Literature Search For Reliability Data of Components in Electric Distribution Networks
Literature Search For Reliability Data of Components in Electric Distribution Networks
Literature Search For Reliability Data of Components in Electric Distribution Networks
____________________
5 STARTS
STARTS
10 STARTS
80 STARTS
-:-
20 STARTS
150 STARTS
o 2 3 4 5 6 7
THOUSANDS OF SERVICE HOURS
Figure 13. Failure rate as a function of annual service hours, for different values of the
number of starts per year, according to Simpson and Stoll {1989J.
20
15
10
5
__________________
5 STARTS
.0 STARTS
-
10 STARTS
80 STARTS
20 STARTS
.. -:- 150 STARTS
____ __ _L __ ____ __ ____ __
o 23456
THOUSANDS OF SERVICE HOURS
7 8
Figure 14. planned unavailability as a function of annual service hours, for different
values of the number of starts per year, according to Simpson and Stoll {1989J.
-82-
Generators.
PER CENT AVAILABILITY
90
85
80
5 STARTS
40 STARTS
10 STARTS
80 STARTS
20 STARTS
150 STARTS
__ ____ __ ____ __ ____
a 1 2 3 4 5 6
THOUSANDS OF SERVICE HOURS
7 8
Figure 15. Availability (forced and planned) versus annual service hours, for different
values of the number of starts per year, according to Simpson and Stoll [1989J.
PER CENT AVAILABILITY PER CENT FORCED OUTAGE RATE
90 14
-- AVAILABILITy FORCED OUTAGE RATE
12
85
10
/ B
80
.' 6
.'
".
'-.
-. -----_. 4
75
2
o 5 10 15 20 25 30 35 40
YEAR
Figure 16. Availability and failure rate as a function of age, according to Simpson and
Stoll {1989J.
-83- Generators.
7.5. Conclusions
Table 35 and table 36 give the ETTF values for generators. as presented in this chapter.
The values fall into two groups: life times of several days and life times of several years.
From the description of the different studies I concluded that the low value holds for
stand-by units and the high one for continous units. A serious descripancy in this are the
values for conituous units presented by Smith et al. [1990].
From the values presented here I would suggest 5 to 20 days for stand-by units and 1
to 3 years for continuous units.
Table 37 and Table 38 give the expected number of starts to failure (ENTFI. according
to the different sources. From the surveys the fail-to-start probability appears to vary
between 0.5 and 2%. The probability values used in reliability studies are in general
higher: 2 - 20 %.
Section Reference ETTF Remarks
7. 1. I Green and Bourne 19n 13 - 23 vears
7.1.2 IEEE 1984 140 years steam-turbine driven
2.2. years gas-turbine driven
7.1.3 IEEE 1991 5.9 years continous service
185 hours stand by
7.2. I Dickinson 1962 2 years steam-turbine driven
7.2.2 IEEE 1974 32 years steam-turbine driven
1.5 Years RBs-turbine driven
15 years engine driven
7.2.4 O/Donnell 1980 1. 7 vears continuous- age! 10 years
8.3 years continuous" age> 10 years
185 hours stand'by
7.2.7 Morzelle at al. 1989 425 hours stand by: before 1980
1000 hours standb)r; 1980-1988
7.2.10 Smith et at. 1990 II 49 days continuous
8 - 68 days stand'by
7.2.12 Ver"lanke 1991 2 vears
Table 35: Summary of generator life times: recommended values and data from surveys.
Section Reference ETTF Remarks
7.3. I Snaith 19n 300 hours
7.3.2 Magnon et a1. 19n 15 dayS stand'by
7.3.3 Allan et a1. 1980 30 dayS stand'by
7.3.4 Dialynas and ALlan 1986 10 years
7.3.6 WhHing, 1989 320 daYS stand by
7.3.9 Allan and IrI9!I'Rojas 1990 14 days standby_
7.3.11 Prescott et a1. 1991 10 years stand by
Table 36. Summary of generator life times: data used in reliability studies.
-84- Generators.
Section Reference ENTf Remarks
7.2.4 O'Donnell 1980 75
7.2.7 Morzelle et al. 1989 600 before 1980
28 000 19801988
7.2.10 Smith et at. 1990 210 gas turbine driven
155 gas turbine driven
125 gas turbine driven
128 Aasturbine driven
33 diesel driven
270 diesel driven
55 diesel driven
200 diesel driven
300 di esel driven
55 diesel driven
100 diesel driven
11 diesel driven
58 diesel driven
Table 37. Summary of fail-to-start data: data from surveys.
Section Reference ENTF Remarks
7.3.1 snaith 1977 33 diesel generator
63 c i rcui t breaker
7.3.2 Magnon et a l. 1977 51
7.3.3 Allan et al. 1980 10
7.3.4 Dialynas and Allan 1986 10 2 10 MVA
5 1 MVA
7.3.9 Allan and (noa-Roias 1990 20 - 30
7.3.10 Dialynas and Koskolos 1991 10
Table 38: Summary of fail-to-start data: data used in reliability studies.
-85- Generators.
8. "UNINTERRUPTABLE" POWER SUPPLIES
8.1. Recommended yalues
8.1.1. IEEE standard 500 [IEEE,1984] gives reliability data for components of nutlear-
power stations. The data has been derived by a Delphi-method combined with the results
from several surveys and databases. For uninterruptable power supplies the following
data are recommended.
All types
No output
Fail to transfer
Degraded
Incipient
: ETTF = 30 years ; range = <4, 600>
: ETTF = 20 years ; range = <3,450>
: ETTF = 57 years ; range = < 8, 1300 >
: ETTF = 57 years ; range = <8,1100>
Single-phase static inverter
No output : ETTF = 110 years ; range = < 10, 400 >
Fail to transfer : ETTF = 85 years ; range = < 7, 300 >
Degraded : ETTF = 350 years ; range = < 30, 1100 >
Incipient : ETTF = 165 years ; range = < 14, 600 >
Three phase static inverter
No output : ETTF = 40 years ; range = < 4, 600 >
Fail to transfer : ETTF = 30 years ; range = < 3, 450 >
Degraded : ETTF = 55 years ; range = < 6, 900 >
Incipient : ETTF = 120 years ; range = < 10, 2000 >
8.1.2. The IEEE gold book [IEEE,1991] recommends:
rectifiers : ETTF = 26 years.
inverters : ETTF = 291 days.
-86- 'Uninterruptable power supplies'.
8.2. Data from surveys
8.2.1. The IEEE sponsored survey completed in 1972 [lEEE,1974) results in:
rectifiers : ETTF = 26 years ; c.L = [15.65).
inverters : ETTF = 300 days ; c.i. = [200,600 days).
-87- Uninterruptable power supplies.
8.3. Data used in reliability studies
8.3.1. The IEEE orange book [IEEE, 1987) states that large non-redundant UPS systems
can have an ETTF of 20,000 hours (2 years) using handbook reliability data; but field
experience indicates ETTF's in the order of 40,000 hours. A redundant system is 2 - 4
times more reliable than a nonredundant system.
8.3.2. Suntio and White [1988) use different types of UPS to optimize the power supply.
They use the following data:
Traditional Battery
ETTF = 100 years
maintenance checking one a year
SLA battery
ETTF = 50 years
maintenance checking once every 3 years
Rectifier
ETTF = 1 5 years
repair readiness 24 hours
maintenance checking once every year
8.3.3. Van der Vaart en Bouwkneght [1989) give data for the failure of UPS-systems.
They refer to this data as generally accepted figures.
rectifier : ETTF = 4.5 years;
battery : ETTF = 11 years;
inverter : ETTF = 3 years;
defective set isolator : ENTF = 20, N = number of inverter failures;
bypass system : ENTF = 20, N = number of inverter failures;
8.3.4. Schneider [1989] presents reliability parameters for components of UPS-systems.
Load-bus : ETTF = 8000 years ; repair time = 4 hours
DC-bus : ETTF = 8000 years ; repair time = 4 hours
Static switch : ETTF = 12 years ; repair time = 4 hours
Inverter : ETTF = 4 years ; repair time = 4 hours
1 battery : ETTF = 4 years ; repair time = 39 hours
2 batteries in parallel : ETTF = 1800 years ; repair time = 19 hours
8.3.5. Suntio et al. (1989) give the following data for a standby UPS:
Inverter : ETTF = 10.3 years
Battery charger : ETTF = 17.1 years
Transfer switch : ETTF = 22.8 years
For a true UPS they give
Inverter : ETTF = 3.5 years
Rectifier : 6.2 years
Bypass switch: 22.8 years
-88- Uninterruptable power supplies.
Figure 17 shows the difference between a standby UPS and a true UPS.
Public
p"""r
L.i ...
-
StatJ.c Dypua Switch
R.cti- Inver-
tier
1-,-
tor
aattery
S .. _
Transrer Swi tc:h
CRITICAL
AC
LOAD
Batt. In-
Char- _ ~
pI" ter
CRITICAL
AC
LOAD
Figure 17: True UPS (left) and standby UPS (right); from Suntio et al. [19891.
8.3.6. Bakker [1989] mentiones the following data, as given by compagny A for their
UPS.
Rectifier/charger : ETTF
=
9 years.
Battery : ETTF
=
14 years
Inventer : ETTF
=
6 years
Static interrupter (ultra rapid stoppage) : ETTF
=
60 years
static by-pass switch : ETTF
=
60 years
For Compagny B the following data were given:
Rectifier/charger
Battery
Inverter
: ETTF = 7.6 years
: repair time = 12 hours
: ETTF = 9.5 years
: repair time = 12 hours
: ETTF = 3.6 years
Static by-pass switch
: repair time = 12 hours
: ETTF = 16.5 years
DC bus
AC bus
: repair time = 12 hours
: ETTF = 11.4 years
: repair time = 2 hours
: ETTF = 43.1 years
: repair time = 2 hours
From this data he determines ETTF-values for emmergency supplies from 3
manufacturers. The results are given in Table 39.
Manuf. A. Manuf. B Manuf. C
Static Static Dvnamic
Standard UPS 24E" 20 yr 23 yr
Extra inverter 41 yr 29 yr
2 UPS chains 60 yr 33 yr 132 yr
3 UPS chains 60 yr
2 9 ~ 59 -"ir
Table 39: ETTF for different UPS types from
three manufacturers [Bakker, 19891.
-89- Uninterruptable power supplies.
8.3.7. Fiorina and Chevalier [1990] compare two methods for the reliability analysis of
UPS-systems. They use the following data (derived from Merlin Gerin studies on
elements):
Bypass switch : ETTF = 50 years
Inverter : ETTF = 10 years
Battery : ETTF = 14 years
Rectifier : ETTF = 8 years
;repair time = 6 hours.
; repair time = 6 hours.
; repair time = 6 hours.
; repair time = 6 hours.
8.3.8. Dialynas and Koskolos [1991] use data for failure of UPS for a reliability study of
an industrial power system. Redundant UPS's are used. They use the following data.
rectifier : ETTF = 27.4 yr ; repair time = 1 hour;
inverter : ETTF = 5.5 yr ; repair time = 1 hour;
main time to discharge battery: 8 hours;
probability of static interrupter not successfully isolating faulted inverter: 1 %.
8.3.9. Prescott et al. [1991] use a value of ETTF = 35 years for the failure of a UPS
plant.
8.3.10. Lee [1991] compares a dual-conversion UPS with a single-conversion on-line
UPS. Figure 18 shows both types. He states that for a dual-conversion UPS:
ETTF - 400 days
This low value is due to the constant heating and stress produced in the power
semiconductors.
The new single-conversion on-line designs are said to have a higher reliability:
ETTF - 2000 days.
-'"
SWkswiU'h
,-------lC
'" - -
'"
~ = - - - - a -
I!
- '--_...J--
- SappiJ1'DaCewimucWtyanUable
- Silpplrnme wIda taiUtJ fIiJun!
.- ~
-. l
T
- Supply rowt wttb oUlky .,aiiIbIt
- Supply I"Mlte wid! ~ . faihlre
Figure 18: Single conversion UPS (left) and dual conversion UPS (right);
from Lee [1991J.
-90- Uninterruptable power supplies.
8.3.11. Warren [1992] examines different UPS system configurations to formulate the
most reliable system. The failure rates used are based on field statistics and MIL-HDBK-
217-E. He uses the following data:
Rectifier
Battery
Inverter
Static Switch
Electromagnetic transfer switch
: ETIF = 20 years;
: ETIF = 11 years;
: ETIF = 6 years;
: ETIF = 45 years;
: ETIF = 22 years;
-91-
Uninterruptable power supplies.
8.4. Ageing data
No ageing data for UPS's has been found.
-92- 'Uninterruptable power supplies'.
8.5. Conclusions
Table 40 summarizes the life time values for components of Uninterruptable power
supplies. Table 41 summarizes these values for complete UPS systems. For batteries,
switches and busses no survey data were available. This makes it hard to judge the
worth of the different values used in reliability studies.
The only survey available gives a lifetime of about 1 year for the inverter, making it by
far the most sensitive part of the UPS. Remarkably, all reliability studies use a higher
reliablity for the inverter: ETIF = 3 - 10 years. The lower values is however confirmed
by [IEEE, 1987) and [Lee, 1991) who give UPS lifetimes of 2 and 1 year, respectively.
All other studies use UPS lifetimes that are probably much too optimistic.
From the available information I would suggest 0.5 to 2 years for the inverter and 10 to
30 years for the rectifier.
Section Reference inverter rectifier battery bypass load-bus DC bus Remarks
switch
8.1.2 IEEE 1991 291 d 26 yr
8.2.1 IEEE 1974 300 d 26 yr
8.3.2 suntio and White 1988 15 yr 50100 yr
8.3.3 van der Veart 1989 3 yr 4.5 yr 11 yr 10
8.3.4 Scheider 1989
4 ~
4 yr 12 yr
8.3.5 suntio et ale 1989 3.5 yr 6.2 yr 22.8 yr true UPS
10.3 yr 17.1 yr 22.8 yr stand-by UPS
8.3.6 Bakker 1989 6 yr
9E
14 yr 30 yr manuf. A
3.6 yr 7_6 yr 9.5 yr 16.5 yr 43.1 yr 11.4 yr manuf. B
8.3.7 Fiorine et al. 1990 10 yr 8 yr 14 yr 50 yr
8.3.8 Dialvnas et at. 1991 5.5 yr 27.4 yr
100 *
8.3.11 Warren 1992 6 yr 20 yr 11 yr 22-45 yr
Table 40: Summary of UPS component lifetimes.
Section Reference ETTF Remarks
8.1_ 1 IEEE 1984 30 years no output
20 years fail to transfer
57 years de.raded
57 years inci2!ent
8.3.1 IEEE 1987 2 - 4 years non- redundant
4 - 16 years redundant
8.3.6 Bakker 1989 20 - 23 years standard UPS
29 - 41 years extra inverter
33 - 132 years 2 UPS chains
29 - 60 years 3 UPS chains
8.3.9 Prescott et ale 1991 35 years
8.3.10 Lee 1991 400 days dual conversion
2000 days single conversion
Table 41: Summary of UPS lifetimes.
-93- 'Uninterruptable power supplies'.
9. CABLES AND ACCESSORIES
All values in this chapter are for 1000 meter of cable, unless otherwise noted I
9.1. Recommended values
9.1.1, Green and Bourne [19721 give average component failure-rates for electrical
components. For cables they give:
less than 1 kV ETTF
1 to 33 kV: ETTF
33 kV to 275 kV
: 190 years
: 26 years
: ETTF = 1 5 years
9.1.2. Kloeppel et al. [19901 give recommended values of component data for reliability
studies. They were based on data from several industries in Eastern Germany, as well
as from the public supply. They recommend the values below:
1 KV : ETTF = 17 years, range = <7,60>
: repair time = 12 hours, range < 1 0, 30 >
6, 10 kV : ETTF = 14 years, range = <7,50>
: repair time = 12 hours, range = < 10, 30>
20, 30 kV : ETTF = 11 years, range = <8, 50>
: repair time = 30 hours, range = < 15, 50 >
110 kV : ETTF = 11 years, range = < 10, 100>
: repair time = 40 hours, range = <30, 100>
9.1.3. The IEEE gold book [IEEE, 1991 1 recommends the ETTF values given in Table 42.
Type of cable ETTF (ye.rs) average median
repair time repair time
(hours) (hours)
Above ground and aerial
o 600 Volt 216 457.0 10.5
600 - 15 000 Volt
All 21.6 40.4 6.9
In trays above ground 33.0 8.9 8.0
In conduit above ground 6.2 140.0 47.5
Aerial cable 2.1 31.6 5.3
Below ground and direct burial
o - 600 Volt 78.6 15.0 24.0
600 - 15 000 Volt
All 49.4 95.5 35.0
In duct or conduit 49.7 96.8 35.0
Above 15 000 Volt 90.7 16.0 16.0
thenmoDlastic 600 15 000 Yolt 78.8 44.5 10.0
thermosetting 600 - 15 000 Volt 34.3 168.0 10.0
lpaper insulated lead covered 600 V - 15 kV 33.4 48.9 26.8
other type of insulation 600 - 15 000 Volt 16.6 16.1 28.5
Table 42: Recommended values according to IEEE Gold Book [IEEE, 1991 J.
