Breaker Failure Relay 7SV60
Breaker Failure Relay 7SV60
Breaker Failure Relay 7SV60
1. Introduction
In this application example, the 7VH600 relay will be applied for breaker fail protection of the HV side breaker of a transformer bay. External trip signals and breaker status signals will be applied. The breaker fail protection will be two-stage with re-trip of the protected breaker followed by a trip to the surrounding breakers.
The breaker fail relay must provide the redundant trip (re-trip) of the HV circuit breaker without time delay, and in the event of a breaker fail condition follow up with a Bus Trip command that trips the adjacent breakers. The routing of the Bus Trip in accordance with the isolator switching state will be done by the Busbar Protection which includes the required isolator replica. [Siemens busbar protection systems, e.g.7SS52, have binary input signals that provide for the coupling of the Bus Trip from external breaker fail relays.
The main protection functions route their trip signals directly to the relevant circuit breakers as well as signaling the trip command to the breaker fail relay. In this example the breaker fail relay is used for an immediate re-trip command to the monitored breaker (trip coil 2). This provides a redundant path for the trip command to the circuit breaker and also ensures that the breaker fail protection always first trips the monitored breaker before, after the monitoring time delay, the Bus Trip signal can be issued. If for example due to a testing or other failure the breaker fail relay is accidentally initiated (simulated protection trip) the breaker fail relay will only trip the protected feeder and then reset when the current via the CT goes to zero. An incorrect bus trip due to such a contingency in the substation is therefore avoided. Bucholz protection trip input is connected separately because this protection function is not associated with a short circuit current measurement. Here the circuit breaker auxiliary contacts will be monitored to obtain confirmation that the circuit breaker opened correctly.
6.1.
Configuration
Depending on the version (MLFB) of the 7SV600, settings in the Configuration must be applied. INTEGRATED OPERATION 7800 SCOPE OF FUNCTIONS Address Function Value 7816 Breaker Failure Protection Three-pole For this application three pole tripping must be applied as shown above for Address 7816. The other settings in the Configuration are not relevant to the protection functions covered in this application example and may be set according to the users specific requirements.
6.2.
The 3 binary inputs of the 7SV600 must be assigned as described above under Heading 4 Allocation of the binary input signals. MARSHALLING 6101 MARSHALLING OF BINARY INPUT 1 Address Function Value 6102 BINARY INPUT 1 1st FUNCTION 001 7703 > BF external start 3-pole Active with voltage The first binary input will be used for the 3 pole trip signal from the transformer main protection, it is assigned as shown above to 7703 >BF external start 3-pole. MARSHALLING 6122 MARSHALLING OF BINARY INPUT 2 Address Function Value 6123 BINARY INPUT 2 1st FUNCTION 001 7704 > BF external start 3-p. without current Active with voltage The second binary input will be used for the 3 pole trip signal from the Bucholz protection which must initiate breaker fail protection without current monitoring. It is assigned as shown above to 7704 >BF external start 3-p. without current. MARSHALLING 6133 MARSHALLING OF BINARY INPUT 3 Address Function Value 6134 BINARY INPUT 3 1st FUNCTION 001 0355 > CB aux. contact: 1 pole closed (parallel) Active with voltage The third binary input is assigned to monitor the circuit breaker auxiliary contact status. It must be connected such that when 1 or more CB poles are closed the input is high. It is assigned as shown above to 0355 >CB aux. contact: 1pole closed (parallel).
6.3.
The first of the 2 command relays in the 7SV600 is used for a re-trip to the monitored circuit breaker via the 2nd trip coil. MARSHALLING 6401 MARSHALLING OF COMMAND RELAY 1 Address Function 6402 COMMAND RELAY 1 1ST CONDITION 001 7710 Breaker failure Trip T1 (local Trip)
For this purpose the condition 7710 Breaker failure Trip T1 (local Trip) is assigned to the command relay 1 as shown. All the command relays have two separate contacts that may be connected according to the scheme requirement. The second of the 2 command relays in the 7SV600 is used for the Bus Trip signal that is routed to the circuit breakers connected to the busbar via the isolator replica of the busbar protection. MARSHALLING 6422 MARSHALLING OF COMMAND RELAY 2 Address Function 6423 COMMAND RELAY 2 1ST CONDITION 001 7711 Breaker failure Trip T2 (Busbar Trip) For this purpose the condition 7711 Breaker failure Trip T2 (Busbar Trip) is assigned to Command Relay 2 as shown.
7.1.
The following settings are applied in the subsection Power System Data, according to the information in Figure 1: PARAMETER SETTINGS A 1100 POWER SYSTEM DATA Address Function Value 1101 Rated system frequency fN 50 Hz 1105 Primary rated current 600 A 1134 Minimum trip command duration 0.15 s
The system frequency must be set accordingly, either 50 or 60 Hz. The primary rated current refers to the CT primary. It is not relevant to any protection functions, but only used for the fault recording. The minimum trip command duration must be set longer than the maximum time taken by the circuit breaker to trip following initiation of a trip command (time from start of trip command until circuit breaker auxiliary contacts indicate that the circuit breaker is open). In this case the circuit breaker requires 75 ms. By including a safety margin of 50 ms a setting of 150 ms is obtained.
7.2.
