Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

K 90 9047 - Print

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Supervisory Pressure Switch (1.5-Inch to 2.

5-Inch Valve)
P/N 06-118262-001 FEATURES
Both Normally Open and Normally Closed Configuration with One Unit Suitable for 10 lb. Through 350 lb. ECS FM-200 Systems

A UTC Fire & Security Company

Effective: January 2010 K-90-9047

UL Listed FM Approved CRUUS Recognized Component (US and Canada)

DESCRIPTION
The cylinder supervisory pressure switch is intended to detect a fall in pressure in the FM-200 cylinder. The cylinder supervisory pressure switch can be wired for either normally open or normally closed operation, depending on installation requirements. This cylinder supervisory pressure switch can be installed on ECS FM-200 cylinders, 10 lb. through 350 lb. size.

OPERATION
When the pressure in the FM-200 container drops from the standard charge pressure of 360 psi (25 bar) to below 288 psi (19.86 bar) the switch operates. If wired in the NC (open-under-pressure) configuration the resulting pressure drop will cause the contacts to close. When connected to a monitored circuit of a suppression control panel the switching will result in an alarm or trouble condition. Note: If the temperature of the cylinder contents drop close to a temperature of 32F (0C) or less the pressure in the cylinder will be equal to or less than 288 psi (19.86 bar) and the switch will operate. However the minimum operating temperature of the system is 32F (0C).

ORDERING INFORMATION
The cylinder supervisory pressure switch offers combined normally opened and normally closed functionally. The part number for ordering the cylinder supervisory pressure switch is 06-118262-001.

SPECIFICATIONS
Setting: 288 psi (19.86 bar) on falling pressure Electrical rating: 5 Amps, 250 Vac Wire color coding: Blue = Normally Open Black = Normally Closed Violet = Common Operating temperature range: 32 to 130F (0 to 54C) Pressure connection: 0.25 SAE 45 flare female with valve core deflector Wetted materials: EPR, Brass Copper Lead length: 36 in. +/- 2 in. (914 mm +/- 50 mm)

INSTALLATION
The supervisory pressure switch can be installed on a fully charged cylinder, without loss of pressure, provided the unit is handled with care and only by trained service personnel. Remove the protective cap from the pressure connection. Do not apply thread compound to the threads. Install the switch with an 1-1/16 open-ended wrench while holding the pressure connection with a 7/ 16 open-end wrench. Tighten hand-tight, plus one-quarter turn. Leak check using a leak detector or bubbling solution. Secure switch body with wrench when connecting electrical conduit. Isolate the assembly from shock, vibration and areas subject to wide-ranging or rapid temperature fluctuations. Disconnect all supply circuits before wiring the supervisory switch.
FM-200 is a registered trademark of the Great Lakes Chemical Corporation.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the products suitability for a particular application. The product must be properly applied to work correctly. If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. K-90-9047 Rev AC 2010 Kidde-Fenwal Inc. Printed in USA

Kidde Fire Systems A UTC Fire & Security Company 400 Main Street Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920 www.kiddefiresystems.com

You might also like