Procontic NCC485
Procontic NCC485
Procontic NCC485
95 - FRCTL
8.1.2 NCC 485 SeriaI Iine converters
RS232/RS485 isolated converter
ABB Procontic CS31
NCC 485 24VDC 1W
SW2
RS232
POWER RXD TXD POWER
ON
SW1
OFF
1
6
4
3
5
7
2 8
POWER SUPPLY
+24 0
RS 485
D2- D2+ D1+ D1- SH
1 2 3 4 5 6 7
ON
8
1 2 3 4 5
6 7 8 9
The NCC 485 module is an RS232/RS485
interface converter. lt is the solution of transmission
problems in industrial data communications.
The NCC 485 allows a isolated connection between two
RS232 interface and an RS485 interface.
ln half or full duplex protocol, the NCC 485 allows long
ranges transfers, the creation of multiple point connection.
lt is particulary adapted for the connection of the central
units 07KR31 and 07KT31 to a MODBUS network.
Description
Removable connector for 24VDC power supply .... `
Removable connector for RS485 interface ............ _
SubD9 connector for RS232 interface .................... ^
Switch for MODBUS/ASCll or active modes.......... ]
Dip-switches for RS485 configuration..................... \
1 green Led labelled "power" to indicate
the presence of supply ........................................... [
1 green Led labelled "iso power" to indicate
the presence of the isolated supply
for RS485 interface ................................................ Z
2 yellow Leds labelled "TXD" and "RXD"
to indicate the data processing ............................... Y
Cable for connection between the RS232
interface of NCC 485 and the RS232 interface
of the CS31central units ......................................... X
C
2
1
4
D
C
2
2
3
D
X
NCC 485 8.1.2-2 ABB Procontic CS31/ Edition : 11.95 - FRCTL
TECHNICAL CHARACTERISTICS
Power supply 24 VDC
lsolated power supply yes
Maximum baud rate 19200
Maximum consumption 40 mA
Mechanical data :
P Mounting on DlL rail yes
P Width x height x depth 120x80x85
Order number FPR3471100R0006
Weight 340g
RS232 interface characteristics
Connector Sub D9 male
Transfer signals TxD, RxD
Direction switching RS485 TxD
Delay 10ks at the begin of frame
2.2ms at the end
Protocol user specific
RS485 interface characteristics
lsolated RS485 interface yes
Half of full duplex communication yes
lntegrated resistance for impedance of end of line yes
Maximum number of NCC 485 on RS485 line 32
Range 1200m twisted pair
Polarization line yes per switch
Cable :
Connectors SubD 9 male-SubD 9 female
Lenght 33cm
Configurations
SW1
P OFF : pin 6 is independant of pin 7
Active mode configuration for CS31 central units.
P ON : pin 6 is connected to pin 7
ASCll or MODBUS mode configuration according CS31
central units and value of the system constant KW00,06
(refer to central units descriptions).
SW2
Dip-switch 1 :
P SW2-1 ON 120 Ohm resistor between D2+ and D2P
P SW2-1 has to be set to ON only if NCC 485 is installed
at one of the ends of RS485 line.
Dip-switch 2 :
P SW2-2 ON 120 Ohm resistor between D1+ and D1P
P SW2-2 has to be set to ON only if NCC 485 is installed
at one of the ends of RS485 line.
Dip-switch 3 : SW2-3 ON OFF
Dip-switch 4 : SW2-4 OFF ON
full duplex half duplex
Dip-switch 5 : SW2-5 ON polarization of D2+ line
Dip-switch 6 : SW2-6 ON polarization of D2P line
Dip-switch 7 : SW2-7 ON polarization of D1+ line
Dip-switch 8 : SW2-8 ON polarization of D1P line
Caution : The RS485 has to be polarized by only one of
the participants.
1 2 3 4 5 6 7
ON
8
C
2
1
4
D
/
5
ON
SW1
OFF
C
2
1
4
D
/
4
!
"
#
$
The 24 VDC power supply of the central unit can be used to supply only one unit NCC 485.
NCC 485 8.1.2-6 ABB Procontic CS31/ Edition : 11.95 - FRCTL
Configuration
HaIf dupIex configuration
SW2-1 ON SW2-1 OFF SW2-1 ON
SW2-2 ON SW2-2 OFF SW2-2 ON
SW2-3 OFF SW2-3 OFF SW2-3 OFF
SW2-4 ON SW2-4 ON SW2-4 ON
SW2-5 ON SW2-5 OFF SW2-5 OFF
SW2-6 ON SW2-6 OFF SW2-6 OFF
SW2-7 ON SW2-7 OFF SW2-7 OFF
SW2-8 ON SW2-8 OFF SW2-8 OFF
ABB Procontic CS31
NCC 485 24VDC 1W
SW2
RS232
POWER RXD TXD POWER
ON
SW1
OFF
POWER SUPPLY
+24 0
RS 485
D2- D2+ D1+ D1- SH
1 2 3 4 5 6 7
ON
8
1 2 3 4 5
6 7 8 9
CPU1
Master
CPU2
Slave
CPUn (n<32)
Slave
24VDC
0VDC
ABB Procontic CS31
NCC 485 24VDC 1W
SW2
RS232
POWER RXD TXD POWER
ON
SW1
OFF
POWER SUPPLY
+24 0
RS 485
D2- D2+ D1+ D1- SH
1 2 3 4 5 6 7
ON
8
1 2 3 4 5
6 7 8 9
24VDC
0VDC
ABB Procontic CS31
NCC 485 24VDC 1W
SW2
RS232
POWER RXD TXD POWER
ON
SW1
OFF
POWER SUPPLY
+24 0
RS 485
D2- D2+ D1+ D1- SH
1 2 3 4 5 6 7
ON
8
1 2 3 4 5
6 7 8 9
24VDC
0VDC
!
"
%
$
FuII dupIex configuration
ABB Procontic CS31
NCC 485 24VDC 1W
SW2
RS232
POWER RXD TXD POWER
ON
SW1
OFF
POWER SUPPLY
+24 0
RS 485
D2- D2+ D1+ D1- SH
1 2 3 4 5 6 7
ON
8
1 2 3 4 5
6 7 8 9
CPU1
Master
CPU2
Slave
CPUn (n<32)
Slave
24VDC
0VDC
ABB Procontic CS31
NCC 485 24VDC 1W
SW2
RS232
POWER RXD TXD POWER
ON
SW1
OFF
POWER SUPPLY
+24 0
RS 485
D2- D2+ D1+ D1- SH
1 2 3 4 5 6 7
ON
8
1 2 3 4 5
6 7 8 9
24VDC
0VDC
ABB Procontic CS31
NCC 485 24VDC 1W
SW2
RS232
POWER RXD TXD POWER
ON
SW1
OFF
POWER SUPPLY
+24 0
RS 485
D2- D2+ D1+ D1- SH
1 2 3 4 5 6 7
ON
8
1 2 3 4 5
6 7 8 9
24VDC
0VDC
!
"
&
$
SW2-1 ON SW2-1 OFF SW2-1 ON
SW2-2 ON SW2-2 OFF SW2-2 ON
SW2-3 ON SW2-3 ON SW2-3 ON
SW2-4 OFF SW2-4 OFF SW2-4 OFF
SW2-5 ON SW2-5 OFF SW2-5 OFF
SW2-6 ON SW2-6 OFF SW2-6 OFF
SW2-7 ON SW2-7 OFF SW2-7 OFF
SW2-8 ON SW2-8 OFF SW2-8 OFF