Ocb CSN
Ocb CSN
Ocb CSN
CSN MANAGEMENT
1.1 Introduction
Handling OM faults is a centralized function which can be broken down into three
main activities:
- edition after faults have been filtered.
- attribution of penalties in functional components and statistical calculation
so as to identify these components.
Taken in isolation, a fault does not mean that the component is not function
properly. A fault is indicated by a spontaneous message emitted by a component
on behalf of the OM.
Message editing
FAULT
BM entry
MESSAGES PROCESSING
memorization
OF
Component diagnosis
FAULTS
SUPERVISION listing
inhibition
BASIC PRINCIPLE
1
1.3 Structure of fault messages
GRAVITY
SUB GROUP
EMITTING UNIT
CN NUMBER
2
(1) Sending context : one or more subscribers can no longer telephone.
3
1.4 Some Typical CSN fault messages:
Given below are some of the examples of fault messages related to the CSN.
(1) Sending context : traffic handling is not disrupted and all subscribers
can still telephone
ENS >
S/ENS > are used to send the diagnostic
P >
(2) Source : CSE – CSN.
(3) Probable cause : UR hardware fault . The fault message is the subject
of a diagnostic sent and output on the terminal assigned to this
purpose.
(4) Action required : Analysis of the diagnostic output on the dedicated
terminal and repair. Receipt of this message at the OMC initiates an
alarm.
4
1.4.3 T11 – F13 ODDQS : QUALITY OF SERVICE FAILURE
5
The action to be taken are specific to each alarm.
An alarm is dealt with by capturing the alarm, analyzing it and taking
specific action,
Message editing
(disk recording)
PROCESSING
event Storage
OF
Identification component
Start, end ALARMS
continue Display on PGS
Tele-maintenance network
6
1.5.2 OVERVIEW OF ALARM PROCESSING
MIC
CNE ICNE TS 16
``````````````` UCN LR
SMX
LR1
Infrastructure CNL
COC
LR
SMT
TS 16
C C
CSND S M C
COC A A
S
L S A
Infrastructure L
TS 16
LR
CSED CMAS
SMA
Infrastructure C C
M
S A
M A S
MAS
A L
L
SMC CMAS
C MLMQ
S
A
L
CMIS
C
Infrastructure S
A MIS
L
C C SMM
S S CMIS
A A
Remote Control L L EL
LCC IAS
SSE
N
NAT TRAIT M
ALA
C LCT T
S EL
AC
A Q
L TRAIT
MLOC
ACTUJ
NMC
TI-PGS CV or TY
7
1.5.3 Description of Alarm message
ADDITIONAL INFORMATION
ALARM TEXT
THRESHOLD
EFFICIENCY
8
1.5.4 Some CSN related Alarm messages.
Examples of some of the CSN related Alarm messages are given below. The
same be consulted by seeing the Fault and Alarm Dictionary (2-4-1) .
1.5.6 * A 005 - Ex % TS – LR
Action required :
(1) Make sure that there is no LOCAVAR test in progress.
(2) Initiate TELIN with AFUR, AFLR and AFVT.
(3) Try to put these TS – LR into service by means of TELEMO.
(4) If this attempt fails, run LOCAVAR for the relevant PCM module
(CSED).
9
1.5.7 * A 005 - Ex % TS – LRI
- AF : Functional address of one or more logic unit. (MR, TR, TX, GX,
GS, PC, ETA, PUPE, URM), etc.
10
The “SM HS” alarm is indicated.
BLOS Blocked by the system The SM is under system control and will
handle only positioning messages. This state
is transitional and precedes SM initialization
or execution of the LOCAVAR test.
ES In service The SM is operational.
INDL Unavailable free The SM has been set to the INDL state by
operator command and is not currently
processing. The SM is under operator control
.The “SM HS” alarm is indicated.
INDO Unavailable busy An INDL state positioning request has been
made by operator command. The SM alarm
is indicated.
INIT Initializing An INDL state positioning request has been
made by operator command. The initializing
procedure (loading data then initializing) with
progress. The initializing phase is controlled
by the system
NEQ Not equipped The “SM ” not implemented..
TEST Being tested LOCAVAR tests, triggered automatically or
by operator command are currently running.
The command used for modifying the SM Status is ESMMO .The parameters of
this command are :
When turning off a station the operator must make sure not to disturb the routines
in progress.
11
1.6.2.1 Transition from ES to INDL
The logical machines carried by the station align their operating mode on this
new status. They see that they are INDO, free themselves of the routines in
progress and inform the MLSM. When all the MLs have gone to INDL, the
station itself becomes INDL and informs the SMM.
Comment : If this positioning involves the disappearance of the PC function or of
an MLPUPE without backup the command is refused by the SMM.
In the INDL state, the station maintains all its previously loaded functions.
The station is blocked, the operator after seeing the editing of the positioning
report can act on the equipment and carry out a test if required.
This transition form necessarily involves initializing the station and hence testing
it by a LOCAVAR launched by the system.
- AFLR : UR – LR
(1 < 223) – (0 < 15)
12
UR – CN – LRI
(1 < 223 ) – (0 < 20) – (0 < 3)
The possible output status can be ES, INDL,BLOS,
BLOM,BLOF, TEST, INIT, NAC, NEQ
The TELINB command is used to check the status of the logic depending upon
what criterion is given as a parameter.
The TELBSC command is used to modify telephone equipment status and switch
the Signaling Links. The parameters for this command are
The TELEMO command is used to change the state of the Connection Unit . The
various possible parameters for this command are
- AFLR :UR – LR
(1 < 223) – (0 < 15)
13
1.10 LOCAVAR
1.10.1 Introduction
LOCAVAR is a software that is loaded and run by a station for the purpose of
locating malfunctioning boards. No LOCAVAR is resident at the station level
except for the CSN case.
The diagnostics can be initiated by man machine command or
automatically by system .The auto diagnostic reports are output on a terminal
assigned to logical file OPMN . This programme takes care of hardware faults
only .If there is a hard fault then this unit is positioned to BLOS status. In the
diagnostic result PCBs are accused . For SM stations the PCB accused is replaced
by a good one and a diagnostic is run by man machine command to check
whether ‘ NO DIAGNOSTIC ‘ result comes .
Normally locavar is not run by man machine command as a routine
maintenance procedure. But if there is a diagnostic found by automatic reaction
then only manual locavar is run to repair the same.
In case of a CSN LOCAVR can be run on
- the standby control logic
- a sub – assembly of the electronic access unit such as:
- A PCM Module
- Subscriber Terminal Units
- Ancillary equipment : test equipment ,etc.
For the testing of CSN each logic has to be tested separately. LOCAVAR can be
run only on the standby logic but it has to be made out of service first . The
command used is TELBSC with status of the reserve unit as BLOM . Next give
the testing command URTL with parameter as :
The output will give NO DIAGNOSTIC if no fault is there .Make the sub-system
in service condition .However for a faulty hardware an output will be given ,
stating the diagnostic code , diagnostic number ,CN number and the slot number.
14
1.10.3 Testing of PCM Interface
First set the LR link concerned to INDL and then to BLOM using the TELEMO
command . Next run the LOCAVAR on the PCM interface by giving URTL with
parameters as :
With the same URTL command all the cards of a particular CONCENTRATOR
(CN) can be tested . The parameters are :
With URTL command individual Terminal units can also be tested .The
parameters to be given are :
15
1.10.6 Confirming the repair of UR , CN or UT
Depending on the component to which the diagnostic report applies , prior setting
may be required . Run the LOCAVAR test to confirm the repair using the URTR
command with parameters as :
Analyze the result of the LOCAVAR Test as per the conditions stated below :
IF THEN
(i) Repair OK. For a CSN or CN the diagnostic report is
deleted.
(ii) Diagnostic maintained is The fault remains .
outputted.
(iii) A new diagnostic report A new fault has occurred . The diagnostic
is outputted. Report indicates which new board may be at
the root of the fault.
(iv) An error message is The message indicates why the test has failed.
outputted.
16
CHAPTER – 2
VRLA BATTERIES
2.0 MAINTENANCE – FREE SECONDARY CELLS (VRLA)
17
to the negative plate. The oxygen gas gets reduced by reaction with the spongy
lead at the negative plate, turning a part of it into a partially discharged condition,
thereby effectively suppressing the hydrogen gas evolution at the negative plate.
This is what is known as the oxygen recombination principle. The part of negative
plate which was partially discharged is then reverted to the original spongy lead
by subsequent charging. Thus, a negative plate keeps equilibrium between the
amount which turns into spongy lead by charging and the amount of spongy lead
which turns into lead sulphate by absorbing the oxygen gas generated at the
positive plate. The oxygen recombination principle can be shown by the following
reaction :
1. Reaction at positive plate :
H2O = ½ O2 + 2e– … (1)
To reaction (2)
3. The total reaction at negative plate
½O2 +2H+ = H2O
Thus, the recombination technology makes the battery virtually Maintenance Fee.
18
(ii) Float charging current at : Maximum current to be limited to 20% of the
2.25 V/cell rated AH
5. Recommended Boost charging : 2.30 V/Cell
condition for quick charging at
27oC
6. Internal resistance of the cell : 0.257 milli ohms
7. Life Expectancy of the Battery : 4000 Cycles at 20% Depth of Discharge or
20 years under Float condition
8. Containers :
(i) Material : Polypropylene (Spl. Grade)
(ii) Thickness of wall : 2.3 mm (Approx.)
Container and cover - Polypropylene Co-polymer housed in a steel
tray
Separator - Spun glass microporous matrix
Safety valve - Explosion proof, pressure-regulating and
self-resealing type
Positive plate - Patented MFX alloy
Negative plate - Lead Calcium allow
Terminal - Integral lead terminal with solid copper core
Self discharge - Less than 0.5% per week
Charging - Current limited, constant potential
Float charge - 2.25 VPC at 27oC with a max. current limit
of 20% of
rated capacity in amperes
Boost charge - 2.30 VPC at 27oC with a max. current limit
of 20%
of rated capacity in amperes
Connectors - Heavy-duty, lead plated copper connectors
Life expectancy - Float service at 27oC – upto 20 years
- Cycle duty at 27oC – 80% DOD – 1200
Cycles
- Cycle duty at 27oC – 20% DOD – 4000
Cycles
19
Fig. Power Stack Cell – Cut Section
General
Batteries lose some charge during as well as during the period prior to installation.
A battery should be installed and given a freshening charge after receipt as soon
as possible. Battery positive (+) terminal should be connected to charge positive
(+) terminal and battery negative (-) terminal to charger negative (-) terminal.
20
Table – B
2.25 30 hrs
2.30 12 hrs
Note : Time periods listed in Table B are for temperatures from 15oC to 40oC. For
temperatures below 15oC double the number of hours.
Raise the voltage to the maximum value not exceeding 2.37 volts per cell
permitted by the system equipment. When charging current has tapered and
stabilized (no further reduction for three hours), charge for the hours shown in the
above table or until the lowest cell voltage ceases to rise. Correct charge time for
the temperature at the time of stabilization. To determine lowest cell, monitoring
should be performed during the final 10% of the charge time.
2.4 Operation
2.4.1 General
All POWER STACK batteries are rated to an end cell voltage of 1.75 VPC
at all rates of discharge.
21
Modern constant voltage output charging equipment is recommended for
the floating charger method of operation of batteries. This type of charger,
properly adjusted to the recommended float voltage and following recommended
surveillance procedures, will assist in obtaining consistent serviceability and
optimum life. The charging current for the battery should be limited to 20% of its
nominal AH capacity.
After the battery has been given its freshening charge (refer to section 4),
the charger should be adjusted to provide the recommended float voltage at the
battery terminals.
Do not use float voltage lower or higher than those recommended. This
will result in reduced capacity and/or reduced battery life.
Check and record battery terminal voltage monthly. See Section 8,
RECORDS Item B. If normal battery float voltage is above or below the
recommended value adjust charger to provide proper voltage as measured at the
battery terminals.
2.4.5 Recharge
All batteries should be recharged as soon as possible following a discharge
with constant voltage chargers.
22
2.4.7 Temperature of the Cell
The temperature of the POWER STACK cells cannot be measured during
operation. However, cell temperatures are normally within +5oC of the ambient.
All performance characteristics are measured at ambient temperature and
corrected to 27oC.
2.5.1 General
Under normal operating conditions an equalizing charge is not required.
An equalizing charge is a special charge given to a battery when non-uniformity
in voltage has developed between cells. It is given to restore all cells to a fully
charged condition. Use a charging voltage higher than the normal float voltage
and for a specified number of hours, as determined by the voltage used.
