Colling Fan Selection For Panel: Tepmerature Different

The document provides specifications for selecting a cooling fan for an electronics panel. It lists the maximum ambient temperature, desired interior temperature, and resulting temperature differential. It then gives the total installed power and calculates the required volume flow of air in m^3/h and CFM based on the panel size, required air changes per hour, and fan sizing formula. Remarks provide context on heat generation from electronics components and converting between air volume units.

Uploaded by

thilipkumar
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views

Colling Fan Selection For Panel: Tepmerature Different

The document provides specifications for selecting a cooling fan for an electronics panel. It lists the maximum ambient temperature, desired interior temperature, and resulting temperature differential. It then gives the total installed power and calculates the required volume flow of air in m^3/h and CFM based on the panel size, required air changes per hour, and fan sizing formula. Remarks provide context on heat generation from electronics components and converting between air volume units.

Uploaded by

thilipkumar
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

COLLING FAN SELECTION FOR PANEL

DESCRIPTION TEPMERATURE DIFFERENT Maximum ambient temperature Desired interior temperature Temperature differential TOTAL INSTALL POWER Bus bar Semi-conductor Realy Transformers Installed stray power AIR CONSTANT Air constant VALUE UNITS 50 k 323 k 273 k

150 20 150 75 395 w

3 3.16 m K/Wh

VOLUME FLOW Required volume flow in m^3/h Required volume flow in CFM

4.572161172 m^3/h 2.691073478 CFM

Air Change Method


DESCRIPTION PANEL SIZE Length Width Height Volume of panel REQUIRED AIR CHANGE Airchanges per hour VOLUME FLOW Fan Requirement Fan Requirement VALUE 3 0.3 3 2.7 UNITS m m m m^3

60 /h

162 m^3/h 95.349636 CFM

TOTAL CFM

98.04070948

INLET AND OUTLET SIZE

V = 4005 x Sqrt(P)

V = 4005 x Sqrt(0.75)

REMARKS

The components installed in enclosures (e.g. transformers, relays, semi-conductors, bus bars, etc.) generate heat when in operation. Standard Air Conditions Air density,for many applications, is taken at standard conditions (70F at 29.92" of mercury).

CFM = (watts x 3.16) / Temp. diff 1m^3/hour = 0.588578 CFM

REMARKS

It means 1 min one changes

1m^3/hour = 0.588578 CFM

V = 4005 x Sqrt(P)

V = 4005 x Sqrt(0.75)

Ft/Min.