Caldera Columbia CT-25 Manual
Caldera Columbia CT-25 Manual
Caldera Columbia CT-25 Manual
Figure 1
Table Of Contents
PARTS WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SERVICE POLICY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 CLEANING AND FILLING A NEW STEAM BOILER . . . . . . . . . . . . . . . . . . . . . . . . . 11 OPERATING THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . STARTING THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . STOPPING THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BURNER START UP AND TEST INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . SIDEWALL VENTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BOILER ROOM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DESCRIPTION OF BOILER COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MAINTENANCE LOGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TESTING OF BOILER COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . WATER TREATMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 13 13 15 16 19 21 25 31 33 39
RETURN SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 BLOWDOWN SEPARATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 APPENDICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Replacement Parts for CT Series Boilers Panel Box - Inside View - Replacements Parts Warrick Probe Assembly - Replacement Parts Replacement Parts List for CT Series Boilers Gas Train Piping Diagrams Gas Train Components Boiler Wiring Diagram Safety Valve Piping, typical Warrick Dual Function Controls Warrick Series 3K Electrode Fittings Warrick Probe Series 26 Controls Tubular Gage Glasses - Use and Care Danfoss Pressure Controls Typical CT Boiler Piping Layout - Drawing PL-098
IMPORTANT
1.
Read and familiarize yourself with this installation, operation, and maintenance manual before installing, operating, or servicing your boiler. All cover plates, enclosures, and safety devices must be installed at all times except while performing maintenance and service. Only trained your boiler. service technicians should do any work on
2.
3.
4.
All state and local codes take precedence over any recommendations given in this manual.
5.
NOTE: The CT Boiler is not designed for continuous, nonstop operation. Normal burner cycling is required. Continuous operation will eventually damage the boiler, voiding the warranty. Wrapping the CT Boiler with insulation will cause the boiler to overheat, voiding the warranty.
6.
-1-
-2-
SERVICE POLICY
Anything mechanical will inevitably need servicing. Steam and hot water boilers are routinely serviced by the installer or another boiler maintenance company. Occasionally the service technician may be unable to determine the cause of the problem. In this situation, the dealer or service organization should contact the selling distributor for help. Should the problem persist, the distributor will contact the sales representative for assistance. Depending on the extent of the problem, the representative may request technical assistance from the factory. If the problem cannot be resolved by the representative, he should contact the Technical Service/Engineering Department at the factory. The sales representative will need the following information. We must insist that this information be available to assure prompt service. Boiler Model and Size (HP) ______________________________________________________ Boiler Serial Number ___________________________________________________________ Boiler National Board Number __________________________________________________ Date Installed _________________________________________________________________ Burner Type and Model ________________________________________________________ Installers Name ____________________________________ Phone (_____) ______________ Address ______________________________________________________________________ Distributors Name __________________________________Phone (_____) ______________ Address ______________________________________________________________________ Sales Representative ________________________________ Phone (_____) ______________ Address ______________________________________________________________________ Specific Problem - Detailed
-3-
INSTALLATION
The Columbia Model CT Steam Boiler is furnished completely piped, wired, and assembled. It has been factory tested and is ready for operation. This steam boiler is designed to operate using No. 2 fuel oil and/or natural, manufactured, or liquid propane (LP) gas, and to be powered by standard AC electrical service. BEFORE BEGINNING INSTALLATION, CAREFULLY STUDY THESE INSTRUCTIONS AND ALL CHARTS, DRAWINGS, AND DIAGRAMS SHIPPED WITH THE BOILER. Installation must follow all state and local code requirements. The electrical installation must be in accordance with the National Electrical Code. CLEARANCES The boiler is to be placed on noncombustible flooring, in an approved boiler room, with the following clearances to combustible materials. Underwriters Laboratories (UL) approved clearances: Side: Top: Front: Chimney connector: 18 18 48 18 inches inches inches inches
Reduced clearance installation must follow the recommendations as outlined in NFPA-31. Reduced clearance installations should be avoided if possible, as this will make it much harder for qualified technicians to perform routine maintenance in and around your boiler. Clearances to noncombustible materials shall be in accordance with state and local codes. In the absence of local codes, it is recommended that the above stated clearances be followed. FLUE The CT series boilers are pressure fired steam boilers, and need only to be properly vented. Consult the factory for proper venting of the boiler for any unusual conditions that may exist at the job-site. For boilers vented into a chimney, be certain the chimney is clean, and clear of obstructions. Connect the boiler flue outlet to the chimney using galvanized flue pipe. Refer to the following list for proper size of the flue pipe. DO NOT REDUCE THE FLUE OR CHIMNEY SIZE TO LESS THAN THE OUTLET SIZE ON THE BOILER. Consult the factory if the boiler must be vented into a chimney that is smaller than the boiler outlet size. The flue pipe should be pitched upward at least 1/4" per foot of run. Use only elbows and straight sections. Tees
FM-148 COLUMBIA BOILER COMPANY, REV 6-06
-4-
may be used in straight sections with a barometric draft regulator. Tees, however, should not be used for a ninety-degree turn. Each joint should be securely fastened with sheet metal screws. The flue pipe must not be inserted beyond the inside wall of the chimney. Columbia Boiler approves the use of galvanized B type vent that is suitable for 550F stack temperature as proper and safe for this application, but any and all codes take precedence. PROPER FLUE PIPE SIZE 6" 6" 8" 8" 10" 12" 12"
BOILER CT-6 CT-10 CT-15 CT-20 CT-25 CT-35 CT-50 GAS SUPPLY PIPING
Contact your local gas company to ensure that adequate gas service is available, and to review applicable installation codes for your area. The minimum gas supply pressure required by the burner is five inches water column for the CT-6 and CT-10, and seven inches water column for the CT-15, CT-20, CT-25, CT-35 and CT-50. The maximum gas supply pressure to the burner is fourteen inches water column. Gas pressure greater than fourteen inches water column will require an additional gas regulator to prevent damage to the primary gas regulator. Gas pressure below the minimum will cause combustion efficiency problems and should be avoided if possible. Low gas pressure may also prevent the boiler from obtaining the desired input rate, which will cause the boiler to be unable to produce the desired output. Consult the factory if your gas supply pressure is not in the recommended range. Use the following tables to determine the size of the main gas line required for the boiler that is being installed. First determine the required input volume of gas needed at the gas manifold, then determine the correct pipe size for the length of run needed.
