Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

MasterPack Catalog

Download as pdf or txt
Download as pdf or txt
You are on page 1of 176

Class 0613

Masterpact

NT and NW
Universal Power Circuit Breakers
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
MASTERPACT

CIRCUIT BREAKERS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
MICROLOGIC

ELECTRONIC TRIP SYSTEMS. . . . . . . . . . . . . . . . . . . . 17


ACCESSORIES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
MASTERPACT

NT DIMENSIONAL DRAWINGS . . . . . . . . . . . . . . . . . . 67
MASTERPACT

NW DIMENSIONAL DRAWINGS. . . . . . . . . . . . . . . . . . 95
SELECTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
TRIP CURVES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Catalog
2004
Building a New Electric World
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit Breakers
3
11/2004 19992004 Schneider Electric All Rights Reserved
SECTION 1MASTERPACT

CIRCUIT BREAKERS
INTRODUCTION............................................................................................................................................ 4
CODES AND STANDARDS........................................................................................................................... 4
FEATURES AND BENEFITS......................................................................................................................... 5
OPERATING CONDITIONS........................................................................................................................... 7
MASTERPACT NW CIRCUIT BREAKER DESIGN....................................................................................... 8
MASTERPACT NW CRADLE DESIGN ......................................................................................................... 9
MASTERPACT NT CIRCUIT BREAKER AND CRADLE DESIGN.............................................................. 10
RATINGS ..................................................................................................................................................... 11
CORRECTION FACTORS........................................................................................................................... 15
SHIPPING WEIGHTS .................................................................................................................................. 16
4
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersIntroduction
INTRODUCTION
Masterpact

NT/NW Universal Power Circuit Breakers are designed to


protect electrical systems from damage caused by overloads, short
circuits and equipment ground faults. All Masterpact circuit breakers
are designed to open and close a circuit manually, and to open the
circuit automatically at a predetermined overcurrent setting.
Masterpact circuit breakers can also:
Enhance coordination by their adjustability.
Provide integral ground-fault protection for equipment.
Provide high interrupting ratings and withstand ratings.
Provide communications.
Provide power monitoring.
Provide protective relaying functions.
Provide zone-selective interlocking (ZSI) which can reduce damage in the event of a fault.
CODES AND STANDARDS
Masterpact circuit breakers are manufactured and tested in accordance with the following standards:
NOTE: Throughout this document, the phrase ANSI Certified means the product meets the requirements
of UL 1066 and ANSI C37. When UL Listed appears, the product meets the requirements of UL 489.
8002000 A ANSI Low Voltage Power Circuit Breakers type L1F and Insulated Case Circuit Breaker
type LF are tested to show the arc flash hazard risk category as referenced by NFPA

70E.
Circuit breakers should be applied according to guidelines detailed in the National Electrical Code


(NEC

) and other local wiring codes.


Masterpact circuit breakers are available in Square D, Merlin Gerin, or Federal Pioneer brands.
UL File Numbers:
Masterpact NW: E63335 Vol. 4 Sec. 1
Masterpact NT: E63335 Vol. 4 Sec. 2
Figure 1: Masterpact NW Drawout Circuit Breakers
Low-voltage Power
Circuit Breaker
Insulated Case
Circuit Breaker
IEC

Rated
Circuit Breaker
IEC

Extreme Atmospheric
Conditions
ANSI C37.13
ANSI C37.16
ANSI C37.17
ANSI C37.50
UL 1066 (cULus Listed)
NEMA SG3
UL 489 (UL Listed)
NEMA AB1
CSA 22.2 NO 5.1
NMX J-266-ANCE
IEC 60947-2
IEC 60947-3
IEC 68-2-1: Dry cold at 55C
IEC 68-2-2: Dry heat at +85C
IEC 68-2-30: Damp heat
(temp. +55C, rel. humidity 95%)
IEC 68-2-52 Level 2: Salt mist
8001600 A Masterpact NT
Drawout Circuit Breaker
NX 08 HA10
Ui 1000V Uimp 12kV
Ue 690(V)
50kA/1s
IEC 947-2 50/60Hz
EN 60947-2 UTE VDE BS CEI UNE AS NBMA
0
6
1
3
3
4
6
8
0
6
1
3
3
4
6
9
8003200 A Masterpact NW Drawout Circuit Breaker
40006300 A Masterpact NW Drawout Circuit Breaker
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersFeatures and Benefits


5
11/2004 19992004 Schneider Electric All Rights Reserved
FEATURES AND BENEFITS
High Ampere Interrupting Rating (AIR): ANSI Certified Masterpact NW circuit breakers have an
interrupting rating of 200,000 A at 508 Vac without fuses.
High Short-time Current Rating: Masterpact NW circuit breakers have exceptional short-time
ratingsup to 100,000 A.
100% Rated Circuit Breaker: Masterpact circuit breakers are designed for continuous operation at
100% of their current rating.
Reverse Fed Circuit Breaker: Masterpact circuit breakers can be fed either from the top of the circuit
breaker or from the bottom.
True Two-step Stored Energy Mechanism: Masterpact circuit breakers are operated via a stored-
energy mechanism which can be manually or motor charged. The closing time is less than five cycles.
Closing and opening operations can be initiated by remote control or by push buttons on the circuit
breaker front cover. An OCO cycle is possible without recharging.
Drawout or Fixed Mount, 3- or 4-pole Construction: ANSI Rated, UL Listed and IEC Rated
Masterpact circuit breakers are available in drawout or fixed mounts, with either 3-pole or 4-pole
construction.
Field-installable Trip Units, Sensor Plugs and Accessories: Trip units, sensor plugs and most
accessories are field installable with only the aid of a screwdriver and without adjusting the circuit
breaker. The uniform design of the circuit breaker line allows most accessories to be common for the
whole line.
Reinforced Insulation: Two insulation barriers separate the circuit breaker front from the current path.
Isolation Function by Positive Indication of Contact Status: The mechanical indicator is truly
representative of the status of all the main contacts.
Segregated Compartment: Once the accessory cover has been removed to provide access to the
accessory compartment, the main contacts remain fully isolated. Furthermore, interphase partitioning
allows full insulation between each pole even if the accessory cover has been removed.
Front Connection of Secondary Circuits: All accessory terminals (ring terminals are available as an
option) are located on a connecting block which is accessible from the front in the connected, test and
disconnected positions. This is particularly useful for field inspection and modification.
Anti-pumping Feature: All Masterpact NT and NW circuit breakers are designed with an anti-pumping
feature that causes an opening order to always takes priority over a closing order. Specifically, if
opening and closing orders occur simultaneously, the charged mechanism discharges without any
movement of the main contacts keeping the circuit breaker in the open (OFF) position.
In the event that opening and closing orders are simultaneously maintained, the standard mechanism
provides and anti-pumping function which continues to keep the main contacts in the open position.
In addition, after fault tripping or opening the circuit breaker intentionally (using the manual or electrical
controls and with the closing coil continuously energized) the circuit breaker cannot be closed until the
power supply to the closing coil is discontinued and then reactivated.
NOTE: When the automatic reset after fault trip (RAR) option is installed, the automatic control system
must take into account the information supplied by the circuit breaker before issuing a new closing
order or before blocking the circuit breaker in the open position. Information on the type of fault, e.g.
overload, short-circuit or ground fault.
6
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersFeatures and Benefits


Disconnection Through the Front Door: The racking handle and racking mechanism are accessible
through the front door cutout. Disconnecting the circuit breaker is possible without opening the door
and exposing live parts.
Drawout Mechanism: The drawout assembly mechanism allows the circuit breaker to be racked in
four positions (connected, test, disconnected, or withdrawn), as shown in the figure below.
NOTE: For UL/ANSI circuit breakers, the clusters are mounted on the circuit breaker; for IEC circuit
breakers, the clusters are mounted on the cradle.
Figure 2: Racking Handle and Mechanism
Figure 3: Racking Positions
0
6
1
3
3
3
4
1
T
TEST
0
6
1
3
3
3
3
9
0
6
1
3
3
8
3
2
Disconnected
Position
Closing and Opening Push Buttons
Racking Handle Storage Space
Racking Handle
Racking Mechanism
Door Escutcheon
T TEST
TEST T
T
0
6
1
3
3
3
3
9
0
6
1
3
3
8
3
0
Connected Position
Disconnected Position Withdrawn Position
Test Position
Secondary
Contacts

Stabs (IEC)
Clusters (UL/ANSI)
Clusters (IEC)
Stabs (UL/ANSI)
TEST
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersOperating Conditions


7
11/2004 19992004 Schneider Electric All Rights Reserved
Reduced Maintenance: Under normal operating conditions, the circuit
breaker does not require maintenance. However, if maintenance or
inspection is necessary, the arc chambers are easily removed so you may
visually inspect the contacts and wear indicator groove (see the figure
below for how wear is indicated). The operation counter can also indicate
when inspections and possible maintenance should be done. The life of
the circuit breaker may be extended by replacing the arc chamber and
spring-charging motor and/or replacing the main contact assembly of
ANSI Certified circuit breakers.
OPERATING CONDITIONS
Masterpact

circuit breakers are suited for use:


At ambient temperatures between -22F (-30C) and 140F (60C).
At altitudes +13,000 ft. (3900 m).
Masterpact circuit breakers have been tested for operation in industrial atmospheres. It is
recommended that the equipment be cooled or heated to the proper operating temperature and kept
free of excessive vibration and dust. Operation at temperatures above 104F (40C) may require
derating or overbussing the circuit breaker. See the appropriate instruction bulletin and page 15 of this
catalog for additional information.
Masterpact circuit breakers meet IEC 68-2-6 Standards for vibration.
2 to 13.2 Hz and amplitude 0.039 in. (1 mm)
13.2 to 100 Hz constant acceleration 0.024 oz. (0.7 g.)
The materials used in Masterpact NT and NW circuit breakers will not support the growth of fungus and
mold.
Masterpact circuit breakers have been tested to the following:
IEC68-2-30 - Damp heat (temperature +55C and relative humidity of 95%)
IEC 68-2-52 level 2 - salt mist
Figure 4: Contact Wear Indicators
0
6
1
3
3
4
7
0
Arc Chamber
0
6
1
3
3
1
8
5
a
Wear Indicator Groove
Good
Contacts
Worn
Contacts
Wear Indicator Groove
8
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersMasterpact NW Circuit Breaker Design


MASTERPACT NW CIRCUIT BREAKER DESIGN
NOTE: For UL Listed and ANSI Certified circuit breakers, the clusters are mounted on the circuit
breaker; for IEC Rated circuit breakers, the clusters are mounted on the cradle.
RESET
Shunt Trip (MX2) or
Undervoltage
Trip Device (MN)
Auxiliary Control
Connection
Trip Unit Connection to
Overcurrent Trip Switch
Cradle Rejection Kit
Cluster
Overcurrent Trip Switch (SDE2)
or Electric Reset
Overcurrent Trip
Switch (SDE1)
Mounting Plate for
Fixed Circuit Breaker
Lifting Tab
Trip Unit
Circuit Breaker
Communication Module
Key Interlock
Padlock Attachment
Push-to-reset
on Fault Trip
Open/Close
Indicator
Charged/Discharged
Indicator
Faceplate
Operation Counter
Opening Push Button
Closing Push Button
Spring-charging Motor (MCH)
Charging Handle
Ready-to-close Contact (PF)
Shunt Close (XF)
Block of Four Form C
Auxiliary Contacts (OF)
Two Blocks of Four Additional Switches (OF) or
Combined "Connected, Closed" Switches (EF)
Auxiliary Contact Connection
Shunt Trip (MX1)
Arc Chamber
Open/Close Push
Button Cover
(lockable with padlock)
Electrical Close
Push Button (BPFE)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersMasterpact NW Cradle Design


9
11/2004 19992004 Schneider Electric All Rights Reserved
MASTERPACT NW CRADLE DESIGN
10
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersMasterpact NT Circuit Breaker and Cradle Design


MASTERPACT NT CIRCUIT BREAKER AND CRADLE DESIGN



Lifting Handle
Terminal Cover
Extension Rail Handle
Padlock Provision
NT Cradle
NT Drawout Circuit Breaker
Position Indicator
Crank Insertion Opening
Stop Release Button
Crank Storage Space
Lifting Tab
Fault Trip
Reset Button
Accessory Cover
Faceplate
Charging Handle
"Push-to-close" Button
"Push-to-open" Button
Trip Unit
Fixed Circuit Breaker
Lifting Tab
Fault Trip
Reset Button
Accessory Cover
Faceplate
Charging Handle
"Push-to-close" Button
"Push-to-open" Button
Trip Unit
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersRatings
11
11/2004 19992004 Schneider Electric All Rights Reserved
RATINGS
Table 1: Ratings for ANSI C37 Certified Masterpact NW Circuit Breakers
Frame Rating 800/1600 A 2000 A 3200/4000 A
4
4000/5000 A
Interrupting Rating Code N1 H1 H2 H3 L1

L1F H1 H2 H3 L1

L1F H1 H2 H3 L1

H2 H3 L1

Interrupting Current (kAIR RMS)


254 Vac 50/60 Hz
508 Vac 50/60 Hz
635 Vac 50/60 Hz
42
42
42
65
65
65
85
85
85
100
100
85
200
200
130
200
200
130
65
65
65
85
85
85
100
100
85
200
200
130
200
200
130
65
65
65
85
85
85
100
100
85
200
200
130
85
85
85
100
100
85
200
200
130
Short-time Withstand Current
(kA RMS)
Vac 50/60 Hz, 1 s 42 65 85 85 30 22 65 85 85 30 22 65 85 85 100 85 85 100
Built-in Instantaneous Override
(kA RMS 10%)

85 35

24 85 35 24 85 117 117
Close and Latch Ratings (kA
RMS)
Vac 50/60 Hz 42 65 40 40 25 22 65 40 40 25 22 65 40 40 40 85 75 40
Tested to show arc flash hazard risk
category as referenced by NFPA70E
Yes Yes
Breaking Time 25 to 30 ms with no intentional delay (9 ms for L1 and L1F)
Closing Time 70 ms
Sensor Rating
100 to 800 A
800 to 1600 A
1000 to 2000 A 1600 to 4000 A
2000 to 4000 A
2500 to 5000 A
Endurance Rating (C/O cycles)
(with no maintenance)
Mechanical 12,500 10,000 10,000 5000 5000
Electrical 2800 1000 1000 1000 1000
4
4000 A standard width circuit breaker is not available in L1 interrupting rating code (see dimensions on page 107)

Interrupting ratings (kAIR RMS) at 50 Hz: 200 kA (254 Vac), 150 kA (508 Vac), 100 kA (635 Vac)

24 kA RMS for 800 A circuit breaker frame with 100 A or 250 A sensor
Table 2: Ratings for ANSI C37 Certified Masterpact NW Non-Automatic Switches
Frame Rating 800 A 1600 A 2000 A 3200 A 4000 A 5000 A
Withstand Rating Code HA HA HA HA HA HA
Breaking Capacity with
External Relay (kA RMS)
Vac, 50/60 Hz
254 65 65 65 65 85 85
508 65 65 65 65 85 85
635 65 65 65 65 85 85
Short-time Withstand current
(kA RMS) Vac 50/60 Hz, 1 s
65 65 65 65 85 85
Table 3: Ratings for ANSI C37 Certified Masterpact NW Automatic Switches
Frame Rating 800 A 1600 A 2000 A 3200 A 4000 A 5000 A
Withstand Rating Code HF HC HF HC HF HC HF HC HF HC HF HC
Breaking Capacity with
External Relay (kA RMS)
Vac, 50/60 Hz
254 100 200 100 200 100 200 100 200 100 200 100 200
508 100 200 100 200 100 200 100 200 100 200 100 200
635 85 130 85 130 85 130 85 130 85 130 85 130
Short-time Withstand current
(kA RMS) Vac 50/60 Hz, 1 s
85 30 85 30 85 30 85 100 85 100 85 100
12
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersRatings
Table 4: Ratings for UL 489 Listed Masterpact NW Circuit Breakers
Frame Rating 800/1200/1600/2000 A 2500/3000 A 4000/5000/6000 A
Interrupting Rating Code N H L LF H L H L
Interrupting Current (kAIR RMS)
240 Vac 50/60 Hz
480 Vac 50/60 Hz
600 Vac 50/60 Hz
65
65
50
100
100
85
200
150
100
200
150
100
100
100
85
200
150
100
100
100
85
200
150
100
Short-time Withstand Current
(kA RMS)
ac 50/60 Hz, 1 s 42
4
65
4
30
O4
22 65 65 85 100
Built-in Instantaneous Override
(kA RMS 10%)
40 40 35
O4
24 65 65 75 75
Close and Latch Ratings (kA RMS) ac 50/60 Hz 40 40 25

22 40 40 40 40
Tested to show arc flash hazard risk category
as referenced by NFPA70E
Yes
Breaking Time 25 to 30 ms with no intentional delay (9 ms for L and LF)
Closing Time 70 ms
Sensor Rating
100 to 250 A / 400 to 800 A / 600 to 1200 A / 800 to
1600 A / 1000 to 2000 A
1200 to 2500 A /
1600 to 3000 A
2000 to 4000 A / 2500 to
5000 A / 3000 to 6000 A
Endurance Rating (C/O cycles)
(with no maintenance)
Mechanical 12,500
O
12,500
O
12,500
O
12,500
O
10,000 10,000 5000 5000
Electrical 2800
O
2800
O
2800
O
2800
O
1000 1000 1000 1000
4
24 kA RMS for 800 A circuit breaker frame with 100 A or 250 A sensor.
O
65 kA RMS for 2000 A

40 kA RMS for 2000 A.


O
The endurance rating for 2000 A, N/H/L is 10,000 for mechanical and 1000 for electrical.
Table 5: Ratings for UL 489 Listed Masterpact NW Automatic Switches
Frame Rating 800 A 1200 A 1600 A 2000 A 2500 A 3000 A 4000 A 5000 A 6000 A
Withstand Rating Code HF HB HF HB HF HB HF HB HF HB HF HB HF HB HF HB HF HB
Withstand Ratings*
(kA RMS) Vac,
50/60 Hz
240 100 200 100 200 100 200 100 200 100 200 100 200 100 200 100 200 100 200
480 100 150 100 150 100 150 100 150 100 150 100 150 100 150 100 150 100 150
600 85 100 85 100 85 100 85 100 85 100 85 100 85 100 85 100 85 100
Instantaneous Override (kA RMS) 40 35 40 35 40 35 40 35 65 65 65 65 75 75 75 75 75 75
* The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit breaker with an equal
continuous-current rating.
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersRatings
13
11/2004 19992004 Schneider Electric All Rights Reserved
Table 6: Ratings for IEC 60947-2 Rated Masterpact NW Circuit Breakers
Frame rating 800/1000/1250/1600 A 2000 A 2500/3200/4000 A 5000/6300 A
Interrupting Rating Code N1 H1 H2 L1 H10 H1 H2 H3 L1 H10 H1 H2 H3 H10 H1 H2
Ultimate
Breaking
Capacity (kA
RMS)
50/60 Hz
I
cu
220/415 Vac
440 Vac
525 Vac
690 Vac
1150 Vac
42
42
42
42

65
65
65
65

100
100
85
85

150
150
130
100

50
65
65
65
65

100
100
85
85

150
150
130
100

150
150
130
100

50
65
65
65
65

100
100
85
85

150
150
130
100

50
100
100
100
100

150
150
130
100

Service Breaking
Capacity
I
cs
%Icu 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Short-time
Withstand
Current
(kA RMS)
I
cw
Vac 50/60 Hz, 1 s
Vac 50/60 Hz, 3 s
42
22
65
36
85
50
30
30
50
50
65
36
85
75
65
65
30
30
50
50
65
65
85
75
65
65
50
50
100
100
100
100
Built-in Instantan-eous Override
(kA RMS 10%)
85
4
35
4
85 65 35 85 65 117
Close and Latch
Ratings (kA
RMS)
50/60 Hz
I
cm
220/415 Vac
440 Vac
525 Vac
690 Vac
1150 Vac
38
38
38
38

62
62
62
62

96
96
81
81

143
143
124
96

46
62
62
62
62

96
96
81
81

143
143
124
96

143
143
124
96

46
62
62
62
62

96
96
81
81

143
143
124
96

46
96
96
81
81

143
143
124
96

Break Time ms 25 25 25 25
Closing Time ms < 70 < 70 < 70 < 80
Endurance Rating
(with no maint.)
C/O cycles x 1000
Mechanical 12.5 10 10 5
Electrical 440 V 10 10 10 3 8 8 3 3 5 5 1.25 1.5 1.5
Electrical 1150 V 0.5 0.5 0.5
4
24 kA RMS for 800 A circuit breaker frame with 100 A or 250 A sensor.
Table 7: Ratings for IEC 60947-3 Rated Masterpact NW Switches
Frame Rating 800/1000/1250/1600 A 2000 A 2500/3200/4000 A 5000/6300 A
Withstand Rating Code

NA HA HF HA10 HA HF HA10 HA HF HA10 HA


Close and Latch Rating
(kA RMS)
I
cm
220/415 Vac, 50/60 Hz
440 Vac, 50/60 Hz
500/690 Vac, 50/60 Hz
1150 Vac, 50/60 Hz
38
38
38

46
46
46

81
81
81

46
46
46
46

81
81
81

46
53
53
53
53
81
81
81

46
81
81
81

Short-time Withstand
Current (kA RMS)
I
cw
Vac 50/60 Hz, 1 s 42 50 85 50 50 85 50 50 85 50 85
Ultimate Breaking
Capacity
(with external protection
relay) (kA RMS)
I
cu
maximum delay 350
ms
42 50 85 50 50 85 50 50 85 50 85

NA, HA, and HA10 are non-automatic switches; HF is an automatic switch.


14
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersRatings
Table 8: Ratings for ANSI C37 Certified Masterpact NT Circuit Breakers
Frame Rating 800 A 800 A
Interrupting Rating Code N1 H1
Interrupting Current (kAIR RMS)
254 Vac 60 Hz
508 Vac 60 Hz
635 Vac 60 Hz
42
42
N/A
42
42
22
Short-time Withstand Current (kA RMS) ac 60 Hz, 0.5 s 42 42
Built-in Instantaneous Override
(kA RMS 10%)

Close and Latch Ratings (kA RMS) ac 60 Hz 40 40
Tested to show arc flash hazard risk category as referenced by NFPA70E
Breaking Time 25 to 30 ms (with no intentional time delay)
Closing Time < 50 ms
Sensor Rating 100 to 250 A / 400 to 800 A
Endurance Rating (C/O cycles)
(with no maintenance)
Mechanical 12,500
Electrical 2800
Table 9: Ratings for ANSI C37 Certified Masterpact NT Non-Automatic Switches
Frame Rating 800 A 800 A
Withstand Rating Code NA HA
Short-time Withstand Current Rating (kA RMS) Vac 50/60 Hz, 0.5 s 42 42
Breaking Capacity (with external protection relay) (kA RMS) 254/508/635 Vac, 60 Hz 42/42/NA 42/42/22
Table 10: Ratings for UL 489 Listed Masterpact NT Circuit Breakers
Frame Rating 800 A 1200 A 1600 A
Interrupting Rating Code N H L1 L LF N H L1 L LF N H L1 L
Interrupting Current (kAIR RMS)
240 Vac, 60 Hz
480 Vac, 60 Hz
600 Vac, 60 Hz
50
50
35
65
50
50
100
65
N/A
200
100
N/A
200
100
N/A
50
50
35
65
50
50
100
65
N/A
200
100
N/A
200
100
N/A
50
50
35
65
50
50
100
65
N/A
200
100
N/A
Short-time Withstand Current Rating (kA
RMS)
ac 60 Hz, 0.5 s 35 35 10 10 10 35 35 10 10 10 35 35 10 10
Built-in Instantaneous Override
(kA RMS 10%)
40 40 10 10 10 40 40 10 10 10 40 40 10 10
Close and Latch Ratings (kA RMS) ac 60 Hz 25 25 10 10 10 25 25 10 10 10 25 25 10 10
Tested to show arc flash hazard risk category
as referenced by NFPA70E
Yes Yes
Breaking Time
25 to 30 ms (with no intentional time delay)
9 ms for L and LF
Closing Time < 50 ms
Sensor Rating 100250 A / 400800 A 6001200 A 8001600 A
Endurance Rating (C/O cycles)
(with no maintenance)
Mechanical 12,500
Electrical 2800
Table 11: Ratings for UL 489 Listed Masterpact NT Automatic Switches
Frame Rating 800 A 1200 A 1600 A
Withstand Rating Code HF HB HF HB HF HB
Withstand Rating
44
(kA RMS) Vac, 50/60 Hz
240
480
600
65
50
50
200
100
NA
65
50
50
200
100
NA
65
50
50
200
100
NA
Instantaneous Override (kA RMS) 40 10 40 10 40 10
44
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit breaker with an equal
continuous current rating.
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersCorrection Factors


15
11/2004 19992004 Schneider Electric All Rights Reserved

CORRECTION FACTORS
Table 12: Ratings for IEC 60947-2 Rated Masterpact NT Circuit Breakers
Frame Rating 800/1000 A 1250/1600 A
Interrupting Rating Code H1 L1 H1
Ultimate Breaking Capacity (kA RMS) I
cu
220/415 Vac, 50/60 Hz
440 Vac, 50/60 Hz
525 Vac, 50/60 Hz
690 Vac, 50/60 Hz
1000 Vac, 50/60 Hz
42
42
42
42

150
130
100
25

42
42
42
42

Service Breaking Capacity (kA RMS) I


cs
%Icu 100% 100% 100%
Short-time Withstand Current (kA RMS) I
cw
Vac 50/60 Hz, 0.5 s 42 10 42
Built-in Instantaneous Override (kA RMS 10%) 10

Close and Latch Rating (kA RMS) I


cm
220/415 Vac, 50/60 Hz
440 Vac, 50/60 Hz
525 Vac, 50/60 Hz
690 Vac, 50/60 Hz
1000 Vac, 50/60 Hz
38
38
38
38

143
124
96
23

38
38
38
38

Break Time ms 25 9 25
Closing Time ms 50 50 50
Endurance Rating (C/O cycles)
(with no maintenance)
Mechanical 12,500 12,500 12,500
Electrical 440 V 6000 3000 6000
4
Electrical 1000 V

SELLIM system
4
1600 A, 3000 cycles
Table 13: Ratings for IEC 60947-3 Rated Non-Automatic Masterpact NT Switches
Frame Rating 800/1000 A 1250/1600 A
Withstand Rating Code HA HA
Close and Latch Rating (kA RMS) I
cm
220/415 Vac, 50/60 Hz
440 Vac, 50/60 Hz
500/690 Vac, 50/60 Hz
1000 Vac, 50/60 Hz
33
33
33

33
33
33

Short-time Withstand Current (kA RMS) I


cw
Vac 50/60 Hz, 0.5 s 42 42
Breaking Capacity (kA RMS at 690 Vac)
(with external protection relay)
I
cu
maximum delay 350 ms 35 35
Table 14: Temperature Correction Factors per ANSI C37.20.1 par. 7.4.2
Maximum Ambient Temperature
F 140 122 104 86 77 68 50 32 14 4 22
C 60 50 40 30 25 20 10 0 10 20 30
Current 0.83 0.92 1.00 1.07 1.11 1.14 1.21 1.27 1.33 1.39 1.44
Table 15: Altitude Correction Factors per ANSI C37.20.1 par. 7.1.4.1 (Table 10)
< 6600 ft. (2000 m) 8500 ft (2600 m) 13,000 ft. (3900 m)
Voltage 1.00 0.95 0.80
Current 1.00 0.99 0.96
16
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact

Circuit BreakersShipping Weights


SHIPPING WEIGHTS

Table 16: Shipping Weights for UL Listed/ANSI Certified Masterpact NW Circuit Breakers
Circuit Breaker
Rating (A)
Circuit Breaker
4
(lb/kg) Cradle (lb/kg) Connector Type and Weight (lb/kg)
Pallet
(lb/kg)
Total Weight (lb/kg)
3-pole 4-pole 3-pole 4-pole Type 3-pole 4-pole 3-pole 4-pole
800
1600
2000
109/50 142/65 97/44 116/53
FCF 42/19 55/25 17/8 265/120 321/145
FCT 84/38 109/50 17/8 307/140 375/170
RCTH or RCTV 17/8 22/10 17/8 240/109 288/130
2500
3000
127/58 165/75 124/57 149/68
FCT 80/36 104/47 17/8 348/157 426/193
RCTH or RCTV 26/12 34/15 17/8 294/134 356/161
2000 (L1, L1F)
3200 (H1, H2, H3)
127/58 165/75 124/57 149/68
RCOV 100/46 130/59
17/8
368/167 452/205
4000 W-frame
(H1, H2, H3)
RCOV (special) 115/52 145/66 383/174 467/212
3200 (L1)
4000
227/103 295/134 278/126 334/152
FCF 84/38 109/50 39/18 268/285 777/352
FCT 168/77 218/99 39/18 712/323 886/401
RCTH or RCTV 52/24 68/31 39/18 596/271 736/333
5000 227/103 295/134 278/126 334/152
FCT 168/77 218/99 39/18 712/323 886/401
RCTH or RCTV 52/24 68/31 39/18 596/271 736/333
6000 227/103 295/134 278/126 334/152 RCTH or RCTV 396/180 528/240 39/18 940/425 1196/541
4
Fixed circuit breaker weight = total weight cradle weight.
Table 17: Shipping Weights for IEC 60947-2 Rated Masterpact NW Circuit Breakers
Circuit Breaker
Rating (A)
Circuit Breaker
4
(lb/kg) Cradle (lb/kg) Connector Type and Weight (lb/kg)
Pallet
(lb/kg)
Total Weight (lb/kg)
3-pole 4-pole 3-pole 4-pole Type 3-pole 4-pole 3-pole 4-pole
800
109/50 132/60 97/44 116/53
FCF 42/19 55/25 17/8 265/120 320/145
1000, 1250,
1600, 2000
RCTH or RCTV 17/8 22/10 17/8 240/109 287/130
2500
3200
127/58 165/75 124/57 149/68
FCF 42/19 55/25 17/8 310/140 386/175
RCTH or RCTV 17/8 22/10 17/8 285/130 353/160
4000 127/58 165/75 124/57 149/68 RCTH or RCTV 42/19 55/25 17/8 310/140 386/175
5000
6300
227/103 295/134 278/126 334/152 RCTH or RCTV 52/24 68/31 39/18 596/270 736/333
4
Fixed circuit breaker weight = total weight cradle weight.
Table 18: Shipping Weights for UL Listed/ANSI Certified Masterpact NT Circuit Breakers
Circuit Breaker
Rating (A)
Circuit Breaker
4
(lb/kg) Cradle (lb/kg) Connector Type and Weight (lb/kg)
Pallet
(lb/kg)
Total Weight (lb/kg)
3-pole 4-pole 3-pole 4-pole Type 3-pole 4-pole 3-pole 4-pole
800
1200
40/18 52/24 36/16 43/20
FCF 15/7 20/9 10/5 101/46 125/57
RCTH or RCTV 6/3 8/4 10/5 92/42 113/51
1600

40/18 52/24 N/A N/A RCTV 18/8 20/9 10/5 104/47 125/57
4
Fixed circuit breaker weight = total weight cradle weight.

