MasterPack Catalog
MasterPack Catalog
MasterPack Catalog
Masterpact
NT and NW
Universal Power Circuit Breakers
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
MASTERPACT
CIRCUIT BREAKERS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
MICROLOGIC
NT DIMENSIONAL DRAWINGS . . . . . . . . . . . . . . . . . . 67
MASTERPACT
NW DIMENSIONAL DRAWINGS. . . . . . . . . . . . . . . . . . 95
SELECTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
TRIP CURVES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Catalog
2004
Building a New Electric World
Masterpact
Circuit Breakers
3
11/2004 19992004 Schneider Electric All Rights Reserved
SECTION 1MASTERPACT
CIRCUIT BREAKERS
INTRODUCTION............................................................................................................................................ 4
CODES AND STANDARDS........................................................................................................................... 4
FEATURES AND BENEFITS......................................................................................................................... 5
OPERATING CONDITIONS........................................................................................................................... 7
MASTERPACT NW CIRCUIT BREAKER DESIGN....................................................................................... 8
MASTERPACT NW CRADLE DESIGN ......................................................................................................... 9
MASTERPACT NT CIRCUIT BREAKER AND CRADLE DESIGN.............................................................. 10
RATINGS ..................................................................................................................................................... 11
CORRECTION FACTORS........................................................................................................................... 15
SHIPPING WEIGHTS .................................................................................................................................. 16
4
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact
Circuit BreakersIntroduction
INTRODUCTION
Masterpact
70E.
Circuit breakers should be applied according to guidelines detailed in the National Electrical Code
(NEC
Extreme Atmospheric
Conditions
ANSI C37.13
ANSI C37.16
ANSI C37.17
ANSI C37.50
UL 1066 (cULus Listed)
NEMA SG3
UL 489 (UL Listed)
NEMA AB1
CSA 22.2 NO 5.1
NMX J-266-ANCE
IEC 60947-2
IEC 60947-3
IEC 68-2-1: Dry cold at 55C
IEC 68-2-2: Dry heat at +85C
IEC 68-2-30: Damp heat
(temp. +55C, rel. humidity 95%)
IEC 68-2-52 Level 2: Salt mist
8001600 A Masterpact NT
Drawout Circuit Breaker
NX 08 HA10
Ui 1000V Uimp 12kV
Ue 690(V)
50kA/1s
IEC 947-2 50/60Hz
EN 60947-2 UTE VDE BS CEI UNE AS NBMA
0
6
1
3
3
4
6
8
0
6
1
3
3
4
6
9
8003200 A Masterpact NW Drawout Circuit Breaker
40006300 A Masterpact NW Drawout Circuit Breaker
Masterpact
Circuit BreakersRatings
11
11/2004 19992004 Schneider Electric All Rights Reserved
RATINGS
Table 1: Ratings for ANSI C37 Certified Masterpact NW Circuit Breakers
Frame Rating 800/1600 A 2000 A 3200/4000 A
4
4000/5000 A
Interrupting Rating Code N1 H1 H2 H3 L1
L1F H1 H2 H3 L1
L1F H1 H2 H3 L1
H2 H3 L1
85 35
24 85 35 24 85 117 117
Close and Latch Ratings (kA
RMS)
Vac 50/60 Hz 42 65 40 40 25 22 65 40 40 25 22 65 40 40 40 85 75 40
Tested to show arc flash hazard risk
category as referenced by NFPA70E
Yes Yes
Breaking Time 25 to 30 ms with no intentional delay (9 ms for L1 and L1F)
Closing Time 70 ms
Sensor Rating
100 to 800 A
800 to 1600 A
1000 to 2000 A 1600 to 4000 A
2000 to 4000 A
2500 to 5000 A
Endurance Rating (C/O cycles)
(with no maintenance)
Mechanical 12,500 10,000 10,000 5000 5000
Electrical 2800 1000 1000 1000 1000
4
4000 A standard width circuit breaker is not available in L1 interrupting rating code (see dimensions on page 107)
Interrupting ratings (kAIR RMS) at 50 Hz: 200 kA (254 Vac), 150 kA (508 Vac), 100 kA (635 Vac)
24 kA RMS for 800 A circuit breaker frame with 100 A or 250 A sensor
Table 2: Ratings for ANSI C37 Certified Masterpact NW Non-Automatic Switches
Frame Rating 800 A 1600 A 2000 A 3200 A 4000 A 5000 A
Withstand Rating Code HA HA HA HA HA HA
Breaking Capacity with
External Relay (kA RMS)
Vac, 50/60 Hz
254 65 65 65 65 85 85
508 65 65 65 65 85 85
635 65 65 65 65 85 85
Short-time Withstand current
(kA RMS) Vac 50/60 Hz, 1 s
65 65 65 65 85 85
Table 3: Ratings for ANSI C37 Certified Masterpact NW Automatic Switches
Frame Rating 800 A 1600 A 2000 A 3200 A 4000 A 5000 A
Withstand Rating Code HF HC HF HC HF HC HF HC HF HC HF HC
Breaking Capacity with
External Relay (kA RMS)
Vac, 50/60 Hz
254 100 200 100 200 100 200 100 200 100 200 100 200
508 100 200 100 200 100 200 100 200 100 200 100 200
635 85 130 85 130 85 130 85 130 85 130 85 130
Short-time Withstand current
(kA RMS) Vac 50/60 Hz, 1 s
85 30 85 30 85 30 85 100 85 100 85 100
12
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact
Circuit BreakersRatings
Table 4: Ratings for UL 489 Listed Masterpact NW Circuit Breakers
Frame Rating 800/1200/1600/2000 A 2500/3000 A 4000/5000/6000 A
Interrupting Rating Code N H L LF H L H L
Interrupting Current (kAIR RMS)
240 Vac 50/60 Hz
480 Vac 50/60 Hz
600 Vac 50/60 Hz
65
65
50
100
100
85
200
150
100
200
150
100
100
100
85
200
150
100
100
100
85
200
150
100
Short-time Withstand Current
(kA RMS)
ac 50/60 Hz, 1 s 42
4
65
4
30
O4
22 65 65 85 100
Built-in Instantaneous Override
(kA RMS 10%)
40 40 35
O4
24 65 65 75 75
Close and Latch Ratings (kA RMS) ac 50/60 Hz 40 40 25
22 40 40 40 40
Tested to show arc flash hazard risk category
as referenced by NFPA70E
Yes
Breaking Time 25 to 30 ms with no intentional delay (9 ms for L and LF)
Closing Time 70 ms
Sensor Rating
100 to 250 A / 400 to 800 A / 600 to 1200 A / 800 to
1600 A / 1000 to 2000 A
1200 to 2500 A /
1600 to 3000 A
2000 to 4000 A / 2500 to
5000 A / 3000 to 6000 A
Endurance Rating (C/O cycles)
(with no maintenance)
Mechanical 12,500
O
12,500
O
12,500
O
12,500
O
10,000 10,000 5000 5000
Electrical 2800
O
2800
O
2800
O
2800
O
1000 1000 1000 1000
4
24 kA RMS for 800 A circuit breaker frame with 100 A or 250 A sensor.