For the breaker fail protection the following settings must be applied. PARAMETER SETTINGS A 1200 BREAKER FAILURE PROTECTION Address Function Value 1201 Breaker Failure Protection ON/OFF on 1202 Current pick-up for Breaker Fail 0.16 I/In 1204 Local trip time delay (T1): 3pole 0.00 s 1205 Busbar trip delay (T2) 0.15 s 1206 Extended criterion for Drop Off Yes The breaker fail protection function is set to on with parameter address 1201. The current threshold for breaker failure protection must be carefully selected. For breaker fail there are two basic philosophies: a) Very secure breaker fail uses a current threshold that is greater than the maximum load. In this manner the Bus Trip command can only be issued if following a trip command and breaker failure the fault current flowing via the breaker is greater than full load current. This approach was often applied with analog protection relays. b) A very sensitive breaker fail uses a current threshold that is equal (marginally smaller) than the most sensitive protection operation that can issue a trip to the monitored circuit breaker. This approach is very secure as every protection operation will result in fault clearance by the breaker fail relay if the circuit breaker does not respond in time. With modern numerical relays this approach is preferred because of the higher security achieved with these devices. In this application the approach b) is followed. The most sensitive protection stage, apart from the Bucholz protection, is the transformer differential protection. Here a setting of 15% of nominal current is applied for transformer differential protection so that the setting for the breaker fail, with 20% margin, can be calculated as follows:
The second time delay for stage 2, 1205 Busbar trip delay (T2), must be calculated to ensure selectivity of the breaker fail protection:
Normal fault clearance time Protection operating time CB operating time I reset time of BF relay safety margin
100 ms 70 ms 30 ms 50 ms
time
The time T2 in the breaker fail relay is started with the trip command of the protection. If the circuit breaker opens in the normal manner following the trip command, the current flow via the breaker is interrupted. In this example the circuit breaker opening time is given as 70 ms. If a further 30 ms are considered for resetting of the current measurement of the 7SV600 then a drop off occurs 100 ms after the trip. As shown in Figure 3 a safety margin of 50 ms is applied so that the set time for T2 is 150 ms. The setting 1206 is used to enable the CB auxiliary contact monitoring for breaker fail protection initiation with St.woI (start without current). In this example, the Bucholz protection is initiating this input so that the setting of 1206 Extended criterion for Drop Off must be Yes.
7.3.
The End-Fault protection provides selective fault clearance of faults between the circuit breaker and the CT (refer to Figure 1). A fault at this position is not covered by the transformer protection, but is inside the busbar protection fault coverage. The trip of the busbar protection must therefore be connected in parallel with the transformer protection initiation of the breaker fail relay. The busbar protection trip will however not isolate the fault because there is still infeed from the LV side of the transformer. The End-Fault protection must provide the trip command to the LV side circuit breaker. For the end fault protection the following settings must be applied. PARAMETER SETTINGS A 1300 END-FAULT PROTECTION Address Function Value 1301 End-Fault Protection on 1302 Time delay for trip by End-Fault Protection 0.10 s
The End-Fault protection is applied so the parameter 1301 must be set to on. The time delay 1302 is started when during breaker fail initiate condition, the circuit breaker auxiliary contacts indicate that the CB is open but the current flow continues. When the time expires the End-Fault trip is issued. The time must allow for the current measurement reset time of the 7SV600 (30 ms) as well as timing difference between the CB primary and auxiliary contacts (20 ms) plus a safety margin of 50 ms. The applied setting is therefore 100 ms.
7.4. Setting Breaker Defective, Trip circuit seal in, Blocking and Monitoring functions
The breaker defective function is not used, as it requires further binary input information regarding the health state of the circuit breaker which is not available in this application. Therefore set as shown in the table below. PARAMETER SETTINGS A 1400 CIRCUIT BREAKER DEFECTIVE Address Function Value 1401 Handling of Binary Input CB defective no 1402 Time delay for trip by BI CB defective 0.00 s The lockout function can be used to seal in the breaker fail trip output. Thereby reclosure can be prevented until the lockout is reset. In this application the lockout function is not used, therefore apply the settings as shown below. PARAMETER SETTINGS A 1500 TRIP LOCKOUT Address Function 1501 Operating mode of Lockout function 1502 Reset of Lockout Value no via LED-quit button
The blocking of the breaker fail protection by monitoring of the binary inputs can be applied if dual channel initiation is applied or with phase segregated initiation. In this application simple three pole initiation is applied so the monitoring of the binary input plausibility is not possible. Therefore apply the following settings. PARAMETER SETTINGS A 1600 BLOCK WITH BINARY INPUT SUPERVISION Address Function Value 1601 Block BF-protection via supervision off 1602 Time delay for BF blocking by supervision 5.00 s 1603 Supervision of two-channel BF start no The current symmetry supervision can be used to alarm and/or trip the circuit breaker if a pole discrepancy condition is indicated by severe non-symmetry of the measured currents. In this example the symmetry monitoring will only be used to generate an alarm when the measured currents are not symmetrical. The following settings are applied. PARAMETER SETTINGS A 1700 SYMMETRY SUPERVISION Address Function Value 1702 Operating mode of current symmetry supervision On 1703 Symmetry threshold for current monitoring 0.50 I/In
Symmetry factor for current monitoring Time delay for current symmetry supervision Local Trip by current symmetry supervision
0.50 3s No
8. Conclusion
Although the 7SV600 is a very compact device, it provides adequate breaker fail protection with special features such as current or auxiliary contact monitoring depending on the initiation (Diff trip or Bucholz trip). End-Fault protection and re-tripping is also included in this application example.