C57 135-2001 PDF
C57 135-2001 PDF
C57 135-2001 PDF
135-2001
IEEE Standards
C57.135
TM
Published by The Institute of Electrical and Electronics Engineers, Inc. 3 Park Avenue, New York, NY 10016-5997, USA 31 May 2002
IEEE Guide for the Application, Specication, and Testing of Phase-Shifting Transformers
Sponsor
Abstract: Theory, application of phase-shifting transformers, and the difference of specification and testing to standard system transformers are described. Various types of phase-shifting transformers and how to select the optimal design to achieve required control of power flow are covered. An understanding of the terminology, types, construction, and testing specifical to phaseshifting transformers is provided. Keywords: advance phase angle, dual-core design, main transformer, power transfer, phaseshifting transformer, retard phase angle, series transformer, single-core design, special tests
The Institute of Electrical and Electronics Engineers, Inc. 3 Park Avenue, New York, NY 10016-5997, USA Copyright 2002 by the Institute of Electrical and Electronics Engineers, Inc. All rights reserved. Published 31 May 2002. Printed in the United States of America. Print: PDF: ISBN 0-7381-3078-8 ISBN 0-7381-3079-6 SH94968 SS94968
No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission of the publisher.
IEEE Standards documents are developed within the IEEE Societies and the Standards Coordinating Committees of the IEEE Standards Association (IEEE-SA) Standards Board. The IEEE develops its standards through a consensus development process, approved by the American National Standards Institute, which brings together volunteers representing varied viewpoints and interests to achieve the nal product. Volunteers are not necessarily members of the Institute and serve without compensation. While the IEEE administers the process and establishes rules to promote fairness in the consensus development process, the IEEE does not independently evaluate, test, or verify the accuracy of any of the information contained in its standards. Use of an IEEE Standard is wholly voluntary. The IEEE disclaims liability for any personal injury, property or other damage, of any nature whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the publication, use of, or reliance upon this, or any other IEEE Standard document. The IEEE does not warrant or represent the accuracy or content of the material contained herein, and expressly disclaims any express or implied warranty, including any implied warranty of merchantability or tness for a specic purpose, or that the use of the material contained herein is free from patent infringement. IEEE Standards documents are supplied AS IS. The existence of an IEEE Standard does not imply that there are no other ways to produce, test, measure, purchase, market, or provide other goods and services related to the scope of the IEEE Standard. Furthermore, the viewpoint expressed at the time a standard is approved and issued is subject to change brought about through developments in the state of the art and comments received from users of the standard. Every IEEE Standard is subjected to review at least every ve years for revision or reafrmation. When a document is more than ve years old and has not been reafrmed, it is reasonable to conclude that its contents, although still of some value, do not wholly reect the present state of the art. Users are cautioned to check to determine that they have the latest edition of any IEEE Standard. In publishing and making this document available, the IEEE is not suggesting or rendering professional or other services for, or on behalf of, any person or entity. Nor is the IEEE undertaking to perform any duty owed by any other person or entity to another. Any person utilizing this, and any other IEEE Standards document, should rely upon the advice of a competent professional in determining the exercise of reasonable care in any given circumstances. Interpretations: Occasionally questions may arise regarding the meaning of portions of standards as they relate to specic applications. When the need for interpretations is brought to the attention of IEEE, the Institute will initiate action to prepare appropriate responses. Since IEEE Standards represent a consensus of concerned interests, it is important to ensure that any interpretation has also received the concurrence of a balance of interests. For this reason, IEEE and the members of its societies and Standards Coordinating Committees are not able to provide an instant response to interpretation requests except in those cases where the matter has previously received formal consideration. Comments for revision of IEEE Standards are welcome from any interested party, regardless of membership afliation with IEEE. Suggestions for changes in documents should be in the form of a proposed change of text, together with appropriate supporting comments. Comments on standards and requests for interpretations should be addressed to: Secretary, IEEE-SA Standards Board 445 Hoes Lane P.O. Box 1331 Piscataway, NJ 08855-1331 USA Note: Attention is called to the possibility that implementation of this standard may require use of subject matter covered by patent rights. By publication of this standard, no position is taken with respect to the existence or validity of any patent rights in connection therewith. The IEEE shall not be responsible for identifying patents for which a license may be required by an IEEE standard or for conducting inquiries into the legal validity or scope of those patents that are brought to its attention. The IEEE and its designees are the sole entities that may authorize the use of the IEEE-owned certication marks and/or trademarks to indicate compliance with the materials set forth herein. Authorization to photocopy portions of any individual standard for internal or personal use is granted by the Institute of Electrical and Electronics Engineers, Inc., provided that the appropriate fee is paid to Copyright Clearance Center. To arrange for payment of licensing fee, please contact Copyright Clearance Center, Customer Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions of any individual standard for educational classroom use can also be obtained through the Copyright Clearance Center.
iii
Introduction
(This introduction is not part of IEEE Std C57.135-2001, IEEE Guide for the Application, Specication, and Testing of Phase-Shifting Transformers.) This guide describes the application, specication, and testing of phase-shifting transformers. It is intended for the following: Organizations responsible for the application and specication of phase-shifting transformers for electric transmission systems to control power ow. Organizations responsible for testing phase-shifting transformers.
This guide is designed to help organizations Understand the various types of phase-shifting transformers and how to apply them to obtain required control of power ow. Prepare specications for the purchase of phase-shifting transformers. Standardize tests and test methods for phase-shifting transformers.
This guide is intended to satisfy the following objectives: Promote consistency within organizations for the application and specication of phase-shifting transformers. Provide an understanding of the terminology, types, construction, and testing relating specically to phase-shifting transformers. Promote the standardization of testing procedures for phase-shifting transformers.