O
65 kA RMS for 2000 A
Circuit BreakersRatings
13
11/2004 19992004 Schneider Electric All Rights Reserved
Table 6: Ratings for IEC 60947-2 Rated Masterpact NW Circuit Breakers
Frame rating 800/1000/1250/1600 A 2000 A 2500/3200/4000 A 5000/6300 A
Interrupting Rating Code N1 H1 H2 L1 H10 H1 H2 H3 L1 H10 H1 H2 H3 H10 H1 H2
Ultimate
Breaking
Capacity (kA
RMS)
50/60 Hz
I
cu
220/415 Vac
440 Vac
525 Vac
690 Vac
1150 Vac
42
42
42
42
65
65
65
65
100
100
85
85
150
150
130
100
50
65
65
65
65
100
100
85
85
150
150
130
100
150
150
130
100
50
65
65
65
65
100
100
85
85
150
150
130
100
50
100
100
100
100
150
150
130
100
Service Breaking
Capacity
I
cs
%Icu 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Short-time
Withstand
Current
(kA RMS)
I
cw
Vac 50/60 Hz, 1 s
Vac 50/60 Hz, 3 s
42
22
65
36
85
50
30
30
50
50
65
36
85
75
65
65
30
30
50
50
65
65
85
75
65
65
50
50
100
100
100
100
Built-in Instantan-eous Override
(kA RMS 10%)
85
4
35
4
85 65 35 85 65 117
Close and Latch
Ratings (kA
RMS)
50/60 Hz
I
cm
220/415 Vac
440 Vac
525 Vac
690 Vac
1150 Vac
38
38
38
38
62
62
62
62
96
96
81
81
143
143
124
96
46
62
62
62
62
96
96
81
81
143
143
124
96
143
143
124
96
46
62
62
62
62
96
96
81
81
143
143
124
96
46
96
96
81
81
143
143
124
96
Break Time ms 25 25 25 25
Closing Time ms < 70 < 70 < 70 < 80
Endurance Rating
(with no maint.)
C/O cycles x 1000
Mechanical 12.5 10 10 5
Electrical 440 V 10 10 10 3 8 8 3 3 5 5 1.25 1.5 1.5
Electrical 1150 V 0.5 0.5 0.5
4
24 kA RMS for 800 A circuit breaker frame with 100 A or 250 A sensor.
Table 7: Ratings for IEC 60947-3 Rated Masterpact NW Switches
Frame Rating 800/1000/1250/1600 A 2000 A 2500/3200/4000 A 5000/6300 A
Withstand Rating Code
46
46
46
81
81
81
46
46
46
46
81
81
81
46
53
53
53
53
81
81
81
46
81
81
81
Short-time Withstand
Current (kA RMS)
I
cw
Vac 50/60 Hz, 1 s 42 50 85 50 50 85 50 50 85 50 85
Ultimate Breaking
Capacity
(with external protection
relay) (kA RMS)
I
cu
maximum delay 350
ms
42 50 85 50 50 85 50 50 85 50 85
Circuit BreakersRatings
Table 8: Ratings for ANSI C37 Certified Masterpact NT Circuit Breakers
Frame Rating 800 A 800 A
Interrupting Rating Code N1 H1
Interrupting Current (kAIR RMS)
254 Vac 60 Hz
508 Vac 60 Hz
635 Vac 60 Hz
42
42
N/A
42
42
22
Short-time Withstand Current (kA RMS) ac 60 Hz, 0.5 s 42 42
Built-in Instantaneous Override
(kA RMS 10%)
Close and Latch Ratings (kA RMS) ac 60 Hz 40 40
Tested to show arc flash hazard risk category as referenced by NFPA70E
Breaking Time 25 to 30 ms (with no intentional time delay)
Closing Time < 50 ms
Sensor Rating 100 to 250 A / 400 to 800 A
Endurance Rating (C/O cycles)
(with no maintenance)
Mechanical 12,500
Electrical 2800
Table 9: Ratings for ANSI C37 Certified Masterpact NT Non-Automatic Switches
Frame Rating 800 A 800 A
Withstand Rating Code NA HA
Short-time Withstand Current Rating (kA RMS) Vac 50/60 Hz, 0.5 s 42 42
Breaking Capacity (with external protection relay) (kA RMS) 254/508/635 Vac, 60 Hz 42/42/NA 42/42/22
Table 10: Ratings for UL 489 Listed Masterpact NT Circuit Breakers
Frame Rating 800 A 1200 A 1600 A
Interrupting Rating Code N H L1 L LF N H L1 L LF N H L1 L
Interrupting Current (kAIR RMS)
240 Vac, 60 Hz
480 Vac, 60 Hz
600 Vac, 60 Hz
50
50
35
65
50
50
100
65
N/A
200
100
N/A
200
100
N/A
50
50
35
65
50
50
100
65
N/A
200
100
N/A
200
100
N/A
50
50
35
65
50
50
100
65
N/A
200
100
N/A
Short-time Withstand Current Rating (kA
RMS)
ac 60 Hz, 0.5 s 35 35 10 10 10 35 35 10 10 10 35 35 10 10
Built-in Instantaneous Override
(kA RMS 10%)
40 40 10 10 10 40 40 10 10 10 40 40 10 10
Close and Latch Ratings (kA RMS) ac 60 Hz 25 25 10 10 10 25 25 10 10 10 25 25 10 10
Tested to show arc flash hazard risk category
as referenced by NFPA70E
Yes Yes
Breaking Time
25 to 30 ms (with no intentional time delay)
9 ms for L and LF
Closing Time < 50 ms
Sensor Rating 100250 A / 400800 A 6001200 A 8001600 A
Endurance Rating (C/O cycles)
(with no maintenance)
Mechanical 12,500
Electrical 2800
Table 11: Ratings for UL 489 Listed Masterpact NT Automatic Switches
Frame Rating 800 A 1200 A 1600 A
Withstand Rating Code HF HB HF HB HF HB
Withstand Rating
44
(kA RMS) Vac, 50/60 Hz
240
480
600
65
50
50
200
100
NA
65
50
50
200
100
NA
65
50
50
200
100
NA
Instantaneous Override (kA RMS) 40 10 40 10 40 10
44
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit breaker with an equal
continuous current rating.
