% full load of 100% full load of
of full load of cooking largest appliance largest appliance
appliances in excess + 80% f. l. of 2nd + 80% f. l. of 2nd
of 10 amperes + largest appliance + largest appliance +
5A if socket-outlet 60% f. l. of remaining 60% f. l. of remaining
incorporated in unit appliances appliances
7. Socket-outlets other 100% current demand 100% current demand 100% current demand
of largest point + 75% of largest point + 75%
than those included in of largest point + 40%
6 above of the current demand of the current demand of the current demand
of every other point of every other point of every point in main
rooms (dining rooms
etc.) + 40% of the
current demand of
every other point
(Source: Table 1B, Appendix 1, “On-Site Guide”)
54
Conventional circuit arrangements;
The floor area served by the circuit is determined by the known or estimated
load but does not exceed the value given in Table 7.
For household installations a single 30A ring circuit may serve a floor area up
to 100 mm2 but consideration should be given to the loading in kitchen which
may require a separate circuit
* The tabulated values of conductor size may be reduced for fused spurs.
(Source: Table 9A, Appendix 9, “On-Site Guide”)
Where two or more ring final circuits are installed the socket-outlets are
reasonably distributed among the circuits.
Circuit protection
The overcurrent protective device is of the type, and has the rating, given in
Table 7
55
Conductor size
A circuit of rating exceeding 15A but not exceeding 50A may supply
two or more cooking appliances where these are installed in one room. The
control switch should be placed within two metres of the appliance. Where
two stationary appliances are installed in one room, one switch may be used
to control both appliances provided that neither appliance is more than two
metres from the switch.
56
TABLE 8. Correction factors for groups of more than one circuit
Single layer
clipped to a non- 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
metallic surface
(Spaced)
(Source: Table 4B1, Appendix 4, 16th Edition of IEE Regulations)
57
58
Selection of a System
Conductors
Some of the materials used as conductors in electrical engineering
are silver, cooper, aluminium, brass, nichrome, manganin, tungsten and
carbon. Silver is the best known conductor of electricity, but it is too expensive
for general use. The contacts of some switches are plated with silver to
make better contact. Copper is the material widely used in electric wires and
cables. It has a low resistance, not very expensive, can be easily formed into
wires and can be soldered easily. Aluminium is also used in electric wires
and cables, but it is not suitable for smaller sizes. Brass is often used for
terminals and various electrical fittings and accessories. Brass is harder than
copper, can be easily machined, readily cast and easily soldered. Nichrome
and manganin are used in heaters and resisters. Tungsten is used in electric
lamp filaments and carbon is used in brushes.
Insulation
Rubber, PVC, XLPE, ceramic, bakelite and Perspex are some of
the insulating materials used in electrical engineering. Most widely used
cable insulation for many years was rubber (Natural rubber vulcanized to
give strength). Poly Vinyl Chloride (PVC), which has now practically replaced
rubber, is a plastic compound impervious to moisture and resistant to most
chemicals. It has the disadvantage that it softens at high temperatures and
it becomes brittle at very low temperatures. Though it can be produced in a
form which is suitable for higher temperatures, it cannot be used in very low
temperatures. Cross Linked Polyethylene (XLPE) is also now used as cable
insulation.
Some of the materials used as cable insulation can be modified
for use as protective sheathing. Toughened rubber was used as a sheath in
rubber insulated cables and PVC modified to make it mechanically stronger
is used for PVC cables. PVC has the advantages being resistant to oils and
most chemicals and being self extinguishing. PVC sheathing is often of a
softer composition than PVC insulation, which facilitates its stripping.
59
Wiring systems
Bare conductor, cleated wiring, wood casing, armoured cable,
mineral insulated copper sheathed cable (MICC), catenary supported wiring,
metal conduit, insulated conduit, cable duct, bus-bar trunking and under
floor concealed ducts are some of the wiring systems in use.
The most popular wiring system for permanent wiring is the conduit
system. The practice of threading the cables through the conduits and
conduit fittings and then connecting elbows and tees to the conduit was
customary in the early days of electrical wiring where the first cost was
the only consideration. After the completion of the building it was quite
impossible to withdraw or rewire any of the cables when faults developed,
as they frequently did. This method of wiring is contrary to the Regulations
which require that the conduit system to be complete, before the cables are
drawn in.
The screwed steel conduit system is popular for industrial
applications. Screwed steel conduits are made to standard sizes with
standard threads, standard conduit fittings, saddles and other accessories.
Advantages of screwed steel conduit system are that it affords good
mechanical protection, permits easy re-wiring when necessary, minimizes fire
risks, provides efficient earth continuity and presents a pleasing appearance
if properly installed. But in domestic wiring screwed steel conduits are hardly
used nowadays.
The advantages of PVC conduit system are that it is less costly, can
be installed much more quickly than steel conduits, non corrosive, impervious
to most chemicals, weather proof and will not support combustion. The
disadvantages are that it is not suitable to be exposed to temperatures below
o
15oC or above 65 C and will not withstand blows and strains as much as
steel conduits.
PVC conduits are available in sizes of 16mm(5/8”), 20mm(3/4”),
25mm(1”), and 32mm(1 1/4”) of nominal diameter. It is generally the insulated
conduits used in domestic wiring these days. In this system circuits are
wired with single core PVC insulted cables in PVC conduits for mechanical
protection. The Regulations allow using PVC cables without a sheath in
conduits. But this type of cables is not readily available in the market in
this country and is not normally used in domestic wiring. What is generally
used is PVC insulated PVC sheathed cables with copper conductor in PVC
conduits.
Overcurrent protection
The ordinary rewirable fuse is still used in many switchgear. Its
advantages are that it is cheap and costs practically nothing to replace
but there is nothing very much more that can be said in favour of them. It
is unreliable as it is subject to deterioration due to oxidation and scaling,
and this may result in reducing its current carrying capacity and which in
turn might cause overheating, and further deterioration and overheating
60
until serious damage is caused to the switchgear before the fusing element
reaches sufficient temperature to melt and open the circuit. Some of the other
disadvantages are that inability to clear heavy faults and the ease with which
the fuse may be replaced by an unskilled person using one of incorrect size.
Fuse elements which are made of the same material and having
the same thickness and length do not always blow off at the same value of
the current. One reason is that they can carry some overcurrent for some
time. Therefore they blow off at different times depending on the value of
the overcurrent. The other reason is ageing. The fuse element is heated up
to some extent when carrying current and cooled again when the flow is
stopped. This causes deterioration and ultimate blowing of the fusing element
at a lesser current, sometimes even below the rated value.
Modern circuit breakers of reputable makes are designed to handle
safely heavy short-circuit currents within their rated breaking capacities.
