Transformer Design
Transformer Design
Transformer Design
430 50 3 connection= Type: Tappings: Temperature rise: %impedance= CALCULATIONS: Taking value of k, for distribution transformers as: Voltage per turn : therefore flux in core is: Taking the flux density as: Thus the iron area required is: Take stacking factor (for cold rolled grain oriented steel) Gross iron Area available is: k= 0.45 Delta-Star Core type, Distribution 2.5% - 5% <=40 deg < 5%
KV V Hz
Ag=
0.04130169 m^2
CORE DESIGN: Per phase primary: Per phasesecondary: Voltage: Current: Voltage: Current: V(H.V)ph= I(H.V)ph= V(L.V)ph= I(L.V)ph= k1= 11000 30.3030303 248.260616 1342.67504 0.92 Actual 0.23908072 m 0.22951749 0.21158643 0.18528756 0.15085993 0.11117253 0.05977018 m m m m m m Taken 240 230 212 186 151 112 60 KV A KV A
d= a= b= c= d= e= f=
mm mm mm mm mm mm mm
Modified values of
Take Window space Factor as: Selecting Current Density: Window area required by Output Equation: Selecting Height to Width Ratio as: Window Height: Window Width: Distance Between Limbs; Taking the Yoke also to be 6 stepped: Height of yoke: Depth Of Yoke:
0.3 2.75 A/mm^2 0.11357226 m^2 2.5 0.53285144 m @ 0.21314057 m @ 455 mm 530 215 mm mm
Hy= Dpth=
230 230
mm mm
H= W=
990 1150
mm mm
WINDING DESIGN: Actual 5% tap Integral value Taken 773.001206 811.6513 819 17.4459778 18
T(H.V)= T(L.V)=
Area of conductors:
H.V: L.V:
ah= al=
L.V WINDING DESIGN: Taking Stranded Conductors: Area per Strand is: Strands= a= 15 32.5496981 mm^2
Selecting a Double Helical Winding , Taking the distribution of each L.V Conductor as: 5 Vertical and 3 horizontal,(Rectangular Conductor) From the Conductor Size data sheet: Dimensions of each Strand is the per strand area is 32.1mm^2,thus modified value of current density: h= w= d'= 6 5.5 mm mm
2.78852553 A/mm^2
Taking 0.25mm insulation all over Dimension of each strand is: Therefore Conductor Size is:
6.5 6 32.5 18
mm mm mm mm
9 conductors per layer for a total of 18 conductors, taking 2mm for duct between the 2 layers: Taking space between conductors for cooling as: sp= Total Winding Height:= Total Winding Width:= H= W= 20 452.5 38 mm mm mm
Taking 5mm clearance for bakelite former between lv and the core: inner diameter of L.V Winding: outer diameter of L.V Winding: Length of mean turn is din= 250 dout= 326 Lmt(h.v)= 904.7808 H.V WINDING DESIGN: The H.V Winding design is done using the cross over winding using rectangular conductors. A total of 819 turns are accomodated using 13 coils and 7 coils per layer. Each coil consists of 9 horizontal winding turns.Thus total turns=7*13*9=819. voltage per coil is: the area of each conductor is 10.9mm^2 thus, modified value of current density: Dimensions for each conductor V/coil= d'= h= w= h'= w'= hc= wc= 846.153846 V mm mm mm
Thus,
using inter coil spacing of 5.5mm and inter layer(horizontal)spacing of 1mm Winding Height= H= W= 457.3 39.5 12 350 429 mm mm mm mm mm mm
Taking the clearance between H.V and L.V as: a= inner diameter of H.V Winding: outer diameter of H.V Winding: Length of mean turn is din= dout=
Lmt(h.v)= 1223.6532
H.V: L.V:
1.8026211
REACTANCE: Average mean turn is: Average Height of Winding: Ratio of Lmt/Lc is value of reactance is: p.u value of reactance: Net impedance is: p.u value of impedance is: Lmt(avg) Lc= Ratio= X= Xp.u= Z= Z(p.u)= 1064.217 454.9 2.33945263 20.8789598 W 0.0575178 20.9028936 W 0.05758373 mm mm
REGULATION: at 0.8 pf full load regulation is: at upf full load the regulation is: Reg(p.u)= 0.04151415 Reg(p.u)= 0.00875434
LOSSES AND EFFICIENCY: IRON LOSSES: From the loss graph of the crgo grade 56 loss curves, Loss per unit volume is now total fluxpath length is: volume of the iron parts: Taking density of grade 56 crgo is: Total mass of the iron parts is: thus total iron loss is: Loss/vol= 1.42 L= volume= s= M= Pi= W/kg
Pc=
8754.3351
thus %full load at max efficiency is and efficiency at 0.8pf is: upf is:
x= h= h=
MAGNETIZATION CHARACTERISTICS: Total iron losses= Pi= 1806.841 0.05475276 110 453.2 AT AT W
Thus the loss component of no load current is: Il= now the mmf/meter for iron is: Total mmf required is taking atotal of 0.05mm air gap per joint Total airgap length is: mmf required for the air gap is: Total mmf Required is the magnetizing current per phase is: thus the no load current is: Ati/m= Ati=
0.3
mm
OVERALL TANK DIMENSIONS AND VOLUME: Taking the basic clearances of: b= l= h= W= L= H= V= 50 80 300 1439 589 1290 1.131 mm mm mm mm mm mm m^3 1450 600 1300 mm mm mm
