Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Rockwell Automation, Allen-Bradley, TechConnect, PLC-5, SLC, SLC 500, SLC 5/03, PanelView, Powermonitor 3000, ControlLogix, Rockwell Software, RSNetworx for DeviceNet, RSNetworx for ControlNet, RSLogix 5000, RSEnergyMetrix, RSPower, RSPowerPlus, and RSLin are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
Introduction
This release of this document contains new and updated information. To find new and updated information, look for change bars, as shown next to this paragraph.
Updated Information
Topic Added information about single-instance parameters Single instance parameter for DeviceNet
Page 19 77
Added Single Element Writes to the primary 80 methods to communicate with a power monitor Added information for writing single element data to a data table Added information about floating-point word order Added information for configuring protocol selections Changed the placeholder from instance 99 to instance 255 Added information about changing the configuration of Instance 1 in the user configured table Added information about setpoint output action logic Added an example of sag alarm for setpoint operation Changed element 3 range in the Discrete Data table to 07 Updated the Native Communication Configuration table, it has nine elements and the range for element 3 is 06 Updated the optional communication configuration table for Ethernet, adding protocol selection as element 13 Updated the optional communication configuration table for DeviceNet, adding floating point data format as element 4 Changed the element 4 range in the RS-232 table to 06 86 100 103 110 122
199
202
203
Summary of Changes
Topic Added Single Password Write data tables Added Single Parameter Read data tables Added sample applications: Read and write power monitor tables by using an SLC 500 controller and a 1747-SCNR ControlNet scanner. Read and write power monitor tables by using a MicroLogix controller over EtherNet/IP and Modbus RTU communication networks. Read and write power monitor tables by using a Component HMI over an EtherNet/IP communication network.
Additioanl minor changes have been made throughout the document. Change bars mark all changes.
Table of Contents
Preface
Using This User Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Additional Resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Terms and Conventions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1 Safety
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Other Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chapter 4 Communication
Configuring Communication . . . . . . . . . . . . . . . . . . . . . . . . 63 Data Messaging Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Data Messaging- application Considerations . . . . . . . . . . . . . 90
Table of Contents
. . . 320 . . . 331
Glossary Index
Preface
You should have a basic understanding of electrical circuitry and familiarity with relay logic. If you do not, obtain the proper training before using this product.
For information about Safety Product Description Communication Options Powermonitor 3000 Unit Operations Metering Functionality Display Module Functionality Configuration by Using the Display Module Metering Update Rate Communication Configuring Communication Data Messaging Overview Data Messaging- application Considerations Setpoint Programming and Operation Theory of Setpoint Operation Configuring Setpoints I/O Operations Relay and KYZ Output Operations Status Input Operations Data Logging Event Log Configurable Trend Log Min/Max Log
Refer to Chapter 1 2 3
Preface
Preface
For information about Advanced Features Oscillography Harmonic Analysis Sag and Swell Load Factor Transient Detection, Metering and Capture Powermonitor 3000 Data Tables Catalog Number Explanation Sample Applications Technical Specifications Frequently Asked Questions Glossary Index
Refer to Chapter 8
A B C D E Glossary Index
Preface
Preface
Additional Resources
Refer to these power and energy management documents for more information.
For this information Powermonitor 3000 Installation Instructions (all communication options) Bulletin 1404 Powermonitor 3000 Display Module Installation Instructions Bulletin 1404 Series B Ethernet Communication Release Note Refer to Publication 1404-IN007 1404-IN005 1404-RN008
You can view or download publications at http://www.rockwellautomation.com/literature. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
Preface
Preface
Abbreviation RAM RTOS R I/O PCCC RMS SNTP SPDT SLC UL VA VAR
Term Random Access Memory Real Time Operating System Remote Input/Output Rockwell Automations proprietary Programmable Controller Communication Commands protocol Rootmeansquare Simple Network Time Protocol Single Pole Double Throw Small Logic Controller Underwriters Laboratories Voltampere Voltampere Reactive
10
Chapter
Safety
Safety Considerations
Before installing and using this product, please read and understand the following precautions.
ATTENTION
Only qualified personnel, following accepted safety procedures, should install, wire and service the Powermonitor 3000 unit and its associated components. Before beginning any work, disconnect all sources of power and verify that they are de-energized and locked out. Failure to follow these instructions may result in personal injury or death, property damage, or economic loss.
ATTENTION
Never open a current transformer (CT) secondary circuit with primary current applied. Wiring between the CTs and the Powermonitor 3000 unit should include a shorting terminal block in the CT secondary circuit. Shorting the secondary with primary current present allows other connections to be removed if needed. An open CT secondary with primary current applied produces a hazardous voltage, which can lead to personal injury, death, property damage, or economic loss.
IMPORTANT
The Powermonitor 3000 unit is not designed for nor intended for use as a circuit protective device. Do not use this equipment in place of a motor overload relay or circuit protective relay.
IMPORTANT
The relay output contacts and solid-state KYZ output contacts on the Powermonitor 3000 unit may be used to control other devices through setpoint control or communication. You configure the response of these outputs to a communication failure. Be sure to evaluate the safety impact of the output configuration on your plant or process.
11
Chapter 1
Safety
Other Precautions
ATTENTION
Electrostatic discharge can damage integrated circuits or semiconductors. Follow these guidelines when you handle the module. Touch a grounded object to discharge static potential. Wear an approved wrist strap-grounding device. Do not open the module or attempt to service internal components. Use a static safe workstation, if available. Keep the module in its static shield bag when not in use.
12
Chapter
Product Description
The Bulletin 1404 Powermonitor 3000 unit is designed and developed to meet the needs of both producers of and users of electric power. A power monitor system consists of: a master module that provides metering, data logging, native RS-485 communication, and other advanced features depending on the model. an optional display module for configuration, entering commands, and displaying data. an optional communication port to serve data to other devices using a choice of networks. optional external devices and applications that display and utilize data for reporting, control, and management of power and energy usage. The Powermonitor 3000 unit is a microprocessor-based monitoring and control device suited for a variety of applications including the following: Load Profiling Using the configurable trending utility to log power parameters such as real power, apparent power, and demand, for analysis of power usage by loads over time Demand Management Understanding when and why demand charges occur lets you to make informed decisions that reduce your electrical power costs Cost Allocation Knowing your actual energy costs promotes manufacturing efficiencies Distribution System Monitoring Using power parameters to show power flow, system topology, and distribution equipment status Emergency Load Shedding Monitoring power usage to preserve system stability in the event of sudden utility outage Power System Control Managing system voltage, harmonic distortion, and power factor The power monitor is a sophisticated modern alternative to traditional electromechanical metering devices. A single Powermonitor 3000 unit can replace many individual transducers and meters. The power monitor is simple to install, configure, and operate, and provides you with accurate information in a compact economical package.
13
Chapter 2
Product Description
Master Module
The master module contains the main microprocessor-based monitoring functions, including terminations for power system connections, status inputs, control outputs, a native RS-485 communication port, and a port for the display module.
Configuration
Although the power monitor ships from the factory with default settings, you need to configure it for your particular requirements. You may configure the power monitor by using the optional display module. Alternately, you may use an external device or application to write configuration, operational parameters, and commands to the master module through its native or optional communication port. Optional external applications that you may use for power monitor configuration include RSPower, RSPowerPlus, and RSEnergyMetrix software operating on a computer with a Microsoft Windows operating system. Contact your local Rockwell Automation sales office or distributor, or visit http://www.software.rockwell.com/ for more information on available software packages.
Communication
Every power monitor comes with a native RS-485 communication port that supports the Allen-Bradley DF1 half- or full-duplex slave and Modbus RTU slave protocols. The native port is suitable for communicating to devices including the following: PLC-5, SLC 500, and ControlLogix processors RSLinx software with DDE/OPC server functionality Modbus RTU masters Other third-party devices Software that you develop
You may also specify power monitors with optional communication ports including the following: Serial RS-232 (DF1 half- or full-duplex or Modbus RTU slave) Remote I/O DeviceNet EtherNet/IP (CIP and/or CSP, Modbus TCP) ControlNet
14
Product Description
Chapter 2
You may integrate a power monitor into a programmable controller based control and monitoring system by using your choice of the native or optional communication methods.
Display Module
The Bulletin 1404 display module is an optional user interface device. The display module provides the most economical and simplest method for setting up and configuring the master module for operation. The display module has a highly visible, two-line LED display and four operator buttons with tactile feedback. Use the buttons and display to navigate through a series of menus for configuration, commands, and data display. The display module is shipped with a 3 m (10 ft) long, shielded four-pair cable that provides power and serial communication between the master module and the display module. The display module fits into a standard ANSI 4 in. analog meter cutout for panel mounting. Only one display module may connect to a master module, although you may use one display module to configure and monitor any number of master modules one at a time.
15
Chapter 2
Product Description
Performance Features
The power monitor is available in four basic models, designated M4, M5, M6, and M8. Each model offers specific functionality as indicated in this table. The M5 model offers M4 functionality and can be field-upgraded to an M6 or M8 model for an additional charge.
Product Features of Powermonitor 3000 Module M4 M5 M6 M8 Master Module Features
(1)
Voltage, current, power measurements and display Compatible with PLC-5, SLC 500, and ControlLogix controllers Compatible with RSLinx, RSPower, RSPowerPlus, RSEnergyMetrix, and RSView32 software Output control via control relays or PLC controllers Demo mode for training 10 user configurable setpoints Discrete condition monitoring via status inputs Electronic KYZ pulse output Form C ANSI C37.90-1989 rated relay for direct breaker tripping Time stamped data logging of system measurements and events Configurable trend log, up to 45,000 records deep Event log 50 records deep Firmware upgrades without removing module Total harmonic distortion (THD) and Crest Factor Automatic network-based time synchronization via SNTP Daylight Saving Time ANSI C12.20 Class 0.5 revenue metering accuracy(1) EN60687 Class 0.5 revenue metering accuracy(1) Canadian Revenue Meter specification accuracy Field upgradeable to M6 or M8 (extra cost option) 10 additional setpoints with more options Event Log an additional 50 records deep User configurable oscillography up to 400 cycles @ 60 Hz TIF, K-factor and IEEE-519 Pass/Fail Sag and swell detection with oscillogram capture Load factor log 12 records (months) deep Calculates amplitude and % distortion for harmonics 141 Calculates amplitude and % distortion for harmonics 163 Sub-cycle transient capture and metering Transducer and Energy Meter modes with improved update rate
16
Product Description
Chapter 2
Communication Options
In addition to the native RS-485 communication port, several factory-installed communication options are also available. These options make it possible for a user to select Powermonitor 3000 units to provide power and energy information into a variety of existing or new control systems and communication networks. Each communication option supports bi-directional data transfer with external devices or applications. Metering measurement, logging, configuration and status data may be accessed via communication. Communication options are set in the master module. You may configure communication by using the display module or via communication to an external application such as RSPower, RSPowerPlus, or RSEnergyMetrix. Refer to the information later in this manual on configuration and operation of the communication options. Refer to the Powermonitor 3000 Installation Manual, publication 1404-IN007, for installation and wiring information related to your selected communication options. The last 3 characters of the catalog number specify the communication option of the Powermonitor 3000 unit.
17
Chapter 2
Product Description
18
Product Description
Chapter 2
19
Chapter 2
Product Description
Compatible with commercially available network bridges, routers, hubs and switches Fully software configurable Supports RSLinx software Supports Allen-Bradley Client Server Protocol (CSP) Supports EtherNet/IP (CIP) protocol Configurable I/O channel assembly instance: six parameters default, twenty-three maximum Configurable explicit assembly instance: seventeen parameters default, twenty-three parameters maximum Explicit assembly instances for access to all data Two I/O assembly instances Remotely resettable through Identity Object Supports up to 64 CIP/HTTP concurrent connections Data read latency: less than 10 ms Update rates for real-time metering data: 100 ms minimum Update rates for logged data: 250 ms minimum Supports network-based time synchronization via SNTP Supports networked demand period synchronization Supports Class 1 scheduled connection for I/O data
20
Product Description
Chapter 2
Supports up to 64 concurrent Class 1 connections to instance 1 and one Class 1 connection to Instance 2. ControlFlash can be used to update ControlNet communication firmware Supports ControlLogix message types: CIP Generic, PLC-5 Typed Set power monitor node address (MAC ID) via display module, native comm port, or ControlNet assembly instance 12
Master Module with Various Communication Options
Removable Status Input Connector Terminal Blocks Status Indicators Display Module Port
Powermonitor 3000
Powermonitor 3000
Powermonitor 3000
Powermonitor 3000
Powermonitor 3000
21
Chapter 2
Product Description
Status Indicators
The power monitor is equipped with six, two-color status indicators arranged as shown. Functions of the indicators differ among the various communication configurations.
Status Indicators
Powermonitor 3000
The three indicators on the left, display the same information on Powermonitor 3000 units with any communication option including native RS-485 communication only. The three indicators on the right have different labels and different indications depending on the communication option selected, as shown in this table.
Status Indicators All Powermonitor 3000 Models Status Indicator Module Status Indicator Color Off Steady Red Indicator State and Communication Condition Control power is off or insufficient Major fault; internal self-test has failed. If a power cycle does not correct the problem, call customer support Powermonitor 3000 unit is operating normally The RS-485 bus is idle; no active data is present Active data is present on the RS-485 bus Powermonitor 3000 unit is not transmitting data onto the RS-485 bus Powermonitor 3000 unit is transmitting data onto the RS-485 bus
Steady Green RS-485 RX Off Flashing Green RS-485 TX Off Flashing Green
22
Product Description
Chapter 2
Powermonitor 3000
F1 F2 F3
Status Indicator F1 F2 F3
Indicator State and Communication Condition Not Used Not Used Not Used
Indicator State and Communication Condition Not Used The RS-232 bus is idle; no active data is present Power monitor is receiving data. The power monitor is not transmitting any data onto the RS-232 bus The power monitor is transmitting data.
F1 RS-232 RX
F1 RX TX
}
F1 F2
RS-232
RS-232 TX
Indicator State and Communication Condition Not Used Not Used Remote I/O communication has not been established Remote I/O communication has been established but there are errors Remote I/O communication has been established
R I/O
23
Chapter 2
Product Description
Indicator Color Off Off Off Flashing Green Steady Green Flashing Red Steady Red
Indicator State and Communication Condition Not Used Not Used Power is off or the power monitor is not online Network status is OK, no connections established Network status is OK, connections established Recoverable communication failure; port is restarting Non-recoverable communication error; check wiring and configuration parameters
F1
F1 F2 NETWORK STATUS
F2 Network Status
Powermonitor 3000
Indicator Color Off Steady Green Strobing or Solid Yellow Off Off Off Flashing Green Steady Green Flashing Red Steady Red Flashing Green/Red
Indicator State and Communication Condition No valid physical Ethernet connection Valid physical Ethernet connection Power monitor transmitting onto Ethernet Not Used Not Used No power No established connections Connected; has at least one established connection Connection timeout; one or more connections to this device has timed-out Duplicate IP; the IP address assigned to this device is already in use Selftest; this device is performing a power-up self test
24
Product Description
Chapter 2
Indicator Color Off Steady Red Alternating red/green Alternating red/off Steady green Flashing green/off Flashing red/off Flashing red/green
Indicator State and Communication Condition No power or Channel disabled Faulted unit Self-test Incorrect node configuration Normal operation Temporary errors or node is not configured to go online Media fault or no other nodes present on network Incorrect network configuration Normal operation Communication card power-up self-test
Status
25
Chapter 2
Product Description
26
Chapter
The Powermonitor 3000 unit is a microprocessor-based electrical power- and energy-measuring device. It connects to your three-phase or single-phase ac power system directly or through instrument transformers (PTs and CTs). It converts instantaneous voltage and current values to digital values, and uses the resulting digital values in calculations of things such as voltage, current, power, and energy. You may access the resulting metering values manually by using the display module or automatically by using communication with an external device or application. The basic operations of the Powermonitor 3000 unit include the following: Metering functionality Operational and status indication Operation of the display module Display module menus and parameter structure Setup and configuration by using the display module Data monitoring by using the display module Issuing commands by using the display module
Other power monitor features such as communication, setpoint operations, I/O operations, data logging, oscillography, harmonics, sag/swell detection, load factor calculation, and transient detection are covered later in this manual.
Metering Functionality
The power monitor performs calculations on scaled, digital voltage and current values. Signals connected to the voltage and current inputs are sampled and their instantaneous values are converted to digital values in an analog-to-digital (A/D) converter section. These values are scaled according to configured PT Primary, PT Secondary, CT Primary, and CT Secondary parameters, and evaluated according to the configured Wiring Mode parameter. Metering results are available for display on the display module, in the communication data tables, and for use in setpoint programming and data logging. The table on page 28 provides a summary of measurements produced in each Powermonitor 3000 unit, and notes which measurements you may view by using the display module.
27
Chapter 3
Measurement Current, per phase and neutral Average current Positive sequence current Negative sequence current Percent current unbalance Voltage per phase L-L, and L-N on four-wire systems Average voltage per phase L-L, and L-N on four-wire systems Positive sequence voltage Negative sequence voltage Percent voltage unbalance Frequency Phase rotation (ABC, ACB) Real power (watts), total and per phase on four-wire systems Reactive power (VARs), total and per phase on four-wire systems Apparent power (VA), total and per phase on four-wire systems True power factor (PF), total and per phase on four-wire systems Displacement PF, total and per phase on four-wire systems Distortion PF, total and per phase on four-wire systems Energy consumption in kilowatt-hours (kWh), forward, reverse, and net Reactive energy consumption in kVAR-hours, forward, reverse, and net Apparent energy consumption in kVA-hours Current consumption in ampere-hours Demand (kA, kW, kVAR, and kVA) Projected demand (kA, kW, kVAR, and kVA) Load factor calculation (amps, watts, VAR, and VA) IEEE percent THD (total harmonic distortion) IEC percent THD (Distortion Index) (DIN) Crest Factor TIF (Telephone Interference Factor) K-factor IEEE 519 TDD (total demand distortion) IEEE 519 pass/fail calculation on voltage and current Individual percent and RMS magnitude, harmonics 141 Individual percent and RMS magnitude, harmonics 4263 Oscillography capture data Transient voltage and current index RMS voltage and current per phase for each cycle of transient capture Transient capture wave form data
If this box is checked, you may view the measurement by using display module. If not, you may access measurements by using communication only.
28
Chapter 3
29
Chapter 3
Chapter 3
Frequency Averaging like the RMS result averaging, the default setting provides for a smoother response by averaging the frequency of each of the last eight cycles. You may select no averaging to return the frequency of only the last cycle Refer to Advanced Device Configuration on page 50 for more information.
The Voltage, Current, and Frequency Metering table on page 32 summarizes the voltage and current metering information provided by the power monitor.
31
Chapter 3
Voltage, Current, and Frequency Metering Parameter Phase 1 L-N Voltage Phase 2 L-N Voltage Phase 3 L-N Voltage 3-Phase Average L-N Voltage Phase 1 L-L Voltage Phase 2 L-L Voltage Phase 3 L-L Voltage 3-Phase L-L Voltage Phase 1 Current Phase 2 Current Phase 3 Current 3-Phase Average Current Phase 4 (Neutral) Current Frequency Phase Rotation Description RMS line to neutral voltage of individual phase or three-phase average Range 0999.9x1022 Units Volts
0999.9x1022
Volts
0999.9x1022
Amps
RMS current of phase 4, also known as neutral or zero-sequence current The frequency of the voltage The phase rotation of a three-phase system
Voltage Positive Sequence Voltage Negative Sequence Current Positive Sequence Current Negative Sequence Voltage Unbalance Current Unbalance
(1)
Magnitude of positive sequence voltage in a three-phase system(1) Magnitude of negative sequence voltage in a three-phase system(1) Magnitude of positive sequence current in a three-phase system
Magnitude of negative sequence current in a three-phase system 0999.9x10 The ratio between the negative and positive voltage sequence in 0100 a three-phase system The ratio between the negative and positive current sequence in 0100 a three-phase system
Expressed in line-to-neutral volts for Wye and line-to-line volts for Delta wiring modes.
Power Results
Real power, that is the portion of the voltage and current applied to a power system that is doing work, is calculated on a per-phase (L1 Real Power, L2 Real Power, L3 Real Power), and Total Real Power. L1 Reactive Power, L2 Reactive Power, L3 Reactive Power and Total Reactive Power similarly return that portion of the power used in capacitive or inductive reactance in the power system and doing no work. L1 Apparent Power, L2 Apparent Power, L3 Apparent Power and Total Apparent Power return the apparent power, which is the simple mathematical product of the system voltage and system current. For single-phase wiring mode, all L3 power values remain at zero and are not included in the total power calculation.
32
Chapter 3
Power and Power Factor Results Parameter Phase 1 Power Phase 2 Power Phase 3 Power 3-Phase Total Power Phase 1 Reactive Power Phase 2 Reactive Power Phase 3 Reactive Power 3-Phase Total Reactive Power Phase 1 Apparent Power Phase 2 Apparent Power Phase 3 Apparent Power 3-Phase Total Apparent Power Apparent power of individual phase or sum of all phases. 0999.9x1022 VA (volt-amperes) Reactive power of individual phase or sum of all phases; signed to show direction. 0999.9x1022 VARs (volt-amperes reactive) Description Power of individual phase or sum of phases; signed to show direction. Range 0999.9x1022 Units Watts
33
Chapter 3
Power and Power Factor Results Parameter Phase 1 True Power Factor Phase 2 True Power Factor Phase 3 True Power Factor Total True Power Factor Phase 1 Distortion Power Factor Phase 2 Distortion Power Factor Phase 3 Distortion Power Factor Total Distortion Power Factor Phase 1 Displacement Power Factor Phase 2 Displacement Power Factor Phase 3 Displacement Power Factor Total Displacement Power Factor Explanation of Power Factor Values
Pf = 0 +kVAR (Import) kVARHR-F (Forward)
Description The ratio between the power and apparent power for an individual phase or all three phases; signed to show lead (+) or lag (-).
Range -100100
Units Percent
The ratio between the magnitude of the fundamental and the sum of the magnitudes for all of the current harmonics for an individual phase or all three phases.
0100
Percent
The cosine of the phase angle between the fundamental voltage and current for an individual phase or all three phases; signed to show lead (+) or lag (-).
-100100
Percent
90
(Power Factor Leading) (+) Pf = 100% 180 -kW (Export) kWH-R (Reverse) (Power Factor Lagging) (-)
II III I IV
0 +kW (Import)
kWH-F (Forward) (Power Factor Leading) (+)
Pf = 100%
270
Pf = 0 -kVAR (Export) kVARHR-R (Reverse)
Energy Results
The power monitor calculates energy values including kWh forward, reverse and net; kVAh; kVARh forward, reverse and net; and kAh. You may read these values by using the display module or via communication.
34
Chapter 3
Demand Calculation
A typical industrial utility bill includes not only an energy (or kWh) charge but also a Demand charge. Demand is equal to the average power level during a predefined time interval. Some power providers may base demand on current, VA, or VARs instead of kW. This interval continuously repeats and is typically between five and 30 minutes in length. The formula for kW demand is shown below.
t+T
1 - Demand = -T
T = Demand interval duration t = Time at beginning of interval P(t) = Power as a function of time
P ( t ) dt
Usually, a utility rate tariff includes a peak demand charge, determined by the peak demand that occurs during a specified period, which may be one month, one year, or some other duration. As a result, only one occurrence of a high demand level can have a long-term effect on your utility bill. The peak demand value indicates to the utility the reserve capacity they need to satisfy your short-term power requirements. The peak demand charge helps to pay the utility for maintaining this instantaneous capacity. The power monitor computes demand levels for watts, VA, amps, and VARs, and provides three different methods for projecting demand.
35
Chapter 3
The utility may provide a pulse that indicates the end of each demand interval. The utility updates the demand value at the end of each interval and maintains the highest value obtained during any interval. This method is known as thermal demand. You may set up a power monitor to determine its demand interval from the utility pulse. To accomplish this, connect the utility pulse to status input #2 and make the appropriate settings in the Advanced Device Configuration. If the utility does not provide a demand interval pulse, you wont be able to synchronize with the utility to control your demand. In this case, you may use the sliding window method. This method breaks the demand interval into many sub-intervals and updates the demand value at the end of each sub-interval. For example a five-minute interval might be divided into five one-minute sub-intervals. The demand for each one-minute interval is calculated and at the end of five minutes the average value of the sub-intervals is computed to obtain a demand value. At the end of the sixth minute, the value for sub-interval one is discarded and a new demand value computed based on sub-intervals two through six. In this way a new five-minute demand value is obtained every minute. The maximum value is then maintained as the peak demand. This method approximates the actual demand the utility measures. How can you minimize your peak demand in order to reduce your utility demand penalty charges? One way is to measure the power being used and project the demand level at the end of the interval. This method permits you to reduce power consumption when the projected demand reaches a predetermined threshold, thus preventing the final demand from exceeding the desired level.
36
Chapter 3
Instantaneous
The power monitor computes instantaneous demand by substituting the elapsed interval duration for the total interval duration (T) in the demand equation. It is therefore identical to the standard computation except it integrates the power only over the elapsed interval duration and calculates the average value over the elapsed duration. The modified equation thus becomes.
1 Demand = -------------- t2 t1
(t2 - t1) = Elapsed interval duration and is less than T
t2
t1
P ( t ) dt
This method may be useful where your system has a significant base load with additional loads that are switched in and out during the interval.
37
Chapter 3
Energy and Demand Results Parameter Kilo-Watt Hours Forward Kilo-Watt Hours Reverse Kilo-Watt Hours Net Kilo-VAR Hours Forward Kilo-VAR Hours Reverse Kilo-VAR Hours Net Kilo-VA Hours Net Amp Hours Net Demand Current Max Demand Current Demand Kilo-Watts Max Demand Kilo-Watts Demand Kilo-VARs Max Demand Kilo-VARs Demand Kilo-VA Max Demand Kilo-VA Projected Current Demand(1) Projected Kilo-Watt Demand(1) Projected Kilo-VAR Demand(1) Projected Kilo-VA Demand(1)
(1)
Description The total real power consumed The total real power produced The sum of forward and reverse power The total reactive power consumed The total reactive power produced The sum of forward and reverse reactive power The total apparent power consumed Accumulated amp-hours consumed The calculated demand for average current The maximum (peak) demand for current. (included in Min/Max Log) The calculated demand for real power The maximum (peak) demand for real power (included in Min/Max Log) The calculated demand for reactive power The maximum (peak) demand for reactive power (included in Min/Max Log) The calculated demand for apparent power The maximum (peak) demand for apparent power (included in Min/Max Log) The projected demand for average current The projected demand for real power The projected demand for reactive power The projected demand for apparent power
Range 01.0x1012
Units kWh
01.0x1012
kVARh
kVAh Ah Amps
0999.9x1021
kW
0999.9x1021
kVAR
0999.9x1021
kVA
Values returned depend on user selection of projected demand type in Advanced Configuration.
The display module is a simple terminal that allows you to easily view metering parameters or change configuration items. The display module uses three modes of operation. Display mode allows you to view power monitor parameters including metering, setpoint, min/max log, event log and self-test information. You may also select a default screen to be displayed at power-up or after 30 minutes without key activity. Program mode allows you to change configuration parameters, with security against unauthorized configuration changes. Each power monitor is password protected. In Program mode, the display module phase indicators (L1,L2,L3,N) flash. Edit mode allows you to modify the selected parameters. In Edit mode, the parameter being modified flashes, and the phase indicators (L1,L2,L3,N) remain solid.
38
Chapter 3
Key Functions
The display module has four keys located on its front bezel: an Escape key, Up Arrow key, Down Arrow key, and an Enter key. These keys differ slightly in how they function in each mode. See Menu/Parameter Structure on page 40 for a description of their functionality.
POWERMONITOR 3000
L1 L2 L3 N
Display mode
Program mode
Edit mode
Cancels changes to the parameter, restores the existing value, and returns to Program mode
Up Arrow Key Steps back to the previous parameter/menu in the list Steps back to the previous parameter/menu in the list Increments the parameter/menu value
Down Arrow Key Enter Key Steps forward to the Steps into a sub-menu or sets next parameter/menu in as default screen the list Steps forward to the Steps into a sub-menu, selects next parameter/menu in the parameter to be modified the list or changes to Edit mode Decrements the parameter value Saves the parameter change to the master module and returns to Program mode
39
Chapter 3
Menu/Parameter Structure
Chart Key
Default Screen Level 1
Next Item (Within Current Level)
Default Screen?
Level 2
Level 1
Level 3 Display Program Level 4
Previous Item (Within Current Level)
Level 2
Display Metering Display Harmonics Display Logs
Level 3
Metering V,I,F(2) Metering Power(3) Metering Power(4) Harmonics L1,L2,L3,N(1)
IEEE %THD V IEEE %THD I IEC %THD V IEC %THD I Crest Fact. V Crest Fact. I TIF V TIF I IEEE 519 TDD IEEE 519 P/F
Event Log
Event n . . . Event 01
Min/Max Log
Most Recent
Level 4
Volts L1-N Volts L2-N Volts L3-N Volts 3Ph Ave L-N Amps L1 Amps L2 Amps L3 Amps 3Ph Ave Amps Neutral Volts L1-L2 Volts L2-L3 Volts L1-L3 Volts 3Ph Ave L-L Frequency Phase Rotation Volts Pos Seq Volts Neg Seq Amps Pos Seq Amps Neg Seq Voltage Unbalance Current Unbalance Watts L1 Watts L2 Watts L3 Total Power VARS L1 VARS L2 VARS L3 Tot. React. Pwr. VA L1 VA L2 VA L3 Tot. App. Pwr. True PF L1 True PF L2 True PF L3 Tot. True PF Displ. PF L1 Displ. PF L2 Displ. PF L3 Tot. Displ. PF Dist. PF L1 Dist. PF L2 Dist. PF L3 Tot. Dist. PF kW Hours Forward kW Hours Reverse kW Hours Net kVARh Forward kVARh Reverse kVARh Net kVAh Net kAh Net Demand Amps Demand Amps Max Demand Watts Demand Watts Max Demand VAR Demand VAR Max Demand VA Demand VA Max Projected Demand I Projected Demand W Projected Demand VAR Projected Demand VA Load Factor I Load Factor W Load Factor VAR Load Factor VA
Oldest
Amps L1 % Unbal Current VA Ave 3 Ph Amps L2 Pos Seq Volts Demand I Amps L3 Neg Seq Volts Demand W Average Amps % Unbal Volts Demand VAR Volts L1-N Average Frequency Demand VA Volts L2-N Watts L1 Projected Demand I Volts L3-N Watts L2 Projected Demand W Volts Ave L-N Watts L3 Projected Demand VAR Volts L1-L2 Watts Ave 3 Ph Projected Demand VA Volts L2-L3 VARS L1 True PF L1 Volts L1-L3 VARS L2 True PF L2 Volts Ave L-L VARS L3 True PF L3 Freq VAR Ave 3 Ph Total True PF Amps N VA L1 Disp. PF L1 Pos Seq Current VA L2 Disp. PF L2 Neg Seq Current VA L3 Disp. PF L3
Total Disp. PF Dist. PF L1 Dist. PF L2 Dist. PF L3 Total Dist. PF IEEE THD L1 V IEEE THD L1 I IEEE THD L2 V IEEE THD L2 I IEEE THD L3 V IEEE THD L3 I IEEE THD L4 I IEC THD L1 V IEC THD L1 I IEC THD L2 V IEC THD L2 I
IEC THD L3 V IEC THD L4 I Crest Factor L1 V Crest Factor L1 I Crest Factor L2 V Crest Factor L2 I Crest Factor L3 V Crest Factor L3 I Crest Factor L4 I
(1) Voltage THD and Crest Factor Voltage are omitted for neutral channel. (2) Parameters displayed depend on the wiring mode. (3) Individual phase parameters are omitted in delta wiring modes. (4) Load factor parameters are available only on M6 and M8 modules.
40
Chapter 3
Configuration Menu
Level 3
Basic Advanced Native Comm.
Protocol Delay Baud Address Format
Optional Comm.
DST
Setpoint(6) 1..n
Type Evaluation High Limit Low Limit Pickup Del. Dropout Del. Output Action Accumu. Time (5) Status
Min/Max Log
Enable/Disable Min/Max Log
Event Log
Log Status Input Changes
Wiring Mode PT Primary PT Secondary CT Primary CT Secondary I4 Primary I4 Secondary Nominal Sys Voltage (7)
Level 2
New Password Demand Period Length # Of Demand Periods Forced Demand Delay Projected Demand Type KYZ Control Source KYZ Pulse Scale KYZ Pulse Width Relay Control Source Relay Pulse Scale Relay Pulse Width RMS Resolution RMS Averaging Frequency Averaging Date Format Date Time Relay State on Comms Loss(8) KYZ State on Comms Loss(8) Watch Dog Action DM Scroll Rate Energy Digits
Enable Start Month Start Day Start Day Inst. Start Hour End Month End Day End Day Inst. End Hour
Display Configuration
Display Status
Program Commands
L1 L2 L3 N
Program Configuration
L1 L2 L3 N
L1
Catalog Number Accuracy Class WIN Number Hardware Revision Master Module FRN Device ID Selftest Status Code Flash RAM Data Flash NVRAM Data Acquisition Watchdog Timer Clock Optional Comms (Version Number, Identifier Type, Status) DM Status DM FRN Date Time Relay Status KYZ Status S1 Status S1 Count S2 Status S2 Count Output Word
L2 Force Relay L3 Force KYZ N Clear Min/Max Log Clear kWH Counter Clear kVARH Counter Clear kVAH Counter Clear Amp H Counter Clear All Energy Counters Clear S1 Counter Clear S2 Counter Restore Defaults Clear Setpoint Timers
(5) In Program Mode, this entry becomes Clear Accumulated Time. (6) 1..10 (M4, M5) or 1..20 (M6, M8). (7) Available on M6 and M8 only. (8) Applies to EtherNet/IP, ControlNet, DeviceNet and remote I/O neworks only.
