Introduction To Power Systems: 1.1: A.C Transmission System
Introduction To Power Systems: 1.1: A.C Transmission System
An electrical substation is a subsidiary station of an electricity generation, transmission and distribution system where voltage is transformed from high to low or the reverse using transformers. Electric power flows through several substations between generating plant and consumer changing the voltage level in several stages. A substation that has a step-up transformer increases the voltage with decreasing current, while a step-down transformer decreases the voltage with increasing the current for domestic and commercial distribution. The word substation comes from the days before the distribution system became a grid. At first substations were connected to only one power station where the generator was housed and were subsidiaries of that power station. Basically there are two systems by which the electrical energy can be transmitted. They are (a) High voltage A.C system (b) High voltage D.C system
ii. The arrester should be mounted close to equipment to be protected and connected with shortest possible leads. On both the line and ground side to reduce the inductive effects of the leads while discharging large surge currents. iii. To protect the transformer windings. It is desirable to interconnect the ground lead of the arrester with the tank and also the neutral of the secondary. This interconnection reduces the stress imposed on the transformer winding by the surge currents to the extent of the drop across the ground.
3.3: Power line carrier communication (PLCC) 3.3.1 Coupling capacitor voltage transformers:
Coupling capacitor voltage transformers, commonly termed capacitor voltage transformers are devices used for coupling to a power line to provide low voltage for the operation of relays and metering instruments. Power line carrier accessories or provisions for future installation of carrier accessories may be included in the base. Coupling capacitor voltage transformers are commonly supplied without carrier accessories, especially at voltages above 11 kV, as a more economical alternative to inductive voltage transformers. Coupling capacitor voltage transformers can be provided with the same ratings and accuracy as inductive voltage transformers.
Fig3.2 coupling capacitor voltage transformers However, because of the energy-storage capability of capacitors, sudden reductions in the power line voltage may result in momentary distortion of the CCVT secondary voltage. The amount of distortion is related to CCVT capacitance and the burden (secondary load) value and configuration. Modern CCVT designs are available to minimize this problem.
It presents high impedance to currents of carrier frequencies of range for which it is tuned. The main coil of the trap is designed to withstand the maximum service current of the line. Various kinds of traps used in the grid are: 66KV....250A 132KV....400A, 500A 220KV850A
This is relevant in Power Line Carrier Communication (PLCC) systems for communication among various substations without dependence on the telecom company network. The signals are primarily teleportation signals and in addition, voice and data communication signals. Line trap also is known as Wave trap. .
3.4: Isolators
Isolators are used to connect and disconnect high voltage power systems under no load conditions. These are essentially off load devices although they are capable of dealing with small charging currents of bus bars and connections. The design of isolators is closely related to the design of substations. Isolator design is considered in the following aspects:
i. ii. iii. iv. v.
Some types of isolators include: i. Horizontal Isolation types ii. Vertical Isolation types iii. Moving Bushing types
Fig of isolators
3.6.2: Various types of mechanisms Spring change mechanism Pneumatic mechanism Hydraulic mechanism 3.6.3: Arc Quenching Medium Bulk oil (called bulk oil circuit breakers BOCB) Minimum oil (called minimum oil circuit breaker-MOCB) Natural air (called air circuit breaker-ACB) Forced air (called air blast circuit breaker-ABCB) Vacuum (called vacuum circuit breaker-VCB) SF6 gas (called sulphur hexa fluoride SF6 gas CB) NRI INSTITUTE OF TECHNOLOGY Page 9
b) Basic Principle
The transformer is based on two principles. Firstly, an electric current can produce a magnetic field (electromagnetism) and secondly that a changing magnetic field within the a coil of wire induces a voltage across the ends of the coil (electromagnetic induction). Changing the current in the primary coil changes the magnitude of the magnetic field. The changing magnetic flux link with the secondary coil where a voltage is induced across its ends.
Fig step down t/f A current passing through the primary coil creates a varying magnetic field. The primary and secondary coils are wrapped around a core of very high magnetic permeability, such as iron, This ensures that most of the magnetic field lines produced by the primary current are within the iron core and pass through the secondary coil as well as the primary coil. Transformers are essential for high voltage power transmission, which makes long distance transmission economically practical.
