Air Handling Units
Air Handling Units
Air Handling Units
I- Arrangements
1-Mixing plenum with Fresh air intake with sand trap louvers 2-Filter G4 3-Cooling Coil 4-Electric Heater 5-Supply Fan
1-Mixing plenum 1-Mixing plenum 2-Cooling Coil 2-Filter G4 3-Cooling Coil 4-Electric Heater 5-Supply Fan 6- Sound attenuator 1-Mixing plenum 2-Electric Heater
Supply Fan
1-Mixing plenum 2-Filter G4 1-Mixing plenum 2-Precooling Coil 3-Air Washer 3-Precooling Coil 4-Heating Coil 5-Air Washer 6-Eliminator 7-Supply Fan 1-Mixing plenum 2-Heating Coil 3-Air Washer
6- Year Round AHU Year- Round Humidity Control Pharmaceutical Clean Single Room Class C
Mixing Box Cooling Coil Empty Module SHF= 0.7 : 0.6 Panel Filter Steam Humidifier G4 Bag Filter Heating / Reheating Coil F9 Supply Fan HEPA Filter H13
1-Mixing plenum with Fresh air intake with sand trap louvers 2-Filter G4 3-Bag Filter F9 4-Cooling Coil 1-Mixing plenum 2-Cooling Coil 3-Reheating Coil 5-Heating / Reheating Coil 6-Empty Module/ Steam Humidifier 7-Supply Fan 8- Built-in HEPA Filter H13 1-Mixing plenum 2-Heating coil 3-Steam Humidifier
7- Year Round AHU Year- Round Humidity Control Pharmaceutical Clean Room Class C with terminal HEPA Filters
Panel Filter G4 Mixing Box Cooling Coil SHF= 0.7 : 0.6 Bag Filter F9 Empty Module Steam Humidifier Heating / Reheating Coil Supply Fan
1-Mixing plenum with Fresh air intake with sand trap louvers 2-Filter G4 3-Bag Filter F9 1-Mixing plenum 2-Cooling Coil 3-Reheating Coil 4-Cooling Coil 5-Heating / Reheating Coil 6-Empty Module/ Steam Humidifier 7-Supply Fan 1-Mixing plenum 2-Heating coil 3-Steam Humidifier
8- Year Round AHU With Return Air and Fresh Air Units Pharmaceutical Clean Room Class C with terminal HEPA Filters
Exhaust Return Fan Return Intake Panel Filter G4
Bag Filter F9
Cooling Coil Heating Coil Empty Module SHF= 0.8 : 0.7 Steam Humidifier
Panel Filter Precooling Coil G4 Fresh Intake SHF= 0.75 : 0.65 Preheating Coil
9- Year Round AHU Year- Round Humidity Control Pharmaceutical Clean Room Class D
Cooling Coil Empty Module Panel Filter SHF= 0.7 : 0.6 Steam Humidifier G4 Heating / Reheating Coil Mixing Box Rigid Bag Filter F9
Supply Fan
1-Mixing plenum with Fresh air intake with sand trap louvers 2-Filter G4 3-Cooling Coil 1-Mixing plenum 2-Cooling Coil 3-Reheating Coil 4-Heating / Reheating Coil 5-Empty Module/ Steam Humidifier 6-Supply Fan 7-Rigid Bag Filter F9 1-Mixing plenum 2-Heating coil 3-Steam Humidifier
10- Year Round All Fresh Outside Air AHU Year- Round Humidity Control Surgical Area in Hospitals
Sand trap louvers Cooling Coil Reheating Coil SHF= 0.5 : 0.45 Panel Filter Empty Module G4 Steam Humidifier Bag Filter Preheating Coil Fresh Intake F9 HEPA Filter H13 Supply Fan
1- Fresh air intake with sand trap louvers 2-Filter G4 3-Bag Filter F9 4-Preheating Coil 5-Cooling Coil 1-Fresh Intake 2-Cooling Coil 3-Reheating Coil 6-Empty Module/ Steam Humidifier 7-Reheating Coil 8-Supply Fan 9-HEPA Filter H13 1-Fresh Intake 2-Preheating coil 3-Steam Humidifier 4-Reheating Coil
11- Year Round All Fresh Outside Air AHU Year- Round Humidity Control Intensive Care in Hospitals
Sand trap louvers Fresh Intake Cooling Coil Reheating Coil SHF= 0.5 : 0.45 Panel Filter Empty Module G4 Steam Humidifier Preheating Coil Supply Fan Rigid Bag Filter F9