41
Chapter 3
Displaying Information
The display screen consists of two rows of five alpha-numeric LED digits. At the right of this screen is a column of phase indicators: L1, L2, L3 and N. These indicators show which phase (or phases) is referred to by the information being displayed on the 2x5 screen. The phase indicators also indicate program mode by flashing.
Power Up
When the display module powers up, it first illuminates all of its LED indicators for approximately 2 seconds. It then displays its firmware revision number:
.. .
After about 2 seconds, the display waits for communication with the master module. If it doesnt receive any messages within 8 seconds, it displays:
At any time, if the display module stops receiving information from the master module, it displays the Check Rx message. If it is receiving messages but not able to send messages (it determines this from a lack of response from the master module), the display module displays:
Once the display module begins communicating with the master module, it displays it on the screen and the Check Rx or Check Tx messages disappear. No operator intervention is required to clear these messages.
42
Chapter 3
Scrolling
When messages are too large to fit on the display, a scrolling mechanism is employed. The message scrolls horizontally. The default scroll rate was chosen to give you enough time to see the message but not take too much time to show the entire message. You may select from two different scroll rates by using the Advanced Configuration Menu on the display module. Take care to see the entire message before taking any action as some of the messages are very similar and differ only by a few characters.
Editing a Parameter
Follow these steps to edit a parameter by using the display module. 1. Using the display module keys, move into Program mode and display the parameter to be modified. Notice the flashing phase indicators on the right-hand side of the screen.
Edit Mode
PT.SEC 120
Powermonitor 3000
L1 L2 L3 N
2. Set the display module into Edit mode by pressing the Enter key. Notice that the phase indicators on the right side turn-on solid and the parameter being modified is now flashing.
Parameter Change
Powermonitor 3000
PT.SEC 250
L1 L2 L3 N
43
Chapter 3
3. Change the value of the parameter by pressing the Up Arrow and Down Arrow keys until the desired parameter value is displayed. Notice the phase indicators on the right-hand side remain solid and the parameter being modified is still flashing. 4. After the desired parameter value is displayed, press the Enter key to write the new value to the master module and set the display module back to Program mode. Notice the phase indicators on the right-hand side are now flashing and the parameter being modified is now solid. If you begin to edit the wrong parameter, press the Escape key. This returns the original parameter value, does not modify the master module, and returns the display module to Program mode. Notice the phase indicators on the right-hand side are flashing again, and the parameter being modified is now solid.
Issuing Commands
The display module allows you to issue commands to the power monitor. These commands include relay and KYZ output forcing; clearing the Min/Max Log; clearing energy and amp-hour counters, status input counters and setpoint counters, and restoring the factory defaults. To issue a command, you must enter Program Mode and enter the correct unit Password.
44
Chapter 3
ATTENTION
The relay and KYZ outputs may be connected to field devices. Before issuing a command to force an output, ensure that any devices connected to outputs cannot operate in an unsafe or undesired manner. Failure to follow these instructions may result in personal injury or death, property damage, or economic loss.
1. Using the four display module keys, move into Program mode and display the command to be issued. Notice the flashing phase indicators on the right-hand side.
Program Mode
FORCE UP-DN
Powermonitor 3000
L1 L2 L3 N
2. Set the display module into Edit mode by pressing the Enter key. Notice that the phase indicators on the right-hand side are now solid and the command option prompt is now flashing.
Edit Mode
RELAY UP-DN
Powermonitor 3000
L1 L2 L3 N
45
Chapter 3
3. Choose the option of the command by pressing the Up Arrow and Down Arrow keys until the desired option is displayed. Notice the phase indicators on the right-hand side remain solid and the command option being selected is still flashing.
Command Option
LAY-1 Energ
Powermonitor 3000
L1 L2 L3 N
4. After the desired command option is displayed, press the Enter key to execute the command. The selection prompt reappears and the display module is set back to Program mode. Notice the phase indicators on the right-hand side are flashing again and the option prompt is now solid.
Program Mode
FORCE UP-DN
Powermonitor 3000
L1 L2 L3 N
To abort a command, press the Escape key. The display module returns to Program mode and the option prompt is displayed again. Notice the phase indicators on the right-hand side are now flashing and the option prompt is now solid.
46
Chapter 3
Commands Parameter Force Relay Description Forces relay to a known state in which the relay remains at that state until the force is removed. Forces KYZ to a known state in which the relay remains at that state until the force is removed. Resets the Min/Max log with the current real time metering information. Resets the kWh net counter to zero. Resets the kVARh net counter to zero. Resets the kVAh net counter to zero. Resets the Ah net counter to zero. Resets all cumulative energy counter to zero. Resets Status 1 counter to zero. Resets Status 2 counter to zero. Restores all settings to factory default. Clears the time accumulated in each setpoint timer. Range De-energize Energize No Force De-energize Energize No Force Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No
Force KYZ
Clear Min/Max Log Clear kWh Counter Clear kVARh Counter Clear kVAh Counter Clear Ah Counter Clear All Energy Counters Clear S1 Counter Clear S2 Counter Restore Defaults Settings Clear Setpoint Timers
The display module provides an inexpensive, easy-to-operate method for setting up power monitor parameters to adapt it to your power system and select the performance options you desire. You configure the power monitor by using Program mode and Edit mode of the display module. You may also configure the power monitor via communication, and certain advanced features of the power monitor may be configured only via communication. Please refer to the appropriate sections of the user manual for more information.
47
Chapter 3
Refer to the Device Configurations Summary table on page 50 for a summary of basic and advanced device configuration settings. You may use a copy of this table to record your configuration settings.
Wiring Mode
Select the wiring mode to match the physical configuration of your power system. Your wiring mode choice must match the wiring diagrams found in the Powermonitor 3000 Unit Installation Instructions, publication 1404-IN007, for proper operation and accuracy. Your choices include the following: Delta 3 CT Delta 2 CT Direct Delta 3 CT Direct Delta 2 CT Open Delta 3 CT Open Delta 2 CT Wye (default) Single Phase Demo
You may choose Demo mode for training or demonstration purposes. In Demo mode, the power monitor returns internally generated results.
48
Chapter 3
PT and CT Ratios
You may directly connect the voltage inputs of the power monitor to power systems rated at 600V line-to-line or less. Above 600V, you need potential transformers (PTs) to step down the power system voltage to one that is measurable. Most commercially available PTs have a secondary rated voltage of 120V (150V full-scale). Nearly every power monitor installation requires CTs to step down the power system current to a value of 5 A full-scale. To perform basic configuration, set the primary and secondary voltage and current ratings of your PTs (if used) and CTs. If your system configuration includes a neutral current CT, you need to separately configure the I4 CT ratio. PT primary: range 110,000,000, default 480 PT secondary: range 1600, default 480 CT primary: range 110,000,000, default 5 CT Secondary: range 15, default 5 I4 primary and I4 secondary: same as CT primary and secondary
For direct connection to power systems of 600V, set the PT ratio to 600:600. For a 480V system, set the PT ratio to 480:480.
TIP
When setting a parameter, you may press and hold the up arrow or down arrow key for a few seconds to increase the rate the value increments or decrements.
Refer to the Powermonitor 3000 Installation Instructions, publication 1404-IN007, for information on selecting and installing PTs and CTs.
49
Chapter 3
Password
The password protects the unit against unauthorized commands or configuration changes. Be sure to write down the new password and keep it in a safe place. Range 09999, default 0000.
TIP
If you forget or lose your password, contact Rockwell Automation Technical Support for assistance. Refer to Rockwell Automation Support on the back cover of this manual.
Device Configurations Summary Parameter Wiring Mode Range 0 = Delta 3 CT 1 = Delta 2 CT 2 = Direct Delta 3 CT 3 = Direct Delta 2 CT 4 = Open Delta 3 CT 110,000,000 1600 110,000,000 1 5 110,000,000 1 5 110,000,000 5 = Open Delta 2 CT 6 = Wye 7 = Single Phase 8 = Demo Default 6 = Wye User Setting
Basic Configuration
PT Primary PT Secondary CT Primary CT Secondary I4 Primary I4 Secondary Nominal System Voltage (M6 and M8 only)
50
Chapter 3
Device Configurations Summary Parameter New Password Demand Period Length Number of Demand Periods Forced Demand Delay Predicted Demand Type Range -19999 -9999 115 0900 s Instantaneous 1st Order 2nd Order 0 = None 1 = Wh Forward 2 = Wh Reverse 3 = VARh Forward 4 = VARh Reverse 130000 0, 402000 Same as KYZ 130000 0, 402000 Nominal / High Default 0000 15 1 10 Instantaneous User Setting
7 = Setpoint
Advanced Configuration
KYZ Pulse Output Scale KYZ Pulse Output Width Relay Control Source Relay Pulse Output Scale Relay Pulse Output Width RMS Resolution RMS Averaging Frequency Averaging Date Format Date: Year Date: Month Date: Day Time: Hour Time: Minutes Time: Seconds Default relay state on comms loss Default KYZ state on comms loss Wdog action Display Module Scroll Speed Energy counter rollover point Metering Result Set (M8 only(1))
On / Off On / Off MM/DD/YYYY DD/MM/YYYY 19982097 112 131 023 059 059 0 = Last state/resume 2 = De-energize/resume 1 = Last state/freeze 3 = De-energize/freeze 0 = Halt 1 = Continue Fast / Slow 415 digits 0 = All results 1 = Transducer mode 2 = Energy meter mode
(1) (2)
Metering result set parameter may only be configured by using communication. Factory default for RMS Resolution is Nominal for the M4 and High for the M5, M6 and M8.
51
Chapter 3
Demand Setup
You may configure the demand period length, the number of demand periods to average for demand calculation, the forced demand delay and the type of calculation used for projected demand. Demand Period Length sets the length in minutes (199) of the demand period used for demand and projected demand calculation. Range 9999, default 15. A positive value (other than 0) configures the power monitor to use its internal clock to measure the demand period. A setting of zero (0) configures the power monitor to use an external synchronizing method to synchronize the demand interval. A negative value configures the power monitor to use its internal clock for calculating projected demand and an external synchronizing method to calculate actual demand. External synchronizing methods include: A dry contact end-of-interval pulse connected to status input #2 For Ethernet network units, a network demand sync broadcast message from a network demand master power monitor or a controller command message from a PLC controller. Refer to Network Demand / Time Configuration on page 55 for more informatin on network demand synchronization. TIP
In RSEnergyMetrix RT software and RSPower software, a negative demand interval is set by checking a checkbox entitled Use Status Input #2 or Enable External Demand Sync.
Number of Demand Periods specifies how many demand intervals are averaged together to a floating window demand calculation. For instance, to configure a 30 minute floating window, specify 2 as the demand period length and 15 as the number of demand periods. Range 115, default 1. Forced Demand Delay is a timeout setting that waits for x number of seconds before ending a demand period when the external demand sync input function is being used. When a missed external demand sync is detected the unit: forces an end to the current demand period. records an event log record of the event. records a trend log record if the trend log interval is set to -1. (Sync with demand setting)
52
Chapter 3
sends out a demand sync broadcast when configured as a Master (Ethernet units). starts the projected demand calculations from the beginning again. Entering a value of 0 disables this function. For more information about this feature read the section Network Demand / Time Configuration on page 55. Projected Demand Type specifies the type of calculation used for projected demand. Selections include the following: Instantaneous (default) First-order Second-order
The Pulse output scale factor sets the number of measurement increments per pulse. Range 130,000, default 10. The Pulse output width parameter determines the pulse width in milliseconds. Range 402000 or 0 to transition the output KYZ-style. Default is 0.
53
Chapter 3
Metering Options
Configuration parameters RMS Result Averaging, RMS Resolution and Frequency Averaging allow you to make choices to fit the power monitor more closely to your application needs. The default settings are to average 8 RMS and frequency calculations, providing a smoother result, and to sample at a high rate, providing greater accuracy where significant harmonics are present. Refer to the discussion of these parameters in Metering Functionality at the beginning of this chapter.
54
Chapter 3
55
Chapter 3
Ethernet units also support synchronization of their internal clocks from up to three SNTP servers, at a configurable synchronization interval. Since SNTP servers operate in UTC (Universal Coordinated Time), a time zone for the power monitor must also be configured for the correct time to be set. The time zone is configured as an offset in hours from UTC (formerly known as GMT). To enable network demand synchronization, the demand period parameter in the advanced configuration table must be set to zero or a negative number. Refer to page 52 for more information. If using RSEnergyMetrix RT option or RSPower software for configuration, the checkbox Use Status Input #2 or Enable External Demand Sync must be checked. You may configure network demand and time synchronization options by using the display module, or by using communication, by writing to the Network Demand Sync and Time Configuration table.
Input Mode
Sets the unit network time sync mode. Range: 0 = Master command input, 1 = Master status 2 input, 2 = Slave broadcast input, 3 = Slave status 2 input (default)
Broadcast Port
Sets the UDP port number for the master slave configuration. Range 300400, default 300
Time IP Address
The IP address of the primary SNTP server, accessed as the 1st 4th octet
Time-set Interval
Determines how often the unit time is automatically set, in seconds. Range: 032,766. 0 = Disables the time set function, Default = 60
56
Chapter 3
SNTP Address 2
The IP address of the primary SNTP server, accessed as the 1st4th octet.
SNTP Address 3
The IP address of a third SNTP server, accessed as the 1st4th octet.
Network Demand/Time Configuration Summary Parameter Name Input mode Broadcast port number Time server IP address-byte 1 Time server IP address-byte 2 Time server IP address-byte 3 Time server IP address-byte 4 Time zone Time set update interval SNTP IP address 2, octet 1 SNTP IP address 2, octet 2 SNTP IP address 2, octet 3 SNTP IP address 2, octet 4 SNTP IP address 3, octet 1 SNTP IP address 3, octet 2 SNTP IP address 3, octet 3 SNTP IP address 3, octet 4 Range 03 300400 0255 0255 0255 0255 -1212 032766 0255 0255 0255 0255 0255 0255 0255 0255 Default 3 300 0 0 0 0 0 60 0 0 0 0 0 0 0 0 User Setting
Controller Command
The Controller Command table is a write table consisting of one integer element. A 1 written to bit 0 signals the end of a demand period. When this occurs, the master power monitor resets this bit to 0 and sends the end of demand broadcast to power monitor units configured as Slave broadcast input. Bits 115 are reserved.
57
Chapter 3
DST Enable
Enables the daylight saving time function. Range 0 = disable, 1 = enable
58
Chapter 3
DST is disabled by default. When enabled, the default start time is 2:00 a.m. on the second Sunday in March, and the default end time is 2:00 a.m. on the first Sunday in November. This corresponds to US Daylight Saving Time beginning in 2007.
Daylight Saving Time Configuration Summary Parameter Name DST Enable DST Start Month DST Start Day DST Start Day Instance DST Start Hour DST End Month DST End Day DST End Day Instance DST End Hour Range 01 112 06 15 023 112 06 15 023 Default 0 3 0 2 2 11 0 1 2 User Setting
59
Chapter 3
The metering update rate is a measure of how often the power monitor calculates new metering results. The metering update rate is not significant in most applications, but can be important in some control applications. The metering update rate affects how quickly a setpoint can respond to an electrical event and affects how often new metering results are available for communication. The metering update rate is dependent on the power monitor model and device configuration. The table below contains information that can be used to calculate the metering update rate for a specific model containing specific configuration selections.
Metering Update Rate Calculation Based on Model and Device Configuration Model and Config Options Base metering update rate If device is an M4 If RMS Resolution = High (see the Advanced Device Configuration table) If catalog # contains ENT, CNT, or DNT If the Min/Max log is enabled (see the Min/Max Log Configuration/Read-back Select table) If more than 5 setpoints are configured If Oscillography is enabled (see the Oscillograph Configuration/Read-back Data Select table) If Transient detection is enabled (see the Transient Analysis Configuration/Read-back Select table) If Meter Result Set is set to Tranducer mode or Emergy Meter Mode (see the Advanced Metering Configuration table) M4 M5 M6 M8 Update Rate 50 ms Add 10 ms Add 10 ms Add 5 ms Add 5 ms Add 5 ms Add 5 ms Add 15 ms
Subtract 5 ms
This table lists the minimum and maximum possible metering update rate for each model based on information from the Metering Update Rate Calculation table.
Min and Max Metering Update Rate for Each Model Model Min and Max Metering Update Rate 6085 ms 5075 ms 5080 ms 4595 ms
Publication 1404-UM001F-EN-P - November 2009
M4 M5 M6 M8
60
Chapter 3
Out-of-the-box metering update rates are based on factory-default configuration data and are listed in the Meter Update Rate with Factory Default Configuration table for all power monitor models and communication options. Factory default settings for configuration parameters can be found in Appendix A.
Meter Update Rate with Factory Default Configuration Model Communication Option 000, 232, ENT, RIO CNT, DNT M4 M5 M6 M8 60 ms 60 ms 65 ms 80 ms 65 ms 65 ms 70 ms 85 ms
61
Chapter 3
62
Chapter
Communication
The communication features of the Powermonitor 3000 unit make it uniquely suited to integrate electric power usage information into your industrial control and information systems. Every power monitor is equipped with a native RS-485 communication port, and you can select optional communication that facilitate seamless integration with a variety of industrial networks. The optional communication choices include the following: Serial - an RS-232 communication port Remote I/O - allows you to connect your power monitor as a quarter rack to any remote I/O scanner device DeviceNet - a port with standard DeviceNet functionality lets your power monitor integrate into an open-standard, multi-vendor architecture Ethernet - a standard 10BaseT port allowing easy integration into factory-floor and office information systems ControlNet - with NAP port and two BNC connectors for connection to single or redundant media applications This chapter covers configuration and operation of the native and optional communication ports. Refer to the Installation Instructions, publication 1404-IN007, for installation, wiring and connection instructions.
Configuring Communication
The display module is the recommended way to configure communication on your power monitor. The display module includes setup menus for native and optional communication. If you need to, review Configuration by Using the Display Module on page 47. You may also configure communication parameters by using the native or optional communication ports. However, because this may lead to loss of communication with the port being configured, we recommend using the display module for initial communication configuration.
63
Chapter 4
Communication
If you choose to configure communication parameters by using communication, please refer to the Native Communication Configuration table and the Optional Communication Configuration Parameters table in Appendix A.
TIP
The native communication port does not support Data Highway 485 (DH-485) communication. Although DH-485 uses the RS-485 physical media, its protocol is not compatible with the DF1 protocol.
64
Communication
Chapter 4
Native Communication Configuration Summary Parameter Protocol Description Range DF1 Full-duplex DF1 Half-duplex Slave Modbus RTU Slave Auto-Sense Time between receiving a request and transmitting a response RS-485 port communication bit rate 075 ms Default Auto-Sense User Setting
Delay
10 ms
Communication Rate
1.2 Kbps 2.4 Kbps 4.8 Kbps 9.6 Kbps 19.2 Kbps 38.4 Kbps 57.6 Kbps 1247
9600 baud
RS-485 Address
Uniquely identifies the Powermonitor device on a multi-drop network Data bits / Stop bits / Parity Mimimum delay between characters that indicates end of Modbus message packet
Unit ID number
Data Format
8 / 1 / none
Inter-Character Timeout
Error Checking
BCC, CRC
CRC
65
Chapter 4
Communication
The RS-232 communication standard supports point-to-point communication between TWO stations or nodes, with a maximum cable length of 15.24 m (50.0 ft). You may not use the optional RS-232 port and the native RS-485 port at the same time.
Optional RS-232 Communication Configuration Summary Parameter Port Protocol Description Select active serial port Range RS-232 RS-485 Default RS-232 User Setting
DF1 Full-duplex Auto-Sense DF1 Half-duplex Slave Modbus RTU Slave Auto-Sense Time between receiving a 075 ms request and transmitting a response 1.2 Kbps 2.4 Kbps 4.8 Kbps 9.6 Kbps 19.2 Kbps 38.4 Kbps 57.6 Kbps 1247 10 ms
Delay
9600 baud
Node Address
Uniquely identifies the Powermonitor device on a multi-drop network Data bits / Stop bits / Parity RS-232 hardware flow control
Data Format
Mimimum delay between 0 to 6553 ms characters that indicates end of Modbus message packet BCC, CRC
Error Checking
66
Communication
Chapter 4
3. When presented with the configuration screen you may use the auto configure feature or enter your own configuration.
67
Chapter 4
Communication
To use the auto configure you must first select the device as SLC-CH0/Micro/PanelView.
4. Click Auto Configure to start the process. The configuration returns with the following message. This message can be disregarded. Recognition of the device is provided after exiting the auto configuration routine.
68
Communication
Chapter 4
6. Return to the main browsing window of the RSLinx application and browse to the DF1 Driver for the Powermonitor 3000 unit. The result is an established communication link between the application and the powermonitor.
69
Chapter 4
Communication
TIP
For a logical rack address of 63 decimal, do not use group number 2, 4, or 6. Power monitor logical rack addresses are expressed in decimal. You may need to convert addresses to octal (range 077) for some PLC applications.
Optional Remote I/O Port Configuration Summary Parameter RIO Rack Address RIO Group Number Description Logical rack address as configured in the scanner Range Default User Setting
063 decimal 1
Logical group number 0 = 1st quarter 0 = 1st quarter of quarter rack 2 = 2nd quarter 4 = 3rd quarter 6 = 4th quarter Indicates highest-numbered logical rack / group address (PLC-2 based systems only) 0 = No 1 = Yes 0 = No
0 = 57.6 Kbps
70
Communication
Chapter 4
71
Chapter 4
Communication
TIP
Some legacy power monitor units with optional DeviceNet communication do no support remotely settable node addressing, AutoBaud, or Program Baud. You can check whether your power monitor supports these functions by viewing the Optional Communication Card status by using your display module. Communication type 81 does not support these functions, type 88 does. You may also view this status item by a read of assembly instance 23, element 25.
Optional DeviceNet Communication Configuration Summary Parameter Node Address Baud Rate Description DeviceNet node number (MAC ID) DeviceNet Communication Rate Range 064 decimal Default 63 User Setting
0 = 125 Kbps 0 = 125 Kbps 1 = 250 Kbps 2 = 500 Kbps 3 = Autobaud 4 = Program Baud
Bus-off Interrupt
0 = Hold in Reset Specifies response 0 = Hold CAN to a CAN bus-off chip in reset interrupt 1 = Reset CAN chip and continue
72
Communication
Chapter 4
Configure the Powermonitor 3000 Unit by using RSNetworx for DeviceNet Software
TIP
The DeviceNet network is an open-standard, multi-vendor communication network. Although other vendors offer DeviceNet configuration tools, all examples in this manual will depict the use of Rockwell Software RSNetWorx for DeviceNet software.
1. Launch RSNetWorx for DeviceNet software. At this point, the DeviceNet scanner module does not know what device to scan. 2. Click Online to list the available devices on the network.
73
Chapter 4
Communication
74
Communication
Chapter 4
4. Read the scanners configuration. Right-click on the DeviceNet scanner icon and upload the scanners present configuration.
5. Edit the Scanner List. The DeviceNet scanner needs to know how the information is coming from the Powermonitor 3000 unit. Select the Scan List tab and move the power monitor into the Scanlist set.
75
Chapter 4
Communication
The DeviceNet scanner needs to know which bytes are scanned from the power monitor. Select the Input tab. This lets you determine where the information is stored inside the scanner module. When finished configuring, click Apply.
7. Click Download to Scanner. All of the configuration data must be downloaded to the scanner module.
76
Communication
Chapter 4
Afterwards, the DeviceNet scanner displays an 80, followed by a 00 when everything is configured properly.
TIP
Powermonitor 3000 units Input parameters are Instance 1 and output parameters are Instance 2.
77
Chapter 4
Communication
IMPORTANT
The IP address for your power monitor must not conflict with the IP address of any other device on the network. Contact your network administrator to obtain a unique IP address for your unit.
The IP address is a 32-bit binary number, which consists of the network address (NetID) and the machine address (HostID). The Subnet Mask defines the boundary between the NetID and HostID in the IP address. Each 1 bit in the subnet mask represents the NetID and each 0 represents the HostID. Here is an example.
78
Communication
Chapter 4
In this example, the NetID is 192.1.1.0 and the HostID is 0.0.0.207. The relationship between NetID and HostID depends on the IP address class, the discussion of which is beyond the scope of this document (the example uses a Class C IP address). Devices on the same subnet can communicate directly; devices on different subnets may communication with each other only through a gateway or router. The Gateway IP Address defines the address of the gateway or router on the units subnet that is used to route messages to other subnets for wide-area networking. Default: 128.1.1.1.
Optional Ethernet Communication Parameter Description IP Address Unit IP address in format Bytes 14 aaa.bbb.ccc.ddd. Subnet Mask Bytes 14 Subnet mask in format aaa.bbb.ccc.ddd Range 0255 decimal, each byte 0255 decimal, each byte 0255 decimal, each byte Default 192.168.254.UnitID User Setting
255.255.255.0
128.1.1.1
79
Chapter 4
Communication
Through communication, the power monitor becomes an effective source of power and energy data to enterprise information and automation systems. This section of the manual provides an overview of data messaging with the power monitor. Following the overview, discussions will focus on the details of messaging using specific communication types (for example, serial, remote I/O, DeviceNet, and Ethernet). The power monitor is a read/write data server. It does not initiate data messages, but responds to messages from client devices. Its data is organized in data tables similar to those found in a SLC 5/03 programmable controller. The primary methods to communicate with a power monitor include the following: Table Writes - A client may write a table of data to the power monitor. Generally, only full data tables may be written. Data writes may be performed to configure device features, set the date and time, reset or preset energy counters, and select records for subsequent reads. Single Element Writes - Beginning with version 4 master module firmware, a client may enable single-element writes by writing a valid password to the Single Element Password Write table. Single element writes are disabled again after 30 minutes of inactivity. Simple Data Reads - A client may read metering or configuration data. The client may read an entire data table or any number of consecutive data elements up to the table boundary. Indexed Data Reads - The power monitor parses large data structures such as logs, oscillograms, harmonics and transient captures into data blocks, records and/or channels. These records are transferred to an interface table. The client selects the read-back mode and/or record, reads the interface table and reassembles the original data structure. I/O Type Communication - The power monitor supports polled, change-of-state and/or cyclical implicit I/O messaging, depending on the communication options. The specific communication setup depends on the communication port type and protocol, whether serial, Ethernet, or others, as well as the type of device controlling the communication. The following sections provide more detail.
80
Communication
Chapter 4
IMPORTANT
For remote I/O communication, a unique Block Transfer Size identifies the data table to read or write using a Block Transfer instruction. For optional DeviceNet and EtherNet/IP communication, a CIP (Control and Information Protocol) Assembly Instance identifies the data table. Data Access - Data tables may be read-only or read/write. Number of Elements - the number of unique data values contained in the table. The number of words or bytes this represents depends on the data type. Data Type - Specified as floating-point or integer. Each floating-point element consists of two 16-bit words or four 8-bit bytes of data. Each integer element consists of one word or two bytes. User-configurability - This attribute determines whether you may configure the content and/or length of the data table.
81
Chapter 4
Communication
Lets look at the Date and Time table as an example. CSP file number: N11 Remote I/O BT length: 12 CIP assembly instance: 6 (Write) or 7 (Read) Data table name: Date and Time Data access: Read/write Number of elements: 8 Data type: Integer User-configurable: No
The power monitor data tables are listed in Appendix A. The table on page 188 shows a summary of all the data tables.
82
Communication
Chapter 4
Timestamp format. The power monitor expresses timestamps in an array of four data table elements: Year, Month/Day, Hour/Minute, Second/ Hundredth of a second Each timestamp parameter (except the Year) is a combination of its first and second element. For instance, the Month is the parameter value divided by 100 and the remainder is the Day. Example: 1230 = December 30th. The timestamp data type may be integer or floating-point and depends on the data table.
83
Chapter 4
Communication
A valid write to a data table must meet the following general criteria: The length of the source data array must equal the data table length. Note that the same data table may have a different length in various power monitor models. The entire data table must be written in one pass. The first element in the source data array must generally contain the correct password (or a value of -1 for read-back data selection). The source and destination data type must match, for example, floating point or integer. Each element of the source data array must be within the legal range listed in the data table specification. Reserved elements must be the correct value, usually 0. For DeviceNet optional communication only, each consecutive write must be unique. You may read the Write Error Status table after writing to a data table to verify that the write was valid and accepted by the power monitor. If there was an error in the last write, the Write Error Status indicates the CSP file or assembly instance (DeviceNet network only) number and the offending element number. You may write data to the power monitor for basic and advanced device configuration, to set the time and date, to set up setpoints, logs, oscillography and transient analysis, and to select records to be read back from indexed data reads such as harmonics, oscillography and logs.
84
Communication
Chapter 4
Allen-Bradley
Powermonitor 3000
Data
Element 0 1
85
Chapter 4
Communication
86
Communication
Chapter 4
87
Chapter 4
Communication
IMPORTANT
The client selects the read-back mode by writing to the Read-back Mode element in the appropriate read-back select table. The Auto-increment mode provides the highest data throughput. In Manual Increment mode, the client must alternate writes of the read-back select table with reads of the read-back table. The Indexed Data Read, Manual Mode Flow Diagram shows the flow of alternating writes and reads required for the Manual Increment mode. First, the client writes to the appropriate read-back select table to identify the desired data block, record or channel. For selecting a read-back record, the client may write either a valid password or a value of -1 to the password element in the read-back select table After a short time delay, the client reads the results table, verifies that it is the desired record and adds it into the target data structure. The client repeats steps 1 and 2 until all the desired data is read.
88
Communication
Chapter 4
Refer to Chapter 5, Setpoint Programming and Operation; Chapter 7, Data Logging; and Chapter 8, Advanced Features for details of indexed mode data reads for each of these functions.
89
Chapter 4
Communication
The power monitor supports a number of different communication networks and protocols. Each of these has unique characteristics and methods. The information in this section is provided to assist you in designing and implementing data messaging with the power monitor by discussing in detail the unique properties of the communication options. Refer also to the Sample ladder diagrams in Appendix C.
90
Communication
Chapter 4
Chapter 4
Communication
IMPORTANT
Because the floating-point word order in the ControlLogix controller is reversed from that in the power monitor, your ladder logic needs to reverse the word order so the data may be interpreted correctly. The swap byte (SWPB) instruction performs this function.
Because of the DF1 protocols inherent handshaking, the completion of each message may be used to activate the next message, without any additional programmed delay.
92
Communication
Chapter 4
The power monitor does not initiate Modbus commands but responds to commands sent by the Modbus master. The following Modbus function codes are supported: 03 Read Holding Registers 04 Read Input Registers 16 Write Multiple Holding Registers 08 Diagnostics 00 Echo Command Data 02 Return Diagnostic Counters 10 Clear Diagnostic Counters 06 Write Single Holding Register Function 06, 16 and the sub function 10 of function 08 support Broadcast packets. Refer to Appendix A for Modbus addresses of the power monitor data tables. The power monitor supports zero-based addressing. The address ranges are arranged as follows (note that not all addresses in the range are used): 30,00140,000 Modbus Input Register (Analog Input) Address Space 40,00150,000 Modbus Holding Register (Analog Output) Address Space The Modbus protocol supports four types of data: Discrete Input, Coil, Input Register and Holding Register. The power monitor supports Input Registers (read-only) and Holding Registers (read-write or write only). Input Registers and Holding Registers are 16 bits long. Floating point values in the data tables are represented as big-Endian two-register arrays in IEEE-754 floating point format. The Modbus client application must be able to reassemble the two-word array into a valid floating-point value. The power monitor returns the Modbus error codes shown in the table below when appropriate. In the event of an exception reply, not only is the exception code sent to the master device, but also the power monitor slaves diagnostic counter records the error code to further explain the error reason.
93
Chapter 4
Communication
The data table number of error request and element offset of error request in the Write Error Status table is updated with the first Modbus address of the table and element offset that the incoming request packet attempts to write to.
Modbus Error Codes Error Code 0 1 2 3 4 5 6 7 8 9 Description Meaning Response Exception Code None Nothing transmitted 1 3 3 3 2 3 3 2
No error. Function Code The function does not support Broadcast. cannot Broadcast. Function Code not The controller does not support this supported. Modbus function or sub-function. Bad Command Length Bad Length Bad Parameter Bad Table Number Bad Modbus Address Table Write Protected Table Access Denied The Modbus Command is the wrong size. The function attempted to read/write past the end of a data file. The function cannot be executed with these parameters. The table number does not exist. The function attempted to access an invalid Modbus address. The function attempted to write to a read-only table. Access to this table is not granted.
If a client device requests too large a data size, the power monitor returns the requested data padded with zeroes up to the requested data size rather than returning an error. When the User-configured Table Setup table is used together with Modbus, the value for element 1 should be 1000. The value for element 0 of the Write Error Status table is the first Modbus address of data table written to last. For function code 03, 04, and 16, the number of words of user data is limited to 100. If it is over 100, exception code 3 will be returned to the master and error code 3 occurs.