Circuit-breaker has several advantages over any type of fuse. The major two
are:
1. In an event of overload all poles are simultaneously opened.
2. The circuit can be closed again quickly.
A remarkable difference between a fuse and a circuit-breaker is
the time that it takes to operate in an overload. The circuit-breakers can be
designed to operate at a predetermined time for a given overcurrent. A fuse
will take more than four hours to operate when an overcurrent of 1.5 times the
rated current flows continuously. On the other hand a circuit-breaker would
trip in less than four hours in a similar situation. The time taken would vary
depending on the type of the circuit-breaker. This fact is taken into account
in the Regulations and it requires the current carrying capacity of a cable
protected by a semi-enclosed fuse to be reduced to a half of the capacity of
the same cable protected by a circuit-breaker of the same rating.
The miniature circuit breaker is more expensive in first cost but it
has much to commend it especially as it can be made to incorporate an earth
leakage trip. If they operate due to overload they can readily be reset. In
domestic wiring the main switch used nowadays is generally a MCB. MCCB
is also sometimes used in large houses.
Means isolation
The Regulations allow the consumer not to provide a main switch if
the supply authority agrees for the consumer to use their equipment to protect
the installation. But the consumer needs to provide a means to isolation at
a readily accessible position. Therefore it is allowed to use an isolator which
opens all the poles (i.e. double pole for single phase and four pole for three
phase supplies) in place of the main switch. But it must be noted that most
isolators may not effectively open the circuits in case of a heavy short circuit
and it is not advisable to use an isolator for the purpose.
61
Earth fault protection
In the early days, current operated e.l.c.b.s were much more
expensive and less sensitive than voltage operated e.l.c.b.s and the latter
were extensively used. With the development of electronic devices, sensitivity
of the residual current detection devices was greatly improved and the cost
has been appreciably reduced. Now there are devices combining both
overcurrent and earth fault protection in the same unit. The device generally
used for earth fault protection in domestic wiring nowadays is RCCB, but
voltage operated earth leakage circuit breakers are still in use in most of the
old installations. (Note: 15th edition of the Regulations refer to them as Fault
Voltage Operated Circuit Breakers, but 16th Edition makes no reference at all
implying that the use of voltage operated circuit breakers is now obsolete).
Distribution boards
There are many types of distribution boards available in the market
and it is wise to select one which provides plenty of wiring space and is of
sufficient size to accommodate the cables, which have to be connected to
them. Two main categories are those that are surface mounted and those
mounted flush with the surface. The selection in this regard lies basically with
the likings of the owner of the dwelling.
Distribution boards can be divided to three different categories
when based on the protective device used for final circuits: Those fitted with
(1) rewirable fuses, (2) HRC fuses and (3) miniature circuit-breakers (MCB).
HRC fuses are not likely to be present in domestic installations in Sri Lanka.
The trend now is to use distribution boards with MCBs in place of rewirable
fuses. However fuses are still used in some installations.
An interesting point about fusing and fuse protection is that circuit
fuses protect the circuit cables being overloaded and should also prevent
main fuses from operating in case of a local short circuit. There is however
no guarantee that circuit fuses will protect any current consuming device
from becoming overloaded, especially on circuits consisting of more than
one point.
Layout
After the positions of the electrical points, switches, DB etc. are
finalized it is possible to decide on the conduit layout which gives the shortest
cable paths. When choosing the route to be followed by the wiring in a
building the following factors must be taken into account as far as possible:
i. Cables should not be located in positions where they are subject to
the risk of mechanical damage or liable to deteriorate because of
vibrations, moisture, heat, corrosive environment etc.
ii. It is an advantage if the runs are easily accessible both for installation
and maintenance, at the same time wiring should be as unobtrusive
as possible.
62
iii. The routes chosen should run as directly as possible, so avoiding
the use of an excessive quantity of materials and keeping voltage
drops to a minimum.
The relative importance of these factors varies so much from one
installation to another and no hard and fast rule can be laid down.
The Regulations state that every cable and flexible cord shall have
a current rating either not less than that of the fuse element or not less than
two-thirds of the operating current of an instantaneous circuit breaker.
If a circuit designed to carry 15A wired with 2.5 mm2 cable it could be
protected by a fuse rated to carry 15A (fusing current of a 15A fuse element
would be around 29A). If a pendent consisting of a 0.5 mm2 flexible cord
is connected to this circuit and a 15A heater is connected to the pendent
by an adapter, the fuse would not operate, but the flexible cable would get
dangerously hot, as it is rated to carry only 3A. It is a well known fact that this
kind of heater should not be connected to a lamp holder, but it is very often
done and circuits must be protected to ‘prevent danger’ from such misuse,
by choosing a suitable fuse rating to protect the flexible cord.
The Regulations divide the final circuits to two broad categories:
those rated less than 15A and those rated equal or more than 15A. A circuit
feeding more than 15A is not permitted to be connected to any other point.
(Except in the case of 13A socket-outlets and cookers). Therefore a separate
circuit is required for each point drawing more than 15A.
If the lighting load in a house does not exceed 15A, all points may
be wired on one circuit. Then the circuit need to be wired with 1.5 mm2 cable
and protected by a 15A fuse, but it would also be necessary to use 1.5 mm2
flexible chord for all pendants.
This rather extreme example shows that although the Regulations
would permit such a circuit, it would prove very inconvenient to the user
and there would be no saving in materials or labour. Such single circuits are
generally discouraged in domestic installations.
In actual practice domestic lighting circuits are now generally rated
at 5A. This means that they are controlled by a 5 or 6A fuse or a MCB, wired
with 1.0 mm2 cable and 0.75 mm2 flexible cords together with ordinary B.C.
lamp holders. (For pendent lamps 0.5 mm2 flexible cords are allowed as an
exception).
If all lights in a house are wired on to a single circuit the whole
premises will be plunged into total darkness when the final circuit fuse or
MCB operates. Therefore it is always advisable to provide at least two lighting
circuits, however small the premises is.
If 5A socket-outlets are to be installed then only one may be installed
to a 5A circuit, two to a 10A circuit and three to a 15A circuit. The usual
practice is to provide two 5A socket-outlets protected by a 10A fuse or a
MCB in a circuit wired with 1 mm2 cable.
63
In the case of final circuits with rated capacity exceeding 15A, no
diversity factor can be applied as it serves only one point. But cable size may
have to be increased to prevent excessive voltage drop. The cables must be
rated to take the full current of the point or equipment which will be fed by the
point, whichever is greater.
There are socket-outlets and plugs of different ratings used for
various current ratings of equipment in use. This had been a nuisance for the
average householder in finding the correct type of accessory for each kind
of equipment. An opportunity arose to get rid of this problem in the United
Kingdom soon after the Second World War when most of the buildings had to
be reconstructed. The 13A socket-outlet with a fused plug was introduced for
the first time as a solution and to keep the cost of wiring as low as possible.
Having long lengths of flexible cable leads from socket-outlets to
portable equipment spreading all over the house is a nuisance and bound
to create accidents. In order to avoid this, one would like to have as many
socket-outlets as possible, close to positions where such equipment is in use.