1- Fresh air intake with sand trap louvers 2-Filter G4 3-Preheating Coil 4-Cooling Coil 1-Fresh Intake 2-Cooling Coil 3-Reheating Coil 5-Empty Module/ Steam Humidifier 6-Reheating Coil 7-Supply Fan 8-Rigid Bag Filter F9 1-Fresh Intake 2-Preheating coil 3-Steam Humidifier 4-Reheating Coil
1-Return Intake 2- Filter G4 3-DX Cooling Coil 4-Reheating Steam Coil 5-Supply Fan 6-Rigid Bag Filter F9
Panel Filter G4 Return Intake After cooler Supply Fan Rigid Bag Filter F9
1-Return Intake 2- Filter G4 3-Decisscent Wheel 3-After Cooler Coil 5-Supply Fan 6-Rigid Bag Filter F9
13- All Fresh Outside Air Low Dew Point Industrial Dehumidification Applications
Decisscent Wheel Decisscent Wheel
After cooler
1-Fresh Intake 2- Filter G4 3-Decisscent Wheel ( 1 ) 4-After Cooler Coil ( 1 ) 5-Decisscent Wheel ( 2 ) 6-After Cooler Coil ( 2 ) 7-Supply Fan 8-Rigid Bag Filter F9
Panel Filter Eliminator Air Washer ( Winter ) Chilled Water Spray ( Summer )
Supply Fan
1-Mixing plenum 1-Mixing plenum 2-Chilled Water Spray 2-Filter G4 3-Air Washer / Chilled Water Spray 4-Eliminator 5-Supply Fan 1-Mixing plenum 2-Air Washer
Specifications
Main
Additional
Sub-additional
Psychrometry
Production
Electrical
Instrumentation
Control
Civil
Architecture
Chemical
Enviromental
Heat Transfer
Fluid Mech.
Combustion
Power
Mechanical
Mechanical
Sound
Electrical
Electrical
Computer
Computer
Main Specifications
Psychrometric Calculations
Supply Air Rate m3/ hr Outside Air Rate in m3 / hr Cooling Capacity in tons-ref ( or kW ) Heating Capacity in kW Steam Humidifier Capacity in kg / hr Washer Capacity make-up water in lit / min
Cooling Coils
Chilled Water Cooling Coil
1. Air Rate 2. Cooling Capacity 3. SHF 4. Air Inlet Condition 5. Chilled Water Inlet Temperature 6. Chilled Water Temperature Rise
DX Cooling Coil
1. Air Rate 2. Cooling Capacity 3. SHF 4. Minimum Evaporating Temperature
Heating Coils
Hot Water Coil
1. Air Rate 2. Heating Capacity 3. Air Inlet Condition 4. Hot Water Inlet Temperature 5. Hot Water Temperature Drop
Steam Coil
1. Air Rate 2. Heating Capacity 3. Air Inlet Condition 4. Available Steam Pressure
Steam Humidifier
1. Air Rate 2. Heating Capacity 3. Air Inlet Condition 4. Maximum Steam Pressure or Temperature
Air Washer
1. Air Rate 2. Water Consumption 3. Air Inlet Condition 4. Operating Wet bulb 5. Wetting Ratio 6. Humidifying Efficiency
Filters
Coarse Dust Filter ( G ) < 7 m > 0.7 m
Air Rate is recommended Type G1 G2 G3 G4 Rated P Pa 30 50 75 150 Substitution P Pa 150 180 250 250 Rated Efficiency 60 -65 % 65 75 % 75 90 % 90 95 %
Filters
Fine Dust Filter ( F ) < 0.7 m > 0.5 m
Air Rate is recommended Type F5 F6 F7 F8 F9 Rated P Pa 85 100 120 150 250 Substitution P Pa 350 350 350 450 450 Rated Efficiency 50 60 % 60 80 % 80 90 % 90 95 % 95 98 %
Filters
High Efficiency Filter ( HEPA ) ( H < 0.5 m)
Air Rate is recommended Type H10 H11 H12 H13 H14 Rated P Pa 270 300 320 350 350 Substitution P Pa 600 600 600 600 600 Rated Efficiency < 85 % < 95 % < 99.5 % < 99.95 % < 99.995 %
Filters
Ultra Efficiency Filter ( ULPA ) ( U ) < 0.3 m
Air Rate is recommended Type U15 Rated P Pa 400 Substitution P Pa 600 Rated Efficiency 99.9995 %
Filters
Special Filters
Air Rate is recommended 1. Sand Trap Louvers 2. Deodorization ( activated Carbon Panel ) 3. Gaseous Filter 4. Viscous Filter 5. Electro-static Filter 6. Air Washer 7. Ultraviolent Ray Lamps
Filters
P = 10x ( 0.5/d )2.2
Old Class
A++ A+ A B C D
Blower
1. Air Rate 2. External Static Pressure Drop ( Static Pressure Drop of Modules Devices not included ) 3. Minimum Efficiency