UPS Handbook EMEA
UPS Handbook EMEA
UPS Handbook EMEA
UPS Handbook
This comprehensive guide includes all the information that resellers need to help them understand and sell the industry-leading power protection solutions from Eaton. Youll find a wealth of useful resources, all designed to help you develop the best solution for your customers. This handbook includes information about power problems, factors affecting battery life, an overview of various UPS topologies in addition to plug and receptacle charts. Eaton is a global leader in power protection, distribution and management solutions. Eaton offers a comprehensive range of products and services designed to serve the power system needs of the industrial, institutional, government, utility, commercial, residential, IT and mission-critical OEM markets globally. Eatons portfolio includes uninterruptible power supplies (UPSs), surge protective devices, power distribution units (ePDUs), remote monitoring, meters, software, connectivity, enclosures and services. Whether youre supplying power protection for small, medium or large data centers, health care facilities, or other environments in which ensuring uptime and safeguarding data are critical, the UPS Handbook is your one-stop source for essential information. TABLE OF CONTENTS
Introduction 2 Everything you need to know about electricity The basics of voltage, amperes and frequency 3 Worldwide voltage 4 Single-phase power 6 Three-phase power 7 Everything you need to know about UPS Why a UPS? 8 Nine power problem overview 9 UPS topologies 10 UPS form factors 11 Input plugs and output receptacles 12 UPS battery overview 13 Factors affecting battery life 15 UPS software overview 16 Service overview 17 Get to know Eaton power quality products Eaton product overview 19 Eaton technologies 21 How to sell UPSs successfully Top 10 UPS design considerations 23 Decentralised or centralised UPS? 26 Critical questions to ask prospective UPS customers 28 FAQs, glossary & acronyms Frequently asked questions 29 Glossary of power terms 31 Commonly-used acronyms 35
EATON CORPORATION
Three of the most common terms used when talking about electricity and electrical products are voltage, amperes and frequency. Put simply, a volt (V) is the measure of the pressure with which electricity moves through a wire or circuit, while an ampere (A), or amp for short, is a measure of the volume . Volts and amps are often compared to water in a hose, with volts representing the amount of pressure and amps the volume of water. When you turn on a hose without a nozzle at the end, there is a lot of water (amps) but not much pressure (volts). By placing your thumb over the end of the hose, you reduce the volume and increase the pressure, so the water squirts further. In terms of electricity, the number of amps is a measure of how many electrons are flowing in the wire, while the voltage level tells us how hard those electrons are being pushed. In the same way as a fire hose operating at the same pressure as a garden hose delivers a larger volume of water, a wire carrying a higher voltage needs to have a larger diameter for an equivalent voltage. Frequency (Hz) is a measure of how many times a second the electrical signal oscillates. The frequency of household voltages varies according to geographical location; in industrial voltages it can be customised to meet specific site requirements. Making sure that the volts, amps and frequency of connected equipment are compatible with the electrical supply can be compared to filling up a car with the correct type of fuel.
Single-phase voltages
110-127V; 60Hz (also 208V; 60Hz) 110-127V; 60Hz 100V 220/230V; 50Hz 240V; 50Hz
Country Afghanistan Albania Algeria Angola Argentina Armenia Australia Austria Azerbaijan Bahrain Bangladesh Belarus Belgium Benin Bolivia Botswana Brazil Brunei Bulgaria Burkina Faso Burma (Myanmar) Burundi Cambodia Cameroon
Single phase Three-Phase Frequency (Hz) voltage (V) voltage (V) 220 380 230 400 230 400 220 380 220 380 230 380 240 415 230 400 220 380 230 400 220 380 220 380 230 400 220 380 110-115/220 400 400 220 400 110-127 220/380 220 400 240 415 230 400 220 230 380 400 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 60 60 50 50 50 50 50 50 50
Canada Chad Chile China Colombia Congo Congo, Dem. Rep. of (formerly Zaire) Costa Rica Croatia Cyprus Czech Republic Denmark Djibouti Dominica Dominican Republic Ecuador Egypt El Salvador England Estonia Ethiopia Faroe Islands Falkland Islands Finland France Gabon Gambia
120 208/240/600 380 380 220 380 220 220 380 110 440 220 400 220 120 380 415
60 50 50 50 50 60 50 50 60 50 50 50 50 50 50 60 60 50 60 50 50 50 50 50 50 50 50 50
220 400 230 380 110 415 120 190 220 380 115 400 240 400 230 400 220 380 230 240 400 415
Bosnia-Herzegovina 220
EATON CORPORATION
Country Gaza Georgia Germany Ghana Greece Guadeloupe Guatemala Guinea Guyana Haiti Honduras Hong Kong Hungary Iceland India Indonesia Iraq Ireland Israel Italy Ivory Coast Jamaica Japan Jordan Kazakhstan Kenya Korea, South Kuwait Kyrgyzstan Laos Latvia Lebanon Lesotho Liberia Libya Liechtenstein Lithuania Luxembourg Macedonia Madagascar Malawi Malaysia Mali Malta Martinique Mauritania Mauritius Mexico Moldova Monaco Mongolia Morocco Mozambique Namibia Nauru Nepal Netherland Antilles Netherlands
Single phase Three-Phase Frequency (Hz) voltage (V) voltage (V) 230 400 220 380 220-230 400 230 400 220-230 400 220 400 120 208 220 208 120-240 - 110 - 110 - 220 380 230 400 230 400 230 400 220 400 230 400 230 400 230 400 220-230 400 220 380 110 - 100 200 230 400 220 380 240 415 220 380 240 415 220 380 230 400 220 400 110-220 400 240 380 120 208 127-230 220/400 230 400 220 400 220-230 400 230 400 220 380 230 400 240 415 220 380 240 400 220 380 220 220 230 400 127 220/480 220 380 230 400 220 400 220 380 220 380 220-250 380 240 415 230 400 120-127/220 220/380 220-230 400 50 50 50 50 50 50 60 50 50 50-60 50-60 60 50 50 50 50 50 50 50 50 50 50 50 50&60 50 50 50 50&60 50 50 50 50 50 50 60 50 50 50 50 50 50 50 50 50 50 60 50 50 50 50 50 50 50 50 50 50 50 50/60 50
New Zealand Nicaragua Niger Nigeria Northern Ireland Norway Oman Pakistan Panama Paraguay Peru Philippines Poland Portugal Puerto Rico Qatar Runion Island Romania Russia Rwanda Saudi Arabia Scotland Senegal Serbia Seychelles Singapore Slovakia Slovenia Somalia South Africa Spain Sri Lanka Sudan Surinam Swaziland Sweden Switzerland Taiwan Tajikistan Tanzania Thailand Togo Tonga Tunisia Turkey Turkmenistan Uganda Ukraine United Arab Emirates United Kingdom United States Uruguay Uzbekistan Venezuela Vietnam Wales Yemen Zambia Zimbabwe
230
415
50 60 50 50 50 50 50 50 60 50 50/60 60 50 50 60 50 50 50 50 50 50/60 50 50 50 50 50 50 50 50 50 50 50 50 60 50 50 50 60 50 50 50 50 60 50 50 50 50 50 50 50 60 50 50 60 50 50 50 50 50
120 208 220 380 240 400 240 400 230 400 240 415 230 400 110-120 - 220 380 110/220 220 220 380 230 400 220 400 120 230 208 400 240 415 230 400 220 400 230 400 127/220 380 220 400 230 400 230 400 240 240 230 400 230 400 230 400 110/220 380 220-250 230 400 400 220-230 400 230 400 115 400 230 220 220-230 400 230 400 110 - 220 380 230 400 220/230 380 220 380 240 415 230 400 230 400 220 380 240 415 220 380 220/230 240 120 415 415 208/480
220 220 220 380 120 240 120/220 380 220 400 220 400 220 400 220 415
Single-phase power
In electrical engineering,single-phase electric powerrefers to the distribution ofalternating currentelectric powerusing a system in which all the voltages of the supply vary in unison. Single-phase distribution is used when loads are mostly lighting and heating, with few large electric motors.