For example, in a kitchen or a pantry, every worktop should be provided with
a number of outlets and in a living room it will be convenient and safe to have
different outlets for the TV set, the booster, the radio, the audio equipment,
the table lamp, the table fan and so on. These suggest a large number of
closely spaced outlets. If they are to be wired back separately, the cost of
cables would be prohibitive. Therefore many people are not willing to install
the necessary number of outlets. Since these outlets, if provided, are closely
spaced, most probably only a small portion of them would be in use at any
given time. Thus, the principle of diversity could be applied to this situation
to bring down the size of the feeding cable. Because the outlets are spread
over a large area, it is possible to form them into a ring by bringing the both
ends of the cables to the distribution board by introducing small lengths of
cables. This makes each outlet to have two parallel paths of supply, which
enables to reduce the size of the cable further. Thus a 30A fuse or a MCB
could easily feed a circuit with twenty outlets. This makes it necessary to
provide a fuse of appropriate rating at the outlet to protect the flexible lead
to the portable equipment and therefore a fuse is inserted inside the plug
top. By selection of the rating of this fuse suitably, both the flexible cable and
the equipment could be protected. This could be used for any equipment
drawing less than 13A by changing the fuse in the plug to an appropriate
rating. The main advantages are that any appliance can be with a load not
exceeding 3 kW could be connected with perfect safety to any socket and as
64
many as ten socket-outlets could be wired to a circuit. With this system cost
of providing three 13A socket-outlets in a room would not exceed the cost of
installing one 15A socket-outlet plus a three-way adapter.
The Regulations regarding circuits containing 13A socket-outlets
have been changed from 14th to 16th editions. Earlier there was a limit to the
number of outlets connected to a particular circuit, now it has been amended
to limit the area served instead of outlets connected. The Appendix relevant to
this stipulation has now been shifted from the Regulations proper to the “On
Site Guide” as per British Standards Institution requirements. (The relevant
particulars were given earlier).
Selection of cables
The current ratings of cables depend on their physical properties
as well as the installation conditions. In deciding the size of the cable for a
particular purpose, it is necessary to consider the voltage drop in addition
to the current rating. IEE Regulations include tables giving the values of
voltage drop per ampere per metre. It is indicated that the values have to
be modified to allow for ambient temperature, grouping of cables, installing
methods and the Regulations give correction factors which have to be used
to multiply the given value to arrive at the corrected value. It also requires
applying different ratings on the type of protective devices. If MCBs are used
to provide overcurrent protection, supplied tables can be applied direct and
when semi-enclosed fuses are used the values have to be multiplied by a
factor of 0.725. Table 9 gives the relevant particulars for most commonly
used cables for domestic wiring.
65
TABLE 9. Current ratings applicable when protected by circuit breakers
(Note: Tables published in the 16th Editions have a slightly different format.
Current ratings and volt drops are given in two separate sets of tables and
for cables above 16 mm2 voltage drop has been divided into resistive and
reactive components.)
Table 10 which was extracted from the data published in the 14th edition
of the Regulations can be applied direct when rewirable fuses are used for
protection of final circuits.
66
TABLE 10. Current Ratings applicable when protected by semi-enclosed
(rewirable) fuses
3 or 4 cables in conduits or 3 or 4 cables clipped direct to a
Nominal cross Number and trunking surface or cable tray
section Area diameter of
Current Rating Volt drop Current Rating Volt drop
mm2 wires mV per Amp
mV per Amp
No./mm A per Metre A per Metre
1 1/1.13 9 35 12 35
1.5 1/1.38 11 23 15 23
2.5 1/1.78,
7/0.67 16 14 20 14
4 7/0.85 22 8.8 27 8.8
6 7/1.04 28 5.9 34 5.9
10 7/1.35 39 3.9 46 3.5
16 7/1.70 53 2.2 61 2.2
25 7/2.14 71 1.4 80 1.4
35 19/1.53 88 1.0 98 1.0
(Source: IEE Regulations - 14th Edition)
67
of the run in the circuit in metres by the current in the circuit in amperes. This
gives a product in Metre Amperes. When 9.2V is divided by this product, the
maximum allowable voltage in volts per ampere per metre is found. As the
values in the table are given in millivolt the result should be multiplied by 1000
to select the cable. The smallest cable having the voltage drop per ampere
per metre value less than the figure arrived from the calculations should be
selected. (The normal practice would be to tentatively select the cable on the
basis of current carrying capacity and calculate the voltage drop at the rated
current. If the voltage drop is excessive a larger cable is selected using the
aforementioned calculation method.)
Example:
Find a suitable cable to carry a current of 20A in a circuit with a
length of 25 metres connected to 230V supply. The metre-ampere figure will
be 20*25 = 500. Therefore maximum allowable mV/A/m will be 9.2 * 1000 /
500 = 18.4. From the table for two wire single phase wiring in conduits the
smallest cable satisfying the requirement will be 2.5 mm2 (1/1.78 or 7/0.67)
having a voltage drop of 17 mV/A/m. The voltage drop when carrying rated
current will be 17*20*25 = 8.5V. (Before using this value it has to be checked
whether it can safely carry 20A under installation conditions. Example is to
show voltage drop calculation only.)
Lighting circuits
The major component of domestic wiring involves lamps which are
normally wired into 5A circuits using 1 mm2 cable. As per the Regulations,
each lamp holder needs to be allowed 100 W. Therefore maximum number
of lamp points that can be allowed to a 5A circuit will be 11 Nos. Allowing for
20% for future use, only 8 o 9 lamp points can be connected to a circuit.
Voltage drop of a 1 mm2 cable is 37 mV per ampere per metre. Thus
the maximum length that is permissible for a 5A circuit is about 50 metres.
This is applicable only to final circuits from the main switchboard. For final
circuits of sub distribution boards, voltage drop along the sub-man cable also
need to be taken into account.
Thus a lamp circuit in a house could consist of 8 lamp points and
wired up to a maximum length of 50 metres measured along the cable path.
Using this criterion the number of circuits to be wired and the position of the
distribution board can be decided.
A ceiling fan also consumes about 100 W and can be allocated to
circuits on the same basis.
Socket-outlet circuits
If 13A socket-outlets are to be wired, a ring circuit using 2.5 mm2
cable can be provided for each 100 square metres of area. However, it would
be better to provide the kitchen with a separate circuit.
68
5A socket-outlets can be wired with 1 mm2 cable protected by a 10A
fuse/mcb with one or two outlets in the circuit. Three 5A socket-outlets can
be wired with 1.5 mm2 cable protected by a 15A fuse/mcb. The maximum
length of the circuit will depend on the number of outlets as the Regulations
require us to assume a demand of 5A for each outlet.
15A socket-outlets can be wired using 1.5 mm2 cable up to 13
metres and using 2.5 mm2 cable up to 21 metres. Cable sizes need to be
increased for longer lengths to compensate for the voltage drop.
