Buildings in Fired-Brick and Other Masonry Units: 4.2.1 Non-Structural Damage
Buildings in Fired-Brick and Other Masonry Units: 4.2.1 Non-Structural Damage
Chapter 4
4.1 INTRODUCTION
The buildings in fired bricks, solid concrete blocks and hollow concrete or mortar blocks are dealt with in this chapter. The general principles and most details of earthquake resistant design and construction of brick-buildings are applicable to those using other rectangular masonry units such as solid blocks of mortar, concrete, or stabilized soil, or hollow blocks of mortar, or concrete having adequate compressive strength. Some construction details only differ for hollow blocks, which are also indicated as necessary.
IAEE MANUAL
Fig 4.1 Cracking in bearing wall building due to bending and shear
wall. Tension cracks occur vertically at the centre, ends or corners of the walls. Longer the wall and longer the openings, more prominent is the damage, Fig 4.1. Since earthquake effects occur along both axes of a building simultaneously, bending and shearing effects occur often together and the two modes of failures are often combined. Failure in the piers occur due to combined action of flexure and shear. (iii) Unreinforced gable end masonry walls are very unstable and the strutting action of purlins imposes additional force to cause their failure. Horizontal bending tension cracks are caused in the gables.
(iv) The deep beam between two openings one above the other is a weak point of the wall under lateral inplane forces. Cracking in this zone occurs before diagonal cracking of piers, Fig 4.2. In order to prevent it and to enable the full distribution of shear among all piers, either a rigid slab or RC band must exist between them. (v) Walls can be damaged due to the seismic force of the roof, which can cause the formation of tension cracks and separation of supporting walls, Fig 4.3. This mode of failure is the characteristic of massive flat roofs (or floors) supported by joists, which in turn are supported by bearing walls, but without proper connection with them. Also if the connection with foundation is not adequate, walls crack there and slide. This may cause failure of plumbing pipes too. (vi) Failure due to torsion and warping: The damage in unsymmetrical building occurs due to torsion and warping in an earthquake, Fig 3.1. This mode of failure causes excessive cracking due to shear in all walls. Larger damage occurs near the corner of the building. (vii) Arches across openings in walls are often badly cracked since the arches tend to lose their end thrust under in-plane shaking of walls. (viii) Under severe prolonged intense ground motions, the following happens: the cracks become wider and the masonary units become loose -
Fig 4.3 Fall of roof because of inadequate connection between roof and wall
partial collapse and gaps in walls occur due to falling of loose masonry units, particularly at location of piers. falling of spandrel masonry due to collapse of piers
3
IAEE MANUAL
falling of gable masonry due to out of plane cantilever action walls get separated at corners and intermediate T-junctions and fall outwards. roof collapse, either partial or full certain types of roofs may slide off the top of walls and the roof beams fall down masonry arches across wall openings as well as those used for roof collapse completely.
typical of sloping roofs, particularly when slates, clay, tiles etc. are used as roofing material. Brittle material like asbestos cement may be broken if the trusses and sheeting purlins are not properly braced together. (ii) Weak roof to support connection is the cause of separation of roof truss from supports,although complete roof collapse mostly occurs due to collapse of supporting structure. The rupture of bottom chord of roof truss may cause a complete collapse of truss as well as that of walls, Fig 4.4. (iii) Heavy roofs as used in rural areas with large thickness of earth over round timbers cause large inertia forces on top of walls and may lead to complete collapse in severe earthquake shocks. (iv) Lean-to roofs easily cause instability in the lower supporting walls or piers and collapse easily due to lack of ties.
Brittle behaviour in tension as well as compression. Weak connection between wall and wall. Stress concentration at corners of windows and doors. Overall unsymmetry in plan and elevation of building. Unsymmetry due to imbalance in the sizes and positions of openings in the walls. Defects in construction such as use of substandard materials, unfilled joints between bricks, not-plumb walls, improper bonding between walls at right angles, etc.