94
Communication
Chapter 4
For function code 16, if the data length is larger or less than the element number of the data table accessed, error code 4 occurs. It means the data length for function code 16 should be strictly the same as the size of the accessed data table. If the data written to the power monitor by using function code 16 is outside of the legal range as shown in Appendix A, error code 5 occurs. For function code 03, 04, and 16, if any undefined starting address is sent to the power monitor, exception code 2 is returned and error code 6 occurs. If the starting addresses other than the first Modbus address of the data tables are sent to the slave with function code 16, this error code also occurs. For function codes 03 and 04, the starting address may be any address within the data table. However, for floating point data tables, one element occupies two Modbus addresses. Therefore, only odd Modbus address are allowed when accessing floating point data table. If the starting address is even, error code 7 occurs. The Controller Command table is the only one table that has write only attribute. If you try to use function code 03 to read this table, error code 8 occurs and a 02 exception response packet is returned.
95
Chapter 4
Communication
I/O Messaging
The power monitor supports polled, change-of-state and cyclic I/O messaging by using assembly instances 1 for input data and 2 for output data. The default input messaging table size is 6 integer elements and the output table size is 2 integer elements. This corresponds to a DeviceNet scanner mapping of 12 Rx and 4 Tx bytes. See the Remote I/O, DeviceNet, EtherNet/IP and ControlNet I/O Messaging Parameters table on page 191 for the contents of the default I/O messaging tables.
TIP
You may reconfigure the input messaging table (instance 1) by selecting up to 23 integer or 14 floating-point parameters through a table write to assembly instance 35. Refer to User-configured I/O on page 122. If you change the size of the input table, you must also re-map the inputs into the DeviceNet scanner by using RSNetworx for DeviceNet software.
96
Communication
Chapter 4
Polled I/O messaging can automatically provide fresh data at update rates as fast as 100 ms. The power monitor supports both Every Scan and Background polled messaging. You select the poll type and polling rate by using RSNetworx for DeviceNet software. Every Scan: Polls the power monitor once per scan. Set the Interscan Delay to at least 100 ms. An Interscan Delay of less than 100 ms slows the power monitors delivery of metering information. Background: Polls the power monitor at intervals you specify by using the Foreground to Background Poll Ratio. So long as the power monitor is polled no more frequently than every 100 ms, it operates and communicate at its optimal rate. You may calculate the total scan time with this formula.
Change of State I/O messaging (COS) reports data only when the content of the I/O table changes. COS messaging can be more efficient for discrete applications because it tends to reduce the network traffic. If you have configured the input message table to include metering data, however, COS may reduce the network efficiency because the data constantly changes. Cyclic I/O messaging reports data periodically according to a time increment you configure. COS and Cyclic messaging typically reduce the network bandwidth loading compared with Polled messaging. To optimize explicit messaging performance, use a Background Polled I/O connection with a high foreground to background poll ratio. To help obtain optimal network operation, verify the following settings by using RSNetworx for DeviceNet software, looking at the scanner Properties dialog: For Polled I/O messaging, verify that the effective polling rate (or scan time) is less than the expected packet rate (EPR) to prevent time-out errors. You may find the EPR on the Module by clicking Advanced. For COS or Cyclic I/O messaging, verify that the COS/Cyclic Inhibit Time is less than the EPR and that the ACK time out is set appropriately. You may find these parameters on the Scanlist by clicking Edit I/O Parameters.
97
Chapter 4
Communication
Please contact Rockwell Automation technical support if you find that the default settings do not result in adequate network performance.
Explicit Messaging
Use explicit messaging to read and write all data tables other than the I/O messaging table. The specific details of explicit messaging depend upon the master device that initiates the message. The example in this section uses an Allen-Bradley SLC 500 controller and DeviceNet Scanner (1747-SDN) as the master. Refer to the DeviceNet Scanner Module Installation Instructions, publication 1747-IN058, for a detailed description of explicit message programming in the SLC 500 controller. Please refer to the Rockwell Automation KnowledgeBase for other examples of explicit messaging to a Powermonitor 3000 unit. In the SLC 500 and PLC-5 controllers, you assemble the explicit message header in an integer file and transfer it to the scanner module. When the response is received, you transfer the response from the scanner to another integer file. The message header consists of 6 words organized as follows.
Explicit Messaging Message Header Word 0 1 2 Body 3 4 5 6 7 ... n High byte Transmit ID Port Service Class Instance Attribute Data to write if applicable Low byte Command Size MAC ID
98
Communication
Chapter 4
Word 0 contains a transmit identifier (TXID) and command byte. Assign each explicit message a unique TXID in the range of 0255 decimal (0 to FF hex). The TXID is used to identify the response to this message request. These are valid command codes: 1 hex = Execute transaction block. Use this command first to start the explicit message. 4 hex = Delete transaction from response queue. Use this command after you copy the response from the scanner to remove the response from the scanner and enable further explicit messages. Word 1 contains the DeviceNet scanner port number and the transaction body size in bytes. The SLC 500 scanner module uses only port 0; a PLC-5 DeviceNet scanner module has two ports, 0 and 1. For a read request, the transaction body size is 3 words, therefore 6 bytes. See the Explicit Messaging table on page 98 for more information. For a write, the body size is the data size in bytes plus the 6-byte path (class/instance/attribute). Word 2 contains the DeviceNet service code and the MAC ID or node number of the server device, in this case, the power monitor. Valid service codes for use on Class 4 assembly instances include the following: 0E hesx (14 decimal) = Get_Attribute_Single. Requests a read of the entire assembly instance defined in the transaction body. 10 hex (16 decimal) = Set_Attribute_Single. Writes the data contained in the message to the assembly instance defined in the transaction body.
TIP
A convenient way to build Words 0, 1, and 2 is to multiply the high byte value by 256 and add the low byte value, using decimal values for each parameter. Example: TXID = 121; Command = 1. Word 0 = 121*256 + 1 = 30977.
Words 35 comprise the DeviceNet path: Class, Instance, and Attribute. For the power monitor data tables, Class = 4, Assembly Objects; Attribute identifies the data table, and Attribute = 3, data. Word 6 and following words contain data to write to the power monitor.
99
Chapter 4
Communication
Once the message is assembled, your ladder program transfers the integer file to the scanner module M0 file starting at word 224 (SLC 500 controller) or block transfers the 64-word integer file to the scanner module (PLC-5 controller). The ControlLogix controller includes in its instruction set a CIP Generic message instruction that builds the transaction header and path from information you enter into the message setup dialog in RSLogix 5000 software.
Message Setup
The example above is a ControlLogix message instruction to read the user-configured table, assembly instance 37.
TIP
Because the floating-point word order in the ControlLogix controller is reversed from the default DeviceNet floating-point word order setting in the Powermonitor 3000 unit, your ladder logic will need to reverse the word order so the data may be interpreted correctly. The SWPB instruction performs this function. You may also select little-Endian word order, however, this may be incompatible with RSPower and RSEnergyMetrix software.
Up to four concurrent explicit messaging connections are supported by the DeviceNet communication port.
100
Communication
Chapter 4
DeviceNet Message Types Group 1 2 CAN Identifier Message Type Field 01101xxxxxx 01111xxxxxx 10xxxxxx010 10yyyyyy011 10xxxxxx100 10xxxxxx101 10xxxxxx110 10xxxxxx111 3 4 11101xxxxxx 11110xxxxxx Not used Slaves I/O COS or Cyclic message Slaves I/O poll response or COS / Cyclic ACK message Masters COS / Cyclic ACK message Slaves explicit / unconnected response message Masters explicit request message Masters I/O poll command / COS / Cyclic message Group 2 only unconnected explicit message request Duplicate MAC ID check message Unconnected explicit response Unconnected explicit request
xxxxxx = Destination MAC ID / node no. (6-bit field) yyyyyy = Source MAC ID / node no. (6-it field)
101
Chapter 4
Communication
DeviceNet Class Services Service Name Reset Get_Attribute_Single Set_Attribute_Single Allocate_Group_2_Identifier_Set Release_Group_2_Identifier_Set Service Code (hex) 05 0E 10 4B 4C Service Code (decimal) 05 14 16 75 76
DeviceNet Object Classes Class (hex) 01 O2 03 04 05 2B Object Identity Message Router DeviceNet Assembly Connection Acknowledge handler
102
Communication
Chapter 4
103
Chapter 4
Communication
Protocol Selection Table Protocol RSLinx Connection Type EtherNet/IP DF1 (CSP) DF1 (CSP) Pure CSP Client Compatibility(1) No Yes Yes RSEnergyMetrix and RSPower Compatibility Yes No No Logix and MicroLogix Compatibility Yes No Yes Implicit Messaging Compatibility Yes No Yes
In addition to the selectable protocols listed above, the Ethernet port supports Modbus TCP beginning with Master Module firmware version 4 and Ethernet firmware version 3. Refer to the description of the Modbus RTU protocol beginning on page 92 for further information. The Ethernet port supports up to 64 concurrent connections. The power monitor supports the following network requests.
Ethernet Message Types Message type CIP PLC-5 Typed Write CIP PLC-5 Typed Read CIP Generic Assembly Object (class 04), Get & Set Attribute Single for Attribute 3 (data) CIP Generic Assembly Object (class 04), Get Attribute Single for Attribute 3 (size) CIP SLC 500 Typed Write CIP SLC 500 Typed Read CIP Data Table Read (using CSP/PCCC addressing for example F15:0) CIP Data Table Write CSP / PCCC PLC-5 Typed Write CSP / PCCC PLC-5 Typed Read CSP / PCCC Protected Typed Logical Read, 2 address fields CSP / PCCC Protected Typed Logical Read, 3 address fields CSP / PCCC Protected Typed Logical Write, 2 address fields CSP / PCCC Protected Typed Logical Write, 3 address fields CSP / PCCC Word Range Read CSP / PCCC Word Range Write CSP / PCCC Diagnostic Loopback
104
Communication
Chapter 4
If you want to execute a sequence of messages, condition each message in the sequence with the previous messages done or error status, and include a brief programmed time delay between messages so that each message receives fresh data and the communication port is not overloaded. As a starting point, program the inter-message time delay at 100 ms.
105
Chapter 4
Communication
EtherNet/IP explicit messaging from a PLC-5E or SLC 5/05 controller to a Powermonitor 3000 unit uses a MultiHop message path. The client controller thinks it is communicating with a ControlLogix controller. The example message detail screens below indicate a PLC/5xxE reading the voltage and current table F15:0 from a power monitor to the controllers F15:0 data table.
PLC-5/xxE Controller Message Detail Screen Example
106
Communication
Chapter 4
When you select Yes in the MultiHop field, the MultiHop tab appears in the dialog. Enter the IP address of the power monitor in the 1756-ENET I. P. field (192.168.4.49 is used here as an example) and any integer in the 1756 backplane Slot field.
PLC-5/xxE Controller MultiHop Configuration
The example below shows the MultiHop configuration for messaging from a PLC-5/xxC ControlNet processor through a ControlLogix Gateway to an Ethernet power monitor.
PLC-5/xxC Controller via ControlLogix Gateway MultiHop Configuration
You may choose between two types of ControlLogix controller to power monitor messaging. PLC-5 Typed read or write, that encapsulates a PCCC message within a CIP wrapper CIP Generic messaging which uses the CIP class/instance/attribute object model common to DeviceNet network
107
Chapter 4
Communication
Set up the Communication tab in the ControlLogix message instruction the same for each messaging type.
ControlLogix Controller to Powermonitor 3000 Unit Communication Tab Example
The first example below reads the Voltage and Current table from a power monitor into the ControlLogix controller tag dataPM3K_VI(0) by using a PLC-5 Typed Read, configured as an array of 14 elements of type Real. You would configure a CIP Data Table Read the same way except for the message type.
ControlLogix PLC-5 Controller Typed Read Example
108
Communication
Chapter 4
The next example shows the message configuration for a CIP Generic message type. A CIP Generic message can read or write data, depending on the Service Type you specify. Refer to DeviceNet Class Services on page 102. In this example, the ControlLogix reads the User-configured Data Table into tag dataPM3K_User(0), configured as an array of 23 elements of Real type.
ControlLogix Controller CIP Generic Messaging Example
This example uses the following message parameter values: Service Type: Get_Attribute_Single, (service code oe hex) Object class: 4 (hex), Assembly Instance: 37 (decimal), User configured table results Attribute: 3 (hex), Data
109
Chapter 4
Communication
TIP
If you wish to establish a Class 1 connection with more than one controller to the same power monitor, use instance 1 and 2 for the first controller and use instance 1 and 255 for all remaining controllers (instance 255 is a placeholder instance since instance 2 only supports one connection). If the controller loses its connection to instance 1 and 2, the instance 255 connection is also lost.
4. Select Data INT as the Communication Format. 5. Enter the IP address of the power monitor. 6. Set the Connection Parameters as shown for the default configuration. If you change the configuration of the input assembly instance, enter its new size in Instance 1 here.
110
Communication
Chapter 4
7. Select 3 as the Configuration instance and leave its Size set to 0 bytes and click the Next. 8. Set the Requested Packet Interval to 100 ms or greater. The power monitor does not respond reliably to an RPI of less than 100 ms.
Requested Packet Interval Setup
111
Chapter 4
Communication
112
Communication
Chapter 4
4. Select Data-INT as the Communication Format. 5. Enter the ControlNet address of the power monitor. 6. Set the Connection Parameters as shown for the default configuration. If you change the configuration of the input assembly instance, enter its new size in Instance 1 here. 7. Select 3 as the Configuration instance and leave its Size set to 0 bytes and click Next. 8. Set the Requested Packet Interval to a binary multiple of the network update time (NUT) greater than 100 ms. The power monitor update rate is typically 100 ms.
Requested Packet
113
Chapter 4
Communication
Controller Tags
9. Download the revised program to the controller. 10. Run RSNetworx for ControlNet software to schedule the connection between the controller and the power monitor. Refer to the RSNetWorx for ControlNet documentation for assistance. The ControlNet power monitor supports up to 64 concurrent Class 1 connections to instance 1 and one concurrent connection to instance 2.
114
Communication
Chapter 4
Communicating to a Powermonitor 3000 Unit from an SLC Controller through 1747-KFC15 ControlNet Module
Connect the 1747-KFC15 module according to your instruction manual documentation. There should be a connection from the KFC15 RS232 port to Channel 0 of the SLC controller. For this example, the communication and configuration of the channel 0 and the KFC15 module were the following: KFC15 KFC15 KFC15 KFC15 KFC15 KFC15 KFC15 KFC15 KFC15 KFC15 DF1 station address - 7 and SLC baud rate at - 19200 and SLC - Full-duplex and SLC Parity - None and SLC Handshaking - None Diagnostic Command Execution - Disabled Duplicate detect - Off and SLC Error Detect - CRC Number of Retries - 3 DF1 ACK Time Out - 3.2
TIP
Since it is easier to configure and much faster to run, full-duplex mode is the preferred mode of operation. Use half-duplex mode only if you do not have a choice.
115
Chapter 4
Communication
Notice that under target device that power monitor data table N11 (Date and Time) was selected. The Local Node Address is the address of the power monitor Controlnet Node Address 4.
116
Communication
Chapter 4
Notice that under target device that power monitor data table F10 (Basic Configuration) was selected. The Local Node Address is the address of the power monitor Controlnet Node Address 4. The information to write was loaded into file F12:0 of the SLC controller and is 9 elements long.
117
Chapter 4
Communication
This example reads the Voltage, Current and Frequency table, File F15 from the power monitor.
Notice that when using an unscheduled message directly to the power monitor, in this case node 4, that the message format is local, multi-hop selection is no.
118
Communication
Chapter 4
This example writes configuration to the Basic Configuration table, File F10 in the power monitor.
This message transfers 9 floats from table F8:0 to the power monitor table F10. The power monitor address is at node 4, local message.
119
Chapter 4
Communication
Parameter Selection Bitfield Value Bitfield Value Binary 000 001 010 100 111 Decimal 0 1 2 4 7 Parameter Table 14 kWh forward kWh reverse kVAh All Table 15 kVARh forward kVARh reverse kAh All
You may select the value at which the energy counters roll over to 0 in the Advanced Device Configuration table.
120
Communication
Chapter 4
121
Chapter 4
Communication
TIP
Refer to the Rockwell Automation KnowledgeBase (http://www.ab.com) for additional information on setting up a user-configured I/O instance.
122
Chapter
Setpoint operation provides a method other than communication for the power monitor to be used in and interact with power and energy applications. Some examples of setpoint applications include the following: Turning on an output relay when predicted demand exceeds a preset level, for simple demand management Turning off an output relay if phase rotation is accidentally reversed, helping to assure that loads rotate in the correct direction Capturing an oscillogram when a status input is energized
Setpoint operation permits the power monitor to simultaneously monitor a number of parameters and take action when specified conditions are met. The M4 and M5 models support 10 setpoints while the M6 and M8 support 20. There are eight parameters to configure for each setpoint: Setpoint Number, Type, Evaluation Condition, High Limit, Low Limit, Action Delay, Release Delay, and Action Type. These parameters are described in the Setpoint Configuration table on page 128. In the M6 and M8 models, setpoints 19 and 20 have special significance and are preset at the factory. Refer to Sag and Swell in Chapter 8. When a setpoint activates, it takes the action defined in Setpoint Action Type and writes a time-stamped entry to the Event Log. Setpoint action types that energize a relay or KYZ output or set an alarm flag are maintained until the setpoint releases. Other setpoint actions such as capturing an oscillograph or clearing a counter occur when the setpoint activates. The power monitor also writes a time-stamped entry in the Event Log when the setpoint releases. The event log record contains the maximum over-voltage or under-voltage recorded during a swell or sag condition, respectively. This applies only to models M6 and M8.
123
Chapter 5
TIP
If more than one setpoint is used to control the relay and/or KYZ output, the individual setpoints are evaluated in a logical and to determine the output state.
You may read setpoint output flags in the Discrete Data table on page 193 and the Remote I/O, DeviceNet, EtherNet/IP and ControlNet I/O Messaging Parameters on page 191. You may read only the first 8 setpoint output flags in the discrete input table with optional remote I/O communication. Setpoints evaluate data based on six different conditions: over forward, over reverse, under forward, under reverse, equal, and not equal. Over and under setpoint evaluation conditions may only be used with analog values such as voltages, currents, power, etc. Reverse setpoints are typically used to monitor power and energy when on-site generation is present. Equal and not equal evaluation conditions are for use with discrete conditions such as phase rotation, status inputs and transient detection.
0 Setpoint Activated
Time (s)
124
Chapter 5
125
Chapter 5
126
Chapter 5
Equal Setpoint
An equal setpoint activates when the monitored parameter equals the Setpoint High Limit for a time greater than the Setpoint Action Delay. An equal setpoint releases when the monitored parameter does not equal the Setpoint High Limit for a period of time greater than the Setpoint Release Delay. The Setpoint Low Limit is not used for equal and not equal setpoints.
127
Chapter 5
Configuring Setpoints
You may configure setpoints by using the display module or by writing the setpoint configuration table through communication. The following tables describe setpoint configuration parameters.
Setpoint Configuration Parameter Name Setpoint Number Setpoint Type Setpoint Evaluation Condition Parameter Description The number of the setpoint being configured. The parameter value to be evaluated by the setpoint. The operator used to evaluate the parameter value. Range 110 (M4, M5) 120 (M6, M8) 052 (Refer to List of Setpoint Types on page 216) 0 = Over forward (+) 1 = Over reverse (-) 2 = Under forward (+) 3 = Under reverse (-) 4 = Equal (=) 5 = Not equal (<>) 010,000,000 Units Default N/A 0 0
The value being used as a reference to activate the setpoint for over comparisons, or to deactivate the setpoint for under comparisons. Note: This parameter is non-numeric when viewed via the display module, and the Setpoint Type is Phase Rotation or Status input.
Depends on type
128
Chapter 5
Setpoint Configuration Parameter Name Setpoint Low Limit Parameter Description The value being used as a reference to deactivate the setpoint for over comparisons, or to activate the setpoint for under comparisons. Range 010,000,000 Units Depends on type Default 0
Setpoint Action Delay The minimum time in seconds that the setpoint limit must be exceeded continuously before the setpoint will trigger. Setpoint Release Delay Setpoint Action Type The minimum time in seconds that the setpoint limit must not be exceeded continuously before the setpoint releases. The action that occurs when the setpoint is triggered. Clear the time accumulator for this setpoint
03600 030,000 03600 030,000 032 (see details in the Setpoint Action Type table on page 131) Yes No
Sec (M4, M5) 0.1 Sec (M6, M8) Sec (M4, M5) 0.1 Sec (M6, M8)
N/A
M4, M5
M6
M8
129
Current(1) Voltage unbalance Current unbalance Neutral current W VAR VA Total true PF Total disp PF Total dist PF W demand VAR demand VA demand Amp demand Projected amp demand Projected W Demand Projected VAR Demand Projected VA Demand Frequency Phase rotation Crest factor voltage Crest factor current
Chapter 5
M4, M5
M6
M8
IEC THD current(1) IEC THD I4 Status input 1 Status input 2 Any status input(1) Setpoint #1 time accumulator Setpoint #2 time accumulator Setpoint #3 time accumulator Setpoint #4 time accumulator Setpoint #5 time accumulator Setpoint #6 time accumulator Setpoint #7 time accumulator Setpoint #8 time accumulator Setpoint #9 time accumulator Setpoint #10 time accumulator Voltage Sag(1) (2) Voltage Swell
(1) (2)
Seconds
Volts %
Transient detected(2) Avg IEEE THD V Avg IEEE THD I Avg IEC THD V Avg IEC THD I Avg Crest Factor V Avg Crest Factor I
A setpoint activates when the magnitude of any phase passes the activation limit and releases when all phases pass the release limit in the appropriate direction for the setpoint evaluation condition. These setpoint types apply only to the applicable Powermonitor 3000 models and will appear as inactive on other models.
(2)
130
Chapter 5
Setpoint Action Type Setpoint Action type 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Description None Energize KYZ (and alarm flag 2) Set alarm flag 3 Set alarm flag 4 Set alarm flag 5 Set alarm flag 6 Set alarm flag 7 Set alarm flag 8 Set alarm flag 9 Set alarm flag 10 Set alarm flag 11 Set alarm flag 12 Set alarm flag 13 Set alarm flag 14 Set alarm flag 15 Set alarm flag 16 Save a trend log record Clear kWh result Clear kVARh result Clear kVAh result Clear Ah result M4 M5 M6 M8 Setpoint Action type 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Description Clear all energy results Clear setpoint #1 time Clear setpoint #2 time Clear setpoint #3 time Clear setpoint #4 time Clear setpoint #5 time Clear setpoint #6 time Clear setpoint #7 time Clear setpoint #8 time Clear setpoint #9 time Clear setpoint #10 time Clear setpoint #11 time Clear setpoint #12 time Clear setpoint #13 time Clear setpoint #14 time Clear setpoint #15 time Clear setpoint #16 time Clear setpoint #17 time Clear setpoint #18 time Clear setpoint #19 time Clear setpoint #20 time Capture oscillograph M4 M5 M 6 M 8
131
Chapter 5
ATTENTION
These examples are intended to demonstrate setpoint configuration only. They should not be used as sample application programming references. Carefully consider all control, operational and safety issues when designing and implementing setpoint operations.
Example 1 Simple demand management: To configure setpoint 1 to energize output relay 1 when projected demand exceeds 100 kW for more than one second and de-energize relay 1 when projected demand falls below 90 kW for more than two seconds, you could use the following settings.
Simple Demand Management Settings Parameter Setpoint number Setpoint type Setpoint evaluation condition Setpoint high limit Setpoint low limit Setpoint action delay Setpoint release delay Setpoint action type Value 1 17 - Projected Watt Demand 0 - Over forward 100,000 watts 90,000 watts 1 second (M4, M5) 10 tenths of a second (M6, M8) 2 seconds (M4, M5) 20 tenths of a second (M6, M8) 1 - Energize relay 1 and set alarm flag 1
Example 2 Phase reversal relay: To use setpoint 2 to energize the output relay as a permissive for starting a three-phase motor, you could use the following settings.
Phase Reversal Relay Settings Parameter Setpoint number Setpoint type Setpoint evaluation condition Setpoint high limit Setpoint low limit Value 2 21 - Phase rotation 4 - Equal 1 - ABC Not used
132
Chapter 5
Phase Reversal Relay Settings Parameter Setpoint action delay Setpoint release delay Setpoint action type Value 0 second (M4, M5) 0 tenths of a second (M6, M8) 0 seconds (M4, M5) 0 tenths of a second (M6, M8) 1 - Energize relay 1 and set alarm flag 1
Example 3 Sag alarm. To set an alarm flag on a sag condition so that RSEnergyMetrix software can log it and take action, use the following settings.
Sag Alarm Settings Parameter Setpoint number Setpoint type Setpoint evaluation condition Setpoint high limit Setpoint low limit Setpoint action delay Setpoint release delay Setpoint action type Suggested Value 3 1 - Voltage 2 - Under forward 110% of nominal system voltage 110% of nominal system voltage 0 90 seconds 3 - Set alarm flag 3
Nominal system voltage is the nominal line to neutral voltage in Wye and single-phase systems and nominal line to line voltage in Delta systems. In 1404-M6 and 1404-M8 units, the high and low limits would be the same as those found in setpoint 19, the built-in sag setpoint. Setpoint release delay of 90 seconds sets alarm flag 3 long enough that RSEnergyMetrix software can reliably log the alarm with a one-minute log rate. Alarm flag 3 is selected because alarm flags 1 and 2 are tied to physical relay and KYZ outputs.
133
Chapter 5
134
Chapter 5
135
Chapter 5
136
Chapter
I/O Operations
The power monitor is equipped with two relay outputs and two status inputs designed to provide a discrete interface with your application.
The Relay output is an electromechanical Form C relay with contacts rated at 10 amperes at 240V ac or 250V dc. This set of contacts is also rated to meet IEEE C37.90 requirements for power circuit breaker tripping duty. The KYZ output is a solid-state relay rated at 80 mA at 240V ac or 250V dc that provides higher reliability and long life for low-power signaling duty such as a kWh pulse output. The two outputs operate independently and you may configure each outputs operation individually. You may use the display module or communication to set the output configuration parameters in the Advanced Device Configuration table. The output configuration options for the relay and KYZ outputs include the following: Control source: specifies what controls the selected output. Options are 0= none; 1 through 6= pulsed output; 7= setpoint control; 8 discrete I/O control. Default = 7 Output scale: specifies the scaling factor for pulsed operation. Range 130,000; default = 10 Output width: specifies the pulse width for pulsed operation. Range 0 or 402,000 ms Force command: overrides setpoint, communication, discrete or pulsed control until the force is released. Options are: 0 = no change; 1 = force the output energized; 2 = forced the output de-energized; 3 = release the force Default output state on communication loss: specifies response to a loss of communication. Options are 0= last state/ resume; 1= last state/ freeze; 2= de-energize/ resume; 3= de-energize/ freeze. See below.
137
Chapter 6
I/O Operations
Pulsed Control
Many electric energy meters provide a dry contact output that changes state at intervals determined by a metered parameter. Pulsed control lets the power monitor emulate this function. You may select the following options for the Control source parameter: 1 2 3 4 5 6 = = = = = = Watt-hours forward Watt-hours reverse VAR-hours forward VAR-hours reverse VA-hours Ampere-hours
Set the Output width to the desired pulse duration in milliseconds. Set this parameter to zero (0) if you want the output to toggle instead of pulse. This operation emulates the KYZ operation of electromechanical energy meters. For a two-wire KYZ connection, use only one side of the relay. For a three-wire KYZ connection, use both sides of the Form C output. In a two-wire interface, (KY connection), an output event occurs only when the output contact closes. In a three-wire connection, an event occurs when either the KY or KZ contact closes. Therefore twice as many output events occur in a three-wire connection as in a two-wire connection for the same number of relay transitions.
138
I/O Operations
Chapter 6
3. Select a maximum pulse rate. This should be between 2 and 5 pulses per second for a two-wire KYZ connection and between 2 and 10 pulses per second for a three-wire connection. Lets use a three-wire KYZ connection and a pulse rate of 4 pps. 4. Compute the output scale by dividing the result of step 2 by the result of step 3 and rounding to the nearest integer. For our example, well set the output scale to 70.
Setpoint Control
Set the Control source to a value of 7 to enable setpoints to control the selected output.
Forced Operation
You may over-ride automatic output control by issuing a force command by using the display module or by writing the appropriate force command parameter in the Advanced Device Configuration table. Forces override all other output control sources. If you force an output either energized or de-energized, be sure to release the force to re-establish your selected control source.
TIP
If you cycle power to the power monitor, all output forces are released.
139
Chapter 6
I/O Operations
No Control Operation
You may also select no output control by selecting a value of zero (0) for the Control source parameter. This mode enables only output forcing.
IMPORTANT
The relay output contacts and solid-state KYZ output contacts on the power monitor may be used to control other devices through setpoint control or communication. You configure the response of these outputs to a communication failure. Be sure to evaluate the safety impact of the output configuration on your plant or process.
The Default output state on communication loss defines the behavior of the output if the power monitor experiences a loss of communication. What constitutes a communication loss depends on the protocol. A remote I/O unit declares a communication loss if it has detected more than 100 ms between valid frames or more than 255 consecutive valid frames not addressed to it. A DeviceNet unit declares a communication loss when the network master (scanner) has not polled it within the Expected Packet Rate that you configured when setting up the I/O connection. You may select one of the following behaviors for each output. Last-state / resume: holds the output in its last state during a communication loss and resume the output control when communication recovers. Last-state / freeze: holds the output in its last state during a communication loss and freezes the output in this state when communication recovers. You may clear the freeze by placing the logic controller into Program mode, changing the behavior to last state / resume, or cycling power to the power monitor. De-energize / resume: de-energizes the output during communication loss and resume output control when communication recovers. De-energize / freeze: de-energizes the output during communication loss and freezes the output de-energized when communication recovers. You may clear the freeze by placing the logic controller into Program mode, changing the behavior to last state / resume, or cycling power to the power monitor.
140
I/O Operations
Chapter 6
The power monitors two self-powered status inputs provide a number of flexible configuration options that help customize the power monitor operation to meet the requirements of your specific application.
Counters
You may use the power monitor to monitor discrete events such as circuit breaker status or kWh pulses from a legacy electrical energy, steam, gas or other type of meter. Each status input has associated with it an independent counter, which increments with every false-to-true transition of its input. The counter rolls over to 0 when it reaches its maximum value of 29,999. The counter value may be read by using the display module or communication to provide a value proportional to the accumulated value of the meter connected to the status input. You may select the input counter values as Trend Log parameters. You may clear either or both status input counters by using the display module or by writing the appropriate command to the Advanced Device Configuration table.
Setpoint Inputs
You may use one or both status inputs to activate setpoint control. Use an equal or not equal setpoint evaluation condition with status inputs.
141
Chapter 6
I/O Operations
142
Chapter
Data Logging
Its inherent data logging capability makes the power monitor a versatile component in a number of power and energy applications. Cost allocation applications can read billing variables like energy usage and demand from the configurable Trend Log, making the accuracy of reports less dependent on a continuous network connection. The Event Log captures time-stamped records of important power system occurrences that can be aligned with corresponding production or environmental effects to better understand and optimize your energy use and costs. This chapter describes in detail the data logging functions in the power monitor.
Event Log
The Event Log contains records stored in nonvolatile memory of the 50 (M4 and M5) or 100 (M6 and M8) most recent events that occurred in the power monitor. Event records may include the following: changes in the unit configuration. setpoint activation and release. relay or KYZ output forcing. status input change of state. power-up and power-down. clearing or presetting of an energy counter. setting the unit time and date. clearing of the trend or min/max log. clearing of setpoint timers. detection of a sag, swell, or transient.
143
Chapter 7
Data Logging
Event Codes Event Type Name No Event Setpoint Activated Setpoint Deactivated Relay Forced Energized Relay Forced De-energized Relay No Force Option Status Input Set Status Input Cleared kWh Counter Set kVARh Counter Set kVAh Counter Set Ah Counter Set Event Type Shown by DM No Evnt Set##A(1) Set##D(1) Rly# F1(1) Rly# F0(1) Rly# NF(1) S# On(1) S# Off(1) Wh Set Varh Set kVAh Set kAh Set Event Type Number 0 1 2 3 4 5 6 7 8 8 8 8 Event Command Code 0 Setpoint Number (110) Setpoint Number (110) Relay Number (12) Relay Number (12) Relay Number (12) Status Input Number(12) Status Input Number(12) 1 2 3 4
144
Data Logging
Chapter 7
Event Codes Event Type Name All Energy Counters Set Trend Log Clear Min/Max Log Set Factory Defaults Restored Status Input Counter 1 Cleared Status Input Counter 2 Cleared Reserved for Future Enhancement Single Setpoint Timer Clear All Setpoint Timers Clear Power Up Power Down Self-test Error Time Set Device Reconfigured Setpoint Reconfigured NVRAM Set Transient Detected
(1)
Event Type Shown by DM All Power Set Trend Clr M/M Clr FactCfg S1 Clr S2 Clr Single SP Set All SP Set Pwr On Pwr Off ST ####(1) TimeSet New Cfg Set Cfg NVRAM Set TRN Det
9 10 11 12 13 14 15 16
0 0 Hexadecimal Status Error Code (See Status Error Codes on page 146) 0 0 0 0 M8 only
145
Chapter 7
Data Logging
Status Error Codes Bits bit 0 bit 1 bit 2 bit 3 bit 4 bit 5 bit 6 bit 7 bit 8 bit 9 bit 10 bit 11 bit 1215 Hex 0001h 0002h 0004h 0008h 0010h 0020h 0040h 0080h 0100h 0200h 0400h 0800h 1000h -8000h Description Master module code flash status Master module data flash status Master module RAM Status Reserved for factory use Master module NVRAM status Master module data acquisition status Master module real time clock status Reserved for factory use Reserved for factory use Display module status Master module watchdog timer status Master module optional communication status Reserved for factory use
146
Data Logging
Chapter 7
147
Chapter 7
Data Logging
TIP
The power monitor expresses timestamps in an array of four data table elements: Year Month/day Hour/minute Second/hundredth of a second Each timestamp parameter (except the Year) is a combination of its first and second element. For instance, the Month = the parameter value divided by 100 with the remainder = the Day. Example: 1230 = December 30th.