It is not intended to mix 5A and 15A socket-outlets with 13A socket-
outlets in the same premises. Using air conditioners with 13A socket-outlets
has been a problem, due to the fuse being blown sometimes due to the starting
current. To overcome this problem a 20A DP switch can be incorporated to
the ring circuit to feed air conditioners.
5 1.0 0.75* 5
10 1.0 1.0 5
13 1.5 1.5 5
15 2.5 1.5 5/15
20 2.5 2.5 13/15
30 2.5 (ring) - 13
30 4.0 (radial) - 13
* It is permissible to use 0.5 sq. mm. flexible cord for a pendent which is
connected to a circuit controlled by a 5A fuse / mcb as an exemption.
Conduit Capacities
The “On-Site Guide” include tables giving details to determine the
number of each size of cable that can be drawn into various sizes of conduits.
These tables have been prepared allowing 40% free space so that the cables
can be drawn into the conduits easily. But these are not directly applicable
since they are based on the dimensions of PVC insulated (only) cables, where
as cables used in Sri Lanka are PVC insulated and sheathed cables. However
these tables could be modified and used taking the overall diameter of the
cables into consideration.
69
The Tables in the Regulations provide different values for different
sizes of conduits and cables for different distances between the adjacent
draw-in boxes. They are further divided based on the nature of the run,
straight, with one ninety degree bend, with two ninety degree bends and so
on.
A table can be prepared for insulated and sheathed cables
interpolating the values given for the insulated cables using the overall
diameter as the base. Table 13 indicates the number of such cables of each
cross section area that can be drawn into the indicated sizes of conduits for
straight runs and incorporating three, ninety-degree bends between draw-in
boxes where the draw-in boxes are not more than three meter apart.
70
Planning the Installation
72
the positions of socket-outlets, the object should be to provide outlets at
convenient positions to feed all portable lamps, table fans, electric irons and
other appliances that are likely to be used. If 5A and 15A socket-outlets are to
be used it would be expensive to provide an outlet at each possible location,
but if 13A ring circuits are to be used it would be economical.
The size of each conduit run can be decided depending on the sizes
and the number of cables to be drawn in each length. Once the correct sizes
of the cables for the circuits are determined it will be necessary to decide the
size of conduits to be used to accommodate the cables.
73
GROUND FLOOR PLAN
74
Example
Let us now consider designing electrical installation for the two
storey house shown in Fig. 21. This is a true plan prepared by an architect
and the electrical points are designed according to his wishes and may be
representing a house existing in Colombo. This house has eighty two lamps
points, six ceiling fans, one electric bell, one cooker control unit, thirty six
13A socket-outlets, four 20A DP switches and four shaver outlets. The lamps
numbered 1-6, 15, 43-52, 55, 56, 59, 71, 76 and the bell push are exposed to
weather and they need to be weatherproof.
Power supply would be brought along the road and the meter point
has been chosen near a corner in the garage. The main switch could be
located on the wall in one of the positions marked as A, B, C or D. When
the lengths of final circuits are considered most economical position would
be somewhere on the wall A as it is closer to the centre of the building. But
it is very unlikely that the occupant would like to have the switchgear in his
living room. If the client has no objection you could locate the main switch
there. The next best position on economic consideration would be on the
wall along point B, but this is on the landing and may not be convenient in
accessing in case of an emergency as you need to climb several steps to
reach it. Besides this is in the lobby for the first floor entrance and there is a
possibility of the door being locked at times. Thus it could not be described
as a readily accessible position as required by the Regulations. The next best
is the location C. Presuming that the occupant has no objection in locating
the switchgear in his dining room, this position is selected for our design. If
the client objects you could choose the wall D. On the other hand, kitchen
being a place with heavy consumers it could be the load centre and the most
suitable place.
Let us now estimate the maximum demand. Assuming that the
house belongs to an affluent owner (results in a very high demand), the list of
equipment likely to be used in this house could be as follows:
1. Incandescent lamps 73 Nos.
2. 1 x 20w fluorescent lamps 7 Nos.
3. 1 x 40w fluorescent lamps 2 Nos.
4. Ceiling fans 6 Nos.
5. Electric bell 1 No.
6. 4 burner cooker with oven 1 No.
7. Refrigerator 1 No.
8. Deep freezer 1 No.
9. Electric kettle 1 No.
10. Blender/Grinder 1 No.
11. Mixer 1 No.
12. Toaster 1 No.
13. Washing Machine 1 No.
14. Television 5 Sets
15. Audio 1 Setup
16. Electric Iron 1 No.
17. Air conditioner 4 Nos.
18. Computer 4 Nos.
19. Electric shaver 4 Nos.
75
The maximum demand occurs when the most of the current
consuming equipment are in use at the same time. In Sri Lanka this normally
occurs during the period 6.00 to 9.00 p.m. and equipment likely to used at
that time need to be considered for computing maximum demand.
Lighting
Incandescent lamps 73 Nos. Regulation requires to assume a minimum of
100 W for each lamp holder (assuming 2 chandeliers have 3 holders each)
Total load = 7700 W
Fluorescent lamps 1 x 20 W 7 Nos. = 140 W x 1.8 (for control
gear)
1 x 40 W 2 Nos. = 80 W x 1.8
Total lighting = 8096 W
Allowance for diversity = 8096 x 66/100 W
= 8096 x 66 / 100 x 230 A
= 23.23 A
Ceiling fans 6 Nos.
Since air conditioners are available it is unlikely that ceiling fans in the bed
rooms will be used. Therefore only two fans need to be considered.
Maximum demand = 2 x 100 /230 A = 0.87 A)
Electric bell may be neglected.
4 Burner cooker with oven
Assume cooker has two 1500W and two 1000W burners and an oven with
1500W element and a socket-outlet at the control unit
Total load = 6500 W = 6500/230 A = 28.26 A
Allowance for diversity = 10 + (28.26-10) x 30/100 + 5A
= 20.48 A
Refrigerator (150 W) 1 No.
Load = 150 / 230 = 0.65 A
76
Washing Machine (1000 W) 1 No.
Load = 1000 / 230 = 4.35 A
It is obvious that the supply authority would not allow such a big
single phase supply and the house needs a three phase supply with capacity
of 36.54 A per phase. The supply authorities usually provide either a 30A or
a 60A three phase supply and a 60A three phase supply need to be obtained
for this house. Therefore a 60A TP MCB shall be provided as the main switch.
At this stage it is necessary to verify from the supply authority whether a
60A three phase supply could be obtained from the location and if it is not
possible the client should be advised to curtail his demand to reduce to 30A
three phase. Perhaps it may be necessary to delete some of the socket-outlets
proposed to avoid simultaneous use of some equipment (e.g. in the kitchen).
When the distribution is considered it can be seen that a fair amount
of points are in the upper floor and a three phase supply can be taken there.
The distribution board for the upper floor can be located in the lobby at
77
F since it is more or less at the centre. Repeating the calculation of the
maximum demand for the upper floor would result a need of 12A three phase
supply. However, there are 13A socket-outlets and size of the main switch
need to be considered only after deciding the final circuit arrangement. It
is necessary to divide the load among the phases as much as possible.