-5-
REQUIRED INPUT - CUBIC FEET OF GAS PER HOUR GAS TYPE NATURAL PROPANE CT-6 252 101 CT-10 399 160 CT-15 630 252 CT-20 840 336 CT-25 1050 420 CT-35 1470 735 CT-50 2100 840
CAPACITY OF PIPE - CUBIC FEET OF GAS PER HOUR AT 0.2" W.C. PRESSURE DROP Equivalent Length (ft) 10 20 30 40 50 60 80 100 150 200 Fitting Std. Tee Std. Elbow 1" 425 300 250 210 190 180 150 135 110 75 1-1/4" 725 520 425 360 325 300 260 230 190 165 1-1/2" 1170 800 690 560 500 480 410 370 300 260 2" 2360 1700 1400 1200 1100 1000 850 750 600 540 2-1/2" 4300 3000 2500 2100 1900 1800 1550 1375 1100 950 3" 6250 4500 3750 3200 2850 2300 2000 1680 1200 1000 4" 12800 9300 7500 6400 5800 4800 4200 3500 2750 2000
Equivalent Lengths of Standard Pipe in Feet for Listed Fittings 5.5 2.7 7.5 3.7 9.0 4.5 12.0 5.5 13.5 6.1 15 8 20 11
Vent lines, if required, are to be run outside the building, stopping clear of windows or fresh air intakes. The vent should terminate in a way that will not allow the possibility of water, dirt, insects, animals, and other matter from entering and clogging the vent pipe. Gas lines should be tested for leaks using a soap solution. Your gas company may wish to witness this test. Do not exceed the maximum pressures allowed by the valve train. Additional gas piping information is included in the burner section of this manual.
-6-
OIL SUPPLY PIPING Consult the burner section of this manual for oil line type and sizing requirements for proper operation. The size of oil lines is extremely important for proper operation. Suction vacuums must be held to acceptable limits. All oil feed lines must be air tight. Use as few fittings as possible when assembling the oil lines. The slightest air leak, usually caused by loose fittings or bad gaskets, can cause poor starts, smoky starts, sooting of burner parts, inefficient operation, and a dangerous combustion condition. A vacuum test should be done on all installation to ensure that all fittings are tight and the oil lines are of proper size. Always use flare fittings instead of compression fittings on oil service lines. Compression fittings allow more of a chance for air to be introduced into the oil supply. WARNING: TEFLON TAPE SHOULD NEVER BE USED WITH ANY OIL LINE CONNECTIONS. THE USE OF TEFLON TAPE ON BURNER COMPONENTS OR OIL SERVICE LINES WILL VOID MOST BURNER WARRANTIES.
For additional information consult the burner section of this manual. ELECTRICAL SUPPLY Connect the electric supply to the boiler and condensate return system as shown in the wiring diagrams. Separate electrical services and disconnects must be provided for both the boiler and the return system. If both 110 volts AC and 220 volts AC are needed, separate disconnects should be provided. The wiring must be installed in accordance with the National Electrical Code and any other state and local codes. All disconnects should provide overload protection to prevent injury to personnel or damage to equipment. Be sure that the incoming voltages match that of the appliances before applying power. Make a special point of checking the internal wiring of the blower motor as most motors can be wired for either 110 or 220 volts. FEEDWATER Connect the feedwater supply from the condensate return tank to the boiler inlet feedwater connection. See Figure 2 and Piping Layout PL-098 in Appendix. Columbia Boiler Company provides one spring type check valve in the feedwater piping. An additional swing type check valve should be installed in the feed line as close to the pump as possible. These valves should be piped in the horizontal position. Do not use the pump as a piping support. It is very important that the piping be independently supported at the pump.
-7-
FEEDWATER PIPING
Figure 2
Do not fill the boiler until the installation is complete and you are ready to fire the burner. Firing the burner will then boil the water which will drive off the dissolved oxygen in the water and help maintain the proper boiler water chemical balance. See the WATER TREATMENT section for important information regarding the proper chemical water treatment required to insure satisfactory service life of the boiler. On long horizontal runs of piping, it is best to maintain the piping as level as possible. Avoid high spots that will collect air and lead to erratic pumping. Install a check valve to prevent the boiler water from back feeding into the service water supply.
STEAM PIPING
Figure 3
FM-148 COLUMBIA BOILER COMPANY, REV 6-06
-8-
STEAM OUTLET Connect the field steam piping to the outlet on top of boiler. See Figure 3. If a main steam manifold is used, it should be pitched 1/4" per foot of horizontal run so that condensate will run into a steam trap, rather than back into the boiler. All steam supplies should be taken off the top of the manifold to prevent condensate from entering the process machines. SAFETY VALVE Safety valves should be piped so that they cannot discharge on people or damage property. The discharge piping must be supported so that the weight of the piping is not transmitted to the safety valve body. Refer to drawing PL-049 in the Appendix for an example of typical safety valve piping. the weight supported by the valve outlet should not exceed the weight of a drip pan elbow. Use only Schedule 40 pipe for discharge piping. DO NOT USE Schedule 80, extra strong, or double extra strong discharge pipe or connections. Installations requiring long discharge piping should not be connected directly to the safety valve. During installation, be sure that pipe compound or tape is used only on external threads and that the inlet of the valve is free of any foreign material. DO NOT USE A PIPE WRENCH when working on the safety valve. use only the proper type and size wrench. WARNING: NEVER REDUCE THE INLET OR OUTLET SIZE OF THE SAFETY VALVE; NEVER HANG PIPING ON THE SAFETY VALVE; NEVER INSTALL VALVES(S) IN THE SAFETY VALVE PIPING; NEVER PLUG THE BONNET VENT. SERIOUS DAMAGE OR INJURY COULD RESULT FROM THE FAILURE OF THE SAFETY VALVE.
BLOWDOWN PIPING Connect the boiler, the Warrick Low Water cut Off, and sight glass blowdown lines in accordance with local code requirements. See Figure 4. the blowdown must be piped to a safe place of discharge to prevent injury to personnel or property damage. It is recommended that a blowdown tank be used to safely discharge the blowdown into the sewers. Check state and local codes concerning the maximum allowable temperature for blowdown entering public sewer systems. All valves, piping, and forged fittings used n the blow-down lines shall be, of suitable rating, and in accordance with ASME Code B31-Power Piping. All pipe nipples used shall be Schedule 80 pipe. WARNING: NEVER REDUCE THE VENT SIZE OF THE BLOWDOWN TANK. To properly and safely blow down the boiler, the vent must be piped full size for the entire length, and must terminate at a safe place of discharge per local codes.
FM-148 COLUMBIA BOILER COMPANY, REV 6-06
-9-
Figure 4
BLOWDOWN PIPING
- 10 -
- 11 -
- 12 -
um gauge, 0-300 PSI pressure gauge, carbon dioxide or oxygen analyzer, carbon monoxide tester, smoke gun, and stack thermometer. STARTING THE BOILER WARNING: NEVER OPERATE A BOILER WITHOUT BEING SURE IT IS FILLED WITH WATER AND THAT PROPER WATER TREATMENT CHEMICALS HAVE BEEN ADDED.
Open the feedwater valve and turn on the main disconnect for the condensate pump. the pump should come on and fill the boiler to its normal operating level. Turn the boiler disconnect switch to the ON position. NOTE: The burner will not operate when the boiler has reached its normal water level, until the reset button on the secondary, probe type, low water cut-off is pushed.
Push the RESET button on the Control panel Cover. The burner should start. NOTE: Combustion efficiency must be checked at this time. See the burner manufacturers instructions for correct settings and more detailed information.
