Fw: Fw: RCM Stairs

SAMUEL MW POON :
: SAMUEL MW POON

XIAO-HUA WANG, SUI-KUEN SO

16/02/2012 09:39

CONG-WEI YANG, YONG-YANG LIU, YING-QING XIAO, CHI-WING WONG, PEN CW CHAN, CHI-KIT YEUNG 16/02/2012 09:39 Fw: RCM Stairs

All, Below info is also provided by RCM's contractor. Regards, Samuel


----- Forwarded by SAMUEL MW POON/HK/PAL/ATNT on 16/02/2012 09:38 ----From: To: Cc: Date: Subject: Mark Auger <Mark.Auger@IBIGroup.com> "scottchan@palhk.com" <scottchan@palhk.com> "samuelpoon@palhk.com" <samuelpoon@palhk.com>, "Mayne, Maureen" <mayne@mint.ca> 16/02/2012 04:34 Stairs

Scott/Samuel As requested at our last meeting, the following is required for the stairs to meet NBC requirements.

Handrail/guardrail at stair nosing 920mm with mid rail Handrail/guardrail at landing 1070mm with mid rail and toe board Stair tread 280mm min. Stair riser min 125mm to max 180mm Toe board 125mm min. recommended

Please note that handrails have to be 1070 high. We had marked-up your drawings at 1050 high which is not correct. Regards
Mark Auger P.Eng. Associate IBI Group 30 International Boulevard Toronto ON M9W 5P3 Canada tel 416 679 1930 ext 5008 fax 416 675 4620

cell 519 562 4728 email Mark.Auger@IBIGroup.com web www.ibigroup.com


NOTE: This e-mail message and attachments may contain privileged and confidential information. If you have received this message in error, please immediately notify the sender and delete this e-mail message. NOTE: Ce courriel peut contenir de l'information privilgie et confidentielle. Si vous avez recu ce message par erreur, veuillez le mentionner immdiatement l'expditeur et effacer ce courriel.