Design of Pile Cap
Design of Pile Cap
Design of Pile Cap
and bearing capacity should be checked. Pile diameter Pile spacing 12 3-0 14 3-6 16 4-0 18 4-6 20 5-0 22 5-6 24 6-0
Pile cap thickness is normal determined by shear strength. For smaller pile cap, the thickness is normally governed by deep beam shear. For large pile cap, the thickness is governed by direct shear. When necessary, shear reinforcement may be used to reduced thickness pile cap.
The edge distance is normally governed by punching shear capacity of corner piles.
Theory:
Punching shear
The punching shear strength according to ACI is Jvc = 4fc where J = 0.85 is strength reduction factor, fc is compressive strength of concrete. The critical section of punching shear stress is at a distance, d/2, from edge of pile, d is the effective depth of pile cap. For corner pile, the critical section normally extends to
the corner edge of pile cap since it gives less shear area.
Flexural reinforcement
Design of flexural reinforcement is the same as spread footing design. The critical section is at face of column.
Ix = 7 dy2, Iy = 7 dx2.
Design procedure
1. Estimate number of pile needed. Selection pile layout pattern. Calculate individual pile load. The maximum pile load shall not exceed allowable pile capacity. 2. Calculate factored pile load. Assume a depth of pile cap, calculate factored moment and shear at critical section, check direct shear 3. Calculate moment and shear at face of column, check deep beam shear. 4. Check punching shear and edge distance. 5. Design flexural reinforcement.
Design Examples
Pile cap design example: Design Data: Column dead load: PD = 300 kip Column live load: PL = 350 kip Column dead load moment: MDX = 40 ft-kip, MDY = 80 ft-kip Column Live load moment: MLX = 35 ft-kip, MLY = 65 ft-kip Column size: 18"x18" concrete column Type of pile: 16 in diameter concrete pile Allowable pile compression capacity: Pc = 125 kip Allowable pile tension capacity: Pt = 50 kip Compressive strength of concrete: fc = 3000 psi Tensile strength of reinforcing steel: fy = 60 ksi Requirement: Design pile group and pile cap Solution: 1. Estimate number of pile and select pile layout pattern Total service pile vertical load: P = PD+PL = 650 kip Estimate number of pile: n = P/Pc = 5.2 Try a six-pile layout pattern, n = 6 Minimum spacing of pile: s = 16 in x 3 = 4 ft
2. Check pile capacity: dx1 = -4 ft, dx2 = -4 ft, dx3 = 0 ft, dx4 = 0 ft, dx5 = 4 ft, dx6 = 4 ft Iy = dx12+ dx22+ dx32+ dx42+ dx52+ dx62 = 64 ft2. dy1 = -2 ft, dy2 = 2 ft, dy3 = -2 ft, dy4 = 2 ft, dy5 = -2 ft, dy6 = 2 ft Ix = dx12+ dx22+ dx32+ dx42+ dx52+ dx62 = 24 ft2. Column service load moment: Mx = MDX+MLX = 75 ft-kip My = MDy+MLy = 145 ft-kip Maximum pile compression load: P1 = P/n+(Mx*dy1/Ix)+(My*dx1/Iy) = 93 kip P2 = P/n+(Mx*dy2/Ix)+(My*dx2/Iy) = 105 kip P3 = P/n+(Mx*dy3/Ix)+(My*dx3/Iy) = 125 kip P4 = P/n+(Mx*dy4/Ix)+(My*dx4/Iy) = 114.5 kip P5 = P/n+(Mx*dy5/Ix)+(My*dx5/Iy) = 111.1 kip P6 = P/n+(Mx*dy6/Ix)+(My*dx6/Iy) = 123.6 kip 3. Assume a pile cap of 3'6" depth, the top of pile is at 6" above bottom of pile cap and the reinforcement is at 2" above top of pile, the effective depth is d = 34 in Since the effective depth d is less than 4 ft, check direct shear in the longitudinal direction. Factored column load, Pu = 1.4*PD+1.7*PL = 1015 kip Factored column moment: Mux = 1.4MDX+1.7MLX = 115.5 ft-kip Muy = 1.4MDy+1.7MLy = 222.5 ft-kip Factored pile load: Pu1 = Pu/n+(Mux*dy1/Ix)+(Muy*dx1/Iy) = 145.6 kip Pu2 = Pu/n+(Mux*dy2/Ix)+(Muy*dx2/Iy) = 164.8 kip Pu3 = Pu/n+(Mux*dy3/Ix)+(Muy*dx3/Iy) = 159.5 kip Pu4 = Pu/n+(Mux*dy4/Ix)+(Muy*dx4/Iy) = 178.7 kip Pu5 = Pu/n+(Mux*dy5/Ix)+(Muy*dx5/Iy) = 168.6 kip Pu6 = Pu/n+(Mux*dy6/Ix)+(Muy*dx6/Iy) = 192.6 kip The factored shear force at the critical section is Vu = Pu5+Pu6 = 361.3 kip The factored moment at one d from face of column is Mu = (Pu5+Pu6)(4 ft d 9 in) = 150.5 ft-kip Assume an edge distance of 1'9", the width of pile cap is b = 7.5 ft The shear strength of pile cap is JVc =0.85[1.9fc+0.1fc(Vud/Mu)]bd = 367.5 kip > 361.3 kip O.K. 3. Check deep beam shear in the short direction. Factored shear force: Vu = Pu2+Pu4+Pu6 = 536.3 kip The factored moment face of column is Mu = (Pu2+ Pu4+Pu6)(2 ft 9 in) = 670.4 ft-kip The deep beam shear strength of concrete is as follows: The distance from pile to face of column, [ = 24 in 9 in = 15 in The length of pile cap is b = 11 ft The ratio, Vu*d/Mu = 2.26 > 1 JVc =0.85{(d/[)[3.5-2.5(Mu/Vud)][1.9fc+0.1fc (Vu*d/Mu)]}bd=2524 kip JVc =0.85(10fc)bd = 2184 kip > 536.3 kip O.K.
4. Design reinforcement in short direction: Mu = 670.5 ft-kip Factor: Rn = Mu/(0.9*b*d2) = 56 ksi, m = fy/0.85fc = 23.5 Reinforcement ratio: V[ = (1/m)[1-(1-2mRn/fy)] = 0.00094 Check minimum reinforcement: Vmin =V[ *4/3 = 0.0012 or Vmin = 0.002 Area of reinforcement: As = 0.002*b*d = 9.4 in2. Use 10#9 bar, As = 10 in2. Design reinforcement in longitudinal direction: b = 7.5 ft Mu = (Pu5+Pu6)(4 ft 9 in) = 1174 ft-kip Factor: Rn = Mu/(0.9*b*d2) = 150.4 ksi Reinforcement ratio: V[ = (1/m)[1-(1-2mRn/fy)] = 0.0026 Check minimum reinforcement: Vmin =V[ *4/3 = 0.0034 Area of reinforcement: As = 0.0034*b*d = 10.5 in2. Use 11#9 bar, As = 11 in2.