Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Instructionmanual: Reactive Power Regulator S5-6 0D, S5-1 20D

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

INSTRUCTION MANUAL Revised Edition P.

1
REACTIVE POWER REGULATOR S5-60D,S5-120D FRONT VIEW
1 Manual operation 5 Power factor value
2 Switching on capacitor 6 Energized capacitor steps
3 Switching off capacitor 7 Kepad
4 Fault alarm 8 Fault status

DESCRIPTION OF FAULT STATUS


:sensitivity of the low current :incorrect frequency range
:the measured voltage exceeds :the measured voltage is less than
the limiting volt. the limiting volt.
:the measured current exceeds :incorrect phase position
the limiting amp.
MANUAL MODE
1.Press + - simultaneously for 2s, the LEDs "MANUAL" will light up after accessing
the manual mode.
SETTING PROCEDURE 2. Press + for 1s, the LEDs "IND" will light up once switching on capacitor manually.

VIEW SETTING VALUE 3. Press SET for 1s, the LEDs "IND" will put out once stopping switching on capacitor.
By pressing SET for 2s, and then the following symbols will be shown on the display 4. Press - for 1s, the LEDs "CAP" will light up once switching off capacitor manually.
subsequently:
(switching delay time) (number of switching steps) (setting of the target 5. Press SET for 1s, the LEDs "CAP" will put out once stopping switching off capacitor.
cosφ value) (type of switching program) (target cosφmode) (setting
6. Press + - simultaneously for 2s, the LEDs "MANUAL" will put out, meanwhile the
of the C/K value)
auto mode will replace the manual one.

FLOWCHART OF PARAMETERS

F SET +
Press both simultaneously for
2s, access the flowchart of F SET - Press both simultaneously for
2s, leave the flowchart of
parameters 4 parameters

- - - - - - - - -
+ + + + + + + + +
SET SET G SET SET G SET SET G SET SET G SET SET G SET SET G SET SET G SET SET G SET SET G SET SET
F F 5 F F 5 F F F F F F
number of setting of type of auto-adjustment
switching delay time
3
+ switching steps

~ steps 1
+ the target cosφ value
3 + switching program
+ target cosφmode

see
+ setting of the C/K value

: Auto 3
+ fast switching performance
+ setting of the over-voltage range
3 + tripping setup for over-voltage
+ in inverse-phase shift
+
~ ~ ~
- - ~
- - - - - ~
- - -
see descriptions
~ sec.
~ descriptions %
steps 2
COSθ ~

Remark 1 :Setting is applied to S5-60D Remark 3 :Press for over 3s during setting the desired value, the value will Remark 5 :All connected capacitors will be switched off in order once any
be increased/decreased by 5 numerical value setting has been changed
Remark 2 : Setting is applied to S5-120D Remark 4 :Access to the flowchart of parameters, it will leave out the
flowchart of parameters automatically after 2 minutes without
any operation on keypads
DESCRIPTION OF THE PARAMETERS P.2
1. :The switching delay time can be set from seconds.
The setting of the switching delay time will be reset once a few conditions (Inductive/
Capacitive/Normal Load) have been changed. :11(AS)→2→4.4. (SICS)
2. :The number of switching steps can be set from to ( ) steps respectively.
This H.S.P mode will be de-activated for proper operation if the setting of the number Step 6 ..........44444444444.....
of switching steps is less than the switching step in circular sequence. Step 5 ........44444444444.44444.
3. : The target power factor can be set in the range of . inductive up to( . ) capacitive. Step 4 ....44444.....444444444444
The target power factor has to be adjusted to reach a proper controlling program in Step 3 ..22..22.2..22..2..2.22..2
accordance with the setting of the parameter in the P.S.L. Mode. Step 2 ...1...1...1...1...1...1..
4. : The type of switching program has to be set in compliance with the capacity of the
installed capacitors on the network distribution. Step 1 .1...1...1...1...1...1...1
:1:1:1 (switching in circular sequence) +++++++++-++++++---+-----
:1→ 2.2. (SICS)
:1→2 → 4.4. (SICS) . :11(AS)→22(AS)→4.4. (SICS)
:1→ 2→4→8.8. (SICS) Step 6 ........444444444444444.444.
Step 5 ....44444444444444444.44....
:11 (Alternate Switching)→2.2. (SICS) Step 4 ......22....2222222....22..
:11 (AS)→2→4.4. (SICS) Step 3 ..22......2222222....2.....2
Step 2 ...1...1...1..1..1...1...1..
:11 (AS)→2→4→8.8 (SICS) .1...1...1...111...1...1...1
Step 1
. :11 (AS)→22 (AS)→4.4. (SICS) ++++++++++++++-------+-----
:1.1.1 (switching in sequential sequence) 5. . . .:The precise setting of the target cosφmode for a variety of applications has to be set
EXAMPLE OF SWITCHING STEPS: in compliance with the measuring threshold of the actual power factor value.
Furthermore, the detecting band of the set C/K value is mainly derived from the actual
:1→2 → 4.4. (SICS) load variations.
:The setting range can be set from1.00 to the target power factor. And further,
Step 6 ........................44 this mode represents a fixed detecting range.(only set as positive inductive)
Step 5 ................4444444... :The target power factor can be permitted to set in the range of capacitive
Step 4 ........44444444444....... power factor. And further, this mode represents a fixed setting point.
Step 3 ....44444444444........... :This mode comprises the above two modes with their specific features, but
Step 2 ..22..22..222..2...22..2.. the target power factor can not be set to capacitive power.
Step 1 .1.1.1.1.1.1.1.1.1.1.1.1.1 6. :The setting of the C/K value has two types of operating modes, which includes the
manual and automatic . / (auto-detecting) mode. The C/K value can be set from
+++++++++++----++------++ . . during the manual mode.
In case of selecting the manual mode, the calculation of the C/K value has to be done
:1→ 2→4→8.8. (SICS) in compliance with the capacity of the first capacitor.