Fixed circuit breaker only


Table 19: Shipping Weights for IEC 60947-2 Rated Masterpact NT Circuit Breakers
Circuit Breaker
Rating (A)
Circuit Breaker
4
(lb/kg) Cradle (lb/kg) Connector Type and Weight (lb/kg)
Pallet
(lb/kg)
Total Weight (lb/kg)
3-pole 4-pole 3-pole 4-pole Type 3-pole 4-pole 3-pole 4-pole
800
35/16 46/21 31/14 37/17
FCF 15/7 20/9 10/5 91/41 113/51
1000, 1250, 1600 RCTH or RCTV 6/3 8/4 10/5 82/37 101/46
4
Fixed circuit breaker weight = total weight cradle weight.
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip Systems


17
11/2004 19992004 Schneider Electric All Rights Reserved
SECTION 2MICROLOGIC

ELECTRONIC TRIP SYSTEMS


OVERVIEW OF MICROLOGIC TRIP SYSTEMS ............................................................................... 18
Thermal Imaging ........................................................................................................................... 18
True RMS Current Sensing ........................................................................................................... 20
POWER SUPPLY INFORMATION ..................................................................................................... 19
Ammeter (A) trip unit with 24 Vdc power supply at F1 and F2 ...................................................... 19
Power (P) and Harmonic (H) trip unit without 24 Vdc power supply at F1 and F2 ........................ 19
Power (P) and Harmonic (H) trip unit with 24 Vdc power supply at F1 and F2 ............................. 19
MICROLOGIC TRIP UNITSOVERVIEW........................................................................................... 20
MICROLOGIC 2.0, 3.0, AND 5.0 BASIC TRIP UNITS ....................................................................... 22
Protection Settings ........................................................................................................................ 22
MICROLOGIC 2.0A, 3.0A, 5.0A, AND 6.0A TRIP UNITS WITH AMMETER ..................................... 23
Protection Settings ........................................................................................................................ 22
Ammeter Measurements ............................................................................................................... 23
Communication Network ............................................................................................................... 23
Configuring Alarms and Other Protection Functions ..................................................................... 25
Maintenance Record ..................................................................................................................... 25
Load Shedding and Reconnection Parameters ............................................................................. 26
Indication Option via Programmable Contacts .............................................................................. 26
Trip and Alarm Histories ................................................................................................................ 27
Metering ........................................................................................................................................ 29
Communication Network ............................................................................................................... 23
Event Log ...................................................................................................................................... 28
MICROLOGIC 5.0H AND 6.0H TRIP UNITS WITH HARMONIC METERING ................................... 29
Metering ........................................................................................................................................ 29
Waveform Capture ........................................................................................................................ 29
Customized Alarm Programming .................................................................................................. 30
Event Logs .................................................................................................................................... 30
ADDITIONAL TECHNICAL CHARACTERISTICS FOR TYPE P AND TYPE H TRIP UNITS ............ 30
MICROLOGIC TRIP UNIT FUNCTIONS ............................................................................................ 31
Long-time Trip Functions ............................................................................................................... 31
Short-time Trip Functions .............................................................................................................. 31
Instantaneous Trip Function .......................................................................................................... 31
Ground-fault Trip Functions ........................................................................................................... 31
COMMUNICATION NETWORK ......................................................................................................... 23
Modbus Circuit Breaker Communication Module (BCM) ............................................................... 32
Modbus Cradle Communication Module (CCM) ............................................................................ 32
Powerlogic System Manager Software (SMS) .............................................................................. 32
18
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsOverview of Micrologic Trip Systems


OVERVIEW OF MICROLOGIC TRIP SYSTEMS
All Masterpact

circuit breakers are equipped with the Micrologic

trip system to protect power circuits


and loads. Micrologic trip systems use a set of current transformers (called CTs or sensors) to sense
current, a trip unit to evaluate the current, and a tripping solenoid to trip the circuit breaker. Adjustable
rotary switches on the trip unit allow the user to set the proper overcurrent or equipment ground-fault
current protection required in the electrical system. If current exceeds a set value for longer than its set
time delay, the trip system opens the circuit breaker. Alarms may be programmed for remote
indications. Measurements of current, voltage, frequency, power, and power quality optimize continuity
of service and energy management. Micrologic trip units can be changed on-site.
Integration of protection functions in the Application Specific Integrated Circuit (ASIC) electronic
component used in all Micrologic trip units guarantees a high degree of reliability and immunity to
conducted or radiated disturbances. On Micrologic P and H trip units, advanced functions are
managed by an independent microprocessor.
Masterpact circuit breakers are shipped with the long-time pickup switch set at 1.0 and all other trip unit
adjustments set at their lowest settings. Actual settings required for a specific application must be
determined by a qualified consultant or plant engineer. A coordination study is recommended to
provide coordination between all circuit breakers in the distribution system.
Thermal Imaging
The thermal imaging function protects the cables or bus bars from overheating in case of low
amplitude repetitive faults. Such overheating can be due to repetitive motor starting, fluctuating load,
intermittent ground faults, or subsequent closing after a fault.
Traditional electronic protection does not protect against repetitive faults because the duration of each
overload above the pickup setting is too short to achieve effective tripping. Nevertheless, each
overload involves a temperature rise in the installation, the cumulative effect of which could lead to
overheating of the system.
The thermal imaging function remembers and integrates the thermal heating caused by each pickup
setting overrun. Before tripping, the integrated heating value will reduce the associated time delay and,
therefore, the reaction of the trip unit will be closer to the real heating of the power network system.
After tripping, the function will also reduce the time delay when closing the circuit breaker on an
overload.
Model
(LS0) (LI) (LSI) (LSIG)
Long-time +
Short-time +
Zero delay
Long-time +
Instantaneous
Protection
Long-time + Short-time
+ Instantaneous
Protection
Long-time + Short-time
+ Instantaneous
Protection + Equipment
Ground-fault Protection
(IEC Rated)
(UL Listed and
ANSI Certified)
(UL LIsted, ANSI
Certified, IEC Rated)
(UL LIsted, ANSI
Certified, IEC Rated)
Basic Trip Unit
A Trip Unit
P Trip Unit
H Trip Unit
2.0
2.0A

3.0
3.0A

5.0
5.0A
5.0P
5.0H

6.0A
6.0P
6.0H
Figure 5: P Trip Unit with Power Metering
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsPower Supply Information


19
11/2004 19992004 Schneider Electric All Rights Reserved
POWER SUPPLY INFORMATION
Ammeter (A) trip unit without 24 Vdc power supply at F1 and F2
Provides fault protection for LSIG functions
Provides LED trip indication (powered by an onboard battery)
All display functions and trip unit features power-up with current flow on one phase greater than or
equal to the values in the following table.
Ground-fault push-to-trip button works for testing ground fault with current flow on one phase
greater than or equal to the values shown in the following table.
Ammeter (A) trip unit with 24 Vdc power supply at F1 and F2
The Ammeter (A) trip unit provides all of the above plus additional functionality when powered by
external 24 Vdc power supply:
Ammeter and bar graph displays are functional with or without current flowing through the circuit
breaker
Trip settings and (Max) current readings can be accessed on the display by pressing navigation
button with or without current flowing through the circuit breaker
Ground-fault push-to-trip button works for testing ground fault with or without current flowing
through the circuit breaker
Optional Modbus communicationsAlso requires a separate 24 Vdc power supply for the circuit
breaker communications module
NOTE: Ground-fault push-to-trip button will also be functional if a hand-held test kit or full-function test
kit is powering the trip unit.
Power (P) and Harmonic (H) trip unit without 24 Vdc power supply at F1 and F2
The P and H trip units were designed to be used with the external 24 Vdc power supply. The large LCD
display requires too much current to be powered by current flow through the circuit breaker. The P and
H trip units do have a voltage power supply which will power the trip unit with 100 Vac or more between
two phases or phase to neutral. The standard configuration for the voltage probes inside the circuit
breaker is at the bottom connections. If the circuit breaker was open in a top fed application, there
would be no voltage at the bottom of the circuit breaker and the trip unit would not be powered.
Provides fault protection for LSIG functions
Provides LED trip indication (powered by an onboard battery)
NOTE: Ground-fault push-to-trip button works for testing ground fault if the trip unit is powered by the
voltage power supply. The ground-fault push-to-trip is also functional if a hand-held test kit or full-
function test kit is powering the trip unit.
Power (P) and Harmonic (H) trip unit with 24 Vdc power supply at F1 and F2
Provides all of the above
LCD display and backlight are functional
Ground-fault push-to-trip button works for testing ground fault
All metering, monitoring, and history logs are functional
Communications from trip unit to M2C and M6C programmable contact modules are powered by a
24 Vdc supply at F1 and F2. M6C also requires a 24 Vdc external power supply
Modbus communicationsAlso requires a separate 24 Vdc power supply for the circuit breaker
communications module.
NOTE: Ground-fault push-to-trip button will also be functional if hand-held test kit or full-function test kit
is powering the trip unit.
Sensor Plug
Value (In)
Minimum
Ground-
fault
Pickup
100250 A
30% of
sensor
rating
4001200 A
20% of
sensor
rating
16006300 A 500 A
20
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic Trip UnitsOverview


MICROLOGIC TRIP UNITSOVERVIEW
True RMS Current Sensing
The sensing system responds to the flow of current through the circuit breaker. Electronic trip circuit
breakers are limited to ac systems because the electronic trip system uses current transformers to
sense the current.The Micrologic trip unit samples the current waveform to provide true RMS
protection through the 15th harmonic.
This true RMS sensing gives accurate values for the magnitude of a non-sinusoidal waveform.
Therefore, the heating effects of harmonically distorted waveforms are accurately evaluated.
The Micrologic H trip unit provides additional sampling of the waveforms to measure and provide
waveform capture of harmonic distortion to the 31st harmonic.
Masterpact

Universal Power Circuit Breakers use Micrologic

electronic trip systems to sense


overcurrents and trip the circuit breaker. The Micrologic basic trip unit is standard and all Masterpact circuit
breakers can be equipped with the optional Micrologic trip systems listed below:
Micrologic Basic Trip Unit (standard).
2.0 basic protection (LS0, IEC)
3.0 basic protection (LI, UL/ANSI)
5.0 selective protection (LSI)
Micrologic A: Trip Unit with Ammeter.
2.0A basic protection (LS0, IEC)
3.0A basic protection (LI, UL/ANSI)
5.0A selective protection (LSI)
6.0A selective protection with ground-fault protection for equipment (LSIG)
Micrologic P: Trip Unit with Power Metering.
5.0P selective protection (LSI)
6.0P selective protection with ground-fault protection for equipment (LSIG)
Micrologic H: Trip Unit with Harmonic Metering.
5.0H selective protection (LSI)
6.0H selective protection with ground-fault protection for equipment (LSIG)
Micrologic 3.0
.4
.5
.6
.7
.8
.9
.95
.98
1
x Ir
2
2.5
3
4
5
6
8
10 1.5
setting
Ii
.5
1
2
4
8
12
16
20
instantaneous
long time
alarm Ir tr
(s)
x In @6 Ir
24
test
0
6
1
3
3
3
3
2
Micrologic 5.0
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short
I i tsd
(s)
on I
2
t
.
.
.
.
.
.
.
.
0
off
instantaneous
long time
alarm Ir
x In
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
3
4
6 8 10
12
15
off 2
test
0
6
1
3
3
7
8
7
Micrologic 3.0A
40
100%
%
menu
.4
.5
.6
.7
.8
.9
.95
.98
1
long time
alarm Ir
x In
.5
1
2
4
8
12
16
20
tr
(s)
@6 Ir
24
x Ir
2
2.5
3
4
5
6
8
10 1.5
setting
Im
instantaneous
test
0
6
1
3
3
4
7
7
kA
s
Ir= Ii=
tr=
Isd=
Ig=
tsd=
t=
tg=
In=
MAX
Micrologic 5.0A
40
100%
%
menu
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short
I i tsd
(s)
on I
2
t
.
.
.
.
.
.
.
.
0
off
instantaneous
long time
alarm Ir
x In
.5
1
2
4
8
12
16
20
tr
(s)
@6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
2
2.5
3
4
5
6
8
10 1.5
test
0
6
1
3
3
4
7
8
kA
s
Ir= Ii=
tr=
Isd=
Ig=
tsd=
t=
tg=
In=
MAX
Micrologic 6.0A
40
100%
%
menu
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short
I i tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
ground fault
B
C
D
E
G
H
J
Ig tg
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
A
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
4
3
6
8 10
12
15
off 2
test
0
6
1
3
3
4
8
1
kA
s
Ir= Ii=
tr=
Isd=
Ig=
tsd=
t=
tg=
In=
MAX
Micrologic 3.0 and 5.0 Basic Trip Units Micrologic 3.0A, 5.0A and 6.0A Trip Units
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic Trip UnitsOverview


21
11/2004 19992004 Schneider Electric All Rights Reserved
Table 20: Micrologic

Trip Unit Features


Micrologic Trip Unit
X = Standard Feature O = Available Option
Standard Ammeter Power Harmonics
Feature 2.0 3.0 5.0 2.0A 3.0A 5.0A 6.0A 5.0P 6.0P 5.0H 6.0H
LI X X
LS0 X X
LSI X X X X
LSIG/Ground-fault trip

X X X
Ground-fault alarm/no trip
4
X X
Ground-fault alarm and trip
4
X X
Adjustable rating plugs X X X X X X X X X X X
True RMS sensing X X X X X X X X X X X
UL Listed X X X X X X X X X
Thermal imaging X X X X X X X X X X X
Phase-loading bar graph X X X X X X X X
LED for long-time pick-up X X X X X X X X X X X
LED for trip indication X X X X X X X X
Digital ammeter X X X X X X X X
Zone-selective interlocking

X X X X X X X
Communications O O O O X X X X
LCD dot matrix display X X X X
Advanced user interface X X X X
Protective relay functions X X X X
Neutral protection

X X X X
Contact wear indication X X X X
Incremental fine tuning of settings X X X X
Selectable long-time delay bands X X X X
Power measurement X X X X
Power quality measurements X X
Waveform capture X X

Requires neutral current transformer on three-phase four-wire loads.

Not available for 2.0A trip unit as upstream devices.


4
Requires M2C/M6C Programmable Contact Module.
Micrologic 5.0P
delay setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
.4
.5
.6
.7
.8
.9
.95
.98
1
short
tsd
(s)
on I
2
t
.
.
.
.
.
.
.3
.
0
off
instantaneous
long time
alarm Ir
x In
.5
1
2
4
8
12
16
20
tr
(s)
@6 Ir
24
test
0
6
1
3
3
4
8
0
85kA
30kA
24s
5000A
I(A)
Trip
0.4s
I i
x In
2
4
10
3
6
8
12
15
off
Micrologic 6.0P
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short
tsd
(s)
on I
2
t
.
.
.
.4
.
.
.
.
0
off
instantaneous
long time
alarm Ir
x In
ground fault
B
C
D
E
G
H
J
Ig tg
(s)
on I
2
t
.
.
.
.
.
.
.3
.
0
off
A
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
test
0
6
1
3
3
4
8
3
85kA
30kA
24s
5000A
I(A)
Trip
0.4s
I i
x In
2
4
10
3
6
8
12
15
off
Micrologic 5.0H
delay setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
.4
.5
.6
.7
.8
.9
.95
.98
1
short
tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
.5
1
2
4
8
12
16
20
tr
(s)
@6 Ir
24
test
I (A)
V (V)
P (kW)
E (kWh)
Harmonics
0
6
1
3
3
4
7
9
I i
x In
2
4
10
3
6
8
12
15
off
Micrologic 6.0H
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short
tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
ground fault
B
C
D
E
G
H
J
Ig tg
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
A
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
.5
1
2
4
8
12
16
20
tr
(s)
@6 Ir
24
test
0
6
1
3
3
4
8
2
I (A)
V (V)
P (kW)
E (kWh)
Harmonics
I i
x In
2
4
10
3
6
8
12
15
off
Micrologic 5.0H and 6.0H Trip Units Micrologic 5.0P and 6.0P Trip Units
22
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic 2.0, 3.0, and 5.0 Basic Trip Units
MICROLOGIC 2.0, 3.0, and 5.0 BASIC TRIP UNITS
The Micrologic 2.0, 3.0, and 5.0 trip units protect power circuits.
Protection Settings
1Overload signal (LED)
2Long-time rating plug
screw
3Long-time current setting
and tripping delay
4Instantaneous pickup
5Short-time pickup and
tripping delay
6Test connector
Protection thresholds and delays are set using the rotary switches.
A full-range of long-time settings are available via field-installable
adjustable rating plugs.
Overload protection
True RMS long-time protection
Thermal imaging: Active thermal imaging before and after tripping
Short-circuit protection.
Short-time RMS
Selection of I
2
t type (ON or OFF) for short-time delay
Instantaneous protection.
Neutral protection on four-pole circuit breakers.
3
5
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
2
4
6
.5
1
2
4
8
12
16
20
tr
(s)
@6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
3
4
6
8
10
12
15
off 2
test
1
Micrologic 5.0
0
6
1
3
3
2
5
3
Micrologic

5.0 Basic Trip Unit


0 I
t
I
r
t
r
I
i
0
6
1
3
3
3
2
2
Table 21: Micrologic 2.0 and 3.0 Basic Trip Unit Settings
Long-time
Protection
Current setting (A)
Tripping between 1.05
and 1.20 x I
r
I
r
= l
n
x...
2.0: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
3.0: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
Other ranges are available by changing rating plug
Maximum time delay (s)
Accuracy: 0 to 20%
t
r
at 1.5 x I
r
12.5 25 50 100 200 300 400 500 600
t
r
at 6 x I
r
0.5 1 2 4 8 12 16 20 24
t
r
at 7.2 x I
r
0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal imaging 20 minutes before or after tripping
Short-time
Protection
Current setting (A)
Accuracy: 10%
No delay
I
sd
= I
r
x... 2.0: 1.5 2 2.5 3 4 5 6 8 10
Instantaneous
Protection
Current setting (A)
Accuracy: 10%
I
i
= I
n
x... 3.0: 1.5 2 3 4 5 6 8 10 12
I
r
t
r
l
sd
t
sd
l
i
0 I
t
0
6
1
3
3
3
2
3
Table 22: Micrologic 5.0 Basic Trip Unit Settings
Long-time
Protection
Current setting (A)
Tripping between 1.05
and 1.20 x I
r
I
r
= l
n
x...
IEC: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
UL/ANSI: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
Other ranges are available by changing rating plug
Maximum time delay (s)
Accuracy: 0 to 20%
t
r
at 1.5 x I
r
12.5 25 50 100 200 300 400 500 600
t
r
at 6 x I
r
0.5 1 2 4 8 12 16 20 24
t
r
at 7.2 x I
r
0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal imaging 20 minutes before or after tripping
Short-time
Protection
Current setting (A)
Accuracy: 10%
l
sd
= I
r
x... 1.5 2 2.5 3 4 5 6 8 10
Maximum time delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
sd
Min. trip
time (ms)
20 80 140 230 350
Max. trip
time(ms)
80 140 200 320 500
Instantaneous
Protection
Current setting (A)
Accuracy: 10%
I
i
= I
n
x... 2 3 4 6 8 10 12 15 off
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic 2.0A, 3.0A, 5.0A, & 6.0A Trip Units with Ammeter
23
11/2004 19992004 Schneider Electric All Rights Reserved
MICROLOGIC

2.0A, 3.0A, 5.0A, & 6.0A TRIP UNITS WITH AMMETER
Micrologic A trip units protect power circuits and provide current measurements, overload protection,
and short-circuit protection. In addition, the 6.0A trip units also provide ground-fault protection for
equipment.
Protection Settings
Ammeter Measurements
Micrologic

A trip units measure the true RMS value of currents. They provide continuous current
measurement from 0.2 to 20 x I
n
with an accuracy of 1.5% (including sensors). No auxiliary source is
needed where I > 0.2 x I
n
. The optional external power supply (24 Vdc) makes it possible to display
currents where I < 0.2 x I
n
and to store values of the interrupted current. A digital LCD screen
continuously displays the most heavily loaded phase (Imax) or displays the Ia, Ib, Ic, Ig, and (on 4-pole
circuit breakers only) In stored current and setting values by successively pressing the navigation button.
Communication Network
Four wire, RTU, RS485
In conjunction with an optional communication network, the trip unit transmits the following parameters:
Setting values.
All ammeter measurements.
Tripping causes.
NOTE: Current-based protection functions require no auxiliary power source. When an external power
supply is added, the value of the interrupted current is stored by the trip unit. The reset button resets
alarms, and stored interrupted current indications.
1Test lamp and reset
2Indication of tripping
cause
3Digital display
4Three-phase bar graph
and ammeter
5Navigation buttons
6Overload signal (LED)
7Long-time rating plug
screw
8Long-time current setting
and tripping delay
9Short-time pickup and
tripping delay
10Instantaneous pickup
11Electronic push-to-trip
12Ground-fault pickup and
tripping delay
13Test connector
Protection thresholds and delays are set using the rotary switches. The
selected values are momentarily displayed in amperes and in seconds.
A full-range of long-time settings are available via field-installable rating
plug.
Overload protection (true RMS long-time protection).
Thermal imaging (active thermal imaging before and after tripping).
Short-circuit protection.
Short-time RMS
I
2
t ON or OFF for short-time delay
Instantaneous protection.
Ground-fault protection for equipment.
Residual ground-fault protection for equipment
Source ground-return ground-fault protection for equipment
Modified differential ground-fault protection (MDGF) for
equipment
Neutral protection on four-pole circuit breakers.
ZSI: Zone-selective interlocking (a ZSI terminal block may be used to
interconnect a number of trip units to provide total discrimination for
short-time and equipment ground-fault protection, without delay for
tripping). Not available for 3.0 A trip unit. Not available for 2.0 A trip
unit if installed as upstream device.
Micrologic 6.0 A
40
100%
%
menu
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
ground fault
B
C
D
E
F
G
H
J
Ig tg
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
A
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
test
2
4
10
3
6
8
12
15
off
kA
s
Ir= Ii=
tr=
Isd=
Ig=
tsd=
t=
tg=
In=
MAX
2
11
10
12
7
8
5
9
6
3
4
1
13
0
6
1
3
3
2
5
4
Micrologic

6.0A Trip Unit


24
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic 2.0A, 3.0A, 5.0A, & 6.0A Trip Units with Ammeter
0 I
t
I
r
t
r
I
i
0
6
1
3
3
3
2
4
Table 23: Micrologic 2.0A and 3.0A Trip Unit Settings
Long-time
Protection
Current setting (A)
Tripping between 1.05
and 1.20 x I
r
I
r
= l
n
x...
2.0A: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
3.0A: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
Other ranges are available by changing rating plug
Maximum time delay (s)
Accuracy: 0 to 20%
t
r
at 1.5 x I
r
12.5 25 50 100 200 300 400 500 600
t
r
at 6 x I
r
0.5 1 2 4 8 12 16 20 24
t
r
at 7.2 x I
r
0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal imaging 20 minutes before or after tripping
Short-time
Protection
Current setting (A)
Accuracy: 10%
No delay
I
sd
= I
r
x... 2.0A: 1.5 2 2.5 3 4 5 6 8 10
Instantaneous
Protection
Current setting (A)
Accuracy: 10%
I
i
= I
n
x... 3.0A: 1.5 2 3 4 5 6 8 10 12
I
r
t
r
l
sd
t
sd
l
i
0 I
t
0
6
1
3
3
3
2
5
Table 24: Micrologic 5.0A and 6.0A Trip Unit Settings
Long-time
Protection
Current setting (A)
Tripping between 1.05
and 1.20 x I
r
I
r
= l
n
x...
IEC: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
UL/ANSI: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
Other ranges are available by changing rating plug
Maximum time delay (s)
Accuracy: 0 to 20%
t
r
at 1.5 x I
r
12.5 25 50 100 200 300 400 500 600
t
r
at 6 x I
r
0.5 1 2 4 8 12 16 20 24
t
r
at 7.2 x I
r
0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal imaging 20 minutes before or after tripping
Short-time
Protection
Current setting (A)
Accuracy: 10%
l
sd
= I
r
x... 1.5 2 2.5 3 4 5 6 8 10
Maximum time delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
sd
Min. trip
time (ms)
20 80 140 230 350
Max. trip
time (ms)
80 140 200 320 500
Instantaneous
Protection
Current setting (A)
Accuracy: 10%
I
i
= I
n
x... 2 3 4 6 8 10 12 15 off
0 I
t
l
g
t
g
I
2
t off
I
2
t on
0
6
1
3
3
3
2
6
Table 25: Micrologic 6.0A Trip Unit Ground-fault Settings
Ground-fault pickup (A)
Accuracy: 10%
I
g
= l
n
x... A B C D E F G H J
l
n
400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
400 A < l
n
1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
l
n
> 1200 A 500 640 720 800 880 960 1040 1120 1200
Maximum time delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
g
Minimum trip time (ms) 20 80 140 230 350
Maximum trip time (ms) 80 140 200 320 500
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic 5.0P & 6.0P Trip Units with Power Metering
25
11/2004 19992004 Schneider Electric All Rights Reserved
MICROLOGIC 5.0P & 6.0P TRIP UNITS WITH POWER METERING
Protection Settings
Configuring Alarms and Other Protection Functions
When the cover is closed, the keypad may no longer be used to change the protection settings, but it
still provides access to the displays for measurements, histories, indicators, etc. Depending on the
thresholds and time delays set, the Micrologic P trip unit monitors current, voltage, power, frequency,
and phase sequence. Each threshold overrun may be signalled remotely via the communication
network.
Each threshold overrun may be combined with tripping (protection) or an indication carried out by an
optional M2C/M6C programmable contact (alarm), or both (protection and alarm).
Maintenance Record
The maintenance record can be consulted using the full-function test kit or remotely via the
communication network. It can be used as an aid in troubleshooting and to assist scheduling for device
maintenance operations.
Recorded indications include:
Highest current measured
Operation counter (both cumulative total and total since last reset)
Number of test kit connections
Number of trips in operating mode
Contact wear (Masterpact NW only)
1Test lamp and indication
reset
2Indication of tripping
cause
3High resolution screen
4Measurement display
5Maintenance indicators
6Protection settings
7Navigation buttons
8Overload signal (LED)
9Long-time rating plug
screw
10Long-time current
setting and tripping delay
11Short-time pickup and
tripping delay
12Instantaneous pickup
13Hole for settings
lockout pin
14Electronic push-to-trip
15Ground-fault pickup and
tripping delay
16Test connector
The adjustable protection functions of the 5.0P and 6.0P trip units
are identical to those of Micrologic A trip unit (overloads, short
circuits, equipment ground-fault protection); see page 23.
These units also feature:
Fine adjustment: Within the range below the rotary switch
setting, fine adjustments of pickups/delays in steps of 1 A/s
(except for short-time and ground-fault) are possible on the
keypad or remotely by the communication network.
Inverse definite minimum time lag (IDMTL) setting:
Coordination with fuse-type or medium-voltage protection systems
is optimized by adjusting the long-time delay curve around 6 x I
r

axis. This setting ensures better coordination with certain loads.
Neutral protection: On three-pole circuit breakers, neutral
protection may be set using the keypad or remotely using the
communication network to one of four positions:
OFF
1/2N (1/2 x I
n
)
1N (1 x I
n
)
2N (2 x I
n
)
NOTE: The neutral protection is disabled if the long-time curve is set
to one of the IDMTL protection settings.
Micrologic 6.0 P
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
ground fault
B
C
D
E
F
G
H
J
Ig tg
(s)
on I
2
t
.2
.3
. 4
.4
.1
.2
.3
.1
0
off
A
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
x In
test
2
4
10
3
6
8
12
15
off
1
4
5
6
7
15
9
10
11
12
16
8
13
14
2
3
0
6
1
3
3
2
5
5
85kA
30kA
24s
5000A
I
(A)
Trip
0.4s
Micrologic

