SHIPS
NEWBUILDINGS
SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS
PART 6 CHAPTER 4
CONTENTS
Sec. Sec. Sec. Sec. 1 2 3 4
PAGE
General Requirements ................................................................................................................ 5 Accommodation ......................................................................................................................... 7 Machinery Spaces....................................................................................................................... 9 Deck and Cargo Area ............................................................................................................... 12
Comments to the rules may be sent by e-mail to rules@dnv.com For subscription orders or information about subscription terms, please use distribution@dnv.com Comprehensive information about DNV and the Society's services is found at the Web site http://www.dnv.com Det Norske Veritas Computer Typesetting (FM+SGML) by Det Norske Veritas Printed in Norway
If any person suffers loss or damage which is proved to have been caused by any negligent act or omission of Det Norske Veritas, then Det Norske Veritas shall pay compensation to such person for his proved direct loss or damage. However, the compensation shall not exceed an amount equal to ten times the fee charged for the service in question, provided that the maximum compensation shall never exceed USD 2 million. In this provision "Det Norske Veritas" shall mean the Foundation Det Norske Veritas as well as all its subsidiaries, directors, officers, employees, agents and any other acting on behalf of Det Norske Veritas.
CONTENTS
SEC. 1 GENERAL REQUIREMENTS .......................... 5
A. Classification..........................................................................5
A 100 A 200 B 100 C 100 C 200 D 100 Application........................................................................5 Class notations ..................................................................5 Manuals and particulars ....................................................5 Manuals.............................................................................5 Signboards.........................................................................5 General ..............................................................................5
C. Hot Surfaces.......................................................................... 9
C 100 C 200 D 100 D 200 E 100 E 200 F F F F 100 200 300 400 Infrared thermoscanning ...................................................9 Insulation of hot surfaces ..................................................9 Fire detection ..................................................................10 TV monitoring system ....................................................10 General............................................................................10 Arrangement ...................................................................10 General............................................................................10 CO2 total flooding system...............................................10 Water mist system...........................................................10 High expansion foam system ..........................................11 Number and location.......................................................11 General............................................................................11
D. Firefighter's Outfit................................................................5
C. Fire Detection and Alarm System........................................7 D. Dry Powder Extinguishers ...................................................7 E. Hose Reel System ..................................................................7 F. Firefighters Outfit................................................................8
B. Fire Detection Systems....................................................... 12 C. Extinguishing Systems for Cargo Holds and Cargo Pump Rooms ........................................................... 12
C 100 C 200 D D D D 100 200 300 400 Dry cargo holds...............................................................12 Cargo pump rooms..........................................................12 Water extinguishing system............................................12 Foam extinguishing system.............................................12 Dry chemical powder fire-extinguishing system ............13 Fire extinguishing in gas venting arrangement...............13 General............................................................................13 Number and location.......................................................13 General............................................................................14
B. Oil Systems.............................................................................9
B 100 B 200 B 300
201 Vessels with the accommodation built and equipped in accordance with the requirements in Sec.1 and Sec.2 will be given the additional class notation F-A. 202 Vessels with the machinery spaces built and equipped in accordance with the requirements in Sec.1 and Sec.3 will be given the additional class notation F-M. 203 Vessels with the deck and cargo areas built and equipped in accordance with the requirements in Sec.1 and Sec.4 will be given the additional class notation F-C. 204 Vessels built and equipped in accordance with all the requirements of this chapter will be given the additional class notation F-AMC.
B. Documentation
B 100 Manuals and particulars 101 The requirements in Sec.1 to Sec.4 shall be identified in the following documentation: fire pumps and fire main including emergency fire pump and number and positions of hydrants and hoses capacity calculation for fire pumps fixed fire extinguishing arrangement in cargo spaces. Specification and location of equipment and calculation of discharge capacities, if required fire control plan automatic sprinkler, fire alarm and fire detection system for fixed fire detection and alarm systems in accommodation spaces, service spaces, machinery spaces and cargo spaces: specification and location of detectors, alarm devices and call points, and cable routing layout drawing ventilation systems. Layout, dimensions and penetrations of ducts through fire divisions and details of fire dampers arrangement of means of control for closure of openings, stop of ventilation fans and stop of fuel oil pumps in machinery spaces of category A structural fire protection drawings showing method of construction, the fire insulation and draught stops. Details of insulation and specification of materials. Doors in fire divisions protection of ro-ro cargo spaces and cargo spaces intended for carriage of vehicles with ventilation system, fire main, fire extinction and precautions against ignition of flammable vapours, if applicable. In addition to these documents and plans, the following documentation shall be submitted for approval or incorporated into plans required above.