Single-phase electricity is what you have in your house. In general, household electrical supply is a single-phase, 220-230 volt AC supply. If you were to take an oscilloscope and measure the power from a normal wall socket in your house, the power would be seen as a sine wave, with an effective root mean square (RMS) voltage of 230 volts and an oscillation rate of 50 cycles per second, or 50 Hz. Power that oscillates in this way is generally referred to as alternating current, or AC. The alternative to AC is DC, or direct current, such as that produced by batteries. AC has at least three advantages over DC in an electrical distribution grid: 1. Large electricity generators generate AC naturally, so conversion to DC requires an extra step. 2. Electrical transformers, which the power distribution grid depends on, need an alternating current in order to operate. 3. Converting AC to DC is easy, whereas converting DC to AC is expensive. This makes AC a better choice.
EATON CORPORATION
Three-phase power
As well being the most efficient way to distribute power over long distances, three-phase power also enables industrial equipment to operate more efficiently. Three-phase power is characterised by three single-phase waves that are offset in their phase angle by 120 degrees, or one third of the sine wave period (see Figure 1 below). Three-phase voltage can be measured from each phase to neutral or from one phase to any other. The voltage relation between phase to neutral and phase to phase is a factor of square root of three (e.g. 230 V versus 400 V). Conversely, single-phase power is distributed through household outlets to power everyday equipment such as laptops, lighting and televisions. As shown in Figure 2, if you were to look at the voltage coming from a single-phase outlet on an oscilloscope, you would see a single wave. This is because single-phase power is obtained by simply using one phase of a 270 three-phase system. Its RMS 90 180 360 voltage is 230V and it oscillates at 50 Hz (or 50 times a second).
90
180
270
360
90
180
270
360
90
180
270
360
EATON CORPORATION
Power problem
Definition*
A total loss of utility power
Cause*
Can be caused by a number of events: lightning strikes, downed power lines, grid over-demands, accidents and natural disasters.
Solution
Overvoltage
Increased line voltage for periods ranging from a few minutes to a few days High frequency waveform caused by EMI interference
Triggered by a rapid reduction in power loads, heavy equipment being turned off, or by utility switching. Can result in damage to hardware. Can be caused by either RFI or EMI interference generated by transmitters, welding devices, SCR driven printers, lightning, etc. Resulting from generator or small co-generation sites being loaded and unloaded. Frequency variation can cause erratic operation, data loss, system crashes and equipment damage.
6
7 8 9
Frequency variation
Instantaneous and under-voltage Normal duration is shorter than a spike and generally falls in the range (notch) of nanoseconds. Distortion of the normal line Switch mode power supplies, variable waveform, generally transmitted speed motors and drives, copiers by nonlinear loads and fax machines are examples of non-linear loads. Can cause communication errors, overheating and hardware damage.
3 4
Can be caused by a lightning strike and can send line voltages to levels in excess of 6,000 volts. A spike almost always results in data loss or hardware damage.
Undervoltage (brownout)
Reduced line voltage for periods Can be caused by an intentional utility voltage ranging from a few minutes to a reduction to conserve power during peak demand periods or other heavy loads that few days exceed supply capacity.
Power sag
Triggered by the startup of large loads, utility switching, utility equipment failure, lightning, and power service being insufficient to meet demand. In addition to causing equipment crashes, power sags can also damage hardware.
Power failure
UPS topologies
Passive standby topology (off-line) is used for protecting PCs against power failure, power sag and power surge. In normal mode, the UPS supplies power to the application directly from the mains, filtered but without active conversion. The battery is charged from the mains. In the event of a power cut or fluctuation, the UPS delivers stable power from the battery. This topology is low cost and provides sufficient protection for office environments. Passive standby topology is not suitable in cases where the power supply is of low quality (for example, on industrial sites) or subject to frequent disruptions.
AC to DC Rectifier
DC to AC Inverter Battery
Line interactive topology is used for protecting enterprise network and IT applications against power failure, power sag, power surge, undervoltage and overvoltage. In normal mode, the device is controlled by a microprocessor that monitors the quality of the supply and reacts to fluctuations. A voltage compensation circuit is enabled to boost or reduce the supply voltage in order to compensate for fluctuations. The main advantage of line-interactive topology is that it enables compensation for under- and overvoltage without using the batteries.
DC to AC Inverter Battery
AC to DC Rectifier AC to DC Rectifier
Double-conversion topology (on-line) is a basis for UPSs designed for continuous power protection of critical equipment against all nine of the common power problems described on page 9. It ensures a consistent quality of power supply regardless of disturbances in the incoming mains. The output voltage is entirely regenerated by a sequence of AC to DC conversion followed by DC to AC conversion in order to create power supply without any electrical interference. Double-conversion UPSs can be used with any type of equipment as there are no transients when changing over to battery power.
Normal operation Battery power
AC to DC Rectifier DC to AC Internal Static Bypass Inverter Internal Static Bypass Battery AC to DC Rectifier AC to DC Rectifier DC to AC Inverter DC to AC Inverter Battery Battery
10
EATON CORPORATION
a. The Eaton Ellipse fits easily on top of or under a desk b. The Eaton 9130 tower UPS fits under a desk or in a network cabinet 2. Wallmount UPS The Eaton 5115 rackmount UPS includes hardware for mounting it on a wall
3. Rackmount UPS
3 4
The Eaton 9130 rackmount UPS occupies only 2U of rack space (fits both 2-post and 4-post racks) 4. Two-in-one rackmount/tower UPS The Eaton 5130 UPS can be mounted in a rack or installed as a tower model 5. Scalable UPS a. The Eaton BladeUPS is a scalable, redundant rackmount UPS b. Eaton MX Frame 6. Large tower UPS The Eaton 9390 and 9395 UPSs are designed to be a central backup for multiple loads, for example in data centres.