Non-uniformity of cells may result from low float voltage due to improper
adjustment of the charger or a panel voltmeter which reads an incorrect (higher)
output voltage. Also, variations in cell temperatures greater than 3oC in the string
at a given time due to environmental conditions or module arrangement, can
cause low cells.
23
Note : Time periods listed in Table C are for ambient temperatures from 15oC to 40oC.
For temperatures less than 15oC double the number of hours.
Raise the voltage to the maximum value permitted by the system
equipment or recommended equalising charge voltage whichever is lower. When
charging current has tapered and stabilized (no further reduction for three hours).
Continue charging for the hours shown in Table C until the lowest cell voltage
ceases to rise. Monitoring of cell voltages should be started during the final 10%
of the applicable time period to determine lowest cell voltage in the battery
system.
2.7 Records
A complete recorded history of the battery operation is most desirable and
helpful in obtaining satisfactory performance. Good records will also show when
corrective action may be required to eliminate possible charging, maintenance or
environmental problems.
The following surveillance data must be read and permanently recorded
for review by supervisory personnel so that any necessary remedial action is
taken.
(A) Upon completion of the freshening charge and with the battery on float
charge at the proper voltage for one week, read and record the following :
(1) Individual cell voltage
(2) Battery terminal voltage
(3) Ambient temperature
(B) Every 3 months, a complete set of readings as specified in paragraph A
above must be recorded.
(C) Whenever the battery is given an equalizing charge, an additional set of
readings should be taken and recorded as specified in paragraph A above.
The suggested frequency of record taking is the absolute minimum to
protect warranty. For system protection and to suit local conditions or
requirements, more frequent readings may be desirable.
24
2.8 Temporary Non-use
As installed battery that is expected to stand idle for over 6 months should
be treated as follows.
Give the battery an equalizing charge as per section 6. Following the
equalizing charge, open connections at the battery terminals to remove charge and
load from the battery.
Every six months, temporarily connect battery to charger and give it an
equalizing charge.
To return the battery to normal service, re-connect the battery to the
charger and load, give an equalizing charge and return the battery to float
operation.
CAUTION
Do not clean plastic parts with solvents, detergents, oils,
mineral spirits or spray-type cleaners as these may cause
crazing or cracking of the plastic materials.
25
flooded batteries, the specific gravity of the electrolyte gives a fairly good
indication of the state of charge of the battery. However, in a VRLA battery, it is
not possible to measure the specific gravity of the electrolyte since it is
completely absorbed in the spun glass microporous separator.
The terminal voltage of the battery is directly related to the concentration
of the electrolyte. Therefore, if one were to measure the open circuit voltage of
the battery, the state of charge can be determined. The Open Circuit Voltage
(OCV) readings should be taken 24 hrs. after charging is discontinued. The OCV
value is co-related to the state of charge of VRLA batteries as per the table
enclosed.
Sometimes, it may not possible to disconnect the batteries from service for
24 hrs. and then check the OCVs. Then the pattern of charging current delivered
by a temperature compensated voltage – regulated charger after a discharge
provides the alternate method for determining the full state of charge. The
temperature compensation factor is –3 mV per cell oC rise from ambient
temperature of 27oC.
Under normal conditions the batteries are floated at around 2.25 volts per
cell, i.e. in a DOT System 24 cells are floated at 53.5 volts. During charging as
the cells approach full charge, the battery voltage rises to approach the charger
output voltage, i.e. 53.5 volts and the charging current decreases to the float
current value of around 50 mA/100 AH for VRLA batteries. So, when the
charging current has stabilised at the float current for three consecutive hours or
the voltage across the battery bank terminals is constant for six consecutive hours,
then the battery bank can be considered as having reached full state of charge.
If the charging voltage has been set at a value higher (but equal to or less
than 2.30 VPC) than normal float voltage (so as to reduce charging time), it is
normal practice to reduce the charging voltage to the float value of 2.25V after 12
hrs. Then the float current will soon stabilize and the above methods can be
adopted for determining the state of charge.
Table
% State of Charge Open Circuit Voltage
100 2.15
90 2.13
80 2.11
70 2.09
60 2.07
50 2.05
40 2.03
30 2.01
20 1.97
0 1.95
26
2.12 Different Methods of Working a Battery
The secondary batteries can be utilised in any of the following ways :
In this system the electrical energy derived from the supply mains is first
converted into chemical energy and stored in the battery. Subsequently the
chemical energy is reconverted into electrical energy when the battery discharges
into the exchange load. In the charge discharge system the entire DC supply for
the equipment is taken from the battery.
2.12.2 Standby battery system :
In this system, the DC electrical energy for the operation of the equipment
is drawn directly from the public AC power supply system through mains
conversion equipment and the standby battery is kept fully charged and idle, i.e.
not connected to the load. Whenever there is mains failure the equipment load is
immediately transferred from the mains conversion equipment to the standby
battery.
27
Fig. Standby Battery System
28
Fig. Batteries worked on Float
(i) Divided battery float system – Batteries floated between 2.02 to 2.07 volts
per cell.
(ii) Parallel battery float system – Batteries floated between 2.15 to 2.20 volts
per cell.
(iii) End cell switching system – Batteries floated between 2.24 to 2.30 volt per
cell.
29
(ii) The 24 cell scheme (battery floated at 2.15 to 2.20 volts per cell) or
parallel battery float scheme.
The 24 cell float scheme or parallel battery float scheme has now been
prescribed as the standard method of supplying power to telephone exchanges. It
is also adopted for 60V plus and minus supply in Telegraph Offices and Telex
Exchanges. In this scheme the battery voltage is maintained within very close
limits (51.5+0.5). The required battery capacity (ordinarily for 6 to 8 busy hours)
is provided equally in two sets of batteries (of 24 cell each for 50 volt exchange)
to facilitate maintenance attention to any one battery set. Both the battery sets are
floated in parallel simultaneously.
As the floating voltage 2.15 per cell is within the trickle charging range, a
steady trickle change current flows and recoups all capacity losses due to local
action, partial discharge on peak loads etc. incurred during the floating periods.
Thus the floated battery is maintained at its full capacity which is available as
reserve for mains failure conditions. Refresher charges at three monthly intervals
and yearly reconditioning cycle are given to the battery to ensure that two battery
is kept in a healthy condition under mains failure conditions. The battery voltage
drops down to 48 volts for 24 cells and the lower operating voltage of exchanges
is limited to 46 volts thus the end point for the discharge of the cells has to be
limited to 1.92 volt per cell. Thus, only about 52% of the rated capacity of the cell
is available for use. Therefore, higher capacity batteries are required.
Alternatively, an end cell switching capacity scheme whereby three cells are
switched in series with the battery when it discharges under mains failure
conditions can also be adopted. It is also adopted for 60V plus and minus supply
in Telegraph offices and Telex Exchanges.
30
(iii) The 23 cells scheme (battery floated at 2.24 to 2.30 volts per cell) or end
cell switching
The system is commonly called end cell system. In this a battery of 23
cells is floated at 2.24V per cell. The floating voltage is high enough to ensure
that the battery is always kept in a fully charged state. Batteries worked on this
float system do not require any refresher charges or yearly reconditioning cycles.
Under mains failure conditions, the battery voltage drops down to 48 volts as with
23 cells. As the limit of operating voltage is reached, the capacity of the battery
cannot be utilised, so three additional cells known as end cells are necessary to be
brought in series with the battery to bring up the voltage. A separate trickle charge
is required to keep the end cells in a fully charged state.
31
Each section can be separately connected to the battery charger without being
disconnected from the main battery.
2.13.1 General
All POWER STACK batteries are rated to an end cell voltage of 1.75 VPC at all
rates of discharge.
32
supply normal connected load where applicable. This sustains the battery in a
fully charged condition and also makes it available to resume the emergency
power requirements in the event of an AC power interruption or charger failure.
Given below are the float and boost voltage recommended for the POWER
STACK battery system. The average “Volts per cell” (VPC) value of the series
string should be set to the recommended voltage under Float and Boost
conditions.
o
RECOMMENDED FLOAT VOLTAGE 2.25 VPC AT 27 C
o
RECOMMENDED BOOST VOLTAGE 2.30 VPC AT 27 C
Modern constant voltage output charging equipment is recommended for
the floating charger method of operation of batteries. This type of charger,
properly adjusted to the recommended float voltage and following recommended
surveillance procedures, will assist in obtaining consistent serviceability and
optimum life. The charging current for the battery should be limited to 20% of its
nominal AH capacity.
After the battery has been given its freshening charge (refer to section 4),
the charger should be adjusted to provide the recommended float voltage at the
battery terminals.
Do not use float voltage lower or higher than those recommended. This
will result in reduced capacity and/or reduced battery life.
Check and record battery terminal voltage monthly. See Section 8,
RECORDS Item B. If normal battery float voltage is above or below the
recommended value adjust charger to provide proper voltage as measured at the
battery terminals.
33
finally stabilize when the battery becomes fully charged, if the normal connected
load is constant (no emergency load connected). The state when the current level
remains constant, after it has started decreasing, for three consecutive hours
would indicate full state of charge condition and the battery will be ready for
normal use.
If the normal connected load is variable (e.g. Telecom application) the
state when the voltage across the battery terminals is stable for six consecutive
hours would indicate full state of charge condition and the battery is ready for
normal use.
2.13.8.1 General
Under normal operating conditions an equalizing charge is not required.
An equalizing charge is a special charge given to a battery when non-uniformity
in voltage has developed between cells. It is given to restore all cells to a fully
charged condition. Use a charging voltage higher than the normal float voltage
and for a specified number of hours, as determined by the voltage used.
Non-uniformity of cells may result from low float voltage due to improper
adjustment of the charger or a panel voltmeter which reads an incorrect (higher)
o
output voltage. Also, variations in cell temperatures greater than 3 C in the string
at a given time due to environmental conditions or module arrangement, can
cause low cells.
34
2.13.8.3 Equalizing Charge Method
Constant Voltage charging is the method for giving an equalizing charge.
Determine the maximum voltage that may be applied to the system. This voltage,
divided by the number of cells connected in series, will establish the maximum
volts per cell that may be used to perform the equalizing charge in the shortest
period of time. Refer to Table-C for voltage and recommended time periods.
Table-C
Temp Cell volts Time
<15° C 2.30 30 hrs
15-32° C 2.30 20 hrs
>32° C 2.30 12 hrs
Raise the voltage to the maximum value permitted by the system
equipment or recommended equalizing charge voltage whichever is lower. When
charging current has tapered and stabilized (no further reduction for three hours).
Continue charging for the hours shown in Table C until the lowest cell voltage
ceases to rise. Monitoring of cell voltages should be started during the final 10%
of the applicable time period to determine lowest cell voltage in the battery
system.
2.15 Records
A complete recorded history of the battery operation is most desirable and
helpful in obtaining satisfactory performance. Good records will also show when
corrective action may be required to eliminate possible charging, maintenance or
environmental problems.
The following surveillance data must be read and permanently recorded
for review by supervisory personnel for any necessary remedial action .
(A) Upon completion of the freshening charge and with the battery on float
charge at the proper voltage for one week, read and record the following :
(1) Individual cell voltage
35
(2) Battery terminal voltage
(3) Ambient temperature
(B) Every 3 months, a complete set of readings as specified in paragraph A above
must be recorded.
(C) Whenever the battery is given an equalizing charge, an additional set of
readings should be taken and recorded as specified in paragraph A above.
36
Chapter – 3
SMPS
Necessity
The SMPS regulators are used in B.S.N.L at various locations like CDOT,
E10B Transmission systems etc.
37
For example
If I/P voltage is 200 volts and D=0.25
O/P voltage = 200 x 0.25 = 50V.
Regulation is achieved by modifying the Duty cycle. Duty cycle depends on
onetime of transistor, which in turn depends on the width of the pulse
applied to the base of the transistor, which is controlled by ‘Pulse width
modulation’ by regulator circuit.
38
For maximum efficiency the duty cycle should be less than 0.5. As long as
the triangular voltage exceeds the reference voltage, the output is high. Since Vref
is adjustable, we can vary the width of the output pulse and hence the duty cycle.
Switching regulators are more efficient than conventional regulators as the power
loss in the switching element is reduced to minimum as it conducts only for a
fraction of a cycle.
Now a days SMPS technology is extended to power plants also. Power plants upto
2000A capacity have been developed using SMPS principle.