Masterpact
150
130
100
25
42
42
42
42
143
124
96
23
38
38
38
38
Break Time ms 25 9 25
Closing Time ms 50 50 50
Endurance Rating (C/O cycles)
(with no maintenance)
Mechanical 12,500 12,500 12,500
Electrical 440 V 6000 3000 6000
4
Electrical 1000 V
SELLIM system
4
1600 A, 3000 cycles
Table 13: Ratings for IEC 60947-3 Rated Non-Automatic Masterpact NT Switches
Frame Rating 800/1000 A 1250/1600 A
Withstand Rating Code HA HA
Close and Latch Rating (kA RMS) I
cm
220/415 Vac, 50/60 Hz
440 Vac, 50/60 Hz
500/690 Vac, 50/60 Hz
1000 Vac, 50/60 Hz
33
33
33
33
33
33
40/18 52/24 N/A N/A RCTV 18/8 20/9 10/5 104/47 125/57
4
Fixed circuit breaker weight = total weight cradle weight.
3.0
3.0A
5.0
5.0A
5.0P
5.0H
6.0A
6.0P
6.0H
Figure 5: P Trip Unit with Power Metering
Masterpact
X X X
Ground-fault alarm/no trip
4
X X
Ground-fault alarm and trip
4
X X
Adjustable rating plugs X X X X X X X X X X X
True RMS sensing X X X X X X X X X X X
UL Listed X X X X X X X X X
Thermal imaging X X X X X X X X X X X
Phase-loading bar graph X X X X X X X X
LED for long-time pick-up X X X X X X X X X X X
LED for trip indication X X X X X X X X
Digital ammeter X X X X X X X X
Zone-selective interlocking
X X X X X X X
Communications O O O O X X X X
LCD dot matrix display X X X X
Advanced user interface X X X X
Protective relay functions X X X X
Neutral protection
X X X X
Contact wear indication X X X X
Incremental fine tuning of settings X X X X
Selectable long-time delay bands X X X X
Power measurement X X X X
Power quality measurements X X
Waveform capture X X
Requires neutral current transformer on three-phase four-wire loads.
Electronic Trip SystemsMicrologic 2.0, 3.0, and 5.0 Basic Trip Units
MICROLOGIC 2.0, 3.0, and 5.0 BASIC TRIP UNITS
The Micrologic 2.0, 3.0, and 5.0 trip units protect power circuits.
Protection Settings
1Overload signal (LED)
2Long-time rating plug
screw
3Long-time current setting
and tripping delay
4Instantaneous pickup
5Short-time pickup and
tripping delay
6Test connector
Protection thresholds and delays are set using the rotary switches.
A full-range of long-time settings are available via field-installable
adjustable rating plugs.
Overload protection
True RMS long-time protection
Thermal imaging: Active thermal imaging before and after tripping
Short-circuit protection.
Short-time RMS
Selection of I
2
t type (ON or OFF) for short-time delay
Instantaneous protection.
Neutral protection on four-pole circuit breakers.
3
5
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
2
4
6
.5
1
2
4
8
12
16
20
tr
(s)
@6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
3
4
6
8
10
12
15
off 2
test
1
Micrologic 5.0
0
6
1
3
3
2
5
3
Micrologic
Electronic Trip SystemsMicrologic 2.0A, 3.0A, 5.0A, & 6.0A Trip Units with Ammeter
23
11/2004 19992004 Schneider Electric All Rights Reserved
MICROLOGIC
2.0A, 3.0A, 5.0A, & 6.0A TRIP UNITS WITH AMMETER
Micrologic A trip units protect power circuits and provide current measurements, overload protection,
and short-circuit protection. In addition, the 6.0A trip units also provide ground-fault protection for
equipment.
Protection Settings
Ammeter Measurements
Micrologic
A trip units measure the true RMS value of currents. They provide continuous current
measurement from 0.2 to 20 x I
n
with an accuracy of 1.5% (including sensors). No auxiliary source is
needed where I > 0.2 x I
n
. The optional external power supply (24 Vdc) makes it possible to display
currents where I < 0.2 x I
n
and to store values of the interrupted current. A digital LCD screen
continuously displays the most heavily loaded phase (Imax) or displays the Ia, Ib, Ic, Ig, and (on 4-pole
circuit breakers only) In stored current and setting values by successively pressing the navigation button.
Communication Network
Four wire, RTU, RS485
In conjunction with an optional communication network, the trip unit transmits the following parameters:
Setting values.
All ammeter measurements.
Tripping causes.
NOTE: Current-based protection functions require no auxiliary power source. When an external power
supply is added, the value of the interrupted current is stored by the trip unit. The reset button resets
alarms, and stored interrupted current indications.
1Test lamp and reset
2Indication of tripping
cause
3Digital display
4Three-phase bar graph
and ammeter
5Navigation buttons
6Overload signal (LED)
7Long-time rating plug
screw
8Long-time current setting
and tripping delay
9Short-time pickup and
tripping delay
10Instantaneous pickup
11Electronic push-to-trip
12Ground-fault pickup and
tripping delay
13Test connector
Protection thresholds and delays are set using the rotary switches. The
selected values are momentarily displayed in amperes and in seconds.
A full-range of long-time settings are available via field-installable rating
plug.
Overload protection (true RMS long-time protection).
Thermal imaging (active thermal imaging before and after tripping).
Short-circuit protection.
Short-time RMS
I
2
t ON or OFF for short-time delay
Instantaneous protection.
Ground-fault protection for equipment.
Residual ground-fault protection for equipment
Source ground-return ground-fault protection for equipment
Modified differential ground-fault protection (MDGF) for
equipment
Neutral protection on four-pole circuit breakers.
ZSI: Zone-selective interlocking (a ZSI terminal block may be used to
interconnect a number of trip units to provide total discrimination for
short-time and equipment ground-fault protection, without delay for
tripping). Not available for 3.0 A trip unit. Not available for 2.0 A trip
unit if installed as upstream device.