11
IEC-320-C13 (female)
IEC-320-C14 (male)
IEC-320-C19 (female)
IEC-320-C20 (male)
FR BS
IEC-309, 16A
IEC-309, 32A
Schuko
12
EATON CORPORATION
Cover/Lid
VRLA batteries are sealed, usually within polypropylene plastic, the advantage being that there is no liquid sloshing around that might leak or drip.
Polypropylene Container/Jar
Separator
The most common type of battery used in UPSs is the valve-regulated lead acid (VRLA) battery, also known as a sealed or maintenance-free battery.
The most common type of battery used in UPSs is valve-regulated lead acid (VRLA) batteries, also known as sealed or maintenance free. VRLA batteries are sealed, usually within polypropylene plastic, which offers the advantage of not containing any sloshing liquid that might leak or drip. Because water cannot be added to VRLA batteries, recombination of water is critical to their life and health, and any factor that increases the rate of evaporation or water loss such as temperature or heat from the charging current reduces the life of the battery.
2. Is there any difference between the batteries used by smaller UPSs, from 250 VA to 3 kVA, and the ones used by larger UPSs? While basic battery technology, and the risks to battery life, remains the same regardless of UPS size, there are some inherent differences between large and small applications. First, smaller UPSs typically have only one VRLA battery that supports the load and needs maintenance. As systems get larger, increasing battery capacity to support the load gets more complicated. Larger systems may require multiple strings of batteries, introducing complexity to battery maintenance and support. Individual batteries must be monitored to prevent a single bad battery from taking down an entire string, thereby putting the load at risk. Also, as systems get larger, wet-cell batteries become much more common. 3. My UPS has been in storage for over a year. Are the batteries still good? As batteries sit unused, with no charging regimen, their life will decrease. Due to the self-discharge characteristics of lead acid batteries, it is imperative that they be charged after every six to 10 months of storage. Otherwise, permanent loss of capacity will occur between 18 and 30 months. To prolong shelf life without charging, store batteries at 10C (50F) or less.
13
4. What is the difference between hotswappable and user-replaceable batteries? Hot-swappable batteries can be changed out while the UPS is running. Userreplaceable batteries are usually found in smaller UPSs and require no special tools or training to replace.
7. What is the average lifespan of UPS batteries? The standard lifespan for VRLA batteries is three to five years. However, expected life can vary greatly due to environmental conditions, number of discharge cycles, and adequate maintenance. Have a regular schedule of battery maintenance and monitoring to ensure you know when your batteries are reaching their end of useful life. The typical life of an Eaton UPS with ABM technology is 50 per cent longer than standard models. 8. How can you be sure UPS batteries are in good condition and ensure they have maximum holdover in the event of a power failure? What preventive maintenance procedures should be done and how often?
11. What is thermal runaway? Thermal runaway occurs when the heat generated in a lead acid cell exceeds its ability to dissipate that heat, which can lead to an explosion, especially in sealed cells. The heat generated in the cell may occur without any warning signs and may be caused by overcharging, excessive charging, internal physical damage, internal short circuit or a hot environment. 12. Why do batteries fail? Batteries can fail for a multitude of reasons, but common reasons are: high or uneven temperatures inaccurate float charge voltage loose inter-cell links or connections loss of electrolyte due to drying out or damage to the case lack of maintenance, ageing 13. How is battery performance generally measured? Batteries are generally rated for 100+ discharges and recharges, but many batteries show a marked decline in charging capacity after as few as 10 discharges. The lower the charge the battery can accept, the less runtime it can deliver. Look for batteries with a high-rate design that sustains stable performance for a long service term.
UPS models like the Eaton 9130 feature hot-swappable batteries for maximum uptime.
5. How is battery runtime affected if I reduce the load on the UPS? The battery runtime will increase if the load is reduced. As a general rule, if you reduce the load by half, you triple the runtime.
6. If I add more batteries to a UPS can I add more load? Adding more batteries to a UPS can increase the battery runtime to support the load. However, adding more batteries to the UPS does not increase its capacity. Ensure that your UPS has sufficient capacity to support your load, then add batteries to fit your runtime needs.
The batteries used in the UPS and associated battery modules and cabinets are sealed, valve-regulated lead acid battery often referred to as maintenance-free batteries. While this type of battery is sealed and you do not need to check the fluid level in the battery, they do require some attention to ensure proper operation. Eatons ABM technology extends the life of valve-regulated lead acid batteries by applying sophisticated logic to the charging regime. ABM also provides an additional feature for monitoring battery condition and advance warning about the end of battery life upon detection of a weak battery. 9. How long does it take for the UPS batteries to recharge? On average, it takes 10 times the discharge time for the UPS batteries to recover. (A 30-minute battery discharge requires about 300 minutes to recharge.) After each power outage, the recharge process begins immediately. It is important to note that the load is fully protected while the batteries are recharging. However, if the batteries are needed during the recharge time, the holdover time available will be less than it would have been if the batteries were fully charged. 10. What are the risks associated with a lack of battery maintenance? The primary risks of improperly maintained batteries are load loss, fire, property damage and personal injury.
Adding extended battery modules increases runtime but does not increase the power rating or capacity of the UPS
14
EATON CORPORATION
15
Eatons Intelligent Power Manager facilitates easy and versatile remote monitoring and management of multiple devices, keeping you informed about power and environmental conditions.
In addition to facilitating automatic, orderly shutdown of all connected devices during an extended outage, power management software delivers a broad spectrum of other advantages. The perfect complement to any UPS solution, management software keeps a constant watch over network health through its monitoring and management capabilities. Most power management software is shipped with the UPS and is usually available as a free download online as well. Power event notifications are available as audible alarms, pop-up alerts on a monitor, e-mails to predefined recipients based on the condition, text messages, and triggers for a multitude of network and building management systems to initiate the orderly shutdown of equipment. Some software offerings are capable of delivering a global view across the network often from any PC with an internet browser. Software can also provide a complete log of events and UPS utility data, which is invaluable when debugging a power anomaly. Many power management products have the ability to centralise alarms, organise data by customised views and maintain event logs for preventive maintenance of the entire installed equipment base. The more robust and versatile software offerings are compatible with devices that support a network interface, including all manufacturers UPSs, environmental sensors, ePDUs and other devices. Furthermore, power management software enables load segment control for UPS models that support this feature. Because power protection and management are just as vital for virtual machines as they are for physical servers, new software technologies have been specifically designed to provide monitoring and management capabilities in virtualised environments. Shutdown software is now compatible with VMwares ESXi and vSphere and Microsofts Hyper-V, enabling graceful shutdown of multiple virtual machines.
To view an online demonstration of Eatons power management software capabilities, please visit www.eaton.com/intelligentpowermanager.