-94- Cables and acessoiries
The last two colums give the industry average and the median plant average of the
actual downtime per failure.
The IEEE gold book recommends the following ETTF values for for cable joints with rated
voltages between 600 and 15,000 Volts ..
all types of insulation; in duct or conduit below ground
ETTF = 1150 year;
average repair time = 36.1 hours;
median repair time = 31.2 hours
thermoplastic
ETTF = 1325 year;
average repair time = 15.8 hours;
median repair time = 8.0 hours.
paper insulated lead covered
ETTF = 950 year;
average repair time = 31.4 hours;
median repair time = 28.0 hours.
The IEEE gold book recommends the following ETTF-values for cable terminations for
rated voltages between 600 and 15,000 kV.
thermoplastic
ETTF = 239 year;
average repair time = 10.6 hours;
median repair time = 11.5 hours.
thermosetting
ETTF = 3260 year;
average repair time = 451.0 hours;
median repair time = 11.3 hours.
paper insulated lead covered
ETTF = 1280 year;
average repair time = 68.8 hours;
median repair time = 29.2 hours.
-95- Cables and acessoiries
9.2. Data from surveys
9.2.1. Dickinson (1962) gives the results of an AlEE survey held in 1959 after the
reliability of electrical equipment in industrial plants. the survey covered 33 compagnies
with 58 plants. The results for power cables are reproduced below.
Lead-covered power cable
aerial : ETTF = 25 yr
above-ground conduit : ETTF = 410 days
underground conduit : ETTF = 12 yr
direct burial : ETTF = 22 yr
Non-leaded power cable
aerial
above-ground conduit
underground conduit
direct burial
: ETTF '" 5% yr
: ETTF '" 12 yr
: ETTF = 8 yr
: ETTF = 6 yr
The following repair times are reported:
Lead-covered power cable.
aerial : 5 hours
above-ground conduit : 5 hours
underground conduit : 111 hours
direct burial : 21 hours
Non leaded power cable
aerial
above-ground conduit
underground conduit
direct burial
: 93 hours
: 36 hours
: 53 hours
: 190 hours
For cable joints and terminations results are:
; sample too small for confidence interval
; c.i. = <300,750 days>
; c.i. = <9,15 yr>
;c.i. = <17, 34yr>
; c.i. = <4, 7% yr>
; c.i. = < 10, 16 yr>
; c.i. = <7,9 yr>
; c.L = <3, 12 yr>
leaded : ETTF = 550 year ; c.L = < 450, 700 yr>
non-leaded: ETTF = 310 year; c.i. = <260,380 yr>
The repair times reported are:
leaded joints! terminations : 15 hours
non-leaded joints/terminations : 17 hours
9.2.2. Connor and Parkins (1966) report about a 14-year survey of failures in networks
with nominal voltages between 2 and 33 kV. The records of some 130,000 km.years
were available. For underground cables the following values are found:
2-5 kV solid or resistance earthing: ETTF = 55 years;
6.6 kV solid or resistance earthing : ETTF = 19 years;
11 kV arc-suppression coil : ETTF = 19 years;
11 kV solid or resistance earthing : ETTF = 23 years;
-96- Cables and acessoiries
22 kV solid or resistance earthing : ETTF = 35 years;
33 kV solid or resistance earthing : ETTF = 58 years.
Table 43 gives the relative contributions of the different faulure causes to the failure
rate:
S.YS.tem vol tege 2-5 kV 6.6 kV 11 kV 11 kV 22 kV 33 kV
method of earthing sol id/res sol id/res arc sup co; 1 sot id/res sol id/res sol id/res total
hlll16n agency 49% 42X 27% 29% 43X 21X 30X
mechanical damage to sheath 4X 7% 3X 4X 5X 4X 4%
corrosion 4X lX 2X
insulation failure l1X l1X 20X 17% 7% 29% 17%
failure 5X 17% lOX lax 7% 11%
termination failure 7% 16X 20X 15X 20X 4X 16X
I joint fai lure l1X 13X ax 13X 2X 25X l1X
I Around subsidence 7% 1X 3X 5X 4% 4X
miscellaneous 7% 5X 4% 8X 7% 5X
Table 43. Contribution of different causes to power cable failures, according to Connor
and Parkins [1966J
The most serious single fault cause is human agency. This is (according to the authors)
mainly due to the increasing use of excavators and other mechanical aids. Since 1951
the fault rate due to human agency has increased in both urban and rural areas. The
most likely times for this type of fault to occur are round 9.00 am and round 3.00 pm.
For failures in the underground cable itself, follows from the above data:
2-5 kV solid or resistance earthing : ETTF = 67 years;
6.6 kV solid or resistance earthing: ETTF = 27 years;
11 kV arc-suppression coil : ETTF = 26 years;
11 kV solid or resistance earthing : ETTF = 32 years;
22 kV solid or resistance earthing : ETTF = 45 years;
33 kV solid or resistance earthing : ETTF = 82 years.
The lower failure rate of 33 kV cables, in comparison with 11 kV cables, is said to be
due to the fact that 33 kV cables are generally larger, mechanically stronger, and usually
buried deeper than 11 kV cables. The main failure causes for 33 kV cables are: insulation
failure and joint failure.
For cable joints they found:
11 kV
33 kV
: ETTF = 1100 years;
: ETTF = 1100 years.
For cable terminations the results are:
11 kV
33 kV
: ETTF = 1000 years;
: ETTF = 2500 years.
-97- Cables and acessoiries
9.2.3. An IEEE sponsored survey of electrical equipment reliability in industrial plants
was completed during 1972 IIEEE,1974J. This survey included a total of 1982
equipment failures that were reported by 30 compagnies covering 68 plants in nine
industries in the United States and Canada. The results for cables are given in Table 44.
The last four columns give, respectively: the industry average of the actual downtime
per failure; the median plant average of the actual downtime per failure; the average
estimated time to fix the failure during 24 hour work day in case of repair of the failed
components and in case of replace with a spare.
Type of cable ETTF c. i. Bvesrege actual down time estimated restore
(years> (hours) time (hours)
; n d u s t ~ plant recall' replace
Cable all type of insulation 50 [40 60]
Above ground and aerfal
o 600 Volt 200 [100 2000] 457.0 10.5 20.8 39.7
600 . 15 000 Vol t
All 20 [15 30] 40.4 6.9 26.8 60.4
In trays above ArOlSld 30 [20 65] 8.9 8.0 49.4 119.0
In conduit above ground 6 [319] 140.0 47.5 19.8
Aerial cabLe 20 [15 30] 31.6 5.3 10.6 28.0
Below growd and direct burial
o - 600 Volt 75 [40 700] 15.0 24.0 26.8
600 - 15 000 Volt
All 50 [40 60] 95.5 35.0 20.4 26.8
In duct or conduit 50 [40 60] 96.8 35.0 20.9 26.8
Above 15 000 Volt 90 [50 450] 16.0 16.0 16.0
Cable - thenmoplastic
600 - 15 000 Volt 75 [50 140] 44.5 10.0 22.5 29.3
Cable - thermosetting
600 - 15 000 Volt 35 [25 50] 168 26.0 27.2 55.2
Cable - paper insulated lead
covered
600 - 15 000 Volt 35 [25 50] 48.9 26.8 17.3 18.3
CabLe - other type of insulation
600 - 15 000 Volt 17 [10 35] 16.1 28.5 23.2 44.8
Table 44: Cable data according to 1972 IEEE survey [IEEE,19741.
The survey resulted in the ETTF-values and corresponding confidence intervals for cable
joints for rated voltages between 600 and 15,000 Volts, as shown in Table 45.
type of joint ETTF c. i. average actual down time estimated restore time
(years) (hours) (hours)
industry i plant repair restore
All tvoes of insulation
all 1000 [800 2000]
above ground and aerial 1200 [600 7500]
in duct or conduit below ground 1150 [850 1800] 36.1 31.2 14.7 5.5
thermoelastic 1300 [900 2300] 15.8 8.0 12.6 22.0
thermosetting 800 [400 5000]
paper insulated lead covered 950 [600 2250] 31.4 28.0 30.0
Table 45. Data for cable joints according to the 1972 IEEE survey [IEEE, 19741
-98- Cables and acessoiries
From the confidence intervals one can conclude that it is not realistic to consider
different ETTF-values for the different types of cable joints.
The survey result for cable terminations are given in Table 46.
type of termination ETTF c. ;. average actuaL down time estimated restore time
(vears) (hours) (hours)
industry 'plant reoair restore
All types of insulation 1650 [1350 2100]
o 600 VoLts
Above ground and areal 7900 [4500 32000] 3.8 4.0 8.0 8.0
600 - 15 000 Volt 1130 [850 1700] 198 11.1 34.6 40.6
Above ground and areaL 1130 [850 1700]
in trays above ground 3000 [1700 12000] 8.0 9.0 48.8 58.3
in condui t above ground 780 [435 4000]
aedal cable 540 [380 1000] 48.5 11.3 15.3 18.0
duct or conduit below ground 3300 [1850 13000] 25.0 23.4 28.8 30.0
thennoDLastic 240 [150 600] 10.6 11.5 12.0 12.0
thermosetting 3300 [2100 7000] 451 11.3 30.2 42.8
paper insulated lead covered 1300 [850 2500] 68.8 29.2 39.0 30.0
Table 46. Data for cable terminations according to the 1972 IEEE survey [IEEE, 19741
9.2.4. Braun [1986] presents some results of the failure data kept by the Northwest
Underground Distribution Committee of the Northwest Electric Light and Power
Association. Their annual report on component reliability is only concerned with natural
failures. All failures caused by abnormal external means, such as through dig-ins or
damage prior to installation are not intended to be included in the data. The author
mentiones that there are still problems with field people not reporting the material
failures. All failure rates reported should therefore he considered on the low side. For 15
kV-cable he finds the ETTF-values in Table 47.
Year HMWPE XLPE
175mn
2
220 1J1112
175 nm
2
220 nm
2
1973 179 yr. 115 yr. 596 yr. -
1974 392 yr. 114 yr. 304 yr. 287 Yr.
1975 223 yr. 107 yr. 488 yr. -
1976 135 yr. 126 yr. 342 yr. 94 yr.
19n 129 yr. 155 yr. 413 yr. -
1978 78 yr. 233 vr. 152 vr. 2011 vr.
1979 60 yr. 179 yr. 237 yr. 1341 yr.
1980 47 vr. 248 yr. 5363 vr. -
1981 30 yr. 169 vr. 1609 yr.
1982 34 yr. 2299 yr. -
1983 37 yr. 93 yr. 304 yr.
-
Table 47: Data for 15 kV cables according to Braun 19861.
The results for low-voltage (oS 600 Volts) cables are given in Table 48.
Figure 19 shows the ETTF for 175 mm
2
and 220 mm
2
, 15 kV, HMWPE-cables plus the
confidence interval for the consecutive years. The author only gives the size of the
population for 1983. It is assumed that the size of the population did not change. There
is a clear decrease in ETTF for 175 mm
2
as a function of time. No explanation for this
-99- Cables and acessoiries
decrease is given. There is no significant change in ETTF for 220 mm
2
.
year ETTF year ETTF year ETTF
1969 107 yr. 1974
322 Yr. 1979 220 yr.
1970 129 yr. 1975
413 yr.
1980 335 yr.
1971 217 yr. 1976
304 yr.
1981 201 yr.
1972 260 Yr. 19n 220 yr. 1982 230 Yr.
1973 460 yr. 1978 227 yr. 1983 206 yr.
Table 48: Data for low-voltage cables according to Braun [1986J.
' ~ r - - - - - - - - - - - - - - - - - - - - - ~
!
5
,.
1 ~ - - - - - - - - - - ~ - - - - - - - - - - ~
,L-__________ ~ ________ ~
1In 1171 1113 1171 117. 1113
ob .. rved y .. r ob .. fwd , r
Figure 19. ETTF for 175 mm
2
(left) and 220 mm
2
(right) 15 kV HMWPE cables,
according to Braun [1986J. The shaded areas represent the 95% confidence intervals.
From the 1983 data, for which the population size has been given, confidence intervals
can be determined:
HMWPE, 175 mm
2
15 kV
HMWPE, 220 mm
2
15 kV
XLPE, 175 mm
2
15 kV
HMWPE, 25 kV
XLPE, low voltage
: ETTF = 37 years, c.i. = <33,41 >
: ETTF = 93 years, c.i. = < 73, 130 >
: ETTF = 300 years, c.i. = < 200,500>
: ETTF = 18 years, c.i. = <15,23>
: ETTF = 180 years, c.i. = < 160, 200>
For primary splices, 15 kV, molded rubber, the 1983 data results in:
ETTF = 470 years; c.i. = <400,550 years>.
For primary splices, 25 kV, molded rubber:
ETTF = 3000 years,
For primary s[lices, 35 kV, molded rubber:
ETTF = 2200 years.
In the two latter cases, there is not enough data for a confidence interval.
-100- Cables and acessoiries
9.2.5. Ferran et al. [1986) give failure data for underground cables in the EdF-network
during the first half of the eighties. Table 49 gives the ETTF for 1 km of underground
MV network. The network under study had a total length of about 75,000 km. From the
text one can conclude that these values include all failures in the network, i.e. not only
those in the underground cable. The increase of the ETTF is significant.
year EnF c.; .
1982 11.2 yr. <10.9 11.4>
1983 11.9 yr. <11.6 12.2>
1984 13.4 yr. <13.0 13.7.
'82-'84 12. I yr. <11.9 12.3>
Table 49: Data for underground MV networks according to Ferran et al. [1986J.
The results for about 70,000 km of underground LV network are given in Table 50. From
the text one can conclude that these values include all failures in the network, i.e. not
only those in the underground cable.
year EnF c. i .
1982 12. I yr. <11.8-12.4>
1983 12.1 yr. <11.812.4.
1984 13.2 yr. <12.813.5.
1985 12.5 yr. <12.3'12.6.
Table 50: Data for underground L V networks according to Ferran et al. [1986J.
Table 51 gives the ETTF-values for underground MV-cables.
lQ)rignated paper isolation
Year EnF c. i.
1980 27.3 yr. <26.228.6.
1981 32.9 yr. <31.4]4.5.
1982 32.3 yr. <30.833.8>
1983 44.3 yr. <42.0-46.8>
1984 53.2 vr. <50.3-65.4>
'80- '84 36.0 yr. <35.336.8.
XLPE insuLation
Year EnF c. i.
1980 30.3 yr. <28.432.3.
1981 35.1 yr. <33.2,37.2.
1982 42.0 yr. <39.8-44.4>
1983 50.8 yr. <48.3,53.6.
1984 54.0 vr. <51.456.9>
'80- '84 43.8 yr. <42.8-44.8>
Table 51: Data for underground MV
cables according to Ferran et al.
[1986J.
I.
-
- .-
5.
00 00 000 000 00 .. ~ ..
/
e
/
/
~
.! 40
00 000 . ~ . 000
-Imprlgnated pap.,
/
"
/
"-XLPE
~
_r
-
31
Y
-
. - .. .. _. _. 00 000
2.
1980 1 1 U82 1983 1984
obMrved y .. ,
Figure 20. Trent in cable life time, according
to Ferran et al. [1986J.
The trent in reliablity is shown in Figure 20. It can easily be seen that the reliability of
cables increases. As the values for both isolation type are about the same and remain
about the same, one can conclude that the failure mechanism may have nothing to do
with the type of isolation. Before 1980 the newly installed cables were mainly paper-
-101- Cables and acessoiries
insulated lead-covered; After 1980 mainly XLPE insulated 3-core twisted.
The values found for cable joints are shown in Table 52.
XLPE/XLPE ~ o i n t s Paper/XlPE joints
observed year ETTF observed year ETTF
1980 1600 yrs 1980 830 yr.
1981 1800 yr. 1981 760 yr.
1982 2000 yrs 1982 910 yr.
1983 4800 yr. 1983 no yr.
1984 14 000 yr. 1984 760 yrs
Table 52: Cable joint data according to Ferran et al. (1986J.
For cable terminations they give:
1980:
1981 :
1982:
1983:
1984:
ETTF = 6,000 years
ETTF = 20,000 years
ETTF = 50,000 years
ETTF > 20,000 years
ETTF > 200,000 years
9.2.6. One of teh Dutch regional electricity authorities, NV PNEM. performed a survey
after the reliability of components in their 10 kV network, covering the period 1980 -
1986 [van Amelsfoort et al.,1986). It resulted for cables in:
ETTF = 100 years, c.i. = [90,110J.
9.2.7. Waumans [19861 presents the result of failure registration in a number of medium
and low-voltage networks in the Netherlands, during 1979 through 1984. The results
are summarized in Table 53.
polymer insulated PBl:Ier fnsulated all twe.
non armored armored lead covered includinLl9ints and terminations
mediun voltage 103_yeafs ,. 1000 years 70_ years 5S years
low voltage 13 years 60 years 32 years 21 years
house service connection 48 years 42 year. 18 years
Table 53. Data for underground cables, according to Waumans {1986J.
9.2.8. During 1987 VDEN registered all failures of power system equipment in Dutch
medium-voltage and low-voltage distribution networks [VDEN, 19881. For the 400 Volt
networks they registered 2006 failures in 69,692 km of underground cable, leading to:
ETTF = 34.7 yrs, c.i. = [33,371.