3.5 50V – 2000A POWER PLANT (Multi Rack Type) Suitable for VRLA Batteries with 100A SMPS
Rectifier
39
connected in parallel. The system employ natural convection cooling and has AC
input distribution, DC output distribution, protection and alarm circuitry for
rectifiers, battery and equipment.
Technical Specification For Module
Input Voltage : (a) 320V to 480V r m s three phase (Nominal Voltage – 400V).
(b) Frequency : 45 Hz …. 65 Hz.
Output Voltage : Float mode : Nominal voltage : -54.0 + 0.5V, Adjustment
range : -48.0 to –56.0 V Charge mode Voltage : -55.2 + 0.5 V
Psophometric noise :
Less than 4 mV without battery floated.
Less than 2 mV with battery floated.
Efficiency :
Greater than 90% at full Load and nominal input.
Protection :
(a) Short circuit protection.
(b) Input over/under voltage protection.
(c) Output over voltage protection.
(d) Constant current features settable from 80 Amps. To 110 Amps. In auto
float/charge mode.
Input Voltage :
(a) 3 Phase, 4 Wire, 50 Hz (Range – 320V to 480V RMS)
(b) Frequency : 45 Hz …. 65 Hz.
Output Voltage :
Float mode Voltage : -54.0 + 0.5V
Charge mode Voltage : -55.2 + 0.5V
Rated Current :
40
Equipment : 1100 Amps.
Batteries : 300 Amps. Each
Protection
(a) Short circuit/Over load protection.
(b) Input over/under voltage protection.
(c) Battery/Equipment over voltage protection.
3.6.1 Rack :
The rack is made of mild steel profiles with hinged front door. The door
accommodates display and alarm enunciator. The rack is convection cooled and
has ventilator slots in the front and sides. The rear panel is screw type and can
be dismantled. The cabinet accommodates 19” subsystems. Air baffles are
provided for better heat transfer. Depending upon the load requirement
(Equipment and Batteries), additional modules can be added. The bottom and
top also have ventilator features. The DC power termination and distribution is
done at the top. The AC power termination and distribution is done at the bottom.
41
3.6.2 AC Distribution Panel :
The AC input to the rack is terminated at the bottom of the rack on screw
type terminals. Individual AC circuit breakers are provided for each module. The
line, neutral and earthing cabinet are terminated on moulded plug which is fixed
to the respective sockets on the rectifier module. To monitor AC input current, 3
nos. of single phase AC current transformers are mounted on the panel of main
rack. A small signal transformer is mounted on the PSC panel to provide AC
input to power system controller card.
3.6.3 Rectifier module : The SMPS rectifier module – 50V, 5600 watts works on
400V AC input and provides – 50V DC for system. The input is through 9 pin AC
socket and the DC output is through terminals. The module has front panel to
indicate status and faults in the module. The control signal is taken through 8 pin
telephone jack and is terminated on to the power system controller card. The
rectifier modules are convection cooled and can be jacked in and out of the cabinet
easily. The DC output from each module is terminated on the respective DC bus
bar mounted on the DC distribution panel.
3.6.4 DC Distribution Panel : This panel is mounted at the top of the cabinet. The
panel incorporates the following : (1) Input from individual rectifier modules
terminated on cabinet. (2) DC shunts to monitor current in various paths. (3)
Termination of battery 1, 2 and 3. (4) Termination of equipment positive and
negative. (5) Fuses for battery 1, 2 and 3.
3.6.5 Metering : The front panel of main rack consists of two AC meters to monitor
individual line to line voltage and current. The selector switch selects the
relevant phases. The DC meters monitor both voltage and current of batteries
and exchange.
3.6.6 Power system controller : The Power system controller card consists of an
electronic circuit which monitors the state of each rectifier module and display
their status. It also controls the operation of the module so as to make it work in
auto float or auto charge mode. The current signals are monitored continuously to
ensure equal sharing of current. In case of faults, the same is displayed and for
faults like input voltage beyond limits, DC output over voltage, over load etc. it
shuts off the module.
The various alarms as per following details are displayed on the front panel with
audible alarm.
(1) Mains out of range : Red
(2) Load voltage high (above 57V) : Red
(3) Load Voltage low (below 42V) : Red
(4) Mains fail : Red
(5) System overload : Red
(6) Mains available : Green
(7) System over load : Red
(8) Mains on battery discharge : Red
(9) FR/BC in Float-charge mode : Green
42
(10) FR/BC Fail : Red
43
circuit either gives a signal for float or charge. These signals are encoded by an
encoder to obtain suitable coded signals M1 and M2.
with a useful output power of 5600W delivered to the load. This unit has been
developed for cost effective but highly intelligent modular telecommunication
power systems. It fulfills the specification of
source. The mains frequency may vary from 45 Hz to 65 Hz. Total harmonic
distortion (THD) of the input current wave form is below 5%.
44
3.10 General description of operation
The SMPS 48V-5600W rectifier is a state-of-the-art switch-mode power
supply. It is composed of 3 identical single-phase sub-modules (R, S and T) as
shown in the block diagram .The sub-modules are connected between neutral
and one of the phases (R, S or T) on the input, and in parallel on the output. All ‘-‘
wires are protected by circuit breakers, which are mechanically coupled.
45
2. Signalization and manual interface (adjustment potentiometers and test jacks)
for the whole unit, and
3. Communication with power system controller ‘ITI’.
46
3.11.1 Input Section
Block 1 of the drawing presented above is the input EMI filter of the
rectifier. The fixed frequency, synchronized operation of the different circuits
allowed to optimize the filter’s performance. It has only one differential and one
common mode filter stage.
47
A general purpose full-wave Bridge Rectifier circuit forms Block 3. It is
directly mounted on the heat sink. Power factor corrector The power stage of
the Power Factor Corrector is a boost converter represented by Block 4. The
circuit operates with 100 kHz constant frequency in continuous inductor current
mode. Because of the relatively high switching frequency a loss-less snubber has
been added to the basic boost converter to reduce switching losses and
semiconductor stresses. When the boost transistor conducts the energy being
stored in the boost inductor increases. During the off-state of the transistor energy
is transferred from the inductor to the output capacitor through the boost diode.
The inductor current is measured with a sense resistor and it is forced to follow
the input voltage wave form. The technical literature refers to this technique as the
resistor emulation mode which is the most preferred load by the utility
companies.
The output Capacitor of the boost converter is marked by number 5 in
the block diagram. This capacitor is used for low-frequency energy storage as
well. Due to the nature of ac sources the energy absorbed at the input of the unit
varies according to the mains cycle. In order to deliver constant power at the
output energy must be stored inside the unit. Therefore, high voltage 450V
electrolytic capacitors are used at the output of the boost converter to provide cost
and volume effective energy storage. Block 12 is the controller of the Power
Factor Corrector. It uses the UC3854B integrated circuit which had been
developed to control boost converters in power factor corrector applications.
This integrated solution takes care about all sensing, controlling and
protection functions which are necessary to achieve proper input current wave
form and to stabilize the output voltage of the power factor corrector circuit. The
control principle implemented in the UC3854B is average current mode control.
DC/DC Converter The heart of the module is the dc/dc Converter shown in
Blocks 6-9.
Block 6 shows the primary arrangement of the full-bridge power
converter employing a safety isolated high-frequency transformer. Because of its
important role in providing safety isolation between the input and the output of
the module, the transformer coupling is emphasized in Block 7.
The secondary side of the dc/dc stage provides rectification (Block 8) and
filtering (Block 9) functions which are realized using current-doubler topology.
Particularity of the implemented solution is integration of two inductors on a
common ferrite core. The full-bridge converter takes energy from its input when
two diagonally located switches are turned on at the same time. This energy is
transferred to the output through the transformer immediately. The energy will be
stored in the output filter inductor showed in Block 9 and transferred to the output
capacitor of the dc/dc converter during the passive interval when energy is not
absorbed from the source. This sequence can be achieved by different ways
depending on the implemented control strategy.
The dc/dc Controller, shown in Block 13, is using the phase-shift pulse
width modulation technique which provides loss-less, zero voltage turn-on
condition for the primary side semiconductors. Further benefit is the greatly
48
reduced electromagnetic interference generated by the converter. The control
principle is peak current mode control.
Like the power stage, the controller circuit of the dc/dc converter is also
divided between the primary and the secondary side of the rectifier.
Communication between the separated parts are realized using optical isolators
marked by number 14.
3.11.3 Housekeeping
The name Housekeeping refers to the auxiliary power supply and to all
internal primary side supervisory functions necessary for the operation of the
unit. Besides the auxiliary power converter (current-mode controlled fly-back
converter), Block 11 also includes the master clock, under- and over-voltage
lock-out, and start-up sequence generator.
The power system controller can set the rectifier into the 3 modes of
operation, i.e. ‘auto float’, ‘auto charge’ and ‘manual boost’.
49
50
51
3.12 INSTALLATION & MAINTENANCE OF SMPS
3.12.1 Installation & Commissioning
The power system installation is simple please do the following step by step.
• Unpack all the boxes. Check for physical damages. Compare the contents with the
packing list.
• Put the main rack at the desired place then, the auxiliary rack in the left side of the
main rack. And then grow the extension racks in the extreme left.
• Connect the joining bus bars to link the main and the Auxiliary racks.
• Put the 5600W rectifiers in their respective slots in each rack. Any rectifier
modules can be put in any slot.
• Connect each ac input cable (White cable with nine pin male connector) to the
respective female socket provided in the right side in each module.
• Connect each pair of DC output cable (Red & blue cable) in the respective terminal
block provided in the left side in each module.
• 02 nos. of eight pin flat cable connectors are provided for each rectifier module
(except the last module, where only one connector is provided). Connect these on
the sockets provided on each module so that control bus is connected in daisy
chain. Finally check that the common system bus is extended to the connector JP3
of the PSC card. Ensure that there is no break in the daisy chaining of control bus.
• Connect three phase four wire input to each rack at TB1. Input points are
marked as R, Y, B, N just below the terminal block TB1. Also the terminal blocks
are provided with red, yellow and blue markers.
PLEASE ENSURE THAT THE NEUTRAL IS CONNECTED TO THE
TERMINAL MARKED AS “N” (HAVING NO MARKER).
• Ensure that all the AC side MCBs (mounted on AC distribution panel) as well
DC side MCBs, (mounted on DC distribution panel) are in OFF condition.
• Switch on the AC input. Check the availability of AC voltage on the front panel
of the power plant for each phase. If the AC I / P is within the range (320-480
volt) switch on the MCCBs in the sequence given in the Table-1 and do the NO
load test for each module.
52
TABLE -1
MCB MCB MODULE DC VM/AM DC output Remarks
AC DC ENERGISED SEL POSN. In all the 6
SIDE SIDE Position of
DC VM/AM
SEL
CB1 CBM1 M1 Posn. 1 – Eqpt 54.0 ± 0.5 v If every thing is OK isolate
Posn. 2 – BTY1 the module M1 by
Posn. 3 – BTY2 switching off the breakers
Posn. 4 – BTY3 CB1 & CBM1.
Posn. 5 – BTY4
Posn6 SYSTEM
CB2 CBM2 M2 -do- -do- If every thing is OK isolate
the module M2 by
switching off the breakers
CB2 & CBM2.
CB3 CBM3 M3 -do- -do- If every thing is OK isolate
the module M3 by
switching off the breakers
CB3 & CBM3.
After each module has been energized separately at no load, switch ON all
the MCBs and check that DC out put remains within 54.0±0.5V in all the five
positions of DC VM SEL.
Load Test:- Load Test of the unit has to be done with suitably rated resistive loads as per
Table-2.
LOAD TEST TABLE-2 MCB AC SIDE MCB DC SIDE Module Energy- sed DC
VM/AM SEL POSN. DC output In all the 6 Posn of VM SEL Resistive load in different
paths Remarks CB1 CBM1 M1 Posn. 1 – Eqpt Posn. 2 – BTY1 Posn. 3 – BTY2 Posn. 4
– BTY3 Posn. 5 – BTY4 Posn. 6 SYSTEM Auto float voltage – 54.0 ± 0.5 v Auto float
voltage – 54.0 ± 0.5 v Auto charge voltage – 55.2 ± 0.5 v Eqpt. Path-increase the current
slowly from 0 to 105 A. The voltage droop phenomena will start at the factory set current
limit(somewhere between 100 to 105 A) BTY1- No load BTY2- No load BTY3- No load
BTY4- No load Eqpt. Path no load. BTY1- No load BTY2- No load BTY4- No load
BTY3 –increase the BTY3 path current slowly from 0 to 100 A. The unit will go to Auto
charge mode when current exceeds factory at limit ( 1% of total AH capacity of both the
batteries) for ex. In case of 4x2500 AH battery banks these limit shall be 1000 A. Check
that Auto float voltage and auto charge voltage are within the limits. If every thing is OK
isolate the module M1 by switching off the breakers CB1 & CBM1. CB2 CBM2 M2 -do-
-do- -do- If every thing is OK isolate the module M2 by switching off the circuit breakers
CB2 & CBM2. CB3 CBM3 M3 -do- -do- -do- If every thing is OK isolate the module
M3 by switching off the circuit breakers CB3 & CBM3.
