March 2004
SUMMARY
1 GENERALITIES 2 CHARACTERISTICS 3 FACILITIES 4 ARCHITECTURE 5 HARDWARE FUNCTIONAL DESCRIPTION 6 SOFTWARE FUNCTIONAL DESCRIPTION
Generalities
1 - GENERALITIES
1 FUNCTION
Exchange of information type ON/OFF between two different goegraphical points of an electrical network, with compliance to the following criteria :
Minimum transfer time Security Reliability
Transfer time :
Total time elapsed between the acquisition of an information at the transmission side up to its restitution at the reception side, excluding the transmission support transfer time.
Security :
Ability of the equipments to avoid any restitution in absence of information at the transmission side, even in case of interference on the transmission support.
Reliability :
Ability of the equipment to restitute, in the appropriate transfer time, all the informations occuring at the transmission side.
1 - GENERALITIES
2 PRINCIPLE
At the transmission side the TA 314 convert the ON/OFF signal in a defined frequency signal with a value in the band of 0 to 4 Khz and send it to the transmission medium. At the reception side using sophisticated and accurate filters the TA 314 will identifiy the frequency signal and convert it in an ON/OFF output signal. The TA 314 continuously supervise the transmission support, transmitting a specific frequency signal in lack of input. This frequency is called guard frequency Fg. The TA 314 being able to transmit up to 4 different informations, there will be one frequency signal for each of it respectively called.
FC1 FC2 FC3 FC4
6
for input / output 1 for input / output 2 for input / output 3 for input / output 4
6
1 - GENERALITIES
APPLICATION
The TA 314 is designed to comply with the electrical network protections needs, in term of transfert time characteristic, reliability and security. However it might be used to transmit any kind of information in ON/OFF type, like alarm, apparatus position indicator for interlocking purpose etc... There are 3 defined applications selected on the TA 314 as follows :
"Permissive" type which favour the reliability criteria (for distance protections) "Blocking" type which favour the transfer time (for distance protections) "Direct transfer trip" type which favour the security criteria (for any kind of protections)
Characteristics
2 - CHARACTERISTICS
TRANSMISSION SUPPORT
Any transmission support with a 600 or high impedance 4 wires AF input/output (2 wires transmission / 2 wires reception), for instance : cable, micro wave, optical fiber terminal, radio, PLC etc...
a dry contact (open = no command, closed = command) a voltage (48 V, 127 V or 250 V Dc)
Input command acknowledgment by relay (1 N/O contact for each command) and LED. Minimum time of command presence to be considered as a true input : 5 ms. Possibility of transmission extension by 200 ms.
OUTPUT
By static relay 1 contact N/O (MOS IRF 841) - Vmax 300 V Dc, Imax 2 A, Pmax : 100 W.
Output repeater by relay (1 N/O or N/C contact for each command) and LED. Possibility of restitution extension by 60 ms.
2 - CHARACTERISTICS
Bandwidth Nb of command Fc1 (Hz) Fc2 (Hz) Fc3 (Hz) Fc4 (Hz) FG (Hz)
300 - 2000 Hz 2 480 1120 4 480 800 1120 1440 2240 or 3680
300 - 3400 Hz 2 900 2100 4 640 1280 1920 2560 3600 or 3680
10
10
2 - CHARACTERISTICS
TRANSFER TIME APPLICATION Nb of command Blocking Permissive Transfer-trip 300 - 3400 Hz 300 - 2400 Hz 2 7 ms 4 2 4 300 - 2000 Hz 2 4 12 ms 15 ms 20 ms
9 ms 10 ms 12 ms 10 ms
10 ms 12 ms 13 ms 15 ms 13 ms 15 ms 17 ms 18 ms 20 ms 18 ms
11
11
2 - CHARACTERISTICS
TRANSMITTER
Frequencies accuracy Transmission level : : +/- 1 Hz. from - 30 dBm up to + 6 dBm : up to 14 dB between two
RECEIVER
Level Adjustment : : from - 40 dBm up to 0 dBm common to all frequencies
DC SUPPLY
Nominal voltage Operating margins Consumption: : : 48 Vdc Vmini 38 Vdc, Vmaxi 58 Vdc
200 mA (maximum)
12
12
Facilities
13
13
3 - FACILITIES
COMMISSIONING
Fully programmable by PC excluding :
AF input/output impedance (600 or ) Type of command inputs (dry contact or voltage) Type of auxiliary command output (NO or NC contact) Connection of + 48 V (grounded or floating)
14
14
3 - FACILITIES
OPERATION / MAINTENANCE
HARDWARE
Reset push button Link test push button Alarm status signalling by LED and contact Input / output command status signalling by LED and contact AF input / output test points
Architecture
16
16
4 - ARCHITECTURE
LAYOUT
The TA 314 is installed in a EUROPE standard rack with 19 inches width and 3 units height (1 inch = 25,4 mm ; 3 U = 132,5 mm). 2 HARDWARE ARRANGEMENT
The equipment consists of 2 or 3 modules according to the configuration (2 or 4 commands) and 1 backplate.