Step 6 .................888........ Ck = IC / k Var:KVar( the first capacitor)


Step 5 ...............888.......... U:Line-Volt (in the system)
Var
Step 4 ........88888888...888888888 IC = K:C.T. transformation ratio
Step 3 ....4444...4444.4.4.4444.... 3xU
Step 2 ..22..22..2..22.2.2.22..22.. For example:Var =10KVar,U = 380V,k = 400:5 =80
Step 1 .1.1.1.1.11.1.1.1.1.1.1.1.1.
Ck = 10K/(1.732x380x80)= 0.19
+++++++++++++++-+-+--------
※Please refer to page 3, table of C/K value
P.3
Table of the C/K values for 380V
7. . .:Fast switching performance, 。 :Start-up
In order to replace the gradual switching on/off capacitor step, there are two solutions
KV AR
to an extended life of both the catactors and the capacitors as follows.
1. Switching on/off the largest possible capacitor step is in order to reduce the frequent CT 比 2.5 5 7.5 10 15 20 25 30 37.5 40 50 60 80 100
switching operations. And the switching program will directly start entering the step 150/5 0.13 0.25 0.38 0.51 0.76 1.01 1.27 1.52 1.90 2.03
in circular sequence for switching on/off capacitor if the actual load is fitted in with
the circular sequence. Furthermore, the rest of the switching program should be 200/5 0.09 0.19 0.28 0.38 0.57 0.76 0.95 1.14 1.42 1.52 1.90 2.28
activated in compliance with the selected mode. 250/5 0.08 0.15 0.23 0.30 0.46 0.61 0.76 0.91 1.14 1.22 1.52 1.82
2. After starting this procedure, in case of the subsequent connection/ disconnection to 300/5 0.06 0.13 0.19 0.25 0.38 0.51 0.63 0.76 0.95 1.01 1.27 1.52 2.03
capacitor again, a half of the preset switching delay time under the model will be
activated; meanwhile, the decimal point of the unit place also flashes. If no longer 400/5 0.05 0.09 0.14 0.19 0.28 0.38 0.47 0.57 0.71 0.76 0.95 1.14 1.52 1.90
switched on/off capacitor, the switching delay time will recover the standard setting. 500/5 0.04 0.08 0.11 0.15 0.23 0.30 0.38 0.46 0.57 0.61 0.76 0.91 1.22 1.52
※This H.S P. mode will be de-activated for switching on/off capacitor if the setting of 600/5 0.03 0.06 0.09 0.13 0.19 0.25 0.32 0.38 0.47 0.51 0.63 0.76 1.01 1.27
the number of switching steps is less than the switching step in circular sequence.
For example: = 30, = 6, = (step 4 as circular sequence) 800/5 0.02 0.05 0.07 0.09 0.14 0.19 0.24 0.28 0.36 0.38 0.47 0.57 0.76 0.95
In case a compensation demand for the reactive power value (KVar) is 10 times of 1000/5 0.02 0.04 0.06 0.08 0.11 0.15 0.19 0.23 0.28 0.30 0.38 0.46 0.61 0.76
the CK value, the following explanations are as follows:
The controller will directly switch on the capacitor (step 4) after 30 seconds because 1500/5 0.03 0.04 0.05 0.08 0.10 0.13 0.15 0.19 0.20 0.25 0.30 0.41 0.51
the reactive power value (KVar) is higher than 4 times of the C/K value, thus the KVar 2000/5 0.02 0.03 0.04 0.06 0.08 0.09 0.11 0.14 0.15 0.19 0.23 0.30 0.38
value in the system should be derived from the designed formula as 10-4=6.
This way, the derived value (10-4=6) in KVar is still higher than 4 times of the C/K 2500/5 0.02 0.03 0.05 0.06 0.08 0.09 0.11 0.12 0.15 0.18 0.24 0.30
value, a half of the preset switching delay time under the mode will be activated 3000/5 0.03 0.04 0.05 0.06 0.08 0.09 0.10 0.13 0.15 0.20 0.25
for switching on again (new default value has been automatically changed as 15s), 4000/5 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.15 0.19
and meanwhile, the decimal point of the unit place also flashes.
Following up the designed formula, now the latest derived value (6-4=2) in KVar in 5000/5 0.02 0.03 0.04 0.05 0.06 0.06 0.08 0.09 0.12 0.15
the system is less than the step 4 in circular sequence so the H.S P. mode should be
de-activated. Table of the C/K values for 220V
※Select the Auto mode, the H.S P. mode is de-activated.
8. . . .:Setting of the over-voltage range: %。 KV AR
It is no loner switched on capacitor once the measured mains supply exceeds the CT 比 2.5 5 7.5 10 15 20 25 30 40 50 60 80 100
preset range.
9. . . .:Tripping setup for over voltage: : Start-up 150/5 0.22 0.44 0.66 0.87 1.31 1.75 2.19
All the steps will be switched off in order once the legend is shown on the display. 200/5 0.16 0.33 0.49 0.66 0.98 1.31 1.64 1.97
This tripping setting must be activated according to the settings of the and mode. 250/5 0.13 0.26 0.39 0.52 0.79 1.05 1.31 1.57 2.10
10. . .:Auto-adjustment in inverted-phase shift 300/5 0.11 0.22 0.33 0.44 0.66 0.87 1.09 1.31 1.75 2.19
。 :Start-up
The phase-shift will be automatically reversed at 180 degrees as the measured phase 400/5 0.08 0.16 0.25 0.33 0.49 0.66 0.82 0.98 1.31 1.64 1.97
angle exceeds 90 degrees, and the displaying screen indicates after 3 seconds. 500/5 0.07 0.13 0.20 0.26 0.39 0.52 0.66 0.79 1.05 1.31 1.57 2.10
Moreover, it is unnecessary to alternate the cable in the electrical network system 600/5 0.05 0.11 0.16 0.22 0.33 0.44 0.55 0.66 0.87 1.09 1.31 1.75 2.19
except for the phase error.
※This procedure is only applied to the following conditions. 800/5 0.04 0.08 0.12 0.16 0.25 0.33 0.41 0.49 0.66 0.82 0.98 1.31 1.64
1.The connected voltage terminals with the reverse polarity 1000/5 0.03 0.07 0.10 0.13 0.20 0.26 0.33 0.39 0.52 0.66 0.79 1.05 1.31
2.The direction of the measured current flow has been inverted 1500/5 0.02 0.04 0.07 0.09 0.13 0.17 0.22 0.26 0.35 0.44 0.52 0.70 0.87
2000/5 0.03 0.05 0.07 0.10 0.13 0.16 0.20 0.26 0.33 0.39 0.52 0.66
2500/5 0.03 0.04 0.05 0.08 0.10 0.13 0.16 0.21 0.26 0.31 0.42 0.52
3000/5 0.02 0.03 0.04 0.07 0.09 0.11 0.13 0.17 0.22 0.26 0.35 0.44
4000/5 0.02 0.03 0.05 0.07 0.08 0.10 0.13 0.16 0.20 0.26 0.33
5000/5 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.13 0.16 0.21 0.26
P.4