53
After each module has been checked on full load of 100 Ampere, switch ON all
MCBs, and load 300 Ampere in equipment path, 100 Amp. In each battery
path, and see that the rack voltage remains at 55.2 ± 0.5 volt for 600 A
system.
Pot R86 in the PSC card is used to set the current limit in the battery path.
For the 2200Amp power system there is a provision of 4x2500AH batteries and
for these batteries, the factory set values of the current limit is 10000A (i.e., 10%
of the total AH capacity of the batteries). However if the user wants to change this
value then the POT R86 needs to be varied carefully to set the current limit at the
desired value. For example, suppose initially the installed capacity is 3x2500 AH
and accordingly the battery path current limit may be set at 750 A. For these when
the battery path draws more then 750 A, vary the pot slowly in one direction and
stop when the bus voltage droops and battery path current becomes 750 A. In
these case, overload lamp ( yellow LED ) shall be lighted on all the modules. If
the voltage does not droop even when the pot has reached it’s extreme end, then
vary the pot in other direction and stop as soon as the bus voltage droops and
battery path current becomes 750 A. In these case, overload lamp ( yellow LED )
shall be lighted on all the modules.
3.13.1 SURGE ARRESTER ASSEMBLY
Four numbers of surge arrestors has been installed directly across A.C.
input terminals in the main rack of the system to protect the rectifier modules
(contained in all the racks) in the system from high energy content surges caused
by lightning or sudden switching OFF, off heavy inductive loads. The surge
arrestors contains two parts- plug and socket. In case of surge arrestors going
faulty, there shall be an indication on the front of the plug. In such case the plug
need to be replaced.
After each module has been checked on full load of 100 Ampere, switch
ON all MCBs, and load 300 Ampere in equipment path, 100 Amp. In each battery
path, and see that the rack voltage remains at 55.2 ± 0.5 volt for 600 A system.
54
3.14 TROUBLE SHOOTING CHART
Sr. Nature of Fault Probable causes Remedy
No
.
FR/FC fail LED -Any one or more rectifier Check each rectifier module front
1. is lighted on the modules has failed. panel to find out which rectifier has
front panel of Following may be reasons failed.
the main rack of failure: Switch ON the input MCB or
(i) Input MCB or AC connect AC input connector.
input connector open, Switch ON the Output MCB or
(ii) Output MCB or output connect AC output connector.
connector open, Check that the 8-pin flat cable is
(iii) Improper load sharing connected properly in each module
between the modules, and there is no break in daisy
(iv) Internal failure of the chaining of the above cable.
rectifier module. Isolate the module by switching off
its i/p & o/p MCBs & replace
- If none of the rectifier faulty modules.
module shows the alarms Check for the faulty flat cable and
LED then the problem replace it.
may be in one of the 8-pin Replace the faulty PSC card.
flat cable connected in
daisy chain between the
modules or in the cable
connected from PSC card
to the first module.
- The PSC card may be
faulty.
‘Battery Isolated -Any one or more of the Close the knife switch properly.
2. ‘ LED is lighted Bty path knife switches Replace the faulty PSC card
on the front are open.
panel of Main -The PSC card may be
rack. faulty.
‘Load Voltage -DC output voltage of the Press the ‘Load Voltage High’
3. High’ LED is system is higher than 57V Reset push button provided on the
lighted on the because of some fault in front panel. All the modules will be
front panel of any one of the module. again ‘ON’ if the fault was of a
main rack. - The PSC card may be temporary nature otherwise all the
faulty. modules will be again “OFF”
simultaneously lighting the ‘Load
voltage High’ LED on the front
panel.
Replace the faulty PSC card
55
‘Load Voltage -This may happen when Urgent action to restore the AC
4. Low’ LED is the system is working on input supply is required as the
lighted on the the batteries for a long batteries need to be manually
front panel of time and the output disconnected for the safety of
the main rack. voltage of the system has batteries.
become lower than 44V
Dimensioning of the bus-bars/cables for load & battery path with respect to
the ultimate capacity of SMPS power plants
(As per the specifications of TEC, the following calculations may be followed)
The basis for calculation ;
1, The Ultimate Load : x
2. Redundancy : 10% of Ultimate load (0.1 *x).
3. Battery-back-up : 6 hours
4. Battery capacity : 6 hour back-up up to 80% DOD (near available capacity)
5. Safety factor : 25% of the load.
6. Power plant Ultimate capacity : C
Calculations :
Load ; x
Redundancy : O.l x
Battery capacity : 6x/0.8 = 7.5x
Battery Charging Current @ Cio = 7.5x /10 = 0.75x
Power plant Ultimate Capacity : C= (x + 0.1x + 0.75x) = 1.85x
Therefore x = C/1.85
Safety factor for bus-bar/cable : 1.25
The bus-bar/cable shall be rated = 1.25*x = 1.25* (C / 1.85) = 0.68*C
So the bus bar / cable chosen for load path shall be capable to handle the
70%of the ultimate capacity of the power plant.
As there may be an eventuality when only one battery is connected to the
load, the size of bus-bar in each battery path shall also be the same.
The size of the bus-bar/cable for load & each battery path shall be higher
than 70% of the power plant ultimate capacity. However the common bus-
bar/cable used for connecting the FR/FCs to the input of the distribution unit shall
be the rating for the ultimate system capacity.
56
TABLE-I
List of spares to be supplied along with each unit of power plant (general)
I. Fuses
AC Input fuses 100%
DC output fuses 100%
Semiconductor device fuses 100%
Smoothing condenser fuses 100%
Auxiliary circuit fuses 100% (each type)
Alarm type fuses 100% (each type)
II1.Semiconductor devices
Diode 50%
Thyristor 50%
Transistors 50%
57
TABLE-2
List of spares to be supplied along with each set.
Description Qty Rating
100A 200A 400A 600A
Fuses
AC Input fuses 3 TIA20 TIS36 VSB63 VSB100
DC Output fuses 1 VSB125 VSF200 VSK400 VST630
Semiconductor device fuses 6 GSA75 GS450/150 GS450/400 GS450/500
58
2 13.0V
Pulse Transformer 2 4503
LEDs 2 5mm Red
Main Indicting LEDs 2 10mm Red
2 10mm Yellow
2 10mm Green
SAFETY NOTICE
Before applying power to the system , please ensure that the body of the
cabinet is properly earthed if the earthing is not proper , the surge protection
set installed in the system /at the site may not work & the consequential
damage to the SMPS modules because of this shall not be governed by the
warranty clause .
Before taking the insulation test of the rack , isolate the SMPS modules &
remove the surge arrestor plug from it’s base.
59
WARNING
• Hazardous voltages of 415 V rms will be present when a AC input power is
energized .
Qualified personnel must use extreme caution when operating & maintaining the
system.
• Initial battery connection & exchange connection shall be done without energizing
the system. When the system is under operation adequate precaution has to be
taken while installing & removing SMPS modules since high voltages (400V AC)
are available on the front panel.
• Please ensure that there is no ceiling fan over the power system racks , as this
disturbs the natural convention cooling of the racks.
MAINTENANCE ROUTINES
OCB-283 system is designed with a good central defense which will take care of
almost all types of situations arising from units becoming faulty. Operating staff are
intimated about the unusual events taking place in the system by messages output on
various peripheral devices. Faulty units are diagnosed by the system and appropriate
action to restore the services are taken by the system. But in the case of a fault which
needs human intervention if the messages are ignored the accumulated faults may cause
to crash the total system. Hence the maintenance routines are devised to keep the
operating staff abreast with the status of the various functions of the system and to correct
faulty units.
Maintenance routines are to :-
1. Identify the faulty functions.
2. Evaluate the system performance.
3. Billing management.
4. Backup.
5. Preventive maintenance.
The maintenance routines may be classified by function as :-
1. Management
2. Operation
3. Preventive maintenance
The routines may have different frequencies viz. daily, weekly etc.
-60-
The events and faults should be recorded in appropriate log books.
MANAGEMENT
1. Human actions with out proper understanding of their consequences or deliberate
misuse may result in affecting functions of the system or revenue loss. The
actions must be classified and restricted to various levels of staff. Proper
classification of commands must be done according to the directives from
directorate. The availability of the classes must be restricted by protection by
passwords.
2. System outputs are through logical files. Appropriate files should be assigned to
terminals. While assigning the files the volume of the output expected through
each file may be considered and number of files assigned to one terminal may be
according to the suggestions by the manufacturer of system. The files to be
assigned are PFAU, PFIM, PFID, YJDB, DGNC, OPTR, OPEC, PTAX, OPMN,
PSAD, ECSY, ELSY, PSAM, YSYS etc.
3. Install TIPGS
4. Install WAM
5. Keep enough Mag tapes
6. Manage activities by calendar
7. Verify calendar executions
8. Entry log books for all diagnostics
9. Preserve all printouts.
Management operations
Period-
Purpose Operations Precautions
Ref.
icity doc.
Check alarm conditions in PGS Check alarms in PGS
Monitoring alarms Daily
by colour. Consult the messages. HOLD user
Find the faulty unit manu
al
Create an EXEC file in Intelligent NIL Opera
Check operational
Terminal (TI). The file is to ting
status of units,
contain the commands. Run the Sheet
Check UR status,
-61-
EXEC file and note the results. s
Check logic status, Daily
Check signaling ESMIN;
channel status, TELIN : AFUR = (Range of
Check peripheral and URs)
SMM status.
TELINB : AFPIL= (Range of
URs)
AFRES=(Range of
URs)
FSMIN : TYR=RL
OPERATION
1. Transfer subscribers meter reading to magnetic tapes.
-62-
Purpose Periodicity Operations Precautions Ref. doc
Save the subs meter reading Fortnightly Prepare GTLC tape Prepare two Charging and
on magnetic tapes for as per the operating copies magnetic tape
processing at billing centre documentation. management
(TAXIL:
OPT=TAMP
followed by
OPT=SV)
Save the detailed billing Fortnightly Prepare GTDT tape Prepare 2 Charging and
data on magnetic tape for as per operating copies. One magnetic tape
processing at billing centre. documentation day before management
(FDTIL: weekend is
OPT=SV) recommended
to avoid
chance of
overflow.
Save alarms, faults, Fortnightly Prepare OPFA tape Prepare before Alarm and
observations and logbook on as per operating overflow of magnetic tap
magnetic tape. documentation buffer occurs. management
(OFAIL:
OPT=SV)
Load and traffic Daily Record NSSIN Fixed time
measurement readout in register Busy hour
Use OCHLA
-63-
General information of Daily Using OCHLA At busy
traffic efficiency command manually hour
or in calendar
Check spare PCBs Monthly Check the PCB in Use
on appropriate unit antistatic
in actual traffic equipment
conditions.
To test all circuits Daily Assign ECSY file Execution Circuit test and
periodically Insert command of the calendar
CIRACT in calendar command management
Check the results to take
from the printout in place at
ECSY file. Recheck night
the circuits reported
faulty using
CIRDEM and
APDLA commands.
