Pid Feature Profile
Pid Feature Profile
now available with NuFlo Scanner 2000 microEFM and NuFlo Scanner 2200 EFM
Scanner Solution
The integrated PID control of the Scanner 2000 and Scanner 2200 and the configuration and tuning controls built into the ModWorX Pro software provide a powerful solution for a variety of control applications. The control valve position is regulated via a 4-20 mA output, as shown in the illustration below. The analog output is standard on the Scanner 2200, and is available on an optional expansion board for the Scanner 2000. When purchased with the PID control option, the Scanner can be used to control parameters such as static pressure (from integrated MVT or external analog input) differential pressure (from integrated MVT or external analog input) temperature (from integrated RTD or external analog input) flow rate (mass, volume or energy) based on a DP or turbine input
The tuning values selected for the controller will determine if the process control is effective and stable. All installations must be tuned and this task is nearly impossible by observing numeric values alone. Competitive products often require that the user observe the mechanical movement of the control valve indicator in response to an upset condition to validate the tuning process. In many installations, this is a twoperson job. Without a partner to validate the valves movement, an operators tuning success may be marginal. The tuning tools within ModWorX Pro eliminate the need for a partner to monitor the valve indicator. The software plots the process variable, setpoint and valve position in an easy-to-read, scaleable graph and updates the output in realtime so a single operator can monitor the impact of every tuning change and determine when an optimum response is achieved. Important: Operators must configure and tune PID control settings to operate in accordance with their specific application. As with any automated control system, operators are advised to take safety precautions to guard against control changes that could cause personal injury or property damage.
H L
RTD assembly
H L
ModWorX Pro
ModWorX Pro, the software interface for the Scanner 2000 and Scanner 2200 , allows the user to configure, tune and maintain a PID controller. When ModWorX Pro is used to connect to a PIDenabled Scanner, the Configuration menu will include a PID Control button in the Outputs section of the screen. This button opens a dialog that guides a user through the configuration of the PID controller. A Manage PID button also appears at the top of the main screen. This button opens a maintenance dialog which allows the user to change the control mode and control setpoint only. All other configuration settings are protected, if security settings are enabled. To configure a controller, the user selects the control method to be used, mode of operation, the process parameter to control, and the range of operation required for the control parameter. Then, using the tuning dialog, the user can change the tuning parameters and observe the system response. The user can switch between manual and automatic operating modes and observe the systems response to changes in valve position and the controllers response to changes in tuning values. A user can even view the progression of the controller response in a time-scale graph and pause the graph as necessary to make tuning adjustments.
When configured with the second method, the Scanner can provide flow rate control and maintain static pressure below a user-configured setpoint. This is essential for industrial applications that require monitoring of two process variables and the flexibility to switch from one to the other as the primary control parameter. For example, when a new gas well or zone is introduced in a field of old wells, the new well often produces at a higher pressure and delivers a higher volume of gas than the old wells. If the new well is tied into an existing production facility, it will dominate and prevent the old wells from flowing into the production system. The new well may also have a shut-in pressure that exceeds the older production system. To limit the flow and the pressure, a single control valve is installed. In this example, the user would configure the Scanner for PID with secondary pressure control. The user would enter two setpoints, one for the flow rate desired and one for the maximum pressure desired. The Scanner would control the valve in accordance with the flow rate setpoint until the pressure reached its limit, at which time the controller would throttle the valve to quickly bring the pressure back to the acceptable range. Once the pressure is in check, the controller would transition back to flow control. Unlike the primary controller that is used to control flow in accordance with a fixed setpoint, the secondary pressure controller does not require a balance of gain and integral values. Because the secondary controller is concerned only with reducing pressure quickly, gain is the only tuning value required.
The following examples show how valve configuration can affect the action setting. In both cases, the process is designed such that when the valve opens, the process value will decrease. In the first example, an increased output is required to actuate a fail close valve. In the second example, a decreased output is required to actuate a fail open valve. With the proper action setting, either valve configuration can be used to achieve the desired result.
Direct Acting
The control valve will fail in the closed position. An increased controller output opens the valve, and decreases the process value. In this example, the error is initially positive (PV - SP>0). The positive error is counteracted by an increased controller output; therefore, this controller is direct-acting.
SETPOINT
SCANNER 2000 CONTROLLER
INCREASED OUTPUT
CONTROL VALVE
FAIL CLOSE
VALVE OPENS
PROCESS VARIABLE
Reverse Acting
The control valve will fail in the open position. A decreased controller output opens the valve and decreases the process value. In this example, the error is initially positive (PV - SP>0). The positive error is counteracted by a decreased controller output; therefore, this controller is reverse-acting.
SCANNER 2000 CONTROLLER
SETPOINT
DECREASED OUTPUT
CONTROL VALVE
FAIL OPEN
VALVE OPENS
PROCESS VARIABLE
The setpoint and valve position can be changed two ways: by moving the slider bar or by entering a value in the field below the bar. Changes will not become effective until you press Apply.
Caution: Before performing a 4-20 mA calibration or test, verify that the position of the automated valve or control is as desired for continued operations and disable the controlled device if necessary. Calibrating and testing the 4-20 mA output with peripheral equipment in operation may change the position of the valve, causing false alarms or unexpected changes in operations.
4-to-20 mA Calibration
To calibrate the analog output, navigate to the Configure Analog Output screen perform the following steps: 1. Under New Output Calibration, click on the 4 mA Setting button to send a 4 mA signal to the receiving device. 2. Enter the output value as read by the receiving device, in the Zero Adjustment screen and click OK. The adjustment will appear in the Active Output Calibration section. Click Apply. 3. Repeat the steps for the 20 mA setting.
4-to-20 mA Testing
To test the analog output following adjustments, click the Test Output button at the bottom of the Configure Analog Output screen. A Test Analog Output dialog box will appear. Enter the output value (in milliamps) you wish to apply and click Apply. The Scanner will send the signal to the receiving device. If everything in the loop is properly connected and calibrated, the readout of the receiving device should match the test value entered in the Test Analog Output screen.
10
11
5569.0501
ms-kl@c-a-m.com
INDIA KENYA