16
EATON CORPORATION
Service overview
One of the best ways to protect your customers investment is by including a service contract with your UPS sales. Scheduled preventive maintenance can help detect a wide range of problems before they become serious and costly issues. In fact, research indicates that regular preventive maintenance is crucial in order to achieve maximum performance from equipment. Studies show that routine preventive maintenance can significantly reduce the likelihood that a UPS will succumb to downtime. The 2007 Study of Root Causes of Load Losses compiled by Eaton revealed that customers who did not take advantage of preventive maintenance visits were almost twice more likely to experience a UPS failure than those who had completed the one recommended preventive maintenance visit per year. UPSs are complex devices that perform several critical power conditioning and backup supply functions, and are subject to failure. Without proper maintenance, all UPSs will eventually fail over their useful life since critical components like batteries and capacitors will wear out from normal use. A properly planned maintenance contract delivered by trained and experienced personnel can greatly minimise the risk of failure.
On-site repair. The customer contacts the UPS service provider and a factory-trained field technician diagnoses and repairs electrical or batteryrelated problems on site. Smaller UPS products up to 3000 kVA are repared at a depot, while products over 3000 VA are normally serviced on-site as they are either hardwired (cannot be unplugged) or too heavy to ship.
17
Service contracts usually combine parts and labour coverage (electronics, batteries or both), at least one or more UPS preventive maintenance inspections annually, and a combination of coverage hours and arrival response time. Plans can be tailored to meet almost any need. Special features such as remote monitoring, battery replacement insurance and spare part kits may also be added.
An extended warranty (or basic warranty) may also be purchased for many UPS products. A warranty commonly covers specified parts and labour such as electronic components for a fixed period of time. It will not include 24/7 coverage or arrival response times, nor will it include preventive maintenance, although extra services can be purchased in addition to a warranty extension. The more services added to a warranty, the closer it becomes to a support agreement.
Time and Material (T&M) service is a pay-as-you-go approach in which the service provider carries out a repair only when something breaks. T&M can be done either via depot repair or on site, depending on the UPS. This method may not be the best solution for some customers, since it is often expensive, and there is the uncertainty of not knowing when a field technician will arrive. Because support agreement (contract) customers always take priority, for non-contract customers T&M response times may be as long as several days, depending on the product and location.
Larger UPS models require on-site preventive maintenance visits for optimal performance
18
EATON CORPORATION
Eatons Protection Box surge suppressors offer the best price/performance ratio for SOHO users looking for a convenient way to combine multiple receptacles and excellent surge suppression capabilities. PC/workstation and home A/V UPS Power range: 500 VA1500 VA These Eaton UPSs provide the perfect level of protection for small office/home office (SOHO) applications. These essential, cost-effective products prevent damage such as data loss, file corruption, flickering lights, hardware damage and equipment shutoff, and they are most commonly used to protect single workstations, telephone systems and point-ofsale (POS) equipment. Eaton Ellipse MAX, 6001500 VA
Ideal for high-density server environments and demanding industrial applications, the Eaton EX RT UPS is specifically engineered to meet the high availability demands of customers with switches, IT systems, measuring instruments, PLCs, industrial PCs and other sensitive electronic equipment.
Data centre and facility UPS Power range: 101100 kVA Featuring an array of inventive features, Eatons data centre and facility UPS solutions incorporate the design elements essential to protecting the most critical of applications. These groundbreaking solutions address current and future power protection requirements, featuring scalable architecture that grows with you to manage changing needs with the highest levels of efficiency and reliability. And, with Eatons Energy Saver System technology, an Eaton UPS can run at 99 per cent efficiency, meaning that the total cost of the UPS can usually be recovered in three to five years. Eaton BladeUPS, 1260 kW
The Eaton Ellipse MAX UPS provides cost-effective, lineinteractive backup power and voltage regulation. With its compact form factor, the Ellipse MAX can be utilised as a standalone tower or under a computer monitor. This UPS is also equipped with local outlets. Network and server UPS Power range: 500 VA18000 VA Eaton offers an extensive and innovative line of network and server UPS solutions to protect rack servers, data storage, storage systems, VoIP equipment, network equipment and other critical devices. Get industry-leading power protection with the highest efficiency for increased energy savings in optimised rack, tower and rack/tower form factors. Eaton 9130, 7006000 VA, rack and tower
The scalable and modular BladeUPS expands power protection up to 60 kW in a single 19-inch rack while reducing energy and cooling costs with its energy-efficient UPS design. The BladeUPS packs 12 kW of power into only 6U of rack space.
The 9130 delivers more real power with a 0.9 power factor and offers a high efficiency mode, performing at a remarkable 95 per cent efficiency or higher. This UPS delivers superior power protection for IT and networking environments as well as medical and manufacturing systems.
19
Eaton enclosures
The 9390 UPS provides a high-end power quality solution for data centres, banks and other critical computing applications.
Designed specifically for IT applications, this 42U modern enclosure offers strength, stability and a vendor-neutral environment to house any IT equipment. The enclosure is complemented with a range of cable management, cooling and power distribution accessories to enable you to tailor your enclosures to your specific application. Software and connectivity Eatons Intelligent Power Software Suite delivers the ability to manage all your power devices over your network or via the internet. With both supervisory and protection capability, our software allows you to monitor your power devices and even gracefully shut operating systems and computers down in the event of an extended power outage. Eatons connectivity products are accessory hardware options that link UPS products with external monitoring system devices. Our connectivity products provide communication compatibility through the internet, serial, ModBus or SNMP .
The Eaton 9395 UPS combines technical innovation with a rich feature set to provide best-in-class power protection with high energy density for large data centres, healthcare applications and other critical systems.
Power distribution Eatons power distribution solutions are designed to help you save money, prevent downtime and use energy more efficiently. Our comprehensive portfolio includes enclosures as well as standard and custom ePDUs (enclosure power distribution units) that are based on different technologies including Basic, Metered, Monitored, Advanced Monitored, Inline Monitored and Managed. ePDU
Eaton services Eaton provides an extensive technical support network to cover the power protection needs of our customers. We offer a number of distinct service packages to match different types of maintenance needs and budgets. Whichever package you choose, you can rest assured that it will deliver power security and reliability to keep your core business running. For more information, please contact your local Eaton service organisation or authorised service partner. Eaton offers power quality services for its UPS products as well as for related equipment such as power distribution units (ePDUs) and batteries. Eaton also services products from legacy brands including Fiskars, Powerware, Exide Electronics, Best Power and MGE Office Protection Systems.
From basic, efficient power distribution to intelligent power management capabilities, Eaton ePDU products are designed to meet the demands of every data centre.