When you examine the layout you would notice that the three bedrooms are
similar and the equipment in each room could be assigned to final circuits
connected to the three different phases. All the lamp points in a bed room
could be allocated to a single circuit. The ceiling fan and the shaver-outlet
could also be assigned to the same final circuit. The total demand of these
circuits would be less than 6A. Thus they can be protected by 6A MCBs and
wired with 1 mm2 cable. The floor area of each bedroom is more than 20 m2
but is less than 50 m2. Therefore the socket-outlets in each room could be
assigned to a final circuit protected by a 30 or 32A MCB. It could be wired
as a radial circuit using 4 mm2 cable or a ring circuit using 2.5 mm2 cable.
The 20A DP switch provided for the air conditioner also can be connected
to this circuit. As the socket-outlets are at least on three walls of the room
wiring in a ring circuit with cables of lesser cross-section area would be more
economical and it would permit easy addition of future extensions. Therefore
they are assigned to a ring circuit protected with a 30A MCB and wired with
2.5 mm2. What remains is the lobby area and the lamps of the area could
be served by a separate final circuit protected by a 6A MCB and wired with
1 mm2 cable. The two socket-outlets could be connected to the ring circuit
of the adjacent room. Thus we would end up with seven final circuits divide
as 3, 2, 2 to the different phases. The Regulations require to provide a further
20% for the future additions and this could be satisfied by adding two more
final circuits making it possible to balance the number of circuits connected
to each phase. The three ring circuits provided cover the entire upper floor
and each circuit serves a floor area of less than 100 m2 and therefore there
is no need to provide spare circuits to connect 13A socket-outlets. Therefore
two 6A MCBs could be provided to protect the spare circuits.
Since there are socket-outlet circuits needing protection with
30A breakers, the main switch also need to be a 30A TP MCB. To provide
protection against earth fault currents a residual current device need to be
provided. This could be a 4 pole RCD connected after the main switch. But
as all the loads are single phase, it would be more prudent to provide three
double pole RCDs on the three phases so that only one phase is affected in
case a RCD trips due to an earth fault. An important thing to remember in this
type of arrangement is to separate the three neutral conductors connected
to each phase throughout the installation beyond the RCDs. Three separate
neutral bars shall be provided at the distribution board for this purpose. The
complete distribution board for the upper floor is shown in FIG. 22.
78
From DB - G
DB-U
30A TP MCB
A sub-main cable need to be drawn from the main switch at the ground floor
to the distribution board to supply electricty. The length would be around
15m and the maximum current would be about 15A (allowing for future
expansions as well). This gives a product of 225 metre amperes. The voltage
drop allowable is 4% of the nominal voltage from the main switch to the end
of the circuit. So in this case let us assume half of that is allowed to drop
along the sub-main cable leaving the other half for the final circuit. So the
voltage drop allowable is (230 x 2/100 =) 4.6V. Thus the maximum allowable
voltage drop would be 4.6/225 = 0.0204 V/A/m = 20.4 milli volts per ampere
per metre. This would allow us to use a cable with a cross-section area of
2.5 mm2. But since the main switch of the distribution board is 30A the sub-
main cable need to be capable of drawing that current. Therefore the cable
cross-section need to be at least 6 mm2. (It is presumed that the sub-main
cable is drawn in a separate conduit and no external influences requiring to
apply derating factors are present.) Since the sub-main cable is of more than
3 metres in length another 30A TP MCB need to be provided at the origin
of the installation (Distribution board at the ground floor). A separate earth
cable of the same cross-sectional area (6mm2) of green-and-yellow colour
also needs to be drawn along with these cables to connect the to earthing
terminals of the distribution board
Maximum demand for the ground floor distribution could also be
similarly computed to be around 25A. There are 48 lamp points and these
could be wired to six final circuits each having around eight lamps per circuit.
It should be noted that the Lamps No. 9 and 10 are chandeliers and they would
demand more current. Therefore the circuit containing them should have less
number of points. (each holder need to be allowed 100W). This would allow
them to be wired with 1 mm2 cable protected with 6A MCBs and easily be
balanced between the phases. Another important point to be considered
in dividing lighting points to final circuits is the location of their switches.
79
It is better if only one circuit is assigned to switches ganged at one place.
(There is no Regulation to prevent such use except to say that a warning
notice need to be provided if 400V could be present at adjacent switches.)
Assignment final circuits can be done as follows:
1. Lamps 1-6, 11, 12 and 15
2. Lamps 7-10, 13 and 14
3. Lamps 16-23 and two ceiling fans in the living room
4. Lamps 28-33, ceilng fan and the shaver-outlet in the bed room
5. Lamps 34-42
6. Lamps 24-27, 43-48
7. The cooker control unit
8. Socket-outlets (in the Kitchen)16-18
9. Socket-outlets 1-8
10. Socket-outlets 9-15 and the AC in the bedroom
Requirement for the additional circuits for future extensions could
be fulfilled by adding another two circuits.
The cooker control unit needs a 30A MCB for protection and should
be wired with 6 mm2 cable. Socket-outlets in the kitchen can be wired as
a radial circuit using 4 mm2 cable with 30A MCB protection and other two
socket-outlet circuits could be wired as ring circuits using 2.5 mm2 cable with
30A MCB protection. Additional circuits could be protected with 6A MCBs
allowing for lamp circuits, since the entire floor has been covered with13A
circuits as in the first floor. When distributing these final circuits among the
phases, it is better if the cooker control and the socket-outlets in the kitchen
are assigned to the same phase to avoid presence of 400V. At the same time
it is better if the lamps in the kitchen are assigned to a different phase so
that even if the RCD connected to the kitchen appliances trip due to a fault
there would be light in the kitchen. Thus the distribution could be as shown
in Fig.23.
To meter point
2
4x16 mm
DB-G
60A TP MCB
30A
TP RCCB 40A DP 30mA RCCB 40A DP 30mA RCCB 40A DP 30mA
MCB (6A) (6A) Lamps 34-42
(6A) Lamps 1-6, 11, 12,15 Lamps 28-33, 1CF, 1Sh
To DB U
(6A) Lamps 7-10,13,14 (6A) Lamps 24-27, 43-48, 1bell (6A)
Spare
(30A) (30A) (30A)
S/O 1-8 S/O 9-15, 1AC 1 Cooker
(6A) (6A) Spare (30A)
Lamp 16-23, 2 CF S/O 16-22
80
Since the main switch for the whole house is installed in this
distribution board, there is no need to provide another device to isolate the
ground floor installation. As explained in the first floor, earth fault protection is
preferably provided to individual phases. Considering the diversity of individual
phases a 40A DP RCD shall be provided for each phase. As socket-outlets
are fed from all RCDs their sensitivity should be 30mA. The arrangements of
these circuits are shown in the layouts in Fig. 24. The load cables from the
meter point should be able to carry 60A and 16 mm2 cables should be used
for the purpose. The earthing conductor should also be 16 mm2. The earth
electrode could be located at E in the garden behind the kitchen.