Participants
At the time this guide was completed, the Working Group on Phase-Shifting Transformers had the following membership: Edgar R. Trummer, Chair Thomas Lundquist, Vice Chair and Secretary Donald Chu, Secretary
Rajendra K. Ahuja Dennis J. Allan Dave Allaway Burhan Becer Enrique Betancourt Alvaro Cancino Donald J. Cash Bob Clark Peter W. Clarke Florian Costa Vince Dahinden D. de la Cruz Dieter Dohnal Fred Elliot Joseph F. Foldi Jim D. Fyvie Donald A. Gillies Everett G. Hager, Jr. N. Wayne Hansen James H. Harlow Bill Kennedy Lincoln Koga Luther Kurtz Mike Lau J. Leech Stan Lindgren Thomas Lundquist Jack McGill Jim McIver Patrick McShane Harold R. Moore Jerry Mundo Gerald A. Paiva Bipin K. Patel Dan D. Perco Sam Perkins V. Pham Gustav Preininger Patrick Pries Jean-Christophe Riboud P. Russman Vallamkonda Sankar M. Saravolac Vic Shenoy John Slapp Bob Stewart Bill Thompson Chuck Todd Robert A. Veitch Jim Warden Joe D. Watson Klaus Weidman
iv
The following members of the balloting committee voted on this standard. Balloters may have voted for approval, disapproval, or abstention.
Samuel H. Aguirre Rajendra K. Ahuja Dennis J. Allan Jacques Aubin Peter M. Balma Ronald L. Barker Mike Barnes William H. Bartley Barry L. Beaster Enrique Betancourt Alain Bolliger Donald J. Cash Peter W. Clarke Jerry L. Corkran John C. Crouse Dieter Dohnal Keith Ellis Joseph F. Foldi Michael A. Franchek Jim D. Fyvie Donald A. Gillies Richard D. Graham Randall C. Groves Robert L. Grunert E.G. Hager, Jr. Ernst Hanique N. Wayne Hansen James H. Harlow Keith R. Highton Philip J. Hopkinson James D. Huddleston, III Mike Iman Charles W. Johnson Anthony J. Jonnatti Lars-Erik Juhlin Sheldon P. Kennedy John G. Lackey Stephen R. Lambert John P. Lazar Maurice Linker Donald L. Lowe Thomas Lundquist Joe D. MacDonald Donald MacMillan William A. Maguire K. T. Massouda John W. Matthews Nigel P. McQuin Joseph P. Melanson Gary L. Michel Harold R. Moore R. J. Musil Shantanu Nandi E.T. Norton Gerald A. Paiva Bipin K. Patel Dhiru S. Patel Sanjay Y. Patel Wesley F. Patterson Paulette A. Payne Carlos O. Peixoto Dan D. Perco Mark D. Perkins Linden W. Pierce Paul J. Pillitteri Donald W. Platts Gustav Preininger Tom A. Prevost E. Purra Jean-Christophe Riboud Vallamkonda Sankar Subhas Sarkar Rick Sawyer Pat Scully Hyeong Jin Sim Charles Simmons Tarkeshwar Singh Ron W. Stoner Richard E. Sullivan Thomas P. Traub Edgar R. Trummer Subhash C. Tuli John Vandermaar Joseph J. Vaschak Robert A. Veitch Barry H. Ward Joe D. Watson B. Scott Wilson
When the IEEE-SA Standards Board approved this standard on 6 December 2001, it had the following membership: Donald N. Heirman, Chair James T. Carlo, Vice Chair Judith Gorman, Secretary
Satish K. Aggarwal Mark D. Bowman Gary R. Engmann Harold E. Epstein H. Landis Floyd Jay Forster* Howard M. Frazier Ruben D. Garzon *Member Emeritus Also included is the following nonvoting IEEE-SA Standards Board liaison: Alan Cookson, NIST Representative Donald R. Volzka, TAB Representative Noelle D. Humenick IEEE Standards Project Editor James H. Gurney Richard J. Holleman Lowell G. Johnson Robert J. Kennelly Joseph L. Koepnger* Peter H. Lips L. Bruce McClung Daleep C. Mohla James W. Moore Robert F. Munzner Ronald C. Petersen Gerald H. Peterson John B. Posey Gary S. Robinson Akio Tojo Donald W. Zipse
Contents
1. Overview.............................................................................................................................................. 1 1.1 Scope............................................................................................................................................ 1 1.2 Purpose......................................................................................................................................... 1 2. 3. 4. References............................................................................................................................................ 1 Definitions............................................................................................................................................ 2 Application and theory of PSTs........................................................................................................... 4 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 5. Introduction.................................................................................................................................. 4 Basic principle of applicationadvanced and retard phase angle .............................................. 4 The PST under load ..................................................................................................................... 5 Power transfer .............................................................................................................................. 6 Types of PSTs .............................................................................................................................. 8 Special on load tap changer (OLTC) features............................................................................ 12 Arrangement of more than one PST .......................................................................................... 14 Design criteria............................................................................................................................ 15
Service conditions.............................................................................................................................. 16 5.1 5.2 5.3 5.4 Usual service conditions ............................................................................................................ 16 Loading at other than rated conditions....................................................................................... 17 Unusual service conditions ........................................................................................................ 17 Protection ................................................................................................................................... 18
6.
Rating data ......................................................................................................................................... 21 6.1 Polarity, angular displacement, and terminal markings............................................................. 22 6.2 Impedance .................................................................................................................................. 22 6.3 Nameplates................................................................................................................................. 22
7.
Construction....................................................................................................................................... 22 7.1 Enclosed throat connections ...................................................................................................... 23 7.2 Liquid insulation and preservation system ................................................................................ 23
8.
9.
Control system ................................................................................................................................... 24 9.1 Control equipment and accessories............................................................................................ 24 9.2 Requirements ............................................................................................................................. 24 9.3 Test code for control systems .................................................................................................... 26
10.
vi
10.2 Special tests for PSTs................................................................................................................. 28 11. Tolerances .......................................................................................................................................... 28 11.1 General....................................................................................................................................... 28 11.2 Tolerances for ratio of series and main units ............................................................................. 29 11.3 Tolerance for phase angle and impedance ................................................................................. 29 12. Bid document checklist...................................................................................................................... 29 12.1 Nontechnical information .......................................................................................................... 29 12.2 Technical information................................................................................................................ 29 12.3 Special requirements or conditions............................................................................................ 30 12.4 Additional information............................................................................................................... 31 Annex A (informative) Bibliography............................................................................................................. 32
vii
viii
IEEE Guide for the Application, Specication, and Testing of Phase-Shifting Transformers
1. Overview
1.1 Scope
This guide covers the application, specication, theory of operation, and factory and eld testing of singlephase and three-phase oil-immersed phase-shifting transformers (PSTs). This guide is limited to matters particular to PSTs and does not include matters relating to general requirements for power transformers covered in existing standards, recommended practices, or guides.