20
EATON CORPORATION
Eaton technologies
Eaton has been developing its innovative technical solutions in the power protection field since receiving its first patent in 1962. As a technology leader, Eaton continues to meet its customers rapidly changing needs with advanced patented technologies. Transformer-free technology The transformer-free technology used in Eaton UPSs brings improved performance and value. This is achieved with small and lightweight filter inductors, high-performance IGBTs in both the inverter and rectifier, and an advanced control algorithm. A transformer-free UPS typically weighs 50 per cent less than legacy UPS topology designs and occupies just 60 per cent of the footprint. Low input THD (<4.5per cent at full load) and high input power factor (>0.99) are supported down to nearly 10per cent load without the need for an additional input filter. In addition, full load efficiency can reach 94.5per cent and above. Energy Saver System (ESS) Eatons innovative ESS technology enables the UPS to reach an industry-leading efficiency level of 99 per cent by allowing the UPS to safely provide mains current directly to a load when the input is within acceptable voltage and frequency limits. ESSs fast detection algorithms continuously monitor incoming power quality. If the predefined limits are exceeded, ESS immediately engages the UPS power converters, allowing transition to full voltage and frequency independent (VFI) double-conversion mode in less than two milliseconds. ESS is available in Eaton 9395 and Eaton 9390 UPSs. Variable Module Management System (VMMS) UPS systems are rarely loaded at full capacity; lighter loads are the rule rather than the exception. At loads less than 40 per cent of the full load rating, UPS efficiency decreases, thus increasing the systems overall energy consumption. The solution is Eatons VMMS technology (implemented in the Eaton 9395 UPS), which allows the UPS to achieve higher efficiency for lighter loads. With VMMS, the UPS can decide which of the power modules are in idle mode. This way, the remaining power modules drive the load with higher efficiency. When the load increases again and more power modules are needed, the system immediately shifts the load into additional modules. VMMS adapts both to a single UPS consisting of multiple power modules and multiple UPS parallel systems.
VMMS
UPS1UPS2UPS3
L O A D
Full system efficiency is automatically optimised according to the load level Variable Module Management System (VMMS) technology maximises efficiencies at lighter loads without compromising reliability.
21
Hot Sync technology Patented Hot Sync parallel load-sharing technology guarantees maximum system availability by eliminating the risk of single point of failure. Hot Sync is based on a parallel configuration in which two or more units share the same load. If one unit fails, the other units take over its tasks, isolates the damaged unit and continues to supply electricity without interruption. The technology is unique because it enables the UPS units to operate completely independently; no communication wiring between units is required to transmit systemlevel information for output phase adjusting. The technology is available for all three-phase UPSs.
ABM technology Eaton has created ABM technology to extend the life of valve regulated lead acid batteries by applying sophisticated logic to the charging regime. Using the traditional trickle-charge method, batteries become subject to electrode corrosion and electrolyte dry-out, especially in standby service use due to continuous float charging. ABM essentially enables a more intelligent charging routine by preventing unnecessary charging, thus significantly reducing wear and tear. ABM provides an additional feature for monitoring battery condition and advance warning about the end of battery life upon detection of a weak battery. It also optimises the recharge time, which is advantageous when there may be consecutive power outages within a short period. ABM has been used for over 15 years in our UPSs ranging from 1 to 160 kVA and is now incorporated into in UPSs up to 1100 kVA.
Easy Capacity Test With Easy Capacity Test, Eatons UPSs (Eaton 9390 and Eaton 9395) are able to test their entire power train under a full load stress without an external load being connected. Because UPS uses its rectifiers and inverters as internal load banks and draws only minimal power (five per cent) from the mains supply, the energy consumption of the UPS testing is significantly reduced.
22
EATON CORPORATION
23
EATON CORPORATION
UPS Handbook
23
5. Scalability Its always important to consider your customers future expansion needs when evaluating a solution. Eatons scalable UPS solutions provide a competitive advantage by offering customers a cost-effective way to increase capacity. Virtually all Eaton UPSs with a 6 kVA or greater power rating offer some form of scalability, whether it be through a simple firmware upgrade, the addition of modular hardware components or the paralleling of multiple UPSs. For the cost-conscious or budget-constrained customer, a UPS with inherent scalability often proves to be the best value in the long run, allowing the customer to increase capacity without having to purchase additional hardware. A simple kVA upgrade is all thats needed to enable a UPS with inherent scalability to operate at full capacity. Customers who have internal IT or facilities staff and who service their own equipment may prefer to add capacity by purchasing additional modules that can be added in an expandable chassis or rack as their power load increases. While modular solutions - including multiple, paralleled systems - are often a more affordable option initially, they can be a more expensive solution in the long term due to additional hardware and installation costs. Depending on the customers specific needs, a larger, centralised, modular system might ultimately be the most cost-effective solution.
The customer was so pleased with the ability to remotely monitor his UPSs and reboot his servers - which eliminated his need to drive to the facility in the event of a power disturbance - that he purchased all the hardware he needed to obtain that functionality. By understanding his communication and control needs, Eaton was able to provide a complete solution. 8. Operation and maintenance While many customers value the ability to service their own equipment, the vast majority of IT and facility management professionals prefer the peace of mind that comes with full factory support through on-site service. Understanding a customers availability requirements and technical proficiency - along with his or her tolerance for risk - can further help reduce the number of viable product options as part of a consultative selling process. In addition, considering the products up-front costs in combination with Eatons service level agreements is an integral component of any sales process. While some IT professionals value the ability to independently swap modules or replace batteries within their products, others prefer a hands-off approach to power in their data centre. In addition, the type of installation (decentralised or centralised large UPS) may also influence the customers service preference. For those who want some level of service autonomy, small single-phase or rack-based equipment with userserviceable batteries and modules may be the ideal solution. Customers with smaller budgets and higher kVA ratings may prefer a low-cost, centralised, end-of-row solution supported by on-site factory support. Anticipating a customers budget and support needs leads you in the right direction during a consultative selling approach.
6. Power distribution It is imperative that you understand your customers power distribution scheme. Keep in mind that Eatons ePDUs and rack power modules, can be used with any UPS product. Just as software, communications and metering can often sell hardware, a well-conceived power distribution and metering scheme can directly address a customers needs and ultimately, sell the solution. In some instances, data centre managers want to more effectively monitor departmental usage of resources in order to better allocate overheads for the organisation. In deploying metering at the rack level, one Eaton customer was able to track each departments demand and allocate expenses based on meter readings. Combined with using the most efficient servers available, the ability to analyse peak hours of usage for computing processes enables an IT manager to further increase efficiency.
7. Manageability Eatons manageability software and accessories very often help to sell our hardware and can be the key to closing the sale. Eatons manageability tools should be introduced at every available opportunity in order to offer the customer a complete solution and help lower the total cost of ownership. As an example, one customer had expressed a need for 15 minutes of runtime in order to reach a remote facility he managed approximately 10 minutes away. Based on the salespersons ability to ascertain the real need, a network interface card for the rack-based UPS was recommended, along with remote management software that would enable the UPS to gracefully shut down applications in the event of an extended outage. ePDUs were also employed to deliver multiple levels of monitoring and control.