Micrologic 6.0 A
40
100%
%
menu
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
ground fault
B
C
D
E
F
G
H
J
Ig tg
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
A
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
test
2
4
10
3
6
8
12
15
off
kA
s
Ir= Ii=
tr=
Isd=
Ig=
tsd=
t=
tg=
In=
MAX
2
11
10
12
7
8
5
9
6
3
4
1
13
0
6
1
3
3
2
5
4
Micrologic
Electronic Trip SystemsMicrologic 2.0A, 3.0A, 5.0A, & 6.0A Trip Units with Ammeter
0 I
t
I
r
t
r
I
i
0
6
1
3
3
3
2
4
Table 23: Micrologic 2.0A and 3.0A Trip Unit Settings
Long-time
Protection
Current setting (A)
Tripping between 1.05
and 1.20 x I
r
I
r
= l
n
x...
2.0A: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
3.0A: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
Other ranges are available by changing rating plug
Maximum time delay (s)
Accuracy: 0 to 20%
t
r
at 1.5 x I
r
12.5 25 50 100 200 300 400 500 600
t
r
at 6 x I
r
0.5 1 2 4 8 12 16 20 24
t
r
at 7.2 x I
r
0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal imaging 20 minutes before or after tripping
Short-time
Protection
Current setting (A)
Accuracy: 10%
No delay
I
sd
= I
r
x... 2.0A: 1.5 2 2.5 3 4 5 6 8 10
Instantaneous
Protection
Current setting (A)
Accuracy: 10%
I
i
= I
n
x... 3.0A: 1.5 2 3 4 5 6 8 10 12
I
r
t
r
l
sd
t
sd
l
i
0 I
t
0
6
1
3
3
3
2
5
Table 24: Micrologic 5.0A and 6.0A Trip Unit Settings
Long-time
Protection
Current setting (A)
Tripping between 1.05
and 1.20 x I
r
I
r
= l
n
x...
IEC: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
UL/ANSI: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
Other ranges are available by changing rating plug
Maximum time delay (s)
Accuracy: 0 to 20%
t
r
at 1.5 x I
r
12.5 25 50 100 200 300 400 500 600
t
r
at 6 x I
r
0.5 1 2 4 8 12 16 20 24
t
r
at 7.2 x I
r
0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal imaging 20 minutes before or after tripping
Short-time
Protection
Current setting (A)
Accuracy: 10%
l
sd
= I
r
x... 1.5 2 2.5 3 4 5 6 8 10
Maximum time delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
sd
Min. trip
time (ms)
20 80 140 230 350
Max. trip
time (ms)
80 140 200 320 500
Instantaneous
Protection
Current setting (A)
Accuracy: 10%
I
i
= I
n
x... 2 3 4 6 8 10 12 15 off
0 I
t
l
g
t
g
I
2
t off
I
2
t on
0
6
1
3
3
3
2
6
Table 25: Micrologic 6.0A Trip Unit Ground-fault Settings
Ground-fault pickup (A)
Accuracy: 10%
I
g
= l
n
x... A B C D E F G H J
l
n
400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
400 A < l
n
1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
l
n
> 1200 A 500 640 720 800 880 960 1040 1120 1200
Maximum time delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
g
Minimum trip time (ms) 20 80 140 230 350
Maximum trip time (ms) 80 140 200 320 500
Masterpact
Electronic Trip SystemsMicrologic 5.0P & 6.0P Trip Units with Power Metering
25
11/2004 19992004 Schneider Electric All Rights Reserved
MICROLOGIC 5.0P & 6.0P TRIP UNITS WITH POWER METERING
Protection Settings
Configuring Alarms and Other Protection Functions
When the cover is closed, the keypad may no longer be used to change the protection settings, but it
still provides access to the displays for measurements, histories, indicators, etc. Depending on the
thresholds and time delays set, the Micrologic P trip unit monitors current, voltage, power, frequency,
and phase sequence. Each threshold overrun may be signalled remotely via the communication
network.
Each threshold overrun may be combined with tripping (protection) or an indication carried out by an
optional M2C/M6C programmable contact (alarm), or both (protection and alarm).
Maintenance Record
The maintenance record can be consulted using the full-function test kit or remotely via the
communication network. It can be used as an aid in troubleshooting and to assist scheduling for device
maintenance operations.
Recorded indications include:
Highest current measured
Operation counter (both cumulative total and total since last reset)
Number of test kit connections
Number of trips in operating mode
Contact wear (Masterpact NW only)
1Test lamp and indication
reset
2Indication of tripping
cause
3High resolution screen
4Measurement display
5Maintenance indicators
6Protection settings
7Navigation buttons
8Overload signal (LED)
9Long-time rating plug
screw
10Long-time current
setting and tripping delay
11Short-time pickup and
tripping delay
12Instantaneous pickup
13Hole for settings
lockout pin
14Electronic push-to-trip
15Ground-fault pickup and
tripping delay
16Test connector
The adjustable protection functions of the 5.0P and 6.0P trip units
are identical to those of Micrologic A trip unit (overloads, short
circuits, equipment ground-fault protection); see page 23.
These units also feature:
Fine adjustment: Within the range below the rotary switch
setting, fine adjustments of pickups/delays in steps of 1 A/s
(except for short-time and ground-fault) are possible on the
keypad or remotely by the communication network.
Inverse definite minimum time lag (IDMTL) setting:
Coordination with fuse-type or medium-voltage protection systems
is optimized by adjusting the long-time delay curve around 6 x I
r
axis. This setting ensures better coordination with certain loads.
Neutral protection: On three-pole circuit breakers, neutral
protection may be set using the keypad or remotely using the
communication network to one of four positions:
OFF
1/2N (1/2 x I
n
)
1N (1 x I
n
)
2N (2 x I
n
)
NOTE: The neutral protection is disabled if the long-time curve is set
to one of the IDMTL protection settings.
Micrologic 6.0 P
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
ground fault
B
C
D
E
F
G
H
J
Ig tg
(s)
on I
2
t
.2
.3
. 4
.4
.1
.2
.3
.1
0
off
A
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
x In
test
2
4
10
3
6
8
12
15
off
1
4
5
6
7
15
9
10
11
12
16
8
13
14
2
3
0
6
1
3
3
2
5
5
85kA
30kA
24s
5000A
I
(A)
Trip
0.4s
Micrologic
Electronic Trip SystemsMicrologic 5.0P & 6.0P Trip Units with Power Metering
Load Shedding and Reconnection Parameters
Load shedding and reconnection parameters can be set according to the power or the current flowing
through the circuit breaker. Load shedding is carried out by a remote computer via the communication
network or by an M2C or M6C programmable contact.
Indication Option via Programmable Contacts
The M2C (two contacts) and M6C (six contacts) programmable contacts may be used to signal
threshold overruns or status changes. They can be programmed using the keypad on the Micrologic P
trip unit or remotely using the communication network. These contacts are required to obtain data from
the protective relay functions on Type P and Type H trip units.