6.0P Trip Unit


26
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic 5.0P & 6.0P Trip Units with Power Metering
Load Shedding and Reconnection Parameters
Load shedding and reconnection parameters can be set according to the power or the current flowing
through the circuit breaker. Load shedding is carried out by a remote computer via the communication
network or by an M2C or M6C programmable contact.
Indication Option via Programmable Contacts
The M2C (two contacts) and M6C (six contacts) programmable contacts may be used to signal
threshold overruns or status changes. They can be programmed using the keypad on the Micrologic P
trip unit or remotely using the communication network. These contacts are required to obtain data from
the protective relay functions on Type P and Type H trip units.
I 0
t
t
r
I
r
IDMTL
I
sd
t
sd
I
i
I
r
I
sd
I
i
0
6
1
3
3
3
2
7
Table 26: Micrologic 5.0P and 6.0P Trip Unit Settings
Long-time
(RMS)
Protection
Current setting (A)
Tripping between 1.05
and 1.20 x I
r
I
r
= l
n
x... IEC: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
I
r
= l
n
x... UL/ANSI: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
Other ranges are available by changing rating plug
Maximum time delay (s)
Accuracy: 0 to 20%
t
r
at 1.5 x I
r
12.5 25 50 100 200 300 400 500 600
t
r
at 6 x I
r
0.5 1 2 4 8 12 16 20 24
t
r
at 7.2 x I
r
0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
IDMTL Setting
Curve
slope
SIT VIT EIT HV Fuse DT
Thermal imaging 20 minutes before or after tripping
Short-time
(RMS)
Protection
Current setting (A)
Accuracy: 10%
l
sd
= I
r
x... 1.5 2 2.5 3 4 5 6 8 10
Maximum time delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
sd
Min. trip time (ms) 20 80 140 230 350
Max. trip time (ms) 80 140 200 320 500
Instantaneous
Protection
Current setting (A)
Accuracy: 10%
I
i
= I
n
x... 2 3 4 6 8 10 12 15 off
0 I
t
l
g
t
g
I
2
t off
I
2
t on
0
6
1
3
3
3
2
6
Table 27: Micrologic 6.0P Trip Unit Ground-fault Setting
Ground-fault pickup (A)
Accuracy: 10%
I
g
= l
n
x... A B C D E F G H J
l
n
400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
400 A < l
n
1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
l
n
> 1200 A 500 640 720 800 880 960 1040 1120 1200
Maximum time delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
g
Minimum trip time (ms) 20 80 140 230 350
Maximum trip time (ms) 80 140 200 320 500
Table 28: Settings for Alarms for Other Protection Functions for Micrologic 5.0P and 6.0P
Trip Units
Threshold Time Delay
Current
Current imbalance 0.05 to 0.6 x I
max
1 to 40 s
Maximum current I
max
: I
a
, I
b
, I
c
, I
n
, I
g
0.2 to 1.0 x I
n
15 to 1500 s
Voltage
Voltage imbalance 0.02 to 0.3 x V
n
1 to 40 s
Minimum voltage V
min
100 to 725 V (phase total) 0.25 to 0.5 s
Maximum voltage V
max
100 to 1200 V (between phases) 0.20 to 5.0 s
Power
Maximum power P
max
5 to 500 kW 0.2 to 20 s
Reverse power P
r
0.02 to 0.2 x P
n
0.5 to 20 s
Frequency
Minimum frequency F
min
45 to 65 Hz 0.2 to 5 s
Maximum frequency F
max
45 to 540 Hz 0.2 to 5 s
Phase Sequence A-B-C or A-C-B Instantaneous
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic 5.0P & 6.0P Trip Units with Power Metering
27
11/2004 19992004 Schneider Electric All Rights Reserved
Trip and Alarm Histories
The last ten trips and ten alarms are recorded in two separate history files that can be displayed on the
screen (sample displays are shown to the left). The following information is contained in these files:
Table 29: Load-shedding Settings for Current and Power Metering for Micrologic 5.0P and
6.0P Trip Units
Pick-up Drop-out
Threshold Time Delay Threshold Time Delay
Current I 0.5 to 1.0 x I
r
per phase 20% to 80% x t
r
0.3 to 1.0 x I
r
per phase 10 to 600 s
Power P 200 kW to 10 MW 10 to 3600 s 100 kW to 10 MW 10 to 3600 s
Trip History
Type of fault
Date and time of fault
Interrupted current
Contact wear
Alarm History
Type of alarm
Date and time of the alarm
Values measured at the time of the
alarm
0
6
1
3
3
2
6
2
Trip
history
30/06/1999
Vmax
27/07/1999
Isd
03/08/1999
Ir
0
6
1
3
3
2
6
3
I1 = 4800 A
I2 = 5600 A
I3 = 4000 A
IN = 200 A
03/08/1999
Ir = 4000 A
11:04:18 am
Trip
28
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic 5.0P & 6.0P Trip Units with Power Metering
Metering
The Micrologic P trip unit calculates in real time all electrical values V, A, W, VAR, VA, Wh, VARh,
VAh, Hz, power factor, and crest factor. The Micrologic P trip unit also calculates demand current and
demand power over an adjustable time period.
Real-time Metering: The value displayed on the screen is refreshed every second. Minimum and
maximum measurement values are stored in memory.
Demand Metering: The demand is calculated over a fixed or sliding time window that can be
programmed from five to 60 minutes. Depending on the contract signed with the power supplier,
specific programming makes it possible to avoid or minimize the cost of overrunning the subscribed
power. Maximum demand values are systematically stored and time stamped.
Communication Network
Four wire Modbus

, RTU, RS485The communication network may be used to:


Remotely read parameters for the protection functions
Transmit all the measurements and calculated values
Signal the causes of tripping and alarms
Consult the history files and the maintenance indicator record
In addition, an event log of the last 100 events and a maintenance record, which is stored in the trip
unit memory but not available locally, may be accessed via the communication network.
The Modbus communication system is compatible with Powerlogic

System Manager
TM
(SMS) software.
Event Log
The event log may be accessed by a remote computer via the communication network. All events are
time stamped and include:
Trips
Beginning and end of alarms
Modifications to settings and parameters
Loss of time
Overrun of wear indicators
Test kit connections.
Counter resets.
System faults (thermal self-protection, major fault and minor fault alarms).
Vinst.
VAB = 460 V
VBC = 464 V
VCA = 461 V
VAN = 270 V
VBN = 279 V
VCN = 273 V
Pinst.
P (kW)
2180
Q (kVAR)
- 650
S (kVA)
2280
F (Hz)
60.0
Pdemand
P (kW)
2180
Q (kVAR)
- 650
S (kVA)
2280
85kA
30kA
24s
5000 A
I(A)
Trip
0.4s
Imax
IA = 4800 A
IB = 4600 A
IC = 4000 A
IN = 200 A
I = 13 A
instant.
0
6
1
3
3
2
5
8
d
Current
Metering
Maximum
Current
Voltage
Metering
Power
Metering
Frequency
Power
Demand
Type of Measurement Unit of Measurement Measurement Source
Current
I
RMS
I
AVERAGE
I
PEAK/ 2
A
A
A
A, B, C or N
(A + B + C)/3
A, B, C or N
Voltage
V
RMS
V
RMS
V
IMBALANCE
V
V
%
(AB), (BC) and (CA)
(AN), (BN) and (CN)
V
RMS
Power
P, Q and S
EP, EQ and ES
Power factor
W, VAR, VA
Wh, VARh, VAh
Total
Total
Total
Frequency F Hz 50/60
Type of Measurement Unit of Measurement Measurement Source
Current I
DEMAND
A A, B, C or N
Power P, Q and S
DEMAND
W, VAR, VA Total
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic 5.0H & 6.0H Trip Units with Harmonic Metering
29
11/2004 19992004 Schneider Electric All Rights Reserved
MICROLOGIC 5.0H & 6.0H TRIP UNITS WITH HARMONIC METERING
In addition to the P functions, the Micrologic H trip units offer:
In-depth analysis of power quality including calculation of harmonics and the fundamentals.
Diagnostics aid and event analysis through waveform capture.
Customized alarm programming to analyze and track down a disturbance on the ac power system.
Systematic time stamping of all events and creation of logs.
Metering
The Micrologic H trip unit offers all the measurements carried out by the Micrologic P trip unit, with the
addition of phase-by-phase measurements of power and energy as well as calculation of:
Current and voltage total harmonic distortion (THD, thd).
Current, voltage and power fundamentals (50/60 Hz).
Harmonic components (amplitude and phase) up to the 31st current and voltage harmonic.
Real-time metering: The value displayed on the screen is refreshed every second. The table below
shows what is measured in real-time metering.
Demand Metering: Similar to the Micrologic P trip unit, demand values are calculated over a fixed or
sliding time window that can be set from five to 60 minutes.
Waveform Capture
Micrologic H trip units can capture and store current and voltage waveforms using digital sampling
techniques similar to those used in oscilloscopes. Using the information available in the captured
waveform, it is possible to determine the level of harmonics as well as the direction and amplitude of
the flow of harmonic power.
Users of Micrologic H trip units can record manually via the keypad the following waveforms:
The four currents: I
a
, I
b
, I
c
, and I
N
The three phase-to-phase voltages: V
ab
, V
bc
, and V
ca
Waveforms may be displayed on the graphic screen of Micrologic H trip units or communicated over a
networked system. The recording takes place over one cycle with a measurement range of 0 to 1.5 I
N

for current and 0 to 690 volts for voltage. The resolution is 64 points per cycle.
0
6
1
3
3
8
1
1
Micrologic 6.0 H
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
lg
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
.5
1
2
4
8
12
16
20
tr
(s)
@6 Ir
24
x In
test
I
(A)
V
(V)
P
(kW)
E
(kWh)
Harmonics
2
4
10
3
6
8
12
15
off
ground fault
B
C
D
E
F
G
H
J A
Ig
Micrologic

6.0H Trip Unit


Type of Measurement Unit of Measurement Measurement Source
Current
I
RMS
I
AVERAGE
I
PEAK/2
DI
IMBALANCE
A
A
A
%
A, B, C or N
(A + B + C) / 3
A, B, C or N
A, B, C or N
Voltage
V
RMS
V
RMS
V
IMBALANCE
V
V
%
(AB), (BC) and (CA)
(AN), (BN) and (CN)
V
RMS
Power
P, Q and S
EP, EQ and ES
Power factor
W, VAR, VA
Wh, VARh, VAh
Total
Total
Total
Frequency F Hz A, B, or C
Power Quality
Indicators
Fundamentals
THD
V and I harmonics
50/60 Hz component
%
Amplitude to phase
V, I, P, Q, and S
V/I
1, 2, 3, 4...50
Type of Measurement Unit of Measurement Measurement Source
Current I
DEMAND
A A, B, C or N
Power P, Q and S
DEMAND
W, VAR, VA Total
30
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic 5.0H & 6.0H Trip Units with Harmonic Metering
Customized Alarm Programming
The instantaneous value of each measurement can be compared to user-set high and low thresholds.
Overrun of a threshold generates an alarm. Programmable action can be linked to each alarm, including
circuit breaker opening, activation of an M2C or M6C contact, recording of measurements in a log, etc.
Event Logs
Each event is recorded with:
The date, time, and name of the event.
The event characteristics.
Additional Technical Characteristics for Type P and Type H Trip Units
Setting the display language: System messages can be displayed in six different languages:
English - US
English - UK
French
German
Spanish
Italian
The desired language is selected via the keypad.
Protection functions: All current-based protection functions require no auxiliary source. Voltage-
based protection functions are connected to AC power via a voltage measurement input built into
the circuit breaker on the bottom side. (Optional external voltage measurement is available.)
Accuracy of measurements (including sensors):
Voltage (V) 1%
Current (A) 1.5% (higher accuracy [1%] may be achieved with special calibration on the current
transformer [CT characterization option])
Frequency (Hz) 0.1 Hz
Power (W) and energy (Wh) 2.5%
The Micrologic H trip unit uses a dedicated metering data chain separate from the protection
data chain so that a greater number of data samples can be used for metering. This increases
the number of samples taken per time period, which in turn gives the H trip unit a higher degree
of metering accuracy.
Stored information: The fine setting adjustments, the last 100 events and the maintenance record
remain in the trip unit memory even when power is lost.
Reset: An individual reset, via the keypad or remotely, will reset alarms, minimum and maximum
data, peak values, counters and the indicators.
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsMicrologic Trip Unit Functions


31
11/2004 19992004 Schneider Electric All Rights Reserved
MICROLOGIC TRIP UNIT FUNCTIONS
Long-time Trip Functions
The long-time pickup switch sets the maximum current level the circuit
breaker will carry continuously. The maximum current level (I
r
) is the long-
time pickup setting multiplied by the sensor plug amperage (I
n
). If the current
exceeds this value for longer than the long-time delay time, the circuit
breaker will trip.
The long-time delay switch sets the length of time that the circuit breaker will
carry a sustained overload before tripping. Delay bands are labeled in
seconds of overcurrent at six times the ampere rating. For maximum
coordination, there are eight delay bands. Long-time delay is an inverse
time characteristic in that the delay time decreases as the current
increases.
The trip unit includes an alarm indicator that will be lit continuously when the
current is above 100% of the pickup setting.
Short-time Trip Functions
The short-time pickup switch sets the short-circuit current level at which
the circuit breaker will trip after the set short-time delay. The short-time
current (I
sd
) equals the short-time pickup setting multiplied by the long-
time pickup (I
r
).
The short-time delay switch sets the length of time the circuit breaker will
carry a short circuit within the short-time pickup range. The delay (based
on 10 times the ampere rating I
r
) can be adjusted to four positions of I
2
t
ramp operation (I
2
t ON) or five positions of fixed time delays (I
2
t OFF). I
2
t
ON delay is an inverse time characteristic in that the delay time
decreases as the current increases. Short-time delay for the 2.0 trip unit is
fixed at a delay band of 20 to 80 ms.
Instantaneous Trip Function
The instantaneous pickup switch sets the short-circuit current level at which the circuit breaker will trip
with no intentional time delay. The instantaneous current (I
i
) is equal to the instantaneous pickup
setting multiplied by the sensor plug amperage (I
n
).
The instantaneous function will override the short-time function if the instantaneous pickup is adjusted
at the same or lower setting than the short-time pickup. In trip units with both adjustable short-time and
instantaneous trip functions, the adjustable instantaneous trip can be disabled by setting
Instantaneous pickup to OFF.
Ground-fault Trip Functions
The ground-fault pickup switch sets the current level at which the circuit
breaker will trip after the set ground-fault delay. Ground-fault pickup values
(I
g
) are based on circuit breaker sensor plug (I
n
) only, not on the rating plug
multiplier (I
r
). Changing the rating plug multiplier has no effect on ground-fault
pickup values.
The ground-fault delay switch sets the length of time the circuit breaker will
carry ground-fault current which exceeds the ground-fault pickup level before
tripping. The delay (based on the sensor plug amperage (I
n
) can be adjusted
to four positions of I
2
t ramp operation (I
2
t ON) or five positions of fixed time
delays (I
2
t OFF). I
2
t ON delay is an inverse time characteristic in that the
delay time decreases as the current increases.
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I2t
.2
.3
.4 .4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
ground fault
B
C
D
E
F
G
H
J
Ig tg
(s)
on I2t
.2
.3
.4 .4
.1
.2
.3
.1
0
off
A
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
x In
3
4
6 8 10
12
15
off 2
test
Long-time
Pickup
Long-time
Delay
Alarm
Indicator
Long-time Trip Functions
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I2t
.2
.3
.4 .4
.1
.2
.3
.1
0
off
long time
alarm Ir
x In
ground fault
B
C
D
E
F
G
H
J
Ig tg
(s)
on I2t
.2
.3
.4 .4
.1
.2
.3
.1
0
off
A
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
.5
1
2
4
8
12
16
20
tr
(s)
@6 Ir
24
x In
3
4
6
8 10
12
15
off 2
test
Short-time
Pickup
Short-time
Delay
Instantane-
ous Pickup
instantaneous
Short-time and
Instantaneous Trip
Functions
Ground-
fault
Pickup
Ground-
fault
Delay
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I2t
.2
.3
.4 .4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm Ir
x In
ground fault
B
C
D
E
F
G
H
J
Ig tg
(s)
on I2t
.2
.3
.4 .4
.1
.2
.3
.1
0
off
A
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
.5
1
2
4
8
12
16
20
tr
(s)
@6 Ir
24
x In
3
4
6
8 10
12
15
off 2
test
Ground-fault Trip
Functions
32
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Micrologic

Electronic Trip SystemsCommunication Network


COMMUNICATION NETWORK
Masterpact NW/NT circuit breaker, and Micrologic

trip unit information is available via a Modbus



network
to Powerlogic

System Manager
TM
software (SMS) or other applications for reporting and recording.
Four wire Modbus, RTU, RS485Types of information available via Modbus communication network:
The Modbus circuit breaker communication feature, standard on the Micrologic P and H trip units and
available for the Micrologic A trip unit, is made up of:
A Modbus circuit breaker communication module (BCM) installed on the circuit breaker and
supplied with a kit for optional connection to the XF shunt close and MX shunt trip.
An optional Modbus cradle communication module (CCM) installed adjacent to the breaker cradle.
Cradle position switches are required for breaker position status (connected, test, or disconnected).
Modbus

Circuit Breaker Communication Module (BCM)


The Modbus circuit breaker communication module (BCM) is installed in the circuit breaker and
requires a separate, isolated 24 Vdc power source. The BCM is optically coupled to the Micrologic trip
unit to ensure a high level of isolation between the trip unit and the communication network. The
Modbus BCM provides circuit breaker status via dedicated O/F (open or closed), SDE (fault tripped),
CH (spring charged), and PF (ready-to-close) switches and provides the capability of remotely
controlling the circuit breaker. It also maintains an event log of circuit breaker status containing the
number of times the circuit breaker has experienced each status position with the date and time of the
last transition. This information and the remote control capability are available to a Modbus supervisor
system via a Modbus communication network.
Modbus

Cradle Communication Module (CCM)


The optional Modbus cradle communication module (CCM) is installed adjacent to the circuit breaker
cradle and is the gateway between the Modbus network and the Modbus BCM. The Modbus CCM
provides circuit breaker cradle status including connected position (CE), disconnected position (CD)
and test position (CT). The CCM monitors the communication parameters of the Modbus BCM and trip
unit when it detects a circuit breaker being racked from the cradle. When the circuit breaker is
reinstalled or a spare circuit breaker is installed and racked into the cradle, the CCM automatically
downloads the address, baud rate, and parity into the BCM. This capability allows a circuit breaker to be
replaced without the need to manually configure the communication parameters in the Modbus BCM.
The CCM maintains an event log of the date and time of the last circuit breaker transition. In order to
aid system communication troubleshooting, the CCM has visual indication of the modules operating
status by means of two LEDs.
Powerlogic

System Manager Software (SMS)


System Manager Software (SMS), used for power systems and energy management, provides the
human-machine interface (HMI) for electrical system information on a PC. SMS displays circuit breaker
and trip unit information in several formats including:
Screens including real-time readings, breaker status and remote control operation.
Tables displaying real-time readings, maintenance information and date and time of last operation.
Waveform captures including harmonic content.
Tabular displays of event logs and data logs.
Alarm annunciation and recording.
Circuit breaker identification and status.
Remote control of circuit breaker operation.
View and set protection function parameters.
Real-time readings.
Trip indication.
Alarm reporting.
Historical files and maintenance records.
Masterpact

NT and NW Universal Power Circuit Breakers


Accessories
33
11/2004 19992004 Schneider Electric All Rights Reserved
SECTION 3ACCESSORIES
OPTIONS FOR REMOTE OPERATION ...................................................................................................... 34
REMOTE OPERATION ACCESSORIES ..................................................................................................... 34
Terminals ................................................................................................................................................ 35
Spring-charging Motor (MCH) ................................................................................................................ 35
Shunt Trip (MX1) and Shunt Close (XF) ................................................................................................ 36
Additional Shunt Trip (MX2) or Undervoltage Trip (MN) ........................................................................ 37
Time-delay Module for Undervoltage Trip .............................................................................................. 38
Ready-to-close Switch (PF) .................................................................................................................... 38
Electrical Closing Push Button (BPFE) .................................................................................................. 39
Remote Reset (RES) and Automatic Reset After Fault Trip .................................................................. 39
SWITCHES AND SWITCH ACCESSORIES ................................................................................................ 39
Auxiliary Switch (OF) .............................................................................................................................. 39
Overcurrent Trip Switch (SDE) ............................................................................................................... 40
Connected/Closed Switch (EF) .............................................................................................................. 40
Cradle Position Switch ........................................................................................................................... 41
COMMUNICATION NETWORK ACCESSORIES ........................................................................................ 42
Modbus Circuit Breaker Communication Module (BCM) ........................................................................ 42
Modbus Cradle Communication Module (CCM) ..................................................................................... 43
MICROLOGIC TRIP UNIT ACCESSORIES ................................................................................................. 44
External Neutral Current Transformer (CT) ............................................................................................ 44
External Sensor for (SGR) and (MDGF) ................................................................................................ 44
Metering Current Transformers (CTs) .................................................................................................... 44
Voltage Measurement Inputs ................................................................................................................. 44
Sensor Plugs .......................................................................................................................................... 44
Adjustable Rating Plugs ......................................................................................................................... 44
External Power Supply Module .............................................................................................................. 45
External Battery Backup Module ............................................................................................................ 45
M2C/M6C Programmable Contact Modules ........................................................................................... 46
Zone-selective Interlocking (ZSI) ............................................................................................................ 46
Restraint Interface Module (RIM) ........................................................................................................... 47
CRADLE CONNECTIONS ........................................................................................................................... 48
TEST EQUIPMENT ...................................................................................................................................... 56
Hand-held Test Kit .................................................................................................................................. 56
Full-function Test Kit ............................................................................................................................... 56
CIRCUIT BREAKER LOCKING AND INTERLOCKING ............................................................................... 57
Push Button Lock ................................................................................................................................... 57
Open Position Padlock and Key Lock Provisions ................................................................................... 57
Cradle Locking and Interlocking ............................................................................................................. 58
Disconnected Position Locking .............................................................................................................. 58
Door Interlock ......................................................................................................................................... 58
Racking Interlock Between Racking Crank and Off Position .................................................................. 58
Cable Door Interlock Kit ......................................................................................................................... 58
Source Changeover Interlocks ............................................................................................................... 59
Open Door Racking Interlock ................................................................................................................. 59
Automatic Spring Discharge Mechanism ............................................................................................... 59
Cradle Rejection Kits .............................................................................................................................. 59
Rail Padlocking ....................................................................................................................................... 59
MISCELLANEOUS ACCESSORIES ............................................................................................................ 60
Mechanical Operation Counter (CDM) ................................................................................................... 60
Shutter and Shutter Lock ........................................................................................................................ 60
Door Escutcheon (CDP) ......................................................................................................................... 60
Transparent Cover (CCP) for Door Escutcheon ..................................................................................... 60
34
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesOptions for Remote Operation
OPTIONS FOR REMOTE OPERATION
Two options are available for remote operation of Masterpact circuit breakers: direct connection or a
communication network.
NOTE: When remote operation features are used, a minimum of four seconds is required for the spring
charging motor (MCH) to completely charge the circuit breaker closing springs prior to actuating the
shunt close (XF) device.
The wiring diagrams for these two options are shown below.
REMOTE OPERATION ACCESSORIES
The remote ON/OFF function is used to remotely open and close the circuit breaker. It is made up of
the following components:
A spring-charging motor (MCH) equipped with a spring-charged limit switch; see page 35 for more
information.
A shunt close (XF); see page 36 for more information.
A shunt trip (MX1); see page 36 for more information.
Optionally, the function may be completed with:
A ready-to-close contact (PF).
An electrical closing push button (BPFE).
A remote reset following a fault (RES).
The remote operation function may be completed with:
Auxiliary contacts (OF).
Overcurrent trip switch (SDE).
Figure 6: Wiring Diagram for Remote ON/OFF Function by Direct Connection
12 14
11
OF1
82 84
81
SDE
252 254
251
PF
A2
XF
A1
MX
C2
C1
MCH
B3 B2
B1
CH
Spring
Charged
Opening
Order
Closing
Order
Ready to
Close
Fault
Open
Closed 0
6
1
3
3
2
6
4
0
6
1
3
3
8
3
2
Masterpact Circuit Breaker Equipped
for Remote ON/OFF Function
Figure 7: Wiring Diagram for Remote ON/OFF Function by Communication Network
NOTE: Induced voltages in the circuit at terminal C2
and/or A2 can cause the shunt close to not work
properly. The best way to prevent induced voltages
is keep the circuit to terminal C2 and A2 as short as
possible. If it is impossible to keep the circuit less
than 10 feet (3 m), use an interposing relay near
terminal C2 or A2.
NOTE: When communicating MX1 or XF coils are
used, terminal (C3 or A3) must be connected to line
even if the communication module is not installed.
The bypass circuit through terminal C2/A2 is only
momentary duty for 0.5 sec. For continuous duty,
use the communications command.
MCH
B3 B2
B1
CH
COM
Supervisor
MX
C2 C3
C1
OF
PF
SDE
A2 A3
XF
A1
Spring
Charged
Opening
Order
10 ft
[3 m]
Closing
Order
0
6
1
3
3
2
6
5
CH
10 ft
[3 m]
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesRemote Operation Accessories
35
11/2004 19992004 Schneider Electric All Rights Reserved
Terminals
Spring-charging Motor (MCH)
The spring-charging motor automatically
charges the spring mechanism for closing
the circuit breaker and also recharges the
spring mechanism when the circuit
breaker is in the ON position.
Instantaneous reclosing of the circuit
breaker is thus possible following circuit
breaker opening. The spring-mechanism
charging handle is used only as a backup
if auxiliary power is absent.
The spring-charging motor is equipped as
standard with a limit switch contact (CH)
that signals the charged position of the
mechanism (springs charged).
Table 30: Terminal Characteristics
Standards UL 486E
Termination Capacity
2214 AWG solid or stranded wire with max. O.D. of insulation
3.5 mm
Current
Nominal 10 A
Minimum 100mA at 24 V
Pull-out Forces
22 AWG = 4.5 lbs (20 N)
20 AWG = 6.75 lbs (30 N)
18 AWG = 6.75 lbs (30 N)
16 AWG = 9 lbs (40 N)
14 AWG = 11.5 lbs (50 N)
Table 31: Spring Charging Motor Characteristics
Characteristics MCH
Voltage Ratings (V
n
)
Vac 50/60 Hz 48/60, 100/130, 200/250, 240/277, 380/415, 400/440, 480
Vdc 24/30, 48/60, 100/125, 200/250
Operating Threshold 0.85 to 1.1 V
n
Power Consumption 180 VA
Motor Overcurrent 23 x I
n
for 0.1 s
Charging Time 4 s maximum on NW, 3 s maximum on NT
Duty Cycle 3 cycles per minute maximum
Endurance
10,000 cycles for NW < 4000 A
5000 cycles for NW 4000 A
CH Contact 10 A at 240 V
Terminal
Spring Charging
Motor (NW)
Spring Charging
Motor (NT)
36
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesRemote Operation Accessories
Shunt Trip (MX1) and Shunt Close (XF)
Maximum Wire LengthThe inrush currents for these devices are approximately 200 VA. When low
supply voltages (12, 24 or 48 V) are used, the maximum allowable wire length is dependent on the
voltage and the wire size.
Shunt trip (MX1): When energized, the shunt trip instantaneously
opens the circuit breaker. The shunt trip may be supplied continuously
or intermittently.
Shunt close (XF): Remotely closes the circuit breaker if the spring
mechanism is charged.
Communication versions of the MX1 and XF are available for direct
connection via the circuit breaker communication module (BCM).
Table 32: Maximum Wire Length
4
Device
Percent of
Source Voltage
Source Voltage
12 Vdc 24 Vdc 48 Vdc
Wire Size
#14 AWG
(2.08 mm
2
)
#16 AWG
(1.31 mm
2
)
#14 AWG
(2.08 mm
2
)
#16 AWG
(1.31 mm
2
)
#14 AWG
(2.08 mm
2
)
#16 AWG
(1.31 mm
2
)
UVR (MN)
100%
159 ft
(48.5 m)
100 ft
(30.5 m)
765 ft
(233.2 m)
472 ft
(143.9 m)
85%
44 ft
(13.4 m)
29 ft
(8.8 m)
205 ft
(62.5 m)
129 ft
(39.3 m)
Shunt Trip (MX) and
Shunt Close (XF)
100%
57 ft
(17.4 m)
34 ft
(10.4 m)
314 ft
(95.7 m)
200 ft
(61.0 m)
1503 ft
(457.8 m)
944 ft
(287.7 m)
85%
27 ft
(8.2 m)
17 ft
(5.2 m)
205 ft
(62.5 m)
126 ft
(38.4 m)
957 ft
(291.7 m)
601 ft
(183.2 m)
4
The length shown in the table is for each of the two supply wires.
Table 33: Shunt Trip and Shunt Close Characteristics
Characteristics MX1 XF Min Max
Voltage Ratings (V
n
)
Vac
50/60 Hz
24 Vac 17 Vac 26 Vac
48 Vac 34 Vac 52 Vac
120 Vac 60 Vac 132 Vac
240 Vac 168 Vac 264 Vac
277 Vac 194 Vac 304 Vac
380 Vac 266 Vac 418 Vac
480 Vac 336 Vac 528 Vac
Vdc
12 Vdc 8 Vdc 13 Vdc
24 Vdc 17 Vdc 26 Vdc
48 Vdc 34 Vdc 52 Vdc
125 Vdc 88 Vdc 137 Vdc
250 Vdc 175 Vdc 275 Vdc
Operating Threshold 0.7 to 1.1 V
n
0.85 to 1.1 V
n
Power Consumption (VA or W) Steady-state/inrush 4.5/200
Circuit Breaker Response Time at V
n
50 ms 10
(NW and NT)
70 ms 10 (NW 4000 A)
80 ms 10 (NW > 4000 A)
55 ms (NT)
Shunt Trip (MX1) and
Shunt Close (XF)
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesRemote Operation Accessories
37
11/2004 19992004 Schneider Electric All Rights Reserved
Additional Shunt Trip (MX2) or Undervoltage Trip (MN)
This function opens the circuit breaker via an electrical order.
It is made up of:
Shunt trip (MX2, second MX) or,
Undervoltage trip (MN)
Instantaneous trip
Fixed undervoltage trip (time delayed) or,
Adjustable undervoltage trip (time delayed)
As shown in the wiring diagram for the remote tripping function on the next page, the delay unit
(installed outside the circuit breaker) may be disabled by an emergency off button to obtain non-
delayed opening of the circuit breaker.
When energized, the shunt trip (MX1) instantaneously opens the circuit breaker. A continuous supply
of power to the second shunt trip (MX2) locks the circuit breaker in the off position.
The undervoltage trip (MN) instantaneously opens the circuit breaker when its supply voltage drops to
a value between 35% and 70% of its rated voltage.
If the undervoltage trip is not energized, it is impossible to close the circuit breaker, either manually or
electrically. An attempt to close the circuit breaker produces no movement of the main contacts.
Closing is allowed when the supply voltage of the undervoltage trip reaches 85% of rated voltage.
Second Shunt Trip (MX2)
Table 34: Undervoltage Trip Characteristics
Characteristics MX2 Min Max
Voltage Ratings (V
n
)
Vac
50/60 Hz
24 Vac 17 Vac 26 Vac
48 Vac 34 Vac 52 Vac
120 Vac 60 Vac 132 Vac
240 Vac 168 Vac 264 Vac
277 Vac 194 Vac 304 Vac
380 Vac 266 Vac 418 Vac
480 Vac 336 Vac 528 Vac
Vdc
12 Vdc 8 Vdc 13 Vdc
24 Vdc 17 Vdc 26 Vdc
48 Vdc 34 Vdc 52 Vdc
125 Vdc 88 Vdc 137 Vdc
250 Vdc 175 Vdc 275 Vdc
Power Consumption (VA or W) Constant/Inrush 4.5/200
Circuit Breaker Response Time at V
n
50 ms 10
Figure 8: Wire Diagram for the Remote Tripping Function
D1
10 12
3 6
MN
D2
D1
MN
D2
MX2
C12
C1
or
1
Opening
Order
Opening
Order
Delayed
Opening
Order
Instantane-
ous Opening
Order
Delayed
Unit
38
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesRemote Operation Accessories
Time-delay Module for Undervoltage Trip
To eliminate circuit breaker nuisance tripping during
temporary voltage dips (micro-breaks), operation of
the undervoltage trip (MN) can be delayed. This
function is achieved by adding an external delay unit
(either adjustable or non-adjustable) to the
undervoltage trip (MN) circuit.
Ready-to-close Switch (PF)
The ready-to-close position switch indicates that the following
conditions are met and the circuit breaker can be closed:
The circuit breaker is open.
The closing springs are charged.
There is no standing closing or opening order.
Table 35: Time-delay Module Characteristics
Voltage Ratings of Undervoltage Trip
Vac 50/60 Hz 24/30, 48/60, 100/130, 200/250, 380/480
Vdc 24/30, 48/60, 100/130, 200/250
Voltage Ratings of Time-delay Module
Adjustable
Vac 50/60 Hz 48/60, 100/130, 200/250, 380/480
Vdc 48/60, 100/130, 200/250, 380/480
Non-Adjustable
Vac 50/60 Hz 100/130, 200/250
Vdc 100/130, 200/250
Operating Threshold
Opening 0.35 to 0.7 V
n
Closing 0.85 V
n
Power Consumption 4.5 VA/W (Holding), 200 VA/W (Inrush)
Time-delay Settings
Adjustable 0.5, 0.9, 1.5, and 3.0 s
Non-Adjustable 0.25 s
Time-delay Module for
Undervoltage Trip (MN)
Ready-to-close
Switch (PF)
Table 36: Ready-to-close Switch Characteristics
Type of Contact 1a/1b Form C
Maximum Number of Contacts 1
Breaking Capacity at a
Power Factor (p.f.) of 0.3
Standard: 100 mA/24V minimum load Low-Level: 2 mA/15 V minimum load
240/380 Vac 5 A 24/48 Vac 3 A
480 Vac 5 A 240 Vac 3 A
600/690 Vac 3 A 380 Vac 3 A
24/48 Vdc 3 A 24/48 Vdc 3 A
240 Vdc 0.3 A 125 Vdc 0.3 A
380 Vdc 0.15 A 250 Vdc 0.15 A
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesSwitches and Switch Accessories
39
11/2004 19992004 Schneider Electric All Rights Reserved
Electrical Closing Push Button (BPFE)
Located on the front panel of the circuit breaker, this push
button carries out electrical closing of the circuit breaker,
taking into account all of the safety functions that are part
of the control/monitoring system of the installation. The
push button is installed on the control circuit of the shunt
close, and connects to the communicating shunt close
module (XF-COM). Terminal A2 of XF-COM is used to
remotely close the circuit breaker.
Remote Reset (RES) and Automatic Reset After Fault Trip
Following tripping, the remote reset (RES) resets the overcurrent trip switch (SDE) and the
mechanical indicator. (Voltage rating: 110/130 Vac and 200/240 Vac.) RES is not compatible with
an additional overcurrent trip switch (SDE2).
Automatic reset after fault-trip: Following tripping, a reset of the mechanical indicator (reset button)
is no longer required to enable circuit breaker closing (factory adjustable only).
SWITCHES AND SWITCH ACCESSORIES
Auxiliary Switch (OF)
The rotary-type auxiliary
switches are directly driven by
the trip mechanism when the
minimum isolation distance
between the main circuit
breaker contact is reached.
Table 37: Auxiliary Switch Characteristics
Circuit Breaker Type NT NW
Supplied as Standard (Form C) 4 4
Maximum Number of Contacts 4 12
Breaking Capacity at a
Power Factor (p.f.) of 0.3
Standard (100 mA/24 V minimum load)
Vac
240/380 6 A 10 A
480 6 A 10 A
600/690 6 A 6 A
Vdc
24/48 2.5 A 10 A
240 0.5 A 10 A
380 0.3 A 3 A
Low-level (1 mA/4 V minimum load with a maximum current and voltage of 100 mA/10 V.
Note: If the maximum voltage and current is exceeded, the low-level function of the switch will be lost
but the switch will continue to function as a standard switch with the following specifications.
Vac
24/48 Vac 5 A 6 A
240 Vac 5 A 6 A
380 Vac 5 A 3 A
Vdc
24/48 Vdc 5/2.5 A 6 A
125 Vdc 0.5 A 6 A
250 Vdc 0.3 A 3 A
BPFE
A2 A3
XF
A1
Remote Order
to Close
0
6
1
3
3
8
0
4
Electrical Closing
Push Button (BPFE)
Auxiliary Switch (OF) with Four Contacts
for Masterpact NW Circuit Breaker
Masterpact NT Aux Switch
(OF) with One Contact
40
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesSwitches and Switch Accessories
Overcurrent Trip Switch (SDE)
Circuit breaker tripping due to a fault is signalled by a red
mechanical fault indicator (reset) and one overcurrent trip
switch (SDE).
Following tripping, the mechanical indicator must be reset
before the circuit breaker may be closed. An additional
overcurrent trip switch (SDE2) is supplied as an option and is
not compatible with the remote reset (RES).
Connected/Closed Switch (EF)
This switch combines the device connected and device closed
information to produce circuit closed information. The connected/closed
switch (EF) is supplied as an option and must be used with an additional
auxiliary switch (OF) and fits into its connector (it is not available for ring
terminals).
Table 38: Overcurrent Trip Switch Characteristics
Supplied as Standard 1a/1b Form C
Maximum Number of Contacts 2
Breaking Capacity at a Power Factor (p.f.) of 0.3
Standard: 100 mA/24 V minimum load Low-level: 2 mA/15 V minimum load
240/380 Vac
480 Vac
600/690 Vac
5 A
5 A
3 A
24/48 Vac
240 Vac
380 Vac
3 A
3 A
3 A
24/48 Vdc
240 Vdc
380 Vdc
3 A
0.3 A
0.15 A
24/48 Vdc
125 Vdc
250 Vdc
3 A
0.3 A
0.15 A
Table 39: Connected/Closed Switch Characteristics
Circuit Breaker Type NW (not available for NT)
Maximum Number of
Contacts
8a/8b Form C
Breaking Capacity at a
Power Factor (p.f.) of 0.3
Standard: 100 mA/24 V minimum
load
Low-level: 2 mA/15 V minimum
load
240/380 Vac 6 A 24/48 Vac 5 A
480 Vac 6 A 240 Vac 5 A
600/690 Vac 6 A 380 Vac 5 A
24/48 Vdc 2.5 A 24/48 Vdc 2.5 A
125 Vdc 0.8 A 125 Vdc 0.8 A
250 Vdc 0.3 A 250 Vdc 0.3 A
Overcurrent
Trip Switch
Connected/Closed
Switch (EF) NW only
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesSwitches and Switch Accessories
41
11/2004 19992004 Schneider Electric All Rights Reserved
Cradle Position Switch
Three series of optional auxiliary switches are available for the cradle:
Cradle position switches (CE) to indicate the connected position.
Cradle position switches (CD) to indicate the disconnected position. This
position is indicated when the required clearance for isolation of the power
and auxiliary circuits is reached.
Cradle position switches (CT) to indicate the test position. In this position, the
power circuits are disconnected and the auxiliary circuits are connected.
Table 40: Cradle Position Switch Characteristics
Circuit Breaker Type
NT NW