Follow the adjustment procedures outlines in the burner section of this manual to set up the burner for proper operation. NOTE: New CT boilers will normally expel a vapor from joints and openings in the jacket. This is a temporary condition, caused by moisture evaporating out of the refractory insulation behind the jacket, and will eventually disappear.
STOPPING THE BOILER To stop the boiler turn the main disconnect to the OFF position.
- 13 -
GAS BURNERS BOILER MODEL CT-6 CT-10 CT-15 CT-20 CT-25 CT-35 CT-50 BURNER POWER FLAME JR15A-10 POWER FLAME JR15A-10 POWER FLAME JR15A-10 POWER FLAME JR30A-12 POWER FLAME JR30A-12 POWER FLAME JR50A-15 POWER FLAME JR50A-15
NATURAL GAS ORIFICE SIZE AND ORIFICE PRESSURE (INCHES WATER OCLUMN) LIQUID PROPANE GAS ORIFICE SIZE AND ORIFICE PRESSURE (INCHES WATER COLUMN)
5/16 (.313) / 3.5" 3/8 (.375) / 3.5" 15/32 (.469) / 3.5" 9/16 (.563) / 3.5" 23/32 (.719) / 3.5" 11/16 (.688) / 3.5" None x 3.5"
D(.242) / 3.5" 19/64 (.297) / 3.5" T(.358) / 3.5" 15/32 (.469) / 3.5" 1/2 (.500) / 3.5" 19/32 (.594) / 3.5" 25/32 x 3.5"
INLET GAS PRESSURE Inlet gas pressure to the main gas valve should be between seven and fourteen inches water column. If the inlet gas pressure exceeds fourteen inches water column, the pilot regulator and main gas regulator will lock up and become inoperative, and damage may occur. Inlet gas pressure above fourteen inches water column will require an additional pressure reducing valve. If the inlet gas pressure is below seven inches water column the burner may not be capable of the rated boiler output. If the gas pressure is below seven inches water column contact your local gas company. If the local gas company is unable to help, contact the factory for assistance.
- 14 -
- 15 -
BOILER MODEL CT-6 CT-10 CT-15 CT-20 CT-25 CT-35 CT-50 Vent Caps
Use only UL listed vent caps for the combustion vent termination and the combustion air intake. The following vent cap model is shipped with your boiler when the direct vent option kit is ordered. Heat-Fab Incorporated 38 Haywood Street Greenfield, MA 01301 (800) 772-2356
- 16 -
Installation The Columbia Model CT Direct Vent Series Steam Boiler is furnished completely piped, wired, and assembled. It has been test fired at the factory and is ready for installation. This steam boiler is designed to operate with natural gas, and is suitable for standard AC electrical service. The CT Series requires the following minimum clearances to combustible material: top, sides, and rear - 18", front - 36", flue vent duct - 18". Location The CT boiler must be mounted on a level non-combustible floor, or the floor must be protected in accordance with the requirements of accepted building code practices. In the absence of local codes, it is suggested that NFPA-31 section 4-4.1.5 be followed. Flue Vent Duct For direct venting, galvanized smoke pipe is acceptable, but local codes take precedence. The maximum length of flue vent duct allowed is 40 feet, and at no time can the diameter of the flue vent duct be less than the diameter of the smoke outlet of the boiler, see Table on the previous page for size. The flue pipe should be sloped upward 1/4" per horizontal foot of run. All sections of flue pipe should be joined and fastened securely with sheet metal screws. The maximum number of 90 elbows in the flue vent duct is four. A barometric swing type draft regulator may be installed in the flue vent duct if desired, but is not necessary. The vent must end with the UL listed vent cap that was shipped with your boiler. the vent cap can be installed either horizontally (Figure 5-A below) or vertically with a tee (Figure 5-B below). It is suggested that a screen or vent pipe plug be inserted into the bottom of the tee to prevent animals and other matter from entering.
Figure 5
- 17 -
All through the wall connections must adhere to safety standards set forth by standard building practices and local codes. In the absence of local codes, UL listed wall thimbles and through the wall connectors should be used. The combustion vent cap must extend a minimum of four feet from the building, and must be located as far from the combustion air intake as possible. The combustion vent must terminate a minimum of seven feet above the ground where pedestrian traffic can be expected. It shall also terminate at least three feet above any forced air inlet within ten feet, and shall terminate at least four feet below or four feet horizontally from, or one foot above and two feet horizontally from, any door, window, or gravity air inlet into any building as provided in the National Fuel Gas Code NFPA 54. See Figure 6. Both the Combustion Flue Vent and the combustion Air Intake must be in the same wall.
Figure 6
Combustion Air Intake The air for combustion must be ducted directly to the burner intake and must terminate outside with the applicable Intake Air cap listed in the Table on page 15. The vent cap can be installed either horizontally or vertically in conjunction with a tee. It is suggested that a screen or vent pipe plug be inserted into the bottom of the tee to prevent animals and other matter from entering. The maximum length of combustion air intake duct shall be 40 feet. The combustion air intake shall be full size for the complete run and shall not have more than four 90 elbows. The combustion air intake cap must be at least one foot off the ground in an area that is always free from obstructions. The Combustion Air Intake must be in the same wall as the Combustion Vent.
Important Note: Surface discoloration of the building may occur due to improper boiler/burner adjustment and maintenance. Columbia Boiler Company will not accept any liability for such discoloration.
FM-148 COLUMBIA BOILER COMPANY, REV 6-06
- 18 -
BOILER ROOM
Lighting The boiler room should be well lighted and should have a source of emergency lighting. If a flashlight is used for this purpose, it should be maintained in usable condition, and it should not be removed from the boiler room. Care should be taken to prevent bright, direct sunlight from shining on the burner, as the flame sensing controls may receive a false flame signal. Water Supply and Drain Connections Convenient water supply connections for flushing the boiler and cleaning the boiler room floor should be installed. Unobstructed floor drains, properly located in the boiler room floor, will aid in the proper cleaning of the boiler room. Make-up Air The burner must have adequate air supply, which must be kept clear at all times. Do not run exhaust fans in the immediate proximity of the boiler room, as they will cause a reversal of draft at the burner. Ensure that sufficient make-up air is available, even if that requires a window to the outside to be left open. This air is necessary to insure complete combustion, a clean fire, and to prevent nuisance shutdowns due to excessively dirty burner parts. Air from the outside may be provided through ducts, fixed louvers, or motorized louvers. WARNING: WITHOUT SUFFICIENT MAKE-UP AIR, THE BOILER WILL NOT OPERATE PROPERLY, AND BURNER COMPONENT DAMAGE COULD OCCUR.
To calculate the required fresh air opening to the outside, allow 21 square inches for every boiler horsepower. For example a 10-horsepower boiler would require two hundred and ten square inches of free opening. This is equal to a 15" x 15" square hole, or a 18" diameter round hole of free, unrestricted area. If louvers or screens are used, contact the manufacturer for percentages (typically around 40%) that must be added to allow for restriction. The following table can be used to size the amount of free area needed for the various sizes of CT boilers. A point to remember for round openings - two 10" round openings DO NOT equal one 20" round opening. Four 10" round openings are needed to obtain the same amount of free area.