I 0
t
t
r
I
r
IDMTL
I
sd
t
sd
I
i
I
r
I
sd
I
i
0
6
1
3
3
3
2
7
Table 26: Micrologic 5.0P and 6.0P Trip Unit Settings
Long-time
(RMS)
Protection
Current setting (A)
Tripping between 1.05
and 1.20 x I
r
I
r
= l
n
x... IEC: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
I
r
= l
n
x... UL/ANSI: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
Other ranges are available by changing rating plug
Maximum time delay (s)
Accuracy: 0 to 20%
t
r
at 1.5 x I
r
12.5 25 50 100 200 300 400 500 600
t
r
at 6 x I
r
0.5 1 2 4 8 12 16 20 24
t
r
at 7.2 x I
r
0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
IDMTL Setting
Curve
slope
SIT VIT EIT HV Fuse DT
Thermal imaging 20 minutes before or after tripping
Short-time
(RMS)
Protection
Current setting (A)
Accuracy: 10%
l
sd
= I
r
x... 1.5 2 2.5 3 4 5 6 8 10
Maximum time delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
sd
Min. trip time (ms) 20 80 140 230 350
Max. trip time (ms) 80 140 200 320 500
Instantaneous
Protection
Current setting (A)
Accuracy: 10%
I
i
= I
n
x... 2 3 4 6 8 10 12 15 off
0 I
t
l
g
t
g
I
2
t off
I
2
t on
0
6
1
3
3
3
2
6
Table 27: Micrologic 6.0P Trip Unit Ground-fault Setting
Ground-fault pickup (A)
Accuracy: 10%
I
g
= l
n
x... A B C D E F G H J
l
n
400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
400 A < l
n
1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
l
n
> 1200 A 500 640 720 800 880 960 1040 1120 1200
Maximum time delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
g
Minimum trip time (ms) 20 80 140 230 350
Maximum trip time (ms) 80 140 200 320 500
Table 28: Settings for Alarms for Other Protection Functions for Micrologic 5.0P and 6.0P
Trip Units
Threshold Time Delay
Current
Current imbalance 0.05 to 0.6 x I
max
1 to 40 s
Maximum current I
max
: I
a
, I
b
, I
c
, I
n
, I
g
0.2 to 1.0 x I
n
15 to 1500 s
Voltage
Voltage imbalance 0.02 to 0.3 x V
n
1 to 40 s
Minimum voltage V
min
100 to 725 V (phase total) 0.25 to 0.5 s
Maximum voltage V
max
100 to 1200 V (between phases) 0.20 to 5.0 s
Power
Maximum power P
max
5 to 500 kW 0.2 to 20 s
Reverse power P
r
0.02 to 0.2 x P
n
0.5 to 20 s
Frequency
Minimum frequency F
min
45 to 65 Hz 0.2 to 5 s
Maximum frequency F
max
45 to 540 Hz 0.2 to 5 s
Phase Sequence A-B-C or A-C-B Instantaneous
Masterpact
Electronic Trip SystemsMicrologic 5.0P & 6.0P Trip Units with Power Metering
27
11/2004 19992004 Schneider Electric All Rights Reserved
Trip and Alarm Histories
The last ten trips and ten alarms are recorded in two separate history files that can be displayed on the
screen (sample displays are shown to the left). The following information is contained in these files:
Table 29: Load-shedding Settings for Current and Power Metering for Micrologic 5.0P and
6.0P Trip Units
Pick-up Drop-out
Threshold Time Delay Threshold Time Delay
Current I 0.5 to 1.0 x I
r
per phase 20% to 80% x t
r
0.3 to 1.0 x I
r
per phase 10 to 600 s
Power P 200 kW to 10 MW 10 to 3600 s 100 kW to 10 MW 10 to 3600 s
Trip History
Type of fault
Date and time of fault
Interrupted current
Contact wear
Alarm History
Type of alarm
Date and time of the alarm
Values measured at the time of the
alarm
0
6
1
3
3
2
6
2
Trip
history
30/06/1999
Vmax
27/07/1999
Isd
03/08/1999
Ir
0
6
1
3
3
2
6
3
I1 = 4800 A
I2 = 5600 A
I3 = 4000 A
IN = 200 A
03/08/1999
Ir = 4000 A
11:04:18 am
Trip
28
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact
Electronic Trip SystemsMicrologic 5.0P & 6.0P Trip Units with Power Metering
Metering
The Micrologic P trip unit calculates in real time all electrical values V, A, W, VAR, VA, Wh, VARh,
VAh, Hz, power factor, and crest factor. The Micrologic P trip unit also calculates demand current and
demand power over an adjustable time period.
Real-time Metering: The value displayed on the screen is refreshed every second. Minimum and
maximum measurement values are stored in memory.
Demand Metering: The demand is calculated over a fixed or sliding time window that can be
programmed from five to 60 minutes. Depending on the contract signed with the power supplier,
specific programming makes it possible to avoid or minimize the cost of overrunning the subscribed
power. Maximum demand values are systematically stored and time stamped.
Communication Network
Four wire Modbus
System Manager
TM
(SMS) software.
Event Log
The event log may be accessed by a remote computer via the communication network. All events are
time stamped and include:
Trips
Beginning and end of alarms
Modifications to settings and parameters
Loss of time
Overrun of wear indicators
Test kit connections.
Counter resets.
System faults (thermal self-protection, major fault and minor fault alarms).
Vinst.
VAB = 460 V
VBC = 464 V
VCA = 461 V
VAN = 270 V
VBN = 279 V
VCN = 273 V
Pinst.
P (kW)
2180
Q (kVAR)
- 650
S (kVA)
2280
F (Hz)
60.0
Pdemand
P (kW)
2180
Q (kVAR)
- 650
S (kVA)
2280
85kA
30kA
24s
5000 A
I(A)
Trip
0.4s
Imax
IA = 4800 A
IB = 4600 A
IC = 4000 A
IN = 200 A
I = 13 A
instant.