(ii) Mix of the mortar used and age at which tested. The mortar used for different wall constructions varies in quality as well as strength. It is generally described on the basis of the main binding material such as cement or lime mortar, cement lime composite mortar, lime-pozzolana or hydraulic lime mortar. Clay mud mortar is also used in many countries particular in rural areas. (iii) Slenderness ratio of the wall, that is, smaller of the ratio of effective height and effective length of the wall to its thickness. Larger is the slenderness ratio, smaller the strength. (iv) Eccentricity of the vertical toad on the wall- Larger the eccentricity, smaller the strength. (v) Percentage of openings in the wall larger the openings, smaller the strength. The tensile and shearing strengths of masonry mainly depend upon the bond or adhesion at the contact surface between the masonry
5
IAEE MANUAL Table 4.1 Typical strengths of masonry Mortar mix cement sand Tensile strength, MPa 0.04 0.25 0.71 Shearing strength, MPa 0.22 0.39 1.04 Compressive strength in MPa corresponding to crushing strength of masonry unit 3.5 1 1 1 12 6 3 1.5 2.1 2.4 7.0 2.4 3.3 4.2 10.5 3.3 5.1 6.3 14.0 3.9 6.0 7.5
show that the shearing strength decreases when acting with tension and increases when acting with compression. Fig 4.5 shows the combined strengths. The tensile strength of masonry is not generally relied upon for design purposes under normal loads and the area subjected to tension is assumed cracked. Under seismic conditions, it is recommended that the permissible tensile and shear stresses on the area of horizontal mortar bed joint in masonry may be adopted as given in Table 4.2. The modulus of elasticity of masonry very much depends upon the density and stiffness of masonry unit, besides the mortar mix. For brickwork the values are of the order 2000 MPa for cement-sand mortar in 1:6 proportion. The mass density of masonry mainly depends on the type of masonry unit. For example brickwork will have a mass density of about 1900 kg/m3 and dressed stone masonry 2400 kg/m3. The slenderness ratio of the wall is taken as the lesser of h/t and l/t where h = effective height of the wall and L = its effective length. The allowable stresses in Table 4.2 must be modified for eccentricity of vertical loading due to its position and seismic moment and the slenderness ratio multiplying factors given in Table 4.3. The effective height h may be taken as a factor times the actual height of wall between floors, the factor being 0.75 when floors are rigid diaphragms and 1.00 for flexible roofs; it will be 2.0 for parapets. The effective length L will be a fraction of actual length between lateral supports, the factor being 0.8 for wall continuous
unit and the mortar and, in general, their values are only a small percentage of the crushing strength. Richer is a mortar in cement or lime content, higher is the percentage of tensile and shearing strength in relation to the crushing strength. Test carried out on brick-couplets using hand made bricks in cement mortar give the typical values as shown in Table 4.1. Brick couplet tests under combined tension-shear and compression-shear stresses
BUILDINGS IN FIRED-BRICK AND OTHER MASONRY UNITS Table 4.2 Typical permissible stresses Mortar mix or equivalent cement 1 1 1 lime 1 sand 6 6 3 Permissible stresses tension MPa 0.05 0.13 0.13 shear MPa 0.08 0.20 0.20 Compression for strength of unit, MPa 3.5 0.35 0.35 0.35 7.0 0.55 0.70 0.70 10.5 0.85 1.00 1.05 14.0 1.00 1.10 1.25
with cross walls or buttresses at both ends, 1.0 for continuous at one end and supported on the other and 1.5 for continuous at one and free at the other.
Table 4.3 Stress factor for slenderness ratio and eccentricity of loading Slenderness ratio 6 8 10 12 14 16 18 21 24 0 1.000 0.920 0.840 0.760 0.670 0.580 0.500 0.470 0.440 Stress factor, K, for eccentricity ratio, e/t 0.04 0.10 0.20 0.30 0.33 1.000 0.920 0.835 0.750 0.660 0.565 0.480 0.448 0.415 1.000 0.920 0.830 0.740 0.640 0.545 0.450 0.420 0.380 0.996 0.910 0.810 0.706 0.604 0.500 0.396 0.354 0.310 0.984 0.880 0.770 0.664 0.556 0.440 0.324 0.276 0.220 0.980 0.870 0.760 0.650 0.540 0.420 0.300 0.250 0.190 Remarks 0.50 0.970 0.850 0.730 0.600 0.480 0.350 0.230 0.170 0.110 Values for e/t = 0.5 are for interpolation only Linear interpolation may be used.
IAEE MANUAL Table 4.4 Recommended mortar mixes Category of construction* I II III IV Proportion of cement-lime-sand Cement-sand 1:4 or cement-lime-sand 1:1:6 or richer Cement-lime-sand 1:2:9 or richer Cement-sand 1:6 or richer Cement-sand 1:6 or lime-cinder** 1:3 or richer
wall between consecutive cross walls in single-storey construction, 42 percent in two-storey construction and 33 percent in three storey buildings. (iii) The horizontal distance (pier width) between two openings to be not less than half the height of the shorter opening, Fig 4.6, but not less than 60 cm. (iv) The vertical distance from an opening to an opening directly above it not to be less than 60 cm nor less than 1/2 of the width of the smaller opening, Fig 4.6. (v) When the openings do not comply with requirements (i) to (iv), they
Notes: * Category of construction is defined in Table 3.1. ** In this case some other pozzolonic material like trass (Indonesia) and surkhi (burnt brick fine powder in India) may be used in place of cinder.
(i) Openings to be located away from the inside corner by a clear distance equal to at least 1/4 of the height of openings but not less than 60 cm. (ii) The total length of openings not to exceed 50 percent of the length of the
should either be boxed in reinforced concrete alround or reinforcing bars provided at the jambs through the Masonry, Fig 4.7.
IAEE MANUAL
many times left hollow and weak. To obtain full bond it is necessary to make a sloping (stepped) joint by making the corners first to a height of 600 mm and then building the wall in between them. Otherwise, the toothed joint should be made in both the walls alternately in lifts of about 45 cm, Fig 4.8.
broken properly from course to course. The following deserves special mention.