Detailed results are given in Table 54.
For 10-12.5 kV cables the survey results in:
ETTF = 79 years c.i. = [74,861 (not including failure of a joint)
-102- Cables and acessoiries
ETTF = 59 years c.i. = [55,63) (including failure of a joint).
For 10-12.5 kV the survey results in a subdivision of failure causes for underground
cables, joints and terminations.
Manufacture and assembly
Excavation
: 9 %
: 43 %
: 7 % Soil warping
Moisture
Pollution and wear
Others external
Others internal
: 5 %
:4%
: 14 %
: 16 %
~ r insulated lead covered
All hi lures
Excavations
Others
oolvmer insulated armoured
All failures
Excavations
others
polymer insulated non-armoured
All failures
Excavations
Others
ETTF (yrl c.;. (yrl
38 [35 42]
IT [70 86]
IT [70 86]
71 [60 88]
110 [90 150]
200 [150 300]
20 [18 22]
32 [28 36]
52 [45 62]
Table 54. Data for 400 Volt cables according to VDEN survey (VDEN, 19881.
9.2.9. Pijls (1988) analysed failures in the electricity supply to a number of chemical
plants during 8 years. For a 10kV cable connection he finds
ETTF = 90 year, c.i. = <65,140 year>.
The typical cable length in the system under study is one kilometer.
70% of the failures occured in the cable itself;
20% in the cable connectors;
10% in the cable terminators.
This implies for failure in the underground cable itself:
ETTF = 125 years; c.i. = <80,275 years>.
From the failure data collected we find for cable terminations of 10 kV cables:
ETTF = 1850 years, c.L = < 900, ->
9.2.10. A group of experts on synthetically insulated MV-cables performed a survey
after the reliability of MV-cables with different types of insulation IBlechschmidt,1989).
-103- Cables and acessoiries
Results were obtained from a population of almost 500,000 km.year.
The results of the survey over the period 1980-1986 are given in Table 55. The results
of the survey over the period 1980-1988 are given in Table 56 for LOPE and XLPE
insulated cables [Blechschmidt et al.,19911. Table 57 gives the results of the survey
over the years 1987 and 1988, i.e. the difference between the two tables above. The
differences between these three tables are considerable.
10 kV 20 kV 30 kV
ETTF c. i. ETTF c.i. ETTF c. i ..
XLPE 260 [240 285] 330 [305 360] 38 [33 45J
LOPE 112 [100 128] 34 [32 36) 26 [23 30)
PVC 25 [23 28) 18 [15 23) 7.3 [6 9)
EPR 32 [28 36) 80 [60 115) 39 [33 46)
Table 55: Cable data over 1980 - 1986, according to Blechschmidt [19891.
10 kV 20 kV 30 kV
ETTF c.L ETTF c. i .. ETTF c. i ..
XLPE 325 [30OJ50) 250 [240 270) 35
LOPE 150 [135 170) 27 [26 28) 23 [21 26)
Table 56: Cable data over 1980-1988, according to Blechschmidt et al. [1991].
10 kV 20 kV 30 kV
ETTF c. i .. ETTF c. i. ETTF c. f ..
XLPE 540 [470 650) 183 [170 200) 33 [27 41)
LOPE 270 [200 400) 16 [15 In 17 [14 20)
Table 57: Cable data over 1987 and 1988 (difference of Table 56 and 57).
9.2.11. The Rural electrical
Association (a credit agency of
the U.S. Department of
Agriculture) conducted a survey
after failures of cables in 1988
and 1989 [Dedman and
Bowles, 19901. By observing a
population of about 400,000
km.year and over 9,000 cable
failures they find:
ETTF = 44 years.
They also registered the year of
installation of the cable. This
made it possible to determine
25o,----------------------------------,
200 1---------------t'I:--I--'I-------l
b
year of installation
the average failure rate during Figure 21. ETTF for cables of different year of
the passed life time of cables installation, according to Dedman and Bowles [19901.
as a function of the year of
installation. The results are
given in table 58. Figure 21 gives the inverse failure rate (ETTF) of cables of different
year of installation, during 1988 and 1989. The value for 1985 (ETTF = 651 years) has
-104- Cables and acessoiries
been omitted for clearity. In general, older cables show more failures than younger
cables; but for very young cables the trent appaers to reverse.
year of observed ETTF (1 kin) c.i. (years)
installation kin. year
1970 13 298 36 vr <33 40>
1971 25 544 17 vr <16 18>
1972 26724 20 vr <19 21>
1973 31 588 42 vr <39 45>
1974 36 347 22 vr <21 23>
1975 36560 40 Yf <37 43>
1976 31 522 38 yr <35 41>
1977 36 569 72 vr <65 80>
1978 45 203 161 vr <140 180>
1979 39 710 89 yr <80 100>
1980 26 370 56 yr <51 62>
1981 19 823 215 yr <180 270>
1982 14 867 162 yr <135 205>
1983 13 303 242 yr <190 330>
1984 11 166 115 yr <95 145>
1985 10 420 651 yr <430 1300>
1986 6 526 96 yr <75 130>
1987 5 738 25 yr <22 29>
1988 2079 40 yr <30 55>
All 433 357 44 yr
Table 58: "Ageing" data according to REA survey [Dedman, Bowles, 19901.
9.2.12. Franke [1990) observed, during 12 years, failures in a chemical plant in Eastern
Germany. Early failures in the wear-in phase (1.5 .. 2 years) have been removed from the
data. For 6 kV cables he finds:
ETTF = 45 years; c.i. = < 30.70>
Included in this value are
single and multi-phase shortcircuits
short-circuits in cable joints
short-circuits in cable terminations
9.2.13. Horton et al. [1990) provide estimates of the failure rates of underground
distribution system components. Data on molded rubber splices was available since
1982 from NELPA (Northwest Electric Light and Power Association) surveys:
15 kV splices : ETTF = 325 years
25 kV splices: ETTF = 550 years
35 kV splices : ETTF = 400 years
; c.i. = <300,350>
; c.i. = <450,700>
;c.i. = <300,650>
-105- Cables and acessoiries
9.2.14. Heiss and Schweer [1991] present the analysis of failure events during 5 years
in 3000 km of underground cables in compensated 20 kV networks. From this they find
for underground cables:
ETTF = 47 years; c.i. = <42,53 years>
70 % of the faults were caused by foreign influences (dredges, trench work and stones),
10% by atmospheric overvoltages (the systems under study contained some 5000 km
of overhead lines),
20% by material faults
74% of all fault locations concerned the underground cables,
6% the cable joints,
20 % the cable terminations.
This implies for failures in the undergroudn cable itself:
ETTF = 63 years; c.i. = < 56,73 >
9.2.15. Morrison and Arhart [1991] give data for cable system performance in the period
1961-1990. Data has been collected from 36 plants of a major industrial manufacturer.
Their results are given in Table 59. A subdivision in failure location is given in Table 60.
Incorporating only failures in the cable itself leads to the lifetime expectations given in
Table 61.
ETTF c.; .
All cables 41 years <35 49>
EPR 29 years <Z3 41>
HMllPE 26 years <ZO 38>
other 66 ye.rs <51 91>
Table 59: Cable lifetimes, according to Morrison and Arhart [1991J.
cable joints term
EPR 98X ZX
.
HMllPE 73X 10X 17X
Other BOX 10X 1 0 ~
Table 60: Failure location, according to Morrison and Arnhart [1991J.
ETTF c.;'
All cables 49 vrs [41 59]
EPR 30 yr. [Z3 4Z]
HMWPE 35 yr. [Z6 56]
Other 8Z vr. [6Z 1Z0]
Table 61: Only failures in the cable itself, according to Morrison and Arnhart [1991J.
-106- Cables and acessoiries
The authors made a comparison between cables in a wet environment and cables a dry
environment. The reliability of cables in a wet environment is significantly lower than
that of cables in a dry environment. The holds expecially for EPR insulated cables where
54 failures occured in 43 circuit-miles of wet environment but none in 23 circuit miles
of dry environment. Some results are given in Table 62.
wet env; rorrnent dry env;rorment
ETTF c. i. ETTF c. i .
EPR 1 4 ~ . [11 19]
. .
HMWPE 23 yr. [17 35] 26 yrs [14 156]
others 73 yrs [53 115] 55 yrs [39 m
all cables 34 yr. [29 42] 73 yrs [53 116]
Table 62: Influence of environment, according to Morrison and Arnhart [1991].
9.2.16. Bovy et al. (1991) analysed the outage occurances in some 4000 km of
underground 10kV cable of a Dutch utility, during 6 years. For 1 km of underground
cable they find:
ETTF = 77 years, c.L = < 68,87 years>
repair time = 12.4 hours
ETTF (phase-to-earth faults) = 1100 years, c.i. = < 1500, 2500 years>
probability of multiple fault following phase-to-earth fault: 26%
9.2.17. Verplanke (1991) studied failures that occured in the power system of a
chemical industry in The Netherlands between 1970 and 1991.
50 kV and 11 kV cable connections:
ETTF = 180 years; c.L <120,300.
25 % of the failures occured in the cable joints, 75 % in the cable itself.
This implies for failures in the cable itself:
ETTF = 240 years.
-107- Cables and acessoiries
9.3. Data used in reliability studies
9.3.1. Dickinson [1957) gives a typical value of ETTF = 12 years for 1 km of cable
2,400 volt and up. and a typical value of ETTF = 22 years for 1 km of cable 600 volt
and below.
Typical repair times are 28 hours if a spare length is on hand and 41 hours if the run is
too long for the spare length.
For cable joints in industrial power systems he gives a typical value of:
ETTF = 200 years.
For the repair time after failures in cable terminations he gives:
2400 volt and below
6900 volt and below
26,400 volt
: 10 hours
: 14 hours
35 hours and more:
9.3.2. Dickinson [1960) uses the following values for power distribution systems for
refinery process units. The values are based on several published papers and on records
obtained from refineries.
straight jOint : ETTF = 1000 years ; repair time = 40 hours.
tee joint. leaded : ETTF = 500 years ; repair time = 40 hours.
tee joint. rubber or equal : ETTF = 1000 years ; repair time = 30 years.
9.3.3. Capra et al. [1969) use the following data for a reliability analysis of 12 kV
underground distribution systems of Pacific Gas and Electric.
three-phase cable : ETTF = 32-160 years;
single-phase cable : ETTF = 80 - 320 years
For 12 kV cable terminations they use the following data:
600 A terminations : ETTF = 670 - 1250 years;
200 A terminations : ETTF = 400 - 1250 years.
They use the following estimated time range for different operations in underground
distribution systems:
receive alarm. travel to open substation breaker. or open main-line interruptor
receive trouble call. travel to open line protective device
identify new sectionalizing location
read fault locators for single-phase system
read fault locators for three-phase system
remove or replace grate
operate switch or automatic interruptor
-108-
: 15 - 30 minutes;
: 40 - 90 minutes;
: 3 - 6 minutes;
: 3 - 6 minutes;
: 6 - 12 minutes;
: 6 - 12 minutes;
: 2 minutes;
Cables and acessoiries
remove 200 A terminations
replace 200 A terminations
drive between adjacent sectionalizing points:
single-phase system
three-phase laterals
three-phase main
operate nonload-break disconnects
call for test
: 9 - 18 minutes;
: 8 - 17 minutes;
: 2 - 3 minutes;
: 3 - 6 minutes;
: 6 - 9 minutes;
: 3 minutes;
: 6 - 12 minutes.
9.3.4. Bocker and Kaufmann [1977] use the following values for 10 kV cable in a public
distribution network:
ETTF = 20 years; repair time = 9 hours.
9.3.5. Lonsdale and Hitchen [1977] use the following value for underground cable in a
public distribution network in the Nothwest of England. The data were based on an
examination of system performance over recent years:
ETTF = 42 years.
9.3.6. Chang [1977] uses the following data for single-phase lateral cable to evaluate
distribution system design:
ETTF = 40 years;
For cable terminations he uses:
ETTF = 1000 years;
average repair time required in restoration work:
receive call, travel to location : 45 minutes;
interrogate fault indicators : 36 minutes;
operate load break connector/switch : 15 minutes;
locate fault with fault locator : 1 hour;
repair cable : 5 hours.
replace cable terminations : 6 hours.
9.3.7. McNab [1977] uses the following values for 33 kV cable in a public distribution
network in the South of Scotland:
ETTF = 42 years; repair time = 128 hours.
9.3.8. Allan, Dialynas and Hormer [1979] use the following data for cables in a reliability
study of a distribution system:
ETTF = 31 years;
repair time = 33.5 hours;
time to maintenance = 4 years;
maintenance time = 8 hours.
-109- Cables and acessoiries
9.3.9. Allan et al. [1980] use, in a reliability study of electrical auxilary systems of a
power station, the cable reliability data shown in Table 63.
ETTF repair time
23.5 kV 200 yr 120 h
11 kV 200 yr 48h
3.2 kV 200 yr 36h
Table 63: Cable data used by Allan et al. [1980}.
9.3.10. Nelson and Johnson [1982] compare three distribution voltages for the power
supply to a gas centrifuge uranium enrichment plant. They use the following reliability
data (based on 1974 IEEE survey and on other available data) for cables:
13.8 kV: ETTF = 50 years;
24.9 kV: ETTF = 45 years;
34.5 kV: ETTF = 42 years.
For cable joints they use:
13.8 kV: ETTF = 1150 years;
24.9 kV: ETTF = 770 years;
34.5 kV: ETTF = 580 years.
For cable terminations they use:
13.8 kV: ETTF = 3300 years;
24.9 kV: ETTF = 2200 years;
34.5 kV: ETTF = 1650 years.
9.3.11. Ruoff and van Meeteren [1983] use a value of ETTF = 53 years for short-
circuits in underground distribution cable.
9.3.12. Williams and Mudge [1983] use a value of ETTF = 25 years for an 11 kV
incoming cable and of ETTF = 20 years for a feeding cable. The repair time used is 30
hours. The values have been drawn from distribution system statistics.
9.3.13. Billinton and Goel [1986] use the following data for cable sections in a reliability
analysis of an existing 14.4 kV distribution network in Saskatchewan, Canada:
ETTF = 59 years;
repair time = 8 hours.
9.3.14. Dialynas and Allan [1986) use the following values for cables, when including
local generation in the reliability analysis of power distribution systems:
ETTF = 31 years;
repair time = 33.5 hours;
time to maintenance = 4 years;
maintenance time = 8 hours.
-110- Cables and acessoiries
9.3.15. Dialynas and Allan [1987) describe a reliability model for a power distribution
network with local generation. For cables they use:
ETTF = 30 years;
repair time = 33.5 hours.
9.3.16. Goldberg et al. [1987) use the following values for an underground 21 kV feeder
of Pacific Gas and Electric:
HMWPE cable after 10 years of service:
ETTF = 32 years
XLPE cable in the first year of operation:
ETTF = 530 years
9.3.17. Billinton [1987) uses for cable sections in the Annaheim distribution system of
the Saskatchewan Power Corporation:
ETTF = 60 years;
repair time = 8 hours.
9.3.18. Dialynas [1988) uses a value of ETTF = 120 years for 150 kV cable.
9.3.19. Brzozowska-Theil and Theil [1988) incorparate reliability in the switching of
medium voltage networks. For 20 kV-cable they use the following data:
ETTF = 7 years;
repair time = 2.0 hours;
switching time = 0.5 hours.
9.3.20. Dialynas and Papadopoulos [1989) use a value of ETTF = 20 years for 20 kV
cables.
9.3.21. Fransen [1989) uses a value of ETTF = 195 years for short circuits in cables.
The value is based on 7 Y. years of failure data in the power system of a large chemical
plant. The author does not relate the ETTF value to a length of cable. Typical cable
lengths in the system under study are between one and two kilometers. The repair time
used is 24 hours. The author mentions 19 failures in 7 Y. years in about 500 cables. This
leads to c.L = < 125. 375 years>
9.3.22. Roos [1989) compares the supply reliability for different configurations of
medium voltage power systems. For cable strings he uses the following values:
Independent failure of cable string due to failure in cable (for 1 km of cable):
ETTF = 31 years;
repair time = 15 hours
Independent failure of cable string due to failure in station (for 1 cable string):
ETTF = 170 years;
repair time = 6.5 hours
-111- Cables and acessoiries
9.3.23. Whiting [1989] determines the reliability of power supplies to broadcast
transmitting stations. Component data are taken from various sources. For single-phase
cable he uses:
11 kV lead-covered cable:
ETTF = 180 years
repair time = 48 hours
11 kV pvc - insulated cable
ETTF = 400 years
repair time = 36 hours
415 V lead-covered cable
ETTF = 180 years
repair time = 24 hours
415 V pvc-insulated cable
ETTF = 400 years
repair time = 12 hours
9.3.24. Horton et al. [1989a] determine the reliability of service of an underground 21
kV feeder of Pacific Gas and Electric. They use the following data:
HMWPE cable after 10 years of service
ETTF = 32 years
XLPE cable in the first year of operation
ETTF = 530 years
9.3.25. Horton et al. [1989b] use their Distribution Reliability Assessment Model
(DREAM) to compute reliability indices for distribution feeders. They use the following
cable data:
HMPWE cable
ETTF = 32 years
repair time: 90 minutes
XLPE cable
ETTF = 530 years
repair time = 90 minutes
9.3.26. Allan and Inga-Rojas [1990] describe a method for distribution system reliability.
In an example they use for cable connections:
ETTF = 10 years.