1 Module UT 131 : Processor unit module for the equipment management and the signal treatment, transmission support interface. 1 Module SR 110 : Dc supply converter, input / output interface for commands 1&2, alarms interfaces. 1 Backplate FB 117 with different buses for DC distribution, signal exchange between modules. All connectors for field connections. 1 Optional module SR 110.1 : Input / Output interface for commands 3&4.
17
17
18
18
1 1.1
19
19
1.2
20
20
1.3
21
21
22
22
23
23
24
24
25
25
26
26
27
27
2 SR 110 MODULE
2.1 FUNCTION
28
28
2.2
29
29
2.3
The total power for the equipment is 10 Watts. The positive pole of the primary voltage (+ BAT) can be connected to the chassis ground by a strap. The OV of the DC / DC converter is always connected to the main + 48 V (+ BAT). A protection circuit guards against :
HF interferences Current surges Polarity reversal Brief power cuts (< 20 MS)
30
30
2.4
31
31
2.5
32
32
2.6
2.7
33
33
2.8
34
34
3 3.1
35
35
3.2
36
36
4 4.1
37
37
5 5.1
5.2
5.3
38
38
5.4
LED's DESCRIPTION
FUN CTIO N LO CATIO N 2 2 2 2 1 LED LED LED LED LED on on on on on SR 1 1 0 SR 1 1 0 -1 SR 1 1 0 SR 1 1 0 -1 UT 1 3 1 No input Input O N No input Input O N Inactive Active Te st Te st OK KO ACTIO N LED STATUS / CO LO R O ff On O ff On O ff On O ff Flashing 0 ,5 s On OK Flashing 0 ,5 s On On O ff Flashing 0 ,5 s On On KO On On O ff On O ff
39
Re se t Watchdo g Lo o p back mo de Main o n Mainte nance mo de Transmissio n alarm Re ce ptio n alarm Batte ry lo w 5 V 1 5 V alarm
1 1 1 1 1 1 1 1 1 1
LED LED LED LED LED LED LED LED LED LED
on on on on on on on on on on
UT 1 3 1 UT 1 3 1 UT 1 3 1 SR 1 1 0 UT 1 3 1 SR 1 1 0 SR 1 1 0 UT 1 3 1 UT 1 3 1 SR 1 1 0
Active Watchdo g Active Main he althy Main faulty Active Active Active Batte ry 5 V he althy 5 V faulty 1 5 V faulty 1 5 V he althy
39
40
40
GENERALITIES
The TA 314 is monitored by 2 software modules. 1 module is managed by the Digital Signal Processor (DSP), the second one is managed by the 87C51FB microcontroller (C). Each module is separate in different tasks as follow.