D. Firefighter's Outfit
D 100 General 101 Ships with one of or combinations of the additional class notations F-A, F-M, F-C are to have at least 4 sets of firefighter's outfit as specified in Ch.3 of Fire Safety Systems (FSS) Code as defined in Pt.4 Ch.10. 102 Each of the breathing apparatus is to be provided with cylinders of 1800 litres capacity. The total weight of one apparatus (including cylinder, valves and mask) is not to exceed 12.0 kg. Two spare cylinders are to be provided for each apparatus. All cylinders, apparatus and valves are to be of same type. Apparatus with less capacity and less weight may be accepted if they are deemed to be more suitable for the intended service and more spares are provided. 103 A high-pressure compressor suitable for filling of the cylinders for the breathing apparatus is to be installed. The compressor is to be driven by a separate diesel engine or from the emergency power plant and is to be placed in an easily accessible and safe place onboard. The capacity of the compres-
fire stations placed at a safe distance from each other. The fire stations are to be clearly marked and are to have access from open deck. 105 The arrangement of the fire stations is to be such that all the equipment is easily accessible and ready for immediate use, and such that the equipment has its own place. There are to be arrangements for hanging up protective clothing and other equipment, which should be stored in a suspended position.
104
SECTION 2 ACCOMMODATION
A. General
A 100 Purpose 101 The purpose of the requirements for fire technical subdivision of the accommodation is: to prevent a fire in any other part of the ship from spreading to the accommodation to prevent a fire in the accommodation from spreading to other parts of the accommodation (within the time limits established for the concerned material's fire-technical class) to reduce the use of combustible material to provide rapid detection and safe escape from the cabins and corridors. B 300 Escape ways
301 Dead end corridors are prohibited. Recesses are accepted where their length along the corridor is greater than its width. 302 Spaces exceeding 30 m2 are to be provided with at least two independent escape routes.
B. Fire Integrity
B 100 Restricted use of combustible materials 101 All materials used in bulkheads including doors in these bulkheads, deckhead and lining are to be of non-combustible material as defined in Pt.4 Ch.10. Construction method IC (see SOLAS Ch. II-2/9.2.3.2) is to be used. 102 Curtains and other suspended textile materials are to have resistance to flame as given in Part 7 of the IMO Fire Test Procedures (FTP) Code as defined in Pt.4 Ch.10. 103 Furniture in stairways and corridors is only accepted when it does not obstruct the escape ways and complies with FTP Code, Part 8. 104 Bedding components are to comply with FTP Code, Part 9. B 200 Subdivision
201 On cargo ships, accommodation exceeding 30 m in length or breadth is to have an A-60 class division preferably placed halfway between the bulkheads in length or breadth. Doors in these bulkheads are to be self-closing. 202 Passageways in the accommodation are to be divided by self-closing class B-15 doors at a maximum distance of 20 m from each other. When transverse corridors and longitudinal corridors are connect to each other, class B-15 doors are also to be provided if the total corridor exceeds 20 m. 203 The self-closing passageway doors may to be equipped with approved hold back arrangements, arranged so that they will automatically release the doors when the fire alarm is sounded. 204 Doors from passageways to lounges, day rooms and other public spaces exceeding 30 m2 are to be of self-closing type. 205 All bulkheads and decks separating the accommodation from all machinery spaces, cargo holds and pump rooms are to be of class A-60. 206 All decks in the accommodation spaces (including corridors) are to be of class A-0. 207 All divisional bulkheads, linings, deckheads in accommodation spaces, service spaces and control stations are to be of at least class B-15.
F. Firefighters Outfit
F 100 General 101 The ship is to be provided with firefighter's outfit as described in Sec.1D.