Longitudinal steel in R.C. bands category II category III no of bars 2 2 2 2 4 diameter of bars, mm 10 12 16 16 12 no of Bars 2 2 2 2 2 diameter of Bars, mm 10 10 12 16 16
Notes: (i) Width of the RC band is assumed to be the same as the thickness of wall. Wall thickness shall be 20 cm minimum. A cover of 25 mm from face of wall will be maintained. For thicker walls, the quantity of steel need not be increased. For thinner walls, see 4.7. (ii) The vertical thickness of RC band may be kept minimum 75 mm where two longitudinal bars are specified and 150 mm where four longitudinal bars are specified. (iii) Concrete mix to be 1:2:4 by volume or having 15 MPa cube crushing strength at 28 days. (iv) The longitudinal bars shall be held in position by steel links or stirrups 6 mm diameter spaced at 150 mm apart (see Fig 4.10 (a)) (v) Bar diameters are for mild-steel. For high strength must deformed bars, equivalent diameter may be used.
10
is through reinforced concrete bands provided continuously through all load bearing longitudinal and transverse walls at plinth, lintel, and roof-eave levels, also at top of gables according to requirements as stated hereunder: (i) Plinth band: This should be provided in those cases where the soil is soft or uneven in their properties as it usually happens in hill tracts. It will also serve as damp proof course. This band is not too critical. (ii) Lintel band: This is the most important band and will incorporate in itself all door and window lintels the
reinforcement of which should be extra to the lintel band steel. It must be provided in all storeys in buildings as per Table 4.5. (iii) Roof band: This band will be required at eave level of trussed roofs, Fig 4.9 and also below or in level with such floors, which consist of joists and covering elements so as to properly integrate them at ends and fix into the walls. (iv) Gable band: Masonry gable ends must have the triangular portion of masonry enclosed in a band, the horizontal part will be continuous with the eave level band on longitudinal
Fig 4.9 Gable band and roof band in barrack type buildings
11
IAEE MANUAL
bands may be kept as follows for wall spans upto 9 m between the cross walls or buttresses. For longer spans, the size of band must be calculated. A band consists of two (or four) longitudinal steel bars with links or stirrups embedded in 75 mm (or 50 mm), thick concrete, Fig 4.10. The thickness of band may be made equal to or a multiple of masonry unit and its width should equal the thickness of wall. The steel bars are located close to the wall faces with 25 mm cover and full continuity is provided at corners and junctions. The minimum size of band and amount of reinforcing will depend upon the unsupported length of wall between cross walls and the effective seismic coefficient based on seismic zone, importance of buildings, type of soil and storey of the building. Appropriate steel and concrete sizes are recommended for various buildings in Table 4.5. Such bands are to be located at critical levels of the building, namely plinth, lintel, roof and gables according to requirements (see 4.5.1).
Fig 4.11 (a) Corner-strengthening by dowel reinforcement placed in one joint (b) Corner-strengthening by dowel reinforcement placed in two consecutive joints. (c) T-junction - strengthening by dowel reinforcements (d) Strengthening by wire fabric at junction and corner 13
IAEE MANUAL Table 4.6 Recommendation for vertical steel at critical sections No of Storeys Diameter of mild steel single bar in mm at each critical section for category (1) category I category II categoryIII category IV 16 Top Bottom Top Middle Bottom Top Third Second Bottom 16 20 16 20 20 (2) 12 12 16 12 16 16 (2) 12 12 16 12 12 16 12 12 16 16 Nil Nil Nil Nil Nil Nil 12 12 12 12
One Two
Three
The jamb steel was shown in Fig 4.7. The jamb steel of window openings will be easiest to provide in box form around it. The vertical steel of opening may be stopped by embedding it into the lintel band but the vertical steel at corners and junctions of walls must be taken into the floor and roof slabs or roof band The total arrangement of providing reinforcing steel in masonry wall construction is schematically shown in Fig 4.13.
Four
Notes: (i) Category of construction is defined in Table 3.1. Equivalent area of twisted grip bars or a number of mild steel bars could be used but the diameter should not be less than 12 mm. (ii) Four storeyed load bearing wall construction may not be used for categories I and II buildings.
IAEE MANUAL
these can be located in two or three consecutive cavities as shown in Fig 4.15. The cavities containing bars are to be filled by using micro-concrete 1:2:3 or cement- coarse sand mortar 1:3 and properly rodded for compaction. Practical difficulty is faced in threading the bars through the hollow blocks since the bars have to be set in footings and have to be kept standing vertically while lifting the blocks whole storey heights, threading the bar into the cavity and lowering it down to the bedding level. To avoid lifting of blocks too high, the bars are made shorter and overlapped with upper portions of bars. This is wastefull of steel as well as the bond strength in small cavities remains doubtful. For solving this problem, two alternatives may be used as shown in Fig.4.16 (a) use of three sided or U-block (b) bent interlocked bars.
17