0
6
1
3
3
2
5
8
d
Current
Metering
Maximum
Current
Voltage
Metering
Power
Metering
Frequency
Power
Demand
Type of Measurement Unit of Measurement Measurement Source
Current
I
RMS
I
AVERAGE
I
PEAK/ 2
A
A
A
A, B, C or N
(A + B + C)/3
A, B, C or N
Voltage
V
RMS
V
RMS
V
IMBALANCE
V
V
%
(AB), (BC) and (CA)
(AN), (BN) and (CN)
V
RMS
Power
P, Q and S
EP, EQ and ES
Power factor
W, VAR, VA
Wh, VARh, VAh
Total
Total
Total
Frequency F Hz 50/60
Type of Measurement Unit of Measurement Measurement Source
Current I
DEMAND
A A, B, C or N
Power P, Q and S
DEMAND
W, VAR, VA Total
Masterpact
Electronic Trip SystemsMicrologic 5.0H & 6.0H Trip Units with Harmonic Metering
29
11/2004 19992004 Schneider Electric All Rights Reserved
MICROLOGIC 5.0H & 6.0H TRIP UNITS WITH HARMONIC METERING
In addition to the P functions, the Micrologic H trip units offer:
In-depth analysis of power quality including calculation of harmonics and the fundamentals.
Diagnostics aid and event analysis through waveform capture.
Customized alarm programming to analyze and track down a disturbance on the ac power system.
Systematic time stamping of all events and creation of logs.
Metering
The Micrologic H trip unit offers all the measurements carried out by the Micrologic P trip unit, with the
addition of phase-by-phase measurements of power and energy as well as calculation of:
Current and voltage total harmonic distortion (THD, thd).
Current, voltage and power fundamentals (50/60 Hz).
Harmonic components (amplitude and phase) up to the 31st current and voltage harmonic.
Real-time metering: The value displayed on the screen is refreshed every second. The table below
shows what is measured in real-time metering.
Demand Metering: Similar to the Micrologic P trip unit, demand values are calculated over a fixed or
sliding time window that can be set from five to 60 minutes.
Waveform Capture
Micrologic H trip units can capture and store current and voltage waveforms using digital sampling
techniques similar to those used in oscilloscopes. Using the information available in the captured
waveform, it is possible to determine the level of harmonics as well as the direction and amplitude of
the flow of harmonic power.
Users of Micrologic H trip units can record manually via the keypad the following waveforms:
The four currents: I
a
, I
b
, I
c
, and I
N
The three phase-to-phase voltages: V
ab
, V
bc
, and V
ca
Waveforms may be displayed on the graphic screen of Micrologic H trip units or communicated over a
networked system. The recording takes place over one cycle with a measurement range of 0 to 1.5 I
N
for current and 0 to 690 volts for voltage. The resolution is 64 points per cycle.
0
6
1
3
3
8
1
1
Micrologic 6.0 H
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
lg
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
.5
1
2
4
8
12
16
20
tr
(s)
@6 Ir
24
x In
test
I
(A)
V
(V)
P
(kW)
E
(kWh)
Harmonics
2
4
10
3
6
8
12
15
off
ground fault
B
C
D
E
F
G
H
J A
Ig
Micrologic
Electronic Trip SystemsMicrologic 5.0H & 6.0H Trip Units with Harmonic Metering
Customized Alarm Programming
The instantaneous value of each measurement can be compared to user-set high and low thresholds.
Overrun of a threshold generates an alarm. Programmable action can be linked to each alarm, including
circuit breaker opening, activation of an M2C or M6C contact, recording of measurements in a log, etc.
Event Logs
Each event is recorded with:
The date, time, and name of the event.
The event characteristics.
Additional Technical Characteristics for Type P and Type H Trip Units
Setting the display language: System messages can be displayed in six different languages:
English - US
English - UK
French
German
Spanish
Italian
The desired language is selected via the keypad.
Protection functions: All current-based protection functions require no auxiliary source. Voltage-
based protection functions are connected to AC power via a voltage measurement input built into
the circuit breaker on the bottom side. (Optional external voltage measurement is available.)
Accuracy of measurements (including sensors):
Voltage (V) 1%
Current (A) 1.5% (higher accuracy [1%] may be achieved with special calibration on the current
transformer [CT characterization option])
Frequency (Hz) 0.1 Hz
Power (W) and energy (Wh) 2.5%
The Micrologic H trip unit uses a dedicated metering data chain separate from the protection
data chain so that a greater number of data samples can be used for metering. This increases
the number of samples taken per time period, which in turn gives the H trip unit a higher degree
of metering accuracy.
Stored information: The fine setting adjustments, the last 100 events and the maintenance record
remain in the trip unit memory even when power is lost.
Reset: An individual reset, via the keypad or remotely, will reset alarms, minimum and maximum
data, peak values, counters and the indicators.
Masterpact
System Manager
TM
software (SMS) or other applications for reporting and recording.
Four wire Modbus, RTU, RS485Types of information available via Modbus communication network:
The Modbus circuit breaker communication feature, standard on the Micrologic P and H trip units and
available for the Micrologic A trip unit, is made up of:
A Modbus circuit breaker communication module (BCM) installed on the circuit breaker and
supplied with a kit for optional connection to the XF shunt close and MX shunt trip.
An optional Modbus cradle communication module (CCM) installed adjacent to the breaker cradle.
Cradle position switches are required for breaker position status (connected, test, or disconnected).
Modbus
1b 1a 1b
1b 1a, 1b 1b
1a, 2b 1a, 2b 1a
With Additional Actuators
9
6
6
0
3
0
0
0
3
1a, 2b 2a, 1b 1b
2a, 1b 1a, 2b 1b
1a 1a 1a
Breaking
Capacity at a
Power Factor
(p.f) of 0.3
Standard (100 mA/24 V minimum load) 3a 3a 1a
Vac
240 8 A 8 A 3b 3b 1b
380 8 A 8 A
Additional Actuators for Cradle
Position Switches on Masterpact NW
Circuit Breakers
A set of additional actuators may be
installed on the cradle to change or add
the functions of the cradle position
switches. Each standard actuator can be
replaced by any other actuator to
change the function of the cradle
position switch.
480 8 A 8 A
600/690 6 A 6 A
Vdc
24/48 2.5 A 2.5 A
125 0.8 A 0.8 A
250 0.3 A 0.3 A
Low-level (2 mA/15 V minimum load)
Vac
24/48 5 A 5 A
240 5 A 5 A
380 5 A 5 A
Vdc
24/48 2.5 A 2.5 A
125 0.8 A 0.8 A
250 0.3 A 0.3 A
Figure 9: Cradle Position Switch Actuators
Cradle Position
Switch (CE, CD, CT)
Actuator for up to Three
CE Switches (standard)
Actuator for up to Three
CD Switches (standard)
Actuator for up to Three
CT Switches (standard)
42
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact
circuit breaker communication module (BCM) (standard on the Micrologic P and H trip
units and available for the Micrologic A trip unit) is comprised of a communication module installed on
the circuit breaker with a kit for connection to the shunt close (XF) and shunt trip (MX1) along with a set
of switches.