B. Oil Systems
101 The term oil systems means systems for fuel oils, thermal oils, lubricating oils and hydraulic oils. 102 The arrangement of oil tanks, pipelines for oil under pressure, oil processing machinery etc. is to be such that the danger of leakage and ignition is reduced to a minimum. B 200 Separation of risk objects
201 The following installations are to be located in separate rooms: oil fired thermal oil heaters fuel oil purifiers incinerators hydraulic power aggregates with output above 7 kW.
102 One of the escape routes from the engine control room is to be independent of the engine room. A 200 Ventilation
202 The rooms are to be provided with fixed main fire extinguishing system as per F100 and a local extinguishing as per E100. The local fire extinguishing system may be omitted for rooms not having sources of ignition, i.e. combustion installations or electric switchgear. B 300 Shielding of oil piping
201 At least one of the machinery space fans is also to have direct power supply from the emergency power source in order to purge the machinery spaces after a gas extinguishing system has been used. This fan is to be of reversible type. 202 All ventilation and air inlets are to be fitted with dampers or other closing arrangements, which can be secured in a closed position. Indicators showing the open or closed position of the dampers are to be fitted adjacent to the controls. The dampers are to be manoeuvrable from the open deck. The hand lever of dampers is not to be located more than 2 m above the deck.
Guidance note: The aim of these requirements is to isolate a fire to the space in which it originated and to prevent supply of oxygen.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
301 Oil piping with working pressure above 15 bar located in machinery spaces outside the rooms addressed in 200 is to be provided with continuous shielding in order to prevent spray, from possible leakage, reaching sources of ignition.
C. Hot Surfaces
C 100 Infrared thermoscanning 101 All engines, exhaust ducts, steam ducts (if any) and similar equipment, where hot surfaces above 220C may be expected, are to be examined by thermoscanning equipment during normal operation of the equipment. 102 A report is to be issued to plan approval centre and the local surveyor, identifying all items with temperatures above 220C. The thermoscanning should be carried out by certified personnel or in co-operation with a DNV surveyor. The calibration of equipment to be documented and the chosen emissivity factor is to be justified. 103 Corrective actions are to be taken for all surfaces with temperatures above 220C. Such actions may include improved or extensive insulation or improved heat dissipation (cooling ribs and similar). Dedicated ventilation, directed towards the identified hot spots, is normally not accepted. 104 The corrective actions may be verified by manual equipment. C 200 Insulation of hot surfaces
203 Dampers exposed to open decks are to be made of corrosion resistant materials, such as stainless steel and brass. A 300 Centralised fire control station
301 Controls for release of the local extinguishing system, main extinguishing system, closing of fuel valves, fuel pumps and ventilation fans are to be located in a centralised fire control station. One set of the firefighters equipment, as given in Sec.1 D104, should be stored in the centralised station. A 400 Emergency fire pump and fire hoses
401 The emergency fire pump is to have a capacity as required in SOLAS Ch. II-2/10.2.2.4, but not less than 50 m3/ hour. The pump is to provide a minimum pressure of 5.0 bar for the hydrants in the vicinity of machinery spaces with two water jets in operation. 402 Size of fire hoses intended for use in machinery spaces should be chosen based on the number of fire fighters dedicated to this task (38 mm hoses are normally recommended).
201 All insulation is to be made of non-combustible insulation protected by steel sheet cladding. The cladding shall be easy to dismantle and assemble wherever inspection of the protected equipment is necessary.
Guidance note: Some small droplet water mist system may be sensitive with respect to performance in well ventilated spaces. Risk of reduced propulsion or power supply in case of erroneously release of the local extinguishing system should also be taken into consideration.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
208 Procedures describing the philosophy for manual release of system, extent of manual fire fighting, escape and preparation of main fire fighting system is to be stored in the engine control room.
201 Colour TV monitoring system is to cover all engines, heated fuel oil separators, oil fired boilers and all oil fired equipment. Monitors are to be available in a manned control station.
102 Operation of at least one of the extinguishing systems (either the main or the local) is to be independent of power from the main or emergency power source.