1.2 Purpose
The terminology, function, application, theory of operation and protection, and design of PSTs are not covered by existing transformer standards and guides. The purpose of this document is to provide guidance to those specifying, designing, and using PSTs.
2. References
This standard shall be used in conjunction with the following publications. When the following standards are superseded by an approved revision, the revision shall apply. IEEE Std 693-1997, IEEE Recommended Practices for Seismic Design of Substations.1 IEEE Std 1313.1-1996, IEEE Standard for Insulation CoordinationDenitions, Principles, and Rules. IEEE Std C37.90.1-2002, IEEE Standard Surge Withstand Capability (SWC) Tests for Protective Relays and Relay Systems.
1IEEE
publications are available from the Institute of Electrical and Electronics Engineers, 445 Hoes Lane, P.O. Box 1331, Piscataway, NJ 08855-1331, USA (http://standards.ieee.org/).
IEEE Std C57.12.00-2000, IEEE Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers. IEEE Std C57.12.10-1988, American National Standard for Transformers 230 kV and Below 833/958 through 8333/10 417 kVA, Single-Phase, and 750/862 through 60 000/80 000/100 000 kVA, Three-Phase without Load Tap Changing; and 3750/4687 Through 60 000/80 000/100 000 kVA with Load Tap ChangingSafety Requirements. IEEE Std C57.12.70-2001, American National Standard Terminal Markings and Connections for Distribution and Power Transformers. IEEE Std C57.12.80-2002, IEEE Standard Terminology for Power and Distribution Transformers. IEEE Std C57.12.90-1993, IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers, and IEEE Guide for Short Circuit Testing of Distribution and Power Transformers. IEEE Std C57.19.00-1991 (Reaff 1997), IEEE Standard General Requirements and Test Procedures for Outdoor Power Apparatus Bushings. IEEE Std C57.19.01-1991 (Reaff 1997), IEEE Standard Performance Characteristics and Dimensions for Outdoor Apparatus Bushings. IEEE Std C57.19.100-1995 (Reaff 1997), IEEE Guide for Application of Power Apparatus Bushings. IEEE Std C57.91-1995, IEEE Guide for Loading Mineral-Oil-Immersed Overhead and Pad-Mounted Distribution Transformers Rated 500 kVA and Less with 65 C or 55 C Average Winding Rise. IEEE Std C57.93-1995 (Reaff 2001), IEEE Guide for Installation of Liquid-Immersed Transformers. IEEE Std C57.131-1995, IEEE Standard Requirements for Load Tap Changers.
3. Denitions
All denitions, except as specically covered in this guide shall be in accordance with IEEE C57.12.801978 and The Authoritative Dictionary of IEEE Standards Terms, Seventh Edition [B10].2 3.1 advance phase angle: The phase angle expressed in degrees that results when the load (L) terminal voltage leads the source (S) terminal voltage. 3.2 excitation-regulating winding: A two-core phase-shifting transformer (PST) design in which the main unit has one winding operating as an autotransformer that performs both functions listed under excitation and regulating winding of a two-core PST. 3.3 excitation winding: The winding of a phase-shifting transformer (PST) that draws power from the source to energize the PST. 3.4 excited winding of a two-core phase-shifting transformer (PST): The winding of the series unit that is excited from the regulating winding of the main unit.
2The
3.5 L terminal: The L terminal is used to measure the voltage phase-shift angle when compared to the S terminal of the phase-shifting transformer (PST). 3.6 main unit of a two-core phase-shifting transformer (PST): The core and coils that furnish excitation to the series unit. 3.7 phase-shifting transformer (PST): A transformer that advances or retards the voltage phase-angle relationship of one circuit with respect to another. 3.8 primary circuit of a phase-shifting transformer (PST): The circuit on the input side of a single-core PST or of the main unit of a two-core PST. This circuit is composed of the excitation winding. 3.9 rated kVA of a phase-shifting transformer (PST): The apparent power at rated voltage for which the PST is designed. 3.10 rated phase angle of a phase-shifting transformer (PST): The phase angle measured between the S and L terminals at maximum advance and/or retard tap position under no-load condition. 3.11 rated voltage of a phase-shifting transformer (PST): The phase-to-phase voltage to which operating and performance characteristics are referred. The voltage ratings are to be dened at no-load and based on turn ratios. 3.12 regulated circuit of a phase-shifting transformer (PST): The circuit on the output side of the PST in which it is desired to control the voltage, or the phase relation, or both.
NOTEIn the regulated circuit the voltage may be held constant or may vary with or without relation to the phase angle, depending on the type of PST.
3.13 regulating winding: The winding of a single-core phase-shifting transformer (PST) or of the main unit of a two-core PST in which taps are changed to vary the phase angle. 3.14 retard phase angle: The phase angle expressed in degrees that results when the L terminal voltage lags the S terminal voltage. 3.15 series unit of a two-core phase-shifting transformer (PST): The core and coil unit that has one winding connected in series in the line circuit. 3.16 series winding of a two-core phase-shifting transformer (PST): The winding of the series unit that is connected in series in the line circuit. 3.17 single-core design: A single-core phase-shifting transformer (PST) consists of a single unit in which all windings are mounted on a single core. 3.18 S terminal: The S terminal is the terminal that is used as the xed reference point when measuring the voltage phase angle of a phase-shifting transformer (PST). 3.19 two-core design: A two-core phase-shifting transformer (PST) consists of a series unit and a main unit. The series and the main unit can be either in one tank or in separate tanks.
