Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Datasheet: Modbus TCP/IP To IEC 61850 Gateway

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

DATASHEET

Modbus TCP/IP to IEC 61850 Gateway


PLX81- MNET- 61850
The ProLinx Modbus TCP/IP to IEC 61850 gateway enables communication between the Intelligent Electronic Devices (IEDs) on an IEC 61850 network and Programmable Logic Controllers (PLCs) or Programmable Automation Controllers (PACs) on a Modbus TCP/IP network. The configuration utility software provided with the gateway uses IED configuration files to import complex IEC 61850 data structures. The utility creates Variable files and Function Block files for import into Unity Pro projects for Quantum or M340 processors. IEC 61850 is the international standard that defines the hardware and communication requirements for all devices within substation automation. The standardized naming conventions imposed by the IEC 61850 standard improves interoperability between systems provided by diverse manufactures or created by multiple system integrators.

Features
Configuration Utility Integrates Tightly with Unity Pro Configuration Archive and Diagnostics Import Configured IED files Modbus TCP/IP Client/Server support Application-specific Variable and Function Block files are automatically generated. Users are not required to develop communication logic or tag structures in their PLC or PAC projects. The gateway configuration file is stored in an industrial SD card. This allows for rapid disaster recovery by moving the SD card from a failed gateway to a replacement gateway. Extensive diagnostics for the gateway and for both Modbus TCP/IP and IEC 61850 networks are available via the configuration utility. All IED data attributes are available for convenient mapping to Modbus registers. Enables multiple Modbus TCP/IP devices or SCADA devices to interface with IEC 61850 devices simultaneously.

Configuration
ProSoft 61850 Configuration Manager, provided with the gateway, is used to develop and manage gateway configuration files, as well as to view communication and network diagnostics. Import CID and SCD files Drag and drop IEC 61850 Data Attributes for Modbus mapping PLC or PAC Tag names are automatically created Print mapped tag list Tag file export (.CSV) Export .XSY (Variable) and .XFM (Function Block) files for use with Unity Pro

Specifications
The gateway is enclosed in a sturdy extruded aluminum case with DIN-rail-mounting. Hardware Software Configuration Storage One (1) Ethernet port for Modbus TCP/IP and IEC 61850 communication ProSoft 61850 Configuration Manager for configuration and diagnostic viewing ProSoft 61850 Tag Monitor for viewing live tag data ProSoft Discovery Service for setting a temporary IP address Configuration settings saved on a removable 1GB Industrial SD Card ProSoft 61850 Configuration Manager saves configuration information to an offline file.

Example Application

Specifications - Modbus TCP/IP


The Modbus TCP/IP driver allows multiple independent, concurrent Ethernet connections. The connections may be Clients, servers, or a combination of both Clients and servers.

Modbus TCP/IP Client


Actively reads data from and writes data to Modbus TCP/IP devices using MBAP messages on Service Port 502 or Encapsulated Modbus RTU messages on other Service Ports Supports up to 10 Client connections with a maximum of 2000 commands to talk to multiple servers

Modbus TCP/IP Server


Accepts incoming connections on Service Port 502 from Clients using Modbus TCP/IP MBAP messages and on Service Port 2000 (or other Service Ports) from Clients using Encapsulated Modbus messages. Supports up to 20 independent, concurrent server connections for any combination of Service Port 502 MBAP messages and Encapsulated Modbus RTU messages on other Service Points 3: Read Holding Registers 16: Preset (Write) Multiple Holding Registers Gateway IP Address PLC Read Start Register (%MW) PLC Write Start Register (%MW) Number of MBAP and MNET servers Gateway Modbus Read Start Address Gateway Modbus Write Start Address Minimum Command Delay Response Timeout Retry Count Command Error Pointer Maximum 2000 Modbus Client commands (one IEC Data Attribute per command) Error codes reported individually for each command High-level status data available from Modbus TCP/IP Client through MNET server (for example PLC or PAC) Each command can be individually enabled or disabled; write-only-on-data-change is available

Modbus Commands Supported (Client and server) Configurable Parameters (Client and server)