81
GROUND FLOOR PLAN
82
Installation
Conduits are mainly run concealed in walls and floors, above ceiling
spaces and sometimes on the surface. PVC casing and capping is now
available and they are used for surface applications. Surface wiring system is
fairly straight forward and is not described any further. However a good deal
of planning and skill is required to produce a first class installation with a neat
appearance.
PVC conduits can be easily formed into required shape by heating.
However it is important to avoid forming wrinkles as it would make the drawing
in of cables difficult. As the walls of the conduits are thin, usually sand is
rammed in and both ends are plugged before heating to retain the circular
shape. Area to be bent is uniformly heated up by carefully exposing to a mild
heat source and formed the required shape and then cooled with a wet cloth
or alike so that the shape is retained. However this is a tedious process and
some skill is required to avoid deforming or burning the conduits.
83
The conduits in the concealed wiring system is usually installed
during the building construction in walls and floors in such a manner that the
cables can be drawn in at any time after the completion of the building.
In installation of conduits it is required to decide the most suitable
runs for the conduits. The routes should be chosen so as to keep the conduits
as straight as possible. However it is a good practice to keep the concealed
conduits in walls only on horizontal and vertical direction in order to minimize
subsequent damage. It must be remembered that the Regulations do not
permit to draw cables through more than two right angle bends or their
equivalent. Therefore additional junction boxes may be required at places
other than where accessories or wiring points are present.
Floor
Wall
Sunk Box
84
The Regulations require that at the switch points the conduit is
terminated a box or similar enclosure. When run buried, taking the conduit
out to the surface through a bend or a set in the conduit is not appropriate.
On the other hand the sunk box shall not be buried too deep leaving a gap
between the box and the switch plate.
When conduits are run to switches or other positions on a wall, they
are usually run in chases cut into the wall. These chases, which will be filled
after the conduits are laid, must be deep enough to allow at least 10 mm
of plaster covering the conduit, to avoid plaster cracks appearing in a later
stage. Sunk boxes fitted to these conduits should be placed allowing for the
plaster cover. These will be applicable to conduits and sunk boxes on ceiling
soffit as well.
Floor
Floor above
Correct Method
85
Conduits for distribution boards
When surface mounted distribution boards are used with a buried
conduit system, the best method to take the cables from the conduits to
the DB is to fit an adaptable box in the wall to take the conduits into it. The
conduits can be taken out of the plaster and enter the DB direct with a set
on the conduits but this method is not recommended. Alternatively adapter
boxes can be mounted on top or bottom or both on the DB to take the cables.
Adapter box can be mounted partially buried so that the conduit can enter it
easily.
Wiring
Wiring is carried on each conduit run from draw-in box to draw-in
box in sequence usually starting from a mid-point in the conduit system so
as to reduce the length of cables which have to be drawn-in. A draw-wire has
to be inserted into the conduit run to draw in the cables. It is a good practice
to keep a draw-wire drawn inside the conduit whilst it being laid. However,
o
if the number of bends do not exceed the stipulated equivalent of two 90
bends and the length is not excessive, it is not difficult to insert the wire at a
later stage. If it is difficult, two wires from either end of conduit run, with small
hooks at the ends could be inserted. Once the two ends reach each other
wires could be twisted so that the two hooks get entangled and one wire
could be pulled out from one end until the draw-wire fed from the other end
comes out. Obviously two persons are required to do this operation.
86
Once the draw-wire is inserted and the conduit is cleaned if
necessary, the required number of cables should be tied to one end of the
draw-wire. The ends of the cables to be tied must be bared for a distance of
about 50 mm and threaded through a loop in the draw wire for this purpose.
When drawing in a number of cables, they must be carefully fed in from the
sending end whilst one pulls them at the receiving end.
Draw
wire
Cables
Fig. 31 - Method of connecting cables to draw wire
Before drawing in the cables into the conduits they must be run off
the reels. If the cables are allowed to spiral off the reels they would become
twisted and kinked inside the conduits.
The cables should be fed into the conduits in such a manner as to
prevent any cables crossing and also to avoid them being pulled against the
sides of the openings of the draw-in boxes. Always some slack has to be left
at the draw-in boxes and it has to be ensured that the cables are fed to the
conduit in such a way that no twisted cables will be left at the draw-in point.
This is particularly applicable when the cables have to be pulled out from one
conduit and fed to another connected to the same draw-in box.
87
This operation needs care and synchronization between the persons
who are feeding and pulling. Sometimes a third person may be required to
be stationed mid-way to relay messages if the persons at both ends are not
within earshot. If the cables are not drawn carefully in this manner, they are
almost certain to become crossed and might result in the cables becoming
jammed inside the conduit. Also the insulation of the cable is liable to get
damaged in the process.
30 A DP
MCB
40 A DP
RCCB 30 mA
(6A) 2x1
LIGHTS 1-9
2x1
(6A) LIGHTS 10-14
(30A) 2 x 4 Radial
SOCKET OUTLETS IN KITCHEN
(6A) SPARE
Conduit layout
A suitable method of wiring the lighting circuits and connected
conduit layout is shown in Fig. 35 and 36. Numbers of cables between
respective points are shown in by the number of lines in the Fig. 35 and the
number inside the parenthesis in Fig. 36. A three dimensional view of the
conduits for the lighting circuits are shown in Fig.37.
89
GROUND FLOOR UPPER FLOOR
Fig. 36 - Conduit Layout
Wiring procedure
The practical method of wiring a conduit installation such as this is
briefly as follows: A start is usually made from the three way box nearest to
the DB (D). There will be four red cables going from this box to the switch
(C) and one black cable going to the DB. Therefore one more draw-in box (E)
is required at the wall above the switch position to separate the two sets of
cables. So the distance along the conduit path from (D) to (C) is measured
and four red cables are reeled off equal to this length and some extra slack
to allow for the connection at the switch and tying to the draw-wire. Then the
distance along the conduit path (D-E-A) from (D) to the DB (A) is measured
and a black cable is reeled off to the corresponding length with some slack.
A draw-wire is inserted into the conduit length from three way box (D) to the
draw-in box (E) on the wall if not done already. The ends of the five (4 red and
1 black) cables are then bared and tied to the draw-wire. Then the chosen
lengths of cables are drawn into the conduit. The excess lengths are drawn
out of the draw-in box (E) on the wall so that all the cables are drawn in up
to the measured length ending at the three way box (D). Another red cable
is required to connect the switch (C) to the DB. This length is measured and
a red cable is cut to the length plus the required slack for connecting and
tying.
The draw-wire connection to previous bundle is untied and red and
black cables are separated. Then the end of the red cable going to the DB
is bared and tied to the draw-wire together with the end of the black cable.
These two cables are then drawn into the conduit connecting to the DB.