Possible Ring-terminal Combinations
CE CD CT CE CD CT CE CD CT
Maximum Push-in Switches with
Standard Actuators
3 2 1 3

1b 1a 1b
1b 1a, 1b 1b
1a, 2b 1a, 2b 1a
With Additional Actuators
9
6
6
0
3
0
0
0
3
1a, 2b 2a, 1b 1b
2a, 1b 1a, 2b 1b
1a 1a 1a
Breaking
Capacity at a
Power Factor
(p.f) of 0.3
Standard (100 mA/24 V minimum load) 3a 3a 1a
Vac
240 8 A 8 A 3b 3b 1b
380 8 A 8 A
Additional Actuators for Cradle
Position Switches on Masterpact NW
Circuit Breakers
A set of additional actuators may be
installed on the cradle to change or add
the functions of the cradle position
switches. Each standard actuator can be
replaced by any other actuator to
change the function of the cradle
position switch.
480 8 A 8 A
600/690 6 A 6 A
Vdc
24/48 2.5 A 2.5 A
125 0.8 A 0.8 A
250 0.3 A 0.3 A
Low-level (2 mA/15 V minimum load)
Vac
24/48 5 A 5 A
240 5 A 5 A
380 5 A 5 A
Vdc
24/48 2.5 A 2.5 A
125 0.8 A 0.8 A
250 0.3 A 0.3 A
Figure 9: Cradle Position Switch Actuators
Cradle Position
Switch (CE, CD, CT)
Actuator for up to Three
CE Switches (standard)
Actuator for up to Three
CD Switches (standard)
Actuator for up to Three
CT Switches (standard)
42
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCommunication Network Accessories
COMMUNICATION NETWORK ACCESSORIES
The Modbus

circuit breaker communication module (BCM) (standard on the Micrologic P and H trip
units and available for the Micrologic A trip unit) is comprised of a communication module installed on
the circuit breaker with a kit for connection to the shunt close (XF) and shunt trip (MX1) along with a set
of switches.
The Modbus cradle communication module (CCM) is connected to the BCM and cell switches.
Modbus Circuit Breaker Communication Module (BCM)
This module is independent of the trip unit. Installed on the circuit
breaker, behind the trip unit, it receives and transmits information on
the communication network. An optical link is used for
communication with the Micrologic A, P, and H trip units. Power
requirements: 30 mA, 24 Vdc.
The following may be connected to this module:
A set of dedicated switches which read the status of the circuit
breaker.
A set of actuators (MX/XF) to control the circuit breaker.
Figure 10: Communication Network Accessories
5
1
7
4
C
3
6
2
MODBUS Communication
Network with CCM
MODBUS Communication
Network without CCM
OF
SDE
PF
MX1
XF
CE
CD
BCM
CH
CT
CCM
(optional)
Terminal
Block
1Circuit breaker switches (OF, SDE, PF, and CH)
2Cradle communication module (CCM)
3Cradle switches (CD, CE and CT)
4Shunt trip (MX1) and shunt close (XF)
5Communication bus
6Circuit breaker communication module (BCM)
7Trip unit
Circuit Breaker
Communication
Module (BCM)
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCommunication Network Accessories
43
11/2004 19992004 Schneider Electric All Rights Reserved
Modbus

Cradle Communication Module (CCM)


This module makes it possible to address the cradle and to
maintain the address when the circuit breaker or the BCM is
replaced. Cradle position switches connected to the module
determine and communicate the position of the circuit breaker in
the cradle. Power requirements: 30 mA, 24 Vdc.
Table 41: Characteristics
Circuit Breaker Identification
ID Code, Address
Size, Rating, Performance
Type of Trip Unit
Type of Long-time Rating Plug
Status Indication
ON/OFF Indication
Connected/Disconnected/Test Pos.
Ready-to-close
Fault Trip
Controls
Opening/Closing
Settings
Circuit
Breaker and
Trip Unit
A P H
Reading of Settings on Rotary Switches
Fine Settings in the Range Imposed by the Rotary Switches
Setting of Protection and Alarms
Customized Alarm Programming
Operating and Maintenance Aids
Reading of Protection and Alarms
Standard
Set
Customized
Reading of Measurements
Current
Voltages, frequency, power, etc.
Power quality: Fundamentals and harmonics
Waveform Capture
Histories
History of trips and alarms
4

Log of trips and alarms
Indicators
Contact wear, counters, etc.
Maintenance record
4
Up to 10 trips and 10 alarms.
Cradle
Communication
Module (CCM)
44
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesMicrologic Trip Unit Accessories
MICROLOGIC

TRIP UNIT ACCESSORIES
External Neutral Current Transformer (CT)
The sensor is installed on the neutral conductor for
neutral protection and metering and residual current
ground-fault protection for equipment.
NOTE: The rating of the external neutral current
transformer must be compatible with the rating of the
circuit breaker.
External Sensor for Source Ground-return
(SGR) and Modified Differential Ground-fault (MDGF) Protection
NOTE: MDGF and SGR are for use on circuit breakers with 1600 A and higher sensors.
For SGR System: The sensor is installed around the connection of the transformer neutral point to
ground and connects to the Micrologic 6.0A, 6.0P or 6.0H trip units. SGR requires a modified
differential ground-fault (MDGF) sensor and MDGF interface module to connect to the trip unit.
For MDGF System: The MDGF sensor is installed on each phase and neutral and connects to the
Micrologic 6.0A, 6.0P or 6.0H trip units. A MDGF interface module is required.
Metering Current Transformers (CTs)
Metering current transformers are optional and are
mounted on the NW UL or ANSI cradle. They permit
connection to the standard metering device. All
metering transformers are accurate with the 0.3%
accuracy class, 5 A output ratio at full load (for example,
a 1600 A metering CT would send 5 A at the full load of
1600 A). A standard wiring harness is also included for
factory-installed MCTs. Not available for neutral pole on
a 4-pole circuit breaker.
Voltage Measurement Inputs
Voltage measurement inputs are required for power
measurements. As standard, the trip unit is supplied by internal
voltage measurement inputs placed on the bottom terminals of
the circuit breaker. On request, the internal voltage
measurement inputs may be replaced by an external source.
Sensor Plugs
Sensor plugs (standard) are used to set the sensor rating (I
n
) of the
circuit breaker, are field replaceable and are offered at 50100% of
frame rating.
External Neutral Current
Transformer (CT)
Toroidal Current
Transformers
(CTs) for W-frame
Circuit Breakers
Voltage
Measurement
Inputs
Sensor Plug
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesMicrologic Trip Unit Accessories
45
11/2004 19992004 Schneider Electric All Rights Reserved
Adjustable Rating Plugs
Eight interchangeable rating plugs are available to limit the
long-time threshold setting range for greater versatility.
External Power Supply Module
Power supply modules are available in six input voltages: 24/30 Vdc,
48/60 Vdc, 125 Vdc, 110/130 Vac, 200/240 Vac, and 380/415 Vac
(all +10%, -15%). The output voltage for each is 24 Vdc; the output power is
5 VA/5 W (ripple < 5%). The modules are not UL Listed.
When used with the Micrologic A, P, and H trip units, a power supply module
makes it possible to:
Display currents less than 20% of sensor (I
n
).
Maintain display of tripping causes after opening of the circuit breaker.
Store the value of the interrupted current (P and H trip units only).
Power the M2C module.
External Battery Backup Module
The external battery backup module provides up to 12 hours of backup
power for the power supply module.
Table 42: Adjustable Rating Plug Settings
Rating Plug Switch Settings I
r
= I
n
x...
UL
Listed/ANSI
Certified
Type A

Type B
Type C
Type D
0.4
0.4
0.42
0.4
0.45
0.44
0.50
0.48
0.5
0.5
0.53
0.64
0.6
0.56
0.58
0.7
0.63
0.63
0.67
0.8
0.7
0.75
0.75
0.9
0.8
0.88
0.83
0.93
0.9
0.95
0.95
0.95
1
1
1
1
Type E
Type F
Type G
Type H
0.6
0.84
0.66
0.48
0.7
0.86
0.68
0.5
0.75
0.88
0.7
0.52
0.8
0.9
0.72
0.54
0.85
0.92
0.74
0.56
0.9
0.94
0.76
0.58
0.93
0.96
0.78
0.6
0.95
0.98
0.8
0.62
1
1
0.82
0.64
IEC Rated
Type R

Type S
Type T
0.4
0.4
0.8
0.5
0.45
0.82
0.6
0.5
0.85
0.7
0.55
0.88
0.8
0.6
0.9
0.9
0.65
0.92
0.95
0.7
0.95
0.98
0.75
0.98
1
0.8
1
Type P
(off plug)
No long-time protection.

Standard
Adjustable
Rating Plug
External Power
Supply Module
External Battery
Backup Module
46
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesMicrologic Trip Unit Accessories
M2C/M6C Programmable Contact Modules
These contacts are used with the Micrologic P and H control units, and indicate the type of fault and
instantaneous or delayed threshold overruns (i.e trip unit protection pick-up, current/voltage
unbalance, under/over voltage, reverse power, phase rotation, under/over frequency, and load
shedding). The M2C unit is powered from the control units 24 Vdc source (100 mA consumption); the
M6C unit requires an external 24 Vdc power supply (100 mA consumption).
They are programmed via the control unit using a
keypad or via a supervisory station with the COM
communication option. They may be programmed:
with instantaneous return to the initial state.
without return to the initial state.
with return to the initial state following a delay.
Zone-selective Interlocking (ZSI)
Table 43: Characteristics for M2C/M6C Programmable Contacts
Minimum Load 100 mA/24 V
Breaking Capacity at a Power Factor (p.f.) of 0.7
240 Vac 5 A
380 Vac 3 A
24 Vdc 1.8 A
48 Vdc 1.5 A
125 Vdc 0.4 A
250 Vdc 0.15 A
Figure 11:
Zone-selective interlocking (ZSI) is used to
reduce the stress on electrical distribution
equipment during fault conditions by reducing
the time it takes to clear the fault, while
maintaining system coordination between
overcurrent protective devices.
During a short-circuit or ground-fault condition
on a ZSI system, the device directly ahead of
the fault sends a signal upstream via control
wiring to restrain upstream circuit breakers from
tripping and then trips with no intentional time
delay to clear the fault. Upstream devices which
receive a restraint signal obey their short-time
and/or ground-fault delay settings to maintain
coordination in other areas of the system.
Upstream devices that do not receive a restraint
signal trip with no intentional time delay.
For ZSI to work, trip settings must be
coordinated so a downstream circuit breaker will
trip before an upstream circuit breaker under
overload, short-circuit or ground-fault
conditions. (Effective coordination requires a
system coordination study.)
M2C Programmable
Contact Module
M6C Programmable
Contact Module
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
Fault 1
Fault 2
0
6
1
3
3
8
0
1
Downstream
Circuit Breakers
Upstream
Circuit Breaker
A
B
Fault 1The upstream circuit breaker (A) will clear the
fault with no intentional delay, regardless of its time-delay
setting.
Fault 2Circuit breaker (B) will inform upstream circuit
breaker (A) that it is clearing the fault. This will prevent
circuit breaker (A) from tripping instantaneously. Circuit
breaker (A) will trip at the end of its time delay setting if
the fault is not cleared during this time.
Example of Zone-selective Interlocking
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesMicrologic Trip Unit Accessories
47
11/2004 19992004 Schneider Electric All Rights Reserved
Restraint Interface Module (RIM)
The restraint interface module (RIM) is used to allow zone-selective
interlocking communications between circuit breakers with old
Micrologic

, Merlin Gerin, or Federal Pioneer trip units and GC series


ground-fault relays.
Downstream circuit breakers with Micrologic 2.0A, 5.0A, 5.0P, 5.0H,
6.0A, 6.0P, and 6.0H trip units can restrain up to 15 upstream circuit
breakers with Micrologic 5.0A, 5.0P, 5.0H, 6.0A, 6.0P and 6.0H trip
units without requiring a restraint interface module. If the number of
upstream circuit breakers exceeds 15, then a RIM is required.
Table 44: RIM Requirements
M
i
c
r
o
l
o
g
i
c

T
r
i
p

U
n
i
t

M
i
c
r
o
l
o
g
i
c

S
e
r
i
e
s

B

T
r
i
p

U
n
i
t
S
q
u
a
r
e

D

G
C
-
1
0
0

R
e
l
a
y
S
q
u
a
r
e

D
G
C
-
2
0
0

R
e
l
a
y
M
e
r
l
i
n

G
e
r
i
n

S
T
R
5
8

T
r
i
p

U
n
i
t
s
F
e
d
e
r
a
l

P
i
o
n
e
e
r

U
S
R
C

a
n
d

U
S
R
C
M

T
r
i
p

U
n
i
t
s
Micrologic Trip Unit

15
4
R R 15 15 R
Square D Micrologic Series B Trip Units R 26 R R R 15
Square D GC-100 Relay R R 7 R R R
Square D GC-200 Relay 15 R R 15 15 R
Merlin Gerin STR58 Trip Units 15 R R 15 15 R
Merlin Gerin STR53 Trip Units 15 R R 15 15 R
Federal Pioneer USRC and USRCM Trip Units R 15 R R R 15
Square D Add-on Ground Fault Module for Equipment Protection R 5 R R R R
R Denotes that a Restraint Interface Module (RIM) is required.

Includes 2.0A (as a downstream trip unit only), 5.0A, 5.0P, 5.0P, 5.0H, 6.0A, 6.0P, and 6.0H trip units.
4
Number denotes maximum number of upstream circuit breakers that can be restrained without requiring a RIM.
Restraint Interface
Module (RIM)
Downstream Device
(sends output to RIM)
Upstream Device
(receives output to RIM)
48
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCradle Connections
CRADLE CONNECTIONS
Table 45: Masterpact NW UL Listed/ANSI Certified 3-pole/4-pole Drawout Circuit Breakers (Rear Connections)
Connector
Type
Ampere
Rating
3-pole Layout (Back/Side/Top) 4-pole Layout (Back/Side/Top)
Rear-connected
T Vertical
(RCTV)
800 to 2000 A
2500 to 3000 A
3200 A (L1)
4000 to 5000 A
6000 A
Rear-connected
T Horizontal
(RCTH)
800 to 2000 A
2500 to 3000 A
3200 A (L1)
4000 to 5000 A
Rear-connected
Offset Vertical
(RCOV)
3200 A
2000 A (L1/L1F)
0
6
1
3
3
6
6
9
0
6
1
3
4
0
3
9
0
6
1
3
3
6
8
3
0
6
1
3
4
0
2
8
0
6
1
3
3
6
8
0
0
6
1
3
4
0
5
0
0
6
1
3
3
6
9
8
0
6
1
3
4
0
4
5
0
6
1
3
3
6
7
5
0
6
1
3
4
0
3
8
0
6
1
3
3
6
8
4
0
6
1
3
4
0
2
7
0
6
1
3
3
6
8
1
0
6
1
3
4
0
4
9
0
6
1
3
3
5
7
4
0
6
1
3
3
5
7
5
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCradle Connections
49
11/2004 19992004 Schneider Electric All Rights Reserved
Table 46: Masterpact NW UL Listed/ANSI Certified 3-pole/4-pole Drawout Circuit Breakers (Front Connections)
Connector
Type
Ampere
Rating
3-pole Layout (Back/Side/Top) 4-pole Layout (Back/Side/Top)
Front-connected
Flat (FCF)
800 to 2000 A
3200 A (L1)
4000 A
Front-connected
T (FCT)
800 to 3000 A
3200 A (L1)
4000 to 5000 A
0
6
1
3
3
6
7
0
0
6
1
3
4
0
3
7
0
6
1
3
3
6
8
5
0
6
1
3
4
0
7
2
0
6
1
3
3
6
7
1
0
6
1
3
4
0
2
6
0
6
1
3
3
6
8
2
0
6
1
3
4
0
4
7
50
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCradle Connections
Table 47: Masterpact NW UL Listed/ANSI Certified 3-pole/4-pole Fixed Circuit Breakers (Rear Connections)
Connector
Type
Ampere Rating 3-pole Layout (Back/Side/Top) 4-pole Layout (Back/Side/Top)
Rear-connected
T Vertical
(RCTV)
800 to 2000 A
2500 to 3000 A
4000 to 5000 A
6000 A
Rear-connected
T Horizontal
(RCTH)
800 to 2000 A
2500 to 3000 A
4000 to 5000 A
Rear-connected
Offset Vertical
(RCOV)
3200 A
Rear-connected
Offset Vertical
(Special)
4000 A (B)
(W-frame)
0
6
1
3
3
6
8
7
0
6
1
3
4
4
0
8
0
6
1
3
3
6
9
0
0
6
1
3
4
0
6
8
0
6
1
3
3
6
9
1
0
6
1
3
4
4
1
7
0
6
1
3
3
7
0
0
0
6
1
3
4
4
1
5
0
6
1
3
3
6
8
6
0
6
1
3
4
0
6
9
0
6
1
3
3
7
0
0
0
6
1
3
4
0
7
0
0
6
1
3
3
6
9
2
0
6
1
3
3
5
7
4
0
6
1
3
3
5
7
5
0
6
1
3
5
5
0
3
0
6
1
3
5
5
0
4
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCradle Connections
51
11/2004 19992004 Schneider Electric All Rights Reserved
Table 48: Masterpact NW UL Listed/ANSI Certified 3-pole/4-pole Fixed Circuit Breakers (Front Connections)
Connector
Type
Ampere Rating 3-pole Layout (Front/Side/Top) 4-pole Layout (Front/Side/Top)
Front-connected
Flat (FCF)
800 to 2000 A
Front-connected
T (FCT)
800 to 3000 A
0
6
1
3
3
6
8
8
0
6
1
3
4
4
0
5
0
6
1
3
3
6
8
9
0
6
1
3
4
4
0
9
52
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCradle Connections
Table 49: Masterpact NW IEC Rated 3-pole/4-pole Drawout Circuit Breakers
Connector
Type
Ampere
Rating
3-pole Layout 4-pole Layout
Front-connected
Flat (FCF)
800 to 3200 A
Rear-connected
T Vertical
(RCTV)
800 to 3200 A
4000 A
5000 A
6300 A
Rear-connected
T Horizontal
(RCTH)
800 to 3200 A
4000 A
5000 A
0
6
1
3
4
4
5
7
0
6
1
3
4
4
6
4
0
6
1
3
4
4
5
5
0
6
1
3
4
4
6
2
0
6
1
3
4
4
5
8
0
6
1
3
4
4
6
5
0
6
1
3
4
4
6
0
0
6
1
3
4
4
6
7
0
6
1
3
4
8
4
3
0
6
1
3
4
8
4
4
0
6
1
3
4
4
5
6
0
6
1
3
4
4
6
3
0
6
1
3
4
4
5
9
0
6
1
3
4
4
6
6
0
6
1
3
4
4
6
1
0
6
1
3
4
4
6
8
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCradle Connections
53
11/2004 19992004 Schneider Electric All Rights Reserved
Table 50: Masterpact NW IEC Rated 3-pole/4-pole Fixed Circuit Breakers
Connector
Type
Ampere
Rating
3-pole Layout 4-pole Layout
Front-connected
Flat (FCF)
800 to 3200 A
Rear-connected
T Vertical
(RCTV)
800 to 3200 A
4000 A
5000 A
6300 A
Rear-connected
T Horizontal
(RCTH)
800 to 3200 A
4000
5000 A
0
6
1
3
4
4
7
5
0
6
1
3
4
4
7
8
0
6
1
3
4
4
7
4
0
6
1
3
4
4
7
7
0
6
1
3
4
4
7
9
0
6
1
3
4
4
8
1
0
6
1
3
4
4
8
3
0
6
1
3
4
4
8
5
0
6
1
3
4
8
4
5
0
6
1
3
4
8
4
6
0
6
1
3
4
4
7
3
0
6
1
3
4
4
7
6
0
6
1
3
4
4
8
0
0
6
1
3
4
4
8
2
0
6
1
3
4
4
8
4
0
6
1
3
4
4
8
6
54
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCradle Connections
Table 51: Masterpact NT UL Listed/ANSI Certified 3-pole/4-pole Fixed and Drawout Circuit Breakers
Connector Type Drawout Circuit Breakers Fixed Circuit Breakers
Front-connected Flat (FCF)
800 to 1200 A
Rear-connected T Vertical
(RCTV)
800 to 1200 A
Rear-connected T Horizontal
(RCTH)
800 to 1200 A
Rear-connected Vertical
1600 A
N/A
0
6
1
3
5
2
6
1
0
6
1
3
5
2
6
2
0
6
1
3
5
2
6
3
0
6
1
3
5
2
6
4
0
6
1
3
5
2
6
5
0
6
1
3
5
2
6
6
0
6
1
3
5
5
0
2
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCradle Connections
55
11/2004 19992004 Schneider Electric All Rights Reserved
Table 52: Masterpact NT IEC Rated 3-pole/4-pole Fixed and Drawout Circuit Breakers
Connector Type Drawout Circuit Breakers Fixed Circuit Breakers
Front-connected Flat (FCF)
800 to 1600 A
Rear-connected T Vertical
(RCTV)
800 to 1600 A
Rear-connected T Horizontal
(RCTH)
800 to 1600 A
56
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesTest Equipment
TEST EQUIPMENT
Hand-held Test Kit
The hand held test kit may be used to:
Verify trip unit operation, the mechanical operation of the
circuit breaker, and the electrical continuity of the
connection between the trip solenoid and the trip unit.
Supply control power to the trip unit for settings via the
keypad when the circuit breaker is open
(Micrologic type A, P or H trip units).
Inhibit thermal imaging for primary injection test
(Micrologic type A, P or H trip units).
Inhibit ground fault for primary injection test
(Micrologic type A, P or H trip units).
Self-restrain zone-selective interlocking (ZSI).
Full-function Test Kit
The full-function test kit can be used to verify
LSIG functionality.
Optional
Can be used to check trip unit operation, for example:
Display of settings
Operating tests on the electronic component
Automatic and manual tests on protection functions
(trip curve verification)
Tests on the zone-selective interlocking
(ZSI) functions
Inhibit thermal imaging for primary injection testing
Self-restrain zone-selective interlocking (ZSI)
Can also be used to:
Check mechanical operation of the circuit breaker
Check the electrical continuity of connection between the trip solenoid and the trip unit.
Print the trip unit and circuit breaker test report when used in conjunction with a PC.
FFTK report generator software (cat. no. FFTKRPT-V1-0) is required.
Hand-held Test Kit
Full-function
Test Kit
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCircuit Breaker Locking and Interlocking
57
11/2004 19992004 Schneider Electric All Rights Reserved
CIRCUIT BREAKER LOCKING AND INTERLOCKING
Push Button Lock
A transparent cover blocks access to the
push buttons used to open and close the
device. It is possible to independently lock
the opening button and/or the closing
button. The push buttons may be locked
using:
One to three padlocks: 3/16 to 5/16
diameter, not supplied.
A lead seal.
Two screws.
Open Position Padlock and Key Lock Provisions
The circuit breaker is locked in the off position by physically
keeping the opening push button pressed down using one of the
following:
One to three padlocks: 3/16 to 5/16 diameter, not supplied.
Key locks: One or two Kirk

or Federal Pioneer

key locks
(keyed alike or differently) are available for UL Listed/ANSI
Certified circuit breakers; for IEC Rated circuit breakers,
Ronis

, Castell

, or Profalux

key locks are available.