9.3.27. Sallam et al. [1990] calculate. as an example. reliability indices for the MV-
network of Port-Fouad. Egypt. For 3-phase cable they use the followinf values:
ETTF = 7.8 years
repair time = 1.09 hours
-112- Cables and acessoiries
For cable terminations at 13.8 kV they use:
ETTF = 550 years
repair time = 25.0 hours
9.3.28. Mohan Rao and Sekhar [1990] compare the reliability of a number of distribution
systems. They use the following data:
13.8 kV cable, conduit below ground
ETTF = 50 years
repair time = 26.5 hours
480 V cable, conduit above ground
ETTF = 230 years
repair time = 11 hours
cable terminations, 13.8 kV
ETTF = 550 years
repair time = 25 hours
cable terminations, 480 V
ETTF = 5000 years
repair time = 4 hours
9.3.29. Dialynas and Koskolos [1991] use a value of ETTF = 120 years for 1 km of
cable. The repair time used is 96.0 hours. The cable in their system is operated at 20
kV.
9.3.30. Volkmann et al. [1991] use a value of
ETTF = 32 years
for underground HMWPE-cable, and a value of
ETTF = 535 years
for underground XLPE-cable.
The average repair time, from historical outage data, is 302 minutes for cables in a rural
system and 229 minutes for cables in an urban system.
They refer to two internal reports of Pacific Gas and Electric as a source for these
values.
9.3.31. Kjelle and Sand [1991] give the following values for cables in distribution
networks in Norway:
22 kV rural network
ETTF = 20 years; repair time = 13.7 hours;
11 kV urban network
ETTF = 22 years; repair time = 13.7 hours.
-113- Cables and acessoiries
9.4. Ageing data
9.4.1. Bar et al. [1990) use a Delphi-method to determine the position of the knee in the
bath-tub curve, i.e. the age where the wear-out phase starts to become-important.
For paper-insulated-Iead-covered low-voltage cable they find, in case of
good-circumstances : 54 years
average-circumstances : 44 years
bad-circumstances : 28 years
For polymer insulated low-voltage cable they find, in case of
good-circumstances : 48 years
average-circumstances : 39 years
bad-circumstances : 25 years
For paper-insulated lead-covered medium-voltage cable they find, in case of
good-circumstances : 45 years
average-circumstances : 42 years
bad-circumstances : 34 years
For polymer-insulated medium-voltage cable they find, in case of
good-circumstances : 34 years
average-circumstances: 30 years
bad-circumstances : 20 years
For "mass" terminations of low-voltage cables they find, in case of
good-circumstances : 55 years
average-circumstances : 48 years
bad-circumstances : 35 years
For low-voltage synthetic terminations they find, in case of
good-circumstances : 52 years
average-circumstances : 46 years
bad-circumstances : 31 years
For medium-voltage oil-filled cable terminations they find, in case of
good-circumstances : 42 years
average-circumstances : 40 years
bad-circumstances : 31 years
For medium-voltage "dry" terminations they find, in case of
good-circumstances : 31 years
average-circumstances : 27 years
bad-circumstances : 19 years
For medium-voltage "mass" terminations they find, in case of
good-circumstances : 44 years
average-circumstances : 36 years
bad-circumstances : 22 years
-114- Cables and acessoiries
9.4.2. Horton et al. [1990) provide estimates of the failure rates of the failure rates of
underground distrbution system components. The estimates are based on information
collected from a number of utility sources throughout the United States of America. For
each component and each year they used the number of units installed or removed and
the number of failures which have occured.
A Weibull-distribution has been assumed for the time-to-failure with repair as-bas-as-old.
Consequently the form of the failure rate is taken to be:
J.( t) = :;:. t
m
-
1
,
where m is the shape factor and 8 the characteristic time-to-failure.
From 764 failures in 98,797 km. years of 15 kV HMWPE unjacketed cable in operation
by San Diego Gas and Electric they find:
m = 1.3; 8 = 85 years.
Assuming a constant failure rate would have led to ETTF = 129 years.
From 226 failures in 86,191 km.years of 15 kV XLPE 175 mm
2
unjacketed cable in
operation by Northwest Electric Light and Power Association they find a constant failure
rate:
m = 1; 8 = 380 years.
An analysis of 18 years and 4700 km of 220 mm
2
cable again gives a constant failure
rate
m = 1; 8 = 1200 years.
The higher value for 220 mm
2
cable might be attributed to lower average voltage stress
in the larger cable.
-115- Cables and acessoiries
9.5 Conclusions
If the results of surveys on cable reliability show one thing, it is the difficulty in obtaining
usefull fail data. Braun [1986] shows a large yea r-to-yea r variation in failure data, for the
same system. The year to year variation is considerably larger than the confidence
intervals. The number of failures in a certain year is thus no good predictor for the
number of failures in later years. Also Ferran et al. [1986]. Blechschmidt et al. [1991]
and Dedman and Bowles [1990] show this large variation. The change in failure rate is
due to, among others, ageing of cable types, introduction of new cable types, changes
in the amount of excavations. Variations might even be due to improved registration of
failures.
As an example, Figure 64 gives the prediction from 1980-1986 data and the value for
1987-1988, according to Blechschmidt [1989] and Blechschmidt et al. [1991]. For the
prediction a 99.5% confidence interval has been chosen.
voltage type 19801986 1987-1988
10 kV XLPE 230-300 years 540 years
LOPE 95-135 years 270 years
20 kV XLPE 290-375 years 183_1ears
LOPE 3137 y.ars 16 years
30 kV XLPE 30-50y.ars 33 years
LOPE 2032 y.ars 17 years
Table 64: Predicted value (1980-1986) and
actual value (1978-1988) for cable life time,
according to Blechschmidt et al. [1989, 19911.
For 10 kV cables the prediction is too pessimistic, for 20 kV cables it is too optimistic;
for 30 kV cables the prediction turned out to be fairly reasonable.
Despite these problems I will try to obtain some acceptable values for cable lifetimes,
Tables 65 and 66 summarize therefore the available data. Table 65 gives data from
suveys; Table 66 data used in reliability studies. The values hold for failures in an
underground cable itself (i.e excluding failures in cable joints and in cable terminations).
Between the strong variations, values between 40 and 75 years appear to be acceptable
for reliability studies. These values are indeed often used in reliability studies.
Data for cable terminations are summarized in Table 67 and Table 68. Values between
1000 and 3000 years seem to be reasonable.
Data for cable jOints are summarized in Table 69 and Table 70. Values between 500 and
2000 years seem to be reasonable.
-116- Cables and acessoiries
Section Reference LV M'I Remarks
9.1.1 Green and Bourne 1972 190 26
9.1.2 Klo...,.1 et al. 1990 17 11-14
9.2.1 Dickinson 1962 22 armored
6 non-armored
9.2.2 COMer and Parkins 1966 2682 depending on nom;nal voltage
9.2.3 IEEE 1974 75 50-90
9.2.4 Brall"l 1986 250 122 M'I strOM Iv time dependent
9.2.5 Ferran et at. 1986 36 DBDer insulation
44 polymer insulation
9.2.6 van Amelsfoort et al. 1986 100
9.2.7 lJaLlOans 1986 42-60 .1000 oolvmer armored
13-48 103 oolvmer non-armored
1832 70 paper insulated lead covered
9.2.8 WEN 1988 35 79
9.2.9 pij Is 1988 90
9.2.10 Blechschmidt, 1989 7.3-260 depending on nominal voltage and on
tYPe of insulation
Blechschmidt et at., 1991 16-540 depending on nominal voltage and on
tYPe of insulation
9.2.11 Dedman and Bowles 1990 44 strong year-to-Year variation
9.2.12 Franke 1990 45
9.2.14 Heiss and Schweer 1991 47
9.2.15 Morrison and Arhart 1991 30-35
9.2.16 BoyY et at. 1991 77
9.2.17 VerplBnke 1991 150
Table 65. Summary of cable life times: recommended values and data from surveys.
-, , 7-
Cables and acessoiries
section Reference LV MY Remarks
9.3.1 Dickinson 1957 200
9.3.3 Capra et al. 1969 32-320
9.3.4 Boeker and Kaufmann 1977 20
9.3.5 Lonsdale and Hitchen 1977 42
9.3.6 Cheng. 1977 40
9.3.7 McNab 1977 42
9.3.8 Allan Dialynas and Hormer 1979 31
9.3.9 Allan et a1. 1980 200
9.3.10 Nelson and Johnson 1982 42-50
9.3.11 Ruoff and van Meeteren 1983 53
9.3.12 Will; oms end MudJje 1983 20-25
9.3.13 Billinton and Goel 1986 59
9.3.14 Dialynas and Allan 1986 31
9.3.15 Dialvnas and Allan 1987 30
9.3.16 Goldberg et al. 1987 32-530
9.3.17 Bil linton 1987 60
9.3.19 BrzozowskaTheil and Theil 1988 7
9.3.20 Olelynas end P!l"ld<>l1QUlos 1989 20
9.3.21 Fransen 1989 195
9.3.22 Roos 1989 31
9.3.23 Whiting, 1989 180 180 lead covered
400 400 lool_r Insuleted
9.3.24 Horton et al. 198ge 32-530
9.3.25 Horton et al. 1989b 32-530
9.3.26 Allan and InQaRojas 1990 10
9.3.27 Sallern et at. 1990 7.8
9.3.28 Mohan Roo end Sekher 1990 230 50
9.3.29 Dialynas and Koskolos 1991 120
9.3.30 Volkmann et a1. 1991 32-535
9.3.31 Kjelle and Sand 1991 20-22
Table 66. Summary of cable lifetimes: data used in reliability studies.
Section Reference ETTF Remarks
9.2.1 Dickinson 1962 550 leaded
310 non leaded
9.2.2 Connor and Parkins 1966 1000 11 kV
2500 33 kV
9.2.3 IEEE 1974 3300
9.2.5 Ferran et at. 1986 > 6000
9.2.9 Pi jls 1988 1850
Table 67. Summary of cable termination life times: recommended
values and data from surveys.
-118- Cables and acessoiries
Section Reference ETTF Remarks
9.3.3 Capra et al. 1969 670-1250 600 A
400-1250 200A
9.3.6 Chan . 19n 1000
9.3.10 Nelson and Johnson 1982 3300 13.8 kV
2200 24.9 kV
1650 34.5 kV
9.3.27 Sallam et at. 1990 550
9.3.28 Mohan Rao and Sekhar 1990 550 13.8 kV
5000 480 Vol t
Table 68. Summary of cable termination life times: data used in
reliability studies.
Section Reference ETTF Remarks
9.2.1 Dickinson 1962 550 leaded
310 non-leaded
9.2.3 IEEE 1974 1000
9.2.4 Braun 1986 470 15 kV
3000 25 kV
2200 35 kV
9.2.5 Ferran et al. 1986 4800 XLPE/XLPE
800 XLPE/paper
9.2.13 Horton et a l. 1990 325 15 kV
550 25 kV
400 35 kV
9.2.17 Verplanke 1991 180
Table 69. Summary of cable joint lifetimes: recommended values and
data from surveys.
Section Reference ETTF Remarks
9.3.1 Dickinson 1957 200
9.3.2 Dickinson 1960 1000 straigt joint
500 leaded tee joint
1000 rubber tee joint
9.3.10 Nelson and Johnson 1982 3300 13.8 kV
2200 24.9 kV
1650 34.5 kV
Table 70. Summary of cable joint life times: data used in reliability
studies.
-119- Cables and acessoiries
10. BUSBARS
10.1. Recommended values
10.1.1. Kloeppel et al. [19901 give recommended values of component data for reliability
studies. The values were based on data from several industries in Eastern Germany, as
well as from the public supply. For busbars they give a relation between the failure rate
of the circuit-breakers, AC.b.' and the failure rate of the busbar, Abusbar:
open busbars:
Abusbar = 0.1 * A
c
.
b
. * # c.b.
closed, air isolated busbars:
Abusbar = 0.05 * A
c
.
b
. * # c.b.
closed, solid isolated busbars:
Abusbar = 0.01 * A
c
.
b
. * # c.b.
Where # c.b. is the number of circuit breakers connected to the bus.
10.1,2. The IEEE gold book IIEEE,19911 recommends for switchgear buses (indoor and
outdoor):
insulated switchgear with rated voltages between 600 and 15,000 volts
ETTF = 885 yrs; repair time = 28 - 261 hours;
bare switchgear with rated voltages below 600 volts
ETTF = 1250 yrs; repair time = 27 - 550 hours;
bare switchgear with rated voltages above 600 volts
ETTF = 521 yrs; repair time = 17.3 - 36 hours.
All these values are for one "unit". The number of units is the number of connected
circuit breakers and connected switches.
The gold book recommends for bus ducts:
ETTF = 2450 years; repair time = 9.5 - 128 hours.
The unit is 1 circuit meter.
-120- Busbars
10.2. Data from surveys
10.2.1. The 1972 IEEE sponsored survey [lEEE,1974] resulted in the following values
for switchgear busses: (the unit was the number of compartements).
All switchgear busses
insulated 600 - 15,000 Volt
bare 0 - 600 Volt
bare 600 - 15,000 Volt
: ETTF = 1 500 year
: ETTF = 600 year
: ETTF = 3000 year
: ETTF = 1 600 year
; c.i. = [1000,2300]
; c.i. = [400,1300]
; c.i. = [1500,12000]
; c.i. = [900,5000)
The survey resulted in the following values for bus ducts (1 unit = 1 circuit meter):
ETTF = 2500 years; c.i. = [1500,5500)
10.2.2. O'Donnell [1979) presents the results of an IEEE survey after switchgear bus
reliability of industrial plants and commercial buildings, performed in 1977. This survey
was held because a major controversy emerged in the results of the 1972 survey [IEEE,
1974). Insulated bus showed a higher failure rate than bare bus, but data were heavily
influenced by chemical industry. The new survey shows the opposite of this, with less
chemical industry influence. The main results are given below:
All buses : ETTF = 950 years ; c.i. = <750, 1300>
Insulated buses
above 600 V : ETTF = 890 years ; c.i.
=
<650, 1450>
Bare buses
all : ETTF = 1 000 years ; c.L
=
<700, 1700>
below 600 V : ETTF = 1250 years ; c.L
=
<850,2350>
above 600 V : ETTF = 500 years ; c.L
=
<300,1800>
The number of units is the number of switchgear connected circuit breakers and
connected switches.
The following data have been found for the repair time:
Insulated busses
repair "round clock" average repair time
median repair time
repair "normal hour" average repair time
median repair time
Bare busses
repair "round clock" average repair time
median repair time
repair "normal hour" average repair time
median repair time
-121-
: 87 hours
: 24 hours
: 430 hours
: 240 hours
: 39 hours
: 32 hours
: 154 hours
: 24 hours
Busbars
10.2.3. The PNEM survey [van Amelsfoort et al.,1986) resulted for busbars (the authors
refer to substations") in:
ETTF = 1800 years, c.i. = [1200,3200).
10.2.4. Pijls [1988] finds from the failure data of an industrial power system collected
during 8 years, for 10 kV busbar systems.
ETTF = 90 years, c.i. <40, ..... >
Most busbars in the system being studied consist of three rails.
10.2.5. Wahlstrom et al. [1988] describe the experience with new 84 kV-420 kV GIS
in Sweden, between 1974 and 1986. By observing a population of 27 GIS with a total
number of 102 bays they find:
ETTF = 40 years
The repair time is between 2 and 4 days.
This low value is due to the problems in manufacturing, installation and maintenance of
this new type of switchgear. This value is therefore not representive for GIS switchgear.
10.2.6. Bovy et al. [1991] analysed the outage occurances in the 10 kV networks of a
Dutch utility for a timeperiod of 6 years. For one section of a 10kV busbar they find:
ETTF = 10.000 years
repair time = 3.2 hours
ETTF = (phase-to-earth faults) = 5000 years
probability of mUltiple fault following phase-to-earth fault: 41 %
10.2.7. Verplanke [1991] studied failures that occured in the power system of a
chemical industry in The Netherlands between 1970 and 1991. He gives the following
data:
Busbars 50 kV and 11 kV
ETTF = 125 years; c.i. <75,300>
-122- Busbars
10.3. Data used in reliability studies
10.3.1. Snaith [1977) uses the following values for the electricity supply of a nuclear
power station:
3.3 kV busbar, per outer section
ETIF = 200 years;
maintenance interval = 1 year;
repair time = 24 hours.
415 Volt busbar, per outer section
ETIF = 200 years;
maintenance interval = 0.5 years;
repair time = 2 hours.
10.3.2. Bocker and Kaufmann (1977) use the following values for the 10 kVequipment
in a system substation 10/0.4 kV in a public distribution network.
ETIF = 300 years; repair time = 26 hours.
10.3.3. Allan et al. [1977) use the following values for 11 kV busbars in the electrical
auxiliary systems of power stations:
ETIF = 200 years;
repair time = 10 hours;
time to maintenance = 1 year;
duration of maintenance = 20 hours.