The Modbus cradle communication module (CCM) is connected to the BCM and cell switches.
Modbus Circuit Breaker Communication Module (BCM)
This module is independent of the trip unit. Installed on the circuit
breaker, behind the trip unit, it receives and transmits information on
the communication network. An optical link is used for
communication with the Micrologic A, P, and H trip units. Power
requirements: 30 mA, 24 Vdc.
The following may be connected to this module:
A set of dedicated switches which read the status of the circuit
breaker.
A set of actuators (MX/XF) to control the circuit breaker.
Figure 10: Communication Network Accessories
5
1
7
4
C
3
6
2
MODBUS Communication
Network with CCM
MODBUS Communication
Network without CCM
OF
SDE
PF
MX1
XF
CE
CD
BCM
CH
CT
CCM
(optional)
Terminal
Block
1Circuit breaker switches (OF, SDE, PF, and CH)
2Cradle communication module (CCM)
3Cradle switches (CD, CE and CT)
4Shunt trip (MX1) and shunt close (XF)
5Communication bus
6Circuit breaker communication module (BCM)
7Trip unit
Circuit Breaker
Communication
Module (BCM)
Masterpact
Type B
Type C
Type D
0.4
0.4
0.42
0.4
0.45
0.44
0.50
0.48
0.5
0.5
0.53
0.64
0.6
0.56
0.58
0.7
0.63
0.63
0.67
0.8
0.7
0.75
0.75
0.9
0.8
0.88
0.83
0.93
0.9
0.95
0.95
0.95
1
1
1
1
Type E
Type F
Type G
Type H
0.6
0.84
0.66
0.48
0.7
0.86
0.68
0.5
0.75
0.88
0.7
0.52
0.8
0.9
0.72
0.54
0.85
0.92
0.74
0.56
0.9
0.94
0.76
0.58
0.93
0.96
0.78
0.6
0.95
0.98
0.8
0.62
1
1
0.82
0.64
IEC Rated
Type R
Type S
Type T
0.4
0.4
0.8
0.5
0.45
0.82
0.6
0.5
0.85
0.7
0.55
0.88
0.8
0.6
0.9
0.9
0.65
0.92
0.95
0.7
0.95
0.98
0.75
0.98
1
0.8
1
Type P
(off plug)
No long-time protection.
Standard
Adjustable
Rating Plug
External Power
Supply Module
External Battery
Backup Module
46
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact
M
i
c
r
o
l
o
g
i
c
S
e
r
i
e
s
B
T
r
i
p
U
n
i
t
S
q
u
a
r
e
D
G
C
-
1
0
0
R
e
l
a
y
S
q
u
a
r
e
D
G
C
-
2
0
0
R
e
l
a
y
M
e
r
l
i
n
G
e
r
i
n
S
T
R
5
8
T
r
i
p
U
n
i
t
s
F
e
d
e
r
a
l
P
i
o
n
e
e
r
U
S
R
C
a
n
d
U
S
R
C
M
T
r
i
p
U
n
i
t
s
Micrologic Trip Unit
15
4
R R 15 15 R
Square D Micrologic Series B Trip Units R 26 R R R 15
Square D GC-100 Relay R R 7 R R R
Square D GC-200 Relay 15 R R 15 15 R
Merlin Gerin STR58 Trip Units 15 R R 15 15 R
Merlin Gerin STR53 Trip Units 15 R R 15 15 R
Federal Pioneer USRC and USRCM Trip Units R 15 R R R 15
Square D Add-on Ground Fault Module for Equipment Protection R 5 R R R R
R Denotes that a Restraint Interface Module (RIM) is required.
Includes 2.0A (as a downstream trip unit only), 5.0A, 5.0P, 5.0P, 5.0H, 6.0A, 6.0P, and 6.0H trip units.
4
Number denotes maximum number of upstream circuit breakers that can be restrained without requiring a RIM.
Restraint Interface
Module (RIM)
Downstream Device
(sends output to RIM)
Upstream Device
(receives output to RIM)
48
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact
or Federal Pioneer
key locks
(keyed alike or differently) are available for UL Listed/ANSI
Certified circuit breakers; for IEC Rated circuit breakers,
Ronis
, Castell
, or Profalux
4
7
1
S1
4
8
4
S2
4
7
4
Q
1
Q
2
Q
3
M6C
M2C M6C
or
Upstream Downstream
0
6
1
3
3
7
9
6
I
V
T
4
T
3
T
2
T
1
24 Vdc
or
or
1
8
1
1
8
2
1
8
4
SDE2
F
a
u
l
t
F
a
u
l
t
8
1
8
2
8
4
SDE1
K
2
RES
K
1
PF
2
5
2
2
5
4
2
5
1
C
h
a
r
g
e
d
MX1
C
2
C
3
C
1
A
2
A
3
A
1
CH
XF
D
2
D
1
MN MX2
C
1
2
C
1
1
B
1
MCH
B
3
B
2
2
Cell Switches Trip Unit Cell Switches Remote Operation
CD3 CD2 CD1 COM UC1 UC2 UC3 UC4 M2C/M6C SDE2/RES SDE1 CE3 CE2 CE1 MN/MX2 MX1 XF PF MCH
834 824 814 E5 E6 Z5 M1 M2 M3 F2+ V3 484/Q3 184/K2 84 334 324 314 D2/C12 C2 A2 254 B2
832 822 812 E3 E4 Z3 Z4 T3 T4 VN V2 474/Q2 182 82 332 322 312 C13 C3 A3 252 B3
831 821 811 E1 E2 Z1 Z2 T1 T2 F1 V1 471/Q1 181/K1 81 331 321 311 D1/C11 C1 A1 251 B1
or
CE6 CE5 CE4
364 354 344
362 352 342
361 351 341
Masterpact
OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 OF4 OF3 OF2 OF1 CT3 CT2 CT1
244 234 224 214 144 134 124 114 44 34 24 14 934 924 914
242 232 222 212 142 132 122 112 42 32 22 12 932 922 912
241 231 221 211 141 131 121 111 41 31 21 11 931 921 911
or or or or
EF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11 CD6 CD5 CD4 CE9 CE8 C7
248 238 228 218 148 138 128 118 864 854 844 394 384 374
246 236 226 216 146 136 126 116 862 852 842 392 382 372
245 235 225 215 145 135 125 115 861 851 841 391 381 371
Note: Fixed-mounted circuit breaker does not have cell switches (CE, CD, CT).