DV
Xi Zi ~ j
I 1 *Z 1 VS VL
I 2 *Z 2
I 1 *Z 1 VL VS
DV I 2 *Z 2
V L V S V L* VL
DV VS V L*
I 1 *Z 1 < I 2 *Z 2 A d v a n c e d: V L * leadsV S
A numerical example should illustrate this. If it is required that both systems are loaded with 50% of the total transferred power 2S, and the impedances are assumed to be z1 = 0.02 and z2 = .30, related to S, the necessary additional voltage becomes V = .30 0.02 = .28. Hence, a load phase angle (advanced) of about 15.6 is necessary. The total angle between source and load becomes 1.1. In the case of z1 = 0.30 and z2 = 0.02, the same load phase angle (retard) would be needed but the total phase angle between source and load would become 16.7. If no measures were taken, the load distribution between system 1 and 2 would be 0.9375 to 0.0625 instead of 0.5 to 0.5. A second important application is the use of a PST to control the power ow between two large independent grids. An advanced phase-shifting angle is necessary to achieve a ow of active power from system 1 to system 2 (Figure 2).
Figure 3Demonstration of load conditions The phasor diagram of the PST can be drawn. Starting with the load voltage VL and calculating the ohmic and reactive voltage drop in the 1:1 transformer, the load voltage VL* at its primary side can be obtained. The load phase angle can be calculated by using Equation (2). I L X cos L I L R sin L z T cos L = arc tan ------------------------------------------------------------------------------------------ arctan ---------------------------------------V L + I L X sin L + I L R cos L 100 + z T sin L (2)
The phase-shifting unit adds and so, nally, the load phase angles of the transformer *(a) and *(r) respectively are obtained. *(a) = *(r) = ( + ) is phase-shift angle (loaded) advance is phase-shift angle (loaded) retard (3) (4)
To obtain an advanced phase angle *(a) under load, the no-load phase angle has to be chosen properly under consideration of the phase angle of the PST. On the other hand, the retard phase angle (r) is increased under load. This has an impact on transformer and tap-changer as dealt with in 4.8.4.
the power components at the source side become VS P ( ) = P 0 cos Q 0 sin + --------* sin XT VS Q ( ) = P 0 sin + Q 0 cos + -------( 1 cos o ) XT
2 2
(5)
(6)
Figure 4 explains the effect of the introduction of the phase-shift angle . In the equation, the rst two terms reect the effect of the phase angle on the original power ow as easily as can be derived from Figure 4. The last term represents the additional power ow generated by the additional voltage V across the impedance jX of the PST. Taking into consideration that the real component of V(V cos(/2) drives a current with a positive imaginary component, and the imaginary component of V(V*sin(/2)) a current with a positive real component and that V= 2*Vs*sin(/2), the last terms in Equation (3) and Equation (4) respectively can be conrmed without difculties.
Figure 4Effect of phase-shift angle Figure 5 shows the variation of the additional power ow (assumption: P0 = Q0 = 0, ZT jXT, Vs2/XT = 1) with the PST angle . Figure 6 shows as an example the variation of the power ow at the source side with the phase angle , depending on different preload conditions. The maximum additional transferred power has been assumed to be 1. It can be seen how the power ow is inuenced when the no-load phase angle of the PST is changed from zero to maximum leading phase shift. The highest increase of active power for the same phase shift appears when a negative reactive power ow exists, i.e., with high capacitive load. An inductive load (positive reactive power) decreases the effect of the PST. The reactive power ow is also inuenced by the preload condition. The active power has the major impact on the inuence of the PST angle.
Figure 6Variation of power ow with the phase-shift angle depending on different preload conditions
so on. The scheme has been plotted for subtractive polarity of the windings and the tap position has been chosen so that the transformer produces an advanced phase angle. Under no-load condition the regulation is symmetrical, i.e., the absolute values of source and load voltage are the same.
(7)
(8) (9)
With consideration of these equations, the phasor diagram can be drawn and absolute values can be determined. V S1 = V L1 = V 1 V 10 = V 1 cos -2 V 1 = V 1 2 sin -2 V = V 10 3 = V 1 3 cos -2 I S1 = I L1 = I 1 V 1 2 sin - = I L1 ------I = I L1 --------- cos -2 2 V 3 (10) (11)
(12)
(16)
whereas the rated design power which determines the size of the unit becomes: I P T = 3 V = P s 2 sin -=1 =L1 2 (17)
In practice many solutions are possible to the design of a PST. The users electric power system requirements and the manufacturers preference generally determine the design. The major factors determining the type of PSTs are given below: Performance factors The power rating and phase-shift angle requirements The voltages The connected systems short-circuit capability
Design factors Type of construction (core form or shell form) Layer or disc winding design Shipping limitations Load tap changer (LTC) performance specication
These factors decide whether a single-core or a two-core type has to be chosen. These two types are described in more detail in the following clauses. 4.5.2 Single-core design With the design outlined in Figure 7a, symmetrical conditions are obtained. The LTC can also be equipped with a reversing change-over selector. This solution permits changing from an advanced phase angle to a retard phase angle. With the single-core design, it is generally accepted practice to supply two sets of three single pole tap changers: one set connected to the S terminals, and the second set connected to the L terminals. As a simplied solution, it is also possible to use only one-half of the tapped winding. But in that case the load voltage increases with respect to the source voltage with increasing phase angle (Figure 7b).
10
In the case of a small rated switching capacity (step voltage through current), a solution with one twophase LTC per phase is possible, using an LTC assembly according to Figure 8.
Figure 8PST with small switching capacity As a further example, Figure 9 shows the connection diagram and the phasor diagram of a delta-hexagonal PST. These transformers have LTCs with linear regulation, i.e., without a change-over selector.3
Figure 9Connection diagram and the phasor diagram of a delta-hexagonal PST The single-core design is less complex and has fewer kVA parts than two-core designs, but has some disadvantages as follows: The LTC and the tapped winding are in the line end of the windings and are directly exposed to the system short-circuit currents and overvoltages. Voltage per tap and current are determined by the phase angle requirement and rating of the PST and cannot be adjusted to obtain optimum switching conditions. If one of these parameters exceeds its limit, the solution would not be possible although the required switching capability may still be given.