10.3.4. Allan et al. [1980) use, in a reliability study of electrical auxiliary systems of a
power station, the busbar reliability data shown in Table 71.
ETTF repair time time to I duration of
maintenance
(vr) (h) (vr) (h)
11 tv 220 120 2 8
3.3. tv 220 48 2 8
415 V 220 24 2 4
Table 71.' Busbar data used by Allan et al. [1980J.
10.3.5. Adams and Jasmob [1981) use the following values for busbars in a distribution
system:
ETIF = 42 years; repair time = 3 hours.
10.3.6. Nelson and Johnson [1982) compare three distribution voltages for the power
supply to a gas centrifuge uranium enrichment plant. They use the following reliability
data (based on 1974 IEEE survey and other available datal for one section of a bus:
13.8 kV : ETIF = 1580 years;
24.9 kV : ETIF = 1580 years;
-123- Busbars
34.5 kV : ETTF = 1580 years.
For the bus duct between the power transformer and the switchgear they use:
13.8 kV : ETTF = 100 years;
24.9 kV : ETTF = 100 years;
34.5 kV : ETTF = 100 years.
10.3.7. Ruoff and van Meeteren [1983] use a value of ETTF = 1000 years for busbar
faults in distribution systems.
10.3.8. William and Mudge [1983] use a value of ETTF = 5000 year, with a repair time
of 60 hours, for an 11 kV busbar. These values have been drawn from distribution
system statistics.
10.3.9. Koval [1983] uses the following values for secondary busses in an industrial
power system:
ETTF = 500 years;
replacement ime = 10 hours;
restoration time = 4.0 hours.
10.3.10. Dialynas and Allan [1987] describe a reliability model for a power distribution
network with local generation. For busbars they use:
ETTF = 1000 years;
repair time = 50 hours.
10.3.11 . Dialynas [1988] uses a value of ETTF = 45 years for 1 km of busbar (i.e ETTF
= 45,000 year for 1 meter of busbar).
10.3.12. Whiting [1989] determines the reliability of power supplies to broadcast
transmitting stations. Component data are taken from various sources. He uses the
following data:
11 kV bus bars
ETTF = 200 years
repair time = 120 hours
415 V bus bars
ETTF = 500 years
repair time = 24 hours
10.3.13. Duke et al. [1989] assess the reliability of an industrial distribution system. For
an 11 kV bus they use the following data:
ETTF = 750 years; repair time = 214 hours.
10.3.14. Allan and Inga-Rojas [1990] describe a method for distribution system
reliability. In an example they use for busbars:
-124- Busbars
ETTF = 200 years.
10.3.15. Sallam et al. [1990] calculate, as an example, reliability indices for the MV-
network of Port Fouad, Egypt. They use the following data.
Switchgear bus, connected to 2 circuit breakers
ETTF = 150 years
repair time = 26,8 hours
Switchgear bus, connected to 4 circuit breakers
ETTF = 75 years
repair time = 26.8 hours
10.3.16. Mohan Rao and Sekhar [1990] compare the relaibility of a number of
distribution systems.
They use the following data:
Switchgear bus, 480 V, bare, connected to 7 breakers
ETTF = 420 years
repair time = 24 hours
Switchgear bus, 13.8 kV, insulated, connected to 1 breaker
ETTF = 300 years
repair time = 26.8 hours
10.3.17. Allan at al [1991] present a reliability test system for distribution networks. For
bus bars they use the data given in Table 72.
permanent active ten.,orary
fai lures fai lures fai lures
33 kV 1000_yrs 1000 vrs 100 vrs
11 kV 1000 yr. 1000 yrs 100 yrs
Table 72: Busbar data used by Allan et al. [T99T}.
10.3.18. Dialynas and Koskolos [1991] use a value of ETTF = 45 years for permanent
failures on busbars. The repair time is 19.0 hours. Maintenance is performed every two
years during 4.0 hours. The busbars in the system under study are operated at voltages
of 150 kV, 20 kV, 6.6 kV and 380 V.
10.3.19. Prescott et al. [1991] use a value of ETTF = 200 years for the failure of an
HV distribution switchboard, with and average repair time of 120 hours. For the LV
distribution switchboard they use ETTF = 330 years and an average repair time of 24
hours.
10.3.20. Dortolino et al. [1991] use in a substation reliability avaluation study a value
of ETTF = 100 years for busbars, with a repair time of 24 hours. Maintenance is
performed once every 3 years during 8 hours.
-125- Busbars
10.4. Ageing data
10.4.1. Bar et al. [1990] use a Delphi method is determine the position of the knee in
the bath-tub curve, i.e. the age where the wear-out phase-starts to become important.
For the busbar in a low-voltage substation they find, in case of
good circumstances : 53 years;
average circumstances : 49 years;
bad circumstances : 29 years.
For a low-voltage busbar in an MV/LV-substation they find, in case of
good circumstances : 43 years;
average circumstances : 37 years;
bad circumstances : 25 years;
For a closed busbar in and MV substation they find, in case of
good circumstances : 26 years;
average circumstances : 26 years;
For an open bus bar in an MV-substation they find, in case of
good circumstances : 14 years;
average circumstances : 14 years;
-126- Busbars
10.5. Conclusions
The failure rate of a busbar is dependent on the number of sections connected to the
busbar, as well as on the actual length of the bus duct. Some authors therefore give a
failure rate per section. The 1972 IEEE survey [IEEE, 1974] also gives a failure rate per
meter. Unfortunately not authors refer their data to the dimensions of the bus, making
a comparison with others difficult.
The results for busbars are summarized in Table 73 and Table 74. From this survey a
value between 500 and 2000 years for the ETTF of one section might be concluded. The
influence of failures per meter of bus duct appears to be neglectable.
Most reliability studies use a value of some hundreds of years for the whole busbar. This
is consistent with the results from surveys.
Section Reference ETTF cer Remarks
section meter busbar
10.1.2 IEEE 1991 1250 < 600 Volt- bare
885 600-15 000 Volt" insulated
521 > 600 Volt- bare
2450 All types
10.2.1 IEEE 1974 3000 < 600 Volt- bare
600 600-15 000 Volt" insulated
1600 600-15 000 Volt bare
2500 All types
10.2.2 O'Donnell 1979 1250 < 600 Volt- bare
890 > 600 Volt- insuLated
500 > 600 Volt- bare
10.2.3 van Amelsfoort et at. 1986 1800
10.2.4 Pi jls 1988 90
10.2.6 Bovy et al. 1991 10 000
10.2.7 Verplanke 1991 125
Table 73. Summary of busbar lifetimes: recommended values and data from surveys.
-127- Busbars
Section Reference ETTF ""r Remarks
section meter busbar
10.3.1 snatth 1977 200
10.3.2 BOeker and Kaufmam 1977 300
10.3.3 A.lIan et at. 1977 200
10.3.4 Allan et at. 1980 220
10.3.5 Adams and Jasmb 1981 42
10.3.6 He 1 son ard Johnson 1982 1580
10.3.7 Ruoff and van Meeteren, 1000
1983
10.3.8 Will i ams and Muclge 1983 5000
10.3.9 Koval 1983 500
10.3.10 Dialynas and Allan 1987 1000
10.3.11 Diahnas 1988 45 000
10.3.12 WhithiM. 1989 200 11 tv
500 415 Volt
10.3.13 Duke et at. 1989 750
10.3.14 Allan and InRa-Ro"ss 1990 200
10.3.15 Sallam et al. 1990 300
10.3.16 Mohan Rao and Sekhar 1990 3000 480 Volt
300 13.8 tv
10.3.17 Allan et al. 1991 1000
10.3.1S Dialvnas and Koskolos 1991 15
10.3.19 Prescott et al. 1991 200 HV
330 LV
10.3.20 Dortolino et at. 1991 100
Table 74: Summary of busbar life times: data used in reliability studies.
-128- Busbars
11. LARGE MOTORS
11 .1. Recommended values
11.1.1. Green and Bourne [1972) give average component failure-rates for electrical
components. For motors they give;
Motors in general
induction motors above 200 kW
below, 200 kW
synchronous motors
small, general motors
stepper motors
: ETTF = 11 years
: ETTF = 11 years
: ETTF = 23 years
: ETTF = 16 years
: ETTF = 29 years
: ETTF = 23 years
11.1.2. IEEE standard 500 [lEEE,1983) gives reliability data for components of
nuclear-power stations. The data has been derived by a Delphi-method combined with
the results form several surveys and databases. For motors the following values are
recommended (catastrophic failures only)
Induction squirrel cage, 150 kW and smaller
Fails to run once started : ETTF = 105 years
Fails to start : ETTF = 98 years
Induction squirrel cage, above 150 kW
Fails to run once started : ETTF = 185 years
Fails to start : ETTF = 185 years
Wound rotor induction
Fails to run once started
Fails to start
Single phase induction
Fails to once started
Fails to start
000>
Synchronous single phase
Fails to run once started
Fails to start
: ETTF = 120 years
: ETTF = 60 years
: ETTF = 175 years
: ETTF = 40,000 years
: ETTF = 165 years
: ETTF = 200 years
; range = < 150, 1000 >
; range = <50, 1000>
; range = < 30, 350 >
; range <45, 500>
; range = < 35,475 >
; range = < 30, 400 >
; range = < 50, 4000 >
; range = < 15 000,250 -
; range = < 135, 200>
; range = < 170, 260>
11.1.3. Kloeppel et al. [1990) give recommended values of component data for
reliability studies. The values were based on data from several industries in Eastern
Germany, as well as from the public supply. For motors they recommend the
following values:
below 1 kV
6 kV
: ETTF = 23 years
: repair time = 6 hours
: ETTF = 12 years
: repair time = 20 hours
; range = <14,50>
; range = <1,10>
; range = <3,65>
; range = < 10, 50 >
-129- Large motors.
11.2. Data from surveys
11.2.1. Dickinson [19621 gives the results of an AlEE survey held in 1959 after the
reliability of electrical equipment in industrial plants. For electric motors the results
are presented below.
Synchronous motors.
180 kW and larger: ETTF = 15 year ; c.i. = <10,20>
Induction motors.
180 kW and larger : ETTF = 9.2 year ; c.i. = <8, 11>
150 kW and below: ETTF = 19.5 year; c.i. = <19,20>
The repair times reported are:
synchronous motors : 209 hours
large induction motors : 162 hours
small induction motors : 41 hours
11.2.2. A 1981 survey [lEEE,19821 in the electric utility industry reported, for motors
750 kW and up and not over 15 years of age, for insulation-related failures:
ETTF = 30 years; c.i. = < 25, 40>
11.2.3. O'Donell et al. [1983,19841 performed a survey after the reliability of motors
of rated power 200 hp (150 kW) and higher. The population under study consisted of
1141 motors in 75 plants of 33 compagnies. A total of 360 failures occured in 5085
unit years i.e.
ETTF = 14years,c.i. = <12,16yr>.
A subdivision to type of motor is given in Table 75. DC motors appear to be somew-
hat more reliable than AC motors, but the difference is not significant.
ETTF c. i.
" DOD
induction motors: 14 yr. <12, 16 yr.>
79"
synchronous motors: 13 yr. <9, 19 yr.>
10 "
"wollld rotor" 19 yr. <13, 34 yr.>
8"
D.C. Motors 2S yr. <14 140 yr.>
3 "
Table 75: Subdivision to type of motor.
Table 76 gives a subdivision to rated voltage. The rated voltage has no influence on
the reliability of a motor.
ETJF c. i.
" pop
0-1 kV 13 yr. <10, 16 yr.>
27 "
1-5 kV 15 yr. <13, 17 yr.>
70"
5-15 kV 16 yr. <9 50 yr.>
3"
Table 76: Subdivision to rated voltage_
Table 77 gives a subdivision to rated power. High-power motors appear to be less
reliable than low-power motors.
-130- Large motors.
ETTF c. i.
150-375 kW 15 yr <13. 17 yr.>
375-3750 kW 14 yr <11. 17 yr>
3750-7500 kW 5 yr <3 12 yr>
Table 77: Subdivision to rated power_
Table 78 gives a subdivision to motor speed_ The higher the speed of the motor, the
higher its reliability_
ETTF c. i .
0-720 RPM 10 yr <8. 13 yr.>
721-1800 RPM 14 yr <12. 16 yr>
1801-3600 RPM 19 yr <15 26 Yr>
Table 78: Subdivision to motor speed.
The repair time found from this survey is:
97.7 hours in case of repair during normal working hours,
81.4 hours in case of repair round the clock,
18.2 hours in case of replacement by a spare motor.
11.2.4. Albrecht et a!. [1987] describe a survey after the reliability of large motors in
power stations. The survey was limited to generating units above 150 MW, low-
voltage motors above 75 kW and all medium-voltage motors, generator units that
went into service between January 1969 and December 1979.
The report covers information on 5797 motors in service at 132 generating units
owned by 56 utilities. From the total population they find:
ETTF = 29.4 years; c.i. = < 28,31 >
There is a large spread in
reliability among different
units, utilities and manufac-
tures. Figure 22 shows the
distribution of estimated
failure rate by unit. A statis-
tical analysis by the authors
shows that there is little
spread among units of one
utility. This leads them to
the conclusion that "a ma-
jor factor in the reliability of
the motors is a function of
who is using them".
40
FREOUENCY 30
(UNITS)
20
10
2
6 8 10 >10
ESTIMATED fAILURE RATE, ./. YEAR
Figure 22. Distribution of estimated failure per unit,
according to Albrecht et a!. [1987J.
-131-
Large motors_
Also among different manufacturers there is a large spread in reliability:
Manufacturer 1 : ETTF = 39 years ; c.i.
=
<34,45>
Manufacturer 2 : ETTF = 33 years ; c.L
=
<28,38>
Manufacturer 3 : ETTF = 22 years ; c.i.
=
<19,25>
Manufacturer 4 : ETTF = 42 years ; c.L
=
<33,57>
Manufacturer 5 : ETTF = 32 years ; c.i.
=
<32, 54>
Manufacturer 6 : ETTF = 6 years ; c.L
=
<5,8>
Manufacturer 7 : ETTF = 120 years ; sample too small
Manufacturer 8 : ETTF = 19 years ; c.i. = <28,31 >
None of them shows a confidence interval overlapping the overall confidence interval
<28,31 >.
A subdivision to failure mode yields for this survey:
bearing related
stator related
rotor related
: 41 %
: 37 %
: 10 %
11.2.5. Franke [1990] observed, during 12 years, failures in a chemical plant in
Eastern Germany. Early failures in the wear-in phase (1.5 ... 2 years) have been
removed from the data. He present the following data:
6 kV motors
motors < 1000 V
: ETTF = 14 years; c.i. = <10,25>
: ETTF = 17 years ; c.i. = < 12,25>
-132- Large motors.
11.3. Data used in reliability studies
11.3.1. Snaith [1977) uses the following value for the electricity supply of a nuclear
power station:
probability of failure to start of 415 V motor: 0.1 %.
11.3.2. Allan et al. [1980) use the following data in a reliability study of electrical
auxiliary systems of a power station:
11 kV motors
3.3 kV motors
415 V motors
: ETIF = 75 years
: ETIF = 100 years
: ETIF = 250 years
-133- Large motors.
11,4. Ageing data
No ageing data on large motors has been found.
-134- Large motors.
11.5. Conclusions
Table 79 summarizes the available data on large motors. From the surveys follows an
ETTF value between 15 and 30 years.
Section Reference ETTF
11.1.1 Green and Bourne 19n 11-29
11.1.2 IEEE 1983 40-175
11.1.3 Kloeppel et ale 1990 12-23
11.2 _1 Dickinson 1962 9.2-19.5
11.2.2 IEEE 1982 30
11.2.3 O'DonneL l 1983 1984 14
11.2.4 Albrecht et ale 1987 30
11.2.5 frenke 1990 14-\7
11.3.2 Allan et ale 1980 75-200
Table 79. Summary of motor life times.
-135- large motors.
12. References
Adams, R.N. and G.B. Jasman
TOPOLOGICAL ASPECTS OF DISTRIBUTION SYSTEM RELIABILITY.
In: Proc. of the 7th Power Systems Computation Conf (PSCC), Lausanne, 12 - 17 July
1981. Ed. by M.A. Laughton.
Guildford, UK: Westbury, 1981. P.256-260.
Albrecht, P. and J.C. Appiarius, E.P. Cornell, DW. Houghtaling, R.M. McCoy, E.l,
Owen, D.K. Sharma
ASSESSMENT OF THE RELIABILITY OF MOTORS IN UTILITY APPLICATIONS.
IEEE Transactions on Energy Conversion, Vol. 2 (1987), p.396-402.
Allan, R.N.
EFFECTS OF PROTECTION SYSTEM OPERATION AND FAILURES IN COMPOSITE
SYSTEM RELIABILITY EVALUATION.
Electric Power and Energy Systems, Vol. 10 (1988), p.180-189.
Allan, R.N. and A.N. Adraktas
TERMINAL EFFECTS AND PROTECTION SYSTEM FAILURES IN COMPOSITE SYSTEM
RELIABILITY EVALUATION.
IEEE Transactions on Power Apparatus and Systems, Vol. 101 (1982), p.4557-4562.