Columbia Boiler Company will not be held liable for damage to the boiler or burner components caused by insufficient burner make up air.
FM-148 COLUMBIA BOILER COMPANY, REV 6-06
- 19 -
OPENING MIN. SQUARE INCHES 126 210 315 420 525 735 1050
6 9.5 15 20 25 35 50 Housekeeping
12 X 12 15 X 15 18 X 18 2 X 21 23 X 23 28 X 28 33 X 33
14 18 20 24 26 32 38
Provide adequate space around the boiler for inspection and service. Do not allow the boiler room to become a storage room. Fire protection apparatus, and fire prevention procedures for boiler room areas shall conform to the recommendations of NFPA and all local codes. WARNING: DO NOT STORE OR USE GASOLINE OR ANY OTHER FLAMMABLE LIQUIDS AND VAPORS IN THE VICINITY OF THE BOILER OR BOILER ROOM.
- 20 -
- 21 -
pump motor switches of the Warrick Series DF Low Water cut Off and Pump Control. A Motor Starter also provides electrical overload protection for the feedwater pump motor. A Motor Contactor is provided as standard equipment on the CT-6 thru CT-25 Boilers, and a Motor Starter is provided as standard equipment on the CT-35 and CT-50 Boilers. Warrick Series 26 Probe Type Low Water Cut-Off The manual reset probe is used as a supplementary safety device for protecting the boiler against damage from low water. It is designed to operate if the Series DF low water cutoff should fail to operate for any reason. This unit is set to operate at a water level in the boiler lower than that of the Warrick Series DF. See drawing CT-415 in the appendix for installation of probe rod. This unit consists of a circuit board design with one normally open (N.O.) non-powered contact. When reset, it completes a circuit between the probe rod and the boiler drum, through the water in the boiler. If the water level falls below the probe rod, the circuit is broken causing the contact to open, breaking the circuit to the burner and energizing an alarm circuit (if equipped). NOTE: This relay must be reset after a low water condition has been corrected or after any interruption in the electrical supply.
- 22 -
Safety Limit Pressure Control The Safety Limit operates essentially the same as the pressure control described previously except this limit is equipped with a reset button and does not have a differential. The purpose of the Safety Limit is to shut down the burner if the operating pressure control becomes inoperable and steam pressure continues to climb. The burner will not start until the situation is corrected and the reset button is pushed. The high limit of the Safety limit must be set above the operating pressure control setting. Adjust the main scale set point about 20 PSI higher than the operating pressure control by turning the main scale adjusting screw on top of the case until the main scale setting indicator is at the desired pressure. There are a number of pressure controls that may be used interchangeably. Please see additional information in the manual appendices. Safety Valve Safety valves shall be piped so that any discharge cannot cause injury to people or damage to property. The discharge piping must be supported so that the weight of the piping is not transmitted to the safety valve body. The weight supported by the valve outlet should not exceed that of a drip pan elbow. Installations requiring long discharge piping should not be connected directly to the safety valve. Refer to Drawing PL-049 in the Appendix. In order to achieve the topmost performance and maximum safety valve life, maintain a proper operating gap between the set pressure of the safety valve and the maximum operating pressure of the boiler. The minimum recommended operating gap for this valve is 10%, but at no time less than 7 PSI. Under no circumstances should this gap be less than 7 PSI or seat leakage can occur. Failure to maintain this operating gap can result in an accumulation of deposits on the seating surface that may impede proper operation of the safety valve. If the valve discharges on its own, contact a qualified service technician to determine the cause. This may be an indication of equipment or system malfunction. Gauge Glass Protector The gauge glass protector is provided to guard against personnel injury and component damage in the event of a breakage of the sight glass. The gauge glass protector must be properly installed prior to operation of the boiler.
- 23 -
- 24 -
MAINTENANCE
RECORD KEEPING All manufacturers literature, spare parts lists, operating and maintenance procedures should be maintained in the boiler room at all times. A log book should also be provided to record maintenance work, inspections, and other performance test results. General Clean the boiler and heating surfaces whenever required. The frequency of the cleaning required to maintain the boiler at peak efficiency will be determined only by frequent inspections. It cannot be predicted. Your operating conditions might be different from your neighbors. When in doubt - check it out. WARNING: DISCONNECT ALL INCOMING ELECTRICAL POWER BEFORE SERVICING THE BOILER. USE EXTREME CAUTION AROUND BOILER PIPING AND THE WARRICK SERIES DF LOW WATER CUT OFF SINCE THEY MAY BE VERY HOT.
The life of your boiler will be determined by the level of care given it by those who are responsible for maintenance. A log of the following items should be maintained in the boiler room at all times. Daily Boiler Check & Maintenance List 1. Water Level Controls and Cut Offs are operating normally. 2. Instrument and equipment settings are normal. 3. Gauge glass is clean and protector is installed. If leaks are detected, replace glass, gaskets, and brass washers immediately. When replacing gauge glass use only 5/8" O.D. x 10-1/4" long Pyrex red line, high pressure, high temperature, glass tubing, with fire polished ends. See gauge glass maintenance section for proper method when installing this gauge glass. 4. Boiler water at proper operating level. 5. Blow down boiler as instructed under BLOWDOWN. 6. Blow down probe type low water cutoff. Weekly Boiler check & Maintenance List 1. Check flame failure detection system. A. Gas boilers: Close fuel supply to pilot and main gas and check shut down timing. B. Oil boilers: Remove cad cell leads and check shut down timing. 2. Check fuel valves; Open limit switch and make aural and visual check. 3. check ignition system flame signal.
- 25 -
Monthly Boiler Check & Maintenance List 1. 2. 3. 4. 5. Test all fan interlocks. Check main burner safety shut off valve(s) for operational closure. Oil fired; check fuel pressure interlocks when provided. Gas fired; check high and low fuel pressure switches. Flue or stack dampers; make visual inspection for proper operation.
Semiannual Boiler Check & Maintenance List 1. Inspect burner components; Refer to burner manufacturers instructions. 2. Check the flame failure system components; Refer to the burner section of this manual. 3. Check piping and wiring of all interlocks and shut off valves. 4. Internal boiler plate inspection. Remove hand-hole assemblies; use new gaskets when replacing covers. Annual Boiler Check & Maintenance List 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Check operating Pressuretrol. Check high limit Pressuretrol. Test safety valves. Remove the Warrick Series DF Low Water Cut Off and clean inside casting. Oil fired - clean/replace oil filters or strainers if equipped. Oil fired - replace ignition electrodes if equipped. Gas pilots - conduct pilot turndown test. Gas fired - replace ignition and flame rods. Gas fired - check drip leg/strainer. Oil fired - check for refractory hold in. Check Automatic Change Over Control if equipped. Gas fired - perform valve leakage test.