To identify fault telephone Daily Assign ELSY file Command Subs test and
lines Insert the command ESSY to calendar
ESSY in calendar. be Management
Recheck the lines executed
reported faulty by during
ESAB command. night hours
-64-
PREVENTIVE MAINTENANCE
4. Verification of TVDR.
7. Rectifier maintenance.
9. Battery maintenance.
DATE:
-65-
TASKS NAME OF THE HOUR RESULTS,
OFFICER ACTION
TAKEN,
REMARKS
Visual inspection of PGS
Functional state of exchange (using
EXEC file)
Analysis of faults and alarms
Observation of traffic efficiency
(OCHLA)
Systematic test of circuits (Results
and follow-up-actions)
Systematic test of subscribers
(Results and follow-up-actions)
Verification of temperature of
Exchange room
Load and traffic measurements
-66-
TASKS NAME OF THE HOUR RESULTS, ACTION
OFFICER TAKEN, REMARKS
Transfer of subscribers meter reading
on mag-tape
Transfer of detailed billing data to
magnetic tape
Transfer of alarm, faults, observations
on magtapes
Exchange data backup
System data backup
Maintenance of magtape drives
Verification of spare PCBs
Preventive maintenance of streamers
Verification of TVDR
3 SMM LOG
Date and Nature of Message Message Action Date and Remarks
Time of Fault on WAM on YSYS time of
Fault restoration
6. Magtape movement log ( Serial number, Type of data, Data, Docket, Date of
return, Remarks)
-67-
Date and Time of Fault Source Fault Action PCB Down NSSIN
message, Alarm or taken changed time
Routine test)
9. ND – NE REGISTER
13 P B MOVEMENT REGISTER
OCB Serial No. FRD No. Nature of Date sent Date Repaired or
Name fault received replaces
after repair
-68-
14 PRINTOUTS TO BE PRESERVED
The following printouts are to be preserved
FSCIL, ACHIN, INFIL, INDIN (TRAD 1 to 4), FSMIN, LDIL, ASMIN, TELIN
(for AFGRX), FSCIN (for each NFSC), CTIN (for every PCM), NLIBR (FOR NE and
ND).
The maintenance routines are only guide lines and are to be adapted according to
circumstances. Detailed billing archiving frequency depends on the type of traffic in the
exchange. Frequency of the subscriber line routine testing depends on the existing
external line plant. If more faults are observed the frequency is to be increased.
CHAPTER - 5
SUBSCRIBER LINE MANAGEMENT
5.0 INTRODUCTION
The subscriber and user line management function incorporates all the tasks for
ensuring that subscribers can:
make and receive telephone calls when they want,
use the facilities and features offered to them as and when they require,
have permanent access to a line with good quality of service.
-69-
• Ordinary Analog or
• Analog Subscriber with home metering.
-70-
ISDN SUBSCRIBER PRIMARY & BASIC ACCESS
PRIMARY ACCESS
SO BUS
PCM
30 B +D ISDN STATIONS
DIGITAL
EPABX
NT2 ANALOG EXTENSIONS
2 B +D
& NT1
OCB-283
SUBSCRIBER PREMISES
DIGITAL
2 B +D
NT1
ISDN STATIONS
BASIC ACCESS
S BUS
Single line
A line that is identified by an equipment number (NE) and a designation
number (ND).
-71-
Principal group
Priority group
A priority group is made up of lines from an existing principal group that are
associated to a priority group designation number (NDP). There can be
several priority groups in a principal group.
ND = 22220001
22220001
2222A001
ND = 22220003 22220003
NDG = 22220004
22220004
2222A002
2222A003
2222A004
-72-
5.3 Subscriber characteristics
5.3.1 Presentation
ND NE/NR
TAX
TAX
CAT TY
MAR
MAR
Example :
@ABOIN,CEN=1:
CEN=1/94-02-03/15 H 49 MN 36/CONSULTATION OF SUBSCRIBER
CHARACTERISTICS
@ND=22220257;
PROCESSING TGLAIN ACC
ND=2222O257 NE =001-02-001
TAX = 00000289 + 00003854 + 00008327 + 00000028
TY= KLA
CAT= RVT
MAR=ART
NAR=22220032
PROCESSING TGLAIN EXC
-73-
5.3.2 Designation number
-74-
identified by AFCT(Subscriber line on PCM link) A relationship can be
established between the designation number (ND) and a telephone circuit , which
means that the subscriber line is connected to the exchange via a time-division
multiplex channel (TDM channel) of a PCM link.
-75-
5.3.4 Charge meter
CAT : Categories are data related to the designation number. They are
assigned either individually to the subscriber line or to a set of
lines of a group (ex : RVT entitlement to temporary transfer).
-76-
Example :
@ABOIN,CEN=1:
CEN=1/94-02-03/15 H 49 MN 36/CONSULTATION OF SUBSCRIBER
CHARACTERISTICS
@ND=22220257;
PROCESSING TGLAIN ACC
ND=2222O257 NE =001-02-001
TAX = 00000289 + 00003854 + 00008327 + 00000028
TY= KLA
CAT= RVT
MAR=ART
NAR=22220032
PROCESSING TGLAIN EXC
@ABOIN:
CEN=1/00-01-03/01 H 53 MN 55/SUBSCRIBER
CHARACTERISTICS INTEROGTN
@ND=310083:
PROCESSING TGLAIN ACC
ND=310083 NE =002-00-083
TAX = 00000052 + 00000000 + 00000000 + 00000000
TY= NBS1+PRAC2
CAT= NAT2+CLAB4
PROCESSING TGLAIN EXC
@ABOIN,CEN=1:
CEN=1/94-02-03/15 H 49 MN 36/CONSULTATION OF SUBSCRIBER
CHARACTERISTICS
@ND=22220257;
PROCESSING TGLAIN ACC
ND=2222O257 NE =001-02-001
TAX = 00000289 + 00003854 + 00008327 + 00000028
TY= KLA
CAT= RVT
MAR=ART
NAR=22220032
PROCESSING TGLAIN EXC
@ABOIN:
CEN=1/00-01-03/01 H 53 MN 55/SUBSCRIBER
CHARACTERISTICS INTEROGTN
@ND=310083:
PROCESSING TGLAIN ACC
ND=310083 NE =002-00-083
TAX = 00000052 + 00000000 + 00000000 + 00000000
TY= NBS1+PRAC2
CAT= NAT2+CLAB4
PROCESSING TGLAIN EXC
-77-
5.4 Description of MMC functions
Presentation
ND NE TAX TY CAT
@ABORT
NE Equipment released
ND - TY=DFn
Consultation functions
-78-
URAIL : Lists the equipment types
This command is used to list the equipment types (subscriber junctor on the
board).
@URAIL:
@ AFUR or NE or NR or AFCN ,CTRL;
@ABOIN:
@ND or NE;
EXAMPLES
@NLIBR:
CEN=1/99-03-15/16 H 05 MN 00/IDLE NUMBER SEARCHING
@ND=383300<383500,NB=4;
ND=383340
ND=383341
ND=383450
ND=383499
EXC
@NE=4-4-1<4-5-10;
NE=4-4-8
NE=4-5-1
NE=4-5-7
EXC
@NUTIL:
CEN=1/99-02-18/20 H 10 MN 00/LIST OF NUMBERS IN USE
@NE=3-1-27<3-1-30:
NE=3-1-27 ND=385111
NE=3-1-28 ND=385120
EXC
@ND=7894800<7894850;
ND=7894827 NE=7-3-45
ND=7894736 NE=7-4-12
EXC
-79-
@URAIL,CEN=1:
CEN=1/99-10-07/00 H 01 MN 00/URA EQUIPMENT LIST
@NE=42-0-1<2:
TRAITEMENT TPSSER ACC
AFUR=002 TYPUR=URA NBEQPT=0253
NE= 042-00-001 (042-00-00-01)ND= 596420001 S2F
NE= 042-00-002 (042-00-00-02)ND= 596420002 S2F
TRAITEMENT TPSSER EXC
@ABOIL:
CEN=1/99-02-03/14 H 57 MN 58/SUBSCRIBER CHARACTERISTICS LIST
@CAT=ZG3;
PROCESSING TGLAIL ACC
ND=223004 NE =056-00-004
TAX = 00000060 + 00000000 + 00000000 + 00000000
TY=KLA+IIB
CAT=RVT+AEN+NA04+ZG03+COF+IAI
MAR=ATT
PROCESSING TGLAIL EXC
-80-
ABOMU : Reallocates a subscriber line
Reallocates a subscriber line to another equipment unit. Allocates new
available equipment to the subscriber's ND, the latter keeps its
discriminations and the value of its charge meters.
The subscriber keeps his directory number, his discriminations and the
contents of his charge account.
The old equipment becomes available (the ND - old NE link is cut) and the
ND - new NE link is created.
ABOSU : Deletes a single line
Erases the discriminations.
Releases the ND that becomes "not in use" (NNU) and releases the NE if the
line was not cancelled-transferred.
EXAMPLE
@ABOCR:
CEN=1/99-02-03/09 H 33 MN 52/NEW SUBSCRIBER LINE ADDITION
@ND=96560003,NE=56-0-3,TY=KLA,CAT=AEN+NA2:
PROCESSING TGLACR ACC
ND =96560003 NE =056-0-003
TAX = 00000011 + 00000000 + 00000000 +00000000
TY=KLA
CAT=AEN+NA02
PROCESSING TGLACR EXC
@ABOCR:
CEN=1/99-02-03/09 H 37 MN 52/NEW SUBSCRIBER LINE ADDITION
@ND=96560005,NE=56-0-5,TY=NBS1+PRAC2,CAT=NAT2+CLAB4;
PROCESSING TGLACR ACC
ND =96560005 NE =056-00-005
TAX = 00000011 + 00000000 + 00000000 + 00000000
TY=NBS1+PRAC2
CAT=NAT2+CLAB04
PROCESSING TGLACR EXC
@ABOMO:
CEN=1/99-02-03/10 H 42 MN 55/MODIFY LINE CLASS OF SERVICE
@ND=223055,TY=KLA,CAT=CT3+ZG2+FD3+AEN;
PROCESS TGLAMO EXC
ND=223055 NE=056-00-055
TAX=00000012 + 00000000 + 00000000 + 00000000
TY=KLA
CAT=AEN+CT03+FD03+ZG02+NA02
PROCESS TGLAMO EXC
@ABORT:
CEN=1/99-12-02/11 H 11 MN 21/SUBSCRIBER CANCELLATION/TRANSFER
@ND=223100,CAT=DF3;
PROCESSING TGLART ACC
ND=223100
CAT=DF03
PROCESSING TGLART EXC
-81-
@ABOMU:
CEN=1/99-02-03/00 H 51 MN 20/SUBSCRIBER LINE CHANGE
@ND=223289,NE=56-3-6:
PROCESSING TGLAMU ACC
ND=223289 NE=056-3-006
TAX=00000050 + 00000000 + 00000000 + 00000000
TY=KLA
CAT=NA03+IAM
PROCESSING TGLAMU EXC
@ABOSU:
CEN=1/99-02-03/11 H 13 MN 20/SUBSCRIBER LINE DELETION
@ND=223100;
PROCESSING TGLASU ACC
ND=223100
CAT=DOP
PROCESSING TGLASU EXC
The MMCs : ABOCR, ABOMO, ABORT and ABOSU only act on one line at
a time. In some special operating cases (creating a UR, number cancellation,
etc.) it is possible to use the commands on a group of lines.
-82-
ABORTM : Multiple subscriber cancellation
ABORTM allows to cancel-transfer subscriber lines.
With ABORTM it is possible to:
-prohibit outgoing subscriber calls,
- transfer incoming calls to a recorded announcement or operator.
The equipment can be immediately reused.
The designation number (ND) can only be reused after executing ABOSU.
One can execute ABORT several times on the same ND to modify call
transfer to a recorded announcement or operator.
ABORTM creates a record item on the itemised billing tape.
ABOSUM : Multiple subscriber deletion
ABOSUM allows to delete single subscriber lines.
With ABOSUM one can delete:
- in-service lines,
- cancelled-transferred lines.
ABOSUM deletes all subscriber characteristics in the exchange andfrees the
equipment number and designation number.
ABOSUM creates a record item on the itemised billing tape.
Caution :
• These commands do not check if the connection unit is present, nor
do they check the presence and the type of board in use.