24
EATON CORPORATION
9. Budget Most customers indicate that redundancy, scalability, modularity and serviceability are all critical components in deciding which UPS to purchase. In turn, the majority of salespeople consider these factors to be critical components of their proposal. However, without first considering the customers budget, important tradeoff decisions cannot be considered and the proposal may be placed in a poor competitive position. Since the customer will be focused on numerous features, it is important for the salesperson to ask probing questions that comprehensively evaluate each item and consider its importance relative to its impact on the budget. By proposing multiple options and ranking the importance of each feature as part of a consultative approach, you build trust with the prospect by helping to determine the optimal solution from a value perspective. Another important budgetary factor that is often overlooked, is identifying the key decision maker within the company. Although a facilities professional or data centre manager may be a strong influence, identifying the decision maker can often make or break the deal. By ascertaining who will ultimately approve or allocate funds for the project, a salesperson gains the opportunity to ask additional questions. The ability to talk directly to the decision maker provides a chance to address his or her needs and capitalise on the opportunity to learn their main concerns and tailor a proposal that addresses those concerns. Failure to do so is a common cause of missed sales opportunities. By always taking into account a customers budget, you cover all bases and prevent the competition from offering a lower-cost alternative.
10. Expanding the opportunity Our broad portfolio of products and capabilities - including singleand three-phase UPSs, power distribution products, connectivity and manageability tools, and world-class service and support enables Eaton to fulfill all our customers power quality needs. When qualifying an opportunity, be sure to speak with all decision makers within the account, including the facility procurement manager and the IT procurement manager. Working with both contacts will help you to identify all potential opportunities to introduce Eaton power quality solutions. As a global provider of power quality infrastructure products and services that provide an industry-leading balance of reliability, energy efficiency and value, Eaton is uniquely positioned to help customers around the globe manage all elements of their power systems. By focusing on only one product or business segment, you miss the opportunity to offer the customer a complete solution and grow Eatons market share.
7. Installing small UPS models behind larger UPS models If you are installing a smaller UPS behind a larger UPS, you must consider the total potential power of the smaller UPS as well as other loads that will be powered by the larger UPS. For example, if you are plugging a 1500 VA UPS into a 10,000 VA UPS, you must consider the 1500 VA load of the smaller UPS rather than just the load that is plugged into it. In addition, the larger UPS must be at least five times larger than the smaller UPS. This design guideline must be followed due to charging capacity that may be required by the smaller UPS, any anomalies associated with the buildings power supply, and to avoid overheating or potential overloading of the larger UPS, which may result in failure of the all UPS units in the string. 8. Using a UPS and a generator together A UPS provides backup power and actively conditions and regulates voltage. Similar to a UPS, a generator provides backup power. However, auxiliary generators typically take 10-15 seconds to start up, depending upon generator type. For longterm backup servers and IT equipment, this is not an optimal situation, so during this time the UPS kicks in. Basically, the UPS bridges the power gap between loss of power and when the generator comes online. When designing your UPS solution, it is important to keep power ratings in mind; you cannot size a generator in a 1:1 match to the UPS and expect successful results. There are two reasons for this: firstly, UPSs arent 100 per cent efficient and secondly, generators need to account for step loads. In addition to accounting for step load, very small generators dont often provide enough kinetic energy to provide a smooth transition. As a rule of thumb, for 20 kVA and above the capacity of the auxiliary generators should be one-and-a-half times the size of the output rating of the UPS in kW, while for 20 kVA and below the capacity should be twice that of the UPS output rating in kW. It is also important to note that the capacity of gas-powered generators should be slightly larger still. 9. Verify that the final UPS solution meets local building codes The facility manager is often the best contact when seeking to understand local building codes.
25
Provides room for future capacity growth and avoids being locked into a specic UPS.
Existing smaller UPS units need not be discarded. (However, most manufacturers offer a trade-in scheme.)
Power conditioning is implemented at the point of use, which mitigates any electrical disturbances that may be coupled into the distribution wiring of centralised system.
Provides exibility in terms of power protection and functionality. For example, extended runtime can be congured for specic applications, eliminating the need to add additional battery modules for less critical equipment.
26
EATON CORPORATION
Disadvantages
A single UPS can mean a single point of failure. However you can overcome this concern with a N+1 or N+X UPS for redundancy. The single UPS may not be in close physical proximity to the equipment that it will protect. It is very likely that not all the equipment will be fed by a single electrical distribution panel. A centralised solution requires more space for a large UPS, which may not be available. Generally requires a trained service technician or electrician to install, service and maintain, which means additional costs.
A single UPS is easier to monitor, service and maintain than lots of smaller UPSs.
A larger UPS will be three-phase, which usually means more efcient operation and lower operating costs. A centralised UPS is often housed away from busy areas. As a result, it is less easily disrupted, accidentally damaged or maliciously interfered with. A centralised UPS can be located in an area where cooling is more tightly controlled. Remember, heat is the enemy of the batteries inside a UPS. Though a technician may need to replace the batteries, you only have to worry about a single UPS. A distributed UPS conguration may result in various models that require different batteries. Consider the time it takes to replace the batteries for between ve and 20 UPSs.
27
28
EATON CORPORATION
9. How are phone systems and IT equipment affected by inconsistent power? Fluctuating power is a waste of valuable time and money. If customers expose their telephone systems (and any other electronic equipment) to inconsistent utility power, they are vulnerable to hardware and software damage, data corruption and communication breakdown. The time and cost of replacing equipment, as well as the business lost during breakdown and replacement, can greatly affect a companys bottom line. 10. We have a generator - do we still need a UPS? Many customers do not realise that a generator will not protect their equipment against power problems. You need a UPS to guarantee that the equipment stays running until the generator kicks in, which often requires several minutes. In addition, UPSs also improve the quality of the power produced by generators. 11. How much UPS capacity do I need? Determine the total load (in watts) of the equipment you want to protect. Add 10-20 per cent to allow for future growth and decide the minimum amount of runtime you need. Use the online sizer at www.eaton.com/powerquality to identify the right solution for your application. 12. I already have surge protection. Why do I need a UPS? Surge protection will not keep your business and phones operational during a blackout. In addition, surge protectors do nothing to improve the quality of power feeding your sensitive and expensive IT & telecom equipment. Eaton UPSs provide reliable, clean power to your equipment at all times. Over time, poor quality power will degrade your equipment. 13. What happens if the UPS is overloaded? For example, if the protected equipment and/or load draws more current than the UPS can provide. The UPS transfers the load to bypass (for a few minutes) until the overload condition is reversed. If the overload condition continues, the UPS automatically shuts down.