- 26 -
Gauge Glass The water gauge glass must be kept clean. Dirt on or in the glass may be mistaken for the water level. Do not allow steam or water to leak from the water glass, as this may effect the accuracy of the level indication. Leaking of the gauge glass will also reduce the wall thickness of the glass to the point where it may explode. WARNING: DO NOT OPERATE THE BOILER WITHOUT THE GAUGE GLASS PROTECTOR INSTALLED. NEVER ATTEMPT TO WORK ON THE GAUGE GLASS WHILE THE BOILER IS UNDER PRESSURE. ALWAYS CLOSE GAUGE VALVES PRIOR TO TIGHTENING GASKETS ON WATER LEVEL GAUGE GLASS. SERIOUS INJURY COULD RESULT.
Gauge Glass Replacement Instructions: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Make absolutely certain that the new water level gauge glass is 5/8" o.d. x 101/4" long Pyrex red line, high pressure, high temperature glass tubing with fire polished ends. Close gauge glass valves. Remove gauge glass protector. Remove the old glass, gaskets, brass washers, and brass nuts. Be sure threads on the gauge valves are clean. Install brass nuts, brass washers, and gaskets on each end of the gauge glass. Insert glass tub into top gauge valve and lower the glass tube into the bottom gauge valve which contains a seat. Then raise glass 1/16". Do not allow glass to rest directly n the valve. Hand tighten the lower glass nut and then the upper nut. While tightening these nuts, be sure to keep the red line opposite the viewing side. With a wrench, snug up the bottom nut and then the top nut. Replace gauge glass protector. Open gauge glass valves fully. Failure to completely open the gauge glass valves renders the ball check safety feature inoperative. Without pressure on boiler and with gauge valves closed, tighten gaskets again after 1 day of operation.
Blowdown Blowing down the boiler is done to remove excess total dissolved solids. The actual amount of blowdown should be determined through boiler water analysis, done by a water treatment specialist. Until an analysis of your boiler water is made, the following guidelines should be used. Blow down should be done in the evening after firing equipment has been shut down for approximately 20 minutes and at a pressure between 20 and 40 psi. some pressure must be left on the boiler for proper blow down. Important: Boiler water must be settled for proper blowdown.
- 27 -
Blowdown Instructions To blow down the boiler, open the slow opening (Y type) blowdown valve first. Open boiler blowdown ball valve for 30 seconds then close. Use this same procedure with the low water cut off blowdown ball valve. then go back to the boiler blowdown valve, open and close the valve, very fast, two more times. Repeat this procedure with the low water cut off valve. This will rid the boiler of most precipitated sediment. DO NOT EMPTY THE BOILER OF ALL ITS WATER. The Warrick Series DF Low Water cut Off & Pump Control should be blown down at least once each day when the boiler is in operation. This is essential to flush accumulation of sediment from the float chamber. Failure to do so will result in the failure of the control to shut off the burner on low water. During the blowdown operation, check to see that all of the control probes are operating properly. To check operation of the probes, open the blowdown valve while the burner is in operation. When the water level drops, the alarm circuit should close and sound the alarm (if alarm is installed) and the burner should stop firing. Hand Hole Gasket Replacement Part number 480210 (fits all models) Remove the old gasket and thoroughly clean the basket surfaces inside the boiler and on the hand hole surfaces. A thin wire or a piece of string tied to the hand hole casting will help prevent losing the casting in the boiler when removing or installing gaskets. Place the new gasket on the hand hole making sure that it fits evenly all the way around. The use of adhesive on the plate gasket is recommended in order to hold the gasket in place while installing the assembly in the boiler.
Figure 7
FM-148 COLUMBIA BOILER COMPANY, REV 6-06
- 28 -
Install the plate assembly in the boiler, evenly spaced as possible. Set the yoke over the bolt, install the nut and make it hand tight to keep the plate from moving. Using the correct size socket wrench, tighten the nut one quarter turn. See Figure 7. If the gasket leaks while the pressure is being brought up on the boiler, tighten the nut only enough to stop leaking. See Figure 8. Check the gaskets for leakage for the next three days after installation and if leakage is detected tighten only enough to stop it. WARNING: EXCESSIVE TIGHTENING WILL FLATTEN OUT THE GASKETS TO A POINT WHERE THEY WILL NO LONGER BE ABLE TO SEAL. DO NOT TIGHTEN MORE THAN IS REQUIRED TO SEAL
Figure 8
Cleaning the Flue Passages Under normal operating conditions the flue passages do not need to be cleaned. If poor combustion has been experienced and soot has built up on the flue passages they can be cleaned following this procedure. Before cleaning have your boiler technician check the stack temperature and combustion efficiency to make sure that cleaning is necessary. Do not disassemble the jacket top ring without first obtaining a millboard top gasket. This gasket can become brittle over time and will be impossible to reinstall after removing. This can cause combustion gasses to leak and can cause a dangerous situation. If your boiler was built after February 1991 you will also need an upper hand hole gasket, part number 480210.
- 29 -
Millboard top gasket part numbers: CT-6 332200 CT-25 332230 CT-10 332210 CT-35 332232 CT-15 332220 CT-50 332233 CT-20 332225
Disassembly, Cleaning and Assembly Instructions 1. Obtain a top refractory millboard ring from your local supplier before attempting to look inside the flue passages. 2. Take off the top jacket by removing the three screws that connect it to itself and the four screws that connect it to the top cover small mounting angles. Set the top jacket and the fiberglass insulation strip found behind it to the side. 3. Scribe or mark a line on the outer jacket and top cover to aid in aligning the top cover during reassembly. This is important to assure that the screw holes will line up later. 4. Remove the sheet metal screws around the outside of the top cover and save for reassembly. 5. Remove the upper hand hole assembly if your boiler was manufactured after February 1991. 6. Lift the top and place as far up and out of the way as possible. The piping and electrical connections do not have to be disconnected but the top ring will not come all the way off. 7. Remove the millboard refractory ring. 8. The flue passages should now be visible and can be cleaned as desired. It is suggested that the soot be brushed down to the bottom and vacuumed out by pushing a long hose or pipe down between the baffles. 9. Clean the baffle area as desired. 10. Place the new millboard refractory ring in place of the old one and seal between the sections and any other small openings with a small amount of furnace cement or high temperature caulk. 11. Place the top jacket back over the millboard making sure to line up the marks made in Step #3 above. 12. Reinstall the sheet metal screws in the top cover, starting at one side and working around the boiler. The use of a pry bar is suggested to pull the outer edge down far enough to line up the holes. 13. Replace the gasket on the hand-hole plate (see previous pages of part number and instructions), and reinstall the top hand hole assembly. 14. Reinstall the top jacket fiberglass insulation strip. Replace this insulation strip with a new one if necessary. 15. Reinstall the top jacket and secure it to the top cover and to itself with the seven (7) screws that were removed.