3There
11
4.5.3 Two-core design The most commonly used circuit for two-core designs is shown in Figure 10. This conguration consists of a series unit and a main unit. For smaller ratings and lower voltages, two-core PSTs may be built into one single tank, while large ratings and high voltage PSTs require a two-tank design. The advantage of a two-core design is the exibility in selecting the step voltage and the current of the regulating winding. They can be optimized in line with the voltage and current ratings of the LTC. Since LTCs have limited current ratings and step voltages per phase as well as limited switching capacity, they are the main limiting feature for the maximum possible rating of PSTs. More than one LTC per phase may have to be utilized for very large ratings. Furthermore, three-pole LTCs can be used. If the rated switching capacity is too high, three single-pole LTCs have to be used. The LTC insulation level to ground is independent of the system voltage and can generally be kept low. The potential connection of the regulating winding has to be checked (see 4.6.1) but often it is not critical and the values are comparable with those of a regulating winding at the neutral end of a common network transformer.
12
Figure 11Impact of shields on recovery voltage Both recovery voltages occurring during reversing change-over selector operation and switched current resulting from capacitances have limitations. The limit of the magnitude of this current is in the range of a few hundred milliamperes. In special cases when a third winding with a low voltage level is specied, it may be possible to use this winding instead of the shields. Shielding has, in addition, the advantage that it protects the regulating winding from capacitively transferred transients. If shielding is not possible, one of the following solutions has to be used to solve the problem: a) The rst way is to connect the tap winding to a xed potential during the reversing change-over operation by a xed ohmic resistor or capacitor that is usually connected to the middle of the regulating winding and to the current take-off terminal of the LTC. This solution is not applicable in every case (especially with arrangements according to Figure 11, when no shields are used). The connection of resistors or capacitors increases the amount of switched current due to the small resistance compared to that of the capacitances. The second possibility is to use an advance-retard switch (ARS) as shown in Figure 12. This switch allows the reversing change-over operation to be carried out in two steps without interruption. The regulating winding remains connected to a xed potential during the whole operation. The limiting parameter for the ARS is the process of commutation, which has to be controlled by the ARS. It is determined by the commutation of the through current from a small inductive loop to a larger one.
b)
4.6.2 LTC with coarse change-over selector By using the change-over selector for inserting a coarse regulating winding, the achievable phase angle in one direction can be enlarged. If a change from advanced to retard position is required, an additional switching device, which has to be designed like an ARS, is necessary so that the switching can be performed without interruption of the load current. The ARS has to control the process of commutation which, in this case, is not only determined by the loop formed by the connecting leads but also by the impedance of the winding itself. If the reversing operation can be carried out with a de-energized transformer, an off-circuit tap changer is sufcient. Figure 13 shows different arrangements with coarse change-over selectors (a, b) and, in addition, the use of two LTCs (c). Also the arrangement of an ARS for the exciting winding of the series transformer is shown in (b).
13
Figure 13Different arrangements with coarse change-over selectors 4.6.3 Number of OLTCs required See Table 1.
14
None
12
6 single-phase units
36 unitsd
6 single-phase units
None
Two-core
10
1 three-phase unit (wye-connected) or 3 single-phase unitsb 1 three-phase unit (wye-connected) or 3 single-phase unitsb 1 three-phase unit (wye-connected) or 3 single-phase unitsb 1 three-phase unit (wye-connected) or 3 single-phase unitsb and 3 single-phase units
None
13(a)
13 unitsd 13 unitsd
13(b)
13(c)
13 unitsd
aThe reversing change-over selector is not shown on Figure 7a and Figure 7b. bDepending on rated switching capacity and through current. The two-phase LTCs have to be connectcAsymmetric regulation. dDepending on voltage level
ed according to Figure 8.
4.7.2 Parallel connection of PSTs If two or more (n) identical PSTs are connected in parallel, the impedance from each PST combine in parallel to provide a reduced total impedance. The MVA rating of the bank of parallel-connected PSTs is equivalent to the sum of the MVA ratings of all parallel-connected PSTs. For example, two 100 MVA PSTs, each with a 5 phase shift and 10% impedance connected in parallel will be equivalent to one 200 MVA PST with a 5 phase shift and 5% impedance.
15
4.8.2 Dielectric design of the two-core type The transmission of transient voltages in the two-core design is rather complex. When applying impulse tests to either the S or the L terminals of the series transformer, the connected exciting winding of the main transformer will also be exposed to a high voltage. There may be high-voltage oscillations of the connecting leads, depending on the capacitive voltage control of the series winding. High voltages may be transferred to other windings coupled to the series winding or to the excitation winding. Therefore, rather complex computer models may be required to compute the transient voltages for this conguration. 4.8.3 Special considerations for a two-tank design When the two-core design is used with two tanks, special precautions must be taken to design connections between the two tanks. As illustrated in Figure 10, the connection operates at the system voltage level so that the leads must be insulated for the overvoltages that may occur under both transients and power frequency conditions. A short-circuit between the connections of the two units has to be considered as an internal fault, which would cause severe damage or even destroy the PST. A short-circuit proof design for this special case would result, if possible at all, in a signicant increase in cost. Therefore, it is strongly recommended to use metal enclosures to protect the connections against lightning strikes and other possible sources of a short circuit. 4.8.4 Overload conditions (loading above nameplate rating) Overloading of a PST in the sense of operating it with a current beyond the name-plate rating increases the internal phase angle [see Equation (2)] and consequently also the load phase-shift angle (r) in the retard position [see Equation (4)]. This may result in a load phase angle that exceeds the maximum rated no-load phase angle. The voltage across the regulating winding and consequently also the voltage per step of a single-core type, as well as the voltage across the series winding of a two-core type will, in this case, exceed the rated voltage. Furthermore, in a two-core design, the main transformer also will experience a certain degree of overexcitation with the same consequences for the regulating winding. The degree depends on the ratio of the impedances of series and main transformer. It mustbeside the effect that parts of the core(s) may be overuxedtherefore also be checked whether the parameters voltage per step, current, and switching capability are still within the limits of the LTC design.