You can learn a great deal about, and learn how to reduce, your enterprises energy costs by keeping a historical record of power and energy usage. The Configurable Trend Log allows you to set up automatic logging of up to 16 parameters at intervals between 1 second and 1 hour. It can store over 45,000 individual records in nonvolatile memory. You must use communication to configure and read the Trend Log. There is no display module interface for either configuration or monitoring.
Default Configuration
As shipped from the factory, a power monitor logs net kilowatt-hours (kWh), net kVAR-hours (kVarh) and demand watts, at 15-minute intervals, in overwrite mode.
148
Data Logging
Chapter 7
TIP
If you use the power monitor with RSEnergyMetrix energy logging software, you should coordinate the parameters selected for the Trend Log with those logged by the software. This allows for the energy logging software to poll the Trend Log data, allowing for automatic data repopulation of the energy database.
Where: D = Depth of the trend log in records F = Fill mode (0 = fill and hold, 1 = overwrite) P = Parameters per record (116) INT (x) = The integer portion of x
EXAMPLE
149
Chapter 7
Data Logging
EXAMPLE
For example, CEIL (1914.28) = 1915. Suppose D = 13400 and F = 0, we will get
16384 P = INT ------------------------------------- 5.5 = INT ( 3.05 ) = 3 CEIL ( 1914.28 )
Examples
Example 1: You want to log kWh every 15 minutes and you want to know how many records the log contains and how long a time that covers. The Trend Log Depth Formula applies to this example. Fill and hold mode allows logging the most records. Logging only 1 parameter per record, the formula results in a total of 17,640 records after rounding down. Logging every 15 minutes, this log configuration will log 6.1 months of kW data.
150
Data Logging
Chapter 7
Example 2: Another user wants to log several parameters every 5 minutes indefinitely, retrieving the records within one week after the end of each month. He saves the retrieved data and creates trend graphs on his PC. The question is how many parameters may be monitored. The Parameters per Record Formula applies to this example. The total log depth of 10,944 is based on the log duration and interval: (31 days per month + 7 days) * (24 hours per day) * (60 minutes per hour) / 5 minute logging interval. Overwrite mode (F = 1) allows you to read the log any time without losing any data. In this example, P, the number of parameters that may be recorded, is 3. From this example, you can see that the trend log can log 3 parameters every 5 minutes in a 38-day sliding window.
151
Chapter 7
Data Logging
TIP
Although you may configure up to 16 Trend Log parameters on units with optional DeviceNet communication, the results table will return only the first 8.
The power monitor clears the trend log when you change any parameter or the logging interval. You may perform a simple table read of the Trend Log Configuration/Read-back Record Select table to view the existing Trend Log configuration. When you read this table, the password element returns a value of -1 and the reserved and command elements return a value of 0. Elements 7 and 8 return the Total Records Logged * 1000 and * 1 respectively.
152
Data Logging
Chapter 7
Only mode 0, 1, and 2 are supported by DF1 and remote I/O communication. In modes 0, 1, and 2 the client need only read the results table repeatedly until the entire Trend Log is read. In modes 36 the client must alternate writes to select the next read-back record with reads of the results table. You may obtain the number of records in the Trend Log by reading the Trend Log Configuration/Read-back Record Select table, elements 7 and 8. The number of records is (element 7) * 1000 + (element 8). Only the following elements are needed during a record-selection write: Password: -1 DeviceNet unique write identifier: as applicable Reserved words: must be 0 Read-back mode: see above
The Trend Log Results table is a read-only table of 14 (DeviceNet network) or 22 (all other communication options) floating-point elements as follows: Reserved element: returns 0 Internal identifier: increments by 1 to 15 for each trend log record then rolls over to 0 Time stamp: in 4-element timestamp format. See page 55. User-selected parameters: parameters you selected when you configured the Trend Log.
Min/Max Log
The Min/max Log maintains a time-stamped record of the minimum and maximum values of up to 74 metering parameters. You can monitor values over a day, a week, a month or any period to record the highest and lowest values of voltage, current, or power factor. Most industrial utility bills include a charge based on the maximum demand recorded during the billing period. You could use the Min/max log to provide that piece of data for generating an internal or shadow billing report.
153
Chapter 7
Data Logging
154
Data Logging
Chapter 7
Min/Max Log Parameter Listing Param. Number 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 Parameter Name L1 Current L2 Current L3 Current Avg Current L1-N Voltage L2-N Voltage L3-N Voltage Avg L-N Voltage L1-L2 Voltage L2-L3 Voltage L3-L1 Voltage Avg L-L Voltage Frequency, last cycle L4 Current Positive Sequence Current Negative Sequence Current % Current unbalance Positive Sequence Voltage Negative Sequence Voltage % Voltage unbalance Average frequency L1 Real Power L2 Real Power L3 Real Power Total Real Power L1 Reactive Power L2 Reactive Power L3 Reactive Power Total Reactive Power L1 Apparent Power L2 Apparent Power L3 Apparent Power Total Apparent Power Demand Current Demand Power Demand Reactive Power Demand Apparent Power Param. Number 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 Parameter Name Projected Demand I Projected Demand W Projected Demand VAR Projected Demand VA L1 True Power Factor L2 True Power Factor L3 True Power Factor Three-phase True PF L1 Displacement Power Factor L2 Displacement Power Factor L3 Displacement Power Factor Three-phase Displacement PF L1 Distortion Power Factor L2 Distortion Power Factor L3 Distortion Power Factor Three-phase Distortion PF V1% IEEE THD I1% IEEE THD V2% IEEE THD I2% IEEE THD V3% IEEE THD I3% IEEE THD I4% IEEE THD V1% IEC thd (DIN) I1% IEC thd (DIN) V2% IEC thd (DIN) I2% IEC thd (DIN) V3% IEC thd (DIN) I3% IEC thd (DIN) I4% IEC thd (DIN) V1 Crest Factor I1 Crest Factor V2 Crest Factor I2 Crest Factor V3 Crest Factor I3 Crest Factor I4 Crest Factor
155
Chapter 7
Data Logging
The Min/Max Log Results table is a read-only data table consisting of 11 floating-point elements containing the following information: Parameter #: See the Min/Max Log Parameter Listing table above Min and max values Timestamps: for Min and Max values in four-element timestamp format
Time-of-use
The power monitor provides a Time-of-Use Log. Also called the TOU log, it provides a one-year time-of-use history of energy usage and demand. The time-of-use log provides the following: User-selectable on-peak, mid-peak and off-peak hours User-selectable off-peak days of the week Real, reactive and apparent energy usage records Real, reactive and apparent power demand records Month-to-date record for the current month Monthly history for the past year User-selectable day of month to begin time-of-use logs
The time-of-use log is designed to support simple billing and cost allocation applications that apply different rates to energy and demand used at different times.
Mid peak AM 8:0010:59 Mid peak PM 3:006:59 Peak AM 10:0011:59 Peak PM 12:00 noon2:59
Publication 1404-UM001F-EN-P - November 2009
Data Logging
Chapter 7
TOU Period
AM
PM
12:00 12:59
10:00 10:59
11:00 11:59
12:00 12:59
10:00 10:59 0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
0 1
0 1
1 X
1 X
0 1
0 1
0 1
0 1
0 0
0 0
0 0
X(1) X
x = Dont care.
11:00 11:59 0 0
1:00 1:59
2:00 2:59
3:00 3:59
4:00 4:59
5:00 5:59
6:00 6:59
7:00 7:59
8:00 8:59
9:00 9:59
1:00 1:59
2:00 2:59
3:00 3:59
4:00 4:59
5:00 5:59
6:00 6:59
7:00 7:59
8:00 8:59
9:00 9:59
157
Chapter 7
Data Logging
Mid peak PM selects afternoon mid peak time-of-use hours. Default 120 (78 Hex, 3:006:59 p.m.) Peak AM selects morning peak time-of-use hours. Default 2048 (800 Hex, 11:0011:59 a.m.) Peak PM selects afternoon peak time-of-use hours. Default 7 (7 Hex, 12:00 noon2:59 p.m.)
The Time of Use Records Reactive Energy and Demand and Time of Use Records Apparent Energy and Demand tables are identical except that one contains reactive energy and demand TOU data and the other contains apparent energy and demand TOU data.
158
Chapter
Advanced Features
In this chapter we discuss major features that, for the most part, are found only in the Powermonitor 3000 M6 and M8 models. The exception is that basic harmonic analysis is supported in the M4 and M5 models.
Oscillography
Oscillography captures waveforms of the voltage and current present at the power monitor input terminals. A client application reads oscillography records by using the indexed read method. The main features of oscillography include the following: Simultaneous capture of all seven voltage and current channels Non-volatile storage of up to 8 (M6) or 2 (M8) captures Configurable sampling rate up to 5.4 kHz or 90 samples per cycle at 60 Hz Captures may hold up to 408 cycles of data per channel at 60 Hz Configurable data resolution of 13 bit w/ sign or 7 bit w/sign Configurable pre-trigger means the capture includes waveform information prior to the triggering event Setpoints or communication may trigger oscillogram captures All communication options support oscillography You may choose to use RSPower, RSPowerPlus, or RSEnergyMetrix software, or create a custom application, to configure oscillography and read waveform data. RSPower software may be configured to automatically download and save waveforms to a disk file, and then clear the oscillography buffers.
159
Chapter 8
Advanced Features
Configuring Oscillography
You may configure oscillography only via communication. The display module does not support an interface to oscillography. Configure oscillography by performing a table write to the Oscillograph Configuration/Read-back Data Select. This read/write table of 11 integer elements comprises the following configuration and command parameters. Password: needed to configure the capture type or pre-trigger, or execute a command to trigger or clear a capture. Not needed for read-back select, use -1. Default 0000. Capture number: selects a capture for read-back or returns the last capture selected. Range 18 (M6) or 12 (M8). Default 1. Channel number: selects a channel number or returns the last channel number selected. Range: 1 = V1, 2 = I1, 3 = V2, 4 = I2, 5 = V3, 6 = I3, 7 = I4. Default 1. Block number: selects a data block for the next read or returns the last block selected. Range depends on communication type. See below. Default 1. Read-back mode: selects a read-back mode or returns the last mode selected. Range 02, default 0. See below. Clear / trigger command: clears one or all captures or triggers a new capture. Always returns 0. In the M8 model, values of 38 have same meaning as 0. These are the options: 0 - no action 1 - clear capture 1 2 - clear capture 2 3 - clear capture 3 (M6 only) 4 - clear capture 4 (M6 only) 5 - clear capture 5 (M6 only) 6 - clear capture 6 (M6 only) 7 - clear capture 7 (M6 only) 8 - clear capture 8 (M6 only) 9 - clear all captures 10 - initiate a new capture Capture type: selects sample rate and data resolution or indicates selected sample rate and resolution. Range -15, default 0. -1 disables oscillography. See the Capture Type Properties table on page 161. Pre-trigger: specifies how much of the captured waveform occurred before the triggering event. Range 0100 per cent, default 90%. Reserved: must be zero (0) on a write, returns 0.
160 Publication 1404-UM001F-EN-P - November 2009
Advanced Features
Chapter 8
Capture clear status: Read-only bitfield that indicates which capture numbers are clear. Bit 0 (LSB) corresponds to capture 1, bit 1 to capture 2 and so on. For each bit, 1 indicates clear, 0 indicates not clear. Capture ready status: read-only bitfield that indicates which capture numbers contain captures that are ready to read. Same bit correspondence as above. For each bit, 1 indicates the capture is ready, 0 indicates no capture or not yet ready. If a client reads a capture that is not ready, -1 is returned for all data points.
Block Number
The block number and the total number of data reads required to read an entire capture depend on the communication option and the capture type. See the Capture Type Properties table. The block number range is 1 to the number of Data reads required listed in the table.
Capture Type
The properties associated with the capture type options are listed in the Capture Type Properties table. You may select a capture type that best suits your application requirements. A higher sample rate provides a more accurate representation of the waveform when higher-order harmonics and transients are present. Higher data resolution provides more accuracy of each data point. Capture type 5 combines low sampling rate and low resolution, but captures almost 7 seconds of waveform at 60 Hz.
Capture Type Properties Capture Type 0 1 2 3 4 5 Sampling Rate 5.4 kHz 2.7 kHz 1.35 kHz 5.4 kHz 2.7 kHz 1.35 kHz 7-bit w/sign Data Samples per Resolution Cycle at 60 / 50 Hz 13-bit w/sign 90 / 108 45 / 54 22.5 / 27 90 / 108 45 / 54 22.5 / 27 Total Cycles per Channel at 60 / 50 Hz 51.1 / 42.6 102.2 / 85.2 204.4 / 170.3 102.2 / 85.2 204.4 / 170.3 408.8 / 340.7 Capture Duration (seconds) 0.85 1.70 3.40 1.70 3.40 6.81 460 184 Data Reads Required DeviceNet 230 Other Comms 92
161
Chapter 8
Advanced Features
Read-back Mode
The data client uses the indexed read method to read oscillogram capture data. The readback mode options include the following: Auto-increment all channels: successive reads of the Oscillograph Results table increment through all remaining blocks of the current channel, increment through all remaining channels and wrap back to the original channel. Auto-increment current channel: successive reads of the results table will increment through all remaining blocks of the current channel only. Manual increment: each write of the Oscillograph Configuration/Read-back Data Select table specifies the channel and block to be read in the next read of the Oscillograph Results table. Successive reads of the results table returns the same block of data each time if no read-back select write is done.
162
Advanced Features
Chapter 8
The data client sets up the read-back configuration with a table write to the Oscillograph Configuration/Read-back Data Select table, the content of which is described above. As with other indexed reads, DeviceNet and Ethernet optional communication support only manual increment read-back mode so that the client must write a read-back select message before each read of the results table. For all other communication options, auto-increment all channels or auto-increment current channel read-back mode provides the highest communication throughput.
The total number of data points is 4600 for capture type 0, 1, and 2 and 9200 for capture types 3, 4, and 5.
163
Chapter 8
Advanced Features
Each data point is expressed in calibrated analog-to-digital (A/D) converter counts with a resolution of 8192 (13-bit w/sign) or 128 (7-bit w/sign). A client may calculate the primary-side instantaneous voltage or current magnitude of each data point by using the following formula:
You would multiply each data point by the following factor to correctly display the waveform:
164
Advanced Features
Chapter 8
Trigger Statistics
The trigger source and capture identifier are combined in one element, and indicate what triggered the capture and a unique capture identifier or serial number. The value divided by 1000 gives the trigger source: 0 = none; 120 = setpoint number; 21 = native communication; 22 = optional communication. The remainder of this calculation is the unique capture identifier which increments by 1 from 0999 and rolls back to 0. A client application may use the identifier to associate with an event log entry and determine chronological order of captures. Example: a parameter value of 15,347 indicates that setpoint 15 triggered the capture and its serial number or identifier is 347. The trigger position returns the number of the data point corresponding with the time the capture was triggered. A client application may use this to place a marker on the displayed waveform. The maximum trigger position is the same as the total number of oscillogram data points. The power monitor configuration may affect the accuracy of the trigger position statistic with respect to the pre-trigger setting. For best results, set RMS resolution to 0 (nominal) and RMS results averaging to 0 (none) in the Advanced Device Configuration table. The capture timestamp and capture type are also important statistics that identify the capture and enable a client application to correctly display the waveform.
165
Chapter 8
Advanced Features
Harmonic Analysis
The power monitor provides harmonic data to help you understand this important element of power quality in your facility. Each model provides a different level of harmonic information. The Harmonic Analysis Functionality table provides an overview of the harmonic analysis available in each model. You may access all harmonic data by using communication. The display module can access average values of the parameters as indicated in the DM column.
Harmonic Analysis Functionality Harmonic data DM (Avg.) M4 M5 M6 M8 Per Current Channel Per Voltage Channel Avg. Of Current Channels Avg. Of Voltage Channels
IEEE Total Harmonic Distortion (THD) IEC Distortion Index (DIN) Crest Factor Telephone Interference Factor (TIF) K-factor IEEE-519 Total Demand Distortion (TDD) IEEE 519 Pass / Fail Harmonic distortion, harmonics 141 Harmonic magnitude, harmonics 141 Harmonic distortion, harmonics 4263 Harmonic magnitude, harmonics 4263
THD = -----------------------H 1
n = 2
Where:
( H )2 n
166
Advanced Features
Chapter 8
The standard IEC definition of harmonic distortion is the Distortion Index (DIN) and is computed for each channel as follows:
DIN =
n = 2 ------------------- n = 1
( H )2 n ( H )2 n
Where: Hn = magnitude of the nth harmonic (n 41 or 63) DIN is equivalent to IEC THD
Crest Factor
This is another quantity that is sometimes used to describe the amount of distortion present in a waveform. It can also be used to express the dynamic range of a measurement device. Crest Factor is the ratio of the peak to the RMS.
167
Chapter 8
Advanced Features
TIF
Another method of measuring signal distortion is the Telephone Influence Factor, sometimes called the Telephone Interference Factor. This measurement is used to estimate the effect that the power line harmonics have on nearby analog telephone conductors. This method weighs each of the harmonics based on the physiological and audiological characteristics of the human ear. The harmonics are additionally weighted to reflect the relationship of harmonic frequency and degree of coupling to the phone lines. These weights are called single frequency TIF weights. The 1404-M6 uses the most recent TIF weights (updated in 1960). The single frequency factors are used to compute the total TIF. You multiply the TIF numbers by the RMS magnitude of the power lines voltage or current to obtain an index for estimating the amount of interfering energy that is coupled to the telephone system. The formula for total TIF is:
TIF =
i = 1 ------------------------- i = 1
Where:
(w X ) i i (X ) i 2 2
Xi = single frequency RMS current or voltage at harmonic i. wi= single frequency TIF weighting factor at harmonic i.
168
Advanced Features
Chapter 8
K-Factor
K-Factor measures additional heating in a power transformer due to the harmonics in the power signal. These harmonics cause additional heating due to increased core losses that occur at higher frequencies. The increased losses are related to the square of the harmonic frequency. Therefore, a slight harmonic content can significantly increase the heat rise in a power transformer. The additional harmonic heating may cause a transformer to exceed designed temperature limits even though the RMS current is less than the transformer rating. The K-Factor is used as justification to oversize a power transformer to allow extra margin for harmonic losses or to select an appropriate K-Factor rated transformer. A K-Factor rated transformer is the preferred choice since it has known performance in the presence of harmonics. The formula for K-Factor is as follows:
169
Chapter 8
Advanced Features
TDD = -----------------------H 1
( Hn )2 n = 2
Table 10.3 of the IEEE standard specifies the limits. The appropriate limits are selected by computing the ratio of the available short circuit current to the maximum fundamental demand load current. The row of the table that corresponds to the ratio is then used to determine the proper limits for each of the individual harmonics and the TDD specified in the table columns. IEEE-519 also recommends maximum voltage distortion levels that the utility should remain below. Table 11.1 of the IEEE standard specifies these limits based on the magnitude of the line to line voltage at the PCC. Once configured, the 1404-M6 will automatically monitor the system voltage and current for IEEE-519 compliance.
Harmonic Magnitude
The powe rmonitor calculates the RMS magnitude of each individual harmonic. Results are calculated for harmonics 141 (M6) or 163 (M8) for all 7 voltage and current channels. Each result is expressed in RMS volts or amps.
170
Advanced Features
Chapter 8
Harmonic Distortion
The power monitor calculates the magnitude of each individual harmonic with respect to the fundamental. Results are calculated for harmonics 141 (M6) or 163 (M8) for all 7 voltage and current channels. Each result is expressed as a percentage of the fundamental.
TIP
The remaining elements listed below are reserved in the M4 and M5 models, return 0 on a read and must be 0 on a write.
Individual harmonic data type: selects% distortion (0) or magnitude (1) on subsequent reads of the individual results tables. Default 0 Enable disable harmonic analysis: 0 disables, 1 enables calculation of TIF, K-factor, IEEE-519 and individual harmonics results. Default 1 IEEE-519 maximum short-circuit current: used for IEEE-519 pass/fail calculation, expressed in integer/exponent format. Range 09999 (integer), -4 to 21 (exponent), defaults are 0. used for IEEE-519 TDD calculation, expressed in integer/exponent format. Range 09999 (integer), -4 21 (exponent), defaults are 0.
171
Chapter 8
Advanced Features
Readback Mode
The data client uses the indexed read method to read harmonic analysis and individual harmonic data. The options include the following: Auto-increment (0): increments the channel after each read of the Harmonic Results; THD, Crest Factor, and More table. This also controls the read-back channel for individual harmonics results tables. If you use the auto-increment mode, read any desired individual harmonic data for the current channel before the next read of the Harmonic Results; THD, Crest Factor, and More table. Manual-increment (1): successive reads of the Harmonic Results; THD, Crest Factor, and More table return harmonic results from the current channel. As with other indexed reads, DeviceNet and Ethernet networks optional communication support only manual increment read-back mode so that the client must write a read-back select message to change the channel returned in the results table. For all other communication options, auto-increment Read-back mode provides the highest communication throughput.
TIP
The remaining elements are reserved in the M4 and M5 models and return values of 0.
172
Advanced Features
Chapter 8
TIF: Telephone influence factor. Range 0.0999.9*1022 K-factor: Range 0.0999.9*1022 IEEE-519 TDD: Total demand distortion. Range 0.0999.9*1022 IEEE-519 Pass/fail: -1 = unknown, 0 = fail, 1 = pass FFT iteration: each new FFT calculation (used in the previous four parameters) increments by one from 032,767 and rolls back to 0 A data client may determine the relative freshness of data by comparing the THD & crest iteration or FFT iteration parameters in repeated reads of this table.
Each of these tables consists of 14 floating-point elements containing the following parameters: Channel: 1 = V1, 2 = I1, 3 = V2, 4 = I2, 5 = V3, 6 = I3, 7 = I4 (no averages) Type of harmonic data: 0 = per cent harmonic distortion, 1 = magnitude Nth harmonic: expressed according to the type parameter. Magnitude type is referenced to the primary side of PTs and CTs. Range: 0.0999.9 * 1022 FFT iteration: each new FFT calculation (used in the previous four parameters) increments by one from 032,767 and rolls back to 0
Publication 1404-UM001F-EN-P - November 2009 173
Chapter 8
Advanced Features
In the Harmonic Results; Odd Harmonics 2341, Harmonic Results; Even Harmonics 220 and Harmonic Results; Even Harmonics 2240 tables the first nth harmonic element is reserved and returns a value of 0.
The Powermonitor 3000 M6 and M8 models are capable of detecting voltage sags and swells. There are many definitions for sag and swell. IEEE 11591 defines sag as: a decrease to between 0.10.9 pu in rms voltage or current at the power frequency for durations of 0.5 cycle to 1 minute. IEEE 11591 defines swell as: an increase in rms voltage or current at the power frequency for durations from 0.5 cycles to 1 minute. Typical values are 1.11.8 pu.
Sag and Swell
The pre-defined setpoint configuration for the detection of sag and swell is based on the IEEE-1159 standard. Although the default setpoint configuration is applicable as-is for many sag and swell applications, it may be necessary to alter the setpoint configuration to adjust the units sensitivity to sags and swells for your particular application.
174
Advanced Features
Chapter 8
Setpoint #19 is setup to detect voltage sag and has the following configuration data: Type = Voltage Sag Evaluation condition = Under forward High Limit = 90% Nominal System Voltage Low Limit = 90% Nominal System Voltage Action delay = 0 Release delay = 0 Output action = Capture oscillograph
Setpoint #20 is setup to detect voltage swell and has the following configuration data: Type = Voltage Swell Evaluation condition = Over forward High Limit = 110% Nominal System Voltage Low Limit = 110% Nominal System Voltage Action delay = 0 Release delay = 0 Output action = Capture oscillograph
TIP
The setpoint limits reference the nominal line-to-line voltage for Delta modes and the nominal line-to-neutral voltage for Wye and single-phase modes.
If the nominal system voltage setting is changed, the high and low limits for setpoint #19 and #20 are automatically adjusted to 90% and 110% of the nominal system voltage.
175
Chapter 8
Advanced Features
3. Periodically check the event log or capture ready status for an indication that a sag or swell has occurred. 4. Read the event log to get the timestamp, duration of the disturbance, the worst case magnitude, and the identifier of the capture. 5. Find the capture that has the same identifier as the one found in the event log record by reading the first block from each capture location. Read the entire capture from the power monitor. Depending on the duration of the disturbance, the capture may contain additional information prior to and during the sag or swell event. The sag or swell duration reported in the event log has a tolerance of 2x the metering update rate. Refer to Metering Update Rate on page 60 for more information. For sag and swell durations less than 500 milliseconds, examining the oscillograph data can result in a more accurate determination of sag or swell duration. References: IEEE Std 1159-1995, IEEE Recommended Practice for Monitoring Electric Power Quality, page 5,6,12. The Institute of Electrical & Electronics Engineers Inc, 345 East 47th Street, New York, NY 10017-2394, ISBN 1-55937-549-3
176
Advanced Features
Chapter 8
Load Factor
The Powermonitor 3000 M6 and M8 models provide a Load Factor Log which calculates and stores a group of plant demand metrics that indicates how stable (or, conversely, how dynamic) a load is over a period of time, usually one month. Use communication to configure load factor operation and read the results. The display module does not support an interface to the load factor log. Load factor is the average demand divided by the peak demand for the month. If the load is constant, load factor is 100%. The power monitor calculates load factor for real, reactive and apparent power and current, and stores the last 12 results in the Load Factor Log in non-volatile memory. You may configure the power monitor to automatically calculate and store load factor on a particular day each month, or you may manually generate a command by using communication to save the load factor result and reset the calculation. This information is useful in reducing peak demand when you look at load factor and peak demand values. The peak demand period is stored in the Mix/Max Log, which has a date and time stamp that indicates when the peak occurred. Using this information, you may be able to identify plant activities that caused the peak. You may be able to prevent or reschedule activities, or install a demand management system. Either option may realize significant savings in demand charges. You can use the load factor values to estimate demand cost savings potential. The lower the load factor, the higher the potential for savings by managing your electric power demand. The power monitor stores the load factor in 13 records. Record 0 stores in-progress calculations and is cleared on a power cycle. Records 112 are a first-in, first-out array saved in non-volatile memory, with the highest record number containing the most recent record. In manual clear/reset mode, when you issue a clear/reset command, the contents of record 0 is written to the highest-numbered record and (if necessary) the remaining records are shifted down, with the oldest being deleted. In auto clear/reset mode, you select a day of the month for this process to occur automatically. Within each record, the power monitor stores peak, average and load factor values for real power (watts), reactive power (VARs) apparent power (VA) and average current (amps). Peak values are the largest such value that has occurred since the last automatic or manual clear/reset occurrence. The in-process record (record 0) is updated at the end of each demand interval. If no demand interval has expired since the last unit power-up, the record will return all zeroes.
177
Chapter 8
Advanced Features
Advanced Features
Chapter 8
Average demand current: expressed in VARs. Range 0.0999.9*1021 Load factor current: expressed in per cent. Range 0.0100.0 Elapsed time: hours that have elapsed since the last automatic or manual clear/reset operation Ending date: for this load factor record. Range 0123199 (mmddyy). 0 if the selected record is blank
Transient detection functionality, available only in the M8 model, continuously monitors your choice of voltage or current inputs for the occurrence of a transient. Transients such as voltage spikes and momentary dropouts can disrupt equipment connected to the power source, but can be difficult to detect. Use communication to configure transient capture parameters and retrieve the data for display and/or processing. The display module does not support an interface for transient detection. Transient detection includes the following: Continuously monitors all six voltage or six current channels Identifies transients at least 200 microseconds in duration Triggers a transient oscillogram capture when it detects a transient Records captures each containing 12 cycles; 6 cycles preceding and 6 cycles following the transient Stores up to six transient captures of all seven voltage and current channels in non-volatile memory Calculates RMS voltage and current values for each cycle in each capture Stores each data point in the capture with 13-bit plus sign resolution Monitors for transients on your choice of voltage channels or current channels Automatically or manually adjusts transient detection thresholds You may configure a detected transient to trigger a setpoint, which may then trigger an oscillogram capture, providing zoom capability. All communication options support transient configuration, metering and capture. Use RSPower, RSPowerPlus, or RSEnergyMetrix software, or create a custom application, to configure and read transient data. The following information provides details of the data table interface for transient detection.
179
Chapter 8
Advanced Features
Transient Capture
180
Advanced Features
Chapter 8
Auto-threshold set margin: range 1.0100.0 per cent, default 20.0 Voltage trigger threshold: range 0.11000.0, default 10.0 Current trigger threshold: range 0.11000.0, default 10.0
Threshold Configuration
The power monitor compares voltage or current transients against a threshold that you may set manually or command to be set automatically. You select either voltage channels or current channels with the Detection mode parameter. When you issue the Auto-threshold set command, the power monitor first determines if there is sufficient signal amplitude on the selected voltage or current channels to set the threshold. If the signal amplitude is greater than 10% of full-scale, the power monitor begins timing the Auto-threshold set duration. During this time, it monitors the selected channels, calculates an average transient index, and decrements the Auto-threshold duration time remaining parameter. At the end of this time, it combines the average transient index with the Auto-threshold set margin and stores the result as the Voltage trigger threshold or Current trigger threshold. Threshold settings relate to both magnitude and duration of a transient, so they are representative of the energy contained in a transient. In most cases, use the automatic threshold calculation as a starting point, by issuing an Auto-threshold set command. Then manually adjust the selected threshold if you want to increase or decrease the sensitivity. The power monitor does not monitor for or capture transient data until a threshold setting has been configured.
181
Chapter 8
Advanced Features
Voltage: three RMS voltage results that express line-to-line (delta wiring modes) or line-to-neutral (all other wiring modes) for the current Cycle number. Range 0.0999.0 * 1021 Current: four RMS current results (L1, L2, L3, L4) for the current Cycle number. Range 0.0999.0 * 1021 Trigger channel: indicates which channel caused the transient capture. 1=V1, 2=I1, 3=V2, 4=I2, 5=V3, 6=I3, 7=I4 Index at trigger: the value of the transient index at the time of the capture. Range -999.0 * 103999.0 * 103 Voltage and Current trigger thresholds: at the time of the transient capture. Range 0.0999.0 * 103 Capture ID: unique identifier that increments by 1 s to 30,000 and then rolls over to 0 Read this data table by using an indexed read method. Select the Read-back Mode, Capture and Cycle by writing to the Transient Analysis Configuration/Read-back Select table.
182
Advanced Features
Chapter 8
Capture clear status: Read-only bitfield that indicates which capture numbers are clear. Bit 0 (LSB) corresponds to capture 1, bit 1 to capture 2 and so on. For each bit, 1 indicates clear, 0 indicates not clear. Capture ready status: read-only bitfield that indicates which capture numbers contain captures that are ready to read. Same bit correspondence as above. For each bit, 1 indicates the capture is ready, 0 indicates no capture or not yet ready.
Block Number
The block number and the total number of data reads required to read an entire capture depend on the communication option. The range is 170 for the DeviceNet network and 128 for all other communication options.
Read-back Mode
The data client uses the indexed read method to read transient capture data. The Read-back mode options include the following: Auto-increment all channels: successive reads of Transient Capture Clear/Read-back Data Select table increment through all remaining blocks of the current channel, increment through all remaining channels and wrap back to the original channel. Auto-increment current channel: successive reads of the results table will increment through all remaining blocks of the current channel only. Manual increment: each write of the Transient Capture Clear/Read-back Data Select table specifies the channel and block to be read in the next read of the Transient Capture Results table. Successive reads of the results table return the same block of data each time if no read-back select write is done. As with other indexed reads, DeviceNet and Ethernet optional communication support only manual increment read-back mode so that the client must write a read-back select message before each read of the results table. For all other communication options, auto-increment all channels or auto-increment current channel read-back mode provides the highest communication throughput.
183
Chapter 8
Advanced Features
The Transient Capture Results table comprises the transient capture results. This read-only table comprises these 29 (DeviceNet network) or 59 (all other communication options) integer elements: Capture timestamp: in three elements using the standard timestamp format except the year is omitted Capture number: in the range 16 Channel number: in the range 17 (1=V1, 2=I1, 3=V2, 4=I2, 5=V3, 6=I3, 7=I4) Block number: block number of the data contained in the table. See above. Transient capture identifier: range 030,000, rolls over to 0 Transient capture data points: see below
The total number of data points is 1400. Each data point is expressed in calibrated analog-to-digital (A/D) converter counts with a resolution of 8192 (13-bit w/sign). A client may calculate the primary-side instantaneous voltage or current magnitude of each data point by using the following formula:
Advanced Features
Chapter 8
For example, consider the following capture: PT primary = 13.8 kV PT secondary = 120V CT primary = 100 A CT secondary = 5 A Delta voltage mode (line-to-line)
You would multiply each data point by the following factor to correctly display the waveform:
Clear Command
Issue the Clear command parameter to clear transient captures from non-volatile memory and provide space for new captures. Write the correct Password for the power monitor to accept the command. The command parameter options include the following: -1 - Clear all transient captures 0 - No action 1 - Clear capture #1 2 - Clear capture #2 3 - Clear capture #3 4 - Clear capture #4 5 - Clear capture #5 6 - Clear capture #6 At least one capture location must be clear for a transient detect event to be processed. If no captures are clear, the power monitor ignores any new transient detection events.