thus total volume of tank is: for calculation of copper volume: volume of lv winding: volume of hv winding: Thus total copper volume is total iron volume is thus volume of oil in transformer (including radiators is:)
0.01555771 m^3 0.02210328 m^3 0.11298295 m^3 0.16632984 m^3 1.34667402 m^3
CONSERVATOR DESIGN: Volume of conservator is taken . as 10% of oil in tank and radiators thus taking length to diameter ratio as: V(cons)= R= D= L= 0.1346674 m^3
DESIGN OF COOLING ARRANGEMENTS (RADIATORS): Value of thermal coefficient at 75 deg c is Temperature rise limits specified: Total Watts dissipating from surface for the requisite temperature rise is: Surface Area of Tank is: Total Watts that are dissipated from the tank walls naturaly is= Thus the total watts required to be dissipated by radiators is Taking height of radiators as: thus the watts per section for this height and temperature is: thus no of section required is now the values of spacing constants are: C= q= W/m^2= 12.5 40 500 W/(m^2-degC) degC W/m^2
St=
5.33
m^2
Diss= Rdwats=
2665 7896.1761
W W
Hrad=
1200
mm
sections= 53.2370564 56
Thus we select 56 elliptical Radiator sections in total of 6 Radiators,with 7 sections per radiator. Thus Radiator section dimensions are: h= w= l= 1200 300 25 50 A= V= Vnet= mm mm mm mm
Horizontal distance between each Section is: vertical surface area of each radiator is: Volume of each radiator= Net Volume of all Radiators
TRANSFORMER DESIGN
KVA= 25000 Vp(line)= 33 Vs(line)= 6.9 frequency= 50 phase= 3 transportation height=3.5m load loss= 20 no load loss= 110 load loss capitalization= load loss capitalization= Bmax= 1.7 tesla current density= 3 width of conductor= 17<x<6 ratio= 2>y>7 specific loss= 1.2 copper rate= 425 iron rate= 180
KVA KV KV Hz
KW KW 1 lakh/KW 5 lakh A/mm2 thickness of conductor= stacking factor= KW/Kg Rs./Kg Rs./Kg CALCULATIONS 4<x<1.5 0.9
Vhv= Vlv=
19.05255888 KV 6.9 KV
Current in HV & LV Current in HV: current in LV: Iph(hv)= Iph(lv)= Core area assuming diameter: core area: D= A= 440 mm 136847.776 mm2 437.3865676 1207.729469
No. of turns in HV & LV HV no. of turns: LV no.of turns N(hv)= N(lv)= 133.6009207 368.9042622 332.1 405.9 134 369 333 406
Height of core structure assuming height of core structure 2500 mm. H= 2500 mm height of core window: H(window)= 1620 mm height of winding: H(wdg)= 1470 mm Design of HV winding using Disc winding. assuming No. of turns/disc=
T(hv)= Discs=
123
width of HV conductor:w(hv)= assuming current density: area of conductor: a(hv)= assuming thickness: No. of parallel paths: paths=
Design of LV conductor area of conductor: a(lv)= width of LV conuctor: w(lv)= assuming thickness: No. of parallel paths: paths= 483.0917874 7.670149254 2.5 25.19334482 26
Design of Tapping winding winding turns: T(tap)= assuming no. of turns per discs: No. of discs: Discs= actual no. of discs: Discs= ht of tapping winding: ht(tap)= 73 3 24.33333333 28 964.6875
25
Calculation of %Z width of air gap btwn core & LV: width of air gap btwn LV & HV: width of air gap btwn HV & tap: width of LV winding: Inner Dia for LV: mean dia of LV: width of HV winding: Inner Dia of HV: mean dia of HV: T1= ID(lv)= D1= T2= ID(hv)= D2= Tg= Tg1= Tg2= 78 470 587 71.46 656 763.19 23.82 818.92 854.65 626 661.73 798.92 813.92 45516.09745 mm2 455.1609745 15 mm 15 mm 10 mm
width of Tapping wdg T3= Inner Dia of Tapping: ID(tap): mean dia of Tapping: D3= ID for air gap btwn HV-LV: mean diameter Dg1= ID for air gap btwn HV-Tap: mean diameter: Dg2= summation ATD: ATD=
Rogowski Factor:
Kr= Heq=
Width of core width of transformer: W(core)= Volume of core volume of 3 limbs: volume of 2 yokes: total volume of core: vlm(limb)= 738977990.3 vlm(yoke)= 736777185.3 total= Core loss Weight of core: No load loss: wt= core loss= 11289.52709 18.06324335 KW 1475755176 2536.76
Copper loss mean dia of LV: mean dia of HV: mean dia of Tap: d(lv)= d(hv)= d(tap)= 548 mm 727.46 mm 842.74 mm 1721.592774 2285.382992 2647.545793 483.0917874 mm2 174.954627 mm2 230693.4317 mm2 843306.324 mm2 74131.2822 mm2 0.009550708 0.09640286 0.008474344 41.79228836 KW 56.94720892 KW
mean length turn LV: Lmt(lv)= mean length turn HV: Lmt(hv)= mean length turn Tap: Lmt(tap)= area of conductor LV: a(lv)= area of conductor HV: a(hv)= length of LV: length of HV: length of Tap: resistance LV: resistance HV: resistance Tap: Copper loss in LV: l(lv)= l(hv)= l(tap)= Rlv= Rhv= Rtap= loss(lv)=
116.8027406