Allan, R.N. and R. Billinton, I. Sjarief, l, Gael, K.S. So
A RELIABILITY TEST SYSTEM FOR EDUCATIONAL PURPOSES - BASIC DISTRIBUTION
SYSTEM DATA AND RESULTS.
IEEE Transactions on Power Systems, Vol. 6 (1991). p.813-820.
Allan, R.N. and M.F. de Oliveira, J.A. Chambers, R. Billinton
RELIABILITY EFFECTS OF THE ELECTRICAL AUXILIARY SYSTEMS IN POWER
STATIONS.
In: Reliability of Power Supply Systems, London, 21 - 23 February 1977. Ed. by M.N.
Eggleton et al"
London: Institution of Electrical Engineers, 1977. P.1-6.
lEE Conf. Publication no. 148.
Allan, R.N. and M.F. de Oliveira, A. Kozlowski, G.T. Williams
EVALUATION THE RELIABILITY OF ELECTRICAL AUXILIARY SYSTEMS IN MULTI-UNIT
GENERATION STATIONS.
Proceedings lEE, Part C, Vol.127 (1980). p. 65-71.
Allan, R.N. and E.N. Dialynas, I.R. Horner
MODELLING AND EVALUATING THE RELIABILITY OF DISTRIBUTION SYSTEMS.
IEEE Transactions on Power Apparatus and Systems, Vol. 98 (1979), p.2181-2189.
Allan, R.N. and T.O. Inga-Rojas
TIME SEQUENTIAL RELIABILITY ASSESMENT OF ELECTRICAL AUXILIARY SYSTEMS.
In: Advances in Reliability Technology Symposium, Liverpool, U.K., 18 - 20 April 1990.
London: Elsevier, 1990. P. 183-198.
-136- References
Anderson, B.G. and J.C. Declerq, P. van Miegroet, H. Rohsler, H.G. Schutte
THE RELIABILITY OF HV SUBSTATIONS WITH SPECIAL REGARD TO THE SECONDARY
EQUIPMENT.
Electra (CIGRE), no. 111 (1987), p. 17-23.
Aquilino, J.W.
REPORT OF TRANSFORMER RELIABILITY SURVEY - INDUSTRIAL PLANTS AND
COMMERCIAL BUILDINGS.
In: Industrial and Commercial Power Systems Technical Conference, 12 - 15 May 1980,
Houston, Texas. Ed. by. B.Bridger et al..
New York: IEEE, 1980. P. 31-39.
Aquilino, J.W.
REPORT OF TRANSFORMER RELIABILITY SURVEY - INDUSTRIAL PLANTS AND
COMMERCIAL BUILDINGS.
IEEE Transactions on Industry Applications, Vol. 19 (1983), p.858-866.
Bakker, G.W.
BETROUWBAARHEIDS-ANAL YSE NOODSTROOMINSTALLATIES (Reliability analYSis of
emergency power installations; in Dutch).
Faculty of Electrical Engineering, Delft University of Technology, 1989.
Student report of practical work.
Bar, J.W.H. and H.l. Doppen, H. Juckers, H.M.A. Konings, P. Wiersma, H. Zuijderduin,
M.J. Voeten
ONDERHOUDSANAL YSE (Maintenance analysis; in Dutch).
Arnhem, The Netherlands: VEEN, Commissie distributievraagstukken 1990.
Billinton, R.
DISPERSION ANALYSIS IN DISTRIBUTION SYSTEM RELIABILITY EVALUATION.
In: Proc. of the 9th Power Systems Computation Conf. (PSCC), Cascais, Portugal, 30
August - 4 September 1987. Ed. by H. Glavitsch.
London: Butterworths, 1987. P.147-153.
Billinton, R. and R.N. Allan
RELIABILITY EVALUATION OF POWER SYSTEMS.
Boston: Pitman, 1984.
Billinton, R. and K. Debnath
GENERATING UNIT MODELING IN POWER SYSTEM ADEQUACY ANALYSIS.
Reliability Engineering and System Safety, Vol. 27 (1990), p. 155-165.
Billinton, R. and R. Goel
AN ANALYTICAL APPROACH TO EVALUATE PROBABILITY DISTRIBUTIONS
ASSOCIATED WITH THE RELIABILITY INDICES OF ELECTRIC DISTRIBUTION SYSTEMS.
IEEE Transactions on Power Delivery, Vol. 1 (1986), no. 3, p.245-251.
-137- References
Blechschmidt, H. et al.
INTERNATIONAL CABLE FAULT STATISTICS ON SYTHETICALLY INSULATED MV-
CABLES.
In: Int. Conf. on Electricity Distribution (CIRED). Brighton, U.K . 8 - 12 May 1989. Ed.
by. H. Lhussier et al ..
London: Institution of Electrical Engineers. 1989. P. 200-206.
lEE Conf. Publication no. 305.
Blechschmidt, H.H. and H. Klockhaus, L. Litters, H.D. Reus
FAILURE OF LDPE-/XLPE-INSULATED MEDIUM VOLTAGE CABLES IN THE FEDERAL
REPUBLIC OF GERMANY.
In: Int. Conf. on Electricity Distribution (CIRED), Liege, Belgium, May 1991.
Liege, Belgium: A.I.M . 1991. Paper 3.8, p.1-8.
Boeker, H. and W. Kaufmann
OPTIMIZING THE EXPENDITURE ON RELIABILITY OF SUPPLY IN SYSTEM PLANNING
FOR THE BENEFIT OF THE CONSUMER.
In: Reliability of Power Supply Systems. London. 21 -23 February 1977. Ed. by M.N.
Eggleton et al ..
London: Institution of Electrical Engineers, 1977. P.1-6.
lEE Conf. Publication no. 148.
Bovy, A. and K.W. Edwin, W.R. Nick, A.H. Schweer
PLANNING DISTRIBUTION NETWORK REDUNDANCY USING RELIABILITY METHODS.
In: Electric Power Systems Reliability Symp., Montreal, Canada, 16 - 18 September
1991.
Paris: CIGRE, 1991. Paper 1 B-5, p.1-6.
Braun, W.F.
RELIABILITY STUDY OF CABLE TERMINATIONS AND SPLICES BY ELECTRIC UTILITIES
IN THE NORTHWEST.
In: Industrial and commercial power systems Technical Conf . Cleveland. Ohio. 5 - 8 May
1986. Ed. by C.E. Becker et al ..
New York: IEEE. 1986. P. 75-85.
Braun, W.F.
RELIABILITY STUDY OF CABLE TERMINATIONS AND SPLICES BY ELECTRIC UTILITIES
IN THE NORTHWEST.
IEEE Transactions on Industry Applications, Vol. 23 (1987), p.144-153.
Brown H.W. and N.J. Gardner
RELIABILITY AND AVAILABILITY ASSESSMENTS OF SELECTED DOMESTIC COMBINED-
CYCLE POWER GENERATING PLANTS.
Palo Alto, CA: Electric Power Research Institute (EPRI), August 1982.
EPRI Report AP-2536
-138- References
Brzozowska-Theil, und G. Theil
VERBESSERING DER SCHAL TUNG VON MITTELSPANNUNGSVERTEILUNGSNETZEN MIT
BEROCKSICHTIGUNG DER ZUVERLASSIGKEIT (Improvement of switching of medium
voltage distribution networks, taking into account the reliability; in German).
Elektrotechnik und Informationstechniek, Vol. 105 (1988), no. 7/8, p.318-326.
Bruggeman, G. and J.E. Daalder, R. Heinemeyer, R.W. Blower
MV/LV DISTRIBUTION TRANSFORMER FAULT PROTECTION.
In: Int. Conf. on Electricity Distribution (CIREDI. May 1991, Liege, Belgium.
Liege, Belgium: A.I.M., 1991. Paper 1.14, p.1-6.
Bunch, J.B. and H.1. Stalder, J.T. Tengdin
RELIABILITY CONSIDERATIONS FOR DISTRIBUTION AUTOMATION EQUIPMENT.
IEEE Transactions on Power Apparatus and Systems, Vol. 102 (1983), p.2656-2664.
Canadian Electrical Association (CEA)
FORCED OUTAGE PERFORMENCE OF TRANSMISSION EQUIPMENT FOR THE PERIOD
JANUARY 1,1984 TO DECEMBER 31,1988.
Montreal: Canadian Electrical Association, 1990.
Capra, R.L. and M.W. Gangel, S.V. Lyon
UNDERGROUND DISTRIBUTION SYSTEM DESIGN FOR RELIABILITY.
IEEE Transactions on Power Apparatus and Systems, Vol. 88 (1969), p.834-842.
Chan, F.C.
PERFORMANCE ASSESSMENT AND CONTROL OF POWER SYSTEM RELAYING.
IEEE Transactions on Power Delivery, Vol. 4 (1988), p. 986-994
Chang, N.E.
EVALUATE DISTRIBUTION SYSTEM DESIGN BY COST RELIABILITY INDICES.
IEEE Transactions on Power Apparatus and Systems, Vol. 96 (1977), p.1480-1490.
CIGRE working group 12.05. (CIGRE, 1983)
AN INTERNATIONAL SURVEY ON FAILURES IN LARGE POWER TRANSFORMERS IN
SERVICE.
Electra (CIGRE), nr. 88 (May 1983), p. 21-42.
CIGRE Working Group 23.07. (CIGRE, 1989)
INSTRUMENT TRANSFORMER TECHNOLOGY AND SERVICE BEHAVIOUR FAILURE
SURVEY.
Electra (CIGRE), nr. 125 (July 1989), p.113-117.
CIGRE Working Group 13.06. (CIGRE, 1991)
HIGH VOLTAGE CIRCUIT BREAKER RELIABILITY DATA FOR USE IN SYSTEM
RELIABILITY SURVEYS.
In: Electric Power Systems Reliability Symp., Montreal, Canada, 16 - 18 September
1991.
Paris: CIGRE, 1991. Paper 2-01, p.1-6.
-139- References
Connor, R.A.W. and R.A. Parkins
OPERATIONAL STATISTICS IN THE MANAGEMENT OF LARGE DISTRIBUTION
SYSTEMS.
Proceedings lEE, Vol. 113 (1966), p.1823-1834.
Declerq, J.C. and P. van Miegroet, H. Roshsler, H.G. Schutte.
SUBSTATION RELIABILITY-COMPARISON OF TWO METHODS AND SUITABLE
PRESENTATION OF RESULTS.
Electra (CIGRE), no. 99 (1985), p. 31-46.
Dedman, J.C. and H.L. Bowles
A SURVEY OF URD CABLE INSTALLED ON RURAL ELECTRIC SYSTEMS AND FAILURES
OF THAT CABLE.
In: Rural Electric Power Conference, 29 April - 1 May 1990, Orlando, Florida. (Ed. by
C.A. Blackmon et al.)
New York: IEEE, 1990. Paper 02, p.1-7.
Dialynas, E.N.
MODELLING THE OPERATION AND VOLTAGE CONTROL EQUIPMENT IN THE
RELIABILITY EVALUATION OF POWER DISTRIBUTION SYSTEMS.
Archiv fur Elektrotechnik, Vol. 71 (1988). p.369-380.
Dialynas, E.N. and R.N. Allan
LOCAL GENERATION FACILITIES IN THE RELIABILITY EVALUATION OF POWER
DISTRIBUTION SYSTEMS.
IEEE Transactions on Power Systems, Vol. 1 (1986), no. 4, p.62-67.
Dialynas, E.N. and R.N. Allan
RELIABILITY MODELLING AND EVALUATION TECHNOLOGY FOR POWER
DISTRIBUTION NETWORKS WITH LOCAL GENERATION.
Proceedings lEE, Part C, Vol. 134 (1987), p. 348-356.
Dialynas, E.N. and M.P. Padadopoulos
RELIABILITY ASSESSMENT STUDIES IN DISTRIBUTION NETWORK OPERATION AND
PLANNING.
In: Int. Conf on Electricity Distribution (CIRED), London, 8 - 12 May 1989. Ed. by H.
Lhussier et al ..
London: Institution of Electrical Engineers, 1989. P.568-572.
lEE Conference Publication no. 305.
Dialynas, E.N. and N.C. Koskolos
EVALUATING THE RELIABILITY PERFORMANCE OF INDUSTRIAL POWER SYSTEMS
WITH STANDBY AND EMERGENCY GENERATING FACILITIES.
Electric Power Systems Research, Vol. 20 (1991), p. 143-155.
Dickinson, W.H.
ECONOMIC EVALUATION OF INDUSTRIAL POWER-SYSTEM RELIABILITY
AlEE Transaction Pt II, Vol. 76 (1957), p. 264-272.
-140- References
Dickinson, W.H.
EVALUATION OF ALTERNATIVE POWER DISTRIBUTION SYSTEMS FOR REFINERY
PROCESS UNITS.
AlEE Transactions on Power Apparatus and Systems, Vol. 179 (1960), p.1 10-124.
Dickinson, W.H.
REPORT ON RELIABILITY OF ELECTRICAL EQUIPMENT IN INDUSTRIAL PLANTS.
AlEE Transactions Pt. II, Vol. 81 (1962), p. 138-151.
Dopazo, J.F. and D.E. Tuite, E.L. Stein, H.M. Merrill
OBJECTIVE CRITERIA FOR POWER PLANT MAINTENANCE SCHEDULING.
In: Reliability of Power Apparatus and Systems, 23 - 24 September 1976, Montreal. Ed.
by M.F. Hashmi.
Piscateway, NJ: IEEE, 1976. P.97-107.
Dortolina, C.A. and J.J. Porta, R. Nadira
AN APPROACH FOR EXPLICITEL Y MODELING THE PROTECTIVE RELAYING SYSTEM
IN SUBSTATION RELIABILITY EVALUATION STUDIES.
IEEE Transactions on Power Systems, Vol. 6. (19911. p. 1373-1379.
Duckett, D.A. and C.M. Mc. Donough
A GUIDE FOR TRANSFORMER REPLACEMENT BASED ON RELIABILITY AND
ECONOMICS.
In: Rural Electric Power Conference, 29 April - 1 May 1990, Orlando, Florida. Ed. by
C.A. Blackmon et al ..
New York: IEEE, 1990. Paper C4, p. 1 -7.
Duke, A.J. and J.T. Maguire, J. Flaherty
RELIABILITY ASSESSMENT OF AN ELECTRICAL POWER DISTRIBUTION SYSTEM.
In: Reliability '89 Proceedings, Brighton, UK, 14 - 16 June 1989.
Warrington, UK: UKAEA, 1989. Paper 3c/3, p. 1 -16, Vol. 1.
Farmer, W.S.
AGING RESEARCH IMPACT ON COMPONENT AND SYSTEM RELIABILITY AND
MAINTENANCE IN NUCLEAR POWER PLANTS.
In: Int. Conf. on Operability of Nuclear Systems in Normal and Advance Environment
(OPERA). Lyon, France, 18 - 22 September 1989.
Paris: Soc. Fracaise d'Energie Nucl., 1989. Paper 58, p.1-8.
Ferran, J. and M. Boudaillier, J. Jacquenet
DISTRIBUTION CABLE PRACTICES AND DEVELOPMENTS IN ELECTRICITE DE FRANCE.
In: Annual conference ofthe Electricity Supply Engineers Association of N.S.W., Sydney,
August 1986.
Ficek, J. and J. Grolich
BETRIEBSZUVERLASSIGKEIT VON DAMPFTURBINEN (Reliability of steam turbine
operation; in German).
Skoda Review, no. 1 (1989), p.22-25.
-141- References
Filter, R. and A.S. Jones
SEPARABLE CONNECTOR SWITCHING PERFORMANCE.
IEEE Transactions on Power Delivery Vol. 5 (1990), p. 435-441.
Fiorina, J.N. and M. Chevalier
A SIMPLE APPROACH TO THE RELIABILITY OP UPS ARCHITECTURES.
In: Power Quality '90 Europe. Official Proc., Paris, 13 - 15 November 1990.
Ventura, CA: Intertec Commun., 1990. P.213-222.
Franke, K.
ZUVERLASSIGKEITSKENNGROBEN FOR INDUSTRIELLEN RELAISSCHUTZ (Reliability
parameters for industrial relay protection; in German).
Energietechnik, Vol. 37 (1987), p.286-288.
Franke, K.
ERMITTLUNG VON ZUVERLASSIGKEITSKENNWERTEN AUSGEWAHLTER
STARKSTROMTECHNISCHER BETRIEBSMITTEL AUS DER STORUNGSST ATISTIK EINES
CHEMIEBETRIEBS (Determination of reliability parameters of selected power engineering
components from the failure statistics of a chemical plant; in German).
Energietechnik, Vol.40 (1990), p.256-259.
Fransen, H.
DE ENKELVOUDIGE RESERVE IN DE ELEKTRICITEITSVOORZIENING VAN EEN
CHEMISCHE INDUSTRIE (The single redundancy in the electric power supply of a
chemical industry; in Dutch).
Elektrotechniek, Vol. 67 (1989), p. 719-722.
Gangel, M.W. and R.J. Ringlee
DISTRIBUTION SYSTEM RELIABILITY PERFORMANCE.
IEEE Transactions on Power Apparatus and Systems, Vol. 87 (1968), p.1657-1665.
Goldberg, S. and W.F. Horton, V. Rose
ANALYSIS OF FEEDER SERVICE RELIABILITY USING COMPONENT FAILURE RATES.
