Type PRS Programmable Resettable Sectionalizer Single-Phase: Section
Type PRS Programmable Resettable Sectionalizer Single-Phase: Section
Type PRS Programmable Resettable Sectionalizer Single-Phase: Section
10DDD
Section
NOTE: Hubbell has a policy of continuous product improvement. We reserve the right to change design and specifications without notice.
Copyright 2011 & 2012 HubbellIncorporated210 North Allen StreetCentralia, MO 65240-1395 USA CHANCECENTRALIA, MISSOURI JANUARY 2012 Printed in USA
H U B B E LL
Power Systems
10DDD-2
Traditional Coordination
FUSE CURVE (25T)
TIME TIME
TIME TIME
800
100
COORDINATION RANGE
CURRENT CURRENT
CURRENT CURRENT
Figure 1. Addition of the CRS eliminates the fuse curve and extends the coordination range.
H U BBE LL
Power Systems
10DDD-3
Application The Type PRS electronic sectionalizer is best suited for use in the following applications: Locations where fuse coordination is difficult to achieve Areas with insufficient load to justify investments in apparatus such as reclosers Remote locations prone to transient faults caused by fauna and/or flora SAIDI improvements Benefits Improves system reliability Distinguishes between permanent and transient faults to reduce outages Programmable parameters: Counts, actuating current, reset time One programmable unit to meet all needs per specific voltage class Historical data storage for system overview and analysis Resettable
Drop-open operation is the same for both types of the PRS electronic sectionalizer: Standard (left) and Loadbreak (right, with Arc Chute interrupter). See following pages for specifications and ordering information.
Operation
The power required for the logic circuit of the Type PRS electronic sectionalizer is obtained from the built-in current transformer. When a fault occurs, which exceeds the minimum actuating current of the sectionalizer, the logic circuit will power-up. The upstream recloser opens the circuit causing the line current to fall below the dead line threshold. The logic circuit recognizes this as a count and stores this occurrence in its memory for two minutes. In doing so, the Type PRS merely counts the backup reclose operations. After a predetermined number of such operations, the Type PRS isolates the circuit while the back-up recloser is in the open position. The recloser is then allowed to close, restoring service to the unfaulted sections of the system. If the fault is temporary and is cleared before the sectionalizer count reaches the predetermined number, the sectionalizer remains closed and resets to its original state after its reset time expires.
H U B B E LL
Power Systems
10DDD-4
Continuous Current:
The sectionalizer must have a continuous current rating equal to or greater than the anticipated system load current plus overload. Where hydraulic reclosers are used, the continuous current rating of the sectionalizer is typically equal to the continuous current rating of the upstream automatic circuit recloser.
reclosers continuous current ratings. The sectionalizers minimum actuating current is 160% of its continuous current rating and the hydraulic reclosers phase pick-up is 200% of its continuous current rating (160/200=.80). (Table A).
Typical Sectionalizer Ratings Minimum Actuating Current, Amps 10% 24 40 56 80 112 160 224 320 Continuous Current, Amps 15 25 35 50 70 100 140 200
The minimum actuating current of sectionalizers should be 80% of the phase minimum trip of the source side single-phase automatic circuit recloser (ACR). Where three-phase reclosers or circuit breakers are used, a user may want to coordinate sectionalize actuating current with the ground trip rating. Where hydraulic reclosers are used, this is easily accomplished by matching the sectionalizer and the
The sectionalizer should be set to operate in at least one less count than the backup recloser. Example: a 4-shot recloser would require a maximum of a 3-count sectionalizer downstream (Figure 2, line A). In case of a 2-fast/2-slow reclose setting, a 2-count sectionalizer may be used to reduce the number of recloser operations (Figure 2, line B). Where sectionalizers are used in series, the downstream sectionalizer should have one less count than the upstream sectionalizer (Figure 3).
Number of Counts:
PRS
PRS
Figure 2. Typical distribution system with Type PRS two- and three-count electronic resettable sectionalizers.
H U BBE LL
Power Systems
10DDD-5
Rated Continuous Current Minimum Actuating Current Number of Counts: Reset time:
Inrush detection time Types of inrush currents detected: Method of inrush currents detection: Deadline detection: Total execution time: Short time current withstand, 15 cycle: 1 second: 3 seconds: 10 seconds: Momentary current rating: *Current measurement accuracy: Temperature range: Maximum Thermal Rating: Surge current withstand Electromagnetic interference Radio frequency interference USB port
* With 5% accuracy, if the unit is programmed for 50 A actuating current, then the unit will pick-up the count at 52.5 A and above but ignore a count at 47.5 A and below.