Then the other end of the red cable is bared and together with the ends of the
other four red cables are tied to the draw-wire and pulled through the conduit
going to the switch. Care should be taken to avoid kinks and entanglements
forming inside the draw-in box in this operation.
90
Fig. 37 - Example wiring using looping in method
91
Once the cables are drawn in to the conduit it will be difficult to
identify the individual ends at a later stage. Therefore it is customary to make
some marks at the ends of the cables before they are drawn into the conduits.
This is normally done by cutting off a small portion of the sheath (usually in
the shape of a diamond) exposing the coloured insulation. Identification is
done by the number of such marks on each cable end.
There will be five red cables drawn into the switch position (1, 2). One
is coming from the DB and is already cut to the required length. Other four
should be terminated at switch (3), lights (1), light (2) and switch (4, 5). The
lengths are measured along the conduit paths and cut with the required slack.
The black cable also goes to the light (1) and can be cut to length. Otherwise
it may be extended up to lights (2) or (3) if desired allowing additional loop
lengths to make connections at the lights. The chosen cable lengths should
be cut and the cables to the next conduit run (between three-way boxes at
(D) and (F)) can be drawn in now. There are three cables to be drawn into this
conduit which are already cut to length. (If the black cable was terminated at
light (1) two new black cables have to be drawn to connect neutral of light (1)
to neutrals of light (3) and light (4). Once three cable ends up to (F) are drawn,
wiring up to switch (3) and light (2) are done in a similar manner introducing a
new red cable length from switch (3) to light (3) and a black cable length from
light (2) and light (3). Now the two cables (The red cable between switches (1,
2) and (4, 5) going in the circuit run between lights (D) and (I) can be drawn in.
This process should be repeated until the whole circuit is wired.
There are five red cables drawn into the two ganged switch at
(C). The cable coming from the DB and the one going to switch (3) shall be
connected to one side of the switch (1). (One side of switch (2) also should
be connected to the same side using a red jumper, if not already connected
by the manufacturers.) Then the other two cables going to the two lights (1)
and (2) shall be connected to the other side of the respective switches. At the
position of the light (1) there will be three black cables (or one end and a loop)
and a red cable. The black cables should be bared and connected to one of
the ends of the ceiling rose and the red cable should be connected to the
other which will form the lighting point. All other connections also need to be
done in a similar manner when the cables are drawn into each position.
Note:
The Regulations require a circuit protective (earth) conductor to
be drawn to connect all switch plates and lighting points up to the ceiling
roses. But this is generally not practised in domestic wiring in Sri Lanka and
therefore not shown in this illustration.
92
To SWITCH (3) at H
To SWITCH (4) at L
From MCB 1 of DB
To LIGHT (2) at G
To LIGHT (1) at D
Black cables
from
Terminal 1 of
Neutral bar
Neutral to
LIGHT (1) To LIGHT (3) at F
To LIGHT (4) at I
93
In the case of 13A socket-outlets, most of them are installed at
skirting level while in kitchen and pantries they are installed at the table top
level. Therefore it will be more convenient to run the conduits along the walls
at the level of the socket-outlets. However they need to be taken up at the
door crossings. The conduiting can be as shown in Fig. 39.
It should be noted that all socket-outlets except those in the kitchen
are grouped into one circuit to reduce the cost. However, it would be more
convenient to the user if the upper floor socket-outlets are wired in a separate
circuit. Further it would be much better if the upper floor lighting and socket-
outlets are wired from a separate distribution board installed in the upper
floor itself on safety considerations. Increase in cost in this regard would be
only marginal.
94
Testing
Test procedure
To test the continuity with supply disconnected a continuity tester or
a lamp and a battery set or a bell and a battery set could be used.
96
Continuity of earth conductors
Method 1.
1. Temporarily connect the phase bus-bar to the earthing terminal at the
Distribution Board
2. Check the continuity between phase and earth terminals at each outlet in
the circuit Continuity Tester
Temporary Connection
Method 2.
1. connect two long leads to the continuity tester
2. connect one lead to the consumer’s main earthing terminal
3. check continuity of earth conductor at various points on the circuit such as
socket-outlets, switches, luminaries etc. with the other testing lead.
Continuity Tester
Consumer’s
Main
Earthing
Terminal
Fig. 41 - Continuity test for earth conductors: Method 2
97
Continuity of ring final circuits
This test is required to see that phase, neutral and earth conductors
of every ring final circuit are connected in complete rings. It should be noted
that even if the ring is open at one point, all the socket-outlets will have
supply, but trouble may develop later due to conductor overloading. For this
test a low reading ohmmeter is required and the socket-outlets connected to
the mid point of the circuit needs to be identified.
Method 1
1. Connect the meter leads to each end of the earth conductors of the ring
circuit to be tested at the distribution board and note down the reading
(Say A).
2. join the two ends of the earth conductor at the DB together and connect
to one lead of the meter.
3. connect the other lead to the mid point of the earth conductor of the ring
and note down the reading (Say B).
4. connect the testing leads together and note down the reading (Say C).
5. check whether A/4 ≈ B-C.
6. the continuity of the phase and neutral conductors shall be checked in a
similar manner.
Continuity
tester
Continuity
tester
(a) Measurement between ends of earth electrodes (b) Measurement between closed ends and mid-point
Continuity
tester
98
Method 2
1. Connect the meter leads to each end of the earth conductors of the ring
circuit to be tested at the distribution board and note down the reading
(Say A)
2. Connect the meter leads to each end of the phase conductors of the ring
circuit to be tested at the distribution board and note down the reading
(Say B)
3. Connect the meter leads to each end of the neutral conductors of the
ring circuit to be tested at the distribution board note down the reading
(Say C)
4. Temporarily connect phase and earth conductors together at the socket-
outlet at mid point
5. Connect one of the meter leads to paralleled end of the phase conductors
of the ring circuit at the distribution board.
6. Connect the other meter lead to paralleled end of the earth conductors
of the ring circuit at the distribution board and note down the reading
(Say D )
7. D ≈ A/4+B/4
8. Remove the connection between phase and earth conductors and
temporarily connect phase and neutral conductors together at the
socket-outlet at mid point
9. Connect one of the meter leads to paralleled end of the phase conductors
of the ring circuit at the distribution board.
10. Connect the other meter lead to paralleled end of the neutral conductors
of the ring circuit at the distribution board and note down the reading
(Say E )
11. E ≈ B/2 ≈ C/2
Temporary Connection
Continuity
tester
99
Insulation resistance
Test procedure
1. make sure ends of meter tails are separated and not touching
anything
2. disconnect all pilot and indicating lamps
3. disconnect devices with electronic circuits
4. check whether all fuses are in place
5. close all MCBs and switches
6. remove all lamps and other current using equipment.
(If it is not practicable to remove any lamp or disconnect any
current-using equipment, the local switch controlling such lamp
or equipment should be open.)