TECHNICAL DATA CONNECTION DIAGRAM


Voltage range : AC 220V ±15% & AC380V ±15%
Power consumption : 4.5 VA(S5-60D), 7.5 VA(S5-120D)
Current range : AC 0.05 ~ 5A
Current consumption: 0.5VA
LEDs display : Digital display, red LED, 14.2mm high, 0.01 PF resolution
Power factor setting range:Cap.0.95~ Ind.0.85 PF.
The default value (0.97) set by factory
Power factor setting mode : Setting value to 1.00 PF. or setting point mode
C/K value setting : Auto/Man setting for the C/K value
Switching delay time: 10 ~ 240 sec. the default value (30s) set by factory
Number of steps : 3 ~ 6 steps for S5-60D, 3 ~ 12 steps for S5-120D
Over voltage setting: the default value (120%) set by factory
Relay Contact Capacity : Max. AC 380V, 5A, typical AC 220V 5A
Operating temperature : 0 ~ 60℃
Storage temperature: -10 ~ 70℃
Dielectric strength : AC 2KV, 60Hz, 1 minute, INPUT/OUTPUT/CASE
Wistanding impulse voltage:IEC 1000-4-5
Wave damping : IEC 1000-4-4
Electrostatic discharge :IEC 1000-4-2
Electrical transient in burst:IEC 1000-4-11
Connection : Plug-in terminal block DIMENSIONS (mm)
Weight : About 0.85kg for S5-60D, 1 kg for S5-120D

You might also like