Configurable Parameters (Client Only) Command List Status Data

Command List Polling

Specifications IEC 61850 Client


Supports up to 45 IEDs Send commands from the PLC or PAC to the IED using Control Types o Direct-with-Normal-Security o Select Before Operate (SBO)-with-Normal-Security o Direct-with-Enhanced Security o Select Before Operate (SBO)-with-Enhanced-Security

ACSI Basic Conformance SCSMs supported ACSI Model Conformance Reporting GOOSE Control

SCSM: IEC 61850 8.1(MMS) used Buffered Report Control Block (BRCB) Unbuffered Report Control Block (URCB) entryID, DataReflnc Direct-with-Normal-Security SBO-with-Normal-Security Direct-with-Enhanced-Security SBO-with-Enhanced-Security IEC 61850 Logical Nodes, including Logical Nodes for Hydro Power Plants and Logical Nodes for Wind Power Plants MMS Command Delay Status available per node Report and GOOSE status available High-level status data available from Modbus TCP/IP Client through the MNET server (for example PLC or PAC)

Where Automation Connects Global Distribution


ProSoft Technology products are distributed and supported worldwide through a network of over 500 distributors in over 50 countries. Our knowledgeable distributors are familiar with your application needs. For a complete list of distributors, go to our web site at: www.prosoft-technology.com

Logical Nodes

Configurable Parameters Status Data

Global Support
We are there for you All ProSoft Technology products are backed with free technical support. Contact our worldwide Technical Support team directly by phone or email.

Specifications SNTP/NTP Client


The gateway supports a Simple Network Time Protocol (SNTP/NTP) client service that can synchronize the gateways time by periodic update requests to a Coordinated Universal Time (UTC) system. The user can configure the SNTP/NTP server details in ProSoft 61850 Configuration Manager. The resolution of the time is in milliseconds (ms). Configurable Parameters SNTP/NTP server synchronization rate (in minutes) SNTP/NTP server Address

Global Offices
We are where you are ProSoft Technology has regional offices worldwide available to help you with all your industrial application needs. If you need help choosing a ProSoft Technology solution for your particular application check out our contact information under distributor sales on the web site at: www.prosoft-technology.com

Whether your application is large or small, our technical professionals are there to help you choose the right communication solution.

Hardware Specifications
Specification Power Supply Description 24 Vdc nominal 10 Vdc to 32 Vdc power input allowed Positive, Negative, GND Terminals 2.5 mm screwdriver blade Current Load 200 mA maximum @ 24 Vdc 150 mA maximum @ 32 Vdc 450 mA maximum @ 10 Vdc Operating Temperature 32F to 140F (0C to 60C) Storage Temperature -40F to 185F (-40C to 85C) Relative Humidity 5% to 95%, with no condensation Dimensions Standard: Height x Width x Depth 4.72 inches x 1.90 inches x 4.18 inches Ethernet Port (E1) 10/100 Base-T half duplex RJ45 Connector Link and Activity LED indicators Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration LED Indicators ERR, CFG, FLT, PWR Shock and Vibration Shock and Vibration tested to EN 60068 Standard Shipped with Each Unit One - Ethernet straight-through cable (gray) One - J180 screw terminal plug One - ProSoft Solutions DVD One - HRD250 screwdriver One - 1GB Industrial SD Card

Additional Products
ProSoft Technology offers a full complement of hardware and software solutions for a wide variety of industrial communication platforms. For a complete list of products, visit our web site at: www.prosoft-technology.com

Ordering Information
To order this product, please use the following:

Modbus TCP/IP to IEC 61850 Gateway


PLX81- MNET- 61850

Agency Approvals & Certifications


ATEX CSA-CB Safety CE GOST-K, GOST-R ROHS UL/cUL

To place an order, please contact your local ProSoft Technology distributor. For a list of ProSoft Technology distributors near you, go to: www.prosoft-technology.com and select How to Buy from the menu.

Copyright 2013 ProSoft Technology, Inc., all rights reserved. 8/22/2013 Specifications subject to change without notice.