(Masterpact

NT circuit breakers may have only one key


lock on the circuit breaker.)
Keys may be removed only when locking is effective. The key
locks are available in any of the following configurations:
One key lock.
One key lock mounted on the device + one identical key lock supplied separately for interlocking
with another device.
Two different key locks mounted on the circuit breaker for double locking.
A locking kit for installation of one or two key locks may be ordered separately.
Table 53: Circuit Breaker and Switch Locking Options
Type of Locking Maximum Number of Locks
Pushbutton Locking Using padlocks Three padlocks
Open Position Locking
Using key locks Two key locks (optional)
Using padlocks and key locks Up to three padlocks and two key locks (optional)
push OFF
O I
push ON

0
6
1
3
3
4
6
3
0
6
1
3
3
4
6
2
Push Button Lock
Open Position Key
Lock (NW)
Open Position Padlock
Provision (NW)
58
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCradle Locking and Interlocking
CRADLE LOCKING AND INTERLOCKING
Disconnected Position Locking
The circuit breaker can be locked in the disconnected
position by key interlock (optional) or padlock (standard).
The key interlock is on the cradle and accessible with the
door locked.
Key interlock, Kirk or Federal Pioneer are available for
UL/ANSI circuit breakers; for IEC circuit breakers, Ronis,
Castell, or Profalux key locks are available. Captive key
when unlocked.
Locking on disconnected, test, and connected positions
is optional for IEC circuit breakers and standard for
UL/ANSI circuit breakers.
Door Interlock
The door interlock prevents the compartment door from being opened
when the circuit breaker is in the connected or test position. If the circuit
breaker is put into the connected position with the door open, the door can
be closed without disconnecting the circuit breaker. For greater protection,
this interlock can be used in conjunction with the open door racking
interlock.
Racking Interlock Between Racking Crank and Off Position
The racking interlock is standard for UL and ANSI circuit breakers, and optional for IEC circuit
breakers. It prevents insertion of the racking crank unless the OFF push button is pressed. Not
available for IEC Rated Masterpact NT circuit breakers.
Cable Door Interlock Kit
This option prevents the compartment door from being opened when the circuit breaker is in the closed
position. This kit includes:
Test 0
6
1
3
3
4
6
4
Key Interlock
Padlock Hasp
Disconnected
Position Locking
Provisions
0
6
1
3
3
7
8
9
Door Interlock (NW)
Figure 12: Cable Door Interlock Kit Contents
Kit Contents
(A) Panel Interlocking Plate
(B) Circuit Breaker Interlocking Plate
(C) Interlocking Cables
(D) Bolts with Washers
(E) Guide-bolt with Washer
(F) Interlocking Bracket
(G) Calibration Tray
0
6
1
3
4
1
8
9A
B
C
E
F
G
D
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesCradle Locking and Interlocking
59
11/2004 19992004 Schneider Electric All Rights Reserved
Source Changeover Interlocks
Source changeover interlocks allow mechanical interlocking between two or three circuit breakers.
(fixed and drawout)
Open Door Racking Interlock
The racking interlock prevents racking in the circuit breaker when the door is
open. (Insertion of the circuit breaker racking crank is not possible when the
compartment door is open.)
Automatic Spring Discharge Mechanism
The automatic spring discharge mechanism is standard for UL and ANSI
circuit breakers, and optional for IEC circuit breakers. It releases the closing
spring energy when the circuit breaker is moved from the disconnected
position to the fully withdrawn position. Not available for IEC Rated
Masterpact NT circuit breakers.
Cradle Rejection Kits
The cradle rejection feature (standard) ensures that only the properly designated circuit breaker or
switch is matched with the selected cradle assembly.
Rail Padlocking
Rail padlocking is standard for UL, ANSI, and IEC cradles. When used in combination with the
disconnected position locking device, rail padlocking prevents the movement of the circuit breaker from
the disconnected position to the fully withdrawn position when the padlock hasp is pulled out and locked.
Figure 13: Source Changeover Interlocks
Interlocking Two Circuit Breakers
Interlocking Two Mains Using Rods
Interlocking Two Mains Using Cables
Interlocking Three Circuit Breakers Using Cables
Interlocking Two Mains and One Generator
Interlocking Two Mains and One Tie
Interlocking Three Mains
Figure 14: Cradle Rejection Kits
0
6
1
3
3
9
5
6
Two NW Circuit Breakers
Interlocked Using Rods
Three NW Circuit Breakers
Interlocked Using Cables
0
6
1
3
3
7
9
0
Open Door Racking
Interlock (NW)
0
6
1
3
3
8
0
2
Automatic Spring
Discharge Mechanism (NW)
Cradle Rejection Kit
Contents (NW)
Cradle Rejection Kit Contents (NT)
60
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


AccessoriesMiscellaneous Accessories
MISCELLANEOUS ACCESSORIES
Mechanical Operation Counter (CDM)
The mechanical operation counter (CDM) registers the total number of
operating cycles. One CDM is installed per circuit breaker.
Shutter and Shutter Lock
The shutters automatically block access
to the main disconnects when the circuit
breaker is in the disconnected, test, or
fully withdrawn position. The shutter lock
is used to prevent connection of the
circuit breaker or to lock the shutters in
the closed position.
Door Escutcheon (CDP)
These door escutcheons provide a
frame and seal for the circuit breaker.
Transparent Cover (CCP) for Door Escutcheon
The cover is hinged-mounted and locked with a milled head, and
is designed to be installed on the door escutcheon.
Figure 15: Door Escutcheons
00399
0
6
1
3
3
7
9
8
Mechanical
Operation
Counter (CDM)
0
6
1
3
3
1
7
4
Shutter Lock
(NW)
UL/ANSI Circuit Breaker
Shutter (NW)
0
6
1
3
4
0
6
5
Escutcheon
Seal
0
6
1
3
3
8
1
8
Escutcheon
Seal
Door Escutcheon (NW Drawout) Door Escutcheon (NW Fixed)
0
6
1
3
3
8
1
9Transparent
Cover (CCP)
Masterpact

NT and NW Universal Power Circuit Breakers


Wiring Diagrams
61
11/2004 19992004 Schneider Electric All Rights Reserved
SECTION 4WIRING DIAGRAMS
WIRING DIAGRAMS FOR MASTERPACT NW CIRCUIT BREAKERS ...................................................... 62
WIRING DIAGRAMS FOR MASTERPACT NT CIRCUIT BREAKERS ........................................................ 64
ADDITIONAL WIRING INFORMATION FOR MASTERPACT NW/NT CIRCUIT BREAKERS .................... 66
62
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Wiring DiagramsWiring Diagrams for Masterpact NW Circuit Breakers
WIRING DIAGRAMS FOR MASTERPACT NW CIRCUIT BREAKERS
Figure 16: Wiring Diagrams for Masterpact NW Circuit Breakers
1
1
Do not remove factory-installed jumper Z3-Z4-Z5 if not ZSI connected. Remove factory-installed jumper T-T2 if neutral CT is connected. Do not install jumper between
T3 and T4.
Power Trip Unit
2
2
24 Vdc power suppy for trip unit must be separate and isolated from 24 Vdc power supply for communication modules.
Remote Operation
3
3
When remote operation features are used, make sure there is a minimum of four seconds for the spring charging motor (MCH) to completely charge the circuit breaker
closing springs prior to actuating the shunt close (XF) device.
Table 54: Markings for Ring Terminals
Table 55: Markings for Ring Terminals
Cell Switches Trip Unit Remote Operation
CD3 CD2 CD1 COM UC1 UC2 UC3 UC3a
M2C/M6
C
M2Ca/M6C
a
SDE2/RE
S
SDE2a SDE1 SDE1a
MN/MX
2
MX1 MX1a XF XFa
834/83
2
824/82
2
814/81
2
E5
E6
Z5
M1
M2
M3
F2+ VN 484/Q3 474/Q2 184/K2 182 84 82 D2/C12 C2 C3 A2 A3
831 821 811
E3
E4
Z3
Z4
T3
T4
F1- 471/Q1 181/K1 81 D1/C11 C1 A1
E1
E2
Z1
Z2
T1
T2
T
4
T
3
T
2
T
1
Z
3
Trip Unit
Z
4
Z
3
Z
2
Z
1
Z
4
,

Z
5
Z
2
Z
1
N C B A
Z
5
V
N
V
1
V
2
V
3
M
3
M
2
M
1
F
2
+
F
1

4
7
1
S1
4
8
4
S2
4
7
4
Q
1
Q
2
Q
3
M6C
M2C M6C
or
Upstream Downstream
0
6
1
3
3
7
9
6
I
V
T
4
T
3
T
2
T
1
24 Vdc
or
or
1
8
1
1
8
2
1
8
4
SDE2
F
a
u
l
t
F
a
u
l
t
8
1
8
2
8
4
SDE1
K
2
RES
K
1
PF
2
5
2
2
5
4
2
5
1
C
h
a
r
g
e
d
MX1
C
2
C
3
C
1
A
2
A
3
A
1
CH
XF
D
2
D
1
MN MX2
C
1
2
C
1
1
B
1
MCH
B
3
B
2
2
Cell Switches Trip Unit Cell Switches Remote Operation
CD3 CD2 CD1 COM UC1 UC2 UC3 UC4 M2C/M6C SDE2/RES SDE1 CE3 CE2 CE1 MN/MX2 MX1 XF PF MCH
834 824 814 E5 E6 Z5 M1 M2 M3 F2+ V3 484/Q3 184/K2 84 334 324 314 D2/C12 C2 A2 254 B2
832 822 812 E3 E4 Z3 Z4 T3 T4 VN V2 474/Q2 182 82 332 322 312 C13 C3 A3 252 B3
831 821 811 E1 E2 Z1 Z2 T1 T2 F1 V1 471/Q1 181/K1 81 331 321 311 D1/C11 C1 A1 251 B1
or
CE6 CE5 CE4
364 354 344
362 352 342
361 351 341
Masterpact

NT and NW Universal Power Circuit Breakers


Wiring DiagramsWiring Diagrams for Masterpact NW Circuit Breakers
63
11/2004 19992004 Schneider Electric All Rights Reserved
8
2
2
8
2
4
8
2
1
8
1
2
8
1
4
8
1
1
8
3
2
8
3
4
8
3
1
CD3
Disconnected
CD2 CD1
3
3
1
3
3
2
3
3
4
CE3
Connected
3
2
1
3
2
2
3
2
4
CE2
3
1
1
3
1
2
3
1
4
CE1
9
1
4
9
1
2
9
1
1
9
2
4
9
2
2
9
2
1
CT3
9
3
4
9
3
2
9
3
1
CT2 CT1
Test Position
0
6
1
3
3
7
9
5

OF . .
Closed
Connected
Closed
OF . .
(OF.. + CE)
EF
Not Connected
or Connected
and Open
or
.

.

1
.

.

2
.

.

4
.

.

6
.

.

8
.

.

5
1
2
1
4
1
1
2
2
2
4
3
2
3
4
3
1
2
1
OF4
4
2
4
4
4
1
OF3 OF2 OF1
Open Closed
0
6
1
3
3
7
9
4
CE
Auxiliary Contacts Cell Switches
Table 56: Markings for Push-in Type Terminals
Auxiliary Contacts Cell Switches

OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 OF4 OF3 OF2 OF1 CT3 CT2 CT1
244 234 224 214 144 134 124 114 44 34 24 14 934 924 914
242 232 222 212 142 132 122 112 42 32 22 12 932 922 912
241 231 221 211 141 131 121 111 41 31 21 11 931 921 911
or or or or
EF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11 CD6 CD5 CD4 CE9 CE8 C7
248 238 228 218 148 138 128 118 864 854 844 394 384 374
246 236 226 216 146 136 126 116 862 852 842 392 382 372
245 235 225 215 145 135 125 115 861 851 841 391 381 371

Note: Fixed-mounted circuit breaker does not have cell switches (CE, CD, CT).
Table 57: Markings for Ring Terminals
Alarm Switches Auxiliary Contacts Cell Switches

PF CT1 MCH MCHa OF14 OF13 OF12 OF11 OF4 OF3 OF2 OF1 CE3 CE2 CE1
252 914/912 B2 B3 144 134 122 112 44 34 22 12
334/33
2
324/32
2
314/31
2
251 911 B1 141 131 121 111 41 31 21 11 331 321 311

Note: Fixed-mounted circuit breaker does not have cell switches (CE, CD, CT).
64
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Wiring DiagramsWiring Diagrams for Masterpact NT Circuit Breakers
WIRING DIAGRAMS FOR MASTERPACT NT CIRCUIT BREAKERS
Figure 17: Markings for Push-in Type Terminals
1
1
Do not remove factory-installed jumper Z3-Z4-Z5 if not ZSI connected. Remove factory-installed jumper T1-T2 if neutral CT is connected. Do not install jumper
between T3 and T4.
Power Trip Unit
2
2
24 Vdc power suppy for trip unit must be separate and isolated from 24 Vdc power supply for communication modules.
Remote Operation
3
3
When remote operation features are used, make sure there is a minimum of four seconds for the spring charging motor (MCH) to completely charge the circuit
breaker closing springs prior to actuating the shunt close (XF) device.
Table 58: Markings for Push-in Type Terminals
Cell Switches Trip Unit
CD2 CD1 COM UC1 UC2 UC3 UC4 / M2C / M6C SDE2 / RES SDE1
824 814 E5 E6 Z5 M1 M2 M3 F2+ V3 / 484 / Q3 184 / K2 84
822 812 E3 E4 Z3 Z4 T3 T4 VN V2 / 474 / Q2 182 82
821 811 E1 E2 Z1 Z2 T1 T2 F1 V1 / 471 / Q1 181 / K1 81
Remote Operation
MN / MX2 MX1 XF PF MCH
D2 / C12 C2 A2 254 B2
C13 C3 A3 252 B3
D1/C11 C1 A1 251 B1
T
4
T
3
T
2
T
1
Micrologic
Z
4
Z
3
Z
2
Z
1
Z
2
Z
1
N L3 L2 L1
Q
Z
5
V
N
V
1
V
2
V
3
M
3
M
2
M
1
F
2
+
F
1
I
V
24 Vdc
T
4
T
3
T
2
T
1
Z
3
Z
4
Z
5
Z
2
Z
1
Z
3
Z
4
Z
5
Power Upstream
Circuit Breaker
0
6
1
3
4
0
6
1
4
7
1
S1
4
7
4
4
8
4
S2
Q
1
Q
2
Q
3
M6C
M2C M6C
or
Downstream
Circuit Breaker
2
or
or
1
8
1
1
8
2
1
8
4
SDE2
F
a
u
l
t
F
a
u
l
t
8
1
8
2
8
4
SDE1
K
2
RES
K
1
PF
2
5
2
2
5
4
2
5
1
C
h
a
r
g
e
d
MX1
C
2
C
3
C
1
A
2
A
3
A
1
CH
XF
D
2
D
1
MN MX2
C
1
2
C
1
1
B
1
MCH
B
3
B
2
0
6
1
3
4
0
6
2
NOTE: All diagrams show circuit
breaker open, connected and charged.
Masterpact

NT and NW Universal Power Circuit Breakers


Wiring DiagramsWiring Diagrams for Masterpact NT Circuit Breakers
65
11/2004 19992004 Schneider Electric All Rights Reserved
Table 59: Markings for Push-in Type Terminals
Auxiliary Switches Cell Switches
OF4 OF3 OF2 OF1 CE3 CE2 CE1 CT1
44 34 24 14 334 324 314 914
42 32 22 12 332 322 312 912
41 31 21 11 331 321 311 911
Figure 18: Spring-charging Motor
1
2
1
4
1
1
2
2
2
4
3
2
3
4
3
1
2
1
OF4
4
2
4
4
4
1
OF3 OF2 OF1
Open Closed
0
6
1
3
4
0
6
3
8
2
2
8
2
4
8
2
1
8
1
2
8
1
4
8
1
1
Disconnected
CD2 CD1
3
3
1
3
3
2
3
3
4
CE3
Connected
3
2
1
3
2
2
3
2
4
CE2
3
1
1
3
1
2
3
1
4
CE1
9
1
4
9
1
2
9
1
1
CT1
Test Position
0
6
1
3
4
0
6
4
Auxiliary Switches
Cell Switches
B1
CN1 - 440/480 V
CN2 - 440/480 V
9 11
CH
B3 B2
R
Spring
Charged
Light
440/480 V
MCH
380V
0
6
1
3
5
2
6
7
Spring-charging Motor 440/480 Vac
(380 Vac Motor + Additional Resistor)
66
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Wiring DiagramsAdditional Wiring Information for Masterpact NW/NT Circuit Breakers
ADDITIONAL WIRING INFORMATION FOR MASTERPACT NW/NT CIRCUIT BREAKERS
Alarm Contacts (OF1, OF2, OF3 and OF4 are standard equipment) Cradle Contacts
OF4
OF3
OF2
OF1
Open/Closed circuit
breaker or switch
position contacts
OF24: Open/Closed circuit breaker or switch position contact
or
EF24: Combined connected and closed contact
CD3
CD2
CD1
Disconnected
position contacts
CE3
CE2
CE1
Connected
position
contacts
CT3
CT2
CT1
Test position
contacts
OF23 or EF23 or or
OF22 or EF22 CE6
CE5
CE4
Connected
position contacts
CE9
CE8
CE7
Connected
position
contacts
OF21 or EF21
OF14 or EF14
OF13 or EF13 or
OF12 or EF12 CD6
CD5
CD4
Disconnected
position
contacts
OF22 or EF22
OF11 or EF11
Trip Unit Remote Operation
Basic A P H
SDE2 or RES
Electrical fault alarm contact
Remote reset Com: E1E6 communication

UC1:
Z1Z5 logical selectivity
Z1 = ZSI OUT
Z2 = ZSI OUT Source; Z3 = ZSI IN Source
Z4 = ZSI IN short-time delay
Z5 = ZSI IN ground fault
SDE1 Electrical fault alarm contact (standard)
MN or MX2
Undervoltage trip device
Additional shunt trip
MX1 Shunt trip (standard or networked)

UC3:
F2+, F1 24 Vdc external power supply
External neutral VN plug
XF Shunt close (standard or networked)
PF Ready-to-close contact
UC4 External phase voltage sensing MCH Spring-charging motor

M2C
or
M6C
Two programmable contacts (internal relay)
Six programmable contacts
(for connection to external M6C module)
NOTE: When communication version of the MX1 or XF coils are
used, terminals (C3, A3) must be connected to line even if the
communications module is not installed.
The bypass circuit through terminal C2/A2 is only momentary duty
for 0.5 sec. For continuous duty, use the communications
command.
Figure 19: Connection of the Communications Option

T
4
T
3
T
2
T
1
Z
3
Trip Unit
Z
4
Z
3
Z
2
Z
1
Z
4
,

Z
5
Z
2
Z
1
N C B A
Z
5
V
N
V
1
V
2
V
3
M
3
M
2
M
1
F
2
+
F
1

Upstream Downstream
XF
com
O
u
t

+
+
2
4

V
d
c
C
o
m
m
o
n
O
u
t

-
Cradle
Communication
Module (CCM)
I
n

+
I
n

-
E
6
E
5
E
4
E
3
Circuit Breaker
Communication
Module (BCM)
E
2
E
1
+24 Vdc
+24 Vdc
Common
Common
In +
Out +
Shield
Out -
In -
M
O
D
B
U
S
P
r
e
v
i
o
u
s