EXAMPLES
@ABOCRM:
CEN=1/99-02-03/14H56MN03/NEW SUBSCRIBER LINE ADDITION
@ND=7894885+7894886,NE=2-1-60+2-1-61,TY=KLA,CAT=AEN+NA2:
PROCESSING TGLACR ACC
ND=7894885 NE = 002-01-060
TAX=00000011 + 00000000 + 00000000 + 00000000
TY=KLA
CAT=AEN+NA02
ND=7894886 NE = 002-01-061
TAX=0003824 + 00000000 + 00000000 + 00000000
TY=KLA
CAT=AEN+NA02
PROCESSING TGLACR EXC
@ABOMOM:
CEN=1/99-02-03/14H56MN03/MODIFICATION OF LINE CLASSES OF SERVICE
@ND=223050+223002,TY=/KLA,CAT=/AEN+FD3+CT3+ZG2;
PROCESSING TGLAMO ACC
ND=223050 NE = 050-00-050
TAX=00000200 + 00000000 + 00000000 + 00000000
ND=223002 NE = 050-00-002
TAX=00000030 + 00000000 + 00000000 + 00000000
PROCESSING TGLAMO EXC
-83-
@ABORTM:
CEN=1/99-02-03/10H45MN03/SUBSCRIBER CANCELLATION-
TRANSFER
@ND=223100+252001,CAT=DF3;
PROCESSING TGLART ACC
ND=223100
CAT=DF03/ZG02
ND=252001
CAT=DF03/RVT
PROCESSING TGLART EXC
@ABOSUM:
CEN=1/99-10-23/14H56MN03/SUBSCRIBER LINES DELETION
@ND=223100+252001;
PROCESSING TGLASU ACC
ND=223100
CAT=DF11
ND=252001 NE=2-5-1
TY=KLA
PROCESSING TGLASU EXC
SUBSCRIBER INSTALLATION
DIGITAL
EXCHANGE TELEPHONE TERMINALS
TE1
DIGITAL DIGITAL
NETWORK SUBSCRIBER S
CSN 30B+D TERMINAL TERMINAL TE2
2048 kb/s
B
TABN U
TNR TNR S
LT CARD
NT1 NT2 TE3
2B+D
192 kb/s
TE4
TE5
-84-
5.6.1 Basic and primary rate access The term subscriber line is replaced
by"access".
In the ISDN, a number of interfaces or physical reference points (R, S, T,
U and V) are defined between the subscriber terminal and the network.
There are two types of ISDN access: basic rate access and primary rate
access.
Basic rate access The basic rate access bearer circuit is the traditional two
wire pair. It is constructed as two 64 kbit/s B channels and one 16 kbit/s
signalling channel (D channel). The total bit rate is 160 kbit/s at the U interface
and 192 kbit/s at the S interface. The useful bit rate is 144 kbit/s at both
interfaces.
Primary rate access The bearer circuit for primary rate access is a PCM
multiplex structured as 32 time slots (TS), comprising 30 x 64 kbit/s B channels
and one 64 kbit/s D channel. The total bit rate is 2 048 kbit/s
Notes on the interfaces: - NT2 is only a physical interface and has no "intelligence" or
sophisticated dialogue functions with the network, unlike NT1
which can interpret messages from the network and
redistribute calls within the customer premises equipment.
- The most important interfaces are the S and U interfaces which are covered by
very precise standards from ITU-T and ETSI committees.
- The V interface is of theoretical interest only since it is part of the local
exchange (CSN in the E10 system) and is not standardized.
- The same situation applies at the primary rate access subscriber's premises:
since NT1 and NT2 are incorporated in the same hardware, the manufacturer
is free to construct its T interface as it wishes.
- The R interface depends on the type of terminal and there are a wide variety
of specifications
-85-
5.6.3 ISDN services The ISDN provides three types of services:
bearer services,
teleservices,
supplementary services.
Bearer services and teleservices can be characterized by a list of attributes.
-86-
Examples of teleservices
telephony,
group 3 facsimile (fax),
group 4 facsimile (fax),
videotex (Minitel in France), combining a screen, modem and keyboard to
access on-line servers,
teletex and electronic mail.
BASIC ACCESS
Creating a terminal unit (UT) The TAN3G and TABNP boards are subscriber
terminal units (UT) for connecting eight two-wire echo cancelling basic rate
access ports in accordance with the ETSI standard.
The TAN3G board can be created using the UTCR command with TFCT
= AQE08, and the TABNP board can be created with the same command UTCR
with TFCT = AQP08.
UT power weighting :
The TAN3G board has a power weighting of 2 (reflecting the board's power
consumption). You cannot therefore install more than eight TAN3G boards in a
digital concentrator (CN), because the total power weighting of a local digital
concentrator (CNL) must not exceed 16.
Backup UT function :
• The TAN3G board can be backed up. The backup UT must be placed in
the second position (UT1) in the CN subrack. The backup option must be software
enabled (OBJ=YES in the UTCR command and hardware enabled by the presence
of an adapter plug.
Creating a basic rate access subscriber line The ABOCR command is used to
attach an NE number (representing an access) to an ND (belonging to a thousands
group that has already been created).A number of categories and types must be
assigned to the line, defining the type of access and related services.
-87-
Parameter TY or CAT Definition Possible values
NCA TY Number of one-way NCAi : 0 i 2
outgoing B channels
NCB TY Number of one-way NCAi : 0 i 2
incoming B channels
CLAB CAT Subscription class CLAB0:analogue
(defines the subscriber's subscriber
entitlement CLAB1 : entitlement
to a bearer service) to SCBNT
and SCBT
CLAB2 : entitlement to SCBNT,
SCBT and SSC
CLAB3 : entitlement to SCBT, VC and SSC
CLAB4 : entitled to all ISDN bearer services
RR TY Presence of repeater
When creating a basic access, it is essential to specify CAT = NAT2 and TY = NBS1.
SUBSCRIBER A NDSA4
TE4
NDSA1 NDSA2 NDSA3
200 METERS
MAX.
OCB-283
EXCHANGE SUBSCRIBER B
S BUS
NT1
PRIMARY RATE ACCESS Creating a terminal unit (UT) The TADP board is a
subscriber terminal unit for connecting a primary rate access carried by a PCM
link. The primary rate access subscriber always has an NT1 (PABX) behind the
NT2.
-88-
TFCT = ADP01 for a TADP board,
TFCT = ACP01 for a TADPB board.
There are three red LEDs mounted on the board's front panel:
the first LED indicates the state of the board:
the second LED indicates a remote alarm condition on the PCM link,
the third LED indicates a local alarm.
Power weighting of the UT : The UT has a power weighting of 1 (indicating the
board's power consumption). It is therefore possible to install up to 16 TADP or
TADPB boards in each digital concentrator (CN), because the total power
weighting of a CNL must not exceed 16.
Creating a primary rate access subscriber The ABOCR command can be used
to attach more than one ND to an access (NE).
Categories and types are described in the basic access section.
The values for a primary rate access are:
TY = NBS2,
CAT = NAT2,
A new category, NBAi 0 i 31, sets the number of channels allocated to
traffic.
Introduction
With the subscriber tests the operating personnel can, from the OM and either
systematically or individually check if the lines and subscriber equipment units
are working correctly.
The subscriber tests refer to the measurements and tests carried out on the
equipment that comes after the subscriber junctor, as well as to the tests
concerning the junctor itself.
There are six different types of tests :
1) on-request tests concerning the line and subscriber equipment (MMC
: ESAB),
2) routine line tests (MMC : ESSY),
3) high speed tests from the subscriber equipment unit via the DERAL
(High speed line/subscriber set tester),
4) manual tests (MMC : ESAMAN),
5) listing of faulty equipment (MMC : ABFASE),
6) periodic junctor tests via the REJA device.
5.8 Test mask
-89-
A test mask consists of a set of measurements which characterize the line.The
Alcatel 1000 E10 (OCB283) supports up to eight different test masks which can be
set by operator command. Each line is assigned a test mask according to its
structure and type (overhead, underground etc). The test mask is used as a
comparative reference when testing the line.
To determine whether a line is satisfactory or malfunctioning during
routine subscriber line tests, the Alcatel 1000 E10 (OCB283) compares the values
stored in the line test mask with the results of measurements performed on the line
Calibrating the tester A test is run on the tester itself by carrying out
measurements on a virtual subscriber line (GABA0) with known reliable
characteristics. If the tester finds the virtual line satisfactory, this means that it is
operating correctly. If it finds the virtual line defective, the tester may be
defective.
Test curve list proposed when the public exchange is commissioned :
MODIFICATION OF MASK
-90-
@GABMO:
CEN=1/03-03-13/15 H 22 MN 51/LINE CALIBER MODIFICATION
@GABA=1,L=8,BI=6250:
PROCESSING TECSMS ACC
GABA = 1 L = 8 BS > 0006.35 BI = 0006.25/ 0000.00
PROCESSING TECSMS EXC
Test priorities :
• ESAB, DERAL, RELEX and REJEX tests have the highest priority,
• routine ESSY tests can be interrupted for 15 minutes,
• internal junctor tests have the lowest priority.
5.10.1 MMC functions
-91-
ESER : Tester calibration
By connecting the tester to a reference unit, this command is used to check
the tester calibration. The only commands that are authorised are open-loop
line test commands (phase L3 to L8). If the tester is already running a test, the
command is refused.
L3 Potential on wire "a" 42V < 53V
L4 Potential on wire "b" 4V < 6V
L5 Insulation wire "a" / Ground 40KΩ < 56KΩ
L6 Insulation wire "b" / Ground 40K < 56KΩ
L7 Insulation wire "a" / wire "b" 368KΩ < 432KΩ
L8 Capacity 1,95µF < 2,50µF
ESMB : UR batteries measurements
This command is used to make several measurements on the UR (connection
unit) batteries. It is very useful on satellites, for measuring the battery level
during power cuts. Phases L1 to L4, corresponding to measurements on a line
in open loop, are the only ones authorised. Non significant measurements are
output with an asterisk.
ESRZ : Tester Reset
Independently from any on-going test, this command is used to reset the
tester. It should be refused if a test is running. this command is not
worthwhile in a test that returns to idle after each order. In some cases it can
be output to get out of a lock-out.
EXAMPLES
@ESER:
CEN=1/00-01-03/01 H 52 MN 44/TEST-CALL RESPONDER CALIBRATION
@NROB=130:
PROCESSING TELDMS ACC
NROB = 130
PROCESSING TELDMS EXC
@PH=L;
PROCESSING TELDMS ACC
L1 R = **** V
L2 R = **** V
L3 R = -0048.5 V
L4 R = +0005.0 V
L5 R = 0048 KOHM
L6 R = **** KOHM
L7 R = 0400 KOHM
L8 R = 0002.25 MICF
PROCESSING TELDMS EXC
@ESMB:
CEN=1/00-01-03/01 H 53 MN 12/BATTERIES MEASURMNT
-92-
@NROB=129:
PROCESSING TELDMS ACC
NROB = 129
PROCESSING TELDMS EXC
@PH=L;
PROCESSING TELDMS ACC
L1 R = **** V
L2 R = **** V
L3 R = -0053.0 V
L4 R = **** V
PROCESSING TELDMS EXC
@ESRZ:
CEN=1/00-01-03/01 H 53 MN 37/TEST-CALL RESPONDER RESETTING
@NROB=130;
PROCESSING TELDMS ACC
NROB = 130
PROCESSING TELDMS EXC
-93-
These tests consist in sending a number of remote charging pulses (they
can be of several kinds) to the subscriber's meter and then the operator
communicates with the subscriber to check if the results are in compliance.
During subscriber premises meter testing no increments are added to the
subscriber's charge meter.
-94-
ESAB
1
ND or NE or NR The "L" phase is automatically run
2
PH=L PH=Li PH=RLi
5
PH=FIN End of tests and tester release
-95-
A : Switch over to calling phase. In this phase the subscriber and the
operator are put in communication. The latter then explains to the
subscriber which manipulations to execute.
NDOP : Operator's number, used in the CSN case.
P : Complete test of a dial set, with execution of phases P10 to P14
on the tester. This test requires that the subscriber dial zero.
Pi : Measurement of one of the set's characteristics (i = 3, 4, 5, 6, 7 :
phases reserved for export applications (test monitoring, remote
charge).
i = 3 and 4, phases not used in the case of a subscriber on CSE.
Pi : Repetitive measurements of one of the set's characteristics (i = 13
or 14).
K : Push-button set test. The operator asks the subscriber to press
successively each of the buttons on his set.
Z : Tester reset.
FIN : End of subscriber test. This parameter is needed to make sure the
test sequence ended normally.
DR : The tester is disconnected to allow moving to phases P5 and P6.