5. Service conditions
PSTs conforming to this guide will be suitable for operation at rated voltage and rated kVA as follows:
b) c) d)
16
e)
f)
purchaser. The manufacturer shall provide for differential motion between the two tanks, if used, and in the case of remotely mounted radiators provide for their differential motion. The manufacturer of the PST shall make provisions for differential alignments that will occur when two tanks are connected. The foundation tolerance shall be dened by agreement between purchaser and manufacturer. Unless specied otherwise, the PST shall be manufactured for operation in the bypassed state with the source and load bushing connected through bus work. This shall require special consideration in design for lightning impulse and switching surges. This condition will require additional testing with the terminals connected, as in operation, to demonstrate that the insulation level meets the specied BIL.
b)
17
5.3.4 Transient recovery voltages Transient voltage may exist circuit breakers are operated. These conditions may be between the PST and the circuit breaker. 5.3.5 Surge protection Any condition where the PST may operate without surge protection applied at all S and L terminals.
5.4 Protection
The protection scheme recommended for PSTs is similar to that for power transformers with one notable exception: differential relaying. In general, transformer differential relays are designed to allow for a difference between the primary and secondary currents of the transformer of at least 10% because of the voltage taps. This is done by means of restraint windings (or logic) that desensitize the relay during heavy through fault currents. For a PST with a phase angle difference of 25 between the source and load currents, the current difference would be about 43%, so a special differential scheme is required. In 5.4.1, differential schemes for PSTs will be briey discussed with emphasis on the PST requirements. Ground protection is also included because of its close association with differential protection. For a more detailed discussion of differential and ground protection, see Applied Protective Relaying[B1], Brown, et al. [B4], Ibrahim, Stacom [B8], [B9], Li [B13], Plumptre [B22], and Sen, Craig [B23]. Other types of protection are discussed in 5.4.2. 5.4.1 Differential and ground protection The complete current transformer (CT) requirements must be determined and the purchaser must agree to the locations before the design can be nalized since internal buried CTs are often required. Protection schemes are different for the two types of PST core construction: single- and two-core arrangements. 5.4.1.1 Single-core arrangement A differential scheme for the single-core arrangements shown in Figure 7a and Figure 7b should provide primary differential protection that will not misoperate because of PST core saturation. A three-phase transformer differential relay is required with three restraint elements per phase. It is preferable that the CTs have the same ratings and ratios, although the relay can typically compensate for some mismatch. 5.4.1.2 Two-core arrangement The most common differential scheme for the two-core arrangement (see Figure 10) is shown in Figure 14 and Figure 15. There are two sets of differential protection. Figure 14 shows the primary set and Figure 15, the secondary set. The two sets provide differential protection with redundancy. The primary differential relay (Figure 14, 87P) requires a set of CTs in the neutral of the primary winding of the main unit. These will probably be inside the tank. It is preferable that these CTs have the same rating and ratio as the high side CTs, although the differential relay can compensate for some mismatch. This scheme is not affected by PST core saturation. A ground relay (51N1) is usually installed in the neutral of the primary of the main unit to provide sensitive protection for ground faults near the neutral. It will see current during ground faults on the system. The amount of current will depend on the sequence network impedance. If the main unit is of shell form construction, the zero sequence current will be relatively high. However, if it is of core form construction or if the secondary circuits provide a path for zero sequence currents because of voltage regulating windings on the main unit (see Applied Protective Relaying [B1], and Sen, Craig [B23]), the zero sequence impedance will be much lower and 51N1 must coordinate with line side ground relays. The 51N1 relay is also subject to false operation due to inrush current when the main unit is
18
energized. To prevent this from happening, the relay must be desensitized or a relay with second harmonic restraint used (see Plumptre [B22]). The associated CT may be external to the tank. The secondary differential relay (Figure 15, 87S) requires a set of CTs in the neutral of the secondary of the main unit. They will also most likely be inside the tank. The ratio of these CTs will be determined by the ratio (K) of the series unit, as shown in Figure 15. The differential relay can compensate for some CT mismatch. The rating of the CTs should closely match the high side CTs. A three-phase transformer differential relay is required with three restraint elements per phase. The integrity of this scheme depends on the value of K remaining constantthe series unit not saturating. Since the voltage rating of the series unit is considerably smaller than rated phase-to-ground voltage, it is possible that it might saturate during heavy through faults (see Ibrahim, Stacom [B8]). If series unit saturation is a problem, desensitizing the secondary relay system is required. A ground relay (50N2) is usually installed in the neutral of the main unit secondary winding. This relay can be set quite sensitive since there should be current in it only during a fault in the main unit secondary circuit. The associated CT may be external to the tank. 5.4.2 Other types of protection 5.4.2.1 Sudden pressure (rapid rate of rise) relaying Sudden pressure relays protect for arcing faults. It is common practice to have one or more sudden pressure relays for each oil-lled tank and separate compartment, the number of relays depending on the oil volume. The PST manufacturer should recommend the quantity, location, and type of sudden pressure relays and the settings, if not specied by the purchaser. Buchholz relays also will protect for oil displacement. 5.4.2.2 Pressure relief device Each oil-lled tank and separate oil-lled compartment shall be provided with a pressure relief device. It is common practice to have more than one pressure relief device on large tanks. The number of pressure relief devices should be determined by the manufacturer.
19
20
Figure 15Secondary differential relay 5.4.2.3 Gas accumulation relay Gas bubbles generated in the oil will migrate toward the top of the oil compartment. The use of a device to accumulate the gas and cause an alarm or trip is recommended for each compartment.
6. Rating data
In general, rating data for PSTs should be in accordance with the requirements for power transformers as covered in IEEE Std C57.12.00-2000 with the following exceptions or additions.
21
6.2 Impedance
Impedance shall be in accordance with IEEE Std C57.12.00-2000 with the following additions. 6.2.1 General Rated impedance shall be at zero phase-shift connections. 6.2.2 Change in impedance with phase-angle regulation The impedance of PSTs can vary substantially over its range of phase-angle regulation. The user must specify the acceptable ranges of impedances and the manufacturer shall calculate and provide a matrix of impedances as required by the user. The extent of test verication of impedance values other than rated impedance should be specied and agreed upon by the purchaser and manufacturer.