C
i
r
c
u
i
t

B
r
e
a
k
e
r
N
e
x
t

C
i
r
c
u
i
t

B
r
e
a
k
e
r
MX1
com
T
4
T
3
T
2
T
1
24 V
OF
SDE
PF
CH
Micro switches
connected to BCM
4
7
1
S1
4
8
4
S2
4
7
4
Q
1
Q
2
Q
3
M6C
M2C M6C
or
0
6
1
3
4
8
9
8
811
CD1
812
311
CE1
314
CE CD CT
911
CT1
914
*
*
*
* Must be two separate isolated 24 Vdc sources.
Note: Fixed-monted circuit breaker does not have
cell switches (CE, CD, CT).
NOTE: A recommended wiring schematic for the
communicating style shunt trip or shunt close coils is
shown below.
Induced voltages in the circuit at terminal C2 and/or
A2 can cause the shunt trip or shunt close to not work
properly. The best way to prevent the induced
voltages is keep the circuit to terminal C2 and A2 as
short as possible. If it is impossible to keep the circuit
less than 10 feet (3 m), use an interposing relay near
terminal C2 or A2.
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional Drawings
67
11/2004 19992004 Schneider Electric All Rights Reserved
SECTION 5MASTERPACT NT DIMENSIONAL DRAWINGS
MASTERPACT NT ENCLOSURE INFORMATION ..................................................................................... 68
UL LISTED AND ANSI CERTIFIED 3-POLE DRAWOUT CIRCUIT BREAKERS ........................................ 68
8001200 A Masterpact NT 3-pole DrawoutMaster Drawing ............................................................. 69
8001200 A Masterpact NT UL/ANSI 3-pole DrawoutRCTH Rear Connected T Horizontal ........... 69
8001200 A Masterpact NT UL/ANSI 3-pole DrawoutRCTV Rear Connected T Vertical ................ 70
8001200 A Masterpact NT UL/ANSI 3-pole DrawoutFCF Front Connected Flat .............................. 70
8001200 A Masterpact NT UL/ANSI 3-pole DrawoutDoor Cutout Dimensions ................................ 70
8001200 A Masterpact NT UL/ANSI 3-pole DrawoutPan Dimensions ............................................. 71
UL LISTED AND ANSI CERTIFIED 3-POLE FIXED CIRCUIT BREAKERS ................................................ 72
8001200 A and 1600 A Masterpact NT UL/ANSI 3-pole FixedMaster Drawing ............................... 72
8001200 A Masterpact NT UL/ANSI 3-pole FixedRCTH Rear Connected T Horizontal ................ 72
8001200 A Masterpact NT UL/ANSI 3-pole FixedRCTV Rear Connected T Vertical .................... 73
8001200 A Masterpact NT UL/ANSI 3-pole FixedFCF Front Connected Flat .................................. 73
1600 A Masterpact NT UL/ANSI 3-pole FixedRCV Rear Connected Fixed Vertical ........................... 74
8001200 A Masterpact NT UL/ANSI 3-pole FixedDoor Cutout Dimensions ..................................... 74
8001200 A Masterpact NT UL/ANSI 3-pole FixedPan Dimensions .................................................. 75
UL LISTED AND ANSI CERTIFIED 4-POLE DRAWOUT CIRCUIT BREAKERS......................................... 76
8001200 A Masterpact NT UL/ANSI 4-pole DrawoutMaster Drawing .............................................. 76
8001200 A Masterpact NT UL/ANSI 4-pole DrawoutRCTH Rear Connected T Horizontal ........... 76
8001200 A Masterpact NT UL/ANSI 4-pole DrawoutRCTV Rear Connected T Vertical ................ 77
8001200 A Masterpact NT UL/ANSI 4-pole DrawoutFCF Front Connected Flat .............................. 77
8001200 A Masterpact NT UL/ANSI 4-pole DrawoutDoor Cutout Dimensions ................................ 78
8001200 A Masterpact NT UL/ANSI 4-pole DrawoutPan Dimensions ............................................. 78
UL LISTED AND ANSI CERTIFIED 4-POLE FIXED CIRCUIT BREAKERS ................................................ 79
8001200 A Masterpact NT UL/ANSI 4-pole FixedMaster Drawing ................................................... 79
8001200 A Masterpact NT UL/ANSI 4-pole FixedRCTH Rear Connected T Horizontal ................ 79
8001200 A Masterpact NT UL/ANSI 4-pole FixedRCTV Rear Connected T Vertical .................... 80
8001200 A Masterpact NT UL/ANSI 4-pole FixedFCF Front Connected Flat .................................. 80
8001200 A Masterpact NT UL/ANSI 4-pole FixedDoor Cutout Dimensions ..................................... 81
8001200 A Masterpact NT UL/ANSI 4-pole FixedPan Dimensions .................................................. 81
IEC RATED 3-POLE DRAWOUT CIRCUIT BREAKERS.............................................................................. 82
8001600 A Masterpact NT 3-pole DrawoutMaster Drawing ............................................................. 82
8001600 A Masterpact NT IEC 3-pole DrawoutRCTV Rear Connected T Vertical ........................ 82
8001600 A Masterpact NT IEC 3-pole DrawoutRCTH Rear Connected T Horizontal ................... 83
8001600 A Masterpact NT IEC 3-pole DrawoutFCF Front Connected Flat ...................................... 83
8001200 A Masterpact NT IEC 3-pole DrawoutRear Cutout Dimensions ........................................ 84
IEC RATED 3-POLE FIXED CIRCUIT BREAKERS ..................................................................................... 85
8001600 A Masterpact NT 3-pole FixedMaster Drawing .................................................................. 85
8001600 A Masterpact NT IEC 3-pole FixedRCTV Rear Connected T Vertical ............................ 85
8001600 A Masterpact NT IEC 3-pole FixedRCTH Rear Connected T Horizontal ........................ 86
8001600 A Masterpact NT IEC 3-pole FixedFCF Front Connected Flat .......................................... 86
8001200 A Masterpact NT IEC 3-pole FixedRear Cutout Dimensions ............................................. 87
IEC RATED 4-POLE DRAWOUT CIRCUIT BREAKERS ............................................................................. 88
8001600 A Masterpact NT 4-pole DrawoutMaster Drawing ............................................................. 88
8001600 A Masterpact NT IEC 4-pole DrawoutRCTV Rear Connected T Vertical ........................ 88
8001600 A Masterpact NT IEC 4-pole DrawoutRCTH Rear Connected T Horizontal ................... 89
8001600 A Masterpact NT IEC 4-pole DrawoutFCF Front Connected Flat ...................................... 89
8001200 A Masterpact NT IEC 4-pole DrawoutRear Cutout Dimensions ........................................ 90
IEC RATED 4-POLE FIXED CIRCUIT BREAKERS ..................................................................................... 91
8001600 A Masterpact NT 4-pole FixedMaster Drawing .................................................................. 91
8001600 A Masterpact NT IEC 4-pole FixedRCTV Rear Connected T Vertical ............................ 91
8001600 A Masterpact NT IEC 4-pole FixedRCTH Rear Connected T Horizontal ........................ 92
8001600 A Masterpact NT IEC 4-pole FixedFCF Front Connected Flat .......................................... 92
8001200 A Masterpact NT IEC 4-pole FixedRear Cutout Dimensions ............................................. 93
NEUTRAL CURRENT TRANSFORMERS FOR MASTERPACT NT CIRCUIT BREAKERS ....................... 93
8001200 A External Neutral Current Transformer ................................................................................ 93
8001200 A External Neutral Current Transformer (Switchboards and Switchgear .............................. 94
8001200 A External Neutral Current Transformer (Panelboards) ........................................................ 94
68
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsMasterpact NT Enclosure Information
MASTERPACT NT ENCLOSURE INFORMATION
UL/ANSI 3-POLE DRAWOUT CIRCUIT BREAKERS
Table 60: Minimum Enclosure Information
Number of
Poles
Circuit Breaker Rating
Circuit Breaker Enclosure Dimensions Ventilation Area
(H x W x D) Top Bottom
in. mm in.
2
mm
2
in.
2
mm
2
3-pole
800 to 1600 A (N, H, L1) 18.25 x 13 x 9.5 463.5 x 330.2 x 241.3 9 5806 9 5806
800 to 1600 A (L) 62.25 x 23 x 14.75 1581.2 x 584.2 x 374.7 16.5 10645 16.5 10645
4-pole
800 to 1600 A (N, H, L1) 18.25 x 15.8 x 9.5 463.5 x 401.3 x 241.3 9 5806 9 5806
800 to 1600 A (L) 62.25 x 25.76 x 14.75 1581.2 x 654.2 x 374.7 16.5 10645 16.5 10645
Figure 20: 8001200 A Masterpact NT 3-pole DrawoutMaster Drawing
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
69
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 21: 8001200 A Masterpact NT UL/ANSI 3-pole DrawoutRCTH Rear Connected T Horizontal
Figure 22: 8001200 A Masterpact NT UL/ANSI 3-pole DrawoutRCTV Rear Connected T Vertical
70
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
Figure 23: 8001200 A Masterpact NT UL/ANSI 3-pole DrawoutFCF Front Connected Flat
Figure 24: 8001200 A Masterpact NT UL/ANSI 3-pole DrawoutDoor Cutout Dimensions
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
71
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 25: 8001200 A Masterpact NT UL/ANSI DrawoutPan Dimensions
72
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 3-pole Fixed Circuit Breakers
UL/ANSI 3-POLE FIXED CIRCUIT BREAKERS
Figure 26: 8001200 A and 1600 A Masterpact NT UL/ANSI 3-pole FixedMaster Drawing
Figure 27: 8001200 A Masterpact NT UL/ANSI 3-pole FixedRCTH Rear Connected T Horizontal
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 3-pole Fixed Circuit Breakers
73
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 28: 8001200 A Masterpact NT UL/ANSI 3-pole FixedRCTV Rear Connected T Vertical
Figure 29: 8001200 A Masterpact NT UL/ANSI 3-pole FixedFCF Front Connected Flat
74
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 3-pole Fixed Circuit Breakers
Figure 30: 1600 A Masterpact NT UL/ANSI 3-pole FixedRCV Rear Connected Vertical
Figure 31: 8001200 A Masterpact NT UL/ANSI 3-pole FixedDoor Cutout Dimensions
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 3-pole Fixed Circuit Breakers
75
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 32: 8001200 A Masterpact NT UL/ANSI FixedPan Dimensions
76
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 4-pole Drawout Circuit Breakers
UL/ANSI 4-POLE DRAWOUT CIRCUIT BREAKERS
Figure 33: 8001200 A and 1600 A Masterpact NT UL/ANSI 4-pole DrawoutMaster Drawing
Figure 34: 8001200 A Masterpact NT UL/ANSI 4-pole DrawoutRCTH Rear Connected T Horizontal
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 4-pole Drawout Circuit Breakers
77
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 35: 8001200 A Masterpact NT UL/ANSI 4-pole DrawoutRCTV Rear Connected T Vertical
Figure 36: 8001200 A Masterpact NT UL/ANSI 4-pole DrawoutFCF Front Connected Flat
78
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 4-pole Drawout Circuit Breakers
Figure 37: 8001200 A Masterpact NT UL/ANSI 4-pole DrawoutDoor Cutout Dimensions
Figure 38: 8001200 A Masterpact NT UL/ANSI DrawoutPan Dimensions
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 4-pole Fixed Circuit Breakers
79
11/2004 19992004 Schneider Electric All Rights Reserved
UL/ANSI 4-POLE FIXED CIRCUIT BREAKERS
Figure 39: 8001200 A Masterpact NT UL/ANSI 4-pole FixedMaster Drawing
Figure 40: 8001200 A Masterpact NT UL/ANSI 4-pole FixedRCTH Rear Connected T Horizontal
80
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 4-pole Fixed Circuit Breakers
Figure 41: 8001200 A Masterpact NT UL/ANSI 4-pole FixedRCTV Rear Connected T Vertical
Figure 42: 8001200 A Masterpact NT UL/ANSI 4-pole FixedFCF Front Connected Flat
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsUL/ANSI 4-pole Fixed Circuit Breakers
81
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 43: 8001200 A Masterpact NT UL/ANSI 4-pole FixedDoor Cutout Dimensions
Figure 44: 8001200 A Masterpact NT UL/ANSI FixedPan Dimensions
82
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsIEC 3-pole Drawout Circuit Breakers
IEC 3-POLE DRAWOUT CIRCUIT BREAKERS
Figure 45: 8001600 A Masterpact NT 3-pole DrawoutMaster Drawing
Figure 46: 8001600 A Masterpact NT IEC 3-pole DrawoutRCTV Rear Connected T Vertical
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsIEC 3-pole Drawout Circuit Breakers
83
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 47: 8001600 A Masterpact NT IEC 3-pole DrawoutRCTH Rear Connected T Horizontal
Figure 48: 8001600 A Masterpact NT IEC 3-pole DrawoutFCF Front Connected Flat
84
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsIEC 3-pole Drawout Circuit Breakers
Figure 49: 8001200 A Masterpact NT IEC 3-pole DrawoutRear Cutout Dimensions
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsIEC 3-pole Fixed Circuit Breakers
85
11/2004 19992004 Schneider Electric All Rights Reserved
IEC 3-POLE FIXED CIRCUIT BREAKERS
Figure 50: 8001600 A Masterpact NT 3-pole FixedMaster Drawing
Figure 51: 8001600 A Masterpact NT IEC 3-pole FixedRCTV Rear Connected T Vertical
86
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsIEC 3-pole Fixed Circuit Breakers
Figure 52: 8001600 A Masterpact NT IEC 3-pole FixedRCTH Rear Connected T Horizontal
Figure 53: 8001600 A Masterpact NT IEC 3-pole FixedFCF Front Connected Flat
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsIEC 3-pole Fixed Circuit Breakers
87
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 54: 8001200 A Masterpact NT IEC 3-pole FixedRear Cutout Dimensions
88
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsIEC 4-pole Drawout Circuit Breakers
IEC 4-POLE DRAWOUT CIRCUIT BREAKERS
Figure 55: 8001600 A Masterpact NT 4-pole DrawoutMaster Drawing
Figure 56: 8001600 A Masterpact NT IEC 4-pole DrawoutRCTV Rear Connected T Vertical
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsIEC 4-pole Drawout Circuit Breakers
89
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 57: 8001600 A Masterpact NT IEC 4-pole DrawoutRCTH Rear Connected T Horizontal
Figure 58: 8001600 A Masterpact NT IEC 4-pole DrawoutFCF Front Connected Flat
90
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsIEC 4-pole Drawout Circuit Breakers
Figure 59: 8001200 A Masterpact NT IEC 4-pole DrawoutRear Cutout Dimensions
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsIEC 4-pole Fixed Circuit Breakers
91
11/2004 19992004 Schneider Electric All Rights Reserved
IEC 4-POLE FIXED CIRCUIT BREAKERS
Figure 60: 8001600 A Masterpact NT 4-pole FixedMaster Drawing
Figure 61: 8001600 A Masterpact NT IEC 4-pole FixedRCTV Rear Connected T Vertical
92
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsIEC 4-pole Fixed Circuit Breakers
Figure 62: 8001600 A Masterpact NT IEC 4-pole FixedRCTH Rear Connected T Horizontal
Figure 63: 8001600 A Masterpact NT IEC 4-pole FixedFCF Front Connected Flat
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsNeutral Current Transformers
93
11/2004 19992004 Schneider Electric All Rights Reserved
NEUTRAL CURRENT TRANSFORMERS
Figure 64: 8001200 A Masterpact NT IEC 4-pole FixedRear Cutout Dimensions
Figure 65: 8001600 A External Neutral Current Transformer
94
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NT Dimensional DrawingsNeutral Current Transformers
Figure 66: 8001600 A External Neutral Current Transformer (Switchboards and Switchgear)
Figure 67: 8001600 A External Neutral Current Transformer (Panelboards)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional Drawings
95
11/2004 19992004 Schneider Electric All Rights Reserved
SECTION 6MASTERPACT NW DIMENSIONAL DRAWINGS
MASTERPACT NW ENCLOSURE INFORMATION .................................................................................... 97
MASTERPACT NW UL/ANSI 3-POLE DRAWOUT CIRCUIT BREAKERS ................................................. 97
800-3000 A and 3200 A (H1, H2, H3) Master Drawing .......................................................................... 97
800-2000 A Rear Connected "T" Vertical (RCTV) .................................................................................. 98
800-2000 A Rear Connected "T" Horizontal (RCTH) ............................................................................. 98
800-2000 A Front Connected Flat (FCF) ................................................................................................ 99
800-3000 A Front Connected "T" (FCT) ................................................................................................. 99
2500-3000 A Rear Connected "T" Horizontal (RCTH) ......................................................................... 100
2000 A L1 & 3200 A Rear Connected Offset Vertical (RCOV) ............................................................. 100
2500-3000 A Rear Connected "T" Vertical (RCTV) .............................................................................. 101
3200 A L1 and 4000-6000 A Master Drawing ...................................................................................... 101
3200 A L1 and 4000-5000 A Rear Connected "T" Vertical (RCTV) ..................................................... 102
3200 A L1 and 4000-5000 A Rear Connected "T" Horizontal (RCTH) ................................................. 102
3200 A L1 and 4000 A Front Connected Flat (FCF) ............................................................................ 103
3200 A L1 and 4000-5000 A Front Connected "T" (FCT) .................................................................... 103
6000 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 104
MASTERPACT NW DRAWOUT CRADLE MOUNTING ............................................................................ 104
800-3000 A and 3200 A (H1, H2, H3) Door Cutout .............................................................................. 105
3200 A L1 and 4000 - 6000 A Door Cutout .......................................................................................... 105
DOOR ESCUTCHEON HOLE PATTERN .................................................................................................. 106
MASTERPACT NW UL/ANSI 3-POLE FIXED CIRCUIT BREAKERS ....................................................... 107
800-3000 A and 3200 A Master Drawing ............................................................................................. 107
800-2000 A Rear Connected "T" Vertical (RCTV) ................................................................................ 107
800-2000 A Rear Connected "T" Horizontal (RCTH) ........................................................................... 108
800-2000 A Front Connected Flat (FCF) .............................................................................................. 108
800-3000 A Front Connected "T" (FCT) ............................................................................................... 109
500-3000 A rear Vertical "T" Horizontal (RCTV) .................................................................................. 109
2500-3000 A Rear Connected "T" Horizontal (RCTH) ......................................................................... 110
2000 L1 and 3200 A Rear Connected Offset Vertical (RCOV) ............................................................ 110
4000 A (W-frame) Rear Connected Offset Vertical (RCOV) ................................................................. 111
4000-6000 A Master Drawing ............................................................................................................... 111
4000-5000 A Rear Connected "T" Vertical (RCTV) .............................................................................. 112
4000-5000 A Rear Connected "T" Horizontal (RCTH) ......................................................................... 112
6000 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 113
800-3200 A Door Cutout ...................................................................................................................... 113
4000-6000 A Door Cutout .................................................................................................................... 114
MASTERPACT NW UL AND ANSI 4-POLE DRAWOUT CIRCUIT BREAKERS ....................................... 114
800-3000 A and 3200 A Master Drawing ............................................................................................. 114
800-2000 A Rear Connected "T" Vertical (RCTV) ................................................................................ 115
800-2000 A Rear Connected "T" Horizontal (RCTH) ........................................................................... 115
800-2000 A Front Connected Flat (FCF) .............................................................................................. 116
800-3000 A Front Connected "T" (FCT) ............................................................................................... 116
2500-3000 A Rear Connected "T" Vertical (RCTV) .............................................................................. 117
2500-3000 A Rear Connected "T" Horizontal (RCTH) ......................................................................... 117
2000 A L1 and 3200 A Rear Connected Offset Vertical (RCOV) ......................................................... 118
3200 A L1 and 4000-6000 A Master Drawing ...................................................................................... 119
3200 A L1 and 4000-5000 A Rear Connected "T" Vertical (RCTV) ..................................................... 119
3200 A L1 and 4000-5000 A Rear Connected "T" Horizontal (RCTH) ................................................. 120
3200 A L1 and 4000 A Front Connected Flat (FCF) ............................................................................ 120
3200 A L1 and 4000-5000 A Front Connected "T" (FCT) .................................................................... 121
6000 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 121
96
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional Drawings
MASTERPACT NW UL AND ANSI 4-POLE FIXED CIRCUIT BREAKERS ............................................... 122
800-3000 A and 3200 A Master Drawing .............................................................................................. 122
800-2000 A Rear Connected "T" Vertical (RCTV) ................................................................................ 122
800-2000 A Rear Connected "T" Horizontal (RCTH) ............................................................................ 123
800-2000 A Front Connected Flat (FCF) .............................................................................................. 123
800-3000 A Front Connected "T" (FCT) ............................................................................................... 124
2000 A L1 and 3200 A Rear Connected Offset Vertical (RCOV) ......................................................... 124
2500-3000 A Rear Vertical "T" Horizontal (RCTV) ............................................................................... 125
2500-3000 A Rear Connected "T" Horizontal (RCTH) .......................................................................... 125
4000-6000 A Master Drawing ............................................................................................................... 126
4000-5000 A Rear Connected "T" Vertical (RCTV) .............................................................................. 126
4000-5000 A Rear Connected "T" Horizontal (RCTH) .......................................................................... 127
6000 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 127
Pan Drawings for 3- and 4-pole Circuit Breakers .................................................................................. 128
MASTERPACT NW NEUTRAL CURRENT TRANSFORMERS ................................................................. 129
Neutral Current Transformer 100-250 A, 400-2000 A .......................................................................... 129
Neutral Current Transformer 2000-4000 A ........................................................................................... 129
Double Neutral Current Transformer 2000-6300 A ............................................................................... 129
MDGF/SGR Current Transformer ......................................................................................................... 130
MASTERPACT NW IEC 3-POLE DRAWOUT CIRCUIT BREAKERS ........................................................ 131
800-3200 A Rear Connected "T" Vertical (RCTV) ................................................................................ 131
800-3200 A Rear Connected "T" Horizontal (RCTH) ............................................................................ 132
800-3200 A Front Connected Flat (FCF) .............................................................................................. 132
4000 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 133
4000 A Rear Connected "T" Horizontal (RCTH) ................................................................................... 133
5000 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 134
5000 A Rear Connected "T" Horizontal (RCTH) ................................................................................... 134
6300 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 135
MASTERPACT NW IEC 3-POLE FIXED CIRCUIT BREAKERS ................................................................ 136
800-3200 A Rear Connected "T" Vertical (RCTV) ................................................................................ 136
800-3200 A Rear Connected "T" Horizontal (RCTH) ............................................................................ 136
800-3200 A Front Connected Flat (FCF) .............................................................................................. 137
4000 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 137
4000 A Rear Connected "T" Horizontal (RCTH) ................................................................................... 138
5000 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 138
5000 A Rear Connected "T" Horizontal (RCTH) ................................................................................... 139
6300 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 139
MASTERPACT NW IEC 4-POLE DRAWOUT CIRCUIT BREAKERS ........................................................ 140
800-3200 A Rear Connected "T" Vertical (RCTV) ................................................................................ 140
800-3200 A Rear Connected "T" Horizontal (RCTH) ............................................................................ 140
800-3200 A Front Connected Flat (FCF) .............................................................................................. 141
4000 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 141
4000 A Rear Connected "T" Horizontal (RCTH) ................................................................................... 142
5000 A Rear Connected T Vertical (RCTV) ....................................................................................... 142
5000 A Rear Connected T Horizontal (RCTH) ................................................................................... 143
6300 A Rear Connected T Vertical (RCTV) ....................................................................................... 143
MASTERPACT NW IEC 4-POLE FIXED CIRCUIT BREAKERS ................................................................ 144
800-3200 A Rear Connected "T" Vertical (RCTV) ................................................................................ 144
800-3200 A Rear Connected "T" Horizontal (RCTH) ............................................................................ 145
800-3200 A Front Connected Flat (FCF) .............................................................................................. 145
4000 A Rear Connected "T" Vertical (RCTV) ....................................................................................... 146
4000 A Rear Connected "T" Horizontal (RCTH) ................................................................................... 146
5000 A Rear Connected T Vertical (RCTV) ....................................................................................... 147
5000 A Rear Connected T Horizontal (RCTH) ................................................................................... 147
6300 Rear Connected T Vertical (RCTV) ........................................................................................... 148
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsEnclosure Information
97
11/2004 19992004 Schneider Electric All Rights Reserved
ENCLOSURE INFORMATION
UL/ANSI 3-POLE DRAWOUT CIRCUIT BREAKERS
Table 61: Minimum Enclosure Information
Number
of Poles
Circuit Breaker Rating
Circuit Breaker Enclosure Dimensions Ventilation Area
(H x W x D) Top Bottom Front Face
in. mm in.
2
mm
2
in.
2
mm
2
in.
2
mm
2
3-pole
2000 A and below, UL 1066 (ANSI C37.50) 21.25 x 21.75 x 15.75 539.8 x 552.5 x 400 59.62 38 460 35.62 22 980
3000 A and below, UL 489 18.37 x 24.00 x 15.75 466.6 x 609.6 x 400 16.62 10 720 16.62 10 720
3200 A, and 4000 A (W-frame)
UL 1066 (ANSI C37.50)
31.00 x 21.75 x 15.75 787.4 x 552.5 x 400 59.62 38 460 93.6 60 390
40005000 A, UL 1066 (ANSI C37.50) 33.00 x 32.62 x 15.75 838.2 x 828.5 x 400 198.75 128 230 130.5 84 190
40006000 A, UL 489 21.75 x 36.00 x 15.75 552.5 x 914.4 x 400 16.62 10 720 16.62 10 720
4-pole
2000 A and below, UL 1066 (ANSI C37.50) 21.25 x 26.28 x 15.75 539.8 x 667.5 x 400 59.62 38 460 35.62 22 980
3000 A and below, UL 489 18.37 x 30.00 x 15.75 466.6 x 762.0 x 400 16.62 10 720 16.62 10 720
3200 A, and 4000 A (W-frame)
UL 1066 (ANSI C37.50)
31.00 x 26.28 x 15.75 787.4 x 667.5 x 400 59.62 38 460 93.6 60 390
40005000 A, UL 1066 (ANSI C37.50) 33.00 x 41.68 x 15.75 838.2 x 1058.7 x 400 198.75 128 230 130.5 84 190
40006000 A, UL 489 21.75 x 45.00 x 15.75 552.5 x 1168.4 x 400 16.62 10 720 16.62 10 720
Figure 68: 800-3000 A and 3200 A (H1, H2, H3) Master Drawing
98
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
Figure 69: 800-2000 A Rear Connected "T" Vertical (RCTV)
Figure 70: 800-2000 A Rear Connected "T" Horizontal (RCTH)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
99
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 71: 800-2000 A Front Connected Flat (FCF)
Figure 72: 800-3000 A Front Connected "T" (FCT)
100
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
Figure 73: 2500-3000 A Rear Connected "T" Horizontal (RCTH)
Figure 74: 2000 A L1 and 3200 A Rear Connected Offset Vertical (RCOV)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
101
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 75: 2500-3000 A Rear Connected "T" Vertical (RCTV)
Figure 76: 3200 A L1 and 4000-6000 A Master Drawing
102
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
Figure 77: 3200 A L1 and 4000-5000 A Rear Connected "T" Vertical (RCTV)
Figure 78: 3200 A L1 and 4000-5000 A Rear Connected "T" Horizontal (RCTH)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
103
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 79: 3200 A L1 and 4000 A Front Connected Flat (FCF)
Figure 80: 3200 A L1 and 4000-5000 A Front Connected "T" (FCT)
104
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
Figure 81: 6000 A Rear Connected "T" Vertical (RCTV)
Figure 82: Drawout Cradle Mounting
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
105
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 83: 800-3000 A and 3200 A (H1, H2, H3) Door Cutout
Figure 84: 3200 A L1 and 4000 - 6000 A Door Cutout
106
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Drawout Circuit Breakers
Figure 85: Door Escutcheon Hole Pattern
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Fixed Circuit Breakers
107
11/2004 19992004 Schneider Electric All Rights Reserved
UL/ANSI 3-POLE FIXED CIRCUIT BREAKERS
Figure 86: 800-3000 A, 3200 A and 4000 A (W-frame) Master Drawing
Figure 87: 800-2000 A Rear Connected "T" Vertical (RCTV)
108
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Fixed Circuit Breakers
Figure 88: 800-2000 A Rear Connected "T" Horizontal (RCTH)
Figure 89: 800-2000 A Front Connected Flat (FCF)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Fixed Circuit Breakers
109
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 90: 800-3000 A Front Connected "T" (FCT)
Figure 91: 2500-3000 A rear Vertical "T" Horizontal (RCTV)
110
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Fixed Circuit Breakers
Figure 92: 2500-3000 A Rear Connected "T" Horizontal (RCTH)
Figure 93: 2000 A L1 and 3200 A Rear Connected Offset Vertical (RCOV)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Fixed Circuit Breakers
111
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 94: 4000 A (W-frame) Rear-connected Offset Vertical (RCOV)
Figure 95: 4000-6000 A Master Drawing
112
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Fixed Circuit Breakers
Figure 96: 4000-5000 A Rear Connected "T" Vertical (RCTV)
Figure 97: 4000-5000 A Rear Connected "T" Horizontal (RCTH)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 3-pole Fixed Circuit Breakers
113
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 98: 6000 A Rear Connected "T" Vertical (RCTV)
Figure 99: 800-3200 A and 4000 A (W-frame) Circuit Breaker Door Cutout
114
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Drawout Circuit Breakers
UL/ANSI 4-POLE DRAWOUT CIRCUIT BREAKERS
Figure 100: 4000-6000 A Door Cutout
Figure 101: 800-3000 A and 3200 A Master Drawing
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Drawout Circuit Breakers
115
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 102: 800-2000 A Rear Connected "T" Vertical (RCTV)
Figure 103: 800-2000 A Rear Connected "T" Horizontal (RCTH)
116
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Drawout Circuit Breakers
Figure 104: 800-2000 A Front Connected Flat (FCF)
Figure 105: 800-3000 A Front Connected "T" (FCT)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Drawout Circuit Breakers
117
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 106: 2500-3000 A Rear Connected "T" Vertical (RCTV)
Figure 107: 2500-3000 A Rear Connected "T" Horizontal (RCTH)
118
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Drawout Circuit Breakers
Figure 108: 2000 A L1 and 3200 A Rear Connected Offset Vertical (RCOV)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Drawout Circuit Breakers
119
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 109: 3200 A L1 and 4000-6000 A Master Drawing
Figure 110: 3200 A L1 and 4000-5000 A Rear Connected "T" Vertical (RCTV)
120
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Drawout Circuit Breakers
Figure 111: 3200 A L1 and 4000-5000 A Rear Connected "T" Horizontal (RCTH)
Figure 112: 3200 A L1 and 4000 A Front Connected Flat (FCF)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Drawout Circuit Breakers
121
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 113: 3200 A L1 and 4000-5000 A Front Connected "T" (FCT)
Figure 114: 6000 A Rear Connected "T" Vertical (RCTV)
122
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Fixed Circuit Breakers
UL/ANSI 4-POLE FIXED CIRCUIT BREAKERS
Figure 115: 800-3000 A, 3200 A and 4000 A (W-frame) Master Drawing
Figure 116: 800-2000 A Rear Connected "T" Vertical (RCTV)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Fixed Circuit Breakers
123
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 117: 800-2000 A Rear Connected "T" Horizontal (RCTH)
Figure 118: 800-2000 A Front Connected Flat (FCF)
124
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Fixed Circuit Breakers
Figure 119: 800-3000 A Front Connected "T" (FCT)
Figure 120: 2000 A L1 and 3200 A Rear Connected Offset Vertical (RCOV)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Fixed Circuit Breakers
125
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 121: 2500-3000 A Rear Vertical "T" Horizontal (RCTV)
Figure 122: 2500-3000 A Rear Connected "T" Horizontal (RCTH)
126
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Fixed Circuit Breakers
Figure 123: 4000-6000 A Master Drawing
Figure 124: 4000-5000 A Rear Connected "T" Vertical (RCTV)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Fixed Circuit Breakers
127
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 125: 4000-5000 A Rear Connected "T" Horizontal (RCTH)
Figure 126: 6000 A Rear Connected "T" Vertical (RCTV)
128
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsUL/ANSI 4-pole Fixed Circuit Breakers
Figure 127: Pan Drawings for 3- and 4-pole Circuit Breakers
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsNeutral Current Transformers
129
11/2004 19992004 Schneider Electric All Rights Reserved
NEUTRAL CURRENT TRANSFORMERS
Figure 128: Neutral Current Transformer 100-250 A, 400-2000 A
Figure 129: Neutral Current Transformer 2000-4000 A
Figure 130: Double Neutral Current Transformer 2000-6300 A
130
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsNeutral Current Transformers
Figure 131: MDGF/SGR Current Transformer
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 3-pole Drawout Circuit Breakers*
131
11/2004 19992004 Schneider Electric All Rights Reserved
IEC 3-POLE DRAWOUT CIRCUIT BREAKERS*
Figure 132: 800-3200 A Rear Connected "T" Vertical (RCTV)
132
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 3-pole Drawout Circuit Breakers*
Figure 133: 800-3200 A Rear Connected "T" Horizontal (RCTH)
Figure 134: 800-3200 A Front Connected Flat (FCF)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 3-pole Drawout Circuit Breakers*
133
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 135: 4000 A Rear Connected "T" Vertical (RCTV)
Figure 136: 4000 A Rear Connected "T" Horizontal (RCTH)
134
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 3-pole Drawout Circuit Breakers*
Figure 137: 5000 A Rear Connected "T" Vertical (RCTV)
Figure 138: 5000 A Rear Connected "T" Horizontal (RCTH)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 3-pole Drawout Circuit Breakers*
135
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 139: 6300 A Rear Connected "T" Vertical (RCTV)
136
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 3-pole Fixed Circuit Breakers
IEC 3-POLE FIXED CIRCUIT BREAKERS
Figure 140: 800-3200 A Rear Connected "T" Vertical (RCTV)
Figure 141: 800-3200 A Rear Connected "T" Horizontal (RCTH)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 3-pole Fixed Circuit Breakers
137
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 142: 800-3200 A Front Connected Flat (FCF)
Figure 143: 4000 A Rear Connected "T" Vertical (RCTV)
138
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 3-pole Fixed Circuit Breakers
Figure 144: 4000 A Rear Connected "T" Horizontal (RCTH)
Figure 145: 5000 A Rear Connected "T" Vertical (RCTV)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 3-pole Fixed Circuit Breakers
139
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 146: 5000 A Rear Connected "T" Horizontal (RCTH)
Figure 147: 6300 A Rear Connected "T" Vertical (RCTV)
140
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 4-pole Drawout Circuit Breakers
IEC 4-POLE DRAWOUT CIRCUIT BREAKERS
Figure 148: 800-3200 A Rear Connected "T" Vertical (RCTV)
Figure 149: 800-3200 A Rear Connected "T" Horizontal (RCTH)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 4-pole Drawout Circuit Breakers
141
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 150: 800-3200 A Front Connected Flat (FCF)
Figure 151: 4000 A Rear Connected "T" Vertical (RCTV)
142
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 4-pole Drawout Circuit Breakers
Figure 152: 4000 A Rear Connected "T" Horizontal (RCTH)
Figure 153: 5000 A Rear Connected T Vertical (RCTV)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 4-pole Drawout Circuit Breakers
143
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 154: 5000 A Rear Connected T Horizontal (RCTH)
Figure 155: 6300 A Rear Connected T Vertical (RCTV)
144
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 4-pole Fixed Circuit Breakers
IEC 4-POLE FIXED CIRCUIT BREAKERS
Figure 156: 800-3200 A Rear Connected "T" Vertical (RCTV)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 4-pole Fixed Circuit Breakers
145
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 157: 800-3200 A Rear Connected "T" Horizontal (RCTH)
Figure 158: 800-3200 A Front Connected Flat (FCF)
146
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 4-pole Fixed Circuit Breakers
Figure 159: 4000 A Rear Connected "T" Vertical (RCTV)
Figure 160: 4000 A Rear Connected "T" Horizontal (RCTH)
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 4-pole Fixed Circuit Breakers
147
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 161: 5000 A Rear Connected T Vertical (RCTV)
Figure 162: 5000 A Rear Connected T Horizontal (RCTH)
148
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Masterpact NW Dimensional DrawingsIEC 4-pole Fixed Circuit Breakers
Figure 163: 6300 Rear Connected T Vertical (RCTV)
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionIntroduction
149
11/2004 19992004 Schneider Electric All Rights Reserved
SECTION 7SELECTION
INTRODUCTION
Masterpact

circuit breakers are available in three frame sizes:


T-frame circuit breakers: rated up to 800 A (ANSI Certified), up to 1600 A (UL Listed), and up to
1600 A (IEC Rated).
W-frame circuit breakers: rated up to 4000 A (ANSI Certified), up to 3000 A (UL Listed), and up to
4000 A (IEC Rated).
Y-frame circuit breakers: rated up to 5000 A (ANSI Certified), up to 6000 A (UL Listed), and up to
6300 A (IEC Rated).
Within each range, several sensor plugs are available to determine the maximum trip rating of each
circuit breaker. In addition to a sensor plug, an adjustable rating plug is available to get lower ampacity
than that available with the sensor plug.
Masterpact circuit breakers can be equipped with a variety of Micrologic electronic trip unit
configurations, ranging from basic circuit protection to more advanced relay protection and power
metering capabilities. Additionally all electronic trip units within the new Micrologic family are field
interchangeable and upgradeable. Each control unit is also equipped with an interchangeable and
upgradeable adjustable rating plug which is used to select the long-time pickup setting of the circuit
breaker.
NOTE: Masterpact circuit breakers are ordered by sensor plug rating, not ampere trip rating. The trip
rating of the circuit breaker is determined by the setting of the adjustable rating plug. Sensor plugs and
rating plugs are field replaceable.
Overview of Selection Procedure
1. Select the completely assembled circuit breaker (circuit breaker frame + trip unit):
The frame ampere rating required
The interrupting rating required
The sensor plug rating required
The connections
2. Select the trip unit, rating plug, and trip unit options.
3. Select circuit breaker frame options, if required.
4. Select cradle options, if required.
150
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionIntroduction
Table 62: Circuit Breaker Selection Options
Model Number NT NW NW
Frame type T W Y (wide-construction)
Maximum frame rating (A)
ANSI UL UL IEC ANSI ANSI UL IEC ANSI UL IEC
800 1200 1600 1600 3200 4000 3000 4000 5000 6000 6300
Maximum Interrupting Rating (kA RMS, 50/60 Hz)
AC rating
254 V
42 kA
240 V
200 kA
240 V
200 kA
240 V
150 kA
254 V
200 kA
254 V
100 kA
240 V
200 kA
240 V
150 kA
254 V
200 kA
240 V
200 kA
240 V
150 kA
508 V
42 kA
480 V
100 kA
480 V
100 kA
440 V
130 kA
508 V
200 kA
508 V
100 kA
480 V
150 kA
440 V
150 kA
508 V
200 kA
480 V
150 kA
440 V
150 kA
635 V
22 kA
600 V
50 kA
600 V
50 kA
690 V
42 kA
635 V
130 kA
635 V
85 kA
600 V
100 kA
690 V
100 kA
635 V
130 kA
600 V
100 kA
690 V
100 kA
Construction
Drawout
Fixed (UL Listed and IEC Rated only)
Termination
Rotatable rear terminals
Front-connected terminals
Accessories Available for the Circuit Breaker and Cradle
Shunt close Ready-to-close contact Door interlock
Shunt trip Overcurrent trip switch (standard) Operations counter
Undervoltage trip Rack in interlock Safety Shutter
Fixed time delay Key locks for circuit breaker and cradle Cradle rejection kit (standard)
Adjustable time delay Padlock attachment (circuit breaker + cradle) Rail Padlocking
Spring-charging motor Mechanical interlocks
Auxiliary contacts (standard) Cradle position switches
Electronic Trip Unit Features
True RMS sensing Zone-selective interlocking (ZSI) Temperature indication
LSI Communications Incremental fine-tuning of settings
Ground-fault alarm (no trip) LCD dot matrix display Selectable long-time delay bands
Ground-fault trip Advanced user interface Power measurement
Ground-fault trip and programmable alarm Protective relay functions Expanded memory
Adjustable rating plugs Thermal imaging Enhanced power quality measurement
Long-time pickup LED Neutral protection
Trip indication LED Contact wear indication
Table 63: Micrologic

Trip Unit Selection


Design Platform Designation Feature Type Protection Model Number
Basic Trip Unit Basic
LS0 (IEC Rated) 2.0
LI (UL Listed/ANSI Certified) 3.0
LSI 5.0
Trip Unit with Ammeter A
LS0 (IEC Rated) 2.0A
LI (UL Listed/ANSI Certified) 3.0A
LSI 5.0A
LSIG 6.0A
Trip Unit with Power Metering P
LSI 5.0P
LSIG 6.0P
Trip Unit with Harmonic Metering H
LSI 5.0H
LSIG 6.0H
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
151
11/2004 19992004 Schneider Electric All Rights Reserved
FACTORY-ASSEMBLED CIRCUIT BREAKERS AND SWITCHES
T-frame Circuit Breaker Selection


NOTE: L1F and LF circuit breakers are tested to show the arc flash hazard risk category as referenced
by NFPA 70E.
Table 64: ANSI C37 Certified/UL 1066 Listed T-frame Circuit Breakers
Frame Rating (A)
Model
Number
Interrupting Rating (kA)
Sensor Plug Rating (A)
254 V 508 V 635 V
800
NT08N1 42 42 100, 250, 400, 600, 800
NT08H1 42 42 22 100, 250, 400, 600, 800
Table 65: UL 489 Listed T-frame Circuit Breakers
Frame Rating (A)
Model
Number
Interrupting Rating (kA)
Sensor Plug Rating (A)
240 V 480 V 600 V
800
NT08N
NT08H
NT08L1
O
NT08L
O
NT08LF
O
50
65
100
200
200
50
50
65
100
100
35
50

100, 250, 400, 600, 800


100, 250, 400, 600, 800
100, 250, 400, 600, 800
100, 250, 400, 600, 800
100, 250, 400, 600, 800
1200
NT12N
NT12H
NT12L1
O
NT12L
O
NT12LF
O
50
65
100
200
200
50
50
65
100
100
35
50

600, 800, 1000, 1200


600, 800, 1000, 1200
600, 800, 1000, 1200
600, 800, 1000, 1200
600, 800, 1000, 1200
1600
NT16N
NT16H
NT16L1
O
NT16L
O
NT16LF
O
50
65
100
200
200
50
50
65
100
100
35
50

800, 1000, 1200, 1600


800, 1000, 1200, 1600
800, 1000, 1200, 1600
800, 1000, 1200, 1600
800, 1000, 1200, 1600
O
Not availabel in four-pole circuit breakers.
Table 66: IEC 60947-2 Rated T-frame Circuit Breakers
Frame Rating (A)
Model
Number
Interrupting Rating (kA)
Sensor Plug Rating
(A)
240 V 440 V 690 V 1000 V
800
NT08H1
NT08L1
42
150
42
130
42
25

250, 400, 630, 800


250, 400, 630, 800
1000
NT10H1
NT10L1
42
150
42
130
42
25

400, 630, 800, 1000


400, 630, 800, 1000
1250 NT12H1 42 42 42 630, 800, 1000, 1250
1600 NT16H1 42 42 42 800, 1000, 1250, 1600
152
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
T-frame Switch Selection


Table 67: ANSI C37 Certified/UL 1066 Listed, Non-automatic T-frame Switch
Frame Rating (A)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (0.5 s) Rating
(kA RMS)
254 V 508 V 635 V
800
NT08NA 42 42 NA 42
NT08HA 42 42 22 42
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Table 68: UL 489 Listed, Automatic T-frame Switches
Frame Rating (A)
Model
Number
Withstand Rating (kA RMS)

Instantaneous Override
(kA RMS)
240 V 480 V 600 V
800
NT08HF 65 50 50 40
NT08HB 200 100 N/A 10
1200
NT12HF 65 50 50 40
NT12HB 200 100 N/A 10
1600
NT16HF 65 50 50 40
NT16HB 200 100 N/A 10

The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
Table 69: IEC 60947-3 Rated, Non-automatic T-frame Switches
Frame Rating (A)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (0.5 s) Rating
(kA RMS)
240 V 440 V 690 V 1000 V
800 NT08HA 42 42 42 42
1000 NT10HA 42 42 42 42
1250 NT12HA 42 42 42 42
1600 NT16HA 42 42 42 42
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
153
11/2004 19992004 Schneider Electric All Rights Reserved
W-frame Circuit Breaker Selection
NOTE: L1F circuit breakers are tested to show the arc flash hazard risk category as referenced by
NFPA 70E.
Table 70: ANSI C37/UL 1066 Listed W-frame Circuit Breakers
Frame Rating (A)
Model
Number
Interrupting Rating (kA)
Sensor Plug Rating (A)
254 V 508 V 635 V
800
NW08N1 42 42 42 100, 250, 400, 600, 800
NW08H1 65 65 65 100, 250, 400, 600, 800
NW08H2 85 85 85 100, 250, 400, 600, 800
NW08H3 100 100 85 100, 250, 400, 600, 800
NW08L1
O
200 200 130 100, 250, 400, 600, 800
NW08L1F
O
200 200 130 100, 250, 400, 600, 800
1600
NW16N1 42 42 42 800, 1000, 1200, 1600
NW16H1 65 65 65 800, 1000, 1200, 1600
NW16H2 85 85 85 800, 1000, 1200, 1600
NW16H3 100 100 85 800, 1000, 1200, 1600
NW16L1
O
200 200 130 800, 1000, 1200, 1600
NW16L1F
O
200 200 130 800, 1000, 1200, 1600
2000
NW20H1 65 65 65 1000, 1200, 1600, 2000
NW20H2 85 85 85 1000, 1200, 1600, 2000
NW20H3 100 100 85 1000, 1200, 1600, 2000
NW20L1
O
100 200 130 1000, 1200, 1600, 2000
NW20L1F
O
200 200 130 1000, 1200, 1600, 2000
3200
NW32H1 65 65 65 1600, 2000, 2500, 3000, 3200
NW32H2 85 85 85 1600, 2000, 2500, 3000, 3200
NW32H3 100 100 85 1600, 2000, 2500, 3000, 3200
4000 (W-frame)

NW40BH1 65 65 65 2000, 2500, 3000, 3200, 3600, 4000


NW40BH2 85 85 85 2000, 2500, 3000, 3200, 3600, 4000
NW40BH3 100 100 85 2000, 2500, 3000, 3200, 3600, 4000
O
Not available for fixed-mounted or 4-pole circuit breakers

Not available in drawout


154
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
NOTE: LF circuit breakers are tested to show the arc flash hazard risk category as referenced by
NFPA 70E.
Table 71: UL 489 Listed W-frame Circuit Breakers
Frame Rating (A)
Model
Number
Interrupting Rating (kA)
Sensor Plug Rating
(A)
240 V 480 V 600 V
800
NW08N 65 65 50 100, 250, 400, 600, 800
NW08H 100 100 85 100, 250, 400, 600, 800
NW08L
O
200 150 100 100, 250, 400, 600, 800
NW08LF
O
200 150 100 100, 250, 400, 600, 800
1200
NW12N 65 65 50 600, 800, 1000, 1200
NW12H 100 100 85 600, 800, 1000, 1200
NW12L
O
200 150 100 600, 800, 1000, 1200
NW12LF
O
200 150 100 600, 800, 1000, 1200
1600
NW16N 65 65 50 800, 1000, 1200, 1600
NW16H 100 100 85 800, 1000, 1200, 1600
NW16L
O
200 150 100 800, 1000, 1200, 1600
NW16LF
O
200 150 100 800, 1000, 1200, 1600
2000
NW20N 65 65 50 1000, 1200, 1600, 2000
NW20H 100 100 85 1000, 1200, 1600, 2000
NW20L
O
200 150 100 1000, 1200, 1600, 2000
NW20LF
O
200 150 100 1000, 1200, 1600, 2000
2500
NW25H 100 100 85 1200, 1600, 2000, 2500
NW25L
O
200 150 100 1200, 1600, 2000, 2500
3000
NW30H 100 100 85 1600, 2000, 2500, 3000
NW30L
O
200 150 100 1600, 2000, 2500, 3000
O
Not available for fixed-mounted, 4-pole fixed, or 4-pole drawout circuit breakers
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
155
11/2004 19992004 Schneider Electric All Rights Reserved
Table 72: IEC 60947-2 Rated W-frame Circuit Breakers
Frame Rating (A)
Model
Number
Interrupting Rating (kA)
Sensor Plug Rating
(A)
240 V 440 V 690 V 1150 V
800
NW08N1 42 42 42 400, 630, 800
NW08H1 65 65 65 400, 630, 800
NW08H2 100 100 85 400, 630, 800
NW08L1

150 150 100 400, 630, 800


NW08H10

50 400, 630, 800


1000
NW10N1 42 42 42 400, 630, 800, 1000
NW10H1 65 65 65 400, 630, 800, 1000
NW10H2 100 100 85 400, 630, 800, 1000
NW10L1

150 150 100 400, 630, 800, 1000


NW10H10

50 400, 630, 800, 1000


1250
NW12N1 42 42 42 630, 800, 1000, 1250
NW12H1 65 65 65 630, 800, 1000, 1250
NW12H2 100 100 85 630, 800, 1000, 1250
NW12L1

150 150 100 630, 800, 1000, 1250


NW12H10

50 630, 800, 1000, 1250


1600
NW16N1 42 42 42 800, 1000, 1250, 1600
NW16H1 65 65 65 800, 1000, 1250, 1600
NW16H2 100 100 85 800, 1000, 1250, 1600
NW16L1

150 150 100 800, 1000, 1250, 1600


NW16H10

50 800, 1000, 1250, 1600


2000
NW20H1 65 65 65 1000, 1250, 1600, 2000
NW20H2 100 100 85 1000, 1250, 1600, 2000
NW20H3

150 150 100 1000, 1250, 1600, 2000
NW20L1

150 150 100 1000, 1250, 1600, 2000


NW20H10

50 1000, 1250, 1600, 2000


2500
NW25H1 65 65 65 1250, 1600, 2000, 2500
NW25H2 100 100 85 1250, 1600, 2000, 2500
NW25H3

150 150 100 1250, 1600, 2000, 2500


NW25H10

50 1250, 1600, 2000, 2500


3200
NW32H1 65 65 65 1600, 2000, 2500, 3200
NW32H2 100 100 85 1600, 2000, 2500, 3200
NW32H3

150 150 100 1600, 2000, 2500, 3200


NW32H10

50 1600, 2000, 2500, 3200


4000
NW40H1 65 65 65 2000, 2500, 3200, 4000
NW40H2 100 100 85 2000, 2500, 3200, 4000
NW40H3

150 150 100 2000, 2500, 3200, 4000


NW40H10

50 2000, 2500, 3200, 4000

Not available for fixed-mounted circuit breakers.


156
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
W-frame Switch Selection
Table 73: ANSI C37 Certified/UL 1066 Listed, Non-automatic Switch
Frame Rating (A)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (1s) Rating
(kA RMS)
254 V 508 V 635 V
800 NW08HA 65 65 65 65
1600 NW16HA 65 65 65 65
2000 NW20HA 65 65 65 65
3200 NW32HA 65 65 65 65
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Table 74: ANSI C37 Certified/UL 1066 Listed, Drawout Automatic Switch
Frame Rating (A)
(W-frame)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (1s) Rating
(kA RMS)
254 V 508 V 635 V
800
NW08HF
NW08HC
O
100
200
100
200
85
130
85
30
1600
NW16HF
NW16HC
O
100
200
100
200
85
130
85
30
2000
NW20HF
NW20HC
O
100
200
100
200
85
130
85
30
3200 NW32HF 100 100 85 85
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
O
Not available in four-pole
Table 75: ANSI C37 Certified/UL 1066 Listed, Fixed Automatic Switch
Frame Rating (A)
(W-frame)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (1s) Rating
(kA RMS)
254 V 508 V 635 V
800 NW08HF 100 100 85 85
1600 NW16HF 100 100 85 85
2000 NW20HF 100 100 85 85
3200 NW32HF 100 100 85 85
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Table 76: UL 489 Listed, Fixed Automatic Switch
Frame Rating (A)
Model
Number
Withstand Rating (kA RMS)

Instantaneous Override
(kA RMS)
240 V 480 V 600 V
800 NW08HF 100 100 85 40
1200 NW12HF 100 100 85 40
1600 NW16HF 100 100 85 40
2000 NW20HF 100 100 85 40
2500 NW25HF 100 100 85 65
3000 NW30HF 100 100 85 65

The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
157
11/2004 19992004 Schneider Electric All Rights Reserved
Table 77: UL 489 Listed, Drawout Automatic Switch
Frame Rating (A)
Model
Number
Withstand Rating (kA RMS)

Instantaneous Override
(kA RMS)
240 V 480 V 600 V
800
NW08HF
NW08HB
O
100
200
100
150
85
100
40
35
1200
NW12HF
NW12HB
O
100
200
100
150
85
100
40
35
1600
NW16HF
NW16HB
O
100
200
100
150
85
100
40
35
2000
NW20HF
NW20HB
O
100
200
100
150
85
100
40
35
2500
NW25HF
NW25HB
O
100
200
100
150
85
100
65
65
3000
NW30HF
NW30HB
O
100
200
100
150
85
100
65
65

The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
O
Not available in four-pole
Table 78: IEC 60947-3 Rated, Automatic Switch
Frame Rating (A)
Model
Number
Withstand Rating (kA RMS)

Instantaneous Override
(kA RMS)
240 V 440 V 690 V
800 NW08HF 85 85 85 85
1000 NW10HF 85 85 85 85
1250 NW12HF 85 85 85 85
1600 NW16HF 85 85 85 85
2000 NW20HF 85 85 85 85
2500 NW25HF 85 85 85 85
3200 NW32HF 85 85 85 85
4000 NW40HF 85 85 85 85

The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
158
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
Y-frame Circuit Breaker Selection
Table 79: IEC 60947-3 Rated, Non-automatic
Frame Rating (A)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (1s) Rating
(kA RMS)
240 V 440 V 690 V 1150 V
800
NW08NA 42 42 42 42
NW08HA 50 50 50 50
NW08HA10

50 50
1000
NW10NA 42 42 42 42
NW10HA 50 50 50 50
NW10HA10

50 50
1250
NW12NA 42 42 42 42
NW12HA 50 50 50 50
NW12HA10

50 50
1600
NW16NA 42 42 42 42
NW16HA 50 50 50 50
NW16HA10

50 50
2000
NW20HA 50 50 50 50
NW20HA10

50 50
2500
NW25HA 50 50 50 50
NW25HA10

50 50
3200
NW32HA 50 50 50 50
NW32HA10

50 50
4000
NW40HA 50 50 50 50
NW40HA10

50 50
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.

Not available for fixed-mounted circuit breakers.


Table 80: ANSI C37 Certified/UL 1066 Listed Y-frame Circuit Breakers
Frame Rating (A)
Model
Number
Interrupting Rating (kA)
Sensor Plug Rating (A)
254 V 508 V 635 V
3200 to 4000
NW32L1
O
200 200 130 1600, 2000, 2500, 3000, 3200
NW40H2 85 85 85 2000, 2500, 3000, 3200, 4000
NW40H3 100 100 85 2000, 2500, 3000, 3200, 4000
NW40L1
O
200 200 130 2000, 2500, 3000, 3200, 4000
5000
NW50H2 85 85 85 2500, 3000, 3200, 4000, 5000
NW50H3 100 100 85 2500, 3000, 3200, 4000, 5000
NW50L1
O
200 200 130 2500, 3000, 3200, 4000, 5000
O
Not available for fixed-mounted, 4-pole fixed, or 4-pole drawout circuit breakers.
Table 81: UL 489 Listed Y-frame Circuit Breakers
Frame Rating (A)
Model
Number
Interrupting Rating (kA)
Sensor Plug Rating (A)
240 V 480 V 600 V
4000
NW40H 100 100 85 2000, 2500, 3000, 4000
NW40L
O
200 150 100 2000, 2500, 3000, 4000
5000
NW50H 100 100 85 2500, 3000, 4000, 5000
NW50L
O
200 150 100 2500, 3000, 4000, 5000
6000
NW60H 100 100 85 3000, 4000, 5000, 6000
NW60L
O
200 150 100 3000, 4000, 5000, 6000
O
Not available for fixed-mounted, 4-pole fixed, or 4-pole drawout circuit breakers.
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
159
11/2004 19992004 Schneider Electric All Rights Reserved
Y-frame Switch Selection
Table 82: IEC 60947-2 Rated Y-frame Circuit Breakers
Frame Rating (A)
Model
Number
Interrupting Rating (kA)
Sensor Plug Rating (A)
240 V 440 V 690 V
5000
NW50H1 100 100 100 2500, 3200, 4000, 5000
NW50H2 150 150 100 2500, 3200, 4000, 5000
6300
NW63H1 100 100 100 3200, 4000, 5000, 6300
NW63H2 150 150 100 3200, 4000, 5000, 6300
Table 83: ANSI C37 Certified/UL 1066 Listed, Non-automatic Switches
Frame Rating (A)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (1s) Rating
(kA RMS)
254 V 508 V 635 V
4000 NW40HA 85 85 85 85
5000 NW50HA 85 85 85 85
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Table 84: ANSI C37 Certified/UL 1066 Listed, Drawout Automatic Switches
Frame Rating (A)
(Y-frame)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (1s) Rating
(kA RMS)
254 V 508 V 635 V
3200 NW32HC
O
200 200 130 100
4000
NW40HF
NW40HC
O
100
200
100
200
85
130
85
100
5000
NW50HF
NW50HC
O
100
200
100
200
85
130
85
100
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
O
Not available in 4-pole
Table 85: ANSI C37 Certified/UL 1066 Listed, Fixed Automatic Switches
Frame Rating (A)
(Y-frame)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (1s) Rating
(kA RMS)
254 V 508 V 635 V
4000 NW40HF 100 100 85 85
5000 NW50HF 100 100 85 85
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Table 86: UL 489 Listed, Fixed Automatic Switches
Frame Rating (A)
Model
Number
Withstand Rating (kA RMS)

Instantaneous Override
(kA RMS)
240 V 480 V 600 V
4000 NW40HF 100 100 85 75
5000 NW50HF 100 100 85 75
6000 NW60HF 100 100 85 75

The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a
circuit breaker with an equal continuous current rating.
160
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
Table 87: UL 489 Listed, Drawout Automatic Switches
Frame Rating (A)
Model
Number
Withstand Rating (kA RMS)

Instantaneous Override
(kA RMS)
240 V 480 V 600 V
4000
NW40HF
NW40HB
O
100
200
100
150
85
100
75
75
5000
NW50HF
NW50HB
O
100
200
100
150
85
100
75
75
6000
NW60HF
NW60HB
O
100
200
100
150
85
100
75
75

The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit
breaker with an equal continuous current rating.
O
Not available in four-pole
Table 88: IEC 60947-3 Rated, Non-automatic Switches
Frame Rating (A)
Model
Number
Interrupting Rating (kA RMS)
4
Short-time (1s) Rating
(kA RMS)
240 V 440 V 690 V
5000 NW50HA 85 85 85 85
6300 NW63HA 85 85 85 85
4
When used in conjunction with an overcurrent relay, circuit breaker, or fuse.
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
161
11/2004 19992004 Schneider Electric All Rights Reserved
REQUEST FOR QUOTATION FORM
For faster quote processing, please use the following request for quotation form. For each section, check the applicable box or enter value
corresponding to your choice. Note: this request for quotation form does not take into account incompatibilities. Orders to be placed on CSSS.
Date
From Location
Customer Name:
Account No.:
Contact Name:
Location:
Choose one:
Push-in terminal (standard)
Ring terminal
Spring-charging motor (MCH)
Shunt close (XF):
Instantaneous
Fixed-time delayed
Adjustable-time delayed
Shunt trip (MX1): Vac
Vac
Vdc
Vdc
Vdc
Vdc
Vdc
Vdc
Vdc
Vac Standard or Communication
Standard or Communication
Vac
Vac
Vac
Vac
Electrical closing push button
Remote reset after fault trip (RES)
(incompatible with SDE2)
Additional shunt trip (MX2)
OR
Undervoltage trip (MN)choose one:
Fax No.:
Phone No.:
Q2C No.:
RFQ No.:
Phone No. Fax No.
Quantity:
Square D Merlin Gerin
Federal Pioneer
ANSI UL IEC
NW
Amperes:
Amperes:
2.0 3.0
5.0 (BPFE)
110130 Vac
200240 Vac 3.0A 2.0A
5.0A
6.0A
5.0P
6.0P
5.0H
6.0H
(CT)
(MDGF)
(SGR)
(RAR)
(M2C)
(M6C)
(BCM)
(CCM)
(RIM)
input voltage
or 2
or 2 quantity: 1
1
4 3
NT
Messages
Circuit Breakers or Switches
Cradle Secondary Disconnects
Accessories for Remote Operation
Wiring for Cradle (Complete only if ordering cradle without circuit breaker)
Micrologic

Trip Units
Dummy Trip Unit (for switch only)
Basic Trip Unit
Trip Unit with Ammeter
Trip Unit with Power Metering
Trip Unit with Harmonic Metering
Micrologic

Trip Unit Accessories


Brand:
Standard
Type
Number of Poles
Frame rating
Sensor plug rating
Cradle options:
Basic protection
Basic protection
Selective protection
Selective protection
Selective protection
Rating plug type (A=UL/ANSI; R=IEC)
(for non-standard, see page 41)
Choose one:
Choose one:
Restraint interface module
External power supply (24 Vdc)
Number of power supplies/circuit breaker:
Battery backup
External voltage sensing
Automatic reset
Modbus

circuit breaker com. module


Modbus

cradle com. module


Programmable contact module
Programmable contact module
External neutral sensor
Wiring for eight additional form C auxiliary switches (push-in terminals) (OF)
Manufacturing Numbers Provided with Quotation
Circuit Breaker:
Cradle:
Wiring for four additional form C auxiliary switches (push-in terminals) or
2a+2b auxiliary switches (ring terminals) (OF)
Wiring for ready-to-close contact (PF)
Wiring for shunt trip (MX), shunt close (XF) and spring-charging motor (MCH)
Wiring for undervoltage trip (MN) or additional shunt trip (MX2)
Wiring for additional overcurrent trip switch (SDE2) or electrical reset (RES)
Wiring for programmable contact modules (M2C and M6C)
See Delivery Schedule on the next page
Not available on Masterpact NT (T-frame circuit breaker)
Wiring for zone-selective interlocking (ZSI), modified differential
ground fault (MDGF), neutral current transformer (CT) and 24 V power supply
Circuit breaker communication module (BCM) wiring
Mod. differential ground-fault
Source ground return
Selective protection + equip. ground fault
Selective protection + equip. ground fault
Selective protection + equip. ground fault
Selective protection
Optional characterization for CTs
Circuit breaker with cradle
Circuit breaker without cradle
Cradle only
Fixed breaker
Interrupting/Withstand rating: N, N1, NA, L, LF, L1,
L1F, H, H2, H3, H10, HA, HA10, HF, HB, HC
Page 1 of 2
162
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


SelectionFactory-Assembled Circuit Breakers and Switches
REQUEST FOR QUOTATION FORM
Auxiliary switch (OF)
Overcurrent trip switches
Additional overcurrent trip switches (choose one)
Ready-to-close switch (PF)
Push-in type cradle postion switches (1a/1b form C)
Choose one:
Connected position (max. qty.: 3 NW/3 NT)
Test position (max. qty.: 3 NW/1 NT)
Disconnected position (max. qty.: 3 NW/2 NT)
Connected/Closed switch
Connected position (max. 3a or 3b)
Test postion (max. 1a or 1b)
Disconnected postion (max. 3a or 3b)
Padlockable push button cover
Padlock provision only
Kirk

Ronis

Profalux

Castell

Federal Pioneer

One key lock


Two key locks keyed alike
(select manufacturer below)
Two key locks keyed differently
(select manufacturer below)
Not available on Masterpact NT (T-frame circuit breaker)
Not available on IEC circuit breaker
Key lock manufacturer
Circuit Breaker:
Cradle:
Circuit breaker and cradle to be shipped together
Cradle to be shipped prior to circuit breaker
Schneider Electric Conditions of Sale Apply
(select manufacturer below)
(max. qty.: 8)
(max. qty.: 8) Connected/Closed switch
Low-level cradle position switch
Ring terminal type cradle position switches (1a or 1b contact)
Standard (1a/1b form C) (SDE1) standard
(SDE2)
(FCF)
(FCT)
(FCF)
(FCT)
(RCTV)
(RCTH)
(RCOV)
(RCOV)
(RCTV)
(RCTH)
Front-connected flat
Front-connected flat
Rear-connected "T" vertical
Rear-connected "T" horizontal
Rear-connected "T" vertical
Rear-connected "T" horizontal
Rear-connected offset vertical
Rear-connected offset vertical
Front-connected "T"
Front-connected "T"
8003200 A
8003200 A
3200 A (ANSI)
4000 A
2000 A L1/L
40005000 A
40006300 A
(CE)
Qty.
Qty.
qty/type
qty/type
qty/type
(CT)
(CD)
(EF)
(low-level EF)
(low-level SDE2)
low-level Std
(1a/1b form C) (incompatible with RES)
(1a/1b form C) (incompatible with RES)
Push-in type terminal or Ring terminal Front-connected
Door interlock
Open door recking interlock
Automatic spring discharge
Cradle rejection kit
Terminal shield
Rail padlocking
Mechanical operation counter
Shutter
Hand-held test kit
Full-function test kit
Shutter with padlock provision and position indicator
Lifting device for lifting hooks
T-frame, W-frame, or Y-frame circuit breaker lifting bar
Transparent cover w/ door escutcheon (drawout circuit breaker only)
Metering CT (optional for UL/ANSI only)
std. on UL/ANSI, check for IEC
std. on UL/ANSI, check for IEC
standard
(Set of 2)
(long)
(short)
std. on UL/ANSI, check for IEC
Racking interlock between racking crank and Off position
Rear-connected
4a/4b form C (std.) 2a + 2b
4a + 4b 4a/4b low level NT
8a/8b form C
12a/12b form C
choose one:
Auxiliary, Alarm and Cradle Position Switches
Locking and Interlocking
Manufacturing Number (provided with quotation)
Delivery Schedule
$
List Price
Delivery (from receipt of order)
$
$ Total
Brkr Cradle
Cradle Connections
Cradle Interlocking and Accessories
Miscellaneous Accessories
Test Equipment
Page 2 of 2
Masterpact