- 30 -
MAINTENANCE LOG
- 31 -
MAINTENANCE LOG
- 32 -
- 33 -
The burner circuit should be open, signifying the burner circuit is broken. 10. Continuity across Terminals TH2-MI and TH2-M2 signifies the boiler feed pump circuit is energized, signifying the pump is attempting to fill the boiler. Warrick Series 26 Probe Type Low Water Cut-Off Testing While Operating. (Red LED ON indicates normal operating condition.) 1. While the boiler is operating normally, open the lower blow down valve and allow the water level to drop below the level of this probe. 2. The probe relay should open and lockout. 3. Fill the boiler to a level higher than the probe. The relay should not reset automatically. 4. After the water level has risen to the normal operating level, depress the Probe Reset switch on the front of the panel box. The burner should start operating normally. Testing While Not in Operation. 1. Energize the control circuit and fill the boiler to the normal operating water level. 2. Depress the Probe Reset switch on the front of the panel box. Open the panel box and locate the terminal blocks; TB1 is the upper block, TB2 is the lower block. 3. Using an AC Continuity Tester, Check for continuity between terminal P2 and Ground, indicating that the Secondary Low Water probe circuit is functioning properly. 4. Open the lower blow down valve and allow the water level to drain below the level of the probe. The relay should open and continuity between terminals P2 and Ground should be broken. 5. Close the lower blowdown valve and fill the boiler to the normal operating water level. The relay should not reset automatically and continuity between terminals P2 and Ground should remain broken.
- 34 -
Danfoss Operating Pressure Control Testing While in Operation. 1. Start the burner and allow the boiler pressure to rise to the main set point. The burner should shut off. 2. Open the steam valve and relieve pressure until the pressure is below the lower set point. the burner should now start. The lower set point is determined by taking the differential from the main set point. Testing while not in operation. 1. To test operation of pressuretrols while unit is not in operation requires the use of an external source of pressure such as an air compressor. 2. Close all valves and connect the pressure source to the boiler. 3. Increase the pressure in the boiler until the pressure is higher than the setting on the controller. The mercury switch should rock over such that continuity is now broken. 4. Decrease the pressure in the boiler until the differential is satisfied. The mercury switch should rock back to a position that causes continuity to be made across the switch. Danfoss Safety Limit Pressure Control Testing while in operation. 1. Adjust the safety limit set point below the main set point. 2. Start the burner and allow the boiler pressure to rise to the safety limit pressure level. 3. The burner should shut off and not restart until the manual reset lever is depressed. Testing while not in operation. 1. To test operation of pressuretrols while unit is not in operation requires the use of an external source of pressure such as an air compressor. 2. Close all valves and connect the pressure source to the boiler.
- 35 -
3. Increase the pressure in the boiler until the pressure is higher than the setting on the controller. The mercury switch should rock over such that continuity is now broken and the manual reset switch should open. 4. Decrease the pressure in the boiler. The mercury switch should rock back to a position that causes continuity to be made across the switch but should not close until the manual reset lever is depressed. Safety Valve WARNING: USE CAUTION PRIOR TO PERFORMING A TRY LEVER TEST SINCE LOUD, VERY HOT AND HIGH VELOCITY STEAM WILL DISCHARGE FREELY FROM THE DISCHARGE PORT AND THROUGH THE DRAIN HOLE PROVIDED IN THE SIDE OF THE VALVE BODY.
1. Bring the boiler pressure up to maximum operating pressure, but not less than 75% of maximum pressure (112 PSI), otherwise distortion could occur. If necessary adjust operating and high limit controls to a higher setting. 2. Test the valve at or near maximum operating pressure by holding the test lever fully open for approximately five seconds to flush the valve seat free of any debris or sediment and then permit the valve check to snap shut. 3. If lift lever does not activate and there is no evidence of valve discharge, shut down equipment immediately and replace the valve. 4. Adjust operating and high limit controls to their normal settings. Honeywell S8600 Series Intermittent Pilot Modules - Gas Fired Units The following is a list of tests that may be required. For more information see Honeywell publication form number 68-0085-2 (Rev 12-89), located in the appendix of this manual. Pilot turndown test Flame failure test Power failure test The S8600 Series control is used to prove a pilot flame. This test insures that the main burner flame can be lit by the smallest pilot flame that will prevent loss of pilot shut down. 1. Shut off the main fuel supply to the burner by closing the manual main burner shut off cock. Do not shut off fuel supply to the pilot valve. 2. Connect a Honeywell W136A tet meter, or equivalent microammeter, in series with the flame rod. Connect a standard electrical meter, set for 24 volt range, to terminals MV-MV on the control.
FM-148 COLUMBIA BOILER COMPANY, REV 6-06
- 36 -
3. Start the burner. After the prepurge is complete, the pilot will light and indicate between 1-1/2 and 4 microamps. The main gas valve should try to open and indicate power between terminals MV-MV. 4. Reduce the size of the pilot flame to the turndown position by slowly closing the manual valve on the pilot gas line. At the turndown condition, the pilot will be small enough so it just barely causes the main gas valve to open (about 1 to 11/2 microamps.). a. slowly turn down the pilot until the main gas valve will not open and the burner shuts down on flame failure. NOTE: The burner motor will continue to run. b. Allow the burner to complete prepurge. If the control locked out, reset the control by depressing the reset switch for sixty seconds and restart the burner. c. As the control attempts to restart the pilot, turn the pilot back up slowly until the gas valve tries to open. d. Again turn the pilot down slightly but not enough so the flame drops out. If the relay drops out simply repeat step c above. If the control locks out allow the safety switch to cool, reset the switch, and repeat step c. 5. Check that the pilot is lit and the gas valve is trying to open. 6. Open the manual main burner gas cock. Main flame should light within one second. If the burner does not light within one second, close the shutoff cock and shut off power to the relay. Proceed to step 8. 7. If the burner lights, repeat step 6 a number of times to verify the light off. Proceed to step 10. 8. If the light off is unsatisfactory, readjust the flame detector to require a larger pilot flame to cause the main gas valve to open. a. Adjusting the flame rod detector so that a larger minimum pilot flame is required by moving the flame rod farther from the grounding rods. 9. repeat the entire turndown test until the flame is established promptly in step number 6. 10. Turn the pilot up to full flame at the completion of the test.
- 37 -
Flame Failure Test 1. Let burner operate normally for five minutes, then manually shut off the fuel supply to simulate flame failure. 2. The system should drop out and fuel valves should close. NOTE: The burner motor will continue to run. 3. Let the safety switch cool, reopen manual fuel valve, and reset safety switch. 4. Burner should start. Power Failure Test 1. Let the burner operate normally for five minutes. Simulate power failure by opening a line switch. All relays should drop out and the fuel valves should close. 2. After a minimum of five seconds, close the line switch. 3. The control should go through a normal operating cycle.