Guidance note: Examples of acceptable solutions are gas-extinguishing systems stored in pressure vessels or accumulator based water mist systems.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
E 200
Arrangement 103 Spaces containing main electric propulsion systems are also to be covered by the main extinguishing system. The system may be omitted for bow thruster rooms if these spaces contain no other fire risks; such as combustion machinery, fuel systems and similar equipment. F 200 CO2 total flooding system
201 The local extinguishing system is to be type approved by the Society in accordance with IMO MSC/Circ.913. 202 The system is to be provided with both main and emergency power, if such power is required to operate the system. 203 Separation of the system into sections is to be approved in each separate case. In any case, risk objects less than 3 m apart are to be covered simultaneously. The water supply should be designed to cover at least half of the auxiliary engines or the main engine (alternatively half of the main engines) whichever demands the largest water supply. 204 The nozzles should not be positioned to discharge the extinguishing medium directly into generators or engine air intakes or on to turbo machinery. 205 Distribution valves and other control equipment are to be located outside the protected spaces. 206 Where automatic release of the system is required, fire detectors of more than one type are to be used. A suitable combination of smoke, flame or heat detectors is to be arranged. To avoid erroneously release of the system, discharge of water may be arranged upon signal from two detectors. More than two detectors should be provided for each section. 207 Automatic stop of all or some of the engine room fans upon release of the local extinguishing system is to be considered based on the effect such ventilation may have on the systems performance.
201 A CO2 total flooding system for the machinery spaces category A is to comply with Ch.5 of the FSS Code as defined in Pt.4 Ch.10. 202 The quantity of CO2 gas is to be sufficient for a minimum volume of 40% of the complete engine and boiler room, including casing. 203 CO2 section valves, including stem and seat, are to be made of corrosion resistant materials, such as stainless steel or brass. 204 Slow leak valves are to be provided for the pneumatic release lines, whereas a pressure gauge should be fitted to the manifold. F 300 Water mist system 301 A water fog and or mist system may be accepted as a fixed fire extinguishing system.
Guidance note: Reference is made to IMO MSC/Circ.668 "Guidelines for the approval of water-based fire-extinguishing systems as referred to in
SOLAS 74 for machinery spaces and cargo pump rooms", as amended by IMO MSC/Circ.728.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
302 Arrangement and dimensioning of the system is to be approved in each case, taking into consideration the size of protected space, capacity, location of nozzles, location of pump units and power source. F 400 High expansion foam system 401 For requirements for high expansion foam systems, reference is made to requirements given in Ch.6 of the FSS Code as defined in Pt.4 Ch.10.
Additionally, one approved dry powder extinguisher of at least 25 kg capacity is to be provided in the engine room. In vessels where the engine and boiler rooms are separated, at least one such extinguisher is to be placed in each room. The extinguisher is to be fitted with an approved type of hose with a length of at least 15 m. 102 Separate boiler rooms are to be provided with at least 2 portable dry powder extinguishers for each boiler, each of minimum 12 kg capacity. 103 At least one spare charge of each extinguisher is to be kept onboard.
Guidance note: The above-mentioned locations of the extinguishers is general, and efforts should be made to place these in the vicinity of the installations representing the greatest risk of fire. When installations are placed in separate rooms, the required extinguishers should be placed outside the doors leading into the rooms. See also guidance in A101.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
H. Firefighter's Outfit
H 100 General 101 The ship is to be provided with firefighter's outfits as specified in Sec.1 D.