185
Chapter 8
Advanced Features
186
Appendix
187
Appendix A
Remote I/O, DeviceNet, EtherNet/IP and ControlNet I/O Messaging Parameters Discrete Data Parameters Basic Device Configuration Parameters Date and Time Parameters Advanced Device Configuration Parameters Native Communication Configuration Parameters Optional Communication Configuration Parameters Metering Voltage, Current, and Frequency Result Parameters Metering Sequence Voltage, and Current Results Parameters Metering Power Results Parameters Metering Demand Results Parameters Metering Power Factor Results Parameters Metering Real and Apparent Energy Results Parameters Metering Reactive Energy and Amp-hour Results Parameters Selftest/Diagnostic Results Parameters DF1 PCCC Diagnostic Status Reply Parameters Setpoint Setup/Read-back Select and Status Parameters Trend Log Configuration/Read-back Record Select Parameters Trend Log Results Parameters Min/Max Log Configuration/Read-back Select Parameters Min/Max Log Results Parameters Event Log Configuration/Read-back Record Select Parameters Event Log Results Parameters User-configured Table Setup Parameters User-configured Table Results Parameters Write Error Status Parameters Harmonic Analysis Configuration/Read-back Select Parameters Harmonic Results; THD, Crest Factor, and More Parameters Harmonic Results; Odd Harmonics 121 Parameters Harmonic Results; Odd Harmonics 2341 Parameters Harmonic Results; Even Harmonics 220 Parameters Harmonic Results; Even Harmonics 2240 Parameters Oscillograph Configuration/Read-back Data Select Parameters
R/W R R/W R/W R/W R/W R/W R R R R R R/W R/W R R R/W R/W R R/W R R/W R R/W R R R/W R R R R R R/W
N9 F10 N11 N12 N13 N14 F15 F16 F17 F18 F19 N20 N21 N22
(5)
I/O 10 20 12 26 11 24 38 27 31 25 33 29 30 36 22 34 48 13 28 9 21 35 62 4 14 23 39 40 41 42 15
1,2 3 4,5 6,7 8,9 10,11 12,13 14 15 16 17 18 19,20 21,22 23 24,25 26,27 28 29,30 31 32,33 34 35,36 37 38 39,40 41 42 43 44 45 46,47
30001 40001 40101 40201 40301 40401 30101 30201 30301 30401 30501 40501 40601 30601 40701 40801 30701 40901 30801 41001 30901 41101 31001 31101 41201 31201 -
M6 M8
191 193 194 195 196 198 199 205 206 207 208 209 210 211 212 213 215 220 221 223 227 228 229 233 235 236 237 238 239 240 241 242 243
N23 N24
F25 N26
14 or 22(10) 9 11 6 14,17,18
(11)
26 14 or 23(12) 2 9 9 or 10(13) 14 14 14 14 11
188
Appendix A
Oscillograph Results Parameters Load Factor Log Configuration/Read-back Select Parameters Load Factor Log Results Parameters Transient Analysis Configuration/Read-back Select Parameters Transient Analysis Metering Results Parameters Transient Capture Clear/Read-back Data Select Parameters Transient Capture Results Parameters Advanced Metering Configuration Parameters Harmonic Results; Odd Harmonics 4363 Parameters Harmonic Results; Even Harmonics 4262 Parameters Catalog Number and WIN Parameters Network Demand Sync and Time Configuration Parameters(2) Controller Command Parameters(2) Daylight Saving Time Configuration Parameters Time of Use Register Configuration Parameters Time of Use Records Real Energy and Demand Parameters Time of Use Records Reactive Energy and Demand Parameters Time of Use Records Apparent Energy and Demand Parameters Single Password Write Parameters Single Parameter Read Parameters
(1) (2) (3) (4) (5) (6) (7)
N40 N41
61 16 43 44 32 17 60 19 45 46 50 47 49 51 52 53 -
M6 M8
29 or 59(14) 6 14 13 14 13 29 or 59(14) 10 14 14 29 20 1 10 10 12 12 12 1 1
244 247 248 249 250 251 252 255 256 257 258 260 261 261 262 263 264 265 266 267
F42 F43 F44 N45 N46 N47 F48 F49 N51 N52 N53 N54 N55 F56 F57 F58 N60 -
Event log user comment feature has been removed from master firmware revision 3.1 and later. Supported only on 1404-xxxxx-ENT-xx. Data is most commonly read from this table by using the Indexed read method. Powermonitor 3000 unit starts with file 9 to avoid any data-type incompatibility with SLC file numbers 18, which are of a fixed data type. This is a reply to a PCCC diagnostic status request, used by RSWho to display text and an icon for the product. Listed Modbus address is one-based. For zero-based addressing, subtract a value of one (1) from the listed address. The default size is 2 input words and 2 output words for remote I/O. The input table (instance 1) default size is 6 words and is user configurable for DeviceNet, EtherNet/IP, and ControlNet networks. Remote I/O tables and the default DeviceNet input channel are PLC/SLC controllers compatible, but if you reconfigure the DeviceNet input channel (Instance 1), it may or may not be PLC/SLC controllers compatible (depending on the number of parameters configured). Basic device configuration data table size is 8 elements for the M4 and M5, and 9 elements for the M6 and M8. Table size increased in revision 3.1x of the master module firmware. The size of the Trend log results table is 28 elements for the DeviceNet network and 44 elements for all other communication protocols. The size of the Event log results table is 14 elements for M4/M5, 17 elements for M6 and 18 elements for the M8.
189
Appendix A
(12)
The User-configured table results table is populated from the bottom up with the number of parameters you configured. The DeviceNet table must contain 14 elements or less to remain PLC/SLC controllers compatible. Harmonic results; THD, crest factor, and more data table size is 18 elements for the M4 and M5 and 20 elements for the M6 and M8. The Oscillograph results and Transient capture results tables are 29 elements for the DeviceNet network and 59 elements for all other communication protocols.
(13) (14)
190
Appendix A
Remote I/O, DeviceNet, EtherNet/IP and ControlNet I/O Messaging Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N/A N/A 1 (Read), 2 (Write) 2 (Default) Integer (Selectable as Floating Point with DeviceNet, EtherNet/IP and ControlNet) Read/Write All
Remote I/O Discrete Data Provided by Powermonitor (Remote I/O Input Data) Element No. 1 Element name Relay, KYZ, and alarm bits Range Comment Bit 0007 08 Description Reserved, used internally for BT information Form C relay state (setpoint output flag 1) 0 = De-energized and not forced 1 = Energized and not forced KYZ output state (setpoint output flag 2) 0 = De-energized and not forced 1 = Energized and not forced Setpoint output flag 3 state Setpoint output flag 4 state Setpoint output flag 5 state Setpoint output flag 6 state Setpoint output flag 7 state Setpoint output flag 8 state Description Status input 1 state Status input 2 state Reserved, returns 0 New oscillograph (M6, M8 only) Indicates at least one capture has been triggered, saved, and is ready to be read. This bit is cleared when all captures are cleared. Reserved, returns 0 Reserved, used internally for BT information Reserved, returns 0
09
0711 1214 15
191
Appendix A
TIP
Data appears in the first two words of the input image table corresponding to the Powermonitor 3000 logical rack. For example, with the unit configured as Rack 1, Group 1 in a 1747-SN scanner residing in Slot 2, the data will appear in words I:2.8 and I:2.9 of the data table.
Remote I/O Discrete Data Accepted by Powermonitor Units (Master Output Data) Element No. 1 2 Element name Relay control KYZ control Range 0 or 128 Comment 0 (Bit 8 = 0): De-energize 128 (Bit 8 = 1): Energize Must be enabled by Control source parameter
DeviceNet, EtherNet/IP, and ControlNet I/O Data Provided by Powermonitor Units (Scanner Input Data; Instance 1) Element No. 0 1 2 Element name Relay output status Solid-state KYZ output status Alarm output word 0FFFF Range 03 Comment 0 = De-energized & not forced 1 = Energized & not forced 2 = Forced de-energized 3 = Forced energized Bitfield indicates state of 16 alarm output flags; 0 = released, 1 = asserted Bit 0 = relay/setpoint output flag 1 Bit 1 = KYZ/setpoint output flag 2 Bit 2 = setpoint output flag 3 Bit 15 = setpoint output flag 16 Bit 0 = status input 1; 0 = open, 1 = contact closure detected Bit 1 = status input 2; 0 = open, 1 = contact closure detected Bit 2 = demand sync timeout; 1 = the demand delay expired before the next expected external demand sync. This bit clears when the next external demand sync occurs. Refer to Advanced Device Configuration Parameters element 23. Bits 315 = unused (always 0) Counts to 29,999, rolls over to 0.
07
4 5
0 29,999
TIP
Size and content of Instance 1 may vary depending on user configuration. Refer to User-configured Data Table on page 121 for more information.
DeviceNet, EtherNet/IP, and ControlNet I/O Data Accepted by Powermonitor Units (Scanner Output Data; Instance 2) Element No. 0 1 Element name Range Default Value Relay output Solid-state KYZ output 01 01 0 (Bit 8 = 0): De-energize 256 (Bit 8 = 1): Energize Must be enabled by Control source parameter
Publication 1404-UM001F-EN-P - November 2009
Comment
192
Appendix A
Discrete Data Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Discrete Data Element Modbus Element name No. Address 0 1 2 30001 30002 30003 Relay output status Solid-state KYZ output status Alarm output word 0FFFF Range 03 Comment 0 = De-energized and not forced 1 = Energized and not forced 2 = Force De-energized 3 = Force Energized Bitfield indicating state of the 16 alarm output flags; 0 = released, 1 = asserted. Bit 0 = relay/setpoint output flag 1 Bit 1 = KYZ/setpoint output flag 2 Bit 2 = setpoint output flag 3 Bit 15 = setpoint output flag 16 Bit 0 = status input #1; 0 = open, 1 = contact closure detected Bit 1 = status input #2; 0 = open, 1 = contact closure detected Bit 2 = demand sync timeout; 1 = the demand delay expired before the next expected external demand sync. This bit clears when the next external demand sync occurs. Refer to Advanced Device Configuration Parameters element 23. Bits 315 = unused (always 0) Counts to 29,999, rolls over to 0 N9 10 3 6 Integer Read Only All
User Configurable No
30004
07
4 5
30005 30006
0 29,999
193
Appendix A
Basic Device Configuration Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F10 20 4 (Write), 5 (Read) 8 (M4, M5), 9 (M6, M8) Floating point Read / Write See table
User Configurable No
Basic Device Configuration Element No. 0 1 Modbus Address 40001-2 40003-4 Element name M4 M M Range M5 6 8 09999 08 Units Defaul Comment t Value 0 6 Valid password required to change configuration. Returns -1 0 = Delta 3 CT 1 = Delta 2 CT 2 = Direct Delta 3 CT 3 = Direct Delta 2 CT 4 = Open Delta 3 CT 5 = Open Delta 2 CT 6 = Wye 7 = Single Phase 8 = Demo The high side of the PT ratio (xxx:xxx) The low side of the PT ratio (xxx:xxx) The high side of the CT ratio (xxx:xxx) The low side of the CT ratio (xxx:xxx) The high side of the I4 CT ratio (xxx:xxx) The low side of the I4 CT ratio (xxx:xxx) Value is used in the default Sag and Swell setpoints. (M6 and M8 only) Nominal line-to-line voltage for Delta mode and line-to-neutral for Wye and single-phase modes
2 3 4 5 6 7 8
Potential transformer (PT) primary PT secondary I1/I2/I3 current transformer (CT) Primary I1/I2/I3 CT secondary I4 CT primary I4 CT secondary Nominal system voltage
1.0 Volts 10,000,000.0 1.0600.0 Volts 1.0 Amps 10,000,000.0 1.05.0 Amps 1.0 Amps 10,000,000.0 1.05.0 Amps
194
Appendix A
Date and Time Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Date and Time Element Modbus Element name No. Address 0 1 2 3 4 5 6 7
(1) (2)
User Configurable No
Range
Default Value(2)
Comment Valid password required to change the date and time. Returns -1 1 = January, 2 = February,12 = December The internal clock adjusts the date for leap year.
Password Date: year Date: month Date: day Time: hour Time: minute Time: seconds Time: hundredths of seconds
09999 0 1998 2097 112 131(1) 023 059 059 099 1998 1 1 0 0 0 0
0 = 12am, 1 = 1am,23 = 11pm The internal clock does not adjust for daylight saving time.
On a write, the maximum value for day depends on the values written to month and the year. The data and time default values are set if one of the following three conditions occur: - When the device is first powered-up at the factory. - A device power-up following the depletion of the real-time clock power source. - In the event of an abnormal condition which may cause the real-time clock to contain values which are not in the valid range. The date and time are not set to the default values when Restore Factory Defaults is performed via the display module or communication port.
195
Appendix A
Advanced Device Configuration Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N12 26 8 (Write), 9 (Read) 25 Integer Read / Write All
User Configurable No
Advanced Device Configuration Element Modbus Element name No. Address 0 1 2 3 4 5 40201 40202 40203 40204 40205 40206 Password New password Demand period length Number of demand periods Predicted demand type KYZ control source Range Units Default Value 0 -1 15 1 0 7 Comment Required to change configuration data. Returns -1 -1 = no action; 09999 = new password; returns -1 Zero or negative demand period length enables external demand synch. Refer to Demand Calculation on page 35 0 = instantaneous; 1 = 1st order; 2 = 2nd order 0 = None (forcing only) 1 = Wh Forward 2 = Wh Reverse 3 = VARh Forward 4 = VARh Reverse 5 = Vah 6 = Ah 7 = Setpoints 8 = Discrete control (RIO, DeviceNet)
6 7 8 9 10
KYZ pulse output scale KYZ pulse output width Relay control source Relay pulse output scale Relay pulse output width
ms ms
10 0 7 10 100
Refer to Relay and KYZ Output Operations on page 137 0 = KYZ-style transition 402000 = pulse duration Same choices as KYZ control source Refer to Relay and KYZ Output Operations on page 137 0 = KYZ-style transition 402000 = pulse duration
11 12 13
0 (M4) 0 = Nominal 1 (M5, 6 or 8) 1 = High 0 (M4) 0 = No averaging. 1 (M5, 6 or 8) 1 = Average of the last 8 results 1 0 = none; 1 = last 8 cycles
196
Appendix A
Advanced Device Configuration Element Modbus Element name No. Address 14 15 16 40215 40216 40217 Restore factory default config Clear status input counters Wdog action Range 01 03 01 Units Default Value 0 0 1 Comment 0 = No action 1 = Restore factory default settings 0 = No action 1 = Clear counter #1 2 = Clear counter #2 3 = Clear both
0 = Restart, log an event and halt operation 1 = Restart, log an event and resume Refer to Watchdog Timeout Action on page 55 0 = No change 1 = Force energize the relay 2 = Force de-energize the relay 3 = Release force of relay output Overrides setpoint or pulse output control 0 = Last state / resume 1 = Last state / freeze 2 = De-energize / resume 3 = De-energize / freeze Refer to Communication Loss Behavior on page 140 0 = Slow; 1 = Fast Refer to Configurable Energy Counter Rollover on page 35 0 = Disable, 1900 = number of seconds delay Reserved. Must be 0 on a write, returns 0 Reserved. Must be 0 on a write, returns 0
17 18
40218 40219
03
0 0
19 20
40220 40221
Default relay state in event of communication loss Default KYZ state in event of communication loss DM text scroll rate Energy counter rollover Forced demand sync delay Reserved Reserved
03
21 22 23 24 25
01 415 0900 0 0
Digits 15 s 10 0 0
197
Appendix A
Native Communication Configuration Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N13 11 10 (Write), 11 (Read) 10 Integer Read / Write All
User Configurable No
Native Communication Configuration Element No. 0 1 Modbus Address 40301 40302 Element name Password Protocol Range 09999 03 Units Default Comment Value 0 0 Valid password required to change configuration data. Returns -1 Communication protocol for the native communication port. 0 = DF1 half-duplex slave 1 = Modbus RTU slave 2 = Auto Sense - Selects the protocol based on the incoming communication packets 3 = DF1 full-duplex Specifies the delay before responding to an external request, useful with slow external devices (such as RF modems) 0 = 1.2 Kbps 1 = 2.4 Kbps 2 = 4.8 Kbps 3 = 9.6 Kbps 4 = 19.2 Kbps 5 = 38.4 Kbps 6 = 57.6 Kbps Identifies the device on a multi-drop network. DF1 master typically uses 0. The broadcast address is 255 Parity, number of data bits, number of stop bits 0 = No parity, 8 data bits, 1 stop bit 1 = Odd parity, 8 data bits, 1 stop bit 2 = Even parity, 8 data bits, 1 stop bit Specifies the minimum delay between characters that indicates the end of a message packet. 0 = 3.5 character times 0 = CRC 1 = BCC Returns 0
2 3
40303 40304
015 06
5 ms -
2 (10ms) 3
4 5
40305 40306
1247 02
(1)
40307
06553
ms
7 8 9
(1)
01 0
0 0
The default address is the Device ID, which is factory assigned and is found on the label on the side of the master module. The device ID is incremented for each device.
198
Appendix A
Optional Communication Configuration Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N14 24 12 (Write), 13 (Read) 20 Integer Read / Write All
User Configurable No
TIP
Ethernet Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
(1)
Modbus Element name Address 40401 40402 40403 40404 40405 40406 40407 40408 40409 40410 40411 40412 40413 40414 40415 40416 40417 40418 40419 40420 Password IP address byte a IP address byte b IP address byte c IP address byte d Subnet mask byte a Subnet mask byte b Subnet mask byte c Subnet mask byte d Gateway IP address byte a Gateway IP address byte b Gateway IP address byte c Gateway IP address byte d Protocol selection(1) Reserved
Range
Units
Default Value
Comment
09999 0255
Valid password required to change configuration data. Returns -1 Format: aaa.bbb.ccc.ddd. Static IP address of this device (for example 130.151.32.86). If connected to a network, IP address must be unique. (255.255.255.255 is not permitted.) Format aaa.bbb.ccc.ddd.
Device ID Factory-assigned device ID 0255 255 255 0 0 0255 128 1 1 1 02 0 0 0 0 = CIP, 1 = CSP, 2 = CIP/CSP Reserved. Must be 0 on a write, returns 0 IP address of the gateway on this subnet used to route messages to other subnets (wide area networking).
199
Appendix A
ControlNet Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Modbus Address 40401 40402 40403 40404 40405 40406 40407 40408 40409 40410 40411 40412 40413 40414 40415 40416 40417 40418 40419 40420 Element name Password MAC ID Reserved Range 09999 099 0 Units Default Value 0 99 0 Comment Valid password required to change configuration data. Returns -1 On a write, sets MAC ID (node address) of Powermonitor 3000 unit on ControlNet network Reserved. Must be 0 on a write, returns 0
200
Appendix A
Remote I/O Element No. 0 1 2 Modbus Element name Address 40401 40402 40403 Password Module group Range 09999 0,2,4,6 Default Value 0 1 0 Comment Valid password required to change configuration data. Returns -1 The scanner uses rack address 0 0 = Group 0 (acts like the first 2 rack slots) 2 = Group 2 4 = Group 4 6 = Group 6 0 = No 1 = Yes 0 = 57.6 Kbps 1 = 115.2 Kbps 2 = 230.4 Kbps Reserved. Must be 0 on a write, returns 0
3 4
40404 40405
01 02
0 0
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
40406 40407 40408 40409 40410 40411 40412 40413 40414 40415 40416 40417 40418 40419 40420
Reserved
201
Appendix A
DeviceNet Element No. 0 1 2 Modbus Address 40401 40402 40403 Element name Password Node address (MAC ID) Baud rate Range 09999 064 04 Default Value 0 63 0 Comment Valid password required to change configuration data. Returns -1 Address 64 enables remote node address programming; there is no actual node address of 64 defined for the DeviceNet network 0 = 125 Kbps 1 = 250 Kbps 2 = 500 Kbps 3 = Auto 4 = Programmable 0 = hold CAN chip in reset 1 = reset CAN chip and continue communication 0 = Compliant with prior versions, word order swapped 1 = CIP compliant, little Endian Reserved. Must be 0 on a write, returns 0
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
40404 40405 40406 40407 40408 40409 40410 40411 40412 40413 40414 40415 40416 40417 40418 40419 40420
01 01 0
0 0 0
202
Appendix A
RS-232 Element No. 0 1 Modbus Address 40401 40402 Element name Password Hardware port Range 09999 01 Default Value 0 0 Comment Required to change configuration data. Returns -1 Select active port 0 = RS-232 port 1 = Native RS-485 port Communication protocol for the native communication port. 0 = DF1 half-duplex slave 1 = Modbus RTU slave 2 = Auto Sense - Selects the protocol based on the incoming communication packets 3 = DF1 full-duplex Specifies the delay before responding to an external request., useful with slow external devices (such as RF modems) 0 = 1.2 Kbps 1 = 2.4 Kbps 2 = 4.8 Kbps 3 = 9.6 Kbps 4 = 19.2 Kbps 5 = 38.4 Kbps 6 = 57.6 Kbps Identifies the device on the link. 0 is typically used by the DF1 master. 255 is the broadcast address Parity, number of data bits, number of stop bits 0 = No parity, 8 data bits, 1 stop bit 1 = Even parity, 8 data bits, 1 stop bit 2 = Odd parity, 8 data bits, 1 stop bit Data flow control for RS-232/RS-485 port. 0 = None 1 = Hardware RTS/CTS
40403
Protocol
03
40404
Delay
015
2 (10 ms)
40405
Baud rate
0 6
5 6
40406 40407
1247 02
(1)
40408
01
8 9 10
RTS On Delay
09995 ms
Inter-character timeout
Specifies the minimum delay between characters that indicates the end of a message packet. 0 = 3.5 character times. 01 0 0 = CRC 1 = BCC
11
40412
Error checking
203
Appendix A
Modbus Address 40413 40414 40415 40416 40417 40418 40419 40420
Range 0
Default Value 0
The default address is the same as the Device ID, which is assigned at the factory and can be found printed on the white label on the side of the master module. The device ID is incremented for each device.
204
Appendix A
Metering Voltage, Current, and Frequency Result Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F15 38 14 14 Floating point Read only All
User Configurable No
Metering Voltage, Current, and Frequency Result Element Modbus No. Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 30101-2 30103-4 30105-6 30107-8 30109-10 30111-12 30113-14 30115-16 30117-18 30119-20 30121-22 30123-24 30125-26 30127-28 Element name L1 Current L2 Current L3 Current Avg. Current L1-N Voltage L2-N Voltage L3-N Voltage Avg. L-N Voltage L1-L2 Voltage L2-L3 Voltage L3-L1 Voltage Avg L-L Voltage Frequency, last cycle Metering iteration Volts (V) Units Amps (A) Range 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0 999.9x1021 0.0 999.9x1021 0.0999.9x1021 0.0999.9x1021 Hertz (Hz) 40.075.0 032,767 Returns 0 or 999.0 if out of range. Increments by 132,767, rolls over to 0. Comment Refer to Voltage, Current, and Frequency Results on page 30.
205
Appendix A
Metering Sequence Voltage, and Current Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F16 27 15 11 Floating point Read only All
User Configurable No
Metering Sequence Voltage, and Current Results Element No. 0 1 2 3 4 5 6 7 Modbus Address 30201-02 30203-04 30205-06 30207-08 30209-10 30211-12 30213-14 30215-16 Element name L4 (Zero sequence) Current Positive Sequence Current Negative Sequence Current % Current unbalance Positive Sequence Voltage Negative Sequence Voltage % Voltage unbalance Phase rotation Per Cent Per Cent Volts (V) Units Amps (A) Range 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0100.0 0.0999.9x1021 0.0999.9x1021 0.0100.0 02 0 = No rotation. 1 = ABC rotation. 2 = ACB rotation. Average of the last 1 or 8 cycles. Returns 0 or 999.0 if out of range. 0 = V1, 1 = V2, 2 = V3. Increments by 132,767, rolls over to 0. Comment Refer to Symmetrical Component Analysis Results on page 31.
8 9 10
206
Appendix A
Metering Power Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F17 31 16 13 Floating point Read only All
User Configurable No
Metering Power Results Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 Modbus Address 30301-02 30303-04 30305-06 30307-08 30309-10 30311-12 30313-14 30315-16 30317-18 30319-20 30321-22 30323-24 30325-26 Element name L1 Real Power L2 Real Power L3 Real Power Total Real Power L1 Reactive Power L2 Reactive Power L3 Reactive Power Total Reactive Power L1 Apparent Power L2 Apparent Power L3 Apparent Power Total Apparent Power Metering iteration Units Range Comment Real power per phase, signed to show direction. Refer to Power Results on page 32.
Watts (W) 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0 999.9x1022 Volt-amps 0.0999.9x1022 reactive (VAR) 0.0 999.9x1022 0.0999.9x1022 0.0999.9x1022 Volt-amps 0.0999.9x1022 (VA) 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 032,767
Total power signed to show direction. Reactive power per phase, signed to show direction.
Total reactive power, signed to show direction. Apparent power per phase.
207
Appendix A
Metering Demand Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F18 25 17 10 Floating point Read only All
User Configurable No
Metering Demand Results Element No. 0 1 2 3 4 5 6 7 8 9 Modbus Address 30401-02 30403-04 30405-06 30407-08 30409-10 30411-12 30413-14 30415-16 30417-18 30419-20 Element name Demand Current Demand Power Demand Reactive Power Demand Apparent Power Projected Demand I Projected Demand W Projected Demand VAR Projected Demand VA Elapsed demand period time Metering iteration Units Amps (A) Range 0.0999.9x1021 Comment Refer to Energy Results on page 34.
Watts (W) 0.0999.9x1021 VAR VA Amps Watts VAR VA Minutes 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 032,767 The time elapsed within the current demand period. Increments by 132,767, rolls over to 0. Refer to Projected Demand Calculation on page 36.
208
Appendix A
Metering Power Factor Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F19 33 18 13 Floating point Read only All
User Configurable No
Metering Power Factor Results Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 Modbus Element name Address 30501-02 L1 True Power Factor 30503-04 L2 True Power Factor 30505-06 L3 True Power Factor 30507-08 Three-phase True PF 30509-10 L1 Displacement Power Factor 30511-12 L2 Displacement Power Factor 30513-14 L3 Displacement Power Factor 30515-16 Three-phase Displacement PF 30517-18 L1 Distortion Power Factor 30519-20 L2 Distortion Power Factor 30521-22 L3 Distortion Power Factor 30523-24 Three-phase Distortion PF 30525-26 Metering iteration Units Percent Range -100100 -100100 -100100 -100100 -100100 -100100 -100100 -100100 0100 0100 0100 0100 032,767 Increments by 132,767, rolls over to 0. The ratio between the magnitude of the fundamental and the sum of the magnitudes for all of the current harmonics. Cosine of the phase angle between the fundamental voltage and current. + = Lead - = Lag Comment Ratio between power and apparent power. + = Lead - = Lag
209
Appendix A
Metering Real and Apparent Energy Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N20 29 19 (Write), 20 (Read) 23 Integer Read / Write All
User Configurable No
Metering Real and Apparent Energy Results Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Modbus Address 40501 40502 40503 40504 40505 40506 40507 40508 40509 40510 40511 40512 40513 40514 40515 40516 40517 40518 40519 40520 40521 40522 40523 Metering iteration 032,767 Increments by 132,767, rolls over to 0. kVAh ### x 109 ### x 106 ### x 103 ### x 100 ### x 10-3 -999999 KVAh kWh net ### x 109 ### x 106 ### x 103 ### x 100 ### x 10-3 -999999 kWh reverse ### x 109 ### x 106 ### x 103 ### x 100 ### x 10-3 -999999 Element Name Password Parameter select kWh forward ### x 109 ### x 106 ### x 103 ### x 100 ### x 10-3 Range 09999 0 to 7 (bitfield) -999999 Units kWh Default Value 0 Comment Required to clear or preset energy counters. Returns -1. Refer to How to Clear or Preset Energy Counters by Using Communication on page 120.
210
Appendix A
Metering Reactive Energy and Amp-hour Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N21 30 21 (Write), 22 (Read) 23 Integer Read/Write All
User Configurable No
Metering Reactive Energy and Amp-hour Results Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Modbus Address 40601 40602 40603 40604 40605 40606 40607 40608 40609 40610 40611 40612 40613 40614 40615 40616 40617 40618 40619 40620 40621 40622 40623 Metering iteration 032,767 Increments by 132,767, rolls over to 0. kAh ### x 109 -999999 ### x 106 ### x 103 ### x 100 ### x 10-3 kAh kVARh net ### x 109 -999999 ### x 106 ### x 103 ### x 100 ### x 10-3 kVARh reverse ### x 109 -999999 ### x 106 ### x 103 ### x 100 ### x 10-3 Element name Range Units Default Value Password Parameter select kVARh forward 09999 07 ### x 109 -999999 ### x 106 ### x 103 ### x 100 ### x 10-3 kVARh 0 Required to clear or preset energy counters. Returns -1. Refer to How to Clear or Preset Energy Counters by Using Communication on page 120. Comment
211
Appendix A
Selftest/Diagnostic Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N22 36 23 27 Integer Read only All
User Configurable No
Selftest/Diagnostic Results Element No. 0 1 2 3 Modbus Address 30601 30602 30603 30604 Element name Bulletin number Series Overall status Data Acquisition status Range 1404 08 0 = A, 1 = B 0 = OK 0 = OK bit 0 = overall status; 0 = pass, 1 = fail bit 1 = reserved bit 2 = data bus connection failure bit 3 = address test failure 0 = OK 0 = OK 0 = OK Non-zero indicates corruption of nonvolatile memory. This does not cause product to shutdown. The error is cleared on a reset/power cycle. If this error is detected, date/time, and energy values are reset. 0 = OK or no optional communication present 0 = OK or no DM connected 0 = OK 0 = OK bit 0 = overall status; 0 = pass, 1 = fail bit 1 = boot code checksum failure bit 2 = application code checksum failure bit 3 = calibration CRC failure bit 4 = no calibration data bit 5 = wrong application firmware loaded 0 = OK bit 0 = read/write test failure 100 indicates version 1.00, 103 indicates version 1.03 100 indicates version 1.00, 101 indicates version 1.01 Comment
4 5 6
7 8 9 10
Option communication status Display module status Watchdog status Code FLASH status
11 12 13
09999 09999
212
Appendix A
Selftest/Diagnostic Results Element No. 14 15 16 17 18 19 20 21 22 23 24 25 Modbus Address 30615 30616 30617 30618 30619 30620 30621 30622 30623 30624 30625 30626 Element name ASIC build # Option communication FRN Display module FRN Reserved Digital board revision Analog board revision Reserved Reserved MM Device ID Master module type, current Display module type Option communication type Range 09999 09999 09999 0 07 07 0 0 0255 4,5,6,or 8 01 Comment Revision number of the code that was used to fabricate the ASIC. 100 indicates version 1.00, 103 indicates version 1.03 0 = none (catalog numbers ending in -000, -232) 104 indicates version 1.04, 105 indicates version 1.05 Returns 0 if no DM connected Returns 0 0 = 02A, 1 = 03A 0 = 02A, 1 = 03A Returns 0 Returns 0 Sequentially assigned at time of manufacture. May not be changed. 4 = M4, 5 = M5, 6 = M6, 8 = M8; reflects any upgrades 0 = No display module connected 1 = 1404-DM connected to master module 00 = No optional communication (native RS-485 only) 81 = DeviceNet version 1 82 = ControlNet 84 = Remote I/O 86 = RS-232 88 = DeviceNet version 2 89 = IEC870 comm card Indicates revenue metering accuracy class as manufactured (refer to page 29). 0 = Class 1 1 = Class 0.5 2 = Class 0.2 This is not truly a data table, but a reply to a PCCC diagnostic status request (used by RSWho to display text and an icon for the Powermonitor 3000 unit). This data is not accessible using Modbus.
26
30627
Accuracy Class
02
TIP
DF1 PCCC Diagnostic Status Reply Parameters Byte 1 Bits 01 23 47 2 3 4 07 07 07 Type extender Extended interface type Extended processor type EE 36h = DF1 half-duplex slave (via native RS485 port or RS-232 port) 65h = Ethernet 8Ah; 1404 Powermonitor 3000 products Contents Mode/status Description Unused
213
Appendix A
DF1 PCCC Diagnostic Status Reply Parameters Byte 5 616 1724 Bits 04 57 All All Catalog number (in ASCII) Catalog number written into the device at time of production or calibration. For example, 1404-M4-05-A-RIO Product Specific Unused Contents Series/revision Description Unused
214
Appendix A
Setpoint Setup/Read-back Select and Status Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N23 22 24 (Write), 25 (Read) 16 Integer Read / Write All
User Configurable No
Setpoint Setup/Read-back Select and Status Element Modbus No. Address 0 1 2 3 4 5 40701 40702 40703 40704 40705 40706 Element name Password Setpoint number Read-back mode Setpoint type Range 09999 110 (M4, M5) 120 (M6, M8) 01 052 Units Depends on setpoint type Default Value 0 0 0(1) 0 0(1) Comment Required for configuration, -1 for readback select, returns -1. Refer to Writing Setpoint Configuration by Using Communication on page 134.