6.3 Nameplates
Nameplates shall be in accordance with IEEE Std C57.12.00-2000 with the following addition: The nameplate of the PST shall show the phase shift in degrees from the S to the L terminals starting at the zero phase-shift tap and for each tap position in the advance and retard direction while operating at no-load. The nameplate shall also show the phase shift in degrees from the S to the L terminals while operating at maximum rated kVA output at unity power factor at the S terminal for all tap positions which result in acceptable service conditions. Intermediary phase shifts at varying loads may be specied by the purchaser for inclusion on the nameplate. The user may request impedance changes be indicated on the nameplate for any tap position.
7. Construction
In general, construction requirements for PSTs should be in accordance with the requirements for power transformers, as covered in IEEE Std C57.12.00-2000 and other applicable IEEE standards based on kV and kVA ratings, with the following exceptions or additions.
22
8. Short-circuit characteristics
8.1 Short circuit requirements
8.1.1 General PSTs shall comply with the short circuit requirements of IEEE Std C57.12.00-2000, unless otherwise agreed upon by the purchaser and manufacturer. 8.1.2 Transformer categories The kVA rating to be considered for determining the category should be the equivalent to the rating according to IEEE Std C57.12.00-2000.
23
8.1.3 Short-circuit current magnitude The manufacturer shall determine the most onerous conditions for short circuit on every winding or active part in accordance with IEEE Std C57.12.00-2000. These conditions should take into account the large impedance swings that can occur as the tap position is changed from the extreme positions to the mid position. Since the system short-circuit levels are critical to the design of PSTs, the user shall specify the maximum system short-circuit fault levels expected throughout the life of the unit. If a short-circuit test is performed, it shall be done in accordance with IEEE Std C57.12.90-1993. The test shall be carried out on the tap position that produces the most severe stresses in each winding. This may require more than a single test depending on the type of construction. For two-core PSTs this usually requires a test on the zero phase-shift position, as this position involves only the series transformer, and a second test on a position to be agreed upon between customer and manufacturer.
9. Control system
9.1 Control equipment and accessories
Control devices to facilitate manual and automatic control of the load tap changing equipment shall be provided. The control system of a PST includes a sensing apparatus to provide a signal proportioned to the system real power ow through the transformer. For this purpose, positive (+) values of power ow relate to an exchange dened as forward power ow (FPF), i.e., power from normal S terminals to normal L terminals. Similarly, negative () values of power ow relate to an exchange dened as reverse power ow (RPF), i.e., power from normal L terminals to normal S terminals. The control system also includes a control device to interpret the input of the sensing apparatus, relate the input to conditions desired by the operator, and to automatically command the tap changer of the PST to function to hold the power ow thereby required. The total control system is usually furnished as a complete package with the transformer; however, the stand-alone nature of the control system makes it appropriate to consider the control system in a unied context. A weather-resistant cabinet shall be provided for housing the automatic control and related devices. The cabinet shall be specied by the user.
9.2 Requirements
9.2.1 Environmental The control must withstand 40 C80 C control enclosure temperature, relative humidity from 0100% and altitude of up to 3000 m without loss of control. 9.2.2 Set point adjustment ranges The default device shall accommodate parameter set point adjustment as follows.
24
a) b) c)
Power ow adjustable from at least 2.0 pu2.0 pu Power ow bandwidth adjustable from at least 0.025 pu0.25 pu Fixed time delay adjustable from 0 s to at least 120 s
NOTEThe base power (1.0 pu power) will be scaled as required based upon the transformer rating.
9.2.3 Accuracy The control system error shall be 1.0% or less. The accuracy is based upon the combined performance of the sensing apparatus (including instrument transformers, transducers, or other means of sensing as required) and the control device. For determining the accuracy of the control system, the percent error is based on the following reference conditions: ambient temperature of 25 C, rated system frequency, no harmonics present on the line, and the PST delivering rated kVA at rated voltage. 9.2.3.1 Accuracy determination criteria The errors to be included in the determination of the accuracy of the control system are the maximum plus (+) error and the maximum minus () error for each of the following. The greater magnitude of the sum of the positive percent errors or the sum of the negative percent errors shall constitute the stated accuracy of the control system. a) Error of the control system due to the ambient temperature. The control system is operated in its intended conguration and environment as pertains to the control enclosure. The use of supplemental control enclosure heaters must be reported, if used. The enclosure temperature is varied in the range of 40 C65 C while holding the transformer kVA and power system frequency at the reference conditions. Error in the control system due to the system frequency. The power system frequency to which the control system sensing apparatus is connected is varied in the range of rated power system frequency 0.25% while holding the transformer kVA and the ambient temperature at reference conditions. Error in the control system due to the power throughput of the PST. The power throughput of the PST to which the sensing apparatus is connected is varied in the range of 2.0 pu2.0 pu (where 1.0 pu is taken as the rated kVA of the PST) while holding the ambient temperature and the power system frequency at the reference conditions.
b)
c)
9.2.3.2 Errors for set point marking deviation of control device The accuracy determination criteria allow for no error in the display of the control device set points. 9.2.4 Ancillary requirements The following ancillary components, accessories, or functionality will be provided as part of the control system. a) Means for display of particular parameters of interest: 1) Phase angle of power system voltage, S terminals relative to L terminals 2) System kVA throughput 3) Power throughput, including direction as forward ow or reverse ow 4) Reactive throughput, including direction as forward ow or reverse ow 5) Tap-changer operations counter 6) Tap-changer tap position Status alarms: 1) Control self-checkdiscrepancy detected
b)
25
c)
2) Tap changer at end of advance tap range 3) Tap changer at end of retard tap range 4) Control system unable to accomplish desired (set point) system power ow Mode selection 1) Off/local manual control/automatic control selector switch 2) Local manual controladvance/retard control switch
26
9.3.2.2 Operational test All features of the control device and its peripherals will be operated and checked for verication of proper functioning. The control is also calibrated at this point.
27
( V SN + V LN V S 1 L 1 ) = arc cos ------------------------------------------------------------( 2 V SN V LN ) The phase angle is advanced if VS1S2 > VS1L2 and retarded if VS1L2 > VS1S2.