The EMF of a transformer at a given flux density increases with frequency. By operating at higher frequencies, transformers can be physically more compact because a given core is able to transfer more power without reaching saturation and fewer turns are needed to achieve the same impedance. Transformer losses are divided into losses in the windings, termed copper loss, and those in the magnetic circuit, termed iron loss. Losses in the transformer arise from: i. Winding resistance ii. Hysteresis losses iii. Eddy currents iv. Magnetostriction v. Mechanical losses vi. Stray losses
C Leakage transformer D Resonant transformers E. Instrument transformers Classification of Transformers is based on following factors. i. By power capacity: from a fraction of a volt-ampere (VA) to over a thousand MVA. ii. By frequency range: power, audio, or radio frequency. iii. By voltage class: from a few volts to hundreds of kilovolts. iv. By cooling type: air cooled, oil filled, fan cooled, or water cooled. v. By application: such as power supply, impedance matching, output voltage and current stabilizer, or circuit isolation. vi. By end purpose: distribution, rectifier, arc furnace, amplifier output. vii. By winding turns ratio: step-up, step-down, isolating (equal or near-equal ratio), and variable. Among the above mentioned transformers only instrument transformers are widely used in the sub station. Hence only instrument transformers are discussed in this section.
Type 1. Single 100% battery and 100% charger 2. Semi duplicate 50% batteries and 100% chargers
Disadvantages System outage for No standby DC maintenance Need to isolate battery/charger combination from load under boost charge conditions in order to prevent high boost voltages appearing on DC distribution system
Medium capital cost Standby DC provided which is 100% capacity on loss of one charger Each battery or charger can be maintained in turn. Each battery can be isolated and...
------------------------------
fig
Neutral bus bars may also be insulated. Earth bus bars are typically bolted directly onto any metal chassis of their enclosure. Bus bars may be enclosed in a metal housing, in the form of bus duct or bus way, segregated-phase bus, or isolated-phase bus.
Fig relay
3.11. Grounding
A properly designed and installed grounding system ensures reliable performance of electrical substations . Just how important is substation reliability? Fast clearing of faults, made possible by good grounding, improves the overall safety and reliability of an electrical system Therefore, substation reliability must be as "built-in" as possible because of the high available fault current levels present and unlikely occurrence of follow-up grounding inspections.
FIG grounding
Types of grounding:
Grounding of earth may be classified as equipment grounding System grounding and Neutral grounding.
) ) i)
Methods of Grounding
The methods commonly used for grounding the neutral point of a 3-phase system are: (i) (ii) (iii) (iv) Solid or effective grounding Resistance grounding Reactance grounding Resonant grounding
Chapter 4
NRI INSTITUTE OF TECHNOLOGY Page 15
Unbalanced current protection (61) for double star connected banks with NTC and neutral displacement protection for single star banks with RVT.
For restoring the normalcy, NBF LC is to be returned. Earth roads are to be removed. Before closing the isolator, it is to confirm that the earths were removed at the other end also. As mentioned earlier, it is 132/220 KV feeder or 220/132 KV power transformer, Permission is to be taken from the divisional engineer/load dispatch for restoring the normalcy. Charging instructions of the DE/LD/VS/Hyderabad are to be followed for restoration.
Over flux relay : from the respective PT metering or protection core. LBB relay: it is in series with the distance protection main-2 CT circuits in case of 220KV feeders and O/L & E/L relay CT circuits in case of PTRs. Under frequency relay and df/dt: any bus PT supply can be extended. Ammeter: in the CT metering core through the ammeter selector switch.
CONCLUSION
The project is successfully documented by acquired knowledge from the substation. The goals that have been achieved are: Study voltage transformations in a substation i.e. step up or step down of high voltage. Study of SF6 circuit breaker. Providing continuous and reliable operation to the consumer. Providing reliable transmission of high voltages with control over losses. A thorough analysis done on the various equipments and protective devices used in the substation.
BIBLIOGRAPHY
1. Electric Power Substations Engineering By James C. Burke and Anne-Marie Sahazizian. NRI INSTITUTE OF TECHNOLOGY Page 20
Publisher CRC. 2. Electric Power Systems: A Conceptual Introduction By Alexandra von Meier Publisher: Wiley-IEEE. 3. Handbook of Transformer Design and Applications ,By, William M. Flanagan Publisher: McGraw-Hill Professional. 4. Power System Engineering, By A.Chakrabarti, M.L.Soni , P.V.Gupta,U.S Bhatnagar. Publisher: Dhanpat Rai & Co 5. Transmission, Distribution and Utilization Volume III, By B.L.THERAJA & A.K.THERAJA Publisher: S.CHAND & COMPANY LTD. 2004