Transformer Oil Testing - SD Myers - Jun 08
Transformer Oil Testing - SD Myers - Jun 08
Transformer Oil Testing - SD Myers - Jun 08
Our Services
Analytical Services Substation Services (SDMI International) Engineered Products (SDMI International) SDMI Solutions PCB Disposal Services (SDMI International)
Analytical Services
On-Line Transformer Testing & Software In-Service Insulating Liquid and Solid Insulation Analysis Electronic Data Management Services for Sampling, Testing, Analysis, Interpretation and Recommendations
SDMI Facts: SDMI Facts:
SDMI Solutions
University & TMI
- e-training
Consulting Services
-
Transformer Assessments Management & Operational Services Oil Processing Specifications Onsite Supervision for Field Service and Transformer Manufacturing
Craig Schley
Corporate and International B.D. TLES Services
OIL!
Acts as a Coolant Provides Dielectric Strength Protects the Paper Used as Diagnostic Tool
PAPER!
PROVIDES
Mechanical Strength Dielectric Strength Dielectric Spacing
Solid Insulation
The life of the insulation is the life of the transformer. Insulation is the weakest link in the transformer. Insulation system is the most important part of the transformer to maintain. Requires early and prompt attention.
1,200 1,000
Life in Service
End of reliable life 200 30,000
WHAT HAPPENS?
Untreated, your oil will attack the paper and drastically cut short the life of your transformer. Oil tests reveal the condition of the oil, paper and therefore the transformer.
39
44
49
54
THE SOLUTION
Remove the sludge, water, etc from the oil and the PAPER. Extend the useful life of the transformer. Perform the work while energized. Minimize unplanned downtime.
OIL RECLAMATION
THE PROCESS
1. Filter oil through 0.5 micron filter. 2. Heat oil up to 200 F - turning it into solvent. 3. Filter with Regenerative Fullers Earth (FLUIDEX) to remove oxidation by-products. 4. Apply vacuum to remove moisture and gases.
34
HOW IT WORKS
Multiple passes of transformer oil through heat, vacuum and fullers earth returning the oil to near virgin condition and cleaning the paper.
WHEN TO RECLAIM . . .
Before the oxidation inhibitors are depleted. While the oil is still in good condition. WHY? The oil is filtered through the paper, removing contaminants. While the oil still appears clean, the paper is actually gathering sludge and deteriorating.
How do we get started? Testing Insulating Liquids Nameplate Information Visual Inspection and Representative Sample Laboratory Analysis Interpretation of Results Review and Clear, Understandable Recommendations Maintenance Acceptance Report Project Management
Qualifying new suppliers. Buying oil for especially large, expensive, or critical units. Acceptance testing.
How well is the oil continuing to fulfill its functions? Non routine testing.
Protect the Paper Insulation Provide Dielectric Strength Provide Heat Transfer (Cooling) Testing Serves as a Diagnostic Tool for the Condition of the Equipment
Liquid Screen Tests Liquid Power Factor @25 and 100C Oxidation Inhibitor Moisture Content Dissolved Gas Analysis
Moisture Content Calculations % Saturation How much moisture is in the oil compared to how much moisture it can hold. % Saturation is a measure of the risk of dielectric failure due to formation of free water in the transformer.
Special testing:
Corrosive sulfur Particle count distribution analysis Particles and filming compounds analysis Others
Results Master Liquid Screen Liquid Power Factor Karl Fischer Gas in Oil Metals in Oil Inhibitor Furan PCB
Any Questions?