IEEE Transactions on Power Delivery, Vol. 2 (1987), p. 1292-1296.
(Government, 1989)
A STUDY OF LONG-TERM ENERGY PLANNING FOR THE ISLAND OF CURACAO, 1989-
2003.
Curat;:ao, Netherlands Antilles: The Government of the Island of Curat;:ao, 1989.
Governmental report.
Green, A.E. and A.J. Bourne
RELIABILITY TECHNOLOGY.
London: Wiley, 1972.
Grover, M.S. and R. Billinton
A COMPUTERIZED APPROACH TO SUBSTATION AND SWITCHING STATION
RELIABILITY EVALUATION.
IEEE Transactions on Power Apparatus and Systems, Vol. 93 (1974), p. 1488-1497.
-142- References
Guertin, M.B. and Y. Lamarre
RELIABILITY ANALYSIS OF SUBSTATIONS WITH AUTOMATIC MODELLING OF
SWITCHING OPERATIONS
IEEE Transactions on Power Apparatus and Systems, Vol. 94 (1975), p. 1599-1605.
Gusciora, R.H.
BATHTUB CURVES, WEI BULL DISTRIBUTIONS AND RELAY RELIABILITY.
In: Proc. of the 36th Relay Conference. Stillwater. OK. April 1988.
Elkhart, IN: Assoc. Relay Manuf . 1988. Paper 8. p. 1 -7.
Heising. C.R.
RELIABILITY OF MEDIUM-VOLTAGE VACUUM POWER CIRCUIT-BREAKERS.
IEEE Transactions on Reliability. Vol. 32 (1983). p. 3-6.
Heising. C.R.
SUMMARY OF CIGRE 13-06 WORKING GROUP WORLD WIDE RELIABILITY DATA.
MAINTENANCE COSTS DATA AND STUDIES ON THE WORTH OF IMPROVED
RELIABILITY OF HIGH VOLTAGE CIRCUIT BREAKERS.
In: Industrial and Commercial Power Systems Technical Conference. Cleveland. Ohio.
5 - 8 May 1986. Ed. by C.E. becker et al. .
New York: IEEE. P. 93-101.
Heising, C.R. and R.C. Patterson
RELIABILITY EXPECTATION FOR PROTECTIVE RELAYS.
In: Fourth International Conference on Developments in Power System Protection.
Edinburgh U.K . April 1989.
London: Institution of Electrical Engineers. 1989. P. 23-26.
lEE Conference Publication no. 302.
Heiss, W. and A. Schweer
RELIABILITY ANALYSIS FOR PLANNING AND OPERATION OF MEDIUM-VOLTAGE
NETWORKS.
In: Int. Conf. on Electricity Distribution (CIRED). Liege. Belgium. 1991.
Liege, Belgium: A.I.M . 1991. Paper 6.2. p.1-5.
Horton. W.F. and S. Goldberg. V. Backman
THE FAILURE RATES OF UNDERGROUND DISTRIBUTION SYSTEM COMPONENTS.
In: Proc. of the 22nd North American Power Symp . Auburn, AL. 15 - 16 October 1990.
Los Alamitos. CA: IEEE Computing Society. 1990. P.306-316.
Horton. W.F. and S. Goldberg. R.A.Hartwell (1989a)
A COST/BENEFIT ANALYSIS IN FEEDER RELIABILITY STUDIES.
In: Power Quality '89. Official Proc . Long Beach. CA. 15 - 20 October 1989.
Venture. CA: Intertec Commun . 1989. P. 552-558.
Horton. W.F. and S. Goldberg. K. McSweeney (1989b)
ACHIEVING DISTRIBUTION FEEDER RELIABILITY USING BENIFIT/COST RATIO
ANALYSIS.
In: Proc. 21th North-American Power Symp . Rolla. MO, 9 - 10 October 1989.
Washington. DC: IEEE Comput. Soc. 1989. P. 254-261.
-143- References
(IEEE, 1974)
REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS, PART I: RELIABILITY OF
INDUSTRIAL PLANTS.
IEEE Transactions on Industry Applications, Vol. 10 (1974), p.213-235.
IEEE Committee report.
IEEE Power Systems Reliability Subcommitte (A.D. Patton, coordinating author). (IEEE,
1975)
RELIABILITY OF ELECTRIC UTILITY SUPPLIES TO INDUSTRIAL PLANTS.
In: Industrial and Commercial Power Systems Technical Conference, Toronto, Canada,
5 - 8 May 1975. Ed. by B.W. Whittington.
New York: IEEE, 1975. P. 131-133.
(IEEE Working Group) (IEEE, 1977)
IEEE GUIDE TO THE COLLECTION AND PRESENTATION OF ELECTRICAL, ELECTRONIC,
AND SENSING COMPONENT RELIABILITY DATA FOR NUCLEAR POWER GENERATING
STATIONS.
New York: IEEE, 1977.
IEEE Std. 500-1977.
(IEEE Working Group.) (IEEE, 1980)
IEEE RECOMMENDED PRACTICE FOR DESIGN OF RELIABLE INDUSTRIAL AND
COMMERCIAL POWER SYSTEMS (IEEE GOLD BOOK). Ed. by C.R. Heising
New York: IEEE, 1980.
ANSIIIEEE Std. 493-1980.
(IEEE Working Group) (IEEE, 1982)
SUMMARY OF REPLIES TO THE 1982 TECHNICAL QUESTIONAIRE ON ROTATING
MACHINERY (MOTORS 1000 HP AND UP).
Unpublished report cited by [IEEE, 1990). p.72.
(IEEE Working Group) (IEEE, 1983)
IEEE GUIDE TO THE COLLECTION AND PRESENTATION OF ELECTRICAL, ELECTRONIC,
SENSING COMPONENT, AND MECHANICAL EQUIPMENT RELIABILITY DATA FOR
NUCLEAR-POWER GENERATING STATIONS.
New York.: IEEE, 1983.
IEEE Std. 500-1984.
(IEEE Working Group) (IEEE, 1987)
IEEE RECOMMENDED PRACTICE FOR EMERGENCY AND STANDBY POWER SYSTEMS
FOR INDUSTRIAL AND COMMERCIAL APPLICATIONS (IEEE ORANGE BOOK).
New York: IEEE, 1987.
ANSIIIEEE Std. 446-1987.
(IEEE Working Group) (IEEE, 1991)
IEEE RECOMMENDED PRACTICE FOR THE DESIGN OF RELIABLE AND COMMERCIAL
POWER SYSTEMS (IEEE GOLD BOOK). Ed. by C.R. Heising
New York: IEEE, 1991.
IEEE Std. 493-1990.
-144- References
Ishibashi, T. and A. Konemura, M. Sakurai, T. Aiyoshi
RELIABILITY OF VACUUM SWITCHING APPARATUS AND THEIR APPLICATION TO
MINING.
Mining Technology, vol. 72, no. 833 (March 1990), P. 75-79.
Kanai, Y. and T. Tsutsumi, N. Okabe
RELIABILITY OF VACUUM SWITCHING EQUIPMENT.
In: Probabilistic methods applied to electric power systems, London, 3 - 5 July 1991.
London: Institution of Electrical Engineers, Ed. by R.N. Allan et al ..
lEE Conference Proceedings 338. 1991.P.272-277.
Kawamura, T. and M. Horikoshi, S. Kabayashi, K. Hamamoto
PROGRESS OF SUBSTATION MAINTENANCE BASED ON RECORDS OF OPERATION
AND MAINTENANCE.
In: Int. Conf. on Large High Voltage Electric Systems (CIGRE), Paris, 26 August - 1
September 1990.
Paris: CIGRE, 1990. Paper 23-102, p.1-6.
Kevers, J.
DE BETROUWBAARHEID VAN DE ENERGIE VOORZIENING TEN ZUIDEN VAN
EINDHOVEN IN DE HUIDIGE SITUATIE EN IN DE SITUATIE OAT HET 150 KV STATION
VELDHOVEN EN DE NIEUWE 150 KV VERBINDING GEREALISEERD ZIJN (The reliability
of the electric power supply south of Eindhoven in the current situation and in the
situation for which the new 150 kV substation will be in operation; in Dutch).
Den Bosch, The Netherlands: N.V. PNEM, 1987.
Internal report .. PNEM (Electricity supply company)
Kj0l1e, G. and K. Sand
RELRAD - AN ANALYTICAL APPROACH FOR DISTRIBUTION SYSTEM RELIABILITY
ASSESSMENT.
In: IEEE Power Engineering Society Transmission and Distribution Conf., September
1991, Dallas.
New York: IEEE, 1991. P.729-734.
Kloeppel, F.W. und G. Adler, W.W. Sorin, W.W. Tislenko
ZUVERLASSIGKEIT VON ELEKTROENERGIESYSTEMEN (Reliability of electric power
systems; in German).
Leipzig: Deutscher Verlag fUr Grundstoffindustrie, 1990.
Koglin, H.-J. and H.-J. Richter, W.H. Wellsson
COMPOSITE RELIABILITY TECHNIQUES IN EHV SYSTEMS IS THERE A NEED IN CASE
OF HIGHLY MESHED SYSTEMS!
In: Electric Power Systems Reliability Symp., Montreal, Canada, 16 - 18 September
1991.
Paris: CIGRE, 1991. Paper 1 A-02, p.1-6.
-145- References
Koval, D.
IMPACT OF DISTRIBUTION SYSTEM ISOLATION-RESTORATION PROCEDURES ON
INDUSTRIAL CONSUMER RELIABILITY LEVELS.
In: Industrial and Commercial Power Systems Technical Cont., Milwaukee, WI, 9 - 12
May 1983.
New York: IEEE, 1983. P.71-76.
Kula, M. and H. Rohster, V. Vachek
COORDINATION OF SUBSTATION MAIN CIRCUITS AND PROTECTION FORM THE VIEW
POINT OF THEIR RELIABILITY.
In: Electric power systems reliability Symp., Montreal, Canada, 16 - 18 September 1991.
Paris: CIGRE, 1991. Paper 2-03, p.1-6.
Lau, P.C.K. and M.S. Grover, W.H. Tanaka
RELIABILITY ASSESSMENT OF SPECIAL PROTECTION SYSTEMS.
In: Electric power systems reliability Symp., Montreal, Canada, 16 - 18 September 1991.
Paris: CIGRE, 1991. Paper 3A-11, p.1-6.
Lee, N.
HOW RELIABLE IS YOUR UPS?
Australian, Asian and Pacific Electrical World, Vol. 56 (1991), no. 2, p.14-15.
Londsdale, J.G. and G.B. Hitchen
RELIABILITY EVALUATION IN THE PLANNING OF DISTRIBUTION SYSTEMS.
In: Reliability of Power Supply Systems, London, 21 - 23 February 1977. Ed. by M.N.
Eggleton et al..
London: Institution of Electrical Engineers, 1977. P.77-80.
lEE Conf. Publication no. 148.
Magnon, B. and J. L'Henoret, Y. Reyraud
RELIABILITY OF STAND-BY DIESEL GENERATOR SETS IN NUCLEAR PLANTS.
In: Reliability of Power Supply Systems, London, 21 - 23 February 1977. Ed. by M.N.
Eggleton et al..
London: Institution of Electrical Engineers, 1977. P.39-42.
lEE Conf. Publication no. 148.
Mazza, G. and R. Michaca
THE FIRST INTERNATIONAL ENQUIRY ON CIRCUIT BREAKER FAILURES AND DEFECTS
IN SERVICE.
Electra (CIGRE), no. 79 (1981), p. 21-91.
Mcnab, W.A.
URBAN ELECTRICITY SUPPLY SYSTEMS.
In: Reliability of Power Supply Systems, London, 21 -23 February 1977. Ed. by M.N.
Eggleton et al..
London: Institution of Electrical Engineers, 1977. P.89-42.
lEE Conf. Publication no. 148.
-146- References
Mohan Rao, N.S. and P.V.S. Sekhar
COMPARISON OF RELIABILITY OF ALTERNATE SYSTEMS OF DISTRIBUTION.
In: VI NPSC 90. Power Systems for the Year 2000 and Beyond. Proc. of the 6th Nat.
Power Systems Conf., Bombay, 4 - 7 June 1990.
New Delhi: Tata McGraw Hill, 1990. P.573-580.
Morrison, W.G. and R.J. Arhart
USING NEW TECHNOLOGY TO IMPROVE RELIABILITY OF AN INDUSTRIAL CABLE
DISTRIBUTION SYSTEM.
In: Annual Pulp and Paper Industry Technical Conf., Montreal, Canada, 3 - 7 June 1991.
New York: IEEE, 1991. P. 93-99.
Morzelle, M. and M. Donnelly, M. Kauffmann
THE RELIABILITY OF EMERGENCY GENERATOR SETS. STUDY, EXPERIMENTATION,
OPERATIONAL EXPERIENCE.
In: Int. Conf. on Operability of Nuclear Systems in Normal and Adverse Environments
(OPERA), Lyon, France, 18 - 22 September 1989.
Paris: Soc. Franc;;aise d'Energie Nucl., 1989. P. 393-403.
Nelson, J.A. and E.F. Johnson
POWER SUPPLY TO GAS CENTRIFUGE URANIUM ENRICHMENT PLANT.
IEEE Transactions on Power Apparatus and Systems, Vol. 101 (1982), p.2150-2157.
Norris, A.T.
REPORT OF CIRCUIT BREAKER RELIABILITY SURVEY OF INDUSTRIAL AND
COMMERCIAL INSTALLATIONS.
In: Industrial and Commercial Power Systems Technical Conference, Chicago, Illinois, 7-
11 May 1989.
New York: IEEE, 1989. P. 1-16.
O'Donnell, P.
REPORT OF SWITCHGEAR BUS RELIABILITY SURVEY OF INDUSTRIAL PLANTS AND
COMMERCIAL BUILDINGS.
IEEE Transactions on Industry Applications, Vol. 15 (1979), p. 141-147.
O'Donnell, P.
REPORT OF GENERATOR RELIABILITY SURVEY OF INDUSTRIAL PLANTS AND
COMMERCIAL BUILDINGS.
In: Industrial and Commercial Power Systems Technical Conf., Houston, Texas, 12 - 15
May 1980.
New York: IEEE, 1980. P. 40-44.
O'Donnell, P. and R.N. Bell, C. Heising, C. Singh, S.J. Wells
REPORT OF LARGE MOTOR RELIABILITY SURVEY OF INDUSTRIAL AND COMMERCIAL
INSTALLATIONS.
In: Industrial and Commercial Power System Technical Conf., Atlanta, GA, 7 - 10 May
1984.
New York: IEEE, 1984. P. 176-185.
-147- References
O'Donell, P. and R.N. Bell, D.W. Mc Williams, C. Singh, S.J. Wells
REPORT OF LARGE MOTOR RELIABILITY SURVEY OF INDUSTRIAL AND COMMERCIAL
INSTALLATIONS.
In: Industrial and Commercial Power System Technical Conference, Milwauki, WI, 9 - 12
May 1983.
New York: IEEE, 1983: P. 58-70.
Parascos, E.T. and J.A. Arceri
RELIABILITY ENGINEERING AND UNDERGROUND EQUIPMENT FAILURE, COST AND
MANUFACTURER'S ANALYSIS.
In: Reliability of Power Apparatus and Systems, 23 -24 September 1976, Montreal,
Canada. Ed. by M.F. Hashmil.
Piscateway, NJ: IEEE, 1976. P.25-30.
Patten, A.D.
DUTY CYCLE EFFECTS ON GENERATING UNIT AVAILABILITY.
In: IEEE Industry Applications Society Annual Meeting 1992.
Piscateway, NJ: IEEE, 1992. P.1286-1290.
Patterson, R.C. and J.E. Teague
FIELD EXPERIENCE - SOLID-STATE PROTECTIVE RELAYS.
In: Proceedings of the American Power Conf., Vol. 36., Chicago, 29 April- 1 May 1974.
Chicago: Illinois Institute of Technology, 1974. P. 1074-1079.
Pijls, R.M.M.
BACK-UP BEVEILIGING IN MIDDENSPANNINGSNETTEN (Back-up protection in medium
voltage networks; in Dutch).
Heerlen, The Netherlands: HTS (Technical College) Heerlen, april 1988.
Bachelor's thesis.
Prescott, W. and A.J. Rapson, C.D. Schofield
PROBABILISTIC EVALUATION OF POWER SUPPLIES FOR LARGE COMPUTER AND
COMMUNICATIONS INSTALLATIONS.
In: Probabilistic methods applied to electric power systems, London, 3 - 5 July 1991.
London: Institution of Electrical Engineers, Ed. by R.N. Allen at al..
lEE Conference Proceedings no. 338.1 991.P.224-228.
Radwan, R.M. and M. EI-Marsafawy
FAILURE ANALYSIS OF CIRCUIT BREAKERS IN THE UPPER EGYPT ZONE OF THE
EGYPTIAN UNIFIED POWER SYSTEM NETWORK.
In: Third Int. Conf. on Future Trends in Distribution Switchgear, London, UK, 23 - 25
April 1990. Ed. by R.N. Allan, et al ..
London: Institution of Electric Engineers, 1990. P. 79-83.
lEE Conference Publication no. 318.
Roos, E.