29
14. What causes a UPS to become overloaded? There are two possible answers: (1) the UPS was undersized (e.g. the load was rated at 1200 VA but a 1000 VA UPS was provided), or (2) the customer plugged more equipment into the UPS than it was designed to handle. 15. Whats the difference between VA and watts? In order to correctly size a UPS, it is important to understand the relationship between watts and VA. However, we must first think about power terminology. Real power (measured in watts) is the proportion of power flow that results in the consumption of energy. The energy consumed is related to the resistance in an electrical circuit. An example of consumed energy is the filament in a light bulb. Reactive power (measured in VAR or volt-amps reactive) is the proportion of power flow resulting from stored energy. Stored energy is related to the presence of inductance and/or capacitance in an electrical circuit. An example of stored energy is a charged flash bulb in a camera. Apparent power (measured in VA or volt-amps) is a mathematical combination of real power and reactive power. The geometric relationship between apparent power, reactive power and real power is illustrated in the power triangle below:
18. What is the difference between a centralised and a decentralised UPS solution? In a centralised configuration, a larger UPS supports multiple loads from a single point. Centralised UPSs are often hardwired into an electrical panelboard. A decentralised configuration allows multiple UPSs to protect a handful of devices. Decentralised UPSs generally utilise plugs and receptacles for the input and output connections. 19. Why is power management software important? Although UPSs are typically rugged and reliable, they do require ongoing monitoring and support. Power management software continuously monitors and diagnoses the state of the grid, batteries and power sources, together with the condition of the UPS internal electronics. Eaton UPS software and connectivity cards enable remote monitoring and management capability, including graceful shutdown and load segment control. 20. Will my current UPS software monitor my new Eaton UPS? Most UPS and power management software support SNMP with the RFC-1628 MIB, which is available for many Eaton UPSs through an optional network card. Some more advanced monitoring systems such as OpenView, Tivoli and Nagios allow importing SNMP MIBs; this would allow you to use Eaton proprietary, which provide more information and a greater level of detail. On the other hand, Eaton network cards have a built-in web interface for viewing data and controlling the UPS as well as email capability for generating alarm without any additional software. 21. What is the difference between single-phase and threephase power? The AC electric power sent out from a power station is commonly three-phase. Single-phase power can be drawn from a connection across one of these lines and a neutral line. Virtually all PCs and small electronic devices use single-phase power. Higher power industrial motors or large air-conditioning systems often use three-phase power. 22. My data centre only went down for a couple of minutes. Whats the big deal? If the servers in a data centre are without power for a few minutes or even seconds it may actually mean hours or even days of downtime. A sudden uncontrolled power off is very likely to cause database and file system corruption. Starting up many services takes a long time because they have to repair their data and some may need to be restored from backup media. Some operating systems may have to be reinstalled completely. Many systems have to wait for other servers to boot up first so that they can get access to the many services required for their operation. 23. Where can I get technical help? Please visit www.eaton.com/powerquality
30
EATON CORPORATION
Communication Bay A communication bay or option slot on a UPS enables you to add various connectivity cards for Web, SNMP , Modbus or relay connectivity interface capabilities.
Converter A device that delivers DC power when energised by a DC source. It is also a section of a switching power supply that performs the actual power conversion and final rectification. Crest Factor Usually refers to current. It is the mathematical relationship between RMS current and peak current. A normal resistive load will have a crest factor of 1.4142, which is the normal relationship between peak and RMS current. A typical PC will have a crest factor of 3. Critical Equipment Equipment such as computers, communications systems or electronic process controls, whose continuous availability is imperative. Delta Connection A circuit formed by connecting three electrical devices in series to form a closed loop; most often used in three-phase connections. Derating A reduction of some operating parameters to compensate for a change in one or more other parameters. In power systems, the output power rating is generally reduced at elevated temperatures. Direct Current (DC) An electric current in which the flow of electrons is in one direction, such as the power supplied by a battery. DC Distribution (DCD) A module in a DC power system that distributes DC power to the loads. It also provides protection for the load cables. DC Power System An AC to DC power supply with integrated control and monitoring, and standby batteries designed to supply no-break DC power (usually 24 V or 48 V) to telecommunications and IT network equipment.
31
Double Conversion A UPS design in which the primary power path consists of a rectifier and inverter. Double-conversion isolates the output power from all input anomalies such as low voltage surges and frequency variations. Downtime The time during which a functional unit cannot be used because of a fault within the functional unit or within the environment. Dry Contact Dry contact refers to a contact of a relay which does not make or break a current. Efficiency The ratio of output power to input power. It is generally measured at full-load and nominal line conditions. If power efficiency of a device is 90per cent, you get back ninety watts for every hundred you put in. The rest is mainly dissipated as heat from the filtration process. Electrical Line Noise Radio frequency interference (RFI), electromagnetic interference (EMI) and other voltage or frequency disturbances. Electromagnetic Interference (EMI) Electrical interference that can cause equipment to work improperly. EMI can be separated into conducted EMI (interference conducted through cables out of the UPS) and radiated EMI (interference conducted through the air). ePDU A power distribution unit that mounts to rack enclosures and distributes power to connected devices via a wide variety of output receptacles. Flooded Battery A form of battery where the plates are completely immersed in a liquid electrolyte. Frequency The number of complete cycles of AC voltage which occurs during one second (Hz). In EMEA region, electrical current is supplied mainly at 50 Hz, or 50 cycles per second. Ground A conducting connection, whether intentional or accidental, by which an electric circuit or equipment is connected to the earth, or to some conducting body of relatively large extent that serves in place of the earth.
High Voltage Spike Rapid voltage peak up to 6,000 volts. Hot Swappable The ability to change a module without taking the critical load off the UPS. See also User Replaceable.
The batteries on this Eaton 9130 UPS are hot swappable.
IGBT Insulated gate bipolar transistor or IGBT is a three-terminal power semiconductor device, noted for high efficiency and fast switching. It switches electrical power in many modern applications such as electric cars, trains and UPSs. Impedance The total opposition to alternating current flow in an electrical circuit. Input Voltage Range The voltage range within which a UPS operates in normal mode and without requiring battery power. Inrush Current The maximum, instantaneous input current drawn by an electrical device when first turned on. Some electrical devices draw several times their normal full-load current when first energised. Inverter UPS assembly that converts internal DC power to output AC power to run the users equipment. When the inverter is supporting 100per cent of the load at all times, as with an online UPS, there is no break from utility power to battery power. Kilovolt Ampere (kVA) One thousand volt-amperes. Common measurement of equipment capacity. An approximation of available power in an AC system that does not take the power factor into account. Kinetic Energy The energy an object possesses because of its motion. Linear Load AC electrical loads where the voltage and current waveforms are sinusoidal. The current at any time is proportional to the voltage. Line Conditioner A device intended to improve the quality of the power that is delivered to electrical load equipment. A line conditioner is generally designed to improve power quality (e.g. proper voltage level, noise suppression, transient impulse protection, etc.). Line Interactive An offline UPS topology in which the system interacts with the utility line in order to regulate the power to the load. Provides better protection than a standby system but is not as fully prepared against irregularities as a full double-conversion system. Load The equipment connected to and protected by a UPS.
Harmonics A sinusoidal component of an AC voltage that a multiple of the fundamental waveform frequency. Certain harmonic patterns may cause equipment problems. Harmonic Distortion Regularly appearing distortion of the sine wave whose frequency is a multiple of the fundamental frequency. Converts the normal sine wave into a complex waveform. Hertz (Hz) A unit of frequency equal to one cycle per second. High Efficiency Mode A mode of UPS operation that cuts energy usage and operating costs.