@PH=A:
PROCESSING TELDMS ACC
CALL ND : 310007
ENTER NDOP
PROCESSING TELDMS EXC
@NDOP=300005:
PROCESSING TELDMS ACC
PROCESSING TELDMS EXC
@PH=P:
PROCESSING TELDMS ACC
DIAL ZERO
P10 R = 0067 MS
P11 R = 0034 MS
P11 R = 0001.97
P11 R = 0009.9 HZ
P12 R = 0010
-96-
P13 R = 0048 MA
P14 R = 0350 OHM
PROCESSING TELDMS EXC
@PH=RP13:
PROCESSING TELDMS ACC
P13 R = 0048 MA
MAX = 0048 MA
MIN = 0048 MA
MOY = 0048 MA
PROCESSING TELDMS EXC
@PH=FIN;
PROCESSING TELDMS ACC
PROCESSING TELDMS EXC
ESAB:
CEN=1/03-03-13/15 H 13 MN 45/TEST ON A SUBSCRIBER LINE
@ND=310007:
PROCESSING TELDMS ACC
ND= 310007 NE=002-00-007 NROB=130 TY=GABA1+KLA STATUS=LIBR
L1= 0 V L2= 0 V L3= 0.0 V L4= 0.0 V
L5> 1016 KO L6> 1016 KO L7> 1016 KO L8= 1.30 MI
@PH=A:
PROCESSING TELDMS ACC
CALL ND : 310007
ENTER NDOP
PROCESSING TELDMS EXC
@NDOP=300005:
PROCESSING TELDMS ACC
PROCESSING TELDMS EXC
@PH=K:
PROCESSING TELDMS ACC
DEPRESS ALL DIGIT KEYS
1
2
3
4
5
6
7
8
9
*
0
#
NO FIGURE
PROCESSING TELDMS EXC
@PH=P13:
PROCESSING TELDMS ACC
-97-
P13 R = 0048 MA
PROCESSING TELDMS EXC
@PH=P14:
PROCESSING TELDMS ACC
P14 R = 0350 OHM
PROCESSING TELDMS EXC
@PH=P15:
PROCESSING TELDMS ACC
ACTIVATE THE FLASHING BUTTON
P15 R = 0072 MS
PROCESSING TELDMS EXC
@PH=END;
PROCESSING TELDMS ACC
PROCESSING TELDMS EXC
5.11.1 Basic rate access maintenance :The line tests (L1 to L8) remain, but the
maintenance functions are enhanced through a maintenance channel at the U
interface. This channel provides continuous transmission quality monitoring (by
CRC computation), and is used to set up loops on the board for repeaters or the
NT1.
The maintenance channel ends at the NT1. This means that neither the S
interface nor the terminals connected to it can be tested directly.
U interface tests: The ESAB command (with PH = L1 to L8) is used to test line
insulation, as with analogue subscriber lines (however, PH = A is no longer
accepted).
This check is run periodically by the system but can also be activated using the
ESAB command with PH=TCO. It does not disrupt traffic The continuity check
involves verifying level 1 activation (if it has not already been activated), and
sending a terminal endpoint identifier (TEI) polling frame (broadcast maintenance
frame) to verify level 2 and the presence of terminals behind the NT1. The test is
run every 20 minutes for a sound access and much more frequently
(approximately every minute) for a defective access.
-98-
The test is more exhaustive than the TCO. It is designed to produce a diagnostic.
It is activated after an NOK TCO test or manually by running a LOCAVAR
sequence. The access is unavailable during the TIED test (seizure of the RELA
bus to the TMLAB) and goes to the DENI state (unidentified failure).The TIED
test involves setting up loops on the subscriber line board for the repeater (if there
is one) and the NT1. A predetermined TMLAB test pattern is sent and looped for
checking. This enables the system to locate a defective entity.
- Access failure states The FXA state (permanent line condition) for analogue
lines is no longer used.
The line state can vary after a TCO check or TIED test, or as a result of
continuous transmission quality monitoring on the maintenance channel.
DLAT
line fault ahead of NT1
-99-
The line is repeatered and a TIED test looped at the NT1 has revealed a
transmission fault while the QTR and QTI thresholds have been reached
DTNR
NT1 fault
The line is repeaterless or repeatered and a TIED test looped at the NT1 has
revealed a transmission fault but the QTI and QTR thresholds have not been
reached.
TNR
NT1 fault
The line is repeaterless or repeatered and a TIED test looped at the NT1 has
revealed a transmission fault but the QTI and QTR thresholds have not been
reached (suggesting an NT1 fault)
DITA
customer premises equipment fault
Level 1 tests are satisfactory, but the level 2 test has failed probably indicating
that there is no terminal connected to the NT1
ALA
local power supply fault
The power supply to the NT1 is inadequate (normal and backup modes)
CIB
Battery low
In normal operation, the backup voltage output by the battery is too low
ASI
Cannot supervise power supply
The NT1 cannot send information about the state of the batteries
The exchange core subsystem periodically uploads a list of defective equipment
and equipment states (every 18 minutes).
-100-
PH=----:Identifies the measurement phase. It is possible to execute a number of
measurements as a sequence.
The result depends on the phase requested.
Phases PH=L, Li, RLi are prohibited for accesses carrying a LS or a LLP. On an
access carrying a LLP, the line tests are however authorized when the FORC
parameter is present on the ND, NE or NR line.
EXAMPLE
@ESAB:
CEN=1/00-01-03/01 H 54 MN 15/TEST ON A SUBSCRIBER LINE
@ND=310083:
PROCESSING TELDMS ACC
ND= 310083 NE= 002-00-083 TY= NBS1
PROCESSING TELDMS EXC
@PH=L:
PROCESSING TELDMS ACC
NROB = 130 ETAT = LIBR
L1 R = 0000 V
L2 R = 0000 V
L3 R = 0000.0 V
L4 R = 0000.0 V
L5 R > 1016 KOHM
L6 R > 1016 KOHM
L7 R > 1016 KOHM
L8 R = 0001.00 MICF
PROCESSING TELDMS EXC
@PH=TCO:
PROCESSING TELDMS ACC
TCO R = OK
PROCESSING TELDMS EXC
@PH=DCB:
PROCESSING TELDMS ACC
DCB R = RUNNING
-101-
PROCESSING TELDMS EXC
@PH=END;
PROCESSING TELDMS ACC
PROCESSING TELDMS EX
5.11.3 Primary rate access maintenance - a primary rate access is a PCM multiplex,
hence it is not possible to run line tests (ESAB command not possible). Nor is it
possible to run continuity checks. Level 1 is always active. NT2 manages the
passive buses directly (S interface activation cannot be controlled from the TADP
board).There is no backup provided for the TADP board.
-102-
5.12 Routine tests
Introduction
These tests are line measurements carried out on all the subscriber lines of an
exchange or just on a list of subscribers. The command is usually
programmed so as to be run at night. Routine tests are done on subscriber
lines that are "free" or "in permanent loop condition". Routine test are not
performed for ISDN access as it is tested automatically by system(every 18
min) and information for the faulty access is displayed on terminal assigned
to LAND.
The line measurements correspond to phases L1 to L8.
The obtained results are compared to previously recorded reference values
(test curve : GABA 1 to 8). These test curves depend on the type of the line.
When the deviation on one or several measurements is higher than a specific
threshold, the line is considered faulty.
The tester is re-gauged if 10 successive measurements are found to be faulty.
@ESSY:
CEN=1/03-03-13/15 H 17 MN 10/ACTUATE SYSTEMATIC TSTS ON SUBSCRBRS
@ND=310007+300005,OPT=1:
PROCESSING TECSMS ACC
* #R0809/054/'TECSMS'/TERMINAL RELEASE
NCEN=JABRTT/03-03-13/15 H 17 MN 31/START OF SYSTEMATIC TESTS ON
SUBSCRIBERS
ND= 300005 NE=001-00-005 NROB=129 TY=GABA1
-103-
L1= 0 V L2= 0 V L3=- 0.5 V L4= 0.0 V
L5> 1016 KO L6> 1016 KO L7> 1016 KO L8= 1.30 MI
NE=001-00-005<001-00-005
NE=002-00-007<002-00-007
NCEN=JABRTT/03-03-13/15 H 17 MN 53/STOP OF SYSTEMATIC TESTS ON
SUBSCRIBERS
PROCESSING TECSMS EXC
@ESSY:
CEN=1/03-03-13/15 H 18 MN 03/ACTUATE SYSTEMATIC TSTS ON SUBSCRBRS
@ND=310007+300005,OPT=2:
PROCESSING TECSMS ACC
* #R0809/054/'TECSMS'/TERMINAL RELEASE
NCEN=JABRTT/03-03-13/15 H 18 MN 24/START OF SYSTEMATIC TESTS ON
SUBSCRIBERS
NE=001-00-005<001-00-005
NE=002-00-007<002-00-007
NCEN=JABRTT/03-03-13/15 H 18 MN 45/STOP OF SYSTEMATIC TESTS ON
SUBSCRIBERS
PROCESSING TECSMS EXC
@ESSY:
CEN=1/03-03-13/15 H 20 MN 23/ACTUATE SYSTEMATIC TSTS ON SUBSCRBRS
@NE=9-0-1<9-0-127+15-0-1<15-7-127,OPT=3;
PROCESSING TECSMS ACC
* #R0809/054/'TECSMS'/TERMINAL RELEASE
NCEN=JABRTT/03-03-13/15 H 20 MN 40/START OF SYSTEMATIC TESTS ON
SUBSCRIBERS
(*) ND= 384500 NE=9-0-63 NROB=2 TY=GABA1
(**) ND= 396657 NE=9-0-125 NROB=2 TY=GABA2
NE=9-0-1<9-0-127
NE=15-0-1<15-7-127
NCEN=JABRTT/03-03-13/15 H 21 MN 02/STOP OF SYSTEMATIC TESTS ON
SUBSCRIBERS
PROCESSING TECSMS EXC
-104-
Manual tests
With these tests the operator can, using one command, make the exchange
transmit signalling or tones to a specified subscriber line.
ESAMAN : Manual subscriber test
5.13 Monitoring faulty equipment
Introduction
This monitoring is used to know all or a part of the sets that are out of order.
The monitoring covers the junctor and the subscriber line :
• The junctor is detected as faulty or inaccessible to the system.
The subscriber lines are considered to be in permanent loop condition :
• Unhook without dialling (ex : 16 s),
• Time delay overflow between two numbers (ex : 16 s),
• Ringing time (ex : 4 min),
• No hang-up on end of call (ex : 30 s),
• Call on busy subscriber (no hang-up),
• Wrong dialling with no recorded announcement.
The time delays are described in the country specifications. 100 to 500 ms are
required to return to normal conditions.
The equipment can be monitored :
• either automatically,
• or on request by MMC : ABFASE.
Processing permanent loop condition thresholds :
• the CSN has a cumulative counter for permanent loop conditions,
• the MLPC automatically consults the URA (60 s period) to report :
. the number of permanent loop conditions per URA,
. the number of permanent loop conditions for the whole set of
URAs.
• If the number of permanent loop conditions per URA or for the
exchange goes beyond the thresholds set by the MMC, the OM sets
off an alarm.
5.13.1 List of status
FXA : Subscriber in permanent loop condition or looped line.
FAUT : Presence of a diagnostic on the subscriber equipment (junctor).
BLOS : Blocked by the system (isolated subscriber board or
isolated CN).
-105-
CN
Set
Line
UT EQ
-106-
NE=...: List of subscriber equipment units of a UR defining the search field .
ND=...: Subscriber designation number for which the access status is
requested.
AFCT=..: List of subs. equipment units of a UR defining the search field .
STTUS=...:List of faulty status examined by the search. When STTUS is
present, either AFUR or AFCT must also be present.
NFAU=...: Maximum number of accesses to be output for each UR.