205 The pumps supplying water for the foam system are, at the required capacity, to have a pressure head sufficient to maintain a pressure of 7,5 bar at the foam monitors. 206 Foam concentrate sufficient for 30 minutes of continuous foam production is to be stored onboard. 207 The monitors are to have a free movement of 45 in the vertical plan and in the horizontal plan they are to be able to point at any part of the deck intended to be protected. The monitors are to be lockable in any position within these ranges. 208 The monitors and their foundations are to be of strong construction and capable of withstanding the loads which they will be subjected to on the open deck. The materials are to be selected with due regard to the corrosive properties of sea water and saline air. 209 At a pressure of 7,5 bar, the monitors are to have a throw of at least 40 metres for both foam and water. Shorter throw may be considered for small deck areas. 210 The two foam monitors on main deck aft part are to be arranged for remote control from the bridge or from another protected area with a good view over the area covered by the monitors. The valves fitted on the open deck for water and foam supply to the monitors are also to be capable of being operated from the same location. The remote control arrangement is to cover the vertical as well as the horizontal movement of the monitors. 211 The foam extinguishing system is to be arranged in such a way that it will be capable of extinguishing burning oil on deck and fighting fires in ruptured tanks. The monitors are to be fitted in such places and at such heights that there will be a free line of throw to the part of the deck which is to be protected. The system is to be arranged so it can be switched over from foam to water by a simple operation in order to be able to wash burning oils over board and cool heated surfaces. 212 In addition to the fixed monitors, mobile foam extinguishing equipment consisting of foam stations is to be provided. 213 Each foam station is to consist of: 1 foam nozzle 3 hoses of 50 mm diameter, each of 15 m length 1 extension spray pipe for spraying foam into the cargo tanks. 214 The equipment specified in 213 is to be kept in clearly visible and marked lockers or boxes on deck placed as close to the hydrants or monitors as practical. The extension spray pipes may be placed outside the lockers or boxes, but in the immediate vicinity of these. The lockers or boxes are to be provided with an inventory list together with brief instructions for operation in the official language of the flag state as well as in English. 215 Where three or more foam stations are required, two of these are to be placed at the poop front. 216 The foam nozzles are to have a water rate capacity of at least 400 to 500 litres per minute at a discharge pressure of 5 bar. The foam nozzle is to be equipped with a stop valve and is to be made of metallic, corrosion resistant material. All movable parts are to be of copper alloy. The foam nozzle couplings and the hose connections onboard are to be completely interchangeable. 217 The hoses are to be of synthetic fibres and coated internally. The hose couplings are to fit all the hydrants onboard and are to be made of copper alloy. 218 The extension spray pipe is to be at least 4 m in length and is to be provided with a coupling connection to the foam nozzle at the lower end and a spray nozzle with a 90 bend. In
order to prevent the foam from submerging below the cargo liquid surface, the spraying appliance is to be so formed that the critical quantity of foam per square unit area for free fall will not be exceeded. The spraying appliance is to be turnable. 219 The following number of foam stations is to be arranged dependent on the size of the ship:
below 10 000 tdw from 10 000 to 100 000 tdw above 100 000 tdw 2 sets 4 sets 6 sets
D 300
301 Dry chemical powder fire-extinguishing systems are to satisfy the requirements as specified in Pt.5 Ch.5 Sec.11. In addition the requirements in 302 to 307 apply. 302 Sufficient dry powder is to be stored on board to provide 60 seconds operation of each system when all attached monitors and hose stations are activated. 303 The dry powder monitors are to have a free movement of 45 in the vertical direction and 360 in the horizontal direction, and are to be lockable in any position within these ranges. 304 The dry powder monitors and their foundations are to be of strong construction and capable of withstanding the loads and environmental conditions to which they will be subjected on the open deck. The materials used for the monitors' individual parts are to be selected with due regard to the corrosive properties of the seawater and saline air. 305 The dry chemical powder fire-extinguishing systems are to be arranged in such a way that they will be capable of extinguishing fires in burning gas from leakages, ruptured pipes etc. in the cargo systems. The monitors are to be fitted in such places and at such height that a free line of throw to the part of the deck that is to be protected is achieved. 306 Each dry powder hose station is to consist of: 1 dry powder trigger nozzle 1 dry powder hose line 1 nitrogen gas container for pneumatic release. 307 The equipment specified in 306 is to be stored in boxes made of steel or other suitable material. The boxes are to be clearly marked and provided with brief instructions for operation of the system in the official language of the flag state as well as in English. D 400 Fire extinguishing in gas venting arrangement
401 Venting masts for cargo tank venting system on liquefied gas carriers are to be provided with a fixed system for extinguishing a fire at the vent outlet.
201 Two portable extinguishers of 12 kg each are to be placed in each cargo pump room or other service room where a leakage of flammable gas or liquids is possible. One of the portable extinguishers is to be located near the entrance door.
202 Rooms for combustion engines (e.g. for the operation of emergency fire pump etc.), hydraulic systems etc. are to be provided with at least one portable extinguisher of 12 kg.
F. Firefighter's Outfit
F 100 General 101 The ship is to have firefighter's outfit as specified in Sec.1 D.