H U B B E LL
Power Systems
10DDD-6
Event Log
The programmable sectionalizer contains onboard memory storage that will record the last 8 events the unit has seen. Users will be able to download the event log via the USB port and have access to the measured fault current, number of counts, and deadline current.
H U BBE LL
Power Systems
10DDD-7
USB port
Latching Device
Trunnion
Cutout Terminal Connectors P =Parallel-groove E =Small eyebolt L =Large eyebolt T=Electronic Module Only
Position 9:
CP7 4 00 1 PP L
Cutout Insulation Level 1 = 15kV, 110kV BIL 2 = 27kV, 125kV BIL (Non-loadbreak only) 15/27kV, 125kV BIL (Loadbreak only)
B
Ideal for use with Standard Electronic Sectionalizer to easily lift out, place, *open and close. Inverted, secure method also fits 100 amp fuse holders of ABB, Chance, S&C cutouts.
Position 6:
Cutout Bracket Z=No bracket B=NEMA B bracket D=D bracket X=Extended bracket Blank = Electronic Module Only
Position 10:
Examples: To order 27kV Polymer cutout programmable sectionalizer with extended bracket and large eyebolt connectors = CP74002PPLX. To order 27kV programmable sectionalizer module only = C74002PPT.
Cat. No. PSC4033484 (Wt. 4 oz.) See Tools Catalog Section 2100. *When opening a cutout, follow all work rules and OSHA regulations. Not for use with Loadbreak cutouts.
To order programmable sectionalizer module only, replace "CP7" with "C7" followed by selections for Positions 3 through 9.
H U B B E LL
Power Systems
10DDD-8
USB port
Latching Device
Trunnion
Cutout Terminal Connectors P =Parallel-groove E =Small eyebolt L =Large eyebolt T=Electronic Module Only
Position 9:
C7
4 00 1 PP L
Cutout Insulation Level
B
Ideal for use with Standard Electronic Sectionalizer to easily lift out, place, *open and close. Inverted, secure method also fits 100 amp fuse holders of ABB, Chance, S&C cutouts.
Position 6:
1 = 15kV, 110kV BIL 2 = 27kV, 125kV BIL (Non-loadbreak only) 15/27kV, 125kV BIL (Loadbreak only) 3 = 38kV, 150kV BIL (Non-loadbreak only) 6 = 38kV, 170kV BIL (Non-loadbreak only)
Cutout Bracket Z=No bracket B=NEMA B bracket D=D bracket X=Extended bracket Blank = Electronic Module Only
Position 10:
Examples: To order 38kV, 170kV BIL Porcelain cutout programmable sectionalizer with extended bracket and large eyebolt connectors = C74006PPLX. To order 38kV, 170kV BIL programmable sectionalizer module only = C74006PPT. CHANCECENTRALIA, MISSOURI JANUARY 2012
Cat. No. PSC4033484 (Wt. 4 oz.) See Tools Catalog Section 2100. *When opening a cutout, follow all work rules and OSHA regulations. Not for use with Loadbreak cutouts.
H U BBE LL
Power Systems
10DDD-9
Terminal Connectors
Accessories
Description Catalog No. T7001325 Parallel-Groove Clamp, tin-plated bronze for No. 6 solid thru 4/0 ACSR or 250 kcmil stranded T7001326 Small Eyebolt for No. 8 solid thru 2/0 stranded T7001327 Large Eyebolt for No. 6 solid thru 4/0 ACSR or 250 kcmil stranded
Wt. (lb./kg.) Min. Order Qty. 10 0.33 / 0.15 10 0.16 / 0.07 10 0.40 / 0.14 2.84 / 1.29 3.75 / 1.70 7.67 / 3.48 4.00 / 1.81
Mounting Brackets
C2060283 C2060280 C2060299 C2060632 NEMA Heavy Duty B Bracket with 11/2" captive bolt for crossarm mounting Extended Crossarm Bracket (Horizontal section is 25/8" longer than NEMA B bracket) D Pole Mounting Bracket Cutout/Arrester Bracket complete with carriage bolts and backstrap