50 TMSS 03 R0
50 TMSS 03 R0
50 TMSS 03 R0
50-TMSS-03, Rev. 0
PAGE NO. 2 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
TABLE OF CONTENTS
1.0 SCOPE
2.0 CROSS REFERENCES
3.0 APPLICABLE CODES AND STANDARDS
4.0 DESIGN AND CONSTRUCTION REQUIREMENTS
4.1 Ratings
4.2 Construction
4.3 Grounding
4.4 Nameplate
5.0 TESTS
5.1 Type ( Design ) Tests
5.2 Routine ( Production ) Tests
6.0 DATA SCHEDULE
TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-03, Rev. 0
PAGE NO. 3 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
1.0 SCOPE
This SEC Transmission Material Standard Specification (TMSS) specifies the minimum
technical requirements for design, engineering, manufacture, inspection, testing and
performance of outdoor/indoor free standing inductive potential transformer, 33kV through
380 kV, intended to be used in the system of the Saudi Electricity Company, Saudi Arabia.
2.0 CROSS REFERENCES
This Material Standard Specification shall always be read in conjunction with SEC General
Specification No. 01-TMSS-01, titled "General Requirements for All Equipment/Materials",
which shall be considered as an integral part of this TMSS.
This TMSS shall also be read in conjunction with SEC Purchase Order or Contract
Schedules for project, as applicable.
3.0 APPLICABLE CODES AND STANDARDS
The latest revision/amendments of the following Codes and Standards shall be applicable for
the equipment/material covered in this TMSS. In case of conflict, the vendor/manufacturer
may propose equipment/material conforming to one group of Industry Codes and Standards
quoted hereunder without jeopardizing the requirements of this TMSS.
3.1 IEC 60044-2 Inductive Voltage Transformers
3.2 IEC 62155 Hollow pressurized and unpressurized ceramic and glass
Insulators for use in electrical equipment with rated voltages
greater than 1000 V.
3.3 IEC 60529 Degree of Protection Provided By Enclosures
3.4 IEC 60836 Specifications for silicone liquids for electrical purposes
3.5 IEEE C57.13 IEEE Standard Requirements for Instrument Transformers
3.6 IEEE C57.13.5 IEEE Trial-Use Standard of Performance and Test
requirements for Instrument Transformers of a Nominal
System Voltage of 115 kV and Above
3.7 ASTM D 4652 Standard Specification for Silicone Fluid Used for Electrical
Insulation.
3.8 54-TMSS-01 Mineral Insulating Oil for Electrical Apparatus.
TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-03, Rev. 0
PAGE NO. 4 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
4.0 DESIGN AND CONSTRUCTION REQUIREMENTS
4.1 Ratings
4.1.1 The burden indicated in the data schedule is the minimum
requirement.Unless otherwise specified in the Data Schedule, minimum
burden of each secondary winding shall be 100 VA. Final burden shall be
based on calculation for the intended application.
4.1.2 PT Connection and Voltage Rating
a. PT connection shall be single phase line to ground type or three phase
type as specified in the Data Schedule.
b. The specific voltage rating shall be as specified in the Data Schedule.
c. Secondary nominal voltage shall be 115/3V or 110/3V or as specified
in the data schedule.
4.1.3 Accuracy
a. Unless otherwise specified, the metering accuracy class at 60 Hz shall be
0.3 per IEEE or 0.5 as per IEC.
b. Unless otherwise specified, the protection accuracy class at 60Hz shall be
1.2R per IEEE or 3P per IEC.
c. When specified in the data schedule dual accuracy class shall be provided
to suite both metering and protection.
4.1.4 Rated Voltage Factor
Unless otherwise specified in the data schedule rated voltage factor shall
per IEC 60044 2.
4.2 Construction
4.2.1 General
a. Type of PT for different voltage class and indoor/outdoor installations
shall be as per Table-1.
b. The PTs shall be hermatically sealed.The lower part of the PTs shall
consist of a steel tank with secondary terminal compartment, ground
terminal (on the case or on the mounting base).The upper part of the
transformer shall consist of a porcelain housing, top cap and cover
assembly with a primary terminal, an expansion tank and oil/liquid filled
indicator.The transformer shall be supplied with lifting lugs.
TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-03, Rev. 0
PAGE NO. 5 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
4.2.2 Insulating Oil
a. PTs shall be filled with mineral insulating oil / liquid silicone as
mentioned in Table -1 .
b. The insulating oil shall be PCB free.
c. The mineral insulating oil shall conform to 54-TMSS-01 .