Default value: 50
EXAMPLE
@ABFASE;
CEN=1/99-05-14/11 H 30 MN 24/LISTING OF DEFECTIVE ACCESSES
PROCESSING TPSSER ACC
AFUR=002 TYPUR=URA NBEQPT=00997 NBFAU=00000 TFAU=000
AFUR=042 TYPUR=URA NBEQPT=00511 NBFAU=00002 TFAU=000
AFUR=050 TYPUR=URC NAC ----NBFAU=00002 (URA:00002 URC:00000)
PROCESSING TPSSER EXC
@AFUR=42+50+128:
PROCESSING TPSSER ACC
AFUR=042 TYPUR=URA NBEQPT=00511 NBFAU=00002 TFAU=000
NE =042-03-031 ND= 96444202 STATUS=FXA
NE =042-03-032 ND= 96444203 STATUS=FXA
AFUR=050 TYPUR=URC NBEQPT=00003 NBFAU=00001 TFAU=000
AFCT =050-2-12 ND= 96505212 STATUS=BLOJ
AFUR=128 TYPUR=URA NBEQPT=00511 NBFAU=00002 TFAU=000
NE =128-01-001 ND= 96702003 STATUS=QTI +DLAN
NE =128-04-012 ND= 96702012 STATUS=ALA
NE =128-04-018 ND= 96702018 STATUS=DTNR
NBDEF=00003 ----NBFAU=00005 (URA:00004 URC:00001)
PROCESSING TPSSER EXC
@AFUR=126+128,STTUS=DTNR:
PROCESSING TPSSER ACC
AFUR=126 TYPUR=URA NBEQPT=00511
NE =126-03-031 ND= 96126331 STATUS=DTNR
NE =126-07-001 ND= 96126701 STATUS=DTNR
AFUR=128 TYPUR=URA NBEQPT=00500
NE =128-01-001 ND= 96128100 STATUS=DTNR
NBDEF=00001 PROCESSING TPSSER EXC
@NE=126-00-100<126-03-127:
PROCESSING TPSSER ACC
AFUR=126 TYPUR=URA NBEQPT=01000
NE =126-00-123 ND= 96126123 STATUS=DTNR
NE =126-03-031 ND= 96126331 STATUS=DTNR
PROCESSING TPSSER EXC
@NE=128-00-100<128-03-127,STTUS=DTNR+QTD:
PROCESSING TPSSER ACC
AFUR=128 TYPUR=URA NBEQPT=01000
NE =128-00-123 ND= 96128123 STATUS=DTNR +QTD
NE =128-03-031 ND= 96128331 STATUS=DTNR NBDEF=0002
PROCESSING TPSSER EXC
-107-
@ND=96128123;
PROCESSING TPSSER ACC
AFUR=128 TYPUR=URA NBEQPT=01000
NE =128-00-123 ND= 96128123 STATUS=DTNR +QTD
PROCESSING TPSSER EXC
-108-
Secondary line : any line that is not a "head of group" is secondary. In the
secondary lines there are :
1) preferential lines : these directly called lines have their own types and
categories. Modifications on the operating of the group should not affect a
preferential line and vice versa.
2) Secondary lines : are "not directly called lines" that have their own types
but not their own categories. They automatically have the group's
categories.
Fig: Telephone Line Group
Group characteristics
Principal group (GX)
A principal group is a group of lines that are associated to the same
designation number.
It is thus defined by a NDG designation number and the list of lines that
compose it.
Priority group (GP)
A priority group is a group that is defined on lines that already belong to a
(GX) principal group.
-109-
It is possible to define several disconnected priority groups within the same
group.
Note : The line in the group that has the same directory number as the group
is called (NDG) head of group for a principal group and (NDP) for a priority
group.
Preferential line (LP)
A preferential line is a line in a (GX or GP) group that can be directly called
by a directory number of its own.
This line has its own categories and types.
Subgroup
A subgroup is a group of consecutive equipment units belonging to the same
UR.
Each group is made of a maximum of 15 subgroups.
Examples of a subgroup :
NE = 42 - 0 -67 < 69 1 subgroup,
NE = 42 - 0 - 90 1 subgroup,
NE = 42 - 0-126 < 42-1- 2 1 subgroup.
Search subgroups (SG)
When searching for free lines, the SPB or Mixed lines can be distributed into
two subgroups.
SG1 : a 1st choice subgroup,
SG2 : a 2nd choice subgroup.
Each subgroup itself is made up of subgroups (15 maximum).
Inside a subgroup, the first subgroup is selected according to a search law
called :
LOI1 in subgroup SG1,
LOI2 in subgroup SG2,
If LOI n = 0, the search is a cyclic search in all subgroups,
If LOI n = 1, the search is systematic, starting from the first subgroup.
A call towards the group's directory number sets off a search for a free line,
following the priorities within the subgroups. The search can only proceed to
the second group, if it exists, once the first subgroup has been totally and
unsuccessfully explored.
A priority group can also have two search subgroups provided there is no
intersection between the two subgroups of the principal group and those of
the priority group.
-110-
5.16 Traffic on URA
To search for a free line, the CSN receives : the No. of the first equipment
unit in the subgroup and the consecutive number of equipment units. If the
subgroups are made up of only one line, there is a risk of getting quite a few
messages in the public exchange to search for the next subgroup and then
address it.
So it is advisable to create search subgroups with fewer subgroups and rather
with consecutive lines. It is safer to select the last and the first equipment
numbers on two consecutive boards.
In the case of total occupancy, a transfer onto a recorded announcement is
possible.
-111-
Allotting categories to grouped lines
The rules for allotting categories to the lines are as follows :
• head of group : the categories allotted to this line are those of the
group (principal or priority).
• non preferential secondary line : the allotted categories are those of
the smallest group to which the line is directly associated (priority
group or by default the group itself).
• preferential secondary line : two cases are to be considered :
1) for an outgoing line, the allotted categories are those that belong
to the line,
2) for an incoming line, the categories are :
either the line's own categories, if it is called by its directory
number,
or the categories of the call's destination group if the line is
called by a group number.
Note(s) : or the categories of the call's destination group if the line is called
by a group number.
-112-
• builds a new search subgroup with the non SPA lines that were
added to the group or inserts these lines in a search subgroup that
already exists.
• if the LOI1 or LOI2 parameter is specified, a value is assigned to the
search law in SG1 (or 2).
• parameters : NDG, NSG, ND, NE, LOI, TAX, CAT, TY are output.
GLXRE : Removes lines from a principal group
Removes one or several line from a principal group; these lines become
single lines, with their own TY and CAT if they were preferential.
• the links between the lines to be removed and the group are cut,
• the links between the lines to be removed and the concerned
subgroups are cut, with the possibility of erasing the subgroups,
• the types that are specific to the removed lines are kept,
• implicit categories are assigned to the "not directly called lines" that
are removed,
• the categories which are specific to the directly called lines that were
removed are kept,
• NDG, NSG, ND, NE, LOI, TAX, CAT, TY parameters are output.
GLXSU : Deletion of a principal group
Removes all the lines of a GX, these lines become single lines with their own
TY and CAT if they were preferential.
• the group - group lines link is deleted.
• information related to the groups is deleted :
. categories,
. search subgroups.
• the types for each line are kept,
• the categories specific to directly called lines are kept,
• implicit categories are assigned to the not directly called lines,
• the ND, NE, NSG, LOI, CAT, TY and TAX parameters are output.
GPPCR : Creation of a priority group
Builds a priority group from lines that belong to a principal group and that
don't already belong to a priority group.
Creates information that marks the priority group :
• creates links between the priority group, the lines that compose it
and the preferential line that becomes the head of the priority group,
• assigns categories to the priority group,
-113-
• builds a 1st choice search subgroup,
• if the LOI1 parameter is specified, a value is assigned to the search
law in the SG,
• the NDG, NDP, ND, NE, NSG, LOI, TAX, CAT and TY parameters
are output
GLPAD : Addition of a line or lines to a priority group
Adds to a priority group one or several lines that belong to a principal group
but do not already belong to a priority group.
• connects the lines specified by ND, or NE or ACFT, to the priority
group defined by NDP,
• connects the lines specified by ND, or NE or ACFT, to the priority
group defined by NDP,
• added lines (non SPA) are inserted in an existing search subgroup or
a new search subgroup is created,
• if the LOI1 or LOI2 parameter is specified, a value is assigned to the
search law in SG1 or SG2,
• the NDG, NDP, ND, NE, NSG, LOI, TAX, CAT and TY parameters
are output.
GLPRE : Removes line(s) from a priority group
Removes lines from a GP, these lines remain assigned to the principal group.
• the links between the lines to be removed and the priority group are
cut,
• the links between the lines to be removed and the concerned search
subgroups are cut. A priority subgroup can be erased,
• the links between the removed lines and the principal group are kept,
• the removed lines keep their type,
• the directly called lines that are removed keep their own categories,
• the non SPA lines that are removed still belong to the subgroups of
the principal group,
• the parameters NDG, NDP, ND, NE, NSG, LOI, TAX, TY and CAT
are output.
GPPSU : Deletion of a priority group
Removes all the lines of a priority group . These lines remain assigned to the
principal group and the line that is the head of the priority group becomes the
preferential line in the principal group, with the CATs of the group that was
deleted.
• The links : priority group - lines of this group are deleted,
-114-
• the following information related to the priority group is deleted :
. priority group categories,
. search subgroups.
• search subgroups :
. keeps its own type,
. keeps its own categories if the line is a directly called line,
the non SPA lines still belong to the search subgroups of the
principal group.
• the links existing between the lines coming from the priority group
and the principal group are kept,
• the parameters NDP, ND, NE, NSG, LOI, CAT, TY and TAX are
output.
5.18 Supplementary services offered to analog & digital subscriber lines List of
supplementary services offered to digital subscriber lines:
- freephone line(CAT=LST),
- advice of charge at end of call(CAT=IDT,IDC),
- essential line(TY=LSS),
- line with itemized billing(CAT=FDn),
- malicious call identification(CAT=IAM+CAMn),
- call waiting, accompanied by an announcement while the waiting call is be
presented,
- three-party conference(CAT=COF),
- variable call forwarding unconditional(CAT=RVFT),
- variable call forwarding on busy(CAT=RVFO),
- variable call forwarding on no reply(CAT=RFNR),
- fixed call forwarding unconditional(CAT=RVT),
- fixed call forwarding on busy(CAT=RVO),
- fixed call forwarding on no reply(CAT=DNR),
- call forwarding to an international number(CAT=RAIN),
- fixed barring of outgoing calls(TY=SRn),
- user-controlled barring of outgoing calls(CAT=SRC),
- calling line identification presentation(CAT=DIPA,TY=DSM or DTMF),
- calling line identification restriction(CAT=SIDR),
- call completion to busy subscriber(CAT=SRS,DROC),
- Connected line identification presentation(CAT=COLP),
- Connected line identification restriction(CAT=COLR),
- Anonymous call rejection(CAT=ACRJ),
- Customised ringing(CAT=SONn),
- Call hold(CAT=DMG)
- Explicit call transfer(CAT=ECT)
- Call waiting(CAT=IAI)
- Hotline(CAT=LAI,LAT)
-115-
- Abbreviated dialling(CAT=NAn),
- barring of incoming calls(CAT=SRAn),
- closed user groups(CAT=GFU),
- Line with telecharging(TY=TTX,TTXN),
- Registered call(CAT=AEN)
- Dedicated line(TY=SPA,SPB)
- User to user signalling(CAT=DIU),
- subscriber-based carrier selection(CAT=TRAi,TRBj,TRCk),
- terminal portability during a call.
Some facility which requires activation and deactivation can be
activated/deactivated either by commands or by codes defined in REDA.e.g.
call transfer on busy facility (CAT=RVO)can be activated by command
@RVTAC:
@ ND= ,NAR= ,TYPE=3;
or by using code 141.
(Note: for facility activation/deactivation codes refer to REDA.)
5.19 CENTREX
Introduction Centrex is a virtual PABX system designed for office application .It
is cheaper than managing a PABX system .The centrex function allows, grouping
the subscribers by business groups (companies). A centrex company is an
administrative entity comprising a set of private lines connected to the same
exchange. For Out-of-Centrex calls subscriber has to dial a short access code.
Centrex subscribers are connected to the exchange in the same way as public
subscribers, thus in addition to being a Centrex subscriber they have the advantage
that they can access all other subscriber features available in the exchange. Also
subscribers belonging to a Centrex group could be geographically OCB
subscribers located far apart, the only limitation being that they should belong to
the same exchange. Also this allow them to access all other types of networks
(international, mobile, etc.)
Centrex Types
An exchange supporting the Centrex function can be organised with or
without number blocks.On an exchange features without number blocks cannot
coexist with features with number blocks.
Internal Dialing
The internal numbering scheme of centrex companies with blocks can be
of 2 to 4 digits length, depending on the size of the company. This ‘internal
dialing plan’ could be integrated into the numbering scheme of the public network
i.e. the digits of the internal number are the last digits of the PSTN number of the
subscriber. This makes it possible to provide Centrex subscribers with the DDI
(Direct Dialing In) facility. The Centrex subscriber could be allowed the access to
the public network by means of a simple access code.
-116-
Capacity
• Number of Centrex subscribers : Any number within the limits of the
Exchange traffic and the connection capacity of the exchange
• Number of centrex companies: 1023 maximum.
• Number of Blocks possible per centrex company : 8 blocks
• Number of subscribers per centrex company : 9000 maximum
• Internal Numbering: 2 to 4 digits.
• Attendant Position : Either Analog or Digital attendant position is possible
- Analog attendant position: 1 per company (could be a single line or line
group).
- ISDN attendant position : 1 ISDN access per company
• Alarm/ reminder call : maximum 600 total reminders , 300 per 5-minute
period
-117-
-118-