32
EATON CORPORATION
90
180
270
360
Sine Wave
Parallel Operation The ability of UPSs to be connected so that the current from corresponding outputs can be combined into a single load. 90 180 270 360
This Eaton 9130 UPS is equipped with two load segments, each with three 5-15R
Peak Demand The highest 15- or 30-minute demand recorded during a 12-month period. Phase Time relationship between current and voltage in AC circuits. Plug and Play An electrical device that does not require extensive setup to operate. Power Factor (PF) The ratio of real power to apparent power. Watts divided by VA. Most power supplies used in communication and computer equipment have a power factor of 0.9. (PF = 0.9) VA x PF = W Power Sag Low voltage. Power Surge High voltage. Pulse Width Modulation (PWM) A circuit used in switching regulated power supplies where the switching frequency is held constant and the width of the power pulse is varied, controlling both lines and load changes with minimal dissipation. Rackmount Ability to mount an electrical assembly into a standardised rack. Rack Unit (U) A unit of height measurement in a rack enclosure. A U is equivalent to 1.75 inches. W/PF = VA
Maintenance Bypass An external wiring path to which the load can be transferred in order to upgrade or perform service on the UPS without powering down the load. Make Before Break Operational sequence of a switch or relay where the new connection is made prior to disconnecting the existing connection, also known as soft-load-transfer switching. Modbus Modbus is a serial communications protocol which is now the most commonly available means of connecting industrial electronic devices. Modbus allows for communication between many devices connected to the same network. Network Transient Protector UPS feature that isolates networks, modems and cables from power threats including surges and spikes. Noise Disturbance that affects a signal; it can distort the information carried by the signal. (2) Random variations of one or more characteristics of any entity such as voltage, current or data. Nominal Output Voltage The intended, ideal voltage of any given output. Non-linear Load AC electrical loads where the current is not proportional to the voltage. Non-linear loads often generate harmonics in the current waveform, which leads to distortion of the voltage waveform. Offline Any UPS that does not fit the definition of online. Lineinteractive and standby topologies are offline. Ohm The unit of measurement for electrical resistance or opposition to current flow. Online A UPS that provides power to the load from its inverter 100 per cent of the time, regulating both voltage and frequency, usually double-conversion topology. Orderly Shutdown The sequenced shutdown of units comprising a computer system to prevent damage to the system and subsequent corruption or loss of data.
The Eaton 5130 UPS occupies 2U of rack space and the optional extended battery module also occupies 2U.
33
Rail Kit A set of metal brackets that allow you install a UPS or extended battery module in a 2- or 4-post rack.
Thermal Regulation Monitoring the temperature of the batteries to assure proper charging. Three Phase Power supplied through at least three wires, each carrying power from a common generator but offset in its cycle from the other two. Used for heavy-duty applications. Topology (UPS) The core technology of a UPS. Typically, a UPS is either standby, line interactive or online though other hybrid technologies have been introduced. Total Harmonic Distortion (THD) The amount by which the circuit voltage deviates from a perfect sine wave. When viewed on a meter, a poor voltage THD is most often manifested in a flat topped waveform that comes from the inability of a power source to respond to the demands of highly non-linear loads. Transfer Time The length of time it takes a UPS to transfer to battery power. Typically measured in milliseconds (ms). Transient A temporary and brief change in a given parameter. Typically associated with input voltage or output loading parameters. Unbalanced Load An AC power system using more that two wires, where the current is not equal in the current-carrying wires due to an uneven loading of the phases. Uninterruptible Power System (UPS) An electrical system designed to provide instant, transientfree back up power during power failure or fault. Some UPSs also filter and/or regulate utility power (line conditioning). Universal Serial Bus (USB) The current communication standard used in computers to connect a wide variety of peripherals. It has widely replaced traditional serial and parallel connections. User Replaceable Capable of being replaced by an end user. Connected equipment may need to be shut down first. See also Hot Swappable. Virtualisation The creation of a virtual (rather than actual) version of something, such as an operating system, server, storage device or network resource. Operating system Virtualisation is the use of software to allow a piece of hardware to run multiple operating system images at the same time. Volt/Voltage (V) Electrical pressure that pushes current through a circuit. High voltage in a computer circuit is represented by 1; low (or zero) voltage is represented by 0. Volt Amps (VA) The voltage applied to a given piece of equipment, multiplied by the current it draws. Not to be confused with Watts, which are similar but represent the actual power drawn by the equipment, and can be somewhat lower than the VA rating. Watts (W) The measure of real power. It is the rate of doing electrical work. W/PF = VA. Wye Connection A connection of three components made in such a manner that one end of each component is connected. Generally used to connect devices to a three-phase power system.
Rectifier UPS component that converts incoming AC power to DC power for feeding the inverter and for charging the battery. Rectifier Magazine (RM) A module in the DC power system used to connect the rectifiers in the power system. Redundancy The ability to connect units in parallel so that if one fails the other(s) will provide continual power to the load. This mode is used in systems where power failure cannot be tolerated. Relay Communication Communication between a UPS and a computer through the opening and closing of solid-state relays that are predefined to indicate UPS status. RS-232 The standard for serial interfaces (serial refers to the eight bits of each character successively sent down one wire) traditionally used by computers, modems and printers. Largely superseded by USB. Sine Wave Mathematical function that plots three qualities of an electrical signal over time: amplitude, frequency and phase. Clean, uninterrupted power is represented by a sine wave. Single Phase Power system with one primary waveform. Lower-capacity distribution of power using only one portion of a power source that is three-phase, such as that supplied by most household mains electrical supplies. Used for heating and lighting, no large motors or other heavy-drain devices. Sliding Demand Calculating average demand by averaging the average demand over several successive time intervals, advancing one interval at a time. SNMP Simple Network Management Protocol is a User Datagram Protocol (UDP)-based network protocol. It is used mostly in network management systems to monitor network-attached devices for conditions that warrant administrative attention. Standby UPS type that stands by, waiting for a power problem from the utility company and rapidly switching to UPS battery power to protect equipment against power failures, sags and surges. Step Load An instantaneous change in the loading conditions presented to the output of a UPS. Switching Frequency The rate at which the source voltage is switched in a switching regulator or chopped in a DC to DC converter. System i Server One of a family of general-purpose systems that supports IBM i5/OS and Operating System 400 and which provides application portability across all models.
34
EATON CORPORATION
Eaton acronyms
35
www.eaton.com/powerquality
Eaton, Powerware, ABM, BladeUPS, ePDU, HotSync, Intelligent Power are trade names, trademarks, and/or service marks of Eaton Corporation or its subsidiaries and affiliates. 2010 Eaton Corporation. All Rights Reserved. December 2010 - 00BROC1018174 revA eaton.com/powerquality