(18)
11. Tolerances
11.1 General
The tolerances should be as in IEEE Std C57.12.00-2000, unless otherwise specied here or agreed between purchaser and manufacturer.
28
29
12.2.2 Special overload conditions With respect to 4.8.4 and 5.15.3 of this guide, the required overload condition and the kind of operation (advance or retard phase angle) should be clearly stated. Especially for the retard phase-angle operation, overload requirements may have a large impact on the size of the PST. 12.2.3 Tap-changer requirements The following detailed tap-changer requirements should be specied: The number of load tap-changer positions. The maximum phase shift under load and no-load conditions. Any anticipated short term rating beyond nameplate. The impedance requirements at various tap-changer positions.
See 4.6 for additional details. 12.2.4 Grounding requirements The grounding requirements for the transformer core(s), neutral, and the tank(s) should be specied.
30
31
Annex A
(informative)
Bibliography
[B1] Applied Protective Relaying, Westinghouse Electric Corporation, Coral Springs, Florida, pp. 822, 1982. [B2] Bladow, J., and Montoya, A., Experiences with Parallel EHV Phase Shifting Transformers, IEEE Transactions on Power Delivery, Transaction No. 91 WM 020-8 PWRD, pp. 10961100, Jul. 1991. [B3] Blume, L. F., et al., Transformer Engineering, Ch. XIV. NY: John Wiley & Sons, 1951, pp. 399402. [B4] Brown, F. B, Frere, G. R., Lundquist, T. G., et.al, The First 525 kV Phase Shifting Transformer Conception to Service, Doble Proceedings of the Sixty-Fourth Annual Conference of Doble Clients, 1997. [B5] Central Station Engineers, Electrical Transmission and Distribution Reference Book, 4th ed, Chapter 5, Part XIII, Westinghouse Electric Corp., East Pittsburgh, Pennsylvania, 1964, pp. 122124. [B6] Cochrane, I. C., Effects of Supply, Converter and Load Variabilities on Harmonic Mitigation Using a Phase-Shifting Transformer, Proceedings of the 29th Universities Power Engineering Conference, Sep. 1994. [B7] Haberl, H. W., and Morehouse, C. E., Phase Angle Control Benets Power System Inter-connection, IEEE Conference Paper #CP58-883, Mar. 25, 1958. [B8] Ibrahim, M. A., and Stacom, F. P., Phase Angle Regulating Transformer Protection, IEEE Transactions on Power Delivery, vol. 9, no. 1, pp. 394413, Jan. 1994. [B9] Ibrahim, M. A., and Stacom, F. P., Protection of the East Garden City 345 kV Phase Angle Regulating Transformers, 46th Annual Georgia Tech Protective Relaying Conference, Atlanta, GA, Apr. 29May 1, 1992. [B10] IEEE 100, The Authoritative Dictionary of IEEE Standards Terms, Seventh Edition. [B11] Kraemer, A., and Ruff, J., Transformer for Phase Angle Regulation Considering the Selection of OnLoad Tap-Changers, IEEE Transaction on Power Delivery, vol. 13, no. 2, pp. 518525, Apr. 1998. [B12] Lee, K., and Poon, K., Statistical Switching Overvoltage Analysis of the First B. C. Hydro Phase Shifting Transformer Using the Electromagnetic Transient Program, IEEE Transactions on Power Systems, vol. 5, no. 4, pp. 10541060, Nov. 1990. [B13] Li, H. J., Protective Relaying for Phase Angle Regulator, Western Protective Relay Conference, Spokane, WA, Oct. 2022, 1975. [B14] Linhe, S., and Spencer, L. B., Representation of Phase-Shifting Transformers on AC Network Analyzers, IEEE Transactions on Power Apparatus and Systems, Part III, vol. 80, pp. 374379, Aug. 1961. [B15] MacDonald, J., Current Activities in Flexible AC Transmission Systems, 92-TH0465-5 PWR, Apr. 1992.
32
[B16] MacDonald, J., Present Phase-Angle Regulating Transformer Technology, ABB Power T&D Company, Inc., Muncie, Indiana, Sep. 24, 1991. [B17] March, W. Jr., and Smith, H. S., Parallel Phase Shifters Require Special Protection, Transmission & Distribution, vol. 39, no. 8, pp. 4649, Aug. 1987. [B18] Mihalic, R., and Zunko, P., Phase-Shifting TransformerA Tool for Fast Load Flow Control in Electric Power Systems, Elektrotehniski Vestnik, vol. 62, no. 2, pp. 9196, Feb. 1995. [B19] Mihalic, R., and Zunko, P., Phase-Shifting Transformers with Fixed Phase Between Terminal Voltage and Voltage Boost: Tools for Transient Stability Margin Enhancement, IEEE Proceedings Generating, Transmission and Distribution, vol. 142, no. 3, pp. 257262, May 1995. [B20] Patel, B. K., Smith, H. S., Hewes, T. S., Jr., Marsh, W. J., Application of Phase Shifting Transformers for Dainiel-McKnight 500-kV Interconnection, IEEE Transactions on Power Delivery, vol. PWRD-1, no. 3, pp. 167173, Jul. 1986. [B21] Phase Shifters Control Power FlowsElectrical World, vol. 179, no. 3, NY: McGraw-Hill Inc., Feb. 1, 1973, p. 48. [B22] Plumptre, P. F., Nelway Substation Phase Shifting Transformer Protection, Western Protective Relay Conference, Spokane, WA, p. 5, Oct. 2325, 1990. [B23] Sen, P. K., and Craig, B. R., Application and Protection Considerations of Large Phase Shifting Transformers, Proceedings of the American Power Conference, vol. 51, pp. 7, 442447, Apr. 1989. [B24] Trummer, E. R., Phase-Shifting Transformer Principles, APDA Meeting, May 2, 1995. [B25] Trummer, E. R., Transformers Principles, PEA Electrical Equipment Committee Presentation, Winter 1995 Meeting, Feb. 1995. [B26] Xing, K., and Kusic, G., Damping Subsynchronous Resonance by Phase Shifters, IEEE Transactions on Energy Conversion, vol. 4, issue 3, pp. 344350, Sept. 1989.
33
34