6 7
40707 40708
-421 09999
0(1) 0(1)
8 9
40709 40710
-421 03600 (M4, M5) Seconds 030,000 (M4, M5) (M6, M8) 0.1 s (M6, M8) 03600 (M4, M5) Seconds 030,000 (M4, M5) (M6, M8) 0.1 s (M6, M8) 032 (M4, M5) 043 (M6, M8) 01 -
0(1) 0
10
40711
Release delay
11 12
40712 40713
0(1) 0
215
Appendix A
Setpoint Setup/Read-back Select and Status Element Modbus No. Address 13 14 15 40714 40415 40716 Element name Accumulated time Integer Accumulated time Exponent Clear time accumulator command Range 09999 -121 01 Units Seconds Default Value 0 Comment
(1)
On the M6 and M8, setpoint #19 and #20 default to detect voltage sag and voltage swell. See Sag and Swell, page 174.
List of Setpoint Types Parameters Applies to PM3000 Type List of Setpoint Types Param. No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Parameter Name Not used Voltage(1) Current(1) Voltage unbalance Current unbalance Neutral current W VAR VA Total true PF Total disp PF Total dist PF W demand VAR demand VA demand Amp demand Projected amp demand Projected W Demand Projected VAR Demand Projected VA Demand Frequency Phase rotation M4 M5 M M Comment 6 8 Disables the setpoint Refer to Metering Voltage, Current, and Frequency Result Parameters Refer to Metering Sequence Voltage, and Current Results Parameters Refer to Metering Power Results Parameters Refer to Metering Power Factor Results Parameters Refer to Metering Demand Results Parameters Refer to Metering Voltage, Current, and Frequency Result Parameters Refer to Metering Sequence Voltage, and Current Results Parameters Setpoint Setup/Read-back Select and Status Parameters on page 215. See table
216
Appendix A
Parameter Name Crest factor voltage Crest factor current Crest factor I4 IEEE THD voltage(1) IEEE THD current(1) IEEE THD I4 IEC THD voltage IEC THD I4 Status input 1 Status input 2 Any status input
(1) (1)
M4 M5
M M Comment 6 8 Refer to Harmonic Results; THD, Crest Factor, and More Parameters Refer to Discrete Data Parameters Refer to Setpoint Output Actions Parameters Refer to Sag and Swell on page 174 Triggers a setpoint when a transient has been detected
Setpoint #1 time accumulator Setpoint #2 time accumulator Setpoint #3 time accumulator Setpoint #4 time accumulator Setpoint #5 time accumulator Setpoint #6 time accumulator Setpoint #7 time accumulator Setpoint #8 time accumulator Setpoint #9 time accumulator Setpoint #10 time accumulator Voltage Sag(2) Voltage Swell(2) Transient detected(2) Avg IEEE THD V Avg IEEE THD I Avg IEC thd V Avg IEC thd I Avg Crest Factor V Avg Crest Factor I
A setpoint activates when the magnitude of any phase passes the activation limit and releases when all phases pass the release limit in the appropriate direction for the setpoint evaluation condition. These setpoint types apply only to the applicable Powermonitor 3000 models and will appear as inactive on other models.
(2)
217
Appendix A
Setpoint Output Actions Parameters Applies to PM3000 Type Refer to Setpoint Setup/Read-back Select and Status Parameters on page 215 See table
Setpoint Output Actions Param. # 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Parameter Name None Energize relay and set alarm flag 1 Energize KYZ and set alarm flag 2 Set alarm flag 3 Set alarm flag 4 Set alarm flag 5 Set alarm flag 6 Set alarm flag 7 Set alarm flag 8 Set alarm flag 9 Set alarm flag 10 Set alarm flag 11 Set alarm flag 12 Set alarm flag 13 Set alarm flag 14 Set alarm flag 15 Set alarm flag 16 Save a trend log record Clear kWh result Clear kVARh result Clear kVAh result Clear Ah result Clear all energy results M4 M5 M M Comment 6 8 No output action, but recorded in the event log and Setpoint status recorded Refer to Discrete Data Parameters Saves record even if periodic trending is disabled
218
Appendix A
Setpoint Output Actions Param. # 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Parameter Name Clear setpoint #1 time Clear setpoint #2 time Clear setpoint #3 time Clear setpoint #4 time Clear setpoint #5 time Clear setpoint #6 time Clear setpoint #7 time Clear setpoint #8 time Clear setpoint #9 time Clear setpoint #10 time Clear setpoint #11 time Clear setpoint #12 time Clear setpoint #13 time Clear setpoint #14 time Clear setpoint #15 time Clear setpoint #16 time Clear setpoint #17 time Clear setpoint #18 time Clear setpoint #19 time Clear setpoint #20 time Capture oscillograph M4 M5 M M Comment 6 8 Clears the corresponding setpoint time accumulator Triggers a capture per the current oscillography configuration
219
Appendix A
Trend Log Configuration/Read-back Record Select Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N24 34 26 (Write), 27 (Read) 26 Integer Read / Write All
User Configurable No
Trend Log Configuration/Read-back Record Select Element Modbus Element Name No. Address 0 1 2 3 4 40801 40802 40803 40804 40805 Password DeviceNet unique write identifier Reserved Read-back mode Logging interval Range 09999 -32,768 32,767 0 06 -13600 Default Comment Value 0 0 0 2 Required for configuration, -1 for readback select, returns -1 Refer to DeviceNet Unique Write Identifier on page 103 Must be 0 on a write; returns 0 Refer to Setting up the Trend Log on page 151, and Reading Data from the Trend Log on page 152
900 Expressed in seconds (15 min) -1 = synchronize logging with demand interval 0 = disable periodic logging 0 0 122 126 100 0 Must be 0 on a write; returns 0 Refer to Setting up the Trend Log on page 151 Defaults: Parameter 1: 122, Net Kilowatt-hours Parameter 2: 126, Net kVAR-hours Parameter 3: 100, Demand watts 0 = Overwrite 1 = Fill and hold 0 = no action 1 = clear trend log; returns 0 Number of records = element 7 x 1000 + element 8
5 6 7 8 9 10 11 12 13 14 15 16 17
40806 40807 40808 40809 40810 40811 40812 40813 40814 40815 40816 40817 40818
Logging mode Clear trend log command Total records logged x 1000 Total records logged x 1 Reserved Parameter #1 selection Parameter #2 selection Parameter #3 selection Parameter #4 selection Parameter #5 selection Parameter #6 selection Parameter #7 selection Parameter #8 selection
220
Appendix A
Trend Log Configuration/Read-back Record Select Element Modbus Element Name No. Address 18 19 20 21 22 23 24 25
(1)
Range 0301
Parameter #9 selection(1) Parameter #10 selection Parameter #11 selection Parameter #12 selection Parameter #13 selection Parameter #14 selection Parameter #15 selection Parameter #16 selection
For DeviceNet Powermonitor units you may configure parameters 916 but the Trend Log Results Parameters tabke returns only the first eight parameters.
Trend Log Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Trend Log Results Element No. 0 1 2 3 4 5 Modbus Address 30701-02 30703-04 30705-06 30707-08 30709-10 30711-12 Element Name Reserved Internal Identifier Timestamp; Year Month/Date Hour/minute Seconds/hsec Range 0 015 19982097 01011231 00002359 00005999 Comment Returns 0 Increment from 115 for each record, rolls to 0 Date and time record was recorded. Refer to Expressing Data in Data Tables on page 82 F25 48 28 14 (DeviceNet network only), 22 (All other communication types) Floating Point Read only All
221
Appendix A
Trend Log Results Element No. 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Modbus Address 30713-14 30715-16 30717-18 30719-20 30721-22 30723-24 30725-26 30727-28 30729-30 30731-32 30733-34 30735-36 30737-38 30739-40 30741-42 30743-44 Element Name User selected parameter #1 User selected parameter #2 User selected parameter #3 User selected parameter #4 User selected parameter #5 User selected parameter #6 User selected parameter #7 User selected parameter #8 User selected parameter #9 User selected parameter #10 User selected parameter #11 User selected parameter #12 User selected parameter #13 User selected parameter #14 User selected parameter #15 User selected parameter #16 Range Comment The values of parameters that were configured.
222
Appendix A
Min/Max Log Configuration/Read-back Select Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N26 13 29 (Write), 30 (Read) 9 Integer Read / Write All
User Configurable No
Min/Max Log Configuration/Read-back Select Element Modbus Element Name No. Address 0 1 2 3 4 5 6 7 8 40901 40902 40903 40904 40905 40906 40907 40908 40909 Password Min/max parameter to read Read-back mode Enable/disable Min/max log Clear min/max log Range 09999 073 01 01 01 Default Comment Value 0 1 0 1 0 Required for configuration, -1 for readback select, returns -1. Refer to Interfacing with the Min/Max Log by Using Communication on page 154.
Timestamp of last min/max clear; year 19982097 month/day 01011231 hour/minute second/hsec 00002359 00005999
223
Appendix A
Min/Max Log Parameter List Parameters Applies to PM3000 Type Min/Max Log Configuration/Read-back Select Parameters on page 223 Min/Max Log Results Parameters on page 227 All
Min/Max Log Parameter List Param No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Parameter Name L1 Current L2 Current L3 Current Avg Current L1-N Voltage L2-N Voltage L3-N Voltage Avg L-N Voltage L1-L2 Voltage L2-L3 Voltage L3-L1 Voltage Avg L-L Voltage Frequency, last cycle L4 Current Positive Sequence Current Negative Sequence Current % Current unbalance Positive Sequence Voltage Negative Sequence Voltage % Voltage unbalance Average frequency Refer to Metering Sequence Voltage, and Current Results Parameters Comment Refer to Metering Voltage, Current, and Frequency Result Parameters
224
Appendix A
Min/Max Log Parameter List Param No. 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 Parameter Name L1 Real Power L2 Real Power L3 Real Power Total Real Power L1 Reactive Power L2 Reactive Power L3 Reactive Power Total Reactive Power L1 Apparent Power L2 Apparent Power L3 Apparent Power Total Apparent Power Demand Current Demand Power Demand Reactive Power Demand Apparent Power Projected Demand I Projected Demand W Projected Demand VAR Projected Demand VA L1 True Power Factor L2 True Power Factor L3 True Power Factor Three-phase True PF L1 Displacement Power Factor L2 Displacement Power Factor L3 Displacement Power Factor Three-phase Displacement PF L1 Distortion Power Factor L2 Distortion Power Factor L3 Distortion Power Factor Three-phase Distortion PF Refer to Metering Power Factor Results Parameters Refer to Metering Power Factor Results Parameters Refer to Metering Demand Results Parameters Comment Refer to Metering Power Results Parameters
225
Appendix A
Min/Max Log Parameter List Param No. 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 Parameter Name V1 % IEEE THD I1 % IEEE THD V2 % IEEE THD I2 % IEEE THD V3 % IEEE THD I3 % IEEE THD I4 % IEEE THD V1 % IEC thd (DIN) I1 % IEC thd (DIN) V2 % IEC thd (DIN) I2 % IEC thd (DIN) V3 % IEC thd (DIN) I3 % IEC thd (DIN) I4 % IEC thd (DIN) V1 Crest Factor I1 Crest Factor V2 Crest Factor I2 Crest Factor V3 Crest Factor I3 Crest Factor I4 Crest Factor Comment Refer to Harmonic Results; THD, Crest Factor, and More Parameters
226
Appendix A
Min/Max Log Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Min/Max Log Results Element No. 0 1 2 3 4 5 6 7 8 9 10 Modbus Address 30801-02 30803-04 30805-06 30807-08 30809-10 30811-12 30813-14 30815-16 30817-18 30819-20 30821-22 MAX timestamp; year month/day hour/minute sec/hsec Element Name Parameter # being returned MIN value for parameter MAX value for parameter MIN timestamp; year month/day hour/minute sec/hsec Range 173 -999.9x10 999.9x10
21 21
User Configurable No
Comment Refer to Reading Data from the Trend Log on page 152
-999.9x1021999.9x1021 19982097 01011231 00002359 0000 5999 19982097 01011231 00002359 00005999
227
Appendix A
Event Log Configuration/Read-back Record Select Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Applies to: N28 9 32 (Write), 33 (Read) 6 Integer Read / Write All Event Log Results Parameters on page 229
User Configurable No
Event Log Configuration/Read-back Record Select Element Modbus No. Address 0 1 2 3 4 5 41001 41002 41003 41004 41005 41006 Element Name Password Range 09999 Default Comment Value 0 0 2 0 1 Required for configuration, -1 for readback select, returns -1 Refer to DeviceNet Unique Write Identifier on page 103 Refer to Configuring the Event Log by Using Communication on page 146
DeviceNet unique write identifier -32,76832,767 Read-back mode Enable/disable logging status input changes # events in the event log Enable/disable logging of time/date set 06 01 150 (M4,M5) 1100 (M6, M8) 01
228
Appendix A
Event Log Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Event Log Results Element Modbus No. Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 30901 30902 30903 30904 30905 30906 30907 30908 30909 30910 30911 30912 30913 30914 30915 30916 30917 30918 M4 M M Element Name M5 6 8 Reserved Internal identifier Timestamp of event; Event type Event code Setpoint type Setpoint evaluation condition Setpoint level Range 0 0 32768 Year 19982097 Month/day Hour/minute 01011231 Second/hsec 00002359 00005999 019 052 05 integer 09999 exponent -2121 03600 (M4, M5) 030,000 (M6, M8) 032 (M4, M5) 043 (M6, M8) integer 09999 exponent -421 0999 0 Returns 0 Refer to List of Event Types Parameters Refer to Reading Data from the Event Log by Using Communication on page 147 Comment Returns 0 Refer to Reading Data from the Event Log by Using Communication on page 147 Refer to Expressing Data in Data Tables on page 82 N29 21 34 14, 17, or 18 (see table) Integer Read only See table
User Configurable No
Setpoint action/release delay Setpoint action Sustain limit timer Capture identifier Reserved
229
Appendix A
Status Error Codes Bits bit 0 bit 1 bit 2 bit 3 bit 4 bit 5 bit 6 bit 7 bit 8 bit 9 bit 10 bit 11 bit 1215 Hex 0001h 0002h 0004h 0008h 0010h 0020h 0040h 0080h 0100h 0200h 0400h 0800h 1000h8000h Description Master module code flash status Master module data flash status Master module RAM Status Reserved for factory use Master module NVRAM status Master module data acquisition status Master module real time clock status Reserved for factory use Reserved for factory use Display module status Master module watchdog timer status Master module optional communication status Reserved for factory use
230
Appendix A
List of Event Types Parameters Applies to PM3000 Type List of Event Types Event Code. 0 1 2 3 4 5 6 7 8 8 8 8 8 8 8 8 8 8 8 8 8 9 10 11 12 13 14 15 16 M4 M M Event Type M5 6 8 No event Setpoint triggered Setpoint released Relay force energized Relay force de-energized Relay force released Status input set Status input cleared kWh counter set or cleared kVARh counter set or cleared kVAh counter set or cleared Ah counter set or cleared All energy counters cleared Trend log cleared Min/max log cleared Factory defaults restored Status input #1 counter cleared Status input #2 counter cleared Reserved Single setpoint timer cleared All setpoint timers cleared Power-up Power-down Selftest failure Date/time set Change of setpoint config data NVRAM Clr Transient detected 1 2 3 4 5 6 7 8 9 10 11 12 13 0 0 Status Error Code 0 0 0 NVRAM has been cleared due to an extended loss of control power or internal error Control power was applied Control power was lost or internal reset occurred Refer to Status Error Codes (bitfield) The date and/or time was set or altered Records command action Status Input Number Relay Number Event Command Code 0 Setpoint Number Comment The log starts with no events recorded A setpoint activated A previously active setpoint released 1 = Form C relay, 2 = KYZ Event Log Results Parameters on page 229 See table
231
Appendix A
List of Event Types Event Code. 17 18 19 M4 M M Event Type M5 6 8 Reserved External Demand Sync Timeout Comm Card Reset Event Command Code Comment Reserved The demand delay expired before the next expected external demand sync An unexpected comm card condition has been detected and the master module has reset the comm card in an attempt to resume normal operation
232
Appendix A
User-configured Table Setup Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Applies to N30 35 35 (Write), 36 (Read) 26 Integer Read /Write All User-configured Table Results Parameters on page 235
User Configurable No
User-configured Table Setup Element Modbus Element Name No. Address 0 1 41101 41102 Password DF1 or Ethernet (CSP) File No. RIO BT No. DeviceNet, EtherNet/IP, or ControlNet Assy Inst. Modbus 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 41103 41104 41105 41106 41107 41108 41109 41110 41111 41112 41113 41114 41115 41116 41117 Range Default Value 09999 31 62 1, 37 1000 0 31 62 37 31 0 71 (L1-L2 V) 72 (L2-L3 V) 73 (L3-L1 V) 63 (I1) 64 (I2) 65 (I3) 90 (W) 98 (VA) 94 (VAR) 111 (PF) 100 (Dmd W) 122 (kWh) 130 (Status) 14 (Year) Required for configuration, returns -1 Refer to User-configured Data Table on page 121 Comment
DeviceNet, EtherNet/IP, or 01 ControlNet instance 1 data type Selection for parameter #1 Selection for parameter #2 Selection for parameter #3 Selection for parameter #4 Selection for parameter #5 Selection for parameter #6 Selection for parameter #7 Selection for parameter #8 Selection for parameter #9 Selection for parameter #10 Selection for parameter #11 Selection for parameter #12 Selection for parameter #13 Selection for parameter #14 0301
233
Appendix A
User-configured Table Setup Element Modbus Element Name No. Address 17 18 19 20 21 22 23 24 25 41118 41119 41120 41121 41122 41123 41124 41125 41126 Selection for parameter #15 Selection for parameter #16 Selection for parameter #17 Selection for parameter #18 Selection for parameter #19 Selection for parameter #20 Selection for parameter #21 Selection for parameter #22 Selection for parameter #23 Range Default Value 0301 21 (Mo/Dy) 22 (Hr/min) 23 (Sec/hsc) 0 Parameters 1523 not supported by the DeviceNet network Comment
234
Appendix A
User-configured Table Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements F31 62 37 14 (DeviceNet network) or 23 (All other communication options) Floating Point Read only All
User-configured Table Results Element Modbus No. Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 31001-02 31003-04 31005-06 31007-08 31009-10 31011-12 31013-14 31015-16 31017-18 31019-20 31021-22 31023-24 31025-26 31027-28 31029-30 31031-32 31033-34 31035-36 31037-38 31039-40 31041-42 31043-44 31045-46 Element Name User selected parameter #1 User selected parameter #2 User selected parameter #3 User selected parameter #4 User selected parameter #5 User selected parameter #6 User selected parameter #7 User selected parameter #8 User selected parameter #9 Range Comment Parameters previously setup during a write to the User-configured Table Setup Parameters table
User selected parameter #10 User selected parameter #11 User selected parameter #12 User selected parameter #13 User selected parameter #14 User selected parameter #15 User selected parameter #16 User selected parameter #17 User selected parameter #18 User selected parameter #19 User selected parameter #20 User selected parameter #21 User selected parameter #22 User selected parameter #23 The DeviceNet network supports a maximum of 14 user-configured parameters
235
Appendix A
Write Error Status Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Write Error Status Element Modbus No. Address 0 1 31101 31102 Element Name File, instance or BT number Offending Element Range Default Comment Value Identifies data table written to last, value depends on comms type. For Modbus, starting address of table written to last. -1 = Last write was successful 026 = first unacceptable element of unsuccessful write For Remote I/O Only: 0 = Last write was successful 127 = First unacceptable word of unsuccessful write For Modbus Only: -1 = Last write was successful 40,00142,001 - first unacceptable address of unsuccessful write. N32 4 38 2 Integer Read only All
User Configurable No
236
Appendix A
Harmonic Analysis Configuration/Read-back Select Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Applies to: N33 14 39 (Write), 40 (Read) 9 Integer Read /Write See table Harmonic Results; THD, Crest Factor, and More Parameters on page 238 (All models) Harmonic Results; Odd Harmonics 121 Parameters on page 239,Harmonic Results; Odd Harmonics 2341 Parameters on page 240, Harmonic Results; Even Harmonics 220 Parameters on page 241, Harmonic Results; Even Harmonics 2240 Parameters on page 242 (M6 & M8) Harmonic Results; Odd Harmonics 4363 Parameters on page 256, Harmonic Results; Even Harmonics 4262 Parameters on page 257 (M8 only)
User Configurable No
Harmonic Analysis Configuration/Read-back Select Element No. 0 1 2 3 4 5 Modbus M4 M M Element Name Address M5 6 8 41201 41202 41203 41204 41205 41206 Password Channel Read-back mode Reserved Individual harmonic data type Reserved Enable/disable Harmonics Reserved IEEE-519 Max IscInteger 6 41207 Reserved IEEE-519 Max IscExponent 7 41208 Reserved IEEE 519 Max IdmndInteger 8 41209 Reserved IEEE 519 Max Idmnd Exponent Range 09999 19 01 0 01 0 01 0 09999 0 -421 0 09999 0 -421 Default Comment Value 0 1 0 0 0 0 1 0 0 0 0 0 0 0 0 Required for configuration, -1 for readback select, returns -1. Refer to Configuring Harmonic Analysis on page 171.
237
Appendix A
Harmonic Results; THD, Crest Factor, and More Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F34 23 41 9 (M4, M5); 10 (M6, M8) Floating Point Read only See table
User Configurable No
Harmonic Results; THD, Crest Factor, and More Element Modbus No. Address 0 1 2 3 4 5 31201-02 31203-04 31205-06 31207-08 31209-10 31211-12 M4 M M Element Name M5 6 8 Channel number % IEEE THD % IEC thd (DIN) Crest Factor Reserved TIF 6 31213-14 Reserved K-Factor 7 31215-16 Reserved IEEE-519 TDD 8 9 31217-18 31219-20 Reserved IEEE-519 Pass/Fail Reserved FFT iteration Range 19 0.01000.0 0.01000.0 0.010.0 0 0.0999.9x1022 0 0.0999.9x1022 0 0.0999.9x1022 0 -11 0 032,767 Comment Refer to Reading Harmonic Analysis Data on page 172
238
Appendix A
Harmonic Results; Odd Harmonics 121 Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F35 39 42 14 Floating Point Read only M6, M8 only
User Configurable No
Harmonic Results; Odd Harmonics 121 Element Modbus No. Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Element Name Channel # returned Type of harmonic data returned 1st Harmonic (Fundamental) 3rd Harmonic 5th Harmonic 7th Harmonic 9th Harmonic 11th Harmonic 13th Harmonic 15th Harmonic 17th Harmonic 19th Harmonic 21st Harmonic FFT iteration Range 17 01 0.0 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 032,767 Comment Refer to Reading Harmonic Analysis Data on page 172
239
Appendix A
Harmonic Results; Odd Harmonics 2341 Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F36 40 43 14 Floating Point Read only M6, M8 only
User Configurable No
Harmonic Results; Odd Harmonics 2341 Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Modbus Address Element Name Channel # returned Type of harmonic data returned Reserved 23rd Harmonic 25th Harmonic 27th Harmonic 29th Harmonic 31st Harmonic 33rd Harmonic 35th Harmonic 37th Harmonic 39th Harmonic 41st Harmonic FFT iteration Range 1 7 01 0 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 032,767 Comment Refer to Reading Harmonic Analysis Data on page 172
240
Appendix A
Harmonic Results; Even Harmonics 220 Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F37 41 44 14 Floating Point Read only M6, M8 only
User Configurable No
Harmonic Results; Even Harmonics 220 Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Modbus Address Element Name Channel # returned Type of harmonic data returned Reserved 2nd Harmonic 4th Harmonic 6th Harmonic 8th Harmonic 10th Harmonic 12th Harmonic 14th Harmonic 16th Harmonic 18th Harmonic 20th Harmonic FFT iteration Range 1 7 0 1 0 0.0999.9x1022 0.0999.9x1022 0.0 999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0 999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 032,767 Comment Refer to Reading Harmonic Analysis Data on page 172
241
Appendix A
Harmonic Results; Even Harmonics 2240 Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F38 42 45 14 Floating Point Read only M6, M8 only
User Configurable No
Harmonic Results; Even Harmonics 2240 Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Modbus Address Element Name Channel # returned Type of harmonic data returned Reserved 22nd Harmonic 24th Harmonic 26th Harmonic 28th Harmonic 30th Harmonic 32nd Harmonic 34th Harmonic 36th Harmonic 38th Harmonic 40th Harmonic FFT iteration Range 17 01 0 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 0.0999.9x1022 032,767 Comment Refer to Reading Harmonic Analysis Data on page 172
242
Appendix A
Oscillograph Configuration/Read-back Data Select Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Applies to: N39 15 46 (Write), 47 (Read) 11 Integer Read / Write M6, M8 only Oscillograph Results Parameters
User Configurable No
Oscillograph Configuration/Read-back Data Select Element No. 0 1 2 3 4 5 6 7 8 9 10 Modbus Address Element Name Password Capture No. Channel No. Block No. Read-back mode Clear/trigger command Capture type % Pre-trigger Reserved Capture clear status Capture ready status Range 09999 08 (M6) 02 (M8) 17 See page 161 02 010 -15 0100 0 0255 0255 Default Value 0 1 1 1 0 0 0 90 0 Comment Required for configuration, -1 for readback select, returns -1 Refer to Configuring Oscillography on page 160
243
Appendix A
Oscillograph Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Oscillograph Results Element No. 0 1 2 Modbus Address Element Name Timestamp; Range Month/day 00001231 Hour/minute 00002359 Second/hsec 00005999 Comment Trigger timestamp, see page 82. N40 61 48 29 (DeviceNet network only) 59 (all other communication types) Integer Read only M6, M8 only
User Configurable No
244
Appendix A
Oscillograph Results Element No. 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Modbus Address Element Name Capture # Channel number Block number Capture type Trigger source and capture identifier Trigger position Oscillograph Data Point 1 Oscillograph Data Point 2 Oscillograph Data Point 3 Oscillograph Data Point 4 Oscillograph Data Point 5 Oscillograph Data Point 6 Oscillograph Data Point 7 Oscillograph Data Point 8 Oscillograph Data Point 9 Oscillograph Data Point 10 Oscillograph Data Point 11 Oscillograph Data Point 12 Oscillograph Data Point 13 Oscillograph Data Point 14 Oscillograph Data Point 15 Oscillograph Data Point 16 Oscillograph Data Point 17 Oscillograph Data Point 18 Oscillograph Data Point 19 Oscillograph Data Point 20 Range 18 (M6) 12 (M8) 17 See page 80 05 022999 14600 19200 -81928191 Comment Refer to Reading Oscillograph Data on page 162
245
Appendix A
Oscillograph Results Element No. 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 Modbus Address Element Name Oscillograph Data Point 21 Oscillograph Data Point 22 Oscillograph Data Point 23 Oscillograph Data Point 24 Oscillograph Data Point 25 Oscillograph Data Point 26 Oscillograph Data Point 27 Oscillograph Data Point 28 Oscillograph Data Point 29 Oscillograph Data Point 30 Oscillograph Data Point 31 Oscillograph Data Point 32 Oscillograph Data Point 33 Oscillograph Data Point 34 Oscillograph Data Point 35 Oscillograph Data Point 36 Oscillograph Data Point 37 Oscillograph Data Point 38 Oscillograph Data Point 39 Oscillograph Data Point 40 Oscillograph Data Point 41 Oscillograph Data Point 42 Oscillograph Data Point 43 Oscillograph Data Point 44 Oscillograph Data Point 45 Oscillograph Data Point 46 Oscillograph Data Point 47 Oscillograph Data Point 48 Oscillograph Data Point 49 Oscillograph Data Point 50 Range Comment DeviceNet supports only 20 data points per read.
246
Appendix A
Load Factor Log Configuration/Read-back Select Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Applies to: N41 16 49 (Write), 50 (Read) 6 Integer Read / Write M6, M8 only Load Factor Log Results Parameters on page 248
User Configurable No
Load Factor Log Configuration/Read-back Select Element No. 0 1 2 3 4 5 Modbus Address Element Name Password Record to read-back Read-back mode Clear peak / reset average command Auto clear/reset day Reserved Range 09999 012 01 01 031 0 Default Value 0 0 1 0 31 0 Comment Required for configuration or command, -1 for readback select, returns -1 Refer to Reading the Load Factor Log on page 178
247
Appendix A
Load Factor Log Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F42 43 51 14 Floating Point Read only M6, M8 only
User Configurable No
Load Factor Log Results Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Modbus Address Element Name Peak Demand W Average Demand W Load Factor W Peak Demand VAR Average Demand VAR Load Factor VAR Peak Demand VA Average Demand VA Load Factor VA Peak Demand I Average Demand I Load Factor I Elapsed time Ending month/day/year Range 0.0999.9x1021 0.0999.9x1021 0100.0 0.0999.9x1021 0.0999.9x1021 0100.0 0.0999.9x1021 0.0999.9x1021 0100.0 0.0999.9x1021 0.0999.9x1021 0100.0 0.0999.9x1021 0123199 Comment Refer to Reading the Load Factor Log on page 178
248
Appendix A
Transient Analysis Configuration/Read-back Select Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Applies to F43 44 52 (Write), 53 (Read) 10 Floating Point Read / Write M8 only Transient analysis metering results
User Configurable No
Transient Analysis Configuration/Read-back Select Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 Modbus Address Element Name Password DeviceNet unique write identifier Capture # Cycle # Read-back mode Detection mode Reserved Auto-threshold set command Auto-threshold set duration Auto-threshold set margin Voltage trigger threshold Current trigger threshold Auto-threshold duration time left Range 09999 -32,76832,767 06 112 01 03 0 01 13600 1.0100.0 0.1100.0 0.1100.0 0 Default Comment Value 0 0 1 1 0 1 0 0 10 20.0 10.0 10.0 0 Required for configuration, -1 for readback select, returns -1. Refer to DeviceNet Unique Write Identifier on page 103. Refer to Transient Analysis Configuration on page 180.
249
Appendix A
Transient Analysis Metering Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F44 32 54 14 Floating Point Read only M8 only
User Configurable No
Transient Analysis Metering Results Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Modbus Address Element Name Capture number Cycle number L1-L2 or L1-N Voltage L2-L3 or L2-N Voltage L3-L1 or L3-N Voltage L1 Current L2 Current L3 Current L4 Current Voltage Index at trigger Current Index at trigger Voltage Trigger Threshold Current Trigger Threshold Unique Transient Capture ID Range 16 112 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 -999.0x103999.0x103 -999.0x103999.0x103 0.0999.0x103 0.0999.0x103 030,000 Comment Refer to Reading Transient Analysis Metering Data on page 181.
250
Appendix A
Transient Capture Clear/Read-back Data Select Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Applies to N45 17 55 (Write), 56 (Read) 13 Integer Read / Write M8 only Transient Capture Results Parameters on page 252
User Configurable No
Transient Capture Clear/Read-back Data Select Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 Modbus Address Element Name Password Dnet unique write identifier Capture number Channel number Block number Read-back mode Clear command Reserved Reserved Reserved Capture clear status Capture ready status Reserved Range 09999 Default Comment Value 0 Required for configuration, -1 for readback select, returns -1. Refer to DeviceNet Unique Write Identifier on page 103. Refer to Reading Transient Capture Data on page 182.
251
Appendix A
Transient Capture Results Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N46 60 57 29 (DeviceNet network only); 59 (All other communication types) Integer Read only M8 only
User Configurable No
Transient Capture Results Element No. 0 1 2 Modbus Address Element Name Timestamp; Month/day Hour/minute Second/hsec Range 00001231 00002359 00005999 Comment Capture trigger timestamp, see page 82.
252
Appendix A
Transient Capture Results Element No. 3 4 5 Modbus Address Element Name Capture # Channel number Block number Range 16 17 170 for DeviceNet 128 for all other comms options 0 030,000 0 -81928191 Comment Refer to Reading Transient Capture Data on page 182.
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Reserved Unique Transient Capture ID Reserved Data Point 1 Data Point 2 Data Point 3 Data Point 4 Data Point 5 Data Point 6 Data Point 7 Data Point 8 Data Point 9 Data Point 10 Data Point 11 Data Point 12 Data Point 13 Data Point 14 Data Point 15 Data Point 16 Data Point 17 Data Point 18 Data Point 19 Data Point 20
253
Appendix A
Transient Capture Results Element No. 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 Modbus Address Element Name Data Point 21 Data Point 22 Data Point 23 Data Point 24 Data Point 25 Data Point 26 Data Point 27 Data Point 28 Data Point 29 Data Point 30 Data Point 31 Data Point 32 Data Point 33 Data Point 34 Data Point 35 Data Point 36 Data Point 37 Data Point 38 Data Point 39 Data Point 40 Data Point 41 Data Point 42 Data Point 43 Data Point 44 Data Point 45 Data Point 46 Data Point 47 Data Point 48 Data Point 49 Data Point 50 Range -81928191 Comment The DeviceNet network returns only 20 data points per read.
254
Appendix A
Advanced Metering Configuration Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N47 19 58 (Write), 59 (Read) 10 Integer Read / Write M8 only
User Configurable No
Advanced Metering Configuration Element No. 0 1 2 3 4 5 6 7 8 9 Modbus Address Element Name Password Meter result set Reserved Range 09999 02 0 Default Value 0 0 0 Comment Required for configuration, returns -1. Refer to Advanced Metering Options on page 54. Must be 0 on a write, returns 0.