TASK Initialisation and configuration Event recording Hardware test MMI communication Alarms monitoring Input / Output command monitoring Transmitter monitoring Receiver monitoring Link test
41 > Analog Teleprotection TA314 - 03/04 -
SOFTWARE MANAGEMENT DSP and C C DSP and C C C C DSP and C DSP and C C
41
2 2.1
ACTION
Re source s initia lisa tion Ha rdwa re te st Te st O K Te st KO Loa ding the configu ra tion pa ra m e te rs (from m e m o ry) Configura tion coh e re n ce te st Te st O K Te st KO : : e nd of ta sk irre ve rsible a la rm : : goe s on irre ve rsible a la rm
42
42
2.2
EVENT RECORDING
Event file monitoring
Events are saved in a backed-up memory stack type FIFO. Up to 64 events are stored. Event file can be erased by operator action.
Counters updating
There are 2 counters per command (1 for input, 1 for output command). The counters cannot be reset and have a capacity of 65535 increments.
43
43
2.3
Memories test (controller internal and external RAM, DSP DATA MEMORY). Loop test on A/D - D/A converters in order to verify the LF level adjustment circuits.
Battery test
It checks the battery capacity and signal the fault by an LED. This does not affect the normal operation of teleprotection.
44
44
2.4
ALARMS MANAGEMENT
This function detects, process and report all fault occurence. Faults are identified following two categories
reversible faults, irreversible faults,
Fault reporting is carried out by 2 LED's, 2 contacts and 1 fault recording file. The file can store up to 32 informations and can be erased by the operator.
45
45
46
46
2.5
COMMANDS INPUT AND OUTPUT This function manages the interface between the command field interfaces and the transmiter / receiver functions.
The test consist to change the status of the signal A on the outputs interface circuit and to drive it to the input B on the inputs interface circuits. The test is carried out permanently if there is no higher priority task. Unsatisfactory test will be repeated once and then irreversible alarm will be initiated in case of new failure.
48
48
2.6
TRANSMITER CONTROL
This function control the transmission over the AF support according to the input command status as follow : 2.6.1 Frequency coding for 2 commands configuration
No order Order 1 Order 2 Order 1 and 2 FC1 FC2 FG FC1 FC2 FG FC1 FC2 FG FC1 FC2 FG
FG+6db
50
50
2.7
RECEIVER CONTROL
This function manages the frequencies filtering and assumes the recognition of commands, unblocking, test and fault conditions. 2.7.1 Recognition of commands
There is one independent chain for each command frequency, plus one for the guard frequency (filtering, detection, logarithmic conversion). If V is the amplitude of the guard frequency and C the command's one after processing, a command is detected if :
51
51
The logic condition C - V > K is continuously computed. Any change result in blocking signal for a T0 period. If command frequency is not detected after a T1 period following loss of the guard frequency, blocking condition is also activated. The transfer time, safety and reliability characteristics depend on the K, T0 and Vmax. parameters
52
52
53
53
2.7.3 Test message recognition Test message consist on the detection of 2 command frequencies and the guard frequency at half level of nominal value for a duration at least equal to 50 ms within normal mode and Fg + 6 dB within enhanced mode. 2.7.4 Fault detection Reversible faults :
Absence of guard frequency not followed by a command 200 ms later. Maximum received signal (command or guard) 16 dB below the reception nominal level, during more than 5 sec.
Irreversible faults :
In case of irreversible faults the receiver functions are no longer assumed.
54
54
2.8
This function can be initiated automatically or manually by a push button. Following action are carried out by the equipment :
Equipment which initiate the test
Activation of test LED. Activation of the transmission blocking command. Transmission of the test message for a duration of 200 ms. Initiating a 200 ms timer and scanning receiver to detect return test message. If the message is detected equipment return to normal immediatly and test LED is turned off after 5 sec. If no message is detected, test is reinitiated after 10 sec. If 3 attemps fail, the equipment is set on irreversible fault condition and the test LED remains on.
55
55
Priority
Any command or fault detection get priority on test. The test is then purely abandoned. If there is a test request during a command or fault treatment, the request is memorized and will be carry on when the higher priority actions will be completed. Any test request during an irreversible fault condition is simply unrecognized.
56
56