General
Four different monitor modules are available for Notifiers intelligent control panels for a variety of applications. Monitor modules supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (FZM-1). FMM-1 is a standard-sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Class A (Style D) or Class B (Style B) circuit of dry-contact input devices. FMM-101 is a miniature monitor module (a mere 1.3" (3.302 cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D) that supervises a Class B (Style B) circuit of dry-contact input devices. Its compact design allows the FMM-101 to often be mounted in a single-gang box behind the device it monitors. FZM-1 is a standard-sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Class A (Style D) or Class B (Style B) circuit. FDM-1 is a standard-sized dual monitor module that monitors and supervises two independent two-wire Style B (Class B) dry-contact initiating device circuits (IDCs) at two separate, consecutive addresses in intelligent, two-wire systems. FlashScan (U.S. Patent 5,539,389) is a communication protocol developed by NOTIFIER that greatly increases the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs. protocols.
M ar
tn
FMM-1 (Type H)
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit.
FMM-1 OPERATION
Each FMM-1 uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop).
Built-in type identification automatically identifies this device as a monitor module to the control panel. Powered directly by two-wire SLC loop. No additional power required. High noise (EMF/RFI) immunity. SEMS screws with clamping plates for ease of wiring. Direct-dial entry of address: 01 159 on FlashScan systems; 01 99 on CLIP systems. , 01 99 on . LED flashes green during normal operation (this is a programmable option) and latches on steady red to indicate alarm. The FMM-1 Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. The FMM-1 can be used to replace MMX-1 modules in existing systems.
FMM-1 SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.0 mA (LED on). Maximum operating current: 375 A (LED flashing). Maximum IDC wiring resistance: 1,500 ohms. EOL resistance: 47K ohms. Temperature range: 32F to 120F (0C to 49C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box.
FMM-1 APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normallyopen dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class
6999cov.jpg
LED flashes during normal operation; this is a programmable option. LED latches steady to indicate alarm on command from control panel. The FZM-1 Interface Module is intended for use in intelligent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two-wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with the module. The FZM-1 can be used to replace MMX-2 modules in existing systems.
FMM-101 APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the circuit.
FMM-101 OPERATION
Each FMM-101 uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC).
FMM-101 SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC. Maximum operating current: 375 A. EOL resistance: 47K ohms.
Temperature range: 32F to 120F (0C to 49C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.65" (1.651 cm) deep. Wire length: 6" (15.24 cm) minimum.
The FMM-101 Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The FMM-101 is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiating device circuit for normally-open-contact fire alarm and security devices. The FMM-101 can be used to replace MMX-101 modules in existing systems.
FZM-1 OPERATION
Each FZM-1 uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop).
FZM-1 SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum IDC wiring resistance: 25 ohms. Maximum operating current: 270 A (LED flashing). EOL resistance: 3.9K ohms. External supply voltage (between Terminals T3 and T4): DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms maximum. Current: 90 mA per module maximum. Temperature range: 32F to 120F (0C to 49C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box.
FDM-1 SPECIFICATIONS
Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 6.4 mA (LED on). Maximum operating current: 750 A (LED flashing). Maximum IDC wiring resistance: 1,500 ohms.
M ar
tn
6720m101.wmf
FZM-1 APPLICATIONS
Use the FZM-1 to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 ohms). Install ELR across terminals 8 and 9 for Style D application.
EOL resistance: 47K ohms. Temperature range: 32 to 120F (0 to 49C). Humidity range: 10% to 93% (non-condensing). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 2.125" (5.398 cm) deep.
Installation
FMM-1, FZM-1, and FDM-1 modules mount directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installation instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regulations. These modules are intended for power-limited wiring only.
The FMM-101 module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations.
In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S635 ULC: S3705 FM Approved CSFM: 7300-0028:202 MEA: 457-99-E, 457-99-E Vol. 3, 143-01-E U.S. Coast Guard: 161.002/23/3 (AFP-200: FMM-1/-101, FZM-1) 161.002/42/1 (NFS-640: FMM-1/-101) Lloyds Register: 03/60011/E1 (FMM-1/-101, FZM-1) 94/60004/E2 (AFP-200: except FDM-1) 02/60007 (NFS-640: FDM-1)
FMM-1(A): Monitor module. FMM-101(A): Monitor module, miniature. FZM-1(A): Monitor module, two-wire detectors. FDM-1(A): Monitor module, dual, two independent Class B circuits. SMB500: Optional surface-mount backbox.
NOTE: See installation instructions and refer to the SLC Wiring Manual, PN 51253.
M ar
tn
This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com
Page 4 of 4 dn-6720:B 01/21/09