7. measure the resistances between phase, neutral and earth
conductors at the distribution board. It could be carried out by
measuring the insulation resistance of the following:
Single Phase
1 between phase and neutral conductors
2 between phase and earth conductors
3 between neutral and earth conductors
Three Phase
1 between phase 1 and phase 2 conductors
2 between phase 2 and phase 3 conductors
3 between phase 3 and phase 1 conductors
4 between phase 1 and neutral conductors
5 between phase 2 and neutral conductors
6 between phase 3 and neutral conductors
7 between phase 1 and earth conductors
8 between phase 2 and earth conductors
9 between phase 3 and earth conductors
10 between neutral and earth conductors
Where it is more convenient, conductors may be joined together for this
test.
100
Switches Lamps
Closed Removed
All fuses
or mcb
closed
Insulation Plugs
Resistance Removed
Tester Closed or By-
RCCB passed and
disconnected
Main Switch
Closed
101
Earth electrode resistance
Test Procedure
1. disconnect earthing conductor from the earth electrode
2. connect common lead of the test instrument to the earth electrode
3. plant one test probe about 30 metres away from the earth electrode
4. connect current lead of the test instrument to the test probe
5. plant the other test probe about 10 metres away from the earth electrode in
line with the current probe and earth electrode as shown below.
6. connect voltage lead of the test instrument to this test probe
7. read the earth resistance value from the meter.
Earth
Resistance
Tester
Common Current
Voltage
Voltage Current
Probe Ground Probe
Earth
Electrode
About 10m
About 30m
Fig. 45 - Measurement of Earth Electrode Resistance
102
Operation of residual current devices
Test procedure:
1. Obtain a lamp holder, a plug top matching to the socket-outlet to
be tested, a low wattage lamp and two pieces of flexible cables
2. Connect two ends of the cables to the lamp holder
3. Connect one of the remaining ends to the earth pin of the plug
top
4. Connect the other end to the live pin of the plug top
5. Insert the lamp in the holder
6. Insert the plug top into the socket-outlet to be tested
7. The RCCB would trip if the conductor connected to the earth pin
is properly earthed and RCCB is in working order.
Note:
1. In new installations electricity supply necessary to do this kind of
testing may not be available.
2. In a complete test on a RCD it is required to ascertain the tripping
time. There is an instrument called a RCD tester which could be
used to do a complete test, but it is not described in here because
it is unlikely that average reader would come across such a tester
in normal practice.
103
Short flexible
cable leads Lamp
104
New Colour Code for Cable Cores
In the past the cable core colour codes used in the United Kingdom
and other European countries were different. The United Kingdom changed
its colour code for flexible cables as far back as 1969 to remove trade
barriers in Europe for its domestic and similar equipment. The countries in the
European Union decided to have one colour code throughout Europe. When
the United Kingdom joined EU it had to follow suit. By 1996 all countries in
Europe except the United Kingdom had the core colours of brown or black
for phase conductors, blue for neutral conductor and green-and-yellow for
earth conductor. Thus the United Kingdom had two conflicting situations with
regard to cable core colours, one between its own rigid and flexible cables
and the other between rigid cables of the United Kingdom and of the other
European countries. The colour codes were as follows:
105
In existing installations there is no intention of changing the core
colours to those with new colour code. In an extension to existing installation,
cables with old core colours may be used up to 31st March 2006. Alternatively
cables with new core colours could be used with markings at the changing
point. Thus in domestic installations the change would not cause much
of a problem as all new cables (rigid and flexible) will have the same core
colours. But as long as the old cables are available in the market there is a
possibility of confusion of core colours of blue and black with the old and new
colour codes. (The Regulations allow the use of yellow and blue single core
cables for the phase conductor for single phase work in place of red colour
in large installations in the old code. Similarly black or grey colour could
be used in place of brown as phase conductor in the new code. Therefore
there is a possibility, of black colour single core cables remaining in future
also, continuing the confusion). Where multi (four or more) core cables are
used, cores with blue and black colours will be available on both sides of the
installation at the changing point (referred to as interface), where an extension
is added to an existing installation, with new core colours. It is important to
mark the connection with the correct core colours at this interface. To deal
with this BS 7671: 2001 (2004) contains a new regulation requiring to provide
a warning notice and also contains an appendix called “Harmonized cable
core colours” to provide guidance on marking at the interface between old
and harmonized (new) colours, and general guidance on the colours to be
used for conductors. The following are some extracts:
106
From the Appendix: Harmonized cable core colours
1. Introduction
BS 7671 has been harmonized with the technical intent of CENELEC Standard
“Identification of cores in cables and flexible cores”.
BS 7671 has been modified to align with these cable core colours, but also
allows other suitable methods of marking connections by colours (tapes,
sleeves or discs), or by alphanumerics (letters and/or numbers). Methods
may be mixed within an installation.
2.1 Single-phase
Phase conductors
Old and new conductors: L1, L2, L3.
TABLE 14
Example of conductor marking at the interface for additions and
alterations to an a. c. installation identified with the old cable colours
Function Old conductor New conductor
Colour Marking Marking Colour
Phase 1 of a. c. Red L1 L1 Brown (1)
Phase 2 of a. c. Yellow L2 L2 Black (1)
Phase 3 of a. c. Blue L3 L3 Grey (1)
Neutral of a. c. Black N N Blue
Protective conductor (earth) Green-and-Yellow Green-and-Yellow
(1) Three single-core cables with insulation of the same colour may be used
if identified at the terminations.
(Source: Table 7A, Appendix 7, BS 7671:2001(2004))
107
3. Switch wires in a new installation or an alteration or addition to
an existing installation
Where a two-core cable with cores coloured brown and blue is used as a
switch wire, both conductors being phase conductors, the blue shall be
marked brown or L at its terminations.
Where a three-core cable with cores coloured brown, black and grey is used
as a switch wire, all three conductors being phase conductors, the black and
grey conductors shall be marked brown or L at their terminations.
In a two- or three-phase power circuit the phase conductors may all be one
of the permitted colours either identified L1, L2, L3 or marked brown, black,
grey at their terminations to show the phase.
108
The Sri Lanka Standards Institution has amended the relevant
standards on cables to suit these changes and the manufacturers have made
necessary changes to produce cables abiding by these standards. Therefore
cables with new core colours are available now and there could be both sets
of colours available in the market for some time. Therefore it is essential to
take necessary care in following the correct colour code to avoid confusion.
From the IEE publication referred to above it shall be noted that:
ii. There is no need to change the colour code of the existing
installation
iii. Where both types of cables are used a warning notice shall be
provided at the distribution board
a. In single phase installations there is no need to mark at the
interface, if the colour code has been correctly followed in
both existing and new installations
b. In two- or three-phase installations cores shall be marked
with alphaneumeric characters (L1, L2, L3 and N)
(Two diagrams provided by IEE to illustrate these are shown in Fig. 47 and
Fig. 48.)
Addition
New Circuit
Fig. 47: Addition and alterations using cables with new core colours to an
existing installation
109
Addition
111
References:
112
113