255
Appendix A
Harmonic Results; Odd Harmonics 4363 Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F48 45 60 14 Floating Point Read Only M8 only
User Configurable No
Harmonic Results; Odd Harmonics 4363 Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Modbus Address Element Name Channel # returned Type of harmonic data returned 43rd Harmonic 45th Harmonic 47th Harmonic 49th Harmonic 51st Harmonic 53rd Harmonic 55th Harmonic 57th Harmonic 59th Harmonic 61st Harmonic 63rd Harmonic FFT iteration 032,767 Range 1 7 01 0.0999.9x1022 Comment Refer to Reading Individual Harmonic Values on page 173.
256
Appendix A
Harmonic Results; Even Harmonics 4262 Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F49 46 61 14 Floating Point Read Only M8 only
User Configurable No
Harmonic Results; Even Harmonics 4262 Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 Modbus Address Element Name Channel # returned Type of harmonic data returned 42nd Harmonic 44th Harmonic 46th Harmonic 48th Harmonic 50th Harmonic 52nd Harmonic 54th Harmonic 56th Harmonic 58th Harmonic 60th Harmonic 62nd Harmonic FFT iteration 032,767 Range 1 7 0 1 0.0999.9x1022 Comment Refer to Reading Individual Harmonic Values on page 173.
257
Appendix A
Catalog Number and WIN Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N51 50 64 29 Integer Read only All
User Configurable No
Catalog Number and WIN Element Modbus No. Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 32301 32302 32303 32304 32305 32306 32307 32308 32309 32310 32311 32312 32313 32314 32315 32316 32317 32318 32319 Original model Current model 09 The model as it was originally built. 4 = M4, 5 = M5 Differs from Original model if field-upgraded Hardware series WIN text character pair #1 WIN text character pair #2 WIN text character pair #3 WIN text character pair #4 WIN text character pair #5 Reserved 0 Returns 0 025 Indicates the series of the product; 0 = A, 1 = B -32,768 WIN (warranty identification number). This is the same 10-character 32,767 alpha-numeric string printed on the master module label. Each element contains a character pair Element Name Catalog # text char pair #1 Catalog # text char pair #2 Catalog # text char pair #3 Catalog # text char pair #4 Catalog # text char pair #5 Catalog # text char pair #6 Catalog # text char pair #7 Reserved 0 Returns 0 Range Comment
-32,768 Catalog number without dashes. Each element contains a character 32,767 pair For each character pair, character 1 = element / 256 and character 2 = remainder The 6th character of the catalog string reflects the Current model of the product
258
Appendix A
Catalog Number and WIN Element Modbus No. Address 19 20 21 22 23 24 25 26 27 28 32320 32321 32322 32323 32324 32325 32326 32327 32328 32329 Element Name Reserved Range 0 Comment Returns 0
259
Appendix A
Network Demand Sync and Time Configuration Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N52 65, 66 20 Integer Read / Write Ethernet
User Configurable No
Network Demand Sync and Time Configuration Element No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Modbus Address 41901 41902 41903 41904 41905 41906 41907 41908 41909 41910 41911 41912 41913 41914 41915 41916 41917 41918 41919 41920 Parameter Name Password Input mode Broadcast port number SNTP IP address 1, octet 1 SNTP IP address 1, octet 2 SNTP IP address 1, octet 3 SNTP IP address 1, octet 4 Time zone Time set update interval SNTP IP address 2, octet 1 SNTP IP address 2, octet 2 SNTP IP address 2, octet 3 SNTP IP address 2, octet 4 SNTP IP address 3, octet 1 SNTP IP address 3, octet 2 SNTP IP address 3, octet 3 SNTP IP address 3, octet 4 Reserved Reserved Reserved 0 0 0 -1212 0 32,766 0255 0 60 s 0 0 0 0 0 0 0 0 0 0 0 Reserved for future use. On a write, only a 0 is accepted. On a read, always returns 0. SNTP IP address 3 is a back-up server address when the secnond address fails. SNTP IP address 2 is a back-up server address when the first address fails. Range Default Description Value On a write, the correct password is required to change configuration data. On a read, -1 is returned. Refer to Network Demand / Time Configuration on page 55.
260
Appendix A
Controller Command Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type Controller Command Element No. 0 Element Name Controller Command Bits 0 Range 032,767 Default Value 0 Comment Refer to Network Demand / Time Configuration on page 55 N53 67 1 Integer Write only Ethernet
User Configurable No
Daylight Saving Time Configuration Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N54 47 68 (Write), 69 (Read) 10 Integer Read / Write All
User Configurable No
Daylight Saving Time Configuration Element No. 0 1 2 3 4 5 6 7 8 9 Modbus Address 42101 42102 42103 42104 42105 42106 42107 42108 42109 43110 Element name Password DST Enable DST Start Month DST Start Day DST Start Day Instance DST Start Hour DST End Month DST End Day DST End Day Instance DST End Hour Range -19999 01 112 06 15 023 112 06 15 023 Default 0 0 3 0 2 2 11 0 1 2 Comment Required for configuration. Returns -1 0 = Disabled, 1 = Enabled 1 = January, 2 = February 0 = Sunday, 1 = Monday 1 = 1st, 2 = 2nd, ... 5 = Last 0 = 12:00 midnight, 1 = 1:00 AM 1 = January, 2 = February 0 = Sunday, 1 = Monday 1 = 1st, 2 = 2nd, ... 5 = Last 0 = 12:00 midnight, 1 = 1:00 AM
261
Appendix A
Time of Use Register Configuration Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N55 49 70 (Write), 71 (Read) 10 Integer Read / Write All
User Configurable No
Time of Use Register Configuration Element No. 0 1 2 3 4 5 6 7 8 9 Modbus Address 42201 42202 42203 42204 42205 42206 42207 42208 42209 42210 Element Name Password Record to read back Reserved Write command Log day Off peak day Mid peak a.m. Mid peak p.m. Peak a.m. Peak p.m. Range -19999 012 0 01 131 0127 04095 Default 0 0 0 0 31 65 1792 120 2048 7 Comment Required for configuration, -1 for readback select, Returns -1 Refer to Configuring the Time-of-use Log on page 157
262
Appendix A
Time of Use Records Real Energy and Demand Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F56 51 72 12 Floating point Read only All
User Configurable No
Time of Use Records Real Energy and Demand Element No. 0 1 2 3 4 5 6 7 8 9 10 11 Modbus Address 32401-02 32403-04 32405-06 32407-08 32409-10 32411-12 32413-14 32415-16 32417-18 33419-20 32421-22 32423-24 Element Name Off-peak real energy Off-peak real energy Off-peak demand Mid-peak real energy Mid-peak real energy Mid-peak demand Peak real energy Peak real energy Peak demand Record number Start date End date Range -999,999.0 999,999.0 -999.999.999 999.999.999 0.0999.9 x 1021 -999,999.0 999,999.0 -999.999.999 999.999.999 0.0999.9 x 1021 -999,999.0 999,999.0 -999.999.999 999.999.999 0.0999.9 x 1021 012 000101991231 000101991231 YYMMDD YYMMDD Start month / day for data stored in this record, inclusive End month / day for data stored in this record, inclusive Units MWh kWh Watts MWh kWh Watts MWh kWh Watts Comment Refer to Reading Time-of-use Log Data on page 158
263
Appendix A
Time of Use Records Reactive Energy and Demand Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F57 52 73 12 Floating point Read only All
User Configurable No
Time of Use Records Reactive Energy and Demand Element No. 0 1 2 3 4 5 6 7 8 9 10 11 Modbus Address 32501-02 32503-04 32505-06 32507-08 32509-10 32511-12 32513-14 32515-16 32517-18 32519-20 32521-22 33523-24 Element Name Off-peak reactive energy Off-peak reactive energy Off-peak demand VARs Mid-peak reactive energy Mid-peak reactive energy Mid-peak demand VARs Peak reactive energy Peak reactive energy Peak demand VARs Record number Start date End date Range -999,999.0 999,999.0 -999.999.999 999.999.999 0.0999.9 x 1021 -999,999.0 999,999.0 -999.999.999 999.999.999 0.0999.9 x 1021 -999,999.0 999,999.0 -999.999.999 999.999.999 0.0999.9 x 1021 012 000101991231 000101991231 YYMMDD YYMMDD Start month / day for data stored in this record, inclusive End month / day for data stored in this record, inclusive Units MVARh kVARh VAR MVARh kVARh VAR MVARh kVARh VAR Comment Refer to Reading Time-of-use Log Data on page 158
264
Appendix A
Time of Use Records Apparent Energy and Demand Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type F58 53 74 12 Floating point Read only All
User Configurable No
Time of Use Records Apparent Energy and Demand Element No. 0 1 2 3 4 5 6 7 8 9 10 11 Modbus Address 32601-02 32603-04 32605-06 32607-08 32609-10 32611-12 32613-14 32615-16 32617-18 32619-20 32621-22 33623-24 Element Name Off-peak apparent energy Off-peak apparent energy Off-peak demand VA Mid-peak apparent energy Mid-peak apparent energy Mid-peak demand VA Peak apparent energy Peak apparent energy Peak demand VA Record number Start date End date Range -999,999.0 999,999.0 -999.999.999 999.999.999 0.0999.9 x 1021 -999,999.0 999,999.0 -999.999.999 999.999.999 0.0999.9 x 1021 -999,999.0 999,999.0 -999.999.999 999.999.999 0.0999.9 x 1021 012 000101991231 000101991231 YYMMDD YYMMDD Start month / day for data stored in this record, inclusive End month / day for data stored in this record, inclusive Units MVAh kVAh VA MVAh kVAh VA MVAh kVAh VA Comment Refer to Reading Time-of-use Log Data on page 158
265
Appendix A
Single Password Write Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type N60 75, 76 1 Integer Read/Write All except Remote I/O units
User Configurable No
Single Password Write Element No. 0 Modbus Address 42701 Element Name Password Range -19999 Default Value 0 Comment On a write, the correct password is required to change configuration data. On a read, -1 is returned.
266
Appendix A
Single Parameter Read Parameters CSP File No. Remote I/O BT CIP Assy. Inst. No. of Elements Data Type Data Access PM3000 Type 80102 1 each Floating point, little-endian, fixed configuration, or integer (see listing) Read only DeviceNet units only
User Configurable No
Single Parameter Read CIP Assy. Instance 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 Parameter Name Ave L-L Volts L1-L2 Volts L2-L3 Volts L3-L1 Volts L1 Amps L2 Amps L3 Amps L4 Amps Demand Power Demand VARs 3 Ph PF Ave Amps Ave L-N Volts Frequency Total Watts Total VARs Total VA Energy kWh x 1 Energy kWh x 1,000 Energy kWh x 1,000,000 Energy kVARh x 1 Energy kVARh x 1,000 Energy kVARh x 1,000,000 Data Type Float Float Float Float Float Float Float Float Float Float Float Float Float Float Float Float Float Integer Integer Integer Integer Integer Integer Range 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0, 40 75, 999 0.0999.9x1021 0.0999.9x1021 0.0999.9x1021 0999 0999 0999 0999 0999 0999 Comment
267
Appendix A
Parameters for Trend Log and Configurable Table Parameters Applies to Trend Log Configuration/Read-back Record Select Parameters on page 220 Trend Log Results Parameters on page 221 User-configured Table Setup Parameters on page 233 User-configured Table Results Parameters on page 235 Ethernet
PM3000 Type
Parameters for Trend Log and Configurable Table Param No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Parameter Name None Relay output status Solid-state KYZ output status Alarm output word Status inputs state Status input #1 counter Status input #2 counter Voltage Mode (Wiring Configuration) PT Primary PT Secondary I1/I2/I3 CT Primary I1/I2/I3 CT Secondary I4 CT Primary I4 CT Secondary Date: Year Date: Month Date: Day Time: Hour Time: Minute Time: Seconds Time: Hundredths of seconds Date: Month/day Time: Hour/minute Time Second/hsec Refer to Date and Time Parameters (compacted to take less space) Refer to Date and Time Parameters Refer to Basic Device Configuration Parameters Comment No parameter Refer to Discrete Data Parameters
268
Appendix A
Parameters for Trend Log and Configurable Table Param No. 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 Parameter Name Demand Period Length Number of Demand Periods Predicted Demand Type KYZ Pulse Output Parameter KYZ Pulse Output Scale KYZ Pulse Output Width Relay Pulse Output Parameter Relay Pulse Output Scale Relay Pulse Output Width RMS Resolution RMS result averaging Frequency averaging Default relay state in event of communication loss Default KYZ state in event of communication loss DM text scroll rate Protocol Delay Baud rate Device address Data format Refer to Native Communication Configuration Parameters Comment Refer to Advanced Device Configuration Parameters
269
Appendix A
Parameters for Trend Log and Configurable Table Param No. 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 Parameter Name Comm parameter #1 Comm parameter #2 Comm parameter #3 Comm parameter #4 Comm parameter #5 Comm parameter #6 Comm parameter #7 Comm parameter #8 Comm parameter #9 Comm parameter #10 Comm parameter #11 Comm parameter #12 Comm parameter #13 Comm parameter #14 Comm parameter #15 Comm parameter #16 Comm parameter #17 Comm parameter #18 Comm parameter #19 L1 Current L2 Current L3 Current Avg Current L1-N Voltage L2-N Voltage L3-N Voltage Avg L-N Voltage L1-L2 Voltage L2-L3 Voltage L3-L1 Voltage Avg L-L Voltage Frequency, last cycle Metering iteration Refer to Metering Voltage, Current, and Frequency Result Parameters Comment Refer to Optional Communication Configuration Parameters
270
Appendix A
Parameters for Trend Log and Configurable Table Param No. 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 Parameter Name L4 Current Positive Sequence Current Negative Sequence Current % Current unbalance Positive Sequence Voltage Negative Sequence Voltage % Voltage unbalance Phase rotation Average frequency Frequency source L1 Real Power L2 Real Power L3 Real Power Total Real Power L1 Reactive Power L2 Reactive Power L3 Reactive Power Total Reactive Power L1 Apparent Power L2 Apparent Power L3 Apparent Power Total Apparent Power Demand Current Demand Power Demand Reactive Power Demand Apparent Power Projected Demand I Projected Demand W Projected Demand VAR Projected Demand VA Elapsed demand period time Refer to Metering Demand Results Parameters Refer to Metering Power Results Parameters Comment Refer to Metering Sequence Voltage, and Current Results Parameters
271
Appendix A
Parameters for Trend Log and Configurable Table Param No. 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 Parameter Name L1 True Power Factor L2 True Power Factor L3 True Power Factor Three-phase True PF L1 Displacement Power Factor L2 Displacement Power Factor L3 Displacement Power Factor Three-phase Displacement PF L1 Distortion Power Factor L2 Distortion Power Factor L3 Distortion Power Factor Three-phase Distortion PF kWh forward kWh reverse kWh net kVAh kVARh forward kVARh reverse kVARh net kAh Refer to Metering Reactive Energy and Amp-hour Results Parameters Refer to Metering Real and Apparent Energy Results Parameters Comment Refer to Metering Power Factor Results Parameters
272
Appendix A
Parameters for Trend Log and Configurable Table Param No. 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 Parameter Name Bulletin number Series Overall status ASIC status Data FLASH status Real-time clock status RTC NVRAM status Option comm status Display module status Watchdog status VCO lock status Reserved Application FRN Boot code FRN ASIC FRN Option comm FRN Display module FRN Reserved Digital board revision Analog board revision Option comm board revision Reserved MM Device ID MM RAM type Display module type Option comm type Reserved Comment Refer to Selftest/Diagnostic Results Parameters
273
Appendix A
Parameters for Trend Log and Configurable Table Param No. 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 Parameter Name Setpoint #1 type Setpoint #2 type Setpoint #3 type Setpoint #4 type Setpoint #5 type Setpoint #6 type Setpoint #7 type Setpoint #8 type Setpoint #9 type Setpoint #10 type Setpoint #1 evaluation condition Setpoint #2 evaluation condition Setpoint #3 evaluation condition Setpoint #4 evaluation condition Setpoint #5 evaluation condition Setpoint #6 evaluation condition Setpoint #7 evaluation condition Setpoint #8 evaluation condition Setpoint #9 evaluation condition Setpoint #10 evaluation condition Setpoint #1 high limit Setpoint #2 high limit Setpoint #3 high limit Setpoint #4 high limit Setpoint #5 high limit Setpoint #6 high limit Setpoint #7 high limit Setpoint #8 high limit Setpoint #9 high limit Setpoint #10 high limit Setpoint #1 low limit Setpoint #2 low limit Setpoint #3 low limit Setpoint #4 low limit Comment Refer to Setpoint Setup/Read-back Select and Status Parameters
274
Appendix A
Parameters for Trend Log and Configurable Table Param No. 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 Parameter Name Setpoint #5 low limit Setpoint #6 low limit Setpoint #7 low limit Setpoint #8 low limit Setpoint #9 low limit Setpoint #10 low limit Setpoint #1 action delay Setpoint #2 action delay Setpoint #3 action delay Setpoint #4 action delay Setpoint #5 action delay Setpoint #6 action delay Setpoint #7 action delay Setpoint #8 action delay Setpoint #9 action delay Setpoint #10 action delay Setpoint #1 release delay Setpoint #2 release delay Setpoint #3 release delay Setpoint #4 release delay Setpoint #5 release delay Setpoint #6 release delay Setpoint #7 release delay Setpoint #8 release delay Setpoint #9 release delay Setpoint #10 release delay Setpoint #1 action type Setpoint #2 action type Setpoint #3 action type Setpoint #4 action type Setpoint #5 action type Setpoint #6 action type Setpoint #7 action type Comment Refer to Setpoint Setup/Read-back Select and Status Parameters
275
Appendix A
Parameters for Trend Log and Configurable Table Param No. 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 Parameter Name Setpoint #8 action type Setpoint #9 action type Setpoint #10 action type Setpoint #1 status Setpoint #2 status Setpoint #3 status Setpoint #4 status Setpoint #5 status Setpoint #6 status Setpoint #7 status Setpoint #8 status Setpoint #9 status Setpoint #10 status Setpoint #1 accumulated active time Setpoint #2 accumulated active time Setpoint #3 accumulated active time Setpoint #4 accumulated active time Setpoint #5 accumulated active time Setpoint #6 accumulated active time Setpoint #7 accumulated active time Setpoint #8 accumulated active time Setpoint #9 accumulated active time Setpoint #10 accumulated active time Comment Refer to Setpoint Setup/Read-back Select and Status Parameters
276
Appendix A
Parameters for Trend Log and Configurable Table Param No. 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 Parameter Name Logging interval Logging mode Total records logged Trend log param #1 Trend log param #2 Trend log param #3 Trend log param #4 Trend log param #5 Trend log param #6 Trend log param #7 Trend log param #8 Trend log param #9 Trend log param #10 Trend log param #11 Trend log param #12 Trend log param #13 Trend log param #14 Trend log param #15 Trend log param #16 Enable/disable Min/max log Timestamp of last min/max clear; year Timestamp of last min/max clear; Month/day Timestamp of last min/max clear; Hour/min Timestamp of last min/max clear; Second/hsec Enable/disable save status input changes to Event log Number of events in the event log Write error status File/BT/Inst.No. Write error status Parameter number Refer to Write Error Status Parameters Refer to Event Log Configuration/Read-back Record Select Parameters Refer to Min/Max Log Configuration/Read-back Select Parameters Comment Refer to Trend Log Configuration/Read-back Record Select Parameters
277
Appendix A
Parameters for Trend Log and Configurable Table Param No. 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 Parameter Name V1 % IEEE THD I1 % IEEE THD V2 % IEEE THD I2 % IEEE THD V3 % IEEE THD I3 % IEEE THD I4 % IEEE THD V1 % IEC THD (DIN) I1 % IEC THD (DIN) V2 % IEC THD (DIN) I2 % IEC THD (DIN) V3 % IEC THD (DIN) I3 % IEC THD (DIN) I4 % IEC THD (DIN) V1 Crest Factor I1 Crest Factor V2 Crest Factor I2 Crest Factor V3 Crest Factor I3 Crest Factor I4 Crest Factor THD & Crest iteration DeviceNet instance 1 data type Avg IEEE THD V Avg IEEE THD I Avg IEC THD V Avg IEC THD I Avg Crest Factor V Avg Crest Factor I Refer to User-configured Table Setup Parameters Refer to Harmonic Results; THD, Crest Factor, and More Parameters Comment Refer to Harmonic Results; THD, Crest Factor, and More Parameters
278
Appendix
Master Module
1404 - M4
05
A - ENT - 02
Type of Device M4 = Master module with three-phase metering, pulse input conversion, setpoints, I/O, and data logging. M5 = M4 functionality, firmware upgradeable to an M6 or M8 M6 = M4 functionality plus oscillography, sag/swell detection, harmonics 141 measurement, additional setpoints and logging, firmware upgradeable to M8. M8 = M6 functionality plus transient capture and analysis, harmonics measurement up to 63rd, transducer and energy meter modes
Current Inputs 05 = 5 A
Communication Options(1) 000 = None 232 = RS-232 Serial DNT = DeviceNet RIO = Remote I/O
Revenue Accuracy Class none = Class 1 (M4), Class 0.5 (M5, M6, M8) 02 = Class 0.2 (M5, M6, M8)
279
Appendix B
Display Module
1404 - DM
280
Appendix
Sample Applications
Introduction
This appendix contains sample applications including ladder diagrams to help you get started in setting up communication between your application and a power monitor. The application samples depict basic methods for reading and writing data between a power monitor and your programmable controller or other application. Expand on these basic steps to customize your application to meet your business needs. The sample applications include the following: Read and write the power monitor system clock by using a variety of controllers, applications and communication networks. Read multiple power monitor data tables into an SLC 500 controller by using a DeviceNet communication network. Set up the user-configured data table by using a ControlLogix controller and an EtherNet/IP communication network. Read and write power monitor tables by using an SLC 500 controller and a 1747-SCNR ControlNet scanner. Read and write power monitor tables by using a MicroLogix controller over EtherNet/IP and Modbus RTU communication networks. Read and write power monitor tables by using a Component HMI over an EtherNet/IP communication network.
ATTENTION
Proper operation of the application is your responsibility. Rockwell Automation makes no warranty, express or implied, for these sample applications. The sample applications are subject to change at any time without notice.
281
Appendix C
Sample Applications
The power monitor system clock (date and time) is an ideal sample application for these reasons: It is important to set the system clock so that data log records or oscillograms are recorded with accurate time stamps. It is easy to see if your application has successfully written and read the system clock. The methods used for reading and writing the system clock are applicable to reading and writing every other power monitor data table. See Date and Time Parameters on page 195 for details of the Date and Time data table. We will look at four methods of reading and writing the system clock.
282
Sample Applications
Appendix C
Data Tables
In the SLC 500 data tables, table N111 is the destination table for the Read message and N211 is the source for the Write message. Table N211 contains the following values for setting the date and time in a power monitor with a password of 0 to January 1, 2003 at 12:00 midnight.
Table N211
The Read Clock from PM3K and Set Clock from SLC bits are used to initiate the messages, and are reset when the message instruction either completes successfully or an error occurs. In your application code, if the message rungs are controlled programmatically, be sure that only one message is enabled at a time.
283
Appendix C
Sample Applications
Ladder Diagram
284
Sample Applications
Appendix C
285
Appendix C
Sample Applications
The source and destination data tables in the PLC-5 must contain at least as many words as the block transfer length. The Read Clock from PM3K and Set Clock from PLC bits are used to initiate the messages, and are reset when the message instruction either completes successfully or an error occurs. In your application code, if the message rungs are controlled programmatically, ensure that only one message is enabled at a time, and add sufficient time delays between block transfers to avoid overloading the channel.
Ladder Diagram
286
Sample Applications
Appendix C
Tags
The example uses two ControlLogix tags, PM3K_Date_Time and Set_date_time. Both are arrays of 8 INT elements. The program also uses two standard MESSAGE tags, Read_time and Set_time. The following figure shows the Set_date_time to set the power monitor clock to January 1, 2003 at midnight. The tag PM3K_Date_Time shows the results of a read 7.13 seconds after the write.
Set Date Time
287
Appendix C
Sample Applications
Ladder Diagram
Read_clock_from_PM3K 0 MSG Type - PLC5 Typed Read Message Control EN DN ER
Read_Time
...
Read_Time.DN Read_Time.ER
Read_clock_from_PM3K U
Set_time_from_CLX 1
Set_time
...
EN DN ER
Set_time.DN Set_time.ER
Set_time_from_CLX U
(End)
Tags
The example uses two ControlLogix tags as shown below. The tags are INT(8) arrays.
288
Sample Applications
Appendix C
ContrlLogix Tags
Ladder Diagram
Read_clock_from_PM3K 0 Type - CIP Generic Message Control MSG Read_Time ... EN DN ER
Read_Time.DN Read_Time.ER
Read_clock_from_PM3K U
Set_Time.DN Set_Time.ER
Set_clock_from_PM3K U
(End)
289
Appendix C
Sample Applications
The communication tab of the message setup simply shows the module name in the I/O configuration for this example.
Communication Tab
290
Sample Applications
Appendix C
Note that the source length is in Bytes, not elements. Since this message write 8 INT elements, the message length is 16 bytes.
291
Appendix C
Sample Applications
3. Click New and enter a name for the DDE/OPC topic. The example uses DF1_1404_123.
292
Sample Applications
Appendix C
4. Browse through the tree in the Data Source dialog to locate your power monitor and click its icon to select it.
5. Click the Data Collection tab, select SLC 5/03+ as the Processor Type, leaving the rest of the settings as default.
293
Appendix C
Sample Applications
6. Click Apply and confirm when prompted. 7. Click the Advanced Communication tab to verify the driver and path settings in the topic and click Done.
294
Sample Applications
Appendix C
The range Sheet1!D7:D14 is the write source range and the read target range. The Read graphic element is associated with the following VBA script or macro. Sub ReadDateAndTime()
'Open DDE link; the first argument is the application we 'want to DDE with. Second argument is the DDE topic name 'configured in RSLinx RSIchan = DDEInitiate(RSLINX, DF1_1404_123) 'Read the date/time table from the PM3000 and put it in 'the excel sheet Range(Sheet1!D7:D14) = DDERequest(RSIchan, N11:0,L8) 'Close DDE link DDETerminate (RSIchan)
End Sub The Write graphic element is associated with the following VBA script. Sub WriteDateAndTime()
'Open DDE link RSIchan = DDEInitiate(RSLINX, DF1_1404_123) 'Write data from the excel sheet into the PM3000 DDEPoke RSIchan, N11:0,L8, Range(Sheet1!D7:D14) 'Close DDE link DDETerminate (RSIchan)
End Sub To read the date and time from the power monitor, click the Read graphic element. To write the data and time to the power monitor, enter the desired data and time into the worksheet along with the power monitor password (default = 0) and click the Write graphic element.
295
Appendix C
Sample Applications
IMPORTANT
If you are using RSLinx Classic software as your OPC software, a licensed RSLinx OEM or higher version is required.
IMPORTANT
The power monitor master module firmware must be 4.x or later and the Ethernet protocol must be set to CIP or CSP/CIP to support communication with a MicroLogix controller.
296
Sample Applications
Appendix C
Data Tables
The MicroLogix 1400 data table N111 is the destination table for the Read message and N211 is the source for the Write message. Table N211 contains the following values for setting the date and time in a power monitor with a password of 0 to January 1, 2003 at 12:00 midnight.
297
Appendix C
Sample Applications
The Read Clock from the Powermonitor 3000 unit and Set Clock from the MicroLogix 1400 controller bits are used to initiate the messages, and are reset when the message instruction either completes successfully or an error occurs. In your application code, if the message rungs are controlled programmatically, be sure that only one message is enabled at a time.
Ladder Program
298
Sample Applications
Appendix C
299
Appendix C
Sample Applications
300
Sample Applications
Appendix C
301
Appendix C
Sample Applications
Data Tables
ML1400 data table N111 is the destination table for the Read message and N211 is the source for the Write message. Table N211 contains the following values for setting the date and time in a power monitor with a password of 0 to January 1, 2003 at 12:00 midnight.
The Read Clock from PM3K and Set Clock from ML1400 bits are used to initiate the messages, and are reset when the message instruction either completes successfully or an error occurs. In your application code, if the message rungs are controlled programmatically, be sure that only one message is enabled at a time.
Ladder Program
302
Sample Applications
Appendix C
303
Appendix C
Sample Applications
304
Sample Applications
Appendix C
The following is a ladder program designed to return a number of real-time data tables from a power monitor to an SLC 500 processor via DeviceNet by using a DeviceNet scanner module. The following example and ladder diagram uses these settings: Node (MAC ID) = 5 Port = 0 Class = 4 Instance = 14, 16, 18, 20, 22, 17, 25 Attribute = 3 Command = 1, 4 Size 3 Size = 3 Service = 14
Word M0:1.224
A unique TXID (Transmit Identifier) and Command byte is needed for this word. These are the valid command codes. 1 = Execute transaction block 4 = Delete transaction from response queue
305
Appendix C
Sample Applications
A command byte of 1 is used first to start the explicit message. After a response has been received from the scanner, a command byte of 4 is used to remove this transaction from the scanner. If the command byte of 4 is not written to the SLC 500 DeviceNet Scanner, then it does not process further transactions.
Word M0:1.225
A port number and transaction body size is needed for this word. The port number is the DeviceNet scanner port that handles this transaction; an SLC 500 controller uses port 0 and the PLC-5 controller uses port 0 or 1. The size is the number of bytes (2 bytes = 1 word) in the transaction body which is 6 (6 bytes = 3 words).
Word M0:1.225 Port Port x 256 0 x 256 + + 6 Size Size 6
Word M0:1.226
A service code and MAC ID is needed for this word. The service code is the DeviceNet network service that can be used on the Class 4 assembly instances; these are the valid service codes. 14 = Get_Attributes_Single 16 = Set_Attributes_Single
306
Sample Applications
Appendix C
The MAC ID is the node number of the device that the DeviceNet scanner is communicating to; this example uses node 5.
Word M0:1.226 Service Service x 256 14 x 256 MAC ID + + 3589 MAC ID 5
Word M0:1.227
The class number is the first word of the transaction body; class 4 is used to retrieve the real-time data assemblies.
Word M0:1.2278
The instance number is the second word of the transaction body; instance 14 is used to retrieve the real-time voltage, current, and frequency metering information.
Word M0:1.229
The attribute number is the third word of the transaction body; attribute 3 is used to get the metering information.
307
Appendix C
Sample Applications
TIP
The speed at which the processor performs the messages may be altered by resetting the On-Delay timer that is located within the sequencer output rung. However, the availability of new data values is controlled by the power monitor table update rate.
Data Files Data File Address N9 N10 R6:0 (Control/Data) N20 / F30 N21 / F31 N22 / F32 N23 / N33 N24 / N34 N25 / F35 N26 / N36 14 13 13 23 23 10 27 Voltage/Current Data Real-Time Power Power Factor kWh and kVAh kVarh Demand Diagnostic Number of Elements 1 Variable Description N9:0 Sequencer Output N10:0 Sequencer Input Sequencer Control
308
Sample Applications
Appendix C
The reset word for the sequencer is N10:0. The first word in the rotation of the sequencer is N10:1. The value in N10:0 must be the same as that in N10:1. The size of file N10 is equal to the size of the largest sequencer input file. This size depends on the number of explicit message transfers to be performed. The sequencer length may be expanded or reduced for Run mode. It is imperative that the corresponding file that serves as the source of the sequencers input file, N10, must be modified accordingly.
IMPORTANT
Failure to modify the length of file N10 for a modification of either the Configuration or Run sequence results in improper operation of the ladder program, and possible fault of the processor due to invalid indirect offsets.
N20:0
Required numbers are 5121, 6, 3589, 4, 14, 3
N21:0
Required numbers are 5377, 6, 3589, 4, 16, 3
N22:0
Required numbers are 5633, 6, 3589, 4, 18, 3
N23:0
Required numbers are 5889, 6, 3589, 4, 20, 3
N24:0
Required numbers are 6145, 6, 3589, 4, 22, 3
N25:0
Required numbers are 6401, 6, 3589, 4, 17, 3
N26:0
Required numbers are 6657, 6, 3589, 4, 23, 3
309
Appendix C
Sample Applications
Ladder Diagram
310
Sample Applications
Appendix C
311
Appendix C
Sample Applications
312
Sample Applications
Appendix C
313
Appendix C
Sample Applications
This example shows a ladder program designed to customize the User-configured Data Table in a power monitor by using a ControlLogix controller via its EtherNet/IP Bridge (1756-ENET/B). Use of the user-configured data table to consolidate parameters from different power monitor data tables can increase the efficiency of communication. The following example and ladder listing use these settings: IP Address: 130.151.70.173 Subnet mask: 255.255.0.0 Message type: PLC-5 Typed Read
314
Sample Applications
Appendix C
ControlLogix Tags Used Tag Name msgReadOld msgWriteNew msgGetStatus Start Failed Success Oneshot_1 Oneshot_2 Timer1 Timer2 Counter1 Default Custom Old Download Pwd Status Select Type MESSAGE MESSAGE MESSAGE BOOL BOOL BOOL BOOL BOOL TIMER TIMER COUNTER INT INT INT INT INT INT INT # of Elems N/A N/A N/A 1 1 1 1 1 1 1 1 26 26 26 26 1 2 1 Description Read Existing Config Write New Config. Write Status Start Operation Failure Flag Success Flag One shot One shot Inter-message Delay PM3000 Reset Time Message Retry Default Configuration Custom Configuration Previous Config New Config to Write PM3000 Password Write Status User Selection Table # N30 N30 N32
You must enter data into the Default and Custom tags. Refer to User-configured Data Table on page 121 for the structure and rules for the User-configured Table Setup data table and its default settings. See Parameters for Trend Log and Configurable Table Parameters on page 268 for parameters that may be included in the User Configured Table Setup.