- 38 -
WATER TREATMENT
Proper treatment of make-up water and boiler water is necessary to prevent scale, or other deposits, and corrosion within the boiler. The absence of adequate external and internal treatments can lead to operational upsets or total boiler failure. Where a choice is available, pretreatment external to the boiler is always preferred and more reliable than treatment within the boiler. Instructions for feed water treatment as prepared by a competent feedwater chemist should be followed. Do not experiment with homemade treatment methods or compounds. Representative samples of feed water and boiler water must be analyzed frequently to ensure that they are in specification. the following terms and guidelines are to be used in conjunction with the advice of a water treatment specialist. Recommended Guidelines for Boiler Water Treatment ANALYSIS pH Total Alkalinity Phosphates Total Hardness Chlorides Total Dissolved Solids Sulfites Specific Conductance Oxygen RECOMMENDED RANGE 10-11 200-700 ppm 30-100 ppm 0-50 ppm 60-200 ppm 2000 ppm Maximum 20-30 ppm < 700 micro ohms cm < .007 mg/liter COMMENTS Low pH promotes corrosion Low: promotes corrosion Prevent scale formation Prevents scale formation A measure of proper blow down High solids may cause surging A good oxygen scavenger A measure of proper blowdown Prevents corrosion and pitting
ppm = parts per million
Use proper water treatment to prevent the buildup of scale on the boiler. After scale has built up on the walls of the boiler it is almost impossible to remove it from the boiler. The introduction of acids into the pressure vessel is thoroughly discouraged, since virtually any solution that will chemically attach the scale will also attack the boiler metal. pH The pH value of the boiler water is a number between zero and fourteen. Values below seven are acidic, seven is neutral, and values above seven ar alkaline. The pH factor is the most important factor influencing scale formation and the corrosive tendencies of boiler water. The pH should be maintained between a minimum of 10.5, and a maximum of 11.0 to prevent acidic corrosion of boiler tubes and plates, and to provide
FM-148 COLUMBIA BOILER COMPANY, REV 6-06
- 39 -
for the precipitation of scale forming salts before scale is deposited. Below a pH of 5.0 the water is acidic enough to dissolve the steel boiler plates. Under these conditions the steel gradually becomes thinner and thinner until its destruction. At a pH between 5 and 9.4 pitting of shell plates will occur at a rate depending on the amount of dissolved oxygen in the boiler. Dissolved Oxygen Dissolved oxygen is caused by the solubility of atmospheric oxygen into the supply water. Aeration of the city water supply is frequently used to remove other noxious gasses. Efficient aeration results in saturation of the water with oxygen. The majority of corrosion problems are directly related to the quantity of dissolved oxygen in the boiler water. Elimination of the corrosive effect of dissolved oxygen can be accomplished both directly or chemically. Direct or mechanical removal of dissolved oxygen is done through the use of a deaerator or by heating the water to a temperature above 180F. Heating the water can be done with a preheater or a sparge tube installed in the return system. Chemical deaerator is done through the introduction of specific chemicals in the boiler to react with the oxygen. The dissolved oxygen content should be maintained at a minimum but at no time should it exceed 0.007 mg/l. Sulfites Sodium sulfite is generally used for the chemical removal of dissolved oxygen within the boiler water. To assure the rapid and complete removal of the oxygen entering the boiler feedwater system the concentration of sulfite in the boiler must be maintained at a minimum of 20 PPM. (parts per million) Solids Solids can be broken up into two categories: suspended solids, and dissolved solids. Suspended solids are those which can be removed by filtration, while dissolved solids are in solution with the water. The best test for the determination of solids content of the boiler water is through a conductance test. The conductance value of boiler water varies by the various ionized salts present. The conductance can be used to measure the total dissolved solids in the boiler water and to serve as an accurate means for the control of solids through the use of blowdown. Another test which is sometimes used as a gauge of solids is to measure the chloride present in the boiler water. The ratio of chlorides in the boiler water to that of the feed water can be used as a means to determine the amount of blowdown required. The chloride test is unsuitable for feedwater with low incoming concentrations and the concentrations in the feedwater must be averaged over time for accuracy.
FM-148 COLUMBIA BOILER COMPANY, REV 6-06
- 40 -
High boiler solids will lead to foaming, priming, surging and carry over. These problems can be overcome by proper, daily blowdown of the boiler. Alkalinity The alkalinity of boiler water should be sufficiently high enough to protect shell and plates against acidic corrosion, but not high enough to produce carryover. A minimum value for alkalinity for adequate protection is 200 PPM. High boiler alkalinity, which is in excess of 700 PPM. should be avoided. Values higher than this can lead to embrittlement of the steel. Phosphates Phosphates are used to react with calcium hardness in the boiler water. In order for this reaction to take place it is important to maintain a pH at a minimum value of 9.50. It is desirable to keep the concentration of phosphates in the water to 30-50 PPM in order for complete reaction of the phosphates with the calcium hardness entering the boiler through the feedwater. Hardness The hardness of water is caused by calcium and magnesium ions which will vary greatly throughout the country depending on the source of the water. In boilers the hardness of the water can cause the formation of scale and sludge or mud. The hardness must be removed in the makeup water to the return system. Total hardness should not exceed 50 PPM. Oils Every effort should be made to prevent oils from getting into the boiler water. Oil causes foaming, or combines with suspended solids to form a sludge which can cause the overheating of boiler plates. If oil does get into the boiler, the boiler should be taken out of service immediately, and thoroughly cleaned.
- 41 -
- 42 -
BLOWDOWN SEPARATOR
Figure 9
- 43 -
TROUBLE SHOOTING
The first step in trouble shooting is to have a qualified service technician, with the required instruments and expertise, diagnose your system and attempt to fix the problem. Please adhere to the Service Policy at the beginning of this manual. Surging or bouncing water level Surging or bouncing water levels are caused by boiler water which has a high concentration of solids or oils. It is recommended that the frequency of blowdown be increased until the surging condition is corrected. Extreme cases may require the boiler to be boiled out following the previously outlined procedures. A water treatment specialist should be consulted immediately. Pump runs but does not put water in the boiler. Check that the feedwater piping is not clogged between pump and boiler. Insure that all of the steam traps in the system and the check valves between the pump and boiler are working properly. Many times, steam in the impeller area of a pump will cause cavitation and damage. Refer to pump manufacturer for instructions. Boiler flooded in the morning. When the boiler is shut off and the steam in the system condenses, a vacuum is created. On tight or new systems there may be no way for air to enter the system to eliminate the vacuum. When this happens, water is drawn through the return system into the boiler, This will also cause flooding of the return tank. The replacement of a swing type check valve and manual valve on the boiler with the direction of flow into the boiler, will eliminate this problem. It is recommended that the manual valve be closed during normal operation so that a failure of the check valve will not result in steam being released into the boiler room. Fan motor runs but burner does not light. The air switch has not proved an air flow. Check for continuity across the terminals of the air switch and replace the air switch if it is defective. If a S8600 Series control is used, try resetting the control. If the S8600 Series control loses the pilot signal, the control will lock out until it reset, and the fan will continue to run.