VERZORGUNGSZUVERLASSIGKEIT VON MITTELSPANNINGSNETZEN DER
OFFENLICHEN ENERGIE-VERSORGUNG (Supply reliability of medium voltage networks
in the public energy supply; in German).
Elektricitiitswirtschaft, Vol.88 (1989), p.316-329
-148- References
Ruoff, J.T. and H.P. van Meeteren
BETROUWBAARHEIDSANAL YSE VAN DISTRIBUTIESYSTEMEN: EEN EENVOUDIGE EN
EEN GEAVANCEERDE METHODE (Reliability analysis of distribution systems: a simple
and an advanced method; in Dutch).
Elektrotechniek, vol. 61 (1983), p. 770-779.
Sallam, A.A and M. Desouky, H. Desouky
EVALUATION OF OPTIMAL-RELIABILITY INDICES FOR ELECTRICAL DISTRIBUTION
SYSTEMS.
IEEE Transactions on Reliability, Vol. 39 (1990) p. 259-264.
Schilling, M.Th. and J.C.G. Praca, J.F. de Queiroz, C. Singh, H. Ascher
CHARACTERIZATION OF THE AGING OF THERMAL GENERATORS FOR RELIABILITY
ASSESSMENT.
In: Probabilistic Methods Applied to Electric Power Systems, Toronto, 11 - 13 July
1986.
Oxford, U.K.: Pergamon, 1987. P. 185-193.
Schilling, M.T. and J.C.G. Praca, J.F. de Queiroz, C. Singh, H. Ascher
DETECTION OF AGEING IN THE RELIABILITY ANALYSIS OF THERMAL GENERATIONS.
IEEE Transactions on Power Systems, Vol. 3 (1988), p. 490-499.
Schneider, F.
RELIABILITY OF UNINTERRUPTIBLE POWER SUPPLY SYSTEMS.
In: Int. Telecommunications Energy Conf. (lNTELEC), Florence, Italy,15 - 18 October
1989
New York: IEEE, 1989. Paper 14.4, p.1-7.
Selseth, N.A.
RELIABILITY OF CIRCUIT-BREAKERS. OUTAGE DATA EVALUATION.
In: Int. Conf. on Large High Voltage Electric Systems (CIGRE), Paris, France, August
1972.
Paris: CIGRE, 1973. Paper 13-04.
Simpson, W.C. and H.G. Stoll
INFLUENCE OF UPGRADING AND MAINTENANCE ON GENERATING UNIT
AVAILABILITY PERFORMANCE.
In: Proc. of the American Power Conf., Chicago, IL, 24 - 25 April 1989.
Chicago, IL: American Power Conf., 1989. P. 947-955.
Smith, C. and H. Donovan, H.J. Bartos
RELIABILITY SURVEY OF 600 TO 1800 kW DIESEL AND GAS-TURBINE GENERATING
UNITS.
IEEE Transactions on Industry Applications, Vol. 26 (1990), p. 741-755.
-149- References
Smith, M.J.
RELIABILITY, AVAILABILITY, AND MAINTAINABILITY OF UTILITY AND INDUSTRIAL
COGENERATION PLANTS.
In: IEEE Industry Applications Society Annual Meeting, San Diego, CA, 1 - 5 October
1989.
Piscatataway, NJ: IEEE, 1989. P. 1783-1787.
Snaith, E.R.
RELIABILITY EVALUATION OF AN ELECTRICAL SUPPLY SYSTEM FOR A NUCLEAR
POWER STATION.
In: Reliability of Power Supply Systems, London, 21 - 23 February 1977.
London: Institution of Electrical Engineers, 1977. P.1-6.
lEE Conf. Publication no. 148.
Stanek, E.K. and S.S. Venkata
MINE POWER SYSTEM RELIABILITY.
IEEE Transactions on Industry Applications, vol. 24 (1988), p. 827-838.
Suntio, T. and J. Uusitalo, l. Jonsson
AC-UPS RELIABILITY AND AVAILABILIITY PERFORMANCE: COMPARISON OF
AVAILABLE SOLUTIONS.
In: Int. Telecommunications Energy Conf. (INTELEC), Florence, Italy, 15 - 18 October
1989.
New York: IEEE, 1989. Paper 14.1, p.1-10
Suntio, T. and K. White
RELIABILITY AND AVAILABILITY PERFORMANCE AS A TOOL TO OPTIMIZE POWER.
In: Int. Telecommunications Energy Conf. (INTELECI. San Diego, CA 30 October - 2
November 1988.
New York: IEEE, 1988. P. 49-56
Todd, Z.G.
A PROBABILITY METHOD FOR TRANSMISSION AND DISTRIBUTION OUTAGE
CALCULATIONS.
IEEE Transactions on Power Apparatus and Systems, Vol. 83 (1964), p.696-701.
Ugokwe, E.C.
OFFLINE 1774 PLC RELIABILITY CASE STUDY.
In: IEEE Industry Applications Society Annual Meeting 1992.
Piscateway, NJ: IEEE, 1992. P.1969-1977.
van Amelsfoort, B. and J. Kevers, F. van Loon
BETROUWBAARHEIDSANALYSE VAN HET 10 kV-DISTRIBUTIENET IN RELATIE TOT
HET AANTAL VERMOGENSSCHAKELAARS EN DE PLAATSING HIERVAN IN HET NET
(Reliability analysis of the 10 kV distribution network in relation to the number of circuit
breakers and their position in the network; in Dutch).
's Hertogenbosch, Netherlands: PNEM, 1986.
Internal report. PNEM. (Electricity supply company)
-150- References
van der Vaart, P. and K. Bouwknegt
SOME ASPECTS OF THE IMPROVEMENT OF THE MTBF OF THE POWER SUPPLIED TO
COMPUTERS.
In: Int. Conf. on Electricity Distribution (CIRED), London, 8 - 12 May 1989.
London: Institution of Electrical Engineers, 1989: P. 402-405.
lEE Conference publication 305.
VDEN
RAPPORTERING VAN DE NIET-BESCHIKBAARHEID T.G. V. STORINGEN IN NETTEN VAN
0,4 kV ... 30 kV, ANALYSE 1987 (Report on the non-availability due to failures in 0.4 ..
30 kV networks, analysis 1987; in Dutch).
Arnhem, Netherlands: VDEN, 1988.
VDEN Report nr. 00043-VB 88-850.
Verplanke, F.W.R.
BETROUWBAARHEIDSONDERZOEK (Reliability research; in Dutch).
Vlissingen, Netherlands: Hogeschool (College) Zeeland, 1991.
Bachelor thesis.
Vesely, W.E.
AGING EFFECTS IN COMPONENT FAILURE AND DOWNTIME DATA AND IMPACTS ON
PLANT RISK.
In: Proc. 17th Water Reactor Safety Information Meeting, Rochville, MD, October 1989.
Washington D.C.: Nuclear Regulatory Commission, 1990. P. 473-496.
NUREG/CP-0105.
Vlutters. H.
VINGER AAN DE POLS VOOR VEILIGHEID (finger on the pulse for safety; in Dutch).
Stroomlijn, Vol. 12 (1991). no.3, p. 3-9.
Volkman, C.A. and S. Goldberg, W.F. Norton
A PROBABILISTIC APPROACH TO DISTRIBUTION SYSTEM RELIABILITY ASSESSMENT.
In: Probabilistic methods applied to electric power systems, London, 3 - 5 July 1991.
London: Institution of Electrical Engineers, 1991. P. 169-173.
lEE Conference Proceedings 338.
Warren, J.C.
INCREASING UPS AND COMPUTER RELIABILITY IN LARGE INSTALLATIONS.
In: IEEE Industry Applications Society Annual Meeting 1992.
Piscateway, NJ: IEEE, '1992. P.1981-1985.
Waumans, R.J.R.
OPENBARE NETTEN VOOR ELEKTRICITEITSDISTRIBUTIE (Public networks for electricity
distribution; in Dutch).
Deventer, The Netherlands: Kluwer, 1986.
Also: Arnhem, The Netherlands: VDEN, 1986.
-151- References
Wahlstrom, B. and W. Lord, K. Petterson, R. Alvinsson, M.A.S. Leijon
EXPERIENCES AND CONSIDERATIONS REGARDING ERECTION TESTING AND
OPERATION AVAILABLE OF GIS IN SWEDEN.
In: Int. Conf. on large High Voltage Electric Systems (CIGREI, Paris, 28 August - 3
September 1988.
CIGRE. Paris, 1988. Paper 23.07, p.1-8.
Whiting, J.P.
RELIABILITY OF POWER SUPPLIES AND SYSTEMS AT BROADCAST TRANSMITIING
STATIONS.
in: Int. Conf. on Electricity Distribution (CIREDI, Brighton, UK, 8 - 12 May 1989.
London: Institution of Electrical Engineers, 1989. P.411-415.
lEE Conference Publication no. 305.
Williams, W.P. and S.G. Mudge
RELIABILITY ASSESSMENT FOR INDUSTRIAL POWER NETWORKS.
In: Int. Conf. on Reliability of Power Supply Systems, 19 - 21 September 1983, London.
Ed. by H. Hammersley.
London: Institution of Electrical Engineers, 1983. P.107-111.
lEE Conf. Publication no. 225.
Wiseman, N.E.
RELIABILITY TESTING.
In: Reliability of Power Apparatus and Systems, 23 - 24 September 1976, Montreal,
Canada. Ed. by M.F. Hashmi.
Piscateway, NJ: IEEE, 1976. P.21-24.
Yaguchi, T. and Y. Oura, A. Tsuboi, F. Andow
IN-SERVICE EXPERIENCE AND RELIABILITY EVALUATION OF PROTECTIVE RELAY
SYSTEMS WITH BUILT-INN AUTOMATIC TESTING AND SUPERVISING DEVICES.
In: Int. Conf. on Large High Voltage Electric Systems (CIGREI, August 1984, Paris,
France.
Paris: CIGRE, 1984. Paper 34-05, p.1-6.
Yotsumoto, K. and S. Muroyama, H. Watanabe
DESIGN CONSIDERATIONS OF A DISTRIBUTED POWER SUPPLY FOR
TELECOMMUNICATIONS NETWORK USE BASED ON RELIABILITY ANALYSIS.
Transactions of the Institute for Electronics, Information, and Communication Engineers,
Part E, Vol. 73 (1990), p. 395-400.
-152- References
iOin<:ihoven Universitv of Technology Research Reports ISSN 0167-9708
[acul!.L of El8ctrica I Enqineerinq
12511 EIJndhovell. J.T.J. van and G.6. de Jonq. L. Stok
THE ASCIS DATA FLOW GRAPH: textual format.
EUT Report 91-E-251. 1991. ISBN 90-614H5H
(2521 Chen. J. ,nd PJ.I de Maag!. M.H.U. Herben
Coden: TElTEDE
WIDE-ANGLE RADIATION PATTERN mCULATION OF PARABOLOIDAL REFLECTOR ANTENNAS A compmtm
study.
EUT Report 91-E-252. 1991. ISBN 90-6144-252-4
(25J) Haan. S.W.H. de
A PWM CURRENT -SOURCE INVERTER FOR INTERCONNECTION BETWEEN A PHOTOVOLTAIC ARRAY AND THE
UTILiTY
EIlT Report 9H-253. 1991. ISBN 90-6144-253-2
(254) Velde. M. van de and U.K. Clultmans
EEG ANALYSIS FOR MONITORING OF ANESTHETIC DEPTH.
EUT Report 9H-254. 1991. ISBN 90-6144-254-0
(255) Smolders, 1.8,
AN EFFICIENT METHOD FOR ANALYZING MICROSTRIP ANTENNAS WITH A DIELECTRIC COVER USING A
SPECTRAL DOMAIN MOMENT METHOD.
EUT Renort 9\-E-255. 1991. iSBN 90-6144-255-9
(256) Backx, A,e,p,M. and A.A.H. Damen
IDENTIFICATION FOR THE CONTROL Of MIMO INDUSTRIAL PROCESSES,
EUT Report 9H-256. 1991. ISBN 90-6144-25(,-7
1257) Maaqt, P J! 1\, and H,G. ter Morsche, J.L.M. van den Broek
A SPXmL RECONSTRUCTION TECHNIQUE APPl.ICABLE TO MICROWAVE RADIOMETRY
EUT Report 92-E-257. 1992. ISBN 90-6144-257-5
!25GI Vieeshoums. J.M
0ERIV!TION OF A MODEL OF THE EXCITER OF A BRUSH LESS SYNCHRONOUS MACHINE.
EUT Report 92--250 1992 ISBN 90-6144-258-3
(259) Orlov, V.B.
DEfECT MOTION AS THE ORIGIN Of THE IIF CONDUCTlNCF. NOISE iN SOLIDS.
WT Report 92-E-259. 1992. ISBN 90-6144-259-1
(2601 RODI!"kers. J.E.
ALGDRITIIMS FOR SPEECH CODING SYSTEMS BASED ON LINEAR PREDICTION.
EUT Report 92-E-260. 1992. ISRN 90-6144-260-5
(261) Boom, LJ.J. van den and A.A.H D,men, Martin Klompstra
IDENTIFICATION FOR ROBUST CONTROL USING AN H-infinlty NORM.
EUT Report 91-E-261. 1992. ISBN 90-6144-261-)
12621 Grot,n. M and W. van Etten
LASER LINEWIDTH MEASUREMENT IN THE PRESENCE OF RIN AND USING THE RECIRCULATING SELF
HETERODYNE METHOD.
WT Report 92--262. 1992. ISBN 90-6l44-262-1
(2631 Smoiders. t
RIGOROliS ANALYSIS Of THICK MICROSTRIP ANTENNAS AND WIRE ANTENNAS EMBEDDED IN A ,lISmATE
EUT Heport 92-E-263. 1991. Isr,N 90-6144-161-j
EHQhoven UniversitY of R-es8arch_R-eoorts 01fi7--9708
Coden, TEl JEDE
!264\ Frenks, MId U M,j von Gils
THE ADAPTIVE RESONINCE THEORY NETWORK IClusterillg-1 behdVIour In re'dilon with hrmst,,,
audltory evoked D"tent"l pdtterllS,
WT Report n-E-164, 1992. ISBN 90-6144-1648
1165i Wellen, J,S. and F. M.r.e. Schem"ann, E. Sm,l\lruqqe, L N,F. KeulIDdfln
MANUFACTURING AND CHARACTERIZATION OF GA!5mGlAS MULTIPLE QUINTliMWELl. RIDGE mEGUIDE
LASERS
WT Report 92+20j 1m. ISBN 90-6\44-165-6
12661 Cluitruans, U.M
USING GENETIC ALGORITHMS fOR SCHEDULING DATA FLOW GRAPHS.
Wi Report n+M \99, 9H14H66-'l
12671 J6zmk, L, dnd A,P.H. van DiJk
12681
12691
mOl
i27l!
( 273)
( 274J
! METHOD FOR GENERAL SIMULTANEOUS FULL DECOMPOSITION Of SEQUENTIAL MACHINES:
Algorithms and lmplement,tlon
EUT Report 9H-267 1992. ISBN 90-6144-267-2
Boom. H. Vdo den and W VdO Etten, W,H.C, de Krom. P VdO Benneko . f. HUl)skens,
L. NJessen, F de =
AN OPTICAL ASK AND fSK PHASE DIVERSITY TRANSMISSION SYSTEM,
RUT Report 92+266, 1992. ISBN 90-6144-168-0
Putten, P H,i, Vdn der
MUlTlOISCIPLlNAIR SPEClFICEREN EN ONTWERPEN VAN MICROELEKTRONICA IN PROaUKTEN 110 Dutch I
EUT Report 1993. ISBN 90-6144-269-9
StnKs, R,HJ
PROGRIL, A lancru,o, for the defloJtion of protocol grarurudrs.
WT Report 93+270. 1993 ISBN 90-6144-270-2
Bloks, R,H,J,
CODE GENERATION FOR THE ATTRIBUTE EVALUATOR OF THE PROTOCOL ENGINE GRAMMAR PROCESSOR UNIT.
WT Report 93+271. 1993 ISBN 90-6144- 27 HI
1,n, KeplnQ dOli V'II Vcldhumn
flUE GAS clEANING BY PULSE CORONA STREAMER
fUT ReDort 9J-E-2J2 1993, ISBN 90-6144-2'12 9
Smolders, 11,.
FINlTE STACKED MICROSTRiP !RRAYS WITH THICK SUBSTR!TES.
EUT Report 93-E-273 1993. ISBN 90-6144-273-7
Bollen, M,H.J, and M I van Houten
ON INSULAR POWER SYSTEMS DraWlng up an inventory of phenomena dOd research POSSibIlities.
EUT Report 9J-f,-274. 1993. ISBN 90-6144-274-5
i27SI O(,I1[:;,n I.P.J van
rIl:CTROMIGNETlC COMPATTBILITY' Part 5, lust,ll,ilon and mitIgatIOn '!llldelJOes, scellOn 3,
,a\llilla dnd w'rllO
EliT Report 9H-175. 1993, iSBN 90-614075-3
12761 Bollen. M.H .1.
LITERATURE SEARCH fOR RELIABILITY om OF COMPONENTS IN ELECTRIC OISTPI8IITlON NFTWORKS,
EUT Report 93+276, 1993, ISBN 90-6144-276-1