Table 57: Markings for Ring Terminals
Alarm Switches Auxiliary Contacts Cell Switches
PF CT1 MCH MCHa OF14 OF13 OF12 OF11 OF4 OF3 OF2 OF1 CE3 CE2 CE1
252 914/912 B2 B3 144 134 122 112 44 34 22 12
334/33
2
324/32
2
314/31
2
251 911 B1 141 131 121 111 41 31 21 11 331 321 311
Note: Fixed-mounted circuit breaker does not have cell switches (CE, CD, CT).
64
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact
UC1:
Z1Z5 logical selectivity
Z1 = ZSI OUT
Z2 = ZSI OUT Source; Z3 = ZSI IN Source
Z4 = ZSI IN short-time delay
Z5 = ZSI IN ground fault
SDE1 Electrical fault alarm contact (standard)
MN or MX2
Undervoltage trip device
Additional shunt trip
MX1 Shunt trip (standard or networked)
UC3:
F2+, F1 24 Vdc external power supply
External neutral VN plug
XF Shunt close (standard or networked)
PF Ready-to-close contact
UC4 External phase voltage sensing MCH Spring-charging motor
M2C
or
M6C
Two programmable contacts (internal relay)
Six programmable contacts
(for connection to external M6C module)
NOTE: When communication version of the MX1 or XF coils are
used, terminals (C3, A3) must be connected to line even if the
communications module is not installed.
The bypass circuit through terminal C2/A2 is only momentary duty
for 0.5 sec. For continuous duty, use the communications
command.
Figure 19: Connection of the Communications Option
T
4
T
3
T
2
T
1
Z
3
Trip Unit
Z
4
Z
3
Z
2
Z
1
Z
4
,
Z
5
Z
2
Z
1
N C B A
Z
5
V
N
V
1
V
2
V
3
M
3
M
2
M
1
F
2
+
F
1
Upstream Downstream
XF
com
O
u
t
+
+
2
4
V
d
c
C
o
m
m
o
n
O
u
t
-
Cradle
Communication
Module (CCM)
I
n
+
I
n
-
E
6
E
5
E
4
E
3
Circuit Breaker
Communication
Module (BCM)
E
2
E
1
+24 Vdc
+24 Vdc
Common
Common
In +
Out +
Shield
Out -
In -
M
O
D
B
U
S
P
r
e
v
i
o
u
s
C
i
r
c
u
i
t
B
r
e
a
k
e
r
N
e
x
t
C
i
r
c
u
i
t
B
r
e
a
k
e
r
MX1
com
T
4
T
3
T
2
T
1
24 V
OF
SDE
PF
CH
Micro switches
connected to BCM
4
7
1
S1
4
8
4
S2
4
7
4
Q
1
Q
2
Q
3
M6C
M2C M6C
or
0
6
1
3
4
8
9
8
811
CD1
812
311
CE1
314
CE CD CT
911
CT1
914
*
*
*
* Must be two separate isolated 24 Vdc sources.
Note: Fixed-monted circuit breaker does not have
cell switches (CE, CD, CT).
NOTE: A recommended wiring schematic for the
communicating style shunt trip or shunt close coils is
shown below.
Induced voltages in the circuit at terminal C2 and/or
A2 can cause the shunt trip or shunt close to not work
properly. The best way to prevent the induced
voltages is keep the circuit to terminal C2 and A2 as
short as possible. If it is impossible to keep the circuit
less than 10 feet (3 m), use an interposing relay near
terminal C2 or A2.
Masterpact
Instantaneous Override
(kA RMS)
240 V 480 V 600 V
800
NT08HF 65 50 50 40
NT08HB 200 100 N/A 10
1200
NT12HF 65 50 50 40
NT12HB 200 100 N/A 10
1600
NT16HF 65 50 50 40
NT16HB 200 100 N/A 10
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
Table 69: IEC 60947-3 Rated, Non-automatic T-frame Switches
Frame Rating (A)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (0.5 s) Rating
(kA RMS)
240 V 440 V 690 V 1000 V
800 NT08HA 42 42 42 42
1000 NT10HA 42 42 42 42
1250 NT12HA 42 42 42 42
1600 NT16HA 42 42 42 42
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Masterpact
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
Masterpact
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
O
Not available in four-pole
Table 78: IEC 60947-3 Rated, Automatic Switch
Frame Rating (A)
Model
Number
Withstand Rating (kA RMS)
Instantaneous Override
(kA RMS)
240 V 440 V 690 V
800 NW08HF 85 85 85 85
1000 NW10HF 85 85 85 85
1250 NW12HF 85 85 85 85
1600 NW16HF 85 85 85 85
2000 NW20HF 85 85 85 85
2500 NW25HF 85 85 85 85
3200 NW32HF 85 85 85 85
4000 NW40HF 85 85 85 85
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
158
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact
50 50
1000
NW10NA 42 42 42 42
NW10HA 50 50 50 50
NW10HA10
50 50
1250
NW12NA 42 42 42 42
NW12HA 50 50 50 50
NW12HA10
50 50
1600
NW16NA 42 42 42 42
NW16HA 50 50 50 50
NW16HA10
50 50
2000
NW20HA 50 50 50 50
NW20HA10
50 50
2500
NW25HA 50 50 50 50
NW25HA10
50 50
3200
NW32HA 50 50 50 50
NW32HA10
50 50
4000
NW40HA 50 50 50 50
NW40HA10
50 50
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Instantaneous Override
(kA RMS)
240 V 480 V 600 V
4000 NW40HF 100 100 85 75
5000 NW50HF 100 100 85 75
6000 NW60HF 100 100 85 75
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a
circuit breaker with an equal continuous current rating.
160
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact
Instantaneous Override
(kA RMS)
240 V 480 V 600 V
4000
NW40HF
NW40HB
O
100
200
100
150
85
100
75
75
5000
NW50HF
NW50HB
O
100
200
100
150
85
100
75
75
6000
NW60HF
NW60HB
O
100
200
100
150
85
100
75
75
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
O
Not available in four-pole
Table 88: IEC 60947-3 Rated, Non-automatic Switches
Frame Rating (A)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (1s) Rating
(kA RMS)
240 V 440 V 690 V
5000 NW50HA 85 85 85 85
6300 NW63HA 85 85 85 85
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Masterpact
Trip Units
Dummy Trip Unit (for switch only)
Basic Trip Unit
Trip Unit with Ammeter
Trip Unit with Power Metering
Trip Unit with Harmonic Metering
Micrologic
Ronis
Profalux
Castell
Federal Pioneer