- 44 -
APPENDICES
NOTES __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________
5 5A 5B 5C 6 6A 6B 6C 7 8 8A 8B 8C 9 10
WARRICK LWCO & PUMP CONTROL HIGH PROBE, PUMP OFF, 8 LOW PROBE, PUMP ON, 9-1/2 PRIMARY LOW WATER CUT-OFF PROBE, 11 WATER GAUGE SET 5/8 X 10-1/4 GAUGE GLASS TRI-COCKS (3) (OPTIONAL) GAUGE GLASS PROTECTOR, LEXAN LWCO BLOWDOWN VALVE, 1 BALL VALVE PRESSURE CONTROLS SAFETY LIMIT W/ MANUAL RESET OPERATING LIMIT, KP36 HIGH FIRE, KP36 STEAM PRESSURE GAUGE, 0-300 PSI SECONDARY LOW WATER CUT-OFF PROBE ASSY. w/MANUAL RESET, WARRICK SECONDARY LWCO PROBE PLUG
558840
10A
ALL
558920
REFERENCE NUMBERS ABOVE REFER TO DWG. CT-545 EXCEPT REFERENCE NO. 4 SERIES REFERS TO DWG. CT-546. WHEN ORDERING PARTS, SUPPLY THE BOILER MODEL NUMBER, SERIAL NUMBER, AND THE SIX DIGIT ITEM NUMBER.
CTPRTSLSTMY03.wpd REV. MAY 2006
GAS TRAIN PIPING DIAGRAM for CT-6/10 BOILER w/POWER FLAME JR15A-10 (3/4") GAS BURNER
GAS TRAIN PIPING DIAGRAM for CT-15 BOILER w/POWER FLAME JR15A-10 GAS BURNER & CT-20 BOILER w/POWER FLAME JR30A-12 GAS BURNER
GAS TRAIN PIPING DIAGRAM for CT-25 BOILER w/POWER FLAME JR30A-12 GAS BURNER & CT-35 BOILER w/POWER FLAME JR50A-15 GAS BURNER
GAS TRAIN PIPING DIAGRAM for CT-50 BOILER w/POWER FLAME JR50A-15 GAS BURNER
REF. No.
DESCRIPTION
52
ORIFICE TEE
53
PRESSURE TAP
54
56
BALL VALVE
58
GAS VALVE
60
62
ELBOW
63
BUSHING
65
66
PLUG
68
70
UNION
72
BALL VALVE
74
COUPLING
75
REDUCER
76
78
80
82
UNION
84
TEE
85
PRESSURE TAP
REFERENCE NUMBERS ABOVE REFER TO DWG. CT-549A. WHEN ORDERING PARTS, SUPPLY THE BOILER MODEL NUMBER, SERIAL NUMBER, A ND THE DESCRIPTION AND SIZE, OR MFRS ITEM NUMBER.
SEE THE BURNER SECTION IN THE BOILER MANUAL BINDER FOR THE APPLICABLE WIRING DIAGRAMS FOR THIS BOILER.
DIMENSIONAL DIAGRAM
WARRICK CONTROLS ONE COWLES ROAD PLAINVILLE, CT 06062-1198 PHONE: (860) 793-4579 FAX: (860) 793-4580
5/95
PRINTED IN U.S.A.
5/93
MODEL NO. CT-6 CT-10 CT-15 CT-20 CT-25 CT-35 CT-50 ___________________________________________________________________________ RATINGS: ___________________________________________________________________________ Horsepower 6 9.5 15 20 25 35 50 ___________________________________________________________________________ Gas INput (BTU per hour) 252,000 399,000 630,000 840,000 1,050,000 1,470,000 2,100,000 ___________________________________________________________________________ Oil Input (Gals. per hour) 2.00 2.85 4.50 6.00 7.50 10.50 15.00 ___________________________________________________________________________ Output (BTU per hour) 201,600 320,000 504,000 672,000 840,000 1,176,000 1,680,000 ___________________________________________________________________________ Output (Lbs. steam per hour) 207 320 517 690 862 1207 1725 ___________________________________________________________________________ Maximum Allowable Working Pressure 150 150 150 150 150 150 150 ___________________________________________________________________________ Water Capacity (Gals.) 16 27 37 43 59 90 240 ___________________________________________________________________________ Steam Release Surface Area 183 sq. in. 262 sq. in. 389 sq. in. 501 sq. in. 627 sq. in. 817 sq. in. 1,402 sq. in. ___________________________________________________________________________ Hand Hole Sizes (3) 3 x 4 (3) 3 x 3-3/4 (3) 3 x 3-3/4 (4) 3 x 3-3/4 (4) 3 x 3-3/4 (4) 3 x 3-3/4 (4) 3 x 3-3/4 ___________________________________________________________________________ BOILER DIMENSIONS: ___________________________________________________________________________ A Boiler Height (includes piping) 70" 78" 84" 88" 92" 96" 103" ___________________________________________________________________________ B Boiler Diameter 34" 36" 40" 41" 42" 43" 56" (left to right, packaged including M & M) ___________________________________________________________________________ C Boiler Diameter 27" 30" 34" 37" 40" 43" 56" (left to right, less trim & piping) ___________________________________________________________________________ D Burner to Flue Outlet (approx.) 47" 48" 54" 58" 62" 71" 94" ___________________________________________________________________________ E Flue Outlet (diameter) 6" 6" 8" 8" 10 12 12" ___________________________________________________________________________ F Flue OUtlet to Floor (centerline) 48-1/4" 55" 60" 63-1/2" 65-1/2" 69" 76-1/4" ___________________________________________________________________________ G Steam Outlet (IPS) 3/4" 3/4" 1" 1" 1-1/4" 1-1/4" 2" ___________________________________________________________________________ H Feedwater Inlet 1/2" 1/2" 1/2" 3/4" 3/4" 3/4" 1" ___________________________________________________________________________ I Feedwater Inlet to Floor (centerline) 22-3/8" 24-3/8" 24-3/8" 27-3/8" 28-3/8" 13-1/2" 15-1/2" ___________________________________________________________________________ J Blowdown Outlet (IPS) 1" 1" 1" 1" 1" 1" 1-1.4" ___________________________________________________________________________ K Normal Water Line to Floor 46-3/4" 54-1/2" 60-1/2" 65" 69" 71-1/2" 81-1/2" ___________________________________________________________________________ Approx. Floor space 3' x 5' 3' x 5' 3-1/4' x 5' 3-1/2' x 5-1/2' 4' x 6' 5' x 8' 6' x 10' ___________________________________________________________________________ CRATED DIMENSIONS: ___________________________________________________________________________ Left to Right 38" 41" 43" 44" 44" 45-1/2" 56" ___________________________________________________________________________ Front to Rear 53" 56" 62" 66" 66" 77" 96" ___________________________________________________________________________ Height 73" 81" 86" 95" 95" 95" 104" ___________________________________________________________________________ Approx. Shipping Wt. (skidded & crated) 1580 lb 1900 lb 2450 lb 3075 lb 3400 lb 4650 lb 6200 lb
PRINTED IN U.S.A.