IMPORTANT
Words 03 of the User Configurable Table Setup array must have specific values. Word 0: power monitor password (default = 0) Word 1 must be one of the following decimal values: 31, for CSP/PCCC 1 or 37 for CIP Word 2: zero (0) for writes to table 31. For configuring instance 1: 0 = all integer or data type, 1 = float data type. Word 3: between 1 and 295 incl.
315
Appendix C
Sample Applications
Ladder Diagram
Sample logic program that shows a way to configure a Powermonitor 3000 User Configurable Data Table from a ControlLogix controller via the 1404-NENET communications option card using EtherNet/IP. See the accompanying text for a list of tags to be created in the ControlLogix controller. The first rung allows a selection of tables to write to the PM3000. Enter a 0, 1, or 2 into the tag "Select" to select between the default table, a custom table, or an "Undo" of the last write. The selected table is copied into the "Download" table. The rung logic also copies the PM3000 password into the "Download" table . If the password is changed from the default (0), the new password must be entered into the tag "pwd." Toggle the "Start" tag to begin.
Start 0
Oneshot_1 ONS EQU Equal Source A Source B Select 2 0 COP Copy File Source Default[0] Dest Download[0] Length 26
msgReadOld
...
EN DN ER
316
Sample Applications
Appendix C
This rung inserts a brief time delay before enabling the WriteNew message instruction.
Start 1
msgReadOld.DN
After clearing the flags from the previous write, this rung performs a data table write to transfer the selected user configured data table setup to the Powermonitor 3000 unit. If the number of paramaters in the User Configurable Data Table is changed, the Powermonitor 3000 unit resets.
Timer1.DN 2
Success U
Failed U EN DN ER
msgWriteNew
msgWriteNew.DN
Counter1.CU
317
Appendix C
Sample Applications
The message configuration for writing the new configuration table to the power monitor is shown below.
318
Sample Applications
Appendix C
Timer2 delays evaluating the write status until the Powermonitor 3000 unit has reset. This rung evaluates the results of writing the new configuration. The "Failed" flag asserts if the WriteNew message instruction errors-out, or if the GetStatus instruction errors out twice, or if the write status indicates bad data in the download table. If there is a bad data indication, verify that word 0 of the download table is the correct Powermonitor 3000 password, that word 1 is a value of 31 (decimal) and that at least one or more words beginning with word 3 are non-zero. Then try toggling "start" again. Counter1 increments if the GetStatus message errors out. The logic will wait until Timer2 times out and then retry the GetStatus message. When the operation is complete with no errors, the "Success" flag asserts and the "Start" flag is cleared. Timer2.DN 3
msgGetStatus
...
EN DN ER
CTU Counter1 2 0 CU DN
EQU Status[0] 30 30
Counter1.DN msgWriteNew.ER
End
319
Appendix C
Sample Applications
Communicating with a SLC 5/05 (1747-L552) Controller and ControlNet Scanner (1747-SCNR), Unscheduled Messaging
The Power Energy and Management Systems development team tested the following example ladder. The scan times for execution of the ladder are as follows.
Operation Table reads for Integer and float files Table writes of Integer and float files
Scan Time 20 ms 30 ms
All the communication operations of the ladder are locked out until the read or write bits are set. This was done so that other operations performed by the ladder will have minimum overhead from communication. The following files are of importance when using the ladder example.
320
Sample Applications
Appendix C
N7 SCNR_FILE
The following items are of importance in file N7:0.
File N7:0 Bit # N7:0/15 N7:0/14 N7:0/13 N7:0/12 N7:0/11 N7:0/10 N7:0/9 N7:0/8 Importance N7:0 EN - Written to by the ladder to enable communication transaction. Unused DN bit - Response received ER bit - Error bit returned form SCNR scanner CO - Continuous mode Not used EW - Message taken into account by 1747 - SCNR scanner Read/Write R/W N/A R R N/A R
SUCCESS - Used by ladder for notification R of successful communication transfer. TO - The message transaction has timed out. R
While other words in the N7 SCNR_FILE are important to communication these values are copied from file N9 CIP_SETUP to file N7.
N9 CIP_SETUP
This file is the CIP message setup file. The importance of the following words should be noted.
N9 CIP Word # N9:0 N9:1 N9:2 N9:3 N9:4 N9:5 Description of Function Not used by CIP_SETUP. Target MAC ID (Power monitor MAC ID) Communication transaction timeout setting in ms. (2048 recommended) Complex IOI size. Not used and set to 0. Service code. 0xE for Get Attribute Single or 0x10 Set Attribute single. Class code of Instance Object. Power monitor class 4 assembly instance.(4)
321
Appendix C
Sample Applications
N9 CIP Word # N9:6 N9:7 N9:8 N9:9 Description of Function Targets Instance number to read or write. Target Attribute. Power monitor Attribute of assembly instance is 3. (3) Target member number. (Not used) Size of the data in words. Used for writes only. When performing a read operation this parameter is forced to 0. Size of Power monitor tables is type N = elements x 1, type F = elements x 2. Not used by CIP_SETUP. Enables a read/write operation. Writing a 1 starts the process for writing an assembly instance of the power monitor. Writing a 2 starts the read process of assembly instance from the power monitor.
N9:10 N9:11
After setting up the communication parameters a 2 is written to location of N9:11. The transaction is complete when bit N7:0/9 becomes true. The information will be located in file F8, FLT_DATA starting at location 0. The length of usable information is the length of elements in table instance 14 VIF table of the power monitor.
TIP
When receiving integer information from the power monitor the data will be readable from file number N10 INT_DATA. The length is the number of elements in the assembly instance being read.
322
Sample Applications
Appendix C
TIP
The write procedure differs slightly from the read process. N9:4 service has been changed to 0x10 or 16 decimal (Set Single Attribute). N9:6 is the write instance assembly number of the power monitor basic configuration table. N9:9 is the size of the table in words for a 1404-M805A-CNT A. The size for float tables is two times the number of elements. Integer tables are one times the size of the table elements.
When a 1 is written to location N9:11 the contents of file F13 WR_TRANSFR are sent to the power monitor. In this case starting with float F13:0 through F13:8. The writing of an integer file sends the contents of N14 WR_TRANSFR. For further reading on the functionality of the 1747-SCNR scanner refer to the user manual, publication 1747-RM623.
323
Appendix C
Sample Applications
Power Monitor Ladder Example for SLC Scanner Module through SCNR
Power Monitor with SLC Scanner Module
While message is pending bring back the CIP message control status. Message Pending B3:0 0000 0 COP Copy File Source #M0:3.1000 Dest #N7:0 Length 10
After setting up N9 CIP_SETUP file, turn on bit N9:11/1 to start the read transfer from the power monitor. This process clears out the first 9 words of N7:0 CIP message file. Copies the request from the CIP_SETUP file to N7 first 9 words. Moves a 0 to M0 scanner location M0:3.1009 (This loacation needs to be set to 0 when requesting information.) Enable the transfer by turning bit N7:0/15 EN to 1. Copy the request information into the request area of the M0 file offset 1000 + 9. Set the bit for Message Pending. Perform Read N9:11 0001 1 0 Message Pending B3:0 FLL Fill File Source Dest Length COP Copy File Source Dest Length MOV Move Source Dest
0 #N7:0 9
#N9:0 #N7:0 9
Enable Transfer Bit N7:0 L 15 COP Copy File Source #N7:0 Dest #M0:3.1000 Length 9 Message Pending B3:0 L 0
324
Sample Applications
Appendix C
When a write of a float file is being performed it is necessary to swap the words in teh float file before sending the write request. This is only necessary for Instance 4 or Instance 52.
Allow Write N9:11 0002 0 EQU Equal Source A Source B JSR Jump To Subroutine SBR File Number
U:4
Allow the scanner to write to the power monitor. Put the new integer configuration data in N14 starting at location 0. Put the configuration if it is of float type in file F13 starting with word 0. Enter the rest of the CIP message information needed for transfer in N9 starting with word 0. The process is similar to the request of information except that the size in words of the data to write is to appear in N7:9 and the service to be performed is changed.
Allow Write N9:11 0003 0 0 Message Pending B3:0
FLL Fill File Source Dest Length COP Copy File Source Dest Length COP Copy File Source Dest Length
0 #N7:0 65
#N9:0 #N7:0 10
#N14:0 #N7:10 64
COP Copy File Source #N7:10 Dest #M0:3.1100 Length 65 Enable Transfer Bit N7:0 L 15 COP Copy File Source #N7:0 Dest #M0:3.1000 Length 10 Message Pending B3:0 L 0
325
Appendix C
Sample Applications
This rung looks for the done bit with no errors. When the done bit is received the return information is tranfered and mainten ance is performed. Integer information can be read from file N10:0. Float information can be read from F8:0. The enable and done bit s are turned off and the bit N7:9 is latched to notify the user that the transfer was successful. Bit B3:0/1 is set to transfer any floats to the F8:0 file after swapping words from the incomming message. Done Bit N7:0 0004 13 0 8 12 Message Pending B3:0 Time Out Bit N7:0 Error bit N7:0 COP Copy File Source #M0:3.1350 Dest #N10:0 Length 64 Message Pending B3:0 U 0 Perform Read N9:11 U 1 Allow Write N9:11 U 0 Enable Transfer Bit N7:0 U 15 Done Bit N7:0 U 13 Transfer Successful N7:0 L 9 Swap Words B3:0 L 1
326
Sample Applications
Appendix C
When an error or timeout occurs bit maintenance is performed to ready the ladder for the next message leaving the timeout or error bit set. Time Out Bit N7:0 0005 8 Error bit N7:0 12 Message Pending B3:0 U 0 Perform Read N9:11 U 1 Allow Write N9:11 U 0 Enable Transfer Bit N7:0 U 15 This calls the word swap routine and returns after the swapping has been completed. Swap Words B3:0 0006 1 JSR Jump To Subroutine SBR File Number Swap Words B3:0 U 1
U:3
0007
END
327
Appendix C
Sample Applications
Perpare to swap words by copying source to N11 temp file. Initialize the word counter N12:0. 0000 SBR Subroutine COP Copy File Source Dest Length MOV Move Source Dest
#N10:0 #N11:0 64
Perform this task until all the words have been swapped. A size of 32 was selected to handle all power monitor files. 0001 Q3:1 LBL LES Less Than (A<B) Source A N12:0 30< Source B 30 30< ADD Add Source A Source B Dest
MOV Move Source N11:[N12:0] 0< Dest N11:[N12:1] 0< MOV Move Source Dest
328
Sample Applications
Appendix C
When the word swapping is complete transfer the results into F8 FLT_DATA file. 0002 EQU Equal Source A Source B COP Copy File Source Dest Length
#N11:0 #F8:0 32
0003
RET Return
0004
END
329
Appendix C
Sample Applications
Initialize N12:0 word counter. Copy F13 configuration float data to N11 temporary file. 0000 SBR Subroutine MOV Move Source Dest
COP Copy File Source Dest Length Continue to swap words until 32 floats have been converted. This is enough to handle all power monitor files. 0001 Q4:1 LBL LES Less Than (A<B) Source A N12:0 30< Source B 62 62< ADD Add Source A Source B Dest
#F13:0 #N11:0 32
MOV Move Source N11:[N12:1] 0< Dest N12:2 0< MOV Move Source N11:[N12:0] 0< Dest N11:[N12:1] 0< MOV Move Source Dest
330
Sample Applications
Appendix C
When the swap operation is complete copy the temp file to the designated WR_TRANSFR file. 0002 EQU Equal Source A Source B COP Copy File Source Dest Length
#N11:0 #N14:0 64
0003
RET Return
0004
END
This example demonstrates reading and writing power monitor date, time, and other configuration parameters by using a PanelView Component HMI terminal, the single element password write, and the EtherNet/IP communication network. Please refer to applicable product literature for information on configuration and use of the PanelView Component HMI terminal. Illustrations in this example were made using a Firefox 2.x browser. The power monitor master module firmware must be version 4.x or later and PanelView Component HMI firmware must be version 1.11 or later. Power monitor Ethernet protocol selection may be either CIP or CIP/CSP.
331
Appendix C
Sample Applications
Tag Configuration
This example includes the following tags.
Name Year Month Day Hour Minutes Seconds Voltage Mode Voltage Primary User Config Table Parm 1 Setup Native Comms Protocol Native Comms Baud Rate Single Element Password
Address N11:1 N11:2 N11:3 N11:4 N11:5 N11:6 F10:1 F10:2 N30:3 N13:1 N13:3 N60:0
Data type 16 bit Integer 16 bit Integer 16 bit Integer 16 bit Integer 16 bit Integer 16 bit Integer Real Real 16 bit Integer 16 bit Integer 16 bit Integer 16 bit Integer
332
Sample Applications
Appendix C
Example Screens
The first example screen lets you read and write date and time to and from the power monitor. Entering the correct password (default = 0) permits single element writes until 30 minutes of inactivity has elapsed.
The second example is a screen that may be used to view and set selected configuration parameters in the power monitor.
333
Appendix C
Sample Applications
334
Appendix
Technical Specifications
Product Approvals
335
Appendix D
Technical Specifications
UL/CUL
UL 508 listed, File E96956, for Industrial Control Equipment and CUL Certified.
CE Certification
If this product bears the CE marking, it is approved for installation within the European Union and EEA regions. It has been designed to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole, documented in a technical construction file: EN 50081-2 - Generic Emission Standard, Part 2 - Industrial Environment EN 50082-2 - Generic Immunity Standard, Part 2 - Industrial Environment This product is intended for use in an industrial environment.
336
Technical Specifications
Appendix D
The Bulletin 1404 display module is rated as IP65 degree of protection per International Standard IEC 529. It is rated as Type 4 (Indoor) per NEMA and UL 508. Follow the recommended installation guidelines to maintain these ratings.
ANSI/IEEE Tested
Meets or exceeds the Surge Withstand Capability (SWC) C37.90.1 1989 for protective relays and relay systems on all power connection circuit terminations.
Technical Specifications
Current Sense Input: I1, I2, I3, I4 Frequency Power Functions: kW, kVA, kVAR Demand Functions: kW, kVA Energy Functions: kWH, kVAH Metering Update Rates
0.05% 0.05 Hz ANSI C12.20 and EN 60687 Class 0.5 Accuracy (Class 0.2 is also available) 4570 ms
0.05% 0.05 Hz ANSI C12.20 and EN 60687 Class 0.5 Accuracy (Class 0.2 is also available) 4575 ms
0.05% 0.05 Hz ANSI C12.20 and EN 60687 Class 0.5 Accuracy (Class 0.2 is also available) 4090 ms
5580 ms
337
Appendix D
Technical Specifications
1404-xxxxB-xxx Voltage Sense Inputs: V1, V2, V3 Current Sense Inputs: I1, I2, I3, I4
Input Impedance: 1 Mohm min, 399V ac max; V1, V2 and V3 to N. Overload Withstand: 15 A Continuous, 200 A for 1 s Burden: 0.05V A Impedance: 0.002 ohms Maximum Crest Factor at 5 A is 3 Starting Current: 5 mA Contact Closure (Internal 24V dc) (1) ANSI C37.90-1989 trip duty (1) Solid State KYZ - 80 mA at 240300V dc
Control Relay(1) Rating 50/60 Hz ac rms DC 10A at 30V and 0.25A at 250V 10 mA at 24V Q300 0.55 A at 125V 0.27 A at 250V (69V A) 0.55A at 125V 0.27 A at 250V (69V A)
Max Resistive Load Switching 10 A at 250V (2500V A) Min Load Switching UL 508, CSA 22.2, IEC Rating Class Max Make Values (Inductive Load) Max Break Values (Inductive Load) Max Motor Load Switching
(1)
10 mA at 24V B300 30 A at 120V 15 A at 240V (3600V A) 3 A at 120V 1.5 A at 240V (360V A) 1/3 HP at 125V 1/2 HP at 250V
338
Technical Specifications
Appendix D
General Specifications Dielectric Withstand Control Power Voltage Inputs Current Inputs Status Inputs Control Relays Terminal Blocks Power Supply and Voltage input Terminals Relay, KYZ outputs, Current input terminals(1) Status inputs, RS485 RIO, DNT (When present) Temperature, Operating Temperature, Storage Humidity Vibration Shock
(1)
2000V 2000V 2000V 500V 1600V 4 mm2 (12 AWG) max, 1.02 Nm (9 lb-in) Torque., 75 C (167 F) or Higher Copper Wire only 2.5 mm2 (14 AWG) max, 1.18 Nm (10.4 lb-in) Torque 75 C (167 F) or Higher Copper Wire only 2.5 mm2 (14 AWG) max 0.56 Nm (5 lb-in) Torque 2.5 mm2 (14 AWG) max 0.56 Nm (5 lb-in) Torque
-2060 C (-40140 F) Cat. No. 1404-DM, 1404-Mxxxx-000, 1404-Mxxxx-DNT 055 C (32131 F) 1404-Mxxxx-232, -RIO, -ENT, -CNT -4085 C (-40185 F) 595%, Noncondensing 10500 Hz: 2 g Operational (0.012 in.) 1/2 Sine Pulse, 11 ms duration: 30 g Operational and 30 g Nonoperational
339
Appendix D
Technical Specifications
340
Appendix
341
Appendix E
Q. Can I change communication networks? A. Unlike the other Allen-Bradley power monitors, the Powermonitor 3000 unit ships with a non-interchangeable communication network card.
342
Glossary
ampere A unit of electrical current or rate of flow of electrons. One volt across one ohm of resistance causes a current flow of one ampere. A flow of one coulomb per second equals one amp. apparent power The product of voltage magnitude and current magnitude in a circuit. Units are VA or some multiple thereof. balanced load An alternating, current power system consisting of more than two current carrying conductors in which these current carrying conductors all carry the same current. billing demand The demand level that a utility uses to calculate the demand charges on the current months bill. Various methods may be used to determine the value, such as minimum demand, peak demand or a ratchet clause. It can be based on Watt Demand, VA Demand, VAR Demand or some combination of these. A rate at which a transmission occurs, where one baud equals one bit per second. broadcast Broadcast address is a value used for performing commands on all Modbus slaves that are connected on the network. Slave address 0 is reserved for this value. burden The electrical load placed on source of VA or the load an instrument or meter places on a current or potential transformer. All current and potential transformers have a rated burden which should not be exceeded or else transformer transformation accuracy deteriorates. capacitor A device consisting essentially of two conducting surfaces separated by an insulating material or dielectric. A capacitor stores electrical energy, blocks the flow of direct current, and permits the flow of alternating current to a degree dependent upon the capacitance and frequency. They may also be used to adjust the power factor in a system.
343
Glossary
coil This is a Modbus mapped location used for reading and writing bit length data. These bits typically reflect the value of the discrete outputs. Powermonitor 3000 units do not support this data type. connected load The total load which a customer can impose on the electrical system if everything was connected at one time. Connected loads can be measured in horsepower, watts or volt-amperes. Some rate schedules establish a minimum demand charge by imposing a fee per unit of connected load. current transformer (CT) A transformer, intended for measuring or control purposes, designed to have its primary winding connected in series with a conductor carrying the current to be measured or controlled. CTs step down high currents to lower values which can be used by measuring instruments. current transformer ratio The ratio of primary amperes divided by secondary amperes. data table Power monitor data is organized in data tables similar to those found in an SLC 5/03 Programmable Controller. The detailed data table definitions are covered in Appendix A of the Bulletin 1404 Powermonitor 3000 User Manual. demand hours The equivalent number of hours in a month during which the peak demand is fully utilized. In other words, if energy consumption for the current month is X kwhr and the peak demand is Y kW, then the demand hours is equal to X/Y hours. The higher the number of demand hours, the better the demand leveling situation, and the more effectively demand is being used. demand interval Demand charges are based on peak demand over a utility specified time interval, not on the instantaneous demand (or connected load) at any given moment. Typical demand intervals are 15, 20, and 30 minutes.
344
Glossary
discrete input This is a Modbus mapped location used for reading bit length data. These bits typically reflect the value of the discrete inputs. Powermonitor 3000 units do not support this data type. exception reply This is the Reply Packet for a Modbus Command that was unsuccessful in operation. frequency The number of recurrences of a periodic phenomenon in a unit of time. In electrical terms, frequency is specified as so many Hertz (Hz) where one Hz equals one cycle per second. function code Function byte: second byte of any Modbus Command packet. holding register This is a Modbus mapped location used for reading the writing word length data. For a power monitor slave device, the locations are defined by the Modbus Memory Map. horsepower (hp) A unit of power, or the capacity of a mechanism to do work. It is equivalent to raising 33,000 pounds one foot in one minute. One horsepower equals 746 watts. impedance The total opposition (that is, resistance and reactance) a circuit offers to the flow of alternating current at a given frequency. It is measured in ohms. induction motor An alternating current motor in which the primary winding (usually the stator) is connected to the power source and induces a current into a secondary (usually the rotor). inductor A device consisting of one or more windings with or without a magnetic core. Motors are largely inductive.
345
Glossary
initiator pulses Electrical impulses generated by pulse-initiator mechanisms installed in utility revenue meters. Each pulse indicates the consumption of a specific number of watts. These pulses can be used to measure energy consumption and demand. input register This is a Modbus mapped location used for reading word length data. For a power monitor slave device, the locations are defined by the Modbus Memory Map. lagging current The current flowing in an ac circuit which is mostly inductive. If a circuit contains only inductance the current lags the applied voltage by 90. Lagging current means lagging power. leading current The current flowing in a circuit which is mostly capacitive. If a circuit contains only capacitance the current leads the applied voltage by 90. Leading current means leading power factor. load Any device or circuit consuming power in an electrical system. load shedding The removal of load from the line to limit load and control demand level. load restoring The energizing of loads that were previously removed from the line to limit load and control demand level. Modbus Industrial communication network protocol created by the Modicon Corporation. neutral The conductor chosen as the return path for the current from the load to the source. It is also a voltage reference point in a power system.
346
Glossary
ohm The unit of electrical resistance. One ohm is the value of resistance through which a potential difference of one volt will maintain a current flow of one ampere. peak demand The highest average load over a utility specified time interval during a billing period. If there is no ratchet clause in the rate schedule, then the peak demand is also the billing demand. polyphase Having or utilizing several phases. A polyphase power circuit has several (typically three) phases of alternating current with a fixed phase angle between phases. potential transformer (PT) An transformer with the primary winding connected in parallel with the circuit whose voltage is to be measured or controlled. PTs are normally used to step down high-voltage potentials to lower levels acceptable to measuring instruments. Also known as voltage transformer (VT). potential transformer ratio The ratio of primary voltage divided by secondary voltage. power factor The ratio of real power in watts of an alternating current circuit to the apparent power in volt-amperes. Also expressed as the cosine of the phase angle between the fundamental voltage applied to a load and the current passing through it. power factor correction Steps taken to raise the power factor by closely aligning the current to be in phase with the applied voltage. Most frequently this consists of added capacitance to increase the lagging power factor of inductive circuits. power factor penalty The charge utilities impose for operating at power factor below some rate schedule-specified level. This level ranges from a lagging power factor of 0.80 to unity. There are innumerable ways by which utilities calculate power factor penalties.
Publication 1404-UM001F-EN-P - November 2009 347
Glossary
ratchet clause A rate schedule clause which states that billing demand may be based on current month peak demand or on historical peak demand, depending on relative magnitude. Usually the historical period is the past eleven months, although it can be for the life of the contract. Billing demand is either the current month peak demand or some percentage (75% is typical) of the highest historical peak demand, depending on which is largest. It is designed to compensate the electric utility for maintaining equipment not fully utilized. reactance The opposition to the flow of alternating current. Capacitive reactance is the opposition offered by capacitors and inductive reactance is the opposition offered by an inductive load. Both reactances are measured in ohms. real power The component of apparent power that represents real work in an alternating current circuit. It is expressed in watts and is equal to the apparent power times the power factor. resistance The property of a substance which impedes current flow and results in the dissipation of power in the form of heat. The unit of resistance is the ohm. One ohm is the resistance through which a difference of potential of one volt will produce a current of one ampere. revenue meter A meter used by a utility to generate billing information. Many types of meters fall in this category depending on the rate structure. root mean square (RMS) The effective value of alternating current or voltage. The RMS values of voltage and current can be used for the accurate computation of power in watts. The RMS value is the same value as if continuous direct current were applied to a pure resistance. RTU Remote Terminal Unit, one of two possible transmission formats supported by Modbus. Powermonitor 3000 units only supports RTU slave function.
348
Glossary
slave address This is the numerical label for slave devices. Valid slave device addresses are in the range of 0247 decimal. The individual slave devices are assigned addresses in the range of 1247. The value of 0 is reserved for broadcast. sliding demand interval A method of calculating average demand by averaging the average demand over several successive short time intervals, advancing one short time interval each time. Updating average demand at short time intervals gives the utility a much better measure of true demand and makes it difficult for the customer to obscure high short-term loads. sub function code Sub function word: third and forth bytes of any Modbus Command packet. unbalanced load A situation existing in a three-phase alternating current system using more than two current carrying conductors where the current is not due to uneven loading of the phases. volt-ampere (VA) The unit of apparent power. It equals volts times amperes regardless of power factor. volt-ampere demand Where peak average demand is measured in volt-amperes rather than watts. The average VA during a predefined interval. The highest average, for example, Peak VA demand, is sometimes used for billing. voltage (V) The force which causes current to flow through a conductor. One volt equals the force required to produce a current flow of one ampere through a resistance of one ohm. watt (W) A measure of real power. The unit of electrical power required to do work at the rate of one joule per second. It is the power expended when one ampere of direct current flows through a resistance of one ohm. Equal to apparent power VA times the power factor.
349
Glossary
watt demand Power during a predetermined interval. The highest average, for example, Peak demand is commonly used for billing. watt hour (Whr) The number of watts used in one hour. Since the power usage varies, it is necessary to integrate this parameter over time. Power flow can be either forward or reverse. wattmeter An instrument for measuring the real power in an electric circuit. Its scale is usually graduated in watts, kilowatts, or megawatts. volt ampere reactive hours (VARH) The number of VARs used in one hour. Since the value of this parameter varies, it is necessary to integrate it over time. VARs can be either forward or reverse.
350
Index
A
advanced device configuration 50 date and time 55 daylight saving time 58 demand setup 52 display scroll speed 55 energy counter rollover 54 metering options 54 network demand and time configuration 55 relay and KYZ pulse 53 watchdog timeout 55 advanced features 159 auto sense protocol 95 DeviceNet 71 DF1 full duplex 67 Ethernet 78 Modbus 64 Remote I/O 70 RS-232 65 RS-485 64 configuring harmonic analysis 171 configuring setpoints 128 examples of setpoint operation 131 reading setpoint status using communication 135 using display module 133 viewing using display module 134 writing configuration using communication 134 configuring time of use log 157 ControlNet 112 communicating from a PLC5 117 communicating from SLC through 1747-KFC15 115 performance features 20 status indicators 25 ControlNet communication 79 counters 141 crest factor 167
B
basic device configuration 48 nominal system voltage 49 PT and CT ratios 49 wiring mode 48
C
clear command 185 clear or preset energy counters 120 communicating from a PLC5 117 communicating via 1747-KFC15 ControlNet 115 communication 14, 63 communication loss behavior 140 communication option DeviceNet 19 communication options 17 ControlNet 20 Ethernet 19 Modbus 17 Remote I/O 18 RS-232 18 RS-485 native communication 17 configurable trend log 148 calculating depth 149 modes of operation 148 reading data 152 set up 151 configuration 14 advanced device configuration 50 basic device configuration 48 configuration using the dispaly module 47 configuring communication 63 ControlNet 79
D
data logging 143 data messaging data table attributes 81 expressing data in data tables 82 I/O type communication 90 indexed reads of large data structures 88 simple reads of data tables 87 writing data to data tables 83 data messaging application considerations 90 ControlNet 112 DeviceNet 96 Ethernet 103 serial communication 91 user-configured data tables 121 data messaging overview 80 data table attributes 81 data tables 187 daylight saving time 58 dst enable 58 dst end month 58 dst start day 58 dst start day instance 58 dst start hour 58
351
Index
dst start month 58 demand calculation 35 demand period synch 141 DeviceNet 71, 96 class services 102 explicit messaging 98 I/O messaging 96 indexed data table reads 102 message types 101 object classes 102 performance features 19 status indicators 24 unique write identifier 103 using RSNetworx 73 DF1 protocol 91 discrete I/O control 139 display module 15 configuring setpoints 133 expressing metered data 29 viewing metered data 29 viewing setpoint data 134 display module functionality 38 displaying information 42 editing a parameter 43 issuing commands 44 key functions 39 power up 42 scrolling 43 setting a default screen 44 displaying information 42
F
file data values 309 forced operation 139 frequently asked questions 341
H
harmonic analysis 166 configuring 171 crest factor 167 harmonic distortion 171 harmonic magnitude 170 IEEE THD and DIN 166 IEEE-519 TDD and IEEE-519 pass/fail 170 K-factor 169 reading data 172 reading individual values 173 TIF 168 harmonic distortion 171 harmonic magnitude 170 hours selection 156
I
I/O operations 137 I/O type communication 90 IEEE 519 Pass Fail 170 IEEE 519 TDD 170 IEEE THD and DIN 166 indexed reads 88 issuing commands 44
E
editing a parameter 43 energy counter 35 energy results 34 equal setpoint 127 Ethernet 78, 103 EtherNet IP I/O connection 110 IP CIP protocol 106 more information 112 PCCC CSP protocol 105 performance features 19 web access 112 event log 143 configuration options 144 configuring using communication 146 reading data using communication 147 viewing using the display module 144 event logging of status inputs 142 expressing data 82 expressing metered data 29
K
k factor 169 key functions 39
L
load factor 177 reading the log 178
M
master module 14 communication 14 configuration 14 metering accuracy class 29 metering functionality 27 configurable energy counter rollover 35 demand calculation 35 energy results 34
352
Index
expressing metered data in the display module 29 metering accuracy class 29 power factor results 33 power results 32 projected demand calculation 36 symmetrical component analysis results 31 viewing metered data using the display module 29 voltage current and frequency results 30 metering update rate 60 min/max log 153 accessing using display module 154 interfacing using communications 154 Modbus 64 Modbus RTU slave protocol 92 multiple data table reads using DeviceNet 305 explicit message transfer setup 305 SLC 500 sequencer operation 308
performance features 16 power factor results 33 power results 32 power up 42 Powermonitor 3000 operations 27 Powermonitor 3000 web access 112 product approvals 335 ANSI/IEEE tested 337 CE certification 336 ControlNet conformance testing 335 EMC directive 336 EtherNet/IP conformance testing 335 IEC529/NEMA/UL 508 336 low voltage directive 336 UL/CUL 336 product description 13 projected demand calculation 36 first order projection 37 instantaneous 37 second order projection 37 pulsed control 138
N
network demand and time configuration 55 broadcast port 56 controller command 57 input mode 56 SNTP address 2 57 SNTP address 3 57 time IP address 56 time set interval 56 world time zone 56 no control operation 140 not equal setpoint 128
R
reading harmonic analysis data 172 reading individual harmonic values 173 reading time of use log 158 reading transient analysis 181 reading transient capture 182 relay and KYZ output operation 137 communication loss behavior 140 descrete I/O control 139 forced operation 139 no control operation 140 pulsed control 138 setpoint control 139 Remote I/O 70 performance features 18 status indicators 23 RS-232 65 performance features 18 status indicators 23 RS-485 64 performance features 17 status indicators 23 RSNetWorx for DeviceNet 73
O
operation editing a digital parameter 43 oscillography 159 configuring 160 reading data 162 other precautions 12 over forward setpoint 124 over reverse setpoint 125
P
PanelView Component HMI and EtherNet/IP Communication Network 331
Publication 1404-UM001F-EN-P - November 2009
S
safety considerations 11 sag and swell 174 sample applications 281
353
Index
scrolling 43 serial communication 91 auto sense protocol 95 DF1 protocol 91 Modbus RTU slave protocol 92 setpoint control 139 setpoint inputs 141 setpoint programming and operation 123 equal 127 not equal 128 over forward 124 over reverse 125 under forward 126 under reverse 127 setting default screen 44 simple reads of data tables 87 specifications 335, 337 control relay 338 general input, output and environmental ratings 338 input and output ratings 338 measurement accuracy, resolution, and range 337 relay life 338 status indicators 22 status input operations 141 counters 141 demand period synchronization 141 event logging of status inputs 142 setpoint inputs 141 symmetrical component analysis 31 system clock sample applications 282 date and time summary 304 EtherNet/IP and ControlLogix 287 MicroLogix controller and EtherNet/IP communication networks 296 MicroLogix controller and Modbus communication network 301 PLC-5 controller using Remote I/O 285 RSLinx DDE/OPC and MicroSoft Excel 291
SLC 500 controller and RS-485 communication 282 use OPC for single element password write 295
T
theory of setpoint operation 123 tif 168 time of use 156 configuring the log 157 hours selection 156 reading the log 158 transient analysis configuration 180 transient detection metering and capture 179 clear command 185 configuration 180 reading capture data 182 reading metering data 181
U
under reverse setpoint 127 underforward setpoint 126 user-configured data table setup using ControlLogix and EtherNet/IP 314 sample program operation 314
V
viewing metered data 29 voltage current and frequency results 30
W
writing data 83 writing setpoint configuration using comms 134
354
Installation Assistance
If you experience an anomoly within the first 24 hours of installation, review the information that's contained in this manual. You can contact Customer Support for initial help in getting your product up and running. United States or Canada Outside United States or Canada 1.440.646.3434 Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
PN-55981
Copyright 2009 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.