Table I
Voltage
Class
Installation
Indoor/Outdoor
Type of PT
33/34.5 kV Outdoor Mineral Oil
69 kV Indoor
Non-
Flammable,Porcelain
Insulated
(Silicone) Liquid
Filled Type
69 , 110,115, 132 & 380 kV Outdoor Mineral Oil Filled
d. Silicone Liquid filled shall be polydimethylsiloxane oil or silicone
liquid as per Table I of ASTM D-4652 or type T-1 per IEC 60836
standard.
4.2.3 Insulator Housing
a. Outdoor insulator housing shall be electrical grade ,wet processed
porcelein of brown color conforming to IEC 60137 standard.
b. Indoor insulator housing shall be either porcelain or silicone rubber
type for PTs provided with silicone insulating liquid, otherwise it
shall be cast resin per Table I.
c. Outdoor insulator housing shall withstand a washing pressure of
3500 kPa without permitting water ingress into internal of PTs or
secondary terminal box of PTs.
4.2.4 Terminals
a. The primary terminals shall be round or flat studs made of non-
corrodible material and shall be suitable for copper or aluminium
connectors as specified in the data schedule.
b. The secondary terminals shall accept a copper wire size of 2.5mm2
minimum .Removable cable gland plate shall be provided on the
terminal box.
TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-03, Rev. 0
PAGE NO. 6 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
c. The degree of protection of enclosures for secondary terminal box
shall be per 01-TMSS-01.
d. Primary and secondary terminals and polarity shall be marked as per
applicable standards.
4.2.5 Protection of Secondary
PT secondary circuit shall be protected by Miniature Circuit Breakers
(MCBs) or fuses as specified in the data schedule .Separate Terminals shall
be provided for PT-fuse supervision or MCB tripped signal as applicable.
4.3 Grounding
The PT shall be provided with grounding terminal sized to accommodate bare copper
conductor of size 1x240mm
2
for station fault current level upto 40kA and 2x240mm
2
for station fault current levels above 40kA.
4.4 Nameplate
The nameplate to be provided shall be :
4.4.1 Written in English containing the information listed in IEEE C57.13 or in
IEC 60044-2 plus additional information as follows:
a. The words kV Potential Transformer
b. SEC Purchase Order Number and Contract No./Job Order No.
c. Design Ambient Temperature
d. 50-TMSS-03, Rev.0.
4.4.2 The Name Plate shall be of stainless steel fastened to the equipment by
stainless screws or rivets.
5.0 TESTS
All test results shall be provided for review and acceptance
5.1 Type (Design) Tests
5.1.1 All type(design) tests described in the relevant IEC or equivalent IEEE
standards shall be performed on the representative unit or on the first unit of
every new design or rating to be supplied.
5.1.2 Chopped impulse test shall be carried out additionally for all PTs
manufactured per IEC standard.
TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-03, Rev. 0
PAGE NO. 7 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
5.1.3 For PTs manufactured per IEEE standards all type tests per IEEE C57.13
shall be carried out . In addition switching impulse and RIV test per IEEE
C57.13.5 shall be performed. Test methods for all type tests per IEEE shall
be per C57.13.5 only.
5.1.4 In lieu of the actual type (design) tests ,certified test reports of type (design)
tests performed on an identical unit may be submitted for review and
approval during the bidding stage.
5.1.5 If PT is manufactured as per ANSI/IEEE standard then partial discharge test
shall be carried out as a routine test.
5.2 Routine ( Production ) Tests
5.2.1 All routine (production) tests prescribed in the relevant IEC or equivalent
IEEE standard shall be performed on all potential transformers.
.
TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-03, Rev. 0
PAGE NO. 8 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
6.0 DATA SCHEDULE
POTENTIAL TRANSFORMER (PT) 33KV THROUGH 380KV
SEC Enquiry No. Date:
SEC Purchase Order
No.
Date:
or Contract No.
SEC PTS No./Project Title with J.O. No.
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Nominal System Voltage (kV)
(33/34.5/69/110/115/132/380)
System Short Circuit Current(kA
sym.)at rated system voltage
(Single Phase to Ground)
Type of System Grounding
Installation ( Outdoor/Indoor)
'A'- SEC SPECIFIED DATA/PARAMETER.
'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS.
'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'.
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'.
TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-03, Rev. 0
PAGE NO. 9 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
6.0 DATA SCHEDULE
POTENTIAL TRANSFORMER (PT) 33KV THROUGH 380KV
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
3.0 APPLICABLE CODES AND STANDARDS
Applicable Industry Standard *
4.0 DESIGN AND CONSTRUCTION REQUIREMENTS
4.1 Ratings
Maximum Rated Primary Voltage
(kV rms) (Phase to Ground)
Rated Voltage Factor
Rated Secondary Voltage ( V rms)
( Nominal)
Secondary 1
Secondary 2
Any tap required on Secondary -1
or Secondary -2 winding Yes /No
If Yes, What is the tap voltage?
Secondary -1 ( V rms)
Secondary -2 ( V rms)
Rated burden ( VA )
Secondary 1
Secondary 2
Continous Thermal Burden ( VA )
Type of insulation (Liquid/Solid)
Maximum Partial Discharge Level
Phase to earth (pc)
@ maximum rated voltage *
@1.2 x max.rated voltage / 3 *
TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-03, Rev. 0
PAGE NO. 10 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
6.0 DATA SCHEDULE
POTENTIAL TRANSFORMER (PT) 33KV THROUGH 380KV
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.1 Ratings (Continued)
Maximum Radio Influence Voltage(RIV)
(applicable only for 115 & 132 kV outdoor
PTs) at 1.1 x maximum rated voltage/3
2500 V
Winding Insulation and class *
Winding Material (Al or Cu) *
BIL of Winding (kV peak) *
Power Frequency Withstand Voltage of
Winding (kV rms)
*
Accuracy class:
Secondary 1
Secondary 2
4.2 Construction
Type of PT ( Mineral Oil filled/silicone
liquid filled)
3-phase type or Single Phase type
Manufacturers type designation *
Country of Manufacture *
4.2.2.
( c )
Insulating Oil
[Refer to Data Schedule of 54-TMSS-01.
Vendor to fill in column B of the same]
4.2.2.
( d )
Silicone Liquid
Applicable Standard
IEC
60836
ASTM
D4652
Color (Max.) 35 15
TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-03, Rev. 0
PAGE NO. 11 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
6.0 DATA SCHEDULE
POTENTIAL TRANSFORMER (PT) 33KV THROUGH 380KV
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.2.
( d )
Silicone Liquid (Continued)
Applicable Standard
IEC
60836
ASTM
D4652
Appearance * *
Viscosity Max. at 40
0
C (mm
2
/s)
40+ 4 39
Flash point, Min .(
0
C) 240 300
Pour point, Max (
0
C) - 50 -50
Density at 20 (
0
C) (
kg/dm
3
)
0.955
to 0.970
*
Dissipation Factor tan
at 60 Hz @
25 C * 0.01
90
C 0.0012 *
Dielectric breakdown
voltage at 60
Hz,Min.(kV)
40 35
Neutralization value
max (mg KOH/g)
0.02 0.01
Water content (ppm) 50 50
PCB content * *
4.2.3 High Voltage Insulator Housing
Name of Manufacturer *
Type (Porcelain/Silicon Rubber)
Rated Voltage (Nominal, kV rms) *
TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-03, Rev. 0
PAGE NO. 12 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
6.0 DATA SCHEDULE
POTENTIAL TRANSFORMER (PT) 33KV THROUGH 380KV
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.3 High Voltage Insulator Housing (Cont.)
BIL (kV peak)
Power frequency Withstand Voltage:
(Wet Withstand applicable for Outdoor
Housings only)
1 minute dry (kV rms) *
10 sec. wet (kV rms) *
Creepage Distance (mm) *
Color *
Cantilever Strength(kg) *
4.2.4 Terminals
Primary Terminal Connector:
For Conductor Material (Al or Cu)
Size (mm
2
)
Number of Conductor/phase
Degree of protection of enclosure for
secondary terminal box
*
4.2.5 Protection of Secondary
PT secondary MCB/fuse rating(A)
4.4 PT Overall Dimensions (mm) *
Weight(Kg)
5.0 TESTS
Optional or Special Test Requirements (if
any)
TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-03, Rev. 0
PAGE NO. 13 OF 13 50TMSS03R0/J SG
Date of Approval: August 28, 2006
6.0 DATA SCHEDULE
POTENTIAL TRANSFORMER (PT) 33KV THROUGH 380KV
ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY
SEC:
A.
ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY
BIDDER/VENDOR/SUPPLIER/CONTRACTOR:
B.
OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/
CONTRACTOR:
B.
Actual Manufacturer
of Equipment/Material
Vendor/Supplier/
Contractor
Name of the Company
Location and address
Name and Signature of
authorized
Representative
and date
Official Seal/Stamp
of the Company &
Date