NT and NW Universal Power Circuit Breakers


Trip Curves
163
11/2004 19992004 Schneider Electric All Rights Reserved
SECTION 8TRIP CURVES
MICROLOGIC 6.0 A/P/H TRIP UNITS:....................................................................................................... 164
Ground Fault I
2
t OFF and ON, In 400 A.............................................................................................. 164
Ground Fault I
2
t OFF and ON, 400 A < I
n
1200 A .............................................................................. 165
Ground Fault I
2
t OFF and ON, I
n
> 1200 A .......................................................................................... 166
MICROLOGIC 5.0/6.0 A/P/H TRIP UNITS ................................................................................................. 167
Long-time Pickup and Delay, Short-time Pickup, and I
2
t OFF Delay..................................................... 167
Short-time Pickup and I
2
t ON Delay...................................................................................................... 168
Instantaneous Pickup, 2x to 15x and OFF............................................................................................ 169
MICROLOGIC 3.0A TRIP UNITS ............................................................................................................... 170
Long-time Pickup and Delay ................................................................................................................. 170
Instantaneous Pickup, 1.5X to 12X....................................................................................................... 171
MICROLOGIC 2.0A TRIP UNIT ................................................................................................................. 172
MICROLOGIC 2.0/3.0/5.0/6.0 A/P/H TRIP UNIT INSTANTANEOUS OVERRIDE VALUES...................... 173
MASTERPACT NW/NT LOW ARC FLASH CIRCUIT BREAKERS ............................................................ 174
Masterpact NW Low Arc Flash Circuit Breaker: L1F and LF................................................................. 174
Masterpact NT Low Arc Flash Circuit Breaker: L1F and LF.................................................................. 174
164
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Trip CurvesMicrologic 6.0 A/P/H Trip Units
MICROLOGIC 6.0 A/P/H TRIP UNITS
Figure 164: Micrologic 6.0 A/P/H Trip Units: I
n
400 A
.1
5 .1
.1
MULTIPLES OF SENSOR RATING (In)
MULTIPLES OF SENSOR RATING (In)
Curve No. 0613TC0001
Drawing No. B48095-613-01
.0
5
.0
6
.0
7
.0
8
.0
9
.1
5
.2.3.4.5.6.7.8.911
.5
234567891
0
.0
5
.0
6
.0
7
.0
8
.0
9.2.3.4.5.6.7.8.91
1
.523456789
1
0
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
6000
7000
8000
9000
5000
10000
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
1.5
2
3
4
5
6
7
8
9
10
1.5
2
3
4
5
6
7
8
9
10
15
20
30
40
50
60
70
80
90
100
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
T
I
M
E

I
N

S
E
C
O
N
D
S
CYCLE 2
1
1 CYCLE
150
0
.
4
O
N
0
.
3
O
N
0
.
2
O
N
0
.
1
O
N
0.4 OFF
0.3 OFF
0.2 OFF
0.1 OFF
0
GROUND-FAULT
DELAY BANDS
I
2
t ON
GROUND-FAULT
PICKUP
x In
GROUND-FAULT
DELAY BANDS
I
2
t OFF
(FIXED DELAY)
DELAY
SECONDS AT 1 x In
0.1
0.2
0.3
0.4
MAXIMUM
UNRESTRAINED
GROUND-FAULT
DELAY
0.5 0.7 0.9
0.4
0.6 0.8 1.0
0.3
MICROLOGIC 6.0 A/P/H Trip Units
with Adjustable Ground-fault Pickup and Delay
Characteristic Trip Curve No. 613-1
Ground Fault I
2
t OFF and ON
I
n
400 A
The time-current curve information is to be used for
application and coordination purposes only.
Curves apply from -30C to +60C (-22F to +140F)
ambient temperature.
B
4
8
0
9
5
-
6
1
3
-
0
1
.
e
p
s
Masterpact

NT and NW Universal Power Circuit Breakers


Trip CurvesMicrologic 6.0 A/P/H Trip Units
165
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 165: Micrologic 6.0 A/P/H Trip Units: 400 A < I
n
1200 A
.1
5 .1
.1
MULTIPLES OF SENSOR RATING (In)
MULTIPLES OF SENSOR RATING (In)
.0
5
.0
6
.0
7
.0
8
.0
9
.1
5
.2.3.4.5.6.7.8.911
.5
234567891
0
.0
5
.0
6
.0
7
.0
8
.0
9.2.3.4.5.6.7.8.91
1
.523456789
1
0
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
6000
7000
8000
9000
5000
10000
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
1.5
2
3
4
5
6
7
8
9
10
1.5
2
3
4
5
6
7
8
9
10
15
20
30
40
50
60
70
80
90
100
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
T
I
M
E

I
N

S
E
C
O
N
D
S
CYCLE 2
1
1 CYCLE
150
0.2
0
.
2
O
N
0
.
4
O
N
0
.
3
O
N
0
.
1
O
N
0.4 OFF
0.3 OFF
0.2 OFF
0.1 OFF
0
GROUND-FAULT
DELAY BANDS
I
2
t ON
GROUND-FAULT
PICKUP
x In
GROUND-FAULT
DELAY BANDS
I
2
t OFF
(FIXED DELAY)
DELAY
SECONDS AT 1 x In
0.1
0.2
0.3
0.4
MAXIMUM
UNRESTRAINED
GROUND-FAULT
DELAY
0.3 0.5 0.7 0.9
0.4 0.6 0.8 1.0
Curve No. 0613TC0002
Drawing No. B48095-613-02
Micrologic 6.0 A/P/H Trip Units
with Adjustable Ground-fault Pickup and Delay
Characteristic Trip Curve No. 613-2
Ground Fault I
2
t OFF and ON
400 A < I
n
1200 A
B
4
8
0
9
5
-
6
1
3
-
0
2
.e
p
s
The time-current curve information is to be used for
application and coordination purposes only.
Curves apply from -30C to +60C (-22F to +140F)
ambient temperature.
166
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Trip CurvesMicrologic 6.0 A/P/H Trip Units
Figure 166: Micrologic 6.0 A/P/H Trip Units: I
n
> 1200 A
.1
5 .1
.1
AMPERES x 10
3
AMPERES x 10
3
.0
5
.0
6
.0
7
.0
8
.0
9
.1
5
.2.3.4.5.6.7.8.911
.5
234567891
0
.0
5
.0
6
.0
7
.0
8
.0
9.2.3.4.5.6.7.8.91
1
.523456789
1
0
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
6000
7000
8000
9000
5000
10000
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
1.5
2
3
4
5
6
7
8
9
10
1.5
2
3
4
5
6
7
8
9
10
15
20
30
40
50
60
70
80
90
100
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
T
I
M
E

I
N

S
E
C
O
N
D
S
CYCLE 2
1
1 CYCLE
150
0
.
1
O
N
0
.
3
O
N
0
.
4
O
N
0
.
2
O
N
0.4 OFF
5
0
0

A
7
2
0

A
1
0
4
0

A
1
2
0
0

A
8
8
0

A
6
4
0

A
8
0
0

A
9
6
0

A
1
1
2
0

A
0.3 OFF
0.2 OFF
0.1 OFF
0
GROUND-FAULT
DELAY BANDS
I
2
t ON
GROUND-FAULT
PICKUP
x In
GROUND-FAULT
DELAY BANDS
I
2
t OFF
(FIXED DELAY)
DELAY
SECONDS AT 1 x In
0.1
0.2
0.3
0.4
MAXIMUM
UNRESTRAINED
GROUND-FAULT
DELAY
Curve No. 0613TC0003
Drawing No. B48095-613-03
Micrologic 6.0 A/P/H Trip Units
with Adjustable Ground-fault Pickup and Delay
Characteristic Trip Curve No. 613-3
Ground Fault I
2
t OFF and ON
I
n
> 1200 A
The time-current curve information is to be used for
application and coordination purposes only.
Curves apply from -30C to +60C (-22F to +140F)
ambient temperature.
B
4
8
0
9
5
-
6
1
3
-
0
3
.
e
p
s
Masterpact

NT and NW Universal Power Circuit Breakers


Trip CurvesMicrologic 5.0/6.0 A/P/H Trip Unit
167
11/2004 19992004 Schneider Electric All Rights Reserved
MICROLOGIC 5.0/6.0 A/P/H TRIP UNIT
Figure 167: Micrologic 5.0/6.0 A/P/H Trip Units: Long-time Pickup and Delay, Short-time Pickup, and I
2
t OFF Delay
1
.5 1
1
CURRENT IN MULTIPLES OF Ir (Ir = LONG-TIME SETTING x In)
CURRENT IN MULTIPLES OF Ir
(Ir = LONG-TIME SETTING x In)
.5.6.7.8.91
.5
234567891
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
.5.6.7.8.923456789
1
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
6000
7000
8000
9000
5000
10000
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
1.5
2
3
4
5
6
7
8
9
10
1.5
2
3
4
5
6
7
8
9
10
15
20
30
40
50
60
70
80
90
100
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
T
I
M
E

I
N

S
E
C
O
N
D
S
CYCLE 2
1
1 CYCLE
150
24
20
.5
24
16
12
8
8
6
4
2.5 1.5 2
3 5
10
4
2
1
16
0.4 OFF
0.3 OFF
0.2 OFF
0.1 OFF
0
LONG-TIME PICKUP
x In = Ir
LONG-TIME
DELAY BANDS
SECONDS AT 6 x Ir
MAXIMUM
UNRESTRAINED
SHORT-TIME
DELAY
SHORT-TIME
DELAY I
2
t OFF
(FIXED-TIME DELAY)
SECONDS AT 10 x Ir
SHORT-TIME
PICKUP
x Ir
Curve No. 0613TC0004
Drawing No. B48095-613-04
B
4
8
0
9
5
-
6
1
3
-
0
4
.
e
p
s
Micrologic 5.0/6.0 A/P/H Trip Units
Characteristic Trip Curve No. 613-4
Long-time Pickup and Delay
Short-time Pickup and I
2
t OFF Delay
The time-current curve information is to be used for
application and coordination purposes only.
Curves apply from -30C to +60C (-22F to +140F)
ambient temperature.
NOTE:
1. There is a thermal-imaging effect that can act to
shorten the long-time delay. The thermal-imaging
effect comes into play if a current above the long-
time delay pickup value exists for a time and then is
cleared by the tripping of a downstream device or
the circuit breaker itself. A subsequent overload will
cause the circuit breaker to trip in a shorter time than
normal. The amount of time delay reduction is
inverse to the amount of time that has elapsed since
the previous overload. Approximately twenty
minutes is required between overloads to completely
reset thermal-imaging.
2. The end of the curve is determined by the
interrupting rating of the circuit breaker.
3. With zone-selective interlocking ON, short-time
delay utilized, and no restraining signal, the
maximum unrestrained short-time delay time band
applies regardless of the setting.
4. Total clearing times shown include the response
times of the trip unit, the circuit breaker opening, and
the extinction of the current.
5. For a withstand circuit breaker, instantaneous can
be turned OFF. See trip curve 613-7 for
instantaneous trip curve. See trip curve 613-10 for
instantaneous override values.
6. Overload indicator illuminates at 100%.
168
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Trip CurvesMicrologic 5.0/6.0 A/P/H Trip Unit
Figure 168: Micrologic 5.0/6.0 A/P/H Trip Units: Short-time Pickup and I
2
t ON Delay
1
.5 1
1
CURRENT IN MULTIPLES OF Ir (Ir = LONG-TIME SETTING x In)
CURRENT IN MULTIPLES OF Ir
(Ir = LONG-TIME SETTING x In)
.5.6.7.8.91
.5
234567891
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
.5.6.7.8.923456789
1
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
6000
7000
8000
9000
5000
10000
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
1.5
2
3
4
5
6
7
8
9
10
1.5
2
3
4
5
6
7
8
9
10
15
20
30
40
50
60
70
80
90
100
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
T
I
M
E

I
N

S
E
C
O
N
D
S
CYCLE 2
1
1 CYCLE
150
2.5 2
3 4 5
6 8 10 1.5
0.4 ON
0
.
4

O
N
0
.
2

O
N
0
.
3

O
N
0
.
1

O
N
0.3 ON
0.2 ON
0.1 ON
SHORT-TIME
DELAY I
2
t ON
SECONDS AT 10 x Ir
SHORT-TIME
PICKUP
x Ir
MAXIMUM
UNRESTRAINED
SHORT-TIME
DELAY
Curve No. 0613TC0005
Drawing No. B48095-613-05
Micrologic 5.0/6.0 A/P/H Trip Units
Characteristic Trip Curve No. 613-5
Short-time Pickup and I
2
t ON Delay
The time-current curve information is to be used for
application and coordination purposes only.
Curves apply from -30C to +60C (-22F to +140F)
ambient temperature.
NOTE:
1. There is a thermal-imaging effect that can act to
shorten the long-time delay. The thermal-imaging
effect comes into play if a current above the long-time
delay pickup value exists for a time and then is cleared
by the tripping of a downstream device or the circuit
breaker itself. A subsequent overload will cause the
circuit breaker to trip in a shorter time than normal. The
amount of time delay reduction is inverse to the
amount of time that has elapsed since the previous
overload. Approximately twenty minutes is required
between overloads to completely reset thermal-
imaging.
2. The end of the curve is determined by the interrupting
rating of the circuit breaker.
3. With zone-selective interlocking ON, short-time delay
utilized, and no restraining signal, the maximum
unrestrained short-time delay time band applies
regardless of the setting.
4. Total clearing times shown include the response times
of the trip unit, the circuit breaker opening, and the
extinction of current.
5. For withstand circuit breaker, instantaneous can be
turned OFF. See trip curve 613-7 for instantaneous trip
curve. See trip curve 613-10 for instantaneous
override values.
6. See Trip Curve 613-4 for long-time pickup and delay
trip curve.
Masterpact

NT and NW Universal Power Circuit Breakers


Trip CurvesMicrologic 5.0/6.0 A/P/H Trip Unit
169
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 169: Micrologic 5.0/6.0 Trip Units: Instantaneous Pickup, 2x to 15x and OFF
1
.5 1
1
MULTIPLES OF SENSOR RATING (In)
MULTIPLES OF SENSOR RATING (In)
.5.6.7.8.91
.5
234567891
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
.5.6.7.8.923456789
1
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
6000
7000
8000
9000
5000
10000
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
1.5
2
3
4
5
6
7
8
9
10
1.5
2
3
4
5
6
7
8
9
10
15
20
30
40
50
60
70
80
90
100
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
T
I
M
E

I
N

S
E
C
O
N
D
S
CYCLE 2
1
1 CYCLE
150
INSTANTANEOUS
PICKUP
x In
10 x
2 x 3 x 4 x 6 x 8 x 12 x 15 x
Curve No. 0613TC0007
Drawing No. B48095-613-07
Micrologic 5.0/6.0 Trip Units
Characteristic Trip Curve No. 613-7
Instantaneous Pickup, 2X to 15X and OFF
The time-current curve information is to be used for
application and coordination purposes only.
Curves apply from -30C to +60C (-22F to +140F)
ambient temperature.
NOTE:
1. The end of the curve is determined by the interrupting
rating of the circuit breaker.
2. Total clearing times shown include the response
times of the trip unit, the circuit breaker opening, and
the extinction of current.
3. The instantaneous region of the trip curve shows
maximum total clearing times. Actual clearing times in
this region can vary depending on the circuit breaker
mechanism design and other factors. The actual
clearing time can be considerably faster than
indicated. Contact your local sales office for additional
information.
4. For a withstand circuit breaker, instantaneous can be
turned OFF. See trip curve 613-7 for the
instantaneous trip curve. See trip curve 613-10 for the
instantaneous override values.
5. See trip curve 613-4 and trip curve
613-5 for long-time pickup, long-time delay, short-
time pickup and short-time delay trip curves.
170
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Trip CurvesMicrologic 3.0 Trip Units
MICROLOGIC 3.0 TRIP UNITS
Figure 170: Micrologic 3.0A Trip Unit: Long-time Pickup and Delay
1
.5 1
1
CURRENT IN MULTIPLES OF Ir (Ir = LONG-TIME SETTING x In)
CURRENT IN MULTIPLES OF Ir
(Ir = LONG-TIME SETTING x In)
.5.6.7.8.91
.5
234567891
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
.5.6.7.8.923456789
1
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
6000
7000
8000
9000
5000
10000
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
1.5
2
3
4
5
6
7
8
9
10
1.5
2
3
4
5
6
7
8
9
10
15
20
30
40
50
60
70
80
90
100
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
T
I
M
E

I
N

S
E
C
O
N
D
S
CYCLE 2
1
1 CYCLE
150
24
20
12
.5
8
4
2
1
16
24
16
LONG-TIME PICKUP
x In = Ir
LONG-TIME DELAY
SECONDS AT 6 x Ir
Curve No. 0613TC0006
Drawing No. B48095-613-06
Micrologic 3.0A Trip Unit
Characteristic Trip Curve No. 613-6
Long-time Pickup and Delay
The time-current curve information is to be used for
application and coordination purposes only.
Curves apply from -30C to +60C (-22F to +140F)
ambient temperature.
NOTE:
1. There is a thermal-imaging effect that can act to
shorten the long-time delay. The thermal-imaging
effect comes into play if a current above the long-time
delay pickup value exists for a time and then is cleared
by the tripping of a downstream device or the circuit
breaker itself. A subsequent overload will cause the
circuit breaker to trip in a shorter time than normal. The
amount of time delay reduction is inverse to the
amount of time that has elapsed since the previous
overload. Approximately twenty minutes is required
between overloads to completely reset thermal-
imaging.
2. The end of the curve is determined by the
instantaneous setting of the circuit breaker.
3. Total clearing times shown include the response times
of the trip unit, the circuit breaker opening, and the
extinction of current.
4. See trip curve 613-8 for instantaneous pickup trip
curve.
Masterpact

NT and NW Universal Power Circuit Breakers


Trip CurvesMicrologic 3.0 Trip Units
171
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 171: Micrologic 3.0A Trip Unit: Instantaneous Pickup, 1.5X to 12X
1
.5 1
1
MULTIPLES OF SENSOR RATING (In)
MULTIPLES OF SENSOR RATING (In)
.5.6.7.8.91
.5
234567891
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
.5.6.7.8.923456789
1
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
6000
7000
8000
9000
5000
10000
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
1.5
2
3
4
5
6
7
8
9
10
1.5
2
3
4
5
6
7
8
9
10
15
20
30
40
50
60
70
80
90
100
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
T
I
M
E

I
N

S
E
C
O
N
D
S
CYCLE 2
1
1 CYCLE
150
1.5 x
INSTANTANEOUS
PICKUP
x In
5 x 10 x
2 x 3 x 4 x 6 x 8 x 12 x
Curve No. 0613TC0008
Drawing No. B48095-613-08
Micrologic 3.0A Trip Unit
Characteristic Trip Curve No. 613-8
Instantaneous Pickup, 1.5X to 12X
The time-current curve information is to be used for
application and coordination purposes only.
Curves apply from -30C to +60C (-22F to +140F)
ambient temperature.
NOTE:
1. The end of the curve is determined by the interrupting
rating of the circuit breaker.
2. Total clearing times shown include the response
times of the trip unit, the circuit breaker opening, and
the extinction of current.
3. The instantaneous region of the trip curve shows
maximum total clearing times. Actual clearing times in
this region can vary depending on the circuit breaker
mechanism design and other factors. The actual
clearing time can be considerably faster than
indicated. Contact your local sales office for additional
information.
4. See trip curve 613-6 for long-time pickup and delay
trip curves.
172
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Trip CurvesMicrologic 3.0 Trip Units
Figure 172: Micrologic 2.0A Trip Unit
1
.5 1
1
CURRENT IN MULTIPLES OF Ir (Ir = LONG-TIME SETTING x In)
CURRENT IN MULTIPLES OF Ir
(Ir = LONG-TIME SETTING x In)
.5.6.7.8.91
.5
234567891
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
.5.6.7.8.923456789
1
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
6000
7000
8000
9000
5000
10000
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
1.5
2
3
4
5
6
7
8
9
10
1.5
2
3
4
5
6
7
8
9
10
15
20
30
40
50
60
70
80
90
100
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
600
700
800
900
1000
1500
2000
3000
4000
5000
6000
7000
8000
9000
10000
T
I
M
E

I
N

S
E
C
O
N
D
S
CYCLE 2
1
1 CYCLE
150
24
20
.5
16
12
8
2.5 1.5 2
4
3 5
6
8
10
4
2
1
16
LONG-TIME PICKUP
x In = Ir
LONG-TIME
DELAY BANDS
SECONDS AT 6 x Ir
SHORT-TIME
PICKUP
x Ir
24
Curve No. 0613TC0009
Drawing No. B48095-613-09
Micrologic 2.0A Trip Unit
Characteristic Trip Curve No. 613-9
Long-time Pickup and Delay
Short-time Pickup with No Delay
The time-current curve information is to be used for
application and coordination purposes only.
Curves apply from -30C to +60C (-22F to +140F)
ambient temperature.
NOTE:
1. There is a thermal-imaging effect that can act to
shorten the long-time delay. The thermal-imaging
effect comes into play if a current above the long-time
delay pickup value exists for a time and then is cleared
by the tripping of a downstream device or the circuit
breaker itself. A subsequent overload will cause the
circuit breaker to trip in a shorter time than normal. The
amount of time delay reduction is inverse to the
amount of time that has elapsed since the previous
overload. Approximately twenty minutes is required
between overloads to completely reset thermal-
imaging.
2. The end of the curve is determined by the short-time
setting.
3. Total clearing times shown include the response times
of the trip unit, the circuit breaker opening, and the
extinction of current.
4. Overload indicator illuminates at 100%.
B
4
8
0
9
5
-
6
1
3
-
0
9
.
e
p
s
Masterpact

NT and NW Universal Power Circuit Breakers


Trip CurvesMicrologic 3.0 Trip Units
173
11/2004 19992004 Schneider Electric All Rights Reserved
Figure 173: Micrologic 2.0/3.0/5.0/6.0 A/P/H Trip Unit Instantaneous Override Values
MASTERPACT NW/NT

a Maximum sensor plug 250 A

ANSI CB
Model No.
Inst.
Override
(kA RMS)
+/- 10%
NW08N1 a 24
NW08N1 None
NW16N1 None
NW08H1 a 24
NW08H1 None
NW16H1 None
NW20H1 None
NW32H1 None
NW08H2 a 24
NW08H2 None
NW16H2 None
NW20H2 None
NW32H2 None
NW40H2 None
NW50H2 None
NW08H3 a 24
NW08H3 85
NW16H3 85
NW20H3 85
NW32H3 85
NW40H3 85
NW50H3 85
NW08L1 a 24
NW08L1 35
NW08L1F 24
NW16L1 35
NW16L1F 24
NW20L1 35
NW20L1F 24
NW32L1 117
NW40L1 117
NW50L1 117
NW08HA None
NW16HA None
NW20HA None
NW32HA None
NW40HA None
NW50HA None
NW08HF 85
NW16HF 85
NW20HF 85
NW32HF 85
NW40HF 85
NW50HF 85
NW08HC 35
NW16HC 35
NW20HC 35
NW32HC 117
NW40HC 117
NW50HC 117
NT08N1 a 24
NT08N1 None
NT08H1 a 24
NT08H1 None
NT08L1F 10
NT08NA None
UL CB
Model No.
Inst.
Override
(kA RMS)
+/- 10%
NW08N a 24
NW08N 40
NW12N 40
NW16N 40
NW20N 40
NW08H a 24
NW08H 40
NW12H 40
NW16H 40
NW20H 40
NW25H 65
NW30H 65
NW40H 75
NW50H 75
NW60H 75
NW08L a 24
NW08L 35
NW08LF 24
NW12L 35
NW12LF 24
NW16L 35
NW16LF 24
NW20L 65
NW20LF 24
NW25L 65
NW30L 65
NW40L 75
NW50L 75
NW60L 75
NW08HF 40
NW12HF 40
NW16HF 40
NW20HF 40
NW25HF 65
NW30HF 65
NW40HF 75
NW50HF 75
NW60HF 75
NW08HB 35
NW12HB 35
NW16HB 35
NW20HB 65
NW25HB 65
NW30HB 65
NW40HB 75
NW50HB 75
NW60HB 75
NT08N a 24
NT08N 40
NT12N 40
NT16N 40
NT08H a 24
NT08H 40
NT12H 40
NT16H 40
NT08L1 10
NT12L1 10
NT16L1 10
NT08L 10
NT08LF 10
NT12L 10
NT16L 10
NT12LF 10
NT08HF 40
NT12HF 40
IEC CB
Model No.
Inst.
Override
(kA RMS)
+/- 10%
NW08N1 None
NW10N1 None
NW12N1 None
NW16N1 None
NW08H1 None
NW10H1 None
NW12H1 None
NW16H1 None
NW20H1 None
NW25H1 None
NW32H1 None
NW40H1 None
NW50H1 None
NW63H1 None
NW08H2 a 24
NW08H2 85
NW10H2 85
NW16H2 85
NW20H2 85
NW25H2 85
NW32H2 85
NW40H2 85
NW50H2 117
NW63H2 117
NW20H3 65
NW25H3 65
NW32H3 65
NW40H3 65
NW08L1 a 24
NW08L1 35
NW10L1 35
NW12L1 35
NW16L1 35
NW20L1 35
NW08H10 None
NW10H10 None
NW12H10 None
NW16H10 None
NW20H10 None
NW25H10 None
NW32H10 None
NW40H10 None
NW08NA None
NW10NA None
NW16NA None
NW08HA None
NW10HA None
NW12HA None
NW16HA None
NW20HA None
NW25HA None
NW32HA None
NW40HA None
NW50HA None
NW63HA None
NW08HF 85
NW10HF 85
NW12HF 85
NW16HF 85
NW20HF 85
NW25HF 85
NW32HF 85
NW40HF 85
NW08HA10 None
NW10HA10 None
NW12HA10 None
NW16HA10 None
NW20HA10 None
NW25HA10 None
NW32HA10 None
NW40HA10 None
NT08H1 None
NT10H1 None
NT12H1 None
NT16H1 None
NT08L1 10
NT08H10 None
NT10H10 None
NT12H10 None
NT16H10 None
NT08HA None
NT10HA None
NT12HA None
NT16HA None
NT08HA10 None
NT10HA10 None
NT12HA10 None
NT16HA10 None
MICROLOGIC

2.0/3.0/5.0/6.0 A/P/H TRIP UNIT


INSTANTANEOUS OVERRIDE VALUES NO. 613-10
POWERPACT / HORIZON /
SELECT / COMPACT


q Tolerance +/- 15%
UL-IEC CB
Model No.
Inst.
Override
(kA RMS)
+/- 10%
RG 600 57
RG 800 57
RG 1000 57
RG 1200 57
RG 1600 57
RG 2000 57
RG 2500 57
RJ 600 48q
RJ 800 48q
RJ 1000 48q
RJ 1200 48q
RJ 1600 48q
RJ 2000 48q
RJ 2500 48q
RK 600 57
RK 800 57
RK 1000 57
RK 1200 57
RK 1600 57
RK 2000 57
RK 2500 57
RL 600 48q
RL 800 48q
RL 1000 48q
RL 1200 48q
RL 1600 48q
RL 2000 48q
RL 2500 48q
PG 250 24
PG 400 24
PG 600 24
PG 800 24
PG 1000 24
PG 1200 24
PJ 250 7
PJ 400 10
PJ 600 10
PJ 800 10
PJ 1000 10
PJ 1200 10
PK 250 24
PK 400 24
PK 600 24
PK 800 24
PK 1000 24
PK 1200 24
PL 250 7
PL 400 10
PL 600 10
PL 800 10
PL 1000 10
PL 1200 10
IEC CB
Model No.
Inst.
Override
(kA RMS)
+/- 10%
NS 800b N 57
NS 1000b N 57
NS 1250b N 57
NS 1600b N 57
NS 2000 N 57
NS 2500 N 57
NS 3200 N 57
NS 800b H 48q
NS 1000b H 48q
NS 1250b H 48q
NS 1600b H 48q
NS 2000 H 48q
NS 2500 H 48q
NS 3200 H 48q
NS 630b N 24
NS 800 N 24
NS 1000 N 24
NS 1250 N 24
NS 1600 N 24
NS 630b H 24
NS 800 H 24
NS 1000 H 24
NS 1250 H 24
NS 1600 H 24
NS 630b L 24
NS 800 L 24
NS 1000 L 24
NS 1250 L 24
NS 1600 L 24
Note:
Faults at or above instantaneous override value
will be cleared at 25 msec or less.
174
19992004 Schneider Electric All Rights Reserved 11/2004
Masterpact

NT and NW Universal Power Circuit Breakers


Trip CurvesMasterpact NW/NT Low Arc Flash Circuit Breakers
MASTERPACT NW/NT LOW ARC FLASH CIRCUIT BREAKERS
Figure 174: Masterpact NW Low Arc Flash Circuit Breaker: L1F and LF
Figure 175: Masterpact NT Low Arc Flash Circuit Breaker: L1F and LF
MASTERPACT

NW Low Arc Flash Circuit Breaker


CHARACTERISTIC TRIP CURVE NO. 613-15
(L1F AND LF) 8002000 A, 60 Hz
7
0
0
1
5
0
2
0
0
3
0
0
4
0
0
6
0
0
8
0
0
9
0
0 1235789
1
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
1
0
0
0
5
0
0
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
T
I
M
E

I
N

S
E
C
O
N
D
S
FAULT CURRENT (KA)
2 I
n
- NW08
AUTOMATIC RANGE:
NO USER CONFIGURABLE SETTINGS
USER DEFINED RANGE:
FAULT LEVEL MUST
TRIP BREAKER IN
INSTANTANEOUS MODE
(1.2X PICKUP)
Masterpact

NT Low Arc Flash Circuit Breaker


CHARACTERISTIC TRIP CURVE NO. 613-16
(LF) 8001200 A, 60 Hz
7
0
0
1
5
0
2
0
0
3
0
0
4
0
0
6
0
0
8
0
0
9
0
0 123456789
1
0
1
5
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
1
0
0
1
0
0
0
5
0
0
.005
.006
.007
.008
.009
.01
.015
.02
.03
.04
.05
.06
.07
.08
.09
.1
.15
.2
.3
.4
.5
.6
.7
.8
.9
1
T
I
M
E

I
N

S
E
C
O
N
D
S
FAULT CURRENT (KA)
AUTOMATIC RANGE:
NO USER CONFIGURABLE SETTINGS
USER DEFINED RANGE:
FAULT LEVEL MUST
TRIP BREAKER IN
INSTANTANEOUS MODE
(1.2X PICKUP)
2 I
n
- NT08
0613CT0001R9/04 19992004 Schneider Electric All Rights Reserved
Replaces 0613CT0001R10/03
3700 Sixth St SW
Cedar Rapids, IA 52404 USA
1-888-Square D
1-888-778-2733
www.us.SquareD.com
11/2004
Schneider Electric USA

You might also like