Relay Settings Tables - 12mar12
Relay Settings Tables - 12mar12
Relay Settings Tables - 12mar12
DATE : Remarks
Breaker No.
Panel No
Setting Function Rated current Rated frequency Line CT Primary Line CT Secondary Line VT Primary Line VT Secondary
Setting Parameter
IN fN
1 or 5A 50 or 60Hz
Ith> K Coefficient Thermal constant T1 Thermal constant T2 Thermal constant Tr Thermal Trip Thermal Alarm Alarm Threshold Thermal Lockout Lockout Thresh Inh Trip Dur St
0.2 to 1.5 In 0 to 10 1 - 180 min. 1 - 360 min. 1 - 999 min. Disabled/Enabled Disabled/Enabled 0.2% to 100% Disabled/Enabled 0.2% to 100% Disabled/Enabled
0.82 In 2 20 min. 20 min. 100 min. Enabled Enabled 80% Enabled 20% Disabled
Page 1 of 5
HT MOTOR RELAY SETTINGS TABLE Motor Feeder Feeder (breaker) Rating Relay / Release Make Relay / Release Type
JOB NO : CLIENT : DOC NO : REV NO : Range Available Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse 0.2 to 15 In 0.04 to 100 0.025 to 1.2 0.01 to 100 0.1 to 10 DT/Inverse 0.0 to 100 Disabled/Enabled 0.2 to 15 In 0.04 to 100
DATE : Remarks
Breaker No.
Panel No
Setting Function
Setting Parameter
Recommended Settings
I>1 Fuction
DT
I>1 Current set Short circuit protection I>1 Time Dealy I>1 TMS I>1 Time Dial I>1 K (RI) I>1 Reset Charac. I>1 t RESET I>2 set as I>1 I>3 Status I>3 Current set I>3 Time Dealy I>4 Set as I>3
Page 2 of 5
HT MOTOR RELAY SETTINGS TABLE Motor Feeder Feeder (breaker) Rating Relay / Release Make Relay / Release Type
DATE : Remarks
Breaker No.
Panel No
Setting Function
Setting Parameter
Recommended Settings
3.5 11.5
ISEF>1 Fuction
Earth Fault Protection ISEF>1 Current ISEF>1 Time Delay ISEF>1 TMS ISEF>1 Time dial ISEF>1 Reset Charac ISEF>1 tReset ISEF>2 Fuction V<1 Function Under voltage protection [27] V<1 Voltage set V< 1 Time delay V<1 TMS V<2 Status
Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse 0.005 to 1 In 0.04 - 200 s 0.025 to 1.2 0.5 to 15 DT/Inverse 0 to 100 sec Disabled/Enabled Disabled/DT/IDMT 15 - 120 V 0.04 - 7200 S 0.05 - 100 Disabled/DT
DT
Page 3 of 5
HT MOTOR RELAY SETTINGS TABLE Motor Feeder Feeder (breaker) Rating Relay / Release Make Relay / Release Type
JOB NO : CLIENT : DOC NO : REV NO : Range Available Disabled/DT/IDMT 50 - 200 V 0.04 - 7200 S Disabled/DT Disabled / DT 0.05 to 0.8 In 0.04 - 200 s Disabled / IMDT Disabled / DT 45.65 Hz 0.1 - 100 s Disabled / IMDT 45.65 Hz 0.1 - 100 s 1In - 120In W 0.04 - 100 sec 0.05 - 300 sec Disabled / Enabled 15 - 75 0.00 - 100.0 sec Disabled / Enabled 0 - 40.0/In 25 - 325.0/In 0 - 100 sec 0 - 100 sec Disabled / Enabled 0 - 40.0/In 25 - 325.0/In
DATE : Remarks
Breaker No.
Panel No
Setting Function Over voltage protection [59] Negative sequence overcurrent (46)
Setting Parameter V> Status V>1 Voltage Set V< 1 Time delay V>2 Status I2>1 Status I2>1 Current I2>1 Time delay I2>2 Status F<1 Status F<1 Setting
Recommended Settings DT 126.5 5 Disabled DT 0.44 In 10 Disabled DT 48.5 5 DT 51.5 5 10In 5 17 Enabled 25 12 Enabled 38 67.3 10 0 Disabled -
F<1 Time delay F<2 Status F<2 Setting F<2 Time delay Rev P < Power set Rev P < Time delay Rev P < Drop-of time FFail Alarm status FFail Alarm angle FFail Alarm delay FFail 1 status FFail 1 -Xa1 FFail 1 -Xb1 FFail 1 Time delay FFail 1 DO Timer FFail 2 status FFail 2 -Xa1 FFail 2 -Xb1
Page 4 of 5
Field failure SETTINGS TABLE HT MOTOR RELAY relay (40) Feeder Motor Feeder (breaker) Rating Relay / Release Make Relay / Release Type
JOB NO : CLIENT : DOC NO : REV NO : Range Available 0 - 100 sec 0 - 100 sec Disabled / DT 0.1 - 0.9 0.05 - 100 sec Disabled / DT 0.1 - 0.9 0.05 - 100 sec 0.05 - 300 sec
DATE : Remarks
Breaker No.
Panel No
Setting Function
Setting Parameter FFail 2 Time delay FFail 2 DO Timer PF<Status Lead Power Fact lead
PF < Lead TD PF<Status Llag Power Fact lag PF < Lag TD PF < Drop-off time